Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:00
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 09:00:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11245.05 | 991.17 | 991.17 |
Net Site Energy | 11245.05 | 991.17 | 991.17 |
Total Source Energy | 25941.65 | 2286.56 | 2286.56 |
Net Source Energy | 25941.65 | 2286.56 | 2286.56 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 182.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1978.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 767.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 242.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 660.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 212.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 191.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.74 | 2671.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 61.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6602.02 | 4643.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 182.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1978.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 767.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 242.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 660.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 212.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 191.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 2671.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 182.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1978.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 767.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 242.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1745.01 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 651.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 660.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 212.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 191.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.74 | 2671.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 61.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 89.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 259.36 | 251.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 233.52 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 581.92 | 409.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 89.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 259.36 | 251.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 233.52 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 581.92 | 409.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6602.022 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6602.022 | 100.00 |
Total On-Site and Utility Electric Sources | 6602.022 | 100.00 |
Total Electricity End Uses | 6602.022 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 656.30 | 54.39 |
Air to Air Heat Recovery for Heating | 550.38 | 45.61 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1206.68 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 114.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7492.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:00 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 9.1389 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.3365 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.3365 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 9.2031 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 6.1031 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.8125 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 10.3656 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.7188 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.5531 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 6.3938 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.5531 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.5531 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 10.3656 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7219 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 6.3938 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 6.8557 | 7.07 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 9.1389 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.3365 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 9.2031 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 6.1031 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.8125 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 10.3656 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.7188 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.5531 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.5531 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 6.3938 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.5531 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.5531 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 10.3656 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7219 | 4.65 | 2934.4875 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 6.3938 | 18.58 | 0.0000 | |
Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Conditioned Total | 11345.29 | 6.8557 | 3.54 | 41.0709 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.4542 | 8.82 | 37.1989 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-19:00 | 16-DEC-22:10 | - | - | - | - | - | - | - | - | - | - | 04-DEC-21:40 |
Heating | 0.00 | 130651.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 195956.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 88772.42 | 54264.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32159.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 43756.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 9286.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3763.50 | 243148.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1870.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 463845.66 | 428064.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 130651.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 195956.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58789.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 24992.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1856.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 43756.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 9286.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3763.50 | 243148.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 535.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 197.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6266.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2429.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 769.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5526.46 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2063.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2092.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 673.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 605.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.38 | 2896.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 20908.60 | 5033.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 552.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 184.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 59.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 53.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 255.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1842.93 | 443.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 552.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 214.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 67.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 487.11 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 181.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 184.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 59.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 53.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 255.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1842.93 | 443.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.93 | 0.514628 | 0.426000 | 1.25 | 1.00 | 0.500000 | 0.000740 | 0.000052 | 1.25 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.394890 | 0.129424 | 0.300000 | 0.118467 | 0.358520 | 0.500000 | 0.002944 | 0.000027 | 0.119564 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.284484 | 0.208039 | 0.471000 | 0.133992 | 0.554769 | 0.500000 | 0.001831 | 0.000013 | 0.133992 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.303025 | 0.413013 | 0.300000 | 0.090908 | 1.00 | 0.500000 | 0.000922 | 0.000018 | 0.090908 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.150373 | 0.480182 | 0.562000 | 0.084510 | 1.00 | 0.500000 | 0.000793 | 0.000012 | 0.084510 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.64 | 0.064739 | 0.300000 | 1.09 | 0.300000 | 0.500000 | 0.023353 | 0.000065 | 1.09 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.60 | 0.089959 | 0.618000 | 0.988656 | 0.618000 | 0.500000 | 0.004235 | 0.000096 | 0.988656 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.25 | 0.190004 | 0.528000 | 2.77 | 0.528000 | 0.500000 | 0.002005 | 0.000248 | 2.77 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.71 | 0.695492 | 0.407000 | 0.694574 | 1.00 | 0.500000 | 0.000548 | 0.000107 | 0.694574 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.49 | 0.101655 | 0.698000 | 1.74 | 0.698000 | 0.500000 | 0.003748 | 0.000122 | 1.74 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.60 | 0.097147 | 0.667000 | 1.74 | 0.667000 | 0.500000 | 0.003922 | 0.000123 | 1.74 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.51 | 0.056436 | 0.300000 | 0.752634 | 0.300000 | 0.500000 | 0.012143 | 0.000047 | 0.752634 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.889130 | 0.353198 | 0.300000 | 0.266739 | 0.941861 | 0.500000 | 0.001079 | 0.000062 | 0.274740 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 5983.05 | 0.000052 | 124.77 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3105.02 | 0.000027 | 84.74 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1513.03 | 0.000013 | 33.95 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2099.48 | 0.000018 | 54.92 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1372.78 | 0.000012 | 32.74 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 7469.37 | 0.000065 | 159.28 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 10999.38 | 0.000096 | 246.35 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 28354.99 | 0.000248 | 628.48 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5574.35 | 0.000049 | 159.30 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5578.91 | 0.000049 | 159.43 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 32041.76 | 0.000280 | 915.66 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 32145.82 | 0.000281 | 918.63 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5564.49 | 0.000049 | 159.02 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5569.05 | 0.000049 | 159.15 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12282.38 | 0.000107 | 298.40 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1686.87 | 0.000015 | 48.20 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1687.41 | 0.000015 | 48.22 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8101.10 | 0.000071 | 231.50 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 13889.13 | 0.000122 | 300.09 |
DINING_FLR_6 VAV BOX REHEAT COIL | 14006.53 | 0.000123 | 302.86 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 5373.31 | 0.000047 | 114.98 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7135.32 | 0.000062 | 194.74 |
VAV WITH REHEAT HEATING COIL | 131459.73 | 0.001150 | 2306.64 |
FLR_3_DOAS HEATING COIL | 10951.44 | 0.000096 | 192.16 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.23 | 0.000049 | 0.000439 |
ROOM_2_FLR_3 FAN COIL | 1.22 | 0.000049 | 0.000436 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.76 | 0.000280 | 0.002408 |
ROOM_4_MULT19_FLR_3 FAN COIL | 7.30 | 0.000281 | 0.002695 |
ROOM_5_FLR_3 FAN COIL | 1.08 | 0.000049 | 0.000384 |
ROOM_6_FLR_3 FAN COIL | 1.07 | 0.000049 | 0.000381 |
ROOM_1_FLR_6 FAN COIL | 0.327138 | 0.000015 | 0.000117 |
ROOM_2_FLR_6 FAN COIL | 0.324563 | 0.000015 | 0.000116 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.43 | 0.000071 | 0.000516 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.23 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.22 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.76 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.30 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.08 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.07 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.327138 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.324563 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.43 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008478 | 12.80 | 0.008478 | 0.000439 | 1.23 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008478 | 12.80 | 0.008478 | 0.000436 | 1.22 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008417 | 12.80 | 0.008417 | 0.002408 | 6.76 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008630 | 12.80 | 0.008500 | 0.002695 | 7.30 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008474 | 12.80 | 0.008474 | 0.000384 | 1.08 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008474 | 12.80 | 0.008474 | 0.000381 | 1.07 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008479 | 12.80 | 0.008479 | 0.000117 | 0.327138 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008479 | 12.80 | 0.008479 | 0.000116 | 0.324563 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008540 | 12.80 | 0.008500 | 0.000516 | 1.43 | |
VAV WITH REHEAT COOLING COIL | 31.95 | 6.70 | 0.007701 | 10.79 | 0.007701 | 0.020736 | 24.62 | 580553.63 |
FLR_3_DOAS COOLING COIL | 40.80 | 6.70 | 0.005631 | 11.84 | 0.005631 | 0.002355 | 2.05 | 65945.86 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 13.64 | 11.71 | 24.75 | 11.71 | 24.62 | 24.62 | 0.300000 | 0.475667 | 24.62 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 24.62 | 11.66 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 24.62 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.020736 | 0.000023 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001150 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002355 | 0.000202 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000096 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.030582 | 6301.84 | |
HEATSYS1 PUMP | 0.003096 | 932.52 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003096 | 0.371576 |
COOLSYS1 | 0.030582 | 3.67 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 353944.71 | 353944.71 | 0.003096 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.030582 | 4362.97 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.030582 | 856217.24 | 856882.29 | 97.68 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 9.139 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.519 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.336 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.096 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 9.203 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.583 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 6.103 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 8.793 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.813 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.343 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 10.366 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.746 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.719 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.789 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.553 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.303 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.553 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 15.073 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 10.366 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 78.186 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.722 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2946.209 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 6.394 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 18084.325 | 9.139 | 169.807 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18084.325 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 894.495 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 894.495 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1035.829 | 13.336 | 82.602 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1035.829 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1511.551 | 9.203 | 569.967 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1511.551 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 578.329 | 6.103 | 283.494 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 578.329 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 453.605 | 5.813 | 54.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 453.605 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1957.673 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1957.673 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11405.759 | 8.719 | 27.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11405.759 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 111.660 | 4.553 | 74.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.660 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2489.757 | 6.394 | 118.803 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.757 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 177.672 | 4.553 | 118.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.672 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 177.651 | 4.553 | 118.434 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 177.651 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 111.691 | 4.553 | 74.460 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 111.691 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3437.839 | 10.366 | 13.757 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3437.839 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1210.923 | 11.722 | 54.453 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1210.923 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2635.024 | 6.394 | 118.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2635.024 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.287 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.608 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.684 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.370 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.442 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6100 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4545 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4264 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5624 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5260 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | 0.16691074E-14 | 0.45207920E-16 | -0.13282787E-09 | -0.59403108E-17 |
29 | 8 | 0.19494068E-07 | 0.16957001E-12 | 0.35230437E-03 | -0.22165426E-09 |
30 | 7 | -0.11479370E-01 | 0.90467759E-08 | -0.21987867E-01 | 0.13052461E-03 |
31 | 6 | 0.38463807 | 0.31869432E-05 | 0.45441076 | -0.45036152E-02 |
32 | 5 | -4.9884079 | 0.12028467E-03 | -4.3052891 | 0.60677235E-01 |
33 | 4 | 32.108494 | 0.99355415E-03 | 20.908458 | -0.41024850 |
34 | 3 | -109.32288 | 0.21841230E-02 | -54.572312 | 1.4876971 |
35 | 2 | 195.24423 | 0.12380226E-02 | 76.910992 | -2.8707534 |
36 | 1 | -170.46733 | 0.13310261E-03 | -54.975783 | 2.7333683 |
37 | 0 | 57.057407 | 0.76355891E-06 | 15.605832 | |
38 | 9 | 0.14115123E-14 | 0.53960859E-16 | -0.11739578E-09 | -0.22900007E-17 |
39 | 8 | 0.17311930E-07 | 0.20639465E-12 | 0.32798840E-03 | -0.19684260E-09 |
40 | 7 | -0.10748946E-01 | 0.11327704E-07 | -0.20934514E-01 | 0.12221941E-03 |
41 | 6 | 0.36478417 | 0.40360747E-05 | 0.43737925 | -0.42695883E-02 |
42 | 5 | -4.7945715 | 0.15382307E-03 | -4.1739388 | 0.58273831E-01 |
43 | 4 | 31.250576 | 0.12816568E-02 | 20.393829 | -0.39885853 |
44 | 3 | -107.49604 | 0.28390629E-02 | -53.554356 | 1.4613070 |
45 | 2 | 193.43186 | 0.16201491E-02 | 75.979619 | -2.8419759 |
46 | 1 | -169.79719 | 0.17527083E-03 | -54.709122 | 2.7216233 |
47 | 0 | 57.057407 | 0.10123612E-05 | 15.653272 | |
48 | 9 | 0.65135446E-15 | 0.56204292E-16 | -0.11372497E-09 | -0.53489081E-17 |
49 | 8 | 0.16791160E-07 | 0.21454591E-12 | 0.32203280E-03 | -0.19092129E-09 |
50 | 7 | -0.10569524E-01 | 0.11862766E-07 | -0.20675571E-01 | 0.12017931E-03 |
51 | 6 | 0.35990649 | 0.42391557E-05 | 0.43318136 | -0.42120931E-02 |
52 | 5 | -4.7469406 | 0.16196889E-03 | -4.1415055 | 0.57683257E-01 |
53 | 4 | 31.039704 | 0.13525358E-02 | 20.266625 | -0.39605902 |
54 | 3 | -107.04684 | 0.30019179E-02 | -53.302690 | 1.4548183 |
55 | 2 | 192.98603 | 0.17160237E-02 | 75.749609 | -2.8348971 |
56 | 1 | -169.63227 | 0.18593554E-03 | -54.643729 | 2.7187328 |
57 | 0 | 57.057407 | 0.10758168E-05 | 15.665287 | |
58 | 9 | 0.10314710E-14 | 0.47183642E-16 | -0.12881513E-09 | -0.40099708E-17 |
59 | 8 | 0.18927665E-07 | 0.17950474E-12 | 0.34608657E-03 | -0.21521408E-09 |
60 | 7 | -0.11292911E-01 | 0.96443222E-08 | -0.21719088E-01 | 0.12840450E-03 |
61 | 6 | 0.37957032 | 0.34070209E-05 | 0.45007157 | -0.44438791E-02 |
62 | 5 | -4.9389364 | 0.12890179E-03 | -4.2718596 | 0.60063826E-01 |
63 | 4 | 31.889569 | 0.10670331E-02 | 20.777560 | -0.40734193 |
64 | 3 | -108.85680 | 0.23501275E-02 | -54.313423 | 1.4809641 |
65 | 2 | 194.78196 | 0.13343675E-02 | 76.673975 | -2.8634131 |
66 | 1 | -170.29645 | 0.14368413E-03 | -54.907648 | 2.7303734 |
67 | 0 | 57.057407 | 0.82565881E-06 | 15.617726 | |
68 | 9 | 0.86975537E-15 | 0.52023775E-16 | -0.12536948E-09 | -0.54620444E-17 |
69 | 8 | 0.18440443E-07 | 0.18784465E-12 | 0.34068694E-03 | -0.20967419E-09 |
70 | 7 | -0.11130813E-01 | 0.10155400E-07 | -0.21485363E-01 | 0.12656138E-03 |
71 | 6 | 0.37516444 | 0.35965268E-05 | 0.44629465 | -0.43919449E-02 |
72 | 5 | -4.8959230 | 0.13636263E-03 | -4.2427425 | 0.59530495E-01 |
73 | 4 | 31.699203 | 0.11309484E-02 | 20.663505 | -0.40481456 |
74 | 3 | -108.45147 | 0.24950915E-02 | -54.087828 | 1.4751087 |
75 | 2 | 194.37988 | 0.14187814E-02 | 76.467519 | -2.8570287 |
76 | 1 | -170.14779 | 0.15298304E-03 | -54.848449 | 2.7277680 |
77 | 0 | 57.057407 | 0.88039223E-06 | 15.628184 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5119_SHGC_0.25 | 37 | 1 | VerySmooth | 2.910 | 2.910 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.5119_SHGC_0.25 | 38 | 1 | VerySmooth | 2.910 | 2.910 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 1.79780E-002 | 0.16139 | 0.60964 | 0.60964 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10364 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 1.79780E-002 | 0.16139 | 0.60964 | 0.60964 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10364 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.058E-002 | 1.052E-003 | 5.193E-004 | 0.956 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 2.724E-002 | 3.507E-004 | 9.551E-004 | 0.319 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 6.438E-002 | 3.920E-004 | 1.025E-003 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 3.715E-002 | 3.920E-004 | 8.507E-004 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.791E-002 | 1.127E-003 | 1.002E-003 | 1.023 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.156 | 8.261E-004 | 4.549E-004 | 0.751 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.446 | 3.407E-004 | 6.517E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 4.096E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 4.095E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.143E-002 | 4.660E-004 | 1.025E-003 | 0.550 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.143E-002 | 4.660E-004 | 1.025E-003 | 0.550 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 4.096E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 4.095E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 4.953E-002 | 1.272E-004 | 1.025E-003 | 0.150 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 4.096E-002 | 1.050E-003 | 5.186E-004 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 4.095E-002 | 1.050E-003 | 5.186E-004 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.096E-002 | 8.543E-004 | 4.660E-004 | 1.009 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 0.100 | 3.015E-004 | 2.330E-004 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 0.100 | 3.015E-004 | 2.330E-004 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 8.953E-002 | 8.667E-004 | 4.697E-004 | 1.024 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 8.763E-002 | 2.126E-004 | 1.761E-004 | 0.251 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 8.7310E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.8709E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.7087E-002 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.2189E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 6.5660E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.4295E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.6511E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.7811E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 9.8430E-002 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.7382E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1097 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.1591E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.2656E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.0684E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 2.9789E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.2036E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.1147E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.2078E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.6306E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.1307E-003 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.5594E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.2294E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.6108E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.2309E-003 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.1147E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.2078E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.6306E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.1307E-003 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.5594E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.2294E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.6108E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.2309E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 36609.91672 | 36609.91672 | 2.93001 | 2.93001 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:30:00 | 32.35450 | 5.61809E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 0.50000 | 4.31558E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4933.90178 | 4933.90178 | 0.39489 | 0.39489 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2532.51288 | 2532.51288 | 0.11956 | 0.11956 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3554.24988 | 3554.24988 | 0.28448 | 0.28448 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 37.60800 | 5.62614E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 871.43109 | 871.43109 | 4.11430E-002 | 9.17347E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3786.74184 | 3786.74184 | 0.30303 | 0.30303 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 36.61050 | 5.62460E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1664.27330 | 1664.27330 | 7.85753E-002 | 7.85753E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1879.12043 | 1879.12043 | 0.15037 | 0.15037 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 38.05133 | 5.62683E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 968.19906 | 968.19906 | 4.57116E-002 | 5.77652E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45546.09193 | 45546.09193 | 3.64498 | 3.64498 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 40.13500 | 5.63007E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2235.00215 | 2235.00215 | 0.10552 | 0.10552 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 19970.77361 | 19970.77361 | 1.59977 | 1.59977 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6264.84996 | 6264.84996 | 0.29578 | 0.67639 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 65527.92905 | 65527.92905 | 5.24641 | 5.24641 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40.80000 | 5.63111E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 15090.20488 | 15090.20488 | 0.71246 | 1.89399 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11424.24333 | 11424.24333 | 1.23196 | 1.23196 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5574.49315 | 5574.49315 | 0.26472 | 0.26472 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11342.92923 | 11342.92923 | 1.22319 | 1.22319 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5579.05193 | 5579.05193 | 0.26494 | 0.26494 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 62682.34837 | 62682.34837 | 6.75941 | 6.75941 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40.80000 | 5.63111E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 32042.15478 | 32042.15478 | 1.52168 | 1.52168 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 67673.90470 | 67673.90470 | 7.29826 | 7.29826 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 40.26800 | 5.63027E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 32146.22281 | 32146.22281 | 1.52663 | 1.52663 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9980.67707 | 9980.67707 | 1.07629 | 1.07629 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 36.74350 | 5.62481E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5564.62584 | 5564.62584 | 0.26426 | 0.26426 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9911.31898 | 9911.31898 | 1.06881 | 1.06881 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 36.41100 | 5.62429E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5569.18721 | 5569.18721 | 0.26447 | 0.26447 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21324.00817 | 21324.00817 | 1.70657 | 1.70657 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 40.40100 | 5.63048E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8955.58122 | 8955.58122 | 0.42283 | 0.47476 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3033.62175 | 3033.62175 | 0.32714 | 0.32714 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1686.91035 | 1686.91035 | 8.01087E-002 | 8.01087E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3009.74627 | 3009.74627 | 0.32456 | 0.32456 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1687.44823 | 1687.44823 | 8.01343E-002 | 8.01343E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 13289.02995 | 13289.02995 | 1.43311 | 1.43311 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40.80000 | 5.63111E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8101.25970 | 8101.25970 | 0.38472 | 0.38472 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 31025.09526 | 31025.09526 | 2.48608 | 2.48608 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5576.86003 | 5576.86003 | 0.26330 | 1.18780 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 32465.20578 | 32465.20578 | 2.60144 | 2.60144 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5694.86988 | 5694.86988 | 0.26887 | 1.18780 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31265.19337 | 31265.19337 | 2.50878 | 2.50878 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 39.60300 | 5.62924E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1778.28186 | 1778.28186 | 8.39469E-002 | 0.36735 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 0.50000 | 4.31558E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 11110.05808 | 11110.05808 | 0.88913 | 0.88913 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 40.80000 | 5.63111E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5819.14331 | 5819.14331 | 0.27474 | 0.27474 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 518010.32 | 24.62375 | 24.62375 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 131162.48 | 7.37042 | 7.37042 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 63092.52 | 20.26729 | 2.05125 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 36503.53 | 4.65167 | 2.05125 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.93001 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.51463 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.24819 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.40340E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.23423E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.24819 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5983.04768 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.23423E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 124.76615 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.39489 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12942 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11847 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35852 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.94381E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.71641E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11956 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3105.02097 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.71641E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 84.73939 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.28448 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20804 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47100 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13399 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55477 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.83139E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.32366E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13399 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1513.02876 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.32366E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 33.95399 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.30303 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.41301 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.09075E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.22489E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.83672E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.09075E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2099.48023 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.83672E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 54.92150 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.15037 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.48018 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.45099E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.93450E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.20097E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.45099E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1372.78174 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.20097E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 32.74049 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.64498 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.47393E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.09349 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33535E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.53453E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.09349 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7469.37098 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.53453E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 159.27761 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59977 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.99585E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.61800 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.98866 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61800 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.23528E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.62274E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.98866 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10999.38444 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.62274E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 246.35319 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.24641 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.77010 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52800 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.00522E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.48062E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.77010 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 28354.99217 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.48062E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 628.47613 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.23196 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.23196 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.87669E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.38985E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74179 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47827E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47827E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.38985E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.23196 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5574.35247 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.87669E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 159.30100 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.22319 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.22319 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.88067E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.35860E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74179 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47803E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47803E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.35860E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.22319 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5578.91114 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.88067E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 159.43124 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.75941 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.75941 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.80315E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.40836E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74197 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.41720E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.41720E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.40836E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.75941 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 32041.75602 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.80315E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 915.65817 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.29826 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.29826 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.81226E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.69455E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74108 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62989E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.69455E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.29826 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 32145.82280 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.81226E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 918.63142 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.07629 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.07629 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.86805E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.83512E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74180 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47403E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47403E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.83512E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.07629 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5564.48539 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.86805E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 159.01910 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.06881 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.06881 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.87204E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.80847E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74180 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47374E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47374E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.80847E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.06881 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5569.04665 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.87204E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 159.14941 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.70657 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.69549 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.40700 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.69457 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.47814E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07452E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69457 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12282.38362 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07452E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 298.39666 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.32714 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.32714 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.47575E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.16569E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74178 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47948E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47948E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.16569E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.32714 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1686.86890 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47575E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 48.20421 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.32456 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.32456 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.47622E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.15652E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74178 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47924E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47924E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.15652E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.32456 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1687.40677 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47622E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 48.21958 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.43311 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.43311 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.08720E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.16289E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74140 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.53960E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.16289E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.43311 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8101.09931 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.08720E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 231.49638 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.48608 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10166 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.69800 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.73528 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69800 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.74796E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21508E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.73528 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13889.13125 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21508E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 300.09240 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.60144 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.71475E-002 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.66700 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.73516 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66700 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.92187E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.22535E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.73516 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14006.53390 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22535E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 302.86254 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.50878 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.64355E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.75263 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21426E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.70081E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75263 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5373.30983 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.70081E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 114.97548 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88913 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35320 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26674 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94186 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07872E-003 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.24229E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27474 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7135.32249 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.24229E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 194.73523 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 13.64465 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.71270 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.74594 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.71270 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.62375 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 24.62375 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.47567 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 24.62375 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.62375 |
338 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 11.66146 |
339 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 31.95058 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.78890 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.70111E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.70111E-003 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 580553.63269 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.07360E-002 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 24.62375 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 131459.72513 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15007E-003 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2306.64448 |
351 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 24.62375 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.07360E-002 |
353 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.29644E-005 |
354 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.15007E-003 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
356 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
357 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 40.80000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.83593 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.63111E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.63111E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 65945.85541 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.35543E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 10951.44367 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.58080E-005 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 192.15837 |
369 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.35543E-003 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.02167E-004 |
372 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.58080E-005 |
373 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.05821E-002 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 6301.83649 |
375 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.09646E-003 |
376 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.37158 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.09646E-003 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 932.51858 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
380 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 353944.70630 |
381 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 353944.71000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.09646E-003 |
383 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.05821E-002 |
384 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.66985 |
385 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.05821E-002 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 4362.97395 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.05821E-002 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 856217.23839 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 856882.29000 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 97.68458 |
391 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
392 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
393 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
395 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6014.20 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3117.46 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1520.36 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2108.19 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1379.12 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 7507.59 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 11052.76 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 28493.82 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 6005.31 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 6010.22 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 34518.74 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 34630.84 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 5994.68 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 5999.59 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12337.37 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1817.23 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1817.81 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8727.13 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 13959.50 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 14077.45 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 5400.73 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7163.91 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 105874.89 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 8820.06 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 20452.85 | 15940.43 | 4512.42 | 0.78 | 2834.99 | 28.75 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 20307.76 | 15827.32 | 4480.44 | 0.78 | 2815.10 | 28.55 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 112916.66 | 87955.86 | 24960.80 | 0.78 | 15975.96 | 162.04 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 123710.41 | 95364.01 | 28346.40 | 0.77 | 16836.39 | 170.76 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 17876.07 | 13931.65 | 3944.42 | 0.78 | 2481.28 | 25.17 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 17752.37 | 13835.22 | 3917.16 | 0.78 | 2464.35 | 24.99 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5430.44 | 4232.39 | 1198.05 | 0.78 | 752.42 | 7.63 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5387.83 | 4199.17 | 1188.66 | 0.78 | 746.57 | 7.57 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 23911.30 | 18574.40 | 5336.90 | 0.78 | 3279.94 | 33.27 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 691902.64 | 436910.77 | 254991.88 | 0.63 | 102074.21 | 1035.29 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 54169.20 | 34464.63 | 19704.58 | 0.64 | 5364.64 | 54.41 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.442 | 1.186 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.442 | 1.186 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.442 | 1.186 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.442 | 1.186 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.442 | 1.186 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.5870025657E-002 | 3.9403928078E-002 | Pass | Pass | 0.1586089121 | 0.6482313946 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.1690587794E-002 | 9.4286015701E-002 | Pass | Pass | 0.1501569923 | 0.4861674759 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.1165753538E-002 | 7.8211811582E-002 | Pass | Pass | 0.5131496989 | 5.0151811494 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.1374569249E-002 | 3.0482686118E-002 | Pass | Pass | 8.7600617144E-002 | 0.2298133495 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.9274468454E-003 | 2.8350708541E-002 | Pass | Pass | 0.2281849464 | 0.8873076284 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1015813412 | 0.3039186944 | Pass | Pass | 7.5691742165E-002 | 0.1755126795 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1210480459 | 0.1938677546 | Pass | Pass | 0.2620752198 | 1.8909865516 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.4111436125E-002 | 0.1026069261 | Pass | Pass | 8.8798686487E-002 | 0.3010975417 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.2467607539E-002 | 0.1985462551 | Pass | Pass | 0.1834745233 | 0.5171032881 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.8943439102E-002 | 0.2216090482 | Pass | Pass | 0.6023768346 | 4.2360835153 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.9121815550E-002 | 4.1367202469E-002 | Pass | Pass | 3.1021593254E-002 | 5.0964345997E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.3435252907E-002 | 8.7449339045E-002 | Pass | Pass | 0.2729522518 | 1.0593962792 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.1411209518E-002 | 0.1254177552 | Pass | Pass | 0.1616985990 | 0.3487962461 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.5825381326E-002 | 0.1660287754 | Pass | Pass | 1.8756917576 | 20.4688726318 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.0994519695E-002 | 2.8292463007E-002 | Pass | Pass | 7.8829426183E-002 | 0.2470333155 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.5202597951E-002 | 0.2365116876 | Pass | Pass | 0.3940310132 | 2.1170074561 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.8040231751E-002 | 0.2518515592 | Pass | Pass | 1.0063075655 | 8.3318600982 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.2710390879E-002 | 0.2355196320 | Pass | Pass | 0.2905417520 | 0.8252894857 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1265146326 | 0.2559747069 | Pass | Pass | 0.1011836135 | 0.3316047531 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1202801705 | 0.2308416091 | Pass | Pass | 9.7838667321E-002 | 0.3072891060 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1254749616 | 0.3354765144 | Pass | Pass | 9.2476124969E-002 | 0.2225837236 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.6398863445E-002 | 3.8219875134E-002 | Pass | Pass | 0.1133025172 | 0.2224819034 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2720.32 | 70.22 | 393.68 | 2424.78 | 8151.25 | 13760.25 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.910 | 0.251 | 0.251 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.910 | 0.251 | 0.251 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.910 | 0.251 | 0.251 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.910 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.910 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.910 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.910 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.910 | 0.251 | 0.251 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.910 | 0.251 | 0.251 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.910 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.910 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.910 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.910 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.910 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.910 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.910 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.910 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.910 | 0.251 | 0.251 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.910 | 0.251 | 0.251 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.910 | 0.251 | 0.251 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.910 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.910 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.910 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.910 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 432.95 | 2.910 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.910 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 9.1389 | 1978.83 | 18084.33 | LightsWired | LTG_SCH_BASEMENT | 51.16 | 168.00 | 51.10 | 0.0000 | Y | 173.46 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.3365 | 67.07 | 894.50 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.61 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.3365 | 77.67 | 1035.83 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 9.97 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 9.2031 | 164.24 | 1511.55 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.63 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 6.1031 | 94.76 | 578.33 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 2.78 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.8125 | 78.04 | 453.60 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 4.37 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 10.3656 | 188.86 | 1957.67 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.02 | 0.0000 | Y | 18.01 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.7188 | 1308.19 | 11405.76 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 56.97 | 0.0000 | Y | 121.97 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.5531 | 1863.81 | 8486.17 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.02 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.5531 | 1864.32 | 8488.49 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 76.04 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.5531 | 156.09 | 710.69 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.5531 | 156.07 | 710.61 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.37 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 6.3938 | 1557.62 | 9959.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 109.60 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.67 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.5531 | 39.02 | 177.65 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.59 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.5531 | 220.77 | 1005.22 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 9.00 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.97 | 0.0000 | Y | 34.83 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 10.3656 | 331.66 | 3437.84 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 53.97 | 0.0000 | Y | 34.83 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7219 | 103.30 | 1210.92 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.33 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 6.3938 | 412.12 | 2635.02 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.00 |
Interior Lighting Total | 6.8557 | 11345.29 | 77780.02 | 507.76 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 11405.76 | 798.40 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 11405.76 | 0.00 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1957.67 | 763.49 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.00 | 1957.67 | 0.00 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3437.84 | 687.57 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.00 | 3437.84 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 15448.40 | AstronomicalClock | - | 83.79 | 83.79 | 242.97 | |
Exterior Lighting Total | 15448.40 | 242.97 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 353944.71 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 856882.29 | 2.96 | 857032.91 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12290.64 | 20452.85 | 15940.43 | 4512.42 | 0.78 | - | 2834.99 | 28.75 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12203.16 | 20307.76 | 15827.32 | 4480.44 | 0.78 | - | 2815.10 | 28.55 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 67429.05 | 112916.66 | 87955.86 | 24960.80 | 0.78 | - | 15975.96 | 162.04 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 75441.70 | 123710.41 | 95364.01 | 28346.40 | 0.77 | - | 16836.39 | 170.76 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10737.52 | 17876.07 | 13931.65 | 3944.42 | 0.78 | - | 2481.28 | 25.17 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10662.90 | 17752.37 | 13835.22 | 3917.16 | 0.78 | - | 2464.35 | 24.99 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3263.69 | 5430.44 | 4232.39 | 1198.05 | 0.78 | - | 752.42 | 7.63 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3238.01 | 5387.83 | 4199.17 | 1188.66 | 0.78 | - | 746.57 | 7.57 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 14455.00 | 23911.30 | 18574.40 | 5336.90 | 0.78 | - | 3279.94 | 33.27 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 580553.63 | 691902.64 | 436910.77 | 254991.88 | 0.63 | - | 102074.21 | 1035.29 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 65945.86 | 54169.20 | 34464.63 | 19704.58 | 0.64 | - | 5364.64 | 54.41 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 5983.05 | 6014.20 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3105.02 | 3117.46 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1513.03 | 1520.36 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2099.48 | 2108.19 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1372.78 | 1379.12 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 7469.37 | 7507.59 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10999.38 | 11052.76 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 28354.99 | 28493.82 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5574.35 | 6005.31 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5578.91 | 6010.22 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 32041.76 | 34518.74 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 32145.82 | 34630.84 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5564.49 | 5994.68 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5569.05 | 5999.59 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12282.38 | 12337.37 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1686.87 | 1817.23 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1687.41 | 1817.81 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 8101.10 | 8727.13 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13889.13 | 13959.50 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14006.53 | 14077.45 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 5373.31 | 5400.73 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7135.32 | 7163.91 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 131459.73 | 105874.89 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 10951.44 | 8820.06 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.23 | 866.85 | 703.64 | 1.00 | 1.15 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.22 | 860.68 | 703.64 | 1.00 | 1.15 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.76 | 4756.17 | 703.64 | 1.00 | 0.95 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.30 | 5135.32 | 703.64 | 1.00 | 0.95 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.08 | 757.32 | 703.64 | 1.00 | 1.18 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.07 | 752.05 | 703.64 | 1.00 | 1.18 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.33 | 230.19 | 703.64 | 1.00 | 1.65 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.32 | 228.37 | 703.64 | 1.00 | 1.66 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.43 | 1008.39 | 703.64 | 1.00 | 1.12 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 24.62 | 55172.92 | 2240.64 | 1.00 | 1.11 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.030582 | 6301.84 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003096 | 932.52 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.030582 | 4362.97 | 142664.32 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 36609.92 | 36609.92 | 18.50 | 2.930 | 2.930 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:30:00 | 24.00 | 24.00 | 0.00916 | 32.35 | 0.00562 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4933.90 | 4933.90 | 73.56 | 0.395 | 0.395 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00886 | 40.80 | 0.00563 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3554.25 | 3554.25 | 45.76 | 0.284 | 0.284 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.00 | 24.00 | 0.00922 | 37.61 | 0.00563 | 0.092 | 0.00 |
MECH_FLR_1 | 3786.74 | 3786.74 | 23.06 | 0.303 | 0.303 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 24.00 | 24.00 | 0.00852 | 36.61 | 0.00562 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1879.12 | 1879.12 | 19.83 | 0.150 | 0.150 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00858 | 38.05 | 0.00563 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45546.09 | 45546.09 | 583.63 | 3.645 | 3.645 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00853 | 40.13 | 0.00563 | 0.000 | 0.00 |
CAFE_FLR_1 | 19970.77 | 19970.77 | 105.74 | 1.600 | 1.600 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.01001 | 40.80 | 0.00563 | 0.676 | 0.00 |
LOBBY_FLR_1 | 65527.93 | 65527.93 | 50.09 | 5.246 | 5.246 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.99 | 0.00988 | 40.80 | 0.00563 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11424.24 | 11424.24 | 292.76 | 1.232 | 1.232 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00848 | 39.12 | 0.00563 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11342.93 | 11342.93 | 290.71 | 1.223 | 1.223 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00848 | 38.94 | 0.00563 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 62682.35 | 62682.35 | 2555.98 | 6.759 | 6.759 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 21.11 | 21.11 | 0.00842 | 40.80 | 0.00563 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 67673.90 | 67673.90 | 2758.76 | 7.298 | 7.298 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 21.11 | 21.11 | 0.00863 | 40.27 | 0.00563 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9980.68 | 9980.68 | 255.77 | 1.076 | 1.076 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 21.11 | 21.11 | 0.00847 | 36.74 | 0.00562 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9911.32 | 9911.32 | 254.02 | 1.069 | 1.069 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 21.11 | 21.11 | 0.00847 | 36.41 | 0.00562 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21324.01 | 21324.01 | 54.76 | 1.707 | 1.707 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00929 | 40.40 | 0.00563 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3033.62 | 3033.62 | 77.74 | 0.327 | 0.327 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00848 | 39.12 | 0.00563 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3009.75 | 3009.75 | 77.14 | 0.325 | 0.325 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00848 | 38.94 | 0.00563 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13289.03 | 13289.03 | 541.73 | 1.433 | 1.433 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 21.11 | 21.11 | 0.00854 | 40.80 | 0.00563 | 0.099 | 0.00 |
BANQUET_FLR_6 | 31025.10 | 31025.10 | 93.55 | 2.486 | 2.486 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.98 | 0.01028 | 40.67 | 0.00563 | 1.188 | 0.00 |
DINING_FLR_6 | 32465.21 | 32465.21 | 97.89 | 2.601 | 2.601 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.98 | 0.01020 | 40.67 | 0.00563 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31265.19 | 31265.19 | 302.65 | 2.509 | 2.509 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01002 | 39.60 | 0.00563 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 11110.06 | 11110.06 | 26.96 | 0.889 | 0.889 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00888 | 40.80 | 0.00563 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 24.00 | 0.00849 | 0.50 | 0.00432 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 2532.51 | 2532.51 | 37.76 | 0.120 | 0.120 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00750 | 0.50 | 0.00432 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 871.43 | 871.43 | 11.22 | 0.041 | 0.092 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00745 | 0.50 | 0.00432 | 0.092 | 0.00 |
MECH_FLR_1 | 1664.27 | 1664.27 | 10.13 | 0.079 | 0.079 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00734 | 0.50 | 0.00432 | 0.000 | 0.00 |
STORAGE_FLR_1 | 968.20 | 968.20 | 10.22 | 0.046 | 0.058 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00735 | 0.50 | 0.00432 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2235.00 | 2235.00 | 28.64 | 0.106 | 0.106 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00733 | 0.50 | 0.00432 | 0.000 | 0.00 |
CAFE_FLR_1 | 6264.85 | 6264.85 | 33.17 | 0.296 | 0.676 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00755 | 0.50 | 0.00432 | 0.676 | 0.00 |
LOBBY_FLR_1 | 15090.20 | 15090.20 | 11.54 | 0.712 | 1.894 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00747 | 0.50 | 0.00432 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5574.49 | 5574.49 | 142.86 | 0.265 | 0.265 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00748 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5579.05 | 5579.05 | 142.99 | 0.265 | 0.265 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00748 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 32042.15 | 32042.15 | 1306.57 | 1.522 | 1.522 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00751 | 0.50 | 0.00432 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 32146.22 | 32146.22 | 1310.46 | 1.527 | 1.527 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00752 | 0.50 | 0.00432 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5564.63 | 5564.63 | 142.60 | 0.264 | 0.264 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00748 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5569.19 | 5569.19 | 142.74 | 0.264 | 0.264 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00748 | 0.50 | 0.00432 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 8955.58 | 8955.58 | 23.00 | 0.423 | 0.475 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00759 | 0.50 | 0.00432 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1686.91 | 1686.91 | 43.23 | 0.080 | 0.080 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00756 | 0.50 | 0.00432 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1687.45 | 1687.45 | 43.25 | 0.080 | 0.080 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00756 | 0.50 | 0.00432 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8101.26 | 8101.26 | 330.25 | 0.385 | 0.385 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00757 | 0.50 | 0.00432 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5576.86 | 5576.86 | 16.82 | 0.263 | 1.188 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00766 | 0.50 | 0.00432 | 1.188 | 0.00 |
DINING_FLR_6 | 5694.87 | 5694.87 | 17.17 | 0.269 | 1.188 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00767 | 0.50 | 0.00432 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1778.28 | 1778.28 | 17.21 | 0.084 | 0.367 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00647 | 0.50 | 0.00432 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5819.14 | 5819.14 | 14.12 | 0.275 | 0.275 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00771 | 0.50 | 0.00432 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 24.62 | 24.62 | 7.37 | 7.37 | 24.6237 | 11.7127 | 24.6237 | 0.4757 | 0.3000 |
FLR_3_DOAS | 20.27 | 2.05 | 4.65 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 5983.048 | 5983.048 | 1.248186 | 0.00005234 | 124.766 | 12/21 00:10:00 | 12/21 00:10:00 | 5983.05 | 5983.05 | 1.248186 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 6016.67 | 6016.67 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3105.021 | 3105.021 | 0.119564 | 0.00002716 | 84.739 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3105.02 | 3105.02 | 0.119564 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00750002 | 44.0536 | 2532.51 | 0.00 | 3120.42 | 3120.42 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1513.029 | 1513.029 | 0.133992 | 0.00001324 | 33.954 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1513.03 | 1513.03 | 0.133992 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00744822 | 43.7518 | 871.43 | 0.00 | 1521.22 | 1521.22 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2099.480 | 2099.480 | 0.090908 | 0.00001837 | 54.921 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2099.48 | 2099.48 | 0.090908 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00734060 | 43.1271 | 1664.27 | 0.00 | 2110.02 | 2110.02 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1372.782 | 1372.782 | 0.084510 | 0.00001201 | 32.740 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1372.78 | 1372.78 | 0.084510 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00734509 | 43.1531 | 968.20 | 0.00 | 1380.07 | 1380.07 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7469.371 | 7469.371 | 1.093495 | 0.00006535 | 159.278 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7469.37 | 7469.37 | 1.093495 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00733159 | 43.0758 | 2235.00 | 0.00 | 7511.03 | 7511.03 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 10999.384 | 10999.384 | 0.988656 | 0.00009623 | 246.353 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10999.38 | 10999.38 | 0.988656 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00754668 | 44.3240 | 6264.85 | 0.00 | 11058.95 | 11058.95 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 28354.992 | 28354.992 | 2.770104 | 0.00024806 | 628.476 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 28354.99 | 28354.99 | 2.770104 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00747428 | 43.9031 | 15090.20 | 0.00 | 28509.18 | 28509.18 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12290.643 | -999.000 | 1.231962 | 0.00043899 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 12290.64 | 12290.64 | 1.231962 | 21.74 | 14.59 | 0.00847827 | 12.80 | 11.21 | 0.00847827 | 39.12 | 0.00562848 | 18.06 | 0.0000 | 21.11 | 0.00847827 | 49.3821 | 11424.24 | 0.00 | 13524.54 | 13232.05 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5574.352 | 5574.352 | 0.264724 | 0.00004877 | 159.301 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5574.35 | 5574.35 | 0.264724 | 21.11 | 13.48 | 0.00747915 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00747915 | 43.6342 | 5574.49 | 0.00 | 6009.28 | 6009.28 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12203.158 | -999.000 | 1.223193 | 0.00043586 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 12203.16 | 12203.16 | 1.223193 | 21.74 | 14.59 | 0.00847803 | 12.80 | 11.21 | 0.00847803 | 38.94 | 0.00562821 | 18.00 | 0.0000 | 21.11 | 0.00847803 | 49.3807 | 11342.93 | 0.00 | 13428.32 | 13138.34 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5578.911 | 5578.911 | 0.264940 | 0.00004881 | 159.431 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5578.91 | 5578.91 | 0.264940 | 21.11 | 13.48 | 0.00747955 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00747955 | 43.6366 | 5579.05 | 0.00 | 6014.19 | 6014.19 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 67429.052 | -999.000 | 6.759412 | 0.00240836 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | unknown | 7/21 14:30:00 | 67429.05 | 67429.05 | 6.759412 | 21.74 | 14.54 | 0.00841720 | 12.80 | 11.15 | 0.00841720 | 40.80 | 0.00563111 | 18.58 | 0.0000 | 21.11 | 0.00841720 | 49.0308 | 62682.35 | 0.00 | 74256.87 | 74256.87 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 32041.756 | 32041.756 | 1.521684 | 0.00028032 | 915.658 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 32041.76 | 32041.76 | 1.521684 | 21.11 | 13.51 | 0.00751429 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00751429 | 43.8357 | 32042.15 | 0.00 | 34541.96 | 34541.96 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 75441.697 | -999.000 | 7.298255 | 0.00269455 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | 7/21 15:40:00 | 75441.70 | 73394.59 | 7.298255 | 21.74 | 14.72 | 0.00862989 | 12.80 | 11.23 | 0.00850000 | 40.27 | 0.00563027 | 18.42 | 0.0000 | 21.11 | 0.00862989 | 50.2548 | 67673.90 | 0.00 | 82867.63 | 78375.83 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 32145.823 | 32145.823 | 1.526626 | 0.00028123 | 918.631 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 32145.82 | 32145.82 | 1.526626 | 21.11 | 13.51 | 0.00751554 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00751554 | 43.8429 | 32146.22 | 0.00 | 34654.15 | 34654.15 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10737.518 | -999.000 | 1.076290 | 0.00038351 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | 7/21 10:30:00 | 10737.52 | 10737.52 | 1.076290 | 21.74 | 14.59 | 0.00847403 | 12.80 | 11.21 | 0.00847403 | 36.74 | 0.00562481 | 17.31 | 0.0000 | 21.11 | 0.00847403 | 49.3577 | 9980.68 | 0.00 | 11816.13 | 11567.50 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5564.485 | 5564.485 | 0.264255 | 0.00004868 | 159.019 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5564.49 | 5564.49 | 0.264255 | 21.11 | 13.48 | 0.00747836 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00747836 | 43.6297 | 5564.63 | 0.00 | 5998.64 | 5998.64 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10662.895 | -999.000 | 1.068810 | 0.00038085 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | 7/21 10:20:00 | 10662.90 | 10662.90 | 1.068810 | 21.74 | 14.59 | 0.00847374 | 12.80 | 11.21 | 0.00847374 | 36.41 | 0.00562429 | 17.20 | 0.0000 | 21.11 | 0.00847374 | 49.3560 | 9911.32 | 0.00 | 11734.05 | 11487.63 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5569.047 | 5569.047 | 0.264472 | 0.00004872 | 159.149 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5569.05 | 5569.05 | 0.264472 | 21.11 | 13.48 | 0.00747876 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00747876 | 43.6320 | 5569.19 | 0.00 | 6003.56 | 6003.56 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12282.384 | 12282.384 | 0.694574 | 0.00010745 | 298.397 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12282.38 | 12282.38 | 0.694574 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00759153 | 44.5832 | 8955.58 | 0.00 | 12346.31 | 12346.31 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3263.694 | -999.000 | 0.327138 | 0.00011657 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3263.69 | 3263.69 | 0.327138 | 21.74 | 14.59 | 0.00847948 | 12.80 | 11.21 | 0.00847948 | 39.12 | 0.00562848 | 18.06 | 0.0000 | 21.11 | 0.00847948 | 49.3890 | 3033.62 | 0.00 | 3591.29 | 3513.03 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1686.869 | 1686.869 | 0.080109 | 0.00001476 | 48.204 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1686.87 | 1686.87 | 0.080109 | 21.11 | 13.55 | 0.00755879 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00755879 | 44.0933 | 1686.91 | 0.00 | 1818.48 | 1818.48 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3238.007 | -999.000 | 0.324563 | 0.00011565 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3238.01 | 3238.01 | 0.324563 | 21.74 | 14.59 | 0.00847924 | 12.80 | 11.21 | 0.00847924 | 38.94 | 0.00562821 | 18.00 | 0.0000 | 21.11 | 0.00847924 | 49.3877 | 3009.75 | 0.00 | 3563.04 | 3485.50 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1687.407 | 1687.407 | 0.080134 | 0.00001476 | 48.220 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1687.41 | 1687.41 | 0.080134 | 21.11 | 13.55 | 0.00755894 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00755894 | 44.0942 | 1687.45 | 0.00 | 1819.06 | 1819.06 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 14455.001 | -999.000 | 1.433110 | 0.00051629 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | unknown | 7/21 14:30:00 | 14455.00 | 14333.13 | 1.433110 | 21.74 | 14.64 | 0.00853960 | 12.80 | 11.23 | 0.00850000 | 40.80 | 0.00563111 | 18.58 | 0.0000 | 21.11 | 0.00853960 | 49.7354 | 13289.03 | 0.00 | 15895.51 | 15357.23 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8101.099 | 8101.099 | 0.384721 | 0.00007087 | 231.496 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8101.10 | 8101.10 | 0.384721 | 21.11 | 13.57 | 0.00757486 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00757486 | 44.1855 | 8101.26 | 0.00 | 8733.19 | 8733.19 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13889.131 | 13889.131 | 1.735282 | 0.00012151 | 300.092 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 13889.13 | 13889.13 | 1.735282 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00766179 | 44.9912 | 5576.86 | 0.00 | 13966.28 | 13966.28 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14006.534 | 14006.534 | 1.735158 | 0.00012254 | 302.863 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 14006.53 | 14006.53 | 1.735158 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00766817 | 45.0283 | 5694.87 | 0.00 | 14084.32 | 14084.32 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 5373.310 | 5373.310 | 0.752634 | 0.00004701 | 114.975 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 5373.31 | 5373.31 | 0.752634 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00646765 | 38.0577 | 1778.28 | 0.00 | 5403.25 | 5403.25 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7135.322 | 7135.322 | 0.274740 | 0.00006242 | 194.735 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7135.32 | 7135.32 | 0.274740 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00771176 | 45.2809 | 5819.14 | 0.00 | 7170.71 | 7170.71 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 580553.633 | -999.000 | 24.623749 | 0.02073603 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 580553.63 | 580553.63 | 24.623749 | 31.95 | 17.40 | 0.00770111 | 10.79 | 9.60 | 0.00770111 | 40.80 | 0.00563111 | 18.58 | 47.3586 | 23.99 | 0.00951785 | 46.4590 | 307475.36 | 0.00 | 619794.71 | 605025.79 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 131459.725 | 131459.725 | 7.387125 | 0.00115007 | 2306.644 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 131459.73 | 131459.73 | 7.387125 | 0.50 | 0.50 | 0.00431558 | 16.70 | 12.29 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 157.8620 | 21.56 | 0.00772561 | 43.8223 | 56823.14 | 0.00 | 128116.02 | 128116.02 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 65945.855 | -999.000 | 2.051317 | 0.00235543 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 65945.86 | 65945.86 | 2.051317 | 40.80 | 18.58 | 0.00563111 | 11.84 | 7.85 | 0.00563111 | 40.80 | 0.00563111 | 18.58 | 99.9965 | 21.11 | 0.00852702 | 49.6629 | 187295.36 | 0.00 | 66000.58 | 66000.58 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 10951.444 | 10951.444 | 0.615395 | 0.00009581 | 192.158 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10951.44 | 10951.44 | 0.615395 | 0.50 | 0.50 | 0.00431558 | 16.70 | 12.29 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 333.3216 | 21.11 | 0.00751518 | 43.8408 | 97951.35 | 0.00 | 10672.89 | 10672.89 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 5983.048 | 5983.048 | 1.248186 | 0.00005234 | 124.766 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 1.6570 | 1.690390 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 5983.05 | 5983.05 | 1.0000 | 1.36450977 | 1.248186 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.05233697 | 60.00 | 32.22 | 27.78 | 0.000 | 5983.05 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 6016.67 | 6016.67 | 1.36450977 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3105.021 | 3105.021 | 0.119564 | 0.00002716 | 84.739 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 0.8600 | 0.877262 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3105.02 | 3105.02 | 1.0000 | 0.13070618 | 0.119564 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.02716131 | 60.00 | 32.22 | 27.78 | 0.000 | 3105.02 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00750002 | 21.00 | 0.00750002 | 44.0536 | 2532.51 | 0.00 | 3120.42 | 3120.42 | 0.13070618 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60808.3 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1513.029 | 1513.029 | 0.133992 | 0.00001324 | 33.954 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 0.4190 | 0.427476 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1513.03 | 1513.03 | 1.0000 | 0.14647938 | 0.133992 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01323529 | 60.00 | 32.22 | 27.78 | 0.000 | 1513.03 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00744822 | 21.00 | 0.00744822 | 43.7518 | 871.43 | 0.00 | 1521.22 | 1521.22 | 0.14647938 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.78 | 16.94 | 0.00800000 | 47319.9 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2099.480 | 2099.480 | 0.090908 | 0.00001837 | 54.921 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 0.5815 | 0.593166 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2099.48 | 2099.48 | 1.0000 | 0.09937956 | 0.090908 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01836530 | 60.00 | 32.22 | 27.78 | 0.000 | 2099.48 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00734060 | 21.00 | 0.00734060 | 43.1271 | 1664.27 | 0.00 | 2110.02 | 2110.02 | 0.09937956 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.42 | 20.41 | 0.00800000 | 58166.7 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1372.782 | 1372.782 | 0.084510 | 0.00001201 | 32.740 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 0.3802 | 0.387852 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1372.78 | 1372.78 | 1.0000 | 0.09238572 | 0.084510 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01200847 | 60.00 | 32.22 | 27.78 | 0.000 | 1372.78 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00734509 | 21.00 | 0.00734509 | 43.1531 | 968.20 | 0.00 | 1380.07 | 1380.07 | 0.09238572 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.25 | 18.45 | 0.00800000 | 51872.8 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7469.371 | 7469.371 | 1.093495 | 0.00006535 | 159.278 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 2.0687 | 2.110321 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7469.37 | 7469.37 | 1.0000 | 1.19540197 | 1.093495 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.06533865 | 60.00 | 32.22 | 27.78 | 0.000 | 7469.37 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00733159 | 21.00 | 0.00733159 | 43.0758 | 2235.00 | 0.00 | 7511.03 | 7511.03 | 1.19540197 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.76 | 15.50 | 0.00800000 | 43218.0 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10999.384 | 10999.384 | 0.988656 | 0.00009623 | 246.353 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 3.0463 | 3.107656 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10999.38 | 10999.38 | 1.0000 | 1.08079343 | 0.988656 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.09621760 | 60.00 | 32.22 | 27.78 | 0.000 | 10999.38 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00754668 | 21.00 | 0.00754668 | 44.3240 | 6264.85 | 0.00 | 11058.95 | 11058.95 | 1.08079343 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.63 | 16.89 | 0.00800000 | 47167.0 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 28354.992 | 28354.992 | 2.770104 | 0.00024806 | 628.476 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 7.8531 | 8.011136 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 28354.99 | 28354.99 | 1.0000 | 3.02826218 | 2.770104 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.24803654 | 60.00 | 32.22 | 27.78 | 0.000 | 28354.99 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00747428 | 21.00 | 0.00747428 | 43.9031 | 15090.20 | 0.00 | 28509.18 | 28509.18 | 3.02826218 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.83 | 16.61 | 0.00800000 | 46349.1 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12290.643 | -999.000 | 1.231962 | 0.00043899 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6007 | 1004.8586 | 1.0932 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.231962 | 1.34677333 | 4197.9300 | 999.8980 | 30.57897620 | 13.37 | 6.70 | 6.67 | 856217.24 | 1.4355 | 1.435432 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 12290.64 | 12290.64 | 1.0000 | 1.34677333 | 1.231962 | 21.74 | 14.59 | 0.00847827 | 43393.3 | 12.80 | 11.21 | 0.00847827 | 34267.3 | 0.43894033 | 6.70 | 13.37 | 6.67 | 0.000 | 12290.64 | 39.12 | 0.00562848 | 18.06 | 0.00000000 | 0.0000 | 21.11 | 0.00847827 | 21.11 | 0.00847827 | 49.3821 | 11424.24 | 0.00 | 13524.54 | 13232.05 | 1.34677333 | 21.74 | 15.56 | 0.00847827 | 43393.3 | 12.12 | 11.71 | 0.00839221 | 33351.1 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5574.352 | 5574.352 | 0.264724 | 0.00004877 | 159.301 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.231962 | 1.34677333 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 1.5439 | 1.574922 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5574.35 | 5574.35 | 1.0000 | 0.28939456 | 0.264724 | 21.11 | 13.48 | 0.00747915 | 40210.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04876189 | 60.00 | 32.22 | 27.78 | 0.000 | 5574.35 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00747915 | 21.11 | 0.00747915 | 43.6342 | 5574.49 | 0.00 | 6009.28 | 6009.28 | 0.28939456 | 16.60 | 12.64 | 0.00747915 | 35616.1 | 36.98 | 19.88 | 0.00747915 | 56381.0 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12203.158 | -999.000 | 1.223193 | 0.00043586 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6002 | 1004.8586 | 1.0932 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.223193 | 1.33718740 | 4197.9300 | 999.8980 | 30.57897620 | 13.37 | 6.70 | 6.67 | 856217.24 | 1.4252 | 1.425214 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 12203.16 | 12203.16 | 1.0000 | 1.33718740 | 1.223193 | 21.74 | 14.59 | 0.00847803 | 43392.7 | 12.80 | 11.21 | 0.00847803 | 34266.7 | 0.43581592 | 6.70 | 13.37 | 6.67 | 0.000 | 12203.16 | 38.94 | 0.00562821 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00847803 | 21.11 | 0.00847803 | 49.3807 | 11342.93 | 0.00 | 13428.32 | 13138.34 | 1.33718740 | 21.74 | 15.56 | 0.00847803 | 43392.7 | 12.11 | 11.71 | 0.00839210 | 33350.5 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5578.911 | 5578.911 | 0.264940 | 0.00004881 | 159.431 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.223193 | 1.33718740 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 1.5451 | 1.576210 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5578.91 | 5578.91 | 1.0000 | 0.28963122 | 0.264940 | 21.11 | 13.48 | 0.00747955 | 40211.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04880177 | 60.00 | 32.22 | 27.78 | 0.000 | 5578.91 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00747955 | 21.11 | 0.00747955 | 43.6366 | 5579.05 | 0.00 | 6014.19 | 6014.19 | 0.28963122 | 16.60 | 12.64 | 0.00747955 | 35617.1 | 36.98 | 19.88 | 0.00747955 | 56382.1 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 67429.052 | -999.000 | 6.759412 | 0.00240836 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4871 | 1004.8586 | 1.0932 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.759412 | 7.38935015 | 4197.9300 | 999.8980 | 30.57897620 | 13.37 | 6.70 | 6.67 | 856217.24 | 7.8752 | 7.875080 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | unknown | unknown | unknown | 7/21 14:30:00 | Sensible | 67429.05 | 67429.05 | 1.0000 | 7.38935015 | 6.759412 | 21.74 | 14.54 | 0.00841720 | 43238.3 | 12.80 | 11.15 | 0.00841720 | 34113.1 | 2.40811886 | 6.70 | 13.37 | 6.67 | 0.000 | 67429.05 | 40.80 | 0.00563111 | 18.58 | 0.00000000 | 0.0000 | 21.11 | 0.00841720 | 21.11 | 0.00841720 | 49.0308 | 62682.35 | 0.00 | 74256.87 | 74256.87 | 7.38935015 | 21.74 | 15.50 | 0.00841720 | 43238.3 | 11.89 | 11.64 | 0.00841720 | 33189.1 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32041.756 | 32041.756 | 1.521684 | 0.00028032 | 915.658 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.759412 | 7.38935015 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 8.8742 | 9.052758 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 32041.76 | 32041.76 | 1.0000 | 1.66349601 | 1.521684 | 21.11 | 13.51 | 0.00751429 | 40300.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.28028666 | 60.00 | 32.22 | 27.78 | 0.000 | 32041.76 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00751429 | 21.11 | 0.00751429 | 43.8357 | 32042.15 | 0.00 | 34541.96 | 34541.96 | 1.66349601 | 16.60 | 12.68 | 0.00751429 | 35705.0 | 36.98 | 19.91 | 0.00751429 | 56469.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 75441.697 | -999.000 | 7.298255 | 0.00269455 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8825 | 1004.8586 | 1.0932 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.298255 | 7.97841033 | 4197.9300 | 999.8980 | 30.57897620 | 13.37 | 6.70 | 6.67 | 856217.24 | 8.8110 | 8.810882 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | unknown | unknown | 7/21 15:40:00 | Sensible | 75441.70 | 73394.59 | 1.0000 | 7.97841033 | 7.298255 | 21.74 | 14.72 | 0.00862989 | 43777.9 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 2.69427744 | 6.70 | 13.37 | 6.67 | 0.000 | 75441.70 | 40.27 | 0.00563027 | 18.42 | 0.00000000 | 0.0000 | 21.11 | 0.00862989 | 21.11 | 0.00862989 | 50.2548 | 67673.90 | 0.00 | 82867.63 | 78375.83 | 7.97841033 | 21.74 | 15.69 | 0.00862989 | 43777.9 | 12.12 | 11.72 | 0.00840679 | 33391.4 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32145.823 | 32145.823 | 1.526626 | 0.00028123 | 918.631 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.298255 | 7.97841033 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 8.9030 | 9.082160 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 32145.82 | 32145.82 | 1.0000 | 1.66889878 | 1.526626 | 21.11 | 13.51 | 0.00751554 | 40303.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.28119699 | 60.00 | 32.22 | 27.78 | 0.000 | 32145.82 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00751554 | 21.11 | 0.00751554 | 43.8429 | 32146.22 | 0.00 | 34654.15 | 34654.15 | 1.66889878 | 16.60 | 12.68 | 0.00751554 | 35708.2 | 36.98 | 19.91 | 0.00751554 | 56472.9 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10737.518 | -999.000 | 1.076290 | 0.00038351 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5928 | 1004.8586 | 1.0932 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.076290 | 1.17659354 | 4197.9300 | 999.8980 | 30.57897620 | 13.37 | 6.70 | 6.67 | 856217.24 | 1.2541 | 1.254041 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | unknown | unknown | 7/21 10:30:00 | Sensible | 10737.52 | 10737.52 | 1.0000 | 1.17659354 | 1.076290 | 21.74 | 14.59 | 0.00847403 | 43382.6 | 12.80 | 11.21 | 0.00847403 | 34256.6 | 0.38347299 | 6.70 | 13.37 | 6.67 | 0.000 | 10737.52 | 36.74 | 0.00562481 | 17.31 | 0.00000000 | 0.0000 | 21.11 | 0.00847403 | 21.11 | 0.00847403 | 49.3577 | 9980.68 | 0.00 | 11816.13 | 11567.50 | 1.17659354 | 21.74 | 15.55 | 0.00847403 | 43382.6 | 12.11 | 11.70 | 0.00839029 | 33339.9 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5564.485 | 5564.485 | 0.264255 | 0.00004868 | 159.019 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.076290 | 1.17659354 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 1.5411 | 1.572134 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5564.49 | 5564.49 | 1.0000 | 0.28888231 | 0.264255 | 21.11 | 13.48 | 0.00747836 | 40208.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04867558 | 60.00 | 32.22 | 27.78 | 0.000 | 5564.49 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00747836 | 21.11 | 0.00747836 | 43.6297 | 5564.63 | 0.00 | 5998.64 | 5998.64 | 0.28888231 | 16.60 | 12.64 | 0.00747836 | 35614.0 | 36.98 | 19.88 | 0.00747836 | 56379.0 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10662.895 | -999.000 | 1.068810 | 0.00038085 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5923 | 1004.8586 | 1.0932 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.068810 | 1.16841700 | 4197.9300 | 999.8980 | 30.57897620 | 13.37 | 6.70 | 6.67 | 856217.24 | 1.2453 | 1.245326 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | unknown | unknown | 7/21 10:20:00 | Sensible | 10662.90 | 10662.90 | 1.0000 | 1.16841700 | 1.068810 | 21.74 | 14.59 | 0.00847374 | 43381.8 | 12.80 | 11.21 | 0.00847374 | 34255.9 | 0.38080795 | 6.70 | 13.37 | 6.67 | 0.000 | 10662.90 | 36.41 | 0.00562429 | 17.20 | 0.00000000 | 0.0000 | 21.11 | 0.00847374 | 21.11 | 0.00847374 | 49.3560 | 9911.32 | 0.00 | 11734.05 | 11487.63 | 1.16841700 | 21.74 | 15.55 | 0.00847374 | 43381.8 | 12.11 | 11.70 | 0.00839016 | 33339.1 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5569.047 | 5569.047 | 0.264472 | 0.00004872 | 159.149 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.068810 | 1.16841700 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 1.5424 | 1.573423 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5569.05 | 5569.05 | 1.0000 | 0.28911910 | 0.264472 | 21.11 | 13.48 | 0.00747876 | 40209.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04871548 | 60.00 | 32.22 | 27.78 | 0.000 | 5569.05 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00747876 | 21.11 | 0.00747876 | 43.6320 | 5569.19 | 0.00 | 6003.56 | 6003.56 | 0.28911910 | 16.60 | 12.64 | 0.00747876 | 35615.1 | 36.98 | 19.88 | 0.00747876 | 56380.1 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12282.384 | 12282.384 | 0.694574 | 0.00010745 | 298.397 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 3.4017 | 3.470142 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 12282.38 | 12282.38 | 1.0000 | 0.75930398 | 0.694574 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.10744069 | 60.00 | 32.22 | 27.78 | 0.000 | 12282.38 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00759153 | 21.00 | 0.00759153 | 44.5832 | 8955.58 | 0.00 | 12346.31 | 12346.31 | 0.75930398 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.55 | 18.87 | 0.00800000 | 53194.8 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3263.694 | -999.000 | 0.327138 | 0.00011657 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6029 | 1004.8586 | 1.0932 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.327138 | 0.35762556 | 4197.9300 | 999.8980 | 30.57897620 | 13.37 | 6.70 | 6.67 | 856217.24 | 0.3812 | 0.381169 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3263.69 | 3263.69 | 1.0000 | 0.35762556 | 0.327138 | 21.74 | 14.59 | 0.00847948 | 43396.4 | 12.80 | 11.21 | 0.00847948 | 34270.4 | 0.11655754 | 6.70 | 13.37 | 6.67 | 0.000 | 3263.69 | 39.12 | 0.00562848 | 18.06 | 0.00000000 | 0.0000 | 21.11 | 0.00847948 | 21.11 | 0.00847948 | 49.3890 | 3033.62 | 0.00 | 3591.29 | 3513.03 | 0.35762556 | 21.74 | 15.56 | 0.00847948 | 43396.4 | 12.12 | 11.71 | 0.00839275 | 33354.3 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1686.869 | 1686.869 | 0.080109 | 0.00001476 | 48.204 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.327138 | 0.35762556 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 0.4672 | 0.476591 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1686.87 | 1686.87 | 1.0000 | 0.08757439 | 0.080109 | 21.11 | 13.55 | 0.00755879 | 40413.1 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01475596 | 60.00 | 32.22 | 27.78 | 0.000 | 1686.87 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00755879 | 21.11 | 0.00755879 | 44.0933 | 1686.91 | 0.00 | 1818.48 | 1818.48 | 0.08757439 | 16.60 | 12.72 | 0.00755879 | 35817.7 | 36.98 | 19.94 | 0.00755879 | 56582.7 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3238.007 | -999.000 | 0.324563 | 0.00011565 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6025 | 1004.8586 | 1.0932 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.324563 | 0.35481094 | 4197.9300 | 999.8980 | 30.57897620 | 13.37 | 6.70 | 6.67 | 856217.24 | 0.3782 | 0.378169 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3238.01 | 3238.01 | 1.0000 | 0.35481094 | 0.324563 | 21.74 | 14.59 | 0.00847924 | 43395.8 | 12.80 | 11.21 | 0.00847924 | 34269.8 | 0.11564015 | 6.70 | 13.37 | 6.67 | 0.000 | 3238.01 | 38.94 | 0.00562821 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00847924 | 21.11 | 0.00847924 | 49.3877 | 3009.75 | 0.00 | 3563.04 | 3485.50 | 0.35481094 | 21.74 | 15.56 | 0.00847924 | 43395.8 | 12.12 | 11.71 | 0.00839264 | 33353.7 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1687.407 | 1687.407 | 0.080134 | 0.00001476 | 48.220 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.324563 | 0.35481094 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 0.4673 | 0.476743 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1687.41 | 1687.41 | 1.0000 | 0.08760232 | 0.080134 | 21.11 | 13.55 | 0.00755894 | 40413.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01476066 | 60.00 | 32.22 | 27.78 | 0.000 | 1687.41 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00755894 | 21.11 | 0.00755894 | 44.0942 | 1687.45 | 0.00 | 1819.06 | 1819.06 | 0.08760232 | 16.60 | 12.72 | 0.00755894 | 35818.1 | 36.98 | 19.94 | 0.00755894 | 56583.1 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14455.001 | -999.000 | 1.433110 | 0.00051629 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7147 | 1004.8586 | 1.0932 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.433110 | 1.56666772 | 4197.9300 | 999.8980 | 30.57897620 | 13.37 | 6.70 | 6.67 | 856217.24 | 1.6882 | 1.688208 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | unknown | unknown | unknown | 7/21 14:30:00 | Sensible | 14455.00 | 14333.13 | 1.0000 | 1.56666772 | 1.433110 | 21.74 | 14.64 | 0.00853960 | 43548.8 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.51623682 | 6.70 | 13.37 | 6.67 | 0.000 | 14455.00 | 40.80 | 0.00563111 | 18.58 | 0.00000000 | 0.0000 | 21.11 | 0.00853960 | 21.11 | 0.00853960 | 49.7354 | 13289.03 | 0.00 | 15895.51 | 15357.23 | 1.56666772 | 21.74 | 15.61 | 0.00853960 | 43548.8 | 12.14 | 11.73 | 0.00840344 | 33402.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8101.099 | 8101.099 | 0.384721 | 0.00007087 | 231.496 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.433110 | 1.56666772 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 2.2436 | 2.288804 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8101.10 | 8101.10 | 1.0000 | 0.42057465 | 0.384721 | 21.11 | 13.57 | 0.00757486 | 40454.1 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.07086472 | 60.00 | 32.22 | 27.78 | 0.000 | 8101.10 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00757486 | 21.11 | 0.00757486 | 44.1855 | 8101.26 | 0.00 | 8733.19 | 8733.19 | 0.42057465 | 16.60 | 12.74 | 0.00757486 | 35858.4 | 36.98 | 19.95 | 0.00757486 | 56623.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13889.131 | 13889.131 | 1.735282 | 0.00012151 | 300.092 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 3.8467 | 3.924096 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 13889.13 | 13889.13 | 1.0000 | 1.89700072 | 1.735282 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.12149578 | 60.00 | 32.22 | 27.78 | 0.000 | 13889.13 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00766179 | 21.00 | 0.00766179 | 44.9912 | 5576.86 | 0.00 | 13966.28 | 13966.28 | 1.89700072 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.82 | 15.89 | 0.00800000 | 44297.0 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14006.534 | 14006.534 | 1.735158 | 0.00012254 | 302.863 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 3.8792 | 3.957266 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 14006.53 | 14006.53 | 1.0000 | 1.89686485 | 1.735158 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.12252277 | 60.00 | 32.22 | 27.78 | 0.000 | 14006.53 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00766817 | 21.00 | 0.00766817 | 45.0283 | 5694.87 | 0.00 | 14084.32 | 14084.32 | 1.89686485 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.88 | 15.91 | 0.00800000 | 44359.8 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5373.310 | 5373.310 | 0.752634 | 0.00004701 | 114.975 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 1.4882 | 1.518121 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 5373.31 | 5373.31 | 1.0000 | 0.82277464 | 0.752634 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04700326 | 60.00 | 32.22 | 27.78 | 0.000 | 5373.31 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.42 | 0.00646765 | 21.00 | 0.00646765 | 38.0577 | 1778.28 | 0.00 | 5403.25 | 5403.25 | 0.82277464 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.04 | 15.61 | 0.00800000 | 43501.8 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7135.322 | 7135.322 | 0.274740 | 0.00006242 | 194.735 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 1.9762 | 2.015943 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7135.32 | 7135.32 | 1.0000 | 0.30034434 | 0.274740 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.06241655 | 60.00 | 32.22 | 27.78 | 0.000 | 7135.32 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00771176 | 21.00 | 0.00771176 | 45.2809 | 5819.14 | 0.00 | 7170.71 | 7170.71 | 0.30034434 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60809.7 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 580553.633 | -999.000 | 24.623749 | 0.02073603 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1560 | 1004.8586 | 1.0932 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.623749 | 26.91854002 | 4197.9300 | 999.8980 | 30.57897620 | 13.37 | 6.70 | 6.67 | 856217.24 | 67.8045 | 67.804478 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 580553.63 | 580553.63 | 1.0000 | 26.91854002 | 24.623749 | 31.95 | 17.40 | 0.00770111 | 51822.6 | 10.79 | 9.60 | 0.00770111 | 30255.6 | 20.73391532 | 6.70 | 13.37 | 6.67 | 55172.923 | 525380.71 | 40.80 | 0.00563111 | 18.58 | 11.66146000 | 47.3586 | 23.99 | 0.00956338 | 23.99 | 0.00951785 | 46.4590 | 307475.36 | 0.00 | 619794.71 | 605025.79 | 26.91854002 | 31.95 | 18.44 | 0.00770111 | 51822.6 | 9.90 | 9.80 | 0.00748333 | 28797.8 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 131459.725 | 131459.725 | 7.387125 | 0.00115007 | 2306.644 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.623749 | 26.91854002 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 36.4086 | 37.141317 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 131459.73 | 131459.73 | 1.0000 | 8.07556201 | 7.387125 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 1.14994970 | 60.00 | 32.22 | 27.78 | 0.000 | 131459.73 | 0.50 | 0.00431558 | 0.50 | 11.66146000 | 157.8620 | 18.53 | 0.00761824 | 21.56 | 0.00772561 | 43.8223 | 56823.14 | 0.00 | 128116.02 | 128116.02 | 8.07556201 | 2.80 | 2.38 | 0.00431558 | 13629.0 | 18.46 | 10.16 | 0.00431558 | 29493.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 65945.855 | -999.000 | 2.051317 | 0.00235543 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.3079 | 1004.8586 | 1.0932 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.24240930 | 4197.9300 | 999.8980 | 30.57897620 | 13.37 | 6.70 | 6.67 | 856217.24 | 7.7020 | 7.702000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 65945.86 | 65945.86 | 1.0000 | 2.24248814 | 2.051317 | 40.80 | 18.58 | 0.00563111 | 55507.6 | 11.84 | 7.85 | 0.00563111 | 26100.2 | 2.35519288 | 6.70 | 13.37 | 6.67 | 2195.006 | 63750.85 | 40.80 | 0.00563111 | 18.58 | 2.05124512 | 99.9965 | 21.11 | 0.00851626 | 21.11 | 0.00852702 | 49.6629 | 187295.36 | 0.00 | 66000.58 | 66000.58 | 2.24248814 | 40.80 | 19.66 | 0.00563111 | 55507.6 | 11.81 | 8.61 | 0.00563111 | 26075.8 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 10951.444 | 10951.444 | 0.615395 | 0.00009581 | 192.158 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.24240930 | 4197.9300 | 999.8980 | 3.09614682 | 54.44 | 82.22 | 27.78 | 361067.98 | 3.0331 | 3.094111 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10951.44 | 10951.44 | 1.0000 | 0.67274644 | 0.615395 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 0.09579823 | 60.00 | 32.22 | 27.78 | 0.000 | 10951.44 | 0.50 | 0.00431558 | 0.50 | 2.05124512 | 333.3216 | 21.11 | 0.00751321 | 21.11 | 0.00751518 | 43.8408 | 97951.35 | 0.00 | 10672.89 | 10672.89 | 0.67274644 | 2.80 | 2.38 | 0.00431558 | 13629.0 | 18.46 | 10.16 | 0.00431558 | 29493.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 11.66 | 24.62 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2062.33 | 5632.33 | 513.50 |
RETAIL_1_FLR_1 | 3492.67 | 3685.67 | 601.33 |
RETAIL_2_FLR_1 | 2291.67 | 4981.33 | 635.00 |
MECH_FLR_1 | 1891.83 | 5647.17 | 126.17 |
STORAGE_FLR_1 | 1196.50 | 6750.67 | 250.50 |
LAUNDRY_FLR_1 | 8724.00 | 4256.67 | 4256.67 |
CAFE_FLR_1 | 3521.83 | 4638.33 | 928.83 |
LOBBY_FLR_1 | 2772.00 | 4526.17 | 945.67 |
ROOM_1_FLR_3 | 407.67 | 8101.00 | 301.00 |
ROOM_2_FLR_3 | 798.33 | 8227.83 | 732.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 675.50 | 8760.00 | 675.50 |
ROOM_5_FLR_3 | 411.83 | 7999.50 | 290.17 |
ROOM_6_FLR_3 | 707.50 | 8091.33 | 654.67 |
CORRIDOR_FLR_3 | 1843.33 | 6700.50 | 777.00 |
ROOM_1_FLR_6 | 966.00 | 7966.50 | 743.83 |
ROOM_2_FLR_6 | 1515.67 | 8102.00 | 1364.50 |
ROOM_3_MULT9_FLR_6 | 270.00 | 7956.00 | 183.33 |
BANQUET_FLR_6 | 3286.17 | 4551.67 | 942.83 |
DINING_FLR_6 | 4033.33 | 3471.67 | 927.50 |
KITCHEN_FLR_6 | 8748.50 | 6698.50 | 6698.50 |
CORRIDOR_FLR_6 | 2091.17 | 5308.83 | 498.50 |
Facility | 8760.00 | 8760.00 | 7492.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 65.50 | 0.00 | 65.50 |
CAFE_FLR_1 | 0.00 | 0.17 | 0.00 | 0.17 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 12.67 | 0.00 | 12.67 |
ROOM_2_FLR_3 | 0.00 | 10.83 | 0.00 | 10.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 4.83 | 0.00 | 4.83 |
ROOM_5_FLR_3 | 0.00 | 8.00 | 0.00 | 8.00 |
ROOM_6_FLR_3 | 0.00 | 7.50 | 0.00 | 7.50 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 16.33 | 0.00 | 16.33 |
ROOM_2_FLR_6 | 0.00 | 15.00 | 0.00 | 15.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 19.17 | 0.00 | 19.17 |
BANQUET_FLR_6 | 0.00 | 2.33 | 0.00 | 2.33 |
DINING_FLR_6 | 0.00 | 4.67 | 0.00 | 4.67 |
KITCHEN_FLR_6 | 0.00 | 72.83 | 0.00 | 72.83 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 114.67 | 0.00 | 114.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.66 | 106.50 | 4826.41 | 1.001 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.27 | 10.83 | 265.76 | 2.043 | 0.241 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.26 | 12.54 | 307.76 | 1.505 | 0.080 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.568 | 0.090 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.712 | 0.089 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 19.767 | 0.258 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.39 | 142.30 | 748.35 | 4.262 | 0.189 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.59 | 422.44 | 5183.56 | 1.824 | 0.078 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.474 | 0.310 | 0.000 | 0.052 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.474 | 0.310 | 0.000 | 0.048 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.537 | 0.138 | 0.000 | 0.076 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.474 | 0.310 | 0.000 | 0.052 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.474 | 0.310 | 0.000 | 0.048 |
CORRIDOR_FLR_3 | 12.13 | 20.96 | 1186.91 | 0.514 | 0.038 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.474 | 0.310 | 0.000 | 0.060 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.473 | 0.310 | 0.000 | 0.056 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.538 | 0.253 | 0.000 | 0.097 |
BANQUET_FLR_6 | 144.69 | 249.90 | 1010.89 | 5.585 | 0.090 | 0.000 | 0.000 |
DINING_FLR_6 | 144.69 | 249.90 | 1010.89 | 5.692 | 0.090 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.88 | 22.24 | 314.87 | 20.878 | 0.259 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.84 | 22.18 | 1256.16 | 0.901 | 0.063 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.66 | 106.50 | 4826.41 | 0.528 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.27 | 10.83 | 265.76 | 0.836 | 0.004 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.26 | 12.54 | 307.76 | 0.846 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.262 | 0.002 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.420 | 0.002 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.86 | 8.40 | 309.22 | 7.268 | 0.004 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.39 | 142.30 | 748.35 | 2.566 | 0.003 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.59 | 422.44 | 5183.56 | 1.092 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.464 | 0.005 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.463 | 0.005 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.526 | 0.002 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.464 | 0.005 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.464 | 0.005 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.13 | 20.96 | 1186.91 | 0.275 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.463 | 0.005 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.462 | 0.005 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.527 | 0.004 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.69 | 249.90 | 1010.89 | 3.499 | 0.002 | 0.000 | 0.000 |
DINING_FLR_6 | 144.69 | 249.90 | 1010.89 | 3.515 | 0.002 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.88 | 22.24 | 314.87 | 4.918 | 0.004 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.84 | 22.18 | 1256.16 | 0.398 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.66 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.27 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.26 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.86 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.39 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.59 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.13 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.69 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.69 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.88 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.84 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 871.60 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41412831.81 | 0.00 | 41412831.81 | 0.00 | 41412831.81 | 26946214.98 | 225.67 | 42.37 | 8491.97 | 0.00 |
RETAIL_1_FLR_1 | 4658759.87 | 0.00 | 4658759.87 | 549390.10 | 5208149.96 | 2498216.28 | 33.77 | 5.34 | 8720.89 | 0.00 |
RETAIL_2_FLR_1 | 3972935.32 | 0.00 | 3972935.32 | 212065.27 | 4185000.59 | 2892943.94 | 38.38 | 21.19 | 8700.42 | 0.00 |
MECH_FLR_1 | 3174556.49 | 0.00 | 3174556.49 | 501196.32 | 3675752.81 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2303930.01 | 0.00 | 2303930.01 | 289162.67 | 2593092.68 | 1821682.01 | 612.47 | 103.91 | 8043.62 | 0.00 |
LAUNDRY_FLR_1 | 52412269.56 | 0.00 | 52412269.56 | 684357.98 | 53096627.53 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 27376596.26 | 0.00 | 27376596.26 | 1214457.92 | 28591054.18 | 21330615.53 | 545.67 | 117.85 | 8096.48 | 0.00 |
LOBBY_FLR_1 | 81013259.30 | 0.00 | 81013259.30 | 3469983.66 | 84483242.97 | 59728886.00 | 31.51 | 20.29 | 8708.21 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 53343.51 | 2000219.13 | 318881.11 | 2319100.24 | 1946875.62 | 0.00 | 7861.67 | 898.33 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 49707.09 | 1996354.60 | 318856.78 | 2315211.38 | 1946647.51 | 0.00 | 7861.67 | 898.33 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 58650.10 | 26456537.38 | 88971.41 | 26545508.78 | 26397887.27 | 0.00 | 7878.67 | 881.33 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 49478.33 | 26454584.06 | 88995.74 | 26543579.79 | 26405105.73 | 0.00 | 7909.23 | 850.77 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 53497.32 | 2000372.94 | 318881.11 | 2319254.05 | 1946875.62 | 0.00 | 7861.67 | 898.33 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 49886.96 | 1996534.47 | 318856.78 | 2315391.25 | 1946647.51 | 0.00 | 7861.67 | 898.33 | 0.00 |
CORRIDOR_FLR_3 | 20938661.23 | 0.00 | 20938661.23 | 385591.42 | 21324252.65 | 14972100.18 | 41.78 | 29.71 | 8688.51 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 62250.72 | 548969.62 | 318945.54 | 867915.16 | 486718.90 | 0.00 | 7861.67 | 898.33 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 57398.51 | 544060.39 | 318921.20 | 862981.59 | 486661.88 | 0.00 | 7861.67 | 898.33 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 62501.31 | 3189421.72 | 163183.70 | 3352605.42 | 3126920.42 | 0.00 | 7861.67 | 898.33 | 0.00 |
BANQUET_FLR_6 | 48439238.95 | 0.00 | 48439238.95 | 778784.84 | 49218023.79 | 37458366.31 | 271.85 | 131.89 | 8356.26 | 0.00 |
DINING_FLR_6 | 49322937.47 | 0.00 | 49322937.47 | 778784.84 | 50101722.31 | 37458366.31 | 72.16 | 66.89 | 8620.95 | 0.00 |
KITCHEN_FLR_6 | 56268582.80 | 0.00 | 56268582.80 | 697192.99 | 56965775.79 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 9702845.92 | 0.00 | 9702845.92 | 682373.60 | 10385219.51 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.45E+10 | 9725661.32 | 0.45E+10 | 32134041.92 | 0.46E+10 | 0.43E+10 | 763.38 | 7924.11 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3132 | 0.0000 | 1.3132 | 0.0000 | 1.3132 | 0.8545 | 225.67 | 42.37 | 8491.97 |
RETAIL_1_FLR_1 | 0.1477 | 0.0000 | 0.1477 | 0.0174 | 0.1651 | 0.0792 | 33.77 | 5.34 | 8720.89 |
RETAIL_2_FLR_1 | 0.1260 | 0.0000 | 0.1260 | 0.0067 | 0.1327 | 0.0917 | 38.38 | 21.19 | 8700.42 |
MECH_FLR_1 | 0.1007 | 0.0000 | 0.1007 | 0.0159 | 0.1166 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0731 | 0.0000 | 0.0731 | 0.0092 | 0.0822 | 0.0578 | 612.47 | 103.91 | 8043.62 |
LAUNDRY_FLR_1 | 1.6620 | 0.0000 | 1.6620 | 0.0217 | 1.6837 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.8681 | 0.0000 | 0.8681 | 0.0385 | 0.9066 | 0.6764 | 545.67 | 117.85 | 8096.48 |
LOBBY_FLR_1 | 2.5689 | 0.0000 | 2.5689 | 0.1100 | 2.6789 | 1.8940 | 31.51 | 20.29 | 8708.21 |
ROOM_1_FLR_3 | 0.0617 | 0.0017 | 0.0634 | 0.0101 | 0.0735 | 0.0617 | 0.00 | 7861.67 | 898.33 |
ROOM_2_FLR_3 | 0.0617 | 0.0016 | 0.0633 | 0.0101 | 0.0734 | 0.0617 | 0.00 | 7861.67 | 898.33 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0016 | 0.8389 | 0.0028 | 0.8417 | 0.8373 | 0.00 | 7909.23 | 850.77 |
ROOM_5_FLR_3 | 0.0617 | 0.0017 | 0.0634 | 0.0101 | 0.0735 | 0.0617 | 0.00 | 7861.67 | 898.33 |
ROOM_6_FLR_3 | 0.0617 | 0.0016 | 0.0633 | 0.0101 | 0.0734 | 0.0617 | 0.00 | 7861.67 | 898.33 |
CORRIDOR_FLR_3 | 0.6640 | 0.0000 | 0.6640 | 0.0122 | 0.6762 | 0.4748 | 41.78 | 29.71 | 8688.51 |
ROOM_1_FLR_6 | 0.0154 | 0.0020 | 0.0174 | 0.0101 | 0.0275 | 0.0154 | 0.00 | 7861.67 | 898.33 |
ROOM_2_FLR_6 | 0.0154 | 0.0018 | 0.0173 | 0.0101 | 0.0274 | 0.0154 | 0.00 | 7861.67 | 898.33 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0020 | 0.1011 | 0.0052 | 0.1063 | 0.0992 | 0.00 | 7861.67 | 898.33 |
BANQUET_FLR_6 | 1.5360 | 0.0000 | 1.5360 | 0.0247 | 1.5607 | 1.1878 | 271.85 | 131.89 | 8356.26 |
DINING_FLR_6 | 1.5640 | 0.0000 | 1.5640 | 0.0247 | 1.5887 | 1.1878 | 72.16 | 66.89 | 8620.95 |
KITCHEN_FLR_6 | 1.7843 | 0.0000 | 1.7843 | 0.0221 | 1.8064 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3077 | 0.0000 | 0.3077 | 0.0216 | 0.3293 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 80.2532 | 0.1671 | 80.4203 | 0.8045 | 81.2248 | 73.9670 | 763.38 | 7924.11 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.48E+09 | 0.00 | 0.48E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 77309717.76 | 496713.84 | 77806431.61 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 15.1966 | 0.0000 | 15.1966 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.4515 | 0.0158 | 2.4672 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 5137.98 | 3622.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 6701.63 | 2058.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 13.9390 | 16.9844 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.4517 | 2.4519 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1318 |
Defaulted Fields | 1181 |
Fields with Defaults | 4005 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6602.02 | 75104.82 | 13-JAN-03:00 | 463845.66 | 21-JUL-20:00 |
Electricity:Building | 2519.24 | 32804.76 | 02-JAN-02:10 | 151906.32 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 323.72 | 3705.45 | 02-JAN-02:10 | 24299.15 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2512.15 | 32663.61 | 02-JAN-02:10 | 151664.99 | 02-JAN-20:10 |
InteriorLights:Electricity | 767.13 | 6971.81 | 02-JAN-02:10 | 62892.57 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 767.13 | 6971.81 | 02-JAN-02:10 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 767.13 | 6971.81 | 02-JAN-02:10 | 62892.57 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 173.46 | 1576.23 | 02-JAN-02:10 | 14185.34 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 767.13 | 6971.81 | 02-JAN-02:10 | 62892.57 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.80 | 222.61 | 02-JAN-02:10 | 1390.02 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.61 | 78.27 | 02-JAN-02:10 | 704.41 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.77 | 257.78 | 02-JAN-02:10 | 1609.65 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.97 | 90.64 | 02-JAN-02:10 | 815.72 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 29.11 | 327.88 | 02-JAN-02:10 | 2199.84 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 16.64 | 151.16 | 02-JAN-02:10 | 1360.40 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.38 | 76.28 | 02-JAN-02:10 | 469.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.78 | 25.30 | 02-JAN-02:10 | 227.72 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.30 | 1002.39 | 02-JAN-02:10 | 4930.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.37 | 39.69 | 02-JAN-02:10 | 357.21 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 32.36 | 398.98 | 02-JAN-02:10 | 2727.18 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 18.02 | 195.77 | 02-JAN-02:10 | 1761.91 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 18.02 | 195.77 | 02-JAN-02:10 | 1761.91 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 270.97 | 3251.99 | 02-JAN-02:10 | 20294.39 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 121.98 | 1140.58 | 02-JAN-02:10 | 10265.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 121.98 | 1140.58 | 02-JAN-02:10 | 10265.18 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 304.77 | 4565.05 | 01-JAN-02:10 | 20923.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 76.02 | 643.59 | 01-JAN-02:10 | 5851.22 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 304.86 | 4566.30 | 01-JAN-02:10 | 20928.98 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 76.04 | 643.77 | 01-JAN-02:10 | 5852.82 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.66 | 264.62 | 01-JAN-02:10 | 1227.54 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.37 | 53.90 | 01-JAN-02:10 | 490.02 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.66 | 264.59 | 01-JAN-02:10 | 1227.39 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.37 | 53.89 | 01-JAN-02:10 | 489.96 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 109.60 | 995.90 | 02-JAN-02:10 | 8963.13 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.50 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.66 | 66.15 | 01-JAN-02:10 | 306.85 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.59 | 13.47 | 01-JAN-02:10 | 122.49 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 36.10 | 540.75 | 01-JAN-02:10 | 2478.43 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 9.00 | 76.24 | 01-JAN-02:10 | 693.10 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 210.69 | 2593.08 | 02-JAN-02:10 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.83 | 343.78 | 02-JAN-02:10 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 34.83 | 343.78 | 02-JAN-02:10 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 210.69 | 2593.08 | 02-JAN-02:10 | 9841.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.83 | 343.78 | 02-JAN-02:10 | 3094.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 34.83 | 343.78 | 02-JAN-02:10 | 3094.06 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 454.16 | 6253.02 | 02-JAN-02:10 | 18944.06 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.33 | 121.09 | 02-JAN-02:10 | 1089.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 29.00 | 263.50 | 02-JAN-02:10 | 2371.52 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1745.01 | 25691.80 | 02-JAN-02:10 | 89475.41 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.81 | 1114.46 | 10-APR-22:30 | 3355.50 | 03-FEB-07:30 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 2336.59 | 2611.09 | 13-OCT-02:00 | 233680.48 | 28-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 20.50 | 0.00 | 01-JAN-11:10 | 1982.94 | 03-MAR-07:00 |
MedTempRefrigeration:Refrigeration:Electricity | 34.21 | 985.03 | 18-DEC-24:00 | 1228.30 | 18-NOV-07:10 |
Fans:Electricity | 660.66 | 12024.80 | 04-NOV-02:10 | 53347.46 | 08-SEP-21:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 884.19 | 12841.22 | 10-FEB-04:00 | 64491.44 | 08-SEP-21:20 |
ExteriorEquipment:Electricity | 651.48 | 9618.58 | 02-JAN-02:20 | 39726.11 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.45 | 553.78 | 05-JAN-04:10 | 1868.65 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 6602.02 | 75104.82 | 13-JAN-03:00 | 463845.66 | 21-JUL-20:00 |
ElectricityPurchased:Plant | 6602.02 | 75104.82 | 13-JAN-03:00 | 463845.66 | 21-JUL-20:00 |
Cogeneration:ElectricityPurchased | 6602.02 | 75104.82 | 13-JAN-03:00 | 463845.66 | 21-JUL-20:00 |
General:Cogeneration:ElectricityPurchased | 6602.02 | 75104.82 | 13-JAN-03:00 | 463845.66 | 21-JUL-20:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6602.02 | 75104.82 | 13-JAN-03:00 | 463845.66 | 21-JUL-20:00 |
ElectricityNet:Plant | 6602.02 | 75104.82 | 13-JAN-03:00 | 463845.66 | 21-JUL-20:00 |
Cogeneration:ElectricityNet | 6602.02 | 75104.82 | 13-JAN-03:00 | 463845.66 | 21-JUL-20:00 |
General:Cogeneration:ElectricityNet | 6602.02 | 75104.82 | 13-JAN-03:00 | 463845.66 | 21-JUL-20:00 |
General:Fans:Electricity | 660.66 | 12024.80 | 04-NOV-02:10 | 53347.46 | 08-SEP-21:20 |
ExteriorLights:Electricity | 242.97 | 0.00 | 01-JAN-07:30 | 15448.40 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 242.97 | 0.00 | 01-JAN-07:30 | 15448.40 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 191.08 | 0.00 | 01-JAN-14:30 | 9938.94 | 11-JAN-02:40 |
General:HeatRecovery:Electricity | 191.08 | 0.00 | 01-JAN-14:30 | 9938.94 | 11-JAN-02:40 |
WaterSystems:Electricity | 90.74 | 1086.55 | 20-NOV-04:00 | 4738.76 | 12-OCT-18:10 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.55 | 20-NOV-04:00 | 4738.76 | 12-OCT-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1978.53 | 0.00 | 01-JAN-00:40 | 217591.64 | 28-JUN-18:10 |
General:Cooling:Electricity | 1978.53 | 0.00 | 01-JAN-00:40 | 217591.64 | 28-JUN-18:10 |
Pumps:Electricity | 212.61 | 47.91 | 09-JAN-08:10 | 9630.15 | 28-JUN-18:50 |
General:Pumps:Electricity | 212.61 | 47.91 | 09-JAN-08:10 | 9630.15 | 28-JUN-18:50 |
WIRED_LTG_ELECTRICITY | 27.00 | 0.00 | 01-JAN-00:10 | 2213.82 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4643.03 | 29270.80 | 11-MAR-02:10 | 428064.21 | 16-DEC-22:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 2854.19 | 15908.90 | 04-APR-10:10 | 373799.96 | 16-DEC-22:10 |
WaterSystems:NaturalGas | 2671.65 | 15908.90 | 01-JAN-00:10 | 245388.03 | 25-JAN-21:20 |
Water Heater:WaterSystems:NaturalGas | 2671.65 | 15908.90 | 01-JAN-00:10 | 245388.03 | 25-JAN-21:20 |
Heating:NaturalGas | 182.54 | 0.00 | 02-JAN-19:20 | 176232.64 | 02-FEB-03:40 |
Boiler:Heating:NaturalGas | 182.54 | 0.00 | 02-JAN-19:20 | 176232.64 | 02-FEB-03:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 5748.46 | 0.00 | 01-JAN-00:40 | 655993.18 | 10-SEP-20:40 |
PlantLoopCoolingDemand:HVAC | 5748.46 | 0.00 | 01-JAN-00:40 | 655993.18 | 10-SEP-20:40 |
CoolingCoils:PlantLoopCoolingDemand | 5748.46 | 0.00 | 01-JAN-00:40 | 655993.18 | 10-SEP-20:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 04-DEC-21:40 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 04-DEC-21:40 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 04-DEC-21:40 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 10-JAN-02:20 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 04-DEC-21:40 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 04-DEC-21:40 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 04-DEC-21:40 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 10-JAN-02:20 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:20 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 28038.16 | 132816.47 | 12-FEB-15:30 | 2489956.66 | 10-SEP-20:40 |
EnergyTransfer:Building | 6311.36 | 74123.34 | 05-DEC-09:20 | 403977.11 | 20-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 744.68 | 8824.40 | 11-JAN-04:00 | 36748.58 | 13-AUG-10:40 |
Refrigeration:EnergyTransfer | 182.18 | 4015.04 | 26-MAR-22:10 | 10423.34 | 07-MAR-08:10 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.09 | 2007.52 | 26-MAR-22:10 | 5211.67 | 07-MAR-08:10 |
General:Refrigeration:EnergyTransfer | 91.09 | 2007.52 | 26-MAR-22:10 | 5211.67 | 07-MAR-08:10 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.09 | 2007.52 | 26-MAR-22:10 | 5211.67 | 07-MAR-08:10 |
EnergyTransfer:Plant | 14645.18 | 12632.81 | 28-OCT-02:50 | 1509533.65 | 10-SEP-20:40 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.57 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.52 | 1905.09 | 18-DEC-24:00 | 2634.89 | 18-NOV-07:10 |
EnergyTransfer:Zone:BASEMENT | 463.29 | 4742.87 | 30-MAR-07:20 | 27111.66 | 08-SEP-21:00 |
Heating:EnergyTransfer | 23.00 | 0.00 | 01-JAN-08:10 | 31734.95 | 07-DEC-06:00 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 212.81 | 25-MAR-03:40 |
General:Heating:EnergyTransfer | 23.00 | 0.00 | 01-JAN-08:10 | 31734.95 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 212.81 | 25-MAR-03:40 |
Cooling:EnergyTransfer | 6197.27 | 60617.03 | 05-DEC-09:20 | 401102.36 | 27-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 463.29 | 4742.87 | 30-MAR-07:20 | 27111.66 | 08-SEP-21:00 |
General:Cooling:EnergyTransfer | 6197.27 | 60617.03 | 05-DEC-09:20 | 401102.36 | 27-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 463.29 | 4742.87 | 30-MAR-07:20 | 27111.66 | 08-SEP-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 52.66 | 2.82 | 27-MAR-04:00 | 4131.85 | 28-SEP-13:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 302.22 | 16-DEC-07:20 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 302.22 | 16-DEC-07:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 52.63 | 0.00 | 13-FEB-07:10 | 4131.85 | 28-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 52.63 | 0.00 | 13-FEB-07:10 | 4131.85 | 28-SEP-13:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.66 | 203.89 | 05-DEC-09:20 | 2769.78 | 28-JUN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 67.49 | 13-FEB-05:50 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 67.49 | 13-FEB-05:50 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.65 | 203.89 | 05-DEC-09:20 | 2769.78 | 28-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.65 | 203.89 | 05-DEC-09:20 | 2769.78 | 28-JUN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 35.52 | 56.37 | 05-DEC-09:20 | 3125.15 | 28-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 117.89 | 21-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 117.89 | 21-DEC-05:20 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 35.51 | 56.37 | 05-DEC-09:20 | 3125.15 | 28-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 35.51 | 56.37 | 05-DEC-09:20 | 3125.15 | 28-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 21.58 | 0.30 | 07-DEC-06:10 | 1356.10 | 28-JUN-19:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 129.46 | 21-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 129.46 | 21-DEC-05:20 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 21.56 | 0.00 | 07-DEC-04:10 | 1356.10 | 28-JUN-19:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 21.56 | 0.00 | 07-DEC-04:10 | 1356.10 | 28-JUN-19:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 610.54 | 6446.76 | 04-NOV-04:30 | 40402.89 | 28-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 610.54 | 6446.76 | 04-NOV-04:30 | 40402.89 | 28-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 610.54 | 6446.76 | 04-NOV-04:30 | 40402.89 | 28-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 281.63 | 1256.13 | 05-DEC-09:20 | 14242.59 | 01-NOV-15:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 535.78 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 535.78 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 281.59 | 1256.13 | 05-DEC-09:20 | 14242.59 | 01-NOV-15:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 281.59 | 1256.13 | 05-DEC-09:20 | 14242.59 | 01-NOV-15:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 889.57 | 5269.04 | 05-DEC-09:20 | 48445.70 | 28-JUN-20:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 474.48 | 17-DEC-08:40 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 474.48 | 17-DEC-08:40 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 889.56 | 5269.04 | 05-DEC-09:20 | 48445.70 | 28-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 889.56 | 5269.04 | 05-DEC-09:20 | 48445.70 | 28-JUN-20:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 96.74 | 0.08 | 25-DEC-04:10 | 13273.33 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 2.18 | 0.00 | 01-JAN-08:10 | 2876.95 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 2.18 | 0.00 | 01-JAN-08:10 | 2876.95 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 94.56 | 0.00 | 01-JAN-00:10 | 13273.33 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 94.56 | 0.00 | 01-JAN-00:10 | 13273.33 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 87.45 | 0.18 | 12-MAR-01:50 | 13529.49 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 4.29 | 0.00 | 01-JAN-08:10 | 4449.35 | 07-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 4.29 | 0.00 | 01-JAN-08:10 | 4449.35 | 07-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 83.15 | 0.00 | 01-JAN-00:10 | 13529.49 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 83.15 | 0.00 | 01-JAN-00:10 | 13529.49 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 629.75 | 4009.67 | 13-FEB-06:00 | 55371.54 | 20-NOV-14:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 629.75 | 4009.67 | 13-FEB-06:00 | 55371.54 | 20-NOV-14:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 629.75 | 4009.67 | 13-FEB-06:00 | 55371.54 | 20-NOV-14:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 598.46 | 3.29 | 20-DEC-06:20 | 79312.54 | 27-JUN-18:30 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 5.19 | 0.00 | 01-JAN-08:10 | 24775.66 | 07-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 5.19 | 0.00 | 01-JAN-08:10 | 24775.66 | 07-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 593.27 | 0.00 | 01-JAN-00:10 | 79312.54 | 27-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 593.27 | 0.00 | 01-JAN-00:10 | 79312.54 | 27-JUN-18:30 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 99.57 | 0.03 | 25-JAN-04:30 | 10794.82 | 27-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 2.17 | 0.00 | 01-JAN-08:10 | 2902.12 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 2.17 | 0.00 | 01-JAN-08:10 | 2902.12 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 97.40 | 0.00 | 01-JAN-00:10 | 10794.82 | 27-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 97.40 | 0.00 | 01-JAN-00:10 | 10794.82 | 27-AUG-15:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 89.71 | 0.04 | 17-JAN-07:00 | 10889.36 | 19-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 4.04 | 0.00 | 01-JAN-08:10 | 3593.66 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 4.04 | 0.00 | 01-JAN-08:10 | 3593.66 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 85.67 | 0.00 | 01-JAN-00:10 | 10889.36 | 19-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 85.67 | 0.00 | 01-JAN-00:10 | 10889.36 | 19-JUN-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 228.89 | 720.06 | 05-DEC-09:20 | 16638.36 | 28-JUN-19:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.07 | 0.00 | 01-JAN-00:10 | 756.21 | 21-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.07 | 0.00 | 01-JAN-00:10 | 756.21 | 21-DEC-05:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 228.82 | 720.06 | 05-DEC-09:20 | 16638.36 | 28-JUN-19:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 228.82 | 720.06 | 05-DEC-09:20 | 16638.36 | 28-JUN-19:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 24.59 | 0.00 | 12-MAR-09:00 | 3560.97 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 1.35 | 0.00 | 01-JAN-08:10 | 1066.64 | 07-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 1.35 | 0.00 | 01-JAN-08:10 | 1066.64 | 07-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 23.24 | 0.00 | 01-JAN-00:10 | 3560.97 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 23.24 | 0.00 | 01-JAN-00:10 | 3560.97 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 22.82 | 0.00 | 27-DEC-21:20 | 3625.50 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 2.28 | 0.00 | 01-JAN-08:10 | 1268.98 | 07-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 2.28 | 0.00 | 01-JAN-08:10 | 1268.98 | 07-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 20.54 | 0.00 | 01-JAN-00:10 | 3625.50 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 20.54 | 0.00 | 01-JAN-00:10 | 3625.50 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 142.61 | 0.06 | 18-DEC-08:00 | 16978.72 | 28-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 1.29 | 0.00 | 01-JAN-00:10 | 3216.34 | 27-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 1.29 | 0.00 | 01-JAN-00:10 | 3216.34 | 27-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 141.32 | 0.00 | 01-JAN-00:40 | 16978.72 | 28-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 141.32 | 0.00 | 01-JAN-00:40 | 16978.72 | 28-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 506.41 | 3167.25 | 05-DEC-09:20 | 24844.64 | 28-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 343.18 | 10-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 343.18 | 10-DEC-05:30 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 506.40 | 3167.25 | 05-DEC-09:20 | 24844.64 | 28-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 506.40 | 3167.25 | 05-DEC-09:20 | 24844.64 | 28-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 530.74 | 3962.00 | 05-DEC-09:20 | 26255.11 | 28-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 229.59 | 22-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 229.59 | 22-JAN-05:30 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 530.74 | 3962.00 | 05-DEC-09:20 | 26255.11 | 28-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 530.74 | 3962.00 | 05-DEC-09:20 | 26255.11 | 28-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 653.59 | 6061.89 | 21-DEC-05:20 | 31667.48 | 18-JUN-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 653.59 | 6061.89 | 21-DEC-05:20 | 31667.48 | 18-JUN-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 110.50 | 9.08 | 07-DEC-06:10 | 8515.40 | 28-JUN-18:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.04 | 0.00 | 01-JAN-00:10 | 352.59 | 21-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.04 | 0.00 | 01-JAN-00:10 | 352.59 | 21-DEC-05:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 110.47 | 0.00 | 07-DEC-06:10 | 8515.40 | 28-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 110.47 | 0.00 | 07-DEC-06:10 | 8515.40 | 28-JUN-18:20 |
PlantLoopHeatingDemand:Facility | 711.01 | 6300.23 | 26-JUL-03:00 | 162800.77 | 18-DEC-07:40 |
PlantLoopHeatingDemand:Plant | 584.54 | 6300.23 | 26-JUL-03:00 | 46116.65 | 24-JAN-07:40 |
WaterSystems:PlantLoopHeatingDemand | 584.54 | 6300.23 | 26-JUL-03:00 | 46116.65 | 24-JAN-07:40 |
General:WaterSystems:PlantLoopHeatingDemand | 584.54 | 6300.23 | 26-JUL-03:00 | 46116.65 | 24-JAN-07:40 |
EnergyTransfer:HVAC | 7081.61 | 90.02 | 24-MAR-14:50 | 759723.84 | 13-JUL-18:10 |
HeatingCoils:EnergyTransfer | 126.47 | 0.00 | 02-JAN-19:20 | 123415.51 | 19-DEC-03:10 |
PlantLoopHeatingDemand:HVAC | 126.47 | 0.00 | 02-JAN-19:20 | 123415.51 | 19-DEC-03:10 |
HeatingCoils:PlantLoopHeatingDemand | 126.47 | 0.00 | 02-JAN-19:20 | 123415.51 | 19-DEC-03:10 |
CoolingCoils:EnergyTransfer | 5748.46 | 0.00 | 01-JAN-00:40 | 655993.18 | 10-SEP-20:40 |
HeatRecoveryForHeating:EnergyTransfer | 550.38 | 0.00 | 01-JAN-14:30 | 305360.76 | 07-DEC-05:00 |
HeatRecoveryForCooling:EnergyTransfer | 656.30 | 0.00 | 01-JAN-00:10 | 206437.66 | 17-JUN-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 584.54 | 6300.23 | 26-JUL-03:00 | 46116.65 | 24-JAN-07:40 |
WaterUse:WaterSystems:EnergyTransfer | 584.54 | 6300.23 | 26-JUL-03:00 | 46116.65 | 24-JAN-07:40 |
Boilers:EnergyTransfer | 124.92 | 0.00 | 02-JAN-19:20 | 122507.04 | 19-DEC-03:10 |
Chillers:EnergyTransfer | 5933.05 | 0.00 | 01-JAN-00:40 | 663077.76 | 10-SEP-20:40 |
HeatRejection:EnergyTransfer | 7911.58 | 0.00 | 01-JAN-00:40 | 822951.02 | 10-SEP-20:40 |
General:HeatRejection:EnergyTransfer | 7911.58 | 0.00 | 01-JAN-00:40 | 822951.02 | 10-SEP-20:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -463.289 | 0.000 | 0.000 | 135.321 | 173.462 | 150.255 | 0.000 | 0.000 | 0.000 | 4.250 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.027 | -52.630 | 0.000 | 0.000 | 14.152 | 8.614 | 10.186 | 25.974 | 0.000 | 1.598 | 2.486 | 0.000 | -7.585 | 0.000 | -2.820 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.003 | -43.654 | 0.000 | 0.000 | 16.171 | 9.975 | 11.795 | 0.000 | 0.000 | 0.634 | 6.193 | 0.000 | 0.000 | 0.000 | -1.118 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.012 | -35.510 | 0.000 | 0.000 | 3.478 | 16.635 | 12.471 | 0.000 | 0.000 | 1.483 | 3.936 | 0.000 | 0.000 | 0.000 | -2.504 | -0.001 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.020 | -21.564 | 0.000 | 0.000 | 2.794 | 2.785 | 3.598 | 0.000 | 0.000 | 0.925 | 12.718 | 0.000 | 0.000 | 0.000 | -1.275 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -610.543 | 0.000 | 0.000 | 10.570 | 4.368 | 658.131 | 0.000 | 0.000 | 1.989 | 0.000 | 0.000 | 0.000 | 0.000 | -3.926 | -60.589 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.035 | -281.592 | 0.000 | 0.000 | 187.847 | 18.015 | 14.341 | 73.873 | 0.000 | 3.833 | 10.960 | 0.000 | -21.233 | 0.000 | -6.080 | -0.000 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.008 | -889.570 | 0.000 | 0.000 | 541.365 | 121.976 | 148.998 | 97.636 | 0.000 | 10.504 | 16.741 | 0.000 | -28.973 | 0.000 | -18.684 | -0.003 |
ROOM_1_FLR_3 | 3.650 | -79.156 | 0.000 | -16.874 | 0.000 | 0.000 | 9.658 | 6.366 | 12.292 | 57.601 | 0.000 | 5.101 | 21.960 | 0.000 | -14.680 | 0.000 | -5.918 | -0.001 |
ROOM_2_FLR_3 | 6.494 | -68.729 | 0.000 | -16.626 | 0.000 | 0.000 | 9.684 | 6.366 | 12.291 | 45.036 | 0.000 | 5.122 | 21.043 | 0.000 | -14.947 | 0.000 | -5.733 | -0.001 |
ROOM_3_MULT19_FLR_3 | 0.000 | -356.791 | 0.000 | -272.960 | 0.000 | 0.000 | 0.000 | 76.021 | 228.754 | 325.177 | 0.000 | 21.682 | 123.466 | 0.000 | -90.670 | 0.000 | -54.680 | -0.007 |
ROOM_4_MULT19_FLR_3 | 19.499 | -385.220 | 0.000 | -222.357 | 0.000 | 0.000 | 184.505 | 76.042 | 228.817 | 142.107 | 0.000 | 28.811 | 43.056 | 0.000 | -78.024 | 0.000 | -37.233 | -0.014 |
ROOM_5_FLR_3 | 3.602 | -81.863 | 0.000 | -16.976 | 0.000 | 0.000 | 9.646 | 6.366 | 12.292 | 59.317 | 0.000 | 5.089 | 22.510 | 0.000 | -13.992 | 0.000 | -5.992 | -0.002 |
ROOM_6_FLR_3 | 6.077 | -70.971 | 0.000 | -16.732 | 0.000 | 0.000 | 9.674 | 6.366 | 12.291 | 46.209 | 0.000 | 5.106 | 21.511 | 0.000 | -13.728 | 0.000 | -5.802 | -0.001 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.067 | -228.822 | 0.000 | 0.000 | 109.654 | 109.603 | 0.000 | 50.435 | 0.000 | 4.517 | 0.002 | 0.000 | -20.699 | 0.000 | -7.834 | -16.921 |
ROOM_1_FLR_6 | 1.880 | -19.575 | 0.000 | -4.201 | 0.000 | 0.000 | 2.417 | 1.592 | 3.073 | 14.364 | 0.000 | 1.269 | 4.258 | 0.000 | -3.579 | 0.000 | -1.498 | -0.000 |
ROOM_2_FLR_6 | 2.992 | -17.121 | 0.000 | -4.131 | 0.000 | 0.000 | 2.424 | 1.591 | 3.073 | 11.260 | 0.000 | 1.275 | 3.703 | 0.000 | -3.621 | 0.000 | -1.445 | -0.000 |
ROOM_3_MULT9_FLR_6 | 2.686 | -115.440 | 0.000 | -27.280 | 0.000 | 0.000 | 21.702 | 9.005 | 27.097 | 72.547 | 0.000 | 5.931 | 28.166 | 0.000 | -16.608 | 0.000 | -7.807 | -0.001 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.006 | -506.406 | 0.000 | 0.000 | 325.115 | 34.830 | 175.857 | 13.917 | 0.000 | 2.448 | 0.000 | 0.000 | -11.708 | 0.000 | -4.072 | -29.988 |
DINING_FLR_6 | 0.000 | 0.000 | 0.002 | -530.746 | 0.000 | 0.000 | 321.448 | 34.830 | 175.857 | 13.459 | 0.000 | 2.376 | 0.000 | 0.000 | -12.211 | 0.000 | -4.194 | -0.822 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -653.582 | 0.000 | 0.000 | 27.932 | 13.327 | 550.372 | 26.592 | 0.000 | 1.997 | 46.933 | 0.000 | -9.508 | 0.000 | -4.063 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.036 | -110.469 | 0.000 | 0.000 | 28.975 | 28.999 | 0.000 | 23.957 | 0.000 | 1.956 | 39.429 | 0.000 | -9.372 | 0.000 | -3.512 | -0.000 |
Total Facility | 46.880 | -1194.865 | 0.216 | -5026.515 | 0.000 | 0.000 | 1974.533 | 767.133 | 2451.839 | 1099.461 | 0.000 | 113.645 | 433.320 | 0.000 | -371.136 | 0.000 | -186.190 | -108.353 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 14-DEC-00:23 | 0.00 | 0.00 | 0.00 | -40532.51 | 0.00 | 0.00 | 6664.24 | 3152.28 | 3193.83 | 0.00 | 0.00 | 0.00 | 27522.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 28-SEP-13:30 | 0.00 | 0.00 | 0.00 | -4131.00 | 0.00 | 0.00 | 150.60 | 195.67 | 252.59 | 3915.55 | 0.00 | 223.40 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -606.81 |
RETAIL_2_FLR_1 | 28-JUN-20:10 | 0.00 | 0.00 | 0.00 | -2769.44 | 0.00 | 0.00 | 697.62 | 725.08 | 752.15 | 0.00 | 0.00 | 89.55 | 505.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 28-JUN-20:00 | 0.00 | 0.00 | 0.00 | -3124.59 | 0.00 | 0.00 | 129.09 | 1360.40 | 839.45 | 0.00 | 0.00 | 216.98 | 578.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 28-JUN-19:10 | 0.00 | 0.00 | 0.00 | -1355.86 | 0.00 | 0.00 | 99.30 | 227.72 | 242.16 | 0.00 | 0.00 | 148.22 | 638.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 04-DEC-21:39 | 0.00 | 0.00 | 0.00 | -48778.66 | 0.00 | 0.00 | 461.79 | 317.52 | 41967.83 | 0.00 | 0.00 | 0.00 | 6531.44 | 0.00 | -0.00 | 0.00 | -499.92 | 0.00 |
CAFE_FLR_1 | 30-JAN-05:38 | 0.00 | 0.00 | 0.00 | -15979.77 | 0.00 | 0.00 | 9694.01 | 391.53 | 304.82 | 0.00 | 0.00 | 0.00 | 8948.09 | 0.00 | -2659.07 | 0.00 | -699.62 | 0.00 |
LOBBY_FLR_1 | 11-JAN-06:27 | 0.00 | 0.00 | 0.00 | -73966.89 | 0.00 | 0.00 | 20562.78 | 4562.30 | 5278.53 | 0.00 | 0.00 | 0.00 | 48855.49 | 0.00 | -3324.02 | 0.00 | -1968.20 | 0.00 |
ROOM_1_FLR_3 | 28-SEP-15:01 | 0.00 | -14489.79 | 0.00 | -680.35 | 0.00 | 0.00 | 235.29 | 137.21 | 273.93 | 9068.23 | 0.00 | 628.11 | 4827.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 27-JUN-18:02 | 0.00 | -14401.68 | 0.00 | -679.74 | 0.00 | 0.00 | 335.50 | 436.07 | 516.20 | 8219.78 | 0.00 | 717.87 | 4856.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 20-NOV-14:30 | 0.00 | -45608.46 | 0.00 | -9760.04 | 0.00 | 0.00 | 0.00 | 1638.34 | 5097.90 | 56800.78 | 0.00 | 845.52 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9014.04 |
ROOM_4_MULT19_FLR_3 | 27-JUN-18:02 | 0.00 | -87454.19 | 0.00 | -9280.52 | 0.00 | 0.00 | 6374.62 | 5209.05 | 9610.21 | 24223.13 | 0.00 | 3791.91 | 47525.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 19-JUN-08:61 | 0.00 | -12675.39 | 0.00 | -680.64 | 0.00 | 0.00 | 87.15 | 215.61 | 453.05 | 8105.23 | 0.00 | 363.16 | 4131.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 19-JUN-08:61 | 0.00 | -12611.89 | 0.00 | -681.97 | 0.00 | 0.00 | 87.15 | 215.58 | 452.99 | 8297.84 | 0.00 | 362.26 | 3878.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 28-JUN-19:10 | 0.00 | 0.00 | 0.00 | -16635.72 | 0.00 | 0.00 | 4080.42 | 8963.13 | 0.00 | 3109.40 | 0.00 | 788.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -305.67 |
ROOM_1_FLR_6 | 28-SEP-15:01 | 0.00 | -3846.97 | 0.00 | -170.10 | 0.00 | 0.00 | 58.82 | 34.30 | 68.48 | 2251.89 | 0.00 | 156.43 | 1447.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 27-JUN-18:02 | 0.00 | -3822.07 | 0.00 | -170.00 | 0.00 | 0.00 | 83.88 | 109.02 | 129.05 | 2042.40 | 0.00 | 178.83 | 1448.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 28-SEP-15:01 | 0.00 | -17155.35 | 0.00 | -1112.29 | 0.00 | 0.00 | 529.41 | 194.07 | 603.86 | 7557.48 | 0.00 | 711.94 | 8670.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 10-JAN-05:05 | 0.00 | 0.00 | 0.00 | -33779.91 | 0.00 | 0.00 | 15215.98 | 687.57 | 2249.30 | 0.00 | 0.00 | 0.00 | 17414.85 | 0.00 | -1371.18 | 0.00 | -416.61 | 0.00 |
DINING_FLR_6 | 14-DEC-23:37 | 0.00 | 0.00 | 0.00 | -34167.07 | 0.00 | 0.00 | 15798.20 | 1031.35 | 6747.90 | 0.00 | 0.00 | 0.00 | 12572.10 | 0.00 | -1454.65 | 0.00 | -527.83 | 0.00 |
KITCHEN_FLR_6 | 13-JAN-07:39 | 0.00 | 0.00 | 0.00 | -36399.75 | 0.00 | 0.00 | 612.47 | 605.46 | 19261.50 | 57.86 | 0.00 | 0.00 | 16323.82 | 0.00 | -0.00 | 0.00 | -461.36 | 0.00 |
CORRIDOR_FLR_6 | 28-JUN-18:13 | 0.00 | 0.00 | 0.00 | -8515.49 | 0.00 | 0.00 | 1079.60 | 2108.02 | 0.00 | 1782.98 | 0.00 | 372.53 | 3172.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-JUN-18:02 | 0.00 | -195535.58 | 0.00 | -235756.70 | 0.00 | 0.00 | 74226.05 | 53571.31 | 122326.88 | 87010.27 | 0.00 | 17497.89 | 76659.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-MAR-03:33 | 0.00 | 0.00 | 638.44 | 0.00 | 0.00 | 0.00 | 6877.63 | 1576.23 | 2129.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -11221.52 |
RETAIL_1_FLR_1 | 13-FEB-05:43 | 0.00 | 0.00 | 373.48 | 0.00 | 0.00 | 0.00 | 802.37 | 156.54 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -721.59 | 0.00 | -267.36 | -559.94 |
RETAIL_2_FLR_1 | 18-DEC-07:48 | 0.00 | 0.00 | 237.04 | 0.00 | 0.00 | 0.00 | 397.19 | 453.18 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -138.12 | -1450.72 |
MECH_FLR_1 | 18-DEC-07:48 | 0.00 | 0.00 | 247.83 | 0.00 | 0.00 | 0.00 | 87.17 | 755.78 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -310.19 | -1310.76 |
STORAGE_FLR_1 | 15-DEC-00:28 | 0.00 | 0.00 | 267.77 | 0.00 | 0.00 | 0.00 | 151.04 | 50.60 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -161.60 | -384.29 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 18-DEC-07:48 | 0.00 | 0.00 | 2538.31 | 0.00 | 0.00 | 0.00 | 4703.30 | 597.09 | 609.65 | 401.79 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -758.24 | -8091.91 |
LOBBY_FLR_1 | 18-DEC-07:48 | 0.00 | 0.00 | 4043.46 | 0.00 | 0.00 | 0.00 | 13238.79 | 5303.68 | 6334.24 | 319.09 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2296.41 | -26942.84 |
ROOM_1_FLR_3 | 06-DEC-09:01 | 8437.17 | 341.51 | 0.00 | -341.51 | 0.00 | 0.00 | 104.86 | 215.61 | 453.05 | 1409.35 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -664.06 | -9955.98 |
ROOM_2_FLR_3 | 07-DEC-09:01 | 8681.01 | 277.32 | 0.00 | -277.32 | 0.00 | 0.00 | 108.88 | 215.58 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -982.87 | 0.00 | -610.14 | -7865.46 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 07-DEC-09:01 | 49097.88 | 4531.16 | 0.00 | -4531.16 | 0.00 | 0.00 | 1970.52 | 2575.24 | 8433.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5950.67 | 0.00 | -3444.39 | -52682.03 |
ROOM_5_FLR_3 | 12-FEB-16:02 | 7996.99 | 354.28 | 0.00 | -354.28 | 0.00 | 0.00 | 156.80 | 161.71 | 305.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -287.97 | 0.00 | -307.73 | -8025.33 |
ROOM_6_FLR_3 | 07-DEC-16:01 | 8128.95 | 352.93 | 0.00 | -352.93 | 0.00 | 0.00 | 281.21 | 137.19 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -640.07 | 0.00 | -632.12 | -7549.07 |
CORRIDOR_FLR_3 | 13-FEB-05:43 | 0.00 | 0.00 | 1822.55 | 0.00 | 0.00 | 0.00 | 6051.21 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2201.64 | 0.00 | -780.14 | -6883.78 |
ROOM_1_FLR_6 | 07-DEC-09:01 | 2520.33 | 72.09 | 0.00 | -72.09 | 0.00 | 0.00 | 27.22 | 53.90 | 113.26 | 346.85 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -155.17 | -2906.40 |
ROOM_2_FLR_6 | 07-DEC-09:01 | 2554.53 | 70.39 | 0.00 | -70.39 | 0.00 | 0.00 | 27.22 | 53.90 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -235.33 | 0.00 | -153.99 | -2359.57 |
ROOM_3_MULT9_FLR_6 | 27-MAR-08:61 | 11617.40 | 554.02 | 0.00 | -554.02 | 0.00 | 0.00 | 235.15 | 304.96 | 998.70 | 131.29 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -584.78 | -12702.71 |
BANQUET_FLR_6 | 06-DEC-08:39 | 0.00 | 0.00 | 2483.29 | 0.00 | 0.00 | 0.00 | 7987.49 | 1191.78 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1017.03 | 0.00 | -513.72 | -16879.72 |
DINING_FLR_6 | 22-JAN-05:30 | 0.00 | 0.00 | 1836.87 | 0.00 | 0.00 | 0.00 | 12599.52 | 687.57 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1414.14 | 0.00 | -453.84 | -15505.28 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 18-DEC-07:48 | 0.00 | 0.00 | 775.21 | 0.00 | 0.00 | 0.00 | 733.33 | 1317.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -397.56 | 0.00 | -420.86 | -2007.63 |
Total Facility | 27-MAR-08:61 | -18470.80 | 115432.51 | 0.00 | -115432.51 | 0.00 | 0.00 | 23442.91 | 26712.50 | 88432.23 | 11143.57 | 0.00 | 0.00 | 0.00 | 0.00 | -7831.91 | 0.00 | -13577.27 | -109851.24 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 24.7459 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 24.6237 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 13.6446 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.7127 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9300 | 2.9300 | 1.2482 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3949 | 0.3949 | 0.1185 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2845 | 0.2845 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3030 | 0.3030 | 0.0909 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1504 | 0.1504 | 0.0845 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.6450 | 3.6450 | 1.0935 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5998 | 1.5998 | 0.9887 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2464 | 5.2464 | 2.7701 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7066 | 1.7066 | 0.6946 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4861 | 2.4861 | 1.7353 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6014 | 2.6014 | 1.7352 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5088 | 2.5088 | 0.7526 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8891 | 0.8891 | 0.2667 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 24.7459 | 24.6237 | 24.7459 | 11.7127 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4650 | 1.4650 | 1.2482 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1974 | 0.1974 | 0.1185 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1422 | 0.1422 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1515 | 0.1515 | 0.0909 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0845 | 0.0845 | 0.0845 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8225 | 1.8225 | 1.0935 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9887 | 0.9887 | 0.9887 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7701 | 2.7701 | 2.7701 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8533 | 0.8533 | 0.6946 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7353 | 1.7353 | 1.7353 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7352 | 1.7352 | 1.7352 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2544 | 1.2544 | 0.7526 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4446 | 0.4446 | 0.2667 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 13.6446 | 11.7127 | 11.7127 | 11.7127 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 114.67 |
Number of hours not met | 114.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 182.54 | 176232.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1978.53 | 217591.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 767.13 | 62892.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 242.97 | 15448.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.56 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.45 | 1868.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 660.66 | 53347.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 212.61 | 9630.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 191.08 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.76 | 2671.65 | 245388.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.50 | 1982.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.21 | 1228.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1806.82 | 6602.02 |
Natural Gas | 1788.84 | 4643.03 |
Additional | 0.00 | 0.00 |
Total | 3595.66 | 11245.05 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 67.62 |
Space Heating | 0.00 |
Space Cooling | 174.39 |
Fans (All) | 58.23 |
Service Water Heating | 8.00 |
Receptacle Equipment | 153.81 |
Miscellaneous (All) | 581.92 |
Subtotal | 581.92 |
Natural Gas [MJ/m2] | |
Space Heating | 16.09 |
Service Water Heating | 235.49 |
Miscellaneous (All) | 409.25 |
Subtotal | 409.25 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.82 |
Space Heating | 1.62 |
Space Cooling | 17.59 |
Fans (All) | 5.88 |
Service Water Heating | 24.57 |
Receptacle Equipment | 31.43 |
Miscellaneous | 12.09 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2667. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 192720.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8365.00 | 395.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8364.67 | 395.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8651.33 | 108.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8330.67 | 429.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8331.83 | 428.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8330.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 429.33 | 0.00 | 0.00 | 0.00 |
Average | 8678.21 | 81.79 | 0.00 | 0.00 | 0.00 |
Sum | 190920.67 | 1799.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50019.50 | 159.50 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59029.50 | 126.50 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 661040.17 | 49376.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1974141.83 | 141287.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 98585.67 | 1772.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1153694.33 | 92020.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1154434.83 | 91280.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108181.33 | 87.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1974141.83 | 141287.17 | 0.00 | 0.00 | 0.00 |
Average | 271791.10 | 17095.95 | 0.00 | 0.00 | 0.00 |
Sum | 5979404.17 | 376110.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:00:32
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.376561E+11 | 38637.81 | 12-JAN-06:34 | 5.33 | 4.82 | 0.820953E+10 | 4978.55 | 26-JAN-05:49 | 7.83 | 4.23 |
February | 0.288369E+11 | 30315.24 | 01-FEB-06:55 | 5.00 | 3.59 | 0.728448E+10 | 4901.96 | 28-FEB-00:20 | 6.67 | 5.49 |
March | 0.293740E+11 | 18717.39 | 13-MAR-04:40 | 6.27 | 5.44 | 0.782386E+10 | 4837.00 | 02-MAR-22:19 | 6.27 | 5.44 |
April | 0.309956E+11 | 18578.47 | 21-APR-03:50 | 8.33 | 0.61 | 0.774172E+10 | 4837.08 | 11-APR-22:10 | 8.33 | 0.61 |
May | 0.309036E+11 | 15114.33 | 01-MAY-21:00 | 24.00 | 9.32 | 0.783704E+10 | 4837.10 | 11-MAY-21:19 | 25.67 | 12.70 |
June | 0.321277E+11 | 16703.60 | 22-JUN-21:00 | 31.00 | 14.48 | 0.776320E+10 | 4837.11 | 23-JUN-21:19 | 30.33 | 15.38 |
July | 0.407046E+11 | 23098.70 | 14-JUL-21:00 | 28.00 | 20.32 | 0.820489E+10 | 4837.16 | 07-JUL-22:10 | 28.00 | 20.32 |
August | 0.444376E+11 | 24801.09 | 24-AUG-21:00 | 30.00 | 12.33 | 0.826339E+10 | 4837.10 | 21-AUG-00:10 | 30.00 | 12.33 |
September | 0.482709E+11 | 27111.66 | 08-SEP-21:00 | 32.20 | 19.39 | 0.797705E+10 | 4837.17 | 15-SEP-03:09 | 19.90 | 14.65 |
October | 0.487882E+11 | 38759.07 | 25-OCT-05:30 | 6.00 | 0.93 | 0.823636E+10 | 5023.69 | 25-OCT-04:30 | 6.00 | 0.93 |
November | 0.461885E+11 | 38841.79 | 05-NOV-06:40 | 6.00 | 2.55 | 0.796404E+10 | 5007.57 | 27-NOV-04:19 | 8.77 | 4.31 |
December | 0.450022E+11 | 40533.31 | 14-DEC-00:23 | 5.00 | 2.11 | 0.823466E+10 | 5058.87 | 07-DEC-23:10 | 5.00 | 2.11 |
Annual Sum or Average | 0.463286E+12 | 0.955402E+11 | ||||||||
Minimum of Months | 0.288369E+11 | 15114.33 | 5.00 | 0.61 | 0.728448E+10 | 4837.00 | 5.00 | 0.61 | ||
Maximum of Months | 0.487882E+11 | 40533.31 | 32.20 | 20.32 | 0.826339E+10 | 5058.87 | 30.33 | 20.32 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.395479E+10 | 3777.40 | 14-JAN-13:40 | 26.67 | 10.98 | 0.764771E+09 | 491.82 | 25-JAN-22:19 | 12.33 | 6.47 |
February | 0.232100E+10 | 2710.84 | 01-FEB-14:00 | 16.00 | 7.74 | 0.636642E+09 | 483.29 | 28-FEB-22:10 | 12.55 | 9.16 |
March | 0.279698E+10 | 2977.15 | 18-MAR-13:40 | 26.27 | 12.12 | 0.739017E+09 | 491.82 | 23-MAR-21:00 | 13.80 | 7.85 |
April | 0.444872E+10 | 3347.16 | 14-APR-14:10 | 34.17 | 14.15 | 0.791422E+09 | 491.86 | 15-APR-01:19 | 24.00 | 12.47 |
May | 0.468689E+10 | 2905.81 | 31-MAY-18:15 | 35.33 | 13.34 | 0.830060E+09 | 491.86 | 10-MAY-23:10 | 35.33 | 13.34 |
June | 0.580011E+10 | 3708.77 | 28-JUN-18:13 | 40.67 | 17.68 | 0.813201E+09 | 491.86 | 09-JUN-23:19 | 40.67 | 17.68 |
July | 0.572087E+10 | 3421.69 | 21-JUL-18:30 | 38.00 | 19.28 | 0.836542E+09 | 491.85 | 01-JUL-00:10 | 38.00 | 19.28 |
August | 0.585818E+10 | 3807.75 | 28-AUG-12:30 | 37.00 | 20.85 | 0.839401E+09 | 491.84 | 10-AUG-22:00 | 37.00 | 20.85 |
September | 0.554641E+10 | 4131.85 | 28-SEP-13:30 | 36.10 | 16.03 | 0.809544E+09 | 491.84 | 07-SEP-21:30 | 36.10 | 16.03 |
October | 0.474376E+10 | 4126.48 | 06-OCT-13:20 | 35.00 | 15.67 | 0.802789E+09 | 491.86 | 19-OCT-22:10 | 19.83 | 11.29 |
November | 0.366002E+10 | 3968.22 | 20-NOV-13:40 | 26.67 | 11.57 | 0.739530E+09 | 491.82 | 15-NOV-22:10 | 26.67 | 11.57 |
December | 0.309210E+10 | 3662.24 | 25-DEC-13:00 | 25.00 | 11.61 | 0.719081E+09 | 491.82 | 22-DEC-22:30 | 25.00 | 11.61 |
Annual Sum or Average | 0.526298E+11 | 0.932200E+10 | ||||||||
Minimum of Months | 0.232100E+10 | 2710.84 | 16.00 | 7.74 | 0.636642E+09 | 483.29 | 12.33 | 6.47 | ||
Maximum of Months | 0.585818E+10 | 4131.85 | 40.67 | 20.85 | 0.839401E+09 | 491.86 | 40.67 | 20.85 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315560E+10 | 2222.30 | 30-JAN-05:38 | 7.33 | 2.10 | 0.913827E+09 | 570.47 | 12-JAN-22:30 | 7.33 | 2.10 |
February | 0.259216E+10 | 2142.61 | 02-FEB-02:35 | 7.33 | 3.96 | 0.785456E+09 | 570.25 | 27-FEB-22:30 | 10.00 | 7.14 |
March | 0.305641E+10 | 1924.06 | 13-MAR-04:40 | 6.27 | 5.44 | 0.899315E+09 | 569.55 | 22-MAR-21:10 | 13.35 | 7.10 |
April | 0.373314E+10 | 2457.28 | 14-APR-20:10 | 30.67 | 13.61 | 0.927138E+09 | 569.57 | 16-APR-23:10 | 18.83 | 12.52 |
May | 0.407897E+10 | 2414.92 | 31-MAY-20:10 | 30.67 | 11.82 | 0.965082E+09 | 569.57 | 26-MAY-03:09 | 30.67 | 11.82 |
June | 0.449791E+10 | 2769.78 | 28-JUN-20:10 | 36.67 | 15.41 | 0.940086E+09 | 569.57 | 09-JUN-23:19 | 36.67 | 15.41 |
July | 0.442496E+10 | 2613.25 | 20-JUL-20:10 | 35.17 | 18.52 | 0.966481E+09 | 569.55 | 01-JUL-00:10 | 35.17 | 18.52 |
August | 0.440277E+10 | 2646.71 | 15-AUG-20:10 | 34.67 | 18.05 | 0.970128E+09 | 569.54 | 10-AUG-22:00 | 34.67 | 18.05 |
September | 0.406551E+10 | 2597.82 | 07-SEP-21:00 | 33.30 | 19.43 | 0.935739E+09 | 569.55 | 15-SEP-03:09 | 19.90 | 14.65 |
October | 0.364377E+10 | 2396.76 | 05-OCT-20:10 | 26.50 | 13.28 | 0.944448E+09 | 569.58 | 19-OCT-22:10 | 19.83 | 11.29 |
November | 0.310015E+10 | 2063.41 | 01-NOV-20:10 | 20.50 | 13.68 | 0.887010E+09 | 569.53 | 14-NOV-22:00 | 13.00 | 13.00 |
December | 0.290205E+10 | 2185.61 | 14-DEC-00:23 | 5.00 | 2.11 | 0.877686E+09 | 570.29 | 28-DEC-22:30 | 9.25 | 3.38 |
Annual Sum or Average | 0.436534E+11 | 0.110124E+11 | ||||||||
Minimum of Months | 0.259216E+10 | 1924.06 | 5.00 | 2.10 | 0.785456E+09 | 569.53 | 7.33 | 2.10 | ||
Maximum of Months | 0.449791E+10 | 2769.78 | 36.67 | 19.43 | 0.970128E+09 | 570.47 | 36.67 | 18.52 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191296E+10 | 1420.98 | 30-JAN-05:38 | 7.33 | 2.10 | 0.179571E+09 | 118.24 | 27-JAN-22:10 | 7.33 | 2.10 |
February | 0.162032E+10 | 1381.07 | 02-FEB-02:35 | 7.33 | 3.96 | 0.155611E+09 | 112.57 | 01-FEB-22:10 | 7.33 | 3.96 |
March | 0.195042E+10 | 1298.93 | 17-MAR-21:00 | 21.60 | 12.64 | 0.181433E+09 | 120.46 | 22-MAR-21:10 | 13.35 | 7.10 |
April | 0.272751E+10 | 2294.71 | 25-APR-20:00 | 28.00 | 14.61 | 0.195486E+09 | 120.46 | 25-APR-00:10 | 28.00 | 14.61 |
May | 0.351019E+10 | 2450.64 | 31-MAY-20:00 | 31.00 | 11.94 | 0.205330E+09 | 120.46 | 10-MAY-23:19 | 31.00 | 11.94 |
June | 0.471275E+10 | 3125.15 | 28-JUN-20:00 | 37.00 | 15.57 | 0.199180E+09 | 120.46 | 09-JUN-23:30 | 37.00 | 15.57 |
July | 0.461937E+10 | 2978.72 | 21-JUL-20:00 | 37.00 | 20.84 | 0.205008E+09 | 120.46 | 07-JUL-22:10 | 37.00 | 20.84 |
August | 0.432224E+10 | 2828.90 | 15-AUG-20:00 | 35.00 | 18.06 | 0.205842E+09 | 120.46 | 21-AUG-00:10 | 26.00 | 16.49 |
September | 0.378627E+10 | 2695.58 | 08-SEP-20:00 | 33.80 | 19.77 | 0.198641E+09 | 120.46 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.268075E+10 | 2452.73 | 03-OCT-20:00 | 30.00 | 18.25 | 0.197069E+09 | 120.46 | 19-OCT-22:10 | 19.83 | 11.29 |
November | 0.193719E+10 | 1393.93 | 02-NOV-20:00 | 21.00 | 15.83 | 0.177909E+09 | 120.45 | 02-NOV-22:10 | 19.83 | 16.01 |
December | 0.173024E+10 | 1384.11 | 14-DEC-00:23 | 5.00 | 2.11 | 0.169574E+09 | 114.64 | 26-DEC-22:10 | 14.83 | 7.20 |
Annual Sum or Average | 0.355102E+11 | 0.227065E+10 | ||||||||
Minimum of Months | 0.162032E+10 | 1298.93 | 5.00 | 2.10 | 0.155611E+09 | 112.57 | 7.33 | 2.10 | ||
Maximum of Months | 0.471275E+10 | 3125.15 | 37.00 | 20.84 | 0.205842E+09 | 120.46 | 37.00 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148689E+10 | 1232.31 | 30-JAN-05:38 | 7.33 | 2.10 | 0.124102E+09 | 78.22 | 27-JAN-22:30 | 7.33 | 2.10 |
February | 0.120040E+10 | 1187.05 | 02-FEB-02:35 | 7.33 | 3.96 | 0.107912E+09 | 76.49 | 01-FEB-00:10 | 7.33 | 3.96 |
March | 0.148281E+10 | 1011.56 | 02-MAR-05:27 | 7.15 | 6.47 | 0.124777E+09 | 82.42 | 17-MAR-21:40 | 20.87 | 12.09 |
April | 0.185658E+10 | 1112.21 | 21-APR-03:50 | 8.33 | 0.61 | 0.136684E+09 | 90.43 | 14-APR-21:40 | 8.33 | 0.61 |
May | 0.206328E+10 | 967.85 | 31-MAY-18:07 | 35.67 | 13.49 | 0.148111E+09 | 92.07 | 18-MAY-21:49 | 35.67 | 13.49 |
June | 0.230870E+10 | 1356.10 | 28-JUN-19:10 | 39.50 | 16.83 | 0.151341E+09 | 92.66 | 09-JUN-23:40 | 39.50 | 16.83 |
July | 0.230646E+10 | 1250.82 | 21-JUL-20:00 | 37.00 | 20.84 | 0.155084E+09 | 92.66 | 07-JUL-22:10 | 37.00 | 20.84 |
August | 0.223395E+10 | 1146.66 | 15-AUG-20:00 | 35.00 | 18.06 | 0.154070E+09 | 92.66 | 14-AUG-23:49 | 35.00 | 18.06 |
September | 0.207240E+10 | 1032.36 | 08-SEP-20:00 | 33.80 | 19.77 | 0.146362E+09 | 92.66 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.183846E+10 | 1169.05 | 12-OCT-04:42 | 7.17 | 3.07 | 0.137943E+09 | 92.66 | 03-OCT-21:40 | 7.17 | 3.07 |
November | 0.151426E+10 | 1130.91 | 30-NOV-05:05 | 8.00 | 2.43 | 0.122058E+09 | 83.10 | 02-NOV-22:10 | 8.00 | 2.43 |
December | 0.119971E+10 | 1188.78 | 14-DEC-00:23 | 5.00 | 2.11 | 0.119537E+09 | 76.38 | 26-DEC-22:40 | 14.33 | 6.96 |
Annual Sum or Average | 0.215639E+11 | 0.162798E+10 | ||||||||
Minimum of Months | 0.119971E+10 | 967.85 | 5.00 | 0.61 | 0.107912E+09 | 76.38 | 7.17 | 0.61 | ||
Maximum of Months | 0.230870E+10 | 1356.10 | 39.50 | 20.84 | 0.155084E+09 | 92.66 | 39.50 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.495011E+11 | 42080.81 | 12-JAN-07:04 | 5.17 | 4.58 | 0.646259E+09 | 458.80 | 11-JAN-05:30 | 5.17 | 4.58 |
February | 0.439819E+11 | 42147.59 | 02-FEB-07:09 | 5.50 | 2.72 | 0.582901E+09 | 497.13 | 28-FEB-00:20 | 6.67 | 5.49 |
March | 0.497441E+11 | 41396.38 | 30-MAR-06:33 | 5.17 | 2.04 | 0.648317E+09 | 427.39 | 07-MAR-05:19 | 5.17 | 2.04 |
April | 0.509193E+11 | 39538.83 | 14-APR-20:00 | 31.00 | 13.66 | 0.629176E+09 | 382.38 | 19-APR-04:00 | 13.00 | 4.78 |
May | 0.536387E+11 | 39633.74 | 09-MAY-20:00 | 31.00 | 13.10 | 0.650748E+09 | 381.79 | 11-MAY-21:10 | 25.83 | 12.78 |
June | 0.535544E+11 | 40402.89 | 28-JUN-20:00 | 37.00 | 15.57 | 0.630919E+09 | 381.91 | 23-JUN-21:10 | 37.00 | 15.57 |
July | 0.546181E+11 | 40201.72 | 21-JUL-20:00 | 37.00 | 20.84 | 0.649371E+09 | 381.88 | 07-JUL-21:10 | 37.00 | 20.84 |
August | 0.545686E+11 | 40086.33 | 15-AUG-20:00 | 35.00 | 18.06 | 0.652148E+09 | 382.22 | 09-AUG-21:10 | 35.00 | 18.06 |
September | 0.519052E+11 | 39908.61 | 08-SEP-20:00 | 33.80 | 19.77 | 0.629260E+09 | 381.90 | 19-SEP-21:10 | 28.02 | 15.82 |
October | 0.515910E+11 | 39481.22 | 12-OCT-06:38 | 7.67 | 3.31 | 0.648235E+09 | 444.50 | 25-OCT-04:30 | 7.00 | 1.35 |
November | 0.481569E+11 | 46138.40 | 23-NOV-21:29 | 4.00 | -1.1 | 0.625148E+09 | 442.38 | 04-NOV-04:40 | 4.00 | -1.1 |
December | 0.483580E+11 | 48778.68 | 04-DEC-21:39 | 5.33 | 0.54 | 0.646425E+09 | 500.64 | 07-DEC-22:00 | 4.00 | -2.3 |
Annual Sum or Average | 0.610537E+12 | 0.763891E+10 | ||||||||
Minimum of Months | 0.439819E+11 | 39481.22 | 4.00 | -1.1 | 0.582901E+09 | 381.79 | 4.00 | -2.3 | ||
Maximum of Months | 0.546181E+11 | 48778.68 | 37.00 | 20.84 | 0.652148E+09 | 500.64 | 37.00 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231998E+11 | 15980.31 | 30-JAN-05:38 | 7.33 | 2.10 | 0.100600E+11 | 6586.78 | 11-JAN-01:00 | 7.33 | 2.10 |
February | 0.178141E+11 | 14860.33 | 02-FEB-01:50 | 8.17 | 4.38 | 0.851870E+10 | 6467.40 | 03-FEB-00:20 | 8.00 | 3.09 |
March | 0.203987E+11 | 12574.73 | 02-MAR-05:27 | 7.15 | 6.47 | 0.961655E+10 | 6547.37 | 14-MAR-04:00 | 7.70 | 6.56 |
April | 0.232905E+11 | 13292.91 | 21-APR-03:50 | 8.33 | 0.61 | 0.100583E+11 | 6461.74 | 15-APR-01:19 | 8.33 | 0.61 |
May | 0.242259E+11 | 11658.96 | 09-MAY-21:10 | 28.83 | 12.76 | 0.104385E+11 | 6461.51 | 10-MAY-23:10 | 25.83 | 15.07 |
June | 0.258669E+11 | 13622.52 | 28-JUN-18:06 | 40.83 | 17.83 | 0.104062E+11 | 6461.69 | 05-JUN-04:10 | 40.83 | 17.83 |
July | 0.264222E+11 | 13329.35 | 21-JUL-21:10 | 33.83 | 20.81 | 0.106794E+11 | 6461.35 | 01-JUL-00:10 | 33.83 | 20.81 |
August | 0.267827E+11 | 13660.64 | 15-AUG-18:05 | 37.83 | 18.62 | 0.107630E+11 | 6461.19 | 20-AUG-23:30 | 26.50 | 16.19 |
September | 0.257468E+11 | 14183.87 | 28-SEP-15:03 | 37.52 | 15.49 | 0.103975E+11 | 6461.13 | 06-SEP-21:30 | 37.52 | 15.49 |
October | 0.247140E+11 | 14098.10 | 05-OCT-15:03 | 34.00 | 15.75 | 0.103839E+11 | 6461.64 | 07-OCT-01:00 | 25.00 | 14.77 |
November | 0.219583E+11 | 14253.41 | 01-NOV-15:03 | 28.83 | 16.12 | 0.965745E+10 | 6460.84 | 01-NOV-21:10 | 18.00 | 13.11 |
December | 0.211701E+11 | 15470.44 | 14-DEC-00:23 | 5.00 | 2.11 | 0.964193E+10 | 6608.44 | 30-DEC-00:40 | 5.33 | 1.33 |
Annual Sum or Average | 0.281590E+12 | 0.120621E+12 | ||||||||
Minimum of Months | 0.178141E+11 | 11658.96 | 5.00 | 0.61 | 0.851870E+10 | 6460.84 | 5.33 | 0.61 | ||
Maximum of Months | 0.267827E+11 | 15980.31 | 40.83 | 20.81 | 0.107630E+11 | 6608.44 | 40.83 | 20.81 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.675816E+11 | 73990.25 | 11-JAN-06:27 | 7.50 | 6.45 | 0.315053E+11 | 19908.85 | 11-JAN-01:00 | 7.50 | 6.45 |
February | 0.560402E+11 | 55655.86 | 24-FEB-05:54 | 7.00 | 7.00 | 0.273843E+11 | 19550.23 | 28-FEB-00:20 | 6.67 | 5.49 |
March | 0.646312E+11 | 56343.11 | 24-MAR-04:43 | 6.70 | 4.74 | 0.309270E+11 | 19600.98 | 14-MAR-04:00 | 6.70 | 4.74 |
April | 0.741729E+11 | 43163.18 | 14-APR-21:10 | 28.67 | 13.19 | 0.311345E+11 | 19188.14 | 20-APR-04:40 | 13.00 | 5.28 |
May | 0.798707E+11 | 42577.69 | 09-MAY-21:10 | 28.83 | 12.76 | 0.322825E+11 | 19185.76 | 26-MAY-03:09 | 21.00 | 13.54 |
June | 0.859703E+11 | 48445.70 | 28-JUN-20:10 | 36.67 | 15.41 | 0.315194E+11 | 19185.25 | 05-JUN-04:10 | 36.67 | 15.41 |
July | 0.872686E+11 | 47508.45 | 21-JUL-20:10 | 36.50 | 20.90 | 0.324250E+11 | 19184.79 | 01-JUL-00:10 | 36.50 | 20.90 |
August | 0.869556E+11 | 46971.73 | 15-AUG-20:10 | 34.67 | 18.05 | 0.325774E+11 | 19184.37 | 10-AUG-22:00 | 34.67 | 18.05 |
September | 0.823107E+11 | 46803.73 | 07-SEP-21:10 | 32.75 | 19.42 | 0.314573E+11 | 19184.58 | 15-SEP-03:09 | 19.90 | 14.65 |
October | 0.758382E+11 | 70167.46 | 30-OCT-04:57 | 9.00 | 5.54 | 0.320716E+11 | 19445.11 | 25-OCT-04:10 | 9.00 | 5.54 |
November | 0.658348E+11 | 43544.48 | 30-NOV-05:05 | 8.00 | 2.43 | 0.304591E+11 | 19633.35 | 04-NOV-04:40 | 8.00 | 2.43 |
December | 0.630878E+11 | 56524.22 | 04-DEC-23:27 | 3.50 | -0.8 | 0.306179E+11 | 19783.50 | 30-DEC-00:40 | 5.33 | 1.33 |
Annual Sum or Average | 0.889563E+12 | 0.374361E+12 | ||||||||
Minimum of Months | 0.560402E+11 | 42577.69 | 3.50 | -0.8 | 0.273843E+11 | 19184.37 | 5.33 | 1.33 | ||
Maximum of Months | 0.872686E+11 | 73990.25 | 36.67 | 20.90 | 0.325774E+11 | 19908.85 | 36.67 | 20.90 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100486E+10 | 3726.19 | 31-JAN-16:01 | 29.00 | 10.73 | 97925458.73 | 56.69 | 19-JAN-22:40 | 29.00 | 10.73 |
February | 0.389383E+09 | 3516.04 | 22-FEB-16:01 | 20.83 | 11.61 | 87163594.68 | 56.69 | 21-FEB-22:19 | 20.83 | 11.61 |
March | 0.825676E+09 | 3684.94 | 18-MAR-15:02 | 27.20 | 12.30 | 97556285.93 | 56.69 | 21-MAR-21:10 | 18.62 | 10.88 |
April | 0.235502E+10 | 3772.61 | 14-APR-15:01 | 35.00 | 14.57 | 95574049.06 | 56.70 | 24-APR-23:30 | 26.50 | 13.00 |
May | 0.279655E+10 | 3758.40 | 30-MAY-18:01 | 31.83 | 13.91 | 99016415.84 | 56.70 | 10-MAY-23:49 | 31.83 | 13.91 |
June | 0.355455E+10 | 3784.51 | 27-JUN-18:02 | 39.83 | 15.83 | 96091595.54 | 56.70 | 29-JUN-22:10 | 33.83 | 15.97 |
July | 0.326302E+10 | 3762.12 | 05-JUL-18:02 | 37.83 | 16.08 | 99087927.99 | 56.70 | 20-JUL-23:19 | 32.67 | 18.65 |
August | 0.320104E+10 | 3775.55 | 27-AUG-15:02 | 40.00 | 18.27 | 99162043.83 | 56.70 | 11-AUG-21:00 | 40.00 | 18.27 |
September | 0.279591E+10 | 3792.54 | 28-SEP-15:01 | 37.52 | 15.49 | 95830173.62 | 56.70 | 08-SEP-22:10 | 37.52 | 15.49 |
October | 0.190424E+10 | 3784.39 | 06-OCT-15:01 | 35.00 | 14.90 | 98539702.71 | 56.70 | 03-OCT-00:30 | 35.00 | 14.90 |
November | 0.101357E+10 | 3752.56 | 20-NOV-16:01 | 26.83 | 12.13 | 94728350.29 | 56.69 | 01-NOV-21:00 | 26.83 | 12.13 |
December | 0.536315E+09 | 3660.65 | 25-DEC-16:02 | 25.67 | 11.87 | 97109516.64 | 56.69 | 26-DEC-22:19 | 14.67 | 7.12 |
Annual Sum or Average | 0.236401E+11 | 0.115779E+10 | ||||||||
Minimum of Months | 0.389383E+09 | 3516.04 | 20.83 | 10.73 | 87163594.68 | 56.69 | 14.67 | 7.12 | ||
Maximum of Months | 0.355455E+10 | 3792.54 | 40.00 | 18.27 | 99162043.83 | 56.70 | 40.00 | 18.65 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485590E+09 | 3639.64 | 31-JAN-16:01 | 29.00 | 10.73 | 96505165.68 | 56.69 | 27-JAN-22:10 | 29.00 | 10.73 |
February | 0.196466E+09 | 3445.19 | 22-FEB-16:01 | 20.83 | 11.61 | 86138019.32 | 56.69 | 21-FEB-22:30 | 20.83 | 11.61 |
March | 0.611836E+09 | 3611.88 | 18-MAR-15:02 | 27.20 | 12.30 | 96842711.08 | 56.69 | 16-MAR-22:19 | 27.20 | 12.30 |
April | 0.209948E+10 | 3738.40 | 25-APR-18:01 | 31.67 | 15.03 | 95473896.02 | 56.70 | 12-APR-23:10 | 31.67 | 15.03 |
May | 0.272992E+10 | 3741.29 | 30-MAY-18:01 | 31.83 | 13.91 | 99023171.92 | 56.70 | 10-MAY-23:49 | 31.83 | 13.91 |
June | 0.359259E+10 | 3770.32 | 27-JUN-18:02 | 39.83 | 15.83 | 96125782.08 | 56.70 | 19-JUN-21:10 | 39.83 | 15.83 |
July | 0.325151E+10 | 3746.56 | 05-JUL-18:02 | 37.83 | 16.08 | 99100405.84 | 56.70 | 20-JUL-23:19 | 32.67 | 18.65 |
August | 0.305270E+10 | 3736.16 | 25-AUG-18:02 | 38.67 | 17.09 | 99149726.42 | 56.70 | 11-AUG-21:40 | 38.67 | 17.09 |
September | 0.253410E+10 | 3732.69 | 28-SEP-15:01 | 37.52 | 15.49 | 95785022.17 | 56.70 | 07-SEP-21:49 | 37.52 | 15.49 |
October | 0.144778E+10 | 3719.53 | 06-OCT-15:01 | 35.00 | 14.90 | 97985109.79 | 56.70 | 03-OCT-23:49 | 35.00 | 14.90 |
November | 0.567366E+09 | 3666.17 | 20-NOV-16:01 | 26.83 | 12.13 | 93667679.32 | 56.69 | 02-NOV-23:40 | 26.83 | 12.13 |
December | 0.219299E+09 | 3554.71 | 25-DEC-16:02 | 25.67 | 11.87 | 95320451.52 | 56.69 | 21-DEC-04:10 | 25.67 | 11.87 |
Annual Sum or Average | 0.207886E+11 | 0.115112E+10 | ||||||||
Minimum of Months | 0.196466E+09 | 3445.19 | 20.83 | 10.73 | 86138019.32 | 56.69 | 20.83 | 10.73 | ||
Maximum of Months | 0.359259E+10 | 3770.32 | 39.83 | 17.09 | 99149726.42 | 56.70 | 39.83 | 18.65 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.689693E+09 | 692.43 | 14-JAN-13:50 | 26.83 | 10.99 | 0.00 | 0.00 | 01-JAN-00:10 | 26.83 | 10.99 |
February | 0.320791E+09 | 533.39 | 01-FEB-15:30 | 15.50 | 6.96 | 0.00 | 0.00 | 01-FEB-00:10 | 15.50 | 6.96 |
March | 0.367391E+09 | 512.74 | 18-MAR-14:30 | 26.65 | 12.20 | 0.00 | 0.00 | 01-MAR-00:10 | 26.65 | 12.20 |
April | 0.672508E+09 | 540.34 | 14-APR-13:40 | 34.00 | 14.40 | 0.00 | 0.00 | 01-APR-00:10 | 34.00 | 14.40 |
May | 0.696912E+09 | 451.74 | 09-MAY-17:17 | 34.67 | 14.40 | 0.00 | 0.00 | 01-MAY-00:10 | 34.67 | 14.40 |
June | 0.879110E+09 | 556.09 | 28-JUN-17:13 | 41.67 | 18.88 | 0.00 | 0.00 | 01-JUN-00:10 | 41.67 | 18.88 |
July | 0.893734E+09 | 529.12 | 21-JUL-19:10 | 37.83 | 19.56 | 0.00 | 0.00 | 01-JUL-00:10 | 37.83 | 19.56 |
August | 0.931215E+09 | 617.82 | 27-AUG-14:00 | 40.00 | 18.27 | 0.00 | 0.00 | 01-AUG-00:10 | 40.00 | 18.27 |
September | 0.915108E+09 | 692.01 | 28-SEP-13:40 | 36.47 | 16.05 | 0.00 | 0.00 | 01-SEP-00:10 | 36.47 | 16.05 |
October | 0.787308E+09 | 706.78 | 18-OCT-13:50 | 30.83 | 12.20 | 0.00 | 0.00 | 01-OCT-00:10 | 30.83 | 12.20 |
November | 0.594187E+09 | 728.57 | 20-NOV-14:30 | 27.00 | 11.68 | 0.00 | 0.00 | 01-NOV-00:10 | 27.00 | 11.68 |
December | 0.538288E+09 | 686.94 | 25-DEC-13:40 | 25.67 | 11.87 | 0.00 | 0.00 | 01-DEC-00:10 | 25.67 | 11.87 |
Annual Sum or Average | 0.828625E+10 | 0.00 | ||||||||
Minimum of Months | 0.320791E+09 | 451.74 | 15.50 | 6.96 | 0.00 | 0.00 | 15.50 | 6.96 | ||
Maximum of Months | 0.931215E+09 | 728.57 | 41.67 | 19.56 | 0.00 | 0.00 | 41.67 | 19.56 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.246504E+09 | 1129.55 | 31-JAN-19:01 | 23.00 | 8.93 | 95624296.55 | 56.69 | 06-JAN-22:19 | 23.00 | 8.93 |
February | 0.185109E+09 | 911.15 | 20-FEB-09:02 | 12.33 | 11.58 | 86287496.05 | 56.69 | 16-FEB-22:30 | 12.33 | 11.58 |
March | 0.340031E+09 | 1211.57 | 15-MAR-18:01 | 26.55 | 12.82 | 96209918.23 | 56.69 | 06-MAR-00:30 | 26.55 | 12.82 |
April | 0.707028E+09 | 1267.98 | 25-APR-18:01 | 31.67 | 15.03 | 94524028.74 | 56.69 | 24-APR-23:40 | 31.67 | 15.03 |
May | 0.928264E+09 | 1269.49 | 30-MAY-18:01 | 31.83 | 13.91 | 98436031.26 | 56.69 | 22-MAY-23:10 | 31.83 | 13.91 |
June | 0.119903E+10 | 1272.81 | 27-JUN-18:02 | 39.83 | 15.83 | 95802303.98 | 56.70 | 23-JUN-21:10 | 39.83 | 15.83 |
July | 0.117196E+10 | 1270.15 | 07-JUL-18:02 | 36.83 | 15.93 | 98785676.36 | 56.69 | 07-JUL-21:10 | 32.00 | 15.37 |
August | 0.107758E+10 | 1266.43 | 27-AUG-15:02 | 40.00 | 18.27 | 98735004.57 | 56.69 | 02-AUG-21:49 | 40.00 | 18.27 |
September | 0.941845E+09 | 1269.39 | 18-SEP-18:01 | 34.12 | 16.15 | 95257541.64 | 56.69 | 06-SEP-21:40 | 34.12 | 16.15 |
October | 0.577277E+09 | 1266.99 | 05-OCT-18:01 | 31.50 | 15.38 | 97005283.46 | 56.69 | 03-OCT-21:19 | 31.50 | 15.38 |
November | 0.281836E+09 | 1139.14 | 20-NOV-16:01 | 26.83 | 12.13 | 92765553.52 | 56.69 | 02-NOV-21:10 | 26.83 | 12.13 |
December | 0.149734E+09 | 975.20 | 23-DEC-09:02 | 14.67 | 5.62 | 95111275.85 | 56.69 | 12-DEC-22:00 | 14.67 | 5.62 |
Annual Sum or Average | 0.780620E+10 | 0.114454E+10 | ||||||||
Minimum of Months | 0.149734E+09 | 911.15 | 12.33 | 5.62 | 86287496.05 | 56.69 | 12.33 | 5.62 | ||
Maximum of Months | 0.119903E+10 | 1272.81 | 40.00 | 18.27 | 98785676.36 | 56.70 | 40.00 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.959050E+09 | 3267.06 | 31-JAN-16:01 | 29.00 | 10.73 | 98269640.92 | 56.69 | 19-JAN-22:40 | 29.00 | 10.73 |
February | 0.442009E+09 | 3063.22 | 22-FEB-16:01 | 20.83 | 11.61 | 87672507.39 | 56.69 | 21-FEB-22:40 | 20.83 | 11.61 |
March | 0.861305E+09 | 3242.19 | 18-MAR-15:02 | 27.20 | 12.30 | 98061539.56 | 56.69 | 16-MAR-23:30 | 27.20 | 12.30 |
April | 0.238344E+10 | 3314.68 | 14-APR-15:01 | 35.00 | 14.57 | 95914077.59 | 56.69 | 25-APR-01:10 | 24.83 | 12.77 |
May | 0.287587E+10 | 3318.34 | 18-MAY-08:61 | 27.33 | 12.53 | 99198528.91 | 56.69 | 11-MAY-00:10 | 27.33 | 12.53 |
June | 0.363344E+10 | 3339.02 | 19-JUN-08:61 | 31.17 | 13.53 | 96062397.25 | 56.70 | 27-JUN-21:10 | 35.50 | 14.88 |
July | 0.347298E+10 | 3319.28 | 01-JUL-08:61 | 27.50 | 10.46 | 99139180.64 | 56.70 | 21-JUL-00:30 | 31.50 | 18.29 |
August | 0.337372E+10 | 3330.17 | 27-AUG-08:61 | 29.67 | 14.57 | 99231468.91 | 56.70 | 17-AUG-22:00 | 29.67 | 14.57 |
September | 0.288641E+10 | 3334.45 | 28-SEP-15:01 | 37.52 | 15.49 | 95920154.96 | 56.70 | 07-SEP-22:40 | 37.52 | 15.49 |
October | 0.196917E+10 | 3324.90 | 06-OCT-15:01 | 35.00 | 14.90 | 98837516.08 | 56.70 | 02-OCT-21:10 | 35.00 | 14.90 |
November | 0.947412E+09 | 3273.66 | 20-NOV-16:01 | 26.83 | 12.13 | 94975851.15 | 56.70 | 02-NOV-21:10 | 26.83 | 12.13 |
December | 0.546437E+09 | 3197.66 | 25-DEC-16:02 | 25.67 | 11.87 | 97442324.31 | 56.69 | 26-DEC-22:19 | 14.67 | 7.12 |
Annual Sum or Average | 0.243512E+11 | 0.116073E+10 | ||||||||
Minimum of Months | 0.442009E+09 | 3063.22 | 20.83 | 10.46 | 87672507.39 | 56.69 | 14.67 | 7.12 | ||
Maximum of Months | 0.363344E+10 | 3339.02 | 37.52 | 15.49 | 99231468.91 | 56.70 | 37.52 | 18.29 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.439311E+09 | 3188.04 | 31-JAN-16:01 | 29.00 | 10.73 | 96728298.16 | 56.69 | 19-JAN-22:10 | 29.00 | 10.73 |
February | 0.227545E+09 | 2821.31 | 22-FEB-16:01 | 20.83 | 11.61 | 86575936.28 | 56.69 | 21-FEB-22:10 | 20.83 | 11.61 |
March | 0.635826E+09 | 3203.87 | 15-MAR-15:01 | 28.30 | 12.89 | 97378897.88 | 56.69 | 22-MAR-21:10 | 13.35 | 7.10 |
April | 0.211700E+10 | 3272.49 | 14-APR-15:01 | 35.00 | 14.57 | 95901876.62 | 56.69 | 25-APR-00:30 | 25.50 | 13.09 |
May | 0.280701E+10 | 3299.57 | 18-MAY-08:61 | 27.33 | 12.53 | 99198496.29 | 56.69 | 29-MAY-23:10 | 24.83 | 13.80 |
June | 0.367091E+10 | 3323.48 | 19-JUN-08:61 | 31.17 | 13.53 | 96076514.98 | 56.70 | 27-JUN-21:10 | 35.50 | 14.88 |
July | 0.346066E+10 | 3303.73 | 01-JUL-08:61 | 27.50 | 10.46 | 99139677.26 | 56.70 | 31-JUL-23:10 | 30.52 | 18.25 |
August | 0.322350E+10 | 3306.40 | 27-AUG-08:61 | 29.67 | 14.57 | 99227851.78 | 56.70 | 11-AUG-22:30 | 29.67 | 14.57 |
September | 0.262058E+10 | 3282.02 | 28-SEP-15:01 | 37.52 | 15.49 | 95911232.49 | 56.70 | 08-SEP-22:19 | 37.52 | 15.49 |
October | 0.149117E+10 | 3267.68 | 06-OCT-15:01 | 35.00 | 14.90 | 98431661.70 | 56.70 | 03-OCT-21:10 | 35.00 | 14.90 |
November | 0.509417E+09 | 3188.91 | 20-NOV-16:01 | 26.83 | 12.13 | 93771967.87 | 56.69 | 03-NOV-00:10 | 26.83 | 12.13 |
December | 0.214165E+09 | 2984.25 | 25-DEC-16:02 | 25.67 | 11.87 | 95459750.31 | 56.69 | 29-DEC-05:19 | 6.67 | 2.09 |
Annual Sum or Average | 0.214171E+11 | 0.115380E+10 | ||||||||
Minimum of Months | 0.214165E+09 | 2821.31 | 20.83 | 10.46 | 86575936.28 | 56.69 | 6.67 | 2.09 | ||
Maximum of Months | 0.367091E+10 | 3323.48 | 37.52 | 15.49 | 99227851.78 | 56.70 | 37.52 | 18.25 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.379529E+10 | 2812.72 | 30-JAN-05:38 | 7.33 | 2.10 | 0.144882E+10 | 920.50 | 31-JAN-22:40 | 13.83 | 4.56 |
February | 0.312126E+10 | 2756.01 | 02-FEB-02:35 | 7.33 | 3.96 | 0.123261E+10 | 906.07 | 01-FEB-00:10 | 7.33 | 3.96 |
March | 0.371117E+10 | 2441.21 | 13-MAR-04:40 | 6.27 | 5.44 | 0.142937E+10 | 923.52 | 17-MAR-21:40 | 20.87 | 12.09 |
April | 0.462494E+10 | 3199.76 | 14-APR-18:15 | 33.00 | 13.86 | 0.153908E+10 | 951.86 | 25-APR-00:10 | 25.83 | 13.25 |
May | 0.532898E+10 | 3270.32 | 31-MAY-18:30 | 35.00 | 13.18 | 0.161663E+10 | 951.88 | 10-MAY-23:30 | 35.00 | 13.18 |
June | 0.643111E+10 | 4159.59 | 28-JUN-19:10 | 39.50 | 16.83 | 0.157384E+10 | 951.87 | 09-JUN-23:40 | 39.50 | 16.83 |
July | 0.632544E+10 | 3819.18 | 21-JUL-19:10 | 37.83 | 19.56 | 0.161962E+10 | 951.87 | 07-JUL-22:10 | 37.83 | 19.56 |
August | 0.619238E+10 | 3661.06 | 25-AUG-18:15 | 38.33 | 16.79 | 0.162539E+10 | 951.85 | 21-AUG-00:10 | 38.33 | 16.79 |
September | 0.567618E+10 | 3547.23 | 08-SEP-18:15 | 35.90 | 20.02 | 0.156773E+10 | 951.86 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.475861E+10 | 3221.75 | 05-OCT-18:13 | 31.00 | 15.12 | 0.156566E+10 | 951.86 | 19-OCT-22:10 | 19.83 | 11.29 |
November | 0.377627E+10 | 2588.25 | 30-NOV-05:05 | 8.00 | 2.43 | 0.142503E+10 | 949.34 | 02-NOV-21:40 | 8.00 | 2.43 |
December | 0.346355E+10 | 2622.63 | 14-DEC-00:23 | 5.00 | 2.11 | 0.137183E+10 | 893.33 | 26-DEC-22:40 | 14.33 | 6.96 |
Annual Sum or Average | 0.572052E+11 | 0.180156E+11 | ||||||||
Minimum of Months | 0.312126E+10 | 2441.21 | 5.00 | 2.10 | 0.123261E+10 | 893.33 | 7.33 | 2.43 | ||
Maximum of Months | 0.643111E+10 | 4159.59 | 39.50 | 20.02 | 0.162539E+10 | 951.88 | 39.50 | 19.56 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.849227E+09 | 3931.14 | 31-JAN-16:01 | 29.00 | 10.73 | 97585789.93 | 56.69 | 18-JAN-22:10 | 29.00 | 10.73 |
February | 0.312632E+09 | 3706.02 | 22-FEB-16:01 | 20.83 | 11.61 | 86751640.84 | 56.69 | 01-FEB-01:10 | 20.83 | 11.61 |
March | 0.721681E+09 | 3894.52 | 18-MAR-15:02 | 27.20 | 12.30 | 97232441.05 | 56.69 | 19-MAR-03:39 | 11.23 | 7.96 |
April | 0.229941E+10 | 3998.38 | 14-APR-15:01 | 35.00 | 14.57 | 95450574.10 | 56.70 | 11-APR-22:30 | 35.00 | 14.57 |
May | 0.279817E+10 | 3981.25 | 07-MAY-15:01 | 35.17 | 13.95 | 98939729.02 | 56.70 | 10-MAY-22:00 | 26.00 | 15.12 |
June | 0.371622E+10 | 4009.02 | 27-JUN-18:02 | 39.83 | 15.83 | 96103356.71 | 56.70 | 29-JUN-21:49 | 34.17 | 16.06 |
July | 0.338911E+10 | 3981.48 | 05-JUL-18:02 | 37.83 | 16.08 | 99074892.12 | 56.70 | 11-JUL-21:40 | 31.00 | 19.81 |
August | 0.330183E+10 | 4002.75 | 27-AUG-15:02 | 40.00 | 18.27 | 99139388.35 | 56.70 | 17-AUG-21:30 | 40.00 | 18.27 |
September | 0.280856E+10 | 4017.08 | 28-SEP-15:01 | 37.52 | 15.49 | 95770336.64 | 56.70 | 06-SEP-21:10 | 37.52 | 15.49 |
October | 0.176035E+10 | 4002.21 | 06-OCT-15:01 | 35.00 | 14.90 | 98306588.43 | 56.70 | 01-OCT-23:10 | 35.00 | 14.90 |
November | 0.843652E+09 | 3967.99 | 20-NOV-16:01 | 26.83 | 12.13 | 94370169.51 | 56.69 | 02-NOV-22:00 | 26.83 | 12.13 |
December | 0.442349E+09 | 3863.03 | 25-DEC-16:02 | 25.67 | 11.87 | 96668982.11 | 56.69 | 26-DEC-22:30 | 14.50 | 7.04 |
Annual Sum or Average | 0.232432E+11 | 0.115539E+10 | ||||||||
Minimum of Months | 0.312632E+09 | 3706.02 | 20.83 | 10.73 | 86751640.84 | 56.69 | 11.23 | 7.04 | ||
Maximum of Months | 0.371622E+10 | 4017.08 | 40.00 | 18.27 | 99139388.35 | 56.70 | 40.00 | 19.81 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.375918E+09 | 3826.24 | 31-JAN-16:01 | 29.00 | 10.73 | 95984400.18 | 56.69 | 26-JAN-05:40 | 29.00 | 10.73 |
February | 0.152226E+09 | 3620.51 | 22-FEB-16:01 | 20.83 | 11.61 | 85633571.45 | 56.69 | 21-FEB-22:10 | 20.83 | 11.61 |
March | 0.517937E+09 | 3810.61 | 18-MAR-15:02 | 27.20 | 12.30 | 96469234.21 | 56.69 | 22-MAR-02:20 | 15.67 | 9.94 |
April | 0.203560E+10 | 3952.25 | 25-APR-18:01 | 31.67 | 15.03 | 95354319.67 | 56.70 | 11-APR-22:10 | 31.67 | 15.03 |
May | 0.272939E+10 | 3950.93 | 30-MAY-18:01 | 31.83 | 13.91 | 98948852.61 | 56.70 | 10-MAY-22:49 | 31.83 | 13.91 |
June | 0.375525E+10 | 3992.03 | 27-JUN-18:02 | 39.83 | 15.83 | 96142128.97 | 56.70 | 29-JUN-21:00 | 34.00 | 15.96 |
July | 0.337685E+10 | 3962.87 | 05-JUL-18:02 | 37.83 | 16.08 | 99089300.10 | 56.70 | 20-JUL-22:40 | 33.00 | 18.53 |
August | 0.314773E+10 | 3956.15 | 25-AUG-18:02 | 38.67 | 17.09 | 99118545.50 | 56.70 | 01-AUG-21:10 | 38.67 | 17.09 |
September | 0.253695E+10 | 3948.59 | 28-SEP-15:01 | 37.52 | 15.49 | 95718321.14 | 56.70 | 07-SEP-21:30 | 37.52 | 15.49 |
October | 0.130683E+10 | 3928.09 | 06-OCT-15:01 | 35.00 | 14.90 | 97678210.46 | 56.70 | 03-OCT-22:19 | 35.00 | 14.90 |
November | 0.432901E+09 | 3863.64 | 20-NOV-16:01 | 26.83 | 12.13 | 93161113.93 | 56.70 | 22-NOV-01:19 | 14.33 | 7.48 |
December | 0.172540E+09 | 3732.14 | 25-DEC-16:02 | 25.67 | 11.87 | 94719433.27 | 56.69 | 21-DEC-04:10 | 25.67 | 11.87 |
Annual Sum or Average | 0.205401E+11 | 0.114802E+10 | ||||||||
Minimum of Months | 0.152226E+09 | 3620.51 | 20.83 | 10.73 | 85633571.45 | 56.69 | 14.33 | 7.48 | ||
Maximum of Months | 0.375525E+10 | 3992.03 | 39.83 | 17.09 | 99118545.50 | 56.70 | 38.67 | 18.53 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117379E+10 | 2010.56 | 31-JAN-16:01 | 29.00 | 10.73 | 98579522.48 | 56.69 | 26-JAN-22:19 | 29.00 | 10.73 |
February | 0.506901E+09 | 1878.98 | 22-FEB-16:01 | 20.83 | 11.61 | 87996438.72 | 56.83 | 06-FEB-23:49 | 20.83 | 11.61 |
March | 0.648869E+09 | 1985.33 | 18-MAR-15:02 | 27.20 | 12.30 | 97932587.78 | 56.69 | 16-MAR-22:10 | 27.20 | 12.30 |
April | 0.132246E+10 | 2006.31 | 14-APR-15:01 | 35.00 | 14.57 | 95488379.17 | 56.69 | 19-APR-21:30 | 20.50 | 9.19 |
May | 0.141488E+10 | 1985.78 | 07-MAY-15:01 | 35.17 | 13.95 | 98899230.80 | 56.69 | 10-MAY-23:30 | 25.50 | 14.96 |
June | 0.180789E+10 | 1982.65 | 27-JUN-15:02 | 41.00 | 15.93 | 95945129.48 | 56.70 | 29-JUN-21:00 | 34.00 | 15.96 |
July | 0.181994E+10 | 1975.20 | 07-JUL-15:02 | 37.00 | 15.61 | 99032260.43 | 56.70 | 24-JUL-21:40 | 31.00 | 18.54 |
August | 0.187237E+10 | 2001.21 | 26-AUG-15:02 | 41.00 | 16.32 | 99124843.58 | 56.70 | 11-AUG-22:30 | 41.00 | 16.32 |
September | 0.179190E+10 | 2029.74 | 28-SEP-15:01 | 37.52 | 15.49 | 95823528.40 | 56.70 | 08-SEP-22:00 | 37.52 | 15.49 |
October | 0.144982E+10 | 2025.86 | 06-OCT-15:01 | 35.00 | 14.90 | 98710800.03 | 56.70 | 03-OCT-21:00 | 35.00 | 14.90 |
November | 0.102910E+10 | 2021.11 | 20-NOV-16:01 | 26.83 | 12.13 | 95187655.67 | 56.69 | 02-NOV-22:19 | 26.83 | 12.13 |
December | 0.864418E+09 | 1991.39 | 25-DEC-16:02 | 25.67 | 11.87 | 98203827.44 | 56.69 | 26-DEC-22:49 | 14.17 | 6.88 |
Annual Sum or Average | 0.157024E+11 | 0.116092E+10 | ||||||||
Minimum of Months | 0.506901E+09 | 1878.98 | 20.83 | 10.73 | 87996438.72 | 56.69 | 14.17 | 6.88 | ||
Maximum of Months | 0.187237E+10 | 2029.74 | 41.00 | 16.32 | 99124843.58 | 56.83 | 41.00 | 18.54 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382182E+11 | 33791.94 | 10-JAN-05:05 | 8.00 | 6.84 | 0.177673E+11 | 12165.18 | 11-JAN-01:00 | 7.00 | 6.45 |
February | 0.338226E+11 | 31904.40 | 24-FEB-05:54 | 7.00 | 7.00 | 0.159081E+11 | 12082.30 | 28-FEB-00:20 | 6.67 | 5.49 |
March | 0.392117E+11 | 32267.07 | 24-MAR-04:43 | 6.70 | 4.74 | 0.180312E+11 | 12086.28 | 14-MAR-04:00 | 6.70 | 4.74 |
April | 0.426160E+11 | 29430.07 | 21-APR-03:54 | 8.00 | 0.42 | 0.180944E+11 | 11346.64 | 15-APR-01:19 | 8.00 | 0.42 |
May | 0.460978E+11 | 22865.87 | 09-MAY-21:10 | 28.83 | 12.76 | 0.189044E+11 | 11347.06 | 26-MAY-02:00 | 21.00 | 13.75 |
June | 0.480914E+11 | 24844.64 | 28-JUN-21:20 | 34.33 | 14.34 | 0.184848E+11 | 11356.00 | 29-JUN-21:19 | 34.67 | 16.35 |
July | 0.488680E+11 | 24361.85 | 21-JUL-21:10 | 33.83 | 20.81 | 0.189901E+11 | 11353.24 | 11-JUL-22:00 | 33.83 | 20.81 |
August | 0.481468E+11 | 23835.65 | 10-AUG-21:10 | 33.33 | 18.08 | 0.190214E+11 | 11345.96 | 20-AUG-23:19 | 26.67 | 16.09 |
September | 0.451602E+11 | 23589.71 | 07-SEP-21:10 | 32.75 | 19.42 | 0.182933E+11 | 11345.59 | 15-SEP-23:30 | 21.90 | 13.27 |
October | 0.421391E+11 | 25816.82 | 12-OCT-04:42 | 7.17 | 3.07 | 0.183937E+11 | 12177.86 | 25-OCT-04:10 | 7.00 | 1.34 |
November | 0.376062E+11 | 25232.52 | 30-NOV-05:05 | 8.00 | 2.43 | 0.173032E+11 | 12320.50 | 04-NOV-04:40 | 8.00 | 2.43 |
December | 0.364239E+11 | 31224.53 | 14-DEC-23:37 | 6.00 | 1.03 | 0.174007E+11 | 12464.25 | 19-DEC-23:40 | 5.67 | 0.87 |
Annual Sum or Average | 0.506402E+12 | 0.216593E+12 | ||||||||
Minimum of Months | 0.338226E+11 | 22865.87 | 6.00 | 0.42 | 0.159081E+11 | 11345.59 | 5.67 | 0.42 | ||
Maximum of Months | 0.488680E+11 | 33791.94 | 34.33 | 20.81 | 0.190214E+11 | 12464.25 | 34.67 | 20.81 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.400946E+11 | 33422.31 | 09-JAN-23:55 | 8.00 | 7.43 | 0.182149E+11 | 12392.58 | 11-JAN-01:00 | 7.00 | 6.45 |
February | 0.357327E+11 | 33994.67 | 24-FEB-05:54 | 7.00 | 7.00 | 0.163948E+11 | 12334.33 | 28-FEB-00:20 | 6.67 | 5.49 |
March | 0.412780E+11 | 33919.77 | 24-MAR-04:43 | 6.70 | 4.74 | 0.184797E+11 | 12115.01 | 14-MAR-04:00 | 6.70 | 4.74 |
April | 0.445757E+11 | 33246.64 | 21-APR-03:54 | 8.00 | 0.42 | 0.183310E+11 | 11421.41 | 28-APR-04:49 | 13.33 | 6.61 |
May | 0.482473E+11 | 24223.83 | 09-MAY-21:10 | 28.83 | 12.76 | 0.190816E+11 | 11347.21 | 26-MAY-02:00 | 21.00 | 13.75 |
June | 0.503191E+11 | 26255.11 | 28-JUN-21:20 | 34.33 | 14.34 | 0.186192E+11 | 11383.72 | 16-JUN-21:19 | 34.33 | 14.34 |
July | 0.511123E+11 | 25745.56 | 21-JUL-21:10 | 33.83 | 20.81 | 0.191388E+11 | 11380.76 | 07-JUL-21:19 | 33.83 | 20.81 |
August | 0.503298E+11 | 25199.47 | 10-AUG-21:10 | 33.33 | 18.08 | 0.191776E+11 | 11357.86 | 15-AUG-22:30 | 30.50 | 16.87 |
September | 0.471904E+11 | 24937.72 | 07-SEP-21:10 | 32.75 | 19.42 | 0.184559E+11 | 11347.82 | 08-SEP-21:30 | 30.80 | 19.18 |
October | 0.440291E+11 | 27337.25 | 25-OCT-04:40 | 7.00 | 1.35 | 0.186957E+11 | 12390.90 | 25-OCT-04:10 | 7.00 | 1.35 |
November | 0.393861E+11 | 27641.91 | 08-NOV-03:30 | 8.00 | 2.81 | 0.177223E+11 | 12483.53 | 04-NOV-04:40 | 8.00 | 2.81 |
December | 0.384472E+11 | 34171.80 | 14-DEC-23:37 | 6.00 | 1.03 | 0.179478E+11 | 12743.98 | 19-DEC-23:40 | 5.67 | 0.87 |
Annual Sum or Average | 0.530742E+12 | 0.220259E+12 | ||||||||
Minimum of Months | 0.357327E+11 | 24223.83 | 6.00 | 0.42 | 0.163948E+11 | 11347.21 | 5.67 | 0.87 | ||
Maximum of Months | 0.511123E+11 | 34171.80 | 34.33 | 20.81 | 0.191776E+11 | 12743.98 | 34.33 | 20.81 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.515866E+11 | 36405.13 | 13-JAN-07:39 | 6.67 | 4.41 | 0.188724E+11 | 11319.63 | 14-JAN-18:19 | 20.00 | 9.94 |
February | 0.458161E+11 | 34465.36 | 28-FEB-07:13 | 5.67 | 4.84 | 0.170453E+11 | 11368.93 | 04-FEB-18:40 | 5.67 | 4.84 |
March | 0.520867E+11 | 34857.39 | 31-MAR-06:53 | 5.50 | 1.22 | 0.188760E+11 | 11319.65 | 18-MAR-17:19 | 5.50 | 1.22 |
April | 0.548620E+11 | 30564.23 | 30-APR-10:40 | 30.00 | 11.09 | 0.182623E+11 | 11319.75 | 15-APR-17:19 | 30.00 | 11.09 |
May | 0.581250E+11 | 30788.78 | 07-MAY-10:40 | 30.00 | 12.89 | 0.188718E+11 | 11319.66 | 13-MAY-17:19 | 29.67 | 11.30 |
June | 0.589734E+11 | 31667.48 | 18-JUN-10:50 | 35.67 | 17.76 | 0.182662E+11 | 11319.66 | 10-JUN-17:19 | 35.67 | 17.76 |
July | 0.603524E+11 | 31667.26 | 22-JUL-10:40 | 35.67 | 19.48 | 0.188685E+11 | 11319.84 | 08-JUL-17:19 | 35.67 | 19.48 |
August | 0.599956E+11 | 31708.56 | 13-AUG-10:40 | 33.67 | 21.36 | 0.188757E+11 | 11319.71 | 19-AUG-17:19 | 31.33 | 19.30 |
September | 0.567852E+11 | 31427.60 | 09-SEP-10:35 | 33.43 | 20.70 | 0.182619E+11 | 11319.67 | 23-SEP-17:19 | 33.27 | 17.89 |
October | 0.549436E+11 | 32601.45 | 25-OCT-08:07 | 8.50 | 2.37 | 0.188690E+11 | 11319.67 | 14-OCT-17:19 | 8.50 | 2.37 |
November | 0.502170E+11 | 33754.42 | 24-NOV-08:15 | 7.67 | 0.28 | 0.182603E+11 | 11319.51 | 18-NOV-18:19 | 7.67 | 0.28 |
December | 0.498468E+11 | 35437.30 | 29-DEC-08:10 | 6.83 | 2.24 | 0.188743E+11 | 11319.49 | 23-DEC-18:19 | 6.83 | 2.24 |
Annual Sum or Average | 0.653590E+12 | 0.222204E+12 | ||||||||
Minimum of Months | 0.458161E+11 | 30564.23 | 5.50 | 0.28 | 0.170453E+11 | 11319.49 | 5.50 | 0.28 | ||
Maximum of Months | 0.603524E+11 | 36405.13 | 35.67 | 21.36 | 0.188760E+11 | 11368.93 | 35.67 | 19.48 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.595610E+10 | 4201.26 | 30-JAN-05:38 | 7.33 | 2.10 | 0.154185E+10 | 988.87 | 31-JAN-22:30 | 14.05 | 4.75 |
February | 0.487016E+10 | 4099.66 | 02-FEB-02:35 | 7.33 | 3.96 | 0.131006E+10 | 965.40 | 01-FEB-00:10 | 7.33 | 3.96 |
March | 0.599548E+10 | 4521.25 | 18-MAR-15:00 | 27.20 | 12.54 | 0.153893E+10 | 1007.38 | 16-MAR-22:40 | 27.20 | 12.54 |
April | 0.926215E+10 | 6911.28 | 14-APR-15:03 | 35.00 | 14.57 | 0.163816E+10 | 1007.42 | 16-APR-23:10 | 18.83 | 12.52 |
May | 0.110669E+11 | 6657.88 | 31-MAY-18:15 | 35.33 | 13.34 | 0.171268E+10 | 1007.44 | 10-MAY-23:19 | 35.33 | 13.34 |
June | 0.140628E+11 | 8515.73 | 28-JUN-18:13 | 40.67 | 17.68 | 0.166580E+10 | 1007.44 | 09-JUN-23:19 | 40.67 | 17.68 |
July | 0.139317E+11 | 7781.02 | 20-JUL-18:17 | 38.33 | 19.15 | 0.171450E+10 | 1007.43 | 07-JUL-22:10 | 38.33 | 19.15 |
August | 0.135055E+11 | 7718.78 | 26-AUG-14:50 | 40.83 | 16.32 | 0.172150E+10 | 1007.41 | 10-AUG-22:00 | 40.83 | 16.32 |
September | 0.119708E+11 | 7723.24 | 07-SEP-15:03 | 37.28 | 19.77 | 0.166083E+10 | 1007.41 | 15-SEP-03:09 | 19.90 | 14.65 |
October | 0.864445E+10 | 7204.97 | 02-OCT-13:10 | 34.17 | 19.45 | 0.165497E+10 | 1007.43 | 19-OCT-22:10 | 19.83 | 11.29 |
November | 0.602791E+10 | 5151.44 | 01-NOV-15:03 | 28.83 | 16.12 | 0.151128E+10 | 1007.39 | 02-NOV-22:10 | 19.83 | 16.01 |
December | 0.517399E+10 | 4012.14 | 14-DEC-00:23 | 5.00 | 2.11 | 0.143429E+10 | 967.16 | 26-DEC-22:30 | 14.50 | 7.04 |
Annual Sum or Average | 0.110468E+12 | 0.191049E+11 | ||||||||
Minimum of Months | 0.487016E+10 | 4012.14 | 5.00 | 2.10 | 0.131006E+10 | 965.40 | 7.33 | 3.96 | ||
Maximum of Months | 0.140628E+11 | 8515.73 | 40.83 | 19.77 | 0.172150E+10 | 1007.44 | 40.83 | 19.15 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89044.72 | 538.69 | 26-JAN-04:50 | 7.17 |
February | 10315.63 | 171.93 | 02-FEB-05:29 | 7.00 |
March | 252285.50 | 638.43 | 25-MAR-03:33 | 7.17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 351645.85 | |||
Minimum of Months | 0.00 | 0.00 | 7.00 | |
Maximum of Months | 252285.50 | 638.43 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6040736.64 | 323.93 | 12-JAN-06:57 | 5.00 |
February | 3147085.27 | 373.46 | 13-FEB-05:43 | 8.00 |
March | 3387426.52 | 351.98 | 07-MAR-05:30 | 7.20 |
April | 7147.20 | 119.12 | 21-APR-03:53 | 8.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 730721.01 | 284.71 | 26-OCT-04:07 | 7.00 |
November | 2506533.19 | 326.30 | 05-NOV-05:56 | 6.00 |
December | 10969401.55 | 351.60 | 30-DEC-07:29 | 5.50 |
Annual Sum or Average | 26789051.38 | |||
Minimum of Months | 0.00 | 0.00 | 5.00 | |
Maximum of Months | 10969401.55 | 373.46 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 902815.50 | 148.08 | 01-JAN-09:17 | 6.10 |
February | 658122.38 | 202.46 | 13-FEB-05:43 | 8.00 |
March | 262409.61 | 143.56 | 07-MAR-05:30 | 7.20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 72082.81 | 85.06 | 26-OCT-04:07 | 7.00 |
November | 298180.41 | 122.23 | 18-NOV-06:17 | 6.00 |
December | 1199459.68 | 237.05 | 18-DEC-07:48 | 4.67 |
Annual Sum or Average | 3393070.39 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 1199459.68 | 237.05 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3617340.33 | 216.41 | 01-JAN-09:17 | 6.10 |
February | 1705879.40 | 238.35 | 13-FEB-05:43 | 8.00 |
March | 767020.10 | 181.31 | 07-MAR-05:30 | 7.20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 217998.63 | 145.54 | 26-OCT-04:07 | 7.00 |
November | 1087660.69 | 187.33 | 27-NOV-05:47 | 7.87 |
December | 4124085.45 | 247.83 | 18-DEC-07:48 | 4.67 |
Annual Sum or Average | 11519984.59 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 4124085.45 | 247.83 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5993538.67 | 266.36 | 26-JAN-04:50 | 7.17 |
February | 2805511.58 | 267.40 | 13-FEB-05:43 | 8.00 |
March | 1627953.47 | 241.09 | 07-MAR-05:30 | 7.20 |
April | 4991.00 | 83.18 | 21-APR-03:53 | 8.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 519337.79 | 219.40 | 26-OCT-04:07 | 7.00 |
November | 2231258.56 | 250.23 | 27-NOV-05:47 | 7.87 |
December | 6330696.63 | 267.77 | 15-DEC-00:28 | 6.00 |
Annual Sum or Average | 19513287.70 | |||
Minimum of Months | 0.00 | 0.00 | 6.00 | |
Maximum of Months | 6330696.63 | 267.77 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11455661.66 | 1971.97 | 12-JAN-07:20 | 5.33 |
February | 4859701.73 | 2362.46 | 02-FEB-07:20 | 6.00 |
March | 1904394.61 | 2296.92 | 30-MAR-06:32 | 5.17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 1589355.36 | 1966.44 | 25-OCT-06:30 | 5.00 |
November | 5048493.76 | 1735.41 | 05-NOV-05:56 | 6.00 |
December | 10557176.33 | 2538.34 | 18-DEC-07:48 | 4.67 |
Annual Sum or Average | 35414783.45 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 11455661.66 | 2538.34 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1970751.59 | 2381.60 | 26-JAN-04:50 | 7.17 |
February | 1071250.32 | 2121.37 | 02-FEB-07:20 | 6.00 |
March | 312450.29 | 2934.72 | 30-MAR-06:32 | 5.17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 41756.17 | 556.75 | 25-OCT-06:30 | 5.00 |
November | 614591.03 | 1450.87 | 05-NOV-05:56 | 6.00 |
December | 3541685.98 | 4043.59 | 18-DEC-07:48 | 4.67 |
Annual Sum or Average | 7552485.38 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 3541685.98 | 4043.59 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 56891796.49 | 2104.63 | 01-JAN-09:01 | 5.90 |
February | 0.123917E+09 | 2059.03 | 08-FEB-09:01 | 10.17 |
March | 85310130.32 | 2101.61 | 26-MAR-08:61 | 7.75 |
April | 1141297.70 | 805.71 | 17-APR-08:03 | 21.30 |
May | 905624.02 | 742.44 | 01-MAY-08:03 | 19.50 |
June | 193765.31 | 327.59 | 13-JUN-08:04 | 25.50 |
July | 392143.18 | 698.31 | 29-JUL-08:04 | 26.33 |
August | 492953.83 | 706.32 | 05-AUG-08:04 | 23.33 |
September | 648573.75 | 789.66 | 04-SEP-08:04 | 23.08 |
October | 9433172.82 | 1159.48 | 25-OCT-08:62 | 8.50 |
November | 40208921.46 | 1467.12 | 24-NOV-09:01 | 9.00 |
December | 0.225364E+09 | 2109.30 | 06-DEC-09:01 | 6.50 |
Annual Sum or Average | 0.544899E+09 | |||
Minimum of Months | 193765.31 | 327.59 | 5.90 | |
Maximum of Months | 0.225364E+09 | 2109.30 | 26.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154218E+09 | 2158.56 | 01-JAN-09:01 | 5.90 |
February | 0.217059E+09 | 2109.35 | 09-FEB-09:01 | 8.50 |
March | 0.126271E+09 | 2116.46 | 26-MAR-08:61 | 7.75 |
April | 1313709.91 | 848.91 | 10-APR-08:03 | 22.50 |
May | 918441.01 | 740.06 | 01-MAY-08:03 | 19.50 |
June | 130577.54 | 267.94 | 13-JUN-08:04 | 25.50 |
July | 361159.17 | 707.93 | 29-JUL-08:04 | 26.33 |
August | 524947.55 | 677.26 | 05-AUG-08:04 | 23.33 |
September | 906076.45 | 786.95 | 04-SEP-08:04 | 23.08 |
October | 23571577.29 | 2055.11 | 25-OCT-08:62 | 8.50 |
November | 0.102206E+09 | 2125.44 | 23-NOV-09:01 | 5.45 |
December | 0.445813E+09 | 2170.22 | 07-DEC-09:01 | 6.67 |
Annual Sum or Average | 0.107329E+10 | |||
Minimum of Months | 130577.54 | 267.94 | 5.45 | |
Maximum of Months | 0.445813E+09 | 2170.22 | 26.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8728503.26 | 627.71 | 02-JAN-09:01 | 12.50 |
February | 5377286.38 | 621.14 | 03-FEB-16:01 | 16.83 |
March | 4388112.79 | 627.63 | 27-MAR-08:61 | 9.77 |
April | 808615.11 | 385.10 | 26-APR-08:04 | 24.33 |
May | 751713.14 | 416.38 | 26-MAY-08:04 | 24.50 |
June | 51816.57 | 108.77 | 30-JUN-08:06 | 31.33 |
July | 80471.63 | 314.22 | 27-JUL-08:05 | 25.33 |
August | 159391.99 | 387.07 | 24-AUG-08:04 | 26.50 |
September | 274999.23 | 342.30 | 29-SEP-08:04 | 26.65 |
October | 958309.10 | 338.92 | 31-OCT-15:03 | 28.00 |
November | 4965461.56 | 629.93 | 24-NOV-09:01 | 9.00 |
December | 41743630.10 | 646.03 | 07-DEC-09:01 | 6.67 |
Annual Sum or Average | 68288310.84 | |||
Minimum of Months | 51816.57 | 108.77 | 6.67 | |
Maximum of Months | 41743630.10 | 646.03 | 31.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66787962.99 | 755.90 | 11-JAN-19:03 | 14.00 |
February | 0.116862E+09 | 1999.25 | 12-FEB-16:02 | 14.00 |
March | 79674962.65 | 1290.09 | 07-MAR-09:02 | 10.87 |
April | 119819.93 | 644.51 | 29-APR-08:04 | 24.33 |
May | 102897.82 | 620.47 | 26-MAY-08:04 | 24.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 31712.23 | 224.15 | 04-AUG-08:05 | 22.33 |
September | 73677.98 | 337.55 | 03-SEP-08:05 | 20.18 |
October | 7625747.47 | 556.62 | 30-OCT-18:04 | 20.67 |
November | 47879579.60 | 963.13 | 25-NOV-16:03 | 17.00 |
December | 0.222481E+09 | 1858.41 | 11-DEC-09:02 | 13.17 |
Annual Sum or Average | 0.541640E+09 | |||
Minimum of Months | 0.00 | 0.00 | 10.87 | |
Maximum of Months | 0.222481E+09 | 1999.25 | 27.73 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162786E+09 | 1991.28 | 01-JAN-16:02 | 15.03 |
February | 0.185229E+09 | 2005.45 | 04-FEB-09:02 | 9.50 |
March | 0.114179E+09 | 1641.97 | 07-MAR-09:02 | 10.87 |
April | 229617.64 | 665.25 | 29-APR-08:04 | 24.33 |
May | 98376.97 | 630.85 | 26-MAY-08:04 | 24.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 24424.45 | 233.94 | 04-AUG-08:05 | 22.33 |
September | 85979.27 | 326.70 | 03-SEP-08:05 | 20.18 |
October | 19463267.71 | 864.21 | 25-OCT-15:03 | 17.00 |
November | 0.111842E+09 | 1519.41 | 23-NOV-19:03 | 8.83 |
December | 0.416671E+09 | 2032.25 | 07-DEC-16:01 | 15.67 |
Annual Sum or Average | 0.101061E+10 | |||
Minimum of Months | 0.00 | 0.00 | 8.83 | |
Maximum of Months | 0.416671E+09 | 2032.25 | 27.73 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5098579.69 | 361.47 | 01-JAN-23:25 | 5.10 |
February | 2504800.74 | 455.63 | 13-FEB-05:43 | 8.00 |
March | 1267145.82 | 314.09 | 07-MAR-05:30 | 7.20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 317001.24 | 198.97 | 26-OCT-04:07 | 7.00 |
November | 1423021.62 | 266.36 | 18-NOV-04:35 | 7.00 |
December | 6156854.00 | 454.47 | 18-DEC-07:48 | 4.67 |
Annual Sum or Average | 16767403.10 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 6156854.00 | 455.63 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180805E+09 | 2505.47 | 01-JAN-09:01 | 5.90 |
February | 0.302898E+09 | 2457.04 | 09-FEB-09:01 | 8.50 |
March | 0.204503E+09 | 2504.75 | 26-MAR-08:61 | 7.75 |
April | 3256056.30 | 863.87 | 24-APR-08:03 | 23.50 |
May | 950506.42 | 910.65 | 13-MAY-08:03 | 21.17 |
June | 182437.14 | 381.10 | 13-JUN-08:04 | 25.50 |
July | 420150.41 | 583.73 | 18-JUL-08:04 | 27.17 |
August | 469401.12 | 718.05 | 05-AUG-08:04 | 23.33 |
September | 969437.72 | 706.79 | 30-SEP-08:04 | 26.05 |
October | 49088893.91 | 2414.05 | 25-OCT-08:62 | 8.50 |
November | 0.137426E+09 | 2474.76 | 23-NOV-09:01 | 5.45 |
December | 0.466452E+09 | 2520.28 | 07-DEC-09:01 | 6.67 |
Annual Sum or Average | 0.134742E+10 | |||
Minimum of Months | 182437.14 | 381.10 | 5.45 | |
Maximum of Months | 0.466452E+09 | 2520.28 | 27.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371367E+09 | 2547.63 | 01-JAN-09:01 | 5.90 |
February | 0.463560E+09 | 2501.51 | 09-FEB-09:01 | 8.50 |
March | 0.276984E+09 | 2516.70 | 26-MAR-08:61 | 7.75 |
April | 5091131.81 | 958.82 | 24-APR-08:03 | 23.50 |
May | 981386.58 | 822.87 | 13-MAY-08:03 | 21.17 |
June | 102466.35 | 319.46 | 13-JUN-08:04 | 25.50 |
July | 384775.81 | 635.00 | 29-JUL-08:04 | 26.33 |
August | 502010.30 | 760.49 | 05-AUG-08:04 | 23.33 |
September | 1109639.96 | 761.20 | 30-SEP-08:04 | 26.05 |
October | 87796516.64 | 2445.30 | 25-OCT-08:62 | 8.50 |
November | 0.268908E+09 | 2534.74 | 23-NOV-09:01 | 5.45 |
December | 0.803372E+09 | 2554.47 | 07-DEC-09:01 | 6.67 |
Annual Sum or Average | 0.228016E+10 | |||
Minimum of Months | 102466.35 | 319.46 | 5.45 | |
Maximum of Months | 0.803372E+09 | 2554.47 | 26.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8344244.80 | 254.68 | 02-JAN-09:03 | 12.50 |
February | 33801882.42 | 1259.17 | 12-FEB-16:02 | 14.00 |
March | 35903524.09 | 1290.83 | 27-MAR-08:61 | 9.77 |
April | 753231.83 | 444.84 | 10-APR-08:03 | 22.50 |
May | 697816.20 | 433.07 | 06-MAY-08:04 | 24.33 |
June | 582950.08 | 439.65 | 21-JUN-08:04 | 27.50 |
July | 539595.87 | 474.76 | 24-JUL-08:04 | 28.00 |
August | 581932.95 | 462.13 | 17-AUG-08:04 | 28.33 |
September | 377602.92 | 407.32 | 29-SEP-08:04 | 26.65 |
October | 1795411.17 | 443.00 | 01-OCT-08:04 | 26.50 |
November | 8827001.90 | 405.56 | 24-NOV-09:03 | 9.00 |
December | 50697622.72 | 452.89 | 17-DEC-16:04 | 15.83 |
Annual Sum or Average | 0.142903E+09 | |||
Minimum of Months | 377602.92 | 254.68 | 9.00 | |
Maximum of Months | 50697622.72 | 1290.83 | 28.33 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2369780.85 | 2319.27 | 22-JAN-05:30 | 7.00 |
February | 479582.86 | 1759.62 | 02-FEB-07:20 | 6.00 |
March | 112685.48 | 1878.09 | 30-MAR-06:32 | 5.17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 90247.34 | 1190.33 | 25-OCT-06:30 | 5.00 |
November | 417092.37 | 874.92 | 05-NOV-05:06 | 6.83 |
December | 3018692.25 | 2483.35 | 06-DEC-08:39 | 4.67 |
Annual Sum or Average | 6488081.14 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 3018692.25 | 2483.35 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 846091.58 | 1836.73 | 22-JAN-05:30 | 7.00 |
February | 162908.47 | 1156.13 | 02-FEB-07:20 | 6.00 |
March | 67022.41 | 1117.04 | 30-MAR-06:32 | 5.17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 44117.08 | 588.23 | 25-OCT-06:30 | 5.00 |
November | 65391.36 | 389.93 | 05-NOV-05:06 | 6.83 |
December | 1006462.12 | 1671.14 | 06-DEC-08:39 | 4.67 |
Annual Sum or Average | 2191993.02 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 1006462.12 | 1836.73 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10770467.93 | 631.26 | 04-JAN-05:53 | 7.00 |
February | 5205014.83 | 752.94 | 13-FEB-05:43 | 8.00 |
March | 2437600.04 | 580.53 | 30-MAR-06:32 | 5.17 |
April | 1216.37 | 20.27 | 21-APR-03:53 | 8.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 848511.22 | 454.13 | 26-OCT-04:07 | 7.00 |
November | 3637463.04 | 547.88 | 27-NOV-05:47 | 7.87 |
December | 12844534.59 | 775.22 | 18-DEC-07:48 | 4.67 |
Annual Sum or Average | 35744808.02 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 12844534.59 | 775.22 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147273E+11 | 14185.34 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.132974E+11 | 14185.34 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.147727E+11 | 14185.34 | 01-MAR-20:10 | 0.127855E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.142280E+11 | 14185.34 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.147528E+11 | 14185.34 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.142932E+11 | 14185.34 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.146876E+11 | 14185.34 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.147784E+11 | 14185.34 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.142337E+11 | 14185.34 | 01-SEP-19:10 | 0.123352E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.147216E+11 | 14185.34 | 02-OCT-19:10 | 0.127549E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.142819E+11 | 14185.34 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.146876E+11 | 14185.34 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.173462E+12 | 0.150255E+12 | ||||
Minimum of Months | 0.132974E+11 | 14185.34 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.147784E+11 | 14185.34 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.731324E+09 | 704.41 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.660319E+09 | 704.41 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.733578E+09 | 704.41 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.706528E+09 | 704.41 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.732592E+09 | 704.41 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.709769E+09 | 704.41 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.729351E+09 | 704.41 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.733860E+09 | 704.41 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.706810E+09 | 704.41 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.731042E+09 | 704.41 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.709205E+09 | 704.41 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.729351E+09 | 704.41 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.861373E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.660319E+09 | 704.41 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.733860E+09 | 704.41 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.846876E+09 | 815.72 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.764651E+09 | 815.72 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.849486E+09 | 815.72 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.818162E+09 | 815.72 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.848344E+09 | 815.72 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.821915E+09 | 815.72 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.844592E+09 | 815.72 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.849812E+09 | 815.72 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.818489E+09 | 815.72 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.846549E+09 | 815.72 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.821262E+09 | 815.72 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.844592E+09 | 815.72 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.997473E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.764651E+09 | 815.72 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.849812E+09 | 815.72 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141236E+10 | 1360.40 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.127524E+10 | 1360.40 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.141672E+10 | 1360.40 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.136448E+10 | 1360.40 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.141481E+10 | 1360.40 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.137074E+10 | 1360.40 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.140855E+10 | 1360.40 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.141726E+10 | 1360.40 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.136502E+10 | 1360.40 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.141182E+10 | 1360.40 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.136965E+10 | 1360.40 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.140855E+10 | 1360.40 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.166352E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.127524E+10 | 1360.40 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.141726E+10 | 1360.40 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.236418E+09 | 227.72 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.213464E+09 | 227.72 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.237147E+09 | 227.72 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.228402E+09 | 227.72 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.236828E+09 | 227.72 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.229450E+09 | 227.72 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.235780E+09 | 227.72 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.237238E+09 | 227.72 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.228493E+09 | 227.72 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.236327E+09 | 227.72 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.229268E+09 | 227.72 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.235780E+09 | 227.72 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.278459E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.213464E+09 | 227.72 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.237238E+09 | 227.72 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.370859E+09 | 357.21 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.334852E+09 | 357.21 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.372002E+09 | 357.21 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.358285E+09 | 357.21 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.371502E+09 | 357.21 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.359929E+09 | 357.21 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.369859E+09 | 357.21 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.372145E+09 | 357.21 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.358428E+09 | 357.21 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.370717E+09 | 357.21 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.359643E+09 | 357.21 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.369859E+09 | 357.21 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.436808E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.334852E+09 | 357.21 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.372145E+09 | 357.21 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.159294E+10 | 1761.91 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.143108E+10 | 1761.91 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.154290E+10 | 1761.91 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.145732E+10 | 1761.91 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.147737E+10 | 1761.91 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.139399E+10 | 1761.91 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.144497E+10 | 1761.91 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.150962E+10 | 1761.91 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.147581E+10 | 1761.91 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.155966E+10 | 1761.91 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.153501E+10 | 1761.91 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.159453E+10 | 1761.91 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.180152E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.139399E+10 | 1761.91 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.159453E+10 | 1761.91 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.104129E+11 | 10265.18 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.939735E+10 | 10265.18 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.103980E+11 | 10265.18 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.998436E+10 | 10265.18 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.103221E+11 | 10265.18 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.996525E+10 | 10265.18 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.102538E+11 | 10265.18 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.103718E+11 | 10265.18 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.100094E+11 | 10265.18 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.103797E+11 | 10265.18 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.100899E+11 | 10265.18 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.103912E+11 | 10265.18 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.121976E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.939735E+10 | 10265.18 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.104129E+11 | 10265.18 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85091918.49 | 76.99 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 76846309.13 | 76.99 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 84415649.14 | 76.99 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 82445007.08 | 76.99 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 84753783.81 | 76.99 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 81790910.76 | 76.99 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 85418966.65 | 76.99 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 84415649.14 | 76.99 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 82467180.11 | 76.99 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 85080831.98 | 76.99 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 82117958.92 | 76.99 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 85430053.17 | 76.99 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.100027E+10 | 0.300992E+10 | ||||
Minimum of Months | 76846309.13 | 76.99 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 85430053.17 | 76.99 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.232638E+10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.210051E+10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.233355E+10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.224750E+10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.233041E+10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.225781E+10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.232011E+10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.233445E+10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.224840E+10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.232548E+10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.225602E+10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.232011E+10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274007E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.210051E+10 | 2240.78 | 0.00 | 0.00 | |
Maximum of Months | 0.233445E+10 | 2240.78 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135397E+09 | 122.50 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.122277E+09 | 122.50 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.134321E+09 | 122.50 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.131185E+09 | 122.50 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.134859E+09 | 122.50 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.130145E+09 | 122.50 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.135918E+09 | 122.50 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.134321E+09 | 122.50 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.131221E+09 | 122.50 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.135380E+09 | 122.50 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.130665E+09 | 122.50 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.135935E+09 | 122.50 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.159162E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.122277E+09 | 122.50 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.135935E+09 | 122.50 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135381E+09 | 122.49 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.122263E+09 | 122.49 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.134305E+09 | 122.49 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.131170E+09 | 122.49 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.134843E+09 | 122.49 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.130129E+09 | 122.49 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.135902E+09 | 122.49 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.134305E+09 | 122.49 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.131205E+09 | 122.49 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.135364E+09 | 122.49 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.130650E+09 | 122.49 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.135919E+09 | 122.49 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.159144E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.122263E+09 | 122.49 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.135919E+09 | 122.49 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 85115186.72 | 77.01 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 76867322.62 | 77.01 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 84438732.44 | 77.01 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 82467551.52 | 77.01 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 84776959.58 | 77.01 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 81813276.33 | 77.01 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 85442324.32 | 77.01 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 84438732.44 | 77.01 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 82489730.61 | 77.01 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 85104097.18 | 77.01 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 82140413.93 | 77.01 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 85453413.86 | 77.01 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.100055E+10 | 0.301074E+10 | ||||
Minimum of Months | 76867322.62 | 77.01 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 85453413.86 | 77.01 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.304304E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.273166E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.297608E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.282542E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.288543E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.275467E+10 | 3094.06 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.284709E+10 | 3094.06 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.292786E+10 | 3094.06 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.284897E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.301378E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.293842E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.303738E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.348298E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.273166E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.304304E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.304304E+10 | 3094.06 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.273166E+10 | 3094.06 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.297608E+10 | 3094.06 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.282542E+10 | 3094.06 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.288543E+10 | 3094.06 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.275467E+10 | 3094.06 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.284709E+10 | 3094.06 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.292786E+10 | 3094.06 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.284897E+10 | 3094.06 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.301378E+10 | 3094.06 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.293842E+10 | 3094.06 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.303738E+10 | 3094.06 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.348298E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.273166E+10 | 3094.06 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.304304E+10 | 3094.06 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113146E+10 | 1089.83 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.102161E+10 | 1089.83 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.113495E+10 | 1089.83 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.109310E+10 | 1089.83 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.113342E+10 | 1089.83 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.109811E+10 | 1089.83 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.112841E+10 | 1089.83 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.113539E+10 | 1089.83 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.109354E+10 | 1089.83 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.113103E+10 | 1089.83 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.109724E+10 | 1089.83 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.112841E+10 | 1089.83 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.133267E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.102161E+10 | 1089.83 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.113539E+10 | 1089.83 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.246211E+10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.222306E+10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.246970E+10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.237864E+10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.246638E+10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.238954E+10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.245547E+10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.247065E+10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.237958E+10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.246116E+10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.238765E+10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.245547E+10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.289994E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.222306E+10 | 2371.52 | 0.00 | 0.00 | |
Maximum of Months | 0.247065E+10 | 2371.52 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.147273E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.147727E+11 | 0.127855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.142280E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.147528E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.142932E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.142337E+11 | 0.123352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.147216E+11 | 0.127549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.142819E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.146876E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.173462E+12 | 0.150255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.132974E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.147784E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.731324E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4169483.99 | 0.456402E+09 |
February | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466116E+09 |
March | 0.199990E+10 | 0.733578E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9655175.04 | 0.401698E+09 |
April | 0.192973E+10 | 0.706528E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111264E+09 | 0.139290E+09 |
May | 0.199475E+10 | 0.732592E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190354E+09 | 73026696.37 |
June | 0.193394E+10 | 0.709769E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356652E+09 | 13335568.10 |
July | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328187E+09 | 8302633.26 |
August | 0.199896E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302256E+09 | 12667101.21 |
September | 0.192879E+10 | 0.706810E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209578E+09 | 27874603.49 |
October | 0.199148E+10 | 0.731042E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77209875.55 | 0.226749E+09 |
November | 0.192552E+10 | 0.709205E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7215153.84 | 0.409426E+09 |
December | 0.199054E+10 | 0.729351E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1048198.68 | 0.585545E+09 |
Annual Sum or Average | 0.234744E+11 | 0.861373E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159759E+10 | 0.282043E+10 |
Minimum of Months | 0.179968E+10 | 0.660319E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8302633.26 |
Maximum of Months | 0.199990E+10 | 0.733860E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356652E+09 | 0.585545E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.846876E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3024294.80 | 0.178222E+09 |
February | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185937E+09 |
March | 0.231589E+10 | 0.849486E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5525871.73 | 0.161802E+09 |
April | 0.223463E+10 | 0.818162E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45930866.02 | 56832321.43 |
May | 0.230993E+10 | 0.848344E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76085487.56 | 29922504.33 |
June | 0.223950E+10 | 0.821915E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138595E+09 | 5163921.69 |
July | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128031E+09 | 3295839.76 |
August | 0.231480E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118078E+09 | 5059055.68 |
September | 0.223354E+10 | 0.818489E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82425280.48 | 10999838.83 |
October | 0.230614E+10 | 0.846549E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31526728.51 | 89499551.40 |
November | 0.222975E+10 | 0.821262E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3990644.13 | 0.161151E+09 |
December | 0.230505E+10 | 0.844592E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 965307.67 | 0.229794E+09 |
Annual Sum or Average | 0.271834E+11 | 0.997473E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634179E+09 | 0.111768E+10 |
Minimum of Months | 0.208403E+10 | 0.764651E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3295839.76 |
Maximum of Months | 0.231589E+10 | 0.849812E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138595E+09 | 0.229794E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.141236E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10197104.44 | 0.390972E+09 |
February | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415176E+09 |
March | 0.489771E+09 | 0.141672E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13398798.03 | 0.364170E+09 |
April | 0.472586E+09 | 0.136448E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105450E+09 | 0.133068E+09 |
May | 0.488511E+09 | 0.141481E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173709E+09 | 71108493.79 |
June | 0.473617E+09 | 0.137074E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325351E+09 | 12211803.97 |
July | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299355E+09 | 7833300.01 |
August | 0.489542E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275746E+09 | 12138094.47 |
September | 0.472357E+09 | 0.136502E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191215E+09 | 26314553.70 |
October | 0.487709E+09 | 0.141182E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73659788.95 | 0.206806E+09 |
November | 0.471555E+09 | 0.136965E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11212719.96 | 0.360290E+09 |
December | 0.487480E+09 | 0.140855E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3609734.44 | 0.504127E+09 |
Annual Sum or Average | 0.574883E+10 | 0.166352E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148290E+10 | 0.250422E+10 |
Minimum of Months | 0.440737E+09 | 0.127524E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7833300.01 |
Maximum of Months | 0.489771E+09 | 0.141726E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325351E+09 | 0.504127E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.236418E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9352404.37 | 0.200716E+09 |
February | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58436.66 | 0.215431E+09 |
March | 0.376747E+09 | 0.237147E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11633860.39 | 0.184582E+09 |
April | 0.363528E+09 | 0.228402E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74006757.58 | 63070385.59 |
May | 0.375778E+09 | 0.236828E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112360E+09 | 33396054.53 |
June | 0.364321E+09 | 0.229450E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190961E+09 | 6000877.30 |
July | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177754E+09 | 3776606.68 |
August | 0.376571E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166150E+09 | 5046805.81 |
September | 0.363352E+09 | 0.228493E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119398E+09 | 11135488.91 |
October | 0.375161E+09 | 0.236327E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50359525.73 | 0.100203E+09 |
November | 0.362735E+09 | 0.229268E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9789601.11 | 0.181532E+09 |
December | 0.374985E+09 | 0.235780E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3429950.22 | 0.270030E+09 |
Annual Sum or Average | 0.442217E+10 | 0.278459E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925253E+09 | 0.127492E+10 |
Minimum of Months | 0.339028E+09 | 0.213464E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58436.66 | 3776606.68 |
Maximum of Months | 0.376747E+09 | 0.237238E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190961E+09 | 0.270030E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.370859E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 5193360.02 | 0.618829E+09 |
February | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676260E+09 |
March | 0.155131E+10 | 0.372002E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 11731336.84 | 0.581146E+09 |
April | 0.149688E+10 | 0.358285E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.138440E+09 | 0.188621E+09 |
May | 0.154732E+10 | 0.371502E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.236896E+09 | 97268815.49 |
June | 0.150015E+10 | 0.359929E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.444221E+09 | 16667829.09 |
July | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.408729E+09 | 10689369.03 |
August | 0.155059E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.376383E+09 | 16624691.08 |
September | 0.149615E+10 | 0.358428E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 0.260995E+09 | 35924376.72 |
October | 0.154478E+10 | 0.370717E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 96155682.60 | 0.307501E+09 |
November | 0.149361E+10 | 0.359643E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 8703748.38 | 0.559732E+09 |
December | 0.154405E+10 | 0.369859E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 1302803.21 | 0.816725E+09 |
Annual Sum or Average | 0.182090E+11 | 0.436808E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.198875E+10 | 0.392599E+10 |
Minimum of Months | 0.139600E+10 | 0.334852E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10689369.03 |
Maximum of Months | 0.155131E+10 | 0.372145E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.444221E+09 | 0.816725E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.159294E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9745945.17 | 0.995059E+09 |
February | 0.236489E+11 | 0.143108E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3814.11 | 0.102384E+10 |
March | 0.262800E+11 | 0.154290E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33644895.34 | 0.859250E+09 |
April | 0.253579E+11 | 0.145732E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282425E+09 | 0.285410E+09 |
May | 0.262123E+11 | 0.147737E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484536E+09 | 0.145004E+09 |
June | 0.254132E+11 | 0.139399E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837514E+09 | 25263452.11 |
July | 0.261570E+11 | 0.144497E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779294E+09 | 15482352.67 |
August | 0.262677E+11 | 0.150962E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710016E+09 | 22057340.24 |
September | 0.253456E+11 | 0.147581E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493896E+09 | 51429929.55 |
October | 0.261693E+11 | 0.155966E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179712E+09 | 0.476942E+09 |
November | 0.253025E+11 | 0.153501E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19592597.43 | 0.884581E+09 |
December | 0.261570E+11 | 0.159453E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2761454.27 | 0.129522E+10 |
Annual Sum or Average | 0.308468E+12 | 0.180152E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383314E+10 | 0.607954E+10 |
Minimum of Months | 0.236489E+11 | 0.139399E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3814.11 | 15482352.67 |
Maximum of Months | 0.262800E+11 | 0.159453E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837514E+09 | 0.129522E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.104129E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37844542.33 | 0.298799E+10 |
February | 0.702046E+11 | 0.939735E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313586E+10 |
March | 0.780153E+11 | 0.103980E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88702962.70 | 0.270178E+10 |
April | 0.752779E+11 | 0.998436E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770098E+09 | 0.923649E+09 |
May | 0.778146E+11 | 0.103221E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128421E+10 | 0.483969E+09 |
June | 0.754422E+11 | 0.996525E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230074E+10 | 84134852.70 |
July | 0.776503E+11 | 0.102538E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212411E+10 | 53867117.81 |
August | 0.779788E+11 | 0.103718E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195532E+10 | 82258032.93 |
September | 0.752414E+11 | 0.100094E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136137E+10 | 0.178128E+09 |
October | 0.776868E+11 | 0.103797E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510889E+09 | 0.148532E+10 |
November | 0.751137E+11 | 0.100899E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58965790.76 | 0.269267E+10 |
December | 0.776503E+11 | 0.103912E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11537954.61 | 0.387429E+10 |
Annual Sum or Average | 0.915726E+12 | 0.121976E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105038E+11 | 0.186839E+11 |
Minimum of Months | 0.702046E+11 | 0.939735E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53867117.81 |
Maximum of Months | 0.780153E+11 | 0.104129E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230074E+10 | 0.387429E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6171147.24 | 0.219087E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4191.14 | 0.242643E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10956836.29 | 0.200715E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93982425.70 | 51779716.83 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150917E+09 | 19566629.51 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262318E+09 | 983522.24 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251217E+09 | 781795.46 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233837E+09 | 1007033.65 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171986E+09 | 3403587.57 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65852887.73 | 95178702.03 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8305795.28 | 0.194613E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1715091.54 | 0.304176E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125726E+10 | 0.133394E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4191.14 | 781795.46 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262318E+09 | 0.304176E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8249673.51 | 0.212646E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12638.12 | 0.236099E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11724471.78 | 0.196880E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94362706.74 | 51520633.51 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150934E+09 | 19590036.03 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262181E+09 | 983424.07 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251157E+09 | 781817.20 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233908E+09 | 1003611.97 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172215E+09 | 3370066.42 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66744161.15 | 92644486.57 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9462653.89 | 0.189551E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2857760.71 | 0.294397E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126381E+10 | 0.129947E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12638.12 | 781817.20 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262181E+09 | 0.294397E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 85091918.49 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1105622.38 | 74021659.41 |
February | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77640325.97 |
March | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2009997.05 | 66115880.24 |
April | 0.00 | 82445007.08 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20460553.01 | 21411484.91 |
May | 0.00 | 84753783.81 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34093871.84 | 10515297.51 |
June | 0.00 | 81790910.76 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62012425.68 | 1525725.50 |
July | 0.00 | 85418966.65 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57846520.73 | 983647.99 |
August | 0.00 | 84415649.14 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53381877.86 | 1460423.60 |
September | 0.00 | 82467180.11 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37675843.27 | 3404949.17 |
October | 0.00 | 85080831.98 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14242326.31 | 35783816.68 |
November | 0.00 | 82117958.92 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1580872.13 | 66050206.90 |
December | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 299397.20 | 97353527.83 |
Annual Sum or Average | 0.00 | 0.100027E+10 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284709E+09 | 0.456267E+09 |
Minimum of Months | 0.00 | 76846309.13 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 983647.99 |
Maximum of Months | 0.00 | 85430053.17 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62012425.68 | 97353527.83 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3442106.33 | 59006559.21 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11010.79 | 66038491.56 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3922048.36 | 54690428.08 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27637459.71 | 14199038.25 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43020298.06 | 5438102.95 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73603030.68 | 274435.10 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70535921.90 | 218158.94 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65851080.88 | 263189.54 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48807666.55 | 908493.22 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19826162.42 | 25603826.15 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3577616.04 | 52292756.07 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1254659.63 | 82136837.90 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361489E+09 | 0.361070E+09 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11010.79 | 218158.94 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73603030.68 | 82136837.90 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6171283.45 | 0.220939E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4064.43 | 0.245630E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10745772.37 | 0.203938E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93714466.55 | 53019511.47 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150428E+09 | 19946376.45 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262022E+09 | 983651.75 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250778E+09 | 786256.44 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233463E+09 | 1077478.78 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171734E+09 | 3607538.62 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65797764.65 | 96763280.49 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8238689.09 | 0.195835E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1689926.41 | 0.305924E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125479E+10 | 0.134845E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4064.43 | 786256.44 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262022E+09 | 0.305924E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8251593.91 | 0.214267E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4162.96 | 0.238946E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11049576.31 | 0.200242E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93773309.03 | 52976390.32 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150424E+09 | 19948934.53 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261931E+09 | 983607.70 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250747E+09 | 786402.59 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233481E+09 | 1072663.83 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171816E+09 | 3594405.92 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66232922.76 | 94987655.43 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9351420.53 | 0.190145E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2958537.34 | 0.295439E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126002E+10 | 0.131339E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4162.96 | 786402.59 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261931E+09 | 0.295439E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.232638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5449590.14 | 0.309383E+09 |
February | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322517E+09 |
March | 0.387034E+10 | 0.233355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9948779.07 | 0.281392E+09 |
April | 0.373454E+10 | 0.224750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80674274.49 | 0.101742E+09 |
May | 0.386038E+10 | 0.233041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133665E+09 | 54297400.07 |
June | 0.374269E+10 | 0.225781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249136E+09 | 9605267.49 |
July | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229072E+09 | 6140597.35 |
August | 0.386853E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211106E+09 | 9397021.69 |
September | 0.373273E+10 | 0.224840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146315E+09 | 20251230.76 |
October | 0.385404E+10 | 0.232548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54966932.93 | 0.161647E+09 |
November | 0.372639E+10 | 0.225602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7041830.20 | 0.283465E+09 |
December | 0.385223E+10 | 0.232011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1973925.71 | 0.398756E+09 |
Annual Sum or Average | 0.454292E+11 | 0.274007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112935E+10 | 0.195859E+10 |
Minimum of Months | 0.348285E+10 | 0.210051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6140597.35 |
Maximum of Months | 0.387034E+10 | 0.233445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249136E+09 | 0.398756E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135397E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6019571.43 | 0.219140E+09 |
February | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3464.01 | 0.242054E+09 |
March | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10825451.13 | 0.200632E+09 |
April | 0.293479E+09 | 0.131185E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93061699.90 | 52049539.19 |
May | 0.303504E+09 | 0.134859E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149806E+09 | 19904950.19 |
June | 0.293842E+09 | 0.130145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260715E+09 | 1043870.63 |
July | 0.303141E+09 | 0.135918E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249581E+09 | 824778.52 |
August | 0.303685E+09 | 0.134321E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232245E+09 | 1051178.19 |
September | 0.293479E+09 | 0.131221E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170596E+09 | 3447605.71 |
October | 0.303322E+09 | 0.135380E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65217099.65 | 95173883.29 |
November | 0.293661E+09 | 0.130665E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8215833.75 | 0.194564E+09 |
December | 0.303141E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1667170.83 | 0.303747E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159162E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124795E+10 | 0.133363E+10 |
Minimum of Months | 0.273974E+09 | 0.122277E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3464.01 | 824778.52 |
Maximum of Months | 0.303685E+09 | 0.135935E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260715E+09 | 0.303747E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.135381E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8785582.50 | 0.212133E+09 |
February | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20466.31 | 0.234871E+09 |
March | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11665547.00 | 0.196522E+09 |
April | 0.293479E+09 | 0.131170E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93409479.59 | 51779997.86 |
May | 0.303504E+09 | 0.134843E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149808E+09 | 19925632.37 |
June | 0.293842E+09 | 0.130129E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260569E+09 | 1043757.85 |
July | 0.303141E+09 | 0.135902E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249517E+09 | 824720.87 |
August | 0.303685E+09 | 0.134305E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232334E+09 | 1047108.22 |
September | 0.293479E+09 | 0.131205E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170851E+09 | 3417718.71 |
October | 0.303322E+09 | 0.135364E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66342273.63 | 92382130.17 |
November | 0.293661E+09 | 0.130650E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9718261.15 | 0.188842E+09 |
December | 0.303141E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3114968.06 | 0.293119E+09 |
Annual Sum or Average | 0.357224E+10 | 0.159144E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125613E+10 | 0.129591E+10 |
Minimum of Months | 0.273974E+09 | 0.122263E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20466.31 | 824720.87 |
Maximum of Months | 0.303685E+09 | 0.135919E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260569E+09 | 0.293119E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 85115186.72 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3015869.57 | 0.114531E+09 |
February | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1543.74 | 0.127407E+09 |
March | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5403053.11 | 0.104852E+09 |
April | 0.293479E+09 | 82467551.52 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47604814.76 | 26702214.11 |
May | 0.303504E+09 | 84776959.58 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76786831.65 | 10180141.04 |
June | 0.293842E+09 | 81813276.33 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133682E+09 | 533927.97 |
July | 0.303141E+09 | 85442324.32 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127815E+09 | 421901.92 |
August | 0.303685E+09 | 84438732.44 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118859E+09 | 537548.93 |
September | 0.293479E+09 | 82489730.61 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87182059.07 | 1798518.94 |
October | 0.303322E+09 | 85104097.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33213779.74 | 49713337.50 |
November | 0.293661E+09 | 82140413.93 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4044693.09 | 0.101450E+09 |
December | 0.303141E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 817505.50 | 0.159397E+09 |
Annual Sum or Average | 0.357224E+10 | 0.100055E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638426E+09 | 0.697524E+09 |
Minimum of Months | 0.273974E+09 | 76867322.62 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1543.74 | 421901.92 |
Maximum of Months | 0.303685E+09 | 85453413.86 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133682E+09 | 0.159397E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.304304E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17663587.31 | 0.637953E+09 |
February | 0.415303E+11 | 0.273166E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692120E+09 |
March | 0.461508E+11 | 0.297608E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22523897.24 | 0.600666E+09 |
April | 0.445315E+11 | 0.282542E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182637E+09 | 0.204573E+09 |
May | 0.460320E+11 | 0.288543E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293620E+09 | 0.108737E+09 |
June | 0.446286E+11 | 0.275467E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521707E+09 | 19488178.39 |
July | 0.459349E+11 | 0.284709E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483191E+09 | 12468395.35 |
August | 0.461292E+11 | 0.292786E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449446E+09 | 18572575.36 |
September | 0.445099E+11 | 0.284897E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320113E+09 | 39729960.55 |
October | 0.459565E+11 | 0.301378E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130165E+09 | 0.320900E+09 |
November | 0.444343E+11 | 0.293842E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20763050.36 | 0.578062E+09 |
December | 0.459349E+11 | 0.303738E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5940955.67 | 0.838492E+09 |
Annual Sum or Average | 0.541708E+12 | 0.348298E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244777E+10 | 0.407176E+10 |
Minimum of Months | 0.415303E+11 | 0.273166E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12468395.35 |
Maximum of Months | 0.461508E+11 | 0.304304E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521707E+09 | 0.838492E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.304304E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14664905.02 | 0.656711E+09 |
February | 0.415303E+11 | 0.273166E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715541E+09 |
March | 0.461508E+11 | 0.297608E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19834782.38 | 0.620089E+09 |
April | 0.445315E+11 | 0.282542E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174067E+09 | 0.209325E+09 |
May | 0.460320E+11 | 0.288543E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284157E+09 | 0.110582E+09 |
June | 0.446286E+11 | 0.275467E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512717E+09 | 19778012.65 |
July | 0.459349E+11 | 0.284709E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473485E+09 | 12706003.49 |
August | 0.461292E+11 | 0.292786E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439749E+09 | 19224724.81 |
September | 0.445099E+11 | 0.284897E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310996E+09 | 40966568.35 |
October | 0.459565E+11 | 0.301378E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123940E+09 | 0.330484E+09 |
November | 0.444343E+11 | 0.293842E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18085290.83 | 0.595702E+09 |
December | 0.459349E+11 | 0.303738E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4714002.52 | 0.863350E+09 |
Annual Sum or Average | 0.541708E+12 | 0.348298E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237641E+10 | 0.419446E+10 |
Minimum of Months | 0.415303E+11 | 0.273166E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12706003.49 |
Maximum of Months | 0.461508E+11 | 0.304304E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512717E+09 | 0.863350E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113146E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4982584.53 | 0.640183E+09 |
February | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698522E+09 |
March | 0.410691E+10 | 0.113495E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 11442782.09 | 0.601007E+09 |
April | 0.396281E+10 | 0.109310E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.138400E+09 | 0.195669E+09 |
May | 0.409635E+10 | 0.113342E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.237710E+09 | 0.101508E+09 |
June | 0.397146E+10 | 0.109811E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.447647E+09 | 17873272.10 |
July | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.410955E+09 | 11530957.62 |
August | 0.410499E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.378349E+09 | 17917705.10 |
September | 0.396089E+10 | 0.109354E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.261657E+09 | 38274694.93 |
October | 0.408962E+10 | 0.113103E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 96122325.03 | 0.318759E+09 |
November | 0.395417E+10 | 0.109724E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 8415541.26 | 0.578724E+09 |
December | 0.408770E+10 | 0.112841E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1224939.47 | 0.842569E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133267E+11 | 0.392709E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.199691E+10 | 0.406254E+10 |
Minimum of Months | 0.369574E+10 | 0.102161E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11530957.62 |
Maximum of Months | 0.410691E+10 | 0.113539E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.447647E+09 | 0.842569E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.246211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5380381.22 | 0.555948E+09 |
February | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580473E+09 |
March | 0.409620E+10 | 0.246970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12442767.47 | 0.510935E+09 |
April | 0.395248E+10 | 0.237864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135567E+09 | 0.182740E+09 |
May | 0.408566E+10 | 0.246638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232320E+09 | 97524282.65 |
June | 0.396110E+10 | 0.238954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437757E+09 | 17546820.12 |
July | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401844E+09 | 11302371.98 |
August | 0.409429E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369958E+09 | 17489583.08 |
September | 0.395056E+10 | 0.237958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255792E+09 | 37327803.31 |
October | 0.407896E+10 | 0.246116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94099779.71 | 0.287846E+09 |
November | 0.394385E+10 | 0.238765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8848129.31 | 0.507688E+09 |
December | 0.407704E+10 | 0.245547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1850675.04 | 0.705570E+09 |
Annual Sum or Average | 0.480803E+11 | 0.289994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195586E+10 | 0.351239E+10 |
Minimum of Months | 0.368610E+10 | 0.222306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11302371.98 |
Maximum of Months | 0.409620E+10 | 0.247065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437757E+09 | 0.705570E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 14185.34 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 14185.34 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 14185.34 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 14185.34 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 14185.34 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 14185.34 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 14185.34 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 14185.34 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 14185.34 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 14185.34 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 14185.34 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 14185.34 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 14185.34 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 704.41 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.54 | 31-JAN-16:00 | 427.09 | 01-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 704.41 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 346.02 | 01-FEB-07:30 |
March | 1169.53 | 01-MAR-00:10 | 704.41 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.39 | 16-MAR-15:00 | 425.65 | 26-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 704.41 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.53 | 14-APR-16:00 | 286.95 | 21-APR-03:57 |
May | 1169.53 | 01-MAY-00:10 | 704.41 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.26 | 31-MAY-17:00 | 218.78 | 01-MAY-04:00 |
June | 1169.53 | 01-JUN-00:10 | 704.41 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.11 | 28-JUN-16:00 | 115.30 | 21-JUN-06:00 |
July | 1169.53 | 01-JUL-00:10 | 704.41 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.68 | 19-JUL-13:00 | 117.48 | 01-JUL-06:00 |
August | 1169.53 | 01-AUG-00:10 | 704.41 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.44 | 25-AUG-14:00 | 137.66 | 05-AUG-18:00 |
September | 1169.53 | 01-SEP-00:10 | 704.41 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.26 | 08-SEP-15:00 | 130.07 | 22-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 704.41 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.13 | 01-OCT-13:00 | 339.87 | 25-OCT-05:55 |
November | 1169.53 | 01-NOV-00:10 | 704.41 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.14 | 01-NOV-15:00 | 438.25 | 23-NOV-06:40 |
December | 1169.53 | 01-DEC-00:10 | 704.41 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 | 21-DEC-15:00 | 460.75 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.30 | |||||
Maximum of Months | 1169.53 | 704.41 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 325.11 | 460.75 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 815.72 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 31-JAN-16:00 | 174.13 | 01-JAN-08:00 |
February | 1354.32 | 01-FEB-00:10 | 815.72 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 146.21 | 01-FEB-07:30 |
March | 1354.32 | 01-MAR-00:10 | 815.72 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.89 | 20-MAR-17:00 | 173.91 | 26-MAR-04:00 |
April | 1354.32 | 01-APR-00:10 | 815.72 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.47 | 14-APR-15:00 | 122.32 | 21-APR-03:57 |
May | 1354.32 | 01-MAY-00:10 | 815.72 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.51 | 15-MAY-17:00 | 91.44 | 01-MAY-04:00 |
June | 1354.32 | 01-JUN-00:10 | 815.72 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.50 | 28-JUN-16:00 | 45.02 | 21-JUN-06:00 |
July | 1354.32 | 01-JUL-00:10 | 815.72 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.87 | 19-JUL-13:00 | 45.35 | 01-JUL-06:00 |
August | 1354.32 | 01-AUG-00:10 | 815.72 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.44 | 25-AUG-14:00 | 53.14 | 05-AUG-18:00 |
September | 1354.32 | 01-SEP-00:10 | 815.72 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 | 08-SEP-15:00 | 55.87 | 22-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 815.72 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.90 | 01-OCT-13:00 | 145.64 | 25-OCT-05:55 |
November | 1354.32 | 01-NOV-00:10 | 815.72 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.53 | 01-NOV-15:00 | 183.51 | 23-NOV-06:30 |
December | 1354.32 | 01-DEC-00:10 | 815.72 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 21-DEC-15:00 | 189.37 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.02 | |||||
Maximum of Months | 1354.32 | 815.72 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 125.50 | 189.37 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 1360.40 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.82 | 31-JAN-16:30 | 389.61 | 01-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 1360.40 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 332.19 | 01-FEB-07:30 |
March | 286.42 | 01-MAR-00:10 | 1360.40 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.57 | 16-MAR-15:30 | 401.61 | 26-MAR-04:00 |
April | 286.42 | 01-APR-00:10 | 1360.40 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.76 | 14-APR-15:00 | 281.39 | 21-APR-04:10 |
May | 286.42 | 01-MAY-00:10 | 1360.40 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.36 | 31-MAY-17:00 | 214.71 | 01-MAY-04:00 |
June | 286.42 | 01-JUN-00:10 | 1360.40 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.59 | 28-JUN-16:00 | 106.42 | 21-JUN-06:00 |
July | 286.42 | 01-JUL-00:10 | 1360.40 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.00 | 19-JUL-13:00 | 107.18 | 01-JUL-06:00 |
August | 286.42 | 01-AUG-00:10 | 1360.40 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.29 | 25-AUG-14:00 | 125.60 | 05-AUG-18:00 |
September | 286.42 | 01-SEP-00:10 | 1360.40 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.25 | 08-SEP-15:00 | 132.77 | 22-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 1360.40 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.15 | 01-OCT-13:00 | 335.81 | 25-OCT-05:55 |
November | 286.42 | 01-NOV-00:10 | 1360.40 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.53 | 01-NOV-15:00 | 424.27 | 23-NOV-06:30 |
December | 286.42 | 01-DEC-00:10 | 1360.40 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.09 | 21-DEC-15:00 | 431.16 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.42 | |||||
Maximum of Months | 286.42 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 296.59 | 431.16 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 227.72 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.63 | 31-JAN-17:00 | 224.79 | 01-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 227.72 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 | 18-FEB-14:00 | 179.71 | 01-FEB-07:30 |
March | 220.32 | 01-MAR-00:10 | 227.72 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.30 | 20-MAR-17:00 | 224.00 | 26-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 227.72 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.54 | 14-APR-16:30 | 151.27 | 21-APR-03:57 |
May | 220.32 | 01-MAY-00:10 | 227.72 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.43 | 15-MAY-17:00 | 113.35 | 01-MAY-04:00 |
June | 220.32 | 01-JUN-00:10 | 227.72 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.50 | 16-JUN-16:00 | 57.86 | 21-JUN-06:00 |
July | 220.32 | 01-JUL-00:10 | 227.72 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.30 | 19-JUL-13:00 | 59.90 | 01-JUL-06:00 |
August | 220.32 | 01-AUG-00:10 | 227.72 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.74 | 25-AUG-16:40 | 64.03 | 05-AUG-18:00 |
September | 220.32 | 01-SEP-00:10 | 227.72 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.29 | 08-SEP-16:00 | 67.39 | 22-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 227.72 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.33 | 01-OCT-13:00 | 181.69 | 25-OCT-05:55 |
November | 220.32 | 01-NOV-00:10 | 227.72 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.86 | 01-NOV-15:00 | 232.63 | 23-NOV-06:00 |
December | 220.32 | 01-DEC-00:10 | 227.72 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.27 | 21-DEC-15:00 | 242.50 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 | 57.86 | |||||
Maximum of Months | 220.32 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 171.50 | 242.50 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 357.21 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 117.77 | 31-JAN-16:00 | 609.81 | 01-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 357.21 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 555.09 | 01-FEB-07:30 |
March | 907.20 | 01-MAR-00:10 | 357.21 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 112.59 | 16-MAR-15:00 | 607.72 | 26-MAR-06:00 |
April | 907.20 | 01-APR-00:10 | 357.21 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 252.28 | 14-APR-15:00 | 415.73 | 21-APR-03:53 |
May | 907.20 | 01-MAY-00:10 | 357.21 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 296.78 | 31-MAY-17:00 | 296.72 | 01-MAY-04:00 |
June | 907.20 | 01-JUN-00:10 | 357.21 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 404.96 | 28-JUN-16:00 | 145.31 | 21-JUN-06:00 |
July | 907.20 | 01-JUL-00:10 | 357.21 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 364.58 | 19-JUL-13:00 | 146.35 | 01-JUL-06:00 |
August | 907.20 | 01-AUG-00:10 | 357.21 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 385.45 | 25-AUG-14:00 | 171.49 | 05-AUG-18:00 |
September | 907.20 | 01-SEP-00:10 | 357.21 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 326.69 | 08-SEP-15:00 | 181.28 | 22-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 357.21 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 297.89 | 01-OCT-13:00 | 539.04 | 25-OCT-06:30 |
November | 907.20 | 01-NOV-00:10 | 357.21 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 117.31 | 01-NOV-15:00 | 623.84 | 23-NOV-06:10 |
December | 907.20 | 01-DEC-00:10 | 357.21 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 47.55 | 21-DEC-15:00 | 652.09 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 145.31 | ||||||
Maximum of Months | 907.20 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 404.96 | 652.09 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1761.91 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.06 | 31-JAN-17:00 | 966.01 | 01-JAN-08:00 |
February | 15368.40 | 01-FEB-00:10 | 1761.91 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.37 | 18-FEB-16:00 | 798.20 | 01-FEB-05:10 |
March | 15368.40 | 01-MAR-00:10 | 1761.91 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.02 | 20-MAR-17:00 | 941.10 | 26-MAR-06:00 |
April | 15368.40 | 01-APR-00:10 | 1761.91 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 457.95 | 14-APR-17:00 | 679.91 | 21-APR-03:57 |
May | 15368.40 | 01-MAY-00:10 | 1761.91 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 558.88 | 31-MAY-17:00 | 491.39 | 01-MAY-04:00 |
June | 15368.40 | 01-JUN-00:10 | 1761.91 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 722.69 | 28-JUN-15:00 | 246.06 | 21-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1761.91 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 670.29 | 12-JUL-14:00 | 232.88 | 01-JUL-06:00 |
August | 15368.40 | 01-AUG-00:10 | 1761.91 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 688.86 | 26-AUG-16:00 | 241.41 | 05-AUG-18:00 |
September | 15368.40 | 01-SEP-00:10 | 1761.91 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 579.79 | 08-SEP-15:00 | 275.08 | 22-SEP-06:00 |
October | 15368.40 | 01-OCT-23:10 | 1761.91 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 542.66 | 01-OCT-13:00 | 798.05 | 25-OCT-05:55 |
November | 15368.40 | 01-NOV-00:10 | 1761.91 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.21 | 01-NOV-15:00 | 989.24 | 23-NOV-06:10 |
December | 15368.40 | 01-DEC-00:10 | 1761.91 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.18 | 02-DEC-15:00 | 1061.49 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 4.37 | 232.88 | |||||
Maximum of Months | 15368.40 | 1761.91 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 722.69 | 1061.49 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10265.18 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 632.73 | 31-JAN-16:00 | 2909.69 | 01-JAN-08:00 |
February | 45622.98 | 01-FEB-00:10 | 10265.18 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2406.94 | 01-FEB-07:10 |
March | 45622.98 | 01-MAR-00:10 | 10265.18 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 666.70 | 20-MAR-17:00 | 2884.15 | 26-MAR-05:40 |
April | 45622.98 | 01-APR-00:10 | 10265.18 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1300.61 | 14-APR-17:00 | 2039.92 | 21-APR-04:10 |
May | 45622.98 | 01-MAY-00:10 | 10265.18 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1549.41 | 15-MAY-17:00 | 1511.60 | 01-MAY-04:00 |
June | 45622.98 | 01-JUN-00:10 | 10265.18 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2055.27 | 28-JUN-15:00 | 736.59 | 21-JUN-06:00 |
July | 45622.98 | 01-JUL-00:10 | 10265.18 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1895.92 | 19-JUL-13:00 | 741.88 | 01-JUL-06:00 |
August | 45622.98 | 01-AUG-00:10 | 10265.18 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1969.57 | 26-AUG-16:00 | 848.57 | 05-AUG-18:00 |
September | 45622.98 | 01-SEP-00:10 | 10265.18 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1656.53 | 08-SEP-15:00 | 919.03 | 22-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 10265.18 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1548.98 | 01-OCT-13:00 | 2430.68 | 25-OCT-05:55 |
November | 45622.98 | 01-NOV-00:10 | 10265.18 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 601.96 | 01-NOV-15:00 | 3031.63 | 23-NOV-06:30 |
December | 45622.98 | 01-DEC-00:10 | 10265.18 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.64 | 21-DEC-15:00 | 3180.84 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 736.59 | |||||
Maximum of Months | 45622.98 | 10265.18 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 2055.27 | 3180.84 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.12 | 31-JAN-17:00 | 249.74 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 18-FEB-16:07 | 192.07 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.58 | 16-MAR-15:10 | 248.88 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.98 | 14-APR-16:00 | 154.25 | 21-APR-04:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.58 | 31-MAY-17:00 | 105.99 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.30 | 16-JUN-16:00 | 35.60 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.78 | 20-JUL-15:10 | 35.86 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.48 | 25-AUG-15:10 | 67.62 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.23 | 08-SEP-16:00 | 52.00 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.37 | 03-OCT-16:00 | 190.93 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.98 | 01-NOV-15:10 | 256.21 | 23-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.88 | 25-DEC-16:08 | 269.28 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 35.60 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 218.30 | 269.28 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.12 | 31-JAN-16:50 | 249.71 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 18-FEB-16:06 | 192.06 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.57 | 16-MAR-15:10 | 248.85 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.97 | 14-APR-16:00 | 154.24 | 21-APR-04:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.57 | 31-MAY-17:00 | 105.98 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.28 | 16-JUN-16:00 | 35.60 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.79 | 20-JUL-15:10 | 35.85 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.47 | 25-AUG-16:00 | 65.91 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.46 | 08-SEP-15:10 | 51.99 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.36 | 03-OCT-16:00 | 190.91 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.98 | 01-NOV-15:10 | 256.19 | 23-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.88 | 25-DEC-16:08 | 269.26 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 35.60 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 218.28 | 269.26 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 76.99 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.22 | 31-JAN-16:40 | 71.74 | 01-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 76.99 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 60.72 | 01-FEB-08:00 |
March | 0.00 | 01-MAR-00:10 | 76.99 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 16-MAR-15:00 | 69.00 | 26-MAR-04:00 |
April | 0.00 | 01-APR-00:10 | 76.99 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.66 | 14-APR-15:00 | 47.09 | 21-APR-03:51 |
May | 0.00 | 01-MAY-00:10 | 76.99 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.44 | 31-MAY-17:00 | 35.64 | 01-MAY-04:00 |
June | 0.00 | 01-JUN-00:10 | 76.99 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.48 | 28-JUN-16:00 | 16.91 | 21-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 76.99 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.25 | 19-JUL-13:00 | 16.21 | 01-JUL-06:00 |
August | 0.00 | 01-AUG-00:10 | 76.99 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.95 | 25-AUG-14:00 | 19.88 | 05-AUG-18:00 |
September | 0.00 | 01-SEP-00:10 | 76.99 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 | 08-SEP-15:00 | 19.75 | 22-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 76.99 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.58 | 01-OCT-14:00 | 58.58 | 25-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 76.99 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.15 | 01-NOV-15:00 | 73.56 | 23-NOV-06:20 |
December | 0.00 | 01-DEC-00:10 | 76.99 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 | 21-DEC-15:00 | 76.87 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 | |||||
Maximum of Months | 0.00 | 76.99 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 54.48 | 76.87 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 31-JAN-16:50 | 69.70 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 18-FEB-16:06 | 53.60 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 16-MAR-15:08 | 69.46 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.30 | 14-APR-15:40 | 43.05 | 21-APR-03:51 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.05 | 31-MAY-17:00 | 29.58 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.98 | 28-JUN-16:00 | 9.94 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.21 | 20-JUL-15:10 | 10.01 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.46 | 25-AUG-15:10 | 16.24 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.93 | 08-SEP-15:10 | 14.51 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.41 | 03-OCT-16:00 | 53.29 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.44 | 01-NOV-15:08 | 71.51 | 23-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.41 | 21-DEC-15:00 | 75.15 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 9.94 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 60.98 | 75.15 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.13 | 31-JAN-17:00 | 249.74 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 18-FEB-16:09 | 192.07 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.58 | 16-MAR-15:08 | 248.88 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.98 | 14-APR-15:09 | 154.25 | 21-APR-04:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.58 | 31-MAY-17:00 | 105.99 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.42 | 28-JUN-16:20 | 35.60 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.79 | 20-JUL-15:10 | 35.86 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.48 | 25-AUG-15:10 | 68.76 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.41 | 08-SEP-15:10 | 52.00 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.37 | 03-OCT-16:00 | 190.93 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.99 | 01-NOV-15:10 | 256.21 | 23-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | 25-DEC-16:10 | 269.28 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 35.60 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 218.42 | 269.28 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.12 | 31-JAN-16:50 | 249.72 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 18-FEB-16:07 | 192.06 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.57 | 16-MAR-15:08 | 248.85 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.97 | 14-APR-16:00 | 154.24 | 21-APR-04:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.56 | 31-MAY-17:00 | 105.98 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.36 | 28-JUN-16:30 | 35.60 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.80 | 20-JUL-15:10 | 35.86 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.47 | 25-AUG-15:10 | 67.06 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.47 | 08-SEP-15:10 | 51.99 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.36 | 03-OCT-16:00 | 190.91 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.98 | 01-NOV-15:07 | 256.19 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.88 | 25-DEC-16:08 | 269.26 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 35.60 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 218.36 | 269.26 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 2240.78 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.28 | 31-JAN-16:00 | 303.75 | 01-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 2240.78 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 257.65 | 01-FEB-07:30 |
March | 2263.36 | 01-MAR-00:10 | 2240.78 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.09 | 16-MAR-15:00 | 314.41 | 26-MAR-04:00 |
April | 2263.36 | 01-APR-00:10 | 2240.78 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.60 | 14-APR-15:00 | 219.83 | 21-APR-03:57 |
May | 2263.36 | 01-MAY-00:10 | 2240.78 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.68 | 31-MAY-17:00 | 164.93 | 01-MAY-04:00 |
June | 2263.36 | 01-JUN-00:10 | 2240.78 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.64 | 28-JUN-16:00 | 82.45 | 21-JUN-06:00 |
July | 2263.36 | 01-JUL-00:10 | 2240.78 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.87 | 19-JUL-13:00 | 83.04 | 01-JUL-06:00 |
August | 2263.36 | 01-AUG-00:10 | 2240.78 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.63 | 25-AUG-14:00 | 96.70 | 05-AUG-18:00 |
September | 2263.36 | 01-SEP-00:10 | 2240.78 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.52 | 08-SEP-15:00 | 99.82 | 22-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 2240.78 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.28 | 01-OCT-13:00 | 258.19 | 25-OCT-05:55 |
November | 2263.36 | 01-NOV-00:10 | 2240.78 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.37 | 01-NOV-15:00 | 332.10 | 23-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 2240.78 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.01 | 21-DEC-15:00 | 340.42 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.45 | ||||
Maximum of Months | 2263.36 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.64 | 340.42 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.50 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.49 | 31-JAN-17:00 | 250.50 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.50 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 18-FEB-16:07 | 192.82 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.50 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.95 | 16-MAR-15:10 | 249.65 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 122.50 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.37 | 14-APR-16:00 | 154.98 | 21-APR-04:00 |
May | 180.00 | 01-MAY-00:10 | 122.50 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.98 | 31-MAY-17:00 | 106.70 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 122.50 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.72 | 16-JUN-16:00 | 36.28 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 122.50 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.74 | 20-JUL-15:10 | 36.54 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 122.50 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.89 | 25-AUG-15:10 | 66.11 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 122.50 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.50 | 08-SEP-16:00 | 52.68 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.50 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.76 | 03-OCT-16:00 | 191.67 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 122.50 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.35 | 01-NOV-15:10 | 256.98 | 23-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 122.50 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.24 | 25-DEC-16:08 | 270.06 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 36.28 | |||||
Maximum of Months | 180.00 | 122.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 217.72 | 270.06 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 122.49 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.48 | 31-JAN-16:50 | 250.49 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 122.49 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 18-FEB-14:00 | 192.80 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 122.49 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.94 | 16-MAR-15:10 | 249.63 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 122.49 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.36 | 14-APR-16:00 | 154.97 | 21-APR-04:00 |
May | 180.00 | 01-MAY-00:10 | 122.49 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.97 | 31-MAY-17:00 | 106.69 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 122.49 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.70 | 16-JUN-16:00 | 36.28 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 122.49 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.32 | 20-JUL-15:10 | 36.54 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 122.49 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.87 | 25-AUG-15:10 | 64.15 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 122.49 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.80 | 08-SEP-15:10 | 52.68 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 122.49 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.75 | 03-OCT-16:00 | 191.65 | 25-OCT-06:43 |
November | 180.00 | 01-NOV-00:10 | 122.49 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.35 | 01-NOV-15:10 | 256.96 | 23-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 122.49 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.24 | 25-DEC-16:07 | 270.04 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 36.28 | |||||
Maximum of Months | 180.00 | 122.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 217.70 | 270.04 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 77.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.74 | 31-JAN-17:00 | 128.17 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 77.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 18-FEB-16:09 | 98.65 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 77.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.44 | 16-MAR-15:10 | 127.73 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 77.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.40 | 14-APR-16:00 | 79.29 | 21-APR-03:53 |
May | 180.00 | 01-MAY-00:10 | 77.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.94 | 31-MAY-17:00 | 54.59 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 77.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.48 | 28-JUN-16:10 | 18.56 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 77.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.89 | 20-JUL-15:10 | 18.69 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 77.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.88 | 25-AUG-16:30 | 32.84 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 77.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.95 | 08-SEP-15:50 | 26.96 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 77.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.59 | 03-OCT-16:00 | 98.06 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 77.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.66 | 01-NOV-15:10 | 131.48 | 23-NOV-06:20 |
December | 180.00 | 01-DEC-00:10 | 77.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.19 | 25-DEC-16:10 | 138.17 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 18.56 | |||||
Maximum of Months | 180.00 | 77.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 111.48 | 138.17 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.82 | 31-JAN-16:00 | 655.08 | 01-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 546.82 | 01-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.49 | 16-MAR-15:00 | 652.54 | 26-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.11 | 14-APR-15:00 | 466.72 | 21-APR-03:53 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.49 | 15-MAY-17:00 | 338.24 | 01-MAY-04:00 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 467.77 | 28-JUN-15:00 | 168.05 | 21-JUN-06:00 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 434.86 | 19-JUL-13:00 | 169.26 | 01-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 456.08 | 26-AUG-16:00 | 182.70 | 05-AUG-18:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 385.53 | 08-SEP-15:00 | 206.70 | 22-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.99 | 01-OCT-13:00 | 557.39 | 25-OCT-05:50 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.29 | 01-NOV-15:00 | 674.38 | 23-NOV-06:30 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.12 | 21-DEC-15:00 | 708.94 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.05 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 467.77 | 708.94 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3094.06 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.00 | 31-JAN-16:00 | 666.35 | 01-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 3094.06 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 553.71 | 01-FEB-07:30 |
March | 26988.77 | 01-MAR-00:10 | 3094.06 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.89 | 16-MAR-15:00 | 661.76 | 26-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 3094.06 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.89 | 14-APR-15:00 | 472.47 | 21-APR-03:53 |
May | 26988.77 | 01-MAY-00:10 | 3094.06 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.05 | 15-MAY-17:00 | 342.04 | 01-MAY-04:00 |
June | 26988.77 | 01-JUN-00:10 | 3094.06 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 460.23 | 28-JUN-15:00 | 168.05 | 21-JUN-06:00 |
July | 26988.77 | 01-JUL-00:10 | 3094.06 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 427.31 | 19-JUL-13:00 | 169.26 | 01-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 3094.06 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 447.93 | 26-AUG-16:00 | 191.32 | 05-AUG-18:00 |
September | 26988.77 | 01-SEP-00:10 | 3094.06 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.32 | 08-SEP-15:00 | 209.03 | 22-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 3094.06 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.18 | 01-OCT-13:00 | 561.56 | 25-OCT-05:50 |
November | 26988.77 | 01-NOV-00:10 | 3094.06 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.73 | 01-NOV-15:00 | 681.69 | 23-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 3094.06 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.74 | 21-DEC-15:00 | 717.45 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.05 | |||||
Maximum of Months | 26988.77 | 3094.06 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 460.23 | 717.45 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1089.83 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 117.91 | 31-JAN-16:40 | 623.68 | 01-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1089.83 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 563.95 | 01-FEB-07:30 |
March | 2401.70 | 01-MAR-00:10 | 1089.83 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 112.57 | 16-MAR-15:40 | 621.59 | 26-MAR-06:00 |
April | 2401.70 | 01-APR-00:10 | 1089.83 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 255.03 | 14-APR-15:40 | 451.03 | 21-APR-03:53 |
May | 2401.70 | 01-MAY-00:10 | 1089.83 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 300.36 | 31-MAY-17:00 | 306.23 | 01-MAY-04:00 |
June | 2401.70 | 01-JUN-00:10 | 1089.83 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 410.58 | 28-JUN-16:00 | 150.34 | 21-JUN-06:00 |
July | 2401.70 | 01-JUL-00:10 | 1089.83 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 369.30 | 19-JUL-13:00 | 151.41 | 01-JUL-06:00 |
August | 2401.70 | 01-AUG-00:10 | 1089.83 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 390.55 | 25-AUG-14:00 | 176.87 | 05-AUG-18:00 |
September | 2401.70 | 01-SEP-00:10 | 1089.83 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 330.69 | 08-SEP-15:00 | 187.03 | 22-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1089.83 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 301.36 | 01-OCT-13:00 | 539.28 | 25-OCT-05:50 |
November | 2401.70 | 01-NOV-00:10 | 1089.83 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 117.33 | 01-NOV-15:00 | 638.11 | 23-NOV-06:00 |
December | 2401.70 | 01-DEC-00:10 | 1089.83 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 46.20 | 21-DEC-15:00 | 666.99 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 150.34 | ||||||
Maximum of Months | 2401.70 | 1089.83 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 410.58 | 666.99 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 2371.52 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.02 | 31-JAN-16:00 | 533.09 | 01-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 2371.52 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 448.29 | 01-FEB-05:05 |
March | 2395.44 | 01-MAR-00:10 | 2371.52 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.88 | 16-MAR-15:00 | 536.65 | 26-MAR-04:00 |
April | 2395.44 | 01-APR-00:10 | 2371.52 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.22 | 14-APR-15:00 | 379.77 | 21-APR-03:57 |
May | 2395.44 | 01-MAY-00:10 | 2371.52 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.60 | 31-MAY-17:00 | 289.83 | 01-MAY-04:00 |
June | 2395.44 | 01-JUN-00:10 | 2371.52 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.51 | 28-JUN-16:00 | 147.34 | 21-JUN-06:00 |
July | 2395.44 | 01-JUL-00:10 | 2371.52 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.19 | 19-JUL-13:00 | 148.40 | 01-JUL-06:00 |
August | 2395.44 | 01-AUG-00:10 | 2371.52 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.02 | 25-AUG-14:00 | 173.49 | 05-AUG-18:00 |
September | 2395.44 | 01-SEP-00:10 | 2371.52 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.41 | 08-SEP-15:00 | 176.47 | 22-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 2371.52 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.67 | 01-OCT-13:00 | 448.32 | 25-OCT-05:55 |
November | 2395.44 | 01-NOV-00:10 | 2371.52 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.56 | 01-NOV-15:00 | 567.03 | 23-NOV-06:00 |
December | 2395.44 | 01-DEC-00:10 | 2371.52 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.44 | 21-DEC-15:00 | 582.83 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.34 | ||||
Maximum of Months | 2395.44 | 2371.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.51 | 582.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 38637.81 | 12-JAN-06:34 | 44729.58 | 31522.79 | 26615.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30315.24 | 01-FEB-06:55 | 89459.16 | 63045.57 | 53230.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18717.39 | 13-MAR-04:40 | 23003.78 | 6304.56 | 6387.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18578.47 | 21-APR-03:50 | 92015.14 | 12609.84 | 17033.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15114.33 | 01-MAY-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16703.60 | 22-JUN-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 23098.70 | 14-JUL-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24801.09 | 24-AUG-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27111.66 | 08-SEP-21:00 | 10223.90 | 12609.30 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38759.07 | 25-OCT-05:30 | 17891.83 | 12609.11 | 10646.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38841.79 | 05-NOV-06:40 | 17891.83 | 12609.11 | 10646.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 40533.31 | 14-DEC-00:23 | 115018.92 | 31522.79 | 31938.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15114.33 | 10223.90 | 6304.56 | 6387.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40533.31 | 115018.92 | 63045.57 | 53230.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3777.40 | 14-JAN-13:40 | 389.84 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 50.93 | 0.00 |
February | 2710.84 | 01-FEB-14:00 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.44 |
March | 2977.15 | 18-MAR-13:40 | 389.84 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 43.32 | 0.00 |
April | 3347.16 | 14-APR-14:10 | 389.84 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 187.86 | 0.00 |
May | 2905.81 | 31-MAY-18:15 | 1819.27 | 1252.29 | 1299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 208.52 | 0.00 |
June | 3708.77 | 28-JUN-18:13 | 2728.91 | 1878.44 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 301.79 | 0.00 |
July | 3421.69 | 21-JUL-18:30 | 909.64 | 626.15 | 649.52 | 0.00 | 0.00 | 0.00 | 0.00 | 256.14 | 0.00 |
August | 3807.75 | 28-AUG-12:30 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 239.14 | 0.00 |
September | 4131.85 | 28-SEP-13:30 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 223.40 | 0.00 |
October | 4126.48 | 06-OCT-13:20 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 202.53 | 0.00 |
November | 3968.22 | 20-NOV-13:40 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 50.61 | 0.00 |
December | 3662.24 | 25-DEC-13:00 | 389.84 | 234.80 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2710.84 | 259.90 | 195.67 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4131.85 | 2728.91 | 1878.44 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 301.79 | 157.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2222.30 | 30-JAN-05:38 | 13543.20 | 1812.70 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.31 |
February | 2142.61 | 02-FEB-02:35 | 2708.64 | 181.27 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.25 |
March | 1924.06 | 13-MAR-04:40 | 2708.64 | 362.54 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.72 |
April | 2457.28 | 14-APR-20:10 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 47.95 | 0.00 |
May | 2414.92 | 31-MAY-20:10 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 48.04 | 0.00 |
June | 2769.78 | 28-JUN-20:10 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 89.55 | 0.00 |
July | 2613.25 | 20-JUL-20:10 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 79.66 | 0.00 |
August | 2646.71 | 15-AUG-20:10 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 76.07 | 0.00 |
September | 2597.82 | 07-SEP-21:00 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 66.93 | 0.00 |
October | 2396.76 | 05-OCT-20:10 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 0.00 |
November | 2063.41 | 01-NOV-20:10 | 1203.84 | 725.08 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.19 |
December | 2185.61 | 14-DEC-00:23 | 13543.20 | 1812.70 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1924.06 | 1203.84 | 181.27 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2769.78 | 13543.20 | 1812.70 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 89.55 | 143.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1420.98 | 30-JAN-05:38 | 2864.16 | 3023.10 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.60 |
February | 1381.07 | 02-FEB-02:35 | 572.83 | 302.31 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.18 |
March | 1298.93 | 17-MAR-21:00 | 254.59 | 1209.24 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.47 |
April | 2294.71 | 25-APR-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 68.83 | 0.00 |
May | 2450.64 | 31-MAY-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 119.06 | 0.00 |
June | 3125.15 | 28-JUN-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 216.98 | 0.00 |
July | 2978.72 | 21-JUL-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 217.80 | 0.00 |
August | 2828.90 | 15-AUG-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 185.15 | 0.00 |
September | 2695.58 | 08-SEP-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 166.06 | 0.00 |
October | 2452.73 | 03-OCT-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 102.69 | 0.00 |
November | 1393.93 | 02-NOV-20:00 | 222.77 | 1360.40 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.01 |
December | 1384.11 | 14-DEC-00:23 | 2864.16 | 3023.10 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1298.93 | 222.77 | 302.31 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3125.15 | 2864.16 | 3023.10 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 217.80 | 321.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1232.31 | 30-JAN-05:38 | 2203.20 | 506.04 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.76 |
February | 1187.05 | 02-FEB-02:35 | 440.64 | 50.60 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.30 |
March | 1011.56 | 02-MAR-05:27 | 660.96 | 151.81 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.11 |
April | 1112.21 | 21-APR-03:50 | 1762.56 | 202.41 | 407.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.57 |
May | 967.85 | 31-MAY-18:07 | 1028.16 | 1214.49 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 117.69 | 0.00 |
June | 1356.10 | 28-JUN-19:10 | 171.36 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 148.22 | 0.00 |
July | 1250.82 | 21-JUL-20:00 | 171.36 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 125.66 | 0.00 |
August | 1146.66 | 15-AUG-20:00 | 171.36 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 106.82 | 0.00 |
September | 1032.36 | 08-SEP-20:00 | 171.36 | 227.72 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 95.81 | 0.00 |
October | 1169.05 | 12-OCT-04:42 | 1321.92 | 303.62 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.01 |
November | 1130.91 | 30-NOV-05:05 | 440.64 | 101.21 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.46 |
December | 1188.78 | 14-DEC-00:23 | 2203.20 | 506.04 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 967.85 | 171.36 | 50.60 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1356.10 | 2203.20 | 1214.49 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 148.22 | 174.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 42080.81 | 12-JAN-07:04 | 4032.00 | 1984.52 | 28880.85 | 250904.69 | 0.00 | 0.00 | 0.00 | 0.00 | 491.73 |
February | 42147.59 | 02-FEB-07:09 | 4032.00 | 1984.52 | 28880.85 | 250904.69 | 0.00 | 0.00 | 0.00 | 0.00 | 479.82 |
March | 41396.38 | 30-MAR-06:33 | 4032.00 | 1984.52 | 28880.85 | 250904.69 | 0.00 | 0.00 | 0.00 | 0.00 | 489.95 |
April | 39538.83 | 14-APR-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 162.25 | 0.00 |
May | 39633.74 | 09-MAY-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 162.44 | 0.00 |
June | 40402.89 | 28-JUN-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 296.31 | 0.00 |
July | 40201.72 | 21-JUL-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 297.40 | 0.00 |
August | 40086.33 | 15-AUG-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 252.76 | 0.00 |
September | 39908.61 | 08-SEP-20:00 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 226.68 | 0.00 |
October | 39481.22 | 12-OCT-06:38 | 4032.00 | 1984.52 | 28880.85 | 250904.69 | 0.00 | 0.00 | 0.00 | 0.00 | 417.97 |
November | 46138.40 | 23-NOV-21:29 | 8064.00 | 2381.43 | 33694.32 | 292722.14 | 0.00 | 0.00 | 0.00 | 0.00 | 515.38 |
December | 48778.68 | 04-DEC-21:39 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 499.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 39481.22 | 705.60 | 357.21 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48778.68 | 8064.00 | 3175.23 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 297.40 | 515.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15980.31 | 30-JAN-05:38 | 153684.00 | 3915.35 | 3048.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 699.62 |
February | 14860.33 | 02-FEB-01:50 | 107578.80 | 2055.56 | 1778.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.34 |
March | 12574.73 | 02-MAR-05:27 | 46105.20 | 1174.60 | 914.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.88 |
April | 13292.91 | 21-APR-03:50 | 122947.20 | 1566.14 | 1625.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.28 |
May | 11658.96 | 09-MAY-21:10 | 15368.40 | 1174.60 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 200.84 | 0.00 |
June | 13622.52 | 28-JUN-18:06 | 59766.00 | 4776.72 | 4572.35 | 0.00 | 0.00 | 0.00 | 0.00 | 673.51 | 0.00 |
July | 13329.35 | 21-JUL-21:10 | 15368.40 | 1174.60 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 403.93 | 0.00 |
August | 13660.64 | 15-AUG-18:05 | 71719.20 | 6953.65 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 559.71 | 0.00 |
September | 14183.87 | 28-SEP-15:03 | 59766.00 | 2089.82 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 548.10 | 0.00 |
October | 14098.10 | 05-OCT-15:03 | 51228.00 | 1791.27 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 408.88 | 0.00 |
November | 14253.41 | 01-NOV-15:03 | 51228.00 | 1791.27 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 201.29 | 0.00 |
December | 15470.44 | 14-DEC-00:23 | 153684.00 | 3915.35 | 3048.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 794.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11658.96 | 15368.40 | 1174.60 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15980.31 | 153684.00 | 6953.65 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 673.51 | 794.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 73990.25 | 11-JAN-06:27 | 106453.62 | 13686.91 | 15835.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1968.20 |
February | 55655.86 | 24-FEB-05:54 | 228114.90 | 11405.76 | 15835.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2172.11 |
March | 56343.11 | 24-MAR-04:43 | 273737.88 | 13686.91 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2209.14 |
April | 43163.18 | 14-APR-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 552.98 | 0.00 |
May | 42577.69 | 09-MAY-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 573.59 | 0.00 |
June | 48445.70 | 28-JUN-20:10 | 40553.76 | 9124.61 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1465.49 | 0.00 |
July | 47508.45 | 21-JUL-20:10 | 40553.76 | 9124.61 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1452.82 | 0.00 |
August | 46971.73 | 15-AUG-20:10 | 40553.76 | 9124.61 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.81 | 0.00 |
September | 46803.73 | 07-SEP-21:10 | 45622.98 | 6843.46 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1032.21 | 0.00 |
October | 70167.46 | 30-OCT-04:57 | 136868.94 | 6843.46 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1771.82 |
November | 43544.48 | 30-NOV-05:05 | 91245.96 | 4562.30 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1937.35 |
December | 56524.22 | 04-DEC-23:27 | 182491.92 | 13686.91 | 16891.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2588.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 42577.69 | 40553.76 | 4562.30 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73990.25 | 273737.88 | 13686.91 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 1465.49 | 2588.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3726.19 | 31-JAN-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 70.20 | 0.00 |
February | 3516.04 | 22-FEB-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.32 |
March | 3684.94 | 18-MAR-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 52.34 | 0.00 |
April | 3772.61 | 14-APR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 131.20 | 0.00 |
May | 3758.40 | 30-MAY-18:01 | 970.20 | 763.21 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 0.00 |
June | 3784.51 | 27-JUN-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 179.82 | 0.00 |
July | 3762.12 | 05-JUL-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 161.14 | 0.00 |
August | 3775.55 | 27-AUG-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 182.29 | 0.00 |
September | 3792.54 | 28-SEP-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 157.03 | 0.00 |
October | 3784.39 | 06-OCT-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 130.79 | 0.00 |
November | 3752.56 | 20-NOV-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 45.88 | 0.00 |
December | 3660.65 | 25-DEC-16:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 35.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3516.04 | 324.00 | 240.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3792.54 | 970.20 | 763.21 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 182.29 | 19.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3639.64 | 31-JAN-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 72.09 | 0.00 |
February | 3445.19 | 22-FEB-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 |
March | 3611.88 | 18-MAR-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 53.82 | 0.00 |
April | 3738.40 | 25-APR-18:01 | 970.20 | 763.12 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 97.17 | 0.00 |
May | 3741.29 | 30-MAY-18:01 | 970.20 | 763.12 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 98.91 | 0.00 |
June | 3770.32 | 27-JUN-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 179.47 | 0.00 |
July | 3746.56 | 05-JUL-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 160.83 | 0.00 |
August | 3736.16 | 25-AUG-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 169.92 | 0.00 |
September | 3732.69 | 28-SEP-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 158.03 | 0.00 |
October | 3719.53 | 06-OCT-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 131.95 | 0.00 |
November | 3666.17 | 20-NOV-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 47.76 | 0.00 |
December | 3554.71 | 25-DEC-16:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 37.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3445.19 | 324.00 | 240.08 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3770.32 | 970.20 | 763.12 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 179.47 | 17.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 692.43 | 14-JAN-13:50 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 0.00 |
February | 533.39 | 01-FEB-15:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.12 |
March | 512.74 | 18-MAR-14:30 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 10.12 | 0.00 |
April | 540.34 | 14-APR-13:40 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 31.84 | 0.00 |
May | 451.74 | 09-MAY-17:17 | 0.00 | 206.33 | 526.30 | 0.00 | 0.00 | 0.00 | 0.00 | 33.70 | 0.00 |
June | 556.09 | 28-JUN-17:13 | 0.00 | 154.75 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 53.48 | 0.00 |
July | 529.12 | 21-JUL-19:10 | 0.00 | 76.99 | 170.27 | 0.00 | 0.00 | 0.00 | 0.00 | 42.86 | 0.00 |
August | 617.82 | 27-AUG-14:00 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 48.97 | 0.00 |
September | 692.01 | 28-SEP-13:40 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 | 0.00 |
October | 706.78 | 18-OCT-13:50 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 | 0.00 |
November | 728.57 | 20-NOV-14:30 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 11.13 | 0.00 |
December | 686.94 | 25-DEC-13:40 | 0.00 | 25.41 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 451.74 | 0.00 | 21.56 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 728.57 | 0.00 | 206.33 | 526.30 | 0.00 | 0.00 | 0.00 | 0.00 | 53.48 | 25.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1129.55 | 31-JAN-19:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 0.00 |
February | 911.15 | 20-FEB-09:02 | 324.00 | 258.76 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.93 |
March | 1211.57 | 15-MAR-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 | 0.00 |
April | 1267.98 | 25-APR-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 26.77 | 0.00 |
May | 1269.49 | 30-MAY-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 27.24 | 0.00 |
June | 1272.81 | 27-JUN-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | 0.00 |
July | 1270.15 | 07-JUL-18:02 | 831.60 | 411.24 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 41.66 | 0.00 |
August | 1266.43 | 27-AUG-15:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 50.68 | 0.00 |
September | 1269.39 | 18-SEP-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 34.01 | 0.00 |
October | 1266.99 | 05-OCT-18:01 | 970.20 | 479.78 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 26.29 | 0.00 |
November | 1139.14 | 20-NOV-16:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 16.90 | 0.00 |
December | 975.20 | 23-DEC-09:02 | 324.00 | 258.76 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 911.15 | 324.00 | 150.94 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1272.81 | 970.20 | 479.78 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 50.68 | 28.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3267.06 | 31-JAN-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 70.60 | 0.00 |
February | 3063.22 | 22-FEB-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.22 |
March | 3242.19 | 18-MAR-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 52.34 | 0.00 |
April | 3314.68 | 14-APR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 131.36 | 0.00 |
May | 3318.34 | 18-MAY-08:61 | 252.00 | 377.32 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 50.95 | 0.00 |
June | 3339.02 | 19-JUN-08:61 | 252.00 | 377.32 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 90.79 | 0.00 |
July | 3319.28 | 01-JUL-08:61 | 378.00 | 480.22 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 52.57 | 0.00 |
August | 3330.17 | 27-AUG-08:61 | 378.00 | 480.22 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 75.49 | 0.00 |
September | 3334.45 | 28-SEP-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 157.11 | 0.00 |
October | 3324.90 | 06-OCT-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 130.95 | 0.00 |
November | 3273.66 | 20-NOV-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 46.85 | 0.00 |
December | 3197.66 | 25-DEC-16:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 35.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3063.22 | 252.00 | 240.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3339.02 | 680.40 | 480.22 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 157.11 | 18.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3188.04 | 31-JAN-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 72.62 | 0.00 |
February | 2821.31 | 22-FEB-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 |
March | 3203.87 | 15-MAR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 64.49 | 0.00 |
April | 3272.49 | 14-APR-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 132.04 | 0.00 |
May | 3299.57 | 18-MAY-08:61 | 252.00 | 377.27 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 50.84 | 0.00 |
June | 3323.48 | 19-JUN-08:61 | 252.00 | 377.27 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 90.57 | 0.00 |
July | 3303.73 | 01-JUL-08:61 | 378.00 | 480.16 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 52.35 | 0.00 |
August | 3306.40 | 27-AUG-08:61 | 378.00 | 480.16 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 75.55 | 0.00 |
September | 3282.02 | 28-SEP-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 158.13 | 0.00 |
October | 3267.68 | 06-OCT-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 132.15 | 0.00 |
November | 3188.91 | 20-NOV-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 49.07 | 0.00 |
December | 2984.25 | 25-DEC-16:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2821.31 | 252.00 | 240.08 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3323.48 | 680.40 | 480.16 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 158.13 | 7.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2812.72 | 30-JAN-05:38 | 22633.56 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.29 |
February | 2756.01 | 02-FEB-02:35 | 4526.71 | 497.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.31 |
March | 2441.21 | 13-MAR-04:40 | 4526.71 | 995.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.85 |
April | 3199.76 | 14-APR-18:15 | 3520.78 | 3983.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.33 | 0.00 |
May | 3270.32 | 31-MAY-18:30 | 1760.39 | 1991.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.62 | 0.00 |
June | 4159.59 | 28-JUN-19:10 | 1760.39 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.11 | 0.00 |
July | 3819.18 | 21-JUL-19:10 | 1760.39 | 2240.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.20 | 0.00 |
August | 3661.06 | 25-AUG-18:15 | 3520.78 | 3983.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.88 | 0.00 |
September | 3547.23 | 08-SEP-18:15 | 3520.78 | 3983.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.52 | 0.00 |
October | 3221.75 | 05-OCT-18:13 | 5281.16 | 5975.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.09 | 0.00 |
November | 2588.25 | 30-NOV-05:05 | 4526.71 | 995.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.71 |
December | 2622.63 | 14-DEC-00:23 | 22633.56 | 4979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2441.21 | 1760.39 | 497.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4159.59 | 22633.56 | 5975.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.11 | 246.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3931.14 | 31-JAN-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 70.02 | 0.00 |
February | 3706.02 | 22-FEB-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.47 |
March | 3894.52 | 18-MAR-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 51.95 | 0.00 |
April | 3998.38 | 14-APR-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 130.52 | 0.00 |
May | 3981.25 | 07-MAY-15:01 | 378.00 | 282.99 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 133.49 | 0.00 |
June | 4009.02 | 27-JUN-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 179.21 | 0.00 |
July | 3981.48 | 05-JUL-18:02 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 160.63 | 0.00 |
August | 4002.75 | 27-AUG-15:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 181.60 | 0.00 |
September | 4017.08 | 28-SEP-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 156.43 | 0.00 |
October | 4002.21 | 06-OCT-15:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 130.36 | 0.00 |
November | 3967.99 | 20-NOV-16:01 | 680.40 | 240.11 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 45.43 | 0.00 |
December | 3863.03 | 25-DEC-16:02 | 324.00 | 242.57 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 34.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3706.02 | 324.00 | 240.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4017.08 | 831.60 | 654.18 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 181.60 | 19.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3826.24 | 31-JAN-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 72.22 | 0.00 |
February | 3620.51 | 22-FEB-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.76 |
March | 3810.61 | 18-MAR-15:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 53.53 | 0.00 |
April | 3952.25 | 25-APR-18:01 | 970.20 | 763.12 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 0.00 |
May | 3950.93 | 30-MAY-18:01 | 970.20 | 763.12 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 98.54 | 0.00 |
June | 3992.03 | 27-JUN-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 178.83 | 0.00 |
July | 3962.87 | 05-JUL-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 160.30 | 0.00 |
August | 3956.15 | 25-AUG-18:02 | 831.60 | 654.11 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 169.27 | 0.00 |
September | 3948.59 | 28-SEP-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 157.49 | 0.00 |
October | 3928.09 | 06-OCT-15:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 131.59 | 0.00 |
November | 3863.64 | 20-NOV-16:01 | 680.40 | 240.08 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 47.60 | 0.00 |
December | 3732.14 | 25-DEC-16:02 | 324.00 | 242.54 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 37.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3620.51 | 324.00 | 240.08 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3992.03 | 970.20 | 763.12 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 178.83 | 17.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2010.56 | 31-JAN-16:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 34.16 | 0.00 |
February | 1878.98 | 22-FEB-16:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.01 |
March | 1985.33 | 18-MAR-15:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 25.11 | 0.00 |
April | 2006.31 | 14-APR-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 66.25 | 0.00 |
May | 1985.78 | 07-MAY-15:01 | 378.00 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 68.12 | 0.00 |
June | 1982.65 | 27-JUN-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 | 0.00 |
July | 1975.20 | 07-JUL-15:02 | 583.20 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 77.95 | 0.00 |
August | 2001.21 | 26-AUG-15:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 97.82 | 0.00 |
September | 2029.74 | 28-SEP-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 79.10 | 0.00 |
October | 2025.86 | 06-OCT-15:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 65.66 | 0.00 |
November | 2021.11 | 20-NOV-16:01 | 680.40 | 150.94 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 21.80 | 0.00 |
December | 1991.39 | 25-DEC-16:02 | 324.00 | 152.48 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 15.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1878.98 | 324.00 | 129.38 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2029.74 | 680.40 | 177.90 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 | 11.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33791.94 | 10-JAN-05:05 | 53977.54 | 1375.14 | 4498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.61 |
February | 31904.40 | 24-FEB-05:54 | 134943.84 | 3437.84 | 11246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.60 |
March | 32267.07 | 24-MAR-04:43 | 161932.61 | 4125.41 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.42 |
April | 29430.07 | 21-APR-03:54 | 269887.68 | 3437.84 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.47 |
May | 22865.87 | 09-MAY-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 126.11 | 0.00 |
June | 24844.64 | 28-JUN-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 267.78 | 0.00 |
July | 24361.85 | 21-JUL-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 256.36 | 0.00 |
August | 23835.65 | 10-AUG-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 242.95 | 0.00 |
September | 23589.71 | 07-SEP-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 229.04 | 0.00 |
October | 25816.82 | 12-OCT-04:42 | 161932.61 | 4125.41 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.43 |
November | 25232.52 | 30-NOV-05:05 | 53977.54 | 1375.14 | 4498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.38 |
December | 31224.53 | 14-DEC-23:37 | 161932.61 | 6188.11 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22865.87 | 26988.77 | 1375.14 | 4498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33791.94 | 269887.68 | 6188.11 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 267.78 | 523.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33422.31 | 09-JAN-23:55 | 161932.61 | 6188.11 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.06 |
February | 33994.67 | 24-FEB-05:54 | 134943.84 | 3437.84 | 11246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.39 |
March | 33919.77 | 24-MAR-04:43 | 161932.61 | 4125.41 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.01 |
April | 33246.64 | 21-APR-03:54 | 269887.68 | 3437.84 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.30 |
May | 24223.83 | 09-MAY-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 126.10 | 0.00 |
June | 26255.11 | 28-JUN-21:20 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 267.59 | 0.00 |
July | 25745.56 | 21-JUL-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 256.36 | 0.00 |
August | 25199.47 | 10-AUG-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 242.95 | 0.00 |
September | 24937.72 | 07-SEP-21:10 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 229.04 | 0.00 |
October | 27337.25 | 25-OCT-04:40 | 134943.84 | 3437.84 | 11246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.95 |
November | 27641.91 | 08-NOV-03:30 | 188921.38 | 2406.49 | 15745.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.36 |
December | 34171.80 | 14-DEC-23:37 | 161932.61 | 6188.11 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24223.83 | 26988.77 | 2062.70 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34171.80 | 269887.68 | 6188.11 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 267.59 | 527.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36405.13 | 13-JAN-07:39 | 10674.24 | 6054.62 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 461.36 |
February | 34465.36 | 28-FEB-07:13 | 10674.24 | 6054.62 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 486.94 |
March | 34857.39 | 31-MAR-06:53 | 10674.24 | 6054.62 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 492.68 |
April | 30564.23 | 30-APR-10:40 | 1601.14 | 726.55 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 140.85 | 0.00 |
May | 30788.78 | 07-MAY-10:40 | 1601.14 | 726.55 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 141.41 | 0.00 |
June | 31667.48 | 18-JUN-10:50 | 800.57 | 363.28 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 268.50 | 0.00 |
July | 31667.26 | 22-JUL-10:40 | 1601.14 | 605.46 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 269.89 | 0.00 |
August | 31708.56 | 13-AUG-10:40 | 1601.14 | 726.55 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 224.58 | 0.00 |
September | 31427.60 | 09-SEP-10:35 | 1601.14 | 605.46 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 221.44 | 0.00 |
October | 32601.45 | 25-OCT-08:07 | 3202.27 | 2906.22 | 89477.13 | 67478.50 | 0.00 | 0.00 | 0.00 | 0.00 | 407.90 |
November | 33754.42 | 24-NOV-08:15 | 4269.70 | 1937.48 | 59651.42 | 59980.88 | 0.00 | 0.00 | 0.00 | 0.00 | 443.25 |
December | 35437.30 | 29-DEC-08:10 | 10674.24 | 4843.69 | 149128.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 452.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 30564.23 | 800.57 | 363.28 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36405.13 | 10674.24 | 6054.62 | 149128.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 269.89 | 492.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4201.26 | 30-JAN-05:38 | 23954.40 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.85 |
February | 4099.66 | 02-FEB-02:35 | 4790.88 | 527.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.07 |
March | 4521.25 | 18-MAR-15:00 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.29 | 0.00 |
April | 6911.28 | 14-APR-15:03 | 9315.60 | 4611.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.21 | 0.00 |
May | 6657.88 | 31-MAY-18:15 | 3726.24 | 4216.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.66 | 0.00 |
June | 8515.73 | 28-JUN-18:13 | 5589.36 | 6324.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.53 | 0.00 |
July | 7781.02 | 20-JUL-18:17 | 5589.36 | 6324.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.60 | 0.00 |
August | 7718.78 | 26-AUG-14:50 | 798.48 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.55 | 0.00 |
September | 7723.24 | 07-SEP-15:03 | 7984.80 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.20 | 0.00 |
October | 7204.97 | 02-OCT-13:10 | 532.32 | 658.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.59 | 0.00 |
November | 5151.44 | 01-NOV-15:03 | 7984.80 | 3952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.70 | 0.00 |
December | 4012.14 | 14-DEC-00:23 | 23954.40 | 5270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4012.14 | 532.32 | 527.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8515.73 | 23954.40 | 6324.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.55 | 435.96 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.447920E+12 | 307407.43 | 31-JAN-19:10 | 0.438810E+12 | 388293.86 | 01-JAN-23:19 |
February | 0.356173E+12 | 259268.36 | 09-FEB-20:10 | 0.399620E+12 | 365962.79 | 04-FEB-19:10 |
March | 0.436696E+12 | 323507.21 | 16-MAR-19:10 | 0.420745E+12 | 348094.92 | 01-MAR-18:00 |
April | 0.545196E+12 | 387513.31 | 14-APR-19:10 | 0.371317E+12 | 341913.71 | 04-APR-17:49 |
May | 0.614088E+12 | 397545.59 | 31-MAY-19:19 | 0.370028E+12 | 318073.31 | 01-MAY-17:10 |
June | 0.692032E+12 | 463255.60 | 28-JUN-19:30 | 0.347772E+12 | 314090.36 | 01-JUN-17:19 |
July | 0.725894E+12 | 463845.66 | 21-JUL-19:00 | 0.353909E+12 | 311222.67 | 03-JUL-17:19 |
August | 0.717101E+12 | 443689.54 | 15-AUG-19:10 | 0.355775E+12 | 312318.41 | 31-AUG-17:30 |
September | 0.665211E+12 | 447125.95 | 08-SEP-19:10 | 0.351735E+12 | 315596.82 | 29-SEP-17:30 |
October | 0.540332E+12 | 405716.76 | 02-OCT-19:10 | 0.383146E+12 | 327833.93 | 31-OCT-17:00 |
November | 0.440941E+12 | 324007.21 | 01-NOV-18:10 | 0.398189E+12 | 360419.22 | 23-NOV-21:10 |
December | 0.420437E+12 | 269219.38 | 26-DEC-20:10 | 0.451985E+12 | 428064.21 | 16-DEC-22:10 |
Annual Sum or Average | 0.660202E+13 | 0.464303E+13 | ||||
Minimum of Months | 0.356173E+12 | 259268.36 | 0.347772E+12 | 311222.67 | ||
Maximum of Months | 0.725894E+12 | 463845.66 | 0.451985E+12 | 428064.21 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.654550E+11 | 0.237936E+11 | 0.148212E+12 | 0.553310E+11 | 0.492966E+11 | 0.144854E+11 | 0.00 | 0.669564E+11 | 0.00 | 0.00 | 0.114693E+11 | 0.770423E+10 | 0.00 |
February | 0.590593E+11 | 0.204104E+11 | 0.133859E+12 | 0.499765E+11 | 0.407491E+11 | 0.986001E+10 | 0.00 | 0.202171E+11 | 0.00 | 0.00 | 0.103155E+11 | 0.696182E+10 | 0.00 |
March | 0.652240E+11 | 0.209851E+11 | 0.148223E+12 | 0.553337E+11 | 0.457684E+11 | 0.136876E+11 | 0.00 | 0.634706E+11 | 0.00 | 0.00 | 0.110632E+11 | 0.770284E+10 | 0.00 |
April | 0.628949E+11 | 0.186586E+11 | 0.143397E+12 | 0.535455E+11 | 0.521232E+11 | 0.189825E+11 | 0.00 | 0.168650E+12 | 0.00 | 0.00 | 0.144581E+11 | 0.746489E+10 | 0.00 |
May | 0.649233E+11 | 0.178614E+11 | 0.148223E+12 | 0.553320E+11 | 0.571170E+11 | 0.206721E+11 | 0.00 | 0.219507E+12 | 0.00 | 0.00 | 0.175537E+11 | 0.770425E+10 | 0.00 |
June | 0.626852E+11 | 0.166935E+11 | 0.143446E+12 | 0.535481E+11 | 0.642709E+11 | 0.217601E+11 | 0.00 | 0.294511E+12 | 0.00 | 0.00 | 0.225853E+11 | 0.745687E+10 | 0.00 |
July | 0.647338E+11 | 0.174721E+11 | 0.148174E+12 | 0.553290E+11 | 0.660041E+11 | 0.230338E+11 | 0.00 | 0.313251E+12 | 0.00 | 0.00 | 0.248830E+11 | 0.771240E+10 | 0.00 |
August | 0.650802E+11 | 0.186400E+11 | 0.148234E+12 | 0.553337E+11 | 0.661980E+11 | 0.229816E+11 | 0.00 | 0.304193E+12 | 0.00 | 0.00 | 0.233971E+11 | 0.770434E+10 | 0.00 |
September | 0.630017E+11 | 0.195762E+11 | 0.143408E+12 | 0.535457E+11 | 0.633041E+11 | 0.220723E+11 | 0.00 | 0.267705E+12 | 0.00 | 0.00 | 0.199663E+11 | 0.746623E+10 | 0.00 |
October | 0.653158E+11 | 0.219491E+11 | 0.148201E+12 | 0.553308E+11 | 0.568804E+11 | 0.185814E+11 | 0.00 | 0.148991E+12 | 0.00 | 0.00 | 0.121388E+11 | 0.770290E+10 | 0.00 |
November | 0.633563E+11 | 0.226813E+11 | 0.143462E+12 | 0.535469E+11 | 0.494485E+11 | 0.146538E+11 | 0.00 | 0.716623E+11 | 0.00 | 0.00 | 0.961927E+10 | 0.744868E+10 | 0.00 |
December | 0.654034E+11 | 0.242478E+11 | 0.148174E+12 | 0.553297E+11 | 0.495019E+11 | 0.118381E+11 | 0.00 | 0.394144E+11 | 0.00 | 0.00 | 0.136258E+11 | 0.771236E+10 | 0.00 |
Annual Sum or Average | 0.767133E+12 | 0.242969E+12 | 0.174501E+13 | 0.651482E+12 | 0.660662E+12 | 0.212609E+12 | 0.00 | 0.197853E+13 | 0.00 | 0.00 | 0.191075E+12 | 0.907418E+11 | 0.00 |
Minimum of Months | 0.590593E+11 | 0.166935E+11 | 0.133859E+12 | 0.499765E+11 | 0.407491E+11 | 0.986001E+10 | 0.00 | 0.202171E+11 | 0.00 | 0.00 | 0.961927E+10 | 0.696182E+10 | 0.00 |
Maximum of Months | 0.654550E+11 | 0.242478E+11 | 0.148234E+12 | 0.553337E+11 | 0.661980E+11 | 0.230338E+11 | 0.00 | 0.313251E+12 | 0.00 | 0.00 | 0.248830E+11 | 0.771240E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.351067E+11 | 0.00 | 0.251785E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.364043E+11 | 0.00 | 0.226012E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.259984E+11 | 0.00 | 0.242723E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.109238E+10 | 0.00 | 0.223269E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.252381E+09 | 0.00 | 0.217797E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 41559702.01 | 0.00 | 0.200616E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 46735438.96 | 0.00 | 0.202042E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 59776674.22 | 0.00 | 0.203676E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 93382907.11 | 0.00 | 0.204671E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.775115E+10 | 0.00 | 0.223492E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.223025E+11 | 0.00 | 0.228795E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.533921E+11 | 0.00 | 0.246772E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.182541E+12 | 0.00 | 0.267165E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 41559702.01 | 0.00 | 0.200616E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.533921E+11 | 0.00 | 0.251785E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 62892.57 | 02-JAN-20:10 | 15448.40 | 01-JAN-00:10 | 89475.41 | 02-JAN-07:10 | 39726.11 | 02-JAN-07:19 | 32420.53 | 22-JAN-07:49 | 8374.27 | 31-JAN-16:30 | 0.00 | 01-JAN-00:10 |
February | 62892.57 | 01-FEB-20:10 | 15448.40 | 01-FEB-00:10 | 89475.41 | 01-FEB-07:10 | 39726.11 | 01-FEB-07:19 | 28267.60 | 24-FEB-05:49 | 7950.00 | 18-FEB-16:10 | 0.00 | 01-FEB-00:10 |
March | 62892.57 | 01-MAR-20:10 | 15448.40 | 01-MAR-00:10 | 89475.41 | 01-MAR-07:10 | 39726.11 | 13-MAR-06:19 | 30295.92 | 17-MAR-21:10 | 9010.32 | 17-MAR-19:49 | 0.00 | 01-MAR-00:10 |
April | 62892.57 | 03-APR-19:10 | 15448.40 | 01-APR-00:10 | 89475.41 | 03-APR-06:10 | 39726.11 | 03-APR-06:19 | 43317.75 | 14-APR-21:10 | 9231.51 | 25-APR-18:00 | 0.00 | 01-APR-00:10 |
May | 62892.57 | 01-MAY-19:10 | 15448.40 | 01-MAY-00:10 | 89475.41 | 01-MAY-06:10 | 39726.11 | 26-MAY-06:19 | 41711.77 | 09-MAY-21:10 | 9096.40 | 29-MAY-20:49 | 0.00 | 01-MAY-00:10 |
June | 62892.57 | 01-JUN-19:19 | 15448.40 | 01-JUN-00:10 | 89475.41 | 01-JUN-06:10 | 39724.80 | 01-JUN-06:19 | 51396.89 | 28-JUN-21:10 | 9630.15 | 28-JUN-18:49 | 0.00 | 01-JUN-00:10 |
July | 62892.57 | 03-JUL-19:30 | 15448.40 | 01-JUL-00:10 | 89475.41 | 03-JUL-06:10 | 39725.67 | 14-JUL-06:19 | 50931.54 | 21-JUL-21:10 | 9407.34 | 07-JUL-20:00 | 0.00 | 01-JUL-00:10 |
August | 62892.57 | 01-AUG-19:10 | 15448.40 | 01-AUG-00:10 | 89475.41 | 01-AUG-06:10 | 39726.11 | 04-AUG-06:19 | 51416.61 | 25-AUG-21:10 | 9478.37 | 27-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 62892.57 | 01-SEP-19:10 | 15448.40 | 01-SEP-00:10 | 89475.41 | 01-SEP-06:10 | 39726.11 | 01-SEP-06:19 | 53347.46 | 08-SEP-21:19 | 9462.34 | 10-SEP-19:19 | 0.00 | 01-SEP-00:10 |
October | 62892.57 | 02-OCT-19:10 | 15448.40 | 01-OCT-00:10 | 89475.41 | 02-OCT-06:10 | 39726.11 | 02-OCT-06:19 | 50260.59 | 03-OCT-21:10 | 9399.98 | 05-OCT-19:19 | 0.00 | 01-OCT-00:10 |
November | 62892.57 | 01-NOV-19:10 | 15448.40 | 01-NOV-00:10 | 89475.41 | 01-NOV-06:10 | 39726.11 | 01-NOV-06:19 | 36401.65 | 01-NOV-21:10 | 9186.86 | 01-NOV-18:10 | 0.00 | 01-NOV-00:10 |
December | 62892.57 | 01-DEC-20:10 | 15448.40 | 01-DEC-00:10 | 89475.41 | 01-DEC-07:10 | 39726.11 | 01-DEC-07:19 | 35574.36 | 04-DEC-22:49 | 8155.15 | 26-DEC-16:40 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 62892.57 | 15448.40 | 89475.41 | 39724.80 | 28267.60 | 7950.00 | 0.00 | |||||||
Maximum of Months | 62892.57 | 15448.40 | 89475.41 | 39726.11 | 53347.46 | 9630.15 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 104100.10 | 31-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:20 | 4738.72 | 12-JAN-19:10 | 0.00 |
February | 62945.86 | 22-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:10 | 4738.39 | 16-FEB-19:10 | 0.00 |
March | 102433.91 | 16-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4738.52 | 31-MAR-06:19 | 0.00 |
April | 148697.84 | 14-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-04:19 | 4738.54 | 27-APR-18:10 | 0.00 |
May | 161986.51 | 31-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-03:20 | 4738.53 | 18-MAY-18:10 | 0.00 |
June | 217591.64 | 28-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 4738.74 | 01-JUN-18:10 | 0.00 |
July | 198654.96 | 20-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 4738.65 | 20-JUL-18:10 | 0.00 |
August | 195071.93 | 25-AUG-15:09 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 4738.66 | 03-AUG-18:10 | 0.00 |
September | 184291.43 | 08-SEP-18:30 | 0.00 | 0.00 | 9938.94 | 01-SEP-00:10 | 4738.75 | 07-SEP-18:10 | 0.00 |
October | 157330.29 | 02-OCT-18:10 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 4738.76 | 12-OCT-18:10 | 0.00 |
November | 112124.01 | 01-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-10:20 | 4738.65 | 15-NOV-19:10 | 0.00 |
December | 88919.44 | 25-DEC-16:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 4738.62 | 28-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 62945.86 | 0.00 | 0.00 | 9938.94 | 4738.39 | 0.00 | |||
Maximum of Months | 217591.64 | 0.00 | 0.00 | 9938.94 | 4738.76 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 307407.43 | 31-JAN-19:10 | 55920.94 | 79417.81 | 15448.40 | 31837.63 | 26443.68 | 8223.99 | 0.00 | 82200.26 | 0.00 |
February | 259268.36 | 09-FEB-20:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 22343.92 | 6018.47 | 0.00 | 25483.01 | 0.00 |
March | 323507.21 | 16-MAR-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 25523.61 | 8449.70 | 0.00 | 82801.43 | 0.00 |
April | 387513.31 | 14-APR-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 35687.38 | 8688.83 | 0.00 | 128543.58 | 0.00 |
May | 397545.59 | 31-MAY-19:19 | 62892.57 | 88772.42 | 15448.40 | 32158.49 | 33752.96 | 8754.77 | 0.00 | 139640.74 | 0.00 |
June | 463255.60 | 28-JUN-19:30 | 62892.57 | 88772.42 | 15448.40 | 32159.27 | 43205.43 | 9095.81 | 0.00 | 195759.96 | 0.00 |
July | 463845.66 | 21-JUL-19:00 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 43756.81 | 9286.40 | 0.00 | 195956.36 | 0.00 |
August | 443689.54 | 15-AUG-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 42869.70 | 9287.71 | 0.00 | 176786.54 | 0.00 |
September | 447125.95 | 08-SEP-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 43381.79 | 9243.35 | 0.00 | 179877.36 | 0.00 |
October | 405716.76 | 02-OCT-19:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 36738.48 | 9179.67 | 0.00 | 144151.40 | 0.00 |
November | 324007.21 | 01-NOV-18:10 | 55920.94 | 79417.81 | 15448.40 | 31837.63 | 29246.39 | 9186.86 | 0.00 | 94715.63 | 0.00 |
December | 269219.38 | 26-DEC-20:10 | 62892.57 | 88772.42 | 15448.40 | 32151.31 | 26414.31 | 6797.27 | 0.00 | 31255.54 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 259268.36 | 55920.94 | 79417.81 | 15448.40 | 31837.63 | 22343.92 | 6018.47 | 0.00 | 25483.01 | 0.00 | |
Maximum of Months | 463845.66 | 62892.57 | 88772.42 | 15448.40 | 32159.77 | 43756.81 | 9287.71 | 0.00 | 195956.36 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 169509.67 | 13-JAN-02:39 | 0.00 | 245388.03 | 25-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 176232.64 | 02-FEB-03:39 | 0.00 | 245341.11 | 01-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 172512.98 | 30-MAR-06:30 | 0.00 | 244509.35 | 01-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 70068.25 | 21-APR-03:30 | 0.00 | 237665.39 | 04-APR-17:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 16247.84 | 01-MAY-04:10 | 0.00 | 214044.61 | 01-MAY-20:10 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 3847.31 | 10-JUN-08:09 | 0.00 | 210227.16 | 01-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 6120.01 | 27-JUL-08:09 | 0.00 | 207207.19 | 05-JUL-20:49 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 6213.45 | 30-AUG-08:09 | 0.00 | 208475.31 | 31-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 6234.40 | 21-SEP-08:09 | 0.00 | 211831.13 | 29-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 159135.30 | 12-OCT-04:00 | 0.00 | 224133.60 | 31-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 173145.29 | 04-NOV-06:30 | 0.00 | 243496.63 | 29-NOV-21:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 174539.79 | 19-DEC-03:09 | 0.00 | 245140.62 | 07-DEC-21:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 3847.31 | 0.00 | 207207.19 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 176232.64 | 0.00 | 245388.03 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 25.03 | 15.67 | 25.03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 24.98 | 10.83 | 24.98 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 24.96 | 10.67 | 24.96 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.87 | 1.67 | 24.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 24.99 | 7.33 | 24.99 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 24.99 | 19.33 | 24.99 |
Annual Sum or Average | 0.00 | 0.00 | 65.50 | 24.99 | 65.50 | 24.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 25.03 | 19.33 | 25.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.70 | 0.17 | 24.70 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.70 | 0.17 | 24.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.70 | 0.17 | 24.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 21.94 | 6.00 | 21.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.79 | 1.50 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.80 | 2.50 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.91 | 1.33 | 21.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.85 | 1.33 | 21.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.67 | 21.88 | 12.67 | 21.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 21.94 | 6.00 | 21.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 21.94 | 7.83 | 21.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.78 | 1.50 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.86 | 0.83 | 21.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.76 | 0.50 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.83 | 21.90 | 10.83 | 21.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 21.94 | 7.83 | 21.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.87 | 2.67 | 21.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.71 | 1.17 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.84 | 0.17 | 21.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.69 | 0.83 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.83 | 21.80 | 4.83 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.87 | 2.67 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.87 | 4.50 | 21.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.79 | 0.83 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.75 | 0.83 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.83 | 0.33 | 21.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.00 | 21.82 | 8.00 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.87 | 4.50 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.89 | 5.50 | 21.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.79 | 0.33 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.50 | 21.85 | 7.50 | 21.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.89 | 5.50 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 22.00 | 8.83 | 22.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.87 | 1.50 | 21.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.85 | 3.17 | 21.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.95 | 1.50 | 21.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.94 | 1.33 | 21.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.33 | 21.95 | 16.33 | 21.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 22.00 | 8.83 | 22.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 22.05 | 9.83 | 22.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.84 | 1.67 | 21.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.79 | 2.67 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.80 | 0.67 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.81 | 0.17 | 21.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.00 | 21.96 | 15.00 | 21.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 22.05 | 9.83 | 22.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.00 | 0.50 | 22.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.82 | 2.17 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.72 | 1.17 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.87 | 4.17 | 21.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.91 | 5.00 | 21.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.97 | 4.33 | 21.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.85 | 1.17 | 21.85 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
Annual Sum or Average | 0.00 | 0.00 | 19.17 | 21.88 | 19.17 | 21.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 22.00 | 5.00 | 22.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.83 | 0.67 | 24.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.17 | 24.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.92 | 0.67 | 24.92 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.58 | 0.17 | 24.58 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.67 | 0.67 | 24.67 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 24.77 | 2.33 | 24.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.92 | 0.67 | 24.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.74 | 1.50 | 24.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.71 | 0.33 | 24.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.87 | 1.00 | 24.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.17 | 24.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.64 | 0.67 | 24.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.72 | 1.00 | 24.72 |
Annual Sum or Average | 0.00 | 0.00 | 4.67 | 24.74 | 4.67 | 24.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.87 | 1.50 | 24.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 25.03 | 18.00 | 25.03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 25.09 | 11.00 | 25.09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 25.08 | 11.83 | 25.08 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.89 | 2.50 | 24.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 24.96 | 9.50 | 24.96 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 25.01 | 20.00 | 25.01 |
Annual Sum or Average | 0.00 | 0.00 | 72.83 | 25.03 | 72.83 | 25.03 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 25.09 | 20.00 | 25.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 547.50 | 23.93 | 12.83 | 23.93 | 0.00 | 23.93 |
February | 418.50 | 23.59 | 39.67 | 23.62 | 0.00 | 23.62 |
March | 724.67 | 23.29 | 0.00 | 23.29 | 0.00 | 23.29 |
April | 705.83 | 23.57 | 0.00 | 23.57 | 0.00 | 23.57 |
May | 744.00 | 23.34 | 0.00 | 23.34 | 0.00 | 23.34 |
June | 611.67 | 23.53 | 5.00 | 23.53 | 0.00 | 23.53 |
July | 277.67 | 23.94 | 517.17 | 23.95 | 173.67 | 23.96 |
August | 222.50 | 24.00 | 618.50 | 23.99 | 173.33 | 23.99 |
September | 115.67 | 24.00 | 541.50 | 24.00 | 115.67 | 24.00 |
October | 280.00 | 24.00 | 157.00 | 24.00 | 21.67 | 24.00 |
November | 344.33 | 24.00 | 164.00 | 24.00 | 29.17 | 24.00 |
December | 640.00 | 24.00 | 6.67 | 24.00 | 0.00 | 24.00 |
Annual Sum or Average | 5632.33 | 23.68 | 2062.33 | 23.76 | 513.50 | 23.77 |
Minimum of Months | 115.67 | 23.29 | 0.00 | 23.29 | 0.00 | 23.29 |
Maximum of Months | 744.00 | 24.00 | 618.50 | 24.00 | 173.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 393.67 | 22.56 | 129.83 | 22.91 | 0.83 | 22.91 |
February | 537.33 | 21.98 | 48.33 | 22.14 | 0.00 | 22.14 |
March | 551.33 | 22.32 | 54.83 | 22.45 | 4.50 | 22.44 |
April | 250.00 | 23.31 | 132.17 | 23.55 | 0.00 | 23.55 |
May | 196.50 | 23.63 | 60.17 | 23.72 | 0.00 | 23.72 |
June | 11.17 | 23.97 | 467.17 | 24.00 | 0.00 | 24.00 |
July | 182.17 | 23.98 | 656.33 | 23.99 | 161.83 | 23.99 |
August | 181.00 | 23.94 | 694.17 | 23.98 | 181.00 | 23.97 |
September | 151.83 | 23.96 | 675.33 | 23.98 | 150.17 | 23.98 |
October | 275.67 | 22.97 | 298.33 | 23.50 | 25.67 | 23.52 |
November | 405.17 | 22.61 | 191.50 | 22.93 | 48.67 | 22.90 |
December | 549.83 | 22.22 | 84.50 | 22.32 | 28.67 | 22.26 |
Annual Sum or Average | 3685.67 | 22.73 | 3492.67 | 23.32 | 601.33 | 23.35 |
Minimum of Months | 11.17 | 21.98 | 48.33 | 22.14 | 0.00 | 22.14 |
Maximum of Months | 551.33 | 23.98 | 694.17 | 24.00 | 181.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 633.83 | 23.13 | 5.50 | 23.13 | 0.00 | 23.13 |
February | 622.00 | 22.59 | 4.83 | 22.60 | 0.00 | 22.60 |
March | 636.00 | 22.82 | 0.83 | 22.82 | 0.00 | 22.82 |
April | 387.17 | 23.57 | 20.50 | 23.59 | 0.00 | 23.59 |
May | 336.17 | 23.69 | 10.33 | 23.70 | 0.00 | 23.70 |
June | 56.67 | 23.68 | 208.83 | 23.92 | 0.00 | 23.92 |
July | 225.83 | 23.97 | 578.67 | 23.95 | 189.33 | 23.95 |
August | 211.50 | 23.97 | 625.00 | 23.94 | 206.67 | 23.95 |
September | 163.17 | 23.97 | 589.00 | 23.94 | 162.33 | 23.94 |
October | 408.50 | 23.37 | 154.50 | 23.53 | 30.33 | 23.55 |
November | 571.00 | 23.14 | 93.67 | 23.20 | 46.33 | 23.20 |
December | 729.50 | 22.80 | 0.00 | 22.80 | 0.00 | 22.80 |
Annual Sum or Average | 4981.33 | 23.17 | 2291.67 | 23.41 | 635.00 | 23.45 |
Minimum of Months | 56.67 | 22.59 | 0.00 | 22.60 | 0.00 | 22.60 |
Maximum of Months | 729.50 | 23.97 | 625.00 | 23.95 | 206.67 | 23.95 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.83 | 22.56 | 0.00 | 22.56 | 0.00 | 22.56 |
February | 672.00 | 22.13 | 0.00 | 22.13 | 0.00 | 22.13 |
March | 739.67 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
April | 609.67 | 23.76 | 0.00 | 23.76 | 0.00 | 23.76 |
May | 587.33 | 23.99 | 0.00 | 23.99 | 0.00 | 23.99 |
June | 140.00 | 24.00 | 57.67 | 24.00 | 0.00 | 24.00 |
July | 88.50 | 24.00 | 550.33 | 24.00 | 23.50 | 24.00 |
August | 69.33 | 24.00 | 618.50 | 24.00 | 18.67 | 24.00 |
September | 42.00 | 24.00 | 509.67 | 24.00 | 39.50 | 24.00 |
October | 527.33 | 23.35 | 107.50 | 23.46 | 2.83 | 23.46 |
November | 683.50 | 22.75 | 23.00 | 22.77 | 16.50 | 22.77 |
December | 744.00 | 22.00 | 25.17 | 21.97 | 25.17 | 21.94 |
Annual Sum or Average | 5647.17 | 22.90 | 1891.83 | 23.16 | 126.17 | 23.16 |
Minimum of Months | 42.00 | 22.00 | 0.00 | 21.97 | 0.00 | 21.94 |
Maximum of Months | 744.00 | 24.00 | 618.50 | 24.00 | 39.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.55 | 10.83 | 21.54 | 10.83 | 21.53 |
February | 672.00 | 21.17 | 0.00 | 21.17 | 0.00 | 21.17 |
March | 744.00 | 21.53 | 19.67 | 21.52 | 19.67 | 21.50 |
April | 719.50 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
May | 742.50 | 23.26 | 0.00 | 23.26 | 0.00 | 23.26 |
June | 380.83 | 23.72 | 37.50 | 23.74 | 0.00 | 23.74 |
July | 165.83 | 23.70 | 412.67 | 23.80 | 32.17 | 23.80 |
August | 167.17 | 23.47 | 361.00 | 23.70 | 17.00 | 23.69 |
September | 308.17 | 23.34 | 187.67 | 23.47 | 39.00 | 23.46 |
October | 642.67 | 22.39 | 38.83 | 22.46 | 3.50 | 22.47 |
November | 720.00 | 21.70 | 12.83 | 21.70 | 12.83 | 21.69 |
December | 744.00 | 21.21 | 115.50 | 21.18 | 115.50 | 21.16 |
Annual Sum or Average | 6750.67 | 22.19 | 1196.50 | 22.38 | 250.50 | 22.36 |
Minimum of Months | 165.83 | 21.17 | 0.00 | 21.17 | 0.00 | 21.16 |
Maximum of Months | 744.00 | 23.72 | 412.67 | 23.80 | 115.50 | 23.80 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 212.50 | 24.06 | 738.50 | 24.00 | 212.50 | 24.01 |
February | 252.17 | 24.04 | 669.67 | 23.98 | 252.17 | 23.99 |
March | 248.83 | 24.04 | 739.50 | 23.99 | 248.83 | 24.00 |
April | 242.00 | 24.00 | 719.67 | 24.00 | 242.00 | 24.00 |
May | 269.50 | 24.00 | 744.00 | 24.00 | 269.50 | 24.00 |
June | 435.33 | 24.00 | 720.00 | 24.00 | 435.33 | 24.00 |
July | 616.67 | 24.00 | 744.00 | 24.00 | 616.67 | 24.00 |
August | 645.33 | 24.00 | 744.00 | 24.00 | 645.33 | 24.00 |
September | 580.17 | 24.00 | 720.00 | 24.00 | 580.17 | 24.00 |
October | 325.33 | 24.01 | 743.83 | 23.99 | 325.33 | 23.99 |
November | 262.50 | 24.02 | 715.67 | 23.98 | 262.50 | 23.99 |
December | 166.33 | 24.12 | 725.17 | 24.02 | 166.33 | 24.03 |
Annual Sum or Average | 4256.67 | 24.01 | 8724.00 | 24.00 | 4256.67 | 24.00 |
Minimum of Months | 166.33 | 24.00 | 669.67 | 23.98 | 166.33 | 23.99 |
Maximum of Months | 645.33 | 24.12 | 744.00 | 24.02 | 645.33 | 24.03 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 434.00 | 22.66 | 169.33 | 23.00 | 4.50 | 22.99 |
February | 568.00 | 22.11 | 65.17 | 22.23 | 22.00 | 22.24 |
March | 628.17 | 22.20 | 33.17 | 22.28 | 0.17 | 22.28 |
April | 322.00 | 22.70 | 141.00 | 23.06 | 0.00 | 23.06 |
May | 368.83 | 22.72 | 105.33 | 22.99 | 0.00 | 22.99 |
June | 115.17 | 22.62 | 414.67 | 23.56 | 2.17 | 23.56 |
July | 303.83 | 23.67 | 616.67 | 23.60 | 262.83 | 23.64 |
August | 304.17 | 23.67 | 681.00 | 23.63 | 289.50 | 23.65 |
September | 255.33 | 23.58 | 665.17 | 23.65 | 237.00 | 23.65 |
October | 315.83 | 22.78 | 316.00 | 23.29 | 48.50 | 23.31 |
November | 449.17 | 22.56 | 229.67 | 22.87 | 62.17 | 22.84 |
December | 573.83 | 22.36 | 84.67 | 22.57 | 0.00 | 22.57 |
Annual Sum or Average | 4638.33 | 22.68 | 3521.83 | 23.11 | 928.83 | 23.16 |
Minimum of Months | 115.17 | 22.11 | 33.17 | 22.23 | 0.00 | 22.24 |
Maximum of Months | 628.17 | 23.67 | 681.00 | 23.65 | 289.50 | 23.65 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.33 | 23.30 | 25.50 | 23.32 | 9.67 | 23.32 |
February | 548.33 | 22.81 | 52.50 | 22.89 | 27.50 | 22.92 |
March | 535.83 | 22.87 | 26.67 | 22.91 | 4.33 | 22.92 |
April | 334.33 | 23.38 | 40.17 | 23.45 | 0.00 | 23.45 |
May | 309.67 | 23.38 | 36.50 | 23.44 | 0.00 | 23.44 |
June | 77.17 | 23.33 | 320.67 | 23.84 | 1.00 | 23.84 |
July | 282.83 | 23.93 | 607.50 | 23.87 | 260.33 | 23.90 |
August | 291.50 | 23.94 | 654.00 | 23.88 | 287.33 | 23.90 |
September | 234.17 | 23.93 | 651.33 | 23.89 | 233.67 | 23.90 |
October | 289.17 | 23.40 | 206.00 | 23.61 | 49.50 | 23.64 |
November | 452.17 | 23.27 | 151.17 | 23.36 | 72.33 | 23.35 |
December | 677.67 | 23.09 | 0.00 | 23.09 | 0.00 | 23.09 |
Annual Sum or Average | 4526.17 | 23.29 | 2772.00 | 23.51 | 945.67 | 23.55 |
Minimum of Months | 77.17 | 22.81 | 0.00 | 22.89 | 0.00 | 22.92 |
Maximum of Months | 677.67 | 23.94 | 654.00 | 23.89 | 287.33 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 739.50 | 21.56 | 15.83 | 21.55 | 15.83 | 21.54 |
February | 671.17 | 21.32 | 8.00 | 21.30 | 8.00 | 21.29 |
March | 740.83 | 21.45 | 36.83 | 21.43 | 36.83 | 21.41 |
April | 694.00 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
May | 713.67 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
June | 628.00 | 21.53 | 8.00 | 21.55 | 0.00 | 21.55 |
July | 606.83 | 21.39 | 25.83 | 21.47 | 0.00 | 21.47 |
August | 591.67 | 21.33 | 36.50 | 21.45 | 0.67 | 21.45 |
September | 582.33 | 21.36 | 32.17 | 21.46 | 4.00 | 21.47 |
October | 689.17 | 21.52 | 8.67 | 21.53 | 2.67 | 21.53 |
November | 700.67 | 21.51 | 56.83 | 21.50 | 54.00 | 21.48 |
December | 743.17 | 21.44 | 179.00 | 21.36 | 179.00 | 21.31 |
Annual Sum or Average | 8101.00 | 21.48 | 407.67 | 21.49 | 301.00 | 21.47 |
Minimum of Months | 582.33 | 21.32 | 0.00 | 21.30 | 0.00 | 21.29 |
Maximum of Months | 743.17 | 21.65 | 179.00 | 21.65 | 179.00 | 21.65 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.30 | 67.00 | 21.26 | 67.00 | 21.22 |
February | 672.00 | 21.08 | 40.00 | 21.04 | 40.00 | 21.01 |
March | 744.00 | 21.31 | 79.50 | 21.27 | 79.50 | 21.23 |
April | 708.17 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
May | 719.33 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
June | 628.83 | 21.54 | 9.00 | 21.57 | 0.00 | 21.57 |
July | 610.00 | 21.40 | 21.50 | 21.47 | 0.00 | 21.47 |
August | 606.17 | 21.38 | 25.00 | 21.45 | 0.83 | 21.46 |
September | 618.17 | 21.46 | 15.33 | 21.50 | 4.50 | 21.51 |
October | 716.83 | 21.47 | 20.50 | 21.46 | 20.33 | 21.44 |
November | 716.33 | 21.34 | 122.67 | 21.30 | 122.67 | 21.26 |
December | 744.00 | 21.09 | 397.83 | 21.01 | 397.83 | 20.98 |
Annual Sum or Average | 8227.83 | 21.39 | 798.33 | 21.36 | 732.67 | 21.32 |
Minimum of Months | 606.17 | 21.08 | 0.00 | 21.01 | 0.00 | 20.98 |
Maximum of Months | 744.00 | 21.67 | 397.83 | 21.67 | 397.83 | 21.67 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.12 | 56.83 | 21.10 | 56.83 | 21.09 |
February | 672.00 | 21.10 | 23.83 | 21.09 | 23.83 | 21.07 |
March | 744.00 | 21.20 | 78.00 | 21.18 | 78.00 | 21.16 |
April | 720.00 | 21.48 | 0.17 | 21.48 | 0.17 | 21.48 |
May | 744.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
June | 720.00 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
July | 744.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
August | 744.00 | 21.66 | 1.33 | 21.67 | 1.33 | 21.67 |
September | 720.00 | 21.63 | 2.17 | 21.63 | 2.17 | 21.63 |
October | 744.00 | 21.36 | 23.83 | 21.35 | 23.83 | 21.35 |
November | 720.00 | 21.16 | 105.33 | 21.14 | 105.33 | 21.13 |
December | 744.00 | 21.03 | 384.00 | 21.00 | 384.00 | 20.98 |
Annual Sum or Average | 8760.00 | 21.40 | 675.50 | 21.37 | 675.50 | 21.34 |
Minimum of Months | 672.00 | 21.03 | 0.00 | 21.00 | 0.00 | 20.98 |
Maximum of Months | 744.00 | 21.70 | 384.00 | 21.70 | 384.00 | 21.70 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.63 | 17.00 | 21.62 | 17.00 | 21.61 |
February | 672.00 | 21.42 | 10.67 | 21.41 | 10.67 | 21.39 |
March | 741.17 | 21.57 | 30.00 | 21.55 | 30.00 | 21.53 |
April | 698.50 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
May | 736.17 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
June | 579.50 | 21.39 | 7.00 | 21.41 | 0.00 | 21.41 |
July | 571.83 | 21.29 | 33.50 | 21.40 | 0.00 | 21.40 |
August | 554.17 | 21.22 | 46.83 | 21.38 | 0.33 | 21.38 |
September | 558.67 | 21.29 | 30.50 | 21.40 | 2.00 | 21.40 |
October | 687.17 | 21.57 | 6.17 | 21.59 | 0.00 | 21.59 |
November | 712.33 | 21.59 | 64.33 | 21.55 | 64.33 | 21.52 |
December | 744.00 | 21.50 | 165.83 | 21.43 | 165.83 | 21.37 |
Annual Sum or Average | 7999.50 | 21.51 | 411.83 | 21.52 | 290.17 | 21.51 |
Minimum of Months | 554.17 | 21.22 | 0.00 | 21.38 | 0.00 | 21.37 |
Maximum of Months | 744.00 | 21.73 | 165.83 | 21.73 | 165.83 | 21.73 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.35 | 67.33 | 21.32 | 67.33 | 21.29 |
February | 672.00 | 21.18 | 24.00 | 21.16 | 24.00 | 21.14 |
March | 744.00 | 21.44 | 46.33 | 21.42 | 46.33 | 21.40 |
April | 717.83 | 21.74 | 0.00 | 21.74 | 0.00 | 21.74 |
May | 738.67 | 21.74 | 0.00 | 21.74 | 0.00 | 21.74 |
June | 581.83 | 21.40 | 7.33 | 21.42 | 0.00 | 21.42 |
July | 574.17 | 21.29 | 28.17 | 21.39 | 0.00 | 21.39 |
August | 568.33 | 21.27 | 16.33 | 21.32 | 1.00 | 21.33 |
September | 576.00 | 21.35 | 5.00 | 21.36 | 3.00 | 21.37 |
October | 710.50 | 21.55 | 7.33 | 21.55 | 7.33 | 21.55 |
November | 720.00 | 21.37 | 133.67 | 21.33 | 133.67 | 21.29 |
December | 744.00 | 21.12 | 372.00 | 21.07 | 372.00 | 21.04 |
Annual Sum or Average | 8091.33 | 21.41 | 707.50 | 21.39 | 654.67 | 21.36 |
Minimum of Months | 568.33 | 21.12 | 0.00 | 21.07 | 0.00 | 21.04 |
Maximum of Months | 744.00 | 21.74 | 372.00 | 21.74 | 372.00 | 21.74 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.81 | 0.00 | 22.81 | 0.00 | 22.81 |
February | 672.00 | 22.18 | 3.50 | 22.18 | 3.50 | 22.17 |
March | 744.00 | 22.59 | 0.00 | 22.59 | 0.00 | 22.59 |
April | 665.67 | 23.73 | 0.00 | 23.73 | 0.00 | 23.73 |
May | 700.83 | 23.94 | 0.00 | 23.94 | 0.00 | 23.94 |
June | 287.00 | 24.00 | 34.17 | 24.00 | 0.00 | 24.00 |
July | 332.83 | 23.99 | 532.33 | 23.99 | 221.83 | 23.99 |
August | 321.17 | 23.98 | 608.00 | 23.98 | 248.17 | 23.98 |
September | 223.50 | 23.97 | 493.83 | 23.98 | 205.67 | 23.97 |
October | 564.17 | 23.49 | 107.67 | 23.57 | 36.00 | 23.59 |
November | 701.33 | 22.96 | 63.83 | 22.95 | 61.83 | 22.94 |
December | 744.00 | 22.27 | 0.00 | 22.27 | 0.00 | 22.27 |
Annual Sum or Average | 6700.50 | 23.15 | 1843.33 | 23.32 | 777.00 | 23.37 |
Minimum of Months | 223.50 | 22.18 | 0.00 | 22.18 | 0.00 | 22.17 |
Maximum of Months | 744.00 | 24.00 | 608.00 | 24.00 | 248.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 738.33 | 21.51 | 69.83 | 21.46 | 69.83 | 21.42 |
February | 670.83 | 21.23 | 62.67 | 21.17 | 62.67 | 21.11 |
March | 737.83 | 21.39 | 84.83 | 21.34 | 84.83 | 21.30 |
April | 675.50 | 21.57 | 9.33 | 21.56 | 9.33 | 21.55 |
May | 693.50 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
June | 590.33 | 21.43 | 20.17 | 21.49 | 0.00 | 21.49 |
July | 589.00 | 21.33 | 57.67 | 21.51 | 0.00 | 21.51 |
August | 577.67 | 21.29 | 72.33 | 21.52 | 1.67 | 21.52 |
September | 570.67 | 21.31 | 63.83 | 21.50 | 9.00 | 21.51 |
October | 682.67 | 21.46 | 51.17 | 21.48 | 36.67 | 21.45 |
November | 698.17 | 21.44 | 148.33 | 21.39 | 144.00 | 21.34 |
December | 742.00 | 21.37 | 325.83 | 21.25 | 325.83 | 21.19 |
Annual Sum or Average | 7966.50 | 21.42 | 966.00 | 21.43 | 743.83 | 21.39 |
Minimum of Months | 570.67 | 21.23 | 0.00 | 21.17 | 0.00 | 21.11 |
Maximum of Months | 742.00 | 21.59 | 325.83 | 21.59 | 325.83 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.20 | 210.50 | 21.12 | 210.50 | 21.08 |
February | 672.00 | 20.98 | 135.00 | 20.88 | 135.00 | 20.81 |
March | 744.00 | 21.24 | 130.00 | 21.17 | 130.00 | 21.12 |
April | 696.50 | 21.60 | 11.00 | 21.59 | 11.00 | 21.58 |
May | 701.83 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
June | 592.00 | 21.45 | 21.83 | 21.51 | 0.00 | 21.51 |
July | 591.00 | 21.34 | 50.17 | 21.50 | 0.00 | 21.50 |
August | 589.17 | 21.32 | 52.50 | 21.49 | 2.00 | 21.49 |
September | 599.50 | 21.39 | 35.00 | 21.48 | 8.67 | 21.49 |
October | 711.67 | 21.40 | 82.83 | 21.36 | 80.50 | 21.32 |
November | 716.33 | 21.25 | 248.67 | 21.17 | 248.67 | 21.13 |
December | 744.00 | 20.98 | 538.17 | 20.91 | 538.17 | 20.89 |
Annual Sum or Average | 8102.00 | 21.31 | 1515.67 | 21.27 | 1364.50 | 21.22 |
Minimum of Months | 589.17 | 20.98 | 0.00 | 20.88 | 0.00 | 20.81 |
Maximum of Months | 744.00 | 21.62 | 538.17 | 21.62 | 538.17 | 21.62 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 655.33 | 21.45 | 2.50 | 21.45 | 2.50 | 21.45 |
February | 640.50 | 21.40 | 4.33 | 21.39 | 4.33 | 21.38 |
March | 730.00 | 21.52 | 41.00 | 21.49 | 41.00 | 21.46 |
April | 692.00 | 21.61 | 7.17 | 21.61 | 7.17 | 21.60 |
May | 744.00 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
June | 675.83 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
July | 633.17 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
August | 602.17 | 21.36 | 14.50 | 21.40 | 2.17 | 21.41 |
September | 581.50 | 21.35 | 47.00 | 21.49 | 4.50 | 21.50 |
October | 648.00 | 21.45 | 21.33 | 21.51 | 0.00 | 21.51 |
November | 651.50 | 21.46 | 57.00 | 21.47 | 46.50 | 21.45 |
December | 702.00 | 21.52 | 75.17 | 21.48 | 75.17 | 21.45 |
Annual Sum or Average | 7956.00 | 21.50 | 270.00 | 21.51 | 183.33 | 21.50 |
Minimum of Months | 581.50 | 21.35 | 0.00 | 21.39 | 0.00 | 21.38 |
Maximum of Months | 744.00 | 21.70 | 75.17 | 21.70 | 75.17 | 21.70 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 602.00 | 22.61 | 26.33 | 22.66 | 6.33 | 22.66 |
February | 520.17 | 22.47 | 79.33 | 22.62 | 27.83 | 22.67 |
March | 487.17 | 22.53 | 87.17 | 22.73 | 3.83 | 22.74 |
April | 280.67 | 22.84 | 129.50 | 23.19 | 0.00 | 23.19 |
May | 173.17 | 22.86 | 178.50 | 23.43 | 0.00 | 23.43 |
June | 25.50 | 22.81 | 487.83 | 23.81 | 2.33 | 23.81 |
July | 266.17 | 23.92 | 658.67 | 23.75 | 259.83 | 23.79 |
August | 298.17 | 23.88 | 676.33 | 23.70 | 291.67 | 23.75 |
September | 242.67 | 23.83 | 637.00 | 23.69 | 235.33 | 23.72 |
October | 396.67 | 22.85 | 202.67 | 23.12 | 50.17 | 23.17 |
November | 549.67 | 22.67 | 119.83 | 22.83 | 65.50 | 22.87 |
December | 709.67 | 22.55 | 3.00 | 22.55 | 0.00 | 22.55 |
Annual Sum or Average | 4551.67 | 22.85 | 3286.17 | 23.21 | 942.83 | 23.28 |
Minimum of Months | 25.50 | 22.47 | 3.00 | 22.55 | 0.00 | 22.55 |
Maximum of Months | 709.67 | 23.92 | 676.33 | 23.81 | 291.67 | 23.81 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.17 | 22.74 | 67.00 | 22.87 | 6.50 | 22.88 |
February | 363.33 | 22.62 | 179.33 | 23.00 | 29.00 | 23.04 |
March | 348.33 | 22.69 | 182.83 | 23.10 | 4.00 | 23.11 |
April | 133.67 | 22.90 | 207.50 | 23.54 | 0.00 | 23.54 |
May | 53.17 | 22.92 | 280.00 | 23.79 | 0.00 | 23.79 |
June | 3.00 | 23.60 | 589.00 | 23.90 | 2.17 | 23.90 |
July | 254.67 | 23.98 | 683.83 | 23.85 | 254.33 | 23.88 |
August | 286.83 | 23.95 | 707.67 | 23.81 | 286.50 | 23.84 |
September | 228.50 | 23.92 | 689.17 | 23.78 | 228.33 | 23.81 |
October | 272.00 | 22.98 | 267.83 | 23.36 | 50.17 | 23.40 |
November | 437.67 | 22.89 | 170.67 | 23.11 | 66.50 | 23.15 |
December | 624.33 | 22.78 | 8.50 | 22.79 | 0.00 | 22.79 |
Annual Sum or Average | 3471.67 | 23.04 | 4033.33 | 23.45 | 927.50 | 23.50 |
Minimum of Months | 3.00 | 22.62 | 8.50 | 22.79 | 0.00 | 22.79 |
Maximum of Months | 624.33 | 23.98 | 707.67 | 23.90 | 286.50 | 23.90 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 511.83 | 24.02 | 744.00 | 24.02 | 511.83 | 24.02 |
February | 479.33 | 24.02 | 670.00 | 24.01 | 479.33 | 24.01 |
March | 519.50 | 24.01 | 743.00 | 24.00 | 519.50 | 24.01 |
April | 511.00 | 23.99 | 720.00 | 23.99 | 511.00 | 23.99 |
May | 535.17 | 23.99 | 744.00 | 23.99 | 535.17 | 23.99 |
June | 554.00 | 23.99 | 720.00 | 23.99 | 554.00 | 23.99 |
July | 691.83 | 23.99 | 744.00 | 23.99 | 691.83 | 23.99 |
August | 701.33 | 23.99 | 744.00 | 23.99 | 701.33 | 23.99 |
September | 643.00 | 23.99 | 720.00 | 23.99 | 643.00 | 23.99 |
October | 548.67 | 23.99 | 744.00 | 23.99 | 548.67 | 23.99 |
November | 519.00 | 24.00 | 719.17 | 24.00 | 519.00 | 24.00 |
December | 483.83 | 24.03 | 736.33 | 24.03 | 483.83 | 24.03 |
Annual Sum or Average | 6698.50 | 24.00 | 8748.50 | 24.00 | 6698.50 | 24.00 |
Minimum of Months | 479.33 | 23.99 | 670.00 | 23.99 | 479.33 | 23.99 |
Maximum of Months | 701.33 | 24.03 | 744.00 | 24.03 | 701.33 | 24.03 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.95 | 0.00 | 22.95 | 0.00 | 22.95 |
February | 672.00 | 22.28 | 0.00 | 22.28 | 0.00 | 22.28 |
March | 695.33 | 22.73 | 0.00 | 22.73 | 0.00 | 22.73 |
April | 459.33 | 23.77 | 0.00 | 23.77 | 0.00 | 23.77 |
May | 335.83 | 23.93 | 1.67 | 23.93 | 0.00 | 23.93 |
June | 51.00 | 24.00 | 118.33 | 24.00 | 0.00 | 24.00 |
July | 172.00 | 24.00 | 578.83 | 24.00 | 136.50 | 24.00 |
August | 177.50 | 23.99 | 633.67 | 24.00 | 153.83 | 24.00 |
September | 131.83 | 24.00 | 546.17 | 24.00 | 131.83 | 24.00 |
October | 477.17 | 23.43 | 135.00 | 23.55 | 22.67 | 23.57 |
November | 648.83 | 22.99 | 67.17 | 23.02 | 43.33 | 23.02 |
December | 744.00 | 22.24 | 10.33 | 22.22 | 10.33 | 22.20 |
Annual Sum or Average | 5308.83 | 23.02 | 2091.17 | 23.29 | 498.50 | 23.32 |
Minimum of Months | 51.00 | 22.24 | 0.00 | 22.22 | 0.00 | 22.20 |
Maximum of Months | 744.00 | 24.00 | 633.67 | 24.00 | 153.83 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.94353 | 25.93477 | 0.23523 | 6.25580 |
February | 672.00000 | 23.69164 | 39.31904 | 0.24704 | 6.43764 |
March | 744.00000 | 23.30600 | 32.15278 | 0.09647 | 5.41297 |
April | 720.00000 | 23.57952 | 23.68104 | 0.11308 | 5.45166 |
May | 744.00000 | 23.34262 | 23.44041 | -0.9299 | 23.52027 |
June | 720.00000 | 23.57551 | 33.27054 | -0.7752 | 17.94904 |
July | 744.00000 | 23.93457 | 48.74092 | -0.5128 | 10.77993 |
August | 744.00000 | 23.98856 | 51.02720 | -0.4650 | 9.64161 |
September | 720.00000 | 23.99954 | 49.79708 | -0.4495 | 9.33052 |
October | 744.00000 | 23.99956 | 30.45716 | 0.31009 | 7.19458 |
November | 720.00000 | 24.00032 | 29.95709 | 0.30398 | 7.13987 |
December | 744.00000 | 24.00237 | 18.85450 | 0.22044 | 6.04586 |
Annual Sum or Average | 8760.00000 | 23.78095 | 33.83821 | -0.1362 | 9.61854 |
Minimum of Months | 672.00000 | 23.30600 | 18.85450 | -0.9299 | 5.41297 |
Maximum of Months | 744.00000 | 24.00237 | 51.02720 | 0.31009 | 23.52027 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.22584 | 26.77659 | 0.15959 | 6.99540 |
February | 672.00000 | 22.36280 | 42.02252 | -0.0133 | 6.51507 |
March | 744.00000 | 22.74459 | 32.46445 | 0.02982 | 6.60378 |
April | 720.00000 | 23.75614 | 22.27873 | 0.27637 | 7.21082 |
May | 744.00000 | 23.90007 | 21.43200 | -0.5665 | 12.21047 |
June | 720.00000 | 23.99864 | 30.47036 | -0.4027 | 8.61191 |
July | 744.00000 | 23.99348 | 47.77055 | -0.2975 | 7.14491 |
August | 744.00000 | 23.98546 | 50.47120 | -0.2749 | 6.85654 |
September | 720.00000 | 23.98032 | 49.89393 | -0.2831 | 7.02312 |
October | 744.00000 | 23.60652 | 31.34100 | 0.31012 | 8.41407 |
November | 720.00000 | 23.19254 | 32.07843 | 0.17887 | 7.21601 |
December | 744.00000 | 22.68098 | 20.55840 | -0.0460 | 7.22955 |
Annual Sum or Average | 8760.00000 | 23.45817 | 33.90004 | -0.0782 | 7.68048 |
Minimum of Months | 672.00000 | 22.36280 | 20.55840 | -0.5665 | 6.51507 |
Maximum of Months | 744.00000 | 23.99864 | 50.47120 | 0.31012 | 12.21047 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.24254 | 27.54867 | 0.11274 | 5.60030 |
February | 672.00000 | 22.67768 | 41.76475 | 0.05414 | 5.47711 |
March | 744.00000 | 22.97170 | 32.67450 | 0.07551 | 5.71937 |
April | 720.00000 | 23.75316 | 23.16111 | 0.22986 | 6.34446 |
May | 744.00000 | 23.85137 | 22.34547 | -0.6411 | 13.85061 |
June | 720.00000 | 23.94946 | 31.70253 | -0.5165 | 10.75248 |
July | 744.00000 | 23.92799 | 48.90909 | -0.4161 | 8.86536 |
August | 744.00000 | 23.92119 | 51.64572 | -0.4007 | 8.52733 |
September | 720.00000 | 23.91150 | 51.03096 | -0.4158 | 8.78884 |
October | 744.00000 | 23.61098 | 32.26587 | 0.25160 | 6.90060 |
November | 720.00000 | 23.27772 | 32.57661 | 0.15673 | 6.03788 |
December | 744.00000 | 22.81938 | 21.24526 | -0.0403 | 5.49628 |
Annual Sum or Average | 8760.00000 | 23.49707 | 34.68280 | -0.1306 | 7.71185 |
Minimum of Months | 672.00000 | 22.67768 | 21.24526 | -0.6411 | 5.47711 |
Maximum of Months | 744.00000 | 23.94946 | 51.64572 | 0.25160 | 13.85061 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.97130 | 22.45234 | 0.84241 | 20.88001 |
February | 672.00000 | 23.95156 | 34.93887 | 0.90746 | 23.31982 |
March | 744.00000 | 23.96076 | 27.01122 | 0.87436 | 22.03822 |
April | 720.00000 | 23.99617 | 19.23266 | 0.88985 | 22.55616 |
May | 744.00000 | 24.00025 | 18.71699 | 0.29698 | 8.62301 |
June | 720.00000 | 24.00036 | 28.55863 | 0.41238 | 10.28074 |
July | 744.00000 | 24.00016 | 45.29113 | 0.50918 | 12.12273 |
August | 744.00000 | 24.00052 | 47.97319 | 0.52309 | 12.36239 |
September | 720.00000 | 24.00059 | 47.18486 | 0.49435 | 11.76809 |
October | 744.00000 | 23.98335 | 27.88242 | 0.92564 | 24.01695 |
November | 720.00000 | 23.96570 | 27.39000 | 0.87997 | 22.35717 |
December | 744.00000 | 23.97431 | 16.09548 | 0.77669 | 18.64453 |
Annual Sum or Average | 8760.00000 | 23.98394 | 30.18460 | 0.69289 | 17.37299 |
Minimum of Months | 672.00000 | 23.95156 | 16.09548 | 0.29698 | 8.62301 |
Maximum of Months | 744.00000 | 24.00059 | 47.97319 | 0.92564 | 24.01695 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.09782 | 30.23250 | 0.22051 | 7.03533 |
February | 672.00000 | 22.29523 | 45.05857 | 0.06105 | 5.90907 |
March | 744.00000 | 22.38193 | 36.05938 | 0.03752 | 5.96540 |
April | 720.00000 | 23.21826 | 26.59586 | 0.23742 | 6.92174 |
May | 744.00000 | 23.18435 | 26.04526 | -0.6892 | 15.89636 |
June | 720.00000 | 23.49931 | 35.52754 | -0.4674 | 10.32981 |
July | 744.00000 | 23.48350 | 52.99507 | -0.3597 | 8.44819 |
August | 744.00000 | 23.55822 | 55.59176 | -0.3099 | 7.70382 |
September | 720.00000 | 23.60627 | 54.68148 | -0.2982 | 7.61220 |
October | 744.00000 | 23.31439 | 35.36772 | 0.33050 | 8.59157 |
November | 720.00000 | 22.97421 | 35.66998 | 0.21752 | 7.15486 |
December | 744.00000 | 22.67601 | 23.74799 | 0.04517 | 6.44122 |
Annual Sum or Average | 8760.00000 | 23.11176 | 38.07429 | -0.0824 | 8.18781 |
Minimum of Months | 672.00000 | 22.29523 | 23.74799 | -0.6892 | 5.90907 |
Maximum of Months | 744.00000 | 23.60627 | 55.59176 | 0.33050 | 15.89636 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.49051 | 30.03350 | 0.21095 | 6.17332 |
February | 672.00000 | 22.98411 | 43.89293 | 0.15972 | 5.95737 |
March | 744.00000 | 23.13735 | 35.21961 | 0.14852 | 6.04106 |
April | 720.00000 | 23.67330 | 25.96825 | 0.25045 | 6.56846 |
May | 744.00000 | 23.71041 | 25.14268 | -0.6386 | 13.89014 |
June | 720.00000 | 23.83959 | 34.41508 | -0.4991 | 10.49760 |
July | 744.00000 | 23.83538 | 51.55809 | -0.3878 | 8.48038 |
August | 744.00000 | 23.84622 | 54.27540 | -0.3671 | 8.03335 |
September | 720.00000 | 23.86467 | 53.51918 | -0.3695 | 8.04818 |
October | 744.00000 | 23.68844 | 34.78051 | 0.31408 | 7.54067 |
November | 720.00000 | 23.46896 | 35.07007 | 0.24086 | 6.64323 |
December | 744.00000 | 23.16894 | 23.76439 | 0.07787 | 5.50756 |
Annual Sum or Average | 8760.00000 | 23.56204 | 37.24981 | -0.0733 | 7.79504 |
Minimum of Months | 672.00000 | 22.98411 | 23.76439 | -0.6386 | 5.50756 |
Maximum of Months | 744.00000 | 23.86467 | 54.27540 | 0.31408 | 13.89014 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.57479 | 31.35848 | -0.2797 | 7.52648 |
February | 672.00000 | 21.31756 | 46.20666 | -0.3104 | 7.52478 |
March | 744.00000 | 21.46127 | 36.46182 | -0.2957 | 7.56243 |
April | 720.00000 | 21.69266 | 26.04459 | -0.1858 | 6.70857 |
May | 744.00000 | 21.72173 | 24.61847 | -1.2348 | 38.18209 |
June | 720.00000 | 21.75462 | 33.15837 | -1.1007 | 32.05022 |
July | 744.00000 | 21.74254 | 45.24108 | -1.0665 | 30.52379 |
August | 744.00000 | 21.73928 | 47.56156 | -1.0589 | 30.27762 |
September | 720.00000 | 21.73226 | 48.80436 | -1.0761 | 31.02352 |
October | 744.00000 | 21.65389 | 34.70554 | -0.1770 | 6.81466 |
November | 720.00000 | 21.56102 | 36.42985 | -0.2476 | 7.26263 |
December | 744.00000 | 21.44556 | 23.69193 | -0.4070 | 9.38739 |
Annual Sum or Average | 8760.00000 | 21.61814 | 36.10879 | -0.6222 | 17.97411 |
Minimum of Months | 672.00000 | 21.31756 | 23.69193 | -1.2348 | 6.70857 |
Maximum of Months | 744.00000 | 21.75462 | 48.80436 | -0.1770 | 38.18209 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.29541 | 31.82787 | -0.4017 | 8.85005 |
February | 672.00000 | 21.08121 | 46.75580 | -0.3984 | 8.58337 |
March | 744.00000 | 21.30992 | 36.74391 | -0.3546 | 8.20247 |
April | 720.00000 | 21.67039 | 26.10071 | -0.2107 | 6.80505 |
May | 744.00000 | 21.72156 | 24.66089 | -1.2413 | 38.43965 |
June | 720.00000 | 21.75878 | 33.16989 | -1.0954 | 31.79865 |
July | 744.00000 | 21.74389 | 45.26745 | -1.0669 | 30.50581 |
August | 744.00000 | 21.73612 | 47.76422 | -1.0728 | 30.79291 |
September | 720.00000 | 21.72257 | 49.23430 | -1.1037 | 32.08526 |
October | 744.00000 | 21.54049 | 35.08270 | -0.2399 | 7.22264 |
November | 720.00000 | 21.35029 | 37.01715 | -0.3431 | 8.21121 |
December | 744.00000 | 21.08841 | 24.09927 | -0.5448 | 11.71469 |
Annual Sum or Average | 8760.00000 | 21.50368 | 36.39359 | -0.6749 | 18.67100 |
Minimum of Months | 672.00000 | 21.08121 | 24.09927 | -1.2413 | 6.80505 |
Maximum of Months | 744.00000 | 21.75878 | 49.23430 | -0.2107 | 38.43965 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.11737 | 31.35610 | -0.4710 | 9.74168 |
February | 672.00000 | 21.09706 | 45.87662 | -0.3956 | 8.41353 |
March | 744.00000 | 21.19977 | 36.15165 | -0.4063 | 8.64466 |
April | 720.00000 | 21.48431 | 25.66410 | -0.3537 | 7.96324 |
May | 744.00000 | 21.60871 | 24.19690 | -1.4372 | 47.83721 |
June | 720.00000 | 21.70418 | 33.08021 | -1.3075 | 41.34725 |
July | 744.00000 | 21.69040 | 45.86789 | -1.2447 | 38.28947 |
August | 744.00000 | 21.66469 | 48.45971 | -1.2530 | 38.66085 |
September | 720.00000 | 21.62503 | 49.76491 | -1.2725 | 39.52239 |
October | 744.00000 | 21.36471 | 34.67173 | -0.3461 | 8.00832 |
November | 720.00000 | 21.15850 | 36.43303 | -0.4219 | 9.04675 |
December | 744.00000 | 21.02790 | 23.49530 | -0.5593 | 11.67321 |
Annual Sum or Average | 8760.00000 | 21.39660 | 36.17258 | -0.7918 | 22.52188 |
Minimum of Months | 672.00000 | 21.02790 | 23.49530 | -1.4372 | 7.96324 |
Maximum of Months | 744.00000 | 21.70418 | 49.76491 | -0.3461 | 47.83721 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.63446 | 31.25468 | -0.2682 | 7.42081 |
February | 672.00000 | 21.42469 | 45.80133 | -0.2782 | 7.28548 |
March | 744.00000 | 21.57337 | 36.28124 | -0.2635 | 7.28152 |
April | 720.00000 | 21.74414 | 26.01743 | -0.1679 | 6.66305 |
May | 744.00000 | 21.75080 | 24.62934 | -1.2126 | 37.23513 |
June | 720.00000 | 21.76483 | 33.23076 | -1.0857 | 31.52206 |
July | 744.00000 | 21.75756 | 45.17721 | -1.0398 | 29.52622 |
August | 744.00000 | 21.75423 | 47.43522 | -1.0356 | 29.40388 |
September | 720.00000 | 21.74799 | 48.64402 | -1.0609 | 30.44665 |
October | 744.00000 | 21.70744 | 34.58605 | -0.1576 | 6.74613 |
November | 720.00000 | 21.60408 | 36.46420 | -0.2420 | 7.18472 |
December | 744.00000 | 21.50243 | 23.62004 | -0.3909 | 9.07656 |
Annual Sum or Average | 8760.00000 | 21.66524 | 36.01542 | -0.6025 | 17.55037 |
Minimum of Months | 672.00000 | 21.42469 | 23.62004 | -1.2126 | 6.66305 |
Maximum of Months | 744.00000 | 21.76483 | 48.64402 | -0.1576 | 37.23513 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.34716 | 31.73527 | -0.3920 | 8.56957 |
February | 672.00000 | 21.18344 | 46.39360 | -0.3654 | 8.06622 |
March | 744.00000 | 21.44213 | 36.49966 | -0.3182 | 7.71525 |
April | 720.00000 | 21.74048 | 26.04867 | -0.1885 | 6.72538 |
May | 744.00000 | 21.75070 | 24.67418 | -1.2192 | 37.49379 |
June | 720.00000 | 21.76737 | 33.25175 | -1.0811 | 31.30174 |
July | 744.00000 | 21.75797 | 45.23591 | -1.0404 | 29.51927 |
August | 744.00000 | 21.75281 | 47.59248 | -1.0491 | 29.89517 |
September | 720.00000 | 21.74416 | 48.97631 | -1.0867 | 31.42764 |
October | 744.00000 | 21.63446 | 34.83256 | -0.2121 | 6.99788 |
November | 720.00000 | 21.37334 | 37.00873 | -0.3421 | 8.06679 |
December | 744.00000 | 21.11764 | 24.03525 | -0.5337 | 11.29212 |
Annual Sum or Average | 8760.00000 | 21.55284 | 36.27493 | -0.6545 | 18.15746 |
Minimum of Months | 672.00000 | 21.11764 | 24.03525 | -1.2192 | 6.72538 |
Maximum of Months | 744.00000 | 21.76737 | 48.97631 | -0.1885 | 37.49379 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.52041 | 31.62878 | -0.3230 | 8.24099 |
February | 672.00000 | 21.23492 | 46.89655 | -0.3595 | 8.37301 |
March | 744.00000 | 21.40206 | 36.80233 | -0.3334 | 8.22738 |
April | 720.00000 | 21.67495 | 26.16814 | -0.1956 | 7.00597 |
May | 744.00000 | 21.71234 | 24.70614 | -1.2375 | 38.55623 |
June | 720.00000 | 21.75630 | 33.32988 | -1.0813 | 31.49171 |
July | 744.00000 | 21.74227 | 45.45497 | -1.0510 | 30.08707 |
August | 744.00000 | 21.73738 | 47.91423 | -1.0464 | 30.00375 |
September | 720.00000 | 21.72438 | 49.43506 | -1.0735 | 31.12320 |
October | 744.00000 | 21.61566 | 35.02499 | -0.2033 | 7.26928 |
November | 720.00000 | 21.50155 | 37.08251 | -0.2888 | 7.91675 |
December | 744.00000 | 21.37128 | 23.87537 | -0.4607 | 10.54709 |
Annual Sum or Average | 8760.00000 | 21.58476 | 36.44160 | -0.6399 | 18.30537 |
Minimum of Months | 672.00000 | 21.23492 | 23.87537 | -1.2375 | 7.00597 |
Maximum of Months | 744.00000 | 21.75630 | 49.43506 | -0.1956 | 38.55623 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.19962 | 32.20015 | -0.4602 | 9.99555 |
February | 672.00000 | 20.97515 | 47.49768 | -0.4559 | 9.73972 |
March | 744.00000 | 21.23920 | 37.11659 | -0.3973 | 9.01680 |
April | 720.00000 | 21.65347 | 26.23845 | -0.2211 | 7.10323 |
May | 744.00000 | 21.71262 | 24.76454 | -1.2439 | 38.79480 |
June | 720.00000 | 21.76081 | 33.36763 | -1.0755 | 31.22417 |
July | 744.00000 | 21.74378 | 45.47765 | -1.0513 | 30.06077 |
August | 744.00000 | 21.73357 | 48.12080 | -1.0608 | 30.51290 |
September | 720.00000 | 21.71392 | 49.90069 | -1.1018 | 32.18798 |
October | 744.00000 | 21.48595 | 35.47198 | -0.2726 | 7.82833 |
November | 720.00000 | 21.25652 | 37.71747 | -0.3972 | 9.21160 |
December | 744.00000 | 20.97600 | 24.34034 | -0.6113 | 13.42277 |
Annual Sum or Average | 8760.00000 | 21.45660 | 36.76415 | -0.6977 | 19.15921 |
Minimum of Months | 672.00000 | 20.97515 | 24.34034 | -1.2439 | 7.10323 |
Maximum of Months | 744.00000 | 21.76081 | 49.90069 | -0.2211 | 38.79480 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.67755 | 32.32711 | -0.2051 | 7.23224 |
February | 672.00000 | 21.48583 | 46.46024 | -0.2439 | 7.19632 |
March | 744.00000 | 21.55164 | 37.09940 | -0.2731 | 7.53811 |
April | 720.00000 | 21.68028 | 27.18860 | -0.2215 | 7.14276 |
May | 744.00000 | 21.70269 | 25.90124 | -1.3156 | 42.14048 |
June | 720.00000 | 21.73581 | 34.42010 | -1.1929 | 36.23377 |
July | 744.00000 | 21.73413 | 45.92095 | -1.1290 | 33.33216 |
August | 744.00000 | 21.73507 | 48.10713 | -1.1078 | 32.52191 |
September | 720.00000 | 21.73367 | 49.25524 | -1.0999 | 32.26217 |
October | 744.00000 | 21.69108 | 35.38027 | -0.1581 | 6.93893 |
November | 720.00000 | 21.63735 | 37.10116 | -0.1986 | 7.08635 |
December | 744.00000 | 21.62643 | 25.07372 | -0.2995 | 8.31243 |
Annual Sum or Average | 8760.00000 | 21.66710 | 36.94231 | -0.6229 | 19.07329 |
Minimum of Months | 672.00000 | 21.48583 | 25.07372 | -1.3156 | 6.93893 |
Maximum of Months | 744.00000 | 21.73581 | 49.25524 | -0.1581 | 42.14048 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.82841 | 30.65327 | 0.09745 | 5.81143 |
February | 672.00000 | 22.70979 | 44.11941 | 0.14645 | 6.13490 |
March | 744.00000 | 22.92243 | 35.34016 | 0.16280 | 6.25723 |
April | 720.00000 | 23.39191 | 26.51603 | 0.27262 | 6.95982 |
May | 744.00000 | 23.53417 | 25.66357 | -0.5526 | 11.91714 |
June | 720.00000 | 23.66709 | 35.25129 | -0.3932 | 8.68281 |
July | 744.00000 | 23.64666 | 52.43078 | -0.2939 | 7.30547 |
August | 744.00000 | 23.59527 | 55.38654 | -0.3034 | 7.39432 |
September | 720.00000 | 23.54711 | 54.80184 | -0.3428 | 7.99111 |
October | 744.00000 | 23.20307 | 35.74473 | 0.26766 | 7.35211 |
November | 720.00000 | 22.89767 | 35.69981 | 0.15593 | 6.38217 |
December | 744.00000 | 22.60822 | 24.03309 | -0.0207 | 5.61579 |
Annual Sum or Average | 8760.00000 | 23.21499 | 37.91844 | -0.0686 | 7.32469 |
Minimum of Months | 672.00000 | 22.60822 | 24.03309 | -0.5526 | 5.61579 |
Maximum of Months | 744.00000 | 23.66709 | 55.38654 | 0.27262 | 11.91714 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.11747 | 30.22571 | 0.18802 | 6.26590 |
February | 672.00000 | 23.05360 | 43.35045 | 0.25351 | 6.96343 |
March | 744.00000 | 23.21809 | 34.80102 | 0.25653 | 6.94812 |
April | 720.00000 | 23.58166 | 26.13899 | 0.33788 | 7.69753 |
May | 744.00000 | 23.69228 | 25.28684 | -0.4701 | 9.99266 |
June | 720.00000 | 23.80367 | 34.81590 | -0.3171 | 7.42637 |
July | 744.00000 | 23.78706 | 51.84679 | -0.2170 | 6.35033 |
August | 744.00000 | 23.74107 | 54.75882 | -0.2253 | 6.39359 |
September | 720.00000 | 23.69683 | 54.17449 | -0.2641 | 6.84165 |
October | 744.00000 | 23.41804 | 35.28085 | 0.33851 | 8.11140 |
November | 720.00000 | 23.17797 | 35.20931 | 0.24371 | 7.01684 |
December | 744.00000 | 22.95253 | 23.70585 | 0.08613 | 5.68427 |
Annual Sum or Average | 8760.00000 | 23.43843 | 37.41659 | 0.01582 | 7.14132 |
Minimum of Months | 672.00000 | 22.95253 | 23.70585 | -0.4701 | 5.68427 |
Maximum of Months | 744.00000 | 23.80367 | 54.75882 | 0.33851 | 9.99266 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.01694 | 29.25451 | 1.03475 | 29.04958 |
February | 672.00000 | 24.00549 | 41.37208 | 1.09658 | 31.64844 |
March | 744.00000 | 23.99879 | 33.55311 | 1.06890 | 30.54520 |
April | 720.00000 | 23.99121 | 25.65556 | 1.10447 | 32.33062 |
May | 744.00000 | 23.99171 | 25.07608 | 0.59602 | 16.23260 |
June | 720.00000 | 23.99260 | 34.56042 | 0.73300 | 19.85531 |
July | 744.00000 | 23.99314 | 50.94116 | 0.82436 | 22.63593 |
August | 744.00000 | 23.99325 | 53.57498 | 0.82925 | 22.78141 |
September | 720.00000 | 23.99322 | 52.84659 | 0.78976 | 21.41162 |
October | 744.00000 | 23.99191 | 34.23487 | 1.12708 | 33.33418 |
November | 720.00000 | 24.00039 | 33.96644 | 1.06892 | 30.58896 |
December | 744.00000 | 24.02741 | 23.27123 | 0.96389 | 26.15642 |
Annual Sum or Average | 8760.00000 | 23.99968 | 36.48321 | 0.93523 | 26.34122 |
Minimum of Months | 672.00000 | 23.99121 | 23.27123 | 0.59602 | 16.23260 |
Maximum of Months | 744.00000 | 24.02741 | 53.57498 | 1.12708 | 33.33418 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.54780 | 26.63316 | -0.3316 | 7.46956 |
February | 672.00000 | 21.17275 | 41.84800 | -0.3365 | 7.49521 |
March | 744.00000 | 21.53093 | 31.85723 | -0.3039 | 7.33818 |
April | 720.00000 | 22.77136 | 21.14548 | -0.0628 | 5.41891 |
May | 744.00000 | 23.25568 | 19.93947 | -0.9257 | 23.31526 |
June | 720.00000 | 23.83195 | 29.07585 | -0.6601 | 14.35455 |
July | 744.00000 | 23.78211 | 46.81394 | -0.5590 | 11.80774 |
August | 744.00000 | 23.65945 | 49.86388 | -0.5838 | 12.38551 |
September | 720.00000 | 23.49261 | 49.61838 | -0.6438 | 13.93887 |
October | 744.00000 | 22.54868 | 30.75477 | -0.0532 | 6.18519 |
November | 720.00000 | 21.70184 | 31.92795 | -0.2585 | 6.95608 |
December | 744.00000 | 21.20808 | 19.50593 | -0.4634 | 9.63466 |
Annual Sum or Average | 8760.00000 | 22.54872 | 33.18135 | -0.4329 | 10.55380 |
Minimum of Months | 672.00000 | 21.17275 | 19.50593 | -0.9257 | 5.41891 |
Maximum of Months | 744.00000 | 23.83195 | 49.86388 | -0.0532 | 23.31526 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.81244 | 29.38545 | -0.0474 | 5.32337 |
February | 672.00000 | 22.17555 | 44.00885 | -0.1139 | 5.38438 |
March | 744.00000 | 22.58941 | 34.52598 | -0.0690 | 5.46093 |
April | 720.00000 | 23.74884 | 24.50338 | 0.15339 | 5.72070 |
May | 744.00000 | 23.93874 | 23.46875 | -0.7252 | 16.13975 |
June | 720.00000 | 23.99801 | 32.41391 | -0.6259 | 13.29419 |
July | 744.00000 | 23.99543 | 49.57837 | -0.5121 | 10.67187 |
August | 744.00000 | 23.98613 | 52.39495 | -0.4979 | 10.29463 |
September | 720.00000 | 23.97999 | 51.85059 | -0.5065 | 10.47216 |
October | 744.00000 | 23.60636 | 33.41315 | 0.18179 | 6.26419 |
November | 720.00000 | 22.97824 | 34.33875 | 0.02646 | 5.39193 |
December | 744.00000 | 22.26686 | 22.87305 | -0.2215 | 6.35789 |
Annual Sum or Average | 8760.00000 | 23.34555 | 36.00076 | -0.2477 | 8.41924 |
Minimum of Months | 672.00000 | 22.17555 | 22.87305 | -0.7252 | 5.32337 |
Maximum of Months | 744.00000 | 23.99801 | 52.39495 | 0.18179 | 16.13975 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.95127 | 27.43609 | -0.0062 | 5.53814 |
February | 672.00000 | 22.28237 | 42.01900 | -0.0808 | 5.44614 |
March | 744.00000 | 22.81228 | 32.32623 | -0.0060 | 5.72361 |
April | 720.00000 | 23.85119 | 22.25882 | 0.20886 | 6.14522 |
May | 744.00000 | 23.96912 | 21.28528 | -0.6538 | 14.10091 |
June | 720.00000 | 23.99976 | 30.41694 | -0.5392 | 11.18893 |
July | 744.00000 | 23.99945 | 47.38666 | -0.4282 | 9.02849 |
August | 744.00000 | 23.99813 | 50.16860 | -0.4151 | 8.72264 |
September | 720.00000 | 23.99614 | 49.60492 | -0.4318 | 9.01567 |
October | 744.00000 | 23.62601 | 31.43988 | 0.20979 | 6.66064 |
November | 720.00000 | 23.07612 | 32.27710 | 0.05979 | 5.85338 |
December | 744.00000 | 22.23741 | 21.12866 | -0.2234 | 6.77265 |
Annual Sum or Average | 8760.00000 | 23.40550 | 33.91665 | -0.1933 | 7.86725 |
Minimum of Months | 672.00000 | 22.23741 | 21.12866 | -0.6538 | 5.44614 |
Maximum of Months | 744.00000 | 23.99976 | 50.16860 | 0.20979 | 14.10091 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.55944 | 25.21848 | -0.1187 | 5.68657 |
February | 672.00000 | 22.12661 | 39.64254 | -0.1337 | 5.62715 |
March | 744.00000 | 22.59002 | 30.02812 | -0.0793 | 5.77698 |
April | 720.00000 | 23.79597 | 19.96921 | 0.15826 | 5.77770 |
May | 744.00000 | 23.99293 | 19.07193 | -0.6897 | 15.06825 |
June | 720.00000 | 23.99999 | 28.63449 | -0.5830 | 12.22069 |
July | 744.00000 | 23.99985 | 45.94936 | -0.4700 | 9.81434 |
August | 744.00000 | 23.99761 | 48.66595 | -0.4610 | 9.56509 |
September | 720.00000 | 23.99908 | 48.05851 | -0.4739 | 9.81307 |
October | 744.00000 | 23.53256 | 29.18676 | 0.15785 | 6.30800 |
November | 720.00000 | 22.80175 | 30.06527 | -0.0259 | 5.74180 |
December | 744.00000 | 21.99669 | 18.65366 | -0.2945 | 7.25101 |
Annual Sum or Average | 8760.00000 | 23.28819 | 31.86799 | -0.2523 | 8.24037 |
Minimum of Months | 672.00000 | 21.99669 | 18.65366 | -0.6897 | 5.62715 |
Maximum of Months | 744.00000 | 23.99999 | 48.66595 | 0.15826 | 15.06825 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.669564E+11 | 125923.77 | 31-JAN-16:01 | 652.21 | 0.201367E+12 | 0.00 | 0.268323E+12 | 2.69 | 3.82 | 27-JAN-19:01 | 0.00 | 0.00 |
February | 0.202171E+11 | 74365.32 | 18-FEB-16:01 | 498.77 | 0.602194E+11 | 0.00 | 0.804364E+11 | 2.30 | 3.50 | 22-FEB-16:01 | 0.00 | 0.00 |
March | 0.634706E+11 | 120703.28 | 16-MAR-15:02 | 627.39 | 0.186606E+12 | 0.00 | 0.250076E+12 | 2.55 | 3.85 | 05-MAR-19:03 | 0.00 | 0.00 |
April | 0.168650E+12 | 163857.71 | 14-APR-18:03 | 718.42 | 0.506347E+12 | 0.00 | 0.674997E+12 | 3.00 | 3.84 | 26-APR-18:03 | 0.00 | 0.00 |
May | 0.219507E+12 | 177055.39 | 31-MAY-18:03 | 744.00 | 0.646282E+12 | 0.00 | 0.865789E+12 | 2.94 | 3.74 | 22-MAY-08:62 | 0.00 | 0.00 |
June | 0.294511E+12 | 219466.45 | 28-JUN-18:06 | 720.00 | 0.832812E+12 | 0.00 | 0.112732E+13 | 2.87 | 3.59 | 13-JUN-08:61 | 0.00 | 0.00 |
July | 0.313251E+12 | 205244.16 | 20-JUL-18:03 | 744.00 | 0.944965E+12 | 0.00 | 0.125822E+13 | 3.04 | 4.02 | 14-JUL-01:00 | 0.00 | 0.00 |
August | 0.304193E+12 | 211530.24 | 25-AUG-18:03 | 744.00 | 0.921148E+12 | 0.00 | 0.122534E+13 | 3.06 | 4.14 | 28-AUG-17:00 | 0.00 | 0.00 |
September | 0.267705E+12 | 194294.43 | 08-SEP-18:03 | 720.00 | 0.842070E+12 | 0.00 | 0.110978E+13 | 3.15 | 4.31 | 03-SEP-08:62 | 0.00 | 0.00 |
October | 0.148991E+12 | 173301.72 | 02-OCT-18:03 | 717.08 | 0.456689E+12 | 0.00 | 0.605680E+12 | 2.95 | 3.88 | 23-OCT-18:01 | 0.00 | 0.00 |
November | 0.716623E+11 | 124628.16 | 01-NOV-15:02 | 644.07 | 0.217265E+12 | 0.00 | 0.288927E+12 | 2.75 | 4.16 | 11-NOV-19:03 | 0.00 | 0.00 |
December | 0.394144E+11 | 105059.33 | 25-DEC-16:02 | 568.52 | 0.117280E+12 | 0.00 | 0.156695E+12 | 2.36 | 3.65 | 24-DEC-16:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.197853E+13 | 8098.46 | 0.593305E+13 | 0.00 | 0.791158E+13 | 2.81 | 0.00 | 0.00 | ||||
Minimum of Months | 0.202171E+11 | 74365.32 | 498.77 | 0.602194E+11 | 0.00 | 0.804364E+11 | 2.30 | 3.50 | 0.00 | 0.00 | ||
Maximum of Months | 0.313251E+12 | 219466.45 | 744.00 | 0.944965E+12 | 0.00 | 0.125822E+13 | 3.15 | 4.31 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.242358E+11 | 0.00 | 446.59 | 125985.40 | 01-JAN-23:25 | 0.00 | 57.58 | 71.57 | 0.08 | 0.00 | 0.03 | 0.36 | 01-JAN-23:25 |
February | 0.247348E+11 | 0.00 | 564.54 | 116799.26 | 02-FEB-03:40 | 0.00 | 57.46 | 75.94 | 0.10 | 0.00 | 0.03 | 0.33 | 02-FEB-03:40 |
March | 0.177589E+11 | 0.00 | 407.01 | 121354.52 | 30-MAR-06:32 | 0.00 | 52.79 | 66.71 | 0.06 | 0.00 | 0.02 | 0.34 | 30-MAR-06:32 |
April | 0.726025E+09 | 0.00 | 48.96 | 91916.92 | 21-APR-03:56 | 0.00 | 48.34 | 50.38 | 0.00 | 0.00 | 0.00 | 0.26 | 21-APR-03:56 |
May | 0.168802E+09 | 0.00 | 7.57 | 43121.14 | 15-MAY-08:04 | 0.00 | 54.42 | 54.70 | 0.00 | 0.00 | 0.00 | 0.12 | 15-MAY-08:04 |
June | 25873005.41 | 0.00 | 0.99 | 12704.33 | 30-JUN-08:06 | 0.00 | 58.90 | 58.93 | 0.00 | 0.00 | 0.00 | 0.04 | 30-JUN-08:06 |
July | 29301677.67 | 0.00 | 1.43 | 24925.24 | 27-JUL-08:05 | 0.00 | 60.15 | 60.19 | 0.00 | 0.00 | 0.00 | 0.07 | 27-JUL-08:05 |
August | 38462967.23 | 0.00 | 1.53 | 29949.04 | 24-AUG-08:04 | 0.00 | 59.96 | 60.00 | 0.00 | 0.00 | 0.00 | 0.08 | 24-AUG-08:04 |
September | 59472129.31 | 0.00 | 1.92 | 29736.66 | 29-SEP-08:04 | 0.00 | 59.13 | 59.18 | 0.00 | 0.00 | 0.00 | 0.08 | 29-SEP-08:04 |
October | 0.532236E+10 | 0.00 | 163.28 | 113264.46 | 25-OCT-06:30 | 0.00 | 56.79 | 62.21 | 0.02 | 0.00 | 0.01 | 0.32 | 25-OCT-06:30 |
November | 0.151051E+11 | 0.00 | 382.27 | 122727.45 | 18-NOV-06:02 | 0.00 | 56.98 | 69.02 | 0.05 | 0.00 | 0.02 | 0.35 | 18-NOV-06:02 |
December | 0.367170E+11 | 0.00 | 611.53 | 155439.89 | 17-DEC-09:01 | 0.00 | 57.57 | 76.29 | 0.13 | 0.00 | 0.04 | 0.44 | 17-DEC-09:01 |
Annual Sum or Average | 0.124922E+12 | 0.00 | 2637.63 | 0.00 | 56.68 | 63.71 | 0.04 | 0.00 | 0.01 | ||||
Minimum of Months | 25873005.41 | 0.00 | 0.99 | 12704.33 | 0.00 | 48.34 | 50.38 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.367170E+11 | 0.00 | 611.53 | 155439.89 | 0.00 | 60.15 | 76.29 | 0.13 | 0.00 | 0.04 | 0.44 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.111591E+12 | 0.00 | 402.02 | 0.111136E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 182073.33 | 31-JAN-16:40 | 182073.33 | 31-JAN-16:40 | 0.00 | 0.00 | 0.00 |
February | 0.273384E+11 | 0.00 | 242.29 | 0.273197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112153.73 | 18-FEB-14:00 | 112153.73 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.119887E+12 | 0.00 | 443.40 | 0.119887E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 199609.91 | 20-MAR-18:10 | 199609.91 | 20-MAR-18:10 | 0.00 | 0.00 | 0.00 |
April | 0.327386E+12 | 0.00 | 665.28 | 0.327386E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 268555.58 | 14-APR-20:10 | 268555.58 | 14-APR-20:10 | 0.00 | 0.00 | 0.00 |
May | 0.425765E+12 | 0.00 | 735.42 | 0.425765E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 280605.53 | 31-MAY-18:05 | 280605.53 | 31-MAY-18:05 | 0.00 | 0.00 | 0.00 |
June | 0.544608E+12 | 0.00 | 720.00 | 0.543691E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 350196.78 | 17-JUN-17:17 | 332997.86 | 28-JUN-18:17 | 0.00 | 0.00 | 0.00 |
July | 0.633802E+12 | 0.00 | 744.00 | 0.555481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 421126.12 | 13-JUL-21:00 | 331148.69 | 21-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.616988E+12 | 0.00 | 744.00 | 0.546295E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 452169.98 | 18-AUG-22:00 | 320731.92 | 15-AUG-19:20 | 0.00 | 0.00 | 0.00 |
September | 0.565901E+12 | 0.00 | 720.00 | 0.489402E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 482812.48 | 10-SEP-19:20 | 315081.08 | 08-SEP-20:10 | 0.00 | 0.00 | 0.00 |
October | 0.290091E+12 | 0.00 | 613.68 | 0.281960E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 347052.84 | 02-OCT-20:00 | 283415.26 | 03-OCT-20:10 | 0.00 | 0.00 | 0.00 |
November | 0.128100E+12 | 0.00 | 433.91 | 0.113732E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 207086.46 | 01-NOV-18:04 | 207086.46 | 01-NOV-18:04 | 0.00 | 0.00 | 0.00 |
December | 0.605304E+11 | 0.00 | 316.92 | 0.605304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162336.27 | 25-DEC-13:00 | 162336.27 | 25-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.385199E+13 | 0.00 | 6780.92 | 0.360258E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.273384E+11 | 0.00 | 242.29 | 0.273197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112153.73 | 112153.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.633802E+12 | 0.00 | 744.00 | 0.555481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 482812.48 | 332997.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.198588E+11 | 0.00 | 362.42 | 0.197255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28113.38 | 31-JAN-16:01 | 28113.38 | 31-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.520638E+10 | 0.00 | 212.17 | 0.520638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23245.80 | 18-FEB-14:00 | 23245.80 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.212817E+11 | 0.00 | 408.00 | 0.212817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28620.15 | 16-MAR-15:02 | 28620.15 | 16-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.506605E+11 | 0.00 | 662.50 | 0.506605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32711.12 | 14-APR-15:00 | 32711.12 | 14-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.642412E+11 | 0.00 | 735.50 | 0.642412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33351.04 | 31-MAY-17:40 | 33351.04 | 31-MAY-17:40 | 0.00 | 0.00 | 0.00 |
June | 0.748094E+11 | 0.00 | 720.00 | 0.747128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41459.59 | 17-JUN-16:00 | 36620.64 | 28-JUN-17:20 | 0.00 | 0.00 | 0.00 |
July | 0.886398E+11 | 0.00 | 744.00 | 0.766701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50861.44 | 13-JUL-18:02 | 36037.45 | 19-JUL-14:00 | 0.00 | 0.00 | 0.00 |
August | 0.877525E+11 | 0.00 | 744.00 | 0.756168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53667.54 | 05-AUG-08:00 | 36153.45 | 25-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.820432E+11 | 0.00 | 720.00 | 0.691968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57485.13 | 04-SEP-08:61 | 34872.36 | 08-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.443045E+11 | 0.00 | 603.18 | 0.428084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45579.85 | 03-OCT-05:00 | 34109.33 | 01-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.227731E+11 | 0.00 | 407.33 | 0.196436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43952.06 | 12-NOV-14:30 | 28787.30 | 01-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.111635E+11 | 0.00 | 250.39 | 0.111635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26310.78 | 25-DEC-16:00 | 26310.78 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.572735E+12 | 0.00 | 6569.49 | 0.530927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.520638E+10 | 0.00 | 212.17 | 0.520638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23245.80 | 23245.80 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.886398E+11 | 0.00 | 744.00 | 0.766701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57485.13 | 36620.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.318585E+10 | 0.00 | 439.11 | 0.305643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16162.35 | 14-JAN-16:02 | 16162.35 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.997826E+09 | 0.00 | 203.62 | 0.835567E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15395.95 | 22-FEB-16:01 | 15395.95 | 22-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.245727E+10 | 0.00 | 384.17 | 0.215335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16192.18 | 18-MAR-15:02 | 16192.18 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.845913E+10 | 0.00 | 663.89 | 0.832734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16191.97 | 25-APR-18:01 | 16191.97 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.101774E+11 | 0.00 | 701.03 | 0.101331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16181.57 | 10-MAY-18:01 | 16181.57 | 10-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.134518E+11 | 0.00 | 696.14 | 0.128553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16196.63 | 01-JUN-18:02 | 16196.63 | 01-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.132264E+11 | 0.00 | 715.00 | 0.973688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17469.17 | 15-JUL-08:61 | 16185.87 | 03-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.129985E+11 | 0.00 | 711.65 | 0.931959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17650.86 | 05-AUG-08:61 | 16197.08 | 27-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.112370E+11 | 0.00 | 682.54 | 0.768271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18370.54 | 04-SEP-08:61 | 16196.29 | 27-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.685331E+10 | 0.00 | 604.42 | 0.574901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16769.37 | 03-OCT-08:62 | 16189.99 | 20-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.329720E+10 | 0.00 | 458.99 | 0.272583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16417.51 | 13-NOV-16:01 | 16172.89 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.148865E+10 | 0.00 | 267.88 | 0.148737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16058.86 | 25-DEC-16:02 | 16058.86 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.878304E+11 | 0.00 | 6528.44 | 0.740625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.997826E+09 | 0.00 | 203.62 | 0.835567E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15395.95 | 15395.95 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.134518E+11 | 0.00 | 715.00 | 0.128553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18370.54 | 16197.08 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.121057E+10 | 0.00 | 232.59 | 0.117117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16047.37 | 14-JAN-16:02 | 16047.37 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.352383E+09 | 0.00 | 92.24 | 0.311162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15286.06 | 22-FEB-16:01 | 15286.06 | 22-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.164078E+10 | 0.00 | 300.19 | 0.145187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16076.28 | 18-MAR-15:02 | 16076.28 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.739021E+10 | 0.00 | 641.25 | 0.726509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16077.28 | 25-APR-18:01 | 16077.28 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.989788E+10 | 0.00 | 699.40 | 0.985382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16066.97 | 18-MAY-08:61 | 16066.97 | 18-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.136168E+11 | 0.00 | 697.75 | 0.130270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16082.16 | 25-JUN-08:61 | 16082.16 | 25-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.131743E+11 | 0.00 | 715.99 | 0.971880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17168.74 | 15-JUL-08:61 | 16071.16 | 03-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.123447E+11 | 0.00 | 709.18 | 0.870720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17735.72 | 28-AUG-18:02 | 16082.06 | 27-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.100701E+11 | 0.00 | 674.97 | 0.660706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18043.92 | 04-SEP-08:61 | 16081.49 | 27-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.496514E+10 | 0.00 | 522.54 | 0.396807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16631.64 | 03-OCT-08:62 | 16074.12 | 20-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.153138E+10 | 0.00 | 303.70 | 0.115898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16476.42 | 13-NOV-16:01 | 16057.95 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.386656E+09 | 0.00 | 90.07 | 0.386643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15945.23 | 25-DEC-16:02 | 15945.23 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.765810E+11 | 0.00 | 5679.86 | 0.636268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.352383E+09 | 0.00 | 90.07 | 0.311162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15286.06 | 15286.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.136168E+11 | 0.00 | 715.99 | 0.130270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18043.92 | 16082.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.330584E+11 | 0.00 | 471.88 | 0.327276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45145.39 | 14-JAN-13:50 | 45145.39 | 14-JAN-13:50 | 0.00 | 0.00 | 0.00 |
February | 0.834135E+10 | 0.00 | 193.49 | 0.795809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35316.13 | 01-FEB-15:30 | 35316.13 | 01-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 0.808011E+10 | 0.00 | 234.84 | 0.777595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30489.27 | 18-MAR-13:50 | 30453.73 | 18-MAR-14:30 | 0.00 | 0.00 | 0.00 |
April | 0.290360E+11 | 0.00 | 557.21 | 0.290317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32671.32 | 14-APR-13:40 | 32671.32 | 14-APR-13:40 | 0.00 | 0.00 | 0.00 |
May | 0.290738E+11 | 0.00 | 617.08 | 0.290738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25700.43 | 09-MAY-17:12 | 25700.43 | 09-MAY-17:12 | 0.00 | 0.00 | 0.00 |
June | 0.436688E+11 | 0.00 | 711.58 | 0.417766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34698.02 | 17-JUN-18:00 | 33176.85 | 28-JUN-19:10 | 0.00 | 0.00 | 0.00 |
July | 0.464737E+11 | 0.00 | 731.33 | 0.291904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33471.84 | 21-JUL-20:20 | 28731.16 | 07-JUL-17:13 | 0.00 | 0.00 | 0.00 |
August | 0.496870E+11 | 0.00 | 725.56 | 0.318723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42003.96 | 28-AUG-12:40 | 39197.27 | 27-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.496719E+11 | 0.00 | 698.08 | 0.341505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45063.74 | 28-SEP-13:40 | 45063.74 | 28-SEP-13:40 | 0.00 | 0.00 | 0.00 |
October | 0.389375E+11 | 0.00 | 582.69 | 0.339561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46300.43 | 18-OCT-13:50 | 46300.43 | 18-OCT-13:50 | 0.00 | 0.00 | 0.00 |
November | 0.264395E+11 | 0.00 | 420.06 | 0.246681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47994.99 | 20-NOV-14:30 | 47994.99 | 20-NOV-14:30 | 0.00 | 0.00 | 0.00 |
December | 0.225500E+11 | 0.00 | 382.40 | 0.225317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44726.61 | 25-DEC-13:40 | 44726.61 | 25-DEC-13:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.385018E+12 | 0.00 | 6326.22 | 0.324713E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.808011E+10 | 0.00 | 193.49 | 0.777595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25700.43 | 25700.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.496870E+11 | 0.00 | 731.33 | 0.417766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47994.99 | 47994.99 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.569310E+10 | 0.00 | 282.58 | 0.518570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87479.22 | 27-JAN-16:01 | 87479.22 | 27-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.398629E+10 | 0.00 | 240.95 | 0.202577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79923.10 | 18-FEB-09:02 | 73396.67 | 20-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.117544E+11 | 0.00 | 377.26 | 0.986548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93212.72 | 15-MAR-18:01 | 93212.72 | 15-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.367336E+11 | 0.00 | 517.49 | 0.360688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96908.64 | 25-APR-18:01 | 96908.64 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.525062E+11 | 0.00 | 575.77 | 0.522484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96843.06 | 10-MAY-18:01 | 96843.06 | 10-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.744244E+11 | 0.00 | 640.33 | 0.712008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96947.28 | 03-JUN-08:61 | 96947.28 | 03-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.787533E+11 | 0.00 | 649.37 | 0.598968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97419.23 | 09-JUL-08:61 | 96867.89 | 03-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.715695E+11 | 0.00 | 626.73 | 0.514060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112511.59 | 28-AUG-18:02 | 96944.18 | 27-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.607458E+11 | 0.00 | 574.82 | 0.411093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105034.57 | 04-SEP-08:61 | 96941.86 | 30-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.285439E+11 | 0.00 | 493.71 | 0.230561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96941.78 | 05-OCT-18:01 | 96941.78 | 05-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.893234E+10 | 0.00 | 334.45 | 0.574244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88218.44 | 20-NOV-16:01 | 88218.44 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.212456E+10 | 0.00 | 142.28 | 0.210124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78586.50 | 23-DEC-09:02 | 78586.50 | 23-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.435767E+12 | 0.00 | 5455.74 | 0.359907E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.212456E+10 | 0.00 | 142.28 | 0.202577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78586.50 | 73396.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.787533E+11 | 0.00 | 649.37 | 0.712008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112511.59 | 96947.28 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.300043E+10 | 0.00 | 447.79 | 0.287421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14127.94 | 14-JAN-16:02 | 14127.94 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.119198E+10 | 0.00 | 241.92 | 0.944717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13457.26 | 22-FEB-16:01 | 13457.26 | 22-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.256296E+10 | 0.00 | 424.60 | 0.222209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14154.34 | 18-MAR-15:02 | 14154.34 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.856871E+10 | 0.00 | 693.39 | 0.844488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14154.55 | 25-APR-18:01 | 14154.55 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.105066E+11 | 0.00 | 728.03 | 0.104674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14144.93 | 18-MAY-08:61 | 14144.93 | 18-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.137799E+11 | 0.00 | 711.26 | 0.133100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14158.39 | 01-JUN-18:02 | 14158.39 | 01-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.141206E+11 | 0.00 | 731.49 | 0.108024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14559.61 | 09-JUL-08:61 | 14149.33 | 03-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.137421E+11 | 0.00 | 727.71 | 0.102492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15244.45 | 04-AUG-08:62 | 14158.23 | 27-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.116497E+11 | 0.00 | 698.20 | 0.823825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15338.04 | 03-SEP-15:02 | 14157.43 | 27-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.712733E+10 | 0.00 | 636.29 | 0.606386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14158.70 | 05-OCT-18:01 | 14158.70 | 05-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.301200E+10 | 0.00 | 455.22 | 0.253165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14137.30 | 20-NOV-16:01 | 14137.30 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.150789E+10 | 0.00 | 274.17 | 0.150014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14037.71 | 25-DEC-16:02 | 14037.71 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.907702E+11 | 0.00 | 6770.07 | 0.776487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.119198E+10 | 0.00 | 241.92 | 0.944717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13457.26 | 13457.26 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.141206E+11 | 0.00 | 731.49 | 0.133100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15338.04 | 14158.70 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.980001E+09 | 0.00 | 232.43 | 0.912336E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14024.96 | 31-JAN-16:01 | 14024.96 | 31-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.416123E+09 | 0.00 | 123.27 | 0.271522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12502.41 | 22-FEB-16:01 | 12502.41 | 22-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.167905E+10 | 0.00 | 339.60 | 0.142803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14055.31 | 18-MAR-15:02 | 14055.31 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.745111E+10 | 0.00 | 685.29 | 0.732987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14056.83 | 25-APR-18:01 | 14056.83 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.102191E+11 | 0.00 | 728.00 | 0.101800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14047.43 | 18-MAY-08:61 | 14047.43 | 18-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.139427E+11 | 0.00 | 711.47 | 0.134842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14061.39 | 20-JUN-18:02 | 14061.39 | 20-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.140619E+11 | 0.00 | 731.61 | 0.107524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14407.84 | 09-JUL-08:61 | 14052.39 | 03-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.130875E+11 | 0.00 | 727.01 | 0.955559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15424.95 | 28-AUG-18:02 | 14060.64 | 27-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.104763E+11 | 0.00 | 695.19 | 0.707363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15382.60 | 03-SEP-15:02 | 14059.84 | 27-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.513203E+10 | 0.00 | 555.05 | 0.413438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14061.32 | 05-OCT-18:01 | 14061.32 | 05-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.126828E+10 | 0.00 | 285.22 | 0.963572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14039.10 | 20-NOV-16:01 | 14039.10 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.326451E+09 | 0.00 | 103.70 | 0.324345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13392.13 | 25-DEC-16:02 | 13392.13 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.790405E+11 | 0.00 | 5917.84 | 0.664100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.326451E+09 | 0.00 | 103.70 | 0.271522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12502.41 | 12502.41 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.140619E+11 | 0.00 | 731.61 | 0.134842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15424.95 | 14061.39 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.668588E+09 | 0.00 | 341.58 | 0.651825E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4291.11 | 14-JAN-16:02 | 4291.11 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.197808E+09 | 0.00 | 138.13 | 0.174850E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4087.64 | 22-FEB-16:01 | 4087.64 | 22-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.532917E+09 | 0.00 | 304.92 | 0.474895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4299.10 | 18-MAR-15:02 | 4299.10 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.206197E+10 | 0.00 | 645.39 | 0.202866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4298.94 | 25-APR-18:01 | 4298.94 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.254770E+10 | 0.00 | 696.85 | 0.253538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4296.15 | 10-MAY-18:01 | 4296.15 | 10-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.353714E+10 | 0.00 | 696.31 | 0.337068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4300.31 | 23-JUN-08:61 | 4300.31 | 23-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.345025E+10 | 0.00 | 715.48 | 0.252889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4763.26 | 15-JUL-08:61 | 4297.26 | 03-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.336392E+10 | 0.00 | 710.61 | 0.240055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4821.78 | 05-AUG-08:61 | 4300.33 | 27-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.282153E+10 | 0.00 | 679.12 | 0.189386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5061.59 | 04-SEP-08:61 | 4300.13 | 27-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.157760E+10 | 0.00 | 548.50 | 0.130245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4608.30 | 03-OCT-08:62 | 4298.16 | 20-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.672990E+09 | 0.00 | 358.98 | 0.566229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4399.61 | 13-NOV-16:01 | 4293.88 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.301949E+09 | 0.00 | 191.76 | 0.301949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4263.62 | 25-DEC-16:02 | 4263.62 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217344E+11 | 0.00 | 6027.62 | 0.182302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.197808E+09 | 0.00 | 138.13 | 0.174850E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4087.64 | 4087.64 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.353714E+10 | 0.00 | 715.48 | 0.337068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5061.59 | 4300.33 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.224364E+09 | 0.00 | 150.17 | 0.222246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4257.25 | 14-JAN-16:02 | 4257.25 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 65767917.60 | 0.00 | 48.63 | 60179316.31 | 0.00 | 0.00 | 0.00 | 0.00 | 4055.27 | 22-FEB-16:01 | 4055.27 | 22-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.342457E+09 | 0.00 | 220.95 | 0.307900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4265.22 | 18-MAR-15:02 | 4265.22 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.178731E+10 | 0.00 | 621.50 | 0.175653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4265.25 | 25-APR-18:01 | 4265.25 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.247560E+10 | 0.00 | 696.03 | 0.246332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4262.50 | 08-MAY-08:61 | 4262.50 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.357859E+10 | 0.00 | 698.34 | 0.341114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4266.67 | 23-JUN-08:61 | 4266.67 | 23-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.343686E+10 | 0.00 | 716.10 | 0.252138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4679.31 | 15-JUL-08:61 | 4263.57 | 03-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.319431E+10 | 0.00 | 708.60 | 0.223722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4810.03 | 28-AUG-18:02 | 4266.55 | 27-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.251876E+10 | 0.00 | 672.69 | 0.161683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4959.40 | 04-SEP-08:61 | 4266.42 | 27-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.111220E+10 | 0.00 | 461.44 | 0.864799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4539.69 | 03-OCT-08:62 | 4264.46 | 20-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.275237E+09 | 0.00 | 193.65 | 0.216389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4321.42 | 13-NOV-16:01 | 4260.15 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 71618469.97 | 0.00 | 51.48 | 71586019.37 | 0.00 | 0.00 | 0.00 | 0.00 | 4230.17 | 25-DEC-16:02 | 4230.17 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190831E+11 | 0.00 | 5239.57 | 0.157495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 65767917.60 | 0.00 | 48.63 | 60179316.31 | 0.00 | 0.00 | 0.00 | 0.00 | 4055.27 | 4055.27 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.357859E+10 | 0.00 | 716.10 | 0.341114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4959.40 | 4266.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.921552E+10 | 0.00 | 584.43 | 0.890466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18831.10 | 14-JAN-16:02 | 18831.10 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.354369E+10 | 0.00 | 358.02 | 0.294074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17934.76 | 22-FEB-16:01 | 17934.76 | 22-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.438053E+10 | 0.00 | 457.67 | 0.383740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18863.86 | 18-MAR-15:02 | 18863.86 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.101656E+11 | 0.00 | 657.34 | 0.998560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18864.30 | 25-APR-18:01 | 18864.30 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.108225E+11 | 0.00 | 689.58 | 0.107603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18851.84 | 10-MAY-18:01 | 18851.84 | 10-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.146313E+11 | 0.00 | 685.06 | 0.137855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18866.69 | 19-JUN-15:02 | 18866.69 | 19-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.160928E+11 | 0.00 | 706.93 | 0.118393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20104.31 | 15-JUL-08:61 | 18856.58 | 03-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.166863E+11 | 0.00 | 705.51 | 0.121795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21028.35 | 05-AUG-08:61 | 18862.52 | 23-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.159186E+11 | 0.00 | 680.51 | 0.114454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21845.36 | 04-SEP-08:61 | 18864.33 | 18-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.117827E+11 | 0.00 | 649.45 | 0.103328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19575.81 | 03-OCT-08:62 | 18859.82 | 20-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.807520E+10 | 0.00 | 547.84 | 0.720237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18974.70 | 13-NOV-16:01 | 18841.72 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.660210E+10 | 0.00 | 465.82 | 0.658636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18708.77 | 25-DEC-16:02 | 18708.77 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127917E+12 | 0.00 | 7188.16 | 0.109800E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.354369E+10 | 0.00 | 358.02 | 0.294074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17934.76 | 17934.76 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.166863E+11 | 0.00 | 706.93 | 0.137855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21845.36 | 18866.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 835.71 | 667.64 | 168.07 | 1276.01 | 426.31 | 0.00 | 0.00 | 0.00 |
February | 521.47 | 349.59 | 171.87 | 718.49 | 395.83 | 0.00 | 0.00 | 0.00 |
March | 431.69 | 218.75 | 212.94 | 643.10 | 364.13 | 0.00 | 0.00 | 0.00 |
April | 378.88 | 156.07 | 222.81 | 719.38 | 210.12 | 0.00 | 0.00 | 0.00 |
May | 253.16 | 44.04 | 209.12 | 533.08 | 143.32 | 0.00 | 0.00 | 0.00 |
June | 214.28 | 16.35 | 197.94 | 609.65 | 53.83 | 0.00 | 0.00 | 0.00 |
July | 217.14 | 20.65 | 196.50 | 600.49 | 36.59 | 0.00 | 0.00 | 0.00 |
August | 268.51 | 75.62 | 192.88 | 690.12 | 49.17 | 0.00 | 0.00 | 0.00 |
September | 381.40 | 161.20 | 220.20 | 821.64 | 74.33 | 0.00 | 0.00 | 0.00 |
October | 612.22 | 423.82 | 188.40 | 1034.49 | 257.77 | 0.00 | 0.00 | 0.00 |
November | 719.63 | 552.71 | 166.92 | 1086.76 | 382.77 | 0.00 | 0.00 | 0.00 |
December | 778.28 | 616.61 | 161.67 | 1138.32 | 499.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 467.74 | 275.23 | 192.51 | 823.63 | 240.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 214.28 | 16.35 | 161.67 | 533.08 | 36.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 835.71 | 667.64 | 222.81 | 1276.01 | 499.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2353.32 | 1880.03 | 473.29 | 3585.48 | 1203.61 | 0.00 | 0.00 | 0.00 |
February | 1468.41 | 984.43 | 483.99 | 2025.34 | 1139.06 | 0.00 | 0.00 | 0.00 |
March | 1215.60 | 615.98 | 599.62 | 1832.76 | 1026.40 | 0.00 | 0.00 | 0.00 |
April | 1066.89 | 439.48 | 627.41 | 2061.23 | 568.43 | 0.00 | 0.00 | 0.00 |
May | 712.87 | 124.01 | 588.87 | 1562.17 | 379.49 | 0.00 | 0.00 | 0.00 |
June | 603.41 | 46.04 | 557.38 | 1770.51 | 140.92 | 0.00 | 0.00 | 0.00 |
July | 611.46 | 58.14 | 553.32 | 1742.21 | 95.42 | 0.00 | 0.00 | 0.00 |
August | 756.09 | 212.94 | 543.15 | 1979.59 | 129.26 | 0.00 | 0.00 | 0.00 |
September | 1074.00 | 453.93 | 620.07 | 2339.01 | 200.25 | 0.00 | 0.00 | 0.00 |
October | 1723.96 | 1193.45 | 530.51 | 2921.62 | 717.07 | 0.00 | 0.00 | 0.00 |
November | 2026.44 | 1556.40 | 470.05 | 3059.54 | 1074.73 | 0.00 | 0.00 | 0.00 |
December | 2191.58 | 1736.32 | 455.26 | 3195.22 | 1426.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1317.12 | 775.03 | 542.09 | 2342.49 | 673.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 603.41 | 46.04 | 455.26 | 1562.17 | 95.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2353.32 | 1880.03 | 627.41 | 3585.48 | 1426.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3057.09 | 2442.27 | 614.83 | 4751.38 | 1620.60 | 0.00 | 0.00 | 0.00 |
February | 1907.55 | 1278.83 | 628.73 | 2671.17 | 1588.07 | 0.00 | 0.00 | 0.00 |
March | 1579.13 | 800.19 | 778.94 | 2402.49 | 1433.41 | 0.00 | 0.00 | 0.00 |
April | 1385.95 | 570.91 | 815.04 | 2724.71 | 776.76 | 0.00 | 0.00 | 0.00 |
May | 926.06 | 161.09 | 764.97 | 2043.78 | 522.50 | 0.00 | 0.00 | 0.00 |
June | 783.87 | 59.80 | 724.06 | 2338.83 | 187.51 | 0.00 | 0.00 | 0.00 |
July | 794.32 | 75.52 | 718.79 | 2299.19 | 127.86 | 0.00 | 0.00 | 0.00 |
August | 982.21 | 276.63 | 705.58 | 2625.78 | 171.08 | 0.00 | 0.00 | 0.00 |
September | 1395.19 | 589.68 | 805.51 | 3102.36 | 261.25 | 0.00 | 0.00 | 0.00 |
October | 2239.52 | 1550.35 | 689.17 | 3869.43 | 967.52 | 0.00 | 0.00 | 0.00 |
November | 2632.46 | 2021.85 | 610.62 | 4046.92 | 1463.18 | 0.00 | 0.00 | 0.00 |
December | 2846.99 | 2255.58 | 591.41 | 4229.41 | 1937.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1711.02 | 1006.81 | 704.21 | 3096.01 | 918.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 783.87 | 59.80 | 591.41 | 2043.78 | 127.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3057.09 | 2442.27 | 815.04 | 4751.38 | 1937.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 259.33 | 75.11 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 146.32 | 72.80 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 131.80 | 66.02 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 151.50 | 30.93 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 118.34 | 18.52 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 140.89 | 4.82 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 140.60 | 3.01 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 155.54 | 3.40 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 178.55 | 5.92 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 213.62 | 40.43 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 221.08 | 66.47 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 231.90 | 92.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 174.37 | 39.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 118.34 | 3.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 259.33 | 92.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 186.40 | 154.76 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 122.78 | 147.19 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 192.91 | 125.93 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 374.47 | 57.45 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 408.23 | 34.26 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 504.17 | 8.71 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 396.71 | 5.50 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 370.71 | 6.23 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 306.11 | 11.15 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 239.24 | 80.83 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 183.24 | 136.19 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 132.74 | 191.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 285.51 | 79.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 122.78 | 5.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 504.17 | 191.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 19.36 | 80.48 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 13.68 | 78.01 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 33.58 | 67.93 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 71.66 | 29.36 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 99.76 | 16.45 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 154.97 | 4.23 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 138.91 | 2.70 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 114.33 | 3.17 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 95.32 | 5.80 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 45.84 | 42.55 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 19.87 | 71.42 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 12.25 | 100.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 68.56 | 41.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 12.25 | 2.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 154.97 | 100.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 194.39 | 149.24 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 128.20 | 142.94 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 197.47 | 123.75 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 376.99 | 56.61 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 408.82 | 34.10 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 503.81 | 8.72 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 396.84 | 5.50 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 372.08 | 6.11 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 308.67 | 10.78 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 244.58 | 78.37 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 189.68 | 131.66 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 140.72 | 185.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 289.22 | 77.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 128.20 | 5.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 503.81 | 185.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.16 | 105.58 | 26.58 | 202.79 | 69.91 | 0.00 | 0.00 | 0.00 |
February | 82.47 | 55.29 | 27.18 | 113.08 | 67.07 | 0.00 | 0.00 | 0.00 |
March | 68.27 | 34.59 | 33.67 | 101.81 | 60.12 | 0.00 | 0.00 | 0.00 |
April | 59.92 | 24.68 | 35.24 | 119.23 | 30.38 | 0.00 | 0.00 | 0.00 |
May | 40.04 | 6.96 | 33.07 | 92.76 | 19.10 | 0.00 | 0.00 | 0.00 |
June | 33.89 | 2.59 | 31.30 | 110.05 | 5.83 | 0.00 | 0.00 | 0.00 |
July | 34.34 | 3.26 | 31.07 | 107.55 | 3.76 | 0.00 | 0.00 | 0.00 |
August | 42.46 | 11.96 | 30.50 | 120.00 | 4.97 | 0.00 | 0.00 | 0.00 |
September | 60.32 | 25.49 | 34.82 | 138.40 | 8.24 | 0.00 | 0.00 | 0.00 |
October | 96.82 | 67.02 | 29.79 | 167.00 | 39.41 | 0.00 | 0.00 | 0.00 |
November | 113.80 | 87.41 | 26.40 | 172.76 | 62.18 | 0.00 | 0.00 | 0.00 |
December | 123.08 | 97.51 | 25.57 | 180.41 | 84.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.97 | 43.53 | 30.44 | 135.68 | 37.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.89 | 2.59 | 25.57 | 92.76 | 3.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.16 | 105.58 | 35.24 | 202.79 | 84.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.03 | 0.00 | 16.03 | 17.30 | 63.48 | 0.00 | 0.00 | 0.00 |
February | 18.27 | 0.00 | 18.27 | 11.54 | 63.32 | 0.00 | 0.00 | 0.00 |
March | 24.29 | 0.00 | 24.28 | 28.80 | 53.69 | 0.00 | 0.00 | 0.00 |
April | 29.74 | 0.44 | 29.30 | 63.31 | 21.41 | 0.00 | 0.00 | 0.00 |
May | 34.89 | 2.96 | 31.92 | 86.42 | 11.48 | 0.00 | 0.00 | 0.00 |
June | 40.29 | 7.36 | 32.93 | 132.37 | 2.47 | 0.00 | 0.00 | 0.00 |
July | 34.47 | 3.70 | 30.76 | 118.67 | 1.69 | 0.00 | 0.00 | 0.00 |
August | 27.73 | 0.68 | 27.05 | 98.81 | 1.88 | 0.00 | 0.00 | 0.00 |
September | 26.15 | 0.02 | 26.14 | 82.61 | 3.61 | 0.00 | 0.00 | 0.00 |
October | 20.22 | 0.00 | 20.22 | 40.63 | 32.34 | 0.00 | 0.00 | 0.00 |
November | 16.85 | 0.00 | 16.85 | 17.91 | 55.84 | 0.00 | 0.00 | 0.00 |
December | 14.98 | 0.00 | 14.98 | 10.42 | 80.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.35 | 1.27 | 24.08 | 59.29 | 32.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.98 | 0.00 | 14.98 | 10.42 | 1.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.29 | 7.36 | 32.93 | 132.37 | 80.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.94 | 75.91 | 45.03 | 160.05 | 140.09 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 69.17 | 51.05 | 141.21 | 137.66 | 0.00 | 0.00 | 0.00 |
March | 149.29 | 76.81 | 72.48 | 203.87 | 116.66 | 0.00 | 0.00 | 0.00 |
April | 212.74 | 126.76 | 85.99 | 377.32 | 51.32 | 0.00 | 0.00 | 0.00 |
May | 220.85 | 131.04 | 89.80 | 425.94 | 29.93 | 0.00 | 0.00 | 0.00 |
June | 229.78 | 142.76 | 87.03 | 521.74 | 7.60 | 0.00 | 0.00 | 0.00 |
July | 194.36 | 109.67 | 84.69 | 455.73 | 4.91 | 0.00 | 0.00 | 0.00 |
August | 184.63 | 105.48 | 79.14 | 422.54 | 5.97 | 0.00 | 0.00 | 0.00 |
September | 151.29 | 72.97 | 78.32 | 334.06 | 10.41 | 0.00 | 0.00 | 0.00 |
October | 151.83 | 92.35 | 59.47 | 255.79 | 74.37 | 0.00 | 0.00 | 0.00 |
November | 116.83 | 70.11 | 46.72 | 154.10 | 124.91 | 0.00 | 0.00 | 0.00 |
December | 106.72 | 64.54 | 42.18 | 124.03 | 175.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.49 | 94.92 | 68.57 | 298.79 | 73.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.72 | 64.54 | 42.18 | 124.03 | 4.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.78 | 142.76 | 89.80 | 521.74 | 175.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 258.26 | 74.50 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 144.56 | 72.84 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 129.88 | 65.84 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 150.47 | 30.79 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 117.30 | 18.31 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 140.10 | 4.60 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 139.29 | 2.94 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 154.44 | 3.40 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 177.80 | 5.87 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 212.24 | 40.15 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 220.28 | 65.76 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 230.76 | 92.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 173.19 | 39.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 117.30 | 2.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 258.26 | 92.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 18.44 | 79.97 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 12.60 | 78.71 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 31.82 | 68.10 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 70.42 | 29.31 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 98.53 | 16.14 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 154.25 | 4.06 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 137.60 | 2.64 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 113.13 | 3.15 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 94.46 | 5.76 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 44.44 | 42.67 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 19.26 | 70.76 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 11.53 | 100.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 67.47 | 41.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 11.53 | 2.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 154.25 | 100.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.94 | 75.91 | 45.03 | 168.28 | 134.54 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 69.17 | 51.05 | 146.55 | 133.42 | 0.00 | 0.00 | 0.00 |
March | 149.29 | 76.81 | 72.48 | 208.07 | 114.47 | 0.00 | 0.00 | 0.00 |
April | 212.74 | 126.76 | 85.99 | 379.56 | 50.58 | 0.00 | 0.00 | 0.00 |
May | 220.85 | 131.04 | 89.80 | 426.53 | 29.79 | 0.00 | 0.00 | 0.00 |
June | 229.78 | 142.76 | 87.03 | 521.48 | 7.63 | 0.00 | 0.00 | 0.00 |
July | 194.36 | 109.67 | 84.69 | 455.90 | 4.91 | 0.00 | 0.00 | 0.00 |
August | 184.63 | 105.48 | 79.14 | 423.86 | 5.86 | 0.00 | 0.00 | 0.00 |
September | 151.29 | 72.97 | 78.32 | 336.49 | 10.07 | 0.00 | 0.00 | 0.00 |
October | 151.83 | 92.35 | 59.47 | 260.62 | 72.07 | 0.00 | 0.00 | 0.00 |
November | 116.83 | 70.11 | 46.72 | 160.62 | 120.08 | 0.00 | 0.00 | 0.00 |
December | 106.72 | 64.54 | 42.18 | 131.74 | 168.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.49 | 94.92 | 68.57 | 302.39 | 70.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.72 | 64.54 | 42.18 | 131.74 | 4.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.78 | 142.76 | 89.80 | 521.48 | 168.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.38 | 0.00 | 25.38 | 19.92 | 119.25 | 0.00 | 0.00 | 0.00 |
February | 28.92 | 0.00 | 28.92 | 14.51 | 114.27 | 0.00 | 0.00 | 0.00 |
March | 38.44 | 0.00 | 38.44 | 38.98 | 98.95 | 0.00 | 0.00 | 0.00 |
April | 47.08 | 0.69 | 46.38 | 85.99 | 48.81 | 0.00 | 0.00 | 0.00 |
May | 55.22 | 4.69 | 50.53 | 119.16 | 29.37 | 0.00 | 0.00 | 0.00 |
June | 63.77 | 11.65 | 52.12 | 187.45 | 9.16 | 0.00 | 0.00 | 0.00 |
July | 54.55 | 5.86 | 48.69 | 163.49 | 6.30 | 0.00 | 0.00 | 0.00 |
August | 43.90 | 1.08 | 42.82 | 133.53 | 8.74 | 0.00 | 0.00 | 0.00 |
September | 41.39 | 0.03 | 41.37 | 110.38 | 14.90 | 0.00 | 0.00 | 0.00 |
October | 32.01 | 0.00 | 32.01 | 51.49 | 69.12 | 0.00 | 0.00 | 0.00 |
November | 26.67 | 0.00 | 26.67 | 20.84 | 108.18 | 0.00 | 0.00 | 0.00 |
December | 23.71 | 0.00 | 23.71 | 11.68 | 144.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.13 | 2.00 | 38.12 | 80.09 | 64.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.71 | 0.00 | 23.71 | 11.68 | 6.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.77 | 11.65 | 52.12 | 187.45 | 144.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.36 | 0.00 | 9.36 | 7.34 | 43.96 | 0.00 | 0.00 | 0.00 |
February | 10.66 | 0.00 | 10.66 | 5.35 | 42.12 | 0.00 | 0.00 | 0.00 |
March | 14.17 | 0.00 | 14.17 | 14.37 | 36.48 | 0.00 | 0.00 | 0.00 |
April | 17.35 | 0.26 | 17.10 | 31.70 | 17.99 | 0.00 | 0.00 | 0.00 |
May | 20.36 | 1.73 | 18.63 | 43.93 | 10.83 | 0.00 | 0.00 | 0.00 |
June | 23.51 | 4.30 | 19.21 | 69.10 | 3.37 | 0.00 | 0.00 | 0.00 |
July | 20.11 | 2.16 | 17.95 | 60.27 | 2.32 | 0.00 | 0.00 | 0.00 |
August | 16.18 | 0.40 | 15.78 | 49.22 | 3.22 | 0.00 | 0.00 | 0.00 |
September | 15.26 | 0.01 | 15.25 | 40.69 | 5.49 | 0.00 | 0.00 | 0.00 |
October | 11.80 | 0.00 | 11.80 | 18.98 | 25.48 | 0.00 | 0.00 | 0.00 |
November | 9.83 | 0.00 | 9.83 | 7.68 | 39.88 | 0.00 | 0.00 | 0.00 |
December | 8.74 | 0.00 | 8.74 | 4.31 | 53.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.79 | 0.74 | 14.05 | 29.52 | 23.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.74 | 0.00 | 8.74 | 4.31 | 2.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.51 | 4.30 | 19.21 | 69.10 | 53.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.10 | 61.59 | 15.51 | 120.63 | 39.22 | 0.00 | 0.00 | 0.00 |
February | 48.11 | 32.25 | 15.86 | 67.86 | 37.91 | 0.00 | 0.00 | 0.00 |
March | 39.82 | 20.18 | 19.64 | 60.89 | 34.74 | 0.00 | 0.00 | 0.00 |
April | 34.95 | 14.40 | 20.56 | 69.43 | 18.54 | 0.00 | 0.00 | 0.00 |
May | 23.36 | 4.06 | 19.29 | 53.07 | 12.16 | 0.00 | 0.00 | 0.00 |
June | 19.77 | 1.51 | 18.26 | 62.63 | 3.90 | 0.00 | 0.00 | 0.00 |
July | 20.03 | 1.90 | 18.13 | 61.13 | 2.57 | 0.00 | 0.00 | 0.00 |
August | 24.77 | 6.98 | 17.79 | 68.80 | 3.41 | 0.00 | 0.00 | 0.00 |
September | 35.19 | 14.87 | 20.31 | 79.95 | 5.44 | 0.00 | 0.00 | 0.00 |
October | 56.48 | 39.10 | 17.38 | 97.90 | 23.36 | 0.00 | 0.00 | 0.00 |
November | 66.39 | 50.99 | 15.40 | 102.42 | 35.59 | 0.00 | 0.00 | 0.00 |
December | 71.80 | 56.88 | 14.92 | 107.93 | 46.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.15 | 25.39 | 17.76 | 79.49 | 21.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.77 | 1.51 | 14.92 | 53.07 | 2.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.10 | 61.59 | 20.56 | 120.63 | 46.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 209.26 | 167.17 | 42.09 | 327.40 | 106.44 | 0.00 | 0.00 | 0.00 |
February | 130.57 | 87.54 | 43.04 | 184.18 | 102.91 | 0.00 | 0.00 | 0.00 |
March | 108.09 | 54.77 | 53.32 | 165.26 | 94.28 | 0.00 | 0.00 | 0.00 |
April | 94.87 | 39.08 | 55.79 | 188.45 | 50.32 | 0.00 | 0.00 | 0.00 |
May | 63.39 | 11.03 | 52.36 | 144.05 | 33.00 | 0.00 | 0.00 | 0.00 |
June | 53.66 | 4.09 | 49.56 | 169.99 | 10.58 | 0.00 | 0.00 | 0.00 |
July | 54.37 | 5.17 | 49.20 | 165.92 | 6.98 | 0.00 | 0.00 | 0.00 |
August | 67.23 | 18.94 | 48.30 | 186.73 | 9.26 | 0.00 | 0.00 | 0.00 |
September | 95.50 | 40.36 | 55.14 | 217.01 | 14.77 | 0.00 | 0.00 | 0.00 |
October | 153.30 | 106.12 | 47.17 | 265.73 | 63.41 | 0.00 | 0.00 | 0.00 |
November | 180.19 | 138.40 | 41.80 | 277.98 | 96.60 | 0.00 | 0.00 | 0.00 |
December | 194.88 | 154.40 | 40.48 | 292.95 | 127.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.12 | 68.92 | 48.20 | 215.75 | 59.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.66 | 4.09 | 40.48 | 144.05 | 6.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.26 | 167.17 | 55.79 | 327.40 | 127.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 258.26 | 73.84 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 145.76 | 71.35 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 131.15 | 65.00 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 150.73 | 29.81 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 118.49 | 17.53 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 141.39 | 4.36 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 140.94 | 2.80 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 155.62 | 3.09 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 178.20 | 5.35 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 212.72 | 39.11 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 220.14 | 65.14 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 231.47 | 91.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 173.98 | 38.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 118.49 | 2.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 258.26 | 91.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 185.60 | 151.23 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 122.01 | 143.62 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 191.91 | 123.48 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 372.08 | 55.33 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 406.64 | 32.52 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 502.64 | 7.99 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 395.93 | 5.17 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 370.03 | 5.73 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 305.58 | 10.21 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 238.49 | 77.90 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 182.37 | 132.79 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 132.44 | 188.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 284.52 | 77.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 122.01 | 5.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 502.64 | 188.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 20.37 | 78.13 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 14.15 | 75.88 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 34.04 | 66.45 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 71.85 | 28.29 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 100.13 | 15.66 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 155.22 | 3.91 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 139.18 | 2.55 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 114.70 | 2.92 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 95.80 | 5.30 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 46.60 | 40.79 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 20.70 | 69.19 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 13.09 | 97.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 69.08 | 40.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 13.09 | 2.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 155.22 | 97.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 194.80 | 144.89 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 128.13 | 138.98 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 196.97 | 121.04 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 374.73 | 54.45 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 407.24 | 32.36 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 502.25 | 8.00 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 396.05 | 5.17 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 371.46 | 5.61 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 308.27 | 9.84 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 244.47 | 75.12 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 189.85 | 127.59 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 141.49 | 181.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 288.68 | 75.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 128.13 | 5.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 502.25 | 181.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 242.33 | 193.60 | 48.74 | 372.62 | 112.85 | 0.00 | 0.00 | 0.00 |
February | 151.21 | 101.37 | 49.84 | 208.24 | 109.80 | 0.00 | 0.00 | 0.00 |
March | 125.18 | 63.43 | 61.75 | 189.14 | 97.19 | 0.00 | 0.00 | 0.00 |
April | 109.86 | 45.26 | 64.61 | 224.34 | 42.32 | 0.00 | 0.00 | 0.00 |
May | 73.41 | 12.77 | 60.64 | 179.91 | 24.04 | 0.00 | 0.00 | 0.00 |
June | 62.14 | 4.74 | 57.40 | 216.76 | 5.31 | 0.00 | 0.00 | 0.00 |
July | 62.97 | 5.99 | 56.98 | 213.81 | 3.63 | 0.00 | 0.00 | 0.00 |
August | 77.86 | 21.93 | 55.93 | 234.01 | 4.07 | 0.00 | 0.00 | 0.00 |
September | 110.60 | 46.74 | 63.85 | 264.28 | 7.41 | 0.00 | 0.00 | 0.00 |
October | 177.53 | 122.90 | 54.63 | 309.83 | 58.49 | 0.00 | 0.00 | 0.00 |
November | 208.67 | 160.27 | 48.40 | 318.04 | 99.08 | 0.00 | 0.00 | 0.00 |
December | 225.68 | 178.80 | 46.88 | 331.74 | 140.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.63 | 79.81 | 55.82 | 255.61 | 58.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.14 | 4.74 | 46.88 | 179.91 | 3.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 242.33 | 193.60 | 64.61 | 372.62 | 140.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 140.27 | 0.00 | 140.27 | 113.19 | 677.14 | 0.00 | 0.00 | 0.00 |
February | 159.84 | 0.00 | 159.84 | 71.33 | 680.00 | 0.00 | 0.00 | 0.00 |
March | 212.46 | 0.01 | 212.45 | 203.34 | 586.89 | 0.00 | 0.00 | 0.00 |
April | 260.20 | 3.83 | 256.37 | 479.16 | 279.86 | 0.00 | 0.00 | 0.00 |
May | 305.21 | 25.92 | 279.29 | 660.52 | 170.49 | 0.00 | 0.00 | 0.00 |
June | 352.47 | 64.40 | 288.07 | 1027.58 | 57.52 | 0.00 | 0.00 | 0.00 |
July | 301.52 | 32.40 | 269.12 | 894.00 | 41.55 | 0.00 | 0.00 | 0.00 |
August | 242.62 | 5.96 | 236.66 | 736.21 | 57.35 | 0.00 | 0.00 | 0.00 |
September | 228.79 | 0.14 | 228.65 | 614.58 | 93.20 | 0.00 | 0.00 | 0.00 |
October | 176.90 | 0.00 | 176.90 | 294.81 | 387.18 | 0.00 | 0.00 | 0.00 |
November | 147.39 | 0.00 | 147.39 | 117.33 | 612.96 | 0.00 | 0.00 | 0.00 |
December | 131.03 | 0.00 | 131.03 | 62.94 | 826.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.78 | 11.08 | 210.70 | 441.29 | 371.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.03 | 0.00 | 131.03 | 62.94 | 41.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.47 | 64.40 | 288.07 | 1027.58 | 826.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 140.27 | 0.00 | 140.27 | 103.39 | 702.96 | 0.00 | 0.00 | 0.00 |
February | 159.84 | 0.00 | 159.84 | 62.90 | 713.66 | 0.00 | 0.00 | 0.00 |
March | 212.46 | 0.01 | 212.45 | 189.64 | 610.99 | 0.00 | 0.00 | 0.00 |
April | 260.20 | 3.83 | 256.37 | 462.94 | 290.77 | 0.00 | 0.00 | 0.00 |
May | 305.21 | 25.92 | 279.29 | 642.28 | 177.08 | 0.00 | 0.00 | 0.00 |
June | 352.47 | 64.40 | 288.07 | 1007.53 | 60.64 | 0.00 | 0.00 | 0.00 |
July | 301.52 | 32.40 | 269.12 | 873.72 | 44.67 | 0.00 | 0.00 | 0.00 |
August | 242.62 | 5.96 | 236.66 | 717.22 | 61.92 | 0.00 | 0.00 | 0.00 |
September | 228.79 | 0.14 | 228.65 | 597.06 | 99.51 | 0.00 | 0.00 | 0.00 |
October | 176.90 | 0.00 | 176.90 | 281.84 | 403.12 | 0.00 | 0.00 | 0.00 |
November | 147.39 | 0.00 | 147.39 | 107.77 | 638.06 | 0.00 | 0.00 | 0.00 |
December | 131.03 | 0.00 | 131.03 | 55.12 | 859.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.78 | 11.08 | 210.70 | 426.79 | 387.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.03 | 0.00 | 131.03 | 55.12 | 44.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.47 | 64.40 | 288.07 | 1007.53 | 859.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 17.80 | 101.48 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 10.80 | 103.30 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 31.18 | 89.28 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 74.97 | 43.58 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 103.52 | 28.61 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 156.92 | 11.53 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 137.23 | 8.85 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 114.92 | 11.58 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 96.84 | 16.85 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 46.36 | 59.28 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 18.52 | 91.97 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 10.18 | 122.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 68.54 | 57.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 10.18 | 8.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 156.92 | 122.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 241.87 | 151.81 | 90.06 | 328.87 | 344.40 | 0.00 | 0.00 | 0.00 |
February | 240.43 | 138.34 | 102.10 | 282.53 | 354.56 | 0.00 | 0.00 | 0.00 |
March | 298.56 | 153.60 | 144.96 | 409.05 | 304.68 | 0.00 | 0.00 | 0.00 |
April | 425.45 | 253.49 | 171.96 | 774.59 | 154.12 | 0.00 | 0.00 | 0.00 |
May | 441.66 | 262.07 | 179.60 | 869.31 | 105.93 | 0.00 | 0.00 | 0.00 |
June | 459.53 | 285.49 | 174.04 | 1050.24 | 43.16 | 0.00 | 0.00 | 0.00 |
July | 388.70 | 219.32 | 169.38 | 908.28 | 32.97 | 0.00 | 0.00 | 0.00 |
August | 369.23 | 210.95 | 158.27 | 851.70 | 43.37 | 0.00 | 0.00 | 0.00 |
September | 302.56 | 145.93 | 156.63 | 679.04 | 61.77 | 0.00 | 0.00 | 0.00 |
October | 303.63 | 184.69 | 118.94 | 526.16 | 204.17 | 0.00 | 0.00 | 0.00 |
November | 233.65 | 140.21 | 93.44 | 314.67 | 315.49 | 0.00 | 0.00 | 0.00 |
December | 213.43 | 129.08 | 84.35 | 252.59 | 415.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 326.95 | 189.82 | 137.13 | 605.46 | 197.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.43 | 129.08 | 84.35 | 252.59 | 32.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 459.53 | 285.49 | 179.60 | 1050.24 | 415.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 262.06 | 91.69 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 145.45 | 93.55 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 131.33 | 85.37 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 155.86 | 44.73 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 122.47 | 30.98 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 142.65 | 12.33 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 139.22 | 9.26 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 156.99 | 11.80 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 181.19 | 16.81 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 216.73 | 54.98 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 223.23 | 83.29 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 233.51 | 109.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 176.14 | 53.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 122.47 | 9.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 262.06 | 109.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.38 | 0.00 | 25.38 | 17.23 | 121.74 | 0.00 | 0.00 | 0.00 |
February | 28.92 | 0.00 | 28.92 | 12.22 | 117.32 | 0.00 | 0.00 | 0.00 |
March | 38.44 | 0.00 | 38.44 | 35.18 | 102.25 | 0.00 | 0.00 | 0.00 |
April | 47.08 | 0.69 | 46.38 | 82.03 | 50.54 | 0.00 | 0.00 | 0.00 |
May | 55.22 | 4.69 | 50.53 | 115.52 | 30.50 | 0.00 | 0.00 | 0.00 |
June | 63.77 | 11.65 | 52.12 | 183.05 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 54.55 | 5.86 | 48.69 | 158.64 | 7.06 | 0.00 | 0.00 | 0.00 |
August | 43.90 | 1.08 | 42.82 | 129.13 | 9.88 | 0.00 | 0.00 | 0.00 |
September | 41.39 | 0.03 | 41.37 | 106.51 | 16.45 | 0.00 | 0.00 | 0.00 |
October | 32.01 | 0.00 | 32.01 | 48.73 | 70.48 | 0.00 | 0.00 | 0.00 |
November | 26.67 | 0.00 | 26.67 | 18.23 | 110.56 | 0.00 | 0.00 | 0.00 |
December | 23.71 | 0.00 | 23.71 | 10.00 | 145.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.13 | 2.00 | 38.12 | 76.67 | 65.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.71 | 0.00 | 23.71 | 10.00 | 7.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.77 | 11.65 | 52.12 | 183.05 | 145.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.71 | 0.00 | 22.71 | 15.42 | 108.91 | 0.00 | 0.00 | 0.00 |
February | 25.87 | 0.00 | 25.87 | 10.94 | 104.96 | 0.00 | 0.00 | 0.00 |
March | 34.39 | 0.00 | 34.39 | 31.48 | 91.48 | 0.00 | 0.00 | 0.00 |
April | 42.12 | 0.62 | 41.50 | 73.39 | 45.22 | 0.00 | 0.00 | 0.00 |
May | 49.41 | 4.20 | 45.21 | 103.36 | 27.28 | 0.00 | 0.00 | 0.00 |
June | 57.06 | 10.43 | 46.63 | 163.78 | 8.84 | 0.00 | 0.00 | 0.00 |
July | 48.81 | 5.24 | 43.56 | 141.94 | 6.32 | 0.00 | 0.00 | 0.00 |
August | 39.27 | 0.96 | 38.31 | 115.53 | 8.84 | 0.00 | 0.00 | 0.00 |
September | 37.04 | 0.02 | 37.01 | 95.29 | 14.72 | 0.00 | 0.00 | 0.00 |
October | 28.64 | 0.00 | 28.64 | 43.60 | 63.06 | 0.00 | 0.00 | 0.00 |
November | 23.86 | 0.00 | 23.86 | 16.31 | 98.91 | 0.00 | 0.00 | 0.00 |
December | 21.21 | 0.00 | 21.21 | 8.95 | 130.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.90 | 1.79 | 34.11 | 68.60 | 58.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.21 | 0.00 | 21.21 | 8.95 | 6.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.06 | 10.43 | 46.63 | 163.78 | 130.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 616.87 | 492.81 | 124.06 | 948.71 | 320.85 | 0.00 | 0.00 | 0.00 |
February | 384.91 | 258.05 | 126.87 | 530.51 | 311.61 | 0.00 | 0.00 | 0.00 |
March | 318.65 | 161.47 | 157.18 | 471.27 | 288.14 | 0.00 | 0.00 | 0.00 |
April | 279.66 | 115.20 | 164.46 | 540.66 | 153.57 | 0.00 | 0.00 | 0.00 |
May | 186.87 | 32.51 | 154.36 | 413.69 | 100.80 | 0.00 | 0.00 | 0.00 |
June | 158.17 | 12.07 | 146.11 | 489.16 | 33.38 | 0.00 | 0.00 | 0.00 |
July | 160.28 | 15.24 | 145.04 | 474.99 | 22.84 | 0.00 | 0.00 | 0.00 |
August | 198.20 | 55.82 | 142.38 | 536.54 | 30.62 | 0.00 | 0.00 | 0.00 |
September | 281.53 | 118.99 | 162.54 | 625.40 | 47.89 | 0.00 | 0.00 | 0.00 |
October | 451.90 | 312.84 | 139.06 | 769.15 | 190.88 | 0.00 | 0.00 | 0.00 |
November | 531.19 | 407.98 | 123.21 | 804.32 | 291.40 | 0.00 | 0.00 | 0.00 |
December | 574.48 | 455.14 | 119.34 | 852.23 | 378.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 345.26 | 203.16 | 142.10 | 622.20 | 180.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 158.17 | 12.07 | 119.34 | 413.69 | 22.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 616.87 | 492.81 | 164.46 | 948.71 | 378.28 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223838E+10 | 0.178821E+10 | 0.450171E+09 | 0.341766E+10 | 0.114183E+10 |
February | 0.126153E+10 | 0.845731E+09 | 0.415798E+09 | 0.173817E+10 | 0.957597E+09 |
March | 0.115623E+10 | 0.585894E+09 | 0.570335E+09 | 0.172247E+10 | 0.975281E+09 |
April | 0.982044E+09 | 0.404532E+09 | 0.577512E+09 | 0.186463E+10 | 0.544638E+09 |
May | 0.678057E+09 | 0.117952E+09 | 0.560105E+09 | 0.142779E+10 | 0.383879E+09 |
June | 0.555427E+09 | 42376069.35 | 0.513050E+09 | 0.158022E+10 | 0.139526E+09 |
July | 0.581591E+09 | 55297824.35 | 0.526293E+09 | 0.160834E+10 | 97997643.97 |
August | 0.719166E+09 | 0.202544E+09 | 0.516622E+09 | 0.184841E+10 | 0.131700E+09 |
September | 0.988595E+09 | 0.417832E+09 | 0.570763E+09 | 0.212968E+10 | 0.192662E+09 |
October | 0.163976E+10 | 0.113516E+10 | 0.504604E+09 | 0.277078E+10 | 0.690407E+09 |
November | 0.186529E+10 | 0.143263E+10 | 0.432667E+09 | 0.281688E+10 | 0.992144E+09 |
December | 0.208454E+10 | 0.165152E+10 | 0.433026E+09 | 0.304886E+10 | 0.133758E+10 |
Annual Sum or Average | 0.147506E+11 | 0.867966E+10 | 0.607095E+10 | 0.259739E+11 | 0.758524E+10 |
Minimum of Months | 0.555427E+09 | 42376069.35 | 0.415798E+09 | 0.142779E+10 | 97997643.97 |
Maximum of Months | 0.223838E+10 | 0.178821E+10 | 0.577512E+09 | 0.341766E+10 | 0.133758E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.630312E+10 | 0.503547E+10 | 0.126765E+10 | 0.960335E+10 | 0.322375E+10 |
February | 0.355238E+10 | 0.238152E+10 | 0.117086E+10 | 0.489970E+10 | 0.275562E+10 |
March | 0.325586E+10 | 0.164984E+10 | 0.160603E+10 | 0.490886E+10 | 0.274910E+10 |
April | 0.276537E+10 | 0.113914E+10 | 0.162624E+10 | 0.534270E+10 | 0.147338E+10 |
May | 0.190936E+10 | 0.332145E+09 | 0.157722E+10 | 0.418411E+10 | 0.101643E+10 |
June | 0.156404E+10 | 0.119328E+09 | 0.144472E+10 | 0.458917E+10 | 0.365274E+09 |
July | 0.163772E+10 | 0.155715E+09 | 0.148201E+10 | 0.466634E+10 | 0.255564E+09 |
August | 0.202512E+10 | 0.570351E+09 | 0.145477E+10 | 0.530214E+10 | 0.346201E+09 |
September | 0.278382E+10 | 0.117659E+10 | 0.160723E+10 | 0.606271E+10 | 0.519043E+09 |
October | 0.461746E+10 | 0.319653E+10 | 0.142093E+10 | 0.782526E+10 | 0.192060E+10 |
November | 0.525254E+10 | 0.403418E+10 | 0.121836E+10 | 0.793033E+10 | 0.278569E+10 |
December | 0.586993E+10 | 0.465056E+10 | 0.121937E+10 | 0.855807E+10 | 0.382197E+10 |
Annual Sum or Average | 0.415367E+11 | 0.244414E+11 | 0.170954E+11 | 0.738728E+11 | 0.212326E+11 |
Minimum of Months | 0.156404E+10 | 0.119328E+09 | 0.117086E+10 | 0.418411E+10 | 0.255564E+09 |
Maximum of Months | 0.630312E+10 | 0.503547E+10 | 0.162624E+10 | 0.960335E+10 | 0.382197E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.818812E+10 | 0.654136E+10 | 0.164675E+10 | 0.127261E+11 | 0.434062E+10 |
February | 0.461475E+10 | 0.309374E+10 | 0.152101E+10 | 0.646210E+10 | 0.384186E+10 |
March | 0.422955E+10 | 0.214323E+10 | 0.208632E+10 | 0.643483E+10 | 0.383924E+10 |
April | 0.359238E+10 | 0.147980E+10 | 0.211257E+10 | 0.706244E+10 | 0.201336E+10 |
May | 0.248037E+10 | 0.431476E+09 | 0.204890E+10 | 0.547407E+10 | 0.139946E+10 |
June | 0.203178E+10 | 0.155014E+09 | 0.187677E+10 | 0.606224E+10 | 0.486018E+09 |
July | 0.212749E+10 | 0.202283E+09 | 0.192521E+10 | 0.615815E+10 | 0.342447E+09 |
August | 0.263075E+10 | 0.740919E+09 | 0.188983E+10 | 0.703290E+10 | 0.458220E+09 |
September | 0.361634E+10 | 0.152845E+10 | 0.208788E+10 | 0.804133E+10 | 0.677155E+09 |
October | 0.599834E+10 | 0.415247E+10 | 0.184587E+10 | 0.103639E+11 | 0.259141E+10 |
November | 0.682335E+10 | 0.524063E+10 | 0.158272E+10 | 0.104896E+11 | 0.379255E+10 |
December | 0.762538E+10 | 0.604134E+10 | 0.158404E+10 | 0.113280E+11 | 0.519051E+10 |
Annual Sum or Average | 0.539586E+11 | 0.317507E+11 | 0.222079E+11 | 0.976357E+11 | 0.289729E+11 |
Minimum of Months | 0.203178E+10 | 0.155014E+09 | 0.152101E+10 | 0.547407E+10 | 0.342447E+09 |
Maximum of Months | 0.818812E+10 | 0.654136E+10 | 0.211257E+10 | 0.127261E+11 | 0.519051E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.694588E+09 | 0.201164E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.353987E+09 | 0.176118E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.353023E+09 | 0.176817E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.392699E+09 | 80168706.92 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.316974E+09 | 49599685.70 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.365185E+09 | 12484660.77 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.376580E+09 | 8055521.87 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.416610E+09 | 9114212.22 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.462809E+09 | 15335304.51 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.572158E+09 | 0.108289E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.573048E+09 | 0.172294E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.621131E+09 | 0.247786E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.549879E+10 | 0.125723E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.316974E+09 | 8055521.87 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.694588E+09 | 0.247786E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.499258E+09 | 0.414521E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.297025E+09 | 0.356074E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.516678E+09 | 0.337300E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.970630E+09 | 0.148900E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.109341E+10 | 91760554.46 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.130681E+10 | 22588250.10 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.106255E+10 | 14738029.40 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.992920E+09 | 16685839.24 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.793438E+09 | 28909066.77 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.640789E+09 | 0.216499E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.474955E+09 | 0.353002E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.355537E+09 | 0.514238E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.900400E+10 | 0.251521E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.297025E+09 | 14738029.40 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.130681E+10 | 0.514238E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 51864716.52 | 0.215564E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 33093896.69 | 0.188729E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 89928196.49 | 0.181934E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.185745E+09 | 76113789.11 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.267194E+09 | 44060318.92 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.401671E+09 | 10970161.75 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.372060E+09 | 7225550.85 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.306230E+09 | 8485874.30 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.247080E+09 | 15026154.02 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.122765E+09 | 0.113962E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 51506315.32 | 0.185125E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 32820848.21 | 0.268758E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.216196E+10 | 0.131595E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 32820848.21 | 7225550.85 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.401671E+09 | 0.268758E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.520647E+09 | 0.399724E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.310133E+09 | 0.345812E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.528906E+09 | 0.331458E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.977168E+09 | 0.146733E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.109498E+10 | 91343107.88 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.130589E+10 | 22609655.49 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.106289E+10 | 14738559.99 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.996568E+09 | 16366553.46 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.800069E+09 | 27951842.40 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.655095E+09 | 0.209901E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.491645E+09 | 0.341258E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.376918E+09 | 0.496687E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.912091E+10 | 0.244458E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.310133E+09 | 14738559.99 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.130589E+10 | 0.496687E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353983E+09 | 0.282791E+09 | 71191720.82 | 0.543155E+09 | 0.187258E+09 |
February | 0.199502E+09 | 0.133746E+09 | 65755807.07 | 0.273561E+09 | 0.162250E+09 |
March | 0.182850E+09 | 92654621.17 | 90194909.73 | 0.272688E+09 | 0.161023E+09 |
April | 0.155304E+09 | 63973596.40 | 91330373.15 | 0.309056E+09 | 78736864.57 |
May | 0.107231E+09 | 18653222.29 | 88577606.46 | 0.248435E+09 | 51168857.69 |
June | 87837819.98 | 6701448.63 | 81136371.35 | 0.285248E+09 | 15109028.51 |
July | 91975290.32 | 8744924.55 | 83230365.76 | 0.288066E+09 | 10060622.97 |
August | 0.113732E+09 | 32030806.41 | 81700800.92 | 0.321405E+09 | 13308117.55 |
September | 0.156339E+09 | 66076882.86 | 90262586.66 | 0.358740E+09 | 21359746.01 |
October | 0.259316E+09 | 0.179516E+09 | 79800009.62 | 0.447296E+09 | 0.105557E+09 |
November | 0.294982E+09 | 0.226559E+09 | 68423598.87 | 0.447797E+09 | 0.161168E+09 |
December | 0.329655E+09 | 0.261175E+09 | 68480327.14 | 0.483204E+09 | 0.226026E+09 |
Annual Sum or Average | 0.233271E+10 | 0.137262E+10 | 0.960084E+09 | 0.427865E+10 | 0.119302E+10 |
Minimum of Months | 87837819.98 | 6701448.63 | 65755807.07 | 0.248435E+09 | 10060622.97 |
Maximum of Months | 0.353983E+09 | 0.282791E+09 | 91330373.15 | 0.543155E+09 | 0.226026E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42944949.46 | 0.00 | 42944949.46 | 46323909.69 | 0.170034E+09 |
February | 44199004.85 | 0.00 | 44199004.85 | 27907259.34 | 0.153185E+09 |
March | 65045237.58 | 2573.27 | 65042664.31 | 77131890.78 | 0.143792E+09 |
April | 77090857.89 | 1135053.46 | 75955804.43 | 0.164098E+09 | 55483929.83 |
May | 93441433.49 | 7934259.35 | 85507174.14 | 0.231469E+09 | 30738754.70 |
June | 0.104430E+09 | 19081199.32 | 85349110.47 | 0.343104E+09 | 6399967.03 |
July | 92312481.83 | 9919050.97 | 82393430.86 | 0.317857E+09 | 4532587.84 |
August | 74279179.59 | 1823766.12 | 72455413.47 | 0.264664E+09 | 5046058.08 |
September | 67785290.05 | 41951.47 | 67743338.59 | 0.214126E+09 | 9355002.92 |
October | 54159300.98 | 0.00 | 54159300.98 | 0.108825E+09 | 86621851.76 |
November | 43668987.75 | 0.00 | 43668987.75 | 46411450.87 | 0.144740E+09 |
December | 40114513.77 | 0.00 | 40114513.77 | 27908009.96 | 0.216700E+09 |
Annual Sum or Average | 0.799472E+09 | 39937853.95 | 0.759534E+09 | 0.186983E+10 | 0.102663E+10 |
Minimum of Months | 40114513.77 | 0.00 | 40114513.77 | 27907259.34 | 4532587.84 |
Maximum of Months | 0.104430E+09 | 19081199.32 | 85507174.14 | 0.343104E+09 | 0.216700E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.323939E+09 | 0.203319E+09 | 0.120620E+09 | 0.428670E+09 | 0.375219E+09 |
February | 0.290851E+09 | 0.167343E+09 | 0.123508E+09 | 0.341605E+09 | 0.333029E+09 |
March | 0.399855E+09 | 0.205717E+09 | 0.194139E+09 | 0.546047E+09 | 0.312465E+09 |
April | 0.551427E+09 | 0.328551E+09 | 0.222876E+09 | 0.978013E+09 | 0.133030E+09 |
May | 0.591518E+09 | 0.350985E+09 | 0.240533E+09 | 0.114083E+10 | 80174013.02 |
June | 0.595597E+09 | 0.370022E+09 | 0.225575E+09 | 0.135235E+10 | 19689204.99 |
July | 0.520577E+09 | 0.293732E+09 | 0.226845E+09 | 0.122063E+10 | 13141059.28 |
August | 0.494504E+09 | 0.282527E+09 | 0.211977E+09 | 0.113173E+10 | 16000340.96 |
September | 0.392148E+09 | 0.189135E+09 | 0.203013E+09 | 0.865871E+09 | 26993819.32 |
October | 0.406651E+09 | 0.247359E+09 | 0.159292E+09 | 0.685109E+09 | 0.199180E+09 |
November | 0.302834E+09 | 0.181731E+09 | 0.121103E+09 | 0.399432E+09 | 0.323775E+09 |
December | 0.285842E+09 | 0.172873E+09 | 0.112970E+09 | 0.332198E+09 | 0.470092E+09 |
Annual Sum or Average | 0.515574E+10 | 0.299329E+10 | 0.216245E+10 | 0.942249E+10 | 0.230279E+10 |
Minimum of Months | 0.285842E+09 | 0.167343E+09 | 0.112970E+09 | 0.332198E+09 | 13141059.28 |
Maximum of Months | 0.595597E+09 | 0.370022E+09 | 0.240533E+09 | 0.135235E+10 | 0.470092E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.691721E+09 | 0.199531E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.349713E+09 | 0.176219E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.347871E+09 | 0.176349E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.390026E+09 | 79809975.50 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.314174E+09 | 49040578.70 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.363146E+09 | 11915226.43 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.373068E+09 | 7872624.76 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.413641E+09 | 9099968.64 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.460852E+09 | 15211300.02 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.568471E+09 | 0.107543E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.570961E+09 | 0.170463E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.618062E+09 | 0.246975E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.546171E+10 | 0.125003E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.314174E+09 | 7872624.76 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.691721E+09 | 0.246975E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 49394843.70 | 0.214186E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 30482447.20 | 0.190421E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 85238212.02 | 0.182391E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.182538E+09 | 75982923.82 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.263903E+09 | 43219989.73 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.399804E+09 | 10519336.15 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.368554E+09 | 7062109.82 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.303008E+09 | 8440286.96 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.244848E+09 | 14935511.56 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.119031E+09 | 0.114286E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 49928479.78 | 0.183410E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 30872787.78 | 0.268310E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.212760E+10 | 0.131316E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 30482447.20 | 7062109.82 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.399804E+09 | 0.268310E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.323939E+09 | 0.203319E+09 | 0.120620E+09 | 0.450708E+09 | 0.360358E+09 |
February | 0.290851E+09 | 0.167343E+09 | 0.123508E+09 | 0.354535E+09 | 0.322765E+09 |
March | 0.399855E+09 | 0.205717E+09 | 0.194139E+09 | 0.557298E+09 | 0.306584E+09 |
April | 0.551427E+09 | 0.328551E+09 | 0.222876E+09 | 0.983816E+09 | 0.131099E+09 |
May | 0.591518E+09 | 0.350985E+09 | 0.240533E+09 | 0.114242E+10 | 79797586.52 |
June | 0.595597E+09 | 0.370022E+09 | 0.225575E+09 | 0.135167E+10 | 19780229.11 |
July | 0.520577E+09 | 0.293732E+09 | 0.226845E+09 | 0.122108E+10 | 13157887.61 |
August | 0.494504E+09 | 0.282527E+09 | 0.211977E+09 | 0.113526E+10 | 15689607.74 |
September | 0.392148E+09 | 0.189135E+09 | 0.203013E+09 | 0.872178E+09 | 26100066.28 |
October | 0.406651E+09 | 0.247359E+09 | 0.159292E+09 | 0.698044E+09 | 0.193032E+09 |
November | 0.302834E+09 | 0.181731E+09 | 0.121103E+09 | 0.416331E+09 | 0.311248E+09 |
December | 0.285842E+09 | 0.172873E+09 | 0.112970E+09 | 0.352863E+09 | 0.450797E+09 |
Annual Sum or Average | 0.515574E+10 | 0.299329E+10 | 0.216245E+10 | 0.953620E+10 | 0.223041E+10 |
Minimum of Months | 0.285842E+09 | 0.167343E+09 | 0.112970E+09 | 0.352863E+09 | 13157887.61 |
Maximum of Months | 0.595597E+09 | 0.370022E+09 | 0.240533E+09 | 0.135167E+10 | 0.450797E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 67974825.56 | 0.00 | 67974825.56 | 53364146.18 | 0.319390E+09 |
February | 69959789.98 | 0.00 | 69959789.98 | 35108050.15 | 0.276436E+09 |
March | 0.102956E+09 | 4073.06 | 0.102952E+09 | 0.104409E+09 | 0.265027E+09 |
April | 0.122022E+09 | 1796603.83 | 0.120226E+09 | 0.222889E+09 | 0.126526E+09 |
May | 0.147902E+09 | 12558633.84 | 0.135344E+09 | 0.319151E+09 | 78677964.86 |
June | 0.165296E+09 | 30202415.22 | 0.135094E+09 | 0.485882E+09 | 23729911.37 |
July | 0.146116E+09 | 15700234.09 | 0.130415E+09 | 0.437897E+09 | 16874445.94 |
August | 0.117572E+09 | 2886723.24 | 0.114685E+09 | 0.357648E+09 | 23406391.53 |
September | 0.107293E+09 | 66402.30 | 0.107227E+09 | 0.286113E+09 | 38617127.68 |
October | 85725308.41 | 0.00 | 85725308.41 | 0.137919E+09 | 0.185135E+09 |
November | 69120859.66 | 0.00 | 69120859.66 | 54004444.72 | 0.280394E+09 |
December | 63494709.17 | 0.00 | 63494709.17 | 31281807.22 | 0.387037E+09 |
Annual Sum or Average | 0.126543E+10 | 63215085.59 | 0.120222E+10 | 0.252567E+10 | 0.202125E+10 |
Minimum of Months | 63494709.17 | 0.00 | 63494709.17 | 31281807.22 | 16874445.94 |
Maximum of Months | 0.165296E+09 | 30202415.22 | 0.135344E+09 | 0.485882E+09 | 0.387037E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25058335.32 | 0.00 | 25058335.32 | 19672233.92 | 0.117740E+09 |
February | 25790075.39 | 0.00 | 25790075.39 | 12942280.99 | 0.101906E+09 |
March | 37953831.47 | 1501.50 | 37952329.97 | 38489376.02 | 97699960.88 |
April | 44982438.94 | 662302.56 | 44320136.38 | 82165963.89 | 46642826.07 |
May | 54522983.56 | 4629632.44 | 49893351.11 | 0.117652E+09 | 29003955.64 |
June | 60934981.96 | 11133860.83 | 49801121.12 | 0.179116E+09 | 8747827.91 |
July | 53864241.38 | 5787756.38 | 48076485.00 | 0.161427E+09 | 6220619.49 |
August | 43341827.45 | 1064165.72 | 42277661.74 | 0.131844E+09 | 8628565.10 |
September | 39552649.37 | 24478.64 | 39528170.73 | 0.105473E+09 | 14235872.27 |
October | 31601898.29 | 0.00 | 31601898.29 | 50842577.34 | 68248500.12 |
November | 25480810.94 | 0.00 | 25480810.94 | 19908274.47 | 0.103365E+09 |
December | 23406778.91 | 0.00 | 23406778.91 | 11531769.42 | 0.142678E+09 |
Annual Sum or Average | 0.466491E+09 | 23303698.08 | 0.443187E+09 | 0.931065E+09 | 0.745117E+09 |
Minimum of Months | 23406778.91 | 0.00 | 23406778.91 | 11531769.42 | 6220619.49 |
Maximum of Months | 60934981.96 | 11133860.83 | 49893351.11 | 0.179116E+09 | 0.142678E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206500E+09 | 0.164969E+09 | 41530470.22 | 0.323084E+09 | 0.105039E+09 |
February | 0.116382E+09 | 78022138.43 | 38359370.38 | 0.164159E+09 | 91722323.32 |
March | 0.106667E+09 | 54051088.25 | 52616188.64 | 0.163079E+09 | 93035051.85 |
April | 90598271.93 | 37319698.27 | 53278573.67 | 0.179966E+09 | 48052889.16 |
May | 62554278.62 | 10881561.56 | 51672717.06 | 0.142151E+09 | 32562100.94 |
June | 51241154.51 | 3909363.47 | 47331791.04 | 0.162340E+09 | 10100940.75 |
July | 53654793.16 | 5101447.54 | 48553345.62 | 0.163733E+09 | 6887737.99 |
August | 66346579.02 | 18685521.81 | 47661057.22 | 0.184268E+09 | 9134648.04 |
September | 91202342.18 | 38546673.46 | 52655668.72 | 0.207238E+09 | 14107218.51 |
October | 0.151275E+09 | 0.104723E+09 | 46552209.79 | 0.262221E+09 | 62575940.55 |
November | 0.172081E+09 | 0.132165E+09 | 39915655.96 | 0.265463E+09 | 92248681.51 |
December | 0.192308E+09 | 0.152359E+09 | 39948749.01 | 0.289087E+09 | 0.125664E+09 |
Annual Sum or Average | 0.136081E+10 | 0.800734E+09 | 0.560076E+09 | 0.250679E+10 | 0.691131E+09 |
Minimum of Months | 51241154.51 | 3909363.47 | 38359370.38 | 0.142151E+09 | 6887737.99 |
Maximum of Months | 0.206500E+09 | 0.164969E+09 | 53278573.67 | 0.323084E+09 | 0.125664E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.560483E+09 | 0.447760E+09 | 0.112722E+09 | 0.876917E+09 | 0.285097E+09 |
February | 0.315883E+09 | 0.211768E+09 | 0.104115E+09 | 0.445562E+09 | 0.248953E+09 |
March | 0.289517E+09 | 0.146706E+09 | 0.142811E+09 | 0.442630E+09 | 0.252516E+09 |
April | 0.245902E+09 | 0.101293E+09 | 0.144609E+09 | 0.488465E+09 | 0.130425E+09 |
May | 0.169785E+09 | 29534783.85 | 0.140250E+09 | 0.385828E+09 | 88380202.39 |
June | 0.139079E+09 | 10610812.10 | 0.128468E+09 | 0.440623E+09 | 27416019.29 |
July | 0.145630E+09 | 13846372.09 | 0.131784E+09 | 0.444405E+09 | 18694729.76 |
August | 0.180078E+09 | 50716328.22 | 0.129362E+09 | 0.500140E+09 | 24793303.23 |
September | 0.247542E+09 | 0.104624E+09 | 0.142918E+09 | 0.562486E+09 | 38289876.60 |
October | 0.410591E+09 | 0.284239E+09 | 0.126352E+09 | 0.711722E+09 | 0.169844E+09 |
November | 0.467063E+09 | 0.358724E+09 | 0.108339E+09 | 0.720522E+09 | 0.250382E+09 |
December | 0.521963E+09 | 0.413534E+09 | 0.108429E+09 | 0.784641E+09 | 0.341078E+09 |
Annual Sum or Average | 0.369352E+10 | 0.217336E+10 | 0.152016E+10 | 0.680394E+10 | 0.187587E+10 |
Minimum of Months | 0.139079E+09 | 10610812.10 | 0.104115E+09 | 0.385828E+09 | 18694729.76 |
Maximum of Months | 0.560483E+09 | 0.447760E+09 | 0.144609E+09 | 0.876917E+09 | 0.341078E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.691723E+09 | 0.197778E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.352616E+09 | 0.172608E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.351279E+09 | 0.174105E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.390680E+09 | 77258851.40 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.317353E+09 | 46964268.13 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.366482E+09 | 11295478.38 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.377481E+09 | 7506952.97 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.416825E+09 | 8273272.00 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.461904E+09 | 13879815.65 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.569758E+09 | 0.104740E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.570602E+09 | 0.168834E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.619957E+09 | 0.244161E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.548666E+10 | 0.122740E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.317353E+09 | 7506952.97 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.691723E+09 | 0.244161E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.497100E+09 | 0.405054E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.295177E+09 | 0.347458E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.514000E+09 | 0.330727E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.964431E+09 | 0.143407E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.108915E+10 | 87107626.74 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.130284E+10 | 20718226.15 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.106045E+10 | 13856639.96 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.991091E+09 | 15339120.73 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.792067E+09 | 26474668.79 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.638776E+09 | 0.208637E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.472714E+09 | 0.344180E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.354714E+09 | 0.503767E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.897251E+10 | 0.244673E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.295177E+09 | 13856639.96 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.130284E+10 | 0.503767E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 54549203.70 | 0.209271E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 34227566.79 | 0.183563E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 91168037.84 | 0.177967E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.186224E+09 | 73329947.08 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.268185E+09 | 41947819.22 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.402327E+09 | 10132948.37 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.372769E+09 | 6818664.12 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.307202E+09 | 7817196.67 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.248323E+09 | 13746381.15 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.124822E+09 | 0.109244E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 53656697.10 | 0.179347E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 35052229.69 | 0.262086E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.217851E+10 | 0.127527E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 34227566.79 | 6818664.12 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.402327E+09 | 0.262086E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.521762E+09 | 0.388076E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.309979E+09 | 0.336230E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.527571E+09 | 0.324206E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.971300E+09 | 0.141133E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.109074E+10 | 86677361.32 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.130183E+10 | 20742949.45 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.106078E+10 | 13856468.25 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.994912E+09 | 15023965.32 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.799047E+09 | 25498446.33 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.654782E+09 | 0.201212E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.492099E+09 | 0.330709E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.378978E+09 | 0.484817E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.910379E+10 | 0.236818E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.309979E+09 | 13856468.25 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.130183E+10 | 0.484817E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.649066E+09 | 0.518528E+09 | 0.130538E+09 | 0.998035E+09 | 0.302250E+09 |
February | 0.365808E+09 | 0.245238E+09 | 0.120570E+09 | 0.503781E+09 | 0.265620E+09 |
March | 0.335275E+09 | 0.169892E+09 | 0.165382E+09 | 0.506592E+09 | 0.260303E+09 |
April | 0.284767E+09 | 0.117303E+09 | 0.167464E+09 | 0.581477E+09 | 0.109700E+09 |
May | 0.196619E+09 | 34202726.45 | 0.162417E+09 | 0.481876E+09 | 64390982.68 |
June | 0.161060E+09 | 12287840.18 | 0.148772E+09 | 0.561837E+09 | 13751561.98 |
July | 0.168647E+09 | 16034777.14 | 0.152612E+09 | 0.572675E+09 | 9720758.27 |
August | 0.208539E+09 | 58731992.40 | 0.149807E+09 | 0.626776E+09 | 10900776.70 |
September | 0.286666E+09 | 0.121159E+09 | 0.165506E+09 | 0.685008E+09 | 19199784.28 |
October | 0.475485E+09 | 0.329163E+09 | 0.146322E+09 | 0.829847E+09 | 0.156665E+09 |
November | 0.540882E+09 | 0.415420E+09 | 0.125462E+09 | 0.824347E+09 | 0.256810E+09 |
December | 0.604458E+09 | 0.478892E+09 | 0.125566E+09 | 0.888523E+09 | 0.375968E+09 |
Annual Sum or Average | 0.427727E+10 | 0.251685E+10 | 0.176042E+10 | 0.806077E+10 | 0.184528E+10 |
Minimum of Months | 0.161060E+09 | 12287840.18 | 0.120570E+09 | 0.481876E+09 | 9720758.27 |
Maximum of Months | 0.649066E+09 | 0.518528E+09 | 0.167464E+09 | 0.998035E+09 | 0.375968E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.303179E+09 | 0.181364E+10 |
February | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.172561E+09 | 0.164507E+10 |
March | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.544617E+09 | 0.157192E+10 |
April | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.124197E+10 | 0.725405E+09 |
May | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.176914E+10 | 0.456628E+09 |
June | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.266349E+10 | 0.149079E+09 |
July | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.239449E+10 | 0.111296E+09 |
August | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.197186E+10 | 0.153600E+09 |
September | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.159299E+10 | 0.241582E+09 |
October | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.789627E+09 | 0.103701E+10 |
November | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.304130E+09 | 0.158879E+10 |
December | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.168571E+09 | 0.221379E+10 |
Annual Sum or Average | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.139166E+11 | 0.117078E+11 |
Minimum of Months | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.168571E+09 | 0.111296E+09 |
Maximum of Months | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.266349E+10 | 0.221379E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.276913E+09 | 0.188281E+10 |
February | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.152179E+09 | 0.172649E+10 |
March | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.507919E+09 | 0.163647E+10 |
April | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.119995E+10 | 0.753678E+09 |
May | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.172028E+10 | 0.474286E+09 |
June | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.261152E+10 | 0.157191E+09 |
July | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.234018E+10 | 0.119648E+09 |
August | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.192099E+10 | 0.165858E+09 |
September | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.154759E+10 | 0.257929E+09 |
October | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.754872E+09 | 0.107972E+10 |
November | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.279348E+09 | 0.165385E+10 |
December | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.147627E+09 | 0.230279E+10 |
Annual Sum or Average | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.134594E+11 | 0.122107E+11 |
Minimum of Months | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.147627E+09 | 0.119648E+09 |
Maximum of Months | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.261152E+10 | 0.230279E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 47685500.87 | 0.271814E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 26138134.98 | 0.249904E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 83507338.53 | 0.239140E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.194328E+09 | 0.112952E+09 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.277257E+09 | 76632286.22 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.406742E+09 | 29874853.75 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.367554E+09 | 23705505.54 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.307815E+09 | 31020455.90 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.251008E+09 | 43675469.89 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.124162E+09 | 0.158763E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 48007473.91 | 0.238389E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 27272461.54 | 0.329298E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.216148E+10 | 0.180517E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 26138134.98 | 23705505.54 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.406742E+09 | 0.329298E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.647832E+09 | 0.406608E+09 | 0.241223E+09 | 0.880853E+09 | 0.922432E+09 |
February | 0.581660E+09 | 0.334662E+09 | 0.246998E+09 | 0.683493E+09 | 0.857740E+09 |
March | 0.799654E+09 | 0.411405E+09 | 0.388250E+09 | 0.109559E+10 | 0.816045E+09 |
April | 0.110278E+10 | 0.657056E+09 | 0.445720E+09 | 0.200773E+10 | 0.399485E+09 |
May | 0.118295E+10 | 0.701920E+09 | 0.481032E+09 | 0.232835E+10 | 0.283728E+09 |
June | 0.119111E+10 | 0.739991E+09 | 0.451119E+09 | 0.272222E+10 | 0.111873E+09 |
July | 0.104108E+10 | 0.587423E+09 | 0.453658E+09 | 0.243274E+10 | 88308093.70 |
August | 0.988937E+09 | 0.565014E+09 | 0.423923E+09 | 0.228118E+10 | 0.116170E+09 |
September | 0.784240E+09 | 0.378243E+09 | 0.405997E+09 | 0.176006E+10 | 0.160100E+09 |
October | 0.813243E+09 | 0.494683E+09 | 0.318561E+09 | 0.140926E+10 | 0.546852E+09 |
November | 0.605626E+09 | 0.363437E+09 | 0.242189E+09 | 0.815624E+09 | 0.817762E+09 |
December | 0.571644E+09 | 0.345721E+09 | 0.225923E+09 | 0.676545E+09 | 0.111306E+10 |
Annual Sum or Average | 0.103108E+11 | 0.598616E+10 | 0.432459E+10 | 0.190936E+11 | 0.623356E+10 |
Minimum of Months | 0.571644E+09 | 0.334662E+09 | 0.225923E+09 | 0.676545E+09 | 88308093.70 |
Maximum of Months | 0.119111E+10 | 0.739991E+09 | 0.481032E+09 | 0.272222E+10 | 0.111306E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.701892E+09 | 0.245588E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.351879E+09 | 0.226307E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.351764E+09 | 0.228654E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.403978E+09 | 0.115933E+09 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.328022E+09 | 82969643.85 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.369737E+09 | 31972005.61 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.372877E+09 | 24809066.13 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.420488E+09 | 31614811.35 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.469633E+09 | 43565979.54 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.580501E+09 | 0.147266E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.578603E+09 | 0.215881E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.625424E+09 | 0.292833E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.555480E+10 | 0.168739E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.328022E+09 | 24809066.13 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.701892E+09 | 0.292833E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 67974825.56 | 0.00 | 67974825.56 | 46150432.76 | 0.326079E+09 |
February | 69959789.98 | 0.00 | 69959789.98 | 29572350.51 | 0.283811E+09 |
March | 0.102956E+09 | 4073.06 | 0.102952E+09 | 94233347.35 | 0.273853E+09 |
April | 0.122022E+09 | 1796603.83 | 0.120226E+09 | 0.212612E+09 | 0.131007E+09 |
May | 0.147902E+09 | 12558633.84 | 0.135344E+09 | 0.309408E+09 | 81680407.87 |
June | 0.165296E+09 | 30202415.22 | 0.135094E+09 | 0.474465E+09 | 25604475.97 |
July | 0.146116E+09 | 15700234.09 | 0.130415E+09 | 0.424908E+09 | 18904752.30 |
August | 0.117572E+09 | 2886723.24 | 0.114685E+09 | 0.345854E+09 | 26460204.73 |
September | 0.107293E+09 | 66402.30 | 0.107227E+09 | 0.276067E+09 | 42633436.62 |
October | 85725308.41 | 0.00 | 85725308.41 | 0.130519E+09 | 0.188773E+09 |
November | 69120859.66 | 0.00 | 69120859.66 | 47242289.51 | 0.286566E+09 |
December | 63494709.17 | 0.00 | 63494709.17 | 26791744.57 | 0.389587E+09 |
Annual Sum or Average | 0.126543E+10 | 63215085.59 | 0.120222E+10 | 0.241782E+10 | 0.207496E+10 |
Minimum of Months | 63494709.17 | 0.00 | 63494709.17 | 26791744.57 | 18904752.30 |
Maximum of Months | 0.165296E+09 | 30202415.22 | 0.135344E+09 | 0.474465E+09 | 0.389587E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60817333.99 | 0.00 | 60817333.99 | 41290967.06 | 0.291713E+09 |
February | 62593289.17 | 0.00 | 62593289.17 | 26458494.05 | 0.253927E+09 |
March | 92115091.26 | 3644.19 | 92111447.08 | 84310932.92 | 0.245018E+09 |
April | 0.109174E+09 | 1607428.26 | 0.107566E+09 | 0.190225E+09 | 0.117213E+09 |
May | 0.132329E+09 | 11236257.28 | 0.121093E+09 | 0.276828E+09 | 73079770.41 |
June | 0.147891E+09 | 27022215.34 | 0.120869E+09 | 0.424505E+09 | 22908421.67 |
July | 0.130730E+09 | 14047058.93 | 0.116683E+09 | 0.380167E+09 | 16914153.51 |
August | 0.105192E+09 | 2582762.23 | 0.102609E+09 | 0.309437E+09 | 23674045.43 |
September | 95995470.41 | 59410.39 | 95936060.02 | 0.246998E+09 | 38144297.28 |
October | 76698758.25 | 0.00 | 76698758.25 | 0.116776E+09 | 0.168898E+09 |
November | 61842695.04 | 0.00 | 61842695.04 | 42267855.42 | 0.256383E+09 |
December | 56808956.88 | 0.00 | 56808956.88 | 23970675.38 | 0.348521E+09 |
Annual Sum or Average | 0.113219E+10 | 56558776.60 | 0.107563E+10 | 0.216324E+10 | 0.185639E+10 |
Minimum of Months | 56808956.88 | 0.00 | 56808956.88 | 23970675.38 | 16914153.51 |
Maximum of Months | 0.147891E+09 | 27022215.34 | 0.121093E+09 | 0.424505E+09 | 0.348521E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165223E+10 | 0.131994E+10 | 0.332291E+09 | 0.254104E+10 | 0.859354E+09 |
February | 0.931184E+09 | 0.624266E+09 | 0.306919E+09 | 0.128340E+10 | 0.753842E+09 |
March | 0.853459E+09 | 0.432470E+09 | 0.420989E+09 | 0.126224E+10 | 0.771744E+09 |
April | 0.724889E+09 | 0.298600E+09 | 0.426289E+09 | 0.140138E+10 | 0.398057E+09 |
May | 0.500505E+09 | 87064857.88 | 0.413440E+09 | 0.110803E+10 | 0.269994E+09 |
June | 0.409987E+09 | 31279350.23 | 0.378708E+09 | 0.126789E+10 | 86512367.18 |
July | 0.429299E+09 | 40817377.39 | 0.388482E+09 | 0.127220E+10 | 61180363.55 |
August | 0.530848E+09 | 0.149505E+09 | 0.381343E+09 | 0.143706E+10 | 82001306.81 |
September | 0.729722E+09 | 0.308417E+09 | 0.421305E+09 | 0.162105E+10 | 0.124120E+09 |
October | 0.121037E+10 | 0.837901E+09 | 0.372471E+09 | 0.206010E+10 | 0.511246E+09 |
November | 0.137684E+10 | 0.105747E+10 | 0.319371E+09 | 0.208479E+10 | 0.755315E+09 |
December | 0.153868E+10 | 0.121905E+10 | 0.319635E+09 | 0.228260E+10 | 0.101319E+10 |
Annual Sum or Average | 0.108880E+11 | 0.640678E+10 | 0.448124E+10 | 0.196218E+11 | 0.568656E+10 |
Minimum of Months | 0.409987E+09 | 31279350.23 | 0.306919E+09 | 0.110803E+10 | 61180363.55 |
Maximum of Months | 0.165223E+10 | 0.131994E+10 | 0.426289E+09 | 0.254104E+10 | 0.101319E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1276.01 | 426.31 | 835.71 | 667.64 | 168.07 | 0.00 | 0.00 |
February | 718.49 | 395.83 | 521.47 | 349.59 | 171.87 | 0.00 | 0.00 |
March | 643.10 | 364.13 | 431.69 | 218.75 | 212.94 | 0.00 | 0.00 |
April | 719.38 | 210.12 | 378.88 | 156.07 | 222.81 | 0.00 | 0.00 |
May | 533.08 | 143.32 | 253.16 | 44.04 | 209.12 | 0.00 | 0.00 |
June | 609.65 | 53.83 | 214.28 | 16.35 | 197.94 | 0.00 | 0.00 |
July | 600.49 | 36.59 | 217.14 | 20.65 | 196.50 | 0.00 | 0.00 |
August | 690.12 | 49.17 | 268.51 | 75.62 | 192.88 | 0.00 | 0.00 |
September | 821.64 | 74.33 | 381.40 | 161.20 | 220.20 | 0.00 | 0.00 |
October | 1034.49 | 257.77 | 612.22 | 423.82 | 188.40 | 0.00 | 0.00 |
November | 1086.76 | 382.77 | 719.63 | 552.71 | 166.92 | 0.00 | 0.00 |
December | 1138.32 | 499.39 | 778.28 | 616.61 | 161.67 | 0.00 | 0.00 |
Annual Sum or Average | 823.63 | 240.53 | 467.74 | 275.23 | 192.51 | 0.00 | 0.00 |
Minimum of Months | 533.08 | 36.59 | 214.28 | 16.35 | 161.67 | 0.00 | 0.00 |
Maximum of Months | 1276.01 | 499.39 | 835.71 | 667.64 | 222.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3585.48 | 1203.61 | 2353.32 | 1880.03 | 473.29 | 0.00 | 0.00 |
February | 2025.34 | 1139.06 | 1468.41 | 984.43 | 483.99 | 0.00 | 0.00 |
March | 1832.76 | 1026.40 | 1215.60 | 615.98 | 599.62 | 0.00 | 0.00 |
April | 2061.23 | 568.43 | 1066.89 | 439.48 | 627.41 | 0.00 | 0.00 |
May | 1562.17 | 379.49 | 712.87 | 124.01 | 588.87 | 0.00 | 0.00 |
June | 1770.51 | 140.92 | 603.41 | 46.04 | 557.38 | 0.00 | 0.00 |
July | 1742.21 | 95.42 | 611.46 | 58.14 | 553.32 | 0.00 | 0.00 |
August | 1979.59 | 129.26 | 756.09 | 212.94 | 543.15 | 0.00 | 0.00 |
September | 2339.01 | 200.25 | 1074.00 | 453.93 | 620.07 | 0.00 | 0.00 |
October | 2921.62 | 717.07 | 1723.96 | 1193.45 | 530.51 | 0.00 | 0.00 |
November | 3059.54 | 1074.73 | 2026.44 | 1556.40 | 470.05 | 0.00 | 0.00 |
December | 3195.22 | 1426.96 | 2191.58 | 1736.32 | 455.26 | 0.00 | 0.00 |
Annual Sum or Average | 2342.49 | 673.28 | 1317.12 | 775.03 | 542.09 | 0.00 | 0.00 |
Minimum of Months | 1562.17 | 95.42 | 603.41 | 46.04 | 455.26 | 0.00 | 0.00 |
Maximum of Months | 3585.48 | 1426.96 | 2353.32 | 1880.03 | 627.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4751.38 | 1620.60 | 3057.09 | 2442.27 | 614.83 | 0.00 | 0.00 |
February | 2671.17 | 1588.07 | 1907.55 | 1278.83 | 628.73 | 0.00 | 0.00 |
March | 2402.49 | 1433.41 | 1579.13 | 800.19 | 778.94 | 0.00 | 0.00 |
April | 2724.71 | 776.76 | 1385.95 | 570.91 | 815.04 | 0.00 | 0.00 |
May | 2043.78 | 522.50 | 926.06 | 161.09 | 764.97 | 0.00 | 0.00 |
June | 2338.83 | 187.51 | 783.87 | 59.80 | 724.06 | 0.00 | 0.00 |
July | 2299.19 | 127.86 | 794.32 | 75.52 | 718.79 | 0.00 | 0.00 |
August | 2625.78 | 171.08 | 982.21 | 276.63 | 705.58 | 0.00 | 0.00 |
September | 3102.36 | 261.25 | 1395.19 | 589.68 | 805.51 | 0.00 | 0.00 |
October | 3869.43 | 967.52 | 2239.52 | 1550.35 | 689.17 | 0.00 | 0.00 |
November | 4046.92 | 1463.18 | 2632.46 | 2021.85 | 610.62 | 0.00 | 0.00 |
December | 4229.41 | 1937.91 | 2846.99 | 2255.58 | 591.41 | 0.00 | 0.00 |
Annual Sum or Average | 3096.01 | 918.72 | 1711.02 | 1006.81 | 704.21 | 0.00 | 0.00 |
Minimum of Months | 2043.78 | 127.86 | 783.87 | 59.80 | 591.41 | 0.00 | 0.00 |
Maximum of Months | 4751.38 | 1937.91 | 3057.09 | 2442.27 | 815.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 437.15 | 221.29 | 292.23 | 211.13 | 81.11 | 0.00 | 0.00 |
February | 262.81 | 213.69 | 205.97 | 119.04 | 86.93 | 0.00 | 0.00 |
March | 322.36 | 189.60 | 221.47 | 108.35 | 113.12 | 0.00 | 0.00 |
April | 525.77 | 88.17 | 283.37 | 149.84 | 133.54 | 0.00 | 0.00 |
May | 526.58 | 52.78 | 259.27 | 125.95 | 133.32 | 0.00 | 0.00 |
June | 645.06 | 13.53 | 264.15 | 133.65 | 130.51 | 0.00 | 0.00 |
July | 537.31 | 8.51 | 204.27 | 79.26 | 125.00 | 0.00 | 0.00 |
August | 526.25 | 9.62 | 207.52 | 92.61 | 114.91 | 0.00 | 0.00 |
September | 484.65 | 17.06 | 209.80 | 88.38 | 121.42 | 0.00 | 0.00 |
October | 450.06 | 118.46 | 259.12 | 162.98 | 96.14 | 0.00 | 0.00 |
November | 397.07 | 195.41 | 268.67 | 185.54 | 83.13 | 0.00 | 0.00 |
December | 353.05 | 272.91 | 255.29 | 179.41 | 75.88 | 0.00 | 0.00 |
Annual Sum or Average | 456.63 | 116.37 | 244.44 | 136.45 | 107.99 | 0.00 | 0.00 |
Minimum of Months | 262.81 | 8.51 | 204.27 | 79.26 | 75.88 | 0.00 | 0.00 |
Maximum of Months | 645.06 | 272.91 | 292.23 | 211.13 | 133.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 213.08 | 229.06 | 147.04 | 79.12 | 67.91 | 0.00 | 0.00 |
February | 140.38 | 219.46 | 125.70 | 49.92 | 75.78 | 0.00 | 0.00 |
March | 229.43 | 190.07 | 166.47 | 65.10 | 101.37 | 0.00 | 0.00 |
April | 448.51 | 85.83 | 245.64 | 119.53 | 126.11 | 0.00 | 0.00 |
May | 507.17 | 49.15 | 252.82 | 120.95 | 131.87 | 0.00 | 0.00 |
June | 658.06 | 12.23 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
July | 535.48 | 7.93 | 204.41 | 79.81 | 124.60 | 0.00 | 0.00 |
August | 486.29 | 9.16 | 189.10 | 78.51 | 110.59 | 0.00 | 0.00 |
September | 403.99 | 16.58 | 167.08 | 56.53 | 110.55 | 0.00 | 0.00 |
October | 289.97 | 120.47 | 163.34 | 79.18 | 84.17 | 0.00 | 0.00 |
November | 208.60 | 202.13 | 147.44 | 76.26 | 71.18 | 0.00 | 0.00 |
December | 151.75 | 284.55 | 120.13 | 57.49 | 62.63 | 0.00 | 0.00 |
Annual Sum or Average | 357.02 | 118.49 | 183.65 | 83.62 | 100.03 | 0.00 | 0.00 |
Minimum of Months | 140.38 | 7.93 | 120.13 | 49.92 | 62.63 | 0.00 | 0.00 |
Maximum of Months | 658.06 | 284.55 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 202.79 | 69.91 | 132.16 | 105.58 | 26.58 | 0.00 | 0.00 |
February | 113.08 | 67.07 | 82.47 | 55.29 | 27.18 | 0.00 | 0.00 |
March | 101.81 | 60.12 | 68.27 | 34.59 | 33.67 | 0.00 | 0.00 |
April | 119.23 | 30.38 | 59.92 | 24.68 | 35.24 | 0.00 | 0.00 |
May | 92.76 | 19.10 | 40.04 | 6.96 | 33.07 | 0.00 | 0.00 |
June | 110.05 | 5.83 | 33.89 | 2.59 | 31.30 | 0.00 | 0.00 |
July | 107.55 | 3.76 | 34.34 | 3.26 | 31.07 | 0.00 | 0.00 |
August | 120.00 | 4.97 | 42.46 | 11.96 | 30.50 | 0.00 | 0.00 |
September | 138.40 | 8.24 | 60.32 | 25.49 | 34.82 | 0.00 | 0.00 |
October | 167.00 | 39.41 | 96.82 | 67.02 | 29.79 | 0.00 | 0.00 |
November | 172.76 | 62.18 | 113.80 | 87.41 | 26.40 | 0.00 | 0.00 |
December | 180.41 | 84.39 | 123.08 | 97.51 | 25.57 | 0.00 | 0.00 |
Annual Sum or Average | 135.68 | 37.83 | 73.97 | 43.53 | 30.44 | 0.00 | 0.00 |
Minimum of Months | 92.76 | 3.76 | 33.89 | 2.59 | 25.57 | 0.00 | 0.00 |
Maximum of Months | 202.79 | 84.39 | 132.16 | 105.58 | 35.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 17.30 | 63.48 | 16.03 | 0.00 | 16.03 | 0.00 | 0.00 |
February | 11.54 | 63.32 | 18.27 | 0.00 | 18.27 | 0.00 | 0.00 |
March | 28.80 | 53.69 | 24.29 | 0.00 | 24.28 | 0.00 | 0.00 |
April | 63.31 | 21.41 | 29.74 | 0.44 | 29.30 | 0.00 | 0.00 |
May | 86.42 | 11.48 | 34.89 | 2.96 | 31.92 | 0.00 | 0.00 |
June | 132.37 | 2.47 | 40.29 | 7.36 | 32.93 | 0.00 | 0.00 |
July | 118.67 | 1.69 | 34.47 | 3.70 | 30.76 | 0.00 | 0.00 |
August | 98.81 | 1.88 | 27.73 | 0.68 | 27.05 | 0.00 | 0.00 |
September | 82.61 | 3.61 | 26.15 | 0.02 | 26.14 | 0.00 | 0.00 |
October | 40.63 | 32.34 | 20.22 | 0.00 | 20.22 | 0.00 | 0.00 |
November | 17.91 | 55.84 | 16.85 | 0.00 | 16.85 | 0.00 | 0.00 |
December | 10.42 | 80.91 | 14.98 | 0.00 | 14.98 | 0.00 | 0.00 |
Annual Sum or Average | 59.29 | 32.55 | 25.35 | 1.27 | 24.08 | 0.00 | 0.00 |
Minimum of Months | 10.42 | 1.69 | 14.98 | 0.00 | 14.98 | 0.00 | 0.00 |
Maximum of Months | 132.37 | 80.91 | 40.29 | 7.36 | 32.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 416.65 | 212.93 | 286.18 | 207.91 | 78.27 | 0.00 | 0.00 |
February | 283.21 | 207.95 | 223.33 | 138.29 | 85.04 | 0.00 | 0.00 |
March | 330.08 | 178.84 | 234.64 | 120.06 | 114.59 | 0.00 | 0.00 |
April | 524.50 | 78.82 | 287.65 | 157.61 | 130.04 | 0.00 | 0.00 |
May | 541.08 | 46.08 | 270.90 | 139.75 | 131.15 | 0.00 | 0.00 |
June | 661.37 | 11.73 | 272.15 | 145.99 | 126.16 | 0.00 | 0.00 |
July | 594.73 | 7.56 | 237.29 | 113.75 | 123.55 | 0.00 | 0.00 |
August | 576.79 | 9.19 | 237.72 | 120.44 | 117.28 | 0.00 | 0.00 |
September | 511.59 | 16.02 | 226.70 | 104.84 | 121.86 | 0.00 | 0.00 |
October | 466.88 | 113.37 | 272.87 | 176.15 | 96.72 | 0.00 | 0.00 |
November | 372.34 | 188.63 | 259.12 | 179.39 | 79.73 | 0.00 | 0.00 |
December | 351.59 | 264.53 | 260.60 | 186.46 | 74.14 | 0.00 | 0.00 |
Annual Sum or Average | 470.24 | 110.92 | 255.97 | 149.33 | 106.63 | 0.00 | 0.00 |
Minimum of Months | 283.21 | 7.56 | 223.33 | 104.84 | 74.14 | 0.00 | 0.00 |
Maximum of Months | 661.37 | 264.53 | 287.65 | 207.91 | 131.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.45 | 207.24 | 140.98 | 75.91 | 65.07 | 0.00 | 0.00 |
February | 152.22 | 205.20 | 143.06 | 69.17 | 73.89 | 0.00 | 0.00 |
March | 233.90 | 176.57 | 179.64 | 76.81 | 102.83 | 0.00 | 0.00 |
April | 447.67 | 77.58 | 249.91 | 127.30 | 122.61 | 0.00 | 0.00 |
May | 524.87 | 45.74 | 264.45 | 134.75 | 129.71 | 0.00 | 0.00 |
June | 675.72 | 11.69 | 280.14 | 151.96 | 128.18 | 0.00 | 0.00 |
July | 593.48 | 7.53 | 237.44 | 114.30 | 123.14 | 0.00 | 0.00 |
August | 536.97 | 8.99 | 219.29 | 106.33 | 112.95 | 0.00 | 0.00 |
September | 430.65 | 15.54 | 183.98 | 72.99 | 110.99 | 0.00 | 0.00 |
October | 301.11 | 110.79 | 177.10 | 92.35 | 84.75 | 0.00 | 0.00 |
November | 173.51 | 184.47 | 137.89 | 70.11 | 67.78 | 0.00 | 0.00 |
December | 133.98 | 259.20 | 125.44 | 64.54 | 60.90 | 0.00 | 0.00 |
Annual Sum or Average | 366.32 | 108.83 | 195.17 | 96.50 | 98.67 | 0.00 | 0.00 |
Minimum of Months | 133.98 | 7.53 | 125.44 | 64.54 | 60.90 | 0.00 | 0.00 |
Maximum of Months | 675.72 | 259.20 | 280.14 | 151.96 | 129.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 463.08 | 296.65 | 321.09 | 228.77 | 92.33 | 0.00 | 0.00 |
February | 262.47 | 287.78 | 218.26 | 119.79 | 98.47 | 0.00 | 0.00 |
March | 277.30 | 262.24 | 200.53 | 74.96 | 125.57 | 0.00 | 0.00 |
April | 375.39 | 135.48 | 194.25 | 54.43 | 139.83 | 0.00 | 0.00 |
May | 358.12 | 83.27 | 162.32 | 21.51 | 140.82 | 0.00 | 0.00 |
June | 487.78 | 25.60 | 160.71 | 21.55 | 139.16 | 0.00 | 0.00 |
July | 450.27 | 17.63 | 149.07 | 15.10 | 133.97 | 0.00 | 0.00 |
August | 438.01 | 24.35 | 152.08 | 27.39 | 124.70 | 0.00 | 0.00 |
September | 447.99 | 40.56 | 187.34 | 55.27 | 132.07 | 0.00 | 0.00 |
October | 429.83 | 177.11 | 253.58 | 145.22 | 108.36 | 0.00 | 0.00 |
November | 397.79 | 269.12 | 283.08 | 189.39 | 93.69 | 0.00 | 0.00 |
December | 400.11 | 355.28 | 299.12 | 211.28 | 87.84 | 0.00 | 0.00 |
Annual Sum or Average | 399.82 | 164.09 | 215.19 | 97.05 | 118.14 | 0.00 | 0.00 |
Minimum of Months | 262.47 | 17.63 | 149.07 | 15.10 | 87.84 | 0.00 | 0.00 |
Maximum of Months | 487.78 | 355.28 | 321.09 | 228.77 | 140.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 435.96 | 217.17 | 292.23 | 211.13 | 81.11 | 0.00 | 0.00 |
February | 261.92 | 209.12 | 205.97 | 119.04 | 86.93 | 0.00 | 0.00 |
March | 320.82 | 186.25 | 221.47 | 108.35 | 113.12 | 0.00 | 0.00 |
April | 522.61 | 84.94 | 283.37 | 149.84 | 133.54 | 0.00 | 0.00 |
May | 525.13 | 50.05 | 259.27 | 125.95 | 133.32 | 0.00 | 0.00 |
June | 644.03 | 12.35 | 264.15 | 133.65 | 130.51 | 0.00 | 0.00 |
July | 536.86 | 7.98 | 204.27 | 79.26 | 125.00 | 0.00 | 0.00 |
August | 525.64 | 8.81 | 207.52 | 92.61 | 114.91 | 0.00 | 0.00 |
September | 483.77 | 15.55 | 209.80 | 88.38 | 121.42 | 0.00 | 0.00 |
October | 448.70 | 114.49 | 259.12 | 162.98 | 96.14 | 0.00 | 0.00 |
November | 395.76 | 191.17 | 268.67 | 185.54 | 83.13 | 0.00 | 0.00 |
December | 353.10 | 268.44 | 255.29 | 179.41 | 75.88 | 0.00 | 0.00 |
Annual Sum or Average | 455.48 | 113.49 | 244.44 | 136.45 | 107.99 | 0.00 | 0.00 |
Minimum of Months | 261.92 | 7.98 | 204.27 | 79.26 | 75.88 | 0.00 | 0.00 |
Maximum of Months | 644.03 | 268.44 | 292.23 | 211.13 | 133.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 214.54 | 222.39 | 147.04 | 79.12 | 67.91 | 0.00 | 0.00 |
February | 140.82 | 213.40 | 125.70 | 49.92 | 75.78 | 0.00 | 0.00 |
March | 229.43 | 185.91 | 166.47 | 65.10 | 101.37 | 0.00 | 0.00 |
April | 446.42 | 82.59 | 245.64 | 119.53 | 126.11 | 0.00 | 0.00 |
May | 506.03 | 46.69 | 252.82 | 120.95 | 131.87 | 0.00 | 0.00 |
June | 656.82 | 11.26 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
July | 534.98 | 7.47 | 204.41 | 79.81 | 124.60 | 0.00 | 0.00 |
August | 486.05 | 8.42 | 189.10 | 78.51 | 110.59 | 0.00 | 0.00 |
September | 404.07 | 15.14 | 167.08 | 56.53 | 110.55 | 0.00 | 0.00 |
October | 290.66 | 115.50 | 163.34 | 79.18 | 84.17 | 0.00 | 0.00 |
November | 209.66 | 195.89 | 147.44 | 76.26 | 71.18 | 0.00 | 0.00 |
December | 153.49 | 277.77 | 120.13 | 57.49 | 62.63 | 0.00 | 0.00 |
Annual Sum or Average | 357.05 | 114.82 | 183.65 | 83.62 | 100.03 | 0.00 | 0.00 |
Minimum of Months | 140.82 | 7.47 | 120.13 | 49.92 | 62.63 | 0.00 | 0.00 |
Maximum of Months | 656.82 | 277.77 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 372.62 | 112.85 | 242.33 | 193.60 | 48.74 | 0.00 | 0.00 |
February | 208.24 | 109.80 | 151.21 | 101.37 | 49.84 | 0.00 | 0.00 |
March | 189.14 | 97.19 | 125.18 | 63.43 | 61.75 | 0.00 | 0.00 |
April | 224.34 | 42.32 | 109.86 | 45.26 | 64.61 | 0.00 | 0.00 |
May | 179.91 | 24.04 | 73.41 | 12.77 | 60.64 | 0.00 | 0.00 |
June | 216.76 | 5.31 | 62.14 | 4.74 | 57.40 | 0.00 | 0.00 |
July | 213.81 | 3.63 | 62.97 | 5.99 | 56.98 | 0.00 | 0.00 |
August | 234.01 | 4.07 | 77.86 | 21.93 | 55.93 | 0.00 | 0.00 |
September | 264.28 | 7.41 | 110.60 | 46.74 | 63.85 | 0.00 | 0.00 |
October | 309.83 | 58.49 | 177.53 | 122.90 | 54.63 | 0.00 | 0.00 |
November | 318.04 | 99.08 | 208.67 | 160.27 | 48.40 | 0.00 | 0.00 |
December | 331.74 | 140.37 | 225.68 | 178.80 | 46.88 | 0.00 | 0.00 |
Annual Sum or Average | 255.61 | 58.51 | 135.63 | 79.81 | 55.82 | 0.00 | 0.00 |
Minimum of Months | 179.91 | 3.63 | 62.14 | 4.74 | 46.88 | 0.00 | 0.00 |
Maximum of Months | 372.62 | 140.37 | 242.33 | 193.60 | 64.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 113.19 | 677.14 | 140.27 | 0.00 | 140.27 | 0.00 | 0.00 |
February | 71.33 | 680.00 | 159.84 | 0.00 | 159.84 | 0.00 | 0.00 |
March | 203.34 | 586.89 | 212.46 | 0.01 | 212.45 | 0.00 | 0.00 |
April | 479.16 | 279.86 | 260.20 | 3.83 | 256.37 | 0.00 | 0.00 |
May | 660.52 | 170.49 | 305.21 | 25.92 | 279.29 | 0.00 | 0.00 |
June | 1027.58 | 57.52 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
July | 894.00 | 41.55 | 301.52 | 32.40 | 269.12 | 0.00 | 0.00 |
August | 736.21 | 57.35 | 242.62 | 5.96 | 236.66 | 0.00 | 0.00 |
September | 614.58 | 93.20 | 228.79 | 0.14 | 228.65 | 0.00 | 0.00 |
October | 294.81 | 387.18 | 176.90 | 0.00 | 176.90 | 0.00 | 0.00 |
November | 117.33 | 612.96 | 147.39 | 0.00 | 147.39 | 0.00 | 0.00 |
December | 62.94 | 826.54 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Annual Sum or Average | 441.29 | 371.25 | 221.78 | 11.08 | 210.70 | 0.00 | 0.00 |
Minimum of Months | 62.94 | 41.55 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Maximum of Months | 1027.58 | 826.54 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 103.39 | 702.96 | 140.27 | 0.00 | 140.27 | 0.00 | 0.00 |
February | 62.90 | 713.66 | 159.84 | 0.00 | 159.84 | 0.00 | 0.00 |
March | 189.64 | 610.99 | 212.46 | 0.01 | 212.45 | 0.00 | 0.00 |
April | 462.94 | 290.77 | 260.20 | 3.83 | 256.37 | 0.00 | 0.00 |
May | 642.28 | 177.08 | 305.21 | 25.92 | 279.29 | 0.00 | 0.00 |
June | 1007.53 | 60.64 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
July | 873.72 | 44.67 | 301.52 | 32.40 | 269.12 | 0.00 | 0.00 |
August | 717.22 | 61.92 | 242.62 | 5.96 | 236.66 | 0.00 | 0.00 |
September | 597.06 | 99.51 | 228.79 | 0.14 | 228.65 | 0.00 | 0.00 |
October | 281.84 | 403.12 | 176.90 | 0.00 | 176.90 | 0.00 | 0.00 |
November | 107.77 | 638.06 | 147.39 | 0.00 | 147.39 | 0.00 | 0.00 |
December | 55.12 | 859.76 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Annual Sum or Average | 426.79 | 387.20 | 221.78 | 11.08 | 210.70 | 0.00 | 0.00 |
Minimum of Months | 55.12 | 44.67 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Maximum of Months | 1007.53 | 859.76 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 596.88 | 525.72 | 427.15 | 283.81 | 143.33 | 0.00 | 0.00 |
February | 425.69 | 538.31 | 366.37 | 207.46 | 158.92 | 0.00 | 0.00 |
March | 560.56 | 468.34 | 414.26 | 196.85 | 217.41 | 0.00 | 0.00 |
April | 999.21 | 236.22 | 537.54 | 284.90 | 252.64 | 0.00 | 0.00 |
May | 1092.33 | 162.56 | 535.32 | 274.48 | 260.84 | 0.00 | 0.00 |
June | 1349.01 | 66.22 | 552.26 | 297.92 | 254.33 | 0.00 | 0.00 |
July | 1184.23 | 50.59 | 474.70 | 228.03 | 246.68 | 0.00 | 0.00 |
August | 1123.31 | 66.45 | 456.98 | 226.75 | 230.22 | 0.00 | 0.00 |
September | 956.30 | 94.66 | 410.66 | 177.82 | 232.84 | 0.00 | 0.00 |
October | 783.16 | 312.34 | 449.95 | 268.49 | 181.46 | 0.00 | 0.00 |
November | 544.57 | 478.90 | 396.99 | 249.50 | 147.50 | 0.00 | 0.00 |
December | 478.43 | 629.99 | 386.03 | 250.99 | 135.03 | 0.00 | 0.00 |
Annual Sum or Average | 843.23 | 301.50 | 451.12 | 245.82 | 205.30 | 0.00 | 0.00 |
Minimum of Months | 425.69 | 50.59 | 366.37 | 177.82 | 135.03 | 0.00 | 0.00 |
Maximum of Months | 1349.01 | 629.99 | 552.26 | 297.92 | 260.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 962.77 | 532.91 | 664.96 | 492.81 | 172.15 | 0.00 | 0.00 |
February | 538.95 | 519.17 | 439.71 | 258.05 | 181.66 | 0.00 | 0.00 |
March | 534.37 | 478.30 | 391.48 | 161.47 | 230.01 | 0.00 | 0.00 |
April | 695.78 | 249.05 | 368.86 | 116.51 | 252.35 | 0.00 | 0.00 |
May | 628.97 | 154.99 | 291.49 | 41.39 | 250.10 | 0.00 | 0.00 |
June | 833.14 | 49.25 | 279.00 | 34.15 | 244.86 | 0.00 | 0.00 |
July | 774.43 | 35.08 | 263.64 | 26.35 | 237.30 | 0.00 | 0.00 |
August | 780.61 | 48.75 | 281.37 | 57.86 | 223.51 | 0.00 | 0.00 |
September | 827.12 | 78.97 | 359.96 | 119.04 | 240.92 | 0.00 | 0.00 |
October | 854.99 | 317.92 | 512.54 | 312.84 | 199.71 | 0.00 | 0.00 |
November | 821.85 | 483.87 | 581.72 | 407.98 | 173.74 | 0.00 | 0.00 |
December | 846.03 | 628.71 | 619.39 | 455.14 | 164.25 | 0.00 | 0.00 |
Annual Sum or Average | 759.66 | 297.17 | 421.29 | 206.96 | 214.33 | 0.00 | 0.00 |
Minimum of Months | 534.37 | 35.08 | 263.64 | 26.35 | 164.25 | 0.00 | 0.00 |
Maximum of Months | 962.77 | 628.71 | 664.96 | 492.81 | 252.35 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.341766E+10 | 0.114183E+10 | 0.223838E+10 | 0.178821E+10 | 0.450171E+09 | 0.00 | 0.00 |
February | 0.173817E+10 | 0.957597E+09 | 0.126153E+10 | 0.845731E+09 | 0.415798E+09 | 0.00 | 0.00 |
March | 0.172247E+10 | 0.975281E+09 | 0.115623E+10 | 0.585894E+09 | 0.570335E+09 | 0.00 | 0.00 |
April | 0.186463E+10 | 0.544638E+09 | 0.982044E+09 | 0.404532E+09 | 0.577512E+09 | 0.00 | 0.00 |
May | 0.142779E+10 | 0.383879E+09 | 0.678057E+09 | 0.117952E+09 | 0.560105E+09 | 0.00 | 0.00 |
June | 0.158022E+10 | 0.139526E+09 | 0.555427E+09 | 42376069.35 | 0.513050E+09 | 0.00 | 0.00 |
July | 0.160834E+10 | 97997643.97 | 0.581591E+09 | 55297824.35 | 0.526293E+09 | 0.00 | 0.00 |
August | 0.184841E+10 | 0.131700E+09 | 0.719166E+09 | 0.202544E+09 | 0.516622E+09 | 0.00 | 0.00 |
September | 0.212968E+10 | 0.192662E+09 | 0.988595E+09 | 0.417832E+09 | 0.570763E+09 | 0.00 | 0.00 |
October | 0.277078E+10 | 0.690407E+09 | 0.163976E+10 | 0.113516E+10 | 0.504604E+09 | 0.00 | 0.00 |
November | 0.281688E+10 | 0.992144E+09 | 0.186529E+10 | 0.143263E+10 | 0.432667E+09 | 0.00 | 0.00 |
December | 0.304886E+10 | 0.133758E+10 | 0.208454E+10 | 0.165152E+10 | 0.433026E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.259739E+11 | 0.758524E+10 | 0.147506E+11 | 0.867966E+10 | 0.607095E+10 | 0.00 | 0.00 |
Minimum of Months | 0.142779E+10 | 97997643.97 | 0.555427E+09 | 42376069.35 | 0.415798E+09 | 0.00 | 0.00 |
Maximum of Months | 0.341766E+10 | 0.133758E+10 | 0.223838E+10 | 0.178821E+10 | 0.577512E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.960335E+10 | 0.322375E+10 | 0.630312E+10 | 0.503547E+10 | 0.126765E+10 | 0.00 | 0.00 |
February | 0.489970E+10 | 0.275562E+10 | 0.355238E+10 | 0.238152E+10 | 0.117086E+10 | 0.00 | 0.00 |
March | 0.490886E+10 | 0.274910E+10 | 0.325586E+10 | 0.164984E+10 | 0.160603E+10 | 0.00 | 0.00 |
April | 0.534270E+10 | 0.147338E+10 | 0.276537E+10 | 0.113914E+10 | 0.162624E+10 | 0.00 | 0.00 |
May | 0.418411E+10 | 0.101643E+10 | 0.190936E+10 | 0.332145E+09 | 0.157722E+10 | 0.00 | 0.00 |
June | 0.458917E+10 | 0.365274E+09 | 0.156404E+10 | 0.119328E+09 | 0.144472E+10 | 0.00 | 0.00 |
July | 0.466634E+10 | 0.255564E+09 | 0.163772E+10 | 0.155715E+09 | 0.148201E+10 | 0.00 | 0.00 |
August | 0.530214E+10 | 0.346201E+09 | 0.202512E+10 | 0.570351E+09 | 0.145477E+10 | 0.00 | 0.00 |
September | 0.606271E+10 | 0.519043E+09 | 0.278382E+10 | 0.117659E+10 | 0.160723E+10 | 0.00 | 0.00 |
October | 0.782526E+10 | 0.192060E+10 | 0.461746E+10 | 0.319653E+10 | 0.142093E+10 | 0.00 | 0.00 |
November | 0.793033E+10 | 0.278569E+10 | 0.525254E+10 | 0.403418E+10 | 0.121836E+10 | 0.00 | 0.00 |
December | 0.855807E+10 | 0.382197E+10 | 0.586993E+10 | 0.465056E+10 | 0.121937E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.738728E+11 | 0.212326E+11 | 0.415367E+11 | 0.244414E+11 | 0.170954E+11 | 0.00 | 0.00 |
Minimum of Months | 0.418411E+10 | 0.255564E+09 | 0.156404E+10 | 0.119328E+09 | 0.117086E+10 | 0.00 | 0.00 |
Maximum of Months | 0.960335E+10 | 0.382197E+10 | 0.630312E+10 | 0.503547E+10 | 0.162624E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.127261E+11 | 0.434062E+10 | 0.818812E+10 | 0.654136E+10 | 0.164675E+10 | 0.00 | 0.00 |
February | 0.646210E+10 | 0.384186E+10 | 0.461475E+10 | 0.309374E+10 | 0.152101E+10 | 0.00 | 0.00 |
March | 0.643483E+10 | 0.383924E+10 | 0.422955E+10 | 0.214323E+10 | 0.208632E+10 | 0.00 | 0.00 |
April | 0.706244E+10 | 0.201336E+10 | 0.359238E+10 | 0.147980E+10 | 0.211257E+10 | 0.00 | 0.00 |
May | 0.547407E+10 | 0.139946E+10 | 0.248037E+10 | 0.431476E+09 | 0.204890E+10 | 0.00 | 0.00 |
June | 0.606224E+10 | 0.486018E+09 | 0.203178E+10 | 0.155014E+09 | 0.187677E+10 | 0.00 | 0.00 |
July | 0.615815E+10 | 0.342447E+09 | 0.212749E+10 | 0.202283E+09 | 0.192521E+10 | 0.00 | 0.00 |
August | 0.703290E+10 | 0.458220E+09 | 0.263075E+10 | 0.740919E+09 | 0.188983E+10 | 0.00 | 0.00 |
September | 0.804133E+10 | 0.677155E+09 | 0.361634E+10 | 0.152845E+10 | 0.208788E+10 | 0.00 | 0.00 |
October | 0.103639E+11 | 0.259141E+10 | 0.599834E+10 | 0.415247E+10 | 0.184587E+10 | 0.00 | 0.00 |
November | 0.104896E+11 | 0.379255E+10 | 0.682335E+10 | 0.524063E+10 | 0.158272E+10 | 0.00 | 0.00 |
December | 0.113280E+11 | 0.519051E+10 | 0.762538E+10 | 0.604134E+10 | 0.158404E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.976357E+11 | 0.289729E+11 | 0.539586E+11 | 0.317507E+11 | 0.222079E+11 | 0.00 | 0.00 |
Minimum of Months | 0.547407E+10 | 0.342447E+09 | 0.203178E+10 | 0.155014E+09 | 0.152101E+10 | 0.00 | 0.00 |
Maximum of Months | 0.127261E+11 | 0.519051E+10 | 0.818812E+10 | 0.654136E+10 | 0.211257E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117085E+10 | 0.592694E+09 | 0.782721E+09 | 0.565485E+09 | 0.217236E+09 | 0.00 | 0.00 |
February | 0.635784E+09 | 0.516963E+09 | 0.498285E+09 | 0.287991E+09 | 0.210294E+09 | 0.00 | 0.00 |
March | 0.863402E+09 | 0.507817E+09 | 0.593196E+09 | 0.290214E+09 | 0.302982E+09 | 0.00 | 0.00 |
April | 0.136281E+10 | 0.228544E+09 | 0.734505E+09 | 0.388376E+09 | 0.346129E+09 | 0.00 | 0.00 |
May | 0.141038E+10 | 0.141358E+09 | 0.694431E+09 | 0.337345E+09 | 0.357087E+09 | 0.00 | 0.00 |
June | 0.167199E+10 | 35070086.76 | 0.684686E+09 | 0.346412E+09 | 0.338274E+09 | 0.00 | 0.00 |
July | 0.143913E+10 | 22793010.63 | 0.547106E+09 | 0.212292E+09 | 0.334813E+09 | 0.00 | 0.00 |
August | 0.140950E+10 | 25772735.59 | 0.555835E+09 | 0.248047E+09 | 0.307788E+09 | 0.00 | 0.00 |
September | 0.125621E+10 | 44207256.70 | 0.543814E+09 | 0.229081E+09 | 0.314733E+09 | 0.00 | 0.00 |
October | 0.120544E+10 | 0.317283E+09 | 0.694021E+09 | 0.436513E+09 | 0.257508E+09 | 0.00 | 0.00 |
November | 0.102921E+10 | 0.506499E+09 | 0.696397E+09 | 0.480919E+09 | 0.215478E+09 | 0.00 | 0.00 |
December | 0.945601E+09 | 0.730957E+09 | 0.683759E+09 | 0.480526E+09 | 0.203233E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.144003E+11 | 0.366996E+10 | 0.770875E+10 | 0.430320E+10 | 0.340555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.635784E+09 | 22793010.63 | 0.498285E+09 | 0.212292E+09 | 0.203233E+09 | 0.00 | 0.00 |
Maximum of Months | 0.167199E+10 | 0.730957E+09 | 0.782721E+09 | 0.565485E+09 | 0.357087E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.570725E+09 | 0.613502E+09 | 0.393828E+09 | 0.211926E+09 | 0.181903E+09 | 0.00 | 0.00 |
February | 0.339606E+09 | 0.530920E+09 | 0.304099E+09 | 0.120775E+09 | 0.183324E+09 | 0.00 | 0.00 |
March | 0.614517E+09 | 0.509076E+09 | 0.445884E+09 | 0.174376E+09 | 0.271508E+09 | 0.00 | 0.00 |
April | 0.116253E+10 | 0.222466E+09 | 0.636687E+09 | 0.309812E+09 | 0.326875E+09 | 0.00 | 0.00 |
May | 0.135842E+10 | 0.131644E+09 | 0.677152E+09 | 0.323940E+09 | 0.353213E+09 | 0.00 | 0.00 |
June | 0.170568E+10 | 31703130.01 | 0.705388E+09 | 0.361882E+09 | 0.343505E+09 | 0.00 | 0.00 |
July | 0.143423E+10 | 21240356.77 | 0.547489E+09 | 0.213756E+09 | 0.333733E+09 | 0.00 | 0.00 |
August | 0.130249E+10 | 24539706.68 | 0.506479E+09 | 0.210280E+09 | 0.296199E+09 | 0.00 | 0.00 |
September | 0.104714E+10 | 42965232.90 | 0.433071E+09 | 0.146521E+09 | 0.286550E+09 | 0.00 | 0.00 |
October | 0.776656E+09 | 0.322659E+09 | 0.437501E+09 | 0.212073E+09 | 0.225428E+09 | 0.00 | 0.00 |
November | 0.540683E+09 | 0.523914E+09 | 0.382175E+09 | 0.197665E+09 | 0.184511E+09 | 0.00 | 0.00 |
December | 0.406434E+09 | 0.762141E+09 | 0.321745E+09 | 0.153993E+09 | 0.167752E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112591E+11 | 0.373677E+10 | 0.579150E+10 | 0.263700E+10 | 0.315450E+10 | 0.00 | 0.00 |
Minimum of Months | 0.339606E+09 | 21240356.77 | 0.304099E+09 | 0.120775E+09 | 0.167752E+09 | 0.00 | 0.00 |
Maximum of Months | 0.170568E+10 | 0.762141E+09 | 0.705388E+09 | 0.361882E+09 | 0.353213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.543155E+09 | 0.187258E+09 | 0.353983E+09 | 0.282791E+09 | 71191720.82 | 0.00 | 0.00 |
February | 0.273561E+09 | 0.162250E+09 | 0.199502E+09 | 0.133746E+09 | 65755807.07 | 0.00 | 0.00 |
March | 0.272688E+09 | 0.161023E+09 | 0.182850E+09 | 92654621.17 | 90194909.73 | 0.00 | 0.00 |
April | 0.309056E+09 | 78736864.57 | 0.155304E+09 | 63973596.40 | 91330373.15 | 0.00 | 0.00 |
May | 0.248435E+09 | 51168857.69 | 0.107231E+09 | 18653222.29 | 88577606.46 | 0.00 | 0.00 |
June | 0.285248E+09 | 15109028.51 | 87837819.98 | 6701448.63 | 81136371.35 | 0.00 | 0.00 |
July | 0.288066E+09 | 10060622.97 | 91975290.32 | 8744924.55 | 83230365.76 | 0.00 | 0.00 |
August | 0.321405E+09 | 13308117.55 | 0.113732E+09 | 32030806.41 | 81700800.92 | 0.00 | 0.00 |
September | 0.358740E+09 | 21359746.01 | 0.156339E+09 | 66076882.86 | 90262586.66 | 0.00 | 0.00 |
October | 0.447296E+09 | 0.105557E+09 | 0.259316E+09 | 0.179516E+09 | 79800009.62 | 0.00 | 0.00 |
November | 0.447797E+09 | 0.161168E+09 | 0.294982E+09 | 0.226559E+09 | 68423598.87 | 0.00 | 0.00 |
December | 0.483204E+09 | 0.226026E+09 | 0.329655E+09 | 0.261175E+09 | 68480327.14 | 0.00 | 0.00 |
Annual Sum or Average | 0.427865E+10 | 0.119302E+10 | 0.233271E+10 | 0.137262E+10 | 0.960084E+09 | 0.00 | 0.00 |
Minimum of Months | 0.248435E+09 | 10060622.97 | 87837819.98 | 6701448.63 | 65755807.07 | 0.00 | 0.00 |
Maximum of Months | 0.543155E+09 | 0.226026E+09 | 0.353983E+09 | 0.282791E+09 | 91330373.15 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 46323909.69 | 0.170034E+09 | 42944949.46 | 0.00 | 42944949.46 | 0.00 | 0.00 |
February | 27907259.34 | 0.153185E+09 | 44199004.85 | 0.00 | 44199004.85 | 0.00 | 0.00 |
March | 77131890.78 | 0.143792E+09 | 65045237.58 | 2573.27 | 65042664.31 | 0.00 | 0.00 |
April | 0.164098E+09 | 55483929.83 | 77090857.89 | 1135053.46 | 75955804.43 | 0.00 | 0.00 |
May | 0.231469E+09 | 30738754.70 | 93441433.49 | 7934259.35 | 85507174.14 | 0.00 | 0.00 |
June | 0.343104E+09 | 6399967.03 | 0.104430E+09 | 19081199.32 | 85349110.47 | 0.00 | 0.00 |
July | 0.317857E+09 | 4532587.84 | 92312481.83 | 9919050.97 | 82393430.86 | 0.00 | 0.00 |
August | 0.264664E+09 | 5046058.08 | 74279179.59 | 1823766.12 | 72455413.47 | 0.00 | 0.00 |
September | 0.214126E+09 | 9355002.92 | 67785290.05 | 41951.47 | 67743338.59 | 0.00 | 0.00 |
October | 0.108825E+09 | 86621851.76 | 54159300.98 | 0.00 | 54159300.98 | 0.00 | 0.00 |
November | 46411450.87 | 0.144740E+09 | 43668987.75 | 0.00 | 43668987.75 | 0.00 | 0.00 |
December | 27908009.96 | 0.216700E+09 | 40114513.77 | 0.00 | 40114513.77 | 0.00 | 0.00 |
Annual Sum or Average | 0.186983E+10 | 0.102663E+10 | 0.799472E+09 | 39937853.95 | 0.759534E+09 | 0.00 | 0.00 |
Minimum of Months | 27907259.34 | 4532587.84 | 40114513.77 | 0.00 | 40114513.77 | 0.00 | 0.00 |
Maximum of Months | 0.343104E+09 | 0.216700E+09 | 0.104430E+09 | 19081199.32 | 85507174.14 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111596E+10 | 0.570322E+09 | 0.766505E+09 | 0.556878E+09 | 0.209627E+09 | 0.00 | 0.00 |
February | 0.685143E+09 | 0.503073E+09 | 0.540277E+09 | 0.334558E+09 | 0.205719E+09 | 0.00 | 0.00 |
March | 0.884097E+09 | 0.478992E+09 | 0.628463E+09 | 0.321558E+09 | 0.306905E+09 | 0.00 | 0.00 |
April | 0.135950E+10 | 0.204305E+09 | 0.745596E+09 | 0.408534E+09 | 0.337062E+09 | 0.00 | 0.00 |
May | 0.144922E+10 | 0.123428E+09 | 0.725583E+09 | 0.374306E+09 | 0.351277E+09 | 0.00 | 0.00 |
June | 0.171428E+10 | 30394210.23 | 0.705417E+09 | 0.378400E+09 | 0.327016E+09 | 0.00 | 0.00 |
July | 0.159293E+10 | 20244129.22 | 0.635569E+09 | 0.304666E+09 | 0.330904E+09 | 0.00 | 0.00 |
August | 0.154489E+10 | 24613971.55 | 0.636696E+09 | 0.322574E+09 | 0.314123E+09 | 0.00 | 0.00 |
September | 0.132603E+10 | 41514985.58 | 0.587611E+09 | 0.271747E+09 | 0.315864E+09 | 0.00 | 0.00 |
October | 0.125050E+10 | 0.303638E+09 | 0.730860E+09 | 0.471799E+09 | 0.259061E+09 | 0.00 | 0.00 |
November | 0.965096E+09 | 0.488941E+09 | 0.671635E+09 | 0.464986E+09 | 0.206650E+09 | 0.00 | 0.00 |
December | 0.941709E+09 | 0.708517E+09 | 0.697993E+09 | 0.499406E+09 | 0.198587E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.148294E+11 | 0.349798E+10 | 0.807221E+10 | 0.470941E+10 | 0.336279E+10 | 0.00 | 0.00 |
Minimum of Months | 0.685143E+09 | 20244129.22 | 0.540277E+09 | 0.271747E+09 | 0.198587E+09 | 0.00 | 0.00 |
Maximum of Months | 0.171428E+10 | 0.708517E+09 | 0.766505E+09 | 0.556878E+09 | 0.351277E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.480637E+09 | 0.555078E+09 | 0.377613E+09 | 0.203319E+09 | 0.174294E+09 | 0.00 | 0.00 |
February | 0.368241E+09 | 0.496410E+09 | 0.346092E+09 | 0.167343E+09 | 0.178749E+09 | 0.00 | 0.00 |
March | 0.626476E+09 | 0.472915E+09 | 0.481151E+09 | 0.205720E+09 | 0.275431E+09 | 0.00 | 0.00 |
April | 0.116036E+10 | 0.201085E+09 | 0.647778E+09 | 0.329970E+09 | 0.317808E+09 | 0.00 | 0.00 |
May | 0.140581E+10 | 0.122503E+09 | 0.708304E+09 | 0.360901E+09 | 0.347403E+09 | 0.00 | 0.00 |
June | 0.175147E+10 | 30296335.89 | 0.726118E+09 | 0.393870E+09 | 0.332248E+09 | 0.00 | 0.00 |
July | 0.158959E+10 | 20174460.46 | 0.635953E+09 | 0.306130E+09 | 0.329823E+09 | 0.00 | 0.00 |
August | 0.143822E+10 | 24083454.80 | 0.587340E+09 | 0.284806E+09 | 0.302534E+09 | 0.00 | 0.00 |
September | 0.111626E+10 | 40266868.94 | 0.476868E+09 | 0.189187E+09 | 0.287681E+09 | 0.00 | 0.00 |
October | 0.806501E+09 | 0.296744E+09 | 0.474341E+09 | 0.247359E+09 | 0.226982E+09 | 0.00 | 0.00 |
November | 0.449739E+09 | 0.478137E+09 | 0.357413E+09 | 0.181731E+09 | 0.175682E+09 | 0.00 | 0.00 |
December | 0.358865E+09 | 0.694237E+09 | 0.335979E+09 | 0.172873E+09 | 0.163106E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115522E+11 | 0.343193E+10 | 0.615495E+10 | 0.304321E+10 | 0.311174E+10 | 0.00 | 0.00 |
Minimum of Months | 0.358865E+09 | 20174460.46 | 0.335979E+09 | 0.167343E+09 | 0.163106E+09 | 0.00 | 0.00 |
Maximum of Months | 0.175147E+10 | 0.694237E+09 | 0.726118E+09 | 0.393870E+09 | 0.347403E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124031E+10 | 0.794544E+09 | 0.860015E+09 | 0.612730E+09 | 0.247286E+09 | 0.00 | 0.00 |
February | 0.634958E+09 | 0.696204E+09 | 0.528015E+09 | 0.289790E+09 | 0.238224E+09 | 0.00 | 0.00 |
March | 0.742711E+09 | 0.702382E+09 | 0.537094E+09 | 0.200762E+09 | 0.336332E+09 | 0.00 | 0.00 |
April | 0.973011E+09 | 0.351172E+09 | 0.503505E+09 | 0.141072E+09 | 0.362433E+09 | 0.00 | 0.00 |
May | 0.959196E+09 | 0.223037E+09 | 0.434765E+09 | 57604611.69 | 0.377160E+09 | 0.00 | 0.00 |
June | 0.126433E+10 | 66366216.43 | 0.416551E+09 | 55856451.63 | 0.360695E+09 | 0.00 | 0.00 |
July | 0.120600E+10 | 47211411.86 | 0.399265E+09 | 40435810.09 | 0.358829E+09 | 0.00 | 0.00 |
August | 0.117316E+10 | 65224260.59 | 0.407338E+09 | 73352738.99 | 0.333986E+09 | 0.00 | 0.00 |
September | 0.116119E+10 | 0.105129E+09 | 0.485590E+09 | 0.143261E+09 | 0.342329E+09 | 0.00 | 0.00 |
October | 0.115126E+10 | 0.474359E+09 | 0.679193E+09 | 0.388962E+09 | 0.290232E+09 | 0.00 | 0.00 |
November | 0.103106E+10 | 0.697551E+09 | 0.733746E+09 | 0.490890E+09 | 0.242857E+09 | 0.00 | 0.00 |
December | 0.107167E+10 | 0.951582E+09 | 0.801172E+09 | 0.565893E+09 | 0.235279E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126089E+11 | 0.517476E+10 | 0.678625E+10 | 0.306061E+10 | 0.372564E+10 | 0.00 | 0.00 |
Minimum of Months | 0.634958E+09 | 47211411.86 | 0.399265E+09 | 40435810.09 | 0.235279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126433E+10 | 0.951582E+09 | 0.860015E+09 | 0.612730E+09 | 0.377160E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116767E+10 | 0.581680E+09 | 0.782721E+09 | 0.565485E+09 | 0.217236E+09 | 0.00 | 0.00 |
February | 0.633636E+09 | 0.505909E+09 | 0.498285E+09 | 0.287991E+09 | 0.210294E+09 | 0.00 | 0.00 |
March | 0.859289E+09 | 0.498841E+09 | 0.593196E+09 | 0.290214E+09 | 0.302982E+09 | 0.00 | 0.00 |
April | 0.135460E+10 | 0.220156E+09 | 0.734505E+09 | 0.388376E+09 | 0.346129E+09 | 0.00 | 0.00 |
May | 0.140650E+10 | 0.134064E+09 | 0.694431E+09 | 0.337345E+09 | 0.357087E+09 | 0.00 | 0.00 |
June | 0.166931E+10 | 32011177.08 | 0.684686E+09 | 0.346412E+09 | 0.338274E+09 | 0.00 | 0.00 |
July | 0.143793E+10 | 21363073.86 | 0.547106E+09 | 0.212292E+09 | 0.334813E+09 | 0.00 | 0.00 |
August | 0.140789E+10 | 23583445.67 | 0.555835E+09 | 0.248047E+09 | 0.307788E+09 | 0.00 | 0.00 |
September | 0.125393E+10 | 40315091.74 | 0.543814E+09 | 0.229081E+09 | 0.314733E+09 | 0.00 | 0.00 |
October | 0.120180E+10 | 0.306642E+09 | 0.694021E+09 | 0.436513E+09 | 0.257508E+09 | 0.00 | 0.00 |
November | 0.102581E+10 | 0.495512E+09 | 0.696397E+09 | 0.480919E+09 | 0.215478E+09 | 0.00 | 0.00 |
December | 0.945745E+09 | 0.719002E+09 | 0.683759E+09 | 0.480526E+09 | 0.203233E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.143641E+11 | 0.357908E+10 | 0.770875E+10 | 0.430320E+10 | 0.340555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.633636E+09 | 21363073.86 | 0.498285E+09 | 0.212292E+09 | 0.203233E+09 | 0.00 | 0.00 |
Maximum of Months | 0.166931E+10 | 0.719002E+09 | 0.782721E+09 | 0.565485E+09 | 0.357087E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.574625E+09 | 0.595660E+09 | 0.393828E+09 | 0.211926E+09 | 0.181903E+09 | 0.00 | 0.00 |
February | 0.340666E+09 | 0.516252E+09 | 0.304099E+09 | 0.120775E+09 | 0.183324E+09 | 0.00 | 0.00 |
March | 0.614500E+09 | 0.497934E+09 | 0.445884E+09 | 0.174376E+09 | 0.271508E+09 | 0.00 | 0.00 |
April | 0.115713E+10 | 0.214067E+09 | 0.636687E+09 | 0.309812E+09 | 0.326875E+09 | 0.00 | 0.00 |
May | 0.135535E+10 | 0.125051E+09 | 0.677152E+09 | 0.323940E+09 | 0.353213E+09 | 0.00 | 0.00 |
June | 0.170247E+10 | 29180211.42 | 0.705388E+09 | 0.361882E+09 | 0.343505E+09 | 0.00 | 0.00 |
July | 0.143289E+10 | 20013343.90 | 0.547489E+09 | 0.213756E+09 | 0.333733E+09 | 0.00 | 0.00 |
August | 0.130183E+10 | 22558937.96 | 0.506479E+09 | 0.210280E+09 | 0.296199E+09 | 0.00 | 0.00 |
September | 0.104736E+10 | 39232035.28 | 0.433071E+09 | 0.146521E+09 | 0.286550E+09 | 0.00 | 0.00 |
October | 0.778494E+09 | 0.309345E+09 | 0.437501E+09 | 0.212073E+09 | 0.225428E+09 | 0.00 | 0.00 |
November | 0.543449E+09 | 0.507749E+09 | 0.382175E+09 | 0.197665E+09 | 0.184511E+09 | 0.00 | 0.00 |
December | 0.411101E+09 | 0.743974E+09 | 0.321745E+09 | 0.153993E+09 | 0.167752E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112599E+11 | 0.362102E+10 | 0.579150E+10 | 0.263700E+10 | 0.315450E+10 | 0.00 | 0.00 |
Minimum of Months | 0.340666E+09 | 20013343.90 | 0.304099E+09 | 0.120775E+09 | 0.167752E+09 | 0.00 | 0.00 |
Maximum of Months | 0.170247E+10 | 0.743974E+09 | 0.705388E+09 | 0.361882E+09 | 0.353213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.998035E+09 | 0.302250E+09 | 0.649066E+09 | 0.518528E+09 | 0.130538E+09 | 0.00 | 0.00 |
February | 0.503781E+09 | 0.265620E+09 | 0.365808E+09 | 0.245238E+09 | 0.120570E+09 | 0.00 | 0.00 |
March | 0.506592E+09 | 0.260303E+09 | 0.335275E+09 | 0.169892E+09 | 0.165382E+09 | 0.00 | 0.00 |
April | 0.581477E+09 | 0.109700E+09 | 0.284767E+09 | 0.117303E+09 | 0.167464E+09 | 0.00 | 0.00 |
May | 0.481876E+09 | 64390982.68 | 0.196619E+09 | 34202726.45 | 0.162417E+09 | 0.00 | 0.00 |
June | 0.561837E+09 | 13751561.98 | 0.161060E+09 | 12287840.18 | 0.148772E+09 | 0.00 | 0.00 |
July | 0.572675E+09 | 9720758.27 | 0.168647E+09 | 16034777.14 | 0.152612E+09 | 0.00 | 0.00 |
August | 0.626776E+09 | 10900776.70 | 0.208539E+09 | 58731992.40 | 0.149807E+09 | 0.00 | 0.00 |
September | 0.685008E+09 | 19199784.28 | 0.286666E+09 | 0.121159E+09 | 0.165506E+09 | 0.00 | 0.00 |
October | 0.829847E+09 | 0.156665E+09 | 0.475485E+09 | 0.329163E+09 | 0.146322E+09 | 0.00 | 0.00 |
November | 0.824347E+09 | 0.256810E+09 | 0.540882E+09 | 0.415420E+09 | 0.125462E+09 | 0.00 | 0.00 |
December | 0.888523E+09 | 0.375968E+09 | 0.604458E+09 | 0.478892E+09 | 0.125566E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.806077E+10 | 0.184528E+10 | 0.427727E+10 | 0.251685E+10 | 0.176042E+10 | 0.00 | 0.00 |
Minimum of Months | 0.481876E+09 | 9720758.27 | 0.161060E+09 | 12287840.18 | 0.120570E+09 | 0.00 | 0.00 |
Maximum of Months | 0.998035E+09 | 0.375968E+09 | 0.649066E+09 | 0.518528E+09 | 0.167464E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.303179E+09 | 0.181364E+10 | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.00 | 0.00 |
February | 0.172561E+09 | 0.164507E+10 | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.00 | 0.00 |
March | 0.544617E+09 | 0.157192E+10 | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.00 | 0.00 |
April | 0.124197E+10 | 0.725405E+09 | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.00 | 0.00 |
May | 0.176914E+10 | 0.456628E+09 | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.00 | 0.00 |
June | 0.266349E+10 | 0.149079E+09 | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.00 | 0.00 |
July | 0.239449E+10 | 0.111296E+09 | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.00 | 0.00 |
August | 0.197186E+10 | 0.153600E+09 | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.00 | 0.00 |
September | 0.159299E+10 | 0.241582E+09 | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.00 | 0.00 |
October | 0.789627E+09 | 0.103701E+10 | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.00 | 0.00 |
November | 0.304130E+09 | 0.158879E+10 | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.00 | 0.00 |
December | 0.168571E+09 | 0.221379E+10 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.139166E+11 | 0.117078E+11 | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.00 | 0.00 |
Minimum of Months | 0.168571E+09 | 0.111296E+09 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Maximum of Months | 0.266349E+10 | 0.221379E+10 | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.276913E+09 | 0.188281E+10 | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.00 | 0.00 |
February | 0.152179E+09 | 0.172649E+10 | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.00 | 0.00 |
March | 0.507919E+09 | 0.163647E+10 | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.00 | 0.00 |
April | 0.119995E+10 | 0.753678E+09 | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.00 | 0.00 |
May | 0.172028E+10 | 0.474286E+09 | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.00 | 0.00 |
June | 0.261152E+10 | 0.157191E+09 | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.00 | 0.00 |
July | 0.234018E+10 | 0.119648E+09 | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.00 | 0.00 |
August | 0.192099E+10 | 0.165858E+09 | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.00 | 0.00 |
September | 0.154759E+10 | 0.257929E+09 | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.00 | 0.00 |
October | 0.754872E+09 | 0.107972E+10 | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.00 | 0.00 |
November | 0.279348E+09 | 0.165385E+10 | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.00 | 0.00 |
December | 0.147627E+09 | 0.230279E+10 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.134594E+11 | 0.122107E+11 | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.00 | 0.00 |
Minimum of Months | 0.147627E+09 | 0.119648E+09 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Maximum of Months | 0.261152E+10 | 0.230279E+10 | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.159869E+10 | 0.140810E+10 | 0.114407E+10 | 0.760168E+09 | 0.383905E+09 | 0.00 | 0.00 |
February | 0.102983E+10 | 0.130227E+10 | 0.886328E+09 | 0.501877E+09 | 0.384451E+09 | 0.00 | 0.00 |
March | 0.150141E+10 | 0.125439E+10 | 0.110956E+10 | 0.527249E+09 | 0.582308E+09 | 0.00 | 0.00 |
April | 0.258995E+10 | 0.612288E+09 | 0.139330E+10 | 0.738458E+09 | 0.654838E+09 | 0.00 | 0.00 |
May | 0.292568E+10 | 0.435388E+09 | 0.143380E+10 | 0.735158E+09 | 0.698645E+09 | 0.00 | 0.00 |
June | 0.349662E+10 | 0.171639E+09 | 0.143145E+10 | 0.772218E+09 | 0.659232E+09 | 0.00 | 0.00 |
July | 0.317184E+10 | 0.135490E+09 | 0.127145E+10 | 0.610754E+09 | 0.660695E+09 | 0.00 | 0.00 |
August | 0.300867E+10 | 0.177987E+09 | 0.122397E+10 | 0.607340E+09 | 0.616627E+09 | 0.00 | 0.00 |
September | 0.247873E+10 | 0.245369E+09 | 0.106442E+10 | 0.460908E+09 | 0.603516E+09 | 0.00 | 0.00 |
October | 0.209761E+10 | 0.836566E+09 | 0.120514E+10 | 0.719123E+09 | 0.486021E+09 | 0.00 | 0.00 |
November | 0.141151E+10 | 0.124131E+10 | 0.102901E+10 | 0.646691E+09 | 0.382315E+09 | 0.00 | 0.00 |
December | 0.128142E+10 | 0.168737E+10 | 0.103393E+10 | 0.672254E+09 | 0.361677E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.265920E+11 | 0.950817E+10 | 0.142264E+11 | 0.775220E+10 | 0.647423E+10 | 0.00 | 0.00 |
Minimum of Months | 0.102983E+10 | 0.135490E+09 | 0.886328E+09 | 0.460908E+09 | 0.361677E+09 | 0.00 | 0.00 |
Maximum of Months | 0.349662E+10 | 0.168737E+10 | 0.143380E+10 | 0.772218E+09 | 0.698645E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.257869E+10 | 0.142735E+10 | 0.178102E+10 | 0.131994E+10 | 0.461083E+09 | 0.00 | 0.00 |
February | 0.130382E+10 | 0.125597E+10 | 0.106374E+10 | 0.624266E+09 | 0.439472E+09 | 0.00 | 0.00 |
March | 0.143126E+10 | 0.128109E+10 | 0.104853E+10 | 0.432478E+09 | 0.616053E+09 | 0.00 | 0.00 |
April | 0.180347E+10 | 0.645529E+09 | 0.956085E+09 | 0.302004E+09 | 0.654081E+09 | 0.00 | 0.00 |
May | 0.168463E+10 | 0.415118E+09 | 0.780737E+09 | 0.110860E+09 | 0.669877E+09 | 0.00 | 0.00 |
June | 0.215950E+10 | 0.127667E+09 | 0.723175E+09 | 88503980.79 | 0.634671E+09 | 0.00 | 0.00 |
July | 0.207424E+10 | 93964946.14 | 0.706145E+09 | 70564670.40 | 0.635580E+09 | 0.00 | 0.00 |
August | 0.209078E+10 | 0.130568E+09 | 0.753612E+09 | 0.154975E+09 | 0.598637E+09 | 0.00 | 0.00 |
September | 0.214390E+10 | 0.204682E+09 | 0.933011E+09 | 0.308543E+09 | 0.624468E+09 | 0.00 | 0.00 |
October | 0.229001E+10 | 0.851523E+09 | 0.137280E+10 | 0.837901E+09 | 0.534895E+09 | 0.00 | 0.00 |
November | 0.213022E+10 | 0.125419E+10 | 0.150781E+10 | 0.105747E+10 | 0.450334E+09 | 0.00 | 0.00 |
December | 0.226601E+10 | 0.168395E+10 | 0.165898E+10 | 0.121905E+10 | 0.439939E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239565E+11 | 0.937159E+10 | 0.132856E+11 | 0.652656E+10 | 0.675909E+10 | 0.00 | 0.00 |
Minimum of Months | 0.130382E+10 | 93964946.14 | 0.706145E+09 | 70564670.40 | 0.439472E+09 | 0.00 | 0.00 |
Maximum of Months | 0.257869E+10 | 0.168395E+10 | 0.178102E+10 | 0.131994E+10 | 0.669877E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770412E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161342347.9 | 81.21 | 0.00 | 0.00 |
February | 0.696172E+10 | -0.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -145753723.5 | 81.21 | 0.00 | 0.00 |
March | 0.770285E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161388461.5 | 81.21 | 0.00 | 0.00 |
April | 0.746480E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156206620.0 | 81.21 | 0.00 | 0.00 |
May | 0.770420E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161411967.4 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156202634.1 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161407948.0 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161407720.1 | 81.21 | 0.00 | 0.00 |
September | 0.746614E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156201104.8 | 81.21 | 0.00 | 0.00 |
October | 0.770285E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161411658.4 | 81.21 | 0.00 | 0.00 |
November | 0.744860E+10 | -0.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156178681.4 | 81.21 | 0.00 | 0.00 |
December | 0.771216E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161306627.6 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907407E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190022E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696172E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161411967.4 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771226E+10 | -0.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145753723.5 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.107700E+12 | -0.105973E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172730E+10 | 81.25 | 0.00 | 0.00 |
February | 0.966512E+11 | -0.950843E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.156695E+10 | 81.25 | 0.00 | 0.00 |
March | 0.103743E+12 | -0.101997E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174661E+10 | 81.25 | 0.00 | 0.00 |
April | 0.954114E+11 | -0.937295E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168194E+10 | 81.24 | 0.00 | 0.00 |
May | 0.930143E+11 | -0.912689E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174531E+10 | 81.24 | 0.00 | 0.00 |
June | 0.856288E+11 | -0.839466E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.168225E+10 | 81.25 | 0.00 | 0.00 |
July | 0.862418E+11 | -0.845147E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172714E+10 | 81.23 | 0.00 | 0.00 |
August | 0.869181E+11 | -0.851923E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172582E+10 | 81.24 | 0.00 | 0.00 |
September | 0.873916E+11 | -0.857220E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.166959E+10 | 81.23 | 0.00 | 0.00 |
October | 0.954879E+11 | -0.937626E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172532E+10 | 81.24 | 0.00 | 0.00 |
November | 0.978035E+11 | -0.961337E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.166979E+10 | 81.24 | 0.00 | 0.00 |
December | 0.105527E+12 | -0.103801E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172547E+10 | 81.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.114152E+13 | -0.112113E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203935E+11 | 81.24 | 0.00 | 0.00 |
Minimum of Months | 0.856288E+11 | -0.105973E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.174661E+10 | 81.23 | 0.00 | 0.00 |
Maximum of Months | 0.107700E+12 | -0.839466E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156695E+10 | 81.25 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.603884E+11 | -0.589243E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146404E+10 | 58.98 | 0.00 | 0.00 |
February | 0.540192E+11 | -0.526874E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.133182E+10 | 58.98 | 0.00 | 0.00 |
March | 0.570369E+11 | -0.555464E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.149058E+10 | 58.98 | 0.00 | 0.00 |
April | 0.508603E+11 | -0.494289E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.143142E+10 | 58.98 | 0.00 | 0.00 |
May | 0.477530E+11 | -0.462641E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148893E+10 | 58.98 | 0.00 | 0.00 |
June | 0.424365E+11 | -0.410050E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.143145E+10 | 58.97 | 0.00 | 0.00 |
July | 0.418685E+11 | -0.404044E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146411E+10 | 58.97 | 0.00 | 0.00 |
August | 0.424950E+11 | -0.410331E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146191E+10 | 58.97 | 0.00 | 0.00 |
September | 0.439334E+11 | -0.425190E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141434E+10 | 58.98 | 0.00 | 0.00 |
October | 0.498502E+11 | -0.483886E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146157E+10 | 58.98 | 0.00 | 0.00 |
November | 0.528961E+11 | -0.514816E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.141450E+10 | 58.98 | 0.00 | 0.00 |
December | 0.585122E+11 | -0.570506E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146159E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.602050E+12 | -0.584733E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.173163E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.418685E+11 | -0.589243E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.149058E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.603884E+11 | -0.404044E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.133182E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.93 | 0.93 | 01-JAN-07:49 | 7548.65 | 38.83 | 306.67 | 291.83 | 1049.88 | 27.72 | 175.83 | 285.67 |
February | 241.00 | 0.93 | 0.93 | 01-FEB-07:49 | 4376.20 | 32.33 | 187.33 | 264.83 | 538.29 | 23.04 | 122.00 | 199.33 |
March | 344.33 | 0.94 | 0.93 | 01-MAR-07:19 | 1012.94 | 19.32 | 11.50 | 321.50 | 384.40 | 20.69 | 124.00 | 245.67 |
April | 380.33 | 0.94 | 0.93 | 01-APR-07:19 | 701.83 | 18.92 | 0.00 | 329.83 | 305.99 | 20.68 | 122.67 | 245.33 |
May | 403.17 | 0.94 | 0.93 | 01-MAY-06:00 | 566.05 | 18.71 | 0.00 | 352.67 | 250.58 | 20.50 | 53.50 | 182.83 |
June | 418.17 | 0.94 | 0.93 | 01-JUN-06:49 | 458.03 | 18.07 | 0.00 | 354.67 | 208.58 | 19.90 | 8.83 | 81.00 |
July | 399.50 | 0.94 | 0.93 | 01-JUL-07:19 | 564.08 | 18.14 | 0.00 | 356.00 | 240.66 | 19.94 | 40.33 | 154.17 |
August | 361.83 | 0.94 | 0.93 | 01-AUG-07:30 | 629.07 | 18.52 | 0.00 | 333.00 | 267.69 | 20.29 | 62.83 | 173.17 |
September | 350.17 | 0.94 | 0.93 | 01-SEP-06:49 | 927.38 | 18.84 | 0.00 | 317.83 | 371.98 | 20.61 | 128.50 | 253.50 |
October | 348.00 | 0.93 | 0.93 | 01-OCT-07:10 | 2543.93 | 25.40 | 135.17 | 318.67 | 414.12 | 21.33 | 111.83 | 263.17 |
November | 288.50 | 0.93 | 0.93 | 01-NOV-07:19 | 7196.60 | 37.59 | 282.50 | 286.00 | 822.19 | 26.25 | 149.50 | 261.50 |
December | 290.67 | 0.93 | 0.93 | 01-DEC-07:40 | 6943.82 | 38.65 | 287.33 | 280.17 | 1201.32 | 28.46 | 172.67 | 271.17 |
Annual Sum or Average | 4135.50 | 0.94 | 2463.19 | 24.24 | 1210.50 | 3807.00 | 470.50 | 22.13 | 1272.50 | 2616.50 | ||
Minimum of Months | 241.00 | 0.93 | 0.93 | 458.03 | 18.07 | 0.00 | 264.83 | 208.58 | 19.90 | 8.83 | 81.00 | |
Maximum of Months | 418.17 | 0.94 | 0.93 | 7548.65 | 38.83 | 306.67 | 356.00 | 1201.32 | 28.46 | 175.83 | 285.67 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.63 | 0.61 | 01-JAN-07:49 | 7971.05 | 38.88 | 306.67 | 294.50 | 1469.74 | 27.24 | 157.17 | 291.50 |
February | 241.00 | 0.63 | 0.61 | 01-FEB-07:49 | 4690.33 | 32.30 | 187.33 | 271.67 | 852.00 | 22.97 | 122.17 | 241.33 |
March | 344.33 | 0.63 | 0.61 | 01-MAR-07:10 | 1228.41 | 19.82 | 15.00 | 336.17 | 600.44 | 21.02 | 161.17 | 300.83 |
April | 380.33 | 0.64 | 0.61 | 01-APR-06:00 | 879.80 | 19.53 | 6.50 | 341.33 | 483.58 | 21.07 | 181.50 | 315.67 |
May | 403.17 | 0.63 | 0.61 | 01-MAY-06:30 | 692.89 | 19.54 | 0.00 | 373.33 | 377.09 | 21.09 | 159.00 | 333.17 |
June | 418.17 | 0.64 | 0.61 | 01-JUN-06:19 | 563.05 | 18.98 | 0.00 | 378.17 | 313.32 | 20.58 | 59.67 | 332.17 |
July | 399.50 | 0.63 | 0.61 | 01-JUL-06:40 | 675.12 | 19.06 | 0.00 | 380.50 | 351.37 | 20.61 | 123.50 | 319.50 |
August | 361.83 | 0.63 | 0.61 | 01-AUG-06:49 | 769.63 | 19.31 | 0.17 | 352.17 | 407.88 | 20.85 | 123.00 | 305.50 |
September | 350.17 | 0.63 | 0.61 | 01-SEP-06:49 | 1118.13 | 19.48 | 10.00 | 330.33 | 562.20 | 21.03 | 172.67 | 299.33 |
October | 348.00 | 0.63 | 0.61 | 01-OCT-06:00 | 2836.22 | 25.50 | 135.17 | 325.00 | 705.54 | 21.33 | 121.50 | 305.17 |
November | 288.50 | 0.62 | 0.61 | 01-NOV-07:19 | 7574.02 | 37.66 | 282.67 | 290.83 | 1200.00 | 25.90 | 140.83 | 274.83 |
December | 290.67 | 0.62 | 0.61 | 01-DEC-07:40 | 7361.07 | 38.71 | 287.67 | 284.50 | 1616.80 | 28.02 | 162.67 | 277.33 |
Annual Sum or Average | 4135.50 | 0.63 | 2689.86 | 24.74 | 1231.17 | 3958.50 | 696.63 | 22.37 | 1684.83 | 3596.33 | ||
Minimum of Months | 241.00 | 0.62 | 0.61 | 563.05 | 18.98 | 0.00 | 271.67 | 313.32 | 20.58 | 59.67 | 241.33 | |
Maximum of Months | 418.17 | 0.64 | 0.61 | 7971.05 | 38.88 | 306.67 | 380.50 | 1616.80 | 28.02 | 181.50 | 333.17 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.84 | 0.80 | 01-JAN-09:20 | 242.49 | 13.26 | 0.00 | 196.50 | 134.54 | 16.92 | 0.00 | 15.67 |
February | 241.00 | 0.83 | 0.80 | 01-FEB-10:30 | 315.97 | 14.16 | 0.00 | 210.00 | 158.01 | 17.58 | 0.00 | 59.00 |
March | 344.33 | 0.82 | 0.80 | 01-MAR-07:40 | 372.30 | 15.40 | 0.00 | 302.83 | 179.12 | 18.67 | 0.00 | 134.83 |
April | 380.33 | 0.82 | 0.80 | 01-APR-07:19 | 417.91 | 16.43 | 0.00 | 339.00 | 213.58 | 19.70 | 11.17 | 215.00 |
May | 403.17 | 0.80 | 0.80 | 01-MAY-06:10 | 522.00 | 18.09 | 23.33 | 391.83 | 272.37 | 21.68 | 75.50 | 324.17 |
June | 418.17 | 0.81 | 0.80 | 01-JUN-05:49 | 556.90 | 19.39 | 60.67 | 401.50 | 304.18 | 23.23 | 119.33 | 310.67 |
July | 399.50 | 0.81 | 0.80 | 01-JUL-05:49 | 541.48 | 18.86 | 47.83 | 399.17 | 280.91 | 22.69 | 101.83 | 295.83 |
August | 361.83 | 0.81 | 0.80 | 01-AUG-06:30 | 434.93 | 16.38 | 0.00 | 354.67 | 213.67 | 19.94 | 16.17 | 181.83 |
September | 350.17 | 0.82 | 0.80 | 01-SEP-06:49 | 431.51 | 15.92 | 0.00 | 321.50 | 204.29 | 19.13 | 0.00 | 186.17 |
October | 348.00 | 0.84 | 0.80 | 01-OCT-07:19 | 286.69 | 14.27 | 0.00 | 224.83 | 148.91 | 17.74 | 0.00 | 60.67 |
November | 288.50 | 0.83 | 0.80 | 01-NOV-07:40 | 271.55 | 13.83 | 0.00 | 210.17 | 142.47 | 17.43 | 0.00 | 29.50 |
December | 290.67 | 0.84 | 0.80 | 01-DEC-08:50 | 251.40 | 13.39 | 0.00 | 191.00 | 135.46 | 17.08 | 0.00 | 13.33 |
Annual Sum or Average | 4135.50 | 0.82 | 400.85 | 16.05 | 131.83 | 3543.00 | 206.28 | 19.59 | 324.00 | 1826.67 | ||
Minimum of Months | 241.00 | 0.80 | 0.80 | 242.49 | 13.26 | 0.00 | 191.00 | 134.54 | 16.92 | 0.00 | 13.33 | |
Maximum of Months | 418.17 | 0.84 | 0.80 | 556.90 | 19.39 | 60.67 | 401.50 | 304.18 | 23.23 | 119.33 | 324.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.84 | 0.80 | 01-JAN-09:20 | 242.49 | 13.26 | 0.00 | 196.50 | 134.54 | 16.92 | 0.00 | 15.67 |
February | 241.00 | 0.83 | 0.80 | 01-FEB-10:30 | 315.97 | 14.16 | 0.00 | 210.00 | 158.01 | 17.58 | 0.00 | 59.00 |
March | 344.33 | 0.82 | 0.80 | 01-MAR-07:40 | 372.30 | 15.40 | 0.00 | 302.83 | 179.12 | 18.67 | 0.00 | 134.83 |
April | 380.33 | 0.82 | 0.80 | 01-APR-07:19 | 417.91 | 16.43 | 0.00 | 339.00 | 213.58 | 19.70 | 11.17 | 215.00 |
May | 403.17 | 0.80 | 0.80 | 01-MAY-06:10 | 522.00 | 18.09 | 23.33 | 391.83 | 272.37 | 21.68 | 75.50 | 324.17 |
June | 418.17 | 0.81 | 0.80 | 01-JUN-05:49 | 556.90 | 19.39 | 60.67 | 401.50 | 304.18 | 23.23 | 119.33 | 310.67 |
July | 399.50 | 0.81 | 0.80 | 01-JUL-05:49 | 541.48 | 18.86 | 47.83 | 399.17 | 280.91 | 22.69 | 101.83 | 295.83 |
August | 361.83 | 0.81 | 0.80 | 01-AUG-06:30 | 434.93 | 16.38 | 0.00 | 354.67 | 213.67 | 19.94 | 16.17 | 181.83 |
September | 350.17 | 0.82 | 0.80 | 01-SEP-06:49 | 431.51 | 15.92 | 0.00 | 321.50 | 204.29 | 19.13 | 0.00 | 186.17 |
October | 348.00 | 0.84 | 0.80 | 01-OCT-07:19 | 286.69 | 14.27 | 0.00 | 224.83 | 148.91 | 17.74 | 0.00 | 60.67 |
November | 288.50 | 0.83 | 0.80 | 01-NOV-07:40 | 271.55 | 13.83 | 0.00 | 210.17 | 142.47 | 17.43 | 0.00 | 29.50 |
December | 290.67 | 0.84 | 0.80 | 01-DEC-08:50 | 251.40 | 13.39 | 0.00 | 191.00 | 135.46 | 17.08 | 0.00 | 13.33 |
Annual Sum or Average | 4135.50 | 0.82 | 400.85 | 16.05 | 131.83 | 3543.00 | 206.28 | 19.59 | 324.00 | 1826.67 | ||
Minimum of Months | 241.00 | 0.80 | 0.80 | 242.49 | 13.26 | 0.00 | 191.00 | 134.54 | 16.92 | 0.00 | 13.33 | |
Maximum of Months | 418.17 | 0.84 | 0.80 | 556.90 | 19.39 | 60.67 | 401.50 | 304.18 | 23.23 | 119.33 | 324.17 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.179099E+11 | 107943.86 | 12-JAN-06:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163900E+11 | 125941.31 | 25-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123889E+11 | 106012.11 | 25-MAR-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.579522E+09 | 92300.84 | 21-APR-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41198910.07 | 13401.96 | 01-MAY-03:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.423339E+10 | 102536.58 | 25-OCT-05:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105801E+11 | 105313.20 | 04-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196442E+11 | 138449.74 | 04-DEC-23:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.817672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.196442E+11 | 138449.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 13709974.90 | 674.69 | 01-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 89566473.90 | 972.18 | 13-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70165983.50 | 898.78 | 27-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 639984.90 | 208.17 | 28-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6761918.15 | 462.21 | 08-NOV-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131201E+09 | 1008.59 | 16-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.312045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131201E+09 | 1008.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3673817.51 | 226.30 | 01-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8554186.22 | 485.79 | 07-DEC-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12228003.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8554186.22 | 485.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 43637932.25 | 667.88 | 01-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 89905176.62 | 433.86 | 13-FEB-05:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 55584865.20 | 558.85 | 27-MAR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11968421.98 | 344.43 | 24-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221730E+09 | 866.45 | 07-DEC-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.422827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.221730E+09 | 866.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 228962.72 | 763.21 | 28-JAN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38908.87 | 129.70 | 02-FEB-02:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 605376.01 | 2017.92 | 30-NOV-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 873247.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 605376.01 | 2017.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2184310.01 | 1210.60 | 09-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285153E+09 | 3326.64 | 12-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137920E+09 | 3935.58 | 27-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6793951.80 | 3078.05 | 25-OCT-06:29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 41237984.29 | 2186.74 | 13-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 79860740.29 | 2531.68 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.553150E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.285153E+09 | 3935.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 33913630.49 | 1810.73 | 02-JAN-07:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 947159.66 | 390.45 | 27-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123311E+09 | 1768.63 | 07-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123311E+09 | 1810.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 652321.83 | 960.34 | 02-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 189590.33 | 251.69 | 27-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 149748.54 | 249.58 | 24-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9013456.58 | 6525.48 | 07-DEC-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10005117.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9013456.58 | 6525.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 672533.33 | 2241.78 | 07-DEC-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 672533.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 672533.33 | 2241.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 114647.01 | 382.16 | 30-NOV-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 114647.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 114647.01 | 382.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 25624.55 | 0.48 | 07-JAN-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18232.78 | 0.48 | 16-FEB-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28479.89 | 0.48 | 29-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46056.85 | 0.48 | 08-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 51734.46 | 0.48 | 28-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79239.35 | 0.48 | 01-JUN-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36776.12 | 0.49 | 12-JUL-18:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35302.66 | 0.49 | 09-AUG-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19996.92 | 0.49 | 18-SEP-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28439.27 | 0.49 | 24-OCT-10:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31588.08 | 0.49 | 03-NOV-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1778060.81 | 290.44 | 07-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2179531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 18232.78 | 0.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1778060.81 | 290.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.402840E+09 | 8865.73 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.792870E+09 | 8765.13 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.535415E+09 | 8832.55 | 26-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6208660.49 | 3551.82 | 17-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4694949.98 | 3265.15 | 01-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1427071.57 | 1742.76 | 13-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2285459.35 | 3164.60 | 29-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2733572.19 | 3185.48 | 05-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3676049.12 | 3487.27 | 04-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90116645.65 | 4958.53 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.291626E+09 | 6193.23 | 24-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121702E+10 | 8909.59 | 07-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1427071.57 | 1742.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121702E+10 | 8909.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.930453E+09 | 8999.40 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126601E+10 | 8851.77 | 09-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.747403E+09 | 8868.70 | 26-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9904375.63 | 3720.75 | 10-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4789297.36 | 3258.10 | 01-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1149102.03 | 1515.03 | 13-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2123958.03 | 3202.14 | 29-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2894060.65 | 3075.21 | 05-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4735547.83 | 3480.27 | 04-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186387E+09 | 8794.46 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.637009E+09 | 8915.48 | 23-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221473E+10 | 9014.35 | 07-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.600758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1149102.03 | 1515.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.221473E+10 | 9014.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.288999E+10 | 50381.37 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268435E+10 | 50140.35 | 03-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165328E+10 | 50409.77 | 27-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107028E+09 | 35170.21 | 26-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100388E+09 | 36856.50 | 15-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15293331.77 | 15014.79 | 30-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16908677.77 | 30059.96 | 27-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 25885691.78 | 35307.17 | 24-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43976311.45 | 32108.48 | 29-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.357126E+09 | 31846.88 | 31-OCT-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197147E+10 | 50491.28 | 24-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797699E+10 | 51287.53 | 07-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15293331.77 | 15014.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.797699E+10 | 51287.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.459466E+09 | 3216.63 | 11-JAN-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.742644E+09 | 8528.54 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.498582E+09 | 5509.57 | 07-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2873748.75 | 2969.44 | 29-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 480500.61 | 2883.50 | 26-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 226008.05 | 1361.21 | 04-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 472461.69 | 1764.29 | 03-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82314625.98 | 2623.21 | 30-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.340870E+09 | 4060.81 | 25-NOV-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120480E+10 | 7905.81 | 11-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.333273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120480E+10 | 8528.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.949227E+09 | 8532.73 | 01-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110035E+10 | 8536.14 | 04-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.673549E+09 | 6971.98 | 07-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7039657.78 | 3050.74 | 29-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 462936.15 | 2924.19 | 26-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 204349.69 | 1399.36 | 04-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 553020.20 | 1723.88 | 03-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159928E+09 | 3676.40 | 25-OCT-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.679529E+09 | 6601.40 | 23-NOV-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208912E+10 | 8591.45 | 07-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208912E+10 | 8591.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.249302E+09 | 2651.02 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.392381E+09 | 2617.16 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270450E+09 | 2645.28 | 26-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7487740.92 | 940.22 | 24-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1248793.47 | 984.74 | 13-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 344943.43 | 488.87 | 13-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 596560.48 | 682.73 | 18-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 637468.56 | 811.59 | 05-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1200810.65 | 798.91 | 30-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74448379.70 | 2612.61 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194843E+09 | 2632.40 | 23-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.558096E+09 | 2665.19 | 07-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 344943.43 | 488.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.558096E+09 | 2665.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.470319E+09 | 2665.76 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.570425E+09 | 2641.22 | 09-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356144E+09 | 2649.59 | 26-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11111431.13 | 1034.91 | 24-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1272030.34 | 898.95 | 13-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 257261.36 | 429.75 | 13-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 548524.47 | 732.65 | 29-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 677745.56 | 852.42 | 05-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1364125.80 | 852.14 | 30-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125048E+09 | 2631.35 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.351112E+09 | 2670.77 | 23-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.914896E+09 | 2670.80 | 16-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 257261.36 | 429.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.914896E+09 | 2670.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.195551E+09 | 2712.92 | 02-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.622973E+09 | 12171.02 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.578964E+09 | 12260.62 | 27-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16230530.26 | 4652.36 | 10-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8945989.92 | 4561.60 | 08-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6380589.07 | 4621.40 | 21-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6480488.22 | 4917.46 | 24-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7172625.81 | 4807.37 | 17-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5112550.04 | 4342.85 | 29-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 70431001.96 | 4641.43 | 01-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200365E+09 | 4040.59 | 24-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.761320E+09 | 4454.54 | 17-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5112550.04 | 2712.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.761320E+09 | 12260.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.111591E+12 | 0.111136E+12 | 182073.33 | 31-JAN-16:40 | 182073.33 | 0.02 |
February | 0.00 | 0.00 | 0.273384E+11 | 0.273197E+11 | 112153.73 | 18-FEB-14:00 | 112153.73 | 0.12 |
March | 0.00 | 0.00 | 0.119887E+12 | 0.119887E+12 | 199609.91 | 20-MAR-18:10 | 199609.91 | 0.06 |
April | 0.00 | 0.00 | 0.327386E+12 | 0.327386E+12 | 268555.58 | 14-APR-20:10 | 268555.58 | 0.03 |
May | 0.00 | 0.00 | 0.425765E+12 | 0.425765E+12 | 280605.53 | 31-MAY-18:05 | 280605.53 | 0.01 |
June | 0.00 | 0.00 | 0.544608E+12 | 0.543691E+12 | 350196.78 | 17-JUN-17:17 | 286583.90 | 0.25 |
July | 0.00 | 0.00 | 0.633802E+12 | 0.555481E+12 | 421126.12 | 13-JUL-21:00 | 247784.56 | 0.80 |
August | 0.00 | 0.00 | 0.616988E+12 | 0.546295E+12 | 452169.98 | 18-AUG-22:00 | 211422.77 | 0.86 |
September | 0.00 | 0.00 | 0.565901E+12 | 0.489402E+12 | 482812.48 | 10-SEP-19:20 | 201188.21 | 0.86 |
October | 0.00 | 0.00 | 0.290091E+12 | 0.281960E+12 | 347052.84 | 02-OCT-20:00 | 259729.68 | 0.26 |
November | 0.00 | 0.00 | 0.128100E+12 | 0.113732E+12 | 207086.46 | 01-NOV-18:04 | 207086.46 | 0.21 |
December | 0.00 | 0.00 | 0.605304E+11 | 0.605304E+11 | 162336.27 | 25-DEC-13:00 | 162336.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.385199E+13 | 0.360258E+13 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 0.273384E+11 | 0.273197E+11 | 112153.73 | 112153.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.633802E+12 | 0.555481E+12 | 482812.48 | 286583.90 | 0.86 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.198588E+11 | 0.197255E+11 | 28113.38 | 31-JAN-16:01 | 28113.38 | 0.02 |
February | 0.00 | 0.00 | 0.520638E+10 | 0.520638E+10 | 23245.80 | 18-FEB-14:00 | 23245.80 | 0.10 |
March | 0.00 | 0.00 | 0.212817E+11 | 0.212817E+11 | 28620.15 | 16-MAR-15:02 | 28620.15 | 0.05 |
April | 0.00 | 0.00 | 0.506605E+11 | 0.506605E+11 | 32711.12 | 14-APR-15:00 | 32711.12 | 0.01 |
May | 0.00 | 0.00 | 0.642412E+11 | 0.642412E+11 | 33351.04 | 31-MAY-17:40 | 33351.04 | 0.01 |
June | 0.00 | 0.00 | 0.748094E+11 | 0.747128E+11 | 41459.59 | 17-JUN-16:00 | 34470.08 | 0.11 |
July | 0.00 | 0.00 | 0.886398E+11 | 0.766701E+11 | 50861.44 | 13-JUL-18:02 | 28087.03 | 0.77 |
August | 0.00 | 0.00 | 0.877525E+11 | 0.756168E+11 | 53667.54 | 05-AUG-08:00 | 24051.13 | 0.85 |
September | 0.00 | 0.00 | 0.820432E+11 | 0.691968E+11 | 57485.13 | 04-SEP-08:61 | 23263.16 | 0.79 |
October | 0.00 | 0.00 | 0.443045E+11 | 0.428084E+11 | 45579.85 | 03-OCT-05:00 | 23302.79 | 0.25 |
November | 0.00 | 0.00 | 0.227731E+11 | 0.196436E+11 | 43952.06 | 12-NOV-14:30 | 21062.33 | 0.21 |
December | 0.00 | 0.00 | 0.111635E+11 | 0.111635E+11 | 26310.78 | 25-DEC-16:00 | 26310.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.572735E+12 | 0.530927E+12 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 0.520638E+10 | 0.520638E+10 | 23245.80 | 21062.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.886398E+11 | 0.766701E+11 | 57485.13 | 34470.08 | 0.85 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.318585E+10 | 0.305643E+10 | 16162.35 | 14-JAN-16:02 | 16162.35 | 0.07 |
February | 0.00 | 0.00 | 0.997826E+09 | 0.835567E+09 | 15395.95 | 22-FEB-16:01 | 15395.95 | 0.13 |
March | 0.00 | 0.00 | 0.245727E+10 | 0.215335E+10 | 16192.18 | 18-MAR-15:02 | 16192.18 | 0.17 |
April | 0.00 | 0.00 | 0.845913E+10 | 0.832734E+10 | 16191.97 | 25-APR-18:01 | 16191.97 | 0.05 |
May | 0.00 | 0.00 | 0.101774E+11 | 0.101331E+11 | 16181.57 | 10-MAY-18:01 | 16181.57 | 0.01 |
June | 0.00 | 0.00 | 0.134518E+11 | 0.128553E+11 | 16196.63 | 01-JUN-18:02 | 16196.63 | 0.23 |
July | 0.00 | 0.00 | 0.132264E+11 | 0.973688E+10 | 17469.17 | 15-JUL-08:61 | 13934.53 | 0.76 |
August | 0.00 | 0.00 | 0.129985E+11 | 0.931959E+10 | 17650.86 | 05-AUG-08:61 | 13043.49 | 0.83 |
September | 0.00 | 0.00 | 0.112370E+11 | 0.768271E+10 | 18370.54 | 04-SEP-08:61 | 12525.80 | 0.86 |
October | 0.00 | 0.00 | 0.685331E+10 | 0.574901E+10 | 16769.37 | 03-OCT-08:62 | 14228.45 | 0.31 |
November | 0.00 | 0.00 | 0.329720E+10 | 0.272583E+10 | 16417.51 | 13-NOV-16:01 | 12616.22 | 0.24 |
December | 0.00 | 0.00 | 0.148865E+10 | 0.148737E+10 | 16058.86 | 25-DEC-16:02 | 16058.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.878304E+11 | 0.740625E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.997826E+09 | 0.835567E+09 | 15395.95 | 12525.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.134518E+11 | 0.128553E+11 | 18370.54 | 16196.63 | 0.86 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.121057E+10 | 0.117117E+10 | 16047.37 | 14-JAN-16:02 | 16047.37 | 0.03 |
February | 0.00 | 0.00 | 0.352383E+09 | 0.311162E+09 | 15286.06 | 22-FEB-16:01 | 15286.06 | 0.05 |
March | 0.00 | 0.00 | 0.164078E+10 | 0.145187E+10 | 16076.28 | 18-MAR-15:02 | 16076.28 | 0.12 |
April | 0.00 | 0.00 | 0.739021E+10 | 0.726509E+10 | 16077.28 | 25-APR-18:01 | 16077.28 | 0.05 |
May | 0.00 | 0.00 | 0.989788E+10 | 0.985382E+10 | 16066.97 | 18-MAY-08:61 | 16066.97 | 0.01 |
June | 0.00 | 0.00 | 0.136168E+11 | 0.130270E+11 | 16082.16 | 25-JUN-08:61 | 16082.16 | 0.23 |
July | 0.00 | 0.00 | 0.131743E+11 | 0.971880E+10 | 17168.74 | 15-JUL-08:61 | 13943.59 | 0.76 |
August | 0.00 | 0.00 | 0.123447E+11 | 0.870720E+10 | 17735.72 | 28-AUG-18:02 | 13236.04 | 0.82 |
September | 0.00 | 0.00 | 0.100701E+11 | 0.660706E+10 | 18043.92 | 04-SEP-08:61 | 12524.42 | 0.85 |
October | 0.00 | 0.00 | 0.496514E+10 | 0.396807E+10 | 16631.64 | 03-OCT-08:62 | 14033.86 | 0.29 |
November | 0.00 | 0.00 | 0.153138E+10 | 0.115898E+10 | 16476.42 | 13-NOV-16:01 | 12415.39 | 0.18 |
December | 0.00 | 0.00 | 0.386656E+09 | 0.386643E+09 | 15945.23 | 25-DEC-16:02 | 15945.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.765810E+11 | 0.636268E+11 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 0.352383E+09 | 0.311162E+09 | 15286.06 | 12415.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.136168E+11 | 0.130270E+11 | 18043.92 | 16082.16 | 0.85 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.330584E+11 | 0.327276E+11 | 45145.39 | 14-JAN-13:50 | 45145.39 | 0.02 |
February | 0.00 | 0.00 | 0.834135E+10 | 0.795809E+10 | 35316.13 | 01-FEB-15:30 | 35316.13 | 0.04 |
March | 0.00 | 0.00 | 0.808011E+10 | 0.777595E+10 | 30489.27 | 18-MAR-13:50 | 27433.33 | 0.02 |
April | 0.00 | 0.00 | 0.290360E+11 | 0.290317E+11 | 32671.32 | 14-APR-13:40 | 32671.32 | 0.00 |
May | 0.00 | 0.00 | 0.290738E+11 | 0.290738E+11 | 25700.43 | 09-MAY-17:12 | 25700.43 | 0.00 |
June | 0.00 | 0.00 | 0.436688E+11 | 0.417766E+11 | 34698.02 | 17-JUN-18:00 | 26448.78 | 0.10 |
July | 0.00 | 0.00 | 0.464737E+11 | 0.291904E+11 | 33471.84 | 21-JUL-20:20 | 26336.85 | 0.76 |
August | 0.00 | 0.00 | 0.496870E+11 | 0.318723E+11 | 42003.96 | 28-AUG-12:40 | 37111.84 | 0.82 |
September | 0.00 | 0.00 | 0.496719E+11 | 0.341505E+11 | 45063.74 | 28-SEP-13:40 | 45063.74 | 0.76 |
October | 0.00 | 0.00 | 0.389375E+11 | 0.339561E+11 | 46300.43 | 18-OCT-13:50 | 46300.43 | 0.25 |
November | 0.00 | 0.00 | 0.264395E+11 | 0.246681E+11 | 47994.99 | 20-NOV-14:30 | 47994.99 | 0.13 |
December | 0.00 | 0.00 | 0.225500E+11 | 0.225317E+11 | 44726.61 | 25-DEC-13:40 | 44726.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.385018E+12 | 0.324713E+12 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 0.808011E+10 | 0.777595E+10 | 25700.43 | 25700.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.496870E+11 | 0.417766E+11 | 47994.99 | 47994.99 | 0.82 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.569310E+10 | 0.518570E+10 | 87479.22 | 27-JAN-16:01 | 87479.22 | 0.05 |
February | 0.00 | 0.00 | 0.398629E+10 | 0.202577E+10 | 79923.10 | 18-FEB-09:02 | 70181.08 | 0.24 |
March | 0.00 | 0.00 | 0.117544E+11 | 0.986548E+10 | 93212.72 | 15-MAR-18:01 | 93212.72 | 0.18 |
April | 0.00 | 0.00 | 0.367336E+11 | 0.360688E+11 | 96908.64 | 25-APR-18:01 | 96908.64 | 0.05 |
May | 0.00 | 0.00 | 0.525062E+11 | 0.522484E+11 | 96843.06 | 10-MAY-18:01 | 96843.06 | 0.01 |
June | 0.00 | 0.00 | 0.744244E+11 | 0.712008E+11 | 96947.28 | 03-JUN-08:61 | 96947.28 | 0.21 |
July | 0.00 | 0.00 | 0.787533E+11 | 0.598968E+11 | 97419.23 | 09-JUL-08:61 | 87295.41 | 0.68 |
August | 0.00 | 0.00 | 0.715695E+11 | 0.514060E+11 | 112511.59 | 28-AUG-18:02 | 77107.39 | 0.72 |
September | 0.00 | 0.00 | 0.607458E+11 | 0.411093E+11 | 105034.57 | 04-SEP-08:61 | 76762.94 | 0.73 |
October | 0.00 | 0.00 | 0.285439E+11 | 0.230561E+11 | 96941.78 | 05-OCT-18:01 | 96941.78 | 0.24 |
November | 0.00 | 0.00 | 0.893234E+10 | 0.574244E+10 | 88218.44 | 20-NOV-16:01 | 88218.44 | 0.20 |
December | 0.00 | 0.00 | 0.212456E+10 | 0.210124E+10 | 78586.50 | 23-DEC-09:02 | 78586.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.435767E+12 | 0.359907E+12 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.212456E+10 | 0.202577E+10 | 78586.50 | 70181.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.787533E+11 | 0.712008E+11 | 112511.59 | 96947.28 | 0.73 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.300043E+10 | 0.287421E+10 | 14127.94 | 14-JAN-16:02 | 14127.94 | 0.08 |
February | 0.00 | 0.00 | 0.119198E+10 | 0.944717E+09 | 13457.26 | 22-FEB-16:01 | 13457.26 | 0.17 |
March | 0.00 | 0.00 | 0.256296E+10 | 0.222209E+10 | 14154.34 | 18-MAR-15:02 | 14154.34 | 0.19 |
April | 0.00 | 0.00 | 0.856871E+10 | 0.844488E+10 | 14154.55 | 25-APR-18:01 | 14154.55 | 0.06 |
May | 0.00 | 0.00 | 0.105066E+11 | 0.104674E+11 | 14144.93 | 18-MAY-08:61 | 14144.93 | 0.02 |
June | 0.00 | 0.00 | 0.137799E+11 | 0.133100E+11 | 14158.39 | 01-JUN-18:02 | 14158.39 | 0.24 |
July | 0.00 | 0.00 | 0.141206E+11 | 0.108024E+11 | 14559.61 | 09-JUL-08:61 | 12493.44 | 0.78 |
August | 0.00 | 0.00 | 0.137421E+11 | 0.102492E+11 | 15244.45 | 04-AUG-08:62 | 11045.27 | 0.85 |
September | 0.00 | 0.00 | 0.116497E+11 | 0.823825E+10 | 15338.04 | 03-SEP-15:02 | 12119.84 | 0.88 |
October | 0.00 | 0.00 | 0.712733E+10 | 0.606386E+10 | 14158.70 | 05-OCT-18:01 | 14158.70 | 0.33 |
November | 0.00 | 0.00 | 0.301200E+10 | 0.253165E+10 | 14137.30 | 20-NOV-16:01 | 14137.30 | 0.23 |
December | 0.00 | 0.00 | 0.150789E+10 | 0.150014E+10 | 14037.71 | 25-DEC-16:02 | 14037.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.907702E+11 | 0.776487E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 0.119198E+10 | 0.944717E+09 | 13457.26 | 11045.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.141206E+11 | 0.133100E+11 | 15338.04 | 14158.70 | 0.88 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.980001E+09 | 0.912336E+09 | 14024.96 | 31-JAN-16:01 | 14024.96 | 0.05 |
February | 0.00 | 0.00 | 0.416123E+09 | 0.271522E+09 | 12502.41 | 22-FEB-16:01 | 12502.41 | 0.10 |
March | 0.00 | 0.00 | 0.167905E+10 | 0.142803E+10 | 14055.31 | 18-MAR-15:02 | 14055.31 | 0.15 |
April | 0.00 | 0.00 | 0.745111E+10 | 0.732987E+10 | 14056.83 | 25-APR-18:01 | 14056.83 | 0.06 |
May | 0.00 | 0.00 | 0.102191E+11 | 0.101800E+11 | 14047.43 | 18-MAY-08:61 | 14047.43 | 0.02 |
June | 0.00 | 0.00 | 0.139427E+11 | 0.134842E+11 | 14061.39 | 20-JUN-18:02 | 14061.39 | 0.24 |
July | 0.00 | 0.00 | 0.140619E+11 | 0.107524E+11 | 14407.84 | 09-JUL-08:61 | 12437.50 | 0.78 |
August | 0.00 | 0.00 | 0.130875E+11 | 0.955559E+10 | 15424.95 | 28-AUG-18:02 | 11618.59 | 0.84 |
September | 0.00 | 0.00 | 0.104763E+11 | 0.707363E+10 | 15382.60 | 03-SEP-15:02 | 11943.24 | 0.88 |
October | 0.00 | 0.00 | 0.513203E+10 | 0.413438E+10 | 14061.32 | 05-OCT-18:01 | 14061.32 | 0.31 |
November | 0.00 | 0.00 | 0.126828E+10 | 0.963572E+09 | 14039.10 | 20-NOV-16:01 | 14039.10 | 0.17 |
December | 0.00 | 0.00 | 0.326451E+09 | 0.324345E+09 | 13392.13 | 25-DEC-16:02 | 13392.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.790405E+11 | 0.664100E+11 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.326451E+09 | 0.271522E+09 | 12502.41 | 11618.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.140619E+11 | 0.134842E+11 | 15424.95 | 14061.39 | 0.88 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.668588E+09 | 0.651825E+09 | 4291.11 | 14-JAN-16:02 | 4291.11 | 0.05 |
February | 0.00 | 0.00 | 0.197808E+09 | 0.174850E+09 | 4087.64 | 22-FEB-16:01 | 4087.64 | 0.08 |
March | 0.00 | 0.00 | 0.532917E+09 | 0.474895E+09 | 4299.10 | 18-MAR-15:02 | 4299.10 | 0.13 |
April | 0.00 | 0.00 | 0.206197E+10 | 0.202866E+10 | 4298.94 | 25-APR-18:01 | 4298.94 | 0.05 |
May | 0.00 | 0.00 | 0.254770E+10 | 0.253538E+10 | 4296.15 | 10-MAY-18:01 | 4296.15 | 0.02 |
June | 0.00 | 0.00 | 0.353714E+10 | 0.337068E+10 | 4300.31 | 23-JUN-08:61 | 4300.31 | 0.23 |
July | 0.00 | 0.00 | 0.345025E+10 | 0.252889E+10 | 4763.26 | 15-JUL-08:61 | 3623.09 | 0.76 |
August | 0.00 | 0.00 | 0.336392E+10 | 0.240055E+10 | 4821.78 | 05-AUG-08:61 | 3351.78 | 0.83 |
September | 0.00 | 0.00 | 0.282153E+10 | 0.189386E+10 | 5061.59 | 04-SEP-08:61 | 3122.53 | 0.86 |
October | 0.00 | 0.00 | 0.157760E+10 | 0.130245E+10 | 4608.30 | 03-OCT-08:62 | 3654.01 | 0.30 |
November | 0.00 | 0.00 | 0.672990E+09 | 0.566229E+09 | 4399.61 | 13-NOV-16:01 | 3325.22 | 0.18 |
December | 0.00 | 0.00 | 0.301949E+09 | 0.301949E+09 | 4263.62 | 25-DEC-16:02 | 4263.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.217344E+11 | 0.182302E+11 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 0.197808E+09 | 0.174850E+09 | 4087.64 | 3122.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.353714E+10 | 0.337068E+10 | 5061.59 | 4300.31 | 0.86 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.224364E+09 | 0.222246E+09 | 4257.25 | 14-JAN-16:02 | 4257.25 | 0.01 |
February | 0.00 | 0.00 | 65767917.60 | 60179316.31 | 4055.27 | 22-FEB-16:01 | 4055.27 | 0.02 |
March | 0.00 | 0.00 | 0.342457E+09 | 0.307900E+09 | 4265.22 | 18-MAR-15:02 | 4265.22 | 0.09 |
April | 0.00 | 0.00 | 0.178731E+10 | 0.175653E+10 | 4265.25 | 25-APR-18:01 | 4265.25 | 0.05 |
May | 0.00 | 0.00 | 0.247560E+10 | 0.246332E+10 | 4262.50 | 08-MAY-08:61 | 4262.50 | 0.02 |
June | 0.00 | 0.00 | 0.357859E+10 | 0.341114E+10 | 4266.67 | 23-JUN-08:61 | 4266.67 | 0.23 |
July | 0.00 | 0.00 | 0.343686E+10 | 0.252138E+10 | 4679.31 | 15-JUL-08:61 | 3623.32 | 0.76 |
August | 0.00 | 0.00 | 0.319431E+10 | 0.223722E+10 | 4810.03 | 28-AUG-18:02 | 3446.86 | 0.83 |
September | 0.00 | 0.00 | 0.251876E+10 | 0.161683E+10 | 4959.40 | 04-SEP-08:61 | 3122.19 | 0.85 |
October | 0.00 | 0.00 | 0.111220E+10 | 0.864799E+09 | 4539.69 | 03-OCT-08:62 | 3545.38 | 0.27 |
November | 0.00 | 0.00 | 0.275237E+09 | 0.216389E+09 | 4321.42 | 13-NOV-16:01 | 3206.60 | 0.12 |
December | 0.00 | 0.00 | 71618469.97 | 71586019.37 | 4230.17 | 25-DEC-16:02 | 4230.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.190831E+11 | 0.157495E+11 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 65767917.60 | 60179316.31 | 4055.27 | 3122.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.357859E+10 | 0.341114E+10 | 4959.40 | 4266.67 | 0.85 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.921552E+10 | 0.890466E+10 | 18831.10 | 14-JAN-16:02 | 18831.10 | 0.12 |
February | 0.00 | 0.00 | 0.354369E+10 | 0.294074E+10 | 17934.76 | 22-FEB-16:01 | 17934.76 | 0.27 |
March | 0.00 | 0.00 | 0.438053E+10 | 0.383740E+10 | 18863.86 | 18-MAR-15:02 | 18863.86 | 0.23 |
April | 0.00 | 0.00 | 0.101656E+11 | 0.998560E+10 | 18864.30 | 25-APR-18:01 | 18864.30 | 0.06 |
May | 0.00 | 0.00 | 0.108225E+11 | 0.107603E+11 | 18851.84 | 10-MAY-18:01 | 18851.84 | 0.02 |
June | 0.00 | 0.00 | 0.146313E+11 | 0.137855E+11 | 18866.69 | 19-JUN-15:02 | 18866.69 | 0.26 |
July | 0.00 | 0.00 | 0.160928E+11 | 0.118393E+11 | 20104.31 | 15-JUL-08:61 | 16426.91 | 0.76 |
August | 0.00 | 0.00 | 0.166863E+11 | 0.121795E+11 | 21028.35 | 05-AUG-08:61 | 14962.70 | 0.83 |
September | 0.00 | 0.00 | 0.159186E+11 | 0.114454E+11 | 21845.36 | 04-SEP-08:61 | 14378.11 | 0.89 |
October | 0.00 | 0.00 | 0.117827E+11 | 0.103328E+11 | 19575.81 | 03-OCT-08:62 | 16590.65 | 0.33 |
November | 0.00 | 0.00 | 0.807520E+10 | 0.720237E+10 | 18974.70 | 13-NOV-16:01 | 14756.69 | 0.27 |
December | 0.00 | 0.00 | 0.660210E+10 | 0.658636E+10 | 18708.77 | 25-DEC-16:02 | 18708.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.127917E+12 | 0.109800E+12 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 0.354369E+10 | 0.294074E+10 | 17934.76 | 14378.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.166863E+11 | 0.137855E+11 | 21845.36 | 18866.69 | 0.89 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 9048.62 | 125985.40 | 01-JAN-23:25 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 10224.37 | 116799.26 | 02-FEB-03:40 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 6630.43 | 121354.52 | 30-MAR-06:32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 280.11 | 91916.92 | 21-APR-03:56 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 63.03 | 43121.14 | 15-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.99 | 12704.33 | 30-JUN-08:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 10.94 | 24925.24 | 27-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 14.36 | 29949.04 | 24-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.95 | 29736.66 | 29-SEP-08:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1987.15 | 113264.46 | 25-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 5827.58 | 122727.45 | 18-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 13708.56 | 155439.89 | 17-DEC-09:01 |
Annual Sum or Average | 0.00 | 3961.25 | ||||
Minimum of Months | 0.00 | 0.00 | 9.99 | 12704.33 | ||
Maximum of Months | 0.00 | 0.00 | 13708.56 | 155439.89 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 75181.67 | 420019.29 | 31-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 24892.27 | 257693.03 | 22-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 69670.52 | 426095.70 | 15-MAR-18:01 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 195349.90 | 498331.73 | 14-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 241294.02 | 508050.65 | 31-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 321300.91 | 581996.87 | 17-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 352809.58 | 669449.90 | 13-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 343917.45 | 618594.23 | 09-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 324872.72 | 663077.76 | 10-SEP-20:40 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 170508.07 | 557201.50 | 01-OCT-18:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 83821.30 | 423443.06 | 20-NOV-16:01 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 43787.44 | 371007.71 | 25-DEC-16:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 188135.78 | 0.00 | ||||
Minimum of Months | 24892.27 | 257693.03 | 0.00 | 0.00 | ||
Maximum of Months | 352809.58 | 669449.90 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 23542.84 | 53917.80 | 23-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 23325.26 | 57289.21 | 08-FEB-07:01 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 22301.57 | 52072.06 | 25-MAR-07:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20648.91 | 43489.08 | 21-APR-06:25 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 18861.19 | 39398.86 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17412.75 | 35832.23 | 01-JUN-06:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16681.21 | 33439.17 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16914.58 | 34388.99 | 31-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 17995.36 | 37196.95 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 19646.90 | 46691.92 | 13-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21422.87 | 49574.57 | 04-NOV-07:41 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 22847.73 | 53735.86 | 29-DEC-08:61 |
Annual Sum or Average | 0.00 | 20115.56 | ||||
Minimum of Months | 0.00 | 0.00 | 16681.21 | 33439.17 | ||
Maximum of Months | 0.00 | 0.00 | 23542.84 | 57289.21 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 0.97 | 2194.93 | 01-JAN-00:01 | 0.97 |
February | 0.530997E+10 | 0.96 | 2194.93 | 01-FEB-00:10 | 0.97 |
March | 0.587890E+10 | 0.96 | 2194.93 | 01-MAR-00:05 | 0.96 |
April | 0.568926E+10 | 0.97 | 2194.93 | 01-APR-00:10 | 0.97 |
May | 0.587890E+10 | 0.97 | 2194.93 | 01-MAY-00:10 | 0.97 |
June | 0.568926E+10 | 0.97 | 2194.93 | 01-JUN-00:10 | 0.97 |
July | 0.587890E+10 | 0.96 | 2194.93 | 01-JUL-00:10 | 0.96 |
August | 0.587890E+10 | 0.96 | 2194.93 | 01-AUG-00:10 | 0.96 |
September | 0.568926E+10 | 0.96 | 2194.93 | 01-SEP-00:10 | 0.96 |
October | 0.587890E+10 | 0.96 | 2194.93 | 01-OCT-00:10 | 0.96 |
November | 0.568926E+10 | 0.96 | 2194.93 | 01-NOV-00:10 | 0.96 |
December | 0.587890E+10 | 0.97 | 2194.93 | 01-DEC-00:10 | 0.97 |
Annual Sum or Average | 0.692193E+11 | 0.96 | |||
Minimum of Months | 0.530997E+10 | 0.96 | 2194.93 | 0.96 | |
Maximum of Months | 0.587890E+10 | 0.97 | 2194.93 | 0.97 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.382663E+11 | 0.89 | 40133.88 | 13-JAN-04:03 | 1.65 |
February | 0.322933E+11 | 0.85 | 39505.15 | 04-FEB-06:22 | 1.63 |
March | 0.359654E+11 | 0.86 | 35201.07 | 24-MAR-05:03 | 1.52 |
April | 0.390802E+11 | 0.92 | 36314.87 | 14-APR-21:10 | 1.55 |
May | 0.424525E+11 | 0.94 | 34392.73 | 19-MAY-21:10 | 1.50 |
June | 0.468266E+11 | 1.01 | 39952.11 | 29-JUN-21:10 | 1.64 |
July | 0.489065E+11 | 1.01 | 42080.93 | 07-JUL-21:10 | 1.70 |
August | 0.495433E+11 | 1.01 | 42998.31 | 25-AUG-21:10 | 1.72 |
September | 0.478399E+11 | 1.01 | 44919.18 | 08-SEP-21:20 | 1.75 |
October | 0.439060E+11 | 0.96 | 43342.79 | 06-OCT-21:10 | 1.73 |
November | 0.390295E+11 | 0.91 | 39505.15 | 05-NOV-06:35 | 1.64 |
December | 0.389823E+11 | 0.90 | 43350.20 | 04-DEC-22:45 | 1.74 |
Annual Sum or Average | 0.503092E+12 | 0.94 | |||
Minimum of Months | 0.322933E+11 | 0.85 | 34392.73 | 1.50 | |
Maximum of Months | 0.495433E+11 | 1.01 | 44919.18 | 1.75 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.29 | 76.61 | 01-JAN-00:01 | 0.29 |
February | 0.185347E+09 | 0.29 | 76.61 | 01-FEB-00:10 | 0.29 |
March | 0.205205E+09 | 0.29 | 76.61 | 01-MAR-00:05 | 0.29 |
April | 0.198586E+09 | 0.29 | 76.61 | 01-APR-00:10 | 0.29 |
May | 0.205205E+09 | 0.29 | 76.61 | 01-MAY-00:10 | 0.29 |
June | 0.198586E+09 | 0.29 | 76.61 | 01-JUN-00:10 | 0.29 |
July | 0.205205E+09 | 0.29 | 76.61 | 01-JUL-00:10 | 0.29 |
August | 0.205205E+09 | 0.29 | 76.61 | 01-AUG-00:10 | 0.29 |
September | 0.198586E+09 | 0.29 | 76.61 | 01-SEP-00:10 | 0.29 |
October | 0.205205E+09 | 0.29 | 76.61 | 01-OCT-00:10 | 0.29 |
November | 0.198586E+09 | 0.29 | 76.61 | 01-NOV-00:10 | 0.29 |
December | 0.205205E+09 | 0.29 | 76.61 | 01-DEC-00:10 | 0.29 |
Annual Sum or Average | 0.241613E+10 | 0.29 | |||
Minimum of Months | 0.185347E+09 | 0.29 | 76.61 | 0.29 | |
Maximum of Months | 0.205205E+09 | 0.29 | 76.61 | 0.29 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.21 | 612.92 | 01-JAN-07:10 | 0.29 |
February | 0.105030E+10 | 0.21 | 612.92 | 01-FEB-07:05 | 0.29 |
March | 0.116283E+10 | 0.21 | 612.92 | 01-MAR-07:03 | 0.29 |
April | 0.112532E+10 | 0.21 | 612.92 | 01-APR-06:05 | 0.29 |
May | 0.116283E+10 | 0.21 | 612.92 | 01-MAY-06:05 | 0.29 |
June | 0.112532E+10 | 0.21 | 612.92 | 01-JUN-06:05 | 0.29 |
July | 0.116283E+10 | 0.21 | 612.92 | 01-JUL-06:05 | 0.29 |
August | 0.116283E+10 | 0.21 | 612.92 | 01-AUG-06:05 | 0.29 |
September | 0.112532E+10 | 0.21 | 612.92 | 01-SEP-06:05 | 0.29 |
October | 0.116283E+10 | 0.21 | 612.92 | 01-OCT-06:10 | 0.29 |
November | 0.112532E+10 | 0.21 | 612.92 | 01-NOV-06:05 | 0.29 |
December | 0.116283E+10 | 0.21 | 612.92 | 01-DEC-07:03 | 0.29 |
Annual Sum or Average | 0.136914E+11 | 0.21 | |||
Minimum of Months | 0.105030E+10 | 0.21 | 612.92 | 0.29 | |
Maximum of Months | 0.116283E+10 | 0.21 | 612.92 | 0.29 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.236186E+09 | 0.54 | 866.85 | 01-JAN-09:01 | 0.63 |
February | 0.141488E+09 | 0.47 | 866.85 | 01-FEB-16:01 | 0.64 |
March | 0.206697E+09 | 0.50 | 866.85 | 02-MAR-16:01 | 0.63 |
April | 0.469260E+09 | 0.59 | 866.85 | 01-APR-15:02 | 0.64 |
May | 0.546529E+09 | 0.60 | 866.85 | 01-MAY-15:02 | 0.64 |
June | 0.735934E+09 | 0.61 | 866.85 | 01-JUN-08:61 | 0.63 |
July | 0.655451E+09 | 0.61 | 866.85 | 01-JUL-08:61 | 0.64 |
August | 0.648081E+09 | 0.60 | 866.85 | 01-AUG-08:62 | 0.63 |
September | 0.557966E+09 | 0.60 | 866.85 | 01-SEP-08:61 | 0.63 |
October | 0.389041E+09 | 0.56 | 866.85 | 01-OCT-08:61 | 0.63 |
November | 0.226495E+09 | 0.53 | 866.85 | 01-NOV-15:02 | 0.63 |
December | 0.194213E+09 | 0.51 | 866.85 | 01-DEC-16:01 | 0.64 |
Annual Sum or Average | 0.500734E+10 | 0.56 | |||
Minimum of Months | 0.141488E+09 | 0.47 | 866.85 | 0.63 | |
Maximum of Months | 0.735934E+09 | 0.61 | 866.85 | 0.64 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.160371E+09 | 0.47 | 860.68 | 01-JAN-09:01 | 0.63 |
February | 0.134110E+09 | 0.45 | 860.68 | 01-FEB-16:01 | 0.64 |
March | 0.172905E+09 | 0.47 | 860.68 | 02-MAR-16:01 | 0.63 |
April | 0.416655E+09 | 0.57 | 860.68 | 01-APR-15:02 | 0.64 |
May | 0.533353E+09 | 0.60 | 860.68 | 01-MAY-15:02 | 0.64 |
June | 0.748730E+09 | 0.61 | 860.68 | 01-JUN-08:61 | 0.63 |
July | 0.653571E+09 | 0.61 | 860.68 | 01-JUL-08:61 | 0.64 |
August | 0.612514E+09 | 0.60 | 860.68 | 01-AUG-08:62 | 0.63 |
September | 0.499398E+09 | 0.59 | 860.68 | 01-SEP-08:61 | 0.63 |
October | 0.297687E+09 | 0.53 | 860.68 | 01-OCT-08:61 | 0.63 |
November | 0.154292E+09 | 0.48 | 860.68 | 01-NOV-15:02 | 0.63 |
December | 0.187906E+09 | 0.46 | 860.68 | 01-DEC-16:01 | 0.64 |
Annual Sum or Average | 0.457149E+10 | 0.54 | |||
Minimum of Months | 0.134110E+09 | 0.45 | 860.68 | 0.63 | |
Maximum of Months | 0.748730E+09 | 0.61 | 860.68 | 0.64 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165812E+10 | 0.40 | 2490.83 | 09-JAN-13:30 | 0.63 |
February | 0.447801E+09 | 0.18 | 2031.75 | 01-FEB-15:30 | 0.64 |
March | 0.438743E+09 | 0.20 | 1412.22 | 18-MAR-13:50 | 0.63 |
April | 0.140077E+10 | 0.49 | 1364.09 | 14-APR-13:40 | 0.64 |
May | 0.143711E+10 | 0.53 | 1118.19 | 09-MAY-17:12 | 0.64 |
June | 0.204475E+10 | 0.63 | 1525.20 | 28-JUN-18:10 | 0.63 |
July | 0.202667E+10 | 0.62 | 1345.41 | 11-JUL-17:13 | 0.63 |
August | 0.213085E+10 | 0.62 | 2136.36 | 28-AUG-12:30 | 0.63 |
September | 0.215988E+10 | 0.61 | 2654.64 | 28-SEP-12:20 | 0.63 |
October | 0.187735E+10 | 0.50 | 2728.68 | 05-OCT-14:50 | 0.63 |
November | 0.132627E+10 | 0.37 | 2557.88 | 15-NOV-14:10 | 0.63 |
December | 0.115578E+10 | 0.33 | 2274.48 | 28-DEC-13:30 | 0.64 |
Annual Sum or Average | 0.181041E+11 | 0.46 | |||
Minimum of Months | 0.438743E+09 | 0.18 | 1118.19 | 0.63 | |
Maximum of Months | 0.215988E+10 | 0.63 | 2728.68 | 0.64 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.719047E+09 | 0.45 | 5135.32 | 01-JAN-16:02 | 0.64 |
February | 0.578115E+09 | 0.45 | 5135.32 | 03-FEB-09:02 | 0.63 |
March | 0.958643E+09 | 0.45 | 5135.32 | 04-MAR-09:02 | 0.63 |
April | 0.207100E+10 | 0.46 | 5135.32 | 01-APR-08:62 | 0.64 |
May | 0.291514E+10 | 0.49 | 5135.32 | 01-MAY-08:62 | 0.64 |
June | 0.418202E+10 | 0.56 | 5135.32 | 01-JUN-08:61 | 0.63 |
July | 0.396303E+10 | 0.55 | 5135.32 | 01-JUL-08:61 | 0.64 |
August | 0.353316E+10 | 0.53 | 5135.32 | 01-AUG-08:62 | 0.63 |
September | 0.305299E+10 | 0.50 | 5135.32 | 01-SEP-08:61 | 0.63 |
October | 0.163411E+10 | 0.46 | 5135.32 | 01-OCT-08:61 | 0.63 |
November | 0.779419E+09 | 0.45 | 5135.32 | 01-NOV-15:02 | 0.63 |
December | 0.840244E+09 | 0.45 | 5135.32 | 04-DEC-09:01 | 0.63 |
Annual Sum or Average | 0.252269E+11 | 0.48 | |||
Minimum of Months | 0.578115E+09 | 0.45 | 5135.32 | 0.63 | |
Maximum of Months | 0.418202E+10 | 0.56 | 5135.32 | 0.64 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.220902E+09 | 0.55 | 757.32 | 01-JAN-16:02 | 0.64 |
February | 0.139309E+09 | 0.48 | 757.32 | 01-FEB-09:02 | 0.63 |
March | 0.200891E+09 | 0.52 | 757.32 | 01-MAR-16:02 | 0.63 |
April | 0.474168E+09 | 0.62 | 757.32 | 01-APR-08:62 | 0.63 |
May | 0.566120E+09 | 0.62 | 757.32 | 01-MAY-08:62 | 0.64 |
June | 0.758718E+09 | 0.63 | 757.32 | 01-JUN-08:61 | 0.63 |
July | 0.710089E+09 | 0.62 | 757.32 | 01-JUL-08:61 | 0.64 |
August | 0.681809E+09 | 0.62 | 757.32 | 01-AUG-08:62 | 0.63 |
September | 0.582114E+09 | 0.61 | 757.32 | 01-SEP-08:61 | 0.63 |
October | 0.402773E+09 | 0.59 | 757.32 | 01-OCT-08:61 | 0.63 |
November | 0.209755E+09 | 0.54 | 757.32 | 01-NOV-15:02 | 0.63 |
December | 0.181885E+09 | 0.51 | 757.32 | 01-DEC-09:02 | 0.63 |
Annual Sum or Average | 0.512853E+10 | 0.58 | |||
Minimum of Months | 0.139309E+09 | 0.48 | 757.32 | 0.63 | |
Maximum of Months | 0.758718E+09 | 0.63 | 757.32 | 0.64 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139246E+09 | 0.45 | 752.05 | 01-JAN-16:02 | 0.64 |
February | 0.116295E+09 | 0.45 | 752.05 | 04-FEB-09:02 | 0.63 |
March | 0.161841E+09 | 0.48 | 752.05 | 02-MAR-09:02 | 0.63 |
April | 0.418523E+09 | 0.61 | 752.05 | 01-APR-08:62 | 0.63 |
May | 0.554044E+09 | 0.62 | 752.05 | 01-MAY-08:62 | 0.64 |
June | 0.771075E+09 | 0.63 | 752.05 | 01-JUN-08:61 | 0.63 |
July | 0.709241E+09 | 0.62 | 752.05 | 01-JUL-08:61 | 0.64 |
August | 0.648717E+09 | 0.62 | 752.05 | 01-AUG-08:62 | 0.63 |
September | 0.522186E+09 | 0.61 | 752.05 | 01-SEP-08:61 | 0.63 |
October | 0.300094E+09 | 0.54 | 752.05 | 01-OCT-08:61 | 0.63 |
November | 0.134544E+09 | 0.46 | 752.05 | 01-NOV-15:02 | 0.63 |
December | 0.161774E+09 | 0.45 | 752.05 | 01-DEC-16:01 | 0.64 |
Annual Sum or Average | 0.463758E+10 | 0.54 | |||
Minimum of Months | 0.116295E+09 | 0.45 | 752.05 | 0.63 | |
Maximum of Months | 0.771075E+09 | 0.63 | 752.05 | 0.64 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 60988039.00 | 0.52 | 230.19 | 01-JAN-09:01 | 0.63 |
February | 42830433.00 | 0.47 | 230.19 | 01-FEB-16:01 | 0.64 |
March | 54637009.01 | 0.49 | 230.19 | 02-MAR-16:01 | 0.63 |
April | 0.115511E+09 | 0.59 | 230.19 | 01-APR-15:02 | 0.64 |
May | 0.137698E+09 | 0.60 | 230.19 | 01-MAY-15:02 | 0.64 |
June | 0.194363E+09 | 0.61 | 230.19 | 01-JUN-08:61 | 0.63 |
July | 0.171581E+09 | 0.61 | 230.19 | 01-JUL-08:61 | 0.64 |
August | 0.168602E+09 | 0.60 | 230.19 | 01-AUG-08:62 | 0.63 |
September | 0.141119E+09 | 0.60 | 230.19 | 01-SEP-08:61 | 0.63 |
October | 93933368.65 | 0.56 | 230.19 | 01-OCT-08:61 | 0.63 |
November | 56250419.86 | 0.52 | 230.19 | 01-NOV-15:02 | 0.63 |
December | 56864164.82 | 0.50 | 230.19 | 01-DEC-16:01 | 0.64 |
Annual Sum or Average | 0.129438E+10 | 0.56 | |||
Minimum of Months | 42830433.00 | 0.47 | 230.19 | 0.63 | |
Maximum of Months | 0.194363E+09 | 0.61 | 230.19 | 0.64 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 48187928.64 | 0.47 | 228.37 | 01-JAN-09:01 | 0.63 |
February | 44697644.13 | 0.45 | 228.37 | 01-FEB-09:02 | 0.63 |
March | 48172082.42 | 0.47 | 228.37 | 02-MAR-16:01 | 0.63 |
April | 0.102245E+09 | 0.57 | 228.37 | 01-APR-15:02 | 0.64 |
May | 0.134392E+09 | 0.60 | 228.37 | 01-MAY-15:02 | 0.64 |
June | 0.197428E+09 | 0.61 | 228.37 | 01-JUN-08:61 | 0.63 |
July | 0.171307E+09 | 0.61 | 228.37 | 01-JUL-08:61 | 0.64 |
August | 0.159718E+09 | 0.60 | 228.37 | 01-AUG-08:62 | 0.63 |
September | 0.126051E+09 | 0.59 | 228.37 | 01-SEP-08:61 | 0.63 |
October | 72767385.66 | 0.52 | 228.37 | 01-OCT-08:61 | 0.63 |
November | 43425083.89 | 0.47 | 228.37 | 01-NOV-15:02 | 0.63 |
December | 61041999.87 | 0.46 | 228.37 | 01-DEC-09:02 | 0.63 |
Annual Sum or Average | 0.120943E+10 | 0.54 | |||
Minimum of Months | 43425083.89 | 0.45 | 228.37 | 0.63 | |
Maximum of Months | 0.197428E+09 | 0.61 | 228.37 | 0.64 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.540273E+09 | 0.58 | 1008.39 | 01-JAN-16:02 | 0.64 |
February | 0.265531E+09 | 0.53 | 1008.39 | 01-FEB-16:01 | 0.64 |
March | 0.313564E+09 | 0.53 | 1008.39 | 01-MAR-16:02 | 0.63 |
April | 0.561678E+09 | 0.59 | 1008.39 | 01-APR-15:02 | 0.64 |
May | 0.593198E+09 | 0.59 | 1008.39 | 01-MAY-15:02 | 0.64 |
June | 0.798053E+09 | 0.60 | 1008.39 | 01-JUN-08:61 | 0.63 |
July | 0.789734E+09 | 0.60 | 1008.39 | 01-JUL-08:61 | 0.64 |
August | 0.824320E+09 | 0.60 | 1008.39 | 01-AUG-08:62 | 0.63 |
September | 0.809253E+09 | 0.60 | 1008.39 | 01-SEP-08:61 | 0.63 |
October | 0.659760E+09 | 0.59 | 1008.39 | 01-OCT-08:61 | 0.63 |
November | 0.475323E+09 | 0.56 | 1008.39 | 01-NOV-15:02 | 0.63 |
December | 0.432973E+09 | 0.57 | 1008.39 | 01-DEC-09:02 | 0.63 |
Annual Sum or Average | 0.706366E+10 | 0.58 | |||
Minimum of Months | 0.265531E+09 | 0.53 | 1008.39 | 0.63 | |
Maximum of Months | 0.824320E+09 | 0.60 | 1008.39 | 0.64 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.175403E+09 | 0.157862E+09 | 595.66 | 01-JAN-09:01 | 536.10 | 536.10 | 60.49 | 0.98 |
February | 0.199052E+09 | 0.179147E+09 | 552.11 | 25-FEB-05:23 | 496.90 | 496.90 | 47.49 | 0.85 |
March | 0.135416E+09 | 0.121874E+09 | 530.01 | 25-MAR-04:50 | 477.01 | 477.01 | 44.54 | 0.80 |
April | 5736604.71 | 5162944.24 | 425.37 | 21-APR-03:56 | 382.83 | 382.83 | 41.21 | 0.57 |
May | 1414150.41 | 1272735.37 | 331.42 | 25-MAY-08:04 | 298.28 | 298.28 | 55.14 | 0.41 |
June | 287818.09 | 259036.28 | 140.26 | 30-JUN-08:06 | 126.23 | 126.23 | 59.40 | 0.15 |
July | 341861.26 | 307675.14 | 266.48 | 27-JUL-08:05 | 239.83 | 239.83 | 60.30 | 0.31 |
August | 432580.99 | 389322.89 | 302.88 | 24-AUG-08:04 | 272.59 | 272.59 | 59.73 | 0.36 |
September | 641170.87 | 577053.79 | 274.93 | 29-SEP-08:04 | 247.44 | 247.44 | 57.47 | 0.32 |
October | 40141074.25 | 36126966.82 | 533.85 | 26-OCT-03:55 | 480.47 | 480.47 | 67.19 | 0.80 |
November | 0.118413E+09 | 0.106571E+09 | 546.80 | 18-NOV-06:17 | 492.12 | 492.12 | 56.33 | 0.84 |
December | 0.290068E+09 | 0.261061E+09 | 581.02 | 07-DEC-23:26 | 522.91 | 522.91 | 48.30 | 0.94 |
Annual Sum or Average | 0.967346E+09 | 0.870611E+09 | ||||||
Minimum of Months | 287818.09 | 259036.28 | 140.26 | 126.23 | 126.23 | 41.21 | 0.15 | |
Maximum of Months | 0.290068E+09 | 0.261061E+09 | 595.66 | 536.10 | 536.10 | 67.19 | 0.98 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.393767E+10 | 0.354390E+10 | 4265.02 | 27-JAN-16:01 | 3838.51 | 3838.51 | 6.73 | 11.17 |
February | 0.171099E+10 | 0.153989E+10 | 4201.53 | 18-FEB-16:01 | 3781.37 | 3781.37 | 7.46 | 10.79 |
March | 0.356961E+10 | 0.321265E+10 | 4711.12 | 17-MAR-18:03 | 4240.00 | 4240.00 | 7.11 | 14.79 |
April | 0.756861E+10 | 0.681175E+10 | 4820.63 | 25-APR-19:00 | 4338.56 | 4338.56 | 6.73 | 16.15 |
May | 0.885659E+10 | 0.797093E+10 | 4685.52 | 29-MAY-20:50 | 4216.97 | 4216.97 | 6.73 | 14.51 |
June | 0.103268E+11 | 0.929411E+10 | 5219.27 | 28-JUN-18:50 | 4697.34 | 4697.34 | 6.73 | 22.41 |
July | 0.112194E+11 | 0.100974E+11 | 5009.09 | 13-JUL-18:03 | 4508.18 | 4508.18 | 6.84 | 19.14 |
August | 0.111671E+11 | 0.100504E+11 | 5081.05 | 27-AUG-18:02 | 4572.94 | 4572.94 | 6.73 | 20.35 |
September | 0.106386E+11 | 0.957475E+10 | 5051.46 | 10-SEP-19:20 | 4546.32 | 4546.32 | 7.30 | 19.86 |
October | 0.714994E+10 | 0.643494E+10 | 4989.10 | 05-OCT-19:20 | 4490.19 | 4490.19 | 6.73 | 18.79 |
November | 0.429500E+10 | 0.386550E+10 | 4848.09 | 01-NOV-18:03 | 4363.28 | 4363.28 | 7.17 | 16.53 |
December | 0.249017E+10 | 0.224116E+10 | 4060.87 | 23-DEC-16:02 | 3654.78 | 3654.78 | 7.31 | 10.03 |
Annual Sum or Average | 0.829304E+11 | 0.746374E+11 | ||||||
Minimum of Months | 0.171099E+10 | 0.153989E+10 | 4060.87 | 3654.78 | 3654.78 | 6.73 | 10.03 | |
Maximum of Months | 0.112194E+11 | 0.100974E+11 | 5219.27 | 4697.34 | 4697.34 | 7.46 | 22.41 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.102440E+11 | 0.921960E+10 | 4362.97 | 01-JAN-00:06 | 3926.68 | 3926.68 | 8.40 | 30.58 |
February | 0.783407E+10 | 0.705066E+10 | 4362.97 | 01-FEB-00:10 | 3926.68 | 3926.68 | 8.50 | 30.58 |
March | 0.985425E+10 | 0.886883E+10 | 4362.97 | 01-MAR-00:05 | 3926.68 | 3926.68 | 8.42 | 30.58 |
April | 0.112840E+11 | 0.101556E+11 | 4362.97 | 01-APR-00:10 | 3926.68 | 3926.68 | 8.53 | 30.58 |
May | 0.116858E+11 | 0.105172E+11 | 4362.97 | 01-MAY-00:10 | 3926.68 | 3926.68 | 8.78 | 30.58 |
June | 0.113088E+11 | 0.101779E+11 | 4362.97 | 01-JUN-00:10 | 3926.68 | 3926.68 | 8.73 | 30.58 |
July | 0.116858E+11 | 0.105172E+11 | 4362.97 | 01-JUL-00:10 | 3926.68 | 3926.68 | 9.02 | 30.58 |
August | 0.116858E+11 | 0.105172E+11 | 4362.97 | 01-AUG-00:10 | 3926.68 | 3926.68 | 9.25 | 30.58 |
September | 0.113088E+11 | 0.101779E+11 | 4362.97 | 01-SEP-00:10 | 3926.68 | 3926.68 | 8.82 | 30.58 |
October | 0.112630E+11 | 0.101367E+11 | 4362.97 | 01-OCT-00:10 | 3926.68 | 3926.68 | 8.87 | 30.58 |
November | 0.101162E+11 | 0.910459E+10 | 4362.97 | 01-NOV-00:10 | 3926.68 | 3926.68 | 8.67 | 30.58 |
December | 0.892959E+10 | 0.803663E+10 | 4362.97 | 01-DEC-00:10 | 3926.68 | 3926.68 | 8.41 | 30.58 |
Annual Sum or Average | 0.127200E+12 | 0.114480E+12 | ||||||
Minimum of Months | 0.783407E+10 | 0.705066E+10 | 4362.97 | 3926.68 | 3926.68 | 8.40 | 30.58 | |
Maximum of Months | 0.116858E+11 | 0.105172E+11 | 4362.97 | 3926.68 | 3926.68 | 9.25 | 30.58 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:01 | 14.37 | 14.37 | 42.94 | 0.08 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:10 | 14.37 | 14.37 | 50.42 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 51.06 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 53.67 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 54.10 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 54.19 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.48 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 54.24 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 54.50 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.25 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 53.53 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 49.35 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 42.94 | 0.08 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.50 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 49.75 | 80.36 | 9048.62 | 125985.40 | 01-JAN-23:25 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.46 | 79.40 | 10224.37 | 116799.26 | 02-FEB-03:40 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 57.90 | 79.40 | 6630.43 | 121354.52 | 30-MAR-06:32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 64.80 | 79.40 | 280.11 | 91916.92 | 21-APR-03:56 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 48.33 | 48.33 | 63.03 | 43121.14 | 15-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.61 | 57.61 | 9.99 | 12704.33 | 30-JUN-08:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 59.28 | 59.28 | 10.94 | 24925.24 | 27-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 60.21 | 60.21 | 14.36 | 29949.04 | 24-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.31 | 58.31 | 22.95 | 29736.66 | 29-SEP-08:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.22 | 57.22 | 1987.15 | 113264.46 | 25-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 51.62 | 51.62 | 5827.58 | 122727.45 | 18-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 46.24 | 79.53 | 13708.56 | 155439.89 | 17-DEC-09:01 |
Annual Sum or Average | 0.00 | 3961.25 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.24 | 48.33 | 9.99 | 12704.33 | ||
Maximum of Months | 0.00 | 0.00 | 64.80 | 80.36 | 13708.56 | 155439.89 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 75181.67 | 420019.29 | 31-JAN-16:01 | 9.98 | 6.70 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 24892.27 | 257693.03 | 22-FEB-16:01 | 9.59 | 7.58 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 69670.52 | 426095.70 | 15-MAR-18:01 | 10.05 | 6.72 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 195349.90 | 498331.73 | 14-APR-18:03 | 10.59 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 241294.02 | 508050.65 | 31-MAY-18:03 | 10.67 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 321300.91 | 581996.87 | 17-JUN-18:03 | 11.24 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 352809.58 | 669449.90 | 13-JUL-18:03 | 12.03 | 6.81 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 343917.45 | 618594.23 | 09-AUG-18:03 | 11.73 | 6.91 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 324872.72 | 663077.76 | 10-SEP-20:40 | 12.39 | 7.21 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 170508.07 | 557201.50 | 01-OCT-18:03 | 11.05 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 83821.30 | 423443.06 | 20-NOV-16:01 | 10.00 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 43787.44 | 371007.71 | 25-DEC-16:02 | 9.75 | 6.86 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 188135.78 | 0.00 | ||||||
Minimum of Months | 24892.27 | 257693.03 | 9.59 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 352809.58 | 669449.90 | 12.39 | 7.58 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 42.94 | 59.97 | 23542.84 | 53917.80 | 23-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 50.42 | 58.44 | 23325.26 | 57289.21 | 08-FEB-07:01 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 51.06 | 59.77 | 22301.57 | 52072.06 | 25-MAR-07:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.67 | 59.57 | 20648.91 | 43489.08 | 21-APR-06:25 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 54.10 | 59.36 | 18861.19 | 39398.86 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 54.19 | 58.72 | 17412.75 | 35832.23 | 01-JUN-06:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.48 | 58.69 | 16681.21 | 33439.17 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 54.24 | 58.32 | 16914.58 | 34388.99 | 31-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.50 | 58.86 | 17995.36 | 37196.95 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.25 | 58.54 | 19646.90 | 46691.92 | 13-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 53.53 | 58.80 | 21422.87 | 49574.57 | 04-NOV-07:41 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 49.35 | 59.19 | 22847.73 | 53735.86 | 29-DEC-08:61 |
Annual Sum or Average | 0.00 | 20115.56 | ||||||
Minimum of Months | 0.00 | 0.00 | 42.94 | 58.32 | 16681.21 | 33439.17 | ||
Maximum of Months | 0.00 | 0.00 | 54.50 | 59.97 | 23542.84 | 57289.21 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.180079E+11 | 0.00 | 0.111591E+12 | 0.382663E+11 | 0.00 | 0.00 |
February | 0.168547E+11 | 0.00 | 0.273384E+11 | 0.322933E+11 | 0.00 | 0.00 |
March | 0.126537E+11 | 0.00 | 0.119887E+12 | 0.359654E+11 | 0.00 | 0.00 |
April | 0.579522E+09 | 0.00 | 0.327386E+12 | 0.390802E+11 | 0.00 | 0.00 |
May | 41198910.07 | 0.00 | 0.425765E+12 | 0.424525E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.544608E+12 | 0.468266E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.633802E+12 | 0.489065E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.616988E+12 | 0.495433E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.565901E+12 | 0.478399E+11 | 0.00 | 0.00 |
October | 0.424083E+10 | 0.00 | 0.290091E+12 | 0.439060E+11 | 0.00 | 0.00 |
November | 0.106409E+11 | 0.00 | 0.128100E+12 | 0.390295E+11 | 0.00 | 0.00 |
December | 0.202185E+11 | 0.00 | 0.605304E+11 | 0.389823E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.832373E+11 | 0.00 | 0.385199E+13 | 0.503092E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.273384E+11 | 0.322933E+11 | 0.00 | 0.00 |
Maximum of Months | 0.202185E+11 | 0.00 | 0.633802E+12 | 0.495433E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 25624.55 | 0.00 | 0.198588E+11 | 0.587890E+10 | 0.00 | 0.00 |
February | 18232.78 | 0.00 | 0.520638E+10 | 0.530997E+10 | 0.00 | 0.00 |
March | 28479.89 | 0.00 | 0.212817E+11 | 0.587890E+10 | 0.00 | 0.00 |
April | 46056.85 | 0.00 | 0.506605E+11 | 0.568926E+10 | 0.00 | 0.00 |
May | 51734.46 | 0.00 | 0.642412E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 79239.35 | 0.00 | 0.748094E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 36776.12 | 0.00 | 0.886398E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 35302.66 | 0.00 | 0.877525E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 19996.92 | 0.00 | 0.820432E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 28439.27 | 0.00 | 0.443045E+11 | 0.587890E+10 | 0.00 | 0.00 |
November | 31588.08 | 0.00 | 0.227731E+11 | 0.568926E+10 | 0.00 | 0.00 |
December | 1778060.81 | 0.00 | 0.111635E+11 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 2179531.73 | 0.00 | 0.572735E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 18232.78 | 0.00 | 0.520638E+10 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 1778060.81 | 0.00 | 0.886398E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.382663E+11 | 0.111591E+12 | 0.180079E+11 | 0.626832E+11 | 0.180479E+09 | 0.00 | 0.00 | 0.00 |
February | 0.322933E+11 | 0.273384E+11 | 0.168547E+11 | 0.573358E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.359654E+11 | 0.119887E+12 | 0.126537E+11 | 0.636390E+11 | 0.741913E+09 | 0.00 | 0.00 | 0.00 |
April | 0.390802E+11 | 0.327386E+12 | 0.579522E+09 | 0.143127E+11 | 0.202275E+11 | 0.00 | 0.00 | 0.00 |
May | 0.424525E+11 | 0.425765E+12 | 41198910.07 | 0.140224E+11 | 0.403727E+11 | 0.00 | 0.00 | 0.00 |
June | 0.468266E+11 | 0.544608E+12 | 0.00 | 0.233470E+11 | 0.875669E+11 | 0.00 | 0.00 | 0.00 |
July | 0.489065E+11 | 0.633802E+12 | 0.00 | 0.118824E+11 | 0.119501E+12 | 0.00 | 0.00 | 0.00 |
August | 0.495433E+11 | 0.616988E+12 | 0.00 | 0.132408E+11 | 0.101743E+12 | 0.00 | 0.00 | 0.00 |
September | 0.478399E+11 | 0.565901E+12 | 0.00 | 0.103540E+11 | 0.713707E+11 | 0.00 | 0.00 | 0.00 |
October | 0.439060E+11 | 0.290091E+12 | 0.424083E+10 | 0.194493E+11 | 0.176574E+11 | 0.00 | 0.00 | 0.00 |
November | 0.390295E+11 | 0.128100E+12 | 0.106409E+11 | 0.447402E+11 | 0.379828E+09 | 0.00 | 0.00 | 0.00 |
December | 0.389823E+11 | 0.605308E+11 | 0.202185E+11 | 0.116911E+12 | 6155976.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.503092E+12 | 0.385199E+13 | 0.832373E+11 | 0.451918E+12 | 0.459748E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.322933E+11 | 0.273384E+11 | 0.00 | 0.103540E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.495433E+11 | 0.633802E+12 | 0.202185E+11 | 0.116911E+12 | 0.119501E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.198588E+11 | 25624.55 | 0.171621E+11 | 0.289273E+09 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.520638E+10 | 18232.78 | 0.165585E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.212817E+11 | 28479.89 | 0.146035E+11 | 0.714940E+09 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.506605E+11 | 46056.85 | 0.142867E+10 | 0.915828E+10 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.642412E+11 | 51734.46 | 0.681966E+09 | 0.157162E+11 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.748094E+11 | 79239.35 | 0.572388E+09 | 0.305639E+11 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.886398E+11 | 36776.12 | 0.193673E+09 | 0.496475E+11 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.877525E+11 | 35302.66 | 0.149604E+09 | 0.454658E+11 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.820432E+11 | 19996.92 | 0.163399E+09 | 0.348908E+11 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.443045E+11 | 28439.27 | 0.448714E+10 | 0.933773E+10 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.227731E+11 | 31588.08 | 0.130885E+11 | 0.633656E+09 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.111635E+11 | 1778060.81 | 0.293742E+11 | 0.129186E+09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.572735E+12 | 2179531.73 | 0.984636E+11 | 0.196547E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.520638E+10 | 18232.78 | 0.149604E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.886398E+11 | 1778060.81 | 0.293742E+11 | 0.496475E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.382663E+11 | 0.180079E+11 | 0.111591E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.322933E+11 | 0.168547E+11 | 0.273384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.359654E+11 | 0.126537E+11 | 0.119887E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.390802E+11 | 0.579522E+09 | 0.327386E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.424525E+11 | 41198910.07 | 0.425765E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.468266E+11 | 0.00 | 0.544608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.489065E+11 | 0.00 | 0.633802E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.495433E+11 | 0.00 | 0.616988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.478399E+11 | 0.00 | 0.565901E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.439060E+11 | 0.424083E+10 | 0.290091E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.390295E+11 | 0.106409E+11 | 0.128100E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.389823E+11 | 0.202185E+11 | 0.605304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.503092E+12 | 0.832373E+11 | 0.385199E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.322933E+11 | 0.00 | 0.273384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.495433E+11 | 0.202185E+11 | 0.633802E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 25624.55 | 0.198588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 18232.78 | 0.520638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 28479.89 | 0.212817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 46056.85 | 0.506605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 51734.46 | 0.642412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 79239.35 | 0.748094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 36776.12 | 0.886398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 35302.66 | 0.877525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 19996.92 | 0.820432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 28439.27 | 0.443045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 31588.08 | 0.227731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 1778060.81 | 0.111635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 2179531.73 | 0.572735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 18232.78 | 0.520638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 1778060.81 | 0.886398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.256940E+09 | 343715.52 | 0.00 | 84379623.67 | 0.00 | 0.00 | 0.438171E+11 | 0.00 | 1.04 |
February | 0.114629E+11 | 0.00 | 0.00 | 26956475.93 | 0.00 | 0.00 | 0.273522E+11 | 0.00 | 0.92 |
March | 0.250658E+11 | 0.00 | 0.00 | 6651239.01 | 8212504.46 | 0.00 | 0.844746E+10 | 0.00 | 0.89 |
April | 0.297322E+10 | 2943224.53 | 0.00 | 17717411.31 | 0.491529E+09 | 0.00 | 0.145409E+11 | 0.00 | 0.85 |
May | 0.863588E+10 | 5962574.36 | 0.00 | 7023635.55 | 0.116583E+10 | 0.00 | 0.322587E+10 | 0.00 | 0.80 |
June | 0.346333E+09 | 0.305877E+09 | 0.00 | 14030794.63 | 0.271907E+10 | 0.00 | 0.483821E+10 | 0.00 | 0.75 |
July | 4125043.17 | 0.629983E+10 | 0.00 | 23552541.19 | 0.188468E+09 | 0.00 | 0.286343E+10 | 0.00 | 0.86 |
August | 0.00 | 0.557549E+10 | 0.00 | 32301442.76 | 3799918.69 | 0.00 | 0.406348E+10 | 0.00 | 0.96 |
September | 0.00 | 0.593628E+10 | 0.00 | 42681774.53 | 0.00 | 0.00 | 0.747736E+10 | 0.00 | 1.13 |
October | 0.00 | 0.780067E+09 | 0.00 | 94498026.42 | 0.00 | 0.00 | 0.357162E+11 | 0.00 | 1.28 |
November | 9304490.09 | 18292047.79 | 0.00 | 0.110097E+09 | 0.00 | 0.00 | 0.502561E+11 | 0.00 | 1.31 |
December | 5350148.29 | 0.00 | 0.00 | 0.128086E+09 | 0.00 | 0.00 | 0.573562E+11 | 0.00 | 1.21 |
Annual Sum or Average | 0.487598E+11 | 0.189251E+11 | 0.00 | 0.587976E+09 | 0.457691E+10 | 0.00 | 0.259954E+12 | 0.00 | 1.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 6651239.01 | 0.00 | 0.00 | 0.286343E+10 | 0.00 | 0.75 |
Maximum of Months | 0.250658E+11 | 0.629983E+10 | 0.00 | 0.128086E+09 | 0.271907E+10 | 0.00 | 0.573562E+11 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.192491E+10 | 99367.74 | 0.00 | 6183970.47 | 0.00 | 0.00 | 0.195439E+10 | 0.00 | 2.12 |
February | 0.271302E+10 | 0.00 | 0.00 | 1576221.37 | 0.00 | 3365644.32 | 0.999519E+09 | 0.00 | 1.65 |
March | 0.247556E+10 | 1157829.84 | 0.00 | 2387606.88 | 0.00 | 28157705.57 | 0.750674E+09 | 0.00 | 1.67 |
April | 0.604206E+09 | 0.106162E+09 | 0.00 | 5450541.39 | 0.00 | 0.00 | 0.121407E+10 | 0.00 | 2.07 |
May | 0.172664E+09 | 0.215248E+09 | 0.00 | 4870090.44 | 0.00 | 0.00 | 0.108316E+10 | 0.00 | 1.98 |
June | 0.00 | 0.613058E+09 | 0.00 | 4859481.38 | 0.00 | 0.00 | 0.667083E+09 | 0.00 | 2.27 |
July | 238032.56 | 0.100108E+10 | 0.00 | 2681573.48 | 0.00 | 0.00 | 0.303674E+09 | 0.00 | 2.16 |
August | 13818290.92 | 0.904590E+09 | 0.00 | 3046790.83 | 6278.88 | 0.00 | 0.352379E+09 | 0.00 | 2.24 |
September | 18215800.00 | 0.758661E+09 | 0.00 | 3560000.19 | 0.00 | 0.00 | 0.531677E+09 | 0.00 | 2.27 |
October | 0.952466E+09 | 0.141426E+09 | 0.00 | 6068520.07 | 0.00 | 0.00 | 0.148205E+10 | 0.00 | 2.22 |
November | 0.166285E+10 | 9631.82 | 0.00 | 5388092.55 | 1557277.53 | 0.00 | 0.185434E+10 | 0.00 | 2.03 |
December | 0.255496E+10 | 0.00 | 0.00 | 3634577.21 | 0.00 | 78140045.14 | 0.141175E+10 | 0.00 | 1.83 |
Annual Sum or Average | 0.130929E+11 | 0.374149E+10 | 0.00 | 49707466.27 | 1563556.41 | 0.109663E+09 | 0.126048E+11 | 0.00 | 2.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1576221.37 | 0.00 | 0.00 | 0.303674E+09 | 0.00 | 1.65 |
Maximum of Months | 0.271302E+10 | 0.100108E+10 | 0.00 | 6183970.47 | 1557277.53 | 78140045.14 | 0.195439E+10 | 0.00 | 2.27 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.215387E+10 | 0.00 | 0.00 | 1459540.32 | 36897.67 | 0.00 | 0.170303E+10 | 0.00 | 1.49 |
February | 0.327841E+10 | 0.00 | 0.00 | 435089.19 | 0.00 | 0.00 | 0.686333E+09 | 0.00 | 1.48 |
March | 0.232604E+10 | 0.00 | 0.00 | 1146040.23 | 881607.89 | 0.00 | 0.130136E+10 | 0.00 | 1.52 |
April | 0.162265E+09 | 47414416.42 | 0.00 | 4514915.02 | 5954050.00 | 0.00 | 0.187323E+10 | 0.00 | 1.56 |
May | 8627363.36 | 0.123125E+09 | 0.00 | 4995606.71 | 4662394.88 | 0.00 | 0.144390E+10 | 0.00 | 1.54 |
June | 27319.51 | 0.351365E+09 | 0.00 | 4620433.59 | 2613872.85 | 0.00 | 0.719905E+09 | 0.00 | 1.55 |
July | 163622.68 | 0.683777E+09 | 0.00 | 2590270.58 | 12326211.42 | 0.00 | 0.324932E+09 | 0.00 | 1.47 |
August | 687132.21 | 0.553558E+09 | 0.00 | 2970838.05 | 14748710.61 | 0.00 | 0.383354E+09 | 0.00 | 1.49 |
September | 1401615.67 | 0.491699E+09 | 0.00 | 3144185.42 | 15857966.72 | 0.00 | 0.582710E+09 | 0.00 | 1.48 |
October | 0.762514E+09 | 68822415.76 | 0.00 | 3505609.23 | 1875296.01 | 0.00 | 0.179678E+10 | 0.00 | 1.54 |
November | 0.180078E+10 | 1562.67 | 0.00 | 1670258.17 | 1764767.24 | 0.00 | 0.171618E+10 | 0.00 | 1.51 |
December | 0.321367E+10 | 0.00 | 0.00 | 604516.13 | 0.00 | 0.00 | 0.919635E+09 | 0.00 | 1.43 |
Annual Sum or Average | 0.137085E+11 | 0.231976E+10 | 0.00 | 31657302.65 | 60721775.31 | 0.00 | 0.134514E+11 | 0.00 | 1.51 |
Minimum of Months | 27319.51 | 0.00 | 0.00 | 435089.19 | 0.00 | 0.00 | 0.324932E+09 | 0.00 | 1.43 |
Maximum of Months | 0.327841E+10 | 0.683777E+09 | 0.00 | 4995606.71 | 15857966.72 | 0.00 | 0.187323E+10 | 0.00 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.255527E+10 | 0.00 | 0.00 | 3600.84 | 25033.39 | 0.00 | 10887304.42 | 0.00 | 0.47 |
February | 0.268642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
March | 0.233295E+10 | 0.00 | 0.00 | 176459.18 | 598130.64 | 0.00 | 0.110441E+09 | 0.00 | 0.48 |
April | 0.457669E+09 | 30172621.76 | 0.00 | 3066389.52 | 8644367.86 | 0.00 | 0.954476E+09 | 0.00 | 0.53 |
May | 414914.11 | 0.110142E+09 | 0.00 | 4966515.07 | 0.00 | 0.00 | 0.113868E+10 | 0.00 | 0.61 |
June | 0.00 | 0.395242E+09 | 0.00 | 4743355.77 | 0.00 | 0.00 | 0.676799E+09 | 0.00 | 0.76 |
July | 0.00 | 0.739298E+09 | 0.00 | 2629116.82 | 0.00 | 0.00 | 0.308165E+09 | 0.00 | 0.71 |
August | 0.00 | 0.576945E+09 | 0.00 | 2853764.51 | 171747.92 | 0.00 | 0.334380E+09 | 0.00 | 0.68 |
September | 0.00 | 0.478535E+09 | 0.00 | 3077970.38 | 0.00 | 0.00 | 0.489787E+09 | 0.00 | 0.64 |
October | 0.107643E+10 | 62278006.34 | 0.00 | 2020583.41 | 2695754.58 | 0.00 | 0.679382E+09 | 0.00 | 0.53 |
November | 0.223715E+10 | 0.00 | 0.00 | 120882.62 | 1198374.07 | 0.00 | 0.101062E+09 | 0.00 | 0.47 |
December | 0.279070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.141370E+11 | 0.239261E+10 | 0.00 | 23658638.13 | 13333408.46 | 0.00 | 0.480406E+10 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.279070E+10 | 0.739298E+09 | 0.00 | 4966515.07 | 8644367.86 | 0.00 | 0.113868E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.238394E+10 | 0.00 | 0.00 | 0.00 | 23271.66 | 1619903.44 | 0.00 | 0.00 | 0.75 |
February | 0.249736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 |
March | 0.226453E+10 | 0.00 | 0.00 | 0.00 | 556037.16 | 252204.46 | 0.00 | 0.00 | 0.77 |
April | 0.116373E+10 | 0.00 | 0.00 | 6694.03 | 33478785.35 | 0.00 | 3732965.27 | 0.00 | 0.72 |
May | 0.753417E+09 | 281207.65 | 0.00 | 134285.87 | 79056482.52 | 0.00 | 48614027.65 | 0.00 | 0.70 |
June | 51392702.99 | 0.180674E+09 | 0.00 | 1320097.29 | 28460845.76 | 0.00 | 0.304249E+09 | 0.00 | 0.67 |
July | 22439054.25 | 0.294660E+09 | 0.00 | 652318.57 | 95395095.57 | 0.00 | 0.141927E+09 | 0.00 | 0.64 |
August | 97269841.10 | 0.193562E+09 | 0.00 | 528986.63 | 0.126681E+09 | 0.00 | 99828239.84 | 0.00 | 0.65 |
September | 0.251042E+09 | 95635164.72 | 0.00 | 196849.83 | 0.192250E+09 | 0.00 | 66077995.79 | 0.00 | 0.66 |
October | 0.150936E+10 | 8646817.85 | 0.00 | 48321.47 | 32860545.39 | 0.00 | 14837145.92 | 0.00 | 0.74 |
November | 0.216783E+10 | 0.00 | 0.00 | 0.00 | 1114038.41 | 0.00 | 0.00 | 0.00 | 0.76 |
December | 0.258531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8993666.58 | 0.00 | 0.00 | 0.73 |
Annual Sum or Average | 0.157476E+11 | 0.773459E+09 | 0.00 | 2887553.69 | 0.589877E+09 | 10865774.48 | 0.679267E+09 | 0.00 | 0.71 |
Minimum of Months | 22439054.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
Maximum of Months | 0.258531E+10 | 0.294660E+09 | 0.00 | 1320097.29 | 0.192250E+09 | 8993666.58 | 0.304249E+09 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 21429405.90 | 452069.89 | 0.00 | 0.127628E+09 | 0.00 | 0.00 | 0.560131E+11 | 0.00 | 21.24 |
February | 11964603.96 | 0.00 | 0.00 | 0.108297E+09 | 0.00 | 0.00 | 0.569969E+11 | 0.00 | 20.91 |
March | 4724531.61 | 10652109.59 | 0.00 | 0.116384E+09 | 0.00 | 0.00 | 0.518981E+11 | 0.00 | 21.70 |
April | 0.00 | 0.637126E+09 | 0.00 | 93588036.73 | 0.00 | 0.00 | 0.252232E+11 | 0.00 | 20.35 |
May | 0.00 | 0.156895E+10 | 0.00 | 81234089.71 | 0.00 | 0.00 | 0.165641E+11 | 0.00 | 19.37 |
June | 0.00 | 0.432167E+10 | 0.00 | 53865535.81 | 0.00 | 0.00 | 0.686180E+10 | 0.00 | 17.87 |
July | 0.00 | 0.887560E+10 | 0.00 | 29999770.87 | 0.00 | 0.00 | 0.319672E+10 | 0.00 | 17.47 |
August | 0.00 | 0.733770E+10 | 0.00 | 35818173.53 | 0.00 | 0.00 | 0.393089E+10 | 0.00 | 17.85 |
September | 0.00 | 0.663644E+10 | 0.00 | 44442881.26 | 0.00 | 0.00 | 0.653243E+10 | 0.00 | 18.27 |
October | 1373567.23 | 0.877142E+09 | 0.00 | 0.100580E+09 | 0.00 | 0.00 | 0.348728E+11 | 0.00 | 20.83 |
November | 12927465.35 | 17566549.60 | 0.00 | 0.113029E+09 | 0.00 | 0.00 | 0.507042E+11 | 0.00 | 21.36 |
December | 3721965.63 | 0.00 | 0.00 | 0.136022E+09 | 0.00 | 0.00 | 0.604909E+11 | 0.00 | 20.05 |
Annual Sum or Average | 56141539.67 | 0.302833E+11 | 0.00 | 0.104089E+10 | 0.00 | 0.00 | 0.373285E+12 | 0.00 | 19.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 29999770.87 | 0.00 | 0.00 | 0.319672E+10 | 0.00 | 17.47 |
Maximum of Months | 21429405.90 | 0.887560E+10 | 0.00 | 0.136022E+09 | 0.00 | 0.00 | 0.604909E+11 | 0.00 | 21.70 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.736190E+10 | 338482.25 | 0.00 | 25620789.44 | 0.00 | 0.00 | 0.207264E+11 | 0.00 | 4.58 |
February | 0.141370E+11 | 0.00 | 0.00 | 7561764.47 | 0.00 | 0.00 | 0.150823E+11 | 0.00 | 4.49 |
March | 0.117892E+11 | 4509783.53 | 0.00 | 9609230.48 | 1999491.20 | 0.00 | 0.147057E+11 | 0.00 | 4.55 |
April | 0.227234E+10 | 0.385525E+09 | 0.00 | 19087753.50 | 11604948.75 | 0.00 | 0.114346E+11 | 0.00 | 4.30 |
May | 0.874614E+09 | 0.859263E+09 | 0.00 | 17864167.04 | 68885611.28 | 0.00 | 0.855520E+10 | 0.00 | 4.12 |
June | 76265487.84 | 0.229609E+10 | 0.00 | 18627353.08 | 0.104386E+09 | 0.00 | 0.415643E+10 | 0.00 | 3.90 |
July | 29726365.54 | 0.420434E+10 | 0.00 | 11571224.99 | 0.349149E+09 | 0.00 | 0.193930E+10 | 0.00 | 3.83 |
August | 55972206.19 | 0.355043E+10 | 0.00 | 13747766.37 | 0.259133E+09 | 0.00 | 0.234280E+10 | 0.00 | 3.92 |
September | 0.175862E+09 | 0.322401E+10 | 0.00 | 14668278.19 | 0.246608E+09 | 0.00 | 0.363435E+10 | 0.00 | 4.05 |
October | 0.378900E+10 | 0.519811E+09 | 0.00 | 23508738.47 | 13961069.55 | 0.00 | 0.141503E+11 | 0.00 | 4.48 |
November | 0.639085E+10 | 15603.36 | 0.00 | 22032178.78 | 13021278.47 | 0.00 | 0.190966E+11 | 0.00 | 4.56 |
December | 0.132946E+11 | 0.00 | 0.00 | 15502516.57 | 0.00 | 0.00 | 0.171737E+11 | 0.00 | 4.38 |
Annual Sum or Average | 0.602474E+11 | 0.150443E+11 | 0.00 | 0.199402E+09 | 0.106875E+10 | 0.00 | 0.132998E+12 | 0.00 | 4.26 |
Minimum of Months | 29726365.54 | 0.00 | 0.00 | 7561764.47 | 0.00 | 0.00 | 0.193930E+10 | 0.00 | 3.83 |
Maximum of Months | 0.141370E+11 | 0.420434E+10 | 0.00 | 25620789.44 | 0.349149E+09 | 0.00 | 0.207264E+11 | 0.00 | 4.58 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.224042E+11 | 762809.29 | 0.00 | 61544077.41 | 0.00 | 0.00 | 0.578244E+11 | 0.00 | 1.84 |
February | 0.438154E+11 | 0.00 | 0.00 | 23928955.60 | 0.00 | 0.00 | 0.383330E+11 | 0.00 | 1.82 |
March | 0.314562E+11 | 3769074.64 | 0.00 | 39862048.10 | 14456970.55 | 0.00 | 0.437281E+11 | 0.00 | 1.87 |
April | 0.311353E+10 | 0.100863E+10 | 0.00 | 81608024.42 | 89396635.94 | 0.00 | 0.387137E+11 | 0.00 | 1.87 |
May | 0.508604E+09 | 0.233112E+10 | 0.00 | 84381280.84 | 0.277442E+09 | 0.00 | 0.294631E+11 | 0.00 | 1.84 |
June | 24969639.76 | 0.664979E+10 | 0.00 | 81816303.87 | 0.262804E+09 | 0.00 | 0.145520E+11 | 0.00 | 1.80 |
July | 5043629.17 | 0.132558E+11 | 0.00 | 50009123.85 | 0.611048E+09 | 0.00 | 0.663071E+10 | 0.00 | 1.75 |
August | 15825876.60 | 0.107407E+11 | 0.00 | 56954099.22 | 0.533639E+09 | 0.00 | 0.796509E+10 | 0.00 | 1.77 |
September | 0.101065E+09 | 0.977653E+10 | 0.00 | 60317908.15 | 0.514439E+09 | 0.00 | 0.124207E+11 | 0.00 | 1.81 |
October | 0.913583E+10 | 0.142298E+10 | 0.00 | 81975288.21 | 36824463.11 | 0.00 | 0.443471E+11 | 0.00 | 1.90 |
November | 0.181947E+11 | 32306.14 | 0.00 | 58887912.06 | 36484164.43 | 0.00 | 0.548585E+11 | 0.00 | 1.86 |
December | 0.425624E+11 | 0.00 | 0.00 | 35056618.69 | 0.00 | 0.00 | 0.432369E+11 | 0.00 | 1.76 |
Annual Sum or Average | 0.171338E+12 | 0.451901E+11 | 0.00 | 0.716342E+09 | 0.237653E+10 | 0.00 | 0.392073E+12 | 0.00 | 1.82 |
Minimum of Months | 5043629.17 | 0.00 | 0.00 | 23928955.60 | 0.00 | 0.00 | 0.663071E+10 | 0.00 | 1.75 |
Maximum of Months | 0.438154E+11 | 0.132558E+11 | 0.00 | 84381280.84 | 0.611048E+09 | 0.00 | 0.578244E+11 | 0.00 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.156684E+09 | 897277.38 | 7950.48 | 7812326.54 | 226834.42 | 0.275419E+09 | 0.768796E+09 | 1706.56 | 0.47 |
February | 0.300561E+09 | 89972.34 | 0.00 | 3502596.64 | 0.00 | 0.493142E+09 | 0.523632E+09 | 0.00 | 0.48 |
March | 0.204437E+09 | 3282146.83 | 10935.79 | 5882248.60 | 352652.25 | 0.312236E+09 | 0.619279E+09 | 2485.21 | 0.47 |
April | 38433390.95 | 57616519.72 | 4733.06 | 7903939.13 | 1723914.66 | 480865.75 | 0.464931E+09 | 2335.15 | 0.47 |
May | 7976773.39 | 0.103478E+09 | 18398.74 | 6334154.83 | 2789687.98 | 58527.33 | 0.278701E+09 | 11037.48 | 0.47 |
June | 356409.17 | 0.230238E+09 | 49199.14 | 4502247.47 | 4498964.20 | 0.00 | 67173351.89 | 7973.25 | 0.47 |
July | 150134.62 | 0.627283E+09 | 272063.05 | 1195533.31 | 21446339.28 | 0.00 | 28234558.91 | 17324.62 | 0.47 |
August | 595332.91 | 0.592377E+09 | 222144.42 | 1225609.64 | 23433302.04 | 0.00 | 17017693.19 | 22198.47 | 0.48 |
September | 1979269.96 | 0.484822E+09 | 334000.97 | 2121910.91 | 21618501.92 | 2315.32 | 42991575.64 | 27165.66 | 0.48 |
October | 83862276.11 | 99401263.84 | 78850.66 | 7303737.62 | 4165222.13 | 65466408.45 | 0.546540E+09 | 11328.99 | 0.47 |
November | 0.139062E+09 | 7501239.49 | 63784.73 | 7236260.91 | 6656433.05 | 0.202852E+09 | 0.730704E+09 | 1907.34 | 0.47 |
December | 0.237842E+09 | 351251.62 | 0.00 | 4480219.64 | 688689.35 | 0.585158E+09 | 0.544517E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.117194E+10 | 0.220734E+10 | 1062061.04 | 59500785.25 | 87600541.28 | 0.193481E+10 | 0.463252E+10 | 105462.72 | 0.47 |
Minimum of Months | 150134.62 | 89972.34 | 0.00 | 1195533.31 | 0.00 | 0.00 | 17017693.19 | 0.00 | 0.47 |
Maximum of Months | 0.300561E+09 | 0.627283E+09 | 334000.97 | 7903939.13 | 23433302.04 | 0.585158E+09 | 0.768796E+09 | 27165.66 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.200222E+09 | 610485.83 | 6902.62 | 3492804.23 | 513494.27 | 0.550855E+09 | 0.453999E+09 | 2753.28 | 0.47 |
February | 0.346697E+09 | 89961.80 | 0.00 | 1596127.98 | 0.00 | 0.709219E+09 | 0.263172E+09 | 0.00 | 0.47 |
March | 0.224985E+09 | 2888875.56 | 8997.41 | 4130236.76 | 745497.66 | 0.411904E+09 | 0.500681E+09 | 4422.03 | 0.47 |
April | 42214735.37 | 56991827.60 | 0.00 | 7125259.31 | 2346401.30 | 793183.20 | 0.461556E+09 | 2320.26 | 0.47 |
May | 7807411.64 | 0.103392E+09 | 20533.34 | 6280022.52 | 2861225.03 | 58520.47 | 0.278890E+09 | 10385.94 | 0.47 |
June | 305880.80 | 0.230464E+09 | 45211.64 | 4614454.40 | 4252739.15 | 0.00 | 67103233.73 | 5495.41 | 0.47 |
July | 133021.04 | 0.627487E+09 | 250856.80 | 1216964.41 | 21189491.63 | 0.00 | 28226775.62 | 16015.50 | 0.47 |
August | 595263.16 | 0.590755E+09 | 220650.97 | 1176671.34 | 24982719.59 | 0.00 | 17064494.02 | 23663.29 | 0.48 |
September | 2076278.30 | 0.480290E+09 | 325339.74 | 1983279.23 | 26092840.69 | 2315.05 | 43027681.38 | 33990.86 | 0.48 |
October | 0.101558E+09 | 95679153.20 | 76687.10 | 5218932.67 | 7876560.99 | 0.141508E+09 | 0.454806E+09 | 12119.43 | 0.47 |
November | 0.193346E+09 | 6885749.04 | 74263.11 | 3615816.17 | 7254700.31 | 0.398084E+09 | 0.484682E+09 | 6985.68 | 0.47 |
December | 0.288606E+09 | 176555.48 | 0.00 | 1455448.74 | 863263.65 | 0.867202E+09 | 0.214573E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.140855E+10 | 0.219571E+10 | 1029442.74 | 41906017.75 | 98978934.25 | 0.307963E+10 | 0.326778E+10 | 118151.67 | 0.47 |
Minimum of Months | 133021.04 | 89961.80 | 0.00 | 1176671.34 | 0.00 | 0.00 | 17064494.02 | 0.00 | 0.47 |
Maximum of Months | 0.346697E+09 | 0.627487E+09 | 325339.74 | 7125259.31 | 26092840.69 | 0.867202E+09 | 0.500681E+09 | 33990.86 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.648165E+10 | 15372888.54 | 0.00 | 99209867.39 | 0.00 | 0.00 | 0.980818E+10 | 0.00 | 0.54 |
February | 0.116654E+11 | 1219944.27 | 0.00 | 30084666.79 | 0.00 | 0.00 | 0.621394E+10 | 0.00 | 0.54 |
March | 0.111036E+11 | 49466592.39 | 0.00 | 28508697.21 | 0.00 | 0.00 | 0.435016E+10 | 0.00 | 0.54 |
April | 0.237039E+10 | 0.804699E+09 | 0.00 | 38704364.98 | 0.00 | 0.00 | 0.452976E+10 | 0.00 | 0.54 |
May | 0.973331E+09 | 0.144129E+10 | 0.00 | 29016271.61 | 0.00 | 0.00 | 0.297142E+10 | 0.00 | 0.54 |
June | 4839947.31 | 0.318360E+10 | 0.00 | 21988390.39 | 0.00 | 0.00 | 0.949861E+09 | 0.00 | 0.54 |
July | 18781527.05 | 0.878604E+10 | 0.00 | 6012530.74 | 14076795.25 | 0.00 | 0.376287E+09 | 0.00 | 0.54 |
August | 2805345.90 | 0.831865E+10 | 0.00 | 5489622.57 | 34487118.18 | 0.00 | 0.247140E+09 | 0.00 | 0.54 |
September | 43075054.94 | 0.687178E+10 | 0.00 | 12006106.36 | 0.00 | 0.00 | 0.583486E+09 | 0.00 | 0.54 |
October | 0.321750E+10 | 0.140549E+10 | 0.00 | 55690421.95 | 0.00 | 0.00 | 0.626119E+10 | 0.00 | 0.54 |
November | 0.588000E+10 | 90015648.61 | 0.00 | 75436713.98 | 0.102840E+09 | 0.00 | 0.868642E+10 | 0.00 | 0.54 |
December | 0.888173E+10 | 4762657.00 | 0.00 | 72117821.45 | 9338009.96 | 0.00 | 0.964921E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.506430E+11 | 0.309724E+11 | 0.00 | 0.474265E+09 | 0.160742E+09 | 0.00 | 0.546271E+11 | 0.00 | 0.54 |
Minimum of Months | 2805345.90 | 1219944.27 | 0.00 | 5489622.57 | 0.00 | 0.00 | 0.247140E+09 | 0.00 | 0.54 |
Maximum of Months | 0.116654E+11 | 0.878604E+10 | 0.00 | 99209867.39 | 0.102840E+09 | 0.00 | 0.980818E+10 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.282527E+10 | 3818301.73 | 96922.82 | 31008248.98 | 11408984.61 | 0.128631E+10 | 0.122509E+11 | 52883.07 | 0.53 |
February | 0.480096E+10 | 1220277.86 | 0.00 | 23765808.52 | 0.00 | 0.128738E+10 | 0.118022E+11 | 0.00 | 0.54 |
March | 0.316843E+10 | 24118051.81 | 278468.43 | 43222384.62 | 25020388.07 | 0.754079E+09 | 0.115207E+11 | 63210.63 | 0.54 |
April | 0.646577E+09 | 0.506826E+09 | 3180670.13 | 55017549.63 | 0.294509E+09 | 6293635.49 | 0.623287E+10 | 403548.89 | 0.54 |
May | 0.137127E+09 | 0.118211E+10 | 5545613.09 | 51962443.16 | 0.253707E+09 | 806988.96 | 0.378496E+10 | 321556.58 | 0.54 |
June | 7042559.03 | 0.295629E+10 | 1451528.20 | 36635256.97 | 0.226691E+09 | 47592.88 | 0.933231E+09 | 40971.45 | 0.54 |
July | 2744149.23 | 0.802597E+10 | 2124222.33 | 9449024.57 | 0.774361E+09 | 0.00 | 0.388998E+09 | 66262.47 | 0.54 |
August | 8074387.61 | 0.742372E+10 | 1763108.13 | 8967933.03 | 0.929817E+09 | 0.00 | 0.238463E+09 | 129398.12 | 0.54 |
September | 31456772.05 | 0.580652E+10 | 3765351.43 | 16811236.33 | 0.106317E+10 | 16291.16 | 0.590457E+09 | 199826.78 | 0.54 |
October | 0.143673E+10 | 0.103891E+10 | 1820920.36 | 46607803.49 | 0.364841E+09 | 46433051.30 | 0.800722E+10 | 305177.45 | 0.54 |
November | 0.280315E+10 | 74261605.43 | 853920.75 | 31781550.17 | 0.117689E+09 | 0.955639E+09 | 0.108553E+11 | 104300.99 | 0.54 |
December | 0.398078E+10 | 785095.54 | 23842.55 | 16946526.97 | 13281938.17 | 0.551009E+10 | 0.910032E+10 | 13646.50 | 0.53 |
Annual Sum or Average | 0.198483E+11 | 0.270445E+11 | 20904568.22 | 0.372176E+09 | 0.407450E+10 | 0.984709E+10 | 0.757057E+11 | 1700782.94 | 0.54 |
Minimum of Months | 2744149.23 | 785095.54 | 0.00 | 8967933.03 | 0.00 | 0.00 | 0.238463E+09 | 0.00 | 0.53 |
Maximum of Months | 0.480096E+10 | 0.802597E+10 | 5545613.09 | 55017549.63 | 0.106317E+10 | 0.551009E+10 | 0.122509E+11 | 403548.89 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127876E+09 | 814250.19 | 6941.73 | 8345105.70 | 309861.61 | 0.298349E+09 | 0.774142E+09 | 2715.30 | 0.47 |
February | 0.265494E+09 | 89972.34 | 0.00 | 4308390.02 | 0.00 | 0.447713E+09 | 0.603323E+09 | 0.00 | 0.48 |
March | 0.170144E+09 | 3295434.20 | 10272.00 | 6570950.55 | 336582.39 | 0.289041E+09 | 0.676078E+09 | 5931.50 | 0.47 |
April | 14020443.19 | 57889152.66 | 0.00 | 9384420.34 | 1457081.12 | 28487.30 | 0.488316E+09 | 1268.80 | 0.47 |
May | 2187436.58 | 0.104123E+09 | 0.00 | 7601372.11 | 2174455.19 | 1658.88 | 0.283280E+09 | 0.00 | 0.47 |
June | 70056.44 | 0.232023E+09 | 0.00 | 5006958.87 | 2771749.74 | 0.00 | 66954993.22 | 0.00 | 0.47 |
July | 49936.53 | 0.638512E+09 | 0.00 | 1290380.71 | 10507609.03 | 0.00 | 28239909.60 | 0.00 | 0.47 |
August | 573978.29 | 0.603278E+09 | 16066.56 | 1179870.72 | 12758813.18 | 33548.73 | 17051237.99 | 876.44 | 0.48 |
September | 1018551.24 | 0.492847E+09 | 78917.95 | 2161848.79 | 13873003.75 | 0.00 | 43914671.80 | 2989.26 | 0.48 |
October | 53377540.57 | 0.101177E+09 | 8077.70 | 8288437.52 | 2470572.15 | 67596409.88 | 0.573910E+09 | 1360.51 | 0.47 |
November | 0.121323E+09 | 6999433.84 | 77471.01 | 7527666.82 | 7144840.62 | 0.229238E+09 | 0.721766E+09 | 1619.14 | 0.47 |
December | 0.252592E+09 | 351251.62 | 0.00 | 5001716.43 | 688689.35 | 0.572925E+09 | 0.541479E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.100873E+10 | 0.224140E+10 | 197746.96 | 66667118.58 | 54493258.14 | 0.190493E+10 | 0.481845E+10 | 16760.95 | 0.47 |
Minimum of Months | 49936.53 | 89972.34 | 0.00 | 1179870.72 | 0.00 | 0.00 | 17051237.99 | 0.00 | 0.47 |
Maximum of Months | 0.265494E+09 | 0.638512E+09 | 78917.95 | 9384420.34 | 13873003.75 | 0.572925E+09 | 0.774142E+09 | 5931.50 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.207411E+09 | 454252.56 | 7432.60 | 3222985.76 | 667430.34 | 0.540650E+09 | 0.457286E+09 | 4520.50 | 0.47 |
February | 0.353886E+09 | 89961.80 | 0.00 | 1779636.25 | 0.00 | 0.593776E+09 | 0.371241E+09 | 0.00 | 0.48 |
March | 0.220154E+09 | 3044193.26 | 7806.65 | 4500942.82 | 586548.74 | 0.364812E+09 | 0.552233E+09 | 9244.00 | 0.47 |
April | 15445066.28 | 57569906.79 | 0.00 | 8535593.52 | 1769373.72 | 3783464.73 | 0.483925E+09 | 1268.65 | 0.47 |
May | 2133237.15 | 0.104075E+09 | 0.00 | 7553706.60 | 2209715.57 | 1658.68 | 0.283347E+09 | 0.00 | 0.47 |
June | 68098.12 | 0.231996E+09 | 0.00 | 5103583.72 | 2771169.07 | 0.00 | 66851887.09 | 0.00 | 0.47 |
July | 46084.95 | 0.638517E+09 | 0.00 | 1313299.86 | 10425773.29 | 0.00 | 28217376.27 | 0.00 | 0.47 |
August | 573911.04 | 0.602776E+09 | 16025.04 | 1129138.74 | 13189408.03 | 33544.80 | 17099833.93 | 915.98 | 0.48 |
September | 1158568.22 | 0.491552E+09 | 78408.88 | 2015204.46 | 15108368.88 | 0.00 | 43915781.28 | 3488.73 | 0.48 |
October | 94796315.25 | 0.100242E+09 | 33410.34 | 5878033.31 | 3359942.48 | 0.125254E+09 | 0.477161E+09 | 8714.96 | 0.47 |
November | 0.205495E+09 | 6903582.49 | 68846.40 | 3446013.74 | 7235501.93 | 0.395388E+09 | 0.475398E+09 | 13767.31 | 0.47 |
December | 0.293473E+09 | 57395.88 | 2304.80 | 1348852.33 | 979176.23 | 0.821913E+09 | 0.255102E+09 | 942.22 | 0.47 |
Annual Sum or Average | 0.139464E+10 | 0.223728E+10 | 214234.71 | 45826991.11 | 58302408.29 | 0.284561E+10 | 0.351178E+10 | 42862.35 | 0.47 |
Minimum of Months | 46084.95 | 57395.88 | 0.00 | 1129138.74 | 0.00 | 0.00 | 17099833.93 | 0.00 | 0.47 |
Maximum of Months | 0.353886E+09 | 0.638517E+09 | 78408.88 | 8535593.52 | 15108368.88 | 0.821913E+09 | 0.552233E+09 | 13767.31 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.196066E+11 | 0.00 | 0.00 | 0.00 | 191266.18 | 0.00 | 0.00 | 0.00 | 0.49 |
February | 0.205254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
March | 0.186139E+11 | 0.00 | 0.00 | 0.00 | 4569983.64 | 0.00 | 0.00 | 0.00 | 0.50 |
April | 0.457172E+10 | 0.236278E+09 | 0.00 | 14105147.72 | 56009159.28 | 0.00 | 0.534428E+10 | 0.00 | 0.50 |
May | 0.666356E+09 | 0.726985E+09 | 0.00 | 20946738.25 | 11932229.84 | 0.00 | 0.643780E+10 | 0.00 | 0.51 |
June | 0.00 | 0.230333E+10 | 0.00 | 24617396.56 | 588128.38 | 0.00 | 0.363179E+10 | 0.00 | 0.57 |
July | 1395587.41 | 0.410849E+10 | 0.00 | 13704291.50 | 7021733.75 | 0.00 | 0.164845E+10 | 0.00 | 0.54 |
August | 65770549.59 | 0.335342E+10 | 0.00 | 14730278.96 | 32035428.73 | 0.00 | 0.187991E+10 | 0.00 | 0.54 |
September | 85646903.78 | 0.284695E+10 | 0.00 | 15196541.35 | 63870109.50 | 0.00 | 0.287075E+10 | 0.00 | 0.53 |
October | 0.853435E+10 | 0.434745E+09 | 0.00 | 12310102.46 | 1215799.51 | 0.00 | 0.433313E+10 | 0.00 | 0.52 |
November | 0.175901E+11 | 0.00 | 0.00 | 236238.79 | 9156109.92 | 0.00 | 0.226717E+09 | 0.00 | 0.50 |
December | 0.213222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.111583E+12 | 0.140102E+11 | 0.00 | 0.115847E+09 | 0.186590E+09 | 0.00 | 0.263728E+11 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.213222E+11 | 0.410849E+10 | 0.00 | 24617396.56 | 63870109.50 | 0.00 | 0.643780E+10 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 41571077.64 | 213548.27 | 1924.62 | 1598962.16 | 67479.68 | 0.133078E+09 | 0.125930E+09 | 489.63 | 0.47 |
February | 76706816.16 | 22493.09 | 0.00 | 720610.46 | 0.00 | 0.167947E+09 | 84834968.56 | 0.00 | 0.48 |
March | 51971055.98 | 800057.26 | 1571.87 | 1245643.73 | 110038.34 | 0.120704E+09 | 0.111537E+09 | 387.55 | 0.47 |
April | 9819977.91 | 14411475.32 | 1338.06 | 1700242.14 | 422065.10 | 4818396.43 | 0.111599E+09 | 1997.17 | 0.47 |
May | 2159042.59 | 25875133.43 | 4328.92 | 1374697.46 | 691751.79 | 23939.24 | 69709841.26 | 3054.47 | 0.47 |
June | 95175.87 | 57639677.74 | 11160.71 | 1047008.34 | 1046113.25 | 0.00 | 16865817.92 | 1699.60 | 0.47 |
July | 37682.12 | 0.156791E+09 | 63208.13 | 276663.28 | 5396239.44 | 0.00 | 7080711.31 | 4626.94 | 0.47 |
August | 148833.23 | 0.147819E+09 | 46997.77 | 285884.43 | 6142528.83 | 0.00 | 4274941.27 | 5413.93 | 0.48 |
September | 529964.54 | 0.120651E+09 | 64208.36 | 473314.89 | 5975838.75 | 854.73 | 10769633.80 | 9018.36 | 0.48 |
October | 22360223.33 | 24775649.70 | 17479.58 | 1500704.40 | 1118672.02 | 42927065.72 | 0.109005E+09 | 2365.11 | 0.47 |
November | 37628844.87 | 1820931.77 | 17066.89 | 1429255.93 | 1716859.49 | 0.100046E+09 | 0.130859E+09 | 983.01 | 0.47 |
December | 62546097.48 | 87812.91 | 0.00 | 895554.58 | 172172.34 | 0.190832E+09 | 88726059.63 | 0.00 | 0.47 |
Annual Sum or Average | 0.305575E+09 | 0.550907E+09 | 229284.90 | 12548541.81 | 22859759.03 | 0.760377E+09 | 0.871193E+09 | 30035.76 | 0.47 |
Minimum of Months | 37682.12 | 22493.09 | 0.00 | 276663.28 | 0.00 | 0.00 | 4274941.27 | 0.00 | 0.47 |
Maximum of Months | 76706816.16 | 0.156791E+09 | 64208.36 | 1700242.14 | 6142528.83 | 0.190832E+09 | 0.130859E+09 | 9018.36 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 50554429.69 | 104301.73 | 2073.81 | 639220.85 | 176693.30 | 0.190119E+09 | 60830183.45 | 340.17 | 0.47 |
February | 87283976.49 | 0.00 | 22269.74 | 297975.76 | 0.00 | 0.210323E+09 | 32265546.09 | 220.71 | 0.47 |
March | 56106561.60 | 710209.33 | 2399.93 | 843457.52 | 198383.97 | 0.143147E+09 | 85327734.32 | 954.93 | 0.47 |
April | 10636821.21 | 14276023.94 | 578.95 | 1511561.41 | 556095.67 | 8119161.94 | 0.107655E+09 | 2438.73 | 0.47 |
May | 2144185.81 | 25851655.69 | 4138.39 | 1360301.20 | 712116.84 | 23175.63 | 69731273.54 | 3244.12 | 0.47 |
June | 89242.19 | 57683017.34 | 5269.69 | 1072345.69 | 1002451.01 | 0.00 | 16844304.36 | 1035.85 | 0.47 |
July | 37094.60 | 0.157032E+09 | 62397.15 | 281886.63 | 5137288.60 | 0.00 | 7075209.04 | 4320.93 | 0.47 |
August | 148815.79 | 0.147368E+09 | 42911.04 | 273341.71 | 6578820.74 | 0.00 | 4286949.63 | 5793.99 | 0.48 |
September | 546427.25 | 0.119551E+09 | 63854.54 | 438630.04 | 7060425.27 | 1057.66 | 10786273.54 | 9854.46 | 0.48 |
October | 25967562.39 | 23776089.19 | 19028.81 | 1019209.30 | 2112838.69 | 61956702.69 | 86828957.39 | 3173.49 | 0.47 |
November | 49459336.59 | 1660143.15 | 3126.23 | 625396.41 | 1890848.30 | 0.147415E+09 | 72432172.04 | 1306.85 | 0.47 |
December | 69906995.20 | 39297.76 | 0.00 | 257408.86 | 220657.02 | 0.247686E+09 | 25109180.48 | 0.00 | 0.47 |
Annual Sum or Average | 0.352881E+09 | 0.548052E+09 | 228048.26 | 8620735.37 | 25646619.42 | 0.100879E+10 | 0.579173E+09 | 32684.23 | 0.47 |
Minimum of Months | 37094.60 | 0.00 | 0.00 | 257408.86 | 0.00 | 0.00 | 4286949.63 | 0.00 | 0.47 |
Maximum of Months | 87283976.49 | 0.157032E+09 | 63854.54 | 1511561.41 | 7060425.27 | 0.247686E+09 | 0.107655E+09 | 9854.46 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161811E+09 | 1820971.45 | 0.00 | 22194532.65 | 0.00 | 0.120870E+09 | 0.163646E+10 | 0.00 | 0.54 |
February | 0.293186E+09 | 144506.59 | 0.00 | 10584424.25 | 0.00 | 0.398224E+09 | 0.141943E+10 | 0.00 | 0.54 |
March | 0.254283E+09 | 5346088.29 | 7561.68 | 10582080.79 | 500811.20 | 0.353767E+09 | 0.121529E+10 | 5026.60 | 0.54 |
April | 59756433.99 | 91712939.61 | 2706.11 | 9710989.15 | 3596890.69 | 5938929.00 | 0.746525E+09 | 6813.06 | 0.54 |
May | 13964348.29 | 0.163730E+09 | 23087.22 | 7259827.37 | 6951110.79 | 118769.29 | 0.449363E+09 | 21808.28 | 0.54 |
June | 733816.66 | 0.365149E+09 | 56501.08 | 5218053.36 | 11857758.65 | 6532.29 | 0.109734E+09 | 45455.05 | 0.54 |
July | 297749.02 | 0.997949E+09 | 755992.08 | 1355252.95 | 43651024.77 | 0.00 | 45856461.04 | 47820.03 | 0.54 |
August | 956177.48 | 0.945164E+09 | 832837.61 | 1506838.16 | 43404148.54 | 0.00 | 27794137.99 | 57000.29 | 0.54 |
September | 3248553.50 | 0.776816E+09 | 546422.96 | 2902140.93 | 36589915.61 | 1304.51 | 69488447.83 | 33577.84 | 0.54 |
October | 96776170.63 | 0.160749E+09 | 114381.87 | 13250364.57 | 5606996.37 | 46901503.27 | 0.972452E+09 | 15182.46 | 0.54 |
November | 0.152152E+09 | 11742537.46 | 108798.29 | 18047005.41 | 10989447.09 | 0.135626E+09 | 0.142855E+10 | 3680.75 | 0.54 |
December | 0.227323E+09 | 564153.08 | 0.00 | 17991376.65 | 1106119.35 | 0.438630E+09 | 0.151965E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.126449E+10 | 0.352089E+10 | 2448288.91 | 0.120603E+09 | 0.164254E+09 | 0.150008E+10 | 0.964061E+10 | 236364.35 | 0.54 |
Minimum of Months | 297749.02 | 144506.59 | 0.00 | 1355252.95 | 0.00 | 0.00 | 27794137.99 | 0.00 | 0.54 |
Maximum of Months | 0.293186E+09 | 0.997949E+09 | 832837.61 | 22194532.65 | 43651024.77 | 0.438630E+09 | 0.163646E+10 | 57000.29 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.965402E+10 | 477848.24 | 0.00 | 35995386.58 | 0.00 | 0.00 | 0.397276E+11 | 0.00 | 5.81 |
February | 0.134004E+11 | 0.00 | 0.00 | 28906495.47 | 0.00 | 0.00 | 0.381044E+11 | 0.00 | 5.86 |
March | 0.762729E+10 | 9013351.74 | 0.00 | 39284414.98 | 2404028.50 | 0.00 | 0.393781E+11 | 0.00 | 5.98 |
April | 0.582407E+09 | 0.663278E+09 | 0.00 | 48783594.32 | 24168739.67 | 0.00 | 0.240772E+11 | 0.00 | 5.71 |
May | 93668956.81 | 0.159037E+10 | 0.00 | 51245431.31 | 39084015.79 | 0.00 | 0.172200E+11 | 0.00 | 5.56 |
June | 14285757.38 | 0.417235E+10 | 0.00 | 44209556.80 | 53683793.12 | 0.00 | 0.795602E+10 | 0.00 | 5.27 |
July | 2265381.93 | 0.802070E+10 | 0.00 | 26857150.20 | 0.147147E+09 | 0.00 | 0.364165E+10 | 0.00 | 5.14 |
August | 4815137.77 | 0.657229E+10 | 0.00 | 29956556.07 | 0.161676E+09 | 0.00 | 0.436123E+10 | 0.00 | 5.19 |
September | 38638660.93 | 0.591584E+10 | 0.00 | 31192400.19 | 0.166361E+09 | 0.00 | 0.685034E+10 | 0.00 | 5.30 |
October | 0.314455E+10 | 0.831719E+09 | 0.00 | 42794727.70 | 36923040.10 | 0.00 | 0.286683E+11 | 0.00 | 5.76 |
November | 0.675180E+10 | 5651221.50 | 0.00 | 35492931.77 | 17223868.81 | 0.00 | 0.380975E+11 | 0.00 | 5.85 |
December | 0.149895E+11 | 0.00 | 0.00 | 29902468.62 | 0.00 | 0.00 | 0.384826E+11 | 0.00 | 5.62 |
Annual Sum or Average | 0.563037E+11 | 0.277817E+11 | 0.00 | 0.444621E+09 | 0.648671E+09 | 0.00 | 0.286565E+12 | 0.00 | 5.59 |
Minimum of Months | 2265381.93 | 0.00 | 0.00 | 26857150.20 | 0.00 | 0.00 | 0.364165E+10 | 0.00 | 5.14 |
Maximum of Months | 0.149895E+11 | 0.802070E+10 | 0.00 | 51245431.31 | 0.166361E+09 | 0.00 | 0.397276E+11 | 0.00 | 5.98 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.438953E+10 | 477814.02 | 0.00 | 49422491.53 | 0.00 | 0.00 | 0.455912E+11 | 0.00 | 5.87 |
February | 0.549654E+10 | 0.00 | 0.00 | 40956384.78 | 0.00 | 0.00 | 0.464650E+11 | 0.00 | 5.91 |
March | 0.263974E+10 | 9131765.00 | 0.00 | 52836169.67 | 2284797.49 | 0.00 | 0.450760E+11 | 0.00 | 6.06 |
April | 0.248487E+09 | 0.673957E+09 | 0.00 | 58769416.63 | 13530616.33 | 0.00 | 0.251150E+11 | 0.00 | 5.84 |
May | 47321444.49 | 0.161419E+10 | 0.00 | 59218594.68 | 16981492.70 | 0.00 | 0.179596E+11 | 0.00 | 5.72 |
June | 2511037.16 | 0.423378E+10 | 0.00 | 48979002.33 | 30935946.71 | 0.00 | 0.832446E+10 | 0.00 | 5.43 |
July | 88367.54 | 0.826892E+10 | 0.00 | 29440534.21 | 65312039.64 | 0.00 | 0.379494E+10 | 0.00 | 5.29 |
August | 1263457.32 | 0.674908E+10 | 0.00 | 32986346.46 | 81236173.69 | 0.00 | 0.454872E+10 | 0.00 | 5.34 |
September | 15575534.99 | 0.610281E+10 | 0.00 | 35013884.49 | 79057778.63 | 0.00 | 0.715586E+10 | 0.00 | 5.44 |
October | 0.110489E+10 | 0.857508E+09 | 0.00 | 52986672.36 | 19736091.27 | 0.00 | 0.312977E+11 | 0.00 | 5.86 |
November | 0.310787E+10 | 22829297.03 | 0.00 | 47873197.43 | 44154.88 | 0.00 | 0.422373E+11 | 0.00 | 5.91 |
December | 0.830682E+10 | 0.00 | 0.00 | 44706147.49 | 0.00 | 0.00 | 0.455712E+11 | 0.00 | 5.66 |
Annual Sum or Average | 0.253606E+11 | 0.285327E+11 | 0.00 | 0.553189E+09 | 0.309119E+09 | 0.00 | 0.323137E+12 | 0.00 | 5.69 |
Minimum of Months | 88367.54 | 0.00 | 0.00 | 29440534.21 | 0.00 | 0.00 | 0.379494E+10 | 0.00 | 5.29 |
Maximum of Months | 0.830682E+10 | 0.826892E+10 | 0.00 | 59218594.68 | 81236173.69 | 0.00 | 0.464650E+11 | 0.00 | 6.06 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1648967.24 | 654552.65 | 0.00 | 0.134434E+09 | 0.00 | 0.00 | 0.519704E+11 | 0.00 | 21.73 |
February | 881847.47 | 0.00 | 0.00 | 0.113690E+09 | 0.00 | 0.00 | 0.564601E+11 | 0.00 | 21.59 |
March | 0.00 | 15779999.28 | 0.00 | 0.123318E+09 | 0.00 | 0.00 | 0.494147E+11 | 0.00 | 22.25 |
April | 0.00 | 0.992166E+09 | 0.00 | 95738474.52 | 0.00 | 0.00 | 0.237663E+11 | 0.00 | 21.50 |
May | 0.00 | 0.235119E+10 | 0.00 | 80376608.31 | 0.00 | 0.00 | 0.157354E+11 | 0.00 | 20.80 |
June | 0.00 | 0.605672E+10 | 0.00 | 53620380.95 | 0.00 | 0.00 | 0.679930E+10 | 0.00 | 19.68 |
July | 0.00 | 0.107627E+11 | 0.00 | 29825784.38 | 0.00 | 0.00 | 0.310718E+10 | 0.00 | 19.35 |
August | 0.00 | 0.923075E+10 | 0.00 | 34849386.53 | 0.00 | 0.00 | 0.381913E+10 | 0.00 | 19.60 |
September | 0.00 | 0.785832E+10 | 0.00 | 43438644.64 | 0.00 | 0.00 | 0.633374E+10 | 0.00 | 19.90 |
October | 0.00 | 0.118045E+10 | 0.00 | 0.104218E+09 | 0.00 | 0.00 | 0.327428E+11 | 0.00 | 21.66 |
November | 0.00 | 28702737.44 | 0.00 | 0.120011E+09 | 0.00 | 0.00 | 0.477071E+11 | 0.00 | 21.90 |
December | 615346.94 | 0.00 | 0.00 | 0.138727E+09 | 0.00 | 0.00 | 0.573411E+11 | 0.00 | 20.63 |
Annual Sum or Average | 3146161.66 | 0.384774E+11 | 0.00 | 0.107225E+10 | 0.00 | 0.00 | 0.355197E+12 | 0.00 | 20.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 29825784.38 | 0.00 | 0.00 | 0.310718E+10 | 0.00 | 19.35 |
Maximum of Months | 1648967.24 | 0.107627E+11 | 0.00 | 0.138727E+09 | 0.00 | 0.00 | 0.573411E+11 | 0.00 | 22.25 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.699975E+10 | 91125.13 | 0.00 | 1452613.45 | 0.00 | 596949.40 | 0.533474E+09 | 0.00 | 0.72 |
February | 0.785465E+10 | 0.00 | 0.00 | 8716.05 | 0.00 | 0.00 | 27774977.38 | 0.00 | 0.72 |
March | 0.660359E+10 | 738467.42 | 0.00 | 1925054.12 | 1168168.74 | 0.00 | 0.576671E+09 | 0.00 | 0.74 |
April | 0.140936E+10 | 0.207337E+09 | 0.00 | 10949918.02 | 9855.05 | 0.00 | 0.262694E+10 | 0.00 | 0.91 |
May | 0.213027E+09 | 0.503666E+09 | 0.00 | 12451786.16 | 0.00 | 0.00 | 0.273882E+10 | 0.00 | 0.99 |
June | 0.00 | 0.149085E+10 | 0.00 | 11928370.14 | 0.00 | 0.00 | 0.164414E+10 | 0.00 | 1.17 |
July | 0.00 | 0.243522E+10 | 0.00 | 6755175.09 | 0.00 | 0.00 | 0.750383E+09 | 0.00 | 1.12 |
August | 622803.59 | 0.205442E+10 | 0.00 | 7451286.54 | 0.00 | 0.00 | 0.874498E+09 | 0.00 | 1.10 |
September | 9815228.41 | 0.163183E+10 | 0.00 | 8175401.75 | 0.00 | 0.00 | 0.128501E+10 | 0.00 | 1.04 |
October | 0.303842E+10 | 0.257992E+09 | 0.00 | 7842020.29 | 0.00 | 0.00 | 0.202088E+10 | 0.00 | 0.86 |
November | 0.607698E+10 | 11499.84 | 0.00 | 2138360.59 | 3506347.83 | 0.00 | 0.793434E+09 | 0.00 | 0.73 |
December | 0.810516E+10 | 0.00 | 0.00 | 178641.31 | 0.00 | 10146887.39 | 72936794.94 | 0.00 | 0.69 |
Annual Sum or Average | 0.403114E+11 | 0.858215E+10 | 0.00 | 71257343.52 | 4684371.62 | 10743836.78 | 0.139450E+11 | 0.00 | 0.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 8716.05 | 0.00 | 0.00 | 27774977.38 | 0.00 | 0.69 |
Maximum of Months | 0.810516E+10 | 0.243522E+10 | 0.00 | 12451786.16 | 3506347.83 | 10146887.39 | 0.273882E+10 | 0.00 | 1.17 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:00:32
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.149234E+12 | 0.145103E+11 | 0.860330E+11 | 0.475079E+12 | 0.296220E+12 |
February | 0.186278E+12 | 0.146167E+11 | 0.988793E+11 | 0.475763E+12 | 0.107235E+12 |
March | 0.247870E+12 | 0.134457E+11 | 0.816118E+11 | 0.442139E+12 | 0.274098E+12 |
April | 0.294696E+12 | 0.499019E+10 | 0.256083E+11 | 0.177621E+12 | 0.689079E+12 |
May | 0.299960E+12 | 0.213951E+10 | 0.681019E+10 | 0.853520E+11 | 0.880218E+12 |
June | 0.313525E+12 | -0.223079E+10 | -0.271461E+11 | -0.554968E+11 | 0.114155E+13 |
July | 0.297869E+12 | -0.645919E+10 | -0.474126E+11 | -0.189466E+12 | 0.127315E+13 |
August | 0.249605E+12 | -0.534983E+10 | -0.398045E+11 | -0.151552E+12 | 0.124038E+13 |
September | 0.210441E+12 | -0.346190E+10 | -0.235143E+11 | -0.906440E+11 | 0.112420E+13 |
October | 0.190699E+12 | 0.715456E+10 | 0.419597E+11 | 0.254804E+12 | 0.622926E+12 |
November | 0.162174E+12 | 0.127808E+11 | 0.784663E+11 | 0.425807E+12 | 0.311189E+12 |
December | 0.117967E+12 | 0.180808E+11 | 0.112185E+12 | 0.575343E+12 | 0.190993E+12 |
Annual Sum or Average | 0.272032E+13 | 0.702168E+11 | 0.393676E+12 | 0.242475E+13 | 0.815125E+13 |
Minimum of Months | 0.117967E+12 | -0.645919E+10 | -0.474126E+11 | -0.189466E+12 | 0.107235E+12 |