Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 10:43:17
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 479.68 | 99.21 | 99.21 |
Net Site Energy | 342.74 | 70.89 | 70.89 |
Total Source Energy | 1519.15 | 314.19 | 314.19 |
Net Source Energy | 1085.47 | 224.50 | 224.50 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 151.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 68.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 42.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 59.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 479.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 151.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 68.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 42.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 32.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 26.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 151.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 68.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 42.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 59.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 22.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 22.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 48.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 99.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 22.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 48.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 99.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 142.840 | 29.78 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -5.90 | -1.2 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 136.938 | 28.55 |
Electricity Coming From Utility | 350.282 | 73.02 |
Surplus Electricity Going To Utility | 7.539 | 1.57 |
Net Electricity From Utility | 342.743 | 71.45 |
Total On-Site and Utility Electric Sources | 479.681 | 100.00 |
Total Electricity End Uses | 479.681 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 99.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3636.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE2 FINE STORAGE_DAYLCTRL | ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 119.93 |
Skylight-Roof Ratio [%] | 2.61 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.1633 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.1969 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.1633 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.1969 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.3473 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-JUN-15:50 | - | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18137.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4460.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5270.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1573.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 39477.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 18137.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 4460.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2965.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1573.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 478.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 216.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 133.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 69.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1519.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 99.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 314.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 99.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 14.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 314.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.10 |
ZONE2 FINE STORAGE DIRECT AIR | 2.69 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 0.976836 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 0.976836 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 39959.00 |
PSZ-OFFICE HEATING COIL | 25287.78 |
PSZ-FINE STORAGE HEATING COIL | 119808.23 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.00 | 1.00 | 1.10 |
PSZ-FINE STORAGE | 2.69 | 2.69 | 2.69 | 2.69 | 2.69 | 2.69 | 1.00 | 1.00 | 2.69 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.10 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 2.69 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.10 | 1218.99 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 2.69 | 2878.36 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.10 | 1.10 | 1.10 | 0.726665 | 23539.62 | 25287.78 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 2.69 | 2.69 | 2.69 | 1.78 | 66797.48 | 119808.23 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.10 | 0.550504 | 0.734007 | 23539.62 | 11769.81 | 0.750660 | 0.750660 |
PSZ-FINE STORAGE COOLING COIL | 2.69 | 1.34 | 1.79 | 66797.48 | 33398.74 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE ROOF | FINESTORAGE_SKYLIGHT_1 | FINESTORAGE_SKYLIGHT_6 | FINESTORAGE_SKYLIGHT_7 | FINESTORAGE_SKYLIGHT_8 | FINESTORAGE_SKYLIGHT_9 | FINESTORAGE_SKYLIGHT_10 | FINESTORAGE_SKYLIGHT_5 | FINESTORAGE_SKYLIGHT_4 | FINESTORAGE_SKYLIGHT_3 | FINESTORAGE_SKYLIGHT_2 | FINESTORAGE_SKYLIGHT_14 | FINESTORAGE_SKYLIGHT_13 | FINESTORAGE_SKYLIGHT_12 | FINESTORAGE_SKYLIGHT_11 | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R8C1 | SKYLIGHT_R8C2 | SKYLIGHT_R8C4 | SKYLIGHT_R1C2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C4 | SKYLIGHT_R1C3 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R3C4 | SKYLIGHT_R3C2 | SKYLIGHT_R3C3 | SKYLIGHT_R3C1 | SKYLIGHT_R4C4 | SKYLIGHT_R4C3 | SKYLIGHT_R4C2 | SKYLIGHT_R4C1 | SKYLIGHT_R5C4 | SKYLIGHT_R5C1 | SKYLIGHT_R5C3 | SKYLIGHT_R5C2 | SKYLIGHT_R6C1 | SKYLIGHT_R6C2 | SKYLIGHT_R8C3 | SKYLIGHT_R6C4 | SKYLIGHT_R7C1 | SKYLIGHT_R7C2 | SKYLIGHT_R7C4 | SKYLIGHT_R6C3 | SKYLIGHT_R7C3 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 102 | 78 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 20.81 | 11 | 20 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 47.57 | 6 | 52 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.163 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 14.237 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.197 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.756 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1459.960 | 6.163 | 114.518 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1459.960 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10245.499 | 3.197 | 148.485 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10245.499 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.2405 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.7173 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.6534 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 2.825 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 2.825 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.158 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.394 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.431 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2546 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2546 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.77015739E-08 | 0.38457199E-13 | 0.23136523E-13 | 0.0000000 |
2 | 1 | -5.2160498 | 0.48395528E-04 | -0.66612159E-04 | 0.14765390E-08 |
3 | 0 | 5.4565497 | 0.24045158 | 0.24056658 | |
4 | 2 | 0.53311453E-11 | 0.59398160E-16 | 0.15345153E-15 | 0.0000000 |
5 | 1 | -5.2159564 | 0.46378490E-04 | -0.22332804E-04 | 0.68713370E-11 |
6 | 0 | 5.9333026 | 0.71729982 | 0.71736853 | |
7 | 4 | 0.74747876E-12 | 0.20825084E-15 | -0.25659737E-14 | 0.12362927E-15 |
8 | 3 | -0.37328678E-03 | 0.45238042E-06 | -0.54038165E-04 | 0.14344535E-12 |
9 | 2 | 1.7123825 | 0.10013958E-01 | 1.1198054 | -0.71564441E-04 |
10 | 1 | -7.1648294 | 0.26145347 | -16.966117 | 0.32817431 |
11 | 0 | 5.8918369 | 0.16754891 | 16.285382 | |
12 | 4 | 0.33466332E-12 | 0.89461943E-14 | -0.12859024E-13 | 0.20877214E-15 |
13 | 3 | -0.22871403E-03 | 0.15053116E-05 | -0.31975464E-04 | 0.68322840E-13 |
14 | 2 | 1.3386772 | 0.41030944E-01 | 0.83718830 | -0.43809927E-04 |
15 | 1 | -7.7424045 | 1.2165027 | -15.097018 | 0.25560053 |
16 | 0 | 8.5066984 | 0.84520726 | 16.362604 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 8.2334813 | 8.2334813 | 8.2334813 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.12859024E-13 | 0.89461943E-14 | 0.33466332E-12 | 0.20877214E-15 |
85 | 3 | -0.31975464E-04 | 0.15053116E-05 | -0.22871403E-03 | 0.68322840E-13 |
86 | 2 | 0.83718830 | 0.41030944E-01 | 1.3386772 | -0.43809927E-04 |
87 | 1 | -15.097018 | 1.2165027 | -7.7424045 | 0.25560053 |
88 | 0 | 16.362604 | 0.84520726 | 8.5066984 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_SOUTH_0.219 | 34 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.220 | ||
2 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.219 | 35 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.220 | ||
3 | NONRESWINDOW_U_0.503_SHGC_EAST_0.219 | 36 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.220 | ||
4 | NONRESWINDOW_U_0.503_SHGC_WEST_0.219 | 37 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.220 | ||
5 | SKYLIGHT_U_0.7_SHGC_0.3 | 38 | 1 | VerySmooth | 3.979 | 3.979 | 1.000 | 0.303 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93472E-002 | 0.13026 | 0.64157 | 0.64157 | 0.21900 | 0.16846 | 0.25665 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93472E-002 | 0.13026 | 0.64157 | 0.64157 | 0.21900 | 0.16846 | 0.25665 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93472E-002 | 0.13026 | 0.64157 | 0.64157 | 0.21900 | 0.16846 | 0.25665 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93472E-002 | 0.13026 | 0.64157 | 0.64157 | 0.21900 | 0.16846 | 0.25665 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.17728 | 0.47032 | 0.47032 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 2.40661E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE2 FINE STORAGE | 14 | 0 |
3 | ZONE3 BULK STORAGE | 32 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE2 FINE STORAGE | 0 | |
3 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.838 | 0.300 | 0.402 |
2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.799 | 0.390 | 0.214 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.289 | 1.219E-003 | 1.882E-003 | 1.029 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.7374E-005 |
2 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.2001E-004 |
3 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0595E-005 |
4 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.6642E-004 |
5 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.6710E-005 |
6 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4963E-004 |
7 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.0157E-004 |
8 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_1 | ZONE2 FINE STORAGE_DAYLREFPT2 | 4.7234E-004 |
9 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.5898E-004 |
10 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.5604E-004 |
11 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3891E-004 |
12 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.6707E-004 |
13 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.4307E-004 |
14 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.4021E-004 |
15 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4476E-004 |
16 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_6 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.5357E-004 |
17 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.0500E-004 |
18 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1395E-004 |
19 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.5392E-004 |
20 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1611E-004 |
21 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.4720E-004 |
22 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0533E-004 |
23 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0436E-004 |
24 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_7 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.1182E-005 |
25 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.6098E-004 |
26 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.4442E-005 |
27 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.3523E-004 |
28 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.5269E-005 |
29 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.2010E-003 |
30 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.1364E-005 |
31 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.3611E-003 |
32 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_8 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3609E-005 |
33 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.5787E-004 |
34 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1686E-005 |
35 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.1059E-004 |
36 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2371E-005 |
37 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.2534E-004 |
38 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1265E-005 |
39 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1206E-004 |
40 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_9 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8484E-005 |
41 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.1885E-004 |
42 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6884E-005 |
43 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3467E-004 |
44 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7596E-005 |
45 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.0345E-004 |
46 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7712E-005 |
47 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.8883E-004 |
48 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_10 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6707E-005 |
49 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.8218E-004 |
50 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7122E-005 |
51 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.2178E-004 |
52 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7829E-005 |
53 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 4.4471E-004 |
54 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.7884E-005 |
55 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4746E-004 |
56 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_5 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.6794E-005 |
57 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.4805E-003 |
58 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.2431E-005 |
59 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8563E-003 |
60 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.3121E-005 |
61 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.3297E-003 |
62 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.1828E-005 |
63 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1327E-003 |
64 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_4 | ZONE2 FINE STORAGE_DAYLREFPT2 | 5.8762E-005 |
65 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.6884E-003 |
66 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.7279E-005 |
67 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 2.8028E-003 |
68 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.8211E-005 |
69 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.3898E-003 |
70 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 7.3616E-005 |
71 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.6038E-003 |
72 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_3 | ZONE2 FINE STORAGE_DAYLREFPT2 | 6.4693E-005 |
73 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7276E-004 |
74 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2808E-004 |
75 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 5.8604E-004 |
76 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.3134E-004 |
77 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.5279E-004 |
78 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.1715E-004 |
79 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6538E-003 |
80 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_2 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.6639E-005 |
81 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.9719E-004 |
82 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.5756E-004 |
83 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.6927E-004 |
84 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.8200E-004 |
85 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.7468E-004 |
86 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2795E-004 |
87 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT1 | 3.4325E-004 |
88 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_14 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.9096E-004 |
89 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 9.4522E-005 |
90 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.7581E-003 |
91 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.6065E-005 |
92 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 2.0041E-003 |
93 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 8.0881E-005 |
94 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.6364E-003 |
95 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT1 | 1.1412E-004 |
96 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_13 | ZONE2 FINE STORAGE_DAYLREFPT2 | 8.0087E-004 |
97 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.7390E-005 |
98 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2431E-003 |
99 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.4769E-005 |
100 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.5292E-003 |
101 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.2264E-005 |
102 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.9010E-003 |
103 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT1 | 7.1055E-005 |
104 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_12 | ZONE2 FINE STORAGE_DAYLREFPT2 | 3.2128E-003 |
105 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.5689E-005 |
106 | Clear Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0451E-003 |
107 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.3496E-005 |
108 | Clear Turbid Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.0460E-003 |
109 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.1516E-005 |
110 | Intermediate Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2869E-003 |
111 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT1 | 6.8879E-005 |
112 | Overcast Sky | 12/21 | ZONE2 FINE STORAGE_DAYLCTRL | ZONE2 FINE STORAGE | FINESTORAGE_SKYLIGHT_11 | ZONE2 FINE STORAGE_DAYLREFPT2 | 1.2630E-003 |
113 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1729E-005 |
114 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5140E-005 |
115 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8675E-005 |
116 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8978E-005 |
117 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6344E-005 |
118 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4187E-005 |
119 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4598E-005 |
120 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5286E-005 |
121 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2964E-005 |
122 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.7173E-005 |
123 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7330E-005 |
124 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2807E-005 |
125 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.3040E-005 |
126 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9195E-005 |
127 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1685E-005 |
128 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2542E-005 |
129 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1702E-005 |
130 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0598E-005 |
131 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.8582E-005 |
132 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9983E-005 |
133 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5916E-005 |
134 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9484E-005 |
135 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4582E-005 |
136 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1042E-005 |
137 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0976E-004 |
138 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8747E-005 |
139 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1334E-004 |
140 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.8914E-005 |
141 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7139E-005 |
142 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.2640E-005 |
143 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2514E-005 |
144 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.3080E-005 |
145 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2697E-005 |
146 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1954E-004 |
147 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2470E-005 |
148 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2404E-004 |
149 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.7968E-005 |
150 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0539E-004 |
151 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4916E-005 |
152 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6240E-005 |
153 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9545E-005 |
154 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2841E-005 |
155 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8750E-005 |
156 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2475E-005 |
157 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.5931E-005 |
158 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2332E-005 |
159 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.4899E-005 |
160 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1079E-005 |
161 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0570E-004 |
162 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4978E-005 |
163 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0838E-004 |
164 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4083E-005 |
165 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4856E-005 |
166 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.2969E-005 |
167 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.2500E-005 |
168 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7738E-005 |
169 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9382E-005 |
170 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6450E-004 |
171 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8360E-005 |
172 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9586E-004 |
173 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5562E-005 |
174 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2863E-004 |
175 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0532E-005 |
176 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.7293E-004 |
177 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9722E-004 |
178 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5274E-004 |
179 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1815E-004 |
180 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5368E-004 |
181 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7238E-004 |
182 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4948E-004 |
183 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5069E-004 |
184 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0290E-004 |
185 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7587E-004 |
186 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.7334E-005 |
187 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9173E-004 |
188 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5195E-005 |
189 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.5966E-004 |
190 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.5490E-005 |
191 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5061E-004 |
192 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8433E-005 |
193 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2068E-005 |
194 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5218E-005 |
195 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9756E-005 |
196 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4460E-005 |
197 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0087E-005 |
198 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4435E-005 |
199 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.0473E-005 |
200 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3210E-005 |
201 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6592E-004 |
202 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1305E-005 |
203 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.4441E-004 |
204 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6991E-005 |
205 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.9245E-004 |
206 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.0856E-005 |
207 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2387E-004 |
208 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.6113E-005 |
209 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.9862E-004 |
210 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.0008E-004 |
211 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.1106E-003 |
212 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9911E-004 |
213 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7987E-004 |
214 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2884E-004 |
215 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2445E-004 |
216 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5215E-004 |
217 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3927E-004 |
218 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7278E-005 |
219 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3257E-004 |
220 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6065E-005 |
221 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4681E-004 |
222 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6225E-005 |
223 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2708E-004 |
224 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5686E-005 |
225 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5237E-004 |
226 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.8106E-003 |
227 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4773E-004 |
228 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.1033E-003 |
229 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5890E-004 |
230 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.5847E-003 |
231 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2726E-004 |
232 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R3C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.9459E-004 |
233 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6573E-004 |
234 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8103E-005 |
235 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5139E-004 |
236 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6542E-005 |
237 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8216E-004 |
238 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6697E-005 |
239 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9961E-004 |
240 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7482E-005 |
241 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4623E-003 |
242 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7982E-005 |
243 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5267E-003 |
244 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1343E-005 |
245 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7894E-003 |
246 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.7853E-005 |
247 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6165E-003 |
248 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3274E-005 |
249 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6573E-003 |
250 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0196E-004 |
251 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7667E-003 |
252 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.8054E-004 |
253 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9796E-003 |
254 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8396E-004 |
255 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6195E-003 |
256 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.2024E-004 |
257 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7909E-004 |
258 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5815E-003 |
259 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.6627E-004 |
260 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0506E-003 |
261 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9821E-004 |
262 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0355E-003 |
263 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0001E-004 |
264 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R4C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6530E-003 |
265 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3750E-004 |
266 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7224E-005 |
267 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2079E-004 |
268 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5599E-005 |
269 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4190E-004 |
270 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5439E-005 |
271 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9852E-004 |
272 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7461E-005 |
273 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4411E-004 |
274 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.1301E-003 |
275 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2784E-004 |
276 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0463E-003 |
277 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5244E-004 |
278 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3848E-003 |
279 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9891E-004 |
280 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.6031E-003 |
281 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.2212E-004 |
282 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.1064E-005 |
283 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.5222E-004 |
284 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.3946E-005 |
285 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7674E-004 |
286 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7929E-005 |
287 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5919E-003 |
288 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.3045E-005 |
289 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.5679E-004 |
290 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.8682E-004 |
291 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9079E-004 |
292 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.5201E-004 |
293 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.3066E-004 |
294 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2473E-004 |
295 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5949E-003 |
296 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R5C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1554E-004 |
297 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1946E-005 |
298 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9360E-004 |
299 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0455E-005 |
300 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4715E-004 |
301 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.5933E-005 |
302 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.9225E-004 |
303 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2574E-004 |
304 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.7337E-004 |
305 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4363E-004 |
306 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.4474E-004 |
307 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0600E-004 |
308 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.2329E-004 |
309 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4276E-004 |
310 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.3591E-004 |
311 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1039E-004 |
312 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 2.4748E-004 |
313 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2958E-005 |
314 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.6385E-005 |
315 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.7278E-005 |
316 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.4471E-005 |
317 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.2745E-005 |
318 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2789E-005 |
319 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1671E-005 |
320 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R8C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.7584E-005 |
321 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.0134E-005 |
322 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5104E-005 |
323 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.8472E-005 |
324 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3714E-005 |
325 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1842E-005 |
326 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3194E-005 |
327 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.2556E-004 |
328 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.5637E-005 |
329 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8355E-005 |
330 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0633E-004 |
331 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2146E-005 |
332 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.9981E-005 |
333 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0337E-005 |
334 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 8.6987E-005 |
335 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9741E-005 |
336 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C1 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.6869E-004 |
337 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.7208E-005 |
338 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 7.5107E-005 |
339 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2864E-005 |
340 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5201E-005 |
341 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.0450E-005 |
342 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.1999E-005 |
343 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4732E-004 |
344 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C2 | ZONE3 BULK STORAGE_DAYLREFPT2 | 1.0119E-004 |
345 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8025E-005 |
346 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.2673E-005 |
347 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1701E-005 |
348 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1672E-005 |
349 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9027E-005 |
350 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.1038E-005 |
351 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.9684E-005 |
352 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C4 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.3161E-005 |
353 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4030E-004 |
354 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.6859E-005 |
355 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0244E-004 |
356 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1341E-005 |
357 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.3496E-004 |
358 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 5.1154E-005 |
359 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.0983E-004 |
360 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R6C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 6.5702E-005 |
361 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.6922E-005 |
362 | Clear Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.4383E-005 |
363 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.2471E-005 |
364 | Clear Turbid Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.0924E-005 |
365 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.9131E-005 |
366 | Intermediate Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 3.9062E-005 |
367 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4724E-004 |
368 | Overcast Sky | 12/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R7C3 | ZONE3 BULK STORAGE_DAYLREFPT2 | 4.8139E-005 |
369 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7626E-003 |
370 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.3912E-004 |
371 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.4131E-003 |
372 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 3.0688E-004 |
373 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.9967E-003 |
374 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 2.7798E-004 |
375 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 1.5715E-003 |
376 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 2.7835E-004 |
377 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.3704E-004 |
378 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.1537E-003 |
379 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.0768E-004 |
380 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.6482E-003 |
381 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.8109E-004 |
382 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1788E-003 |
383 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.7513E-004 |
384 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1086E-003 |
385 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.2717E-003 |
386 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.7328E-004 |
387 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.7424E-003 |
388 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.4138E-004 |
389 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.0524E-003 |
390 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.0560E-004 |
391 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 1.9727E-003 |
392 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 1.6943E-004 |
393 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.2639E-003 |
394 | Clear Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.7321E-004 |
395 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.7448E-003 |
396 | Clear Turbid Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.4135E-004 |
397 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.0904E-003 |
398 | Intermediate Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.0566E-004 |
399 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 1.9727E-003 |
400 | Overcast Sky | 12/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 1.6943E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11145.43787 | 13374.52545 | 0.91751 | 1.10101 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | 34.69000 | 1.71572E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 1554.18632 | 1865.02359 | 4.30846E-002 | 0.10228 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 34927.52089 | 41913.02507 | 2.24161 | 2.68993 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.42471 | 00:10:00 | 20.10000 | 1.47983E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 | |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71581E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 0.00000 | 0.00000 | 0.00000 | 0.97684 | 00:10:00 | 20.10000 | 1.47983E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 17185.59 | 1.10101 | 1.10101 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 2461.78 | 0.10228 | 0.10228 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 52177.63 | 2.68993 | 2.68993 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 10221.91 | 0.42471 | 0.42471 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10101 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.68993 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.97684 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 0.97684 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 39959.00499 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 0.00000 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.10101 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.10101 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.10101 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.10101 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10101 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.10101 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.68993 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.68993 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.68993 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.68993 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.68993 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 2.68993 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.10101 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 2.68993 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10101 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10101 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1218.99043 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10101 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10101 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10101 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.72667 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10101 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55050 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.73401 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23539.62000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11769.81000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75066 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75066 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23539.62000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25287.77563 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 25287.77563 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.68993 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.68993 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2878.35714 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.68993 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.68993 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.68993 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.77536 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.68993 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.34497 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.79329 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 66797.48000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 33398.74000 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 66797.48000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 119808.22906 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 119808.22906 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 22684.4 | 12.71 | 12.42 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 64706.6 | 12.83 | 12.54 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 1.7735137392E-002 | 1.5635968464E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.1571174712 | 0.2141089069 | Pass | Pass | 0.1089934741 | 0.6380786697 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.9774395638E-002 | 5.3127768392E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 11317.91 | 606.57 | 0.00 | -252.3 | 828.49 | 12500.71 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.595 | 0.653 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.233 | 0.240 | 1393.41 | 1372.60 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.985 | 2.825 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.653 | 0.717 | 3204.84 | 3105.72 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.685 | 2.825 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 1.685 | 2.825 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.503_SHGC_WEST_0.219 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.860 | 0.220 | 0.220 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.503_SHGC_WEST_0.219 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 2.860 | 0.220 | 0.220 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.219 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.860 | 0.220 | 0.220 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.503_SHGC_NORTH_0.219 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 2.860 | 0.220 | 0.220 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINESTORAGE_SKYLIGHT_1 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_6 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_7 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_8 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_9 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_10 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_5 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_4 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_3 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_2 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_14 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_13 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_12 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
FINESTORAGE_SKYLIGHT_11 | SKYLIGHT_U_0.7_SHGC_0.3 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.979 | 0.303 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.838 | 0.300 | 0.402 | No | FINE STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R3C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R4C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R5C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R8C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R6C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
SKYLIGHT_R7C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 1.61 | 0.00 | 3.10 | 3.10 | 5.799 | 0.551 | 0.401 | 283.913 | 0.000 | CurtainWall | 5.799 | 0.390 | 0.214 | No | BULK STORAGE ROOF | 180.00 | 0.00 | |
Total or Average | 137.59 | 5.146 | 0.471 | 0.378 | |||||||||||||||||
North Total or Average | 6.51 | 2.860 | 0.220 | 0.220 | |||||||||||||||||
Non-North Total or Average | 131.09 | 5.260 | 0.483 | 0.386 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 3.688 | 8.233 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.492 | 3.975 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
FINESTORAGE_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_10 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_14 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_13 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FINESTORAGE_SKYLIGHT_11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R5C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R8C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R6C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R7C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.1633 | 236.88 | 1459.96 | LightsWired | LTG_SCH_OFFICE | 44.65 | 168.00 | 27.72 | 0.0000 | Y | 7.60 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 16.95 | 0.0000 | Y | 29.63 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.1969 | 3204.84 | 10245.50 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 16.26 | 0.0000 | Y | 31.27 |
Interior Lighting Total | 4.3473 | 4835.13 | 21019.54 | 68.50 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE2 FINE STORAGE_DAYLREFPT1 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 9314.08 | 2328.52 |
ZONE2 FINE STORAGE_DAYLREFPT2 | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 9314.08 | 2328.52 |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10245.50 | 2561.37 |
ZONE3 BULK STORAGE_DAYLREFPT2 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.25 | 10245.50 | 2561.37 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1459.96 | 423.39 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1459.96 | 146.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 119.03 | AstronomicalClock | - | 41.93 | 41.93 | 0.94 | |
EXTERIOR_LIGHTS_B | 2955.82 | AstronomicalClock | - | 83.83 | 62.88 | 34.89 | |
EXTERIOR_LIGHTS_C | 694.12 | AstronomicalClock | - | 83.83 | 48.88 | 6.37 | |
Exterior Lighting Total | 3768.97 | 42.19 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23539.62 | 17670.25 | 5869.37 | 0.75 | 4.08 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 66797.48 | 46830.38 | 19967.10 | 0.70 | 4.01 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 22684.4 | 12.71 | 12.42 | ||||
PSZ-FINE STORAGE COOLING COIL | 64706.6 | 12.83 | 12.54 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 39959.00 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 25287.78 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 119808.23 | 0.81 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.98 | 90.76 | 92.91 | 1.00 | 4.17 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 1.10 | 1218.99 | 1107.16 | 1.00 | 1.38 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 2.69 | 2878.36 | 1070.05 | 1.00 | 1.28 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11145.44 | 13374.53 | 56.46 | 0.918 | 1.101 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | 23.90 | 23.90 | 0.00862 | 34.69 | 0.01716 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 34927.52 | 41913.03 | 30.08 | 2.242 | 2.690 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 26.70 | 26.70 | 0.00930 | 35.20 | 0.01716 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 0.00 | 35.55 | 0.01724 | 35.20 | 0.01716 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 1554.19 | 1865.02 | 7.87 | 0.043 | 0.102 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.01394 | 20.10 | 0.01480 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.425 | 00:10:00 | 15.56 | 18.48 | 0.01335 | 20.10 | 0.01480 | 0.425 | 0.00 | |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | 00:10:00 | 10.00 | 17.89 | 0.01285 | 20.10 | 0.01480 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.10 | 1.10 | 0.10 | 0.10 | 1.1010 | 1.1010 | 1.1010 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 2.69 | 2.69 | 0.42 | 0.42 | 2.6899 | 2.6899 | 2.6899 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 39959.005 | 39959.005 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 39959.00 | 39959.00 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 43.33 | 22.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 23539.620 | 17670.251 | 1.101010 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | 11769.81 | 9543.08 | 0.734007 | 25.81 | 17.77 | 0.00941122 | 12.00 | 11.25 | 0.00800000 | 34.78 | 0.01715734 | 25.72 | 13.9351 | 23.90 | 0.00861773 | 46.6454 | 11143.36 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 25287.776 | 25287.776 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 25287.78 | 25287.78 | 1.101008 | 21.01 | 20.02 | 0.01431256 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 9.2901 | 19.52 | 0.01426281 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 66797.480 | 46830.377 | 2.689930 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 33398.74 | 24755.83 | 1.793287 | 28.91 | 19.67 | 0.01053850 | 12.00 | 11.25 | 0.00800000 | 35.20 | 0.01715815 | 25.83 | 23.6834 | 26.70 | 0.00929737 | 42.5629 | 34927.52 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 119808.229 | 119808.229 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 119808.23 | 119808.23 | 2.689935 | 3.17 | 3.17 | 0.01357540 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 15.7889 | 18.48 | 0.01334612 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 39959.005 | 39959.005 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.976836 | 1.17571482 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 39959.00 | 39959.00 | 1.0000 | 1.17571482 | 0.976836 | 10.00 | 10.00 | 0.00800000 | 30204.6 | 43.33 | 22.14 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39959.00 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 10.00 | 0.00800000 | 10.00 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23539.620 | 17670.251 | 1.101010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.3350 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.101008 | 1.32516749 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | Sensible | 11769.81 | 9543.08 | 1.0000 | 0.88344674 | 0.734007 | 25.81 | 17.77 | 0.00941122 | 49921.4 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11769.81 | 34.78 | 0.01715734 | 25.72 | 0.10228463 | 13.9351 | 23.90 | 0.00861773 | 23.90 | 0.00861773 | 46.6454 | 11143.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25287.776 | 25287.776 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.101008 | 1.32516749 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 25287.78 | 25287.78 | 1.0000 | 1.32516749 | 1.101008 | 21.01 | 20.02 | 0.01431256 | 57465.1 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25287.78 | 20.10 | 0.01479830 | 20.10 | 0.10228463 | 9.2901 | 21.10 | 0.01426281 | 19.52 | 0.01426281 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 66797.480 | 46830.377 | 2.689930 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4305 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.689935 | 3.23759174 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | Sensible | 33398.74 | 24755.83 | 1.0000 | 2.15839083 | 1.793287 | 28.91 | 19.67 | 0.01053850 | 55968.4 | 12.00 | 11.25 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33398.74 | 35.20 | 0.01715815 | 25.83 | 0.42471127 | 23.6834 | 26.70 | 0.00929737 | 26.70 | 0.00929737 | 42.5629 | 34927.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 119808.229 | 119808.229 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 2.689935 | 3.23759174 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 119808.23 | 119808.23 | 1.0000 | 3.23759174 | 2.689935 | 3.17 | 3.17 | 0.01357540 | 37220.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 119808.23 | 20.10 | 0.01479830 | 20.10 | 0.42471127 | 15.7889 | 0.00 | 0.01334612 | 18.48 | 0.01334612 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 3636.00 | 1063.83 | 1063.83 |
ZONE2 FINE STORAGE | 3636.00 | 3626.00 | 3626.00 |
ZONE3 BULK STORAGE | 3636.00 | 3636.00 | 3636.00 |
Facility | 3636.00 | 3636.00 | 3636.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 0.00 | 100.00 | 0.00 | 98.17 |
ZONE2 FINE STORAGE | 0.00 | 322.33 | 0.00 | 1.17 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 422.33 | 0.00 | 99.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.360 | 0.374 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.499 | 0.158 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 0.000 | 0.086 | 0.000 | 2.716 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.43 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.43 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.60 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.57 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 1282406.64 | 0.00 | 1282406.64 | 1771116.47 | 3053523.11 | 3225648.14 | 5361.35 | 3398.65 | 0.00 | 65.52 |
ZONE2 FINE STORAGE | 6075800.46 | 0.00 | 6075800.46 | 4070082.89 | 10145883.34 | 13393694.68 | 5395.27 | 3364.73 | 0.00 | 2157.26 |
ZONE3 BULK STORAGE | 0.00 | 0.50E+09 | 0.50E+09 | 20296612.30 | 0.52E+09 | 30805497.77 | 4826.07 | 0.11 | 3933.82 | 4937.32 |
Total Facility | 7358207.09 | 0.50E+09 | 0.51E+09 | 26137811.66 | 0.54E+09 | 47424840.58 | 6217.72 | 3429.13 | 3933.82 | 4978.70 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.0976 | 0.0000 | 0.0976 | 0.1013 | 0.1990 | 0.1023 | 237.38 | 3398.62 | 0.00 |
ZONE2 FINE STORAGE | 0.3911 | 0.0000 | 0.3911 | 0.1235 | 0.5145 | 0.4247 | 301.30 | 3334.70 | 0.00 |
ZONE3 BULK STORAGE | 0.0000 | 24.7889 | 24.7889 | 0.7886 | 25.5775 | 0.9768 | 1084.90 | 0.00 | 2551.10 |
Total Facility | 0.4887 | 24.7889 | 25.2776 | 1.0134 | 26.2910 | 1.5038 | 1093.72 | 3399.01 | 2551.10 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 1857807.26 | 0.00 | 1857807.26 | 3225648.14 | 5333.74 | 2.63 | 3423.63 | 64.73 |
PSZ-FINE STORAGE | 8801692.60 | 0.00 | 8801692.60 | 13393694.68 | 5265.05 | 21.51 | 3473.44 | 2155.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.1414 | 0.0000 | 0.1414 | 0.1023 | 212.65 | 2.24 | 3421.11 |
PSZ-FINE STORAGE | 0.5665 | 0.0000 | 0.5665 | 0.4247 | 299.40 | 0.26 | 3336.33 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 3642.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 5561.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.1438 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.6048 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 50 | 50 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 451 |
Defaulted Fields | 395 |
Fields with Defaults | 1183 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 206 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 479.68 | 1525.96 | 01-JAN-08:10 | 39477.49 | 13-JUN-15:50 |
Electricity:Building | 237.62 | 1044.96 | 01-JAN-08:10 | 18999.19 | 04-DEC-17:00 |
Electricity:Zone:ZONE1 OFFICE | 36.76 | 520.87 | 01-JAN-00:10 | 2573.73 | 18-DEC-16:50 |
Electricity:SpaceType:GENERAL | 205.00 | 1044.96 | 01-JAN-08:10 | 16728.47 | 18-DEC-17:00 |
InteriorLights:Electricity | 68.50 | 575.09 | 01-JAN-08:10 | 6693.29 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 7.60 | 51.00 | 01-JAN-00:10 | 738.68 | 18-DEC-16:50 |
InteriorLights:Electricity:SpaceType:GENERAL | 68.50 | 575.09 | 01-JAN-08:10 | 6693.29 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity | 68.50 | 575.09 | 01-JAN-08:10 | 6693.29 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 7.60 | 51.00 | 01-JAN-00:10 | 738.68 | 18-DEC-16:50 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 68.50 | 575.09 | 01-JAN-08:10 | 6693.29 | 18-DEC-17:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 29.63 | 299.97 | 01-JAN-00:10 | 3007.39 | 18-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 29.63 | 299.97 | 01-JAN-00:10 | 3007.39 | 18-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 29.63 | 299.97 | 01-JAN-00:10 | 3007.39 | 18-DEC-16:00 |
Electricity:Zone:ZONE3 BULK STORAGE | 171.23 | 224.12 | 01-JAN-08:10 | 13556.21 | 04-DEC-17:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 31.27 | 224.12 | 01-JAN-08:10 | 3058.71 | 09-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 31.27 | 224.12 | 01-JAN-08:10 | 3058.71 | 09-DEC-17:00 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 59.26 | 0.00 | 01-JAN-00:10 | 5357.98 | 06-MAY-15:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 32.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-JAN-15:20 |
Ventilation (simple):Fans:Electricity | 32.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-JAN-15:20 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 32.62 | 0.00 | 01-JAN-00:10 | 2305.29 | 02-JAN-15:20 |
ElectricityProduced:Facility | 136.94 | -0.00 | 30-SEP-17:40 | 19854.74 | 19-MAR-11:30 |
ElectricityProduced:Plant | 136.94 | -0.00 | 30-SEP-17:40 | 19854.74 | 19-MAR-11:30 |
Photovoltaic:ElectricityProduced | 142.84 | 0.00 | 01-JAN-00:10 | 20664.19 | 19-MAR-11:30 |
PowerConversion:ElectricityProduced | -5.90 | -809.45 | 19-MAR-11:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 22.05 | 481.00 | 02-JAN-06:10 | 1702.65 | 14-JAN-12:40 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 350.28 | 0.00 | 01-JAN-07:20 | 31798.32 | 15-JUN-16:00 |
ElectricityPurchased:Plant | 350.28 | 0.00 | 01-JAN-07:20 | 31798.32 | 15-JUN-16:00 |
Cogeneration:ElectricityPurchased | 350.28 | 0.00 | 01-JAN-07:20 | 31798.32 | 15-JUN-16:00 |
General:Cogeneration:ElectricityPurchased | 350.28 | 0.00 | 01-JAN-07:20 | 31798.32 | 15-JUN-16:00 |
ElectricitySurplusSold:Facility | 7.54 | 0.00 | 01-JAN-00:10 | 16023.49 | 19-MAR-11:30 |
ElectricitySurplusSold:Plant | 7.54 | 0.00 | 01-JAN-00:10 | 16023.49 | 19-MAR-11:30 |
Cogeneration:ElectricitySurplusSold | 7.54 | 0.00 | 01-JAN-00:10 | 16023.49 | 19-MAR-11:30 |
General:Cogeneration:ElectricitySurplusSold | 7.54 | 0.00 | 01-JAN-00:10 | 16023.49 | 19-MAR-11:30 |
ElectricityNet:Facility | 342.74 | -16023.49 | 19-MAR-11:30 | 31798.32 | 15-JUN-16:00 |
ElectricityNet:Plant | 342.74 | -16023.49 | 19-MAR-11:30 | 31798.32 | 15-JUN-16:00 |
Cogeneration:ElectricityNet | 342.74 | -16023.49 | 19-MAR-11:30 | 31798.32 | 15-JUN-16:00 |
General:Cogeneration:ElectricityNet | 342.74 | -16023.49 | 19-MAR-11:30 | 31798.32 | 15-JUN-16:00 |
Electricity:HVAC | 177.81 | 0.00 | 01-JAN-00:10 | 21641.72 | 06-MAY-15:10 |
General:Fans:Electricity | 26.64 | 0.00 | 01-JAN-00:10 | 3052.69 | 06-MAY-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 151.17 | 0.00 | 01-JAN-00:10 | 18589.03 | 06-MAY-15:10 |
General:Cooling:Electricity | 151.17 | 0.00 | 01-JAN-00:10 | 18589.03 | 06-MAY-15:10 |
ExteriorLights:Electricity | 42.19 | 0.00 | 01-JAN-06:20 | 3768.97 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 42.19 | 0.00 | 01-JAN-06:20 | 3768.97 | 01-JAN-06:10 |
WaterSystems:Electricity | 22.05 | 481.00 | 02-JAN-06:10 | 1702.65 | 14-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 22.05 | 481.00 | 02-JAN-06:10 | 1702.65 | 14-JAN-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1029.12 | 0.00 | 01-JAN-00:10 | 116798.37 | 06-MAY-15:10 |
EnergyTransfer:Building | 351.80 | 0.00 | 01-JAN-00:10 | 42355.02 | 06-MAY-15:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 97.53 | 0.00 | 01-JAN-00:10 | 12439.00 | 01-MAY-12:00 |
Heating:EnergyTransfer | 0.01 | 0.00 | 01-JAN-00:10 | 724.11 | 12-AUG-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 0.01 | 0.00 | 01-JAN-00:10 | 724.11 | 12-AUG-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 351.79 | 0.00 | 01-JAN-00:10 | 42355.02 | 06-MAY-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 97.53 | 0.00 | 01-JAN-00:10 | 12439.00 | 01-MAY-12:00 |
General:Cooling:EnergyTransfer | 351.79 | 0.00 | 01-JAN-00:10 | 42355.02 | 06-MAY-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 97.53 | 0.00 | 01-JAN-00:10 | 12439.00 | 01-MAY-12:00 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 254.27 | 0.00 | 01-JAN-00:10 | 31925.72 | 06-MAY-15:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.01 | 0.00 | 01-JAN-00:10 | 724.11 | 12-AUG-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 0.01 | 0.00 | 01-JAN-00:10 | 724.11 | 12-AUG-06:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 254.26 | 0.00 | 01-JAN-00:10 | 31925.72 | 06-MAY-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 254.26 | 0.00 | 01-JAN-00:10 | 31925.72 | 06-MAY-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 677.32 | 0.00 | 01-JAN-00:10 | 75579.21 | 13-JUN-15:40 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 677.32 | 0.00 | 01-JAN-00:10 | 75579.21 | 13-JUN-15:40 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 0.000 | -97.526 | 0.000 | 0.000 | 9.115 | 7.597 | 29.165 | 12.706 | 0.000 | 8.820 | 32.902 | 0.000 | -1.935 | 0.000 | -0.844 | -0.001 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 0.010 | -254.247 | 0.000 | 0.000 | 17.087 | 29.627 | 0.000 | 39.368 | 0.000 | 9.473 | 167.857 | 0.000 | -5.786 | 0.000 | -3.390 | 0.000 |
ZONE3 BULK STORAGE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21.074 | 31.272 | 107.344 | 873.735 | 0.000 | 3.698 | 0.001 | 0.000 | -147.933 | 0.000 | -662.504 | -226.686 |
Total Facility | 0.000 | 0.000 | 0.010 | -351.772 | 0.000 | 0.000 | 47.276 | 68.497 | 136.508 | 925.808 | 0.000 | 21.992 | 200.761 | 0.000 | -155.654 | 0.000 | -666.738 | -226.686 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 23-FEB-06:01 | 0.00 | 0.00 | 0.00 | -19899.50 | 0.00 | 0.00 | 72.29 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 19753.42 | 0.00 | -254.02 | 0.00 | -273.70 | 0.00 |
ZONE2 FINE STORAGE | 16-JAN-15:23 | 0.00 | 0.00 | 0.00 | -54656.47 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 2471.31 | 0.00 | 392.87 | 51492.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-FEB-06:01 | 0.00 | 0.00 | 0.00 | -67307.49 | 0.00 | 0.00 | 572.32 | 799.21 | 2600.55 | 0.00 | 0.00 | 0.00 | 78038.23 | 0.00 | -14095.52 | 0.00 | -607.28 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 12-AUG-06:10 | 0.00 | 0.00 | 1448.58 | 0.00 | 0.00 | 0.00 | 339.76 | 2325.97 | 0.00 | 101.01 | 0.00 | 91.70 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4307.03 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-AUG-06:10 | -5325.55 | 5325.55 | 1448.58 | -5325.55 | 0.00 | 0.00 | 1129.63 | 5145.32 | 2967.56 | 822.93 | 0.00 | 227.45 | 93595.99 | 0.00 | 0.00 | 0.00 | -100011.90 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1010 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1010 | 0.0929 | 1.0000 | Not calculated | 0.1023 | 0.0929 | ||
PSZ-FINE STORAGE | 2.6899 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6899 | 0.1579 | 1.0000 | Not calculated | 0.4247 | 0.1579 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.1010 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.1010 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0929 | ||
PSZ-FINE STORAGE | 2.6899 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 2.6899 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.1579 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1010 | 1.1010 | 1.1010 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6899 | 2.6899 | 2.6899 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1010 | 1.1010 | 1.1010 | 1.1010 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6899 | 2.6899 | 2.6899 | 2.6899 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1010 | 1.1010 | 1.1010 | No | 0.1023 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6899 | 2.6899 | 2.6899 | No | 0.4247 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.1010 | 1.1010 | 1.1010 | 1.1010 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 2.6899 | 2.6899 | 2.6899 | 2.6899 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 4835.13 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 99.33 |
Number of hours not met | 99.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 151.17 | 18589.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 68.50 | 6693.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 42.19 | 3768.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 32.62 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 26.64 | 3052.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 22.05 | 1702.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 479.68 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 479.68 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 142.84 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 14.17 |
Space Heating | 0.00 |
Space Cooling | 31.27 |
Fans (All) | 12.26 |
Service Water Heating | 4.56 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 99.21 |
Subtotal | 99.21 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.28 |
Space Heating | 0.00 |
Space Cooling | 31.52 |
Fans (All) | 12.35 |
Service Water Heating | 4.60 |
Receptacle Equipment | 28.46 |
Miscellaneous | 8.80 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
LTG_SCH_OFFICE | 2328. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 3803.33 | 4466.50 | 490.17 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 133.50 | 8626.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 1396.00 | 6511.83 | 852.17 | 0.00 |
Min | 0.00 | 1396.00 | 0.00 | 0.00 | 0.00 |
Max | 3803.33 | 8626.50 | 6511.83 | 852.17 | 0.00 |
Average | 1312.28 | 4829.67 | 2334.00 | 284.06 | 0.00 |
Sum | 3936.83 | 14489.00 | 7002.00 | 852.17 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33022.83 | 4.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 60.50 | 82658.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 14227.67 | 136659.00 | 40306.33 | 0.00 |
Min | 0.00 | 4.17 | 0.00 | 0.00 | 0.00 |
Max | 33022.83 | 82658.50 | 136659.00 | 40306.33 | 0.00 |
Average | 11027.78 | 32296.78 | 45553.00 | 13435.44 | 0.00 |
Sum | 33083.33 | 96890.33 | 136659.00 | 40306.33 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 2559.17 | 6034.33 | 166.50 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 2.33 | 8757.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 2883.00 | 5151.83 | 724.33 | 0.83 |
Min | 0.00 | 2883.00 | 0.00 | 0.00 | 0.00 |
Max | 2559.17 | 8757.67 | 5151.83 | 724.33 | 0.83 |
Average | 853.83 | 5891.67 | 1772.78 | 241.44 | 0.28 |
Sum | 2561.50 | 17675.00 | 5318.33 | 724.33 | 0.83 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 27474.50 | 5552.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 82719.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 42455.00 | 114342.00 | 34349.50 | 46.50 |
Min | 0.00 | 5552.50 | 0.00 | 0.00 | 0.00 |
Max | 27474.50 | 82719.00 | 114342.00 | 34349.50 | 46.50 |
Average | 9158.17 | 43575.50 | 38114.00 | 11449.83 | 15.50 |
Sum | 27474.50 | 130726.50 | 114342.00 | 34349.50 | 46.50 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:17
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 5840.00 | 0.00 |
Sum | 0.00 | 8760.00 | 17520.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 82719.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 82719.00 | 0.00 |
Average | 0.00 | 63731.00 | 38582.00 | 0.00 |
Sum | 0.00 | 191193.00 | 115746.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.761952E+10 | 18001.43 | 24-JAN-06:01 | 19.57 | 17.63 | 0.635158E+09 | 769.07 | 31-JAN-15:30 | 32.05 | 22.58 |
February | 0.740698E+10 | 19901.10 | 23-FEB-06:01 | 22.85 | 19.63 | 0.584388E+09 | 769.07 | 24-FEB-15:39 | 34.27 | 21.16 |
March | 0.906895E+10 | 17009.85 | 04-MAR-06:01 | 24.10 | 20.01 | 0.686046E+09 | 769.06 | 13-MAR-10:20 | 31.07 | 24.25 |
April | 0.863690E+10 | 14965.05 | 27-APR-05:01 | 26.00 | 23.88 | 0.635280E+09 | 769.06 | 26-APR-10:50 | 26.00 | 23.88 |
May | 0.898766E+10 | 14888.92 | 31-MAY-05:01 | 24.17 | 24.17 | 0.660729E+09 | 769.07 | 05-MAY-12:09 | 24.17 | 24.17 |
June | 0.916210E+10 | 14571.79 | 27-JUN-05:01 | 23.00 | 23.00 | 0.660727E+09 | 769.08 | 14-JUN-12:09 | 23.00 | 23.00 |
July | 0.799795E+10 | 16460.03 | 11-JUL-05:01 | 24.12 | 23.83 | 0.635250E+09 | 769.06 | 10-JUL-10:30 | 24.12 | 23.83 |
August | 0.861443E+10 | 14632.94 | 24-AUG-05:01 | 24.00 | 24.00 | 0.686060E+09 | 769.08 | 14-AUG-12:09 | 24.00 | 24.00 |
September | 0.794437E+10 | 15178.22 | 06-SEP-05:01 | 25.08 | 24.21 | 0.635249E+09 | 769.06 | 23-SEP-13:30 | 31.00 | 26.41 |
October | 0.749656E+10 | 14970.35 | 11-OCT-05:01 | 24.00 | 23.32 | 0.635209E+09 | 769.06 | 07-OCT-13:09 | 24.00 | 23.32 |
November | 0.730441E+10 | 16893.83 | 25-NOV-06:01 | 20.58 | 18.85 | 0.609793E+09 | 769.06 | 20-NOV-11:30 | 20.58 | 18.85 |
December | 0.728839E+10 | 17370.32 | 21-DEC-06:01 | 18.07 | 17.39 | 0.635123E+09 | 769.06 | 07-DEC-13:50 | 18.07 | 17.39 |
Annual Sum or Average | 0.975282E+11 | 0.769901E+10 | ||||||||
Minimum of Months | 0.728839E+10 | 14571.79 | 18.07 | 17.39 | 0.584388E+09 | 769.06 | 18.07 | 17.39 | ||
Maximum of Months | 0.916210E+10 | 19901.10 | 26.00 | 24.21 | 0.686060E+09 | 769.08 | 34.27 | 26.41 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180819E+11 | 54657.57 | 16-JAN-15:23 | 31.65 | 21.95 | 0.185443E+10 | 2246.95 | 21-JAN-15:50 | 29.92 | 22.45 |
February | 0.198116E+11 | 50719.37 | 22-FEB-06:01 | 23.88 | 22.47 | 0.170654E+10 | 2247.02 | 28-FEB-13:39 | 34.70 | 24.67 |
March | 0.251807E+11 | 50653.16 | 12-MAR-16:03 | 32.08 | 24.26 | 0.200319E+10 | 2247.02 | 29-MAR-13:30 | 35.80 | 23.34 |
April | 0.259730E+11 | 48929.73 | 23-APR-13:02 | 33.08 | 24.58 | 0.185463E+10 | 2247.01 | 27-APR-13:39 | 33.67 | 25.36 |
May | 0.256942E+11 | 46448.90 | 14-MAY-11:02 | 33.00 | 25.66 | 0.192889E+10 | 2247.00 | 27-MAY-12:50 | 34.08 | 26.69 |
June | 0.269952E+11 | 45680.11 | 20-JUN-05:09 | 24.00 | 24.00 | 0.192881E+10 | 2246.99 | 27-JUN-12:39 | 32.97 | 26.82 |
July | 0.211639E+11 | 50637.71 | 16-JUL-15:43 | 24.92 | 23.40 | 0.185476E+10 | 2246.95 | 26-JUL-15:20 | 32.70 | 25.52 |
August | 0.202990E+11 | 45850.50 | 24-AUG-05:01 | 24.00 | 24.00 | 0.200316E+10 | 2246.99 | 23-AUG-13:39 | 24.00 | 24.00 |
September | 0.204195E+11 | 47361.95 | 10-SEP-12:02 | 32.92 | 25.65 | 0.185474E+10 | 2247.00 | 12-SEP-13:09 | 32.50 | 27.07 |
October | 0.172913E+11 | 46874.40 | 08-OCT-13:02 | 32.33 | 26.78 | 0.185487E+10 | 2247.00 | 04-OCT-13:50 | 32.33 | 26.78 |
November | 0.169290E+11 | 49320.53 | 19-NOV-15:02 | 31.27 | 25.08 | 0.178056E+10 | 2246.96 | 24-NOV-13:50 | 29.07 | 22.15 |
December | 0.164198E+11 | 50963.24 | 03-DEC-16:23 | 29.00 | 22.59 | 0.185416E+10 | 2246.95 | 06-DEC-16:30 | 29.85 | 23.14 |
Annual Sum or Average | 0.254259E+12 | 0.224787E+11 | ||||||||
Minimum of Months | 0.164198E+11 | 45680.11 | 23.88 | 21.95 | 0.170654E+10 | 2246.95 | 24.00 | 22.15 | ||
Maximum of Months | 0.269952E+11 | 54657.57 | 33.08 | 26.78 | 0.200319E+10 | 2247.02 | 35.80 | 27.07 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 | 23.60 | 0.561509E+10 | 8378.00 | 04-JAN-13:39 | 34.03 | 23.47 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 | 22.46 | 0.538610E+10 | 8833.06 | 28-FEB-14:39 | 35.00 | 24.83 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 | 0.653203E+10 | 9097.65 | 21-MAR-12:50 | 36.17 | 23.06 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 | 25.10 | 0.611857E+10 | 9048.69 | 01-APR-14:20 | 35.33 | 26.89 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 | 26.40 | 0.634345E+10 | 9097.65 | 01-MAY-12:09 | 34.40 | 26.31 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 | 23.91 | 0.640003E+10 | 9097.65 | 12-JUN-15:09 | 35.90 | 27.62 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 | 24.33 | 0.557730E+10 | 8056.98 | 15-JUL-15:00 | 33.20 | 25.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 | 24.75 | 0.609591E+10 | 8365.87 | 14-AUG-13:20 | 33.53 | 27.57 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 | 25.66 | 0.566631E+10 | 8433.72 | 06-SEP-14:20 | 33.67 | 26.68 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 | 25.35 | 0.544736E+10 | 8008.02 | 04-OCT-14:20 | 32.83 | 26.21 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 | 24.37 | 0.526383E+10 | 8300.10 | 18-NOV-13:20 | 33.20 | 25.24 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 | 0.548027E+10 | 8054.61 | 08-DEC-14:39 | 33.00 | 23.51 |
Annual Sum or Average | 0.00 | 0.699263E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | 23.80 | 22.46 | 0.526383E+10 | 8008.02 | 32.83 | 23.06 | ||
Maximum of Months | 0.00 | 0.00 | 28.62 | 26.40 | 0.653203E+10 | 9097.65 | 36.17 | 27.62 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 451081.35 | 582.29 | 03-JAN-07:10 | 25.27 |
February | 292674.69 | 722.19 | 16-FEB-07:10 | 25.50 |
March | 1575978.43 | 1015.47 | 27-MAR-06:10 | 26.20 |
April | 91197.20 | 303.99 | 24-APR-06:10 | 24.93 |
May | 1010269.25 | 1180.14 | 20-MAY-06:07 | 26.38 |
June | 296052.42 | 432.16 | 22-JUN-06:10 | 25.40 |
July | 1064092.48 | 550.56 | 28-JUL-06:10 | 25.17 |
August | 1907424.85 | 1448.21 | 12-AUG-06:10 | 27.05 |
September | 1044159.48 | 1030.27 | 27-SEP-06:10 | 26.18 |
October | 944064.62 | 567.52 | 16-OCT-06:10 | 26.20 |
November | 1113728.27 | 649.14 | 09-NOV-07:10 | 25.50 |
December | 603727.28 | 896.98 | 09-DEC-07:05 | 25.25 |
Annual Sum or Average | 10394450.33 | |||
Minimum of Months | 91197.20 | 303.99 | 24.93 | |
Maximum of Months | 1907424.85 | 1448.21 | 27.05 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.644202E+09 | 704.96 | 02-JAN-16:00 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.576821E+09 | 679.14 | 08-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.664615E+09 | 701.42 | 28-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.613298E+09 | 700.04 | 21-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.640615E+09 | 706.29 | 17-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.606980E+09 | 697.39 | 20-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.624167E+09 | 700.31 | 11-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.663045E+09 | 703.80 | 21-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.638069E+09 | 704.24 | 21-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.646009E+09 | 715.38 | 23-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.624549E+09 | 722.21 | 27-NOV-16:00 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.655019E+09 | 738.68 | 18-DEC-16:49 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.759739E+10 | 0.291647E+11 | ||||
Minimum of Months | 0.576821E+09 | 679.14 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.664615E+09 | 738.68 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.251897E+10 | 2846.06 | 02-JAN-16:00 | 0.00 | 0.00 |
February | 0.226450E+10 | 2713.27 | 03-FEB-16:00 | 0.00 | 0.00 |
March | 0.257580E+10 | 2711.63 | 01-MAR-16:00 | 0.00 | 0.00 |
April | 0.241411E+10 | 2626.08 | 01-APR-07:10 | 0.00 | 0.00 |
May | 0.252425E+10 | 2684.90 | 05-MAY-08:09 | 0.00 | 0.00 |
June | 0.251425E+10 | 2591.63 | 20-JUN-07:10 | 0.00 | 0.00 |
July | 0.246138E+10 | 2610.56 | 11-JUL-07:10 | 0.00 | 0.00 |
August | 0.256082E+10 | 2609.11 | 21-AUG-07:10 | 0.00 | 0.00 |
September | 0.240062E+10 | 2572.85 | 21-SEP-07:10 | 0.00 | 0.00 |
October | 0.244368E+10 | 2641.01 | 23-OCT-07:10 | 0.00 | 0.00 |
November | 0.240862E+10 | 2925.27 | 09-NOV-15:00 | 0.00 | 0.00 |
December | 0.254013E+10 | 3007.39 | 18-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296271E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.226450E+10 | 2572.85 | 0.00 | 0.00 | |
Maximum of Months | 0.257580E+10 | 3007.39 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.269000E+10 | 2957.68 | 02-JAN-16:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.242284E+10 | 2708.93 | 03-FEB-16:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.273126E+10 | 2693.58 | 01-MAR-16:00 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.253173E+10 | 2523.67 | 21-APR-06:10 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.261528E+10 | 2389.98 | 11-MAY-06:10 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.257576E+10 | 2507.82 | 20-JUN-06:10 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.255508E+10 | 2512.67 | 11-JUL-06:10 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.268699E+10 | 2493.11 | 21-AUG-06:10 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.254496E+10 | 2512.49 | 21-SEP-06:10 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.260846E+10 | 2560.84 | 23-OCT-06:10 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.259084E+10 | 3047.14 | 27-NOV-16:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.271882E+10 | 3058.71 | 09-DEC-16:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.312720E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.242284E+10 | 2389.98 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.273126E+10 | 3058.71 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.644202E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613899E+09 | 0.132232E+09 |
February | 0.127628E+10 | 0.576821E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676522E+09 | 64825970.88 |
March | 0.149825E+10 | 0.664615E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976930E+09 | 84310566.61 |
April | 0.138726E+10 | 0.613298E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912085E+09 | 30769764.90 |
May | 0.144276E+10 | 0.640615E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995700E+09 | 43623649.89 |
June | 0.144276E+10 | 0.606980E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999668E+09 | 49004602.58 |
July | 0.138726E+10 | 0.624167E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599203E+09 | 50317248.19 |
August | 0.149825E+10 | 0.663045E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788192E+09 | 77852788.56 |
September | 0.138726E+10 | 0.638069E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642464E+09 | 47923990.04 |
October | 0.138726E+10 | 0.646009E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552888E+09 | 66331936.00 |
November | 0.133177E+10 | 0.624549E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562074E+09 | 69648532.76 |
December | 0.138726E+10 | 0.655019E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500407E+09 | 0.127089E+09 |
Annual Sum or Average | 0.168137E+11 | 0.759739E+10 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882003E+10 | 0.843930E+09 |
Minimum of Months | 0.127628E+10 | 0.576821E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500407E+09 | 30769764.90 |
Maximum of Months | 0.149825E+10 | 0.664615E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999668E+09 | 0.132232E+09 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.251897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435701E+09 | 0.532648E+09 |
February | 0.300332E+10 | 0.226450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710980E+09 | 0.206271E+09 |
March | 0.352563E+10 | 0.257580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120938E+10 | 0.306822E+09 |
April | 0.326447E+10 | 0.241411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123046E+10 | 63393242.07 |
May | 0.339505E+10 | 0.252425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142040E+10 | 0.156757E+09 |
June | 0.339505E+10 | 0.251425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129588E+10 | 0.141341E+09 |
July | 0.326447E+10 | 0.246138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700828E+09 | 0.187657E+09 |
August | 0.352563E+10 | 0.256082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.797166E+09 | 0.344909E+09 |
September | 0.326447E+10 | 0.240062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614737E+09 | 0.200396E+09 |
October | 0.326447E+10 | 0.244368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433806E+09 | 0.309430E+09 |
November | 0.313390E+10 | 0.240862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323925E+09 | 0.343230E+09 |
December | 0.326447E+10 | 0.254013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299884E+09 | 0.597296E+09 |
Annual Sum or Average | 0.395654E+11 | 0.296271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947314E+10 | 0.339015E+10 |
Minimum of Months | 0.300332E+10 | 0.226450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299884E+09 | 63393242.07 |
Maximum of Months | 0.352563E+10 | 0.257580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142040E+10 | 0.597296E+09 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.269000E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 777114.03 | 0.494764E+10 |
February | 0.690763E+10 | 0.242284E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2208577.42 | 0.330648E+10 |
March | 0.810895E+10 | 0.273126E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15615784.01 | 0.558800E+10 |
April | 0.750829E+10 | 0.253173E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9556003.87 | 0.306697E+10 |
May | 0.780862E+10 | 0.261528E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27466039.75 | 0.364827E+10 |
June | 0.780862E+10 | 0.257576E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4954736.92 | 0.367571E+10 |
July | 0.750829E+10 | 0.255508E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 601167.25 | 0.344295E+10 |
August | 0.810895E+10 | 0.268699E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14423682.52 | 0.530560E+10 |
September | 0.750829E+10 | 0.254496E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1666808.90 | 0.338466E+10 |
October | 0.750829E+10 | 0.260846E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 823988.42 | 0.401366E+10 |
November | 0.720796E+10 | 0.259084E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1515368.03 | 0.385488E+10 |
December | 0.750829E+10 | 0.271882E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 767184.90 | 0.493182E+10 |
Annual Sum or Average | 0.910005E+11 | 0.312720E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 80376456.01 | 0.491666E+11 |
Minimum of Months | 0.690763E+10 | 0.242284E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 601167.25 | 0.306697E+10 |
Maximum of Months | 0.810895E+10 | 0.273126E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27466039.75 | 0.558800E+10 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 704.96 | 02-JAN-16:00 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3687.33 | 04-JAN-13:00 | 1621.97 | 24-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 679.14 | 08-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3752.94 | 28-FEB-13:00 | 976.86 | 01-FEB-07:10 |
March | 1680.92 | 01-MAR-08:09 | 701.42 | 28-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4050.73 | 20-MAR-16:10 | 368.83 | 03-MAR-06:01 |
April | 1680.92 | 01-APR-07:10 | 700.04 | 21-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4167.79 | 11-APR-16:10 | 224.91 | 13-APR-05:01 |
May | 1680.92 | 01-MAY-07:10 | 706.29 | 17-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4692.74 | 05-MAY-16:10 | 438.80 | 08-MAY-22:00 |
June | 1680.92 | 01-JUN-07:10 | 697.39 | 20-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4359.48 | 13-JUN-16:10 | 466.13 | 20-JUN-22:53 |
July | 1680.92 | 01-JUL-07:10 | 700.31 | 11-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3560.50 | 26-JUL-17:00 | 288.33 | 19-JUL-18:55 |
August | 1680.92 | 01-AUG-07:10 | 703.80 | 21-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3595.15 | 09-AUG-16:10 | 399.52 | 23-AUG-19:55 |
September | 1680.92 | 01-SEP-07:10 | 704.24 | 21-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3202.12 | 12-SEP-12:00 | 430.49 | 15-SEP-17:00 |
October | 1680.92 | 02-OCT-07:10 | 715.38 | 23-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3080.64 | 04-OCT-12:00 | 368.01 | 23-OCT-05:01 |
November | 1680.92 | 01-NOV-07:10 | 722.21 | 27-NOV-16:00 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2899.83 | 10-NOV-12:10 | 666.29 | 27-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 738.68 | 18-DEC-16:49 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2878.14 | 26-DEC-13:00 | 2012.37 | 21-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 679.14 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2878.14 | 224.91 | |||||
Maximum of Months | 1680.92 | 738.68 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 4692.74 | 2012.37 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 2846.06 | 02-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2057.30 | 31-JAN-16:10 | 5017.81 | 07-JAN-05:00 |
February | 3955.50 | 01-FEB-08:09 | 2713.27 | 03-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3181.92 | 28-FEB-16:05 | 1420.27 | 01-FEB-07:10 |
March | 3955.50 | 01-MAR-08:09 | 2711.63 | 01-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4818.58 | 19-MAR-16:00 | 1113.08 | 03-MAR-05:00 |
April | 3955.50 | 01-APR-07:10 | 2626.08 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3303.95 | 11-APR-16:00 | 1001.52 | 14-APR-16:00 |
May | 3955.50 | 01-MAY-07:10 | 2684.90 | 05-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5657.62 | 06-MAY-15:10 | 1855.67 | 08-MAY-22:00 |
June | 3955.50 | 01-JUN-07:10 | 2591.63 | 20-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4531.03 | 16-JUN-15:30 | 2171.62 | 20-JUN-23:00 |
July | 3955.50 | 01-JUL-07:10 | 2610.56 | 11-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2779.69 | 13-JUL-16:00 | 1475.64 | 19-JUL-19:05 |
August | 3955.50 | 01-AUG-07:10 | 2609.11 | 21-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3174.55 | 09-AUG-16:00 | 1838.65 | 23-AUG-19:55 |
September | 3955.50 | 01-SEP-07:10 | 2572.85 | 21-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3225.44 | 10-SEP-15:00 | 2921.37 | 15-SEP-17:00 |
October | 3955.50 | 02-OCT-07:10 | 2641.01 | 23-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2807.85 | 29-OCT-13:00 | 1322.12 | 30-OCT-16:20 |
November | 3955.50 | 01-NOV-07:10 | 2925.27 | 09-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1462.47 | 04-NOV-15:10 | 1242.39 | 25-NOV-08:00 |
December | 3955.50 | 01-DEC-08:09 | 3007.39 | 18-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1321.97 | 13-DEC-16:10 | 1876.39 | 21-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 2572.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1321.97 | 1001.52 | ||||
Maximum of Months | 3955.50 | 3007.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5657.62 | 5017.81 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 2957.68 | 02-JAN-16:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 777.56 | 11-JAN-10:55 | 28551.72 | 07-JAN-05:00 |
February | 9097.65 | 01-FEB-08:09 | 2708.93 | 03-FEB-16:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 639.67 | 12-FEB-12:53 | 6836.66 | 01-FEB-07:00 |
March | 9097.65 | 01-MAR-08:09 | 2693.58 | 01-MAR-16:00 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1290.30 | 19-MAR-11:45 | 8090.17 | 14-MAR-22:00 |
April | 9097.65 | 01-APR-07:10 | 2523.67 | 21-APR-06:10 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.12 | 17-APR-09:43 | 6651.17 | 14-APR-16:00 |
May | 9097.65 | 01-MAY-07:10 | 2389.98 | 11-MAY-06:10 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3407.77 | 01-MAY-13:53 | 12436.88 | 08-MAY-22:00 |
June | 9097.65 | 01-JUN-07:10 | 2507.82 | 20-JUN-06:10 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 728.62 | 18-JUN-13:43 | 14418.78 | 20-JUN-22:53 |
July | 9097.65 | 01-JUL-07:10 | 2512.67 | 11-JUL-06:10 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 594.09 | 27-JUL-16:55 | 16714.26 | 03-JUL-13:00 |
August | 9097.65 | 01-AUG-07:10 | 2493.11 | 21-AUG-06:10 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1326.20 | 06-AUG-12:00 | 17382.54 | 25-AUG-11:00 |
September | 9097.65 | 01-SEP-07:10 | 2512.49 | 21-SEP-06:10 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1239.66 | 22-SEP-15:55 | 15168.45 | 15-SEP-17:00 |
October | 9097.65 | 02-OCT-07:10 | 2560.84 | 23-OCT-06:10 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 418.99 | 06-OCT-10:55 | 10445.52 | 11-OCT-13:20 |
November | 9097.65 | 01-NOV-07:10 | 3047.14 | 27-NOV-16:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.91 | 17-NOV-18:55 | 7660.48 | 25-NOV-08:70 |
December | 9097.65 | 01-DEC-08:09 | 3058.71 | 09-DEC-16:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 703.40 | 29-DEC-18:55 | 12205.28 | 20-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 2389.98 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 418.99 | 6651.17 | |||||
Maximum of Months | 9097.65 | 3058.71 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3407.77 | 28551.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18001.43 | 24-JAN-06:01 | 1479.21 | 407.96 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.93 |
February | 19901.10 | 23-FEB-06:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.70 |
March | 17009.85 | 04-MAR-06:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.20 |
April | 14965.05 | 27-APR-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.87 |
May | 14888.92 | 31-MAY-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.93 |
June | 14571.79 | 27-JUN-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.82 |
July | 16460.03 | 11-JUL-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.58 |
August | 14632.94 | 24-AUG-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.29 |
September | 15178.22 | 06-SEP-05:01 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.28 |
October | 14970.35 | 11-OCT-05:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.42 |
November | 16893.83 | 25-NOV-06:01 | 1664.11 | 458.96 | 4954.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.42 |
December | 17370.32 | 21-DEC-06:01 | 1294.31 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14571.79 | 1294.31 | 356.97 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.20 | |
Maximum of Months | 19901.10 | 1849.01 | 509.95 | 5505.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 54657.57 | 16-JAN-15:23 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.87 | 0.00 |
February | 50719.37 | 22-FEB-06:01 | 4351.05 | 2999.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.01 |
March | 50653.16 | 12-MAR-16:03 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.99 | 0.00 |
April | 48929.73 | 23-APR-13:02 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.95 | 0.00 |
May | 46448.90 | 14-MAY-11:02 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1358.61 | 0.00 |
June | 45680.11 | 20-JUN-05:09 | 3915.95 | 2699.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.33 |
July | 50637.71 | 16-JUL-15:43 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.59 |
August | 45850.50 | 24-AUG-05:01 | 3915.95 | 2699.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 47361.95 | 10-SEP-12:02 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 954.63 | 0.00 |
October | 46874.40 | 08-OCT-13:02 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.45 | 0.00 |
November | 49320.53 | 19-NOV-15:02 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 640.01 | 0.00 |
December | 50963.24 | 03-DEC-16:23 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 45680.11 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54657.57 | 4351.05 | 2999.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1358.61 | 421.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1174.02 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1774.45 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2481.43 |
April | 0.00 | 01-APR-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2198.24 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 896.48 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 997.65 |
June | 0.00 | 01-JUN-00:05 | 0.00 | 896.48 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3011.02 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2293.45 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3372.66 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2068.19 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 896.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.37 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.75 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1635.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.37 | |
Maximum of Months | 0.00 | 0.00 | 896.48 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3372.66 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.369038E+11 | 32504.18 | 05-JAN-15:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.355883E+11 | 34074.20 | 28-FEB-14:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.429058E+11 | 35423.35 | 28-MAR-15:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.431090E+11 | 35949.42 | 17-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.453444E+11 | 39434.46 | 06-MAY-15:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.455468E+11 | 39477.49 | 13-JUN-15:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.388376E+11 | 32925.46 | 19-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.417939E+11 | 35417.59 | 11-AUG-14:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.395073E+11 | 34698.05 | 06-SEP-14:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.378031E+11 | 33938.41 | 04-OCT-15:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.361022E+11 | 32294.95 | 20-NOV-15:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.362384E+11 | 31984.91 | 13-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.479681E+12 | 0.00 | ||||
Minimum of Months | 0.355883E+11 | 31984.91 | 0.00 | 0.00 | ||
Maximum of Months | 0.455468E+11 | 39477.49 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.106591E+11 | 17086.26 | 28-JAN-12:30 | 0.00 | 0.00 |
February | 0.109372E+11 | 19134.69 | 24-FEB-12:30 | 0.00 | 0.00 |
March | 0.137312E+11 | 19854.74 | 19-MAR-11:30 | 0.00 | 0.00 |
April | 0.134332E+11 | 18527.02 | 13-APR-11:30 | 0.00 | 0.00 |
May | 0.119146E+11 | 18544.98 | 05-MAY-10:00 | 0.00 | 0.00 |
June | 0.123765E+11 | 16787.72 | 17-JUN-12:20 | 0.00 | 0.00 |
July | 0.111105E+11 | 17127.92 | 13-JUL-11:00 | 0.00 | 0.00 |
August | 0.120938E+11 | 17992.79 | 27-AUG-11:30 | 0.00 | 0.00 |
September | 0.108144E+11 | 17046.21 | 14-SEP-11:30 | 0.00 | 0.00 |
October | 0.103425E+11 | 16611.81 | 04-OCT-12:30 | 0.00 | 0.00 |
November | 0.957333E+10 | 15525.06 | 02-NOV-11:39 | 0.00 | 0.00 |
December | 0.995194E+10 | 15996.00 | 27-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.136938E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.957333E+10 | 15525.06 | 0.00 | 0.00 | |
Maximum of Months | 0.137312E+11 | 19854.74 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.585317E+10 | 0.382596E+10 | 0.112984E+11 | 0.00 | 0.412328E+10 | 0.00 | 0.00 | 0.992148E+10 | 0.00 | 0.00 | 0.00 | 0.188154E+10 | 0.00 |
February | 0.526416E+10 | 0.338122E+10 | 0.103734E+11 | 0.00 | 0.434987E+10 | 0.00 | 0.00 | 0.105155E+11 | 0.00 | 0.00 | 0.00 | 0.170410E+10 | 0.00 |
March | 0.597168E+10 | 0.358399E+10 | 0.121089E+11 | 0.00 | 0.548135E+10 | 0.00 | 0.00 | 0.138519E+11 | 0.00 | 0.00 | 0.00 | 0.190799E+10 | 0.00 |
April | 0.555914E+10 | 0.335283E+10 | 0.112578E+11 | 0.00 | 0.616727E+10 | 0.00 | 0.00 | 0.149585E+11 | 0.00 | 0.00 | 0.00 | 0.181346E+10 | 0.00 |
May | 0.578015E+10 | 0.338047E+10 | 0.117000E+11 | 0.00 | 0.640121E+10 | 0.00 | 0.00 | 0.162171E+11 | 0.00 | 0.00 | 0.00 | 0.186553E+10 | 0.00 |
June | 0.569699E+10 | 0.321715E+10 | 0.116594E+11 | 0.00 | 0.639055E+10 | 0.00 | 0.00 | 0.167699E+11 | 0.00 | 0.00 | 0.00 | 0.181289E+10 | 0.00 |
July | 0.564062E+10 | 0.336238E+10 | 0.112984E+11 | 0.00 | 0.469438E+10 | 0.00 | 0.00 | 0.120048E+11 | 0.00 | 0.00 | 0.00 | 0.183706E+10 | 0.00 |
August | 0.591086E+10 | 0.342343E+10 | 0.121016E+11 | 0.00 | 0.487114E+10 | 0.00 | 0.00 | 0.136103E+11 | 0.00 | 0.00 | 0.00 | 0.187666E+10 | 0.00 |
September | 0.558365E+10 | 0.343424E+10 | 0.112504E+11 | 0.00 | 0.475961E+10 | 0.00 | 0.00 | 0.126747E+11 | 0.00 | 0.00 | 0.00 | 0.180467E+10 | 0.00 |
October | 0.569815E+10 | 0.367897E+10 | 0.113057E+11 | 0.00 | 0.419824E+10 | 0.00 | 0.00 | 0.110615E+11 | 0.00 | 0.00 | 0.00 | 0.186048E+10 | 0.00 |
November | 0.562401E+10 | 0.369304E+10 | 0.108562E+11 | 0.00 | 0.393995E+10 | 0.00 | 0.00 | 0.101815E+11 | 0.00 | 0.00 | 0.00 | 0.180755E+10 | 0.00 |
December | 0.591396E+10 | 0.386105E+10 | 0.112984E+11 | 0.00 | 0.387934E+10 | 0.00 | 0.00 | 0.940632E+10 | 0.00 | 0.00 | 0.00 | 0.187937E+10 | 0.00 |
Annual Sum or Average | 0.684966E+11 | 0.421947E+11 | 0.136508E+12 | 0.00 | 0.592562E+11 | 0.00 | 0.00 | 0.151174E+12 | 0.00 | 0.00 | 0.00 | 0.220513E+11 | 0.00 |
Minimum of Months | 0.526416E+10 | 0.321715E+10 | 0.103734E+11 | 0.00 | 0.387934E+10 | 0.00 | 0.00 | 0.940632E+10 | 0.00 | 0.00 | 0.00 | 0.170410E+10 | 0.00 |
Maximum of Months | 0.597168E+10 | 0.386105E+10 | 0.121089E+11 | 0.00 | 0.640121E+10 | 0.00 | 0.00 | 0.167699E+11 | 0.00 | 0.00 | 0.00 | 0.190799E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 6508.70 | 02-JAN-16:00 | 3768.97 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 4321.23 | 04-JAN-12:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 5887.62 | 03-FEB-16:00 | 3768.97 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 4493.25 | 15-FEB-12:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 6056.43 | 01-MAR-16:00 | 3768.97 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 4767.85 | 20-MAR-15:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 5540.77 | 21-APR-07:10 | 3768.97 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 4815.38 | 18-APR-15:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 5718.63 | 17-MAY-07:10 | 3768.97 | 01-MAY-05:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 5357.98 | 06-MAY-15:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 5587.00 | 20-JUN-07:10 | 3768.97 | 01-JUN-05:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 5305.18 | 13-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 5653.64 | 11-JUL-07:10 | 3768.97 | 01-JUL-05:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 4331.58 | 26-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 5657.58 | 21-AUG-07:10 | 3768.97 | 01-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4796.65 | 15-AUG-11:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 5497.40 | 16-SEP-07:10 | 3768.97 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 4660.12 | 06-SEP-11:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 5831.20 | 30-OCT-15:00 | 3768.97 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 4486.07 | 04-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6661.98 | 27-NOV-16:00 | 3768.97 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 4347.81 | 13-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 6693.29 | 18-DEC-16:00 | 3768.97 | 01-DEC-17:30 | 10035.17 | 01-DEC-08:09 | 0.00 | 4332.70 | 11-DEC-12:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5497.40 | 3768.97 | 10035.17 | 0.00 | 4321.23 | 0.00 | 0.00 | |||||
Maximum of Months | 6693.29 | 3768.97 | 10035.17 | 0.00 | 5357.98 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 12727.53 | 04-JAN-12:00 | 0.00 | 0.00 | 0.00 | 1702.65 | 14-JAN-12:39 | 0.00 | 01-JAN-00:10 |
February | 13803.48 | 28-FEB-14:00 | 0.00 | 0.00 | 0.00 | 1702.18 | 01-FEB-12:50 | 0.00 | 01-FEB-00:10 |
March | 15035.90 | 20-MAR-15:09 | 0.00 | 0.00 | 0.00 | 1699.84 | 01-MAR-12:09 | 0.00 | 01-MAR-00:10 |
April | 15438.64 | 11-APR-15:00 | 0.00 | 0.00 | 0.00 | 1695.75 | 01-APR-11:20 | 0.00 | 01-APR-00:10 |
May | 18589.03 | 06-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1691.34 | 01-MAY-11:39 | 0.00 | 01-MAY-00:10 |
June | 18274.83 | 13-JUN-15:09 | 0.00 | 0.00 | 0.00 | 1687.53 | 01-JUN-11:50 | 0.00 | 01-JUN-00:10 |
July | 12846.27 | 26-JUL-15:09 | 0.00 | 0.00 | 0.00 | 1685.59 | 31-JUL-11:50 | 0.00 | 01-JUL-00:10 |
August | 15308.21 | 15-AUG-11:00 | 0.00 | 0.00 | 0.00 | 1687.97 | 31-AUG-11:00 | 0.00 | 01-AUG-00:10 |
September | 14560.06 | 06-SEP-11:00 | 0.00 | 0.00 | 0.00 | 1691.89 | 30-SEP-11:09 | 0.00 | 01-SEP-00:10 |
October | 13698.13 | 04-OCT-11:00 | 0.00 | 0.00 | 0.00 | 1696.46 | 31-OCT-11:09 | 0.00 | 01-OCT-00:10 |
November | 12347.56 | 10-NOV-12:00 | 0.00 | 0.00 | 0.00 | 1700.15 | 28-NOV-12:20 | 0.00 | 01-NOV-00:10 |
December | 11929.03 | 12-DEC-12:00 | 0.00 | 0.00 | 0.00 | 1702.42 | 30-DEC-12:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11929.03 | 0.00 | 0.00 | 0.00 | 1685.59 | 0.00 | |||
Maximum of Months | 18589.03 | 0.00 | 0.00 | 0.00 | 1702.65 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 32504.18 | 05-JAN-15:09 | 4911.68 | 10035.17 | 0.00 | 0.00 | 4110.45 | 0.00 | 0.00 | 11767.41 | 0.00 |
February | 34074.20 | 28-FEB-14:00 | 4102.33 | 10035.17 | 0.00 | 0.00 | 4477.94 | 0.00 | 0.00 | 13803.48 | 0.00 |
March | 35423.35 | 28-MAR-15:50 | 4424.95 | 10035.17 | 0.00 | 0.00 | 4697.38 | 0.00 | 0.00 | 14690.00 | 0.00 |
April | 35949.42 | 17-APR-15:00 | 4710.08 | 10035.17 | 0.00 | 0.00 | 4738.75 | 0.00 | 0.00 | 14890.36 | 0.00 |
May | 39434.46 | 06-MAY-15:20 | 4059.60 | 10035.17 | 0.00 | 0.00 | 5334.24 | 0.00 | 0.00 | 18431.18 | 0.00 |
June | 39477.49 | 13-JUN-15:50 | 4460.47 | 10035.17 | 0.00 | 0.00 | 5270.99 | 0.00 | 0.00 | 18137.59 | 0.00 |
July | 32925.46 | 19-JUL-14:00 | 4571.99 | 10035.17 | 0.00 | 0.00 | 4235.41 | 0.00 | 0.00 | 12418.17 | 0.00 |
August | 35417.59 | 11-AUG-14:39 | 4289.85 | 10035.17 | 0.00 | 0.00 | 4657.08 | 0.00 | 0.00 | 14770.29 | 0.00 |
September | 34698.05 | 06-SEP-14:09 | 4122.04 | 10035.17 | 0.00 | 0.00 | 4577.42 | 0.00 | 0.00 | 14295.99 | 0.00 |
October | 33938.41 | 04-OCT-15:20 | 4386.02 | 10035.17 | 0.00 | 0.00 | 4452.26 | 0.00 | 0.00 | 13490.10 | 0.00 |
November | 32294.95 | 20-NOV-15:50 | 5610.26 | 10035.17 | 0.00 | 0.00 | 4088.42 | 0.00 | 0.00 | 10884.80 | 0.00 |
December | 31984.91 | 13-DEC-15:00 | 5923.39 | 10035.17 | 0.00 | 0.00 | 4019.86 | 0.00 | 0.00 | 10372.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 31984.91 | 4059.60 | 10035.17 | 0.00 | 0.00 | 4019.86 | 0.00 | 0.00 | 10372.94 | 0.00 | |
Maximum of Months | 39477.49 | 5923.39 | 10035.17 | 0.00 | 0.00 | 5334.24 | 0.00 | 0.00 | 18431.18 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 24.74 | 7.67 | 24.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 25.02 | 7.67 | 24.92 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 25.12 | 9.00 | 25.03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 25.33 | 7.17 | 25.22 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 25.28 | 9.50 | 25.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 25.43 | 9.33 | 25.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 25.06 | 7.83 | 25.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 25.15 | 9.33 | 25.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 25.01 | 7.67 | 25.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 25.01 | 8.00 | 24.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 24.86 | 8.17 | 24.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 24.71 | 6.83 | 24.71 |
Annual Sum or Average | 0.00 | 0.00 | 100.00 | 25.08 | 98.17 | 25.03 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 24.71 | 6.83 | 24.71 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 25.43 | 9.50 | 25.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 27.46 | 0.00 | 27.46 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 27.49 | 0.17 | 27.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 27.55 | 0.00 | 27.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 27.54 | 0.00 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 27.53 | 0.17 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 31.67 | 27.54 | 0.00 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 27.44 | 0.33 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.45 | 0.00 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 27.45 | 0.17 | 27.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.43 | 0.00 | 27.43 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 27.44 | 0.17 | 27.43 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27.46 | 0.17 | 27.46 |
Annual Sum or Average | 0.00 | 0.00 | 322.33 | 27.48 | 1.17 | 27.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27.43 | 0.00 | 27.43 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 27.55 | 0.33 | 27.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.00 | 24.05 | 300.00 | 23.94 | 43.00 | 23.95 |
February | 30.17 | 24.11 | 276.00 | 23.95 | 30.17 | 23.96 |
March | 62.50 | 24.07 | 324.00 | 23.96 | 62.50 | 23.97 |
April | 80.33 | 24.06 | 300.00 | 23.97 | 80.33 | 23.98 |
May | 135.83 | 24.02 | 312.00 | 23.97 | 135.83 | 23.98 |
June | 125.67 | 24.02 | 312.00 | 23.97 | 125.67 | 23.98 |
July | 76.33 | 24.04 | 300.00 | 23.96 | 76.33 | 23.97 |
August | 148.33 | 23.99 | 324.00 | 23.96 | 148.33 | 23.97 |
September | 110.17 | 24.00 | 300.00 | 23.96 | 110.17 | 23.97 |
October | 117.17 | 23.99 | 300.00 | 23.95 | 117.17 | 23.96 |
November | 83.50 | 24.01 | 288.00 | 23.95 | 83.50 | 23.96 |
December | 50.83 | 24.02 | 300.00 | 23.94 | 50.83 | 23.95 |
Annual Sum or Average | 1063.83 | 24.02 | 3636.00 | 23.96 | 1063.83 | 23.97 |
Minimum of Months | 30.17 | 23.99 | 276.00 | 23.94 | 30.17 | 23.95 |
Maximum of Months | 148.33 | 24.11 | 324.00 | 23.97 | 148.33 | 23.98 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 295.00 | 26.71 | 300.00 | 26.71 | 295.00 | 26.71 |
February | 273.17 | 26.72 | 276.00 | 26.72 | 273.17 | 26.72 |
March | 324.00 | 26.72 | 324.00 | 26.72 | 324.00 | 26.72 |
April | 300.00 | 26.71 | 300.00 | 26.71 | 300.00 | 26.71 |
May | 312.00 | 26.71 | 312.00 | 26.71 | 312.00 | 26.71 |
June | 312.00 | 26.71 | 312.00 | 26.71 | 312.00 | 26.71 |
July | 298.50 | 26.72 | 300.00 | 26.72 | 298.50 | 26.72 |
August | 324.00 | 26.72 | 324.00 | 26.72 | 324.00 | 26.72 |
September | 300.00 | 26.72 | 300.00 | 26.72 | 300.00 | 26.72 |
October | 300.00 | 26.72 | 300.00 | 26.72 | 300.00 | 26.72 |
November | 288.00 | 26.72 | 288.00 | 26.72 | 288.00 | 26.72 |
December | 299.33 | 26.70 | 300.00 | 26.70 | 299.33 | 26.70 |
Annual Sum or Average | 3626.00 | 26.72 | 3636.00 | 26.72 | 3626.00 | 26.72 |
Minimum of Months | 273.17 | 26.70 | 276.00 | 26.70 | 273.17 | 26.70 |
Maximum of Months | 324.00 | 26.72 | 324.00 | 26.72 | 324.00 | 26.72 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 30.40 | 300.00 | 30.40 | 300.00 | 30.40 |
February | 276.00 | 31.06 | 276.00 | 31.06 | 276.00 | 31.06 |
March | 324.00 | 31.52 | 324.00 | 31.52 | 324.00 | 31.52 |
April | 300.00 | 31.73 | 300.00 | 31.73 | 300.00 | 31.73 |
May | 312.00 | 31.71 | 312.00 | 31.71 | 312.00 | 31.71 |
June | 312.00 | 31.83 | 312.00 | 31.83 | 312.00 | 31.83 |
July | 300.00 | 30.44 | 300.00 | 30.44 | 300.00 | 30.44 |
August | 324.00 | 30.56 | 324.00 | 30.56 | 324.00 | 30.56 |
September | 300.00 | 30.63 | 300.00 | 30.63 | 300.00 | 30.63 |
October | 300.00 | 30.06 | 300.00 | 30.06 | 300.00 | 30.06 |
November | 288.00 | 30.13 | 288.00 | 30.13 | 288.00 | 30.13 |
December | 300.00 | 30.04 | 300.00 | 30.04 | 300.00 | 30.04 |
Annual Sum or Average | 3636.00 | 30.85 | 3636.00 | 30.85 | 3636.00 | 30.85 |
Minimum of Months | 276.00 | 30.04 | 276.00 | 30.04 | 276.00 | 30.04 |
Maximum of Months | 324.00 | 31.83 | 324.00 | 31.83 | 324.00 | 31.83 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.127704E+11 | 0.281218E+10 | 297.79 | 0.879119E+10 | 0.397918E+10 | 0.00 | 1.00 | 02-JAN-06:01 | 0.00 | 01-JAN-00:10 | 30721.00 | 02-JAN-06:02 | 19063.38 | 24-JAN-06:01 | 16294.57 | 02-JAN-06:03 | 5785.89 | 02-JAN-06:01 | 0.00 | 01-JAN-00:10 |
February | 0.123707E+11 | 0.276014E+10 | 276.26 | 0.861381E+10 | 0.375685E+10 | 0.00 | 1.00 | 01-FEB-06:01 | 0.00 | 01-FEB-00:10 | 30203.04 | 06-FEB-06:01 | 21182.14 | 23-FEB-06:01 | 14709.58 | 15-FEB-06:03 | 5757.92 | 16-FEB-06:01 | 0.00 | 01-FEB-00:10 |
March | 0.157747E+11 | 0.354135E+10 | 327.17 | 0.106663E+11 | 0.510835E+10 | 0.00 | 1.00 | 01-MAR-06:01 | 0.00 | 01-MAR-00:10 | 30430.44 | 25-MAR-05:01 | 18453.70 | 04-MAR-06:01 | 15672.76 | 27-MAR-05:04 | 5856.57 | 28-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.161818E+11 | 0.361390E+10 | 305.01 | 0.102338E+11 | 0.594801E+10 | 0.00 | 1.00 | 01-APR-05:01 | 0.00 | 01-APR-00:10 | 30439.15 | 24-APR-05:01 | 16430.94 | 27-APR-05:01 | 16619.87 | 03-APR-05:06 | 5856.57 | 03-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.182651E+11 | 0.404429E+10 | 317.82 | 0.107010E+11 | 0.756410E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:05 | 30691.93 | 18-MAY-05:02 | 16090.02 | 31-MAY-05:01 | 19532.95 | 22-MAY-05:07 | 6047.78 | 29-MAY-13:10 | 0.00 | 01-MAY-00:05 |
June | 0.185343E+11 | 0.411451E+10 | 317.77 | 0.109049E+11 | 0.762941E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:05 | 30721.00 | 21-JUN-05:01 | 15721.73 | 03-JUN-05:01 | 18734.07 | 10-JUN-05:08 | 6237.44 | 18-JUN-13:37 | 0.00 | 01-JUN-00:05 |
July | 0.145676E+11 | 0.315060E+10 | 299.89 | 0.921639E+10 | 0.535118E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 30452.22 | 24-JUL-05:01 | 17715.36 | 11-JUL-05:01 | 15577.14 | 24-JUL-05:04 | 5819.72 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 |
August | 0.177312E+11 | 0.381653E+10 | 323.60 | 0.100844E+11 | 0.764687E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 30691.93 | 04-AUG-05:01 | 15865.51 | 24-AUG-05:01 | 18226.28 | 07-AUG-05:07 | 5856.57 | 12-AUG-05:12 | 0.00 | 01-AUG-00:10 |
September | 0.156629E+11 | 0.338632E+10 | 300.79 | 0.927046E+10 | 0.639239E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 30527.97 | 22-SEP-05:01 | 16445.57 | 06-SEP-05:01 | 18031.65 | 25-SEP-05:09 | 5856.57 | 08-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 0.147730E+11 | 0.315552E+10 | 297.28 | 0.868012E+10 | 0.609290E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:05 | 30721.00 | 23-OCT-05:02 | 16211.26 | 11-OCT-05:01 | 17504.12 | 30-OCT-05:05 | 5830.49 | 05-OCT-05:01 | 0.00 | 01-OCT-00:05 |
November | 0.135016E+11 | 0.290930E+10 | 284.21 | 0.842776E+10 | 0.507388E+10 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 30604.37 | 24-NOV-06:01 | 17865.48 | 25-NOV-06:01 | 17870.07 | 13-NOV-06:06 | 5826.63 | 08-NOV-06:01 | 0.00 | 01-NOV-00:10 |
December | 0.124919E+11 | 0.272578E+10 | 296.17 | 0.839406E+10 | 0.409781E+10 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 | 30721.00 | 11-DEC-06:02 | 18392.23 | 21-DEC-06:01 | 16067.81 | 11-DEC-06:03 | 5785.89 | 11-DEC-06:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.182625E+12 | 0.400304E+11 | 3643.78 | 0.113984E+12 | 0.686409E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.123707E+11 | 0.272578E+10 | 276.26 | 0.839406E+10 | 0.375685E+10 | 0.00 | 1.00 | 0.00 | 30203.04 | 15721.73 | 14709.58 | 5757.92 | 0.00 | |||||||
Maximum of Months | 0.185343E+11 | 0.411451E+10 | 327.17 | 0.109049E+11 | 0.764687E+10 | 0.00 | 1.00 | 0.00 | 30721.00 | 21182.14 | 19532.95 | 6237.44 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.310857E+11 | 0.710930E+10 | 398.42 | 0.207032E+11 | 0.103825E+11 | 0.00 | 1.00 | 01-JAN-11:05 | 0.00 | 01-JAN-00:10 | 74625.40 | 15-JAN-11:23 | 59951.89 | 16-JAN-15:23 | 28342.04 | 22-JAN-08:47 | 16457.78 | 08-JAN-11:23 | 0.00 | 01-JAN-00:10 |
February | 0.337861E+11 | 0.775537E+10 | 405.97 | 0.228016E+11 | 0.109845E+11 | 0.00 | 1.00 | 01-FEB-18:10 | 0.00 | 01-FEB-00:15 | 80884.54 | 16-FEB-06:01 | 57149.80 | 26-FEB-14:43 | 35262.53 | 16-FEB-06:01 | 16918.84 | 26-FEB-14:43 | 0.00 | 01-FEB-00:10 |
March | 0.449406E+11 | 0.103105E+11 | 494.90 | 0.294058E+11 | 0.155348E+11 | 0.00 | 1.00 | 01-MAR-01:33 | 0.00 | 01-MAR-00:20 | 82737.11 | 25-MAR-05:10 | 57187.36 | 19-MAR-14:12 | 39651.50 | 25-MAR-05:10 | 17160.83 | 26-MAR-13:43 | 0.00 | 01-MAR-00:10 |
April | 0.500289E+11 | 0.113446E+11 | 522.65 | 0.304540E+11 | 0.195749E+11 | 0.00 | 1.00 | 01-APR-00:30 | 0.00 | 01-APR-00:15 | 81073.66 | 06-APR-05:08 | 54785.14 | 23-APR-15:02 | 36972.85 | 06-APR-05:08 | 17246.65 | 02-APR-15:02 | 0.00 | 01-APR-00:10 |
May | 0.542454E+11 | 0.121728E+11 | 533.03 | 0.303747E+11 | 0.238707E+11 | 0.00 | 1.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:10 | 84746.12 | 04-MAY-05:09 | 54337.85 | 07-MAY-13:02 | 46414.73 | 19-MAY-05:18 | 17373.64 | 29-MAY-11:53 | 0.00 | 01-MAY-00:05 |
June | 0.566092E+11 | 0.126554E+11 | 533.41 | 0.317352E+11 | 0.248740E+11 | 0.00 | 1.00 | 01-JUN-03:33 | 0.00 | 01-JUN-00:10 | 84623.77 | 10-JUN-05:07 | 50930.46 | 18-JUN-14:23 | 45311.40 | 10-JUN-05:07 | 17682.02 | 18-JUN-13:43 | 0.00 | 01-JUN-00:05 |
July | 0.395717E+11 | 0.885419E+10 | 487.76 | 0.240055E+11 | 0.155662E+11 | 0.00 | 1.00 | 01-JUL-05:08 | 0.00 | 01-JUL-00:10 | 84569.03 | 01-JUL-05:08 | 54158.71 | 16-JUL-15:43 | 44303.00 | 01-JUL-05:08 | 17027.55 | 26-JUL-17:08 | 0.00 | 01-JUL-00:10 |
August | 0.446351E+11 | 0.979375E+10 | 469.20 | 0.236315E+11 | 0.210036E+11 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 84951.22 | 25-AUG-05:01 | 51252.94 | 27-AUG-16:03 | 45251.86 | 25-AUG-05:01 | 17520.32 | 13-AUG-12:53 | 0.00 | 01-AUG-00:10 |
September | 0.419810E+11 | 0.928843E+10 | 471.38 | 0.235496E+11 | 0.184314E+11 | 0.00 | 1.00 | 01-SEP-12:10 | 0.00 | 01-SEP-00:10 | 82564.17 | 20-SEP-05:01 | 53465.32 | 10-SEP-14:02 | 38992.51 | 20-SEP-05:01 | 17120.73 | 04-SEP-15:35 | 0.00 | 01-SEP-00:10 |
October | 0.358371E+11 | 0.790598E+10 | 436.88 | 0.198527E+11 | 0.159844E+11 | 0.00 | 1.00 | 01-OCT-08:25 | 0.00 | 01-OCT-00:05 | 83625.96 | 26-OCT-05:09 | 52657.16 | 08-OCT-14:23 | 41598.59 | 26-OCT-05:09 | 17079.74 | 29-OCT-12:55 | 0.00 | 01-OCT-00:05 |
November | 0.325707E+11 | 0.727216E+10 | 405.47 | 0.193575E+11 | 0.132132E+11 | 0.00 | 1.00 | 01-NOV-17:12 | 0.00 | 01-NOV-00:10 | 82944.26 | 13-NOV-06:06 | 54917.28 | 19-NOV-13:43 | 40002.39 | 13-NOV-06:06 | 16664.12 | 12-NOV-14:13 | 0.00 | 01-NOV-00:10 |
December | 0.294019E+11 | 0.668054E+10 | 383.62 | 0.188117E+11 | 0.105902E+11 | 0.00 | 1.00 | 03-DEC-09:05 | 0.00 | 01-DEC-00:10 | 80221.49 | 09-DEC-06:10 | 56576.64 | 03-DEC-16:23 | 33010.83 | 09-DEC-06:10 | 16695.03 | 24-DEC-12:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.494693E+12 | 0.111143E+12 | 5542.68 | 0.294683E+12 | 0.200010E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.294019E+11 | 0.668054E+10 | 383.62 | 0.188117E+11 | 0.103825E+11 | 0.00 | 1.00 | 0.00 | 74625.40 | 50930.46 | 28342.04 | 16457.78 | 0.00 | |||||||
Maximum of Months | 0.566092E+11 | 0.126554E+11 | 533.41 | 0.317352E+11 | 0.248740E+11 | 0.00 | 1.00 | 0.00 | 84951.22 | 59951.89 | 46414.73 | 17682.02 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.80 | 23.59 | 43.21 | 136.72 | 28.33 | 0.00 | 0.00 | 0.00 |
February | 73.18 | 25.90 | 47.28 | 153.94 | 23.98 | 0.00 | 0.00 | 0.00 |
March | 82.08 | 32.45 | 49.63 | 176.58 | 19.36 | 0.00 | 0.00 | 0.00 |
April | 82.33 | 31.47 | 50.86 | 177.45 | 11.98 | 0.00 | 0.00 | 0.00 |
May | 70.13 | 20.77 | 49.36 | 155.73 | 12.36 | 0.00 | 0.00 | 0.00 |
June | 75.96 | 26.16 | 49.80 | 166.73 | 13.13 | 0.00 | 0.00 | 0.00 |
July | 64.83 | 15.30 | 49.53 | 134.42 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 70.52 | 20.91 | 49.61 | 144.69 | 16.73 | 0.00 | 0.00 | 0.00 |
September | 65.93 | 18.24 | 47.69 | 138.44 | 16.63 | 0.00 | 0.00 | 0.00 |
October | 61.97 | 15.97 | 46.01 | 124.60 | 19.61 | 0.00 | 0.00 | 0.00 |
November | 60.35 | 16.40 | 43.95 | 122.46 | 22.05 | 0.00 | 0.00 | 0.00 |
December | 61.88 | 20.27 | 41.62 | 126.28 | 30.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69.62 | 22.25 | 47.37 | 146.39 | 19.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.35 | 15.30 | 41.62 | 122.46 | 11.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.33 | 32.45 | 50.86 | 177.45 | 30.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.80 | 23.59 | 43.21 | 136.72 | 28.33 | 0.00 | 0.00 | 0.00 |
February | 73.18 | 25.90 | 47.28 | 153.94 | 23.98 | 0.00 | 0.00 | 0.00 |
March | 82.08 | 32.45 | 49.63 | 176.58 | 19.36 | 0.00 | 0.00 | 0.00 |
April | 82.33 | 31.47 | 50.86 | 177.45 | 11.98 | 0.00 | 0.00 | 0.00 |
May | 70.13 | 20.77 | 49.36 | 155.73 | 12.36 | 0.00 | 0.00 | 0.00 |
June | 75.96 | 26.16 | 49.80 | 166.73 | 13.13 | 0.00 | 0.00 | 0.00 |
July | 64.83 | 15.30 | 49.53 | 134.42 | 18.82 | 0.00 | 0.00 | 0.00 |
August | 70.52 | 20.91 | 49.61 | 144.69 | 16.73 | 0.00 | 0.00 | 0.00 |
September | 65.93 | 18.24 | 47.69 | 138.44 | 16.63 | 0.00 | 0.00 | 0.00 |
October | 61.97 | 15.97 | 46.01 | 124.60 | 19.61 | 0.00 | 0.00 | 0.00 |
November | 60.35 | 16.40 | 43.95 | 122.46 | 22.05 | 0.00 | 0.00 | 0.00 |
December | 61.88 | 20.27 | 41.62 | 126.28 | 30.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69.62 | 22.25 | 47.37 | 146.39 | 19.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.35 | 15.30 | 41.62 | 122.46 | 11.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.33 | 32.45 | 50.86 | 177.45 | 30.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.89 | 0.00 | 19.89 | 41.26 | 16.46 | 0.00 | 0.00 | 0.00 |
February | 21.22 | 0.00 | 21.22 | 46.61 | 13.96 | 0.00 | 0.00 | 0.00 |
March | 21.80 | 0.00 | 21.79 | 50.94 | 11.19 | 0.00 | 0.00 | 0.00 |
April | 24.01 | 0.45 | 23.55 | 57.01 | 6.91 | 0.00 | 0.00 | 0.00 |
May | 30.47 | 3.33 | 27.14 | 73.86 | 7.22 | 0.00 | 0.00 | 0.00 |
June | 37.00 | 7.39 | 29.61 | 88.84 | 7.73 | 0.00 | 0.00 | 0.00 |
July | 31.81 | 3.24 | 28.57 | 69.26 | 10.85 | 0.00 | 0.00 | 0.00 |
August | 26.47 | 1.30 | 25.17 | 57.87 | 9.77 | 0.00 | 0.00 | 0.00 |
September | 22.41 | 0.03 | 22.38 | 49.57 | 9.74 | 0.00 | 0.00 | 0.00 |
October | 21.55 | 0.00 | 21.55 | 44.24 | 11.45 | 0.00 | 0.00 | 0.00 |
November | 20.40 | 0.00 | 20.40 | 42.04 | 12.84 | 0.00 | 0.00 | 0.00 |
December | 19.33 | 0.00 | 19.33 | 39.77 | 17.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.71 | 1.32 | 23.40 | 55.13 | 11.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.33 | 0.00 | 19.33 | 39.77 | 6.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.00 | 7.39 | 29.61 | 88.84 | 17.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.89 | 0.00 | 19.89 | 41.26 | 16.46 | 0.00 | 0.00 | 0.00 |
February | 21.22 | 0.00 | 21.22 | 46.61 | 13.96 | 0.00 | 0.00 | 0.00 |
March | 21.80 | 0.00 | 21.79 | 50.94 | 11.19 | 0.00 | 0.00 | 0.00 |
April | 24.01 | 0.45 | 23.55 | 57.01 | 6.91 | 0.00 | 0.00 | 0.00 |
May | 30.47 | 3.33 | 27.14 | 73.86 | 7.21 | 0.00 | 0.00 | 0.00 |
June | 37.00 | 7.39 | 29.61 | 88.84 | 7.73 | 0.00 | 0.00 | 0.00 |
July | 31.81 | 3.24 | 28.57 | 69.26 | 10.85 | 0.00 | 0.00 | 0.00 |
August | 26.47 | 1.30 | 25.17 | 57.87 | 9.77 | 0.00 | 0.00 | 0.00 |
September | 22.41 | 0.03 | 22.38 | 49.56 | 9.74 | 0.00 | 0.00 | 0.00 |
October | 21.55 | 0.00 | 21.55 | 44.23 | 11.45 | 0.00 | 0.00 | 0.00 |
November | 20.39 | 0.00 | 20.39 | 42.04 | 12.84 | 0.00 | 0.00 | 0.00 |
December | 19.33 | 0.00 | 19.33 | 39.77 | 17.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.71 | 1.32 | 23.39 | 55.13 | 11.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.33 | 0.00 | 19.33 | 39.77 | 6.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.00 | 7.39 | 29.61 | 88.84 | 17.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.80 | 21.52 | 23.28 | 79.78 | 17.49 | 0.00 | 0.00 | 0.00 |
February | 51.67 | 26.88 | 24.79 | 93.28 | 17.70 | 0.00 | 0.00 | 0.00 |
March | 60.11 | 35.38 | 24.73 | 109.18 | 14.71 | 0.00 | 0.00 | 0.00 |
April | 60.74 | 34.13 | 26.61 | 111.03 | 10.74 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 22.18 | 28.63 | 94.25 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 54.96 | 27.30 | 27.66 | 101.57 | 9.24 | 0.00 | 0.00 | 0.00 |
July | 46.19 | 15.39 | 30.80 | 83.89 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 51.05 | 22.01 | 29.04 | 89.77 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 47.19 | 18.43 | 28.76 | 85.90 | 10.92 | 0.00 | 0.00 | 0.00 |
October | 43.12 | 15.37 | 27.75 | 75.52 | 11.92 | 0.00 | 0.00 | 0.00 |
November | 41.03 | 15.54 | 25.49 | 72.94 | 14.18 | 0.00 | 0.00 | 0.00 |
December | 41.50 | 18.67 | 22.82 | 73.77 | 18.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.39 | 22.69 | 26.71 | 89.17 | 13.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.03 | 15.37 | 22.82 | 72.94 | 9.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.74 | 35.38 | 30.80 | 111.03 | 18.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.80 | 21.52 | 23.28 | 79.78 | 17.49 | 0.00 | 0.00 | 0.00 |
February | 51.67 | 26.88 | 24.79 | 93.28 | 17.70 | 0.00 | 0.00 | 0.00 |
March | 60.11 | 35.38 | 24.73 | 109.18 | 14.71 | 0.00 | 0.00 | 0.00 |
April | 60.74 | 34.13 | 26.61 | 111.03 | 10.74 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 22.18 | 28.63 | 94.25 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 54.96 | 27.30 | 27.66 | 101.57 | 9.24 | 0.00 | 0.00 | 0.00 |
July | 46.19 | 15.39 | 30.80 | 83.89 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 51.05 | 22.01 | 29.04 | 89.77 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 47.19 | 18.43 | 28.76 | 85.90 | 10.92 | 0.00 | 0.00 | 0.00 |
October | 43.12 | 15.37 | 27.75 | 75.52 | 11.92 | 0.00 | 0.00 | 0.00 |
November | 41.03 | 15.54 | 25.49 | 72.94 | 14.18 | 0.00 | 0.00 | 0.00 |
December | 41.50 | 18.67 | 22.82 | 73.77 | 18.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.39 | 22.69 | 26.71 | 89.17 | 13.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.03 | 15.37 | 22.82 | 72.94 | 9.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.74 | 35.38 | 30.80 | 111.03 | 18.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.80 | 21.52 | 23.28 | 79.78 | 17.49 | 0.00 | 0.00 | 0.00 |
February | 51.67 | 26.88 | 24.79 | 93.28 | 17.70 | 0.00 | 0.00 | 0.00 |
March | 60.11 | 35.38 | 24.73 | 109.18 | 14.71 | 0.00 | 0.00 | 0.00 |
April | 60.74 | 34.13 | 26.61 | 111.03 | 10.74 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 22.18 | 28.63 | 94.25 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 54.96 | 27.30 | 27.66 | 101.57 | 9.24 | 0.00 | 0.00 | 0.00 |
July | 46.19 | 15.39 | 30.80 | 83.89 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 51.05 | 22.01 | 29.04 | 89.77 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 47.19 | 18.43 | 28.76 | 85.90 | 10.92 | 0.00 | 0.00 | 0.00 |
October | 43.12 | 15.37 | 27.75 | 75.52 | 11.92 | 0.00 | 0.00 | 0.00 |
November | 41.03 | 15.54 | 25.49 | 72.94 | 14.18 | 0.00 | 0.00 | 0.00 |
December | 41.50 | 18.67 | 22.82 | 73.77 | 18.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.39 | 22.69 | 26.71 | 89.17 | 13.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.03 | 15.37 | 22.82 | 72.94 | 9.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.74 | 35.38 | 30.80 | 111.03 | 18.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.80 | 21.52 | 23.28 | 79.78 | 17.49 | 0.00 | 0.00 | 0.00 |
February | 51.67 | 26.88 | 24.79 | 93.28 | 17.70 | 0.00 | 0.00 | 0.00 |
March | 60.11 | 35.38 | 24.73 | 109.18 | 14.71 | 0.00 | 0.00 | 0.00 |
April | 60.74 | 34.13 | 26.61 | 111.03 | 10.74 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 22.18 | 28.63 | 94.25 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 54.96 | 27.30 | 27.66 | 101.57 | 9.24 | 0.00 | 0.00 | 0.00 |
July | 46.19 | 15.39 | 30.80 | 83.89 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 51.05 | 22.01 | 29.04 | 89.77 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 47.19 | 18.43 | 28.76 | 85.90 | 10.92 | 0.00 | 0.00 | 0.00 |
October | 43.12 | 15.37 | 27.75 | 75.52 | 11.92 | 0.00 | 0.00 | 0.00 |
November | 41.03 | 15.54 | 25.49 | 72.94 | 14.18 | 0.00 | 0.00 | 0.00 |
December | 41.50 | 18.67 | 22.82 | 73.77 | 18.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.39 | 22.69 | 26.71 | 89.17 | 13.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.03 | 15.37 | 22.82 | 72.94 | 9.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.74 | 35.38 | 30.80 | 111.03 | 18.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.80 | 21.52 | 23.28 | 79.78 | 17.49 | 0.00 | 0.00 | 0.00 |
February | 51.67 | 26.88 | 24.79 | 93.28 | 17.70 | 0.00 | 0.00 | 0.00 |
March | 60.11 | 35.38 | 24.73 | 109.18 | 14.71 | 0.00 | 0.00 | 0.00 |
April | 60.74 | 34.13 | 26.61 | 111.03 | 10.74 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 22.18 | 28.63 | 94.25 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 54.96 | 27.30 | 27.66 | 101.57 | 9.24 | 0.00 | 0.00 | 0.00 |
July | 46.19 | 15.39 | 30.80 | 83.89 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 51.05 | 22.01 | 29.04 | 89.77 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 47.19 | 18.43 | 28.76 | 85.90 | 10.92 | 0.00 | 0.00 | 0.00 |
October | 43.12 | 15.37 | 27.75 | 75.52 | 11.92 | 0.00 | 0.00 | 0.00 |
November | 41.03 | 15.54 | 25.49 | 72.94 | 14.18 | 0.00 | 0.00 | 0.00 |
December | 41.50 | 18.67 | 22.82 | 73.77 | 18.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.39 | 22.69 | 26.71 | 89.17 | 13.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.03 | 15.37 | 22.82 | 72.94 | 9.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.74 | 35.38 | 30.80 | 111.03 | 18.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.80 | 21.52 | 23.28 | 79.78 | 17.49 | 0.00 | 0.00 | 0.00 |
February | 51.67 | 26.88 | 24.79 | 93.28 | 17.70 | 0.00 | 0.00 | 0.00 |
March | 60.11 | 35.38 | 24.73 | 109.18 | 14.71 | 0.00 | 0.00 | 0.00 |
April | 60.74 | 34.13 | 26.61 | 111.03 | 10.74 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 22.18 | 28.63 | 94.25 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 54.96 | 27.30 | 27.66 | 101.57 | 9.24 | 0.00 | 0.00 | 0.00 |
July | 46.19 | 15.39 | 30.80 | 83.89 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 51.05 | 22.01 | 29.04 | 89.77 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 47.19 | 18.43 | 28.76 | 85.90 | 10.92 | 0.00 | 0.00 | 0.00 |
October | 43.12 | 15.37 | 27.75 | 75.52 | 11.92 | 0.00 | 0.00 | 0.00 |
November | 41.03 | 15.54 | 25.49 | 72.94 | 14.18 | 0.00 | 0.00 | 0.00 |
December | 41.50 | 18.67 | 22.82 | 73.77 | 18.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.39 | 22.69 | 26.71 | 89.17 | 13.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.03 | 15.37 | 22.82 | 72.94 | 9.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.74 | 35.38 | 30.80 | 111.03 | 18.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.80 | 21.52 | 23.28 | 79.78 | 17.49 | 0.00 | 0.00 | 0.00 |
February | 51.67 | 26.88 | 24.79 | 93.28 | 17.70 | 0.00 | 0.00 | 0.00 |
March | 60.11 | 35.38 | 24.73 | 109.18 | 14.71 | 0.00 | 0.00 | 0.00 |
April | 60.74 | 34.13 | 26.61 | 111.03 | 10.74 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 22.18 | 28.63 | 94.25 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 54.96 | 27.30 | 27.66 | 101.57 | 9.24 | 0.00 | 0.00 | 0.00 |
July | 46.19 | 15.39 | 30.80 | 83.89 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 51.05 | 22.01 | 29.04 | 89.77 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 47.19 | 18.43 | 28.76 | 85.90 | 10.92 | 0.00 | 0.00 | 0.00 |
October | 43.12 | 15.37 | 27.75 | 75.52 | 11.92 | 0.00 | 0.00 | 0.00 |
November | 41.03 | 15.54 | 25.49 | 72.94 | 14.18 | 0.00 | 0.00 | 0.00 |
December | 41.50 | 18.67 | 22.82 | 73.77 | 18.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.39 | 22.69 | 26.71 | 89.17 | 13.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.03 | 15.37 | 22.82 | 72.94 | 9.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.74 | 35.38 | 30.80 | 111.03 | 18.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.80 | 21.52 | 23.28 | 79.78 | 17.49 | 0.00 | 0.00 | 0.00 |
February | 51.67 | 26.88 | 24.79 | 93.28 | 17.70 | 0.00 | 0.00 | 0.00 |
March | 60.11 | 35.38 | 24.73 | 109.18 | 14.71 | 0.00 | 0.00 | 0.00 |
April | 60.74 | 34.13 | 26.61 | 111.03 | 10.74 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 22.18 | 28.63 | 94.25 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 54.96 | 27.30 | 27.66 | 101.57 | 9.24 | 0.00 | 0.00 | 0.00 |
July | 46.19 | 15.39 | 30.80 | 83.89 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 51.05 | 22.01 | 29.04 | 89.77 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 47.19 | 18.43 | 28.76 | 85.90 | 10.92 | 0.00 | 0.00 | 0.00 |
October | 43.12 | 15.37 | 27.75 | 75.52 | 11.92 | 0.00 | 0.00 | 0.00 |
November | 41.03 | 15.54 | 25.49 | 72.94 | 14.18 | 0.00 | 0.00 | 0.00 |
December | 41.50 | 18.67 | 22.82 | 73.77 | 18.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.39 | 22.69 | 26.71 | 89.17 | 13.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.03 | 15.37 | 22.82 | 72.94 | 9.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.74 | 35.38 | 30.80 | 111.03 | 18.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.80 | 21.52 | 23.28 | 79.78 | 17.49 | 0.00 | 0.00 | 0.00 |
February | 51.67 | 26.88 | 24.79 | 93.28 | 17.70 | 0.00 | 0.00 | 0.00 |
March | 60.11 | 35.38 | 24.73 | 109.18 | 14.71 | 0.00 | 0.00 | 0.00 |
April | 60.74 | 34.13 | 26.61 | 111.03 | 10.74 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 22.18 | 28.63 | 94.25 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 54.96 | 27.30 | 27.66 | 101.57 | 9.24 | 0.00 | 0.00 | 0.00 |
July | 46.19 | 15.39 | 30.80 | 83.89 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 51.05 | 22.01 | 29.04 | 89.77 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 47.19 | 18.43 | 28.76 | 85.90 | 10.92 | 0.00 | 0.00 | 0.00 |
October | 43.12 | 15.37 | 27.75 | 75.52 | 11.92 | 0.00 | 0.00 | 0.00 |
November | 41.03 | 15.54 | 25.49 | 72.94 | 14.18 | 0.00 | 0.00 | 0.00 |
December | 41.50 | 18.67 | 22.82 | 73.77 | 18.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.39 | 22.69 | 26.71 | 89.17 | 13.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.03 | 15.37 | 22.82 | 72.94 | 9.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.74 | 35.38 | 30.80 | 111.03 | 18.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.80 | 21.52 | 23.28 | 79.78 | 17.49 | 0.00 | 0.00 | 0.00 |
February | 51.67 | 26.88 | 24.79 | 93.28 | 17.70 | 0.00 | 0.00 | 0.00 |
March | 60.11 | 35.38 | 24.73 | 109.18 | 14.71 | 0.00 | 0.00 | 0.00 |
April | 60.74 | 34.13 | 26.61 | 111.03 | 10.74 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 22.18 | 28.63 | 94.25 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 54.96 | 27.30 | 27.66 | 101.57 | 9.24 | 0.00 | 0.00 | 0.00 |
July | 46.19 | 15.39 | 30.80 | 83.89 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 51.05 | 22.01 | 29.04 | 89.77 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 47.19 | 18.43 | 28.76 | 85.90 | 10.92 | 0.00 | 0.00 | 0.00 |
October | 43.12 | 15.37 | 27.75 | 75.52 | 11.92 | 0.00 | 0.00 | 0.00 |
November | 41.03 | 15.54 | 25.49 | 72.94 | 14.18 | 0.00 | 0.00 | 0.00 |
December | 41.50 | 18.67 | 22.82 | 73.77 | 18.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.39 | 22.69 | 26.71 | 89.17 | 13.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.03 | 15.37 | 22.82 | 72.94 | 9.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.74 | 35.38 | 30.80 | 111.03 | 18.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.80 | 21.52 | 23.28 | 79.78 | 17.49 | 0.00 | 0.00 | 0.00 |
February | 51.67 | 26.88 | 24.79 | 93.28 | 17.70 | 0.00 | 0.00 | 0.00 |
March | 60.11 | 35.38 | 24.73 | 109.18 | 14.71 | 0.00 | 0.00 | 0.00 |
April | 60.74 | 34.13 | 26.61 | 111.03 | 10.74 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 22.18 | 28.63 | 94.25 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 54.96 | 27.30 | 27.66 | 101.57 | 9.24 | 0.00 | 0.00 | 0.00 |
July | 46.19 | 15.39 | 30.80 | 83.89 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 51.05 | 22.01 | 29.04 | 89.77 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 47.19 | 18.43 | 28.76 | 85.90 | 10.92 | 0.00 | 0.00 | 0.00 |
October | 43.12 | 15.37 | 27.75 | 75.52 | 11.92 | 0.00 | 0.00 | 0.00 |
November | 41.03 | 15.54 | 25.49 | 72.94 | 14.18 | 0.00 | 0.00 | 0.00 |
December | 41.50 | 18.67 | 22.82 | 73.77 | 18.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.39 | 22.69 | 26.71 | 89.17 | 13.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.03 | 15.37 | 22.82 | 72.94 | 9.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.74 | 35.38 | 30.80 | 111.03 | 18.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.80 | 21.52 | 23.28 | 79.78 | 17.49 | 0.00 | 0.00 | 0.00 |
February | 51.67 | 26.88 | 24.79 | 93.28 | 17.70 | 0.00 | 0.00 | 0.00 |
March | 60.11 | 35.38 | 24.73 | 109.18 | 14.71 | 0.00 | 0.00 | 0.00 |
April | 60.74 | 34.13 | 26.61 | 111.03 | 10.74 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 22.18 | 28.63 | 94.25 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 54.96 | 27.30 | 27.66 | 101.57 | 9.24 | 0.00 | 0.00 | 0.00 |
July | 46.19 | 15.39 | 30.80 | 83.89 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 51.05 | 22.01 | 29.04 | 89.77 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 47.19 | 18.43 | 28.76 | 85.90 | 10.92 | 0.00 | 0.00 | 0.00 |
October | 43.12 | 15.37 | 27.75 | 75.52 | 11.92 | 0.00 | 0.00 | 0.00 |
November | 41.03 | 15.54 | 25.49 | 72.94 | 14.18 | 0.00 | 0.00 | 0.00 |
December | 41.50 | 18.67 | 22.82 | 73.77 | 18.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.39 | 22.69 | 26.71 | 89.17 | 13.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.03 | 15.37 | 22.82 | 72.94 | 9.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.74 | 35.38 | 30.80 | 111.03 | 18.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.80 | 21.52 | 23.28 | 79.78 | 17.49 | 0.00 | 0.00 | 0.00 |
February | 51.67 | 26.88 | 24.79 | 93.28 | 17.70 | 0.00 | 0.00 | 0.00 |
March | 60.11 | 35.38 | 24.73 | 109.18 | 14.71 | 0.00 | 0.00 | 0.00 |
April | 60.74 | 34.13 | 26.61 | 111.03 | 10.74 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 22.18 | 28.63 | 94.25 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 54.96 | 27.30 | 27.66 | 101.57 | 9.24 | 0.00 | 0.00 | 0.00 |
July | 46.19 | 15.39 | 30.80 | 83.89 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 51.05 | 22.01 | 29.04 | 89.77 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 47.19 | 18.43 | 28.76 | 85.90 | 10.92 | 0.00 | 0.00 | 0.00 |
October | 43.12 | 15.37 | 27.75 | 75.52 | 11.92 | 0.00 | 0.00 | 0.00 |
November | 41.03 | 15.54 | 25.49 | 72.94 | 14.18 | 0.00 | 0.00 | 0.00 |
December | 41.50 | 18.67 | 22.82 | 73.77 | 18.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.39 | 22.69 | 26.71 | 89.17 | 13.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.03 | 15.37 | 22.82 | 72.94 | 9.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.74 | 35.38 | 30.80 | 111.03 | 18.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.80 | 21.52 | 23.28 | 79.78 | 17.49 | 0.00 | 0.00 | 0.00 |
February | 51.67 | 26.88 | 24.79 | 93.28 | 17.70 | 0.00 | 0.00 | 0.00 |
March | 60.11 | 35.38 | 24.73 | 109.18 | 14.71 | 0.00 | 0.00 | 0.00 |
April | 60.74 | 34.13 | 26.61 | 111.03 | 10.74 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 22.18 | 28.63 | 94.25 | 9.44 | 0.00 | 0.00 | 0.00 |
June | 54.96 | 27.30 | 27.66 | 101.57 | 9.24 | 0.00 | 0.00 | 0.00 |
July | 46.19 | 15.39 | 30.80 | 83.89 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 51.05 | 22.01 | 29.04 | 89.77 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 47.19 | 18.43 | 28.76 | 85.90 | 10.92 | 0.00 | 0.00 | 0.00 |
October | 43.12 | 15.37 | 27.75 | 75.52 | 11.92 | 0.00 | 0.00 | 0.00 |
November | 41.03 | 15.54 | 25.49 | 72.94 | 14.18 | 0.00 | 0.00 | 0.00 |
December | 41.50 | 18.67 | 22.82 | 73.77 | 18.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.39 | 22.69 | 26.71 | 89.17 | 13.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.03 | 15.37 | 22.82 | 72.94 | 9.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.74 | 35.38 | 30.80 | 111.03 | 18.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.78 | 48.68 | 53.09 | 141.35 | 38.97 | 0.00 | 0.00 | 0.00 |
February | 117.12 | 60.58 | 56.54 | 163.92 | 40.53 | 0.00 | 0.00 | 0.00 |
March | 135.93 | 79.52 | 56.40 | 190.20 | 35.02 | 0.00 | 0.00 | 0.00 |
April | 137.38 | 76.70 | 60.68 | 192.03 | 28.00 | 0.33 | 0.00 | 0.00 |
May | 115.18 | 49.89 | 65.29 | 159.90 | 26.28 | 157.17 | 0.00 | 0.00 |
June | 124.49 | 61.41 | 63.08 | 173.78 | 25.28 | 68.83 | 0.00 | 0.00 |
July | 104.87 | 34.63 | 70.24 | 147.12 | 28.64 | 4.33 | 0.00 | 0.00 |
August | 115.72 | 49.49 | 66.23 | 154.97 | 27.50 | 86.67 | 0.00 | 0.00 |
September | 107.03 | 41.44 | 65.60 | 149.59 | 27.54 | 29.67 | 0.00 | 0.00 |
October | 97.91 | 34.62 | 63.29 | 131.11 | 29.73 | 67.50 | 0.00 | 0.00 |
November | 93.25 | 35.13 | 58.13 | 128.31 | 32.76 | 22.67 | 0.00 | 0.00 |
December | 94.36 | 42.31 | 52.06 | 130.87 | 39.33 | 36.33 | 0.00 | 0.00 |
Annual Sum or Average | 112.01 | 51.09 | 60.91 | 155.13 | 31.59 | 473.50 | 0.00 | 0.00 |
Minimum of Months | 93.25 | 34.62 | 52.06 | 128.31 | 25.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.38 | 79.52 | 70.24 | 192.03 | 40.53 | 157.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.178922E+09 | 63184799.48 | 0.115737E+09 | 0.366180E+09 | 75888593.66 |
February | 0.177039E+09 | 62659275.77 | 0.114380E+09 | 0.372409E+09 | 58018386.55 |
March | 0.219832E+09 | 86910756.02 | 0.132921E+09 | 0.472952E+09 | 51867156.97 |
April | 0.213387E+09 | 81563796.51 | 0.131823E+09 | 0.459947E+09 | 31049948.70 |
May | 0.187840E+09 | 55636303.28 | 0.132204E+09 | 0.417100E+09 | 33092117.06 |
June | 0.196892E+09 | 67800815.94 | 0.129091E+09 | 0.432165E+09 | 34045521.95 |
July | 0.173640E+09 | 40989388.99 | 0.132650E+09 | 0.360038E+09 | 50414793.34 |
August | 0.188883E+09 | 56004744.74 | 0.132879E+09 | 0.387544E+09 | 44805103.97 |
September | 0.170883E+09 | 47283009.57 | 0.123600E+09 | 0.358831E+09 | 43111957.63 |
October | 0.165993E+09 | 42769475.92 | 0.123223E+09 | 0.333717E+09 | 52528766.18 |
November | 0.156430E+09 | 42507184.71 | 0.113923E+09 | 0.317417E+09 | 57157883.05 |
December | 0.165752E+09 | 54281676.98 | 0.111470E+09 | 0.338230E+09 | 81091776.81 |
Annual Sum or Average | 0.219549E+10 | 0.701591E+09 | 0.149390E+10 | 0.461653E+10 | 0.613072E+09 |
Minimum of Months | 0.156430E+09 | 40989388.99 | 0.111470E+09 | 0.317417E+09 | 31049948.70 |
Maximum of Months | 0.219832E+09 | 86910756.02 | 0.132921E+09 | 0.472952E+09 | 81091776.81 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.178922E+09 | 63184799.48 | 0.115737E+09 | 0.366180E+09 | 75888593.66 |
February | 0.177039E+09 | 62659275.77 | 0.114380E+09 | 0.372409E+09 | 58018386.55 |
March | 0.219832E+09 | 86910756.02 | 0.132921E+09 | 0.472952E+09 | 51867156.97 |
April | 0.213387E+09 | 81563796.51 | 0.131823E+09 | 0.459947E+09 | 31049948.70 |
May | 0.187840E+09 | 55636303.28 | 0.132204E+09 | 0.417100E+09 | 33092117.06 |
June | 0.196892E+09 | 67800815.94 | 0.129091E+09 | 0.432165E+09 | 34045521.95 |
July | 0.173640E+09 | 40989388.99 | 0.132650E+09 | 0.360038E+09 | 50414793.34 |
August | 0.188883E+09 | 56004744.74 | 0.132879E+09 | 0.387544E+09 | 44805103.97 |
September | 0.170883E+09 | 47283009.57 | 0.123600E+09 | 0.358831E+09 | 43111957.63 |
October | 0.165993E+09 | 42769475.92 | 0.123223E+09 | 0.333717E+09 | 52528766.18 |
November | 0.156430E+09 | 42507184.71 | 0.113923E+09 | 0.317417E+09 | 57157883.05 |
December | 0.165752E+09 | 54281676.98 | 0.111470E+09 | 0.338230E+09 | 81091776.81 |
Annual Sum or Average | 0.219549E+10 | 0.701591E+09 | 0.149390E+10 | 0.461653E+10 | 0.613072E+09 |
Minimum of Months | 0.156430E+09 | 40989388.99 | 0.111470E+09 | 0.317417E+09 | 31049948.70 |
Maximum of Months | 0.219832E+09 | 86910756.02 | 0.132921E+09 | 0.472952E+09 | 81091776.81 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53281111.81 | 0.00 | 53281111.81 | 0.110516E+09 | 44098742.69 |
February | 51336067.83 | 0.00 | 51336067.83 | 0.112769E+09 | 33776816.85 |
March | 58379204.54 | 10308.65 | 58368895.89 | 0.136447E+09 | 29983022.45 |
April | 62225058.72 | 1172709.11 | 61052349.61 | 0.147764E+09 | 17923131.32 |
May | 81611932.80 | 8906887.59 | 72705045.22 | 0.197823E+09 | 19325036.31 |
June | 95905148.72 | 19152819.85 | 76752328.88 | 0.230269E+09 | 20033403.63 |
July | 85192697.07 | 8671532.12 | 76521164.96 | 0.185502E+09 | 29070868.10 |
August | 70908743.61 | 3483024.27 | 67425719.34 | 0.155000E+09 | 26170081.73 |
September | 58083863.24 | 80134.49 | 58003728.75 | 0.128475E+09 | 25244952.50 |
October | 57731326.90 | 0.00 | 57731326.90 | 0.118480E+09 | 30672333.33 |
November | 52864403.48 | 0.00 | 52864403.48 | 0.108966E+09 | 33273692.89 |
December | 51761861.07 | 0.00 | 51761861.07 | 0.106517E+09 | 47113802.29 |
Annual Sum or Average | 0.779281E+09 | 41477416.06 | 0.737804E+09 | 0.173853E+10 | 0.356686E+09 |
Minimum of Months | 51336067.83 | 0.00 | 51336067.83 | 0.106517E+09 | 17923131.32 |
Maximum of Months | 95905148.72 | 19152819.85 | 76752328.88 | 0.230269E+09 | 47113802.29 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53279468.87 | 0.00 | 53279468.87 | 0.110514E+09 | 44097987.10 |
February | 51334543.10 | 0.00 | 51334543.10 | 0.112766E+09 | 33775966.02 |
March | 58377579.46 | 10308.16 | 58367271.30 | 0.136444E+09 | 29982195.79 |
April | 62223232.22 | 1172654.14 | 61050578.08 | 0.147761E+09 | 17922477.29 |
May | 81609064.33 | 8906470.11 | 72702594.22 | 0.197817E+09 | 19324519.06 |
June | 95901649.86 | 19151922.13 | 76749727.73 | 0.230262E+09 | 20032941.85 |
July | 85189583.27 | 8671125.67 | 76518457.60 | 0.185496E+09 | 29070314.87 |
August | 70906380.81 | 3482861.02 | 67423519.80 | 0.154995E+09 | 26169522.30 |
September | 58082004.07 | 80130.73 | 58001873.33 | 0.128472E+09 | 25244459.32 |
October | 57729442.97 | 0.00 | 57729442.97 | 0.118477E+09 | 30671846.33 |
November | 52862687.63 | 0.00 | 52862687.63 | 0.108963E+09 | 33273098.27 |
December | 51760231.57 | 0.00 | 51760231.57 | 0.106515E+09 | 47113072.49 |
Annual Sum or Average | 0.779256E+09 | 41475471.96 | 0.737780E+09 | 0.173848E+10 | 0.356678E+09 |
Minimum of Months | 51334543.10 | 0.00 | 51334543.10 | 0.106515E+09 | 17922477.29 |
Maximum of Months | 95901649.86 | 19151922.13 | 76749727.73 | 0.230262E+09 | 47113072.49 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120004E+09 | 57652055.58 | 62352137.05 | 0.213680E+09 | 46854769.25 |
February | 0.124996E+09 | 65022840.16 | 59972940.90 | 0.225665E+09 | 42818165.44 |
March | 0.161003E+09 | 94762243.87 | 66240296.71 | 0.292434E+09 | 39386027.99 |
April | 0.157431E+09 | 88466047.56 | 68964491.52 | 0.287798E+09 | 27846255.94 |
May | 0.136085E+09 | 59407739.89 | 76677047.89 | 0.252428E+09 | 25281431.55 |
June | 0.142443E+09 | 70753638.87 | 71689748.60 | 0.263274E+09 | 23944329.27 |
July | 0.123709E+09 | 41223006.98 | 82486238.54 | 0.224701E+09 | 31376137.82 |
August | 0.136730E+09 | 58951344.09 | 77778987.35 | 0.240431E+09 | 30241501.83 |
September | 0.122310E+09 | 47761381.67 | 74548732.73 | 0.222651E+09 | 28292325.69 |
October | 0.115484E+09 | 41163003.39 | 74320942.08 | 0.202266E+09 | 31914557.84 |
November | 0.106344E+09 | 40281825.28 | 66062534.08 | 0.189067E+09 | 36755194.87 |
December | 0.111150E+09 | 50015701.74 | 61134418.65 | 0.197597E+09 | 48548443.60 |
Annual Sum or Average | 0.155769E+10 | 0.715461E+09 | 0.842229E+09 | 0.281199E+10 | 0.413259E+09 |
Minimum of Months | 0.106344E+09 | 40281825.28 | 59972940.90 | 0.189067E+09 | 23944329.27 |
Maximum of Months | 0.161003E+09 | 94762243.87 | 82486238.54 | 0.292434E+09 | 48548443.60 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_6
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120004E+09 | 57652055.58 | 62352137.05 | 0.213680E+09 | 46854769.25 |
February | 0.124996E+09 | 65022840.16 | 59972940.90 | 0.225665E+09 | 42818165.44 |
March | 0.161003E+09 | 94762243.87 | 66240296.71 | 0.292434E+09 | 39386027.99 |
April | 0.157431E+09 | 88466047.56 | 68964491.52 | 0.287798E+09 | 27846255.94 |
May | 0.136085E+09 | 59407739.89 | 76677047.89 | 0.252428E+09 | 25281431.55 |
June | 0.142443E+09 | 70753638.87 | 71689748.60 | 0.263274E+09 | 23944329.27 |
July | 0.123709E+09 | 41223006.98 | 82486238.54 | 0.224701E+09 | 31376137.82 |
August | 0.136730E+09 | 58951344.09 | 77778987.35 | 0.240431E+09 | 30241501.83 |
September | 0.122310E+09 | 47761381.67 | 74548732.73 | 0.222651E+09 | 28292325.69 |
October | 0.115484E+09 | 41163003.39 | 74320942.08 | 0.202266E+09 | 31914557.84 |
November | 0.106344E+09 | 40281825.28 | 66062534.08 | 0.189067E+09 | 36755194.87 |
December | 0.111150E+09 | 50015701.74 | 61134418.65 | 0.197597E+09 | 48548443.60 |
Annual Sum or Average | 0.155769E+10 | 0.715461E+09 | 0.842229E+09 | 0.281199E+10 | 0.413259E+09 |
Minimum of Months | 0.106344E+09 | 40281825.28 | 59972940.90 | 0.189067E+09 | 23944329.27 |
Maximum of Months | 0.161003E+09 | 94762243.87 | 82486238.54 | 0.292434E+09 | 48548443.60 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_7
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120004E+09 | 57652055.58 | 62352137.05 | 0.213680E+09 | 46854769.25 |
February | 0.124996E+09 | 65022840.16 | 59972940.90 | 0.225665E+09 | 42818165.44 |
March | 0.161003E+09 | 94762243.87 | 66240296.71 | 0.292434E+09 | 39386027.99 |
April | 0.157431E+09 | 88466047.56 | 68964491.52 | 0.287798E+09 | 27846255.94 |
May | 0.136085E+09 | 59407739.89 | 76677047.89 | 0.252428E+09 | 25281431.55 |
June | 0.142443E+09 | 70753638.87 | 71689748.60 | 0.263274E+09 | 23944329.27 |
July | 0.123709E+09 | 41223006.98 | 82486238.54 | 0.224701E+09 | 31376137.82 |
August | 0.136730E+09 | 58951344.09 | 77778987.35 | 0.240431E+09 | 30241501.83 |
September | 0.122310E+09 | 47761381.67 | 74548732.73 | 0.222651E+09 | 28292325.69 |
October | 0.115484E+09 | 41163003.39 | 74320942.08 | 0.202266E+09 | 31914557.84 |
November | 0.106344E+09 | 40281825.28 | 66062534.08 | 0.189067E+09 | 36755194.87 |
December | 0.111150E+09 | 50015701.74 | 61134418.65 | 0.197597E+09 | 48548443.60 |
Annual Sum or Average | 0.155769E+10 | 0.715461E+09 | 0.842229E+09 | 0.281199E+10 | 0.413259E+09 |
Minimum of Months | 0.106344E+09 | 40281825.28 | 59972940.90 | 0.189067E+09 | 23944329.27 |
Maximum of Months | 0.161003E+09 | 94762243.87 | 82486238.54 | 0.292434E+09 | 48548443.60 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_8
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120004E+09 | 57652055.58 | 62352137.05 | 0.213680E+09 | 46854769.25 |
February | 0.124996E+09 | 65022840.16 | 59972940.90 | 0.225665E+09 | 42818165.44 |
March | 0.161003E+09 | 94762243.87 | 66240296.71 | 0.292434E+09 | 39386027.99 |
April | 0.157431E+09 | 88466047.56 | 68964491.52 | 0.287798E+09 | 27846255.94 |
May | 0.136085E+09 | 59407739.89 | 76677047.89 | 0.252428E+09 | 25281431.55 |
June | 0.142443E+09 | 70753638.87 | 71689748.60 | 0.263274E+09 | 23944329.27 |
July | 0.123709E+09 | 41223006.98 | 82486238.54 | 0.224701E+09 | 31376137.82 |
August | 0.136730E+09 | 58951344.09 | 77778987.35 | 0.240431E+09 | 30241501.83 |
September | 0.122310E+09 | 47761381.67 | 74548732.73 | 0.222651E+09 | 28292325.69 |
October | 0.115484E+09 | 41163003.39 | 74320942.08 | 0.202266E+09 | 31914557.84 |
November | 0.106344E+09 | 40281825.28 | 66062534.08 | 0.189067E+09 | 36755194.87 |
December | 0.111150E+09 | 50015701.74 | 61134418.65 | 0.197597E+09 | 48548443.60 |
Annual Sum or Average | 0.155769E+10 | 0.715461E+09 | 0.842229E+09 | 0.281199E+10 | 0.413259E+09 |
Minimum of Months | 0.106344E+09 | 40281825.28 | 59972940.90 | 0.189067E+09 | 23944329.27 |
Maximum of Months | 0.161003E+09 | 94762243.87 | 82486238.54 | 0.292434E+09 | 48548443.60 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_9
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120004E+09 | 57652055.58 | 62352137.05 | 0.213680E+09 | 46854769.25 |
February | 0.124996E+09 | 65022840.16 | 59972940.90 | 0.225665E+09 | 42818165.44 |
March | 0.161003E+09 | 94762243.87 | 66240296.71 | 0.292434E+09 | 39386027.99 |
April | 0.157431E+09 | 88466047.56 | 68964491.52 | 0.287798E+09 | 27846255.94 |
May | 0.136085E+09 | 59407739.89 | 76677047.89 | 0.252428E+09 | 25281431.55 |
June | 0.142443E+09 | 70753638.87 | 71689748.60 | 0.263274E+09 | 23944329.27 |
July | 0.123709E+09 | 41223006.98 | 82486238.54 | 0.224701E+09 | 31376137.82 |
August | 0.136730E+09 | 58951344.09 | 77778987.35 | 0.240431E+09 | 30241501.83 |
September | 0.122310E+09 | 47761381.67 | 74548732.73 | 0.222651E+09 | 28292325.69 |
October | 0.115484E+09 | 41163003.39 | 74320942.08 | 0.202266E+09 | 31914557.84 |
November | 0.106344E+09 | 40281825.28 | 66062534.08 | 0.189067E+09 | 36755194.87 |
December | 0.111150E+09 | 50015701.74 | 61134418.65 | 0.197597E+09 | 48548443.60 |
Annual Sum or Average | 0.155769E+10 | 0.715461E+09 | 0.842229E+09 | 0.281199E+10 | 0.413259E+09 |
Minimum of Months | 0.106344E+09 | 40281825.28 | 59972940.90 | 0.189067E+09 | 23944329.27 |
Maximum of Months | 0.161003E+09 | 94762243.87 | 82486238.54 | 0.292434E+09 | 48548443.60 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_10
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120004E+09 | 57652055.58 | 62352137.05 | 0.213680E+09 | 46854769.25 |
February | 0.124996E+09 | 65022840.16 | 59972940.90 | 0.225665E+09 | 42818165.44 |
March | 0.161003E+09 | 94762243.87 | 66240296.71 | 0.292434E+09 | 39386027.99 |
April | 0.157431E+09 | 88466047.56 | 68964491.52 | 0.287798E+09 | 27846255.94 |
May | 0.136085E+09 | 59407739.89 | 76677047.89 | 0.252428E+09 | 25281431.55 |
June | 0.142443E+09 | 70753638.87 | 71689748.60 | 0.263274E+09 | 23944329.27 |
July | 0.123709E+09 | 41223006.98 | 82486238.54 | 0.224701E+09 | 31376137.82 |
August | 0.136730E+09 | 58951344.09 | 77778987.35 | 0.240431E+09 | 30241501.83 |
September | 0.122310E+09 | 47761381.67 | 74548732.73 | 0.222651E+09 | 28292325.69 |
October | 0.115484E+09 | 41163003.39 | 74320942.08 | 0.202266E+09 | 31914557.84 |
November | 0.106344E+09 | 40281825.28 | 66062534.08 | 0.189067E+09 | 36755194.87 |
December | 0.111150E+09 | 50015701.74 | 61134418.65 | 0.197597E+09 | 48548443.60 |
Annual Sum or Average | 0.155769E+10 | 0.715461E+09 | 0.842229E+09 | 0.281199E+10 | 0.413259E+09 |
Minimum of Months | 0.106344E+09 | 40281825.28 | 59972940.90 | 0.189067E+09 | 23944329.27 |
Maximum of Months | 0.161003E+09 | 94762243.87 | 82486238.54 | 0.292434E+09 | 48548443.60 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_5
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120004E+09 | 57652055.58 | 62352137.05 | 0.213680E+09 | 46854769.25 |
February | 0.124996E+09 | 65022840.16 | 59972940.90 | 0.225665E+09 | 42818165.44 |
March | 0.161003E+09 | 94762243.87 | 66240296.71 | 0.292434E+09 | 39386027.99 |
April | 0.157431E+09 | 88466047.56 | 68964491.52 | 0.287798E+09 | 27846255.94 |
May | 0.136085E+09 | 59407739.89 | 76677047.89 | 0.252428E+09 | 25281431.55 |
June | 0.142443E+09 | 70753638.87 | 71689748.60 | 0.263274E+09 | 23944329.27 |
July | 0.123709E+09 | 41223006.98 | 82486238.54 | 0.224701E+09 | 31376137.82 |
August | 0.136730E+09 | 58951344.09 | 77778987.35 | 0.240431E+09 | 30241501.83 |
September | 0.122310E+09 | 47761381.67 | 74548732.73 | 0.222651E+09 | 28292325.69 |
October | 0.115484E+09 | 41163003.39 | 74320942.08 | 0.202266E+09 | 31914557.84 |
November | 0.106344E+09 | 40281825.28 | 66062534.08 | 0.189067E+09 | 36755194.87 |
December | 0.111150E+09 | 50015701.74 | 61134418.65 | 0.197597E+09 | 48548443.60 |
Annual Sum or Average | 0.155769E+10 | 0.715461E+09 | 0.842229E+09 | 0.281199E+10 | 0.413259E+09 |
Minimum of Months | 0.106344E+09 | 40281825.28 | 59972940.90 | 0.189067E+09 | 23944329.27 |
Maximum of Months | 0.161003E+09 | 94762243.87 | 82486238.54 | 0.292434E+09 | 48548443.60 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120004E+09 | 57652055.58 | 62352137.05 | 0.213680E+09 | 46854769.25 |
February | 0.124996E+09 | 65022840.16 | 59972940.90 | 0.225665E+09 | 42818165.44 |
March | 0.161003E+09 | 94762243.87 | 66240296.71 | 0.292434E+09 | 39386027.99 |
April | 0.157431E+09 | 88466047.56 | 68964491.52 | 0.287798E+09 | 27846255.94 |
May | 0.136085E+09 | 59407739.89 | 76677047.89 | 0.252428E+09 | 25281431.55 |
June | 0.142443E+09 | 70753638.87 | 71689748.60 | 0.263274E+09 | 23944329.27 |
July | 0.123709E+09 | 41223006.98 | 82486238.54 | 0.224701E+09 | 31376137.82 |
August | 0.136730E+09 | 58951344.09 | 77778987.35 | 0.240431E+09 | 30241501.83 |
September | 0.122310E+09 | 47761381.67 | 74548732.73 | 0.222651E+09 | 28292325.69 |
October | 0.115484E+09 | 41163003.39 | 74320942.08 | 0.202266E+09 | 31914557.84 |
November | 0.106344E+09 | 40281825.28 | 66062534.08 | 0.189067E+09 | 36755194.87 |
December | 0.111150E+09 | 50015701.74 | 61134418.65 | 0.197597E+09 | 48548443.60 |
Annual Sum or Average | 0.155769E+10 | 0.715461E+09 | 0.842229E+09 | 0.281199E+10 | 0.413259E+09 |
Minimum of Months | 0.106344E+09 | 40281825.28 | 59972940.90 | 0.189067E+09 | 23944329.27 |
Maximum of Months | 0.161003E+09 | 94762243.87 | 82486238.54 | 0.292434E+09 | 48548443.60 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120004E+09 | 57652055.58 | 62352137.05 | 0.213680E+09 | 46854769.25 |
February | 0.124996E+09 | 65022840.16 | 59972940.90 | 0.225665E+09 | 42818165.44 |
March | 0.161003E+09 | 94762243.87 | 66240296.71 | 0.292434E+09 | 39386027.99 |
April | 0.157431E+09 | 88466047.56 | 68964491.52 | 0.287798E+09 | 27846255.94 |
May | 0.136085E+09 | 59407739.89 | 76677047.89 | 0.252428E+09 | 25281431.55 |
June | 0.142443E+09 | 70753638.87 | 71689748.60 | 0.263274E+09 | 23944329.27 |
July | 0.123709E+09 | 41223006.98 | 82486238.54 | 0.224701E+09 | 31376137.82 |
August | 0.136730E+09 | 58951344.09 | 77778987.35 | 0.240431E+09 | 30241501.83 |
September | 0.122310E+09 | 47761381.67 | 74548732.73 | 0.222651E+09 | 28292325.69 |
October | 0.115484E+09 | 41163003.39 | 74320942.08 | 0.202266E+09 | 31914557.84 |
November | 0.106344E+09 | 40281825.28 | 66062534.08 | 0.189067E+09 | 36755194.87 |
December | 0.111150E+09 | 50015701.74 | 61134418.65 | 0.197597E+09 | 48548443.60 |
Annual Sum or Average | 0.155769E+10 | 0.715461E+09 | 0.842229E+09 | 0.281199E+10 | 0.413259E+09 |
Minimum of Months | 0.106344E+09 | 40281825.28 | 59972940.90 | 0.189067E+09 | 23944329.27 |
Maximum of Months | 0.161003E+09 | 94762243.87 | 82486238.54 | 0.292434E+09 | 48548443.60 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120004E+09 | 57652055.58 | 62352137.05 | 0.213680E+09 | 46854769.25 |
February | 0.124996E+09 | 65022840.16 | 59972940.90 | 0.225665E+09 | 42818165.44 |
March | 0.161003E+09 | 94762243.87 | 66240296.71 | 0.292434E+09 | 39386027.99 |
April | 0.157431E+09 | 88466047.56 | 68964491.52 | 0.287798E+09 | 27846255.94 |
May | 0.136085E+09 | 59407739.89 | 76677047.89 | 0.252428E+09 | 25281431.55 |
June | 0.142443E+09 | 70753638.87 | 71689748.60 | 0.263274E+09 | 23944329.27 |
July | 0.123709E+09 | 41223006.98 | 82486238.54 | 0.224701E+09 | 31376137.82 |
August | 0.136730E+09 | 58951344.09 | 77778987.35 | 0.240431E+09 | 30241501.83 |
September | 0.122310E+09 | 47761381.67 | 74548732.73 | 0.222651E+09 | 28292325.69 |
October | 0.115484E+09 | 41163003.39 | 74320942.08 | 0.202266E+09 | 31914557.84 |
November | 0.106344E+09 | 40281825.28 | 66062534.08 | 0.189067E+09 | 36755194.87 |
December | 0.111150E+09 | 50015701.74 | 61134418.65 | 0.197597E+09 | 48548443.60 |
Annual Sum or Average | 0.155769E+10 | 0.715461E+09 | 0.842229E+09 | 0.281199E+10 | 0.413259E+09 |
Minimum of Months | 0.106344E+09 | 40281825.28 | 59972940.90 | 0.189067E+09 | 23944329.27 |
Maximum of Months | 0.161003E+09 | 94762243.87 | 82486238.54 | 0.292434E+09 | 48548443.60 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_14
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120004E+09 | 57652055.58 | 62352137.05 | 0.213680E+09 | 46854769.25 |
February | 0.124996E+09 | 65022840.16 | 59972940.90 | 0.225665E+09 | 42818165.44 |
March | 0.161003E+09 | 94762243.87 | 66240296.71 | 0.292434E+09 | 39386027.99 |
April | 0.157431E+09 | 88466047.56 | 68964491.52 | 0.287798E+09 | 27846255.94 |
May | 0.136085E+09 | 59407739.89 | 76677047.89 | 0.252428E+09 | 25281431.55 |
June | 0.142443E+09 | 70753638.87 | 71689748.60 | 0.263274E+09 | 23944329.27 |
July | 0.123709E+09 | 41223006.98 | 82486238.54 | 0.224701E+09 | 31376137.82 |
August | 0.136730E+09 | 58951344.09 | 77778987.35 | 0.240431E+09 | 30241501.83 |
September | 0.122310E+09 | 47761381.67 | 74548732.73 | 0.222651E+09 | 28292325.69 |
October | 0.115484E+09 | 41163003.39 | 74320942.08 | 0.202266E+09 | 31914557.84 |
November | 0.106344E+09 | 40281825.28 | 66062534.08 | 0.189067E+09 | 36755194.87 |
December | 0.111150E+09 | 50015701.74 | 61134418.65 | 0.197597E+09 | 48548443.60 |
Annual Sum or Average | 0.155769E+10 | 0.715461E+09 | 0.842229E+09 | 0.281199E+10 | 0.413259E+09 |
Minimum of Months | 0.106344E+09 | 40281825.28 | 59972940.90 | 0.189067E+09 | 23944329.27 |
Maximum of Months | 0.161003E+09 | 94762243.87 | 82486238.54 | 0.292434E+09 | 48548443.60 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_13
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120004E+09 | 57652055.58 | 62352137.05 | 0.213680E+09 | 46854769.25 |
February | 0.124996E+09 | 65022840.16 | 59972940.90 | 0.225665E+09 | 42818165.44 |
March | 0.161003E+09 | 94762243.87 | 66240296.71 | 0.292434E+09 | 39386027.99 |
April | 0.157431E+09 | 88466047.56 | 68964491.52 | 0.287798E+09 | 27846255.94 |
May | 0.136085E+09 | 59407739.89 | 76677047.89 | 0.252428E+09 | 25281431.55 |
June | 0.142443E+09 | 70753638.87 | 71689748.60 | 0.263274E+09 | 23944329.27 |
July | 0.123709E+09 | 41223006.98 | 82486238.54 | 0.224701E+09 | 31376137.82 |
August | 0.136730E+09 | 58951344.09 | 77778987.35 | 0.240431E+09 | 30241501.83 |
September | 0.122310E+09 | 47761381.67 | 74548732.73 | 0.222651E+09 | 28292325.69 |
October | 0.115484E+09 | 41163003.39 | 74320942.08 | 0.202266E+09 | 31914557.84 |
November | 0.106344E+09 | 40281825.28 | 66062534.08 | 0.189067E+09 | 36755194.87 |
December | 0.111150E+09 | 50015701.74 | 61134418.65 | 0.197597E+09 | 48548443.60 |
Annual Sum or Average | 0.155769E+10 | 0.715461E+09 | 0.842229E+09 | 0.281199E+10 | 0.413259E+09 |
Minimum of Months | 0.106344E+09 | 40281825.28 | 59972940.90 | 0.189067E+09 | 23944329.27 |
Maximum of Months | 0.161003E+09 | 94762243.87 | 82486238.54 | 0.292434E+09 | 48548443.60 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_12
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120004E+09 | 57652055.58 | 62352137.05 | 0.213680E+09 | 46854769.25 |
February | 0.124996E+09 | 65022840.16 | 59972940.90 | 0.225665E+09 | 42818165.44 |
March | 0.161003E+09 | 94762243.87 | 66240296.71 | 0.292434E+09 | 39386027.99 |
April | 0.157431E+09 | 88466047.56 | 68964491.52 | 0.287798E+09 | 27846255.94 |
May | 0.136085E+09 | 59407739.89 | 76677047.89 | 0.252428E+09 | 25281431.55 |
June | 0.142443E+09 | 70753638.87 | 71689748.60 | 0.263274E+09 | 23944329.27 |
July | 0.123709E+09 | 41223006.98 | 82486238.54 | 0.224701E+09 | 31376137.82 |
August | 0.136730E+09 | 58951344.09 | 77778987.35 | 0.240431E+09 | 30241501.83 |
September | 0.122310E+09 | 47761381.67 | 74548732.73 | 0.222651E+09 | 28292325.69 |
October | 0.115484E+09 | 41163003.39 | 74320942.08 | 0.202266E+09 | 31914557.84 |
November | 0.106344E+09 | 40281825.28 | 66062534.08 | 0.189067E+09 | 36755194.87 |
December | 0.111150E+09 | 50015701.74 | 61134418.65 | 0.197597E+09 | 48548443.60 |
Annual Sum or Average | 0.155769E+10 | 0.715461E+09 | 0.842229E+09 | 0.281199E+10 | 0.413259E+09 |
Minimum of Months | 0.106344E+09 | 40281825.28 | 59972940.90 | 0.189067E+09 | 23944329.27 |
Maximum of Months | 0.161003E+09 | 94762243.87 | 82486238.54 | 0.292434E+09 | 48548443.60 |
Report: WindowEnergyReportMonthly
For: FINESTORAGE_SKYLIGHT_11
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120004E+09 | 57652055.58 | 62352137.05 | 0.213680E+09 | 46854769.25 |
February | 0.124996E+09 | 65022840.16 | 59972940.90 | 0.225665E+09 | 42818165.44 |
March | 0.161003E+09 | 94762243.87 | 66240296.71 | 0.292434E+09 | 39386027.99 |
April | 0.157431E+09 | 88466047.56 | 68964491.52 | 0.287798E+09 | 27846255.94 |
May | 0.136085E+09 | 59407739.89 | 76677047.89 | 0.252428E+09 | 25281431.55 |
June | 0.142443E+09 | 70753638.87 | 71689748.60 | 0.263274E+09 | 23944329.27 |
July | 0.123709E+09 | 41223006.98 | 82486238.54 | 0.224701E+09 | 31376137.82 |
August | 0.136730E+09 | 58951344.09 | 77778987.35 | 0.240431E+09 | 30241501.83 |
September | 0.122310E+09 | 47761381.67 | 74548732.73 | 0.222651E+09 | 28292325.69 |
October | 0.115484E+09 | 41163003.39 | 74320942.08 | 0.202266E+09 | 31914557.84 |
November | 0.106344E+09 | 40281825.28 | 66062534.08 | 0.189067E+09 | 36755194.87 |
December | 0.111150E+09 | 50015701.74 | 61134418.65 | 0.197597E+09 | 48548443.60 |
Annual Sum or Average | 0.155769E+10 | 0.715461E+09 | 0.842229E+09 | 0.281199E+10 | 0.413259E+09 |
Minimum of Months | 0.106344E+09 | 40281825.28 | 59972940.90 | 0.189067E+09 | 23944329.27 |
Maximum of Months | 0.161003E+09 | 94762243.87 | 82486238.54 | 0.292434E+09 | 48548443.60 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R3C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R4C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R5C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R8C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C1
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C2
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C4
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R6C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R7C3
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272598E+09 | 0.130392E+09 | 0.142207E+09 | 0.378594E+09 | 0.104377E+09 |
February | 0.283338E+09 | 0.146558E+09 | 0.136780E+09 | 0.396561E+09 | 98056215.05 |
March | 0.364068E+09 | 0.212994E+09 | 0.151074E+09 | 0.509424E+09 | 93791170.80 |
April | 0.356093E+09 | 0.198806E+09 | 0.157287E+09 | 0.497739E+09 | 72570855.51 |
May | 0.308496E+09 | 0.133619E+09 | 0.174877E+09 | 0.428283E+09 | 70395031.22 |
June | 0.322674E+09 | 0.159172E+09 | 0.163503E+09 | 0.450442E+09 | 65524907.57 |
July | 0.280878E+09 | 92751447.63 | 0.188126E+09 | 0.394044E+09 | 76696504.41 |
August | 0.309932E+09 | 0.132542E+09 | 0.177391E+09 | 0.415085E+09 | 73661634.13 |
September | 0.277428E+09 | 0.107405E+09 | 0.170023E+09 | 0.387743E+09 | 71389117.39 |
October | 0.262236E+09 | 92731839.15 | 0.169504E+09 | 0.351170E+09 | 79631204.41 |
November | 0.241714E+09 | 91044922.54 | 0.150669E+09 | 0.332568E+09 | 84906798.09 |
December | 0.252740E+09 | 0.113310E+09 | 0.139429E+09 | 0.350515E+09 | 0.105336E+09 |
Annual Sum or Average | 0.353220E+10 | 0.161132E+10 | 0.192087E+10 | 0.489217E+10 | 0.996336E+09 |
Minimum of Months | 0.241714E+09 | 91044922.54 | 0.136780E+09 | 0.332568E+09 | 65524907.57 |
Maximum of Months | 0.364068E+09 | 0.212994E+09 | 0.188126E+09 | 0.509424E+09 | 0.105336E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 355.91 | 89.55 | 173.39 | 47.18 | 126.21 | 0.00 | 0.00 |
February | 401.10 | 75.89 | 188.80 | 51.80 | 137.00 | 0.00 | 0.00 |
March | 455.01 | 61.08 | 207.74 | 64.91 | 142.84 | 0.00 | 0.00 |
April | 468.81 | 37.69 | 212.66 | 63.84 | 148.82 | 0.00 | 0.00 |
May | 459.01 | 38.98 | 201.20 | 48.20 | 153.01 | 0.00 | 0.00 |
June | 510.87 | 41.47 | 225.92 | 67.09 | 158.83 | 0.00 | 0.00 |
July | 406.99 | 58.98 | 193.27 | 37.08 | 156.19 | 0.00 | 0.00 |
August | 404.92 | 52.80 | 193.99 | 44.42 | 149.57 | 0.00 | 0.00 |
September | 375.89 | 52.63 | 176.67 | 36.55 | 140.13 | 0.00 | 0.00 |
October | 337.54 | 62.01 | 167.06 | 31.94 | 135.12 | 0.00 | 0.00 |
November | 328.86 | 69.64 | 161.49 | 32.80 | 128.69 | 0.00 | 0.00 |
December | 332.06 | 95.70 | 162.42 | 40.53 | 121.89 | 0.00 | 0.00 |
Annual Sum or Average | 402.90 | 61.37 | 188.66 | 47.13 | 141.53 | 0.00 | 0.00 |
Minimum of Months | 328.86 | 37.69 | 161.49 | 31.94 | 121.89 | 0.00 | 0.00 |
Maximum of Months | 510.87 | 95.70 | 225.92 | 67.09 | 158.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1116.91 | 244.91 | 627.26 | 301.35 | 325.91 | 0.00 | 0.00 |
February | 1305.93 | 247.79 | 723.36 | 376.29 | 347.07 | 0.00 | 0.00 |
March | 1528.55 | 205.87 | 841.56 | 495.32 | 346.24 | 0.00 | 0.00 |
April | 1554.47 | 150.40 | 850.32 | 477.83 | 372.49 | 0.00 | 0.00 |
May | 1319.44 | 132.15 | 711.32 | 310.52 | 400.79 | 0.00 | 0.00 |
June | 1422.01 | 129.33 | 769.37 | 382.16 | 387.21 | 0.00 | 0.00 |
July | 1174.51 | 164.00 | 646.63 | 215.47 | 431.16 | 0.00 | 0.00 |
August | 1256.73 | 158.07 | 714.69 | 308.14 | 406.55 | 0.00 | 0.00 |
September | 1202.59 | 152.81 | 660.63 | 257.97 | 402.66 | 0.00 | 0.00 |
October | 1057.24 | 166.82 | 603.63 | 215.16 | 388.48 | 0.00 | 0.00 |
November | 1021.20 | 198.52 | 574.39 | 217.57 | 356.82 | 0.00 | 0.00 |
December | 1032.84 | 253.76 | 580.98 | 261.43 | 319.55 | 0.00 | 0.00 |
Annual Sum or Average | 1248.35 | 183.46 | 691.52 | 317.62 | 373.90 | 0.00 | 0.00 |
Minimum of Months | 1021.20 | 129.33 | 574.39 | 215.16 | 319.55 | 0.00 | 0.00 |
Maximum of Months | 1554.47 | 253.76 | 850.32 | 495.32 | 431.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 24479.80 | 5587.88 | 3256.85 | 1557.85 | 1699.00 | 0.00 | 0.00 |
February | 31167.98 | 6725.83 | 3747.86 | 1938.60 | 1809.26 | 0.00 | 0.00 |
March | 34843.28 | 6406.30 | 4349.68 | 2544.73 | 1804.95 | 0.00 | 0.00 |
April | 36529.53 | 5562.71 | 4396.21 | 2454.40 | 1941.82 | 0.00 | 0.00 |
May | 34995.85 | 5070.02 | 3685.73 | 1596.40 | 2089.33 | 0.00 | 0.00 |
June | 36960.91 | 5184.88 | 3983.63 | 1965.08 | 2018.55 | 0.00 | 0.00 |
July | 27805.53 | 5076.41 | 3355.77 | 1108.14 | 2247.63 | 0.00 | 0.00 |
August | 31745.74 | 4673.64 | 3702.89 | 1583.53 | 2119.36 | 0.00 | 0.00 |
September | 29300.62 | 4917.28 | 3425.04 | 1325.98 | 2099.05 | 0.00 | 0.00 |
October | 23191.25 | 4675.61 | 3133.04 | 1107.91 | 2025.13 | 0.00 | 0.00 |
November | 23927.54 | 4751.32 | 2984.12 | 1124.01 | 1860.11 | 0.00 | 0.00 |
December | 22377.90 | 5248.75 | 3019.59 | 1353.77 | 1665.82 | 0.00 | 0.00 |
Annual Sum or Average | 29744.88 | 5314.26 | 3584.17 | 1635.03 | 1949.13 | 0.00 | 0.00 |
Minimum of Months | 22377.90 | 4673.64 | 2984.12 | 1107.91 | 1665.82 | 0.00 | 0.00 |
Maximum of Months | 36960.91 | 6725.83 | 4396.21 | 2544.73 | 2247.63 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.953278E+09 | 0.239863E+09 | 0.464405E+09 | 0.126370E+09 | 0.338035E+09 | 0.00 | 0.00 |
February | 0.970349E+09 | 0.183586E+09 | 0.456749E+09 | 0.125319E+09 | 0.331430E+09 | 0.00 | 0.00 |
March | 0.121870E+10 | 0.163608E+09 | 0.556421E+09 | 0.173842E+09 | 0.382579E+09 | 0.00 | 0.00 |
April | 0.121515E+10 | 97679685.78 | 0.551222E+09 | 0.165473E+09 | 0.385749E+09 | 0.00 | 0.00 |
May | 0.122940E+10 | 0.104398E+09 | 0.538902E+09 | 0.129086E+09 | 0.409816E+09 | 0.00 | 0.00 |
June | 0.132418E+10 | 0.107478E+09 | 0.585591E+09 | 0.173906E+09 | 0.411685E+09 | 0.00 | 0.00 |
July | 0.109009E+10 | 0.157983E+09 | 0.517662E+09 | 99321435.76 | 0.418340E+09 | 0.00 | 0.00 |
August | 0.108455E+10 | 0.141412E+09 | 0.519582E+09 | 0.118975E+09 | 0.400607E+09 | 0.00 | 0.00 |
September | 0.974315E+09 | 0.136419E+09 | 0.457933E+09 | 94726284.36 | 0.363207E+09 | 0.00 | 0.00 |
October | 0.904066E+09 | 0.166078E+09 | 0.447447E+09 | 85538951.85 | 0.361908E+09 | 0.00 | 0.00 |
November | 0.852412E+09 | 0.180512E+09 | 0.418587E+09 | 85014369.42 | 0.333573E+09 | 0.00 | 0.00 |
December | 0.889398E+09 | 0.256317E+09 | 0.435026E+09 | 0.108563E+09 | 0.326463E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127059E+11 | 0.193533E+10 | 0.594953E+10 | 0.148614E+10 | 0.446339E+10 | 0.00 | 0.00 |
Minimum of Months | 0.852412E+09 | 97679685.78 | 0.418587E+09 | 85014369.42 | 0.326463E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132418E+10 | 0.256317E+09 | 0.585591E+09 | 0.173906E+09 | 0.418340E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.299153E+10 | 0.655967E+09 | 0.168006E+10 | 0.807129E+09 | 0.872930E+09 | 0.00 | 0.00 |
February | 0.315931E+10 | 0.599454E+09 | 0.174994E+10 | 0.910320E+09 | 0.839621E+09 | 0.00 | 0.00 |
March | 0.409407E+10 | 0.551404E+09 | 0.225404E+10 | 0.132667E+10 | 0.927364E+09 | 0.00 | 0.00 |
April | 0.402918E+10 | 0.389848E+09 | 0.220403E+10 | 0.123852E+10 | 0.965503E+09 | 0.00 | 0.00 |
May | 0.353399E+10 | 0.353940E+09 | 0.190519E+10 | 0.831708E+09 | 0.107348E+10 | 0.00 | 0.00 |
June | 0.368584E+10 | 0.335221E+09 | 0.199421E+10 | 0.990551E+09 | 0.100366E+10 | 0.00 | 0.00 |
July | 0.314582E+10 | 0.439266E+09 | 0.173193E+10 | 0.577122E+09 | 0.115481E+10 | 0.00 | 0.00 |
August | 0.336604E+10 | 0.423381E+09 | 0.191422E+10 | 0.825319E+09 | 0.108891E+10 | 0.00 | 0.00 |
September | 0.311711E+10 | 0.396093E+09 | 0.171234E+10 | 0.668659E+09 | 0.104368E+10 | 0.00 | 0.00 |
October | 0.283172E+10 | 0.446804E+09 | 0.161678E+10 | 0.576282E+09 | 0.104049E+10 | 0.00 | 0.00 |
November | 0.264694E+10 | 0.514573E+09 | 0.148882E+10 | 0.563946E+09 | 0.924875E+09 | 0.00 | 0.00 |
December | 0.276636E+10 | 0.679678E+09 | 0.155610E+10 | 0.700220E+09 | 0.855882E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.393679E+11 | 0.578563E+10 | 0.218077E+11 | 0.100165E+11 | 0.117912E+11 | 0.00 | 0.00 |
Minimum of Months | 0.264694E+10 | 0.335221E+09 | 0.148882E+10 | 0.563946E+09 | 0.839621E+09 | 0.00 | 0.00 |
Maximum of Months | 0.409407E+10 | 0.679678E+09 | 0.225404E+10 | 0.132667E+10 | 0.115481E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.655667E+11 | 0.149666E+11 | 0.872315E+10 | 0.417254E+10 | 0.455061E+10 | 0.00 | 0.00 |
February | 0.754016E+11 | 0.162711E+11 | 0.906683E+10 | 0.468986E+10 | 0.437697E+10 | 0.00 | 0.00 |
March | 0.933242E+11 | 0.171586E+11 | 0.116502E+11 | 0.681580E+10 | 0.483438E+10 | 0.00 | 0.00 |
April | 0.946845E+11 | 0.144186E+11 | 0.113950E+11 | 0.636179E+10 | 0.503319E+10 | 0.00 | 0.00 |
May | 0.937329E+11 | 0.135795E+11 | 0.987187E+10 | 0.427579E+10 | 0.559607E+10 | 0.00 | 0.00 |
June | 0.958027E+11 | 0.134392E+11 | 0.103256E+11 | 0.509349E+10 | 0.523209E+10 | 0.00 | 0.00 |
July | 0.744743E+11 | 0.135967E+11 | 0.898809E+10 | 0.296805E+10 | 0.602004E+10 | 0.00 | 0.00 |
August | 0.850278E+11 | 0.125179E+11 | 0.991783E+10 | 0.424133E+10 | 0.567650E+10 | 0.00 | 0.00 |
September | 0.759472E+11 | 0.127456E+11 | 0.887769E+10 | 0.343695E+10 | 0.544074E+10 | 0.00 | 0.00 |
October | 0.621154E+11 | 0.125232E+11 | 0.839154E+10 | 0.296742E+10 | 0.542412E+10 | 0.00 | 0.00 |
November | 0.620202E+11 | 0.123154E+11 | 0.773484E+10 | 0.291344E+10 | 0.482140E+10 | 0.00 | 0.00 |
December | 0.599370E+11 | 0.140582E+11 | 0.808767E+10 | 0.362593E+10 | 0.446174E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.938035E+12 | 0.167591E+12 | 0.113030E+12 | 0.515624E+11 | 0.614679E+11 | 0.00 | 0.00 |
Minimum of Months | 0.599370E+11 | 0.123154E+11 | 0.773484E+10 | 0.291344E+10 | 0.437697E+10 | 0.00 | 0.00 |
Maximum of Months | 0.958027E+11 | 0.171586E+11 | 0.116502E+11 | 0.681580E+10 | 0.602004E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.593142E+09 | -522980035.7 | 0.00 | 0.00 | 744.00 | 0.00 | -70162409.7 | 58.98 | 0.00 | 0.00 |
February | 0.540668E+09 | -477414532.2 | 0.00 | 0.00 | 672.00 | 0.00 | -63253136.6 | 58.99 | 0.00 | 0.00 |
March | 0.619315E+09 | -549156189.4 | 0.00 | 0.00 | 744.00 | 0.00 | -70159288.9 | 58.99 | 0.00 | 0.00 |
April | 0.566520E+09 | -499168925.9 | 0.00 | 0.00 | 720.00 | 0.00 | -67351360.7 | 58.98 | 0.00 | 0.00 |
May | 0.577411E+09 | -507772268.3 | 0.00 | 0.00 | 744.00 | 0.00 | -69639142.3 | 58.99 | 0.00 | 0.00 |
June | 0.565755E+09 | -498277099.7 | 0.00 | 0.00 | 720.00 | 0.00 | -67478174.3 | 58.99 | 0.00 | 0.00 |
July | 0.548791E+09 | -479124360.6 | 0.00 | 0.00 | 744.00 | 0.00 | -69666752.0 | 58.99 | 0.00 | 0.00 |
August | 0.588496E+09 | -518268758.8 | 0.00 | 0.00 | 744.00 | 0.00 | -70227261.4 | 58.98 | 0.00 | 0.00 |
September | 0.557744E+09 | -490096324.5 | 0.00 | 0.00 | 720.00 | 0.00 | -67647527.5 | 58.99 | 0.00 | 0.00 |
October | 0.572248E+09 | -502254212.3 | 0.00 | 0.00 | 744.00 | 0.00 | -69993611.8 | 58.99 | 0.00 | 0.00 |
November | 0.560558E+09 | -492728544.1 | 0.00 | 0.00 | 720.00 | 0.00 | -67829220.4 | 58.99 | 0.00 | 0.00 |
December | 0.590908E+09 | -520534871.4 | 0.00 | 0.00 | 744.00 | 0.00 | -70372866.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.688156E+10 | -0.605778E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -823780751.8 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.540668E+09 | -549156189.4 | 0.00 | 0.00 | 672.00 | 0.00 | -70372866.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.619315E+09 | -477414532.2 | 0.00 | 0.00 | 744.00 | 0.00 | -63253136.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE2 FINE STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.66 | 0.50 | 01-JAN-10:30 | 277.44 | 0.00 | 0.00 | 154.17 | 226.13 | 0.00 | 0.00 | 110.33 |
February | 321.17 | 0.65 | 0.50 | 01-FEB-09:00 | 298.51 | 0.00 | 0.00 | 151.67 | 245.21 | 0.00 | 0.00 | 113.33 |
March | 361.17 | 0.64 | 0.50 | 01-MAR-09:30 | 766.85 | 0.00 | 0.00 | 182.50 | 1350.48 | 0.00 | 0.00 | 127.83 |
April | 358.33 | 0.65 | 0.50 | 01-APR-09:50 | 779.24 | 0.00 | 0.00 | 186.33 | 226.86 | 0.00 | 0.00 | 101.33 |
May | 376.33 | 0.66 | 0.50 | 01-MAY-10:20 | 343.12 | 0.00 | 0.00 | 199.00 | 195.35 | 0.00 | 0.00 | 56.67 |
June | 370.50 | 0.66 | 0.50 | 01-JUN-09:00 | 334.48 | 0.00 | 0.00 | 193.33 | 180.39 | 0.00 | 0.00 | 25.67 |
July | 383.17 | 0.66 | 0.50 | 01-JUL-10:09 | 345.88 | 0.00 | 0.00 | 200.00 | 191.31 | 0.00 | 0.00 | 63.83 |
August | 369.33 | 0.64 | 0.50 | 01-AUG-10:20 | 415.42 | 0.00 | 0.00 | 203.17 | 222.30 | 0.00 | 0.00 | 104.00 |
September | 357.83 | 0.65 | 0.50 | 01-SEP-09:09 | 842.62 | 0.00 | 0.00 | 189.67 | 625.02 | 0.00 | 0.00 | 141.17 |
October | 356.83 | 0.64 | 0.50 | 01-OCT-09:20 | 340.45 | 0.00 | 0.00 | 184.67 | 590.88 | 0.00 | 0.00 | 145.33 |
November | 337.67 | 0.65 | 0.50 | 01-NOV-09:09 | 304.88 | 0.00 | 0.00 | 163.00 | 244.61 | 0.00 | 0.00 | 121.83 |
December | 349.33 | 0.66 | 0.50 | 01-DEC-09:09 | 647.73 | 0.00 | 0.00 | 163.50 | 220.08 | 0.00 | 0.00 | 103.83 |
Annual Sum or Average | 4292.33 | 0.65 | 475.40 | 0.00 | 0.00 | 2171.00 | 376.68 | 0.00 | 0.00 | 1215.17 | ||
Minimum of Months | 321.17 | 0.64 | 0.50 | 277.44 | 0.00 | 0.00 | 151.67 | 180.39 | 0.00 | 0.00 | 25.67 | |
Maximum of Months | 383.17 | 0.66 | 0.50 | 842.62 | 0.00 | 0.00 | 203.17 | 1350.48 | 0.00 | 0.00 | 145.33 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.59 | 0.50 | 01-JAN-08:09 | 314.32 | 14.19 | 0.00 | 242.83 | 266.15 | 17.73 | 88.33 | 205.83 |
February | 321.17 | 0.58 | 0.50 | 01-FEB-07:00 | 340.85 | 14.34 | 0.00 | 231.17 | 290.82 | 17.98 | 90.67 | 198.00 |
March | 361.17 | 0.57 | 0.50 | 01-MAR-07:00 | 1165.77 | 14.49 | 0.00 | 269.33 | 1986.33 | 19.79 | 104.00 | 228.33 |
April | 358.33 | 0.57 | 0.50 | 01-APR-07:19 | 363.05 | 14.73 | 0.00 | 268.50 | 310.69 | 18.53 | 105.67 | 228.50 |
May | 376.33 | 0.57 | 0.50 | 01-MAY-07:10 | 370.46 | 14.56 | 0.00 | 277.17 | 322.64 | 18.02 | 93.00 | 243.67 |
June | 370.50 | 0.57 | 0.50 | 01-JUN-07:30 | 1512.88 | 15.80 | 36.67 | 271.67 | 325.37 | 18.32 | 105.67 | 237.83 |
July | 383.17 | 0.58 | 0.50 | 01-JUL-07:19 | 371.96 | 14.32 | 0.00 | 275.83 | 329.20 | 17.62 | 92.17 | 242.17 |
August | 369.33 | 0.57 | 0.50 | 01-AUG-07:19 | 384.67 | 14.82 | 0.00 | 276.83 | 335.30 | 18.31 | 100.00 | 243.83 |
September | 357.83 | 0.58 | 0.50 | 01-SEP-07:10 | 370.78 | 14.32 | 0.00 | 259.67 | 340.15 | 19.06 | 111.33 | 239.17 |
October | 356.83 | 0.57 | 0.50 | 01-OCT-07:10 | 691.01 | 15.61 | 35.50 | 257.83 | 342.78 | 18.76 | 96.33 | 232.67 |
November | 337.67 | 0.58 | 0.50 | 01-NOV-07:30 | 341.31 | 14.64 | 0.00 | 239.33 | 290.58 | 18.08 | 87.50 | 207.83 |
December | 349.33 | 0.59 | 0.50 | 01-DEC-07:30 | 306.89 | 14.11 | 0.00 | 238.67 | 258.66 | 17.60 | 75.67 | 203.33 |
Annual Sum or Average | 4292.33 | 0.58 | 549.13 | 14.67 | 72.17 | 3108.83 | 451.95 | 18.32 | 1150.33 | 2711.17 | ||
Minimum of Months | 321.17 | 0.57 | 0.50 | 306.89 | 14.11 | 0.00 | 231.17 | 258.66 | 17.60 | 75.67 | 198.00 | |
Maximum of Months | 383.17 | 0.59 | 0.50 | 1512.88 | 15.80 | 36.67 | 277.17 | 1986.33 | 19.79 | 111.33 | 243.83 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.79 | 0.61 | 21-JAN-16:10 | 261.87 | 22.95 | 174.00 | 42.83 | 154.21 | 21.89 | 173.67 | 10.83 |
February | 321.17 | 0.77 | 0.61 | 01-FEB-16:10 | 290.46 | 23.04 | 155.67 | 64.00 | 205.76 | 23.54 | 170.00 | 29.50 |
March | 361.17 | 0.76 | 0.61 | 02-MAR-14:39 | 297.67 | 22.33 | 161.17 | 76.33 | 240.23 | 23.19 | 190.67 | 46.67 |
April | 358.33 | 0.75 | 0.61 | 01-APR-14:20 | 258.34 | 20.75 | 134.83 | 56.67 | 233.60 | 22.03 | 185.17 | 46.50 |
May | 376.33 | 0.76 | 0.61 | 01-MAY-14:20 | 253.10 | 19.71 | 107.83 | 53.67 | 187.71 | 21.09 | 165.67 | 26.83 |
June | 370.50 | 0.73 | 0.61 | 01-JUN-14:39 | 282.63 | 20.17 | 118.67 | 66.17 | 221.35 | 21.64 | 180.50 | 30.33 |
July | 383.17 | 0.77 | 0.61 | 02-JUL-16:10 | 242.24 | 19.19 | 94.67 | 32.33 | 175.37 | 20.56 | 147.67 | 25.00 |
August | 369.33 | 0.76 | 0.61 | 01-AUG-14:30 | 252.13 | 20.06 | 114.83 | 48.50 | 198.55 | 21.38 | 171.33 | 30.83 |
September | 357.83 | 0.79 | 0.61 | 02-SEP-14:30 | 221.05 | 19.64 | 114.17 | 28.33 | 166.86 | 21.68 | 158.00 | 20.17 |
October | 356.83 | 0.79 | 0.61 | 02-OCT-14:09 | 225.91 | 21.83 | 152.17 | 34.17 | 147.39 | 22.90 | 181.33 | 11.83 |
November | 337.67 | 0.79 | 0.61 | 02-NOV-14:30 | 223.22 | 22.45 | 165.50 | 24.00 | 134.08 | 22.02 | 170.33 | 2.83 |
December | 349.33 | 0.80 | 0.63 | 05-DEC-15:30 | 229.53 | 22.43 | 172.33 | 29.00 | 123.91 | 20.82 | 163.17 | 0.00 |
Annual Sum or Average | 4292.33 | 0.77 | 253.09 | 21.16 | 1665.83 | 556.00 | 182.81 | 21.87 | 2057.50 | 281.33 | ||
Minimum of Months | 321.17 | 0.73 | 0.61 | 221.05 | 19.19 | 94.67 | 24.00 | 123.91 | 20.56 | 147.67 | 0.00 | |
Maximum of Months | 383.17 | 0.80 | 0.63 | 297.67 | 23.04 | 174.00 | 76.33 | 240.23 | 23.54 | 190.67 | 46.67 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.127704E+11 | 0.879119E+10 | 30721.00 | 02-JAN-06:02 | 14561.29 | 0.00 |
February | 0.00 | 0.00 | 0.123707E+11 | 0.861381E+10 | 30203.04 | 06-FEB-06:01 | 16175.33 | 0.00 |
March | 0.00 | 0.00 | 0.157747E+11 | 0.106663E+11 | 30430.44 | 25-MAR-05:01 | 14827.08 | 0.00 |
April | 0.00 | 0.00 | 0.161818E+11 | 0.102338E+11 | 30439.15 | 24-APR-05:01 | 15536.51 | 0.00 |
May | 0.00 | 0.00 | 0.182651E+11 | 0.107010E+11 | 30691.93 | 18-MAY-05:02 | 13086.08 | 0.00 |
June | 0.00 | 0.00 | 0.185343E+11 | 0.109049E+11 | 30721.00 | 21-JUN-05:01 | 14230.76 | 0.00 |
July | 0.00 | 0.00 | 0.145676E+11 | 0.921639E+10 | 30452.22 | 24-JUL-05:01 | 15196.99 | 0.00 |
August | 0.00 | 0.00 | 0.177312E+11 | 0.100844E+11 | 30691.93 | 04-AUG-05:01 | 13652.45 | 0.00 |
September | 0.00 | 0.00 | 0.156629E+11 | 0.927046E+10 | 30527.97 | 22-SEP-05:01 | 14967.38 | 0.00 |
October | 0.00 | 0.00 | 0.147730E+11 | 0.868012E+10 | 30721.00 | 23-OCT-05:02 | 13736.24 | 0.00 |
November | 0.00 | 0.00 | 0.135016E+11 | 0.842776E+10 | 30604.37 | 24-NOV-06:01 | 15545.89 | 0.00 |
December | 0.00 | 0.00 | 0.124919E+11 | 0.839406E+10 | 30721.00 | 11-DEC-06:02 | 14665.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.182625E+12 | 0.113984E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.123707E+11 | 0.839406E+10 | 30203.04 | 13086.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.185343E+11 | 0.109049E+11 | 30721.00 | 16175.33 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.310857E+11 | 0.207032E+11 | 74625.40 | 15-JAN-11:23 | 51992.92 | 0.00 |
February | 0.00 | 0.00 | 0.337861E+11 | 0.228016E+11 | 80884.54 | 16-FEB-06:01 | 45622.01 | 0.00 |
March | 0.00 | 0.00 | 0.449406E+11 | 0.294058E+11 | 82737.11 | 25-MAR-05:10 | 43085.61 | 0.00 |
April | 0.00 | 0.00 | 0.500289E+11 | 0.304540E+11 | 81073.66 | 06-APR-05:08 | 44100.81 | 0.00 |
May | 0.00 | 0.00 | 0.542454E+11 | 0.303747E+11 | 84746.12 | 04-MAY-05:09 | 38732.36 | 0.00 |
June | 0.00 | 0.00 | 0.566092E+11 | 0.317352E+11 | 84623.77 | 10-JUN-05:07 | 39312.37 | 0.00 |
July | 0.00 | 0.00 | 0.395717E+11 | 0.240055E+11 | 84569.03 | 01-JUL-05:08 | 40266.03 | 0.00 |
August | 0.00 | 0.00 | 0.446351E+11 | 0.236315E+11 | 84951.22 | 25-AUG-05:01 | 39699.36 | 0.00 |
September | 0.00 | 0.00 | 0.419810E+11 | 0.235496E+11 | 82564.17 | 20-SEP-05:01 | 43571.66 | 0.00 |
October | 0.00 | 0.00 | 0.358371E+11 | 0.198527E+11 | 83625.96 | 26-OCT-05:09 | 42027.37 | 0.00 |
November | 0.00 | 0.00 | 0.325707E+11 | 0.193575E+11 | 82944.26 | 13-NOV-06:06 | 42941.87 | 0.00 |
December | 0.00 | 0.00 | 0.294019E+11 | 0.188117E+11 | 80221.49 | 09-DEC-06:10 | 47210.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.494693E+12 | 0.294683E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.294019E+11 | 0.188117E+11 | 74625.40 | 38732.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.566092E+11 | 0.317352E+11 | 84951.22 | 51992.92 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.554891E+09 | 0.23 | 1218.99 | 02-JAN-06:01 | 0.89 |
February | 0.542331E+09 | 0.24 | 1218.99 | 01-FEB-06:01 | 0.89 |
March | 0.676743E+09 | 0.27 | 1218.99 | 01-MAR-06:01 | 0.89 |
April | 0.687975E+09 | 0.27 | 1218.99 | 01-APR-05:01 | 0.89 |
May | 0.774563E+09 | 0.29 | 1218.99 | 01-MAY-05:01 | 0.88 |
June | 0.790828E+09 | 0.30 | 1218.99 | 01-JUN-05:01 | 0.89 |
July | 0.603949E+09 | 0.24 | 1218.99 | 01-JUL-05:01 | 0.89 |
August | 0.727155E+09 | 0.28 | 1218.99 | 01-AUG-05:01 | 0.89 |
September | 0.645846E+09 | 0.26 | 1218.99 | 01-SEP-05:01 | 0.89 |
October | 0.601450E+09 | 0.24 | 1218.99 | 02-OCT-05:01 | 0.89 |
November | 0.558334E+09 | 0.23 | 1218.99 | 01-NOV-05:01 | 0.89 |
December | 0.539639E+09 | 0.23 | 1218.99 | 01-DEC-06:01 | 0.89 |
Annual Sum or Average | 0.770370E+10 | 0.26 | |||
Minimum of Months | 0.539639E+09 | 0.23 | 1218.99 | 0.88 | |
Maximum of Months | 0.790828E+09 | 0.30 | 1218.99 | 0.89 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136632E+10 | 0.29 | 2878.36 | 08-JAN-11:23 | 0.87 |
February | 0.135035E+10 | 0.33 | 2878.36 | 05-FEB-10:23 | 0.87 |
March | 0.170614E+10 | 0.37 | 2878.36 | 05-MAR-10:13 | 0.86 |
April | 0.177235E+10 | 0.41 | 2878.36 | 01-APR-17:06 | 0.86 |
May | 0.188640E+10 | 0.41 | 2878.36 | 01-MAY-17:06 | 0.86 |
June | 0.194586E+10 | 0.43 | 2878.36 | 02-JUN-17:10 | 0.86 |
July | 0.155076E+10 | 0.36 | 2878.36 | 01-JUL-05:08 | 0.86 |
August | 0.164814E+10 | 0.35 | 2878.36 | 01-AUG-05:01 | 0.86 |
September | 0.156188E+10 | 0.36 | 2878.36 | 01-SEP-17:08 | 0.86 |
October | 0.145555E+10 | 0.32 | 2878.36 | 01-OCT-10:23 | 0.86 |
November | 0.134717E+10 | 0.31 | 2878.36 | 03-NOV-05:01 | 0.86 |
December | 0.134467E+10 | 0.28 | 2878.36 | 03-DEC-10:23 | 0.87 |
Annual Sum or Average | 0.189356E+11 | 0.35 | |||
Minimum of Months | 0.134467E+10 | 0.28 | 2878.36 | 0.86 | |
Maximum of Months | 0.194586E+10 | 0.43 | 2878.36 | 0.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.336707E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.330247E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.421810E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.430187E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.481886E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.490534E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.375455E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.454368E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.403216E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.375697E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.346763E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.326542E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.477341E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.326542E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.490534E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.847561E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.910572E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.120167E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.131170E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.140592E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.146012E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.104050E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.114419E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.108503E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.936153E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.861934E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.802521E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.130079E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.802521E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.146012E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.554891E+09 | 0.127704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.542331E+09 | 0.123707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.676743E+09 | 0.157747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.687975E+09 | 0.161818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.774563E+09 | 0.182651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.790828E+09 | 0.185343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.603949E+09 | 0.145676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.727155E+09 | 0.177312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.645846E+09 | 0.156629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.601450E+09 | 0.147730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.558334E+09 | 0.135016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.539639E+09 | 0.124919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.770370E+10 | 0.182625E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.539639E+09 | 0.123707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.790828E+09 | 0.185343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136632E+10 | 0.310857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135035E+10 | 0.337861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170614E+10 | 0.449406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177235E+10 | 0.500289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.188640E+10 | 0.542454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194586E+10 | 0.566092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155076E+10 | 0.395717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164814E+10 | 0.446351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156188E+10 | 0.419810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145555E+10 | 0.358371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134717E+10 | 0.325707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134467E+10 | 0.294019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189356E+11 | 0.494693E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134467E+10 | 0.294019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.194586E+10 | 0.566092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.554891E+09 | 0.00 | 0.00 | 0.00 | 0.281218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.542331E+09 | 0.00 | 0.00 | 0.00 | 0.276014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.676743E+09 | 0.00 | 0.00 | 0.00 | 0.354135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.687975E+09 | 0.00 | 0.00 | 0.00 | 0.361390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.774563E+09 | 0.00 | 0.00 | 0.00 | 0.404429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.790828E+09 | 0.00 | 0.00 | 0.00 | 0.411451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.603949E+09 | 0.00 | 0.00 | 0.00 | 0.315060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.727155E+09 | 0.00 | 0.00 | 0.00 | 0.381653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.645846E+09 | 0.00 | 0.00 | 0.00 | 0.338632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.601450E+09 | 0.00 | 0.00 | 0.00 | 0.315552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.558334E+09 | 0.00 | 0.00 | 0.00 | 0.290930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.539639E+09 | 0.00 | 0.00 | 0.00 | 0.272578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.770370E+10 | 0.00 | 0.00 | 0.00 | 0.400304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.539639E+09 | 0.00 | 0.00 | 0.00 | 0.272578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.790828E+09 | 0.00 | 0.00 | 0.00 | 0.411451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136632E+10 | 0.00 | 0.00 | 0.00 | 0.710930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135035E+10 | 0.00 | 0.00 | 0.00 | 0.775537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170614E+10 | 0.00 | 0.00 | 0.00 | 0.103105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177235E+10 | 0.00 | 0.00 | 0.00 | 0.113446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.188640E+10 | 0.00 | 0.00 | 0.00 | 0.121728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194586E+10 | 0.00 | 0.00 | 0.00 | 0.126554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155076E+10 | 0.00 | 0.00 | 0.00 | 0.885419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164814E+10 | 0.00 | 0.00 | 0.00 | 0.979375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156188E+10 | 0.00 | 0.00 | 0.00 | 0.928843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145555E+10 | 0.00 | 0.00 | 0.00 | 0.790598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134717E+10 | 0.00 | 0.00 | 0.00 | 0.727216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134467E+10 | 0.00 | 0.00 | 0.00 | 0.668054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189356E+11 | 0.00 | 0.00 | 0.00 | 0.111143E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134467E+10 | 0.00 | 0.00 | 0.00 | 0.668054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.194586E+10 | 0.00 | 0.00 | 0.00 | 0.126554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.214115E+10 | 0.00 | 1655945.52 | 0.00 | 0.00 | 2897376.69 | 0.00 | 0.14 |
February | 0.00 | 0.214660E+10 | 0.00 | 601014.97 | 0.00 | 0.00 | 258078.03 | 0.00 | 0.15 |
March | 0.00 | 0.280811E+10 | 0.00 | 418022.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
April | 0.00 | 0.331950E+10 | 0.00 | 37308.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
May | 0.00 | 0.399231E+10 | 0.00 | 153621.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
June | 0.00 | 0.414433E+10 | 0.00 | 89424.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.284596E+10 | 0.00 | 92408.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
August | 0.00 | 0.389583E+10 | 0.00 | 122704.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.347212E+10 | 0.00 | 1980.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.315755E+10 | 0.00 | 357465.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
November | 0.00 | 0.265386E+10 | 0.00 | 1090349.83 | 0.00 | 0.00 | 142915.72 | 0.00 | 0.14 |
December | 0.00 | 0.225158E+10 | 0.00 | 1739229.38 | 0.00 | 0.00 | 781069.85 | 0.00 | 0.14 |
Annual Sum or Average | 0.00 | 0.368289E+11 | 0.00 | 6359475.19 | 0.00 | 0.00 | 4079440.29 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.214115E+10 | 0.00 | 1980.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Maximum of Months | 0.00 | 0.414433E+10 | 0.00 | 1739229.38 | 0.00 | 0.00 | 2897376.69 | 0.00 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 32370366.93 | 0.661058E+10 | 0.00 | 1056347.32 | 10539704.82 | 0.00 | 86190490.53 | 0.00 | 0.22 |
February | 2113046.31 | 0.754525E+10 | 0.00 | 471365.96 | 13872100.73 | 0.00 | 25999946.03 | 0.00 | 0.24 |
March | 0.00 | 0.985661E+10 | 0.00 | 99759.14 | 18823058.32 | 0.00 | 5155363.41 | 0.00 | 0.26 |
April | 0.00 | 0.132855E+11 | 0.00 | 0.00 | 2038849.14 | 0.00 | 0.00 | 0.00 | 0.26 |
May | 0.00 | 0.158751E+11 | 0.00 | 0.00 | 16447079.84 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.169028E+11 | 0.00 | 0.00 | 14418145.89 | 0.00 | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.102102E+11 | 0.00 | 0.00 | 30454437.87 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.133625E+11 | 0.00 | 31459.18 | 30521512.94 | 0.00 | 919675.49 | 0.00 | 0.25 |
September | 0.00 | 0.126808E+11 | 0.00 | 0.00 | 40669133.55 | 0.00 | 0.00 | 0.00 | 0.25 |
October | 0.00 | 0.104086E+11 | 0.00 | 30989.78 | 32615117.00 | 0.00 | 5551494.39 | 0.00 | 0.23 |
November | 0.00 | 0.887407E+10 | 0.00 | 176807.42 | 24372008.11 | 0.00 | 19371540.99 | 0.00 | 0.23 |
December | 14279392.28 | 0.688231E+10 | 0.00 | 697178.85 | 12356127.13 | 0.00 | 83893060.66 | 0.00 | 0.22 |
Annual Sum or Average | 48762805.53 | 0.132494E+12 | 0.00 | 2563907.64 | 0.247127E+09 | 0.00 | 0.227082E+09 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.661058E+10 | 0.00 | 0.00 | 2038849.14 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 32370366.93 | 0.169028E+11 | 0.00 | 1056347.32 | 40669133.55 | 0.00 | 86190490.53 | 0.00 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:17
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.828781E+12 | 0.457047E+11 | 0.00 | -0.125934E+11 | 0.537775E+11 |
February | 0.827825E+12 | 0.478812E+11 | 0.00 | -0.146189E+11 | 0.566723E+11 |
March | 0.108595E+13 | 0.590056E+11 | 0.00 | -0.178994E+11 | 0.745672E+11 |
April | 0.107924E+13 | 0.593007E+11 | 0.00 | -0.241611E+11 | 0.811692E+11 |
May | 0.103898E+13 | 0.527264E+11 | 0.00 | -0.288495E+11 | 0.887277E+11 |
June | 0.106513E+13 | 0.644895E+11 | 0.00 | -0.293539E+11 | 0.919134E+11 |
July | 0.884440E+12 | 0.529863E+11 | 0.00 | -0.213564E+11 | 0.661441E+11 |
August | 0.112125E+13 | 0.455981E+11 | 0.00 | -0.244839E+11 | 0.759766E+11 |
September | 0.882610E+12 | 0.482541E+11 | 0.00 | -0.249881E+11 | 0.703186E+11 |
October | 0.946299E+12 | 0.427485E+11 | 0.00 | -0.219249E+11 | 0.616716E+11 |
November | 0.780603E+12 | 0.430014E+11 | 0.00 | -0.185352E+11 | 0.562538E+11 |
December | 0.776812E+12 | 0.448703E+11 | 0.00 | -0.135010E+11 | 0.513001E+11 |
Annual Sum or Average | 0.113179E+14 | 0.606567E+12 | 0.00 | -0.252266E+12 | 0.828492E+12 |
Minimum of Months | 0.776812E+12 | 0.427485E+11 | 0.00 | -0.293539E+11 | 0.513001E+11 |
Maximum of Months | 0.112125E+13 | 0.644895E+11 | 0.00 | -0.125934E+11 | 0.919134E+11 |