Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 10:43:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 412.27 | 85.27 | 85.27 |
Net Site Energy | 412.27 | 85.27 | 85.27 |
Total Source Energy | 1299.54 | 268.77 | 268.77 |
Net Source Energy | 1299.54 | 268.77 | 268.77 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 70.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 82.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 61.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 34.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 409.33 | 2.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 2.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 70.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 82.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 61.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 13.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 21.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 23.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 70.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 82.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 61.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 34.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 23.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 29.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 26.57 | 0.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 84.66 | 0.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 29.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 26.57 | 0.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 84.66 | 0.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 409.330 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 409.330 | 100.00 |
Total On-Site and Utility Electric Sources | 409.330 | 100.00 |
Total Electricity End Uses | 409.330 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 4.33 |
Time Setpoint Not Met During Occupied Cooling | 48.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2955.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.9682 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.5521 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.9682 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.5521 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.8362 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-15:30 | 10-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 13-JUL-11:39 |
Heating | 0.00 | 18541.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15775.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4182.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4718.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1577.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 36288.45 | 18541.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 18541.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 15775.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 4182.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2413.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1577.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 222.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 261.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 195.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 110.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 73.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1296.35 | 3.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 46.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 54.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 268.11 | 0.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 46.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 54.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 15.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 268.11 | 0.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.08 |
ZONE2 FINE STORAGE DIRECT AIR | 2.56 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.992790 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.992790 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 40597.98 |
PSZ-OFFICE HEATING COIL | 26718.29 |
PSZ-FINE STORAGE HEATING COIL | 81133.74 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 40597.98 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.00 | 1.08 |
PSZ-FINE STORAGE | 2.56 | 2.56 | 2.56 | 2.56 | 2.56 | 2.56 | 1.00 | 1.00 | 2.56 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.08 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.56 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.08 | 1190.80 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.56 | 2734.20 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 0.709859 | 22106.26 | 26718.29 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.56 | 2.56 | 2.56 | 1.69 | 63452.10 | 81133.74 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.08 | 0.537772 | 0.717027 | 22106.26 | 11053.13 | 0.765100 | 0.765100 |
PSZ-FINE STORAGE COOLING COIL | 2.56 | 1.28 | 1.70 | 63452.10 | 31726.05 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.968 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.042 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.552 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1650.627 | 6.968 | 129.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1650.627 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 11383.888 | 3.552 | 164.984 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11383.888 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5892 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.697 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.53319589E-11 | 0.95168195E-16 | 0.18684196E-15 | 0.0000000 |
5 | 1 | -5.2159738 | 0.43009049E-04 | -0.27188221E-04 | 0.68723469E-11 |
6 | 0 | 5.8052090 | 0.58919217 | 0.58926237 | |
7 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
8 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
9 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
10 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
11 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
12 | 4 | 0.65556131E-12 | 0.57298371E-15 | -0.14028959E-14 | 0.12439065E-15 |
13 | 3 | -0.34087882E-03 | 0.75102955E-06 | -0.49042705E-04 | 0.12583838E-12 |
14 | 2 | 1.6337693 | 0.17263784E-01 | 1.0601096 | -0.65347397E-04 |
15 | 1 | -7.2734424 | 0.46143774 | -16.581274 | 0.31301327 |
16 | 0 | 6.4190060 | 0.30028979 | 16.300205 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.14028959E-14 | 0.57298371E-15 | 0.65556131E-12 | 0.12439065E-15 |
85 | 3 | -0.49042705E-04 | 0.75102955E-06 | -0.34087882E-03 | 0.12583838E-12 |
86 | 2 | 1.0601096 | 0.17263784E-01 | 1.6337693 | -0.65347397E-04 |
87 | 1 | -16.581274 | 0.46143774 | -7.2734424 | 0.31301327 |
88 | 0 | 16.300205 | 0.30028979 | 6.4190060 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.454_SHGC_SOUTH_0.249 | 34 | 1 | VerySmooth | 2.580 | 2.580 | 1.000 | 0.250 | ||
2 | NONRESWINDOW_U_0.454_SHGC_NORTH_0.249 | 35 | 1 | VerySmooth | 2.580 | 2.580 | 1.000 | 0.250 | ||
3 | NONRESWINDOW_U_0.454_SHGC_EAST_0.249 | 36 | 1 | VerySmooth | 2.580 | 2.580 | 1.000 | 0.250 | ||
4 | NONRESWINDOW_U_0.454_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.580 | 2.580 | 1.000 | 0.250 | ||
5 | SKYLIGHT_U_0.65_SHGC_0.3 | 38 | 1 | VerySmooth | 3.695 | 3.695 | 1.000 | 0.302 | ||
6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | 39 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.61639E-002 | 0.16038 | 0.61778 | 0.61778 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12084 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.61639E-002 | 0.16038 | 0.61778 | 0.61778 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12084 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.61639E-002 | 0.16038 | 0.61778 | 0.61778 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12084 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.61639E-002 | 0.16038 | 0.61778 | 0.61778 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12084 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.19440 | 0.51093 | 0.51093 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.96142E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.12500 | 0.12500 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.575 | 0.301 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.867 | 0.549 | 0.401 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.6220E-005 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4525E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7981E-005 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5447E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4652E-005 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.7024E-004 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.8648E-005 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.6551E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5640E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4729E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3307E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5838E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4024E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5040E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3945E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4949E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5520E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1873E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9860E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2322E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.0368E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1078E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9614E-004 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8929E-005 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7840E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.5905E-005 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1141E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7862E-005 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3954E-004 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1940E-005 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3502E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2167E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1640E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0947E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1781E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2073E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.9141E-004 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9976E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0462E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7378E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9599E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5120E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0879E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5955E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1018E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5726E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8419E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5748E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.6465E-004 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6344E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0141E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7414E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1483E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6226E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4212E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5828E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0731E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4494E-005 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6376E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6320E-005 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4898E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1518E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1230E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7635E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0797E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.8368E-005 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.0669E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.2888E-005 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.7280E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7763E-005 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5923E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3189E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0890E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7551E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.1618E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9236E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.3656E-004 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3946E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6412E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.4188E-005 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9561E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1102E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6476E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0779E-004 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8565E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.4490E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3714E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8629E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3343E-005 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.9182E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.3632E-005 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.5098E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1466E-005 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0639E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1086E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.9267E-004 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5174E-005 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4845E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1991E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5970E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0436E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.0696E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.9227E-005 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1977E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3589E-005 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1590E-004 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.0736E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6126E-004 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9096E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0005E-003 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7155E-005 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2526E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2676E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7216E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8717E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9784E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6059E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6106E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5080E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8003E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8065E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3075E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3931E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1788E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2026E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0199E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8583E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9501E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8047E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9805E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3183E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2926E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4101E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4190E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1462E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0024E-004 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1503E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7938E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1089E-005 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9957E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1096E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3773E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7576E-005 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5836E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3175E-005 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5950E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3350E-005 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4807E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8018E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7922E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0228E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.9651E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3191E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2146E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0343E-005 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8221E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7707E-005 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7449E-004 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8417E-005 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3904E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1730E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6864E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4428E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9840E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0325E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2391E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5946E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5127E-005 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5302E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6246E-005 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.9645E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2000E-005 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3984E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8582E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4797E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8267E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2788E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8090E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5305E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9485E-005 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7956E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.7857E-005 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2461E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.5095E-005 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4784E-004 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6433E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9947E-004 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0186E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5562E-004 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8016E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9480E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0320E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9864E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9402E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1179E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0757E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2749E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0564E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1896E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4329E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5545E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6395E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0015E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0194E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9023E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8752E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5404E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1251E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4990E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0250E-005 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5747E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.4791E-005 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8428E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0372E-004 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0183E-003 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8474E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9030E-004 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7759E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3798E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.4227E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4733E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.2495E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3089E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3895E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8676E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.7135E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4834E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8220E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3216E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6605E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8858E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9056E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2760E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.0953E-004 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0941E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.9845E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4503E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1568E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.7011E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6329E-005 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9350E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9445E-005 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0494E-004 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6768E-005 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8779E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9924E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0366E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6493E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4625E-004 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1057E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9343E-005 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8334E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6080E-005 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3255E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.4317E-005 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0129E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3300E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4721E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9064E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2508E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3626E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6732E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.4533E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6324E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7893E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4239E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.5295E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4179E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2794E-005 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5310E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0948E-005 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3883E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0192E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5457E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9430E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0997E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1795E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1020E-005 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0090E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3922E-005 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0063E-004 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6793E-005 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3462E-005 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6108E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3162E-005 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1381E-005 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8972E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2462E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2304E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1397E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5988E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2131E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3751E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8453E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9731E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2895E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6608E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.0989E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9761E-005 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4747E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3581E-005 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1150E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8907E-005 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3149E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9209E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.6519E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.4892E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1921E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.3591E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0748E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.7866E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1636E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.6409E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4328E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.2321E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.7942E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1311E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.5113E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1270E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3974E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7815E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.0997E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.1219E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.6781E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.5111E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.2925E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2429E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9254E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.9076E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1054E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.1678E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.6810E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.3018E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.2891E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2428E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9254E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10884.21100 | 13061.05321 | 0.89629 | 1.07554 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 33.00467 | 1.65347E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 6832.80419 | 8199.36503 | 0.19173 | 0.23008 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 4.60000 | 5.25715E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 33168.81719 | 39802.58063 | 2.12935 | 2.55522 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65362E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 14173.96847 | 17008.76216 | 0.33543 | 0.42471 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 4.60000 | 5.25715E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 33.90000 | 1.65364E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 33831.65340 | 40597.98409 | 0.82733 | 0.99279 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60000 | 5.25715E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 16601.81 | 1.07554 | 1.07554 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 7311.18 | 0.23008 | 0.23008 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 49067.47 | 2.55522 | 2.55522 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 18177.24 | 0.42471 | 0.42471 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07554 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.55522 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.99279 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.99279 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 40597.98297 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 40597.98409 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07554 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07554 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07554 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07554 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07554 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.07554 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.55522 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.55522 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.55522 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.55522 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.55522 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.55522 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.07554 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.55522 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07554 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07554 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1190.79822 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07554 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07554 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07554 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70986 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07554 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53777 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71703 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22106.26000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11053.13000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76510 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76510 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22106.26000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26718.29487 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26718.29487 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.55522 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.55522 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2734.20183 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.55522 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.55522 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.55522 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.68644 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.55522 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.27761 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.70348 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 63452.10000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 31726.05000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 63452.10000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 81133.73940 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 81133.73940 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 21271.0 | 11.88 | 11.61 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 61466.0 | 12.06 | 11.79 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 4.4261045722E-002 | 3.4867040714E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1107072933 | 0.1925355655 | Pass | Pass | 0.5814767036 | 4.3726024716 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 6.0199469366E-002 | 5.1314805121E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 10650.79 | 440.77 | 0.00 | -28.2 | 363.12 | 11426.53 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.545 | 0.589 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.454_SHGC_WEST_0.249 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.580 | 0.250 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.454_SHGC_WEST_0.249 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.580 | 0.250 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.454_SHGC_NORTH_0.249 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.580 | 0.250 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.454_SHGC_NORTH_0.249 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.580 | 0.250 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.65_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.695 | 0.302 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.575 | 0.301 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.247 | 0.429 | 0.370 | |||||||||||||||||
North Total or Average | 6.51 | 2.580 | 0.250 | 0.250 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.384 | 0.444 | 0.380 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.9682 | 236.88 | 1650.63 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 32.87 | 0.0000 | Y | 10.18 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 18.32 | 0.0000 | Y | 35.59 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.5521 | 3204.84 | 11383.89 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 17.26 | 0.0000 | Y | 36.88 |
Interior Lighting Total | 4.8362 | 4835.13 | 23383.49 | 82.66 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10348.98 | 2587.24 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 11383.89 | 2845.97 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1650.63 | 478.68 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1650.63 | 165.06 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 41.73 | 41.73 | 0.97 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.73 | 62.73 | 50.70 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.73 | 48.93 | 10.02 | |
Exterior Lighting Total | 5520.82 | 61.69 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22106.26 | 16913.50 | 5192.76 | 0.77 | 3.80 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 63452.10 | 44485.00 | 18967.10 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 21271.0 | 11.88 | 11.61 | ||||
PSZ-FINE STORAGE COOLING COIL | 61466.0 | 12.06 | 11.79 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 40597.98 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26718.29 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 81133.74 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.99 | 92.24 | 92.91 | 1.00 | 4.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1190.80 | 1107.16 | 1.00 | 1.38 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.56 | 2734.20 | 1070.05 | 1.00 | 1.28 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10884.21 | 13061.05 | 55.14 | 0.896 | 1.076 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 23.90 | 23.90 | 0.00853 | 33.00 | 0.01653 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 33168.82 | 39802.58 | 28.56 | 2.129 | 2.555 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 26.70 | 26.70 | 0.00908 | 33.82 | 0.01654 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 0.00 | 34.36 | 0.01661 | 33.90 | 0.01654 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 6832.80 | 8199.37 | 34.61 | 0.192 | 0.230 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00793 | 4.60 | 0.00526 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 14173.97 | 17008.76 | 12.21 | 0.335 | 0.425 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00700 | 4.60 | 0.00526 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 33831.65 | 40597.98 | 12.67 | 0.827 | 0.993 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00638 | 4.60 | 0.00526 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.08 | 1.08 | 0.23 | 0.23 | 1.0755 | 1.0755 | 1.0755 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.56 | 2.56 | 0.42 | 0.42 | 2.5552 | 2.5552 | 2.5552 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 40597.983 | 40597.983 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 40597.98 | 40597.98 | 0.992790 | 10.00 | 8.61 | 0.00637564 | 43.33 | 22.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 10.00 | 0.00637564 | 83.6460 | 40597.98 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 22106.260 | 16913.500 | 1.075540 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 11053.13 | 9092.52 | 0.717027 | 25.67 | 17.63 | 0.00929322 | 12.00 | 11.25 | 0.00800000 | 33.11 | 0.01653489 | 24.92 | 14.2651 | 23.90 | 0.00853168 | 46.1685 | 10877.96 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26718.295 | 26718.295 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26718.29 | 26718.29 | 1.075544 | 19.45 | 13.95 | 0.00767330 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 9.5100 | 21.10 | 0.00792722 | 50.8978 | 6832.80 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 63452.100 | 44484.998 | 2.555220 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 31726.05 | 24003.07 | 1.703480 | 28.76 | 19.45 | 0.01032200 | 12.00 | 11.25 | 0.00800000 | 33.90 | 0.01653638 | 25.13 | 24.9320 | 26.70 | 0.00908211 | 41.5747 | 33144.82 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 81133.739 | 81133.739 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 81133.74 | 81133.74 | 2.555216 | 13.74 | 10.65 | 0.00670838 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 16.6213 | 15.56 | 0.00699768 | 63.7085 | 13923.22 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 40597.983 | 40597.983 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.992790 | 1.19449244 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 40597.98 | 40597.98 | 1.0000 | 1.19449244 | 0.992790 | 10.00 | 8.61 | 0.00637564 | 26111.4 | 43.33 | 22.14 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40597.98 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 10.00 | 0.00637564 | 10.00 | 0.00637564 | 83.6460 | 40597.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22106.260 | 16913.500 | 1.075540 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1156 | 1004.8586 | 1.2032 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.075544 | 1.29405924 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | Sensible | 11053.13 | 9092.52 | 1.0000 | 0.86270275 | 0.717027 | 25.67 | 17.63 | 0.00929322 | 49484.5 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11053.13 | 33.11 | 0.01653489 | 24.92 | 0.10228463 | 14.2651 | 23.90 | 0.00853168 | 23.90 | 0.00853168 | 46.1685 | 10877.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26718.295 | 26718.295 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.075544 | 1.29405924 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 26718.29 | 26718.29 | 1.0000 | 1.29405924 | 1.075544 | 19.45 | 13.95 | 0.00767330 | 39015.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26718.29 | 4.60 | 0.00525715 | 4.60 | 0.10228463 | 9.5100 | 21.01 | 0.00792722 | 21.10 | 0.00792722 | 50.8978 | 6832.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 63452.100 | 44484.998 | 2.555220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0281 | 1004.8586 | 1.2032 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.555216 | 3.07435122 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 31726.05 | 24003.07 | 1.0000 | 2.04957075 | 1.703480 | 28.76 | 19.45 | 0.01032200 | 55268.9 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31726.05 | 33.90 | 0.01653638 | 25.13 | 0.42471127 | 24.9320 | 26.70 | 0.00908211 | 26.70 | 0.00908211 | 41.5747 | 33144.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 81133.739 | 81133.739 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.555216 | 3.07435122 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 81133.74 | 81133.74 | 1.0000 | 3.07435122 | 2.555216 | 13.74 | 10.65 | 0.00670838 | 30752.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81133.74 | 4.60 | 0.00525715 | 4.60 | 0.42471127 | 16.6213 | 15.56 | 0.00699768 | 15.56 | 0.00699768 | 63.7085 | 13923.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialEnthalpy | 0.10 | 1.08 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialEnthalpy | 0.42 | 2.56 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2683.00 | 1535.50 | 779.00 |
ZONE2 FINE STORAGE | 3058.00 | 3278.50 | 2771.50 |
ZONE3 BULK STORAGE | 3096.17 | 3359.17 | 2896.17 |
Facility | 3163.33 | 3473.17 | 2955.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 4.33 | 48.67 | 4.33 | 48.00 |
ZONE2 FINE STORAGE | 0.00 | 142.33 | 0.00 | 0.33 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 4.33 | 191.00 | 4.33 | 48.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.488 | 0.395 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.511 | 0.186 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.101 | 0.000 | 1.169 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.59 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.56 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1755579.03 | 0.00 | 1755579.03 | 1966467.98 | 3722047.01 | 3225648.14 | 5712.13 | 2503.75 | 544.12 | 0.33 |
ZONE2 FINE STORAGE | 5330722.83 | 0.00 | 5330722.83 | 4988068.29 | 10318791.12 | 13393694.68 | 5706.21 | 2780.56 | 273.23 | 2.04 |
ZONE3 BULK STORAGE | 0.00 | 0.22E+09 | 0.22E+09 | 24851933.40 | 0.25E+09 | 30805497.77 | 7017.57 | 21.26 | 1721.17 | 4952.94 |
Total Facility | 7086301.86 | 0.22E+09 | 0.23E+09 | 31806469.67 | 0.26E+09 | 47424840.58 | 7658.28 | 3006.40 | 2486.32 | 4952.94 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1341 | 0.0000 | 0.1341 | 0.1087 | 0.2428 | 0.1023 | 588.46 | 2503.75 | 543.79 |
ZONE2 FINE STORAGE | 0.4066 | 0.0000 | 0.4066 | 0.1486 | 0.5552 | 0.4247 | 584.25 | 2780.56 | 271.19 |
ZONE3 BULK STORAGE | 0.0000 | 10.8165 | 10.8165 | 0.9539 | 11.7704 | 0.9768 | 2525.60 | 6.61 | 1103.78 |
Total Facility | 0.5407 | 10.8165 | 11.3572 | 1.2112 | 12.5684 | 1.5038 | 2534.28 | 2991.75 | 1866.89 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2541392.61 | 0.00 | 2541392.61 | 3225648.14 | 5710.63 | 0.67 | 3048.70 | 0.33 |
PSZ-FINE STORAGE | 7716834.46 | 0.00 | 7716834.46 | 13393694.68 | 5701.88 | 0.33 | 3057.79 | 2.04 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1941 | 0.0000 | 0.1941 | 0.1023 | 586.96 | 0.67 | 3048.38 |
PSZ-FINE STORAGE | 0.5886 | 0.0000 | 0.5886 | 0.4247 | 579.92 | 0.33 | 3055.75 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2800.51 | 252.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2949.09 | 112.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2145 | 0.4172 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6839 | 1.1115 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 446 |
Defaulted Fields | 391 |
Fields with Defaults | 1172 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 409.33 | 1550.86 | 01-JAN-09:50 | 36288.45 | 03-AUG-15:30 |
Electricity:Building | 232.89 | 1069.86 | 01-JAN-09:50 | 19737.10 | 06-NOV-15:40 |
Electricity:Zone:ZONE1 OFFICE | 39.35 | 520.87 | 01-JAN-00:10 | 2831.56 | 25-OCT-07:10 |
Electricity:SpaceType:GENERAL | 219.17 | 1069.86 | 01-JAN-09:50 | 18193.86 | 27-NOV-15:30 |
InteriorLights:Electricity | 82.66 | 599.99 | 01-JAN-09:50 | 8158.68 | 27-NOV-15:30 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.18 | 51.00 | 01-JAN-00:10 | 996.50 | 25-OCT-07:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 82.66 | 599.99 | 01-JAN-09:50 | 8158.68 | 27-NOV-15:30 |
LightsWired:InteriorLights:Electricity | 82.66 | 599.99 | 01-JAN-09:50 | 8158.68 | 27-NOV-15:30 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 10.18 | 51.00 | 01-JAN-00:10 | 996.50 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 82.66 | 599.99 | 01-JAN-09:50 | 8158.68 | 27-NOV-15:30 |
Electricity:Zone:ZONE2 FINE STORAGE | 35.59 | 299.97 | 01-JAN-00:10 | 3546.98 | 27-NOV-15:30 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 35.59 | 299.97 | 01-JAN-00:10 | 3546.98 | 27-NOV-15:30 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 35.59 | 299.97 | 01-JAN-00:10 | 3546.98 | 27-NOV-15:30 |
Electricity:Zone:ZONE3 BULK STORAGE | 157.95 | 249.02 | 01-JAN-09:50 | 13860.44 | 06-NOV-15:40 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 36.88 | 249.02 | 01-JAN-09:50 | 3686.43 | 27-NOV-15:30 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 36.88 | 249.02 | 01-JAN-09:50 | 3686.43 | 27-NOV-15:30 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 34.84 | 0.00 | 01-JAN-00:10 | 4785.80 | 03-AUG-16:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 13.72 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
Ventilation (simple):Fans:Electricity | 13.72 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 13.72 | 0.00 | 01-JAN-00:10 | 2305.29 | 07-MAY-14:30 |
ElectricityPurchased:Facility | 409.33 | 1550.86 | 01-JAN-09:50 | 36288.45 | 03-AUG-15:30 |
ElectricityPurchased:Plant | 409.33 | 1550.86 | 01-JAN-09:50 | 36288.45 | 03-AUG-15:30 |
Cogeneration:ElectricityPurchased | 409.33 | 1550.86 | 01-JAN-09:50 | 36288.45 | 03-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 409.33 | 1550.86 | 01-JAN-09:50 | 36288.45 | 03-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 409.33 | 1550.86 | 01-JAN-09:50 | 36288.45 | 03-AUG-15:30 |
ElectricityNet:Plant | 409.33 | 1550.86 | 01-JAN-09:50 | 36288.45 | 03-AUG-15:30 |
Cogeneration:ElectricityNet | 409.33 | 1550.86 | 01-JAN-09:50 | 36288.45 | 03-AUG-15:30 |
General:Cogeneration:ElectricityNet | 409.33 | 1550.86 | 01-JAN-09:50 | 36288.45 | 03-AUG-15:30 |
Electricity:HVAC | 91.42 | 0.00 | 01-JAN-00:10 | 18406.68 | 03-AUG-16:10 |
General:Fans:Electricity | 21.12 | 0.00 | 01-JAN-00:10 | 2480.51 | 03-AUG-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 70.31 | 0.00 | 01-JAN-00:10 | 15926.17 | 03-AUG-16:10 |
General:Cooling:Electricity | 70.31 | 0.00 | 01-JAN-00:10 | 15926.17 | 03-AUG-16:10 |
ExteriorLights:Electricity | 61.69 | 0.00 | 01-JAN-07:30 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 61.69 | 0.00 | 01-JAN-07:30 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 23.33 | 481.00 | 26-JAN-06:10 | 1773.02 | 25-JAN-13:00 |
WaterSystems:Electricity | 23.33 | 481.00 | 26-JAN-06:10 | 1773.02 | 25-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 23.33 | 481.00 | 26-JAN-06:10 | 1773.02 | 25-JAN-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2.94 | 0.00 | 01-JAN-00:10 | 18541.38 | 10-JAN-07:10 |
NaturalGas:HVAC | 2.94 | 0.00 | 01-JAN-00:10 | 18541.38 | 10-JAN-07:10 |
Heating:NaturalGas | 2.94 | 0.00 | 01-JAN-00:10 | 18541.38 | 10-JAN-07:10 |
General:Heating:NaturalGas | 2.94 | 0.00 | 01-JAN-00:10 | 18541.38 | 10-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 13-JUL-11:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 474.19 | 0.00 | 01-JAN-00:10 | 97047.35 | 03-AUG-16:10 |
EnergyTransfer:Building | 180.33 | 0.00 | 01-JAN-00:10 | 36569.62 | 03-AUG-16:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 61.48 | 0.00 | 01-JAN-00:10 | 12700.81 | 06-FEB-06:10 |
Heating:EnergyTransfer | 3.03 | 0.00 | 01-JAN-00:10 | 14412.70 | 10-JAN-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 1.99 | 0.00 | 01-JAN-00:10 | 12700.81 | 06-FEB-06:10 |
General:Heating:EnergyTransfer | 3.03 | 0.00 | 01-JAN-00:10 | 14412.70 | 10-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 1.99 | 0.00 | 01-JAN-00:10 | 12700.81 | 06-FEB-06:10 |
Cooling:EnergyTransfer | 177.30 | 0.00 | 01-JAN-00:10 | 36569.62 | 03-AUG-16:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 59.49 | 0.00 | 01-JAN-00:10 | 11971.50 | 03-AUG-16:10 |
General:Cooling:EnergyTransfer | 177.30 | 0.00 | 01-JAN-00:10 | 36569.62 | 03-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 59.49 | 0.00 | 01-JAN-00:10 | 11971.50 | 03-AUG-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 118.85 | 0.00 | 01-JAN-00:10 | 26903.76 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 1.04 | 0.00 | 01-JAN-00:10 | 7070.46 | 05-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 1.04 | 0.00 | 01-JAN-00:10 | 7070.46 | 05-FEB-08:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 117.81 | 0.00 | 01-JAN-00:10 | 26903.76 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 117.81 | 0.00 | 01-JAN-00:10 | 26903.76 | 10-SEP-14:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 293.86 | 0.00 | 01-JAN-00:10 | 60477.73 | 03-AUG-16:10 |
HeatingCoils:EnergyTransfer | 1.99 | 0.00 | 01-JAN-00:10 | 12897.41 | 10-JAN-07:10 |
CoolingCoils:EnergyTransfer | 291.86 | 0.00 | 01-JAN-00:10 | 60477.73 | 03-AUG-16:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 1.986 | -59.491 | 0.000 | 0.000 | 9.285 | 10.184 | 29.165 | 10.724 | 0.000 | 4.173 | 6.396 | 0.000 | -4.300 | 0.000 | -8.122 | -0.000 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 1.041 | -117.801 | 0.000 | 0.000 | 19.391 | 35.591 | 0.000 | 33.899 | 0.000 | 3.764 | 57.073 | 0.000 | -9.860 | 0.000 | -23.098 | -0.002 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 36.713 | 36.883 | 107.344 | 695.774 | 0.000 | 4.719 | 0.012 | 0.000 | -107.489 | 0.000 | -411.073 | -362.870 |
Total Facility | 0.000 | 0.000 | 3.027 | -177.292 | 0.000 | 0.000 | 65.388 | 82.658 | 136.508 | 740.398 | 0.000 | 12.656 | 63.481 | 0.000 | -121.649 | 0.000 | -442.293 | -362.872 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-OCT-05:02 | 0.00 | 0.00 | 0.00 | -24529.04 | 0.00 | 0.00 | 90.63 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 25262.68 | 0.00 | -451.28 | 0.00 | -974.51 | 0.00 |
ZONE2 FINE STORAGE | 11-JUN-16:12 | 0.00 | 0.00 | 0.00 | -55283.74 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 3198.06 | 0.00 | 567.56 | 51218.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-AUG-05:01 | 0.00 | 0.00 | 0.00 | -69920.53 | 0.00 | 0.00 | 561.74 | 849.01 | 2600.55 | 0.00 | 0.00 | 0.00 | 78404.62 | 0.00 | -10119.51 | 0.00 | -2375.87 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 06-FEB-06:01 | 0.00 | 0.00 | 27034.52 | 0.00 | 0.00 | 0.00 | 141.20 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -554.52 | 0.00 | -1089.51 | -26133.20 |
ZONE2 FINE STORAGE | 05-FEB-07:55 | 0.00 | 0.00 | 14140.93 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1179.25 | 0.00 | -7609.39 | -5652.25 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-FEB-06:01 | 0.00 | 0.00 | 27034.52 | 0.00 | 0.00 | 0.00 | 1298.19 | 849.01 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15646.03 | 0.00 | -11408.06 | -4728.18 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0755 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0755 | 0.0951 | 1.0000 | Not calculated | 0.1023 | 0.0951 | ||
PSZ-FINE STORAGE | 2.5552 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.5552 | 0.1662 | 1.0000 | Not calculated | 0.4247 | 0.1662 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0755 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0755 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0951 | ||
PSZ-FINE STORAGE | 2.5552 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.5552 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1662 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0755 | 1.0755 | 1.0755 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5552 | 2.5552 | 2.5552 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0755 | 1.0755 | 1.0755 | 1.0755 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.5552 | 2.5552 | 2.5552 | 2.5552 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0755 | 1.0755 | 1.0755 | No | 0.1023 | 0.4446 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5552 | 2.5552 | 2.5552 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0755 | 1.0755 | 1.0755 | 1.0755 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.5552 | 2.5552 | 2.5552 | 2.5552 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 4.33 |
Number of hours cooling loads not met | 48.33 |
Number of hours not met | 52.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 2.94 | 18541.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 70.31 | 15926.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 82.66 | 8158.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 61.69 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 13.72 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 21.12 | 2480.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 23.33 | 1773.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 409.33 |
Natural Gas | 0.00 | 2.94 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 412.27 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 17.10 |
Space Heating | 0.00 |
Space Cooling | 14.54 |
Fans (All) | 7.20 |
Service Water Heating | 4.83 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 84.66 |
Subtotal | 84.66 |
Natural Gas [MJ/m2] | |
Space Heating | 0.61 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.61 |
Subtotal | 0.61 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 20.05 |
Space Heating | 0.71 |
Space Cooling | 17.05 |
Fans (All) | 8.45 |
Service Water Heating | 5.66 |
Receptacle Equipment | 33.11 |
Miscellaneous | 14.96 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 6172.00 | 2459.17 | 128.83 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 4244.00 | 4516.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3787.00 | 2059.00 | 2865.17 | 48.83 | 0.00 |
Min | 3787.00 | 2059.00 | 0.00 | 0.00 | 0.00 |
Max | 6172.00 | 4516.00 | 2865.17 | 48.83 | 0.00 |
Average | 4734.33 | 3011.39 | 998.00 | 16.28 | 0.00 |
Sum | 14203.00 | 9034.17 | 2994.00 | 48.83 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 32463.00 | 50256.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 73490.67 | 39073.50 | 76868.17 | 1760.67 | 0.00 |
Min | 32463.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 73490.67 | 50256.00 | 76868.17 | 1760.67 | 0.00 |
Average | 46326.89 | 29776.50 | 25622.72 | 586.89 | 0.00 |
Sum | 138980.67 | 89329.50 | 76868.17 | 1760.67 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 4871.33 | 3873.50 | 15.17 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 3126.00 | 5634.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 3042.17 | 4223.83 | 1469.33 | 24.67 | 0.00 |
Min | 3042.17 | 3873.50 | 0.00 | 0.00 | 0.00 |
Max | 4871.33 | 5634.00 | 1469.33 | 24.67 | 0.00 |
Average | 3679.83 | 4577.11 | 494.83 | 8.22 | 0.00 |
Sum | 11039.50 | 13731.33 | 1484.50 | 24.67 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 29136.50 | 3890.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 24905.50 | 57813.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 59581.17 | 83641.83 | 47440.00 | 530.00 | 0.00 |
Min | 24905.50 | 3890.50 | 0.00 | 0.00 | 0.00 |
Max | 59581.17 | 83641.83 | 47440.00 | 530.00 | 0.00 |
Average | 37874.39 | 48448.61 | 15813.33 | 176.67 | 0.00 |
Sum | 113623.17 | 145345.83 | 47440.00 | 530.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:06
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100379E+10 | 19399.55 | 02-JAN-06:02 | 16.00 | 15.39 | 0.579197E+09 | 769.02 | 02-JAN-13:20 | 26.00 | 18.72 |
February | 0.138991E+10 | 15406.47 | 28-FEB-06:03 | 18.38 | 17.90 | 0.548701E+09 | 769.03 | 28-FEB-16:00 | 23.80 | 20.44 |
March | 0.219895E+10 | 14709.49 | 30-MAR-05:03 | 20.83 | 19.77 | 0.654813E+09 | 769.03 | 28-MAR-15:09 | 20.83 | 19.77 |
April | 0.435052E+10 | 18114.55 | 25-APR-05:02 | 19.30 | 17.20 | 0.632914E+09 | 769.06 | 28-APR-14:39 | 33.10 | 23.05 |
May | 0.733763E+10 | 16851.20 | 05-MAY-05:01 | 23.30 | 20.65 | 0.660523E+09 | 769.07 | 04-MAY-15:39 | 23.30 | 20.65 |
June | 0.786218E+10 | 17238.43 | 16-JUN-05:01 | 24.50 | 23.35 | 0.660560E+09 | 769.07 | 10-JUN-15:50 | 24.50 | 23.35 |
July | 0.776717E+10 | 15955.45 | 19-JUL-05:01 | 27.12 | 24.30 | 0.635217E+09 | 769.06 | 08-JUL-12:00 | 27.12 | 24.30 |
August | 0.850091E+10 | 19004.62 | 31-AUG-05:01 | 24.13 | 22.97 | 0.686028E+09 | 769.06 | 25-AUG-15:50 | 24.13 | 22.97 |
September | 0.722798E+10 | 17052.17 | 22-SEP-05:01 | 21.70 | 19.78 | 0.635178E+09 | 769.06 | 16-SEP-14:00 | 21.70 | 19.78 |
October | 0.653005E+10 | 24531.49 | 27-OCT-05:02 | 15.00 | 7.96 | 0.634867E+09 | 769.07 | 11-OCT-14:50 | 15.00 | 7.96 |
November | 0.328819E+10 | 18450.87 | 06-NOV-06:01 | 18.80 | 17.70 | 0.603988E+09 | 769.04 | 07-NOV-13:30 | 28.30 | 24.43 |
December | 0.203511E+10 | 15435.54 | 16-DEC-06:02 | 20.83 | 19.18 | 0.596921E+09 | 769.03 | 12-DEC-16:00 | 20.83 | 19.18 |
Annual Sum or Average | 0.594924E+11 | 0.752891E+10 | ||||||||
Minimum of Months | 0.100379E+10 | 14709.49 | 15.00 | 7.96 | 0.548701E+09 | 769.02 | 15.00 | 7.96 | ||
Maximum of Months | 0.850091E+10 | 24531.49 | 27.12 | 24.30 | 0.686028E+09 | 769.07 | 33.10 | 24.43 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187117E+10 | 34011.99 | 01-JAN-13:43 | 25.83 | 18.00 | 0.121004E+10 | 2246.80 | 02-JAN-15:00 | 26.00 | 18.38 |
February | 0.142253E+10 | 7040.27 | 27-FEB-15:10 | 26.00 | 20.45 | 0.123830E+10 | 2246.82 | 28-FEB-16:00 | 23.80 | 20.44 |
March | 0.184497E+10 | 13868.19 | 26-MAR-14:05 | 28.97 | 20.05 | 0.157427E+10 | 2246.81 | 31-MAR-14:39 | 23.87 | 20.12 |
April | 0.552706E+10 | 50136.46 | 23-APR-14:03 | 27.88 | 21.09 | 0.176802E+10 | 2246.94 | 27-APR-14:50 | 30.22 | 21.84 |
May | 0.156628E+11 | 54262.89 | 29-MAY-16:23 | 31.70 | 23.61 | 0.192860E+10 | 2246.94 | 12-MAY-12:39 | 31.70 | 23.61 |
June | 0.189828E+11 | 55283.53 | 11-JUN-16:12 | 32.57 | 21.40 | 0.192886E+10 | 2247.00 | 14-JUN-14:00 | 33.30 | 25.93 |
July | 0.200203E+11 | 52464.74 | 23-JUL-14:13 | 32.77 | 25.73 | 0.185481E+10 | 2247.00 | 19-JUL-12:50 | 32.77 | 25.73 |
August | 0.198417E+11 | 53072.28 | 02-AUG-05:01 | 26.00 | 25.09 | 0.200314E+10 | 2246.99 | 03-AUG-13:20 | 33.47 | 25.02 |
September | 0.149325E+11 | 52186.40 | 10-SEP-17:03 | 32.73 | 26.54 | 0.185453E+10 | 2246.95 | 09-SEP-15:09 | 32.73 | 26.54 |
October | 0.126214E+11 | 54827.60 | 01-OCT-15:43 | 27.75 | 18.33 | 0.182245E+10 | 2246.99 | 07-OCT-15:39 | 31.80 | 25.57 |
November | 0.283904E+10 | 26828.60 | 05-NOV-13:55 | 27.20 | 20.73 | 0.159721E+10 | 2246.85 | 08-NOV-14:50 | 22.88 | 16.53 |
December | 0.224294E+10 | 10193.37 | 15-DEC-14:40 | 29.00 | 21.74 | 0.139429E+10 | 2246.82 | 02-DEC-14:00 | 29.00 | 21.74 |
Annual Sum or Average | 0.117809E+12 | 0.201745E+11 | ||||||||
Minimum of Months | 0.142253E+10 | 7040.27 | 25.83 | 18.00 | 0.121004E+10 | 2246.80 | 22.88 | 16.53 | ||
Maximum of Months | 0.200203E+11 | 55283.53 | 32.77 | 26.54 | 0.200314E+10 | 2247.00 | 33.47 | 26.54 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 | 0.263476E+10 | 5486.45 | 02-JAN-14:20 | 26.33 | 18.48 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 | 0.268621E+10 | 5569.97 | 27-FEB-15:20 | 25.90 | 20.46 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 | 0.362553E+10 | 5859.31 | 30-MAR-13:50 | 27.98 | 22.39 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 | 0.460712E+10 | 7888.24 | 28-APR-15:09 | 33.12 | 23.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.11 | 0.573837E+10 | 8040.88 | 18-MAY-15:20 | 33.30 | 23.34 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 | 0.590707E+10 | 8683.94 | 14-JUN-14:20 | 34.43 | 24.69 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 | 23.10 | 0.571255E+10 | 9030.81 | 22-JUL-15:00 | 36.10 | 27.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.55 | 0.605025E+10 | 8855.13 | 03-AUG-15:00 | 35.50 | 24.80 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 | 0.528296E+10 | 8552.99 | 09-SEP-15:00 | 35.60 | 26.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 | 0.510087E+10 | 8173.29 | 05-OCT-15:09 | 33.67 | 23.96 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 | 0.381687E+10 | 6522.07 | 02-NOV-13:20 | 29.80 | 24.39 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 | 0.312525E+10 | 6026.12 | 16-DEC-14:20 | 27.00 | 21.75 |
Annual Sum or Average | 0.00 | 0.542878E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 14.12 | 12.36 | 0.263476E+10 | 5486.45 | 25.90 | 18.48 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 24.22 | 0.605025E+10 | 9030.81 | 36.10 | 27.07 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.731050E+09 | 27032.10 | 10-JAN-06:01 | 3.00 |
February | 0.435075E+09 | 27034.48 | 06-FEB-06:01 | 2.88 |
March | 0.322328E+09 | 27014.13 | 13-MAR-05:01 | 6.68 |
April | 26808044.40 | 901.19 | 11-APR-06:10 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 8850366.44 | 795.94 | 27-OCT-06:10 | 14.83 |
November | 52463171.41 | 3600.53 | 15-NOV-07:20 | 7.90 |
December | 0.409147E+09 | 26942.16 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.198572E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.731050E+09 | 27034.48 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203376E+09 | 2683.22 | 10-JAN-07:10 | 3.17 |
February | 0.199952E+09 | 14140.92 | 05-FEB-07:55 | -3.4 |
March | 0.175550E+09 | 1382.11 | 24-MAR-17:00 | 26.60 |
April | 82374941.97 | 1098.03 | 10-APR-06:50 | 12.20 |
May | 5252524.05 | 1258.86 | 08-MAY-06:10 | 23.98 |
June | 8487667.30 | 1390.95 | 13-JUN-06:04 | 24.18 |
July | 4449773.39 | 1267.40 | 26-JUL-06:10 | 25.78 |
August | 4348088.28 | 1422.31 | 31-AUG-06:04 | 24.00 |
September | 4516594.03 | 1209.00 | 02-SEP-06:10 | 24.58 |
October | 40506976.99 | 1259.30 | 07-OCT-06:10 | 26.67 |
November | 0.143189E+09 | 2114.61 | 28-NOV-13:00 | 28.30 |
December | 0.169252E+09 | 1549.29 | 09-DEC-13:40 | 27.00 |
Annual Sum or Average | 0.104125E+10 | |||
Minimum of Months | 4348088.28 | 1098.03 | -3.4 | |
Maximum of Months | 0.203376E+09 | 14140.92 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.880284E+09 | 986.72 | 31-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.779271E+09 | 990.71 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.921652E+09 | 987.28 | 18-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.830599E+09 | 984.89 | 14-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.853331E+09 | 964.43 | 20-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.833737E+09 | 940.12 | 03-JUN-07:30 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.808013E+09 | 945.72 | 14-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.870558E+09 | 961.73 | 21-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.829902E+09 | 982.10 | 26-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.843638E+09 | 996.50 | 25-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.844153E+09 | 990.95 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.888877E+09 | 995.32 | 12-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.101840E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.779271E+09 | 940.12 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.921652E+09 | 996.50 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.332059E+10 | 3489.68 | 04-JAN-09:09 | 0.00 | 0.00 |
February | 0.286944E+10 | 3492.24 | 14-FEB-09:09 | 0.00 | 0.00 |
March | 0.321097E+10 | 3543.01 | 13-MAR-08:09 | 0.00 | 0.00 |
April | 0.279507E+10 | 3465.40 | 03-APR-08:09 | 0.00 | 0.00 |
May | 0.282304E+10 | 3380.85 | 03-MAY-08:09 | 0.00 | 0.00 |
June | 0.277866E+10 | 3301.63 | 08-JUN-08:09 | 0.00 | 0.00 |
July | 0.268670E+10 | 3270.06 | 25-JUL-08:30 | 0.00 | 0.00 |
August | 0.285750E+10 | 3381.32 | 30-AUG-08:09 | 0.00 | 0.00 |
September | 0.275076E+10 | 3391.27 | 22-SEP-08:09 | 0.00 | 0.00 |
October | 0.296350E+10 | 3418.99 | 18-OCT-08:09 | 0.00 | 0.00 |
November | 0.315100E+10 | 3546.98 | 27-NOV-15:30 | 0.00 | 0.00 |
December | 0.338391E+10 | 3544.62 | 28-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.355911E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.268670E+10 | 3270.06 | 0.00 | 0.00 | |
Maximum of Months | 0.338391E+10 | 3546.98 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.343541E+10 | 3488.52 | 06-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.293054E+10 | 3435.26 | 01-FEB-08:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.324799E+10 | 3450.44 | 13-MAR-07:10 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.293491E+10 | 3363.92 | 14-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.293645E+10 | 3101.67 | 20-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.286537E+10 | 2931.63 | 03-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.282104E+10 | 2920.08 | 14-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.302920E+10 | 3142.58 | 08-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.292997E+10 | 3329.42 | 26-SEP-07:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.308231E+10 | 3523.73 | 25-OCT-07:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.320716E+10 | 3686.43 | 27-NOV-15:30 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.346223E+10 | 3605.68 | 28-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.368826E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.282104E+10 | 2920.08 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.346223E+10 | 3686.43 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.880284E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15525449.28 | 0.172316E+10 |
February | 0.127628E+10 | 0.779271E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25712117.01 | 0.114931E+10 |
March | 0.149825E+10 | 0.921652E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66043141.80 | 0.133757E+10 |
April | 0.138726E+10 | 0.830599E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195047E+09 | 0.563976E+09 |
May | 0.144276E+10 | 0.853331E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648606E+09 | 97984104.52 |
June | 0.144276E+10 | 0.833737E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754528E+09 | 79743193.12 |
July | 0.138726E+10 | 0.808013E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686694E+09 | 54749945.03 |
August | 0.149825E+10 | 0.870558E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772647E+09 | 0.116841E+09 |
September | 0.138726E+10 | 0.829902E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419426E+09 | 0.177059E+09 |
October | 0.138726E+10 | 0.843638E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436327E+09 | 0.486762E+09 |
November | 0.133177E+10 | 0.844153E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102512E+09 | 0.869333E+09 |
December | 0.138726E+10 | 0.888877E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50039142.12 | 0.146535E+10 |
Annual Sum or Average | 0.168137E+11 | 0.101840E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417311E+10 | 0.812185E+10 |
Minimum of Months | 0.127628E+10 | 0.779271E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15525449.28 | 54749945.03 |
Maximum of Months | 0.149825E+10 | 0.921652E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772647E+09 | 0.172316E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.332059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14418014.55 | 0.384110E+10 |
February | 0.300332E+10 | 0.286944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14962319.90 | 0.282356E+10 |
March | 0.352563E+10 | 0.321097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19022743.61 | 0.356012E+10 |
April | 0.326447E+10 | 0.279507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100139E+09 | 0.195666E+10 |
May | 0.339505E+10 | 0.282304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521374E+09 | 0.612064E+09 |
June | 0.339505E+10 | 0.277866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602676E+09 | 0.402124E+09 |
July | 0.326447E+10 | 0.268670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728152E+09 | 0.242305E+09 |
August | 0.352563E+10 | 0.285750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774926E+09 | 0.593385E+09 |
September | 0.326447E+10 | 0.275076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508812E+09 | 0.912702E+09 |
October | 0.326447E+10 | 0.296350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437370E+09 | 0.204784E+10 |
November | 0.313390E+10 | 0.315100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24370684.57 | 0.251846E+10 |
December | 0.326447E+10 | 0.338391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17395638.97 | 0.358722E+10 |
Annual Sum or Average | 0.395654E+11 | 0.355911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376362E+10 | 0.230975E+11 |
Minimum of Months | 0.300332E+10 | 0.268670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14418014.55 | 0.242305E+09 |
Maximum of Months | 0.352563E+10 | 0.338391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774926E+09 | 0.384110E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.343541E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277220E+09 | 0.167884E+11 |
February | 0.690763E+10 | 0.293054E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204889E+09 | 0.120556E+11 |
March | 0.810895E+10 | 0.324799E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102940E+09 | 0.165499E+11 |
April | 0.750829E+10 | 0.293491E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1537140.64 | 0.110470E+11 |
May | 0.780862E+10 | 0.293645E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4921565.20 | 0.681706E+10 |
June | 0.780862E+10 | 0.286537E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1971288.42 | 0.451522E+10 |
July | 0.750829E+10 | 0.282104E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5926282.44 | 0.406767E+10 |
August | 0.810895E+10 | 0.302920E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26775533.57 | 0.651139E+10 |
September | 0.750829E+10 | 0.292997E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37314527.99 | 0.834034E+10 |
October | 0.750829E+10 | 0.308231E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1504604.47 | 0.141963E+11 |
November | 0.720796E+10 | 0.320716E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65245564.82 | 0.121241E+11 |
December | 0.750829E+10 | 0.346223E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164208E+09 | 0.159547E+11 |
Annual Sum or Average | 0.910005E+11 | 0.368826E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894454E+09 | 0.128968E+12 |
Minimum of Months | 0.690763E+10 | 0.282104E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1504604.47 | 0.406767E+10 |
Maximum of Months | 0.810895E+10 | 0.346223E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277220E+09 | 0.167884E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 986.72 | 31-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 741.07 | 02-JAN-13:00 | 8489.20 | 05-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 990.71 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1664.87 | 02-FEB-13:00 | 7960.52 | 17-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 987.28 | 18-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1591.42 | 30-MAR-12:00 | 8839.18 | 09-MAR-07:10 |
April | 1680.92 | 01-APR-07:10 | 984.89 | 14-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3147.24 | 28-APR-16:10 | 4940.10 | 11-APR-06:05 |
May | 1680.92 | 01-MAY-07:10 | 964.43 | 20-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3475.70 | 10-MAY-16:10 | 679.38 | 02-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 940.12 | 03-JUN-07:30 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3558.84 | 28-JUN-16:10 | 1012.85 | 07-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 945.72 | 14-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4172.41 | 21-JUL-16:10 | 373.89 | 13-JUL-11:05 |
August | 1680.92 | 01-AUG-07:10 | 961.73 | 21-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4638.10 | 03-AUG-16:10 | 830.15 | 16-AUG-17:00 |
September | 1680.92 | 01-SEP-07:10 | 982.10 | 26-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3143.20 | 06-SEP-16:10 | 1622.43 | 07-SEP-17:00 |
October | 1680.92 | 02-OCT-07:10 | 996.50 | 25-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3333.63 | 05-OCT-17:00 | 4104.02 | 27-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 990.95 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1942.61 | 02-NOV-12:00 | 5550.13 | 09-NOV-07:05 |
December | 1680.92 | 01-DEC-08:09 | 995.32 | 12-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1496.23 | 13-DEC-13:00 | 8911.99 | 20-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 940.12 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 741.07 | 373.89 | |||||
Maximum of Months | 1680.92 | 996.50 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 4638.10 | 8911.99 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3489.68 | 04-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.80 | 16-JAN-15:00 | 7553.96 | 03-JAN-09:00 |
February | 3955.50 | 01-FEB-08:09 | 3492.24 | 14-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 944.14 | 20-FEB-15:00 | 8695.25 | 16-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 3543.01 | 13-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.44 | 27-MAR-15:10 | 7983.77 | 09-MAR-09:00 |
April | 3955.50 | 01-APR-07:10 | 3465.40 | 03-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2186.32 | 28-APR-15:10 | 5493.09 | 15-APR-17:00 |
May | 3955.50 | 01-MAY-07:10 | 3380.85 | 03-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2351.42 | 18-MAY-16:35 | 1810.77 | 05-MAY-06:10 |
June | 3955.50 | 01-JUN-07:10 | 3301.63 | 08-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3239.61 | 08-JUN-15:10 | 2308.98 | 06-JUN-21:00 |
July | 3955.50 | 01-JUL-07:10 | 3270.06 | 25-JUL-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2969.51 | 06-JUL-15:10 | 1126.52 | 12-JUL-15:10 |
August | 3955.50 | 01-AUG-07:10 | 3381.32 | 30-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3742.20 | 03-AUG-16:40 | 2436.25 | 25-AUG-24:00 |
September | 3955.50 | 01-SEP-07:10 | 3391.27 | 22-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3588.90 | 09-SEP-17:00 | 2243.79 | 19-SEP-18:40 |
October | 3955.50 | 02-OCT-07:10 | 3418.99 | 18-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.45 | 09-OCT-13:50 | 5560.94 | 27-OCT-07:00 |
November | 3955.50 | 01-NOV-07:10 | 3546.98 | 27-NOV-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 779.37 | 02-NOV-15:10 | 5903.19 | 09-NOV-07:10 |
December | 3955.50 | 01-DEC-08:09 | 3544.62 | 28-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.90 | 13-DEC-16:10 | 6707.80 | 04-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3270.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.90 | 1126.52 | ||||
Maximum of Months | 3955.50 | 3546.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3742.20 | 8695.25 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3488.52 | 06-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3885.42 | 31-JAN-13:10 | 33420.74 | 03-JAN-09:00 |
February | 9097.65 | 01-FEB-08:09 | 3435.26 | 01-FEB-08:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6664.25 | 02-FEB-13:10 | 37084.08 | 04-FEB-11:00 |
March | 9097.65 | 01-MAR-08:09 | 3450.44 | 13-MAR-07:10 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3191.06 | 27-MAR-15:00 | 35771.58 | 09-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 3363.92 | 14-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 848.02 | 15-APR-12:00 | 24455.65 | 01-APR-16:00 |
May | 9097.65 | 01-MAY-07:10 | 3101.67 | 20-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1277.42 | 27-MAY-13:53 | 15478.91 | 26-MAY-15:00 |
June | 9097.65 | 01-JUN-07:10 | 2931.63 | 03-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.95 | 25-JUN-12:53 | 14138.24 | 01-JUN-13:00 |
July | 9097.65 | 01-JUL-07:10 | 2920.08 | 14-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 704.01 | 02-JUL-10:55 | 18044.15 | 31-JUL-11:00 |
August | 9097.65 | 01-AUG-07:10 | 3142.58 | 08-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 994.86 | 30-AUG-15:55 | 13088.86 | 25-AUG-24:00 |
September | 9097.65 | 01-SEP-07:10 | 3329.42 | 26-SEP-07:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1374.94 | 09-SEP-17:00 | 15444.11 | 12-SEP-20:00 |
October | 9097.65 | 02-OCT-07:10 | 3523.73 | 25-OCT-07:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 435.88 | 08-OCT-13:55 | 27846.80 | 27-OCT-11:00 |
November | 9097.65 | 01-NOV-07:10 | 3686.43 | 27-NOV-15:30 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4389.81 | 28-NOV-13:10 | 23914.36 | 09-NOV-08:10 |
December | 9097.65 | 01-DEC-08:09 | 3605.68 | 28-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2838.21 | 13-DEC-14:00 | 29976.64 | 19-DEC-12:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2920.08 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 314.95 | 13088.86 | |||||
Maximum of Months | 9097.65 | 3686.43 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 6664.25 | 37084.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19399.55 | 02-JAN-06:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.65 |
February | 15406.47 | 28-FEB-06:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.68 |
March | 14709.49 | 30-MAR-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.13 |
April | 18114.55 | 25-APR-05:02 | 1109.41 | 305.97 | 3303.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.61 |
May | 16851.20 | 05-MAY-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.15 |
June | 17238.43 | 16-JUN-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.10 |
July | 15955.45 | 19-JUL-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.34 |
August | 19004.62 | 31-AUG-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.74 |
September | 17052.17 | 22-SEP-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.41 |
October | 24531.49 | 27-OCT-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 974.51 |
November | 18450.87 | 06-NOV-06:01 | 1294.31 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.81 |
December | 15435.54 | 16-DEC-06:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14709.49 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.34 | |
Maximum of Months | 24531.49 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 974.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34011.99 | 01-JAN-13:43 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.10 |
February | 7040.27 | 27-FEB-15:10 | 3955.50 | 2822.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.34 |
March | 13868.19 | 26-MAR-14:05 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.42 | 0.00 |
April | 50136.46 | 23-APR-14:03 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.12 | 0.00 |
May | 54262.89 | 29-MAY-16:23 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 765.62 | 0.00 |
June | 55283.53 | 11-JUN-16:12 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.56 | 0.00 |
July | 52464.74 | 23-JUL-14:13 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1101.77 | 0.00 |
August | 53072.28 | 02-AUG-05:01 | 4351.05 | 2999.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.58 |
September | 52186.40 | 10-SEP-17:03 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 777.61 | 0.00 |
October | 54827.60 | 01-OCT-15:43 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.18 | 0.00 |
November | 26828.60 | 05-NOV-13:55 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.72 | 0.00 |
December | 10193.37 | 15-DEC-14:40 | 3955.50 | 3140.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 7040.27 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55283.53 | 4351.05 | 3140.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1101.77 | 78.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6494.78 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2154.94 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4232.42 |
April | 0.00 | 01-APR-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4718.59 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3076.84 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1983.65 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 996.09 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1998.73 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3081.30 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.47 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6013.19 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2659.98 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5642.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.47 | |
Maximum of Months | 0.00 | 0.00 | 996.09 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6494.78 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.290216E+11 | 23037.71 | 02-JAN-16:49 | 0.114192E+10 | 18541.38 | 10-JAN-07:10 |
February | 0.259944E+11 | 24501.16 | 27-FEB-15:00 | 0.660729E+09 | 16286.38 | 06-FEB-06:10 |
March | 0.294463E+11 | 24415.19 | 06-MAR-15:50 | 0.462905E+09 | 13290.05 | 13-MAR-05:10 |
April | 0.297611E+11 | 32386.75 | 28-APR-15:50 | 290163.23 | 262.79 | 11-APR-06:00 |
May | 0.384699E+11 | 32404.23 | 24-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.400797E+11 | 34878.26 | 28-JUN-15:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.409779E+11 | 35576.40 | 18-JUL-15:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.424416E+11 | 36288.45 | 03-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.375853E+11 | 35129.70 | 09-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.364379E+11 | 34543.86 | 07-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.292481E+11 | 30918.67 | 02-NOV-14:00 | 31625610.28 | 4590.24 | 15-NOV-07:19 |
December | 0.298667E+11 | 27568.09 | 15-DEC-15:09 | 0.645738E+09 | 15252.71 | 21-DEC-07:10 |
Annual Sum or Average | 0.409330E+12 | 0.294320E+10 | ||||
Minimum of Months | 0.259944E+11 | 23037.71 | 0.00 | 0.00 | ||
Maximum of Months | 0.424416E+11 | 36288.45 | 0.114192E+10 | 18541.38 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.763629E+10 | 0.620081E+10 | 0.112984E+11 | 0.00 | 0.158087E+10 | 0.00 | 0.00 | 0.249068E+09 | 0.00 | 0.00 | 0.00 | 0.205620E+10 | 0.00 |
February | 0.657925E+10 | 0.527108E+10 | 0.103734E+11 | 0.00 | 0.144457E+10 | 0.00 | 0.00 | 0.464221E+09 | 0.00 | 0.00 | 0.00 | 0.186194E+10 | 0.00 |
March | 0.738061E+10 | 0.533956E+10 | 0.121089E+11 | 0.00 | 0.168954E+10 | 0.00 | 0.00 | 0.857469E+09 | 0.00 | 0.00 | 0.00 | 0.207021E+10 | 0.00 |
April | 0.656058E+10 | 0.468626E+10 | 0.112578E+11 | 0.00 | 0.200955E+10 | 0.00 | 0.00 | 0.331461E+10 | 0.00 | 0.00 | 0.00 | 0.193233E+10 | 0.00 |
May | 0.661283E+10 | 0.441268E+10 | 0.117000E+11 | 0.00 | 0.401064E+10 | 0.00 | 0.00 | 0.978056E+10 | 0.00 | 0.00 | 0.00 | 0.195319E+10 | 0.00 |
June | 0.647777E+10 | 0.404773E+10 | 0.116594E+11 | 0.00 | 0.469210E+10 | 0.00 | 0.00 | 0.113322E+11 | 0.00 | 0.00 | 0.00 | 0.187048E+10 | 0.00 |
July | 0.631575E+10 | 0.430783E+10 | 0.112984E+11 | 0.00 | 0.493943E+10 | 0.00 | 0.00 | 0.122387E+11 | 0.00 | 0.00 | 0.00 | 0.187784E+10 | 0.00 |
August | 0.675726E+10 | 0.464357E+10 | 0.121016E+11 | 0.00 | 0.469446E+10 | 0.00 | 0.00 | 0.123223E+11 | 0.00 | 0.00 | 0.00 | 0.192241E+10 | 0.00 |
September | 0.651063E+10 | 0.496450E+10 | 0.112504E+11 | 0.00 | 0.356119E+10 | 0.00 | 0.00 | 0.943227E+10 | 0.00 | 0.00 | 0.00 | 0.186629E+10 | 0.00 |
October | 0.688945E+10 | 0.563437E+10 | 0.113057E+11 | 0.00 | 0.305818E+10 | 0.00 | 0.00 | 0.759725E+10 | 0.00 | 0.00 | 0.00 | 0.195287E+10 | 0.00 |
November | 0.720231E+10 | 0.587213E+10 | 0.108562E+11 | 0.00 | 0.158547E+10 | 0.00 | 0.00 | 0.180141E+10 | 0.00 | 0.00 | 0.00 | 0.193057E+10 | 0.00 |
December | 0.773502E+10 | 0.631012E+10 | 0.112984E+11 | 0.00 | 0.156994E+10 | 0.00 | 0.00 | 0.916352E+09 | 0.00 | 0.00 | 0.00 | 0.203687E+10 | 0.00 |
Annual Sum or Average | 0.826577E+11 | 0.616906E+11 | 0.136508E+12 | 0.00 | 0.348359E+11 | 0.00 | 0.00 | 0.703064E+11 | 0.00 | 0.00 | 0.00 | 0.233312E+11 | 0.00 |
Minimum of Months | 0.631575E+10 | 0.404773E+10 | 0.103734E+11 | 0.00 | 0.144457E+10 | 0.00 | 0.00 | 0.249068E+09 | 0.00 | 0.00 | 0.00 | 0.186194E+10 | 0.00 |
Maximum of Months | 0.773502E+10 | 0.631012E+10 | 0.121089E+11 | 0.00 | 0.493943E+10 | 0.00 | 0.00 | 0.123223E+11 | 0.00 | 0.00 | 0.00 | 0.207021E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.114192E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.660729E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.462905E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 290163.23 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 31625610.28 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.645738E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.294320E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.114192E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 7708.86 | 06-JAN-15:00 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 1902.26 | 10-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 7847.34 | 01-FEB-09:09 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 1857.70 | 06-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 7776.55 | 13-MAR-08:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 1800.48 | 13-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 7640.86 | 14-APR-08:09 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 4147.10 | 28-APR-16:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7210.30 | 03-MAY-08:09 | 5520.82 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 4180.21 | 30-MAY-11:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 6956.03 | 03-JUN-07:10 | 5520.82 | 01-JUN-05:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 4469.92 | 28-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 6899.74 | 14-JUL-07:10 | 5520.82 | 01-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 4578.47 | 18-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 7262.82 | 08-AUG-07:10 | 5520.82 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4785.80 | 03-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 7519.31 | 30-SEP-07:10 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4532.81 | 09-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 7814.32 | 25-OCT-07:10 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 4453.47 | 06-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 8158.68 | 27-NOV-15:30 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 3983.52 | 07-NOV-12:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 8124.53 | 28-DEC-09:09 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 1857.28 | 21-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 6899.74 | 5520.82 | 10035.17 | 0.00 | 1800.48 | 0.00 | 0.00 | |||||
Maximum of Months | 8158.68 | 5520.82 | 10035.17 | 0.00 | 4785.80 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 7693.05 | 01-JAN-12:39 | 0.00 | 0.00 | 0.00 | 1773.02 | 25-JAN-12:00 | 0.00 |
February | 5054.09 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 | 1772.19 | 03-FEB-12:39 | 0.00 |
March | 5698.36 | 29-MAR-14:00 | 0.00 | 0.00 | 0.00 | 1765.14 | 01-MAR-12:20 | 0.00 |
April | 12054.67 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 1749.53 | 01-APR-11:39 | 0.00 |
May | 12176.08 | 25-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1731.13 | 01-MAY-11:30 | 0.00 |
June | 14374.79 | 28-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1713.85 | 01-JUN-11:50 | 0.00 |
July | 15155.24 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1703.21 | 01-JUL-11:09 | 0.00 |
August | 15926.17 | 03-AUG-16:10 | 0.00 | 0.00 | 0.00 | 1707.47 | 31-AUG-11:50 | 0.00 |
September | 15132.88 | 09-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1721.33 | 30-SEP-11:20 | 0.00 |
October | 14143.42 | 06-OCT-11:00 | 0.00 | 0.00 | 0.00 | 1739.95 | 31-OCT-11:09 | 0.00 |
November | 9075.02 | 02-NOV-14:20 | 0.00 | 0.00 | 0.00 | 1757.53 | 30-NOV-12:30 | 0.00 |
December | 7367.95 | 15-DEC-14:09 | 0.00 | 0.00 | 0.00 | 1769.41 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5054.09 | 0.00 | 0.00 | 0.00 | 1703.21 | 0.00 | ||
Maximum of Months | 15926.17 | 0.00 | 0.00 | 0.00 | 1773.02 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 23037.71 | 02-JAN-16:49 | 6983.34 | 10035.17 | 0.00 | 0.00 | 1570.00 | 0.00 | 0.00 | 2854.50 | 0.00 |
February | 24501.16 | 27-FEB-15:00 | 6409.21 | 10035.17 | 0.00 | 0.00 | 1570.00 | 0.00 | 0.00 | 4753.86 | 0.00 |
March | 24415.19 | 06-MAR-15:50 | 6650.65 | 10035.17 | 0.00 | 0.00 | 1570.00 | 0.00 | 0.00 | 4429.28 | 0.00 |
April | 32386.75 | 28-APR-15:50 | 4720.88 | 10035.17 | 0.00 | 0.00 | 4040.29 | 0.00 | 0.00 | 12004.85 | 0.00 |
May | 32404.23 | 24-MAY-12:00 | 5180.50 | 10035.17 | 0.00 | 0.00 | 3975.31 | 0.00 | 0.00 | 11521.05 | 0.00 |
June | 34878.26 | 28-JUN-15:30 | 4584.75 | 10035.17 | 0.00 | 0.00 | 4442.28 | 0.00 | 0.00 | 14238.15 | 0.00 |
July | 35576.40 | 18-JUL-15:39 | 4368.75 | 10035.17 | 0.00 | 0.00 | 4575.81 | 0.00 | 0.00 | 15019.63 | 0.00 |
August | 36288.45 | 03-AUG-15:30 | 4182.27 | 10035.17 | 0.00 | 0.00 | 4718.82 | 0.00 | 0.00 | 15775.18 | 0.00 |
September | 35129.70 | 09-SEP-15:00 | 4947.83 | 10035.17 | 0.00 | 0.00 | 4532.81 | 0.00 | 0.00 | 15132.88 | 0.00 |
October | 34543.86 | 07-OCT-15:00 | 5660.02 | 10035.17 | 0.00 | 0.00 | 4237.43 | 0.00 | 0.00 | 13027.76 | 0.00 |
November | 30918.67 | 02-NOV-14:00 | 6264.36 | 10035.17 | 0.00 | 0.00 | 3911.48 | 0.00 | 0.00 | 8995.50 | 0.00 |
December | 27568.09 | 15-DEC-15:09 | 7171.53 | 10035.17 | 0.00 | 0.00 | 1570.00 | 0.00 | 0.00 | 7059.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 23037.71 | 4182.27 | 10035.17 | 0.00 | 0.00 | 1570.00 | 0.00 | 0.00 | 2854.50 | 0.00 | |
Maximum of Months | 36288.45 | 7171.53 | 10035.17 | 0.00 | 0.00 | 4718.82 | 0.00 | 0.00 | 15775.18 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 18541.38 | 10-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 16286.38 | 06-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 13290.05 | 13-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 262.79 | 11-APR-06:00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 4590.24 | 15-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 15252.71 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 18541.38 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 20.38 | 2.17 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
February | 1.17 | 20.34 | 1.17 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
March | 0.33 | 20.37 | 0.33 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.49 | 1.00 | 24.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 24.87 | 8.33 | 24.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 24.78 | 7.83 | 24.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.92 | 8.33 | 24.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 24.89 | 8.50 | 24.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 25.00 | 8.00 | 24.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.76 | 5.17 | 24.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.17 | 24.49 |
December | 0.67 | 20.43 | 0.67 | 20.43 | 0.67 | 21.79 | 0.67 | 22.47 |
Annual Sum or Average | 4.33 | 20.37 | 4.33 | 20.37 | 48.67 | 24.18 | 48.00 | 24.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.34 | 0.00 | 20.34 |
Maximum of Months | 2.17 | 20.43 | 2.17 | 20.43 | 8.67 | 25.00 | 8.50 | 24.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.00 | 27.33 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 27.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.36 | 0.00 | 27.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.46 | 0.00 | 27.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 27.44 | 0.00 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 27.45 | 0.17 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 27.43 | 0.00 | 27.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 27.51 | 0.00 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.48 | 0.17 | 27.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.00 | 27.30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 142.33 | 27.46 | 0.33 | 27.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 27.51 | 0.17 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 272.50 | 22.46 | 131.00 | 22.41 | 110.83 | 22.33 |
February | 220.83 | 22.72 | 140.67 | 22.84 | 93.83 | 22.78 |
March | 231.00 | 22.91 | 133.50 | 23.01 | 67.17 | 22.93 |
April | 68.00 | 23.60 | 216.67 | 23.83 | 27.17 | 23.84 |
May | 53.00 | 24.01 | 312.00 | 23.94 | 53.00 | 23.94 |
June | 55.00 | 24.02 | 312.00 | 23.94 | 55.00 | 23.95 |
July | 78.00 | 24.03 | 300.00 | 23.95 | 78.00 | 23.97 |
August | 76.83 | 24.03 | 324.00 | 23.95 | 76.83 | 23.96 |
September | 66.67 | 24.02 | 300.00 | 23.95 | 66.67 | 23.96 |
October | 53.00 | 23.97 | 263.33 | 23.93 | 43.00 | 23.94 |
November | 133.00 | 23.44 | 120.17 | 23.66 | 30.00 | 23.69 |
December | 227.67 | 22.70 | 129.67 | 22.84 | 77.50 | 22.79 |
Annual Sum or Average | 1535.50 | 23.12 | 2683.00 | 23.50 | 779.00 | 23.47 |
Minimum of Months | 53.00 | 22.46 | 120.17 | 22.41 | 27.17 | 22.33 |
Maximum of Months | 272.50 | 24.03 | 324.00 | 23.95 | 110.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 288.50 | 20.84 | 188.33 | 20.74 | 178.00 | 20.62 |
February | 269.17 | 22.14 | 190.33 | 22.20 | 186.67 | 22.21 |
March | 274.00 | 22.88 | 188.00 | 23.21 | 157.17 | 23.23 |
April | 219.17 | 25.93 | 263.33 | 26.10 | 192.50 | 26.16 |
May | 309.33 | 26.70 | 312.00 | 26.70 | 309.33 | 26.70 |
June | 306.50 | 26.71 | 312.00 | 26.71 | 306.50 | 26.71 |
July | 299.17 | 26.72 | 300.00 | 26.72 | 299.17 | 26.72 |
August | 319.00 | 26.72 | 324.00 | 26.72 | 319.00 | 26.72 |
September | 295.33 | 26.71 | 300.00 | 26.71 | 295.33 | 26.71 |
October | 248.50 | 26.57 | 284.83 | 26.56 | 240.83 | 26.60 |
November | 183.00 | 24.68 | 191.33 | 25.31 | 108.83 | 25.48 |
December | 266.83 | 22.26 | 203.83 | 22.47 | 178.17 | 22.41 |
Annual Sum or Average | 3278.50 | 24.96 | 3058.00 | 25.22 | 2771.50 | 25.30 |
Minimum of Months | 183.00 | 20.84 | 188.00 | 20.74 | 108.83 | 20.62 |
Maximum of Months | 319.00 | 26.72 | 324.00 | 26.72 | 319.00 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 288.50 | 20.23 | 211.17 | 20.08 | 204.83 | 19.97 |
February | 276.00 | 21.51 | 204.33 | 21.48 | 204.33 | 21.47 |
March | 275.50 | 22.87 | 182.50 | 23.17 | 155.00 | 23.19 |
April | 237.50 | 27.93 | 275.50 | 27.87 | 221.17 | 28.00 |
May | 312.00 | 30.27 | 312.00 | 30.27 | 312.00 | 30.27 |
June | 312.00 | 30.71 | 312.00 | 30.71 | 312.00 | 30.71 |
July | 300.00 | 30.79 | 300.00 | 30.79 | 300.00 | 30.79 |
August | 324.00 | 30.52 | 324.00 | 30.52 | 324.00 | 30.52 |
September | 300.00 | 29.63 | 300.00 | 29.63 | 300.00 | 29.63 |
October | 270.00 | 29.40 | 293.33 | 29.27 | 266.17 | 29.34 |
November | 191.33 | 25.38 | 181.83 | 25.99 | 116.83 | 26.28 |
December | 272.33 | 21.97 | 199.50 | 22.10 | 179.83 | 22.05 |
Annual Sum or Average | 3359.17 | 26.95 | 3096.17 | 27.26 | 2896.17 | 27.40 |
Minimum of Months | 191.33 | 20.23 | 181.83 | 20.08 | 116.83 | 19.97 |
Maximum of Months | 324.00 | 30.79 | 324.00 | 30.79 | 324.00 | 30.79 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.908468E+09 | 0.214012E+09 | 53.95 | 0.585804E+09 | 0.322665E+09 | 0.00 | 1.00 | 02-JAN-06:02 | 0.00 | 01-JAN-00:10 | 22874.85 | 02-JAN-06:02 | 12480.09 | 02-JAN-06:02 | 10394.76 | 02-JAN-06:02 | 4969.12 | 02-JAN-06:02 | 0.00 | 01-JAN-00:10 |
February | 0.161094E+10 | 0.379392E+09 | 91.85 | 0.106263E+10 | 0.548302E+09 | 0.00 | 1.00 | 27-FEB-06:03 | 0.00 | 01-FEB-00:10 | 23931.91 | 27-FEB-06:03 | 11380.09 | 28-FEB-06:03 | 12556.28 | 27-FEB-06:03 | 5161.26 | 27-FEB-06:03 | 0.00 | 01-FEB-00:10 |
March | 0.268793E+10 | 0.632329E+09 | 142.63 | 0.184400E+10 | 0.843935E+09 | 0.00 | 1.00 | 07-MAR-06:03 | 0.00 | 01-MAR-00:10 | 25975.01 | 07-MAR-06:03 | 17083.04 | 30-MAR-05:03 | 14819.42 | 07-MAR-06:03 | 5485.85 | 07-MAR-06:03 | 0.00 | 01-MAR-00:10 |
April | 0.598824E+10 | 0.141359E+10 | 243.72 | 0.431682E+10 | 0.167142E+10 | 0.00 | 1.00 | 01-APR-05:03 | 0.00 | 01-APR-00:10 | 27160.94 | 29-APR-05:01 | 17313.23 | 28-APR-05:01 | 14569.54 | 29-APR-05:02 | 5646.64 | 29-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.125678E+11 | 0.295519E+10 | 309.32 | 0.851793E+10 | 0.404985E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 28664.90 | 23-MAY-05:01 | 20590.52 | 28-MAY-15:23 | 17736.05 | 23-MAY-05:01 | 6202.30 | 28-MAY-15:23 | 0.00 | 01-MAY-00:10 |
June | 0.135144E+11 | 0.320739E+10 | 308.92 | 0.918840E+10 | 0.432600E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 28248.37 | 30-JUN-05:01 | 22691.93 | 11-JUN-15:23 | 16103.34 | 05-JUN-05:01 | 5870.29 | 11-JUN-15:23 | 0.00 | 01-JUN-00:10 |
July | 0.140277E+11 | 0.330658E+10 | 296.40 | 0.905548E+10 | 0.497218E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:05 | 28615.57 | 31-JUL-05:01 | 17625.69 | 19-JUL-05:01 | 17016.53 | 31-JUL-05:01 | 5893.53 | 24-JUL-05:01 | 0.00 | 01-JUL-00:05 |
August | 0.151044E+11 | 0.353810E+10 | 319.82 | 0.984894E+10 | 0.525550E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 28765.77 | 11-AUG-05:01 | 20819.80 | 31-AUG-05:01 | 17725.74 | 11-AUG-05:02 | 6058.91 | 06-AUG-15:05 | 0.00 | 01-AUG-00:10 |
September | 0.127564E+11 | 0.291956E+10 | 301.73 | 0.819790E+10 | 0.455850E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 28475.28 | 11-SEP-05:01 | 18372.70 | 01-SEP-05:01 | 17885.75 | 05-SEP-05:01 | 5871.13 | 19-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.103638E+11 | 0.240483E+10 | 268.58 | 0.700492E+10 | 0.335884E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:10 | 28700.28 | 23-OCT-05:01 | 20131.31 | 26-OCT-05:01 | 17676.09 | 21-OCT-05:01 | 5897.56 | 25-OCT-05:01 | 0.00 | 01-OCT-00:10 |
November | 0.419043E+10 | 0.975084E+09 | 192.43 | 0.289229E+10 | 0.129814E+10 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 27474.40 | 02-NOV-05:01 | 17202.16 | 03-NOV-05:01 | 14609.04 | 04-NOV-05:04 | 5685.79 | 02-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.252064E+10 | 0.587021E+09 | 113.66 | 0.167523E+10 | 0.845410E+09 | 0.00 | 1.00 | 11-DEC-06:03 | 0.00 | 01-DEC-00:10 | 26553.61 | 15-DEC-06:02 | 12810.34 | 16-DEC-06:02 | 15598.25 | 15-DEC-06:02 | 5566.81 | 15-DEC-06:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.962411E+11 | 0.225331E+11 | 2642.99 | 0.641904E+11 | 0.320507E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.908468E+09 | 0.214012E+09 | 53.95 | 0.585804E+09 | 0.322665E+09 | 0.00 | 1.00 | 0.00 | 22874.85 | 11380.09 | 10394.76 | 4969.12 | 0.00 | |||||||
Maximum of Months | 0.151044E+11 | 0.353810E+10 | 319.82 | 0.984894E+10 | 0.525550E+10 | 0.00 | 1.00 | 0.00 | 28765.77 | 22691.93 | 17885.75 | 6202.30 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.142978E+09 | 35056609.30 | 6.39 | 0.107567E+09 | 35411367.90 | 0.00 | 1.00 | 01-JAN-12:35 | 0.00 | 01-JAN-00:10 | 69559.32 | 01-JAN-12:35 | 52237.85 | 01-JAN-13:43 | 21077.87 | 01-JAN-12:35 | 15386.10 | 01-JAN-12:35 | 0.00 | 01-JAN-00:10 |
February | 0.336419E+09 | 84828384.75 | 18.50 | 0.206309E+09 | 0.130109E+09 | 0.00 | 0.38 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 12246.86 | 27-FEB-15:00 | 7792.54 | 27-FEB-15:00 | 4454.32 | 27-FEB-15:00 | 3031.12 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.896694E+09 | 0.225140E+09 | 38.42 | 0.511356E+09 | 0.385339E+09 | 0.00 | 0.66 | 26-MAR-14:05 | 0.00 | 01-MAR-00:10 | 21713.27 | 26-MAR-14:05 | 15204.02 | 26-MAR-14:05 | 6509.25 | 26-MAR-14:05 | 5404.24 | 26-MAR-14:05 | 0.00 | 01-MAR-00:10 |
April | 0.768518E+10 | 0.190103E+10 | 146.09 | 0.525238E+10 | 0.243281E+10 | 0.00 | 1.00 | 16-APR-13:25 | 0.00 | 01-APR-00:10 | 77874.57 | 30-APR-14:25 | 55828.07 | 16-APR-14:45 | 40529.59 | 30-APR-14:25 | 16694.40 | 30-APR-14:25 | 0.00 | 01-APR-00:10 |
May | 0.276564E+11 | 0.682537E+10 | 388.64 | 0.181322E+11 | 0.952423E+10 | 0.00 | 1.00 | 01-MAY-17:10 | 0.00 | 01-MAY-00:10 | 80197.60 | 21-MAY-08:65 | 57397.95 | 29-MAY-16:23 | 44834.11 | 21-MAY-08:65 | 17090.12 | 21-MAY-08:65 | 0.00 | 01-MAY-00:10 |
June | 0.329517E+11 | 0.812485E+10 | 422.20 | 0.220319E+11 | 0.109198E+11 | 0.00 | 1.00 | 01-JUN-17:08 | 0.00 | 01-JUN-00:10 | 71232.00 | 24-JUN-17:08 | 58618.49 | 11-JUN-16:12 | 25480.51 | 20-JUN-17:08 | 16951.26 | 20-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.365660E+11 | 0.893210E+10 | 465.41 | 0.230354E+11 | 0.135307E+11 | 0.00 | 1.00 | 01-JUL-17:08 | 0.00 | 01-JUL-00:10 | 75310.10 | 31-JUL-17:10 | 56258.22 | 23-JUL-11:33 | 33605.53 | 31-JUL-17:10 | 17208.17 | 22-JUL-17:08 | 0.00 | 01-JUL-00:05 |
August | 0.361295E+11 | 0.878421E+10 | 455.74 | 0.227521E+11 | 0.133774E+11 | 0.00 | 1.00 | 01-AUG-13:30 | 0.00 | 01-AUG-00:10 | 80318.86 | 11-AUG-05:10 | 57182.02 | 02-AUG-05:01 | 39072.93 | 11-AUG-05:10 | 17239.57 | 02-AUG-17:06 | 0.00 | 01-AUG-00:10 |
September | 0.270190E+11 | 0.651270E+10 | 372.68 | 0.163654E+11 | 0.106537E+11 | 0.00 | 1.00 | 01-SEP-14:10 | 0.00 | 01-SEP-00:10 | 77500.61 | 02-SEP-22:45 | 55150.72 | 10-SEP-17:03 | 41098.81 | 19-SEP-18:45 | 17690.93 | 09-SEP-17:06 | 0.00 | 01-SEP-00:10 |
October | 0.215142E+11 | 0.519242E+10 | 294.23 | 0.134577E+11 | 0.805649E+10 | 0.00 | 1.00 | 01-OCT-09:45 | 0.00 | 01-OCT-00:10 | 81436.79 | 08-OCT-07:45 | 59809.22 | 01-OCT-15:43 | 49084.58 | 08-OCT-07:45 | 17156.14 | 08-OCT-13:43 | 0.00 | 01-OCT-00:10 |
November | 0.339613E+10 | 0.826327E+09 | 66.81 | 0.202149E+10 | 0.137464E+10 | 0.00 | 1.00 | 05-NOV-13:15 | 0.00 | 01-NOV-00:10 | 38200.83 | 05-NOV-13:55 | 29079.95 | 05-NOV-13:55 | 14649.93 | 11-NOV-13:10 | 8787.65 | 05-NOV-13:55 | 0.00 | 01-NOV-00:10 |
December | 0.132948E+10 | 0.329331E+09 | 36.50 | 0.769937E+09 | 0.559541E+09 | 0.00 | 0.58 | 15-DEC-14:20 | 0.00 | 01-DEC-00:10 | 19543.14 | 15-DEC-14:10 | 12472.66 | 15-DEC-14:40 | 8060.50 | 15-DEC-13:10 | 4855.98 | 15-DEC-14:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.195624E+12 | 0.477734E+11 | 2711.60 | 0.124644E+12 | 0.709801E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.142978E+09 | 35056609.30 | 6.39 | 0.107567E+09 | 35411367.90 | 0.00 | 0.38 | 0.00 | 12246.86 | 7792.54 | 4454.32 | 3031.12 | 0.00 | |||||||
Maximum of Months | 0.365660E+11 | 0.893210E+10 | 465.41 | 0.230354E+11 | 0.135307E+11 | 0.00 | 1.00 | 0.00 | 81436.79 | 59809.22 | 49084.58 | 17690.93 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.66 | 39.24 | 33.42 | 100.02 | 79.38 | 0.00 | 0.00 | 0.00 |
February | 82.22 | 41.56 | 40.67 | 116.81 | 66.56 | 0.00 | 0.00 | 0.00 |
March | 81.19 | 35.92 | 45.27 | 117.20 | 60.66 | 0.00 | 0.00 | 0.00 |
April | 100.70 | 46.25 | 54.45 | 158.01 | 46.33 | 0.00 | 0.00 | 0.00 |
May | 83.88 | 27.30 | 56.58 | 155.25 | 19.22 | 0.00 | 0.00 | 0.00 |
June | 93.27 | 32.78 | 60.49 | 175.90 | 17.91 | 0.00 | 0.00 | 0.00 |
July | 84.98 | 23.55 | 61.44 | 159.17 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 85.92 | 26.20 | 59.72 | 161.32 | 18.47 | 0.00 | 0.00 | 0.00 |
September | 79.21 | 27.20 | 52.02 | 141.27 | 24.06 | 0.00 | 0.00 | 0.00 |
October | 80.89 | 34.87 | 46.02 | 139.54 | 36.33 | 0.00 | 0.00 | 0.00 |
November | 69.45 | 34.89 | 34.56 | 102.28 | 62.82 | 0.00 | 0.00 | 0.00 |
December | 66.82 | 35.53 | 31.29 | 94.11 | 72.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.72 | 33.69 | 48.03 | 135.12 | 43.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.82 | 23.55 | 31.29 | 94.11 | 14.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.70 | 46.25 | 61.44 | 175.90 | 79.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.66 | 39.24 | 33.42 | 100.02 | 79.38 | 0.00 | 0.00 | 0.00 |
February | 82.22 | 41.56 | 40.67 | 116.81 | 66.56 | 0.00 | 0.00 | 0.00 |
March | 81.19 | 35.92 | 45.27 | 117.20 | 60.66 | 0.00 | 0.00 | 0.00 |
April | 100.70 | 46.25 | 54.45 | 158.01 | 46.33 | 0.00 | 0.00 | 0.00 |
May | 83.88 | 27.30 | 56.58 | 155.25 | 19.22 | 0.00 | 0.00 | 0.00 |
June | 93.27 | 32.78 | 60.49 | 175.90 | 17.91 | 0.00 | 0.00 | 0.00 |
July | 84.98 | 23.55 | 61.44 | 159.17 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 85.92 | 26.20 | 59.72 | 161.32 | 18.47 | 0.00 | 0.00 | 0.00 |
September | 79.21 | 27.20 | 52.02 | 141.27 | 24.06 | 0.00 | 0.00 | 0.00 |
October | 80.89 | 34.87 | 46.02 | 139.54 | 36.33 | 0.00 | 0.00 | 0.00 |
November | 69.45 | 34.89 | 34.56 | 102.28 | 62.82 | 0.00 | 0.00 | 0.00 |
December | 66.82 | 35.53 | 31.29 | 94.11 | 72.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.72 | 33.69 | 48.03 | 135.12 | 43.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.82 | 23.55 | 31.29 | 94.11 | 14.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.70 | 46.25 | 61.44 | 175.90 | 79.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.50 | 0.00 | 15.50 | 13.02 | 49.04 | 0.00 | 0.00 | 0.00 |
February | 18.29 | 0.00 | 18.29 | 17.25 | 40.60 | 0.00 | 0.00 | 0.00 |
March | 21.22 | 0.00 | 21.22 | 23.28 | 36.59 | 0.00 | 0.00 | 0.00 |
April | 25.11 | 0.15 | 24.96 | 33.30 | 27.38 | 0.00 | 0.00 | 0.00 |
May | 28.42 | 1.07 | 27.35 | 54.08 | 10.81 | 0.00 | 0.00 | 0.00 |
June | 32.21 | 2.19 | 30.02 | 63.97 | 10.06 | 0.00 | 0.00 | 0.00 |
July | 31.28 | 1.17 | 30.12 | 60.76 | 8.13 | 0.00 | 0.00 | 0.00 |
August | 28.13 | 0.29 | 27.84 | 54.67 | 10.51 | 0.00 | 0.00 | 0.00 |
September | 24.22 | 0.00 | 24.22 | 43.04 | 14.04 | 0.00 | 0.00 | 0.00 |
October | 21.04 | 0.00 | 21.04 | 34.49 | 21.47 | 0.00 | 0.00 | 0.00 |
November | 15.97 | 0.00 | 15.97 | 16.47 | 37.94 | 0.00 | 0.00 | 0.00 |
December | 14.41 | 0.00 | 14.41 | 12.60 | 44.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.01 | 0.41 | 22.60 | 35.69 | 25.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.41 | 0.00 | 14.41 | 12.60 | 8.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.21 | 2.19 | 30.12 | 63.97 | 49.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.50 | 0.00 | 15.50 | 13.02 | 49.04 | 0.00 | 0.00 | 0.00 |
February | 18.29 | 0.00 | 18.29 | 17.24 | 40.60 | 0.00 | 0.00 | 0.00 |
March | 21.22 | 0.00 | 21.22 | 23.28 | 36.59 | 0.00 | 0.00 | 0.00 |
April | 25.11 | 0.15 | 24.96 | 33.30 | 27.38 | 0.00 | 0.00 | 0.00 |
May | 28.42 | 1.07 | 27.35 | 54.08 | 10.81 | 0.00 | 0.00 | 0.00 |
June | 32.21 | 2.19 | 30.02 | 63.97 | 10.05 | 0.00 | 0.00 | 0.00 |
July | 31.28 | 1.17 | 30.12 | 60.75 | 8.13 | 0.00 | 0.00 | 0.00 |
August | 28.13 | 0.29 | 27.84 | 54.67 | 10.51 | 0.00 | 0.00 | 0.00 |
September | 24.22 | 0.00 | 24.22 | 43.04 | 14.04 | 0.00 | 0.00 | 0.00 |
October | 21.04 | 0.00 | 21.04 | 34.49 | 21.47 | 0.00 | 0.00 | 0.00 |
November | 15.97 | 0.00 | 15.97 | 16.47 | 37.94 | 0.00 | 0.00 | 0.00 |
December | 14.41 | 0.00 | 14.41 | 12.60 | 44.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.01 | 0.41 | 22.60 | 35.69 | 25.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.41 | 0.00 | 14.41 | 12.60 | 8.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.21 | 2.19 | 30.12 | 63.97 | 49.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.41 | 34.51 | 21.50 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.80 | 31.26 | 50.17 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.21 | 28.28 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.05 | 25.01 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.71 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.48 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.51 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.21 | 12.64 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.76 | 15.15 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.74 | 20.02 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.33 | 31.75 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.59 | 32.89 | 5.17 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.78 | 22.33 | 76.83 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.59 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.48 | 34.51 | 50.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.41 | 34.51 | 21.50 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.80 | 31.26 | 50.17 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.21 | 28.28 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.05 | 25.01 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.71 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.48 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.51 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.21 | 12.64 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.76 | 15.15 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.74 | 20.02 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.33 | 31.75 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.59 | 32.89 | 5.17 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.78 | 22.33 | 76.83 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.59 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.48 | 34.51 | 50.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.41 | 34.51 | 21.50 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.80 | 31.26 | 50.17 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.21 | 28.28 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.05 | 25.01 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.71 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.48 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.51 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.21 | 12.64 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.76 | 15.15 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.74 | 20.02 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.33 | 31.75 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.59 | 32.89 | 5.17 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.78 | 22.33 | 76.83 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.59 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.48 | 34.51 | 50.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.41 | 34.51 | 21.50 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.80 | 31.26 | 50.17 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.21 | 28.28 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.05 | 25.01 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.71 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.48 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.51 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.21 | 12.64 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.76 | 15.15 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.74 | 20.02 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.33 | 31.75 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.59 | 32.89 | 5.17 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.78 | 22.33 | 76.83 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.59 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.48 | 34.51 | 50.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.41 | 34.51 | 21.50 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.80 | 31.26 | 50.17 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.21 | 28.28 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.05 | 25.01 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.71 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.48 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.51 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.21 | 12.64 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.76 | 15.15 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.74 | 20.02 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.33 | 31.75 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.59 | 32.89 | 5.17 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.78 | 22.33 | 76.83 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.59 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.48 | 34.51 | 50.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.41 | 34.51 | 21.50 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.80 | 31.26 | 50.17 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.21 | 28.28 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.05 | 25.01 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.71 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.48 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.51 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.21 | 12.64 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.76 | 15.15 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.74 | 20.02 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.33 | 31.75 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.59 | 32.89 | 5.17 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.78 | 22.33 | 76.83 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.59 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.48 | 34.51 | 50.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.41 | 34.51 | 21.50 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.80 | 31.26 | 50.17 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.21 | 28.28 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.05 | 25.01 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.71 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.48 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.51 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.21 | 12.64 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.76 | 15.15 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.74 | 20.02 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.33 | 31.75 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.59 | 32.89 | 5.17 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.78 | 22.33 | 76.83 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.59 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.48 | 34.51 | 50.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.41 | 34.51 | 21.50 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.80 | 31.26 | 50.17 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.21 | 28.28 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.05 | 25.01 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.71 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.48 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.51 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.21 | 12.64 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.76 | 15.15 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.74 | 20.02 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.33 | 31.75 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.59 | 32.89 | 5.17 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.78 | 22.33 | 76.83 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.59 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.48 | 34.51 | 50.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.41 | 34.51 | 21.50 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.80 | 31.26 | 50.17 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.21 | 28.28 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.05 | 25.01 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.71 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.48 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.51 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.21 | 12.64 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.76 | 15.15 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.74 | 20.02 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.33 | 31.75 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.59 | 32.89 | 5.17 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.78 | 22.33 | 76.83 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.59 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.48 | 34.51 | 50.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.41 | 34.51 | 21.50 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.80 | 31.26 | 50.17 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.21 | 28.28 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.05 | 25.01 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.71 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.48 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.51 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.21 | 12.64 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.76 | 15.15 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.74 | 20.02 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.33 | 31.75 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.59 | 32.89 | 5.17 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.78 | 22.33 | 76.83 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.59 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.48 | 34.51 | 50.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.41 | 34.51 | 21.50 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.80 | 31.26 | 50.17 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.21 | 28.28 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.05 | 25.01 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.71 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.48 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.51 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.21 | 12.64 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.76 | 15.15 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.74 | 20.02 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.33 | 31.75 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.59 | 32.89 | 5.17 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.78 | 22.33 | 76.83 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.59 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.48 | 34.51 | 50.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.41 | 34.51 | 21.50 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.80 | 31.26 | 50.17 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.21 | 28.28 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.05 | 25.01 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.71 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.48 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.51 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.21 | 12.64 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.76 | 15.15 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.74 | 20.02 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.33 | 31.75 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.59 | 32.89 | 5.17 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.78 | 22.33 | 76.83 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.59 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.48 | 34.51 | 50.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.41 | 34.51 | 21.50 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.80 | 31.26 | 50.17 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.21 | 28.28 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.05 | 25.01 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.71 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.48 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.51 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.21 | 12.64 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.76 | 15.15 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.74 | 20.02 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.33 | 31.75 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.59 | 32.89 | 5.17 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.78 | 22.33 | 76.83 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.59 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.48 | 34.51 | 50.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.02 | 23.36 | 11.66 | 48.41 | 34.51 | 21.50 | 0.00 | 0.00 |
February | 44.76 | 30.74 | 14.01 | 62.80 | 31.26 | 50.17 | 0.00 | 0.00 |
March | 49.45 | 30.95 | 18.49 | 70.21 | 28.28 | 0.00 | 0.00 | 0.00 |
April | 63.08 | 41.29 | 21.79 | 93.05 | 25.01 | 0.00 | 0.00 | 0.00 |
May | 60.46 | 34.85 | 25.61 | 96.71 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 66.80 | 38.95 | 27.85 | 108.48 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 62.15 | 32.34 | 29.81 | 100.51 | 10.96 | 0.00 | 0.00 | 0.00 |
August | 58.00 | 29.39 | 28.60 | 94.21 | 12.64 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 24.82 | 24.55 | 77.76 | 15.15 | 0.00 | 0.00 | 0.00 |
October | 46.76 | 27.87 | 18.88 | 72.74 | 20.02 | 0.00 | 0.00 | 0.00 |
November | 37.59 | 25.62 | 11.96 | 52.33 | 31.75 | 0.00 | 0.00 | 0.00 |
December | 31.69 | 20.81 | 10.88 | 43.59 | 32.89 | 5.17 | 0.00 | 0.00 |
Annual Sum or Average | 50.43 | 30.05 | 20.38 | 76.78 | 22.33 | 76.83 | 0.00 | 0.00 |
Minimum of Months | 31.69 | 20.81 | 10.88 | 43.59 | 10.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.80 | 41.29 | 29.81 | 108.48 | 34.51 | 50.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.97 | 50.27 | 24.70 | 99.64 | 40.45 | 68.50 | 0.00 | 0.00 |
February | 94.58 | 64.90 | 29.68 | 126.68 | 35.78 | 128.83 | 0.00 | 0.00 |
March | 103.83 | 64.66 | 39.17 | 138.85 | 34.28 | 19.00 | 0.00 | 0.00 |
April | 131.79 | 85.64 | 46.15 | 177.42 | 33.28 | 0.00 | 0.00 | 0.00 |
May | 126.34 | 72.09 | 54.25 | 175.18 | 22.51 | 1.00 | 0.00 | 0.00 |
June | 139.43 | 80.43 | 59.00 | 195.97 | 22.26 | 0.00 | 0.00 | 0.00 |
July | 129.89 | 66.76 | 63.13 | 180.43 | 19.96 | 4.67 | 0.00 | 0.00 |
August | 121.38 | 60.80 | 60.59 | 169.62 | 21.98 | 10.33 | 0.00 | 0.00 |
September | 103.59 | 51.58 | 52.01 | 142.20 | 25.22 | 1.17 | 0.00 | 0.00 |
October | 98.45 | 58.45 | 40.00 | 135.45 | 30.03 | 19.83 | 0.00 | 0.00 |
November | 79.99 | 54.65 | 25.34 | 105.08 | 39.14 | 37.00 | 0.00 | 0.00 |
December | 68.06 | 45.01 | 23.05 | 89.91 | 38.94 | 58.17 | 0.00 | 0.00 |
Annual Sum or Average | 106.03 | 62.86 | 43.17 | 144.74 | 30.28 | 348.50 | 0.00 | 0.00 |
Minimum of Months | 68.06 | 45.01 | 23.05 | 89.91 | 19.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.43 | 85.64 | 63.13 | 195.97 | 40.45 | 128.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194611E+09 | 0.105110E+09 | 89501092.54 | 0.267892E+09 | 0.212601E+09 |
February | 0.198918E+09 | 0.100540E+09 | 98377706.66 | 0.282585E+09 | 0.161019E+09 |
March | 0.217457E+09 | 96218383.29 | 0.121239E+09 | 0.313920E+09 | 0.162462E+09 |
April | 0.261006E+09 | 0.119869E+09 | 0.141136E+09 | 0.409573E+09 | 0.120083E+09 |
May | 0.224677E+09 | 73120105.75 | 0.151557E+09 | 0.415812E+09 | 51471934.58 |
June | 0.241752E+09 | 84969007.38 | 0.156783E+09 | 0.455942E+09 | 46412936.74 |
July | 0.227617E+09 | 63068180.83 | 0.164548E+09 | 0.426312E+09 | 37950356.14 |
August | 0.230136E+09 | 70173695.79 | 0.159962E+09 | 0.432074E+09 | 49472788.13 |
September | 0.205325E+09 | 70495794.42 | 0.134829E+09 | 0.366184E+09 | 62368882.30 |
October | 0.216657E+09 | 93406824.73 | 0.123250E+09 | 0.373731E+09 | 97310268.79 |
November | 0.180008E+09 | 90429008.90 | 89578959.29 | 0.265101E+09 | 0.162820E+09 |
December | 0.178966E+09 | 95159512.64 | 83806726.57 | 0.252062E+09 | 0.195053E+09 |
Annual Sum or Average | 0.257713E+10 | 0.106256E+10 | 0.151457E+10 | 0.426119E+10 | 0.135902E+10 |
Minimum of Months | 0.178966E+09 | 63068180.83 | 83806726.57 | 0.252062E+09 | 37950356.14 |
Maximum of Months | 0.261006E+09 | 0.119869E+09 | 0.164548E+09 | 0.455942E+09 | 0.212601E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194611E+09 | 0.105110E+09 | 89501092.54 | 0.267892E+09 | 0.212601E+09 |
February | 0.198918E+09 | 0.100540E+09 | 98377706.66 | 0.282585E+09 | 0.161019E+09 |
March | 0.217457E+09 | 96218383.29 | 0.121239E+09 | 0.313920E+09 | 0.162462E+09 |
April | 0.261006E+09 | 0.119869E+09 | 0.141136E+09 | 0.409573E+09 | 0.120083E+09 |
May | 0.224677E+09 | 73120105.75 | 0.151557E+09 | 0.415812E+09 | 51471934.58 |
June | 0.241752E+09 | 84969007.38 | 0.156783E+09 | 0.455942E+09 | 46412936.74 |
July | 0.227617E+09 | 63068180.83 | 0.164548E+09 | 0.426312E+09 | 37950356.14 |
August | 0.230136E+09 | 70173695.79 | 0.159962E+09 | 0.432074E+09 | 49472788.13 |
September | 0.205325E+09 | 70495794.42 | 0.134829E+09 | 0.366184E+09 | 62368882.30 |
October | 0.216657E+09 | 93406824.73 | 0.123250E+09 | 0.373731E+09 | 97310268.79 |
November | 0.180008E+09 | 90429008.90 | 89578959.29 | 0.265101E+09 | 0.162820E+09 |
December | 0.178966E+09 | 95159512.64 | 83806726.57 | 0.252062E+09 | 0.195053E+09 |
Annual Sum or Average | 0.257713E+10 | 0.106256E+10 | 0.151457E+10 | 0.426119E+10 | 0.135902E+10 |
Minimum of Months | 0.178966E+09 | 63068180.83 | 83806726.57 | 0.252062E+09 | 37950356.14 |
Maximum of Months | 0.261006E+09 | 0.119869E+09 | 0.164548E+09 | 0.455942E+09 | 0.212601E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41523770.04 | 0.00 | 41523770.04 | 34869793.10 | 0.131346E+09 |
February | 44247244.57 | 0.00 | 44247244.57 | 41720250.28 | 98218793.24 |
March | 56842127.69 | 2657.73 | 56839469.96 | 62359005.53 | 97992639.36 |
April | 65080792.85 | 384956.40 | 64695836.45 | 86306147.84 | 70975802.56 |
May | 76109983.40 | 2865947.94 | 73244035.46 | 0.144851E+09 | 28949045.22 |
June | 83499391.23 | 5685212.29 | 77814178.95 | 0.165812E+09 | 26062861.31 |
July | 83793663.07 | 3127227.13 | 80666435.94 | 0.162727E+09 | 21771797.98 |
August | 75354197.92 | 775877.88 | 74578320.04 | 0.146428E+09 | 28142324.16 |
September | 62790968.62 | 12212.73 | 62778755.89 | 0.111571E+09 | 36392464.91 |
October | 56357047.91 | 0.00 | 56357047.91 | 92375181.41 | 57512735.14 |
November | 41403896.54 | 0.00 | 41403896.54 | 42685453.99 | 98349360.17 |
December | 38601065.29 | 0.00 | 38601065.29 | 33738528.57 | 0.119936E+09 |
Annual Sum or Average | 0.725604E+09 | 12854092.10 | 0.712750E+09 | 0.112544E+10 | 0.815649E+09 |
Minimum of Months | 38601065.29 | 0.00 | 38601065.29 | 33738528.57 | 21771797.98 |
Maximum of Months | 83793663.07 | 5685212.29 | 80666435.94 | 0.165812E+09 | 0.131346E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41522626.07 | 0.00 | 41522626.07 | 34868645.71 | 0.131345E+09 |
February | 44246067.70 | 0.00 | 44246067.70 | 41719048.62 | 98218099.75 |
March | 56840518.83 | 2657.60 | 56837861.22 | 62357155.27 | 97992103.47 |
April | 65079030.33 | 384938.36 | 64694091.98 | 86303923.73 | 70975140.44 |
May | 76107688.38 | 2865813.60 | 73241874.77 | 0.144848E+09 | 28948506.35 |
June | 83496833.73 | 5684945.81 | 77811887.91 | 0.165808E+09 | 26062314.07 |
July | 83791048.04 | 3127080.56 | 80663967.48 | 0.162723E+09 | 21771244.06 |
August | 75351899.12 | 775841.51 | 74576057.61 | 0.146425E+09 | 28141773.41 |
September | 62789054.11 | 12212.16 | 62776841.95 | 0.111568E+09 | 36391914.21 |
October | 56355422.90 | 0.00 | 56355422.90 | 92372914.37 | 57512126.16 |
November | 41402775.75 | 0.00 | 41402775.75 | 42684283.91 | 98348485.23 |
December | 38599992.55 | 0.00 | 38599992.55 | 33737472.46 | 0.119935E+09 |
Annual Sum or Average | 0.725583E+09 | 12853489.61 | 0.712729E+09 | 0.112541E+10 | 0.815642E+09 |
Minimum of Months | 38599992.55 | 0.00 | 38599992.55 | 33737472.46 | 21771244.06 |
Maximum of Months | 83791048.04 | 5684945.81 | 80663967.48 | 0.165808E+09 | 0.131345E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129660E+09 | 92441528.46 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.151937E+09 | 75626549.72 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188040E+09 | 75732953.71 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241193E+09 | 64825897.82 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259017E+09 | 35553510.06 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281181E+09 | 33576387.81 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269193E+09 | 29355391.77 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252341E+09 | 33856192.92 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201546E+09 | 39274644.13 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194835E+09 | 53632990.09 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135643E+09 | 82305373.66 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 88097146.78 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242134E+10 | 0.704279E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 29355391.77 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281181E+09 | 92441528.46 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129660E+09 | 92441528.46 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.151937E+09 | 75626549.72 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188040E+09 | 75732953.71 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241193E+09 | 64825897.82 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259017E+09 | 35553510.06 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281181E+09 | 33576387.81 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269193E+09 | 29355391.77 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252341E+09 | 33856192.92 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201546E+09 | 39274644.13 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194835E+09 | 53632990.09 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135643E+09 | 82305373.66 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 88097146.78 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242134E+10 | 0.704279E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 29355391.77 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281181E+09 | 92441528.46 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129660E+09 | 92441528.46 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.151937E+09 | 75626549.72 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188040E+09 | 75732953.71 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241193E+09 | 64825897.82 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259017E+09 | 35553510.06 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281181E+09 | 33576387.81 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269193E+09 | 29355391.77 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252341E+09 | 33856192.92 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201546E+09 | 39274644.13 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194835E+09 | 53632990.09 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135643E+09 | 82305373.66 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 88097146.78 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242134E+10 | 0.704279E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 29355391.77 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281181E+09 | 92441528.46 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129660E+09 | 92441528.46 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.151937E+09 | 75626549.72 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188040E+09 | 75732953.71 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241193E+09 | 64825897.82 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259017E+09 | 35553510.06 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281181E+09 | 33576387.81 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269193E+09 | 29355391.77 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252341E+09 | 33856192.92 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201546E+09 | 39274644.13 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194835E+09 | 53632990.09 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135643E+09 | 82305373.66 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 88097146.78 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242134E+10 | 0.704279E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 29355391.77 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281181E+09 | 92441528.46 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129660E+09 | 92441528.46 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.151937E+09 | 75626549.72 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188040E+09 | 75732953.71 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241193E+09 | 64825897.82 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259017E+09 | 35553510.06 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281181E+09 | 33576387.81 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269193E+09 | 29355391.77 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252341E+09 | 33856192.92 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201546E+09 | 39274644.13 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194835E+09 | 53632990.09 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135643E+09 | 82305373.66 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 88097146.78 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242134E+10 | 0.704279E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 29355391.77 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281181E+09 | 92441528.46 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129660E+09 | 92441528.46 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.151937E+09 | 75626549.72 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188040E+09 | 75732953.71 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241193E+09 | 64825897.82 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259017E+09 | 35553510.06 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281181E+09 | 33576387.81 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269193E+09 | 29355391.77 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252341E+09 | 33856192.92 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201546E+09 | 39274644.13 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194835E+09 | 53632990.09 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135643E+09 | 82305373.66 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 88097146.78 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242134E+10 | 0.704279E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 29355391.77 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281181E+09 | 92441528.46 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129660E+09 | 92441528.46 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.151937E+09 | 75626549.72 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188040E+09 | 75732953.71 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241193E+09 | 64825897.82 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259017E+09 | 35553510.06 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281181E+09 | 33576387.81 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269193E+09 | 29355391.77 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252341E+09 | 33856192.92 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201546E+09 | 39274644.13 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194835E+09 | 53632990.09 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135643E+09 | 82305373.66 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 88097146.78 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242134E+10 | 0.704279E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 29355391.77 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281181E+09 | 92441528.46 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129660E+09 | 92441528.46 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.151937E+09 | 75626549.72 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188040E+09 | 75732953.71 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241193E+09 | 64825897.82 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259017E+09 | 35553510.06 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281181E+09 | 33576387.81 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269193E+09 | 29355391.77 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252341E+09 | 33856192.92 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201546E+09 | 39274644.13 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194835E+09 | 53632990.09 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135643E+09 | 82305373.66 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 88097146.78 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242134E+10 | 0.704279E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 29355391.77 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281181E+09 | 92441528.46 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129660E+09 | 92441528.46 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.151937E+09 | 75626549.72 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188040E+09 | 75732953.71 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241193E+09 | 64825897.82 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259017E+09 | 35553510.06 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281181E+09 | 33576387.81 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269193E+09 | 29355391.77 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252341E+09 | 33856192.92 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201546E+09 | 39274644.13 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194835E+09 | 53632990.09 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135643E+09 | 82305373.66 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 88097146.78 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242134E+10 | 0.704279E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 29355391.77 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281181E+09 | 92441528.46 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129660E+09 | 92441528.46 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.151937E+09 | 75626549.72 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188040E+09 | 75732953.71 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241193E+09 | 64825897.82 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259017E+09 | 35553510.06 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281181E+09 | 33576387.81 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269193E+09 | 29355391.77 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252341E+09 | 33856192.92 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201546E+09 | 39274644.13 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194835E+09 | 53632990.09 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135643E+09 | 82305373.66 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 88097146.78 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242134E+10 | 0.704279E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 29355391.77 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281181E+09 | 92441528.46 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129660E+09 | 92441528.46 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.151937E+09 | 75626549.72 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188040E+09 | 75732953.71 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241193E+09 | 64825897.82 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259017E+09 | 35553510.06 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281181E+09 | 33576387.81 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269193E+09 | 29355391.77 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252341E+09 | 33856192.92 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201546E+09 | 39274644.13 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194835E+09 | 53632990.09 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135643E+09 | 82305373.66 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 88097146.78 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242134E+10 | 0.704279E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 29355391.77 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281181E+09 | 92441528.46 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129660E+09 | 92441528.46 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.151937E+09 | 75626549.72 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188040E+09 | 75732953.71 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241193E+09 | 64825897.82 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259017E+09 | 35553510.06 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281181E+09 | 33576387.81 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269193E+09 | 29355391.77 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252341E+09 | 33856192.92 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201546E+09 | 39274644.13 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194835E+09 | 53632990.09 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135643E+09 | 82305373.66 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 88097146.78 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242134E+10 | 0.704279E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 29355391.77 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281181E+09 | 92441528.46 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129660E+09 | 92441528.46 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.151937E+09 | 75626549.72 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188040E+09 | 75732953.71 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241193E+09 | 64825897.82 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259017E+09 | 35553510.06 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281181E+09 | 33576387.81 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269193E+09 | 29355391.77 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252341E+09 | 33856192.92 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201546E+09 | 39274644.13 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194835E+09 | 53632990.09 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135643E+09 | 82305373.66 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 88097146.78 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242134E+10 | 0.704279E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 29355391.77 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281181E+09 | 92441528.46 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93789781.47 | 62558844.91 | 31230936.57 | 0.129660E+09 | 92441528.46 |
February | 0.108276E+09 | 74372626.17 | 33903479.59 | 0.151937E+09 | 75626549.72 |
March | 0.132436E+09 | 82909163.00 | 49526558.35 | 0.188040E+09 | 75732953.71 |
April | 0.163508E+09 | 0.107027E+09 | 56480769.85 | 0.241193E+09 | 64825897.82 |
May | 0.161941E+09 | 93346126.68 | 68594801.13 | 0.259017E+09 | 35553510.06 |
June | 0.173154E+09 | 0.100955E+09 | 72199269.70 | 0.281181E+09 | 33576387.81 |
July | 0.166461E+09 | 86626483.94 | 79834055.37 | 0.269193E+09 | 29355391.77 |
August | 0.155336E+09 | 78723581.95 | 76612125.11 | 0.252341E+09 | 33856192.92 |
September | 0.127970E+09 | 64327122.64 | 63642760.89 | 0.201546E+09 | 39274644.13 |
October | 0.125235E+09 | 74656934.50 | 50577876.70 | 0.194835E+09 | 53632990.09 |
November | 97424705.79 | 66419672.73 | 31005033.06 | 0.135643E+09 | 82305373.66 |
December | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 88097146.78 |
Annual Sum or Average | 0.159042E+10 | 0.947667E+09 | 0.642751E+09 | 0.242134E+10 | 0.704279E+09 |
Minimum of Months | 84887787.38 | 55744794.92 | 29142992.46 | 0.116758E+09 | 29355391.77 |
Maximum of Months | 0.173154E+09 | 0.107027E+09 | 79834055.37 | 0.281181E+09 | 92441528.46 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200787E+09 | 0.134637E+09 | 66149917.80 | 0.266875E+09 | 0.108354E+09 |
February | 0.228817E+09 | 0.157007E+09 | 71810603.03 | 0.306465E+09 | 86569564.65 |
March | 0.278099E+09 | 0.173198E+09 | 0.104902E+09 | 0.371890E+09 | 91804999.55 |
April | 0.341602E+09 | 0.221971E+09 | 0.119631E+09 | 0.459872E+09 | 86258946.03 |
May | 0.338383E+09 | 0.193093E+09 | 0.145290E+09 | 0.469207E+09 | 60302547.15 |
June | 0.361400E+09 | 0.208475E+09 | 0.152925E+09 | 0.507959E+09 | 57708991.89 |
July | 0.347901E+09 | 0.178805E+09 | 0.169096E+09 | 0.483263E+09 | 53451666.66 |
August | 0.325110E+09 | 0.162839E+09 | 0.162271E+09 | 0.454302E+09 | 58866866.07 |
September | 0.268503E+09 | 0.133702E+09 | 0.134801E+09 | 0.368588E+09 | 65364135.56 |
October | 0.263690E+09 | 0.156562E+09 | 0.107128E+09 | 0.362791E+09 | 80442779.50 |
November | 0.207331E+09 | 0.141659E+09 | 65671433.97 | 0.272369E+09 | 0.101464E+09 |
December | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 0.104307E+09 |
Annual Sum or Average | 0.334391E+10 | 0.198250E+10 | 0.136140E+10 | 0.456439E+10 | 0.954895E+09 |
Minimum of Months | 0.182283E+09 | 0.120556E+09 | 61727465.37 | 0.240809E+09 | 53451666.66 |
Maximum of Months | 0.361400E+09 | 0.221971E+09 | 0.169096E+09 | 0.507959E+09 | 0.108354E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 221.34 | 252.10 | 176.33 | 78.49 | 97.84 | 0.00 | 0.00 |
February | 265.09 | 211.30 | 201.03 | 83.12 | 117.91 | 0.00 | 0.00 |
March | 279.21 | 192.72 | 204.82 | 71.85 | 132.97 | 0.00 | 0.00 |
April | 381.48 | 146.28 | 251.61 | 92.79 | 158.82 | 0.00 | 0.00 |
May | 418.15 | 59.55 | 224.60 | 56.74 | 167.86 | 0.00 | 0.00 |
June | 479.28 | 55.46 | 250.96 | 69.95 | 181.02 | 0.00 | 0.00 |
July | 439.55 | 44.31 | 232.53 | 49.43 | 183.10 | 0.00 | 0.00 |
August | 431.83 | 57.81 | 228.11 | 52.98 | 175.13 | 0.00 | 0.00 |
September | 368.42 | 75.99 | 206.88 | 54.40 | 152.47 | 0.00 | 0.00 |
October | 347.44 | 115.00 | 203.86 | 69.75 | 134.11 | 0.00 | 0.00 |
November | 235.21 | 199.24 | 170.84 | 69.78 | 101.07 | 0.00 | 0.00 |
December | 209.91 | 231.70 | 162.46 | 71.06 | 91.40 | 0.00 | 0.00 |
Annual Sum or Average | 340.07 | 136.37 | 209.46 | 68.20 | 141.26 | 0.00 | 0.00 |
Minimum of Months | 209.91 | 44.31 | 162.46 | 49.43 | 91.40 | 0.00 | 0.00 |
Maximum of Months | 479.28 | 252.10 | 251.61 | 92.79 | 183.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 677.74 | 483.19 | 490.24 | 327.00 | 163.24 | 0.00 | 0.00 |
February | 879.26 | 437.65 | 626.60 | 430.40 | 196.20 | 0.00 | 0.00 |
March | 982.89 | 395.86 | 692.24 | 433.37 | 258.88 | 0.00 | 0.00 |
April | 1302.74 | 350.14 | 883.14 | 578.08 | 305.07 | 0.00 | 0.00 |
May | 1353.88 | 185.84 | 846.47 | 487.92 | 358.55 | 0.00 | 0.00 |
June | 1518.73 | 181.35 | 935.25 | 545.28 | 389.97 | 0.00 | 0.00 |
July | 1407.07 | 153.44 | 870.09 | 452.80 | 417.29 | 0.00 | 0.00 |
August | 1318.98 | 176.97 | 811.94 | 411.49 | 400.45 | 0.00 | 0.00 |
September | 1088.60 | 212.13 | 691.20 | 347.45 | 343.75 | 0.00 | 0.00 |
October | 1018.40 | 280.34 | 654.60 | 390.23 | 264.37 | 0.00 | 0.00 |
November | 732.64 | 444.55 | 526.21 | 358.75 | 167.47 | 0.00 | 0.00 |
December | 610.30 | 460.48 | 443.71 | 291.38 | 152.33 | 0.00 | 0.00 |
Annual Sum or Average | 1074.92 | 312.66 | 706.05 | 420.70 | 285.34 | 0.00 | 0.00 |
Minimum of Months | 610.30 | 153.44 | 443.71 | 291.38 | 152.33 | 0.00 | 0.00 |
Maximum of Months | 1518.73 | 483.19 | 935.25 | 578.08 | 417.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13393.62 | 4440.75 | 2398.89 | 1608.57 | 790.32 | 0.00 | 0.00 |
February | 16266.38 | 3706.42 | 3026.68 | 2076.81 | 949.88 | 0.00 | 0.00 |
March | 18152.25 | 3476.41 | 3322.57 | 2069.27 | 1253.31 | 0.00 | 0.00 |
April | 23612.35 | 3444.69 | 4217.31 | 2740.38 | 1476.93 | 0.00 | 0.00 |
May | 31006.42 | 3035.31 | 4042.81 | 2306.97 | 1735.84 | 0.00 | 0.00 |
June | 34939.20 | 3395.27 | 4461.72 | 2573.77 | 1887.96 | 0.00 | 0.00 |
July | 35280.91 | 3337.42 | 4156.52 | 2136.26 | 2020.26 | 0.00 | 0.00 |
August | 32237.38 | 3490.19 | 3884.23 | 1945.50 | 1938.73 | 0.00 | 0.00 |
September | 27809.07 | 3364.73 | 3314.85 | 1650.64 | 1664.21 | 0.00 | 0.00 |
October | 22498.38 | 3593.46 | 3150.42 | 1870.51 | 1279.91 | 0.00 | 0.00 |
November | 13657.62 | 3985.12 | 2559.64 | 1748.88 | 810.76 | 0.00 | 0.00 |
December | 11297.55 | 4176.39 | 2177.82 | 1440.33 | 737.48 | 0.00 | 0.00 |
Annual Sum or Average | 23385.94 | 3620.61 | 3393.11 | 2011.67 | 1381.43 | 0.00 | 0.00 |
Minimum of Months | 11297.55 | 3035.31 | 2177.82 | 1440.33 | 737.48 | 0.00 | 0.00 |
Maximum of Months | 35280.91 | 4440.75 | 4461.72 | 2740.38 | 2020.26 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.592848E+09 | 0.675218E+09 | 0.472269E+09 | 0.210221E+09 | 0.262049E+09 | 0.00 | 0.00 |
February | 0.641304E+09 | 0.511168E+09 | 0.486329E+09 | 0.201080E+09 | 0.285249E+09 | 0.00 | 0.00 |
March | 0.747834E+09 | 0.516186E+09 | 0.548597E+09 | 0.192442E+09 | 0.356155E+09 | 0.00 | 0.00 |
April | 0.988785E+09 | 0.379146E+09 | 0.652171E+09 | 0.240508E+09 | 0.411662E+09 | 0.00 | 0.00 |
May | 0.111998E+10 | 0.159501E+09 | 0.601571E+09 | 0.151972E+09 | 0.449600E+09 | 0.00 | 0.00 |
June | 0.124229E+10 | 0.143740E+09 | 0.650501E+09 | 0.181308E+09 | 0.469192E+09 | 0.00 | 0.00 |
July | 0.117730E+10 | 0.118671E+09 | 0.622818E+09 | 0.132391E+09 | 0.490427E+09 | 0.00 | 0.00 |
August | 0.115660E+10 | 0.154832E+09 | 0.610978E+09 | 0.141899E+09 | 0.469079E+09 | 0.00 | 0.00 |
September | 0.954942E+09 | 0.196958E+09 | 0.536231E+09 | 0.141016E+09 | 0.395214E+09 | 0.00 | 0.00 |
October | 0.930586E+09 | 0.308021E+09 | 0.546027E+09 | 0.186814E+09 | 0.359213E+09 | 0.00 | 0.00 |
November | 0.609665E+09 | 0.516431E+09 | 0.442823E+09 | 0.180858E+09 | 0.261965E+09 | 0.00 | 0.00 |
December | 0.562213E+09 | 0.620589E+09 | 0.435134E+09 | 0.190319E+09 | 0.244815E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107244E+11 | 0.430046E+10 | 0.660545E+10 | 0.215083E+10 | 0.445462E+10 | 0.00 | 0.00 |
Minimum of Months | 0.562213E+09 | 0.118671E+09 | 0.435134E+09 | 0.132391E+09 | 0.244815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.124229E+10 | 0.675218E+09 | 0.652171E+09 | 0.240508E+09 | 0.490427E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181525E+10 | 0.129418E+10 | 0.131306E+10 | 0.875824E+09 | 0.437233E+09 | 0.00 | 0.00 |
February | 0.212712E+10 | 0.105877E+10 | 0.151587E+10 | 0.104122E+10 | 0.474649E+09 | 0.00 | 0.00 |
March | 0.263256E+10 | 0.106026E+10 | 0.185410E+10 | 0.116073E+10 | 0.693372E+09 | 0.00 | 0.00 |
April | 0.337670E+10 | 0.907563E+09 | 0.228911E+10 | 0.149837E+10 | 0.790731E+09 | 0.00 | 0.00 |
May | 0.362624E+10 | 0.497749E+09 | 0.226717E+10 | 0.130685E+10 | 0.960327E+09 | 0.00 | 0.00 |
June | 0.393654E+10 | 0.470069E+09 | 0.242416E+10 | 0.141337E+10 | 0.101079E+10 | 0.00 | 0.00 |
July | 0.376870E+10 | 0.410975E+09 | 0.233045E+10 | 0.121277E+10 | 0.111768E+10 | 0.00 | 0.00 |
August | 0.353277E+10 | 0.473987E+09 | 0.217470E+10 | 0.110213E+10 | 0.107257E+10 | 0.00 | 0.00 |
September | 0.282165E+10 | 0.549845E+09 | 0.179158E+10 | 0.900580E+09 | 0.890999E+09 | 0.00 | 0.00 |
October | 0.272769E+10 | 0.750862E+09 | 0.175329E+10 | 0.104520E+10 | 0.708090E+09 | 0.00 | 0.00 |
November | 0.189900E+10 | 0.115228E+10 | 0.136395E+10 | 0.929875E+09 | 0.434070E+09 | 0.00 | 0.00 |
December | 0.163462E+10 | 0.123336E+10 | 0.118843E+10 | 0.780427E+09 | 0.408002E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.338988E+11 | 0.985990E+10 | 0.222658E+11 | 0.132673E+11 | 0.899851E+10 | 0.00 | 0.00 |
Minimum of Months | 0.163462E+10 | 0.410975E+09 | 0.118843E+10 | 0.780427E+09 | 0.408002E+09 | 0.00 | 0.00 |
Maximum of Months | 0.393654E+10 | 0.129418E+10 | 0.242416E+10 | 0.149837E+10 | 0.111768E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.358735E+11 | 0.118941E+11 | 0.642520E+10 | 0.430840E+10 | 0.211680E+10 | 0.00 | 0.00 |
February | 0.393516E+11 | 0.896656E+10 | 0.732215E+10 | 0.502421E+10 | 0.229794E+10 | 0.00 | 0.00 |
March | 0.486190E+11 | 0.931121E+10 | 0.889918E+10 | 0.554233E+10 | 0.335685E+10 | 0.00 | 0.00 |
April | 0.612032E+11 | 0.892863E+10 | 0.109313E+11 | 0.710307E+10 | 0.382820E+10 | 0.00 | 0.00 |
May | 0.830476E+11 | 0.812977E+10 | 0.108283E+11 | 0.617899E+10 | 0.464928E+10 | 0.00 | 0.00 |
June | 0.905624E+11 | 0.880055E+10 | 0.115648E+11 | 0.667121E+10 | 0.489358E+10 | 0.00 | 0.00 |
July | 0.944964E+11 | 0.893896E+10 | 0.111328E+11 | 0.572176E+10 | 0.541106E+10 | 0.00 | 0.00 |
August | 0.863446E+11 | 0.934814E+10 | 0.104035E+11 | 0.521083E+10 | 0.519268E+10 | 0.00 | 0.00 |
September | 0.720811E+11 | 0.872138E+10 | 0.859210E+10 | 0.427846E+10 | 0.431363E+10 | 0.00 | 0.00 |
October | 0.602597E+11 | 0.962472E+10 | 0.843808E+10 | 0.500997E+10 | 0.342811E+10 | 0.00 | 0.00 |
November | 0.354005E+11 | 0.103294E+11 | 0.663458E+10 | 0.453310E+10 | 0.210149E+10 | 0.00 | 0.00 |
December | 0.302594E+11 | 0.111860E+11 | 0.583307E+10 | 0.385779E+10 | 0.197528E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.737499E+12 | 0.114180E+12 | 0.107005E+12 | 0.634401E+11 | 0.435649E+11 | 0.00 | 0.00 |
Minimum of Months | 0.302594E+11 | 0.812977E+10 | 0.583307E+10 | 0.385779E+10 | 0.197528E+10 | 0.00 | 0.00 |
Maximum of Months | 0.944964E+11 | 0.118941E+11 | 0.115648E+11 | 0.710307E+10 | 0.541106E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.767948E+09 | -688258662.8 | 0.00 | 0.00 | 744.00 | 0.00 | -79689801.6 | 58.99 | 0.00 | 0.00 |
February | 0.698335E+09 | -627186212.6 | 0.00 | 0.00 | 672.00 | 0.00 | -71149055.4 | 58.99 | 0.00 | 0.00 |
March | 0.781893E+09 | -704944711.7 | 0.00 | 0.00 | 744.00 | 0.00 | -76948524.7 | 58.99 | 0.00 | 0.00 |
April | 0.685335E+09 | -614745471.7 | 0.00 | 0.00 | 720.00 | 0.00 | -70589613.8 | 58.99 | 0.00 | 0.00 |
May | 0.664988E+09 | -594416979.5 | 0.00 | 0.00 | 744.00 | 0.00 | -70571508.7 | 58.99 | 0.00 | 0.00 |
June | 0.623479E+09 | -555366201.6 | 0.00 | 0.00 | 720.00 | 0.00 | -68112492.5 | 58.98 | 0.00 | 0.00 |
July | 0.589277E+09 | -519486199.6 | 0.00 | 0.00 | 744.00 | 0.00 | -69790649.8 | 58.99 | 0.00 | 0.00 |
August | 0.634241E+09 | -564071937.1 | 0.00 | 0.00 | 744.00 | 0.00 | -70169032.7 | 58.99 | 0.00 | 0.00 |
September | 0.619563E+09 | -551590951.4 | 0.00 | 0.00 | 720.00 | 0.00 | -67972175.5 | 58.99 | 0.00 | 0.00 |
October | 0.664403E+09 | -593436760.3 | 0.00 | 0.00 | 744.00 | 0.00 | -70966610.7 | 58.99 | 0.00 | 0.00 |
November | 0.683336E+09 | -611316792.2 | 0.00 | 0.00 | 720.00 | 0.00 | -72018882.8 | 58.99 | 0.00 | 0.00 |
December | 0.748630E+09 | -671014113.5 | 0.00 | 0.00 | 744.00 | 0.00 | -77615654.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.816143E+10 | -0.729583E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -865594002.2 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.589277E+09 | -704944711.7 | 0.00 | 0.00 | 672.00 | 0.00 | -79689801.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.781893E+09 | -519486199.6 | 0.00 | 0.00 | 744.00 | 0.00 | -67972175.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.80 | 0.50 | 02-JAN-11:20 | 137.56 | 0.00 | 0.00 | 10.50 | 641.25 | 0.00 | 0.00 | 19.00 |
February | 295.50 | 0.75 | 0.50 | 01-FEB-11:00 | 1397.68 | 0.00 | 0.00 | 47.67 | 618.47 | 0.00 | 0.00 | 20.83 |
March | 296.00 | 0.73 | 0.50 | 02-MAR-12:50 | 198.49 | 0.00 | 0.00 | 58.67 | 163.22 | 0.00 | 0.00 | 29.00 |
April | 347.33 | 0.70 | 0.50 | 01-APR-09:50 | 229.24 | 0.00 | 0.00 | 94.50 | 1127.87 | 0.00 | 0.00 | 86.33 |
May | 353.67 | 0.68 | 0.50 | 01-MAY-09:20 | 1047.56 | 0.00 | 0.00 | 168.50 | 193.02 | 0.00 | 0.00 | 61.17 |
June | 394.00 | 0.68 | 0.50 | 01-JUN-10:20 | 695.53 | 0.00 | 0.00 | 169.50 | 194.26 | 0.00 | 0.00 | 67.50 |
July | 390.00 | 0.67 | 0.50 | 01-JUL-09:00 | 1458.95 | 0.00 | 0.00 | 181.00 | 216.42 | 0.00 | 0.00 | 94.17 |
August | 380.83 | 0.66 | 0.50 | 01-AUG-10:09 | 626.47 | 0.00 | 0.00 | 174.83 | 1295.26 | 0.00 | 0.00 | 135.00 |
September | 342.17 | 0.68 | 0.50 | 01-SEP-10:39 | 263.00 | 0.00 | 0.00 | 129.33 | 210.87 | 0.00 | 0.00 | 83.83 |
October | 330.00 | 0.70 | 0.50 | 04-OCT-10:00 | 219.22 | 0.00 | 0.00 | 75.17 | 179.40 | 0.00 | 0.00 | 42.17 |
November | 308.00 | 0.79 | 0.50 | 01-NOV-11:39 | 144.62 | 0.00 | 0.00 | 9.33 | 122.68 | 0.00 | 0.00 | 3.33 |
December | 282.83 | 0.80 | 0.50 | 03-DEC-12:09 | 135.43 | 0.00 | 0.00 | 4.33 | 114.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | 0.72 | 568.80 | 0.00 | 0.00 | 1123.33 | 433.01 | 0.00 | 0.00 | 642.33 | ||
Minimum of Months | 282.83 | 0.66 | 0.50 | 135.43 | 0.00 | 0.00 | 4.33 | 114.97 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 394.00 | 0.80 | 0.50 | 1458.95 | 0.00 | 0.00 | 181.00 | 1295.26 | 0.00 | 0.00 | 135.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.68 | 0.50 | 01-JAN-09:50 | 164.96 | 10.89 | 0.00 | 89.33 | 137.75 | 14.54 | 11.50 | 58.00 |
February | 295.50 | 0.63 | 0.50 | 01-FEB-11:39 | 654.58 | 11.61 | 0.00 | 159.33 | 161.93 | 15.36 | 23.83 | 88.17 |
March | 296.00 | 0.62 | 0.50 | 02-MAR-12:39 | 234.13 | 12.68 | 0.00 | 191.00 | 198.28 | 16.58 | 55.50 | 137.17 |
April | 347.33 | 0.61 | 0.50 | 01-APR-08:09 | 264.90 | 12.55 | 0.00 | 231.17 | 222.96 | 16.24 | 61.50 | 179.17 |
May | 353.67 | 0.59 | 0.50 | 01-MAY-07:49 | 294.44 | 13.62 | 0.00 | 265.17 | 250.29 | 17.31 | 76.17 | 221.50 |
June | 394.00 | 0.59 | 0.50 | 01-JUN-07:19 | 306.40 | 13.58 | 0.00 | 271.00 | 265.68 | 17.16 | 91.83 | 224.83 |
July | 390.00 | 0.57 | 0.50 | 01-JUL-07:10 | 333.50 | 14.13 | 0.00 | 285.67 | 288.74 | 17.62 | 94.50 | 239.83 |
August | 380.83 | 0.58 | 0.50 | 01-AUG-07:30 | 504.88 | 13.96 | 0.00 | 272.50 | 288.89 | 17.45 | 93.83 | 231.83 |
September | 342.17 | 0.59 | 0.50 | 01-SEP-07:00 | 958.37 | 13.62 | 0.00 | 236.17 | 258.05 | 17.12 | 79.17 | 190.67 |
October | 330.00 | 0.60 | 0.50 | 01-OCT-08:30 | 385.95 | 13.62 | 7.33 | 206.00 | 378.87 | 16.87 | 63.67 | 156.83 |
November | 308.00 | 0.66 | 0.50 | 01-NOV-09:50 | 951.79 | 13.14 | 29.17 | 113.50 | 1029.63 | 14.94 | 11.00 | 73.50 |
December | 282.83 | 0.67 | 0.50 | 02-DEC-09:00 | 162.53 | 10.91 | 0.00 | 74.00 | 135.19 | 14.47 | 0.00 | 43.67 |
Annual Sum or Average | 4027.67 | 0.61 | 433.76 | 12.95 | 36.50 | 2394.83 | 300.63 | 16.41 | 662.50 | 1845.17 | ||
Minimum of Months | 282.83 | 0.57 | 0.50 | 162.53 | 10.89 | 0.00 | 74.00 | 135.19 | 14.47 | 0.00 | 43.67 | |
Maximum of Months | 394.00 | 0.68 | 0.50 | 958.37 | 14.13 | 29.17 | 285.67 | 1029.63 | 17.62 | 94.50 | 239.83 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.83 | 0.61 | 30-JAN-16:30 | 303.74 | 22.72 | 117.67 | 37.83 | 100.83 | 19.72 | 85.50 | 0.00 |
February | 295.50 | 0.80 | 0.61 | 08-FEB-16:30 | 416.59 | 23.71 | 134.00 | 53.50 | 145.89 | 22.01 | 127.17 | 11.50 |
March | 296.00 | 0.79 | 0.61 | 02-MAR-15:30 | 238.58 | 21.81 | 121.83 | 42.00 | 178.57 | 22.90 | 138.17 | 23.50 |
April | 347.33 | 0.78 | 0.61 | 01-APR-16:10 | 223.61 | 19.97 | 123.67 | 40.50 | 221.53 | 21.82 | 160.33 | 44.33 |
May | 353.67 | 0.78 | 0.61 | 01-MAY-15:20 | 234.11 | 20.16 | 114.50 | 36.83 | 195.90 | 21.40 | 162.50 | 34.33 |
June | 394.00 | 0.77 | 0.61 | 01-JUN-15:09 | 241.50 | 19.85 | 121.50 | 42.00 | 206.65 | 21.13 | 175.83 | 39.17 |
July | 390.00 | 0.77 | 0.61 | 01-JUL-14:00 | 248.00 | 20.12 | 126.83 | 49.50 | 185.48 | 21.30 | 182.50 | 33.00 |
August | 380.83 | 0.77 | 0.61 | 01-AUG-15:09 | 243.32 | 20.31 | 143.67 | 50.83 | 190.33 | 21.39 | 187.17 | 37.17 |
September | 342.17 | 0.78 | 0.61 | 01-SEP-14:00 | 271.53 | 21.26 | 146.33 | 48.33 | 208.46 | 22.42 | 178.50 | 34.50 |
October | 330.00 | 0.78 | 0.61 | 01-OCT-15:30 | 312.06 | 23.40 | 164.33 | 59.50 | 224.67 | 23.61 | 168.83 | 27.00 |
November | 308.00 | 0.83 | 0.63 | 02-NOV-16:19 | 228.17 | 21.93 | 119.17 | 30.50 | 104.69 | 19.91 | 92.67 | 0.00 |
December | 282.83 | 0.82 | 0.65 | 03-DEC-15:30 | 243.59 | 22.95 | 119.17 | 27.50 | 101.68 | 19.91 | 83.00 | 0.00 |
Annual Sum or Average | 4027.67 | 0.79 | 264.95 | 21.39 | 1552.67 | 518.83 | 175.26 | 21.48 | 1742.17 | 284.50 | ||
Minimum of Months | 282.83 | 0.77 | 0.61 | 223.61 | 19.85 | 114.50 | 27.50 | 100.83 | 19.72 | 83.00 | 0.00 | |
Maximum of Months | 394.00 | 0.83 | 0.65 | 416.59 | 23.71 | 164.33 | 59.50 | 224.67 | 23.61 | 187.17 | 44.33 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.775422E+09 | 26718.29 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.443868E+09 | 26718.29 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311861E+09 | 26718.29 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 185975.79 | 168.45 | 11-APR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20626955.55 | 3020.79 | 15-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.435418E+09 | 26718.29 | 20-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.775422E+09 | 26718.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2157036.38 | 1937.35 | 10-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5079543.77 | 13938.72 | 05-FEB-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7236580.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5079543.77 | 13938.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.908468E+09 | 0.585804E+09 | 22874.85 | 02-JAN-06:02 | 12480.09 | 0.00 |
February | 0.00 | 0.00 | 0.161094E+10 | 0.106263E+10 | 23931.91 | 27-FEB-06:03 | 11375.63 | 0.00 |
March | 0.00 | 0.00 | 0.268793E+10 | 0.184400E+10 | 25975.01 | 07-MAR-06:03 | 11155.59 | 0.00 |
April | 0.00 | 0.00 | 0.598824E+10 | 0.431682E+10 | 27160.94 | 29-APR-05:01 | 12610.41 | 0.00 |
May | 0.00 | 0.00 | 0.125678E+11 | 0.851793E+10 | 28664.90 | 23-MAY-05:01 | 10928.85 | 0.00 |
June | 0.00 | 0.00 | 0.135144E+11 | 0.918840E+10 | 28248.37 | 30-JUN-05:01 | 14889.38 | 0.00 |
July | 0.00 | 0.00 | 0.140277E+11 | 0.905548E+10 | 28615.57 | 31-JUL-05:01 | 11599.04 | 0.00 |
August | 0.00 | 0.00 | 0.151044E+11 | 0.984894E+10 | 28765.77 | 11-AUG-05:01 | 11079.69 | 0.00 |
September | 0.00 | 0.00 | 0.127564E+11 | 0.819790E+10 | 28475.28 | 11-SEP-05:01 | 15829.67 | 0.00 |
October | 0.00 | 0.00 | 0.103638E+11 | 0.700492E+10 | 28700.28 | 23-OCT-05:01 | 11031.32 | 0.00 |
November | 0.00 | 0.00 | 0.419043E+10 | 0.289229E+10 | 27474.40 | 02-NOV-05:01 | 15055.97 | 0.00 |
December | 0.00 | 0.00 | 0.252064E+10 | 0.167523E+10 | 26553.61 | 15-DEC-06:02 | 10955.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.962411E+11 | 0.641904E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.908468E+09 | 0.585804E+09 | 22874.85 | 10928.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.151044E+11 | 0.984894E+10 | 28765.77 | 15829.67 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.142978E+09 | 0.107567E+09 | 69559.32 | 01-JAN-12:35 | 48481.46 | 0.00 |
February | 0.00 | 0.00 | 0.336419E+09 | 0.206309E+09 | 12246.86 | 27-FEB-15:00 | 7792.54 | 0.00 |
March | 0.00 | 0.00 | 0.896694E+09 | 0.511356E+09 | 21713.27 | 26-MAR-14:05 | 15204.02 | 0.00 |
April | 0.00 | 0.00 | 0.768518E+10 | 0.525238E+10 | 77874.57 | 30-APR-14:25 | 37344.98 | 0.00 |
May | 0.00 | 0.00 | 0.276564E+11 | 0.181322E+11 | 80197.60 | 21-MAY-08:65 | 35363.49 | 0.00 |
June | 0.00 | 0.00 | 0.329517E+11 | 0.220319E+11 | 71232.00 | 24-JUN-17:08 | 49460.88 | 0.00 |
July | 0.00 | 0.00 | 0.365660E+11 | 0.230354E+11 | 75310.10 | 31-JUL-17:10 | 41704.58 | 0.00 |
August | 0.00 | 0.00 | 0.361295E+11 | 0.227521E+11 | 80318.86 | 11-AUG-05:10 | 41245.94 | 0.00 |
September | 0.00 | 0.00 | 0.270190E+11 | 0.163654E+11 | 77500.61 | 02-SEP-22:45 | 36934.83 | 0.00 |
October | 0.00 | 0.00 | 0.215142E+11 | 0.134577E+11 | 81436.79 | 08-OCT-07:45 | 32352.22 | 0.00 |
November | 0.00 | 0.00 | 0.339613E+10 | 0.202149E+10 | 38200.83 | 05-NOV-13:55 | 29079.95 | 0.00 |
December | 0.00 | 0.00 | 0.132948E+10 | 0.769937E+09 | 19543.14 | 15-DEC-14:10 | 12214.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.195624E+12 | 0.124644E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.142978E+09 | 0.107567E+09 | 12246.86 | 7792.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.365660E+11 | 0.230354E+11 | 81436.79 | 49460.88 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.496067E+09 | 0.22 | 1190.80 | 02-JAN-06:02 | 0.90 |
February | 0.448276E+09 | 0.22 | 1190.80 | 06-FEB-06:01 | 0.91 |
March | 0.519891E+09 | 0.23 | 1190.80 | 10-MAR-06:02 | 0.91 |
April | 0.482988E+09 | 0.22 | 1190.80 | 01-APR-05:03 | 0.89 |
May | 0.562692E+09 | 0.24 | 1190.80 | 01-MAY-05:01 | 0.89 |
June | 0.598086E+09 | 0.26 | 1190.80 | 01-JUN-05:01 | 0.89 |
July | 0.617049E+09 | 0.25 | 1190.80 | 01-JUL-05:01 | 0.89 |
August | 0.662283E+09 | 0.26 | 1190.80 | 01-AUG-05:01 | 0.89 |
September | 0.560458E+09 | 0.24 | 1190.80 | 01-SEP-05:01 | 0.89 |
October | 0.544447E+09 | 0.23 | 1190.80 | 02-OCT-05:01 | 0.90 |
November | 0.460058E+09 | 0.20 | 1190.80 | 01-NOV-05:02 | 0.89 |
December | 0.487198E+09 | 0.21 | 1190.80 | 12-DEC-06:03 | 0.89 |
Annual Sum or Average | 0.643949E+10 | 0.23 | |||
Minimum of Months | 0.448276E+09 | 0.20 | 1190.80 | 0.89 | |
Maximum of Months | 0.662283E+09 | 0.26 | 1190.80 | 0.91 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.108480E+10 | 0.20 | 1132.85 | 10-JAN-07:10 | 0.55 |
February | 0.996296E+09 | 0.20 | 1093.68 | 02-FEB-14:40 | 0.52 |
March | 0.116965E+10 | 0.21 | 1093.68 | 31-MAR-14:30 | 0.52 |
April | 0.111615E+10 | 0.22 | 2734.20 | 23-APR-14:03 | 0.87 |
May | 0.131799E+10 | 0.28 | 2734.20 | 02-MAY-17:08 | 0.87 |
June | 0.137860E+10 | 0.32 | 2734.20 | 04-JUN-10:23 | 0.87 |
July | 0.145658E+10 | 0.34 | 2734.20 | 02-JUL-16:33 | 0.87 |
August | 0.147145E+10 | 0.33 | 2734.20 | 01-AUG-17:06 | 0.87 |
September | 0.130621E+10 | 0.29 | 2734.20 | 03-SEP-10:23 | 0.87 |
October | 0.124706E+10 | 0.26 | 2734.20 | 01-OCT-13:43 | 0.87 |
November | 0.104887E+10 | 0.20 | 1281.41 | 05-NOV-13:55 | 0.58 |
December | 0.108274E+10 | 0.20 | 1093.68 | 14-DEC-12:20 | 0.52 |
Annual Sum or Average | 0.146764E+11 | 0.25 | |||
Minimum of Months | 0.996296E+09 | 0.20 | 1093.68 | 0.52 | |
Maximum of Months | 0.147145E+10 | 0.34 | 2734.20 | 0.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.710079E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.827668E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.115222E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.189657E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.351788E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.380547E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.392363E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.420039E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.348002E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.294927E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.143514E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.107422E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.289726E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.710079E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.420039E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.111986E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.108112E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.139479E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.301718E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.814336E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.950345E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.103887E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.102557E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.781892E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.643949E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.187520E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.141208E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.624498E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.108112E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.103887E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.496067E+09 | 0.908468E+09 | 0.775422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.448276E+09 | 0.160931E+10 | 0.443868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.519891E+09 | 0.268288E+10 | 0.311861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.482988E+09 | 0.597774E+10 | 185975.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.562692E+09 | 0.125638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.598086E+09 | 0.135100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.617049E+09 | 0.140277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.662283E+09 | 0.151017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.560458E+09 | 0.127564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.544447E+09 | 0.103503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.460058E+09 | 0.418287E+10 | 20626955.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.487198E+09 | 0.251701E+10 | 0.435418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.643949E+10 | 0.961880E+11 | 0.198738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.448276E+09 | 0.908468E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.662283E+09 | 0.151017E+11 | 0.775422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.108480E+10 | 0.131265E+09 | 2157036.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.996296E+09 | 0.336419E+09 | 5079543.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116965E+10 | 0.896694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111615E+10 | 0.764950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131799E+10 | 0.276482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137860E+10 | 0.329517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145658E+10 | 0.365660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147145E+10 | 0.361222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130621E+10 | 0.270034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124706E+10 | 0.214427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104887E+10 | 0.339613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108274E+10 | 0.132948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146764E+11 | 0.195474E+12 | 7236580.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.996296E+09 | 0.131265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147145E+10 | 0.365660E+11 | 5079543.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.496067E+09 | 0.00 | 0.00 | 0.00 | 0.214012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.448276E+09 | 0.00 | 0.00 | 0.00 | 0.379392E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.519891E+09 | 0.00 | 0.00 | 0.00 | 0.632329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.482988E+09 | 0.00 | 0.00 | 0.00 | 0.141359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.562692E+09 | 0.00 | 0.00 | 0.00 | 0.295519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.598086E+09 | 0.00 | 0.00 | 0.00 | 0.320739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.617049E+09 | 0.00 | 0.00 | 0.00 | 0.330658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.662283E+09 | 0.00 | 0.00 | 0.00 | 0.353810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.560458E+09 | 0.00 | 0.00 | 0.00 | 0.291956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.544447E+09 | 0.00 | 0.00 | 0.00 | 0.240483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.460058E+09 | 0.00 | 0.00 | 0.00 | 0.975084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.487198E+09 | 0.00 | 0.00 | 0.00 | 0.587021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.643949E+10 | 0.00 | 0.00 | 0.00 | 0.225331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.448276E+09 | 0.00 | 0.00 | 0.00 | 0.214012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.662283E+09 | 0.00 | 0.00 | 0.00 | 0.353810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.108480E+10 | 0.00 | 0.00 | 0.00 | 35056609.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.996296E+09 | 0.00 | 0.00 | 0.00 | 84828384.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116965E+10 | 0.00 | 0.00 | 0.00 | 0.225140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111615E+10 | 0.00 | 0.00 | 0.00 | 0.190103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131799E+10 | 0.00 | 0.00 | 0.00 | 0.682537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137860E+10 | 0.00 | 0.00 | 0.00 | 0.812485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145658E+10 | 0.00 | 0.00 | 0.00 | 0.893210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147145E+10 | 0.00 | 0.00 | 0.00 | 0.878421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130621E+10 | 0.00 | 0.00 | 0.00 | 0.651270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124706E+10 | 0.00 | 0.00 | 0.00 | 0.519242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104887E+10 | 0.00 | 0.00 | 0.00 | 0.826327E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108274E+10 | 0.00 | 0.00 | 0.00 | 0.329331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146764E+11 | 0.00 | 0.00 | 0.00 | 0.477734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.996296E+09 | 0.00 | 0.00 | 0.00 | 35056609.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147145E+10 | 0.00 | 0.00 | 0.00 | 0.893210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.603840E+09 | 81522115.88 | 0.00 | 513698.20 | 0.00 | 0.142972E+09 | 0.423342E+09 | 0.00 | 0.18 |
February | 0.378559E+09 | 0.147381E+09 | 0.00 | 744372.17 | 0.00 | 83463633.54 | 0.469673E+09 | 0.00 | 0.23 |
March | 0.359723E+09 | 0.293524E+09 | 0.00 | 1255735.92 | 0.00 | 25493030.09 | 0.732014E+09 | 0.00 | 0.28 |
April | 16029067.93 | 0.656306E+09 | 0.00 | 2443168.53 | 0.00 | 0.00 | 0.694437E+09 | 0.00 | 0.31 |
May | 0.00 | 0.203197E+10 | 0.00 | 879888.91 | 0.00 | 0.00 | 1059891.49 | 0.00 | 0.13 |
June | 0.00 | 0.233076E+10 | 0.00 | 953558.51 | 0.00 | 0.00 | 2559236.25 | 0.00 | 0.14 |
July | 0.00 | 0.261854E+10 | 0.00 | 1175688.70 | 0.00 | 0.00 | 1588086.75 | 0.00 | 0.13 |
August | 0.00 | 0.260532E+10 | 0.00 | 1715514.97 | 0.00 | 0.00 | 1149541.48 | 0.00 | 0.14 |
September | 0.00 | 0.213142E+10 | 0.00 | 2897428.39 | 0.00 | 0.00 | 2545073.52 | 0.00 | 0.13 |
October | 875385.94 | 0.160177E+10 | 0.00 | 3753231.18 | 0.00 | 0.00 | 0.521397E+09 | 0.00 | 0.22 |
November | 70942505.68 | 0.486628E+09 | 0.00 | 2340202.00 | 0.00 | 958343.99 | 0.959721E+09 | 0.00 | 0.33 |
December | 0.477216E+09 | 0.324280E+09 | 0.00 | 929713.01 | 0.00 | 88765285.82 | 0.492563E+09 | 0.00 | 0.22 |
Annual Sum or Average | 0.190718E+10 | 0.153094E+11 | 0.00 | 19602200.48 | 0.00 | 0.341652E+09 | 0.430205E+10 | 0.00 | 0.20 |
Minimum of Months | 0.00 | 81522115.88 | 0.00 | 513698.20 | 0.00 | 0.00 | 1059891.49 | 0.00 | 0.13 |
Maximum of Months | 0.603840E+09 | 0.261854E+10 | 0.00 | 3753231.18 | 0.00 | 0.142972E+09 | 0.959721E+09 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.324058E+10 | 0.00 | 0.00 | 117457.84 | 6644198.90 | 0.00 | 75105167.23 | 0.00 | 0.18 |
February | 0.243779E+10 | 6148584.02 | 0.00 | 332439.12 | 3287350.60 | 0.00 | 0.225541E+09 | 0.00 | 0.21 |
March | 0.270307E+10 | 78257860.07 | 0.00 | 368146.27 | 3481932.08 | 0.00 | 0.258942E+09 | 0.00 | 0.23 |
April | 0.115250E+10 | 0.974088E+09 | 0.00 | 1938958.74 | 2562639.44 | 0.00 | 0.111551E+10 | 0.00 | 0.27 |
May | 251220.82 | 0.507687E+10 | 0.00 | 290608.73 | 0.00 | 0.00 | 61347500.36 | 0.00 | 0.20 |
June | 1419260.21 | 0.704101E+10 | 0.00 | 152260.65 | 0.00 | 0.00 | 49683443.63 | 0.00 | 0.20 |
July | 0.00 | 0.788372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
August | 0.00 | 0.748080E+10 | 0.00 | 190774.66 | 0.00 | 0.00 | 40772977.20 | 0.00 | 0.21 |
September | 548427.18 | 0.497135E+10 | 0.00 | 1142140.97 | 0.00 | 0.00 | 0.449495E+09 | 0.00 | 0.24 |
October | 0.543991E+09 | 0.381247E+10 | 0.00 | 2680954.85 | 0.00 | 0.00 | 0.736157E+09 | 0.00 | 0.24 |
November | 0.193111E+10 | 0.643831E+09 | 0.00 | 640032.42 | 14256663.12 | 0.00 | 0.556007E+09 | 0.00 | 0.21 |
December | 0.271063E+10 | 0.173740E+09 | 0.00 | 204020.81 | 10570315.69 | 0.00 | 0.233323E+09 | 0.00 | 0.20 |
Annual Sum or Average | 0.147219E+11 | 0.381423E+11 | 0.00 | 8057795.05 | 40803099.83 | 0.00 | 0.380188E+10 | 0.00 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.324058E+10 | 0.788372E+10 | 0.00 | 2680954.85 | 14256663.12 | 0.00 | 0.111551E+10 | 0.00 | 0.27 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:06
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.701281E+12 | 0.329501E+11 | 0.00 | 0.443565E+10 | 0.166485E+10 |
February | 0.764879E+12 | 0.247436E+11 | 0.00 | 0.348281E+10 | 0.262336E+10 |
March | 0.888147E+12 | 0.332060E+11 | 0.00 | 0.373110E+10 | 0.459314E+10 |
April | 0.105504E+13 | 0.279531E+11 | 0.00 | 0.136126E+10 | 0.169881E+11 |
May | 0.104893E+13 | 0.402396E+11 | 0.00 | -0.699788E+10 | 0.500047E+11 |
June | 0.106214E+13 | 0.485040E+11 | 0.00 | -0.930343E+10 | 0.577983E+11 |
July | 0.108456E+13 | 0.497392E+11 | 0.00 | -0.104995E+11 | 0.628324E+11 |
August | 0.101953E+13 | 0.447825E+11 | 0.00 | -0.100420E+11 | 0.635563E+11 |
September | 0.854773E+12 | 0.381143E+11 | 0.00 | -0.664429E+10 | 0.492077E+11 |
October | 0.866948E+12 | 0.425951E+11 | 0.00 | -0.358862E+10 | 0.394752E+11 |
November | 0.665735E+12 | 0.260408E+11 | 0.00 | 0.237701E+10 | 0.939897E+10 |
December | 0.638824E+12 | 0.319020E+11 | 0.00 | 0.350274E+10 | 0.497679E+10 |
Annual Sum or Average | 0.106508E+14 | 0.440770E+12 | 0.00 | -0.281851E+11 | 0.363120E+12 |
Minimum of Months | 0.638824E+12 | 0.247436E+11 | 0.00 | -0.104995E+11 | 0.166485E+10 |