Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 10:43:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 609.00 | 125.95 | 125.95 |
Net Site Energy | 609.00 | 125.95 | 125.95 |
Total Source Energy | 1367.19 | 282.76 | 282.76 |
Net Source Energy | 1367.19 | 282.76 | 282.76 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 269.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 87.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 339.43 | 269.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 269.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 2.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 87.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 62.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 25.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 269.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 87.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 62.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 25.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 25.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 30.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 11.11 | 55.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 70.20 | 55.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 30.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 11.11 | 55.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 70.20 | 55.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 339.433 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 339.433 | 100.00 |
Total On-Site and Utility Electric Sources | 339.433 | 100.00 |
Total Electricity End Uses | 339.433 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 62.00 |
Time Setpoint Not Met During Occupied Cooling | 1.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2476.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.9682 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.5521 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.9682 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.5521 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.8362 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-14:00 | 19-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 133568.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5937.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6119.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4162.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1754.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28009.22 | 133568.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 133568.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5937.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 6119.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1857.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1754.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 292.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 275.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 196.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 81.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 81.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1074.98 | 292.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 60.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 57.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 222.33 | 60.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 60.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 57.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 222.33 | 60.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.944984 |
ZONE2 FINE STORAGE DIRECT AIR | 1.89 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 2.47 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 2.47 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 99686.34 |
PSZ-OFFICE HEATING COIL | 24482.79 |
PSZ-FINE STORAGE HEATING COIL | 65241.56 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 99686.35 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.944984 | 0.944984 | 0.944984 | 0.944984 | 0.944984 | 0.944984 | 1.00 | 1.00 | 0.944984 |
PSZ-FINE STORAGE | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.89 | 1.00 | 1.00 | 1.89 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.944984 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.89 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.944984 | 1046.25 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.89 | 2027.08 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.944984 | 0.944984 | 0.944984 | 0.944984 | 15844.45 | 24482.79 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.89 | 1.89 | 1.89 | 1.25 | 39271.96 | 65241.56 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.944980 | 0.472492 | 0.629987 | 15844.45 | 7922.23 | 0.800980 | 0.800980 |
PSZ-FINE STORAGE COOLING COIL | 1.89 | 0.947190 | 1.26 | 39271.96 | 19635.98 | 0.762570 | 0.762570 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.968 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.042 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.552 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1650.627 | 6.968 | 129.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1650.627 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 11383.888 | 3.552 | 164.984 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11383.888 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2163 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.4974 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.4322 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.044 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.622 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.010 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.214 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4892 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.18741198E-13 | -0.13599760E-18 | 0.18147593E-18 | 0.0000000 |
2 | 1 | -5.2160601 | 0.51384690E-04 | -0.74050972E-04 | 0.35929797E-14 |
3 | 0 | 5.4323994 | 0.21628790 | 0.21641333 | |
4 | 2 | 0.53330648E-11 | 0.17872838E-15 | 0.22136589E-15 | 0.0000000 |
5 | 1 | -5.2159880 | 0.41449123E-04 | -0.32205733E-04 | 0.68736940E-11 |
6 | 0 | 5.7134214 | 0.49739196 | 0.49746561 | |
7 | 4 | 0.79186034E-12 | 0.10405078E-15 | -0.20960309E-14 | 0.11445272E-15 |
8 | 3 | -0.38819576E-03 | 0.30481201E-06 | -0.56344247E-04 | 0.15193845E-12 |
9 | 2 | 1.7477700 | 0.66393353E-02 | 1.1467116 | -0.74423695E-04 |
10 | 1 | -7.1178476 | 0.17160399 | -17.138090 | 0.33498210 |
11 | 0 | 5.6579463 | 0.10923685 | 16.278915 | |
12 | 4 | 0.65556131E-12 | 0.57298371E-15 | -0.14028959E-14 | 0.12439065E-15 |
13 | 3 | -0.34087882E-03 | 0.75102955E-06 | -0.49042705E-04 | 0.12583838E-12 |
14 | 2 | 1.6337693 | 0.17263784E-01 | 1.0601096 | -0.65347397E-04 |
15 | 1 | -7.2734424 | 0.46143774 | -16.581274 | 0.31301327 |
16 | 0 | 6.4190060 | 0.30028979 | 16.300205 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.0441747 | 2.0441747 | 2.0441747 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.14028959E-14 | 0.57298371E-15 | 0.65556131E-12 | 0.12439065E-15 |
85 | 3 | -0.49042705E-04 | 0.75102955E-06 | -0.34087882E-03 | 0.12583838E-12 |
86 | 2 | 1.0601096 | 0.17263784E-01 | 1.6337693 | -0.65347397E-04 |
87 | 1 | -16.581274 | 0.46143774 | -7.2734424 | 0.31301327 |
88 | 0 | 16.300205 | 0.30028979 | 6.4190060 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.362_SHGC_SOUTH_0.359 | 34 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.360 | ||
2 | NONRESWINDOW_U_0.362_SHGC_NORTH_0.359 | 35 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.360 | ||
3 | NONRESWINDOW_U_0.362_SHGC_EAST_0.359 | 36 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.360 | ||
4 | NONRESWINDOW_U_0.362_SHGC_WEST_0.359 | 37 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.360 | ||
5 | SKYLIGHT_U_0.5_SHGC_0.4 | 38 | 1 | VerySmooth | 2.843 | 2.843 | 1.000 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.555 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.63679E-002 | 0.27216 | 0.52074 | 0.52074 | 0.35900 | 0.14248 | 0.19174 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.63679E-002 | 0.27216 | 0.52074 | 0.52074 | 0.35900 | 0.14248 | 0.19174 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.63679E-002 | 0.27216 | 0.52074 | 0.52074 | 0.35900 | 0.14248 | 0.19174 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.63679E-002 | 0.27216 | 0.52074 | 0.52074 | 0.35900 | 0.14248 | 0.19174 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.31435 | 0.46556 | 0.46556 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.41263 | 0.18041 | 0.18041 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | CurtainWall | 2.775 | 0.408 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.553 | 0.552 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.8383E-005 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9059E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.6724E-005 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1833E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7716E-005 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2223E-004 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5724E-005 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5867E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7280E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.3162E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4265E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.7242E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6356E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7307E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3414E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4540E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8126E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7061E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1714E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9369E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.0355E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1840E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8792E-004 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6675E-005 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5223E-004 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8894E-005 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8442E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0962E-004 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0916E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3360E-005 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3392E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0724E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3939E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8837E-005 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5304E-004 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3587E-005 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.5445E-004 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9124E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9718E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6272E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.8173E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5921E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.2485E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7956E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3760E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4026E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7955E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4789E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8644E-004 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0204E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3822E-004 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3600E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2493E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4581E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3679E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4861E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4239E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.2287E-005 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5589E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.1342E-005 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6407E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0957E-005 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1133E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6508E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3970E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4655E-004 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2759E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7259E-004 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3502E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0531E-005 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5808E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1684E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2486E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0875E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.1378E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.7498E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1308E-004 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4765E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6286E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1734E-005 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.2443E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6901E-004 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8173E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0446E-004 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0750E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.0643E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3102E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8162E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8706E-005 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3001E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.4334E-005 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4627E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3836E-005 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3293E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0760E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8446E-004 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2755E-005 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5114E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7255E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4348E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9135E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4372E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7398E-005 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1825E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0364E-005 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.8487E-004 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.5512E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2943E-004 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8046E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1354E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5431E-005 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2422E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0886E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8931E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3569E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4148E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3007E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.8130E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0686E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8896E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4358E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1664E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0794E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1607E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5611E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9659E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3969E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1488E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0478E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9470E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3362E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7547E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.3452E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0493E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0664E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2423E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1711E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9330E-004 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7628E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1942E-004 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8026E-004 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3323E-004 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5103E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2222E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1080E-004 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9086E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1774E-004 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0571E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4732E-005 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1406E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1117E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0201E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1944E-004 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5535E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2893E-004 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5088E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6996E-005 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6682E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1095E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2472E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5391E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5556E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2541E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7809E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8558E-004 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9368E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5083E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1405E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5631E-004 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3914E-004 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6071E-004 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1341E-003 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5863E-004 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7513E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6080E-005 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3729E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0962E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1361E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0835E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4546E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5467E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7454E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0654E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4057E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.6663E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2538E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8389E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2566E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6772E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.4727E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0642E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5894E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6786E-004 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8459E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7528E-004 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7305E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6326E-004 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1099E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6000E-005 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5319E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1030E-003 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0683E-004 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2103E-003 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0232E-004 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2166E-003 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2559E-004 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2332E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0027E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0365E-003 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5420E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1244E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6592E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1866E-003 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6164E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2412E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4700E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1585E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0445E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1194E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8445E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6782E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4904E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7391E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8641E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0393E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6215E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9761E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8341E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5969E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6389E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7417E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5926E-004 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2822E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0694E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0853E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8014E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.3433E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5984E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7422E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1060E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2545E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0991E-004 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1971E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0080E-004 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0072E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4042E-004 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2266E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1357E-004 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2146E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9510E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1499E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5797E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9641E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9470E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2308E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1830E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2063E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8994E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9987E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8443E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2435E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9795E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7477E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6474E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9041E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9024E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6537E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6064E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6494E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3367E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7271E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1031E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8871E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1264E-003 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6297E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5265E-004 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5773E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7027E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7326E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5789E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0983E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.8919E-005 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8729E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.8172E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2535E-003 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2124E-004 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1930E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1325E-004 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0562E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7460E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.8124E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2072E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2311E-003 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7274E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1970E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1180E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3399E-004 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5471E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1321E-004 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6316E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4537E-004 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9165E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7207E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2995E-004 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7364E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2008E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0027E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8164E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0842E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5055E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0466E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4053E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4038E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0102E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0625E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5619E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5943E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7266E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3950E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1198E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3323E-004 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6008E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1313E-004 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3180E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4867E-004 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8546E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7182E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8575E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8112E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8206E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5080E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4543E-004 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9734E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4918E-004 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4996E-005 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3143E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6365E-004 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1960E-004 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3170E-004 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.9105E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3569E-004 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0613E-004 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0188E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3821E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7352E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2567E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4734E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0144E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0958E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3863E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4918E-005 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5252E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.7159E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.0390E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9947E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0951E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1409E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6505E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0389E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9465E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6273E-004 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.2706E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3123E-004 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5845E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3697E-004 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0702E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0177E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5496E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.5090E-003 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.4018E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.0575E-003 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.8807E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.6089E-003 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.4270E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5669E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.5086E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.6804E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.9150E-003 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.3567E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.0760E-003 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.5412E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.0218E-003 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.4572E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4523E-003 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 5.2106E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.6471E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.9172E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.8718E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5105E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.1176E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.2194E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.7466E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.2723E-003 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.6492E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.9488E-003 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.8730E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.4559E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1163E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.2193E-003 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.7466E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9435.21797 | 11322.26157 | 0.78749 | 0.94498 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 28.22133 | 8.81961E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 8592.38230 | 10310.85876 | 0.24454 | 0.29345 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20000 | 2.69032E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 24264.41366 | 29117.29639 | 1.57865 | 1.89438 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 23826.35577 | 28591.62693 | 0.57149 | 0.68579 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -4.20000 | 2.69032E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40000 | 8.82150E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 83071.95566 | 99686.34679 | 2.05902 | 2.47083 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 13946.74 | 0.94498 | 0.94498 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 9723.04 | 0.29345 | 0.29345 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 34580.67 | 1.89438 | 1.89438 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 30002.90 | 0.68579 | 0.68579 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94498 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.89438 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.47083 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 2.47083 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 99686.34121 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 99686.34679 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94498 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94498 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94498 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94498 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.94498 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.94498 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.89438 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.89438 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.89438 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.89438 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.89438 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.89438 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.94498 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.89438 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.94498 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.94498 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1046.24745 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.94498 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.94498 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.94498 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.94498 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.94498 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47249 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62999 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15844.45000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7922.22500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80098 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80098 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15844.45000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24482.79467 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 24482.79467 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.89438 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.89438 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2027.07719 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.89438 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.89438 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.89438 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.25029 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.89438 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.94719 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.26292 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 39271.96000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19635.98000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76257 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76257 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39271.96000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 65241.56355 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 65241.56355 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 15111.2 | 12.19 | 11.91 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 37800.7 | 11.90 | 11.63 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.1941978368 | 0.1696787999 | Pass | Pass | 1.2312923526 | 8.2857254362 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.3982998450 | 0.3599507944 | Pass | Pass | 0.1811242939 | 0.5356843437 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.1480388853E-005 | 3.2465659541E-005 | Pass | Pass | 4.4167680098E-002 | 4.7651182716E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7138.45 | 385.40 | 0.00 | 66.00 | 82.44 | 7672.31 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.406 | 0.432 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.210 | 0.216 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.466 | 0.497 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.362_SHGC_WEST_0.359 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.057 | 0.360 | 0.360 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.362_SHGC_WEST_0.359 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.057 | 0.360 | 0.360 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.362_SHGC_NORTH_0.359 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.057 | 0.360 | 0.360 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.362_SHGC_NORTH_0.359 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.057 | 0.360 | 0.360 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.5_SHGC_0.4 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 2.843 | 0.401 | 0.402 | 0.000 | 0.000 | CurtainWall | 2.775 | 0.408 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 3.466 | 0.478 | 0.476 | |||||||||||||||||
North Total or Average | 6.51 | 2.057 | 0.360 | 0.360 | |||||||||||||||||
Non-North Total or Average | 79.53 | 3.581 | 0.487 | 0.486 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.9682 | 236.88 | 1650.63 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 33.06 | 0.0000 | Y | 10.24 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 20.03 | 0.0000 | Y | 38.92 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.5521 | 3204.84 | 11383.89 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 17.72 | 0.0000 | Y | 37.87 |
Interior Lighting Total | 4.8362 | 4835.13 | 23383.49 | 87.03 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1650.63 | 478.68 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1650.63 | 165.06 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 42.59 | 42.59 | 0.99 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.55 | 63.07 | 50.97 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.55 | 49.79 | 10.20 | |
Exterior Lighting Total | 5520.82 | 62.16 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15844.45 | 12691.09 | 3153.36 | 0.80 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 39271.96 | 29947.62 | 9324.34 | 0.76 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 15111.2 | 12.19 | 11.91 | ||||
PSZ-FINE STORAGE COOLING COIL | 37800.7 | 11.90 | 11.63 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 99686.34 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 24482.79 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 65241.56 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 2.47 | 229.57 | 92.91 | 1.00 | 3.46 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.94 | 1046.25 | 1107.16 | 1.00 | 1.42 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.89 | 2027.08 | 1070.05 | 1.00 | 1.32 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9435.22 | 11322.26 | 47.80 | 0.787 | 0.945 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 23.90 | 23.90 | 0.00835 | 28.22 | 0.00882 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 24264.41 | 29117.30 | 20.90 | 1.579 | 1.894 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.70 | 26.70 | 0.00852 | 29.40 | 0.00882 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 0.00 | 30.10 | 0.00888 | 29.40 | 0.00882 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 8592.38 | 10310.86 | 43.53 | 0.245 | 0.293 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00736 | -4.20 | 0.00269 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 23826.36 | 28591.63 | 20.52 | 0.571 | 0.686 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 15.56 | 15.56 | 0.00602 | -4.20 | 0.00269 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 83071.96 | 99686.35 | 31.10 | 2.059 | 2.471 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10.00 | 10.00 | 0.00535 | -4.20 | 0.00269 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.94 | 0.94 | 0.29 | 0.29 | 0.9450 | 0.9450 | 0.9450 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.89 | 1.89 | 0.69 | 0.69 | 1.8944 | 1.8944 | 1.8944 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 99686.341 | 99686.341 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 99686.34 | 99686.34 | 2.470828 | 10.00 | 7.32 | 0.00534793 | 43.33 | 21.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 10.00 | 0.00534793 | 69.3416 | 99686.35 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 15844.450 | 12691.088 | 0.944980 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 7922.23 | 7423.35 | 0.629987 | 25.30 | 16.61 | 0.00839843 | 12.00 | 11.13 | 0.00800000 | 28.36 | 0.00881983 | 18.00 | 16.2360 | 23.90 | 0.00834724 | 44.5739 | 9428.78 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 24482.795 | 24482.795 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 24482.79 | 24482.79 | 0.944984 | 18.28 | 12.58 | 0.00685802 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 10.8240 | 21.10 | 0.00736388 | 46.6918 | 8592.38 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 39271.960 | 29947.619 | 1.894380 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 19635.98 | 18123.21 | 1.262920 | 28.19 | 17.76 | 0.00859022 | 12.00 | 11.13 | 0.00800000 | 29.40 | 0.00882150 | 18.34 | 33.6293 | 26.70 | 0.00852339 | 38.5214 | 24264.41 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 65241.564 | 65241.564 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 65241.56 | 65241.56 | 1.894381 | 11.13 | 7.76 | 0.00526992 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 22.4195 | 15.56 | 0.00601538 | 54.1253 | 23826.36 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 99686.341 | 99686.341 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 2.470828 | 2.93285032 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 99686.34 | 99686.34 | 1.0000 | 2.93285032 | 2.470828 | 10.00 | 7.32 | 0.00534793 | 23520.1 | 43.33 | 21.98 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99686.34 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 10.00 | 0.00534793 | 10.00 | 0.00534793 | 69.3416 | 99686.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15844.450 | 12691.088 | 0.944980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4523 | 1004.8586 | 1.1870 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.944984 | 1.12168747 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | Sensible | 7922.23 | 7423.35 | 1.0000 | 0.74778837 | 0.629987 | 25.30 | 16.61 | 0.00839843 | 46817.4 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7922.23 | 28.36 | 0.00881983 | 18.00 | 0.10228463 | 16.2360 | 23.90 | 0.00834724 | 23.90 | 0.00834724 | 44.5739 | 9428.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24482.795 | 24482.795 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.944984 | 1.12168747 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 24482.79 | 24482.79 | 1.0000 | 1.12168747 | 0.944984 | 18.28 | 12.58 | 0.00685802 | 35751.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24482.79 | -4.20 | 0.00269032 | -4.20 | 0.10228463 | 10.8240 | 21.01 | 0.00736388 | 21.10 | 0.00736388 | 46.6918 | 8592.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 39271.960 | 29947.619 | 1.894380 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8088 | 1004.8586 | 1.1870 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.894381 | 2.24861275 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 19635.98 | 18123.21 | 1.0000 | 1.49907440 | 1.262920 | 28.19 | 17.76 | 0.00859022 | 50257.6 | 12.00 | 11.13 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19635.98 | 29.40 | 0.00882150 | 18.34 | 0.42471127 | 33.6293 | 26.70 | 0.00852339 | 26.70 | 0.00852339 | 38.5214 | 24264.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 65241.564 | 65241.564 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.894381 | 2.24861275 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 65241.56 | 65241.56 | 1.0000 | 2.24861275 | 1.894381 | 11.13 | 7.76 | 0.00526992 | 24468.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 65241.56 | -4.20 | 0.00269032 | -4.20 | 0.42471127 | 22.4195 | 15.56 | 0.00601538 | 15.56 | 0.00601538 | 54.1253 | 23826.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 0.94 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.89 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2186.67 | 3098.50 | 1935.50 |
ZONE2 FINE STORAGE | 2769.17 | 3064.00 | 2304.50 |
ZONE3 BULK STORAGE | 2870.67 | 3142.00 | 2473.67 |
Facility | 2899.67 | 3243.83 | 2476.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 62.33 | 1.00 | 57.00 | 1.00 |
ZONE2 FINE STORAGE | 255.00 | 1.00 | 13.50 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 308.83 | 2.00 | 62.00 | 1.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.647 | 0.299 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.448 | 0.224 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.43 | 69.00 | 35277.63 | 0.000 | 0.117 | 0.000 | 0.055 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.43 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.43 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.29 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2329911.92 | 0.00 | 2329911.92 | 1769020.99 | 4098932.91 | 3225648.14 | 5716.49 | 2175.08 | 868.42 | 0.00 |
ZONE2 FINE STORAGE | 4780628.15 | 0.00 | 4780628.15 | 6389014.32 | 11169642.47 | 13393694.68 | 5728.82 | 2941.33 | 89.84 | 1.17 |
ZONE3 BULK STORAGE | 0.00 | 15911426.33 | 15911426.33 | 31317628.16 | 47229054.49 | 30805497.77 | 8448.69 | 47.00 | 264.31 | 4996.00 |
Total Facility | 7110540.08 | 15911426.33 | 23021966.41 | 39475663.47 | 62497629.88 | 47424840.58 | 8601.86 | 3015.33 | 1170.18 | 4996.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1780 | 0.0000 | 0.1780 | 0.0826 | 0.2606 | 0.1023 | 592.49 | 2175.08 | 868.42 |
ZONE2 FINE STORAGE | 0.3649 | 0.0000 | 0.3649 | 0.1829 | 0.5478 | 0.4247 | 606.00 | 2941.33 | 88.67 |
ZONE3 BULK STORAGE | 0.0000 | 0.5379 | 0.5379 | 1.1520 | 1.6899 | 0.9768 | 3467.53 | 26.83 | 141.64 |
Total Facility | 0.5429 | 0.5379 | 1.0808 | 1.4175 | 2.4983 | 1.5038 | 3477.86 | 2995.17 | 1046.34 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3282722.69 | 0.00 | 3282722.69 | 3225648.14 | 5713.60 | 0.00 | 3046.40 | 0.00 |
PSZ-FINE STORAGE | 6735484.17 | 0.00 | 6735484.17 | 13393694.68 | 5728.82 | 0.00 | 3031.17 | 1.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2508 | 0.0000 | 0.2508 | 0.1023 | 589.60 | 0.00 | 3046.40 |
PSZ-FINE STORAGE | 0.5141 | 0.0000 | 0.5141 | 0.4247 | 606.00 | 0.00 | 3030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2501.97 | 552.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 3005.34 | 25.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2561 | 0.4918 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6136 | 1.0472 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 446 |
Defaulted Fields | 391 |
Fields with Defaults | 1172 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 339.43 | 1550.86 | 22-JAN-12:40 | 28009.22 | 10-AUG-15:00 |
Electricity:Building | 223.59 | 1069.86 | 15-JAN-11:10 | 18906.49 | 16-DEC-16:00 |
Electricity:Zone:ZONE1 OFFICE | 39.41 | 520.87 | 01-JAN-00:10 | 2846.16 | 02-JAN-16:30 |
Electricity:SpaceType:GENERAL | 223.54 | 1069.86 | 15-JAN-11:10 | 18906.49 | 16-DEC-16:00 |
InteriorLights:Electricity | 87.03 | 599.99 | 15-JAN-11:10 | 8871.32 | 16-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.24 | 51.00 | 01-JAN-00:10 | 1011.11 | 02-JAN-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 87.03 | 599.99 | 15-JAN-11:10 | 8871.32 | 16-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 87.03 | 599.99 | 15-JAN-11:10 | 8871.32 | 16-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.24 | 51.00 | 01-JAN-00:10 | 1011.11 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 87.03 | 599.99 | 15-JAN-11:10 | 8871.32 | 16-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 38.92 | 299.97 | 01-JAN-00:10 | 3792.65 | 16-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 38.92 | 299.97 | 01-JAN-00:10 | 3792.65 | 16-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 38.92 | 299.97 | 01-JAN-00:10 | 3792.65 | 16-DEC-16:00 |
Electricity:Zone:ZONE3 BULK STORAGE | 145.26 | 249.02 | 15-JAN-11:10 | 13113.44 | 31-JUL-16:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 37.87 | 249.02 | 15-JAN-11:10 | 4078.94 | 16-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 37.87 | 249.02 | 15-JAN-11:10 | 4078.94 | 16-DEC-16:00 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 25.84 | 0.00 | 08-JAN-13:20 | 4162.37 | 10-AUG-16:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.05 | 0.00 | 01-JAN-00:10 | 2305.29 | 31-JUL-16:00 |
Ventilation (simple):Fans:Electricity | 0.05 | 0.00 | 01-JAN-00:10 | 2305.29 | 31-JUL-16:00 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.05 | 0.00 | 01-JAN-00:10 | 2305.29 | 31-JUL-16:00 |
ElectricityPurchased:Facility | 339.43 | 1550.86 | 22-JAN-12:40 | 28009.22 | 10-AUG-15:00 |
ElectricityPurchased:Plant | 339.43 | 1550.86 | 22-JAN-12:40 | 28009.22 | 10-AUG-15:00 |
Cogeneration:ElectricityPurchased | 339.43 | 1550.86 | 22-JAN-12:40 | 28009.22 | 10-AUG-15:00 |
General:Cogeneration:ElectricityPurchased | 339.43 | 1550.86 | 22-JAN-12:40 | 28009.22 | 10-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 339.43 | 1550.86 | 22-JAN-12:40 | 28009.22 | 10-AUG-15:00 |
ElectricityNet:Plant | 339.43 | 1550.86 | 22-JAN-12:40 | 28009.22 | 10-AUG-15:00 |
Cogeneration:ElectricityNet | 339.43 | 1550.86 | 22-JAN-12:40 | 28009.22 | 10-AUG-15:00 |
General:Cogeneration:ElectricityNet | 339.43 | 1550.86 | 22-JAN-12:40 | 28009.22 | 10-AUG-15:00 |
Electricity:HVAC | 27.95 | 0.00 | 08-JAN-13:20 | 7961.40 | 10-AUG-15:30 |
General:Fans:Electricity | 25.79 | 0.00 | 08-JAN-13:20 | 2470.79 | 18-FEB-18:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 2.15 | 0.00 | 01-JAN-00:10 | 6104.32 | 10-AUG-15:30 |
General:Cooling:Electricity | 2.15 | 0.00 | 01-JAN-00:10 | 6104.32 | 10-AUG-15:30 |
ExteriorLights:Electricity | 62.16 | 0.00 | 01-JAN-08:10 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 62.16 | 0.00 | 01-JAN-08:10 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 25.73 | 481.00 | 18-MAY-05:10 | 2334.70 | 13-FEB-13:00 |
WaterSystems:Electricity | 25.73 | 481.00 | 18-MAY-05:10 | 2334.70 | 13-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 25.73 | 481.00 | 18-MAY-05:10 | 2334.70 | 13-FEB-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 269.56 | 0.00 | 08-JAN-13:20 | 133568.34 | 19-FEB-07:10 |
NaturalGas:HVAC | 269.56 | 0.00 | 08-JAN-13:20 | 133568.34 | 19-FEB-07:10 |
Heating:NaturalGas | 269.56 | 0.00 | 08-JAN-13:20 | 133568.34 | 19-FEB-07:10 |
General:Heating:NaturalGas | 269.56 | 0.00 | 08-JAN-13:20 | 133568.34 | 19-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 429.56 | 0.00 | 08-JAN-13:20 | 208754.21 | 19-FEB-06:50 |
EnergyTransfer:Building | 220.68 | 0.00 | 08-JAN-13:20 | 104605.01 | 19-FEB-06:50 |
EnergyTransfer:Zone:ZONE1 OFFICE | 36.01 | 0.00 | 01-JAN-00:10 | 18194.08 | 09-JAN-06:10 |
Heating:EnergyTransfer | 190.49 | 0.00 | 08-JAN-13:20 | 104605.01 | 19-FEB-06:50 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 25.90 | 0.00 | 01-JAN-00:10 | 18194.08 | 09-JAN-06:10 |
General:Heating:EnergyTransfer | 190.49 | 0.00 | 08-JAN-13:20 | 104605.01 | 19-FEB-06:50 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 25.90 | 0.00 | 01-JAN-00:10 | 18194.08 | 09-JAN-06:10 |
Cooling:EnergyTransfer | 30.20 | 0.00 | 01-JAN-00:10 | 18782.29 | 10-AUG-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 10.11 | 0.00 | 01-JAN-00:10 | 7319.44 | 10-AUG-17:00 |
General:Cooling:EnergyTransfer | 30.20 | 0.00 | 01-JAN-00:10 | 18782.29 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 10.11 | 0.00 | 01-JAN-00:10 | 7319.44 | 10-AUG-17:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 81.68 | 0.00 | 01-JAN-00:40 | 29484.86 | 19-FEB-04:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 61.60 | 0.00 | 01-JAN-00:40 | 29484.86 | 19-FEB-04:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 61.60 | 0.00 | 01-JAN-00:40 | 29484.86 | 19-FEB-04:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 20.09 | 0.00 | 01-JAN-00:10 | 12327.29 | 23-JUL-17:50 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 20.09 | 0.00 | 01-JAN-00:10 | 12327.29 | 23-JUL-17:50 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 102.99 | 0.00 | 02-JAN-09:10 | 75560.32 | 19-FEB-07:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 102.99 | 0.00 | 02-JAN-09:10 | 75560.32 | 19-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 102.99 | 0.00 | 02-JAN-09:10 | 75560.32 | 19-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 208.87 | 0.00 | 08-JAN-13:20 | 104149.20 | 19-FEB-06:50 |
HeatingCoils:EnergyTransfer | 199.07 | 0.00 | 08-JAN-13:20 | 104149.20 | 19-FEB-06:50 |
CoolingCoils:EnergyTransfer | 9.80 | 0.00 | 01-JAN-00:10 | 25809.13 | 10-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 25.896 | -10.114 | 0.000 | 0.000 | 10.110 | 10.244 | 29.165 | 9.376 | 0.000 | 0.161 | 0.001 | 0.000 | -6.039 | 0.000 | -20.386 | -48.413 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 61.598 | -20.086 | 0.000 | 0.000 | 27.118 | 38.918 | 0.000 | 27.091 | 0.000 | 0.212 | 0.002 | 0.000 | -10.911 | 0.000 | -57.129 | -66.812 |
ZONE3 BULK STORAGE | 102.991 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 66.292 | 37.868 | 107.344 | 368.957 | 0.000 | 3.122 | 0.000 | 0.000 | -103.594 | 0.000 | -278.980 | -304.000 |
Total Facility | 102.991 | 0.000 | 87.494 | -30.199 | 0.000 | 0.000 | 103.520 | 87.031 | 136.508 | 405.424 | 0.000 | 3.495 | 0.003 | 0.000 | -120.544 | 0.000 | -356.494 | -419.225 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 15-AUG-05:03 | 0.00 | 0.00 | 0.00 | -18421.27 | 0.00 | 0.00 | 90.96 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 18638.78 | 0.00 | -376.34 | 0.00 | -533.63 | 0.00 |
ZONE2 FINE STORAGE | 10-AUG-17:10 | 0.00 | 0.00 | 0.00 | -34079.54 | 0.00 | 0.00 | 0.00 | 415.77 | 0.00 | 1671.46 | 0.00 | 834.17 | 31158.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-17:10 | 0.00 | 0.00 | 0.00 | -34079.54 | 0.00 | 0.00 | 0.00 | 951.05 | 2519.91 | 68332.92 | 0.00 | 32328.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -70052.39 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 30-JAN-06:32 | 0.00 | 0.00 | 25900.78 | 0.00 | 0.00 | 0.00 | 136.26 | 302.02 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -348.52 | 0.00 | -1544.74 | -24996.30 |
ZONE2 FINE STORAGE | 19-FEB-04:42 | 0.00 | 0.00 | 66538.42 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1229.24 | 0.00 | -5636.41 | -59972.75 |
ZONE3 BULK STORAGE | 19-FEB-07:00 | 75559.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8811.30 | 0.00 | -36781.55 | -30464.83 |
Total Facility | 19-FEB-06:42 | 75375.59 | 0.00 | 72198.02 | 0.00 | 0.00 | 0.00 | 0.00 | 849.01 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16708.08 | 0.00 | -45606.29 | -86578.12 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9450 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9450 | 0.1082 | 1.0000 | Not calculated | 0.1023 | 0.1082 | ||
PSZ-FINE STORAGE | 1.8944 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.8944 | 0.2242 | 1.0000 | Not calculated | 0.4247 | 0.2242 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9450 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9450 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1082 | ||
PSZ-FINE STORAGE | 1.8944 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.8944 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2242 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9450 | 0.9450 | 0.9450 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8944 | 1.8944 | 1.8944 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9450 | 0.9450 | 0.9450 | 0.9450 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.8944 | 1.8944 | 1.8944 | 1.8944 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9450 | 0.9450 | 0.9450 | No | 0.1023 | 0.3486 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8944 | 1.8944 | 1.8944 | No | 0.4247 | 0.6193 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9450 | 0.9450 | 0.9450 | 0.9450 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.8944 | 1.8944 | 1.8944 | 1.8944 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 62.00 |
Number of hours cooling loads not met | 1.00 |
Number of hours not met | 63.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 269.56 | 133568.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2.15 | 6104.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 87.03 | 8871.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 62.16 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.05 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 25.79 | 2470.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 25.73 | 2334.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 339.43 |
Natural Gas | 0.00 | 269.56 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 609.00 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 18.00 |
Space Heating | 0.00 |
Space Cooling | 0.45 |
Fans (All) | 5.34 |
Service Water Heating | 5.32 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 70.20 |
Subtotal | 70.20 |
Natural Gas [MJ/m2] | |
Space Heating | 55.75 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 55.75 |
Subtotal | 55.75 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.29 |
Space Heating | 44.26 |
Space Cooling | 0.35 |
Fans (All) | 4.24 |
Service Water Heating | 4.23 |
Receptacle Equipment | 22.42 |
Miscellaneous | 10.21 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8707.33 | 52.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8623.00 | 137.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8543.50 | 216.50 | 0.00 | 0.00 | 0.00 |
Min | 8543.50 | 52.67 | 0.00 | 0.00 | 0.00 |
Max | 8707.33 | 216.50 | 0.00 | 0.00 | 0.00 |
Average | 8624.61 | 135.39 | 0.00 | 0.00 | 0.00 |
Sum | 25873.83 | 406.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 79995.50 | 2723.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 182391.83 | 8801.17 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 182391.83 | 8801.17 | 0.00 | 0.00 | 0.00 |
Average | 98471.44 | 3841.56 | 0.00 | 0.00 | 0.00 |
Sum | 295414.33 | 11524.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8689.17 | 70.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8476.33 | 283.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8453.00 | 307.00 | 0.00 | 0.00 | 0.00 |
Min | 8453.00 | 70.83 | 0.00 | 0.00 | 0.00 |
Max | 8689.17 | 307.00 | 0.00 | 0.00 | 0.00 |
Average | 8539.50 | 220.50 | 0.00 | 0.00 | 0.00 |
Sum | 25618.50 | 661.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 76960.00 | 5759.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 179050.83 | 12142.17 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 179050.83 | 12142.17 | 0.00 | 0.00 | 0.00 |
Average | 96345.94 | 5967.06 | 0.00 | 0.00 | 0.00 |
Sum | 289037.83 | 17901.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 | 4.99 | 0.497161E+09 | 603.25 | 24-JAN-08:09 | 5.10 | 4.18 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 | 6.66 | 0.458324E+09 | 685.39 | 27-FEB-16:10 | 19.32 | 12.38 |
March | 3032913.58 | 222.82 | 25-MAR-14:30 | 11.40 | 3.76 | 0.539698E+09 | 717.73 | 18-MAR-15:00 | 11.40 | 3.76 |
April | 82443869.90 | 2467.13 | 27-APR-16:00 | 27.20 | 16.90 | 0.520015E+09 | 768.98 | 27-APR-15:00 | 27.20 | 16.90 |
May | 0.504498E+09 | 3577.81 | 15-MAY-16:00 | 23.90 | 12.85 | 0.604366E+09 | 769.00 | 06-MAY-13:09 | 23.90 | 12.85 |
June | 0.140802E+10 | 5232.67 | 28-JUN-16:00 | 26.10 | 16.29 | 0.642627E+09 | 768.98 | 21-JUN-12:50 | 26.10 | 16.29 |
July | 0.294871E+10 | 17418.26 | 24-JUL-05:02 | 15.87 | 13.15 | 0.632764E+09 | 769.00 | 15-JUL-13:00 | 15.87 | 13.15 |
August | 0.352869E+10 | 18424.47 | 15-AUG-05:03 | 13.05 | 11.44 | 0.684165E+09 | 769.01 | 29-AUG-09:09 | 23.27 | 17.82 |
September | 0.152318E+10 | 5109.11 | 14-SEP-16:00 | 24.40 | 17.04 | 0.618950E+09 | 769.00 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.114224E+09 | 2106.38 | 04-OCT-15:50 | 21.20 | 11.42 | 0.528709E+09 | 768.96 | 04-OCT-15:00 | 21.10 | 11.40 |
November | 1027972.55 | 155.42 | 06-NOV-15:10 | 11.10 | 10.26 | 0.480087E+09 | 768.97 | 04-NOV-15:39 | 11.10 | 10.26 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.40 | 3.48 | 0.497181E+09 | 603.25 | 30-DEC-08:09 | 4.32 | 4.10 |
Annual Sum or Average | 0.101138E+11 | 0.670405E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.458324E+09 | 603.25 | 4.32 | 3.76 | ||
Maximum of Months | 0.352869E+10 | 18424.47 | 27.20 | 17.04 | 0.684165E+09 | 769.01 | 27.20 | 17.84 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.320917E+09 | 3897.12 | 20-JAN-13:20 | 6.70 | 4.72 | 0.651172E+09 | 896.61 | 11-JAN-14:30 | 6.70 | 4.72 |
February | 0.757264E+09 | 5816.84 | 18-FEB-11:05 | 1.88 | -0.4 | 0.622231E+09 | 1193.97 | 27-FEB-15:39 | 19.60 | 12.34 |
March | 0.175128E+10 | 4567.10 | 24-MAR-08:25 | 4.45 | -0.5 | 0.779187E+09 | 1251.68 | 18-MAR-15:00 | 4.45 | -0.5 |
April | 0.168531E+10 | 4057.86 | 18-APR-10:00 | 6.10 | 4.31 | 0.850929E+09 | 1822.84 | 27-APR-15:39 | 27.20 | 17.03 |
May | 0.209403E+10 | 4897.57 | 18-MAY-08:20 | 6.47 | 5.77 | 0.117891E+10 | 2021.93 | 15-MAY-15:00 | 6.47 | 5.77 |
June | 0.193289E+10 | 4674.52 | 29-JUN-07:05 | 12.20 | 11.29 | 0.141589E+10 | 2246.80 | 28-JUN-14:09 | 12.20 | 11.29 |
July | 0.269635E+10 | 32045.54 | 31-JUL-17:12 | 27.77 | 18.62 | 0.161860E+10 | 2246.88 | 31-JUL-12:50 | 27.77 | 18.62 |
August | 0.319527E+10 | 34080.93 | 10-AUG-17:10 | 31.62 | 18.84 | 0.178356E+10 | 2246.89 | 10-AUG-12:39 | 31.62 | 18.84 |
September | 0.210147E+10 | 5194.01 | 16-SEP-08:20 | 11.10 | 11.01 | 0.135377E+10 | 2246.80 | 14-SEP-15:09 | 11.10 | 11.01 |
October | 0.172587E+10 | 4358.26 | 12-OCT-07:10 | 6.38 | 5.17 | 0.870912E+09 | 1707.91 | 04-OCT-15:09 | 6.38 | 5.17 |
November | 0.116155E+10 | 3719.46 | 10-NOV-10:00 | 6.70 | 5.65 | 0.667852E+09 | 1338.05 | 04-NOV-14:50 | 6.70 | 5.65 |
December | 0.663122E+09 | 4440.27 | 30-DEC-09:20 | 4.47 | 4.03 | 0.653986E+09 | 902.84 | 02-DEC-13:00 | 4.47 | 4.03 |
Annual Sum or Average | 0.200853E+11 | 0.124470E+11 | ||||||||
Minimum of Months | 0.320917E+09 | 3719.46 | 1.88 | -0.5 | 0.622231E+09 | 896.61 | 4.45 | -0.5 | ||
Maximum of Months | 0.319527E+10 | 34080.93 | 31.62 | 18.84 | 0.178356E+10 | 2246.89 | 31.62 | 18.84 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 | 4.99 | 0.696064E+09 | 1213.19 | 11-JAN-15:09 | 14.40 | 10.49 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 7.00 | 6.66 | 0.760489E+09 | 1864.72 | 27-FEB-15:50 | 19.50 | 12.39 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.92 | 4.69 | 0.121737E+10 | 2159.34 | 18-MAR-15:39 | 20.40 | 10.40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 | 0.159947E+10 | 3564.72 | 29-APR-15:20 | 21.47 | 14.98 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.258650E+10 | 4454.37 | 15-MAY-15:20 | 23.50 | 12.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.29 | 0.317766E+10 | 5363.27 | 28-JUN-15:30 | 26.10 | 15.92 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.22 | 0.380629E+10 | 6273.42 | 31-JUL-14:30 | 28.30 | 18.91 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.75 | 0.431459E+10 | 6726.93 | 10-AUG-15:00 | 31.20 | 18.74 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.311613E+10 | 5222.07 | 14-SEP-15:09 | 23.98 | 16.97 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.42 | 0.173115E+10 | 3529.17 | 04-OCT-15:09 | 21.60 | 11.48 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 | 8.04 | 0.964476E+09 | 2314.88 | 04-NOV-15:09 | 20.92 | 15.94 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 4.40 | 3.48 | 0.738060E+09 | 1225.20 | 05-DEC-14:30 | 10.30 | 6.71 |
Annual Sum or Average | 0.00 | 0.247082E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.696064E+09 | 1213.19 | 10.30 | 6.71 | ||
Maximum of Months | 0.00 | 0.00 | 17.17 | 13.75 | 0.431459E+10 | 6726.93 | 31.20 | 18.91 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.544101E+10 | 25900.92 | 30-JAN-06:32 | 5.77 |
February | 0.432047E+10 | 25890.91 | 16-FEB-06:32 | 2.80 |
March | 0.357590E+10 | 25058.55 | 24-MAR-05:12 | 2.43 |
April | 0.210407E+10 | 24954.03 | 11-APR-05:12 | 5.60 |
May | 0.542703E+09 | 24721.06 | 19-MAY-05:01 | 7.88 |
June | 0.194944E+09 | 24120.41 | 15-JUN-05:02 | 8.98 |
July | 65279023.35 | 1243.03 | 25-JUL-06:10 | 13.98 |
August | 66107073.38 | 1310.95 | 01-AUG-06:10 | 11.32 |
September | 0.146188E+09 | 24126.57 | 28-SEP-05:02 | 8.30 |
October | 0.153380E+10 | 24897.16 | 30-OCT-05:12 | 7.20 |
November | 0.330068E+10 | 25010.20 | 13-NOV-06:12 | 1.70 |
December | 0.460461E+10 | 25105.72 | 26-DEC-06:12 | -1.0 |
Annual Sum or Average | 0.258958E+11 | |||
Minimum of Months | 65279023.35 | 1243.03 | -1.0 | |
Maximum of Months | 0.544101E+10 | 25900.92 | 13.98 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172624E+11 | 66351.39 | 15-JAN-05:23 | -2.5 |
February | 0.125053E+11 | 66538.32 | 19-FEB-04:42 | -5.5 |
March | 0.633914E+10 | 66005.98 | 06-MAR-06:01 | 6.70 |
April | 0.191319E+10 | 64328.31 | 12-APR-05:01 | 3.80 |
May | 91104117.42 | 1106.85 | 05-MAY-16:00 | 25.00 |
June | 67801844.73 | 842.60 | 13-JUN-07:00 | 11.70 |
July | 63408998.22 | 830.11 | 28-JUL-07:00 | 15.60 |
August | 75195797.43 | 912.50 | 31-AUG-07:00 | 14.00 |
September | 67038252.84 | 867.37 | 27-SEP-07:00 | 8.90 |
October | 0.889923E+09 | 31800.11 | 16-OCT-05:38 | 6.87 |
November | 0.768612E+10 | 65993.33 | 30-NOV-06:01 | 5.60 |
December | 0.146378E+11 | 66033.62 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.615984E+11 | |||
Minimum of Months | 63408998.22 | 830.11 | -5.5 | |
Maximum of Months | 0.172624E+11 | 66538.32 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.410275E+11 | 54525.43 | 15-JAN-05:00 | -2.8 |
February | 0.268238E+11 | 75560.32 | 19-FEB-07:00 | -5.0 |
March | 0.142573E+09 | 7503.49 | 05-MAR-06:40 | 2.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.563163E+10 | 27921.93 | 29-NOV-21:00 | 5.00 |
December | 0.293656E+11 | 41201.66 | 25-DEC-01:53 | 1.10 |
Annual Sum or Average | 0.102991E+12 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.410275E+11 | 75560.32 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.946325E+09 | 1011.11 | 02-JAN-16:30 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.824035E+09 | 995.08 | 04-FEB-16:00 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.903616E+09 | 983.23 | 22-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.791147E+09 | 962.51 | 03-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.793180E+09 | 924.48 | 17-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.794853E+09 | 911.58 | 29-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.785272E+09 | 959.60 | 12-JUL-08:30 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.854523E+09 | 951.16 | 02-AUG-07:30 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.809108E+09 | 984.35 | 25-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.872365E+09 | 1009.33 | 31-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.906778E+09 | 1011.11 | 06-NOV-16:49 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.962841E+09 | 1011.11 | 01-DEC-16:19 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.102440E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.785272E+09 | 911.58 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.962841E+09 | 1011.11 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.369907E+10 | 3771.48 | 13-JAN-15:00 | 0.00 | 0.00 |
February | 0.320261E+10 | 3681.65 | 06-FEB-15:00 | 0.00 | 0.00 |
March | 0.343892E+10 | 3614.88 | 14-MAR-08:09 | 0.00 | 0.00 |
April | 0.293345E+10 | 3439.58 | 19-APR-08:09 | 0.00 | 0.00 |
May | 0.283527E+10 | 3429.43 | 04-MAY-08:09 | 0.00 | 0.00 |
June | 0.282564E+10 | 3265.74 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.291407E+10 | 3584.17 | 12-JUL-08:09 | 0.00 | 0.00 |
August | 0.320475E+10 | 3471.59 | 23-AUG-08:09 | 0.00 | 0.00 |
September | 0.312593E+10 | 3546.11 | 21-SEP-08:09 | 0.00 | 0.00 |
October | 0.345421E+10 | 3649.20 | 31-OCT-08:09 | 0.00 | 0.00 |
November | 0.351754E+10 | 3781.76 | 30-NOV-15:00 | 0.00 | 0.00 |
December | 0.376659E+10 | 3792.65 | 16-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389181E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.282564E+10 | 3265.74 | 0.00 | 0.00 | |
Maximum of Months | 0.376659E+10 | 3792.65 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.372827E+10 | 4022.25 | 13-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.311968E+10 | 3757.17 | 06-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.323229E+10 | 3447.56 | 02-MAR-15:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.281831E+10 | 3074.85 | 03-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.282350E+10 | 2803.20 | 06-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.274671E+10 | 2429.78 | 22-JUN-06:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.278912E+10 | 3165.84 | 12-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.298910E+10 | 2981.66 | 28-AUG-07:30 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.295435E+10 | 3361.18 | 21-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.327993E+10 | 3710.44 | 31-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.348490E+10 | 4049.09 | 30-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.390227E+10 | 4078.94 | 16-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.378684E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.274671E+10 | 2429.78 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.390227E+10 | 4078.94 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.946325E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259880E+10 |
February | 0.127628E+10 | 0.824035E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218820E+10 |
March | 0.149825E+10 | 0.903616E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209780E+10 |
April | 0.138726E+10 | 0.791147E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11314253.34 | 0.170297E+10 |
May | 0.144276E+10 | 0.793180E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 850119.04 | 0.156295E+10 |
June | 0.144276E+10 | 0.794853E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6594328.99 | 0.132196E+10 |
July | 0.138726E+10 | 0.785272E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38147653.96 | 0.103644E+10 |
August | 0.149825E+10 | 0.854523E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102942E+09 | 0.971110E+09 |
September | 0.138726E+10 | 0.809108E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1385981.40 | 0.958255E+09 |
October | 0.138726E+10 | 0.872365E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162888E+10 |
November | 0.133177E+10 | 0.906778E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202459E+10 |
December | 0.138726E+10 | 0.962841E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229371E+10 |
Annual Sum or Average | 0.168137E+11 | 0.102440E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161234E+09 | 0.203857E+11 |
Minimum of Months | 0.127628E+10 | 0.785272E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958255E+09 |
Maximum of Months | 0.149825E+10 | 0.962841E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102942E+09 | 0.259880E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.369907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730493E+10 |
February | 0.300332E+10 | 0.320261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332629.64 | 0.611339E+10 |
March | 0.352563E+10 | 0.343892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2774562.55 | 0.520147E+10 |
April | 0.326447E+10 | 0.293345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90680155.04 | 0.451498E+10 |
May | 0.339505E+10 | 0.283527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509849.90 | 0.462400E+10 |
June | 0.339505E+10 | 0.282564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433934E+10 |
July | 0.326447E+10 | 0.291407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29507014.57 | 0.410343E+10 |
August | 0.352563E+10 | 0.320475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87834951.66 | 0.375911E+10 |
September | 0.326447E+10 | 0.312593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248126E+10 |
October | 0.326447E+10 | 0.345421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394471E+10 |
November | 0.313390E+10 | 0.351754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178901.10 | 0.482164E+10 |
December | 0.326447E+10 | 0.376659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592061E+10 |
Annual Sum or Average | 0.395654E+11 | 0.389181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211818E+09 | 0.571289E+11 |
Minimum of Months | 0.300332E+10 | 0.282564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248126E+10 |
Maximum of Months | 0.352563E+10 | 0.376659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90680155.04 | 0.730493E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.372827E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89017608.37 | 0.168965E+11 |
February | 0.690763E+10 | 0.311968E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332271E+09 | 0.144825E+11 |
March | 0.810895E+10 | 0.323229E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253248E+09 | 0.138430E+11 |
April | 0.750829E+10 | 0.281831E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.887105E+09 | 0.153602E+11 |
May | 0.780862E+10 | 0.282350E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31372869.71 | 0.202163E+11 |
June | 0.780862E+10 | 0.274671E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8896.64 | 0.193199E+11 |
July | 0.750829E+10 | 0.278912E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10373520.07 | 0.191640E+11 |
August | 0.810895E+10 | 0.298910E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136863E+09 | 0.188514E+11 |
September | 0.750829E+10 | 0.295435E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82899.60 | 0.117825E+11 |
October | 0.750829E+10 | 0.327993E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 415536.34 | 0.140673E+11 |
November | 0.720796E+10 | 0.348490E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114598E+09 | 0.110177E+11 |
December | 0.750829E+10 | 0.390227E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47385123.91 | 0.123114E+11 |
Annual Sum or Average | 0.910005E+11 | 0.378684E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190274E+10 | 0.187313E+12 |
Minimum of Months | 0.690763E+10 | 0.274671E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8896.64 | 0.110177E+11 |
Maximum of Months | 0.810895E+10 | 0.390227E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.887105E+09 | 0.202163E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1011.11 | 02-JAN-16:30 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 6019.79 | 06-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 995.08 | 04-FEB-16:00 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6268.74 | 13-FEB-18:00 |
March | 1680.92 | 01-MAR-08:09 | 983.23 | 22-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6222.22 | 24-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 962.51 | 03-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 809.89 | 27-APR-16:10 | 5133.95 | 19-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 924.48 | 17-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.85 | 05-MAY-16:10 | 4536.91 | 24-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 911.58 | 29-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 702.13 | 28-JUN-17:00 | 3592.07 | 14-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 959.60 | 12-JUL-08:30 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1314.35 | 24-JUL-16:10 | 2930.59 | 12-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 951.16 | 02-AUG-07:30 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1877.52 | 10-AUG-17:00 | 3427.42 | 01-AUG-07:00 |
September | 1680.92 | 01-SEP-07:10 | 984.35 | 25-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.77 | 14-SEP-17:00 | 3260.69 | 27-SEP-07:00 |
October | 1680.92 | 02-OCT-07:10 | 1009.33 | 31-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4336.07 | 31-OCT-17:00 |
November | 1680.92 | 01-NOV-07:10 | 1011.11 | 06-NOV-16:49 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6037.99 | 29-NOV-18:00 |
December | 1680.92 | 01-DEC-08:09 | 1011.11 | 01-DEC-16:19 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 6200.60 | 26-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 911.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2930.59 | |||||
Maximum of Months | 1680.92 | 1011.11 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1877.52 | 6268.74 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3771.48 | 13-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10097.99 | 28-JAN-08:00 |
February | 3955.50 | 01-FEB-08:09 | 3681.65 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.11 | 27-FEB-15:00 | 8753.23 | 13-FEB-08:00 |
March | 3955.50 | 01-MAR-08:09 | 3614.88 | 14-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.59 | 18-MAR-16:00 | 7982.38 | 24-MAR-06:10 |
April | 3955.50 | 01-APR-07:10 | 3439.58 | 19-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3409.03 | 01-APR-16:00 | 6717.18 | 08-APR-07:00 |
May | 3955.50 | 01-MAY-07:10 | 3429.43 | 04-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.21 | 05-MAY-16:00 | 6990.12 | 17-MAY-19:00 |
June | 3955.50 | 01-JUN-07:10 | 3265.74 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 7329.55 | 13-JUN-03:00 |
July | 3955.50 | 01-JUL-07:10 | 3584.17 | 12-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1015.15 | 24-JUL-15:10 | 4651.27 | 28-JUL-07:00 |
August | 3955.50 | 01-AUG-07:10 | 3471.59 | 23-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1750.10 | 08-AUG-17:00 | 7086.42 | 11-AUG-04:00 |
September | 3955.50 | 01-SEP-07:10 | 3546.11 | 21-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 4647.99 | 26-SEP-16:00 |
October | 3955.50 | 02-OCT-07:10 | 3649.20 | 31-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 6019.20 | 31-OCT-20:00 |
November | 3955.50 | 01-NOV-07:10 | 3781.76 | 30-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.92 | 04-NOV-15:10 | 9471.90 | 29-NOV-18:00 |
December | 3955.50 | 01-DEC-08:09 | 3792.65 | 16-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 7013.79 | 22-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3265.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4647.99 | ||||
Maximum of Months | 3955.50 | 3792.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3409.03 | 10097.99 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 4022.25 | 13-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6372.02 | 11-JAN-14:00 | 19763.72 | 14-JAN-19:53 |
February | 9097.65 | 01-FEB-08:09 | 3757.17 | 06-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4443.44 | 24-FEB-04:00 | 24892.66 | 13-FEB-11:00 |
March | 9097.65 | 01-MAR-08:09 | 3447.56 | 02-MAR-15:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8131.73 | 18-MAR-16:00 | 23262.83 | 22-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 3074.85 | 03-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23179.07 | 01-APR-16:00 | 20301.26 | 18-APR-16:00 |
May | 9097.65 | 01-MAY-07:10 | 2803.20 | 06-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1676.82 | 05-MAY-16:00 | 28176.23 | 10-MAY-15:00 |
June | 9097.65 | 01-JUN-07:10 | 2429.78 | 22-JUN-06:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 20-JUN-17:00 | 29151.14 | 13-JUN-10:00 |
July | 9097.65 | 01-JUL-07:10 | 3165.84 | 12-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1284.85 | 24-JUL-15:00 | 20469.13 | 03-JUL-16:00 |
August | 9097.65 | 01-AUG-07:10 | 2981.66 | 28-AUG-07:30 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3698.17 | 29-AUG-18:00 | 28785.88 | 11-AUG-04:00 |
September | 9097.65 | 01-SEP-07:10 | 3361.18 | 21-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.11 | 22-SEP-15:50 | 18333.10 | 26-SEP-15:40 |
October | 9097.65 | 02-OCT-07:10 | 3710.44 | 31-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.98 | 08-OCT-16:00 | 15521.14 | 14-OCT-11:00 |
November | 9097.65 | 01-NOV-07:10 | 4049.09 | 30-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5596.42 | 27-NOV-02:55 | 18012.46 | 29-NOV-17:00 |
December | 9097.65 | 01-DEC-08:09 | 4078.94 | 16-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7026.76 | 14-DEC-12:00 | 25370.46 | 26-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2429.78 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 15521.14 | |||||
Maximum of Months | 9097.65 | 4078.94 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 23179.07 | 29151.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 859.46 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 101.99 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.31 |
March | 222.82 | 25-MAR-14:30 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.50 |
April | 2467.13 | 27-APR-16:00 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 280.23 | 0.00 |
May | 3577.81 | 15-MAY-16:00 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 5232.67 | 28-JUN-16:00 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 204.01 | 0.00 |
July | 17418.26 | 24-JUL-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.80 |
August | 18424.47 | 15-AUG-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.63 |
September | 5109.11 | 14-SEP-16:00 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 32.01 | 0.00 |
October | 2106.38 | 04-OCT-15:50 | 1680.92 | 641.63 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.61 |
November | 155.42 | 06-NOV-15:10 | 1680.92 | 950.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 638.82 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 101.99 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 101.99 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18424.47 | 1680.92 | 950.42 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 280.23 | 859.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3897.12 | 20-JAN-13:20 | 3955.50 | 3521.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.70 |
February | 5816.84 | 18-FEB-11:05 | 7911.00 | 4664.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1579.57 |
March | 4567.10 | 24-MAR-08:25 | 7911.00 | 6884.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3019.36 |
April | 4057.86 | 18-APR-10:00 | 3955.50 | 2224.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 904.84 |
May | 4897.57 | 18-MAY-08:20 | 3955.50 | 2919.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2179.42 |
June | 4674.52 | 29-JUN-07:05 | 7911.00 | 5920.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2661.56 |
July | 32045.54 | 31-JUL-17:12 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.83 | 0.00 |
August | 34080.93 | 10-AUG-17:10 | 0.00 | 1663.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 834.17 | 0.00 |
September | 5194.01 | 16-SEP-08:20 | 3955.50 | 3302.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.34 |
October | 4358.26 | 12-OCT-07:10 | 3955.50 | 3187.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2333.38 |
November | 3719.46 | 10-NOV-10:00 | 3955.50 | 3145.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 686.30 |
December | 4440.27 | 30-DEC-09:20 | 3955.50 | 3601.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3719.46 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34080.93 | 7911.00 | 6884.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 834.17 | 3019.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1494.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8984.93 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 996.09 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3479.16 |
March | 0.00 | 01-MAR-00:05 | 0.00 | 996.09 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6362.72 |
April | 0.00 | 01-APR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4548.13 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12170.60 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3916.93 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5496.52 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7617.05 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8468.04 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3875.30 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 996.09 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5488.25 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 996.09 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3728.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3479.16 | |
Maximum of Months | 0.00 | 0.00 | 1494.14 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12170.60 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.320746E+11 | 27652.72 | 18-JAN-16:49 | 0.891334E+11 | 108479.48 | 09-JAN-06:10 |
February | 0.277982E+11 | 21924.81 | 15-FEB-15:00 | 0.608797E+11 | 133568.34 | 19-FEB-07:10 |
March | 0.296311E+11 | 21461.74 | 14-MAR-08:09 | 0.157852E+11 | 43255.06 | 24-MAR-06:10 |
April | 0.261302E+11 | 20720.30 | 03-APR-08:09 | 0.578284E+10 | 35014.42 | 12-APR-05:10 |
May | 0.259542E+11 | 20626.11 | 05-MAY-14:30 | 0.604465E+09 | 11349.23 | 18-MAY-05:10 |
June | 0.253454E+11 | 20638.50 | 28-JUN-14:00 | 0.115838E+09 | 6120.70 | 07-JUN-05:10 |
July | 0.258144E+11 | 26939.26 | 31-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.284833E+11 | 28009.22 | 10-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.270028E+11 | 21417.89 | 21-SEP-08:09 | 65011096.03 | 6120.70 | 28-SEP-05:10 |
October | 0.289735E+11 | 21846.67 | 31-OCT-08:09 | 0.350032E+10 | 26888.86 | 30-OCT-05:10 |
November | 0.298118E+11 | 27630.90 | 29-NOV-16:49 | 0.250538E+11 | 66201.02 | 29-NOV-17:00 |
December | 0.324133E+11 | 27654.59 | 26-DEC-16:30 | 0.686421E+11 | 88555.88 | 26-DEC-07:10 |
Annual Sum or Average | 0.339433E+12 | 0.269563E+12 | ||||
Minimum of Months | 0.253454E+11 | 20626.11 | 0.00 | 0.00 | ||
Maximum of Months | 0.324133E+11 | 28009.22 | 0.891334E+11 | 133568.34 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.837367E+10 | 0.728068E+10 | 0.112984E+11 | 0.00 | 0.289708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222479E+10 | 0.00 |
February | 0.714632E+10 | 0.583421E+10 | 0.103734E+11 | 0.00 | 0.241690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202734E+10 | 0.00 |
March | 0.757483E+10 | 0.544225E+10 | 0.121089E+11 | 0.00 | 0.222281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228228E+10 | 0.00 |
April | 0.654291E+10 | 0.424635E+10 | 0.112578E+11 | 0.00 | 0.191614E+10 | 0.00 | 0.00 | 18868528.94 | 0.00 | 0.00 | 0.00 | 0.214814E+10 | 0.00 |
May | 0.645195E+10 | 0.363833E+10 | 0.117000E+11 | 0.00 | 0.192116E+10 | 0.00 | 0.00 | 53217630.45 | 0.00 | 0.00 | 0.00 | 0.218955E+10 | 0.00 |
June | 0.636720E+10 | 0.316486E+10 | 0.116594E+11 | 0.00 | 0.191391E+10 | 0.00 | 0.00 | 0.132005E+09 | 0.00 | 0.00 | 0.00 | 0.210802E+10 | 0.00 |
July | 0.648847E+10 | 0.340235E+10 | 0.112984E+11 | 0.00 | 0.185041E+10 | 0.00 | 0.00 | 0.672280E+09 | 0.00 | 0.00 | 0.00 | 0.210248E+10 | 0.00 |
August | 0.704838E+10 | 0.400307E+10 | 0.121016E+11 | 0.00 | 0.204375E+10 | 0.00 | 0.00 | 0.113736E+10 | 0.00 | 0.00 | 0.00 | 0.214916E+10 | 0.00 |
September | 0.688939E+10 | 0.482207E+10 | 0.112504E+11 | 0.00 | 0.183953E+10 | 0.00 | 0.00 | 0.138225E+09 | 0.00 | 0.00 | 0.00 | 0.206320E+10 | 0.00 |
October | 0.760650E+10 | 0.603849E+10 | 0.113057E+11 | 0.00 | 0.188222E+10 | 0.00 | 0.00 | 1576889.26 | 0.00 | 0.00 | 0.00 | 0.213896E+10 | 0.00 |
November | 0.790922E+10 | 0.676981E+10 | 0.108562E+11 | 0.00 | 0.217968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209692E+10 | 0.00 |
December | 0.863170E+10 | 0.752249E+10 | 0.112984E+11 | 0.00 | 0.275804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220275E+10 | 0.00 |
Annual Sum or Average | 0.870306E+11 | 0.621650E+11 | 0.136508E+12 | 0.00 | 0.258416E+11 | 0.00 | 0.00 | 0.215353E+10 | 0.00 | 0.00 | 0.00 | 0.257336E+11 | 0.00 |
Minimum of Months | 0.636720E+10 | 0.316486E+10 | 0.103734E+11 | 0.00 | 0.183953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202734E+10 | 0.00 |
Maximum of Months | 0.863170E+10 | 0.752249E+10 | 0.121089E+11 | 0.00 | 0.289708E+10 | 0.00 | 0.00 | 0.113736E+10 | 0.00 | 0.00 | 0.00 | 0.228228E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.891334E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.608797E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.157852E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.578284E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.604465E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.115838E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 65011096.03 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.350032E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.250538E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.686421E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.269563E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.891334E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 8781.69 | 13-JAN-15:00 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2457.55 | 07-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 8206.02 | 15-FEB-15:00 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2470.79 | 18-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 7841.76 | 14-MAR-08:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2317.66 | 24-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 7208.79 | 03-APR-07:10 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2001.61 | 18-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 6762.63 | 04-MAY-08:09 | 4975.14 | 01-MAY-19:19 | 10035.17 | 01-MAY-07:10 | 0.00 | 1857.08 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 6277.23 | 29-JUN-07:10 | 4975.14 | 01-JUN-19:00 | 10035.17 | 01-JUN-07:10 | 0.00 | 1857.08 | 28-JUN-13:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 7708.54 | 12-JUL-08:09 | 4975.14 | 01-JUL-20:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 4162.37 | 31-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 7226.52 | 23-AUG-08:09 | 5520.82 | 16-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4162.37 | 10-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 7864.64 | 21-SEP-08:09 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 1857.08 | 14-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8285.38 | 31-OCT-08:09 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 1962.30 | 19-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 8827.98 | 30-NOV-15:00 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2388.27 | 29-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 8871.32 | 16-DEC-15:00 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2445.60 | 26-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 6277.23 | 4975.14 | 10035.17 | 0.00 | 1857.08 | 0.00 | 0.00 | |||||
Maximum of Months | 8871.32 | 5520.82 | 10035.17 | 0.00 | 4162.37 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2328.79 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2334.70 | 13-FEB-12:00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2319.94 | 01-MAR-12:20 | 0.00 |
April | 919.24 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 | 2229.33 | 01-APR-11:39 | 0.00 |
May | 945.68 | 15-MAY-15:00 | 0.00 | 0.00 | 0.00 | 2071.71 | 02-MAY-11:00 | 0.00 |
June | 2195.03 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1833.31 | 10-JUN-11:00 | 0.00 |
July | 5427.04 | 31-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1798.47 | 01-JUL-11:09 | 0.00 |
August | 6104.32 | 10-AUG-15:30 | 0.00 | 0.00 | 0.00 | 1792.74 | 31-AUG-11:09 | 0.00 |
September | 1446.75 | 14-SEP-14:00 | 0.00 | 0.00 | 0.00 | 1800.39 | 27-SEP-11:30 | 0.00 |
October | 276.77 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 1911.42 | 27-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2115.69 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2253.91 | 30-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1792.74 | 0.00 | ||
Maximum of Months | 6104.32 | 0.00 | 0.00 | 0.00 | 2334.70 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 27652.72 | 18-JAN-16:49 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 2341.09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21924.81 | 15-FEB-15:00 | 8206.02 | 10035.17 | 0.00 | 0.00 | 1879.56 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21461.74 | 14-MAR-08:09 | 7841.76 | 10035.17 | 0.00 | 0.00 | 1901.96 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20720.30 | 03-APR-08:09 | 7148.62 | 10035.17 | 0.00 | 0.00 | 1857.08 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20626.11 | 05-MAY-14:30 | 6087.47 | 10035.17 | 0.00 | 0.00 | 1857.08 | 0.00 | 0.00 | 865.00 | 0.00 |
June | 20638.50 | 28-JUN-14:00 | 4856.10 | 10035.17 | 0.00 | 0.00 | 1857.08 | 0.00 | 0.00 | 2128.91 | 0.00 |
July | 26939.26 | 31-JUL-14:30 | 5813.42 | 10035.17 | 0.00 | 0.00 | 4162.37 | 0.00 | 0.00 | 5173.28 | 0.00 |
August | 28009.22 | 10-AUG-14:00 | 6119.46 | 10035.17 | 0.00 | 0.00 | 4162.37 | 0.00 | 0.00 | 5937.46 | 0.00 |
September | 21417.89 | 21-SEP-08:09 | 7864.64 | 10035.17 | 0.00 | 0.00 | 1857.08 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21846.67 | 31-OCT-08:09 | 8285.38 | 10035.17 | 0.00 | 0.00 | 1857.08 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27630.90 | 29-NOV-16:49 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 2323.47 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27654.59 | 26-DEC-16:30 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 2344.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 20626.11 | 4856.10 | 10035.17 | 0.00 | 0.00 | 1857.08 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28009.22 | 8285.38 | 10035.17 | 5520.82 | 0.00 | 4162.37 | 0.00 | 0.00 | 5937.46 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 108479.48 | 09-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 133568.34 | 19-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 43255.06 | 24-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 35014.42 | 12-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 11349.23 | 18-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6120.70 | 07-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 6120.70 | 28-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 26888.86 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 66201.02 | 29-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 88555.88 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 133568.34 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.33 | 18.73 | 8.50 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
February | 10.17 | 18.77 | 8.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
March | 9.50 | 19.61 | 9.17 | 19.69 | 0.00 | 19.69 | 0.00 | 19.69 |
April | 7.33 | 20.00 | 7.33 | 20.00 | 0.00 | 20.00 | 0.00 | 20.00 |
May | 1.17 | 20.44 | 1.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
June | 0.33 | 20.44 | 0.33 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.55 | 1.00 | 24.55 |
September | 0.50 | 20.41 | 0.50 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
October | 5.50 | 20.21 | 5.50 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
November | 7.67 | 19.91 | 7.67 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 |
December | 9.83 | 18.99 | 8.50 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Annual Sum or Average | 62.33 | 19.39 | 57.00 | 19.59 | 1.00 | 19.63 | 1.00 | 19.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.33 | 20.44 | 9.17 | 20.44 | 1.00 | 24.55 | 1.00 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 85.00 | 14.81 | 3.67 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
February | 59.00 | 14.78 | 2.83 | 14.78 | 0.00 | 14.78 | 0.00 | 14.78 |
March | 18.00 | 14.93 | 1.83 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
April | 4.33 | 14.97 | 0.33 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.28 | 0.00 | 27.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.00 | 27.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.67 | 14.98 | 0.17 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
November | 22.17 | 14.94 | 1.50 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
December | 63.83 | 14.89 | 3.17 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
Annual Sum or Average | 255.00 | 14.85 | 13.50 | 14.85 | 1.00 | 14.89 | 0.00 | 14.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.00 | 14.98 | 3.67 | 14.98 | 0.67 | 27.28 | 0.00 | 27.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.05 | 300.00 | 21.05 | 300.00 | 21.05 |
February | 276.00 | 21.07 | 271.50 | 21.06 | 271.50 | 21.06 |
March | 324.00 | 21.11 | 313.17 | 21.09 | 313.17 | 21.08 |
April | 300.00 | 21.49 | 226.83 | 21.33 | 226.83 | 21.26 |
May | 310.50 | 22.60 | 52.83 | 22.38 | 52.83 | 22.22 |
June | 275.50 | 23.27 | 6.50 | 23.26 | 2.83 | 23.23 |
July | 115.50 | 23.62 | 87.17 | 23.74 | 0.00 | 23.74 |
August | 78.33 | 23.60 | 139.33 | 23.80 | 0.83 | 23.80 |
September | 230.67 | 23.27 | 26.67 | 23.28 | 4.83 | 23.23 |
October | 300.00 | 21.65 | 187.50 | 21.43 | 187.50 | 21.34 |
November | 288.00 | 21.12 | 275.17 | 21.09 | 275.17 | 21.09 |
December | 300.00 | 21.06 | 300.00 | 21.06 | 300.00 | 21.06 |
Annual Sum or Average | 3098.50 | 21.84 | 2186.67 | 21.66 | 1935.50 | 21.50 |
Minimum of Months | 78.33 | 21.05 | 6.50 | 21.05 | 0.00 | 21.05 |
Maximum of Months | 324.00 | 23.62 | 313.17 | 23.80 | 313.17 | 23.80 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.57 | 300.00 | 15.57 | 300.00 | 15.57 |
February | 276.00 | 15.82 | 276.00 | 15.82 | 276.00 | 15.82 |
March | 324.00 | 16.30 | 324.00 | 16.30 | 324.00 | 16.30 |
April | 300.00 | 17.61 | 273.67 | 17.40 | 273.67 | 17.32 |
May | 296.83 | 20.24 | 157.83 | 19.86 | 152.50 | 19.63 |
June | 236.17 | 21.69 | 85.67 | 21.98 | 39.00 | 21.71 |
July | 115.00 | 23.45 | 175.50 | 24.90 | 20.33 | 25.02 |
August | 105.50 | 24.11 | 229.33 | 25.21 | 36.50 | 25.35 |
September | 222.50 | 21.54 | 99.00 | 22.08 | 34.33 | 21.80 |
October | 300.00 | 17.84 | 261.17 | 17.58 | 261.17 | 17.49 |
November | 288.00 | 16.02 | 287.00 | 16.01 | 287.00 | 16.01 |
December | 300.00 | 15.60 | 300.00 | 15.60 | 300.00 | 15.60 |
Annual Sum or Average | 3064.00 | 18.08 | 2769.17 | 18.16 | 2304.50 | 17.76 |
Minimum of Months | 105.50 | 15.57 | 85.67 | 15.57 | 20.33 | 15.57 |
Maximum of Months | 324.00 | 24.11 | 324.00 | 25.21 | 324.00 | 25.35 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.35 | 300.00 | 10.35 | 300.00 | 10.35 |
February | 276.00 | 11.21 | 276.00 | 11.21 | 276.00 | 11.21 |
March | 324.00 | 13.14 | 324.00 | 13.14 | 324.00 | 13.14 |
April | 300.00 | 15.72 | 286.17 | 15.59 | 286.17 | 15.54 |
May | 309.33 | 19.88 | 191.50 | 19.44 | 191.50 | 19.24 |
June | 249.50 | 21.41 | 92.83 | 21.53 | 53.83 | 21.20 |
July | 140.17 | 24.32 | 174.83 | 25.41 | 45.00 | 25.74 |
August | 130.17 | 25.84 | 243.17 | 26.16 | 72.67 | 26.50 |
September | 224.83 | 21.49 | 107.33 | 21.84 | 49.67 | 21.49 |
October | 300.00 | 16.45 | 286.83 | 16.34 | 286.83 | 16.31 |
November | 288.00 | 12.36 | 288.00 | 12.36 | 288.00 | 12.36 |
December | 300.00 | 10.62 | 300.00 | 10.62 | 300.00 | 10.62 |
Annual Sum or Average | 3142.00 | 15.90 | 2870.67 | 15.84 | 2473.67 | 15.37 |
Minimum of Months | 130.17 | 10.35 | 92.83 | 10.35 | 45.00 | 10.35 |
Maximum of Months | 324.00 | 25.84 | 324.00 | 26.16 | 324.00 | 26.50 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 85819328.03 | 18868528.94 | 12.50 | 82156092.85 | 3663235.19 | 0.00 | 0.53 | 27-APR-16:00 | 0.00 | 01-APR-00:10 | 4222.17 | 27-APR-16:00 | 3920.68 | 27-APR-16:00 | 301.49 | 27-APR-16:00 | 919.24 | 27-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.253932E+09 | 53217630.45 | 29.17 | 0.231083E+09 | 22848815.03 | 0.00 | 0.59 | 15-MAY-16:00 | 0.00 | 01-MAY-00:10 | 4623.78 | 15-MAY-16:00 | 4623.78 | 15-MAY-16:00 | 875.77 | 06-MAY-13:00 | 945.68 | 15-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.594767E+09 | 0.124257E+09 | 69.58 | 0.577648E+09 | 17118907.06 | 0.00 | 0.81 | 28-JUN-16:00 | 0.00 | 01-JUN-00:10 | 6785.71 | 28-JUN-16:00 | 6549.44 | 28-JUN-16:00 | 327.56 | 21-JUN-17:00 | 1384.91 | 28-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.206214E+10 | 0.423602E+09 | 144.47 | 0.180697E+10 | 0.255171E+09 | 0.00 | 1.00 | 24-JUL-05:02 | 0.00 | 01-JUL-00:10 | 15900.60 | 31-JUL-05:55 | 11294.51 | 24-JUL-05:02 | 6050.19 | 25-JUL-05:03 | 3197.13 | 31-JUL-05:55 | 0.00 | 01-JUL-00:10 |
August | 0.304240E+10 | 0.628147E+09 | 184.51 | 0.264394E+10 | 0.398468E+09 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 16093.76 | 25-AUG-05:03 | 11235.82 | 09-AUG-05:03 | 6567.67 | 26-AUG-05:03 | 3232.50 | 25-AUG-05:03 | 0.00 | 01-AUG-00:10 |
September | 0.673427E+09 | 0.138129E+09 | 59.25 | 0.565991E+09 | 0.107436E+09 | 0.00 | 0.81 | 14-SEP-16:00 | 0.00 | 01-SEP-00:10 | 7131.90 | 14-SEP-16:00 | 6213.80 | 14-SEP-16:00 | 1456.82 | 14-SEP-13:00 | 1406.03 | 14-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 7178557.08 | 1576889.26 | 4.50 | 7178555.83 | 1.25 | 0.00 | 0.18 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1269.09 | 04-OCT-15:00 | 1269.09 | 04-OCT-15:00 | 0.00 | 07-OCT-12:20 | 276.77 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.671967E+10 | 0.138780E+10 | 503.98 | 0.591496E+10 | 0.804706E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.304240E+10 | 0.628147E+09 | 184.51 | 0.264394E+10 | 0.398468E+09 | 0.00 | 1.00 | 0.00 | 16093.76 | 11294.51 | 6567.67 | 3232.50 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
June | 29807428.05 | 7747828.57 | 3.67 | 29226950.71 | 580477.34 | 0.00 | 0.19 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 3176.01 | 28-JUN-15:00 | 3176.01 | 28-JUN-15:00 | 86.73 | 28-JUN-16:00 | 823.64 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.100884E+10 | 0.248678E+09 | 44.73 | 0.878734E+09 | 0.130103E+09 | 0.00 | 1.00 | 23-JUL-13:15 | 0.00 | 01-JUL-00:10 | 41935.07 | 31-JUL-18:02 | 39197.50 | 23-JUL-17:45 | 6791.59 | 31-JUL-18:02 | 9398.33 | 31-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 0.203756E+10 | 0.509209E+09 | 76.25 | 0.177229E+10 | 0.265269E+09 | 0.00 | 1.00 | 08-AUG-17:20 | 0.00 | 01-AUG-00:10 | 41866.04 | 13-AUG-12:53 | 38519.88 | 15-AUG-17:42 | 6879.70 | 13-AUG-11:25 | 9757.30 | 10-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 373924.39 | 95268.91 | 1.17 | 293342.86 | 80581.53 | 0.00 | 0.02 | 14-SEP-15:00 | 0.00 | 01-SEP-00:10 | 351.23 | 14-SEP-15:00 | 273.55 | 14-SEP-15:00 | 77.68 | 14-SEP-15:00 | 89.21 | 14-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.307658E+10 | 0.765730E+09 | 125.82 | 0.268055E+10 | 0.396033E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.203756E+10 | 0.509209E+09 | 76.25 | 0.177229E+10 | 0.265269E+09 | 0.00 | 1.00 | 0.00 | 41935.07 | 39197.50 | 6879.70 | 9757.30 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.95 | 10.38 | 24.57 | 18.77 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 62.09 | 23.13 | 38.96 | 52.72 | 79.18 | 0.00 | 0.00 | 0.00 |
March | 87.46 | 29.55 | 57.91 | 87.57 | 60.77 | 0.00 | 0.00 | 0.00 |
April | 132.77 | 50.66 | 82.11 | 153.66 | 48.49 | 0.00 | 0.00 | 0.00 |
May | 171.26 | 69.65 | 101.61 | 205.72 | 46.69 | 0.00 | 0.00 | 0.00 |
June | 164.65 | 63.94 | 100.71 | 197.11 | 40.14 | 0.00 | 0.00 | 0.00 |
July | 203.76 | 107.26 | 96.50 | 258.22 | 42.40 | 0.00 | 0.00 | 0.00 |
August | 168.21 | 85.80 | 82.41 | 215.04 | 43.28 | 0.00 | 0.00 | 0.00 |
September | 137.49 | 66.14 | 71.34 | 165.27 | 54.29 | 0.00 | 0.00 | 0.00 |
October | 78.30 | 32.03 | 46.27 | 83.29 | 57.01 | 0.00 | 0.00 | 0.00 |
November | 38.96 | 11.10 | 27.86 | 28.21 | 70.71 | 0.00 | 0.00 | 0.00 |
December | 33.05 | 11.59 | 21.46 | 21.81 | 94.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.70 | 46.95 | 62.75 | 124.40 | 60.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.05 | 10.38 | 21.46 | 18.77 | 40.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 203.76 | 107.26 | 101.61 | 258.22 | 94.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.95 | 10.38 | 24.57 | 18.77 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 62.09 | 23.13 | 38.96 | 52.72 | 79.18 | 0.00 | 0.00 | 0.00 |
March | 87.46 | 29.55 | 57.91 | 87.57 | 60.77 | 0.00 | 0.00 | 0.00 |
April | 132.77 | 50.66 | 82.11 | 153.66 | 48.49 | 0.00 | 0.00 | 0.00 |
May | 171.26 | 69.65 | 101.61 | 205.72 | 46.69 | 0.00 | 0.00 | 0.00 |
June | 164.65 | 63.94 | 100.71 | 197.11 | 40.14 | 0.00 | 0.00 | 0.00 |
July | 203.76 | 107.26 | 96.50 | 258.22 | 42.40 | 0.00 | 0.00 | 0.00 |
August | 168.21 | 85.80 | 82.41 | 215.04 | 43.28 | 0.00 | 0.00 | 0.00 |
September | 137.49 | 66.14 | 71.34 | 165.27 | 54.29 | 0.00 | 0.00 | 0.00 |
October | 78.30 | 32.03 | 46.27 | 83.29 | 57.01 | 0.00 | 0.00 | 0.00 |
November | 38.96 | 11.10 | 27.86 | 28.21 | 70.71 | 0.00 | 0.00 | 0.00 |
December | 33.05 | 11.59 | 21.46 | 21.81 | 94.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.70 | 46.95 | 62.75 | 124.40 | 60.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.05 | 10.38 | 21.46 | 18.77 | 40.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 203.76 | 107.26 | 101.61 | 258.22 | 94.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.98 | 0.00 | 11.98 | 1.23 | 57.35 | 0.00 | 0.00 | 0.00 |
February | 18.63 | 0.00 | 18.63 | 6.74 | 48.40 | 0.00 | 0.00 | 0.00 |
March | 27.46 | 0.00 | 27.46 | 17.60 | 36.33 | 0.00 | 0.00 | 0.00 |
April | 38.91 | 0.19 | 38.73 | 34.31 | 27.96 | 0.00 | 0.00 | 0.00 |
May | 49.97 | 1.46 | 48.51 | 48.47 | 26.29 | 0.00 | 0.00 | 0.00 |
June | 52.56 | 3.46 | 49.11 | 52.61 | 22.19 | 0.00 | 0.00 | 0.00 |
July | 50.00 | 3.94 | 46.07 | 52.04 | 23.30 | 0.00 | 0.00 | 0.00 |
August | 40.62 | 1.24 | 39.38 | 42.55 | 23.90 | 0.00 | 0.00 | 0.00 |
September | 31.43 | 0.02 | 31.41 | 26.24 | 32.05 | 0.00 | 0.00 | 0.00 |
October | 21.52 | 0.00 | 21.52 | 14.34 | 33.91 | 0.00 | 0.00 | 0.00 |
November | 13.56 | 0.00 | 13.56 | 4.23 | 42.62 | 0.00 | 0.00 | 0.00 |
December | 10.18 | 0.00 | 10.18 | 0.89 | 56.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.63 | 0.87 | 29.76 | 25.21 | 35.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.18 | 0.00 | 10.18 | 0.89 | 22.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.56 | 3.94 | 49.11 | 52.61 | 57.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.97 | 0.00 | 11.97 | 1.23 | 57.35 | 0.00 | 0.00 | 0.00 |
February | 18.63 | 0.00 | 18.63 | 6.74 | 48.40 | 0.00 | 0.00 | 0.00 |
March | 27.46 | 0.00 | 27.46 | 17.60 | 36.33 | 0.00 | 0.00 | 0.00 |
April | 38.91 | 0.19 | 38.73 | 34.31 | 27.96 | 0.00 | 0.00 | 0.00 |
May | 49.97 | 1.46 | 48.51 | 48.47 | 26.29 | 0.00 | 0.00 | 0.00 |
June | 52.56 | 3.46 | 49.10 | 52.60 | 22.19 | 0.00 | 0.00 | 0.00 |
July | 50.00 | 3.94 | 46.07 | 52.04 | 23.30 | 0.00 | 0.00 | 0.00 |
August | 40.62 | 1.24 | 39.38 | 42.55 | 23.90 | 0.00 | 0.00 | 0.00 |
September | 31.43 | 0.02 | 31.41 | 26.24 | 32.05 | 0.00 | 0.00 | 0.00 |
October | 21.52 | 0.00 | 21.52 | 14.34 | 33.91 | 0.00 | 0.00 | 0.00 |
November | 13.56 | 0.00 | 13.56 | 4.23 | 42.62 | 0.00 | 0.00 | 0.00 |
December | 10.18 | 0.00 | 10.18 | 0.89 | 56.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.63 | 0.86 | 29.76 | 25.21 | 35.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.18 | 0.00 | 10.18 | 0.89 | 22.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.56 | 3.94 | 49.10 | 52.60 | 57.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.29 | 35.01 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.49 | 31.01 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.75 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.70 | 19.84 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.50 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.41 | 17.93 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.47 | 19.68 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.58 | 20.57 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 66.99 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.39 | 23.00 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.75 | 26.26 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.36 | 24.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.47 | 35.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.29 | 35.01 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.49 | 31.01 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.75 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.70 | 19.84 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.50 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.41 | 17.93 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.47 | 19.68 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.58 | 20.57 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 66.99 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.39 | 23.00 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.75 | 26.26 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.36 | 24.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.47 | 35.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.29 | 35.01 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.49 | 31.01 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.75 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.70 | 19.84 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.50 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.41 | 17.93 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.47 | 19.68 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.58 | 20.57 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 66.99 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.39 | 23.00 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.75 | 26.26 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.36 | 24.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.47 | 35.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.29 | 35.01 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.49 | 31.01 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.75 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.70 | 19.84 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.50 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.41 | 17.93 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.47 | 19.68 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.58 | 20.57 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 66.99 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.39 | 23.00 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.75 | 26.26 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.36 | 24.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.47 | 35.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.29 | 35.01 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.49 | 31.01 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.75 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.70 | 19.84 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.50 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.41 | 17.93 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.47 | 19.68 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.58 | 20.57 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 66.99 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.39 | 23.00 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.75 | 26.26 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.36 | 24.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.47 | 35.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.29 | 35.01 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.49 | 31.01 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.75 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.70 | 19.84 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.50 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.41 | 17.93 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.47 | 19.68 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.58 | 20.57 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 66.99 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.39 | 23.00 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.75 | 26.26 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.36 | 24.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.47 | 35.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.29 | 35.01 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.49 | 31.01 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.75 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.70 | 19.84 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.50 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.41 | 17.93 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.47 | 19.68 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.58 | 20.57 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 66.99 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.39 | 23.00 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.75 | 26.26 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.36 | 24.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.47 | 35.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.29 | 35.01 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.49 | 31.01 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.75 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.70 | 19.84 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.50 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.41 | 17.93 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.47 | 19.68 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.58 | 20.57 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 66.99 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.39 | 23.00 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.75 | 26.26 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.36 | 24.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.47 | 35.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.29 | 35.01 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.49 | 31.01 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.75 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.70 | 19.84 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.50 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.41 | 17.93 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.47 | 19.68 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.58 | 20.57 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 66.99 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.39 | 23.00 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.75 | 26.26 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.36 | 24.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.47 | 35.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.29 | 35.01 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.49 | 31.01 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.75 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.70 | 19.84 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.50 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.41 | 17.93 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.47 | 19.68 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.58 | 20.57 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 66.99 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.39 | 23.00 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.75 | 26.26 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.36 | 24.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.47 | 35.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.29 | 35.01 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.49 | 31.01 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.75 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.70 | 19.84 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.50 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.41 | 17.93 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.47 | 19.68 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.58 | 20.57 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 66.99 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.39 | 23.00 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.75 | 26.26 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.36 | 24.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.47 | 35.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.29 | 35.01 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.49 | 31.01 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.75 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.70 | 19.84 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.50 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.41 | 17.93 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.47 | 19.68 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.58 | 20.57 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 66.99 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.39 | 23.00 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.75 | 26.26 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.36 | 24.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.47 | 35.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.29 | 35.01 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.49 | 31.01 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.75 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.70 | 19.84 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.50 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.41 | 17.93 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.47 | 19.68 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.58 | 20.57 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 66.99 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.39 | 23.00 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.75 | 26.26 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.36 | 24.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.47 | 35.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.04 | 2.74 | 11.30 | 8.29 | 35.01 | 0.00 | 0.00 | 0.00 |
February | 25.12 | 8.35 | 16.78 | 22.49 | 31.01 | 0.00 | 0.00 | 0.00 |
March | 43.98 | 18.87 | 25.11 | 46.75 | 24.17 | 0.00 | 0.00 | 0.00 |
April | 70.02 | 35.65 | 34.37 | 81.70 | 19.84 | 0.00 | 0.00 | 0.00 |
May | 91.00 | 46.95 | 44.05 | 107.50 | 19.73 | 0.00 | 0.00 | 0.00 |
June | 99.72 | 58.53 | 41.19 | 117.41 | 17.93 | 0.00 | 0.00 | 0.00 |
July | 104.02 | 68.68 | 35.34 | 124.47 | 19.68 | 0.00 | 0.00 | 0.00 |
August | 83.39 | 53.05 | 30.34 | 99.58 | 20.57 | 0.00 | 0.00 | 0.00 |
September | 58.63 | 32.55 | 26.07 | 66.99 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 34.62 | 16.16 | 18.46 | 37.39 | 23.00 | 0.00 | 0.00 | 0.00 |
November | 16.87 | 4.13 | 12.74 | 13.75 | 26.26 | 0.00 | 0.00 | 0.00 |
December | 12.13 | 2.92 | 9.21 | 7.36 | 35.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.63 | 29.18 | 25.45 | 61.36 | 24.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.13 | 2.74 | 9.21 | 7.36 | 17.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.02 | 68.68 | 44.05 | 124.47 | 35.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.20 | 4.53 | 15.66 | 19.13 | 29.86 | 14.17 | 0.00 | 0.00 |
February | 36.04 | 12.79 | 23.25 | 40.89 | 27.34 | 34.67 | 0.00 | 0.00 |
March | 61.43 | 26.63 | 34.80 | 74.69 | 23.36 | 10.33 | 0.00 | 0.00 |
April | 96.76 | 49.12 | 47.64 | 123.26 | 21.76 | 0.83 | 0.00 | 0.00 |
May | 124.93 | 63.87 | 61.05 | 157.53 | 24.73 | 0.00 | 0.00 | 0.00 |
June | 136.42 | 79.32 | 57.10 | 171.31 | 22.81 | 0.00 | 0.00 | 0.00 |
July | 142.36 | 93.38 | 48.98 | 180.37 | 25.83 | 0.00 | 0.00 | 0.00 |
August | 114.84 | 72.79 | 42.05 | 143.98 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 81.70 | 45.56 | 36.14 | 99.10 | 31.61 | 0.00 | 0.00 | 0.00 |
October | 48.97 | 23.39 | 25.58 | 57.99 | 26.68 | 5.17 | 0.00 | 0.00 |
November | 24.12 | 6.46 | 17.66 | 25.92 | 23.01 | 45.50 | 0.00 | 0.00 |
December | 17.63 | 4.87 | 12.76 | 16.90 | 29.76 | 43.67 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 40.40 | 35.27 | 92.88 | 26.26 | 154.33 | 0.00 | 0.00 |
Minimum of Months | 17.63 | 4.53 | 12.76 | 16.90 | 21.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 93.38 | 61.05 | 180.37 | 31.61 | 45.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93609665.34 | 27794440.75 | 65815224.59 | 50285816.93 | 0.250542E+09 |
February | 0.150213E+09 | 55949557.06 | 94263196.03 | 0.127538E+09 | 0.191543E+09 |
March | 0.234262E+09 | 79147176.98 | 0.155114E+09 | 0.234546E+09 | 0.162756E+09 |
April | 0.344143E+09 | 0.131311E+09 | 0.212832E+09 | 0.398281E+09 | 0.125682E+09 |
May | 0.458698E+09 | 0.186554E+09 | 0.272144E+09 | 0.551003E+09 | 0.125065E+09 |
June | 0.426781E+09 | 0.165731E+09 | 0.261050E+09 | 0.510916E+09 | 0.104053E+09 |
July | 0.545756E+09 | 0.287298E+09 | 0.258458E+09 | 0.691604E+09 | 0.113561E+09 |
August | 0.450522E+09 | 0.229801E+09 | 0.220721E+09 | 0.575968E+09 | 0.115913E+09 |
September | 0.356369E+09 | 0.171446E+09 | 0.184923E+09 | 0.428385E+09 | 0.140719E+09 |
October | 0.209711E+09 | 85792715.97 | 0.123919E+09 | 0.223078E+09 | 0.152688E+09 |
November | 0.100982E+09 | 28765899.50 | 72215864.18 | 73118738.24 | 0.183281E+09 |
December | 88528491.19 | 31053499.54 | 57474991.65 | 58407746.56 | 0.252286E+09 |
Annual Sum or Average | 0.345957E+10 | 0.148064E+10 | 0.197893E+10 | 0.392313E+10 | 0.191809E+10 |
Minimum of Months | 88528491.19 | 27794440.75 | 57474991.65 | 50285816.93 | 0.104053E+09 |
Maximum of Months | 0.545756E+09 | 0.287298E+09 | 0.272144E+09 | 0.691604E+09 | 0.252286E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93609665.34 | 27794440.75 | 65815224.59 | 50285816.93 | 0.250542E+09 |
February | 0.150213E+09 | 55949557.06 | 94263196.03 | 0.127538E+09 | 0.191543E+09 |
March | 0.234262E+09 | 79147176.98 | 0.155114E+09 | 0.234546E+09 | 0.162756E+09 |
April | 0.344143E+09 | 0.131311E+09 | 0.212832E+09 | 0.398281E+09 | 0.125682E+09 |
May | 0.458698E+09 | 0.186554E+09 | 0.272144E+09 | 0.551003E+09 | 0.125065E+09 |
June | 0.426781E+09 | 0.165731E+09 | 0.261050E+09 | 0.510916E+09 | 0.104053E+09 |
July | 0.545756E+09 | 0.287298E+09 | 0.258458E+09 | 0.691604E+09 | 0.113561E+09 |
August | 0.450522E+09 | 0.229801E+09 | 0.220721E+09 | 0.575968E+09 | 0.115913E+09 |
September | 0.356369E+09 | 0.171446E+09 | 0.184923E+09 | 0.428385E+09 | 0.140719E+09 |
October | 0.209711E+09 | 85792715.97 | 0.123919E+09 | 0.223078E+09 | 0.152688E+09 |
November | 0.100982E+09 | 28765899.50 | 72215864.18 | 73118738.24 | 0.183281E+09 |
December | 88528491.19 | 31053499.54 | 57474991.65 | 58407746.56 | 0.252286E+09 |
Annual Sum or Average | 0.345957E+10 | 0.148064E+10 | 0.197893E+10 | 0.392313E+10 | 0.191809E+10 |
Minimum of Months | 88528491.19 | 27794440.75 | 57474991.65 | 50285816.93 | 0.104053E+09 |
Maximum of Months | 0.545756E+09 | 0.287298E+09 | 0.272144E+09 | 0.691604E+09 | 0.252286E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 32074850.23 | 0.00 | 32074850.23 | 3293154.08 | 0.153598E+09 |
February | 45079413.90 | 0.00 | 45079413.90 | 16311614.49 | 0.117100E+09 |
March | 73544133.97 | 1466.78 | 73542667.18 | 47130626.79 | 97317772.17 |
April | 0.100868E+09 | 488603.01 | 0.100379E+09 | 88930077.21 | 72470254.29 |
May | 0.133835E+09 | 3913254.10 | 0.129921E+09 | 0.129817E+09 | 70414105.40 |
June | 0.136248E+09 | 8965120.00 | 0.127282E+09 | 0.136357E+09 | 57510044.72 |
July | 0.133925E+09 | 10540813.15 | 0.123384E+09 | 0.139376E+09 | 62418834.74 |
August | 0.108790E+09 | 3317738.52 | 0.105473E+09 | 0.113973E+09 | 64025310.65 |
September | 81468951.01 | 52736.79 | 81416214.22 | 68025511.83 | 83079614.33 |
October | 57650012.96 | 0.00 | 57650012.96 | 38409823.57 | 90831235.14 |
November | 35142384.98 | 0.00 | 35142384.98 | 10976216.30 | 0.110483E+09 |
December | 27255351.36 | 0.00 | 27255351.36 | 2394650.72 | 0.152081E+09 |
Annual Sum or Average | 0.965880E+09 | 27279732.36 | 0.938601E+09 | 0.794994E+09 | 0.113133E+10 |
Minimum of Months | 27255351.36 | 0.00 | 27255351.36 | 2394650.72 | 57510044.72 |
Maximum of Months | 0.136248E+09 | 10540813.15 | 0.129921E+09 | 0.139376E+09 | 0.153598E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 32073727.19 | 0.00 | 32073727.19 | 3292690.00 | 0.153598E+09 |
February | 45077910.44 | 0.00 | 45077910.44 | 16310308.46 | 0.117100E+09 |
March | 73541746.59 | 1466.72 | 73540279.88 | 47128087.60 | 97317543.31 |
April | 0.100864E+09 | 488580.11 | 0.100376E+09 | 88926387.69 | 72470007.54 |
May | 0.133830E+09 | 3913070.68 | 0.129917E+09 | 0.129811E+09 | 70413835.21 |
June | 0.136243E+09 | 8964699.80 | 0.127279E+09 | 0.136352E+09 | 57509797.78 |
July | 0.133921E+09 | 10540319.09 | 0.123381E+09 | 0.139371E+09 | 62418562.92 |
August | 0.108787E+09 | 3317583.01 | 0.105470E+09 | 0.113969E+09 | 64024937.55 |
September | 81466488.84 | 52734.32 | 81413754.52 | 68022687.09 | 83079129.66 |
October | 57648172.51 | 0.00 | 57648172.51 | 38407856.02 | 90830781.22 |
November | 35141163.59 | 0.00 | 35141163.59 | 10975261.42 | 0.110483E+09 |
December | 27254410.75 | 0.00 | 27254410.75 | 2394324.13 | 0.152080E+09 |
Annual Sum or Average | 0.965850E+09 | 27278453.72 | 0.938572E+09 | 0.794961E+09 | 0.113133E+10 |
Minimum of Months | 27254410.75 | 0.00 | 27254410.75 | 2394324.13 | 57509797.78 |
Maximum of Months | 0.136243E+09 | 10540319.09 | 0.129917E+09 | 0.139371E+09 | 0.153598E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22190942.73 | 93760108.59 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54416702.53 | 75011542.46 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125226E+09 | 64742408.43 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211760E+09 | 51436478.16 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.287923E+09 | 52833279.83 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304314E+09 | 46463247.70 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333393E+09 | 52697623.35 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266709E+09 | 55096057.55 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173641E+09 | 62985556.82 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100154E+09 | 61603010.16 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35630076.27 | 68076227.23 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19715591.13 | 94637136.32 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193507E+10 | 0.779343E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19715591.13 | 46463247.70 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333393E+09 | 94637136.32 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22190942.73 | 93760108.59 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54416702.53 | 75011542.46 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125226E+09 | 64742408.43 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211760E+09 | 51436478.16 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.287923E+09 | 52833279.83 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304314E+09 | 46463247.70 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333393E+09 | 52697623.35 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266709E+09 | 55096057.55 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173641E+09 | 62985556.82 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100154E+09 | 61603010.16 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35630076.27 | 68076227.23 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19715591.13 | 94637136.32 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193507E+10 | 0.779343E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19715591.13 | 46463247.70 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333393E+09 | 94637136.32 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22190942.73 | 93760108.59 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54416702.53 | 75011542.46 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125226E+09 | 64742408.43 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211760E+09 | 51436478.16 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.287923E+09 | 52833279.83 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304314E+09 | 46463247.70 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333393E+09 | 52697623.35 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266709E+09 | 55096057.55 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173641E+09 | 62985556.82 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100154E+09 | 61603010.16 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35630076.27 | 68076227.23 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19715591.13 | 94637136.32 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193507E+10 | 0.779343E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19715591.13 | 46463247.70 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333393E+09 | 94637136.32 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22190942.73 | 93760108.59 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54416702.53 | 75011542.46 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125226E+09 | 64742408.43 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211760E+09 | 51436478.16 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.287923E+09 | 52833279.83 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304314E+09 | 46463247.70 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333393E+09 | 52697623.35 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266709E+09 | 55096057.55 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173641E+09 | 62985556.82 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100154E+09 | 61603010.16 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35630076.27 | 68076227.23 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19715591.13 | 94637136.32 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193507E+10 | 0.779343E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19715591.13 | 46463247.70 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333393E+09 | 94637136.32 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22190942.73 | 93760108.59 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54416702.53 | 75011542.46 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125226E+09 | 64742408.43 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211760E+09 | 51436478.16 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.287923E+09 | 52833279.83 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304314E+09 | 46463247.70 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333393E+09 | 52697623.35 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266709E+09 | 55096057.55 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173641E+09 | 62985556.82 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100154E+09 | 61603010.16 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35630076.27 | 68076227.23 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19715591.13 | 94637136.32 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193507E+10 | 0.779343E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19715591.13 | 46463247.70 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333393E+09 | 94637136.32 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22190942.73 | 93760108.59 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54416702.53 | 75011542.46 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125226E+09 | 64742408.43 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211760E+09 | 51436478.16 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.287923E+09 | 52833279.83 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304314E+09 | 46463247.70 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333393E+09 | 52697623.35 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266709E+09 | 55096057.55 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173641E+09 | 62985556.82 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100154E+09 | 61603010.16 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35630076.27 | 68076227.23 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19715591.13 | 94637136.32 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193507E+10 | 0.779343E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19715591.13 | 46463247.70 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333393E+09 | 94637136.32 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22190942.73 | 93760108.59 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54416702.53 | 75011542.46 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125226E+09 | 64742408.43 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211760E+09 | 51436478.16 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.287923E+09 | 52833279.83 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304314E+09 | 46463247.70 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333393E+09 | 52697623.35 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266709E+09 | 55096057.55 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173641E+09 | 62985556.82 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100154E+09 | 61603010.16 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35630076.27 | 68076227.23 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19715591.13 | 94637136.32 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193507E+10 | 0.779343E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19715591.13 | 46463247.70 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333393E+09 | 94637136.32 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22190942.73 | 93760108.59 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54416702.53 | 75011542.46 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125226E+09 | 64742408.43 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211760E+09 | 51436478.16 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.287923E+09 | 52833279.83 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304314E+09 | 46463247.70 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333393E+09 | 52697623.35 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266709E+09 | 55096057.55 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173641E+09 | 62985556.82 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100154E+09 | 61603010.16 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35630076.27 | 68076227.23 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19715591.13 | 94637136.32 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193507E+10 | 0.779343E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19715591.13 | 46463247.70 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333393E+09 | 94637136.32 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22190942.73 | 93760108.59 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54416702.53 | 75011542.46 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125226E+09 | 64742408.43 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211760E+09 | 51436478.16 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.287923E+09 | 52833279.83 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304314E+09 | 46463247.70 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333393E+09 | 52697623.35 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266709E+09 | 55096057.55 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173641E+09 | 62985556.82 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100154E+09 | 61603010.16 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35630076.27 | 68076227.23 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19715591.13 | 94637136.32 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193507E+10 | 0.779343E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19715591.13 | 46463247.70 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333393E+09 | 94637136.32 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22190942.73 | 93760108.59 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54416702.53 | 75011542.46 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125226E+09 | 64742408.43 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211760E+09 | 51436478.16 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.287923E+09 | 52833279.83 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304314E+09 | 46463247.70 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333393E+09 | 52697623.35 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266709E+09 | 55096057.55 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173641E+09 | 62985556.82 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100154E+09 | 61603010.16 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35630076.27 | 68076227.23 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19715591.13 | 94637136.32 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193507E+10 | 0.779343E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19715591.13 | 46463247.70 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333393E+09 | 94637136.32 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22190942.73 | 93760108.59 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54416702.53 | 75011542.46 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125226E+09 | 64742408.43 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211760E+09 | 51436478.16 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.287923E+09 | 52833279.83 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304314E+09 | 46463247.70 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333393E+09 | 52697623.35 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266709E+09 | 55096057.55 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173641E+09 | 62985556.82 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100154E+09 | 61603010.16 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35630076.27 | 68076227.23 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19715591.13 | 94637136.32 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193507E+10 | 0.779343E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19715591.13 | 46463247.70 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333393E+09 | 94637136.32 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22190942.73 | 93760108.59 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54416702.53 | 75011542.46 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125226E+09 | 64742408.43 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211760E+09 | 51436478.16 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.287923E+09 | 52833279.83 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304314E+09 | 46463247.70 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333393E+09 | 52697623.35 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266709E+09 | 55096057.55 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173641E+09 | 62985556.82 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100154E+09 | 61603010.16 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35630076.27 | 68076227.23 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19715591.13 | 94637136.32 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193507E+10 | 0.779343E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19715591.13 | 46463247.70 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333393E+09 | 94637136.32 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22190942.73 | 93760108.59 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54416702.53 | 75011542.46 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125226E+09 | 64742408.43 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211760E+09 | 51436478.16 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.287923E+09 | 52833279.83 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304314E+09 | 46463247.70 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333393E+09 | 52697623.35 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266709E+09 | 55096057.55 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173641E+09 | 62985556.82 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100154E+09 | 61603010.16 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35630076.27 | 68076227.23 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19715591.13 | 94637136.32 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193507E+10 | 0.779343E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19715591.13 | 46463247.70 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333393E+09 | 94637136.32 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37612137.41 | 7345306.94 | 30266830.47 | 22190942.73 | 93760108.59 |
February | 60780041.92 | 20194538.57 | 40585503.35 | 54416702.53 | 75011542.46 |
March | 0.117789E+09 | 50536040.57 | 67252614.65 | 0.125226E+09 | 64742408.43 |
April | 0.181500E+09 | 92405350.45 | 89094460.34 | 0.211760E+09 | 51436478.16 |
May | 0.243733E+09 | 0.125754E+09 | 0.117979E+09 | 0.287923E+09 | 52833279.83 |
June | 0.258477E+09 | 0.151704E+09 | 0.106773E+09 | 0.304314E+09 | 46463247.70 |
July | 0.278609E+09 | 0.183956E+09 | 94652905.99 | 0.333393E+09 | 52697623.35 |
August | 0.223353E+09 | 0.142090E+09 | 81262303.26 | 0.266709E+09 | 55096057.55 |
September | 0.151961E+09 | 84376796.79 | 67584366.11 | 0.173641E+09 | 62985556.82 |
October | 92726895.24 | 43295646.68 | 49431248.55 | 0.100154E+09 | 61603010.16 |
November | 43725115.28 | 10702521.30 | 33022593.98 | 35630076.27 | 68076227.23 |
December | 32493553.24 | 7832190.96 | 24661362.29 | 19715591.13 | 94637136.32 |
Annual Sum or Average | 0.172276E+10 | 0.920193E+09 | 0.802566E+09 | 0.193507E+10 | 0.779343E+09 |
Minimum of Months | 32493553.24 | 7345306.94 | 24661362.29 | 19715591.13 | 46463247.70 |
Maximum of Months | 0.278609E+09 | 0.183956E+09 | 0.117979E+09 | 0.333393E+09 | 94637136.32 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54092584.75 | 12140923.29 | 41951661.46 | 51226835.54 | 79976168.65 |
February | 87197909.54 | 30943942.07 | 56253967.47 | 98914151.21 | 66141285.53 |
March | 0.164544E+09 | 71327737.91 | 93216199.98 | 0.200043E+09 | 62580396.96 |
April | 0.250810E+09 | 0.127320E+09 | 0.123490E+09 | 0.319489E+09 | 56403594.65 |
May | 0.334600E+09 | 0.171073E+09 | 0.163527E+09 | 0.421936E+09 | 66244423.95 |
June | 0.353592E+09 | 0.205598E+09 | 0.147994E+09 | 0.444032E+09 | 59127377.40 |
July | 0.381293E+09 | 0.250099E+09 | 0.131195E+09 | 0.483105E+09 | 69180439.64 |
August | 0.307585E+09 | 0.194951E+09 | 0.112634E+09 | 0.385648E+09 | 75749700.24 |
September | 0.211759E+09 | 0.118083E+09 | 93676027.61 | 0.256866E+09 | 81943822.99 |
October | 0.131158E+09 | 62643489.56 | 68514706.45 | 0.155309E+09 | 71450175.23 |
November | 62510191.83 | 16738875.13 | 45771316.71 | 67172784.96 | 59644175.70 |
December | 47231980.48 | 13049837.67 | 34182142.82 | 45268742.11 | 79715854.68 |
Annual Sum or Average | 0.238638E+10 | 0.127397E+10 | 0.111241E+10 | 0.292901E+10 | 0.828157E+09 |
Minimum of Months | 47231980.48 | 12140923.29 | 34182142.82 | 45268742.11 | 56403594.65 |
Maximum of Months | 0.381293E+09 | 0.250099E+09 | 0.163527E+09 | 0.483105E+09 | 81943822.99 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 35.90 | 297.67 | 93.85 | 20.75 | 73.10 | 0.00 | 0.00 |
February | 116.06 | 252.30 | 161.45 | 46.25 | 115.20 | 0.00 | 0.00 |
March | 208.82 | 192.69 | 229.84 | 59.10 | 170.74 | 0.00 | 0.00 |
April | 375.39 | 152.35 | 343.37 | 101.70 | 241.67 | 0.00 | 0.00 |
May | 507.09 | 144.68 | 442.45 | 142.22 | 300.23 | 0.00 | 0.00 |
June | 497.45 | 122.68 | 434.43 | 134.80 | 299.64 | 0.00 | 0.00 |
July | 618.30 | 129.20 | 507.53 | 222.40 | 285.13 | 0.00 | 0.00 |
August | 514.08 | 133.26 | 417.65 | 174.07 | 243.57 | 0.00 | 0.00 |
September | 382.08 | 171.73 | 337.84 | 132.33 | 205.51 | 0.00 | 0.00 |
October | 193.90 | 180.49 | 199.64 | 64.06 | 135.58 | 0.00 | 0.00 |
November | 63.00 | 224.78 | 105.03 | 22.20 | 82.84 | 0.00 | 0.00 |
December | 42.32 | 298.86 | 86.46 | 23.19 | 63.27 | 0.00 | 0.00 |
Annual Sum or Average | 297.32 | 191.49 | 280.66 | 95.63 | 185.03 | 0.00 | 0.00 |
Minimum of Months | 35.90 | 122.68 | 86.46 | 20.75 | 63.27 | 0.00 | 0.00 |
Maximum of Months | 618.30 | 298.86 | 507.53 | 222.40 | 300.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 115.99 | 490.08 | 196.60 | 38.39 | 158.20 | 0.00 | 0.00 |
February | 314.91 | 434.09 | 351.74 | 116.87 | 234.87 | 0.00 | 0.00 |
March | 654.56 | 338.41 | 615.68 | 264.15 | 351.53 | 0.00 | 0.00 |
April | 1143.76 | 277.82 | 980.32 | 499.10 | 481.22 | 0.00 | 0.00 |
May | 1504.97 | 276.16 | 1273.99 | 657.32 | 616.68 | 0.00 | 0.00 |
June | 1643.67 | 250.96 | 1396.10 | 819.39 | 576.70 | 0.00 | 0.00 |
July | 1742.64 | 275.45 | 1456.29 | 961.54 | 494.75 | 0.00 | 0.00 |
August | 1394.09 | 287.99 | 1167.46 | 742.71 | 424.76 | 0.00 | 0.00 |
September | 937.88 | 340.20 | 820.78 | 455.74 | 365.04 | 0.00 | 0.00 |
October | 523.50 | 322.00 | 484.68 | 226.31 | 258.38 | 0.00 | 0.00 |
November | 192.45 | 367.70 | 236.17 | 57.81 | 178.36 | 0.00 | 0.00 |
December | 103.05 | 494.67 | 169.84 | 40.94 | 128.90 | 0.00 | 0.00 |
Annual Sum or Average | 859.05 | 345.98 | 764.80 | 408.51 | 356.29 | 0.00 | 0.00 |
Minimum of Months | 103.05 | 250.96 | 169.84 | 38.39 | 128.90 | 0.00 | 0.00 |
Maximum of Months | 1742.64 | 494.67 | 1456.29 | 961.54 | 616.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2878.52 | 5918.71 | 646.27 | 145.05 | 501.21 | 0.00 | 0.00 |
February | 5810.98 | 5448.01 | 1153.41 | 409.31 | 744.10 | 0.00 | 0.00 |
March | 9563.83 | 3925.53 | 1965.88 | 852.18 | 1113.69 | 0.00 | 0.00 |
April | 15558.57 | 2806.85 | 3096.42 | 1571.85 | 1524.57 | 0.00 | 0.00 |
May | 20667.71 | 2469.93 | 3997.61 | 2043.89 | 1953.72 | 0.00 | 0.00 |
June | 21849.71 | 2206.46 | 4365.33 | 2538.25 | 1827.08 | 0.00 | 0.00 |
July | 22156.87 | 2501.24 | 4555.48 | 2988.04 | 1567.44 | 0.00 | 0.00 |
August | 17691.18 | 2783.11 | 3674.85 | 2329.16 | 1345.69 | 0.00 | 0.00 |
September | 12500.37 | 3092.10 | 2614.31 | 1457.82 | 1156.49 | 0.00 | 0.00 |
October | 7450.48 | 3111.27 | 1567.00 | 748.43 | 818.57 | 0.00 | 0.00 |
November | 3397.26 | 3822.87 | 771.73 | 206.65 | 565.08 | 0.00 | 0.00 |
December | 2367.70 | 5545.19 | 564.30 | 155.91 | 408.39 | 0.00 | 0.00 |
Annual Sum or Average | 11857.40 | 3628.21 | 2421.49 | 1292.71 | 1128.77 | 0.00 | 0.00 |
Minimum of Months | 2367.70 | 2206.46 | 564.30 | 145.05 | 408.39 | 0.00 | 0.00 |
Maximum of Months | 22156.87 | 5918.71 | 4555.48 | 2988.04 | 1953.72 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 96160995.52 | 0.797283E+09 | 0.251368E+09 | 55588881.50 | 0.195779E+09 | 0.00 | 0.00 |
February | 0.280775E+09 | 0.610363E+09 | 0.390583E+09 | 0.111899E+09 | 0.278684E+09 | 0.00 | 0.00 |
March | 0.559302E+09 | 0.516098E+09 | 0.615609E+09 | 0.158297E+09 | 0.457312E+09 | 0.00 | 0.00 |
April | 0.973017E+09 | 0.394903E+09 | 0.890019E+09 | 0.263599E+09 | 0.626419E+09 | 0.00 | 0.00 |
May | 0.135820E+10 | 0.387522E+09 | 0.118506E+10 | 0.380934E+09 | 0.804127E+09 | 0.00 | 0.00 |
June | 0.128939E+10 | 0.317980E+09 | 0.112605E+10 | 0.349392E+09 | 0.776662E+09 | 0.00 | 0.00 |
July | 0.165605E+10 | 0.346057E+09 | 0.135936E+10 | 0.595677E+09 | 0.763682E+09 | 0.00 | 0.00 |
August | 0.137692E+10 | 0.356912E+09 | 0.111862E+10 | 0.466238E+09 | 0.652384E+09 | 0.00 | 0.00 |
September | 0.990348E+09 | 0.445126E+09 | 0.875673E+09 | 0.342997E+09 | 0.532676E+09 | 0.00 | 0.00 |
October | 0.519348E+09 | 0.483412E+09 | 0.534721E+09 | 0.171585E+09 | 0.363135E+09 | 0.00 | 0.00 |
November | 0.163292E+09 | 0.582632E+09 | 0.272247E+09 | 57531799.00 | 0.214715E+09 | 0.00 | 0.00 |
December | 0.113348E+09 | 0.800476E+09 | 0.231567E+09 | 62106999.08 | 0.169460E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.937615E+10 | 0.603876E+10 | 0.885088E+10 | 0.301585E+10 | 0.583503E+10 | 0.00 | 0.00 |
Minimum of Months | 96160995.52 | 0.317980E+09 | 0.231567E+09 | 55588881.50 | 0.169460E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165605E+10 | 0.800476E+09 | 0.135936E+10 | 0.595677E+09 | 0.804127E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.310673E+09 | 0.131264E+10 | 0.526570E+09 | 0.102834E+09 | 0.423736E+09 | 0.00 | 0.00 |
February | 0.761834E+09 | 0.105016E+10 | 0.850921E+09 | 0.282724E+09 | 0.568197E+09 | 0.00 | 0.00 |
March | 0.175317E+10 | 0.906394E+09 | 0.164904E+10 | 0.707505E+09 | 0.941537E+09 | 0.00 | 0.00 |
April | 0.296463E+10 | 0.720111E+09 | 0.254100E+10 | 0.129367E+10 | 0.124732E+10 | 0.00 | 0.00 |
May | 0.403092E+10 | 0.739666E+09 | 0.341227E+10 | 0.176055E+10 | 0.165171E+10 | 0.00 | 0.00 |
June | 0.426039E+10 | 0.650485E+09 | 0.361868E+10 | 0.212386E+10 | 0.149482E+10 | 0.00 | 0.00 |
July | 0.466750E+10 | 0.737767E+09 | 0.390053E+10 | 0.257539E+10 | 0.132514E+10 | 0.00 | 0.00 |
August | 0.373392E+10 | 0.771345E+09 | 0.312694E+10 | 0.198926E+10 | 0.113767E+10 | 0.00 | 0.00 |
September | 0.243098E+10 | 0.881798E+09 | 0.212746E+10 | 0.118128E+10 | 0.946181E+09 | 0.00 | 0.00 |
October | 0.140215E+10 | 0.862442E+09 | 0.129818E+10 | 0.606139E+09 | 0.692037E+09 | 0.00 | 0.00 |
November | 0.498821E+09 | 0.953067E+09 | 0.612152E+09 | 0.149835E+09 | 0.462316E+09 | 0.00 | 0.00 |
December | 0.276018E+09 | 0.132492E+10 | 0.454910E+09 | 0.109651E+09 | 0.345259E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.270910E+11 | 0.109108E+11 | 0.241186E+11 | 0.128827E+11 | 0.112359E+11 | 0.00 | 0.00 |
Minimum of Months | 0.276018E+09 | 0.650485E+09 | 0.454910E+09 | 0.102834E+09 | 0.345259E+09 | 0.00 | 0.00 |
Maximum of Months | 0.466750E+10 | 0.132492E+10 | 0.390053E+10 | 0.257539E+10 | 0.165171E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.770982E+10 | 0.158527E+11 | 0.173096E+10 | 0.388510E+09 | 0.134245E+10 | 0.00 | 0.00 |
February | 0.140579E+11 | 0.131798E+11 | 0.279033E+10 | 0.990206E+09 | 0.180013E+10 | 0.00 | 0.00 |
March | 0.256158E+11 | 0.105141E+11 | 0.526541E+10 | 0.228249E+10 | 0.298292E+10 | 0.00 | 0.00 |
April | 0.403278E+11 | 0.727535E+10 | 0.802592E+10 | 0.407423E+10 | 0.395169E+10 | 0.00 | 0.00 |
May | 0.553564E+11 | 0.661545E+10 | 0.107072E+11 | 0.547435E+10 | 0.523285E+10 | 0.00 | 0.00 |
June | 0.566345E+11 | 0.571914E+10 | 0.113149E+11 | 0.657915E+10 | 0.473579E+10 | 0.00 | 0.00 |
July | 0.593449E+11 | 0.669932E+10 | 0.122014E+11 | 0.800316E+10 | 0.419823E+10 | 0.00 | 0.00 |
August | 0.473841E+11 | 0.745428E+10 | 0.984273E+10 | 0.623842E+10 | 0.360430E+10 | 0.00 | 0.00 |
September | 0.324010E+11 | 0.801472E+10 | 0.677630E+10 | 0.377867E+10 | 0.299763E+10 | 0.00 | 0.00 |
October | 0.199554E+11 | 0.833323E+10 | 0.419706E+10 | 0.200459E+10 | 0.219247E+10 | 0.00 | 0.00 |
November | 0.880569E+10 | 0.990887E+10 | 0.200033E+10 | 0.535644E+09 | 0.146468E+10 | 0.00 | 0.00 |
December | 0.634166E+10 | 0.148522E+11 | 0.151142E+10 | 0.417595E+09 | 0.109383E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.373935E+12 | 0.114419E+12 | 0.763640E+11 | 0.407670E+11 | 0.355970E+11 | 0.00 | 0.00 |
Minimum of Months | 0.634166E+10 | 0.571914E+10 | 0.151142E+10 | 0.388510E+09 | 0.109383E+10 | 0.00 | 0.00 |
Maximum of Months | 0.593449E+11 | 0.158527E+11 | 0.122014E+11 | 0.800316E+10 | 0.523285E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.936536E+09 | -848751178.8 | 0.00 | 0.00 | 744.00 | 0.00 | -87785013.4 | 58.99 | 0.00 | 0.00 |
February | 0.864019E+09 | -785126926.7 | 0.00 | 0.00 | 672.00 | 0.00 | -78891579.5 | 58.99 | 0.00 | 0.00 |
March | 0.993533E+09 | -907218384.2 | 0.00 | 0.00 | 744.00 | 0.00 | -86314788.8 | 58.99 | 0.00 | 0.00 |
April | 0.901415E+09 | -819657006.7 | 0.00 | 0.00 | 720.00 | 0.00 | -81758328.0 | 58.99 | 0.00 | 0.00 |
May | 0.901003E+09 | -820655364.3 | 0.00 | 0.00 | 744.00 | 0.00 | -80347372.6 | 58.99 | 0.00 | 0.00 |
June | 0.861499E+09 | -786765673.7 | 0.00 | 0.00 | 720.00 | 0.00 | -74733489.0 | 59.00 | 0.00 | 0.00 |
July | 0.813695E+09 | -739273911.4 | 0.00 | 0.00 | 744.00 | 0.00 | -74421075.7 | 59.00 | 0.00 | 0.00 |
August | 0.861310E+09 | -787239442.4 | 0.00 | 0.00 | 744.00 | 0.00 | -74070388.5 | 59.00 | 0.00 | 0.00 |
September | 0.815940E+09 | -741745089.5 | 0.00 | 0.00 | 720.00 | 0.00 | -74194962.3 | 59.00 | 0.00 | 0.00 |
October | 0.850736E+09 | -767152585.8 | 0.00 | 0.00 | 744.00 | 0.00 | -83583620.0 | 58.99 | 0.00 | 0.00 |
November | 0.849968E+09 | -766214721.0 | 0.00 | 0.00 | 720.00 | 0.00 | -83753736.9 | 58.99 | 0.00 | 0.00 |
December | 0.914710E+09 | -827203577.4 | 0.00 | 0.00 | 744.00 | 0.00 | -87506222.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.105644E+11 | -0.959700E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -967360577.1 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.813695E+09 | -907218384.2 | 0.00 | 0.00 | 672.00 | 0.00 | -87785013.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.993533E+09 | -739273911.4 | 0.00 | 0.00 | 744.00 | 0.00 | -74070388.5 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.88 | 0.70 | 31-JAN-12:30 | 91.08 | 0.00 | 0.00 | 0.00 | 68.92 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.83 | 0.50 | 26-FEB-11:20 | 116.76 | 0.00 | 0.00 | 0.00 | 279.16 | 0.00 | 0.00 | 20.33 |
March | 247.00 | 0.77 | 0.50 | 06-MAR-11:30 | 164.45 | 0.00 | 0.00 | 18.33 | 187.92 | 0.00 | 0.00 | 5.17 |
April | 379.50 | 0.73 | 0.50 | 02-APR-10:00 | 192.86 | 0.00 | 0.00 | 66.00 | 150.66 | 0.00 | 0.00 | 17.17 |
May | 427.83 | 0.71 | 0.50 | 01-MAY-10:20 | 234.12 | 0.00 | 0.00 | 120.17 | 180.85 | 0.00 | 0.00 | 66.00 |
June | 375.17 | 0.71 | 0.50 | 01-JUN-10:30 | 212.49 | 0.00 | 0.00 | 102.17 | 736.24 | 0.00 | 0.00 | 74.83 |
July | 471.00 | 0.76 | 0.50 | 01-JUL-11:39 | 182.49 | 0.00 | 0.00 | 87.33 | 143.10 | 0.00 | 0.00 | 45.33 |
August | 366.67 | 0.77 | 0.50 | 02-AUG-10:09 | 258.12 | 0.00 | 0.00 | 51.67 | 132.32 | 0.00 | 0.00 | 17.33 |
September | 301.17 | 0.75 | 0.50 | 01-SEP-12:09 | 791.88 | 0.00 | 0.00 | 40.17 | 135.74 | 0.00 | 0.00 | 4.00 |
October | 245.33 | 0.82 | 0.50 | 01-OCT-12:30 | 124.55 | 0.00 | 0.00 | 1.00 | 101.17 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.86 | 0.70 | 19-NOV-11:30 | 100.10 | 0.00 | 0.00 | 0.00 | 75.51 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.89 | 0.71 | 10-DEC-12:30 | 77.57 | 0.00 | 0.00 | 0.00 | 61.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.78 | 224.02 | 0.00 | 0.00 | 486.83 | 203.51 | 0.00 | 0.00 | 250.17 | ||
Minimum of Months | 160.33 | 0.71 | 0.50 | 77.57 | 0.00 | 0.00 | 0.00 | 61.54 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 471.00 | 0.89 | 0.71 | 791.88 | 0.00 | 0.00 | 120.17 | 736.24 | 0.00 | 0.00 | 74.83 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.69 | 0.50 | 02-JAN-10:00 | 147.31 | 10.88 | 0.00 | 42.00 | 121.97 | 13.89 | 0.00 | 15.00 |
February | 259.50 | 0.64 | 0.50 | 01-FEB-11:09 | 190.84 | 12.23 | 0.00 | 104.17 | 157.57 | 15.51 | 5.33 | 71.33 |
March | 247.00 | 0.60 | 0.50 | 01-MAR-09:50 | 757.52 | 14.69 | 14.50 | 194.67 | 733.25 | 17.23 | 45.00 | 151.50 |
April | 379.50 | 0.59 | 0.50 | 01-APR-08:09 | 567.28 | 14.84 | 17.33 | 256.33 | 542.92 | 17.70 | 92.67 | 211.83 |
May | 427.83 | 0.58 | 0.50 | 01-MAY-07:19 | 1219.09 | 16.14 | 39.67 | 313.50 | 311.49 | 17.98 | 99.17 | 258.00 |
June | 375.17 | 0.58 | 0.50 | 01-JUN-07:19 | 346.87 | 14.22 | 2.33 | 307.50 | 545.61 | 19.27 | 111.33 | 277.17 |
July | 471.00 | 0.62 | 0.50 | 01-JUL-06:10 | 294.22 | 12.56 | 2.33 | 264.00 | 1072.67 | 17.97 | 98.17 | 231.33 |
August | 366.67 | 0.61 | 0.50 | 01-AUG-06:19 | 272.07 | 13.07 | 0.33 | 259.83 | 542.18 | 17.52 | 75.83 | 211.50 |
September | 301.17 | 0.59 | 0.50 | 01-SEP-07:49 | 278.42 | 13.72 | 0.00 | 216.83 | 224.01 | 17.41 | 50.00 | 164.17 |
October | 245.33 | 0.63 | 0.50 | 01-OCT-08:30 | 207.76 | 12.37 | 0.00 | 146.17 | 545.00 | 17.58 | 38.83 | 102.17 |
November | 242.67 | 0.66 | 0.50 | 01-NOV-10:09 | 161.65 | 11.52 | 0.00 | 65.50 | 134.07 | 14.58 | 0.00 | 26.67 |
December | 160.33 | 0.72 | 0.50 | 01-DEC-10:20 | 129.85 | 10.56 | 0.00 | 15.83 | 106.81 | 13.92 | 0.00 | 4.33 |
Annual Sum or Average | 3714.00 | 0.62 | 423.22 | 13.36 | 76.50 | 2186.33 | 471.16 | 17.08 | 616.33 | 1725.00 | ||
Minimum of Months | 160.33 | 0.58 | 0.50 | 129.85 | 10.56 | 0.00 | 15.83 | 106.81 | 13.89 | 0.00 | 4.33 | |
Maximum of Months | 471.00 | 0.72 | 0.50 | 1219.09 | 16.14 | 39.67 | 313.50 | 1072.67 | 19.27 | 111.33 | 277.17 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.87 | 0.66 | 20-JAN-15:30 | 148.78 | 20.67 | 61.17 | 7.17 | 71.34 | 18.60 | 27.50 | 0.00 |
February | 259.50 | 0.83 | 0.61 | 19-FEB-15:30 | 289.57 | 22.88 | 115.50 | 25.17 | 100.07 | 20.03 | 84.50 | 0.00 |
March | 247.00 | 0.77 | 0.61 | 01-MAR-15:20 | 343.01 | 23.46 | 134.33 | 59.50 | 225.63 | 23.55 | 148.50 | 23.33 |
April | 379.50 | 0.76 | 0.61 | 01-APR-14:30 | 293.29 | 21.58 | 188.67 | 86.17 | 369.35 | 23.47 | 229.17 | 56.83 |
May | 427.83 | 0.74 | 0.61 | 02-MAY-14:09 | 301.82 | 21.10 | 216.83 | 123.33 | 305.60 | 22.15 | 261.83 | 79.17 |
June | 375.17 | 0.74 | 0.61 | 01-JUN-14:09 | 297.89 | 21.05 | 200.00 | 96.17 | 342.01 | 22.20 | 266.33 | 71.00 |
July | 471.00 | 0.76 | 0.61 | 01-JUL-13:39 | 261.96 | 19.87 | 186.00 | 103.00 | 409.69 | 21.12 | 239.00 | 95.17 |
August | 366.67 | 0.76 | 0.61 | 02-AUG-14:09 | 285.83 | 21.04 | 175.50 | 78.50 | 357.64 | 22.10 | 212.00 | 68.50 |
September | 301.17 | 0.74 | 0.61 | 01-SEP-14:50 | 471.10 | 24.26 | 172.00 | 97.83 | 390.44 | 24.71 | 190.67 | 64.17 |
October | 245.33 | 0.79 | 0.61 | 01-OCT-15:09 | 296.41 | 23.38 | 132.33 | 41.17 | 149.03 | 21.62 | 125.50 | 7.33 |
November | 242.67 | 0.87 | 0.65 | 04-NOV-15:30 | 152.16 | 19.73 | 53.33 | 5.00 | 77.02 | 18.98 | 40.33 | 0.00 |
December | 160.33 | 0.87 | 0.66 | 06-DEC-14:30 | 137.46 | 19.17 | 42.00 | 0.00 | 74.17 | 19.02 | 20.67 | 0.00 |
Annual Sum or Average | 3714.00 | 0.78 | 282.50 | 21.47 | 1677.67 | 723.00 | 271.06 | 21.70 | 1846.00 | 465.50 | ||
Minimum of Months | 160.33 | 0.74 | 0.61 | 137.46 | 19.17 | 42.00 | 0.00 | 71.34 | 18.60 | 20.67 | 0.00 | |
Maximum of Months | 471.00 | 0.87 | 0.66 | 471.10 | 24.26 | 216.83 | 123.33 | 409.69 | 24.71 | 266.33 | 95.17 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.609331E+10 | 24482.79 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.473846E+10 | 24482.79 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.377627E+10 | 24482.79 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.209521E+10 | 24482.79 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.412747E+09 | 24482.79 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 78348579.34 | 24482.79 | 07-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44290891.74 | 24482.79 | 28-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148580E+10 | 24482.79 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.359068E+10 | 24482.79 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.516458E+10 | 24482.79 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.609331E+10 | 24482.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.203447E+11 | 65241.56 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143064E+11 | 65241.56 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.681071E+10 | 65241.56 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182507E+10 | 63550.23 | 12-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.875332E+09 | 31373.28 | 16-OCT-05:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.873080E+10 | 65241.56 | 30-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170081E+11 | 65241.56 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.699011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.203447E+11 | 65241.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.405784E+11 | 54295.71 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.265399E+11 | 75330.50 | 19-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135425E+09 | 7273.92 | 05-MAR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.548963E+10 | 27692.31 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289502E+11 | 40972.20 | 25-DEC-01:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101694E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.405784E+11 | 75330.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 85819328.03 | 82156092.85 | 4222.17 | 27-APR-16:00 | 3920.68 | 0.00 |
May | 0.00 | 0.00 | 0.253932E+09 | 0.231083E+09 | 4623.78 | 15-MAY-16:00 | 4623.78 | 0.00 |
June | 0.00 | 0.00 | 0.594767E+09 | 0.577648E+09 | 6785.71 | 28-JUN-16:00 | 6549.44 | 0.00 |
July | 0.00 | 0.00 | 0.206214E+10 | 0.180697E+10 | 15900.60 | 31-JUL-05:55 | 11013.61 | 0.00 |
August | 0.00 | 0.00 | 0.304240E+10 | 0.264394E+10 | 16093.76 | 25-AUG-05:03 | 10560.41 | 0.00 |
September | 0.00 | 0.00 | 0.673427E+09 | 0.565991E+09 | 7131.90 | 14-SEP-16:00 | 6213.80 | 0.00 |
October | 0.00 | 0.00 | 7178557.08 | 7178555.83 | 1269.09 | 04-OCT-15:00 | 1269.09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.671967E+10 | 0.591496E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.304240E+10 | 0.264394E+10 | 16093.76 | 11013.61 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 29807428.05 | 29226950.71 | 3176.01 | 28-JUN-15:00 | 3176.01 | 0.00 |
July | 0.00 | 0.00 | 0.100884E+10 | 0.878734E+09 | 41935.07 | 31-JUL-18:02 | 35143.48 | 0.00 |
August | 0.00 | 0.00 | 0.203756E+10 | 0.177229E+10 | 41866.04 | 13-AUG-12:53 | 35369.33 | 0.00 |
September | 0.00 | 0.00 | 373924.39 | 293342.86 | 351.23 | 14-SEP-15:00 | 273.55 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.307658E+10 | 0.268055E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203756E+10 | 0.177229E+10 | 41935.07 | 35369.33 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.446795E+09 | 0.06 | 229.57 | 01-JAN-00:03 | 0.08 |
February | 0.283298E+09 | 0.04 | 229.57 | 01-FEB-00:05 | 0.08 |
March | 7056851.35 | 0.00 | 229.57 | 05-MAR-02:50 | 0.08 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.141596E+09 | 0.02 | 229.57 | 13-NOV-00:40 | 0.08 |
December | 0.413955E+09 | 0.05 | 229.57 | 01-DEC-00:05 | 0.08 |
Annual Sum or Average | 0.129270E+10 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.446795E+09 | 0.06 | 229.57 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109460E+10 | 0.46 | 1046.25 | 02-JAN-10:50 | 0.92 |
February | 0.999885E+09 | 0.44 | 1046.25 | 01-FEB-15:50 | 0.92 |
March | 0.115383E+10 | 0.40 | 1046.25 | 01-MAR-10:40 | 0.92 |
April | 0.106044E+10 | 0.38 | 1046.25 | 01-APR-10:10 | 0.92 |
May | 0.108633E+10 | 0.37 | 1046.25 | 05-MAY-12:00 | 0.91 |
June | 0.107908E+10 | 0.37 | 1046.25 | 03-JUN-13:40 | 0.92 |
July | 0.103825E+10 | 0.34 | 1046.25 | 07-JUL-07:30 | 0.92 |
August | 0.112355E+10 | 0.37 | 1046.25 | 01-AUG-15:00 | 0.91 |
September | 0.103681E+10 | 0.35 | 1046.25 | 08-SEP-14:50 | 0.92 |
October | 0.105416E+10 | 0.36 | 1046.25 | 04-OCT-13:50 | 0.92 |
November | 0.102316E+10 | 0.37 | 1046.25 | 01-NOV-11:00 | 0.91 |
December | 0.107587E+10 | 0.39 | 1046.25 | 02-DEC-11:20 | 0.92 |
Annual Sum or Average | 0.128260E+11 | 0.38 | |||
Minimum of Months | 0.999885E+09 | 0.34 | 1046.25 | 0.91 | |
Maximum of Months | 0.115383E+10 | 0.46 | 1046.25 | 0.92 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135568E+10 | 0.56 | 2027.08 | 02-JAN-06:01 | 0.89 |
February | 0.113372E+10 | 0.51 | 2027.08 | 07-FEB-06:01 | 0.89 |
March | 0.106192E+10 | 0.43 | 2027.08 | 06-MAR-06:01 | 0.89 |
April | 0.855704E+09 | 0.27 | 1974.53 | 12-APR-05:01 | 0.89 |
May | 0.834831E+09 | 0.21 | 810.83 | 01-MAY-06:10 | 0.54 |
June | 0.834831E+09 | 0.21 | 810.83 | 28-JUN-13:40 | 0.54 |
July | 0.809395E+09 | 0.20 | 1909.17 | 31-JUL-17:12 | 0.86 |
August | 0.876168E+09 | 0.22 | 2027.08 | 10-AUG-17:10 | 0.88 |
September | 0.802723E+09 | 0.20 | 810.83 | 14-SEP-16:00 | 0.53 |
October | 0.828063E+09 | 0.23 | 1021.27 | 19-OCT-06:05 | 0.62 |
November | 0.101492E+10 | 0.44 | 2027.08 | 30-NOV-06:01 | 0.89 |
December | 0.126821E+10 | 0.55 | 2027.08 | 01-DEC-06:01 | 0.89 |
Annual Sum or Average | 0.116762E+11 | 0.34 | |||
Minimum of Months | 0.802723E+09 | 0.20 | 810.83 | 0.53 | |
Maximum of Months | 0.135568E+10 | 0.56 | 2027.08 | 0.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.109460E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.999885E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.115383E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.107931E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.113955E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.120334E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.146185E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.175169E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.117494E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.105573E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.102316E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.107587E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.142138E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.999885E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.175169E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.135568E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.113372E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.106192E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.855704E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.834831E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.842579E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.105807E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.138538E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.802818E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.828063E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.101492E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.126821E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.124419E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.802818E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.138538E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109460E+10 | 0.00 | 0.609331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.999885E+09 | 0.00 | 0.473846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115383E+10 | 0.00 | 0.377627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106044E+10 | 85819328.03 | 0.209521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108633E+10 | 0.253932E+09 | 0.412747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107908E+10 | 0.594767E+09 | 78348579.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103825E+10 | 0.206214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112355E+10 | 0.304240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103681E+10 | 0.673427E+09 | 44290891.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105416E+10 | 7178557.08 | 0.148580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102316E+10 | 0.00 | 0.359068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107587E+10 | 0.00 | 0.516458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128260E+11 | 0.671967E+10 | 0.274797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.999885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115383E+10 | 0.304240E+10 | 0.609331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135568E+10 | 0.00 | 0.203447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113372E+10 | 0.00 | 0.143064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106192E+10 | 0.00 | 0.681071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.855704E+09 | 0.00 | 0.182507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.834831E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.834831E+09 | 29807428.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.809395E+09 | 0.978297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.876168E+09 | 0.201128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.802723E+09 | 373924.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.828063E+09 | 0.00 | 0.875332E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101492E+10 | 0.00 | 0.873080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126821E+10 | 0.00 | 0.170081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116762E+11 | 0.301976E+10 | 0.699011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.802723E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135568E+10 | 0.201128E+10 | 0.203447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.109460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.999885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106044E+10 | 0.00 | 0.00 | 0.00 | 18868528.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108633E+10 | 0.00 | 0.00 | 0.00 | 53217630.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107908E+10 | 0.00 | 0.00 | 0.00 | 0.124257E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103825E+10 | 0.00 | 0.00 | 0.00 | 0.423602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112355E+10 | 0.00 | 0.00 | 0.00 | 0.628147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103681E+10 | 0.00 | 0.00 | 0.00 | 0.138129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105416E+10 | 0.00 | 0.00 | 0.00 | 1576889.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128260E+11 | 0.00 | 0.00 | 0.00 | 0.138780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.999885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115383E+10 | 0.00 | 0.00 | 0.00 | 0.628147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.855704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.834831E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.834831E+09 | 0.00 | 0.00 | 0.00 | 7747828.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.809395E+09 | 0.00 | 0.00 | 0.00 | 0.248678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.876168E+09 | 0.00 | 0.00 | 0.00 | 0.509209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.802723E+09 | 0.00 | 0.00 | 0.00 | 95268.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.828063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116762E+11 | 0.00 | 0.00 | 0.00 | 0.765730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.802723E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135568E+10 | 0.00 | 0.00 | 0.00 | 0.509209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194703E+10 | 0.00 | 0.00 | 0.12 |
February | 27751278.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158243E+10 | 0.00 | 0.00 | 0.13 |
March | 0.123130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147818E+10 | 0.00 | 0.00 | 0.13 |
April | 0.364935E+09 | 3317628.77 | 0.00 | 64707.77 | 0.00 | 0.838521E+09 | 89428584.87 | 0.00 | 0.14 |
May | 0.853472E+09 | 3499083.77 | 0.00 | 595762.21 | 0.00 | 46819920.83 | 0.641058E+09 | 0.00 | 0.24 |
June | 0.354868E+09 | 3870431.60 | 0.00 | 2174924.01 | 0.00 | 0.00 | 0.190710E+10 | 0.00 | 0.44 |
July | 30984503.52 | 48053014.73 | 0.00 | 3904198.26 | 0.00 | 0.00 | 0.242346E+10 | 0.00 | 0.60 |
August | 18480468.15 | 0.120671E+09 | 0.00 | 3677174.93 | 0.00 | 0.00 | 0.231890E+10 | 0.00 | 0.58 |
September | 0.351397E+09 | 4185891.16 | 0.00 | 2258783.29 | 0.00 | 0.00 | 0.191858E+10 | 0.00 | 0.43 |
October | 0.535162E+09 | 0.00 | 0.00 | 109411.75 | 0.00 | 0.641983E+09 | 0.200325E+09 | 0.00 | 0.15 |
November | 79696034.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143176E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185014E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.273988E+10 | 0.183597E+09 | 0.00 | 12784962.22 | 0.00 | 0.981687E+10 | 0.949886E+10 | 0.00 | 0.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.853472E+09 | 0.120671E+09 | 0.00 | 3904198.26 | 0.00 | 0.194703E+10 | 0.242346E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363597E+10 | 0.00 | 0.00 | 0.17 |
February | 0.176434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217755E+10 | 0.00 | 0.00 | 0.18 |
March | 0.315540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535576E+09 | 0.00 | 0.00 | 0.19 |
April | 0.287338E+10 | 0.00 | 0.00 | 0.00 | 43355675.52 | 76161238.42 | 0.00 | 0.00 | 0.18 |
May | 0.347429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
June | 0.354097E+10 | 0.00 | 0.00 | 56689.62 | 0.00 | 0.00 | 52258201.08 | 0.00 | 0.19 |
July | 0.275861E+10 | 18556640.05 | 0.00 | 1151277.23 | 0.00 | 0.00 | 0.720560E+09 | 0.00 | 0.21 |
August | 0.267339E+10 | 58906346.90 | 0.00 | 1582792.39 | 0.00 | 0.00 | 0.628961E+09 | 0.00 | 0.23 |
September | 0.359709E+10 | 0.00 | 0.00 | 42052.81 | 0.00 | 0.00 | 0.116083E+09 | 0.00 | 0.19 |
October | 0.299919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49600605.05 | 0.00 | 0.00 | 0.17 |
November | 0.239139E+10 | 0.00 | 0.00 | 0.00 | 112182.58 | 0.111018E+10 | 0.00 | 0.00 | 0.17 |
December | 0.169793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285099E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.322497E+11 | 77462986.95 | 0.00 | 2832812.06 | 43467858.10 | 0.104360E+11 | 0.151786E+10 | 0.00 | 0.19 |
Minimum of Months | 0.132371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.359709E+10 | 58906346.90 | 0.00 | 1582792.39 | 43355675.52 | 0.363597E+10 | 0.720560E+09 | 0.00 | 0.23 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.918846E+11 | 0.364354E+11 | 0.00 | 0.690671E+10 | 0.221158E+11 |
February | 0.239993E+12 | 0.307628E+11 | 0.00 | 0.555208E+10 | 0.152950E+11 |
March | 0.488887E+12 | 0.294035E+11 | 0.00 | 0.529228E+10 | 0.506281E+10 |
April | 0.796886E+12 | 0.298410E+11 | 0.00 | 0.419582E+10 | 0.196724E+10 |
May | 0.108283E+13 | 0.393215E+11 | 0.00 | 0.501274E+10 | 0.498867E+09 |
June | 0.110312E+13 | 0.381207E+11 | 0.00 | 0.585356E+10 | 0.794069E+09 |
July | 0.118789E+13 | 0.379544E+11 | 0.00 | 0.587968E+10 | 0.374325E+10 |
August | 0.934930E+12 | 0.370736E+11 | 0.00 | 0.548480E+10 | 0.621732E+10 |
September | 0.652482E+12 | 0.245839E+11 | 0.00 | 0.598127E+10 | 0.832746E+09 |
October | 0.377331E+12 | 0.291014E+11 | 0.00 | 0.442637E+10 | 0.114795E+10 |
November | 0.123820E+12 | 0.248800E+11 | 0.00 | 0.501292E+10 | 0.724269E+10 |
December | 0.583872E+11 | 0.279266E+11 | 0.00 | 0.639905E+10 | 0.175192E+11 |
Annual Sum or Average | 0.713845E+13 | 0.385405E+12 | 0.00 | 0.659973E+11 | 0.824369E+11 |
Minimum of Months | 0.583872E+11 | 0.245839E+11 | 0.00 | 0.419582E+10 | 0.498867E+09 |
Maximum of Months | 0.118789E+13 | 0.393215E+11 | 0.00 | 0.690671E+10 | 0.221158E+11 |