Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 10:42:57
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 555.97 | 114.98 | 114.98 |
Net Site Energy | 555.97 | 114.98 | 114.98 |
Total Source Energy | 1381.43 | 285.71 | 285.71 |
Net Source Energy | 1381.43 | 285.71 | 285.71 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 182.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 35.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 84.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 30.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 373.86 | 182.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 182.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 35.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 84.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 7.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 22.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 182.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 35.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 84.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 30.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 24.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 30.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 18.77 | 37.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 77.32 | 37.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 30.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 18.77 | 37.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 77.32 | 37.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 373.865 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 373.865 | 100.00 |
Total On-Site and Utility Electric Sources | 373.865 | 100.00 |
Total Electricity End Uses | 373.865 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 38.67 |
Time Setpoint Not Met During Occupied Cooling | 19.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3039.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:42 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.9682 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.5521 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.9682 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.5521 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.8362 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-JUL-14:50 | 12-FEB-06:10 | - | - | - | - | - | - | - | - | - | - | 27-JUL-11:00 |
Heating | 0.00 | 227326.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14245.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4686.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4412.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1703.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 35082.85 | 227326.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 227326.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14245.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 4686.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2106.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1703.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 197.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 113.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 195.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 96.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 77.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1184.03 | 197.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 40.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 55.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 244.88 | 40.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 40.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 55.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 244.88 | 40.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.08 |
ZONE2 FINE STORAGE DIRECT AIR | 2.62 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 3.26 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 3.26 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 128684.64 |
PSZ-OFFICE HEATING COIL | 27072.24 |
PSZ-FINE STORAGE HEATING COIL | 85629.32 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 128684.65 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.00 | 1.08 |
PSZ-FINE STORAGE | 2.62 | 2.62 | 2.62 | 2.62 | 2.62 | 2.62 | 1.00 | 1.00 | 2.62 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.08 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.62 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.08 | 1192.32 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.62 | 2806.53 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 0.710768 | 21202.20 | 27072.24 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.62 | 2.62 | 2.62 | 1.73 | 65130.57 | 85629.32 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.08 | 0.538461 | 0.717947 | 21202.20 | 10601.10 | 0.782130 | 0.782130 |
PSZ-FINE STORAGE COOLING COIL | 2.62 | 1.31 | 1.75 | 65130.57 | 32565.28 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.968 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.042 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.552 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1650.627 | 6.968 | 129.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1650.627 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 11383.888 | 3.552 | 164.984 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11383.888 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5892 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.044 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.697 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4892 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.53319589E-11 | 0.95168195E-16 | 0.18684196E-15 | 0.0000000 |
5 | 1 | -5.2159738 | 0.43009049E-04 | -0.27188221E-04 | 0.68723469E-11 |
6 | 0 | 5.8052090 | 0.58919217 | 0.58926237 | |
7 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
8 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
9 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
10 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
11 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
12 | 4 | 0.65556131E-12 | 0.57298371E-15 | -0.14028959E-14 | 0.12439065E-15 |
13 | 3 | -0.34087882E-03 | 0.75102955E-06 | -0.49042705E-04 | 0.12583838E-12 |
14 | 2 | 1.6337693 | 0.17263784E-01 | 1.0601096 | -0.65347397E-04 |
15 | 1 | -7.2734424 | 0.46143774 | -16.581274 | 0.31301327 |
16 | 0 | 6.4190060 | 0.30028979 | 16.300205 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.0441747 | 2.0441747 | 2.0441747 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.14028959E-14 | 0.57298371E-15 | 0.65556131E-12 | 0.12439065E-15 |
85 | 3 | -0.49042705E-04 | 0.75102955E-06 | -0.34087882E-03 | 0.12583838E-12 |
86 | 2 | 1.0601096 | 0.17263784E-01 | 1.6337693 | -0.65347397E-04 |
87 | 1 | -16.581274 | 0.46143774 | -7.2734424 | 0.31301327 |
88 | 0 | 16.300205 | 0.30028979 | 6.4190060 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.423_SHGC_SOUTH_0.249 | 34 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
2 | NONRESWINDOW_U_0.423_SHGC_NORTH_0.249 | 35 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
3 | NONRESWINDOW_U_0.423_SHGC_EAST_0.249 | 36 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
4 | NONRESWINDOW_U_0.423_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
5 | SKYLIGHT_U_0.55_SHGC_0.3 | 38 | 1 | VerySmooth | 3.127 | 3.127 | 1.000 | 0.301 | ||
6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | 39 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.15759E-002 | 0.21195 | 0.55558 | 0.55558 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 7.71143E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.12500 | 0.12500 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.043 | 0.303 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.867 | 0.549 | 0.401 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.4325E-005 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.1213E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.5495E-005 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.1648E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.3186E-005 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5731E-004 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5724E-005 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5867E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5663E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4272E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3174E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5473E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4083E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4773E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3414E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4540E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5176E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1794E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9295E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2353E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.0865E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0883E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8792E-004 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6675E-005 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3526E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4381E-005 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6465E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6793E-005 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2366E-004 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0015E-005 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3392E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0724E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7428E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8883E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6923E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0102E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7403E-004 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8144E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9718E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6272E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8825E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.2827E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0139E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.3587E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0670E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.3977E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7955E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4789E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0144E-003 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4512E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2157E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5656E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3464E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4522E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3679E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4861E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4549E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3806E-005 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8584E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6167E-005 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1741E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9847E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1133E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6508E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8407E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.1768E-005 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7846E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8307E-005 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5420E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6526E-005 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5808E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1684E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9400E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9667E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.9896E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.2158E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4345E-004 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4107E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6286E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1734E-005 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9610E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2370E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6358E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5918E-004 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8910E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.6135E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3102E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8162E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.1428E-005 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.2914E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1141E-005 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7177E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0431E-005 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7903E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0760E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8446E-004 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2604E-005 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1438E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9150E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1840E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8780E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7960E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7398E-005 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1825E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1072E-005 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6508E-004 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7928E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0513E-004 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7373E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7890E-004 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5431E-005 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2422E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3309E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8674E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8869E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0497E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6348E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7121E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6539E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8575E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8763E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3236E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4714E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2714E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2212E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9843E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8490E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9024E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8739E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9859E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4228E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5807E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5457E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7930E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1930E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0816E-004 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2331E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1121E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2105E-005 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4112E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2602E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4660E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0086E-004 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6683E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1025E-004 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6983E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7851E-005 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5353E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2892E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3113E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6584E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6220E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4367E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4378E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0238E-005 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5351E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7595E-005 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6957E-004 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0110E-004 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5535E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2489E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1405E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5478E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5757E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0915E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3942E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3630E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.0566E-005 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8531E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3016E-005 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3550E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5602E-005 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5596E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9340E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6858E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9157E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3580E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8889E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4663E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3312E-005 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7208E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2451E-005 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1998E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0005E-004 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9800E-004 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8668E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3888E-004 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3137E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3364E-004 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9640E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0528E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0802E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1177E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9925E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2288E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1753E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2524E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7247E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1639E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0155E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5954E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4783E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0242E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0338E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9289E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8860E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6660E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2279E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3570E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1841E-005 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4018E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6561E-005 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7482E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0918E-004 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2207E-004 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7729E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7749E-004 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6903E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3175E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5698E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4446E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9082E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2762E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9705E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9198E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4426E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4832E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8107E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3202E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6413E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9890E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9907E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2753E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5921E-004 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0868E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4300E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4980E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1369E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4154E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6719E-005 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6187E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9776E-005 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0914E-004 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1202E-005 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6693E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9477E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8000E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5987E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4402E-004 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2754E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1106E-005 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8798E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6916E-005 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3438E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6992E-005 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1223E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3850E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4819E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9331E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2543E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4426E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7640E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5650E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6214E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8399E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3943E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6366E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4589E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3276E-005 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5060E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1151E-005 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3532E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0737E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6007E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0827E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1377E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2447E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3246E-005 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1131E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7708E-005 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0439E-004 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8079E-005 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5629E-005 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6788E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6014E-005 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4498E-005 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9474E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2148E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2473E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0968E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8113E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2392E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3989E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8568E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9804E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2864E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7812E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3583E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0248E-004 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4769E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5152E-005 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0984E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2826E-005 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4316E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9761E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.7233E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5435E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.2449E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.4877E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1641E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.7866E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1636E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.7250E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.5144E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.3078E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.8592E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.2270E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.6484E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1270E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3974E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9162E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.1886E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2200E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.7388E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.6241E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.3437E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2429E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9254E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1056E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1963E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.3004E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.7427E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.3696E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.3393E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2428E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9254E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10516.00694 | 12619.20832 | 0.89743 | 1.07692 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.19667 | 1.44711E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10022.78212 | 12027.33854 | 0.29176 | 0.35011 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30000 | 2.29779E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 32852.71796 | 39423.26155 | 2.18567 | 2.62281 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 34.21000 | 1.44729E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 31254.63185 | 37505.55822 | 0.76643 | 0.91971 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -6.30000 | 2.29779E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 107237.20599 | 128684.64718 | 2.71747 | 3.26096 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16066.26 | 1.07692 | 1.07692 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 11003.84 | 0.35011 | 0.35011 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 48707.12 | 2.62281 | 2.62281 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 37057.68 | 0.91971 | 0.91971 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07692 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.62281 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.26096 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 3.26096 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 128684.64118 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 128684.64718 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07692 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07692 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07692 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07692 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07692 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.07692 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.62281 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.62281 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.62281 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.62281 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.62281 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.62281 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.07692 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.62281 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07692 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07692 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1192.32268 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07692 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07692 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07692 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71077 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07692 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53846 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71795 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21202.20000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10601.10000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78213 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78213 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21202.20000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27072.24417 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 27072.24417 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.62281 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.62281 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2806.52857 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.62281 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.62281 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.62281 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.73105 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.62281 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.31140 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.74854 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 65130.57000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32565.28500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 65130.57000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 85629.32469 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 85629.32469 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 20366.0 | 11.79 | 11.53 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 63091.9 | 12.06 | 11.79 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 8.9225430999E-002 | 0.1486963361 | Pass | Pass | 2.2660234033E-002 | 0.1275547403 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2226535540 | 0.2409038831 | Pass | Pass | 1.4807896130 | 3.9629116909 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.7806627686E-002 | 3.9967714341E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 9783.75 | 476.19 | 0.00 | 22.32 | 228.86 | 10511.13 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.545 | 0.589 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.423_SHGC_WEST_0.249 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.404 | 0.250 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.423_SHGC_WEST_0.249 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.404 | 0.250 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.423_SHGC_NORTH_0.249 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.404 | 0.250 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.423_SHGC_NORTH_0.249 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.404 | 0.250 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.074 | 0.429 | 0.370 | |||||||||||||||||
North Total or Average | 6.51 | 2.404 | 0.250 | 0.250 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.210 | 0.443 | 0.380 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.9682 | 236.88 | 1650.63 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 33.57 | 0.0000 | Y | 10.40 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 18.76 | 0.0000 | Y | 36.45 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.5521 | 3204.84 | 11383.89 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 17.74 | 0.0000 | Y | 37.91 |
Interior Lighting Total | 4.8362 | 4835.13 | 23383.49 | 84.77 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1650.63 | 478.68 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1650.63 | 165.06 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 41.77 | 41.77 | 0.97 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.77 | 62.77 | 50.73 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.77 | 49.33 | 10.11 | |
Exterior Lighting Total | 5520.82 | 61.81 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21202.20 | 16582.88 | 4619.32 | 0.78 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 65130.57 | 45661.74 | 19468.83 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 20366.0 | 11.79 | 11.53 | ||||
PSZ-FINE STORAGE COOLING COIL | 63091.9 | 12.06 | 11.79 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 128684.64 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 27072.24 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 85629.32 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.26 | 302.98 | 92.91 | 1.00 | 3.32 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1192.32 | 1107.16 | 1.00 | 1.38 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.62 | 2806.53 | 1070.05 | 1.00 | 1.28 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10516.01 | 12619.21 | 53.27 | 0.897 | 1.077 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 23.90 | 23.90 | 0.00853 | 33.20 | 0.01447 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 32852.72 | 39423.26 | 28.29 | 2.186 | 2.623 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 26.70 | 26.70 | 0.00902 | 34.21 | 0.01447 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 34.71 | 0.01455 | 34.30 | 0.01447 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10022.78 | 12027.34 | 50.77 | 0.292 | 0.350 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00734 | -6.30 | 0.00230 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 31254.63 | 37505.56 | 26.92 | 0.766 | 0.920 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00597 | -6.30 | 0.00230 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 107237.21 | 128684.65 | 40.15 | 2.717 | 3.261 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00524 | -6.30 | 0.00230 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.08 | 1.08 | 0.35 | 0.35 | 1.0769 | 1.0769 | 1.0769 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.62 | 2.62 | 0.92 | 0.92 | 2.6228 | 2.6228 | 2.6228 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 128684.641 | 128684.641 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 128684.64 | 128684.64 | 3.260963 | 10.00 | 7.03 | 0.00524485 | 43.33 | 21.72 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 10.00 | 0.00524485 | 66.5297 | 128684.65 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 21202.200 | 16582.877 | 1.076920 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 10601.10 | 9016.35 | 0.717947 | 25.73 | 17.11 | 0.00909535 | 12.00 | 10.94 | 0.00800000 | 33.32 | 0.01447128 | 23.26 | 14.2468 | 23.90 | 0.00853090 | 44.5455 | 10511.40 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 27072.244 | 27072.244 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 27072.24 | 27072.24 | 1.076921 | 18.45 | 12.45 | 0.00686321 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 9.4979 | 21.10 | 0.00734234 | 45.5375 | 10022.78 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 65130.570 | 45661.740 | 2.622810 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 32565.28 | 25928.52 | 1.748540 | 28.83 | 18.77 | 0.00990862 | 12.00 | 10.94 | 0.00800000 | 34.30 | 0.01447309 | 23.52 | 24.2895 | 26.70 | 0.00902595 | 39.8720 | 32829.82 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 85629.325 | 85629.325 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 85629.32 | 85629.32 | 2.622808 | 12.01 | 8.13 | 0.00537574 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 16.1930 | 15.55 | 0.00597046 | 52.5527 | 31254.63 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 128684.641 | 128684.641 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 3.260963 | 3.78590128 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 128684.64 | 128684.64 | 1.0000 | 3.78590128 | 3.260963 | 10.00 | 7.03 | 0.00524485 | 23259.5 | 43.33 | 21.72 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 128684.64 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 10.00 | 0.00524485 | 10.00 | 0.00524485 | 66.5297 | 128684.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21202.200 | 16582.877 | 1.076920 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7478 | 1004.8586 | 1.1610 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.076921 | 1.25028021 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | Sensible | 10601.10 | 9016.35 | 1.0000 | 0.83351924 | 0.717947 | 25.73 | 17.11 | 0.00909535 | 49033.4 | 12.00 | 10.94 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10601.10 | 33.32 | 0.01447128 | 23.26 | 0.10228463 | 14.2468 | 23.90 | 0.00853090 | 23.90 | 0.00853090 | 44.5455 | 10511.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27072.244 | 27072.244 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.076921 | 1.25028021 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 27072.24 | 27072.24 | 1.0000 | 1.25028021 | 1.076921 | 18.45 | 12.45 | 0.00686321 | 35941.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27072.24 | -6.30 | 0.00229779 | -6.30 | 0.10228463 | 9.4979 | 21.05 | 0.00734234 | 21.10 | 0.00734234 | 45.5375 | 10022.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 65130.570 | 45661.740 | 2.622810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2596 | 1004.8586 | 1.1610 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.622808 | 3.04501859 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 32565.28 | 25928.52 | 1.0000 | 2.03001392 | 1.748540 | 28.83 | 18.77 | 0.00990862 | 54281.6 | 12.00 | 10.94 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32565.28 | 34.30 | 0.01447309 | 23.52 | 0.42471127 | 24.2895 | 26.70 | 0.00902595 | 26.70 | 0.00902595 | 39.8720 | 32829.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 85629.325 | 85629.325 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.622808 | 3.04501859 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 85629.32 | 85629.32 | 1.0000 | 3.04501859 | 2.622808 | 12.01 | 8.13 | 0.00537574 | 25637.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85629.32 | -6.30 | 0.00229779 | -6.30 | 0.42471127 | 16.1930 | 15.55 | 0.00597046 | 15.55 | 0.00597046 | 52.5527 | 31254.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialEnthalpy | 0.10 | 1.08 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialEnthalpy | 0.42 | 2.62 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2628.17 | 2135.83 | 1323.17 |
ZONE2 FINE STORAGE | 3100.67 | 3226.83 | 2750.83 |
ZONE3 BULK STORAGE | 3250.67 | 3335.33 | 2998.17 |
Facility | 3281.00 | 3466.17 | 3039.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 41.50 | 20.17 | 32.50 | 19.83 |
ZONE2 FINE STORAGE | 170.17 | 74.83 | 11.83 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 205.83 | 95.00 | 38.67 | 19.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.506 | 0.305 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.527 | 0.246 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.130 | 0.000 | 0.656 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.53 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1824814.21 | 0.00 | 1824814.21 | 1813741.60 | 3638555.81 | 3225648.14 | 5697.38 | 2487.92 | 574.71 | 0.29 |
ZONE2 FINE STORAGE | 5553818.41 | 0.00 | 5553818.41 | 6743274.88 | 12297093.29 | 13393694.68 | 5719.88 | 2700.14 | 339.98 | 2.95 |
ZONE3 BULK STORAGE | 0.00 | 0.13E+09 | 0.13E+09 | 33321292.93 | 0.17E+09 | 30805497.77 | 7428.77 | 36.33 | 1294.90 | 4988.28 |
Total Facility | 7378632.62 | 0.13E+09 | 0.14E+09 | 41878309.41 | 0.18E+09 | 47424840.58 | 7964.00 | 3000.33 | 2131.62 | 4988.36 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1394 | 0.0000 | 0.1394 | 0.0843 | 0.2237 | 0.1023 | 573.67 | 2487.92 | 574.41 |
ZONE2 FINE STORAGE | 0.4233 | 0.0000 | 0.4233 | 0.1991 | 0.6223 | 0.4247 | 598.83 | 2700.14 | 337.03 |
ZONE3 BULK STORAGE | 0.0000 | 6.0974 | 6.0974 | 1.2609 | 7.3583 | 0.9768 | 2821.08 | 18.58 | 796.34 |
Total Facility | 0.5626 | 6.0974 | 6.6600 | 1.5443 | 8.2043 | 1.5038 | 2840.00 | 2982.58 | 1630.18 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2459548.95 | 0.00 | 2459548.95 | 3225648.14 | 5695.21 | 0.33 | 3064.46 | 0.29 |
PSZ-FINE STORAGE | 7485781.73 | 0.00 | 7485781.73 | 13393694.68 | 5716.21 | 0.33 | 3043.45 | 2.95 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1878 | 0.0000 | 0.1878 | 0.1023 | 571.50 | 0.33 | 3064.16 |
PSZ-FINE STORAGE | 0.5705 | 0.0000 | 0.5705 | 0.4247 | 595.17 | 0.33 | 3040.50 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2820.93 | 250.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2930.29 | 127.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2069 | 0.3987 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6642 | 1.0240 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 446 |
Defaulted Fields | 391 |
Fields with Defaults | 1172 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 373.86 | 1550.86 | 01-JAN-10:50 | 35082.85 | 08-JUL-14:50 |
Electricity:Building | 228.83 | 1069.86 | 01-JAN-10:50 | 19550.83 | 07-JUL-08:10 |
Electricity:Zone:ZONE1 OFFICE | 39.57 | 520.87 | 01-JAN-00:10 | 2845.83 | 30-OCT-07:10 |
Electricity:SpaceType:GENERAL | 221.28 | 1069.86 | 01-JAN-10:50 | 18934.03 | 30-OCT-08:10 |
InteriorLights:Electricity | 84.77 | 599.99 | 01-JAN-10:50 | 8898.85 | 30-OCT-08:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.40 | 51.00 | 01-JAN-00:10 | 1010.77 | 30-OCT-07:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 84.77 | 599.99 | 01-JAN-10:50 | 8898.85 | 30-OCT-08:10 |
LightsWired:InteriorLights:Electricity | 84.77 | 599.99 | 01-JAN-10:50 | 8898.85 | 30-OCT-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.40 | 51.00 | 01-JAN-00:10 | 1010.77 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 84.77 | 599.99 | 01-JAN-10:50 | 8898.85 | 30-OCT-08:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 36.45 | 285.70 | 16-JUN-17:10 | 3787.01 | 30-OCT-08:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 36.45 | 285.70 | 16-JUN-17:10 | 3787.01 | 30-OCT-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 36.45 | 285.70 | 16-JUN-17:10 | 3787.01 | 30-OCT-08:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 152.81 | 249.02 | 01-JAN-10:50 | 13435.78 | 07-JUL-08:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 37.91 | 249.02 | 01-JAN-10:50 | 4108.03 | 30-OCT-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 37.91 | 249.02 | 01-JAN-10:50 | 4108.03 | 30-OCT-08:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 30.39 | 0.00 | 01-JAN-01:20 | 4526.07 | 07-JUL-16:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 7.55 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-MAY-13:00 |
Ventilation (simple):Fans:Electricity | 7.55 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-MAY-13:00 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 7.55 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-MAY-13:00 |
ElectricityPurchased:Facility | 373.86 | 1550.86 | 01-JAN-10:50 | 35082.85 | 08-JUL-14:50 |
ElectricityPurchased:Plant | 373.86 | 1550.86 | 01-JAN-10:50 | 35082.85 | 08-JUL-14:50 |
Cogeneration:ElectricityPurchased | 373.86 | 1550.86 | 01-JAN-10:50 | 35082.85 | 08-JUL-14:50 |
General:Cogeneration:ElectricityPurchased | 373.86 | 1550.86 | 01-JAN-10:50 | 35082.85 | 08-JUL-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 373.86 | 1550.86 | 01-JAN-10:50 | 35082.85 | 08-JUL-14:50 |
ElectricityNet:Plant | 373.86 | 1550.86 | 01-JAN-10:50 | 35082.85 | 08-JUL-14:50 |
Cogeneration:ElectricityNet | 373.86 | 1550.86 | 01-JAN-10:50 | 35082.85 | 08-JUL-14:50 |
General:Cogeneration:ElectricityNet | 373.86 | 1550.86 | 01-JAN-10:50 | 35082.85 | 08-JUL-14:50 |
Electricity:HVAC | 58.71 | 0.00 | 01-JAN-01:20 | 16807.24 | 08-JUL-15:10 |
General:Fans:Electricity | 22.84 | 0.00 | 01-JAN-01:20 | 2973.62 | 13-FEB-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 35.87 | 0.00 | 01-JAN-00:10 | 14621.86 | 08-JUL-15:10 |
General:Cooling:Electricity | 35.87 | 0.00 | 01-JAN-00:10 | 14621.86 | 08-JUL-15:10 |
ExteriorLights:Electricity | 61.81 | 0.00 | 01-JAN-07:50 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.81 | 0.00 | 01-JAN-07:50 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 24.52 | 481.00 | 02-JAN-06:30 | 2121.03 | 30-JAN-12:10 |
WaterSystems:Electricity | 24.52 | 481.00 | 02-JAN-06:30 | 2121.03 | 30-JAN-12:10 |
Water Heater:WaterSystems:Electricity | 24.52 | 481.00 | 02-JAN-06:30 | 2121.03 | 30-JAN-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 182.10 | 0.00 | 01-JAN-01:20 | 227326.08 | 12-FEB-06:10 |
NaturalGas:HVAC | 182.10 | 0.00 | 01-JAN-01:20 | 227326.08 | 12-FEB-06:10 |
Heating:NaturalGas | 182.10 | 0.00 | 01-JAN-01:20 | 227326.08 | 12-FEB-06:10 |
General:Heating:NaturalGas | 182.10 | 0.00 | 01-JAN-01:20 | 227326.08 | 12-FEB-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 517.94 | 0.00 | 01-JAN-01:20 | 357478.95 | 12-FEB-06:10 |
EnergyTransfer:Building | 236.66 | 0.00 | 01-JAN-01:20 | 179224.83 | 12-FEB-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 50.48 | 0.00 | 01-JAN-00:10 | 20205.30 | 13-FEB-06:10 |
Heating:EnergyTransfer | 130.79 | 0.00 | 01-JAN-01:20 | 179224.83 | 12-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 15.24 | 0.00 | 01-JAN-00:10 | 20205.30 | 13-FEB-06:10 |
General:Heating:EnergyTransfer | 130.79 | 0.00 | 01-JAN-01:20 | 179224.83 | 12-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 15.24 | 0.00 | 01-JAN-00:10 | 20205.30 | 13-FEB-06:10 |
Cooling:EnergyTransfer | 105.87 | 0.00 | 01-JAN-00:10 | 34256.68 | 07-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 35.24 | 0.00 | 01-JAN-00:10 | 10135.22 | 17-JUL-05:10 |
General:Cooling:EnergyTransfer | 105.87 | 0.00 | 01-JAN-00:10 | 34256.68 | 07-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 35.24 | 0.00 | 01-JAN-00:10 | 10135.22 | 17-JUL-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 113.10 | 0.00 | 01-JAN-00:40 | 45297.09 | 12-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 42.46 | 0.00 | 01-JAN-00:40 | 45297.09 | 12-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 42.46 | 0.00 | 01-JAN-00:40 | 45297.09 | 12-FEB-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 70.63 | 0.00 | 01-JAN-00:10 | 26009.26 | 16-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 70.63 | 0.00 | 01-JAN-00:10 | 26009.26 | 16-JUL-14:40 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 73.09 | 0.00 | 01-JAN-00:10 | 129024.37 | 12-FEB-05:50 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 73.09 | 0.00 | 01-JAN-00:10 | 129024.37 | 12-FEB-05:50 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 73.09 | 0.00 | 01-JAN-00:10 | 129024.37 | 12-FEB-05:50 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 281.28 | 0.00 | 01-JAN-01:20 | 178254.12 | 12-FEB-06:10 |
HeatingCoils:EnergyTransfer | 135.20 | 0.00 | 01-JAN-01:20 | 178254.12 | 12-FEB-06:10 |
CoolingCoils:EnergyTransfer | 146.08 | 0.00 | 01-JAN-00:10 | 54858.61 | 03-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 15.240 | -35.238 | 0.000 | 0.000 | 9.719 | 10.402 | 29.165 | 9.414 | 0.000 | 1.719 | 0.000 | 0.000 | -5.982 | 0.000 | -14.984 | -19.454 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 42.463 | -70.629 | 0.000 | 0.000 | 23.033 | 36.452 | 0.000 | 29.808 | 0.000 | 2.994 | 0.001 | 0.000 | -11.178 | 0.000 | -49.456 | -3.487 |
ZONE3 BULK STORAGE | 73.087 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 50.448 | 37.915 | 107.344 | 608.908 | 0.000 | 9.393 | 0.008 | 0.000 | -130.432 | 0.000 | -398.918 | -357.743 |
Total Facility | 73.087 | 0.000 | 57.703 | -105.867 | 0.000 | 0.000 | 83.199 | 84.769 | 136.508 | 648.130 | 0.000 | 14.105 | 0.009 | 0.000 | -147.592 | 0.000 | -463.358 | -380.685 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 15-SEP-05:02 | 0.00 | 0.00 | 0.00 | -22126.68 | 0.00 | 0.00 | 89.33 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 22129.41 | 0.00 | -436.14 | 0.00 | -257.43 | 0.00 |
ZONE2 FINE STORAGE | 11-JUN-14:23 | 0.00 | 0.00 | 0.00 | -54834.44 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 5580.94 | 0.00 | 1810.15 | 47143.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-JUL-16:33 | 0.00 | 0.00 | 0.00 | -63246.37 | 0.00 | 0.00 | 0.00 | 599.99 | 469.88 | 63996.35 | 0.00 | 989.46 | 9961.22 | 0.00 | 0.00 | 0.00 | -12770.52 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 13-FEB-06:11 | 0.00 | 0.00 | 27881.59 | 0.00 | 0.00 | 0.00 | 118.54 | 302.02 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -849.11 | 0.00 | -3135.68 | -24867.88 |
ZONE2 FINE STORAGE | 11-FEB-18:42 | 0.00 | 0.00 | 87845.06 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1361.31 | 0.00 | -15767.81 | -71015.91 |
ZONE3 BULK STORAGE | 12-FEB-05:47 | 129029.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43612.97 | 0.00 | -85421.21 | -493.09 |
Total Facility | 12-FEB-06:02 | 128994.44 | 0.00 | 91157.01 | 0.00 | 0.00 | 0.00 | 0.00 | 849.01 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -26887.68 | 0.00 | -106696.14 | -87886.52 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0769 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0769 | 0.0950 | 1.0000 | Not calculated | 0.1023 | 0.0950 | ||
PSZ-FINE STORAGE | 2.6228 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6228 | 0.1619 | 1.0000 | Not calculated | 0.4247 | 0.1619 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0769 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0769 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0950 | ||
PSZ-FINE STORAGE | 2.6228 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6228 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1619 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0769 | 1.0769 | 1.0769 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6228 | 2.6228 | 2.6228 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0769 | 1.0769 | 1.0769 | 1.0769 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6228 | 2.6228 | 2.6228 | 2.6228 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0769 | 1.0769 | 1.0769 | No | 0.1023 | 0.2921 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6228 | 2.6228 | 2.6228 | No | 0.4247 | 0.4618 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0769 | 1.0769 | 1.0769 | 1.0769 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6228 | 2.6228 | 2.6228 | 2.6228 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 38.67 |
Number of hours cooling loads not met | 19.83 |
Number of hours not met | 58.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 182.10 | 227326.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 35.87 | 14621.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 84.77 | 8898.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.81 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 7.55 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 22.84 | 2973.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.52 | 2121.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 373.86 |
Natural Gas | 0.00 | 182.10 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 555.97 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 17.53 |
Space Heating | 0.00 |
Space Cooling | 7.42 |
Fans (All) | 6.29 |
Service Water Heating | 5.07 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 77.32 |
Subtotal | 77.32 |
Natural Gas [MJ/m2] | |
Space Heating | 37.66 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 37.66 |
Subtotal | 37.66 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.25 |
Space Heating | 32.75 |
Space Cooling | 6.45 |
Fans (All) | 5.47 |
Service Water Heating | 4.41 |
Receptacle Equipment | 24.55 |
Miscellaneous | 11.12 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7388.83 | 1365.83 | 5.33 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 6488.33 | 2271.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5621.67 | 2386.00 | 752.33 | 0.00 | 0.00 |
Min | 5621.67 | 1365.83 | 0.00 | 0.00 | 0.00 |
Max | 7388.83 | 2386.00 | 752.33 | 0.00 | 0.00 |
Average | 6499.61 | 2007.83 | 252.56 | 0.00 | 0.00 |
Sum | 19498.83 | 6023.50 | 757.67 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 55470.50 | 27248.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 114369.00 | 51309.17 | 25514.83 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 114369.00 | 51309.17 | 25514.83 | 0.00 | 0.00 |
Average | 67622.17 | 26185.89 | 8504.94 | 0.00 | 0.00 |
Sum | 202866.50 | 78557.67 | 25514.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 6813.50 | 1946.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 5617.83 | 3142.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5275.00 | 3293.00 | 192.00 | 0.00 | 0.00 |
Min | 5275.00 | 1946.50 | 0.00 | 0.00 | 0.00 |
Max | 6813.50 | 3293.00 | 192.00 | 0.00 | 0.00 |
Average | 5902.11 | 2793.89 | 64.00 | 0.00 | 0.00 |
Sum | 17706.33 | 8381.67 | 192.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32086.33 | 940.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 50150.50 | 32568.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 109464.17 | 72724.33 | 9004.50 | 0.00 | 0.00 |
Min | 32086.33 | 940.67 | 0.00 | 0.00 | 0.00 |
Max | 109464.17 | 72724.33 | 9004.50 | 0.00 | 0.00 |
Average | 63900.33 | 35411.17 | 3001.50 | 0.00 | 0.00 |
Sum | 191701.00 | 106233.50 | 9004.50 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:42:57
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6140964.60 | 771.09 | 21-JAN-15:40 | 9.60 | 4.99 | 0.498716E+09 | 679.10 | 31-JAN-15:00 | 20.00 | 13.58 |
February | 46189441.89 | 1630.27 | 28-FEB-16:40 | 23.70 | 12.80 | 0.470923E+09 | 768.96 | 28-FEB-16:40 | 23.70 | 12.80 |
March | 0.542645E+09 | 4421.57 | 30-MAR-16:00 | 27.80 | 17.47 | 0.598208E+09 | 769.01 | 30-MAR-14:50 | 27.80 | 17.47 |
April | 0.191772E+10 | 5994.93 | 17-APR-16:00 | 28.90 | 16.41 | 0.611067E+09 | 769.02 | 19-APR-12:39 | 25.00 | 17.82 |
May | 0.392895E+10 | 19593.27 | 20-MAY-05:02 | 17.38 | 14.91 | 0.657667E+09 | 769.03 | 23-MAY-13:00 | 22.80 | 20.55 |
June | 0.640399E+10 | 21250.93 | 07-JUN-05:02 | 13.80 | 12.13 | 0.660272E+09 | 769.07 | 05-JUN-15:50 | 13.80 | 12.13 |
July | 0.687672E+10 | 19049.69 | 03-JUL-05:01 | 17.88 | 16.41 | 0.635063E+09 | 769.06 | 03-JUL-15:30 | 29.40 | 21.81 |
August | 0.770738E+10 | 19028.03 | 26-AUG-05:01 | 21.70 | 17.15 | 0.685938E+09 | 769.06 | 07-AUG-10:09 | 21.70 | 17.15 |
September | 0.529148E+10 | 22129.11 | 15-SEP-05:02 | 14.90 | 12.38 | 0.634804E+09 | 769.06 | 08-SEP-15:09 | 14.90 | 12.38 |
October | 0.207638E+10 | 11695.47 | 19-OCT-05:03 | 20.92 | 20.92 | 0.606432E+09 | 769.03 | 19-OCT-15:09 | 23.98 | 18.47 |
November | 0.382128E+09 | 2778.37 | 06-NOV-16:00 | 20.60 | 10.48 | 0.529059E+09 | 768.99 | 04-NOV-15:00 | 20.60 | 10.48 |
December | 59584362.72 | 796.85 | 14-DEC-11:00 | 10.60 | 7.34 | 0.506688E+09 | 768.28 | 12-DEC-15:39 | 10.60 | 7.34 |
Annual Sum or Average | 0.352393E+11 | 0.709484E+10 | ||||||||
Minimum of Months | 6140964.60 | 771.09 | 9.60 | 4.99 | 0.470923E+09 | 679.10 | 10.60 | 7.34 | ||
Maximum of Months | 0.770738E+10 | 22129.11 | 28.90 | 20.92 | 0.685938E+09 | 769.07 | 29.40 | 21.81 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103483E+10 | 5239.69 | 27-JAN-14:00 | 2.80 | -2.4 | 0.692420E+09 | 1238.75 | 31-JAN-15:20 | 20.73 | 13.19 |
February | 0.719394E+09 | 5271.55 | 02-FEB-14:10 | 2.70 | -1.3 | 0.725497E+09 | 1697.33 | 28-FEB-15:00 | 23.30 | 12.53 |
March | 0.146540E+10 | 5185.26 | 18-MAR-08:70 | 2.98 | -0.5 | 0.115090E+10 | 2226.06 | 30-MAR-15:00 | 27.80 | 17.47 |
April | 0.175790E+10 | 17999.88 | 16-APR-14:30 | 28.05 | 15.93 | 0.145993E+10 | 2246.86 | 17-APR-14:09 | 28.90 | 16.59 |
May | 0.470640E+10 | 41789.60 | 19-MAY-17:43 | 29.60 | 18.93 | 0.179964E+10 | 2246.94 | 20-MAY-15:30 | 28.05 | 18.93 |
June | 0.136135E+11 | 54834.31 | 11-JUN-14:23 | 31.65 | 20.47 | 0.191484E+10 | 2246.95 | 20-JUN-14:09 | 30.28 | 22.54 |
July | 0.172191E+11 | 53896.16 | 04-JUL-15:02 | 31.28 | 22.90 | 0.184753E+10 | 2247.01 | 07-JUL-14:30 | 34.70 | 23.71 |
August | 0.182117E+11 | 53454.74 | 27-AUG-15:53 | 31.70 | 21.48 | 0.200199E+10 | 2247.02 | 18-AUG-15:00 | 31.70 | 21.48 |
September | 0.737178E+10 | 48279.00 | 08-SEP-17:06 | 30.32 | 22.02 | 0.179834E+10 | 2246.95 | 06-SEP-15:09 | 30.32 | 22.02 |
October | 0.190315E+10 | 7012.63 | 11-OCT-15:00 | 27.20 | 20.13 | 0.141417E+10 | 2246.81 | 02-OCT-12:50 | 27.20 | 20.13 |
November | 0.135082E+10 | 5345.23 | 20-NOV-12:00 | 3.90 | 1.60 | 0.955709E+09 | 1830.32 | 06-NOV-15:39 | 3.90 | 1.60 |
December | 0.127922E+10 | 5763.67 | 02-DEC-10:05 | 0.78 | -2.6 | 0.771623E+09 | 1447.29 | 12-DEC-14:50 | 22.80 | 16.32 |
Annual Sum or Average | 0.706332E+11 | 0.165326E+11 | ||||||||
Minimum of Months | 0.719394E+09 | 5185.26 | 0.78 | -2.6 | 0.692420E+09 | 1238.75 | 3.90 | 1.60 | ||
Maximum of Months | 0.182117E+11 | 54834.31 | 31.70 | 22.90 | 0.200199E+10 | 2247.02 | 34.70 | 23.71 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 | 4.97 | 0.863176E+09 | 1999.03 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 | 0.109833E+10 | 3482.89 | 28-FEB-15:39 | 23.87 | 12.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.51 | 0.242927E+10 | 4632.08 | 30-MAR-15:39 | 27.80 | 17.34 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.82 | 0.343966E+10 | 6125.18 | 17-APR-15:20 | 28.90 | 16.41 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 | 0.464176E+10 | 6905.28 | 19-MAY-14:50 | 30.60 | 18.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 | 0.555457E+10 | 8317.01 | 06-JUN-15:20 | 34.23 | 22.26 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 | 0.555030E+10 | 9097.65 | 08-JUL-13:50 | 36.02 | 24.42 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 | 0.597133E+10 | 8660.76 | 18-AUG-15:00 | 35.00 | 23.11 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.46 | 0.479969E+10 | 7357.55 | 07-SEP-15:39 | 31.70 | 23.45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 | 0.319969E+10 | 5687.31 | 02-OCT-14:00 | 26.70 | 20.22 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.60 | 0.186310E+10 | 3675.36 | 06-NOV-15:20 | 20.60 | 10.48 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 | 0.114183E+10 | 2458.70 | 12-DEC-14:50 | 22.80 | 16.32 |
Annual Sum or Average | 0.00 | 0.405527E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.80 | 1.51 | 0.863176E+09 | 1999.03 | 20.37 | 10.48 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 21.87 | 0.597133E+10 | 9097.65 | 36.02 | 24.42 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.552714E+10 | 27770.21 | 09-JAN-06:12 | -2.6 |
February | 0.379276E+10 | 27881.57 | 13-FEB-06:11 | -5.6 |
March | 0.109056E+10 | 27367.18 | 07-MAR-06:42 | 5.10 |
April | 0.235521E+09 | 27266.05 | 06-APR-05:01 | 0.18 |
May | 28888339.06 | 767.35 | 11-MAY-06:15 | 8.53 |
June | 4492246.48 | 697.69 | 08-JUN-06:10 | 12.07 |
July | 187152.26 | 250.85 | 29-JUL-06:10 | 17.80 |
August | 36102.21 | 120.34 | 25-AUG-06:05 | 18.40 |
September | 7834863.18 | 712.94 | 14-SEP-06:10 | 12.30 |
October | 0.216783E+09 | 27245.88 | 31-OCT-05:01 | 8.30 |
November | 0.119587E+10 | 27514.40 | 22-NOV-06:12 | -3.3 |
December | 0.314019E+10 | 27600.21 | 04-DEC-06:22 | -3.0 |
Annual Sum or Average | 0.152402E+11 | |||
Minimum of Months | 36102.21 | 120.34 | -5.6 | |
Maximum of Months | 0.552714E+10 | 27881.57 | 18.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187228E+11 | 87616.04 | 07-JAN-05:22 | -0.9 |
February | 0.108479E+11 | 87843.90 | 11-FEB-18:42 | -5.9 |
March | 0.548422E+09 | 20582.81 | 22-MAR-23:40 | 5.20 |
April | 0.252053E+09 | 1743.77 | 04-APR-16:20 | 25.60 |
May | 97329393.32 | 1242.48 | 02-MAY-07:00 | 15.00 |
June | 60436363.07 | 1219.29 | 26-JUN-06:10 | 23.30 |
July | 23865174.92 | 1257.63 | 14-JUL-06:04 | 23.48 |
August | 20738259.28 | 1289.07 | 05-AUG-06:10 | 22.80 |
September | 81484606.46 | 1162.52 | 20-SEP-07:00 | 16.10 |
October | 0.125969E+09 | 1271.24 | 13-OCT-06:50 | 5.60 |
November | 0.179046E+10 | 86124.77 | 22-NOV-06:01 | -3.3 |
December | 0.989138E+10 | 86196.85 | 17-DEC-04:12 | 0.40 |
Annual Sum or Average | 0.424628E+11 | |||
Minimum of Months | 20738259.28 | 1162.52 | -5.9 | |
Maximum of Months | 0.187228E+11 | 87843.90 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423283E+11 | 92198.76 | 07-JAN-18:57 | -5.6 |
February | 0.253291E+11 | 129030.31 | 12-FEB-05:47 | -12.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.542966E+10 | 40262.85 | 03-DEC-07:00 | -3.3 |
Annual Sum or Average | 0.730871E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.1 | |
Maximum of Months | 0.423283E+11 | 129030.31 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.914040E+09 | 998.94 | 03-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.822244E+09 | 1007.27 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.917534E+09 | 1000.27 | 21-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.844268E+09 | 989.57 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.846558E+09 | 954.16 | 24-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.832085E+09 | 945.45 | 23-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.816900E+09 | 966.22 | 29-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.872303E+09 | 983.12 | 24-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.856809E+09 | 997.60 | 30-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.896151E+09 | 1010.77 | 30-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.864466E+09 | 1009.37 | 04-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.918945E+09 | 999.25 | 06-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.104023E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.816900E+09 | 945.45 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.918945E+09 | 1010.77 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.340260E+10 | 3677.35 | 11-JAN-09:09 | 0.00 | 0.00 |
February | 0.303894E+10 | 3750.63 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.316713E+10 | 3647.06 | 18-MAR-08:09 | 0.00 | 0.00 |
April | 0.289227E+10 | 3561.64 | 08-APR-08:09 | 0.00 | 0.00 |
May | 0.280402E+10 | 3404.58 | 06-MAY-08:09 | 0.00 | 0.00 |
June | 0.274575E+10 | 3345.09 | 08-JUN-08:09 | 0.00 | 0.00 |
July | 0.272437E+10 | 3393.35 | 07-JUL-08:09 | 0.00 | 0.00 |
August | 0.287553E+10 | 3436.73 | 26-AUG-08:09 | 0.00 | 0.00 |
September | 0.296337E+10 | 3544.52 | 25-SEP-08:09 | 0.00 | 0.00 |
October | 0.327529E+10 | 3787.01 | 30-OCT-08:09 | 0.00 | 0.00 |
November | 0.319894E+10 | 3640.79 | 04-NOV-08:09 | 0.00 | 0.00 |
December | 0.336357E+10 | 3657.86 | 19-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.364518E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.272437E+10 | 3345.09 | 0.00 | 0.00 | |
Maximum of Months | 0.340260E+10 | 3787.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.352583E+10 | 3774.88 | 11-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.319499E+10 | 4033.93 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.327946E+10 | 3656.06 | 18-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.296128E+10 | 3432.45 | 01-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.293447E+10 | 3079.89 | 24-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.285338E+10 | 2932.80 | 08-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.285404E+10 | 3138.01 | 29-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.304055E+10 | 3344.94 | 24-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.303311E+10 | 3571.32 | 30-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.339420E+10 | 4108.03 | 30-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.326725E+10 | 3798.04 | 04-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.357630E+10 | 3784.96 | 04-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.379149E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.285338E+10 | 2932.80 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.357630E+10 | 4108.03 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.914040E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303481E+10 |
February | 0.127628E+10 | 0.822244E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5381597.26 | 0.234772E+10 |
March | 0.149825E+10 | 0.917534E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16883638.25 | 0.151366E+10 |
April | 0.138726E+10 | 0.844268E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58735848.33 | 0.998057E+09 |
May | 0.144276E+10 | 0.846558E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134504E+09 | 0.670363E+09 |
June | 0.144276E+10 | 0.832085E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428801E+09 | 0.337499E+09 |
July | 0.138726E+10 | 0.816900E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417144E+09 | 0.243119E+09 |
August | 0.149825E+10 | 0.872303E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466739E+09 | 0.175451E+09 |
September | 0.138726E+10 | 0.856809E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154766E+09 | 0.428351E+09 |
October | 0.138726E+10 | 0.896151E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31829760.78 | 0.126129E+10 |
November | 0.133177E+10 | 0.864466E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4042983.85 | 0.165327E+10 |
December | 0.138726E+10 | 0.918945E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232017E+10 |
Annual Sum or Average | 0.168137E+11 | 0.104023E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171883E+10 | 0.149838E+11 |
Minimum of Months | 0.127628E+10 | 0.816900E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175451E+09 |
Maximum of Months | 0.149825E+10 | 0.918945E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466739E+09 | 0.303481E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.340260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18003603.29 | 0.956693E+10 |
February | 0.300332E+10 | 0.303894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59244779.70 | 0.738197E+10 |
March | 0.352563E+10 | 0.316713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77915951.44 | 0.429269E+10 |
April | 0.326447E+10 | 0.289227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56354547.50 | 0.348583E+10 |
May | 0.339505E+10 | 0.280402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108148E+09 | 0.279588E+10 |
June | 0.339505E+10 | 0.274575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777271E+09 | 0.169312E+10 |
July | 0.326447E+10 | 0.272437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820844E+09 | 0.124002E+10 |
August | 0.352563E+10 | 0.287553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824978E+09 | 0.939871E+09 |
September | 0.326447E+10 | 0.296337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151917E+09 | 0.186845E+10 |
October | 0.326447E+10 | 0.327529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15807228.08 | 0.427112E+10 |
November | 0.313390E+10 | 0.319894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73867426.55 | 0.454350E+10 |
December | 0.326447E+10 | 0.336357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9774060.09 | 0.737634E+10 |
Annual Sum or Average | 0.395654E+11 | 0.364518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299413E+10 | 0.494557E+11 |
Minimum of Months | 0.300332E+10 | 0.272437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9774060.09 | 0.939871E+09 |
Maximum of Months | 0.352563E+10 | 0.340260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824978E+09 | 0.956693E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.352583E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988629E+09 | 0.283306E+11 |
February | 0.690763E+10 | 0.319499E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130195E+10 | 0.217993E+11 |
March | 0.810895E+10 | 0.327946E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839772E+09 | 0.180478E+11 |
April | 0.750829E+10 | 0.296128E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304581E+09 | 0.172495E+11 |
May | 0.780862E+10 | 0.293447E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1006987.71 | 0.156142E+11 |
June | 0.780862E+10 | 0.285338E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23325795.40 | 0.117810E+11 |
July | 0.750829E+10 | 0.285404E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10188641.69 | 0.937805E+10 |
August | 0.810895E+10 | 0.304055E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13995921.62 | 0.826655E+10 |
September | 0.750829E+10 | 0.303311E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 207917.94 | 0.121402E+11 |
October | 0.750829E+10 | 0.339420E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67165272.07 | 0.197878E+11 |
November | 0.720796E+10 | 0.326725E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.885725E+09 | 0.164527E+11 |
December | 0.750829E+10 | 0.357630E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777749E+09 | 0.191015E+11 |
Annual Sum or Average | 0.910005E+11 | 0.379149E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521429E+10 | 0.197949E+12 |
Minimum of Months | 0.690763E+10 | 0.285338E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 207917.94 | 0.826655E+10 |
Maximum of Months | 0.810895E+10 | 0.357630E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130195E+10 | 0.283306E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 998.94 | 03-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 8402.52 | 27-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1007.27 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 295.33 | 26-FEB-13:00 | 9483.24 | 13-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1000.27 | 21-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.98 | 30-MAR-16:10 | 5679.46 | 22-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 989.57 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1119.24 | 17-APR-16:10 | 5694.57 | 06-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 954.16 | 24-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1787.22 | 19-MAY-16:10 | 3818.81 | 11-MAY-06:05 |
June | 1680.92 | 01-JUN-07:10 | 945.45 | 23-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3047.67 | 06-JUN-17:00 | 3081.73 | 08-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 966.22 | 29-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2720.98 | 07-JUL-16:10 | 1564.09 | 28-JUL-17:00 |
August | 1680.92 | 01-AUG-07:10 | 983.12 | 24-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3123.56 | 01-AUG-17:00 | 1421.71 | 25-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 997.60 | 30-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1894.44 | 08-SEP-16:10 | 3026.51 | 14-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 1010.77 | 30-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1468.04 | 10-OCT-16:10 | 5332.37 | 26-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1009.37 | 04-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.44 | 19-NOV-15:00 | 7218.88 | 21-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 999.25 | 06-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7407.10 | 18-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 945.45 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.71 | |||||
Maximum of Months | 1680.92 | 1010.77 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 3123.56 | 9483.24 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3677.35 | 11-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.54 | 19-JAN-23:00 | 17963.59 | 07-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 3750.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1609.13 | 26-FEB-13:00 | 20069.64 | 11-FEB-17:40 |
March | 3955.50 | 01-MAR-08:09 | 3647.06 | 18-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1254.71 | 11-MAR-16:10 | 9027.59 | 22-MAR-06:10 |
April | 3955.50 | 01-APR-07:10 | 3561.64 | 08-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.92 | 04-APR-17:30 | 8286.62 | 05-APR-15:15 |
May | 3955.50 | 01-MAY-07:10 | 3404.58 | 06-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1669.57 | 19-MAY-16:00 | 5989.87 | 10-MAY-08:00 |
June | 3955.50 | 01-JUN-07:10 | 3345.09 | 08-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4925.50 | 06-JUN-15:10 | 5760.43 | 07-JUN-07:00 |
July | 3955.50 | 01-JUL-07:10 | 3393.35 | 07-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2966.79 | 10-JUL-15:10 | 4380.74 | 28-JUL-17:00 |
August | 3955.50 | 01-AUG-07:10 | 3436.73 | 26-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4187.45 | 01-AUG-17:00 | 2499.19 | 28-AUG-07:00 |
September | 3955.50 | 01-SEP-07:10 | 3544.52 | 25-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.92 | 08-SEP-16:00 | 4180.63 | 28-SEP-17:00 |
October | 3955.50 | 02-OCT-07:10 | 3787.01 | 30-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 975.68 | 10-OCT-16:00 | 9675.03 | 25-OCT-08:00 |
November | 3955.50 | 01-NOV-07:10 | 3640.79 | 04-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.35 | 19-NOV-15:00 | 9451.21 | 20-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 3657.86 | 19-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.16 | 24-DEC-10:00 | 16024.65 | 02-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3345.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.16 | 2499.19 | ||||
Maximum of Months | 3955.50 | 3787.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4925.50 | 20069.64 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3774.88 | 11-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14670.38 | 19-JAN-16:00 | 60088.91 | 07-JAN-10:00 |
February | 9097.65 | 01-FEB-08:09 | 4033.93 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13560.70 | 16-FEB-17:00 | 59957.17 | 11-FEB-17:00 |
March | 9097.65 | 01-MAR-08:09 | 3656.06 | 18-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10006.23 | 11-MAR-16:00 | 37763.61 | 18-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 3432.45 | 01-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5840.27 | 04-APR-15:00 | 49320.70 | 05-APR-11:00 |
May | 9097.65 | 01-MAY-07:10 | 3079.89 | 24-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.84 | 06-MAY-16:00 | 28054.12 | 10-MAY-08:00 |
June | 9097.65 | 01-JUN-07:10 | 2932.80 | 08-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1209.49 | 06-JUN-11:45 | 30140.40 | 30-JUN-15:55 |
July | 9097.65 | 01-JUL-07:10 | 3138.01 | 29-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 473.35 | 22-JUL-10:45 | 23125.87 | 28-JUL-14:00 |
August | 9097.65 | 01-AUG-07:10 | 3344.94 | 24-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1004.07 | 01-AUG-17:00 | 15194.49 | 31-AUG-09:00 |
September | 9097.65 | 01-SEP-07:10 | 3571.32 | 30-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.33 | 25-SEP-14:00 | 20409.57 | 28-SEP-14:00 |
October | 9097.65 | 02-OCT-07:10 | 4108.03 | 30-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2889.73 | 10-OCT-16:00 | 40770.86 | 25-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 3798.04 | 04-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12126.49 | 27-NOV-13:10 | 36458.21 | 20-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 3784.96 | 04-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9495.67 | 11-DEC-14:00 | 45994.22 | 02-DEC-08:70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2932.80 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 174.33 | 15194.49 | |||||
Maximum of Months | 9097.65 | 4108.03 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14670.38 | 60088.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 771.09 | 21-JAN-15:40 | 1680.92 | 840.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.51 |
February | 1630.27 | 28-FEB-16:40 | 1680.92 | 639.21 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 |
March | 4421.57 | 30-MAR-16:00 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 491.37 | 0.00 |
April | 5994.93 | 17-APR-16:00 | 1680.92 | 642.58 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 276.72 | 0.00 |
May | 19593.27 | 20-MAY-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21250.93 | 07-JUN-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.98 |
July | 19049.69 | 03-JUL-05:01 | 1479.21 | 407.96 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.75 |
August | 19028.03 | 26-AUG-05:01 | 1479.21 | 407.96 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.95 |
September | 22129.11 | 15-SEP-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.43 |
October | 11695.47 | 19-OCT-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.00 |
November | 2778.37 | 06-NOV-16:00 | 1680.92 | 659.79 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.30 |
December | 796.85 | 14-DEC-11:00 | 1680.92 | 874.17 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 771.09 | 739.61 | 203.98 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22129.11 | 1680.92 | 874.17 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 491.37 | 831.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5239.69 | 27-JAN-14:00 | 3955.50 | 3170.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.28 |
February | 5271.55 | 02-FEB-14:10 | 3955.50 | 2620.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4002.79 |
March | 5185.26 | 18-MAR-08:70 | 3955.50 | 3647.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3620.48 |
April | 17999.88 | 16-APR-14:30 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.54 | 0.00 |
May | 41789.60 | 19-MAY-17:43 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 912.20 | 0.00 |
June | 54834.31 | 11-JUN-14:23 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1810.15 | 0.00 |
July | 53896.16 | 04-JUL-15:02 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.41 | 0.00 |
August | 53454.74 | 27-AUG-15:53 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1215.62 | 0.00 |
September | 48279.00 | 08-SEP-17:06 | 0.00 | 2043.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 812.20 | 0.00 |
October | 7012.63 | 11-OCT-15:00 | 3955.50 | 2907.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.16 | 0.00 |
November | 5345.23 | 20-NOV-12:00 | 3955.50 | 2193.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3868.32 |
December | 5763.67 | 02-DEC-10:05 | 7911.00 | 6792.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3934.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5185.26 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54834.31 | 7911.00 | 6792.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1810.15 | 4002.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1494.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6819.95 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5539.86 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4038.09 |
April | 0.00 | 01-APR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8357.73 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4993.17 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5596.66 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5744.99 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2418.33 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6729.49 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9719.35 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9872.90 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21101.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2418.33 | |
Maximum of Months | 0.00 | 0.00 | 1494.14 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21101.55 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.305652E+11 | 22459.15 | 11-JAN-09:09 | 0.923316E+11 | 172580.72 | 07-JAN-17:00 |
February | 0.269834E+11 | 22783.57 | 01-FEB-09:09 | 0.551926E+11 | 227326.08 | 12-FEB-06:10 |
March | 0.288845E+11 | 21635.47 | 18-MAR-08:09 | 0.226986E+10 | 28146.69 | 22-MAR-05:10 |
April | 0.268260E+11 | 24103.78 | 17-APR-14:50 | 0.320156E+09 | 12504.44 | 06-APR-05:10 |
May | 0.291219E+11 | 28821.87 | 19-MAY-13:00 | 83903.40 | 139.84 | 11-MAY-06:40 |
June | 0.352335E+11 | 32297.10 | 06-JUN-15:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.377244E+11 | 35082.85 | 08-JUL-14:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.403810E+11 | 34356.19 | 18-AUG-15:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.313916E+11 | 32438.74 | 07-SEP-15:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.287676E+11 | 25047.98 | 10-OCT-15:00 | 0.315228E+09 | 11166.80 | 31-OCT-05:10 |
November | 0.279436E+11 | 21641.37 | 04-NOV-08:20 | 0.454425E+10 | 46963.73 | 22-NOV-06:10 |
December | 0.300419E+11 | 21925.31 | 19-DEC-09:09 | 0.271278E+11 | 90249.85 | 03-DEC-06:49 |
Annual Sum or Average | 0.373865E+12 | 0.182102E+12 | ||||
Minimum of Months | 0.268260E+11 | 21635.47 | 0.00 | 0.00 | ||
Maximum of Months | 0.403810E+11 | 35082.85 | 0.923316E+11 | 227326.08 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.784247E+10 | 0.645918E+10 | 0.112984E+11 | 0.00 | 0.278126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218393E+10 | 0.00 |
February | 0.705618E+10 | 0.540689E+10 | 0.103734E+11 | 0.00 | 0.215516E+10 | 0.00 | 0.00 | 6786500.03 | 0.00 | 0.00 | 0.00 | 0.198496E+10 | 0.00 |
March | 0.736412E+10 | 0.536606E+10 | 0.121089E+11 | 0.00 | 0.175689E+10 | 0.00 | 0.00 | 78181496.36 | 0.00 | 0.00 | 0.00 | 0.221030E+10 | 0.00 |
April | 0.669781E+10 | 0.457592E+10 | 0.112578E+11 | 0.00 | 0.159185E+10 | 0.00 | 0.00 | 0.650759E+09 | 0.00 | 0.00 | 0.00 | 0.205191E+10 | 0.00 |
May | 0.658505E+10 | 0.420875E+10 | 0.117000E+11 | 0.00 | 0.197463E+10 | 0.00 | 0.00 | 0.259257E+10 | 0.00 | 0.00 | 0.00 | 0.206098E+10 | 0.00 |
June | 0.643122E+10 | 0.385272E+10 | 0.116594E+11 | 0.00 | 0.371326E+10 | 0.00 | 0.00 | 0.762016E+10 | 0.00 | 0.00 | 0.00 | 0.195680E+10 | 0.00 |
July | 0.639530E+10 | 0.406943E+10 | 0.112984E+11 | 0.00 | 0.442715E+10 | 0.00 | 0.00 | 0.958782E+10 | 0.00 | 0.00 | 0.00 | 0.194638E+10 | 0.00 |
August | 0.678839E+10 | 0.449668E+10 | 0.121016E+11 | 0.00 | 0.444640E+10 | 0.00 | 0.00 | 0.105600E+11 | 0.00 | 0.00 | 0.00 | 0.198799E+10 | 0.00 |
September | 0.685328E+10 | 0.492475E+10 | 0.112504E+11 | 0.00 | 0.221881E+10 | 0.00 | 0.00 | 0.421519E+10 | 0.00 | 0.00 | 0.00 | 0.192914E+10 | 0.00 |
October | 0.756564E+10 | 0.573043E+10 | 0.113057E+11 | 0.00 | 0.159105E+10 | 0.00 | 0.00 | 0.544247E+09 | 0.00 | 0.00 | 0.00 | 0.203047E+10 | 0.00 |
November | 0.733066E+10 | 0.610731E+10 | 0.108562E+11 | 0.00 | 0.161349E+10 | 0.00 | 0.00 | 13993855.14 | 0.00 | 0.00 | 0.00 | 0.202196E+10 | 0.00 |
December | 0.785882E+10 | 0.661156E+10 | 0.112984E+11 | 0.00 | 0.212268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215047E+10 | 0.00 |
Annual Sum or Average | 0.847689E+11 | 0.618097E+11 | 0.136508E+12 | 0.00 | 0.303926E+11 | 0.00 | 0.00 | 0.358697E+11 | 0.00 | 0.00 | 0.00 | 0.245153E+11 | 0.00 |
Minimum of Months | 0.639530E+10 | 0.385272E+10 | 0.103734E+11 | 0.00 | 0.159105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192914E+10 | 0.00 |
Maximum of Months | 0.785882E+10 | 0.661156E+10 | 0.121089E+11 | 0.00 | 0.444640E+10 | 0.00 | 0.00 | 0.105600E+11 | 0.00 | 0.00 | 0.00 | 0.221030E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.923316E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.551926E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.226986E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.320156E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 83903.40 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.315228E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.454425E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.271278E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.182102E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.923316E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 8413.53 | 11-JAN-09:09 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2885.66 | 07-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 8784.07 | 01-FEB-09:09 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2973.62 | 13-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8247.74 | 18-MAR-08:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2031.00 | 22-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 7909.08 | 08-APR-08:09 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 1802.67 | 06-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7252.12 | 06-MAY-08:09 | 5520.82 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 3904.83 | 18-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7000.96 | 08-JUN-08:09 | 5520.82 | 01-JUN-05:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 4165.99 | 06-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 7353.87 | 27-JUL-08:09 | 5520.82 | 01-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 4526.07 | 07-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 7541.02 | 24-AUG-07:10 | 5520.82 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4480.38 | 03-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 8079.82 | 30-SEP-08:09 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4081.25 | 07-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8898.85 | 30-OCT-08:09 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 1789.67 | 26-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 8424.01 | 04-NOV-08:09 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2236.04 | 22-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 8345.10 | 19-DEC-09:09 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2652.26 | 18-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 7000.96 | 5520.82 | 10035.17 | 0.00 | 1789.67 | 0.00 | 0.00 | |||||
Maximum of Months | 8898.85 | 5520.82 | 10035.17 | 0.00 | 4526.07 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2121.03 | 30-JAN-12:09 | 0.00 |
February | 584.01 | 28-FEB-14:00 | 0.00 | 0.00 | 0.00 | 2119.72 | 01-FEB-12:00 | 0.00 |
March | 1530.73 | 30-MAR-15:00 | 0.00 | 0.00 | 0.00 | 2047.13 | 01-MAR-12:00 | 0.00 |
April | 5336.33 | 17-APR-14:50 | 0.00 | 0.00 | 0.00 | 1803.79 | 01-APR-11:30 | 0.00 |
May | 8360.97 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1778.07 | 01-MAY-11:09 | 0.00 |
June | 12500.93 | 06-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1751.97 | 01-JUN-11:50 | 0.00 |
July | 14621.86 | 08-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1733.61 | 01-JUL-11:50 | 0.00 |
August | 14139.82 | 03-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1731.74 | 31-AUG-11:50 | 0.00 |
September | 11652.02 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1748.60 | 30-SEP-11:09 | 0.00 |
October | 5615.54 | 10-OCT-15:00 | 0.00 | 0.00 | 0.00 | 1774.79 | 31-OCT-11:09 | 0.00 |
November | 531.45 | 02-NOV-13:00 | 0.00 | 0.00 | 0.00 | 1800.36 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 1953.52 | 21-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1731.74 | 0.00 | ||
Maximum of Months | 14621.86 | 0.00 | 0.00 | 0.00 | 2121.03 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 22459.15 | 11-JAN-09:09 | 8413.53 | 10035.17 | 0.00 | 0.00 | 2336.62 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22783.57 | 01-FEB-09:09 | 8784.07 | 10035.17 | 0.00 | 0.00 | 2288.96 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21635.47 | 18-MAR-08:09 | 8247.74 | 10035.17 | 0.00 | 0.00 | 1684.09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24103.78 | 17-APR-14:50 | 5734.97 | 10035.17 | 0.00 | 0.00 | 1599.54 | 0.00 | 0.00 | 5336.33 | 0.00 |
May | 28821.87 | 19-MAY-13:00 | 5483.36 | 10035.17 | 0.00 | 0.00 | 3904.83 | 0.00 | 0.00 | 7698.88 | 0.00 |
June | 32297.10 | 06-JUN-15:50 | 4394.40 | 10035.17 | 0.00 | 0.00 | 4108.09 | 0.00 | 0.00 | 12170.23 | 0.00 |
July | 35082.85 | 08-JUL-14:50 | 4686.21 | 10035.17 | 0.00 | 0.00 | 4412.27 | 0.00 | 0.00 | 14245.91 | 0.00 |
August | 34356.19 | 18-AUG-15:50 | 4678.08 | 10035.17 | 0.00 | 0.00 | 4384.21 | 0.00 | 0.00 | 13674.71 | 0.00 |
September | 32438.74 | 07-SEP-15:50 | 5094.20 | 10035.17 | 0.00 | 0.00 | 4076.45 | 0.00 | 0.00 | 11647.00 | 0.00 |
October | 25047.98 | 10-OCT-15:00 | 6206.23 | 10035.17 | 0.00 | 0.00 | 1599.54 | 0.00 | 0.00 | 5615.54 | 0.00 |
November | 21641.37 | 04-NOV-08:20 | 8354.61 | 10035.17 | 0.00 | 0.00 | 1599.54 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21925.31 | 19-DEC-09:09 | 8345.10 | 10035.17 | 0.00 | 0.00 | 1876.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 21635.47 | 4394.40 | 10035.17 | 0.00 | 0.00 | 1599.54 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35082.85 | 8784.07 | 10035.17 | 0.00 | 0.00 | 4412.27 | 0.00 | 0.00 | 14245.91 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 172580.72 | 07-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 227326.08 | 12-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 28146.69 | 22-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 12504.44 | 06-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 139.84 | 11-MAY-06:40 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 11166.80 | 31-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 46963.73 | 22-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 90249.85 | 03-DEC-06:49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 227326.08 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.83 | 18.26 | 9.00 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
February | 11.83 | 17.77 | 7.33 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
March | 3.83 | 20.24 | 3.83 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
April | 0.50 | 20.35 | 0.50 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.51 | 0.17 | 24.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.56 | 2.50 | 24.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 24.91 | 6.50 | 24.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 24.74 | 8.17 | 24.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.56 | 2.50 | 24.56 |
October | 0.33 | 20.39 | 0.33 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
November | 3.17 | 20.10 | 3.17 | 20.10 | 0.00 | 20.10 | 0.00 | 20.10 |
December | 10.00 | 18.88 | 8.33 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
Annual Sum or Average | 41.50 | 18.64 | 32.50 | 19.09 | 20.17 | 20.30 | 19.83 | 21.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.45 | 0.00 | 18.45 |
Maximum of Months | 11.83 | 20.39 | 9.00 | 20.39 | 8.17 | 24.91 | 8.17 | 24.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.83 | 14.61 | 4.67 | 14.60 | 0.00 | 14.60 | 0.00 | 14.60 |
February | 42.17 | 14.54 | 3.00 | 14.55 | 0.00 | 14.55 | 0.00 | 14.55 |
March | 0.50 | 14.98 | 0.17 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.00 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.29 | 0.00 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.46 | 0.00 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 27.52 | 0.00 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 27.49 | 0.00 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.31 | 0.00 | 27.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5.83 | 14.84 | 0.50 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
December | 43.83 | 14.78 | 3.50 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 |
Annual Sum or Average | 170.17 | 14.64 | 11.83 | 14.64 | 74.83 | 18.38 | 0.00 | 18.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.83 | 14.98 | 4.67 | 14.98 | 27.67 | 27.52 | 0.00 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.07 | 283.33 | 21.06 | 283.33 | 21.05 |
February | 276.00 | 21.33 | 224.33 | 21.21 | 224.33 | 21.17 |
March | 317.67 | 22.11 | 136.67 | 21.82 | 136.67 | 21.66 |
April | 214.00 | 23.02 | 73.83 | 22.99 | 33.67 | 22.86 |
May | 103.00 | 23.61 | 209.17 | 23.80 | 56.83 | 23.81 |
June | 29.17 | 23.92 | 286.83 | 23.91 | 23.67 | 23.91 |
July | 35.00 | 24.03 | 299.67 | 23.93 | 35.00 | 23.94 |
August | 48.17 | 24.06 | 324.00 | 23.94 | 48.17 | 23.95 |
September | 11.83 | 23.90 | 273.50 | 23.91 | 8.67 | 23.91 |
October | 213.00 | 22.94 | 95.33 | 23.07 | 51.33 | 23.05 |
November | 288.00 | 22.07 | 147.83 | 21.81 | 147.83 | 21.69 |
December | 300.00 | 21.23 | 273.67 | 21.18 | 273.67 | 21.17 |
Annual Sum or Average | 2135.83 | 22.09 | 2628.17 | 22.44 | 1323.17 | 22.26 |
Minimum of Months | 11.83 | 21.07 | 73.83 | 21.06 | 8.67 | 21.05 |
Maximum of Months | 317.67 | 24.06 | 324.00 | 23.94 | 283.33 | 23.95 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.98 | 300.00 | 15.98 | 300.00 | 15.98 |
February | 276.00 | 16.95 | 262.33 | 16.82 | 262.33 | 16.77 |
March | 314.00 | 19.56 | 221.50 | 19.14 | 213.83 | 18.90 |
April | 196.17 | 21.98 | 157.00 | 22.82 | 70.67 | 22.56 |
May | 212.17 | 25.43 | 268.00 | 25.74 | 176.17 | 25.80 |
June | 264.83 | 26.63 | 304.50 | 26.60 | 263.33 | 26.62 |
July | 293.00 | 26.64 | 300.00 | 26.64 | 293.00 | 26.64 |
August | 321.33 | 26.70 | 324.00 | 26.70 | 321.33 | 26.70 |
September | 228.50 | 26.45 | 282.50 | 26.38 | 222.00 | 26.43 |
October | 232.83 | 22.19 | 176.67 | 22.73 | 124.00 | 22.68 |
November | 288.00 | 19.02 | 210.00 | 18.58 | 210.00 | 18.39 |
December | 300.00 | 16.79 | 294.17 | 16.75 | 294.17 | 16.74 |
Annual Sum or Average | 3226.83 | 21.84 | 3100.67 | 22.04 | 2750.83 | 21.96 |
Minimum of Months | 196.17 | 15.98 | 157.00 | 15.98 | 70.67 | 15.98 |
Maximum of Months | 321.33 | 26.70 | 324.00 | 26.70 | 321.33 | 26.70 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 11.43 | 300.00 | 11.43 | 300.00 | 11.43 |
February | 276.00 | 13.28 | 272.83 | 13.24 | 272.83 | 13.22 |
March | 319.33 | 18.75 | 243.67 | 18.35 | 239.67 | 18.15 |
April | 201.00 | 22.59 | 181.00 | 23.28 | 105.00 | 23.19 |
May | 254.50 | 27.31 | 274.50 | 27.43 | 224.67 | 27.58 |
June | 299.17 | 29.86 | 312.00 | 29.78 | 299.17 | 29.81 |
July | 300.00 | 30.36 | 300.00 | 30.36 | 300.00 | 30.36 |
August | 324.00 | 30.32 | 324.00 | 30.32 | 324.00 | 30.32 |
September | 246.50 | 28.74 | 296.33 | 28.44 | 246.50 | 28.53 |
October | 226.83 | 21.77 | 195.67 | 22.34 | 135.67 | 22.21 |
November | 288.00 | 17.36 | 250.67 | 17.09 | 250.67 | 17.00 |
December | 300.00 | 13.13 | 300.00 | 13.13 | 300.00 | 13.13 |
Annual Sum or Average | 3335.33 | 22.01 | 3250.67 | 22.15 | 2998.17 | 22.11 |
Minimum of Months | 201.00 | 11.43 | 181.00 | 11.43 | 105.00 | 11.43 |
Maximum of Months | 324.00 | 30.36 | 324.00 | 30.36 | 324.00 | 30.36 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 26949984.30 | 6786500.03 | 5.67 | 26949984.30 | 0.00 | 0.00 | 0.26 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 | 2311.56 | 28-FEB-15:00 | 2311.56 | 28-FEB-15:00 | 0.00 | 28-FEB-15:10 | 584.01 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.314432E+09 | 78181496.36 | 39.67 | 0.259747E+09 | 54685382.79 | 0.00 | 0.62 | 30-MAR-16:00 | 0.00 | 01-MAR-00:10 | 6153.24 | 30-MAR-16:00 | 5367.32 | 30-MAR-16:00 | 1200.33 | 30-MAR-12:10 | 1530.73 | 30-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.178176E+10 | 0.436784E+09 | 131.50 | 0.154553E+10 | 0.236237E+09 | 0.00 | 0.76 | 17-APR-16:00 | 0.00 | 01-APR-00:10 | 7546.74 | 12-APR-16:00 | 7546.74 | 12-APR-16:00 | 2097.95 | 22-APR-15:00 | 1846.27 | 17-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.472577E+10 | 0.113035E+10 | 232.67 | 0.364969E+10 | 0.107608E+10 | 0.00 | 1.00 | 06-MAY-05:45 | 0.00 | 01-MAY-00:10 | 24039.81 | 31-MAY-05:02 | 15079.31 | 17-MAY-05:03 | 13212.64 | 26-MAY-05:05 | 5130.02 | 31-MAY-05:02 | 0.00 | 01-MAY-00:10 |
June | 0.962398E+10 | 0.229156E+10 | 292.71 | 0.716801E+10 | 0.245596E+10 | 0.00 | 1.00 | 01-JUN-05:02 | 0.00 | 01-JUN-00:10 | 26064.39 | 26-JUN-05:01 | 18018.63 | 12-JUN-05:01 | 14628.16 | 23-JUN-05:04 | 5417.52 | 26-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.110170E+11 | 0.262478E+10 | 297.08 | 0.784510E+10 | 0.317193E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 26463.30 | 27-JUL-05:01 | 18473.38 | 18-JUL-05:01 | 16338.78 | 27-JUL-05:02 | 5738.87 | 23-JUL-16:53 | 0.00 | 01-JUL-00:10 |
August | 0.126861E+11 | 0.298794E+10 | 319.54 | 0.885626E+10 | 0.382982E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 26930.36 | 24-AUG-05:01 | 19387.74 | 13-AUG-17:45 | 16385.22 | 21-AUG-05:01 | 5674.27 | 13-AUG-17:45 | 0.00 | 01-AUG-00:10 |
September | 0.727484E+10 | 0.169301E+10 | 258.07 | 0.535316E+10 | 0.192167E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 25510.25 | 07-SEP-05:01 | 19349.84 | 16-SEP-05:01 | 13678.06 | 05-SEP-05:05 | 5344.92 | 07-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.179323E+10 | 0.423444E+09 | 112.68 | 0.129035E+10 | 0.502877E+09 | 0.00 | 1.00 | 11-OCT-05:05 | 0.00 | 01-OCT-00:10 | 25697.32 | 19-OCT-05:03 | 9848.43 | 18-OCT-05:03 | 16018.86 | 19-OCT-05:03 | 5369.94 | 19-OCT-05:03 | 0.00 | 01-OCT-00:10 |
November | 55968658.64 | 13993855.14 | 15.17 | 45336632.48 | 10632026.16 | 0.00 | 0.22 | 02-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2154.56 | 02-NOV-14:00 | 1600.67 | 02-NOV-14:30 | 653.68 | 04-NOV-16:00 | 531.45 | 02-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.493000E+11 | 0.116868E+11 | 1704.75 | 0.360401E+11 | 0.132599E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.126861E+11 | 0.298794E+10 | 319.54 | 0.885626E+10 | 0.382982E+10 | 0.00 | 1.00 | 0.00 | 26930.36 | 19387.74 | 16385.22 | 5738.87 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.803537E+09 | 0.213975E+09 | 41.64 | 0.731886E+09 | 71651417.66 | 0.00 | 0.67 | 16-APR-14:30 | 0.00 | 01-APR-00:10 | 20121.70 | 16-APR-14:30 | 19547.74 | 16-APR-14:30 | 2345.36 | 19-APR-14:30 | 5098.81 | 16-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.574533E+10 | 0.146222E+10 | 136.97 | 0.426822E+10 | 0.147711E+10 | 0.00 | 1.00 | 17-MAY-18:55 | 0.00 | 01-MAY-00:10 | 73930.11 | 21-MAY-10:55 | 57203.72 | 17-MAY-18:55 | 31430.08 | 21-MAY-10:55 | 16682.83 | 29-MAY-11:25 | 0.00 | 01-MAY-00:10 |
June | 0.212023E+11 | 0.532860E+10 | 308.95 | 0.149640E+11 | 0.623830E+10 | 0.00 | 1.00 | 01-JUN-17:10 | 0.00 | 01-JUN-00:10 | 77938.72 | 25-JUN-08:25 | 61621.60 | 08-JUN-17:11 | 38242.45 | 25-JUN-08:25 | 17106.35 | 23-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.277504E+11 | 0.696303E+10 | 366.09 | 0.191626E+11 | 0.858777E+10 | 0.00 | 1.00 | 01-JUL-17:20 | 0.00 | 01-JUL-00:10 | 78867.65 | 09-JUL-08:65 | 57233.48 | 04-JUL-15:02 | 43581.03 | 27-JUL-17:25 | 17324.39 | 14-JUL-17:08 | 0.00 | 01-JUL-00:10 |
August | 0.306227E+11 | 0.757209E+10 | 402.75 | 0.202582E+11 | 0.103646E+11 | 0.00 | 1.00 | 01-AUG-14:30 | 0.00 | 01-AUG-00:10 | 84400.15 | 20-AUG-07:25 | 56793.00 | 27-AUG-15:53 | 54071.14 | 20-AUG-07:25 | 17485.07 | 20-AUG-07:25 | 0.00 | 01-AUG-00:10 |
September | 0.101880E+11 | 0.252218E+10 | 194.52 | 0.692391E+10 | 0.326411E+10 | 0.00 | 1.00 | 03-SEP-13:05 | 0.00 | 01-SEP-00:10 | 80008.05 | 17-SEP-11:25 | 58141.58 | 14-SEP-17:12 | 43386.08 | 10-SEP-09:15 | 17338.07 | 17-SEP-11:25 | 0.00 | 01-SEP-00:10 |
October | 0.468886E+09 | 0.120803E+09 | 16.67 | 0.304764E+09 | 0.164122E+09 | 0.00 | 0.40 | 11-OCT-14:20 | 0.00 | 01-OCT-00:10 | 13300.20 | 11-OCT-14:10 | 8768.20 | 10-OCT-16:00 | 5010.01 | 11-OCT-14:00 | 3357.85 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.967811E+11 | 0.241829E+11 | 1467.58 | 0.666135E+11 | 0.301676E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.306227E+11 | 0.757209E+10 | 402.75 | 0.202582E+11 | 0.103646E+11 | 0.00 | 1.00 | 0.00 | 84400.15 | 61621.60 | 54071.14 | 17485.07 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.80 | 25.09 | 28.71 | 50.90 | 113.39 | 0.00 | 0.00 | 0.00 |
February | 61.34 | 28.68 | 32.66 | 73.03 | 90.98 | 0.00 | 0.00 | 0.00 |
March | 90.21 | 43.52 | 46.69 | 125.59 | 57.06 | 0.00 | 0.00 | 0.00 |
April | 101.45 | 46.34 | 55.11 | 152.38 | 55.12 | 0.00 | 0.00 | 0.00 |
May | 102.22 | 38.77 | 63.46 | 161.89 | 42.73 | 0.00 | 0.00 | 0.00 |
June | 107.63 | 41.56 | 66.06 | 187.36 | 32.65 | 0.00 | 0.00 | 0.00 |
July | 101.21 | 37.49 | 63.71 | 180.95 | 25.34 | 0.00 | 0.00 | 0.00 |
August | 99.18 | 37.05 | 62.13 | 179.15 | 23.04 | 0.00 | 0.00 | 0.00 |
September | 81.10 | 33.88 | 47.22 | 128.40 | 42.30 | 0.00 | 0.00 | 0.00 |
October | 71.80 | 37.17 | 34.63 | 100.64 | 69.66 | 0.00 | 0.00 | 0.00 |
November | 57.18 | 25.50 | 31.68 | 72.83 | 77.39 | 0.00 | 0.00 | 0.00 |
December | 47.55 | 20.87 | 26.69 | 49.51 | 92.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.32 | 34.69 | 46.64 | 122.14 | 59.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.55 | 20.87 | 26.69 | 49.51 | 23.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.63 | 46.34 | 66.06 | 187.36 | 113.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.80 | 25.09 | 28.71 | 50.90 | 113.39 | 0.00 | 0.00 | 0.00 |
February | 61.34 | 28.68 | 32.66 | 73.03 | 90.98 | 0.00 | 0.00 | 0.00 |
March | 90.21 | 43.52 | 46.69 | 125.59 | 57.06 | 0.00 | 0.00 | 0.00 |
April | 101.45 | 46.34 | 55.11 | 152.38 | 55.12 | 0.00 | 0.00 | 0.00 |
May | 102.22 | 38.77 | 63.46 | 161.89 | 42.73 | 0.00 | 0.00 | 0.00 |
June | 107.63 | 41.56 | 66.06 | 187.36 | 32.65 | 0.00 | 0.00 | 0.00 |
July | 101.21 | 37.49 | 63.71 | 180.95 | 25.34 | 0.00 | 0.00 | 0.00 |
August | 99.18 | 37.05 | 62.13 | 179.15 | 23.04 | 0.00 | 0.00 | 0.00 |
September | 81.10 | 33.88 | 47.22 | 128.40 | 42.30 | 0.00 | 0.00 | 0.00 |
October | 71.80 | 37.17 | 34.63 | 100.64 | 69.66 | 0.00 | 0.00 | 0.00 |
November | 57.18 | 25.50 | 31.68 | 72.83 | 77.39 | 0.00 | 0.00 | 0.00 |
December | 47.55 | 20.87 | 26.69 | 49.51 | 92.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.32 | 34.69 | 46.64 | 122.14 | 59.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.55 | 20.87 | 26.69 | 49.51 | 23.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.63 | 46.34 | 66.06 | 187.36 | 113.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.80 | 0.00 | 13.80 | 3.59 | 71.99 | 0.00 | 0.00 | 0.00 |
February | 15.30 | 0.00 | 15.30 | 9.66 | 56.43 | 0.00 | 0.00 | 0.00 |
March | 21.49 | 0.00 | 21.48 | 19.94 | 34.42 | 0.00 | 0.00 | 0.00 |
April | 26.01 | 0.14 | 25.88 | 31.24 | 32.25 | 0.00 | 0.00 | 0.00 |
May | 31.07 | 0.97 | 30.10 | 43.42 | 23.86 | 0.00 | 0.00 | 0.00 |
June | 34.08 | 2.14 | 31.94 | 58.99 | 17.91 | 0.00 | 0.00 | 0.00 |
July | 32.27 | 1.57 | 30.70 | 58.32 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 28.77 | 0.36 | 28.40 | 52.80 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 21.71 | 0.01 | 21.70 | 30.19 | 24.92 | 0.00 | 0.00 | 0.00 |
October | 16.49 | 0.00 | 16.49 | 14.76 | 41.59 | 0.00 | 0.00 | 0.00 |
November | 14.76 | 0.00 | 14.76 | 10.62 | 46.62 | 0.00 | 0.00 | 0.00 |
December | 12.76 | 0.00 | 12.76 | 4.46 | 56.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.42 | 0.43 | 21.98 | 28.27 | 36.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.76 | 0.00 | 12.76 | 3.59 | 13.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.08 | 2.14 | 31.94 | 58.99 | 71.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.80 | 0.00 | 13.80 | 3.59 | 71.99 | 0.00 | 0.00 | 0.00 |
February | 15.30 | 0.00 | 15.30 | 9.66 | 56.43 | 0.00 | 0.00 | 0.00 |
March | 21.49 | 0.00 | 21.48 | 19.94 | 34.42 | 0.00 | 0.00 | 0.00 |
April | 26.01 | 0.14 | 25.88 | 31.24 | 32.25 | 0.00 | 0.00 | 0.00 |
May | 31.07 | 0.97 | 30.10 | 43.42 | 23.86 | 0.00 | 0.00 | 0.00 |
June | 34.08 | 2.14 | 31.94 | 58.99 | 17.91 | 0.00 | 0.00 | 0.00 |
July | 32.27 | 1.57 | 30.70 | 58.32 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 28.77 | 0.36 | 28.40 | 52.80 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 21.71 | 0.01 | 21.70 | 30.19 | 24.92 | 0.00 | 0.00 | 0.00 |
October | 16.49 | 0.00 | 16.49 | 14.76 | 41.59 | 0.00 | 0.00 | 0.00 |
November | 14.76 | 0.00 | 14.76 | 10.62 | 46.62 | 0.00 | 0.00 | 0.00 |
December | 12.76 | 0.00 | 12.76 | 4.46 | 56.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.41 | 0.43 | 21.98 | 28.27 | 36.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.76 | 0.00 | 12.76 | 3.59 | 13.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.08 | 2.14 | 31.94 | 58.99 | 71.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.98 | 40.56 | 6.33 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.08 | 33.70 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 65.94 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.13 | 24.85 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.30 | 20.30 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.47 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.87 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.21 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.91 | 21.39 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 52.92 | 28.40 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.00 | 30.62 | 2.33 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.57 | 34.57 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.52 | 25.32 | 12.00 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.57 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.47 | 40.56 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.98 | 40.56 | 6.33 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.08 | 33.70 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 65.94 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.13 | 24.85 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.30 | 20.30 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.47 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.87 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.21 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.91 | 21.39 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 52.92 | 28.40 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.00 | 30.62 | 2.33 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.57 | 34.57 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.52 | 25.32 | 12.00 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.57 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.47 | 40.56 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.98 | 40.56 | 6.33 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.08 | 33.70 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 65.94 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.13 | 24.85 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.30 | 20.30 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.47 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.87 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.21 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.91 | 21.39 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 52.92 | 28.40 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.00 | 30.62 | 2.33 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.57 | 34.57 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.52 | 25.32 | 12.00 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.57 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.47 | 40.56 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.98 | 40.56 | 6.33 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.08 | 33.70 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 65.94 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.13 | 24.85 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.30 | 20.30 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.47 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.87 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.21 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.91 | 21.39 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 52.92 | 28.40 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.00 | 30.62 | 2.33 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.57 | 34.57 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.52 | 25.32 | 12.00 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.57 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.47 | 40.56 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.98 | 40.56 | 6.33 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.08 | 33.70 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 65.94 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.13 | 24.85 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.30 | 20.30 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.47 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.87 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.21 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.91 | 21.39 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 52.92 | 28.40 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.00 | 30.62 | 2.33 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.57 | 34.57 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.52 | 25.32 | 12.00 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.57 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.47 | 40.56 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.98 | 40.56 | 6.33 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.08 | 33.70 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 65.94 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.13 | 24.85 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.30 | 20.30 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.47 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.87 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.21 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.91 | 21.39 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 52.92 | 28.40 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.00 | 30.62 | 2.33 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.57 | 34.57 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.52 | 25.32 | 12.00 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.57 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.47 | 40.56 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.98 | 40.56 | 6.33 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.08 | 33.70 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 65.94 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.13 | 24.85 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.30 | 20.30 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.47 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.87 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.21 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.91 | 21.39 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 52.92 | 28.40 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.00 | 30.62 | 2.33 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.57 | 34.57 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.52 | 25.32 | 12.00 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.57 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.47 | 40.56 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.98 | 40.56 | 6.33 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.08 | 33.70 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 65.94 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.13 | 24.85 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.30 | 20.30 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.47 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.87 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.21 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.91 | 21.39 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 52.92 | 28.40 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.00 | 30.62 | 2.33 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.57 | 34.57 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.52 | 25.32 | 12.00 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.57 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.47 | 40.56 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.98 | 40.56 | 6.33 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.08 | 33.70 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 65.94 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.13 | 24.85 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.30 | 20.30 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.47 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.87 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.21 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.91 | 21.39 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 52.92 | 28.40 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.00 | 30.62 | 2.33 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.57 | 34.57 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.52 | 25.32 | 12.00 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.57 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.47 | 40.56 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.98 | 40.56 | 6.33 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.08 | 33.70 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 65.94 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.13 | 24.85 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.30 | 20.30 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.47 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.87 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.21 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.91 | 21.39 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 52.92 | 28.40 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.00 | 30.62 | 2.33 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.57 | 34.57 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.52 | 25.32 | 12.00 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.57 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.47 | 40.56 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.98 | 40.56 | 6.33 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.08 | 33.70 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 65.94 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.13 | 24.85 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.30 | 20.30 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.47 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.87 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.21 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.91 | 21.39 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 52.92 | 28.40 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.00 | 30.62 | 2.33 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.57 | 34.57 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.52 | 25.32 | 12.00 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.57 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.47 | 40.56 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.98 | 40.56 | 6.33 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.08 | 33.70 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 65.94 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.13 | 24.85 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.30 | 20.30 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.47 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.87 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.21 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.91 | 21.39 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 52.92 | 28.40 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.00 | 30.62 | 2.33 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.57 | 34.57 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.52 | 25.32 | 12.00 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.57 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.47 | 40.56 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.98 | 40.56 | 6.33 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.08 | 33.70 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 65.94 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.13 | 24.85 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.30 | 20.30 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.47 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.87 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.21 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.91 | 21.39 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 52.92 | 28.40 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.00 | 30.62 | 2.33 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.57 | 34.57 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.52 | 25.32 | 12.00 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.57 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.47 | 40.56 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.98 | 40.56 | 6.33 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.08 | 33.70 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 65.94 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.13 | 24.85 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.30 | 20.30 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.47 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.87 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.21 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.91 | 21.39 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 52.92 | 28.40 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.00 | 30.62 | 2.33 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.57 | 34.57 | 3.33 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.52 | 25.32 | 12.00 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.57 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.47 | 40.56 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.51 | 40.66 | 24.50 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.67 | 35.08 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.85 | 31.60 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.45 | 34.68 | 0.17 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.66 | 30.61 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.15 | 29.71 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.89 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.68 | 25.69 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.06 | 33.76 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.08 | 38.45 | 10.67 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.86 | 36.92 | 38.33 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.42 | 35.08 | 41.67 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.52 | 33.16 | 170.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.42 | 25.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.15 | 40.66 | 51.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144099E+09 | 67190086.89 | 76909197.70 | 0.136340E+09 | 0.303697E+09 |
February | 0.148397E+09 | 69387007.56 | 79009896.41 | 0.176681E+09 | 0.220096E+09 |
March | 0.241608E+09 | 0.116565E+09 | 0.125044E+09 | 0.336387E+09 | 0.152825E+09 |
April | 0.262950E+09 | 0.120103E+09 | 0.142847E+09 | 0.394982E+09 | 0.142880E+09 |
May | 0.273795E+09 | 0.103834E+09 | 0.169961E+09 | 0.433599E+09 | 0.114448E+09 |
June | 0.278965E+09 | 0.107736E+09 | 0.171228E+09 | 0.485646E+09 | 84627537.26 |
July | 0.271068E+09 | 0.100423E+09 | 0.170645E+09 | 0.484655E+09 | 67880390.78 |
August | 0.265646E+09 | 99244081.66 | 0.166402E+09 | 0.479846E+09 | 61723611.17 |
September | 0.210210E+09 | 87824097.10 | 0.122385E+09 | 0.332815E+09 | 0.109640E+09 |
October | 0.192301E+09 | 99549954.50 | 92751352.52 | 0.269558E+09 | 0.186584E+09 |
November | 0.148212E+09 | 66087259.20 | 82124365.90 | 0.188765E+09 | 0.200601E+09 |
December | 0.127367E+09 | 55892649.05 | 71473937.90 | 0.132615E+09 | 0.246442E+09 |
Annual Sum or Average | 0.256462E+10 | 0.109384E+10 | 0.147078E+10 | 0.385189E+10 | 0.189144E+10 |
Minimum of Months | 0.127367E+09 | 55892649.05 | 71473937.90 | 0.132615E+09 | 61723611.17 |
Maximum of Months | 0.278965E+09 | 0.120103E+09 | 0.171228E+09 | 0.485646E+09 | 0.303697E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144099E+09 | 67190086.89 | 76909197.70 | 0.136340E+09 | 0.303697E+09 |
February | 0.148397E+09 | 69387007.56 | 79009896.41 | 0.176681E+09 | 0.220096E+09 |
March | 0.241608E+09 | 0.116565E+09 | 0.125044E+09 | 0.336387E+09 | 0.152825E+09 |
April | 0.262950E+09 | 0.120103E+09 | 0.142847E+09 | 0.394982E+09 | 0.142880E+09 |
May | 0.273795E+09 | 0.103834E+09 | 0.169961E+09 | 0.433599E+09 | 0.114448E+09 |
June | 0.278965E+09 | 0.107736E+09 | 0.171228E+09 | 0.485646E+09 | 84627537.26 |
July | 0.271068E+09 | 0.100423E+09 | 0.170645E+09 | 0.484655E+09 | 67880390.78 |
August | 0.265646E+09 | 99244081.66 | 0.166402E+09 | 0.479846E+09 | 61723611.17 |
September | 0.210210E+09 | 87824097.10 | 0.122385E+09 | 0.332815E+09 | 0.109640E+09 |
October | 0.192301E+09 | 99549954.50 | 92751352.52 | 0.269558E+09 | 0.186584E+09 |
November | 0.148212E+09 | 66087259.20 | 82124365.90 | 0.188765E+09 | 0.200601E+09 |
December | 0.127367E+09 | 55892649.05 | 71473937.90 | 0.132615E+09 | 0.246442E+09 |
Annual Sum or Average | 0.256462E+10 | 0.109384E+10 | 0.147078E+10 | 0.385189E+10 | 0.189144E+10 |
Minimum of Months | 0.127367E+09 | 55892649.05 | 71473937.90 | 0.132615E+09 | 61723611.17 |
Maximum of Months | 0.278965E+09 | 0.120103E+09 | 0.171228E+09 | 0.485646E+09 | 0.303697E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36970919.86 | 0.00 | 36970919.86 | 9627533.90 | 0.192819E+09 |
February | 37012989.26 | 0.00 | 37012989.26 | 23377327.64 | 0.136505E+09 |
March | 57548283.46 | 3066.27 | 57545217.19 | 53415000.32 | 92181492.91 |
April | 67426402.71 | 352601.56 | 67073801.15 | 80975568.96 | 83598349.61 |
May | 83228708.08 | 2597172.86 | 80631535.22 | 0.116288E+09 | 63918180.24 |
June | 88335254.71 | 5551815.21 | 82783439.50 | 0.152897E+09 | 46413194.89 |
July | 86441676.67 | 4209343.05 | 82232333.62 | 0.156208E+09 | 38011185.85 |
August | 77050157.49 | 974289.45 | 76075868.04 | 0.141417E+09 | 34894018.08 |
September | 56261806.02 | 22895.89 | 56238910.14 | 78253233.69 | 64600598.59 |
October | 44173323.99 | 0.00 | 44173323.99 | 39535546.43 | 0.111392E+09 |
November | 38258235.74 | 0.00 | 38258235.74 | 27523883.02 | 0.120846E+09 |
December | 34176865.45 | 0.00 | 34176865.45 | 11946669.97 | 0.151045E+09 |
Annual Sum or Average | 0.706885E+09 | 13711184.29 | 0.693173E+09 | 0.891464E+09 | 0.113622E+10 |
Minimum of Months | 34176865.45 | 0.00 | 34176865.45 | 9627533.90 | 34894018.08 |
Maximum of Months | 88335254.71 | 5551815.21 | 82783439.50 | 0.156208E+09 | 0.192819E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36969807.32 | 0.00 | 36969807.32 | 9626925.40 | 0.192819E+09 |
February | 37011928.69 | 0.00 | 37011928.69 | 23376460.01 | 0.136504E+09 |
March | 57546628.30 | 3066.12 | 57543562.18 | 53413058.59 | 92180837.57 |
April | 67424490.45 | 352585.04 | 67071905.41 | 80973162.23 | 83597785.14 |
May | 83226228.11 | 2597051.13 | 80629176.98 | 0.116284E+09 | 63917724.07 |
June | 88332578.85 | 5551554.99 | 82781023.86 | 0.152892E+09 | 46412640.90 |
July | 86439043.15 | 4209145.75 | 82229897.40 | 0.156204E+09 | 38010658.00 |
August | 77047855.32 | 974243.79 | 76073611.54 | 0.141414E+09 | 34893435.28 |
September | 56260122.22 | 22894.81 | 56237227.41 | 78250995.83 | 64599935.88 |
October | 44172118.43 | 0.00 | 44172118.43 | 39534244.83 | 0.111392E+09 |
November | 38257080.74 | 0.00 | 38257080.74 | 27522769.23 | 0.120846E+09 |
December | 34175826.23 | 0.00 | 34175826.23 | 11945862.44 | 0.151044E+09 |
Annual Sum or Average | 0.706864E+09 | 13710541.63 | 0.693153E+09 | 0.891438E+09 | 0.113622E+10 |
Minimum of Months | 34175826.23 | 0.00 | 34175826.23 | 9626925.40 | 34893435.28 |
Maximum of Months | 88332578.85 | 5551554.99 | 82781023.86 | 0.156204E+09 | 0.192819E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74934220.01 | 0.108630E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 96962319.90 | 81536696.70 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176627E+09 | 65608882.09 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223254E+09 | 64422441.95 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263291E+09 | 54365763.65 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283747E+09 | 45165513.20 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278212E+09 | 38003372.66 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257694E+09 | 37241520.38 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168249E+09 | 55448185.42 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141733E+09 | 76077705.11 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93301274.33 | 79377142.96 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 92579624.08 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.212918E+10 | 0.798457E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 37241520.38 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283747E+09 | 0.108630E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74934220.01 | 0.108630E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 96962319.90 | 81536696.70 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176627E+09 | 65608882.09 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223254E+09 | 64422441.95 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263291E+09 | 54365763.65 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283747E+09 | 45165513.20 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278212E+09 | 38003372.66 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257694E+09 | 37241520.38 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168249E+09 | 55448185.42 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141733E+09 | 76077705.11 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93301274.33 | 79377142.96 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 92579624.08 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.212918E+10 | 0.798457E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 37241520.38 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283747E+09 | 0.108630E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74934220.01 | 0.108630E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 96962319.90 | 81536696.70 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176627E+09 | 65608882.09 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223254E+09 | 64422441.95 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263291E+09 | 54365763.65 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283747E+09 | 45165513.20 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278212E+09 | 38003372.66 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257694E+09 | 37241520.38 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168249E+09 | 55448185.42 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141733E+09 | 76077705.11 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93301274.33 | 79377142.96 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 92579624.08 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.212918E+10 | 0.798457E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 37241520.38 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283747E+09 | 0.108630E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74934220.01 | 0.108630E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 96962319.90 | 81536696.70 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176627E+09 | 65608882.09 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223254E+09 | 64422441.95 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263291E+09 | 54365763.65 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283747E+09 | 45165513.20 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278212E+09 | 38003372.66 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257694E+09 | 37241520.38 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168249E+09 | 55448185.42 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141733E+09 | 76077705.11 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93301274.33 | 79377142.96 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 92579624.08 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.212918E+10 | 0.798457E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 37241520.38 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283747E+09 | 0.108630E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74934220.01 | 0.108630E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 96962319.90 | 81536696.70 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176627E+09 | 65608882.09 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223254E+09 | 64422441.95 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263291E+09 | 54365763.65 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283747E+09 | 45165513.20 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278212E+09 | 38003372.66 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257694E+09 | 37241520.38 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168249E+09 | 55448185.42 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141733E+09 | 76077705.11 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93301274.33 | 79377142.96 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 92579624.08 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.212918E+10 | 0.798457E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 37241520.38 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283747E+09 | 0.108630E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74934220.01 | 0.108630E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 96962319.90 | 81536696.70 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176627E+09 | 65608882.09 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223254E+09 | 64422441.95 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263291E+09 | 54365763.65 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283747E+09 | 45165513.20 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278212E+09 | 38003372.66 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257694E+09 | 37241520.38 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168249E+09 | 55448185.42 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141733E+09 | 76077705.11 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93301274.33 | 79377142.96 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 92579624.08 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.212918E+10 | 0.798457E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 37241520.38 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283747E+09 | 0.108630E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74934220.01 | 0.108630E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 96962319.90 | 81536696.70 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176627E+09 | 65608882.09 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223254E+09 | 64422441.95 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263291E+09 | 54365763.65 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283747E+09 | 45165513.20 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278212E+09 | 38003372.66 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257694E+09 | 37241520.38 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168249E+09 | 55448185.42 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141733E+09 | 76077705.11 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93301274.33 | 79377142.96 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 92579624.08 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.212918E+10 | 0.798457E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 37241520.38 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283747E+09 | 0.108630E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74934220.01 | 0.108630E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 96962319.90 | 81536696.70 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176627E+09 | 65608882.09 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223254E+09 | 64422441.95 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263291E+09 | 54365763.65 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283747E+09 | 45165513.20 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278212E+09 | 38003372.66 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257694E+09 | 37241520.38 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168249E+09 | 55448185.42 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141733E+09 | 76077705.11 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93301274.33 | 79377142.96 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 92579624.08 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.212918E+10 | 0.798457E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 37241520.38 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283747E+09 | 0.108630E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74934220.01 | 0.108630E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 96962319.90 | 81536696.70 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176627E+09 | 65608882.09 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223254E+09 | 64422441.95 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263291E+09 | 54365763.65 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283747E+09 | 45165513.20 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278212E+09 | 38003372.66 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257694E+09 | 37241520.38 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168249E+09 | 55448185.42 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141733E+09 | 76077705.11 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93301274.33 | 79377142.96 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 92579624.08 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.212918E+10 | 0.798457E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 37241520.38 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283747E+09 | 0.108630E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74934220.01 | 0.108630E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 96962319.90 | 81536696.70 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176627E+09 | 65608882.09 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223254E+09 | 64422441.95 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263291E+09 | 54365763.65 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283747E+09 | 45165513.20 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278212E+09 | 38003372.66 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257694E+09 | 37241520.38 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168249E+09 | 55448185.42 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141733E+09 | 76077705.11 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93301274.33 | 79377142.96 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 92579624.08 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.212918E+10 | 0.798457E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 37241520.38 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283747E+09 | 0.108630E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74934220.01 | 0.108630E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 96962319.90 | 81536696.70 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176627E+09 | 65608882.09 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223254E+09 | 64422441.95 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263291E+09 | 54365763.65 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283747E+09 | 45165513.20 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278212E+09 | 38003372.66 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257694E+09 | 37241520.38 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168249E+09 | 55448185.42 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141733E+09 | 76077705.11 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93301274.33 | 79377142.96 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 92579624.08 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.212918E+10 | 0.798457E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 37241520.38 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283747E+09 | 0.108630E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74934220.01 | 0.108630E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 96962319.90 | 81536696.70 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176627E+09 | 65608882.09 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223254E+09 | 64422441.95 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263291E+09 | 54365763.65 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283747E+09 | 45165513.20 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278212E+09 | 38003372.66 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257694E+09 | 37241520.38 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168249E+09 | 55448185.42 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141733E+09 | 76077705.11 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93301274.33 | 79377142.96 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 92579624.08 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.212918E+10 | 0.798457E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 37241520.38 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283747E+09 | 0.108630E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74934220.01 | 0.108630E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 96962319.90 | 81536696.70 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176627E+09 | 65608882.09 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223254E+09 | 64422441.95 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263291E+09 | 54365763.65 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283747E+09 | 45165513.20 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278212E+09 | 38003372.66 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257694E+09 | 37241520.38 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168249E+09 | 55448185.42 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141733E+09 | 76077705.11 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93301274.33 | 79377142.96 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 92579624.08 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.212918E+10 | 0.798457E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 37241520.38 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283747E+09 | 0.108630E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74934220.01 | 0.108630E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 96962319.90 | 81536696.70 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176627E+09 | 65608882.09 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223254E+09 | 64422441.95 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263291E+09 | 54365763.65 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283747E+09 | 45165513.20 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278212E+09 | 38003372.66 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257694E+09 | 37241520.38 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168249E+09 | 55448185.42 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141733E+09 | 76077705.11 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93301274.33 | 79377142.96 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 92579624.08 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.212918E+10 | 0.798457E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71172525.00 | 37241520.38 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283747E+09 | 0.108630E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186162E+09 | 0.108909E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216932E+09 | 84864671.11 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361189E+09 | 84643039.45 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441816E+09 | 89899510.63 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510664E+09 | 81980188.21 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534348E+09 | 76999233.36 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69343727.28 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481260E+09 | 68801515.66 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324145E+09 | 87494503.89 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289482E+09 | 0.102981E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204414E+09 | 95704414.02 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 93955039.01 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424223E+10 | 0.104558E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172533E+09 | 68801515.66 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534348E+09 | 0.108909E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 100.51 | 362.27 | 135.21 | 50.17 | 85.04 | 0.00 | 0.00 |
February | 159.95 | 289.36 | 153.28 | 57.36 | 95.92 | 0.00 | 0.00 |
March | 289.55 | 181.43 | 223.38 | 87.04 | 136.34 | 0.00 | 0.00 |
April | 366.26 | 173.77 | 254.92 | 92.94 | 161.98 | 0.00 | 0.00 |
May | 409.69 | 132.28 | 266.59 | 79.47 | 187.12 | 0.00 | 0.00 |
June | 491.33 | 99.74 | 283.41 | 87.41 | 196.00 | 0.00 | 0.00 |
July | 477.62 | 78.15 | 266.96 | 78.13 | 188.83 | 0.00 | 0.00 |
August | 463.64 | 71.88 | 255.90 | 74.83 | 181.06 | 0.00 | 0.00 |
September | 316.70 | 133.97 | 205.61 | 67.78 | 137.83 | 0.00 | 0.00 |
October | 229.17 | 220.87 | 176.58 | 74.34 | 102.24 | 0.00 | 0.00 |
November | 164.87 | 246.01 | 143.88 | 50.99 | 92.89 | 0.00 | 0.00 |
December | 103.99 | 292.85 | 120.63 | 41.74 | 78.89 | 0.00 | 0.00 |
Annual Sum or Average | 298.50 | 189.69 | 207.48 | 70.24 | 137.24 | 0.00 | 0.00 |
Minimum of Months | 100.51 | 71.88 | 120.63 | 41.74 | 78.89 | 0.00 | 0.00 |
Maximum of Months | 491.33 | 362.27 | 283.41 | 92.94 | 196.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 391.68 | 567.81 | 393.05 | 216.79 | 176.26 | 0.00 | 0.00 |
February | 561.12 | 471.86 | 481.98 | 294.52 | 187.46 | 0.00 | 0.00 |
March | 923.23 | 342.94 | 720.22 | 441.96 | 278.26 | 0.00 | 0.00 |
April | 1205.85 | 347.96 | 904.78 | 559.94 | 344.85 | 0.00 | 0.00 |
May | 1376.22 | 284.17 | 1011.10 | 586.78 | 424.32 | 0.00 | 0.00 |
June | 1532.58 | 243.95 | 1080.41 | 639.91 | 440.50 | 0.00 | 0.00 |
July | 1454.21 | 198.64 | 1006.56 | 572.92 | 433.64 | 0.00 | 0.00 |
August | 1346.97 | 194.66 | 926.03 | 509.73 | 416.29 | 0.00 | 0.00 |
September | 908.75 | 299.49 | 678.20 | 375.37 | 302.83 | 0.00 | 0.00 |
October | 740.84 | 397.66 | 587.23 | 395.55 | 191.69 | 0.00 | 0.00 |
November | 503.94 | 428.73 | 420.87 | 232.11 | 188.76 | 0.00 | 0.00 |
December | 372.02 | 483.91 | 346.39 | 184.33 | 162.05 | 0.00 | 0.00 |
Annual Sum or Average | 945.22 | 354.46 | 714.33 | 418.13 | 296.20 | 0.00 | 0.00 |
Minimum of Months | 372.02 | 194.66 | 346.39 | 184.33 | 162.05 | 0.00 | 0.00 |
Maximum of Months | 1532.58 | 567.81 | 1080.41 | 639.91 | 440.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9655.86 | 8839.61 | 1822.58 | 1025.18 | 797.40 | 0.00 | 0.00 |
February | 11924.45 | 7037.58 | 2203.25 | 1355.20 | 848.05 | 0.00 | 0.00 |
March | 17217.34 | 3517.69 | 3234.96 | 1976.14 | 1258.83 | 0.00 | 0.00 |
April | 21519.32 | 3484.60 | 4035.11 | 2475.05 | 1560.06 | 0.00 | 0.00 |
May | 26037.26 | 3064.28 | 4495.54 | 2575.93 | 1919.61 | 0.00 | 0.00 |
June | 35410.17 | 3477.60 | 4797.07 | 2804.29 | 1992.79 | 0.00 | 0.00 |
July | 35240.78 | 3777.66 | 4476.19 | 2514.43 | 1961.76 | 0.00 | 0.00 |
August | 34070.66 | 3659.79 | 4126.34 | 2243.04 | 1883.29 | 0.00 | 0.00 |
September | 19711.12 | 3665.39 | 3042.60 | 1672.64 | 1369.97 | 0.00 | 0.00 |
October | 13464.64 | 3934.89 | 2652.20 | 1785.02 | 867.18 | 0.00 | 0.00 |
November | 10051.78 | 4633.96 | 1941.40 | 1087.45 | 853.94 | 0.00 | 0.00 |
December | 8378.65 | 6470.91 | 1620.29 | 887.17 | 733.12 | 0.00 | 0.00 |
Annual Sum or Average | 20275.83 | 4619.48 | 3209.44 | 1869.43 | 1340.01 | 0.00 | 0.00 |
Minimum of Months | 8378.65 | 3064.28 | 1620.29 | 887.17 | 733.12 | 0.00 | 0.00 |
Maximum of Months | 35410.17 | 8839.61 | 4797.07 | 2804.29 | 1992.79 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.269197E+09 | 0.970295E+09 | 0.362139E+09 | 0.134380E+09 | 0.227759E+09 | 0.00 | 0.00 |
February | 0.386943E+09 | 0.700027E+09 | 0.370819E+09 | 0.138774E+09 | 0.232045E+09 | 0.00 | 0.00 |
March | 0.775520E+09 | 0.485929E+09 | 0.598312E+09 | 0.233135E+09 | 0.365176E+09 | 0.00 | 0.00 |
April | 0.949355E+09 | 0.450400E+09 | 0.660751E+09 | 0.240911E+09 | 0.419839E+09 | 0.00 | 0.00 |
May | 0.109733E+10 | 0.354287E+09 | 0.714045E+09 | 0.212862E+09 | 0.501183E+09 | 0.00 | 0.00 |
June | 0.127353E+10 | 0.258528E+09 | 0.734598E+09 | 0.226576E+09 | 0.508021E+09 | 0.00 | 0.00 |
July | 0.127925E+10 | 0.209307E+09 | 0.715017E+09 | 0.209265E+09 | 0.505752E+09 | 0.00 | 0.00 |
August | 0.124181E+10 | 0.192526E+09 | 0.685389E+09 | 0.200437E+09 | 0.484953E+09 | 0.00 | 0.00 |
September | 0.820898E+09 | 0.347245E+09 | 0.532941E+09 | 0.175694E+09 | 0.357247E+09 | 0.00 | 0.00 |
October | 0.613806E+09 | 0.591572E+09 | 0.472948E+09 | 0.199100E+09 | 0.273848E+09 | 0.00 | 0.00 |
November | 0.427350E+09 | 0.637668E+09 | 0.372939E+09 | 0.132175E+09 | 0.240764E+09 | 0.00 | 0.00 |
December | 0.278526E+09 | 0.784376E+09 | 0.323086E+09 | 0.111785E+09 | 0.211301E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.941351E+10 | 0.598216E+10 | 0.654298E+10 | 0.221509E+10 | 0.432789E+10 | 0.00 | 0.00 |
Minimum of Months | 0.269197E+09 | 0.192526E+09 | 0.323086E+09 | 0.111785E+09 | 0.211301E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127925E+10 | 0.970295E+09 | 0.734598E+09 | 0.240911E+09 | 0.508021E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104908E+10 | 0.152082E+10 | 0.105275E+10 | 0.580649E+09 | 0.472100E+09 | 0.00 | 0.00 |
February | 0.135747E+10 | 0.114151E+10 | 0.116600E+10 | 0.712502E+09 | 0.453501E+09 | 0.00 | 0.00 |
March | 0.247277E+10 | 0.918524E+09 | 0.192905E+10 | 0.118376E+10 | 0.745288E+09 | 0.00 | 0.00 |
April | 0.312556E+10 | 0.901914E+09 | 0.234520E+10 | 0.145136E+10 | 0.893839E+09 | 0.00 | 0.00 |
May | 0.368608E+10 | 0.761121E+09 | 0.270814E+10 | 0.157164E+10 | 0.113650E+10 | 0.00 | 0.00 |
June | 0.397246E+10 | 0.632317E+09 | 0.280043E+10 | 0.165866E+10 | 0.114177E+10 | 0.00 | 0.00 |
July | 0.389496E+10 | 0.532047E+09 | 0.269598E+10 | 0.153452E+10 | 0.116146E+10 | 0.00 | 0.00 |
August | 0.360771E+10 | 0.521381E+09 | 0.248028E+10 | 0.136527E+10 | 0.111500E+10 | 0.00 | 0.00 |
September | 0.235548E+10 | 0.776275E+09 | 0.175789E+10 | 0.972969E+09 | 0.784924E+09 | 0.00 | 0.00 |
October | 0.198426E+10 | 0.106509E+10 | 0.157285E+10 | 0.105944E+10 | 0.513411E+09 | 0.00 | 0.00 |
November | 0.130622E+10 | 0.111128E+10 | 0.109090E+10 | 0.601627E+09 | 0.489268E+09 | 0.00 | 0.00 |
December | 0.996415E+09 | 0.129611E+10 | 0.927760E+09 | 0.493717E+09 | 0.434043E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.298085E+11 | 0.111784E+11 | 0.225272E+11 | 0.131861E+11 | 0.934111E+10 | 0.00 | 0.00 |
Minimum of Months | 0.996415E+09 | 0.521381E+09 | 0.927760E+09 | 0.493717E+09 | 0.434043E+09 | 0.00 | 0.00 |
Maximum of Months | 0.397246E+10 | 0.152082E+10 | 0.280043E+10 | 0.165866E+10 | 0.116146E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.258623E+11 | 0.236760E+11 | 0.488160E+10 | 0.274585E+10 | 0.213575E+10 | 0.00 | 0.00 |
February | 0.288476E+11 | 0.170253E+11 | 0.533010E+10 | 0.327849E+10 | 0.205161E+10 | 0.00 | 0.00 |
March | 0.461149E+11 | 0.942179E+10 | 0.866453E+10 | 0.529289E+10 | 0.337164E+10 | 0.00 | 0.00 |
April | 0.557781E+11 | 0.903207E+10 | 0.104590E+11 | 0.641532E+10 | 0.404368E+10 | 0.00 | 0.00 |
May | 0.697382E+11 | 0.820737E+10 | 0.120409E+11 | 0.689938E+10 | 0.514147E+10 | 0.00 | 0.00 |
June | 0.917832E+11 | 0.901393E+10 | 0.124340E+11 | 0.726871E+10 | 0.516530E+10 | 0.00 | 0.00 |
July | 0.943889E+11 | 0.101181E+11 | 0.119890E+11 | 0.673464E+10 | 0.525438E+10 | 0.00 | 0.00 |
August | 0.912548E+11 | 0.980239E+10 | 0.110520E+11 | 0.600776E+10 | 0.504422E+10 | 0.00 | 0.00 |
September | 0.510912E+11 | 0.950069E+10 | 0.788643E+10 | 0.433548E+10 | 0.355095E+10 | 0.00 | 0.00 |
October | 0.360637E+11 | 0.105392E+11 | 0.710364E+10 | 0.478100E+10 | 0.232264E+10 | 0.00 | 0.00 |
November | 0.260542E+11 | 0.120112E+11 | 0.503210E+10 | 0.281868E+10 | 0.221342E+10 | 0.00 | 0.00 |
December | 0.224414E+11 | 0.173317E+11 | 0.433978E+10 | 0.237619E+10 | 0.196359E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.639419E+12 | 0.145680E+12 | 0.101213E+12 | 0.589544E+11 | 0.422587E+11 | 0.00 | 0.00 |
Minimum of Months | 0.224414E+11 | 0.820737E+10 | 0.433978E+10 | 0.237619E+10 | 0.196359E+10 | 0.00 | 0.00 |
Maximum of Months | 0.943889E+11 | 0.236760E+11 | 0.124340E+11 | 0.726871E+10 | 0.525438E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.895701E+09 | -808233259.1 | 0.00 | 0.00 | 744.00 | 0.00 | -87468167.6 | 58.99 | 0.00 | 0.00 |
February | 0.821520E+09 | -744043492.0 | 0.00 | 0.00 | 672.00 | 0.00 | -77476028.5 | 58.99 | 0.00 | 0.00 |
March | 0.921807E+09 | -840257165.4 | 0.00 | 0.00 | 744.00 | 0.00 | -81550144.7 | 58.99 | 0.00 | 0.00 |
April | 0.805165E+09 | -730853645.0 | 0.00 | 0.00 | 720.00 | 0.00 | -74311653.7 | 58.99 | 0.00 | 0.00 |
May | 0.772484E+09 | -699073336.5 | 0.00 | 0.00 | 744.00 | 0.00 | -73410274.1 | 58.99 | 0.00 | 0.00 |
June | 0.709991E+09 | -641064914.7 | 0.00 | 0.00 | 720.00 | 0.00 | -68926575.9 | 58.99 | 0.00 | 0.00 |
July | 0.657887E+09 | -587556089.9 | 0.00 | 0.00 | 744.00 | 0.00 | -70331240.0 | 58.99 | 0.00 | 0.00 |
August | 0.699340E+09 | -628939300.8 | 0.00 | 0.00 | 744.00 | 0.00 | -70401064.2 | 58.99 | 0.00 | 0.00 |
September | 0.682612E+09 | -613267741.2 | 0.00 | 0.00 | 720.00 | 0.00 | -69344508.1 | 58.99 | 0.00 | 0.00 |
October | 0.741804E+09 | -665279902.4 | 0.00 | 0.00 | 744.00 | 0.00 | -76524397.6 | 59.00 | 0.00 | 0.00 |
November | 0.774986E+09 | -695384610.4 | 0.00 | 0.00 | 720.00 | 0.00 | -79601604.3 | 58.99 | 0.00 | 0.00 |
December | 0.862270E+09 | -775885008.7 | 0.00 | 0.00 | 744.00 | 0.00 | -86384821.6 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.934557E+10 | -0.842984E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -915730480.3 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.657887E+09 | -840257165.4 | 0.00 | 0.00 | 672.00 | 0.00 | -87468167.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.921807E+09 | -587556089.9 | 0.00 | 0.00 | 744.00 | 0.00 | -68926575.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.81 | 0.50 | 08-JAN-11:30 | 136.69 | 0.00 | 0.00 | 4.67 | 109.92 | 0.00 | 0.00 | 0.00 |
February | 263.00 | 0.79 | 0.50 | 01-FEB-14:20 | 147.62 | 0.00 | 0.00 | 22.17 | 119.77 | 0.00 | 0.00 | 6.33 |
March | 351.67 | 0.72 | 0.50 | 01-MAR-13:09 | 1890.93 | 0.00 | 0.00 | 110.00 | 154.89 | 0.00 | 0.00 | 23.83 |
April | 369.33 | 0.71 | 0.50 | 01-APR-11:09 | 227.20 | 0.00 | 0.00 | 100.83 | 180.59 | 0.00 | 0.00 | 59.83 |
May | 407.00 | 0.68 | 0.50 | 01-MAY-09:00 | 275.87 | 0.00 | 0.00 | 150.67 | 2357.38 | 0.00 | 0.00 | 133.00 |
June | 411.67 | 0.68 | 0.50 | 01-JUN-10:09 | 287.77 | 0.00 | 0.00 | 163.00 | 1597.69 | 0.00 | 0.00 | 100.67 |
July | 411.00 | 0.68 | 0.50 | 01-JUL-10:09 | 289.98 | 0.00 | 0.00 | 171.33 | 1423.43 | 0.00 | 0.00 | 113.00 |
August | 390.50 | 0.67 | 0.50 | 01-AUG-11:09 | 282.84 | 0.00 | 0.00 | 164.67 | 1195.64 | 0.00 | 0.00 | 134.67 |
September | 298.50 | 0.71 | 0.50 | 01-SEP-10:39 | 216.86 | 0.00 | 0.00 | 75.17 | 174.88 | 0.00 | 0.00 | 40.00 |
October | 293.50 | 0.78 | 0.50 | 01-OCT-11:09 | 153.92 | 0.00 | 0.00 | 25.83 | 1197.08 | 0.00 | 0.00 | 39.67 |
November | 299.00 | 0.79 | 0.50 | 02-NOV-10:00 | 460.10 | 0.00 | 0.00 | 25.83 | 114.07 | 0.00 | 0.00 | 0.00 |
December | 285.17 | 0.79 | 0.50 | 28-DEC-12:20 | 1388.95 | 0.00 | 0.00 | 68.00 | 102.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4071.00 | 0.73 | 474.42 | 0.00 | 0.00 | 1082.17 | 815.69 | 0.00 | 0.00 | 651.00 | ||
Minimum of Months | 263.00 | 0.67 | 0.50 | 136.69 | 0.00 | 0.00 | 4.67 | 102.80 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 411.67 | 0.81 | 0.50 | 1890.93 | 0.00 | 0.00 | 171.33 | 2357.38 | 0.00 | 0.00 | 134.67 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.68 | 0.50 | 01-JAN-10:50 | 162.73 | 10.92 | 0.00 | 83.33 | 135.93 | 14.37 | 1.00 | 55.67 |
February | 263.00 | 0.68 | 0.50 | 01-FEB-13:39 | 173.57 | 10.64 | 0.00 | 83.50 | 142.81 | 14.15 | 6.33 | 58.67 |
March | 351.67 | 0.62 | 0.50 | 01-MAR-09:09 | 226.65 | 12.23 | 0.00 | 173.33 | 189.08 | 15.86 | 33.33 | 133.33 |
April | 369.33 | 0.61 | 0.50 | 01-APR-09:39 | 1271.89 | 14.06 | 33.83 | 214.67 | 224.01 | 16.35 | 57.83 | 166.67 |
May | 407.00 | 0.59 | 0.50 | 01-MAY-07:49 | 305.78 | 13.59 | 0.00 | 270.67 | 262.74 | 17.21 | 80.00 | 226.50 |
June | 411.67 | 0.59 | 0.50 | 01-JUN-07:19 | 308.95 | 13.53 | 0.00 | 274.17 | 265.93 | 17.13 | 84.33 | 224.17 |
July | 411.00 | 0.59 | 0.50 | 01-JUL-08:39 | 315.84 | 13.78 | 0.00 | 277.17 | 271.49 | 17.42 | 92.83 | 228.33 |
August | 390.50 | 0.58 | 0.50 | 01-AUG-08:09 | 959.44 | 15.08 | 33.83 | 270.50 | 274.36 | 17.64 | 92.00 | 224.50 |
September | 298.50 | 0.61 | 0.50 | 01-SEP-07:00 | 254.83 | 12.83 | 0.00 | 200.50 | 211.37 | 16.52 | 47.00 | 151.50 |
October | 293.50 | 0.66 | 0.50 | 01-OCT-10:39 | 1185.78 | 13.03 | 32.33 | 119.50 | 886.77 | 16.69 | 46.00 | 96.00 |
November | 299.00 | 0.66 | 0.50 | 01-NOV-09:20 | 168.36 | 11.20 | 0.00 | 86.17 | 303.36 | 16.66 | 30.17 | 79.17 |
December | 285.17 | 0.69 | 0.50 | 01-DEC-11:09 | 152.88 | 10.92 | 0.00 | 70.33 | 127.24 | 14.37 | 0.00 | 36.83 |
Annual Sum or Average | 4071.00 | 0.63 | 470.78 | 12.83 | 100.00 | 2123.83 | 273.10 | 16.34 | 570.83 | 1681.33 | ||
Minimum of Months | 263.00 | 0.58 | 0.50 | 152.88 | 10.64 | 0.00 | 70.33 | 127.24 | 14.15 | 0.00 | 36.83 | |
Maximum of Months | 411.67 | 0.69 | 0.50 | 1271.89 | 15.08 | 33.83 | 277.17 | 886.77 | 17.64 | 92.83 | 228.33 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.85 | 0.65 | 29-JAN-16:30 | 227.96 | 21.55 | 95.33 | 21.50 | 84.01 | 19.22 | 57.17 | 0.00 |
February | 263.00 | 0.83 | 0.61 | 11-FEB-17:10 | 338.75 | 22.08 | 109.00 | 34.33 | 117.65 | 20.52 | 92.67 | 6.33 |
March | 351.67 | 0.80 | 0.61 | 02-MAR-17:19 | 237.74 | 21.62 | 143.17 | 44.33 | 193.36 | 22.78 | 155.33 | 28.33 |
April | 369.33 | 0.80 | 0.61 | 03-APR-17:10 | 212.23 | 19.98 | 133.50 | 34.83 | 245.34 | 21.72 | 171.00 | 37.83 |
May | 407.00 | 0.77 | 0.61 | 01-MAY-15:20 | 236.69 | 20.24 | 146.83 | 50.00 | 256.94 | 21.47 | 189.33 | 54.50 |
June | 411.67 | 0.77 | 0.61 | 01-JUN-15:09 | 244.59 | 20.10 | 141.67 | 56.17 | 218.91 | 21.41 | 199.33 | 42.83 |
July | 411.00 | 0.77 | 0.61 | 02-JUL-14:00 | 245.02 | 20.19 | 147.33 | 62.67 | 212.44 | 21.44 | 197.33 | 50.17 |
August | 390.50 | 0.76 | 0.61 | 01-AUG-14:00 | 251.67 | 20.74 | 167.67 | 69.50 | 255.14 | 21.84 | 203.00 | 58.50 |
September | 298.50 | 0.78 | 0.61 | 03-SEP-15:09 | 312.11 | 21.89 | 130.83 | 48.83 | 269.65 | 22.66 | 145.83 | 37.00 |
October | 293.50 | 0.82 | 0.61 | 01-OCT-16:10 | 313.36 | 21.96 | 113.83 | 35.17 | 246.60 | 22.20 | 111.00 | 27.17 |
November | 299.00 | 0.84 | 0.64 | 01-NOV-15:20 | 265.44 | 22.25 | 112.33 | 28.67 | 91.68 | 19.39 | 78.83 | 0.00 |
December | 285.17 | 0.86 | 0.66 | 26-DEC-15:30 | 218.68 | 21.30 | 84.67 | 17.83 | 80.60 | 19.14 | 51.33 | 0.00 |
Annual Sum or Average | 4071.00 | 0.80 | 255.52 | 21.04 | 1526.17 | 503.83 | 196.24 | 21.24 | 1652.17 | 342.67 | ||
Minimum of Months | 263.00 | 0.76 | 0.61 | 212.23 | 19.98 | 84.67 | 17.83 | 80.60 | 19.14 | 51.33 | 0.00 | |
Maximum of Months | 411.67 | 0.86 | 0.66 | 338.75 | 22.25 | 167.67 | 69.50 | 269.65 | 22.78 | 203.00 | 58.50 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.656939E+10 | 27072.24 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.439666E+10 | 27072.24 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123392E+10 | 27072.24 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215558E+09 | 27072.24 | 06-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53742.59 | 89.57 | 11-MAY-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211817E+09 | 27072.24 | 26-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139982E+10 | 27072.24 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.369283E+10 | 27072.24 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.656939E+10 | 27072.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.209097E+11 | 85629.32 | 04-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119808E+11 | 85629.32 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.297346E+09 | 20405.75 | 22-MAR-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167263E+10 | 85629.32 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102583E+11 | 85629.32 | 02-DEC-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.451188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209097E+11 | 85629.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.419337E+11 | 91895.78 | 07-JAN-18:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.251106E+11 | 128684.64 | 12-FEB-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.531260E+10 | 39959.73 | 03-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.723569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.419337E+11 | 128684.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 26949984.30 | 26949984.30 | 2311.56 | 28-FEB-15:00 | 2311.56 | 0.00 |
March | 0.00 | 0.00 | 0.314432E+09 | 0.259747E+09 | 6153.24 | 30-MAR-16:00 | 5367.32 | 0.00 |
April | 0.00 | 0.00 | 0.178176E+10 | 0.154553E+10 | 7546.74 | 12-APR-16:00 | 7546.74 | 0.00 |
May | 0.00 | 0.00 | 0.472577E+10 | 0.364969E+10 | 24039.81 | 31-MAY-05:02 | 11668.97 | 0.00 |
June | 0.00 | 0.00 | 0.962398E+10 | 0.716801E+10 | 26064.39 | 26-JUN-05:01 | 12227.90 | 0.00 |
July | 0.00 | 0.00 | 0.110170E+11 | 0.784510E+10 | 26463.30 | 27-JUL-05:01 | 10133.41 | 0.00 |
August | 0.00 | 0.00 | 0.126861E+11 | 0.885626E+10 | 26930.36 | 24-AUG-05:01 | 14380.36 | 0.00 |
September | 0.00 | 0.00 | 0.727484E+10 | 0.535316E+10 | 25510.25 | 07-SEP-05:01 | 16522.62 | 0.00 |
October | 0.00 | 0.00 | 0.179323E+10 | 0.129035E+10 | 25697.32 | 19-OCT-05:03 | 9678.46 | 0.00 |
November | 0.00 | 0.00 | 55968658.64 | 45336632.48 | 2154.56 | 02-NOV-14:00 | 1597.56 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.493000E+11 | 0.360401E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.126861E+11 | 0.885626E+10 | 26930.36 | 16522.62 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.803537E+09 | 0.731886E+09 | 20121.70 | 16-APR-14:30 | 19547.74 | 0.00 |
May | 0.00 | 0.00 | 0.574533E+10 | 0.426822E+10 | 73930.11 | 21-MAY-10:55 | 42500.03 | 0.00 |
June | 0.00 | 0.00 | 0.212023E+11 | 0.149640E+11 | 77938.72 | 25-JUN-08:25 | 39696.27 | 0.00 |
July | 0.00 | 0.00 | 0.277504E+11 | 0.191626E+11 | 78867.65 | 09-JUL-08:65 | 35494.63 | 0.00 |
August | 0.00 | 0.00 | 0.306227E+11 | 0.202582E+11 | 84400.15 | 20-AUG-07:25 | 30329.01 | 0.00 |
September | 0.00 | 0.00 | 0.101880E+11 | 0.692391E+10 | 80008.05 | 17-SEP-11:25 | 38662.54 | 0.00 |
October | 0.00 | 0.00 | 0.468886E+09 | 0.304764E+09 | 13300.20 | 11-OCT-14:10 | 8327.63 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.967811E+11 | 0.666135E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.306227E+11 | 0.202582E+11 | 84400.15 | 42500.03 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.393116E+09 | 0.04 | 302.98 | 03-JAN-04:00 | 0.08 |
February | 0.217295E+09 | 0.02 | 302.98 | 01-FEB-07:00 | 0.08 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.116525E+09 | 0.01 | 302.98 | 02-DEC-05:00 | 0.08 |
Annual Sum or Average | 0.726937E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.393116E+09 | 0.04 | 302.98 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.672473E+09 | 0.38 | 1192.32 | 02-JAN-06:01 | 0.94 |
February | 0.569919E+09 | 0.33 | 1192.32 | 01-FEB-06:01 | 0.94 |
March | 0.548501E+09 | 0.25 | 1192.32 | 01-MAR-06:01 | 0.94 |
April | 0.478963E+09 | 0.22 | 1192.32 | 06-APR-05:01 | 0.94 |
May | 0.495485E+09 | 0.22 | 1192.32 | 19-MAY-05:02 | 0.93 |
June | 0.533732E+09 | 0.24 | 1192.32 | 01-JUN-05:02 | 0.93 |
July | 0.551182E+09 | 0.24 | 1192.32 | 01-JUL-05:01 | 0.92 |
August | 0.605900E+09 | 0.26 | 1192.32 | 01-AUG-05:01 | 0.92 |
September | 0.495712E+09 | 0.23 | 1192.32 | 01-SEP-05:01 | 0.93 |
October | 0.479665E+09 | 0.21 | 1192.32 | 19-OCT-05:03 | 0.92 |
November | 0.495939E+09 | 0.23 | 1192.32 | 01-NOV-05:01 | 0.94 |
December | 0.584732E+09 | 0.29 | 1192.32 | 01-DEC-06:01 | 0.94 |
Annual Sum or Average | 0.651220E+10 | 0.26 | |||
Minimum of Months | 0.478963E+09 | 0.21 | 1192.32 | 0.92 | |
Maximum of Months | 0.672473E+09 | 0.38 | 1192.32 | 0.94 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.171567E+10 | 0.52 | 2806.53 | 04-JAN-06:01 | 0.91 |
February | 0.136795E+10 | 0.40 | 2806.53 | 02-FEB-06:01 | 0.91 |
March | 0.120839E+10 | 0.23 | 1490.50 | 22-MAR-06:05 | 0.66 |
April | 0.111289E+10 | 0.21 | 1122.61 | 19-APR-15:50 | 0.55 |
May | 0.118367E+10 | 0.22 | 2110.84 | 19-MAY-17:43 | 0.79 |
June | 0.131804E+10 | 0.28 | 2806.53 | 04-JUN-13:53 | 0.90 |
July | 0.139917E+10 | 0.31 | 2806.53 | 02-JUL-12:13 | 0.90 |
August | 0.146961E+10 | 0.32 | 2806.53 | 01-AUG-17:06 | 0.90 |
September | 0.117813E+10 | 0.24 | 2806.53 | 07-SEP-17:08 | 0.90 |
October | 0.111139E+10 | 0.20 | 1122.61 | 10-OCT-13:20 | 0.54 |
November | 0.111755E+10 | 0.25 | 2806.53 | 22-NOV-06:01 | 0.91 |
December | 0.142142E+10 | 0.44 | 2806.53 | 02-DEC-05:33 | 0.91 |
Annual Sum or Average | 0.156039E+11 | 0.30 | |||
Minimum of Months | 0.111139E+10 | 0.20 | 1122.61 | 0.54 | |
Maximum of Months | 0.171567E+10 | 0.52 | 2806.53 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.672473E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.576706E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.626683E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.915747E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.162584E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.282529E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.317597E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.359384E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.218872E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.903110E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.509933E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.584732E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.181990E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.509933E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.359384E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.171567E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.136795E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.120839E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.132687E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.264589E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.664664E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.836220E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.904171E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.370031E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.123219E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.111755E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.142142E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.397868E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111755E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.904171E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.672473E+09 | 0.00 | 0.656939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.569919E+09 | 26949984.30 | 0.439666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.548501E+09 | 0.314432E+09 | 0.123392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.478963E+09 | 0.178176E+10 | 0.215558E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.495485E+09 | 0.471322E+10 | 53742.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.533732E+09 | 0.960395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.551182E+09 | 0.109992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.605900E+09 | 0.126696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.495712E+09 | 0.725123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.479665E+09 | 0.179028E+10 | 0.211817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.495939E+09 | 55968658.64 | 0.139982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.584732E+09 | 0.00 | 0.369283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.651220E+10 | 0.492066E+11 | 0.177201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.478963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.672473E+09 | 0.126696E+11 | 0.656939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.171567E+10 | 0.00 | 0.209097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136795E+10 | 0.00 | 0.119808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120839E+10 | 0.00 | 0.297346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111289E+10 | 0.803537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118367E+10 | 0.567352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131804E+10 | 0.211198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139917E+10 | 0.277344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146961E+10 | 0.306062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117813E+10 | 0.101372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111139E+10 | 0.468886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111755E+10 | 0.00 | 0.167263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142142E+10 | 0.00 | 0.102583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156039E+11 | 0.965436E+11 | 0.451188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171567E+10 | 0.306062E+11 | 0.209097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.672473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.569919E+09 | 0.00 | 0.00 | 0.00 | 6786500.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.548501E+09 | 0.00 | 0.00 | 0.00 | 78181496.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.478963E+09 | 0.00 | 0.00 | 0.00 | 0.436784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.495485E+09 | 0.00 | 0.00 | 0.00 | 0.113035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.533732E+09 | 0.00 | 0.00 | 0.00 | 0.229156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.551182E+09 | 0.00 | 0.00 | 0.00 | 0.262478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.605900E+09 | 0.00 | 0.00 | 0.00 | 0.298794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.495712E+09 | 0.00 | 0.00 | 0.00 | 0.169301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.479665E+09 | 0.00 | 0.00 | 0.00 | 0.423444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.495939E+09 | 0.00 | 0.00 | 0.00 | 13993855.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.584732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.651220E+10 | 0.00 | 0.00 | 0.00 | 0.116868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.478963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.672473E+09 | 0.00 | 0.00 | 0.00 | 0.298794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.171567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111289E+10 | 0.00 | 0.00 | 0.00 | 0.213975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118367E+10 | 0.00 | 0.00 | 0.00 | 0.146222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131804E+10 | 0.00 | 0.00 | 0.00 | 0.532860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139917E+10 | 0.00 | 0.00 | 0.00 | 0.696303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146961E+10 | 0.00 | 0.00 | 0.00 | 0.757209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117813E+10 | 0.00 | 0.00 | 0.00 | 0.252218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111139E+10 | 0.00 | 0.00 | 0.00 | 0.120803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156039E+11 | 0.00 | 0.00 | 0.00 | 0.241829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171567E+10 | 0.00 | 0.00 | 0.00 | 0.757209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 62545190.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186009E+10 | 0.00 | 0.00 | 0.12 |
February | 0.161443E+09 | 41360.16 | 0.00 | 31711.68 | 0.00 | 0.119805E+10 | 17994095.42 | 0.00 | 0.14 |
March | 0.574636E+09 | 10136866.55 | 0.00 | 341215.98 | 284489.74 | 0.338293E+09 | 0.325655E+09 | 0.00 | 0.21 |
April | 0.272113E+09 | 47160475.02 | 0.00 | 1422963.85 | 0.00 | 37551521.47 | 0.817211E+09 | 0.00 | 0.31 |
May | 25445767.35 | 0.373846E+09 | 0.00 | 2482130.54 | 0.00 | 0.00 | 0.926802E+09 | 0.00 | 0.35 |
June | 1200553.65 | 0.132862E+10 | 0.00 | 3931028.13 | 0.00 | 0.00 | 0.269768E+09 | 0.00 | 0.22 |
July | 33376.43 | 0.175440E+10 | 0.00 | 3087543.29 | 0.00 | 0.00 | 73794782.55 | 0.00 | 0.15 |
August | 0.00 | 0.206362E+10 | 0.00 | 2717356.53 | 0.00 | 0.00 | 29287936.23 | 0.00 | 0.15 |
September | 1308460.05 | 0.853771E+09 | 0.00 | 3389007.05 | 0.00 | 0.00 | 0.617616E+09 | 0.00 | 0.27 |
October | 0.353721E+09 | 0.147769E+09 | 0.00 | 1953107.78 | 0.00 | 53750667.27 | 0.115618E+10 | 0.00 | 0.31 |
November | 0.510070E+09 | 0.00 | 188315.36 | 368359.48 | 0.00 | 0.421237E+09 | 0.397422E+09 | 1484.39 | 0.19 |
December | 0.252863E+09 | 0.00 | 50278.38 | 0.00 | 107776.98 | 0.113370E+10 | 0.00 | 507.80 | 0.12 |
Annual Sum or Average | 0.221538E+10 | 0.657937E+10 | 238593.74 | 19724424.30 | 392266.72 | 0.504267E+10 | 0.463173E+10 | 1992.18 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.574636E+09 | 0.206362E+10 | 188315.36 | 3931028.13 | 284489.74 | 0.186009E+10 | 0.115618E+10 | 1484.39 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.225195E+10 | 0.00 | 0.00 | 0.00 | 44531.07 | 0.287668E+10 | 0.00 | 0.00 | 0.17 |
February | 0.166161E+10 | 0.00 | 0.00 | 0.00 | 9886817.42 | 0.175144E+10 | 0.00 | 0.00 | 0.18 |
March | 0.282534E+10 | 0.00 | 0.00 | 0.00 | 19138036.68 | 52067653.00 | 0.00 | 0.00 | 0.19 |
April | 0.232575E+10 | 4023999.47 | 0.00 | 715446.52 | 864562.44 | 0.00 | 0.368462E+09 | 0.00 | 0.24 |
May | 0.140835E+10 | 0.391315E+09 | 0.00 | 1950161.58 | 0.00 | 0.00 | 0.101839E+10 | 0.00 | 0.27 |
June | 0.195732E+09 | 0.294535E+10 | 0.00 | 3564949.60 | 0.00 | 0.00 | 0.960652E+09 | 0.00 | 0.28 |
July | 0.239459E+09 | 0.439909E+10 | 0.00 | 1570448.01 | 0.00 | 0.00 | 0.460053E+09 | 0.00 | 0.22 |
August | 37329262.52 | 0.511670E+10 | 0.00 | 1993365.29 | 0.00 | 0.00 | 0.680854E+09 | 0.00 | 0.25 |
September | 0.847735E+09 | 0.123174E+10 | 0.00 | 3913184.32 | 4102569.32 | 0.00 | 0.140231E+10 | 0.00 | 0.30 |
October | 0.316990E+10 | 40806044.83 | 0.00 | 153976.48 | 0.00 | 0.00 | 0.196658E+09 | 0.00 | 0.19 |
November | 0.275414E+10 | 0.00 | 0.00 | 0.00 | 12228721.59 | 0.107310E+09 | 0.00 | 0.00 | 0.17 |
December | 0.257540E+10 | 0.00 | 0.00 | 0.00 | 16818303.08 | 0.726006E+09 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.202927E+11 | 0.141290E+11 | 0.00 | 13861531.79 | 63083541.60 | 0.551350E+10 | 0.508738E+10 | 0.00 | 0.22 |
Minimum of Months | 37329262.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.316990E+10 | 0.511670E+10 | 0.00 | 3913184.32 | 19138036.68 | 0.287668E+10 | 0.140231E+10 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:42:57
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.515654E+12 | 0.543463E+11 | 0.00 | 0.706257E+10 | 0.229188E+11 |
February | 0.538091E+12 | 0.421932E+11 | 0.00 | 0.482160E+10 | 0.137383E+11 |
March | 0.861533E+12 | 0.342687E+11 | 0.00 | 0.412623E+10 | 0.113121E+10 |
April | 0.101687E+13 | 0.329346E+11 | 0.00 | 0.381350E+10 | 0.334066E+10 |
May | 0.115508E+13 | 0.341342E+11 | 0.00 | 0.266123E+10 | 0.130637E+11 |
June | 0.115823E+13 | 0.418180E+11 | 0.00 | -0.279708E+10 | 0.384464E+11 |
July | 0.111896E+13 | 0.489611E+11 | 0.00 | -0.536967E+10 | 0.483552E+11 |
August | 0.103746E+13 | 0.464597E+11 | 0.00 | -0.641943E+10 | 0.538688E+11 |
September | 0.778250E+12 | 0.312088E+11 | 0.00 | 0.799355E+09 | 0.216780E+11 |
October | 0.706637E+12 | 0.391334E+11 | 0.00 | 0.474470E+10 | 0.290977E+10 |
November | 0.476621E+12 | 0.315695E+11 | 0.00 | 0.418311E+10 | 0.154176E+10 |
December | 0.420356E+12 | 0.391607E+11 | 0.00 | 0.469380E+10 | 0.786403E+10 |
Annual Sum or Average | 0.978375E+13 | 0.476188E+12 | 0.00 | 0.223199E+11 | 0.228857E+12 |
Minimum of Months | 0.420356E+12 | 0.312088E+11 | 0.00 | -0.641943E+10 | 0.113121E+10 |