Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 10:43:14
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1789.51 | 370.11 | 370.11 |
Net Site Energy | 1682.70 | 348.02 | 348.02 |
Total Source Energy | 2658.60 | 549.85 | 549.85 |
Net Source Energy | 2320.34 | 479.89 | 479.89 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1444.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 99.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 42.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 34.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 345.07 | 1444.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1444.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 99.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 42.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 34.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 26.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1444.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 5.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 99.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 42.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 34.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 26.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 29.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 13.83 | 298.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 71.37 | 298.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 29.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 13.83 | 298.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 71.37 | 298.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 111.814 | 32.40 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -5.01 | -1.5 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 106.807 | 30.95 |
Electricity Coming From Utility | 252.855 | 73.28 |
Surplus Electricity Going To Utility | 14.595 | 4.23 |
Net Electricity From Utility | 238.261 | 69.05 |
Total On-Site and Utility Electric Sources | 345.068 | 100.00 |
Total Electricity End Uses | 345.068 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 94.33 |
Time Setpoint Not Met During Occupied Cooling | 1.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3121.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 10:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.1633 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 6.6844 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.1969 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.3473 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.1633 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 6.6844 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.1969 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.3473 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.3473 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-15:30 | 18-JAN-17:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 391004.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10371.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6493.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4308.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1604.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 32812.53 | 391004.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 391004.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 10371.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 6493.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2003.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1604.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1565.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 17.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 314.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 133.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 109.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 84.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1092.83 | 1565.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 323.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 65.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 226.02 | 323.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 323.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 65.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 226.02 | 323.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.935804 |
ZONE2 FINE STORAGE DIRECT AIR | 1.66 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 6.12 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 6.12 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 238876.77 |
PSZ-OFFICE HEATING COIL | 26046.75 |
PSZ-FINE STORAGE HEATING COIL | 67300.01 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 238876.77 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.935804 | 0.935804 | 0.935804 | 0.935804 | 0.935804 | 0.935804 | 1.00 | 1.00 | 0.935804 |
PSZ-FINE STORAGE | 1.66 | 1.66 | 1.66 | 1.66 | 1.66 | 1.66 | 1.00 | 1.00 | 1.66 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.935804 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.66 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.935804 | 1036.08 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.66 | 1775.95 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.935804 | 0.935804 | 0.935804 | 0.935804 | 18552.81 | 26046.75 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.66 | 1.66 | 1.66 | 1.10 | 41214.15 | 67300.01 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.935800 | 0.467902 | 0.623867 | 18552.81 | 9276.41 | 0.779980 | 0.779980 |
PSZ-FINE STORAGE COOLING COIL | 1.66 | 0.829847 | 1.11 | 41214.15 | 20607.08 | 0.701080 | 0.701080 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.163 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 14.237 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 6.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.684 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.197 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 5.756 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1459.960 | 6.163 | 114.518 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1459.960 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 9314.081 | 6.684 | 310.469 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 9314.081 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 10245.499 | 3.197 | 148.485 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10245.499 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1804 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.3574 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.3330 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.6144 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.044 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.6144 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.544 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.798 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.904 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.528 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4892 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.528 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.60435670E-09 | 0.47630797E-14 | 0.24204839E-14 | 0.0000000 |
2 | 1 | -5.2160796 | 0.57881174E-04 | -0.88809346E-04 | 0.11586416E-09 |
3 | 0 | 5.3964676 | 0.18033005 | 0.18047674 | |
4 | 2 | 0.92894805E-09 | 0.33911764E-13 | 0.21779261E-14 | 0.0000000 |
5 | 1 | -5.2160150 | 0.41827095E-04 | -0.44821328E-04 | 0.18401191E-09 |
6 | 0 | 5.5734381 | 0.35738136 | 0.35746801 | |
7 | 4 | 0.81205461E-12 | -0.60820818E-16 | 0.53959138E-14 | 0.11194769E-15 |
8 | 3 | -0.39487908E-03 | 0.23668407E-06 | -0.57379545E-04 | 0.15580508E-12 |
9 | 2 | 1.7634853 | 0.51193665E-02 | 1.1586669 | -0.75705256E-04 |
10 | 1 | -7.0973464 | 0.13173731 | -17.214220 | 0.33800211 |
11 | 0 | 5.5547270 | 0.83614094E-01 | 16.276082 | |
12 | 4 | 0.75524091E-12 | 0.18585927E-15 | -0.24619336E-14 | 0.12165746E-15 |
13 | 3 | -0.37591709E-03 | 0.42679598E-06 | -0.54444663E-04 | 0.14493025E-12 |
14 | 2 | 1.7186597 | 0.94202666E-02 | 1.1245767 | -0.72068922E-04 |
15 | 1 | -7.1564116 | 0.24550773 | -16.996678 | 0.32938266 |
16 | 0 | 5.8501984 | 0.15714209 | 16.284226 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.0441747 | 2.0441747 | 2.0441747 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
55 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
56 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
57 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
58 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
59 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
60 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
61 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
62 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
63 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
64 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
65 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
66 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
67 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
68 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
69 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.24619336E-14 | 0.18585927E-15 | 0.75524091E-12 | 0.12165746E-15 |
85 | 3 | -0.54444663E-04 | 0.42679598E-06 | -0.37591709E-03 | 0.14493025E-12 |
86 | 2 | 1.1245767 | 0.94202666E-02 | 1.7186597 | -0.72068922E-04 |
87 | 1 | -16.996678 | 0.24550773 | -7.1564116 | 0.32938266 |
88 | 0 | 16.284226 | 0.15714209 | 5.8501984 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.342_SHGC_SOUTH_0.379 | 34 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
2 | NONRESWINDOW_U_0.342_SHGC_NORTH_0.379 | 35 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
3 | NONRESWINDOW_U_0.342_SHGC_EAST_0.379 | 36 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
4 | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 37 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
5 | SKYLIGHT_U_0.47_SHGC_0.4 | 38 | 1 | VerySmooth | 2.672 | 2.672 | 1.000 | 0.401 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.555 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.37900 | 0.13994 | 0.18549 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.37900 | 0.13994 | 0.18549 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.37900 | 0.13994 | 0.18549 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.37900 | 0.13994 | 0.18549 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.40629E-002 | 0.31435 | 0.46917 | 0.46917 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11822 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.41263 | 0.18041 | 0.18041 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.055 | 0.5319 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.553 | 0.552 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0426E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7455E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6964E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.8300E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9108E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3918E-004 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0880E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2172E-004 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5266E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4690E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.0600E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.1822E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.1637E-004 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1355E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8576E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9979E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4455E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.2037E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.5775E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.7133E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.1756E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3627E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1682E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1771E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.0426E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4690E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0171E-003 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8900E-004 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5219E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8046E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6087E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.0384E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.2532E-003 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.2649E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.6839E-003 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.6304E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 4.5191E-003 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.4083E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 2.7098E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 4.7591E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.4043E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.8387E-003 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.9142E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.9001E-003 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.5236E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.8560E-003 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.7049E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.6445E-003 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.9991E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.5964E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.7603E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.8328E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 2.5364E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.1276E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.3987E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.8991E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.1728E-003 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.6027E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.8448E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.8361E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.3608E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.1241E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.3986E-003 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.8991E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9039.51873 | 10847.42247 | 0.77984 | 0.93580 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 29.85733 | 1.53626E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 12793.78126 | 15352.53751 | 0.37663 | 0.45196 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20000 | 3.61342E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 20564.00223 | 24676.80268 | 1.38308 | 1.65969 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 46886.87232 | 56264.24678 | 1.16205 | 1.39446 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -26.20000 | 3.61342E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 199063.97854 | 238876.77425 | 5.09852 | 6.11822 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 13578.79 | 0.93580 | 0.93580 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 15463.42 | 0.45196 | 0.45196 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 30351.64 | 1.65969 | 1.65969 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 59815.23 | 1.39446 | 1.39446 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.93580 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.65969 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.11822 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 6.11822 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 238876.77098 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 238876.77425 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.93580 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.93580 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.93580 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.93580 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.93580 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.93580 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.65969 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.65969 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.65969 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.65969 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.65969 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.65969 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.93580 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.65969 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.93580 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.93580 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1036.08374 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.93580 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.93580 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.93580 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.93580 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.93580 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46790 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62387 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18552.81000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9276.40500 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77998 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77998 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18552.81000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26046.75307 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26046.75307 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.65969 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.65969 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1775.95092 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.65969 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.65969 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.65969 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.09540 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.65969 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.82985 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.10646 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41214.15000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20607.07500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41214.15000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 67300.01085 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 67300.01085 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 17826.2 | 12.62 | 12.33 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 39924.1 | 12.06 | 11.79 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.2649972058 | 0.2313045667 | Pass | Pass | 0.2996881689 | 1.0617769579 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.5070575170 | 0.4603980561 | Pass | Pass | 0.4798795813 | 0.6309394412 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 4.8875608296E-005 | 1.2487586209E-004 | Pass | Pass | 1.9528120996E-002 | 2.0931055878E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8310.47 | 1018.64 | 0.00 | 83.92 | 286.41 | 9699.46 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.317 | 0.333 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.176 | 0.180 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.563 | 0.614 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.563 | 0.614 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.563 | 0.614 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.341 | 0.357 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.614 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.536 | 0.614 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.943 | 0.380 | 0.380 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.342_SHGC_WEST_0.379 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.943 | 0.380 | 0.380 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.342_SHGC_NORTH_0.379 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.943 | 0.380 | 0.380 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.342_SHGC_NORTH_0.379 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.943 | 0.380 | 0.380 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 3.003 | 0.460 | 0.459 | |||||||||||||||||
North Total or Average | 6.51 | 1.943 | 0.380 | 0.380 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.268 | 0.480 | 0.478 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.565 | 2.044 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 1.598 | 2.101 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.1633 | 236.88 | 1459.96 | LightsWired | LTG_SCH_OFFICE | 44.65 | 168.00 | 28.16 | 0.0000 | Y | 7.72 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 6.6844 | 1393.41 | 9314.08 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 25.41 | 0.0000 | Y | 44.43 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.1969 | 3204.84 | 10245.50 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 24.55 | 0.0000 | Y | 47.22 |
Interior Lighting Total | 4.3473 | 4835.13 | 21019.54 | 99.37 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.12 | 10245.50 | 1188.48 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1459.96 | 423.39 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1459.96 | 146.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 119.03 | AstronomicalClock | - | 42.24 | 42.24 | 0.94 | |
EXTERIOR_LIGHTS_B | 2955.82 | AstronomicalClock | - | 83.63 | 62.93 | 34.92 | |
EXTERIOR_LIGHTS_C | 694.12 | AstronomicalClock | - | 83.63 | 49.46 | 6.44 | |
Exterior Lighting Total | 3768.97 | 42.31 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18552.81 | 14470.82 | 4081.99 | 0.78 | 4.12 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41214.15 | 28894.42 | 12319.73 | 0.70 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 17826.2 | 12.62 | 12.33 | ||||
PSZ-FINE STORAGE COOLING COIL | 39924.1 | 12.06 | 11.79 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 238876.77 | 0.85 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26046.75 | 0.84 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 67300.01 | 0.85 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 6.12 | 568.45 | 92.91 | 1.00 | 3.09 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.94 | 1036.08 | 1107.16 | 1.00 | 1.42 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.66 | 1775.95 | 1070.05 | 1.00 | 1.34 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.06 | 0.53 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9039.52 | 10847.42 | 45.79 | 0.780 | 0.936 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 23.90 | 23.90 | 0.00885 | 29.86 | 0.01536 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 20564.00 | 24676.80 | 17.71 | 1.383 | 1.660 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 26.70 | 26.69 | 0.01026 | 31.09 | 0.01536 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 31.34 | 0.01543 | 31.09 | 0.01536 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12793.78 | 15352.54 | 64.81 | 0.377 | 0.452 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00715 | -26.20 | 0.00036 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 46886.87 | 56264.25 | 40.38 | 1.162 | 1.394 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.55 | 0.00572 | -26.20 | 0.00036 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 199063.98 | 238876.77 | 74.54 | 5.099 | 6.118 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 9.99 | 0.00520 | -26.20 | 0.00036 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.94 | 0.94 | 0.45 | 0.45 | 0.9358 | 0.9358 | 0.9358 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.66 | 1.66 | 1.39 | 1.39 | 1.6597 | 1.6597 | 1.6597 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 238876.771 | 238876.771 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 238876.77 | 238876.77 | 6.118219 | 9.99 | 6.89 | 0.00519952 | 43.33 | 21.59 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 9.99 | 0.00519952 | 65.2669 | 238876.77 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 18552.810 | 14470.821 | 0.935800 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 9276.41 | 7411.49 | 0.623867 | 25.54 | 17.31 | 0.00956557 | 12.00 | 10.84 | 0.00800000 | 30.28 | 0.01536338 | 22.88 | 16.3953 | 23.90 | 0.00885258 | 45.7096 | 9022.37 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26046.753 | 26046.753 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26046.75 | 26046.75 | 0.935804 | 15.88 | 10.85 | 0.00640661 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 10.9301 | 21.10 | 0.00714845 | 43.8781 | 12793.78 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 41214.150 | 28894.416 | 1.659690 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 20607.08 | 13962.29 | 1.106460 | 28.76 | 19.86 | 0.01156523 | 12.00 | 10.84 | 0.00800000 | 31.20 | 0.01536508 | 23.13 | 38.3847 | 26.69 | 0.01025815 | 44.7471 | 20560.34 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 67300.011 | 67300.011 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 67300.01 | 67300.01 | 1.659694 | 4.87 | 3.25 | 0.00435008 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 25.5897 | 15.55 | 0.00572181 | 49.8586 | 46886.87 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 238876.771 | 238876.771 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 6.118219 | 7.02711643 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 238876.77 | 238876.77 | 1.0000 | 7.02711643 | 6.118219 | 9.99 | 6.89 | 0.00519952 | 23142.2 | 43.33 | 21.59 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 238876.77 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 9.99 | 0.00519952 | 9.99 | 0.00519952 | 65.2669 | 238876.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18552.810 | 14470.821 | 0.935800 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.6219 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.935804 | 1.07482331 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | Sensible | 9276.41 | 7411.49 | 1.0000 | 0.71654570 | 0.623867 | 25.54 | 17.31 | 0.00956557 | 50039.6 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9276.41 | 30.28 | 0.01536338 | 22.88 | 0.10228463 | 16.3953 | 23.90 | 0.00885258 | 23.90 | 0.00885258 | 45.7096 | 9022.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26046.753 | 26046.753 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.935804 | 1.07482331 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 26046.75 | 26046.75 | 1.0000 | 1.07482331 | 0.935804 | 15.88 | 10.85 | 0.00640661 | 32172.2 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26046.75 | -26.20 | 0.00036134 | -26.20 | 0.10228463 | 10.9301 | 21.05 | 0.00714845 | 21.10 | 0.00714845 | 43.8781 | 12793.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41214.150 | 28894.416 | 1.659690 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.3392 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.659694 | 1.90625109 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 20607.08 | 13962.29 | 1.0000 | 1.27083108 | 1.106460 | 28.76 | 19.86 | 0.01156523 | 58437.1 | 12.00 | 10.84 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20607.08 | 31.20 | 0.01536508 | 23.13 | 0.42471127 | 38.3847 | 26.69 | 0.01025815 | 26.69 | 0.01025815 | 44.7471 | 20560.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 67300.011 | 67300.011 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.659694 | 1.90625109 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 67300.01 | 67300.01 | 1.0000 | 1.90625109 | 1.659694 | 4.87 | 3.25 | 0.00435008 | 15808.0 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 67300.01 | -26.20 | 0.00036134 | -26.20 | 0.42471127 | 25.5897 | 15.55 | 0.00572181 | 15.55 | 0.00572181 | 49.8586 | 46886.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 0.94 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.66 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2948.67 | 3050.50 | 2530.00 |
ZONE2 FINE STORAGE | 3317.00 | 3254.00 | 2984.33 |
ZONE3 BULK STORAGE | 3375.00 | 3276.17 | 3069.17 |
Facility | 3414.83 | 3369.17 | 3121.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 245.33 | 1.33 | 74.17 | 1.33 |
ZONE2 FINE STORAGE | 592.50 | 1.17 | 29.17 | 0.00 |
ZONE3 BULK STORAGE | 18.17 | 0.00 | 11.17 | 0.00 |
Facility | 763.00 | 2.50 | 94.33 | 1.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.583 | 0.366 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.450 | 0.352 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.185 | 0.000 | 0.099 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.28 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2097765.76 | 0.00 | 2097765.76 | 2349425.27 | 4447191.03 | 3225648.14 | 5691.70 | 2528.08 | 540.22 | 0.00 |
ZONE2 FINE STORAGE | 4803788.39 | 0.00 | 4803788.39 | 9790874.37 | 14594662.76 | 13393694.68 | 5728.58 | 2903.22 | 128.19 | 1.25 |
ZONE3 BULK STORAGE | 0.00 | 25674547.86 | 25674547.86 | 48436561.36 | 74111109.22 | 30805497.77 | 6728.08 | 131.33 | 1900.58 | 5100.17 |
Total Facility | 6901554.15 | 25674547.86 | 32576102.01 | 60576861.00 | 93152963.01 | 47424840.58 | 7871.83 | 3094.58 | 2492.64 | 5100.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1603 | 0.0000 | 0.1603 | 0.1012 | 0.2614 | 0.1023 | 567.70 | 2528.08 | 540.22 |
ZONE2 FINE STORAGE | 0.3667 | 0.0000 | 0.3667 | 0.2881 | 0.6548 | 0.4247 | 605.83 | 2903.22 | 126.94 |
ZONE3 BULK STORAGE | 0.0000 | 0.9619 | 0.9619 | 1.8313 | 2.7931 | 0.9768 | 2630.67 | 53.00 | 952.33 |
Total Facility | 0.5270 | 0.9619 | 1.4889 | 2.2206 | 3.7094 | 1.5038 | 2747.83 | 3016.25 | 1543.14 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2767331.66 | 0.00 | 2767331.66 | 3225648.14 | 5688.11 | 0.00 | 3071.89 | 0.00 |
PSZ-FINE STORAGE | 6337188.66 | 0.00 | 6337188.66 | 13393694.68 | 5728.58 | 0.00 | 3031.42 | 1.25 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2114 | 0.0000 | 0.2114 | 0.1023 | 564.11 | 0.00 | 3071.89 |
PSZ-FINE STORAGE | 0.4838 | 0.0000 | 0.4838 | 0.4247 | 605.83 | 0.00 | 3030.17 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2872.69 | 207.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 3008.42 | 23.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2298 | 0.5252 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5785 | 0.8494 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 411 |
Defaulted Fields | 323 |
Fields with Defaults | 1058 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 345.07 | 1698.09 | 19-MAR-09:20 | 32812.53 | 04-AUG-15:30 |
Electricity:Building | 236.02 | 1217.09 | 01-JAN-10:10 | 19679.04 | 04-AUG-11:00 |
Electricity:Zone:ZONE1 OFFICE | 36.88 | 520.87 | 01-JAN-00:10 | 2598.04 | 02-JAN-16:40 |
Electricity:SpaceType:GENERAL | 235.87 | 1217.09 | 01-JAN-10:10 | 18023.64 | 12-DEC-16:00 |
InteriorLights:Electricity | 99.37 | 747.21 | 01-JAN-10:10 | 7988.46 | 12-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 7.72 | 51.00 | 01-JAN-00:10 | 762.98 | 02-JAN-16:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 99.37 | 747.21 | 01-JAN-10:10 | 7988.46 | 12-DEC-16:00 |
LightsWired:InteriorLights:Electricity | 99.37 | 747.21 | 01-JAN-10:10 | 7988.46 | 12-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 7.72 | 51.00 | 01-JAN-00:10 | 762.98 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 99.37 | 747.21 | 01-JAN-10:10 | 7988.46 | 12-DEC-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 44.43 | 299.97 | 01-JAN-00:10 | 3463.72 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 44.43 | 299.97 | 01-JAN-00:10 | 3463.72 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 44.43 | 299.97 | 01-JAN-00:10 | 3463.72 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 154.71 | 396.24 | 01-JAN-10:10 | 13873.54 | 29-JUN-14:10 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 47.22 | 396.24 | 01-JAN-10:10 | 3774.93 | 05-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 47.22 | 396.24 | 01-JAN-10:10 | 3774.93 | 05-DEC-16:00 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 34.63 | 0.00 | 18-MAR-17:10 | 4308.84 | 04-AUG-15:30 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.15 | 0.00 | 01-JAN-00:10 | 2305.29 | 03-AUG-17:10 |
Ventilation (simple):Fans:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 2305.29 | 03-AUG-17:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.15 | 0.00 | 01-JAN-00:10 | 2305.29 | 03-AUG-17:10 |
ElectricityProduced:Facility | 106.81 | -0.00 | 03-APR-18:30 | 21002.45 | 25-APR-12:20 |
ElectricityProduced:Plant | 106.81 | -0.00 | 03-APR-18:30 | 21002.45 | 25-APR-12:20 |
Photovoltaic:ElectricityProduced | 111.81 | 0.00 | 01-JAN-00:10 | 21870.23 | 25-APR-12:20 |
PowerConversion:ElectricityProduced | -5.01 | -867.78 | 25-APR-12:20 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 26.79 | 481.00 | 02-JAN-06:40 | 2938.59 | 17-FEB-12:50 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 252.86 | 0.00 | 01-JAN-10:00 | 25993.72 | 18-JAN-17:00 |
ElectricityPurchased:Plant | 252.86 | 0.00 | 01-JAN-10:00 | 25993.72 | 18-JAN-17:00 |
Cogeneration:ElectricityPurchased | 252.86 | 0.00 | 01-JAN-10:00 | 25993.72 | 18-JAN-17:00 |
General:Cogeneration:ElectricityPurchased | 252.86 | 0.00 | 01-JAN-10:00 | 25993.72 | 18-JAN-17:00 |
ElectricitySurplusSold:Facility | 14.59 | 0.00 | 01-JAN-00:10 | 18535.30 | 23-APR-12:10 |
ElectricitySurplusSold:Plant | 14.59 | 0.00 | 01-JAN-00:10 | 18535.30 | 23-APR-12:10 |
Cogeneration:ElectricitySurplusSold | 14.59 | 0.00 | 01-JAN-00:10 | 18535.30 | 23-APR-12:10 |
General:Cogeneration:ElectricitySurplusSold | 14.59 | 0.00 | 01-JAN-00:10 | 18535.30 | 23-APR-12:10 |
ElectricityNet:Facility | 238.26 | -18535.30 | 23-APR-12:10 | 25993.72 | 18-JAN-17:00 |
ElectricityNet:Plant | 238.26 | -18535.30 | 23-APR-12:10 | 25993.72 | 18-JAN-17:00 |
Cogeneration:ElectricityNet | 238.26 | -18535.30 | 23-APR-12:10 | 25993.72 | 18-JAN-17:00 |
General:Cogeneration:ElectricityNet | 238.26 | -18535.30 | 23-APR-12:10 | 25993.72 | 18-JAN-17:00 |
Electricity:HVAC | 39.95 | 0.00 | 18-MAR-17:10 | 12379.38 | 04-AUG-15:40 |
General:Fans:Electricity | 34.48 | 0.00 | 18-MAR-17:10 | 3380.48 | 18-JAN-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 5.47 | 0.00 | 01-JAN-00:10 | 10378.84 | 04-AUG-15:40 |
General:Cooling:Electricity | 5.47 | 0.00 | 01-JAN-00:10 | 10378.84 | 04-AUG-15:40 |
ExteriorLights:Electricity | 42.31 | 0.00 | 01-JAN-08:00 | 3768.97 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 42.31 | 0.00 | 01-JAN-08:00 | 3768.97 | 01-JAN-06:10 |
WaterSystems:Electricity | 26.79 | 481.00 | 02-JAN-06:40 | 2938.59 | 17-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 26.79 | 481.00 | 02-JAN-06:40 | 2938.59 | 17-FEB-12:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1444.44 | 0.00 | 18-MAR-17:10 | 391004.26 | 18-JAN-17:10 |
NaturalGas:HVAC | 1444.44 | 0.00 | 18-MAR-17:10 | 391004.26 | 18-JAN-17:10 |
Heating:NaturalGas | 1444.44 | 0.00 | 18-MAR-17:10 | 391004.26 | 18-JAN-17:10 |
General:Heating:NaturalGas | 1444.44 | 0.00 | 18-MAR-17:10 | 391004.26 | 18-JAN-17:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2388.18 | 0.00 | 18-MAR-17:10 | 663278.76 | 09-DEC-06:10 |
EnergyTransfer:Building | 1175.03 | 0.00 | 18-MAR-17:10 | 332852.22 | 09-DEC-06:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 73.59 | 0.00 | 01-JAN-00:40 | 27375.68 | 19-JAN-07:20 |
Heating:EnergyTransfer | 1150.17 | 0.00 | 18-MAR-17:10 | 332852.22 | 09-DEC-06:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 61.73 | 0.00 | 01-JAN-00:40 | 27375.68 | 19-JAN-07:20 |
General:Heating:EnergyTransfer | 1150.17 | 0.00 | 18-MAR-17:10 | 332852.22 | 09-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 61.73 | 0.00 | 01-JAN-00:40 | 27375.68 | 19-JAN-07:20 |
Cooling:EnergyTransfer | 24.86 | 0.00 | 01-JAN-00:10 | 20163.37 | 04-AUG-15:30 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 11.86 | 0.00 | 01-JAN-00:10 | 7438.39 | 04-AUG-16:10 |
General:Cooling:EnergyTransfer | 24.86 | 0.00 | 01-JAN-00:10 | 20163.37 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 11.86 | 0.00 | 01-JAN-00:10 | 7438.39 | 04-AUG-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 220.51 | 0.00 | 01-JAN-00:40 | 68932.71 | 09-DEC-08:00 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 207.52 | 0.00 | 01-JAN-00:40 | 68932.71 | 09-DEC-08:00 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 207.52 | 0.00 | 01-JAN-00:40 | 68932.71 | 09-DEC-08:00 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 13.00 | 0.00 | 01-JAN-00:10 | 12826.20 | 04-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 13.00 | 0.00 | 01-JAN-00:10 | 12826.20 | 04-AUG-15:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 880.93 | 0.00 | 24-FEB-09:40 | 241384.91 | 09-DEC-09:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 880.93 | 0.00 | 24-FEB-09:40 | 241384.91 | 09-DEC-09:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 880.93 | 0.00 | 24-FEB-09:40 | 241384.91 | 09-DEC-09:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1213.15 | 0.00 | 18-MAR-17:10 | 332223.53 | 18-JAN-17:10 |
HeatingCoils:EnergyTransfer | 1188.32 | 0.00 | 18-MAR-17:10 | 332223.53 | 18-JAN-17:10 |
CoolingCoils:EnergyTransfer | 24.83 | 0.00 | 01-JAN-00:10 | 43166.46 | 04-AUG-15:40 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 61.730 | -11.860 | 0.000 | 0.000 | 10.215 | 7.717 | 29.165 | 11.036 | 0.000 | 0.602 | 0.001 | 0.000 | -9.279 | 0.000 | -41.414 | -57.913 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 207.519 | -12.995 | 0.000 | 0.000 | 27.313 | 44.427 | 0.000 | 0.000 | 0.000 | 1.470 | 0.002 | 0.000 | 0.000 | 0.000 | -150.328 | -117.405 |
ZONE3 BULK STORAGE | 880.924 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 68.107 | 47.222 | 107.344 | 126.558 | 0.000 | 19.329 | 0.000 | 0.000 | -72.606 | 0.000 | -817.599 | -359.279 |
Total Facility | 880.924 | 0.000 | 269.248 | -24.855 | 0.000 | 0.000 | 105.635 | 99.366 | 136.508 | 137.594 | 0.000 | 21.402 | 0.003 | 0.000 | -81.885 | 0.000 | -1009.341 | -534.596 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 08-SEP-05:03 | 0.00 | 0.00 | 0.00 | -17323.45 | 0.00 | 0.00 | 93.17 | 51.00 | 550.52 | 0.00 | 0.00 | 0.00 | 17502.34 | 0.00 | -369.98 | 0.00 | -503.58 | 0.00 |
ZONE2 FINE STORAGE | 05-JUL-17:12 | 0.00 | 0.00 | 0.00 | -26884.98 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 26591.70 | 0.00 | -0.00 | 0.00 | -6.69 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-JUL-17:12 | 0.00 | 0.00 | 0.00 | -26884.98 | 0.00 | 0.00 | 0.00 | 764.92 | 2519.91 | 14345.78 | 0.00 | 57.65 | 12604.03 | 0.00 | 0.00 | 0.00 | -3407.31 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 15-DEC-06:31 | 0.00 | 0.00 | 27874.82 | 0.00 | 0.00 | 0.00 | 140.34 | 227.91 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -924.03 | 0.00 | -2807.09 | -25062.46 |
ZONE2 FINE STORAGE | 09-DEC-06:01 | 0.00 | 0.00 | 72183.97 | 0.00 | 0.00 | 0.00 | 404.88 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -36031.88 | -36856.95 |
ZONE3 BULK STORAGE | 09-DEC-08:55 | 241852.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8633.13 | 3275.07 | 8200.12 | 0.00 | 0.00 | 0.00 | 21706.32 | 0.00 | -6850.53 | 0.00 | -276816.13 | 0.00 |
Total Facility | 09-DEC-06:01 | 240371.60 | 0.00 | 98773.29 | 0.00 | 0.00 | 0.00 | 1488.00 | 799.21 | 2600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9426.00 | 0.00 | -262751.74 | -71854.91 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9358 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9358 | 0.1093 | 1.0000 | Not calculated | 0.1023 | 0.1093 | ||
PSZ-FINE STORAGE | 1.6597 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.6597 | 0.2559 | 1.0000 | Not calculated | 0.4247 | 0.2559 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9358 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9358 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1093 | ||
PSZ-FINE STORAGE | 1.6597 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.6597 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2559 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9358 | 0.9358 | 0.9358 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6597 | 1.6597 | 1.6597 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9358 | 0.9358 | 0.9358 | 0.9358 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.6597 | 1.6597 | 1.6597 | 1.6597 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9358 | 0.9358 | 0.9358 | No | 0.1023 | 0.2263 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6597 | 1.6597 | 1.6597 | No | 0.4247 | 0.3046 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9358 | 0.9358 | 0.9358 | 0.9358 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.6597 | 1.6597 | 1.6597 | 1.6597 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 94.33 |
Number of hours cooling loads not met | 1.33 |
Number of hours not met | 95.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1444.44 | 391004.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 5.47 | 10378.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 99.37 | 7988.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 42.31 | 3768.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.15 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 34.48 | 3380.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 26.79 | 2938.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 345.07 |
Natural Gas | 0.00 | 1444.44 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 1789.51 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 111.81 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 20.55 |
Space Heating | 0.00 |
Space Cooling | 1.13 |
Fans (All) | 7.16 |
Service Water Heating | 5.54 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 71.37 |
Subtotal | 71.37 |
Natural Gas [MJ/m2] | |
Space Heating | 298.74 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 298.74 |
Subtotal | 298.74 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.55 |
Space Heating | 80.72 |
Space Cooling | 0.31 |
Fans (All) | 1.94 |
Service Water Heating | 1.50 |
Receptacle Equipment | 7.63 |
Miscellaneous | 2.36 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
LTG_SCH_OFFICE | 2328. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8614.50 | 145.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8341.00 | 419.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8167.33 | 568.00 | 24.67 | 0.00 | 0.00 |
Min | 8167.33 | 145.50 | 0.00 | 0.00 | 0.00 |
Max | 8614.50 | 568.00 | 24.67 | 0.00 | 0.00 |
Average | 8374.28 | 377.50 | 8.22 | 0.00 | 0.00 |
Sum | 25122.83 | 1132.50 | 24.67 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 74496.50 | 8222.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 170637.00 | 19440.50 | 1115.50 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 170637.00 | 19440.50 | 1115.50 | 0.00 | 0.00 |
Average | 92720.17 | 9221.00 | 371.83 | 0.00 | 0.00 |
Sum | 278160.50 | 27663.00 | 1115.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7826.17 | 933.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7456.67 | 1303.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7427.83 | 1322.83 | 9.33 | 0.00 | 0.00 |
Min | 7427.83 | 933.83 | 0.00 | 0.00 | 0.00 |
Max | 7826.17 | 1322.83 | 9.33 | 0.00 | 0.00 |
Average | 7570.22 | 1186.67 | 3.11 | 0.00 | 0.00 |
Sum | 22710.67 | 3560.00 | 9.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31175.50 | 1851.50 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 66470.00 | 16249.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 156918.83 | 33733.67 | 540.50 | 0.00 | 0.00 |
Min | 31175.50 | 1851.50 | 0.00 | 0.00 | 0.00 |
Max | 156918.83 | 33733.67 | 540.50 | 0.00 | 0.00 |
Average | 84854.78 | 17278.06 | 180.17 | 0.00 | 0.00 |
Sum | 254564.33 | 51834.17 | 540.50 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 10:43:14
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.496703E+09 | 603.25 | 23-JAN-08:09 | -17.8 | -18.4 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.457197E+09 | 603.25 | 18-FEB-08:09 | -15.3 | -15.7 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -11.0 | -12.0 | 0.536810E+09 | 625.09 | 25-MAR-15:20 | 18.53 | 10.46 |
April | 41145903.70 | 2316.06 | 18-APR-15:10 | 27.75 | 20.46 | 0.509202E+09 | 783.04 | 18-APR-10:50 | 27.75 | 20.46 |
May | 0.101570E+09 | 3215.30 | 31-MAY-15:50 | 28.58 | 18.94 | 0.564677E+09 | 773.23 | 12-MAY-14:30 | 28.58 | 18.94 |
June | 0.219556E+10 | 14844.59 | 28-JUN-05:03 | 17.48 | 16.30 | 0.636639E+09 | 769.02 | 30-JUN-08:09 | 24.68 | 21.44 |
July | 0.369098E+10 | 17038.96 | 01-JUL-05:03 | 15.78 | 13.80 | 0.634358E+09 | 769.02 | 05-JUL-08:30 | 22.25 | 20.08 |
August | 0.384971E+10 | 14993.29 | 14-AUG-05:03 | 15.68 | 14.97 | 0.684970E+09 | 769.02 | 23-AUG-15:20 | 22.97 | 20.08 |
September | 0.197758E+10 | 17329.62 | 08-SEP-05:03 | 14.32 | 13.31 | 0.597233E+09 | 769.02 | 11-SEP-09:20 | 24.27 | 19.86 |
October | 3326725.48 | 233.46 | 31-OCT-14:50 | 10.57 | 4.59 | 0.504936E+09 | 764.50 | 20-OCT-15:39 | 10.57 | 4.59 |
November | 50356.20 | 53.94 | 04-NOV-16:00 | 12.80 | 6.21 | 0.478508E+09 | 671.74 | 03-NOV-15:09 | 12.80 | 6.21 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.3 | 0.496977E+09 | 603.25 | 09-DEC-09:09 | -22.7 | -22.9 |
Annual Sum or Average | 0.118599E+11 | 0.659821E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.457197E+09 | 603.25 | -22.7 | -22.9 | ||
Maximum of Months | 0.384971E+10 | 17329.62 | 28.58 | 20.46 | 0.684970E+09 | 783.04 | 28.58 | 21.44 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6334146.56 | 5409.84 | 12-JAN-14:35 | 2.60 | 0.93 | 0.648873E+09 | 787.42 | 02-JAN-11:00 | 2.60 | 0.93 |
February | 93135954.44 | 6888.41 | 21-FEB-13:55 | -0.6 | -2.8 | 0.597406E+09 | 821.85 | 24-FEB-15:30 | 8.30 | 5.75 |
March | 0.338624E+09 | 3920.73 | 27-MAR-14:10 | 6.20 | 2.76 | 0.712942E+09 | 1067.59 | 25-MAR-15:20 | 6.20 | 2.76 |
April | 0.935307E+09 | 6029.23 | 22-APR-13:50 | 2.12 | -0.3 | 0.754411E+09 | 1859.06 | 18-APR-15:30 | 2.12 | -0.3 |
May | 0.908895E+09 | 3841.54 | 02-MAY-10:10 | 6.38 | 3.59 | 0.102327E+10 | 2063.57 | 31-MAY-15:39 | 28.87 | 19.09 |
June | 0.183461E+10 | 25042.76 | 30-JUN-17:20 | 28.30 | 20.31 | 0.152820E+10 | 2246.80 | 30-JUN-12:09 | 28.30 | 20.31 |
July | 0.254421E+10 | 26882.21 | 05-JUL-17:12 | 26.70 | 20.75 | 0.173669E+10 | 2246.83 | 08-JUL-14:00 | 22.80 | 17.34 |
August | 0.210586E+10 | 23600.07 | 03-AUG-17:20 | 30.20 | 24.42 | 0.185189E+10 | 2246.89 | 04-AUG-13:20 | 32.23 | 26.41 |
September | 0.195490E+10 | 6344.56 | 08-SEP-15:10 | 29.90 | 18.99 | 0.135983E+10 | 2246.84 | 09-SEP-15:39 | 28.13 | 16.40 |
October | 0.170070E+10 | 5150.05 | 23-OCT-10:00 | 3.70 | 1.00 | 0.736013E+09 | 1320.73 | 20-OCT-15:30 | 3.70 | 1.00 |
November | 0.554376E+09 | 4211.97 | 04-NOV-09:00 | 5.60 | 2.83 | 0.655235E+09 | 1126.57 | 03-NOV-14:50 | 5.60 | 2.83 |
December | 18655944.46 | 1950.21 | 02-DEC-15:30 | 5.85 | 3.25 | 0.648156E+09 | 787.42 | 30-DEC-10:00 | -1.1 | -1.8 |
Annual Sum or Average | 0.129956E+11 | 0.122529E+11 | ||||||||
Minimum of Months | 6334146.56 | 1950.21 | -0.6 | -2.8 | 0.597406E+09 | 787.42 | -1.1 | -1.8 | ||
Maximum of Months | 0.254421E+10 | 26882.21 | 30.20 | 24.42 | 0.185189E+10 | 2246.89 | 32.23 | 26.41 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.643527E+09 | 780.74 | 12-JAN-13:20 | 2.20 | 0.51 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.596961E+09 | 1000.66 | 24-FEB-15:30 | 8.30 | 5.75 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -11.0 | -12.0 | 0.767560E+09 | 1612.17 | 25-MAR-15:30 | 18.35 | 10.46 |
April | 0.00 | 0.00 | 01-APR-00:05 | -1.2 | -2.2 | 0.108915E+10 | 3819.30 | 18-APR-15:09 | 27.75 | 20.46 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 8.22 | 5.15 | 0.202870E+10 | 4383.61 | 31-MAY-15:30 | 29.15 | 19.25 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.69 | 0.350725E+10 | 6376.04 | 29-JUN-15:00 | 30.00 | 20.53 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.94 | 0.430154E+10 | 6495.73 | 03-JUL-15:20 | 29.63 | 24.33 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 | 0.444120E+10 | 7806.56 | 04-AUG-15:50 | 33.90 | 26.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 | 0.304156E+10 | 5688.95 | 08-SEP-14:50 | 30.10 | 19.14 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 | 1.39 | 0.107618E+10 | 2157.17 | 02-OCT-15:39 | 17.17 | 14.05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.5 | 0.763502E+09 | 1690.79 | 03-NOV-14:50 | 16.10 | 9.74 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.3 | 0.636634E+09 | 831.62 | 02-DEC-15:50 | 5.68 | 3.15 |
Annual Sum or Average | 0.00 | 0.228938E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.596961E+09 | 780.74 | 2.20 | 0.51 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.444120E+10 | 7806.56 | 33.90 | 26.17 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139441E+11 | 27401.79 | 14-JAN-06:32 | -3.7 |
February | 0.106999E+11 | 27346.80 | 02-FEB-07:10 | -36.7 |
March | 0.894088E+10 | 26833.90 | 06-MAR-06:11 | -13.9 |
April | 0.498224E+10 | 26800.70 | 03-APR-05:11 | -7.2 |
May | 0.164777E+10 | 26522.43 | 02-MAY-05:22 | 2.20 |
June | 0.284793E+09 | 26304.11 | 05-JUN-05:01 | 9.32 |
July | 31059975.18 | 1170.12 | 31-JUL-06:10 | 18.17 |
August | 53264496.33 | 1286.53 | 07-AUG-06:20 | 9.43 |
September | 0.524492E+09 | 26325.23 | 29-SEP-05:01 | 0.92 |
October | 0.295642E+10 | 26477.58 | 24-OCT-05:12 | 2.07 |
November | 0.677685E+10 | 26791.37 | 24-NOV-06:11 | -13.5 |
December | 0.108881E+11 | 27874.56 | 15-DEC-06:31 | -13.5 |
Annual Sum or Average | 0.617299E+11 | |||
Minimum of Months | 31059975.18 | 1170.12 | -36.7 | |
Maximum of Months | 0.139441E+11 | 27874.56 | 18.17 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.548104E+11 | 71708.16 | 27-JAN-06:01 | -17.4 |
February | 0.384995E+11 | 70488.07 | 03-FEB-22:01 | -28.3 |
March | 0.265777E+11 | 69896.82 | 05-MAR-10:02 | -8.8 |
April | 0.116496E+11 | 69805.85 | 03-APR-00:22 | -5.8 |
May | 0.126161E+10 | 67950.27 | 02-MAY-05:11 | 2.20 |
June | 0.201790E+09 | 2703.54 | 09-JUN-12:00 | 28.30 |
July | 62429579.48 | 960.27 | 25-JUL-11:20 | 27.23 |
August | 70086418.16 | 810.77 | 21-AUG-12:20 | 27.03 |
September | 0.555753E+09 | 66791.11 | 30-SEP-05:01 | 0.10 |
October | 0.608976E+10 | 67945.61 | 17-OCT-05:01 | 0.77 |
November | 0.249247E+11 | 69949.07 | 21-NOV-05:22 | -9.2 |
December | 0.428156E+11 | 72184.07 | 09-DEC-06:01 | -22.8 |
Annual Sum or Average | 0.207519E+12 | |||
Minimum of Months | 62429579.48 | 810.77 | -28.3 | |
Maximum of Months | 0.548104E+11 | 72184.07 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265933E+12 | 240529.67 | 18-JAN-18:00 | -18.3 |
February | 0.180587E+12 | 232745.42 | 01-FEB-21:00 | -28.9 |
March | 0.993041E+11 | 171744.28 | 06-MAR-08:70 | -11.8 |
April | 0.231343E+11 | 100104.34 | 02-APR-24:00 | -5.6 |
May | 0.512840E+09 | 20263.09 | 02-MAY-03:00 | 2.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.366452E+10 | 26499.02 | 24-OCT-05:53 | 2.20 |
November | 0.102914E+12 | 164994.73 | 25-NOV-16:00 | -17.8 |
December | 0.204875E+12 | 241852.00 | 09-DEC-08:55 | -22.8 |
Annual Sum or Average | 0.880925E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.265933E+12 | 241852.00 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.694788E+09 | 762.98 | 02-JAN-16:40 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.613337E+09 | 744.42 | 11-FEB-16:00 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.673234E+09 | 720.92 | 01-MAR-16:00 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.625923E+09 | 723.91 | 10-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.617734E+09 | 668.93 | 25-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.599867E+09 | 707.76 | 13-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.588118E+09 | 708.67 | 20-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.633190E+09 | 693.00 | 31-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.621044E+09 | 724.39 | 21-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.645703E+09 | 740.88 | 21-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.673029E+09 | 762.98 | 06-NOV-16:00 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.731493E+09 | 762.98 | 01-DEC-16:30 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.771746E+10 | 0.291647E+11 | ||||
Minimum of Months | 0.588118E+09 | 668.93 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.731493E+09 | 762.98 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.368849E+10 | 3463.72 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.337993E+10 | 3463.72 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.391929E+10 | 3463.72 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.366257E+10 | 3463.72 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.380389E+10 | 3463.72 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.377797E+10 | 3463.72 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.368849E+10 | 3463.72 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.391929E+10 | 3463.72 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.366257E+10 | 3463.72 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.368849E+10 | 3463.72 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.354717E+10 | 3463.72 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.368849E+10 | 3463.72 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.444266E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.337993E+10 | 3463.72 | 0.00 | 0.00 | |
Maximum of Months | 0.391929E+10 | 3463.72 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.405341E+10 | 3755.17 | 02-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.366772E+10 | 3724.94 | 08-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.412903E+10 | 3684.41 | 13-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.382918E+10 | 3554.20 | 10-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.394631E+10 | 3512.58 | 04-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.390115E+10 | 3463.06 | 05-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.383448E+10 | 3501.54 | 20-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.406689E+10 | 3541.75 | 29-AUG-08:20 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.384840E+10 | 3603.35 | 21-SEP-08:30 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.396665E+10 | 3692.87 | 30-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.386426E+10 | 3755.45 | 29-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.411404E+10 | 3774.93 | 05-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.472215E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.366772E+10 | 3463.06 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.412903E+10 | 3774.93 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.694788E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819329E+10 |
February | 0.127628E+10 | 0.613337E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611612E+10 |
March | 0.149825E+10 | 0.673234E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1474687.25 | 0.502656E+10 |
April | 0.138726E+10 | 0.625923E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55735982.58 | 0.282810E+10 |
May | 0.144276E+10 | 0.617734E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40927960.98 | 0.134397E+10 |
June | 0.144276E+10 | 0.599867E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160735E+09 | 0.863462E+09 |
July | 0.138726E+10 | 0.588118E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102438E+09 | 0.634867E+09 |
August | 0.149825E+10 | 0.633190E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150054E+09 | 0.899428E+09 |
September | 0.138726E+10 | 0.621044E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90688736.77 | 0.149343E+10 |
October | 0.138726E+10 | 0.645703E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105040.72 | 0.255319E+10 |
November | 0.133177E+10 | 0.673029E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472823E+10 |
December | 0.138726E+10 | 0.731493E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673351E+10 |
Annual Sum or Average | 0.168137E+11 | 0.771746E+10 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602160E+09 | 0.414141E+11 |
Minimum of Months | 0.127628E+10 | 0.588118E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634867E+09 |
Maximum of Months | 0.149825E+10 | 0.731493E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160735E+09 | 0.819329E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309880E+11 |
February | 0.300332E+10 | 0.337993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226974E+11 |
March | 0.352563E+10 | 0.391929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19818904.83 | 0.176074E+11 |
April | 0.326447E+10 | 0.366257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434811E+09 | 0.910585E+10 |
May | 0.339505E+10 | 0.380389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226692E+09 | 0.361621E+10 |
June | 0.339505E+10 | 0.377797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426178E+09 | 0.300321E+10 |
July | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92824638.53 | 0.293252E+10 |
August | 0.352563E+10 | 0.391929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133611E+09 | 0.405200E+10 |
September | 0.326447E+10 | 0.366257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114821E+09 | 0.515999E+10 |
October | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21414359.55 | 0.774388E+10 |
November | 0.313390E+10 | 0.354717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176924E+11 |
December | 0.326447E+10 | 0.368849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257290E+11 |
Annual Sum or Average | 0.395654E+11 | 0.444266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147017E+10 | 0.150328E+12 |
Minimum of Months | 0.300332E+10 | 0.337993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293252E+10 |
Maximum of Months | 0.352563E+10 | 0.391929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434811E+09 | 0.309880E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.405341E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122213E+12 |
February | 0.690763E+10 | 0.366772E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849402E+11 |
March | 0.810895E+10 | 0.412903E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111093E+10 | 0.573072E+11 |
April | 0.750829E+10 | 0.382918E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460521E+10 | 0.270227E+11 |
May | 0.780862E+10 | 0.394631E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281280E+10 | 0.118959E+11 |
June | 0.780862E+10 | 0.390115E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180156E+10 | 0.134128E+11 |
July | 0.750829E+10 | 0.383448E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143003E+09 | 0.159467E+11 |
August | 0.810895E+10 | 0.406689E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187479E+09 | 0.193773E+11 |
September | 0.750829E+10 | 0.384840E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627177E+09 | 0.218981E+11 |
October | 0.750829E+10 | 0.396665E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116238E+10 | 0.201230E+11 |
November | 0.720796E+10 | 0.386426E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225747E+09 | 0.590835E+11 |
December | 0.750829E+10 | 0.411404E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957937E+11 |
Annual Sum or Average | 0.910005E+11 | 0.472215E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126763E+11 | 0.549014E+12 |
Minimum of Months | 0.690763E+10 | 0.366772E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118959E+11 |
Maximum of Months | 0.810895E+10 | 0.412903E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460521E+10 | 0.122213E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 762.98 | 02-JAN-16:40 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 18948.79 | 18-JAN-18:00 |
February | 1680.92 | 01-FEB-08:09 | 744.42 | 11-FEB-16:00 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 18862.85 | 02-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 720.92 | 01-MAR-16:00 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 143.12 | 19-MAR-14:00 | 14166.26 | 06-MAR-08:00 |
April | 1680.92 | 01-APR-07:10 | 723.91 | 10-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1101.38 | 15-APR-17:00 | 9781.05 | 03-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 668.93 | 25-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1371.96 | 31-MAY-17:00 | 6080.18 | 02-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 707.76 | 13-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2064.93 | 26-JUN-16:10 | 4359.53 | 02-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 708.67 | 20-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1820.85 | 25-JUL-16:10 | 2815.14 | 24-JUL-06:10 |
August | 1680.92 | 01-AUG-07:10 | 693.00 | 31-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2478.83 | 04-AUG-16:10 | 3879.86 | 07-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 724.39 | 21-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2050.45 | 06-SEP-16:10 | 6040.26 | 29-SEP-06:10 |
October | 1680.92 | 02-OCT-07:10 | 740.88 | 21-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 01-OCT-12:40 | 7354.91 | 24-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 762.98 | 06-NOV-16:00 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 11990.35 | 24-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 762.98 | 01-DEC-16:30 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 18266.32 | 08-DEC-17:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 668.93 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2815.14 | |||||
Maximum of Months | 1680.92 | 762.98 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2478.83 | 18948.79 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3463.72 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 51157.38 | 18-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 3463.72 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 33244.30 | 04-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 3463.72 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1303.89 | 19-MAR-16:00 | 32673.63 | 06-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 3463.72 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7616.17 | 15-APR-15:10 | 20410.76 | 25-APR-06:10 |
May | 3955.50 | 01-MAY-07:10 | 3463.72 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4165.67 | 05-MAY-15:10 | 8913.73 | 01-MAY-23:57 |
June | 3955.50 | 01-JUN-07:10 | 3463.72 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4765.04 | 11-JUN-15:00 | 7314.68 | 02-JUN-05:00 |
July | 3955.50 | 01-JUL-07:10 | 3463.72 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2374.13 | 25-JUL-16:00 | 4695.73 | 10-JUL-15:10 |
August | 3955.50 | 01-AUG-07:10 | 3463.72 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2967.56 | 04-AUG-16:15 | 5717.76 | 06-AUG-06:00 |
September | 3955.50 | 01-SEP-07:10 | 3463.72 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2596.91 | 06-SEP-15:40 | 7818.25 | 18-SEP-23:00 |
October | 3955.50 | 02-OCT-07:10 | 3463.72 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1557.82 | 20-OCT-15:10 | 13974.87 | 24-OCT-06:10 |
November | 3955.50 | 01-NOV-07:10 | 3463.72 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 29671.83 | 25-NOV-16:10 |
December | 3955.50 | 01-DEC-08:09 | 3463.72 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 54459.86 | 09-DEC-08:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4695.73 | ||||
Maximum of Months | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7616.17 | 54459.86 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 3755.17 | 02-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 164362.69 | 18-JAN-16:00 |
February | 9097.65 | 01-FEB-08:09 | 3724.94 | 08-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 117875.74 | 28-FEB-10:00 |
March | 9097.65 | 01-MAR-08:09 | 3684.41 | 13-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19938.07 | 25-MAR-15:00 | 107457.59 | 06-MAR-08:70 |
April | 9097.65 | 01-APR-07:10 | 3554.20 | 10-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44476.50 | 15-APR-15:00 | 51067.54 | 02-APR-24:00 |
May | 9097.65 | 01-MAY-07:10 | 3512.58 | 04-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29429.69 | 04-MAY-14:00 | 29748.48 | 13-MAY-12:55 |
June | 9097.65 | 01-JUN-07:10 | 3463.06 | 05-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21256.00 | 11-JUN-15:00 | 29414.58 | 02-JUN-08:00 |
July | 9097.65 | 01-JUL-07:10 | 3501.54 | 20-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5744.22 | 25-JUL-16:00 | 29389.96 | 10-JUL-14:00 |
August | 9097.65 | 01-AUG-07:10 | 3541.75 | 29-AUG-08:20 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4922.36 | 21-AUG-13:00 | 24866.85 | 06-AUG-06:00 |
September | 9097.65 | 01-SEP-07:10 | 3603.35 | 21-SEP-08:30 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10884.32 | 06-SEP-14:00 | 30689.36 | 18-SEP-16:00 |
October | 9097.65 | 02-OCT-07:10 | 3692.87 | 30-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17849.29 | 20-OCT-15:00 | 29689.25 | 24-OCT-07:10 |
November | 9097.65 | 01-NOV-07:10 | 3755.45 | 29-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10365.50 | 20-NOV-10:00 | 115821.36 | 25-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 3774.93 | 05-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 197034.37 | 09-DEC-08:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 3463.06 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24866.85 | |||||
Maximum of Months | 9097.65 | 3774.93 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 44476.50 | 197034.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 203.98 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.34 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 305.97 | 2819.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2469.43 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 305.97 | 2819.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2779.12 |
April | 2316.06 | 18-APR-15:10 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 746.75 | 0.00 |
May | 3215.30 | 31-MAY-15:50 | 1680.92 | 465.42 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 510.82 | 0.00 |
June | 14844.59 | 28-JUN-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.46 |
July | 17038.96 | 01-JUL-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.89 |
August | 14993.29 | 14-AUG-05:03 | 554.70 | 152.99 | 1651.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.32 |
September | 17329.62 | 08-SEP-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.58 |
October | 233.46 | 31-OCT-14:50 | 1680.92 | 482.26 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.36 |
November | 53.94 | 04-NOV-16:00 | 1680.92 | 501.28 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.57 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 203.98 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1314.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 152.99 | 1651.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17329.62 | 1680.92 | 501.28 | 2819.25 | 0.00 | 0.00 | 0.00 | 0.00 | 746.75 | 2779.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5409.84 | 12-JAN-14:35 | 7911.00 | 6927.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2820.46 |
February | 6888.41 | 21-FEB-13:55 | 7911.00 | 6927.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2668.40 |
March | 3920.73 | 27-MAR-14:10 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.58 |
April | 6029.23 | 22-APR-13:50 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737.28 |
May | 3841.54 | 02-MAY-10:10 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1799.85 |
June | 25042.76 | 30-JUN-17:20 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.65 | 0.00 |
July | 26882.21 | 05-JUL-17:12 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 |
August | 23600.07 | 03-AUG-17:20 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1595.41 | 0.00 |
September | 6344.56 | 08-SEP-15:10 | 3955.50 | 3056.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1509.83 | 0.00 |
October | 5150.05 | 23-OCT-10:00 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1382.40 |
November | 4211.97 | 04-NOV-09:00 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1297.37 |
December | 1950.21 | 02-DEC-15:30 | 3955.50 | 3463.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1502.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1950.21 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26882.21 | 7911.00 | 6927.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1595.41 | 2820.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 1792.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21104.27 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2689.44 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51792.97 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 2689.44 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53605.73 |
April | 0.00 | 01-APR-00:05 | 0.00 | 896.48 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9734.80 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 896.48 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5078.46 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6631.48 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6707.08 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7685.83 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9420.03 |
October | 0.00 | 01-OCT-00:05 | 0.00 | 896.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9288.41 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 448.24 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6443.15 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1792.96 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21685.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 448.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5078.46 | |
Maximum of Months | 0.00 | 0.00 | 2689.44 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53605.73 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.317851E+11 | 25993.72 | 18-JAN-16:00 | 0.417160E+12 | 391004.26 | 18-JAN-17:10 |
February | 0.281898E+11 | 23156.23 | 02-FEB-13:30 | 0.287874E+12 | 350839.20 | 01-FEB-21:30 |
March | 0.308125E+11 | 22749.92 | 01-MAR-15:50 | 0.171422E+12 | 289103.64 | 06-MAR-08:09 |
April | 0.272028E+11 | 22381.43 | 01-APR-12:39 | 0.527036E+11 | 172035.79 | 03-APR-00:30 |
May | 0.268726E+11 | 22173.75 | 31-MAY-14:00 | 0.373581E+10 | 58806.85 | 02-MAY-05:19 |
June | 0.273778E+11 | 29256.53 | 30-JUN-14:50 | 0.261704E+09 | 11943.32 | 05-JUN-05:10 |
July | 0.276427E+11 | 30364.03 | 03-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.294437E+11 | 32812.53 | 04-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.271919E+11 | 25498.17 | 08-SEP-14:09 | 0.136298E+10 | 32502.34 | 30-SEP-05:10 |
October | 0.279628E+11 | 21356.90 | 23-OCT-08:09 | 0.176821E+11 | 67319.26 | 24-OCT-05:00 |
November | 0.289852E+11 | 25710.64 | 25-NOV-16:49 | 0.168893E+12 | 270482.88 | 25-NOV-16:10 |
December | 0.316009E+11 | 25986.79 | 09-DEC-16:40 | 0.323344E+12 | 391004.26 | 08-DEC-17:10 |
Annual Sum or Average | 0.345068E+12 | 0.144444E+13 | ||||
Minimum of Months | 0.268726E+11 | 21356.90 | 0.00 | 0.00 | ||
Maximum of Months | 0.317851E+11 | 32812.53 | 0.417160E+12 | 391004.26 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.451076E+10 | 13530.32 | 29-JAN-12:30 | 0.00 | 0.00 |
February | 0.552877E+10 | 13916.64 | 24-FEB-12:30 | 0.00 | 0.00 |
March | 0.877826E+10 | 19103.51 | 16-MAR-12:30 | 0.00 | 0.00 |
April | 0.109917E+11 | 21002.45 | 25-APR-12:20 | 0.00 | 0.00 |
May | 0.130505E+11 | 20439.47 | 18-MAY-11:30 | 0.00 | 0.00 |
June | 0.140150E+11 | 20158.17 | 22-JUN-11:00 | 0.00 | 0.00 |
July | 0.144981E+11 | 19653.41 | 15-JUL-12:30 | 0.00 | 0.00 |
August | 0.122406E+11 | 19515.22 | 07-AUG-12:30 | 0.00 | 0.00 |
September | 0.945246E+10 | 17136.07 | 04-SEP-11:00 | 0.00 | 0.00 |
October | 0.668665E+10 | 13966.29 | 01-OCT-12:39 | 0.00 | 0.00 |
November | 0.403833E+10 | 11136.64 | 04-NOV-11:50 | 0.00 | 0.00 |
December | 0.301621E+10 | 9012.93 | 01-DEC-11:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106807E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.301621E+10 | 9012.93 | 0.00 | 0.00 | |
Maximum of Months | 0.144981E+11 | 21002.45 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [J] | |
January | 0.843668E+10 | 0.479383E+10 | 0.112984E+11 | 0.00 | 0.490312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235312E+10 | 0.00 |
February | 0.766099E+10 | 0.389230E+10 | 0.103734E+11 | 0.00 | 0.410373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215944E+10 | 0.00 |
March | 0.872156E+10 | 0.370384E+10 | 0.121089E+11 | 0.00 | 0.384322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243494E+10 | 0.00 |
April | 0.811767E+10 | 0.296387E+10 | 0.112578E+11 | 0.00 | 0.255879E+10 | 0.00 | 0.00 | 27771535.26 | 0.00 | 0.00 | 0.00 | 0.227694E+10 | 0.00 |
May | 0.836793E+10 | 0.258625E+10 | 0.117000E+11 | 0.00 | 0.186474E+10 | 0.00 | 0.00 | 56430309.86 | 0.00 | 0.00 | 0.00 | 0.229727E+10 | 0.00 |
June | 0.827899E+10 | 0.229949E+10 | 0.116594E+11 | 0.00 | 0.185514E+10 | 0.00 | 0.00 | 0.110350E+10 | 0.00 | 0.00 | 0.00 | 0.218136E+10 | 0.00 |
July | 0.811108E+10 | 0.244499E+10 | 0.112984E+11 | 0.00 | 0.178581E+10 | 0.00 | 0.00 | 0.185675E+10 | 0.00 | 0.00 | 0.00 | 0.214573E+10 | 0.00 |
August | 0.861937E+10 | 0.282916E+10 | 0.121016E+11 | 0.00 | 0.194815E+10 | 0.00 | 0.00 | 0.176287E+10 | 0.00 | 0.00 | 0.00 | 0.218259E+10 | 0.00 |
September | 0.813201E+10 | 0.330760E+10 | 0.112504E+11 | 0.00 | 0.174804E+10 | 0.00 | 0.00 | 0.658979E+09 | 0.00 | 0.00 | 0.00 | 0.209491E+10 | 0.00 |
October | 0.830084E+10 | 0.405888E+10 | 0.113057E+11 | 0.00 | 0.210867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218865E+10 | 0.00 |
November | 0.808446E+10 | 0.448126E+10 | 0.108562E+11 | 0.00 | 0.339567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216761E+10 | 0.00 |
December | 0.853402E+10 | 0.494534E+10 | 0.112984E+11 | 0.00 | 0.451769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230552E+10 | 0.00 |
Annual Sum or Average | 0.993656E+11 | 0.423068E+11 | 0.136508E+12 | 0.00 | 0.346328E+11 | 0.00 | 0.00 | 0.546630E+10 | 0.00 | 0.00 | 0.00 | 0.267881E+11 | 0.00 |
Minimum of Months | 0.766099E+10 | 0.229949E+10 | 0.103734E+11 | 0.00 | 0.174804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209491E+10 | 0.00 |
Maximum of Months | 0.872156E+10 | 0.494534E+10 | 0.121089E+11 | 0.00 | 0.490312E+10 | 0.00 | 0.00 | 0.185675E+10 | 0.00 | 0.00 | 0.00 | 0.243494E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.417160E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.287874E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.171422E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.527036E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.373581E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.261704E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.136298E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.176821E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.168893E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.323344E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144444E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.417160E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 7926.85 | 10-JAN-15:00 | 3768.97 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 3380.48 | 18-JAN-16:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 7860.48 | 08-FEB-09:09 | 3768.97 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 3380.48 | 02-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 7831.24 | 13-MAR-08:09 | 3768.97 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 3178.91 | 06-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 7716.43 | 10-APR-08:09 | 3768.97 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2830.11 | 03-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 7609.42 | 04-MAY-08:09 | 3421.91 | 01-MAY-19:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 2509.66 | 02-MAY-06:19 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 7604.34 | 05-JUN-08:09 | 3421.91 | 01-JUN-19:40 | 10035.17 | 01-JUN-07:10 | 0.00 | 4051.76 | 29-JUN-14:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 7651.61 | 20-JUL-08:09 | 3421.91 | 01-JUL-19:00 | 10035.17 | 01-JUL-07:10 | 0.00 | 4051.76 | 03-JUL-13:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 7646.64 | 29-AUG-08:20 | 3768.97 | 08-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 4308.84 | 04-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 7779.41 | 21-SEP-08:30 | 3768.97 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 1926.75 | 30-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 7843.07 | 30-OCT-08:09 | 3768.97 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2579.82 | 24-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 7938.63 | 27-NOV-15:00 | 3768.97 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 3187.49 | 25-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7988.46 | 12-DEC-15:00 | 3768.97 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 3380.48 | 08-DEC-16:49 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 7604.34 | 3421.91 | 10035.17 | 0.00 | 1926.75 | 0.00 | 0.00 | |||||
Maximum of Months | 7988.46 | 3768.97 | 10035.17 | 0.00 | 4308.84 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 2912.15 | 30-JAN-12:20 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 2938.59 | 17-FEB-12:50 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 2932.45 | 01-MAR-12:20 | 0.00 | 01-MAR-00:10 |
April | 1179.00 | 18-APR-15:09 | 0.00 | 0.00 | 0.00 | 2826.22 | 03-APR-11:39 | 0.00 | 01-APR-00:10 |
May | 1333.11 | 31-MAY-15:09 | 0.00 | 0.00 | 0.00 | 2637.09 | 01-MAY-11:50 | 0.00 | 01-MAY-00:10 |
June | 6231.03 | 30-JUN-15:09 | 0.00 | 0.00 | 0.00 | 2345.79 | 02-JUN-11:30 | 0.00 | 01-JUN-00:10 |
July | 7278.44 | 03-JUL-15:09 | 0.00 | 0.00 | 0.00 | 2029.72 | 05-JUL-11:00 | 0.00 | 01-JUL-00:10 |
August | 10378.84 | 04-AUG-15:39 | 0.00 | 0.00 | 0.00 | 1814.84 | 22-AUG-11:30 | 0.00 | 01-AUG-00:10 |
September | 4782.45 | 08-SEP-15:09 | 0.00 | 0.00 | 0.00 | 1965.77 | 28-SEP-11:00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 2225.52 | 28-OCT-11:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 2541.74 | 30-NOV-12:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 2766.48 | 29-DEC-12:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1814.84 | 0.00 | |||
Maximum of Months | 10378.84 | 0.00 | 0.00 | 0.00 | 2938.59 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 25993.72 | 18-JAN-16:00 | 7180.87 | 10035.17 | 3768.97 | 0.00 | 3380.48 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23156.23 | 02-FEB-13:30 | 7725.65 | 10035.17 | 0.00 | 0.00 | 2941.32 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22749.92 | 01-MAR-15:50 | 7643.05 | 10035.17 | 0.00 | 0.00 | 2601.05 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22381.43 | 01-APR-12:39 | 7459.82 | 10035.17 | 0.00 | 0.00 | 2525.40 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22173.75 | 31-MAY-14:00 | 7297.27 | 10035.17 | 0.00 | 0.00 | 1746.46 | 0.00 | 0.00 | 1272.75 | 0.00 |
June | 29256.53 | 30-JUN-14:50 | 7297.27 | 10035.17 | 0.00 | 0.00 | 4051.76 | 0.00 | 0.00 | 6089.15 | 0.00 |
July | 30364.03 | 03-JUL-14:00 | 7297.27 | 10035.17 | 0.00 | 0.00 | 4051.76 | 0.00 | 0.00 | 7198.27 | 0.00 |
August | 32812.53 | 04-AUG-15:30 | 6493.35 | 10035.17 | 0.00 | 0.00 | 4308.84 | 0.00 | 0.00 | 10371.16 | 0.00 |
September | 25498.17 | 08-SEP-14:09 | 7297.27 | 10035.17 | 0.00 | 0.00 | 1746.46 | 0.00 | 0.00 | 4650.89 | 0.00 |
October | 21356.90 | 23-OCT-08:09 | 7813.18 | 10035.17 | 0.00 | 0.00 | 1830.68 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25710.64 | 25-NOV-16:49 | 7180.87 | 10035.17 | 3768.97 | 0.00 | 3107.51 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25986.79 | 09-DEC-16:40 | 7180.87 | 10035.17 | 3768.97 | 0.00 | 3380.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 21356.90 | 6493.35 | 10035.17 | 0.00 | 0.00 | 1746.46 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32812.53 | 7813.18 | 10035.17 | 3768.97 | 0.00 | 4308.84 | 0.00 | 0.00 | 10371.16 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 391004.26 | 18-JAN-17:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 350839.20 | 01-FEB-21:30 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 289103.64 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 172035.79 | 03-APR-00:30 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 58806.85 | 02-MAY-05:19 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 11943.32 | 05-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 32502.34 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 67319.26 | 24-OCT-05:00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 270482.88 | 25-NOV-16:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 391004.26 | 08-DEC-17:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 391004.26 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 74.50 | 15.38 | 12.33 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
February | 47.17 | 15.62 | 9.17 | 16.21 | 0.00 | 16.21 | 0.00 | 16.21 |
March | 29.83 | 16.38 | 10.67 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
April | 14.33 | 17.56 | 8.50 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
May | 5.67 | 19.62 | 5.33 | 19.77 | 0.00 | 19.77 | 0.00 | 19.77 |
June | 0.33 | 20.28 | 0.33 | 20.28 | 0.33 | 21.69 | 0.33 | 22.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.60 | 0.33 | 24.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.52 | 0.50 | 24.52 |
September | 1.50 | 20.17 | 1.50 | 20.17 | 0.17 | 20.39 | 0.17 | 20.60 |
October | 8.17 | 19.87 | 8.17 | 19.87 | 0.00 | 19.87 | 0.00 | 19.87 |
November | 26.83 | 16.35 | 8.83 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
December | 37.00 | 15.81 | 9.33 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 |
Annual Sum or Average | 245.33 | 16.13 | 74.17 | 16.86 | 1.33 | 16.89 | 1.33 | 16.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.85 | 0.00 | 15.85 |
Maximum of Months | 74.50 | 20.28 | 12.33 | 20.28 | 0.50 | 24.60 | 0.50 | 24.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 125.50 | 13.93 | 5.67 | 13.93 | 0.00 | 13.93 | 0.00 | 13.93 |
February | 105.00 | 14.17 | 3.83 | 14.17 | 0.00 | 14.17 | 0.00 | 14.17 |
March | 88.17 | 14.43 | 4.67 | 14.42 | 0.00 | 14.42 | 0.00 | 14.42 |
April | 45.00 | 14.67 | 2.83 | 14.67 | 0.00 | 14.67 | 0.00 | 14.67 |
May | 4.50 | 14.86 | 0.83 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.30 | 0.00 | 27.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.00 | 27.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1.00 | 14.97 | 0.17 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
October | 19.33 | 14.91 | 2.00 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
November | 79.17 | 14.36 | 2.67 | 14.36 | 0.00 | 14.36 | 0.00 | 14.36 |
December | 124.83 | 14.16 | 6.50 | 14.15 | 0.00 | 14.15 | 0.00 | 14.15 |
Annual Sum or Average | 592.50 | 14.25 | 29.17 | 14.25 | 1.17 | 14.27 | 0.00 | 14.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 125.50 | 14.97 | 6.50 | 14.97 | 0.83 | 27.30 | 0.00 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 9.41 | 0.67 | 9.41 | 0.00 | 9.41 | 0.00 | 9.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17.50 | 8.46 | 10.50 | 8.35 | 0.00 | 8.35 | 0.00 | 8.35 |
Annual Sum or Average | 18.17 | 8.50 | 11.17 | 8.40 | 0.00 | 8.40 | 0.00 | 8.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.50 | 9.41 | 10.50 | 9.41 | 0.00 | 9.41 | 0.00 | 9.41 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.99 | 300.00 | 20.99 | 300.00 | 20.99 |
February | 276.00 | 21.03 | 276.00 | 21.03 | 276.00 | 21.03 |
March | 324.00 | 21.03 | 324.00 | 21.03 | 324.00 | 21.03 |
April | 300.00 | 21.28 | 275.33 | 21.22 | 275.33 | 21.21 |
May | 311.67 | 21.91 | 154.33 | 21.76 | 154.33 | 21.69 |
June | 215.83 | 23.09 | 133.33 | 23.22 | 80.83 | 23.21 |
July | 118.33 | 23.84 | 251.17 | 23.88 | 102.33 | 23.89 |
August | 135.67 | 23.83 | 250.50 | 23.88 | 109.33 | 23.88 |
September | 181.00 | 22.47 | 138.83 | 22.56 | 62.67 | 22.34 |
October | 300.00 | 21.21 | 268.50 | 21.15 | 268.50 | 21.13 |
November | 288.00 | 21.07 | 276.67 | 21.06 | 276.67 | 21.05 |
December | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
Annual Sum or Average | 3050.50 | 21.63 | 2948.67 | 21.68 | 2530.00 | 21.60 |
Minimum of Months | 118.33 | 20.99 | 133.33 | 20.99 | 62.67 | 20.99 |
Maximum of Months | 324.00 | 23.84 | 324.00 | 23.88 | 324.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.52 | 300.00 | 15.52 | 300.00 | 15.52 |
February | 276.00 | 15.54 | 276.00 | 15.54 | 276.00 | 15.54 |
March | 324.00 | 15.65 | 324.00 | 15.65 | 324.00 | 15.65 |
April | 300.00 | 16.61 | 291.50 | 16.54 | 291.50 | 16.51 |
May | 310.17 | 18.91 | 261.00 | 18.76 | 259.17 | 18.69 |
June | 246.50 | 22.87 | 228.83 | 23.27 | 172.50 | 23.25 |
July | 220.50 | 25.78 | 273.33 | 25.83 | 201.50 | 25.89 |
August | 200.50 | 25.30 | 275.83 | 25.59 | 164.67 | 25.64 |
September | 188.33 | 20.36 | 198.50 | 21.29 | 107.00 | 20.79 |
October | 300.00 | 16.43 | 300.00 | 16.43 | 300.00 | 16.43 |
November | 288.00 | 15.89 | 288.00 | 15.89 | 288.00 | 15.89 |
December | 300.00 | 15.52 | 300.00 | 15.52 | 300.00 | 15.52 |
Annual Sum or Average | 3254.00 | 18.21 | 3317.00 | 18.43 | 2984.33 | 18.25 |
Minimum of Months | 188.33 | 15.52 | 198.50 | 15.52 | 107.00 | 15.52 |
Maximum of Months | 324.00 | 25.78 | 324.00 | 25.83 | 324.00 | 25.89 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
February | 276.00 | 10.03 | 276.00 | 10.03 | 276.00 | 10.03 |
March | 324.00 | 10.45 | 324.00 | 10.45 | 324.00 | 10.45 |
April | 300.00 | 12.71 | 299.50 | 12.70 | 299.50 | 12.70 |
May | 308.67 | 17.36 | 298.50 | 17.29 | 298.50 | 17.27 |
June | 247.50 | 22.72 | 221.17 | 23.17 | 168.33 | 23.16 |
July | 213.50 | 27.00 | 284.17 | 26.85 | 203.50 | 26.95 |
August | 210.67 | 26.17 | 282.33 | 26.25 | 182.50 | 26.36 |
September | 207.83 | 20.31 | 201.33 | 20.91 | 128.83 | 20.48 |
October | 300.00 | 12.83 | 300.00 | 12.83 | 300.00 | 12.83 |
November | 288.00 | 11.02 | 288.00 | 11.02 | 288.00 | 11.02 |
December | 300.00 | 9.94 | 300.00 | 9.94 | 300.00 | 9.94 |
Annual Sum or Average | 3276.17 | 15.09 | 3375.00 | 15.36 | 3069.17 | 15.12 |
Minimum of Months | 207.83 | 9.94 | 201.33 | 9.94 | 128.83 | 9.94 |
Maximum of Months | 324.00 | 27.00 | 324.00 | 26.85 | 324.00 | 26.95 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.125295E+09 | 27771535.26 | 11.67 | 85889599.76 | 39404939.52 | 0.00 | 0.54 | 18-APR-15:10 | 0.00 | 01-APR-00:05 | 5485.69 | 18-APR-15:10 | 3813.68 | 18-APR-15:10 | 1672.01 | 18-APR-15:10 | 1179.00 | 18-APR-15:10 | 0.00 | 01-APR-00:05 |
May | 0.255188E+09 | 56430309.86 | 22.33 | 0.193785E+09 | 61403267.65 | 0.00 | 0.62 | 31-MAY-15:10 | 0.00 | 01-MAY-00:05 | 5983.50 | 31-MAY-15:10 | 4911.95 | 31-MAY-15:10 | 1273.16 | 30-MAY-14:20 | 1333.11 | 31-MAY-15:10 | 0.00 | 01-MAY-00:05 |
June | 0.313370E+10 | 0.649800E+09 | 162.15 | 0.227779E+10 | 0.855909E+09 | 0.00 | 1.00 | 26-JUN-05:03 | 0.00 | 01-JUN-00:10 | 21952.46 | 26-JUN-05:55 | 11095.23 | 27-JUN-05:51 | 11879.29 | 26-JUN-05:03 | 4268.22 | 26-JUN-05:55 | 0.00 | 01-JUN-00:10 |
July | 0.530185E+10 | 0.107156E+10 | 237.76 | 0.367187E+10 | 0.162998E+10 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 21434.56 | 27-JUL-05:03 | 11525.87 | 01-JUL-05:03 | 12381.10 | 27-JUL-05:03 | 4198.50 | 27-JUL-05:03 | 0.00 | 01-JUL-00:10 |
August | 0.538925E+10 | 0.110069E+10 | 242.83 | 0.376624E+10 | 0.162301E+10 | 0.00 | 1.00 | 02-AUG-05:03 | 0.00 | 01-AUG-00:10 | 23634.54 | 04-AUG-05:01 | 10025.20 | 05-AUG-05:03 | 15180.39 | 04-AUG-05:01 | 4465.56 | 04-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.205017E+10 | 0.435790E+09 | 113.48 | 0.177747E+10 | 0.272699E+09 | 0.00 | 1.00 | 08-SEP-05:03 | 0.00 | 01-SEP-00:10 | 20001.75 | 11-SEP-05:02 | 12728.40 | 11-SEP-05:25 | 9661.16 | 12-SEP-05:03 | 3983.33 | 11-SEP-05:02 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.162555E+11 | 0.334204E+10 | 790.22 | 0.117730E+11 | 0.448241E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.538925E+10 | 0.110069E+10 | 242.83 | 0.376624E+10 | 0.162998E+10 | 0.00 | 1.00 | 0.00 | 23634.54 | 12728.40 | 15180.39 | 4465.56 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 |
June | 0.180994E+10 | 0.453699E+09 | 47.93 | 0.115594E+10 | 0.654008E+09 | 0.00 | 1.00 | 25-JUN-14:15 | 0.00 | 01-JUN-00:10 | 45681.55 | 30-JUN-18:55 | 30523.48 | 30-JUN-18:55 | 15158.07 | 30-JUN-18:55 | 10265.52 | 30-JUN-18:55 | 0.00 | 01-JUN-00:10 |
July | 0.322332E+10 | 0.785193E+09 | 108.63 | 0.190491E+10 | 0.131840E+10 | 0.00 | 1.00 | 01-JUL-17:23 | 0.00 | 01-JUL-00:10 | 49718.37 | 06-JUL-18:55 | 32043.11 | 30-JUL-16:45 | 25856.77 | 06-JUL-18:55 | 10937.52 | 03-JUL-17:12 | 0.00 | 01-JUL-00:10 |
August | 0.270107E+10 | 0.662176E+09 | 87.99 | 0.154582E+10 | 0.115525E+10 | 0.00 | 1.00 | 03-AUG-17:20 | 0.00 | 01-AUG-00:10 | 48373.67 | 03-AUG-17:20 | 26063.19 | 03-AUG-17:20 | 22310.48 | 03-AUG-17:20 | 11192.59 | 03-AUG-17:20 | 0.00 | 01-AUG-00:10 |
September | 0.835577E+09 | 0.223189E+09 | 41.83 | 0.648247E+09 | 0.187330E+09 | 0.00 | 0.55 | 08-SEP-15:10 | 0.00 | 01-SEP-00:10 | 10848.40 | 08-SEP-15:10 | 8639.56 | 08-SEP-15:10 | 3021.71 | 11-SEP-15:10 | 2843.71 | 08-SEP-15:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.856991E+10 | 0.212426E+10 | 286.38 | 0.525492E+10 | 0.331499E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.322332E+10 | 0.785193E+09 | 108.63 | 0.190491E+10 | 0.131840E+10 | 0.00 | 1.00 | 0.00 | 49718.37 | 32043.11 | 25856.77 | 11192.59 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.15 | 26.83 | 39.31 | 32.99 | 213.46 | 0.00 | 0.00 | 0.00 |
February | 96.22 | 47.20 | 49.02 | 68.76 | 164.74 | 0.00 | 0.00 | 0.00 |
March | 115.53 | 43.04 | 72.49 | 100.53 | 98.00 | 0.00 | 0.00 | 0.00 |
April | 168.42 | 83.23 | 85.19 | 190.68 | 61.81 | 0.00 | 0.00 | 0.00 |
May | 168.88 | 67.47 | 101.41 | 213.35 | 33.14 | 0.00 | 0.00 | 0.00 |
June | 197.85 | 85.58 | 112.27 | 259.24 | 29.74 | 0.00 | 0.00 | 0.00 |
July | 212.89 | 101.17 | 111.71 | 279.31 | 33.08 | 0.00 | 0.00 | 0.00 |
August | 185.54 | 84.86 | 100.68 | 244.31 | 39.03 | 0.00 | 0.00 | 0.00 |
September | 150.56 | 71.38 | 79.18 | 184.70 | 58.01 | 0.00 | 0.00 | 0.00 |
October | 105.38 | 46.97 | 58.41 | 111.79 | 72.29 | 0.00 | 0.00 | 0.00 |
November | 63.04 | 23.41 | 39.62 | 45.34 | 122.73 | 0.00 | 0.00 | 0.00 |
December | 48.69 | 23.16 | 25.53 | 29.37 | 190.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.74 | 58.71 | 73.03 | 147.08 | 92.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.69 | 23.16 | 25.53 | 29.37 | 29.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 212.89 | 101.17 | 112.27 | 279.31 | 213.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.15 | 26.83 | 39.31 | 32.99 | 213.46 | 0.00 | 0.00 | 0.00 |
February | 96.22 | 47.20 | 49.02 | 68.76 | 164.74 | 0.00 | 0.00 | 0.00 |
March | 115.53 | 43.04 | 72.49 | 100.53 | 98.00 | 0.00 | 0.00 | 0.00 |
April | 168.42 | 83.23 | 85.19 | 190.68 | 61.81 | 0.00 | 0.00 | 0.00 |
May | 168.88 | 67.47 | 101.41 | 213.35 | 33.14 | 0.00 | 0.00 | 0.00 |
June | 197.85 | 85.58 | 112.27 | 259.24 | 29.74 | 0.00 | 0.00 | 0.00 |
July | 212.89 | 101.17 | 111.71 | 279.31 | 33.08 | 0.00 | 0.00 | 0.00 |
August | 185.54 | 84.86 | 100.68 | 244.31 | 39.03 | 0.00 | 0.00 | 0.00 |
September | 150.56 | 71.38 | 79.18 | 184.70 | 58.01 | 0.00 | 0.00 | 0.00 |
October | 105.38 | 46.97 | 58.41 | 111.79 | 72.29 | 0.00 | 0.00 | 0.00 |
November | 63.04 | 23.41 | 39.62 | 45.34 | 122.73 | 0.00 | 0.00 | 0.00 |
December | 48.69 | 23.16 | 25.53 | 29.37 | 190.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.74 | 58.71 | 73.03 | 147.08 | 92.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.69 | 23.16 | 25.53 | 29.37 | 29.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 212.89 | 101.17 | 112.27 | 279.31 | 213.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.10 | 0.00 | 18.10 | 0.18 | 136.02 | 0.00 | 0.00 | 0.00 |
February | 22.95 | 0.00 | 22.95 | 2.27 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 34.40 | 0.00 | 34.40 | 15.48 | 60.83 | 0.00 | 0.00 | 0.00 |
April | 39.80 | 0.27 | 39.53 | 29.67 | 36.71 | 0.00 | 0.00 | 0.00 |
May | 51.87 | 2.01 | 49.86 | 58.17 | 18.29 | 0.00 | 0.00 | 0.00 |
June | 60.48 | 5.46 | 55.02 | 74.49 | 16.52 | 0.00 | 0.00 | 0.00 |
July | 56.74 | 3.81 | 52.93 | 68.52 | 18.49 | 0.00 | 0.00 | 0.00 |
August | 47.69 | 0.99 | 46.70 | 56.94 | 21.92 | 0.00 | 0.00 | 0.00 |
September | 36.47 | 0.02 | 36.45 | 35.85 | 34.39 | 0.00 | 0.00 | 0.00 |
October | 27.09 | 0.00 | 27.09 | 17.89 | 43.69 | 0.00 | 0.00 | 0.00 |
November | 18.95 | 0.00 | 18.95 | 4.99 | 75.91 | 0.00 | 0.00 | 0.00 |
December | 12.29 | 0.00 | 12.29 | 0.08 | 118.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.64 | 1.05 | 34.59 | 30.54 | 57.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.29 | 0.00 | 12.29 | 0.08 | 16.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.48 | 5.46 | 55.02 | 74.49 | 136.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.10 | 0.00 | 18.10 | 0.18 | 136.03 | 0.00 | 0.00 | 0.00 |
February | 22.95 | 0.00 | 22.95 | 2.27 | 105.58 | 0.00 | 0.00 | 0.00 |
March | 34.40 | 0.00 | 34.40 | 15.48 | 60.83 | 0.00 | 0.00 | 0.00 |
April | 39.80 | 0.27 | 39.53 | 29.67 | 36.71 | 0.00 | 0.00 | 0.00 |
May | 51.86 | 2.01 | 49.86 | 58.16 | 18.29 | 0.00 | 0.00 | 0.00 |
June | 60.48 | 5.46 | 55.02 | 74.49 | 16.52 | 0.00 | 0.00 | 0.00 |
July | 56.74 | 3.81 | 52.93 | 68.52 | 18.49 | 0.00 | 0.00 | 0.00 |
August | 47.69 | 0.99 | 46.70 | 56.93 | 21.92 | 0.00 | 0.00 | 0.00 |
September | 36.47 | 0.02 | 36.45 | 35.85 | 34.39 | 0.00 | 0.00 | 0.00 |
October | 27.09 | 0.00 | 27.09 | 17.89 | 43.69 | 0.00 | 0.00 | 0.00 |
November | 18.95 | 0.00 | 18.95 | 4.99 | 75.91 | 0.00 | 0.00 | 0.00 |
December | 12.29 | 0.00 | 12.29 | 0.08 | 118.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.64 | 1.05 | 34.58 | 30.54 | 57.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.29 | 0.00 | 12.29 | 0.08 | 16.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.48 | 5.46 | 55.02 | 74.49 | 136.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.29 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.41 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.74 | 39.02 | 9.83 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 130.16 | 25.49 | 37.50 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 165.26 | 18.41 | 33.83 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 185.16 | 21.05 | 20.00 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 182.19 | 26.39 | 16.00 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.80 | 27.02 | 19.17 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.67 | 36.37 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.78 | 30.75 | 7.67 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.10 | 48.06 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 100.24 | 42.03 | 144.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 185.16 | 89.29 | 37.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.29 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.41 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.74 | 39.02 | 9.83 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 130.16 | 25.49 | 37.50 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 165.26 | 18.41 | 33.83 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 185.16 | 21.05 | 20.00 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 182.19 | 26.39 | 16.00 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.80 | 27.02 | 19.17 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.67 | 36.37 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.78 | 30.75 | 7.67 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.10 | 48.06 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 100.24 | 42.03 | 144.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 185.16 | 89.29 | 37.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.29 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.41 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.74 | 39.02 | 9.83 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 130.16 | 25.49 | 37.50 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 165.26 | 18.41 | 33.83 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 185.16 | 21.05 | 20.00 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 182.19 | 26.39 | 16.00 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.80 | 27.02 | 19.17 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.67 | 36.37 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.78 | 30.75 | 7.67 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.10 | 48.06 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 100.24 | 42.03 | 144.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 185.16 | 89.29 | 37.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.29 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.41 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.74 | 39.02 | 9.83 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 130.16 | 25.49 | 37.50 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 165.26 | 18.41 | 33.83 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 185.16 | 21.05 | 20.00 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 182.19 | 26.39 | 16.00 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.80 | 27.02 | 19.17 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.67 | 36.37 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.78 | 30.75 | 7.67 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.10 | 48.06 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 100.24 | 42.03 | 144.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 185.16 | 89.29 | 37.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.29 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.41 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.74 | 39.02 | 9.83 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 130.16 | 25.49 | 37.50 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 165.26 | 18.41 | 33.83 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 185.16 | 21.05 | 20.00 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 182.19 | 26.39 | 16.00 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.80 | 27.02 | 19.17 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.67 | 36.37 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.78 | 30.75 | 7.67 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.10 | 48.06 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 100.24 | 42.03 | 144.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 185.16 | 89.29 | 37.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.29 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.41 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.74 | 39.02 | 9.83 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 130.16 | 25.49 | 37.50 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 165.26 | 18.41 | 33.83 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 185.16 | 21.05 | 20.00 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 182.19 | 26.39 | 16.00 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.80 | 27.02 | 19.17 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.67 | 36.37 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.78 | 30.75 | 7.67 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.10 | 48.06 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 100.24 | 42.03 | 144.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 185.16 | 89.29 | 37.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.29 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.41 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.74 | 39.02 | 9.83 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 130.16 | 25.49 | 37.50 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 165.26 | 18.41 | 33.83 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 185.16 | 21.05 | 20.00 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 182.19 | 26.39 | 16.00 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.80 | 27.02 | 19.17 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.67 | 36.37 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.78 | 30.75 | 7.67 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.10 | 48.06 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 100.24 | 42.03 | 144.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 185.16 | 89.29 | 37.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.29 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.41 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.74 | 39.02 | 9.83 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 130.16 | 25.49 | 37.50 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 165.26 | 18.41 | 33.83 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 185.16 | 21.05 | 20.00 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 182.19 | 26.39 | 16.00 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.80 | 27.02 | 19.17 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.67 | 36.37 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.78 | 30.75 | 7.67 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.10 | 48.06 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 100.24 | 42.03 | 144.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 185.16 | 89.29 | 37.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.29 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.41 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.74 | 39.02 | 9.83 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 130.16 | 25.49 | 37.50 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 165.26 | 18.41 | 33.83 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 185.16 | 21.05 | 20.00 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 182.19 | 26.39 | 16.00 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.80 | 27.02 | 19.17 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.67 | 36.37 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.78 | 30.75 | 7.67 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.10 | 48.06 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 100.24 | 42.03 | 144.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 185.16 | 89.29 | 37.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.08 | 15.15 | 19.94 | 20.90 | 89.29 | 0.00 | 0.00 | 0.00 |
February | 48.20 | 24.01 | 24.19 | 40.95 | 68.41 | 0.00 | 0.00 | 0.00 |
March | 76.09 | 36.43 | 39.66 | 86.74 | 39.02 | 9.83 | 0.00 | 0.00 |
April | 103.40 | 62.21 | 41.19 | 130.16 | 25.49 | 37.50 | 0.00 | 0.00 |
May | 124.24 | 69.91 | 54.33 | 165.26 | 18.41 | 33.83 | 0.00 | 0.00 |
June | 141.27 | 82.72 | 58.55 | 185.16 | 21.05 | 20.00 | 0.00 | 0.00 |
July | 142.36 | 87.68 | 54.68 | 182.19 | 26.39 | 16.00 | 0.00 | 0.00 |
August | 118.53 | 67.57 | 50.95 | 153.80 | 27.02 | 19.17 | 0.00 | 0.00 |
September | 92.05 | 53.47 | 38.58 | 114.67 | 36.37 | 0.00 | 0.00 | 0.00 |
October | 58.33 | 28.87 | 29.46 | 71.78 | 30.75 | 7.67 | 0.00 | 0.00 |
November | 34.71 | 12.75 | 21.95 | 33.10 | 48.06 | 0.00 | 0.00 | 0.00 |
December | 23.74 | 11.54 | 12.19 | 14.42 | 75.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.35 | 46.13 | 37.22 | 100.24 | 42.03 | 144.00 | 0.00 | 0.00 |
Minimum of Months | 23.74 | 11.54 | 12.19 | 14.42 | 18.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 142.36 | 87.68 | 58.55 | 185.16 | 89.29 | 37.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177164E+09 | 71868735.54 | 0.105295E+09 | 88372084.88 | 0.571731E+09 |
February | 0.232773E+09 | 0.114177E+09 | 0.118596E+09 | 0.166333E+09 | 0.398547E+09 |
March | 0.309440E+09 | 0.115273E+09 | 0.194167E+09 | 0.269248E+09 | 0.262471E+09 |
April | 0.436545E+09 | 0.215723E+09 | 0.220821E+09 | 0.494253E+09 | 0.160201E+09 |
May | 0.452321E+09 | 0.180716E+09 | 0.271605E+09 | 0.571428E+09 | 88751244.06 |
June | 0.512839E+09 | 0.221835E+09 | 0.291004E+09 | 0.671941E+09 | 77087349.04 |
July | 0.570193E+09 | 0.270977E+09 | 0.299216E+09 | 0.748094E+09 | 88594211.35 |
August | 0.496950E+09 | 0.227280E+09 | 0.269670E+09 | 0.654361E+09 | 0.104525E+09 |
September | 0.390252E+09 | 0.185011E+09 | 0.205242E+09 | 0.478749E+09 | 0.150368E+09 |
October | 0.282254E+09 | 0.125817E+09 | 0.156437E+09 | 0.299421E+09 | 0.193612E+09 |
November | 0.163395E+09 | 60689328.10 | 0.102706E+09 | 0.117513E+09 | 0.318113E+09 |
December | 0.130405E+09 | 62020230.89 | 68384856.96 | 78653130.34 | 0.510825E+09 |
Annual Sum or Average | 0.415453E+10 | 0.185139E+10 | 0.230314E+10 | 0.463836E+10 | 0.292483E+10 |
Minimum of Months | 0.130405E+09 | 60689328.10 | 68384856.96 | 78653130.34 | 77087349.04 |
Maximum of Months | 0.570193E+09 | 0.270977E+09 | 0.299216E+09 | 0.748094E+09 | 0.571731E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177164E+09 | 71868735.54 | 0.105295E+09 | 88372084.88 | 0.571731E+09 |
February | 0.232773E+09 | 0.114177E+09 | 0.118596E+09 | 0.166333E+09 | 0.398547E+09 |
March | 0.309440E+09 | 0.115273E+09 | 0.194167E+09 | 0.269248E+09 | 0.262471E+09 |
April | 0.436545E+09 | 0.215723E+09 | 0.220821E+09 | 0.494253E+09 | 0.160201E+09 |
May | 0.452321E+09 | 0.180716E+09 | 0.271605E+09 | 0.571428E+09 | 88751244.06 |
June | 0.512839E+09 | 0.221835E+09 | 0.291004E+09 | 0.671941E+09 | 77087349.04 |
July | 0.570193E+09 | 0.270977E+09 | 0.299216E+09 | 0.748094E+09 | 88594211.35 |
August | 0.496950E+09 | 0.227280E+09 | 0.269670E+09 | 0.654361E+09 | 0.104525E+09 |
September | 0.390252E+09 | 0.185011E+09 | 0.205242E+09 | 0.478749E+09 | 0.150368E+09 |
October | 0.282254E+09 | 0.125817E+09 | 0.156437E+09 | 0.299421E+09 | 0.193612E+09 |
November | 0.163395E+09 | 60689328.10 | 0.102706E+09 | 0.117513E+09 | 0.318113E+09 |
December | 0.130405E+09 | 62020230.89 | 68384856.96 | 78653130.34 | 0.510825E+09 |
Annual Sum or Average | 0.415453E+10 | 0.185139E+10 | 0.230314E+10 | 0.463836E+10 | 0.292483E+10 |
Minimum of Months | 0.130405E+09 | 60689328.10 | 68384856.96 | 78653130.34 | 77087349.04 |
Maximum of Months | 0.570193E+09 | 0.270977E+09 | 0.299216E+09 | 0.748094E+09 | 0.571731E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48488126.83 | 0.00 | 48488126.83 | 485336.01 | 0.364329E+09 |
February | 55524446.54 | 0.00 | 55524446.54 | 5495633.23 | 0.255422E+09 |
March | 92146307.37 | 2499.55 | 92143807.82 | 41469462.90 | 0.162915E+09 |
April | 0.103167E+09 | 702085.40 | 0.102464E+09 | 76908336.49 | 95157899.28 |
May | 0.138917E+09 | 5379542.38 | 0.133537E+09 | 0.155794E+09 | 48991522.63 |
June | 0.156769E+09 | 14161738.08 | 0.142608E+09 | 0.193072E+09 | 42830871.92 |
July | 0.151972E+09 | 10196569.90 | 0.141776E+09 | 0.183526E+09 | 49512778.09 |
August | 0.127740E+09 | 2661251.59 | 0.125078E+09 | 0.152495E+09 | 58706683.06 |
September | 94536431.71 | 63161.34 | 94473270.37 | 92927560.01 | 89127413.11 |
October | 72562893.63 | 0.00 | 72562893.63 | 47929599.77 | 0.117008E+09 |
November | 49121072.59 | 0.00 | 49121072.59 | 12932306.65 | 0.196749E+09 |
December | 32924996.33 | 0.00 | 32924996.33 | 221695.22 | 0.317429E+09 |
Annual Sum or Average | 0.112387E+10 | 33166848.24 | 0.109070E+10 | 0.963257E+09 | 0.179818E+10 |
Minimum of Months | 32924996.33 | 0.00 | 32924996.33 | 221695.22 | 42830871.92 |
Maximum of Months | 0.156769E+09 | 14161738.08 | 0.142608E+09 | 0.193072E+09 | 0.364329E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48486565.90 | 0.00 | 48486565.90 | 485214.00 | 0.364330E+09 |
February | 55522718.22 | 0.00 | 55522718.22 | 5495013.17 | 0.255423E+09 |
March | 92143381.60 | 2499.43 | 92140882.17 | 41466723.40 | 0.162915E+09 |
April | 0.103164E+09 | 702052.49 | 0.102461E+09 | 76905352.54 | 95158156.79 |
May | 0.138913E+09 | 5379290.24 | 0.133533E+09 | 0.155788E+09 | 48991172.98 |
June | 0.156765E+09 | 14161074.30 | 0.142603E+09 | 0.193066E+09 | 42830474.64 |
July | 0.151968E+09 | 10196091.97 | 0.141771E+09 | 0.183520E+09 | 49512258.73 |
August | 0.127736E+09 | 2661126.85 | 0.125075E+09 | 0.152490E+09 | 58706268.81 |
September | 94533632.71 | 63158.38 | 94470474.33 | 92924456.07 | 89126872.67 |
October | 72560611.18 | 0.00 | 72560611.18 | 47927186.69 | 0.117007E+09 |
November | 49119433.09 | 0.00 | 49119433.09 | 12931324.99 | 0.196749E+09 |
December | 32923954.99 | 0.00 | 32923954.99 | 221640.09 | 0.317430E+09 |
Annual Sum or Average | 0.112383E+10 | 33165293.66 | 0.109067E+10 | 0.963221E+09 | 0.179818E+10 |
Minimum of Months | 32923954.99 | 0.00 | 32923954.99 | 221640.09 | 42830474.64 |
Maximum of Months | 0.156765E+09 | 14161074.30 | 0.142603E+09 | 0.193066E+09 | 0.364330E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55973349.37 | 0.239146E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99062062.87 | 0.165488E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232325E+09 | 0.104508E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.337377E+09 | 66081689.67 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.442621E+09 | 49313189.72 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.479928E+09 | 54554353.76 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.487972E+09 | 70678599.95 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.411932E+09 | 72357479.70 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.297236E+09 | 94282478.01 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.192265E+09 | 82356436.80 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85807808.51 | 0.124573E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 0.202000E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.316111E+10 | 0.132534E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 49313189.72 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.487972E+09 | 0.239146E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55973349.37 | 0.239146E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99062062.87 | 0.165488E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232325E+09 | 0.104508E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.337377E+09 | 66081689.67 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.442621E+09 | 49313189.72 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.479928E+09 | 54554353.76 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.487972E+09 | 70678599.95 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.411932E+09 | 72357479.70 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.297236E+09 | 94282478.01 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.192265E+09 | 82356436.80 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85807808.51 | 0.124573E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 0.202000E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.316111E+10 | 0.132534E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 49313189.72 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.487972E+09 | 0.239146E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55973349.37 | 0.239146E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99062062.87 | 0.165488E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232325E+09 | 0.104508E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.337377E+09 | 66081689.67 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.442621E+09 | 49313189.72 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.479928E+09 | 54554353.76 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.487972E+09 | 70678599.95 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.411932E+09 | 72357479.70 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.297236E+09 | 94282478.01 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.192265E+09 | 82356436.80 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85807808.51 | 0.124573E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 0.202000E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.316111E+10 | 0.132534E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 49313189.72 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.487972E+09 | 0.239146E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55973349.37 | 0.239146E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99062062.87 | 0.165488E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232325E+09 | 0.104508E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.337377E+09 | 66081689.67 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.442621E+09 | 49313189.72 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.479928E+09 | 54554353.76 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.487972E+09 | 70678599.95 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.411932E+09 | 72357479.70 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.297236E+09 | 94282478.01 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.192265E+09 | 82356436.80 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85807808.51 | 0.124573E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 0.202000E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.316111E+10 | 0.132534E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 49313189.72 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.487972E+09 | 0.239146E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55973349.37 | 0.239146E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99062062.87 | 0.165488E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232325E+09 | 0.104508E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.337377E+09 | 66081689.67 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.442621E+09 | 49313189.72 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.479928E+09 | 54554353.76 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.487972E+09 | 70678599.95 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.411932E+09 | 72357479.70 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.297236E+09 | 94282478.01 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.192265E+09 | 82356436.80 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85807808.51 | 0.124573E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 0.202000E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.316111E+10 | 0.132534E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 49313189.72 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.487972E+09 | 0.239146E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55973349.37 | 0.239146E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99062062.87 | 0.165488E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232325E+09 | 0.104508E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.337377E+09 | 66081689.67 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.442621E+09 | 49313189.72 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.479928E+09 | 54554353.76 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.487972E+09 | 70678599.95 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.411932E+09 | 72357479.70 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.297236E+09 | 94282478.01 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.192265E+09 | 82356436.80 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85807808.51 | 0.124573E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 0.202000E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.316111E+10 | 0.132534E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 49313189.72 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.487972E+09 | 0.239146E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55973349.37 | 0.239146E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99062062.87 | 0.165488E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232325E+09 | 0.104508E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.337377E+09 | 66081689.67 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.442621E+09 | 49313189.72 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.479928E+09 | 54554353.76 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.487972E+09 | 70678599.95 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.411932E+09 | 72357479.70 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.297236E+09 | 94282478.01 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.192265E+09 | 82356436.80 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85807808.51 | 0.124573E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 0.202000E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.316111E+10 | 0.132534E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 49313189.72 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.487972E+09 | 0.239146E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55973349.37 | 0.239146E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99062062.87 | 0.165488E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232325E+09 | 0.104508E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.337377E+09 | 66081689.67 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.442621E+09 | 49313189.72 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.479928E+09 | 54554353.76 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.487972E+09 | 70678599.95 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.411932E+09 | 72357479.70 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.297236E+09 | 94282478.01 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.192265E+09 | 82356436.80 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85807808.51 | 0.124573E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 0.202000E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.316111E+10 | 0.132534E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 49313189.72 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.487972E+09 | 0.239146E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55973349.37 | 0.239146E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99062062.87 | 0.165488E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232325E+09 | 0.104508E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.337377E+09 | 66081689.67 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.442621E+09 | 49313189.72 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.479928E+09 | 54554353.76 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.487972E+09 | 70678599.95 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.411932E+09 | 72357479.70 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.297236E+09 | 94282478.01 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.192265E+09 | 82356436.80 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85807808.51 | 0.124573E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 0.202000E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.316111E+10 | 0.132534E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 49313189.72 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.487972E+09 | 0.239146E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93966471.70 | 40570756.49 | 53395715.21 | 55973349.37 | 0.239146E+09 |
February | 0.116617E+09 | 58085951.96 | 58531160.69 | 99062062.87 | 0.165488E+09 |
March | 0.203786E+09 | 97567371.78 | 0.106219E+09 | 0.232325E+09 | 0.104508E+09 |
April | 0.268014E+09 | 0.161239E+09 | 0.106775E+09 | 0.337377E+09 | 66081689.67 |
May | 0.332776E+09 | 0.187250E+09 | 0.145526E+09 | 0.442621E+09 | 49313189.72 |
June | 0.366161E+09 | 0.214410E+09 | 0.151751E+09 | 0.479928E+09 | 54554353.76 |
July | 0.381296E+09 | 0.234830E+09 | 0.146465E+09 | 0.487972E+09 | 70678599.95 |
August | 0.317469E+09 | 0.180993E+09 | 0.136476E+09 | 0.411932E+09 | 72357479.70 |
September | 0.238604E+09 | 0.138603E+09 | 0.100001E+09 | 0.297236E+09 | 94282478.01 |
October | 0.156236E+09 | 77319406.69 | 78916576.83 | 0.192265E+09 | 82356436.80 |
November | 89960587.24 | 33053317.93 | 56907269.31 | 85807808.51 | 0.124573E+09 |
December | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 0.202000E+09 |
Annual Sum or Average | 0.262847E+10 | 0.145484E+10 | 0.117363E+10 | 0.316111E+10 | 0.132534E+10 |
Minimum of Months | 63580839.28 | 30920305.10 | 32660534.18 | 38615541.54 | 49313189.72 |
Maximum of Months | 0.381296E+09 | 0.234830E+09 | 0.151751E+09 | 0.487972E+09 | 0.239146E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 51.01 | 683.63 | 168.50 | 53.67 | 114.83 | 0.00 | 0.00 |
February | 126.16 | 524.75 | 238.34 | 94.39 | 143.95 | 0.00 | 0.00 |
March | 226.55 | 312.17 | 299.87 | 86.08 | 213.79 | 0.00 | 0.00 |
April | 439.14 | 195.47 | 416.44 | 166.99 | 249.45 | 0.00 | 0.00 |
May | 541.59 | 101.41 | 441.48 | 138.96 | 302.52 | 0.00 | 0.00 |
June | 665.50 | 90.58 | 516.67 | 182.10 | 334.57 | 0.00 | 0.00 |
July | 694.25 | 101.73 | 539.25 | 209.96 | 329.29 | 0.00 | 0.00 |
August | 601.85 | 121.25 | 466.46 | 171.70 | 294.76 | 0.00 | 0.00 |
September | 439.86 | 183.55 | 374.06 | 142.80 | 231.26 | 0.00 | 0.00 |
October | 256.84 | 229.41 | 264.95 | 93.95 | 171.00 | 0.00 | 0.00 |
November | 94.65 | 391.27 | 163.98 | 46.83 | 117.15 | 0.00 | 0.00 |
December | 48.16 | 607.73 | 121.96 | 46.31 | 75.65 | 0.00 | 0.00 |
Annual Sum or Average | 349.96 | 294.24 | 334.75 | 119.52 | 215.24 | 0.00 | 0.00 |
Minimum of Months | 48.16 | 90.58 | 121.96 | 46.31 | 75.65 | 0.00 | 0.00 |
Maximum of Months | 694.25 | 683.63 | 539.25 | 209.96 | 334.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1295.96 | 8548.01 | 350.83 | 151.47 | 199.36 | 0.00 | 0.00 |
February | 2193.15 | 6153.21 | 482.05 | 240.10 | 241.94 | 0.00 | 0.00 |
March | 4185.66 | 3126.44 | 760.85 | 364.27 | 396.58 | 0.00 | 0.00 |
April | 5357.81 | 1565.36 | 1034.01 | 622.06 | 411.94 | 0.00 | 0.00 |
May | 6379.86 | 644.44 | 1242.44 | 699.11 | 543.33 | 0.00 | 0.00 |
June | 7204.88 | 641.08 | 1412.66 | 827.20 | 585.46 | 0.00 | 0.00 |
July | 6923.24 | 810.28 | 1423.59 | 876.76 | 546.84 | 0.00 | 0.00 |
August | 5842.50 | 822.66 | 1185.29 | 675.75 | 509.54 | 0.00 | 0.00 |
September | 4398.88 | 1212.54 | 920.54 | 534.73 | 385.81 | 0.00 | 0.00 |
October | 2831.73 | 1600.62 | 583.32 | 288.68 | 294.64 | 0.00 | 0.00 |
November | 1534.81 | 3881.86 | 347.07 | 127.52 | 219.55 | 0.00 | 0.00 |
December | 783.01 | 6177.65 | 237.38 | 115.44 | 121.94 | 0.00 | 0.00 |
Annual Sum or Average | 4087.13 | 2917.67 | 833.48 | 461.33 | 372.15 | 0.00 | 0.00 |
Minimum of Months | 783.01 | 641.08 | 237.38 | 115.44 | 121.94 | 0.00 | 0.00 |
Maximum of Months | 7204.88 | 8548.01 | 1423.59 | 876.76 | 585.46 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136638E+09 | 0.183104E+10 | 0.451302E+09 | 0.143737E+09 | 0.307564E+09 | 0.00 | 0.00 |
February | 0.305203E+09 | 0.126949E+10 | 0.576593E+09 | 0.228354E+09 | 0.348239E+09 | 0.00 | 0.00 |
March | 0.606779E+09 | 0.836120E+09 | 0.803169E+09 | 0.230550E+09 | 0.572619E+09 | 0.00 | 0.00 |
April | 0.113825E+10 | 0.506649E+09 | 0.107942E+10 | 0.432851E+09 | 0.646569E+09 | 0.00 | 0.00 |
May | 0.145058E+10 | 0.271630E+09 | 0.118247E+10 | 0.372190E+09 | 0.810281E+09 | 0.00 | 0.00 |
June | 0.172497E+10 | 0.234785E+09 | 0.133921E+10 | 0.471994E+09 | 0.867218E+09 | 0.00 | 0.00 |
July | 0.185948E+10 | 0.272462E+09 | 0.144433E+10 | 0.562347E+09 | 0.881979E+09 | 0.00 | 0.00 |
August | 0.161199E+10 | 0.324749E+09 | 0.124937E+10 | 0.459882E+09 | 0.789492E+09 | 0.00 | 0.00 |
September | 0.114012E+10 | 0.475761E+09 | 0.969575E+09 | 0.370148E+09 | 0.599427E+09 | 0.00 | 0.00 |
October | 0.687917E+09 | 0.614456E+09 | 0.709632E+09 | 0.251634E+09 | 0.457997E+09 | 0.00 | 0.00 |
November | 0.245326E+09 | 0.101416E+10 | 0.425030E+09 | 0.121379E+09 | 0.303652E+09 | 0.00 | 0.00 |
December | 0.128993E+09 | 0.162775E+10 | 0.326659E+09 | 0.124040E+09 | 0.202619E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110363E+11 | 0.927906E+10 | 0.105568E+11 | 0.376911E+10 | 0.678766E+10 | 0.00 | 0.00 |
Minimum of Months | 0.128993E+09 | 0.234785E+09 | 0.326659E+09 | 0.121379E+09 | 0.202619E+09 | 0.00 | 0.00 |
Maximum of Months | 0.185948E+10 | 0.183104E+10 | 0.144433E+10 | 0.562347E+09 | 0.881979E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.347110E+10 | 0.228950E+11 | 0.939665E+09 | 0.405708E+09 | 0.533957E+09 | 0.00 | 0.00 |
February | 0.530566E+10 | 0.148858E+11 | 0.116617E+10 | 0.580860E+09 | 0.585312E+09 | 0.00 | 0.00 |
March | 0.112109E+11 | 0.837387E+10 | 0.203786E+10 | 0.975674E+09 | 0.106219E+10 | 0.00 | 0.00 |
April | 0.138874E+11 | 0.405741E+10 | 0.268014E+10 | 0.161239E+10 | 0.106775E+10 | 0.00 | 0.00 |
May | 0.170878E+11 | 0.172607E+10 | 0.332776E+10 | 0.187250E+10 | 0.145526E+10 | 0.00 | 0.00 |
June | 0.186750E+11 | 0.166168E+10 | 0.366161E+10 | 0.214410E+10 | 0.151751E+10 | 0.00 | 0.00 |
July | 0.185432E+11 | 0.217025E+10 | 0.381296E+10 | 0.234830E+10 | 0.146465E+10 | 0.00 | 0.00 |
August | 0.156486E+11 | 0.220340E+10 | 0.317469E+10 | 0.180993E+10 | 0.136476E+10 | 0.00 | 0.00 |
September | 0.114019E+11 | 0.314291E+10 | 0.238604E+10 | 0.138603E+10 | 0.100001E+10 | 0.00 | 0.00 |
October | 0.758452E+10 | 0.428710E+10 | 0.156236E+10 | 0.773194E+09 | 0.789166E+09 | 0.00 | 0.00 |
November | 0.397822E+10 | 0.100618E+11 | 0.899606E+09 | 0.330533E+09 | 0.569073E+09 | 0.00 | 0.00 |
December | 0.209722E+10 | 0.165462E+11 | 0.635808E+09 | 0.309203E+09 | 0.326605E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.128892E+12 | 0.920115E+11 | 0.262847E+11 | 0.145484E+11 | 0.117363E+11 | 0.00 | 0.00 |
Minimum of Months | 0.209722E+10 | 0.166168E+10 | 0.635808E+09 | 0.309203E+09 | 0.326605E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186750E+11 | 0.228950E+11 | 0.381296E+10 | 0.234830E+10 | 0.151751E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.106535E+10 | -977156615.9 | 0.00 | 0.00 | 744.00 | 0.00 | -88190046.0 | 58.99 | 0.00 | 0.00 |
February | 0.995149E+09 | -915648298.2 | 0.00 | 0.00 | 672.00 | 0.00 | -79500992.1 | 58.99 | 0.00 | 0.00 |
March | 0.114696E+10 | -0.105947E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -87495677.8 | 58.99 | 0.00 | 0.00 |
April | 0.102981E+10 | -946398308.2 | 0.00 | 0.00 | 720.00 | 0.00 | -83409197.5 | 58.99 | 0.00 | 0.00 |
May | 0.100905E+10 | -926226869.6 | 0.00 | 0.00 | 744.00 | 0.00 | -82820907.4 | 58.99 | 0.00 | 0.00 |
June | 0.934485E+09 | -860527437.7 | 0.00 | 0.00 | 720.00 | 0.00 | -73957572.3 | 58.99 | 0.00 | 0.00 |
July | 0.857700E+09 | -784692900.0 | 0.00 | 0.00 | 744.00 | 0.00 | -73007233.0 | 58.99 | 0.00 | 0.00 |
August | 0.894163E+09 | -820496708.5 | 0.00 | 0.00 | 744.00 | 0.00 | -73666679.8 | 58.99 | 0.00 | 0.00 |
September | 0.847840E+09 | -773205936.6 | 0.00 | 0.00 | 720.00 | 0.00 | -74634285.8 | 59.00 | 0.00 | 0.00 |
October | 0.900245E+09 | -814143998.5 | 0.00 | 0.00 | 744.00 | 0.00 | -86100603.9 | 58.99 | 0.00 | 0.00 |
November | 0.920533E+09 | -835945893.5 | 0.00 | 0.00 | 720.00 | 0.00 | -84587294.1 | 58.99 | 0.00 | 0.00 |
December | 0.101726E+10 | -929159799.8 | 0.00 | 0.00 | 744.00 | 0.00 | -88104296.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.116185E+11 | -0.106431E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -975474786.3 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.847840E+09 | -0.105947E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -88190046.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.114696E+10 | -773205936.6 | 0.00 | 0.00 | 744.00 | 0.00 | -73007233.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.94 | 0.88 | 01-JAN-10:09 | 122.09 | 9.12 | 0.00 | 30.67 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.93 | 0.88 | 03-FEB-10:30 | 131.14 | 9.24 | 0.00 | 60.17 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.91 | 0.88 | 01-MAR-08:39 | 215.13 | 11.77 | 0.00 | 164.83 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.90 | 0.88 | 02-APR-14:39 | 239.89 | 11.77 | 0.00 | 190.33 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.90 | 0.88 | 01-MAY-07:10 | 798.49 | 12.54 | 0.00 | 265.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.90 | 0.88 | 01-JUN-06:49 | 1989.55 | 12.88 | 0.00 | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.90 | 0.88 | 01-JUL-07:10 | 1832.96 | 13.59 | 20.00 | 278.17 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.90 | 0.88 | 01-AUG-07:49 | 1103.05 | 12.99 | 14.67 | 260.33 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.91 | 0.88 | 01-SEP-07:19 | 212.64 | 11.67 | 0.00 | 161.83 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.92 | 0.88 | 01-OCT-09:20 | 162.73 | 10.29 | 0.00 | 93.33 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.93 | 0.88 | 01-NOV-09:30 | 139.43 | 9.76 | 0.00 | 51.67 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.96 | 0.88 | 04-DEC-12:20 | 79.37 | 6.96 | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | 0.91 | 714.50 | 11.50 | 34.67 | 1839.17 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 186.17 | 0.90 | 0.88 | 79.37 | 6.96 | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 428.67 | 0.96 | 0.88 | 1989.55 | 13.59 | 20.00 | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.79 | 0.64 | 24-JAN-14:39 | 318.49 | 23.75 | 113.00 | 25.50 | 114.90 | 20.83 | 94.33 | 0.00 |
February | 226.83 | 0.78 | 0.61 | 20-FEB-16:10 | 583.26 | 24.66 | 128.50 | 49.83 | 134.21 | 21.08 | 119.00 | 0.67 |
March | 334.33 | 0.76 | 0.61 | 03-MAR-16:10 | 364.89 | 23.31 | 188.67 | 79.17 | 267.16 | 23.67 | 207.83 | 33.17 |
April | 285.17 | 0.73 | 0.61 | 03-APR-14:09 | 430.63 | 22.74 | 156.50 | 100.17 | 421.79 | 23.63 | 205.17 | 71.50 |
May | 428.67 | 0.74 | 0.61 | 01-MAY-13:50 | 296.24 | 21.34 | 206.17 | 103.50 | 280.60 | 22.45 | 274.33 | 67.33 |
June | 400.67 | 0.71 | 0.61 | 01-JUN-16:19 | 347.36 | 21.86 | 228.00 | 131.83 | 421.58 | 23.15 | 298.83 | 92.50 |
July | 414.00 | 0.71 | 0.61 | 01-JUL-13:39 | 352.63 | 22.13 | 230.50 | 153.50 | 467.04 | 23.37 | 314.17 | 116.17 |
August | 410.83 | 0.73 | 0.61 | 01-AUG-14:30 | 352.25 | 21.93 | 229.67 | 130.33 | 366.21 | 22.94 | 271.50 | 92.00 |
September | 326.50 | 0.74 | 0.61 | 01-SEP-14:30 | 504.12 | 24.42 | 188.33 | 98.17 | 430.69 | 24.95 | 232.50 | 65.00 |
October | 325.17 | 0.78 | 0.61 | 01-OCT-14:50 | 404.51 | 24.10 | 179.33 | 59.67 | 167.14 | 23.00 | 181.00 | 17.50 |
November | 254.83 | 0.82 | 0.63 | 03-NOV-15:30 | 236.22 | 22.23 | 112.83 | 17.33 | 104.57 | 20.46 | 96.67 | 0.00 |
December | 186.17 | 0.85 | 0.65 | 02-DEC-14:30 | 197.28 | 21.83 | 63.67 | 12.83 | 83.73 | 19.14 | 28.33 | 0.00 |
Annual Sum or Average | 3807.33 | 0.75 | 366.46 | 22.74 | 2025.17 | 961.83 | 298.07 | 22.67 | 2323.67 | 555.83 | ||
Minimum of Months | 186.17 | 0.71 | 0.61 | 197.28 | 21.34 | 63.67 | 12.83 | 83.73 | 19.14 | 28.33 | 0.00 | |
Maximum of Months | 428.67 | 0.85 | 0.65 | 583.26 | 24.66 | 230.50 | 153.50 | 467.04 | 24.95 | 314.17 | 116.17 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.163401E+11 | 26046.75 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124056E+11 | 26046.75 | 01-FEB-04:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.997818E+10 | 26046.75 | 01-MAR-01:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.539515E+10 | 26046.75 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132476E+10 | 26046.75 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186565E+09 | 26046.75 | 02-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.493502E+09 | 26046.75 | 23-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.314664E+10 | 26046.75 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.767075E+10 | 26046.75 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127129E+11 | 26046.75 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.696541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163401E+11 | 26046.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.654032E+11 | 67300.01 | 01-JAN-00:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.461911E+11 | 67300.01 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315646E+11 | 67300.01 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136245E+11 | 67300.01 | 01-APR-18:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.962741E+09 | 67300.01 | 02-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.477057E+09 | 66141.49 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.661521E+10 | 67300.01 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.290410E+11 | 67300.01 | 10-NOV-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.510815E+11 | 67300.01 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.244961E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.654032E+11 | 67300.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.264410E+12 | 238876.77 | 18-JAN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179239E+12 | 232177.01 | 01-FEB-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.981401E+11 | 171175.53 | 06-MAR-08:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226669E+11 | 99536.00 | 02-APR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.489134E+09 | 19694.61 | 02-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347116E+10 | 25930.58 | 24-OCT-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101928E+12 | 164424.44 | 25-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203365E+12 | 238876.77 | 08-DEC-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.873709E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.264410E+12 | 238876.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.125295E+09 | 85889599.76 | 5485.69 | 18-APR-15:10 | 3813.68 | 0.00 |
May | 0.00 | 0.00 | 0.255188E+09 | 0.193785E+09 | 5983.50 | 31-MAY-15:10 | 4911.95 | 0.00 |
June | 0.00 | 0.00 | 0.313370E+10 | 0.227779E+10 | 21952.46 | 26-JUN-05:55 | 10168.65 | 0.00 |
July | 0.00 | 0.00 | 0.530185E+10 | 0.367187E+10 | 21434.56 | 27-JUL-05:03 | 9053.46 | 0.00 |
August | 0.00 | 0.00 | 0.538925E+10 | 0.376624E+10 | 23634.54 | 04-AUG-05:01 | 8454.15 | 0.00 |
September | 0.00 | 0.00 | 0.205017E+10 | 0.177747E+10 | 20001.75 | 11-SEP-05:02 | 11885.19 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.162555E+11 | 0.117730E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.538925E+10 | 0.376624E+10 | 23634.54 | 11885.19 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.180994E+10 | 0.115594E+10 | 45681.55 | 30-JUN-18:55 | 30523.48 | 0.00 |
July | 0.00 | 0.00 | 0.322332E+10 | 0.190491E+10 | 49718.37 | 06-JUL-18:55 | 23861.60 | 0.00 |
August | 0.00 | 0.00 | 0.270107E+10 | 0.154582E+10 | 48373.67 | 03-AUG-17:20 | 26063.19 | 0.00 |
September | 0.00 | 0.00 | 0.835577E+09 | 0.648247E+09 | 10848.40 | 08-SEP-15:10 | 8639.56 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.856991E+10 | 0.525492E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.322332E+10 | 0.190491E+10 | 49718.37 | 30523.48 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.152253E+10 | 0.08 | 568.45 | 01-JAN-00:03 | 0.08 |
February | 0.134739E+10 | 0.08 | 568.45 | 01-FEB-00:02 | 0.08 |
March | 0.116316E+10 | 0.06 | 568.45 | 01-MAR-00:02 | 0.08 |
April | 0.465444E+09 | 0.03 | 568.45 | 01-APR-00:05 | 0.08 |
May | 23647374.17 | 0.00 | 568.45 | 01-MAY-20:40 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.192703E+09 | 0.01 | 568.45 | 15-OCT-20:40 | 0.08 |
November | 0.985061E+09 | 0.05 | 568.45 | 01-NOV-00:10 | 0.08 |
December | 0.151468E+10 | 0.08 | 568.45 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.721461E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152253E+10 | 0.08 | 568.45 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.125184E+10 | 0.78 | 1036.08 | 02-JAN-07:10 | 0.95 |
February | 0.110344E+10 | 0.71 | 1036.08 | 01-FEB-08:30 | 0.96 |
March | 0.122079E+10 | 0.63 | 1036.08 | 01-MAR-08:00 | 0.96 |
April | 0.108023E+10 | 0.48 | 1036.08 | 01-APR-06:40 | 0.95 |
May | 0.108662E+10 | 0.39 | 1036.08 | 01-MAY-06:40 | 0.95 |
June | 0.107471E+10 | 0.38 | 1036.08 | 01-JUN-06:10 | 0.94 |
July | 0.103701E+10 | 0.35 | 1036.08 | 01-JUL-06:40 | 0.94 |
August | 0.111399E+10 | 0.38 | 1036.08 | 01-AUG-08:50 | 0.94 |
September | 0.103343E+10 | 0.37 | 1036.08 | 01-SEP-09:20 | 0.94 |
October | 0.105303E+10 | 0.38 | 1036.08 | 02-OCT-06:10 | 0.95 |
November | 0.108172E+10 | 0.56 | 1036.08 | 01-NOV-06:40 | 0.95 |
December | 0.118563E+10 | 0.70 | 1036.08 | 01-DEC-07:30 | 0.95 |
Annual Sum or Average | 0.133224E+11 | 0.51 | |||
Minimum of Months | 0.103343E+10 | 0.35 | 1036.08 | 0.94 | |
Maximum of Months | 0.125184E+10 | 0.78 | 1036.08 | 0.96 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.212876E+10 | 0.70 | 1775.95 | 01-JAN-00:08 | 0.92 |
February | 0.165290E+10 | 0.67 | 1775.95 | 01-FEB-00:02 | 0.93 |
March | 0.145928E+10 | 0.60 | 1775.95 | 01-MAR-00:02 | 0.93 |
April | 0.101311E+10 | 0.45 | 1775.95 | 01-APR-18:23 | 0.92 |
May | 0.754471E+09 | 0.24 | 1775.95 | 02-MAY-05:11 | 0.92 |
June | 0.734779E+09 | 0.22 | 1461.34 | 30-JUN-17:20 | 0.83 |
July | 0.716985E+09 | 0.21 | 1775.95 | 03-JUL-17:12 | 0.90 |
August | 0.762921E+09 | 0.22 | 1775.95 | 03-AUG-17:20 | 0.90 |
September | 0.714605E+09 | 0.23 | 1745.38 | 30-SEP-05:01 | 0.92 |
October | 0.862937E+09 | 0.41 | 1775.95 | 17-OCT-05:01 | 0.92 |
November | 0.132889E+10 | 0.55 | 1775.95 | 10-NOV-02:62 | 0.92 |
December | 0.181737E+10 | 0.67 | 1775.95 | 01-DEC-00:03 | 0.92 |
Annual Sum or Average | 0.139470E+11 | 0.43 | |||
Minimum of Months | 0.714605E+09 | 0.21 | 1461.34 | 0.83 | |
Maximum of Months | 0.212876E+10 | 0.70 | 1775.95 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.125184E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.110344E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.122079E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.110800E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.114305E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.172451E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.210857E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.221468E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.146922E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.105303E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.108172E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.118563E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.166645E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.105303E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.221468E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.212876E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.165290E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.145928E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.101311E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.754471E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.118848E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.150218E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.142510E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.937794E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.862937E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.132889E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.181737E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.160713E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.754471E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.212876E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.125184E+10 | 0.00 | 0.163401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110344E+10 | 0.00 | 0.124056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122079E+10 | 0.00 | 0.997818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108023E+10 | 0.125295E+09 | 0.539515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108662E+10 | 0.255188E+09 | 0.132476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107471E+10 | 0.313370E+10 | 0.186565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103701E+10 | 0.530185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111399E+10 | 0.538925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103343E+10 | 0.205017E+10 | 0.493502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105303E+10 | 0.00 | 0.314664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108172E+10 | 0.00 | 0.767075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118563E+10 | 0.00 | 0.127129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133224E+11 | 0.162555E+11 | 0.696541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125184E+10 | 0.538925E+10 | 0.163401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.212876E+10 | 0.00 | 0.654032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165290E+10 | 0.00 | 0.461911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145928E+10 | 0.00 | 0.315646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101311E+10 | 0.00 | 0.136245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.754471E+09 | 0.00 | 0.962741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.734779E+09 | 0.180528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.716985E+09 | 0.315835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.762921E+09 | 0.270107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.714605E+09 | 0.835577E+09 | 0.477057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.862937E+09 | 0.00 | 0.661521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132889E+10 | 0.00 | 0.290410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181737E+10 | 0.00 | 0.510815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139470E+11 | 0.850028E+10 | 0.244961E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.714605E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.212876E+10 | 0.315835E+10 | 0.654032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.125184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108023E+10 | 0.00 | 0.00 | 0.00 | 27771535.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108662E+10 | 0.00 | 0.00 | 0.00 | 56430309.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107471E+10 | 0.00 | 0.00 | 0.00 | 0.649800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103701E+10 | 0.00 | 0.00 | 0.00 | 0.107156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111399E+10 | 0.00 | 0.00 | 0.00 | 0.110069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103343E+10 | 0.00 | 0.00 | 0.00 | 0.435790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133224E+11 | 0.00 | 0.00 | 0.00 | 0.334204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125184E+10 | 0.00 | 0.00 | 0.00 | 0.110069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.212876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.754471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.734779E+09 | 0.00 | 0.00 | 0.00 | 0.453699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.716985E+09 | 0.00 | 0.00 | 0.00 | 0.785193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.762921E+09 | 0.00 | 0.00 | 0.00 | 0.662176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.714605E+09 | 0.00 | 0.00 | 0.00 | 0.223189E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.862937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139470E+11 | 0.00 | 0.00 | 0.00 | 0.212426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.714605E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.212876E+10 | 0.00 | 0.00 | 0.00 | 0.785193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380083E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296048E+10 | 0.00 | 0.00 | 0.13 |
March | 3115759.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241620E+10 | 0.00 | 0.00 | 0.13 |
April | 0.103754E+09 | 14282021.65 | 29565.05 | 3544.99 | 15136250.26 | 0.152622E+10 | 13699912.47 | 693.05 | 0.13 |
May | 0.494508E+09 | 23545494.22 | 0.00 | 16159.86 | 1604523.56 | 0.341063E+09 | 27406638.23 | 0.00 | 0.15 |
June | 0.230899E+09 | 0.403628E+09 | 0.00 | 1453579.64 | 637049.69 | 64215443.24 | 0.851915E+09 | 0.00 | 0.42 |
July | 10922134.97 | 0.603380E+09 | 0.00 | 2495262.63 | 12242.61 | 0.00 | 0.100522E+10 | 0.00 | 0.52 |
August | 11966032.68 | 0.649449E+09 | 0.00 | 2587479.16 | 186560.49 | 0.00 | 0.117286E+10 | 0.00 | 0.58 |
September | 0.281548E+09 | 0.128458E+09 | 0.00 | 1678065.94 | 0.00 | 0.216010E+09 | 0.107047E+10 | 0.00 | 0.35 |
October | 0.172966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127058E+10 | 0.00 | 0.00 | 0.12 |
November | 73289219.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208638E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317925E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.138297E+10 | 0.182274E+10 | 29565.05 | 8234092.22 | 17576626.62 | 0.178612E+11 | 0.414157E+10 | 693.05 | 0.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.494508E+09 | 0.649449E+09 | 29565.05 | 2587479.16 | 15136250.26 | 0.380083E+10 | 0.117286E+10 | 693.05 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 69011569.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127025E+11 | 0.00 | 0.00 | 0.17 |
February | 0.292878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.922930E+10 | 0.00 | 0.00 | 0.18 |
March | 0.900230E+09 | 0.00 | 0.00 | 0.00 | 468011.44 | 0.600247E+10 | 0.00 | 0.00 | 0.19 |
April | 0.196882E+10 | 0.00 | 0.00 | 0.00 | 0.148569E+09 | 0.235161E+10 | 0.00 | 0.00 | 0.18 |
May | 0.174736E+10 | 0.00 | 0.00 | 0.00 | 77518020.98 | 55150345.02 | 0.00 | 0.00 | 0.18 |
June | 0.187576E+10 | 0.274011E+09 | 0.00 | 124113.73 | 29054396.21 | 0.00 | 32911349.76 | 0.00 | 0.20 |
July | 0.139519E+10 | 0.437083E+09 | 0.00 | 1151357.72 | 5548198.14 | 0.00 | 0.629288E+09 | 0.00 | 0.23 |
August | 0.163732E+10 | 0.507469E+09 | 0.00 | 665332.69 | 4812436.01 | 0.00 | 0.425348E+09 | 0.00 | 0.22 |
September | 0.254037E+10 | 82915878.39 | 0.00 | 271766.48 | 8143333.90 | 39793626.02 | 0.197341E+09 | 0.00 | 0.19 |
October | 0.292173E+10 | 0.00 | 0.00 | 0.00 | 9488447.50 | 0.478527E+09 | 0.00 | 0.00 | 0.17 |
November | 0.121426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501583E+10 | 0.00 | 0.00 | 0.17 |
December | 0.180469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100116E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.167434E+11 | 0.130148E+10 | 0.00 | 2212570.62 | 0.283602E+09 | 0.458868E+11 | 0.128489E+10 | 0.00 | 0.19 |
Minimum of Months | 69011569.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.292173E+10 | 0.507469E+09 | 0.00 | 1151357.72 | 0.148569E+09 | 0.127025E+11 | 0.629288E+09 | 0.00 | 0.23 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 10:43:14
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.357367E+12 | 0.222866E+12 | 0.00 | 0.165724E+11 | 0.710057E+11 |
February | 0.430069E+12 | 0.156310E+12 | 0.00 | 0.124827E+11 | 0.500382E+11 |
March | 0.718876E+12 | 0.107945E+12 | 0.00 | 0.932155E+10 | 0.317394E+11 |
April | 0.885711E+12 | 0.465321E+11 | 0.00 | 0.578610E+10 | 0.111701E+11 |
May | 0.105754E+13 | 0.206913E+11 | 0.00 | 0.256283E+10 | 0.127080E+10 |
June | 0.112148E+13 | 0.243441E+11 | 0.00 | 0.235237E+10 | 0.612228E+10 |
July | 0.115058E+13 | 0.312219E+11 | 0.00 | 0.200643E+10 | 0.103819E+11 |
August | 0.995696E+12 | 0.373432E+11 | 0.00 | 0.210657E+10 | 0.985319E+10 |
September | 0.687356E+12 | 0.430805E+11 | 0.00 | 0.413246E+10 | 0.393715E+10 |
October | 0.477446E+12 | 0.404262E+11 | 0.00 | 0.483431E+10 | 0.444910E+10 |
November | 0.256443E+12 | 0.111513E+12 | 0.00 | 0.838977E+10 | 0.302541E+11 |
December | 0.171900E+12 | 0.176372E+12 | 0.00 | 0.133713E+11 | 0.561843E+11 |
Annual Sum or Average | 0.831047E+13 | 0.101864E+13 | 0.00 | 0.839187E+11 | 0.286406E+12 |
Minimum of Months | 0.171900E+12 | 0.206913E+11 | 0.00 | 0.200643E+10 | 0.127080E+10 |
Maximum of Months | 0.115058E+13 | 0.222866E+12 | 0.00 | 0.165724E+11 | 0.710057E+11 |