Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 10:43:17
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 514.52 | 106.41 | 106.41 |
Net Site Energy | 387.35 | 80.11 | 80.11 |
Total Source Energy | 1267.41 | 262.12 | 262.12 |
Net Source Energy | 864.66 | 178.83 | 178.83 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 173.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 32.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 75.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 42.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 29.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 340.70 | 173.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 173.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 32.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 75.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 42.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 7.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 22.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 173.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 32.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 75.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 42.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 29.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 24.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 24.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 17.88 | 35.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 70.46 | 35.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 24.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 17.88 | 35.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 70.46 | 35.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 132.837 | 38.99 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -5.67 | -1.7 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 127.170 | 37.33 |
Electricity Coming From Utility | 230.429 | 67.63 |
Surplus Electricity Going To Utility | 16.903 | 4.96 |
Net Electricity From Utility | 213.526 | 62.67 |
Total On-Site and Utility Electric Sources | 340.695 | 100.00 |
Total Electricity End Uses | 340.695 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 38.00 |
Time Setpoint Not Met During Occupied Cooling | 20.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3041.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 68.38 |
Skylight-Roof Ratio [%] | 1.49 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.1633 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.1969 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.1633 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.1969 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.3473 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-JUL-14:50 | 12-FEB-06:10 | - | - | - | - | - | - | - | - | - | - | 27-JUL-11:00 |
Heating | 0.00 | 213741.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12850.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4123.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4405.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1703.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 33118.48 | 213741.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 213741.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 12850.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 4123.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2100.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1703.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 188.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 101.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 239.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 133.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 94.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 77.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1078.98 | 188.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 38.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 223.15 | 38.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 38.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 223.15 | 38.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.06 |
ZONE2 FINE STORAGE DIRECT AIR | 2.54 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 3.26 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 3.26 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 128684.64 |
PSZ-OFFICE HEATING COIL | 26625.85 |
PSZ-FINE STORAGE HEATING COIL | 83323.61 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 128684.65 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-FINE STORAGE | 2.54 | 2.54 | 2.54 | 2.54 | 2.54 | 2.54 | 1.00 | 1.00 | 2.54 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.06 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.54 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.06 | 1169.97 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.54 | 2720.02 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.697442 | 20873.07 | 26625.85 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.54 | 2.54 | 2.54 | 1.68 | 63122.95 | 83323.61 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.06 | 0.528365 | 0.704487 | 20873.07 | 10436.53 | 0.781110 | 0.781110 |
PSZ-FINE STORAGE COOLING COIL | 2.54 | 1.27 | 1.69 | 63122.95 | 31561.47 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.163 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 14.237 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.197 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.756 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1459.960 | 6.163 | 114.518 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1459.960 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10245.499 | 3.197 | 148.485 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10245.499 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.5892 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.044 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 1.134 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.697 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4892 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7826 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.53319589E-11 | 0.95168195E-16 | 0.18684196E-15 | 0.0000000 |
5 | 1 | -5.2159738 | 0.43009049E-04 | -0.27188221E-04 | 0.68723469E-11 |
6 | 0 | 5.8052090 | 0.58919217 | 0.58926237 | |
7 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
8 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
9 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
10 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
11 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
12 | 4 | 0.65556131E-12 | 0.57298371E-15 | -0.14028959E-14 | 0.12439065E-15 |
13 | 3 | -0.34087882E-03 | 0.75102955E-06 | -0.49042705E-04 | 0.12583838E-12 |
14 | 2 | 1.6337693 | 0.17263784E-01 | 1.0601096 | -0.65347397E-04 |
15 | 1 | -7.2734424 | 0.46143774 | -16.581274 | 0.31301327 |
16 | 0 | 6.4190060 | 0.30028979 | 16.300205 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.0441747 | 2.0441747 | 2.0441747 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.14028959E-14 | 0.57298371E-15 | 0.65556131E-12 | 0.12439065E-15 |
85 | 3 | -0.49042705E-04 | 0.75102955E-06 | -0.34087882E-03 | 0.12583838E-12 |
86 | 2 | 1.0601096 | 0.17263784E-01 | 1.6337693 | -0.65347397E-04 |
87 | 1 | -16.581274 | 0.46143774 | -7.2734424 | 0.31301327 |
88 | 0 | 16.300205 | 0.30028979 | 6.4190060 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.423_SHGC_SOUTH_0.249 | 34 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
2 | NONRESWINDOW_U_0.423_SHGC_NORTH_0.249 | 35 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
3 | NONRESWINDOW_U_0.423_SHGC_EAST_0.249 | 36 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
4 | NONRESWINDOW_U_0.423_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.250 | ||
5 | SKYLIGHT_U_0.55_SHGC_0.3 | 38 | 1 | VerySmooth | 3.127 | 3.127 | 1.000 | 0.301 | ||
6 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | 39 | 1 | VerySmooth | 5.108 | 5.108 | 1.000 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.99333E-002 | 0.16038 | 0.62145 | 0.62145 | 0.24900 | 0.16165 | 0.23931 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 1.15759E-002 | 0.21195 | 0.55558 | 0.55558 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 7.71143E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.12500 | 0.12500 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.043 | 0.303 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.867 | 0.549 | 0.401 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.4325E-005 |
2 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.1213E-004 |
3 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.5495E-005 |
4 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.1648E-004 |
5 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.3186E-005 |
6 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.5731E-004 |
7 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.5724E-005 |
8 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.5867E-004 |
9 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5663E-004 |
10 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4272E-004 |
11 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3174E-004 |
12 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5473E-004 |
13 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4083E-004 |
14 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4773E-004 |
15 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3414E-004 |
16 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4540E-004 |
17 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5176E-004 |
18 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1794E-004 |
19 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.9295E-004 |
20 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2353E-004 |
21 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.0865E-004 |
22 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0883E-004 |
23 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.8792E-004 |
24 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6675E-005 |
25 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3526E-004 |
26 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4381E-005 |
27 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6465E-004 |
28 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6793E-005 |
29 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2366E-004 |
30 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.0015E-005 |
31 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3392E-003 |
32 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0724E-005 |
33 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7428E-004 |
34 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8883E-005 |
35 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.6923E-004 |
36 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0102E-005 |
37 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.7403E-004 |
38 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8144E-005 |
39 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9718E-004 |
40 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6272E-005 |
41 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8825E-004 |
42 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.2827E-005 |
43 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0139E-004 |
44 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.3587E-005 |
45 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0670E-004 |
46 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.3977E-005 |
47 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7955E-004 |
48 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4789E-005 |
49 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0144E-003 |
50 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4512E-005 |
51 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2157E-003 |
52 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.5656E-005 |
53 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3464E-004 |
54 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4522E-005 |
55 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3679E-004 |
56 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.4861E-005 |
57 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4549E-003 |
58 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3806E-005 |
59 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8584E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6167E-005 |
61 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.1741E-003 |
62 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.9847E-005 |
63 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1133E-003 |
64 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6508E-005 |
65 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8407E-003 |
66 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.1768E-005 |
67 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7846E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.8307E-005 |
69 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.5420E-003 |
70 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6526E-005 |
71 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5808E-003 |
72 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1684E-005 |
73 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9400E-004 |
74 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9667E-004 |
75 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.9896E-004 |
76 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.2158E-004 |
77 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.4345E-004 |
78 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.4107E-004 |
79 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6286E-003 |
80 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1734E-005 |
81 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9610E-004 |
82 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2370E-004 |
83 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6358E-004 |
84 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.5918E-004 |
85 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8910E-004 |
86 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.6135E-004 |
87 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3102E-004 |
88 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.8162E-004 |
89 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.1428E-005 |
90 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.2914E-003 |
91 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.1141E-005 |
92 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7177E-003 |
93 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0431E-005 |
94 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7903E-003 |
95 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0760E-004 |
96 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8446E-004 |
97 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2604E-005 |
98 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1438E-003 |
99 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.9150E-005 |
100 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.1840E-003 |
101 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8780E-005 |
102 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.7960E-003 |
103 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7398E-005 |
104 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.1825E-003 |
105 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1072E-005 |
106 | Clear Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.6508E-004 |
107 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7928E-005 |
108 | Clear Turbid Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.0513E-004 |
109 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.7373E-005 |
110 | Intermediate Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 9.7890E-004 |
111 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5431E-005 |
112 | Overcast Sky | 01/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2422E-003 |
113 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3309E-005 |
114 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8674E-005 |
115 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8869E-005 |
116 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.0497E-005 |
117 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6348E-005 |
118 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7121E-005 |
119 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6539E-005 |
122 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8575E-005 |
123 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8763E-005 |
124 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.3236E-005 |
125 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4714E-005 |
126 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2714E-005 |
127 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2212E-005 |
130 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9843E-005 |
131 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8490E-005 |
132 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9024E-005 |
133 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8739E-005 |
134 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9859E-005 |
135 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4228E-004 |
138 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5807E-004 |
139 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5457E-004 |
140 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7930E-004 |
141 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1930E-004 |
142 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0816E-004 |
143 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2331E-005 |
146 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1121E-004 |
147 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2105E-005 |
148 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4112E-004 |
149 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2602E-005 |
150 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4660E-004 |
151 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0086E-004 |
154 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6683E-005 |
155 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1025E-004 |
156 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6983E-005 |
157 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7851E-005 |
158 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5353E-005 |
159 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2892E-004 |
162 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3113E-005 |
163 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6584E-004 |
164 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6220E-005 |
165 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4367E-004 |
166 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.4378E-005 |
167 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0238E-005 |
170 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5351E-004 |
171 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7595E-005 |
172 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6957E-004 |
173 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0110E-004 |
174 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.5535E-004 |
175 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2489E-004 |
178 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1405E-004 |
179 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5478E-004 |
180 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5757E-004 |
181 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0915E-004 |
182 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3942E-004 |
183 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3630E-004 |
186 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.0566E-005 |
187 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.8531E-004 |
188 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3016E-005 |
189 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3550E-004 |
190 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5602E-005 |
191 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5596E-004 |
194 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9340E-005 |
195 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6858E-004 |
196 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9157E-005 |
197 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3580E-004 |
198 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8889E-005 |
199 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4663E-003 |
202 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3312E-005 |
203 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7208E-003 |
204 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.2451E-005 |
205 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1998E-003 |
206 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0005E-004 |
207 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9800E-004 |
210 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8668E-004 |
211 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.3888E-004 |
212 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3137E-004 |
213 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3364E-004 |
214 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.9640E-004 |
215 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0528E-004 |
218 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0802E-005 |
219 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1177E-004 |
220 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9925E-005 |
221 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2288E-004 |
222 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.1753E-005 |
223 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2524E-004 |
226 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7247E-003 |
227 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1639E-004 |
228 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.0155E-003 |
229 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5954E-004 |
230 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4783E-003 |
231 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0242E-004 |
234 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0338E-005 |
235 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9289E-004 |
236 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8860E-005 |
237 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6660E-004 |
238 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2279E-005 |
239 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3570E-003 |
242 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1841E-005 |
243 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4018E-003 |
244 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6561E-005 |
245 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7482E-003 |
246 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0918E-004 |
247 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2207E-004 |
250 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7729E-004 |
251 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7749E-004 |
252 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.6903E-004 |
253 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3175E-003 |
254 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5698E-004 |
255 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4446E-004 |
258 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9082E-003 |
259 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2762E-004 |
260 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.9705E-003 |
261 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9198E-004 |
262 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4426E-003 |
263 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4832E-004 |
266 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8107E-005 |
267 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3202E-004 |
268 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6413E-005 |
269 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9890E-004 |
270 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9907E-005 |
271 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2753E-004 |
274 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.5921E-004 |
275 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0868E-004 |
276 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4300E-004 |
277 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4980E-004 |
278 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1369E-003 |
279 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.4154E-004 |
282 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.6719E-005 |
283 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6187E-004 |
284 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9776E-005 |
285 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0914E-004 |
286 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.1202E-005 |
287 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.6693E-004 |
290 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9477E-004 |
291 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8000E-004 |
292 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5987E-004 |
293 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.4402E-004 |
294 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2754E-004 |
295 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1106E-005 |
298 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8798E-004 |
299 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.6916E-005 |
300 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.3438E-004 |
301 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6992E-005 |
302 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1223E-004 |
303 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3850E-004 |
306 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4819E-004 |
307 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9331E-004 |
308 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2543E-004 |
309 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4426E-004 |
310 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7640E-004 |
311 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5650E-005 |
314 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6214E-005 |
315 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.8399E-005 |
316 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3943E-005 |
317 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.6366E-005 |
318 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4589E-005 |
319 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3276E-005 |
322 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5060E-005 |
323 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1151E-005 |
324 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3532E-005 |
325 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0737E-004 |
326 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6007E-005 |
327 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0827E-005 |
330 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1377E-004 |
331 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2447E-005 |
332 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.3246E-005 |
333 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1131E-005 |
334 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 9.7708E-005 |
335 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0439E-004 |
338 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8079E-005 |
339 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5629E-005 |
340 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6788E-005 |
341 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6014E-005 |
342 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.4498E-005 |
343 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9474E-005 |
346 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2148E-005 |
347 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2473E-005 |
348 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0968E-005 |
349 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8113E-005 |
350 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2392E-005 |
351 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3989E-004 |
354 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.8568E-005 |
355 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9804E-004 |
356 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2864E-005 |
357 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7812E-004 |
358 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3583E-005 |
359 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0248E-004 |
362 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4769E-005 |
363 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5152E-005 |
364 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0984E-005 |
365 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2826E-005 |
366 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4316E-005 |
367 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
369 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9761E-003 |
370 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.7233E-004 |
371 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5435E-003 |
372 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.2449E-004 |
373 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.4877E-003 |
374 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1641E-004 |
375 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.7866E-003 |
376 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.1636E-004 |
377 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.7250E-004 |
378 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.5144E-003 |
379 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.3078E-004 |
380 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.8592E-003 |
381 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.2270E-004 |
382 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.6484E-003 |
383 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1270E-004 |
384 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.3974E-003 |
385 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.9162E-003 |
386 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.1886E-004 |
387 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2200E-003 |
388 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.7388E-004 |
389 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.6241E-003 |
390 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.3437E-004 |
391 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2429E-003 |
392 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.9254E-004 |
393 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.1056E-003 |
394 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1963E-004 |
395 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.3004E-003 |
396 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.7427E-004 |
397 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.3696E-003 |
398 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.3393E-004 |
399 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2428E-003 |
400 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.9254E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 10318.83892 | 12382.60670 | 0.88061 | 1.05673 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.19667 | 1.44711E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10022.78212 | 12027.33854 | 0.29176 | 0.35011 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30000 | 2.29779E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 31840.05287 | 38208.06344 | 2.11830 | 2.54196 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 34.21000 | 1.44729E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 31254.63185 | 37505.55822 | 0.76643 | 0.91971 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -6.30000 | 2.29779E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 107237.20599 | 128684.64718 | 2.71747 | 3.26096 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15785.84 | 1.05673 | 1.05673 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 11003.84 | 0.35011 | 0.35011 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 47320.59 | 2.54196 | 2.54196 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 37057.68 | 0.91971 | 0.91971 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05673 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.54196 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.26096 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 3.26096 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 128684.64118 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 128684.64718 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05673 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05673 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05673 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05673 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05673 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.05673 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.54196 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.54196 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.54196 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.54196 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.54196 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.54196 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.05673 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.54196 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05673 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05673 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1169.96763 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05673 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05673 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05673 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69744 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05673 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52836 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70449 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20873.07000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10436.53500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78111 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78111 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20873.07000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26625.85055 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26625.85055 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.54196 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.54196 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2720.01872 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.54196 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.54196 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.54196 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.67769 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.54196 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.27098 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.69464 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 63122.95000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 31561.47500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 63122.95000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 83323.60859 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 83323.60859 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 20052.5 | 12.76 | 12.47 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 61147.1 | 13.08 | 12.79 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 8.6583835207E-002 | 0.1420123616 | Pass | Pass | 2.9954442140E-002 | 0.1591536054 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.2282720282 | 0.2411746075 | Pass | Pass | 1.4819444635 | 3.9667008433 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 3.7740709450E-002 | 4.0220763644E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 9782.45 | 474.46 | 0.00 | 21.85 | 212.67 | 10491.46 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.969 | 1.134 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.545 | 0.589 | 3204.84 | 3157.28 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.892 | 1.134 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.423_SHGC_WEST_0.249 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.404 | 0.250 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.423_SHGC_WEST_0.249 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.404 | 0.250 | 0.250 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.423_SHGC_NORTH_0.249 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.404 | 0.250 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.423_SHGC_NORTH_0.249 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.404 | 0.250 | 0.250 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.55_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.127 | 0.301 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.043 | 0.303 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_0.9_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.551 | 0.401 | 0.000 | 0.000 | CurtainWall | 4.867 | 0.549 | 0.401 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 86.04 | 4.074 | 0.429 | 0.370 | |||||||||||||||||
North Total or Average | 6.51 | 2.404 | 0.250 | 0.250 | |||||||||||||||||
Non-North Total or Average | 79.53 | 4.210 | 0.443 | 0.380 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.1633 | 236.88 | 1459.96 | LightsWired | LTG_SCH_OFFICE | 44.65 | 168.00 | 29.48 | 0.0000 | Y | 8.08 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 19.08 | 0.0000 | Y | 33.36 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.1969 | 3204.84 | 10245.50 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 17.74 | 0.0000 | Y | 34.12 |
Interior Lighting Total | 4.3473 | 4835.13 | 21019.54 | 75.56 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 9314.08 | 2328.52 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 9314.08 | 2328.52 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10245.50 | 2561.37 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10245.50 | 2561.37 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1459.96 | 423.39 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1459.96 | 146.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 119.03 | AstronomicalClock | - | 41.77 | 41.77 | 0.93 | |
EXTERIOR_LIGHTS_B | 2955.82 | AstronomicalClock | - | 83.77 | 62.77 | 34.83 | |
EXTERIOR_LIGHTS_C | 694.12 | AstronomicalClock | - | 83.77 | 49.33 | 6.43 | |
Exterior Lighting Total | 3768.97 | 42.19 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20873.07 | 16304.16 | 4568.91 | 0.78 | 4.18 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 63122.95 | 44254.24 | 18868.71 | 0.70 | 4.11 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 20052.5 | 12.76 | 12.47 | ||||
PSZ-FINE STORAGE COOLING COIL | 61147.1 | 13.08 | 12.79 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 128684.64 | 0.85 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26625.85 | 0.84 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 83323.61 | 0.85 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.26 | 302.98 | 92.91 | 1.00 | 3.32 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1169.97 | 1107.16 | 1.00 | 1.39 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.54 | 2720.02 | 1070.05 | 1.00 | 1.28 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10318.84 | 12382.61 | 52.27 | 0.881 | 1.057 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 23.90 | 23.90 | 0.00854 | 33.20 | 0.01447 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 31840.05 | 38208.06 | 27.42 | 2.118 | 2.542 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 26.70 | 26.70 | 0.00905 | 34.21 | 0.01447 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 34.69 | 0.01455 | 34.30 | 0.01447 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10022.78 | 12027.34 | 50.77 | 0.292 | 0.350 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00734 | -6.30 | 0.00230 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 31254.63 | 37505.56 | 26.92 | 0.766 | 0.920 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00597 | -6.30 | 0.00230 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 107237.21 | 128684.65 | 40.15 | 2.717 | 3.261 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00524 | -6.30 | 0.00230 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.06 | 1.06 | 0.35 | 0.35 | 1.0567 | 1.0567 | 1.0567 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.54 | 2.54 | 0.92 | 0.92 | 2.5420 | 2.5420 | 2.5420 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 128684.641 | 128684.641 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 128684.64 | 128684.64 | 3.260963 | 10.00 | 7.03 | 0.00524485 | 43.33 | 21.72 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 10.00 | 0.00524485 | 66.5297 | 128684.65 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 20873.070 | 16304.164 | 1.056730 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 10436.53 | 8854.11 | 0.704487 | 25.74 | 17.13 | 0.00911499 | 12.00 | 10.94 | 0.00800000 | 33.32 | 0.01447128 | 23.26 | 14.5190 | 23.90 | 0.00854069 | 44.5959 | 10314.12 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26625.851 | 26625.851 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26625.85 | 26625.85 | 1.056730 | 18.40 | 12.42 | 0.00685406 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 9.6794 | 21.10 | 0.00734234 | 45.5375 | 10022.78 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 63122.950 | 44254.238 | 2.541960 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 31561.47 | 25000.34 | 1.694640 | 28.87 | 18.82 | 0.00996097 | 12.00 | 10.94 | 0.00800000 | 34.30 | 0.01447309 | 23.52 | 25.0620 | 26.70 | 0.00905507 | 39.9987 | 31816.86 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 83323.609 | 83323.609 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 83323.61 | 83323.61 | 2.541961 | 11.90 | 8.05 | 0.00535683 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 16.7080 | 15.55 | 0.00597046 | 52.5527 | 31254.63 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 128684.641 | 128684.641 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 3.260963 | 3.78590128 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 128684.64 | 128684.64 | 1.0000 | 3.78590128 | 3.260963 | 10.00 | 7.03 | 0.00524485 | 23259.5 | 43.33 | 21.72 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 128684.64 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 10.00 | 0.00524485 | 10.00 | 0.00524485 | 66.5297 | 128684.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20873.070 | 16304.164 | 1.056730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7843 | 1004.8586 | 1.1610 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.056730 | 1.22683851 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | Sensible | 10436.53 | 8854.11 | 1.0000 | 0.81789249 | 0.704487 | 25.74 | 17.13 | 0.00911499 | 49100.9 | 12.00 | 10.94 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10436.53 | 33.32 | 0.01447128 | 23.26 | 0.10228463 | 14.5190 | 23.90 | 0.00854069 | 23.90 | 0.00854069 | 44.5959 | 10314.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26625.851 | 26625.851 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.056730 | 1.22683851 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 26625.85 | 26625.85 | 1.0000 | 1.22683851 | 1.056730 | 18.40 | 12.42 | 0.00685406 | 35867.2 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26625.85 | -6.30 | 0.00229779 | -6.30 | 0.10228463 | 9.6794 | 21.05 | 0.00734234 | 21.10 | 0.00734234 | 45.5375 | 10022.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 63122.950 | 44254.238 | 2.541960 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3569 | 1004.8586 | 1.1610 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.541961 | 2.95115740 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 31561.47 | 25000.34 | 1.0000 | 1.96743728 | 1.694640 | 28.87 | 18.82 | 0.00996097 | 54455.4 | 12.00 | 10.94 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31561.47 | 34.30 | 0.01447309 | 23.52 | 0.42471127 | 25.0620 | 26.70 | 0.00905507 | 26.70 | 0.00905507 | 39.9987 | 31816.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 83323.609 | 83323.609 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.541961 | 2.95115740 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 83323.61 | 83323.61 | 1.0000 | 2.95115740 | 2.541961 | 11.90 | 8.05 | 0.00535683 | 25475.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 83323.61 | -6.30 | 0.00229779 | -6.30 | 0.42471127 | 16.7080 | 15.55 | 0.00597046 | 15.55 | 0.00597046 | 52.5527 | 31254.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialEnthalpy | 0.10 | 1.06 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialEnthalpy | 0.42 | 2.54 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2635.50 | 2152.17 | 1348.00 |
ZONE2 FINE STORAGE | 3102.67 | 3231.17 | 2757.50 |
ZONE3 BULK STORAGE | 3252.17 | 3335.33 | 3001.00 |
Facility | 3280.50 | 3472.83 | 3041.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 42.33 | 20.67 | 32.50 | 20.33 |
ZONE2 FINE STORAGE | 169.83 | 74.00 | 12.17 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 205.17 | 94.67 | 38.00 | 20.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.496 | 0.305 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.522 | 0.246 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.130 | 0.000 | 0.655 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.53 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1786779.94 | 0.00 | 1786779.94 | 1813741.60 | 3600521.54 | 3225648.14 | 5698.76 | 2509.67 | 551.58 | 0.26 |
ZONE2 FINE STORAGE | 5500092.90 | 0.00 | 5500092.90 | 6743274.88 | 12243367.78 | 13393694.68 | 5721.19 | 2707.81 | 331.01 | 2.48 |
ZONE3 BULK STORAGE | 0.00 | 0.13E+09 | 0.13E+09 | 33321292.93 | 0.16E+09 | 30805497.77 | 7430.02 | 36.50 | 1293.48 | 4988.11 |
Total Facility | 7286872.83 | 0.13E+09 | 0.14E+09 | 41878309.41 | 0.18E+09 | 47424840.58 | 7964.72 | 3002.17 | 2100.19 | 4988.20 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1365 | 0.0000 | 0.1365 | 0.0843 | 0.2208 | 0.1023 | 575.02 | 2509.67 | 551.31 |
ZONE2 FINE STORAGE | 0.4193 | 0.0000 | 0.4193 | 0.1991 | 0.6184 | 0.4247 | 599.67 | 2707.81 | 328.53 |
ZONE3 BULK STORAGE | 0.0000 | 6.0899 | 6.0899 | 1.2609 | 7.3508 | 0.9768 | 2821.76 | 18.75 | 795.49 |
Total Facility | 0.5558 | 6.0899 | 6.6457 | 1.5443 | 8.1900 | 1.5038 | 2840.72 | 2984.42 | 1599.72 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2408283.00 | 0.00 | 2408283.00 | 3225648.14 | 5697.09 | 0.17 | 3062.74 | 0.26 |
PSZ-FINE STORAGE | 7413368.85 | 0.00 | 7413368.85 | 13393694.68 | 5718.19 | 0.19 | 3041.62 | 2.48 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1839 | 0.0000 | 0.1839 | 0.1023 | 573.35 | 0.17 | 3062.48 |
PSZ-FINE STORAGE | 0.5652 | 0.0000 | 0.5652 | 0.4247 | 596.67 | 0.19 | 3039.14 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2835.05 | 234.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2936.98 | 117.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2035 | 0.3938 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6599 | 1.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 451 |
Defaulted Fields | 395 |
Fields with Defaults | 1183 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 340.70 | 1525.96 | 01-JAN-10:50 | 33118.48 | 08-JUL-14:50 |
Electricity:Building | 219.61 | 1044.96 | 01-JAN-10:50 | 18700.88 | 07-JUL-08:10 |
Electricity:Zone:ZONE1 OFFICE | 37.25 | 520.87 | 01-JAN-00:10 | 2597.78 | 30-OCT-07:10 |
Electricity:SpaceType:GENERAL | 212.07 | 1044.96 | 01-JAN-10:50 | 17898.19 | 30-OCT-08:10 |
InteriorLights:Electricity | 75.56 | 554.51 | 31-JUL-17:20 | 7863.02 | 30-OCT-08:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 8.08 | 51.00 | 01-JAN-00:10 | 762.73 | 30-OCT-07:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 75.56 | 554.51 | 31-JUL-17:20 | 7863.02 | 30-OCT-08:10 |
LightsWired:InteriorLights:Electricity | 75.56 | 554.51 | 31-JUL-17:20 | 7863.02 | 30-OCT-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 8.08 | 51.00 | 01-JAN-00:10 | 762.73 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 75.56 | 554.51 | 31-JUL-17:20 | 7863.02 | 30-OCT-08:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 33.36 | 257.13 | 16-JUN-17:10 | 3408.31 | 30-OCT-08:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 33.36 | 257.13 | 16-JUN-17:10 | 3408.31 | 30-OCT-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 33.36 | 257.13 | 16-JUN-17:10 | 3408.31 | 30-OCT-08:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 149.00 | 224.12 | 01-JAN-10:50 | 13142.74 | 07-JUL-08:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 34.12 | 224.12 | 01-JAN-10:50 | 3697.23 | 30-OCT-08:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 34.12 | 224.12 | 01-JAN-10:50 | 3697.23 | 30-OCT-08:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 29.87 | 0.00 | 01-JAN-01:20 | 4519.34 | 07-JUL-16:00 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 7.54 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-MAY-13:00 |
Ventilation (simple):Fans:Electricity | 7.54 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-MAY-13:00 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 7.54 | 0.00 | 01-JAN-00:10 | 2305.29 | 18-MAY-13:00 |
ElectricityProduced:Facility | 127.17 | -0.00 | 01-FEB-08:10 | 21267.01 | 06-APR-12:40 |
ElectricityProduced:Plant | 127.17 | -0.00 | 01-FEB-08:10 | 21267.01 | 06-APR-12:40 |
Photovoltaic:ElectricityProduced | 132.84 | 0.00 | 01-JAN-00:10 | 22148.55 | 06-APR-12:40 |
PowerConversion:ElectricityProduced | -5.67 | -881.54 | 06-APR-12:40 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 24.52 | 481.00 | 02-JAN-06:30 | 2120.88 | 31-JAN-12:30 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 230.43 | 0.00 | 01-JAN-09:20 | 25597.80 | 07-AUG-16:00 |
ElectricityPurchased:Plant | 230.43 | 0.00 | 01-JAN-09:20 | 25597.80 | 07-AUG-16:00 |
Cogeneration:ElectricityPurchased | 230.43 | 0.00 | 01-JAN-09:20 | 25597.80 | 07-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 230.43 | 0.00 | 01-JAN-09:20 | 25597.80 | 07-AUG-16:00 |
ElectricitySurplusSold:Facility | 16.90 | 0.00 | 01-JAN-00:10 | 18802.31 | 09-APR-12:30 |
ElectricitySurplusSold:Plant | 16.90 | 0.00 | 01-JAN-00:10 | 18802.31 | 09-APR-12:30 |
Cogeneration:ElectricitySurplusSold | 16.90 | 0.00 | 01-JAN-00:10 | 18802.31 | 09-APR-12:30 |
General:Cogeneration:ElectricitySurplusSold | 16.90 | 0.00 | 01-JAN-00:10 | 18802.31 | 09-APR-12:30 |
ElectricityNet:Facility | 213.53 | -18802.31 | 09-APR-12:30 | 25597.80 | 07-AUG-16:00 |
ElectricityNet:Plant | 213.53 | -18802.31 | 09-APR-12:30 | 25597.80 | 07-AUG-16:00 |
Cogeneration:ElectricityNet | 213.53 | -18802.31 | 09-APR-12:30 | 25597.80 | 07-AUG-16:00 |
General:Cogeneration:ElectricityNet | 213.53 | -18802.31 | 09-APR-12:30 | 25597.80 | 07-AUG-16:00 |
Electricity:HVAC | 54.38 | 0.00 | 01-JAN-01:20 | 15377.79 | 08-JUL-15:10 |
General:Fans:Electricity | 22.33 | 0.00 | 01-JAN-01:20 | 2931.69 | 13-FEB-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 32.05 | 0.00 | 01-JAN-00:10 | 13197.99 | 08-JUL-15:10 |
General:Cooling:Electricity | 32.05 | 0.00 | 01-JAN-00:10 | 13197.99 | 08-JUL-15:10 |
ExteriorLights:Electricity | 42.19 | 0.00 | 01-JAN-07:50 | 3768.97 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 42.19 | 0.00 | 01-JAN-07:50 | 3768.97 | 01-JAN-06:10 |
WaterSystems:Electricity | 24.52 | 481.00 | 02-JAN-06:30 | 2120.88 | 31-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 24.52 | 481.00 | 02-JAN-06:30 | 2120.88 | 31-JAN-12:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 173.82 | 0.00 | 01-JAN-01:20 | 213741.31 | 12-FEB-06:10 |
NaturalGas:HVAC | 173.82 | 0.00 | 01-JAN-01:20 | 213741.31 | 12-FEB-06:10 |
Heating:NaturalGas | 173.82 | 0.00 | 01-JAN-01:20 | 213741.31 | 12-FEB-06:10 |
General:Heating:NaturalGas | 173.82 | 0.00 | 01-JAN-01:20 | 213741.31 | 12-FEB-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 27-JUL-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 516.68 | 0.00 | 01-JAN-01:20 | 357609.10 | 12-FEB-06:10 |
EnergyTransfer:Building | 235.99 | 0.00 | 01-JAN-01:20 | 179288.94 | 12-FEB-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 50.02 | 0.00 | 01-JAN-00:10 | 20170.41 | 13-FEB-06:10 |
Heating:EnergyTransfer | 132.34 | 0.00 | 01-JAN-01:20 | 179288.94 | 12-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 15.85 | 0.00 | 01-JAN-00:10 | 20170.41 | 13-FEB-06:10 |
General:Heating:EnergyTransfer | 132.34 | 0.00 | 01-JAN-01:20 | 179288.94 | 12-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 15.85 | 0.00 | 01-JAN-00:10 | 20170.41 | 13-FEB-06:10 |
Cooling:EnergyTransfer | 103.65 | 0.00 | 01-JAN-00:10 | 33932.72 | 07-JUL-16:00 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 34.17 | 0.00 | 01-JAN-00:10 | 10065.78 | 17-JUL-05:10 |
General:Cooling:EnergyTransfer | 103.65 | 0.00 | 01-JAN-00:10 | 33932.72 | 07-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 34.17 | 0.00 | 01-JAN-00:10 | 10065.78 | 17-JUL-05:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 112.41 | 0.00 | 01-JAN-00:40 | 45332.22 | 12-FEB-06:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 42.92 | 0.00 | 01-JAN-00:40 | 45332.22 | 12-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 42.92 | 0.00 | 01-JAN-00:40 | 45332.22 | 12-FEB-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 69.48 | 0.00 | 01-JAN-00:10 | 25819.16 | 16-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 69.48 | 0.00 | 01-JAN-00:10 | 25819.16 | 16-JUL-14:40 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 73.56 | 0.00 | 01-JAN-00:10 | 129025.42 | 12-FEB-05:50 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 73.56 | 0.00 | 01-JAN-00:10 | 129025.42 | 12-FEB-05:50 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 73.56 | 0.00 | 01-JAN-00:10 | 129025.42 | 12-FEB-05:50 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 280.70 | 0.00 | 01-JAN-01:20 | 178320.16 | 12-FEB-06:10 |
HeatingCoils:EnergyTransfer | 136.95 | 0.00 | 01-JAN-01:20 | 178320.16 | 12-FEB-06:10 |
CoolingCoils:EnergyTransfer | 143.75 | 0.00 | 01-JAN-00:10 | 54487.33 | 03-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 15.855 | -34.165 | 0.000 | 0.000 | 9.732 | 8.080 | 29.165 | 9.423 | 0.000 | 1.721 | 0.000 | 0.000 | -5.959 | 0.000 | -14.929 | -18.922 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 42.924 | -69.480 | 0.000 | 0.000 | 23.087 | 33.360 | 0.000 | 29.829 | 0.000 | 3.010 | 0.002 | 0.000 | -11.151 | 0.000 | -49.229 | -2.350 |
ZONE3 BULK STORAGE | 73.557 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 50.491 | 34.123 | 107.344 | 607.771 | 0.000 | 9.507 | 0.001 | 0.000 | -130.146 | 0.000 | -397.410 | -355.238 |
Total Facility | 73.557 | 0.000 | 58.778 | -103.645 | 0.000 | 0.000 | 83.309 | 75.564 | 136.508 | 647.024 | 0.000 | 14.238 | 0.004 | 0.000 | -147.256 | 0.000 | -461.569 | -376.510 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 15-SEP-05:02 | 0.00 | 0.00 | 0.00 | -21742.15 | 0.00 | 0.00 | 89.53 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 21743.56 | 0.00 | -435.21 | 0.00 | -257.24 | 0.00 |
ZONE2 FINE STORAGE | 11-JUN-14:23 | 0.00 | 0.00 | 0.00 | -53757.10 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 5580.92 | 0.00 | 1798.88 | 46077.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-JUL-16:33 | 0.00 | 0.00 | 0.00 | -61594.81 | 0.00 | 0.00 | 0.00 | 575.09 | 469.88 | 63996.92 | 0.00 | 984.47 | 8331.79 | 0.00 | 0.00 | 0.00 | -12763.34 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 13-FEB-06:11 | 0.00 | 0.00 | 27435.88 | 0.00 | 0.00 | 0.00 | 118.54 | 227.91 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -849.42 | 0.00 | -3129.70 | -24353.73 |
ZONE2 FINE STORAGE | 11-FEB-18:42 | 0.00 | 0.00 | 85590.07 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1360.75 | 0.00 | -15733.29 | -68796.01 |
ZONE3 BULK STORAGE | 12-FEB-05:47 | 129030.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43608.25 | 0.00 | -85414.96 | -455.55 |
Total Facility | 12-FEB-06:02 | 128994.63 | 0.00 | 89136.16 | 0.00 | 0.00 | 0.00 | 0.00 | 799.21 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -26883.64 | 0.00 | -106667.12 | -85849.13 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0567 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0567 | 0.0968 | 1.0000 | Not calculated | 0.1023 | 0.0968 | ||
PSZ-FINE STORAGE | 2.5420 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.5420 | 0.1671 | 1.0000 | Not calculated | 0.4247 | 0.1671 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.0567 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.0567 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0968 | ||
PSZ-FINE STORAGE | 2.5420 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.5420 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1671 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0567 | 1.0567 | 1.0567 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5420 | 2.5420 | 2.5420 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0567 | 1.0567 | 1.0567 | 1.0567 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.5420 | 2.5420 | 2.5420 | 2.5420 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0567 | 1.0567 | 1.0567 | No | 0.1023 | 0.2921 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5420 | 2.5420 | 2.5420 | No | 0.4247 | 0.4618 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.0567 | 1.0567 | 1.0567 | 1.0567 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.5420 | 2.5420 | 2.5420 | 2.5420 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 38.00 |
Number of hours cooling loads not met | 20.33 |
Number of hours not met | 58.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 173.82 | 213741.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 32.05 | 13197.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 75.56 | 7863.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 42.19 | 3768.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 7.54 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 22.33 | 2931.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 24.52 | 2120.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 340.70 |
Natural Gas | 0.00 | 173.82 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 514.52 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 132.84 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 15.63 |
Space Heating | 0.00 |
Space Cooling | 6.63 |
Fans (All) | 6.18 |
Service Water Heating | 5.07 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 70.46 |
Subtotal | 70.46 |
Natural Gas [MJ/m2] | |
Space Heating | 35.95 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 35.95 |
Subtotal | 35.95 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.69 |
Space Heating | 33.78 |
Space Cooling | 6.23 |
Fans (All) | 5.81 |
Service Water Heating | 4.76 |
Receptacle Equipment | 26.53 |
Miscellaneous | 8.20 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
LTG_SCH_OFFICE | 2328. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7397.00 | 1357.83 | 5.17 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 6492.83 | 2267.17 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5627.00 | 2380.67 | 752.33 | 0.00 | 0.00 |
Min | 5627.00 | 1357.83 | 0.00 | 0.00 | 0.00 |
Max | 7397.00 | 2380.67 | 752.33 | 0.00 | 0.00 |
Average | 6505.61 | 2001.89 | 252.50 | 0.00 | 0.00 |
Sum | 19516.83 | 6005.67 | 757.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 55628.50 | 27090.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 114514.17 | 51195.00 | 25483.83 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 114514.17 | 51195.00 | 25483.83 | 0.00 | 0.00 |
Average | 67723.22 | 26095.17 | 8494.61 | 0.00 | 0.00 |
Sum | 203169.67 | 78285.50 | 25483.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 6811.33 | 1948.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 5619.67 | 3140.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 5280.17 | 3288.17 | 191.67 | 0.00 | 0.00 |
Min | 5280.17 | 1948.67 | 0.00 | 0.00 | 0.00 |
Max | 6811.33 | 3288.17 | 191.67 | 0.00 | 0.00 |
Average | 5903.72 | 2792.39 | 63.89 | 0.00 | 0.00 |
Sum | 17711.17 | 8377.17 | 191.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32039.83 | 987.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 50156.00 | 32563.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 109669.83 | 72510.83 | 9012.33 | 0.00 | 0.00 |
Min | 32039.83 | 987.17 | 0.00 | 0.00 | 0.00 |
Max | 109669.83 | 72510.83 | 9012.33 | 0.00 | 0.00 |
Average | 63955.22 | 35353.67 | 3004.11 | 0.00 | 0.00 |
Sum | 191865.67 | 106061.00 | 9012.33 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3105455.83 | 427.85 | 28-JAN-16:00 | 12.20 | 4.56 | 0.498468E+09 | 671.36 | 31-JAN-15:50 | 20.18 | 13.49 |
February | 37684509.66 | 1460.90 | 28-FEB-16:40 | 23.70 | 12.80 | 0.469797E+09 | 768.96 | 28-FEB-16:10 | 23.70 | 12.80 |
March | 0.483841E+09 | 4273.56 | 30-MAR-16:00 | 27.80 | 17.47 | 0.594955E+09 | 769.01 | 30-MAR-14:00 | 27.80 | 17.47 |
April | 0.180828E+10 | 5843.59 | 17-APR-16:00 | 28.90 | 16.41 | 0.609073E+09 | 769.02 | 19-APR-12:00 | 25.00 | 17.82 |
May | 0.378566E+10 | 19250.98 | 20-MAY-05:02 | 17.38 | 14.91 | 0.657409E+09 | 769.03 | 23-MAY-13:00 | 22.80 | 20.55 |
June | 0.626626E+10 | 20888.40 | 07-JUN-05:02 | 13.80 | 12.13 | 0.660262E+09 | 769.06 | 05-JUN-15:39 | 13.80 | 12.13 |
July | 0.673827E+10 | 18727.55 | 03-JUL-05:01 | 17.88 | 16.41 | 0.635057E+09 | 769.06 | 03-JUL-15:30 | 29.40 | 21.81 |
August | 0.756276E+10 | 18702.31 | 26-AUG-05:01 | 21.70 | 17.15 | 0.685938E+09 | 769.05 | 07-AUG-09:00 | 21.70 | 17.15 |
September | 0.514513E+10 | 21744.51 | 15-SEP-05:02 | 14.90 | 12.38 | 0.634750E+09 | 769.06 | 08-SEP-15:09 | 14.90 | 12.38 |
October | 0.196020E+10 | 11461.83 | 19-OCT-05:03 | 20.92 | 20.92 | 0.604275E+09 | 769.03 | 19-OCT-15:30 | 24.15 | 18.51 |
November | 0.328534E+09 | 2637.24 | 06-NOV-16:00 | 20.60 | 10.48 | 0.526223E+09 | 768.98 | 03-NOV-13:50 | 20.60 | 10.48 |
December | 46565142.84 | 744.51 | 14-DEC-11:20 | 11.13 | 7.65 | 0.505476E+09 | 758.69 | 12-DEC-15:30 | 11.13 | 7.65 |
Annual Sum or Average | 0.341663E+11 | 0.708168E+10 | ||||||||
Minimum of Months | 3105455.83 | 427.85 | 11.13 | 4.56 | 0.469797E+09 | 671.36 | 11.13 | 7.65 | ||
Maximum of Months | 0.756276E+10 | 21744.51 | 28.90 | 20.92 | 0.685938E+09 | 769.06 | 29.40 | 21.81 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.995718E+09 | 5219.33 | 10-JAN-13:10 | 2.98 | 0.76 | 0.690442E+09 | 1230.99 | 31-JAN-15:20 | 20.73 | 13.19 |
February | 0.689744E+09 | 5059.66 | 02-FEB-14:00 | 2.80 | -1.2 | 0.722274E+09 | 1685.95 | 28-FEB-15:00 | 23.30 | 12.53 |
March | 0.144614E+10 | 5130.11 | 18-MAR-08:20 | 3.17 | -0.5 | 0.114192E+10 | 2213.15 | 30-MAR-15:00 | 27.80 | 17.47 |
April | 0.170769E+10 | 36172.41 | 16-APR-14:45 | 27.48 | 15.75 | 0.145157E+10 | 2246.86 | 17-APR-14:30 | 28.90 | 16.52 |
May | 0.456301E+10 | 41384.97 | 19-MAY-17:43 | 29.60 | 18.93 | 0.179483E+10 | 2246.94 | 20-MAY-15:39 | 27.60 | 18.98 |
June | 0.133906E+11 | 53756.89 | 11-JUN-14:23 | 31.65 | 20.47 | 0.191417E+10 | 2246.94 | 20-JUN-13:20 | 30.40 | 23.07 |
July | 0.170298E+11 | 52316.26 | 04-JUL-15:02 | 31.28 | 22.90 | 0.184690E+10 | 2247.01 | 07-JUL-13:39 | 34.23 | 23.84 |
August | 0.180164E+11 | 51890.45 | 27-AUG-15:53 | 31.70 | 21.48 | 0.200184E+10 | 2247.01 | 18-AUG-15:20 | 31.70 | 21.48 |
September | 0.720128E+10 | 47201.35 | 08-SEP-17:43 | 29.18 | 21.94 | 0.179556E+10 | 2246.95 | 06-SEP-15:30 | 29.18 | 21.94 |
October | 0.186861E+10 | 6677.53 | 11-OCT-15:00 | 27.20 | 20.13 | 0.140441E+10 | 2246.80 | 02-OCT-12:00 | 27.20 | 20.13 |
November | 0.133069E+10 | 5342.00 | 20-NOV-12:00 | 3.90 | 1.60 | 0.947339E+09 | 1815.77 | 06-NOV-15:39 | 3.90 | 1.60 |
December | 0.124466E+10 | 4706.52 | 01-DEC-10:50 | 3.95 | 0.75 | 0.767274E+09 | 1437.63 | 12-DEC-14:50 | 22.80 | 16.32 |
Annual Sum or Average | 0.694843E+11 | 0.164785E+11 | ||||||||
Minimum of Months | 0.689744E+09 | 4706.52 | 2.80 | -1.2 | 0.690442E+09 | 1230.99 | 3.90 | 1.60 | ||
Maximum of Months | 0.180164E+11 | 53756.89 | 31.70 | 22.90 | 0.200184E+10 | 2247.01 | 34.23 | 23.84 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.70 | 4.97 | 0.861651E+09 | 1995.33 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 | 0.109601E+10 | 3476.39 | 28-FEB-15:39 | 23.87 | 12.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.51 | 0.242339E+10 | 4623.19 | 30-MAR-15:39 | 27.80 | 17.34 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.82 | 0.343281E+10 | 6115.58 | 17-APR-15:20 | 28.90 | 16.41 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 | 0.463608E+10 | 6902.75 | 19-MAY-14:50 | 30.60 | 18.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 | 0.555458E+10 | 8315.24 | 06-JUN-15:20 | 34.23 | 22.26 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 | 0.555023E+10 | 9097.65 | 08-JUL-13:50 | 36.02 | 24.42 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 | 0.596990E+10 | 8659.98 | 18-AUG-15:00 | 35.00 | 23.11 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.46 | 0.479590E+10 | 7354.98 | 07-SEP-15:39 | 31.70 | 23.45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 | 0.319276E+10 | 5678.24 | 02-OCT-14:00 | 26.70 | 20.22 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.60 | 0.185800E+10 | 3667.63 | 06-NOV-15:20 | 20.60 | 10.48 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 | 1.51 | 0.113856E+10 | 2452.63 | 12-DEC-14:50 | 22.80 | 16.32 |
Annual Sum or Average | 0.00 | 0.405099E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.80 | 1.51 | 0.861651E+09 | 1995.33 | 20.37 | 10.48 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 21.87 | 0.596990E+10 | 9097.65 | 36.02 | 24.42 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.569114E+10 | 27329.37 | 09-JAN-06:12 | -2.6 |
February | 0.391793E+10 | 27435.85 | 13-FEB-06:11 | -5.6 |
March | 0.116067E+10 | 26926.32 | 07-MAR-06:01 | 5.50 |
April | 0.249021E+09 | 26922.76 | 07-APR-05:01 | 3.22 |
May | 29033232.58 | 834.08 | 11-MAY-06:30 | 8.90 |
June | 4777395.87 | 678.66 | 09-JUN-06:10 | 13.95 |
July | 248968.06 | 274.53 | 29-JUL-06:13 | 17.80 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 8356100.08 | 694.17 | 14-SEP-06:10 | 12.30 |
October | 0.231930E+09 | 26812.29 | 31-OCT-05:01 | 8.30 |
November | 0.126731E+10 | 27041.32 | 21-NOV-06:12 | -2.8 |
December | 0.329419E+10 | 27275.62 | 18-DEC-06:22 | -5.0 |
Annual Sum or Average | 0.158546E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 0.569114E+10 | 27435.85 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189336E+11 | 85367.01 | 07-JAN-05:22 | -0.9 |
February | 0.109128E+11 | 85588.95 | 11-FEB-18:42 | -5.9 |
March | 0.569957E+09 | 20745.30 | 23-MAR-00:30 | 5.00 |
April | 0.257582E+09 | 1748.65 | 12-APR-13:20 | 28.17 |
May | 96009005.87 | 1205.18 | 02-MAY-07:00 | 15.00 |
June | 60948445.10 | 1186.79 | 26-JUN-06:10 | 23.30 |
July | 25602534.36 | 1211.82 | 14-JUL-06:04 | 23.48 |
August | 21842900.81 | 1247.04 | 05-AUG-06:10 | 22.80 |
September | 80939017.88 | 1128.57 | 20-SEP-07:00 | 16.10 |
October | 0.125465E+09 | 1234.84 | 13-OCT-06:50 | 5.60 |
November | 0.182202E+10 | 83456.38 | 22-NOV-05:53 | -3.3 |
December | 0.100168E+11 | 83964.93 | 03-DEC-06:42 | -3.3 |
Annual Sum or Average | 0.429237E+11 | |||
Minimum of Months | 21842900.81 | 1128.57 | -5.9 | |
Maximum of Months | 0.189336E+11 | 85588.95 | 28.17 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.425400E+11 | 92326.93 | 07-JAN-18:57 | -5.6 |
February | 0.254520E+11 | 129031.61 | 12-FEB-05:47 | -12.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.556562E+10 | 40491.64 | 03-DEC-07:00 | -3.3 |
Annual Sum or Average | 0.735576E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.1 | |
Maximum of Months | 0.425400E+11 | 129031.61 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.709741E+09 | 753.80 | 03-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.638309E+09 | 760.09 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.711296E+09 | 754.81 | 21-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.656009E+09 | 746.73 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.658278E+09 | 720.01 | 24-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.646276E+09 | 713.44 | 23-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.636439E+09 | 729.11 | 29-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.677165E+09 | 741.87 | 24-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.665473E+09 | 752.79 | 30-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.696242E+09 | 762.73 | 30-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.671792E+09 | 761.67 | 04-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.713443E+09 | 754.03 | 06-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.808046E+10 | 0.291647E+11 | ||||
Minimum of Months | 0.636439E+09 | 713.44 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.713443E+09 | 762.73 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.311029E+10 | 3309.61 | 11-JAN-09:09 | 0.00 | 0.00 |
February | 0.277781E+10 | 3375.57 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.289577E+10 | 3282.35 | 18-MAR-08:09 | 0.00 | 0.00 |
April | 0.264840E+10 | 3205.48 | 08-APR-08:09 | 0.00 | 0.00 |
May | 0.257027E+10 | 3064.12 | 06-MAY-08:09 | 0.00 | 0.00 |
June | 0.251523E+10 | 3010.58 | 08-JUN-08:09 | 0.00 | 0.00 |
July | 0.249986E+10 | 3054.01 | 07-JUL-08:09 | 0.00 | 0.00 |
August | 0.263335E+10 | 3093.06 | 26-AUG-08:09 | 0.00 | 0.00 |
September | 0.271239E+10 | 3190.07 | 25-SEP-08:09 | 0.00 | 0.00 |
October | 0.299571E+10 | 3408.31 | 30-OCT-08:09 | 0.00 | 0.00 |
November | 0.292570E+10 | 3276.71 | 04-NOV-08:09 | 0.00 | 0.00 |
December | 0.307516E+10 | 3292.07 | 19-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.333599E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.249986E+10 | 3010.58 | 0.00 | 0.00 | |
Maximum of Months | 0.311029E+10 | 3408.31 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317325E+10 | 3397.39 | 11-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.287549E+10 | 3630.54 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.295151E+10 | 3290.46 | 18-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.266515E+10 | 3089.20 | 01-APR-07:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.264102E+10 | 2771.90 | 24-MAY-07:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.256804E+10 | 2639.52 | 08-JUN-07:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.256863E+10 | 2824.21 | 29-JUL-07:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.273650E+10 | 3010.45 | 24-AUG-07:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.272980E+10 | 3214.19 | 30-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.305478E+10 | 3697.23 | 30-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.294053E+10 | 3418.24 | 04-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.321867E+10 | 3406.46 | 04-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.341234E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.256804E+10 | 2639.52 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.321867E+10 | 3697.23 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.709741E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303381E+10 |
February | 0.127628E+10 | 0.638309E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5489625.17 | 0.234360E+10 |
March | 0.149825E+10 | 0.711296E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17023840.20 | 0.150229E+10 |
April | 0.138726E+10 | 0.656009E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59014331.74 | 0.990277E+09 |
May | 0.144276E+10 | 0.658278E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134610E+09 | 0.667096E+09 |
June | 0.144276E+10 | 0.646276E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429035E+09 | 0.336808E+09 |
July | 0.138726E+10 | 0.636439E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417563E+09 | 0.242313E+09 |
August | 0.149825E+10 | 0.677165E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466916E+09 | 0.175106E+09 |
September | 0.138726E+10 | 0.665473E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154986E+09 | 0.426640E+09 |
October | 0.138726E+10 | 0.696242E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31910354.18 | 0.125273E+10 |
November | 0.133177E+10 | 0.671792E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4297263.78 | 0.164346E+10 |
December | 0.138726E+10 | 0.713443E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231529E+10 |
Annual Sum or Average | 0.168137E+11 | 0.808046E+10 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172085E+10 | 0.149294E+11 |
Minimum of Months | 0.127628E+10 | 0.636439E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175106E+09 |
Maximum of Months | 0.149825E+10 | 0.713443E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466916E+09 | 0.303381E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.311029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19012503.33 | 0.956103E+10 |
February | 0.300332E+10 | 0.277781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61943489.47 | 0.736631E+10 |
March | 0.352563E+10 | 0.289577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83682771.07 | 0.424761E+10 |
April | 0.326447E+10 | 0.264840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60050644.36 | 0.345178E+10 |
May | 0.339505E+10 | 0.257027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107832E+09 | 0.277955E+10 |
June | 0.339505E+10 | 0.251523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776748E+09 | 0.169261E+10 |
July | 0.326447E+10 | 0.249986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820696E+09 | 0.123598E+10 |
August | 0.352563E+10 | 0.263335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824780E+09 | 0.939635E+09 |
September | 0.326447E+10 | 0.271239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151871E+09 | 0.185929E+10 |
October | 0.326447E+10 | 0.299571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16207673.89 | 0.422731E+10 |
November | 0.313390E+10 | 0.292570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76347980.51 | 0.450573E+10 |
December | 0.326447E+10 | 0.307516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10697442.88 | 0.736253E+10 |
Annual Sum or Average | 0.395654E+11 | 0.333599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300987E+10 | 0.492294E+11 |
Minimum of Months | 0.300332E+10 | 0.249986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10697442.88 | 0.939635E+09 |
Maximum of Months | 0.352563E+10 | 0.311029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824780E+09 | 0.956103E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.317325E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994696E+09 | 0.283103E+11 |
February | 0.690763E+10 | 0.287549E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131507E+10 | 0.217686E+11 |
March | 0.810895E+10 | 0.295151E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853136E+09 | 0.179694E+11 |
April | 0.750829E+10 | 0.266515E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311184E+09 | 0.171880E+11 |
May | 0.780862E+10 | 0.264102E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1073341.08 | 0.155700E+11 |
June | 0.780862E+10 | 0.256804E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23817391.99 | 0.117792E+11 |
July | 0.750829E+10 | 0.256863E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10264302.84 | 0.938047E+10 |
August | 0.810895E+10 | 0.273650E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14218015.40 | 0.825212E+10 |
September | 0.750829E+10 | 0.272980E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 207608.85 | 0.121035E+11 |
October | 0.750829E+10 | 0.305478E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68863697.82 | 0.197117E+11 |
November | 0.720796E+10 | 0.294053E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895883E+09 | 0.163850E+11 |
December | 0.750829E+10 | 0.321867E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786361E+09 | 0.190474E+11 |
Annual Sum or Average | 0.910005E+11 | 0.341234E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527478E+10 | 0.197466E+12 |
Minimum of Months | 0.690763E+10 | 0.256804E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 207608.85 | 0.825212E+10 |
Maximum of Months | 0.810895E+10 | 0.321867E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131507E+10 | 0.283103E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 753.80 | 03-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 8402.52 | 27-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 760.09 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 299.45 | 26-FEB-13:00 | 9483.24 | 13-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 754.81 | 21-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.98 | 30-MAR-16:10 | 5679.46 | 22-MAR-06:10 |
April | 1680.92 | 01-APR-07:10 | 746.73 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1119.24 | 17-APR-16:10 | 5694.57 | 06-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 720.01 | 24-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1787.22 | 19-MAY-16:10 | 3798.42 | 11-MAY-06:05 |
June | 1680.92 | 01-JUN-07:10 | 713.44 | 23-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3047.67 | 06-JUN-17:00 | 3080.53 | 08-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 729.11 | 29-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2720.98 | 07-JUL-16:10 | 1564.09 | 28-JUL-17:00 |
August | 1680.92 | 01-AUG-07:10 | 741.87 | 24-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3123.56 | 01-AUG-17:00 | 1420.31 | 25-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 752.79 | 30-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1894.44 | 08-SEP-16:10 | 3025.27 | 14-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 762.73 | 30-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1468.04 | 10-OCT-16:10 | 5332.37 | 26-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 761.67 | 04-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.56 | 19-NOV-15:00 | 7218.88 | 21-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 754.03 | 06-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7407.10 | 18-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 713.44 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1420.31 | |||||
Maximum of Months | 1680.92 | 762.73 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 3123.56 | 9483.24 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3309.61 | 11-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1159.17 | 19-JAN-23:00 | 17963.59 | 07-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 3375.57 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.96 | 26-FEB-13:00 | 20069.64 | 11-FEB-17:40 |
March | 3955.50 | 01-MAR-08:09 | 3282.35 | 18-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1333.06 | 11-MAR-16:10 | 9026.58 | 22-MAR-06:10 |
April | 3955.50 | 01-APR-07:10 | 3205.48 | 08-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1214.27 | 04-APR-17:00 | 8222.63 | 05-APR-15:15 |
May | 3955.50 | 01-MAY-07:10 | 3064.12 | 06-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1669.58 | 19-MAY-16:00 | 5959.71 | 10-MAY-08:00 |
June | 3955.50 | 01-JUN-07:10 | 3010.58 | 08-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4925.38 | 06-JUN-15:10 | 5739.69 | 07-JUN-07:00 |
July | 3955.50 | 01-JUL-07:10 | 3054.01 | 07-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2966.65 | 10-JUL-15:10 | 4351.18 | 28-JUL-17:00 |
August | 3955.50 | 01-AUG-07:10 | 3093.06 | 26-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4187.35 | 01-AUG-17:00 | 2497.73 | 28-AUG-07:00 |
September | 3955.50 | 01-SEP-07:10 | 3190.07 | 25-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.96 | 08-SEP-16:00 | 4148.26 | 28-SEP-17:00 |
October | 3955.50 | 02-OCT-07:10 | 3408.31 | 30-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 975.68 | 10-OCT-16:00 | 9595.44 | 25-OCT-08:00 |
November | 3955.50 | 01-NOV-07:10 | 3276.71 | 04-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2052.63 | 19-NOV-15:00 | 9381.42 | 20-NOV-09:00 |
December | 3955.50 | 01-DEC-08:09 | 3292.07 | 19-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.89 | 24-DEC-10:00 | 16024.65 | 02-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3010.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.89 | 2497.73 | ||||
Maximum of Months | 3955.50 | 3408.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4925.38 | 20069.64 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3397.39 | 11-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14723.90 | 19-JAN-16:00 | 60088.91 | 07-JAN-10:00 |
February | 9097.65 | 01-FEB-08:09 | 3630.54 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13604.27 | 16-FEB-17:00 | 59957.16 | 11-FEB-17:00 |
March | 9097.65 | 01-MAR-08:09 | 3290.46 | 18-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10102.64 | 11-MAR-16:00 | 37675.18 | 18-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 3089.20 | 01-APR-07:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5937.75 | 04-APR-15:00 | 49225.71 | 05-APR-11:00 |
May | 9097.65 | 01-MAY-07:10 | 2771.90 | 24-MAY-07:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.85 | 06-MAY-16:00 | 28002.79 | 10-MAY-08:00 |
June | 9097.65 | 01-JUN-07:10 | 2639.52 | 08-JUN-07:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1217.30 | 06-JUN-11:45 | 30121.58 | 30-JUN-15:55 |
July | 9097.65 | 01-JUL-07:10 | 2824.21 | 29-JUL-07:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 476.23 | 22-JUL-10:45 | 23096.35 | 28-JUL-14:00 |
August | 9097.65 | 01-AUG-07:10 | 3010.45 | 24-AUG-07:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1011.04 | 01-AUG-17:00 | 15167.48 | 31-AUG-09:00 |
September | 9097.65 | 01-SEP-07:10 | 3214.19 | 30-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.27 | 25-SEP-14:00 | 20344.62 | 28-SEP-14:00 |
October | 9097.65 | 02-OCT-07:10 | 3697.23 | 30-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2923.86 | 10-OCT-16:00 | 40671.64 | 25-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 3418.24 | 04-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12187.85 | 27-NOV-13:10 | 36364.26 | 20-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 3406.46 | 04-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9539.79 | 11-DEC-14:00 | 45994.27 | 02-DEC-08:70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2639.52 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 177.27 | 15167.48 | |||||
Maximum of Months | 9097.65 | 3697.23 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14723.90 | 60088.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 427.85 | 28-JAN-16:00 | 1680.92 | 607.74 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.31 |
February | 1460.90 | 28-FEB-16:40 | 1680.92 | 482.35 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 |
March | 4273.56 | 30-MAR-16:00 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 491.37 | 0.00 |
April | 5843.59 | 17-APR-16:00 | 1680.92 | 484.89 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 276.72 | 0.00 |
May | 19250.98 | 20-MAY-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20888.40 | 07-JUN-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 832.05 |
July | 18727.55 | 03-JUL-05:01 | 1479.21 | 407.96 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.80 |
August | 18702.31 | 26-AUG-05:01 | 1479.21 | 407.96 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.92 |
September | 21744.51 | 15-SEP-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.24 |
October | 11461.83 | 19-OCT-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.87 |
November | 2637.24 | 06-NOV-16:00 | 1680.92 | 497.88 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.30 |
December | 744.51 | 14-DEC-11:20 | 1680.92 | 654.53 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 427.85 | 739.61 | 203.98 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21744.51 | 1680.92 | 654.53 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 491.37 | 832.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5219.33 | 10-JAN-13:10 | 3955.50 | 2775.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.34 |
February | 5059.66 | 02-FEB-14:00 | 3955.50 | 2345.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3807.38 |
March | 5130.11 | 18-MAR-08:20 | 3955.50 | 3256.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3649.49 |
April | 36172.41 | 16-APR-14:45 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.76 | 0.00 |
May | 41384.97 | 19-MAY-17:43 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 912.62 | 0.00 |
June | 53756.89 | 11-JUN-14:23 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1798.88 | 0.00 |
July | 52316.26 | 04-JUL-15:02 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.49 | 0.00 |
August | 51890.45 | 27-AUG-15:53 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1206.22 | 0.00 |
September | 47201.35 | 08-SEP-17:43 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.88 | 0.00 |
October | 6677.53 | 11-OCT-15:00 | 3955.50 | 2616.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.16 | 0.00 |
November | 5342.00 | 20-NOV-12:00 | 3955.50 | 1973.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3844.99 |
December | 4706.52 | 01-DEC-10:50 | 3955.50 | 2740.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1703.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4706.52 | 0.00 | 599.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53756.89 | 3955.50 | 3256.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1798.88 | 3844.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1344.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6806.72 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5519.05 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4009.36 |
April | 0.00 | 01-APR-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8332.96 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4974.00 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5595.05 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5767.91 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2411.23 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6722.06 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9688.28 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9839.22 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1344.72 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21134.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2411.23 | |
Maximum of Months | 0.00 | 0.00 | 1344.72 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21134.36 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.276329E+11 | 21443.67 | 11-JAN-09:09 | 0.877672E+11 | 163199.08 | 07-JAN-17:00 |
February | 0.244674E+11 | 21727.33 | 01-FEB-09:09 | 0.524362E+11 | 213741.31 | 12-FEB-06:10 |
March | 0.263191E+11 | 20540.24 | 18-MAR-08:20 | 0.231701E+10 | 27065.56 | 22-MAR-05:10 |
April | 0.245153E+11 | 23136.65 | 17-APR-14:00 | 0.324555E+09 | 11952.65 | 06-APR-05:10 |
May | 0.267156E+11 | 27280.14 | 19-MAY-13:00 | 452992.72 | 387.50 | 11-MAY-06:30 |
June | 0.324384E+11 | 30515.97 | 06-JUN-15:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.347159E+11 | 33118.48 | 08-JUL-14:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.370785E+11 | 32686.40 | 03-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.285669E+11 | 30608.62 | 07-SEP-15:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.260142E+11 | 23476.20 | 10-OCT-15:50 | 0.331721E+09 | 10860.09 | 31-OCT-05:10 |
November | 0.251710E+11 | 20681.44 | 04-NOV-08:09 | 0.447085E+10 | 43156.24 | 22-NOV-06:10 |
December | 0.270600E+11 | 21069.10 | 18-DEC-08:09 | 0.261751E+11 | 85105.71 | 03-DEC-06:49 |
Annual Sum or Average | 0.340695E+12 | 0.173823E+12 | ||||
Minimum of Months | 0.244674E+11 | 20540.24 | 0.00 | 0.00 | ||
Maximum of Months | 0.370785E+11 | 33118.48 | 0.877672E+11 | 213741.31 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.679827E+10 | 15175.12 | 27-JAN-12:50 | 0.00 | 0.00 |
February | 0.733320E+10 | 17525.91 | 24-FEB-12:50 | 0.00 | 0.00 |
March | 0.111864E+11 | 20708.04 | 18-MAR-12:50 | 0.00 | 0.00 |
April | 0.130867E+11 | 21267.01 | 06-APR-12:39 | 0.00 | 0.00 |
May | 0.146741E+11 | 21248.15 | 10-MAY-12:20 | 0.00 | 0.00 |
June | 0.149525E+11 | 20776.89 | 10-JUN-12:30 | 0.00 | 0.00 |
July | 0.143291E+11 | 20042.64 | 24-JUL-12:30 | 0.00 | 0.00 |
August | 0.132416E+11 | 19239.95 | 02-AUG-12:30 | 0.00 | 0.00 |
September | 0.976622E+10 | 18356.95 | 14-SEP-12:30 | 0.00 | 0.00 |
October | 0.900891E+10 | 17674.46 | 25-OCT-12:30 | 0.00 | 0.00 |
November | 0.674725E+10 | 14394.07 | 07-NOV-12:30 | 0.00 | 0.00 |
December | 0.604533E+10 | 13475.67 | 02-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.127170E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.604533E+10 | 13475.67 | 0.00 | 0.00 | |
Maximum of Months | 0.149525E+11 | 21267.01 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.699328E+10 | 0.440939E+10 | 0.112984E+11 | 0.00 | 0.274796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218392E+10 | 0.00 |
February | 0.629161E+10 | 0.369103E+10 | 0.103734E+11 | 0.00 | 0.212058E+10 | 0.00 | 0.00 | 5381194.10 | 0.00 | 0.00 | 0.00 | 0.198537E+10 | 0.00 |
March | 0.655858E+10 | 0.366314E+10 | 0.121089E+11 | 0.00 | 0.171330E+10 | 0.00 | 0.00 | 64853863.73 | 0.00 | 0.00 | 0.00 | 0.221026E+10 | 0.00 |
April | 0.596956E+10 | 0.312363E+10 | 0.112578E+11 | 0.00 | 0.154906E+10 | 0.00 | 0.00 | 0.563344E+09 | 0.00 | 0.00 | 0.00 | 0.205191E+10 | 0.00 |
May | 0.586957E+10 | 0.287204E+10 | 0.117000E+11 | 0.00 | 0.192480E+10 | 0.00 | 0.00 | 0.228822E+10 | 0.00 | 0.00 | 0.00 | 0.206099E+10 | 0.00 |
June | 0.572955E+10 | 0.262826E+10 | 0.116594E+11 | 0.00 | 0.365594E+10 | 0.00 | 0.00 | 0.680851E+10 | 0.00 | 0.00 | 0.00 | 0.195684E+10 | 0.00 |
July | 0.570493E+10 | 0.277617E+10 | 0.112984E+11 | 0.00 | 0.438200E+10 | 0.00 | 0.00 | 0.860806E+10 | 0.00 | 0.00 | 0.00 | 0.194643E+10 | 0.00 |
August | 0.604701E+10 | 0.306893E+10 | 0.121016E+11 | 0.00 | 0.439098E+10 | 0.00 | 0.00 | 0.948262E+10 | 0.00 | 0.00 | 0.00 | 0.198745E+10 | 0.00 |
September | 0.610766E+10 | 0.336187E+10 | 0.112504E+11 | 0.00 | 0.216947E+10 | 0.00 | 0.00 | 0.374784E+10 | 0.00 | 0.00 | 0.00 | 0.192965E+10 | 0.00 |
October | 0.674673E+10 | 0.391189E+10 | 0.113057E+11 | 0.00 | 0.154830E+10 | 0.00 | 0.00 | 0.471118E+09 | 0.00 | 0.00 | 0.00 | 0.203039E+10 | 0.00 |
November | 0.653802E+10 | 0.416919E+10 | 0.108562E+11 | 0.00 | 0.157533E+10 | 0.00 | 0.00 | 10092718.72 | 0.00 | 0.00 | 0.00 | 0.202220E+10 | 0.00 |
December | 0.700727E+10 | 0.451342E+10 | 0.112984E+11 | 0.00 | 0.209021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215074E+10 | 0.00 |
Annual Sum or Average | 0.755638E+11 | 0.421890E+11 | 0.136508E+12 | 0.00 | 0.298679E+11 | 0.00 | 0.00 | 0.320500E+11 | 0.00 | 0.00 | 0.00 | 0.245161E+11 | 0.00 |
Minimum of Months | 0.570493E+10 | 0.262826E+10 | 0.103734E+11 | 0.00 | 0.154830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192965E+10 | 0.00 |
Maximum of Months | 0.700727E+10 | 0.451342E+10 | 0.121089E+11 | 0.00 | 0.439098E+10 | 0.00 | 0.00 | 0.948262E+10 | 0.00 | 0.00 | 0.00 | 0.221026E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.877672E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.524362E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.231701E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.324555E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 452992.72 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.331721E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.447085E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.261751E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.173823E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.877672E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 7432.40 | 11-JAN-09:09 | 3768.97 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2848.23 | 07-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 7760.33 | 01-FEB-09:09 | 3768.97 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2931.69 | 13-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 7285.62 | 18-MAR-08:09 | 3768.97 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 1999.21 | 22-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 6983.17 | 08-APR-08:09 | 3768.97 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 1763.43 | 06-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 6396.75 | 06-MAY-08:09 | 3768.97 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 3861.29 | 06-MAY-16:19 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 6172.99 | 08-JUN-08:09 | 3768.97 | 01-JUN-05:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 4159.55 | 06-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 6481.93 | 27-JUL-08:09 | 3768.97 | 01-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 4519.34 | 07-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 6643.97 | 24-AUG-07:10 | 3768.97 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4474.45 | 03-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 7130.60 | 30-SEP-08:09 | 3768.97 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4037.91 | 07-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 7863.02 | 30-OCT-08:09 | 3768.97 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 1750.97 | 26-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 7438.36 | 04-NOV-08:09 | 3768.97 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2209.32 | 22-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7371.40 | 19-DEC-09:09 | 3768.97 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2697.85 | 18-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 6172.99 | 3768.97 | 10035.17 | 0.00 | 1750.97 | 0.00 | 0.00 | |||||
Maximum of Months | 7863.02 | 3768.97 | 10035.17 | 0.00 | 4519.34 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2120.88 | 31-JAN-12:30 | 0.00 | 01-JAN-00:10 |
February | 486.37 | 28-FEB-14:00 | 0.00 | 0.00 | 0.00 | 2120.38 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 1356.04 | 30-MAR-15:00 | 0.00 | 0.00 | 0.00 | 2020.64 | 06-MAR-12:30 | 0.00 | 01-MAR-00:10 |
April | 6690.43 | 17-APR-17:40 | 0.00 | 0.00 | 0.00 | 1803.53 | 01-APR-11:30 | 0.00 | 01-APR-00:10 |
May | 7477.97 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1777.82 | 01-MAY-11:09 | 0.00 | 01-MAY-00:10 |
June | 11266.52 | 06-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1751.90 | 01-JUN-11:50 | 0.00 | 01-JUN-00:10 |
July | 13197.99 | 08-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1733.51 | 01-JUL-11:50 | 0.00 | 01-JUL-00:10 |
August | 12760.24 | 03-AUG-15:00 | 0.00 | 0.00 | 0.00 | 1731.69 | 31-AUG-11:39 | 0.00 | 01-AUG-00:10 |
September | 10462.26 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 1748.62 | 30-SEP-11:09 | 0.00 | 01-SEP-00:10 |
October | 4950.36 | 10-OCT-15:00 | 0.00 | 0.00 | 0.00 | 1774.92 | 31-OCT-11:39 | 0.00 | 01-OCT-00:10 |
November | 422.38 | 02-NOV-14:09 | 0.00 | 0.00 | 0.00 | 1800.62 | 30-NOV-12:09 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 1971.51 | 23-DEC-12:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1731.69 | 0.00 | |||
Maximum of Months | 13197.99 | 0.00 | 0.00 | 0.00 | 2120.88 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 21443.67 | 11-JAN-09:09 | 7432.40 | 10035.17 | 0.00 | 0.00 | 2302.26 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21727.33 | 01-FEB-09:09 | 7760.33 | 10035.17 | 0.00 | 0.00 | 2256.41 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20540.24 | 18-MAR-08:20 | 7192.12 | 10035.17 | 0.00 | 0.00 | 1644.12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23136.65 | 17-APR-14:00 | 5071.82 | 10035.17 | 0.00 | 0.00 | 1555.99 | 0.00 | 0.00 | 4720.30 | 0.00 |
May | 27280.14 | 19-MAY-13:00 | 4818.44 | 10035.17 | 0.00 | 0.00 | 3861.29 | 0.00 | 0.00 | 6865.74 | 0.00 |
June | 30515.97 | 06-JUN-15:30 | 3674.37 | 10035.17 | 0.00 | 0.00 | 4124.99 | 0.00 | 0.00 | 11092.05 | 0.00 |
July | 33118.48 | 08-JUL-14:50 | 4123.78 | 10035.17 | 0.00 | 0.00 | 4405.60 | 0.00 | 0.00 | 12850.93 | 0.00 |
August | 32686.40 | 03-AUG-15:00 | 3832.88 | 10035.17 | 0.00 | 0.00 | 4474.45 | 0.00 | 0.00 | 12760.24 | 0.00 |
September | 30608.62 | 07-SEP-15:50 | 4495.10 | 10035.17 | 0.00 | 0.00 | 4033.19 | 0.00 | 0.00 | 10459.30 | 0.00 |
October | 23476.20 | 10-OCT-15:50 | 5356.04 | 10035.17 | 0.00 | 0.00 | 1555.99 | 0.00 | 0.00 | 4937.78 | 0.00 |
November | 20681.44 | 04-NOV-08:09 | 7438.36 | 10035.17 | 0.00 | 0.00 | 1555.99 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21069.10 | 18-DEC-08:09 | 6868.44 | 10035.17 | 0.00 | 0.00 | 2529.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 20540.24 | 3674.37 | 10035.17 | 0.00 | 0.00 | 1555.99 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33118.48 | 7760.33 | 10035.17 | 0.00 | 0.00 | 4474.45 | 0.00 | 0.00 | 12850.93 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 163199.08 | 07-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 213741.31 | 12-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 27065.56 | 22-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 11952.65 | 06-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 387.50 | 11-MAY-06:30 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 10860.09 | 31-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 43156.24 | 22-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 85105.71 | 03-DEC-06:49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 213741.31 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.33 | 18.31 | 8.67 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
February | 12.50 | 17.55 | 7.17 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 |
March | 3.83 | 20.22 | 3.83 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 |
April | 0.33 | 20.23 | 0.33 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.54 | 2.83 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 24.91 | 6.50 | 24.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 24.74 | 8.17 | 24.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.55 | 2.50 | 24.55 |
October | 0.33 | 20.36 | 0.33 | 20.36 | 0.17 | 21.18 | 0.17 | 21.73 |
November | 3.67 | 20.03 | 3.67 | 20.03 | 0.00 | 20.03 | 0.00 | 20.03 |
December | 10.33 | 18.71 | 8.50 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Annual Sum or Average | 42.33 | 18.53 | 32.50 | 19.01 | 20.67 | 20.25 | 20.33 | 21.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.26 | 0.00 | 18.26 |
Maximum of Months | 12.50 | 20.36 | 8.67 | 20.36 | 8.17 | 24.91 | 8.17 | 24.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.67 | 14.60 | 4.83 | 14.60 | 0.00 | 14.60 | 0.00 | 14.60 |
February | 41.17 | 14.53 | 2.67 | 14.53 | 0.00 | 14.53 | 0.00 | 14.53 |
March | 0.83 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.29 | 0.00 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.46 | 0.00 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 27.53 | 0.00 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 27.48 | 0.00 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.31 | 0.00 | 27.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.00 | 14.83 | 0.67 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
December | 44.17 | 14.77 | 4.00 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 |
Annual Sum or Average | 169.83 | 14.64 | 12.17 | 14.64 | 74.00 | 18.35 | 0.00 | 18.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.67 | 14.99 | 4.83 | 14.99 | 26.33 | 27.53 | 0.00 | 27.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.07 | 283.83 | 21.06 | 283.83 | 21.05 |
February | 276.00 | 21.31 | 227.00 | 21.20 | 227.00 | 21.16 |
March | 319.00 | 22.06 | 143.83 | 21.78 | 143.83 | 21.63 |
April | 216.67 | 22.98 | 73.17 | 22.95 | 34.83 | 22.82 |
May | 104.00 | 23.59 | 204.33 | 23.79 | 56.50 | 23.80 |
June | 29.83 | 23.92 | 286.00 | 23.91 | 24.17 | 23.92 |
July | 36.83 | 24.03 | 299.67 | 23.93 | 36.83 | 23.94 |
August | 49.50 | 24.06 | 324.00 | 23.94 | 49.50 | 23.96 |
September | 15.00 | 23.83 | 271.33 | 23.90 | 10.17 | 23.91 |
October | 217.33 | 22.90 | 95.17 | 23.03 | 54.17 | 23.01 |
November | 288.00 | 22.01 | 152.17 | 21.77 | 152.17 | 21.65 |
December | 300.00 | 21.20 | 275.00 | 21.16 | 275.00 | 21.15 |
Annual Sum or Average | 2152.17 | 22.07 | 2635.50 | 22.42 | 1348.00 | 22.24 |
Minimum of Months | 15.00 | 21.07 | 73.17 | 21.06 | 10.17 | 21.05 |
Maximum of Months | 319.00 | 24.06 | 324.00 | 23.94 | 283.83 | 23.96 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.96 | 300.00 | 15.96 | 300.00 | 15.96 |
February | 276.00 | 16.92 | 263.00 | 16.79 | 263.00 | 16.75 |
March | 315.83 | 19.51 | 224.00 | 19.09 | 216.50 | 18.85 |
April | 198.00 | 21.91 | 155.17 | 22.73 | 71.00 | 22.47 |
May | 212.33 | 25.39 | 267.17 | 25.70 | 175.67 | 25.77 |
June | 264.33 | 26.63 | 304.50 | 26.60 | 263.00 | 26.61 |
July | 293.17 | 26.63 | 300.00 | 26.63 | 293.17 | 26.63 |
August | 321.33 | 26.70 | 324.00 | 26.70 | 321.33 | 26.70 |
September | 227.00 | 26.43 | 280.33 | 26.37 | 220.33 | 26.42 |
October | 235.17 | 22.13 | 176.83 | 22.64 | 125.83 | 22.58 |
November | 288.00 | 18.94 | 213.00 | 18.51 | 213.00 | 18.34 |
December | 300.00 | 16.75 | 294.67 | 16.71 | 294.67 | 16.70 |
Annual Sum or Average | 3231.17 | 21.80 | 3102.67 | 22.00 | 2757.50 | 21.92 |
Minimum of Months | 198.00 | 15.96 | 155.17 | 15.96 | 71.00 | 15.96 |
Maximum of Months | 321.33 | 26.70 | 324.00 | 26.70 | 321.33 | 26.70 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 11.42 | 300.00 | 11.42 | 300.00 | 11.42 |
February | 276.00 | 13.27 | 272.83 | 13.22 | 272.83 | 13.21 |
March | 319.33 | 18.73 | 244.17 | 18.32 | 240.33 | 18.13 |
April | 201.17 | 22.56 | 180.50 | 23.24 | 105.17 | 23.15 |
May | 254.33 | 27.29 | 274.17 | 27.41 | 224.33 | 27.56 |
June | 299.17 | 29.86 | 312.00 | 29.78 | 299.17 | 29.81 |
July | 300.00 | 30.36 | 300.00 | 30.36 | 300.00 | 30.36 |
August | 324.00 | 30.31 | 324.00 | 30.31 | 324.00 | 30.31 |
September | 246.17 | 28.73 | 296.17 | 28.43 | 246.17 | 28.52 |
October | 227.17 | 21.75 | 196.33 | 22.29 | 137.00 | 22.16 |
November | 288.00 | 17.33 | 252.00 | 17.08 | 252.00 | 16.99 |
December | 300.00 | 13.11 | 300.00 | 13.11 | 300.00 | 13.11 |
Annual Sum or Average | 3335.33 | 21.99 | 3252.17 | 22.13 | 3001.00 | 22.09 |
Minimum of Months | 201.17 | 11.42 | 180.50 | 11.42 | 105.17 | 11.42 |
Maximum of Months | 324.00 | 30.36 | 324.00 | 30.36 | 324.00 | 30.36 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 23458482.87 | 5381194.10 | 5.33 | 23458482.87 | 0.00 | 0.00 | 0.24 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 | 2111.72 | 28-FEB-15:00 | 2111.72 | 28-FEB-15:00 | 0.00 | 28-FEB-15:20 | 486.37 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.286472E+09 | 64853863.73 | 37.33 | 0.236756E+09 | 49716078.75 | 0.00 | 0.62 | 30-MAR-16:00 | 0.00 | 01-MAR-00:10 | 5990.40 | 30-MAR-16:00 | 5210.40 | 30-MAR-16:00 | 1155.20 | 30-MAR-12:10 | 1356.04 | 30-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.169760E+10 | 0.378857E+09 | 129.67 | 0.147158E+10 | 0.226017E+09 | 0.00 | 0.76 | 17-APR-16:00 | 0.00 | 01-APR-00:10 | 7344.76 | 12-APR-16:00 | 7344.76 | 12-APR-16:00 | 2022.06 | 22-APR-15:00 | 1643.41 | 17-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.459224E+10 | 0.999392E+09 | 231.65 | 0.354201E+10 | 0.105023E+10 | 0.00 | 1.00 | 08-MAY-05:05 | 0.00 | 01-MAY-00:10 | 23666.26 | 31-MAY-05:02 | 14824.68 | 17-MAY-05:03 | 13021.68 | 26-MAY-05:05 | 4591.20 | 31-MAY-05:02 | 0.00 | 01-MAY-00:10 |
June | 0.946609E+10 | 0.204924E+10 | 292.87 | 0.702643E+10 | 0.243966E+10 | 0.00 | 1.00 | 01-JUN-05:02 | 0.00 | 01-JUN-00:10 | 25656.91 | 26-JUN-05:01 | 17709.21 | 12-JUN-05:01 | 14407.25 | 23-JUN-05:04 | 4848.24 | 26-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.108490E+11 | 0.234972E+10 | 297.11 | 0.769688E+10 | 0.315212E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 26065.30 | 27-JUL-05:01 | 18146.32 | 18-JUL-05:01 | 16126.35 | 27-JUL-05:02 | 5136.05 | 23-JUL-16:53 | 0.00 | 01-JUL-00:10 |
August | 0.125160E+11 | 0.267943E+10 | 319.83 | 0.870291E+10 | 0.381312E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 26519.27 | 24-AUG-05:01 | 19042.38 | 13-AUG-17:45 | 16083.96 | 21-AUG-05:12 | 5079.58 | 13-AUG-17:45 | 0.00 | 01-AUG-00:10 |
September | 0.711315E+10 | 0.150535E+10 | 257.00 | 0.521226E+10 | 0.190090E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 25114.24 | 07-SEP-05:01 | 18997.16 | 16-SEP-05:01 | 13471.63 | 05-SEP-05:05 | 4783.59 | 07-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.171296E+10 | 0.368224E+09 | 110.47 | 0.122692E+10 | 0.486039E+09 | 0.00 | 1.00 | 11-OCT-05:35 | 0.00 | 01-OCT-00:10 | 25296.63 | 19-OCT-05:03 | 9679.53 | 18-OCT-05:03 | 15784.24 | 19-OCT-05:03 | 4805.77 | 19-OCT-05:03 | 0.00 | 01-OCT-00:10 |
November | 44291055.59 | 10092718.72 | 14.17 | 36338898.00 | 7952157.59 | 0.00 | 0.19 | 02-NOV-14:20 | 0.00 | 01-NOV-00:10 | 1875.85 | 02-NOV-14:10 | 1399.29 | 02-NOV-14:30 | 520.88 | 04-NOV-16:00 | 422.38 | 02-NOV-14:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.483013E+11 | 0.104105E+11 | 1695.43 | 0.351755E+11 | 0.131257E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.125160E+11 | 0.267943E+10 | 319.83 | 0.870291E+10 | 0.381312E+10 | 0.00 | 1.00 | 0.00 | 26519.27 | 19042.38 | 16126.35 | 5136.05 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.765525E+09 | 0.184487E+09 | 39.58 | 0.699472E+09 | 66052495.45 | 0.00 | 1.00 | 16-APR-14:45 | 0.00 | 01-APR-00:10 | 62647.90 | 17-APR-17:35 | 60926.16 | 16-APR-14:45 | 3862.26 | 17-APR-17:35 | 13380.86 | 17-APR-17:35 | 0.00 | 01-APR-00:10 |
May | 0.557578E+10 | 0.128883E+10 | 136.14 | 0.413841E+10 | 0.143737E+10 | 0.00 | 1.00 | 08-MAY-17:20 | 0.00 | 01-MAY-00:10 | 71649.95 | 21-MAY-10:55 | 55424.23 | 17-MAY-18:55 | 30466.03 | 21-MAY-10:55 | 14698.17 | 29-MAY-11:25 | 0.00 | 01-MAY-00:10 |
June | 0.208644E+11 | 0.475927E+10 | 307.99 | 0.147086E+11 | 0.615583E+10 | 0.00 | 1.00 | 01-JUN-17:10 | 0.00 | 01-JUN-00:10 | 68556.27 | 18-JUN-14:03 | 59735.02 | 08-JUN-17:12 | 23101.26 | 26-JUN-17:08 | 15075.56 | 23-JUN-17:08 | 0.00 | 01-JUN-00:10 |
July | 0.274919E+11 | 0.625833E+10 | 366.01 | 0.189579E+11 | 0.853399E+10 | 0.00 | 1.00 | 01-JUL-17:20 | 0.00 | 01-JUL-00:10 | 76437.94 | 09-JUL-08:65 | 55449.27 | 04-JUL-15:02 | 42263.01 | 27-JUL-17:25 | 15268.28 | 14-JUL-17:08 | 0.00 | 01-JUL-00:10 |
August | 0.303292E+11 | 0.680320E+10 | 401.93 | 0.200418E+11 | 0.102874E+11 | 0.00 | 1.00 | 01-AUG-13:40 | 0.00 | 01-AUG-00:10 | 72270.75 | 11-AUG-17:10 | 55025.21 | 27-AUG-15:53 | 28368.96 | 07-AUG-23:02 | 15341.51 | 01-AUG-17:06 | 0.00 | 01-AUG-00:10 |
September | 0.998134E+10 | 0.224249E+10 | 192.75 | 0.676968E+10 | 0.321165E+10 | 0.00 | 1.00 | 03-SEP-12:35 | 0.00 | 01-SEP-00:10 | 77538.21 | 17-SEP-11:25 | 56346.84 | 14-SEP-17:12 | 42084.22 | 10-SEP-09:15 | 15275.65 | 17-SEP-11:25 | 0.00 | 01-SEP-00:10 |
October | 0.439138E+09 | 0.102895E+09 | 16.00 | 0.284702E+09 | 0.154436E+09 | 0.00 | 0.40 | 11-OCT-14:20 | 0.00 | 01-OCT-00:10 | 12787.52 | 11-OCT-14:10 | 8399.50 | 10-OCT-16:00 | 4853.44 | 11-OCT-14:00 | 2934.72 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.954473E+11 | 0.216395E+11 | 1460.42 | 0.656005E+11 | 0.298468E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.303292E+11 | 0.680320E+10 | 401.93 | 0.200418E+11 | 0.102874E+11 | 0.00 | 1.00 | 0.00 | 77538.21 | 60926.16 | 42263.01 | 15341.51 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.80 | 25.09 | 28.71 | 50.92 | 113.32 | 0.00 | 0.00 | 0.00 |
February | 61.34 | 28.68 | 32.66 | 73.12 | 90.80 | 0.00 | 0.00 | 0.00 |
March | 90.21 | 43.52 | 46.69 | 125.85 | 56.67 | 0.00 | 0.00 | 0.00 |
April | 101.45 | 46.34 | 55.11 | 152.63 | 54.76 | 0.00 | 0.00 | 0.00 |
May | 102.22 | 38.77 | 63.46 | 161.98 | 42.54 | 0.00 | 0.00 | 0.00 |
June | 107.63 | 41.56 | 66.06 | 187.37 | 32.57 | 0.00 | 0.00 | 0.00 |
July | 101.21 | 37.49 | 63.71 | 180.97 | 25.25 | 0.00 | 0.00 | 0.00 |
August | 99.18 | 37.05 | 62.13 | 179.14 | 22.98 | 0.00 | 0.00 | 0.00 |
September | 81.10 | 33.88 | 47.22 | 128.44 | 42.15 | 0.00 | 0.00 | 0.00 |
October | 71.80 | 37.17 | 34.63 | 100.81 | 69.19 | 0.00 | 0.00 | 0.00 |
November | 57.18 | 25.50 | 31.68 | 73.04 | 76.94 | 0.00 | 0.00 | 0.00 |
December | 47.55 | 20.87 | 26.69 | 49.58 | 91.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.32 | 34.69 | 46.64 | 122.24 | 59.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.55 | 20.87 | 26.69 | 49.58 | 22.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.63 | 46.34 | 66.06 | 187.37 | 113.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 53.80 | 25.09 | 28.71 | 50.92 | 113.32 | 0.00 | 0.00 | 0.00 |
February | 61.34 | 28.68 | 32.66 | 73.12 | 90.80 | 0.00 | 0.00 | 0.00 |
March | 90.21 | 43.52 | 46.69 | 125.85 | 56.67 | 0.00 | 0.00 | 0.00 |
April | 101.45 | 46.34 | 55.11 | 152.63 | 54.76 | 0.00 | 0.00 | 0.00 |
May | 102.22 | 38.77 | 63.46 | 161.98 | 42.54 | 0.00 | 0.00 | 0.00 |
June | 107.63 | 41.56 | 66.06 | 187.37 | 32.57 | 0.00 | 0.00 | 0.00 |
July | 101.21 | 37.49 | 63.71 | 180.97 | 25.25 | 0.00 | 0.00 | 0.00 |
August | 99.18 | 37.05 | 62.13 | 179.14 | 22.98 | 0.00 | 0.00 | 0.00 |
September | 81.10 | 33.88 | 47.22 | 128.44 | 42.15 | 0.00 | 0.00 | 0.00 |
October | 71.80 | 37.17 | 34.63 | 100.81 | 69.19 | 0.00 | 0.00 | 0.00 |
November | 57.18 | 25.50 | 31.68 | 73.04 | 76.94 | 0.00 | 0.00 | 0.00 |
December | 47.55 | 20.87 | 26.69 | 49.58 | 91.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.32 | 34.69 | 46.64 | 122.24 | 59.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.55 | 20.87 | 26.69 | 49.58 | 22.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.63 | 46.34 | 66.06 | 187.37 | 113.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.80 | 0.00 | 13.80 | 3.60 | 71.95 | 0.00 | 0.00 | 0.00 |
February | 15.30 | 0.00 | 15.30 | 9.70 | 56.32 | 0.00 | 0.00 | 0.00 |
March | 21.49 | 0.00 | 21.48 | 20.08 | 34.17 | 0.00 | 0.00 | 0.00 |
April | 26.01 | 0.14 | 25.88 | 31.37 | 32.03 | 0.00 | 0.00 | 0.00 |
May | 31.07 | 0.97 | 30.10 | 43.48 | 23.75 | 0.00 | 0.00 | 0.00 |
June | 34.08 | 2.14 | 31.94 | 58.99 | 17.86 | 0.00 | 0.00 | 0.00 |
July | 32.27 | 1.57 | 30.70 | 58.33 | 14.14 | 0.00 | 0.00 | 0.00 |
August | 28.77 | 0.36 | 28.40 | 52.79 | 12.99 | 0.00 | 0.00 | 0.00 |
September | 21.71 | 0.01 | 21.70 | 30.21 | 24.83 | 0.00 | 0.00 | 0.00 |
October | 16.49 | 0.00 | 16.49 | 14.85 | 41.30 | 0.00 | 0.00 | 0.00 |
November | 14.76 | 0.00 | 14.76 | 10.72 | 46.34 | 0.00 | 0.00 | 0.00 |
December | 12.76 | 0.00 | 12.76 | 4.49 | 56.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.42 | 0.43 | 21.98 | 28.32 | 35.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.76 | 0.00 | 12.76 | 3.60 | 12.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.08 | 2.14 | 31.94 | 58.99 | 71.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.80 | 0.00 | 13.80 | 3.60 | 71.95 | 0.00 | 0.00 | 0.00 |
February | 15.30 | 0.00 | 15.30 | 9.70 | 56.32 | 0.00 | 0.00 | 0.00 |
March | 21.49 | 0.00 | 21.48 | 20.08 | 34.17 | 0.00 | 0.00 | 0.00 |
April | 26.01 | 0.14 | 25.88 | 31.37 | 32.03 | 0.00 | 0.00 | 0.00 |
May | 31.07 | 0.97 | 30.10 | 43.47 | 23.75 | 0.00 | 0.00 | 0.00 |
June | 34.08 | 2.14 | 31.94 | 58.99 | 17.86 | 0.00 | 0.00 | 0.00 |
July | 32.27 | 1.57 | 30.70 | 58.33 | 14.14 | 0.00 | 0.00 | 0.00 |
August | 28.77 | 0.36 | 28.40 | 52.79 | 12.99 | 0.00 | 0.00 | 0.00 |
September | 21.71 | 0.01 | 21.70 | 30.21 | 24.83 | 0.00 | 0.00 | 0.00 |
October | 16.49 | 0.00 | 16.49 | 14.85 | 41.30 | 0.00 | 0.00 | 0.00 |
November | 14.76 | 0.00 | 14.76 | 10.72 | 46.34 | 0.00 | 0.00 | 0.00 |
December | 12.76 | 0.00 | 12.76 | 4.48 | 56.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.41 | 0.43 | 21.98 | 28.32 | 35.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.76 | 0.00 | 12.76 | 3.60 | 12.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.08 | 2.14 | 31.94 | 58.99 | 71.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.99 | 40.54 | 6.50 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.12 | 33.65 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 66.04 | 24.38 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.23 | 24.74 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.36 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.48 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.89 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.22 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.94 | 21.35 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 53.00 | 28.26 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.07 | 30.49 | 2.67 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.61 | 34.52 | 3.67 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.56 | 25.26 | 12.83 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.61 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.48 | 40.54 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.99 | 40.54 | 6.50 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.12 | 33.65 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 66.04 | 24.38 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.23 | 24.74 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.36 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.48 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.89 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.22 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.94 | 21.35 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 53.00 | 28.26 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.07 | 30.49 | 2.67 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.61 | 34.52 | 3.67 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.56 | 25.26 | 12.83 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.61 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.48 | 40.54 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.99 | 40.54 | 6.50 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.12 | 33.65 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 66.04 | 24.38 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.23 | 24.74 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.36 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.48 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.89 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.22 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.94 | 21.35 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 53.00 | 28.26 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.07 | 30.49 | 2.67 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.61 | 34.52 | 3.67 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.56 | 25.26 | 12.83 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.61 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.48 | 40.54 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.99 | 40.54 | 6.50 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.12 | 33.65 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 66.04 | 24.38 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.23 | 24.74 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.36 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.48 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.89 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.22 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.94 | 21.35 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 53.00 | 28.26 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.07 | 30.49 | 2.67 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.61 | 34.52 | 3.67 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.56 | 25.26 | 12.83 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.61 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.48 | 40.54 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.99 | 40.54 | 6.50 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.12 | 33.65 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 66.04 | 24.38 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.23 | 24.74 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.36 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.48 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.89 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.22 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.94 | 21.35 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 53.00 | 28.26 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.07 | 30.49 | 2.67 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.61 | 34.52 | 3.67 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.56 | 25.26 | 12.83 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.61 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.48 | 40.54 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.99 | 40.54 | 6.50 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.12 | 33.65 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 66.04 | 24.38 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.23 | 24.74 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.36 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.48 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.89 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.22 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.94 | 21.35 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 53.00 | 28.26 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.07 | 30.49 | 2.67 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.61 | 34.52 | 3.67 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.56 | 25.26 | 12.83 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.61 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.48 | 40.54 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.99 | 40.54 | 6.50 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.12 | 33.65 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 66.04 | 24.38 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.23 | 24.74 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.36 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.48 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.89 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.22 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.94 | 21.35 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 53.00 | 28.26 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.07 | 30.49 | 2.67 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.61 | 34.52 | 3.67 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.56 | 25.26 | 12.83 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.61 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.48 | 40.54 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.99 | 40.54 | 6.50 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.12 | 33.65 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 66.04 | 24.38 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.23 | 24.74 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.36 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.48 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.89 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.22 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.94 | 21.35 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 53.00 | 28.26 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.07 | 30.49 | 2.67 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.61 | 34.52 | 3.67 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.56 | 25.26 | 12.83 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.61 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.48 | 40.54 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.99 | 40.54 | 6.50 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.12 | 33.65 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 66.04 | 24.38 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.23 | 24.74 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.36 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.48 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.89 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.22 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.94 | 21.35 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 53.00 | 28.26 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.07 | 30.49 | 2.67 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.61 | 34.52 | 3.67 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.56 | 25.26 | 12.83 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.61 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.48 | 40.54 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.99 | 40.54 | 6.50 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.12 | 33.65 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 66.04 | 24.38 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.23 | 24.74 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.36 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.48 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.89 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.22 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.94 | 21.35 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 53.00 | 28.26 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.07 | 30.49 | 2.67 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.61 | 34.52 | 3.67 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.56 | 25.26 | 12.83 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.61 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.48 | 40.54 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.99 | 40.54 | 6.50 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.12 | 33.65 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 66.04 | 24.38 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.23 | 24.74 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.36 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.48 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.89 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.22 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.94 | 21.35 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 53.00 | 28.26 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.07 | 30.49 | 2.67 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.61 | 34.52 | 3.67 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.56 | 25.26 | 12.83 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.61 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.48 | 40.54 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.99 | 40.54 | 6.50 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.12 | 33.65 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 66.04 | 24.38 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.23 | 24.74 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.36 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.48 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.89 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.22 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.94 | 21.35 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 53.00 | 28.26 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.07 | 30.49 | 2.67 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.61 | 34.52 | 3.67 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.56 | 25.26 | 12.83 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.61 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.48 | 40.54 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.99 | 40.54 | 6.50 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.12 | 33.65 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 66.04 | 24.38 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.23 | 24.74 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.36 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.48 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.89 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.22 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.94 | 21.35 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 53.00 | 28.26 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.07 | 30.49 | 2.67 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.61 | 34.52 | 3.67 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.56 | 25.26 | 12.83 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.61 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.48 | 40.54 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.08 | 15.48 | 12.59 | 27.99 | 40.54 | 6.50 | 0.00 | 0.00 |
February | 34.43 | 21.04 | 13.39 | 40.12 | 33.65 | 0.00 | 0.00 | 0.00 |
March | 51.44 | 31.57 | 19.88 | 66.04 | 24.38 | 0.00 | 0.00 | 0.00 |
April | 64.63 | 40.00 | 24.63 | 86.23 | 24.74 | 0.00 | 0.00 | 0.00 |
May | 72.22 | 41.91 | 30.31 | 98.36 | 20.24 | 0.00 | 0.00 | 0.00 |
June | 77.17 | 45.71 | 31.46 | 109.48 | 17.42 | 0.00 | 0.00 | 0.00 |
July | 71.90 | 40.92 | 30.97 | 103.89 | 14.17 | 0.00 | 0.00 | 0.00 |
August | 66.14 | 36.41 | 29.74 | 96.22 | 13.90 | 0.00 | 0.00 | 0.00 |
September | 48.44 | 26.81 | 21.63 | 64.94 | 21.35 | 0.00 | 0.00 | 0.00 |
October | 41.95 | 28.25 | 13.69 | 53.00 | 28.26 | 0.00 | 0.00 | 0.00 |
November | 30.06 | 16.58 | 13.48 | 36.07 | 30.49 | 2.67 | 0.00 | 0.00 |
December | 24.74 | 13.17 | 11.58 | 26.61 | 34.52 | 3.67 | 0.00 | 0.00 |
Annual Sum or Average | 51.02 | 29.87 | 21.16 | 67.56 | 25.26 | 12.83 | 0.00 | 0.00 |
Minimum of Months | 24.74 | 13.17 | 11.58 | 26.61 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.17 | 45.71 | 31.46 | 109.48 | 40.54 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.96 | 32.04 | 24.92 | 69.52 | 40.65 | 25.00 | 0.00 | 0.00 |
February | 68.85 | 42.35 | 26.50 | 89.70 | 35.05 | 51.83 | 0.00 | 0.00 |
March | 101.09 | 61.75 | 39.34 | 134.90 | 31.54 | 0.00 | 0.00 | 0.00 |
April | 126.10 | 77.35 | 48.75 | 170.51 | 34.62 | 0.50 | 0.00 | 0.00 |
May | 140.49 | 80.50 | 59.99 | 190.71 | 30.56 | 1.00 | 0.00 | 0.00 |
June | 149.91 | 87.63 | 62.27 | 206.16 | 29.70 | 0.00 | 0.00 | 0.00 |
July | 139.88 | 78.58 | 61.31 | 193.88 | 25.90 | 1.67 | 0.00 | 0.00 |
August | 128.95 | 70.10 | 58.85 | 179.70 | 25.67 | 0.00 | 0.00 | 0.00 |
September | 95.08 | 52.27 | 42.81 | 125.09 | 33.71 | 0.50 | 0.00 | 0.00 |
October | 82.88 | 55.78 | 27.10 | 108.13 | 38.38 | 11.17 | 0.00 | 0.00 |
November | 60.67 | 33.98 | 26.69 | 78.91 | 36.85 | 39.50 | 0.00 | 0.00 |
December | 50.63 | 27.72 | 22.91 | 64.45 | 35.03 | 42.17 | 0.00 | 0.00 |
Annual Sum or Average | 100.30 | 58.42 | 41.88 | 134.55 | 33.12 | 173.33 | 0.00 | 0.00 |
Minimum of Months | 50.63 | 27.72 | 22.91 | 64.45 | 25.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.91 | 87.63 | 62.27 | 206.16 | 40.65 | 51.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144099E+09 | 67190086.89 | 76909197.70 | 0.136372E+09 | 0.303509E+09 |
February | 0.148397E+09 | 69387007.56 | 79009896.41 | 0.176882E+09 | 0.219666E+09 |
March | 0.241608E+09 | 0.116565E+09 | 0.125044E+09 | 0.337085E+09 | 0.151789E+09 |
April | 0.262950E+09 | 0.120103E+09 | 0.142847E+09 | 0.395610E+09 | 0.141943E+09 |
May | 0.273795E+09 | 0.103834E+09 | 0.169961E+09 | 0.433859E+09 | 0.113934E+09 |
June | 0.278965E+09 | 0.107736E+09 | 0.171228E+09 | 0.485667E+09 | 84429924.00 |
July | 0.271068E+09 | 0.100423E+09 | 0.170645E+09 | 0.484707E+09 | 67636602.33 |
August | 0.265646E+09 | 99244081.66 | 0.166402E+09 | 0.479807E+09 | 61554002.83 |
September | 0.210210E+09 | 87824097.10 | 0.122385E+09 | 0.332923E+09 | 0.109243E+09 |
October | 0.192301E+09 | 99549954.50 | 92751352.52 | 0.270012E+09 | 0.185331E+09 |
November | 0.148212E+09 | 66087259.20 | 82124365.90 | 0.189310E+09 | 0.199423E+09 |
December | 0.127367E+09 | 55892649.05 | 71473937.90 | 0.132795E+09 | 0.245829E+09 |
Annual Sum or Average | 0.256462E+10 | 0.109384E+10 | 0.147078E+10 | 0.385503E+10 | 0.188429E+10 |
Minimum of Months | 0.127367E+09 | 55892649.05 | 71473937.90 | 0.132795E+09 | 61554002.83 |
Maximum of Months | 0.278965E+09 | 0.120103E+09 | 0.171228E+09 | 0.485667E+09 | 0.303509E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144099E+09 | 67190086.89 | 76909197.70 | 0.136372E+09 | 0.303509E+09 |
February | 0.148397E+09 | 69387007.56 | 79009896.41 | 0.176882E+09 | 0.219666E+09 |
March | 0.241608E+09 | 0.116565E+09 | 0.125044E+09 | 0.337085E+09 | 0.151789E+09 |
April | 0.262950E+09 | 0.120103E+09 | 0.142847E+09 | 0.395610E+09 | 0.141943E+09 |
May | 0.273795E+09 | 0.103834E+09 | 0.169961E+09 | 0.433859E+09 | 0.113934E+09 |
June | 0.278965E+09 | 0.107736E+09 | 0.171228E+09 | 0.485667E+09 | 84429924.00 |
July | 0.271068E+09 | 0.100423E+09 | 0.170645E+09 | 0.484707E+09 | 67636602.33 |
August | 0.265646E+09 | 99244081.66 | 0.166402E+09 | 0.479807E+09 | 61554002.83 |
September | 0.210210E+09 | 87824097.10 | 0.122385E+09 | 0.332923E+09 | 0.109243E+09 |
October | 0.192301E+09 | 99549954.50 | 92751352.52 | 0.270012E+09 | 0.185331E+09 |
November | 0.148212E+09 | 66087259.20 | 82124365.90 | 0.189310E+09 | 0.199423E+09 |
December | 0.127367E+09 | 55892649.05 | 71473937.90 | 0.132795E+09 | 0.245829E+09 |
Annual Sum or Average | 0.256462E+10 | 0.109384E+10 | 0.147078E+10 | 0.385503E+10 | 0.188429E+10 |
Minimum of Months | 0.127367E+09 | 55892649.05 | 71473937.90 | 0.132795E+09 | 61554002.83 |
Maximum of Months | 0.278965E+09 | 0.120103E+09 | 0.171228E+09 | 0.485667E+09 | 0.303509E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36970919.86 | 0.00 | 36970919.86 | 9642384.04 | 0.192706E+09 |
February | 37012989.26 | 0.00 | 37012989.26 | 23475823.13 | 0.136238E+09 |
March | 57548283.46 | 3066.27 | 57545217.19 | 53771030.52 | 91526669.40 |
April | 67426402.71 | 352601.56 | 67073801.15 | 81312287.79 | 83023888.96 |
May | 83228708.08 | 2597172.86 | 80631535.22 | 0.116444E+09 | 63613110.77 |
June | 88335254.71 | 5551815.21 | 82783439.50 | 0.152911E+09 | 46299255.77 |
July | 86441676.67 | 4209343.05 | 82232333.62 | 0.156238E+09 | 37869339.88 |
August | 77050157.49 | 974289.45 | 76075868.04 | 0.141399E+09 | 34793534.95 |
September | 56261806.02 | 22895.89 | 56238910.14 | 78309677.46 | 64357205.71 |
October | 44173323.99 | 0.00 | 44173323.99 | 39767143.40 | 0.110613E+09 |
November | 38258235.74 | 0.00 | 38258235.74 | 27795540.96 | 0.120102E+09 |
December | 34176865.45 | 0.00 | 34176865.45 | 12013306.97 | 0.150650E+09 |
Annual Sum or Average | 0.706885E+09 | 13711184.29 | 0.693173E+09 | 0.893079E+09 | 0.113179E+10 |
Minimum of Months | 34176865.45 | 0.00 | 34176865.45 | 9642384.04 | 34793534.95 |
Maximum of Months | 88335254.71 | 5551815.21 | 82783439.50 | 0.156238E+09 | 0.192706E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36969807.32 | 0.00 | 36969807.32 | 9641774.26 | 0.192706E+09 |
February | 37011928.69 | 0.00 | 37011928.69 | 23474954.77 | 0.136237E+09 |
March | 57546628.30 | 3066.12 | 57543562.18 | 53769086.28 | 91526012.16 |
April | 67424490.45 | 352585.04 | 67071905.41 | 81309878.05 | 83023324.79 |
May | 83226228.11 | 2597051.13 | 80629176.98 | 0.116440E+09 | 63612653.00 |
June | 88332578.85 | 5551554.99 | 82781023.86 | 0.152907E+09 | 46298701.37 |
July | 86439043.15 | 4209145.75 | 82229897.40 | 0.156234E+09 | 37868811.44 |
August | 77047855.32 | 974243.79 | 76073611.54 | 0.141396E+09 | 34792951.80 |
September | 56260122.22 | 22894.81 | 56237227.41 | 78307373.61 | 64356543.25 |
October | 44172118.43 | 0.00 | 44172118.43 | 39765838.68 | 0.110613E+09 |
November | 38257080.74 | 0.00 | 38257080.74 | 27794428.15 | 0.120102E+09 |
December | 34175826.23 | 0.00 | 34175826.23 | 12012498.18 | 0.150649E+09 |
Annual Sum or Average | 0.706864E+09 | 13710541.63 | 0.693153E+09 | 0.893052E+09 | 0.113179E+10 |
Minimum of Months | 34175826.23 | 0.00 | 34175826.23 | 9641774.26 | 34792951.80 |
Maximum of Months | 88332578.85 | 5551554.99 | 82781023.86 | 0.156234E+09 | 0.192706E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74978749.82 | 0.108573E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 97049575.16 | 81410191.16 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176877E+09 | 65294140.04 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223504E+09 | 64138902.21 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263442E+09 | 54222047.09 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283784E+09 | 45151112.60 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278257E+09 | 37952558.71 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257720E+09 | 37227826.26 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168332E+09 | 55338778.02 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141960E+09 | 75703793.23 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93505247.88 | 79028255.44 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 92445885.28 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.213068E+10 | 0.796486E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 37227826.26 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283784E+09 | 0.108573E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74978749.82 | 0.108573E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 97049575.16 | 81410191.16 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176877E+09 | 65294140.04 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223504E+09 | 64138902.21 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263442E+09 | 54222047.09 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283784E+09 | 45151112.60 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278257E+09 | 37952558.71 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257720E+09 | 37227826.26 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168332E+09 | 55338778.02 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141960E+09 | 75703793.23 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93505247.88 | 79028255.44 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 92445885.28 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.213068E+10 | 0.796486E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 37227826.26 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283784E+09 | 0.108573E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74978749.82 | 0.108573E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 97049575.16 | 81410191.16 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176877E+09 | 65294140.04 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223504E+09 | 64138902.21 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263442E+09 | 54222047.09 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283784E+09 | 45151112.60 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278257E+09 | 37952558.71 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257720E+09 | 37227826.26 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168332E+09 | 55338778.02 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141960E+09 | 75703793.23 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93505247.88 | 79028255.44 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 92445885.28 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.213068E+10 | 0.796486E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 37227826.26 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283784E+09 | 0.108573E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74978749.82 | 0.108573E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 97049575.16 | 81410191.16 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176877E+09 | 65294140.04 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223504E+09 | 64138902.21 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263442E+09 | 54222047.09 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283784E+09 | 45151112.60 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278257E+09 | 37952558.71 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257720E+09 | 37227826.26 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168332E+09 | 55338778.02 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141960E+09 | 75703793.23 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93505247.88 | 79028255.44 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 92445885.28 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.213068E+10 | 0.796486E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 37227826.26 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283784E+09 | 0.108573E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74978749.82 | 0.108573E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 97049575.16 | 81410191.16 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176877E+09 | 65294140.04 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223504E+09 | 64138902.21 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263442E+09 | 54222047.09 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283784E+09 | 45151112.60 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278257E+09 | 37952558.71 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257720E+09 | 37227826.26 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168332E+09 | 55338778.02 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141960E+09 | 75703793.23 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93505247.88 | 79028255.44 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 92445885.28 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.213068E+10 | 0.796486E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 37227826.26 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283784E+09 | 0.108573E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74978749.82 | 0.108573E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 97049575.16 | 81410191.16 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176877E+09 | 65294140.04 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223504E+09 | 64138902.21 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263442E+09 | 54222047.09 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283784E+09 | 45151112.60 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278257E+09 | 37952558.71 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257720E+09 | 37227826.26 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168332E+09 | 55338778.02 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141960E+09 | 75703793.23 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93505247.88 | 79028255.44 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 92445885.28 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.213068E+10 | 0.796486E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 37227826.26 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283784E+09 | 0.108573E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74978749.82 | 0.108573E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 97049575.16 | 81410191.16 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176877E+09 | 65294140.04 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223504E+09 | 64138902.21 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263442E+09 | 54222047.09 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283784E+09 | 45151112.60 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278257E+09 | 37952558.71 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257720E+09 | 37227826.26 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168332E+09 | 55338778.02 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141960E+09 | 75703793.23 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93505247.88 | 79028255.44 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 92445885.28 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.213068E+10 | 0.796486E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 37227826.26 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283784E+09 | 0.108573E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74978749.82 | 0.108573E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 97049575.16 | 81410191.16 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176877E+09 | 65294140.04 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223504E+09 | 64138902.21 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263442E+09 | 54222047.09 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283784E+09 | 45151112.60 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278257E+09 | 37952558.71 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257720E+09 | 37227826.26 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168332E+09 | 55338778.02 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141960E+09 | 75703793.23 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93505247.88 | 79028255.44 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 92445885.28 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.213068E+10 | 0.796486E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 37227826.26 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283784E+09 | 0.108573E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74978749.82 | 0.108573E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 97049575.16 | 81410191.16 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176877E+09 | 65294140.04 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223504E+09 | 64138902.21 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263442E+09 | 54222047.09 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283784E+09 | 45151112.60 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278257E+09 | 37952558.71 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257720E+09 | 37227826.26 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168332E+09 | 55338778.02 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141960E+09 | 75703793.23 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93505247.88 | 79028255.44 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 92445885.28 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.213068E+10 | 0.796486E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 37227826.26 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283784E+09 | 0.108573E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74978749.82 | 0.108573E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 97049575.16 | 81410191.16 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176877E+09 | 65294140.04 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223504E+09 | 64138902.21 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263442E+09 | 54222047.09 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283784E+09 | 45151112.60 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278257E+09 | 37952558.71 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257720E+09 | 37227826.26 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168332E+09 | 55338778.02 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141960E+09 | 75703793.23 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93505247.88 | 79028255.44 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 92445885.28 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.213068E+10 | 0.796486E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 37227826.26 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283784E+09 | 0.108573E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74978749.82 | 0.108573E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 97049575.16 | 81410191.16 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176877E+09 | 65294140.04 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223504E+09 | 64138902.21 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263442E+09 | 54222047.09 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283784E+09 | 45151112.60 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278257E+09 | 37952558.71 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257720E+09 | 37227826.26 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168332E+09 | 55338778.02 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141960E+09 | 75703793.23 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93505247.88 | 79028255.44 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 92445885.28 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.213068E+10 | 0.796486E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 37227826.26 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283784E+09 | 0.108573E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74978749.82 | 0.108573E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 97049575.16 | 81410191.16 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176877E+09 | 65294140.04 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223504E+09 | 64138902.21 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263442E+09 | 54222047.09 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283784E+09 | 45151112.60 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278257E+09 | 37952558.71 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257720E+09 | 37227826.26 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168332E+09 | 55338778.02 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141960E+09 | 75703793.23 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93505247.88 | 79028255.44 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 92445885.28 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.213068E+10 | 0.796486E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 37227826.26 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283784E+09 | 0.108573E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74978749.82 | 0.108573E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 97049575.16 | 81410191.16 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176877E+09 | 65294140.04 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223504E+09 | 64138902.21 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263442E+09 | 54222047.09 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283784E+09 | 45151112.60 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278257E+09 | 37952558.71 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257720E+09 | 37227826.26 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168332E+09 | 55338778.02 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141960E+09 | 75703793.23 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93505247.88 | 79028255.44 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 92445885.28 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.213068E+10 | 0.796486E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 37227826.26 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283784E+09 | 0.108573E+09 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75196349.69 | 41474944.07 | 33721405.61 | 74978749.82 | 0.108573E+09 |
February | 83285899.81 | 50893004.90 | 32392894.91 | 97049575.16 | 81410191.16 |
March | 0.137789E+09 | 84554150.37 | 53234844.09 | 0.176877E+09 | 65294140.04 |
April | 0.167514E+09 | 0.103669E+09 | 63845653.92 | 0.223504E+09 | 64138902.21 |
May | 0.193438E+09 | 0.112260E+09 | 81178787.14 | 0.263442E+09 | 54222047.09 |
June | 0.200031E+09 | 0.118476E+09 | 81554940.43 | 0.283784E+09 | 45151112.60 |
July | 0.192570E+09 | 0.109609E+09 | 82961466.13 | 0.278257E+09 | 37952558.71 |
August | 0.177163E+09 | 97519462.22 | 79643155.34 | 0.257720E+09 | 37227826.26 |
September | 0.125564E+09 | 69497799.71 | 56066027.62 | 0.168332E+09 | 55338778.02 |
October | 0.112346E+09 | 75674014.47 | 36672230.03 | 0.141960E+09 | 75703793.23 |
November | 77921107.05 | 42973366.94 | 34947740.12 | 93505247.88 | 79028255.44 |
December | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 92445885.28 |
Annual Sum or Average | 0.160909E+10 | 0.941865E+09 | 0.667222E+09 | 0.213068E+10 | 0.796486E+09 |
Minimum of Months | 66268568.13 | 35265478.96 | 31003089.17 | 71269206.36 | 37227826.26 |
Maximum of Months | 0.200031E+09 | 0.118476E+09 | 82961466.13 | 0.283784E+09 | 0.108573E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152550E+09 | 85807884.48 | 66742252.54 | 0.186206E+09 | 0.108864E+09 |
February | 0.166566E+09 | 0.102453E+09 | 64112830.81 | 0.216991E+09 | 84790120.82 |
March | 0.270766E+09 | 0.165403E+09 | 0.105364E+09 | 0.361324E+09 | 84478777.10 |
April | 0.326844E+09 | 0.200479E+09 | 0.126365E+09 | 0.441959E+09 | 89745056.01 |
May | 0.376277E+09 | 0.215606E+09 | 0.160671E+09 | 0.510785E+09 | 81856254.98 |
June | 0.388563E+09 | 0.227147E+09 | 0.161416E+09 | 0.534378E+09 | 76988330.46 |
July | 0.374657E+09 | 0.210458E+09 | 0.164199E+09 | 0.519280E+09 | 69361145.35 |
August | 0.345374E+09 | 0.187743E+09 | 0.157632E+09 | 0.481307E+09 | 68750595.00 |
September | 0.246451E+09 | 0.135484E+09 | 0.110967E+09 | 0.324240E+09 | 87375833.96 |
October | 0.221989E+09 | 0.149406E+09 | 72582598.31 | 0.289609E+09 | 0.102784E+09 |
November | 0.157253E+09 | 88083604.99 | 69169444.58 | 0.204526E+09 | 95521747.79 |
December | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 93824460.85 |
Annual Sum or Average | 0.316291E+10 | 0.184232E+10 | 0.132058E+10 | 0.424322E+10 | 0.104434E+10 |
Minimum of Months | 0.135618E+09 | 74255984.30 | 61362092.41 | 0.172613E+09 | 68750595.00 |
Maximum of Months | 0.388563E+09 | 0.227147E+09 | 0.164199E+09 | 0.534378E+09 | 0.108864E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 100.55 | 362.05 | 135.21 | 50.17 | 85.04 | 0.00 | 0.00 |
February | 160.21 | 288.80 | 153.28 | 57.36 | 95.92 | 0.00 | 0.00 |
March | 290.37 | 180.20 | 223.38 | 87.04 | 136.34 | 0.00 | 0.00 |
April | 367.03 | 172.62 | 254.92 | 92.94 | 161.98 | 0.00 | 0.00 |
May | 410.01 | 131.67 | 266.59 | 79.47 | 187.12 | 0.00 | 0.00 |
June | 491.36 | 99.50 | 283.41 | 87.41 | 196.00 | 0.00 | 0.00 |
July | 477.68 | 77.86 | 266.96 | 78.13 | 188.83 | 0.00 | 0.00 |
August | 463.60 | 71.68 | 255.90 | 74.83 | 181.06 | 0.00 | 0.00 |
September | 316.84 | 133.48 | 205.61 | 67.78 | 137.83 | 0.00 | 0.00 |
October | 229.71 | 219.38 | 176.58 | 74.34 | 102.24 | 0.00 | 0.00 |
November | 165.53 | 244.56 | 143.88 | 50.99 | 92.89 | 0.00 | 0.00 |
December | 104.20 | 292.12 | 120.63 | 41.74 | 78.89 | 0.00 | 0.00 |
Annual Sum or Average | 298.82 | 188.97 | 207.48 | 70.24 | 137.24 | 0.00 | 0.00 |
Minimum of Months | 100.55 | 71.68 | 120.63 | 41.74 | 78.89 | 0.00 | 0.00 |
Maximum of Months | 491.36 | 362.05 | 283.41 | 92.94 | 196.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 391.91 | 567.51 | 393.05 | 216.79 | 176.26 | 0.00 | 0.00 |
February | 561.63 | 471.12 | 481.98 | 294.52 | 187.46 | 0.00 | 0.00 |
March | 924.54 | 341.29 | 720.22 | 441.96 | 278.26 | 0.00 | 0.00 |
April | 1207.20 | 346.43 | 904.78 | 559.94 | 344.85 | 0.00 | 0.00 |
May | 1377.01 | 283.42 | 1011.10 | 586.78 | 424.32 | 0.00 | 0.00 |
June | 1532.78 | 243.87 | 1080.41 | 639.91 | 440.50 | 0.00 | 0.00 |
July | 1454.45 | 198.38 | 1006.56 | 572.92 | 433.64 | 0.00 | 0.00 |
August | 1347.10 | 194.59 | 926.03 | 509.73 | 416.29 | 0.00 | 0.00 |
September | 909.20 | 298.90 | 678.20 | 375.37 | 302.83 | 0.00 | 0.00 |
October | 742.02 | 395.70 | 587.23 | 395.55 | 191.69 | 0.00 | 0.00 |
November | 505.04 | 426.85 | 420.87 | 232.11 | 188.76 | 0.00 | 0.00 |
December | 372.52 | 483.21 | 346.39 | 184.33 | 162.05 | 0.00 | 0.00 |
Annual Sum or Average | 945.89 | 353.59 | 714.33 | 418.13 | 296.20 | 0.00 | 0.00 |
Minimum of Months | 372.52 | 194.59 | 346.39 | 184.33 | 162.05 | 0.00 | 0.00 |
Maximum of Months | 1532.78 | 567.51 | 1080.41 | 639.91 | 440.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9731.84 | 8810.87 | 1822.58 | 1025.18 | 797.40 | 0.00 | 0.00 |
February | 12002.98 | 6988.03 | 2203.25 | 1355.20 | 848.05 | 0.00 | 0.00 |
March | 17175.82 | 3522.53 | 3234.96 | 1976.14 | 1258.83 | 0.00 | 0.00 |
April | 21495.21 | 3486.86 | 4035.11 | 2475.05 | 1560.06 | 0.00 | 0.00 |
May | 25942.30 | 3050.33 | 4495.54 | 2575.93 | 1919.61 | 0.00 | 0.00 |
June | 35118.13 | 3452.99 | 4797.07 | 2804.29 | 1992.79 | 0.00 | 0.00 |
July | 35196.23 | 3761.09 | 4476.19 | 2514.43 | 1961.76 | 0.00 | 0.00 |
August | 34015.02 | 3638.80 | 4126.34 | 2243.04 | 1883.29 | 0.00 | 0.00 |
September | 19597.84 | 3689.14 | 3042.60 | 1672.64 | 1369.97 | 0.00 | 0.00 |
October | 13419.57 | 3925.11 | 2652.20 | 1785.02 | 867.18 | 0.00 | 0.00 |
November | 10032.04 | 4664.39 | 1941.40 | 1087.45 | 853.94 | 0.00 | 0.00 |
December | 8374.35 | 6481.60 | 1620.29 | 887.17 | 733.12 | 0.00 | 0.00 |
Annual Sum or Average | 20227.09 | 4611.96 | 3209.44 | 1869.43 | 1340.01 | 0.00 | 0.00 |
Minimum of Months | 8374.35 | 3050.33 | 1620.29 | 887.17 | 733.12 | 0.00 | 0.00 |
Maximum of Months | 35196.23 | 8810.87 | 4797.07 | 2804.29 | 1992.79 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.269306E+09 | 0.969709E+09 | 0.362139E+09 | 0.134380E+09 | 0.227759E+09 | 0.00 | 0.00 |
February | 0.387571E+09 | 0.698662E+09 | 0.370819E+09 | 0.138774E+09 | 0.232045E+09 | 0.00 | 0.00 |
March | 0.777716E+09 | 0.482635E+09 | 0.598312E+09 | 0.233135E+09 | 0.365176E+09 | 0.00 | 0.00 |
April | 0.951342E+09 | 0.447433E+09 | 0.660751E+09 | 0.240911E+09 | 0.419839E+09 | 0.00 | 0.00 |
May | 0.109817E+10 | 0.352662E+09 | 0.714045E+09 | 0.212862E+09 | 0.501183E+09 | 0.00 | 0.00 |
June | 0.127360E+10 | 0.257909E+09 | 0.734598E+09 | 0.226576E+09 | 0.508021E+09 | 0.00 | 0.00 |
July | 0.127941E+10 | 0.208536E+09 | 0.715017E+09 | 0.209265E+09 | 0.505752E+09 | 0.00 | 0.00 |
August | 0.124170E+10 | 0.191986E+09 | 0.685389E+09 | 0.200437E+09 | 0.484953E+09 | 0.00 | 0.00 |
September | 0.821241E+09 | 0.345979E+09 | 0.532941E+09 | 0.175694E+09 | 0.357247E+09 | 0.00 | 0.00 |
October | 0.615252E+09 | 0.587584E+09 | 0.472948E+09 | 0.199100E+09 | 0.273848E+09 | 0.00 | 0.00 |
November | 0.429057E+09 | 0.633898E+09 | 0.372939E+09 | 0.132175E+09 | 0.240764E+09 | 0.00 | 0.00 |
December | 0.279076E+09 | 0.782417E+09 | 0.323086E+09 | 0.111785E+09 | 0.211301E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.942345E+10 | 0.595941E+10 | 0.654298E+10 | 0.221509E+10 | 0.432789E+10 | 0.00 | 0.00 |
Minimum of Months | 0.269306E+09 | 0.191986E+09 | 0.323086E+09 | 0.111785E+09 | 0.211301E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127941E+10 | 0.969709E+09 | 0.734598E+09 | 0.240911E+09 | 0.508021E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104970E+10 | 0.152002E+10 | 0.105275E+10 | 0.580649E+09 | 0.472100E+09 | 0.00 | 0.00 |
February | 0.135869E+10 | 0.113974E+10 | 0.116600E+10 | 0.712502E+09 | 0.453501E+09 | 0.00 | 0.00 |
March | 0.247628E+10 | 0.914118E+09 | 0.192905E+10 | 0.118376E+10 | 0.745288E+09 | 0.00 | 0.00 |
April | 0.312905E+10 | 0.897945E+09 | 0.234520E+10 | 0.145136E+10 | 0.893839E+09 | 0.00 | 0.00 |
May | 0.368819E+10 | 0.759109E+09 | 0.270814E+10 | 0.157164E+10 | 0.113650E+10 | 0.00 | 0.00 |
June | 0.397297E+10 | 0.632116E+09 | 0.280043E+10 | 0.165866E+10 | 0.114177E+10 | 0.00 | 0.00 |
July | 0.389560E+10 | 0.531336E+09 | 0.269598E+10 | 0.153452E+10 | 0.116146E+10 | 0.00 | 0.00 |
August | 0.360808E+10 | 0.521190E+09 | 0.248028E+10 | 0.136527E+10 | 0.111500E+10 | 0.00 | 0.00 |
September | 0.235664E+10 | 0.774743E+09 | 0.175789E+10 | 0.972969E+09 | 0.784924E+09 | 0.00 | 0.00 |
October | 0.198743E+10 | 0.105985E+10 | 0.157285E+10 | 0.105944E+10 | 0.513411E+09 | 0.00 | 0.00 |
November | 0.130907E+10 | 0.110640E+10 | 0.109090E+10 | 0.601627E+09 | 0.489268E+09 | 0.00 | 0.00 |
December | 0.997769E+09 | 0.129424E+10 | 0.927760E+09 | 0.493717E+09 | 0.434043E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.298295E+11 | 0.111508E+11 | 0.225272E+11 | 0.131861E+11 | 0.934111E+10 | 0.00 | 0.00 |
Minimum of Months | 0.997769E+09 | 0.521190E+09 | 0.927760E+09 | 0.493717E+09 | 0.434043E+09 | 0.00 | 0.00 |
Maximum of Months | 0.397297E+10 | 0.152002E+10 | 0.280043E+10 | 0.165866E+10 | 0.116146E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.260658E+11 | 0.235990E+11 | 0.488160E+10 | 0.274585E+10 | 0.213575E+10 | 0.00 | 0.00 |
February | 0.290376E+11 | 0.169054E+11 | 0.533010E+10 | 0.327849E+10 | 0.205161E+10 | 0.00 | 0.00 |
March | 0.460037E+11 | 0.943476E+10 | 0.866453E+10 | 0.529289E+10 | 0.337164E+10 | 0.00 | 0.00 |
April | 0.557156E+11 | 0.903795E+10 | 0.104590E+11 | 0.641532E+10 | 0.404368E+10 | 0.00 | 0.00 |
May | 0.694839E+11 | 0.816999E+10 | 0.120409E+11 | 0.689938E+10 | 0.514147E+10 | 0.00 | 0.00 |
June | 0.910262E+11 | 0.895016E+10 | 0.124340E+11 | 0.726871E+10 | 0.516530E+10 | 0.00 | 0.00 |
July | 0.942696E+11 | 0.100737E+11 | 0.119890E+11 | 0.673464E+10 | 0.525438E+10 | 0.00 | 0.00 |
August | 0.911058E+11 | 0.974616E+10 | 0.110520E+11 | 0.600776E+10 | 0.504422E+10 | 0.00 | 0.00 |
September | 0.507976E+11 | 0.956225E+10 | 0.788643E+10 | 0.433548E+10 | 0.355095E+10 | 0.00 | 0.00 |
October | 0.359430E+11 | 0.105130E+11 | 0.710364E+10 | 0.478100E+10 | 0.232264E+10 | 0.00 | 0.00 |
November | 0.260030E+11 | 0.120901E+11 | 0.503210E+10 | 0.281868E+10 | 0.221342E+10 | 0.00 | 0.00 |
December | 0.224299E+11 | 0.173603E+11 | 0.433978E+10 | 0.237619E+10 | 0.196359E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.637882E+12 | 0.145443E+12 | 0.101213E+12 | 0.589544E+11 | 0.422587E+11 | 0.00 | 0.00 |
Minimum of Months | 0.224299E+11 | 0.816999E+10 | 0.433978E+10 | 0.237619E+10 | 0.196359E+10 | 0.00 | 0.00 |
Maximum of Months | 0.942696E+11 | 0.235990E+11 | 0.124340E+11 | 0.726871E+10 | 0.525438E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.895719E+09 | -808232845.9 | 0.00 | 0.00 | 744.00 | 0.00 | -87486121.7 | 58.99 | 0.00 | 0.00 |
February | 0.821572E+09 | -744039100.5 | 0.00 | 0.00 | 672.00 | 0.00 | -77532530.2 | 59.00 | 0.00 | 0.00 |
March | 0.921936E+09 | -840263518.0 | 0.00 | 0.00 | 744.00 | 0.00 | -81672457.4 | 58.99 | 0.00 | 0.00 |
April | 0.805273E+09 | -730849793.6 | 0.00 | 0.00 | 720.00 | 0.00 | -74423427.3 | 58.99 | 0.00 | 0.00 |
May | 0.772530E+09 | -699076611.0 | 0.00 | 0.00 | 744.00 | 0.00 | -73453108.6 | 58.99 | 0.00 | 0.00 |
June | 0.710006E+09 | -641065664.8 | 0.00 | 0.00 | 720.00 | 0.00 | -68939924.4 | 58.99 | 0.00 | 0.00 |
July | 0.657913E+09 | -587556753.5 | 0.00 | 0.00 | 744.00 | 0.00 | -70356133.5 | 58.99 | 0.00 | 0.00 |
August | 0.699348E+09 | -628940450.3 | 0.00 | 0.00 | 744.00 | 0.00 | -70407480.3 | 58.99 | 0.00 | 0.00 |
September | 0.682650E+09 | -613266603.5 | 0.00 | 0.00 | 720.00 | 0.00 | -69383694.6 | 58.99 | 0.00 | 0.00 |
October | 0.741921E+09 | -665288798.9 | 0.00 | 0.00 | 744.00 | 0.00 | -76631837.6 | 58.99 | 0.00 | 0.00 |
November | 0.775116E+09 | -695376271.6 | 0.00 | 0.00 | 720.00 | 0.00 | -79739371.4 | 58.99 | 0.00 | 0.00 |
December | 0.862330E+09 | -775885235.0 | 0.00 | 0.00 | 744.00 | 0.00 | -86444427.0 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.934631E+10 | -0.842984E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -916470513.9 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.657913E+09 | -840263518.0 | 0.00 | 0.00 | 672.00 | 0.00 | -87486121.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.921936E+09 | -587556753.5 | 0.00 | 0.00 | 744.00 | 0.00 | -68939924.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.81 | 0.50 | 08-JAN-11:30 | 136.69 | 0.00 | 0.00 | 4.67 | 109.92 | 0.00 | 0.00 | 0.00 |
February | 263.00 | 0.79 | 0.50 | 01-FEB-14:20 | 147.62 | 0.00 | 0.00 | 22.17 | 119.77 | 0.00 | 0.00 | 6.33 |
March | 351.67 | 0.72 | 0.50 | 01-MAR-13:09 | 1890.93 | 0.00 | 0.00 | 110.00 | 154.89 | 0.00 | 0.00 | 23.83 |
April | 369.33 | 0.71 | 0.50 | 01-APR-11:09 | 227.20 | 0.00 | 0.00 | 100.83 | 180.59 | 0.00 | 0.00 | 59.83 |
May | 407.00 | 0.68 | 0.50 | 01-MAY-09:00 | 275.87 | 0.00 | 0.00 | 150.67 | 2357.38 | 0.00 | 0.00 | 133.00 |
June | 411.67 | 0.68 | 0.50 | 01-JUN-10:09 | 287.77 | 0.00 | 0.00 | 163.00 | 1597.69 | 0.00 | 0.00 | 100.67 |
July | 411.00 | 0.68 | 0.50 | 01-JUL-10:09 | 289.98 | 0.00 | 0.00 | 171.33 | 1423.43 | 0.00 | 0.00 | 113.00 |
August | 390.50 | 0.67 | 0.50 | 01-AUG-11:09 | 282.84 | 0.00 | 0.00 | 164.67 | 1195.64 | 0.00 | 0.00 | 134.67 |
September | 298.50 | 0.71 | 0.50 | 01-SEP-10:39 | 216.86 | 0.00 | 0.00 | 75.17 | 174.88 | 0.00 | 0.00 | 40.00 |
October | 293.50 | 0.78 | 0.50 | 01-OCT-11:09 | 153.92 | 0.00 | 0.00 | 25.83 | 1197.08 | 0.00 | 0.00 | 39.67 |
November | 299.00 | 0.79 | 0.50 | 02-NOV-10:00 | 460.10 | 0.00 | 0.00 | 25.83 | 114.07 | 0.00 | 0.00 | 0.00 |
December | 285.17 | 0.79 | 0.50 | 28-DEC-12:20 | 1388.95 | 0.00 | 0.00 | 68.00 | 102.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4071.00 | 0.73 | 474.42 | 0.00 | 0.00 | 1082.17 | 815.69 | 0.00 | 0.00 | 651.00 | ||
Minimum of Months | 263.00 | 0.67 | 0.50 | 136.69 | 0.00 | 0.00 | 4.67 | 102.80 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 411.67 | 0.81 | 0.50 | 1890.93 | 0.00 | 0.00 | 171.33 | 2357.38 | 0.00 | 0.00 | 134.67 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.68 | 0.50 | 01-JAN-10:50 | 162.73 | 10.92 | 0.00 | 83.33 | 135.93 | 14.37 | 1.00 | 55.67 |
February | 263.00 | 0.68 | 0.50 | 01-FEB-13:39 | 173.57 | 10.64 | 0.00 | 83.50 | 142.81 | 14.15 | 6.33 | 58.67 |
March | 351.67 | 0.62 | 0.50 | 01-MAR-09:09 | 226.65 | 12.23 | 0.00 | 173.33 | 189.08 | 15.86 | 33.33 | 133.33 |
April | 369.33 | 0.61 | 0.50 | 01-APR-09:39 | 1271.89 | 14.06 | 33.83 | 214.67 | 224.01 | 16.35 | 57.83 | 166.67 |
May | 407.00 | 0.59 | 0.50 | 01-MAY-07:49 | 305.78 | 13.59 | 0.00 | 270.67 | 262.74 | 17.21 | 80.00 | 226.50 |
June | 411.67 | 0.59 | 0.50 | 01-JUN-07:19 | 308.95 | 13.53 | 0.00 | 274.17 | 265.93 | 17.13 | 84.33 | 224.17 |
July | 411.00 | 0.59 | 0.50 | 01-JUL-08:39 | 315.84 | 13.78 | 0.00 | 277.17 | 271.49 | 17.42 | 92.83 | 228.33 |
August | 390.50 | 0.58 | 0.50 | 01-AUG-08:09 | 959.44 | 15.08 | 33.83 | 270.50 | 274.36 | 17.64 | 92.00 | 224.50 |
September | 298.50 | 0.61 | 0.50 | 01-SEP-07:00 | 254.83 | 12.83 | 0.00 | 200.50 | 211.37 | 16.52 | 47.00 | 151.50 |
October | 293.50 | 0.66 | 0.50 | 01-OCT-10:39 | 1185.78 | 13.03 | 32.33 | 119.50 | 886.77 | 16.69 | 46.00 | 96.00 |
November | 299.00 | 0.66 | 0.50 | 01-NOV-09:20 | 168.36 | 11.20 | 0.00 | 86.17 | 303.36 | 16.66 | 30.17 | 79.17 |
December | 285.17 | 0.69 | 0.50 | 01-DEC-11:09 | 152.88 | 10.92 | 0.00 | 70.33 | 127.24 | 14.37 | 0.00 | 36.83 |
Annual Sum or Average | 4071.00 | 0.63 | 470.78 | 12.83 | 100.00 | 2123.83 | 273.10 | 16.34 | 570.83 | 1681.33 | ||
Minimum of Months | 263.00 | 0.58 | 0.50 | 152.88 | 10.64 | 0.00 | 70.33 | 127.24 | 14.15 | 0.00 | 36.83 | |
Maximum of Months | 411.67 | 0.69 | 0.50 | 1271.89 | 15.08 | 33.83 | 277.17 | 886.77 | 17.64 | 92.83 | 228.33 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.85 | 0.65 | 29-JAN-16:30 | 227.96 | 21.55 | 95.33 | 21.50 | 84.01 | 19.22 | 57.17 | 0.00 |
February | 263.00 | 0.83 | 0.61 | 11-FEB-17:10 | 338.75 | 22.08 | 109.00 | 34.33 | 117.65 | 20.52 | 92.67 | 6.33 |
March | 351.67 | 0.80 | 0.61 | 02-MAR-17:19 | 237.74 | 21.62 | 143.17 | 44.33 | 193.36 | 22.78 | 155.33 | 28.33 |
April | 369.33 | 0.80 | 0.61 | 03-APR-17:10 | 212.23 | 19.98 | 133.50 | 34.83 | 245.34 | 21.72 | 171.00 | 37.83 |
May | 407.00 | 0.77 | 0.61 | 01-MAY-15:20 | 236.69 | 20.24 | 146.83 | 50.00 | 256.94 | 21.47 | 189.33 | 54.50 |
June | 411.67 | 0.77 | 0.61 | 01-JUN-15:09 | 244.59 | 20.10 | 141.67 | 56.17 | 218.91 | 21.41 | 199.33 | 42.83 |
July | 411.00 | 0.77 | 0.61 | 02-JUL-14:00 | 245.02 | 20.19 | 147.33 | 62.67 | 212.44 | 21.44 | 197.33 | 50.17 |
August | 390.50 | 0.76 | 0.61 | 01-AUG-14:00 | 251.67 | 20.74 | 167.67 | 69.50 | 255.14 | 21.84 | 203.00 | 58.50 |
September | 298.50 | 0.78 | 0.61 | 03-SEP-15:09 | 312.11 | 21.89 | 130.83 | 48.83 | 269.65 | 22.66 | 145.83 | 37.00 |
October | 293.50 | 0.82 | 0.61 | 01-OCT-16:10 | 313.36 | 21.96 | 113.83 | 35.17 | 246.60 | 22.20 | 111.00 | 27.17 |
November | 299.00 | 0.84 | 0.64 | 01-NOV-15:20 | 265.44 | 22.25 | 112.33 | 28.67 | 91.68 | 19.39 | 78.83 | 0.00 |
December | 285.17 | 0.86 | 0.66 | 26-DEC-15:30 | 218.68 | 21.30 | 84.67 | 17.83 | 80.60 | 19.14 | 51.33 | 0.00 |
Annual Sum or Average | 4071.00 | 0.80 | 255.52 | 21.04 | 1526.17 | 503.83 | 196.24 | 21.24 | 1652.17 | 342.67 | ||
Minimum of Months | 263.00 | 0.76 | 0.61 | 212.23 | 19.98 | 84.67 | 17.83 | 80.60 | 19.14 | 51.33 | 0.00 | |
Maximum of Months | 411.67 | 0.86 | 0.66 | 338.75 | 22.25 | 167.67 | 69.50 | 269.65 | 22.78 | 203.00 | 58.50 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.674021E+10 | 26625.85 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.452733E+10 | 26625.85 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131524E+10 | 26625.85 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.229955E+09 | 26625.85 | 06-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 305138.42 | 261.04 | 11-MAY-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234249E+09 | 26625.85 | 26-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148434E+10 | 26625.85 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386126E+10 | 26625.85 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.674021E+10 | 26625.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.211752E+11 | 83323.61 | 04-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120860E+11 | 83323.61 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.329539E+09 | 20564.40 | 23-MAR-00:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171543E+10 | 83323.61 | 22-NOV-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104257E+11 | 83323.61 | 02-DEC-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.457319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.211752E+11 | 83323.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.421441E+11 | 92023.95 | 07-JAN-18:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.252325E+11 | 128684.64 | 12-FEB-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.544558E+10 | 40188.52 | 03-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.728222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.421441E+11 | 128684.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 23458482.87 | 23458482.87 | 2111.72 | 28-FEB-15:00 | 2111.72 | 0.00 |
March | 0.00 | 0.00 | 0.286472E+09 | 0.236756E+09 | 5990.40 | 30-MAR-16:00 | 5210.40 | 0.00 |
April | 0.00 | 0.00 | 0.169760E+10 | 0.147158E+10 | 7344.76 | 12-APR-16:00 | 7344.76 | 0.00 |
May | 0.00 | 0.00 | 0.459224E+10 | 0.354201E+10 | 23666.26 | 31-MAY-05:02 | 11474.50 | 0.00 |
June | 0.00 | 0.00 | 0.946609E+10 | 0.702643E+10 | 25656.91 | 26-JUN-05:01 | 12031.73 | 0.00 |
July | 0.00 | 0.00 | 0.108490E+11 | 0.769688E+10 | 26065.30 | 27-JUL-05:01 | 9945.66 | 0.00 |
August | 0.00 | 0.00 | 0.125160E+11 | 0.870291E+10 | 26519.27 | 24-AUG-05:01 | 14113.26 | 0.00 |
September | 0.00 | 0.00 | 0.711315E+10 | 0.521226E+10 | 25114.24 | 07-SEP-05:01 | 16222.88 | 0.00 |
October | 0.00 | 0.00 | 0.171296E+10 | 0.122692E+10 | 25296.63 | 19-OCT-05:03 | 9512.39 | 0.00 |
November | 0.00 | 0.00 | 44291055.59 | 36338898.00 | 1875.85 | 02-NOV-14:10 | 1395.32 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.483013E+11 | 0.351755E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125160E+11 | 0.870291E+10 | 26519.27 | 16222.88 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.765525E+09 | 0.699472E+09 | 62647.90 | 17-APR-17:35 | 58785.63 | 0.00 |
May | 0.00 | 0.00 | 0.557578E+10 | 0.413841E+10 | 71649.95 | 21-MAY-10:55 | 41183.92 | 0.00 |
June | 0.00 | 0.00 | 0.208644E+11 | 0.147086E+11 | 68556.27 | 18-JUN-14:03 | 48926.33 | 0.00 |
July | 0.00 | 0.00 | 0.274919E+11 | 0.189579E+11 | 76437.94 | 09-JUL-08:65 | 34393.67 | 0.00 |
August | 0.00 | 0.00 | 0.303292E+11 | 0.200418E+11 | 72270.75 | 11-AUG-17:10 | 45834.55 | 0.00 |
September | 0.00 | 0.00 | 0.998134E+10 | 0.676968E+10 | 77538.21 | 17-SEP-11:25 | 37457.83 | 0.00 |
October | 0.00 | 0.00 | 0.439138E+09 | 0.284702E+09 | 12787.52 | 11-OCT-14:10 | 7969.01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.954473E+11 | 0.656005E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.303292E+11 | 0.200418E+11 | 77538.21 | 58785.63 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.394586E+09 | 0.04 | 302.98 | 03-JAN-04:00 | 0.08 |
February | 0.218438E+09 | 0.02 | 302.98 | 01-FEB-06:50 | 0.08 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.119458E+09 | 0.01 | 302.98 | 02-DEC-04:53 | 0.08 |
Annual Sum or Average | 0.732481E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.394586E+09 | 0.04 | 302.98 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.667928E+09 | 0.38 | 1169.97 | 02-JAN-06:01 | 0.94 |
February | 0.565111E+09 | 0.34 | 1169.97 | 01-FEB-06:01 | 0.94 |
March | 0.541177E+09 | 0.25 | 1169.97 | 01-MAR-06:01 | 0.94 |
April | 0.470523E+09 | 0.22 | 1169.97 | 06-APR-05:01 | 0.94 |
May | 0.485550E+09 | 0.22 | 1169.97 | 19-MAY-05:02 | 0.93 |
June | 0.523859E+09 | 0.24 | 1169.97 | 01-JUN-05:02 | 0.93 |
July | 0.541265E+09 | 0.24 | 1169.97 | 01-JUL-05:01 | 0.92 |
August | 0.595359E+09 | 0.26 | 1169.97 | 01-AUG-05:01 | 0.92 |
September | 0.486246E+09 | 0.23 | 1169.97 | 01-SEP-05:01 | 0.93 |
October | 0.471175E+09 | 0.21 | 1169.97 | 19-OCT-05:03 | 0.92 |
November | 0.489728E+09 | 0.23 | 1169.97 | 01-NOV-05:01 | 0.94 |
December | 0.580388E+09 | 0.29 | 1169.97 | 01-DEC-06:01 | 0.94 |
Annual Sum or Average | 0.641831E+10 | 0.26 | |||
Minimum of Months | 0.470523E+09 | 0.21 | 1169.97 | 0.92 | |
Maximum of Months | 0.667928E+09 | 0.38 | 1169.97 | 0.94 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168545E+10 | 0.52 | 2720.02 | 04-JAN-06:01 | 0.91 |
February | 0.133703E+10 | 0.40 | 2720.02 | 02-FEB-06:01 | 0.91 |
March | 0.117212E+10 | 0.23 | 1472.04 | 22-MAR-06:05 | 0.66 |
April | 0.107854E+10 | 0.21 | 1088.01 | 13-APR-12:50 | 0.55 |
May | 0.114643E+10 | 0.22 | 2101.86 | 19-MAY-17:43 | 0.80 |
June | 0.127571E+10 | 0.28 | 2720.02 | 04-JUN-13:13 | 0.90 |
July | 0.136072E+10 | 0.30 | 2720.02 | 02-JUL-12:13 | 0.90 |
August | 0.142964E+10 | 0.32 | 2720.02 | 01-AUG-17:06 | 0.90 |
September | 0.114085E+10 | 0.24 | 2720.02 | 07-SEP-17:08 | 0.90 |
October | 0.107713E+10 | 0.20 | 1088.01 | 10-OCT-12:30 | 0.54 |
November | 0.108560E+10 | 0.25 | 2720.02 | 22-NOV-05:53 | 0.91 |
December | 0.139037E+10 | 0.45 | 2720.02 | 02-DEC-04:53 | 0.91 |
Annual Sum or Average | 0.151796E+11 | 0.30 | |||
Minimum of Months | 0.107713E+10 | 0.20 | 1088.01 | 0.54 | |
Maximum of Months | 0.168545E+10 | 0.52 | 2720.02 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.667928E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.570492E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.606030E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.849381E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.148494E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.257310E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.289099E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.327479E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.199160E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.839398E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.499820E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.580388E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.168288E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.499820E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.327479E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.168545E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.133703E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.117212E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.126302E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.243526E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.603497E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.761906E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.823284E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.338334E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.118002E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.108560E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.139037E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.368191E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.108560E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.823284E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.667928E+09 | 0.00 | 0.674021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.565111E+09 | 23458482.87 | 0.452733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.541177E+09 | 0.286472E+09 | 0.131524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.470523E+09 | 0.169760E+10 | 0.229955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.485550E+09 | 0.457984E+10 | 305138.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.523859E+09 | 0.944650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.541265E+09 | 0.108323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.595359E+09 | 0.124998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.486246E+09 | 0.708758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471175E+09 | 0.171130E+10 | 0.234249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.489728E+09 | 44291055.59 | 0.148434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.580388E+09 | 0.00 | 0.386126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.641831E+10 | 0.482091E+11 | 0.183929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.470523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.667928E+09 | 0.124998E+11 | 0.674021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.168545E+10 | 0.00 | 0.211752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133703E+10 | 0.00 | 0.120860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117212E+10 | 0.00 | 0.329539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107854E+10 | 0.752871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114643E+10 | 0.550613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127571E+10 | 0.208110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136072E+10 | 0.274765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142964E+10 | 0.303292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114085E+10 | 0.993714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107713E+10 | 0.439138E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108560E+10 | 0.00 | 0.171543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139037E+10 | 0.00 | 0.104257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151796E+11 | 0.952519E+11 | 0.457319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168545E+10 | 0.303292E+11 | 0.211752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.667928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.565111E+09 | 0.00 | 0.00 | 0.00 | 5381194.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.541177E+09 | 0.00 | 0.00 | 0.00 | 64853863.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.470523E+09 | 0.00 | 0.00 | 0.00 | 0.378857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.485550E+09 | 0.00 | 0.00 | 0.00 | 0.999392E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.523859E+09 | 0.00 | 0.00 | 0.00 | 0.204924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.541265E+09 | 0.00 | 0.00 | 0.00 | 0.234972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.595359E+09 | 0.00 | 0.00 | 0.00 | 0.267943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.486246E+09 | 0.00 | 0.00 | 0.00 | 0.150535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471175E+09 | 0.00 | 0.00 | 0.00 | 0.368224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.489728E+09 | 0.00 | 0.00 | 0.00 | 10092718.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.580388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.641831E+10 | 0.00 | 0.00 | 0.00 | 0.104105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.470523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.667928E+09 | 0.00 | 0.00 | 0.00 | 0.267943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.168545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107854E+10 | 0.00 | 0.00 | 0.00 | 0.184487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114643E+10 | 0.00 | 0.00 | 0.00 | 0.128883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127571E+10 | 0.00 | 0.00 | 0.00 | 0.475927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136072E+10 | 0.00 | 0.00 | 0.00 | 0.625833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142964E+10 | 0.00 | 0.00 | 0.00 | 0.680320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114085E+10 | 0.00 | 0.00 | 0.00 | 0.224249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107713E+10 | 0.00 | 0.00 | 0.00 | 0.102895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151796E+11 | 0.00 | 0.00 | 0.00 | 0.216395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168545E+10 | 0.00 | 0.00 | 0.00 | 0.680320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 46067400.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187611E+10 | 0.00 | 0.00 | 0.12 |
February | 0.135317E+09 | 36764.10 | 0.00 | 26490.94 | 0.00 | 0.122157E+10 | 16245873.27 | 0.00 | 0.14 |
March | 0.539908E+09 | 9761304.49 | 0.00 | 286423.91 | 219151.71 | 0.378253E+09 | 0.287044E+09 | 0.00 | 0.20 |
April | 0.296841E+09 | 45251483.31 | 0.00 | 1304062.51 | 0.00 | 42313946.64 | 0.745612E+09 | 0.00 | 0.30 |
May | 27565120.52 | 0.370038E+09 | 0.00 | 2335338.67 | 0.00 | 0.00 | 0.895084E+09 | 0.00 | 0.34 |
June | 816526.50 | 0.132150E+10 | 0.00 | 3886309.74 | 0.00 | 0.00 | 0.263409E+09 | 0.00 | 0.22 |
July | 19856.03 | 0.174454E+10 | 0.00 | 3058658.56 | 0.00 | 0.00 | 73726643.39 | 0.00 | 0.15 |
August | 0.00 | 0.205378E+10 | 0.00 | 2738161.20 | 0.00 | 0.00 | 26442404.80 | 0.00 | 0.15 |
September | 2381205.52 | 0.846297E+09 | 0.00 | 3354086.36 | 0.00 | 0.00 | 0.605212E+09 | 0.00 | 0.26 |
October | 0.360641E+09 | 0.143408E+09 | 0.00 | 1805529.38 | 0.00 | 66097776.91 | 0.108171E+10 | 0.00 | 0.30 |
November | 0.476224E+09 | 0.00 | 187449.34 | 301207.42 | 0.00 | 0.461358E+09 | 0.349154E+09 | 2020.20 | 0.18 |
December | 0.216341E+09 | 0.00 | 98306.14 | 0.00 | 61726.77 | 0.116742E+10 | 0.00 | 981.77 | 0.12 |
Annual Sum or Average | 0.210212E+10 | 0.653461E+10 | 285755.48 | 19096268.68 | 280878.48 | 0.521312E+10 | 0.434364E+10 | 3001.97 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.539908E+09 | 0.205378E+10 | 187449.34 | 3886309.74 | 219151.71 | 0.187611E+10 | 0.108171E+10 | 2020.20 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.217805E+10 | 0.00 | 0.00 | 0.00 | 65859.73 | 0.294015E+10 | 0.00 | 0.00 | 0.17 |
February | 0.162834E+10 | 0.00 | 0.00 | 0.00 | 10862600.17 | 0.176914E+10 | 0.00 | 0.00 | 0.18 |
March | 0.278157E+10 | 0.00 | 0.00 | 0.00 | 20915373.09 | 54717086.36 | 0.00 | 0.00 | 0.19 |
April | 0.231536E+10 | 3891287.13 | 0.00 | 682330.57 | 1135274.78 | 0.00 | 0.337577E+09 | 0.00 | 0.23 |
May | 0.144048E+10 | 0.382201E+09 | 0.00 | 1828085.63 | 0.00 | 0.00 | 0.938321E+09 | 0.00 | 0.26 |
June | 0.206446E+09 | 0.291824E+10 | 0.00 | 3466133.40 | 0.00 | 0.00 | 0.918628E+09 | 0.00 | 0.27 |
July | 0.246556E+09 | 0.436711E+10 | 0.00 | 1510008.20 | 0.00 | 0.00 | 0.433016E+09 | 0.00 | 0.22 |
August | 43122716.76 | 0.508295E+10 | 0.00 | 1894919.53 | 0.00 | 0.00 | 0.654338E+09 | 0.00 | 0.25 |
September | 0.872498E+09 | 0.121195E+10 | 0.00 | 3769804.32 | 4186329.74 | 0.00 | 0.132406E+10 | 0.00 | 0.30 |
October | 0.314341E+10 | 36939329.04 | 0.00 | 127400.95 | 160324.07 | 0.00 | 0.170323E+09 | 0.00 | 0.19 |
November | 0.271032E+10 | 0.00 | 0.00 | 0.00 | 13229622.96 | 0.109193E+09 | 0.00 | 0.00 | 0.17 |
December | 0.253010E+10 | 0.00 | 0.00 | 0.00 | 18013672.49 | 0.747885E+09 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.200963E+11 | 0.140033E+11 | 0.00 | 13278682.59 | 68569057.04 | 0.562108E+10 | 0.477626E+10 | 0.00 | 0.22 |
Minimum of Months | 43122716.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.314341E+10 | 0.508295E+10 | 0.00 | 3769804.32 | 20915373.09 | 0.294015E+10 | 0.132406E+10 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.515592E+12 | 0.542455E+11 | 0.00 | 0.705010E+10 | 0.177077E+11 |
February | 0.538002E+12 | 0.420648E+11 | 0.00 | 0.480345E+10 | 0.106192E+11 |
March | 0.861347E+12 | 0.340634E+11 | 0.00 | 0.404626E+10 | 0.102355E+10 |
April | 0.101670E+13 | 0.327943E+11 | 0.00 | 0.372717E+10 | 0.312107E+10 |
May | 0.115496E+13 | 0.339691E+11 | 0.00 | 0.259500E+10 | 0.124564E+11 |
June | 0.115820E+13 | 0.414338E+11 | 0.00 | -0.280384E+10 | 0.371390E+11 |
July | 0.111895E+13 | 0.492412E+11 | 0.00 | -0.534794E+10 | 0.469490E+11 |
August | 0.103742E+13 | 0.461481E+11 | 0.00 | -0.639922E+10 | 0.523279E+11 |
September | 0.778157E+12 | 0.311138E+11 | 0.00 | 0.765335E+09 | 0.208423E+11 |
October | 0.706452E+12 | 0.389465E+11 | 0.00 | 0.464676E+10 | 0.272068E+10 |
November | 0.476440E+12 | 0.313855E+11 | 0.00 | 0.409904E+10 | 0.132547E+10 |
December | 0.420236E+12 | 0.390570E+11 | 0.00 | 0.467014E+10 | 0.644250E+10 |
Annual Sum or Average | 0.978245E+13 | 0.474463E+12 | 0.00 | 0.218523E+11 | 0.212675E+12 |
Minimum of Months | 0.420236E+12 | 0.311138E+11 | 0.00 | -0.639922E+10 | 0.102355E+10 |