Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:46

Tabular Output Report in Format: HTML

Building: HotelSmall

Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440

Simulation Timestamp: 2023-10-16 08:47:03


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 3108.16 774.41 834.39
Net Site Energy 3108.16 774.41 834.39
Total Source Energy 6526.42 1626.08 1752.02
Net Source Energy 6526.42 1626.08 1752.02


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 284.96 101.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 224.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 199.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 49.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 471.46 421.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 284.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1069.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2578.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1515.69 1592.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2578.17
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 284.96 101.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 224.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 199.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 49.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 311.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 130.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 0.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 28.48 421.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 284.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2578.17
  Water Heater 0.00 1069.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 284.96 101.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 224.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 199.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 49.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 471.46 421.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 284.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 1069.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2578.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 66.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 213.39 314.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.69
Other 126.56 113.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 406.89 427.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 62.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 198.05 291.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.64
Other 117.47 105.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 377.64 396.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 1515.685 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 1515.685 100.00
     
Total On-Site and Utility Electric Sources 1515.685 100.00
Total Electricity End Uses 1515.685 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.17 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.17 100.00
Total Water End Uses 2578.17 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 13.00
Time Setpoint Not Met During Occupied Cooling 334.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 6881.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELSMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER

| Environment |

ZoneCoolingSummaryMonthly

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

ZoneHeatingSummaryMonthly

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

ZoneElectricSummaryMonthly

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

SpaceGainsMonthly

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PeakSpaceGainsMonthly

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

SpaceGainComponentsAtCoolingPeakMonthly

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

ComfortReportSimple55Monthly

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

OccupantComfortDataSummaryMonthly

| CORRIDORFLR1_PEOPLE | CORRIDORFLR2_PEOPLE | CORRIDORFLR3_PEOPLE | CORRIDORFLR4_PEOPLE | ELEVATORCOREFLR1_PEOPLE | ELEVATORCOREFLR2_PEOPLE | ELEVATORCOREFLR3_PEOPLE | ELEVATORCOREFLR4_PEOPLE | EMPLOYEELOUNGEFLR1_PEOPLE | EXERCISECENTERFLR1_PEOPLE | FRONTLOUNGEFLR1_PEOPLE | FRONTOFFICEFLR1_PEOPLE | FRONTSTAIRSFLR1_PEOPLE | FRONTSTAIRSFLR2_PEOPLE | FRONTSTAIRSFLR3_PEOPLE | FRONTSTAIRSFLR4_PEOPLE | FRONTSTORAGEFLR1_PEOPLE | FRONTSTORAGEFLR2_PEOPLE | FRONTSTORAGEFLR3_PEOPLE | FRONTSTORAGEFLR4_PEOPLE | GUESTROOM101_PEOPLE | GUESTROOM102_PEOPLE | GUESTROOM103_PEOPLE | GUESTROOM104_PEOPLE | GUESTROOM105_PEOPLE | GUESTROOM201_PEOPLE | GUESTROOM202_205_PEOPLE | GUESTROOM206_208_PEOPLE | GUESTROOM209_212_PEOPLE | GUESTROOM213_PEOPLE | GUESTROOM214_PEOPLE | GUESTROOM215_218_PEOPLE | GUESTROOM219_PEOPLE | GUESTROOM220_223_PEOPLE | GUESTROOM224_PEOPLE | GUESTROOM301_PEOPLE | GUESTROOM302_305_PEOPLE | GUESTROOM306_308_PEOPLE | GUESTROOM309_312_PEOPLE | GUESTROOM313_PEOPLE | GUESTROOM314_PEOPLE | GUESTROOM315_318_PEOPLE | GUESTROOM319_PEOPLE | GUESTROOM320_323_PEOPLE | GUESTROOM324_PEOPLE | GUESTROOM401_PEOPLE | GUESTROOM402_405_PEOPLE | GUESTROOM406_408_PEOPLE | GUESTROOM409_412_PEOPLE | GUESTROOM413_PEOPLE | GUESTROOM414_PEOPLE | GUESTROOM415_418_PEOPLE | GUESTROOM419_PEOPLE | GUESTROOM420_423_PEOPLE | GUESTROOM424_PEOPLE | LAUNDRYROOMFLR1_PEOPLE | MECHANICALROOMFLR1_PEOPLE | MEETINGROOMFLR1_PEOPLE | REARSTAIRSFLR1_PEOPLE | REARSTAIRSFLR2_PEOPLE | REARSTAIRSFLR3_PEOPLE | REARSTAIRSFLR4_PEOPLE | REARSTORAGEFLR1_PEOPLE | REARSTORAGEFLR2_PEOPLE | REARSTORAGEFLR3_PEOPLE | REARSTORAGEFLR4_PEOPLE | RESTROOMFLR1_PEOPLE |

DXReportMonthly

| 101 PTAC PTAC COOLING COIL | 102 PTAC PTAC COOLING COIL | 103 PTAC PTAC COOLING COIL | 104 PTAC PTAC COOLING COIL | 105 PTAC PTAC COOLING COIL | 201 PTAC PTAC COOLING COIL | 202_205 PTAC PTAC COOLING COIL | 206_208 PTAC PTAC COOLING COIL | 209_212 PTAC PTAC COOLING COIL | 213 PTAC PTAC COOLING COIL | 214 PTAC PTAC COOLING COIL | 215_218 PTAC PTAC COOLING COIL | 219 PTAC PTAC COOLING COIL | 220_223 PTAC PTAC COOLING COIL | 224 PTAC PTAC COOLING COIL | 301 PTAC PTAC COOLING COIL | 302_305 PTAC PTAC COOLING COIL | 306_308 PTAC PTAC COOLING COIL | 309_312 PTAC PTAC COOLING COIL | 313 PTAC PTAC COOLING COIL | 314 PTAC PTAC COOLING COIL | 315_318 PTAC PTAC COOLING COIL | 319 PTAC PTAC COOLING COIL | 320_323 PTAC PTAC COOLING COIL | 324 PTAC PTAC COOLING COIL | 401 PTAC PTAC COOLING COIL | 402_405 PTAC PTAC COOLING COIL | 406_408 PTAC PTAC COOLING COIL | 409_412 PTAC PTAC COOLING COIL | 413 PTAC PTAC COOLING COIL | 414 PTAC PTAC COOLING COIL | 415_418 PTAC PTAC COOLING COIL | 419 PTAC PTAC COOLING COIL | 420_423 PTAC PTAC COOLING COIL | 424 PTAC PTAC COOLING COIL | CORRIDORFLR1 PTAC PTAC COOLING COIL | CORRIDORFLR2 PTAC PTAC COOLING COIL | CORRIDORFLR3 PTAC PTAC COOLING COIL | CORRIDORFLR4 PTAC PTAC COOLING COIL | SAC_FRONTOFFICE COOLING COIL | SAC_FRONTLOUNGE COOLING COIL | SAC_MEETINGROOM COOLING COIL | SAC_EMPLOYEELOUNGE COOLING COIL | SAC_EXERCISECENTER COOLING COIL | SAC_RESTROOM COOLING COIL |

WindowReportMonthly

| W_CORRIDORFLR1_2_0_0_0_0 | D_CORRIDORFLR1_16_0_0_0_0 | W_CORRIDORFLR1_20_0_0_0_0 | W_FRONTLOUNGEFLR1_5_0_0_0_0 | W_FRONTLOUNGEFLR1_5_0_0_0_1 | W_FRONTLOUNGEFLR1_5_0_0_0_2 | W_FRONTLOUNGEFLR1_5_0_0_0_3 | W_FRONTLOUNGEFLR1_5_0_0_0_4 | W_MEETINGROOMFLR1_5_0_0_0_0 | W_MEETINGROOMFLR1_5_0_0_0_1 | W_MEETINGROOMFLR1_5_0_0_0_2 | W_GUESTROOM101_5_0_0_0_0 | W_GUESTROOM102_5_0_0_0_0 | W_GUESTROOM103_5_0_0_0_0 | W_GUESTROOM104_3_0_0_0_0 | W_GUESTROOM105_3_0_0_0_0 | W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | W_LAUNDRYROOMFLR1_3_0_0_0_0 | W_LAUNDRYROOMFLR1_3_0_0_0_1 | W_LAUNDRYROOMFLR1_3_0_0_0_2 | W_EXERCISECENTERFLR1_3_0_0_0_0 | W_FRONTOFFICEFLR1_3_0_0_0_0 | W_FRONTOFFICEFLR1_3_0_0_0_1 | W_FRONTOFFICEFLR1_3_0_0_0_2 | W_FRONTOFFICEFLR1_3_0_0_0_3 | W_CORRIDORFLR2_2_0_0_0_0 | W_CORRIDORFLR2_15_0_0_0_0 | W_GUESTROOM201_5_0_0_0_0 | W_GUESTROOM202_205_5_0_0_0_0 | W_GUESTROOM202_205_5_0_0_0_1 | W_GUESTROOM202_205_5_0_0_0_2 | W_GUESTROOM202_205_5_0_0_0_3 | W_GUESTROOM206_208_5_0_0_0_0 | W_GUESTROOM206_208_5_0_0_0_1 | W_GUESTROOM206_208_5_0_0_0_2 | W_GUESTROOM209_212_5_0_0_0_0 | W_GUESTROOM209_212_5_0_0_0_1 | W_GUESTROOM209_212_5_0_0_0_2 | W_GUESTROOM209_212_5_0_0_0_3 | W_GUESTROOM213_5_0_0_0_0 | W_GUESTROOM214_3_0_0_0_0 | W_GUESTROOM215_218_3_0_0_0_0 | W_GUESTROOM215_218_3_0_0_0_1 | W_GUESTROOM215_218_3_0_0_0_2 | W_GUESTROOM215_218_3_0_0_0_3 | W_GUESTROOM219_3_0_0_0_0 | W_GUESTROOM220_223_3_0_0_0_0 | W_GUESTROOM220_223_3_0_0_0_1 | W_GUESTROOM220_223_3_0_0_0_2 | W_GUESTROOM220_223_3_0_0_0_3 | W_GUESTROOM224_3_0_0_0_0 | W_CORRIDORFLR3_2_0_0_0_0 | W_CORRIDORFLR3_15_0_0_0_0 | W_GUESTROOM301_5_0_0_0_0 | W_GUESTROOM302_305_5_0_0_0_0 | W_GUESTROOM302_305_5_0_0_0_1 | W_GUESTROOM302_305_5_0_0_0_2 | W_GUESTROOM302_305_5_0_0_0_3 | W_GUESTROOM306_308_5_0_0_0_0 | W_GUESTROOM306_308_5_0_0_0_1 | W_GUESTROOM306_308_5_0_0_0_2 | W_GUESTROOM309_312_5_0_0_0_0 | W_GUESTROOM309_312_5_0_0_0_1 | W_GUESTROOM309_312_5_0_0_0_2 | W_GUESTROOM309_312_5_0_0_0_3 | W_GUESTROOM313_5_0_0_0_0 | W_GUESTROOM314_3_0_0_0_0 | W_GUESTROOM315_318_3_0_0_0_0 | W_GUESTROOM315_318_3_0_0_0_1 | W_GUESTROOM315_318_3_0_0_0_2 | W_GUESTROOM315_318_3_0_0_0_3 | W_GUESTROOM319_3_0_0_0_0 | W_GUESTROOM320_323_3_0_0_0_0 | W_GUESTROOM320_323_3_0_0_0_1 | W_GUESTROOM320_323_3_0_0_0_2 | W_GUESTROOM320_323_3_0_0_0_3 | W_GUESTROOM324_3_0_0_0_0 | W_CORRIDORFLR4_2_0_0_0_0 | W_CORRIDORFLR4_15_0_0_0_0 | W_GUESTROOM401_5_0_0_0_0 | W_GUESTROOM402_405_5_0_0_0_0 | W_GUESTROOM402_405_5_0_0_0_1 | W_GUESTROOM402_405_5_0_0_0_2 | W_GUESTROOM402_405_5_0_0_0_3 | W_GUESTROOM406_408_5_0_0_0_0 | W_GUESTROOM406_408_5_0_0_0_1 | W_GUESTROOM406_408_5_0_0_0_2 | W_GUESTROOM409_412_5_0_0_0_0 | W_GUESTROOM409_412_5_0_0_0_1 | W_GUESTROOM409_412_5_0_0_0_2 | W_GUESTROOM409_412_5_0_0_0_3 | W_GUESTROOM413_5_0_0_0_0 | W_GUESTROOM414_3_0_0_0_0 | W_GUESTROOM415_418_3_0_0_0_0 | W_GUESTROOM415_418_3_0_0_0_1 | W_GUESTROOM415_418_3_0_0_0_2 | W_GUESTROOM415_418_3_0_0_0_3 | W_GUESTROOM419_3_0_0_0_0 | W_GUESTROOM420_423_3_0_0_0_0 | W_GUESTROOM420_423_3_0_0_0_1 | W_GUESTROOM420_423_3_0_0_0_2 | W_GUESTROOM420_423_3_0_0_0_3 | W_GUESTROOM424_3_0_0_0_0 |

WindowEnergyReportMonthly

| W_CORRIDORFLR1_2_0_0_0_0 | D_CORRIDORFLR1_16_0_0_0_0 | W_CORRIDORFLR1_20_0_0_0_0 | W_FRONTLOUNGEFLR1_5_0_0_0_0 | W_FRONTLOUNGEFLR1_5_0_0_0_1 | W_FRONTLOUNGEFLR1_5_0_0_0_2 | W_FRONTLOUNGEFLR1_5_0_0_0_3 | W_FRONTLOUNGEFLR1_5_0_0_0_4 | W_MEETINGROOMFLR1_5_0_0_0_0 | W_MEETINGROOMFLR1_5_0_0_0_1 | W_MEETINGROOMFLR1_5_0_0_0_2 | W_GUESTROOM101_5_0_0_0_0 | W_GUESTROOM102_5_0_0_0_0 | W_GUESTROOM103_5_0_0_0_0 | W_GUESTROOM104_3_0_0_0_0 | W_GUESTROOM105_3_0_0_0_0 | W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | W_LAUNDRYROOMFLR1_3_0_0_0_0 | W_LAUNDRYROOMFLR1_3_0_0_0_1 | W_LAUNDRYROOMFLR1_3_0_0_0_2 | W_EXERCISECENTERFLR1_3_0_0_0_0 | W_FRONTOFFICEFLR1_3_0_0_0_0 | W_FRONTOFFICEFLR1_3_0_0_0_1 | W_FRONTOFFICEFLR1_3_0_0_0_2 | W_FRONTOFFICEFLR1_3_0_0_0_3 | W_CORRIDORFLR2_2_0_0_0_0 | W_CORRIDORFLR2_15_0_0_0_0 | W_GUESTROOM201_5_0_0_0_0 | W_GUESTROOM202_205_5_0_0_0_0 | W_GUESTROOM202_205_5_0_0_0_1 | W_GUESTROOM202_205_5_0_0_0_2 | W_GUESTROOM202_205_5_0_0_0_3 | W_GUESTROOM206_208_5_0_0_0_0 | W_GUESTROOM206_208_5_0_0_0_1 | W_GUESTROOM206_208_5_0_0_0_2 | W_GUESTROOM209_212_5_0_0_0_0 | W_GUESTROOM209_212_5_0_0_0_1 | W_GUESTROOM209_212_5_0_0_0_2 | W_GUESTROOM209_212_5_0_0_0_3 | W_GUESTROOM213_5_0_0_0_0 | W_GUESTROOM214_3_0_0_0_0 | W_GUESTROOM215_218_3_0_0_0_0 | W_GUESTROOM215_218_3_0_0_0_1 | W_GUESTROOM215_218_3_0_0_0_2 | W_GUESTROOM215_218_3_0_0_0_3 | W_GUESTROOM219_3_0_0_0_0 | W_GUESTROOM220_223_3_0_0_0_0 | W_GUESTROOM220_223_3_0_0_0_1 | W_GUESTROOM220_223_3_0_0_0_2 | W_GUESTROOM220_223_3_0_0_0_3 | W_GUESTROOM224_3_0_0_0_0 | W_CORRIDORFLR3_2_0_0_0_0 | W_CORRIDORFLR3_15_0_0_0_0 | W_GUESTROOM301_5_0_0_0_0 | W_GUESTROOM302_305_5_0_0_0_0 | W_GUESTROOM302_305_5_0_0_0_1 | W_GUESTROOM302_305_5_0_0_0_2 | W_GUESTROOM302_305_5_0_0_0_3 | W_GUESTROOM306_308_5_0_0_0_0 | W_GUESTROOM306_308_5_0_0_0_1 | W_GUESTROOM306_308_5_0_0_0_2 | W_GUESTROOM309_312_5_0_0_0_0 | W_GUESTROOM309_312_5_0_0_0_1 | W_GUESTROOM309_312_5_0_0_0_2 | W_GUESTROOM309_312_5_0_0_0_3 | W_GUESTROOM313_5_0_0_0_0 | W_GUESTROOM314_3_0_0_0_0 | W_GUESTROOM315_318_3_0_0_0_0 | W_GUESTROOM315_318_3_0_0_0_1 | W_GUESTROOM315_318_3_0_0_0_2 | W_GUESTROOM315_318_3_0_0_0_3 | W_GUESTROOM319_3_0_0_0_0 | W_GUESTROOM320_323_3_0_0_0_0 | W_GUESTROOM320_323_3_0_0_0_1 | W_GUESTROOM320_323_3_0_0_0_2 | W_GUESTROOM320_323_3_0_0_0_3 | W_GUESTROOM324_3_0_0_0_0 | W_CORRIDORFLR4_2_0_0_0_0 | W_CORRIDORFLR4_15_0_0_0_0 | W_GUESTROOM401_5_0_0_0_0 | W_GUESTROOM402_405_5_0_0_0_0 | W_GUESTROOM402_405_5_0_0_0_1 | W_GUESTROOM402_405_5_0_0_0_2 | W_GUESTROOM402_405_5_0_0_0_3 | W_GUESTROOM406_408_5_0_0_0_0 | W_GUESTROOM406_408_5_0_0_0_1 | W_GUESTROOM406_408_5_0_0_0_2 | W_GUESTROOM409_412_5_0_0_0_0 | W_GUESTROOM409_412_5_0_0_0_1 | W_GUESTROOM409_412_5_0_0_0_2 | W_GUESTROOM409_412_5_0_0_0_3 | W_GUESTROOM413_5_0_0_0_0 | W_GUESTROOM414_3_0_0_0_0 | W_GUESTROOM415_418_3_0_0_0_0 | W_GUESTROOM415_418_3_0_0_0_1 | W_GUESTROOM415_418_3_0_0_0_2 | W_GUESTROOM415_418_3_0_0_0_3 | W_GUESTROOM419_3_0_0_0_0 | W_GUESTROOM420_423_3_0_0_0_0 | W_GUESTROOM420_423_3_0_0_0_1 | W_GUESTROOM420_423_3_0_0_0_2 | W_GUESTROOM420_423_3_0_0_0_3 | W_GUESTROOM424_3_0_0_0_0 |

WindowZoneSummaryMonthly

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

WindowEnergyZoneSummaryMonthly

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH SHOWER WATER HEATER | SWH LAUNDRY WATER HEATER |

DaylightingReportMonthly

| FRONTLOUNGEFLR1_DAYLCTRL | MEETINGROOMFLR1_DAYLCTRL | FRONTOFFICEFLR1_DAYLCTRL | LAUNDRYROOMFLR1_DAYLCTRL |

CoilReportMonthly

| 101 PTAC HEATING COIL | 102 PTAC HEATING COIL | 103 PTAC HEATING COIL | 104 PTAC HEATING COIL | 105 PTAC HEATING COIL | 201 PTAC HEATING COIL | 202_205 PTAC HEATING COIL | 206_208 PTAC HEATING COIL | 209_212 PTAC HEATING COIL | 213 PTAC HEATING COIL | 214 PTAC HEATING COIL | 215_218 PTAC HEATING COIL | 219 PTAC HEATING COIL | 220_223 PTAC HEATING COIL | 224 PTAC HEATING COIL | 301 PTAC HEATING COIL | 302_305 PTAC HEATING COIL | 306_308 PTAC HEATING COIL | 309_312 PTAC HEATING COIL | 313 PTAC HEATING COIL | 314 PTAC HEATING COIL | 315_318 PTAC HEATING COIL | 319 PTAC HEATING COIL | 320_323 PTAC HEATING COIL | 324 PTAC HEATING COIL | 401 PTAC HEATING COIL | 402_405 PTAC HEATING COIL | 406_408 PTAC HEATING COIL | 409_412 PTAC HEATING COIL | 413 PTAC HEATING COIL | 414 PTAC HEATING COIL | 415_418 PTAC HEATING COIL | 419 PTAC HEATING COIL | 420_423 PTAC HEATING COIL | 424 PTAC HEATING COIL | CORRIDORFLR1 PTAC HEATING COIL | CORRIDORFLR2 PTAC HEATING COIL | CORRIDORFLR3 PTAC HEATING COIL | CORRIDORFLR4 PTAC HEATING COIL | FRONTSTAIRSFLR1 UNITHEATER HEATING COIL | FRONTSTAIRSFLR2 UNITHEATER HEATING COIL | FRONTSTAIRSFLR3 UNITHEATER HEATING COIL | FRONTSTAIRSFLR4 UNITHEATER HEATING COIL | REARSTAIRSFLR1 UNITHEATER HEATING COIL | REARSTAIRSFLR2 UNITHEATER HEATING COIL | REARSTAIRSFLR3 UNITHEATER HEATING COIL | REARSTAIRSFLR4 UNITHEATER HEATING COIL | MECHRM UNITHEATER HEATING COIL | SAC_FRONTOFFICE HEATING COIL | SAC_FRONTLOUNGE HEATING COIL | SAC_MEETINGROOM HEATING COIL | SAC_EMPLOYEELOUNGE HEATING COIL | SAC_EXERCISECENTER HEATING COIL | SAC_RESTROOM HEATING COIL | 101 PTAC PTAC COOLING COIL | 102 PTAC PTAC COOLING COIL | 103 PTAC PTAC COOLING COIL | 104 PTAC PTAC COOLING COIL | 105 PTAC PTAC COOLING COIL | 201 PTAC PTAC COOLING COIL | 202_205 PTAC PTAC COOLING COIL | 206_208 PTAC PTAC COOLING COIL | 209_212 PTAC PTAC COOLING COIL | 213 PTAC PTAC COOLING COIL | 214 PTAC PTAC COOLING COIL | 215_218 PTAC PTAC COOLING COIL | 219 PTAC PTAC COOLING COIL | 220_223 PTAC PTAC COOLING COIL | 224 PTAC PTAC COOLING COIL | 301 PTAC PTAC COOLING COIL | 302_305 PTAC PTAC COOLING COIL | 306_308 PTAC PTAC COOLING COIL | 309_312 PTAC PTAC COOLING COIL | 313 PTAC PTAC COOLING COIL | 314 PTAC PTAC COOLING COIL | 315_318 PTAC PTAC COOLING COIL | 319 PTAC PTAC COOLING COIL | 320_323 PTAC PTAC COOLING COIL | 324 PTAC PTAC COOLING COIL | 401 PTAC PTAC COOLING COIL | 402_405 PTAC PTAC COOLING COIL | 406_408 PTAC PTAC COOLING COIL | 409_412 PTAC PTAC COOLING COIL | 413 PTAC PTAC COOLING COIL | 414 PTAC PTAC COOLING COIL | 415_418 PTAC PTAC COOLING COIL | 419 PTAC PTAC COOLING COIL | 420_423 PTAC PTAC COOLING COIL | 424 PTAC PTAC COOLING COIL | CORRIDORFLR1 PTAC PTAC COOLING COIL | CORRIDORFLR2 PTAC PTAC COOLING COIL | CORRIDORFLR3 PTAC PTAC COOLING COIL | CORRIDORFLR4 PTAC PTAC COOLING COIL | SAC_FRONTOFFICE COOLING COIL | SAC_FRONTLOUNGE COOLING COIL | SAC_MEETINGROOM COOLING COIL | SAC_EMPLOYEELOUNGE COOLING COIL | SAC_EXERCISECENTER COOLING COIL | SAC_RESTROOM COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYSSHOWER | SWHSYSLAUNDRY |

FanReportMonthly

| FRONTSTAIRSFLR1 UNITHEATER FAN | FRONTSTAIRSFLR2 UNITHEATER FAN | FRONTSTAIRSFLR3 UNITHEATER FAN | FRONTSTAIRSFLR4 UNITHEATER FAN | REARSTAIRSFLR1 UNITHEATER FAN | REARSTAIRSFLR2 UNITHEATER FAN | REARSTAIRSFLR3 UNITHEATER FAN | REARSTAIRSFLR4 UNITHEATER FAN | MECHRM UNITHEATER FAN | 101 PTAC SUPPLY FAN | 102 PTAC SUPPLY FAN | 103 PTAC SUPPLY FAN | 104 PTAC SUPPLY FAN | 105 PTAC SUPPLY FAN | 201 PTAC SUPPLY FAN | 202_205 PTAC SUPPLY FAN | 206_208 PTAC SUPPLY FAN | 209_212 PTAC SUPPLY FAN | 213 PTAC SUPPLY FAN | 214 PTAC SUPPLY FAN | 215_218 PTAC SUPPLY FAN | 219 PTAC SUPPLY FAN | 220_223 PTAC SUPPLY FAN | 224 PTAC SUPPLY FAN | 301 PTAC SUPPLY FAN | 302_305 PTAC SUPPLY FAN | 306_308 PTAC SUPPLY FAN | 309_312 PTAC SUPPLY FAN | 313 PTAC SUPPLY FAN | 314 PTAC SUPPLY FAN | 315_318 PTAC SUPPLY FAN | 319 PTAC SUPPLY FAN | 320_323 PTAC SUPPLY FAN | 324 PTAC SUPPLY FAN | 401 PTAC SUPPLY FAN | 402_405 PTAC SUPPLY FAN | 406_408 PTAC SUPPLY FAN | 409_412 PTAC SUPPLY FAN | 413 PTAC SUPPLY FAN | 414 PTAC SUPPLY FAN | 415_418 PTAC SUPPLY FAN | 419 PTAC SUPPLY FAN | 420_423 PTAC SUPPLY FAN | 424 PTAC SUPPLY FAN | CORRIDORFLR1 PTAC SUPPLY FAN | CORRIDORFLR2 PTAC SUPPLY FAN | CORRIDORFLR3 PTAC SUPPLY FAN | CORRIDORFLR4 PTAC SUPPLY FAN | SAC_FRONTOFFICE_ADDAQ SUPPLY FAN | SAC_FRONTLOUNGE_ADDAQ SUPPLY FAN | SAC_MEETINGROOM_ADDAQ SUPPLY FAN | SAC_EMPLOYEELOUNGE_ADDAQ SUPPLY FAN | SAC_EXERCISECENTER_ADDAQ SUPPLY FAN | SAC_RESTROOM_ADDAQ SUPPLY FAN |

PumpReportMonthly

| SWHSYSSHOWER PUMP | SWHSYSLAUNDRY PUMP |

CondLoopDemandReportMonthly

| SWHSYSSHOWER | SWHSYSLAUNDRY |

ZoneTemperatureOscillationReportMonthly

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

AirLoopSystemEnergyAndWaterUseMonthly

| SAC_FRONTOFFICE | SAC_FRONTLOUNGE | SAC_MEETINGROOM | SAC_EMPLOYEELOUNGE | SAC_EXERCISECENTER | SAC_RESTROOM |

AirLoopSystemComponentLoadsMonthly

| SAC_FRONTOFFICE | SAC_FRONTLOUNGE | SAC_MEETINGROOM | SAC_EMPLOYEELOUNGE | SAC_EXERCISECENTER | SAC_RESTROOM |

AirLoopSystemComponentEnergyUseMonthly

| SAC_FRONTOFFICE | SAC_FRONTLOUNGE | SAC_MEETINGROOM | SAC_EMPLOYEELOUNGE | SAC_EXERCISECENTER | SAC_RESTROOM |

MechanicalVentilationLoadsMonthly

| REARSTAIRSFLR1 | CORRIDORFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTAIRSFLR4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:46
RunPeriod RUNPERIOD 1
Weather File Rochester International Arpt MN USA TMY3 WMO#=726440
Latitude [deg] 43.90
Longitude [deg] -92.5
Elevation [m] 398.00
Time Zone -6.0
North Axis Angle [deg] 90.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 211.83 635.46 211.83 635.46
Above Ground Wall Area [m2] 1694.58 211.83 635.46 211.83 635.46
Window Opening Area [m2] 184.30 8.38 72.42 6.62 96.88
Gross Window-Wall Ratio [%] 10.88 3.95 11.40 3.13 15.25
Above Ground Window-Wall Ratio [%] 10.88 3.95 11.40 3.13 15.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 211.83 556.77 116.50 607.21
Above Ground Wall Area [m2] 1492.32 211.83 556.77 116.50 607.21
Window Opening Area [m2] 179.37 8.38 67.50 6.62 96.88
Gross Window-Wall Ratio [%] 12.02 3.95 12.12 5.68 15.96
Above Ground Window-Wall Ratio [%] 12.02 3.95 12.12 5.68 15.96


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 0.00 0.00 5.2743 18.59 0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 0.00 9.82 9.82 4.4132 18.58 0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 0.00 0.00 4.0903 46.47 0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 0.00 14.83 14.83 9.0417 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 0.00 0.00 6.7813 18.58 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 0.00 4.93 4.93 10.4410 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 0.00 0.00 4.6285 61.88 0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 0.00 1.64 1.64 4.4132 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 0.00 1.64 1.64 4.4132 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 0.00 1.64 1.64 4.4132 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 0.00 1.64 1.64 4.4132 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 0.00 1.64 1.64 4.4132 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 0.00 1.64 1.64 6.3507 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 0.00 4.93 4.93 5.7049 9.29 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.00 0.00 0.0000 61.94 1073.0223
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 0.00 1.64 1.64 9.6875 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 0.00 6.57 6.57 7.6155 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 0.00 0.00 5.2743 18.58 0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 0.00 0.00 4.0903 46.45 0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 0.00 0.00 5.2743 18.59 0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 0.00 2.62 2.62 4.4132 18.58 0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 0.00 0.00 4.0903 46.47 0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 0.00 1.65 1.65 4.4132 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 0.00 6.60 6.60 4.4132 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 0.00 6.71 6.71 4.4132 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 0.00 6.60 6.60 4.4132 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 0.00 1.65 1.65 4.4132 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 0.00 1.65 1.65 4.4132 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 0.00 6.60 6.60 4.4132 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.00 0.00 0.0000 61.94 0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 0.00 1.65 1.65 4.4132 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 0.00 6.60 6.60 4.4132 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 0.00 1.65 1.65 4.4132 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 0.00 0.00 4.0903 46.45 0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 0.00 0.00 5.2743 18.58 0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 0.00 0.00 5.2743 18.59 0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 0.00 2.62 2.62 4.4132 18.58 0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 0.00 0.00 4.0903 46.47 0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 0.00 1.65 1.65 4.4132 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 0.00 6.58 6.58 4.4132 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 0.00 6.70 6.70 4.4132 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 0.00 6.58 6.58 4.4132 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 0.00 1.65 1.65 4.4132 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 0.00 1.65 1.65 4.4132 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 0.00 6.58 6.58 4.4132 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.00 0.00 0.0000 61.94 0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 0.00 1.65 1.65 4.4132 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 0.00 6.58 6.58 4.4132 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 0.00 1.65 1.65 4.4132 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 0.00 0.00 4.0903 46.45 0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 0.00 0.00 5.2743 18.58 0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 0.00 0.00 5.2743 18.59 0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 0.00 2.62 2.62 4.4132 18.58 0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 0.00 0.00 4.0903 46.47 0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 0.00 1.65 1.65 4.4132 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 0.00 6.58 6.58 4.4132 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 0.00 6.70 6.70 4.4132 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 0.00 6.58 6.58 4.4132 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 0.00 1.65 1.65 4.4132 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 0.00 1.65 1.65 4.4132 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 0.00 6.58 6.58 4.4132 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.00 0.00 0.0000 61.94 0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 0.00 1.65 1.65 4.4132 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 0.00 6.58 6.58 4.4132 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 0.00 1.65 1.65 4.4132 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 0.00 0.00 4.0903 46.45 0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 0.00 0.00 5.2743 18.58 0.0000
Total 4013.58     11621.73   1694.58 0.00 184.30 184.30 4.8947 13.37 24.1524
Conditioned Total 3725.09     10741.65   1492.32 0.00 179.37 179.37 4.9807 13.04 10.1966
Unconditioned Total 288.49     880.07   202.26 0.00 4.93 4.93 3.7842 20.16 204.3559
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
REARSTAIRSFLR1 20.07 Yes Yes 1.00 REARSTAIRSFLR1 GENERAL REARSTAIRSFLR1 5.2743 18.59 0.0000  
CORRIDORFLR1 150.51 Yes Yes 1.00 CORRIDORFLR1 GENERAL CORRIDORFLR1 4.4132 18.58 0.0000  
REARSTORAGEFLR1 20.07 No Yes 1.00 REARSTORAGEFLR1 GENERAL REARSTORAGEFLR1 4.0903 46.47 0.0000  
FRONTLOUNGEFLR1 163.06 Yes Yes 1.00 FRONTLOUNGEFLR1 GENERAL FRONTLOUNGEFLR1 9.0417 3.08 26.0600  
RESTROOMFLR1 32.61 Yes Yes 1.00 RESTROOMFLR1 GENERAL RESTROOMFLR1 6.7813 18.58 0.0000  
MEETINGROOMFLR1 80.27 Yes Yes 1.00 MEETINGROOMFLR1 GENERAL MEETINGROOMFLR1 10.4410 1.87 6.1800  
MECHANICALROOMFLR1 32.61 Yes Yes 1.00 MECHANICALROOMFLR1 GENERAL MECHANICALROOMFLR1 4.6285 61.88 0.0000  
GUESTROOM101 32.61 Yes Yes 1.00 GUESTROOM101 GENERAL GUESTROOM101 4.4132 21.74 11.8935  
GUESTROOM102 32.61 Yes Yes 1.00 GUESTROOM102 GENERAL GUESTROOM102 4.4132 21.74 11.8935  
GUESTROOM103 32.61 Yes Yes 1.00 GUESTROOM103 GENERAL GUESTROOM103 4.4132 21.74 11.8935  
GUESTROOM104 32.61 Yes Yes 1.00 GUESTROOM104 GENERAL GUESTROOM104 4.4132 21.74 11.8935  
GUESTROOM105 32.61 Yes Yes 1.00 GUESTROOM105 GENERAL GUESTROOM105 4.4132 21.74 11.8935  
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 1.00 EMPLOYEELOUNGEFLR1 GENERAL EMPLOYEELOUNGEFLR1 6.3507 1.81 21.5100  
LAUNDRYROOMFLR1 97.83 No Yes 1.00 LAUNDRYROOMFLR1 GENERAL LAUNDRYROOMFLR1 5.7049 9.29 437.5596  
ELEVATORCOREFLR1 15.05 No Yes 1.00 ELEVATORCOREFLR1 GENERAL ELEVATORCOREFLR1 0.0000 61.94 1073.0223  
EXERCISECENTERFLR1 32.61 Yes Yes 1.00 EXERCISECENTERFLR1 GENERAL EXERCISECENTERFLR1 9.6875 4.66 18.5900  
FRONTOFFICEFLR1 130.44 Yes Yes 1.00 FRONTOFFICEFLR1 GENERAL FRONTOFFICEFLR1 7.6155 13.04 13.7800  
FRONTSTAIRSFLR1 20.07 Yes Yes 1.00 FRONTSTAIRSFLR1 GENERAL FRONTSTAIRSFLR1 5.2743 18.58 0.0000  
FRONTSTORAGEFLR1 12.54 No Yes 1.00 FRONTSTORAGEFLR1 GENERAL FRONTSTORAGEFLR1 4.0903 46.45 0.0000  
REARSTAIRSFLR2 20.07 Yes Yes 1.00 REARSTAIRSFLR2 GENERAL REARSTAIRSFLR2 5.2743 18.59 0.0000  
CORRIDORFLR2 125.42 Yes Yes 1.00 CORRIDORFLR2 GENERAL CORRIDORFLR2 4.4132 18.58 0.0000  
REARSTORAGEFLR2 20.07 No Yes 1.00 REARSTORAGEFLR2 GENERAL REARSTORAGEFLR2 4.0903 46.47 0.0000  
GUESTROOM201 32.61 Yes Yes 1.00 GUESTROOM201 GENERAL GUESTROOM201 4.4132 21.74 11.8935  
GUESTROOM202_205 130.45 Yes Yes 1.00 GUESTROOM202_205 GENERAL GUESTROOM202_205 4.4132 21.74 11.8935  
GUESTROOM206_208 105.36 Yes Yes 1.00 GUESTROOM206_208 GENERAL GUESTROOM206_208 4.4132 23.41 11.8935  
GUESTROOM209_212 130.45 Yes Yes 1.00 GUESTROOM209_212 GENERAL GUESTROOM209_212 4.4132 21.74 11.8935  
GUESTROOM213 32.61 Yes Yes 1.00 GUESTROOM213 GENERAL GUESTROOM213 4.4132 21.74 11.8935  
GUESTROOM214 32.61 Yes Yes 1.00 GUESTROOM214 GENERAL GUESTROOM214 4.4132 21.74 11.8935  
GUESTROOM215_218 130.44 Yes Yes 1.00 GUESTROOM215_218 GENERAL GUESTROOM215_218 4.4132 21.74 11.8935  
ELEVATORCOREFLR2 15.05 No Yes 1.00 ELEVATORCOREFLR2 GENERAL ELEVATORCOREFLR2 0.0000 61.94 0.0000  
GUESTROOM219 32.61 Yes Yes 1.00 GUESTROOM219 GENERAL GUESTROOM219 4.4132 21.74 11.8935  
GUESTROOM220_223 130.44 Yes Yes 1.00 GUESTROOM220_223 GENERAL GUESTROOM220_223 4.4132 21.74 11.8935  
GUESTROOM224 32.61 Yes Yes 1.00 GUESTROOM224 GENERAL GUESTROOM224 4.4132 21.74 11.8935  
FRONTSTORAGEFLR2 12.54 No Yes 1.00 FRONTSTORAGEFLR2 GENERAL FRONTSTORAGEFLR2 4.0903 46.45 0.0000  
FRONTSTAIRSFLR2 20.07 Yes Yes 1.00 FRONTSTAIRSFLR2 GENERAL FRONTSTAIRSFLR2 5.2743 18.58 0.0000  
REARSTAIRSFLR3 20.07 Yes Yes 1.00 REARSTAIRSFLR3 GENERAL REARSTAIRSFLR3 5.2743 18.59 0.0000  
CORRIDORFLR3 125.42 Yes Yes 1.00 CORRIDORFLR3 GENERAL CORRIDORFLR3 4.4132 18.58 0.0000  
REARSTORAGEFLR3 20.07 No Yes 1.00 REARSTORAGEFLR3 GENERAL REARSTORAGEFLR3 4.0903 46.47 0.0000  
GUESTROOM301 32.61 Yes Yes 1.00 GUESTROOM301 GENERAL GUESTROOM301 4.4132 21.74 11.8935  
GUESTROOM302_305 130.45 Yes Yes 1.00 GUESTROOM302_305 GENERAL GUESTROOM302_305 4.4132 21.74 11.8935  
GUESTROOM306_308 105.36 Yes Yes 1.00 GUESTROOM306_308 GENERAL GUESTROOM306_308 4.4132 23.41 11.8935  
GUESTROOM309_312 130.45 Yes Yes 1.00 GUESTROOM309_312 GENERAL GUESTROOM309_312 4.4132 21.74 11.8935  
GUESTROOM313 32.61 Yes Yes 1.00 GUESTROOM313 GENERAL GUESTROOM313 4.4132 21.74 11.8935  
GUESTROOM314 32.61 Yes Yes 1.00 GUESTROOM314 GENERAL GUESTROOM314 4.4132 21.74 11.8935  
GUESTROOM315_318 130.44 Yes Yes 1.00 GUESTROOM315_318 GENERAL GUESTROOM315_318 4.4132 21.74 11.8935  
ELEVATORCOREFLR3 15.05 No Yes 1.00 ELEVATORCOREFLR3 GENERAL ELEVATORCOREFLR3 0.0000 61.94 0.0000  
GUESTROOM319 32.61 Yes Yes 1.00 GUESTROOM319 GENERAL GUESTROOM319 4.4132 21.74 11.8935  
GUESTROOM320_323 130.44 Yes Yes 1.00 GUESTROOM320_323 GENERAL GUESTROOM320_323 4.4132 21.74 11.8935  
GUESTROOM324 32.61 Yes Yes 1.00 GUESTROOM324 GENERAL GUESTROOM324 4.4132 21.74 11.8935  
FRONTSTORAGEFLR3 12.54 No Yes 1.00 FRONTSTORAGEFLR3 GENERAL FRONTSTORAGEFLR3 4.0903 46.45 0.0000  
FRONTSTAIRSFLR3 20.07 Yes Yes 1.00 FRONTSTAIRSFLR3 GENERAL FRONTSTAIRSFLR3 5.2743 18.58 0.0000  
REARSTAIRSFLR4 20.07 Yes Yes 1.00 REARSTAIRSFLR4 GENERAL REARSTAIRSFLR4 5.2743 18.59 0.0000  
CORRIDORFLR4 125.42 Yes Yes 1.00 CORRIDORFLR4 GENERAL CORRIDORFLR4 4.4132 18.58 0.0000  
REARSTORAGEFLR4 20.07 No Yes 1.00 REARSTORAGEFLR4 GENERAL REARSTORAGEFLR4 4.0903 46.47 0.0000  
GUESTROOM401 32.61 Yes Yes 1.00 GUESTROOM401 GENERAL GUESTROOM401 4.4132 21.74 11.8935  
GUESTROOM402_405 130.45 Yes Yes 1.00 GUESTROOM402_405 GENERAL GUESTROOM402_405 4.4132 21.74 11.8935  
GUESTROOM406_408 105.36 Yes Yes 1.00 GUESTROOM406_408 GENERAL GUESTROOM406_408 4.4132 23.41 11.8935  
GUESTROOM409_412 130.45 Yes Yes 1.00 GUESTROOM409_412 GENERAL GUESTROOM409_412 4.4132 21.74 11.8935  
GUESTROOM413 32.61 Yes Yes 1.00 GUESTROOM413 GENERAL GUESTROOM413 4.4132 21.74 11.8935  
GUESTROOM414 32.61 Yes Yes 1.00 GUESTROOM414 GENERAL GUESTROOM414 4.4132 21.74 11.8935  
GUESTROOM415_418 130.44 Yes Yes 1.00 GUESTROOM415_418 GENERAL GUESTROOM415_418 4.4132 21.74 11.8935  
ELEVATORCOREFLR4 15.05 No Yes 1.00 ELEVATORCOREFLR4 GENERAL ELEVATORCOREFLR4 0.0000 61.94 0.0000  
GUESTROOM419 32.61 Yes Yes 1.00 GUESTROOM419 GENERAL GUESTROOM419 4.4132 21.74 11.8935  
GUESTROOM420_423 130.44 Yes Yes 1.00 GUESTROOM420_423 GENERAL GUESTROOM420_423 4.4132 21.74 11.8935  
GUESTROOM424 32.61 Yes Yes 1.00 GUESTROOM424 GENERAL GUESTROOM424 4.4132 21.74 11.8935  
FRONTSTORAGEFLR4 12.54 No Yes 1.00 FRONTSTORAGEFLR4 GENERAL FRONTSTORAGEFLR4 4.0903 46.45 0.0000  
FRONTSTAIRSFLR4 20.07 Yes Yes 1.00 FRONTSTAIRSFLR4 GENERAL FRONTSTAIRSFLR4 5.2743 18.58 0.0000  
Total 4013.58             4.8947 6.69 24.1524  
Conditioned Total 3725.09             4.9807 6.52 10.1966  
Unconditioned Total 288.49             3.7842 10.08 204.3559  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 4013.58 3725.09 288.49 0.00 4.8947 13.37 24.1524
Total 4013.58 3725.09 288.49 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 02-FEB-07:10 02-FEB-09:39 - - - - - - - - - - 01-JAN-08:09
Heating 153452.85 31992.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 7568.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 3177.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 31369.28 40096.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 10742.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 8.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 84539.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 206318.75 156628.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 153452.85 31992.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 7568.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 3177.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 23294.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 8012.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 62.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 40096.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 10742.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 8.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 84539.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 902.48 110.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 712.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 631.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 157.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1493.13 456.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 901.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1158.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 4800.17 1726.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 242.27 29.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 191.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 169.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 42.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 400.83 122.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 242.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 311.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1288.61 463.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 224.86 27.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 177.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 157.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 39.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 372.02 113.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 224.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 288.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1195.98 430.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

ZoneHVAC:UnitHeater

Design Size Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNIT HEATER 0.006118
MECHANICALROOMFLR1 UNIT HEATER 0.000000
FRONTSTAIRSFLR1 UNIT HEATER 0.006116
REARSTAIRSFLR2 UNIT HEATER 0.006118
FRONTSTAIRSFLR2 UNIT HEATER 0.006116
REARSTAIRSFLR3 UNIT HEATER 0.006118
FRONTSTAIRSFLR3 UNIT HEATER 0.006116
REARSTAIRSFLR4 UNIT HEATER 0.006118
FRONTSTAIRSFLR4 UNIT HEATER 0.012078
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER FAN 0.006118
MECHRM UNITHEATER FAN 0.000000
FRONTSTAIRSFLR1 UNITHEATER FAN 0.006116
REARSTAIRSFLR2 UNITHEATER FAN 0.006118
FRONTSTAIRSFLR2 UNITHEATER FAN 0.006116
REARSTAIRSFLR3 UNITHEATER FAN 0.006118
FRONTSTAIRSFLR3 UNITHEATER FAN 0.006116
REARSTAIRSFLR4 UNITHEATER FAN 0.006118
FRONTSTAIRSFLR4 UNITHEATER FAN 0.012078
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
REARSTAIRSFLR1 UNITHEATER HEATING COIL 306.67
CORRIDORFLR1 PTAC HEATING COIL 76487.20
MECHRM UNITHEATER HEATING COIL 0.000000
101 PTAC HEATING COIL 1279.86
102 PTAC HEATING COIL 1343.44
103 PTAC HEATING COIL 1868.29
104 PTAC HEATING COIL 1891.34
105 PTAC HEATING COIL 1342.11
FRONTSTAIRSFLR1 UNITHEATER HEATING COIL 306.62
REARSTAIRSFLR2 UNITHEATER HEATING COIL 306.67
CORRIDORFLR2 PTAC HEATING COIL 4060.99
201 PTAC HEATING COIL 1771.23
202_205 PTAC HEATING COIL 4908.57
206_208 PTAC HEATING COIL 3860.93
209_212 PTAC HEATING COIL 4812.02
213 PTAC HEATING COIL 1741.29
214 PTAC HEATING COIL 1734.89
215_218 PTAC HEATING COIL 4811.67
219 PTAC HEATING COIL 1202.92
220_223 PTAC HEATING COIL 4811.67
224 PTAC HEATING COIL 1545.17
FRONTSTAIRSFLR2 UNITHEATER HEATING COIL 306.62
REARSTAIRSFLR3 UNITHEATER HEATING COIL 306.67
CORRIDORFLR3 PTAC HEATING COIL 4366.46
301 PTAC HEATING COIL 1842.00
302_305 PTAC HEATING COIL 5032.36
306_308 PTAC HEATING COIL 4052.85
309_312 PTAC HEATING COIL 5009.43
313 PTAC HEATING COIL 1833.95
314 PTAC HEATING COIL 1804.07
315_318 PTAC HEATING COIL 4970.13
319 PTAC HEATING COIL 1308.61
320_323 PTAC HEATING COIL 4897.96
324 PTAC HEATING COIL 1608.14
FRONTSTAIRSFLR3 UNITHEATER HEATING COIL 306.62
REARSTAIRSFLR4 UNITHEATER HEATING COIL 306.69
CORRIDORFLR4 PTAC HEATING COIL 5798.44
401 PTAC HEATING COIL 2408.72
402_405 PTAC HEATING COIL 6290.63
406_408 PTAC HEATING COIL 5076.57
409_412 PTAC HEATING COIL 6281.93
413 PTAC HEATING COIL 2291.33
414 PTAC HEATING COIL 2202.50
415_418 PTAC HEATING COIL 6227.35
419 PTAC HEATING COIL 1708.85
420_423 PTAC HEATING COIL 5819.44
424 PTAC HEATING COIL 1991.94
FRONTSTAIRSFLR4 UNITHEATER HEATING COIL 605.48
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:PackagedTerminalAirConditioner

Design Size Cooling Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size No Load Supply Air Flow Rate [m3/s] Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s]
CORRIDORFLR1 PTAC 2.18 2.18 2.18 0.045874 0.045874 0.045874
101 PTAC 0.119873 0.119873 0.119873 0.013480 0.013480 0.013480
102 PTAC 0.097243 0.097243 0.097243 0.013480 0.013480 0.013480
103 PTAC 0.175460 0.175460 0.175460 0.013480 0.013480 0.013480
104 PTAC 0.182500 0.182500 0.182500 0.013479 0.013479 0.013479
105 PTAC 0.262821 0.262821 0.262821 0.013479 0.013479 0.013479
CORRIDORFLR2 PTAC 0.261872 0.261872 0.261872 0.038228 0.038228 0.038228
201 PTAC 0.134993 0.134993 0.134993 0.013480 0.013480 0.013480
202_205 PTAC 0.696413 0.696413 0.696413 0.053919 0.053919 0.053919
206_208 PTAC 0.575671 0.575671 0.575671 0.042733 0.042733 0.042733
209_212 PTAC 0.642785 0.642785 0.642785 0.053919 0.053919 0.053919
213 PTAC 0.176672 0.176672 0.176672 0.013480 0.013480 0.013480
214 PTAC 0.198049 0.198049 0.198049 0.013479 0.013479 0.013479
215_218 PTAC 1.95 1.95 1.95 0.053915 0.053915 0.053915
219 PTAC 1.04 1.04 1.04 0.013479 0.013479 0.013479
220_223 PTAC 0.659979 0.659979 0.659979 0.053915 0.053915 0.053915
224 PTAC 0.188615 0.188615 0.188615 0.013479 0.013479 0.013479
CORRIDORFLR3 PTAC 0.085830 0.085830 0.085830 0.038228 0.038228 0.038228
301 PTAC 0.098542 0.098542 0.098542 0.013480 0.013480 0.013480
302_305 PTAC 0.317885 0.317885 0.317885 0.053919 0.053919 0.053919
306_308 PTAC 0.289135 0.289135 0.289135 0.042733 0.042733 0.042733
309_312 PTAC 0.612690 0.612690 0.612690 0.053919 0.053919 0.053919
313 PTAC 0.108776 0.108776 0.108776 0.013480 0.013480 0.013480
314 PTAC 0.171187 0.171187 0.171187 0.013479 0.013479 0.013479
315_318 PTAC 0.753324 0.753324 0.753324 0.053915 0.053915 0.053915
319 PTAC 0.177887 0.177887 0.177887 0.013479 0.013479 0.013479
320_323 PTAC 0.590153 0.590153 0.590153 0.053915 0.053915 0.053915
324 PTAC 0.103341 0.103341 0.103341 0.013479 0.013479 0.013479
CORRIDORFLR4 PTAC 0.141289 0.141289 0.141289 0.038228 0.038228 0.038228
401 PTAC 0.210090 0.210090 0.210090 0.013480 0.013480 0.013480
402_405 PTAC 0.428969 0.428969 0.428969 0.053919 0.053919 0.053919
406_408 PTAC 0.385391 0.385391 0.385391 0.042733 0.042733 0.042733
409_412 PTAC 0.761081 0.761081 0.761081 0.053919 0.053919 0.053919
413 PTAC 0.152627 0.152627 0.152627 0.013480 0.013480 0.013480
414 PTAC 0.133173 0.133173 0.133173 0.013479 0.013479 0.013479
415_418 PTAC 0.752437 0.752437 0.752437 0.053915 0.053915 0.053915
419 PTAC 0.204053 0.204053 0.204053 0.013479 0.013479 0.013479
420_423 PTAC 0.696755 0.696755 0.696755 0.053915 0.053915 0.053915
424 PTAC 0.199388 0.199388 0.199388 0.013479 0.013479 0.013479
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
CORRIDORFLR1 PTAC PTAC COOLING COIL 2.18 41350.04 0.797836
101 PTAC PTAC COOLING COIL 0.119873 1984.33 0.800655
102 PTAC PTAC COOLING COIL 0.097243 1609.72 0.800655
103 PTAC PTAC COOLING COIL 0.175460 2904.49 0.800655
104 PTAC PTAC COOLING COIL 0.182500 3021.03 0.800655
105 PTAC PTAC COOLING COIL 0.262821 4350.62 0.800655
CORRIDORFLR2 PTAC PTAC COOLING COIL 0.261872 4334.91 0.800655
201 PTAC PTAC COOLING COIL 0.134993 2234.62 0.800655
202_205 PTAC PTAC COOLING COIL 0.696413 11528.11 0.800655
206_208 PTAC PTAC COOLING COIL 0.575671 9529.40 0.800655
209_212 PTAC PTAC COOLING COIL 0.642785 10640.37 0.800655
213 PTAC PTAC COOLING COIL 0.176672 2924.56 0.800655
214 PTAC PTAC COOLING COIL 0.198049 3278.41 0.800655
215_218 PTAC PTAC COOLING COIL 1.95 32246.13 0.800655
219 PTAC PTAC COOLING COIL 1.04 17172.47 0.800655
220_223 PTAC PTAC COOLING COIL 0.659979 10924.99 0.800655
224 PTAC PTAC COOLING COIL 0.188615 3122.25 0.800655
CORRIDORFLR3 PTAC PTAC COOLING COIL 0.085830 1932.59 0.732293
301 PTAC PTAC COOLING COIL 0.098542 1631.22 0.800655
302_305 PTAC PTAC COOLING COIL 0.317885 5262.13 0.800655
306_308 PTAC PTAC COOLING COIL 0.289135 4786.20 0.800655
309_312 PTAC PTAC COOLING COIL 0.612690 10142.20 0.800655
313 PTAC PTAC COOLING COIL 0.108776 1800.62 0.800655
314 PTAC PTAC COOLING COIL 0.171187 2833.75 0.800655
315_318 PTAC PTAC COOLING COIL 0.753324 12470.18 0.800655
319 PTAC PTAC COOLING COIL 0.177887 2944.66 0.800655
320_323 PTAC PTAC COOLING COIL 0.590153 9769.13 0.800655
324 PTAC PTAC COOLING COIL 0.103341 1710.66 0.800655
CORRIDORFLR4 PTAC PTAC COOLING COIL 0.141289 2867.53 0.770870
401 PTAC PTAC COOLING COIL 0.210090 3477.74 0.800655
402_405 PTAC PTAC COOLING COIL 0.428969 7100.96 0.800655
406_408 PTAC PTAC COOLING COIL 0.385391 6379.59 0.800655
409_412 PTAC PTAC COOLING COIL 0.761081 12598.60 0.800655
413 PTAC PTAC COOLING COIL 0.152627 2526.52 0.800655
414 PTAC PTAC COOLING COIL 0.133173 2204.48 0.800655
415_418 PTAC PTAC COOLING COIL 0.752437 12455.50 0.800655
419 PTAC PTAC COOLING COIL 0.204053 3377.81 0.800655
420_423 PTAC PTAC COOLING COIL 0.696755 11533.78 0.800655
424 PTAC PTAC COOLING COIL 0.199388 3300.57 0.800655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
CORRIDORFLR1 PTAC SUPPLY FAN 2.18
101 PTAC SUPPLY FAN 0.119873
102 PTAC SUPPLY FAN 0.097243
103 PTAC SUPPLY FAN 0.175460
104 PTAC SUPPLY FAN 0.182500
105 PTAC SUPPLY FAN 0.262821
CORRIDORFLR2 PTAC SUPPLY FAN 0.261872
201 PTAC SUPPLY FAN 0.134993
202_205 PTAC SUPPLY FAN 0.696413
206_208 PTAC SUPPLY FAN 0.575671
209_212 PTAC SUPPLY FAN 0.642785
213 PTAC SUPPLY FAN 0.176672
214 PTAC SUPPLY FAN 0.198049
215_218 PTAC SUPPLY FAN 1.95
219 PTAC SUPPLY FAN 1.04
220_223 PTAC SUPPLY FAN 0.659979
224 PTAC SUPPLY FAN 0.188615
CORRIDORFLR3 PTAC SUPPLY FAN 0.085830
301 PTAC SUPPLY FAN 0.098542
302_305 PTAC SUPPLY FAN 0.317885
306_308 PTAC SUPPLY FAN 0.289135
309_312 PTAC SUPPLY FAN 0.612690
313 PTAC SUPPLY FAN 0.108776
314 PTAC SUPPLY FAN 0.171187
315_318 PTAC SUPPLY FAN 0.753324
319 PTAC SUPPLY FAN 0.177887
320_323 PTAC SUPPLY FAN 0.590153
324 PTAC SUPPLY FAN 0.103341
CORRIDORFLR4 PTAC SUPPLY FAN 0.141289
401 PTAC SUPPLY FAN 0.210090
402_405 PTAC SUPPLY FAN 0.428969
406_408 PTAC SUPPLY FAN 0.385391
409_412 PTAC SUPPLY FAN 0.761081
413 PTAC SUPPLY FAN 0.152627
414 PTAC SUPPLY FAN 0.133173
415_418 PTAC SUPPLY FAN 0.752437
419 PTAC SUPPLY FAN 0.204053
420_423 PTAC SUPPLY FAN 0.696755
424 PTAC SUPPLY FAN 0.199388
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 1.03
RESTROOMFLR1 DIRECT AIR 0.082820
MEETINGROOMFLR1 DIRECT AIR 0.461335
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.826090
EXERCISECENTERFLR1 DIRECT AIR 0.158196
FRONTOFFICEFLR1 DIRECT AIR 0.403869
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.403869 0.403869 0.403869 0.403869 0.403869 0.403869 1.00 1.00 0.403869
SAC_FRONTLOUNGE 1.03 1.03 1.03 1.03 1.03 1.03 1.00 1.00 1.03
SAC_MEETINGROOM 0.461335 0.461335 0.461335 0.461335 0.461335 0.461335 1.00 1.00 0.461335
SAC_EMPLOYEELOUNGE 0.826090 0.826090 0.826090 0.826090 0.826090 0.826090 1.00 1.00 0.826090
SAC_EXERCISECENTER 0.158196 0.158196 0.158196 0.158196 0.158196 0.158196 1.00 1.00 0.158196
SAC_RESTROOM 0.082820 0.082820 0.082820 0.082820 0.082820 0.082820 1.00 1.00 0.082820
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE_OA_CONTROLLER 0.403869 0.063354
SAC_FRONTLOUNGE_OA_CONTROLLER 1.03  
SAC_MEETINGROOM_OA_CONTROLLER 0.461335 0.125936
SAC_EMPLOYEELOUNGE_OA_CONTROLLER 0.826090 0.052414
SAC_EXERCISECENTER_OA_CONTROLLER 0.158196 0.076012
SAC_RESTROOM_OA_CONTROLLER 0.082820 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
SAC_FRONTOFFICE_ADDAQ SUPPLY FAN 0.403869 452.38
SAC_FRONTLOUNGE_ADDAQ SUPPLY FAN 1.03 1136.10
SAC_MEETINGROOM_ADDAQ SUPPLY FAN 0.461335 516.74
SAC_EMPLOYEELOUNGE_ADDAQ SUPPLY FAN 0.826090 914.61
SAC_EXERCISECENTER_ADDAQ SUPPLY FAN 0.158196 177.20
SAC_RESTROOM_ADDAQ SUPPLY FAN 0.082820 92.77
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitarySystem

Design Size Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size Cooling Supply Air Flow Rate [m3/s] Design Size No Load Supply Air Flow Rate [m3/s] User-Specified Nominal Cooling Capacity [W] Design Size Nominal Heating Capacity [W] Design Size Maximum Supply Air Temperature [C] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE_UNITARY_PACKAGE_DX 0.403869 0.403869 0.403869 0.403869 7988.38 12264.01 40.00 1.00
SAC_FRONTLOUNGE_UNITARY_PACKAGE_DX 1.03 1.03 1.03 0.677251 23116.92 35327.96 40.00 1.00
SAC_MEETINGROOM_UNITARY_PACKAGE_DX 0.461335 0.461335 0.461335 0.461335 11416.48 16933.96 40.00 1.00
SAC_EMPLOYEELOUNGE_UNITARY_PACKAGE_DX 0.826090 0.826090 0.826090 0.826090 14670.50 20871.37 40.00 1.00
SAC_EXERCISECENTER_UNITARY_PACKAGE_DX 0.158196 0.158196 0.158196 0.158196 3848.78 7599.15 40.00 1.00
SAC_RESTROOM_UNITARY_PACKAGE_DX 0.082820 0.082820 0.082820 0.082820 1370.97 1805.54 40.00 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:MultiSpeed

User-Specified Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] User-Specified Speed 2 Rated Sensible Heat Ratio User-Specified Speed 1 Rated Sensible Heat Ratio
SAC_FRONTOFFICE COOLING COIL 0.403870 0.201935 0.269247 7988.38 3994.19 0.780690 0.780690
SAC_FRONTLOUNGE COOLING COIL 1.03 0.513069 0.684093 23116.92 11558.46 0.732150 0.732150
SAC_MEETINGROOM COOLING COIL 0.461330 0.230667 0.307553 11416.48 5708.24 0.702930 0.702930
SAC_EMPLOYEELOUNGE COOLING COIL 0.826090 0.413045 0.550727 14670.50 7335.25 0.800700 0.800700
SAC_EXERCISECENTER COOLING COIL 0.158200 0.079098 0.105467 3848.78 1924.39 0.708150 0.708150
SAC_RESTROOM COOLING COIL 0.082820 0.041410 0.055213 1370.97 685.49 0.800660 0.800660
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 12264.01
SAC_FRONTLOUNGE HEATING COIL 35327.96
SAC_MEETINGROOM HEATING COIL 16933.96
SAC_EMPLOYEELOUNGE HEATING COIL 20871.37
SAC_EXERCISECENTER HEATING COIL 7599.15
SAC_RESTROOM HEATING COIL 1805.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYSSHOWER 0.000180 0.021594
SWHSYSLAUNDRY 0.000129 0.015520
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYSSHOWER PUMP 0.000180 8.11
SWHSYSLAUNDRY PUMP 0.000129 0.000001
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWH SHOWER WATER HEATER 0.000180
SWH LAUNDRY WATER HEATER 0.000129
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
ENTRY CANOPY W_CORRIDORFLR1_16_0_0 | W_FRONTLOUNGEFLR1_4_0_0 | W_FRONTSTAIRSFLR1_4_0_0 | W_CORRIDORFLR2_15_0_0 | W_GUESTROOM201_4_0_0 | W_FRONTSTAIRSFLR2_4_0_0 | W_CORRIDORFLR3_15_0_0 | W_GUESTROOM301_4_0_0 | W_FRONTSTAIRSFLR3_4_0_0 | W_CORRIDORFLR4_15_0_0 | W_GUESTROOM401_4_0_0 | W_FRONTSTAIRSFLR4_4_0_0 |
Mir-ENTRY CANOPY W_CORRIDORFLR1_16_0_0 | W_FRONTLOUNGEFLR1_4_0_0 | W_FRONTSTAIRSFLR1_4_0_0 |
W_CORRIDORFLR1_16_0_0 Mir-ENTRY CANOPY |
W_FRONTLOUNGEFLR1_4_0_0 Mir-ENTRY CANOPY |
W_FRONTSTAIRSFLR1_4_0_0 Mir-ENTRY CANOPY |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
W_REARSTAIRSFLR1_3_0_0 W_REARSTAIRSFLR1_3_0_0_DOOR |
W_CORRIDORFLR1_2_0_0 W_CORRIDORFLR1_2_0_0_0_0 |
W_CORRIDORFLR1_10_0_0 W_CORRIDORFLR1_10_0_0_DOOR |
W_CORRIDORFLR1_16_0_0 D_CORRIDORFLR1_16_0_0_0_0 |
W_CORRIDORFLR1_20_0_0 W_CORRIDORFLR1_20_0_0_0_0 |
W_FRONTLOUNGEFLR1_5_0_0 W_FRONTLOUNGEFLR1_5_0_0_0_0 | W_FRONTLOUNGEFLR1_5_0_0_0_1 | W_FRONTLOUNGEFLR1_5_0_0_0_2 | W_FRONTLOUNGEFLR1_5_0_0_0_3 | W_FRONTLOUNGEFLR1_5_0_0_0_4 |
W_MEETINGROOMFLR1_5_0_0 W_MEETINGROOMFLR1_5_0_0_0_0 | W_MEETINGROOMFLR1_5_0_0_0_1 | W_MEETINGROOMFLR1_5_0_0_0_2 |
W_GUESTROOM101_5_0_0 W_GUESTROOM101_5_0_0_0_0 |
W_GUESTROOM102_5_0_0 W_GUESTROOM102_5_0_0_0_0 |
W_GUESTROOM103_5_0_0 W_GUESTROOM103_5_0_0_0_0 |
W_GUESTROOM104_3_0_0 W_GUESTROOM104_3_0_0_0_0 |
W_GUESTROOM105_3_0_0 W_GUESTROOM105_3_0_0_0_0 |
W_EMPLOYEELOUNGEFLR1_3_0_0 W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 |
W_LAUNDRYROOMFLR1_3_0_0 W_LAUNDRYROOMFLR1_3_0_0_0_0 | W_LAUNDRYROOMFLR1_3_0_0_0_1 | W_LAUNDRYROOMFLR1_3_0_0_0_2 |
W_EXERCISECENTERFLR1_3_0_0 W_EXERCISECENTERFLR1_3_0_0_0_0 |
W_FRONTOFFICEFLR1_3_0_0 W_FRONTOFFICEFLR1_3_0_0_0_0 | W_FRONTOFFICEFLR1_3_0_0_0_1 | W_FRONTOFFICEFLR1_3_0_0_0_2 | W_FRONTOFFICEFLR1_3_0_0_0_3 |
W_FRONTSTAIRSFLR1_3_0_0 W_FRONTSTAIRSFLR1_3_0_0_DOOR |
W_CORRIDORFLR2_2_0_0 W_CORRIDORFLR2_2_0_0_0_0 |
W_CORRIDORFLR2_15_0_0 W_CORRIDORFLR2_15_0_0_0_0 |
W_GUESTROOM201_5_0_0 W_GUESTROOM201_5_0_0_0_0 |
W_GUESTROOM202_205_5_0_0 W_GUESTROOM202_205_5_0_0_0_0 | W_GUESTROOM202_205_5_0_0_0_1 | W_GUESTROOM202_205_5_0_0_0_2 | W_GUESTROOM202_205_5_0_0_0_3 |
W_GUESTROOM206_208_5_0_0 W_GUESTROOM206_208_5_0_0_0_0 | W_GUESTROOM206_208_5_0_0_0_1 | W_GUESTROOM206_208_5_0_0_0_2 |
W_GUESTROOM209_212_5_0_0 W_GUESTROOM209_212_5_0_0_0_0 | W_GUESTROOM209_212_5_0_0_0_1 | W_GUESTROOM209_212_5_0_0_0_2 | W_GUESTROOM209_212_5_0_0_0_3 |
W_GUESTROOM213_5_0_0 W_GUESTROOM213_5_0_0_0_0 |
W_GUESTROOM214_3_0_0 W_GUESTROOM214_3_0_0_0_0 |
W_GUESTROOM215_218_3_0_0 W_GUESTROOM215_218_3_0_0_0_0 | W_GUESTROOM215_218_3_0_0_0_1 | W_GUESTROOM215_218_3_0_0_0_2 | W_GUESTROOM215_218_3_0_0_0_3 |
W_GUESTROOM219_3_0_0 W_GUESTROOM219_3_0_0_0_0 |
W_GUESTROOM220_223_3_0_0 W_GUESTROOM220_223_3_0_0_0_0 | W_GUESTROOM220_223_3_0_0_0_1 | W_GUESTROOM220_223_3_0_0_0_2 | W_GUESTROOM220_223_3_0_0_0_3 |
W_GUESTROOM224_3_0_0 W_GUESTROOM224_3_0_0_0_0 |
W_CORRIDORFLR3_2_0_0 W_CORRIDORFLR3_2_0_0_0_0 |
W_CORRIDORFLR3_15_0_0 W_CORRIDORFLR3_15_0_0_0_0 |
W_GUESTROOM301_5_0_0 W_GUESTROOM301_5_0_0_0_0 |
W_GUESTROOM302_305_5_0_0 W_GUESTROOM302_305_5_0_0_0_0 | W_GUESTROOM302_305_5_0_0_0_1 | W_GUESTROOM302_305_5_0_0_0_2 | W_GUESTROOM302_305_5_0_0_0_3 |
W_GUESTROOM306_308_5_0_0 W_GUESTROOM306_308_5_0_0_0_0 | W_GUESTROOM306_308_5_0_0_0_1 | W_GUESTROOM306_308_5_0_0_0_2 |
W_GUESTROOM309_312_5_0_0 W_GUESTROOM309_312_5_0_0_0_0 | W_GUESTROOM309_312_5_0_0_0_1 | W_GUESTROOM309_312_5_0_0_0_2 | W_GUESTROOM309_312_5_0_0_0_3 |
W_GUESTROOM313_5_0_0 W_GUESTROOM313_5_0_0_0_0 |
W_GUESTROOM314_3_0_0 W_GUESTROOM314_3_0_0_0_0 |
W_GUESTROOM315_318_3_0_0 W_GUESTROOM315_318_3_0_0_0_0 | W_GUESTROOM315_318_3_0_0_0_1 | W_GUESTROOM315_318_3_0_0_0_2 | W_GUESTROOM315_318_3_0_0_0_3 |
W_GUESTROOM319_3_0_0 W_GUESTROOM319_3_0_0_0_0 |
W_GUESTROOM320_323_3_0_0 W_GUESTROOM320_323_3_0_0_0_0 | W_GUESTROOM320_323_3_0_0_0_1 | W_GUESTROOM320_323_3_0_0_0_2 | W_GUESTROOM320_323_3_0_0_0_3 |
W_GUESTROOM324_3_0_0 W_GUESTROOM324_3_0_0_0_0 |
W_CORRIDORFLR4_2_0_0 W_CORRIDORFLR4_2_0_0_0_0 |
W_CORRIDORFLR4_15_0_0 W_CORRIDORFLR4_15_0_0_0_0 |
W_GUESTROOM401_5_0_0 W_GUESTROOM401_5_0_0_0_0 |
W_GUESTROOM402_405_5_0_0 W_GUESTROOM402_405_5_0_0_0_0 | W_GUESTROOM402_405_5_0_0_0_1 | W_GUESTROOM402_405_5_0_0_0_2 | W_GUESTROOM402_405_5_0_0_0_3 |
W_GUESTROOM406_408_5_0_0 W_GUESTROOM406_408_5_0_0_0_0 | W_GUESTROOM406_408_5_0_0_0_1 | W_GUESTROOM406_408_5_0_0_0_2 |
W_GUESTROOM409_412_5_0_0 W_GUESTROOM409_412_5_0_0_0_0 | W_GUESTROOM409_412_5_0_0_0_1 | W_GUESTROOM409_412_5_0_0_0_2 | W_GUESTROOM409_412_5_0_0_0_3 |
W_GUESTROOM413_5_0_0 W_GUESTROOM413_5_0_0_0_0 |
W_GUESTROOM414_3_0_0 W_GUESTROOM414_3_0_0_0_0 |
W_GUESTROOM415_418_3_0_0 W_GUESTROOM415_418_3_0_0_0_0 | W_GUESTROOM415_418_3_0_0_0_1 | W_GUESTROOM415_418_3_0_0_0_2 | W_GUESTROOM415_418_3_0_0_0_3 |
W_GUESTROOM419_3_0_0 W_GUESTROOM419_3_0_0_0_0 |
W_GUESTROOM420_423_3_0_0 W_GUESTROOM420_423_3_0_0_0_0 | W_GUESTROOM420_423_3_0_0_0_1 | W_GUESTROOM420_423_3_0_0_0_2 | W_GUESTROOM420_423_3_0_0_0_3 |
W_GUESTROOM424_3_0_0 W_GUESTROOM424_3_0_0_0_0 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 7.40 -0.00 -7.60 -12.60 -7.70 0.30 7.00 14.20 19.20 20.90 20.00 15.40


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Rochester International Arpt MN USA TMY3 WMO#=726440 43.90 -92.50 -6.00 398.00 96634 1.1486


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 6.38 33.50 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelSmall 90.000 Suburbs 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.220 370.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 2


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 67 591 106


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 REARSTAIRSFLR1 0.0 0.00 0.00 0.00 14.22 -53.69 1.68 1 1 1 10.11 18.34 -54.91 -52.47 0.00 3.35 3.35 67.30 TARP TARP 20.07 35.77 33.82 0.00 6 1 0 Yes
2 CORRIDORFLR1 0.0 0.00 0.00 0.00 9.43 -26.68 1.68 1 1 1 4.88E-002 18.34 -54.91 -4.87E-002 0.00 3.35 3.35 504.62 TARP TARP 150.51 32.70 20.94 9.82 29 4 2 Yes
3 REARSTORAGEFLR1 0.0 0.00 0.00 0.00 4.16 -53.69 1.68 1 1 1 4.88E-002 8.28 -54.91 -52.47 0.00 3.35 3.35 67.30 TARP TARP 20.07 35.77 35.77 0.00 6 0 0 Yes
4 FRONTLOUNGEFLR1 0.0 0.00 0.00 0.00 4.16 -9.95 1.68 1 1 1 4.88E-002 8.28 -19.86 -4.87E-002 0.00 3.35 3.35 546.70 TARP TARP 163.06 94.02 79.19 14.83 7 5 0 Yes
5 RESTROOMFLR1 0.0 0.00 0.00 0.00 4.16 -21.84 1.68 1 1 1 4.88E-002 8.28 -23.82 -19.86 0.00 3.35 3.35 109.34 TARP TARP 32.61 13.29 13.29 0.00 6 0 0 Yes
6 MEETINGROOMFLR1 0.0 0.00 0.00 0.00 4.16 -31.75 1.68 1 1 1 4.88E-002 8.28 -36.62 -26.87 0.00 3.35 3.35 269.14 TARP TARP 80.27 32.70 27.77 4.93 7 3 0 Yes
7 MECHANICALROOMFLR1 0.0 0.00 0.00 0.00 4.16 -38.61 1.68 1 1 1 4.88E-002 8.28 -40.59 -36.62 0.00 3.35 3.35 109.34 TARP TARP 32.61 13.29 13.29 0.00 6 0 0 Yes
8 GUESTROOM101 0.0 0.00 0.00 0.00 4.16 -42.57 1.68 1 1 1 4.88E-002 8.28 -44.55 -40.59 0.00 3.35 3.35 109.34 TARP TARP 32.61 13.29 11.64 1.64 6 1 0 Yes
9 GUESTROOM102 0.0 0.00 0.00 0.00 4.16 -46.53 1.68 1 1 1 4.88E-002 8.28 -48.51 -44.55 0.00 3.35 3.35 109.34 TARP TARP 32.61 13.29 11.64 1.64 6 1 0 Yes
10 GUESTROOM103 0.0 0.00 0.00 0.00 4.16 -50.49 1.68 1 1 1 4.88E-002 8.28 -52.47 -48.51 0.00 3.35 3.35 109.34 TARP TARP 32.61 13.29 11.64 1.64 6 1 0 Yes
11 GUESTROOM104 0.0 0.00 0.00 0.00 14.22 -50.49 1.68 1 1 1 10.11 18.34 -52.47 -48.51 0.00 3.35 3.35 109.33 TARP TARP 32.61 13.29 11.64 1.64 6 1 0 Yes
12 GUESTROOM105 0.0 0.00 0.00 0.00 14.22 -46.53 1.68 1 1 1 10.11 18.34 -48.51 -44.55 0.00 3.35 3.35 109.33 TARP TARP 32.61 13.29 11.64 1.64 6 1 0 Yes
13 EMPLOYEELOUNGEFLR1 0.0 0.00 0.00 0.00 14.22 -42.57 1.68 1 1 1 10.11 18.34 -44.55 -40.59 0.00 3.35 3.35 109.33 TARP TARP 32.61 13.29 11.64 1.64 6 1 0 Yes
14 LAUNDRYROOMFLR1 0.0 0.00 0.00 0.00 14.22 -34.64 1.68 1 1 1 10.11 18.34 -40.59 -28.70 0.00 3.35 3.35 327.99 TARP TARP 97.83 39.86 34.93 4.93 7 3 0 Yes
15 ELEVATORCOREFLR1 0.0 0.00 0.00 0.00 14.22 -27.79 1.68 1 1 1 10.11 18.34 -28.70 -26.87 0.00 3.35 3.35 50.46 TARP TARP 15.05 6.13 6.13 0.00 6 0 0 Yes
16 EXERCISECENTERFLR1 0.0 0.00 0.00 0.00 14.22 -21.84 1.68 1 1 1 10.11 18.34 -23.82 -19.86 0.00 3.35 3.35 109.33 TARP TARP 32.61 13.29 11.64 1.64 6 1 0 Yes
17 FRONTOFFICEFLR1 0.0 0.00 0.00 0.00 14.22 -11.94 1.68 1 1 1 10.11 18.34 -19.86 -4.01 0.00 3.35 3.35 437.33 TARP TARP 130.44 53.14 46.57 6.57 7 4 0 Yes
18 FRONTSTAIRSFLR1 0.0 0.00 0.00 0.00 14.22 -1.27 1.68 1 1 1 10.11 18.34 -2.49 -4.87E-002 0.00 3.35 3.35 67.28 TARP TARP 20.07 35.77 33.82 0.00 6 1 0 Yes
19 FRONTSTORAGEFLR1 0.0 0.00 0.00 0.00 14.22 -3.25 1.68 1 1 1 10.11 18.34 -4.01 -2.49 0.00 3.35 3.35 42.05 TARP TARP 12.54 5.11 5.11 0.00 6 0 0 Yes
20 REARSTAIRSFLR2 0.0 0.00 0.00 0.00 14.22 -53.69 4.72 1 1 1 10.11 18.34 -54.91 -52.47 3.35 6.10 2.74 55.06 TARP TARP 20.07 29.27 29.27 0.00 6 0 0 Yes
21 CORRIDORFLR2 0.0 0.00 0.00 0.00 10.72 -26.88 4.72 1 1 1 8.28 18.34 -54.91 -4.87E-002 3.35 6.10 2.74 344.05 TARP TARP 125.42 18.39 15.77 2.62 22 2 0 Yes
22 REARSTORAGEFLR2 0.0 0.00 0.00 0.00 4.16 -53.69 4.72 1 1 1 4.88E-002 8.28 -54.91 -52.47 3.35 6.10 2.74 55.07 TARP TARP 20.07 29.27 29.27 0.00 6 0 0 Yes
23 GUESTROOM201 0.0 0.00 0.00 0.00 4.16 -2.03 4.72 1 1 1 4.88E-002 8.28 -4.01 -4.87E-002 3.35 6.10 2.74 89.46 TARP TARP 32.61 33.45 31.80 1.65 6 1 0 Yes
24 GUESTROOM202_205 0.0 0.00 0.00 0.00 4.16 -11.94 4.72 1 1 1 4.88E-002 8.28 -19.86 -4.01 3.35 6.10 2.74 357.84 TARP TARP 130.45 43.48 36.88 6.60 6 4 0 Yes
25 GUESTROOM206_208 0.0 0.00 0.00 0.00 4.16 -26.26 4.72 1 1 1 4.88E-002 8.28 -32.66 -19.86 3.35 6.10 2.74 289.02 TARP TARP 105.36 35.12 28.41 6.71 8 3 0 Yes
26 GUESTROOM209_212 0.0 0.00 0.00 0.00 4.16 -40.59 4.72 1 1 1 4.88E-002 8.28 -48.51 -32.66 3.35 6.10 2.74 357.84 TARP TARP 130.45 43.48 36.88 6.60 9 4 0 Yes
27 GUESTROOM213 0.0 0.00 0.00 0.00 4.16 -50.49 4.72 1 1 1 4.88E-002 8.28 -52.47 -48.51 3.35 6.10 2.74 89.46 TARP TARP 32.61 10.87 9.22 1.65 6 1 0 Yes
28 GUESTROOM214 0.0 0.00 0.00 0.00 14.22 -50.49 4.72 1 1 1 10.11 18.34 -52.47 -48.51 3.35 6.10 2.74 89.45 TARP TARP 32.61 10.87 9.22 1.65 6 1 0 Yes
29 GUESTROOM215_218 0.0 0.00 0.00 0.00 14.22 -40.59 4.72 1 1 1 10.11 18.34 -48.51 -32.66 3.35 6.10 2.74 357.81 TARP TARP 130.44 43.48 36.88 6.60 8 4 0 Yes
30 ELEVATORCOREFLR2 0.0 0.00 0.00 0.00 14.22 -27.79 4.72 1 1 1 10.11 18.34 -28.70 -26.87 3.35 6.10 2.74 41.29 TARP TARP 15.05 5.02 5.02 0.00 6 0 0 Yes
31 GUESTROOM219 0.0 0.00 0.00 0.00 14.22 -30.68 4.72 1 1 1 10.11 18.34 -32.66 -28.70 3.35 6.10 2.74 89.45 TARP TARP 32.61 10.87 9.22 1.65 6 1 0 Yes
32 GUESTROOM220_223 0.0 0.00 0.00 0.00 14.22 -15.90 4.72 1 1 1 10.11 18.34 -23.82 -7.97 3.35 6.10 2.74 357.81 TARP TARP 130.44 43.48 36.88 6.60 7 4 0 Yes
33 GUESTROOM224 0.0 0.00 0.00 0.00 14.22 -5.99 4.72 1 1 1 10.11 18.34 -7.97 -4.01 3.35 6.10 2.74 89.45 TARP TARP 32.61 10.87 9.22 1.65 6 1 0 Yes
34 FRONTSTORAGEFLR2 0.0 0.00 0.00 0.00 14.22 -3.25 4.72 1 1 1 10.11 18.34 -4.01 -2.49 3.35 6.10 2.74 34.40 TARP TARP 12.54 4.18 4.18 0.00 6 0 0 Yes
35 FRONTSTAIRSFLR2 0.0 0.00 0.00 0.00 14.22 -1.27 4.72 1 1 1 10.11 18.34 -2.49 -4.87E-002 3.35 6.10 2.74 55.05 TARP TARP 20.07 29.26 29.26 0.00 6 0 0 Yes
36 REARSTAIRSFLR3 0.0 0.00 0.00 0.00 14.22 -53.69 7.47 1 1 1 10.11 18.34 -54.91 -52.47 6.10 8.84 2.74 55.06 TARP TARP 20.07 29.27 29.27 0.00 6 0 0 Yes
37 CORRIDORFLR3 0.0 0.00 0.00 0.00 10.72 -26.88 7.47 1 1 1 8.28 18.34 -54.91 -4.87E-002 6.10 8.84 2.74 344.05 TARP TARP 125.42 18.39 15.77 2.62 22 2 0 Yes
38 REARSTORAGEFLR3 0.0 0.00 0.00 0.00 4.16 -53.69 7.47 1 1 1 4.88E-002 8.28 -54.91 -52.47 6.10 8.84 2.74 55.07 TARP TARP 20.07 29.27 29.27 0.00 6 0 0 Yes
39 GUESTROOM301 0.0 0.00 0.00 0.00 4.16 -2.03 7.47 1 1 1 4.88E-002 8.28 -4.01 -4.87E-002 6.10 8.84 2.74 89.46 TARP TARP 32.61 33.45 31.80 1.65 6 1 0 Yes
40 GUESTROOM302_305 0.0 0.00 0.00 0.00 4.16 -11.94 7.47 1 1 1 4.88E-002 8.28 -19.86 -4.01 6.10 8.84 2.74 357.84 TARP TARP 130.45 43.48 36.90 6.58 6 4 0 Yes
41 GUESTROOM306_308 0.0 0.00 0.00 0.00 4.16 -26.26 7.47 1 1 1 4.88E-002 8.28 -32.66 -19.86 6.10 8.84 2.74 289.02 TARP TARP 105.36 35.12 28.42 6.70 6 3 0 Yes
42 GUESTROOM309_312 0.0 0.00 0.00 0.00 4.16 -40.59 7.47 1 1 1 4.88E-002 8.28 -48.51 -32.66 6.10 8.84 2.74 357.84 TARP TARP 130.45 43.48 36.90 6.58 6 4 0 Yes
43 GUESTROOM313 0.0 0.00 0.00 0.00 4.16 -50.49 7.47 1 1 1 4.88E-002 8.28 -52.47 -48.51 6.10 8.84 2.74 89.46 TARP TARP 32.61 10.87 9.22 1.65 6 1 0 Yes
44 GUESTROOM314 0.0 0.00 0.00 0.00 14.22 -50.49 7.47 1 1 1 10.11 18.34 -52.47 -48.51 6.10 8.84 2.74 89.45 TARP TARP 32.61 10.87 9.22 1.65 6 1 0 Yes
45 GUESTROOM315_318 0.0 0.00 0.00 0.00 14.22 -40.59 7.47 1 1 1 10.11 18.34 -48.51 -32.66 6.10 8.84 2.74 357.81 TARP TARP 130.44 43.48 36.90 6.58 6 4 0 Yes
46 ELEVATORCOREFLR3 0.0 0.00 0.00 0.00 14.22 -27.79 7.47 1 1 1 10.11 18.34 -28.70 -26.87 6.10 8.84 2.74 41.29 TARP TARP 15.05 5.02 5.02 0.00 6 0 0 Yes
47 GUESTROOM319 0.0 0.00 0.00 0.00 14.22 -30.68 7.47 1 1 1 10.11 18.34 -32.66 -28.70 6.10 8.84 2.74 89.45 TARP TARP 32.61 10.87 9.22 1.65 6 1 0 Yes
48 GUESTROOM320_323 0.0 0.00 0.00 0.00 14.22 -15.90 7.47 1 1 1 10.11 18.34 -23.82 -7.97 6.10 8.84 2.74 357.81 TARP TARP 130.44 43.48 36.90 6.58 6 4 0 Yes
49 GUESTROOM324 0.0 0.00 0.00 0.00 14.22 -5.99 7.47 1 1 1 10.11 18.34 -7.97 -4.01 6.10 8.84 2.74 89.45 TARP TARP 32.61 10.87 9.22 1.65 6 1 0 Yes
50 FRONTSTORAGEFLR3 0.0 0.00 0.00 0.00 14.22 -3.25 7.47 1 1 1 10.11 18.34 -4.01 -2.49 6.10 8.84 2.74 34.40 TARP TARP 12.54 4.18 4.18 0.00 6 0 0 Yes
51 FRONTSTAIRSFLR3 0.0 0.00 0.00 0.00 14.22 -1.27 7.47 1 1 1 10.11 18.34 -2.49 -4.87E-002 6.10 8.84 2.74 55.05 TARP TARP 20.07 29.26 29.26 0.00 6 0 0 Yes
52 REARSTAIRSFLR4 0.0 0.00 0.00 0.00 14.22 -53.69 10.21 1 1 1 10.11 18.34 -54.91 -52.47 8.84 11.58 2.74 55.06 TARP TARP 20.07 29.27 29.27 0.00 6 0 0 Yes
53 CORRIDORFLR4 0.0 0.00 0.00 0.00 10.72 -26.88 10.21 1 1 1 8.28 18.34 -54.91 -4.87E-002 8.84 11.58 2.74 344.05 TARP TARP 125.42 18.39 15.77 2.62 22 2 0 Yes
54 REARSTORAGEFLR4 0.0 0.00 0.00 0.00 4.16 -53.69 10.21 1 1 1 4.88E-002 8.28 -54.91 -52.47 8.84 11.58 2.74 55.07 TARP TARP 20.07 29.27 29.27 0.00 6 0 0 Yes
55 GUESTROOM401 0.0 0.00 0.00 0.00 4.16 -2.03 10.21 1 1 1 4.88E-002 8.28 -4.01 -4.87E-002 8.84 11.58 2.74 89.46 TARP TARP 32.61 33.45 31.80 1.65 6 1 0 Yes
56 GUESTROOM402_405 0.0 0.00 0.00 0.00 4.16 -11.94 10.21 1 1 1 4.88E-002 8.28 -19.86 -4.01 8.84 11.58 2.74 357.84 TARP TARP 130.45 43.48 36.90 6.58 6 4 0 Yes
57 GUESTROOM406_408 0.0 0.00 0.00 0.00 4.16 -26.26 10.21 1 1 1 4.88E-002 8.28 -32.66 -19.86 8.84 11.58 2.74 289.02 TARP TARP 105.36 35.12 28.42 6.70 6 3 0 Yes
58 GUESTROOM409_412 0.0 0.00 0.00 0.00 4.16 -40.59 10.21 1 1 1 4.88E-002 8.28 -48.51 -32.66 8.84 11.58 2.74 357.84 TARP TARP 130.45 43.48 36.90 6.58 6 4 0 Yes
59 GUESTROOM413 0.0 0.00 0.00 0.00 4.16 -50.49 10.21 1 1 1 4.88E-002 8.28 -52.47 -48.51 8.84 11.58 2.74 89.46 TARP TARP 32.61 10.87 9.22 1.65 6 1 0 Yes
60 GUESTROOM414 0.0 0.00 0.00 0.00 14.22 -50.49 10.21 1 1 1 10.11 18.34 -52.47 -48.51 8.84 11.58 2.74 89.45 TARP TARP 32.61 10.87 9.22 1.65 6 1 0 Yes
61 GUESTROOM415_418 0.0 0.00 0.00 0.00 14.22 -40.59 10.21 1 1 1 10.11 18.34 -48.51 -32.66 8.84 11.58 2.74 357.81 TARP TARP 130.44 43.48 36.90 6.58 6 4 0 Yes
62 ELEVATORCOREFLR4 0.0 0.00 0.00 0.00 14.22 -27.79 10.21 1 1 1 10.11 18.34 -28.70 -26.87 8.84 11.58 2.74 41.29 TARP TARP 15.05 5.02 5.02 0.00 6 0 0 Yes
63 GUESTROOM419 0.0 0.00 0.00 0.00 14.22 -30.68 10.21 1 1 1 10.11 18.34 -32.66 -28.70 8.84 11.58 2.74 89.45 TARP TARP 32.61 10.87 9.22 1.65 6 1 0 Yes
64 GUESTROOM420_423 0.0 0.00 0.00 0.00 14.22 -15.90 10.21 1 1 1 10.11 18.34 -23.82 -7.97 8.84 11.58 2.74 357.81 TARP TARP 130.44 43.48 36.90 6.58 6 4 0 Yes
65 GUESTROOM424 0.0 0.00 0.00 0.00 14.22 -5.99 10.21 1 1 1 10.11 18.34 -7.97 -4.01 8.84 11.58 2.74 89.45 TARP TARP 32.61 10.87 9.22 1.65 6 1 0 Yes
66 FRONTSTORAGEFLR4 0.0 0.00 0.00 0.00 14.22 -3.25 10.21 1 1 1 10.11 18.34 -4.01 -2.49 8.84 11.58 2.74 34.40 TARP TARP 12.54 4.18 4.18 0.00 6 0 0 Yes
67 FRONTSTAIRSFLR4 0.0 0.00 0.00 0.00 14.22 -1.27 10.21 1 1 1 10.11 18.34 -2.49 -4.87E-002 8.84 11.58 2.74 55.05 TARP TARP 20.07 29.26 29.26 0.00 6 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 REARSTAIRSFLR1 20.07 1.1 18.585 5.381E-002 5.274 0.000 0.000 0.000 0.000 0.000 5.274 No
2 CORRIDORFLR1 150.51 8.1 18.581 5.382E-002 4.413 0.000 0.000 0.000 0.000 0.000 4.413 No
3 REARSTORAGEFLR1 20.07 0.4 46.466 2.152E-002 4.090 0.000 0.000 0.000 0.000 0.000 4.090 No
4 FRONTLOUNGEFLR1 163.06 53.0 3.077 0.325 9.042 26.060 0.000 0.000 0.000 0.000 35.102 No
5 RESTROOMFLR1 32.61 1.8 18.582 5.382E-002 6.781 0.000 0.000 0.000 0.000 0.000 6.781 No
6 MEETINGROOMFLR1 80.27 43.0 1.867 0.536 10.441 6.180 0.000 0.000 0.000 0.000 16.621 No
7 MECHANICALROOMFLR1 32.61 0.5 61.881 1.616E-002 4.628 0.000 0.000 0.000 0.000 0.000 4.628 No
8 GUESTROOM101 32.61 1.5 21.741 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
9 GUESTROOM102 32.61 1.5 21.741 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
10 GUESTROOM103 32.61 1.5 21.741 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
11 GUESTROOM104 32.61 1.5 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
12 GUESTROOM105 32.61 1.5 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
13 EMPLOYEELOUNGEFLR1 32.61 18.0 1.812 0.552 6.351 21.510 0.000 0.000 0.000 0.000 27.861 No
14 LAUNDRYROOMFLR1 97.83 10.5 9.290 0.108 5.705 27.693 409.867 0.000 0.000 0.000 443.265 No
15 ELEVATORCOREFLR1 15.05 0.2 61.935 1.615E-002 0.000 1073.022 0.000 0.000 0.000 0.000 1073.022 No
16 EXERCISECENTERFLR1 32.61 7.0 4.658 0.215 9.688 18.590 0.000 0.000 0.000 0.000 28.278 No
17 FRONTOFFICEFLR1 130.44 10.0 13.044 7.667E-002 7.615 13.780 0.000 0.000 0.000 0.000 21.395 No
18 FRONTSTAIRSFLR1 20.07 1.1 18.581 5.382E-002 5.274 0.000 0.000 0.000 0.000 0.000 5.274 No
19 FRONTSTORAGEFLR1 12.54 0.3 46.452 2.153E-002 4.090 0.000 0.000 0.000 0.000 0.000 4.090 No
20 REARSTAIRSFLR2 20.07 1.1 18.585 5.381E-002 5.274 0.000 0.000 0.000 0.000 0.000 5.274 No
21 CORRIDORFLR2 125.42 6.8 18.581 5.382E-002 4.413 0.000 0.000 0.000 0.000 0.000 4.413 No
22 REARSTORAGEFLR2 20.07 0.4 46.466 2.152E-002 4.090 0.000 0.000 0.000 0.000 0.000 4.090 No
23 GUESTROOM201 32.61 1.5 21.741 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
24 GUESTROOM202_205 130.45 6.0 21.741 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
25 GUESTROOM206_208 105.36 4.5 23.413 4.271E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
26 GUESTROOM209_212 130.45 6.0 21.741 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
27 GUESTROOM213 32.61 1.5 21.741 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
28 GUESTROOM214 32.61 1.5 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
29 GUESTROOM215_218 130.44 6.0 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
30 ELEVATORCOREFLR2 15.05 0.2 61.935 1.615E-002 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
31 GUESTROOM219 32.61 1.5 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
32 GUESTROOM220_223 130.44 6.0 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
33 GUESTROOM224 32.61 1.5 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
34 FRONTSTORAGEFLR2 12.54 0.3 46.452 2.153E-002 4.090 0.000 0.000 0.000 0.000 0.000 4.090 No
35 FRONTSTAIRSFLR2 20.07 1.1 18.581 5.382E-002 5.274 0.000 0.000 0.000 0.000 0.000 5.274 No
36 REARSTAIRSFLR3 20.07 1.1 18.585 5.381E-002 5.274 0.000 0.000 0.000 0.000 0.000 5.274 No
37 CORRIDORFLR3 125.42 6.8 18.581 5.382E-002 4.413 0.000 0.000 0.000 0.000 0.000 4.413 No
38 REARSTORAGEFLR3 20.07 0.4 46.466 2.152E-002 4.090 0.000 0.000 0.000 0.000 0.000 4.090 No
39 GUESTROOM301 32.61 1.5 21.741 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
40 GUESTROOM302_305 130.45 6.0 21.741 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
41 GUESTROOM306_308 105.36 4.5 23.413 4.271E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
42 GUESTROOM309_312 130.45 6.0 21.741 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
43 GUESTROOM313 32.61 1.5 21.741 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
44 GUESTROOM314 32.61 1.5 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
45 GUESTROOM315_318 130.44 6.0 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
46 ELEVATORCOREFLR3 15.05 0.2 61.935 1.615E-002 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
47 GUESTROOM319 32.61 1.5 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
48 GUESTROOM320_323 130.44 6.0 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
49 GUESTROOM324 32.61 1.5 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
50 FRONTSTORAGEFLR3 12.54 0.3 46.452 2.153E-002 4.090 0.000 0.000 0.000 0.000 0.000 4.090 No
51 FRONTSTAIRSFLR3 20.07 1.1 18.581 5.382E-002 5.274 0.000 0.000 0.000 0.000 0.000 5.274 No
52 REARSTAIRSFLR4 20.07 1.1 18.585 5.381E-002 5.274 0.000 0.000 0.000 0.000 0.000 5.274 No
53 CORRIDORFLR4 125.42 6.8 18.581 5.382E-002 4.413 0.000 0.000 0.000 0.000 0.000 4.413 No
54 REARSTORAGEFLR4 20.07 0.4 46.466 2.152E-002 4.090 0.000 0.000 0.000 0.000 0.000 4.090 No
55 GUESTROOM401 32.61 1.5 21.741 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
56 GUESTROOM402_405 130.45 6.0 21.741 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
57 GUESTROOM406_408 105.36 4.5 23.413 4.271E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
58 GUESTROOM409_412 130.45 6.0 21.741 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
59 GUESTROOM413 32.61 1.5 21.741 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
60 GUESTROOM414 32.61 1.5 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
61 GUESTROOM415_418 130.44 6.0 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
62 ELEVATORCOREFLR4 15.05 0.2 61.935 1.615E-002 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
63 GUESTROOM419 32.61 1.5 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
64 GUESTROOM420_423 130.44 6.0 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
65 GUESTROOM424 32.61 1.5 21.739 4.600E-002 4.413 11.893 0.000 0.000 0.000 0.000 16.307 No
66 FRONTSTORAGEFLR4 12.54 0.3 46.452 2.153E-002 4.090 0.000 0.000 0.000 0.000 0.000 4.090 No
67 FRONTSTAIRSFLR4 20.07 1.1 18.581 5.382E-002 5.274 0.000 0.000 0.000 0.000 0.000 5.274 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORRIDORFLR1_PEOPLE ALWAYSOFF CORRIDORFLR1 150.51 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
2 CORRIDORFLR2_PEOPLE ALWAYSOFF CORRIDORFLR2 125.42 6.8 6.8 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
3 CORRIDORFLR3_PEOPLE ALWAYSOFF CORRIDORFLR3 125.42 6.8 6.8 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
4 CORRIDORFLR4_PEOPLE ALWAYSOFF CORRIDORFLR4 125.42 6.8 6.8 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
5 ELEVATORCOREFLR1_PEOPLE ALWAYSOFF ELEVATORCOREFLR1 15.05 0.2 0.2 1.615E-002 61.935 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
6 ELEVATORCOREFLR2_PEOPLE ALWAYSOFF ELEVATORCOREFLR2 15.05 0.2 0.2 1.615E-002 61.935 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
7 ELEVATORCOREFLR3_PEOPLE ALWAYSOFF ELEVATORCOREFLR3 15.05 0.2 0.2 1.615E-002 61.935 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
8 ELEVATORCOREFLR4_PEOPLE ALWAYSOFF ELEVATORCOREFLR4 15.05 0.2 0.2 1.615E-002 61.935 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
9 EMPLOYEELOUNGEFLR1_PEOPLE EMPLOYEELOUNGE_OCC_SCH EMPLOYEELOUNGEFLR1 32.61 18.0 18.0 0.552 1.812 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 18
10 EXERCISECENTERFLR1_PEOPLE EXERCISECENTER_OCC_SCH EXERCISECENTERFLR1 32.61 7.0 7.0 0.215 4.658 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7
11 FRONTLOUNGEFLR1_PEOPLE LOBBY_OCC_SCH FRONTLOUNGEFLR1 163.06 53.0 53.0 0.325 3.077 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53
12 FRONTOFFICEFLR1_PEOPLE OFFICE_OCC_W_SB_SCH FRONTOFFICEFLR1 130.44 10.0 10.0 7.667E-002 13.044 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 10
13 FRONTSTAIRSFLR1_PEOPLE ALWAYSOFF FRONTSTAIRSFLR1 20.07 1.1 1.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
14 FRONTSTAIRSFLR2_PEOPLE ALWAYSOFF FRONTSTAIRSFLR2 20.07 1.1 1.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
15 FRONTSTAIRSFLR3_PEOPLE ALWAYSOFF FRONTSTAIRSFLR3 20.07 1.1 1.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
16 FRONTSTAIRSFLR4_PEOPLE ALWAYSOFF FRONTSTAIRSFLR4 20.07 1.1 1.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
17 FRONTSTORAGEFLR1_PEOPLE ALWAYSOFF FRONTSTORAGEFLR1 12.54 0.3 0.3 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
18 FRONTSTORAGEFLR2_PEOPLE ALWAYSOFF FRONTSTORAGEFLR2 12.54 0.3 0.3 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
19 FRONTSTORAGEFLR3_PEOPLE ALWAYSOFF FRONTSTORAGEFLR3 12.54 0.3 0.3 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
20 FRONTSTORAGEFLR4_PEOPLE ALWAYSOFF FRONTSTORAGEFLR4 12.54 0.3 0.3 2.153E-002 46.452 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
21 GUESTROOM101_PEOPLE ALWAYSOFF GUESTROOM101 32.61 1.5 1.5 4.600E-002 21.741 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
22 GUESTROOM102_PEOPLE ALWAYSOFF GUESTROOM102 32.61 1.5 1.5 4.600E-002 21.741 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
23 GUESTROOM103_PEOPLE GUESTROOM_OCC_SCH GUESTROOM103 32.61 1.5 1.5 4.600E-002 21.741 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
24 GUESTROOM104_PEOPLE GUESTROOM_OCC_SCH GUESTROOM104 32.61 1.5 1.5 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
25 GUESTROOM105_PEOPLE GUESTROOM_OCC_SCH GUESTROOM105 32.61 1.5 1.5 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
26 GUESTROOM201_PEOPLE ALWAYSOFF GUESTROOM201 32.61 1.5 1.5 4.600E-002 21.741 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
27 GUESTROOM202_205_PEOPLE GUESTROOM_OCC_SCH GUESTROOM202_205 130.45 6.0 6.0 4.600E-002 21.741 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
28 GUESTROOM206_208_PEOPLE GUESTROOM_OCC_SCH GUESTROOM206_208 105.36 4.5 4.5 4.271E-002 23.413 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 5
29 GUESTROOM209_212_PEOPLE GUESTROOM_OCC_SCH GUESTROOM209_212 130.45 6.0 6.0 4.600E-002 21.741 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
30 GUESTROOM213_PEOPLE GUESTROOM_OCC_SCH GUESTROOM213 32.61 1.5 1.5 4.600E-002 21.741 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
31 GUESTROOM214_PEOPLE GUESTROOM_OCC_SCH GUESTROOM214 32.61 1.5 1.5 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
32 GUESTROOM215_218_PEOPLE ALWAYSOFF GUESTROOM215_218 130.44 6.0 6.0 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
33 GUESTROOM219_PEOPLE GUESTROOM_OCC_SCH GUESTROOM219 32.61 1.5 1.5 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
34 GUESTROOM220_223_PEOPLE GUESTROOM_OCC_SCH GUESTROOM220_223 130.44 6.0 6.0 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
35 GUESTROOM224_PEOPLE GUESTROOM_OCC_SCH GUESTROOM224 32.61 1.5 1.5 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
36 GUESTROOM301_PEOPLE ALWAYSOFF GUESTROOM301 32.61 1.5 1.5 4.600E-002 21.741 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
37 GUESTROOM302_305_PEOPLE ALWAYSOFF GUESTROOM302_305 130.45 6.0 6.0 4.600E-002 21.741 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
38 GUESTROOM306_308_PEOPLE ALWAYSOFF GUESTROOM306_308 105.36 4.5 4.5 4.271E-002 23.413 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
39 GUESTROOM309_312_PEOPLE GUESTROOM_OCC_SCH GUESTROOM309_312 130.45 6.0 6.0 4.600E-002 21.741 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
40 GUESTROOM313_PEOPLE ALWAYSOFF GUESTROOM313 32.61 1.5 1.5 4.600E-002 21.741 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
41 GUESTROOM314_PEOPLE GUESTROOM_OCC_SCH GUESTROOM314 32.61 1.5 1.5 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
42 GUESTROOM315_318_PEOPLE GUESTROOM_OCC_SCH GUESTROOM315_318 130.44 6.0 6.0 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
43 GUESTROOM319_PEOPLE ALWAYSOFF GUESTROOM319 32.61 1.5 1.5 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
44 GUESTROOM320_323_PEOPLE GUESTROOM_OCC_SCH GUESTROOM320_323 130.44 6.0 6.0 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
45 GUESTROOM324_PEOPLE ALWAYSOFF GUESTROOM324 32.61 1.5 1.5 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
46 GUESTROOM401_PEOPLE GUESTROOM_OCC_SCH GUESTROOM401 32.61 1.5 1.5 4.600E-002 21.741 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
47 GUESTROOM402_405_PEOPLE ALWAYSOFF GUESTROOM402_405 130.45 6.0 6.0 4.600E-002 21.741 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
48 GUESTROOM406_408_PEOPLE ALWAYSOFF GUESTROOM406_408 105.36 4.5 4.5 4.271E-002 23.413 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
49 GUESTROOM409_412_PEOPLE GUESTROOM_OCC_SCH GUESTROOM409_412 130.45 6.0 6.0 4.600E-002 21.741 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
50 GUESTROOM413_PEOPLE ALWAYSOFF GUESTROOM413 32.61 1.5 1.5 4.600E-002 21.741 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
51 GUESTROOM414_PEOPLE ALWAYSOFF GUESTROOM414 32.61 1.5 1.5 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
52 GUESTROOM415_418_PEOPLE GUESTROOM_OCC_SCH GUESTROOM415_418 130.44 6.0 6.0 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
53 GUESTROOM419_PEOPLE GUESTROOM_OCC_SCH GUESTROOM419 32.61 1.5 1.5 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
54 GUESTROOM420_423_PEOPLE GUESTROOM_OCC_SCH GUESTROOM420_423 130.44 6.0 6.0 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
55 GUESTROOM424_PEOPLE GUESTROOM_OCC_SCH GUESTROOM424 32.61 1.5 1.5 4.600E-002 21.739 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
56 LAUNDRYROOMFLR1_PEOPLE LAUNDRYROOM_OCC_SCH LAUNDRYROOMFLR1 97.83 10.5 10.5 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11
57 MECHANICALROOMFLR1_PEOPLE ALWAYSOFF MECHANICALROOMFLR1 32.61 0.5 0.5 1.616E-002 61.881 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
58 MEETINGROOMFLR1_PEOPLE MEETINGROOM_OCC_W_SB_SCH MEETINGROOMFLR1 80.27 43.0 43.0 0.536 1.867 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 43
59 REARSTAIRSFLR1_PEOPLE ALWAYSOFF REARSTAIRSFLR1 20.07 1.1 1.1 5.381E-002 18.585 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
60 REARSTAIRSFLR2_PEOPLE ALWAYSOFF REARSTAIRSFLR2 20.07 1.1 1.1 5.381E-002 18.585 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
61 REARSTAIRSFLR3_PEOPLE ALWAYSOFF REARSTAIRSFLR3 20.07 1.1 1.1 5.381E-002 18.585 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
62 REARSTAIRSFLR4_PEOPLE ALWAYSOFF REARSTAIRSFLR4 20.07 1.1 1.1 5.381E-002 18.585 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
63 REARSTORAGEFLR1_PEOPLE ALWAYSOFF REARSTORAGEFLR1 20.07 0.4 0.4 2.152E-002 46.466 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
64 REARSTORAGEFLR2_PEOPLE ALWAYSOFF REARSTORAGEFLR2 20.07 0.4 0.4 2.152E-002 46.466 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
65 REARSTORAGEFLR3_PEOPLE ALWAYSOFF REARSTORAGEFLR3 20.07 0.4 0.4 2.152E-002 46.466 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
66 REARSTORAGEFLR4_PEOPLE ALWAYSOFF REARSTORAGEFLR4 20.07 0.4 0.4 2.152E-002 46.466 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0
67 RESTROOMFLR1_PEOPLE LOBBY_OCC_SCH RESTROOMFLR1 32.61 1.8 1.8 5.382E-002 18.582 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORRIDORFLR1_LIGHTS LTG_SCH_CORRIDOR CORRIDORFLR1 150.51 8.1 664.212 4.413 82.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 664.212
2 CORRIDORFLR2_LIGHTS LTG_SCH_CORRIDOR CORRIDORFLR2 125.42 6.8 553.504 4.413 82.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 553.504
3 CORRIDORFLR3_LIGHTS LTG_SCH_CORRIDOR CORRIDORFLR3 125.42 6.8 553.504 4.413 82.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 553.504
4 CORRIDORFLR4_LIGHTS LTG_SCH_CORRIDOR CORRIDORFLR4 125.42 6.8 553.504 4.413 82.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 553.504
5 ELEVATORCOREFLR1_LIGHTS LTG_SCH_ELEVATOR ELEVATORCOREFLR1 15.05 0.2 0.000 0.000 0.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
6 ELEVATORCOREFLR2_LIGHTS LTG_SCH_ELEVATOR ELEVATORCOREFLR2 15.05 0.2 0.000 0.000 0.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
7 ELEVATORCOREFLR3_LIGHTS LTG_SCH_ELEVATOR ELEVATORCOREFLR3 15.05 0.2 0.000 0.000 0.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
8 ELEVATORCOREFLR4_LIGHTS LTG_SCH_ELEVATOR ELEVATORCOREFLR4 15.05 0.2 0.000 0.000 0.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
9 EMPLOYEELOUNGEFLR1_LIGHTS LTG_SCH_LOUNGE EMPLOYEELOUNGEFLR1 32.61 18.0 207.090 6.351 11.505 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 207.090
10 EXERCISECENTERFLR1_LIGHTS LTG_SCH_EXERCISE EXERCISECENTERFLR1 32.61 7.0 315.900 9.688 45.129 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 315.900
11 FRONTLOUNGEFLR1_LIGHTS LTG_SCH_LOBBY FRONTLOUNGEFLR1 163.06 53.0 1474.304 9.042 27.817 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1474.304
12 FRONTOFFICEFLR1_LIGHTS LTG_SCH_OFFICE FRONTOFFICEFLR1 130.44 10.0 993.329 7.615 99.333 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 993.329
13 FRONTSTAIRSFLR1_LIGHTS LTG_SCH_STAIR FRONTSTAIRSFLR1 20.07 1.1 105.840 5.274 98.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 105.840
14 FRONTSTAIRSFLR2_LIGHTS LTG_SCH_STAIR FRONTSTAIRSFLR2 20.07 1.1 105.840 5.274 98.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 105.840
15 FRONTSTAIRSFLR3_LIGHTS LTG_SCH_STAIR FRONTSTAIRSFLR3 20.07 1.1 105.840 5.274 98.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 105.840
16 FRONTSTAIRSFLR4_LIGHTS LTG_SCH_STAIR FRONTSTAIRSFLR4 20.07 1.1 105.840 5.274 98.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 105.840
17 FRONTSTORAGEFLR1_LIGHTS LTG_SCH_STORAGE FRONTSTORAGEFLR1 12.54 0.3 51.300 4.090 190.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 51.300
18 FRONTSTORAGEFLR2_LIGHTS LTG_SCH_STORAGE FRONTSTORAGEFLR2 12.54 0.3 51.300 4.090 190.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 51.300
19 FRONTSTORAGEFLR3_LIGHTS LTG_SCH_STORAGE FRONTSTORAGEFLR3 12.54 0.3 51.300 4.090 190.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 51.300
20 FRONTSTORAGEFLR4_LIGHTS LTG_SCH_STORAGE FRONTSTORAGEFLR4 12.54 0.3 51.300 4.090 190.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 51.300
21 GUESTROOM101_LIGHTS ALWAYSOFF GUESTROOM101 32.61 1.5 143.920 4.413 95.947 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
22 GUESTROOM102_LIGHTS ALWAYSOFF GUESTROOM102 32.61 1.5 143.920 4.413 95.947 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
23 GUESTROOM103_LIGHTS LTG_SCH_GUESTROOM GUESTROOM103 32.61 1.5 143.920 4.413 95.947 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 143.920
24 GUESTROOM104_LIGHTS LTG_SCH_GUESTROOM GUESTROOM104 32.61 1.5 143.910 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 143.910
25 GUESTROOM105_LIGHTS LTG_SCH_GUESTROOM GUESTROOM105 32.61 1.5 143.910 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 143.910
26 GUESTROOM201_LIGHTS ALWAYSOFF GUESTROOM201 32.61 1.5 143.920 4.413 95.947 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
27 GUESTROOM202_205_LIGHTS LTG_SCH_GUESTROOM GUESTROOM202_205 130.45 6.0 575.680 4.413 95.947 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 575.680
28 GUESTROOM206_208_LIGHTS LTG_SCH_GUESTROOM GUESTROOM206_208 105.36 4.5 464.973 4.413 103.327 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 464.973
29 GUESTROOM209_212_LIGHTS LTG_SCH_GUESTROOM GUESTROOM209_212 130.45 6.0 575.680 4.413 95.947 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 575.680
30 GUESTROOM213_LIGHTS LTG_SCH_GUESTROOM GUESTROOM213 32.61 1.5 143.920 4.413 95.947 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 143.920
31 GUESTROOM214_LIGHTS LTG_SCH_GUESTROOM GUESTROOM214 32.61 1.5 143.910 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 143.910
32 GUESTROOM215_218_LIGHTS ALWAYSOFF GUESTROOM215_218 130.44 6.0 575.640 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
33 GUESTROOM219_LIGHTS LTG_SCH_GUESTROOM GUESTROOM219 32.61 1.5 143.910 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 143.910
34 GUESTROOM220_223_LIGHTS LTG_SCH_GUESTROOM GUESTROOM220_223 130.44 6.0 575.640 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 575.640
35 GUESTROOM224_LIGHTS LTG_SCH_GUESTROOM GUESTROOM224 32.61 1.5 143.910 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 143.910
36 GUESTROOM301_LIGHTS ALWAYSOFF GUESTROOM301 32.61 1.5 143.920 4.413 95.947 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
37 GUESTROOM302_305_LIGHTS ALWAYSOFF GUESTROOM302_305 130.45 6.0 575.680 4.413 95.947 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
38 GUESTROOM306_308_LIGHTS ALWAYSOFF GUESTROOM306_308 105.36 4.5 464.973 4.413 103.327 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
39 GUESTROOM309_312_LIGHTS LTG_SCH_GUESTROOM GUESTROOM309_312 130.45 6.0 575.680 4.413 95.947 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 575.680
40 GUESTROOM313_LIGHTS ALWAYSOFF GUESTROOM313 32.61 1.5 143.920 4.413 95.947 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
41 GUESTROOM314_LIGHTS LTG_SCH_GUESTROOM GUESTROOM314 32.61 1.5 143.910 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 143.910
42 GUESTROOM315_318_LIGHTS LTG_SCH_GUESTROOM GUESTROOM315_318 130.44 6.0 575.640 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 575.640
43 GUESTROOM319_LIGHTS ALWAYSOFF GUESTROOM319 32.61 1.5 143.910 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
44 GUESTROOM320_323_LIGHTS LTG_SCH_GUESTROOM GUESTROOM320_323 130.44 6.0 575.640 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 575.640
45 GUESTROOM324_LIGHTS ALWAYSOFF GUESTROOM324 32.61 1.5 143.910 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
46 GUESTROOM401_LIGHTS LTG_SCH_GUESTROOM GUESTROOM401 32.61 1.5 143.920 4.413 95.947 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 143.920
47 GUESTROOM402_405_LIGHTS ALWAYSOFF GUESTROOM402_405 130.45 6.0 575.680 4.413 95.947 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
48 GUESTROOM406_408_LIGHTS ALWAYSOFF GUESTROOM406_408 105.36 4.5 464.973 4.413 103.327 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
49 GUESTROOM409_412_LIGHTS LTG_SCH_GUESTROOM GUESTROOM409_412 130.45 6.0 575.680 4.413 95.947 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 575.680
50 GUESTROOM413_LIGHTS ALWAYSOFF GUESTROOM413 32.61 1.5 143.920 4.413 95.947 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
51 GUESTROOM414_LIGHTS ALWAYSOFF GUESTROOM414 32.61 1.5 143.910 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 0.000
52 GUESTROOM415_418_LIGHTS LTG_SCH_GUESTROOM GUESTROOM415_418 130.44 6.0 575.640 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 575.640
53 GUESTROOM419_LIGHTS LTG_SCH_GUESTROOM GUESTROOM419 32.61 1.5 143.910 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 143.910
54 GUESTROOM420_423_LIGHTS LTG_SCH_GUESTROOM GUESTROOM420_423 130.44 6.0 575.640 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 575.640
55 GUESTROOM424_LIGHTS LTG_SCH_GUESTROOM GUESTROOM424 32.61 1.5 143.910 4.413 95.940 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 143.910
56 LAUNDRYROOMFLR1_LIGHTS LTG_SCH_LAUNDRY LAUNDRYROOMFLR1 97.83 10.5 558.090 5.705 53.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 558.090
57 MECHANICALROOMFLR1_LIGHTS LTG_SCH_MECHANICAL MECHANICALROOMFLR1 32.61 0.5 150.941 4.628 286.415 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 150.941
58 MEETINGROOMFLR1_LIGHTS LTG_SCH_MEETING MEETINGROOMFLR1 80.27 43.0 838.138 10.441 19.492 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 838.138
59 REARSTAIRSFLR1_LIGHTS LTG_SCH_STAIR REARSTAIRSFLR1 20.07 1.1 105.865 5.274 98.023 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 105.865
60 REARSTAIRSFLR2_LIGHTS LTG_SCH_STAIR REARSTAIRSFLR2 20.07 1.1 105.865 5.274 98.023 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 105.865
61 REARSTAIRSFLR3_LIGHTS LTG_SCH_STAIR REARSTAIRSFLR3 20.07 1.1 105.865 5.274 98.023 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 105.865
62 REARSTAIRSFLR4_LIGHTS LTG_SCH_STAIR REARSTAIRSFLR4 20.07 1.1 105.865 5.274 98.023 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 105.865
63 REARSTORAGEFLR1_LIGHTS LTG_SCH_STORAGE REARSTORAGEFLR1 20.07 0.4 82.105 4.090 190.059 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 82.105
64 REARSTORAGEFLR2_LIGHTS LTG_SCH_STORAGE REARSTORAGEFLR2 20.07 0.4 82.105 4.090 190.059 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 82.105
65 REARSTORAGEFLR3_LIGHTS LTG_SCH_STORAGE REARSTORAGEFLR3 20.07 0.4 82.105 4.090 190.059 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 82.105
66 REARSTORAGEFLR4_LIGHTS LTG_SCH_STORAGE REARSTORAGEFLR4 20.07 0.4 82.105 4.090 190.059 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 82.105
67 RESTROOMFLR1_LIGHTS LTG_SCH_RESTROOM RESTROOMFLR1 32.61 1.8 221.146 6.781 126.009 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 221.146


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORRIDORFLR1_PLUGLOAD ALWAYSOFF CORRIDORFLR1 150.51 8.1 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
2 CORRIDORFLR2_PLUGLOAD ALWAYSOFF CORRIDORFLR2 125.42 6.8 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
3 CORRIDORFLR3_PLUGLOAD ALWAYSOFF CORRIDORFLR3 125.42 6.8 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
4 CORRIDORFLR4_PLUGLOAD ALWAYSOFF CORRIDORFLR4 125.42 6.8 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
5 ELEVATORCOREFLR1_ELEVATORS_EQUIP BLDG_ELEVATORS ELEVATORCOREFLR1 15.05 0.2 16024.300 1064.717 65943.621 0.000 0.500 0.000 0.500 ElevatorLift 1922.916 8012.150
6 ELEVATORS_LIGHTS_FAN ELEV_LIGHT_FAN_SCH_ADD_DF ELEVATORCOREFLR1 15.05 0.2 125.000 8.305 514.403 0.000 0.500 0.000 0.500 ElevatorLightsFan 6.250 62.500
7 ELEVATORCOREFLR2_PLUGLOAD ALWAYSOFF ELEVATORCOREFLR2 15.05 0.2 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
8 ELEVATORCOREFLR3_PLUGLOAD ALWAYSOFF ELEVATORCOREFLR3 15.05 0.2 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
9 ELEVATORCOREFLR4_PLUGLOAD ALWAYSOFF ELEVATORCOREFLR4 15.05 0.2 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
10 EMPLOYEELOUNGEFLR1_PLUGLOAD EMPLOYEELOUNGE_EQP_SCH EMPLOYEELOUNGEFLR1 32.61 18.0 701.419 21.510 38.968 0.000 0.500 0.000 0.500 MiscPlug 0.000 701.419
11 EXERCISECENTERFLR1_PLUGLOAD EXERCISECENTER_EQP_SCH EXERCISECENTERFLR1 32.61 7.0 606.201 18.590 86.600 0.000 0.500 0.000 0.500 MiscPlug 0.000 606.201
12 FRONTLOUNGEFLR1_PLUGLOAD LOBBY_EQP_SCH FRONTLOUNGEFLR1 163.06 53.0 4249.250 26.060 80.175 0.000 0.500 0.000 0.500 MiscPlug 0.000 4249.250
13 FRONTOFFICEFLR1_PLUGLOAD OFF_EQUIP_SCH FRONTOFFICEFLR1 130.44 10.0 1797.406 13.780 179.741 0.000 0.500 0.000 0.500 MiscPlug 0.000 1797.406
14 FRONTSTAIRSFLR1_PLUGLOAD ALWAYSOFF FRONTSTAIRSFLR1 20.07 1.1 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
15 FRONTSTAIRSFLR2_PLUGLOAD ALWAYSOFF FRONTSTAIRSFLR2 20.07 1.1 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
16 FRONTSTAIRSFLR3_PLUGLOAD ALWAYSOFF FRONTSTAIRSFLR3 20.07 1.1 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
17 FRONTSTAIRSFLR4_PLUGLOAD ALWAYSOFF FRONTSTAIRSFLR4 20.07 1.1 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
18 FRONTSTORAGEFLR1_PLUGLOAD ALWAYSOFF FRONTSTORAGEFLR1 12.54 0.3 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
19 FRONTSTORAGEFLR2_PLUGLOAD ALWAYSOFF FRONTSTORAGEFLR2 12.54 0.3 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
20 FRONTSTORAGEFLR3_PLUGLOAD ALWAYSOFF FRONTSTORAGEFLR3 12.54 0.3 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
21 FRONTSTORAGEFLR4_PLUGLOAD ALWAYSOFF FRONTSTORAGEFLR4 12.54 0.3 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
22 GUESTROOM101_PLUGLOAD ALWAYSOFF GUESTROOM101 32.61 1.5 387.861 11.893 258.574 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
23 GUESTROOM102_PLUGLOAD ALWAYSOFF GUESTROOM102 32.61 1.5 387.861 11.893 258.574 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
24 GUESTROOM103_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM103 32.61 1.5 387.861 11.893 258.574 0.000 0.500 0.000 0.500 MiscPlug 0.000 387.861
25 GUESTROOM104_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM104 32.61 1.5 387.833 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 387.833
26 GUESTROOM105_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM105 32.61 1.5 387.833 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 387.833
27 GUESTROOM201_PLUGLOAD ALWAYSOFF GUESTROOM201 32.61 1.5 387.861 11.893 258.574 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
28 GUESTROOM202_205_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM202_205 130.45 6.0 1551.444 11.893 258.574 0.000 0.500 0.000 0.500 MiscPlug 0.000 1551.444
29 GUESTROOM206_208_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM206_208 105.36 4.5 1253.089 11.893 278.464 0.000 0.500 0.000 0.500 MiscPlug 0.000 1253.089
30 GUESTROOM209_212_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM209_212 130.45 6.0 1551.444 11.893 258.574 0.000 0.500 0.000 0.500 MiscPlug 0.000 1551.444
31 GUESTROOM213_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM213 32.61 1.5 387.861 11.893 258.574 0.000 0.500 0.000 0.500 MiscPlug 0.000 387.861
32 GUESTROOM214_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM214 32.61 1.5 387.833 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 387.833
33 GUESTROOM215_218_PLUGLOAD ALWAYSOFF GUESTROOM215_218 130.44 6.0 1551.334 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
34 GUESTROOM219_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM219 32.61 1.5 387.833 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 387.833
35 GUESTROOM220_223_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM220_223 130.44 6.0 1551.334 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 1551.334
36 GUESTROOM224_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM224 32.61 1.5 387.833 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 387.833
37 GUESTROOM301_PLUGLOAD ALWAYSOFF GUESTROOM301 32.61 1.5 387.861 11.893 258.574 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
38 GUESTROOM302_305_PLUGLOAD ALWAYSOFF GUESTROOM302_305 130.45 6.0 1551.444 11.893 258.574 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
39 GUESTROOM306_308_PLUGLOAD ALWAYSOFF GUESTROOM306_308 105.36 4.5 1253.089 11.893 278.464 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
40 GUESTROOM309_312_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM309_312 130.45 6.0 1551.444 11.893 258.574 0.000 0.500 0.000 0.500 MiscPlug 0.000 1551.444
41 GUESTROOM313_PLUGLOAD ALWAYSOFF GUESTROOM313 32.61 1.5 387.861 11.893 258.574 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
42 GUESTROOM314_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM314 32.61 1.5 387.833 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 387.833
43 GUESTROOM315_318_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM315_318 130.44 6.0 1551.334 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 1551.334
44 GUESTROOM319_PLUGLOAD ALWAYSOFF GUESTROOM319 32.61 1.5 387.833 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
45 GUESTROOM320_323_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM320_323 130.44 6.0 1551.334 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 1551.334
46 GUESTROOM324_PLUGLOAD ALWAYSOFF GUESTROOM324 32.61 1.5 387.833 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
47 GUESTROOM401_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM401 32.61 1.5 387.861 11.893 258.574 0.000 0.500 0.000 0.500 MiscPlug 0.000 387.861
48 GUESTROOM402_405_PLUGLOAD ALWAYSOFF GUESTROOM402_405 130.45 6.0 1551.444 11.893 258.574 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
49 GUESTROOM406_408_PLUGLOAD ALWAYSOFF GUESTROOM406_408 105.36 4.5 1253.089 11.893 278.464 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
50 GUESTROOM409_412_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM409_412 130.45 6.0 1551.444 11.893 258.574 0.000 0.500 0.000 0.500 MiscPlug 0.000 1551.444
51 GUESTROOM413_PLUGLOAD ALWAYSOFF GUESTROOM413 32.61 1.5 387.861 11.893 258.574 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
52 GUESTROOM414_PLUGLOAD ALWAYSOFF GUESTROOM414 32.61 1.5 387.833 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
53 GUESTROOM415_418_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM415_418 130.44 6.0 1551.334 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 1551.334
54 GUESTROOM419_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM419 32.61 1.5 387.833 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 387.833
55 GUESTROOM420_423_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM420_423 130.44 6.0 1551.334 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 1551.334
56 GUESTROOM424_PLUGLOAD GUESTROOM_EQP_SCH_BASE GUESTROOM424 32.61 1.5 387.833 11.893 258.556 0.000 0.500 0.000 0.500 MiscPlug 0.000 387.833
57 MECHANICALROOMFLR1_PLUGLOAD ALWAYSOFF MECHANICALROOMFLR1 32.61 0.5 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
58 MEETINGROOMFLR1_PLUGLOAD MEETINGROOM_EQP_SCH MEETINGROOMFLR1 80.27 43.0 496.093 6.180 11.537 0.000 0.500 0.000 0.500 MiscPlug 0.000 237.692
59 REARSTAIRSFLR1_PLUGLOAD ALWAYSOFF REARSTAIRSFLR1 20.07 1.1 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
60 REARSTAIRSFLR2_PLUGLOAD ALWAYSOFF REARSTAIRSFLR2 20.07 1.1 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
61 REARSTAIRSFLR3_PLUGLOAD ALWAYSOFF REARSTAIRSFLR3 20.07 1.1 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
62 REARSTAIRSFLR4_PLUGLOAD ALWAYSOFF REARSTAIRSFLR4 20.07 1.1 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
63 REARSTORAGEFLR1_PLUGLOAD ALWAYSOFF REARSTORAGEFLR1 20.07 0.4 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
64 REARSTORAGEFLR2_PLUGLOAD ALWAYSOFF REARSTORAGEFLR2 20.07 0.4 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
65 REARSTORAGEFLR3_PLUGLOAD ALWAYSOFF REARSTORAGEFLR3 20.07 0.4 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
66 REARSTORAGEFLR4_PLUGLOAD ALWAYSOFF REARSTORAGEFLR4 20.07 0.4 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
67 RESTROOMFLR1_PLUGLOAD ALWAYSOFF RESTROOMFLR1 32.61 1.8 0.000 0.000 0.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 0.000
68 LAUNDRY EQUIPMENT 1 LAUNDRYROOM_EQP_ELEC_SCH LAUNDRYROOMFLR1 97.83 10.5 2709.075 27.693 257.272 0.000 0.200 0.000 0.800 Laundry 0.000 2709.075


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 DRYER EQUIPMENT 1 LAUNDRYROOM_EQP_GAS_SCH LAUNDRYROOMFLR1 97.83 10.5 40096.028 409.867 3807.790 0.000 0.200 0.000 0.800 Laundry 0.000 40096.028


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
3 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
4 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
5 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
6 RES_ROOF 18 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
7 NONRES_EXT_WALL_GRD 20 4 7 0.167 0.4732 0.900 0.900 0.700 0.700 Smooth
8 NONRES_EXT_WALL_MID 21 4 7 0.167 0.5387 0.900 0.900 0.700 0.700 Smooth
9 NONRES_EXT_WALL_TOP 22 4 7 0.167 0.8637 0.900 0.900 0.700 0.700 Smooth
10 RES_EXT_WALL_GRD 23 4 7 0.167 0.4732 0.900 0.900 0.700 0.700 Smooth
11 RES_EXT_WALL_MID 24 4 7 0.167 0.5387 0.900 0.900 0.700 0.700 Smooth
12 RES_EXT_WALL_TOP 25 4 7 0.167 0.8637 0.900 0.900 0.700 0.700 Smooth
13 S_REARSTAIRSFLR1_0_0_0_FFACTOR 37 2 7 0.167 0.5060 0.000 0.900 0.000 0.700 MediumRough
14 S_CORRIDORFLR1_0_0_0_FFACTOR 38 2 7 0.167 0.5772E-01 0.000 0.900 0.000 0.700 MediumRough
15 S_REARSTORAGEFLR1_0_0_0_FFACTOR 39 2 7 0.167 0.5060 0.000 0.900 0.000 0.700 MediumRough
16 S_FRONTLOUNGEFLR1_0_0_0_FFACTOR 40 2 7 0.167 0.1555 0.000 0.900 0.000 0.700 MediumRough
17 S_RESTROOMFLR1_0_0_0_FFACTOR 41 2 7 0.167 0.1091 0.000 0.900 0.000 0.700 MediumRough
18 S_MEETINGROOMFLR1_0_0_0_FFACTOR 42 2 7 0.167 0.1091 0.000 0.900 0.000 0.700 MediumRough
19 S_MECHANICALROOMFLR1_0_0_0_FFACTOR 43 2 7 0.167 0.1091 0.000 0.900 0.000 0.700 MediumRough
20 S_GUESTROOM101_0_0_0_FFACTOR 44 2 7 0.167 0.1091 0.000 0.900 0.000 0.700 MediumRough
21 S_GUESTROOM102_0_0_0_FFACTOR 45 2 7 0.167 0.1091 0.000 0.900 0.000 0.700 MediumRough
22 S_GUESTROOM103_0_0_0_FFACTOR 46 2 7 0.167 0.1091 0.000 0.900 0.000 0.700 MediumRough
23 S_GUESTROOM104_0_0_0_FFACTOR 47 2 7 0.167 0.1091 0.000 0.900 0.000 0.700 MediumRough
24 S_GUESTROOM105_0_0_0_FFACTOR 48 2 7 0.167 0.1091 0.000 0.900 0.000 0.700 MediumRough
25 S_EMPLOYEELOUNGEFLR1_0_0_0_FFACTOR 49 2 7 0.167 0.1091 0.000 0.900 0.000 0.700 MediumRough
26 S_LAUNDRYROOMFLR1_0_0_0_FFACTOR 50 2 7 0.167 0.1091 0.000 0.900 0.000 0.700 MediumRough
27 S_ELEVATORCOREFLR1_0_0_0_FFACTOR 51 2 7 0.167 0.1091 0.000 0.900 0.000 0.700 MediumRough
28 S_EXERCISECENTERFLR1_0_0_0_FFACTOR 52 2 7 0.167 0.1091 0.000 0.900 0.000 0.700 MediumRough
29 S_FRONTOFFICEFLR1_0_0_0_FFACTOR 53 2 7 0.167 0.1091 0.000 0.900 0.000 0.700 MediumRough
30 S_FRONTSTAIRSFLR1_0_0_0_FFACTOR 54 2 7 0.167 0.5061 0.000 0.900 0.000 0.700 MediumRough
31 S_FRONTSTORAGEFLR1_0_0_0_FFACTOR 55 2 7 0.167 0.1091 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
3 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
4 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
5 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
6 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
7 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
8 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
9 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
10 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
11 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
12 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
13 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
14 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
15 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.879
17 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
18 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
19 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
20 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.622
21 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
22 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
23 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
24 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.9237
25 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
26 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
27 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
28 RES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.879
29 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
30 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
31 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
32 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.622
33 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
34 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
35 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
36 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.9237
37 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
38 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 1.899
39 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
40 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 17.25
41 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
42 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 1.899
43 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
44 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 6.355
45 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
46 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 9.091
47 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
48 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 9.091
49 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
50 ~FC_Insulation_7 0.0000 0.000 0.000 0.000 9.091
51 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
52 ~FC_Insulation_8 0.0000 0.000 0.000 0.000 9.091
53 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
54 ~FC_Insulation_9 0.0000 0.000 0.000 0.000 9.091
55 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
56 ~FC_Insulation_10 0.0000 0.000 0.000 0.000 9.091
57 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
58 ~FC_Insulation_11 0.0000 0.000 0.000 0.000 9.090
59 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
60 ~FC_Insulation_12 0.0000 0.000 0.000 0.000 9.090
61 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
62 ~FC_Insulation_13 0.0000 0.000 0.000 0.000 9.090
63 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
64 ~FC_Insulation_14 0.0000 0.000 0.000 0.000 9.090
65 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
66 ~FC_Insulation_15 0.0000 0.000 0.000 0.000 9.090
67 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
68 ~FC_Insulation_16 0.0000 0.000 0.000 0.000 9.090
69 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
70 ~FC_Insulation_17 0.0000 0.000 0.000 0.000 9.090
71 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
72 ~FC_Insulation_18 0.0000 0.000 0.000 0.000 1.899
73 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
74 ~FC_Insulation_19 0.0000 0.000 0.000 0.000 9.090
75 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
4 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
5 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
6 1 -12.650482 3.3590720 -12.650482 0.19281313
7 0 16.907513 1.4507143 16.907513  
8 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
9 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
10 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
11 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
12 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
13 2 51.553741 0.22121684 1.2284947 -0.25833933
14 1 -128.86110 0.21944682 -5.1479470 1.1228340
15 0 81.526494 0.16043334E-01 4.4519351  
16 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
17 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
18 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
19 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
20 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
21 2 1.2284947 0.22121684 51.553741 -0.25833933
22 1 -5.1479470 0.21944682 -128.86110 1.1228340
23 0 4.4519351 0.16043334E-01 81.526494  
24 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
25 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
26 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
27 0 21.357363 0.71091016E-01 5.4032014  
28 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
29 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
30 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
31 0 21.357363 0.71091016E-01 5.4032014  
32 7 -0.36647918E-12 0.99017352E-15 -0.12524254E-12 0.11287137E-15
33 6 0.32232689E-07 0.13745501E-09 0.73540832E-08 -0.15443095E-12
34 5 -0.20802731E-03 0.11514800E-05 -0.10673604E-03 0.72577554E-08
35 4 0.31287659 0.54979965E-03 0.10715012 -0.36520600E-04
36 3 -7.6763135 0.16745365E-01 -2.4606096 0.31019774E-01
37 2 42.222658 0.58633745E-01 15.762905 -0.34839622
38 1 -81.580790 0.26106638E-01 -29.587615 1.1006766
39 0 46.824332 0.51830896E-03 16.280831  
40 7 -0.34356788E-12 0.73952097E-15 -0.11064625E-12 0.10727094E-15
41 6 0.31471220E-07 0.15553233E-09 0.71859949E-08 -0.15030115E-12
42 5 -0.20422126E-03 0.13085274E-05 -0.10483869E-03 0.70944080E-08
43 4 0.30851178 0.62719578E-03 0.10557613 -0.35895552E-04
44 3 -7.5900769 0.19168116E-01 -2.4350051 0.30596578E-01
45 2 41.938480 0.67322081E-01 15.658386 -0.34522994
46 1 -81.363271 0.30055761E-01 -29.494050 1.0960408
47 0 46.824334 0.59828989E-03 16.282970  
48 7 -0.29401507E-12 0.13966947E-14 -0.85785846E-13 0.14808880E-15
49 6 0.27633466E-07 0.24031617E-09 0.63389272E-08 -0.12963365E-12
50 5 -0.18482502E-03 0.20702380E-05 -0.95134628E-04 0.62694462E-08
51 4 0.28594721 0.10134342E-02 0.97454672E-01 -0.32698170E-04
52 3 -7.1435086 0.31556460E-01 -2.3024714 0.28407239E-01
53 2 40.466036 0.11268181 15.115524 -0.32882875
54 1 -80.235306 0.51039798E-01 -29.007554 1.0720029
55 0 46.824341 0.10305452E-02 16.294467  
56 7 -0.36647918E-12 0.99017352E-15 -0.12524254E-12 0.11287137E-15
57 6 0.32232689E-07 0.13745501E-09 0.73540832E-08 -0.15443095E-12
58 5 -0.20802731E-03 0.11514800E-05 -0.10673604E-03 0.72577554E-08
59 4 0.31287659 0.54979965E-03 0.10715012 -0.36520600E-04
60 3 -7.6763135 0.16745365E-01 -2.4606096 0.31019774E-01
61 2 42.222658 0.58633745E-01 15.762905 -0.34839622
62 1 -81.580790 0.26106638E-01 -29.587615 1.1006766
63 0 46.824332 0.51830896E-03 16.280831  
64 7 -0.34356788E-12 0.73952097E-15 -0.11064625E-12 0.10727094E-15
65 6 0.31471220E-07 0.15553233E-09 0.71859949E-08 -0.15030115E-12
66 5 -0.20422126E-03 0.13085274E-05 -0.10483869E-03 0.70944080E-08
67 4 0.30851178 0.62719578E-03 0.10557613 -0.35895552E-04
68 3 -7.5900769 0.19168116E-01 -2.4350051 0.30596578E-01
69 2 41.938480 0.67322081E-01 15.658386 -0.34522994
70 1 -81.363271 0.30055761E-01 -29.494050 1.0960408
71 0 46.824334 0.59828989E-03 16.282970  
72 7 -0.29401507E-12 0.13966947E-14 -0.85785846E-13 0.14808880E-15
73 6 0.27633466E-07 0.24031617E-09 0.63389272E-08 -0.12963365E-12
74 5 -0.18482502E-03 0.20702380E-05 -0.95134628E-04 0.62694462E-08
75 4 0.28594721 0.10134342E-02 0.97454672E-01 -0.32698170E-04
76 3 -7.1435086 0.31556460E-01 -2.3024714 0.28407239E-01
77 2 40.466036 0.11268181 15.115524 -0.32882875
78 1 -80.235306 0.51039798E-01 -29.007554 1.0720029
79 0 46.824341 0.10305452E-02 16.294467  
80 7 -0.80791508E-09 -0.47892449E-16 0.12593346E-14 0.30165100E-17
81 6 0.14268398E-04 0.98357463E-08 0.31653513E-02 -0.26553620E-04
82 5 -0.10362005E-02 0.58396321E-05 -0.22233067 0.19438470E-02
83 4 0.23885967E-01 0.26611927E-03 4.8063229 -0.45041755E-01
84 3 -0.20985966 0.21188845E-02 -37.890197 0.39720340
85 2 0.74525450 0.35281416E-02 116.22852 -1.4145227
86 1 -1.0756870 0.10767437E-02 -143.75693 2.0465681
87 0 0.52444971 0.25832383E-04 60.838472  
88 7 -0.74192065E-08 0.17093607E-15 -0.20405444E-14 0.24793010E-16
89 6 0.21091315E-05 0.11198761E-08 0.32008996E-02 -0.26851828E-04
90 5 -0.12695536E-03 0.65644340E-06 -0.22435124 0.19616816E-02
91 4 0.27551020E-02 0.29721570E-04 4.8399788 -0.45365275E-01
92 3 -0.23662671E-01 0.23527614E-03 -38.080331 0.39930499
93 2 0.83265029E-01 0.38974022E-03 116.59858 -1.4194727
94 1 -0.11968738 0.11808122E-03 -143.97478 2.0501489
95 0 0.58231101E-01 0.28520223E-05 60.838472  
96 7 -0.80792997E-09 -0.47690880E-16 0.11846361E-14 0.38794322E-17
97 6 0.14268139E-04 0.98355770E-08 0.31653521E-02 -0.26553626E-04
98 5 -0.10361816E-02 0.58395262E-05 -0.22233071 0.19438474E-02
99 4 0.23885534E-01 0.26611448E-03 4.8063236 -0.45041761E-01
100 3 -0.20985585 0.21188460E-02 -37.890201 0.39720344
101 2 0.74524099 0.35280780E-02 116.22853 -1.4145228
102 1 -1.0756675 0.10767236E-02 -143.75693 2.0465682
103 0 0.52444020 0.25832174E-04 60.838472  
104 7 -0.27270831E-08 -0.14640994E-14 0.77246880E-14 -0.11136204E-15
105 6 0.44380016E-05 0.29728288E-08 0.31933073E-02 -0.26788137E-04
106 5 -0.31392667E-03 0.17590414E-05 -0.22391994 0.19578747E-02
107 4 0.71873766E-02 0.80023484E-04 4.8327995 -0.45296259E-01
108 3 -0.63011199E-01 0.63603456E-03 -38.039797 0.39885692
109 2 0.22359600 0.10575923E-02 116.51972 -1.4184178
110 1 -0.32263580 0.32204047E-03 -143.92837 2.0493861
111 0 0.15727836 0.77932528E-05 60.838472  
112 7 -0.39057053E-08 -0.42506287E-14 0.10712727E-14 -0.44813707E-16
113 6 0.32493862E-05 0.20875134E-08 0.31969172E-02 -0.26818420E-04
114 5 -0.22295241E-03 0.12328060E-05 -0.22412507 0.19596853E-02
115 4 0.50578988E-02 0.56036772E-04 4.8362151 -0.45329093E-01
116 3 -0.44192477E-01 0.44503248E-03 -38.059087 0.39907015
117 2 0.15660491 0.73951266E-03 116.55726 -1.4189199
118 1 -0.22583334 0.22493252E-03 -143.95046 2.0497492
119 0 0.11005492 0.54598006E-05 60.838472  
120 7 -0.39057053E-08 -0.42504162E-14 0.12085340E-14 -0.43676917E-16
121 6 0.32493862E-05 0.20875134E-08 0.31969172E-02 -0.26818420E-04
122 5 -0.22295241E-03 0.12328060E-05 -0.22412507 0.19596853E-02
123 4 0.50578988E-02 0.56036772E-04 4.8362151 -0.45329093E-01
124 3 -0.44192477E-01 0.44503248E-03 -38.059087 0.39907015
125 2 0.15660491 0.73951266E-03 116.55726 -1.4189199
126 1 -0.22583334 0.22493252E-03 -143.95046 2.0497492
127 0 0.11005492 0.54598012E-05 60.838472  
128 7 -0.39057053E-08 -0.42506264E-14 0.10639975E-14 -0.44604563E-16
129 6 0.32493862E-05 0.20875134E-08 0.31969172E-02 -0.26818420E-04
130 5 -0.22295241E-03 0.12328060E-05 -0.22412507 0.19596853E-02
131 4 0.50578988E-02 0.56036772E-04 4.8362151 -0.45329093E-01
132 3 -0.44192477E-01 0.44503248E-03 -38.059087 0.39907015
133 2 0.15660491 0.73951266E-03 116.55726 -1.4189199
134 1 -0.22583334 0.22493252E-03 -143.95046 2.0497492
135 0 0.11005492 0.54598006E-05 60.838472  
136 7 -0.39057053E-08 -0.42505100E-14 0.11250828E-14 -0.42241137E-16
137 6 0.32493862E-05 0.20875134E-08 0.31969172E-02 -0.26818420E-04
138 5 -0.22295241E-03 0.12328060E-05 -0.22412507 0.19596853E-02
139 4 0.50578988E-02 0.56036772E-04 4.8362151 -0.45329093E-01
140 3 -0.44192477E-01 0.44503248E-03 -38.059087 0.39907015
141 2 0.15660491 0.73951266E-03 116.55726 -1.4189199
142 1 -0.22583334 0.22493252E-03 -143.95046 2.0497492
143 0 0.11005492 0.54598005E-05 60.838472  
144 7 -0.39057053E-08 -0.42505099E-14 0.11250826E-14 -0.42241134E-16
145 6 0.32493862E-05 0.20875134E-08 0.31969172E-02 -0.26818420E-04
146 5 -0.22295241E-03 0.12328060E-05 -0.22412507 0.19596853E-02
147 4 0.50578988E-02 0.56036772E-04 4.8362151 -0.45329093E-01
148 3 -0.44192477E-01 0.44503248E-03 -38.059087 0.39907015
149 2 0.15660491 0.73951266E-03 116.55726 -1.4189199
150 1 -0.22583334 0.22493252E-03 -143.95046 2.0497492
151 0 0.11005492 0.54598005E-05 60.838472  
152 7 -0.39057053E-08 -0.42506287E-14 0.10712725E-14 -0.44813704E-16
153 6 0.32493862E-05 0.20875134E-08 0.31969172E-02 -0.26818420E-04
154 5 -0.22295241E-03 0.12328060E-05 -0.22412507 0.19596853E-02
155 4 0.50578988E-02 0.56036772E-04 4.8362151 -0.45329093E-01
156 3 -0.44192477E-01 0.44503248E-03 -38.059087 0.39907015
157 2 0.15660491 0.73951266E-03 116.55726 -1.4189199
158 1 -0.22583334 0.22493252E-03 -143.95046 2.0497492
159 0 0.11005492 0.54598006E-05 60.838472  
160 7 -0.39054204E-08 -0.42493446E-14 0.10663444E-14 -0.40159033E-16
161 6 0.32495807E-05 0.20876626E-08 0.31969166E-02 -0.26818415E-04
162 5 -0.22296763E-03 0.12328949E-05 -0.22412503 0.19596850E-02
163 4 0.50582574E-02 0.56040825E-04 4.8362146 -0.45329088E-01
164 3 -0.44195652E-01 0.44506477E-03 -38.059084 0.39907011
165 2 0.15661623 0.73956643E-03 116.55725 -1.4189199
166 1 -0.22584970 0.22494896E-03 -143.95046 2.0497492
167 0 0.11006290 0.54601860E-05 60.838472  
168 7 -0.39054204E-08 -0.42494337E-14 0.10899344E-14 -0.41616146E-16
169 6 0.32495807E-05 0.20876627E-08 0.31969166E-02 -0.26818415E-04
170 5 -0.22296763E-03 0.12328949E-05 -0.22412503 0.19596850E-02
171 4 0.50582574E-02 0.56040826E-04 4.8362146 -0.45329088E-01
172 3 -0.44195652E-01 0.44506477E-03 -38.059084 0.39907011
173 2 0.15661623 0.73956644E-03 116.55725 -1.4189199
174 1 -0.22584970 0.22494896E-03 -143.95046 2.0497492
175 0 0.11006290 0.54601880E-05 60.838472  
176 7 -0.39054204E-08 -0.42494337E-14 0.10899346E-14 -0.41616150E-16
177 6 0.32495807E-05 0.20876627E-08 0.31969166E-02 -0.26818415E-04
178 5 -0.22296763E-03 0.12328949E-05 -0.22412503 0.19596850E-02
179 4 0.50582574E-02 0.56040826E-04 4.8362146 -0.45329088E-01
180 3 -0.44195652E-01 0.44506477E-03 -38.059084 0.39907011
181 2 0.15661623 0.73956644E-03 116.55725 -1.4189199
182 1 -0.22584970 0.22494896E-03 -143.95046 2.0497492
183 0 0.11006290 0.54601880E-05 60.838472  
184 7 -0.39054204E-08 -0.42494334E-14 0.10899625E-14 -0.41615940E-16
185 6 0.32495807E-05 0.20876627E-08 0.31969166E-02 -0.26818415E-04
186 5 -0.22296763E-03 0.12328949E-05 -0.22412503 0.19596850E-02
187 4 0.50582574E-02 0.56040826E-04 4.8362146 -0.45329088E-01
188 3 -0.44195652E-01 0.44506477E-03 -38.059084 0.39907011
189 2 0.15661623 0.73956644E-03 116.55725 -1.4189199
190 1 -0.22584970 0.22494896E-03 -143.95046 2.0497492
191 0 0.11006290 0.54601880E-05 60.838472  
192 7 -0.39054204E-08 -0.42494243E-14 0.10980222E-14 -0.40602274E-16
193 6 0.32495807E-05 0.20876627E-08 0.31969166E-02 -0.26818415E-04
194 5 -0.22296763E-03 0.12328949E-05 -0.22412503 0.19596850E-02
195 4 0.50582574E-02 0.56040826E-04 4.8362146 -0.45329088E-01
196 3 -0.44195652E-01 0.44506477E-03 -38.059084 0.39907011
197 2 0.15661623 0.73956644E-03 116.55725 -1.4189199
198 1 -0.22584970 0.22494896E-03 -143.95046 2.0497492
199 0 0.11006290 0.54601880E-05 60.838472  
200 7 -0.39054204E-08 -0.42494877E-14 0.10325159E-14 -0.41679037E-16
201 6 0.32495807E-05 0.20876626E-08 0.31969166E-02 -0.26818415E-04
202 5 -0.22296763E-03 0.12328949E-05 -0.22412503 0.19596850E-02
203 4 0.50582574E-02 0.56040825E-04 4.8362146 -0.45329088E-01
204 3 -0.44195652E-01 0.44506477E-03 -38.059084 0.39907011
205 2 0.15661623 0.73956643E-03 116.55725 -1.4189199
206 1 -0.22584970 0.22494896E-03 -143.95046 2.0497492
207 0 0.11006290 0.54601862E-05 60.838472  
208 7 -0.39054204E-08 -0.42494335E-14 0.10899337E-14 -0.41616135E-16
209 6 0.32495807E-05 0.20876627E-08 0.31969166E-02 -0.26818415E-04
210 5 -0.22296763E-03 0.12328949E-05 -0.22412503 0.19596850E-02
211 4 0.50582574E-02 0.56040826E-04 4.8362146 -0.45329088E-01
212 3 -0.44195652E-01 0.44506477E-03 -38.059084 0.39907011
213 2 0.15661623 0.73956644E-03 116.55725 -1.4189199
214 1 -0.22584970 0.22494896E-03 -143.95046 2.0497492
215 0 0.11006290 0.54601880E-05 60.838472  
216 7 -0.80774553E-09 -0.47850353E-16 0.12017108E-14 0.41673088E-17
217 6 0.14271341E-04 0.98377638E-08 0.31653431E-02 -0.26553551E-04
218 5 -0.10364148E-02 0.58408312E-05 -0.22233020 0.19438429E-02
219 4 0.23890906E-01 0.26617403E-03 4.8063151 -0.45041680E-01
220 3 -0.20990303 0.21193212E-02 -37.890153 0.39720291
221 2 0.74540843 0.35288700E-02 116.22843 -1.4145216
222 1 -1.0759091 0.10769662E-02 -143.75688 2.0465673
223 0 0.52455799 0.25837790E-04 60.838472  
224 7 -0.39054204E-08 -0.42494242E-14 0.10980220E-14 -0.40602271E-16
225 6 0.32495807E-05 0.20876627E-08 0.31969166E-02 -0.26818415E-04
226 5 -0.22296763E-03 0.12328949E-05 -0.22412503 0.19596850E-02
227 4 0.50582574E-02 0.56040826E-04 4.8362146 -0.45329088E-01
228 3 -0.44195652E-01 0.44506477E-03 -38.059084 0.39907011
229 2 0.15661623 0.73956644E-03 116.55725 -1.4189199
230 1 -0.22584970 0.22494896E-03 -143.95046 2.0497492
231 0 0.11006290 0.54601880E-05 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.3464_SHGC_0.38 35 1 VerySmooth 1.968 1.968 1.000 0.381    
2 RESWINDOW_U_0.3464_SHGC_0.38 36 1 VerySmooth 1.968 1.968 1.000 0.381    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   3.78357E-002 0.29373 0.50217 0.50217 0.38000 0.13982 0.18519 0.00000 0.84000 0.84000 0.11289 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   3.78357E-002 0.29373 0.50217 0.50217 0.38000 0.13982 0.18519 0.00000 0.84000 0.84000 0.11289 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 FRONTLOUNGEFLR1 5 0
2 MEETINGROOMFLR1 3 0
3 LAUNDRYROOMFLR1 3 0
4 FRONTOFFICEFLR1 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 FRONTLOUNGEFLR1 0  
2 MEETINGROOMFLR1 0  
3 LAUNDRYROOMFLR1 0  
4 FRONTOFFICEFLR1 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH SHOWER WATER HEATER 1.1356 87921.3 0.487 6.1110E-002
2 WaterHeater:Mixed SWH LAUNDRY WATER HEATER 0.7570 58614.2 0.799 0.4880


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 W_REARSTAIRSFLR1_2_0_0 0 211.83 138.95 11.58 0 3.35 10.67 3.76 0.00 0 No No
2 W_REARSTAIRSFLR1_3_0_0 0 635.46 138.95 11.58 0 3.35 10.67 3.76 0.00 0 No No
3 W_REARSTAIRSFLR1_3_0_0_DOOR 0 635.46 138.95 11.58 0 3.35 10.67 3.76 0.00 0 No No
4 P_REARSTAIRSFLR1_4_0_0 0 0.00 0.00 0.00 0 3.35 10.67 3.76 0.00 0 No No
5 P_REARSTAIRSFLR1_5_0_0 0 0.00 0.00 0.00 0 3.35 10.67 3.76 0.00 0 No No
6 S_REARSTAIRSFLR1_0_0_0 0 0.00 0.00 0.00 0 3.35 10.67 3.76 0.00 0 No No
7 C_REARSTAIRSFLR1_1_0_0 0 0.00 0.00 0.00 0 3.35 10.67 3.76 0.00 0 No No
8 P_CORRIDORFLR1_10003_0_10002 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
9 W_CORRIDORFLR1_2_0_0 0 211.83 138.95 11.58 0 3.35 9.75 4.11 0.30 4 No No
10 W_CORRIDORFLR1_2_0_0_0_0 0 211.83 138.95 11.58 0 3.35 9.75 4.11 0.30 1 No No
11 P_CORRIDORFLR1_4_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
12 P_CORRIDORFLR1_5_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
13 P_CORRIDORFLR1_6_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
14 P_CORRIDORFLR1_7_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
15 P_CORRIDORFLR1_8_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
16 P_CORRIDORFLR1_9_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
17 W_CORRIDORFLR1_10_0_0 0 635.46 138.95 11.58 0 3.35 9.75 4.11 0.30 4 No No
18 W_CORRIDORFLR1_10_0_0_DOOR 0 635.46 138.95 11.58 0 3.35 9.75 4.11 0.30 0 No No
19 P_CORRIDORFLR1_11_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
20 P_CORRIDORFLR1_12_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
21 P_CORRIDORFLR1_13_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
22 P_CORRIDORFLR1_14_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
23 P_CORRIDORFLR1_15_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
24 W_CORRIDORFLR1_16_0_0 0 211.83 59.84 11.58 0 3.35 9.75 4.11 0.30 4 No No
25 D_CORRIDORFLR1_16_0_0_0_0 0 211.83 59.84 11.58 0 3.35 9.75 4.11 0.30 1 No No
26 P_CORRIDORFLR1_17_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
27 P_CORRIDORFLR1_18_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
28 P_CORRIDORFLR1_19_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
29 W_CORRIDORFLR1_20_0_0 0 635.46 132.99 11.58 0 3.35 9.75 4.11 0.30 4 No No
30 W_CORRIDORFLR1_20_0_0_0_0 0 635.46 132.99 11.58 0 3.35 9.75 4.11 0.30 1 No No
31 P_CORRIDORFLR1_21_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
32 P_CORRIDORFLR1_22_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
33 P_CORRIDORFLR1_23_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
34 P_CORRIDORFLR1_24_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
35 P_CORRIDORFLR1_25_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
36 P_CORRIDORFLR1_26_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
37 P_CORRIDORFLR1_27_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
38 S_CORRIDORFLR1_0_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
39 C_CORRIDORFLR1_1_0_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
40 C_CORRIDORFLR1_1_1_0 0 0.00 0.00 0.00 0 3.35 9.75 4.11 0.30 0 No No
41 P_REARSTORAGEFLR1_10027_0_10025 0 0.00 0.00 0.00 0 3.35 10.67 3.76 0.00 0 No No
42 W_REARSTORAGEFLR1_2_0_0 0 211.83 138.95 11.58 0 3.35 10.67 3.76 0.00 0 No No
43 P_REARSTORAGEFLR1_4_0_0 0 0.00 0.00 0.00 0 3.35 10.67 3.76 0.00 0 No No
44 W_REARSTORAGEFLR1_5_0_0 0 635.46 132.99 11.58 0 3.35 10.67 3.76 0.00 0 No No
45 S_REARSTORAGEFLR1_0_0_0 0 0.00 0.00 0.00 0 3.35 10.67 3.76 0.00 0 No No
46 C_REARSTORAGEFLR1_1_0_0 0 0.00 0.00 0.00 0 3.35 10.67 3.76 0.00 0 No No
47 P_FRONTLOUNGEFLR1_10018_0_10016 0 0.00 0.00 0.00 0 3.35 28.04 11.63 0.16 0 No No
48 P_FRONTLOUNGEFLR1_2_0_0 0 0.00 0.00 0.00 0 3.35 28.04 11.63 0.16 0 No No
49 W_FRONTLOUNGEFLR1_4_0_0 0 211.83 59.84 11.58 0 3.35 28.04 11.63 0.16 4 No No
50 W_FRONTLOUNGEFLR1_5_0_0 0 635.46 132.99 11.58 0 3.35 28.04 11.63 0.16 3 No No
51 W_FRONTLOUNGEFLR1_5_0_0_0_0 0 635.46 132.99 11.58 0 3.35 28.04 11.63 0.16 2 No No
52 W_FRONTLOUNGEFLR1_5_0_0_0_1 0 635.46 132.99 11.58 0 3.35 28.04 11.63 0.16 2 No No
53 W_FRONTLOUNGEFLR1_5_0_0_0_2 0 635.46 132.99 11.58 0 3.35 28.04 11.63 0.16 2 No No
54 W_FRONTLOUNGEFLR1_5_0_0_0_3 0 635.46 132.99 11.58 0 3.35 28.04 11.63 0.16 2 No No
55 W_FRONTLOUNGEFLR1_5_0_0_0_4 0 635.46 132.99 11.58 0 3.35 28.04 11.63 0.16 2 No No
56 S_FRONTLOUNGEFLR1_0_0_0 0 0.00 0.00 0.00 0 3.35 28.04 11.63 0.16 0 No No
57 C_FRONTLOUNGEFLR1_1_0_0 0 0.00 0.00 0.00 0 3.35 28.04 11.63 0.16 0 No No
58 C_FRONTLOUNGEFLR1_1_1_0 0 0.00 0.00 0.00 0 3.35 28.04 11.63 0.16 0 No No
59 P_RESTROOMFLR1_10019_0_10017 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.00 0 No No
60 P_RESTROOMFLR1_10020_0_10018 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.00 0 No No
61 P_RESTROOMFLR1_10033_0_10030 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.00 0 No No
62 W_RESTROOMFLR1_5_0_0 0 635.46 132.99 11.58 0 3.35 3.96 5.35 0.00 0 No No
63 S_RESTROOMFLR1_0_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.00 0 No No
64 C_RESTROOMFLR1_1_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.00 0 No No
65 P_MEETINGROOMFLR1_10021_0_10019 0 0.00 0.00 0.00 0 3.35 9.75 8.93 0.15 0 No No
66 P_MEETINGROOMFLR1_10022_0_10020 0 0.00 0.00 0.00 0 3.35 9.75 8.93 0.15 0 No No
67 P_MEETINGROOMFLR1_2_0_0 0 0.00 0.00 0.00 0 3.35 9.75 8.93 0.15 0 No No
68 W_MEETINGROOMFLR1_5_0_0 0 635.46 132.99 11.58 0 3.35 9.75 8.93 0.15 3 No No
69 W_MEETINGROOMFLR1_5_0_0_0_0 0 635.46 132.99 11.58 0 3.35 9.75 8.93 0.15 2 No No
70 W_MEETINGROOMFLR1_5_0_0_0_1 0 635.46 132.99 11.58 0 3.35 9.75 8.93 0.15 2 No No
71 W_MEETINGROOMFLR1_5_0_0_0_2 0 635.46 132.99 11.58 0 3.35 9.75 8.93 0.15 2 No No
72 S_MEETINGROOMFLR1_0_0_0 0 0.00 0.00 0.00 0 3.35 9.75 8.93 0.15 0 No No
73 C_MEETINGROOMFLR1_1_0_0 0 0.00 0.00 0.00 0 3.35 9.75 8.93 0.15 0 No No
74 C_MEETINGROOMFLR1_1_1_0 0 0.00 0.00 0.00 0 3.35 9.75 8.93 0.15 0 No No
75 P_MECHANICALROOMFLR1_10023_0_10021 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.00 0 No No
76 P_MECHANICALROOMFLR1_10041_0_10034 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.00 0 No No
77 P_MECHANICALROOMFLR1_2_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.00 0 No No
78 W_MECHANICALROOMFLR1_5_0_0 0 635.46 132.99 11.58 0 3.35 3.96 5.35 0.00 0 No No
79 S_MECHANICALROOMFLR1_0_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.00 0 No No
80 C_MECHANICALROOMFLR1_1_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.00 0 No No
81 P_GUESTROOM101_10024_0_10022 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
82 P_GUESTROOM101_10045_0_10036 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
83 P_GUESTROOM101_2_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
84 W_GUESTROOM101_5_0_0 0 635.46 132.99 11.58 0 3.35 3.96 5.35 0.12 3 No No
85 W_GUESTROOM101_5_0_0_0_0 0 635.46 132.99 11.58 0 3.35 3.96 5.35 0.12 2 No No
86 S_GUESTROOM101_0_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
87 C_GUESTROOM101_1_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
88 P_GUESTROOM102_10025_0_10023 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
89 P_GUESTROOM102_10049_0_10038 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
90 P_GUESTROOM102_2_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
91 W_GUESTROOM102_5_0_0 0 635.46 132.99 11.58 0 3.35 3.96 5.35 0.12 3 No No
92 W_GUESTROOM102_5_0_0_0_0 0 635.46 132.99 11.58 0 3.35 3.96 5.35 0.12 2 No No
93 S_GUESTROOM102_0_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
94 C_GUESTROOM102_1_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
95 P_GUESTROOM103_10026_0_10024 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
96 P_GUESTROOM103_10030_0_10027 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
97 P_GUESTROOM103_10053_0_10040 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
98 W_GUESTROOM103_5_0_0 0 635.46 132.99 11.58 0 3.35 3.96 5.35 0.12 3 No No
99 W_GUESTROOM103_5_0_0_0_0 0 635.46 132.99 11.58 0 3.35 3.96 5.35 0.12 2 No No
100 S_GUESTROOM103_0_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
101 C_GUESTROOM103_1_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
102 P_GUESTROOM104_10002_0_10001 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
103 P_GUESTROOM104_10007_0_10005 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
104 W_GUESTROOM104_3_0_0 0 635.46 138.95 11.58 0 3.35 3.96 5.35 0.12 3 No No
105 W_GUESTROOM104_3_0_0_0_0 0 635.46 138.95 11.58 0 3.35 3.96 5.35 0.12 2 No No
106 P_GUESTROOM104_4_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
107 S_GUESTROOM104_0_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
108 C_GUESTROOM104_1_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
109 P_GUESTROOM105_10008_0_10006 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
110 P_GUESTROOM105_10062_0_10043 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
111 W_GUESTROOM105_3_0_0 0 635.46 138.95 11.58 0 3.35 3.96 5.35 0.12 3 No No
112 W_GUESTROOM105_3_0_0_0_0 0 635.46 138.95 11.58 0 3.35 3.96 5.35 0.12 2 No No
113 P_GUESTROOM105_4_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
114 S_GUESTROOM105_0_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
115 C_GUESTROOM105_1_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
116 P_EMPLOYEELOUNGEFLR1_10009_0_10007 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
117 P_EMPLOYEELOUNGEFLR1_10066_0_10045 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
118 W_EMPLOYEELOUNGEFLR1_3_0_0 0 635.46 138.95 11.58 0 3.35 3.96 5.35 0.12 3 No No
119 W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 0 635.46 138.95 11.58 0 3.35 3.96 5.35 0.12 2 No No
120 P_EMPLOYEELOUNGEFLR1_4_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
121 S_EMPLOYEELOUNGEFLR1_0_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
122 C_EMPLOYEELOUNGEFLR1_1_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
123 P_LAUNDRYROOMFLR1_10010_0_10008 0 0.00 0.00 0.00 0 3.35 11.89 9.73 0.12 0 No No
124 P_LAUNDRYROOMFLR1_10070_0_10047 0 0.00 0.00 0.00 0 3.35 11.89 9.73 0.12 0 No No
125 W_LAUNDRYROOMFLR1_3_0_0 0 635.46 138.95 11.58 0 3.35 11.89 9.73 0.12 3 No No
126 W_LAUNDRYROOMFLR1_3_0_0_0_0 0 635.46 138.95 11.58 0 3.35 11.89 9.73 0.12 2 No No
127 W_LAUNDRYROOMFLR1_3_0_0_0_1 0 635.46 138.95 11.58 0 3.35 11.89 9.73 0.12 2 No No
128 W_LAUNDRYROOMFLR1_3_0_0_0_2 0 635.46 138.95 11.58 0 3.35 11.89 9.73 0.12 2 No No
129 P_LAUNDRYROOMFLR1_4_0_0 0 0.00 0.00 0.00 0 3.35 11.89 9.73 0.12 0 No No
130 S_LAUNDRYROOMFLR1_0_0_0 0 0.00 0.00 0.00 0 3.35 11.89 9.73 0.12 0 No No
131 C_LAUNDRYROOMFLR1_1_0_0 0 0.00 0.00 0.00 0 3.35 11.89 9.73 0.12 0 No No
132 C_LAUNDRYROOMFLR1_1_1_0 0 0.00 0.00 0.00 0 3.35 11.89 9.73 0.12 0 No No
133 P_ELEVATORCOREFLR1_10011_0_10009 0 0.00 0.00 0.00 0 3.35 1.83 2.99 0.00 0 No No
134 P_ELEVATORCOREFLR1_10012_0_10010 0 0.00 0.00 0.00 0 3.35 1.83 2.99 0.00 0 No No
135 P_ELEVATORCOREFLR1_10075_0_10050 0 0.00 0.00 0.00 0 3.35 1.83 2.99 0.00 0 No No
136 W_ELEVATORCOREFLR1_3_0_0 0 635.46 138.95 11.58 0 3.35 1.83 2.99 0.00 0 No No
137 S_ELEVATORCOREFLR1_0_0_0 0 0.00 0.00 0.00 0 3.35 1.83 2.99 0.00 0 No No
138 C_ELEVATORCOREFLR1_1_0_0 0 0.00 0.00 0.00 0 3.35 1.83 2.99 0.00 0 No No
139 P_EXERCISECENTERFLR1_10013_0_10011 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
140 P_EXERCISECENTERFLR1_10014_0_10012 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
141 W_EXERCISECENTERFLR1_3_0_0 0 635.46 138.95 11.58 0 3.35 3.96 5.35 0.12 3 No No
142 W_EXERCISECENTERFLR1_3_0_0_0_0 0 635.46 138.95 11.58 0 3.35 3.96 5.35 0.12 2 No No
143 P_EXERCISECENTERFLR1_4_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
144 S_EXERCISECENTERFLR1_0_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
145 C_EXERCISECENTERFLR1_1_0_0 0 0.00 0.00 0.00 0 3.35 3.96 5.35 0.12 0 No No
146 P_FRONTOFFICEFLR1_10015_0_10013 0 0.00 0.00 0.00 0 3.35 15.85 10.83 0.12 0 No No
147 P_FRONTOFFICEFLR1_10083_0_10053 0 0.00 0.00 0.00 0 3.35 15.85 10.83 0.12 0 No No
148 W_FRONTOFFICEFLR1_3_0_0 0 635.46 138.95 11.58 0 3.35 15.85 10.83 0.12 3 No No
149 W_FRONTOFFICEFLR1_3_0_0_0_0 0 635.46 138.95 11.58 0 3.35 15.85 10.83 0.12 2 No No
150 W_FRONTOFFICEFLR1_3_0_0_0_1 0 635.46 138.95 11.58 0 3.35 15.85 10.83 0.12 2 No No
151 W_FRONTOFFICEFLR1_3_0_0_0_2 0 635.46 138.95 11.58 0 3.35 15.85 10.83 0.12 2 No No
152 W_FRONTOFFICEFLR1_3_0_0_0_3 0 635.46 138.95 11.58 0 3.35 15.85 10.83 0.12 2 No No
153 P_FRONTOFFICEFLR1_4_0_0 0 0.00 0.00 0.00 0 3.35 15.85 10.83 0.12 0 No No
154 S_FRONTOFFICEFLR1_0_0_0 0 0.00 0.00 0.00 0 3.35 15.85 10.83 0.12 0 No No
155 C_FRONTOFFICEFLR1_1_0_0 0 0.00 0.00 0.00 0 3.35 15.85 10.83 0.12 0 No No
156 C_FRONTOFFICEFLR1_1_1_0 0 0.00 0.00 0.00 0 3.35 15.85 10.83 0.12 0 No No
157 P_FRONTSTAIRSFLR1_10017_0_10015 0 0.00 0.00 0.00 0 3.35 10.67 3.76 0.00 0 No No
158 P_FRONTSTAIRSFLR1_2_0_0 0 0.00 0.00 0.00 0 3.35 10.67 3.76 0.00 0 No No
159 W_FRONTSTAIRSFLR1_3_0_0 0 635.46 138.95 11.58 0 3.35 10.67 3.76 0.00 0 No No
160 W_FRONTSTAIRSFLR1_3_0_0_DOOR 0 635.46 138.95 11.58 0 3.35 10.67 3.76 0.00 0 No No
161 W_FRONTSTAIRSFLR1_4_0_0 0 211.83 59.84 11.58 0 3.35 10.67 3.76 0.00 0 No No
162 S_FRONTSTAIRSFLR1_0_0_0 0 0.00 0.00 0.00 0 3.35 10.67 3.76 0.00 0 No No
163 C_FRONTSTAIRSFLR1_1_0_0 0 0.00 0.00 0.00 0 3.35 10.67 3.76 0.00 0 No No
164 P_FRONTSTORAGEFLR1_10016_0_10014 0 0.00 0.00 0.00 0 3.35 1.52 2.57 0.00 0 No No
165 P_FRONTSTORAGEFLR1_10088_0_10056 0 0.00 0.00 0.00 0 3.35 1.52 2.57 0.00 0 No No
166 P_FRONTSTORAGEFLR1_10091_0_10058 0 0.00 0.00 0.00 0 3.35 1.52 2.57 0.00 0 No No
167 W_FRONTSTORAGEFLR1_3_0_0 0 635.46 138.95 11.58 0 3.35 1.52 2.57 0.00 0 No No
168 S_FRONTSTORAGEFLR1_0_0_0 0 0.00 0.00 0.00 0 3.35 1.52 2.57 0.00 0 No No
169 C_FRONTSTORAGEFLR1_1_0_0 0 0.00 0.00 0.00 0 3.35 1.52 2.57 0.00 0 No No
170 W_REARSTAIRSFLR2_2_0_0 0 211.83 138.95 11.58 0 2.74 10.67 3.76 0.00 0 No No
171 W_REARSTAIRSFLR2_3_0_0 0 635.46 138.95 11.58 0 2.74 10.67 3.76 0.00 0 No No
172 P_REARSTAIRSFLR2_4_0_0 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
173 P_REARSTAIRSFLR2_5_0_0 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
174 F_REARSTAIRSFLR2_10001_0_10000 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
175 C_REARSTAIRSFLR2_1_0_0 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
176 P_CORRIDORFLR2_10100_0_10062 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
177 W_CORRIDORFLR2_2_0_0 0 211.83 138.95 11.58 0 2.74 6.71 3.86 0.14 3 No No
178 W_CORRIDORFLR2_2_0_0_0_0 0 211.83 138.95 11.58 0 2.74 6.71 3.86 0.14 2 No No
179 P_CORRIDORFLR2_4_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
180 P_CORRIDORFLR2_5_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
181 P_CORRIDORFLR2_6_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
182 P_CORRIDORFLR2_7_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
183 P_CORRIDORFLR2_8_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
184 W_CORRIDORFLR2_9_0_0 0 635.46 138.95 11.58 0 2.74 6.71 3.86 0.14 4 No No
185 P_CORRIDORFLR2_10_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
186 P_CORRIDORFLR2_11_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
187 P_CORRIDORFLR2_12_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
188 P_CORRIDORFLR2_13_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
189 P_CORRIDORFLR2_14_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
190 W_CORRIDORFLR2_15_0_0 0 211.83 59.84 11.58 0 2.74 6.71 3.86 0.14 3 No No
191 W_CORRIDORFLR2_15_0_0_0_0 0 211.83 59.84 11.58 0 2.74 6.71 3.86 0.14 2 No No
192 P_CORRIDORFLR2_16_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
193 P_CORRIDORFLR2_17_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
194 P_CORRIDORFLR2_18_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
195 P_CORRIDORFLR2_19_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
196 P_CORRIDORFLR2_20_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
197 P_CORRIDORFLR2_21_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
198 F_CORRIDORFLR2_10004_0_10003 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
199 C_CORRIDORFLR2_1_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
200 P_REARSTORAGEFLR2_10119_0_10079 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
201 W_REARSTORAGEFLR2_2_0_0 0 211.83 138.95 11.58 0 2.74 10.67 3.76 0.00 0 No No
202 P_REARSTORAGEFLR2_4_0_0 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
203 W_REARSTORAGEFLR2_5_0_0 0 635.46 132.99 11.58 0 2.74 10.67 3.76 0.00 0 No No
204 F_REARSTORAGEFLR2_10028_0_10026 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
205 C_REARSTORAGEFLR2_1_0_0 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
206 P_GUESTROOM201_10114_0_10074 0 0.00 0.00 0.00 0 2.74 12.19 5.35 4.93E-002 0 No No
207 P_GUESTROOM201_2_0_0 0 0.00 0.00 0.00 0 2.74 12.19 5.35 4.93E-002 0 No No
208 W_GUESTROOM201_4_0_0 0 211.83 59.84 11.58 0 2.74 12.19 5.35 4.93E-002 4 No No
209 W_GUESTROOM201_5_0_0 0 635.46 132.99 11.58 0 2.74 12.19 5.35 4.93E-002 3 No No
210 W_GUESTROOM201_5_0_0_0_0 0 635.46 132.99 11.58 0 2.74 12.19 5.35 4.93E-002 2 No No
211 F_GUESTROOM201_10031_0_10028 0 0.00 0.00 0.00 0 2.74 12.19 5.35 4.93E-002 0 No No
212 C_GUESTROOM201_1_0_0 0 0.00 0.00 0.00 0 2.74 12.19 5.35 4.93E-002 0 No No
213 P_GUESTROOM202_205_10115_0_10075 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
214 P_GUESTROOM202_205_10126_0_10083 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
215 P_GUESTROOM202_205_2_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
216 W_GUESTROOM202_205_5_0_0 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 3 No No
217 W_GUESTROOM202_205_5_0_0_0_0 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
218 W_GUESTROOM202_205_5_0_0_0_1 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
219 W_GUESTROOM202_205_5_0_0_0_2 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
220 W_GUESTROOM202_205_5_0_0_0_3 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
221 F_GUESTROOM202_205_10032_0_10029 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
222 C_GUESTROOM202_205_1_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
223 P_GUESTROOM206_208_10116_0_10076 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
224 P_GUESTROOM206_208_10130_0_10085 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
225 P_GUESTROOM206_208_2_0_0 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
226 W_GUESTROOM206_208_5_0_0 0 635.46 132.99 11.58 0 2.74 12.80 10.02 0.19 3 No No
227 W_GUESTROOM206_208_5_0_0_0_0 0 635.46 132.99 11.58 0 2.74 12.80 10.02 0.19 2 No No
228 W_GUESTROOM206_208_5_0_0_0_1 0 635.46 132.99 11.58 0 2.74 12.80 10.02 0.19 2 No No
229 W_GUESTROOM206_208_5_0_0_0_2 0 635.46 132.99 11.58 0 2.74 12.80 10.02 0.19 2 No No
230 F_GUESTROOM206_208_10005_0_10004 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
231 F_GUESTROOM206_208_10035_0_10031 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
232 F_GUESTROOM206_208_10039_0_10032 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
233 C_GUESTROOM206_208_1_0_0 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
234 P_GUESTROOM209_212_10117_0_10077 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
235 P_GUESTROOM209_212_10137_0_10087 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
236 P_GUESTROOM209_212_2_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
237 W_GUESTROOM209_212_5_0_0 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 3 No No
238 W_GUESTROOM209_212_5_0_0_0_0 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
239 W_GUESTROOM209_212_5_0_0_0_1 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
240 W_GUESTROOM209_212_5_0_0_0_2 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
241 W_GUESTROOM209_212_5_0_0_0_3 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
242 F_GUESTROOM209_212_10040_0_10033 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
243 F_GUESTROOM209_212_10044_0_10035 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
244 F_GUESTROOM209_212_10048_0_10037 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
245 F_GUESTROOM209_212_10052_0_10039 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
246 C_GUESTROOM209_212_1_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
247 P_GUESTROOM213_10118_0_10078 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
248 P_GUESTROOM213_10123_0_10081 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
249 P_GUESTROOM213_10145_0_10089 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
250 W_GUESTROOM213_5_0_0 0 635.46 132.99 11.58 0 2.74 3.96 5.35 0.15 3 No No
251 W_GUESTROOM213_5_0_0_0_0 0 635.46 132.99 11.58 0 2.74 3.96 5.35 0.15 2 No No
252 F_GUESTROOM213_10056_0_10041 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
253 C_GUESTROOM213_1_0_0 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
254 P_GUESTROOM214_10099_0_10061 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
255 P_GUESTROOM214_10104_0_10064 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
256 W_GUESTROOM214_3_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 3 No No
257 W_GUESTROOM214_3_0_0_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 2 No No
258 P_GUESTROOM214_4_0_0 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
259 F_GUESTROOM214_10060_0_10042 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
260 C_GUESTROOM214_1_0_0 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
261 P_GUESTROOM215_218_10105_0_10065 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
262 P_GUESTROOM215_218_10156_0_10092 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
263 W_GUESTROOM215_218_3_0_0 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 3 No No
264 W_GUESTROOM215_218_3_0_0_0_0 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
265 W_GUESTROOM215_218_3_0_0_0_1 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
266 W_GUESTROOM215_218_3_0_0_0_2 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
267 W_GUESTROOM215_218_3_0_0_0_3 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
268 P_GUESTROOM215_218_4_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
269 F_GUESTROOM215_218_10064_0_10044 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
270 F_GUESTROOM215_218_10068_0_10046 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
271 F_GUESTROOM215_218_10072_0_10048 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
272 C_GUESTROOM215_218_1_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
273 P_ELEVATORCOREFLR2_10107_0_10067 0 0.00 0.00 0.00 0 2.74 1.83 2.99 0.00 0 No No
274 P_ELEVATORCOREFLR2_10108_0_10068 0 0.00 0.00 0.00 0 2.74 1.83 2.99 0.00 0 No No
275 P_ELEVATORCOREFLR2_2_0_0 0 0.00 0.00 0.00 0 2.74 1.83 2.99 0.00 0 No No
276 W_ELEVATORCOREFLR2_3_0_0 0 635.46 138.95 11.58 0 2.74 1.83 2.99 0.00 0 No No
277 F_ELEVATORCOREFLR2_10077_0_10051 0 0.00 0.00 0.00 0 2.74 1.83 2.99 0.00 0 No No
278 C_ELEVATORCOREFLR2_1_0_0 0 0.00 0.00 0.00 0 2.74 1.83 2.99 0.00 0 No No
279 P_GUESTROOM219_10106_0_10066 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
280 P_GUESTROOM219_10163_0_10094 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
281 P_GUESTROOM219_10167_0_10096 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
282 W_GUESTROOM219_3_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 3 No No
283 W_GUESTROOM219_3_0_0_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 2 No No
284 F_GUESTROOM219_10073_0_10049 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
285 C_GUESTROOM219_1_0_0 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
286 P_GUESTROOM220_223_10109_0_10069 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
287 P_GUESTROOM220_223_10110_0_10070 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
288 W_GUESTROOM220_223_3_0_0 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 3 No No
289 W_GUESTROOM220_223_3_0_0_0_0 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
290 W_GUESTROOM220_223_3_0_0_0_1 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
291 W_GUESTROOM220_223_3_0_0_0_2 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
292 W_GUESTROOM220_223_3_0_0_0_3 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
293 P_GUESTROOM220_223_4_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
294 F_GUESTROOM220_223_10081_0_10052 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
295 F_GUESTROOM220_223_10085_0_10054 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
296 C_GUESTROOM220_223_1_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
297 P_GUESTROOM224_10111_0_10071 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
298 P_GUESTROOM224_10179_0_10099 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
299 W_GUESTROOM224_3_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 3 No No
300 W_GUESTROOM224_3_0_0_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 2 No No
301 P_GUESTROOM224_4_0_0 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
302 F_GUESTROOM224_10086_0_10055 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
303 C_GUESTROOM224_1_0_0 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
304 P_FRONTSTORAGEFLR2_10112_0_10072 0 0.00 0.00 0.00 0 2.74 1.52 2.57 0.00 0 No No
305 P_FRONTSTORAGEFLR2_10184_0_10101 0 0.00 0.00 0.00 0 2.74 1.52 2.57 0.00 0 No No
306 W_FRONTSTORAGEFLR2_3_0_0 0 635.46 138.95 11.58 0 2.74 1.52 2.57 0.00 0 No No
307 P_FRONTSTORAGEFLR2_4_0_0 0 0.00 0.00 0.00 0 2.74 1.52 2.57 0.00 0 No No
308 F_FRONTSTORAGEFLR2_10093_0_10059 0 0.00 0.00 0.00 0 2.74 1.52 2.57 0.00 0 No No
309 C_FRONTSTORAGEFLR2_1_0_0 0 0.00 0.00 0.00 0 2.74 1.52 2.57 0.00 0 No No
310 P_FRONTSTAIRSFLR2_10113_0_10073 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
311 P_FRONTSTAIRSFLR2_10189_0_10103 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
312 W_FRONTSTAIRSFLR2_3_0_0 0 635.46 138.95 11.58 0 2.74 10.67 3.76 0.00 0 No No
313 W_FRONTSTAIRSFLR2_4_0_0 0 211.83 59.84 11.58 0 2.74 10.67 3.76 0.00 0 No No
314 F_FRONTSTAIRSFLR2_10090_0_10057 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
315 C_FRONTSTAIRSFLR2_1_0_0 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
316 W_REARSTAIRSFLR3_2_0_0 0 211.83 138.95 11.58 0 2.74 10.67 3.76 0.00 0 No No
317 W_REARSTAIRSFLR3_3_0_0 0 635.46 138.95 11.58 0 2.74 10.67 3.76 0.00 0 No No
318 P_REARSTAIRSFLR3_4_0_0 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
319 P_REARSTAIRSFLR3_5_0_0 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
320 F_REARSTAIRSFLR3_10098_0_10060 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
321 C_REARSTAIRSFLR3_1_0_0 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
322 P_CORRIDORFLR3_10198_0_10107 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
323 W_CORRIDORFLR3_2_0_0 0 211.83 138.95 11.58 0 2.74 6.71 3.86 0.14 3 No No
324 W_CORRIDORFLR3_2_0_0_0_0 0 211.83 138.95 11.58 0 2.74 6.71 3.86 0.14 2 No No
325 P_CORRIDORFLR3_4_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
326 P_CORRIDORFLR3_5_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
327 P_CORRIDORFLR3_6_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
328 P_CORRIDORFLR3_7_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
329 P_CORRIDORFLR3_8_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
330 W_CORRIDORFLR3_9_0_0 0 635.46 138.95 11.58 0 2.74 6.71 3.86 0.14 3 No No
331 P_CORRIDORFLR3_10_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
332 P_CORRIDORFLR3_11_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
333 P_CORRIDORFLR3_12_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
334 P_CORRIDORFLR3_13_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
335 P_CORRIDORFLR3_14_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
336 W_CORRIDORFLR3_15_0_0 0 211.83 59.84 11.58 0 2.74 6.71 3.86 0.14 3 No No
337 W_CORRIDORFLR3_15_0_0_0_0 0 211.83 59.84 11.58 0 2.74 6.71 3.86 0.14 2 No No
338 P_CORRIDORFLR3_16_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
339 P_CORRIDORFLR3_17_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
340 P_CORRIDORFLR3_18_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
341 P_CORRIDORFLR3_19_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
342 P_CORRIDORFLR3_20_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
343 P_CORRIDORFLR3_21_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
344 F_CORRIDORFLR3_10102_0_10063 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
345 C_CORRIDORFLR3_1_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
346 P_REARSTORAGEFLR3_10217_0_10124 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
347 W_REARSTORAGEFLR3_2_0_0 0 211.83 138.95 11.58 0 2.74 10.67 3.76 0.00 0 No No
348 P_REARSTORAGEFLR3_4_0_0 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
349 W_REARSTORAGEFLR3_5_0_0 0 635.46 132.99 11.58 0 2.74 10.67 3.76 0.00 0 No No
350 F_REARSTORAGEFLR3_10121_0_10080 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
351 C_REARSTORAGEFLR3_1_0_0 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
352 P_GUESTROOM301_10212_0_10119 0 0.00 0.00 0.00 0 2.74 12.19 5.35 4.92E-002 0 No No
353 P_GUESTROOM301_2_0_0 0 0.00 0.00 0.00 0 2.74 12.19 5.35 4.92E-002 0 No No
354 W_GUESTROOM301_4_0_0 0 211.83 59.84 11.58 0 2.74 12.19 5.35 4.92E-002 3 No No
355 W_GUESTROOM301_5_0_0 0 635.46 132.99 11.58 0 2.74 12.19 5.35 4.92E-002 3 No No
356 W_GUESTROOM301_5_0_0_0_0 0 635.46 132.99 11.58 0 2.74 12.19 5.35 4.92E-002 2 No No
357 F_GUESTROOM301_10125_0_10082 0 0.00 0.00 0.00 0 2.74 12.19 5.35 4.92E-002 0 No No
358 C_GUESTROOM301_1_0_0 0 0.00 0.00 0.00 0 2.74 12.19 5.35 4.92E-002 0 No No
359 P_GUESTROOM302_305_10213_0_10120 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
360 P_GUESTROOM302_305_10224_0_10128 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
361 P_GUESTROOM302_305_2_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
362 W_GUESTROOM302_305_5_0_0 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 3 No No
363 W_GUESTROOM302_305_5_0_0_0_0 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
364 W_GUESTROOM302_305_5_0_0_0_1 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
365 W_GUESTROOM302_305_5_0_0_0_2 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
366 W_GUESTROOM302_305_5_0_0_0_3 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
367 F_GUESTROOM302_305_10129_0_10084 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
368 C_GUESTROOM302_305_1_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
369 P_GUESTROOM306_308_10214_0_10121 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
370 P_GUESTROOM306_308_10228_0_10130 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
371 P_GUESTROOM306_308_2_0_0 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
372 W_GUESTROOM306_308_5_0_0 0 635.46 132.99 11.58 0 2.74 12.80 10.02 0.19 3 No No
373 W_GUESTROOM306_308_5_0_0_0_0 0 635.46 132.99 11.58 0 2.74 12.80 10.02 0.19 2 No No
374 W_GUESTROOM306_308_5_0_0_0_1 0 635.46 132.99 11.58 0 2.74 12.80 10.02 0.19 1 No No
375 W_GUESTROOM306_308_5_0_0_0_2 0 635.46 132.99 11.58 0 2.74 12.80 10.02 0.19 2 No No
376 F_GUESTROOM306_308_10136_0_10086 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
377 C_GUESTROOM306_308_1_0_0 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
378 P_GUESTROOM309_312_10215_0_10122 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
379 P_GUESTROOM309_312_10233_0_10132 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
380 P_GUESTROOM309_312_2_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
381 W_GUESTROOM309_312_5_0_0 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 3 No No
382 W_GUESTROOM309_312_5_0_0_0_0 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
383 W_GUESTROOM309_312_5_0_0_0_1 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
384 W_GUESTROOM309_312_5_0_0_0_2 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
385 W_GUESTROOM309_312_5_0_0_0_3 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
386 F_GUESTROOM309_312_10144_0_10088 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
387 C_GUESTROOM309_312_1_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
388 P_GUESTROOM313_10216_0_10123 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
389 P_GUESTROOM313_10221_0_10126 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
390 P_GUESTROOM313_10238_0_10134 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
391 W_GUESTROOM313_5_0_0 0 635.46 132.99 11.58 0 2.74 3.96 5.35 0.15 3 No No
392 W_GUESTROOM313_5_0_0_0_0 0 635.46 132.99 11.58 0 2.74 3.96 5.35 0.15 2 No No
393 F_GUESTROOM313_10149_0_10090 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
394 C_GUESTROOM313_1_0_0 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
395 P_GUESTROOM314_10197_0_10106 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
396 P_GUESTROOM314_10202_0_10109 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
397 W_GUESTROOM314_3_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 3 No No
398 W_GUESTROOM314_3_0_0_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 2 No No
399 P_GUESTROOM314_4_0_0 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
400 F_GUESTROOM314_10154_0_10091 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
401 C_GUESTROOM314_1_0_0 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
402 P_GUESTROOM315_318_10203_0_10110 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
403 P_GUESTROOM315_318_10249_0_10137 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
404 W_GUESTROOM315_318_3_0_0 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 3 No No
405 W_GUESTROOM315_318_3_0_0_0_0 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
406 W_GUESTROOM315_318_3_0_0_0_1 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
407 W_GUESTROOM315_318_3_0_0_0_2 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
408 W_GUESTROOM315_318_3_0_0_0_3 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
409 P_GUESTROOM315_318_4_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
410 F_GUESTROOM315_318_10161_0_10093 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
411 C_GUESTROOM315_318_1_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
412 P_ELEVATORCOREFLR3_10205_0_10112 0 0.00 0.00 0.00 0 2.74 1.83 2.99 0.00 0 No No
413 P_ELEVATORCOREFLR3_10206_0_10113 0 0.00 0.00 0.00 0 2.74 1.83 2.99 0.00 0 No No
414 P_ELEVATORCOREFLR3_2_0_0 0 0.00 0.00 0.00 0 2.74 1.83 2.99 0.00 0 No No
415 W_ELEVATORCOREFLR3_3_0_0 0 635.46 138.95 11.58 0 2.74 1.83 2.99 0.00 0 No No
416 F_ELEVATORCOREFLR3_10166_0_10095 0 0.00 0.00 0.00 0 2.74 1.83 2.99 0.00 0 No No
417 C_ELEVATORCOREFLR3_1_0_0 0 0.00 0.00 0.00 0 2.74 1.83 2.99 0.00 0 No No
418 P_GUESTROOM319_10204_0_10111 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
419 P_GUESTROOM319_10254_0_10139 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
420 P_GUESTROOM319_10258_0_10141 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
421 W_GUESTROOM319_3_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 3 No No
422 W_GUESTROOM319_3_0_0_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 2 No No
423 F_GUESTROOM319_10171_0_10097 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
424 C_GUESTROOM319_1_0_0 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
425 P_GUESTROOM320_323_10207_0_10114 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
426 P_GUESTROOM320_323_10208_0_10115 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
427 W_GUESTROOM320_323_3_0_0 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 3 No No
428 W_GUESTROOM320_323_3_0_0_0_0 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
429 W_GUESTROOM320_323_3_0_0_0_1 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
430 W_GUESTROOM320_323_3_0_0_0_2 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
431 W_GUESTROOM320_323_3_0_0_0_3 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
432 P_GUESTROOM320_323_4_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
433 F_GUESTROOM320_323_10177_0_10098 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
434 C_GUESTROOM320_323_1_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
435 P_GUESTROOM324_10209_0_10116 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
436 P_GUESTROOM324_10269_0_10144 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
437 W_GUESTROOM324_3_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 3 No No
438 W_GUESTROOM324_3_0_0_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 2 No No
439 P_GUESTROOM324_4_0_0 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
440 F_GUESTROOM324_10182_0_10100 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
441 C_GUESTROOM324_1_0_0 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
442 P_FRONTSTORAGEFLR3_10210_0_10117 0 0.00 0.00 0.00 0 2.74 1.52 2.57 0.00 0 No No
443 P_FRONTSTORAGEFLR3_10274_0_10146 0 0.00 0.00 0.00 0 2.74 1.52 2.57 0.00 0 No No
444 W_FRONTSTORAGEFLR3_3_0_0 0 635.46 138.95 11.58 0 2.74 1.52 2.57 0.00 0 No No
445 P_FRONTSTORAGEFLR3_4_0_0 0 0.00 0.00 0.00 0 2.74 1.52 2.57 0.00 0 No No
446 F_FRONTSTORAGEFLR3_10187_0_10102 0 0.00 0.00 0.00 0 2.74 1.52 2.57 0.00 0 No No
447 C_FRONTSTORAGEFLR3_1_0_0 0 0.00 0.00 0.00 0 2.74 1.52 2.57 0.00 0 No No
448 P_FRONTSTAIRSFLR3_10211_0_10118 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
449 P_FRONTSTAIRSFLR3_10279_0_10148 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
450 W_FRONTSTAIRSFLR3_3_0_0 0 635.46 138.95 11.58 0 2.74 10.67 3.76 0.00 0 No No
451 W_FRONTSTAIRSFLR3_4_0_0 0 211.83 59.84 11.58 0 2.74 10.67 3.76 0.00 0 No No
452 F_FRONTSTAIRSFLR3_10192_0_10104 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
453 C_FRONTSTAIRSFLR3_1_0_0 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
454 W_REARSTAIRSFLR4_2_0_0 0 211.83 138.95 11.58 0 2.74 10.67 3.76 0.00 0 No No
455 W_REARSTAIRSFLR4_3_0_0 0 635.46 138.95 11.58 0 2.74 10.67 3.76 0.00 0 No No
456 P_REARSTAIRSFLR4_4_0_0 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
457 P_REARSTAIRSFLR4_5_0_0 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
458 F_REARSTAIRSFLR4_10196_0_10105 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
459 R_REARSTAIRSFLR4_1_0_0 0 1003.40 107.81 0.00 0 2.74 10.67 3.76 0.00 0 No No
460 P_CORRIDORFLR4_10287_0_10151 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
461 W_CORRIDORFLR4_2_0_0 0 211.83 138.95 11.58 0 2.74 6.71 3.86 0.14 3 No No
462 W_CORRIDORFLR4_2_0_0_0_0 0 211.83 138.95 11.58 0 2.74 6.71 3.86 0.14 2 No No
463 P_CORRIDORFLR4_4_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
464 P_CORRIDORFLR4_5_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
465 P_CORRIDORFLR4_6_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
466 P_CORRIDORFLR4_7_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
467 P_CORRIDORFLR4_8_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
468 W_CORRIDORFLR4_9_0_0 0 635.46 138.95 11.58 0 2.74 6.71 3.86 0.14 3 No No
469 P_CORRIDORFLR4_10_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
470 P_CORRIDORFLR4_11_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
471 P_CORRIDORFLR4_12_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
472 P_CORRIDORFLR4_13_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
473 P_CORRIDORFLR4_14_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
474 W_CORRIDORFLR4_15_0_0 0 211.83 59.84 11.58 0 2.74 6.71 3.86 0.14 3 No No
475 W_CORRIDORFLR4_15_0_0_0_0 0 211.83 59.84 11.58 0 2.74 6.71 3.86 0.14 2 No No
476 P_CORRIDORFLR4_16_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
477 P_CORRIDORFLR4_17_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
478 P_CORRIDORFLR4_18_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
479 P_CORRIDORFLR4_19_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
480 P_CORRIDORFLR4_20_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
481 P_CORRIDORFLR4_21_0_0 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
482 F_CORRIDORFLR4_10200_0_10108 0 0.00 0.00 0.00 0 2.74 6.71 3.86 0.14 0 No No
483 R_CORRIDORFLR4_1_0_0 0 1003.40 129.85 0.00 0 2.74 6.71 3.86 0.14 0 No No
484 P_REARSTORAGEFLR4_10305_0_10167 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
485 W_REARSTORAGEFLR4_2_0_0 0 211.83 138.95 11.58 0 2.74 10.67 3.76 0.00 0 No No
486 P_REARSTORAGEFLR4_4_0_0 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
487 W_REARSTORAGEFLR4_5_0_0 0 635.46 132.99 11.58 0 2.74 10.67 3.76 0.00 0 No No
488 F_REARSTORAGEFLR4_10219_0_10125 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
489 R_REARSTORAGEFLR4_1_0_0 0 1003.40 107.81 0.00 0 2.74 10.67 3.76 0.00 0 No No
490 P_GUESTROOM401_10300_0_10162 0 0.00 0.00 0.00 0 2.74 12.19 5.35 4.92E-002 0 No No
491 P_GUESTROOM401_2_0_0 0 0.00 0.00 0.00 0 2.74 12.19 5.35 4.92E-002 0 No No
492 W_GUESTROOM401_4_0_0 0 211.83 59.84 11.58 0 2.74 12.19 5.35 4.92E-002 3 No No
493 W_GUESTROOM401_5_0_0 0 635.46 132.99 11.58 0 2.74 12.19 5.35 4.92E-002 3 No No
494 W_GUESTROOM401_5_0_0_0_0 0 635.46 132.99 11.58 0 2.74 12.19 5.35 4.92E-002 2 No No
495 F_GUESTROOM401_10223_0_10127 0 0.00 0.00 0.00 0 2.74 12.19 5.35 4.92E-002 0 No No
496 R_GUESTROOM401_1_0_0 0 1003.40 107.81 0.00 0 2.74 12.19 5.35 4.92E-002 0 No No
497 P_GUESTROOM402_405_10301_0_10163 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
498 P_GUESTROOM402_405_10310_0_10169 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
499 P_GUESTROOM402_405_2_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
500 W_GUESTROOM402_405_5_0_0 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 3 No No
501 W_GUESTROOM402_405_5_0_0_0_0 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
502 W_GUESTROOM402_405_5_0_0_0_1 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
503 W_GUESTROOM402_405_5_0_0_0_2 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
504 W_GUESTROOM402_405_5_0_0_0_3 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
505 F_GUESTROOM402_405_10227_0_10129 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
506 R_GUESTROOM402_405_1_0_0 0 1003.40 107.81 0.00 0 2.74 15.85 10.83 0.15 0 No No
507 P_GUESTROOM406_408_10302_0_10164 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
508 P_GUESTROOM406_408_10313_0_10170 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
509 P_GUESTROOM406_408_2_0_0 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
510 W_GUESTROOM406_408_5_0_0 0 635.46 132.99 11.58 0 2.74 12.80 10.02 0.19 3 No No
511 W_GUESTROOM406_408_5_0_0_0_0 0 635.46 132.99 11.58 0 2.74 12.80 10.02 0.19 2 No No
512 W_GUESTROOM406_408_5_0_0_0_1 0 635.46 132.99 11.58 0 2.74 12.80 10.02 0.19 2 No No
513 W_GUESTROOM406_408_5_0_0_0_2 0 635.46 132.99 11.58 0 2.74 12.80 10.02 0.19 1 No No
514 F_GUESTROOM406_408_10232_0_10131 0 0.00 0.00 0.00 0 2.74 12.80 10.02 0.19 0 No No
515 R_GUESTROOM406_408_1_0_0 0 1003.40 107.81 0.00 0 2.74 12.80 10.02 0.19 0 No No
516 P_GUESTROOM409_412_10303_0_10165 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
517 P_GUESTROOM409_412_10317_0_10171 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
518 P_GUESTROOM409_412_2_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
519 W_GUESTROOM409_412_5_0_0 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 3 No No
520 W_GUESTROOM409_412_5_0_0_0_0 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
521 W_GUESTROOM409_412_5_0_0_0_1 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
522 W_GUESTROOM409_412_5_0_0_0_2 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
523 W_GUESTROOM409_412_5_0_0_0_3 0 635.46 132.99 11.58 0 2.74 15.85 10.83 0.15 2 No No
524 F_GUESTROOM409_412_10237_0_10133 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
525 R_GUESTROOM409_412_1_0_0 0 1003.40 107.81 0.00 0 2.74 15.85 10.83 0.15 0 No No
526 P_GUESTROOM413_10304_0_10166 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
527 P_GUESTROOM413_10308_0_10168 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
528 P_GUESTROOM413_10321_0_10172 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
529 W_GUESTROOM413_5_0_0 0 635.46 132.99 11.58 0 2.74 3.96 5.35 0.15 3 No No
530 W_GUESTROOM413_5_0_0_0_0 0 635.46 132.99 11.58 0 2.74 3.96 5.35 0.15 2 No No
531 F_GUESTROOM413_10242_0_10135 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
532 R_GUESTROOM413_1_0_0 0 1003.40 107.81 0.00 0 2.74 3.96 5.35 0.15 0 No No
533 P_GUESTROOM414_10286_0_10150 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
534 P_GUESTROOM414_10290_0_10152 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
535 W_GUESTROOM414_3_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 3 No No
536 W_GUESTROOM414_3_0_0_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 2 No No
537 P_GUESTROOM414_4_0_0 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
538 F_GUESTROOM414_10247_0_10136 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
539 R_GUESTROOM414_1_0_0 0 1003.40 107.81 0.00 0 2.74 3.96 5.35 0.15 0 No No
540 P_GUESTROOM415_418_10291_0_10153 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
541 P_GUESTROOM415_418_10330_0_10173 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
542 W_GUESTROOM415_418_3_0_0 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 3 No No
543 W_GUESTROOM415_418_3_0_0_0_0 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
544 W_GUESTROOM415_418_3_0_0_0_1 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
545 W_GUESTROOM415_418_3_0_0_0_2 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
546 W_GUESTROOM415_418_3_0_0_0_3 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
547 P_GUESTROOM415_418_4_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
548 F_GUESTROOM415_418_10252_0_10138 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
549 R_GUESTROOM415_418_1_0_0 0 1003.40 107.81 0.00 0 2.74 15.85 10.83 0.15 0 No No
550 P_ELEVATORCOREFLR4_10293_0_10155 0 0.00 0.00 0.00 0 2.74 1.83 2.99 0.00 0 No No
551 P_ELEVATORCOREFLR4_10294_0_10156 0 0.00 0.00 0.00 0 2.74 1.83 2.99 0.00 0 No No
552 P_ELEVATORCOREFLR4_2_0_0 0 0.00 0.00 0.00 0 2.74 1.83 2.99 0.00 0 No No
553 W_ELEVATORCOREFLR4_3_0_0 0 635.46 138.95 11.58 0 2.74 1.83 2.99 0.00 0 No No
554 F_ELEVATORCOREFLR4_10257_0_10140 0 0.00 0.00 0.00 0 2.74 1.83 2.99 0.00 0 No No
555 R_ELEVATORCOREFLR4_1_0_0 0 1003.40 107.81 0.00 0 2.74 1.83 2.99 0.00 0 No No
556 P_GUESTROOM419_10292_0_10154 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
557 P_GUESTROOM419_10334_0_10174 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
558 P_GUESTROOM419_10337_0_10175 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
559 W_GUESTROOM419_3_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 3 No No
560 W_GUESTROOM419_3_0_0_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 2 No No
561 F_GUESTROOM419_10262_0_10142 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
562 R_GUESTROOM419_1_0_0 0 1003.40 107.81 0.00 0 2.74 3.96 5.35 0.15 0 No No
563 P_GUESTROOM420_423_10295_0_10157 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
564 P_GUESTROOM420_423_10296_0_10158 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
565 W_GUESTROOM420_423_3_0_0 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 3 No No
566 W_GUESTROOM420_423_3_0_0_0_0 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
567 W_GUESTROOM420_423_3_0_0_0_1 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
568 W_GUESTROOM420_423_3_0_0_0_2 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
569 W_GUESTROOM420_423_3_0_0_0_3 0 635.46 138.95 11.58 0 2.74 15.85 10.83 0.15 2 No No
570 P_GUESTROOM420_423_4_0_0 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
571 F_GUESTROOM420_423_10267_0_10143 0 0.00 0.00 0.00 0 2.74 15.85 10.83 0.15 0 No No
572 R_GUESTROOM420_423_1_0_0 0 1003.40 107.81 0.00 0 2.74 15.85 10.83 0.15 0 No No
573 P_GUESTROOM424_10297_0_10159 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
574 P_GUESTROOM424_10346_0_10176 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
575 W_GUESTROOM424_3_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 3 No No
576 W_GUESTROOM424_3_0_0_0_0 0 635.46 138.95 11.58 0 2.74 3.96 5.35 0.15 2 No No
577 P_GUESTROOM424_4_0_0 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
578 F_GUESTROOM424_10272_0_10145 0 0.00 0.00 0.00 0 2.74 3.96 5.35 0.15 0 No No
579 R_GUESTROOM424_1_0_0 0 1003.40 107.81 0.00 0 2.74 3.96 5.35 0.15 0 No No
580 P_FRONTSTORAGEFLR4_10298_0_10160 0 0.00 0.00 0.00 0 2.74 1.52 2.57 0.00 0 No No
581 P_FRONTSTORAGEFLR4_10350_0_10177 0 0.00 0.00 0.00 0 2.74 1.52 2.57 0.00 0 No No
582 W_FRONTSTORAGEFLR4_3_0_0 0 635.46 138.95 11.58 0 2.74 1.52 2.57 0.00 0 No No
583 P_FRONTSTORAGEFLR4_4_0_0 0 0.00 0.00 0.00 0 2.74 1.52 2.57 0.00 0 No No
584 F_FRONTSTORAGEFLR4_10277_0_10147 0 0.00 0.00 0.00 0 2.74 1.52 2.57 0.00 0 No No
585 R_FRONTSTORAGEFLR4_1_0_0 0 1003.40 107.81 0.00 0 2.74 1.52 2.57 0.00 0 No No
586 P_FRONTSTAIRSFLR4_10299_0_10161 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
587 P_FRONTSTAIRSFLR4_10354_0_10178 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
588 W_FRONTSTAIRSFLR4_3_0_0 0 635.46 138.95 11.58 0 2.74 10.67 3.76 0.00 0 No No
589 W_FRONTSTAIRSFLR4_4_0_0 0 211.83 59.84 11.58 0 2.74 10.67 3.76 0.00 0 No No
590 F_FRONTSTAIRSFLR4_10282_0_10149 0 0.00 0.00 0.00 0 2.74 10.67 3.76 0.00 0 No No
591 R_FRONTSTAIRSFLR4_1_0_0 0 1003.40 107.81 0.00 0 2.74 10.67 3.76 0.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 CORRIDORFLR1_INFILTRATION ALWAYSON CORRIDORFLR1 150.51 8.1 4.657E-003 3.094E-005 1.344E-004 3.322E-002 0.000 0.000 0.224 0.000
2 CORRIDORFLR1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH CORRIDORFLR1 150.51 8.1 0.916 6.083E-003 2.642E-002 6.532 1.000 0.000 0.000 0.000
3 CORRIDORFLR2_INFILTRATION ALWAYSON CORRIDORFLR2 125.42 6.8 2.619E-003 2.088E-005 1.424E-004 2.741E-002 0.000 0.000 0.224 0.000
4 CORRIDORFLR3_INFILTRATION ALWAYSON CORRIDORFLR3 125.42 6.8 2.619E-003 2.088E-005 1.424E-004 2.741E-002 0.000 0.000 0.224 0.000
5 CORRIDORFLR4_INFILTRATION ALWAYSON CORRIDORFLR4 125.42 6.8 2.619E-003 2.088E-005 1.821E-005 2.741E-002 0.000 0.000 0.224 0.000
6 ELEVATORCOREFLR1_INFILTRATION ALWAYSON ELEVATORCOREFLR1 15.05 0.2 8.731E-004 5.801E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
7 ELEVATORCOREFLR2_INFILTRATION ALWAYSON ELEVATORCOREFLR2 15.05 0.2 7.144E-004 4.746E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
8 ELEVATORCOREFLR3_INFILTRATION ALWAYSON ELEVATORCOREFLR3 15.05 0.2 7.144E-004 4.746E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
9 ELEVATORCOREFLR4_INFILTRATION ALWAYSON ELEVATORCOREFLR4 15.05 0.2 7.144E-004 4.746E-005 3.560E-005 6.229E-002 0.000 0.000 0.224 0.000
10 EMPLOYEELOUNGEFLR1_INFILTRATION COMMONAREA_INFIL_SCH EMPLOYEELOUNGEFLR1 32.61 18.0 1.892E-003 5.801E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
11 EXERCISECENTERFLR1_INFILTRATION COMMONAREA_INFIL_SCH EXERCISECENTERFLR1 32.61 7.0 1.892E-003 5.801E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
12 FRONTLOUNGEFLR1_INFILTRATION COMMONAREA_INFIL_SCH FRONTLOUNGEFLR1 163.06 53.0 1.339E-002 8.211E-005 1.424E-004 8.816E-002 0.000 0.000 0.224 0.000
13 FRONTOFFICEFLR1_INFILTRATION COMMONAREA_INFIL_SCH FRONTOFFICEFLR1 130.44 10.0 7.567E-003 5.801E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
14 FRONTSTAIRSFLR1_INFILTRATION ALWAYSON FRONTSTAIRSFLR1 20.07 1.1 5.093E-003 2.538E-004 1.350E-004 0.273 0.000 0.000 0.224 0.000
15 FRONTSTAIRSFLR2_INFILTRATION ALWAYSON FRONTSTAIRSFLR2 20.07 1.1 4.167E-003 2.077E-004 1.424E-004 0.273 0.000 0.000 0.224 0.000
16 FRONTSTAIRSFLR3_INFILTRATION ALWAYSON FRONTSTAIRSFLR3 20.07 1.1 4.167E-003 2.077E-004 1.424E-004 0.273 0.000 0.000 0.224 0.000
17 FRONTSTAIRSFLR4_INFILTRATION ALWAYSON FRONTSTAIRSFLR4 20.07 1.1 4.167E-003 2.077E-004 8.447E-005 0.273 0.000 0.000 0.224 0.000
18 FRONTSTORAGEFLR1_INFILTRATION ALWAYSON FRONTSTORAGEFLR1 12.54 0.3 7.276E-004 5.801E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
19 FRONTSTORAGEFLR2_INFILTRATION ALWAYSON FRONTSTORAGEFLR2 12.54 0.3 5.953E-004 4.746E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
20 FRONTSTORAGEFLR3_INFILTRATION ALWAYSON FRONTSTORAGEFLR3 12.54 0.3 5.953E-004 4.746E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
21 FRONTSTORAGEFLR4_INFILTRATION ALWAYSON FRONTSTORAGEFLR4 12.54 0.3 5.953E-004 4.746E-005 3.560E-005 6.229E-002 0.000 0.000 0.224 0.000
22 GUESTROOM101_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM101 32.61 1.5 1.892E-003 5.801E-005 1.424E-004 6.228E-002 0.000 0.000 0.224 0.000
23 GUESTROOM102_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM102 32.61 1.5 1.892E-003 5.801E-005 1.424E-004 6.228E-002 0.000 0.000 0.224 0.000
24 GUESTROOM103_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM103 32.61 1.5 1.892E-003 5.801E-005 1.424E-004 6.228E-002 0.000 0.000 0.224 0.000
25 GUESTROOM104_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM104 32.61 1.5 1.892E-003 5.801E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
26 GUESTROOM105_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM105 32.61 1.5 1.892E-003 5.801E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
27 GUESTROOM201_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM201 32.61 1.5 4.763E-003 1.460E-004 1.424E-004 0.192 0.000 0.000 0.224 0.000
28 GUESTROOM202_205_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM202_205 130.45 6.0 6.191E-003 4.746E-005 1.424E-004 6.228E-002 0.000 0.000 0.224 0.000
29 GUESTROOM206_208_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM206_208 105.36 4.5 5.000E-003 4.746E-005 1.424E-004 6.228E-002 0.000 0.000 0.224 0.000
30 GUESTROOM209_212_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM209_212 130.45 6.0 6.191E-003 4.746E-005 1.424E-004 6.228E-002 0.000 0.000 0.224 0.000
31 GUESTROOM213_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM213 32.61 1.5 1.548E-003 4.746E-005 1.424E-004 6.228E-002 0.000 0.000 0.224 0.000
32 GUESTROOM214_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM214 32.61 1.5 1.548E-003 4.746E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
33 GUESTROOM215_218_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM215_218 130.44 6.0 6.191E-003 4.746E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
34 GUESTROOM219_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM219 32.61 1.5 1.548E-003 4.746E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
35 GUESTROOM220_223_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM220_223 130.44 6.0 6.191E-003 4.746E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
36 GUESTROOM224_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM224 32.61 1.5 1.548E-003 4.746E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
37 GUESTROOM301_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM301 32.61 1.5 4.763E-003 1.460E-004 1.424E-004 0.192 0.000 0.000 0.224 0.000
38 GUESTROOM302_305_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM302_305 130.45 6.0 6.191E-003 4.746E-005 1.424E-004 6.228E-002 0.000 0.000 0.224 0.000
39 GUESTROOM306_308_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM306_308 105.36 4.5 5.000E-003 4.746E-005 1.424E-004 6.228E-002 0.000 0.000 0.224 0.000
40 GUESTROOM309_312_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM309_312 130.45 6.0 6.191E-003 4.746E-005 1.424E-004 6.228E-002 0.000 0.000 0.224 0.000
41 GUESTROOM313_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM313 32.61 1.5 1.548E-003 4.746E-005 1.424E-004 6.228E-002 0.000 0.000 0.224 0.000
42 GUESTROOM314_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM314 32.61 1.5 1.548E-003 4.746E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
43 GUESTROOM315_318_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM315_318 130.44 6.0 6.191E-003 4.746E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
44 GUESTROOM319_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM319 32.61 1.5 1.548E-003 4.746E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
45 GUESTROOM320_323_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM320_323 130.44 6.0 6.191E-003 4.746E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
46 GUESTROOM324_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM324 32.61 1.5 1.548E-003 4.746E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
47 GUESTROOM401_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM401 32.61 1.5 4.763E-003 1.460E-004 7.210E-005 0.192 0.000 0.000 0.224 0.000
48 GUESTROOM402_405_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM402_405 130.45 6.0 6.191E-003 4.746E-005 3.560E-005 6.228E-002 0.000 0.000 0.224 0.000
49 GUESTROOM406_408_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM406_408 105.36 4.5 5.000E-003 4.746E-005 3.560E-005 6.228E-002 0.000 0.000 0.224 0.000
50 GUESTROOM409_412_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM409_412 130.45 6.0 6.191E-003 4.746E-005 3.560E-005 6.228E-002 0.000 0.000 0.224 0.000
51 GUESTROOM413_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM413 32.61 1.5 1.548E-003 4.746E-005 3.560E-005 6.228E-002 0.000 0.000 0.224 0.000
52 GUESTROOM414_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM414 32.61 1.5 1.548E-003 4.746E-005 3.560E-005 6.229E-002 0.000 0.000 0.224 0.000
53 GUESTROOM415_418_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM415_418 130.44 6.0 6.191E-003 4.746E-005 3.560E-005 6.229E-002 0.000 0.000 0.224 0.000
54 GUESTROOM419_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM419 32.61 1.5 1.548E-003 4.746E-005 3.560E-005 6.229E-002 0.000 0.000 0.224 0.000
55 GUESTROOM420_423_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM420_423 130.44 6.0 6.191E-003 4.746E-005 3.560E-005 6.229E-002 0.000 0.000 0.224 0.000
56 GUESTROOM424_INFILTRATION GUESTROOM_INFIL_SCH GUESTROOM424 32.61 1.5 1.548E-003 4.746E-005 3.560E-005 6.229E-002 0.000 0.000 0.224 0.000
57 LAUNDRYROOMFLR1_INFILTRATION GUESTROOM_INFIL_SCH LAUNDRYROOMFLR1 97.83 10.5 5.675E-003 5.801E-005 1.424E-004 6.229E-002 0.000 0.000 0.224 0.000
58 MECHANICALROOMFLR1_INFILTRATION GUESTROOM_INFIL_SCH MECHANICALROOMFLR1 32.61 0.5 1.892E-003 5.801E-005 1.424E-004 6.228E-002 0.000 0.000 0.224 0.000
59 MEETINGROOMFLR1_INFILTRATION GUESTROOM_INFIL_SCH MEETINGROOMFLR1 80.27 43.0 4.657E-003 5.801E-005 1.424E-004 6.228E-002 0.000 0.000 0.224 0.000
60 REARSTAIRSFLR1_INFILTRATION ALWAYSON REARSTAIRSFLR1 20.07 1.1 5.093E-003 2.538E-004 1.350E-004 0.272 0.000 0.000 0.224 0.000
61 REARSTAIRSFLR2_INFILTRATION ALWAYSON REARSTAIRSFLR2 20.07 1.1 4.167E-003 2.076E-004 1.424E-004 0.272 0.000 0.000 0.224 0.000
62 REARSTAIRSFLR3_INFILTRATION ALWAYSON REARSTAIRSFLR3 20.07 1.1 4.167E-003 2.076E-004 1.424E-004 0.272 0.000 0.000 0.224 0.000
63 REARSTAIRSFLR4_INFILTRATION ALWAYSON REARSTAIRSFLR4 20.07 1.1 4.167E-003 2.076E-004 8.446E-005 0.272 0.000 0.000 0.224 0.000
64 REARSTORAGEFLR1_INFILTRATION ALWAYSON REARSTORAGEFLR1 20.07 0.4 5.094E-003 2.538E-004 1.424E-004 0.272 0.000 0.000 0.224 0.000
65 REARSTORAGEFLR2_INFILTRATION ALWAYSON REARSTORAGEFLR2 20.07 0.4 4.168E-003 2.076E-004 1.424E-004 0.272 0.000 0.000 0.224 0.000
66 REARSTORAGEFLR3_INFILTRATION ALWAYSON REARSTORAGEFLR3 20.07 0.4 4.168E-003 2.076E-004 1.424E-004 0.272 0.000 0.000 0.224 0.000
67 REARSTORAGEFLR4_INFILTRATION ALWAYSON REARSTORAGEFLR4 20.07 0.4 4.168E-003 2.076E-004 8.446E-005 0.272 0.000 0.000 0.224 0.000
68 RESTROOMFLR1_INFILTRATION COMMONAREA_INFIL_SCH RESTROOMFLR1 32.61 1.8 1.892E-003 5.801E-005 1.424E-004 6.228E-002 0.000 0.000 0.224 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 GUESTROOM103 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM103 32.61 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 GUESTROOM104 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM104 32.61 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 GUESTROOM105 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM105 32.61 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 GUESTROOM202_205 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM202_205 130.45 6.0 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 GUESTROOM206_208 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM206_208 105.36 4.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 GUESTROOM209_212 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM209_212 130.45 6.0 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 GUESTROOM213 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM213 32.61 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 GUESTROOM214 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM214 32.61 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 GUESTROOM219 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM219 32.61 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
10 GUESTROOM220_223 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM220_223 130.44 6.0 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
11 GUESTROOM224 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM224 32.61 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
12 GUESTROOM309_312 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM309_312 130.45 6.0 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
13 GUESTROOM314 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM314 32.61 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
14 GUESTROOM315_318 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM315_318 130.44 6.0 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
15 GUESTROOM320_323 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM320_323 130.44 6.0 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
16 GUESTROOM401 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM401 32.61 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
17 GUESTROOM409_412 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM409_412 130.45 6.0 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
18 GUESTROOM415_418 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM415_418 130.44 6.0 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
19 GUESTROOM419 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM419 32.61 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
20 GUESTROOM420_423 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM420_423 130.44 6.0 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
21 GUESTROOM424 SLIDING DOOR VENTILATION Constant-0.0 GUESTROOM424 32.61 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 REARSTAIRSFLR1 Mixing/Well-Stirred
2 CORRIDORFLR1 Mixing/Well-Stirred
3 REARSTORAGEFLR1 Mixing/Well-Stirred
4 FRONTLOUNGEFLR1 Mixing/Well-Stirred
5 RESTROOMFLR1 Mixing/Well-Stirred
6 MEETINGROOMFLR1 Mixing/Well-Stirred
7 MECHANICALROOMFLR1 Mixing/Well-Stirred
8 GUESTROOM101 Mixing/Well-Stirred
9 GUESTROOM102 Mixing/Well-Stirred
10 GUESTROOM103 Mixing/Well-Stirred
11 GUESTROOM104 Mixing/Well-Stirred
12 GUESTROOM105 Mixing/Well-Stirred
13 EMPLOYEELOUNGEFLR1 Mixing/Well-Stirred
14 LAUNDRYROOMFLR1 Mixing/Well-Stirred
15 ELEVATORCOREFLR1 Mixing/Well-Stirred
16 EXERCISECENTERFLR1 Mixing/Well-Stirred
17 FRONTOFFICEFLR1 Mixing/Well-Stirred
18 FRONTSTAIRSFLR1 Mixing/Well-Stirred
19 FRONTSTORAGEFLR1 Mixing/Well-Stirred
20 REARSTAIRSFLR2 Mixing/Well-Stirred
21 CORRIDORFLR2 Mixing/Well-Stirred
22 REARSTORAGEFLR2 Mixing/Well-Stirred
23 GUESTROOM201 Mixing/Well-Stirred
24 GUESTROOM202_205 Mixing/Well-Stirred
25 GUESTROOM206_208 Mixing/Well-Stirred
26 GUESTROOM209_212 Mixing/Well-Stirred
27 GUESTROOM213 Mixing/Well-Stirred
28 GUESTROOM214 Mixing/Well-Stirred
29 GUESTROOM215_218 Mixing/Well-Stirred
30 ELEVATORCOREFLR2 Mixing/Well-Stirred
31 GUESTROOM219 Mixing/Well-Stirred
32 GUESTROOM220_223 Mixing/Well-Stirred
33 GUESTROOM224 Mixing/Well-Stirred
34 FRONTSTORAGEFLR2 Mixing/Well-Stirred
35 FRONTSTAIRSFLR2 Mixing/Well-Stirred
36 REARSTAIRSFLR3 Mixing/Well-Stirred
37 CORRIDORFLR3 Mixing/Well-Stirred
38 REARSTORAGEFLR3 Mixing/Well-Stirred
39 GUESTROOM301 Mixing/Well-Stirred
40 GUESTROOM302_305 Mixing/Well-Stirred
41 GUESTROOM306_308 Mixing/Well-Stirred
42 GUESTROOM309_312 Mixing/Well-Stirred
43 GUESTROOM313 Mixing/Well-Stirred
44 GUESTROOM314 Mixing/Well-Stirred
45 GUESTROOM315_318 Mixing/Well-Stirred
46 ELEVATORCOREFLR3 Mixing/Well-Stirred
47 GUESTROOM319 Mixing/Well-Stirred
48 GUESTROOM320_323 Mixing/Well-Stirred
49 GUESTROOM324 Mixing/Well-Stirred
50 FRONTSTORAGEFLR3 Mixing/Well-Stirred
51 FRONTSTAIRSFLR3 Mixing/Well-Stirred
52 REARSTAIRSFLR4 Mixing/Well-Stirred
53 CORRIDORFLR4 Mixing/Well-Stirred
54 REARSTORAGEFLR4 Mixing/Well-Stirred
55 GUESTROOM401 Mixing/Well-Stirred
56 GUESTROOM402_405 Mixing/Well-Stirred
57 GUESTROOM406_408 Mixing/Well-Stirred
58 GUESTROOM409_412 Mixing/Well-Stirred
59 GUESTROOM413 Mixing/Well-Stirred
60 GUESTROOM414 Mixing/Well-Stirred
61 GUESTROOM415_418 Mixing/Well-Stirred
62 ELEVATORCOREFLR4 Mixing/Well-Stirred
63 GUESTROOM419 Mixing/Well-Stirred
64 GUESTROOM420_423 Mixing/Well-Stirred
65 GUESTROOM424 Mixing/Well-Stirred
66 FRONTSTORAGEFLR4 Mixing/Well-Stirred
67 FRONTSTAIRSFLR4 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone REARSTAIRSFLR1 1.2000
3 Zone CORRIDORFLR1 1.2000
4 Zone FRONTLOUNGEFLR1 1.2000
5 Zone RESTROOMFLR1 1.2000
6 Zone MEETINGROOMFLR1 1.2000
7 Zone MECHANICALROOMFLR1 1.2000
8 Zone GUESTROOM101 1.2000
9 Zone GUESTROOM102 1.2000
10 Zone GUESTROOM103 1.2000
11 Zone GUESTROOM104 1.2000
12 Zone GUESTROOM105 1.2000
13 Zone EMPLOYEELOUNGEFLR1 1.2000
14 Zone EXERCISECENTERFLR1 1.2000
15 Zone FRONTOFFICEFLR1 1.2000
16 Zone FRONTSTAIRSFLR1 1.2000
17 Zone REARSTAIRSFLR2 1.2000
18 Zone CORRIDORFLR2 1.2000
19 Zone GUESTROOM201 1.2000
20 Zone GUESTROOM202_205 1.2000
21 Zone GUESTROOM206_208 1.2000
22 Zone GUESTROOM209_212 1.2000
23 Zone GUESTROOM213 1.2000
24 Zone GUESTROOM214 1.2000
25 Zone GUESTROOM215_218 1.2000
26 Zone GUESTROOM219 1.2000
27 Zone GUESTROOM220_223 1.2000
28 Zone GUESTROOM224 1.2000
29 Zone FRONTSTAIRSFLR2 1.2000
30 Zone REARSTAIRSFLR3 1.2000
31 Zone CORRIDORFLR3 1.2000
32 Zone GUESTROOM301 1.2000
33 Zone GUESTROOM302_305 1.2000
34 Zone GUESTROOM306_308 1.2000
35 Zone GUESTROOM309_312 1.2000
36 Zone GUESTROOM313 1.2000
37 Zone GUESTROOM314 1.2000
38 Zone GUESTROOM315_318 1.2000
39 Zone GUESTROOM319 1.2000
40 Zone GUESTROOM320_323 1.2000
41 Zone GUESTROOM324 1.2000
42 Zone FRONTSTAIRSFLR3 1.2000
43 Zone REARSTAIRSFLR4 1.2000
44 Zone CORRIDORFLR4 1.2000
45 Zone GUESTROOM401 1.2000
46 Zone GUESTROOM402_405 1.2000
47 Zone GUESTROOM406_408 1.2000
48 Zone GUESTROOM409_412 1.2000
49 Zone GUESTROOM413 1.2000
50 Zone GUESTROOM414 1.2000
51 Zone GUESTROOM415_418 1.2000
52 Zone GUESTROOM419 1.2000
53 Zone GUESTROOM420_423 1.2000
54 Zone GUESTROOM424 1.2000
55 Zone FRONTSTAIRSFLR4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone REARSTAIRSFLR1 1.2000
3 Zone CORRIDORFLR1 1.2000
4 Zone FRONTLOUNGEFLR1 1.2000
5 Zone RESTROOMFLR1 1.2000
6 Zone MEETINGROOMFLR1 1.2000
7 Zone MECHANICALROOMFLR1 1.2000
8 Zone GUESTROOM101 1.2000
9 Zone GUESTROOM102 1.2000
10 Zone GUESTROOM103 1.2000
11 Zone GUESTROOM104 1.2000
12 Zone GUESTROOM105 1.2000
13 Zone EMPLOYEELOUNGEFLR1 1.2000
14 Zone EXERCISECENTERFLR1 1.2000
15 Zone FRONTOFFICEFLR1 1.2000
16 Zone FRONTSTAIRSFLR1 1.2000
17 Zone REARSTAIRSFLR2 1.2000
18 Zone CORRIDORFLR2 1.2000
19 Zone GUESTROOM201 1.2000
20 Zone GUESTROOM202_205 1.2000
21 Zone GUESTROOM206_208 1.2000
22 Zone GUESTROOM209_212 1.2000
23 Zone GUESTROOM213 1.2000
24 Zone GUESTROOM214 1.2000
25 Zone GUESTROOM215_218 1.2000
26 Zone GUESTROOM219 1.2000
27 Zone GUESTROOM220_223 1.2000
28 Zone GUESTROOM224 1.2000
29 Zone FRONTSTAIRSFLR2 1.2000
30 Zone REARSTAIRSFLR3 1.2000
31 Zone CORRIDORFLR3 1.2000
32 Zone GUESTROOM301 1.2000
33 Zone GUESTROOM302_305 1.2000
34 Zone GUESTROOM306_308 1.2000
35 Zone GUESTROOM309_312 1.2000
36 Zone GUESTROOM313 1.2000
37 Zone GUESTROOM314 1.2000
38 Zone GUESTROOM315_318 1.2000
39 Zone GUESTROOM319 1.2000
40 Zone GUESTROOM320_323 1.2000
41 Zone GUESTROOM324 1.2000
42 Zone FRONTSTAIRSFLR3 1.2000
43 Zone REARSTAIRSFLR4 1.2000
44 Zone CORRIDORFLR4 1.2000
45 Zone GUESTROOM401 1.2000
46 Zone GUESTROOM402_405 1.2000
47 Zone GUESTROOM406_408 1.2000
48 Zone GUESTROOM409_412 1.2000
49 Zone GUESTROOM413 1.2000
50 Zone GUESTROOM414 1.2000
51 Zone GUESTROOM415_418 1.2000
52 Zone GUESTROOM419 1.2000
53 Zone GUESTROOM420_423 1.2000
54 Zone GUESTROOM424 1.2000
55 Zone FRONTSTAIRSFLR4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_0 FRONTLOUNGEFLR1_DAYLREFPT1 6.2113E-004
2 Clear Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_0 FRONTLOUNGEFLR1_DAYLREFPT2 7.3293E-004
3 Clear Turbid Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_0 FRONTLOUNGEFLR1_DAYLREFPT1 5.5549E-004
4 Clear Turbid Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_0 FRONTLOUNGEFLR1_DAYLREFPT2 6.3684E-004
5 Intermediate Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_0 FRONTLOUNGEFLR1_DAYLREFPT1 5.2800E-004
6 Intermediate Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_0 FRONTLOUNGEFLR1_DAYLREFPT2 5.6064E-004
7 Overcast Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_0 FRONTLOUNGEFLR1_DAYLREFPT1 4.6849E-004
8 Overcast Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_0 FRONTLOUNGEFLR1_DAYLREFPT2 5.1087E-004
9 Clear Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_1 FRONTLOUNGEFLR1_DAYLREFPT1 1.5628E-003
10 Clear Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_1 FRONTLOUNGEFLR1_DAYLREFPT2 2.0306E-003
11 Clear Turbid Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_1 FRONTLOUNGEFLR1_DAYLREFPT1 1.2490E-003
12 Clear Turbid Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_1 FRONTLOUNGEFLR1_DAYLREFPT2 1.6085E-003
13 Intermediate Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_1 FRONTLOUNGEFLR1_DAYLREFPT1 9.2611E-004
14 Intermediate Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_1 FRONTLOUNGEFLR1_DAYLREFPT2 1.1505E-003
15 Overcast Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_1 FRONTLOUNGEFLR1_DAYLREFPT1 1.0554E-003
16 Overcast Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_1 FRONTLOUNGEFLR1_DAYLREFPT2 1.2447E-003
17 Clear Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_2 FRONTLOUNGEFLR1_DAYLREFPT1 2.4155E-002
18 Clear Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_2 FRONTLOUNGEFLR1_DAYLREFPT2 7.3796E-003
19 Clear Turbid Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_2 FRONTLOUNGEFLR1_DAYLREFPT1 2.0702E-002
20 Clear Turbid Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_2 FRONTLOUNGEFLR1_DAYLREFPT2 6.2059E-003
21 Intermediate Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_2 FRONTLOUNGEFLR1_DAYLREFPT1 2.8891E-002
22 Intermediate Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_2 FRONTLOUNGEFLR1_DAYLREFPT2 7.1067E-003
23 Overcast Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_2 FRONTLOUNGEFLR1_DAYLREFPT1 2.7064E-002
24 Overcast Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_2 FRONTLOUNGEFLR1_DAYLREFPT2 5.7013E-003
25 Clear Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_3 FRONTLOUNGEFLR1_DAYLREFPT1 3.4363E-003
26 Clear Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_3 FRONTLOUNGEFLR1_DAYLREFPT2 3.2878E-003
27 Clear Turbid Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_3 FRONTLOUNGEFLR1_DAYLREFPT1 3.6620E-003
28 Clear Turbid Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_3 FRONTLOUNGEFLR1_DAYLREFPT2 3.2381E-003
29 Intermediate Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_3 FRONTLOUNGEFLR1_DAYLREFPT1 2.2669E-003
30 Intermediate Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_3 FRONTLOUNGEFLR1_DAYLREFPT2 2.4722E-003
31 Overcast Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_3 FRONTLOUNGEFLR1_DAYLREFPT1 1.0554E-003
32 Overcast Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_3 FRONTLOUNGEFLR1_DAYLREFPT2 1.2409E-003
33 Clear Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_4 FRONTLOUNGEFLR1_DAYLREFPT1 7.3689E-004
34 Clear Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_4 FRONTLOUNGEFLR1_DAYLREFPT2 9.7986E-004
35 Clear Turbid Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_4 FRONTLOUNGEFLR1_DAYLREFPT1 7.0671E-004
36 Clear Turbid Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_4 FRONTLOUNGEFLR1_DAYLREFPT2 9.6085E-004
37 Intermediate Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_4 FRONTLOUNGEFLR1_DAYLREFPT1 5.8307E-004
38 Intermediate Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_4 FRONTLOUNGEFLR1_DAYLREFPT2 7.1261E-004
39 Overcast Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_4 FRONTLOUNGEFLR1_DAYLREFPT1 4.6849E-004
40 Overcast Sky 01/21 FRONTLOUNGEFLR1_DAYLCTRL FRONTLOUNGEFLR1 W_FRONTLOUNGEFLR1_5_0_0_0_4 FRONTLOUNGEFLR1_DAYLREFPT2 5.1063E-004
41 Clear Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_0 MEETINGROOMFLR1_DAYLREFPT1 2.0772E-003
42 Clear Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_0 MEETINGROOMFLR1_DAYLREFPT2 2.2473E-003
43 Clear Turbid Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_0 MEETINGROOMFLR1_DAYLREFPT1 1.6637E-003
44 Clear Turbid Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_0 MEETINGROOMFLR1_DAYLREFPT2 1.8112E-003
45 Intermediate Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_0 MEETINGROOMFLR1_DAYLREFPT1 1.4459E-003
46 Intermediate Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_0 MEETINGROOMFLR1_DAYLREFPT2 1.5759E-003
47 Overcast Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_0 MEETINGROOMFLR1_DAYLREFPT1 1.8517E-003
48 Overcast Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_0 MEETINGROOMFLR1_DAYLREFPT2 1.7621E-003
49 Clear Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_1 MEETINGROOMFLR1_DAYLREFPT1 4.6270E-003
50 Clear Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_1 MEETINGROOMFLR1_DAYLREFPT2 3.4062E-003
51 Clear Turbid Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_1 MEETINGROOMFLR1_DAYLREFPT1 4.8875E-003
52 Clear Turbid Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_1 MEETINGROOMFLR1_DAYLREFPT2 3.2681E-003
53 Intermediate Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_1 MEETINGROOMFLR1_DAYLREFPT1 3.8284E-003
54 Intermediate Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_1 MEETINGROOMFLR1_DAYLREFPT2 3.1680E-003
55 Overcast Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_1 MEETINGROOMFLR1_DAYLREFPT1 1.8472E-003
56 Overcast Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_1 MEETINGROOMFLR1_DAYLREFPT2 1.7598E-003
57 Clear Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_2 MEETINGROOMFLR1_DAYLREFPT1 1.2664E-002
58 Clear Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_2 MEETINGROOMFLR1_DAYLREFPT2 4.8020E-003
59 Clear Turbid Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_2 MEETINGROOMFLR1_DAYLREFPT1 1.0902E-002
60 Clear Turbid Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_2 MEETINGROOMFLR1_DAYLREFPT2 4.0766E-003
61 Intermediate Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_2 MEETINGROOMFLR1_DAYLREFPT1 1.7894E-002
62 Intermediate Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_2 MEETINGROOMFLR1_DAYLREFPT2 5.3566E-003
63 Overcast Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_2 MEETINGROOMFLR1_DAYLREFPT1 1.9160E-002
64 Overcast Sky 01/21 MEETINGROOMFLR1_DAYLCTRL MEETINGROOMFLR1 W_MEETINGROOMFLR1_5_0_0_0_2 MEETINGROOMFLR1_DAYLREFPT2 4.6539E-003
65 Clear Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_0 FRONTOFFICEFLR1_DAYLREFPT1 1.0190E-003
66 Clear Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_0 FRONTOFFICEFLR1_DAYLREFPT2 1.4949E-003
67 Clear Turbid Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_0 FRONTOFFICEFLR1_DAYLREFPT1 1.0927E-003
68 Clear Turbid Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_0 FRONTOFFICEFLR1_DAYLREFPT2 1.5968E-003
69 Intermediate Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_0 FRONTOFFICEFLR1_DAYLREFPT1 6.4118E-004
70 Intermediate Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_0 FRONTOFFICEFLR1_DAYLREFPT2 9.2624E-004
71 Overcast Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_0 FRONTOFFICEFLR1_DAYLREFPT1 3.9107E-004
72 Overcast Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_0 FRONTOFFICEFLR1_DAYLREFPT2 4.8600E-004
73 Clear Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_1 FRONTOFFICEFLR1_DAYLREFPT1 1.0701E-002
74 Clear Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_1 FRONTOFFICEFLR1_DAYLREFPT2 5.0835E-003
75 Clear Turbid Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_1 FRONTOFFICEFLR1_DAYLREFPT1 1.1587E-002
76 Clear Turbid Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_1 FRONTOFFICEFLR1_DAYLREFPT2 4.9728E-003
77 Intermediate Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_1 FRONTOFFICEFLR1_DAYLREFPT1 9.5275E-003
78 Intermediate Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_1 FRONTOFFICEFLR1_DAYLREFPT2 4.9685E-003
79 Overcast Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_1 FRONTOFFICEFLR1_DAYLREFPT1 4.3875E-003
80 Overcast Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_1 FRONTOFFICEFLR1_DAYLREFPT2 2.5764E-003
81 Clear Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_2 FRONTOFFICEFLR1_DAYLREFPT1 3.6927E-003
82 Clear Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_2 FRONTOFFICEFLR1_DAYLREFPT2 2.8687E-003
83 Clear Turbid Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_2 FRONTOFFICEFLR1_DAYLREFPT1 2.9603E-003
84 Clear Turbid Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_2 FRONTOFFICEFLR1_DAYLREFPT2 2.3598E-003
85 Intermediate Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_2 FRONTOFFICEFLR1_DAYLREFPT1 3.2670E-003
86 Intermediate Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_2 FRONTOFFICEFLR1_DAYLREFPT2 2.5371E-003
87 Overcast Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_2 FRONTOFFICEFLR1_DAYLREFPT1 4.3734E-003
88 Overcast Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_2 FRONTOFFICEFLR1_DAYLREFPT2 2.5726E-003
89 Clear Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_3 FRONTOFFICEFLR1_DAYLREFPT1 5.8552E-004
90 Clear Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_3 FRONTOFFICEFLR1_DAYLREFPT2 7.6555E-004
91 Clear Turbid Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_3 FRONTOFFICEFLR1_DAYLREFPT1 5.3200E-004
92 Clear Turbid Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_3 FRONTOFFICEFLR1_DAYLREFPT2 6.6713E-004
93 Intermediate Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_3 FRONTOFFICEFLR1_DAYLREFPT1 4.6197E-004
94 Intermediate Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_3 FRONTOFFICEFLR1_DAYLREFPT2 5.4221E-004
95 Overcast Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_3 FRONTOFFICEFLR1_DAYLREFPT1 3.9092E-004
96 Overcast Sky 01/21 FRONTOFFICEFLR1_DAYLCTRL FRONTOFFICEFLR1 W_FRONTOFFICEFLR1_3_0_0_0_3 FRONTOFFICEFLR1_DAYLREFPT2 4.8571E-004
97 Clear Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_0 LAUNDRYROOMFLR1_DAYLREFPT1 3.0973E-003
98 Clear Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_0 LAUNDRYROOMFLR1_DAYLREFPT2 3.1260E-003
99 Clear Turbid Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_0 LAUNDRYROOMFLR1_DAYLREFPT1 3.4838E-003
100 Clear Turbid Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_0 LAUNDRYROOMFLR1_DAYLREFPT2 3.2891E-003
101 Intermediate Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_0 LAUNDRYROOMFLR1_DAYLREFPT1 1.8285E-003
102 Intermediate Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_0 LAUNDRYROOMFLR1_DAYLREFPT2 2.2124E-003
103 Overcast Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_0 LAUNDRYROOMFLR1_DAYLREFPT1 8.2747E-004
104 Overcast Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_0 LAUNDRYROOMFLR1_DAYLREFPT2 1.0355E-003
105 Clear Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_1 LAUNDRYROOMFLR1_DAYLREFPT1 1.3946E-002
106 Clear Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_1 LAUNDRYROOMFLR1_DAYLREFPT2 5.2854E-003
107 Clear Turbid Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_1 LAUNDRYROOMFLR1_DAYLREFPT1 1.2392E-002
108 Clear Turbid Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_1 LAUNDRYROOMFLR1_DAYLREFPT2 4.6271E-003
109 Intermediate Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_1 LAUNDRYROOMFLR1_DAYLREFPT1 2.0127E-002
110 Intermediate Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_1 LAUNDRYROOMFLR1_DAYLREFPT2 6.1812E-003
111 Overcast Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_1 LAUNDRYROOMFLR1_DAYLREFPT1 1.9073E-002
112 Overcast Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_1 LAUNDRYROOMFLR1_DAYLREFPT2 4.7389E-003
113 Clear Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_2 LAUNDRYROOMFLR1_DAYLREFPT1 1.1426E-003
114 Clear Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_2 LAUNDRYROOMFLR1_DAYLREFPT2 1.4919E-003
115 Clear Turbid Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_2 LAUNDRYROOMFLR1_DAYLREFPT1 9.7965E-004
116 Clear Turbid Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_2 LAUNDRYROOMFLR1_DAYLREFPT2 1.2534E-003
117 Intermediate Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_2 LAUNDRYROOMFLR1_DAYLREFPT1 8.2193E-004
118 Intermediate Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_2 LAUNDRYROOMFLR1_DAYLREFPT2 1.0477E-003
119 Overcast Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_2 LAUNDRYROOMFLR1_DAYLREFPT1 8.2625E-004
120 Overcast Sky 01/21 LAUNDRYROOMFLR1_DAYLCTRL LAUNDRYROOMFLR1 W_LAUNDRYROOMFLR1_3_0_0_0_2 LAUNDRYROOMFLR1_DAYLREFPT2 1.0343E-003


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 REARSTAIRSFLR1 Cooling 0.00000 0.00000 0.00000 6.11790E-003 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 30.88200 1.53645E-002 20.07186 1.08000 6.11790E-003 0.00000
2 REARSTAIRSFLR1 Heating 0.00000 0.00000 0.00000 6.11790E-003 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -26.20000 3.61342E-004 20.07186 1.08000 6.11790E-003 0.00000
3 CORRIDORFLR1 Cooling 20944.12171 25132.94606 1.81070 2.17284 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.65600 1.53604E-002 150.50577 8.10000 4.58742E-002 0.00000
4 CORRIDORFLR1 Heating 61582.82570 73899.39084 1.81655 2.17985 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 150.50577 8.10000 4.58742E-002 0.00000
5 FRONTLOUNGEFLR1 Cooling 9895.89080 11875.06896 0.85511 1.02614 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.65600 1.53604E-002 163.05641 53.00000 0.23730 0.00000
6 FRONTLOUNGEFLR1 Heating 2919.49604 3503.39524 8.62859E-002 0.23730 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:40:00 -26.20000 3.61342E-004 163.05641 53.00000 0.23730 0.00000
7 RESTROOMFLR1 Cooling 799.24383 959.09259 6.90167E-002 8.28201E-002 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 27.33100 1.53579E-002 32.61128 1.75500 0.00000 0.00000
8 RESTROOMFLR1 Heating 403.17550 483.81060 1.19159E-002 1.42991E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 -26.20000 3.61342E-004 32.61128 1.75500 0.00000 0.00000
9 MEETINGROOMFLR1 Cooling 4446.86367 5336.23640 0.38445 0.46133 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.65600 1.53604E-002 80.27392 43.00000 0.12594 0.00000
10 MEETINGROOMFLR1 Heating 1040.96963 1249.16356 3.07661E-002 0.12594 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:00:00 -26.20000 3.61342E-004 80.27392 43.00000 0.12594 0.00000
11 GUESTROOM101 Cooling 831.95006 998.34007 9.98943E-002 0.11987 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 28.39100 1.53599E-002 32.61128 1.50000 1.34798E-002 0.00000
12 GUESTROOM101 Heating 444.11785 532.94142 1.31260E-002 1.57512E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -26.20000 3.61342E-004 32.61128 1.50000 1.34798E-002 0.00000
13 GUESTROOM102 Cooling 674.89132 809.86959 8.10359E-002 9.72430E-002 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 28.39100 1.53599E-002 32.61128 1.50000 1.34798E-002 0.00000
14 GUESTROOM102 Heating 497.10057 596.52069 1.46919E-002 1.76303E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 -26.20000 3.61342E-004 32.61128 1.50000 1.34798E-002 0.00000
15 GUESTROOM103 Cooling 1217.64296 1461.17155 0.14622 0.17546 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 28.39100 1.53599E-002 32.61128 1.50000 1.34798E-002 0.00000
16 GUESTROOM103 Heating 934.48042 1121.37650 2.76188E-002 3.31425E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:10:00 -26.20000 3.61342E-004 32.61128 1.50000 1.34798E-002 0.00000
17 GUESTROOM104 Cooling 1266.49766 1519.79719 0.15208 0.18250 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 28.23200 1.53596E-002 32.60897 1.50000 1.34788E-002 0.00000
18 GUESTROOM104 Heating 953.72853 1144.47423 2.81877E-002 3.38252E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:10:00 -26.20000 3.61342E-004 32.60897 1.50000 1.34788E-002 0.00000
19 GUESTROOM105 Cooling 1823.90570 2188.68684 0.21902 0.26282 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 27.96700 1.53591E-002 32.60897 1.50000 1.34788E-002 0.00000
20 GUESTROOM105 Heating 496.03510 595.24212 1.46604E-002 1.75925E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 -26.20000 3.61342E-004 32.60897 1.50000 1.34788E-002 0.00000
21 EMPLOYEELOUNGEFLR1 Cooling 7965.22972 9558.27566 0.68841 0.82609 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 27.96700 1.53591E-002 32.60897 18.00000 5.24145E-002 0.00000
22 EMPLOYEELOUNGEFLR1 Heating 456.87735 548.25282 1.35031E-002 5.24145E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -26.20000 3.61342E-004 32.60897 18.00000 5.24145E-002 0.00000
23 EXERCISECENTERFLR1 Cooling 1526.09445 1831.31335 0.13183 0.15820 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 25.37000 1.53543E-002 32.60897 7.00000 7.60119E-002 0.00000
24 EXERCISECENTERFLR1 Heating 344.86868 413.84242 1.01931E-002 7.60119E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:00:00 -26.20000 3.61342E-004 32.60897 7.00000 7.60119E-002 0.00000
25 FRONTOFFICEFLR1 Cooling 3897.19949 4676.63939 0.33656 0.40387 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 27.96700 1.53591E-002 130.43587 10.00000 6.33542E-002 0.00000
26 FRONTOFFICEFLR1 Heating 1943.42490 2332.10989 5.74383E-002 6.89259E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:20:00 -26.20000 3.61342E-004 130.43587 10.00000 6.33542E-002 0.00000
27 FRONTSTAIRSFLR1 Cooling 0.00000 0.00000 0.00000 6.11644E-003 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 30.67000 1.53641E-002 20.06706 1.08000 6.11644E-003 0.00000
28 FRONTSTAIRSFLR1 Heating 122.48956 146.98748 2.44343E-003 6.11644E-003 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 -26.20000 3.61342E-004 20.06706 1.08000 6.11644E-003 0.00000
29 REARSTAIRSFLR2 Cooling 0.00000 0.00000 0.00000 6.11790E-003 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 30.67000 1.53641E-002 20.07186 1.08000 6.11790E-003 0.00000
30 REARSTAIRSFLR2 Heating 0.00000 0.00000 0.00000 6.11790E-003 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -26.20000 3.61342E-004 20.07186 1.08000 6.11790E-003 0.00000
31 CORRIDORFLR2 Cooling 2527.45007 3032.94008 0.21823 0.26187 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.65600 1.53604E-002 125.42017 6.75000 3.82281E-002 0.00000
32 CORRIDORFLR2 Heating 1618.98380 1942.78056 4.78490E-002 5.74188E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:20:00 -26.20000 3.61342E-004 125.42017 6.75000 3.82281E-002 0.00000
33 GUESTROOM201 Cooling 936.86814 1124.24176 0.11249 0.13499 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 28.83267 1.53607E-002 32.61128 1.50000 1.34798E-002 0.00000
34 GUESTROOM201 Heating 853.60552 1024.32663 2.52280E-002 3.02736E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 -26.20000 3.61342E-004 32.61128 1.50000 1.34798E-002 0.00000
35 GUESTROOM202_205 Cooling 4832.77737 5799.33284 0.58034 0.69641 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 28.83267 1.53607E-002 130.44512 6.00000 5.39191E-002 0.00000
36 GUESTROOM202_205 Heating 1600.76080 1920.91297 4.73107E-002 5.67729E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 -26.20000 3.61342E-004 130.44512 6.00000 5.39191E-002 0.00000
37 GUESTROOM206_208 Cooling 3994.91934 4793.90321 0.47973 0.57567 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 28.83267 1.53607E-002 105.35952 4.50000 4.27331E-002 0.00000
38 GUESTROOM206_208 Heating 1244.24052 1493.08863 3.67737E-002 4.41284E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 -26.20000 3.61342E-004 105.35952 4.50000 4.27331E-002 0.00000
39 GUESTROOM209_212 Cooling 4460.61630 5352.73956 0.53565 0.64278 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 28.83267 1.53607E-002 130.44512 6.00000 5.39191E-002 0.00000
40 GUESTROOM209_212 Heating 1479.17882 1775.01459 4.37173E-002 5.39191E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20000 3.61342E-004 130.44512 6.00000 5.39191E-002 0.00000
41 GUESTROOM213 Cooling 1226.03621 1471.24345 0.14723 0.17667 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 28.83267 1.53607E-002 32.61128 1.50000 1.34798E-002 0.00000
42 GUESTROOM213 Heating 828.64632 994.37559 2.44908E-002 2.93890E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 -26.20000 3.61342E-004 32.61128 1.50000 1.34798E-002 0.00000
43 GUESTROOM214 Cooling 1374.38347 1649.26016 0.16504 0.19805 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 27.17200 1.53576E-002 32.60897 1.50000 1.34788E-002 0.00000
44 GUESTROOM214 Heating 823.36004 988.03204 2.43346E-002 2.92015E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 -26.20000 3.61342E-004 32.60897 1.50000 1.34788E-002 0.00000
45 GUESTROOM215_218 Cooling 13519.52102 16223.42523 1.62332 1.94799 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 26.87167 1.53571E-002 130.43587 6.00000 5.39153E-002 0.00000
46 GUESTROOM215_218 Heating 1462.26500 1754.71800 4.32175E-002 5.39153E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -26.20000 3.61342E-004 130.43587 6.00000 5.39153E-002 0.00000
47 GUESTROOM219 Cooling 7199.22437 8639.06924 0.86449 1.03739 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 26.87167 1.53571E-002 32.60897 1.50000 1.34788E-002 0.00000
48 GUESTROOM219 Heating 373.36580 448.03896 1.10349E-002 1.34788E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -26.20000 3.61342E-004 32.60897 1.50000 1.34788E-002 0.00000
49 GUESTROOM220_223 Cooling 4579.93633 5495.92359 0.54998 0.65998 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 27.17200 1.53576E-002 130.43587 6.00000 5.39153E-002 0.00000
50 GUESTROOM220_223 Heating 1452.72071 1743.26485 4.29354E-002 5.39153E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20000 3.61342E-004 130.43587 6.00000 5.39153E-002 0.00000
51 GUESTROOM224 Cooling 1308.91492 1570.69790 0.15718 0.18862 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 27.17200 1.53576E-002 32.60897 1.50000 1.34788E-002 0.00000
52 GUESTROOM224 Heating 665.25222 798.30266 1.96616E-002 2.35940E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 -26.20000 3.61342E-004 32.60897 1.50000 1.34788E-002 0.00000
53 FRONTSTAIRSFLR2 Cooling 0.00000 0.00000 0.00000 6.11644E-003 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 30.14000 1.53631E-002 20.06706 1.08000 6.11644E-003 0.00000
54 FRONTSTAIRSFLR2 Heating 143.87257 172.64709 2.86996E-003 6.11644E-003 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 -26.20000 3.61342E-004 20.06706 1.08000 6.11644E-003 0.00000
55 REARSTAIRSFLR3 Cooling 0.00000 0.00000 0.00000 6.11790E-003 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 30.28133 1.53634E-002 20.07186 1.08000 6.11790E-003 0.00000
56 REARSTAIRSFLR3 Heating 0.00000 0.00000 0.00000 6.11790E-003 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -26.20000 3.61342E-004 20.07186 1.08000 6.11790E-003 0.00000
57 CORRIDORFLR3 Cooling 828.38739 994.06487 7.15254E-002 8.58305E-002 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 28.39100 1.53599E-002 125.42017 6.75000 3.82281E-002 0.00000
58 CORRIDORFLR3 Heating 1873.54371 2248.25245 5.53725E-002 6.64470E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 -26.20000 3.61342E-004 125.42017 6.75000 3.82281E-002 0.00000
59 GUESTROOM301 Cooling 683.88937 820.66725 8.21183E-002 9.85420E-002 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.65600 1.53604E-002 32.61128 1.50000 1.34798E-002 0.00000
60 GUESTROOM301 Heating 912.57808 1095.09369 2.69709E-002 3.23651E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 -26.20000 3.61342E-004 32.61128 1.50000 1.34798E-002 0.00000
61 GUESTROOM302_305 Cooling 2206.19560 2647.43472 0.26490 0.31789 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.65600 1.53604E-002 130.44512 6.00000 5.39191E-002 0.00000
62 GUESTROOM302_305 Heating 1703.91740 2044.70089 5.03596E-002 6.04315E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 -26.20000 3.61342E-004 130.44512 6.00000 5.39191E-002 0.00000
63 GUESTROOM306_308 Cooling 2006.65978 2407.99174 0.24095 0.28913 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 28.83267 1.53607E-002 105.35952 4.50000 4.27331E-002 0.00000
64 GUESTROOM306_308 Heating 1404.17165 1685.00598 4.15005E-002 4.98006E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:20:00 -26.20000 3.61342E-004 105.35952 4.50000 4.27331E-002 0.00000
65 GUESTROOM309_312 Cooling 4251.76680 5102.12015 0.51058 0.61269 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.65600 1.53604E-002 130.44512 6.00000 5.39191E-002 0.00000
66 GUESTROOM309_312 Heating 1684.80901 2021.77081 4.97948E-002 5.97538E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 -26.20000 3.61342E-004 130.44512 6.00000 5.39191E-002 0.00000
67 GUESTROOM313 Cooling 754.92877 905.91452 9.06464E-002 0.10878 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.65600 1.53604E-002 32.61128 1.50000 1.34798E-002 0.00000
68 GUESTROOM313 Heating 905.86151 1087.03381 2.67729E-002 3.21275E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 -26.20000 3.61342E-004 32.61128 1.50000 1.34798E-002 0.00000
69 GUESTROOM314 Cooling 1187.96574 1425.55888 0.14266 0.17119 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 27.43700 1.53581E-002 32.60897 1.50000 1.34788E-002 0.00000
70 GUESTROOM314 Heating 881.00844 1057.21012 2.60384E-002 3.12461E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 -26.20000 3.61342E-004 32.60897 1.50000 1.34788E-002 0.00000
71 GUESTROOM315_318 Cooling 5227.71062 6273.25274 0.62777 0.75332 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 27.17200 1.53576E-002 130.43587 6.00000 5.39153E-002 0.00000
72 GUESTROOM315_318 Heating 1652.23441 1982.68129 4.88321E-002 5.85985E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 -26.20000 3.61342E-004 130.43587 6.00000 5.39153E-002 0.00000
73 GUESTROOM319 Cooling 1234.57626 1481.49151 0.14824 0.17789 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 27.17200 1.53576E-002 32.60897 1.50000 1.34788E-002 0.00000
74 GUESTROOM319 Heating 468.11959 561.74351 1.38354E-002 1.66024E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 -26.20000 3.61342E-004 32.60897 1.50000 1.34788E-002 0.00000
75 GUESTROOM320_323 Cooling 4095.36805 4914.44166 0.49179 0.59015 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 27.17200 1.53576E-002 130.43587 6.00000 5.39153E-002 0.00000
76 GUESTROOM320_323 Heating 1592.09660 1910.51592 4.70546E-002 5.64655E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:20:00 -26.20000 3.61342E-004 130.43587 6.00000 5.39153E-002 0.00000
77 GUESTROOM324 Cooling 717.21115 860.65338 8.61175E-002 0.10334 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 27.43700 1.53581E-002 32.60897 1.50000 1.34788E-002 0.00000
78 GUESTROOM324 Heating 717.73244 861.27893 2.12127E-002 2.54552E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 -26.20000 3.61342E-004 32.60897 1.50000 1.34788E-002 0.00000
79 FRONTSTAIRSFLR3 Cooling 0.00000 0.00000 0.00000 6.11644E-003 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 29.36267 1.53617E-002 20.06706 1.08000 6.11644E-003 0.00000
80 FRONTSTAIRSFLR3 Heating 197.92103 237.50524 3.94806E-003 6.11644E-003 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 -26.20000 3.61342E-004 20.06706 1.08000 6.11644E-003 0.00000
81 REARSTAIRSFLR4 Cooling 0.00000 0.00000 0.00000 6.11790E-003 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 30.98800 1.53647E-002 20.07186 1.08000 6.11790E-003 0.00000
82 REARSTAIRSFLR4 Heating 196.13039 235.35646 3.91236E-003 6.11790E-003 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 -26.20000 3.61342E-004 20.07186 1.08000 6.11790E-003 0.00000
83 CORRIDORFLR4 Cooling 1363.64092 1636.36911 0.11774 0.14129 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 31.20000 1.53651E-002 125.42017 6.75000 3.82281E-002 0.00000
84 CORRIDORFLR4 Heating 3066.86838 3680.24205 9.06411E-002 0.10877 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 -26.20000 3.61342E-004 125.42017 6.75000 3.82281E-002 0.00000
85 GUESTROOM401 Cooling 1457.91342 1749.49610 0.17508 0.21009 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 29.36267 1.53617E-002 32.61128 1.50000 1.34798E-002 0.00000
86 GUESTROOM401 Heating 1384.85770 1661.82924 4.09289E-002 4.91147E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:20:00 -26.20000 3.61342E-004 32.61128 1.50000 1.34798E-002 0.00000
87 GUESTROOM402_405 Cooling 2977.14051 3572.56861 0.35747 0.42897 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 29.36267 1.53617E-002 130.44512 6.00000 5.39191E-002 0.00000
88 GUESTROOM402_405 Heating 2752.47970 3302.97565 8.13499E-002 9.76198E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 -26.20000 3.61342E-004 130.44512 6.00000 5.39191E-002 0.00000
89 GUESTROOM406_408 Cooling 2674.70134 3209.64161 0.32116 0.38539 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 29.36267 1.53617E-002 105.35952 4.50000 4.27331E-002 0.00000
90 GUESTROOM406_408 Heating 2257.28092 2708.73710 6.67142E-002 8.00570E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 -26.20000 3.61342E-004 105.35952 4.50000 4.27331E-002 0.00000
91 GUESTROOM409_412 Cooling 5281.53971 6337.84765 0.63423 0.76108 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 29.36267 1.53617E-002 130.44512 6.00000 5.39191E-002 0.00000
92 GUESTROOM409_412 Heating 2745.23142 3294.27771 8.11356E-002 9.73628E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 -26.20000 3.61342E-004 130.44512 6.00000 5.39191E-002 0.00000
93 GUESTROOM413 Cooling 1059.26615 1271.11938 0.12719 0.15263 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 29.36267 1.53617E-002 32.61128 1.50000 1.34798E-002 0.00000
94 GUESTROOM413 Heating 1287.01104 1544.41325 3.80379E-002 4.56454E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 -26.20000 3.61342E-004 32.61128 1.50000 1.34798E-002 0.00000
95 GUESTROOM414 Cooling 924.25057 1109.10068 0.11098 0.13317 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 28.76200 1.53606E-002 32.60897 1.50000 1.34788E-002 0.00000
96 GUESTROOM414 Heating 1213.03185 1455.63822 3.58514E-002 4.30216E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 -26.20000 3.61342E-004 32.60897 1.50000 1.34788E-002 0.00000
97 GUESTROOM415_418 Cooling 5221.54628 6265.85553 0.62703 0.75244 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 27.70200 1.53586E-002 130.43587 6.00000 5.39153E-002 0.00000
98 GUESTROOM415_418 Heating 2699.92831 3239.91397 7.97967E-002 9.57560E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 -26.20000 3.61342E-004 130.43587 6.00000 5.39153E-002 0.00000
99 GUESTROOM419 Cooling 1416.05012 1699.26014 0.17004 0.20405 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 28.23200 1.53596E-002 32.60897 1.50000 1.34788E-002 0.00000
100 GUESTROOM419 Heating 801.65967 961.99161 2.36932E-002 2.84318E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 -26.20000 3.61342E-004 32.60897 1.50000 1.34788E-002 0.00000
101 GUESTROOM420_423 Cooling 4835.14181 5802.17017 0.58063 0.69676 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 27.70200 1.53586E-002 130.43587 6.00000 5.39153E-002 0.00000
102 GUESTROOM420_423 Heating 2359.99718 2831.99662 6.97500E-002 8.37000E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 -26.20000 3.61342E-004 130.43587 6.00000 5.39153E-002 0.00000
103 GUESTROOM424 Cooling 1383.67078 1660.40494 0.16616 0.19939 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 28.23200 1.53596E-002 32.60897 1.50000 1.34788E-002 0.00000
104 GUESTROOM424 Heating 1037.56690 1245.08028 3.06655E-002 3.67985E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 -26.20000 3.61342E-004 32.60897 1.50000 1.34788E-002 0.00000
105 FRONTSTAIRSFLR4 Cooling 0.00000 0.00000 0.00000 6.11644E-003 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 30.67000 1.53641E-002 20.06706 1.08000 6.11644E-003 0.00000
106 FRONTSTAIRSFLR4 Heating 504.58759 605.50511 1.00649E-002 1.20779E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:20:00 -26.20000 3.61342E-004 20.06706 1.08000 6.11644E-003 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 SAC_FRONTOFFICE Cooling Sensible 5839.09 0.40387 0.40387 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 SAC_FRONTOFFICE Heating Sensible 4961.97 6.89259E-002 6.89259E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:20:00
3 SAC_FRONTLOUNGE Cooling Sensible 15378.46 1.02614 1.02614 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 SAC_FRONTLOUNGE Heating Sensible 18130.53 0.23730 0.23730 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
5 SAC_MEETINGROOM Cooling Sensible 7018.13 0.46133 0.46133 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 SAC_MEETINGROOM Heating Sensible 9622.00 0.12594 0.12594 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
7 SAC_EMPLOYEELOUNGE Cooling Sensible 11573.18 0.82609 0.82609 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 SAC_EMPLOYEELOUNGE Heating Sensible 4004.67 5.24145E-002 5.24145E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 SAC_EXERCISECENTER Cooling Sensible 2300.15 0.15820 0.15820 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 SAC_EXERCISECENTER Heating Sensible 5807.60 7.60119E-002 7.60119E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 SAC_RESTROOM Cooling Sensible 1136.29 8.28201E-002 8.28201E-002 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
12 SAC_RESTROOM Heating Sensible 311.73 1.42991E-002 1.42991E-002 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 ZoneHVAC:UnitHeater REARSTAIRSFLR1 UNIT HEATER Design Size Maximum Supply Air Flow Rate [m3/s] 6.11790E-003
2 Fan:ConstantVolume REARSTAIRSFLR1 UNITHEATER FAN Design Size Maximum Flow Rate [m3/s] 6.11790E-003
3 Coil:Heating:Electric REARSTAIRSFLR1 UNITHEATER HEATING COIL Design Size Nominal Capacity [W] 306.67324
4 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR1 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 2.17985
5 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR1 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 2.17985
6 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR1 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 2.17985
7 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR1 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 4.58742E-002
8 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR1 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 4.58742E-002
9 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR1 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.58742E-002
10 Coil:Cooling:DX:SingleSpeed CORRIDORFLR1 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 2.17985
11 Coil:Cooling:DX:SingleSpeed CORRIDORFLR1 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 41350.03635
12 Coil:Cooling:DX:SingleSpeed CORRIDORFLR1 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.79784
13 Coil:Heating:Electric CORRIDORFLR1 PTAC HEATING COIL Design Size Nominal Capacity [W] 76487.20009
14 Fan:OnOff CORRIDORFLR1 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 2.17985
15 AirTerminal:SingleDuct:ConstantVolume:NoReheat FRONTLOUNGEFLR1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.02614
16 AirTerminal:SingleDuct:ConstantVolume:NoReheat RESTROOMFLR1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 8.28201E-002
17 AirTerminal:SingleDuct:ConstantVolume:NoReheat MEETINGROOMFLR1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.46133
18 ZoneHVAC:UnitHeater MECHANICALROOMFLR1 UNIT HEATER Design Size Maximum Supply Air Flow Rate [m3/s] 0.00000
19 Fan:ConstantVolume MECHRM UNITHEATER FAN Design Size Maximum Flow Rate [m3/s] 0.00000
20 Coil:Heating:Electric MECHRM UNITHEATER HEATING COIL Design Size Nominal Capacity [W] 0.00000
21 ZoneHVAC:PackagedTerminalAirConditioner 101 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.11987
22 ZoneHVAC:PackagedTerminalAirConditioner 101 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.11987
23 ZoneHVAC:PackagedTerminalAirConditioner 101 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.11987
24 ZoneHVAC:PackagedTerminalAirConditioner 101 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34798E-002
25 ZoneHVAC:PackagedTerminalAirConditioner 101 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34798E-002
26 ZoneHVAC:PackagedTerminalAirConditioner 101 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34798E-002
27 Coil:Cooling:DX:SingleSpeed 101 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.11987
28 Coil:Cooling:DX:SingleSpeed 101 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 1984.32581
29 Coil:Cooling:DX:SingleSpeed 101 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
30 Coil:Heating:Electric 101 PTAC HEATING COIL Design Size Nominal Capacity [W] 1279.85828
31 Fan:OnOff 101 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.11987
32 ZoneHVAC:PackagedTerminalAirConditioner 102 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 9.72430E-002
33 ZoneHVAC:PackagedTerminalAirConditioner 102 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 9.72430E-002
34 ZoneHVAC:PackagedTerminalAirConditioner 102 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 9.72430E-002
35 ZoneHVAC:PackagedTerminalAirConditioner 102 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34798E-002
36 ZoneHVAC:PackagedTerminalAirConditioner 102 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34798E-002
37 ZoneHVAC:PackagedTerminalAirConditioner 102 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34798E-002
38 Coil:Cooling:DX:SingleSpeed 102 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 9.72430E-002
39 Coil:Cooling:DX:SingleSpeed 102 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 1609.71747
40 Coil:Cooling:DX:SingleSpeed 102 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
41 Coil:Heating:Electric 102 PTAC HEATING COIL Design Size Nominal Capacity [W] 1343.43681
42 Fan:OnOff 102 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 9.72430E-002
43 ZoneHVAC:PackagedTerminalAirConditioner 103 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.17546
44 ZoneHVAC:PackagedTerminalAirConditioner 103 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.17546
45 ZoneHVAC:PackagedTerminalAirConditioner 103 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.17546
46 ZoneHVAC:PackagedTerminalAirConditioner 103 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34798E-002
47 ZoneHVAC:PackagedTerminalAirConditioner 103 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34798E-002
48 ZoneHVAC:PackagedTerminalAirConditioner 103 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34798E-002
49 Coil:Cooling:DX:SingleSpeed 103 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.17546
50 Coil:Cooling:DX:SingleSpeed 103 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 2904.49328
51 Coil:Cooling:DX:SingleSpeed 103 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
52 Coil:Heating:Electric 103 PTAC HEATING COIL Design Size Nominal Capacity [W] 1868.29285
53 Fan:OnOff 103 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.17546
54 ZoneHVAC:PackagedTerminalAirConditioner 104 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.18250
55 ZoneHVAC:PackagedTerminalAirConditioner 104 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.18250
56 ZoneHVAC:PackagedTerminalAirConditioner 104 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.18250
57 ZoneHVAC:PackagedTerminalAirConditioner 104 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34788E-002
58 ZoneHVAC:PackagedTerminalAirConditioner 104 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34788E-002
59 ZoneHVAC:PackagedTerminalAirConditioner 104 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34788E-002
60 Coil:Cooling:DX:SingleSpeed 104 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.18250
61 Coil:Cooling:DX:SingleSpeed 104 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 3021.02650
62 Coil:Cooling:DX:SingleSpeed 104 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
63 Coil:Heating:Electric 104 PTAC HEATING COIL Design Size Nominal Capacity [W] 1891.33759
64 Fan:OnOff 104 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.18250
65 ZoneHVAC:PackagedTerminalAirConditioner 105 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.26282
66 ZoneHVAC:PackagedTerminalAirConditioner 105 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.26282
67 ZoneHVAC:PackagedTerminalAirConditioner 105 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.26282
68 ZoneHVAC:PackagedTerminalAirConditioner 105 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34788E-002
69 ZoneHVAC:PackagedTerminalAirConditioner 105 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34788E-002
70 ZoneHVAC:PackagedTerminalAirConditioner 105 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34788E-002
71 Coil:Cooling:DX:SingleSpeed 105 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.26282
72 Coil:Cooling:DX:SingleSpeed 105 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4350.61576
73 Coil:Cooling:DX:SingleSpeed 105 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
74 Coil:Heating:Electric 105 PTAC HEATING COIL Design Size Nominal Capacity [W] 1342.10525
75 Fan:OnOff 105 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.26282
76 AirTerminal:SingleDuct:ConstantVolume:NoReheat EMPLOYEELOUNGEFLR1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.82609
77 AirTerminal:SingleDuct:ConstantVolume:NoReheat EXERCISECENTERFLR1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.15820
78 AirTerminal:SingleDuct:ConstantVolume:NoReheat FRONTOFFICEFLR1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.40387
79 ZoneHVAC:UnitHeater FRONTSTAIRSFLR1 UNIT HEATER Design Size Maximum Supply Air Flow Rate [m3/s] 6.11644E-003
80 Fan:ConstantVolume FRONTSTAIRSFLR1 UNITHEATER FAN Design Size Maximum Flow Rate [m3/s] 6.11644E-003
81 Coil:Heating:Electric FRONTSTAIRSFLR1 UNITHEATER HEATING COIL Design Size Nominal Capacity [W] 306.61841
82 ZoneHVAC:UnitHeater REARSTAIRSFLR2 UNIT HEATER Design Size Maximum Supply Air Flow Rate [m3/s] 6.11790E-003
83 Fan:ConstantVolume REARSTAIRSFLR2 UNITHEATER FAN Design Size Maximum Flow Rate [m3/s] 6.11790E-003
84 Coil:Heating:Electric REARSTAIRSFLR2 UNITHEATER HEATING COIL Design Size Nominal Capacity [W] 306.67324
85 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR2 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.26187
86 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR2 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.26187
87 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR2 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.26187
88 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR2 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 3.82281E-002
89 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR2 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 3.82281E-002
90 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR2 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 3.82281E-002
91 Coil:Cooling:DX:SingleSpeed CORRIDORFLR2 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.26187
92 Coil:Cooling:DX:SingleSpeed CORRIDORFLR2 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4334.91051
93 Coil:Cooling:DX:SingleSpeed CORRIDORFLR2 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
94 Coil:Heating:Electric CORRIDORFLR2 PTAC HEATING COIL Design Size Nominal Capacity [W] 4060.99127
95 Fan:OnOff CORRIDORFLR2 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.26187
96 ZoneHVAC:PackagedTerminalAirConditioner 201 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.13499
97 ZoneHVAC:PackagedTerminalAirConditioner 201 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.13499
98 ZoneHVAC:PackagedTerminalAirConditioner 201 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.13499
99 ZoneHVAC:PackagedTerminalAirConditioner 201 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34798E-002
100 ZoneHVAC:PackagedTerminalAirConditioner 201 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34798E-002
101 ZoneHVAC:PackagedTerminalAirConditioner 201 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34798E-002
102 Coil:Cooling:DX:SingleSpeed 201 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.13499
103 Coil:Cooling:DX:SingleSpeed 201 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 2234.61738
104 Coil:Cooling:DX:SingleSpeed 201 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
105 Coil:Heating:Electric 201 PTAC HEATING COIL Design Size Nominal Capacity [W] 1771.22913
106 Fan:OnOff 201 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.13499
107 ZoneHVAC:PackagedTerminalAirConditioner 202_205 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.69641
108 ZoneHVAC:PackagedTerminalAirConditioner 202_205 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.69641
109 ZoneHVAC:PackagedTerminalAirConditioner 202_205 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.69641
110 ZoneHVAC:PackagedTerminalAirConditioner 202_205 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 5.39191E-002
111 ZoneHVAC:PackagedTerminalAirConditioner 202_205 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 5.39191E-002
112 ZoneHVAC:PackagedTerminalAirConditioner 202_205 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.39191E-002
113 Coil:Cooling:DX:SingleSpeed 202_205 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.69641
114 Coil:Cooling:DX:SingleSpeed 202_205 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 11528.11265
115 Coil:Cooling:DX:SingleSpeed 202_205 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
116 Coil:Heating:Electric 202_205 PTAC HEATING COIL Design Size Nominal Capacity [W] 4908.57384
117 Fan:OnOff 202_205 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.69641
118 ZoneHVAC:PackagedTerminalAirConditioner 206_208 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.57567
119 ZoneHVAC:PackagedTerminalAirConditioner 206_208 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.57567
120 ZoneHVAC:PackagedTerminalAirConditioner 206_208 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.57567
121 ZoneHVAC:PackagedTerminalAirConditioner 206_208 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 4.27331E-002
122 ZoneHVAC:PackagedTerminalAirConditioner 206_208 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 4.27331E-002
123 ZoneHVAC:PackagedTerminalAirConditioner 206_208 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.27331E-002
124 Coil:Cooling:DX:SingleSpeed 206_208 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.57567
125 Coil:Cooling:DX:SingleSpeed 206_208 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 9529.40261
126 Coil:Cooling:DX:SingleSpeed 206_208 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
127 Coil:Heating:Electric 206_208 PTAC HEATING COIL Design Size Nominal Capacity [W] 3860.93021
128 Fan:OnOff 206_208 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.57567
129 ZoneHVAC:PackagedTerminalAirConditioner 209_212 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.64278
130 ZoneHVAC:PackagedTerminalAirConditioner 209_212 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.64278
131 ZoneHVAC:PackagedTerminalAirConditioner 209_212 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.64278
132 ZoneHVAC:PackagedTerminalAirConditioner 209_212 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 5.39191E-002
133 ZoneHVAC:PackagedTerminalAirConditioner 209_212 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 5.39191E-002
134 ZoneHVAC:PackagedTerminalAirConditioner 209_212 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.39191E-002
135 Coil:Cooling:DX:SingleSpeed 209_212 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.64278
136 Coil:Cooling:DX:SingleSpeed 209_212 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 10640.37148
137 Coil:Cooling:DX:SingleSpeed 209_212 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
138 Coil:Heating:Electric 209_212 PTAC HEATING COIL Design Size Nominal Capacity [W] 4812.01621
139 Fan:OnOff 209_212 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.64278
140 ZoneHVAC:PackagedTerminalAirConditioner 213 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.17667
141 ZoneHVAC:PackagedTerminalAirConditioner 213 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.17667
142 ZoneHVAC:PackagedTerminalAirConditioner 213 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.17667
143 ZoneHVAC:PackagedTerminalAirConditioner 213 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34798E-002
144 ZoneHVAC:PackagedTerminalAirConditioner 213 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34798E-002
145 ZoneHVAC:PackagedTerminalAirConditioner 213 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34798E-002
146 Coil:Cooling:DX:SingleSpeed 213 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.17667
147 Coil:Cooling:DX:SingleSpeed 213 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 2924.55649
148 Coil:Cooling:DX:SingleSpeed 213 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
149 Coil:Heating:Electric 213 PTAC HEATING COIL Design Size Nominal Capacity [W] 1741.29102
150 Fan:OnOff 213 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.17667
151 ZoneHVAC:PackagedTerminalAirConditioner 214 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.19805
152 ZoneHVAC:PackagedTerminalAirConditioner 214 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.19805
153 ZoneHVAC:PackagedTerminalAirConditioner 214 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.19805
154 ZoneHVAC:PackagedTerminalAirConditioner 214 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34788E-002
155 ZoneHVAC:PackagedTerminalAirConditioner 214 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34788E-002
156 ZoneHVAC:PackagedTerminalAirConditioner 214 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34788E-002
157 Coil:Cooling:DX:SingleSpeed 214 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.19805
158 Coil:Cooling:DX:SingleSpeed 214 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 3278.41430
159 Coil:Cooling:DX:SingleSpeed 214 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
160 Coil:Heating:Electric 214 PTAC HEATING COIL Design Size Nominal Capacity [W] 1734.89449
161 Fan:OnOff 214 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.19805
162 ZoneHVAC:PackagedTerminalAirConditioner 215_218 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 1.94799
163 ZoneHVAC:PackagedTerminalAirConditioner 215_218 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 1.94799
164 ZoneHVAC:PackagedTerminalAirConditioner 215_218 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 1.94799
165 ZoneHVAC:PackagedTerminalAirConditioner 215_218 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 5.39153E-002
166 ZoneHVAC:PackagedTerminalAirConditioner 215_218 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 5.39153E-002
167 ZoneHVAC:PackagedTerminalAirConditioner 215_218 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.39153E-002
168 Coil:Cooling:DX:SingleSpeed 215_218 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 1.94799
169 Coil:Cooling:DX:SingleSpeed 215_218 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 32246.12983
170 Coil:Cooling:DX:SingleSpeed 215_218 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
171 Coil:Heating:Electric 215_218 PTAC HEATING COIL Design Size Nominal Capacity [W] 4811.67476
172 Fan:OnOff 215_218 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 1.94799
173 ZoneHVAC:PackagedTerminalAirConditioner 219 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 1.03739
174 ZoneHVAC:PackagedTerminalAirConditioner 219 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 1.03739
175 ZoneHVAC:PackagedTerminalAirConditioner 219 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 1.03739
176 ZoneHVAC:PackagedTerminalAirConditioner 219 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34788E-002
177 ZoneHVAC:PackagedTerminalAirConditioner 219 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34788E-002
178 ZoneHVAC:PackagedTerminalAirConditioner 219 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34788E-002
179 Coil:Cooling:DX:SingleSpeed 219 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 1.03739
180 Coil:Cooling:DX:SingleSpeed 219 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 17172.47288
181 Coil:Cooling:DX:SingleSpeed 219 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
182 Coil:Heating:Electric 219 PTAC HEATING COIL Design Size Nominal Capacity [W] 1202.91869
183 Fan:OnOff 219 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 1.03739
184 ZoneHVAC:PackagedTerminalAirConditioner 220_223 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.65998
185 ZoneHVAC:PackagedTerminalAirConditioner 220_223 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.65998
186 ZoneHVAC:PackagedTerminalAirConditioner 220_223 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.65998
187 ZoneHVAC:PackagedTerminalAirConditioner 220_223 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 5.39153E-002
188 ZoneHVAC:PackagedTerminalAirConditioner 220_223 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 5.39153E-002
189 ZoneHVAC:PackagedTerminalAirConditioner 220_223 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.39153E-002
190 Coil:Cooling:DX:SingleSpeed 220_223 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.65998
191 Coil:Cooling:DX:SingleSpeed 220_223 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 10924.99140
192 Coil:Cooling:DX:SingleSpeed 220_223 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
193 Coil:Heating:Electric 220_223 PTAC HEATING COIL Design Size Nominal Capacity [W] 4811.67476
194 Fan:OnOff 220_223 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.65998
195 ZoneHVAC:PackagedTerminalAirConditioner 224 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.18862
196 ZoneHVAC:PackagedTerminalAirConditioner 224 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.18862
197 ZoneHVAC:PackagedTerminalAirConditioner 224 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.18862
198 ZoneHVAC:PackagedTerminalAirConditioner 224 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34788E-002
199 ZoneHVAC:PackagedTerminalAirConditioner 224 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34788E-002
200 ZoneHVAC:PackagedTerminalAirConditioner 224 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34788E-002
201 Coil:Cooling:DX:SingleSpeed 224 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.18862
202 Coil:Cooling:DX:SingleSpeed 224 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 3122.24974
203 Coil:Cooling:DX:SingleSpeed 224 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
204 Coil:Heating:Electric 224 PTAC HEATING COIL Design Size Nominal Capacity [W] 1545.16508
205 Fan:OnOff 224 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.18862
206 ZoneHVAC:UnitHeater FRONTSTAIRSFLR2 UNIT HEATER Design Size Maximum Supply Air Flow Rate [m3/s] 6.11644E-003
207 Fan:ConstantVolume FRONTSTAIRSFLR2 UNITHEATER FAN Design Size Maximum Flow Rate [m3/s] 6.11644E-003
208 Coil:Heating:Electric FRONTSTAIRSFLR2 UNITHEATER HEATING COIL Design Size Nominal Capacity [W] 306.61554
209 ZoneHVAC:UnitHeater REARSTAIRSFLR3 UNIT HEATER Design Size Maximum Supply Air Flow Rate [m3/s] 6.11790E-003
210 Fan:ConstantVolume REARSTAIRSFLR3 UNITHEATER FAN Design Size Maximum Flow Rate [m3/s] 6.11790E-003
211 Coil:Heating:Electric REARSTAIRSFLR3 UNITHEATER HEATING COIL Design Size Nominal Capacity [W] 306.67324
212 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR3 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 8.58305E-002
213 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR3 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 8.58305E-002
214 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR3 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 8.58305E-002
215 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR3 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 3.82281E-002
216 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR3 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 3.82281E-002
217 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR3 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 3.82281E-002
218 Coil:Cooling:DX:SingleSpeed CORRIDORFLR3 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 8.58305E-002
219 Coil:Cooling:DX:SingleSpeed CORRIDORFLR3 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 1932.58870
220 Coil:Cooling:DX:SingleSpeed CORRIDORFLR3 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.73229
221 Coil:Heating:Electric CORRIDORFLR3 PTAC HEATING COIL Design Size Nominal Capacity [W] 4366.45831
222 Fan:OnOff CORRIDORFLR3 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 8.58305E-002
223 ZoneHVAC:PackagedTerminalAirConditioner 301 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 9.85420E-002
224 ZoneHVAC:PackagedTerminalAirConditioner 301 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 9.85420E-002
225 ZoneHVAC:PackagedTerminalAirConditioner 301 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 9.85420E-002
226 ZoneHVAC:PackagedTerminalAirConditioner 301 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34798E-002
227 ZoneHVAC:PackagedTerminalAirConditioner 301 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34798E-002
228 ZoneHVAC:PackagedTerminalAirConditioner 301 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34798E-002
229 Coil:Cooling:DX:SingleSpeed 301 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 9.85420E-002
230 Coil:Cooling:DX:SingleSpeed 301 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 1631.21936
231 Coil:Cooling:DX:SingleSpeed 301 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
232 Coil:Heating:Electric 301 PTAC HEATING COIL Design Size Nominal Capacity [W] 1841.99756
233 Fan:OnOff 301 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 9.85420E-002
234 ZoneHVAC:PackagedTerminalAirConditioner 302_305 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.31789
235 ZoneHVAC:PackagedTerminalAirConditioner 302_305 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.31789
236 ZoneHVAC:PackagedTerminalAirConditioner 302_305 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.31789
237 ZoneHVAC:PackagedTerminalAirConditioner 302_305 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 5.39191E-002
238 ZoneHVAC:PackagedTerminalAirConditioner 302_305 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 5.39191E-002
239 ZoneHVAC:PackagedTerminalAirConditioner 302_305 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.39191E-002
240 Coil:Cooling:DX:SingleSpeed 302_305 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.31789
241 Coil:Cooling:DX:SingleSpeed 302_305 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5262.12985
242 Coil:Cooling:DX:SingleSpeed 302_305 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
243 Coil:Heating:Electric 302_305 PTAC HEATING COIL Design Size Nominal Capacity [W] 5032.36204
244 Fan:OnOff 302_305 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.31789
245 ZoneHVAC:PackagedTerminalAirConditioner 306_308 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.28913
246 ZoneHVAC:PackagedTerminalAirConditioner 306_308 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.28913
247 ZoneHVAC:PackagedTerminalAirConditioner 306_308 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.28913
248 ZoneHVAC:PackagedTerminalAirConditioner 306_308 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 4.27331E-002
249 ZoneHVAC:PackagedTerminalAirConditioner 306_308 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 4.27331E-002
250 ZoneHVAC:PackagedTerminalAirConditioner 306_308 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.27331E-002
251 Coil:Cooling:DX:SingleSpeed 306_308 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.28913
252 Coil:Cooling:DX:SingleSpeed 306_308 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4786.20407
253 Coil:Cooling:DX:SingleSpeed 306_308 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
254 Coil:Heating:Electric 306_308 PTAC HEATING COIL Design Size Nominal Capacity [W] 4052.84695
255 Fan:OnOff 306_308 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.28913
256 ZoneHVAC:PackagedTerminalAirConditioner 309_312 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.61269
257 ZoneHVAC:PackagedTerminalAirConditioner 309_312 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.61269
258 ZoneHVAC:PackagedTerminalAirConditioner 309_312 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.61269
259 ZoneHVAC:PackagedTerminalAirConditioner 309_312 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 5.39191E-002
260 ZoneHVAC:PackagedTerminalAirConditioner 309_312 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 5.39191E-002
261 ZoneHVAC:PackagedTerminalAirConditioner 309_312 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.39191E-002
262 Coil:Cooling:DX:SingleSpeed 309_312 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.61269
263 Coil:Cooling:DX:SingleSpeed 309_312 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 10142.19851
264 Coil:Cooling:DX:SingleSpeed 309_312 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
265 Coil:Heating:Electric 309_312 PTAC HEATING COIL Design Size Nominal Capacity [W] 5009.43201
266 Fan:OnOff 309_312 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.61269
267 ZoneHVAC:PackagedTerminalAirConditioner 313 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.10878
268 ZoneHVAC:PackagedTerminalAirConditioner 313 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.10878
269 ZoneHVAC:PackagedTerminalAirConditioner 313 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.10878
270 ZoneHVAC:PackagedTerminalAirConditioner 313 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34798E-002
271 ZoneHVAC:PackagedTerminalAirConditioner 313 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34798E-002
272 ZoneHVAC:PackagedTerminalAirConditioner 313 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34798E-002
273 Coil:Cooling:DX:SingleSpeed 313 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.10878
274 Coil:Cooling:DX:SingleSpeed 313 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 1800.62330
275 Coil:Cooling:DX:SingleSpeed 313 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
276 Coil:Heating:Electric 313 PTAC HEATING COIL Design Size Nominal Capacity [W] 1833.94862
277 Fan:OnOff 313 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.10878
278 ZoneHVAC:PackagedTerminalAirConditioner 314 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.17119
279 ZoneHVAC:PackagedTerminalAirConditioner 314 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.17119
280 ZoneHVAC:PackagedTerminalAirConditioner 314 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.17119
281 ZoneHVAC:PackagedTerminalAirConditioner 314 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34788E-002
282 ZoneHVAC:PackagedTerminalAirConditioner 314 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34788E-002
283 ZoneHVAC:PackagedTerminalAirConditioner 314 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34788E-002
284 Coil:Cooling:DX:SingleSpeed 314 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.17119
285 Coil:Cooling:DX:SingleSpeed 314 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 2833.74779
286 Coil:Cooling:DX:SingleSpeed 314 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
287 Coil:Heating:Electric 314 PTAC HEATING COIL Design Size Nominal Capacity [W] 1804.07197
288 Fan:OnOff 314 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.17119
289 ZoneHVAC:PackagedTerminalAirConditioner 315_318 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.75332
290 ZoneHVAC:PackagedTerminalAirConditioner 315_318 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.75332
291 ZoneHVAC:PackagedTerminalAirConditioner 315_318 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.75332
292 ZoneHVAC:PackagedTerminalAirConditioner 315_318 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 5.39153E-002
293 ZoneHVAC:PackagedTerminalAirConditioner 315_318 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 5.39153E-002
294 ZoneHVAC:PackagedTerminalAirConditioner 315_318 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.39153E-002
295 Coil:Cooling:DX:SingleSpeed 315_318 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.75332
296 Coil:Cooling:DX:SingleSpeed 315_318 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 12470.18493
297 Coil:Cooling:DX:SingleSpeed 315_318 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
298 Coil:Heating:Electric 315_318 PTAC HEATING COIL Design Size Nominal Capacity [W] 4970.13056
299 Fan:OnOff 315_318 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.75332
300 ZoneHVAC:PackagedTerminalAirConditioner 319 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.17789
301 ZoneHVAC:PackagedTerminalAirConditioner 319 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.17789
302 ZoneHVAC:PackagedTerminalAirConditioner 319 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.17789
303 ZoneHVAC:PackagedTerminalAirConditioner 319 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34788E-002
304 ZoneHVAC:PackagedTerminalAirConditioner 319 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34788E-002
305 ZoneHVAC:PackagedTerminalAirConditioner 319 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34788E-002
306 Coil:Cooling:DX:SingleSpeed 319 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.17789
307 Coil:Cooling:DX:SingleSpeed 319 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 2944.65614
308 Coil:Cooling:DX:SingleSpeed 319 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
309 Coil:Heating:Electric 319 PTAC HEATING COIL Design Size Nominal Capacity [W] 1308.60608
310 Fan:OnOff 319 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.17789
311 ZoneHVAC:PackagedTerminalAirConditioner 320_323 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.59015
312 ZoneHVAC:PackagedTerminalAirConditioner 320_323 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.59015
313 ZoneHVAC:PackagedTerminalAirConditioner 320_323 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.59015
314 ZoneHVAC:PackagedTerminalAirConditioner 320_323 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 5.39153E-002
315 ZoneHVAC:PackagedTerminalAirConditioner 320_323 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 5.39153E-002
316 ZoneHVAC:PackagedTerminalAirConditioner 320_323 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.39153E-002
317 Coil:Cooling:DX:SingleSpeed 320_323 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.59015
318 Coil:Cooling:DX:SingleSpeed 320_323 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 9769.13131
319 Coil:Cooling:DX:SingleSpeed 320_323 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
320 Coil:Heating:Electric 320_323 PTAC HEATING COIL Design Size Nominal Capacity [W] 4897.96280
321 Fan:OnOff 320_323 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.59015
322 ZoneHVAC:PackagedTerminalAirConditioner 324 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.10334
323 ZoneHVAC:PackagedTerminalAirConditioner 324 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.10334
324 ZoneHVAC:PackagedTerminalAirConditioner 324 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.10334
325 ZoneHVAC:PackagedTerminalAirConditioner 324 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34788E-002
326 ZoneHVAC:PackagedTerminalAirConditioner 324 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34788E-002
327 ZoneHVAC:PackagedTerminalAirConditioner 324 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34788E-002
328 Coil:Cooling:DX:SingleSpeed 324 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.10334
329 Coil:Cooling:DX:SingleSpeed 324 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 1710.66114
330 Coil:Cooling:DX:SingleSpeed 324 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
331 Coil:Heating:Electric 324 PTAC HEATING COIL Design Size Nominal Capacity [W] 1608.14008
332 Fan:OnOff 324 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.10334
333 ZoneHVAC:UnitHeater FRONTSTAIRSFLR3 UNIT HEATER Design Size Maximum Supply Air Flow Rate [m3/s] 6.11644E-003
334 Fan:ConstantVolume FRONTSTAIRSFLR3 UNITHEATER FAN Design Size Maximum Flow Rate [m3/s] 6.11644E-003
335 Coil:Heating:Electric FRONTSTAIRSFLR3 UNITHEATER HEATING COIL Design Size Nominal Capacity [W] 306.61895
336 ZoneHVAC:UnitHeater REARSTAIRSFLR4 UNIT HEATER Design Size Maximum Supply Air Flow Rate [m3/s] 6.11790E-003
337 Fan:ConstantVolume REARSTAIRSFLR4 UNITHEATER FAN Design Size Maximum Flow Rate [m3/s] 6.11790E-003
338 Coil:Heating:Electric REARSTAIRSFLR4 UNITHEATER HEATING COIL Design Size Nominal Capacity [W] 306.69150
339 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR4 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.14129
340 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR4 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.14129
341 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR4 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.14129
342 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR4 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 3.82281E-002
343 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR4 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 3.82281E-002
344 ZoneHVAC:PackagedTerminalAirConditioner CORRIDORFLR4 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 3.82281E-002
345 Coil:Cooling:DX:SingleSpeed CORRIDORFLR4 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.14129
346 Coil:Cooling:DX:SingleSpeed CORRIDORFLR4 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 2867.52810
347 Coil:Cooling:DX:SingleSpeed CORRIDORFLR4 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.77087
348 Coil:Heating:Electric CORRIDORFLR4 PTAC HEATING COIL Design Size Nominal Capacity [W] 5798.43983
349 Fan:OnOff CORRIDORFLR4 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.14129
350 ZoneHVAC:PackagedTerminalAirConditioner 401 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.21009
351 ZoneHVAC:PackagedTerminalAirConditioner 401 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.21009
352 ZoneHVAC:PackagedTerminalAirConditioner 401 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.21009
353 ZoneHVAC:PackagedTerminalAirConditioner 401 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34798E-002
354 ZoneHVAC:PackagedTerminalAirConditioner 401 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34798E-002
355 ZoneHVAC:PackagedTerminalAirConditioner 401 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34798E-002
356 Coil:Cooling:DX:SingleSpeed 401 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.21009
357 Coil:Cooling:DX:SingleSpeed 401 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 3477.74278
358 Coil:Cooling:DX:SingleSpeed 401 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
359 Coil:Heating:Electric 401 PTAC HEATING COIL Design Size Nominal Capacity [W] 2408.72249
360 Fan:OnOff 401 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.21009
361 ZoneHVAC:PackagedTerminalAirConditioner 402_405 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.42897
362 ZoneHVAC:PackagedTerminalAirConditioner 402_405 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.42897
363 ZoneHVAC:PackagedTerminalAirConditioner 402_405 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.42897
364 ZoneHVAC:PackagedTerminalAirConditioner 402_405 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 5.39191E-002
365 ZoneHVAC:PackagedTerminalAirConditioner 402_405 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 5.39191E-002
366 ZoneHVAC:PackagedTerminalAirConditioner 402_405 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.39191E-002
367 Coil:Cooling:DX:SingleSpeed 402_405 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.42897
368 Coil:Cooling:DX:SingleSpeed 402_405 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 7100.96006
369 Coil:Cooling:DX:SingleSpeed 402_405 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
370 Coil:Heating:Electric 402_405 PTAC HEATING COIL Design Size Nominal Capacity [W] 6290.62820
371 Fan:OnOff 402_405 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.42897
372 ZoneHVAC:PackagedTerminalAirConditioner 406_408 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.38539
373 ZoneHVAC:PackagedTerminalAirConditioner 406_408 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.38539
374 ZoneHVAC:PackagedTerminalAirConditioner 406_408 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.38539
375 ZoneHVAC:PackagedTerminalAirConditioner 406_408 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 4.27331E-002
376 ZoneHVAC:PackagedTerminalAirConditioner 406_408 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 4.27331E-002
377 ZoneHVAC:PackagedTerminalAirConditioner 406_408 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.27331E-002
378 Coil:Cooling:DX:SingleSpeed 406_408 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.38539
379 Coil:Cooling:DX:SingleSpeed 406_408 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6379.59239
380 Coil:Cooling:DX:SingleSpeed 406_408 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
381 Coil:Heating:Electric 406_408 PTAC HEATING COIL Design Size Nominal Capacity [W] 5076.57336
382 Fan:OnOff 406_408 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.38539
383 ZoneHVAC:PackagedTerminalAirConditioner 409_412 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.76108
384 ZoneHVAC:PackagedTerminalAirConditioner 409_412 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.76108
385 ZoneHVAC:PackagedTerminalAirConditioner 409_412 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.76108
386 ZoneHVAC:PackagedTerminalAirConditioner 409_412 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 5.39191E-002
387 ZoneHVAC:PackagedTerminalAirConditioner 409_412 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 5.39191E-002
388 ZoneHVAC:PackagedTerminalAirConditioner 409_412 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.39191E-002
389 Coil:Cooling:DX:SingleSpeed 409_412 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.76108
390 Coil:Cooling:DX:SingleSpeed 409_412 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 12598.59729
391 Coil:Cooling:DX:SingleSpeed 409_412 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
392 Coil:Heating:Electric 409_412 PTAC HEATING COIL Design Size Nominal Capacity [W] 6281.93029
393 Fan:OnOff 409_412 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.76108
394 ZoneHVAC:PackagedTerminalAirConditioner 413 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.15263
395 ZoneHVAC:PackagedTerminalAirConditioner 413 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.15263
396 ZoneHVAC:PackagedTerminalAirConditioner 413 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.15263
397 ZoneHVAC:PackagedTerminalAirConditioner 413 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34798E-002
398 ZoneHVAC:PackagedTerminalAirConditioner 413 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34798E-002
399 ZoneHVAC:PackagedTerminalAirConditioner 413 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34798E-002
400 Coil:Cooling:DX:SingleSpeed 413 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.15263
401 Coil:Cooling:DX:SingleSpeed 413 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 2526.51639
402 Coil:Cooling:DX:SingleSpeed 413 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
403 Coil:Heating:Electric 413 PTAC HEATING COIL Design Size Nominal Capacity [W] 2291.32704
404 Fan:OnOff 413 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.15263
405 ZoneHVAC:PackagedTerminalAirConditioner 414 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.13317
406 ZoneHVAC:PackagedTerminalAirConditioner 414 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.13317
407 ZoneHVAC:PackagedTerminalAirConditioner 414 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.13317
408 ZoneHVAC:PackagedTerminalAirConditioner 414 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34788E-002
409 ZoneHVAC:PackagedTerminalAirConditioner 414 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34788E-002
410 ZoneHVAC:PackagedTerminalAirConditioner 414 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34788E-002
411 Coil:Cooling:DX:SingleSpeed 414 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.13317
412 Coil:Cooling:DX:SingleSpeed 414 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 2204.48354
413 Coil:Cooling:DX:SingleSpeed 414 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
414 Coil:Heating:Electric 414 PTAC HEATING COIL Design Size Nominal Capacity [W] 2202.49746
415 Fan:OnOff 414 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.13317
416 ZoneHVAC:PackagedTerminalAirConditioner 415_418 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.75244
417 ZoneHVAC:PackagedTerminalAirConditioner 415_418 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.75244
418 ZoneHVAC:PackagedTerminalAirConditioner 415_418 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.75244
419 ZoneHVAC:PackagedTerminalAirConditioner 415_418 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 5.39153E-002
420 ZoneHVAC:PackagedTerminalAirConditioner 415_418 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 5.39153E-002
421 ZoneHVAC:PackagedTerminalAirConditioner 415_418 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.39153E-002
422 Coil:Cooling:DX:SingleSpeed 415_418 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.75244
423 Coil:Cooling:DX:SingleSpeed 415_418 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 12455.49667
424 Coil:Cooling:DX:SingleSpeed 415_418 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
425 Coil:Heating:Electric 415_418 PTAC HEATING COIL Design Size Nominal Capacity [W] 6227.35473
426 Fan:OnOff 415_418 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.75244
427 ZoneHVAC:PackagedTerminalAirConditioner 419 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.20405
428 ZoneHVAC:PackagedTerminalAirConditioner 419 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.20405
429 ZoneHVAC:PackagedTerminalAirConditioner 419 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.20405
430 ZoneHVAC:PackagedTerminalAirConditioner 419 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34788E-002
431 ZoneHVAC:PackagedTerminalAirConditioner 419 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34788E-002
432 ZoneHVAC:PackagedTerminalAirConditioner 419 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34788E-002
433 Coil:Cooling:DX:SingleSpeed 419 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.20405
434 Coil:Cooling:DX:SingleSpeed 419 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 3377.80957
435 Coil:Cooling:DX:SingleSpeed 419 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
436 Coil:Heating:Electric 419 PTAC HEATING COIL Design Size Nominal Capacity [W] 1708.85323
437 Fan:OnOff 419 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.20405
438 ZoneHVAC:PackagedTerminalAirConditioner 420_423 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.69676
439 ZoneHVAC:PackagedTerminalAirConditioner 420_423 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.69676
440 ZoneHVAC:PackagedTerminalAirConditioner 420_423 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.69676
441 ZoneHVAC:PackagedTerminalAirConditioner 420_423 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 5.39153E-002
442 ZoneHVAC:PackagedTerminalAirConditioner 420_423 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 5.39153E-002
443 ZoneHVAC:PackagedTerminalAirConditioner 420_423 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.39153E-002
444 Coil:Cooling:DX:SingleSpeed 420_423 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.69676
445 Coil:Cooling:DX:SingleSpeed 420_423 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 11533.77667
446 Coil:Cooling:DX:SingleSpeed 420_423 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
447 Coil:Heating:Electric 420_423 PTAC HEATING COIL Design Size Nominal Capacity [W] 5819.43879
448 Fan:OnOff 420_423 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.69676
449 ZoneHVAC:PackagedTerminalAirConditioner 424 PTAC Design Size Cooling Supply Air Flow Rate [m3/s] 0.19939
450 ZoneHVAC:PackagedTerminalAirConditioner 424 PTAC Design Size Heating Supply Air Flow Rate [m3/s] 0.19939
451 ZoneHVAC:PackagedTerminalAirConditioner 424 PTAC Design Size No Load Supply Air Flow Rate [m3/s] 0.19939
452 ZoneHVAC:PackagedTerminalAirConditioner 424 PTAC Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] 1.34788E-002
453 ZoneHVAC:PackagedTerminalAirConditioner 424 PTAC Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] 1.34788E-002
454 ZoneHVAC:PackagedTerminalAirConditioner 424 PTAC Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] 1.34788E-002
455 Coil:Cooling:DX:SingleSpeed 424 PTAC PTAC COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.19939
456 Coil:Cooling:DX:SingleSpeed 424 PTAC PTAC COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 3300.57439
457 Coil:Cooling:DX:SingleSpeed 424 PTAC PTAC COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
458 Coil:Heating:Electric 424 PTAC HEATING COIL Design Size Nominal Capacity [W] 1991.94004
459 Fan:OnOff 424 PTAC SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.19939
460 ZoneHVAC:UnitHeater FRONTSTAIRSFLR4 UNIT HEATER Design Size Maximum Supply Air Flow Rate [m3/s] 1.20779E-002
461 Fan:ConstantVolume FRONTSTAIRSFLR4 UNITHEATER FAN Design Size Maximum Flow Rate [m3/s] 1.20779E-002
462 Coil:Heating:Electric FRONTSTAIRSFLR4 UNITHEATER HEATING COIL Design Size Nominal Capacity [W] 605.47846
463 AirLoopHVAC SAC_FRONTOFFICE Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.40387
464 AirLoopHVAC SAC_FRONTOFFICE Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.40387
465 AirLoopHVAC SAC_FRONTOFFICE Sum of Air Terminal Maximum Flow Rates [m3/s] 0.40387
466 AirLoopHVAC SAC_FRONTOFFICE Adjusted Heating Design Air Flow Rate [m3/s] 0.40387
467 AirLoopHVAC SAC_FRONTOFFICE Adjusted Cooling Design Air Flow Rate [m3/s] 0.40387
468 AirLoopHVAC SAC_FRONTOFFICE Adjusted Main Design Air Flow Rate [m3/s] 0.40387
469 AirLoopHVAC SAC_FRONTOFFICE User Heating Air Flow Ratio [] 1.00000
470 AirLoopHVAC SAC_FRONTOFFICE Calculated Heating Air Flow Ratio [] 1.00000
471 AirLoopHVAC SAC_FRONTLOUNGE Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.02614
472 AirLoopHVAC SAC_FRONTLOUNGE Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.02614
473 AirLoopHVAC SAC_FRONTLOUNGE Sum of Air Terminal Maximum Flow Rates [m3/s] 1.02614
474 AirLoopHVAC SAC_FRONTLOUNGE Adjusted Heating Design Air Flow Rate [m3/s] 1.02614
475 AirLoopHVAC SAC_FRONTLOUNGE Adjusted Cooling Design Air Flow Rate [m3/s] 1.02614
476 AirLoopHVAC SAC_FRONTLOUNGE Adjusted Main Design Air Flow Rate [m3/s] 1.02614
477 AirLoopHVAC SAC_FRONTLOUNGE User Heating Air Flow Ratio [] 1.00000
478 AirLoopHVAC SAC_FRONTLOUNGE Calculated Heating Air Flow Ratio [] 1.00000
479 AirLoopHVAC SAC_MEETINGROOM Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.46133
480 AirLoopHVAC SAC_MEETINGROOM Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.46133
481 AirLoopHVAC SAC_MEETINGROOM Sum of Air Terminal Maximum Flow Rates [m3/s] 0.46133
482 AirLoopHVAC SAC_MEETINGROOM Adjusted Heating Design Air Flow Rate [m3/s] 0.46133
483 AirLoopHVAC SAC_MEETINGROOM Adjusted Cooling Design Air Flow Rate [m3/s] 0.46133
484 AirLoopHVAC SAC_MEETINGROOM Adjusted Main Design Air Flow Rate [m3/s] 0.46133
485 AirLoopHVAC SAC_MEETINGROOM User Heating Air Flow Ratio [] 1.00000
486 AirLoopHVAC SAC_MEETINGROOM Calculated Heating Air Flow Ratio [] 1.00000
487 AirLoopHVAC SAC_EMPLOYEELOUNGE Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.82609
488 AirLoopHVAC SAC_EMPLOYEELOUNGE Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.82609
489 AirLoopHVAC SAC_EMPLOYEELOUNGE Sum of Air Terminal Maximum Flow Rates [m3/s] 0.82609
490 AirLoopHVAC SAC_EMPLOYEELOUNGE Adjusted Heating Design Air Flow Rate [m3/s] 0.82609
491 AirLoopHVAC SAC_EMPLOYEELOUNGE Adjusted Cooling Design Air Flow Rate [m3/s] 0.82609
492 AirLoopHVAC SAC_EMPLOYEELOUNGE Adjusted Main Design Air Flow Rate [m3/s] 0.82609
493 AirLoopHVAC SAC_EMPLOYEELOUNGE User Heating Air Flow Ratio [] 1.00000
494 AirLoopHVAC SAC_EMPLOYEELOUNGE Calculated Heating Air Flow Ratio [] 1.00000
495 AirLoopHVAC SAC_EXERCISECENTER Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.15820
496 AirLoopHVAC SAC_EXERCISECENTER Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.15820
497 AirLoopHVAC SAC_EXERCISECENTER Sum of Air Terminal Maximum Flow Rates [m3/s] 0.15820
498 AirLoopHVAC SAC_EXERCISECENTER Adjusted Heating Design Air Flow Rate [m3/s] 0.15820
499 AirLoopHVAC SAC_EXERCISECENTER Adjusted Cooling Design Air Flow Rate [m3/s] 0.15820
500 AirLoopHVAC SAC_EXERCISECENTER Adjusted Main Design Air Flow Rate [m3/s] 0.15820
501 AirLoopHVAC SAC_EXERCISECENTER User Heating Air Flow Ratio [] 1.00000
502 AirLoopHVAC SAC_EXERCISECENTER Calculated Heating Air Flow Ratio [] 1.00000
503 AirLoopHVAC SAC_RESTROOM Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 8.28201E-002
504 AirLoopHVAC SAC_RESTROOM Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 8.28201E-002
505 AirLoopHVAC SAC_RESTROOM Sum of Air Terminal Maximum Flow Rates [m3/s] 8.28201E-002
506 AirLoopHVAC SAC_RESTROOM Adjusted Heating Design Air Flow Rate [m3/s] 8.28201E-002
507 AirLoopHVAC SAC_RESTROOM Adjusted Cooling Design Air Flow Rate [m3/s] 8.28201E-002
508 AirLoopHVAC SAC_RESTROOM Adjusted Main Design Air Flow Rate [m3/s] 8.28201E-002
509 AirLoopHVAC SAC_RESTROOM User Heating Air Flow Ratio [] 1.00000
510 AirLoopHVAC SAC_RESTROOM Calculated Heating Air Flow Ratio [] 1.00000
511 AirLoopHVAC SAC_FRONTOFFICE Design Supply Air Flow Rate [m3/s] 0.40387
512 AirLoopHVAC SAC_FRONTLOUNGE Design Supply Air Flow Rate [m3/s] 1.02614
513 AirLoopHVAC SAC_MEETINGROOM Design Supply Air Flow Rate [m3/s] 0.46133
514 AirLoopHVAC SAC_EMPLOYEELOUNGE Design Supply Air Flow Rate [m3/s] 0.82609
515 AirLoopHVAC SAC_EXERCISECENTER Design Supply Air Flow Rate [m3/s] 0.15820
516 AirLoopHVAC SAC_RESTROOM Design Supply Air Flow Rate [m3/s] 8.28201E-002
517 Controller:OutdoorAir SAC_FRONTOFFICE_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.40387
518 Controller:OutdoorAir SAC_FRONTOFFICE_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.33542E-002
519 Fan:SystemModel SAC_FRONTOFFICE_ADDAQ SUPPLY FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.40387
520 Fan:SystemModel SAC_FRONTOFFICE_ADDAQ SUPPLY FAN Design Electric Power Consumption [W] 452.37736
521 AirLoopHVAC:UnitarySystem SAC_FRONTOFFICE_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.40387
522 AirLoopHVAC:UnitarySystem SAC_FRONTOFFICE_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.40387
523 AirLoopHVAC:UnitarySystem SAC_FRONTOFFICE_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.40387
524 AirLoopHVAC:UnitarySystem SAC_FRONTOFFICE_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.40387
525 Coil:Cooling:DX:MultiSpeed SAC_FRONTOFFICE COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.40387
526 Coil:Cooling:DX:MultiSpeed SAC_FRONTOFFICE COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.20193
527 Coil:Cooling:DX:MultiSpeed SAC_FRONTOFFICE COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.26925
528 Coil:Cooling:DX:MultiSpeed SAC_FRONTOFFICE COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 7988.38000
529 Coil:Cooling:DX:MultiSpeed SAC_FRONTOFFICE COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 3994.19000
530 Coil:Cooling:DX:MultiSpeed SAC_FRONTOFFICE COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.78069
531 Coil:Cooling:DX:MultiSpeed SAC_FRONTOFFICE COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.78069
532 AirLoopHVAC:UnitarySystem SAC_FRONTOFFICE_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 7988.38000
533 AirLoopHVAC:UnitarySystem SAC_FRONTOFFICE_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 12264.01195
534 AirLoopHVAC:UnitarySystem SAC_FRONTOFFICE_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
535 AirLoopHVAC:UnitarySystem SAC_FRONTOFFICE_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
536 Coil:Heating:Fuel SAC_FRONTOFFICE HEATING COIL Design Size Nominal Capacity [W] 12264.01195
537 Controller:OutdoorAir SAC_FRONTLOUNGE_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.02614
538 Fan:SystemModel SAC_FRONTLOUNGE_ADDAQ SUPPLY FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.02614
539 Fan:SystemModel SAC_FRONTLOUNGE_ADDAQ SUPPLY FAN Design Electric Power Consumption [W] 1136.09727
540 AirLoopHVAC:UnitarySystem SAC_FRONTLOUNGE_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.02614
541 AirLoopHVAC:UnitarySystem SAC_FRONTLOUNGE_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.02614
542 AirLoopHVAC:UnitarySystem SAC_FRONTLOUNGE_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.02614
543 AirLoopHVAC:UnitarySystem SAC_FRONTLOUNGE_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.67725
544 Coil:Cooling:DX:MultiSpeed SAC_FRONTLOUNGE COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.02614
545 Coil:Cooling:DX:MultiSpeed SAC_FRONTLOUNGE COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.51307
546 Coil:Cooling:DX:MultiSpeed SAC_FRONTLOUNGE COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.68409
547 Coil:Cooling:DX:MultiSpeed SAC_FRONTLOUNGE COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 23116.92000
548 Coil:Cooling:DX:MultiSpeed SAC_FRONTLOUNGE COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 11558.46000
549 Coil:Cooling:DX:MultiSpeed SAC_FRONTLOUNGE COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.73215
550 Coil:Cooling:DX:MultiSpeed SAC_FRONTLOUNGE COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.73215
551 AirLoopHVAC:UnitarySystem SAC_FRONTLOUNGE_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 23116.92000
552 AirLoopHVAC:UnitarySystem SAC_FRONTLOUNGE_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 35327.96054
553 AirLoopHVAC:UnitarySystem SAC_FRONTLOUNGE_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
554 AirLoopHVAC:UnitarySystem SAC_FRONTLOUNGE_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
555 Coil:Heating:Fuel SAC_FRONTLOUNGE HEATING COIL Design Size Nominal Capacity [W] 35327.96054
556 Controller:OutdoorAir SAC_MEETINGROOM_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.46133
557 Controller:OutdoorAir SAC_MEETINGROOM_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.12594
558 Fan:SystemModel SAC_MEETINGROOM_ADDAQ SUPPLY FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.46133
559 Fan:SystemModel SAC_MEETINGROOM_ADDAQ SUPPLY FAN Design Electric Power Consumption [W] 516.74463
560 AirLoopHVAC:UnitarySystem SAC_MEETINGROOM_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.46133
561 AirLoopHVAC:UnitarySystem SAC_MEETINGROOM_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.46133
562 AirLoopHVAC:UnitarySystem SAC_MEETINGROOM_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.46133
563 AirLoopHVAC:UnitarySystem SAC_MEETINGROOM_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.46133
564 Coil:Cooling:DX:MultiSpeed SAC_MEETINGROOM COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.46133
565 Coil:Cooling:DX:MultiSpeed SAC_MEETINGROOM COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.23067
566 Coil:Cooling:DX:MultiSpeed SAC_MEETINGROOM COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.30755
567 Coil:Cooling:DX:MultiSpeed SAC_MEETINGROOM COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 11416.48000
568 Coil:Cooling:DX:MultiSpeed SAC_MEETINGROOM COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 5708.24000
569 Coil:Cooling:DX:MultiSpeed SAC_MEETINGROOM COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.70293
570 Coil:Cooling:DX:MultiSpeed SAC_MEETINGROOM COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.70293
571 AirLoopHVAC:UnitarySystem SAC_MEETINGROOM_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 11416.48000
572 AirLoopHVAC:UnitarySystem SAC_MEETINGROOM_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 16933.96278
573 AirLoopHVAC:UnitarySystem SAC_MEETINGROOM_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
574 AirLoopHVAC:UnitarySystem SAC_MEETINGROOM_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
575 Coil:Heating:Fuel SAC_MEETINGROOM HEATING COIL Design Size Nominal Capacity [W] 16933.96278
576 Controller:OutdoorAir SAC_EMPLOYEELOUNGE_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.82609
577 Controller:OutdoorAir SAC_EMPLOYEELOUNGE_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 5.24145E-002
578 Fan:SystemModel SAC_EMPLOYEELOUNGE_ADDAQ SUPPLY FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.82609
579 Fan:SystemModel SAC_EMPLOYEELOUNGE_ADDAQ SUPPLY FAN Design Electric Power Consumption [W] 914.61297
580 AirLoopHVAC:UnitarySystem SAC_EMPLOYEELOUNGE_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.82609
581 AirLoopHVAC:UnitarySystem SAC_EMPLOYEELOUNGE_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.82609
582 AirLoopHVAC:UnitarySystem SAC_EMPLOYEELOUNGE_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.82609
583 AirLoopHVAC:UnitarySystem SAC_EMPLOYEELOUNGE_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.82609
584 Coil:Cooling:DX:MultiSpeed SAC_EMPLOYEELOUNGE COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.82609
585 Coil:Cooling:DX:MultiSpeed SAC_EMPLOYEELOUNGE COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.41305
586 Coil:Cooling:DX:MultiSpeed SAC_EMPLOYEELOUNGE COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.55073
587 Coil:Cooling:DX:MultiSpeed SAC_EMPLOYEELOUNGE COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 14670.50000
588 Coil:Cooling:DX:MultiSpeed SAC_EMPLOYEELOUNGE COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 7335.25000
589 Coil:Cooling:DX:MultiSpeed SAC_EMPLOYEELOUNGE COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80070
590 Coil:Cooling:DX:MultiSpeed SAC_EMPLOYEELOUNGE COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80070
591 AirLoopHVAC:UnitarySystem SAC_EMPLOYEELOUNGE_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 14670.50000
592 AirLoopHVAC:UnitarySystem SAC_EMPLOYEELOUNGE_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 20871.36572
593 AirLoopHVAC:UnitarySystem SAC_EMPLOYEELOUNGE_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
594 AirLoopHVAC:UnitarySystem SAC_EMPLOYEELOUNGE_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
595 Coil:Heating:Fuel SAC_EMPLOYEELOUNGE HEATING COIL Design Size Nominal Capacity [W] 20871.36572
596 Controller:OutdoorAir SAC_EXERCISECENTER_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.15820
597 Controller:OutdoorAir SAC_EXERCISECENTER_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 7.60119E-002
598 Fan:SystemModel SAC_EXERCISECENTER_ADDAQ SUPPLY FAN Design Size Design Maximum Air Flow Rate [m3/s] 0.15820
599 Fan:SystemModel SAC_EXERCISECENTER_ADDAQ SUPPLY FAN Design Electric Power Consumption [W] 177.19648
600 AirLoopHVAC:UnitarySystem SAC_EXERCISECENTER_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 0.15820
601 AirLoopHVAC:UnitarySystem SAC_EXERCISECENTER_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 0.15820
602 AirLoopHVAC:UnitarySystem SAC_EXERCISECENTER_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 0.15820
603 AirLoopHVAC:UnitarySystem SAC_EXERCISECENTER_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.15820
604 Coil:Cooling:DX:MultiSpeed SAC_EXERCISECENTER COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 0.15820
605 Coil:Cooling:DX:MultiSpeed SAC_EXERCISECENTER COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 7.90979E-002
606 Coil:Cooling:DX:MultiSpeed SAC_EXERCISECENTER COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.10547
607 Coil:Cooling:DX:MultiSpeed SAC_EXERCISECENTER COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 3848.78000
608 Coil:Cooling:DX:MultiSpeed SAC_EXERCISECENTER COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 1924.39000
609 Coil:Cooling:DX:MultiSpeed SAC_EXERCISECENTER COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.70815
610 Coil:Cooling:DX:MultiSpeed SAC_EXERCISECENTER COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.70815
611 AirLoopHVAC:UnitarySystem SAC_EXERCISECENTER_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 3848.78000
612 AirLoopHVAC:UnitarySystem SAC_EXERCISECENTER_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 7599.14934
613 AirLoopHVAC:UnitarySystem SAC_EXERCISECENTER_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
614 AirLoopHVAC:UnitarySystem SAC_EXERCISECENTER_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
615 Coil:Heating:Fuel SAC_EXERCISECENTER HEATING COIL Design Size Nominal Capacity [W] 7599.14934
616 Controller:OutdoorAir SAC_RESTROOM_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.28201E-002
617 Controller:OutdoorAir SAC_RESTROOM_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.00000
618 Fan:SystemModel SAC_RESTROOM_ADDAQ SUPPLY FAN Design Size Design Maximum Air Flow Rate [m3/s] 8.28201E-002
619 Fan:SystemModel SAC_RESTROOM_ADDAQ SUPPLY FAN Design Electric Power Consumption [W] 92.76743
620 AirLoopHVAC:UnitarySystem SAC_RESTROOM_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 8.28201E-002
621 AirLoopHVAC:UnitarySystem SAC_RESTROOM_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 8.28201E-002
622 AirLoopHVAC:UnitarySystem SAC_RESTROOM_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 8.28201E-002
623 AirLoopHVAC:UnitarySystem SAC_RESTROOM_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 8.28201E-002
624 Coil:Cooling:DX:MultiSpeed SAC_RESTROOM COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 8.28201E-002
625 Coil:Cooling:DX:MultiSpeed SAC_RESTROOM COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 4.14100E-002
626 Coil:Cooling:DX:MultiSpeed SAC_RESTROOM COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 5.52134E-002
627 Coil:Cooling:DX:MultiSpeed SAC_RESTROOM COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 1370.97000
628 Coil:Cooling:DX:MultiSpeed SAC_RESTROOM COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 685.48500
629 Coil:Cooling:DX:MultiSpeed SAC_RESTROOM COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.80066
630 Coil:Cooling:DX:MultiSpeed SAC_RESTROOM COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.80066
631 AirLoopHVAC:UnitarySystem SAC_RESTROOM_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 1370.97000
632 AirLoopHVAC:UnitarySystem SAC_RESTROOM_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 1805.54266
633 AirLoopHVAC:UnitarySystem SAC_RESTROOM_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
634 AirLoopHVAC:UnitarySystem SAC_RESTROOM_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
635 Coil:Heating:Fuel SAC_RESTROOM HEATING COIL Design Size Nominal Capacity [W] 1805.54266
636 PlantLoop SWHSYSSHOWER Maximum Loop Flow Rate [m3/s] 1.79949E-004
637 PlantLoop SWHSYSSHOWER Plant Loop Volume [m3] 2.15939E-002
638 Pump:ConstantSpeed SWHSYSSHOWER PUMP Design Flow Rate [m3/s] 1.79949E-004
639 Pump:ConstantSpeed SWHSYSSHOWER PUMP Design Power Consumption [W] 8.11290
640 WaterHeater:Mixed SWH SHOWER WATER HEATER Use Side Design Flow Rate [m3/s] 1.79949E-004
641 PlantLoop SWHSYSLAUNDRY Maximum Loop Flow Rate [m3/s] 1.29330E-004
642 PlantLoop SWHSYSLAUNDRY Plant Loop Volume [m3] 1.55196E-002
643 Pump:ConstantSpeed SWHSYSLAUNDRY PUMP Design Flow Rate [m3/s] 1.29330E-004
644 Pump:ConstantSpeed SWHSYSLAUNDRY PUMP Design Power Consumption [W] 5.52692E-007
645 WaterHeater:Mixed SWH LAUNDRY WATER HEATER Use Side Design Flow Rate [m3/s] 1.29330E-004


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed CORRIDORFLR1 PTAC PTAC COOLING COIL 39657.7 3.16 10.79 11.43 10.82 10.73
2 Coil:Cooling:DX:SingleSpeed 101 PTAC PTAC COOLING COIL 1891.3 3.08 10.52 11.14 10.54 10.33
3 Coil:Cooling:DX:SingleSpeed 102 PTAC PTAC COOLING COIL 1534.3 3.08 10.52 11.14 10.54 10.33
4 Coil:Cooling:DX:SingleSpeed 103 PTAC PTAC COOLING COIL 2768.3 3.08 10.52 11.14 10.54 10.33
5 Coil:Cooling:DX:SingleSpeed 104 PTAC PTAC COOLING COIL 2879.4 3.08 10.52 11.14 10.54 10.33
6 Coil:Cooling:DX:SingleSpeed 105 PTAC PTAC COOLING COIL 4146.7 3.08 10.52 11.14 10.54 10.33
7 Coil:Cooling:DX:SingleSpeed CORRIDORFLR2 PTAC PTAC COOLING COIL 4131.7 3.08 10.52 11.14 10.54 10.33
8 Coil:Cooling:DX:SingleSpeed 201 PTAC PTAC COOLING COIL 2129.9 3.08 10.52 11.14 10.54 10.33
9 Coil:Cooling:DX:SingleSpeed 202_205 PTAC PTAC COOLING COIL 10987.7 3.08 10.52 11.14 10.54 10.33
10 Coil:Cooling:DX:SingleSpeed 206_208 PTAC PTAC COOLING COIL 9082.7 3.08 10.52 11.14 10.54 10.33
11 Coil:Cooling:DX:SingleSpeed 209_212 PTAC PTAC COOLING COIL 10141.6 3.08 10.52 11.14 10.54 10.33
12 Coil:Cooling:DX:SingleSpeed 213 PTAC PTAC COOLING COIL 2787.5 3.08 10.52 11.14 10.54 10.33
13 Coil:Cooling:DX:SingleSpeed 214 PTAC PTAC COOLING COIL 3124.7 3.08 10.52 11.14 10.54 10.33
14 Coil:Cooling:DX:SingleSpeed 215_218 PTAC PTAC COOLING COIL 30734.6 3.08 10.52 11.14 10.54 10.33
15 Coil:Cooling:DX:SingleSpeed 219 PTAC PTAC COOLING COIL 16367.5 3.08 10.52 11.14 10.54 10.33
16 Coil:Cooling:DX:SingleSpeed 220_223 PTAC PTAC COOLING COIL 10412.9 3.08 10.52 11.14 10.54 10.33
17 Coil:Cooling:DX:SingleSpeed 224 PTAC PTAC COOLING COIL 2975.9 3.08 10.52 11.14 10.54 10.33
18 Coil:Cooling:DX:SingleSpeed CORRIDORFLR3 PTAC PTAC COOLING COIL 1865.9 3.25 11.10 11.77 11.13 11.20
19 Coil:Cooling:DX:SingleSpeed 301 PTAC PTAC COOLING COIL 1554.8 3.08 10.52 11.14 10.54 10.33
20 Coil:Cooling:DX:SingleSpeed 302_305 PTAC PTAC COOLING COIL 5015.5 3.08 10.52 11.14 10.54 10.33
21 Coil:Cooling:DX:SingleSpeed 306_308 PTAC PTAC COOLING COIL 4561.8 3.08 10.52 11.14 10.54 10.33
22 Coil:Cooling:DX:SingleSpeed 309_312 PTAC PTAC COOLING COIL 9666.8 3.08 10.52 11.14 10.54 10.33
23 Coil:Cooling:DX:SingleSpeed 313 PTAC PTAC COOLING COIL 1716.2 3.08 10.52 11.14 10.54 10.33
24 Coil:Cooling:DX:SingleSpeed 314 PTAC PTAC COOLING COIL 2700.9 3.08 10.52 11.14 10.54 10.33
25 Coil:Cooling:DX:SingleSpeed 315_318 PTAC PTAC COOLING COIL 11885.6 3.08 10.52 11.14 10.54 10.33
26 Coil:Cooling:DX:SingleSpeed 319 PTAC PTAC COOLING COIL 2806.6 3.08 10.52 11.14 10.54 10.33
27 Coil:Cooling:DX:SingleSpeed 320_323 PTAC PTAC COOLING COIL 9311.2 3.08 10.52 11.14 10.54 10.33
28 Coil:Cooling:DX:SingleSpeed 324 PTAC PTAC COOLING COIL 1630.5 3.08 10.52 11.14 10.54 10.33
29 Coil:Cooling:DX:SingleSpeed CORRIDORFLR4 PTAC PTAC COOLING COIL 2757.8 3.20 10.92 11.57 10.95 10.92
30 Coil:Cooling:DX:SingleSpeed 401 PTAC PTAC COOLING COIL 3314.7 3.08 10.52 11.14 10.54 10.33
31 Coil:Cooling:DX:SingleSpeed 402_405 PTAC PTAC COOLING COIL 6768.1 3.08 10.52 11.14 10.54 10.33
32 Coil:Cooling:DX:SingleSpeed 406_408 PTAC PTAC COOLING COIL 6080.5 3.08 10.52 11.14 10.54 10.33
33 Coil:Cooling:DX:SingleSpeed 409_412 PTAC PTAC COOLING COIL 12008.0 3.08 10.52 11.14 10.54 10.33
34 Coil:Cooling:DX:SingleSpeed 413 PTAC PTAC COOLING COIL 2408.1 3.08 10.52 11.14 10.54 10.33
35 Coil:Cooling:DX:SingleSpeed 414 PTAC PTAC COOLING COIL 2101.1 3.08 10.52 11.14 10.54 10.33
36 Coil:Cooling:DX:SingleSpeed 415_418 PTAC PTAC COOLING COIL 11871.6 3.08 10.52 11.14 10.54 10.33
37 Coil:Cooling:DX:SingleSpeed 419 PTAC PTAC COOLING COIL 3219.5 3.08 10.52 11.14 10.54 10.33
38 Coil:Cooling:DX:SingleSpeed 420_423 PTAC PTAC COOLING COIL 10993.1 3.08 10.52 11.14 10.54 10.33
39 Coil:Cooling:DX:SingleSpeed 424 PTAC PTAC COOLING COIL 3145.9 3.08 10.52 11.14 10.54 10.33
40 Coil:Cooling:DX:MultiSpeed SAC_FRONTOFFICE COOLING COIL 7674.8     12.61 12.32  
41 Coil:Cooling:DX:MultiSpeed SAC_FRONTLOUNGE COOLING COIL 22319.7     12.06 11.79  
42 Coil:Cooling:DX:MultiSpeed SAC_MEETINGROOM COOLING COIL 11057.9     13.11 12.81  
43 Coil:Cooling:DX:MultiSpeed SAC_EMPLOYEELOUNGE COOLING COIL 14029.3     12.34 12.06  
44 Coil:Cooling:DX:MultiSpeed SAC_EXERCISECENTER COOLING COIL 3725.8     13.07 12.78  
45 Coil:Cooling:DX:MultiSpeed SAC_RESTROOM COOLING COIL 1306.7     12.15 11.88  


Zone Surfaces

Zone Name # Surfaces
1 REARSTAIRSFLR1 7
2 CORRIDORFLR1 33
3 REARSTORAGEFLR1 6
4 FRONTLOUNGEFLR1 12
5 RESTROOMFLR1 6
6 MEETINGROOMFLR1 10
7 MECHANICALROOMFLR1 6
8 GUESTROOM101 7
9 GUESTROOM102 7
10 GUESTROOM103 7
11 GUESTROOM104 7
12 GUESTROOM105 7
13 EMPLOYEELOUNGEFLR1 7
14 LAUNDRYROOMFLR1 10
15 ELEVATORCOREFLR1 6
16 EXERCISECENTERFLR1 7
17 FRONTOFFICEFLR1 11
18 FRONTSTAIRSFLR1 7
19 FRONTSTORAGEFLR1 6
20 REARSTAIRSFLR2 6
21 CORRIDORFLR2 24
22 REARSTORAGEFLR2 6
23 GUESTROOM201 7
24 GUESTROOM202_205 10
25 GUESTROOM206_208 11
26 GUESTROOM209_212 13
27 GUESTROOM213 7
28 GUESTROOM214 7
29 GUESTROOM215_218 12
30 ELEVATORCOREFLR2 6
31 GUESTROOM219 7
32 GUESTROOM220_223 11
33 GUESTROOM224 7
34 FRONTSTORAGEFLR2 6
35 FRONTSTAIRSFLR2 6
36 REARSTAIRSFLR3 6
37 CORRIDORFLR3 24
38 REARSTORAGEFLR3 6
39 GUESTROOM301 7
40 GUESTROOM302_305 10
41 GUESTROOM306_308 9
42 GUESTROOM309_312 10
43 GUESTROOM313 7
44 GUESTROOM314 7
45 GUESTROOM315_318 10
46 ELEVATORCOREFLR3 6
47 GUESTROOM319 7
48 GUESTROOM320_323 10
49 GUESTROOM324 7
50 FRONTSTORAGEFLR3 6
51 FRONTSTAIRSFLR3 6
52 REARSTAIRSFLR4 6
53 CORRIDORFLR4 24
54 REARSTORAGEFLR4 6
55 GUESTROOM401 7
56 GUESTROOM402_405 10
57 GUESTROOM406_408 9
58 GUESTROOM409_412 10
59 GUESTROOM413 7
60 GUESTROOM414 7
61 GUESTROOM415_418 10
62 ELEVATORCOREFLR4 6
63 GUESTROOM419 7
64 GUESTROOM420_423 10
65 GUESTROOM424 7
66 FRONTSTORAGEFLR4 6
67 FRONTSTAIRSFLR4 6


Shading Surfaces

Number of Shading Surfaces # Surfaces
1 Number of Shading Surfaces 2


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 W_REARSTAIRSFLR1_2_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
2 W_REARSTAIRSFLR1_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   6.23 8.18 6.23 90.00 90.00 2.44 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
3 W_REARSTAIRSFLR1_3_0_0_DOOR Door W_REARSTAIRSFLR1_3_0_0 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
4 P_REARSTAIRSFLR1_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_GUESTROOM104_10002_0_10001 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 P_REARSTAIRSFLR1_5_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.18 8.18 8.18 270.00 90.00 2.44 3.35 0.00 P_CORRIDORFLR1_10003_0_10002 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
6 S_REARSTAIRSFLR1_0_0_0 Floor   CTF - ConductionTransferFunction S_REARSTAIRSFLR1_0_0_0_FFACTOR 0.506 0.451   20.07 20.07 20.07 90.00 180.00 2.44 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
7 C_REARSTAIRSFLR1_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   20.07 20.07 20.07 270.00 0.00 2.44 8.23 0.00 F_REARSTAIRSFLR2_10001_0_10000 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 P_CORRIDORFLR1_10003_0_10002 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.18 8.18 8.18 90.00 90.00 2.44 3.35 0.00 P_REARSTAIRSFLR1_5_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
9 W_CORRIDORFLR1_2_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   3.44 6.13 3.44 180.00 90.00 1.83 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
10 W_CORRIDORFLR1_2_0_0_0_0 Window W_CORRIDORFLR1_2_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 2.69 2.69 2.69 180.00 90.00 1.14 2.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
11 P_CORRIDORFLR1_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 90.00 90.00 3.96 3.35 0.00 P_GUESTROOM104_10007_0_10005 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
12 P_CORRIDORFLR1_5_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 90.00 90.00 3.96 3.35 0.00 P_GUESTROOM105_10008_0_10006 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
13 P_CORRIDORFLR1_6_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 90.00 90.00 3.96 3.35 0.00 P_EMPLOYEELOUNGEFLR1_10009_0_10007 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 P_CORRIDORFLR1_7_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   39.86 39.86 39.86 90.00 90.00 11.89 3.35 0.00 P_LAUNDRYROOMFLR1_10010_0_10008 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 P_CORRIDORFLR1_8_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.13 6.13 6.13 90.00 90.00 1.83 3.35 0.00 P_ELEVATORCOREFLR1_10011_0_10009 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
16 P_CORRIDORFLR1_9_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_ELEVATORCOREFLR1_10012_0_10010 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
17 W_CORRIDORFLR1_10_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   8.27 10.22 8.27 90.00 90.00 3.05 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 W_CORRIDORFLR1_10_0_0_DOOR Door W_CORRIDORFLR1_10_0_0 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
19 P_CORRIDORFLR1_11_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_EXERCISECENTERFLR1_10013_0_10011 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 P_CORRIDORFLR1_12_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 90.00 90.00 3.96 3.35 0.00 P_EXERCISECENTERFLR1_10014_0_10012 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
21 P_CORRIDORFLR1_13_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   53.14 53.14 53.14 90.00 90.00 15.85 3.35 0.00 P_FRONTOFFICEFLR1_10015_0_10013 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 P_CORRIDORFLR1_14_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.11 5.11 5.11 90.00 90.00 1.52 3.35 0.00 P_FRONTSTORAGEFLR1_10016_0_10014 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 P_CORRIDORFLR1_15_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.18 8.18 8.18 90.00 90.00 2.44 3.35 0.00 P_FRONTSTAIRSFLR1_10017_0_10015 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
24 W_CORRIDORFLR1_16_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   1.69 6.13 1.69 0.00 90.00 1.83 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.96 3.65E-002 4
25 D_CORRIDORFLR1_16_0_0_0_0 Window W_CORRIDORFLR1_16_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 4.44 4.44 4.44 0.00 90.00 1.82 2.43 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.83 0.17 4
26 P_CORRIDORFLR1_17_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.43 66.43 66.43 270.00 90.00 19.81 3.35 0.00 P_FRONTLOUNGEFLR1_10018_0_10016 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 P_CORRIDORFLR1_18_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 270.00 90.00 3.96 3.35 0.00 P_RESTROOMFLR1_10019_0_10017 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 P_CORRIDORFLR1_19_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_RESTROOMFLR1_10020_0_10018 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 W_CORRIDORFLR1_20_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   7.53 10.22 7.53 270.00 90.00 3.05 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
30 W_CORRIDORFLR1_20_0_0_0_0 Window W_CORRIDORFLR1_20_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 2.69 2.69 2.69 270.00 90.00 1.14 2.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
31 P_CORRIDORFLR1_21_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_MEETINGROOMFLR1_10021_0_10019 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
32 P_CORRIDORFLR1_22_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   32.70 32.70 32.70 270.00 90.00 9.75 3.35 0.00 P_MEETINGROOMFLR1_10022_0_10020 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 P_CORRIDORFLR1_23_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 270.00 90.00 3.96 3.35 0.00 P_MECHANICALROOMFLR1_10023_0_10021 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 P_CORRIDORFLR1_24_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 270.00 90.00 3.96 3.35 0.00 P_GUESTROOM101_10024_0_10022 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 P_CORRIDORFLR1_25_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 270.00 90.00 3.96 3.35 0.00 P_GUESTROOM102_10025_0_10023 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
36 P_CORRIDORFLR1_26_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 270.00 90.00 3.96 3.35 0.00 P_GUESTROOM103_10026_0_10024 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
37 P_CORRIDORFLR1_27_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.18 8.18 8.18 270.00 90.00 2.44 3.35 0.00 P_REARSTORAGEFLR1_10027_0_10025 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
38 S_CORRIDORFLR1_0_0_0 Floor   CTF - ConductionTransferFunction S_CORRIDORFLR1_0_0_0_FFACTOR 5.772E-002 5.692E-002   150.51 150.51 150.51 90.00 180.00 12.27 12.27 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
39 C_CORRIDORFLR1_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   125.42 125.42 125.42 270.00 0.00 11.20 11.20 0.00 F_CORRIDORFLR2_10004_0_10003 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 8
40 C_CORRIDORFLR1_1_1_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   25.09 25.09 25.09 270.00 0.00 3.05 8.23 0.00 F_GUESTROOM206_208_10005_0_10004 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
41 P_REARSTORAGEFLR1_10027_0_10025 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.18 8.18 8.18 90.00 90.00 2.44 3.35 0.00 P_CORRIDORFLR1_27_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 W_REARSTORAGEFLR1_2_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 P_REARSTORAGEFLR1_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_GUESTROOM103_10030_0_10027 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 W_REARSTORAGEFLR1_5_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   8.18 8.18 8.18 270.00 90.00 2.44 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
45 S_REARSTORAGEFLR1_0_0_0 Floor   CTF - ConductionTransferFunction S_REARSTORAGEFLR1_0_0_0_FFACTOR 0.506 0.451   20.07 20.07 20.07 90.00 180.00 2.44 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
46 C_REARSTORAGEFLR1_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   20.07 20.07 20.07 270.00 0.00 2.44 8.23 0.00 F_REARSTORAGEFLR2_10028_0_10026 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
47 P_FRONTLOUNGEFLR1_10018_0_10016 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.43 66.43 66.43 90.00 90.00 19.81 3.35 0.00 P_CORRIDORFLR1_17_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
48 P_FRONTLOUNGEFLR1_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_RESTROOMFLR1_10033_0_10030 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
49 W_FRONTLOUNGEFLR1_4_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.68 0.32 4
50 W_FRONTLOUNGEFLR1_5_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   51.60 66.43 51.60 270.00 90.00 19.81 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
51 W_FRONTLOUNGEFLR1_5_0_0_0_0 Window W_FRONTLOUNGEFLR1_5_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 2.97 2.97 2.97 270.00 90.00 2.05 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 W_FRONTLOUNGEFLR1_5_0_0_0_1 Window W_FRONTLOUNGEFLR1_5_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 2.97 2.97 2.97 270.00 90.00 2.05 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 W_FRONTLOUNGEFLR1_5_0_0_0_2 Window W_FRONTLOUNGEFLR1_5_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 2.97 2.97 2.97 270.00 90.00 2.05 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 W_FRONTLOUNGEFLR1_5_0_0_0_3 Window W_FRONTLOUNGEFLR1_5_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 2.97 2.97 2.97 270.00 90.00 2.05 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 W_FRONTLOUNGEFLR1_5_0_0_0_4 Window W_FRONTLOUNGEFLR1_5_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 2.97 2.97 2.97 270.00 90.00 2.05 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 S_FRONTLOUNGEFLR1_0_0_0 Floor   CTF - ConductionTransferFunction S_FRONTLOUNGEFLR1_0_0_0_FFACTOR 0.155 0.150   163.06 163.06 163.06 90.00 180.00 19.81 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
57 C_FRONTLOUNGEFLR1_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM201_10031_0_10028 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
58 C_FRONTLOUNGEFLR1_1_1_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   130.45 130.45 130.45 270.00 0.00 15.85 8.23 0.00 F_GUESTROOM202_205_10032_0_10029 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
59 P_RESTROOMFLR1_10019_0_10017 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 90.00 90.00 3.96 3.35 0.00 P_CORRIDORFLR1_18_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 P_RESTROOMFLR1_10020_0_10018 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_CORRIDORFLR1_19_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 P_RESTROOMFLR1_10033_0_10030 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_FRONTLOUNGEFLR1_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
62 W_RESTROOMFLR1_5_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   13.29 13.29 13.29 270.00 90.00 3.96 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
63 S_RESTROOMFLR1_0_0_0 Floor   CTF - ConductionTransferFunction S_RESTROOMFLR1_0_0_0_FFACTOR 0.109 0.106   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
64 C_RESTROOMFLR1_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM206_208_10035_0_10031 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
65 P_MEETINGROOMFLR1_10021_0_10019 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_CORRIDORFLR1_21_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
66 P_MEETINGROOMFLR1_10022_0_10020 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   32.70 32.70 32.70 90.00 90.00 9.75 3.35 0.00 P_CORRIDORFLR1_22_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
67 P_MEETINGROOMFLR1_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_MECHANICALROOMFLR1_10041_0_10034 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
68 W_MEETINGROOMFLR1_5_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   27.77 32.70 27.77 270.00 90.00 9.75 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 W_MEETINGROOMFLR1_5_0_0_0_0 Window W_MEETINGROOMFLR1_5_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 W_MEETINGROOMFLR1_5_0_0_0_1 Window W_MEETINGROOMFLR1_5_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 W_MEETINGROOMFLR1_5_0_0_0_2 Window W_MEETINGROOMFLR1_5_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 S_MEETINGROOMFLR1_0_0_0 Floor   CTF - ConductionTransferFunction S_MEETINGROOMFLR1_0_0_0_FFACTOR 0.109 0.106   80.27 80.27 80.27 90.00 180.00 9.75 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
73 C_MEETINGROOMFLR1_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   47.66 47.66 47.66 270.00 0.00 5.79 8.23 0.00 F_GUESTROOM206_208_10039_0_10032 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
74 C_MEETINGROOMFLR1_1_1_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM209_212_10040_0_10033 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
75 P_MECHANICALROOMFLR1_10023_0_10021 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 90.00 90.00 3.96 3.35 0.00 P_CORRIDORFLR1_23_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 P_MECHANICALROOMFLR1_10041_0_10034 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_MEETINGROOMFLR1_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 P_MECHANICALROOMFLR1_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_GUESTROOM101_10045_0_10036 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 W_MECHANICALROOMFLR1_5_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   13.29 13.29 13.29 270.00 90.00 3.96 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
79 S_MECHANICALROOMFLR1_0_0_0 Floor   CTF - ConductionTransferFunction S_MECHANICALROOMFLR1_0_0_0_FFACTOR 0.109 0.106   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
80 C_MECHANICALROOMFLR1_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM209_212_10044_0_10035 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
81 P_GUESTROOM101_10024_0_10022 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 90.00 90.00 3.96 3.35 0.00 P_CORRIDORFLR1_24_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
82 P_GUESTROOM101_10045_0_10036 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_MECHANICALROOMFLR1_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
83 P_GUESTROOM101_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_GUESTROOM102_10049_0_10038 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
84 W_GUESTROOM101_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_GRD 0.473 0.442   11.64 13.29 11.64 270.00 90.00 3.96 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 W_GUESTROOM101_5_0_0_0_0 Window W_GUESTROOM101_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 S_GUESTROOM101_0_0_0 Floor   CTF - ConductionTransferFunction S_GUESTROOM101_0_0_0_FFACTOR 0.109 0.106   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
87 C_GUESTROOM101_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM209_212_10048_0_10037 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
88 P_GUESTROOM102_10025_0_10023 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 90.00 90.00 3.96 3.35 0.00 P_CORRIDORFLR1_25_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
89 P_GUESTROOM102_10049_0_10038 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_GUESTROOM101_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 P_GUESTROOM102_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_GUESTROOM103_10053_0_10040 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 W_GUESTROOM102_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_GRD 0.473 0.442   11.64 13.29 11.64 270.00 90.00 3.96 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
92 W_GUESTROOM102_5_0_0_0_0 Window W_GUESTROOM102_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
93 S_GUESTROOM102_0_0_0 Floor   CTF - ConductionTransferFunction S_GUESTROOM102_0_0_0_FFACTOR 0.109 0.106   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
94 C_GUESTROOM102_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM209_212_10052_0_10039 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
95 P_GUESTROOM103_10026_0_10024 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 90.00 90.00 3.96 3.35 0.00 P_CORRIDORFLR1_26_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 P_GUESTROOM103_10030_0_10027 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_REARSTORAGEFLR1_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 P_GUESTROOM103_10053_0_10040 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_GUESTROOM102_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 W_GUESTROOM103_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_GRD 0.473 0.442   11.64 13.29 11.64 270.00 90.00 3.96 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 W_GUESTROOM103_5_0_0_0_0 Window W_GUESTROOM103_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
100 S_GUESTROOM103_0_0_0 Floor   CTF - ConductionTransferFunction S_GUESTROOM103_0_0_0_FFACTOR 0.109 0.106   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
101 C_GUESTROOM103_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM213_10056_0_10041 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
102 P_GUESTROOM104_10002_0_10001 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_REARSTAIRSFLR1_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
103 P_GUESTROOM104_10007_0_10005 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 270.00 90.00 3.96 3.35 0.00 P_CORRIDORFLR1_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
104 W_GUESTROOM104_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_GRD 0.473 0.442   11.64 13.29 11.64 90.00 90.00 3.96 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 W_GUESTROOM104_3_0_0_0_0 Window W_GUESTROOM104_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 P_GUESTROOM104_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_GUESTROOM105_10062_0_10043 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 S_GUESTROOM104_0_0_0 Floor   CTF - ConductionTransferFunction S_GUESTROOM104_0_0_0_FFACTOR 0.109 0.106   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 C_GUESTROOM104_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM214_10060_0_10042 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 P_GUESTROOM105_10008_0_10006 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 270.00 90.00 3.96 3.35 0.00 P_CORRIDORFLR1_5_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
110 P_GUESTROOM105_10062_0_10043 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_GUESTROOM104_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 W_GUESTROOM105_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_GRD 0.473 0.442   11.64 13.29 11.64 90.00 90.00 3.96 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 W_GUESTROOM105_3_0_0_0_0 Window W_GUESTROOM105_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 P_GUESTROOM105_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_EMPLOYEELOUNGEFLR1_10066_0_10045 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
114 S_GUESTROOM105_0_0_0 Floor   CTF - ConductionTransferFunction S_GUESTROOM105_0_0_0_FFACTOR 0.109 0.106   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
115 C_GUESTROOM105_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM215_218_10064_0_10044 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
116 P_EMPLOYEELOUNGEFLR1_10009_0_10007 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 270.00 90.00 3.96 3.35 0.00 P_CORRIDORFLR1_6_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 P_EMPLOYEELOUNGEFLR1_10066_0_10045 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_GUESTROOM105_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
118 W_EMPLOYEELOUNGEFLR1_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   11.64 13.29 11.64 90.00 90.00 3.96 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
119 W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 Window W_EMPLOYEELOUNGEFLR1_3_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 P_EMPLOYEELOUNGEFLR1_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_LAUNDRYROOMFLR1_10070_0_10047 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
121 S_EMPLOYEELOUNGEFLR1_0_0_0 Floor   CTF - ConductionTransferFunction S_EMPLOYEELOUNGEFLR1_0_0_0_FFACTOR 0.109 0.106   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
122 C_EMPLOYEELOUNGEFLR1_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM215_218_10068_0_10046 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
123 P_LAUNDRYROOMFLR1_10010_0_10008 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   39.86 39.86 39.86 270.00 90.00 11.89 3.35 0.00 P_CORRIDORFLR1_7_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 P_LAUNDRYROOMFLR1_10070_0_10047 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_EMPLOYEELOUNGEFLR1_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 W_LAUNDRYROOMFLR1_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   34.93 39.86 34.93 90.00 90.00 11.89 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
126 W_LAUNDRYROOMFLR1_3_0_0_0_0 Window W_LAUNDRYROOMFLR1_3_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
127 W_LAUNDRYROOMFLR1_3_0_0_0_1 Window W_LAUNDRYROOMFLR1_3_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 W_LAUNDRYROOMFLR1_3_0_0_0_2 Window W_LAUNDRYROOMFLR1_3_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 P_LAUNDRYROOMFLR1_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_ELEVATORCOREFLR1_10075_0_10050 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 S_LAUNDRYROOMFLR1_0_0_0 Floor   CTF - ConductionTransferFunction S_LAUNDRYROOMFLR1_0_0_0_FFACTOR 0.109 0.106   97.83 97.83 97.83 90.00 180.00 11.89 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
131 C_LAUNDRYROOMFLR1_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   65.22 65.22 65.22 270.00 0.00 7.92 8.23 0.00 F_GUESTROOM215_218_10072_0_10048 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
132 C_LAUNDRYROOMFLR1_1_1_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM219_10073_0_10049 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
133 P_ELEVATORCOREFLR1_10011_0_10009 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.13 6.13 6.13 270.00 90.00 1.83 3.35 0.00 P_CORRIDORFLR1_8_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 P_ELEVATORCOREFLR1_10012_0_10010 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_CORRIDORFLR1_9_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 P_ELEVATORCOREFLR1_10075_0_10050 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_LAUNDRYROOMFLR1_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
136 W_ELEVATORCOREFLR1_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   6.13 6.13 6.13 90.00 90.00 1.83 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 S_ELEVATORCOREFLR1_0_0_0 Floor   CTF - ConductionTransferFunction S_ELEVATORCOREFLR1_0_0_0_FFACTOR 0.109 0.106   15.05 15.05 15.05 90.00 180.00 1.83 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
138 C_ELEVATORCOREFLR1_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   15.05 15.05 15.05 270.00 0.00 1.83 8.23 0.00 F_ELEVATORCOREFLR2_10077_0_10051 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
139 P_EXERCISECENTERFLR1_10013_0_10011 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_CORRIDORFLR1_11_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 P_EXERCISECENTERFLR1_10014_0_10012 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.29 13.29 13.29 270.00 90.00 3.96 3.35 0.00 P_CORRIDORFLR1_12_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 W_EXERCISECENTERFLR1_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   11.64 13.29 11.64 90.00 90.00 3.96 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 W_EXERCISECENTERFLR1_3_0_0_0_0 Window W_EXERCISECENTERFLR1_3_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 P_EXERCISECENTERFLR1_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_FRONTOFFICEFLR1_10083_0_10053 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
144 S_EXERCISECENTERFLR1_0_0_0 Floor   CTF - ConductionTransferFunction S_EXERCISECENTERFLR1_0_0_0_FFACTOR 0.109 0.106   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
145 C_EXERCISECENTERFLR1_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM220_223_10081_0_10052 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
146 P_FRONTOFFICEFLR1_10015_0_10013 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   53.14 53.14 53.14 270.00 90.00 15.85 3.35 0.00 P_CORRIDORFLR1_13_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 P_FRONTOFFICEFLR1_10083_0_10053 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_EXERCISECENTERFLR1_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 W_FRONTOFFICEFLR1_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   46.57 53.14 46.57 90.00 90.00 15.85 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
149 W_FRONTOFFICEFLR1_3_0_0_0_0 Window W_FRONTOFFICEFLR1_3_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
150 W_FRONTOFFICEFLR1_3_0_0_0_1 Window W_FRONTOFFICEFLR1_3_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
151 W_FRONTOFFICEFLR1_3_0_0_0_2 Window W_FRONTOFFICEFLR1_3_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
152 W_FRONTOFFICEFLR1_3_0_0_0_3 Window W_FRONTOFFICEFLR1_3_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.64 1.64 1.64 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
153 P_FRONTOFFICEFLR1_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_FRONTSTORAGEFLR1_10088_0_10056 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 S_FRONTOFFICEFLR1_0_0_0 Floor   CTF - ConductionTransferFunction S_FRONTOFFICEFLR1_0_0_0_FFACTOR 0.109 0.106   130.44 130.44 130.44 90.00 180.00 15.85 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
155 C_FRONTOFFICEFLR1_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   97.83 97.83 97.83 270.00 0.00 11.89 8.23 0.00 F_GUESTROOM220_223_10085_0_10054 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
156 C_FRONTOFFICEFLR1_1_1_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM224_10086_0_10055 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
157 P_FRONTSTAIRSFLR1_10017_0_10015 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   8.18 8.18 8.18 270.00 90.00 2.44 3.35 0.00 P_CORRIDORFLR1_15_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 P_FRONTSTAIRSFLR1_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_FRONTSTORAGEFLR1_10091_0_10058 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
159 W_FRONTSTAIRSFLR1_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   6.22 8.18 6.22 90.00 90.00 2.44 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
160 W_FRONTSTAIRSFLR1_3_0_0_DOOR Door W_FRONTSTAIRSFLR1_3_0_0 CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
161 W_FRONTSTAIRSFLR1_4_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.68 0.32 4
162 S_FRONTSTAIRSFLR1_0_0_0 Floor   CTF - ConductionTransferFunction S_FRONTSTAIRSFLR1_0_0_0_FFACTOR 0.506 0.451   20.07 20.07 20.07 90.00 180.00 2.44 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
163 C_FRONTSTAIRSFLR1_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   20.07 20.07 20.07 270.00 0.00 2.44 8.23 0.00 F_FRONTSTAIRSFLR2_10090_0_10057 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
164 P_FRONTSTORAGEFLR1_10016_0_10014 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.11 5.11 5.11 270.00 90.00 1.52 3.35 0.00 P_CORRIDORFLR1_14_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
165 P_FRONTSTORAGEFLR1_10088_0_10056 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 180.00 90.00 8.23 3.35 0.00 P_FRONTOFFICEFLR1_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
166 P_FRONTSTORAGEFLR1_10091_0_10058 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   27.59 27.59 27.59 0.00 90.00 8.23 3.35 0.00 P_FRONTSTAIRSFLR1_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
167 W_FRONTSTORAGEFLR1_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.473 0.442   5.11 5.11 5.11 90.00 90.00 1.52 3.35 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
168 S_FRONTSTORAGEFLR1_0_0_0 Floor   CTF - ConductionTransferFunction S_FRONTSTORAGEFLR1_0_0_0_FFACTOR 0.109 0.106   12.54 12.54 12.54 90.00 180.00 1.52 8.23 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 C_FRONTSTORAGEFLR1_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   12.54 12.54 12.54 270.00 0.00 1.52 8.23 0.00 F_FRONTSTORAGEFLR2_10093_0_10059 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
170 W_REARSTAIRSFLR2_2_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
171 W_REARSTAIRSFLR2_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   6.69 6.69 6.69 90.00 90.00 2.44 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
172 P_REARSTAIRSFLR2_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM214_10099_0_10061 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
173 P_REARSTAIRSFLR2_5_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 270.00 90.00 2.44 2.74 0.00 P_CORRIDORFLR2_10100_0_10062 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
174 F_REARSTAIRSFLR2_10001_0_10000 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   20.07 20.07 20.07 90.00 180.00 2.44 8.23 0.00 C_REARSTAIRSFLR1_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
175 C_REARSTAIRSFLR2_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   20.07 20.07 20.07 270.00 0.00 2.44 8.23 0.00 F_REARSTAIRSFLR3_10098_0_10060 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
176 P_CORRIDORFLR2_10100_0_10062 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 90.00 90.00 2.44 2.74 0.00 P_REARSTAIRSFLR2_5_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 W_CORRIDORFLR2_2_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   3.71 5.02 3.71 180.00 90.00 1.83 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
178 W_CORRIDORFLR2_2_0_0_0_0 Window W_CORRIDORFLR2_2_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.31 1.31 1.31 180.00 90.00 0.92 1.42 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
179 P_CORRIDORFLR2_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 90.00 90.00 3.96 2.74 0.00 P_GUESTROOM214_10104_0_10064 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
180 P_CORRIDORFLR2_5_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 90.00 90.00 15.85 2.74 0.00 P_GUESTROOM215_218_10105_0_10065 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
181 P_CORRIDORFLR2_6_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 90.00 90.00 3.96 2.74 0.00 P_GUESTROOM219_10106_0_10066 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
182 P_CORRIDORFLR2_7_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.02 5.02 5.02 90.00 90.00 1.83 2.74 0.00 P_ELEVATORCOREFLR2_10107_0_10067 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
183 P_CORRIDORFLR2_8_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_ELEVATORCOREFLR2_10108_0_10068 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 W_CORRIDORFLR2_9_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   8.36 8.36 8.36 90.00 90.00 3.05 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 P_CORRIDORFLR2_10_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM220_223_10109_0_10069 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 P_CORRIDORFLR2_11_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 90.00 90.00 15.85 2.74 0.00 P_GUESTROOM220_223_10110_0_10070 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
187 P_CORRIDORFLR2_12_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 90.00 90.00 3.96 2.74 0.00 P_GUESTROOM224_10111_0_10071 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
188 P_CORRIDORFLR2_13_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.18 4.18 4.18 90.00 90.00 1.52 2.74 0.00 P_FRONTSTORAGEFLR2_10112_0_10072 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
189 P_CORRIDORFLR2_14_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 90.00 90.00 2.44 2.74 0.00 P_FRONTSTAIRSFLR2_10113_0_10073 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
190 W_CORRIDORFLR2_15_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   3.71 5.02 3.71 0.00 90.00 1.83 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 W_CORRIDORFLR2_15_0_0_0_0 Window W_CORRIDORFLR2_15_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.31 1.31 1.31 0.00 90.00 0.92 1.42 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
192 P_CORRIDORFLR2_16_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 270.00 90.00 3.96 2.74 0.00 P_GUESTROOM201_10114_0_10074 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 P_CORRIDORFLR2_17_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 270.00 90.00 15.85 2.74 0.00 P_GUESTROOM202_205_10115_0_10075 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 P_CORRIDORFLR2_18_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   35.12 35.12 35.12 270.00 90.00 12.80 2.74 0.00 P_GUESTROOM206_208_10116_0_10076 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
195 P_CORRIDORFLR2_19_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 270.00 90.00 15.85 2.74 0.00 P_GUESTROOM209_212_10117_0_10077 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
196 P_CORRIDORFLR2_20_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 270.00 90.00 3.96 2.74 0.00 P_GUESTROOM213_10118_0_10078 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
197 P_CORRIDORFLR2_21_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 270.00 90.00 2.44 2.74 0.00 P_REARSTORAGEFLR2_10119_0_10079 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
198 F_CORRIDORFLR2_10004_0_10003 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   125.42 125.42 125.42 90.00 180.00 11.20 11.20 0.00 C_CORRIDORFLR1_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 8
199 C_CORRIDORFLR2_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   125.42 125.42 125.42 270.00 0.00 11.20 11.20 0.00 F_CORRIDORFLR3_10102_0_10063 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 8
200 P_REARSTORAGEFLR2_10119_0_10079 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 90.00 90.00 2.44 2.74 0.00 P_CORRIDORFLR2_21_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 W_REARSTORAGEFLR2_2_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
202 P_REARSTORAGEFLR2_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM213_10123_0_10081 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
203 W_REARSTORAGEFLR2_5_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   6.69 6.69 6.69 270.00 90.00 2.44 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
204 F_REARSTORAGEFLR2_10028_0_10026 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   20.07 20.07 20.07 90.00 180.00 2.44 8.23 0.00 C_REARSTORAGEFLR1_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
205 C_REARSTORAGEFLR2_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   20.07 20.07 20.07 270.00 0.00 2.44 8.23 0.00 F_REARSTORAGEFLR3_10121_0_10080 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 P_GUESTROOM201_10114_0_10074 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 90.00 90.00 3.96 2.74 0.00 P_CORRIDORFLR2_16_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
207 P_GUESTROOM201_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM202_205_10126_0_10083 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
208 W_GUESTROOM201_4_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 W_GUESTROOM201_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   9.22 10.87 9.22 270.00 90.00 3.96 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 W_GUESTROOM201_5_0_0_0_0 Window W_GUESTROOM201_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 F_GUESTROOM201_10031_0_10028 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_FRONTLOUNGEFLR1_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
212 C_GUESTROOM201_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM301_10125_0_10082 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
213 P_GUESTROOM202_205_10115_0_10075 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 90.00 90.00 15.85 2.74 0.00 P_CORRIDORFLR2_17_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 P_GUESTROOM202_205_10126_0_10083 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM201_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
215 P_GUESTROOM202_205_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM206_208_10130_0_10085 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
216 W_GUESTROOM202_205_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   36.88 43.48 36.88 270.00 90.00 15.85 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
217 W_GUESTROOM202_205_5_0_0_0_0 Window W_GUESTROOM202_205_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 W_GUESTROOM202_205_5_0_0_0_1 Window W_GUESTROOM202_205_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 W_GUESTROOM202_205_5_0_0_0_2 Window W_GUESTROOM202_205_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 W_GUESTROOM202_205_5_0_0_0_3 Window W_GUESTROOM202_205_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 F_GUESTROOM202_205_10032_0_10029 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   130.45 130.45 130.45 90.00 180.00 15.85 8.23 0.00 C_FRONTLOUNGEFLR1_1_1_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
222 C_GUESTROOM202_205_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   130.45 130.45 130.45 270.00 0.00 15.85 8.23 0.00 F_GUESTROOM302_305_10129_0_10084 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
223 P_GUESTROOM206_208_10116_0_10076 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   35.12 35.12 35.12 90.00 90.00 12.80 2.74 0.00 P_CORRIDORFLR2_18_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 P_GUESTROOM206_208_10130_0_10085 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM202_205_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 P_GUESTROOM206_208_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM209_212_10137_0_10087 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 W_GUESTROOM206_208_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   28.41 35.12 28.41 270.00 90.00 12.80 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
227 W_GUESTROOM206_208_5_0_0_0_0 Window W_GUESTROOM206_208_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
228 W_GUESTROOM206_208_5_0_0_0_1 Window W_GUESTROOM206_208_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 3.41 3.41 3.41 270.00 90.00 2.36 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
229 W_GUESTROOM206_208_5_0_0_0_2 Window W_GUESTROOM206_208_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
230 F_GUESTROOM206_208_10005_0_10004 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   25.09 25.09 25.09 90.00 180.00 3.05 8.23 0.00 C_CORRIDORFLR1_1_1_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
231 F_GUESTROOM206_208_10035_0_10031 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_RESTROOMFLR1_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
232 F_GUESTROOM206_208_10039_0_10032 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   47.66 47.66 47.66 90.00 180.00 5.79 8.23 0.00 C_MEETINGROOMFLR1_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
233 C_GUESTROOM206_208_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   105.36 105.36 105.36 270.00 0.00 12.80 8.23 0.00 F_GUESTROOM306_308_10136_0_10086 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
234 P_GUESTROOM209_212_10117_0_10077 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 90.00 90.00 15.85 2.74 0.00 P_CORRIDORFLR2_19_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
235 P_GUESTROOM209_212_10137_0_10087 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM206_208_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
236 P_GUESTROOM209_212_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM213_10145_0_10089 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
237 W_GUESTROOM209_212_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   36.88 43.48 36.88 270.00 90.00 15.85 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
238 W_GUESTROOM209_212_5_0_0_0_0 Window W_GUESTROOM209_212_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
239 W_GUESTROOM209_212_5_0_0_0_1 Window W_GUESTROOM209_212_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
240 W_GUESTROOM209_212_5_0_0_0_2 Window W_GUESTROOM209_212_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
241 W_GUESTROOM209_212_5_0_0_0_3 Window W_GUESTROOM209_212_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
242 F_GUESTROOM209_212_10040_0_10033 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_MEETINGROOMFLR1_1_1_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
243 F_GUESTROOM209_212_10044_0_10035 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_MECHANICALROOMFLR1_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
244 F_GUESTROOM209_212_10048_0_10037 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_GUESTROOM101_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
245 F_GUESTROOM209_212_10052_0_10039 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_GUESTROOM102_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
246 C_GUESTROOM209_212_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   130.45 130.45 130.45 270.00 0.00 15.85 8.23 0.00 F_GUESTROOM309_312_10144_0_10088 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
247 P_GUESTROOM213_10118_0_10078 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 90.00 90.00 3.96 2.74 0.00 P_CORRIDORFLR2_20_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
248 P_GUESTROOM213_10123_0_10081 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_REARSTORAGEFLR2_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
249 P_GUESTROOM213_10145_0_10089 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM209_212_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
250 W_GUESTROOM213_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   9.22 10.87 9.22 270.00 90.00 3.96 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
251 W_GUESTROOM213_5_0_0_0_0 Window W_GUESTROOM213_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
252 F_GUESTROOM213_10056_0_10041 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_GUESTROOM103_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
253 C_GUESTROOM213_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM313_10149_0_10090 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
254 P_GUESTROOM214_10099_0_10061 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_REARSTAIRSFLR2_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
255 P_GUESTROOM214_10104_0_10064 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 270.00 90.00 3.96 2.74 0.00 P_CORRIDORFLR2_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
256 W_GUESTROOM214_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   9.22 10.87 9.22 90.00 90.00 3.96 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
257 W_GUESTROOM214_3_0_0_0_0 Window W_GUESTROOM214_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
258 P_GUESTROOM214_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM215_218_10156_0_10092 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
259 F_GUESTROOM214_10060_0_10042 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_GUESTROOM104_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
260 C_GUESTROOM214_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM314_10154_0_10091 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
261 P_GUESTROOM215_218_10105_0_10065 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 270.00 90.00 15.85 2.74 0.00 P_CORRIDORFLR2_5_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
262 P_GUESTROOM215_218_10156_0_10092 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM214_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
263 W_GUESTROOM215_218_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   36.88 43.48 36.88 90.00 90.00 15.85 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
264 W_GUESTROOM215_218_3_0_0_0_0 Window W_GUESTROOM215_218_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
265 W_GUESTROOM215_218_3_0_0_0_1 Window W_GUESTROOM215_218_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
266 W_GUESTROOM215_218_3_0_0_0_2 Window W_GUESTROOM215_218_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
267 W_GUESTROOM215_218_3_0_0_0_3 Window W_GUESTROOM215_218_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
268 P_GUESTROOM215_218_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM219_10163_0_10094 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
269 F_GUESTROOM215_218_10064_0_10044 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_GUESTROOM105_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
270 F_GUESTROOM215_218_10068_0_10046 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_EMPLOYEELOUNGEFLR1_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
271 F_GUESTROOM215_218_10072_0_10048 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   65.22 65.22 65.22 90.00 180.00 7.92 8.23 0.00 C_LAUNDRYROOMFLR1_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
272 C_GUESTROOM215_218_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   130.44 130.44 130.44 270.00 0.00 15.85 8.23 0.00 F_GUESTROOM315_318_10161_0_10093 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
273 P_ELEVATORCOREFLR2_10107_0_10067 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.02 5.02 5.02 270.00 90.00 1.83 2.74 0.00 P_CORRIDORFLR2_7_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
274 P_ELEVATORCOREFLR2_10108_0_10068 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_CORRIDORFLR2_8_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
275 P_ELEVATORCOREFLR2_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM219_10167_0_10096 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
276 W_ELEVATORCOREFLR2_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   5.02 5.02 5.02 90.00 90.00 1.83 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
277 F_ELEVATORCOREFLR2_10077_0_10051 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   15.05 15.05 15.05 90.00 180.00 1.83 8.23 0.00 C_ELEVATORCOREFLR1_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
278 C_ELEVATORCOREFLR2_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   15.05 15.05 15.05 270.00 0.00 1.83 8.23 0.00 F_ELEVATORCOREFLR3_10166_0_10095 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
279 P_GUESTROOM219_10106_0_10066 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 270.00 90.00 3.96 2.74 0.00 P_CORRIDORFLR2_6_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
280 P_GUESTROOM219_10163_0_10094 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM215_218_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
281 P_GUESTROOM219_10167_0_10096 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_ELEVATORCOREFLR2_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
282 W_GUESTROOM219_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   9.22 10.87 9.22 90.00 90.00 3.96 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
283 W_GUESTROOM219_3_0_0_0_0 Window W_GUESTROOM219_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
284 F_GUESTROOM219_10073_0_10049 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_LAUNDRYROOMFLR1_1_1_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
285 C_GUESTROOM219_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM319_10171_0_10097 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
286 P_GUESTROOM220_223_10109_0_10069 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_CORRIDORFLR2_10_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
287 P_GUESTROOM220_223_10110_0_10070 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 270.00 90.00 15.85 2.74 0.00 P_CORRIDORFLR2_11_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
288 W_GUESTROOM220_223_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   36.88 43.48 36.88 90.00 90.00 15.85 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
289 W_GUESTROOM220_223_3_0_0_0_0 Window W_GUESTROOM220_223_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
290 W_GUESTROOM220_223_3_0_0_0_1 Window W_GUESTROOM220_223_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
291 W_GUESTROOM220_223_3_0_0_0_2 Window W_GUESTROOM220_223_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
292 W_GUESTROOM220_223_3_0_0_0_3 Window W_GUESTROOM220_223_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
293 P_GUESTROOM220_223_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM224_10179_0_10099 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
294 F_GUESTROOM220_223_10081_0_10052 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_EXERCISECENTERFLR1_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
295 F_GUESTROOM220_223_10085_0_10054 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   97.83 97.83 97.83 90.00 180.00 11.89 8.23 0.00 C_FRONTOFFICEFLR1_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
296 C_GUESTROOM220_223_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   130.44 130.44 130.44 270.00 0.00 15.85 8.23 0.00 F_GUESTROOM320_323_10177_0_10098 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
297 P_GUESTROOM224_10111_0_10071 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 270.00 90.00 3.96 2.74 0.00 P_CORRIDORFLR2_12_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
298 P_GUESTROOM224_10179_0_10099 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM220_223_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
299 W_GUESTROOM224_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   9.22 10.87 9.22 90.00 90.00 3.96 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
300 W_GUESTROOM224_3_0_0_0_0 Window W_GUESTROOM224_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
301 P_GUESTROOM224_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_FRONTSTORAGEFLR2_10184_0_10101 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
302 F_GUESTROOM224_10086_0_10055 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_FRONTOFFICEFLR1_1_1_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
303 C_GUESTROOM224_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM324_10182_0_10100 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
304 P_FRONTSTORAGEFLR2_10112_0_10072 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.18 4.18 4.18 270.00 90.00 1.52 2.74 0.00 P_CORRIDORFLR2_13_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
305 P_FRONTSTORAGEFLR2_10184_0_10101 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM224_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
306 W_FRONTSTORAGEFLR2_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   4.18 4.18 4.18 90.00 90.00 1.52 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
307 P_FRONTSTORAGEFLR2_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_FRONTSTAIRSFLR2_10189_0_10103 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
308 F_FRONTSTORAGEFLR2_10093_0_10059 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   12.54 12.54 12.54 90.00 180.00 1.52 8.23 0.00 C_FRONTSTORAGEFLR1_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
309 C_FRONTSTORAGEFLR2_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   12.54 12.54 12.54 270.00 0.00 1.52 8.23 0.00 F_FRONTSTORAGEFLR3_10187_0_10102 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
310 P_FRONTSTAIRSFLR2_10113_0_10073 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 270.00 90.00 2.44 2.74 0.00 P_CORRIDORFLR2_14_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
311 P_FRONTSTAIRSFLR2_10189_0_10103 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_FRONTSTORAGEFLR2_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
312 W_FRONTSTAIRSFLR2_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   6.69 6.69 6.69 90.00 90.00 2.44 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
313 W_FRONTSTAIRSFLR2_4_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
314 F_FRONTSTAIRSFLR2_10090_0_10057 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   20.07 20.07 20.07 90.00 180.00 2.44 8.23 0.00 C_FRONTSTAIRSFLR1_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
315 C_FRONTSTAIRSFLR2_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   20.07 20.07 20.07 270.00 0.00 2.44 8.23 0.00 F_FRONTSTAIRSFLR3_10192_0_10104 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
316 W_REARSTAIRSFLR3_2_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
317 W_REARSTAIRSFLR3_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   6.69 6.69 6.69 90.00 90.00 2.44 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
318 P_REARSTAIRSFLR3_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM314_10197_0_10106 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
319 P_REARSTAIRSFLR3_5_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 270.00 90.00 2.44 2.74 0.00 P_CORRIDORFLR3_10198_0_10107 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
320 F_REARSTAIRSFLR3_10098_0_10060 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   20.07 20.07 20.07 90.00 180.00 2.44 8.23 0.00 C_REARSTAIRSFLR2_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
321 C_REARSTAIRSFLR3_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   20.07 20.07 20.07 270.00 0.00 2.44 8.23 0.00 F_REARSTAIRSFLR4_10196_0_10105 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
322 P_CORRIDORFLR3_10198_0_10107 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 90.00 90.00 2.44 2.74 0.00 P_REARSTAIRSFLR3_5_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
323 W_CORRIDORFLR3_2_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   3.71 5.02 3.71 180.00 90.00 1.83 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
324 W_CORRIDORFLR3_2_0_0_0_0 Window W_CORRIDORFLR3_2_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.31 1.31 1.31 180.00 90.00 0.92 1.42 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
325 P_CORRIDORFLR3_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 90.00 90.00 3.96 2.74 0.00 P_GUESTROOM314_10202_0_10109 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
326 P_CORRIDORFLR3_5_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 90.00 90.00 15.85 2.74 0.00 P_GUESTROOM315_318_10203_0_10110 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
327 P_CORRIDORFLR3_6_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 90.00 90.00 3.96 2.74 0.00 P_GUESTROOM319_10204_0_10111 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
328 P_CORRIDORFLR3_7_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.02 5.02 5.02 90.00 90.00 1.83 2.74 0.00 P_ELEVATORCOREFLR3_10205_0_10112 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
329 P_CORRIDORFLR3_8_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_ELEVATORCOREFLR3_10206_0_10113 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
330 W_CORRIDORFLR3_9_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   8.36 8.36 8.36 90.00 90.00 3.05 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
331 P_CORRIDORFLR3_10_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM320_323_10207_0_10114 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
332 P_CORRIDORFLR3_11_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 90.00 90.00 15.85 2.74 0.00 P_GUESTROOM320_323_10208_0_10115 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
333 P_CORRIDORFLR3_12_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 90.00 90.00 3.96 2.74 0.00 P_GUESTROOM324_10209_0_10116 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
334 P_CORRIDORFLR3_13_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.18 4.18 4.18 90.00 90.00 1.52 2.74 0.00 P_FRONTSTORAGEFLR3_10210_0_10117 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
335 P_CORRIDORFLR3_14_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 90.00 90.00 2.44 2.74 0.00 P_FRONTSTAIRSFLR3_10211_0_10118 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
336 W_CORRIDORFLR3_15_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   3.71 5.02 3.71 0.00 90.00 1.83 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
337 W_CORRIDORFLR3_15_0_0_0_0 Window W_CORRIDORFLR3_15_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.31 1.31 1.31 0.00 90.00 0.92 1.42 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
338 P_CORRIDORFLR3_16_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 270.00 90.00 3.96 2.74 0.00 P_GUESTROOM301_10212_0_10119 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
339 P_CORRIDORFLR3_17_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 270.00 90.00 15.85 2.74 0.00 P_GUESTROOM302_305_10213_0_10120 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
340 P_CORRIDORFLR3_18_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   35.12 35.12 35.12 270.00 90.00 12.80 2.74 0.00 P_GUESTROOM306_308_10214_0_10121 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
341 P_CORRIDORFLR3_19_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 270.00 90.00 15.85 2.74 0.00 P_GUESTROOM309_312_10215_0_10122 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
342 P_CORRIDORFLR3_20_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 270.00 90.00 3.96 2.74 0.00 P_GUESTROOM313_10216_0_10123 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
343 P_CORRIDORFLR3_21_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 270.00 90.00 2.44 2.74 0.00 P_REARSTORAGEFLR3_10217_0_10124 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
344 F_CORRIDORFLR3_10102_0_10063 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   125.42 125.42 125.42 90.00 180.00 11.20 11.20 0.00 C_CORRIDORFLR2_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 8
345 C_CORRIDORFLR3_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   125.42 125.42 125.42 270.00 0.00 11.20 11.20 0.00 F_CORRIDORFLR4_10200_0_10108 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 8
346 P_REARSTORAGEFLR3_10217_0_10124 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 90.00 90.00 2.44 2.74 0.00 P_CORRIDORFLR3_21_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
347 W_REARSTORAGEFLR3_2_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
348 P_REARSTORAGEFLR3_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM313_10221_0_10126 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
349 W_REARSTORAGEFLR3_5_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   6.69 6.69 6.69 270.00 90.00 2.44 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
350 F_REARSTORAGEFLR3_10121_0_10080 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   20.07 20.07 20.07 90.00 180.00 2.44 8.23 0.00 C_REARSTORAGEFLR2_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
351 C_REARSTORAGEFLR3_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   20.07 20.07 20.07 270.00 0.00 2.44 8.23 0.00 F_REARSTORAGEFLR4_10219_0_10125 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
352 P_GUESTROOM301_10212_0_10119 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 90.00 90.00 3.96 2.74 0.00 P_CORRIDORFLR3_16_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
353 P_GUESTROOM301_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM302_305_10224_0_10128 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
354 W_GUESTROOM301_4_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
355 W_GUESTROOM301_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   9.22 10.87 9.22 270.00 90.00 3.96 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
356 W_GUESTROOM301_5_0_0_0_0 Window W_GUESTROOM301_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
357 F_GUESTROOM301_10125_0_10082 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_GUESTROOM201_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
358 C_GUESTROOM301_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM401_10223_0_10127 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
359 P_GUESTROOM302_305_10213_0_10120 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 90.00 90.00 15.85 2.74 0.00 P_CORRIDORFLR3_17_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
360 P_GUESTROOM302_305_10224_0_10128 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM301_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
361 P_GUESTROOM302_305_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM306_308_10228_0_10130 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
362 W_GUESTROOM302_305_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   36.90 43.48 36.90 270.00 90.00 15.85 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
363 W_GUESTROOM302_305_5_0_0_0_0 Window W_GUESTROOM302_305_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
364 W_GUESTROOM302_305_5_0_0_0_1 Window W_GUESTROOM302_305_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
365 W_GUESTROOM302_305_5_0_0_0_2 Window W_GUESTROOM302_305_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
366 W_GUESTROOM302_305_5_0_0_0_3 Window W_GUESTROOM302_305_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
367 F_GUESTROOM302_305_10129_0_10084 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   130.45 130.45 130.45 90.00 180.00 15.85 8.23 0.00 C_GUESTROOM202_205_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
368 C_GUESTROOM302_305_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   130.45 130.45 130.45 270.00 0.00 15.85 8.23 0.00 F_GUESTROOM402_405_10227_0_10129 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
369 P_GUESTROOM306_308_10214_0_10121 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   35.12 35.12 35.12 90.00 90.00 12.80 2.74 0.00 P_CORRIDORFLR3_18_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
370 P_GUESTROOM306_308_10228_0_10130 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM302_305_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
371 P_GUESTROOM306_308_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM309_312_10233_0_10132 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
372 W_GUESTROOM306_308_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   28.42 35.12 28.42 270.00 90.00 12.80 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
373 W_GUESTROOM306_308_5_0_0_0_0 Window W_GUESTROOM306_308_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
374 W_GUESTROOM306_308_5_0_0_0_1 Window W_GUESTROOM306_308_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 3.41 3.41 3.41 270.00 90.00 2.36 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
375 W_GUESTROOM306_308_5_0_0_0_2 Window W_GUESTROOM306_308_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
376 F_GUESTROOM306_308_10136_0_10086 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   105.36 105.36 105.36 90.00 180.00 12.80 8.23 0.00 C_GUESTROOM206_208_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
377 C_GUESTROOM306_308_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   105.36 105.36 105.36 270.00 0.00 12.80 8.23 0.00 F_GUESTROOM406_408_10232_0_10131 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
378 P_GUESTROOM309_312_10215_0_10122 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 90.00 90.00 15.85 2.74 0.00 P_CORRIDORFLR3_19_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
379 P_GUESTROOM309_312_10233_0_10132 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM306_308_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
380 P_GUESTROOM309_312_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM313_10238_0_10134 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
381 W_GUESTROOM309_312_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   36.90 43.48 36.90 270.00 90.00 15.85 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
382 W_GUESTROOM309_312_5_0_0_0_0 Window W_GUESTROOM309_312_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
383 W_GUESTROOM309_312_5_0_0_0_1 Window W_GUESTROOM309_312_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
384 W_GUESTROOM309_312_5_0_0_0_2 Window W_GUESTROOM309_312_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
385 W_GUESTROOM309_312_5_0_0_0_3 Window W_GUESTROOM309_312_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
386 F_GUESTROOM309_312_10144_0_10088 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   130.45 130.45 130.45 90.00 180.00 15.85 8.23 0.00 C_GUESTROOM209_212_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
387 C_GUESTROOM309_312_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   130.45 130.45 130.45 270.00 0.00 15.85 8.23 0.00 F_GUESTROOM409_412_10237_0_10133 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
388 P_GUESTROOM313_10216_0_10123 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 90.00 90.00 3.96 2.74 0.00 P_CORRIDORFLR3_20_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
389 P_GUESTROOM313_10221_0_10126 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_REARSTORAGEFLR3_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
390 P_GUESTROOM313_10238_0_10134 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM309_312_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
391 W_GUESTROOM313_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   9.22 10.87 9.22 270.00 90.00 3.96 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
392 W_GUESTROOM313_5_0_0_0_0 Window W_GUESTROOM313_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
393 F_GUESTROOM313_10149_0_10090 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_GUESTROOM213_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
394 C_GUESTROOM313_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM413_10242_0_10135 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
395 P_GUESTROOM314_10197_0_10106 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_REARSTAIRSFLR3_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
396 P_GUESTROOM314_10202_0_10109 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 270.00 90.00 3.96 2.74 0.00 P_CORRIDORFLR3_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
397 W_GUESTROOM314_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   9.22 10.87 9.22 90.00 90.00 3.96 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
398 W_GUESTROOM314_3_0_0_0_0 Window W_GUESTROOM314_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
399 P_GUESTROOM314_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM315_318_10249_0_10137 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
400 F_GUESTROOM314_10154_0_10091 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_GUESTROOM214_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
401 C_GUESTROOM314_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM414_10247_0_10136 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
402 P_GUESTROOM315_318_10203_0_10110 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 270.00 90.00 15.85 2.74 0.00 P_CORRIDORFLR3_5_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
403 P_GUESTROOM315_318_10249_0_10137 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM314_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
404 W_GUESTROOM315_318_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   36.90 43.48 36.90 90.00 90.00 15.85 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
405 W_GUESTROOM315_318_3_0_0_0_0 Window W_GUESTROOM315_318_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
406 W_GUESTROOM315_318_3_0_0_0_1 Window W_GUESTROOM315_318_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
407 W_GUESTROOM315_318_3_0_0_0_2 Window W_GUESTROOM315_318_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
408 W_GUESTROOM315_318_3_0_0_0_3 Window W_GUESTROOM315_318_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
409 P_GUESTROOM315_318_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM319_10254_0_10139 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
410 F_GUESTROOM315_318_10161_0_10093 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   130.44 130.44 130.44 90.00 180.00 15.85 8.23 0.00 C_GUESTROOM215_218_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
411 C_GUESTROOM315_318_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   130.44 130.44 130.44 270.00 0.00 15.85 8.23 0.00 F_GUESTROOM415_418_10252_0_10138 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
412 P_ELEVATORCOREFLR3_10205_0_10112 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.02 5.02 5.02 270.00 90.00 1.83 2.74 0.00 P_CORRIDORFLR3_7_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
413 P_ELEVATORCOREFLR3_10206_0_10113 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_CORRIDORFLR3_8_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
414 P_ELEVATORCOREFLR3_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM319_10258_0_10141 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
415 W_ELEVATORCOREFLR3_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   5.02 5.02 5.02 90.00 90.00 1.83 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
416 F_ELEVATORCOREFLR3_10166_0_10095 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   15.05 15.05 15.05 90.00 180.00 1.83 8.23 0.00 C_ELEVATORCOREFLR2_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
417 C_ELEVATORCOREFLR3_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   15.05 15.05 15.05 270.00 0.00 1.83 8.23 0.00 F_ELEVATORCOREFLR4_10257_0_10140 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
418 P_GUESTROOM319_10204_0_10111 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 270.00 90.00 3.96 2.74 0.00 P_CORRIDORFLR3_6_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
419 P_GUESTROOM319_10254_0_10139 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM315_318_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
420 P_GUESTROOM319_10258_0_10141 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_ELEVATORCOREFLR3_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
421 W_GUESTROOM319_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   9.22 10.87 9.22 90.00 90.00 3.96 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
422 W_GUESTROOM319_3_0_0_0_0 Window W_GUESTROOM319_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
423 F_GUESTROOM319_10171_0_10097 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_GUESTROOM219_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
424 C_GUESTROOM319_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM419_10262_0_10142 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
425 P_GUESTROOM320_323_10207_0_10114 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_CORRIDORFLR3_10_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
426 P_GUESTROOM320_323_10208_0_10115 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 270.00 90.00 15.85 2.74 0.00 P_CORRIDORFLR3_11_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
427 W_GUESTROOM320_323_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   36.90 43.48 36.90 90.00 90.00 15.85 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
428 W_GUESTROOM320_323_3_0_0_0_0 Window W_GUESTROOM320_323_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
429 W_GUESTROOM320_323_3_0_0_0_1 Window W_GUESTROOM320_323_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
430 W_GUESTROOM320_323_3_0_0_0_2 Window W_GUESTROOM320_323_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
431 W_GUESTROOM320_323_3_0_0_0_3 Window W_GUESTROOM320_323_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
432 P_GUESTROOM320_323_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM324_10269_0_10144 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
433 F_GUESTROOM320_323_10177_0_10098 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   130.44 130.44 130.44 90.00 180.00 15.85 8.23 0.00 C_GUESTROOM220_223_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
434 C_GUESTROOM320_323_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   130.44 130.44 130.44 270.00 0.00 15.85 8.23 0.00 F_GUESTROOM420_423_10267_0_10143 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
435 P_GUESTROOM324_10209_0_10116 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 270.00 90.00 3.96 2.74 0.00 P_CORRIDORFLR3_12_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
436 P_GUESTROOM324_10269_0_10144 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM320_323_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
437 W_GUESTROOM324_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   9.22 10.87 9.22 90.00 90.00 3.96 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
438 W_GUESTROOM324_3_0_0_0_0 Window W_GUESTROOM324_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
439 P_GUESTROOM324_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_FRONTSTORAGEFLR3_10274_0_10146 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
440 F_GUESTROOM324_10182_0_10100 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_GUESTROOM224_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
441 C_GUESTROOM324_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 F_GUESTROOM424_10272_0_10145 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
442 P_FRONTSTORAGEFLR3_10210_0_10117 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.18 4.18 4.18 270.00 90.00 1.52 2.74 0.00 P_CORRIDORFLR3_13_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
443 P_FRONTSTORAGEFLR3_10274_0_10146 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM324_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
444 W_FRONTSTORAGEFLR3_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   4.18 4.18 4.18 90.00 90.00 1.52 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
445 P_FRONTSTORAGEFLR3_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_FRONTSTAIRSFLR3_10279_0_10148 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
446 F_FRONTSTORAGEFLR3_10187_0_10102 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   12.54 12.54 12.54 90.00 180.00 1.52 8.23 0.00 C_FRONTSTORAGEFLR2_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
447 C_FRONTSTORAGEFLR3_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   12.54 12.54 12.54 270.00 0.00 1.52 8.23 0.00 F_FRONTSTORAGEFLR4_10277_0_10147 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
448 P_FRONTSTAIRSFLR3_10211_0_10118 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 270.00 90.00 2.44 2.74 0.00 P_CORRIDORFLR3_14_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
449 P_FRONTSTAIRSFLR3_10279_0_10148 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_FRONTSTORAGEFLR3_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
450 W_FRONTSTAIRSFLR3_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   6.69 6.69 6.69 90.00 90.00 2.44 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
451 W_FRONTSTAIRSFLR3_4_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.539 0.498   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
452 F_FRONTSTAIRSFLR3_10192_0_10104 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   20.07 20.07 20.07 90.00 180.00 2.44 8.23 0.00 C_FRONTSTAIRSFLR2_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
453 C_FRONTSTAIRSFLR3_1_0_0 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   20.07 20.07 20.07 270.00 0.00 2.44 8.23 0.00 F_FRONTSTAIRSFLR4_10282_0_10149 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
454 W_REARSTAIRSFLR4_2_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.864 0.765   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
455 W_REARSTAIRSFLR4_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.864 0.765   6.69 6.69 6.69 90.00 90.00 2.44 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
456 P_REARSTAIRSFLR4_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM414_10286_0_10150 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
457 P_REARSTAIRSFLR4_5_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 270.00 90.00 2.44 2.74 0.00 P_CORRIDORFLR4_10287_0_10151 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
458 F_REARSTAIRSFLR4_10196_0_10105 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   20.07 20.07 20.07 90.00 180.00 2.44 8.23 0.00 C_REARSTAIRSFLR3_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
459 R_REARSTAIRSFLR4_1_0_0 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   20.07 20.07 20.07 270.00 0.00 2.44 8.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
460 P_CORRIDORFLR4_10287_0_10151 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 90.00 90.00 2.44 2.74 0.00 P_REARSTAIRSFLR4_5_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
461 W_CORRIDORFLR4_2_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.864 0.765   3.71 5.02 3.71 180.00 90.00 1.83 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
462 W_CORRIDORFLR4_2_0_0_0_0 Window W_CORRIDORFLR4_2_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.31 1.31 1.31 180.00 90.00 0.92 1.42 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
463 P_CORRIDORFLR4_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 90.00 90.00 3.96 2.74 0.00 P_GUESTROOM414_10290_0_10152 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
464 P_CORRIDORFLR4_5_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 90.00 90.00 15.85 2.74 0.00 P_GUESTROOM415_418_10291_0_10153 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
465 P_CORRIDORFLR4_6_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 90.00 90.00 3.96 2.74 0.00 P_GUESTROOM419_10292_0_10154 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
466 P_CORRIDORFLR4_7_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.02 5.02 5.02 90.00 90.00 1.83 2.74 0.00 P_ELEVATORCOREFLR4_10293_0_10155 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
467 P_CORRIDORFLR4_8_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_ELEVATORCOREFLR4_10294_0_10156 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
468 W_CORRIDORFLR4_9_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.864 0.765   8.36 8.36 8.36 90.00 90.00 3.05 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
469 P_CORRIDORFLR4_10_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM420_423_10295_0_10157 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
470 P_CORRIDORFLR4_11_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 90.00 90.00 15.85 2.74 0.00 P_GUESTROOM420_423_10296_0_10158 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
471 P_CORRIDORFLR4_12_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 90.00 90.00 3.96 2.74 0.00 P_GUESTROOM424_10297_0_10159 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
472 P_CORRIDORFLR4_13_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.18 4.18 4.18 90.00 90.00 1.52 2.74 0.00 P_FRONTSTORAGEFLR4_10298_0_10160 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
473 P_CORRIDORFLR4_14_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 90.00 90.00 2.44 2.74 0.00 P_FRONTSTAIRSFLR4_10299_0_10161 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
474 W_CORRIDORFLR4_15_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.864 0.765   3.71 5.02 3.71 0.00 90.00 1.83 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
475 W_CORRIDORFLR4_15_0_0_0_0 Window W_CORRIDORFLR4_15_0_0 Window5 Detailed Fenestration NONRESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.31 1.31 1.31 0.00 90.00 0.92 1.42 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
476 P_CORRIDORFLR4_16_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 270.00 90.00 3.96 2.74 0.00 P_GUESTROOM401_10300_0_10162 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
477 P_CORRIDORFLR4_17_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 270.00 90.00 15.85 2.74 0.00 P_GUESTROOM402_405_10301_0_10163 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
478 P_CORRIDORFLR4_18_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   35.12 35.12 35.12 270.00 90.00 12.80 2.74 0.00 P_GUESTROOM406_408_10302_0_10164 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
479 P_CORRIDORFLR4_19_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 270.00 90.00 15.85 2.74 0.00 P_GUESTROOM409_412_10303_0_10165 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
480 P_CORRIDORFLR4_20_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 270.00 90.00 3.96 2.74 0.00 P_GUESTROOM413_10304_0_10166 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
481 P_CORRIDORFLR4_21_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 270.00 90.00 2.44 2.74 0.00 P_REARSTORAGEFLR4_10305_0_10167 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
482 F_CORRIDORFLR4_10200_0_10108 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   125.42 125.42 125.42 90.00 180.00 11.20 11.20 0.00 C_CORRIDORFLR3_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 8
483 R_CORRIDORFLR4_1_0_0 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   125.42 125.42 125.42 270.00 0.00 11.20 11.20 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
484 P_REARSTORAGEFLR4_10305_0_10167 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 90.00 90.00 2.44 2.74 0.00 P_CORRIDORFLR4_21_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
485 W_REARSTORAGEFLR4_2_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.864 0.765   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
486 P_REARSTORAGEFLR4_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM413_10308_0_10168 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
487 W_REARSTORAGEFLR4_5_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.864 0.765   6.69 6.69 6.69 270.00 90.00 2.44 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
488 F_REARSTORAGEFLR4_10219_0_10125 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   20.07 20.07 20.07 90.00 180.00 2.44 8.23 0.00 C_REARSTORAGEFLR3_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
489 R_REARSTORAGEFLR4_1_0_0 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   20.07 20.07 20.07 270.00 0.00 2.44 8.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
490 P_GUESTROOM401_10300_0_10162 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 90.00 90.00 3.96 2.74 0.00 P_CORRIDORFLR4_16_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
491 P_GUESTROOM401_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM402_405_10310_0_10169 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
492 W_GUESTROOM401_4_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.864 0.765   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
493 W_GUESTROOM401_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.864 0.765   9.22 10.87 9.22 270.00 90.00 3.96 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
494 W_GUESTROOM401_5_0_0_0_0 Window W_GUESTROOM401_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
495 F_GUESTROOM401_10223_0_10127 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_GUESTROOM301_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
496 R_GUESTROOM401_1_0_0 Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
497 P_GUESTROOM402_405_10301_0_10163 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 90.00 90.00 15.85 2.74 0.00 P_CORRIDORFLR4_17_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
498 P_GUESTROOM402_405_10310_0_10169 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM401_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
499 P_GUESTROOM402_405_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM406_408_10313_0_10170 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
500 W_GUESTROOM402_405_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.864 0.765   36.90 43.48 36.90 270.00 90.00 15.85 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
501 W_GUESTROOM402_405_5_0_0_0_0 Window W_GUESTROOM402_405_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
502 W_GUESTROOM402_405_5_0_0_0_1 Window W_GUESTROOM402_405_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
503 W_GUESTROOM402_405_5_0_0_0_2 Window W_GUESTROOM402_405_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
504 W_GUESTROOM402_405_5_0_0_0_3 Window W_GUESTROOM402_405_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
505 F_GUESTROOM402_405_10227_0_10129 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   130.45 130.45 130.45 90.00 180.00 15.85 8.23 0.00 C_GUESTROOM302_305_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
506 R_GUESTROOM402_405_1_0_0 Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   130.45 130.45 130.45 270.00 0.00 15.85 8.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
507 P_GUESTROOM406_408_10302_0_10164 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   35.12 35.12 35.12 90.00 90.00 12.80 2.74 0.00 P_CORRIDORFLR4_18_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
508 P_GUESTROOM406_408_10313_0_10170 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM402_405_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
509 P_GUESTROOM406_408_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM409_412_10317_0_10171 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
510 W_GUESTROOM406_408_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.864 0.765   28.42 35.12 28.42 270.00 90.00 12.80 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
511 W_GUESTROOM406_408_5_0_0_0_0 Window W_GUESTROOM406_408_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
512 W_GUESTROOM406_408_5_0_0_0_1 Window W_GUESTROOM406_408_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
513 W_GUESTROOM406_408_5_0_0_0_2 Window W_GUESTROOM406_408_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 3.41 3.41 3.41 270.00 90.00 2.36 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
514 F_GUESTROOM406_408_10232_0_10131 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   105.36 105.36 105.36 90.00 180.00 12.80 8.23 0.00 C_GUESTROOM306_308_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
515 R_GUESTROOM406_408_1_0_0 Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   105.36 105.36 105.36 270.00 0.00 12.80 8.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
516 P_GUESTROOM409_412_10303_0_10165 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 90.00 90.00 15.85 2.74 0.00 P_CORRIDORFLR4_19_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
517 P_GUESTROOM409_412_10317_0_10171 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM406_408_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
518 P_GUESTROOM409_412_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM413_10321_0_10172 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
519 W_GUESTROOM409_412_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.864 0.765   36.90 43.48 36.90 270.00 90.00 15.85 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
520 W_GUESTROOM409_412_5_0_0_0_0 Window W_GUESTROOM409_412_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
521 W_GUESTROOM409_412_5_0_0_0_1 Window W_GUESTROOM409_412_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
522 W_GUESTROOM409_412_5_0_0_0_2 Window W_GUESTROOM409_412_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
523 W_GUESTROOM409_412_5_0_0_0_3 Window W_GUESTROOM409_412_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
524 F_GUESTROOM409_412_10237_0_10133 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   130.45 130.45 130.45 90.00 180.00 15.85 8.23 0.00 C_GUESTROOM309_312_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
525 R_GUESTROOM409_412_1_0_0 Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   130.45 130.45 130.45 270.00 0.00 15.85 8.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
526 P_GUESTROOM413_10304_0_10166 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 90.00 90.00 3.96 2.74 0.00 P_CORRIDORFLR4_20_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
527 P_GUESTROOM413_10308_0_10168 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_REARSTORAGEFLR4_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
528 P_GUESTROOM413_10321_0_10172 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM409_412_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
529 W_GUESTROOM413_5_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.864 0.765   9.22 10.87 9.22 270.00 90.00 3.96 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
530 W_GUESTROOM413_5_0_0_0_0 Window W_GUESTROOM413_5_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 270.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
531 F_GUESTROOM413_10242_0_10135 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_GUESTROOM313_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
532 R_GUESTROOM413_1_0_0 Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
533 P_GUESTROOM414_10286_0_10150 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_REARSTAIRSFLR4_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
534 P_GUESTROOM414_10290_0_10152 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 270.00 90.00 3.96 2.74 0.00 P_CORRIDORFLR4_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
535 W_GUESTROOM414_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.864 0.765   9.22 10.87 9.22 90.00 90.00 3.96 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
536 W_GUESTROOM414_3_0_0_0_0 Window W_GUESTROOM414_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
537 P_GUESTROOM414_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM415_418_10330_0_10173 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
538 F_GUESTROOM414_10247_0_10136 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_GUESTROOM314_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
539 R_GUESTROOM414_1_0_0 Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
540 P_GUESTROOM415_418_10291_0_10153 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 270.00 90.00 15.85 2.74 0.00 P_CORRIDORFLR4_5_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
541 P_GUESTROOM415_418_10330_0_10173 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM414_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
542 W_GUESTROOM415_418_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.864 0.765   36.90 43.48 36.90 90.00 90.00 15.85 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
543 W_GUESTROOM415_418_3_0_0_0_0 Window W_GUESTROOM415_418_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
544 W_GUESTROOM415_418_3_0_0_0_1 Window W_GUESTROOM415_418_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
545 W_GUESTROOM415_418_3_0_0_0_2 Window W_GUESTROOM415_418_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
546 W_GUESTROOM415_418_3_0_0_0_3 Window W_GUESTROOM415_418_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
547 P_GUESTROOM415_418_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM419_10334_0_10174 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
548 F_GUESTROOM415_418_10252_0_10138 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   130.44 130.44 130.44 90.00 180.00 15.85 8.23 0.00 C_GUESTROOM315_318_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
549 R_GUESTROOM415_418_1_0_0 Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   130.44 130.44 130.44 270.00 0.00 15.85 8.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
550 P_ELEVATORCOREFLR4_10293_0_10155 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   5.02 5.02 5.02 270.00 90.00 1.83 2.74 0.00 P_CORRIDORFLR4_7_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
551 P_ELEVATORCOREFLR4_10294_0_10156 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_CORRIDORFLR4_8_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
552 P_ELEVATORCOREFLR4_2_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM419_10337_0_10175 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
553 W_ELEVATORCOREFLR4_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.864 0.765   5.02 5.02 5.02 90.00 90.00 1.83 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
554 F_ELEVATORCOREFLR4_10257_0_10140 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   15.05 15.05 15.05 90.00 180.00 1.83 8.23 0.00 C_ELEVATORCOREFLR3_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
555 R_ELEVATORCOREFLR4_1_0_0 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   15.05 15.05 15.05 270.00 0.00 1.83 8.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
556 P_GUESTROOM419_10292_0_10154 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 270.00 90.00 3.96 2.74 0.00 P_CORRIDORFLR4_6_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
557 P_GUESTROOM419_10334_0_10174 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM415_418_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
558 P_GUESTROOM419_10337_0_10175 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_ELEVATORCOREFLR4_2_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
559 W_GUESTROOM419_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.864 0.765   9.22 10.87 9.22 90.00 90.00 3.96 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
560 W_GUESTROOM419_3_0_0_0_0 Window W_GUESTROOM419_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
561 F_GUESTROOM419_10262_0_10142 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_GUESTROOM319_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
562 R_GUESTROOM419_1_0_0 Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
563 P_GUESTROOM420_423_10295_0_10157 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_CORRIDORFLR4_10_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
564 P_GUESTROOM420_423_10296_0_10158 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   43.48 43.48 43.48 270.00 90.00 15.85 2.74 0.00 P_CORRIDORFLR4_11_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
565 W_GUESTROOM420_423_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 0.539 0.498   36.90 43.48 36.90 90.00 90.00 15.85 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
566 W_GUESTROOM420_423_3_0_0_0_0 Window W_GUESTROOM420_423_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
567 W_GUESTROOM420_423_3_0_0_0_1 Window W_GUESTROOM420_423_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
568 W_GUESTROOM420_423_3_0_0_0_2 Window W_GUESTROOM420_423_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
569 W_GUESTROOM420_423_3_0_0_0_3 Window W_GUESTROOM420_423_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
570 P_GUESTROOM420_423_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_GUESTROOM424_10346_0_10176 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
571 F_GUESTROOM420_423_10267_0_10143 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   130.44 130.44 130.44 90.00 180.00 15.85 8.23 0.00 C_GUESTROOM320_323_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
572 R_GUESTROOM420_423_1_0_0 Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   130.44 130.44 130.44 270.00 0.00 15.85 8.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
573 P_GUESTROOM424_10297_0_10159 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   10.87 10.87 10.87 270.00 90.00 3.96 2.74 0.00 P_CORRIDORFLR4_12_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
574 P_GUESTROOM424_10346_0_10176 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM420_423_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
575 W_GUESTROOM424_3_0_0 Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 0.864 0.765   9.22 10.87 9.22 90.00 90.00 3.96 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
576 W_GUESTROOM424_3_0_0_0_0 Window W_GUESTROOM424_3_0_0 Window5 Detailed Fenestration RESWINDOW_U_0.3464_SHGC_0.38 N/A 1.968 No 1.65 1.65 1.65 90.00 90.00 1.14 1.44 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
577 P_GUESTROOM424_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_FRONTSTORAGEFLR4_10350_0_10177 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
578 F_GUESTROOM424_10272_0_10145 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   32.61 32.61 32.61 90.00 180.00 3.96 8.23 0.00 C_GUESTROOM324_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
579 R_GUESTROOM424_1_0_0 Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   32.61 32.61 32.61 270.00 0.00 3.96 8.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
580 P_FRONTSTORAGEFLR4_10298_0_10160 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   4.18 4.18 4.18 270.00 90.00 1.52 2.74 0.00 P_CORRIDORFLR4_13_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
581 P_FRONTSTORAGEFLR4_10350_0_10177 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_GUESTROOM424_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
582 W_FRONTSTORAGEFLR4_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.864 0.765   4.18 4.18 4.18 90.00 90.00 1.52 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
583 P_FRONTSTORAGEFLR4_4_0_0 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 P_FRONTSTAIRSFLR4_10354_0_10178 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
584 F_FRONTSTORAGEFLR4_10277_0_10147 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   12.54 12.54 12.54 90.00 180.00 1.52 8.23 0.00 C_FRONTSTORAGEFLR3_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
585 R_FRONTSTORAGEFLR4_1_0_0 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   12.54 12.54 12.54 270.00 0.00 1.52 8.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
586 P_FRONTSTAIRSFLR4_10299_0_10161 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   6.69 6.69 6.69 270.00 90.00 2.44 2.74 0.00 P_CORRIDORFLR4_14_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
587 P_FRONTSTAIRSFLR4_10354_0_10178 Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.58 22.58 22.58 180.00 90.00 8.23 2.74 0.00 P_FRONTSTORAGEFLR4_4_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
588 W_FRONTSTAIRSFLR4_3_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.864 0.765   6.69 6.69 6.69 90.00 90.00 2.44 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
589 W_FRONTSTAIRSFLR4_4_0_0 Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.864 0.765   22.58 22.58 22.58 0.00 90.00 8.23 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
590 F_FRONTSTAIRSFLR4_10282_0_10149 Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   20.07 20.07 20.07 90.00 180.00 2.44 8.23 0.00 C_FRONTSTAIRSFLR3_1_0_0 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
591 R_FRONTSTAIRSFLR4_1_0_0 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   20.07 20.07 20.07 270.00 0.00 2.44 8.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4


Shading Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Transmittance Schedule Min Schedule Value Max Schedule Value Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 ENTRY CANOPY Shading W_CORRIDORFLR1_2_0_0 None   0.0 0.0   83.60 83.60 83.60 180.00 0.00 9.14 9.14                     4
2 Mir-ENTRY CANOPY Shading W_CORRIDORFLR1_2_0_0 None   0.0 0.0   83.60 83.60 83.60 0.00 180.00 9.14 9.14                     4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No Yes Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/02 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 REARSTAIRSFLR1 RunPeriod: RUNPERIOD 1 1.4949936161E-002 1.3783280397E-002 Pass Pass 6.6283156804E-002 0.1198099486 Pass Pass
2 CORRIDORFLR1 RunPeriod: RUNPERIOD 1 7.1981441915E-002 0.2238668090 Pass Pass 5.5530128544 43.5582161082 Pass Pass
3 REARSTORAGEFLR1 RunPeriod: RUNPERIOD 1 1.2881879471E-002 1.3047550232E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 FRONTLOUNGEFLR1 RunPeriod: RUNPERIOD 1 5.8951804179E-003 2.8727804057E-002 Pass Pass 3.9752732562E-002 0.2015617582 Pass Pass
5 RESTROOMFLR1 RunPeriod: RUNPERIOD 1 6.9756514474E-003 1.0880551056E-002 Pass Pass 1.5046063053E-003 2.3661386206E-003 Pass Pass
6 MEETINGROOMFLR1 RunPeriod: RUNPERIOD 1 1.6490644065E-002 5.6930341455E-002 Pass Pass 3.5157815055E-002 0.2167964436 Pass Pass
7 MECHANICALROOMFLR1 RunPeriod: RUNPERIOD 1 8.1849553293E-003 5.2521894120E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 GUESTROOM101 RunPeriod: RUNPERIOD 1 2.1360549023E-002 7.0773041226E-002 Pass Pass 7.2753277965E-003 7.7758123207E-002 Pass Pass
9 GUESTROOM102 RunPeriod: RUNPERIOD 1 2.1238419448E-002 7.3052308415E-002 Pass Pass 7.2221812348E-003 7.8729214785E-002 Pass Pass
10 GUESTROOM103 RunPeriod: RUNPERIOD 1 3.3831471764E-002 0.1044552900 Pass Pass 8.0549069800E-002 0.2086476551 Pass Pass
11 GUESTROOM104 RunPeriod: RUNPERIOD 1 4.2800906609E-002 0.1227021488 Pass Pass 9.0043924783E-002 0.2179688917 Pass Pass
12 GUESTROOM105 RunPeriod: RUNPERIOD 1 9.7675136067E-002 0.3413433768 Pass Pass 0.1010955013 0.2991771398 Pass Pass
13 EMPLOYEELOUNGEFLR1 RunPeriod: RUNPERIOD 1 3.6330714007E-006 5.8559478279E-006 Pass Pass 1.5004339079E-002 2.5700414073E-002 Pass Pass
14 LAUNDRYROOMFLR1 RunPeriod: RUNPERIOD 1 0.6575256254 2.3330204395 Pass Pass 0.0000000000 0.0000000000 Pass Pass
15 ELEVATORCOREFLR1 RunPeriod: RUNPERIOD 1 0.4632358807 0.8925549927 Pass Pass 0.0000000000 0.0000000000 Pass Pass
16 EXERCISECENTERFLR1 RunPeriod: RUNPERIOD 1 8.8692231566E-006 2.8461215824E-005 Pass Pass 5.4073273867E-002 0.2115214556 Pass Pass
17 FRONTOFFICEFLR1 RunPeriod: RUNPERIOD 1 9.2604753128E-007 2.2150051413E-006 Pass Pass 2.6701670252E-002 8.5437205163E-002 Pass Pass
18 FRONTSTAIRSFLR1 RunPeriod: RUNPERIOD 1 1.1454275647E-002 1.1552673239E-002 Pass Pass 5.1626551849E-002 0.1068969938 Pass Pass
19 FRONTSTORAGEFLR1 RunPeriod: RUNPERIOD 1 4.4333798696E-003 3.4678142869E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
20 REARSTAIRSFLR2 RunPeriod: RUNPERIOD 1 1.6141461839E-002 1.5624551559E-002 Pass Pass 7.7796000613E-002 0.1485571509 Pass Pass
21 CORRIDORFLR2 RunPeriod: RUNPERIOD 1 9.4091199086E-004 2.2219943146E-003 Pass Pass 5.1604929571E-003 4.4956770271E-003 Pass Pass
22 REARSTORAGEFLR2 RunPeriod: RUNPERIOD 1 1.2974933369E-002 1.3086949110E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
23 GUESTROOM201 RunPeriod: RUNPERIOD 1 2.0072899464E-002 5.7536737256E-002 Pass Pass 7.2357734028E-003 7.6438172537E-002 Pass Pass
24 GUESTROOM202_205 RunPeriod: RUNPERIOD 1 3.9862236704E-002 0.1157349282 Pass Pass 0.2061980438 1.0440800140 Pass Pass
25 GUESTROOM206_208 RunPeriod: RUNPERIOD 1 4.7598370147E-002 0.1410093037 Pass Pass 0.1398126141 0.3189698265 Pass Pass
26 GUESTROOM209_212 RunPeriod: RUNPERIOD 1 7.1317469718E-002 0.1951853250 Pass Pass 7.1054348523E-002 0.1874219322 Pass Pass
27 GUESTROOM213 RunPeriod: RUNPERIOD 1 4.3383517339E-002 0.1425226615 Pass Pass 6.3437661104E-002 0.1576223044 Pass Pass
28 GUESTROOM214 RunPeriod: RUNPERIOD 1 6.7231574958E-002 0.1967370936 Pass Pass 5.5675857387E-002 0.1579422079 Pass Pass
29 GUESTROOM215_218 RunPeriod: RUNPERIOD 1 3.8165158003E-006 6.2422244174E-006 Pass Pass 2.8420280516E-002 1.9892626311E-002 Pass Pass
30 ELEVATORCOREFLR2 RunPeriod: RUNPERIOD 1 2.1818726295E-002 1.6085681849E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
31 GUESTROOM219 RunPeriod: RUNPERIOD 1 9.2631577951E-002 0.4122507446 Pass Pass 2.4207122498E-002 6.5050868886E-002 Pass Pass
32 GUESTROOM220_223 RunPeriod: RUNPERIOD 1 8.4018749089E-002 0.2280355097 Pass Pass 6.4967634984E-002 0.1816913855 Pass Pass
33 GUESTROOM224 RunPeriod: RUNPERIOD 1 3.2872249645E-002 9.9384249631E-002 Pass Pass 0.1912371004 0.7585680527 Pass Pass
34 FRONTSTORAGEFLR2 RunPeriod: RUNPERIOD 1 3.5404230851E-003 3.2717753521E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
35 FRONTSTAIRSFLR2 RunPeriod: RUNPERIOD 1 1.1916921662E-002 1.2555093887E-002 Pass Pass 5.5753271559E-002 0.1155672512 Pass Pass
36 REARSTAIRSFLR3 RunPeriod: RUNPERIOD 1 1.3507251035E-002 1.4286906461E-002 Pass Pass 7.0712037772E-002 0.1792633012 Pass Pass
37 CORRIDORFLR3 RunPeriod: RUNPERIOD 1 2.7100333077E-006 5.4427470406E-006 Pass Pass 5.9575673491E-003 4.4967291268E-003 Pass Pass
38 REARSTORAGEFLR3 RunPeriod: RUNPERIOD 1 1.3893842110E-002 1.4021041664E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
39 GUESTROOM301 RunPeriod: RUNPERIOD 1 1.6654369039E-002 5.5244706635E-002 Pass Pass 8.5951858300E-003 7.8626255710E-002 Pass Pass
40 GUESTROOM302_305 RunPeriod: RUNPERIOD 1 2.5382810949E-002 8.2957501625E-002 Pass Pass 7.1656833460E-003 8.1487448290E-002 Pass Pass
41 GUESTROOM306_308 RunPeriod: RUNPERIOD 1 2.4636614324E-002 7.8937966316E-002 Pass Pass 7.1881988155E-003 8.0447008131E-002 Pass Pass
42 GUESTROOM309_312 RunPeriod: RUNPERIOD 1 4.5383663291E-002 0.1326804490 Pass Pass 0.6353920755 2.8783881816 Pass Pass
43 GUESTROOM313 RunPeriod: RUNPERIOD 1 1.8841798420E-002 6.2861097119E-002 Pass Pass 7.1952168962E-003 7.8097776527E-002 Pass Pass
44 GUESTROOM314 RunPeriod: RUNPERIOD 1 3.5460974394E-002 0.1039529419 Pass Pass 0.2651847264 1.1862051894 Pass Pass
45 GUESTROOM315_318 RunPeriod: RUNPERIOD 1 0.1121660755 0.3243188966 Pass Pass 6.6455587052E-002 0.2196220739 Pass Pass
46 ELEVATORCOREFLR3 RunPeriod: RUNPERIOD 1 4.4016777279E-003 4.2129866456E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
47 GUESTROOM319 RunPeriod: RUNPERIOD 1 2.3068445090E-002 6.9520631116E-002 Pass Pass 7.3533296767E-003 7.3920473539E-002 Pass Pass
48 GUESTROOM320_323 RunPeriod: RUNPERIOD 1 6.1982128419E-002 0.1700815150 Pass Pass 8.4441012003E-002 0.2102306702 Pass Pass
49 GUESTROOM324 RunPeriod: RUNPERIOD 1 2.2123088946E-002 7.3363746387E-002 Pass Pass 7.2202111845E-003 7.7736899428E-002 Pass Pass
50 FRONTSTORAGEFLR3 RunPeriod: RUNPERIOD 1 4.3323976932E-003 3.6856234618E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
51 FRONTSTAIRSFLR3 RunPeriod: RUNPERIOD 1 1.1781175195E-002 1.3062019778E-002 Pass Pass 6.0323905161E-002 0.1397961977 Pass Pass
52 REARSTAIRSFLR4 RunPeriod: RUNPERIOD 1 2.9105352901E-002 2.9225389835E-002 Pass Pass 0.2778083665 1.2654947765 Pass Pass
53 CORRIDORFLR4 RunPeriod: RUNPERIOD 1 4.2814818844E-006 8.2255837300E-006 Pass Pass 6.0949181613E-003 6.4853166711E-003 Pass Pass
54 REARSTORAGEFLR4 RunPeriod: RUNPERIOD 1 2.7385870587E-002 2.7081842639E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
55 GUESTROOM401 RunPeriod: RUNPERIOD 1 9.2651105643E-002 0.3316995320 Pass Pass 6.3018195523E-002 0.1647324747 Pass Pass
56 GUESTROOM402_405 RunPeriod: RUNPERIOD 1 1.1165451562E-002 3.6714287020E-002 Pass Pass 5.8770946005E-002 0.1640016140 Pass Pass
57 GUESTROOM406_408 RunPeriod: RUNPERIOD 1 2.1058195123E-002 5.3057802995E-002 Pass Pass 3.4561037440E-002 0.1571636056 Pass Pass
58 GUESTROOM409_412 RunPeriod: RUNPERIOD 1 4.3092517908E-002 0.1494057111 Pass Pass 0.1091874656 0.2815003545 Pass Pass
59 GUESTROOM413 RunPeriod: RUNPERIOD 1 8.7288760985E-003 2.5503681164E-002 Pass Pass 5.6594388084E-002 0.1927240834 Pass Pass
60 GUESTROOM414 RunPeriod: RUNPERIOD 1 2.6379491224E-002 5.7968824545E-002 Pass Pass 7.3063570912E-003 7.6862349613E-002 Pass Pass
61 GUESTROOM415_418 RunPeriod: RUNPERIOD 1 4.4681498050E-002 0.1249703265 Pass Pass 0.4774101286 3.7488210975 Pass Pass
62 ELEVATORCOREFLR4 RunPeriod: RUNPERIOD 1 9.4431940712E-003 8.6374226388E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
63 GUESTROOM419 RunPeriod: RUNPERIOD 1 3.1300910539E-002 9.8480428430E-002 Pass Pass 0.2814977622 0.9306517636 Pass Pass
64 GUESTROOM420_423 RunPeriod: RUNPERIOD 1 4.6475910728E-002 0.1328153208 Pass Pass 0.1702489595 0.5764951209 Pass Pass
65 GUESTROOM424 RunPeriod: RUNPERIOD 1 5.7903988536E-002 0.2070764267 Pass Pass 8.1180994454E-002 0.1798819578 Pass Pass
66 FRONTSTORAGEFLR4 RunPeriod: RUNPERIOD 1 9.0685558906E-003 8.0640039918E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
67 FRONTSTAIRSFLR4 RunPeriod: RUNPERIOD 1 1.9807791372E-002 1.7572083223E-002 Pass Pass 9.3302770101E-002 0.1738092066 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3353.32 159.74 0.00 262.14 1193.41 4968.62



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB -26.20 0.00 -26.20 Wetbulb [C] 5.70 310.00
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 31.20 10.60 23.10 Wetbulb [C] 6.70 200.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 26.00 35      
Feb 0.00 0      
Mar 0.00 0      
Apr 29.00 23      
May 0.00 0      
Jun 107.00 45      
Jul 72.00 29      
Aug 0.00 0      
Sep 20.00 11      
Oct 0.00 0      
Nov 0.00 0      
Dec 4.00 8      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 27.59 27.59 180.00 90.00 S
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 8.18 6.23 90.00 90.00 E
S_REARSTAIRSFLR1_0_0_0 S_REARSTAIRSFLR1_0_0_0_FFACTOR 1.00 0.468 0.506 20.07 20.07 90.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 6.13 3.44 180.00 90.00 S
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 10.22 8.27 90.00 90.00 E
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 6.13 1.69 0.00 90.00 N
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 10.22 7.53 270.00 90.00 W
S_CORRIDORFLR1_0_0_0 S_CORRIDORFLR1_0_0_0_FFACTOR 1.00 0.057 0.058 150.51 150.51 90.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 27.59 27.59 180.00 90.00 S
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 8.18 8.18 270.00 90.00 W
S_REARSTORAGEFLR1_0_0_0 S_REARSTORAGEFLR1_0_0_0_FFACTOR 1.00 0.468 0.506 20.07 20.07 90.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 27.59 27.59 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 66.43 51.60 270.00 90.00 W
S_FRONTLOUNGEFLR1_0_0_0 S_FRONTLOUNGEFLR1_0_0_0_FFACTOR 1.00 0.152 0.155 163.06 163.06 90.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 13.29 13.29 270.00 90.00 W
S_RESTROOMFLR1_0_0_0 S_RESTROOMFLR1_0_0_0_FFACTOR 1.00 0.107 0.109 32.61 32.61 90.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 32.70 27.77 270.00 90.00 W
S_MEETINGROOMFLR1_0_0_0 S_MEETINGROOMFLR1_0_0_0_FFACTOR 1.00 0.107 0.109 80.27 80.27 90.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 13.29 13.29 270.00 90.00 W
S_MECHANICALROOMFLR1_0_0_0 S_MECHANICALROOMFLR1_0_0_0_FFACTOR 1.00 0.107 0.109 32.61 32.61 90.00 180.00  
W_GUESTROOM101_5_0_0 RES_EXT_WALL_GRD 0.30 0.442 0.473 13.29 11.64 270.00 90.00 W
S_GUESTROOM101_0_0_0 S_GUESTROOM101_0_0_0_FFACTOR 1.00 0.107 0.109 32.61 32.61 90.00 180.00  
W_GUESTROOM102_5_0_0 RES_EXT_WALL_GRD 0.30 0.442 0.473 13.29 11.64 270.00 90.00 W
S_GUESTROOM102_0_0_0 S_GUESTROOM102_0_0_0_FFACTOR 1.00 0.107 0.109 32.61 32.61 90.00 180.00  
W_GUESTROOM103_5_0_0 RES_EXT_WALL_GRD 0.30 0.442 0.473 13.29 11.64 270.00 90.00 W
S_GUESTROOM103_0_0_0 S_GUESTROOM103_0_0_0_FFACTOR 1.00 0.107 0.109 32.61 32.61 90.00 180.00  
W_GUESTROOM104_3_0_0 RES_EXT_WALL_GRD 0.30 0.442 0.473 13.29 11.64 90.00 90.00 E
S_GUESTROOM104_0_0_0 S_GUESTROOM104_0_0_0_FFACTOR 1.00 0.107 0.109 32.61 32.61 90.00 180.00  
W_GUESTROOM105_3_0_0 RES_EXT_WALL_GRD 0.30 0.442 0.473 13.29 11.64 90.00 90.00 E
S_GUESTROOM105_0_0_0 S_GUESTROOM105_0_0_0_FFACTOR 1.00 0.107 0.109 32.61 32.61 90.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 13.29 11.64 90.00 90.00 E
S_EMPLOYEELOUNGEFLR1_0_0_0 S_EMPLOYEELOUNGEFLR1_0_0_0_FFACTOR 1.00 0.107 0.109 32.61 32.61 90.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 39.86 34.93 90.00 90.00 E
S_LAUNDRYROOMFLR1_0_0_0 S_LAUNDRYROOMFLR1_0_0_0_FFACTOR 1.00 0.107 0.109 97.83 97.83 90.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 6.13 6.13 90.00 90.00 E
S_ELEVATORCOREFLR1_0_0_0 S_ELEVATORCOREFLR1_0_0_0_FFACTOR 1.00 0.107 0.109 15.05 15.05 90.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 13.29 11.64 90.00 90.00 E
S_EXERCISECENTERFLR1_0_0_0 S_EXERCISECENTERFLR1_0_0_0_FFACTOR 1.00 0.107 0.109 32.61 32.61 90.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 53.14 46.57 90.00 90.00 E
S_FRONTOFFICEFLR1_0_0_0 S_FRONTOFFICEFLR1_0_0_0_FFACTOR 1.00 0.107 0.109 130.44 130.44 90.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 8.18 6.22 90.00 90.00 E
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 27.59 27.59 0.00 90.00 N
S_FRONTSTAIRSFLR1_0_0_0 S_FRONTSTAIRSFLR1_0_0_0_FFACTOR 1.00 0.468 0.506 20.07 20.07 90.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL_GRD 0.30 0.442 0.473 5.11 5.11 90.00 90.00 E
S_FRONTSTORAGEFLR1_0_0_0 S_FRONTSTORAGEFLR1_0_0_0_FFACTOR 1.00 0.107 0.109 12.54 12.54 90.00 180.00  
W_REARSTAIRSFLR2_2_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 22.58 22.58 180.00 90.00 S
W_REARSTAIRSFLR2_3_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 6.69 6.69 90.00 90.00 E
W_CORRIDORFLR2_2_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 5.02 3.71 180.00 90.00 S
W_CORRIDORFLR2_9_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 8.36 8.36 90.00 90.00 E
W_CORRIDORFLR2_15_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 5.02 3.71 0.00 90.00 N
W_REARSTORAGEFLR2_2_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 22.58 22.58 180.00 90.00 S
W_REARSTORAGEFLR2_5_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 6.69 6.69 270.00 90.00 W
W_GUESTROOM201_4_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 22.58 22.58 0.00 90.00 N
W_GUESTROOM201_5_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 10.87 9.22 270.00 90.00 W
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 43.48 36.88 270.00 90.00 W
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 35.12 28.41 270.00 90.00 W
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 43.48 36.88 270.00 90.00 W
W_GUESTROOM213_5_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 10.87 9.22 270.00 90.00 W
W_GUESTROOM214_3_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 10.87 9.22 90.00 90.00 E
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 43.48 36.88 90.00 90.00 E
W_ELEVATORCOREFLR2_3_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 5.02 5.02 90.00 90.00 E
W_GUESTROOM219_3_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 10.87 9.22 90.00 90.00 E
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 43.48 36.88 90.00 90.00 E
W_GUESTROOM224_3_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 10.87 9.22 90.00 90.00 E
W_FRONTSTORAGEFLR2_3_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 4.18 4.18 90.00 90.00 E
W_FRONTSTAIRSFLR2_3_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 6.69 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR2_4_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 22.58 22.58 0.00 90.00 N
W_REARSTAIRSFLR3_2_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 22.58 22.58 180.00 90.00 S
W_REARSTAIRSFLR3_3_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 6.69 6.69 90.00 90.00 E
W_CORRIDORFLR3_2_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 5.02 3.71 180.00 90.00 S
W_CORRIDORFLR3_9_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 8.36 8.36 90.00 90.00 E
W_CORRIDORFLR3_15_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 5.02 3.71 0.00 90.00 N
W_REARSTORAGEFLR3_2_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 22.58 22.58 180.00 90.00 S
W_REARSTORAGEFLR3_5_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 6.69 6.69 270.00 90.00 W
W_GUESTROOM301_4_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 22.58 22.58 0.00 90.00 N
W_GUESTROOM301_5_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 10.87 9.22 270.00 90.00 W
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 43.48 36.90 270.00 90.00 W
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 35.12 28.42 270.00 90.00 W
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 43.48 36.90 270.00 90.00 W
W_GUESTROOM313_5_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 10.87 9.22 270.00 90.00 W
W_GUESTROOM314_3_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 10.87 9.22 90.00 90.00 E
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 43.48 36.90 90.00 90.00 E
W_ELEVATORCOREFLR3_3_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 5.02 5.02 90.00 90.00 E
W_GUESTROOM319_3_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 10.87 9.22 90.00 90.00 E
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 43.48 36.90 90.00 90.00 E
W_GUESTROOM324_3_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 10.87 9.22 90.00 90.00 E
W_FRONTSTORAGEFLR3_3_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 4.18 4.18 90.00 90.00 E
W_FRONTSTAIRSFLR3_3_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 6.69 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR3_4_0_0 NONRES_EXT_WALL_MID 0.30 0.498 0.539 22.58 22.58 0.00 90.00 N
W_REARSTAIRSFLR4_2_0_0 NONRES_EXT_WALL_TOP 0.30 0.765 0.864 22.58 22.58 180.00 90.00 S
W_REARSTAIRSFLR4_3_0_0 NONRES_EXT_WALL_TOP 0.30 0.765 0.864 6.69 6.69 90.00 90.00 E
R_REARSTAIRSFLR4_1_0_0 NONRES_ROOF 0.23 0.182 0.186 20.07 20.07 270.00 0.00  
W_CORRIDORFLR4_2_0_0 NONRES_EXT_WALL_TOP 0.30 0.765 0.864 5.02 3.71 180.00 90.00 S
W_CORRIDORFLR4_9_0_0 NONRES_EXT_WALL_TOP 0.30 0.765 0.864 8.36 8.36 90.00 90.00 E
W_CORRIDORFLR4_15_0_0 NONRES_EXT_WALL_TOP 0.30 0.765 0.864 5.02 3.71 0.00 90.00 N
R_CORRIDORFLR4_1_0_0 NONRES_ROOF 0.23 0.182 0.186 125.42 125.42 270.00 0.00  
W_REARSTORAGEFLR4_2_0_0 NONRES_EXT_WALL_TOP 0.30 0.765 0.864 22.58 22.58 180.00 90.00 S
W_REARSTORAGEFLR4_5_0_0 NONRES_EXT_WALL_TOP 0.30 0.765 0.864 6.69 6.69 270.00 90.00 W
R_REARSTORAGEFLR4_1_0_0 NONRES_ROOF 0.23 0.182 0.186 20.07 20.07 270.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL_TOP 0.30 0.765 0.864 22.58 22.58 0.00 90.00 N
W_GUESTROOM401_5_0_0 RES_EXT_WALL_TOP 0.30 0.765 0.864 10.87 9.22 270.00 90.00 W
R_GUESTROOM401_1_0_0 RES_ROOF 0.23 0.182 0.186 32.61 32.61 270.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL_TOP 0.30 0.765 0.864 43.48 36.90 270.00 90.00 W
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.23 0.182 0.186 130.45 130.45 270.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL_TOP 0.30 0.765 0.864 35.12 28.42 270.00 90.00 W
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.23 0.182 0.186 105.36 105.36 270.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL_TOP 0.30 0.765 0.864 43.48 36.90 270.00 90.00 W
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.23 0.182 0.186 130.45 130.45 270.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL_TOP 0.30 0.765 0.864 10.87 9.22 270.00 90.00 W
R_GUESTROOM413_1_0_0 RES_ROOF 0.23 0.182 0.186 32.61 32.61 270.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL_TOP 0.30 0.765 0.864 10.87 9.22 90.00 90.00 E
R_GUESTROOM414_1_0_0 RES_ROOF 0.23 0.182 0.186 32.61 32.61 270.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL_TOP 0.30 0.765 0.864 43.48 36.90 90.00 90.00 E
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.23 0.182 0.186 130.44 130.44 270.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 NONRES_EXT_WALL_TOP 0.30 0.765 0.864 5.02 5.02 90.00 90.00 E
R_ELEVATORCOREFLR4_1_0_0 NONRES_ROOF 0.23 0.182 0.186 15.05 15.05 270.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL_TOP 0.30 0.765 0.864 10.87 9.22 90.00 90.00 E
R_GUESTROOM419_1_0_0 RES_ROOF 0.23 0.182 0.186 32.61 32.61 270.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL_MID 0.30 0.498 0.539 43.48 36.90 90.00 90.00 E
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.23 0.182 0.186 130.44 130.44 270.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL_TOP 0.30 0.765 0.864 10.87 9.22 90.00 90.00 E
R_GUESTROOM424_1_0_0 RES_ROOF 0.23 0.182 0.186 32.61 32.61 270.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 NONRES_EXT_WALL_TOP 0.30 0.765 0.864 4.18 4.18 90.00 90.00 E
R_FRONTSTORAGEFLR4_1_0_0 NONRES_ROOF 0.23 0.182 0.186 12.54 12.54 270.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 NONRES_EXT_WALL_TOP 0.30 0.765 0.864 6.69 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR4_4_0_0 NONRES_EXT_WALL_TOP 0.30 0.765 0.864 22.58 22.58 0.00 90.00 N
R_FRONTSTAIRSFLR4_1_0_0 NONRES_ROOF 0.23 0.182 0.186 20.07 20.07 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
P_REARSTAIRSFLR1_4_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
P_REARSTAIRSFLR1_5_0_0 INT_WALL 0.30 2.511 6.299 8.18 8.18 270.00 90.00 W
C_REARSTAIRSFLR1_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 20.07 20.07 270.00 0.00  
P_CORRIDORFLR1_10003_0_10002 INT_WALL 0.30 2.511 6.299 8.18 8.18 90.00 90.00 E
P_CORRIDORFLR1_4_0_0 INT_WALL 0.30 2.511 6.299 13.29 13.29 90.00 90.00 E
P_CORRIDORFLR1_5_0_0 INT_WALL 0.30 2.511 6.299 13.29 13.29 90.00 90.00 E
P_CORRIDORFLR1_6_0_0 INT_WALL 0.30 2.511 6.299 13.29 13.29 90.00 90.00 E
P_CORRIDORFLR1_7_0_0 INT_WALL 0.30 2.511 6.299 39.86 39.86 90.00 90.00 E
P_CORRIDORFLR1_8_0_0 INT_WALL 0.30 2.511 6.299 6.13 6.13 90.00 90.00 E
P_CORRIDORFLR1_9_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
P_CORRIDORFLR1_11_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
P_CORRIDORFLR1_12_0_0 INT_WALL 0.30 2.511 6.299 13.29 13.29 90.00 90.00 E
P_CORRIDORFLR1_13_0_0 INT_WALL 0.30 2.511 6.299 53.14 53.14 90.00 90.00 E
P_CORRIDORFLR1_14_0_0 INT_WALL 0.30 2.511 6.299 5.11 5.11 90.00 90.00 E
P_CORRIDORFLR1_15_0_0 INT_WALL 0.30 2.511 6.299 8.18 8.18 90.00 90.00 E
P_CORRIDORFLR1_17_0_0 INT_WALL 0.30 2.511 6.299 66.43 66.43 270.00 90.00 W
P_CORRIDORFLR1_18_0_0 INT_WALL 0.30 2.511 6.299 13.29 13.29 270.00 90.00 W
P_CORRIDORFLR1_19_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
P_CORRIDORFLR1_21_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
P_CORRIDORFLR1_22_0_0 INT_WALL 0.30 2.511 6.299 32.70 32.70 270.00 90.00 W
P_CORRIDORFLR1_23_0_0 INT_WALL 0.30 2.511 6.299 13.29 13.29 270.00 90.00 W
P_CORRIDORFLR1_24_0_0 INT_WALL 0.30 2.511 6.299 13.29 13.29 270.00 90.00 W
P_CORRIDORFLR1_25_0_0 INT_WALL 0.30 2.511 6.299 13.29 13.29 270.00 90.00 W
P_CORRIDORFLR1_26_0_0 INT_WALL 0.30 2.511 6.299 13.29 13.29 270.00 90.00 W
P_CORRIDORFLR1_27_0_0 INT_WALL 0.30 2.511 6.299 8.18 8.18 270.00 90.00 W
C_CORRIDORFLR1_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 125.42 125.42 270.00 0.00  
C_CORRIDORFLR1_1_1_0 INT_SLAB_CEILING 0.30 1.887 3.839 25.09 25.09 270.00 0.00  
P_REARSTORAGEFLR1_10027_0_10025 INT_WALL 0.30 2.511 6.299 8.18 8.18 90.00 90.00 E
P_REARSTORAGEFLR1_4_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
C_REARSTORAGEFLR1_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 20.07 20.07 270.00 0.00  
P_FRONTLOUNGEFLR1_10018_0_10016 INT_WALL 0.30 2.511 6.299 66.43 66.43 90.00 90.00 E
P_FRONTLOUNGEFLR1_2_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
C_FRONTLOUNGEFLR1_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
C_FRONTLOUNGEFLR1_1_1_0 INT_SLAB_CEILING 0.30 1.887 3.839 130.45 130.45 270.00 0.00  
P_RESTROOMFLR1_10019_0_10017 INT_WALL 0.30 2.511 6.299 13.29 13.29 90.00 90.00 E
P_RESTROOMFLR1_10020_0_10018 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
P_RESTROOMFLR1_10033_0_10030 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
C_RESTROOMFLR1_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_MEETINGROOMFLR1_10021_0_10019 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
P_MEETINGROOMFLR1_10022_0_10020 INT_WALL 0.30 2.511 6.299 32.70 32.70 90.00 90.00 E
P_MEETINGROOMFLR1_2_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
C_MEETINGROOMFLR1_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 47.66 47.66 270.00 0.00  
C_MEETINGROOMFLR1_1_1_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_MECHANICALROOMFLR1_10023_0_10021 INT_WALL 0.30 2.511 6.299 13.29 13.29 90.00 90.00 E
P_MECHANICALROOMFLR1_10041_0_10034 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
P_MECHANICALROOMFLR1_2_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
C_MECHANICALROOMFLR1_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_GUESTROOM101_10024_0_10022 INT_WALL 0.30 2.511 6.299 13.29 13.29 90.00 90.00 E
P_GUESTROOM101_10045_0_10036 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
P_GUESTROOM101_2_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
C_GUESTROOM101_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_GUESTROOM102_10025_0_10023 INT_WALL 0.30 2.511 6.299 13.29 13.29 90.00 90.00 E
P_GUESTROOM102_10049_0_10038 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
P_GUESTROOM102_2_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
C_GUESTROOM102_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_GUESTROOM103_10026_0_10024 INT_WALL 0.30 2.511 6.299 13.29 13.29 90.00 90.00 E
P_GUESTROOM103_10030_0_10027 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
P_GUESTROOM103_10053_0_10040 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
C_GUESTROOM103_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_GUESTROOM104_10002_0_10001 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
P_GUESTROOM104_10007_0_10005 INT_WALL 0.30 2.511 6.299 13.29 13.29 270.00 90.00 W
P_GUESTROOM104_4_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
C_GUESTROOM104_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_GUESTROOM105_10008_0_10006 INT_WALL 0.30 2.511 6.299 13.29 13.29 270.00 90.00 W
P_GUESTROOM105_10062_0_10043 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
P_GUESTROOM105_4_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
C_GUESTROOM105_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_EMPLOYEELOUNGEFLR1_10009_0_10007 INT_WALL 0.30 2.511 6.299 13.29 13.29 270.00 90.00 W
P_EMPLOYEELOUNGEFLR1_10066_0_10045 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
P_EMPLOYEELOUNGEFLR1_4_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
C_EMPLOYEELOUNGEFLR1_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_LAUNDRYROOMFLR1_10010_0_10008 INT_WALL 0.30 2.511 6.299 39.86 39.86 270.00 90.00 W
P_LAUNDRYROOMFLR1_10070_0_10047 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
P_LAUNDRYROOMFLR1_4_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
C_LAUNDRYROOMFLR1_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 65.22 65.22 270.00 0.00  
C_LAUNDRYROOMFLR1_1_1_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_ELEVATORCOREFLR1_10011_0_10009 INT_WALL 0.30 2.511 6.299 6.13 6.13 270.00 90.00 W
P_ELEVATORCOREFLR1_10012_0_10010 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
P_ELEVATORCOREFLR1_10075_0_10050 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
C_ELEVATORCOREFLR1_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 15.05 15.05 270.00 0.00  
P_EXERCISECENTERFLR1_10013_0_10011 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
P_EXERCISECENTERFLR1_10014_0_10012 INT_WALL 0.30 2.511 6.299 13.29 13.29 270.00 90.00 W
P_EXERCISECENTERFLR1_4_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
C_EXERCISECENTERFLR1_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_FRONTOFFICEFLR1_10015_0_10013 INT_WALL 0.30 2.511 6.299 53.14 53.14 270.00 90.00 W
P_FRONTOFFICEFLR1_10083_0_10053 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
P_FRONTOFFICEFLR1_4_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
C_FRONTOFFICEFLR1_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 97.83 97.83 270.00 0.00  
C_FRONTOFFICEFLR1_1_1_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_FRONTSTAIRSFLR1_10017_0_10015 INT_WALL 0.30 2.511 6.299 8.18 8.18 270.00 90.00 W
P_FRONTSTAIRSFLR1_2_0_0 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
C_FRONTSTAIRSFLR1_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 20.07 20.07 270.00 0.00  
P_FRONTSTORAGEFLR1_10016_0_10014 INT_WALL 0.30 2.511 6.299 5.11 5.11 270.00 90.00 W
P_FRONTSTORAGEFLR1_10088_0_10056 INT_WALL 0.30 2.511 6.299 27.59 27.59 180.00 90.00 S
P_FRONTSTORAGEFLR1_10091_0_10058 INT_WALL 0.30 2.511 6.299 27.59 27.59 0.00 90.00 N
C_FRONTSTORAGEFLR1_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 12.54 12.54 270.00 0.00  
P_REARSTAIRSFLR2_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_REARSTAIRSFLR2_5_0_0 INT_WALL 0.30 2.511 6.299 6.69 6.69 270.00 90.00 W
F_REARSTAIRSFLR2_10001_0_10000 INT_SLAB_FLOOR 0.30 1.887 3.839 20.07 20.07 90.00 180.00  
C_REARSTAIRSFLR2_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 20.07 20.07 270.00 0.00  
P_CORRIDORFLR2_10100_0_10062 INT_WALL 0.30 2.511 6.299 6.69 6.69 90.00 90.00 E
P_CORRIDORFLR2_4_0_0 INT_WALL 0.30 2.511 6.299 10.87 10.87 90.00 90.00 E
P_CORRIDORFLR2_5_0_0 INT_WALL 0.30 2.511 6.299 43.48 43.48 90.00 90.00 E
P_CORRIDORFLR2_6_0_0 INT_WALL 0.30 2.511 6.299 10.87 10.87 90.00 90.00 E
P_CORRIDORFLR2_7_0_0 INT_WALL 0.30 2.511 6.299 5.02 5.02 90.00 90.00 E
P_CORRIDORFLR2_8_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_CORRIDORFLR2_10_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_CORRIDORFLR2_11_0_0 INT_WALL 0.30 2.511 6.299 43.48 43.48 90.00 90.00 E
P_CORRIDORFLR2_12_0_0 INT_WALL 0.30 2.511 6.299 10.87 10.87 90.00 90.00 E
P_CORRIDORFLR2_13_0_0 INT_WALL 0.30 2.511 6.299 4.18 4.18 90.00 90.00 E
P_CORRIDORFLR2_14_0_0 INT_WALL 0.30 2.511 6.299 6.69 6.69 90.00 90.00 E
P_CORRIDORFLR2_16_0_0 INT_WALL 0.30 2.511 6.299 10.87 10.87 270.00 90.00 W
P_CORRIDORFLR2_17_0_0 INT_WALL 0.30 2.511 6.299 43.48 43.48 270.00 90.00 W
P_CORRIDORFLR2_18_0_0 INT_WALL 0.30 2.511 6.299 35.12 35.12 270.00 90.00 W
P_CORRIDORFLR2_19_0_0 INT_WALL 0.30 2.511 6.299 43.48 43.48 270.00 90.00 W
P_CORRIDORFLR2_20_0_0 INT_WALL 0.30 2.511 6.299 10.87 10.87 270.00 90.00 W
P_CORRIDORFLR2_21_0_0 INT_WALL 0.30 2.511 6.299 6.69 6.69 270.00 90.00 W
F_CORRIDORFLR2_10004_0_10003 INT_SLAB_FLOOR 0.30 1.887 3.839 125.42 125.42 90.00 180.00  
C_CORRIDORFLR2_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 125.42 125.42 270.00 0.00  
P_REARSTORAGEFLR2_10119_0_10079 INT_WALL 0.30 2.511 6.299 6.69 6.69 90.00 90.00 E
P_REARSTORAGEFLR2_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_REARSTORAGEFLR2_10028_0_10026 INT_SLAB_FLOOR 0.30 1.887 3.839 20.07 20.07 90.00 180.00  
C_REARSTORAGEFLR2_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 20.07 20.07 270.00 0.00  
P_GUESTROOM201_10114_0_10074 INT_WALL 0.30 2.511 6.299 10.87 10.87 90.00 90.00 E
P_GUESTROOM201_2_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_GUESTROOM201_10031_0_10028 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
C_GUESTROOM201_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_GUESTROOM202_205_10115_0_10075 INT_WALL 0.30 2.511 6.299 43.48 43.48 90.00 90.00 E
P_GUESTROOM202_205_10126_0_10083 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_GUESTROOM202_205_2_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_GUESTROOM202_205_10032_0_10029 INT_SLAB_FLOOR 0.30 1.887 3.839 130.45 130.45 90.00 180.00  
C_GUESTROOM202_205_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 130.45 130.45 270.00 0.00  
P_GUESTROOM206_208_10116_0_10076 INT_WALL 0.30 2.511 6.299 35.12 35.12 90.00 90.00 E
P_GUESTROOM206_208_10130_0_10085 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_GUESTROOM206_208_2_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_GUESTROOM206_208_10005_0_10004 INT_SLAB_FLOOR 0.30 1.887 3.839 25.09 25.09 90.00 180.00  
F_GUESTROOM206_208_10035_0_10031 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
F_GUESTROOM206_208_10039_0_10032 INT_SLAB_FLOOR 0.30 1.887 3.839 47.66 47.66 90.00 180.00  
C_GUESTROOM206_208_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 105.36 105.36 270.00 0.00  
P_GUESTROOM209_212_10117_0_10077 INT_WALL 0.30 2.511 6.299 43.48 43.48 90.00 90.00 E
P_GUESTROOM209_212_10137_0_10087 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_GUESTROOM209_212_2_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_GUESTROOM209_212_10040_0_10033 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
F_GUESTROOM209_212_10044_0_10035 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
F_GUESTROOM209_212_10048_0_10037 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
F_GUESTROOM209_212_10052_0_10039 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
C_GUESTROOM209_212_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 130.45 130.45 270.00 0.00  
P_GUESTROOM213_10118_0_10078 INT_WALL 0.30 2.511 6.299 10.87 10.87 90.00 90.00 E
P_GUESTROOM213_10123_0_10081 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM213_10145_0_10089 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM213_10056_0_10041 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
C_GUESTROOM213_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_GUESTROOM214_10099_0_10061 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM214_10104_0_10064 INT_WALL 0.30 2.511 6.299 10.87 10.87 270.00 90.00 W
P_GUESTROOM214_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM214_10060_0_10042 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
C_GUESTROOM214_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_GUESTROOM215_218_10105_0_10065 INT_WALL 0.30 2.511 6.299 43.48 43.48 270.00 90.00 W
P_GUESTROOM215_218_10156_0_10092 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM215_218_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM215_218_10064_0_10044 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
F_GUESTROOM215_218_10068_0_10046 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
F_GUESTROOM215_218_10072_0_10048 INT_SLAB_FLOOR 0.30 1.887 3.839 65.22 65.22 90.00 180.00  
C_GUESTROOM215_218_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 130.44 130.44 270.00 0.00  
P_ELEVATORCOREFLR2_10107_0_10067 INT_WALL 0.30 2.511 6.299 5.02 5.02 270.00 90.00 W
P_ELEVATORCOREFLR2_10108_0_10068 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_ELEVATORCOREFLR2_2_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_ELEVATORCOREFLR2_10077_0_10051 INT_SLAB_FLOOR 0.30 1.887 3.839 15.05 15.05 90.00 180.00  
C_ELEVATORCOREFLR2_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 15.05 15.05 270.00 0.00  
P_GUESTROOM219_10106_0_10066 INT_WALL 0.30 2.511 6.299 10.87 10.87 270.00 90.00 W
P_GUESTROOM219_10163_0_10094 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM219_10167_0_10096 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM219_10073_0_10049 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
C_GUESTROOM219_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_GUESTROOM220_223_10109_0_10069 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM220_223_10110_0_10070 INT_WALL 0.30 2.511 6.299 43.48 43.48 270.00 90.00 W
P_GUESTROOM220_223_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM220_223_10081_0_10052 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
F_GUESTROOM220_223_10085_0_10054 INT_SLAB_FLOOR 0.30 1.887 3.839 97.83 97.83 90.00 180.00  
C_GUESTROOM220_223_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 130.44 130.44 270.00 0.00  
P_GUESTROOM224_10111_0_10071 INT_WALL 0.30 2.511 6.299 10.87 10.87 270.00 90.00 W
P_GUESTROOM224_10179_0_10099 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM224_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM224_10086_0_10055 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
C_GUESTROOM224_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_FRONTSTORAGEFLR2_10112_0_10072 INT_WALL 0.30 2.511 6.299 4.18 4.18 270.00 90.00 W
P_FRONTSTORAGEFLR2_10184_0_10101 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_FRONTSTORAGEFLR2_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_FRONTSTORAGEFLR2_10093_0_10059 INT_SLAB_FLOOR 0.30 1.887 3.839 12.54 12.54 90.00 180.00  
C_FRONTSTORAGEFLR2_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 12.54 12.54 270.00 0.00  
P_FRONTSTAIRSFLR2_10113_0_10073 INT_WALL 0.30 2.511 6.299 6.69 6.69 270.00 90.00 W
P_FRONTSTAIRSFLR2_10189_0_10103 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_FRONTSTAIRSFLR2_10090_0_10057 INT_SLAB_FLOOR 0.30 1.887 3.839 20.07 20.07 90.00 180.00  
C_FRONTSTAIRSFLR2_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 20.07 20.07 270.00 0.00  
P_REARSTAIRSFLR3_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_REARSTAIRSFLR3_5_0_0 INT_WALL 0.30 2.511 6.299 6.69 6.69 270.00 90.00 W
F_REARSTAIRSFLR3_10098_0_10060 INT_SLAB_FLOOR 0.30 1.887 3.839 20.07 20.07 90.00 180.00  
C_REARSTAIRSFLR3_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 20.07 20.07 270.00 0.00  
P_CORRIDORFLR3_10198_0_10107 INT_WALL 0.30 2.511 6.299 6.69 6.69 90.00 90.00 E
P_CORRIDORFLR3_4_0_0 INT_WALL 0.30 2.511 6.299 10.87 10.87 90.00 90.00 E
P_CORRIDORFLR3_5_0_0 INT_WALL 0.30 2.511 6.299 43.48 43.48 90.00 90.00 E
P_CORRIDORFLR3_6_0_0 INT_WALL 0.30 2.511 6.299 10.87 10.87 90.00 90.00 E
P_CORRIDORFLR3_7_0_0 INT_WALL 0.30 2.511 6.299 5.02 5.02 90.00 90.00 E
P_CORRIDORFLR3_8_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_CORRIDORFLR3_10_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_CORRIDORFLR3_11_0_0 INT_WALL 0.30 2.511 6.299 43.48 43.48 90.00 90.00 E
P_CORRIDORFLR3_12_0_0 INT_WALL 0.30 2.511 6.299 10.87 10.87 90.00 90.00 E
P_CORRIDORFLR3_13_0_0 INT_WALL 0.30 2.511 6.299 4.18 4.18 90.00 90.00 E
P_CORRIDORFLR3_14_0_0 INT_WALL 0.30 2.511 6.299 6.69 6.69 90.00 90.00 E
P_CORRIDORFLR3_16_0_0 INT_WALL 0.30 2.511 6.299 10.87 10.87 270.00 90.00 W
P_CORRIDORFLR3_17_0_0 INT_WALL 0.30 2.511 6.299 43.48 43.48 270.00 90.00 W
P_CORRIDORFLR3_18_0_0 INT_WALL 0.30 2.511 6.299 35.12 35.12 270.00 90.00 W
P_CORRIDORFLR3_19_0_0 INT_WALL 0.30 2.511 6.299 43.48 43.48 270.00 90.00 W
P_CORRIDORFLR3_20_0_0 INT_WALL 0.30 2.511 6.299 10.87 10.87 270.00 90.00 W
P_CORRIDORFLR3_21_0_0 INT_WALL 0.30 2.511 6.299 6.69 6.69 270.00 90.00 W
F_CORRIDORFLR3_10102_0_10063 INT_SLAB_FLOOR 0.30 1.887 3.839 125.42 125.42 90.00 180.00  
C_CORRIDORFLR3_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 125.42 125.42 270.00 0.00  
P_REARSTORAGEFLR3_10217_0_10124 INT_WALL 0.30 2.511 6.299 6.69 6.69 90.00 90.00 E
P_REARSTORAGEFLR3_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_REARSTORAGEFLR3_10121_0_10080 INT_SLAB_FLOOR 0.30 1.887 3.839 20.07 20.07 90.00 180.00  
C_REARSTORAGEFLR3_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 20.07 20.07 270.00 0.00  
P_GUESTROOM301_10212_0_10119 INT_WALL 0.30 2.511 6.299 10.87 10.87 90.00 90.00 E
P_GUESTROOM301_2_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_GUESTROOM301_10125_0_10082 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
C_GUESTROOM301_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_GUESTROOM302_305_10213_0_10120 INT_WALL 0.30 2.511 6.299 43.48 43.48 90.00 90.00 E
P_GUESTROOM302_305_10224_0_10128 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_GUESTROOM302_305_2_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_GUESTROOM302_305_10129_0_10084 INT_SLAB_FLOOR 0.30 1.887 3.839 130.45 130.45 90.00 180.00  
C_GUESTROOM302_305_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 130.45 130.45 270.00 0.00  
P_GUESTROOM306_308_10214_0_10121 INT_WALL 0.30 2.511 6.299 35.12 35.12 90.00 90.00 E
P_GUESTROOM306_308_10228_0_10130 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_GUESTROOM306_308_2_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_GUESTROOM306_308_10136_0_10086 INT_SLAB_FLOOR 0.30 1.887 3.839 105.36 105.36 90.00 180.00  
C_GUESTROOM306_308_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 105.36 105.36 270.00 0.00  
P_GUESTROOM309_312_10215_0_10122 INT_WALL 0.30 2.511 6.299 43.48 43.48 90.00 90.00 E
P_GUESTROOM309_312_10233_0_10132 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_GUESTROOM309_312_2_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_GUESTROOM309_312_10144_0_10088 INT_SLAB_FLOOR 0.30 1.887 3.839 130.45 130.45 90.00 180.00  
C_GUESTROOM309_312_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 130.45 130.45 270.00 0.00  
P_GUESTROOM313_10216_0_10123 INT_WALL 0.30 2.511 6.299 10.87 10.87 90.00 90.00 E
P_GUESTROOM313_10221_0_10126 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM313_10238_0_10134 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM313_10149_0_10090 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
C_GUESTROOM313_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_GUESTROOM314_10197_0_10106 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM314_10202_0_10109 INT_WALL 0.30 2.511 6.299 10.87 10.87 270.00 90.00 W
P_GUESTROOM314_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM314_10154_0_10091 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
C_GUESTROOM314_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_GUESTROOM315_318_10203_0_10110 INT_WALL 0.30 2.511 6.299 43.48 43.48 270.00 90.00 W
P_GUESTROOM315_318_10249_0_10137 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM315_318_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM315_318_10161_0_10093 INT_SLAB_FLOOR 0.30 1.887 3.839 130.44 130.44 90.00 180.00  
C_GUESTROOM315_318_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 130.44 130.44 270.00 0.00  
P_ELEVATORCOREFLR3_10205_0_10112 INT_WALL 0.30 2.511 6.299 5.02 5.02 270.00 90.00 W
P_ELEVATORCOREFLR3_10206_0_10113 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_ELEVATORCOREFLR3_2_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_ELEVATORCOREFLR3_10166_0_10095 INT_SLAB_FLOOR 0.30 1.887 3.839 15.05 15.05 90.00 180.00  
C_ELEVATORCOREFLR3_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 15.05 15.05 270.00 0.00  
P_GUESTROOM319_10204_0_10111 INT_WALL 0.30 2.511 6.299 10.87 10.87 270.00 90.00 W
P_GUESTROOM319_10254_0_10139 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM319_10258_0_10141 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM319_10171_0_10097 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
C_GUESTROOM319_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_GUESTROOM320_323_10207_0_10114 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM320_323_10208_0_10115 INT_WALL 0.30 2.511 6.299 43.48 43.48 270.00 90.00 W
P_GUESTROOM320_323_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM320_323_10177_0_10098 INT_SLAB_FLOOR 0.30 1.887 3.839 130.44 130.44 90.00 180.00  
C_GUESTROOM320_323_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 130.44 130.44 270.00 0.00  
P_GUESTROOM324_10209_0_10116 INT_WALL 0.30 2.511 6.299 10.87 10.87 270.00 90.00 W
P_GUESTROOM324_10269_0_10144 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM324_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM324_10182_0_10100 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
C_GUESTROOM324_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 32.61 32.61 270.00 0.00  
P_FRONTSTORAGEFLR3_10210_0_10117 INT_WALL 0.30 2.511 6.299 4.18 4.18 270.00 90.00 W
P_FRONTSTORAGEFLR3_10274_0_10146 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_FRONTSTORAGEFLR3_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_FRONTSTORAGEFLR3_10187_0_10102 INT_SLAB_FLOOR 0.30 1.887 3.839 12.54 12.54 90.00 180.00  
C_FRONTSTORAGEFLR3_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 12.54 12.54 270.00 0.00  
P_FRONTSTAIRSFLR3_10211_0_10118 INT_WALL 0.30 2.511 6.299 6.69 6.69 270.00 90.00 W
P_FRONTSTAIRSFLR3_10279_0_10148 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_FRONTSTAIRSFLR3_10192_0_10104 INT_SLAB_FLOOR 0.30 1.887 3.839 20.07 20.07 90.00 180.00  
C_FRONTSTAIRSFLR3_1_0_0 INT_SLAB_CEILING 0.30 1.887 3.839 20.07 20.07 270.00 0.00  
P_REARSTAIRSFLR4_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_REARSTAIRSFLR4_5_0_0 INT_WALL 0.30 2.511 6.299 6.69 6.69 270.00 90.00 W
F_REARSTAIRSFLR4_10196_0_10105 INT_SLAB_FLOOR 0.30 1.887 3.839 20.07 20.07 90.00 180.00  
P_CORRIDORFLR4_10287_0_10151 INT_WALL 0.30 2.511 6.299 6.69 6.69 90.00 90.00 E
P_CORRIDORFLR4_4_0_0 INT_WALL 0.30 2.511 6.299 10.87 10.87 90.00 90.00 E
P_CORRIDORFLR4_5_0_0 INT_WALL 0.30 2.511 6.299 43.48 43.48 90.00 90.00 E
P_CORRIDORFLR4_6_0_0 INT_WALL 0.30 2.511 6.299 10.87 10.87 90.00 90.00 E
P_CORRIDORFLR4_7_0_0 INT_WALL 0.30 2.511 6.299 5.02 5.02 90.00 90.00 E
P_CORRIDORFLR4_8_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_CORRIDORFLR4_10_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_CORRIDORFLR4_11_0_0 INT_WALL 0.30 2.511 6.299 43.48 43.48 90.00 90.00 E
P_CORRIDORFLR4_12_0_0 INT_WALL 0.30 2.511 6.299 10.87 10.87 90.00 90.00 E
P_CORRIDORFLR4_13_0_0 INT_WALL 0.30 2.511 6.299 4.18 4.18 90.00 90.00 E
P_CORRIDORFLR4_14_0_0 INT_WALL 0.30 2.511 6.299 6.69 6.69 90.00 90.00 E
P_CORRIDORFLR4_16_0_0 INT_WALL 0.30 2.511 6.299 10.87 10.87 270.00 90.00 W
P_CORRIDORFLR4_17_0_0 INT_WALL 0.30 2.511 6.299 43.48 43.48 270.00 90.00 W
P_CORRIDORFLR4_18_0_0 INT_WALL 0.30 2.511 6.299 35.12 35.12 270.00 90.00 W
P_CORRIDORFLR4_19_0_0 INT_WALL 0.30 2.511 6.299 43.48 43.48 270.00 90.00 W
P_CORRIDORFLR4_20_0_0 INT_WALL 0.30 2.511 6.299 10.87 10.87 270.00 90.00 W
P_CORRIDORFLR4_21_0_0 INT_WALL 0.30 2.511 6.299 6.69 6.69 270.00 90.00 W
F_CORRIDORFLR4_10200_0_10108 INT_SLAB_FLOOR 0.30 1.887 3.839 125.42 125.42 90.00 180.00  
P_REARSTORAGEFLR4_10305_0_10167 INT_WALL 0.30 2.511 6.299 6.69 6.69 90.00 90.00 E
P_REARSTORAGEFLR4_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_REARSTORAGEFLR4_10219_0_10125 INT_SLAB_FLOOR 0.30 1.887 3.839 20.07 20.07 90.00 180.00  
P_GUESTROOM401_10300_0_10162 INT_WALL 0.30 2.511 6.299 10.87 10.87 90.00 90.00 E
P_GUESTROOM401_2_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_GUESTROOM401_10223_0_10127 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
P_GUESTROOM402_405_10301_0_10163 INT_WALL 0.30 2.511 6.299 43.48 43.48 90.00 90.00 E
P_GUESTROOM402_405_10310_0_10169 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_GUESTROOM402_405_2_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_GUESTROOM402_405_10227_0_10129 INT_SLAB_FLOOR 0.30 1.887 3.839 130.45 130.45 90.00 180.00  
P_GUESTROOM406_408_10302_0_10164 INT_WALL 0.30 2.511 6.299 35.12 35.12 90.00 90.00 E
P_GUESTROOM406_408_10313_0_10170 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_GUESTROOM406_408_2_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_GUESTROOM406_408_10232_0_10131 INT_SLAB_FLOOR 0.30 1.887 3.839 105.36 105.36 90.00 180.00  
P_GUESTROOM409_412_10303_0_10165 INT_WALL 0.30 2.511 6.299 43.48 43.48 90.00 90.00 E
P_GUESTROOM409_412_10317_0_10171 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_GUESTROOM409_412_2_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_GUESTROOM409_412_10237_0_10133 INT_SLAB_FLOOR 0.30 1.887 3.839 130.45 130.45 90.00 180.00  
P_GUESTROOM413_10304_0_10166 INT_WALL 0.30 2.511 6.299 10.87 10.87 90.00 90.00 E
P_GUESTROOM413_10308_0_10168 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM413_10321_0_10172 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM413_10242_0_10135 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
P_GUESTROOM414_10286_0_10150 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM414_10290_0_10152 INT_WALL 0.30 2.511 6.299 10.87 10.87 270.00 90.00 W
P_GUESTROOM414_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM414_10247_0_10136 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
P_GUESTROOM415_418_10291_0_10153 INT_WALL 0.30 2.511 6.299 43.48 43.48 270.00 90.00 W
P_GUESTROOM415_418_10330_0_10173 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM415_418_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM415_418_10252_0_10138 INT_SLAB_FLOOR 0.30 1.887 3.839 130.44 130.44 90.00 180.00  
P_ELEVATORCOREFLR4_10293_0_10155 INT_WALL 0.30 2.511 6.299 5.02 5.02 270.00 90.00 W
P_ELEVATORCOREFLR4_10294_0_10156 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
P_ELEVATORCOREFLR4_2_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_ELEVATORCOREFLR4_10257_0_10140 INT_SLAB_FLOOR 0.30 1.887 3.839 15.05 15.05 90.00 180.00  
P_GUESTROOM419_10292_0_10154 INT_WALL 0.30 2.511 6.299 10.87 10.87 270.00 90.00 W
P_GUESTROOM419_10334_0_10174 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM419_10337_0_10175 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM419_10262_0_10142 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
P_GUESTROOM420_423_10295_0_10157 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM420_423_10296_0_10158 INT_WALL 0.30 2.511 6.299 43.48 43.48 270.00 90.00 W
P_GUESTROOM420_423_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM420_423_10267_0_10143 INT_SLAB_FLOOR 0.30 1.887 3.839 130.44 130.44 90.00 180.00  
P_GUESTROOM424_10297_0_10159 INT_WALL 0.30 2.511 6.299 10.87 10.87 270.00 90.00 W
P_GUESTROOM424_10346_0_10176 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_GUESTROOM424_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_GUESTROOM424_10272_0_10145 INT_SLAB_FLOOR 0.30 1.887 3.839 32.61 32.61 90.00 180.00  
P_FRONTSTORAGEFLR4_10298_0_10160 INT_WALL 0.30 2.511 6.299 4.18 4.18 270.00 90.00 W
P_FRONTSTORAGEFLR4_10350_0_10177 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
P_FRONTSTORAGEFLR4_4_0_0 INT_WALL 0.30 2.511 6.299 22.58 22.58 0.00 90.00 N
F_FRONTSTORAGEFLR4_10277_0_10147 INT_SLAB_FLOOR 0.30 1.887 3.839 12.54 12.54 90.00 180.00  
P_FRONTSTAIRSFLR4_10299_0_10161 INT_WALL 0.30 2.511 6.299 6.69 6.69 270.00 90.00 W
P_FRONTSTAIRSFLR4_10354_0_10178 INT_WALL 0.30 2.511 6.299 22.58 22.58 180.00 90.00 S
F_FRONTSTAIRSFLR4_10282_0_10149 INT_SLAB_FLOOR 0.30 1.887 3.839 20.07 20.07 90.00 180.00  


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 NONRESWINDOW_U_0.3464_SHGC_0.38   2.69 0.00 0.00 2.69 2.69 1.968 0.381 0.381             No W_CORRIDORFLR1_2_0_0 180.00 90.00 S
D_CORRIDORFLR1_16_0_0_0_0 NONRESWINDOW_U_0.3464_SHGC_0.38   4.44 0.00 0.00 4.44 4.44 1.968 0.381 0.381             No W_CORRIDORFLR1_16_0_0 0.00 90.00 N
W_CORRIDORFLR1_20_0_0_0_0 NONRESWINDOW_U_0.3464_SHGC_0.38   2.69 0.00 0.00 2.69 2.69 1.968 0.381 0.381             No W_CORRIDORFLR1_20_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_0 NONRESWINDOW_U_0.3464_SHGC_0.38   2.97 0.00 0.00 2.97 2.97 1.968 0.381 0.381             No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_1 NONRESWINDOW_U_0.3464_SHGC_0.38   2.97 0.00 0.00 2.97 2.97 1.968 0.381 0.381             No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_2 NONRESWINDOW_U_0.3464_SHGC_0.38   2.97 0.00 0.00 2.97 2.97 1.968 0.381 0.381             No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_3 NONRESWINDOW_U_0.3464_SHGC_0.38   2.97 0.00 0.00 2.97 2.97 1.968 0.381 0.381             No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_4 NONRESWINDOW_U_0.3464_SHGC_0.38   2.97 0.00 0.00 2.97 2.97 1.968 0.381 0.381             No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_0 NONRESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_1 NONRESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_2 NONRESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_GUESTROOM101_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_GUESTROOM101_5_0_0 270.00 90.00 W
W_GUESTROOM102_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_GUESTROOM102_5_0_0 270.00 90.00 W
W_GUESTROOM103_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_GUESTROOM103_5_0_0 270.00 90.00 W
W_GUESTROOM104_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_GUESTROOM104_3_0_0 90.00 90.00 E
W_GUESTROOM105_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_GUESTROOM105_3_0_0 90.00 90.00 E
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 NONRESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_EMPLOYEELOUNGEFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_0 NONRESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_1 NONRESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_2 NONRESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_EXERCISECENTERFLR1_3_0_0_0_0 NONRESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_EXERCISECENTERFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_0 NONRESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_1 NONRESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_2 NONRESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_3 NONRESWINDOW_U_0.3464_SHGC_0.38   1.64 0.00 0.00 1.64 1.64 1.968 0.381 0.381             No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_CORRIDORFLR2_2_0_0_0_0 NONRESWINDOW_U_0.3464_SHGC_0.38   1.31 0.00 0.00 1.31 1.31 1.968 0.381 0.381             No W_CORRIDORFLR2_2_0_0 180.00 90.00 S
W_CORRIDORFLR2_15_0_0_0_0 NONRESWINDOW_U_0.3464_SHGC_0.38   1.31 0.00 0.00 1.31 1.31 1.968 0.381 0.381             No W_CORRIDORFLR2_15_0_0 0.00 90.00 N
W_GUESTROOM201_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM201_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_1 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_2 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_3 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_1 RESWINDOW_U_0.3464_SHGC_0.38   3.41 0.00 0.00 3.41 3.41 1.968 0.381 0.381             No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_2 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_1 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_2 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_3 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM213_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM213_5_0_0 270.00 90.00 W
W_GUESTROOM214_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM214_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_1 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_2 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_3 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM219_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM219_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_1 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_2 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_3 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM224_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM224_3_0_0 90.00 90.00 E
W_CORRIDORFLR3_2_0_0_0_0 NONRESWINDOW_U_0.3464_SHGC_0.38   1.31 0.00 0.00 1.31 1.31 1.968 0.381 0.381             No W_CORRIDORFLR3_2_0_0 180.00 90.00 S
W_CORRIDORFLR3_15_0_0_0_0 NONRESWINDOW_U_0.3464_SHGC_0.38   1.31 0.00 0.00 1.31 1.31 1.968 0.381 0.381             No W_CORRIDORFLR3_15_0_0 0.00 90.00 N
W_GUESTROOM301_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM301_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_1 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_2 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_3 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_1 RESWINDOW_U_0.3464_SHGC_0.38   3.41 0.00 0.00 3.41 3.41 1.968 0.381 0.381             No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_2 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_1 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_2 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_3 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM313_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM313_5_0_0 270.00 90.00 W
W_GUESTROOM314_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM314_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_1 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_2 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_3 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM319_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM319_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_1 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_2 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_3 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM324_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM324_3_0_0 90.00 90.00 E
W_CORRIDORFLR4_2_0_0_0_0 NONRESWINDOW_U_0.3464_SHGC_0.38   1.31 0.00 0.00 1.31 1.31 1.968 0.381 0.381             No W_CORRIDORFLR4_2_0_0 180.00 90.00 S
W_CORRIDORFLR4_15_0_0_0_0 NONRESWINDOW_U_0.3464_SHGC_0.38   1.31 0.00 0.00 1.31 1.31 1.968 0.381 0.381             No W_CORRIDORFLR4_15_0_0 0.00 90.00 N
W_GUESTROOM401_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM401_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_1 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_2 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_3 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_1 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_2 RESWINDOW_U_0.3464_SHGC_0.38   3.41 0.00 0.00 3.41 3.41 1.968 0.381 0.381             No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_1 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_2 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_3 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM413_5_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM413_5_0_0 270.00 90.00 W
W_GUESTROOM414_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM414_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_1 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_2 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_3 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM419_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM419_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_1 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_2 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_3 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM424_3_0_0_0_0 RESWINDOW_U_0.3464_SHGC_0.38   1.65 0.00 0.00 1.65 1.65 1.968 0.381 0.381             No W_GUESTROOM424_3_0_0 90.00 90.00 E
Total or Average             184.30 1.968 0.381 0.381                      
North Total or Average             8.38 1.968 0.381 0.381                      
Non-North Total or Average             175.93 1.968 0.381 0.381                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
W_REARSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 W_REARSTAIRSFLR1_3_0_0
W_CORRIDORFLR1_10_0_0_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 W_CORRIDORFLR1_10_0_0
W_FRONTSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 W_FRONTSTAIRSFLR1_3_0_0


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
W_CORRIDORFLR1_2_0_0_0_0 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
D_CORRIDORFLR1_16_0_0_0_0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
W_CORRIDORFLR1_20_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_FRONTLOUNGEFLR1_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_FRONTLOUNGEFLR1_5_0_0_0_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_FRONTLOUNGEFLR1_5_0_0_0_2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_FRONTLOUNGEFLR1_5_0_0_0_3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_FRONTLOUNGEFLR1_5_0_0_0_4 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_MEETINGROOMFLR1_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_MEETINGROOMFLR1_5_0_0_0_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_MEETINGROOMFLR1_5_0_0_0_2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM101_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM102_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM103_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM104_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM105_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_LAUNDRYROOMFLR1_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_LAUNDRYROOMFLR1_3_0_0_0_1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_LAUNDRYROOMFLR1_3_0_0_0_2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_EXERCISECENTERFLR1_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_FRONTOFFICEFLR1_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_FRONTOFFICEFLR1_3_0_0_0_1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_FRONTOFFICEFLR1_3_0_0_0_2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_FRONTOFFICEFLR1_3_0_0_0_3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_CORRIDORFLR2_2_0_0_0_0 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
W_CORRIDORFLR2_15_0_0_0_0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
W_GUESTROOM201_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM202_205_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM202_205_5_0_0_0_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM202_205_5_0_0_0_2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM202_205_5_0_0_0_3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM206_208_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM206_208_5_0_0_0_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM206_208_5_0_0_0_2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM209_212_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM209_212_5_0_0_0_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM209_212_5_0_0_0_2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM209_212_5_0_0_0_3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM213_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM214_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM215_218_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM215_218_3_0_0_0_1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM215_218_3_0_0_0_2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM215_218_3_0_0_0_3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM219_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM220_223_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM220_223_3_0_0_0_1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM220_223_3_0_0_0_2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM220_223_3_0_0_0_3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM224_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_CORRIDORFLR3_2_0_0_0_0 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
W_CORRIDORFLR3_15_0_0_0_0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
W_GUESTROOM301_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM302_305_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM302_305_5_0_0_0_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM302_305_5_0_0_0_2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM302_305_5_0_0_0_3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM306_308_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM306_308_5_0_0_0_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM306_308_5_0_0_0_2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM309_312_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM309_312_5_0_0_0_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM309_312_5_0_0_0_2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM309_312_5_0_0_0_3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM313_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM314_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM315_318_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM315_318_3_0_0_0_1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM315_318_3_0_0_0_2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM315_318_3_0_0_0_3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM319_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM320_323_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM320_323_3_0_0_0_1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM320_323_3_0_0_0_2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM320_323_3_0_0_0_3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM324_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_CORRIDORFLR4_2_0_0_0_0 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
W_CORRIDORFLR4_15_0_0_0_0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
W_GUESTROOM401_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM402_405_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM402_405_5_0_0_0_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM402_405_5_0_0_0_2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM402_405_5_0_0_0_3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM406_408_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM406_408_5_0_0_0_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM406_408_5_0_0_0_2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM409_412_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM409_412_5_0_0_0_1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM409_412_5_0_0_0_2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM409_412_5_0_0_0_3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM413_5_0_0_0_0 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
W_GUESTROOM414_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM415_418_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM415_418_3_0_0_0_1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM415_418_3_0_0_0_2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM415_418_3_0_0_0_3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM419_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM420_423_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM420_423_3_0_0_0_1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM420_423_3_0_0_0_2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM420_423_3_0_0_0_3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
W_GUESTROOM424_3_0_0_0_0 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORRIDORFLR1_LIGHTS CORRIDORFLR1 CORRIDORFLR1 GENERAL 4.4132 150.51 664.21 LightsWired LTG_SCH_CORRIDOR 126.00 168.00 126.00 0.0000 Y 15.71
CORRIDORFLR2_LIGHTS CORRIDORFLR2 CORRIDORFLR2 GENERAL 4.4132 125.42 553.50 LightsWired LTG_SCH_CORRIDOR 126.00 168.00 126.00 0.0000 Y 13.09
CORRIDORFLR3_LIGHTS CORRIDORFLR3 CORRIDORFLR3 GENERAL 4.4132 125.42 553.50 LightsWired LTG_SCH_CORRIDOR 126.00 168.00 126.00 0.0000 Y 13.09
CORRIDORFLR4_LIGHTS CORRIDORFLR4 CORRIDORFLR4 GENERAL 4.4132 125.42 553.50 LightsWired LTG_SCH_CORRIDOR 126.00 168.00 126.00 0.0000 Y 13.09
ELEVATORCOREFLR1_LIGHTS ELEVATORCOREFLR1 ELEVATORCOREFLR1 GENERAL 0.0000 15.05 0.00 LightsWired LTG_SCH_ELEVATOR 0.00 0.00   0.0000 N 0.00
ELEVATORCOREFLR2_LIGHTS ELEVATORCOREFLR2 ELEVATORCOREFLR2 GENERAL 0.0000 15.05 0.00 LightsWired LTG_SCH_ELEVATOR 0.00 0.00   0.0000 N 0.00
ELEVATORCOREFLR3_LIGHTS ELEVATORCOREFLR3 ELEVATORCOREFLR3 GENERAL 0.0000 15.05 0.00 LightsWired LTG_SCH_ELEVATOR 0.00 0.00   0.0000 N 0.00
ELEVATORCOREFLR4_LIGHTS ELEVATORCOREFLR4 ELEVATORCOREFLR4 GENERAL 0.0000 15.05 0.00 LightsWired LTG_SCH_ELEVATOR 0.00 0.00   0.0000 N 0.00
EMPLOYEELOUNGEFLR1_LIGHTS EMPLOYEELOUNGEFLR1 EMPLOYEELOUNGEFLR1 GENERAL 6.3507 32.61 207.09 LightsWired LTG_SCH_LOUNGE 84.35 119.00 84.35 0.0000 Y 3.28
EXERCISECENTERFLR1_LIGHTS EXERCISECENTERFLR1 EXERCISECENTERFLR1 GENERAL 9.6875 32.61 315.90 LightsWired LTG_SCH_EXERCISE 112.00 119.00 112.00 0.0000 Y 6.64
FRONTLOUNGEFLR1_LIGHTS FRONTLOUNGEFLR1 FRONTLOUNGEFLR1 GENERAL 9.0417 163.06 1474.30 LightsWired LTG_SCH_LOBBY 84.35 119.00 44.33 0.0000 Y 12.27
FRONTOFFICEFLR1_LIGHTS FRONTOFFICEFLR1 FRONTOFFICEFLR1 GENERAL 7.6155 130.44 993.33 LightsWired LTG_SCH_OFFICE 74.97 168.00 60.80 0.0000 Y 11.34
FRONTSTAIRSFLR1_LIGHTS FRONTSTAIRSFLR1 FRONTSTAIRSFLR1 GENERAL 5.2743 20.07 105.84 LightsWired LTG_SCH_STAIR 168.00 168.00 168.00 0.0000 Y 3.34
FRONTSTAIRSFLR2_LIGHTS FRONTSTAIRSFLR2 FRONTSTAIRSFLR2 GENERAL 5.2743 20.07 105.84 LightsWired LTG_SCH_STAIR 168.00 168.00 168.00 0.0000 Y 3.34
FRONTSTAIRSFLR3_LIGHTS FRONTSTAIRSFLR3 FRONTSTAIRSFLR3 GENERAL 5.2743 20.07 105.84 LightsWired LTG_SCH_STAIR 168.00 168.00 168.00 0.0000 Y 3.34
FRONTSTAIRSFLR4_LIGHTS FRONTSTAIRSFLR4 FRONTSTAIRSFLR4 GENERAL 5.2743 20.07 105.84 LightsWired LTG_SCH_STAIR 168.00 168.00 168.00 0.0000 Y 3.34
FRONTSTORAGEFLR1_LIGHTS FRONTSTORAGEFLR1 FRONTSTORAGEFLR1 GENERAL 4.0903 12.54 51.30 LightsWired LTG_SCH_STORAGE 18.38 168.00 18.37 0.0000 N 0.18
FRONTSTORAGEFLR2_LIGHTS FRONTSTORAGEFLR2 FRONTSTORAGEFLR2 GENERAL 4.0903 12.54 51.30 LightsWired LTG_SCH_STORAGE 18.38 168.00 18.37 0.0000 N 0.18
FRONTSTORAGEFLR3_LIGHTS FRONTSTORAGEFLR3 FRONTSTORAGEFLR3 GENERAL 4.0903 12.54 51.30 LightsWired LTG_SCH_STORAGE 18.38 168.00 18.37 0.0000 N 0.18
FRONTSTORAGEFLR4_LIGHTS FRONTSTORAGEFLR4 FRONTSTORAGEFLR4 GENERAL 4.0903 12.54 51.30 LightsWired LTG_SCH_STORAGE 18.38 168.00 18.37 0.0000 N 0.18
GUESTROOM101_LIGHTS GUESTROOM101 GUESTROOM101 GENERAL 4.4132 32.61 143.92 LightsWired ALWAYSOFF 0.00 0.00 0.00 0.0000 Y 0.00
GUESTROOM102_LIGHTS GUESTROOM102 GUESTROOM102 GENERAL 4.4132 32.61 143.92 LightsWired ALWAYSOFF 0.00 0.00 0.00 0.0000 Y 0.00
GUESTROOM103_LIGHTS GUESTROOM103 GUESTROOM103 GENERAL 4.4132 32.61 143.92 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 1.29
GUESTROOM104_LIGHTS GUESTROOM104 GUESTROOM104 GENERAL 4.4132 32.61 143.91 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 1.29
GUESTROOM105_LIGHTS GUESTROOM105 GUESTROOM105 GENERAL 4.4132 32.61 143.91 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 1.29
GUESTROOM201_LIGHTS GUESTROOM201 GUESTROOM201 GENERAL 4.4132 32.61 143.92 LightsWired ALWAYSOFF 0.00 0.00 0.00 0.0000 Y 0.00
GUESTROOM202_205_LIGHTS GUESTROOM202_205 GUESTROOM202_205 GENERAL 4.4132 130.45 575.68 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 5.16
GUESTROOM206_208_LIGHTS GUESTROOM206_208 GUESTROOM206_208 GENERAL 4.4132 105.36 464.97 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 4.17
GUESTROOM209_212_LIGHTS GUESTROOM209_212 GUESTROOM209_212 GENERAL 4.4132 130.45 575.68 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 5.16
GUESTROOM213_LIGHTS GUESTROOM213 GUESTROOM213 GENERAL 4.4132 32.61 143.92 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 1.29
GUESTROOM214_LIGHTS GUESTROOM214 GUESTROOM214 GENERAL 4.4132 32.61 143.91 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 1.29
GUESTROOM215_218_LIGHTS GUESTROOM215_218 GUESTROOM215_218 GENERAL 4.4132 130.44 575.64 LightsWired ALWAYSOFF 0.00 0.00 0.00 0.0000 Y 0.00
GUESTROOM219_LIGHTS GUESTROOM219 GUESTROOM219 GENERAL 4.4132 32.61 143.91 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 1.29
GUESTROOM220_223_LIGHTS GUESTROOM220_223 GUESTROOM220_223 GENERAL 4.4132 130.44 575.64 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 5.16
GUESTROOM224_LIGHTS GUESTROOM224 GUESTROOM224 GENERAL 4.4132 32.61 143.91 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 1.29
GUESTROOM301_LIGHTS GUESTROOM301 GUESTROOM301 GENERAL 4.4132 32.61 143.92 LightsWired ALWAYSOFF 0.00 0.00 0.00 0.0000 Y 0.00
GUESTROOM302_305_LIGHTS GUESTROOM302_305 GUESTROOM302_305 GENERAL 4.4132 130.45 575.68 LightsWired ALWAYSOFF 0.00 0.00 0.00 0.0000 Y 0.00
GUESTROOM306_308_LIGHTS GUESTROOM306_308 GUESTROOM306_308 GENERAL 4.4132 105.36 464.97 LightsWired ALWAYSOFF 0.00 0.00 0.00 0.0000 Y 0.00
GUESTROOM309_312_LIGHTS GUESTROOM309_312 GUESTROOM309_312 GENERAL 4.4132 130.45 575.68 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 5.16
GUESTROOM313_LIGHTS GUESTROOM313 GUESTROOM313 GENERAL 4.4132 32.61 143.92 LightsWired ALWAYSOFF 0.00 0.00 0.00 0.0000 Y 0.00
GUESTROOM314_LIGHTS GUESTROOM314 GUESTROOM314 GENERAL 4.4132 32.61 143.91 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 1.29
GUESTROOM315_318_LIGHTS GUESTROOM315_318 GUESTROOM315_318 GENERAL 4.4132 130.44 575.64 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 5.16
GUESTROOM319_LIGHTS GUESTROOM319 GUESTROOM319 GENERAL 4.4132 32.61 143.91 LightsWired ALWAYSOFF 0.00 0.00 0.00 0.0000 Y 0.00
GUESTROOM320_323_LIGHTS GUESTROOM320_323 GUESTROOM320_323 GENERAL 4.4132 130.44 575.64 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 5.16
GUESTROOM324_LIGHTS GUESTROOM324 GUESTROOM324 GENERAL 4.4132 32.61 143.91 LightsWired ALWAYSOFF 0.00 0.00 0.00 0.0000 Y 0.00
GUESTROOM401_LIGHTS GUESTROOM401 GUESTROOM401 GENERAL 4.4132 32.61 143.92 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 1.29
GUESTROOM402_405_LIGHTS GUESTROOM402_405 GUESTROOM402_405 GENERAL 4.4132 130.45 575.68 LightsWired ALWAYSOFF 0.00 0.00 0.00 0.0000 Y 0.00
GUESTROOM406_408_LIGHTS GUESTROOM406_408 GUESTROOM406_408 GENERAL 4.4132 105.36 464.97 LightsWired ALWAYSOFF 0.00 0.00 0.00 0.0000 Y 0.00
GUESTROOM409_412_LIGHTS GUESTROOM409_412 GUESTROOM409_412 GENERAL 4.4132 130.45 575.68 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 5.16
GUESTROOM413_LIGHTS GUESTROOM413 GUESTROOM413 GENERAL 4.4132 32.61 143.92 LightsWired ALWAYSOFF 0.00 0.00 0.00 0.0000 Y 0.00
GUESTROOM414_LIGHTS GUESTROOM414 GUESTROOM414 GENERAL 4.4132 32.61 143.91 LightsWired ALWAYSOFF 0.00 0.00 0.00 0.0000 Y 0.00
GUESTROOM415_418_LIGHTS GUESTROOM415_418 GUESTROOM415_418 GENERAL 4.4132 130.44 575.64 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 5.16
GUESTROOM419_LIGHTS GUESTROOM419 GUESTROOM419 GENERAL 4.4132 32.61 143.91 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 1.29
GUESTROOM420_423_LIGHTS GUESTROOM420_423 GUESTROOM420_423 GENERAL 4.4132 130.44 575.64 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 5.16
GUESTROOM424_LIGHTS GUESTROOM424 GUESTROOM424 GENERAL 4.4132 32.61 143.91 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.75 0.0000 Y 1.29
LAUNDRYROOMFLR1_LIGHTS LAUNDRYROOMFLR1 LAUNDRYROOMFLR1 GENERAL 5.7049 97.83 558.09 LightsWired LTG_SCH_LAUNDRY 63.00 63.00 39.13 0.0000 N 4.10
MECHANICALROOMFLR1_LIGHTS MECHANICALROOMFLR1 MECHANICALROOMFLR1 GENERAL 4.6285 32.61 150.94 LightsWired LTG_SCH_MECHANICAL 42.00 168.00 42.00 0.0000 Y 1.19
MEETINGROOMFLR1_LIGHTS MEETINGROOMFLR1 MEETINGROOMFLR1 GENERAL 10.4410 80.27 838.14 LightsWired LTG_SCH_MEETING 84.35 119.00 53.73 0.0000 Y 8.45
REARSTAIRSFLR1_LIGHTS REARSTAIRSFLR1 REARSTAIRSFLR1 GENERAL 5.2743 20.07 105.87 LightsWired LTG_SCH_STAIR 168.00 168.00 168.00 0.0000 Y 3.34
REARSTAIRSFLR2_LIGHTS REARSTAIRSFLR2 REARSTAIRSFLR2 GENERAL 5.2743 20.07 105.87 LightsWired LTG_SCH_STAIR 168.00 168.00 168.00 0.0000 Y 3.34
REARSTAIRSFLR3_LIGHTS REARSTAIRSFLR3 REARSTAIRSFLR3 GENERAL 5.2743 20.07 105.87 LightsWired LTG_SCH_STAIR 168.00 168.00 168.00 0.0000 Y 3.34
REARSTAIRSFLR4_LIGHTS REARSTAIRSFLR4 REARSTAIRSFLR4 GENERAL 5.2743 20.07 105.87 LightsWired LTG_SCH_STAIR 168.00 168.00 168.00 0.0000 Y 3.34
REARSTORAGEFLR1_LIGHTS REARSTORAGEFLR1 REARSTORAGEFLR1 GENERAL 4.0903 20.07 82.11 LightsWired LTG_SCH_STORAGE 18.38 168.00 18.37 0.0000 N 0.28
REARSTORAGEFLR2_LIGHTS REARSTORAGEFLR2 REARSTORAGEFLR2 GENERAL 4.0903 20.07 82.11 LightsWired LTG_SCH_STORAGE 18.38 168.00 18.37 0.0000 N 0.28
REARSTORAGEFLR3_LIGHTS REARSTORAGEFLR3 REARSTORAGEFLR3 GENERAL 4.0903 20.07 82.11 LightsWired LTG_SCH_STORAGE 18.38 168.00 18.37 0.0000 N 0.28
REARSTORAGEFLR4_LIGHTS REARSTORAGEFLR4 REARSTORAGEFLR4 GENERAL 4.0903 20.07 82.11 LightsWired LTG_SCH_STORAGE 18.38 168.00 18.37 0.0000 N 0.28
RESTROOMFLR1_LIGHTS RESTROOMFLR1 RESTROOMFLR1 GENERAL 6.7813 32.61 221.15 LightsWired LTG_SCH_RESTROOM 92.40 168.00 92.40 0.0000 Y 3.84
Interior Lighting Total       4.8947 4013.58 19645.23               199.44


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
FRONTLOUNGEFLR1_DAYLREFPT1 FRONTLOUNGEFLR1 FRONTLOUNGEFLR1_DAYLCTRL SplitFlux Continuous/Off 0.29 1474.30 427.55
FRONTLOUNGEFLR1_DAYLREFPT2 FRONTLOUNGEFLR1 FRONTLOUNGEFLR1_DAYLCTRL SplitFlux Continuous/Off 0.29 1474.30 427.55
MEETINGROOMFLR1_DAYLREFPT1 MEETINGROOMFLR1 MEETINGROOMFLR1_DAYLCTRL SplitFlux Continuous/Off 0.28 838.14 234.68
MEETINGROOMFLR1_DAYLREFPT2 MEETINGROOMFLR1 MEETINGROOMFLR1_DAYLCTRL SplitFlux Continuous/Off 0.28 838.14 234.68
FRONTOFFICEFLR1_DAYLREFPT1 FRONTOFFICEFLR1 FRONTOFFICEFLR1_DAYLCTRL SplitFlux Continuous/Off 0.26 993.33 258.27
FRONTOFFICEFLR1_DAYLREFPT2 FRONTOFFICEFLR1 FRONTOFFICEFLR1_DAYLCTRL SplitFlux Continuous/Off 0.26 993.33 258.27
LAUNDRYROOMFLR1_DAYLREFPT1 LAUNDRYROOMFLR1 LAUNDRYROOMFLR1_DAYLCTRL SplitFlux Continuous/Off 0.26 558.09 145.10
LAUNDRYROOMFLR1_DAYLREFPT2 LAUNDRYROOMFLR1 LAUNDRYROOMFLR1_DAYLCTRL SplitFlux Continuous/Off 0.26 558.09 145.10


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS 3177.58 AstronomicalClock -   83.63 83.63 49.88
Exterior Lighting Total 3177.58           49.88



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   41350.04 32990.56 8359.48 0.80 3.81    
101 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   1984.33 1588.76 395.56 0.80 3.81    
102 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   1609.72 1288.83 320.89 0.80 3.81    
103 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2904.49 2325.50 579.00 0.80 3.81    
104 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   3021.03 2418.80 602.23 0.80 3.81    
105 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   4350.62 3483.34 867.27 0.80 3.81    
CORRIDORFLR2 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   4334.91 3470.77 864.14 0.80 3.81    
201 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2234.62 1789.16 445.46 0.80 3.81    
202_205 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   11528.11 9230.04 2298.07 0.80 3.81    
206_208 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   9529.40 7629.77 1899.64 0.80 3.81    
209_212 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10640.37 8519.27 2121.10 0.80 3.81    
213 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2924.56 2341.56 582.99 0.80 3.81    
214 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   3278.41 2624.88 653.53 0.80 3.81    
215_218 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   32246.13 25818.03 6428.10 0.80 3.81    
219 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   17172.47 13749.23 3423.24 0.80 3.81    
220_223 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10924.99 8747.15 2177.84 0.80 3.81    
224 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   3122.25 2499.85 622.40 0.80 3.81    
CORRIDORFLR3 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   1932.59 1415.22 517.37 0.73 3.81    
301 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   1631.22 1306.04 325.17 0.80 3.81    
302_305 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   5262.13 4213.15 1048.98 0.80 3.81    
306_308 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   4786.20 3832.10 954.10 0.80 3.81    
309_312 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10142.20 8120.40 2021.79 0.80 3.81    
313 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   1800.62 1441.68 358.94 0.80 3.81    
314 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2833.75 2268.86 564.89 0.80 3.81    
315_318 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   12470.18 9984.32 2485.87 0.80 3.81    
319 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2944.66 2357.65 587.00 0.80 3.81    
320_323 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   9769.13 7821.71 1947.42 0.80 3.81    
324 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   1710.66 1369.65 341.01 0.80 3.81    
CORRIDORFLR4 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2867.53 2210.49 657.04 0.77 3.81    
401 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   3477.74 2784.47 693.27 0.80 3.81    
402_405 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7100.96 5685.42 1415.54 0.80 3.81    
406_408 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   6379.59 5107.85 1271.74 0.80 3.81    
409_412 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   12598.60 10087.13 2511.46 0.80 3.81    
413 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2526.52 2022.87 503.65 0.80 3.81    
414 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2204.48 1765.03 439.45 0.80 3.81    
415_418 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   12455.50 9972.56 2482.94 0.80 3.81    
419 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   3377.81 2704.46 673.35 0.80 3.81    
420_423 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   11533.78 9234.58 2299.20 0.80 3.81    
424 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   3300.57 2642.62 657.95 0.80 3.81    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:MultiSpeed   7988.38 6236.45 1751.93 0.78 4.12    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:MultiSpeed   23116.92 16925.05 6191.87 0.73 3.80    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:MultiSpeed   11416.48 8024.99 3391.49 0.70 4.12    
SAC_EMPLOYEELOUNGE COOLING COIL Coil:Cooling:DX:MultiSpeed   14670.50 11746.67 2923.83 0.80 4.12    
SAC_EXERCISECENTER COOLING COIL Coil:Cooling:DX:MultiSpeed   3848.78 2725.51 1123.27 0.71 4.12    
SAC_RESTROOM COOLING COIL Coil:Cooling:DX:MultiSpeed   1370.97 1097.68 273.29 0.80 4.12    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC PTAC COOLING COIL   39657.7 3.16 10.79 11.43 10.82 10.73
101 PTAC PTAC COOLING COIL   1891.3 3.08 10.52 11.14 10.54 10.33
102 PTAC PTAC COOLING COIL   1534.3 3.08 10.52 11.14 10.54 10.33
103 PTAC PTAC COOLING COIL   2768.3 3.08 10.52 11.14 10.54 10.33
104 PTAC PTAC COOLING COIL   2879.4 3.08 10.52 11.14 10.54 10.33
105 PTAC PTAC COOLING COIL   4146.7 3.08 10.52 11.14 10.54 10.33
CORRIDORFLR2 PTAC PTAC COOLING COIL   4131.7 3.08 10.52 11.14 10.54 10.33
201 PTAC PTAC COOLING COIL   2129.9 3.08 10.52 11.14 10.54 10.33
202_205 PTAC PTAC COOLING COIL   10987.7 3.08 10.52 11.14 10.54 10.33
206_208 PTAC PTAC COOLING COIL   9082.7 3.08 10.52 11.14 10.54 10.33
209_212 PTAC PTAC COOLING COIL   10141.6 3.08 10.52 11.14 10.54 10.33
213 PTAC PTAC COOLING COIL   2787.5 3.08 10.52 11.14 10.54 10.33
214 PTAC PTAC COOLING COIL   3124.7 3.08 10.52 11.14 10.54 10.33
215_218 PTAC PTAC COOLING COIL   30734.6 3.08 10.52 11.14 10.54 10.33
219 PTAC PTAC COOLING COIL   16367.5 3.08 10.52 11.14 10.54 10.33
220_223 PTAC PTAC COOLING COIL   10412.9 3.08 10.52 11.14 10.54 10.33
224 PTAC PTAC COOLING COIL   2975.9 3.08 10.52 11.14 10.54 10.33
CORRIDORFLR3 PTAC PTAC COOLING COIL   1865.9 3.25 11.10 11.77 11.13 11.20
301 PTAC PTAC COOLING COIL   1554.8 3.08 10.52 11.14 10.54 10.33
302_305 PTAC PTAC COOLING COIL   5015.5 3.08 10.52 11.14 10.54 10.33
306_308 PTAC PTAC COOLING COIL   4561.8 3.08 10.52 11.14 10.54 10.33
309_312 PTAC PTAC COOLING COIL   9666.8 3.08 10.52 11.14 10.54 10.33
313 PTAC PTAC COOLING COIL   1716.2 3.08 10.52 11.14 10.54 10.33
314 PTAC PTAC COOLING COIL   2700.9 3.08 10.52 11.14 10.54 10.33
315_318 PTAC PTAC COOLING COIL   11885.6 3.08 10.52 11.14 10.54 10.33
319 PTAC PTAC COOLING COIL   2806.6 3.08 10.52 11.14 10.54 10.33
320_323 PTAC PTAC COOLING COIL   9311.2 3.08 10.52 11.14 10.54 10.33
324 PTAC PTAC COOLING COIL   1630.5 3.08 10.52 11.14 10.54 10.33
CORRIDORFLR4 PTAC PTAC COOLING COIL   2757.8 3.20 10.92 11.57 10.95 10.92
401 PTAC PTAC COOLING COIL   3314.7 3.08 10.52 11.14 10.54 10.33
402_405 PTAC PTAC COOLING COIL   6768.1 3.08 10.52 11.14 10.54 10.33
406_408 PTAC PTAC COOLING COIL   6080.5 3.08 10.52 11.14 10.54 10.33
409_412 PTAC PTAC COOLING COIL   12008.0 3.08 10.52 11.14 10.54 10.33
413 PTAC PTAC COOLING COIL   2408.1 3.08 10.52 11.14 10.54 10.33
414 PTAC PTAC COOLING COIL   2101.1 3.08 10.52 11.14 10.54 10.33
415_418 PTAC PTAC COOLING COIL   11871.6 3.08 10.52 11.14 10.54 10.33
419 PTAC PTAC COOLING COIL   3219.5 3.08 10.52 11.14 10.54 10.33
420_423 PTAC PTAC COOLING COIL   10993.1 3.08 10.52 11.14 10.54 10.33
424 PTAC PTAC COOLING COIL   3145.9 3.08 10.52 11.14 10.54 10.33
SAC_FRONTOFFICE COOLING COIL   7674.8     12.61 12.32  
SAC_FRONTLOUNGE COOLING COIL   22319.7     12.06 11.79  
SAC_MEETINGROOM COOLING COIL   11057.9     13.11 12.81  
SAC_EMPLOYEELOUNGE COOLING COIL   14029.3     12.34 12.06  
SAC_EXERCISECENTER COOLING COIL   3725.8     13.07 12.78  
SAC_RESTROOM COOLING COIL   1306.7     12.15 11.88  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
CORRIDORFLR1 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
101 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
102 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
103 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
104 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
105 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
CORRIDORFLR2 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
201 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
202_205 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
206_208 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
209_212 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
213 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
214 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
215_218 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
219 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
220_223 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
224 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
CORRIDORFLR3 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
301 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
302_305 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
306_308 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
309_312 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
313 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
314 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
315_318 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
319 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
320_323 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
324 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
CORRIDORFLR4 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
401 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
402_405 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
406_408 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
409_412 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
413 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
414 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
415_418 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
419 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
420_423 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
424 PTAC PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed                
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:MultiSpeed                
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:MultiSpeed                
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:MultiSpeed                
SAC_EMPLOYEELOUNGE COOLING COIL Coil:Cooling:DX:MultiSpeed                
SAC_EXERCISECENTER COOLING COIL Coil:Cooling:DX:MultiSpeed                
SAC_RESTROOM COOLING COIL Coil:Cooling:DX:MultiSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1 UNITHEATER HEATING COIL Coil:Heating:Electric   306.67 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   76487.20 1.00
MECHRM UNITHEATER HEATING COIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   1279.86 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   1343.44 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   1868.29 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   1891.34 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   1342.11 1.00
FRONTSTAIRSFLR1 UNITHEATER HEATING COIL Coil:Heating:Electric   306.62 1.00
REARSTAIRSFLR2 UNITHEATER HEATING COIL Coil:Heating:Electric   306.67 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   4060.99 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   1771.23 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   4908.57 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   3860.93 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   4812.02 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   1741.29 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   1734.89 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   4811.67 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   1202.92 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   4811.67 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   1545.17 1.00
FRONTSTAIRSFLR2 UNITHEATER HEATING COIL Coil:Heating:Electric   306.62 1.00
REARSTAIRSFLR3 UNITHEATER HEATING COIL Coil:Heating:Electric   306.67 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   4366.46 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   1842.00 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   5032.36 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   4052.85 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   5009.43 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   1833.95 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   1804.07 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   4970.13 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   1308.61 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   4897.96 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   1608.14 1.00
FRONTSTAIRSFLR3 UNITHEATER HEATING COIL Coil:Heating:Electric   306.62 1.00
REARSTAIRSFLR4 UNITHEATER HEATING COIL Coil:Heating:Electric   306.69 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   5798.44 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   2408.72 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   6290.63 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   5076.57 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   6281.93 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   2291.33 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   2202.50 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   6227.35 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   1708.85 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   5819.44 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   1991.94 1.00
FRONTSTAIRSFLR4 UNITHEATER HEATING COIL Coil:Heating:Electric   605.48 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Fuel   12264.01 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Fuel   35327.96 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Fuel   16933.96 0.80
SAC_EMPLOYEELOUNGE HEATING COIL Coil:Heating:Fuel   20871.37 0.80
SAC_EXERCISECENTER HEATING COIL Coil:Heating:Fuel   7599.15 0.80
SAC_RESTROOM HEATING COIL Coil:Heating:Fuel   1805.54 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
REARSTAIRSFLR1 UNITHEATER FAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 149.55 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00
CORRIDORFLR1 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 2.18 1388.27 636.87 1.00 1.34 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00
MECHRM UNITHEATER FAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 0.00 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00
101 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.12 76.34 636.87 1.00 3.39 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00
102 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.10 61.93 636.87 1.00 3.86 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00
103 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.18 111.74 636.87 1.00 2.74 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00
104 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.18 116.23 636.87 1.00 2.69 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00
105 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.26 167.38 636.87 1.00 2.27 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00
FRONTSTAIRSFLR1 UNITHEATER FAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 149.58 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00
REARSTAIRSFLR2 UNITHEATER FAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 149.55 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00
CORRIDORFLR2 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.26 166.78 636.87 1.00 2.27 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00
201 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 85.97 636.87 1.00 3.16 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00
202_205 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.70 443.52 636.87 1.00 1.64 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00
206_208 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.58 366.63 636.87 1.00 1.72 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00
209_212 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.64 409.37 636.87 1.00 1.67 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00
213 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.18 112.52 636.87 1.00 2.73 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00
214 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.20 126.13 636.87 1.00 2.58 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00
215_218 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 1.95 1240.61 636.87 1.00 1.36 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00
219 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 1.04 660.68 636.87 1.00 1.50 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00
220_223 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.66 420.32 636.87 1.00 1.66 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00
224 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.19 120.12 636.87 1.00 2.64 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00
FRONTSTAIRSFLR2 UNITHEATER FAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 149.58 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00
REARSTAIRSFLR3 UNITHEATER FAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 149.55 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00
CORRIDORFLR3 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.09 54.66 636.87 1.00 4.20 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00
301 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.10 62.76 636.87 1.00 3.83 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00
302_305 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.32 202.45 636.87 1.00 2.10 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00
306_308 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.29 184.14 636.87 1.00 2.18 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00
309_312 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.61 390.20 636.87 1.00 1.69 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00
313 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.11 69.28 636.87 1.00 3.60 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00
314 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.17 109.02 636.87 1.00 2.78 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00
315_318 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.75 479.77 636.87 1.00 1.61 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00
319 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.18 113.29 636.87 1.00 2.72 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00
320_323 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.59 375.85 636.87 1.00 1.71 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00
324 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.10 65.81 636.87 1.00 3.72 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00
FRONTSTAIRSFLR3 UNITHEATER FAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 149.58 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00
REARSTAIRSFLR4 UNITHEATER FAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 149.55 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00
CORRIDORFLR4 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.14 89.98 636.87 1.00 3.08 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00
401 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.21 133.80 636.87 1.00 2.51 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00
402_405 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.43 273.20 636.87 1.00 1.88 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00
406_408 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 245.44 636.87 1.00 1.95 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00
409_412 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.76 484.71 636.87 1.00 1.60 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00
413 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.15 97.20 636.87 1.00 2.95 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00
414 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 84.81 636.87 1.00 3.19 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00
415_418 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.75 479.20 636.87 1.00 1.61 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00
419 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.20 129.95 636.87 1.00 2.54 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00
420_423 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.70 443.74 636.87 1.00 1.64 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00
424 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.20 126.98 636.87 1.00 2.57 General ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00
FRONTSTAIRSFLR4 UNITHEATER FAN Fan:ConstantVolume 0.54 49.80 0.01 1.12 92.91 1.00 77.30 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:20:00
SAC_FRONTOFFICE_ADDAQ SUPPLY FAN Fan:SystemModel 0.56 622.50 0.40 452.38 1120.11 1.00 1.73 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:20:00
SAC_FRONTLOUNGE_ADDAQ SUPPLY FAN Fan:SystemModel 0.56 622.50 1.03 1136.10 1107.16 1.00 1.40 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
SAC_MEETINGROOM_ADDAQ SUPPLY FAN Fan:SystemModel 0.56 622.50 0.46 516.74 1120.11 1.00 1.66 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
SAC_EMPLOYEELOUNGE_ADDAQ SUPPLY FAN Fan:SystemModel 0.56 622.50 0.83 914.61 1107.16 1.00 1.45 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 01:20:00
SAC_EXERCISECENTER_ADDAQ SUPPLY FAN Fan:SystemModel 0.56 622.50 0.16 177.20 1120.11 1.00 2.54 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
SAC_RESTROOM_ADDAQ SUPPLY FAN Fan:SystemModel 0.56 622.50 0.08 92.77 1120.11 1.00 3.72 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000180 8.11 45084.46 0.85 General
SWHSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.000129 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH SHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.49 0.06
SWH LAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.49



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
REARSTAIRSFLR1 0.00 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 0.00 26.62 0.01536 30.88 0.01536 0.006 0.00
CORRIDORFLR1 20944.12 25132.95 166.99 1.811 2.173 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 23.89 23.87 0.01038 28.66 0.01536 0.046 0.00
FRONTLOUNGEFLR1 9895.89 11875.07 72.83 0.855 1.026 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 23.89 23.88 0.00930 28.66 0.01536 0.237 0.00
RESTROOMFLR1 799.24 959.09 29.41 0.069 0.083 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 23.89 23.89 0.00856 27.33 0.01536 0.000 0.00
MEETINGROOMFLR1 4446.86 5336.24 66.48 0.384 0.461 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 23.89 23.88 0.01032 28.66 0.01536 0.126 0.00
MECHANICALROOMFLR1 0.0 0.0 0.0 0.0 0.0 N/A N/A 0.0 0.0 0.0 0.0 0.0 0.0 0.0
GUESTROOM101 831.95 998.34 30.61 0.100 0.120 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 21.11 21.11 0.00802 28.39 0.01536 0.013 0.00
GUESTROOM102 674.89 809.87 24.83 0.081 0.097 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 21.11 21.11 0.00803 28.39 0.01536 0.013 0.00
GUESTROOM103 1217.64 1461.17 44.81 0.146 0.175 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 21.11 21.11 0.00818 28.39 0.01536 0.013 0.00
GUESTROOM104 1266.50 1519.80 46.61 0.152 0.183 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 21.11 21.11 0.00818 28.23 0.01536 0.013 0.00
GUESTROOM105 1823.91 2188.69 67.12 0.219 0.263 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 21.11 21.11 0.00812 27.97 0.01536 0.013 0.00
EMPLOYEELOUNGEFLR1 7965.23 9558.28 293.12 0.688 0.826 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 23.89 23.88 0.00854 27.97 0.01536 0.052 0.00
EXERCISECENTERFLR1 1526.09 1831.31 56.16 0.132 0.158 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 23.89 23.88 0.00911 25.37 0.01535 0.076 0.00
FRONTOFFICEFLR1 3897.20 4676.64 35.85 0.337 0.404 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 23.89 23.89 0.00864 27.97 0.01536 0.063 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 0.00 27.74 0.01536 30.67 0.01536 0.006 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 0.00 27.53 0.01536 30.67 0.01536 0.006 0.00
CORRIDORFLR2 2527.45 3032.94 24.18 0.218 0.262 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 23.89 23.89 0.00808 28.66 0.01536 0.038 0.00
GUESTROOM201 936.87 1124.24 34.47 0.112 0.135 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 21.11 21.11 0.00807 28.83 0.01536 0.013 0.00
GUESTROOM202_205 4832.78 5799.33 44.46 0.580 0.696 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 21.11 21.11 0.00818 28.83 0.01536 0.054 0.00
GUESTROOM206_208 3994.92 4793.90 45.50 0.480 0.576 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 21.11 21.11 0.00817 28.83 0.01536 0.043 0.00
GUESTROOM209_212 4460.62 5352.74 41.03 0.536 0.643 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 21.11 21.11 0.00820 28.83 0.01536 0.054 0.00
GUESTROOM213 1226.04 1471.24 45.11 0.147 0.177 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 21.11 21.11 0.00818 28.83 0.01536 0.013 0.00
GUESTROOM214 1374.38 1649.26 50.58 0.165 0.198 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 21.11 21.11 0.00816 27.17 0.01536 0.013 0.00
GUESTROOM215_218 13519.52 16223.43 124.38 1.623 1.948 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 21.11 21.11 0.00801 26.87 0.01536 0.054 0.00
GUESTROOM219 7199.22 8639.07 264.93 0.864 1.037 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 21.11 21.11 0.00803 26.87 0.01536 0.013 0.00
GUESTROOM220_223 4579.94 5495.92 42.14 0.550 0.660 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 21.11 21.11 0.00819 27.17 0.01536 0.054 0.00
GUESTROOM224 1308.91 1570.70 48.17 0.157 0.189 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 21.11 21.11 0.00817 27.17 0.01536 0.013 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 0.00 28.30 0.01536 30.14 0.01536 0.006 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 0.00 27.58 0.01536 30.28 0.01536 0.006 0.00
CORRIDORFLR3 828.39 994.06 7.93 0.072 0.086 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 23.89 23.89 0.00825 28.39 0.01536 0.038 0.00
GUESTROOM301 683.89 820.67 25.17 0.082 0.099 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 21.11 21.11 0.00810 28.66 0.01536 0.013 0.00
GUESTROOM302_305 2206.20 2647.43 20.30 0.265 0.318 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 21.11 21.11 0.00804 28.66 0.01536 0.054 0.00
GUESTROOM306_308 2006.66 2407.99 22.85 0.241 0.289 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 21.11 21.11 0.00804 28.83 0.01536 0.043 0.00
GUESTROOM309_312 4251.77 5102.12 39.11 0.511 0.613 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 21.11 21.11 0.00821 28.66 0.01536 0.054 0.00
GUESTROOM313 754.93 905.91 27.78 0.091 0.109 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 21.11 21.11 0.00803 28.66 0.01536 0.013 0.00
GUESTROOM314 1187.97 1425.56 43.72 0.143 0.171 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 21.11 21.11 0.00819 27.44 0.01536 0.013 0.00
GUESTROOM315_318 5227.71 6273.25 48.09 0.628 0.753 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 21.11 21.11 0.00817 27.17 0.01536 0.054 0.00
GUESTROOM319 1234.58 1481.49 45.43 0.148 0.178 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 21.11 21.11 0.00802 27.17 0.01536 0.013 0.00
GUESTROOM320_323 4095.37 4914.44 37.68 0.492 0.590 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 21.11 21.11 0.00822 27.17 0.01536 0.054 0.00
GUESTROOM324 717.21 860.65 26.39 0.086 0.103 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 21.11 21.11 0.00803 27.44 0.01536 0.013 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 0.00 28.31 0.01536 29.36 0.01536 0.006 0.00
REARSTAIRSFLR4 0.00 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 0.00 29.63 0.01536 30.99 0.01536 0.006 0.00
CORRIDORFLR4 1363.64 1636.37 13.05 0.118 0.141 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 23.89 23.89 0.00817 31.20 0.01537 0.038 0.00
GUESTROOM401 1457.91 1749.50 53.65 0.175 0.210 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 21.11 21.11 0.00819 29.36 0.01536 0.013 0.00
GUESTROOM402_405 2977.14 3572.57 27.39 0.357 0.429 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 21.11 21.11 0.00803 29.36 0.01536 0.054 0.00
GUESTROOM406_408 2674.70 3209.64 30.46 0.321 0.385 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 21.11 21.11 0.00803 29.36 0.01536 0.043 0.00
GUESTROOM409_412 5281.54 6337.85 48.59 0.634 0.761 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 21.11 21.11 0.00817 29.36 0.01536 0.054 0.00
GUESTROOM413 1059.27 1271.12 38.98 0.127 0.153 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 21.11 21.11 0.00802 29.36 0.01536 0.013 0.00
GUESTROOM414 924.25 1109.10 34.01 0.111 0.133 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 21.11 21.11 0.00803 28.76 0.01536 0.013 0.00
GUESTROOM415_418 5221.55 6265.86 48.04 0.627 0.752 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 21.11 21.11 0.00817 27.70 0.01536 0.054 0.00
GUESTROOM419 1416.05 1699.26 52.11 0.170 0.204 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 21.11 21.11 0.00816 28.23 0.01536 0.013 0.00
GUESTROOM420_423 4835.14 5802.17 44.48 0.581 0.697 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 21.11 21.11 0.00819 27.70 0.01536 0.054 0.00
GUESTROOM424 1383.67 1660.40 50.92 0.166 0.199 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 21.11 21.11 0.00816 28.23 0.01536 0.013 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 0.00 30.10 0.01536 30.67 0.01536 0.006 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
REARSTAIRSFLR1 0.00 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 7.20 8.96 0.00036 -26.20 0.00036 0.006 0.00
CORRIDORFLR1 61582.83 73899.39 491.01 1.817 2.180 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.11 21.03 0.00513 -26.20 0.00036 0.046 0.00
FRONTLOUNGEFLR1 2919.50 3503.40 21.49 0.086 0.237 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:40:00 21.11 21.11 0.00779 -26.20 0.00036 0.237 0.00
RESTROOMFLR1 403.18 483.81 14.84 0.012 0.014 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 21.11 21.11 0.00778 -26.20 0.00036 0.000 0.00
MEETINGROOMFLR1 1040.97 1249.16 15.56 0.031 0.126 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:00:00 21.11 21.11 0.00779 -26.20 0.00036 0.126 0.00
MECHANICALROOMFLR1 0.0 0.0 0.0 0.0 0.0 N/A N/A 0.0 0.0 0.0 0.0 0.0 0.0 0.0
GUESTROOM101 444.12 532.94 16.34 0.013 0.016 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00780 -26.20 0.00036 0.013 0.00
GUESTROOM102 497.10 596.52 18.29 0.015 0.018 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 21.11 21.11 0.00782 -26.20 0.00036 0.013 0.00
GUESTROOM103 934.48 1121.38 34.39 0.028 0.033 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:10:00 21.11 21.11 0.00791 -26.20 0.00036 0.013 0.00
GUESTROOM104 953.73 1144.47 35.10 0.028 0.034 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:10:00 21.11 21.11 0.00791 -26.20 0.00036 0.013 0.00
GUESTROOM105 496.04 595.24 18.25 0.015 0.018 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 21.11 21.11 0.00782 -26.20 0.00036 0.013 0.00
EMPLOYEELOUNGEFLR1 456.88 548.25 16.81 0.014 0.052 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00781 -26.20 0.00036 0.052 0.00
EXERCISECENTERFLR1 344.87 413.84 12.69 0.010 0.076 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:00:00 21.11 21.11 0.00873 -26.20 0.00036 0.076 0.00
FRONTOFFICEFLR1 1943.42 2332.11 17.88 0.057 0.069 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:20:00 21.11 21.11 0.00782 -26.20 0.00036 0.063 0.00
FRONTSTAIRSFLR1 122.49 146.99 7.32 0.002 0.006 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 7.20 7.20 0.00338 -26.20 0.00036 0.006 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 7.20 8.70 0.00036 -26.20 0.00036 0.006 0.00
CORRIDORFLR2 1618.98 1942.78 15.49 0.048 0.057 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:20:00 21.11 21.11 0.00763 -26.20 0.00036 0.038 0.00
GUESTROOM201 853.61 1024.33 31.41 0.025 0.030 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 21.11 21.11 0.00768 -26.20 0.00036 0.013 0.00
GUESTROOM202_205 1600.76 1920.91 14.73 0.047 0.057 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 21.11 21.11 0.00778 -26.20 0.00036 0.054 0.00
GUESTROOM206_208 1244.24 1493.09 14.17 0.037 0.044 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 21.11 21.11 0.00777 -26.20 0.00036 0.043 0.00
GUESTROOM209_212 1479.18 1775.01 13.61 0.044 0.054 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 21.11 21.11 0.00776 -26.20 0.00036 0.054 0.00
GUESTROOM213 828.65 994.38 30.49 0.024 0.029 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 21.11 21.11 0.00789 -26.20 0.00036 0.013 0.00
GUESTROOM214 823.36 988.03 30.30 0.024 0.029 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 21.11 21.11 0.00789 -26.20 0.00036 0.013 0.00
GUESTROOM215_218 1462.26 1754.72 13.45 0.043 0.054 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00776 -26.20 0.00036 0.054 0.00
GUESTROOM219 373.37 448.04 13.74 0.011 0.013 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00776 -26.20 0.00036 0.013 0.00
GUESTROOM220_223 1452.72 1743.26 13.36 0.043 0.054 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.11 21.11 0.00775 -26.20 0.00036 0.054 0.00
GUESTROOM224 665.25 798.30 24.48 0.020 0.024 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 21.11 21.11 0.00786 -26.20 0.00036 0.013 0.00
FRONTSTAIRSFLR2 143.87 172.65 8.60 0.003 0.006 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 7.20 7.20 0.00363 -26.20 0.00036 0.006 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 7.20 8.13 0.00036 -26.20 0.00036 0.006 0.00
CORRIDORFLR3 1873.54 2248.25 17.93 0.055 0.066 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 21.11 21.11 0.00765 -26.20 0.00036 0.038 0.00
GUESTROOM301 912.58 1095.09 33.58 0.027 0.032 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 21.11 21.11 0.00767 -26.20 0.00036 0.013 0.00
GUESTROOM302_305 1703.92 2044.70 15.67 0.050 0.060 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 21.11 21.11 0.00777 -26.20 0.00036 0.054 0.00
GUESTROOM306_308 1404.17 1685.01 15.99 0.042 0.050 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:20:00 21.11 21.11 0.00777 -26.20 0.00036 0.043 0.00
GUESTROOM309_312 1684.81 2021.77 15.50 0.050 0.060 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 21.11 21.11 0.00777 -26.20 0.00036 0.054 0.00
GUESTROOM313 905.86 1087.03 33.33 0.027 0.032 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 21.11 21.11 0.00789 -26.20 0.00036 0.013 0.00
GUESTROOM314 881.01 1057.21 32.42 0.026 0.031 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 21.11 21.11 0.00789 -26.20 0.00036 0.013 0.00
GUESTROOM315_318 1652.23 1982.68 15.20 0.049 0.059 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 21.11 21.11 0.00776 -26.20 0.00036 0.054 0.00
GUESTROOM319 468.12 561.74 17.23 0.014 0.017 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 21.11 21.11 0.00779 -26.20 0.00036 0.013 0.00
GUESTROOM320_323 1592.10 1910.52 14.65 0.047 0.056 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:20:00 21.11 21.11 0.00775 -26.20 0.00036 0.054 0.00
GUESTROOM324 717.73 861.28 26.41 0.021 0.025 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 21.11 21.11 0.00786 -26.20 0.00036 0.013 0.00
FRONTSTAIRSFLR3 197.92 237.51 11.84 0.004 0.006 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 7.20 7.20 0.00404 -26.20 0.00036 0.006 0.00
REARSTAIRSFLR4 196.13 235.36 11.73 0.004 0.006 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 7.20 7.20 0.00389 -26.20 0.00036 0.006 0.00
CORRIDORFLR4 3066.87 3680.24 29.34 0.091 0.109 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 21.11 21.11 0.00777 -26.20 0.00036 0.038 0.00
GUESTROOM401 1384.86 1661.83 50.96 0.041 0.049 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:20:00 21.11 21.11 0.00777 -26.20 0.00036 0.013 0.00
GUESTROOM402_405 2752.48 3302.98 25.32 0.081 0.098 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 21.11 21.11 0.00784 -26.20 0.00036 0.054 0.00
GUESTROOM406_408 2257.28 2708.74 25.71 0.067 0.080 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 21.11 21.11 0.00785 -26.20 0.00036 0.043 0.00
GUESTROOM409_412 2745.23 3294.28 25.25 0.081 0.097 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 21.11 21.11 0.00784 -26.20 0.00036 0.054 0.00
GUESTROOM413 1287.01 1544.41 47.36 0.038 0.046 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 21.11 21.11 0.00792 -26.20 0.00036 0.013 0.00
GUESTROOM414 1213.03 1455.64 44.64 0.036 0.043 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 21.11 21.11 0.00791 -26.20 0.00036 0.013 0.00
GUESTROOM415_418 2699.93 3239.91 24.84 0.080 0.096 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 21.11 21.11 0.00784 -26.20 0.00036 0.054 0.00
GUESTROOM419 801.66 961.99 29.50 0.024 0.028 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 21.11 21.11 0.00787 -26.20 0.00036 0.013 0.00
GUESTROOM420_423 2360.00 2832.00 21.71 0.070 0.084 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 21.11 21.11 0.00782 -26.20 0.00036 0.054 0.00
GUESTROOM424 1037.57 1245.08 38.18 0.031 0.037 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 21.11 21.11 0.00790 -26.20 0.00036 0.013 0.00
FRONTSTAIRSFLR4 504.59 605.51 30.17 0.010 0.012 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:20:00 7.20 7.20 0.00562 -26.20 0.00036 0.006 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
SAC_FRONTOFFICE 0.40 0.40 0.07 0.07 0.4039 0.4039 0.4039 1.0000 1.0000
SAC_FRONTLOUNGE 1.03 1.03 0.24 0.24 1.0261 1.0261 1.0261 1.0000 1.0000
SAC_MEETINGROOM 0.46 0.46 0.13 0.13 0.4613 0.4613 0.4613 1.0000 1.0000
SAC_EMPLOYEELOUNGE 0.83 0.83 0.05 0.05 0.8261 0.8261 0.8261 1.0000 1.0000
SAC_EXERCISECENTER 0.16 0.16 0.08 0.08 0.1582 0.1582 0.1582 1.0000 1.0000
SAC_RESTROOM 0.08 0.08 0.01 0.01 0.0828 0.0828 0.0828 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
REARSTAIRSFLR1 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:UNITHEATER REARSTAIRSFLR1 UNIT HEATER 306.673 306.673 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 306.67 306.67 0.006118 7.20 7.20 0.00800000 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 0.0000 7.20 0.00800000 100.0000 0.00 0.00 -999.00 -999.00
CORRIDORFLR1 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR1 PTAC 41350.036 32990.561 2.179854 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown 7/21 18:00:00 41474.94 28716.07 2.179854 23.97 17.53 0.01048843 13.46 11.45 0.00800000 28.66 0.01536037 22.44 2.1045 23.87 0.01038336 53.5732 25132.95 0.00 41370.28 32181.28
CORRIDORFLR1 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR1 PTAC 76487.200 76487.200 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 76487.20 76487.20 2.179854 20.04 11.18 0.00503436 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 2.1045 21.03 0.00513481 31.7387 73899.39 0.00 -999.00 -999.00
MECHRM UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:UNITHEATER MECHANICALROOMFLR1 UNIT HEATER 0.000 0.000 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 0.00 0.00 -999.0 7.20 7.20 0.00800000 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 -999.0000 7.20 0.00800000 100.0000 0.00 0.00 -999.00 -999.00
101 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 101 PTAC 1984.326 1588.761 0.119873 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 unknown 7/21 18:10:00 1866.14 1585.23 0.119873 21.93 15.47 0.00884883 13.46 11.45 0.00800000 28.39 0.01535988 22.36 11.2450 21.11 0.00802389 49.1383 998.34 0.00 1985.30 1549.03
101 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 101 PTAC 1279.858 1279.858 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1279.86 1279.86 0.015751 -19.38 -19.38 0.00143455 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 85.5793 21.11 0.00780343 47.8055 532.94 0.00 -999.00 -999.00
102 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 102 PTAC 1609.717 1288.829 0.097243 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 unknown 7/21 18:10:00 1525.48 1255.66 0.097243 22.12 15.71 0.00904560 13.46 11.45 0.00800000 28.39 0.01535988 22.36 13.8619 21.11 0.00802946 49.1720 809.87 0.00 1610.51 1256.60
102 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 102 PTAC 1343.437 1343.437 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 1343.44 1343.44 0.017630 -15.06 -15.06 0.00211817 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 76.4580 21.11 0.00782389 47.9293 596.52 0.00 -999.00 -999.00
103 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 103 PTAC 2904.493 2325.498 0.175460 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 unknown 7/21 18:10:00 2714.61 2346.95 0.175460 21.67 15.28 0.00873420 13.46 11.45 0.00800000 28.39 0.01535988 22.36 7.6825 21.11 0.00818283 50.1007 1461.17 0.00 2905.92 2267.34
103 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 103 PTAC 1868.293 1868.293 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:10:00 1868.29 1868.29 0.033143 1.87 1.87 0.00483701 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 40.6721 21.11 0.00790530 48.4217 1121.38 0.00 -999.00 -999.00
104 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 104 PTAC 3021.027 2418.801 0.182500 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 unknown 7/21 10:40:00 2825.47 2454.46 0.182500 21.64 15.25 0.00870644 13.46 11.45 0.00800000 28.23 0.01535959 22.32 7.3856 21.11 0.00817587 50.0587 1519.80 0.00 3022.51 2358.31
104 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 104 PTAC 1891.338 1891.338 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:10:00 1891.34 1891.34 0.033825 2.26 2.26 0.00490029 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 39.8485 21.11 0.00790719 48.4332 1144.47 0.00 -999.00 -999.00
105 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 105 PTAC 4350.616 3483.343 0.262821 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 unknown 7/21 10:30:00 4049.10 3657.22 0.262821 21.46 15.00 0.00849335 13.46 11.45 0.00800000 27.97 0.01535910 22.25 5.1285 21.11 0.00812221 49.7342 2188.69 0.00 4352.75 3396.24
105 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 105 PTAC 1342.105 1342.105 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 1342.11 1342.11 0.017593 -15.14 -15.14 0.00210624 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 76.6168 21.11 0.00782351 47.9270 595.24 0.00 -999.00 -999.00
FRONTSTAIRSFLR1 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:UNITHEATER FRONTSTAIRSFLR1 UNIT HEATER 306.618 306.618 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 306.62 306.62 0.006116 7.20 3.22 0.00338043 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 0.0000 7.20 0.00338043 51.4331 146.99 0.00 -999.00 -999.00
REARSTAIRSFLR2 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:UNITHEATER REARSTAIRSFLR2 UNIT HEATER 306.673 306.673 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 306.67 306.67 0.006118 7.20 7.20 0.00800000 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 0.0000 7.20 0.00800000 100.0000 0.00 0.00 -999.00 -999.00
CORRIDORFLR2 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR2 PTAC 4334.911 3470.769 0.261872 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown 7/21 18:00:00 4222.50 3533.81 0.261872 24.58 16.64 0.00913893 13.46 11.45 0.00800000 28.66 0.01536037 22.44 14.5980 23.89 0.00807548 41.7694 3032.94 0.00 4337.03 3383.98
CORRIDORFLR2 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR2 PTAC 4060.991 4060.991 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:20:00 4060.99 4060.99 0.057419 -10.39 -10.39 0.00279182 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 66.5776 21.11 0.00763335 46.7769 1942.78 0.00 -999.00 -999.00
201 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 201 PTAC 2234.617 1789.158 0.134993 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown 7/21 17:50:00 2086.46 1788.48 0.134993 21.88 15.41 0.00879493 13.46 11.45 0.00800000 28.83 0.01536070 22.49 9.9855 21.11 0.00806658 49.3968 1124.24 0.00 2235.71 1744.42
201 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 201 PTAC 1771.229 1771.229 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 1771.23 1771.23 0.030274 0.04 0.04 0.00442230 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 44.5265 21.11 0.00768188 47.0709 1024.33 0.00 -999.00 -999.00
202_205 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 202_205 PTAC 11528.113 9230.044 0.696413 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown 7/21 17:50:00 10725.57 9266.84 0.696413 21.71 15.30 0.00874018 13.46 11.45 0.00800000 28.83 0.01536070 22.49 7.7424 21.11 0.00818458 50.1119 5799.33 0.00 11533.76 8999.23
202_205 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 202_205 PTAC 4908.574 4908.574 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 4908.57 4908.57 0.056773 -23.82 -23.82 0.00073408 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 94.9733 21.11 0.00777663 47.6432 1920.91 0.00 -999.00 -999.00
206_208 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 206_208 PTAC 9529.403 7629.766 0.575671 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown 7/21 17:50:00 8854.09 7701.02 0.575671 21.68 15.26 0.00870258 13.46 11.45 0.00800000 28.83 0.01536070 22.49 7.4232 21.11 0.00816870 50.0157 4793.90 0.00 9534.07 7438.97
206_208 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 206_208 PTAC 3860.930 3860.930 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 3860.93 3860.93 0.044128 -24.70 -24.70 0.00059554 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 96.8380 21.11 0.00776812 47.5921 1493.09 0.00 -999.00 -999.00
209_212 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 209_212 PTAC 10640.371 8519.269 0.642785 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown 7/21 17:50:00 9922.23 8483.75 0.642785 21.76 15.37 0.00880064 13.46 11.45 0.00800000 28.83 0.01536070 22.49 8.3884 21.11 0.00819997 50.2049 5352.74 0.00 10645.58 8306.23
209_212 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 209_212 PTAC 4812.016 4812.016 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 4812.02 4812.02 0.053919 -26.20 -26.20 0.00036134 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 100.0000 21.11 0.00775882 47.5359 1775.01 0.00 -999.00 -999.00
213 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 213 PTAC 2924.556 2341.562 0.176672 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown 7/21 17:50:00 2719.88 2354.30 0.176672 21.70 15.29 0.00872963 13.46 11.45 0.00800000 28.83 0.01536070 22.49 7.6298 21.11 0.00818190 50.0954 1471.24 0.00 2925.99 2283.01
213 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 213 PTAC 1741.291 1741.291 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 1741.29 1741.29 0.029389 -0.59 -0.59 0.00443710 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 45.8667 21.11 0.00789047 48.3319 994.38 0.00 -999.00 -999.00
214 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 214 PTAC 3278.414 2624.880 0.198049 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown 7/21 10:00:00 3095.39 2713.10 0.198049 21.52 15.16 0.00865216 13.46 11.45 0.00800000 27.17 0.01535764 22.03 6.8058 21.11 0.00816247 49.9779 1649.26 0.00 3280.02 2559.24
214 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 214 PTAC 1734.894 1734.894 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 1734.89 1734.89 0.029202 -0.73 -0.73 0.00441481 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 46.1579 21.11 0.00788978 48.3277 988.03 0.00 -999.00 -999.00
215_218 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 215_218 PTAC 32246.130 25818.033 1.947989 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 unknown 7/21 09:50:00 30090.61 28759.58 1.947989 21.27 14.68 0.00820956 13.46 11.45 0.00800000 26.87 0.01535708 21.94 2.7677 21.11 0.00800610 49.0308 16223.43 0.00 32261.91 25172.40
215_218 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 215_218 PTAC 4811.675 4811.675 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4811.67 4811.67 0.053915 -26.20 -26.20 0.00036134 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 100.0000 21.11 0.00775613 47.5196 1754.72 0.00 -999.00 -999.00
219 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 219 PTAC 17172.473 13749.231 1.037389 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 unknown 7/21 09:50:00 15971.55 15535.04 1.037389 21.19 14.57 0.00812627 13.46 11.45 0.00800000 26.87 0.01535708 21.94 1.2993 21.11 0.00803109 49.1834 8639.07 0.00 17180.88 13405.40
219 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 219 PTAC 1202.919 1202.919 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1202.92 1202.92 0.013479 -26.20 -26.20 0.00036134 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 100.0000 21.11 0.00776104 47.5492 448.04 0.00 -999.00 -999.00
220_223 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 220_223 PTAC 10924.991 8747.152 0.659979 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown 7/21 10:00:00 10361.45 8875.94 0.659979 21.61 15.30 0.00878012 13.46 11.45 0.00800000 27.17 0.01535764 22.03 8.1692 21.11 0.00819499 50.1748 5495.92 0.00 10930.34 8528.41
220_223 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 220_223 PTAC 4811.675 4811.675 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4811.67 4811.67 0.053915 -26.20 -26.20 0.00036134 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 100.0000 21.11 0.00775396 47.5065 1743.26 0.00 -999.00 -999.00
224 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 224 PTAC 3122.250 2499.846 0.188615 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown 7/21 10:00:00 2951.26 2571.76 0.188615 21.54 15.19 0.00868419 13.46 11.45 0.00800000 27.17 0.01535764 22.03 7.1462 21.11 0.00817059 50.0270 1570.70 0.00 3123.78 2437.33
224 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 224 PTAC 1545.165 1545.165 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 1545.17 1545.17 0.023594 -5.92 -5.92 0.00357788 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 57.1282 21.11 0.00786403 48.1723 798.30 0.00 -999.00 -999.00
FRONTSTAIRSFLR2 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:UNITHEATER FRONTSTAIRSFLR2 UNIT HEATER 306.616 306.616 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 306.62 306.62 0.006116 7.20 3.55 0.00362905 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 0.0000 7.20 0.00362905 55.1925 172.65 0.00 -999.00 -999.00
REARSTAIRSFLR3 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:UNITHEATER REARSTAIRSFLR3 UNIT HEATER 306.673 306.673 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 306.67 306.67 0.006118 7.20 7.20 0.00800000 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 0.0000 7.20 0.00800000 100.0000 0.00 0.00 -999.00 -999.00
CORRIDORFLR3 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR3 PTAC 1932.589 1415.220 0.085830 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 unknown 7/21 18:10:00 2032.35 1322.14 0.085830 25.89 18.87 0.01141761 13.46 11.45 0.00800000 28.39 0.01535988 22.36 44.5390 23.89 0.00825170 42.6691 994.06 0.00 1933.53 1384.64
CORRIDORFLR3 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR3 PTAC 4366.458 4366.458 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 4366.46 4366.46 0.066447 -6.11 -6.11 0.00345626 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 57.5317 21.11 0.00764892 46.8708 2248.25 0.00 -999.00 -999.00
301 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 301 PTAC 1631.219 1306.044 0.098542 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown 7/21 18:00:00 1543.61 1260.78 0.098542 22.14 15.76 0.00909362 13.46 11.45 0.00800000 28.66 0.01536037 22.44 13.6792 21.11 0.00810053 49.6021 820.67 0.00 1632.02 1273.38
301 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 301 PTAC 1841.998 1841.998 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 1842.00 1842.00 0.032365 1.41 1.41 0.00462680 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 41.6491 21.11 0.00767136 47.0074 1095.09 0.00 -999.00 -999.00
302_305 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 302_305 PTAC 5262.130 4213.152 0.317885 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown 7/21 18:00:00 5019.80 3990.77 0.317885 22.39 16.01 0.00928243 13.46 11.45 0.00800000 28.66 0.01536037 22.44 16.9618 21.11 0.00804092 49.2413 2647.43 0.00 5264.71 4107.79
302_305 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 302_305 PTAC 5032.362 5032.362 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 5032.36 5032.36 0.060431 -21.10 -21.10 0.00115954 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 89.2235 21.11 0.00776817 47.5921 2044.70 0.00 -999.00 -999.00
306_308 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 306_308 PTAC 4786.204 3832.099 0.289135 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown 7/21 17:50:00 4528.78 3689.50 0.289135 22.25 15.82 0.00911884 13.46 11.45 0.00800000 28.83 0.01536070 22.49 14.7797 21.11 0.00803633 49.2136 2407.99 0.00 4788.55 3736.27
306_308 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 306_308 PTAC 4052.847 4052.847 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:20:00 4052.85 4052.85 0.049801 -19.49 -19.49 0.00141312 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 85.8084 21.11 0.00777264 47.6191 1685.01 0.00 -999.00 -999.00
309_312 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 309_312 PTAC 10142.199 8120.405 0.612690 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown 7/21 18:00:00 9489.68 8056.87 0.612690 21.77 15.41 0.00884089 13.46 11.45 0.00800000 28.66 0.01536037 22.44 8.8004 21.11 0.00821178 50.2763 5102.12 0.00 10147.16 7917.34
309_312 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 309_312 PTAC 5009.432 5009.432 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 5009.43 5009.43 0.059754 -21.58 -21.58 0.00108433 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 90.2355 21.11 0.00776562 47.5767 2021.77 0.00 -999.00 -999.00
313 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 313 PTAC 1800.623 1441.679 0.108776 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown 7/21 18:00:00 1694.68 1419.32 0.108776 22.05 15.59 0.00893829 13.46 11.45 0.00800000 28.66 0.01536037 22.44 12.3923 21.11 0.00802987 49.1745 905.91 0.00 1801.50 1405.63
313 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 313 PTAC 1833.949 1833.949 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 1833.95 1833.95 0.032128 1.26 1.26 0.00473073 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 41.9571 21.11 0.00788920 48.3242 1087.03 0.00 -999.00 -999.00
314 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 314 PTAC 2833.748 2268.855 0.171187 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown 7/21 10:10:00 2677.55 2304.77 0.171187 21.61 15.28 0.00875412 13.46 11.45 0.00800000 27.44 0.01535813 22.10 7.8738 21.11 0.00818970 50.1426 1425.56 0.00 2835.13 2212.12
314 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 314 PTAC 1804.072 1804.072 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 1804.07 1804.07 0.031246 0.70 0.70 0.00464011 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 43.1377 21.11 0.00788612 48.3056 1057.21 0.00 -999.00 -999.00
315_318 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 315_318 PTAC 12470.185 9984.319 0.753324 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown 7/21 10:00:00 11788.14 10267.55 0.753324 21.54 15.20 0.00868670 13.46 11.45 0.00800000 27.17 0.01535764 22.03 7.1570 21.11 0.00817246 50.0386 6273.25 0.00 12476.29 9734.64
315_318 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 315_318 PTAC 4970.131 4970.131 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 4970.13 4970.13 0.058598 -22.42 -22.42 0.00095273 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 92.0080 21.11 0.00776113 47.5495 1982.68 0.00 -999.00 -999.00
319 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 319 PTAC 2944.656 2357.654 0.177887 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown 7/21 10:00:00 2775.78 2470.37 0.177887 21.57 15.11 0.00857454 13.46 11.45 0.00800000 27.17 0.01535764 22.03 7.5772 21.11 0.00801843 49.1053 1481.49 0.00 2946.10 2298.70
319 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 319 PTAC 1308.606 1308.606 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 1308.61 1308.61 0.016602 -17.30 -17.30 0.00175869 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 81.1858 21.11 0.00778845 47.7148 561.74 0.00 -999.00 -999.00
320_323 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 320_323 PTAC 9769.131 7821.706 0.590153 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown 7/21 10:00:00 9294.96 7836.15 0.590153 21.66 15.40 0.00887210 13.46 11.45 0.00800000 27.17 0.01535764 22.03 9.1358 21.11 0.00822002 50.3261 4914.44 0.00 9773.91 7626.11
320_323 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 320_323 PTAC 4897.963 4897.963 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:20:00 4897.96 4897.96 0.056466 -24.06 -24.06 0.00069516 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 95.4835 21.11 0.00775239 47.4966 1910.52 0.00 -999.00 -999.00
324 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 324 PTAC 1710.661 1369.650 0.103341 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown 7/21 10:10:00 1632.90 1353.99 0.103341 21.94 15.60 0.00898728 13.46 11.45 0.00800000 27.44 0.01535813 22.10 13.0430 21.11 0.00803169 49.1855 860.65 0.00 1711.50 1335.40
324 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 324 PTAC 1608.140 1608.140 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 1608.14 1608.14 0.025455 -3.94 -3.94 0.00388971 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 52.9511 21.11 0.00786069 48.1518 861.28 0.00 -999.00 -999.00
FRONTSTAIRSFLR3 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:UNITHEATER FRONTSTAIRSFLR3 UNIT HEATER 306.619 306.619 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 306.62 306.62 0.006116 7.20 4.08 0.00404205 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 0.0000 7.20 0.00404205 61.4350 237.51 0.00 -999.00 -999.00
REARSTAIRSFLR4 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:UNITHEATER REARSTAIRSFLR4 UNIT HEATER 306.691 306.691 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 306.69 306.69 0.006118 7.20 3.89 0.00389357 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 0.0000 7.20 0.00389357 59.1918 235.36 0.00 -999.00 -999.00
CORRIDORFLR4 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR4 PTAC 2867.528 2210.491 0.141289 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 unknown 7/21 15:00:00 2827.88 2121.78 0.141289 25.87 17.86 0.01011372 13.46 11.45 0.00800000 31.20 0.01536508 23.13 27.0566 23.89 0.00816585 42.2309 1636.37 0.00 2868.93 2158.56
CORRIDORFLR4 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR4 PTAC 5798.440 5798.440 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 5798.44 5798.44 0.108769 4.48 4.10 0.00516390 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 35.1460 21.11 0.00776653 47.5826 3680.24 0.00 -999.00 -999.00
401 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 401 PTAC 3477.743 2784.473 0.210090 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 unknown 7/21 17:20:00 3204.72 2813.90 0.210090 21.64 15.20 0.00864930 13.46 11.45 0.00800000 29.36 0.01536168 22.63 6.4162 21.11 0.00818909 50.1393 1749.50 0.00 3479.45 2714.84
401 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 401 PTAC 2408.722 2408.722 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:20:00 2408.72 2408.72 0.049115 8.13 6.62 0.00573304 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 27.4455 21.11 0.00776501 47.5740 1661.83 0.00 -999.00 -999.00
402_405 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 402_405 PTAC 7100.960 5685.421 0.428969 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 unknown 7/21 17:20:00 6639.22 5553.36 0.428969 22.15 15.64 0.00895363 13.46 11.45 0.00800000 29.36 0.01536168 22.63 12.5695 21.11 0.00803238 49.1897 3572.57 0.00 7104.44 5543.25
402_405 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 402_405 PTAC 6290.628 6290.628 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 6290.63 6290.63 0.097620 -5.02 -5.02 0.00371134 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 55.2338 21.11 0.00784466 48.0549 3302.98 0.00 -999.00 -999.00
406_408 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 406_408 PTAC 6379.592 5107.854 0.385391 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 unknown 7/21 17:20:00 5937.65 5055.84 0.385391 22.03 15.50 0.00884216 13.46 11.45 0.00800000 29.36 0.01536168 22.63 11.0882 21.11 0.00802911 49.1699 3209.64 0.00 6382.72 4980.12
406_408 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 406_408 PTAC 5076.573 5076.573 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 5076.57 5076.57 0.080057 -4.14 -4.14 0.00385127 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 53.3783 21.11 0.00784696 48.0688 2708.74 0.00 -999.00 -999.00
409_412 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 409_412 PTAC 12598.597 10087.133 0.761081 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 unknown 7/21 17:20:00 11627.54 10154.97 0.761081 21.69 15.25 0.00868109 13.46 11.45 0.00800000 29.36 0.01536168 22.63 7.0845 21.11 0.00817172 50.0341 6337.85 0.00 12604.76 9834.88
409_412 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 409_412 PTAC 6281.930 6281.930 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 6281.93 6281.93 0.097363 -5.09 -5.09 0.00370025 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 55.3796 21.11 0.00784426 48.0525 3294.28 0.00 -999.00 -999.00
413 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 413 PTAC 2526.516 2022.869 0.152627 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 unknown 7/21 17:20:00 2335.06 2046.30 0.152627 21.84 15.29 0.00867092 13.46 11.45 0.00800000 29.36 0.01536168 22.63 8.8319 21.11 0.00802276 49.1315 1271.12 0.00 2527.75 1972.28
413 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 413 PTAC 2291.327 2291.327 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 2291.33 2291.33 0.045645 7.14 6.09 0.00568510 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 29.5315 21.11 0.00791615 48.4873 1544.41 0.00 -999.00 -999.00
414 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 414 PTAC 2204.484 1765.031 0.133173 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 unknown 7/21 11:00:00 2058.58 1773.05 0.133173 21.89 15.39 0.00876856 13.46 11.45 0.00800000 28.76 0.01536057 22.47 10.1213 21.11 0.00802623 49.1525 1109.10 0.00 2205.56 1720.89
414 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 414 PTAC 2202.497 2202.497 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 2202.50 2202.50 0.043022 6.29 5.50 0.00554573 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 31.3303 21.11 0.00791110 48.4567 1455.64 0.00 -999.00 -999.00
415_418 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 415_418 PTAC 12455.497 9972.559 0.752437 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 unknown 7/21 10:20:00 11708.05 10198.68 0.752437 21.58 15.21 0.00868851 13.46 11.45 0.00800000 27.70 0.01535861 22.17 7.1654 21.11 0.00817368 50.0460 6265.86 0.00 12461.59 9723.17
415_418 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 415_418 PTAC 6227.355 6227.355 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 6227.35 6227.35 0.095756 -5.53 -5.53 0.00362990 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 56.3048 21.11 0.00784170 48.0370 3239.91 0.00 -999.00 -999.00
419 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 419 PTAC 3377.810 2704.461 0.204053 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 unknown 7/21 10:40:00 3150.87 2771.97 0.204053 21.58 15.16 0.00863581 13.46 11.45 0.00800000 28.23 0.01535959 22.32 6.6055 21.11 0.00816025 49.9646 1699.26 0.00 3379.46 2636.83
419 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 419 PTAC 1708.853 1708.853 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 1708.85 1708.85 0.028432 -1.32 -1.32 0.00430838 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 47.4075 21.11 0.00786628 48.1856 961.99 0.00 -999.00 -999.00
420_423 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 420_423 PTAC 11533.777 9234.579 0.696755 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 unknown 7/21 10:20:00 10862.66 9371.75 0.696755 21.62 15.27 0.00874248 13.46 11.45 0.00800000 27.70 0.01535861 22.17 7.7380 21.11 0.00818758 50.1300 5802.17 0.00 11539.42 9003.65
420_423 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 420_423 PTAC 5819.439 5819.439 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 5819.44 5819.44 0.083700 -9.36 -9.36 0.00301531 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 64.4149 21.11 0.00781944 47.9023 2832.00 0.00 -999.00 -999.00
424 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 424 PTAC 3300.574 2642.622 0.199388 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 unknown 7/21 10:40:00 3080.48 2702.91 0.199388 21.59 15.18 0.00865038 13.46 11.45 0.00800000 28.23 0.01535959 22.32 6.7601 21.11 0.00816394 49.9869 1660.40 0.00 3302.19 2576.54
424 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 424 PTAC 1991.940 1991.940 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 1991.94 1991.94 0.036799 3.78 3.70 0.00513632 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 36.6287 21.11 0.00789627 48.3670 1245.08 0.00 -999.00 -999.00
FRONTSTAIRSFLR4 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:UNITHEATER FRONTSTAIRSFLR4 UNIT HEATER 605.478 605.478 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:20:00 605.48 605.48 0.012078 7.20 6.04 0.00562279 50.00 23.40 0.00800000 -26.20 0.00036134 -26.20 0.0000 7.20 0.00562279 85.2495 605.51 0.00 -999.00 -999.00
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC SAC_FRONTOFFICE 7988.380 6236.448 0.403870 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 3994.19 3136.83 0.269247 25.48 17.40 0.00969422 12.00 10.84 0.00800000 27.97 0.01535910 22.25 23.5302 23.89 0.00864142 44.6615 3884.91 0.00 -999.00 -999.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Fuel AirLoopHVAC SAC_FRONTOFFICE 12264.012 12264.012 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:20:00 12264.01 12264.01 0.403869 13.69 10.17 0.00664961 40.00 20.63 0.00800000 -26.20 0.00036134 -26.20 15.6868 21.11 0.00781956 47.9032 1943.42 0.00 -999.00 -999.00
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC SAC_FRONTLOUNGE 23116.920 16925.053 1.026140 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 11558.46 8121.50 0.684093 25.93 18.33 0.01069781 12.00 10.84 0.00800000 28.66 0.01536037 22.44 34.6881 23.88 0.00930632 48.0648 9796.63 0.00 -999.00 -999.00
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Fuel AirLoopHVAC SAC_FRONTLOUNGE 35327.961 35327.961 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 35327.96 35327.96 1.026138 10.17 7.97 0.00607116 40.00 20.63 0.00800000 -26.20 0.00036134 -26.20 23.1254 21.11 0.00778861 47.7163 2918.31 0.00 -999.00 -999.00
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC SAC_MEETINGROOM 11416.480 8024.986 0.461330 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 5708.24 3630.76 0.307553 26.13 19.15 0.01169403 12.00 10.84 0.00800000 28.66 0.01536037 22.44 40.9478 23.88 0.01034807 53.3726 4384.26 0.00 -999.00 -999.00
SAC_MEETINGROOM HEATING COIL Coil:Heating:Fuel AirLoopHVAC SAC_MEETINGROOM 16933.963 16933.963 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 16933.96 16933.96 0.461335 8.20 6.69 0.00576461 40.00 20.63 0.00800000 -26.20 0.00036134 -26.20 27.2982 21.11 0.00779040 47.7268 1036.21 0.00 -999.00 -999.00
SAC_EMPLOYEELOUNGE COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC SAC_EMPLOYEELOUNGE 14670.500 11746.669 0.826090 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:40:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 7335.25 6315.55 0.550727 25.08 16.68 0.00897539 12.00 10.84 0.00800000 27.97 0.01535910 22.25 9.5173 23.88 0.00854543 44.1928 7937.61 0.00 -999.00 -999.00
SAC_EMPLOYEELOUNGE HEATING COIL Coil:Heating:Fuel AirLoopHVAC SAC_EMPLOYEELOUNGE 20871.366 20871.366 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 01:20:00 20871.37 20871.37 0.826090 18.11 12.67 0.00733624 40.00 20.63 0.00800000 -26.20 0.00036134 -26.20 6.3449 21.11 0.00780791 47.8326 456.56 0.00 -999.00 -999.00
SAC_EXERCISECENTER COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC SAC_EXERCISECENTER 3848.780 2725.514 0.158200 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 1924.39 1159.05 0.105467 25.55 19.28 0.01211060 12.00 10.84 0.00800000 25.37 0.01535432 21.52 72.0719 23.88 0.00916977 47.3608 1453.58 0.00 -999.00 -999.00
SAC_EXERCISECENTER HEATING COIL Coil:Heating:Fuel AirLoopHVAC SAC_EXERCISECENTER 7599.149 7599.149 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 7599.15 7599.15 0.158196 -1.62 -1.62 0.00470786 40.00 20.63 0.00800000 -26.20 0.00036134 -26.20 48.0492 21.12 0.01444509 87.5371 268.70 0.00 -999.00 -999.00
SAC_RESTROOM COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC SAC_RESTROOM 1370.970 1097.681 0.082820 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 685.49 626.66 0.055213 24.84 16.25 0.00855821 12.00 10.84 0.00800000 27.33 0.01535793 22.07 0.0000 23.89 0.00855821 44.2354 799.24 0.00 -999.00 -999.00
SAC_RESTROOM HEATING COIL Coil:Heating:Fuel AirLoopHVAC SAC_RESTROOM 1805.543 1805.543 -999.0 -999.0 -999.000 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 1805.54 1805.54 0.082820 21.11 14.24 0.00778387 40.00 20.63 0.00800000 -26.20 0.00036134 -26.20 0.0000 21.11 0.00778387 47.6872 403.18 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
REARSTAIRSFLR1 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:UNITHEATER REARSTAIRSFLR1 UNIT HEATER REARSTAIRSFLR1 N/A N/A N/A Yes No unknown No 306.673 306.673 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 REARSTAIRSFLR1 UNITHEATER FAN Fan:ConstantVolume 0.006118 0.00702675   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 306.67 306.67 1.0000 0.00702675 0.006118 7.20 7.20 0.00800000 27349.4 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 306.67 -26.20 0.00036134 -26.20 0.00000000 0.0000 7.20 0.00800000 7.20 0.00800000 100.0000 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
CORRIDORFLR1 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR1 PTAC CORRIDORFLR1 N/A N/A N/A Yes Yes unknown No 41350.036 32990.561 2.179854 -999.0 -999.000 -999.0000 1.00000 1.00000 1024.3375 1004.8586 1.1486 CORRIDORFLR1 PTAC SUPPLY FAN Fan:OnOff 2.179854 2.50368441   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown unknown unknown 7/21 18:00:00 Sensible 41474.94 28716.07 1.0030 2.50368441 2.179854 23.97 17.53 0.01048843 50784.8 13.46 11.45 0.00800000 33731.5 -999.0 -999.00 -999.00 -999.00 1388.274 40086.67 28.66 0.01536037 22.44 0.04587416 2.1045 23.87 0.01038336 23.87 0.01038336 53.5732 25132.95 0.00 41370.28 32181.28 2.40480780 26.67 19.44 0.01118466 55322.4 13.58 13.57 0.00968650 38119.2
CORRIDORFLR1 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR1 PTAC CORRIDORFLR1 N/A N/A N/A Yes No unknown No 76487.200 76487.200 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 CORRIDORFLR1 PTAC SUPPLY FAN Fan:OnOff 2.179854 2.50368441   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 76487.20 76487.20 1.0000 2.50368441 2.179854 20.04 11.18 0.00503436 32915.9 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 76487.20 -26.20 0.00036134 -26.20 0.04587416 2.1045 21.05 0.00513481 21.03 0.00513481 31.7387 73899.39 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
MECHRM UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:UNITHEATER MECHANICALROOMFLR1 UNIT HEATER MECHANICALROOMFLR1 N/A N/A N/A Yes No unknown No 0.000 0.000 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 MECHRM UNITHEATER FAN Fan:ConstantVolume 0.000000 0.00000000   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 0.00 0.00 1.0000 Too Big -999.0 7.20 7.20 0.00800000 27349.4 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 0.00 -26.20 0.00036134 -26.20 0.00000000 -999.0000 7.20 0.00800000 7.20 0.00800000 100.0000 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
101 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 101 PTAC GUESTROOM101 N/A N/A N/A Yes Yes unknown No 1984.326 1588.761 0.119873 -999.0 -999.000 -999.0000 1.28010 1.00000 1021.2895 1004.8586 1.1486 101 PTAC SUPPLY FAN Fan:OnOff 0.119873 0.13768097   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 unknown unknown unknown 7/21 18:10:00 Sensible 1866.14 1585.23 0.9404 0.13768097 0.119873 21.93 15.47 0.00884883 44526.8 13.46 11.45 0.00800000 33729.8 -999.0 -999.00 -999.00 -999.00 76.343 1789.80 28.39 0.01535988 22.36 0.01347978 11.2450 21.11 0.00802389 21.11 0.00802389 49.1383 998.34 0.00 1985.30 1549.03 0.13224362 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
101 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 101 PTAC GUESTROOM101 N/A N/A N/A Yes No unknown No 1279.858 1279.858 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 101 PTAC SUPPLY FAN Fan:OnOff 0.119873 0.13768097   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1279.86 1279.86 1.0000 0.01809115 0.015751 -19.38 -19.38 0.00143455 -15935.2 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1279.86 -26.20 0.00036134 -26.20 0.01347978 85.5793 21.11 0.00780343 21.11 0.00780343 47.8055 532.94 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
102 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 102 PTAC GUESTROOM102 N/A N/A N/A Yes Yes unknown No 1609.717 1288.829 0.097243 -999.0 -999.000 -999.0000 1.21314 1.00000 1021.6553 1004.8586 1.1486 102 PTAC SUPPLY FAN Fan:OnOff 0.097243 0.11168905   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 unknown unknown unknown 7/21 18:10:00 Sensible 1525.48 1255.66 0.9477 0.11168905 0.097243 22.12 15.71 0.00904560 45221.6 13.46 11.45 0.00800000 33730.0 -999.0 -999.00 -999.00 -999.00 61.931 1463.55 28.39 0.01535988 22.36 0.01347978 13.8619 21.11 0.00802946 21.11 0.00802946 49.1720 809.87 0.00 1610.51 1256.60 0.10727818 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
102 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 102 PTAC GUESTROOM102 N/A N/A N/A Yes No unknown No 1343.437 1343.437 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 102 PTAC SUPPLY FAN Fan:OnOff 0.097243 0.11168905   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 Sensible 1343.44 1343.44 1.0000 0.02024938 0.017630 -15.06 -15.06 0.00211817 -9896.9 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1343.44 -26.20 0.00036134 -26.20 0.01347978 76.4580 21.11 0.00782389 21.11 0.00782389 47.9293 596.52 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
103 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 103 PTAC GUESTROOM103 N/A N/A N/A Yes Yes unknown No 2904.493 2325.498 0.175460 -999.0 -999.000 -999.0000 1.33991 1.00000 1021.0764 1004.8586 1.1486 103 PTAC SUPPLY FAN Fan:OnOff 0.175460 0.20152611   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 unknown unknown unknown 7/21 18:10:00 Sensible 2714.61 2346.95 0.9346 0.20152611 0.175460 21.67 15.28 0.00873420 43970.2 13.46 11.45 0.00800000 33729.7 -999.0 -999.00 -999.00 -999.00 111.745 2602.86 28.39 0.01535988 22.36 0.01347978 7.6825 21.11 0.00818283 21.11 0.00818283 50.1007 1461.17 0.00 2905.92 2267.34 0.19356735 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
103 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 103 PTAC GUESTROOM103 N/A N/A N/A Yes No unknown No 1868.293 1868.293 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 103 PTAC SUPPLY FAN Fan:OnOff 0.175460 0.20152611   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:10:00 Sensible 1868.29 1868.29 1.0000 0.03806605 0.033143 1.87 1.87 0.00483701 13991.4 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1868.29 -26.20 0.00036134 -26.20 0.01347978 40.6721 21.11 0.00790530 21.11 0.00790530 48.4217 1121.38 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
104 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 104 PTAC GUESTROOM104 N/A N/A N/A Yes Yes unknown No 3021.027 2418.801 0.182500 -999.0 -999.000 -999.0000 1.35446 1.00000 1021.0248 1004.8586 1.1486 104 PTAC SUPPLY FAN Fan:OnOff 0.182500 0.20961168   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 unknown unknown unknown 7/21 10:40:00 Sensible 2825.47 2454.46 0.9353 0.20961168 0.182500 21.64 15.25 0.00870644 43865.5 13.46 11.45 0.00800000 33729.7 -999.0 -999.00 -999.00 -999.00 116.228 2709.24 28.23 0.01535959 22.32 0.01347882 7.3856 21.11 0.00817587 21.11 0.00817587 50.0587 1519.80 0.00 3022.51 2358.31 0.20133360 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
104 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 104 PTAC GUESTROOM104 N/A N/A N/A Yes No unknown No 1891.338 1891.338 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 104 PTAC SUPPLY FAN Fan:OnOff 0.182500 0.20961168   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:10:00 Sensible 1891.34 1891.34 1.0000 0.03885013 0.033825 2.26 2.26 0.00490029 14545.0 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1891.34 -26.20 0.00036134 -26.20 0.01347882 39.8485 21.11 0.00790719 21.11 0.00790719 48.4332 1144.47 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
105 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 105 PTAC GUESTROOM105 N/A N/A N/A Yes Yes unknown No 4350.616 3483.343 0.262821 -999.0 -999.000 -999.0000 1.44941 1.00000 1020.6287 1004.8586 1.1486 105 PTAC SUPPLY FAN Fan:OnOff 0.262821 0.30186424   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 unknown unknown unknown 7/21 10:30:00 Sensible 4049.10 3657.22 0.9307 0.30186424 0.262821 21.46 15.00 0.00849335 43146.2 13.46 11.45 0.00800000 33729.5 -999.0 -999.00 -999.00 -999.00 167.381 3881.71 27.97 0.01535910 22.25 0.01347882 5.1285 21.11 0.00812221 21.11 0.00812221 49.7342 2188.69 0.00 4352.75 3396.24 0.28994289 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
105 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 105 PTAC GUESTROOM105 N/A N/A N/A Yes No unknown No 1342.105 1342.105 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 105 PTAC SUPPLY FAN Fan:OnOff 0.262821 0.30186424   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 Sensible 1342.11 1342.11 1.0000 0.02020598 0.017593 -15.14 -15.14 0.00210624 -10002.2 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1342.11 -26.20 0.00036134 -26.20 0.01347882 76.6168 21.11 0.00782351 21.11 0.00782351 47.9270 595.24 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FRONTSTAIRSFLR1 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:UNITHEATER FRONTSTAIRSFLR1 UNIT HEATER FRONTSTAIRSFLR1 N/A N/A N/A Yes No unknown No 306.618 306.618 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 FRONTSTAIRSFLR1 UNITHEATER FAN Fan:ConstantVolume 0.006116 0.00702507   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 Sensible 306.62 306.62 1.0000 0.00702507 0.006116 7.20 3.22 0.00338043 15731.7 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 306.62 -26.20 0.00036134 -26.20 0.00000000 0.0000 7.20 0.00338043 7.20 0.00338043 51.4331 146.99 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
REARSTAIRSFLR2 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:UNITHEATER REARSTAIRSFLR2 UNIT HEATER REARSTAIRSFLR2 N/A N/A N/A Yes No unknown No 306.673 306.673 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 REARSTAIRSFLR2 UNITHEATER FAN Fan:ConstantVolume 0.006118 0.00702675   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 306.67 306.67 1.0000 0.00702675 0.006118 7.20 7.20 0.00800000 27349.4 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 306.67 -26.20 0.00036134 -26.20 0.00000000 0.0000 7.20 0.00800000 7.20 0.00800000 100.0000 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
CORRIDORFLR2 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR2 PTAC CORRIDORFLR2 N/A N/A N/A Yes Yes unknown No 4334.911 3470.769 0.261872 -999.0 -999.000 -999.0000 1.01418 1.00000 1021.8288 1004.8586 1.1486 CORRIDORFLR2 PTAC SUPPLY FAN Fan:OnOff 0.261872 0.30077455   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown unknown unknown 7/21 18:00:00 Sensible 4222.50 3533.81 0.9741 0.30077455 0.261872 24.58 16.64 0.00913893 47977.3 13.46 11.45 0.00800000 33730.1 -999.0 -999.00 -999.00 -999.00 166.777 4055.72 28.66 0.01536037 22.44 0.03822807 14.5980 23.89 0.00807548 23.89 0.00807548 41.7694 3032.94 0.00 4337.03 3383.98 0.28889623 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
CORRIDORFLR2 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR2 PTAC CORRIDORFLR2 N/A N/A N/A Yes No unknown No 4060.991 4060.991 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 CORRIDORFLR2 PTAC SUPPLY FAN Fan:OnOff 0.261872 0.30077455   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:20:00 Sensible 4060.99 4060.99 1.0000 0.06594867 0.057419 -10.39 -10.39 0.00279182 -3509.7 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 4060.99 -26.20 0.00036134 -26.20 0.03822807 66.5776 21.11 0.00763335 21.11 0.00763335 46.7769 1942.78 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
201 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 201 PTAC GUESTROOM201 N/A N/A N/A Yes Yes unknown No 2234.617 1789.158 0.134993 -999.0 -999.000 -999.0000 1.29284 1.00000 1021.1893 1004.8586 1.1486 201 PTAC SUPPLY FAN Fan:OnOff 0.134993 0.15504727   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown unknown unknown 7/21 17:50:00 Sensible 2086.46 1788.48 0.9337 0.15504727 0.134993 21.88 15.41 0.00879493 44341.1 13.46 11.45 0.00800000 33729.8 -999.0 -999.00 -999.00 -999.00 85.973 2000.49 28.83 0.01536070 22.49 0.01347978 9.9855 21.11 0.00806658 21.11 0.00806658 49.3968 1124.24 0.00 2235.71 1744.42 0.14892407 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
201 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 201 PTAC GUESTROOM201 N/A N/A N/A Yes No unknown No 1771.229 1771.229 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 201 PTAC SUPPLY FAN Fan:OnOff 0.134993 0.15504727   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 Sensible 1771.23 1771.23 1.0000 0.03477093 0.030274 0.04 0.04 0.00442230 11105.2 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1771.23 -26.20 0.00036134 -26.20 0.01347978 44.5265 21.11 0.00768188 21.11 0.00768188 47.0709 1024.33 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
202_205 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 202_205 PTAC GUESTROOM202_205 N/A N/A N/A Yes Yes unknown No 11528.113 9230.044 0.696413 -999.0 -999.000 -999.0000 1.32697 1.00000 1021.0876 1004.8586 1.1486 202_205 PTAC SUPPLY FAN Fan:OnOff 0.696413 0.79986954   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown unknown unknown 7/21 17:50:00 Sensible 10725.57 9266.84 0.9304 0.79986954 0.696413 21.71 15.30 0.00874018 44024.6 13.46 11.45 0.00800000 33729.7 -999.0 -999.00 -999.00 -999.00 443.522 10282.05 28.83 0.01536070 22.49 0.05391910 7.7424 21.11 0.00818458 21.11 0.00818458 50.1119 5799.33 0.00 11533.76 8999.23 0.76828074 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
202_205 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 202_205 PTAC GUESTROOM202_205 N/A N/A N/A Yes No unknown No 4908.574 4908.574 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 202_205 PTAC SUPPLY FAN Fan:OnOff 0.696413 0.79986954   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 Sensible 4908.57 4908.57 1.0000 0.06520683 0.056773 -23.82 -23.82 0.00073408 -22133.7 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 4908.57 -26.20 0.00036134 -26.20 0.05391910 94.9733 21.11 0.00777663 21.11 0.00777663 47.6432 1920.91 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
206_208 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 206_208 PTAC GUESTROOM206_208 N/A N/A N/A Yes Yes unknown No 9529.403 7629.766 0.575671 -999.0 -999.000 -999.0000 1.34071 1.00000 1021.0177 1004.8586 1.1486 206_208 PTAC SUPPLY FAN Fan:OnOff 0.575671 0.66119053   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown unknown unknown 7/21 17:50:00 Sensible 8854.09 7701.02 0.9291 0.66119053 0.575671 21.68 15.26 0.00870258 43903.9 13.46 11.45 0.00800000 33729.7 -999.0 -999.00 -999.00 -999.00 366.625 8487.46 28.83 0.01536070 22.49 0.04273309 7.4232 21.11 0.00816870 21.11 0.00816870 50.0157 4793.90 0.00 9534.07 7438.97 0.63507850 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
206_208 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 206_208 PTAC GUESTROOM206_208 N/A N/A N/A Yes No unknown No 3860.930 3860.930 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 206_208 PTAC SUPPLY FAN Fan:OnOff 0.575671 0.66119053   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 Sensible 3860.93 3860.93 1.0000 0.05068395 0.044128 -24.70 -24.70 0.00059554 -23361.5 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 3860.93 -26.20 0.00036134 -26.20 0.04273309 96.8380 21.11 0.00776812 21.11 0.00776812 47.5921 1493.09 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
209_212 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 209_212 PTAC GUESTROOM209_212 N/A N/A N/A Yes Yes unknown No 10640.371 8519.269 0.642785 -999.0 -999.000 -999.0000 1.30444 1.00000 1021.1999 1004.8586 1.1486 209_212 PTAC SUPPLY FAN Fan:OnOff 0.642785 0.73827428   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown unknown unknown 7/21 17:50:00 Sensible 9922.23 8483.75 0.9325 0.73827428 0.642785 21.76 15.37 0.00880064 44229.1 13.46 11.45 0.00800000 33729.8 -999.0 -999.00 -999.00 -999.00 409.367 9512.86 28.83 0.01536070 22.49 0.05391910 8.3884 21.11 0.00819997 21.11 0.00819997 50.2049 5352.74 0.00 10645.58 8306.23 0.70911802 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
209_212 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 209_212 PTAC GUESTROOM209_212 N/A N/A N/A Yes No unknown No 4812.016 4812.016 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 209_212 PTAC SUPPLY FAN Fan:OnOff 0.642785 0.73827428   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 Sensible 4812.02 4812.02 1.0000 0.06192910 0.053919 -26.20 -26.20 0.00036134 -25440.7 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 4812.02 -26.20 0.00036134 -26.20 0.05391910 100.0000 21.11 0.00775882 21.11 0.00775882 47.5359 1775.01 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
213 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 213 PTAC GUESTROOM213 N/A N/A N/A Yes Yes unknown No 2924.556 2341.562 0.176672 -999.0 -999.000 -999.0000 1.33099 1.00000 1021.0679 1004.8586 1.1486 213 PTAC SUPPLY FAN Fan:OnOff 0.176672 0.20291818   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown unknown unknown 7/21 17:50:00 Sensible 2719.88 2354.30 0.9300 0.20291818 0.176672 21.70 15.29 0.00872963 43988.9 13.46 11.45 0.00800000 33729.7 -999.0 -999.00 -999.00 -999.00 112.517 2607.36 28.83 0.01536070 22.49 0.01347978 7.6298 21.11 0.00818190 21.11 0.00818190 50.0954 1471.24 0.00 2925.99 2283.01 0.19490445 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
213 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 213 PTAC GUESTROOM213 N/A N/A N/A Yes No unknown No 1741.291 1741.291 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 213 PTAC SUPPLY FAN Fan:OnOff 0.176672 0.20291818   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 Sensible 1741.29 1741.29 1.0000 0.03375490 0.029389 -0.59 -0.59 0.00443710 10500.1 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1741.29 -26.20 0.00036134 -26.20 0.01347978 45.8667 21.11 0.00789047 21.11 0.00789047 48.3319 994.38 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
214 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 214 PTAC GUESTROOM214 N/A N/A N/A Yes Yes unknown No 3278.414 2624.880 0.198049 -999.0 -999.000 -999.0000 1.40181 1.00000 1020.9239 1004.8586 1.1486 214 PTAC SUPPLY FAN Fan:OnOff 0.198049 0.22747034   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown unknown unknown 7/21 10:00:00 Sensible 3095.39 2713.10 0.9442 0.22747034 0.198049 21.52 15.16 0.00865216 43611.7 13.46 11.45 0.00800000 33729.6 -999.0 -999.00 -999.00 -999.00 126.131 2969.26 27.17 0.01535764 22.03 0.01347882 6.8058 21.11 0.00816247 21.11 0.00816247 49.9779 1649.26 0.00 3280.02 2559.24 0.21848698 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
214 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 214 PTAC GUESTROOM214 N/A N/A N/A Yes No unknown No 1734.894 1734.894 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 214 PTAC SUPPLY FAN Fan:OnOff 0.198049 0.22747034   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 Sensible 1734.89 1734.89 1.0000 0.03353957 0.029202 -0.73 -0.73 0.00441481 10304.8 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1734.89 -26.20 0.00036134 -26.20 0.01347882 46.1579 21.11 0.00788978 21.11 0.00788978 48.3277 988.03 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
215_218 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 215_218 PTAC GUESTROOM215_218 N/A N/A N/A Yes Yes unknown No 32246.130 25818.033 1.947989 -999.0 -999.000 -999.0000 1.60810 1.00000 1020.1012 1004.8586 1.1486 215_218 PTAC SUPPLY FAN Fan:OnOff 1.947989 2.23737378   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 unknown unknown unknown 7/21 09:50:00 Sensible 30090.61 28759.58 0.9332 2.23737378 1.947989 21.27 14.68 0.00820956 42229.5 13.46 11.45 0.00800000 33729.2 -999.0 -999.00 -999.00 -999.00 1240.607 28850.00 26.87 0.01535708 21.94 0.05391527 2.7677 21.11 0.00800610 21.11 0.00800610 49.0308 16223.43 0.00 32261.91 25172.40 2.14901443 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
215_218 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 215_218 PTAC GUESTROOM215_218 N/A N/A N/A Yes No unknown No 4811.675 4811.675 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 215_218 PTAC SUPPLY FAN Fan:OnOff 1.947989 2.23737378   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4811.67 4811.67 1.0000 0.06192470 0.053915 -26.20 -26.20 0.00036134 -25440.7 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 4811.67 -26.20 0.00036134 -26.20 0.05391527 100.0000 21.11 0.00775613 21.11 0.00775613 47.5196 1754.72 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
219 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 219 PTAC GUESTROOM219 N/A N/A N/A Yes Yes unknown No 17172.473 13749.231 1.037389 -999.0 -999.000 -999.0000 1.66036 1.00000 1019.9463 1004.8586 1.1486 219 PTAC SUPPLY FAN Fan:OnOff 1.037389 1.19149928   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 unknown unknown unknown 7/21 09:50:00 Sensible 15971.55 15535.04 0.9301 1.19149928 1.037389 21.19 14.57 0.00812627 41931.2 13.46 11.45 0.00800000 33729.1 -999.0 -999.00 -999.00 -999.00 660.677 15310.87 26.87 0.01535708 21.94 0.01347882 1.2993 21.11 0.00803109 21.11 0.00803109 49.1834 8639.07 0.00 17180.88 13405.40 1.14444407 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
219 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 219 PTAC GUESTROOM219 N/A N/A N/A Yes No unknown No 1202.919 1202.919 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 219 PTAC SUPPLY FAN Fan:OnOff 1.037389 1.19149928   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1202.92 1202.92 1.0000 0.01548118 0.013479 -26.20 -26.20 0.00036134 -25440.7 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1202.92 -26.20 0.00036134 -26.20 0.01347882 100.0000 21.11 0.00776104 21.11 0.00776104 47.5492 448.04 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
220_223 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 220_223 PTAC GUESTROOM220_223 N/A N/A N/A Yes Yes unknown No 10924.991 8747.152 0.659979 -999.0 -999.000 -999.0000 1.35277 1.00000 1021.1618 1004.8586 1.1486 220_223 PTAC SUPPLY FAN Fan:OnOff 0.659979 0.75802242   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown unknown unknown 7/21 10:00:00 Sensible 10361.45 8875.94 0.9484 0.75802242 0.659979 21.61 15.30 0.00878012 44021.2 13.46 11.45 0.00800000 33729.8 -999.0 -999.00 -999.00 -999.00 420.318 9941.13 27.17 0.01535764 22.03 0.05391527 8.1692 21.11 0.00819499 21.11 0.00819499 50.1748 5495.92 0.00 10930.34 8528.41 0.72808626 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
220_223 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 220_223 PTAC GUESTROOM220_223 N/A N/A N/A Yes No unknown No 4811.675 4811.675 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 220_223 PTAC SUPPLY FAN Fan:OnOff 0.659979 0.75802242   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 4811.67 4811.67 1.0000 0.06192470 0.053915 -26.20 -26.20 0.00036134 -25440.7 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 4811.67 -26.20 0.00036134 -26.20 0.05391527 100.0000 21.11 0.00775396 21.11 0.00775396 47.5065 1743.26 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
224 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 224 PTAC GUESTROOM224 N/A N/A N/A Yes Yes unknown No 3122.250 2499.846 0.188615 -999.0 -999.000 -999.0000 1.38916 1.00000 1020.9835 1004.8586 1.1486 224 PTAC SUPPLY FAN Fan:OnOff 0.188615 0.21663498   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown unknown unknown 7/21 10:00:00 Sensible 2951.26 2571.76 0.9452 0.21663498 0.188615 21.54 15.19 0.00868419 43714.2 13.46 11.45 0.00800000 33729.7 -999.0 -999.00 -999.00 -999.00 120.122 2831.13 27.17 0.01535764 22.03 0.01347882 7.1462 21.11 0.00817059 21.11 0.00817059 50.0270 1570.70 0.00 3123.78 2437.33 0.20807954 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
224 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 224 PTAC GUESTROOM224 N/A N/A N/A Yes No unknown No 1545.165 1545.165 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 224 PTAC SUPPLY FAN Fan:OnOff 0.188615 0.21663498   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 Sensible 1545.17 1545.17 1.0000 0.02709899 0.023594 -5.92 -5.92 0.00357788 2963.0 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1545.17 -26.20 0.00036134 -26.20 0.01347882 57.1282 21.11 0.00786403 21.11 0.00786403 48.1723 798.30 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FRONTSTAIRSFLR2 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:UNITHEATER FRONTSTAIRSFLR2 UNIT HEATER FRONTSTAIRSFLR2 N/A N/A N/A Yes No unknown No 306.616 306.616 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 FRONTSTAIRSFLR2 UNITHEATER FAN Fan:ConstantVolume 0.006116 0.00702507   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 Sensible 306.62 306.62 1.0000 0.00702507 0.006116 7.20 3.55 0.00362905 16357.2 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 306.62 -26.20 0.00036134 -26.20 0.00000000 0.0000 7.20 0.00362905 7.20 0.00362905 55.1925 172.65 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
REARSTAIRSFLR3 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:UNITHEATER REARSTAIRSFLR3 UNIT HEATER REARSTAIRSFLR3 N/A N/A N/A Yes No unknown No 306.673 306.673 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 REARSTAIRSFLR3 UNITHEATER FAN Fan:ConstantVolume 0.006118 0.00702675   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 306.67 306.67 1.0000 0.00702675 0.006118 7.20 7.20 0.00800000 27349.4 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 306.67 -26.20 0.00036134 -26.20 0.00000000 0.0000 7.20 0.00800000 7.20 0.00800000 100.0000 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
CORRIDORFLR3 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR3 PTAC CORRIDORFLR3 N/A N/A N/A Yes Yes unknown No 1932.589 1415.220 0.085830 -999.0 -999.000 -999.0000 1.00000 1.00000 1026.0648 1004.8586 1.1486 CORRIDORFLR3 PTAC SUPPLY FAN Fan:OnOff 0.085830 0.09858110   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 unknown unknown unknown 7/21 18:10:00 Sensible 2032.35 1322.14 1.0516 0.09858110 0.085830 25.89 18.87 0.01141761 55123.7 13.46 11.45 0.00800000 33732.4 -999.0 -999.00 -999.00 -999.00 54.662 1977.69 28.39 0.01535988 22.36 0.03822807 44.5390 23.89 0.00825170 23.89 0.00825170 42.6691 994.06 0.00 1933.53 1384.64 0.09468789 26.67 19.44 0.01118466 55322.4 12.35 12.32 0.00891183 34902.3
CORRIDORFLR3 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR3 PTAC CORRIDORFLR3 N/A N/A N/A Yes No unknown No 4366.458 4366.458 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 CORRIDORFLR3 PTAC SUPPLY FAN Fan:OnOff 0.085830 0.09858110   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 Sensible 4366.46 4366.46 1.0000 0.07631808 0.066447 -6.11 -6.11 0.00345626 2467.1 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 4366.46 -26.20 0.00036134 -26.20 0.03822807 57.5317 21.11 0.00764892 21.11 0.00764892 46.8708 2248.25 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
301 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 301 PTAC GUESTROOM301 N/A N/A N/A Yes Yes unknown No 1631.219 1306.044 0.098542 -999.0 -999.000 -999.0000 1.19644 1.00000 1021.7446 1004.8586 1.1486 301 PTAC SUPPLY FAN Fan:OnOff 0.098542 0.11318094   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown unknown unknown 7/21 18:00:00 Sensible 1543.61 1260.78 0.9463 0.11318094 0.098542 22.14 15.76 0.00909362 45367.0 13.46 11.45 0.00800000 33730.1 -999.0 -999.00 -999.00 -999.00 62.758 1480.85 28.66 0.01536037 22.44 0.01347978 13.6792 21.11 0.00810053 21.11 0.00810053 49.6021 820.67 0.00 1632.02 1273.38 0.10871115 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
301 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 301 PTAC GUESTROOM301 N/A N/A N/A Yes No unknown No 1841.998 1841.998 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 301 PTAC SUPPLY FAN Fan:OnOff 0.098542 0.11318094   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 Sensible 1842.00 1842.00 1.0000 0.03717314 0.032365 1.41 1.41 0.00462680 12996.3 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1842.00 -26.20 0.00036134 -26.20 0.01347978 41.6491 21.11 0.00767136 21.11 0.00767136 47.0074 1095.09 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
302_305 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 302_305 PTAC GUESTROOM302_305 N/A N/A N/A Yes Yes unknown No 5262.130 4213.152 0.317885 -999.0 -999.000 -999.0000 1.13593 1.00000 1022.0956 1004.8586 1.1486 302_305 PTAC SUPPLY FAN Fan:OnOff 0.317885 0.36510897   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown unknown unknown 7/21 18:00:00 Sensible 5019.80 3990.77 0.9539 0.36510897 0.317885 22.39 16.01 0.00928243 46100.2 13.46 11.45 0.00800000 33730.3 -999.0 -999.00 -999.00 -999.00 202.450 4817.35 28.66 0.01536037 22.44 0.05391910 16.9618 21.11 0.00804092 21.11 0.00804092 49.2413 2647.43 0.00 5264.71 4107.79 0.35068993 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
302_305 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 302_305 PTAC GUESTROOM302_305 N/A N/A N/A Yes No unknown No 5032.362 5032.362 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 302_305 PTAC SUPPLY FAN Fan:OnOff 0.317885 0.36510897   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 Sensible 5032.36 5032.36 1.0000 0.06940892 0.060431 -21.10 -21.10 0.00115954 -18349.3 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 5032.36 -26.20 0.00036134 -26.20 0.05391910 89.2235 21.11 0.00776817 21.11 0.00776817 47.5921 2044.70 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
306_308 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 306_308 PTAC GUESTROOM306_308 N/A N/A N/A Yes Yes unknown No 4786.204 3832.099 0.289135 -999.0 -999.000 -999.0000 1.17902 1.00000 1021.7915 1004.8586 1.1486 306_308 PTAC SUPPLY FAN Fan:OnOff 0.289135 0.33208722   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 unknown unknown unknown 7/21 17:50:00 Sensible 4528.78 3689.50 0.9462 0.33208722 0.289135 22.25 15.82 0.00911884 45542.8 13.46 11.45 0.00800000 33730.1 -999.0 -999.00 -999.00 -999.00 184.140 4344.64 28.83 0.01536070 22.49 0.04273309 14.7797 21.11 0.00803633 21.11 0.00803633 49.2136 2407.99 0.00 4788.55 3736.27 0.31897228 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
306_308 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 306_308 PTAC GUESTROOM306_308 N/A N/A N/A Yes No unknown No 4052.847 4052.847 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 306_308 PTAC SUPPLY FAN Fan:OnOff 0.289135 0.33208722   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:20:00 Sensible 4052.85 4052.85 1.0000 0.05719874 0.049801 -19.49 -19.49 0.00141312 -16097.2 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 4052.85 -26.20 0.00036134 -26.20 0.04273309 85.8084 21.11 0.00777264 21.11 0.00777264 47.6191 1685.01 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
309_312 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 309_312 PTAC GUESTROOM309_312 N/A N/A N/A Yes Yes unknown No 10142.199 8120.405 0.612690 -999.0 -999.000 -999.0000 1.29436 1.00000 1021.2748 1004.8586 1.1486 309_312 PTAC SUPPLY FAN Fan:OnOff 0.612690 0.70370891   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown unknown unknown 7/21 18:00:00 Sensible 9489.68 8056.87 0.9357 0.70370891 0.612690 21.77 15.41 0.00884089 44348.0 13.46 11.45 0.00800000 33729.8 -999.0 -999.00 -999.00 -999.00 390.201 9099.48 28.66 0.01536037 22.44 0.05391910 8.8004 21.11 0.00821178 21.11 0.00821178 50.2763 5102.12 0.00 10147.16 7917.34 0.67591773 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
309_312 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 309_312 PTAC GUESTROOM309_312 N/A N/A N/A Yes No unknown No 5009.432 5009.432 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 309_312 PTAC SUPPLY FAN Fan:OnOff 0.612690 0.70370891   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 Sensible 5009.43 5009.43 1.0000 0.06863054 0.059754 -21.58 -21.58 0.00108433 -19016.4 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 5009.43 -26.20 0.00036134 -26.20 0.05391910 90.2355 21.11 0.00776562 21.11 0.00776562 47.5767 2021.77 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
313 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 313 PTAC GUESTROOM313 N/A N/A N/A Yes Yes unknown No 1800.623 1441.679 0.108776 -999.0 -999.000 -999.0000 1.24195 1.00000 1021.4558 1004.8586 1.1486 313 PTAC SUPPLY FAN Fan:OnOff 0.108776 0.12493491   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 unknown unknown unknown 7/21 18:00:00 Sensible 1694.68 1419.32 0.9412 0.12493491 0.108776 22.05 15.59 0.00893829 44873.1 13.46 11.45 0.00800000 33729.9 -999.0 -999.00 -999.00 -999.00 69.275 1625.40 28.66 0.01536037 22.44 0.01347978 12.3923 21.11 0.00802987 21.11 0.00802987 49.1745 905.91 0.00 1801.50 1405.63 0.12000093 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
313 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 313 PTAC GUESTROOM313 N/A N/A N/A Yes No unknown No 1833.949 1833.949 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 313 PTAC SUPPLY FAN Fan:OnOff 0.108776 0.12493491   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 Sensible 1833.95 1833.95 1.0000 0.03690024 0.032128 1.26 1.26 0.00473073 13109.0 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1833.95 -26.20 0.00036134 -26.20 0.01347978 41.9571 21.11 0.00788920 21.11 0.00788920 48.3242 1087.03 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
314 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 314 PTAC GUESTROOM314 N/A N/A N/A Yes Yes unknown No 2833.748 2268.855 0.171187 -999.0 -999.000 -999.0000 1.35597 1.00000 1021.1135 1004.8586 1.1486 314 PTAC SUPPLY FAN Fan:OnOff 0.171187 0.19661749   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown unknown unknown 7/21 10:10:00 Sensible 2677.55 2304.77 0.9449 0.19661749 0.171187 21.61 15.28 0.00875412 43958.2 13.46 11.45 0.00800000 33729.8 -999.0 -999.00 -999.00 -999.00 109.023 2568.53 27.44 0.01535813 22.10 0.01347882 7.8738 21.11 0.00818970 21.11 0.00818970 50.1426 1425.56 0.00 2835.13 2212.12 0.18885258 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
314 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 314 PTAC GUESTROOM314 N/A N/A N/A Yes No unknown No 1804.072 1804.072 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 314 PTAC SUPPLY FAN Fan:OnOff 0.171187 0.19661749   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 Sensible 1804.07 1804.07 1.0000 0.03588785 0.031246 0.70 0.70 0.00464011 12316.1 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1804.07 -26.20 0.00036134 -26.20 0.01347882 43.1377 21.11 0.00788612 21.11 0.00788612 48.3056 1057.21 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
315_318 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 315_318 PTAC GUESTROOM315_318 N/A N/A N/A Yes Yes unknown No 12470.185 9984.319 0.753324 -999.0 -999.000 -999.0000 1.38831 1.00000 1020.9881 1004.8586 1.1486 315_318 PTAC SUPPLY FAN Fan:OnOff 0.753324 0.86523452   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown unknown unknown 7/21 10:00:00 Sensible 11788.14 10267.55 0.9453 0.86523452 0.753324 21.54 15.20 0.00868670 43721.1 13.46 11.45 0.00800000 33729.7 -999.0 -999.00 -999.00 -999.00 479.766 11308.38 27.17 0.01535764 22.03 0.05391527 7.1570 21.11 0.00817246 21.11 0.00817246 50.0386 6273.25 0.00 12476.29 9734.64 0.83106430 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
315_318 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 315_318 PTAC GUESTROOM315_318 N/A N/A N/A Yes No unknown No 4970.131 4970.131 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 315_318 PTAC SUPPLY FAN Fan:OnOff 0.753324 0.86523452   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 Sensible 4970.13 4970.13 1.0000 0.06730362 0.058598 -22.42 -22.42 0.00095273 -20184.4 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 4970.13 -26.20 0.00036134 -26.20 0.05391527 92.0080 21.11 0.00776113 21.11 0.00776113 47.5495 1982.68 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
319 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 319 PTAC GUESTROOM319 N/A N/A N/A Yes Yes unknown No 2944.656 2357.654 0.177887 -999.0 -999.000 -999.0000 1.42099 1.00000 1020.7796 1004.8586 1.1486 319 PTAC SUPPLY FAN Fan:OnOff 0.177887 0.20431278   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown unknown unknown 7/21 10:00:00 Sensible 2775.78 2470.37 0.9427 0.20431278 0.177887 21.57 15.11 0.00857454 43462.8 13.46 11.45 0.00800000 33729.6 -999.0 -999.00 -999.00 -999.00 113.290 2662.49 27.17 0.01535764 22.03 0.01347882 7.5772 21.11 0.00801843 21.11 0.00801843 49.1053 1481.49 0.00 2946.10 2298.70 0.19624397 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
319 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 319 PTAC GUESTROOM319 N/A N/A N/A Yes No unknown No 1308.606 1308.606 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 319 PTAC SUPPLY FAN Fan:OnOff 0.177887 0.20431278   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 Sensible 1308.61 1308.61 1.0000 0.01906882 0.016602 -17.30 -17.30 0.00175869 -13040.7 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1308.61 -26.20 0.00036134 -26.20 0.01347882 81.1858 21.11 0.00778845 21.11 0.00778845 47.7148 561.74 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
320_323 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 320_323 PTAC GUESTROOM320_323 N/A N/A N/A Yes Yes unknown No 9769.131 7821.706 0.590153 -999.0 -999.000 -999.0000 1.31995 1.00000 1021.3328 1004.8586 1.1486 320_323 PTAC SUPPLY FAN Fan:OnOff 0.590153 0.67782392   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown unknown unknown 7/21 10:00:00 Sensible 9294.96 7836.15 0.9515 0.67782392 0.590153 21.66 15.40 0.00887210 44314.7 13.46 11.45 0.00800000 33729.9 -999.0 -999.00 -999.00 -999.00 375.848 8919.11 27.17 0.01535764 22.03 0.05391527 9.1358 21.11 0.00822002 21.11 0.00822002 50.3261 4914.44 0.00 9773.91 7626.11 0.65105500 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
320_323 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 320_323 PTAC GUESTROOM320_323 N/A N/A N/A Yes No unknown No 4897.963 4897.963 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 320_323 PTAC SUPPLY FAN Fan:OnOff 0.590153 0.67782392   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:20:00 Sensible 4897.96 4897.96 1.0000 0.06485382 0.056466 -24.06 -24.06 0.00069516 -22472.2 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 4897.96 -26.20 0.00036134 -26.20 0.05391527 95.4835 21.11 0.00775239 21.11 0.00775239 47.4966 1910.52 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
324 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 324 PTAC GUESTROOM324 N/A N/A N/A Yes Yes unknown No 1710.661 1369.650 0.103341 -999.0 -999.000 -999.0000 1.25788 1.00000 1021.5469 1004.8586 1.1486 324 PTAC SUPPLY FAN Fan:OnOff 0.103341 0.11869295   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown unknown unknown 7/21 10:10:00 Sensible 1632.90 1353.99 0.9545 0.11869295 0.103341 21.94 15.60 0.00898728 44885.3 13.46 11.45 0.00800000 33730.0 -999.0 -999.00 -999.00 -999.00 65.814 1567.08 27.44 0.01535813 22.10 0.01347882 13.0430 21.11 0.00803169 21.11 0.00803169 49.1855 860.65 0.00 1711.50 1335.40 0.11400548 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
324 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 324 PTAC GUESTROOM324 N/A N/A N/A Yes No unknown No 1608.140 1608.140 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 324 PTAC SUPPLY FAN Fan:OnOff 0.103341 0.11869295   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 Sensible 1608.14 1608.14 1.0000 0.02923677 0.025455 -3.94 -3.94 0.00388971 5739.6 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1608.14 -26.20 0.00036134 -26.20 0.01347882 52.9511 21.11 0.00786069 21.11 0.00786069 48.1518 861.28 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FRONTSTAIRSFLR3 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:UNITHEATER FRONTSTAIRSFLR3 UNIT HEATER FRONTSTAIRSFLR3 N/A N/A N/A Yes No unknown No 306.619 306.619 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 FRONTSTAIRSFLR3 UNITHEATER FAN Fan:ConstantVolume 0.006116 0.00702507   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 Sensible 306.62 306.62 1.0000 0.00702507 0.006116 7.20 4.08 0.00404205 17395.2 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 306.62 -26.20 0.00036134 -26.20 0.00000000 0.0000 7.20 0.00404205 7.20 0.00404205 61.4350 237.51 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
REARSTAIRSFLR4 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:UNITHEATER REARSTAIRSFLR4 UNIT HEATER REARSTAIRSFLR4 N/A N/A N/A Yes No unknown No 306.691 306.691 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 REARSTAIRSFLR4 UNITHEATER FAN Fan:ConstantVolume 0.006118 0.00702675   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 Sensible 306.69 306.69 1.0000 0.00702675 0.006118 7.20 3.89 0.00389357 17022.0 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 306.69 -26.20 0.00036134 -26.20 0.00000000 0.0000 7.20 0.00389357 7.20 0.00389357 59.1918 235.36 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
CORRIDORFLR4 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR4 PTAC CORRIDORFLR4 N/A N/A N/A Yes Yes unknown No 2867.528 2210.491 0.141289 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.6409 1004.8586 1.1486 CORRIDORFLR4 PTAC SUPPLY FAN Fan:OnOff 0.141289 0.16227836   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 unknown unknown unknown 7/21 15:00:00 Sensible 2827.88 2121.78 0.9862 0.16227836 0.141289 25.87 17.86 0.01011372 51772.3 13.46 11.45 0.00800000 33731.1 -999.0 -999.00 -999.00 -999.00 89.982 2737.89 31.20 0.01536508 23.13 0.03822807 27.0566 23.89 0.00816585 23.89 0.00816585 42.2309 1636.37 0.00 2868.93 2158.56 0.15586959 26.67 19.44 0.01118466 55322.4 13.12 13.11 0.00939778 36916.4
CORRIDORFLR4 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER CORRIDORFLR4 PTAC CORRIDORFLR4 N/A N/A N/A Yes No unknown No 5798.440 5798.440 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 CORRIDORFLR4 PTAC SUPPLY FAN Fan:OnOff 0.141289 0.16227836   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 Sensible 5798.44 5798.44 1.0000 0.12492764 0.108769 4.48 4.10 0.00516390 17462.2 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 5798.44 -26.20 0.00036134 -26.20 0.03822807 35.1460 21.11 0.00776653 21.11 0.00776653 47.5826 3680.24 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
401 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 401 PTAC GUESTROOM401 N/A N/A N/A Yes Yes unknown No 3477.743 2784.473 0.210090 -999.0 -999.000 -999.0000 1.35333 1.00000 1020.9186 1004.8586 1.1486 401 PTAC SUPPLY FAN Fan:OnOff 0.210090 0.24130060   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 unknown unknown unknown 7/21 17:20:00 Sensible 3204.72 2813.90 0.9215 0.24130060 0.210090 21.64 15.20 0.00864930 43723.7 13.46 11.45 0.00800000 33729.6 -999.0 -999.00 -999.00 -999.00 133.799 3070.92 29.36 0.01536168 22.63 0.01347978 6.4162 21.11 0.00818909 21.11 0.00818909 50.1393 1749.50 0.00 3479.45 2714.84 0.23177105 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
401 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 401 PTAC GUESTROOM401 N/A N/A N/A Yes No unknown No 2408.722 2408.722 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 401 PTAC SUPPLY FAN Fan:OnOff 0.210090 0.24130060   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:20:00 Sensible 2408.72 2408.72 1.0000 0.05641092 0.049115 8.13 6.62 0.00573304 22589.7 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 2408.72 -26.20 0.00036134 -26.20 0.01347978 27.4455 21.11 0.00776501 21.11 0.00776501 47.5740 1661.83 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
402_405 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 402_405 PTAC GUESTROOM402_405 N/A N/A N/A Yes Yes unknown No 7100.960 5685.421 0.428969 -999.0 -999.000 -999.0000 1.21857 1.00000 1021.4844 1004.8586 1.1486 402_405 PTAC SUPPLY FAN Fan:OnOff 0.428969 0.49269484   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 unknown unknown unknown 7/21 17:20:00 Sensible 6639.22 5553.36 0.9350 0.49269484 0.428969 22.15 15.64 0.00895363 45016.5 13.46 11.45 0.00800000 33730.0 -999.0 -999.00 -999.00 -999.00 273.196 6366.03 29.36 0.01536168 22.63 0.05391910 12.5695 21.11 0.00803238 21.11 0.00803238 49.1897 3572.57 0.00 7104.44 5543.25 0.47323712 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
402_405 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 402_405 PTAC GUESTROOM402_405 N/A N/A N/A Yes No unknown No 6290.628 6290.628 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 402_405 PTAC SUPPLY FAN Fan:OnOff 0.428969 0.49269484   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 Sensible 6290.63 6290.63 1.0000 0.11212181 0.097620 -5.02 -5.02 0.00371134 4202.1 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 6290.63 -26.20 0.00036134 -26.20 0.05391910 55.2338 21.11 0.00784466 21.11 0.00784466 48.0549 3302.98 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
406_408 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 406_408 PTAC GUESTROOM406_408 N/A N/A N/A Yes Yes unknown No 6379.592 5107.854 0.385391 -999.0 -999.000 -999.0000 1.25779 1.00000 1021.2771 1004.8586 1.1486 406_408 PTAC SUPPLY FAN Fan:OnOff 0.385391 0.44264328   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 unknown unknown unknown 7/21 17:20:00 Sensible 5937.65 5055.84 0.9307 0.44264328 0.385391 22.03 15.50 0.00884216 44608.3 13.46 11.45 0.00800000 33729.8 -999.0 -999.00 -999.00 -999.00 245.442 5692.21 29.36 0.01536168 22.63 0.04273309 11.0882 21.11 0.00802911 21.11 0.00802911 49.1699 3209.64 0.00 6382.72 4980.12 0.42516222 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
406_408 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 406_408 PTAC GUESTROOM406_408 N/A N/A N/A Yes No unknown No 5076.573 5076.573 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 406_408 PTAC SUPPLY FAN Fan:OnOff 0.385391 0.44264328   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 Sensible 5076.57 5076.57 1.0000 0.09194998 0.080057 -4.14 -4.14 0.00385127 5439.2 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 5076.57 -26.20 0.00036134 -26.20 0.04273309 53.3783 21.11 0.00784696 21.11 0.00784696 48.0688 2708.74 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
409_412 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 409_412 PTAC GUESTROOM409_412 N/A N/A N/A Yes Yes unknown No 12598.597 10087.133 0.761081 -999.0 -999.000 -999.0000 1.33740 1.00000 1020.9777 1004.8586 1.1486 409_412 PTAC SUPPLY FAN Fan:OnOff 0.761081 0.87414432   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 unknown unknown unknown 7/21 17:20:00 Sensible 11627.54 10154.97 0.9229 0.87414432 0.761081 21.69 15.25 0.00868109 43860.8 13.46 11.45 0.00800000 33729.7 -999.0 -999.00 -999.00 -999.00 484.706 11142.84 29.36 0.01536168 22.63 0.05391910 7.0845 21.11 0.00817172 21.11 0.00817172 50.0341 6337.85 0.00 12604.76 9834.88 0.83962223 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
409_412 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 409_412 PTAC GUESTROOM409_412 N/A N/A N/A Yes No unknown No 6281.930 6281.930 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 409_412 PTAC SUPPLY FAN Fan:OnOff 0.761081 0.87414432   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 Sensible 6281.93 6281.93 1.0000 0.11182656 0.097363 -5.09 -5.09 0.00370025 4104.7 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 6281.93 -26.20 0.00036134 -26.20 0.05391910 55.3796 21.11 0.00784426 21.11 0.00784426 48.0525 3294.28 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
413 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 413 PTAC GUESTROOM413 N/A N/A N/A Yes Yes unknown No 2526.516 2022.869 0.152627 -999.0 -999.000 -999.0000 1.32395 1.00000 1020.9588 1004.8586 1.1486 413 PTAC SUPPLY FAN Fan:OnOff 0.152627 0.17530046   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 unknown unknown unknown 7/21 17:20:00 Sensible 2335.06 2046.30 0.9242 0.17530046 0.152627 21.84 15.29 0.00867092 43982.9 13.46 11.45 0.00800000 33729.7 -999.0 -999.00 -999.00 -999.00 97.203 2237.86 29.36 0.01536168 22.63 0.01347978 8.8319 21.11 0.00802276 21.11 0.00802276 49.1315 1271.12 0.00 2527.75 1972.28 0.16837742 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
413 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 413 PTAC GUESTROOM413 N/A N/A N/A Yes No unknown No 2291.327 2291.327 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 413 PTAC SUPPLY FAN Fan:OnOff 0.152627 0.17530046   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 Sensible 2291.33 2291.33 1.0000 0.05242633 0.045645 7.14 6.09 0.00568510 21467.3 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 2291.33 -26.20 0.00036134 -26.20 0.01347978 29.5315 21.11 0.00791615 21.11 0.00791615 48.4873 1544.41 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
414 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 414 PTAC GUESTROOM414 N/A N/A N/A Yes Yes unknown No 2204.484 1765.031 0.133173 -999.0 -999.000 -999.0000 1.30074 1.00000 1021.1403 1004.8586 1.1486 414 PTAC SUPPLY FAN Fan:OnOff 0.133173 0.15295645   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 unknown unknown unknown 7/21 11:00:00 Sensible 2058.58 1773.05 0.9338 0.15295645 0.133173 21.89 15.39 0.00876856 44277.6 13.46 11.45 0.00800000 33729.8 -999.0 -999.00 -999.00 -999.00 84.813 1973.76 28.76 0.01536057 22.47 0.01347882 10.1213 21.11 0.00802623 21.11 0.00802623 49.1525 1109.10 0.00 2205.56 1720.89 0.14691583 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
414 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 414 PTAC GUESTROOM414 N/A N/A N/A Yes No unknown No 2202.497 2202.497 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 414 PTAC SUPPLY FAN Fan:OnOff 0.133173 0.15295645   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 Sensible 2202.50 2202.50 1.0000 0.04941273 0.043022 6.29 5.50 0.00554573 20253.0 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 2202.50 -26.20 0.00036134 -26.20 0.01347882 31.3303 21.11 0.00791110 21.11 0.00791110 48.4567 1455.64 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
415_418 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 415_418 PTAC GUESTROOM415_418 N/A N/A N/A Yes Yes unknown No 12455.497 9972.559 0.752437 -999.0 -999.000 -999.0000 1.37465 1.00000 1020.9915 1004.8586 1.1486 415_418 PTAC SUPPLY FAN Fan:OnOff 0.752437 0.86421539   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 unknown unknown unknown 7/21 10:20:00 Sensible 11708.05 10198.68 0.9400 0.86421539 0.752437 21.58 15.21 0.00868851 43765.0 13.46 11.45 0.00800000 33729.7 -999.0 -999.00 -999.00 -999.00 479.201 11228.85 27.70 0.01535861 22.17 0.05391527 7.1654 21.11 0.00817368 21.11 0.00817368 50.0460 6265.86 0.00 12461.59 9723.17 0.83008541 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
415_418 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 415_418 PTAC GUESTROOM415_418 N/A N/A N/A Yes No unknown No 6227.355 6227.355 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 415_418 PTAC SUPPLY FAN Fan:OnOff 0.752437 0.86421539   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 Sensible 6227.35 6227.35 1.0000 0.10998114 0.095756 -5.53 -5.53 0.00362990 3486.6 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 6227.35 -26.20 0.00036134 -26.20 0.05391527 56.3048 21.11 0.00784170 21.11 0.00784170 48.0370 3239.91 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
419 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 419 PTAC GUESTROOM419 N/A N/A N/A Yes Yes unknown No 3377.810 2704.461 0.204053 -999.0 -999.000 -999.0000 1.38272 1.00000 1020.8935 1004.8586 1.1486 419 PTAC SUPPLY FAN Fan:OnOff 0.204053 0.23436681   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 unknown unknown unknown 7/21 10:40:00 Sensible 3150.87 2771.97 0.9328 0.23436681 0.204053 21.58 15.16 0.00863581 43629.2 13.46 11.45 0.00800000 33729.6 -999.0 -999.00 -999.00 -999.00 129.955 3020.92 28.23 0.01535959 22.32 0.01347882 6.6055 21.11 0.00816025 21.11 0.00816025 49.9646 1699.26 0.00 3379.46 2636.83 0.22511109 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
419 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 419 PTAC GUESTROOM419 N/A N/A N/A Yes No unknown No 1708.853 1708.853 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 419 PTAC SUPPLY FAN Fan:OnOff 0.204053 0.23436681   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:10:00 Sensible 1708.85 1708.85 1.0000 0.03265555 0.028432 -1.32 -1.32 0.00430838 9440.0 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1708.85 -26.20 0.00036134 -26.20 0.01347882 47.4075 21.11 0.00786628 21.11 0.00786628 48.1856 961.99 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
420_423 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 420_423 PTAC GUESTROOM420_423 N/A N/A N/A Yes Yes unknown No 11533.777 9234.579 0.696755 -999.0 -999.000 -999.0000 1.35391 1.00000 1021.0918 1004.8586 1.1486 420_423 PTAC SUPPLY FAN Fan:OnOff 0.696755 0.80026253   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 unknown unknown unknown 7/21 10:20:00 Sensible 10862.66 9371.75 0.9418 0.80026253 0.696755 21.62 15.27 0.00874248 43940.7 13.46 11.45 0.00800000 33729.7 -999.0 -999.00 -999.00 -999.00 443.739 10418.92 27.70 0.01535861 22.17 0.05391527 7.7380 21.11 0.00818758 21.11 0.00818758 50.1300 5802.17 0.00 11539.42 9003.65 0.76865821 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
420_423 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 420_423 PTAC GUESTROOM420_423 N/A N/A N/A Yes No unknown No 5819.439 5819.439 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 420_423 PTAC SUPPLY FAN Fan:OnOff 0.696755 0.80026253   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 Sensible 5819.44 5819.44 1.0000 0.09613409 0.083700 -9.36 -9.36 0.00301531 -1921.1 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 5819.44 -26.20 0.00036134 -26.20 0.05391527 64.4149 21.11 0.00781944 21.11 0.00781944 47.9023 2832.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
424 PTAC PTAC COOLING COIL COIL:COOLING:DX:SINGLESPEED Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 424 PTAC GUESTROOM424 N/A N/A N/A Yes Yes unknown No 3300.574 2642.622 0.199388 -999.0 -999.000 -999.0000 1.37684 1.00000 1020.9206 1004.8586 1.1486 424 PTAC SUPPLY FAN Fan:OnOff 0.199388 0.22900790   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 unknown unknown unknown 7/21 10:40:00 Sensible 3080.48 2702.91 0.9333 0.22900790 0.199388 21.59 15.18 0.00865038 43677.5 13.46 11.45 0.00800000 33729.6 -999.0 -999.00 -999.00 -999.00 126.983 2953.50 28.23 0.01535959 22.32 0.01347882 6.7601 21.11 0.00816394 21.11 0.00816394 49.9869 1660.40 0.00 3302.19 2576.54 0.21996382 26.67 19.44 0.01118466 55322.4 15.22 14.39 0.00989121 40310.0
424 PTAC HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER 424 PTAC GUESTROOM424 N/A N/A N/A Yes No unknown No 1991.940 1991.940 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 424 PTAC SUPPLY FAN Fan:OnOff 0.199388 0.22900790   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:20:00 Sensible 1991.94 1991.94 1.0000 0.04226518 0.036799 3.78 3.70 0.00513632 16681.5 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 1991.94 -26.20 0.00036134 -26.20 0.01347882 36.6287 21.11 0.00789627 21.11 0.00789627 48.3670 1245.08 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
FRONTSTAIRSFLR4 UNITHEATER HEATING COIL COIL:HEATING:ELECTRIC Zone Equipment ZONEHVAC:UNITHEATER FRONTSTAIRSFLR4 UNIT HEATER FRONTSTAIRSFLR4 N/A N/A N/A Yes No unknown No 605.478 605.478 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 FRONTSTAIRSFLR4 UNITHEATER FAN Fan:ConstantVolume 0.012078 0.01387214   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:20:00 Sensible 605.48 605.48 1.0000 0.01387214 0.012078 7.20 6.04 0.00562279 21369.0 50.00 23.40 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 605.48 -26.20 0.00036134 -26.20 0.00000000 0.0000 7.19 0.00562279 7.20 0.00562279 85.2495 605.51 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC SAC_FRONTOFFICE FRONTOFFICEFLR1 Non-Coincident CoolingDesignCapacity N/A No No unknown No 7988.380 6236.448 0.403870 -999.0 -999.000 -999.0000 1.00000 1.00000 1022.8611 1004.8586 1.1486 SAC_FRONTOFFICE_ADDAQ SUPPLY FAN Fan:SystemModel 0.403869 0.46386658   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 Sensible 3994.19 3136.83 1.0000 0.30924483 0.269247 25.48 17.40 0.00969422 50307.6 12.00 10.84 0.00800000 32244.1 -999.0 -999.00 -999.00 -999.00 0.000 3994.19 27.97 0.01535910 22.25 0.06335422 23.5302 23.89 0.00864025 23.89 0.00864142 44.6615 3884.91 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC SAC_FRONTOFFICE FRONTOFFICEFLR1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 12264.012 12264.012 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 SAC_FRONTOFFICE_ADDAQ SUPPLY FAN Fan:SystemModel 0.403869 0.46386658   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:20:00 Sensible 12264.01 12264.01 1.0000 0.46386658 0.403869 13.69 10.17 0.00664961 30554.9 40.00 20.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 12264.01 -26.20 0.00036134 -26.20 0.06335422 15.6868 21.11 0.00781956 21.11 0.00781956 47.9032 1943.42 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC SAC_FRONTLOUNGE FRONTLOUNGEFLR1 Non-Coincident CoolingDesignCapacity N/A No No unknown No 23116.920 16925.053 1.026140 -999.0 -999.000 -999.0000 1.00000 1.00000 1024.7267 1004.8586 1.1486 SAC_FRONTLOUNGE_ADDAQ SUPPLY FAN Fan:SystemModel 1.026138 1.17857638   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 Sensible 11558.46 8121.50 1.0000 0.78571938 0.684093 25.93 18.33 0.01069781 53321.6 12.00 10.84 0.00800000 32244.1 -999.0 -999.00 -999.00 -999.00 0.000 11558.46 28.66 0.01536037 22.44 0.23729871 34.6881 23.88 0.00929522 23.88 0.00930632 48.0648 9796.63 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC SAC_FRONTLOUNGE FRONTLOUNGEFLR1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 35327.961 35327.961 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 SAC_FRONTLOUNGE_ADDAQ SUPPLY FAN Fan:SystemModel 1.026138 1.17857638   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 35327.96 35327.96 1.0000 1.17857638 1.026138 10.17 7.97 0.00607116 25517.4 40.00 20.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 35327.96 -26.20 0.00036134 -26.20 0.23729871 23.1254 21.11 0.00778878 21.11 0.00778861 47.7163 2918.31 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC SAC_MEETINGROOM MEETINGROOMFLR1 Non-Coincident CoolingDesignCapacity N/A No No unknown No 11416.480 8024.986 0.461330 -999.0 -999.000 -999.0000 1.00000 1.00000 1026.5786 1004.8586 1.1486 SAC_MEETINGROOM_ADDAQ SUPPLY FAN Fan:SystemModel 0.461335 0.52986861   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 Sensible 5708.24 3630.76 1.0000 0.35324217 0.307553 26.13 19.15 0.01169403 56071.6 12.00 10.84 0.00800000 32244.1 -999.0 -999.00 -999.00 -999.00 0.000 5708.24 28.66 0.01536037 22.44 0.12593618 40.9478 23.88 0.01031738 23.88 0.01034807 53.3726 4384.26 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SAC_MEETINGROOM HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC SAC_MEETINGROOM MEETINGROOMFLR1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 16933.963 16933.963 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 SAC_MEETINGROOM_ADDAQ SUPPLY FAN Fan:SystemModel 0.461335 0.52986861   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 16933.96 16933.96 1.0000 0.52986861 0.461335 8.20 6.69 0.00576461 22740.2 40.00 20.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 16933.96 -26.20 0.00036134 -26.20 0.12593618 27.2982 21.11 0.00779344 21.11 0.00779040 47.7268 1036.21 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SAC_EMPLOYEELOUNGE COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC SAC_EMPLOYEELOUNGE EMPLOYEELOUNGEFLR1 Non-Coincident CoolingDesignCapacity N/A No No unknown No 14670.500 11746.669 0.826090 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.5248 1004.8586 1.1486 SAC_EMPLOYEELOUNGE_ADDAQ SUPPLY FAN Fan:SystemModel 0.826090 0.94881071   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:40:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:50:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 Sensible 7335.25 6315.55 1.0000 0.63254032 0.550727 25.08 16.68 0.00897539 48069.0 12.00 10.84 0.00800000 32244.1 -999.0 -999.00 -999.00 -999.00 0.000 7335.25 27.97 0.01535910 22.25 0.05241448 9.5173 23.88 0.00854291 23.88 0.00854543 44.1928 7937.61 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SAC_EMPLOYEELOUNGE HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC SAC_EMPLOYEELOUNGE EMPLOYEELOUNGEFLR1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 20871.366 20871.366 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 SAC_EMPLOYEELOUNGE_ADDAQ SUPPLY FAN Fan:SystemModel 0.826090 0.94881071   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 01:20:00 Sensible 20871.37 20871.37 1.0000 0.94881071 0.826090 18.11 12.67 0.00733624 36791.1 40.00 20.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 20871.37 -26.20 0.00036134 -26.20 0.05241448 6.3449 21.11 0.00780877 21.11 0.00780791 47.8326 456.56 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SAC_EXERCISECENTER COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC SAC_EXERCISECENTER EXERCISECENTERFLR1 Non-Coincident CoolingDesignCapacity N/A No No unknown No 3848.780 2725.514 0.158200 -999.0 -999.000 -999.0000 1.00000 1.00000 1027.3530 1004.8586 1.1486 SAC_EXERCISECENTER_ADDAQ SUPPLY FAN Fan:SystemModel 0.158196 0.18169681   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 Sensible 1924.39 1159.05 1.0000 0.12113435 0.105467 25.55 19.28 0.01211060 56534.0 12.00 10.84 0.00800000 32244.1 -999.0 -999.00 -999.00 -999.00 0.000 1924.39 25.37 0.01535432 21.52 0.07601186 72.0719 23.88 0.00911048 23.88 0.00916977 47.3608 1453.58 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SAC_EXERCISECENTER HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC SAC_EXERCISECENTER EXERCISECENTERFLR1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 7599.149 7599.149 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 SAC_EXERCISECENTER_ADDAQ SUPPLY FAN Fan:SystemModel 0.158196 0.18169681   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 7599.15 7599.15 1.0000 0.18169681 0.158196 -1.62 -1.62 0.00470786 10131.0 40.00 20.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7599.15 -26.20 0.00036134 -26.20 0.07601186 48.0492 21.11 0.00872794 21.12 0.01444509 87.5371 268.70 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SAC_RESTROOM COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC SAC_RESTROOM RESTROOMFLR1 Non-Coincident CoolingDesignCapacity N/A No No unknown No 1370.970 1097.681 0.082820 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.7493 1004.8586 1.1486 SAC_RESTROOM_ADDAQ SUPPLY FAN Fan:SystemModel 0.082820 0.09512348   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 Sensible 685.49 626.66 1.0000 0.06341567 0.055213 24.84 16.25 0.00855821 46762.1 12.00 10.84 0.00800000 32244.1 -999.0 -999.00 -999.00 -999.00 0.000 685.49 27.33 0.01535793 22.07 0.00000000 0.0000 23.89 0.00855821 23.89 0.00855821 44.2354 799.24 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SAC_RESTROOM HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC SAC_RESTROOM RESTROOMFLR1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 1805.543 1805.543 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1486 SAC_RESTROOM_ADDAQ SUPPLY FAN Fan:SystemModel 0.082820 0.09512348   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:50:00 Sensible 1805.54 1805.54 1.0000 0.09512348 0.082820 21.11 14.24 0.00778387 40985.4 40.00 20.63 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1805.54 -26.20 0.00036134 -26.20 0.00000000 0.0000 21.11 0.00778387 21.11 0.00778387 47.6872 403.18 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
SAC_FRONTLOUNGE_OA_CONTROLLER DifferentialDryBulb 0.00 1.03 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
FRONTLOUNGEFLR1 FRONTLOUNGEFLR1_DCV 0.003540 0.000305 0.000000 0.000000 Sum   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTLOUNGEFLR1 4191.17 5698.17 2187.83
RESTROOMFLR1 3860.50 3910.17 3110.83
MEETINGROOMFLR1 766.67 1467.83 411.17
MECHANICALROOMFLR1 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 2755.00 8234.83 2472.17
GUESTROOM104 1398.00 8136.17 1084.33
GUESTROOM105 743.17 7270.17 33.33
EMPLOYEELOUNGEFLR1 4993.83 1606.67 1451.33
EXERCISECENTERFLR1 2070.50 3957.17 607.50
FRONTOFFICEFLR1 3506.83 5151.67 1715.17
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 2489.17 7578.67 1830.50
GUESTROOM206_208 1999.17 7576.00 1351.00
GUESTROOM209_212 1601.33 7741.67 1088.33
GUESTROOM213 3097.33 8009.00 2726.33
GUESTROOM214 1288.17 7579.17 741.17
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 5129.83 2477.17 936.17
GUESTROOM220_223 1103.83 7735.00 675.50
GUESTROOM224 2072.83 7845.50 1665.83
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 2243.00 7858.33 1783.00
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 2617.83 7776.83 2170.83
GUESTROOM315_318 1040.33 7305.83 142.83
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 1586.50 7891.33 1233.17
GUESTROOM324 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
GUESTROOM401 4933.33 7698.00 4246.33
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 3653.00 7613.50 2886.33
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 2702.50 7445.17 1820.67
GUESTROOM419 2454.00 7496.00 1741.33
GUESTROOM420_423 2682.00 7606.50 2031.50
GUESTROOM424 3553.33 7694.67 3024.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 8329.83 8759.67 6881.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00 0.00
FRONTLOUNGEFLR1 0.00 0.00 0.00 0.00
RESTROOMFLR1 0.00 0.00 0.00 0.00
MEETINGROOMFLR1 0.17 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00 0.00
GUESTROOM103 1.33 68.33 1.33 68.33
GUESTROOM104 0.00 87.67 0.00 87.67
GUESTROOM105 0.00 95.00 0.00 95.00
EMPLOYEELOUNGEFLR1 0.00 15.83 0.00 15.83
EXERCISECENTERFLR1 0.17 0.00 0.00 0.00
FRONTOFFICEFLR1 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00 0.00
GUESTROOM201 0.00 0.00 0.00 0.00
GUESTROOM202_205 1.17 73.17 1.17 73.17
GUESTROOM206_208 0.17 73.50 0.17 73.50
GUESTROOM209_212 0.00 73.67 0.00 73.67
GUESTROOM213 1.50 70.33 1.50 70.33
GUESTROOM214 0.00 91.83 0.00 91.83
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 180.33 0.00 180.33
GUESTROOM220_223 0.00 92.83 0.00 92.83
GUESTROOM224 1.17 88.50 1.17 88.50
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.83 0.00 0.00
GUESTROOM301 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00 0.00
GUESTROOM309_312 0.67 73.17 0.67 73.17
GUESTROOM313 0.00 0.00 0.00 0.00
GUESTROOM314 0.50 90.67 0.50 90.67
GUESTROOM315_318 0.00 93.17 0.00 93.17
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 0.33 92.67 0.33 92.67
GUESTROOM324 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 1.67 0.00 0.00 0.00
CORRIDORFLR4 2.00 5.17 0.00 0.00
GUESTROOM401 11.00 69.33 11.00 69.33
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00
GUESTROOM409_412 5.50 73.00 5.50 73.00
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00
GUESTROOM415_418 2.17 93.17 2.17 93.17
GUESTROOM419 0.83 92.50 0.83 92.50
GUESTROOM420_423 3.67 93.33 3.67 93.33
GUESTROOM424 2.83 89.50 2.83 89.50
FRONTSTAIRSFLR4 0.00 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 15.83 339.67 13.00 334.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
REARSTAIRSFLR1   1.08 67.30        
CORRIDORFLR1   8.10 504.62        
FRONTLOUNGEFLR1 14.76 53.00 546.70 1.224 0.014 0.000 0.000
RESTROOMFLR1 0.49 1.75 109.34 0.000 0.010 0.000 0.000
MEETINGROOMFLR1 15.57 43.00 269.14 1.419 0.011 0.000 0.000
MECHANICALROOMFLR1   0.53 109.34        
GUESTROOM101   1.50 109.34        
GUESTROOM102   1.50 109.34        
GUESTROOM103 0.96 1.50 109.34 0.341 0.010 0.000 0.006
GUESTROOM104 0.96 1.50 109.33 0.341 0.010 0.000 0.007
GUESTROOM105 0.96 1.50 109.33 0.346 0.010 0.000 0.004
EMPLOYEELOUNGEFLR1 3.58 18.00 109.33 1.758 0.011 0.000 0.000
EXERCISECENTERFLR1 6.34 7.00 109.33 2.539 0.010 0.000 0.000
FRONTOFFICEFLR1 4.38 10.00 437.33 0.530 0.010 0.000 0.000
FRONTSTAIRSFLR1   1.08 67.28        
REARSTAIRSFLR2   1.08 55.06        
CORRIDORFLR2   6.75 344.05        
GUESTROOM201   1.50 89.46        
GUESTROOM202_205 3.83 6.00 357.84 0.419 0.013 0.000 0.001
GUESTROOM206_208 2.87 4.50 289.02 0.411 0.013 0.000 0.002
GUESTROOM209_212 3.83 6.00 357.84 0.419 0.013 0.000 0.002
GUESTROOM213 0.96 1.50 89.46 0.418 0.013 0.000 0.008
GUESTROOM214 0.96 1.50 89.45 0.420 0.013 0.000 0.007
GUESTROOM215_218   6.00 357.81        
GUESTROOM219 0.96 1.50 89.45 0.433 0.013 0.000 0.002
GUESTROOM220_223 3.83 6.00 357.81 0.419 0.013 0.000 0.002
GUESTROOM224 0.96 1.50 89.45 0.418 0.013 0.000 0.009
FRONTSTAIRSFLR2   1.08 55.05        
REARSTAIRSFLR3   1.08 55.06        
CORRIDORFLR3   6.75 344.05        
GUESTROOM301   1.50 89.46        
GUESTROOM302_305   6.00 357.84        
GUESTROOM306_308   4.50 289.02        
GUESTROOM309_312 3.83 6.00 357.84 0.418 0.014 0.000 0.002
GUESTROOM313   1.50 89.46        
GUESTROOM314 0.96 1.50 89.45 0.419 0.014 0.000 0.009
GUESTROOM315_318 3.83 6.00 357.81 0.423 0.014 0.000 0.002
GUESTROOM319   1.50 89.45        
GUESTROOM320_323 3.83 6.00 357.81 0.418 0.014 0.000 0.002
GUESTROOM324   1.50 89.45        
FRONTSTAIRSFLR3   1.08 55.05        
REARSTAIRSFLR4   1.08 55.06        
CORRIDORFLR4   6.75 344.05        
GUESTROOM401 0.96 1.50 89.46 0.428 0.046 0.000 0.007
GUESTROOM402_405   6.00 357.84        
GUESTROOM406_408   4.50 289.02        
GUESTROOM409_412 3.83 6.00 357.84 0.420 0.015 0.000 0.001
GUESTROOM413   1.50 89.46        
GUESTROOM414   1.50 89.45        
GUESTROOM415_418 3.83 6.00 357.81 0.421 0.015 0.000 0.002
GUESTROOM419 0.96 1.50 89.45 0.421 0.015 0.000 0.008
GUESTROOM420_423 3.83 6.00 357.81 0.420 0.015 0.000 0.002
GUESTROOM424 0.96 1.50 89.45 0.422 0.015 0.000 0.009
FRONTSTAIRSFLR4   1.08 55.05        
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
REARSTAIRSFLR1   1.08 67.30        
CORRIDORFLR1   8.10 504.62        
FRONTLOUNGEFLR1 14.76 53.00 546.70 0.443 0.000 0.000 0.000
RESTROOMFLR1 0.49 1.75 109.34 0.000 0.000 0.000 0.000
MEETINGROOMFLR1 15.57 43.00 269.14 0.000 0.000 0.000 0.000
MECHANICALROOMFLR1   0.53 109.34        
GUESTROOM101   1.50 109.34        
GUESTROOM102   1.50 109.34        
GUESTROOM103 0.96 1.50 109.34 0.000 0.000 0.000 0.000
GUESTROOM104 0.96 1.50 109.33 0.000 0.000 0.000 0.000
GUESTROOM105 0.96 1.50 109.33 0.000 0.000 0.000 0.000
EMPLOYEELOUNGEFLR1 3.58 18.00 109.33 1.696 0.000 0.000 0.000
EXERCISECENTERFLR1 6.34 7.00 109.33 2.460 0.000 0.000 0.000
FRONTOFFICEFLR1 4.38 10.00 437.33 0.512 0.000 0.000 0.000
FRONTSTAIRSFLR1   1.08 67.28        
REARSTAIRSFLR2   1.08 55.06        
CORRIDORFLR2   6.75 344.05        
GUESTROOM201   1.50 89.46        
GUESTROOM202_205 3.83 6.00 357.84 0.000 0.000 0.000 0.000
GUESTROOM206_208 2.87 4.50 289.02 0.000 0.000 0.000 0.000
GUESTROOM209_212 3.83 6.00 357.84 0.000 0.000 0.000 0.000
GUESTROOM213 0.96 1.50 89.46 0.000 0.000 0.000 0.000
GUESTROOM214 0.96 1.50 89.45 0.000 0.000 0.000 0.000
GUESTROOM215_218   6.00 357.81        
GUESTROOM219 0.96 1.50 89.45 0.000 0.000 0.000 0.000
GUESTROOM220_223 3.83 6.00 357.81 0.000 0.000 0.000 0.000
GUESTROOM224 0.96 1.50 89.45 0.000 0.000 0.000 0.000
FRONTSTAIRSFLR2   1.08 55.05        
REARSTAIRSFLR3   1.08 55.06        
CORRIDORFLR3   6.75 344.05        
GUESTROOM301   1.50 89.46        
GUESTROOM302_305   6.00 357.84        
GUESTROOM306_308   4.50 289.02        
GUESTROOM309_312 3.83 6.00 357.84 0.000 0.000 0.000 0.000
GUESTROOM313   1.50 89.46        
GUESTROOM314 0.96 1.50 89.45 0.000 0.000 0.000 0.000
GUESTROOM315_318 3.83 6.00 357.81 0.000 0.000 0.000 0.000
GUESTROOM319   1.50 89.45        
GUESTROOM320_323 3.83 6.00 357.81 0.000 0.000 0.000 0.000
GUESTROOM324   1.50 89.45        
FRONTSTAIRSFLR3   1.08 55.05        
REARSTAIRSFLR4   1.08 55.06        
CORRIDORFLR4   6.75 344.05        
GUESTROOM401 0.96 1.50 89.46 0.000 0.000 0.000 0.000
GUESTROOM402_405   6.00 357.84        
GUESTROOM406_408   4.50 289.02        
GUESTROOM409_412 3.83 6.00 357.84 0.000 0.000 0.000 0.000
GUESTROOM413   1.50 89.46        
GUESTROOM414   1.50 89.45        
GUESTROOM415_418 3.83 6.00 357.81 0.000 0.000 0.000 0.000
GUESTROOM419 0.96 1.50 89.45 0.000 0.000 0.000 0.000
GUESTROOM420_423 3.83 6.00 357.81 0.000 0.000 0.000 0.000
GUESTROOM424 0.96 1.50 89.45 0.000 0.000 0.000 0.000
FRONTSTAIRSFLR4   1.08 55.05        
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
REARSTAIRSFLR1     1.08 67.30 20.07   0.006
CORRIDORFLR1     8.10 504.62 150.51   0.046
FRONTLOUNGEFLR1 SAC_FRONTLOUNGE 14.76 53.00 546.70 163.06 0.2373 0.050
RESTROOMFLR1 SAC_RESTROOM 0.49 1.75 109.34 32.61 0.0000 0.000
MEETINGROOMFLR1 SAC_MEETINGROOM 15.57 43.00 269.14 80.27 0.1259 0.024
MECHANICALROOMFLR1     0.53 109.34 32.61   0.000
GUESTROOM101     1.50 109.34 32.61   0.013
GUESTROOM102     1.50 109.34 32.61   0.013
GUESTROOM103   0.96 1.50 109.34 32.61   0.013
GUESTROOM104   0.96 1.50 109.33 32.61   0.013
GUESTROOM105   0.96 1.50 109.33 32.61   0.013
EMPLOYEELOUNGEFLR1 SAC_EMPLOYEELOUNGE 3.58 18.00 109.33 32.61 0.0524 0.010
EXERCISECENTERFLR1 SAC_EXERCISECENTER 6.34 7.00 109.33 32.61 0.0760 0.010
FRONTOFFICEFLR1 SAC_FRONTOFFICE 4.38 10.00 437.33 130.44 0.0634 0.040
FRONTSTAIRSFLR1     1.08 67.28 20.07   0.006
REARSTAIRSFLR2     1.08 55.06 20.07   0.006
CORRIDORFLR2     6.75 344.05 125.42   0.038
GUESTROOM201     1.50 89.46 32.61   0.013
GUESTROOM202_205   3.83 6.00 357.84 130.45   0.054
GUESTROOM206_208   2.87 4.50 289.02 105.36   0.043
GUESTROOM209_212   3.83 6.00 357.84 130.45   0.054
GUESTROOM213   0.96 1.50 89.46 32.61   0.013
GUESTROOM214   0.96 1.50 89.45 32.61   0.013
GUESTROOM215_218     6.00 357.81 130.44   0.054
GUESTROOM219   0.96 1.50 89.45 32.61   0.013
GUESTROOM220_223   3.83 6.00 357.81 130.44   0.054
GUESTROOM224   0.96 1.50 89.45 32.61   0.013
FRONTSTAIRSFLR2     1.08 55.05 20.07   0.006
REARSTAIRSFLR3     1.08 55.06 20.07   0.006
CORRIDORFLR3     6.75 344.05 125.42   0.038
GUESTROOM301     1.50 89.46 32.61   0.013
GUESTROOM302_305     6.00 357.84 130.45   0.054
GUESTROOM306_308     4.50 289.02 105.36   0.043
GUESTROOM309_312   3.83 6.00 357.84 130.45   0.054
GUESTROOM313     1.50 89.46 32.61   0.013
GUESTROOM314   0.96 1.50 89.45 32.61   0.013
GUESTROOM315_318   3.83 6.00 357.81 130.44   0.054
GUESTROOM319     1.50 89.45 32.61   0.013
GUESTROOM320_323   3.83 6.00 357.81 130.44   0.054
GUESTROOM324     1.50 89.45 32.61   0.013
FRONTSTAIRSFLR3     1.08 55.05 20.07   0.006
REARSTAIRSFLR4     1.08 55.06 20.07   0.006
CORRIDORFLR4     6.75 344.05 125.42   0.038
GUESTROOM401   0.96 1.50 89.46 32.61   0.013
GUESTROOM402_405     6.00 357.84 130.45   0.054
GUESTROOM406_408     4.50 289.02 105.36   0.043
GUESTROOM409_412   3.83 6.00 357.84 130.45   0.054
GUESTROOM413     1.50 89.46 32.61   0.013
GUESTROOM414     1.50 89.45 32.61   0.013
GUESTROOM415_418   3.83 6.00 357.81 130.44   0.054
GUESTROOM419   0.96 1.50 89.45 32.61   0.013
GUESTROOM420_423   3.83 6.00 357.81 130.44   0.054
GUESTROOM424   0.96 1.50 89.45 32.61   0.013
FRONTSTAIRSFLR4     1.08 55.05 20.07   0.006
Total Facility   92.95 285.77 10741.65 3725.09 0.5550 1.388


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
REARSTAIRSFLR1 0.00 0.00 0.00 102926.82 102926.82 192934.21 8760.00 0.00 0.00 0.00
CORRIDORFLR1 1446687.50 0.00 1446687.50 5122762.42 6569449.91 1446687.50 0.00 8760.00 0.00 8760.00
FRONTLOUNGEFLR1 5744365.57 0.00 5744365.57 67635.33 5812000.90 3116594.90 0.00 5090.05 3669.95 0.00
RESTROOMFLR1 0.00 0.00 0.00 9556.97 9556.97 0.00 0.00 0.00 0.00 0.00
MEETINGROOMFLR1 1743714.03 0.00 1743714.03 23524.84 1767238.87 996897.75 4971.28 8.94 3779.78 4717.29
MECHANICALROOMFLR1 0.00 0.00 0.00 9556.97 9556.97 0.00 0.00 0.00 0.00 0.00
GUESTROOM101 17719.75 0.00 17719.75 9556.97 27276.72 425098.19 8395.00 365.00 0.00 377.79
GUESTROOM102 17712.42 0.00 17712.42 9556.97 27269.39 425098.19 8395.00 365.00 0.00 365.00
GUESTROOM103 321883.05 5715.46 327598.52 9556.97 337155.48 425098.19 2187.59 6052.96 519.45 0.00
GUESTROOM104 322395.69 6425.32 328821.01 9556.97 338377.97 425068.03 2187.42 6031.64 540.94 0.00
GUESTROOM105 326627.18 4009.19 330636.38 9556.97 340193.34 425068.03 2186.98 6230.66 342.36 0.00
EMPLOYEELOUNGEFLR1 1652943.01 0.00 1652943.01 9556.97 1662499.98 455688.44 0.00 0.00 8760.00 3285.00
EXERCISECENTERFLR1 2397109.90 0.00 2397109.90 9556.97 2406666.86 1572325.09 0.00 4745.00 4015.00 2920.00
FRONTOFFICEFLR1 1997938.76 0.00 1997938.76 38227.87 2036166.63 1544345.40 0.00 1750.00 7010.00 730.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 102921.19 102921.19 192888.02 8760.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 105779.76 105779.76 192934.21 8760.00 0.00 0.00 0.00
CORRIDORFLR2 1205560.37 0.00 1205560.37 66486.49 1272046.86 1205560.37 0.00 8760.00 0.00 8760.00
GUESTROOM201 19696.75 0.00 19696.75 30222.58 49919.33 425098.19 8395.00 365.00 0.00 998.37
GUESTROOM202_205 1296424.46 4209.53 1300633.99 39287.47 1339921.46 1700392.76 2186.68 6237.76 335.56 0.00
GUESTROOM206_208 1026877.60 4191.35 1031068.95 31732.19 1062801.14 1347630.58 2186.80 6235.61 337.58 0.00
GUESTROOM209_212 1294423.87 4666.18 1299090.05 39287.47 1338377.52 1700392.76 2186.65 6200.31 373.05 0.00
GUESTROOM213 322854.33 5920.05 328774.37 9821.87 338596.24 425098.19 2187.16 6130.63 442.21 0.00
GUESTROOM214 324887.46 5680.48 330567.94 9821.87 340389.81 425068.03 2186.98 6178.97 394.06 0.00
GUESTROOM215_218 168557.17 0.00 168557.17 39287.47 207844.64 1700272.11 8394.98 365.02 0.00 8544.50
GUESTROOM219 334323.09 1578.17 335901.26 9821.87 345723.13 425068.03 2161.80 6471.41 126.79 0.00
GUESTROOM220_223 1295296.93 6400.18 1301697.11 39287.47 1340984.59 1700272.11 2186.88 6120.70 452.42 0.00
GUESTROOM224 323300.56 6710.57 330011.13 9821.87 339833.00 425068.03 2187.15 6107.28 465.56 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 105773.97 105773.97 192888.02 8760.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 116996.81 116996.81 192934.21 8760.00 0.00 0.00 0.00
CORRIDORFLR3 1205560.37 0.00 1205560.37 73536.83 1279097.19 1205560.37 0.00 8760.00 0.00 8760.00
GUESTROOM301 26220.61 0.00 26220.61 33427.43 59648.04 425098.19 8395.00 365.00 0.00 1874.42
GUESTROOM302_305 74516.45 0.00 74516.45 43453.58 117970.03 1700392.76 8395.00 365.00 0.00 759.64
GUESTROOM306_308 57822.83 0.00 57822.83 35097.12 92919.95 1347630.58 8395.00 365.00 0.00 620.35
GUESTROOM309_312 1291806.49 5705.53 1297512.02 43453.58 1340965.60 1700392.76 2186.58 6173.27 400.15 0.00
GUESTROOM313 19561.92 0.00 19561.92 10863.40 30425.32 425098.19 8395.00 365.00 0.00 919.37
GUESTROOM314 324143.49 6973.95 331117.44 10863.40 341980.83 425068.03 2187.00 6134.01 438.99 0.00
GUESTROOM315_318 1307434.90 4728.34 1312163.24 43453.58 1355616.82 1700272.11 2186.47 6252.35 321.18 0.00
GUESTROOM319 18255.54 0.00 18255.54 10863.40 29118.93 425068.03 8395.00 365.00 0.00 1096.63
GUESTROOM320_323 1293078.24 7587.74 1300665.99 43453.58 1344119.57 1700272.11 2186.81 6086.31 486.88 0.00
GUESTROOM324 17711.17 0.00 17711.17 10863.40 28574.56 425068.03 8395.00 365.00 0.00 365.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 116990.41 116990.41 192888.02 8760.00 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00 125341.61 125341.61 192934.21 8760.00 0.00 0.00 0.00
CORRIDORFLR4 1205560.37 0.00 1205560.37 78781.84 1284342.21 1205560.37 0.00 8760.00 0.00 8760.00
GUESTROOM401 330559.82 5124.67 335684.49 35811.64 371496.14 425098.19 2186.87 6236.17 336.96 0.00
GUESTROOM402_405 127492.15 0.00 127492.15 46552.91 174045.05 1700392.76 8395.00 365.00 0.00 2808.05
GUESTROOM406_408 94959.73 0.00 94959.73 37600.42 132560.15 1347630.58 8395.00 365.00 0.00 2543.98
GUESTROOM409_412 1299226.78 4498.91 1303725.69 46552.91 1350278.60 1700392.76 2186.34 6251.11 322.55 0.00
GUESTROOM413 31092.89 0.00 31092.89 11638.23 42731.11 425098.19 8395.00 365.00 0.00 2749.02
GUESTROOM414 23540.54 0.00 23540.54 11638.23 35178.76 425068.03 8395.00 365.00 0.00 1670.08
GUESTROOM415_418 1301904.54 6030.57 1307935.11 46552.91 1354488.01 1700272.11 2186.35 6190.04 383.60 0.00
GUESTROOM419 325544.25 6268.47 331812.72 11638.23 343450.95 425068.03 2186.80 6187.32 385.88 0.00
GUESTROOM420_423 1298422.28 6696.48 1305118.76 46552.91 1351671.66 1700272.11 2186.49 6152.73 420.78 0.00
GUESTROOM424 325856.47 7146.44 333002.91 11638.23 344641.14 425068.03 2187.02 6142.65 430.33 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00 125334.75 125334.75 192888.02 8760.00 0.00 0.00 0.00
Total Facility 35601571.26 116267.58 35717838.84 7309394.84 43027233.68 47241022.05 8760.00 8760.00 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
FRONTLOUNGEFLR1 0.1822 0.0000 0.1822 0.0021 0.1843 0.0988 0.00 5090.05 3669.95
RESTROOMFLR1 0.0000 0.0000 0.0000 0.0003 0.0003 0.0000 0.00 0.00 0.00
MEETINGROOMFLR1 0.1045 0.0000 0.1045 0.0008 0.1053 0.0546 365.00 0.00 1710.00
GUESTROOM103 0.0102 0.0002 0.0104 0.0003 0.0107 0.0135 2187.59 6052.96 519.45
GUESTROOM104 0.0102 0.0002 0.0104 0.0003 0.0107 0.0135 2187.42 6031.64 540.94
GUESTROOM105 0.0104 0.0001 0.0105 0.0003 0.0108 0.0135 2186.98 6230.66 342.36
EMPLOYEELOUNGEFLR1 0.0524 0.0000 0.0524 0.0003 0.0527 0.0172 0.00 0.00 5475.00
EXERCISECENTERFLR1 0.0760 0.0000 0.0760 0.0003 0.0763 0.0698 0.00 4745.00 1095.00
FRONTOFFICEFLR1 0.0634 0.0000 0.0634 0.0012 0.0646 0.0498 0.00 1750.00 6280.00
GUESTROOM202_205 0.0411 0.0001 0.0412 0.0012 0.0425 0.0539 2186.68 6237.76 335.56
GUESTROOM206_208 0.0326 0.0001 0.0327 0.0010 0.0337 0.0427 2186.80 6235.61 337.58
GUESTROOM209_212 0.0410 0.0001 0.0412 0.0012 0.0424 0.0539 2186.65 6200.31 373.05
GUESTROOM213 0.0102 0.0002 0.0104 0.0003 0.0107 0.0135 2187.16 6130.63 442.21
GUESTROOM214 0.0103 0.0002 0.0105 0.0003 0.0108 0.0135 2186.98 6178.97 394.06
GUESTROOM219 0.0106 0.0001 0.0107 0.0003 0.0110 0.0135 2161.80 6471.41 126.79
GUESTROOM220_223 0.0411 0.0002 0.0413 0.0012 0.0425 0.0539 2186.88 6120.70 452.42
GUESTROOM224 0.0103 0.0002 0.0105 0.0003 0.0108 0.0135 2187.15 6107.28 465.56
GUESTROOM309_312 0.0410 0.0002 0.0411 0.0014 0.0425 0.0539 2186.58 6173.27 400.15
GUESTROOM314 0.0103 0.0002 0.0105 0.0003 0.0108 0.0135 2187.00 6134.01 438.99
GUESTROOM315_318 0.0415 0.0001 0.0416 0.0014 0.0430 0.0539 2186.47 6252.35 321.18
GUESTROOM320_323 0.0410 0.0002 0.0412 0.0014 0.0426 0.0539 2186.81 6086.31 486.88
GUESTROOM401 0.0105 0.0002 0.0106 0.0011 0.0118 0.0135 2186.87 6236.17 336.96
GUESTROOM409_412 0.0412 0.0001 0.0413 0.0015 0.0428 0.0539 2186.34 6251.11 322.55
GUESTROOM415_418 0.0413 0.0002 0.0415 0.0015 0.0430 0.0539 2186.35 6190.04 383.60
GUESTROOM419 0.0103 0.0002 0.0105 0.0004 0.0109 0.0135 2186.80 6187.32 385.88
GUESTROOM420_423 0.0412 0.0002 0.0414 0.0015 0.0429 0.0539 2186.49 6152.73 420.78
GUESTROOM424 0.0103 0.0002 0.0106 0.0004 0.0109 0.0135 2187.02 6142.65 430.33
Total Facility 0.9949 0.0037 0.9986 0.0227 1.0214 0.9665 8760.00 8760.00 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
SAC_FRONTOFFICE 2635641.84 0.00 2635641.84 1544345.40 0.00 0.00 8760.00 730.00
SAC_FRONTLOUNGE 7577707.74 0.00 7577707.74 3116594.90 0.00 0.00 8760.00 0.00
SAC_MEETINGROOM 2300273.53 0.00 2300273.53 996897.75 4817.20 11.58 3931.22 4470.10
SAC_EMPLOYEELOUNGE 2180530.18 0.00 2180530.18 455688.44 0.00 0.00 8760.00 3285.00
SAC_EXERCISECENTER 3162220.61 0.00 3162220.61 1572325.09 0.00 0.00 8760.00 2920.00
SAC_RESTROOM 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
SAC_FRONTOFFICE 0.0836 0.0000 0.0836 0.0498 0.00 0.00 8030.00
SAC_FRONTLOUNGE 0.2403 0.0000 0.2403 0.0988 0.00 0.00 8760.00
SAC_MEETINGROOM 0.1379 0.0000 0.1379 0.0546 364.87 0.13 1710.00
SAC_EMPLOYEELOUNGE 0.0691 0.0000 0.0691 0.0172 0.00 0.00 5475.00
SAC_EXERCISECENTER 0.1003 0.0000 0.1003 0.0698 0.00 0.00 5840.00
SAC_RESTROOM 0.0000 0.0000 0.0000 0.0000 0.00 0.00 0.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
SAC_FRONTOFFICE 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SAC_FRONTLOUNGE 0.00 1159.20 2658.78 0.00 0.00 0.00 4942.02 0.00 0.00 0.00
SAC_MEETINGROOM 0.00 6369.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SAC_EMPLOYEELOUNGE 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SAC_EXERCISECENTER 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
SAC_RESTROOM 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
SAC_FRONTOFFICE 0.0000 0.0836 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
SAC_FRONTLOUNGE 0.0000 0.6255 0.2830 0.0000 0.0000 0.0000 0.1270 0.0000 0.0000 0.0000
SAC_MEETINGROOM 0.0000 0.1507 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
SAC_EMPLOYEELOUNGE 0.0000 0.0691 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
SAC_EXERCISECENTER 0.0000 0.1003 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
SAC_RESTROOM 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Surfaces by Class

Total Outdoors
Wall 338 92
Floor 75 19
Roof 72 16
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 103 103
Door 3 3
Glass Door 0 0
Shading 2 2
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 6
Conditioned Zones 54
Unconditioned Zones 13
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 2323
Defaulted Fields 2697
Fields with Defaults 8573
Autosized Fields 750
Autosizable Fields 989
Autocalculated Fields 903
Autocalculatable Fields 1495



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 1515.69 26699.17 26-APR-10:10 206318.75 02-FEB-07:10
Electricity:Building 670.90 9206.41 01-JAN-02:10 44617.09 23-DEC-08:10
Electricity:Zone:CORRIDORFLR1 15.71 498.16 01-JAN-00:10 498.16 01-JAN-00:10
Electricity:SpaceType:GENERAL 670.90 9206.41 01-JAN-02:10 44617.09 23-DEC-08:10
InteriorLights:Electricity 199.44 3637.03 01-JAN-02:10 9486.08 23-DEC-08:10
InteriorLights:Electricity:Zone:CORRIDORFLR1 15.71 498.16 01-JAN-00:10 498.16 01-JAN-00:10
InteriorLights:Electricity:SpaceType:GENERAL 199.44 3637.03 01-JAN-02:10 9486.08 23-DEC-08:10
LightsWired:InteriorLights:Electricity 199.44 3637.03 01-JAN-02:10 9486.08 23-DEC-08:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDORFLR1 15.71 498.16 01-JAN-00:10 498.16 01-JAN-00:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 199.44 3637.03 01-JAN-02:10 9486.08 23-DEC-08:10
Electricity:Zone:CORRIDORFLR2 13.09 415.13 01-JAN-00:10 415.13 01-JAN-00:10
InteriorLights:Electricity:Zone:CORRIDORFLR2 13.09 415.13 01-JAN-00:10 415.13 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDORFLR2 13.09 415.13 01-JAN-00:10 415.13 01-JAN-00:10
Electricity:Zone:CORRIDORFLR3 13.09 415.13 01-JAN-00:10 415.13 01-JAN-00:10
InteriorLights:Electricity:Zone:CORRIDORFLR3 13.09 415.13 01-JAN-00:10 415.13 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDORFLR3 13.09 415.13 01-JAN-00:10 415.13 01-JAN-00:10
Electricity:Zone:CORRIDORFLR4 13.09 415.13 01-JAN-00:10 415.13 01-JAN-00:10
InteriorLights:Electricity:Zone:CORRIDORFLR4 13.09 415.13 01-JAN-00:10 415.13 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDORFLR4 13.09 415.13 01-JAN-00:10 415.13 01-JAN-00:10
Electricity:Zone:ELEVATORCOREFLR1 131.94 1929.17 01-JAN-00:10 8074.65 01-JAN-07:10
InteriorLights:Electricity:Zone:ELEVATORCOREFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:ELEVATORCOREFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:ELEVATORCOREFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:ELEVATORCOREFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:ELEVATORCOREFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:ELEVATORCOREFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:ELEVATORCOREFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:ELEVATORCOREFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:ELEVATORCOREFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:ELEVATORCOREFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:ELEVATORCOREFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:EMPLOYEELOUNGEFLR1 12.85 55.76 01-JAN-00:10 879.34 01-JAN-08:10
InteriorLights:Electricity:Zone:EMPLOYEELOUNGEFLR1 3.28 0.00 01-JAN-00:10 207.09 01-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:EMPLOYEELOUNGEFLR1 3.28 0.00 01-JAN-00:10 207.09 01-JAN-08:10
Electricity:Zone:EXERCISECENTERFLR1 15.01 0.00 01-JAN-00:10 922.10 01-JAN-07:10
InteriorLights:Electricity:Zone:EXERCISECENTERFLR1 6.64 0.00 01-JAN-00:10 315.90 01-JAN-07:10
LightsWired:InteriorLights:Electricity:Zone:EXERCISECENTERFLR1 6.64 0.00 01-JAN-00:10 315.90 01-JAN-07:10
Electricity:Zone:FRONTLOUNGEFLR1 62.63 892.34 01-JAN-00:10 5602.24 23-DEC-08:10
InteriorLights:Electricity:Zone:FRONTLOUNGEFLR1 12.27 0.00 01-JAN-00:10 1474.30 01-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:FRONTLOUNGEFLR1 12.27 0.00 01-JAN-00:10 1474.30 01-JAN-16:40
Electricity:Zone:FRONTOFFICEFLR1 40.78 794.71 24-MAY-06:00 2272.99 03-JAN-16:40
InteriorLights:Electricity:Zone:FRONTOFFICEFLR1 11.34 162.41 24-MAY-06:00 609.04 01-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:FRONTOFFICEFLR1 11.34 162.41 24-MAY-06:00 609.04 01-JAN-16:40
Electricity:Zone:FRONTSTAIRSFLR1 3.34 105.84 01-JAN-00:10 105.84 01-JAN-00:10
InteriorLights:Electricity:Zone:FRONTSTAIRSFLR1 3.34 105.84 01-JAN-00:10 105.84 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:FRONTSTAIRSFLR1 3.34 105.84 01-JAN-00:10 105.84 01-JAN-00:10
Electricity:Zone:FRONTSTAIRSFLR2 3.34 105.84 01-JAN-00:10 105.84 01-JAN-00:10
InteriorLights:Electricity:Zone:FRONTSTAIRSFLR2 3.34 105.84 01-JAN-00:10 105.84 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:FRONTSTAIRSFLR2 3.34 105.84 01-JAN-00:10 105.84 01-JAN-00:10
Electricity:Zone:FRONTSTAIRSFLR3 3.34 105.84 01-JAN-00:10 105.84 01-JAN-00:10
InteriorLights:Electricity:Zone:FRONTSTAIRSFLR3 3.34 105.84 01-JAN-00:10 105.84 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:FRONTSTAIRSFLR3 3.34 105.84 01-JAN-00:10 105.84 01-JAN-00:10
Electricity:Zone:FRONTSTAIRSFLR4 3.34 105.84 01-JAN-00:10 105.84 01-JAN-00:10
InteriorLights:Electricity:Zone:FRONTSTAIRSFLR4 3.34 105.84 01-JAN-00:10 105.84 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:FRONTSTAIRSFLR4 3.34 105.84 01-JAN-00:10 105.84 01-JAN-00:10
Electricity:Zone:FRONTSTORAGEFLR1 0.18 2.24 01-JAN-00:10 8.98 01-JAN-08:10
InteriorLights:Electricity:Zone:FRONTSTORAGEFLR1 0.18 2.24 01-JAN-00:10 8.98 01-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:FRONTSTORAGEFLR1 0.18 2.24 01-JAN-00:10 8.98 01-JAN-08:10
Electricity:Zone:FRONTSTORAGEFLR2 0.18 2.24 01-JAN-00:10 8.98 01-JAN-08:10
InteriorLights:Electricity:Zone:FRONTSTORAGEFLR2 0.18 2.24 01-JAN-00:10 8.98 01-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:FRONTSTORAGEFLR2 0.18 2.24 01-JAN-00:10 8.98 01-JAN-08:10
Electricity:Zone:FRONTSTORAGEFLR3 0.18 2.24 01-JAN-00:10 8.98 01-JAN-08:10
InteriorLights:Electricity:Zone:FRONTSTORAGEFLR3 0.18 2.24 01-JAN-00:10 8.98 01-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:FRONTSTORAGEFLR3 0.18 2.24 01-JAN-00:10 8.98 01-JAN-08:10
Electricity:Zone:FRONTSTORAGEFLR4 0.18 2.24 01-JAN-00:10 8.98 01-JAN-08:10
InteriorLights:Electricity:Zone:FRONTSTORAGEFLR4 0.18 2.24 01-JAN-00:10 8.98 01-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:FRONTSTORAGEFLR4 0.18 2.24 01-JAN-00:10 8.98 01-JAN-08:10
Electricity:Zone:GUESTROOM101 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:GUESTROOM101 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM101 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:GUESTROOM102 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:GUESTROOM102 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM102 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:GUESTROOM103 5.49 53.58 01-JAN-02:10 404.65 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM103 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM103 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
Electricity:Zone:GUESTROOM104 5.49 53.58 01-JAN-02:10 404.62 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM104 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM104 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
Electricity:Zone:GUESTROOM105 5.49 53.58 01-JAN-02:10 404.62 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM105 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM105 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
Electricity:Zone:GUESTROOM201 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:GUESTROOM201 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM201 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:GUESTROOM202_205 21.98 214.32 01-JAN-02:10 1618.58 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM202_205 5.16 43.66 01-JAN-02:10 396.93 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM202_205 5.16 43.66 01-JAN-02:10 396.93 01-JAN-19:10
Electricity:Zone:GUESTROOM206_208 17.75 173.10 01-JAN-02:10 1307.32 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM206_208 4.17 35.26 01-JAN-02:10 320.60 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM206_208 4.17 35.26 01-JAN-02:10 320.60 01-JAN-19:10
Electricity:Zone:GUESTROOM209_212 21.98 214.32 01-JAN-02:10 1618.58 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM209_212 5.16 43.66 01-JAN-02:10 396.93 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM209_212 5.16 43.66 01-JAN-02:10 396.93 01-JAN-19:10
Electricity:Zone:GUESTROOM213 5.49 53.58 01-JAN-02:10 404.65 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM213 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM213 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
Electricity:Zone:GUESTROOM214 5.49 53.58 01-JAN-02:10 404.62 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM214 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM214 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
Electricity:Zone:GUESTROOM215_218 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:GUESTROOM215_218 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM215_218 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:GUESTROOM219 5.49 53.58 01-JAN-02:10 404.62 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM219 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM219 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
Electricity:Zone:GUESTROOM220_223 21.98 214.30 01-JAN-02:10 1618.47 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM220_223 5.16 43.66 01-JAN-02:10 396.90 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM220_223 5.16 43.66 01-JAN-02:10 396.90 01-JAN-19:10
Electricity:Zone:GUESTROOM224 5.49 53.58 01-JAN-02:10 404.62 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM224 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM224 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
Electricity:Zone:GUESTROOM301 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:GUESTROOM301 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM301 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:GUESTROOM302_305 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:GUESTROOM302_305 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM302_305 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:GUESTROOM306_308 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:GUESTROOM306_308 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM306_308 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:GUESTROOM309_312 21.98 214.32 01-JAN-02:10 1618.58 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM309_312 5.16 43.66 01-JAN-02:10 396.93 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM309_312 5.16 43.66 01-JAN-02:10 396.93 01-JAN-19:10
Electricity:Zone:GUESTROOM313 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:GUESTROOM313 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM313 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:GUESTROOM314 5.49 53.58 01-JAN-02:10 404.62 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM314 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM314 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
Electricity:Zone:GUESTROOM315_318 21.98 214.30 01-JAN-02:10 1618.47 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM315_318 5.16 43.66 01-JAN-02:10 396.90 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM315_318 5.16 43.66 01-JAN-02:10 396.90 01-JAN-19:10
Electricity:Zone:GUESTROOM319 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:GUESTROOM319 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM319 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:GUESTROOM320_323 21.98 214.30 01-JAN-02:10 1618.47 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM320_323 5.16 43.66 01-JAN-02:10 396.90 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM320_323 5.16 43.66 01-JAN-02:10 396.90 01-JAN-19:10
Electricity:Zone:GUESTROOM324 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:GUESTROOM324 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM324 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:GUESTROOM401 5.49 53.58 01-JAN-02:10 404.65 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM401 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM401 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
Electricity:Zone:GUESTROOM402_405 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:GUESTROOM402_405 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM402_405 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:GUESTROOM406_408 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:GUESTROOM406_408 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM406_408 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:GUESTROOM409_412 21.98 214.32 01-JAN-02:10 1618.58 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM409_412 5.16 43.66 01-JAN-02:10 396.93 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM409_412 5.16 43.66 01-JAN-02:10 396.93 01-JAN-19:10
Electricity:Zone:GUESTROOM413 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:GUESTROOM413 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM413 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:GUESTROOM414 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorLights:Electricity:Zone:GUESTROOM414 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM414 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Zone:GUESTROOM415_418 21.98 214.30 01-JAN-02:10 1618.47 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM415_418 5.16 43.66 01-JAN-02:10 396.90 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM415_418 5.16 43.66 01-JAN-02:10 396.90 01-JAN-19:10
Electricity:Zone:GUESTROOM419 5.49 53.58 01-JAN-02:10 404.62 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM419 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM419 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
Electricity:Zone:GUESTROOM420_423 21.98 214.30 01-JAN-02:10 1618.47 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM420_423 5.16 43.66 01-JAN-02:10 396.90 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM420_423 5.16 43.66 01-JAN-02:10 396.90 01-JAN-19:10
Electricity:Zone:GUESTROOM424 5.49 53.58 01-JAN-02:10 404.62 01-JAN-08:10
InteriorLights:Electricity:Zone:GUESTROOM424 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:GUESTROOM424 1.29 10.91 01-JAN-02:10 99.23 01-JAN-19:10
Electricity:Zone:LAUNDRYROOMFLR1 32.58 0.00 01-JAN-00:10 3251.18 22-DEC-08:10
InteriorLights:Electricity:Zone:LAUNDRYROOMFLR1 4.10 0.00 01-JAN-00:10 558.09 01-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:LAUNDRYROOMFLR1 4.10 0.00 01-JAN-00:10 558.09 01-JAN-16:40
Electricity:Zone:MECHANICALROOMFLR1 1.19 15.09 01-JAN-00:10 60.38 01-JAN-08:10
InteriorLights:Electricity:Zone:MECHANICALROOMFLR1 1.19 15.09 01-JAN-00:10 60.38 01-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:MECHANICALROOMFLR1 1.19 15.09 01-JAN-00:10 60.38 01-JAN-08:10
Electricity:Zone:MEETINGROOMFLR1 10.57 0.00 01-JAN-00:10 1049.81 23-DEC-08:10
InteriorLights:Electricity:Zone:MEETINGROOMFLR1 8.45 0.00 01-JAN-00:10 838.14 01-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:MEETINGROOMFLR1 8.45 0.00 01-JAN-00:10 838.14 01-JAN-16:40
Electricity:Zone:REARSTAIRSFLR1 3.34 105.87 01-JAN-00:10 105.87 01-JAN-00:10
InteriorLights:Electricity:Zone:REARSTAIRSFLR1 3.34 105.87 01-JAN-00:10 105.87 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:REARSTAIRSFLR1 3.34 105.87 01-JAN-00:10 105.87 01-JAN-00:10
Electricity:Zone:REARSTAIRSFLR2 3.34 105.87 01-JAN-00:10 105.87 01-JAN-00:10
InteriorLights:Electricity:Zone:REARSTAIRSFLR2 3.34 105.87 01-JAN-00:10 105.87 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:REARSTAIRSFLR2 3.34 105.87 01-JAN-00:10 105.87 01-JAN-00:10
Electricity:Zone:REARSTAIRSFLR3 3.34 105.87 01-JAN-00:10 105.87 01-JAN-00:10
InteriorLights:Electricity:Zone:REARSTAIRSFLR3 3.34 105.87 01-JAN-00:10 105.87 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:REARSTAIRSFLR3 3.34 105.87 01-JAN-00:10 105.87 01-JAN-00:10
Electricity:Zone:REARSTAIRSFLR4 3.34 105.87 01-JAN-00:10 105.87 01-JAN-00:10
InteriorLights:Electricity:Zone:REARSTAIRSFLR4 3.34 105.87 01-JAN-00:10 105.87 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:REARSTAIRSFLR4 3.34 105.87 01-JAN-00:10 105.87 01-JAN-00:10
Electricity:Zone:REARSTORAGEFLR1 0.28 3.59 01-JAN-00:10 14.37 01-JAN-08:10
InteriorLights:Electricity:Zone:REARSTORAGEFLR1 0.28 3.59 01-JAN-00:10 14.37 01-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:REARSTORAGEFLR1 0.28 3.59 01-JAN-00:10 14.37 01-JAN-08:10
Electricity:Zone:REARSTORAGEFLR2 0.28 3.59 01-JAN-00:10 14.37 01-JAN-08:10
InteriorLights:Electricity:Zone:REARSTORAGEFLR2 0.28 3.59 01-JAN-00:10 14.37 01-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:REARSTORAGEFLR2 0.28 3.59 01-JAN-00:10 14.37 01-JAN-08:10
Electricity:Zone:REARSTORAGEFLR3 0.28 3.59 01-JAN-00:10 14.37 01-JAN-08:10
InteriorLights:Electricity:Zone:REARSTORAGEFLR3 0.28 3.59 01-JAN-00:10 14.37 01-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:REARSTORAGEFLR3 0.28 3.59 01-JAN-00:10 14.37 01-JAN-08:10
Electricity:Zone:REARSTORAGEFLR4 0.28 3.59 01-JAN-00:10 14.37 01-JAN-08:10
InteriorLights:Electricity:Zone:REARSTORAGEFLR4 0.28 3.59 01-JAN-00:10 14.37 01-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:REARSTORAGEFLR4 0.28 3.59 01-JAN-00:10 14.37 01-JAN-08:10
Electricity:Zone:RESTROOMFLR1 3.84 121.63 01-JAN-00:10 121.63 01-JAN-00:10
InteriorLights:Electricity:Zone:RESTROOMFLR1 3.84 121.63 01-JAN-00:10 121.63 01-JAN-00:10
LightsWired:InteriorLights:Electricity:Zone:RESTROOMFLR1 3.84 121.63 01-JAN-00:10 121.63 01-JAN-00:10
InteriorEquipment:Electricity 471.46 5569.37 01-JAN-00:10 35131.01 01-JAN-08:10
InteriorEquipment:Electricity:Zone:CORRIDORFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 471.46 5569.37 01-JAN-00:10 35131.01 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 311.05 3640.21 01-JAN-00:10 24347.29 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDORFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 311.05 3640.21 01-JAN-00:10 24347.29 01-JAN-08:10
InteriorEquipment:Electricity:Zone:CORRIDORFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDORFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:CORRIDORFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDORFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:CORRIDORFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDORFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR1 131.94 1929.17 01-JAN-00:10 8074.65 01-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity 130.97 1922.92 01-JAN-00:10 8012.15 01-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR1 130.97 1922.92 01-JAN-00:10 8012.15 01-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL 130.97 1922.92 01-JAN-00:10 8012.15 01-JAN-07:10
ElevatorLightsFan:InteriorEquipment:Electricity 0.97 6.25 01-JAN-00:10 62.50 01-JAN-07:10
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR1 0.97 6.25 01-JAN-00:10 62.50 01-JAN-07:10
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL 0.97 6.25 01-JAN-00:10 62.50 01-JAN-07:10
InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:EMPLOYEELOUNGEFLR1 9.57 55.76 01-JAN-00:10 672.25 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:EMPLOYEELOUNGEFLR1 9.57 55.76 01-JAN-00:10 672.25 01-JAN-08:10
InteriorEquipment:Electricity:Zone:EXERCISECENTERFLR1 8.36 0.00 01-JAN-00:10 606.20 01-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:EXERCISECENTERFLR1 8.36 0.00 01-JAN-00:10 606.20 01-JAN-07:10
InteriorEquipment:Electricity:Zone:FRONTLOUNGEFLR1 50.36 892.34 01-JAN-00:10 4249.25 01-JAN-06:10
MiscPlug:InteriorEquipment:Electricity:Zone:FRONTLOUNGEFLR1 50.36 892.34 01-JAN-00:10 4249.25 01-JAN-06:10
InteriorEquipment:Electricity:Zone:FRONTOFFICEFLR1 29.44 549.10 01-JAN-00:10 1663.95 03-JAN-10:10
MiscPlug:InteriorEquipment:Electricity:Zone:FRONTOFFICEFLR1 29.44 549.10 01-JAN-00:10 1663.95 03-JAN-10:10
InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:GUESTROOM101 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM101 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:GUESTROOM102 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM102 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:GUESTROOM103 4.20 42.66 01-JAN-00:10 349.07 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM103 4.20 42.66 01-JAN-00:10 349.07 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM104 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM104 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM105 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM105 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM201 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM201 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:GUESTROOM202_205 16.82 170.66 01-JAN-00:10 1396.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM202_205 16.82 170.66 01-JAN-00:10 1396.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM206_208 13.58 137.84 01-JAN-00:10 1127.78 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM206_208 13.58 137.84 01-JAN-00:10 1127.78 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM209_212 16.82 170.66 01-JAN-00:10 1396.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM209_212 16.82 170.66 01-JAN-00:10 1396.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM213 4.20 42.66 01-JAN-00:10 349.07 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM213 4.20 42.66 01-JAN-00:10 349.07 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM214 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM214 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM215_218 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM215_218 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:GUESTROOM219 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM219 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM220_223 16.82 170.65 01-JAN-00:10 1396.20 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM220_223 16.82 170.65 01-JAN-00:10 1396.20 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM224 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM224 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM301 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM301 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:GUESTROOM302_305 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM302_305 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:GUESTROOM306_308 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM306_308 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:GUESTROOM309_312 16.82 170.66 01-JAN-00:10 1396.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM309_312 16.82 170.66 01-JAN-00:10 1396.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM313 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM313 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:GUESTROOM314 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM314 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM315_318 16.82 170.65 01-JAN-00:10 1396.20 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM315_318 16.82 170.65 01-JAN-00:10 1396.20 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM319 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM319 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:GUESTROOM320_323 16.82 170.65 01-JAN-00:10 1396.20 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM320_323 16.82 170.65 01-JAN-00:10 1396.20 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM324 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM324 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:GUESTROOM401 4.20 42.66 01-JAN-00:10 349.07 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM401 4.20 42.66 01-JAN-00:10 349.07 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM402_405 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM402_405 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:GUESTROOM406_408 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM406_408 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:GUESTROOM409_412 16.82 170.66 01-JAN-00:10 1396.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM409_412 16.82 170.66 01-JAN-00:10 1396.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM413 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM413 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:GUESTROOM414 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM414 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:GUESTROOM415_418 16.82 170.65 01-JAN-00:10 1396.20 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM415_418 16.82 170.65 01-JAN-00:10 1396.20 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM419 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM419 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM420_423 16.82 170.65 01-JAN-00:10 1396.20 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM420_423 16.82 170.65 01-JAN-00:10 1396.20 01-JAN-08:10
InteriorEquipment:Electricity:Zone:GUESTROOM424 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM424 4.20 42.66 01-JAN-00:10 349.05 01-JAN-08:10
InteriorEquipment:Electricity:Zone:MECHANICALROOMFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECHANICALROOMFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:MEETINGROOMFLR1 2.12 0.00 01-JAN-00:10 237.69 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:MEETINGROOMFLR1 2.12 0.00 01-JAN-00:10 237.69 01-JAN-08:10
InteriorEquipment:Electricity:Zone:REARSTAIRSFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:REARSTAIRSFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:REARSTAIRSFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:REARSTAIRSFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:REARSTAIRSFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:REARSTAIRSFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:REARSTAIRSFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:REARSTAIRSFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:REARSTORAGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:REARSTORAGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:REARSTORAGEFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:REARSTORAGEFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:REARSTORAGEFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:REARSTORAGEFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:REARSTORAGEFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:REARSTORAGEFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:RESTROOMFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:Zone:RESTROOMFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
InteriorEquipment:Electricity:Zone:LAUNDRYROOMFLR1 28.48 0.00 01-JAN-00:10 2709.07 01-JAN-08:10
Laundry:InteriorEquipment:Electricity 28.48 0.00 01-JAN-00:10 2709.07 01-JAN-08:10
Laundry:InteriorEquipment:Electricity:Zone:LAUNDRYROOMFLR1 28.48 0.00 01-JAN-00:10 2709.07 01-JAN-08:10
Laundry:InteriorEquipment:Electricity:SpaceType:GENERAL 28.48 0.00 01-JAN-00:10 2709.07 01-JAN-08:10
Fans:Electricity 284.74 3931.22 19-MAR-17:50 11706.74 01-FEB-17:50
Fans:Electricity:Zone:GUESTROOM103 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM103 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM104 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM104 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM105 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM105 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM202_205 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM202_205 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM206_208 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM206_208 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM209_212 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM209_212 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM213 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM213 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM214 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM214 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM219 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM219 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM220_223 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM220_223 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM224 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM224 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM309_312 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM309_312 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM314 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM314 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM315_318 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM315_318 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM320_323 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM320_323 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM401 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM401 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM409_412 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM409_412 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM415_418 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM415_418 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM419 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM419 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM420_423 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM420_423 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:GUESTROOM424 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:GUESTROOM424 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityPurchased:Facility 1515.69 26699.17 26-APR-10:10 206318.75 02-FEB-07:10
ElectricityPurchased:Plant 1515.69 26699.17 26-APR-10:10 206318.75 02-FEB-07:10
Cogeneration:ElectricityPurchased 1515.69 26699.17 26-APR-10:10 206318.75 02-FEB-07:10
General:Cogeneration:ElectricityPurchased 1515.69 26699.17 26-APR-10:10 206318.75 02-FEB-07:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 1515.69 26699.17 26-APR-10:10 206318.75 02-FEB-07:10
ElectricityNet:Plant 1515.69 26699.17 26-APR-10:10 206318.75 02-FEB-07:10
Cogeneration:ElectricityNet 1515.69 26699.17 26-APR-10:10 206318.75 02-FEB-07:10
General:Cogeneration:ElectricityNet 1515.69 26699.17 26-APR-10:10 206318.75 02-FEB-07:10
Electricity:HVAC 794.64 5586.24 24-APR-07:10 164195.22 02-FEB-07:10
General:Fans:Electricity 284.74 3931.22 19-MAR-17:50 11706.74 01-FEB-17:50
Heating:Electricity 284.96 0.00 18-MAR-16:10 153452.85 02-FEB-07:10
General:Heating:Electricity 284.96 0.00 18-MAR-16:10 153452.85 02-FEB-07:10
Cooling:Electricity 224.94 0.00 05-JAN-24:00 47771.05 04-AUG-15:10
General:Cooling:Electricity 224.94 0.00 05-JAN-24:00 47771.05 04-AUG-15:10
ExteriorLights:Electricity 49.88 0.00 01-JAN-08:00 3177.58 01-JAN-00:10
General:ExteriorLights:Electricity 49.88 0.00 01-JAN-08:00 3177.58 01-JAN-00:10
Electricity:Plant 0.26 8.11 01-JAN-00:10 8.11 24-JAN-12:50
Pumps:Electricity 0.26 8.11 01-JAN-00:10 8.11 24-JAN-12:50
General:Pumps:Electricity 0.26 8.11 01-JAN-00:10 8.11 24-JAN-12:50


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 1592.48 7231.83 18-MAR-16:10 156628.46 02-FEB-09:40
NaturalGas:Building 421.49 0.00 01-JAN-00:10 40096.03 01-JAN-09:10
NaturalGas:Zone:LAUNDRYROOMFLR1 421.49 0.00 01-JAN-00:10 40096.03 01-JAN-09:10
NaturalGas:SpaceType:GENERAL 421.49 0.00 01-JAN-00:10 40096.03 01-JAN-09:10
InteriorEquipment:NaturalGas 421.49 0.00 01-JAN-00:10 40096.03 01-JAN-09:10
InteriorEquipment:NaturalGas:Zone:LAUNDRYROOMFLR1 421.49 0.00 01-JAN-00:10 40096.03 01-JAN-09:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 421.49 0.00 01-JAN-00:10 40096.03 01-JAN-09:10
Laundry:InteriorEquipment:NaturalGas 421.49 0.00 01-JAN-00:10 40096.03 01-JAN-09:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRYROOMFLR1 421.49 0.00 01-JAN-00:10 40096.03 01-JAN-09:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 421.49 0.00 01-JAN-00:10 40096.03 01-JAN-09:10
NaturalGas:HVAC 101.94 0.00 24-FEB-13:40 35248.02 02-FEB-08:10
Heating:NaturalGas 101.94 0.00 24-FEB-13:40 35248.02 02-FEB-08:10
General:Heating:NaturalGas 101.94 0.00 24-FEB-13:40 35248.02 02-FEB-08:10
NaturalGas:Plant 1069.05 7231.83 01-JAN-06:10 95277.14 18-FEB-08:40
WaterSystems:NaturalGas 1069.05 7231.83 01-JAN-06:10 95277.14 18-FEB-08:40
Water Heater:WaterSystems:NaturalGas 1069.05 7231.83 01-JAN-06:10 95277.14 18-FEB-08:40


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 2578.17 0.00 01-JAN-01:10 0.00 01-JAN-08:10
Water:Plant 2578.17 0.00 01-JAN-01:10 0.00 01-JAN-08:10
WaterSystems:Water 2578.17 0.00 01-JAN-01:10 0.00 01-JAN-08:10
WaterUse:WaterSystems:Water 2578.17 0.00 01-JAN-01:10 0.00 01-JAN-08:10
MainsWater:Facility 2578.17 0.00 01-JAN-01:10 0.00 01-JAN-08:10
MainsWater:Plant 2578.17 0.00 01-JAN-01:10 0.00 01-JAN-08:10
WaterSystems:MainsWater 2578.17 0.00 01-JAN-01:10 0.00 01-JAN-08:10
WaterUse:WaterSystems:MainsWater 2578.17 0.00 01-JAN-01:10 0.00 01-JAN-08:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 2942.87 26178.54 25-MAR-16:10 335600.78 02-AUG-09:00
EnergyTransfer:Building 997.67 9010.63 04-MAR-11:10 108580.06 02-FEB-07:10
EnergyTransfer:Zone:REARSTAIRSFLR1 0.02 0.00 20-OCT-11:50 1.82 29-JAN-02:00
Heating:EnergyTransfer 128.07 0.07 10-APR-12:00 102401.42 02-FEB-07:10
Heating:EnergyTransfer:Zone:REARSTAIRSFLR1 0.02 0.00 06-JAN-12:30 1.82 29-JAN-02:00
General:Heating:EnergyTransfer 128.07 0.07 10-APR-12:00 102401.42 02-FEB-07:10
General:Heating:EnergyTransfer:Zone:REARSTAIRSFLR1 0.02 0.00 06-JAN-12:30 1.82 29-JAN-02:00
Cooling:EnergyTransfer 869.60 3142.91 03-FEB-12:30 105486.75 18-JUL-18:40
Cooling:EnergyTransfer:Zone:REARSTAIRSFLR1 0.00 0.00 01-JAN-00:10 0.22 15-DEC-11:00
General:Cooling:EnergyTransfer 869.60 3142.91 03-FEB-12:30 105486.75 18-JUL-18:40
General:Cooling:EnergyTransfer:Zone:REARSTAIRSFLR1 0.00 0.00 01-JAN-00:10 0.22 15-DEC-11:00
EnergyTransfer:Zone:CORRIDORFLR1 121.76 0.02 07-MAR-12:30 74864.90 02-FEB-07:10
Heating:EnergyTransfer:Zone:CORRIDORFLR1 39.24 0.00 01-JAN-00:10 74864.90 02-FEB-07:10
General:Heating:EnergyTransfer:Zone:CORRIDORFLR1 39.24 0.00 01-JAN-00:10 74864.90 02-FEB-07:10
Cooling:EnergyTransfer:Zone:CORRIDORFLR1 82.52 0.00 01-JAN-06:10 17379.86 04-AUG-16:10
General:Cooling:EnergyTransfer:Zone:CORRIDORFLR1 82.52 0.00 01-JAN-06:10 17379.86 04-AUG-16:10
EnergyTransfer:Zone:REARSTORAGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:REARSTORAGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:REARSTORAGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:REARSTORAGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:REARSTORAGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:FRONTLOUNGEFLR1 62.13 5.16 04-JAN-02:20 5910.15 03-AUG-09:00
Heating:EnergyTransfer:Zone:FRONTLOUNGEFLR1 0.52 0.00 01-JAN-00:10 1887.71 03-FEB-18:30
General:Heating:EnergyTransfer:Zone:FRONTLOUNGEFLR1 0.52 0.00 01-JAN-00:10 1887.71 03-FEB-18:30
Cooling:EnergyTransfer:Zone:FRONTLOUNGEFLR1 61.61 0.00 03-JAN-03:20 5910.15 03-AUG-09:00
General:Cooling:EnergyTransfer:Zone:FRONTLOUNGEFLR1 61.61 0.00 03-JAN-03:20 5910.15 03-AUG-09:00
EnergyTransfer:Zone:RESTROOMFLR1 4.77 5.01 23-APR-12:50 474.25 07-SEP-17:00
Heating:EnergyTransfer:Zone:RESTROOMFLR1 1.11 0.00 24-FEB-17:20 149.17 03-FEB-05:00
General:Heating:EnergyTransfer:Zone:RESTROOMFLR1 1.11 0.00 24-FEB-17:20 149.17 03-FEB-05:00
Cooling:EnergyTransfer:Zone:RESTROOMFLR1 3.67 0.00 01-JAN-00:10 474.25 07-SEP-17:00
General:Cooling:EnergyTransfer:Zone:RESTROOMFLR1 3.67 0.00 01-JAN-00:10 474.25 07-SEP-17:00
EnergyTransfer:Zone:MEETINGROOMFLR1 16.25 0.00 01-JAN-00:10 4432.49 10-DEC-13:50
Heating:EnergyTransfer:Zone:MEETINGROOMFLR1 0.68 0.00 01-JAN-00:10 2462.83 10-DEC-13:50
General:Heating:EnergyTransfer:Zone:MEETINGROOMFLR1 0.68 0.00 01-JAN-00:10 2462.83 10-DEC-13:50
Cooling:EnergyTransfer:Zone:MEETINGROOMFLR1 15.57 0.00 01-JAN-00:10 2783.05 23-OCT-07:10
General:Cooling:EnergyTransfer:Zone:MEETINGROOMFLR1 15.57 0.00 01-JAN-00:10 2783.05 23-OCT-07:10
EnergyTransfer:Zone:MECHANICALROOMFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:MECHANICALROOMFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:MECHANICALROOMFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:MECHANICALROOMFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:MECHANICALROOMFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:GUESTROOM101 0.20 0.00 01-JAN-00:10 630.96 02-FEB-15:40
Heating:EnergyTransfer:Zone:GUESTROOM101 0.02 0.00 01-JAN-00:10 159.92 04-AUG-14:10
General:Heating:EnergyTransfer:Zone:GUESTROOM101 0.02 0.00 01-JAN-00:10 159.92 04-AUG-14:10
Cooling:EnergyTransfer:Zone:GUESTROOM101 0.17 0.00 01-JAN-00:10 630.96 02-FEB-15:40
General:Cooling:EnergyTransfer:Zone:GUESTROOM101 0.17 0.00 01-JAN-00:10 630.96 02-FEB-15:40
EnergyTransfer:Zone:GUESTROOM102 0.20 0.00 01-JAN-00:10 631.97 02-FEB-15:40
Heating:EnergyTransfer:Zone:GUESTROOM102 0.02 0.00 01-JAN-00:10 174.42 04-AUG-15:00
General:Heating:EnergyTransfer:Zone:GUESTROOM102 0.02 0.00 01-JAN-00:10 174.42 04-AUG-15:00
Cooling:EnergyTransfer:Zone:GUESTROOM102 0.18 0.00 01-JAN-00:10 631.97 02-FEB-15:40
General:Cooling:EnergyTransfer:Zone:GUESTROOM102 0.18 0.00 01-JAN-00:10 631.97 02-FEB-15:40
EnergyTransfer:Zone:GUESTROOM103 8.81 0.00 01-JAN-08:10 1697.49 01-SEP-21:00
Heating:EnergyTransfer:Zone:GUESTROOM103 2.01 0.00 01-JAN-08:10 961.41 03-FEB-09:10
General:Heating:EnergyTransfer:Zone:GUESTROOM103 2.01 0.00 01-JAN-08:10 961.41 03-FEB-09:10
Cooling:EnergyTransfer:Zone:GUESTROOM103 6.80 0.00 01-JAN-00:10 1697.49 01-SEP-21:00
General:Cooling:EnergyTransfer:Zone:GUESTROOM103 6.80 0.00 01-JAN-00:10 1697.49 01-SEP-21:00
EnergyTransfer:Zone:GUESTROOM104 9.21 0.00 01-JAN-08:10 1688.20 10-SEP-21:00
Heating:EnergyTransfer:Zone:GUESTROOM104 0.61 0.00 01-JAN-00:10 752.63 03-FEB-16:10
General:Heating:EnergyTransfer:Zone:GUESTROOM104 0.61 0.00 01-JAN-00:10 752.63 03-FEB-16:10
Cooling:EnergyTransfer:Zone:GUESTROOM104 8.60 0.00 01-JAN-08:10 1688.20 10-SEP-21:00
General:Cooling:EnergyTransfer:Zone:GUESTROOM104 8.60 0.00 01-JAN-08:10 1688.20 10-SEP-21:00
EnergyTransfer:Zone:GUESTROOM105 19.43 0.00 01-JAN-08:10 1906.31 08-MAY-17:00
Heating:EnergyTransfer:Zone:GUESTROOM105 0.09 0.00 01-JAN-00:10 138.85 04-FEB-19:10
General:Heating:EnergyTransfer:Zone:GUESTROOM105 0.09 0.00 01-JAN-00:10 138.85 04-FEB-19:10
Cooling:EnergyTransfer:Zone:GUESTROOM105 19.35 0.00 01-JAN-08:10 1876.93 03-SEP-19:40
General:Cooling:EnergyTransfer:Zone:GUESTROOM105 19.35 0.00 01-JAN-08:10 1876.93 03-SEP-19:40
EnergyTransfer:Zone:EMPLOYEELOUNGEFLR1 69.53 979.04 07-FEB-05:00 4143.47 02-AUG-12:00
Heating:EnergyTransfer:Zone:EMPLOYEELOUNGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:EMPLOYEELOUNGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:EMPLOYEELOUNGEFLR1 69.53 979.04 07-FEB-05:00 4143.47 02-AUG-12:00
General:Cooling:EnergyTransfer:Zone:EMPLOYEELOUNGEFLR1 69.53 979.04 07-FEB-05:00 4143.47 02-AUG-12:00
EnergyTransfer:Zone:LAUNDRYROOMFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:LAUNDRYROOMFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRYROOMFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRYROOMFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:LAUNDRYROOMFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:ELEVATORCOREFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ELEVATORCOREFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ELEVATORCOREFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:EXERCISECENTERFLR1 22.69 5.05 29-JAN-23:20 2068.20 30-JAN-23:10
Heating:EnergyTransfer:Zone:EXERCISECENTERFLR1 0.05 0.00 01-JAN-00:10 984.58 30-JAN-23:10
General:Heating:EnergyTransfer:Zone:EXERCISECENTERFLR1 0.05 0.00 01-JAN-00:10 984.58 30-JAN-23:10
Cooling:EnergyTransfer:Zone:EXERCISECENTERFLR1 22.64 0.00 05-JAN-04:30 1512.13 09-NOV-17:00
General:Cooling:EnergyTransfer:Zone:EXERCISECENTERFLR1 22.64 0.00 05-JAN-04:30 1512.13 09-NOV-17:00
EnergyTransfer:Zone:FRONTOFFICEFLR1 30.31 5.22 01-FEB-18:40 2853.15 02-AUG-10:20
Heating:EnergyTransfer:Zone:FRONTOFFICEFLR1 0.30 0.00 01-JAN-00:10 1562.45 09-DEC-12:00
General:Heating:EnergyTransfer:Zone:FRONTOFFICEFLR1 0.30 0.00 01-JAN-00:10 1562.45 09-DEC-12:00
Cooling:EnergyTransfer:Zone:FRONTOFFICEFLR1 30.01 0.00 05-JAN-03:30 2853.15 02-AUG-10:20
General:Cooling:EnergyTransfer:Zone:FRONTOFFICEFLR1 30.01 0.00 05-JAN-03:30 2853.15 02-AUG-10:20
EnergyTransfer:Zone:FRONTSTAIRSFLR1 0.02 0.01 16-AUG-07:00 52.94 02-FEB-04:00
Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR1 0.02 0.00 28-JAN-01:00 52.94 02-FEB-04:00
General:Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR1 0.02 0.00 28-JAN-01:00 52.94 02-FEB-04:00
Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR1 0.00 0.00 01-JAN-00:10 0.17 06-FEB-12:40
General:Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR1 0.00 0.00 01-JAN-00:10 0.17 06-FEB-12:40
EnergyTransfer:Zone:FRONTSTORAGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:REARSTAIRSFLR2 0.02 0.00 07-FEB-13:00 1.84 29-JAN-02:00
Heating:EnergyTransfer:Zone:REARSTAIRSFLR2 0.02 0.00 06-JAN-12:10 1.84 29-JAN-02:00
General:Heating:EnergyTransfer:Zone:REARSTAIRSFLR2 0.02 0.00 06-JAN-12:10 1.84 29-JAN-02:00
Cooling:EnergyTransfer:Zone:REARSTAIRSFLR2 0.00 0.00 01-JAN-00:10 0.38 10-APR-12:00
General:Cooling:EnergyTransfer:Zone:REARSTAIRSFLR2 0.00 0.00 01-JAN-00:10 0.38 10-APR-12:00
EnergyTransfer:Zone:CORRIDORFLR2 26.03 0.08 12-DEC-22:50 2146.32 15-JUL-19:10
Heating:EnergyTransfer:Zone:CORRIDORFLR2 0.14 0.00 01-JAN-00:10 725.70 07-JAN-01:50
General:Heating:EnergyTransfer:Zone:CORRIDORFLR2 0.14 0.00 01-JAN-00:10 725.70 07-JAN-01:50
Cooling:EnergyTransfer:Zone:CORRIDORFLR2 25.89 0.00 06-JAN-05:40 2146.32 15-JUL-19:10
General:Cooling:EnergyTransfer:Zone:CORRIDORFLR2 25.89 0.00 06-JAN-05:40 2146.32 15-JUL-19:10
EnergyTransfer:Zone:REARSTORAGEFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:REARSTORAGEFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:REARSTORAGEFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:REARSTORAGEFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:REARSTORAGEFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:GUESTROOM201 0.32 0.00 01-JAN-00:10 344.91 24-NOV-15:40
Heating:EnergyTransfer:Zone:GUESTROOM201 0.17 0.00 01-JAN-00:10 316.22 02-FEB-09:20
General:Heating:EnergyTransfer:Zone:GUESTROOM201 0.17 0.00 01-JAN-00:10 316.22 02-FEB-09:20
Cooling:EnergyTransfer:Zone:GUESTROOM201 0.14 0.00 01-JAN-00:10 344.91 24-NOV-15:40
General:Cooling:EnergyTransfer:Zone:GUESTROOM201 0.14 0.00 01-JAN-00:10 344.91 24-NOV-15:40
EnergyTransfer:Zone:GUESTROOM202_205 34.77 0.00 01-JAN-08:10 6373.91 16-AUG-18:10
Heating:EnergyTransfer:Zone:GUESTROOM202_205 2.53 0.00 01-JAN-07:10 2269.78 09-DEC-16:10
General:Heating:EnergyTransfer:Zone:GUESTROOM202_205 2.53 0.00 01-JAN-07:10 2269.78 09-DEC-16:10
Cooling:EnergyTransfer:Zone:GUESTROOM202_205 32.24 0.00 01-JAN-00:10 6373.91 16-AUG-18:10
General:Cooling:EnergyTransfer:Zone:GUESTROOM202_205 32.24 0.00 01-JAN-00:10 6373.91 16-AUG-18:10
EnergyTransfer:Zone:GUESTROOM206_208 28.17 0.00 01-JAN-08:10 5242.21 29-AUG-16:40
Heating:EnergyTransfer:Zone:GUESTROOM206_208 1.23 0.00 01-JAN-00:10 1519.28 09-DEC-16:10
General:Heating:EnergyTransfer:Zone:GUESTROOM206_208 1.23 0.00 01-JAN-00:10 1519.28 09-DEC-16:10
Cooling:EnergyTransfer:Zone:GUESTROOM206_208 26.94 0.00 01-JAN-08:10 5242.21 29-AUG-16:40
General:Cooling:EnergyTransfer:Zone:GUESTROOM206_208 26.94 0.00 01-JAN-08:10 5242.21 29-AUG-16:40
EnergyTransfer:Zone:GUESTROOM209_212 32.44 0.00 01-JAN-08:10 6136.38 23-JUL-18:10
Heating:EnergyTransfer:Zone:GUESTROOM209_212 0.69 0.00 01-JAN-00:10 1340.99 12-DEC-16:10
General:Heating:EnergyTransfer:Zone:GUESTROOM209_212 0.69 0.00 01-JAN-00:10 1340.99 12-DEC-16:10
Cooling:EnergyTransfer:Zone:GUESTROOM209_212 31.75 0.00 01-JAN-08:10 6136.38 23-JUL-18:10
General:Cooling:EnergyTransfer:Zone:GUESTROOM209_212 31.75 0.00 01-JAN-08:10 6136.38 23-JUL-18:10
EnergyTransfer:Zone:GUESTROOM213 8.80 0.00 01-JAN-08:10 1528.38 12-SEP-20:50
Heating:EnergyTransfer:Zone:GUESTROOM213 2.30 0.00 01-JAN-08:10 953.06 09-DEC-16:20
General:Heating:EnergyTransfer:Zone:GUESTROOM213 2.30 0.00 01-JAN-08:10 953.06 09-DEC-16:20
Cooling:EnergyTransfer:Zone:GUESTROOM213 6.49 0.00 01-JAN-00:10 1528.38 12-SEP-20:50
General:Cooling:EnergyTransfer:Zone:GUESTROOM213 6.49 0.00 01-JAN-00:10 1528.38 12-SEP-20:50
EnergyTransfer:Zone:GUESTROOM214 11.71 0.00 01-JAN-08:10 1596.21 15-JUL-21:30
Heating:EnergyTransfer:Zone:GUESTROOM214 0.28 0.00 01-JAN-00:10 517.50 09-DEC-16:10
General:Heating:EnergyTransfer:Zone:GUESTROOM214 0.28 0.00 01-JAN-00:10 517.50 09-DEC-16:10
Cooling:EnergyTransfer:Zone:GUESTROOM214 11.43 0.00 01-JAN-08:10 1596.21 15-JUL-21:30
General:Cooling:EnergyTransfer:Zone:GUESTROOM214 11.43 0.00 01-JAN-08:10 1596.21 15-JUL-21:30
EnergyTransfer:Zone:GUESTROOM215_218 57.70 0.00 03-JAN-06:50 4079.12 29-JUN-16:30
Heating:EnergyTransfer:Zone:GUESTROOM215_218 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:GUESTROOM215_218 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:GUESTROOM215_218 57.70 0.00 03-JAN-06:50 4079.12 29-JUN-16:30
General:Cooling:EnergyTransfer:Zone:GUESTROOM215_218 57.70 0.00 03-JAN-06:50 4079.12 29-JUN-16:30
EnergyTransfer:Zone:ELEVATORCOREFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ELEVATORCOREFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ELEVATORCOREFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:GUESTROOM219 75.13 0.00 19-MAR-17:50 5026.92 12-AUG-17:00
Heating:EnergyTransfer:Zone:GUESTROOM219 0.03 0.00 01-JAN-00:10 254.55 16-APR-06:10
General:Heating:EnergyTransfer:Zone:GUESTROOM219 0.03 0.00 01-JAN-00:10 254.55 16-APR-06:10
Cooling:EnergyTransfer:Zone:GUESTROOM219 75.10 0.00 19-MAR-17:50 5026.92 12-AUG-17:00
General:Cooling:EnergyTransfer:Zone:GUESTROOM219 75.10 0.00 19-MAR-17:50 5026.92 12-AUG-17:00
EnergyTransfer:Zone:GUESTROOM220_223 34.40 0.00 01-JAN-08:10 5621.01 25-JUL-06:50
Heating:EnergyTransfer:Zone:GUESTROOM220_223 0.39 0.00 01-JAN-00:10 1020.99 02-FEB-16:10
General:Heating:EnergyTransfer:Zone:GUESTROOM220_223 0.39 0.00 01-JAN-00:10 1020.99 02-FEB-16:10
Cooling:EnergyTransfer:Zone:GUESTROOM220_223 34.01 0.00 01-JAN-08:10 5621.01 25-JUL-06:50
General:Cooling:EnergyTransfer:Zone:GUESTROOM220_223 34.01 0.00 01-JAN-08:10 5621.01 25-JUL-06:50
EnergyTransfer:Zone:GUESTROOM224 9.35 0.00 01-JAN-08:10 1551.81 28-JUN-06:50
Heating:EnergyTransfer:Zone:GUESTROOM224 1.00 0.00 01-JAN-07:10 734.63 03-FEB-16:20
General:Heating:EnergyTransfer:Zone:GUESTROOM224 1.00 0.00 01-JAN-07:10 734.63 03-FEB-16:20
Cooling:EnergyTransfer:Zone:GUESTROOM224 8.35 0.00 01-JAN-00:10 1551.81 28-JUN-06:50
General:Cooling:EnergyTransfer:Zone:GUESTROOM224 8.35 0.00 01-JAN-00:10 1551.81 28-JUN-06:50
EnergyTransfer:Zone:FRONTSTORAGEFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:FRONTSTAIRSFLR2 0.03 0.00 23-MAR-11:50 131.92 02-FEB-09:50
Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR2 0.03 0.00 28-JAN-00:30 131.92 02-FEB-09:50
General:Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR2 0.03 0.00 28-JAN-00:30 131.92 02-FEB-09:50
Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR2 0.00 0.00 01-JAN-00:10 0.23 06-FEB-12:50
General:Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR2 0.00 0.00 01-JAN-00:10 0.23 06-FEB-12:50
EnergyTransfer:Zone:REARSTAIRSFLR3 0.02 0.00 30-OCT-11:50 1.96 29-JAN-02:00
Heating:EnergyTransfer:Zone:REARSTAIRSFLR3 0.02 0.00 06-JAN-12:20 1.96 29-JAN-02:00
General:Heating:EnergyTransfer:Zone:REARSTAIRSFLR3 0.02 0.00 06-JAN-12:20 1.96 29-JAN-02:00
Cooling:EnergyTransfer:Zone:REARSTAIRSFLR3 0.00 0.00 01-JAN-00:10 0.37 29-JAN-13:50
General:Cooling:EnergyTransfer:Zone:REARSTAIRSFLR3 0.00 0.00 01-JAN-00:10 0.37 29-JAN-13:50
EnergyTransfer:Zone:CORRIDORFLR3 19.86 0.22 20-OCT-12:50 1882.20 02-FEB-08:30
Heating:EnergyTransfer:Zone:CORRIDORFLR3 8.27 0.00 08-FEB-13:10 1882.20 02-FEB-08:30
General:Heating:EnergyTransfer:Zone:CORRIDORFLR3 8.27 0.00 08-FEB-13:10 1882.20 02-FEB-08:30
Cooling:EnergyTransfer:Zone:CORRIDORFLR3 11.59 0.00 01-JAN-00:10 1413.43 15-JUL-19:00
General:Cooling:EnergyTransfer:Zone:CORRIDORFLR3 11.59 0.00 01-JAN-00:10 1413.43 15-JUL-19:00
EnergyTransfer:Zone:REARSTORAGEFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:REARSTORAGEFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:REARSTORAGEFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:REARSTORAGEFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:REARSTORAGEFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:GUESTROOM301 0.96 0.00 01-JAN-00:10 542.56 02-FEB-09:30
Heating:EnergyTransfer:Zone:GUESTROOM301 0.86 0.00 01-JAN-00:10 542.56 02-FEB-09:30
General:Heating:EnergyTransfer:Zone:GUESTROOM301 0.86 0.00 01-JAN-00:10 542.56 02-FEB-09:30
Cooling:EnergyTransfer:Zone:GUESTROOM301 0.10 0.00 01-JAN-00:10 274.96 21-NOV-15:30
General:Cooling:EnergyTransfer:Zone:GUESTROOM301 0.10 0.00 01-JAN-00:10 274.96 21-NOV-15:30
EnergyTransfer:Zone:GUESTROOM302_305 0.78 0.00 01-JAN-00:10 1663.61 25-NOV-15:10
Heating:EnergyTransfer:Zone:GUESTROOM302_305 0.14 0.00 01-JAN-00:10 516.51 06-SEP-14:10
General:Heating:EnergyTransfer:Zone:GUESTROOM302_305 0.14 0.00 01-JAN-00:10 516.51 06-SEP-14:10
Cooling:EnergyTransfer:Zone:GUESTROOM302_305 0.64 0.00 01-JAN-00:10 1663.61 25-NOV-15:10
General:Cooling:EnergyTransfer:Zone:GUESTROOM302_305 0.64 0.00 01-JAN-00:10 1663.61 25-NOV-15:10
EnergyTransfer:Zone:GUESTROOM306_308 0.62 0.00 01-JAN-00:10 1471.25 29-JAN-15:10
Heating:EnergyTransfer:Zone:GUESTROOM306_308 0.05 0.00 01-JAN-00:10 415.76 06-SEP-14:10
General:Heating:EnergyTransfer:Zone:GUESTROOM306_308 0.05 0.00 01-JAN-00:10 415.76 06-SEP-14:10
Cooling:EnergyTransfer:Zone:GUESTROOM306_308 0.57 0.00 01-JAN-00:10 1471.25 29-JAN-15:10
General:Cooling:EnergyTransfer:Zone:GUESTROOM306_308 0.57 0.00 01-JAN-00:10 1471.25 29-JAN-15:10
EnergyTransfer:Zone:GUESTROOM309_312 28.67 0.00 01-JAN-08:10 5945.48 23-JUL-18:10
Heating:EnergyTransfer:Zone:GUESTROOM309_312 1.91 0.00 01-JAN-00:10 2140.06 09-DEC-16:10
General:Heating:EnergyTransfer:Zone:GUESTROOM309_312 1.91 0.00 01-JAN-00:10 2140.06 09-DEC-16:10
Cooling:EnergyTransfer:Zone:GUESTROOM309_312 26.76 0.00 01-JAN-00:20 5945.48 23-JUL-18:10
General:Cooling:EnergyTransfer:Zone:GUESTROOM309_312 26.76 0.00 01-JAN-00:20 5945.48 23-JUL-18:10
EnergyTransfer:Zone:GUESTROOM313 0.31 0.00 01-JAN-00:10 335.00 24-NOV-15:10
Heating:EnergyTransfer:Zone:GUESTROOM313 0.20 0.00 01-JAN-00:10 280.15 02-FEB-09:30
General:Heating:EnergyTransfer:Zone:GUESTROOM313 0.20 0.00 01-JAN-00:10 280.15 02-FEB-09:30
Cooling:EnergyTransfer:Zone:GUESTROOM313 0.11 0.00 01-JAN-00:10 335.00 24-NOV-15:10
General:Cooling:EnergyTransfer:Zone:GUESTROOM313 0.11 0.00 01-JAN-00:10 335.00 24-NOV-15:10
EnergyTransfer:Zone:GUESTROOM314 9.91 0.00 01-JAN-08:10 1566.96 15-JUL-21:30
Heating:EnergyTransfer:Zone:GUESTROOM314 1.78 0.00 01-JAN-08:10 927.59 09-DEC-16:20
General:Heating:EnergyTransfer:Zone:GUESTROOM314 1.78 0.00 01-JAN-08:10 927.59 09-DEC-16:20
Cooling:EnergyTransfer:Zone:GUESTROOM314 8.13 0.00 01-JAN-00:10 1566.96 15-JUL-21:30
General:Cooling:EnergyTransfer:Zone:GUESTROOM314 8.13 0.00 01-JAN-00:10 1566.96 15-JUL-21:30
EnergyTransfer:Zone:GUESTROOM315_318 53.14 0.00 01-JAN-08:10 6715.05 02-JUL-08:10
Heating:EnergyTransfer:Zone:GUESTROOM315_318 0.16 0.00 01-JAN-00:10 534.08 11-DEC-09:10
General:Heating:EnergyTransfer:Zone:GUESTROOM315_318 0.16 0.00 01-JAN-00:10 534.08 11-DEC-09:10
Cooling:EnergyTransfer:Zone:GUESTROOM315_318 52.98 0.00 01-JAN-08:10 6715.05 02-JUL-08:10
General:Cooling:EnergyTransfer:Zone:GUESTROOM315_318 52.98 0.00 01-JAN-08:10 6715.05 02-JUL-08:10
EnergyTransfer:Zone:ELEVATORCOREFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ELEVATORCOREFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ELEVATORCOREFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:GUESTROOM319 0.27 0.00 01-JAN-00:10 623.98 02-FEB-15:40
Heating:EnergyTransfer:Zone:GUESTROOM319 0.01 0.00 01-JAN-00:10 124.65 15-APR-14:10
General:Heating:EnergyTransfer:Zone:GUESTROOM319 0.01 0.00 01-JAN-00:10 124.65 15-APR-14:10
Cooling:EnergyTransfer:Zone:GUESTROOM319 0.26 0.00 01-JAN-00:10 623.98 02-FEB-15:40
General:Cooling:EnergyTransfer:Zone:GUESTROOM319 0.26 0.00 01-JAN-00:10 623.98 02-FEB-15:40
EnergyTransfer:Zone:GUESTROOM320_323 29.19 0.00 01-JAN-08:10 5472.59 20-JUN-20:30
Heating:EnergyTransfer:Zone:GUESTROOM320_323 0.94 0.00 01-JAN-00:10 1768.69 09-DEC-16:10
General:Heating:EnergyTransfer:Zone:GUESTROOM320_323 0.94 0.00 01-JAN-00:10 1768.69 09-DEC-16:10
Cooling:EnergyTransfer:Zone:GUESTROOM320_323 28.25 0.00 01-JAN-08:10 5472.59 20-JUN-20:30
General:Cooling:EnergyTransfer:Zone:GUESTROOM320_323 28.25 0.00 01-JAN-08:10 5472.59 20-JUN-20:30
EnergyTransfer:Zone:GUESTROOM324 0.17 0.00 01-JAN-00:10 439.81 25-NOV-15:20
Heating:EnergyTransfer:Zone:GUESTROOM324 0.03 0.00 01-JAN-00:10 177.80 04-AUG-14:50
General:Heating:EnergyTransfer:Zone:GUESTROOM324 0.03 0.00 01-JAN-00:10 177.80 04-AUG-14:50
Cooling:EnergyTransfer:Zone:GUESTROOM324 0.14 0.00 01-JAN-00:10 439.81 25-NOV-15:20
General:Cooling:EnergyTransfer:Zone:GUESTROOM324 0.14 0.00 01-JAN-00:10 439.81 25-NOV-15:20
EnergyTransfer:Zone:FRONTSTORAGEFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:FRONTSTAIRSFLR3 0.08 0.00 28-JAN-00:20 250.70 02-FEB-09:50
Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR3 0.08 0.00 28-JAN-00:20 250.70 02-FEB-09:50
General:Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR3 0.08 0.00 28-JAN-00:20 250.70 02-FEB-09:50
Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR3 0.00 0.00 01-JAN-00:10 0.28 06-FEB-12:40
General:Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR3 0.00 0.00 01-JAN-00:10 0.28 06-FEB-12:40
EnergyTransfer:Zone:REARSTAIRSFLR4 0.12 0.00 14-JUL-11:10 307.78 09-DEC-02:00
Heating:EnergyTransfer:Zone:REARSTAIRSFLR4 0.12 0.00 01-JAN-12:00 307.78 09-DEC-02:00
General:Heating:EnergyTransfer:Zone:REARSTAIRSFLR4 0.12 0.00 01-JAN-12:00 307.78 09-DEC-02:00
Cooling:EnergyTransfer:Zone:REARSTAIRSFLR4 0.00 0.00 01-JAN-00:10 1.70 20-OCT-10:50
General:Cooling:EnergyTransfer:Zone:REARSTAIRSFLR4 0.00 0.00 01-JAN-00:10 1.70 20-OCT-10:50
EnergyTransfer:Zone:CORRIDORFLR4 31.84 0.11 20-MAR-19:20 3525.98 03-FEB-09:10
Heating:EnergyTransfer:Zone:CORRIDORFLR4 21.74 0.00 20-FEB-15:30 3525.98 03-FEB-09:10
General:Heating:EnergyTransfer:Zone:CORRIDORFLR4 21.74 0.00 20-FEB-15:30 3525.98 03-FEB-09:10
Cooling:EnergyTransfer:Zone:CORRIDORFLR4 10.10 0.00 01-JAN-00:10 2203.04 07-SEP-13:30
General:Cooling:EnergyTransfer:Zone:CORRIDORFLR4 10.10 0.00 01-JAN-00:10 2203.04 07-SEP-13:30
EnergyTransfer:Zone:REARSTORAGEFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:REARSTORAGEFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:REARSTORAGEFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:REARSTORAGEFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:REARSTORAGEFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:GUESTROOM401 14.93 0.00 01-JAN-08:10 2248.33 23-JUL-18:10
Heating:EnergyTransfer:Zone:GUESTROOM401 9.21 0.00 01-JAN-08:10 1824.30 09-DEC-16:10
General:Heating:EnergyTransfer:Zone:GUESTROOM401 9.21 0.00 01-JAN-08:10 1824.30 09-DEC-16:10
Cooling:EnergyTransfer:Zone:GUESTROOM401 5.72 0.00 01-JAN-00:10 2248.33 23-JUL-18:10
General:Cooling:EnergyTransfer:Zone:GUESTROOM401 5.72 0.00 01-JAN-00:10 2248.33 23-JUL-18:10
EnergyTransfer:Zone:GUESTROOM402_405 5.57 0.00 01-JAN-10:00 2076.74 02-FEB-07:30
Heating:EnergyTransfer:Zone:GUESTROOM402_405 3.80 0.00 01-JAN-10:00 2076.74 02-FEB-07:30
General:Heating:EnergyTransfer:Zone:GUESTROOM402_405 3.80 0.00 01-JAN-10:00 2076.74 02-FEB-07:30
Cooling:EnergyTransfer:Zone:GUESTROOM402_405 1.76 0.00 01-JAN-00:10 1616.93 05-JUL-17:00
General:Cooling:EnergyTransfer:Zone:GUESTROOM402_405 1.76 0.00 01-JAN-00:10 1616.93 05-JUL-17:00
EnergyTransfer:Zone:GUESTROOM406_408 4.17 0.00 01-JAN-00:10 1618.57 02-FEB-07:30
Heating:EnergyTransfer:Zone:GUESTROOM406_408 2.52 0.00 01-JAN-00:10 1618.57 02-FEB-07:30
General:Heating:EnergyTransfer:Zone:GUESTROOM406_408 2.52 0.00 01-JAN-00:10 1618.57 02-FEB-07:30
Cooling:EnergyTransfer:Zone:GUESTROOM406_408 1.66 0.00 01-JAN-00:10 1467.65 05-JUL-17:00
General:Cooling:EnergyTransfer:Zone:GUESTROOM406_408 1.66 0.00 01-JAN-00:10 1467.65 05-JUL-17:00
EnergyTransfer:Zone:GUESTROOM409_412 30.45 0.00 01-JAN-08:10 7970.81 23-JUL-18:10
Heating:EnergyTransfer:Zone:GUESTROOM409_412 7.46 0.00 01-JAN-08:10 3510.82 09-DEC-16:10
General:Heating:EnergyTransfer:Zone:GUESTROOM409_412 7.46 0.00 01-JAN-08:10 3510.82 09-DEC-16:10
Cooling:EnergyTransfer:Zone:GUESTROOM409_412 23.00 0.00 01-JAN-00:10 7970.81 23-JUL-18:10
General:Cooling:EnergyTransfer:Zone:GUESTROOM409_412 23.00 0.00 01-JAN-00:10 7970.81 23-JUL-18:10
EnergyTransfer:Zone:GUESTROOM413 2.01 0.00 01-JAN-10:20 852.59 02-FEB-07:30
Heating:EnergyTransfer:Zone:GUESTROOM413 1.69 0.00 01-JAN-10:20 852.59 02-FEB-07:30
General:Heating:EnergyTransfer:Zone:GUESTROOM413 1.69 0.00 01-JAN-10:20 852.59 02-FEB-07:30
Cooling:EnergyTransfer:Zone:GUESTROOM413 0.32 0.00 01-JAN-00:10 384.81 05-JUL-17:30
General:Cooling:EnergyTransfer:Zone:GUESTROOM413 0.32 0.00 01-JAN-00:10 384.81 05-JUL-17:30
EnergyTransfer:Zone:GUESTROOM414 0.88 0.00 01-JAN-00:10 554.34 02-FEB-07:30
Heating:EnergyTransfer:Zone:GUESTROOM414 0.62 0.00 01-JAN-00:10 554.34 02-FEB-07:30
General:Heating:EnergyTransfer:Zone:GUESTROOM414 0.62 0.00 01-JAN-00:10 554.34 02-FEB-07:30
Cooling:EnergyTransfer:Zone:GUESTROOM414 0.26 0.00 01-JAN-00:10 316.82 05-MAR-15:40
General:Cooling:EnergyTransfer:Zone:GUESTROOM414 0.26 0.00 01-JAN-00:10 316.82 05-MAR-15:40
EnergyTransfer:Zone:GUESTROOM415_418 31.60 0.00 01-JAN-08:10 7262.48 31-MAY-09:00
Heating:EnergyTransfer:Zone:GUESTROOM415_418 3.78 0.00 01-JAN-07:20 3043.61 09-DEC-16:10
General:Heating:EnergyTransfer:Zone:GUESTROOM415_418 3.78 0.00 01-JAN-07:20 3043.61 09-DEC-16:10
Cooling:EnergyTransfer:Zone:GUESTROOM415_418 27.82 0.00 01-JAN-00:10 7262.48 31-MAY-09:00
General:Cooling:EnergyTransfer:Zone:GUESTROOM415_418 27.82 0.00 01-JAN-00:10 7262.48 31-MAY-09:00
EnergyTransfer:Zone:ELEVATORCOREFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ELEVATORCOREFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ELEVATORCOREFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:GUESTROOM419 9.50 0.00 01-JAN-08:10 1956.33 31-MAY-09:00
Heating:EnergyTransfer:Zone:GUESTROOM419 1.27 0.00 01-JAN-07:50 903.28 09-DEC-16:10
General:Heating:EnergyTransfer:Zone:GUESTROOM419 1.27 0.00 01-JAN-07:50 903.28 09-DEC-16:10
Cooling:EnergyTransfer:Zone:GUESTROOM419 8.23 0.00 01-JAN-00:10 1956.33 31-MAY-09:00
General:Cooling:EnergyTransfer:Zone:GUESTROOM419 8.23 0.00 01-JAN-00:10 1956.33 31-MAY-09:00
EnergyTransfer:Zone:GUESTROOM420_423 27.81 0.00 01-JAN-08:10 6534.76 31-MAY-09:00
Heating:EnergyTransfer:Zone:GUESTROOM420_423 3.53 0.00 01-JAN-07:20 2912.07 09-DEC-16:10
General:Heating:EnergyTransfer:Zone:GUESTROOM420_423 3.53 0.00 01-JAN-07:20 2912.07 09-DEC-16:10
Cooling:EnergyTransfer:Zone:GUESTROOM420_423 24.29 0.00 01-JAN-00:10 6534.76 31-MAY-09:00
General:Cooling:EnergyTransfer:Zone:GUESTROOM420_423 24.29 0.00 01-JAN-00:10 6534.76 31-MAY-09:00
EnergyTransfer:Zone:GUESTROOM424 10.11 0.00 01-JAN-08:10 1825.99 28-JUN-09:00
Heating:EnergyTransfer:Zone:GUESTROOM424 3.88 0.00 01-JAN-08:10 1295.77 09-DEC-16:10
General:Heating:EnergyTransfer:Zone:GUESTROOM424 3.88 0.00 01-JAN-08:10 1295.77 09-DEC-16:10
Cooling:EnergyTransfer:Zone:GUESTROOM424 6.23 0.00 01-JAN-00:10 1825.99 28-JUN-09:00
General:Cooling:EnergyTransfer:Zone:GUESTROOM424 6.23 0.00 01-JAN-00:10 1825.99 28-JUN-09:00
EnergyTransfer:Zone:FRONTSTORAGEFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:FRONTSTAIRSFLR4 0.51 0.00 26-JUN-12:10 606.94 02-FEB-08:00
Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR4 0.51 0.00 08-JAN-12:00 606.94 02-FEB-08:00
General:Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR4 0.51 0.00 08-JAN-12:00 606.94 02-FEB-08:00
Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR4 0.00 0.00 01-JAN-00:10 1.81 05-SEP-10:50
General:Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR4 0.00 0.00 01-JAN-00:10 1.81 05-SEP-10:50
PlantLoopHeatingDemand:Facility 657.38 3072.40 21-AUG-02:30 64125.41 18-FEB-09:00
PlantLoopHeatingDemand:Plant 657.38 3072.40 21-AUG-02:30 64125.41 18-FEB-09:00
WaterSystems:PlantLoopHeatingDemand 657.38 3072.40 21-AUG-02:30 64125.41 18-FEB-09:00
General:WaterSystems:PlantLoopHeatingDemand 657.38 3072.40 21-AUG-02:30 64125.41 18-FEB-09:00
EnergyTransfer:HVAC 1287.86 4550.78 27-APR-07:10 190322.92 02-AUG-09:00
HeatingCoils:EnergyTransfer 353.15 0.00 18-MAR-16:10 172773.79 02-FEB-07:10
CoolingCoils:EnergyTransfer 934.72 0.00 05-JAN-24:00 190322.92 02-AUG-09:00
EnergyTransfer:Plant 657.34 3072.40 21-AUG-02:30 64121.08 18-FEB-09:00
WaterSystems:EnergyTransfer 657.34 3072.40 21-AUG-02:30 64121.08 18-FEB-09:00
WaterUse:WaterSystems:EnergyTransfer 657.34 3072.40 21-AUG-02:30 64121.08 18-FEB-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
REARSTAIRSFLR1 0.018 -0.000 0.000 0.000 0.000 0.000 0.000 3.339 0.000 0.000 0.000 0.017 0.000 0.000 0.000 0.000 -1.743 -1.630
CORRIDORFLR1 39.244 -82.519 0.000 0.000 0.000 0.000 0.000 15.710 0.000 4.767 0.000 1.843 126.779 0.000 -7.264 0.000 -98.560 0.000
FRONTLOUNGEFLR1 0.000 0.000 0.517 -61.611 0.000 0.000 33.538 12.269 50.363 11.845 0.000 0.017 0.000 0.000 -9.786 0.000 -1.393 -35.760
RESTROOMFLR1 0.000 0.000 1.107 -3.668 0.000 0.000 1.063 3.836 0.000 0.000 0.000 0.002 0.000 0.000 0.000 0.000 -0.206 -2.135
MEETINGROOMFLR1 0.000 0.000 0.678 -15.568 0.000 0.000 7.445 8.454 2.117 3.912 0.000 0.006 0.000 0.000 -3.417 0.000 -0.480 -3.146
MECHANICALROOMFLR1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.190 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.227 -0.963
GUESTROOM101 0.024 -0.174 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.279 0.000 0.001 0.197 0.000 -1.133 0.000 -0.194 -0.000
GUESTROOM102 0.025 -0.179 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.297 0.000 0.002 0.138 0.000 -1.095 0.000 -0.187 -0.000
GUESTROOM103 2.007 -6.799 0.000 0.000 0.000 0.000 2.459 1.290 4.205 1.332 0.000 0.004 0.000 0.000 -1.050 0.000 -0.218 -3.230
GUESTROOM104 0.613 -8.601 0.000 0.000 0.000 0.000 2.452 1.290 4.204 1.268 0.000 0.004 0.039 0.000 -1.046 0.000 -0.223 -0.000
GUESTROOM105 0.086 -19.345 0.000 0.000 0.000 0.000 2.420 1.290 4.204 1.230 0.000 0.004 11.460 0.000 -1.135 0.000 -0.216 0.000
EMPLOYEELOUNGEFLR1 0.000 0.000 0.000 -69.531 0.000 0.000 4.329 3.279 9.572 1.129 0.000 0.002 52.830 0.000 -1.401 0.000 -0.210 0.000
EXERCISECENTERFLR1 0.000 0.000 0.051 -22.638 0.000 0.000 10.456 6.641 8.364 1.262 0.000 0.002 0.000 0.000 -1.086 0.000 -0.191 -2.863
FRONTOFFICEFLR1 0.000 0.000 0.297 -30.013 0.000 0.000 9.447 11.337 29.444 5.038 0.000 0.010 0.000 0.000 -4.280 0.000 -0.785 -20.495
FRONTSTAIRSFLR1 0.019 -0.000 0.000 0.000 0.000 0.000 0.000 3.338 0.000 0.000 0.000 0.018 0.000 0.000 0.000 0.000 -1.593 -1.782
REARSTAIRSFLR2 0.018 -0.000 0.000 0.000 0.000 0.000 0.000 3.339 0.000 0.000 0.000 0.009 0.000 0.000 0.000 0.000 -1.848 -1.518
CORRIDORFLR2 0.138 -25.890 0.000 0.000 0.000 0.000 0.000 13.091 0.000 1.558 0.000 0.017 14.284 0.000 -1.830 0.000 -1.369 0.000
GUESTROOM201 0.173 -0.144 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.302 0.000 0.003 0.246 0.000 -1.028 0.000 -0.553 -0.000
GUESTROOM202_205 2.530 -32.238 0.000 0.000 0.000 0.000 9.743 5.161 16.818 5.264 0.000 0.016 0.000 0.000 -4.304 0.000 -0.799 -2.192
GUESTROOM206_208 1.235 -26.938 0.000 0.000 0.000 0.000 7.299 4.168 13.584 5.333 0.000 0.013 0.384 0.000 -4.425 0.000 -0.652 -0.000
GUESTROOM209_212 0.688 -31.749 0.000 0.000 0.000 0.000 9.735 5.161 16.818 5.273 0.000 0.016 0.000 0.000 -4.354 0.000 -0.805 -0.782
GUESTROOM213 2.304 -6.491 0.000 0.000 0.000 0.000 2.454 1.290 4.205 1.330 0.000 0.004 0.000 0.000 -1.056 0.000 -0.226 -3.814
GUESTROOM214 0.280 -11.428 0.000 0.000 0.000 0.000 2.435 1.290 4.204 1.252 0.000 0.005 3.273 0.000 -1.082 0.000 -0.228 -0.000
GUESTROOM215_218 0.000 -57.701 0.000 0.000 0.000 0.000 0.000 0.000 0.000 4.402 0.000 0.003 60.132 0.000 -5.847 0.000 -0.988 0.000
GUESTROOM219 0.033 -75.099 0.000 0.000 0.000 0.000 2.347 1.290 4.204 1.119 0.000 0.005 67.704 0.000 -1.395 0.000 -0.208 0.000
GUESTROOM220_223 0.392 -34.010 0.000 0.000 0.000 0.000 9.752 5.160 16.817 5.059 0.000 0.017 1.880 0.000 -4.252 0.000 -0.815 -0.000
GUESTROOM224 1.000 -8.351 0.000 0.000 0.000 0.000 2.449 1.290 4.204 1.264 0.000 0.005 0.000 0.000 -1.048 0.000 -0.231 -0.582
FRONTSTAIRSFLR2 0.025 -0.000 0.000 0.000 0.000 0.000 0.000 3.338 0.000 0.000 0.000 0.011 0.000 0.000 0.000 0.000 -1.645 -1.729
REARSTAIRSFLR3 0.018 -0.000 0.000 0.000 0.000 0.000 0.000 3.339 0.000 0.000 0.000 0.008 0.000 0.000 0.000 0.000 -1.965 -1.400
CORRIDORFLR3 8.268 -11.588 0.000 0.000 0.000 0.000 0.000 13.091 0.000 1.600 0.000 0.018 0.000 0.000 -1.738 0.000 -1.472 -8.179
GUESTROOM301 0.859 -0.101 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.321 0.000 0.004 0.000 0.000 -0.971 0.000 -0.578 -0.534
GUESTROOM302_305 0.138 -0.641 0.000 0.000 0.000 0.000 0.000 0.000 0.000 5.236 0.000 0.005 0.135 0.000 -4.081 0.000 -0.792 -0.000
GUESTROOM306_308 0.051 -0.568 0.000 0.000 0.000 0.000 0.000 0.000 0.000 5.302 0.000 0.004 0.086 0.000 -4.224 0.000 -0.651 -0.000
GUESTROOM309_312 1.909 -26.755 0.000 0.000 0.000 0.000 9.766 5.161 16.818 5.290 0.000 0.018 0.000 0.000 -4.275 0.000 -0.889 -7.043
GUESTROOM313 0.202 -0.107 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.321 0.000 0.002 0.000 0.000 -0.999 0.000 -0.193 -0.227
GUESTROOM314 1.775 -8.132 0.000 0.000 0.000 0.000 2.451 1.290 4.204 1.263 0.000 0.005 0.000 0.000 -1.038 0.000 -0.252 -1.567
GUESTROOM315_318 0.163 -52.980 0.000 0.000 0.000 0.000 9.688 5.160 16.817 4.949 0.000 0.018 21.526 0.000 -4.444 0.000 -0.897 0.000
GUESTROOM319 0.007 -0.261 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.186 0.000 0.001 0.494 0.000 -1.191 0.000 -0.236 0.000
GUESTROOM320_323 0.943 -28.246 0.000 0.000 0.000 0.000 9.780 5.160 16.817 5.074 0.000 0.018 0.000 0.000 -4.173 0.000 -0.900 -4.473
GUESTROOM324 0.027 -0.143 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.252 0.000 0.002 0.078 0.000 -1.014 0.000 -0.202 -0.000
FRONTSTAIRSFLR3 0.077 -0.000 0.000 0.000 0.000 0.000 0.000 3.338 0.000 0.000 0.000 0.010 0.000 0.000 0.000 0.000 -1.746 -1.679
REARSTAIRSFLR4 0.117 -0.002 0.000 0.000 0.000 0.000 0.000 3.339 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -1.927 -1.528
CORRIDORFLR4 21.742 -10.096 0.000 0.000 0.000 0.000 0.000 13.091 0.000 1.602 0.000 0.020 0.000 0.000 -1.675 0.000 -1.567 -23.117
GUESTROOM401 9.209 -5.722 0.000 0.000 0.000 0.000 2.458 1.290 4.205 1.326 0.000 0.015 0.000 0.000 -0.995 0.000 -0.721 -11.065
GUESTROOM402_405 3.805 -1.764 0.000 0.000 0.000 0.000 0.000 0.000 0.000 5.203 0.000 0.004 0.000 0.000 -3.754 0.000 -0.805 -2.689
GUESTROOM406_408 2.517 -1.656 0.000 0.000 0.000 0.000 0.000 0.000 0.000 5.264 0.000 0.003 0.000 0.000 -3.864 0.000 -0.657 -1.606
GUESTROOM409_412 7.455 -22.996 0.000 0.000 0.000 0.000 9.763 5.161 16.818 5.246 0.000 0.019 0.000 0.000 -4.128 0.000 -0.938 -16.398
GUESTROOM413 1.692 -0.321 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.314 0.000 0.001 0.000 0.000 -0.932 0.000 -0.198 -1.555
GUESTROOM414 0.620 -0.262 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.243 0.000 0.001 0.000 0.000 -0.948 0.000 -0.207 -0.446
GUESTROOM415_418 3.779 -27.817 0.000 0.000 0.000 0.000 9.766 5.160 16.817 5.004 0.000 0.020 0.000 0.000 -4.099 0.000 -0.952 -7.678
GUESTROOM419 1.274 -8.225 0.000 0.000 0.000 0.000 2.443 1.290 4.204 1.246 0.000 0.005 0.000 0.000 -1.042 0.000 -0.265 -0.930
GUESTROOM420_423 3.526 -24.284 0.000 0.000 0.000 0.000 9.782 5.160 16.817 5.037 0.000 0.020 0.000 0.000 -4.055 0.000 -0.954 -11.048
GUESTROOM424 3.878 -6.229 0.000 0.000 0.000 0.000 2.457 1.290 4.204 1.264 0.000 0.005 0.000 0.000 -1.000 0.000 -0.267 -5.604
FRONTSTAIRSFLR4 0.512 -0.001 0.000 0.000 0.000 0.000 0.000 3.338 0.000 0.000 0.000 0.004 0.000 0.000 0.000 0.000 -1.745 -2.108
REARSTORAGEFLR1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.283 0.000 0.000 0.000 0.026 1.328 0.000 0.000 0.000 -1.637 0.000
LAUNDRYROOMFLR1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 4.099 449.967 1.863 0.000 0.000 0.001 0.000 -10.180 0.000 -2.004 -443.745
ELEVATORCOREFLR1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 131.937 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1.152 -130.785
FRONTSTORAGEFLR1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.177 0.000 0.000 0.000 0.002 0.090 0.000 0.000 0.000 -0.269 -0.000
REARSTORAGEFLR2 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.283 0.000 0.000 0.000 0.017 1.370 0.000 0.000 0.000 -1.670 0.000
ELEVATORCOREFLR2 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.539 0.000 0.000 0.000 -0.539 0.000
FRONTSTORAGEFLR2 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.177 0.000 0.000 0.000 0.002 0.089 0.000 0.000 0.000 -0.269 -0.000
REARSTORAGEFLR3 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.283 0.000 0.000 0.000 0.015 1.436 0.000 0.000 0.000 -1.734 0.000
ELEVATORCOREFLR3 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.001 0.433 0.000 0.000 0.000 -0.434 0.000
FRONTSTORAGEFLR3 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.177 0.000 0.000 0.000 0.002 0.105 0.000 0.000 0.000 -0.284 -0.000
REARSTORAGEFLR4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.283 0.000 0.000 0.000 0.005 1.424 0.000 0.000 0.000 -1.713 0.000
ELEVATORCOREFLR4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.002 0.408 0.000 0.000 0.000 -0.410 0.000
FRONTSTORAGEFLR4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.177 0.000 0.000 0.000 0.002 0.113 0.000 0.000 0.000 -0.292 -0.000
Total Facility 125.414 -666.553 2.650 -203.028 0.000 0.000 188.177 199.438 892.953 136.921 0.000 2.365 369.004 0.000 -128.137 0.000 -151.176 -768.026


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
REARSTAIRSFLR1 15-DEC-10:55 0.00 -0.43 0.00 0.00 0.00 0.00 0.00 105.87 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -69.13 -36.30
CORRIDORFLR1 04-AUG-16:02 0.00 -17392.51 0.00 0.00 0.00 0.00 0.00 498.16 0.00 731.49 0.00 9344.05 6818.81 0.00 -0.00 0.00 0.00 0.00
FRONTLOUNGEFLR1 03-AUG-08:53 0.00 0.00 0.00 -5910.30 0.00 0.00 2656.62 619.21 4249.25 683.85 0.00 10.41 0.00 0.00 -0.00 0.00 0.00 -2309.04
RESTROOMFLR1 15-NOV-09:01 0.00 0.00 0.00 -549.61 0.00 0.00 87.00 121.63 0.00 0.00 0.00 0.00 353.05 0.00 -0.00 0.00 -12.07 0.00
MEETINGROOMFLR1 30-JAN-17:51 0.00 0.00 0.00 -6104.67 0.00 0.00 0.00 838.14 114.44 0.00 0.00 0.00 5595.50 0.00 -409.50 0.00 -33.92 0.00
MECHANICALROOMFLR1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GUESTROOM101 02-FEB-15:25 0.00 -642.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 240.06 0.00 0.00 415.38 0.00 -0.00 0.00 -13.38 0.00
GUESTROOM102 02-FEB-15:25 0.00 -643.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 241.49 0.00 0.00 415.54 0.00 -0.00 0.00 -13.22 0.00
GUESTROOM103 20-SEP-17:01 0.00 -2610.12 0.00 0.00 0.00 0.00 51.83 66.49 197.81 265.49 0.00 0.00 2045.34 0.00 -0.00 0.00 -16.84 0.00
GUESTROOM104 25-NOV-09:01 0.00 -2974.29 0.00 0.00 0.00 0.00 36.27 55.57 240.46 168.68 0.00 0.00 2496.44 0.00 -0.00 0.00 -23.12 0.00
GUESTROOM105 07-JAN-09:01 0.00 -4263.53 0.00 0.00 0.00 0.00 33.45 55.57 240.46 184.18 0.00 0.00 3763.04 0.00 -0.00 0.00 -13.16 0.00
EMPLOYEELOUNGEFLR1 30-JAN-13:01 0.00 0.00 0.00 -6701.06 0.00 0.00 222.98 207.09 578.13 0.00 0.00 0.00 5811.35 0.00 -98.04 0.00 -20.45 0.00
EXERCISECENTERFLR1 30-JAN-23:01 0.00 0.00 0.00 -4033.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4188.97 0.00 -141.20 0.00 -14.44 0.00
FRONTOFFICEFLR1 04-FEB-09:22 0.00 0.00 0.00 -2960.18 0.00 0.00 422.57 292.34 1048.29 769.88 0.00 0.00 477.43 0.00 -0.00 0.00 -50.33 0.00
FRONTSTAIRSFLR1 06-FEB-12:40 0.00 -0.17 0.00 0.00 0.00 0.00 0.00 105.84 0.00 0.00 0.00 0.00 13.75 0.00 -0.00 0.00 -119.42 0.00
REARSTAIRSFLR2 01-DEC-10:55 0.00 -0.60 0.00 0.00 0.00 0.00 0.00 105.87 0.00 0.00 0.00 0.00 0.28 0.00 -0.00 0.00 -105.55 0.00
CORRIDORFLR2 15-JUL-19:01 0.00 -2146.34 0.00 0.00 0.00 0.00 0.00 415.13 0.00 22.42 0.00 0.00 1712.12 0.00 -0.00 0.00 -3.32 0.00
GUESTROOM201 25-NOV-15:13 0.00 -417.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 164.14 0.00 0.00 320.52 0.00 -0.00 0.00 -66.67 0.00
GUESTROOM202_205 21-MAY-17:01 0.00 -10727.73 0.00 0.00 0.00 0.00 196.87 337.39 791.24 1757.60 0.00 0.00 7652.84 0.00 -0.00 0.00 -8.21 0.00
GUESTROOM206_208 21-MAY-17:01 0.00 -8940.09 0.00 0.00 0.00 0.00 147.65 272.51 639.08 1782.94 0.00 0.00 6104.53 0.00 -0.00 0.00 -6.62 0.00
GUESTROOM209_212 15-JAN-09:01 0.00 -10489.73 0.00 0.00 0.00 0.00 142.02 222.28 961.90 0.00 0.00 0.00 9518.99 0.00 -301.96 0.00 -53.50 0.00
GUESTROOM213 06-MAY-16:51 0.00 -2651.51 0.00 0.00 0.00 0.00 49.94 32.75 166.78 392.18 0.00 0.00 2013.18 0.00 -0.00 0.00 -3.32 0.00
GUESTROOM214 25-NOV-09:01 0.00 -3095.43 0.00 0.00 0.00 0.00 35.75 55.57 240.46 167.29 0.00 0.00 2620.18 0.00 -0.00 0.00 -23.82 0.00
GUESTROOM215_218 29-JUN-16:22 0.00 -4079.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 263.02 0.00 3.67 3812.55 0.00 -0.00 0.00 0.00 0.00
GUESTROOM219 04-FEB-10:31 0.00 -13329.01 0.00 0.00 0.00 0.00 15.88 40.68 112.47 70.28 0.00 0.00 13109.07 0.00 -0.00 0.00 -19.38 0.00
GUESTROOM220_223 26-NOV-09:01 0.00 -11335.98 0.00 0.00 0.00 0.00 142.37 222.27 961.83 221.72 0.00 0.00 9824.66 0.00 -0.00 0.00 -36.86 0.00
GUESTROOM224 06-MAY-16:51 0.00 -2828.60 0.00 0.00 0.00 0.00 50.85 32.75 166.77 18.91 0.00 0.00 2593.37 0.00 -0.00 0.00 -34.04 0.00
FRONTSTAIRSFLR2 06-FEB-12:50 0.00 -0.23 0.00 0.00 0.00 0.00 0.00 105.84 0.00 0.00 0.00 0.00 4.89 0.00 -0.00 0.00 -110.50 0.00
REARSTAIRSFLR3 01-DEC-10:55 0.00 -0.55 0.00 0.00 0.00 0.00 0.00 105.87 0.00 0.00 0.00 0.00 4.47 0.00 -0.00 0.00 -109.79 0.00
CORRIDORFLR3 15-JUL-18:52 0.00 -1414.68 0.00 0.00 0.00 0.00 0.00 415.13 0.00 39.00 0.00 0.00 963.70 0.00 -0.00 0.00 -3.15 0.00
GUESTROOM301 05-MAR-15:03 0.00 -306.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 331.54 0.00 0.00 37.00 0.00 -0.00 0.00 -62.02 0.00
GUESTROOM302_305 01-FEB-15:02 0.00 -2275.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 785.11 0.00 0.00 1563.34 0.00 -0.00 0.00 -73.03 0.00
GUESTROOM306_308 02-FEB-15:02 0.00 -1909.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 910.49 0.00 0.00 1047.68 0.00 -0.00 0.00 -48.77 0.00
GUESTROOM309_312 21-MAY-17:01 0.00 -9437.50 0.00 0.00 0.00 0.00 196.87 337.39 791.24 1754.21 0.00 0.00 6367.00 0.00 -0.00 0.00 -9.21 0.00
GUESTROOM313 25-NOV-15:13 0.00 -436.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 163.42 0.00 0.00 297.18 0.00 -0.00 0.00 -23.97 0.00
GUESTROOM314 06-MAY-16:51 0.00 -2634.66 0.00 0.00 0.00 0.00 49.15 32.75 166.77 17.78 0.00 0.00 2372.01 0.00 -0.00 0.00 -3.79 0.00
GUESTROOM315_318 07-JAN-09:01 0.00 -12838.05 0.00 0.00 0.00 0.00 135.60 222.27 961.83 743.83 0.00 0.00 10834.21 0.00 -0.00 0.00 -59.68 0.00
GUESTROOM319 02-FEB-15:25 0.00 -644.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 772.92 0.00 -112.49 0.00 -16.28 0.00
GUESTROOM320_323 25-NOV-09:01 0.00 -9864.48 0.00 0.00 0.00 0.00 142.85 222.27 961.83 677.12 0.00 0.00 7966.34 0.00 -0.00 0.00 -105.92 0.00
GUESTROOM324 02-FEB-15:02 0.00 -587.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 697.98 0.00 -95.74 0.00 -15.05 0.00
FRONTSTAIRSFLR3 06-FEB-12:40 0.00 -0.28 0.00 0.00 0.00 0.00 0.00 105.84 0.00 0.00 0.00 0.00 21.79 0.00 -0.00 0.00 -127.35 0.00
REARSTAIRSFLR4 15-SEP-10:45 0.00 -2.37 0.00 0.00 0.00 0.00 0.00 105.87 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -7.69 -95.80
CORRIDORFLR4 07-SEP-13:30 0.00 -2202.96 0.00 0.00 0.00 0.00 0.00 415.13 0.00 366.64 0.00 5.86 1415.33 0.00 -0.00 0.00 0.00 0.00
GUESTROOM401 21-MAY-18:01 0.00 -3354.90 0.00 0.00 0.00 0.00 48.42 99.23 190.05 296.89 0.00 0.00 2728.18 0.00 -0.00 0.00 -7.88 0.00
GUESTROOM402_405 05-JUL-16:54 0.00 -1617.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1821.64 0.00 0.00 0.00 0.00 -0.00 0.00 -0.02 -204.58
GUESTROOM406_408 05-JUL-16:54 0.00 -1467.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1851.43 0.00 0.00 0.00 0.00 -0.00 0.00 -0.02 -383.68
GUESTROOM409_412 20-MAY-17:21 0.00 -12706.98 0.00 0.00 0.00 0.00 142.15 337.39 791.24 1446.88 0.00 0.00 10004.10 0.00 -0.00 0.00 -14.78 0.00
GUESTROOM413 05-JUL-17:27 0.00 -384.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 435.18 0.00 0.00 0.00 0.00 -0.00 0.00 -0.01 -50.35
GUESTROOM414 05-FEB-15:03 0.00 -357.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 419.75 0.00 -51.87 0.00 -10.23 0.00
GUESTROOM415_418 15-SEP-16:21 0.00 -11948.97 0.00 0.00 0.00 0.00 176.55 111.13 791.18 83.10 0.00 0.00 10789.25 0.00 -0.00 0.00 -2.24 0.00
GUESTROOM419 22-JUN-16:21 0.00 -3177.66 0.00 0.00 0.00 0.00 44.05 27.78 197.80 51.64 0.00 0.00 2857.21 0.00 -0.00 0.00 -0.83 0.00
GUESTROOM420_423 21-MAY-16:51 0.00 -10865.32 0.00 0.00 0.00 0.00 193.23 130.98 667.07 61.63 0.00 0.00 9822.37 0.00 -0.00 0.00 -9.96 0.00
GUESTROOM424 21-MAY-16:51 0.00 -3073.95 0.00 0.00 0.00 0.00 48.51 32.75 166.77 16.07 0.00 0.00 2812.28 0.00 -0.00 0.00 -2.41 0.00
FRONTSTAIRSFLR4 05-SEP-10:45 0.00 -2.64 0.00 0.00 0.00 0.00 0.00 105.84 0.00 0.00 0.00 1.99 0.00 0.00 -0.00 0.00 0.00 -105.19
REARSTORAGEFLR1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 06-MAY-16:51 0.00 -156492.27 0.00 -9105.53 0.00 0.00 4070.68 6376.87 19473.11 23693.39 0.00 0.00 118688.87 0.00 -271.39 0.00 -6433.73 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
REARSTAIRSFLR1 29-JAN-02:00 1.82 0.00 0.00 0.00 0.00 0.00 0.00 105.87 0.00 0.00 0.00 0.00 136.54 0.00 -0.00 0.00 -244.23 0.00
CORRIDORFLR1 02-FEB-07:02 74891.22 0.00 0.00 0.00 0.00 0.00 0.00 498.16 0.00 0.00 0.00 0.00 2789.56 0.00 -985.50 0.00 -77193.44 0.00
FRONTLOUNGEFLR1 03-FEB-18:09 0.00 0.00 6495.43 0.00 0.00 0.00 895.85 737.15 977.33 0.00 0.00 0.00 0.00 0.00 -1224.38 0.00 -77.30 -7804.08
RESTROOMFLR1 03-FEB-05:00 0.00 0.00 149.18 0.00 0.00 0.00 14.83 121.63 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -8.53 -277.11
MEETINGROOMFLR1 30-JAN-17:57 0.00 0.00 9447.31 0.00 0.00 0.00 0.00 838.14 114.44 0.00 0.00 0.00 0.00 0.00 -409.50 0.00 -34.35 -9956.05
MECHANICALROOMFLR1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GUESTROOM101 04-AUG-14:05 166.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 296.35 0.00 1.52 0.00 0.00 -0.00 0.00 0.00 -464.68
GUESTROOM102 04-AUG-15:00 174.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 375.23 0.00 1.89 0.00 0.00 -0.00 0.00 0.00 -551.56
GUESTROOM103 11-MAR-16:01 1642.11 0.00 0.00 0.00 0.00 0.00 39.08 32.75 112.48 0.00 0.00 0.00 0.00 0.00 -20.77 0.00 -9.64 -1796.00
GUESTROOM104 04-MAR-16:01 1558.67 0.00 0.00 0.00 0.00 0.00 39.09 32.75 112.47 0.00 0.00 0.00 0.00 0.00 -33.91 0.00 -10.84 -1698.22
GUESTROOM105 24-MAR-08:03 1356.50 0.00 0.00 0.00 0.00 0.00 22.30 43.66 166.77 137.39 0.00 0.00 0.00 0.00 -0.00 0.00 -5.45 -1721.16
EMPLOYEELOUNGEFLR1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
EXERCISECENTERFLR1 06-MAR-03:37 0.00 0.00 4431.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -109.43 0.00 -15.23 -4306.51
FRONTOFFICEFLR1 04-FEB-09:24 0.00 0.00 4392.64 0.00 0.00 0.00 422.57 292.34 1048.29 769.88 0.00 0.00 0.00 0.00 -0.00 0.00 -50.68 -6875.04
FRONTSTAIRSFLR1 02-FEB-04:00 52.94 0.00 0.00 0.00 0.00 0.00 0.00 105.84 0.00 0.00 0.00 0.00 33.14 0.00 -0.00 0.00 -191.91 0.00
REARSTAIRSFLR2 29-JAN-02:00 1.84 0.00 0.00 0.00 0.00 0.00 0.00 105.87 0.00 0.00 0.00 0.00 142.35 0.00 -0.00 0.00 -250.05 0.00
CORRIDORFLR2 07-JAN-01:47 2177.08 0.00 0.00 0.00 0.00 0.00 0.00 415.13 0.00 0.00 0.00 0.00 0.00 0.00 -204.28 0.00 -68.33 -2319.60
GUESTROOM201 26-JAN-15:13 407.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -64.51 0.00 -63.28 -279.29
GUESTROOM202_205 06-APR-15:03 4618.35 0.00 0.00 0.00 0.00 0.00 248.14 111.14 403.38 1531.19 0.00 0.00 0.00 0.00 -0.00 0.00 -35.57 -6876.63
GUESTROOM206_208 31-MAR-15:03 3654.46 0.00 0.00 0.00 0.00 0.00 185.41 89.77 325.80 218.10 0.00 0.00 0.00 0.00 -0.00 0.00 -22.85 -4450.69
GUESTROOM209_212 14-NOV-16:03 4243.41 0.00 0.00 0.00 0.00 0.00 251.88 111.14 403.38 0.00 0.00 0.00 0.00 0.00 -53.84 0.00 -13.27 -4942.70
GUESTROOM213 07-FEB-16:01 1498.16 0.00 0.00 0.00 0.00 0.00 72.92 27.79 100.84 98.62 0.00 0.00 0.00 0.00 -0.00 0.00 -6.85 -1791.48
GUESTROOM214 01-APR-08:03 1398.91 0.00 0.00 0.00 0.00 0.00 33.44 55.57 240.46 0.00 0.00 0.00 0.00 0.00 -44.24 0.00 -8.58 -1675.56
GUESTROOM215_218 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GUESTROOM219 12-JUL-19:42 1225.68 0.00 0.00 0.00 0.00 0.00 28.23 99.23 255.97 0.00 0.00 0.00 0.00 0.00 -38.50 0.00 -0.88 -1569.73
GUESTROOM220_223 02-DEC-16:03 4261.08 0.00 0.00 0.00 0.00 0.00 139.65 130.98 449.89 0.00 0.00 0.00 0.00 0.00 -185.25 0.00 -14.12 -4782.23
GUESTROOM224 25-APR-15:03 1388.35 0.00 0.00 0.00 0.00 0.00 61.21 27.78 100.84 16.84 0.00 0.00 0.00 0.00 -0.00 0.00 -12.28 -1582.74
FRONTSTAIRSFLR2 02-FEB-09:43 131.92 0.00 0.00 0.00 0.00 0.00 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -184.38 -53.38
REARSTAIRSFLR3 29-JAN-02:00 1.96 0.00 0.00 0.00 0.00 0.00 0.00 105.87 0.00 0.00 0.00 0.00 155.54 0.00 -0.00 0.00 -263.37 0.00
CORRIDORFLR3 02-FEB-08:11 1886.40 0.00 0.00 0.00 0.00 0.00 0.00 415.13 0.00 0.00 0.00 0.00 0.00 0.00 -197.98 0.00 -140.78 -1962.77
GUESTROOM301 02-FEB-09:23 542.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -112.24 0.00 -66.77 -363.56
GUESTROOM302_305 19-JAN-15:05 707.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -143.90 0.00 -48.83 -515.00
GUESTROOM306_308 04-AUG-14:05 467.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1204.28 0.00 5.27 0.00 0.00 -0.00 0.00 0.00 -1677.46
GUESTROOM309_312 07-APR-08:03 4461.93 0.00 0.00 0.00 0.00 0.00 92.67 174.65 667.12 0.00 0.00 0.00 0.00 0.00 -71.98 0.00 -36.99 -5287.41
GUESTROOM313 02-FEB-09:23 280.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -114.26 0.00 -21.70 -144.19
GUESTROOM314 23-FEB-16:01 1547.89 0.00 0.00 0.00 0.00 0.00 70.58 27.78 100.84 0.00 0.00 0.00 0.00 0.00 -19.12 0.00 -14.71 -1713.27
GUESTROOM315_318 21-MAR-15:03 4280.63 0.00 0.00 0.00 0.00 0.00 240.79 111.13 403.35 0.00 0.00 0.00 0.00 0.00 -78.91 0.00 -49.18 -4907.81
GUESTROOM319 15-APR-14:05 130.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76.17 0.00 2.70 0.00 0.00 -0.00 0.00 0.00 -209.76
GUESTROOM320_323 17-OCT-08:03 4269.38 0.00 0.00 0.00 0.00 0.00 92.72 174.64 667.07 386.02 0.00 0.00 0.00 0.00 -0.00 0.00 -40.77 -5549.05
GUESTROOM324 04-AUG-14:50 177.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96.06 0.00 2.02 0.00 0.00 -0.00 0.00 0.00 -275.90
FRONTSTAIRSFLR3 02-FEB-09:43 250.70 0.00 0.00 0.00 0.00 0.00 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -204.03 -152.51
REARSTAIRSFLR4 09-DEC-02:00 307.78 0.00 0.00 0.00 0.00 0.00 0.00 105.87 0.00 0.00 0.00 0.00 37.40 0.00 -0.00 0.00 -451.05 0.00
CORRIDORFLR4 03-FEB-09:11 3539.40 0.00 0.00 0.00 0.00 0.00 0.00 415.13 0.00 42.75 0.00 0.00 0.00 0.00 -0.00 0.00 -105.16 -3892.12
GUESTROOM401 20-NOV-09:01 2264.72 0.00 0.00 0.00 0.00 0.00 26.90 43.66 166.78 7.02 0.00 0.00 0.00 0.00 -0.00 0.00 -18.10 -2490.98
GUESTROOM402_405 02-FEB-07:23 2076.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -584.89 0.00 -68.52 -1423.33
GUESTROOM406_408 02-FEB-07:23 1618.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -597.04 0.00 -55.34 -966.19
GUESTROOM409_412 17-NOV-16:01 5235.21 0.00 0.00 0.00 0.00 0.00 292.03 111.14 403.38 0.00 0.00 0.00 0.00 0.00 -170.57 0.00 -67.29 -5803.90
GUESTROOM413 02-FEB-07:23 852.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -146.94 0.00 -17.13 -688.52
GUESTROOM414 02-FEB-07:23 554.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -143.49 0.00 -17.13 -393.73
GUESTROOM415_418 21-MAR-15:03 5503.52 0.00 0.00 0.00 0.00 0.00 240.85 111.13 403.35 0.00 0.00 0.00 0.00 0.00 -71.94 0.00 -52.75 -6134.16
GUESTROOM419 16-JAN-16:01 1425.94 0.00 0.00 0.00 0.00 0.00 38.97 32.75 112.47 0.00 0.00 0.00 0.00 0.00 -35.49 0.00 -7.58 -1567.06
GUESTROOM420_423 28-OCT-08:03 5101.43 0.00 0.00 0.00 0.00 0.00 135.75 222.27 961.83 451.70 0.00 0.00 0.00 0.00 -0.00 0.00 -11.20 -6861.77
GUESTROOM424 15-NOV-16:01 1795.04 0.00 0.00 0.00 0.00 0.00 71.00 27.78 100.84 0.00 0.00 0.00 0.00 0.00 -26.26 0.00 -7.25 -1961.16
FRONTSTAIRSFLR4 02-FEB-07:55 607.02 0.00 0.00 0.00 0.00 0.00 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -176.24 -536.62
REARSTORAGEFLR1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 02-FEB-07:02 95154.42 4806.66 1101.55 -4806.66 0.00 0.00 7353.73 7568.56 31369.28 0.00 0.00 0.00 0.00 0.00 -17853.00 0.00 -80868.72 -43825.83



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
SAC_FRONTOFFICE 0.4039 0.0000 10.0000 1.0000 Calculated from schedules 0.0634 0.4039 0.1569 1.0000 Not calculated 0.0634 0.1569    
SAC_FRONTLOUNGE 1.0261 0.0000 53.0000 1.0000 Calculated from schedules 0.2373 1.0261 0.2313 1.0000 Not calculated 0.2373 0.2313    
SAC_MEETINGROOM 0.4613 0.0000 43.0000 1.0000 Calculated from schedules 0.1259 0.4613 0.2730 1.0000 Not calculated 0.1259 0.2730    
SAC_EMPLOYEELOUNGE 0.8261 0.0000 18.0000 1.0000 Calculated from schedules 0.0524 0.8261 0.0634 1.0000 Not calculated 0.0524 0.0634    
SAC_EXERCISECENTER 0.1582 0.0000 7.0000 1.0000 Calculated from schedules 0.0760 0.1582 0.4805 1.0000 Not calculated 0.0760 0.4805    
SAC_RESTROOM 0.0828 0.0000 1.7550 1.0000 Calculated from schedules 0.0000 0.0828 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
SAC_FRONTOFFICE 0.4039 0.0000 10.0000 1.0000 Calculated from schedules 0.0634 0.4039 1.0000 1.0000 Not calculated 0.0634 0.1569    
SAC_FRONTLOUNGE 1.0261 0.0000 53.0000 1.0000 Calculated from schedules 0.2373 1.0261 1.0000 1.0000 Not calculated 0.2373 0.2313    
SAC_MEETINGROOM 0.4613 0.0000 43.0000 1.0000 Calculated from schedules 0.1259 0.4613 1.0000 1.0000 Not calculated 0.1259 0.2730    
SAC_EMPLOYEELOUNGE 0.8261 0.0000 18.0000 1.0000 Calculated from schedules 0.0524 0.8261 1.0000 1.0000 Not calculated 0.0524 0.0634    
SAC_EXERCISECENTER 0.1582 0.0000 7.0000 1.0000 Calculated from schedules 0.0760 0.1582 1.0000 1.0000 Not calculated 0.0760 0.4805    
SAC_RESTROOM 0.0828 0.0000 1.7550 1.0000 Calculated from schedules 0.0000 0.0828 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
FRONTLOUNGEFLR1 SAC_FRONTLOUNGE 0.003540 53.0000 0.000305 163.06 0.2373 1.0000 0.2373 1.000 0.2373
RESTROOMFLR1 SAC_RESTROOM 0.000000 1.7550 0.000000 32.61 0.0000 1.0000 0.0000 1.000 0.0000
MEETINGROOMFLR1 SAC_MEETINGROOM 0.002360 43.0000 0.000305 80.27 0.1259 1.0000 0.1259 1.000 0.1259
EMPLOYEELOUNGEFLR1 SAC_EMPLOYEELOUNGE 0.002360 18.0000 0.000305 32.61 0.0524 1.0000 0.0524 1.000 0.0524
EXERCISECENTERFLR1 SAC_EXERCISECENTER 0.009439 7.0000 0.000305 32.61 0.0760 1.0000 0.0760 1.000 0.0760
FRONTOFFICEFLR1 SAC_FRONTOFFICE 0.002360 10.0000 0.000305 130.44 0.0634 1.0000 0.0634 1.000 0.0634


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
SAC_FRONTOFFICE 0.002360 10.00 0.000305 130.4359 0.0634 0.0634 0.0634
SAC_FRONTLOUNGE 0.003540 53.00 0.000305 163.0564 0.2373 0.2373 0.2373
SAC_MEETINGROOM 0.002360 43.00 0.000305 80.2739 0.1259 0.1259 0.1259
SAC_EMPLOYEELOUNGE 0.002360 18.00 0.000305 32.6090 0.0524 0.0524 0.0524
SAC_EXERCISECENTER 0.009439 7.00 0.000305 32.6090 0.0760 0.0760 0.0760
SAC_RESTROOM 0.000000 1.75 0.000000 32.6113 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
FRONTLOUNGEFLR1 SAC_FRONTLOUNGE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.0261 1.0261 1.0261 No 0.2373 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RESTROOMFLR1 SAC_RESTROOM AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0828 0.0828 0.0828 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MEETINGROOMFLR1 SAC_MEETINGROOM AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4613 0.4613 0.4613 No 0.1259 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
EMPLOYEELOUNGEFLR1 SAC_EMPLOYEELOUNGE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8261 0.8261 0.8261 No 0.0524 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
EXERCISECENTERFLR1 SAC_EXERCISECENTER AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.1582 0.1582 0.1582 No 0.0760 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FRONTOFFICEFLR1 SAC_FRONTOFFICE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4039 0.4039 0.4039 No 0.0634 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
SAC_FRONTOFFICE 0.4039 0.4039 0.4039 0.4039 0.0634 1.0000
SAC_FRONTLOUNGE 1.0261 1.0261 1.0261 1.0261 0.2373 1.0000
SAC_MEETINGROOM 0.4613 0.4613 0.4613 0.4613 0.1259 1.0000
SAC_EMPLOYEELOUNGE 0.8261 0.8261 0.8261 0.8261 0.0524 1.0000
SAC_EXERCISECENTER 0.1582 0.1582 0.1582 0.1582 0.0760 1.0000
SAC_RESTROOM 0.0828 0.0828 0.0828 0.0828 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
FRONTLOUNGEFLR1 SAC_FRONTLOUNGE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.0261 1.0261 1.0261 No 0.2373 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RESTROOMFLR1 SAC_RESTROOM AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0828 0.0828 0.0828 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MEETINGROOMFLR1 SAC_MEETINGROOM AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4613 0.4613 0.4613 No 0.1259 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
EMPLOYEELOUNGEFLR1 SAC_EMPLOYEELOUNGE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8261 0.8261 0.8261 No 0.0524 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
EXERCISECENTERFLR1 SAC_EXERCISECENTER AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.1582 0.1582 0.1582 No 0.0760 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
FRONTOFFICEFLR1 SAC_FRONTOFFICE AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4039 0.4039 0.4039 No 0.0634 0.9192 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
SAC_FRONTOFFICE 0.4039 0.4039 0.4039 0.4039 0.0634 1.0000
SAC_FRONTLOUNGE 1.0261 1.0261 1.0261 1.0261 0.2373 1.0000
SAC_MEETINGROOM 0.4613 0.4613 0.4613 0.4613 0.1259 1.0000
SAC_EMPLOYEELOUNGE 0.8261 0.8261 0.8261 0.8261 0.0524 1.0000
SAC_EXERCISECENTER 0.1582 0.1582 0.1582 0.1582 0.0760 1.0000
SAC_RESTROOM 0.0828 0.0828 0.0828 0.0828 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Total gross floor area [m2] 4013.58
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
REARSTAIRSFLR1 20.07 20.07 0.00 0.00
CORRIDORFLR1 150.51 150.51 0.00 0.00
FRONTLOUNGEFLR1 163.06 163.06 0.00 168.00
RESTROOMFLR1 32.61 32.61 0.00 168.00
MEETINGROOMFLR1 80.27 80.27 0.00 39.79
MECHANICALROOMFLR1 32.61 32.61 0.00 0.00
GUESTROOM101 32.61 32.61 0.00 0.00
GUESTROOM102 32.61 32.61 0.00 0.00
GUESTROOM103 32.61 32.61 0.00 168.00
GUESTROOM104 32.61 32.61 0.00 168.00
GUESTROOM105 32.61 32.61 0.00 168.00
EMPLOYEELOUNGEFLR1 32.61 32.61 0.00 105.00
EXERCISECENTERFLR1 32.61 32.61 0.00 112.00
FRONTOFFICEFLR1 130.44 130.44 0.00 154.00
FRONTSTAIRSFLR1 20.07 20.07 0.00 0.00
REARSTAIRSFLR2 20.07 20.07 0.00 0.00
CORRIDORFLR2 125.42 125.42 0.00 0.00
GUESTROOM201 32.61 32.61 0.00 0.00
GUESTROOM202_205 130.45 130.45 0.00 168.00
GUESTROOM206_208 105.36 105.36 0.00 168.00
GUESTROOM209_212 130.45 130.45 0.00 168.00
GUESTROOM213 32.61 32.61 0.00 168.00
GUESTROOM214 32.61 32.61 0.00 168.00
GUESTROOM215_218 130.44 130.44 0.00 0.00
GUESTROOM219 32.61 32.61 0.00 168.00
GUESTROOM220_223 130.44 130.44 0.00 168.00
GUESTROOM224 32.61 32.61 0.00 168.00
FRONTSTAIRSFLR2 20.07 20.07 0.00 0.00
REARSTAIRSFLR3 20.07 20.07 0.00 0.00
CORRIDORFLR3 125.42 125.42 0.00 0.00
GUESTROOM301 32.61 32.61 0.00 0.00
GUESTROOM302_305 130.45 130.45 0.00 0.00
GUESTROOM306_308 105.36 105.36 0.00 0.00
GUESTROOM309_312 130.45 130.45 0.00 168.00
GUESTROOM313 32.61 32.61 0.00 0.00
GUESTROOM314 32.61 32.61 0.00 168.00
GUESTROOM315_318 130.44 130.44 0.00 168.00
GUESTROOM319 32.61 32.61 0.00 0.00
GUESTROOM320_323 130.44 130.44 0.00 168.00
GUESTROOM324 32.61 32.61 0.00 0.00
FRONTSTAIRSFLR3 20.07 20.07 0.00 0.00
REARSTAIRSFLR4 20.07 20.07 0.00 0.00
CORRIDORFLR4 125.42 125.42 0.00 0.00
GUESTROOM401 32.61 32.61 0.00 168.00
GUESTROOM402_405 130.45 130.45 0.00 0.00
GUESTROOM406_408 105.36 105.36 0.00 0.00
GUESTROOM409_412 130.45 130.45 0.00 168.00
GUESTROOM413 32.61 32.61 0.00 0.00
GUESTROOM414 32.61 32.61 0.00 0.00
GUESTROOM415_418 130.44 130.44 0.00 168.00
GUESTROOM419 32.61 32.61 0.00 168.00
GUESTROOM420_423 130.44 130.44 0.00 168.00
GUESTROOM424 32.61 32.61 0.00 168.00
FRONTSTAIRSFLR4 20.07 20.07 0.00 0.00
REARSTORAGEFLR1 20.07 0.00 20.07 0.00
LAUNDRYROOMFLR1 97.83 0.00 97.83 56.00
ELEVATORCOREFLR1 15.05 0.00 15.05 0.00
FRONTSTORAGEFLR1 12.54 0.00 12.54 0.00
REARSTORAGEFLR2 20.07 0.00 20.07 0.00
ELEVATORCOREFLR2 15.05 0.00 15.05 0.00
FRONTSTORAGEFLR2 12.54 0.00 12.54 0.00
REARSTORAGEFLR3 20.07 0.00 20.07 0.00
ELEVATORCOREFLR3 15.05 0.00 15.05 0.00
FRONTSTORAGEFLR3 12.54 0.00 12.54 0.00
REARSTORAGEFLR4 20.07 0.00 20.07 0.00
ELEVATORCOREFLR4 15.05 0.00 15.05 0.00
FRONTSTORAGEFLR4 12.54 0.00 12.54 0.00
Totals 4013.58 3725.09 288.49  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 13.00
Number of hours cooling loads not met 334.50
Number of hours not met 339.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 284.96 153452.85 101.94 35248.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 224.94 47771.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 199.44 9486.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 49.88 3177.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 311.05 24347.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLift 130.97 8012.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLightsFan 0.97 62.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 28.48 2709.07 421.49 40096.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 284.74 11706.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.26 8.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 1069.05 95277.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 471.46 1515.69
Natural Gas 421.49 1592.48
Additional 0.00 0.00
Total 892.95 3108.16


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 49.69
Space Heating 71.00
Space Cooling 56.04
Fans (All) 70.94
Service Water Heating 0.00
Receptacle Equipment 117.47
Miscellaneous (All) 377.64
Subtotal 377.64


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 25.40
Service Water Heating 266.36
Miscellaneous (All) 396.77
Subtotal 396.77


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.42
Space Heating 12.45
Space Cooling 7.24
Fans (All) 9.16
Service Water Heating 34.39
Receptacle Equipment 28.73
Miscellaneous 1.61


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
OFFICE_FAN_SCH 8030. 8030.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
OFFICE_OCC_W_SB_SCH 3459. 8030.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
MEETINGROOM_OCC_W_SB_SCH 620. 2085.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISECENTER_OCC_SCH 5292. 5840.
ALWAYSOFF_SCH 0. 0.
ALWAYSON_SCH 8760. 8760.
LTG_SCH_OFFICE 3909. 8760.
LTG_SCH_LOBBY 4398. 6205.
LTG_SCH_MECHANICAL 2190. 8760.
LTG_SCH_STORAGE 958. 8760.
LTG_SCH_MEETING 4398. 6205.
LTG_SCH_GUESTROOM 2482. 8760.
LTG_SCH_EXERCISE 5840. 6205.
LTG_SCH_STAIR 8760. 8760.
LTG_SCH_ELEVATOR 0. 0.
LTG_SCH_LAUNDRY 3285. 3285.
LTG_SCH_LOUNGE 4398. 6205.
LTG_SCH_CORRIDOR 6570. 8760.
LTG_SCH_RESTROOM 4818. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
GUESTROOM_EQP_SCH_BASE 3009. 8760.
GUESTROOM_EQP_SCH_ADVA 2558. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFF_EQUIP_SCH 4574. 8760.
EMPLOYEELOUNGE_EQP_SCH 3791. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1185. 4745.
EXERCISECENTER_EQP_SCH 3832. 5840.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
MEETINGROOM_FAN_SCH 1720. 1720.
GUESTROOM_INFIL_SCH 2190. 8760.
COMMONAREA_INFIL_SCH 2190. 8760.
INFIL_DOOR_OPENING_SCH 1466. 5840.
GUESTROOM_SHW_SCH 2899. 8760.
LAUNDRYROOM_SHW_SCH 2920. 2920.
SHW LATENT FRACT SCHED 438. 8760.
SHW SENSIBLE FRACT SCHED 1752. 8760.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
VAC_GUESTROOM_VENT_CTRL 365. 365.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.
SZ_SYSTEM_OA_MAX_FRAC_SCH 6132. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
SEMIHEATED_HTGSP_SCH SEMIHEATED_HTGSP January 7.20 365 7.20 365
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 15.56 365 15.56 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 26.67 365 26.67 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
COMMONAREA_HTGSP_SCH COMMONAREA THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
COMMONAREA_CLGSP_SCH COMMONAREA THERMOSTAT DUAL SP CONTROL July 23.89 365 23.89 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
REARSTAIRSFLR1 8718.67 41.33 0.00 0.00 0.00
CORRIDORFLR1 8760.00 0.00 0.00 0.00 0.00
FRONTLOUNGEFLR1 8760.00 0.00 0.00 0.00 0.00
RESTROOMFLR1 8760.00 0.00 0.00 0.00 0.00
MEETINGROOMFLR1 8760.00 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 6085.17 2674.83 0.00 0.00 0.00
GUESTROOM101 8696.50 63.50 0.00 0.00 0.00
GUESTROOM102 8758.67 1.33 0.00 0.00 0.00
GUESTROOM103 8760.00 0.00 0.00 0.00 0.00
GUESTROOM104 8760.00 0.00 0.00 0.00 0.00
GUESTROOM105 8755.50 4.50 0.00 0.00 0.00
EMPLOYEELOUNGEFLR1 8760.00 0.00 0.00 0.00 0.00
EXERCISECENTERFLR1 8760.00 0.00 0.00 0.00 0.00
FRONTOFFICEFLR1 8760.00 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR1 8703.33 56.67 0.00 0.00 0.00
REARSTAIRSFLR2 8400.83 359.17 0.00 0.00 0.00
CORRIDORFLR2 8760.00 0.00 0.00 0.00 0.00
GUESTROOM201 8546.50 213.50 0.00 0.00 0.00
GUESTROOM202_205 8700.33 59.67 0.00 0.00 0.00
GUESTROOM206_208 8719.00 41.00 0.00 0.00 0.00
GUESTROOM209_212 8752.83 7.17 0.00 0.00 0.00
GUESTROOM213 8760.00 0.00 0.00 0.00 0.00
GUESTROOM214 8758.33 1.67 0.00 0.00 0.00
GUESTROOM215_218 8755.67 4.33 0.00 0.00 0.00
GUESTROOM219 8186.17 573.83 0.00 0.00 0.00
GUESTROOM220_223 8759.67 0.33 0.00 0.00 0.00
GUESTROOM224 8759.67 0.33 0.00 0.00 0.00
FRONTSTAIRSFLR2 8325.83 434.17 0.00 0.00 0.00
REARSTAIRSFLR3 8242.00 517.33 0.67 0.00 0.00
CORRIDORFLR3 8760.00 0.00 0.00 0.00 0.00
GUESTROOM301 8588.17 171.83 0.00 0.00 0.00
GUESTROOM302_305 8532.50 227.50 0.00 0.00 0.00
GUESTROOM306_308 8533.83 226.17 0.00 0.00 0.00
GUESTROOM309_312 8756.33 3.67 0.00 0.00 0.00
GUESTROOM313 8700.67 59.33 0.00 0.00 0.00
GUESTROOM314 8759.33 0.67 0.00 0.00 0.00
GUESTROOM315_318 8736.17 23.83 0.00 0.00 0.00
GUESTROOM319 8113.00 647.00 0.00 0.00 0.00
GUESTROOM320_323 8760.00 0.00 0.00 0.00 0.00
GUESTROOM324 8757.17 2.83 0.00 0.00 0.00
FRONTSTAIRSFLR3 8172.50 584.50 3.00 0.00 0.00
REARSTAIRSFLR4 7696.17 1022.33 41.50 0.00 0.00
CORRIDORFLR4 8760.00 0.00 0.00 0.00 0.00
GUESTROOM401 8669.33 90.67 0.00 0.00 0.00
GUESTROOM402_405 8417.00 343.00 0.00 0.00 0.00
GUESTROOM406_408 8449.83 310.17 0.00 0.00 0.00
GUESTROOM409_412 8633.00 127.00 0.00 0.00 0.00
GUESTROOM413 8490.50 269.50 0.00 0.00 0.00
GUESTROOM414 8421.67 338.33 0.00 0.00 0.00
GUESTROOM415_418 8744.33 15.67 0.00 0.00 0.00
GUESTROOM419 8748.67 11.33 0.00 0.00 0.00
GUESTROOM420_423 8752.50 7.50 0.00 0.00 0.00
GUESTROOM424 8756.00 4.00 0.00 0.00 0.00
FRONTSTAIRSFLR4 7904.33 837.83 17.83 0.00 0.00
REARSTORAGEFLR1 8757.00 3.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00 8760.00
ELEVATORCOREFLR1 0.00 0.00 0.00 5352.83 3407.17
FRONTSTORAGEFLR1 8749.67 10.33 0.00 0.00 0.00
REARSTORAGEFLR2 8715.50 44.50 0.00 0.00 0.00
ELEVATORCOREFLR2 982.33 6145.67 1632.00 0.00 0.00
FRONTSTORAGEFLR2 8749.00 11.00 0.00 0.00 0.00
REARSTORAGEFLR3 8528.00 232.00 0.00 0.00 0.00
ELEVATORCOREFLR3 7435.00 1325.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 8638.67 121.33 0.00 0.00 0.00
REARSTORAGEFLR4 8004.83 740.83 14.33 0.00 0.00
ELEVATORCOREFLR4 8648.83 111.17 0.00 0.00 0.00
FRONTSTORAGEFLR4 8444.83 315.17 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 6145.67 1632.00 5352.83 8760.00
Average 8182.86 290.14 25.51 79.89 181.60
Sum 548251.33 19439.33 1709.33 5352.83 12167.17


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
REARSTAIRSFLR1 0.00 0.00 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00 0.00 0.00
FRONTLOUNGEFLR1 117890.00 0.00 0.00 0.00 0.00
RESTROOMFLR1 1345.00 0.00 0.00 0.00 0.00
MEETINGROOMFLR1 25650.00 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00 0.00 0.00
GUESTROOM103 4150.00 0.00 0.00 0.00 0.00
GUESTROOM104 4150.00 0.00 0.00 0.00 0.00
GUESTROOM105 4149.50 0.50 0.00 0.00 0.00
EMPLOYEELOUNGEFLR1 12880.00 0.00 0.00 0.00 0.00
EXERCISECENTERFLR1 36500.00 0.00 0.00 0.00 0.00
FRONTOFFICEFLR1 34205.00 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00 0.00 0.00
GUESTROOM201 0.00 0.00 0.00 0.00 0.00
GUESTROOM202_205 30055.00 165.00 0.00 0.00 0.00
GUESTROOM206_208 19862.50 77.50 0.00 0.00 0.00
GUESTROOM209_212 30197.50 22.50 0.00 0.00 0.00
GUESTROOM213 4150.00 0.00 0.00 0.00 0.00
GUESTROOM214 4149.33 0.67 0.00 0.00 0.00
GUESTROOM215_218 0.00 0.00 0.00 0.00 0.00
GUESTROOM219 3917.50 232.50 0.00 0.00 0.00
GUESTROOM220_223 30219.67 0.33 0.00 0.00 0.00
GUESTROOM224 4150.00 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00 0.00 0.00
GUESTROOM301 0.00 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00 0.00 0.00
GUESTROOM309_312 30207.50 12.50 0.00 0.00 0.00
GUESTROOM313 0.00 0.00 0.00 0.00 0.00
GUESTROOM314 4149.83 0.17 0.00 0.00 0.00
GUESTROOM315_318 30144.33 75.67 0.00 0.00 0.00
GUESTROOM319 0.00 0.00 0.00 0.00 0.00
GUESTROOM320_323 30220.00 0.00 0.00 0.00 0.00
GUESTROOM324 0.00 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00 0.00 0.00
GUESTROOM401 4115.83 34.17 0.00 0.00 0.00
GUESTROOM402_405 0.00 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00 0.00
GUESTROOM409_412 29820.17 399.83 0.00 0.00 0.00
GUESTROOM413 0.00 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00 0.00
GUESTROOM415_418 30181.83 38.17 0.00 0.00 0.00
GUESTROOM419 4149.17 0.83 0.00 0.00 0.00
GUESTROOM420_423 30203.83 16.17 0.00 0.00 0.00
GUESTROOM424 4150.00 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00 1825.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 117890.00 399.83 0.00 0.00 1825.00
Average 8432.29 16.07 0.00 0.00 27.24
Sum 564963.50 1076.50 0.00 0.00 1825.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
REARSTAIRSFLR1 7609.83 1150.17 0.00 0.00 0.00
CORRIDORFLR1 8732.17 27.83 0.00 0.00 0.00
FRONTLOUNGEFLR1 8286.50 473.50 0.00 0.00 0.00
RESTROOMFLR1 5762.50 2997.50 0.00 0.00 0.00
MEETINGROOMFLR1 8622.50 137.50 0.00 0.00 0.00
MECHANICALROOMFLR1 6206.83 2553.17 0.00 0.00 0.00
GUESTROOM101 7067.67 1692.33 0.00 0.00 0.00
GUESTROOM102 7341.50 1418.50 0.00 0.00 0.00
GUESTROOM103 8464.50 295.50 0.00 0.00 0.00
GUESTROOM104 8569.33 190.67 0.00 0.00 0.00
GUESTROOM105 8512.67 247.33 0.00 0.00 0.00
EMPLOYEELOUNGEFLR1 8760.00 0.00 0.00 0.00 0.00
EXERCISECENTERFLR1 8399.50 360.50 0.00 0.00 0.00
FRONTOFFICEFLR1 8735.50 24.50 0.00 0.00 0.00
FRONTSTAIRSFLR1 7484.33 1275.67 0.00 0.00 0.00
REARSTAIRSFLR2 7235.83 1524.17 0.00 0.00 0.00
CORRIDORFLR2 8760.00 0.00 0.00 0.00 0.00
GUESTROOM201 7285.33 1474.67 0.00 0.00 0.00
GUESTROOM202_205 8287.50 472.50 0.00 0.00 0.00
GUESTROOM206_208 8318.83 441.17 0.00 0.00 0.00
GUESTROOM209_212 8294.67 465.33 0.00 0.00 0.00
GUESTROOM213 8358.50 401.50 0.00 0.00 0.00
GUESTROOM214 8442.83 317.17 0.00 0.00 0.00
GUESTROOM215_218 8745.00 15.00 0.00 0.00 0.00
GUESTROOM219 8261.50 498.50 0.00 0.00 0.00
GUESTROOM220_223 8427.50 332.50 0.00 0.00 0.00
GUESTROOM224 8467.33 292.67 0.00 0.00 0.00
FRONTSTAIRSFLR2 7270.67 1489.33 0.00 0.00 0.00
REARSTAIRSFLR3 7186.50 1573.50 0.00 0.00 0.00
CORRIDORFLR3 8760.00 0.00 0.00 0.00 0.00
GUESTROOM301 7377.67 1382.33 0.00 0.00 0.00
GUESTROOM302_305 7222.50 1537.50 0.00 0.00 0.00
GUESTROOM306_308 7304.17 1455.83 0.00 0.00 0.00
GUESTROOM309_312 8294.67 465.33 0.00 0.00 0.00
GUESTROOM313 7427.67 1332.33 0.00 0.00 0.00
GUESTROOM314 8446.00 314.00 0.00 0.00 0.00
GUESTROOM315_318 8392.33 367.67 0.00 0.00 0.00
GUESTROOM319 6954.00 1806.00 0.00 0.00 0.00
GUESTROOM320_323 8431.33 328.67 0.00 0.00 0.00
GUESTROOM324 7471.83 1288.17 0.00 0.00 0.00
FRONTSTAIRSFLR3 7222.83 1537.17 0.00 0.00 0.00
REARSTAIRSFLR4 7099.67 1653.67 6.67 0.00 0.00
CORRIDORFLR4 8646.67 113.33 0.00 0.00 0.00
GUESTROOM401 8320.00 440.00 0.00 0.00 0.00
GUESTROOM402_405 7992.83 767.17 0.00 0.00 0.00
GUESTROOM406_408 8065.00 695.00 0.00 0.00 0.00
GUESTROOM409_412 8263.00 497.00 0.00 0.00 0.00
GUESTROOM413 8093.17 666.83 0.00 0.00 0.00
GUESTROOM414 7750.67 1009.33 0.00 0.00 0.00
GUESTROOM415_418 8404.67 355.33 0.00 0.00 0.00
GUESTROOM419 8431.67 328.33 0.00 0.00 0.00
GUESTROOM420_423 8412.00 348.00 0.00 0.00 0.00
GUESTROOM424 8449.83 310.17 0.00 0.00 0.00
FRONTSTAIRSFLR4 7246.83 1507.17 6.00 0.00 0.00
REARSTORAGEFLR1 7939.00 821.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00 8760.00
ELEVATORCOREFLR1 0.00 0.00 29.00 698.50 8032.50
FRONTSTORAGEFLR1 7404.33 1355.67 0.00 0.00 0.00
REARSTORAGEFLR2 7661.50 1098.50 0.00 0.00 0.00
ELEVATORCOREFLR2 4057.50 4582.33 120.17 0.00 0.00
FRONTSTORAGEFLR2 7438.00 1322.00 0.00 0.00 0.00
REARSTORAGEFLR3 7519.67 1240.33 0.00 0.00 0.00
ELEVATORCOREFLR3 6529.00 2231.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 7372.33 1387.67 0.00 0.00 0.00
REARSTORAGEFLR4 7382.17 1372.67 5.17 0.00 0.00
ELEVATORCOREFLR4 7370.83 1389.17 0.00 0.00 0.00
FRONTSTORAGEFLR4 7391.83 1368.17 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 4582.33 120.17 698.50 8760.00
Average 7588.72 907.72 2.49 10.43 250.63
Sum 508444.50 60817.50 167.00 698.50 16792.50


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
REARSTAIRSFLR1 0.00 0.00 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00 0.00 0.00
FRONTLOUNGEFLR1 112074.83 5815.17 0.00 0.00 0.00
RESTROOMFLR1 879.67 465.33 0.00 0.00 0.00
MEETINGROOMFLR1 24592.17 1057.83 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00 0.00 0.00
GUESTROOM103 4036.50 113.50 0.00 0.00 0.00
GUESTROOM104 4058.50 91.50 0.00 0.00 0.00
GUESTROOM105 4035.33 114.67 0.00 0.00 0.00
EMPLOYEELOUNGEFLR1 12880.00 0.00 0.00 0.00 0.00
EXERCISECENTERFLR1 35271.67 1228.33 0.00 0.00 0.00
FRONTOFFICEFLR1 34092.00 113.00 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00 0.00 0.00
GUESTROOM201 0.00 0.00 0.00 0.00 0.00
GUESTROOM202_205 28736.33 1483.67 0.00 0.00 0.00
GUESTROOM206_208 19010.00 930.00 0.00 0.00 0.00
GUESTROOM209_212 28756.67 1463.33 0.00 0.00 0.00
GUESTROOM213 3991.83 158.17 0.00 0.00 0.00
GUESTROOM214 4001.33 148.67 0.00 0.00 0.00
GUESTROOM215_218 0.00 0.00 0.00 0.00 0.00
GUESTROOM219 3951.17 198.83 0.00 0.00 0.00
GUESTROOM220_223 29096.83 1123.17 0.00 0.00 0.00
GUESTROOM224 4014.67 135.33 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00 0.00 0.00
GUESTROOM301 0.00 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00 0.00 0.00
GUESTROOM309_312 28752.17 1467.83 0.00 0.00 0.00
GUESTROOM313 0.00 0.00 0.00 0.00 0.00
GUESTROOM314 4000.33 149.67 0.00 0.00 0.00
GUESTROOM315_318 28975.83 1244.17 0.00 0.00 0.00
GUESTROOM319 0.00 0.00 0.00 0.00 0.00
GUESTROOM320_323 29107.67 1112.33 0.00 0.00 0.00
GUESTROOM324 0.00 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00 0.00 0.00
GUESTROOM401 3980.33 169.67 0.00 0.00 0.00
GUESTROOM402_405 0.00 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00 0.00
GUESTROOM409_412 28678.17 1541.83 0.00 0.00 0.00
GUESTROOM413 0.00 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00 0.00
GUESTROOM415_418 29040.00 1180.00 0.00 0.00 0.00
GUESTROOM419 4003.17 146.83 0.00 0.00 0.00
GUESTROOM420_423 29068.17 1151.83 0.00 0.00 0.00
GUESTROOM424 4010.67 139.33 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00 1825.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 112074.83 5815.17 0.00 0.00 1825.00
Average 8105.91 342.45 0.00 0.00 27.24
Sum 543096.00 22944.00 0.00 0.00 1825.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:47:03

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00 0.00
FRONTLOUNGEFLR1 0.00 8760.00 0.00 0.00
RESTROOMFLR1 0.00 0.00 0.00 0.00
MEETINGROOMFLR1 0.00 0.00 8760.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00 0.00
GUESTROOM103 0.00 0.00 0.00 0.00
GUESTROOM104 0.00 0.00 0.00 0.00
GUESTROOM105 0.00 0.00 0.00 0.00
EMPLOYEELOUNGEFLR1 0.00 0.00 0.00 0.00
EXERCISECENTERFLR1 0.00 0.00 0.00 0.00
FRONTOFFICEFLR1 0.00 0.00 8760.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00 0.00
GUESTROOM201 0.00 0.00 0.00 0.00
GUESTROOM202_205 0.00 0.00 0.00 0.00
GUESTROOM206_208 0.00 0.00 0.00 0.00
GUESTROOM209_212 0.00 0.00 0.00 0.00
GUESTROOM213 0.00 0.00 0.00 0.00
GUESTROOM214 0.00 0.00 0.00 0.00
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 0.00 0.00 0.00
GUESTROOM220_223 0.00 0.00 0.00 0.00
GUESTROOM224 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00 0.00
GUESTROOM301 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00 0.00
GUESTROOM309_312 0.00 0.00 0.00 0.00
GUESTROOM313 0.00 0.00 0.00 0.00
GUESTROOM314 0.00 0.00 0.00 0.00
GUESTROOM315_318 0.00 0.00 0.00 0.00
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 0.00 0.00 0.00 0.00
GUESTROOM324 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00 0.00
GUESTROOM401 0.00 0.00 0.00 0.00
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00
GUESTROOM409_412 0.00 0.00 0.00 0.00
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00
GUESTROOM415_418 0.00 0.00 0.00 0.00
GUESTROOM419 0.00 0.00 0.00 0.00
GUESTROOM420_423 0.00 0.00 0.00 0.00
GUESTROOM424 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 8760.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 8760.00 0.00
Average 0.00 130.75 392.24 0.00
Sum 0.00 8760.00 26280.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00 0.00
FRONTLOUNGEFLR1 0.00 117890.00 0.00 0.00
RESTROOMFLR1 0.00 0.00 0.00 0.00
MEETINGROOMFLR1 0.00 0.00 25650.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00 0.00
GUESTROOM103 0.00 0.00 0.00 0.00
GUESTROOM104 0.00 0.00 0.00 0.00
GUESTROOM105 0.00 0.00 0.00 0.00
EMPLOYEELOUNGEFLR1 0.00 0.00 0.00 0.00
EXERCISECENTERFLR1 0.00 0.00 0.00 0.00
FRONTOFFICEFLR1 0.00 0.00 34205.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00 0.00
GUESTROOM201 0.00 0.00 0.00 0.00
GUESTROOM202_205 0.00 0.00 0.00 0.00
GUESTROOM206_208 0.00 0.00 0.00 0.00
GUESTROOM209_212 0.00 0.00 0.00 0.00
GUESTROOM213 0.00 0.00 0.00 0.00
GUESTROOM214 0.00 0.00 0.00 0.00
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 0.00 0.00 0.00
GUESTROOM220_223 0.00 0.00 0.00 0.00
GUESTROOM224 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00 0.00
GUESTROOM301 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00 0.00
GUESTROOM309_312 0.00 0.00 0.00 0.00
GUESTROOM313 0.00 0.00 0.00 0.00
GUESTROOM314 0.00 0.00 0.00 0.00
GUESTROOM315_318 0.00 0.00 0.00 0.00
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 0.00 0.00 0.00 0.00
GUESTROOM324 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00 0.00
GUESTROOM401 0.00 0.00 0.00 0.00
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00
GUESTROOM409_412 0.00 0.00 0.00 0.00
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00
GUESTROOM415_418 0.00 0.00 0.00 0.00
GUESTROOM419 0.00 0.00 0.00 0.00
GUESTROOM420_423 0.00 0.00 0.00 0.00
GUESTROOM424 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 1825.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 117890.00 34205.00 0.00
Average 0.00 1759.55 920.60 0.00
Sum 0.00 117890.00 61680.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELSMALL

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -12.56
February -7.67
March 0.331
April 7.021
May 14.194
June 19.161
July 20.915
August 20.049
September 15.390
October 7.428
November -0.02
December -7.58
   
Annual Sum or Average 6.460
Minimum of Months -12.56
Maximum of Months 20.915



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: REARSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 1950.31 0.35 27-JAN-10:55 -17.8 -18.4 0.00 0.00 01-JAN-00:10 -17.8 -18.4
February 678.20 0.23 02-FEB-10:55 -31.7 -31.9 0.00 0.00 01-FEB-00:10 -31.7 -31.9
March 755.11 0.27 25-MAR-13:45 15.87 9.13 0.00 0.00 01-MAR-00:10 15.87 9.13
April 552.20 0.26 10-APR-12:55 18.30 12.56 0.00 0.00 01-APR-00:10 18.30 12.56
May 18.30 0.06 02-MAY-10:45 7.52 4.19 0.00 0.00 01-MAY-00:10 7.52 4.19
June 28.05 0.02 13-JUN-11:50 26.05 22.87 0.00 0.00 01-JUN-00:10 26.05 22.87
July 2.91 0.01 24-JUL-07:53 18.90 15.77 0.00 0.00 01-JUL-00:10 18.90 15.77
August 44.37 0.06 13-AUG-12:00 22.80 19.05 0.00 0.00 01-AUG-00:10 22.80 19.05
September 593.54 0.25 15-SEP-09:55 17.20 12.64 0.00 0.00 01-SEP-00:10 17.20 12.64
October 842.47 0.23 19-OCT-10:45 12.62 6.98 0.00 0.00 01-OCT-00:10 12.62 6.98
November 565.71 0.24 11-NOV-11:35 0.20 -2.3 0.00 0.00 01-NOV-00:10 0.20 -2.3
December 1750.17 0.43 15-DEC-10:55 -10.0 -11.3 0.00 0.00 01-DEC-00:10 -10.0 -11.3
                     
Annual Sum or Average 7781.34         0.00        
Minimum of Months 2.91 0.01   -31.7 -31.9 0.00 0.00   -31.7 -31.9
Maximum of Months 1950.31 0.43   26.05 22.87 0.00 0.00   26.05 22.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDORFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.848207E+09 3231.82 13-JAN-22:05 2.02 0.71 0.00 0.00 01-JAN-00:10 2.02 0.71
February 0.103312E+10 4128.62 25-FEB-22:04 0.50 -1.1 0.00 0.00 01-FEB-00:10 0.50 -1.1
March 0.222367E+10 4475.85 20-MAR-21:04 -1.8 -3.5 0.00 0.00 01-MAR-00:10 -1.8 -3.5
April 0.496448E+10 13023.73 15-APR-16:11 30.00 18.83 0.00 0.00 01-APR-00:10 30.00 18.83
May 0.951307E+10 12236.34 31-MAY-16:21 28.60 19.31 0.00 0.00 01-MAY-00:10 28.60 19.31
June 0.127476E+11 16512.88 11-JUN-16:10 32.62 23.87 0.00 0.00 01-JUN-00:10 32.62 23.87
July 0.147735E+11 13873.04 26-JUL-16:02 29.82 25.48 0.00 0.00 01-JUL-00:10 29.82 25.48
August 0.145480E+11 17380.89 04-AUG-16:10 33.15 26.05 0.00 0.00 01-AUG-00:10 33.15 26.05
September 0.113844E+11 15980.08 07-SEP-16:10 31.52 18.72 0.00 0.00 01-SEP-00:10 31.52 18.72
October 0.631415E+10 7029.31 21-OCT-17:02 15.47 11.99 0.00 0.00 01-OCT-00:10 15.47 11.99
November 0.315595E+10 5511.69 03-NOV-17:07 11.73 7.54 0.00 0.00 01-NOV-00:10 11.73 7.54
December 0.101399E+10 3429.95 02-DEC-22:14 -0.7 -1.1 0.00 0.00 01-DEC-00:10 -0.7 -1.1
                     
Annual Sum or Average 0.825201E+11         0.00        
Minimum of Months 0.848207E+09 3231.82   -1.8 -3.5 0.00 0.00   -1.8 -3.5
Maximum of Months 0.147735E+11 17380.89   33.15 26.05 0.00 0.00   33.15 26.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: REARSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.00 0.00 01-JAN-00:10 -2.8 -3.2
February 0.00 0.00 01-FEB-00:10 -24.1 -24.4 0.00 0.00 01-FEB-00:10 -24.1 -24.4
March 0.00 0.00 01-MAR-00:10 -11.0 -12.0 0.00 0.00 01-MAR-00:10 -11.0 -12.0
April 0.00 0.00 01-APR-00:10 -1.2 -2.2 0.00 0.00 01-APR-00:10 -1.2 -2.2
May 0.00 0.00 01-MAY-00:10 8.22 5.15 0.00 0.00 01-MAY-00:10 8.22 5.15
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.00 0.00 01-JUN-00:10 14.70 10.69
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 0.00 0.00 01-AUG-00:10 18.15 17.82 0.00 0.00 01-AUG-00:10 18.15 17.82
September 0.00 0.00 01-SEP-00:10 16.07 15.67 0.00 0.00 01-SEP-00:10 16.07 15.67
October 0.00 0.00 01-OCT-00:10 3.92 1.39 0.00 0.00 01-OCT-00:10 3.92 1.39
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.00 0.00 01-NOV-00:10 1.65 -0.5
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 0.00 0.00 01-DEC-00:10 -0.7 -1.3
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -24.1 -24.4 0.00 0.00   -24.1 -24.4
Maximum of Months 0.00 0.00   18.93 17.82 0.00 0.00   18.93 17.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONTLOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.279818E+10 4899.86 14-JAN-07:01 -4.0 -4.6 0.175554E+10 1867.95 13-JAN-09:00 -4.0 -4.6
February 0.313864E+10 4937.40 26-FEB-07:01 -3.8 -4.7 0.161487E+10 2046.99 24-FEB-09:00 -3.8 -4.7
March 0.396118E+10 4989.37 21-MAR-08:53 -5.6 -7.4 0.191827E+10 2240.51 24-MAR-05:19 7.03 4.30
April 0.451633E+10 5270.97 01-APR-06:01 -5.8 -6.3 0.200742E+10 2240.64 18-APR-06:10 16.97 15.18
May 0.535841E+10 5274.08 31-MAY-08:51 26.10 19.69 0.224655E+10 2240.75 05-MAY-08:50 26.10 19.69
June 0.669307E+10 5723.98 26-JUN-09:00 27.20 22.45 0.218897E+10 2240.83 23-JUN-08:50 27.20 22.45
July 0.782010E+10 5838.92 03-JUL-08:51 25.00 21.49 0.223082E+10 2240.74 07-JUL-08:50 22.70 20.77
August 0.776614E+10 5910.30 03-AUG-08:53 27.20 23.97 0.226537E+10 2240.83 25-AUG-08:50 15.82 15.22
September 0.650107E+10 5715.00 11-SEP-08:51 23.90 19.77 0.216013E+10 2240.82 09-SEP-07:10 23.90 19.77
October 0.496663E+10 4953.03 23-OCT-06:00 -3.3 -4.2 0.219622E+10 2240.56 21-OCT-08:00 -3.3 -4.2
November 0.444463E+10 5869.10 12-NOV-07:01 -9.1 -9.7 0.189398E+10 2240.52 01-NOV-05:19 -9.1 -9.7
December 0.364665E+10 5116.57 03-DEC-07:01 -5.0 -5.6 0.175933E+10 1930.07 03-DEC-09:00 2.20 0.78
                     
Annual Sum or Average 0.616110E+11         0.242375E+11        
Minimum of Months 0.279818E+10 4899.86   -9.1 -9.7 0.161487E+10 1867.95   -9.1 -9.7
Maximum of Months 0.782010E+10 5910.30   27.20 23.97 0.226537E+10 2240.83   27.20 22.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RESTROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 65158368.61 72.29 14-JAN-09:00 -3.3 -3.7
February 449409.62 166.10 25-FEB-17:03 4.63 1.87 61354812.03 74.19 25-FEB-08:09 4.63 1.87
March 19809230.19 156.42 22-MAR-16:03 6.60 3.31 71795705.94 74.76 30-MAR-06:00 1.10 0.61
April 0.135019E+09 517.17 09-APR-15:01 11.20 5.97 71251876.06 74.79 26-APR-07:10 0.87 -1.8
May 0.385694E+09 363.82 31-MAY-16:52 28.90 19.84 74634645.37 74.33 03-MAY-05:10 28.90 19.84
June 0.606190E+09 418.85 30-JUN-16:52 28.30 20.13 72496518.11 74.19 07-JUN-08:50 28.30 20.13
July 0.776782E+09 451.16 05-JUL-16:52 26.70 20.53 73870096.80 74.19 12-JUL-08:50 19.63 16.73
August 0.779979E+09 449.94 02-AUG-16:52 28.90 22.60 75014782.11 74.19 07-AUG-08:50 17.33 12.60
September 0.598190E+09 474.25 07-SEP-16:52 30.60 19.55 71733766.33 74.19 27-SEP-08:50 8.62 6.76
October 0.273864E+09 308.25 29-OCT-04:02 5.13 2.17 74253432.22 74.33 27-OCT-05:10 5.13 2.17
November 91604170.44 549.64 15-NOV-09:01 0.68 0.20 70130934.88 75.17 15-NOV-09:50 1.02 0.53
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 68289310.16 73.97 03-DEC-09:00 2.20 0.78
                     
Annual Sum or Average 0.366758E+10         0.849984E+09        
Minimum of Months 0.00 0.00   -2.8 -3.2 61354812.03 72.29   -3.3 -3.7
Maximum of Months 0.779979E+09 549.64   30.60 22.60 75014782.11 75.17   28.90 20.13



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MEETINGROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.596505E+09 6104.69 30-JAN-17:51 -26.7 -27.0 0.382281E+09 1104.36 14-JAN-08:09 -26.7 -27.0
February 0.679228E+09 4993.41 05-FEB-17:41 -18.6 -19.2 0.348545E+09 1151.82 25-FEB-08:09 0.10 -0.7
March 0.942529E+09 3722.47 05-MAR-12:41 -9.7 -10.5 0.399758E+09 1297.97 28-MAR-12:00 15.60 9.79
April 0.117187E+10 3389.62 03-APR-07:01 -6.6 -7.5 0.407175E+09 1298.52 17-APR-12:00 17.80 11.87
May 0.123043E+10 2338.70 02-MAY-07:01 2.98 0.72 0.481619E+09 1298.54 23-MAY-12:00 16.70 12.57
June 0.171043E+10 1974.71 26-JUN-13:00 31.10 21.43 0.475044E+09 1298.58 20-JUN-12:00 31.10 21.43
July 0.209357E+10 2008.99 05-JUL-13:00 26.70 20.54 0.485648E+09 1298.49 23-JUL-07:49 15.82 13.67
August 0.207544E+10 2025.72 02-AUG-13:00 28.30 21.74 0.495471E+09 1298.58 09-AUG-12:50 26.70 16.82
September 0.173990E+10 2644.33 30-SEP-07:01 0.97 -0.8 0.462479E+09 1298.57 08-SEP-12:30 0.97 -0.8
October 0.143943E+10 2969.08 23-OCT-07:01 -1.2 -2.6 0.439872E+09 1298.52 11-OCT-12:00 -1.2 -2.6
November 0.110519E+10 4386.06 24-NOV-08:61 -13.6 -14.1 0.396950E+09 1298.49 08-NOV-09:50 -13.6 -14.1
December 0.782892E+09 5103.03 11-DEC-14:21 -19.4 -20.0 0.382942E+09 1129.20 03-DEC-08:09 -19.4 -20.0
                     
Annual Sum or Average 0.155674E+11         0.515779E+10        
Minimum of Months 0.596505E+09 1974.71   -26.7 -27.0 0.348545E+09 1104.36   -26.7 -27.0
Maximum of Months 0.209357E+10 6104.69   31.10 21.74 0.495471E+09 1298.58   31.10 21.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECHANICALROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.00 0.00 01-JAN-00:10 -2.8 -3.2
February 0.00 0.00 01-FEB-00:10 -24.1 -24.4 0.00 0.00 01-FEB-00:10 -24.1 -24.4
March 0.00 0.00 01-MAR-00:10 -11.0 -12.0 0.00 0.00 01-MAR-00:10 -11.0 -12.0
April 0.00 0.00 01-APR-00:10 -1.2 -2.2 0.00 0.00 01-APR-00:10 -1.2 -2.2
May 0.00 0.00 01-MAY-00:10 8.22 5.15 0.00 0.00 01-MAY-00:10 8.22 5.15
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.00 0.00 01-JUN-00:10 14.70 10.69
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 0.00 0.00 01-AUG-00:10 18.15 17.82 0.00 0.00 01-AUG-00:10 18.15 17.82
September 0.00 0.00 01-SEP-00:10 16.07 15.67 0.00 0.00 01-SEP-00:10 16.07 15.67
October 0.00 0.00 01-OCT-00:10 3.92 1.39 0.00 0.00 01-OCT-00:10 3.92 1.39
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.00 0.00 01-NOV-00:10 1.65 -0.5
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 0.00 0.00 01-DEC-00:10 -0.7 -1.3
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -24.1 -24.4 0.00 0.00   -24.1 -24.4
Maximum of Months 0.00 0.00   18.93 17.82 0.00 0.00   18.93 17.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM101

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 39497391.41 580.91 30-JAN-15:25 -24.1 -24.5 0.00 0.00 01-JAN-00:10 -24.1 -24.5
February 29107039.77 642.07 02-FEB-15:25 -28.9 -29.2 0.00 0.00 01-FEB-00:10 -28.9 -29.2
March 19208599.51 372.43 05-MAR-15:25 -9.4 -10.5 0.00 0.00 01-MAR-00:10 -9.4 -10.5
April 11984296.86 281.49 01-APR-14:13 -2.6 -3.3 0.00 0.00 01-APR-00:10 -2.6 -3.3
May 3291018.64 114.32 13-MAY-15:00 11.10 10.20 0.00 0.00 01-MAY-00:10 11.10 10.20
June 1674108.75 120.85 01-JUN-15:00 11.00 9.83 0.00 0.00 01-JUN-00:10 11.00 9.83
July 947822.95 50.14 10-JUL-14:10 16.47 14.47 0.00 0.00 01-JUL-00:10 16.47 14.47
August 257240.21 39.90 30-AUG-15:00 17.80 14.99 0.00 0.00 01-AUG-00:10 17.80 14.99
September 3694115.07 121.94 28-SEP-15:00 10.00 5.63 0.00 0.00 01-SEP-00:10 10.00 5.63
October 9836900.34 182.83 22-OCT-15:00 6.10 3.25 0.00 0.00 01-OCT-00:10 6.10 3.25
November 21760691.96 493.51 25-NOV-15:13 -17.4 -18.0 0.00 0.00 01-NOV-00:10 -17.4 -18.0
December 32675634.20 509.93 11-DEC-15:25 -19.7 -20.2 0.00 0.00 01-DEC-00:10 -19.7 -20.2
                     
Annual Sum or Average 0.173935E+09         0.00        
Minimum of Months 257240.21 39.90   -28.9 -29.2 0.00 0.00   -28.9 -29.2
Maximum of Months 39497391.41 642.07   17.80 14.99 0.00 0.00   17.80 14.99



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM102

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 40463353.36 583.25 30-JAN-15:25 -24.1 -24.5 0.00 0.00 01-JAN-00:10 -24.1 -24.5
February 29636668.61 643.81 02-FEB-15:25 -28.9 -29.2 0.00 0.00 01-FEB-00:10 -28.9 -29.2
March 19944541.37 377.00 05-MAR-15:25 -9.4 -10.5 0.00 0.00 01-MAR-00:10 -9.4 -10.5
April 12514161.98 287.08 01-APR-14:13 -2.6 -3.3 0.00 0.00 01-APR-00:10 -2.6 -3.3
May 3616878.57 120.06 13-MAY-15:00 11.10 10.20 0.00 0.00 01-MAY-00:10 11.10 10.20
June 1836933.04 125.67 01-JUN-15:00 11.00 9.83 0.00 0.00 01-JUN-00:10 11.00 9.83
July 352148.36 55.87 10-JUL-14:10 16.47 14.47 0.00 0.00 01-JUL-00:10 16.47 14.47
August 289721.67 45.78 30-AUG-15:00 17.80 14.99 0.00 0.00 01-AUG-00:10 17.80 14.99
September 3879557.64 127.08 28-SEP-15:00 10.00 5.63 0.00 0.00 01-SEP-00:10 10.00 5.63
October 10455699.13 188.47 22-OCT-15:00 6.10 3.25 0.00 0.00 01-OCT-00:10 6.10 3.25
November 22515860.07 499.60 25-NOV-15:13 -17.4 -18.0 0.00 0.00 01-NOV-00:10 -17.4 -18.0
December 33599043.55 513.13 11-DEC-15:25 -19.7 -20.2 0.00 0.00 01-DEC-00:10 -19.7 -20.2
                     
Annual Sum or Average 0.179105E+09         0.00        
Minimum of Months 289721.67 45.78   -28.9 -29.2 0.00 0.00   -28.9 -29.2
Maximum of Months 40463353.36 643.81   17.80 14.99 0.00 0.00   17.80 14.99



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM103

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 11679659.14 944.06 16-JAN-16:03 0.92 -0.1 0.117670E+09 71.23 31-JAN-00:40 -29.6 -29.8
February 26999869.36 2165.53 26-FEB-09:01 -2.0 -3.2 0.106930E+09 71.23 03-FEB-00:40 -2.0 -3.2
March 0.103322E+09 2468.01 21-MAR-18:01 -2.7 -5.5 0.119706E+09 71.23 01-MAR-00:40 -2.7 -5.5
April 0.311052E+09 2402.17 20-APR-18:01 8.30 3.01 0.118553E+09 92.98 18-APR-21:49 8.30 3.01
May 0.642739E+09 2500.78 21-MAY-19:51 12.20 6.71 0.127689E+09 99.45 31-MAY-21:49 20.20 15.15
June 0.103128E+10 2465.40 23-JUN-20:01 21.42 14.84 0.126426E+09 105.21 30-JUN-21:10 22.03 17.04
July 0.126061E+10 2460.82 18-JUL-18:31 22.97 16.12 0.134398E+09 106.67 31-JUL-21:10 19.33 18.49
August 0.128234E+10 2596.30 06-AUG-17:01 19.03 11.91 0.135019E+09 106.17 10-AUG-21:10 18.22 14.84
September 0.111941E+10 2610.20 20-SEP-17:01 20.13 11.51 0.125306E+09 106.85 07-SEP-21:30 20.13 11.51
October 0.673150E+09 2474.81 28-OCT-08:61 1.55 -0.3 0.123569E+09 85.40 20-OCT-20:19 1.55 -0.3
November 0.306349E+09 2607.05 12-NOV-09:01 -5.3 -6.6 0.116818E+09 71.23 28-NOV-00:40 -18.3 -18.5
December 30914525.35 1912.64 03-DEC-09:01 -1.5 -1.7 0.118461E+09 71.23 12-DEC-00:49 -20.0 -20.4
                     
Annual Sum or Average 0.679985E+10         0.147055E+10        
Minimum of Months 11679659.14 944.06   -5.3 -6.6 0.106930E+09 71.23   -29.6 -29.8
Maximum of Months 0.128234E+10 2610.20   22.97 16.12 0.135019E+09 106.85   22.03 18.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM104

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 74297179.78 2621.28 02-JAN-09:01 -8.5 -9.0 0.119022E+09 71.23 31-JAN-00:40 -29.6 -29.8
February 0.128283E+09 2598.57 21-FEB-09:01 -4.8 -6.3 0.108191E+09 71.23 03-FEB-00:40 -4.8 -6.3
March 0.271173E+09 2683.94 21-MAR-08:61 -6.5 -8.1 0.121356E+09 71.23 06-MAR-01:49 -6.5 -8.1
April 0.495883E+09 2610.42 01-APR-08:61 -3.4 -4.4 0.119657E+09 97.70 18-APR-21:19 15.93 13.15
May 0.870650E+09 2649.03 06-MAY-16:51 18.90 10.90 0.128080E+09 100.58 31-MAY-21:40 20.60 15.57
June 0.118240E+10 2575.75 22-JUN-16:41 20.68 13.36 0.126470E+09 104.04 23-JUN-21:10 19.82 14.32
July 0.137335E+10 2563.49 23-JUL-16:21 22.80 15.36 0.133548E+09 106.72 19-JUL-21:10 22.80 15.36
August 0.139552E+10 2648.56 07-AUG-16:31 22.80 14.05 0.134100E+09 106.78 04-AUG-21:10 22.80 14.05
September 0.126113E+10 2734.88 20-SEP-16:51 20.60 11.60 0.125111E+09 106.58 07-SEP-21:19 20.60 11.60
October 0.893994E+09 2650.09 28-OCT-08:61 1.55 -0.3 0.124199E+09 88.25 20-OCT-20:19 1.55 -0.3
November 0.499738E+09 2974.41 25-NOV-09:01 -17.7 -18.0 0.117891E+09 71.23 28-NOV-01:30 -18.3 -18.5
December 0.155361E+09 2793.36 25-DEC-09:01 -12.5 -12.9 0.119902E+09 71.23 10-DEC-00:40 -12.5 -12.9
                     
Annual Sum or Average 0.860177E+10         0.147753E+10        
Minimum of Months 74297179.78 2563.49   -17.7 -18.0 0.108191E+09 71.23   -29.6 -29.8
Maximum of Months 0.139552E+10 2974.41   22.80 15.36 0.134100E+09 106.78   22.80 15.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM105

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.970949E+09 4263.56 07-JAN-09:01 -24.7 -25.1 0.123161E+09 71.23 31-JAN-05:19 -30.6 -30.8
February 0.997610E+09 4180.44 05-FEB-09:01 -19.1 -19.7 0.111467E+09 71.23 03-FEB-05:19 -19.1 -19.7
March 0.133931E+10 4042.28 06-MAR-09:01 -9.5 -10.4 0.124453E+09 80.65 23-MAR-18:10 13.53 8.78
April 0.150974E+10 3942.45 30-APR-18:21 14.45 9.03 0.122328E+09 108.35 18-APR-21:10 14.45 9.03
May 0.182192E+10 4013.91 21-MAY-16:51 17.80 9.67 0.130891E+09 109.17 05-MAY-21:10 17.80 9.67
June 0.198483E+10 3833.40 22-JUN-16:41 20.68 13.36 0.128803E+09 110.60 12-JUN-21:40 20.68 13.36
July 0.209283E+10 3800.81 23-JUL-16:21 22.80 15.36 0.136168E+09 113.37 17-JUL-21:10 22.80 15.36
August 0.208849E+10 3912.64 06-AUG-16:51 19.40 12.05 0.136585E+09 114.25 01-AUG-21:19 19.40 12.05
September 0.202774E+10 4064.01 24-SEP-16:11 14.63 7.59 0.126567E+09 109.20 01-SEP-21:40 14.63 7.59
October 0.187382E+10 3992.99 30-OCT-16:11 12.97 7.94 0.125047E+09 95.10 20-OCT-20:19 12.97 7.94
November 0.147990E+10 4230.22 26-NOV-09:01 -22.7 -23.1 0.119819E+09 71.23 26-NOV-03:30 -22.7 -23.1
December 0.115828E+10 4224.73 09-DEC-09:01 -22.7 -22.9 0.123456E+09 71.23 13-DEC-01:39 -12.8 -13.2
                     
Annual Sum or Average 0.193454E+11         0.150875E+10        
Minimum of Months 0.970949E+09 3800.81   -24.7 -25.1 0.111467E+09 71.23   -30.6 -30.8
Maximum of Months 0.209283E+10 4263.56   22.80 15.36 0.136585E+09 114.25   22.80 15.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: EMPLOYEELOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.508192E+10 6701.33 30-JAN-13:01 -24.9 -25.2 0.294183E+09 874.14 30-JAN-12:00 -24.9 -25.2
February 0.465422E+10 3535.86 24-FEB-13:00 6.70 4.10 0.275078E+09 847.01 01-FEB-12:00 6.70 4.10
March 0.534804E+10 3653.68 20-MAR-12:00 10.60 7.27 0.321108E+09 760.99 29-MAR-11:00 8.90 7.98
April 0.549452E+10 3947.85 18-APR-12:00 27.80 20.94 0.295467E+09 761.06 18-APR-11:00 27.80 20.94
May 0.621436E+10 4032.45 31-MAY-12:00 29.40 19.85 0.314458E+09 761.08 16-MAY-11:00 29.40 19.85
June 0.635813E+10 4086.33 29-JUN-12:00 27.80 20.62 0.309182E+09 761.10 13-JUN-11:39 27.80 20.62
July 0.675088E+10 4106.99 05-JUL-12:00 26.10 20.34 0.300775E+09 761.12 07-JUL-11:00 24.40 22.05
August 0.676208E+10 4143.47 02-AUG-12:00 27.20 20.63 0.321319E+09 761.13 31-AUG-11:00 21.10 20.27
September 0.631496E+10 4128.10 07-SEP-12:00 30.60 18.67 0.295472E+09 761.06 12-SEP-11:00 18.30 15.81
October 0.601813E+10 3829.08 20-OCT-12:00 21.10 12.25 0.307596E+09 761.04 02-OCT-11:00 21.10 12.25
November 0.539135E+10 3710.94 03-NOV-12:00 15.60 11.02 0.294821E+09 761.04 08-NOV-12:00 13.90 12.22
December 0.514194E+10 3434.76 05-DEC-13:00 -3.9 -7.2 0.298761E+09 760.94 05-DEC-12:09 -3.9 -7.2
                     
Annual Sum or Average 0.695305E+11         0.362822E+10        
Minimum of Months 0.465422E+10 3434.76   -24.9 -25.2 0.275078E+09 760.94   -24.9 -25.2
Maximum of Months 0.676208E+10 6701.33   30.60 20.94 0.321319E+09 874.14   29.40 22.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRYROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.181490E+09 250.19 01-JAN-10:09 -2.8 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1 -24.4 0.163926E+09 250.19 01-FEB-10:09 -30.7 -30.9
March 0.00 0.00 01-MAR-00:10 -11.0 -12.0 0.181490E+09 250.19 01-MAR-10:09 -4.5 -5.9
April 0.00 0.00 01-APR-00:10 -1.2 -2.2 0.175635E+09 250.19 01-APR-09:09 -4.0 -4.4
May 0.00 0.00 01-MAY-00:10 8.22 5.15 0.181490E+09 250.19 01-MAY-09:09 7.88 5.26
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.175635E+09 250.19 01-JUN-09:09 13.58 10.29
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.181490E+09 250.19 01-JUL-09:09 24.60 18.53
August 0.00 0.00 01-AUG-00:10 18.15 17.82 0.181490E+09 250.19 01-AUG-09:09 24.68 21.68
September 0.00 0.00 01-SEP-00:10 16.07 15.67 0.175635E+09 250.19 01-SEP-09:09 19.60 14.14
October 0.00 0.00 01-OCT-00:10 3.92 1.39 0.181490E+09 250.19 01-OCT-09:09 13.58 10.36
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.175635E+09 250.19 01-NOV-09:09 8.27 6.96
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 0.181490E+09 250.19 01-DEC-10:09 -3.1 -4.6
                     
Annual Sum or Average 0.00         0.213690E+10        
Minimum of Months 0.00 0.00   -24.1 -24.4 0.163926E+09 250.19   -30.7 -30.9
Maximum of Months 0.00 0.00   18.93 17.82 0.181490E+09 250.19   24.68 21.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ELEVATORCOREFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.00 0.00 01-JAN-00:10 -2.8 -3.2
February 0.00 0.00 01-FEB-00:10 -24.1 -24.4 0.00 0.00 01-FEB-00:10 -24.1 -24.4
March 0.00 0.00 01-MAR-00:10 -11.0 -12.0 0.00 0.00 01-MAR-00:10 -11.0 -12.0
April 0.00 0.00 01-APR-00:10 -1.2 -2.2 0.00 0.00 01-APR-00:10 -1.2 -2.2
May 0.00 0.00 01-MAY-00:10 8.22 5.15 0.00 0.00 01-MAY-00:10 8.22 5.15
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.00 0.00 01-JUN-00:10 14.70 10.69
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 0.00 0.00 01-AUG-00:10 18.15 17.82 0.00 0.00 01-AUG-00:10 18.15 17.82
September 0.00 0.00 01-SEP-00:10 16.07 15.67 0.00 0.00 01-SEP-00:10 16.07 15.67
October 0.00 0.00 01-OCT-00:10 3.92 1.39 0.00 0.00 01-OCT-00:10 3.92 1.39
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.00 0.00 01-NOV-00:10 1.65 -0.5
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 0.00 0.00 01-DEC-00:10 -0.7 -1.3
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -24.1 -24.4 0.00 0.00   -24.1 -24.4
Maximum of Months 0.00 0.00   18.93 17.82 0.00 0.00   18.93 17.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: EXERCISECENTERFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.142675E+10 4033.44 30-JAN-23:01 -28.9 -29.1 0.537895E+09 332.40 16-JAN-19:49 -28.9 -29.1
February 0.143072E+10 3903.71 03-FEB-12:41 -27.4 -27.7 0.485987E+09 354.12 24-FEB-16:19 7.93 5.63
March 0.180429E+10 2974.12 06-MAR-03:31 -16.3 -16.8 0.554700E+09 422.78 19-MAR-15:09 18.40 13.72
April 0.190497E+10 1358.10 25-APR-19:05 3.72 -0.3 0.569517E+09 422.79 15-APR-20:10 3.72 -0.3
May 0.199064E+10 1375.31 01-MAY-20:01 3.80 2.36 0.662579E+09 422.80 29-MAY-13:30 24.15 19.85
June 0.199184E+10 1245.78 26-JUN-16:00 31.70 22.11 0.653929E+09 422.80 21-JUN-14:39 31.70 22.11
July 0.208520E+10 1242.10 05-JUL-16:00 27.80 20.26 0.683066E+09 422.81 26-JUL-19:40 27.07 24.87
August 0.211562E+10 1262.50 04-AUG-15:55 33.90 26.33 0.682201E+09 422.80 03-AUG-13:50 33.90 26.33
September 0.212255E+10 1439.62 28-SEP-20:01 3.22 1.80 0.639433E+09 422.80 09-SEP-07:10 3.22 1.80
October 0.226849E+10 1466.91 31-OCT-18:40 -0.3 -2.1 0.596570E+09 422.79 02-OCT-13:50 -0.3 -2.1
November 0.189637E+10 3702.58 26-NOV-03:11 -25.0 -25.3 0.545031E+09 422.77 08-NOV-21:10 -25.0 -25.3
December 0.160013E+10 3518.81 09-DEC-01:01 -22.8 -23.0 0.537895E+09 332.40 14-DEC-19:00 -5.0 -6.1
                     
Annual Sum or Average 0.226376E+11         0.714880E+10        
Minimum of Months 0.142675E+10 1242.10   -28.9 -29.1 0.485987E+09 332.40   -28.9 -29.1
Maximum of Months 0.226849E+10 4033.44   33.90 26.33 0.683066E+09 422.81   33.90 26.33



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONTOFFICEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.116236E+10 2916.74 30-JAN-19:22 -27.2 -27.5 0.490995E+09 559.93 13-JAN-16:19 -27.2 -27.5
February 0.137321E+10 2960.18 04-FEB-09:22 -27.8 -28.0 0.456961E+09 602.43 24-FEB-16:19 7.93 5.63
March 0.189471E+10 2121.36 05-MAR-23:53 -16.1 -16.6 0.548573E+09 603.93 29-MAR-15:09 8.90 8.32
April 0.210071E+10 2252.49 18-APR-10:30 26.15 20.69 0.555357E+09 603.96 14-APR-12:00 26.15 20.69
May 0.258209E+10 2511.52 31-MAY-10:15 27.57 19.40 0.632445E+09 603.96 11-MAY-14:50 27.57 19.40
June 0.334725E+10 2709.01 29-JUN-10:01 26.70 20.54 0.622663E+09 603.96 14-JUN-12:39 26.70 20.54
July 0.389429E+10 2747.17 05-JUL-10:30 24.70 20.49 0.621155E+09 603.96 10-JUL-12:00 16.10 14.74
August 0.392777E+10 2853.16 02-AUG-10:15 25.97 21.13 0.646590E+09 603.96 23-AUG-14:09 22.80 20.14
September 0.333330E+10 2765.87 07-SEP-10:40 28.87 18.66 0.602888E+09 603.96 12-SEP-12:09 18.77 15.90
October 0.254010E+10 1774.94 11-OCT-16:00 17.80 11.96 0.606332E+09 603.95 02-OCT-15:09 17.80 11.96
November 0.219072E+10 2687.51 26-NOV-00:42 -24.4 -24.7 0.530973E+09 603.95 08-NOV-13:00 -24.4 -24.7
December 0.166664E+10 2475.78 09-DEC-11:32 -21.3 -21.5 0.492408E+09 531.41 04-DEC-16:00 -21.3 -21.5
                     
Annual Sum or Average 0.300132E+11         0.680734E+10        
Minimum of Months 0.116236E+10 1774.94   -27.8 -28.0 0.456961E+09 531.41   -27.2 -27.5
Maximum of Months 0.392777E+10 2960.18   28.87 21.13 0.646590E+09 603.96   27.57 20.69



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONTSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 113.47 0.13 28-JAN-01:00 -22.8 -23.0 0.00 0.00 01-JAN-00:10 -22.8 -23.0
February 314.11 0.17 06-FEB-12:40 -7.8 -8.5 0.00 0.00 01-FEB-00:10 -7.8 -8.5
March 0.00 0.00 01-MAR-00:10 -11.0 -12.0 0.00 0.00 01-MAR-00:10 -11.0 -12.0
April 56.77 0.11 26-APR-06:45 0.13 -2.2 0.00 0.00 01-APR-00:10 0.13 -2.2
May 0.00 0.00 01-MAY-00:10 8.22 5.15 0.00 0.00 01-MAY-00:10 8.22 5.15
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.00 0.00 01-JUN-00:10 14.70 10.69
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 6.64 0.01 16-AUG-07:00 12.80 12.80 0.00 0.00 01-AUG-00:10 12.80 12.80
September 21.79 0.06 15-SEP-09:55 17.20 12.64 0.00 0.00 01-SEP-00:10 17.20 12.64
October 0.00 0.00 01-OCT-00:10 3.92 1.39 0.00 0.00 01-OCT-00:10 3.92 1.39
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.00 0.00 01-NOV-00:10 1.65 -0.5
December 240.29 0.11 09-DEC-02:30 -22.5 -22.8 0.00 0.00 01-DEC-00:10 -22.5 -22.8
                     
Annual Sum or Average 753.06         0.00        
Minimum of Months 0.00 0.00   -22.8 -23.0 0.00 0.00   -22.8 -23.0
Maximum of Months 314.11 0.17   18.93 15.94 0.00 0.00   18.93 15.94



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONTSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.00 0.00 01-JAN-00:10 -2.8 -3.2
February 0.00 0.00 01-FEB-00:10 -24.1 -24.4 0.00 0.00 01-FEB-00:10 -24.1 -24.4
March 0.00 0.00 01-MAR-00:10 -11.0 -12.0 0.00 0.00 01-MAR-00:10 -11.0 -12.0
April 0.00 0.00 01-APR-00:10 -1.2 -2.2 0.00 0.00 01-APR-00:10 -1.2 -2.2
May 0.00 0.00 01-MAY-00:10 8.22 5.15 0.00 0.00 01-MAY-00:10 8.22 5.15
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.00 0.00 01-JUN-00:10 14.70 10.69
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 0.00 0.00 01-AUG-00:10 18.15 17.82 0.00 0.00 01-AUG-00:10 18.15 17.82
September 0.00 0.00 01-SEP-00:10 16.07 15.67 0.00 0.00 01-SEP-00:10 16.07 15.67
October 0.00 0.00 01-OCT-00:10 3.92 1.39 0.00 0.00 01-OCT-00:10 3.92 1.39
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.00 0.00 01-NOV-00:10 1.65 -0.5
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 0.00 0.00 01-DEC-00:10 -0.7 -1.3
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -24.1 -24.4 0.00 0.00   -24.1 -24.4
Maximum of Months 0.00 0.00   18.93 17.82 0.00 0.00   18.93 17.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: REARSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 5050.37 0.53 30-JAN-11:45 -25.8 -26.0 0.00 0.00 01-JAN-00:10 -25.8 -26.0
February 2788.27 0.44 02-FEB-10:55 -31.7 -31.9 0.00 0.00 01-FEB-00:10 -31.7 -31.9
March 5644.77 0.43 06-MAR-11:35 -2.9 -4.6 0.00 0.00 01-MAR-00:10 -2.9 -4.6
April 5161.92 0.38 10-APR-12:55 18.30 12.56 0.00 0.00 01-APR-00:10 18.30 12.56
May 715.54 0.41 02-MAY-10:45 7.52 4.19 0.00 0.00 01-MAY-00:10 7.52 4.19
June 800.42 0.20 13-JUN-11:30 24.75 21.89 0.00 0.00 01-JUN-00:10 24.75 21.89
July 83.14 0.05 11-JUL-11:00 21.10 17.51 0.00 0.00 01-JUL-00:10 21.10 17.51
August 1101.44 0.31 13-AUG-12:00 22.80 19.05 0.00 0.00 01-AUG-00:10 22.80 19.05
September 4875.83 0.41 20-SEP-10:45 20.40 11.74 0.00 0.00 01-SEP-00:10 20.40 11.74
October 5357.33 0.46 20-OCT-10:45 17.62 11.24 0.00 0.00 01-OCT-00:10 17.62 11.24
November 2608.18 0.45 11-NOV-11:35 0.20 -2.3 0.00 0.00 01-NOV-00:10 0.20 -2.3
December 4956.43 0.60 01-DEC-10:55 -2.2 -4.1 0.00 0.00 01-DEC-00:10 -2.2 -4.1
                     
Annual Sum or Average 39143.63         0.00        
Minimum of Months 83.14 0.05   -31.7 -31.9 0.00 0.00   -31.7 -31.9
Maximum of Months 5644.77 0.60   24.75 21.89 0.00 0.00   24.75 21.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDORFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.855052E+09 1817.82 06-JAN-05:13 -26.7 -26.9 0.00 0.00 01-JAN-00:10 -26.7 -26.9
February 0.129148E+10 1505.12 05-FEB-09:23 -18.6 -19.2 0.00 0.00 01-FEB-00:10 -18.6 -19.2
March 0.172777E+10 1183.39 10-MAR-22:23 -9.4 -9.9 0.00 0.00 01-MAR-00:10 -9.4 -9.9
April 0.186621E+10 1730.59 17-APR-18:02 18.03 11.63 0.00 0.00 01-APR-00:10 18.03 11.63
May 0.232079E+10 1779.46 31-MAY-15:01 29.72 19.55 0.00 0.00 01-MAY-00:10 29.72 19.55
June 0.316098E+10 1973.29 21-JUN-19:01 17.93 14.32 0.00 0.00 01-JUN-00:10 17.93 14.32
July 0.384726E+10 2146.34 15-JUL-19:01 21.32 18.15 0.00 0.00 01-JUL-00:10 21.32 18.15
August 0.365795E+10 2086.29 29-AUG-18:03 20.37 14.64 0.00 0.00 01-AUG-00:10 20.37 14.64
September 0.265997E+10 1949.24 12-SEP-17:52 21.10 14.41 0.00 0.00 01-SEP-00:10 21.10 14.41
October 0.160512E+10 1094.64 11-OCT-18:22 14.85 9.29 0.00 0.00 01-OCT-00:10 14.85 9.29
November 0.154446E+10 1107.66 12-NOV-03:00 -7.8 -8.8 0.00 0.00 01-NOV-00:10 -7.8 -8.8
December 0.135332E+10 1589.16 11-DEC-20:10 -20.6 -20.9 0.00 0.00 01-DEC-00:10 -20.6 -20.9
                     
Annual Sum or Average 0.258904E+11         0.00        
Minimum of Months 0.855052E+09 1094.64   -26.7 -26.9 0.00 0.00   -26.7 -26.9
Maximum of Months 0.384726E+10 2146.34   29.72 19.55 0.00 0.00   29.72 19.55



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: REARSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.00 0.00 01-JAN-00:10 -2.8 -3.2
February 0.00 0.00 01-FEB-00:10 -24.1 -24.4 0.00 0.00 01-FEB-00:10 -24.1 -24.4
March 0.00 0.00 01-MAR-00:10 -11.0 -12.0 0.00 0.00 01-MAR-00:10 -11.0 -12.0
April 0.00 0.00 01-APR-00:10 -1.2 -2.2 0.00 0.00 01-APR-00:10 -1.2 -2.2
May 0.00 0.00 01-MAY-00:10 8.22 5.15 0.00 0.00 01-MAY-00:10 8.22 5.15
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.00 0.00 01-JUN-00:10 14.70 10.69
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 0.00 0.00 01-AUG-00:10 18.15 17.82 0.00 0.00 01-AUG-00:10 18.15 17.82
September 0.00 0.00 01-SEP-00:10 16.07 15.67 0.00 0.00 01-SEP-00:10 16.07 15.67
October 0.00 0.00 01-OCT-00:10 3.92 1.39 0.00 0.00 01-OCT-00:10 3.92 1.39
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.00 0.00 01-NOV-00:10 1.65 -0.5
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 0.00 0.00 01-DEC-00:10 -0.7 -1.3
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -24.1 -24.4 0.00 0.00   -24.1 -24.4
Maximum of Months 0.00 0.00   18.93 17.82 0.00 0.00   18.93 17.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM201

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 17173411.65 393.49 18-JAN-15:02 -17.3 -17.6 0.00 0.00 01-JAN-00:10 -17.3 -17.6
February 16513937.45 361.67 05-FEB-15:03 -15.6 -16.5 0.00 0.00 01-FEB-00:10 -15.6 -16.5
March 15684209.05 324.27 05-MAR-15:25 -9.4 -10.5 0.00 0.00 01-MAR-00:10 -9.4 -10.5
April 9979463.08 240.21 03-APR-15:00 -3.3 -5.4 0.00 0.00 01-APR-00:10 -3.3 -5.4
May 3188472.58 103.80 13-MAY-15:00 11.10 10.20 0.00 0.00 01-MAY-00:10 11.10 10.20
June 14801313.43 152.95 30-JUN-18:03 27.93 20.46 0.00 0.00 01-JUN-00:10 27.93 20.46
July 16445166.54 156.35 03-JUL-18:03 29.22 24.10 0.00 0.00 01-JUL-00:10 29.22 24.10
August 4191995.70 107.99 04-AUG-15:33 33.90 26.00 0.00 0.00 01-AUG-00:10 33.90 26.00
September 3692201.30 100.51 18-SEP-15:00 12.00 11.45 0.00 0.00 01-SEP-00:10 12.00 11.45
October 6977159.47 149.78 22-OCT-15:00 6.10 3.25 0.00 0.00 01-OCT-00:10 6.10 3.25
November 14868915.24 417.99 25-NOV-15:13 -17.4 -18.0 0.00 0.00 01-NOV-00:10 -17.4 -18.0
December 20235162.83 396.05 08-DEC-15:13 -16.1 -16.4 0.00 0.00 01-DEC-00:10 -16.1 -16.4
                     
Annual Sum or Average 0.143751E+09         0.00        
Minimum of Months 3188472.58 100.51   -17.4 -18.0 0.00 0.00   -17.4 -18.0
Maximum of Months 20235162.83 417.99   33.90 26.00 0.00 0.00   33.90 26.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM202_205

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.138528E+09 9438.95 14-JAN-09:01 -3.8 -4.0 0.474126E+09 284.93 31-JAN-00:49 -29.8 -30.0
February 0.410838E+09 9815.09 26-FEB-09:01 -2.0 -3.2 0.431971E+09 284.93 02-FEB-00:49 -2.0 -3.2
March 0.117165E+10 10161.73 21-MAR-08:61 -6.5 -8.1 0.486650E+09 290.57 23-MAR-18:10 13.53 8.78
April 0.260262E+10 10486.74 17-APR-16:51 19.40 11.31 0.486191E+09 420.47 18-APR-21:00 14.40 12.17
May 0.402328E+10 10728.57 21-MAY-17:01 17.70 9.59 0.526230E+09 451.05 31-MAY-21:30 21.00 15.98
June 0.496330E+10 10172.11 16-JUN-16:21 24.15 16.77 0.517627E+09 463.23 12-JUN-21:10 24.15 16.77
July 0.536123E+10 10307.10 22-JUL-16:31 19.97 14.36 0.549988E+09 463.91 20-JUL-21:10 19.97 14.36
August 0.508822E+10 10629.45 07-AUG-16:31 22.80 14.05 0.550888E+09 459.87 21-AUG-21:10 23.72 21.58
September 0.424226E+10 10585.24 12-SEP-16:21 23.90 15.37 0.506986E+09 463.44 07-SEP-21:10 23.90 15.37
October 0.271208E+10 9780.38 28-OCT-08:61 1.55 -0.3 0.497453E+09 369.23 20-OCT-20:19 1.55 -0.3
November 0.128947E+10 10213.63 12-NOV-09:01 -5.3 -6.6 0.469026E+09 284.93 28-NOV-00:40 -18.3 -18.5
December 0.235803E+09 9497.97 02-DEC-09:01 -0.2 -1.8 0.476137E+09 284.93 12-DEC-00:49 -20.0 -20.4
                     
Annual Sum or Average 0.322393E+11         0.597327E+10        
Minimum of Months 0.138528E+09 9438.95   -6.5 -8.1 0.431971E+09 284.93   -29.8 -30.0
Maximum of Months 0.536123E+10 10728.57   24.15 16.77 0.550888E+09 463.91   24.15 21.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM206_208

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.218460E+09 8266.02 02-JAN-09:01 -8.5 -9.0 0.357293E+09 213.69 31-JAN-00:49 -29.8 -30.0
February 0.533161E+09 8433.77 12-FEB-09:01 -7.2 -7.8 0.325669E+09 213.70 02-FEB-00:49 -7.2 -7.8
March 0.120257E+10 8591.88 21-MAR-08:61 -6.5 -8.1 0.366749E+09 225.85 23-MAR-18:10 13.53 8.78
April 0.228641E+10 8710.49 17-APR-16:51 19.40 11.31 0.365632E+09 314.37 18-APR-21:00 14.40 12.17
May 0.327952E+10 8940.89 21-MAY-17:01 17.70 9.59 0.394828E+09 335.12 31-MAY-21:30 21.00 15.98
June 0.393581E+10 8483.06 16-JUN-16:21 24.15 16.77 0.387915E+09 345.02 12-JUN-21:10 24.15 16.77
July 0.423193E+10 8584.33 22-JUL-16:31 19.97 14.36 0.411876E+09 345.26 20-JUL-21:10 19.97 14.36
August 0.401765E+10 8850.63 07-AUG-16:31 22.80 14.05 0.412593E+09 341.61 21-AUG-21:10 23.72 21.58
September 0.339466E+10 8837.65 24-SEP-16:11 14.63 7.59 0.380061E+09 343.89 07-SEP-21:10 14.63 7.59
October 0.227838E+10 8232.20 28-OCT-08:61 1.55 -0.3 0.373513E+09 280.50 20-OCT-20:19 1.55 -0.3
November 0.121272E+10 8679.89 12-NOV-09:01 -5.3 -6.6 0.353017E+09 213.69 28-NOV-00:49 -18.3 -18.5
December 0.348568E+09 8301.10 05-DEC-16:01 -5.1 -8.3 0.358921E+09 213.69 12-DEC-00:49 -20.0 -20.4
                     
Annual Sum or Average 0.269398E+11         0.448807E+10        
Minimum of Months 0.218460E+09 8232.20   -8.5 -9.0 0.325669E+09 213.69   -29.8 -30.0
Maximum of Months 0.423193E+10 8940.89   24.15 16.77 0.412593E+09 345.26   24.15 21.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM209_212

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.489474E+09 10490.23 15-JAN-09:01 -15.1 -15.8 0.478651E+09 284.92 31-JAN-01:39 -30.4 -30.6
February 0.825811E+09 10339.55 18-FEB-09:01 -13.4 -14.0 0.435764E+09 284.92 02-FEB-01:30 -13.4 -14.0
March 0.158567E+10 9767.03 05-MAR-19:01 -14.0 -14.7 0.489840E+09 301.35 23-MAR-18:10 13.53 8.78
April 0.261218E+10 9606.96 17-APR-16:51 19.40 11.31 0.486850E+09 414.45 10-APR-21:10 19.40 11.31
May 0.361790E+10 9921.24 21-MAY-17:01 17.70 9.59 0.524386E+09 434.62 12-MAY-21:10 17.70 9.59
June 0.429630E+10 9259.40 22-JUN-16:51 20.60 13.29 0.514892E+09 451.70 12-JUN-21:10 20.60 13.29
July 0.466032E+10 8999.45 24-JUL-16:21 23.10 17.52 0.546333E+09 450.17 20-JUL-21:10 23.10 17.52
August 0.448946E+10 9640.65 07-AUG-16:31 22.80 14.05 0.547607E+09 446.70 31-AUG-21:10 18.18 17.78
September 0.391555E+10 9760.02 20-SEP-17:01 20.13 11.51 0.505473E+09 448.09 07-SEP-21:10 20.13 11.51
October 0.283530E+10 9200.82 28-OCT-08:61 1.55 -0.3 0.498130E+09 374.07 20-OCT-20:19 1.55 -0.3
November 0.168740E+10 10482.78 25-NOV-09:01 -17.7 -18.0 0.472161E+09 284.92 26-NOV-02:00 -25.0 -25.3
December 0.735690E+09 10193.22 16-DEC-09:01 -11.9 -12.8 0.480895E+09 284.92 12-DEC-00:00 -11.9 -12.8
                     
Annual Sum or Average 0.317511E+11         0.598098E+10        
Minimum of Months 0.489474E+09 8999.45   -17.7 -18.0 0.435764E+09 284.92   -30.4 -30.6
Maximum of Months 0.466032E+10 10490.23   23.10 17.52 0.547607E+09 451.70   23.10 17.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM213

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 6961567.58 779.80 13-JAN-16:02 3.62 1.75 0.117311E+09 71.23 31-JAN-00:40 -29.6 -29.8
February 26676508.91 2193.13 25-FEB-09:01 0.78 -0.3 0.106783E+09 71.23 02-FEB-00:40 0.78 -0.3
March 0.128551E+09 2443.07 21-MAR-18:01 -2.7 -5.5 0.119955E+09 71.23 01-MAR-00:40 -2.7 -5.5
April 0.411269E+09 2599.79 17-APR-16:51 19.40 11.31 0.119584E+09 100.35 18-APR-21:49 14.78 12.42
May 0.765336E+09 2651.57 06-MAY-16:51 18.90 10.90 0.129497E+09 106.86 31-MAY-21:49 20.20 15.15
June 0.109447E+10 2508.02 22-JUN-16:51 20.60 13.29 0.127940E+09 109.73 12-JUN-21:10 20.60 13.29
July 0.125772E+10 2449.70 18-JUL-18:31 22.97 16.12 0.135867E+09 109.76 20-JUL-21:10 19.90 19.04
August 0.119411E+10 2648.25 06-AUG-17:01 19.03 11.91 0.136161E+09 108.53 21-AUG-21:10 23.72 21.58
September 0.946274E+09 2619.99 20-SEP-17:01 20.13 11.51 0.125591E+09 110.74 07-SEP-21:10 20.13 11.51
October 0.465659E+09 2364.64 28-OCT-08:61 1.55 -0.3 0.122983E+09 86.55 20-OCT-20:19 1.55 -0.3
November 0.180911E+09 2409.71 04-NOV-18:01 5.50 2.14 0.115996E+09 71.23 28-NOV-00:40 -18.3 -18.5
December 13674749.79 774.99 06-DEC-16:03 -4.2 -7.5 0.117794E+09 71.23 10-DEC-00:40 -19.4 -20.0
                     
Annual Sum or Average 0.649161E+10         0.147546E+10        
Minimum of Months 6961567.58 774.99   -4.2 -7.5 0.106783E+09 71.23   -29.6 -29.8
Maximum of Months 0.125772E+10 2651.57   22.97 16.12 0.136161E+09 110.74   23.72 21.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM214

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.160940E+09 3073.12 15-JAN-09:01 -15.1 -15.8 0.119814E+09 71.23 31-JAN-01:39 -30.4 -30.6
February 0.289604E+09 3030.30 18-FEB-09:01 -13.4 -14.0 0.109220E+09 71.23 03-FEB-00:49 -13.4 -14.0
March 0.563464E+09 2914.66 13-MAR-08:61 -7.7 -9.2 0.122890E+09 75.00 19-MAR-20:10 14.50 11.38
April 0.892176E+09 2973.76 17-APR-16:51 19.40 11.31 0.121525E+09 108.21 18-APR-21:10 16.32 13.39
May 0.132019E+10 3039.58 06-MAY-16:51 18.90 10.90 0.130320E+09 109.25 31-MAY-21:19 21.40 16.40
June 0.156285E+10 2868.73 22-JUN-16:41 20.68 13.36 0.128572E+09 111.13 12-JUN-21:40 20.68 13.36
July 0.169035E+10 2830.31 23-JUL-16:21 22.80 15.36 0.135920E+09 113.41 17-JUL-21:10 22.80 15.36
August 0.163526E+10 2937.97 06-AUG-16:51 19.40 12.05 0.136201E+09 112.46 01-AUG-21:19 19.40 12.05
September 0.143787E+10 3022.99 20-SEP-16:51 20.60 11.60 0.126231E+09 108.02 11-SEP-21:30 20.60 11.60
October 0.102737E+10 2867.43 20-OCT-16:51 19.20 11.72 0.124643E+09 93.65 20-OCT-20:19 14.63 9.75
November 0.592131E+09 3095.61 25-NOV-09:01 -17.7 -18.0 0.118280E+09 71.23 26-NOV-05:10 -25.2 -25.5
December 0.256695E+09 2935.70 25-DEC-09:01 -12.5 -12.9 0.120485E+09 71.23 10-DEC-00:49 -12.5 -12.9
                     
Annual Sum or Average 0.114289E+11         0.149410E+10        
Minimum of Months 0.160940E+09 2830.31   -17.7 -18.0 0.109220E+09 71.23   -30.4 -30.6
Maximum of Months 0.169035E+10 3095.61   22.80 15.36 0.136201E+09 113.41   22.80 16.40



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM215_218

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.217723E+10 2373.16 19-JAN-16:05 -22.9 -23.2 0.00 0.00 01-JAN-00:10 -22.9 -23.2
February 0.255866E+10 2580.30 24-FEB-17:21 5.55 3.92 0.00 0.00 01-FEB-00:10 5.55 3.92
March 0.378473E+10 3076.40 28-MAR-16:35 14.80 9.85 0.00 0.00 01-MAR-00:10 14.80 9.85
April 0.467030E+10 3760.54 18-APR-16:12 25.20 19.65 0.00 0.00 01-APR-00:10 25.20 19.65
May 0.616196E+10 4001.02 31-MAY-16:22 28.60 19.31 0.00 0.00 01-MAY-00:10 28.60 19.31
June 0.670389E+10 4079.25 29-JUN-16:22 29.70 20.49 0.00 0.00 01-JUN-00:10 29.70 20.49
July 0.733532E+10 4063.71 15-JUL-16:32 23.70 17.61 0.00 0.00 01-JUL-00:10 23.70 17.61
August 0.714017E+10 4056.03 02-AUG-16:22 28.90 22.60 0.00 0.00 01-AUG-00:10 28.90 22.60
September 0.615330E+10 4006.93 07-SEP-16:21 31.15 19.07 0.00 0.00 01-SEP-00:10 31.15 19.07
October 0.489687E+10 3362.05 20-OCT-16:35 19.90 12.06 0.00 0.00 01-OCT-00:10 19.90 12.06
November 0.354513E+10 3046.01 03-NOV-16:22 13.60 8.59 0.00 0.00 01-NOV-00:10 13.60 8.59
December 0.257336E+10 2382.19 03-DEC-17:22 1.40 -0.5 0.00 0.00 01-DEC-00:10 1.40 -0.5
                     
Annual Sum or Average 0.577009E+11         0.00        
Minimum of Months 0.217723E+10 2373.16   -22.9 -23.2 0.00 0.00   -22.9 -23.2
Maximum of Months 0.733532E+10 4079.25   31.15 22.60 0.00 0.00   31.15 22.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ELEVATORCOREFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.00 0.00 01-JAN-00:10 -2.8 -3.2
February 0.00 0.00 01-FEB-00:10 -24.1 -24.4 0.00 0.00 01-FEB-00:10 -24.1 -24.4
March 0.00 0.00 01-MAR-00:10 -11.0 -12.0 0.00 0.00 01-MAR-00:10 -11.0 -12.0
April 0.00 0.00 01-APR-00:10 -1.2 -2.2 0.00 0.00 01-APR-00:10 -1.2 -2.2
May 0.00 0.00 01-MAY-00:10 8.22 5.15 0.00 0.00 01-MAY-00:10 8.22 5.15
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.00 0.00 01-JUN-00:10 14.70 10.69
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 0.00 0.00 01-AUG-00:10 18.15 17.82 0.00 0.00 01-AUG-00:10 18.15 17.82
September 0.00 0.00 01-SEP-00:10 16.07 15.67 0.00 0.00 01-SEP-00:10 16.07 15.67
October 0.00 0.00 01-OCT-00:10 3.92 1.39 0.00 0.00 01-OCT-00:10 3.92 1.39
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.00 0.00 01-NOV-00:10 1.65 -0.5
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 0.00 0.00 01-DEC-00:10 -0.7 -1.3
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -24.1 -24.4 0.00 0.00   -24.1 -24.4
Maximum of Months 0.00 0.00   18.93 17.82 0.00 0.00   18.93 17.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM219

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.517150E+10 13168.56 31-JAN-10:41 -24.8 -25.1 0.132338E+09 160.00 30-JAN-22:10 -24.8 -25.1
February 0.472220E+10 13329.11 04-FEB-10:31 -24.8 -25.2 0.126467E+09 169.57 03-FEB-22:10 -24.8 -25.2
March 0.610673E+10 12975.34 28-MAR-16:51 14.40 9.63 0.125628E+09 105.69 19-MAR-18:10 14.40 9.63
April 0.629044E+10 13043.27 17-APR-16:51 19.40 11.31 0.125353E+09 144.67 14-APR-20:10 19.40 11.31
May 0.682761E+10 13099.84 21-MAY-19:21 13.90 7.66 0.138155E+09 157.18 30-MAY-21:10 19.82 17.01
June 0.688888E+10 13084.44 22-JUN-16:41 20.68 13.36 0.136552E+09 162.56 15-JUN-21:10 20.68 13.36
July 0.708466E+10 13078.87 23-JUL-16:21 22.80 15.36 0.146738E+09 159.07 11-JUL-21:10 22.80 15.36
August 0.701092E+10 13068.06 16-AUG-16:21 23.90 15.40 0.147097E+09 162.56 11-AUG-21:19 23.90 15.40
September 0.678498E+10 13058.41 14-SEP-16:51 17.80 10.93 0.132549E+09 162.53 01-SEP-21:19 17.80 10.93
October 0.667299E+10 12986.85 20-OCT-16:51 19.20 11.72 0.126485E+09 125.18 20-OCT-19:19 15.73 10.27
November 0.593312E+10 12899.38 03-NOV-16:11 14.07 8.84 0.120745E+09 122.71 26-NOV-05:00 -26.1 -26.4
December 0.560548E+10 7993.63 03-DEC-16:01 3.03 0.61 0.123858E+09 71.23 13-DEC-01:39 -12.8 -13.2
                     
Annual Sum or Average 0.750995E+11         0.158196E+10        
Minimum of Months 0.472220E+10 7993.63   -24.8 -25.2 0.120745E+09 71.23   -26.1 -26.4
Maximum of Months 0.708466E+10 13329.11   23.90 15.40 0.147097E+09 169.57   23.90 17.01



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM220_223

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.744344E+09 11335.34 07-JAN-09:01 -24.7 -25.1 0.480938E+09 284.92 31-JAN-03:09 -30.2 -30.4
February 0.103137E+10 11016.17 05-FEB-09:01 -19.1 -19.7 0.437731E+09 284.92 03-FEB-01:39 -19.1 -19.7
March 0.188351E+10 10251.90 05-MAR-09:01 -8.9 -9.7 0.491927E+09 297.76 23-MAR-18:10 13.53 8.78
April 0.274956E+10 9850.90 17-APR-16:51 19.40 11.31 0.485502E+09 423.01 18-APR-21:19 15.93 13.15
May 0.396977E+10 10022.19 06-MAY-16:51 18.90 10.90 0.519465E+09 427.39 31-MAY-21:30 21.00 15.98
June 0.447217E+10 9526.97 22-JUN-16:41 20.68 13.36 0.511723E+09 429.14 16-JUN-21:10 20.68 13.36
July 0.470852E+10 9320.43 23-JUL-16:21 22.80 15.36 0.539933E+09 441.21 17-JUL-21:10 22.80 15.36
August 0.452612E+10 9560.73 07-AUG-16:31 22.80 14.05 0.540715E+09 437.10 01-AUG-21:19 22.80 14.05
September 0.405410E+10 9917.00 20-SEP-16:51 20.60 11.60 0.502346E+09 427.42 07-SEP-21:19 20.60 11.60
October 0.303621E+10 9447.17 28-OCT-08:61 1.55 -0.3 0.497730E+09 364.58 20-OCT-20:19 1.55 -0.3
November 0.186487E+10 11336.40 26-NOV-09:01 -22.7 -23.1 0.473166E+09 284.92 26-NOV-05:10 -22.7 -23.1
December 0.971031E+09 11327.10 10-DEC-09:01 -18.7 -19.3 0.482766E+09 284.92 10-DEC-01:30 -18.7 -19.3
                     
Annual Sum or Average 0.340116E+11         0.596394E+10        
Minimum of Months 0.744344E+09 9320.43   -24.7 -25.1 0.437731E+09 284.92   -30.2 -30.4
Maximum of Months 0.470852E+10 11336.40   22.80 15.36 0.540715E+09 441.21   22.80 15.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM224

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 29175258.29 2496.41 14-JAN-09:01 -3.8 -4.0 0.118275E+09 71.23 31-JAN-00:40 -29.6 -29.8
February 75225774.76 2567.39 26-FEB-09:01 -2.0 -3.2 0.107724E+09 71.23 03-FEB-00:40 -2.0 -3.2
March 0.267363E+09 2725.53 21-MAR-08:61 -6.5 -8.1 0.121370E+09 71.23 01-MAR-00:40 -6.5 -8.1
April 0.588816E+09 2775.63 17-APR-16:51 19.40 11.31 0.120374E+09 104.30 18-APR-21:19 15.93 13.15
May 0.105238E+10 2828.66 06-MAY-16:51 18.90 10.90 0.129368E+09 106.82 31-MAY-21:40 20.60 15.57
June 0.132783E+10 2715.86 22-JUN-16:41 20.68 13.36 0.127871E+09 107.63 12-JUN-21:40 20.68 13.36
July 0.144267E+10 2666.46 23-JUL-16:21 22.80 15.36 0.135052E+09 110.19 17-JUL-21:10 22.80 15.36
August 0.136800E+10 2726.52 07-AUG-16:31 22.80 14.05 0.135185E+09 109.21 01-AUG-21:19 22.80 14.05
September 0.115029E+10 2799.01 20-SEP-16:51 20.60 11.60 0.125491E+09 106.86 07-SEP-21:19 20.60 11.60
October 0.685224E+09 2605.29 23-OCT-08:61 0.70 -1.1 0.123923E+09 86.59 20-OCT-20:19 0.70 -1.1
November 0.319269E+09 2758.25 12-NOV-09:01 -5.3 -6.6 0.117080E+09 71.23 28-NOV-00:40 -18.3 -18.5
December 44764374.76 2537.76 02-DEC-09:01 -0.2 -1.8 0.118815E+09 71.23 12-DEC-00:49 -20.0 -20.4
                     
Annual Sum or Average 0.835100E+10         0.148053E+10        
Minimum of Months 29175258.29 2496.41   -6.5 -8.1 0.107724E+09 71.23   -29.6 -29.8
Maximum of Months 0.144267E+10 2828.66   22.80 15.36 0.135185E+09 110.19   22.80 15.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONTSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.00 0.00 01-JAN-00:10 -2.8 -3.2
February 0.00 0.00 01-FEB-00:10 -24.1 -24.4 0.00 0.00 01-FEB-00:10 -24.1 -24.4
March 0.00 0.00 01-MAR-00:10 -11.0 -12.0 0.00 0.00 01-MAR-00:10 -11.0 -12.0
April 0.00 0.00 01-APR-00:10 -1.2 -2.2 0.00 0.00 01-APR-00:10 -1.2 -2.2
May 0.00 0.00 01-MAY-00:10 8.22 5.15 0.00 0.00 01-MAY-00:10 8.22 5.15
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.00 0.00 01-JUN-00:10 14.70 10.69
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 0.00 0.00 01-AUG-00:10 18.15 17.82 0.00 0.00 01-AUG-00:10 18.15 17.82
September 0.00 0.00 01-SEP-00:10 16.07 15.67 0.00 0.00 01-SEP-00:10 16.07 15.67
October 0.00 0.00 01-OCT-00:10 3.92 1.39 0.00 0.00 01-OCT-00:10 3.92 1.39
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.00 0.00 01-NOV-00:10 1.65 -0.5
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 0.00 0.00 01-DEC-00:10 -0.7 -1.3
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -24.1 -24.4 0.00 0.00   -24.1 -24.4
Maximum of Months 0.00 0.00   18.93 17.82 0.00 0.00   18.93 17.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONTSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 251.26 0.18 28-JAN-01:00 -22.8 -23.0 0.00 0.00 01-JAN-00:10 -22.8 -23.0
February 443.49 0.23 06-FEB-12:50 -7.5 -8.2 0.00 0.00 01-FEB-00:10 -7.5 -8.2
March 51.64 0.09 28-MAR-10:45 12.33 7.42 0.00 0.00 01-MAR-00:10 12.33 7.42
April 247.94 0.16 18-APR-09:55 25.60 20.52 0.00 0.00 01-APR-00:10 25.60 20.52
May 20.90 0.06 02-MAY-10:45 7.52 4.19 0.00 0.00 01-MAY-00:10 7.52 4.19
June 18.22 0.03 09-JUN-08:11 22.23 17.14 0.00 0.00 01-JUN-00:10 22.23 17.14
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 16.31 0.04 11-AUG-09:55 25.60 18.63 0.00 0.00 01-AUG-00:10 25.60 18.63
September 121.22 0.11 15-SEP-09:55 17.20 12.64 0.00 0.00 01-SEP-00:10 17.20 12.64
October 5.48 0.02 19-OCT-10:45 12.62 6.98 0.00 0.00 01-OCT-00:10 12.62 6.98
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.00 0.00 01-NOV-00:10 1.65 -0.5
December 412.54 0.18 09-DEC-03:00 -22.2 -22.5 0.00 0.00 01-DEC-00:10 -22.2 -22.5
                     
Annual Sum or Average 1589.01         0.00        
Minimum of Months 0.00 0.00   -22.8 -23.0 0.00 0.00   -22.8 -23.0
Maximum of Months 443.49 0.23   25.60 20.52 0.00 0.00   25.60 20.52



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: REARSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 3536.04 0.51 27-JAN-10:55 -17.8 -18.4 0.00 0.00 01-JAN-00:10 -17.8 -18.4
February 2474.59 0.51 02-FEB-10:55 -31.7 -31.9 0.00 0.00 01-FEB-00:10 -31.7 -31.9
March 4443.12 0.35 05-MAR-10:55 -8.3 -9.3 0.00 0.00 01-MAR-00:10 -8.3 -9.3
April 6434.90 0.39 15-APR-10:45 25.13 19.38 0.00 0.00 01-APR-00:10 25.13 19.38
May 1127.61 0.27 02-MAY-10:45 7.52 4.19 0.00 0.00 01-MAY-00:10 7.52 4.19
June 947.89 0.16 13-JUN-11:40 25.40 22.38 0.00 0.00 01-JUN-00:10 25.40 22.38
July 264.45 0.09 31-JUL-13:40 26.30 21.26 0.00 0.00 01-JUL-00:10 26.30 21.26
August 1612.60 0.28 11-AUG-10:45 27.43 19.26 0.00 0.00 01-AUG-00:10 27.43 19.26
September 7096.42 0.37 20-SEP-10:45 20.40 11.74 0.00 0.00 01-SEP-00:10 20.40 11.74
October 5196.54 0.43 20-OCT-10:45 17.62 11.24 0.00 0.00 01-OCT-00:10 17.62 11.24
November 1923.64 0.42 11-NOV-11:35 0.20 -2.3 0.00 0.00 01-NOV-00:10 0.20 -2.3
December 3812.98 0.55 01-DEC-10:55 -2.2 -4.1 0.00 0.00 01-DEC-00:10 -2.2 -4.1
                     
Annual Sum or Average 38870.78         0.00        
Minimum of Months 264.45 0.09   -31.7 -31.9 0.00 0.00   -31.7 -31.9
Maximum of Months 7096.42 0.55   27.43 22.38 0.00 0.00   27.43 22.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDORFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.00 0.00 01-JAN-00:10 -2.8 -3.2
February 31748842.19 871.11 08-FEB-19:35 -0.4 -1.2 0.00 0.00 01-FEB-00:10 -0.4 -1.2
March 0.427594E+09 874.61 24-MAR-22:35 0.20 -0.9 0.00 0.00 01-MAR-00:10 0.20 -0.9
April 0.990046E+09 1057.70 06-APR-06:12 -4.4 -5.2 0.00 0.00 01-APR-00:10 -4.4 -5.2
May 0.125788E+10 1231.18 31-MAY-18:13 26.83 18.97 0.00 0.00 01-MAY-00:10 26.83 18.97
June 0.185070E+10 1318.65 30-JUN-18:50 26.47 19.59 0.00 0.00 01-JUN-00:10 26.47 19.59
July 0.217256E+10 1414.68 15-JUL-18:52 21.70 18.33 0.00 0.00 01-JUL-00:10 21.70 18.33
August 0.188128E+10 1303.48 04-AUG-18:42 19.18 18.72 0.00 0.00 01-AUG-00:10 19.18 18.72
September 0.145541E+10 1221.03 07-SEP-15:13 31.70 18.53 0.00 0.00 01-SEP-00:10 31.70 18.53
October 0.116204E+10 895.32 31-OCT-18:45 -0.3 -2.1 0.00 0.00 01-OCT-00:10 -0.3 -2.1
November 0.358593E+09 808.59 04-NOV-02:00 1.70 0.39 0.00 0.00 01-NOV-00:10 1.70 0.39
December 211557.72 33.98 03-DEC-15:00 5.00 1.89 0.00 0.00 01-DEC-00:10 5.00 1.89
                     
Annual Sum or Average 0.115881E+11         0.00        
Minimum of Months 0.00 0.00   -4.4 -5.2 0.00 0.00   -4.4 -5.2
Maximum of Months 0.217256E+10 1414.68   31.70 19.59 0.00 0.00   31.70 19.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: REARSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.00 0.00 01-JAN-00:10 -2.8 -3.2
February 0.00 0.00 01-FEB-00:10 -24.1 -24.4 0.00 0.00 01-FEB-00:10 -24.1 -24.4
March 0.00 0.00 01-MAR-00:10 -11.0 -12.0 0.00 0.00 01-MAR-00:10 -11.0 -12.0
April 0.00 0.00 01-APR-00:10 -1.2 -2.2 0.00 0.00 01-APR-00:10 -1.2 -2.2
May 0.00 0.00 01-MAY-00:10 8.22 5.15 0.00 0.00 01-MAY-00:10 8.22 5.15
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.00 0.00 01-JUN-00:10 14.70 10.69
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 0.00 0.00 01-AUG-00:10 18.15 17.82 0.00 0.00 01-AUG-00:10 18.15 17.82
September 0.00 0.00 01-SEP-00:10 16.07 15.67 0.00 0.00 01-SEP-00:10 16.07 15.67
October 0.00 0.00 01-OCT-00:10 3.92 1.39 0.00 0.00 01-OCT-00:10 3.92 1.39
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.00 0.00 01-NOV-00:10 1.65 -0.5
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 0.00 0.00 01-DEC-00:10 -0.7 -1.3
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -24.1 -24.4 0.00 0.00   -24.1 -24.4
Maximum of Months 0.00 0.00   18.93 17.82 0.00 0.00   18.93 17.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM301

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 4886619.71 294.63 02-JAN-15:03 -8.5 -9.8 0.00 0.00 01-JAN-00:10 -8.5 -9.8
February 10764411.41 281.69 17-FEB-15:13 -6.7 -8.6 0.00 0.00 01-FEB-00:10 -6.7 -8.6
March 13741592.48 306.53 05-MAR-15:03 -9.4 -10.5 0.00 0.00 01-MAR-00:10 -9.4 -10.5
April 10427769.62 239.75 01-APR-14:13 -2.6 -3.3 0.00 0.00 01-APR-00:10 -2.6 -3.3
May 3749363.14 119.82 13-MAY-15:00 11.10 10.20 0.00 0.00 01-MAY-00:10 11.10 10.20
June 13895601.08 159.85 30-JUN-18:03 27.93 20.46 0.00 0.00 01-JUN-00:10 27.93 20.46
July 12328446.04 159.21 03-JUL-18:03 29.22 24.10 0.00 0.00 01-JUL-00:10 29.22 24.10
August 2288649.51 91.80 04-AUG-16:02 33.15 26.05 0.00 0.00 01-AUG-00:10 33.15 26.05
September 3025343.58 117.60 18-SEP-15:00 12.00 11.45 0.00 0.00 01-SEP-00:10 12.00 11.45
October 6928127.96 152.31 22-OCT-15:00 6.10 3.25 0.00 0.00 01-OCT-00:10 6.10 3.25
November 10391051.22 286.27 21-NOV-15:13 -6.7 -8.4 0.00 0.00 01-NOV-00:10 -6.7 -8.4
December 8866089.40 276.67 20-DEC-15:03 -7.4 -8.8 0.00 0.00 01-DEC-00:10 -7.4 -8.8
                     
Annual Sum or Average 0.101293E+09         0.00        
Minimum of Months 2288649.51 91.80   -9.4 -10.5 0.00 0.00   -9.4 -10.5
Maximum of Months 13895601.08 306.53   33.15 26.05 0.00 0.00   33.15 26.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM302_305

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 79882343.53 2164.51 30-JAN-15:02 -24.0 -24.3 0.00 0.00 01-JAN-00:10 -24.0 -24.3
February 79630379.83 2275.44 01-FEB-15:02 -26.1 -26.4 0.00 0.00 01-FEB-00:10 -26.1 -26.4
March 74143419.18 1431.24 05-MAR-15:25 -9.4 -10.5 0.00 0.00 01-MAR-00:10 -9.4 -10.5
April 49796373.54 1077.43 01-APR-14:13 -2.6 -3.3 0.00 0.00 01-APR-00:10 -2.6 -3.3
May 20417287.84 539.64 13-MAY-15:00 11.10 10.20 0.00 0.00 01-MAY-00:10 11.10 10.20
June 50845995.97 558.20 01-JUN-14:05 11.08 10.67 0.00 0.00 01-JUN-00:10 11.08 10.67
July 63312182.37 530.77 05-JUL-17:37 26.70 20.97 0.00 0.00 01-JUL-00:10 26.70 20.97
August 17069375.57 339.45 02-AUG-16:45 28.90 22.60 0.00 0.00 01-AUG-00:10 28.90 22.60
September 17954901.18 517.99 18-SEP-15:00 12.00 11.45 0.00 0.00 01-SEP-00:10 12.00 11.45
October 35128832.45 684.38 22-OCT-14:05 6.27 3.67 0.00 0.00 01-OCT-00:10 6.27 3.67
November 65786366.31 1845.56 25-NOV-15:13 -17.4 -18.0 0.00 0.00 01-NOV-00:10 -17.4 -18.0
December 87283607.65 1736.88 08-DEC-15:13 -16.1 -16.4 0.00 0.00 01-DEC-00:10 -16.1 -16.4
                     
Annual Sum or Average 0.641251E+09         0.00        
Minimum of Months 17069375.57 339.45   -26.1 -26.4 0.00 0.00   -26.1 -26.4
Maximum of Months 87283607.65 2275.44   28.90 22.60 0.00 0.00   28.90 22.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM306_308

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 82795030.72 1705.43 30-JAN-15:02 -24.0 -24.3 0.00 0.00 01-JAN-00:10 -24.0 -24.3
February 70880787.59 1909.41 02-FEB-15:02 -28.9 -29.2 0.00 0.00 01-FEB-00:10 -28.9 -29.2
March 59165450.69 1148.77 05-MAR-15:25 -9.4 -10.5 0.00 0.00 01-MAR-00:10 -9.4 -10.5
April 39787869.30 855.48 03-APR-15:00 -3.3 -5.4 0.00 0.00 01-APR-00:10 -3.3 -5.4
May 16244363.56 409.19 13-MAY-15:00 11.10 10.20 0.00 0.00 01-MAY-00:10 11.10 10.20
June 46233817.56 440.59 30-JUN-17:37 28.30 20.49 0.00 0.00 01-JUN-00:10 28.30 20.49
July 59188630.32 478.47 05-JUL-17:27 26.70 20.86 0.00 0.00 01-JUL-00:10 26.70 20.86
August 18025265.78 331.47 02-AUG-16:33 28.90 22.60 0.00 0.00 01-AUG-00:10 28.90 22.60
September 15041391.76 388.83 18-SEP-15:00 12.00 11.45 0.00 0.00 01-SEP-00:10 12.00 11.45
October 27324218.51 526.79 22-OCT-15:00 6.10 3.25 0.00 0.00 01-OCT-00:10 6.10 3.25
November 56656320.21 1466.17 25-NOV-15:13 -17.4 -18.0 0.00 0.00 01-NOV-00:10 -17.4 -18.0
December 77022988.18 1436.01 11-DEC-15:03 -19.5 -20.0 0.00 0.00 01-DEC-00:10 -19.5 -20.0
                     
Annual Sum or Average 0.568366E+09         0.00        
Minimum of Months 15041391.76 331.47   -28.9 -29.2 0.00 0.00   -28.9 -29.2
Maximum of Months 82795030.72 1909.41   28.90 22.60 0.00 0.00   28.90 22.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM309_312

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.188640E+09 8839.46 02-JAN-09:01 -8.5 -9.0 0.475111E+09 284.93 31-JAN-00:40 -29.6 -29.8
February 0.487449E+09 8987.02 12-FEB-09:01 -7.2 -7.8 0.432698E+09 284.93 02-FEB-00:40 -7.2 -7.8
March 0.115195E+10 9120.70 04-MAR-09:01 -7.0 -7.7 0.486804E+09 296.44 19-MAR-20:10 14.50 11.38
April 0.224218E+10 9133.72 17-APR-16:51 19.40 11.31 0.484691E+09 413.63 10-APR-21:10 19.40 11.31
May 0.333112E+10 9437.87 21-MAY-17:01 17.70 9.59 0.523349E+09 438.00 12-MAY-21:10 17.70 9.59
June 0.404354E+10 8782.32 22-JUN-16:51 20.60 13.29 0.513879E+09 449.03 12-JUN-21:10 20.60 13.29
July 0.442377E+10 8536.74 18-JUL-18:31 22.97 16.12 0.544779E+09 447.40 20-JUL-21:10 19.90 19.04
August 0.416329E+10 9123.29 06-AUG-17:01 19.03 11.91 0.545828E+09 442.14 21-AUG-21:10 23.72 21.58
September 0.335067E+10 9189.28 20-SEP-17:01 20.13 11.51 0.503398E+09 444.65 07-SEP-21:10 20.13 11.51
October 0.205223E+10 8636.32 28-OCT-08:61 1.55 -0.3 0.494827E+09 366.91 20-OCT-20:19 1.55 -0.3
November 0.102641E+10 9168.14 12-NOV-09:01 -5.3 -6.6 0.468148E+09 284.92 26-NOV-01:39 -24.4 -24.7
December 0.294970E+09 8680.54 17-DEC-09:01 -5.5 -5.9 0.476825E+09 284.93 10-DEC-00:40 -5.5 -5.9
                     
Annual Sum or Average 0.267562E+11         0.595034E+10        
Minimum of Months 0.188640E+09 8536.74   -8.5 -9.0 0.432698E+09 284.92   -29.6 -29.8
Maximum of Months 0.442377E+10 9437.87   22.97 16.12 0.545828E+09 449.03   23.72 21.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM313

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 14654013.89 418.05 05-JAN-15:03 -18.0 -18.7 0.00 0.00 01-JAN-00:10 -18.0 -18.7
February 16244313.27 381.07 05-FEB-15:03 -15.6 -16.5 0.00 0.00 01-FEB-00:10 -15.6 -16.5
March 16258550.61 338.39 05-MAR-15:25 -9.4 -10.5 0.00 0.00 01-MAR-00:10 -9.4 -10.5
April 10327449.39 246.08 03-APR-15:00 -3.3 -5.4 0.00 0.00 01-APR-00:10 -3.3 -5.4
May 2707973.89 111.89 13-MAY-15:00 11.10 10.20 0.00 0.00 01-MAY-00:10 11.10 10.20
June 1997608.08 113.19 01-JUN-15:00 11.00 9.83 0.00 0.00 01-JUN-00:10 11.00 9.83
July 1319786.84 61.03 05-JUL-18:03 26.52 21.27 0.00 0.00 01-JUL-00:10 26.52 21.27
August 148771.17 31.96 30-AUG-15:00 17.80 14.99 0.00 0.00 01-AUG-00:10 17.80 14.99
September 2465800.77 108.78 18-SEP-15:00 12.00 11.45 0.00 0.00 01-SEP-00:10 12.00 11.45
October 6917670.11 151.64 22-OCT-15:00 6.10 3.25 0.00 0.00 01-OCT-00:10 6.10 3.25
November 14071520.35 436.63 25-NOV-15:13 -17.4 -18.0 0.00 0.00 01-NOV-00:10 -17.4 -18.0
December 19428350.99 409.29 08-DEC-15:13 -16.1 -16.4 0.00 0.00 01-DEC-00:10 -16.1 -16.4
                     
Annual Sum or Average 0.106542E+09         0.00        
Minimum of Months 148771.17 31.96   -18.0 -18.7 0.00 0.00   -18.0 -18.7
Maximum of Months 19428350.99 436.63   26.52 21.27 0.00 0.00   26.52 21.27



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM314

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 15711871.73 1372.02 13-JAN-19:01 0.40 -0.6 0.117652E+09 71.23 31-JAN-00:40 -29.6 -29.8
February 57302235.55 2334.00 26-FEB-09:01 -2.0 -3.2 0.107305E+09 71.23 02-FEB-00:40 -2.0 -3.2
March 0.228427E+09 2379.65 21-MAR-18:01 -2.7 -5.5 0.120931E+09 71.23 01-MAR-00:40 -2.7 -5.5
April 0.571633E+09 2589.33 17-APR-16:51 19.40 11.31 0.120186E+09 107.40 18-APR-21:10 16.32 13.39
May 0.105346E+10 2634.67 06-MAY-16:51 18.90 10.90 0.129601E+09 109.06 31-MAY-21:19 21.40 16.40
June 0.137004E+10 2488.39 22-JUN-16:41 20.68 13.36 0.128093E+09 109.43 20-JUN-21:19 20.68 13.36
July 0.152061E+10 2444.00 23-JUL-16:21 22.80 15.36 0.135349E+09 113.03 27-JUL-21:10 20.92 17.78
August 0.142177E+10 2491.67 06-AUG-16:51 19.40 12.05 0.135496E+09 111.97 01-AUG-21:19 19.40 12.05
September 0.110843E+10 2549.02 20-SEP-16:51 20.60 11.60 0.125498E+09 106.86 06-SEP-21:10 20.60 11.60
October 0.546798E+09 2360.39 20-OCT-20:11 14.63 9.75 0.123261E+09 88.93 20-OCT-20:19 14.63 9.75
November 0.213233E+09 2344.43 04-NOV-08:61 2.77 0.71 0.116270E+09 71.23 28-NOV-00:40 -18.3 -18.5
December 24546152.56 2278.52 03-DEC-09:01 -1.5 -1.7 0.118120E+09 71.23 10-DEC-00:40 -19.4 -20.0
                     
Annual Sum or Average 0.813196E+10         0.147776E+10        
Minimum of Months 15711871.73 1372.02   -2.7 -5.5 0.107305E+09 71.23   -29.6 -29.8
Maximum of Months 0.152061E+10 2634.67   22.80 15.36 0.135496E+09 113.03   21.40 17.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM315_318

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.202672E+10 12838.43 07-JAN-09:01 -24.7 -25.1 0.487558E+09 284.92 31-JAN-05:19 -30.6 -30.8
February 0.235013E+10 12564.51 05-FEB-09:01 -19.1 -19.7 0.443456E+09 284.92 02-FEB-05:19 -19.1 -19.7
March 0.360086E+10 11768.97 06-MAR-09:01 -9.5 -10.4 0.496857E+09 327.75 19-MAR-20:10 14.50 11.38
April 0.450171E+10 11615.39 30-APR-17:11 15.60 8.87 0.489736E+09 454.05 18-APR-21:10 15.60 8.87
May 0.578542E+10 11715.48 21-MAY-16:51 17.80 9.67 0.525159E+09 456.42 31-MAY-21:19 21.40 16.40
June 0.626240E+10 11634.81 22-JUN-16:21 20.85 13.49 0.517334E+09 459.64 12-JUN-21:40 20.85 13.49
July 0.654459E+10 11064.07 15-JUL-16:21 23.60 17.57 0.547140E+09 469.83 17-JUL-21:10 20.92 19.44
August 0.629014E+10 11202.01 06-AUG-16:51 19.40 12.05 0.547946E+09 467.60 01-AUG-21:19 19.40 12.05
September 0.562427E+10 11498.34 24-SEP-16:11 14.63 7.59 0.506550E+09 442.78 11-SEP-21:30 14.63 7.59
October 0.451233E+10 11131.02 30-OCT-16:11 12.97 7.94 0.499612E+09 380.40 20-OCT-20:19 12.97 7.94
November 0.319159E+10 12824.78 26-NOV-09:01 -22.7 -23.1 0.477151E+09 284.92 26-NOV-03:30 -22.7 -23.1
December 0.229203E+10 12736.56 10-DEC-09:01 -18.7 -19.3 0.489278E+09 284.92 10-DEC-05:19 -18.7 -19.3
                     
Annual Sum or Average 0.529822E+11         0.602778E+10        
Minimum of Months 0.202672E+10 11064.07   -24.7 -25.1 0.443456E+09 284.92   -30.6 -30.8
Maximum of Months 0.654459E+10 12838.43   23.60 17.57 0.547946E+09 469.83   21.40 19.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ELEVATORCOREFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.00 0.00 01-JAN-00:10 -2.8 -3.2
February 0.00 0.00 01-FEB-00:10 -24.1 -24.4 0.00 0.00 01-FEB-00:10 -24.1 -24.4
March 0.00 0.00 01-MAR-00:10 -11.0 -12.0 0.00 0.00 01-MAR-00:10 -11.0 -12.0
April 0.00 0.00 01-APR-00:10 -1.2 -2.2 0.00 0.00 01-APR-00:10 -1.2 -2.2
May 0.00 0.00 01-MAY-00:10 8.22 5.15 0.00 0.00 01-MAY-00:10 8.22 5.15
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.00 0.00 01-JUN-00:10 14.70 10.69
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 0.00 0.00 01-AUG-00:10 18.15 17.82 0.00 0.00 01-AUG-00:10 18.15 17.82
September 0.00 0.00 01-SEP-00:10 16.07 15.67 0.00 0.00 01-SEP-00:10 16.07 15.67
October 0.00 0.00 01-OCT-00:10 3.92 1.39 0.00 0.00 01-OCT-00:10 3.92 1.39
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.00 0.00 01-NOV-00:10 1.65 -0.5
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 0.00 0.00 01-DEC-00:10 -0.7 -1.3
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -24.1 -24.4 0.00 0.00   -24.1 -24.4
Maximum of Months 0.00 0.00   18.93 17.82 0.00 0.00   18.93 17.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM319

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 36720888.87 570.55 30-JAN-15:25 -24.1 -24.5 0.00 0.00 01-JAN-00:10 -24.1 -24.5
February 27155549.40 644.15 02-FEB-15:25 -28.9 -29.2 0.00 0.00 01-FEB-00:10 -28.9 -29.2
March 17575112.73 363.27 05-MAR-15:25 -9.4 -10.5 0.00 0.00 01-MAR-00:10 -9.4 -10.5
April 10812715.02 258.20 01-APR-14:13 -2.6 -3.3 0.00 0.00 01-APR-00:10 -2.6 -3.3
May 8698982.80 147.00 31-MAY-09:11 26.47 19.61 0.00 0.00 01-MAY-00:10 26.47 19.61
June 36492766.10 140.73 29-JUN-09:02 25.78 20.55 0.00 0.00 01-JUN-00:10 25.78 20.55
July 44599560.96 147.02 05-JUL-08:52 22.80 20.41 0.00 0.00 01-JUL-00:10 22.80 20.41
August 18427146.91 157.91 02-AUG-09:11 24.47 20.38 0.00 0.00 01-AUG-00:10 24.47 20.38
September 6186487.41 95.65 28-SEP-15:00 10.00 5.63 0.00 0.00 01-SEP-00:10 10.00 5.63
October 6902142.93 151.14 22-OCT-15:00 6.10 3.25 0.00 0.00 01-OCT-00:10 6.10 3.25
November 18233944.40 457.40 25-NOV-15:13 -17.4 -18.0 0.00 0.00 01-NOV-00:10 -17.4 -18.0
December 29389030.43 489.08 11-DEC-15:25 -19.7 -20.2 0.00 0.00 01-DEC-00:10 -19.7 -20.2
                     
Annual Sum or Average 0.261194E+09         0.00        
Minimum of Months 6186487.41 95.65   -28.9 -29.2 0.00 0.00   -28.9 -29.2
Maximum of Months 44599560.96 644.15   26.47 20.55 0.00 0.00   26.47 20.55



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM320_323

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.380450E+09 9750.64 15-JAN-09:01 -15.1 -15.8 0.477763E+09 284.92 31-JAN-00:49 -29.8 -30.0
February 0.693970E+09 9644.64 18-FEB-09:01 -13.4 -14.0 0.435061E+09 284.93 03-FEB-00:40 -13.4 -14.0
March 0.144369E+10 9225.11 05-MAR-09:01 -8.9 -9.7 0.489516E+09 290.85 19-MAR-20:10 14.50 11.38
April 0.230927E+10 8778.23 17-APR-16:51 19.40 11.31 0.483612E+09 418.47 18-APR-21:10 16.32 13.39
May 0.350222E+10 8949.46 06-MAY-16:51 18.90 10.90 0.517945E+09 426.15 31-MAY-21:40 20.60 15.57
June 0.406773E+10 8527.79 22-JUN-16:41 20.68 13.36 0.510301E+09 427.42 16-JUN-21:19 20.68 13.36
July 0.435509E+10 8352.73 23-JUL-16:21 22.80 15.36 0.537983E+09 437.48 17-JUL-21:10 22.80 15.36
August 0.411140E+10 8550.46 07-AUG-16:31 22.80 14.05 0.538540E+09 430.56 01-AUG-21:19 22.80 14.05
September 0.342101E+10 8712.99 20-SEP-16:51 20.60 11.60 0.500410E+09 427.42 07-SEP-21:19 20.60 11.60
October 0.221310E+10 8496.45 28-OCT-08:61 1.55 -0.3 0.495505E+09 354.04 20-OCT-20:19 1.55 -0.3
November 0.123122E+10 9865.03 25-NOV-09:01 -17.7 -18.0 0.470041E+09 284.92 26-NOV-02:30 -24.7 -25.0
December 0.518431E+09 9453.93 16-DEC-09:01 -11.9 -12.8 0.479274E+09 284.92 10-DEC-00:40 -11.9 -12.8
                     
Annual Sum or Average 0.282476E+11         0.593595E+10        
Minimum of Months 0.380450E+09 8352.73   -17.7 -18.0 0.435061E+09 284.92   -29.8 -30.0
Maximum of Months 0.435509E+10 9865.03   22.80 15.36 0.538540E+09 437.48   22.80 15.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM324

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 30340993.31 524.42 30-JAN-15:02 -24.0 -24.3 0.00 0.00 01-JAN-00:10 -24.0 -24.3
February 21566688.01 587.19 02-FEB-15:02 -28.9 -29.2 0.00 0.00 01-FEB-00:10 -28.9 -29.2
March 18235366.28 357.50 05-MAR-15:25 -9.4 -10.5 0.00 0.00 01-MAR-00:10 -9.4 -10.5
April 11227233.57 267.72 01-APR-14:13 -2.6 -3.3 0.00 0.00 01-APR-00:10 -2.6 -3.3
May 3154621.79 119.70 13-MAY-15:00 11.10 10.20 0.00 0.00 01-MAY-00:10 11.10 10.20
June 1534931.54 125.33 01-JUN-15:00 11.00 9.83 0.00 0.00 01-JUN-00:10 11.00 9.83
July 243229.09 41.41 10-JUL-14:10 16.47 14.47 0.00 0.00 01-JUL-00:10 16.47 14.47
August 108747.82 25.07 30-AUG-15:00 17.80 14.99 0.00 0.00 01-AUG-00:10 17.80 14.99
September 2913481.24 110.34 18-SEP-15:00 12.00 11.45 0.00 0.00 01-SEP-00:10 12.00 11.45
October 7846238.59 163.82 22-OCT-15:00 6.10 3.25 0.00 0.00 01-OCT-00:10 6.10 3.25
November 18687054.77 458.11 25-NOV-15:13 -17.4 -18.0 0.00 0.00 01-NOV-00:10 -17.4 -18.0
December 26751950.14 449.31 11-DEC-15:03 -19.5 -20.0 0.00 0.00 01-DEC-00:10 -19.5 -20.0
                     
Annual Sum or Average 0.142611E+09         0.00        
Minimum of Months 108747.82 25.07   -28.9 -29.2 0.00 0.00   -28.9 -29.2
Maximum of Months 30340993.31 587.19   17.80 14.99 0.00 0.00   17.80 14.99



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONTSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.00 0.00 01-JAN-00:10 -2.8 -3.2
February 0.00 0.00 01-FEB-00:10 -24.1 -24.4 0.00 0.00 01-FEB-00:10 -24.1 -24.4
March 0.00 0.00 01-MAR-00:10 -11.0 -12.0 0.00 0.00 01-MAR-00:10 -11.0 -12.0
April 0.00 0.00 01-APR-00:10 -1.2 -2.2 0.00 0.00 01-APR-00:10 -1.2 -2.2
May 0.00 0.00 01-MAY-00:10 8.22 5.15 0.00 0.00 01-MAY-00:10 8.22 5.15
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.00 0.00 01-JUN-00:10 14.70 10.69
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 0.00 0.00 01-AUG-00:10 18.15 17.82 0.00 0.00 01-AUG-00:10 18.15 17.82
September 0.00 0.00 01-SEP-00:10 16.07 15.67 0.00 0.00 01-SEP-00:10 16.07 15.67
October 0.00 0.00 01-OCT-00:10 3.92 1.39 0.00 0.00 01-OCT-00:10 3.92 1.39
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.00 0.00 01-NOV-00:10 1.65 -0.5
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 0.00 0.00 01-DEC-00:10 -0.7 -1.3
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -24.1 -24.4 0.00 0.00   -24.1 -24.4
Maximum of Months 0.00 0.00   18.93 17.82 0.00 0.00   18.93 17.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONTSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 365.46 0.19 28-JAN-01:00 -22.8 -23.0 0.00 0.00 01-JAN-00:10 -22.8 -23.0
February 561.69 0.28 06-FEB-12:40 -7.8 -8.5 0.00 0.00 01-FEB-00:10 -7.8 -8.5
March 70.25 0.05 06-MAR-11:35 -2.9 -4.6 0.00 0.00 01-MAR-00:10 -2.9 -4.6
April 332.42 0.21 18-APR-09:55 25.60 20.52 0.00 0.00 01-APR-00:10 25.60 20.52
May 5.33 0.01 02-MAY-10:45 7.52 4.19 0.00 0.00 01-MAY-00:10 7.52 4.19
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.00 0.00 01-JUN-00:10 14.70 10.69
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 0.00 0.00 01-AUG-00:10 18.15 17.82 0.00 0.00 01-AUG-00:10 18.15 17.82
September 27.95 0.03 15-SEP-09:55 17.20 12.64 0.00 0.00 01-SEP-00:10 17.20 12.64
October 9.03 0.02 19-OCT-10:45 12.62 6.98 0.00 0.00 01-OCT-00:10 12.62 6.98
November 15.83 0.03 26-NOV-06:00 -26.1 -26.4 0.00 0.00 01-NOV-00:10 -26.1 -26.4
December 161.02 0.19 09-DEC-03:00 -22.2 -22.5 0.00 0.00 01-DEC-00:10 -22.2 -22.5
                     
Annual Sum or Average 1548.96         0.00        
Minimum of Months 0.00 0.00   -26.1 -26.4 0.00 0.00   -26.1 -26.4
Maximum of Months 561.69 0.28   25.60 20.52 0.00 0.00   25.60 20.52



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: REARSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 80746.33 1.64 06-JAN-11:45 -21.9 -22.4 0.00 0.00 01-JAN-00:10 -21.9 -22.4
February 81489.47 1.73 24-FEB-11:35 5.93 2.90 0.00 0.00 01-FEB-00:10 5.93 2.90
March 121837.63 1.82 06-MAR-11:35 -2.9 -4.6 0.00 0.00 01-MAR-00:10 -2.9 -4.6
April 157787.84 1.96 09-APR-10:45 5.40 3.03 0.00 0.00 01-APR-00:10 5.40 3.03
May 135764.18 1.61 30-MAY-10:45 23.62 19.32 0.00 0.00 01-MAY-00:10 23.62 19.32
June 127107.30 1.28 08-JUN-10:45 21.42 15.97 0.00 0.00 01-JUN-00:10 21.42 15.97
July 150413.97 1.53 29-JUL-10:35 25.93 19.88 0.00 0.00 01-JUL-00:10 25.93 19.88
August 178383.36 2.06 11-AUG-10:45 27.43 19.26 0.00 0.00 01-AUG-00:10 27.43 19.26
September 223017.48 2.37 15-SEP-10:45 18.62 12.54 0.00 0.00 01-SEP-00:10 18.62 12.54
October 170568.07 2.36 20-OCT-10:45 17.62 11.24 0.00 0.00 01-OCT-00:10 17.62 11.24
November 81750.40 1.80 04-NOV-10:35 10.20 5.24 0.00 0.00 01-NOV-00:10 10.20 5.24
December 86623.34 1.96 07-DEC-11:35 -6.8 -9.6 0.00 0.00 01-DEC-00:10 -6.8 -9.6
                     
Annual Sum or Average 1595489.36         0.00        
Minimum of Months 80746.33 1.28   -21.9 -22.4 0.00 0.00   -21.9 -22.4
Maximum of Months 223017.48 2.37   27.43 19.88 0.00 0.00   27.43 19.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDORFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.00 0.00 01-JAN-00:10 -2.8 -3.2
February 9294240.40 625.79 25-FEB-12:45 4.22 2.33 0.00 0.00 01-FEB-00:10 4.22 2.33
March 0.140364E+09 877.75 10-MAR-16:02 -0.7 -3.1 0.00 0.00 01-MAR-00:10 -0.7 -3.1
April 0.607465E+09 1770.48 18-APR-15:02 27.75 20.46 0.00 0.00 01-APR-00:10 27.75 20.46
May 0.127498E+10 2113.09 31-MAY-14:50 29.90 19.65 0.00 0.00 01-MAY-00:10 29.90 19.65
June 0.198858E+10 2150.64 09-JUN-14:10 25.68 19.98 0.00 0.00 01-JUN-00:10 25.68 19.98
July 0.231136E+10 2170.71 05-JUL-14:00 27.20 19.77 0.00 0.00 01-JUL-00:10 27.20 19.77
August 0.201521E+10 2011.86 01-AUG-15:23 28.60 21.48 0.00 0.00 01-AUG-00:10 28.60 21.48
September 0.127900E+10 2203.04 07-SEP-13:30 31.95 18.23 0.00 0.00 01-SEP-00:10 31.95 18.23
October 0.362767E+09 740.22 16-OCT-19:05 1.50 -0.4 0.00 0.00 01-OCT-00:10 1.50 -0.4
November 0.107122E+09 681.06 09-NOV-14:45 2.88 0.85 0.00 0.00 01-NOV-00:10 2.88 0.85
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 0.00 0.00 01-DEC-00:10 -0.7 -1.3
                     
Annual Sum or Average 0.100961E+11         0.00        
Minimum of Months 0.00 0.00   -2.8 -3.2 0.00 0.00   -2.8 -3.2
Maximum of Months 0.231136E+10 2203.04   31.95 21.48 0.00 0.00   31.95 21.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: REARSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.00 0.00 01-JAN-00:10 -2.8 -3.2
February 0.00 0.00 01-FEB-00:10 -24.1 -24.4 0.00 0.00 01-FEB-00:10 -24.1 -24.4
March 0.00 0.00 01-MAR-00:10 -11.0 -12.0 0.00 0.00 01-MAR-00:10 -11.0 -12.0
April 0.00 0.00 01-APR-00:10 -1.2 -2.2 0.00 0.00 01-APR-00:10 -1.2 -2.2
May 0.00 0.00 01-MAY-00:10 8.22 5.15 0.00 0.00 01-MAY-00:10 8.22 5.15
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.00 0.00 01-JUN-00:10 14.70 10.69
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 0.00 0.00 01-AUG-00:10 18.15 17.82 0.00 0.00 01-AUG-00:10 18.15 17.82
September 0.00 0.00 01-SEP-00:10 16.07 15.67 0.00 0.00 01-SEP-00:10 16.07 15.67
October 0.00 0.00 01-OCT-00:10 3.92 1.39 0.00 0.00 01-OCT-00:10 3.92 1.39
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.00 0.00 01-NOV-00:10 1.65 -0.5
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 0.00 0.00 01-DEC-00:10 -0.7 -1.3
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -24.1 -24.4 0.00 0.00   -24.1 -24.4
Maximum of Months 0.00 0.00   18.93 17.82 0.00 0.00   18.93 17.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM401

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 217746.47 639.29 13-JAN-19:04 0.40 -0.6 0.116466E+09 71.24 31-JAN-00:40 -29.6 -29.8
February 1651993.14 815.13 25-FEB-16:02 5.50 2.74 0.105376E+09 71.24 03-FEB-00:40 5.50 2.74
March 34737312.64 2780.60 23-MAR-18:01 13.53 8.78 0.118586E+09 71.24 06-MAR-00:49 13.53 8.78
April 0.293093E+09 3223.38 17-APR-17:42 18.48 11.79 0.119238E+09 102.26 18-APR-21:49 14.78 12.42
May 0.661793E+09 3354.99 21-MAY-18:01 16.93 9.12 0.131310E+09 112.76 31-MAY-21:30 21.00 15.98
June 0.122743E+10 3154.28 16-JUN-16:21 24.15 16.77 0.129200E+09 118.35 23-JUN-21:19 19.63 14.25
July 0.142107E+10 3239.60 22-JUL-16:31 19.97 14.36 0.136984E+09 114.82 06-JUL-21:40 19.97 14.36
August 0.123369E+10 3326.08 29-AUG-16:11 23.13 15.02 0.137260E+09 114.43 09-AUG-21:19 23.13 15.02
September 0.715124E+09 3234.50 12-SEP-16:21 23.90 15.37 0.125425E+09 114.49 07-SEP-21:10 23.90 15.37
October 0.101816E+09 2679.40 30-OCT-16:11 12.97 7.94 0.121094E+09 88.01 20-OCT-20:10 12.97 7.94
November 31010163.25 2663.71 04-NOV-18:01 5.50 2.14 0.113969E+09 71.58 09-NOV-05:10 15.00 13.04
December 258058.90 675.67 02-DEC-19:04 1.10 0.57 0.116475E+09 71.24 09-DEC-00:40 -22.8 -23.0
                     
Annual Sum or Average 0.572189E+10         0.147138E+10        
Minimum of Months 217746.47 639.29   0.40 -0.6 0.105376E+09 71.24   -29.6 -29.8
Maximum of Months 0.142107E+10 3354.99   24.15 16.77 0.137260E+09 118.35   23.90 15.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM402_405

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 21071731.39 1278.31 03-JAN-15:43 -11.7 -12.5 0.00 0.00 01-JAN-00:10 -11.7 -12.5
February 43354340.43 1154.82 17-FEB-15:13 -6.7 -8.6 0.00 0.00 01-FEB-00:10 -6.7 -8.6
March 58070274.76 1339.41 05-MAR-15:25 -9.4 -10.5 0.00 0.00 01-MAR-00:10 -9.4 -10.5
April 89046171.38 1001.36 03-APR-15:00 -3.3 -5.4 0.00 0.00 01-APR-00:10 -3.3 -5.4
May 0.104441E+09 1155.84 31-MAY-16:45 28.80 19.66 0.00 0.00 01-MAY-00:10 28.80 19.66
June 0.394172E+09 1510.30 25-JUN-16:54 31.70 21.68 0.00 0.00 01-JUN-00:10 31.70 21.68
July 0.485574E+09 1617.07 05-JUL-16:54 26.70 20.53 0.00 0.00 01-JUL-00:10 26.70 20.53
August 0.307680E+09 1407.92 04-AUG-15:23 33.90 25.83 0.00 0.00 01-AUG-00:10 33.90 25.83
September 0.158025E+09 1318.65 07-SEP-16:00 31.70 18.53 0.00 0.00 01-SEP-00:10 31.70 18.53
October 29586835.78 546.63 22-OCT-14:30 6.20 3.50 0.00 0.00 01-OCT-00:10 6.20 3.50
November 38033310.54 1135.70 21-NOV-15:13 -6.7 -8.4 0.00 0.00 01-NOV-00:10 -6.7 -8.4
December 34898664.74 1169.14 25-DEC-15:13 -8.0 -9.0 0.00 0.00 01-DEC-00:10 -8.0 -9.0
                     
Annual Sum or Average 0.176395E+10         0.00        
Minimum of Months 21071731.39 546.63   -11.7 -12.5 0.00 0.00   -11.7 -12.5
Maximum of Months 0.485574E+09 1617.07   33.90 25.83 0.00 0.00   33.90 25.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM406_408

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 27725240.72 1046.45 24-JAN-15:03 -12.9 -13.8 0.00 0.00 01-JAN-00:10 -12.9 -13.8
February 40380219.28 1164.45 05-FEB-15:03 -15.6 -16.5 0.00 0.00 01-FEB-00:10 -15.6 -16.5
March 48391378.45 1072.67 05-MAR-15:25 -9.4 -10.5 0.00 0.00 01-MAR-00:10 -9.4 -10.5
April 81828059.45 949.05 15-APR-16:33 30.00 18.83 0.00 0.00 01-APR-00:10 30.00 18.83
May 0.108900E+09 1069.69 31-MAY-16:45 28.80 19.66 0.00 0.00 01-MAY-00:10 28.80 19.66
June 0.362676E+09 1384.15 25-JUN-16:54 31.70 21.68 0.00 0.00 01-JUN-00:10 31.70 21.68
July 0.446982E+09 1467.76 05-JUL-16:54 26.70 20.53 0.00 0.00 01-JUL-00:10 26.70 20.53
August 0.292799E+09 1295.63 02-AUG-16:22 28.90 22.60 0.00 0.00 01-AUG-00:10 28.90 22.60
September 0.152118E+09 1212.50 07-SEP-16:00 31.70 18.53 0.00 0.00 01-SEP-00:10 31.70 18.53
October 23271467.10 419.74 23-OCT-15:00 8.30 3.68 0.00 0.00 01-OCT-00:10 8.30 3.68
November 33538908.85 1240.56 25-NOV-15:03 -17.3 -17.9 0.00 0.00 01-NOV-00:10 -17.3 -17.9
December 37009860.30 923.66 20-DEC-15:25 -7.8 -9.0 0.00 0.00 01-DEC-00:10 -7.8 -9.0
                     
Annual Sum or Average 0.165562E+10         0.00        
Minimum of Months 23271467.10 419.74   -17.3 -17.9 0.00 0.00   -17.3 -17.9
Maximum of Months 0.446982E+09 1467.76   31.70 22.60 0.00 0.00   31.70 22.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM409_412

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 33348749.74 8063.77 12-JAN-16:01 2.62 1.03 0.470104E+09 284.94 31-JAN-00:49 -29.8 -30.0
February 0.171908E+09 10006.96 21-FEB-16:01 -0.6 -2.5 0.428980E+09 284.94 02-FEB-00:49 -0.6 -2.5
March 0.647927E+09 10947.33 21-MAR-18:01 -2.7 -5.5 0.485753E+09 329.11 23-MAR-18:10 13.53 8.78
April 0.177110E+10 11720.26 17-APR-17:42 18.48 11.79 0.486403E+09 453.70 10-APR-21:10 18.48 11.79
May 0.296768E+10 12708.72 20-MAY-17:21 15.85 8.56 0.529179E+09 452.62 12-MAY-21:10 15.85 8.56
June 0.404727E+10 12345.40 08-JUN-16:21 23.30 16.39 0.517666E+09 466.63 23-JUN-21:19 19.63 14.25
July 0.450712E+10 12531.88 23-JUL-16:21 22.80 15.36 0.548275E+09 460.83 20-JUL-21:10 22.80 15.36
August 0.409985E+10 12587.76 16-AUG-16:21 23.90 15.40 0.549832E+09 456.33 21-AUG-21:10 23.72 21.58
September 0.292712E+10 11722.58 12-SEP-16:21 23.90 15.37 0.505864E+09 461.51 05-SEP-21:10 23.90 15.37
October 0.127529E+10 10973.98 19-OCT-17:11 13.67 8.35 0.495420E+09 380.40 20-OCT-20:19 14.63 9.75
November 0.501703E+09 10455.27 04-NOV-18:01 5.50 2.14 0.464483E+09 284.93 26-NOV-00:49 -24.4 -24.7
December 47297494.64 8609.64 02-DEC-16:01 4.95 2.78 0.471752E+09 284.93 09-DEC-00:40 -22.8 -23.0
                     
Annual Sum or Average 0.229976E+11         0.595371E+10        
Minimum of Months 33348749.74 8063.77   -2.7 -5.5 0.428980E+09 284.93   -29.8 -30.0
Maximum of Months 0.450712E+10 12708.72   23.90 16.39 0.549832E+09 466.63   23.90 21.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM413

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 4101083.26 289.29 02-JAN-15:25 -8.9 -10.1 0.00 0.00 01-JAN-00:10 -8.9 -10.1
February 8262772.38 253.13 17-FEB-15:13 -6.7 -8.6 0.00 0.00 01-FEB-00:10 -6.7 -8.6
March 11496788.83 305.21 05-MAR-15:25 -9.4 -10.5 0.00 0.00 01-MAR-00:10 -9.4 -10.5
April 15388512.84 224.03 03-APR-15:00 -3.3 -5.4 0.00 0.00 01-APR-00:10 -3.3 -5.4
May 13791981.49 255.08 31-MAY-16:45 28.80 19.66 0.00 0.00 01-MAY-00:10 28.80 19.66
June 70400671.33 364.94 30-JUN-17:45 28.30 20.58 0.00 0.00 01-JUN-00:10 28.30 20.58
July 90160454.64 384.84 05-JUL-17:27 26.70 20.86 0.00 0.00 01-JUL-00:10 26.70 20.86
August 54363465.59 354.16 04-AUG-15:23 33.90 25.83 0.00 0.00 01-AUG-00:10 33.90 25.83
September 32845486.08 379.03 07-SEP-16:02 31.52 18.72 0.00 0.00 01-SEP-00:10 31.52 18.72
October 5191502.27 112.28 23-OCT-15:00 8.30 3.68 0.00 0.00 01-OCT-00:10 8.30 3.68
November 7169119.31 250.01 21-NOV-15:13 -6.7 -8.4 0.00 0.00 01-NOV-00:10 -6.7 -8.4
December 8129890.89 262.30 25-DEC-15:13 -8.0 -9.0 0.00 0.00 01-DEC-00:10 -8.0 -9.0
                     
Annual Sum or Average 0.321302E+09         0.00        
Minimum of Months 4101083.26 112.28   -9.4 -10.5 0.00 0.00   -9.4 -10.5
Maximum of Months 90160454.64 384.84   33.90 25.83 0.00 0.00   33.90 25.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM414

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 10900644.19 354.87 27-JAN-15:30 -16.9 -17.5 0.00 0.00 01-JAN-00:10 -16.9 -17.5
February 14196508.91 357.66 05-FEB-15:03 -15.6 -16.5 0.00 0.00 01-FEB-00:10 -15.6 -16.5
March 15658152.92 330.10 05-MAR-15:25 -9.4 -10.5 0.00 0.00 01-MAR-00:10 -9.4 -10.5
April 11931583.19 228.31 03-APR-15:00 -3.3 -5.4 0.00 0.00 01-APR-00:10 -3.3 -5.4
May 10766365.24 193.40 31-MAY-11:10 28.48 19.45 0.00 0.00 01-MAY-00:10 28.48 19.45
June 54739920.91 224.03 26-JUN-14:00 31.70 22.11 0.00 0.00 01-JUN-00:10 31.70 22.11
July 58412548.09 217.33 05-JUL-11:30 25.55 20.57 0.00 0.00 01-JUL-00:10 25.55 20.57
August 32810243.56 216.41 04-AUG-15:01 33.90 25.49 0.00 0.00 01-AUG-00:10 33.90 25.49
September 19219161.68 230.63 07-SEP-13:50 32.12 18.34 0.00 0.00 01-SEP-00:10 32.12 18.34
October 6587404.83 132.68 22-OCT-15:00 6.10 3.25 0.00 0.00 01-OCT-00:10 6.10 3.25
November 11978510.84 345.53 24-NOV-15:25 -12.2 -13.0 0.00 0.00 01-NOV-00:10 -12.2 -13.0
December 14757950.44 287.55 25-DEC-15:13 -8.0 -9.0 0.00 0.00 01-DEC-00:10 -8.0 -9.0
                     
Annual Sum or Average 0.261959E+09         0.00        
Minimum of Months 6587404.83 132.68   -16.9 -17.5 0.00 0.00   -16.9 -17.5
Maximum of Months 58412548.09 357.66   33.90 25.49 0.00 0.00   33.90 25.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM415_418

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.154686E+09 10496.98 02-JAN-09:01 -8.5 -9.0 0.473984E+09 284.93 31-JAN-00:49 -29.8 -30.0
February 0.397974E+09 11008.31 19-FEB-09:01 -4.6 -5.5 0.433445E+09 284.93 02-FEB-00:49 -4.6 -5.5
March 0.113068E+10 11404.11 05-MAR-09:01 -8.9 -9.7 0.490774E+09 325.70 23-MAR-18:10 13.53 8.78
April 0.221299E+10 11573.58 30-APR-17:11 15.60 8.87 0.485742E+09 432.47 18-APR-21:10 15.60 8.87
May 0.363810E+10 11712.54 21-MAY-16:51 17.80 9.67 0.522648E+09 435.09 05-MAY-21:10 17.80 9.67
June 0.451115E+10 11825.05 22-JUN-16:21 20.85 13.49 0.513956E+09 440.22 16-JUN-21:10 20.85 13.49
July 0.489730E+10 11087.07 15-JUL-16:21 23.60 17.57 0.542007E+09 454.98 17-JUL-21:10 20.92 19.44
August 0.450233E+10 11114.57 06-AUG-16:51 19.40 12.05 0.542968E+09 451.09 01-AUG-21:19 19.40 12.05
September 0.345982E+10 11949.52 15-SEP-16:21 22.50 12.80 0.503040E+09 427.42 07-SEP-21:19 22.50 12.80
October 0.184021E+10 11072.53 20-OCT-16:51 19.20 11.72 0.496917E+09 380.40 20-OCT-20:19 14.63 9.75
November 0.857319E+09 11223.33 12-NOV-09:01 -5.3 -6.6 0.468604E+09 284.93 26-NOV-00:49 -24.4 -24.7
December 0.215769E+09 11190.63 25-DEC-09:01 -12.5 -12.9 0.476016E+09 284.93 09-DEC-00:40 -12.5 -12.9
                     
Annual Sum or Average 0.278183E+11         0.595010E+10        
Minimum of Months 0.154686E+09 10496.98   -12.5 -12.9 0.433445E+09 284.93   -29.8 -30.0
Maximum of Months 0.489730E+10 11949.52   23.60 17.57 0.542968E+09 454.98   22.50 19.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ELEVATORCOREFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.00 0.00 01-JAN-00:10 -2.8 -3.2
February 0.00 0.00 01-FEB-00:10 -24.1 -24.4 0.00 0.00 01-FEB-00:10 -24.1 -24.4
March 0.00 0.00 01-MAR-00:10 -11.0 -12.0 0.00 0.00 01-MAR-00:10 -11.0 -12.0
April 0.00 0.00 01-APR-00:10 -1.2 -2.2 0.00 0.00 01-APR-00:10 -1.2 -2.2
May 0.00 0.00 01-MAY-00:10 8.22 5.15 0.00 0.00 01-MAY-00:10 8.22 5.15
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.00 0.00 01-JUN-00:10 14.70 10.69
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 0.00 0.00 01-AUG-00:10 18.15 17.82 0.00 0.00 01-AUG-00:10 18.15 17.82
September 0.00 0.00 01-SEP-00:10 16.07 15.67 0.00 0.00 01-SEP-00:10 16.07 15.67
October 0.00 0.00 01-OCT-00:10 3.92 1.39 0.00 0.00 01-OCT-00:10 3.92 1.39
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.00 0.00 01-NOV-00:10 1.65 -0.5
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 0.00 0.00 01-DEC-00:10 -0.7 -1.3
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -24.1 -24.4 0.00 0.00   -24.1 -24.4
Maximum of Months 0.00 0.00   18.93 17.82 0.00 0.00   18.93 17.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM419

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 28951488.49 2309.55 13-JAN-16:01 3.62 1.75 0.118234E+09 71.23 31-JAN-00:49 -29.8 -30.0
February 84184081.03 2865.46 19-FEB-09:01 -4.6 -5.5 0.108080E+09 71.23 02-FEB-00:49 -4.6 -5.5
March 0.282215E+09 2962.77 05-MAR-09:01 -8.9 -9.7 0.122298E+09 77.20 23-MAR-18:10 13.53 8.78
April 0.624359E+09 3085.18 17-APR-16:51 19.40 11.31 0.121226E+09 108.10 18-APR-21:10 16.32 13.39
May 0.109473E+10 3146.82 21-MAY-16:51 17.80 9.67 0.130665E+09 108.34 05-MAY-21:10 17.80 9.67
June 0.138411E+10 3177.97 22-JUN-16:21 20.85 13.49 0.128576E+09 111.01 16-JUN-21:10 20.85 13.49
July 0.151517E+10 2989.67 15-JUL-16:21 23.60 17.57 0.135648E+09 113.84 17-JUL-21:10 20.92 19.44
August 0.139261E+10 3032.22 06-AUG-16:51 19.40 12.05 0.135879E+09 112.30 01-AUG-21:19 19.40 12.05
September 0.105393E+10 3126.14 20-SEP-16:51 20.60 11.60 0.125818E+09 106.86 06-SEP-21:10 20.60 11.60
October 0.508202E+09 3005.43 20-OCT-16:51 19.20 11.72 0.124066E+09 93.40 20-OCT-20:19 14.63 9.75
November 0.218423E+09 2932.35 12-NOV-09:01 -5.3 -6.6 0.116912E+09 71.23 26-NOV-00:49 -24.4 -24.7
December 38859219.56 2755.52 02-DEC-09:01 -0.2 -1.8 0.118730E+09 71.23 09-DEC-00:40 -22.8 -23.0
                     
Annual Sum or Average 0.822574E+10         0.148613E+10        
Minimum of Months 28951488.49 2309.55   -8.9 -9.7 0.108080E+09 71.23   -29.8 -30.0
Maximum of Months 0.151517E+10 3177.97   23.60 17.57 0.135879E+09 113.84   20.92 19.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM420_423

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.140516E+09 9877.42 02-JAN-09:01 -8.5 -9.0 0.473902E+09 284.93 31-JAN-00:49 -29.8 -30.0
February 0.340581E+09 10304.75 19-FEB-09:01 -4.6 -5.5 0.432670E+09 284.93 02-FEB-00:49 -4.6 -5.5
March 0.958081E+09 10700.37 05-MAR-09:01 -8.9 -9.7 0.489291E+09 311.85 23-MAR-18:10 13.53 8.78
April 0.190833E+10 10625.66 30-APR-17:11 15.60 8.87 0.484418E+09 426.01 18-APR-21:30 15.60 8.87
May 0.318090E+10 10865.40 21-MAY-16:51 17.80 9.67 0.520891E+09 427.42 12-MAY-21:19 17.80 9.67
June 0.396302E+10 10745.03 22-JUN-16:21 20.85 13.49 0.512127E+09 431.90 16-JUN-21:10 20.85 13.49
July 0.430982E+10 10002.63 23-JUL-16:21 22.80 15.36 0.539751E+09 446.38 17-JUL-21:10 22.80 15.36
August 0.396193E+10 10289.71 06-AUG-16:51 19.40 12.05 0.540623E+09 440.86 28-AUG-21:10 21.70 20.86
September 0.302249E+10 10604.55 20-SEP-16:51 20.60 11.60 0.501451E+09 427.42 07-SEP-21:19 20.60 11.60
October 0.156706E+10 10148.29 20-OCT-16:51 19.20 11.72 0.495797E+09 367.55 20-OCT-20:19 14.63 9.75
November 0.735821E+09 10531.55 12-NOV-09:01 -5.3 -6.6 0.467757E+09 284.93 26-NOV-00:49 -24.4 -24.7
December 0.197195E+09 10564.34 25-DEC-09:01 -12.5 -12.9 0.475553E+09 284.93 09-DEC-00:40 -12.5 -12.9
                     
Annual Sum or Average 0.242857E+11         0.593423E+10        
Minimum of Months 0.140516E+09 9877.42   -12.5 -12.9 0.432670E+09 284.93   -29.8 -30.0
Maximum of Months 0.430982E+10 10865.40   22.80 15.36 0.540623E+09 446.38   22.80 20.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GUESTROOM424

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 1974437.79 659.37 09-JAN-19:04 -4.7 -5.3 0.116886E+09 71.24 31-JAN-00:40 -29.6 -29.8
February 10657616.89 1984.54 25-FEB-09:01 0.78 -0.3 0.106408E+09 71.24 02-FEB-00:40 0.78 -0.3
March 94363966.14 2591.28 28-MAR-16:51 14.40 9.63 0.120276E+09 71.23 06-MAR-00:49 14.40 9.63
April 0.370659E+09 2997.82 17-APR-16:51 19.40 11.31 0.119847E+09 105.99 18-APR-21:30 15.55 12.91
May 0.818241E+09 3073.96 21-MAY-16:51 17.80 9.67 0.129790E+09 106.85 31-MAY-21:30 21.00 15.98
June 0.120711E+10 2898.10 22-JUN-16:41 20.68 13.36 0.128007E+09 108.60 16-JUN-21:10 20.68 13.36
July 0.135526E+10 2862.72 23-JUL-16:21 22.80 15.36 0.135031E+09 112.32 27-JUL-21:10 20.92 17.78
August 0.120922E+10 2939.74 06-AUG-16:51 19.40 12.05 0.135194E+09 110.86 01-AUG-21:19 19.40 12.05
September 0.827745E+09 3025.17 20-SEP-16:51 20.60 11.60 0.125096E+09 106.86 07-SEP-21:19 20.60 11.60
October 0.245526E+09 2755.60 20-OCT-16:51 19.20 11.72 0.122693E+09 86.63 20-OCT-20:19 14.63 9.75
November 85763322.53 2522.86 04-NOV-08:61 2.77 0.71 0.115301E+09 71.23 26-NOV-00:49 -24.4 -24.7
December 2696584.30 733.08 01-DEC-16:04 -2.1 -4.3 0.117122E+09 71.23 09-DEC-00:40 -22.8 -23.0
                     
Annual Sum or Average 0.622922E+10         0.147165E+10        
Minimum of Months 1974437.79 659.37   -4.7 -5.3 0.106408E+09 71.23   -29.6 -29.8
Maximum of Months 0.135526E+10 3073.96   22.80 15.36 0.135194E+09 112.32   21.00 17.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONTSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8 -3.2 0.00 0.00 01-JAN-00:10 -2.8 -3.2
February 0.00 0.00 01-FEB-00:10 -24.1 -24.4 0.00 0.00 01-FEB-00:10 -24.1 -24.4
March 0.00 0.00 01-MAR-00:10 -11.0 -12.0 0.00 0.00 01-MAR-00:10 -11.0 -12.0
April 0.00 0.00 01-APR-00:10 -1.2 -2.2 0.00 0.00 01-APR-00:10 -1.2 -2.2
May 0.00 0.00 01-MAY-00:10 8.22 5.15 0.00 0.00 01-MAY-00:10 8.22 5.15
June 0.00 0.00 01-JUN-00:10 14.70 10.69 0.00 0.00 01-JUN-00:10 14.70 10.69
July 0.00 0.00 01-JUL-00:10 18.93 15.94 0.00 0.00 01-JUL-00:10 18.93 15.94
August 0.00 0.00 01-AUG-00:10 18.15 17.82 0.00 0.00 01-AUG-00:10 18.15 17.82
September 0.00 0.00 01-SEP-00:10 16.07 15.67 0.00 0.00 01-SEP-00:10 16.07 15.67
October 0.00 0.00 01-OCT-00:10 3.92 1.39 0.00 0.00 01-OCT-00:10 3.92 1.39
November 0.00 0.00 01-NOV-00:10 1.65 -0.5 0.00 0.00 01-NOV-00:10 1.65 -0.5
December 0.00 0.00 01-DEC-00:10 -0.7 -1.3 0.00 0.00 01-DEC-00:10 -0.7 -1.3
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -24.1 -24.4 0.00 0.00   -24.1 -24.4
Maximum of Months 0.00 0.00   18.93 17.82 0.00 0.00   18.93 17.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FRONTSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 3238.59 0.72 08-JAN-11:35 -8.5 -9.3 0.00 0.00 01-JAN-00:10 -8.5 -9.3
February 10624.73 0.93 19-FEB-11:35 0.53 -1.3 0.00 0.00 01-FEB-00:10 0.53 -1.3
March 58660.49 1.74 28-MAR-10:45 12.33 7.42 0.00 0.00 01-MAR-00:10 12.33 7.42
April 88029.07 2.32 15-APR-10:45 25.13 19.38 0.00 0.00 01-APR-00:10 25.13 19.38
May 81747.16 1.77 30-MAY-10:45 23.62 19.32 0.00 0.00 01-MAY-00:10 23.62 19.32
June 71160.57 1.74 11-JUN-08:53 26.70 21.18 0.00 0.00 01-JUN-00:10 26.70 21.18
July 84836.04 1.77 17-JUL-09:55 26.70 22.30 0.00 0.00 01-JUL-00:10 26.70 22.30
August 113496.20 2.35 11-AUG-10:45 27.43 19.26 0.00 0.00 01-AUG-00:10 27.43 19.26
September 134422.48 2.64 05-SEP-10:45 24.22 15.07 0.00 0.00 01-SEP-00:10 24.22 15.07
October 64706.75 2.06 20-OCT-10:45 17.62 11.24 0.00 0.00 01-OCT-00:10 17.62 11.24
November 15885.16 1.12 14-NOV-11:35 7.77 4.86 0.00 0.00 01-NOV-00:10 7.77 4.86
December 4294.11 1.11 02-DEC-11:35 4.63 2.51 0.00 0.00 01-DEC-00:10 4.63 2.51
                     
Annual Sum or Average 731101.34         0.00        
Minimum of Months 3238.59 0.72   -8.5 -9.3 0.00 0.00   -8.5 -9.3
Maximum of Months 134422.48 2.64   27.43 22.30 0.00 0.00   27.43 22.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: REARSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1549467.84 1.82 29-JAN-02:00 -10.6
February 1383912.98 1.61 01-FEB-20:30 -28.6
March 1523120.77 1.25 08-MAR-22:45 -2.7
April 1480067.93 1.24 25-APR-05:55 1.10
May 1529263.17 1.39 13-MAY-13:00 12.20
June 1492946.68 1.34 09-JUN-16:11 18.67
July 1539904.18 1.24 11-JUL-14:10 17.70
August 1528872.08 1.22 06-AUG-21:00 11.10
September 1490914.70 1.27 15-SEP-21:00 11.70
October 1532856.19 1.18 11-OCT-19:30 13.35
November 1489651.55 1.36 20-NOV-16:55 -0.6
December 1526496.87 1.46 08-DEC-14:35 -14.3
         
Annual Sum or Average 18067474.92      
Minimum of Months 1383912.98 1.18   -28.6
Maximum of Months 1549467.84 1.82   18.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDORFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.107208E+11 64139.58 31-JAN-07:01 -30.5
February 0.752819E+10 74891.74 02-FEB-07:02 -36.7
March 0.406727E+10 37092.37 06-MAR-07:02 -12.7
April 0.216815E+10 29684.81 01-APR-06:02 -5.8
May 0.531879E+09 19979.61 03-MAY-06:04 3.17
June 0.201452E+09 12070.78 03-JUN-06:05 6.78
July 70876790.05 2184.56 23-JUL-06:02 12.15
August 0.109401E+09 7508.94 07-AUG-06:06 8.87
September 0.539892E+09 20748.85 29-SEP-06:04 0.10
October 0.162826E+10 29277.79 23-OCT-06:02 -3.0
November 0.422300E+10 59477.37 26-NOV-07:01 -28.3
December 0.745468E+10 51723.32 09-DEC-07:02 -22.8
         
Annual Sum or Average 0.392438E+11      
Minimum of Months 70876790.05 2184.56   -36.7
Maximum of Months 0.107208E+11 74891.74   12.15



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: REARSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONTLOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.230170E+09 5504.57 05-JAN-21:14 -23.5
February 0.186853E+09 6495.50 03-FEB-18:09 -27.8
March 11102257.03 2110.68 04-MAR-02:00 -9.4
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 17961834.21 2925.77 25-NOV-04:57 -15.0
December 71297849.55 4884.23 11-DEC-20:05 -20.6
         
Annual Sum or Average 0.517385E+09      
Minimum of Months 0.00 0.00   -27.8
Maximum of Months 0.230170E+09 6495.50   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RESTROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.248635E+09 97.14 29-JAN-10:33 -22.4
February 0.223739E+09 149.17 03-FEB-05:00 -33.9
March 0.178856E+09 96.26 01-MAR-10:33 -4.8
April 80335515.28 98.34 09-APR-15:02 11.20
May 1118301.30 90.47 02-MAY-09:01 5.18
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 311402.33 89.37 30-SEP-04:05 -0.5
October 1417378.41 96.77 29-OCT-04:03 5.13
November 0.125185E+09 99.36 15-NOV-09:02 0.68
December 0.247372E+09 97.06 09-DEC-10:33 -21.9
         
Annual Sum or Average 0.110697E+10      
Minimum of Months 0.00 0.00   -33.9
Maximum of Months 0.248635E+09 149.17   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MEETINGROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.308037E+09 9447.41 30-JAN-17:57 -26.7
February 0.189395E+09 7704.70 05-FEB-17:47 -18.6
March 37265063.93 5689.95 05-MAR-12:49 -9.7
April 979833.93 75.17 03-APR-01:40 -6.1
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 30235057.88 291.59 26-NOV-05:00 -25.0
December 0.111709E+09 7859.71 11-DEC-14:27 -19.4
         
Annual Sum or Average 0.677621E+09      
Minimum of Months 0.00 0.00   -26.7
Maximum of Months 0.308037E+09 9447.41   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECHANICALROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM101

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 37805.98 9.75 19-MAR-14:10 18.30
April 1490374.21 146.20 15-APR-15:00 30.00
May 2016787.77 131.55 31-MAY-14:15 29.60
June 5652761.15 155.69 25-JUN-14:05 32.20
July 5790727.63 118.80 03-JUL-14:15 29.60
August 5690784.13 166.79 04-AUG-14:05 33.40
September 3366345.12 150.92 06-SEP-14:05 32.20
October 225293.01 51.37 20-OCT-14:15 22.83
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 24270878.99      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 5790727.63 166.79   33.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM102

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 19321.76 6.03 19-MAR-14:10 18.30
April 1443358.29 142.26 15-APR-15:00 30.00
May 1877804.05 128.26 31-MAY-14:15 29.60
June 5664867.77 169.28 11-JUN-15:00 33.30
July 5819275.66 120.21 26-JUL-15:00 30.00
August 5899112.94 174.42 04-AUG-15:00 33.90
September 3918788.43 150.23 06-SEP-14:05 32.20
October 195498.96 46.71 20-OCT-14:15 22.83
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 24838027.86      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 5899112.94 174.42   33.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM103

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.680841E+09 1614.64 12-JAN-16:01 2.62
February 0.463007E+09 1634.64 07-FEB-16:01 3.22
March 0.248368E+09 1642.18 11-MAR-16:01 4.32
April 50024491.27 1595.41 02-APR-15:01 0.60
May 9024358.25 1154.72 19-MAY-08:03 10.28
June 12909727.23 912.20 03-JUN-08:04 8.68
July 15166870.42 338.97 04-JUL-21:01 21.70
August 12098683.34 953.82 07-AUG-08:04 15.47
September 7442849.26 1183.61 30-SEP-08:03 3.35
October 4854750.97 1343.86 28-OCT-08:03 1.55
November 0.111341E+09 1573.99 30-NOV-16:01 -0.6
December 0.392193E+09 1597.78 14-DEC-16:01 0.92
         
Annual Sum or Average 0.200727E+10      
Minimum of Months 4854750.97 338.97   -0.6
Maximum of Months 0.680841E+09 1642.18   21.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM104

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.235628E+09 1549.07 10-JAN-16:01 -3.4
February 0.158594E+09 1547.84 06-FEB-16:01 -4.4
March 43215047.80 1558.74 04-MAR-16:01 -2.9
April 9395196.90 1309.83 25-APR-15:03 6.70
May 7803299.73 1187.25 02-MAY-08:03 4.08
June 10949521.45 930.39 15-JUN-08:04 14.60
July 12302838.55 313.71 15-JUL-16:51 23.90
August 10743112.45 639.55 25-AUG-08:04 14.68
September 6868260.97 1053.18 30-SEP-18:04 5.92
October 5053527.45 1149.31 15-OCT-18:04 5.47
November 22416661.75 1461.56 27-NOV-16:01 -9.5
December 89922411.76 1552.66 13-DEC-16:01 -3.9
         
Annual Sum or Average 0.612891E+09      
Minimum of Months 5053527.45 313.71   -9.5
Maximum of Months 0.235628E+09 1558.74   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM105

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3827495.98 1287.06 13-JAN-16:03 3.62
February 3762835.01 1315.51 24-FEB-16:03 8.12
March 5469870.31 1356.60 24-MAR-08:03 8.48
April 6899074.40 1354.60 06-APR-15:03 8.30
May 7300551.39 1298.01 02-MAY-08:03 4.08
June 11114057.39 926.77 08-JUN-16:25 23.30
July 13649128.81 882.55 18-JUL-18:35 22.97
August 13053630.64 782.63 17-AUG-18:45 20.05
September 8350290.78 1225.44 29-SEP-08:03 5.05
October 4203188.01 1315.67 19-OCT-08:03 5.78
November 3868569.75 1315.76 16-NOV-16:03 6.32
December 4482567.28 1305.37 02-DEC-16:03 4.95
         
Annual Sum or Average 85981259.74      
Minimum of Months 3762835.01 782.63   3.62
Maximum of Months 13649128.81 1356.60   23.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: EMPLOYEELOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRYROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ELEVATORCOREFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: EXERCISECENTERFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 24279033.18 4400.42 23-JAN-02:57 -16.7
February 16559939.89 4398.97 28-FEB-05:47 -16.7
March 762960.57 4431.17 06-MAR-03:37 -16.3
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 2126815.74 4030.81 28-NOV-04:47 -21.3
December 7026711.55 4186.31 09-DEC-23:32 -19.4
         
Annual Sum or Average 50755460.92      
Minimum of Months 0.00 0.00   -21.3
Maximum of Months 24279033.18 4431.17   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONTOFFICEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.123771E+09 4366.74 30-JAN-19:24 -27.2
February 0.131100E+09 4392.58 04-FEB-09:24 -27.8
March 1814519.41 3144.97 05-MAR-23:55 -16.1
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 2839630.29 3954.25 26-NOV-00:45 -24.4
December 37815873.45 3663.80 09-DEC-11:35 -21.3
         
Annual Sum or Average 0.297340E+09      
Minimum of Months 0.00 0.00   -27.8
Maximum of Months 0.131100E+09 4392.58   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONTSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1548808.61 1.80 29-JAN-02:00 -10.6
February 2541924.52 52.94 02-FEB-04:00 -35.0
March 1518444.71 1.17 20-MAR-20:00 0.00
April 1486094.41 1.22 25-APR-05:55 1.10
May 1533831.35 1.37 13-MAY-13:00 12.20
June 1503674.73 1.24 18-JUN-21:00 23.30
July 1553899.06 1.07 11-JUL-14:00 17.80
August 1538856.50 1.12 04-AUG-18:40 19.47
September 1503089.23 1.13 18-SEP-15:55 11.00
October 1535646.82 0.84 07-OCT-20:35 1.40
November 1490436.38 1.19 20-NOV-16:55 -0.6
December 1524397.78 1.39 08-DEC-16:55 -18.9
         
Annual Sum or Average 19279104.12      
Minimum of Months 1486094.41 0.84   -35.0
Maximum of Months 2541924.52 52.94   23.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONTSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: REARSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1552615.10 1.84 29-JAN-02:00 -10.6
February 1385371.04 1.77 01-FEB-20:30 -28.6
March 1524470.84 1.50 08-MAR-22:45 -2.7
April 1485439.91 1.63 25-APR-05:55 1.10
May 1534445.53 1.81 13-MAY-13:00 12.20
June 1496594.88 1.42 18-JUN-21:00 23.30
July 1542178.24 1.31 11-JUL-14:10 17.70
August 1527422.97 1.28 06-AUG-21:00 11.10
September 1495145.14 1.34 15-SEP-21:00 11.70
October 1540849.46 1.20 31-OCT-19:10 -0.5
November 1494742.48 1.50 20-NOV-16:55 -0.6
December 1530040.97 1.59 08-DEC-14:35 -14.3
         
Annual Sum or Average 18109316.57      
Minimum of Months 1385371.04 1.20   -28.6
Maximum of Months 1552615.10 1.84   23.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDORFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 48969998.33 2177.09 07-JAN-01:47 -22.6
February 43248041.34 2088.70 05-FEB-09:25 -18.6
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 45921334.82 2055.73 11-DEC-19:57 -20.6
         
Annual Sum or Average 0.138139E+09      
Minimum of Months 0.00 0.00   -22.6
Maximum of Months 48969998.33 2177.09   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: REARSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM201

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 60946749.91 407.08 26-JAN-15:13 -12.0
February 62782644.78 316.22 02-FEB-09:12 -34.8
March 148350.62 25.01 25-MAR-15:00 18.90
April 1412270.70 135.50 15-APR-15:00 30.00
May 1750481.63 122.43 31-MAY-14:15 29.60
June 2446736.52 145.41 25-JUN-14:05 32.20
July 3360046.65 112.05 26-JUL-14:05 29.50
August 4926121.84 120.79 22-AUG-14:05 30.00
September 3422112.81 153.22 06-SEP-14:05 32.20
October 498723.01 76.08 20-OCT-14:15 22.83
November 3415721.04 103.32 26-NOV-05:00 -25.0
December 27507237.61 160.14 09-DEC-08:55 -22.8
         
Annual Sum or Average 0.172617E+09      
Minimum of Months 148350.62 25.01   -34.8
Maximum of Months 62782644.78 407.08   32.20



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM202_205

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.967118E+09 3928.90 01-JAN-09:02 -3.2
February 0.499345E+09 4165.66 25-FEB-09:03 0.78
March 0.124743E+09 4202.96 27-MAR-08:03 1.20
April 20241446.42 4619.12 06-APR-15:03 8.30
May 12605644.44 3042.28 02-MAY-08:03 4.08
June 20935043.04 3036.17 04-JUN-18:04 13.22
July 24555992.47 1542.42 11-JUL-15:04 17.77
August 23802295.38 1598.96 25-AUG-08:04 14.68
September 16638164.44 4438.97 29-SEP-08:03 5.05
October 14615622.83 4446.22 19-OCT-08:03 5.78
November 0.206943E+09 3940.56 10-NOV-16:03 0.92
December 0.598598E+09 4033.69 30-DEC-09:02 -1.1
         
Annual Sum or Average 0.253014E+10      
Minimum of Months 12605644.44 1542.42   -3.2
Maximum of Months 0.967118E+09 4619.12   17.77



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM206_208

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.477936E+09 3184.37 13-JAN-09:02 -0.5
February 0.257293E+09 3299.16 08-FEB-09:02 1.78
March 37611370.18 3655.08 31-MAR-15:03 8.12
April 12255269.34 3465.65 28-APR-15:03 4.90
May 10225468.31 2482.56 02-MAY-08:03 4.08
June 19046227.84 2243.68 04-JUN-18:04 13.22
July 23265050.82 1547.91 18-JUL-21:56 18.30
August 21582790.44 1337.57 25-AUG-15:04 22.30
September 14454229.45 3520.69 29-SEP-08:03 5.05
October 10488979.08 3537.07 19-OCT-08:03 5.78
November 89754179.72 3539.32 15-NOV-16:03 8.03
December 0.260757E+09 3055.64 04-DEC-19:03 1.20
         
Annual Sum or Average 0.123467E+10      
Minimum of Months 10225468.31 1337.57   -0.5
Maximum of Months 0.477936E+09 3655.08   22.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM209_212

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.234480E+09 3770.22 14-JAN-09:03 -3.8
February 0.152922E+09 4079.35 08-FEB-16:03 2.02
March 17579702.54 4222.02 23-MAR-08:03 4.18
April 15698483.45 4086.96 28-APR-08:03 1.78
May 13615857.08 3415.03 01-MAY-18:04 6.93
June 21995720.06 3178.16 05-JUN-15:04 11.70
July 24259491.56 1159.88 04-JUL-21:01 21.70
August 23505838.71 2119.92 07-AUG-08:04 15.47
September 17668038.88 3543.56 29-SEP-18:04 6.52
October 14964574.57 4184.46 27-OCT-08:03 3.15
November 40544348.89 4244.19 14-NOV-16:03 6.93
December 0.110401E+09 3965.62 02-DEC-09:03 -0.2
         
Annual Sum or Average 0.687635E+09      
Minimum of Months 13615857.08 1159.88   -3.8
Maximum of Months 0.234480E+09 4244.19   21.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM213

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.774271E+09 1480.99 12-JAN-16:01 2.62
February 0.462817E+09 1498.24 07-FEB-16:01 3.22
March 0.208578E+09 1486.31 11-MAR-16:01 4.32
April 35113988.00 1461.00 02-APR-15:01 0.60
May 5716869.57 1145.58 18-MAY-08:03 10.18
June 8672096.86 815.76 03-JUN-18:04 14.22
July 9988888.57 472.52 11-JUL-15:04 17.77
August 9107350.86 364.70 25-AUG-08:04 14.68
September 6101131.76 955.84 30-SEP-15:03 10.92
October 4364034.41 1211.17 23-OCT-15:03 8.02
November 0.216373E+09 1460.08 19-NOV-16:01 1.10
December 0.563207E+09 1467.40 14-DEC-16:01 0.92
         
Annual Sum or Average 0.230431E+10      
Minimum of Months 4364034.41 364.70   0.60
Maximum of Months 0.774271E+09 1498.24   17.77



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM214

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.104714E+09 1347.78 22-JAN-09:02 -8.3
February 69922738.54 1374.60 06-FEB-16:01 -4.4
March 5530269.77 1341.90 21-MAR-15:03 -0.1
April 4156946.93 1399.00 01-APR-08:03 -3.4
May 3598719.01 711.72 02-MAY-08:03 4.08
June 5732089.52 565.70 05-JUN-18:04 12.12
July 6781191.49 270.15 15-JUL-16:51 23.90
August 6634546.97 280.15 22-AUG-20:51 22.20
September 4031806.43 867.43 24-SEP-16:14 14.63
October 2834680.99 1330.00 26-OCT-08:03 1.28
November 13771599.43 1357.92 12-NOV-09:03 -5.3
December 52770815.05 1384.86 13-DEC-16:01 -3.9
         
Annual Sum or Average 0.280479E+09      
Minimum of Months 2834680.99 270.15   -8.3
Maximum of Months 0.104714E+09 1399.00   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM215_218

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ELEVATORCOREFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM219

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 436518.69 615.77 30-JAN-13:03 -24.9
February 146176.30 396.66 06-FEB-09:02 -13.6
March 398742.56 698.69 28-MAR-16:12 15.20
April 1721785.32 1058.55 18-APR-20:42 16.97
May 3279997.65 940.67 27-MAY-08:12 16.67
June 5478766.48 1200.79 17-JUN-19:42 20.97
July 8699504.22 1225.64 12-JUL-19:42 20.87
August 7506127.53 1206.57 27-AUG-20:12 21.50
September 3982863.87 1195.14 16-SEP-20:22 21.40
October 432714.99 656.96 10-OCT-16:12 15.23
November 124775.47 343.17 28-NOV-09:02 -13.0
December 405999.46 502.28 12-DEC-09:02 -18.8
         
Annual Sum or Average 32613972.55      
Minimum of Months 124775.47 343.17   -24.9
Maximum of Months 8699504.22 1225.64   21.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM220_223

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 88184937.53 3870.44 16-JAN-09:03 -1.6
February 80865897.22 4097.20 08-FEB-09:03 1.78
March 16824360.56 4238.30 11-MAR-16:03 4.32
April 16106622.06 3985.64 04-APR-15:03 0.50
May 15044808.00 3302.49 01-MAY-18:04 6.93
June 22423079.10 2779.52 06-JUN-08:04 12.30
July 24024388.06 1817.43 11-JUL-15:04 17.77
August 24402543.51 2517.43 25-AUG-08:04 14.68
September 17943246.20 3254.34 24-SEP-16:14 14.63
October 13720608.96 3906.95 30-OCT-16:14 12.97
November 20793747.74 4121.48 18-NOV-16:03 2.02
December 51466812.36 4262.03 02-DEC-16:03 4.95
         
Annual Sum or Average 0.391801E+09      
Minimum of Months 13720608.96 1817.43   -1.6
Maximum of Months 88184937.53 4262.03   17.77



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM224

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.377788E+09 1274.14 16-JAN-16:01 0.92
February 0.214963E+09 1306.12 07-FEB-16:01 3.22
March 53181910.32 1259.41 25-MAR-08:03 2.57
April 7887785.52 1388.58 25-APR-15:03 6.70
May 4893259.51 715.36 10-MAY-18:04 14.32
June 6964936.37 738.04 05-JUN-18:04 12.12
July 8266519.78 277.67 08-JUL-16:51 22.80
August 8517963.35 399.34 06-AUG-16:55 19.40
September 5372033.83 672.51 21-SEP-18:04 12.80
October 4040642.70 1324.18 28-OCT-08:03 1.55
November 76222819.61 1252.58 30-NOV-16:01 -0.6
December 0.231625E+09 1278.09 14-DEC-16:01 0.92
         
Annual Sum or Average 0.999724E+09      
Minimum of Months 4040642.70 277.67   -0.6
Maximum of Months 0.377788E+09 1388.58   22.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONTSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONTSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1547649.09 1.75 18-JAN-05:00 -5.6
February 8705232.55 131.92 02-FEB-09:43 -33.7
March 1513408.15 1.36 08-MAR-22:45 -2.7
April 1485944.38 1.59 25-APR-05:55 1.10
May 1535448.18 1.75 13-MAY-13:00 12.20
June 1507367.64 1.33 18-JUN-21:00 23.30
July 1557412.20 1.14 23-JUL-24:00 12.20
August 1536039.37 1.20 30-AUG-15:00 17.80
September 1502136.17 1.26 18-SEP-17:45 10.18
October 1534971.57 0.90 07-OCT-20:35 1.40
November 1490566.88 1.30 20-NOV-16:55 -0.6
December 1523051.11 1.55 08-DEC-16:55 -18.9
         
Annual Sum or Average 25439227.28      
Minimum of Months 1485944.38 0.90   -33.7
Maximum of Months 8705232.55 131.92   23.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: REARSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1554854.72 1.96 29-JAN-02:00 -10.6
February 1388046.44 1.80 01-FEB-20:30 -28.6
March 1524266.21 1.42 21-MAR-00:40 -5.2
April 1487689.22 1.74 25-APR-05:55 1.10
May 1533208.42 1.74 13-MAY-13:00 12.20
June 1494533.28 1.44 18-JUN-21:00 23.30
July 1539730.11 1.29 11-JUL-14:10 17.70
August 1528728.55 1.26 16-AUG-22:45 13.58
September 1500035.77 1.32 15-SEP-21:00 11.70
October 1544166.54 1.13 31-OCT-19:10 -0.5
November 1498161.30 1.43 20-NOV-16:55 -0.6
December 1531493.96 1.65 08-DEC-14:35 -14.3
         
Annual Sum or Average 18124914.53      
Minimum of Months 1388046.44 1.13   -28.6
Maximum of Months 1554854.72 1.96   23.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDORFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.277358E+10 1716.75 31-JAN-07:27 -30.3
February 0.161143E+10 1886.40 02-FEB-08:11 -36.3
March 0.674446E+09 1213.65 23-MAR-05:07 2.20
April 90505836.36 1539.39 06-APR-06:15 -4.4
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 268182.14 51.53 20-OCT-15:00 23.30
November 0.894399E+09 1469.77 26-NOV-05:00 -25.0
December 0.222368E+10 1881.27 09-DEC-15:00 -18.9
         
Annual Sum or Average 0.826832E+10      
Minimum of Months 0.00 0.00   -36.3
Maximum of Months 0.277358E+10 1886.40   23.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: REARSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM301

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.380274E+09 441.55 31-JAN-07:55 -30.0
February 0.196551E+09 542.56 02-FEB-09:23 -34.5
March 11765085.68 177.64 06-MAR-07:02 -12.7
April 1266184.67 124.34 15-APR-14:05 29.50
May 1408726.81 108.06 31-MAY-14:15 29.60
June 2317707.65 135.67 25-JUN-14:05 32.20
July 3677564.05 101.56 26-JUL-14:05 29.50
August 4719565.54 146.18 04-AUG-14:05 33.40
September 3732790.47 147.07 06-SEP-14:05 32.20
October 490179.72 76.15 20-OCT-14:15 22.83
November 69818768.41 336.31 26-NOV-08:00 -25.6
December 0.183427E+09 405.06 09-DEC-08:55 -22.8
         
Annual Sum or Average 0.859449E+09      
Minimum of Months 490179.72 76.15   -34.5
Maximum of Months 0.380274E+09 542.56   33.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM302_305

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 24234556.81 707.75 19-JAN-15:05 -22.8
February 54416697.67 677.31 03-FEB-15:05 -26.6
March 65924.66 26.15 19-MAR-14:10 18.30
April 4030074.91 456.02 15-APR-14:05 29.50
May 3361552.42 379.97 31-MAY-14:15 29.60
June 5693140.54 509.82 25-JUN-14:05 32.20
July 7693957.36 369.11 26-JUL-14:05 29.50
August 12765279.46 550.85 04-AUG-14:05 33.40
September 10180750.20 543.47 06-SEP-14:05 32.20
October 1035458.85 231.60 20-OCT-14:15 22.83
November 86038.58 315.62 26-NOV-15:07 -13.4
December 14611362.59 230.94 08-DEC-15:10 -15.9
         
Annual Sum or Average 0.138175E+09      
Minimum of Months 65924.66 26.15   -26.6
Maximum of Months 54416697.67 707.75   33.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM306_308

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 555645.60 259.74 19-JAN-15:08 -22.8
February 12926533.48 459.22 01-FEB-15:08 -26.1
March 17570.38 12.00 19-MAR-14:10 18.30
April 3160643.06 364.39 15-APR-14:05 29.50
May 2833218.45 317.19 31-MAY-14:15 29.60
June 4852189.81 417.82 25-JUN-14:05 32.20
July 6556829.56 309.64 26-JUL-14:05 29.50
August 10912562.10 467.84 04-AUG-14:05 33.40
September 8156771.91 439.38 06-SEP-14:05 32.20
October 806850.72 184.09 20-OCT-14:15 22.83
November 16907.83 84.54 26-NOV-15:10 -13.4
December 142281.35 345.47 11-DEC-15:07 -19.5
         
Annual Sum or Average 50938004.24      
Minimum of Months 16907.83 12.00   -26.1
Maximum of Months 12926533.48 467.84   33.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM309_312

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.719997E+09 3845.93 17-JAN-16:01 -0.9
February 0.376788E+09 4080.25 24-FEB-09:02 3.07
March 66923020.44 4046.59 22-MAR-08:02 -1.4
April 17948209.28 4462.44 07-APR-08:03 6.20
May 13227387.50 4390.27 02-MAY-08:03 4.08
June 21984310.32 3152.79 05-JUN-08:04 9.90
July 25293287.32 1167.22 04-JUL-21:01 21.70
August 23668377.19 2861.24 07-AUG-08:04 15.47
September 18780882.29 3434.15 30-SEP-18:04 5.92
October 17216909.60 4374.96 06-OCT-08:03 6.45
November 0.159443E+09 4197.75 09-NOV-16:03 2.12
December 0.447868E+09 3827.56 30-DEC-16:01 -1.1
         
Annual Sum or Average 0.190914E+10      
Minimum of Months 13227387.50 1167.22   -1.4
Maximum of Months 0.719997E+09 4462.44   21.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM313

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 71317439.99 196.57 31-JAN-09:02 -28.0
February 56432775.16 280.15 02-FEB-09:23 -34.5
March 160126.82 26.96 25-MAR-15:00 18.90
April 1448845.94 135.87 15-APR-14:50 29.90
May 1923934.18 120.42 31-MAY-14:15 29.60
June 4964137.88 148.94 25-JUN-14:05 32.20
July 5689067.55 117.87 26-JUL-15:00 30.00
August 6091301.34 162.01 04-AUG-14:05 33.40
September 4300399.57 153.49 06-SEP-14:05 32.20
October 521525.25 76.80 20-OCT-14:15 22.83
November 4832096.47 78.82 26-NOV-08:00 -25.6
December 44799613.62 236.99 13-DEC-15:30 -4.2
         
Annual Sum or Average 0.202481E+09      
Minimum of Months 160126.82 26.96   -34.5
Maximum of Months 71317439.99 280.15   33.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM314

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.634258E+09 1525.30 16-JAN-16:01 0.92
February 0.345640E+09 1547.98 23-FEB-16:01 3.30
March 0.110634E+09 1500.17 06-MAR-16:01 -0.7
April 17558157.60 1512.04 02-APR-15:01 0.60
May 3824343.25 1197.72 02-MAY-08:03 4.08
June 5123695.00 781.25 04-JUN-18:04 13.22
July 5520177.22 416.30 10-JUL-15:04 18.30
August 5974873.41 450.49 25-AUG-08:04 14.68
September 4499491.09 1126.99 30-SEP-08:03 3.35
October 4204068.60 1183.60 14-OCT-08:03 2.32
November 0.178217E+09 1502.91 30-NOV-16:01 -0.6
December 0.459978E+09 1521.48 14-DEC-16:01 0.92
         
Annual Sum or Average 0.177543E+10      
Minimum of Months 3824343.25 416.30   -0.7
Maximum of Months 0.634258E+09 1547.98   18.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM315_318

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 16565562.23 4075.88 09-JAN-09:03 -3.2
February 12451763.59 4069.57 13-FEB-09:03 -3.7
March 13008301.89 4281.08 21-MAR-15:03 -0.1
April 10011832.67 3898.98 03-APR-08:03 -5.9
May 8135191.39 1661.45 17-MAY-18:04 13.22
June 16004993.53 2403.36 05-JUN-18:04 12.12
July 19643797.33 1158.31 23-JUL-18:36 22.20
August 20134654.99 1187.98 22-AUG-20:51 22.20
September 11916105.66 2277.71 21-SEP-18:04 12.80
October 6707328.66 2343.20 26-OCT-08:03 1.28
November 11668949.65 4180.76 30-NOV-16:03 -0.6
December 16299005.19 4249.14 04-DEC-16:03 0.00
         
Annual Sum or Average 0.162547E+09      
Minimum of Months 6707328.66 1158.31   -5.9
Maximum of Months 20134654.99 4281.08   22.20



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ELEVATORCOREFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM319

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 85860.07 22.54 25-MAR-15:00 18.90
April 746938.99 130.88 15-APR-14:05 29.50
May 1325648.53 82.84 04-MAY-15:00 25.00
June 549587.76 59.00 14-JUN-14:50 23.40
July 965709.85 74.78 20-JUL-14:10 26.20
August 1751321.40 70.22 31-AUG-15:00 24.40
September 1480692.26 125.78 16-SEP-14:05 29.32
October 511726.20 73.93 20-OCT-15:00 23.30
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 7417485.07      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 1751321.40 130.88   29.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM320_323

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.339628E+09 3780.87 09-JAN-09:02 -3.2
February 0.201731E+09 4182.61 24-FEB-09:03 3.07
March 23921496.86 4089.85 27-MAR-08:03 1.20
April 17088965.01 3902.78 02-APR-08:03 -2.2
May 13611902.66 3140.47 17-MAY-15:04 13.90
June 18415215.01 2660.93 02-JUN-08:04 9.07
July 21517910.03 1152.10 04-JUL-20:51 21.70
August 22659626.47 1569.39 06-AUG-15:04 19.22
September 18248558.94 3831.06 24-SEP-16:14 14.63
October 17052248.68 4269.82 17-OCT-08:03 4.35
November 66025930.98 4023.19 13-NOV-09:03 -0.4
December 0.182992E+09 4013.12 02-DEC-09:03 -0.2
         
Annual Sum or Average 0.942894E+09      
Minimum of Months 13611902.66 1152.10   -3.2
Maximum of Months 0.339628E+09 4269.82   21.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM324

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3707.75 18.54 31-JAN-15:10 -20.0
February 36291.18 145.62 01-FEB-15:08 -26.1
March 83817.77 22.17 25-MAR-15:00 18.90
April 1462006.41 142.09 15-APR-15:00 30.00
May 1817709.35 119.67 31-MAY-15:00 30.00
June 5610595.60 168.12 11-JUN-15:00 33.30
July 6285530.68 127.25 26-JUL-15:00 30.00
August 6621333.92 177.80 04-AUG-14:50 33.80
September 4571695.70 160.69 06-SEP-14:50 32.20
October 432916.35 67.10 20-OCT-15:00 23.30
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 26925604.71      
Minimum of Months 0.00 0.00   -26.1
Maximum of Months 6621333.92 177.80   33.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONTSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONTSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 13930863.33 138.85 31-JAN-07:53 -30.0
February 39875890.84 250.70 02-FEB-09:43 -33.7
March 1510459.29 1.34 21-MAR-00:40 -5.2
April 1483303.15 1.70 25-APR-05:55 1.10
May 1532804.05 1.71 13-MAY-13:00 12.20
June 1503370.68 1.48 18-JUN-21:00 23.30
July 1551111.10 1.12 23-JUL-24:00 12.20
August 1532877.90 1.18 04-AUG-18:40 19.47
September 1503749.52 1.27 18-SEP-17:45 10.18
October 1535729.72 0.89 31-OCT-20:35 -1.0
November 1490466.30 1.31 20-NOV-16:55 -0.6
December 9464197.33 176.48 09-DEC-09:53 -22.2
         
Annual Sum or Average 76914823.21      
Minimum of Months 1483303.15 0.89   -33.7
Maximum of Months 39875890.84 250.70   23.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: REARSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 34250299.73 268.89 19-JAN-05:00 -27.2
February 37333118.03 307.67 02-FEB-07:45 -36.7
March 1650689.48 2.11 05-MAR-18:45 -13.6
April 1639870.36 2.12 17-APR-20:35 14.07
May 1660605.26 2.04 13-MAY-13:00 12.20
June 1617451.40 2.53 09-JUN-16:11 18.67
July 1656801.12 2.35 11-JUL-14:10 17.70
August 1639526.55 2.06 04-AUG-18:40 19.47
September 1682725.94 2.43 15-SEP-21:00 11.70
October 1713483.76 2.51 31-OCT-18:35 -0.3
November 2951623.83 84.87 26-NOV-04:20 -25.0
December 29008870.55 307.78 09-DEC-02:00 -22.8
         
Annual Sum or Average 0.116805E+09      
Minimum of Months 1617451.40 2.04   -36.7
Maximum of Months 37333118.03 307.78   19.47



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDORFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.590971E+10 3473.53 31-JAN-05:00 -30.6
February 0.400658E+10 3539.40 03-FEB-09:11 -32.1
March 0.231756E+10 2623.33 06-MAR-06:02 -14.1
April 0.830025E+09 1885.75 03-APR-05:02 -7.2
May 25081614.21 574.20 02-MAY-05:02 2.20
June 1205340.82 147.29 03-JUN-05:00 5.60
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 96766736.63 1061.71 30-SEP-05:23 0.30
October 0.626928E+09 1202.81 27-OCT-05:02 0.00
November 0.278910E+10 3190.89 26-NOV-05:00 -25.0
December 0.513899E+10 3425.79 09-DEC-15:00 -18.9
         
Annual Sum or Average 0.217420E+11      
Minimum of Months 0.00 0.00   -32.1
Maximum of Months 0.590971E+10 3539.40   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: REARSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM401

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.242614E+10 2146.30 13-JAN-16:01 3.62
February 0.168381E+10 2148.98 24-FEB-09:01 3.07
March 0.101784E+10 2193.31 24-MAR-08:61 8.48
April 0.387344E+09 2224.22 07-APR-15:01 10.60
May 30774179.81 2137.20 02-MAY-08:61 4.08
June 13072131.40 705.45 06-JUN-15:04 16.28
July 11318880.68 371.58 22-JUL-08:55 17.80
August 10710784.85 953.11 07-AUG-08:03 15.47
September 69388363.39 2181.38 28-SEP-08:61 7.38
October 0.343771E+09 2220.17 20-OCT-08:61 9.70
November 0.115325E+10 2264.73 20-NOV-09:01 12.98
December 0.206140E+10 2161.46 02-DEC-16:01 4.95
         
Annual Sum or Average 0.920882E+10      
Minimum of Months 10710784.85 371.58   3.07
Maximum of Months 0.242614E+10 2264.73   17.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM402_405

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.155661E+10 1738.41 03-JAN-15:47 -11.7
February 0.791230E+09 2076.74 02-FEB-07:23 -36.7
March 0.125834E+09 791.82 06-MAR-05:50 -14.6
April 4188549.23 224.23 03-APR-05:45 -7.2
May 175155.23 72.74 04-MAY-14:10 24.50
June 346316.35 70.50 14-JUN-14:10 23.80
July 85405.44 86.83 14-JUL-14:10 24.40
August 691992.16 107.44 12-AUG-14:10 24.45
September 28485.78 27.97 20-SEP-14:10 22.70
October 696648.71 197.30 20-OCT-14:15 22.83
November 0.347501E+09 1466.60 26-NOV-07:23 -27.2
December 0.977429E+09 1405.69 09-DEC-08:55 -22.8
         
Annual Sum or Average 0.380482E+10      
Minimum of Months 28485.78 27.97   -36.7
Maximum of Months 0.155661E+10 2076.74   24.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM406_408

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.107486E+10 1322.06 31-JAN-07:23 -30.3
February 0.545336E+09 1618.57 02-FEB-07:23 -36.7
March 53802746.85 549.78 06-MAR-06:00 -14.4
April 703018.98 82.49 03-APR-05:45 -7.2
May 150476.25 52.74 04-MAY-14:10 24.50
June 379863.96 69.17 14-JUN-14:10 23.80
July 49237.72 82.06 14-JUL-14:10 24.40
August 676099.61 104.81 12-AUG-14:10 24.45
September 14714.68 18.66 20-SEP-14:10 22.70
October 548208.15 155.79 20-OCT-14:15 22.83
November 0.222994E+09 1117.98 26-NOV-07:12 -27.8
December 0.617183E+09 1065.14 09-DEC-08:55 -22.8
         
Annual Sum or Average 0.251670E+10      
Minimum of Months 14714.68 18.66   -36.7
Maximum of Months 0.107486E+10 1618.57   24.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM409_412

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.237234E+10 5209.06 16-JAN-16:01 0.92
February 0.143155E+10 5234.38 22-FEB-16:01 1.10
March 0.611780E+09 5219.06 10-MAR-16:03 -0.7
April 0.160772E+09 5202.95 02-APR-15:01 0.60
May 13461846.09 4741.27 18-MAY-08:03 10.18
June 26525509.76 4613.87 02-JUN-08:03 9.07
July 31364242.82 2502.23 10-JUL-21:16 15.73
August 30137319.21 2311.19 10-AUG-21:16 18.13
September 34124961.63 4348.53 29-SEP-15:03 10.00
October 94312731.89 4877.69 01-OCT-08:03 10.72
November 0.835390E+09 5235.49 17-NOV-16:01 1.10
December 0.181398E+10 5190.23 04-DEC-16:01 0.00
         
Annual Sum or Average 0.745574E+10      
Minimum of Months 13461846.09 2311.19   -0.7
Maximum of Months 0.237234E+10 5235.49   18.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM413

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.680244E+09 715.84 31-JAN-07:23 -30.3
February 0.351039E+09 852.59 02-FEB-07:23 -36.7
March 71078282.32 352.93 06-MAR-06:02 -14.1
April 3577383.88 122.57 03-APR-05:45 -7.2
May 802231.35 51.79 05-MAY-14:30 26.15
June 489035.95 49.74 17-JUN-14:30 24.75
July 533775.38 51.46 20-JUL-14:10 26.20
August 1122364.20 58.88 31-AUG-15:00 24.40
September 448442.18 114.97 16-SEP-14:05 29.32
October 410803.90 72.68 20-OCT-14:15 22.83
November 0.158675E+09 600.39 26-NOV-07:12 -27.8
December 0.423223E+09 647.12 09-DEC-09:23 -22.5
         
Annual Sum or Average 0.169164E+10      
Minimum of Months 410803.90 49.74   -36.7
Maximum of Months 0.680244E+09 852.59   29.32



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM414

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.286289E+09 457.74 31-JAN-06:02 -30.6
February 0.150935E+09 554.34 02-FEB-07:23 -36.7
March 6495007.08 174.62 06-MAR-06:02 -14.1
April 181963.02 31.38 14-APR-15:00 22.20
May 596843.21 53.27 04-MAY-15:00 25.00
June 230175.36 39.29 14-JUN-14:10 23.80
July 701539.00 62.92 20-JUL-14:40 26.50
August 734462.71 54.82 13-AUG-14:50 26.10
September 332824.88 44.87 10-SEP-14:10 26.88
October 300000.82 51.16 20-OCT-14:15 22.83
November 45745820.87 391.26 26-NOV-07:12 -27.8
December 0.126978E+09 375.36 09-DEC-09:12 -22.6
         
Annual Sum or Average 0.619521E+09      
Minimum of Months 181963.02 31.38   -36.7
Maximum of Months 0.286289E+09 554.34   26.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM415_418

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.134098E+10 5055.06 17-JAN-16:01 -0.9
February 0.750858E+09 5202.98 24-FEB-09:03 3.07
March 0.226397E+09 5504.26 21-MAR-15:03 -0.1
April 51754702.04 5094.80 06-APR-08:03 -0.7
May 13481114.48 3754.14 06-MAY-16:55 18.90
June 23431698.05 3072.85 05-JUN-18:04 12.12
July 27770971.14 2520.36 09-JUL-16:56 19.40
August 28042234.03 2374.35 06-AUG-16:55 19.40
September 20920760.83 4764.85 29-SEP-08:03 5.05
October 22392401.79 4919.97 12-OCT-08:03 7.30
November 0.380216E+09 5319.22 11-NOV-09:03 -2.5
December 0.893383E+09 5096.31 17-DEC-09:02 -5.5
         
Annual Sum or Average 0.377963E+10      
Minimum of Months 13481114.48 2374.35   -5.5
Maximum of Months 0.134098E+10 5504.26   19.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ELEVATORCOREFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM419

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.457850E+09 1426.03 16-JAN-16:01 0.92
February 0.243199E+09 1374.22 11-FEB-16:01 -2.9
March 76165751.36 1375.28 02-MAR-16:01 -3.2
April 15953289.60 1275.69 25-APR-08:03 1.20
May 3420150.58 788.00 02-MAY-08:03 4.08
June 6069507.29 705.14 02-JUN-08:03 9.07
July 7807762.98 383.55 11-JUL-18:06 18.80
August 7532648.91 652.12 06-AUG-16:55 19.40
September 5297468.50 1220.05 26-SEP-08:03 11.38
October 5291683.82 1312.57 14-OCT-08:03 2.32
November 0.130378E+09 1409.62 22-NOV-16:01 -1.1
December 0.314852E+09 1416.98 04-DEC-16:01 0.00
         
Annual Sum or Average 0.127382E+10      
Minimum of Months 3420150.58 383.55   -3.2
Maximum of Months 0.457850E+09 1426.03   19.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM420_423

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.121373E+10 4729.99 16-JAN-16:01 0.92
February 0.697718E+09 4740.97 22-FEB-16:01 1.10
March 0.222530E+09 5013.44 25-MAR-08:03 2.57
April 53476812.95 4957.93 06-APR-08:03 -0.7
May 14553581.39 3186.07 13-MAY-18:04 12.12
June 23582353.24 3144.87 04-JUN-18:04 13.22
July 27191076.30 2785.09 22-JUL-18:56 18.90
August 25406797.93 2640.29 25-AUG-08:04 14.68
September 21381116.79 4024.29 29-SEP-08:03 5.05
October 23979888.43 5101.79 28-OCT-08:03 1.55
November 0.358974E+09 4735.23 17-NOV-16:01 1.10
December 0.843604E+09 4908.76 03-DEC-09:03 -1.5
         
Annual Sum or Average 0.352613E+10      
Minimum of Months 14553581.39 2640.29   -1.5
Maximum of Months 0.121373E+10 5101.79   18.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GUESTROOM424

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.118579E+10 1738.77 13-JAN-16:01 3.62
February 0.750714E+09 1742.95 23-FEB-16:01 3.30
March 0.345313E+09 1707.59 17-MAR-15:01 1.70
April 0.103838E+09 1707.24 02-APR-15:01 0.60
May 5932611.03 995.84 01-MAY-08:03 7.80
June 6993482.89 829.90 02-JUN-08:03 9.07
July 8580260.37 432.93 21-JUL-18:36 20.00
August 8343480.64 421.19 15-AUG-18:06 20.73
September 11741572.91 1183.74 29-SEP-15:03 10.00
October 57551903.97 1367.06 26-OCT-08:61 1.28
November 0.450709E+09 1795.14 15-NOV-16:01 8.03
December 0.942973E+09 1759.18 02-DEC-16:01 4.95
         
Annual Sum or Average 0.387848E+10      
Minimum of Months 5932611.03 421.19   0.60
Maximum of Months 0.118579E+10 1795.14   20.73



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONTSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 -2.8
February 0.00 0.00 01-FEB-00:10 -24.1
March 0.00 0.00 01-MAR-00:10 -11.0
April 0.00 0.00 01-APR-00:10 -1.2
May 0.00 0.00 01-MAY-00:10 8.22
June 0.00 0.00 01-JUN-00:10 14.70
July 0.00 0.00 01-JUL-00:10 18.93
August 0.00 0.00 01-AUG-00:10 18.15
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 3.92
November 0.00 0.00 01-NOV-00:10 1.65
December 0.00 0.00 01-DEC-00:10 -0.7
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -24.1
Maximum of Months 0.00 0.00   18.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FRONTSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.213025E+09 474.52 31-JAN-07:53 -30.0
February 0.155937E+09 607.02 02-FEB-07:55 -36.7
March 3911571.20 81.87 06-MAR-07:02 -12.7
April 3055278.35 3.75 16-APR-24:00 13.90
May 3165897.59 3.71 13-MAY-13:00 12.20
June 3124875.18 4.02 09-JUN-16:11 18.67
July 3202250.59 3.49 11-JUL-14:00 17.80
August 3126876.85 3.62 04-AUG-18:40 19.47
September 3106344.19 4.08 18-SEP-17:45 10.18
October 3124237.27 2.85 31-OCT-18:35 -0.3
November 22311726.10 308.69 26-NOV-04:00 -25.0
December 94456855.64 540.88 09-DEC-09:00 -22.8
         
Annual Sum or Average 0.511548E+09      
Minimum of Months 3055278.35 2.85   -36.7
Maximum of Months 0.213025E+09 607.02   19.47



Table of Contents

Report: ZoneElectricSummaryMonthly

For: REARSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.283549E+09 105.87 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.256109E+09 105.87 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.283549E+09 105.87 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.274403E+09 105.87 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.283549E+09 105.87 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.274403E+09 105.87 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.283549E+09 105.87 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.283549E+09 105.87 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.274403E+09 105.87 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.283549E+09 105.87 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.274403E+09 105.87 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.283549E+09 105.87 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.333857E+10     0.00    
Minimum of Months 0.256109E+09 105.87   0.00 0.00  
Maximum of Months 0.283549E+09 105.87   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDORFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133427E+10 498.16 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.120515E+10 498.16 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.133427E+10 498.16 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.129123E+10 498.16 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.133427E+10 498.16 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.129123E+10 498.16 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.133427E+10 498.16 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.133427E+10 498.16 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.129123E+10 498.16 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.133427E+10 498.16 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.129123E+10 498.16 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.133427E+10 498.16 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.157099E+11     0.00    
Minimum of Months 0.120515E+10 498.16   0.00 0.00  
Maximum of Months 0.133427E+10 498.16   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: REARSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 24052766.60 14.37 01-JAN-08:09 0.00 0.00 01-JAN-00:10
February 21725079.51 14.37 01-FEB-08:09 0.00 0.00 01-FEB-00:10
March 24052766.60 14.37 01-MAR-08:09 0.00 0.00 01-MAR-00:10
April 23276870.90 14.37 01-APR-07:10 0.00 0.00 01-APR-00:10
May 24052766.60 14.37 01-MAY-07:10 0.00 0.00 01-MAY-00:10
June 23276870.90 14.37 01-JUN-07:10 0.00 0.00 01-JUN-00:10
July 24052766.60 14.37 01-JUL-07:10 0.00 0.00 01-JUL-00:10
August 24052766.60 14.37 01-AUG-07:10 0.00 0.00 01-AUG-00:10
September 23276870.90 14.37 01-SEP-07:10 0.00 0.00 01-SEP-00:10
October 24052766.60 14.37 01-OCT-07:10 0.00 0.00 01-OCT-00:10
November 23276870.90 14.37 01-NOV-07:10 0.00 0.00 01-NOV-00:10
December 24052766.60 14.37 01-DEC-08:09 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.283202E+09     0.00    
Minimum of Months 21725079.51 14.37   0.00 0.00  
Maximum of Months 24052766.60 14.37   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONTLOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123758E+10 1474.30 01-JAN-16:40 0.427743E+10 4249.25 01-JAN-06:10
February 0.102568E+10 1474.30 01-FEB-17:19 0.386349E+10 4249.25 01-FEB-06:10
March 0.100956E+10 1474.30 01-MAR-17:00 0.427743E+10 4249.25 01-MAR-06:10
April 0.927055E+09 918.03 10-APR-07:10 0.413945E+10 4249.25 01-APR-05:10
May 0.898021E+09 776.04 25-MAY-07:10 0.427743E+10 4249.25 01-MAY-05:10
June 0.858192E+09 868.29 13-JUN-07:10 0.413945E+10 4249.25 01-JUN-05:10
July 0.895176E+09 878.01 09-JUL-07:10 0.427743E+10 4249.25 01-JUL-05:10
August 0.918059E+09 838.95 31-AUG-07:10 0.427743E+10 4249.25 01-AUG-05:10
September 0.943512E+09 921.64 21-SEP-07:10 0.413945E+10 4249.25 01-SEP-05:10
October 0.105917E+10 1474.30 28-OCT-16:00 0.427743E+10 4249.25 01-OCT-05:10
November 0.116854E+10 1474.30 01-NOV-16:00 0.413945E+10 4249.25 01-NOV-05:10
December 0.132859E+10 1474.30 01-DEC-16:30 0.427743E+10 4249.25 01-DEC-06:10
             
Annual Sum or Average 0.122691E+11     0.503633E+11    
Minimum of Months 0.858192E+09 776.04   0.386349E+10 4249.25  
Maximum of Months 0.132859E+10 1474.30   0.427743E+10 4249.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RESTROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.325774E+09 121.63 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.294247E+09 121.63 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.325774E+09 121.63 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.315265E+09 121.63 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.325774E+09 121.63 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.315265E+09 121.63 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.325774E+09 121.63 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.325774E+09 121.63 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.315265E+09 121.63 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.325774E+09 121.63 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.315265E+09 121.63 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.325774E+09 121.63 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.383573E+10     0.00    
Minimum of Months 0.294247E+09 121.63   0.00 0.00  
Maximum of Months 0.325774E+09 121.63   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MEETINGROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.834574E+09 838.14 01-JAN-16:40 0.179790E+09 237.69 01-JAN-08:09
February 0.701717E+09 838.14 01-FEB-17:19 0.162391E+09 237.69 01-FEB-08:09
March 0.696928E+09 838.14 01-MAR-17:00 0.179790E+09 237.69 01-MAR-08:09
April 0.652308E+09 722.99 10-APR-07:10 0.173991E+09 237.69 01-APR-07:10
May 0.627783E+09 662.13 04-MAY-07:10 0.179790E+09 237.69 01-MAY-07:10
June 0.596110E+09 677.79 13-JUN-07:10 0.173991E+09 237.69 01-JUN-07:10
July 0.622944E+09 686.50 09-JUL-07:10 0.179790E+09 237.69 01-JUL-07:10
August 0.634807E+09 678.13 24-AUG-07:10 0.179790E+09 237.69 01-AUG-07:10
September 0.657708E+09 727.74 21-SEP-07:10 0.173991E+09 237.69 01-SEP-07:10
October 0.732966E+09 838.14 28-OCT-16:00 0.179790E+09 237.69 01-OCT-07:10
November 0.790089E+09 838.14 01-NOV-16:00 0.173991E+09 237.69 01-NOV-07:10
December 0.906116E+09 838.14 01-DEC-16:30 0.179790E+09 237.69 01-DEC-08:09
             
Annual Sum or Average 0.845405E+10     0.211689E+10    
Minimum of Months 0.596110E+09 662.13   0.162391E+09 237.69  
Maximum of Months 0.906116E+09 838.14   0.179790E+09 237.69  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECHANICALROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101070E+09 60.38 01-JAN-08:09 0.00 0.00 01-JAN-00:10
February 91288912.54 60.38 01-FEB-08:09 0.00 0.00 01-FEB-00:10
March 0.101070E+09 60.38 01-MAR-08:09 0.00 0.00 01-MAR-00:10
April 97809549.15 60.38 01-APR-07:10 0.00 0.00 01-APR-00:10
May 0.101070E+09 60.38 01-MAY-07:10 0.00 0.00 01-MAY-00:10
June 97809549.15 60.38 01-JUN-07:10 0.00 0.00 01-JUN-00:10
July 0.101070E+09 60.38 01-JUL-07:10 0.00 0.00 01-JUL-00:10
August 0.101070E+09 60.38 01-AUG-07:10 0.00 0.00 01-AUG-00:10
September 97809549.15 60.38 01-SEP-07:10 0.00 0.00 01-SEP-00:10
October 0.101070E+09 60.38 01-OCT-07:10 0.00 0.00 01-OCT-00:10
November 97809549.15 60.38 01-NOV-07:10 0.00 0.00 01-NOV-00:10
December 0.101070E+09 60.38 01-DEC-08:09 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.119002E+10     0.00    
Minimum of Months 91288912.54 60.38   0.00 0.00  
Maximum of Months 0.101070E+09 60.38   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM101

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM102

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM103

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110112E+09 99.23 01-JAN-19:10 0.357425E+09 349.07 01-JAN-08:09
February 99048113.69 99.23 01-FEB-20:10 0.322587E+09 349.07 01-FEB-07:10
March 0.108804E+09 99.23 01-MAR-20:10 0.356629E+09 349.07 01-MAR-07:10
April 0.106264E+09 99.23 01-APR-18:10 0.345724E+09 349.07 01-APR-07:10
May 0.109240E+09 99.23 01-MAY-19:10 0.356894E+09 349.07 01-MAY-06:10
June 0.105421E+09 99.23 01-JUN-19:10 0.345193E+09 349.07 01-JUN-06:10
July 0.110098E+09 99.23 01-JUL-18:10 0.357425E+09 349.07 01-JUL-07:10
August 0.108804E+09 99.23 01-AUG-19:10 0.356629E+09 349.07 01-AUG-06:10
September 0.106293E+09 99.23 01-SEP-19:10 0.345724E+09 349.07 01-SEP-06:10
October 0.109662E+09 99.23 01-OCT-18:10 0.357159E+09 349.07 01-OCT-07:10
November 0.106279E+09 99.23 01-NOV-19:10 0.345724E+09 349.07 01-NOV-06:10
December 0.110112E+09 99.23 01-DEC-20:10 0.357425E+09 349.07 01-DEC-07:10
             
Annual Sum or Average 0.129014E+10     0.420454E+10    
Minimum of Months 99048113.69 99.23   0.322587E+09 349.07  
Maximum of Months 0.110112E+09 99.23   0.357425E+09 349.07  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM104

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110104E+09 99.23 01-JAN-19:10 0.357399E+09 349.05 01-JAN-08:09
February 99041085.40 99.23 01-FEB-20:10 0.322564E+09 349.05 01-FEB-07:10
March 0.108797E+09 99.23 01-MAR-20:10 0.356604E+09 349.05 01-MAR-07:10
April 0.106257E+09 99.23 01-APR-18:10 0.345699E+09 349.05 01-APR-07:10
May 0.109232E+09 99.23 01-MAY-19:10 0.356869E+09 349.05 01-MAY-06:10
June 0.105414E+09 99.23 01-JUN-19:10 0.345169E+09 349.05 01-JUN-06:10
July 0.110090E+09 99.23 01-JUL-18:10 0.357399E+09 349.05 01-JUL-07:10
August 0.108797E+09 99.23 01-AUG-19:10 0.356604E+09 349.05 01-AUG-06:10
September 0.106285E+09 99.23 01-SEP-19:10 0.345699E+09 349.05 01-SEP-06:10
October 0.109654E+09 99.23 01-OCT-18:10 0.357134E+09 349.05 01-OCT-07:10
November 0.106271E+09 99.23 01-NOV-19:10 0.345699E+09 349.05 01-NOV-06:10
December 0.110104E+09 99.23 01-DEC-20:10 0.357399E+09 349.05 01-DEC-07:10
             
Annual Sum or Average 0.129005E+10     0.420424E+10    
Minimum of Months 99041085.40 99.23   0.322564E+09 349.05  
Maximum of Months 0.110104E+09 99.23   0.357399E+09 349.05  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM105

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110104E+09 99.23 01-JAN-19:10 0.357399E+09 349.05 01-JAN-08:09
February 99041085.40 99.23 01-FEB-20:10 0.322564E+09 349.05 01-FEB-07:10
March 0.108797E+09 99.23 01-MAR-20:10 0.356604E+09 349.05 01-MAR-07:10
April 0.106257E+09 99.23 01-APR-18:10 0.345699E+09 349.05 01-APR-07:10
May 0.109232E+09 99.23 01-MAY-19:10 0.356869E+09 349.05 01-MAY-06:10
June 0.105414E+09 99.23 01-JUN-19:10 0.345169E+09 349.05 01-JUN-06:10
July 0.110090E+09 99.23 01-JUL-18:10 0.357399E+09 349.05 01-JUL-07:10
August 0.108797E+09 99.23 01-AUG-19:10 0.356604E+09 349.05 01-AUG-06:10
September 0.106285E+09 99.23 01-SEP-19:10 0.345699E+09 349.05 01-SEP-06:10
October 0.109654E+09 99.23 01-OCT-18:10 0.357134E+09 349.05 01-OCT-07:10
November 0.106271E+09 99.23 01-NOV-19:10 0.345699E+09 349.05 01-NOV-06:10
December 0.110104E+09 99.23 01-DEC-20:10 0.357399E+09 349.05 01-DEC-07:10
             
Annual Sum or Average 0.129005E+10     0.420424E+10    
Minimum of Months 99041085.40 99.23   0.322564E+09 349.05  
Maximum of Months 0.110104E+09 99.23   0.357399E+09 349.05  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: EMPLOYEELOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.278490E+09 207.09 01-JAN-08:09 0.812993E+09 672.25 01-JAN-08:09
February 0.251540E+09 207.09 01-FEB-08:09 0.734316E+09 672.25 01-FEB-08:09
March 0.278490E+09 207.09 01-MAR-08:09 0.812993E+09 672.25 01-MAR-08:09
April 0.269507E+09 207.09 01-APR-07:10 0.786767E+09 672.25 01-APR-07:10
May 0.278490E+09 207.09 01-MAY-07:10 0.812993E+09 672.25 01-MAY-07:10
June 0.269507E+09 207.09 01-JUN-07:10 0.786767E+09 672.25 01-JUN-07:10
July 0.278490E+09 207.09 01-JUL-07:10 0.812993E+09 672.25 01-JUL-07:10
August 0.278490E+09 207.09 01-AUG-07:10 0.812993E+09 672.25 01-AUG-07:10
September 0.269507E+09 207.09 01-SEP-07:10 0.786767E+09 672.25 01-SEP-07:10
October 0.278490E+09 207.09 01-OCT-07:10 0.812993E+09 672.25 01-OCT-07:10
November 0.269507E+09 207.09 01-NOV-07:10 0.786767E+09 672.25 01-NOV-07:10
December 0.278490E+09 207.09 01-DEC-08:09 0.812993E+09 672.25 01-DEC-08:09
             
Annual Sum or Average 0.327900E+10     0.957233E+10    
Minimum of Months 0.251540E+09 207.09   0.734316E+09 672.25  
Maximum of Months 0.278490E+09 207.09   0.812993E+09 672.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRYROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.395890E+09 558.09 01-JAN-16:40 0.241866E+10 2709.07 01-JAN-08:09
February 0.335801E+09 533.15 01-FEB-16:00 0.218460E+10 2709.07 01-FEB-08:09
March 0.328583E+09 513.17 12-MAR-07:10 0.241866E+10 2709.07 01-MAR-08:09
April 0.319633E+09 471.80 10-APR-07:10 0.234064E+10 2709.07 01-APR-07:10
May 0.313318E+09 466.52 24-MAY-15:50 0.241866E+10 2709.07 01-MAY-07:10
June 0.299531E+09 438.89 09-JUN-15:20 0.234064E+10 2709.07 01-JUN-07:10
July 0.311320E+09 444.29 31-JUL-15:20 0.241866E+10 2709.07 01-JUL-07:10
August 0.309981E+09 450.83 16-AUG-14:30 0.241866E+10 2709.07 01-AUG-07:10
September 0.315923E+09 473.99 29-SEP-15:00 0.234064E+10 2709.07 01-SEP-07:10
October 0.349492E+09 507.58 21-OCT-07:10 0.241866E+10 2709.07 01-OCT-07:10
November 0.380499E+09 558.09 06-NOV-16:00 0.234064E+10 2709.07 01-NOV-07:10
December 0.439234E+09 558.09 01-DEC-16:30 0.241866E+10 2709.07 01-DEC-08:09
             
Annual Sum or Average 0.409920E+10     0.284778E+11    
Minimum of Months 0.299531E+09 438.89   0.218460E+10 2709.07  
Maximum of Months 0.439234E+09 558.09   0.241866E+10 2709.07  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ELEVATORCOREFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.112056E+11 8074.65 01-JAN-07:10
February 0.00 0.00 01-FEB-00:10 0.101212E+11 8074.65 01-FEB-07:10
March 0.00 0.00 01-MAR-00:10 0.112056E+11 8074.65 01-MAR-07:10
April 0.00 0.00 01-APR-00:10 0.108441E+11 8074.65 01-APR-06:10
May 0.00 0.00 01-MAY-00:10 0.112056E+11 8074.65 01-MAY-06:10
June 0.00 0.00 01-JUN-00:10 0.108441E+11 8074.65 01-JUN-06:10
July 0.00 0.00 01-JUL-00:10 0.112056E+11 8074.65 01-JUL-06:10
August 0.00 0.00 01-AUG-00:10 0.112056E+11 8074.65 01-AUG-06:10
September 0.00 0.00 01-SEP-00:10 0.108441E+11 8074.65 01-SEP-06:10
October 0.00 0.00 01-OCT-00:10 0.112056E+11 8074.65 01-OCT-06:10
November 0.00 0.00 01-NOV-00:10 0.108441E+11 8074.65 01-NOV-06:10
December 0.00 0.00 01-DEC-00:10 0.112056E+11 8074.65 01-DEC-07:10
             
Annual Sum or Average 0.00     0.131937E+12    
Minimum of Months 0.00 0.00   0.101212E+11 8074.65  
Maximum of Months 0.00 0.00   0.112056E+11 8074.65  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: EXERCISECENTERFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.564070E+09 315.90 01-JAN-07:10 0.710346E+09 606.20 01-JAN-07:10
February 0.509483E+09 315.90 01-FEB-07:10 0.641603E+09 606.20 01-FEB-07:10
March 0.564070E+09 315.90 01-MAR-07:10 0.710346E+09 606.20 01-MAR-07:10
April 0.545875E+09 315.90 01-APR-06:10 0.687432E+09 606.20 01-APR-06:10
May 0.564070E+09 315.90 01-MAY-06:10 0.710346E+09 606.20 01-MAY-06:10
June 0.545875E+09 315.90 01-JUN-06:10 0.687432E+09 606.20 01-JUN-06:10
July 0.564070E+09 315.90 01-JUL-06:10 0.710346E+09 606.20 01-JUL-06:10
August 0.564070E+09 315.90 01-AUG-06:10 0.710346E+09 606.20 01-AUG-06:10
September 0.545875E+09 315.90 01-SEP-06:10 0.687432E+09 606.20 01-SEP-06:10
October 0.564070E+09 315.90 01-OCT-06:10 0.710346E+09 606.20 01-OCT-06:10
November 0.545875E+09 315.90 01-NOV-06:10 0.687432E+09 606.20 01-NOV-06:10
December 0.564070E+09 315.90 01-DEC-07:10 0.710346E+09 606.20 01-DEC-07:10
             
Annual Sum or Average 0.664148E+10     0.836375E+10    
Minimum of Months 0.509483E+09 315.90   0.641603E+09 606.20  
Maximum of Months 0.564070E+09 315.90   0.710346E+09 606.20  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONTOFFICEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.103365E+10 609.04 01-JAN-16:40 0.248187E+10 1663.95 03-JAN-10:09
February 0.906775E+09 592.77 11-FEB-16:00 0.225598E+10 1663.95 01-FEB-10:09
March 0.947855E+09 581.15 12-MAR-07:10 0.252769E+10 1663.95 01-MAR-10:09
April 0.919254E+09 556.53 10-APR-07:10 0.241166E+10 1663.95 03-APR-09:09
May 0.902434E+09 537.75 24-MAY-15:00 0.251242E+10 1663.95 01-MAY-09:09
June 0.861051E+09 535.66 13-JUN-07:10 0.244221E+10 1663.95 01-JUN-09:09
July 0.895760E+09 539.98 09-JUL-07:10 0.248187E+10 1663.95 03-JUL-09:09
August 0.904315E+09 516.84 16-AUG-14:30 0.252769E+10 1663.95 01-AUG-09:09
September 0.912281E+09 553.86 29-SEP-15:00 0.241166E+10 1663.95 01-SEP-09:09
October 0.976383E+09 577.20 21-OCT-07:10 0.249714E+10 1663.95 02-OCT-09:09
November 0.997105E+09 609.04 06-NOV-16:00 0.241166E+10 1663.95 01-NOV-09:09
December 0.108043E+10 609.04 01-DEC-16:30 0.248187E+10 1663.95 01-DEC-10:09
             
Annual Sum or Average 0.113373E+11     0.294437E+11    
Minimum of Months 0.861051E+09 516.84   0.225598E+10 1663.95  
Maximum of Months 0.108043E+10 609.04   0.252769E+10 1663.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONTSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.283482E+09 105.84 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.256048E+09 105.84 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.283482E+09 105.84 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.274337E+09 105.84 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.283482E+09 105.84 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.274337E+09 105.84 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.283482E+09 105.84 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.283482E+09 105.84 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.274337E+09 105.84 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.283482E+09 105.84 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.274337E+09 105.84 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.283482E+09 105.84 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.333777E+10     0.00    
Minimum of Months 0.256048E+09 105.84   0.00 0.00  
Maximum of Months 0.283482E+09 105.84   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONTSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 15028313.11 8.98 01-JAN-08:09 0.00 0.00 01-JAN-00:10
February 13573960.23 8.98 01-FEB-08:09 0.00 0.00 01-FEB-00:10
March 15028313.11 8.98 01-MAR-08:09 0.00 0.00 01-MAR-00:10
April 14543528.81 8.98 01-APR-07:10 0.00 0.00 01-APR-00:10
May 15028313.11 8.98 01-MAY-07:10 0.00 0.00 01-MAY-00:10
June 14543528.81 8.98 01-JUN-07:10 0.00 0.00 01-JUN-00:10
July 15028313.11 8.98 01-JUL-07:10 0.00 0.00 01-JUL-00:10
August 15028313.11 8.98 01-AUG-07:10 0.00 0.00 01-AUG-00:10
September 14543528.81 8.98 01-SEP-07:10 0.00 0.00 01-SEP-00:10
October 15028313.11 8.98 01-OCT-07:10 0.00 0.00 01-OCT-00:10
November 14543528.81 8.98 01-NOV-07:10 0.00 0.00 01-NOV-00:10
December 15028313.11 8.98 01-DEC-08:09 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.176946E+09     0.00    
Minimum of Months 13573960.23 8.98   0.00 0.00  
Maximum of Months 15028313.11 8.98   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: REARSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.283549E+09 105.87 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.256109E+09 105.87 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.283549E+09 105.87 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.274403E+09 105.87 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.283549E+09 105.87 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.274403E+09 105.87 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.283549E+09 105.87 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.283549E+09 105.87 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.274403E+09 105.87 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.283549E+09 105.87 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.274403E+09 105.87 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.283549E+09 105.87 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.333857E+10     0.00    
Minimum of Months 0.256109E+09 105.87   0.00 0.00  
Maximum of Months 0.283549E+09 105.87   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDORFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.111188E+10 415.13 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.100428E+10 415.13 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.111188E+10 415.13 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.107601E+10 415.13 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.111188E+10 415.13 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.107601E+10 415.13 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.111188E+10 415.13 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.111188E+10 415.13 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.107601E+10 415.13 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.111188E+10 415.13 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.107601E+10 415.13 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.111188E+10 415.13 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.130915E+11     0.00    
Minimum of Months 0.100428E+10 415.13   0.00 0.00  
Maximum of Months 0.111188E+10 415.13   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: REARSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 24052766.60 14.37 01-JAN-08:09 0.00 0.00 01-JAN-00:10
February 21725079.51 14.37 01-FEB-08:09 0.00 0.00 01-FEB-00:10
March 24052766.60 14.37 01-MAR-08:09 0.00 0.00 01-MAR-00:10
April 23276870.90 14.37 01-APR-07:10 0.00 0.00 01-APR-00:10
May 24052766.60 14.37 01-MAY-07:10 0.00 0.00 01-MAY-00:10
June 23276870.90 14.37 01-JUN-07:10 0.00 0.00 01-JUN-00:10
July 24052766.60 14.37 01-JUL-07:10 0.00 0.00 01-JUL-00:10
August 24052766.60 14.37 01-AUG-07:10 0.00 0.00 01-AUG-00:10
September 23276870.90 14.37 01-SEP-07:10 0.00 0.00 01-SEP-00:10
October 24052766.60 14.37 01-OCT-07:10 0.00 0.00 01-OCT-00:10
November 23276870.90 14.37 01-NOV-07:10 0.00 0.00 01-NOV-00:10
December 24052766.60 14.37 01-DEC-08:09 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.283202E+09     0.00    
Minimum of Months 21725079.51 14.37   0.00 0.00  
Maximum of Months 24052766.60 14.37   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM201

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM202_205

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.440447E+09 396.93 01-JAN-19:10 0.142970E+10 1396.30 01-JAN-08:09
February 0.396192E+09 396.93 01-FEB-20:10 0.129035E+10 1396.30 01-FEB-07:10
March 0.435217E+09 396.93 01-MAR-20:10 0.142652E+10 1396.30 01-MAR-07:10
April 0.425057E+09 396.93 01-APR-18:10 0.138290E+10 1396.30 01-APR-07:10
May 0.436961E+09 396.93 01-MAY-19:10 0.142758E+10 1396.30 01-MAY-06:10
June 0.421685E+09 396.93 01-JUN-19:10 0.138077E+10 1396.30 01-JUN-06:10
July 0.440390E+09 396.93 01-JUL-18:10 0.142970E+10 1396.30 01-JUL-07:10
August 0.435217E+09 396.93 01-AUG-19:10 0.142652E+10 1396.30 01-AUG-06:10
September 0.425172E+09 396.93 01-SEP-19:10 0.138290E+10 1396.30 01-SEP-06:10
October 0.438647E+09 396.93 01-OCT-18:10 0.142864E+10 1396.30 01-OCT-07:10
November 0.425115E+09 396.93 01-NOV-19:10 0.138290E+10 1396.30 01-NOV-06:10
December 0.440447E+09 396.93 01-DEC-20:10 0.142970E+10 1396.30 01-DEC-07:10
             
Annual Sum or Average 0.516055E+10     0.168182E+11    
Minimum of Months 0.396192E+09 396.93   0.129035E+10 1396.30  
Maximum of Months 0.440447E+09 396.93   0.142970E+10 1396.30  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM206_208

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.355746E+09 320.60 01-JAN-19:10 0.115476E+10 1127.78 01-JAN-08:09
February 0.320002E+09 320.60 01-FEB-20:10 0.104220E+10 1127.78 01-FEB-07:10
March 0.351522E+09 320.60 01-MAR-20:10 0.115219E+10 1127.78 01-MAR-07:10
April 0.343316E+09 320.60 01-APR-18:10 0.111695E+10 1127.78 01-APR-07:10
May 0.352930E+09 320.60 01-MAY-19:10 0.115304E+10 1127.78 01-MAY-06:10
June 0.340592E+09 320.60 01-JUN-19:10 0.111524E+10 1127.78 01-JUN-06:10
July 0.355700E+09 320.60 01-JUL-18:10 0.115476E+10 1127.78 01-JUL-07:10
August 0.351522E+09 320.60 01-AUG-19:10 0.115219E+10 1127.78 01-AUG-06:10
September 0.343408E+09 320.60 01-SEP-19:10 0.111695E+10 1127.78 01-SEP-06:10
October 0.354292E+09 320.60 01-OCT-18:10 0.115390E+10 1127.78 01-OCT-07:10
November 0.343362E+09 320.60 01-NOV-19:10 0.111695E+10 1127.78 01-NOV-06:10
December 0.355746E+09 320.60 01-DEC-20:10 0.115476E+10 1127.78 01-DEC-07:10
             
Annual Sum or Average 0.416813E+10     0.135839E+11    
Minimum of Months 0.320002E+09 320.60   0.104220E+10 1127.78  
Maximum of Months 0.355746E+09 320.60   0.115476E+10 1127.78  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM209_212

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.440447E+09 396.93 01-JAN-19:10 0.142970E+10 1396.30 01-JAN-08:09
February 0.396192E+09 396.93 01-FEB-20:10 0.129035E+10 1396.30 01-FEB-07:10
March 0.435217E+09 396.93 01-MAR-20:10 0.142652E+10 1396.30 01-MAR-07:10
April 0.425057E+09 396.93 01-APR-18:10 0.138290E+10 1396.30 01-APR-07:10
May 0.436961E+09 396.93 01-MAY-19:10 0.142758E+10 1396.30 01-MAY-06:10
June 0.421685E+09 396.93 01-JUN-19:10 0.138077E+10 1396.30 01-JUN-06:10
July 0.440390E+09 396.93 01-JUL-18:10 0.142970E+10 1396.30 01-JUL-07:10
August 0.435217E+09 396.93 01-AUG-19:10 0.142652E+10 1396.30 01-AUG-06:10
September 0.425172E+09 396.93 01-SEP-19:10 0.138290E+10 1396.30 01-SEP-06:10
October 0.438647E+09 396.93 01-OCT-18:10 0.142864E+10 1396.30 01-OCT-07:10
November 0.425115E+09 396.93 01-NOV-19:10 0.138290E+10 1396.30 01-NOV-06:10
December 0.440447E+09 396.93 01-DEC-20:10 0.142970E+10 1396.30 01-DEC-07:10
             
Annual Sum or Average 0.516055E+10     0.168182E+11    
Minimum of Months 0.396192E+09 396.93   0.129035E+10 1396.30  
Maximum of Months 0.440447E+09 396.93   0.142970E+10 1396.30  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM213

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110112E+09 99.23 01-JAN-19:10 0.357425E+09 349.07 01-JAN-08:09
February 99048113.69 99.23 01-FEB-20:10 0.322587E+09 349.07 01-FEB-07:10
March 0.108804E+09 99.23 01-MAR-20:10 0.356629E+09 349.07 01-MAR-07:10
April 0.106264E+09 99.23 01-APR-18:10 0.345724E+09 349.07 01-APR-07:10
May 0.109240E+09 99.23 01-MAY-19:10 0.356894E+09 349.07 01-MAY-06:10
June 0.105421E+09 99.23 01-JUN-19:10 0.345193E+09 349.07 01-JUN-06:10
July 0.110098E+09 99.23 01-JUL-18:10 0.357425E+09 349.07 01-JUL-07:10
August 0.108804E+09 99.23 01-AUG-19:10 0.356629E+09 349.07 01-AUG-06:10
September 0.106293E+09 99.23 01-SEP-19:10 0.345724E+09 349.07 01-SEP-06:10
October 0.109662E+09 99.23 01-OCT-18:10 0.357159E+09 349.07 01-OCT-07:10
November 0.106279E+09 99.23 01-NOV-19:10 0.345724E+09 349.07 01-NOV-06:10
December 0.110112E+09 99.23 01-DEC-20:10 0.357425E+09 349.07 01-DEC-07:10
             
Annual Sum or Average 0.129014E+10     0.420454E+10    
Minimum of Months 99048113.69 99.23   0.322587E+09 349.07  
Maximum of Months 0.110112E+09 99.23   0.357425E+09 349.07  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM214

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110104E+09 99.23 01-JAN-19:10 0.357399E+09 349.05 01-JAN-08:09
February 99041085.40 99.23 01-FEB-20:10 0.322564E+09 349.05 01-FEB-07:10
March 0.108797E+09 99.23 01-MAR-20:10 0.356604E+09 349.05 01-MAR-07:10
April 0.106257E+09 99.23 01-APR-18:10 0.345699E+09 349.05 01-APR-07:10
May 0.109232E+09 99.23 01-MAY-19:10 0.356869E+09 349.05 01-MAY-06:10
June 0.105414E+09 99.23 01-JUN-19:10 0.345169E+09 349.05 01-JUN-06:10
July 0.110090E+09 99.23 01-JUL-18:10 0.357399E+09 349.05 01-JUL-07:10
August 0.108797E+09 99.23 01-AUG-19:10 0.356604E+09 349.05 01-AUG-06:10
September 0.106285E+09 99.23 01-SEP-19:10 0.345699E+09 349.05 01-SEP-06:10
October 0.109654E+09 99.23 01-OCT-18:10 0.357134E+09 349.05 01-OCT-07:10
November 0.106271E+09 99.23 01-NOV-19:10 0.345699E+09 349.05 01-NOV-06:10
December 0.110104E+09 99.23 01-DEC-20:10 0.357399E+09 349.05 01-DEC-07:10
             
Annual Sum or Average 0.129005E+10     0.420424E+10    
Minimum of Months 99041085.40 99.23   0.322564E+09 349.05  
Maximum of Months 0.110104E+09 99.23   0.357399E+09 349.05  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM215_218

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ELEVATORCOREFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM219

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110104E+09 99.23 01-JAN-19:10 0.357399E+09 349.05 01-JAN-08:09
February 99041085.40 99.23 01-FEB-20:10 0.322564E+09 349.05 01-FEB-07:10
March 0.108797E+09 99.23 01-MAR-20:10 0.356604E+09 349.05 01-MAR-07:10
April 0.106257E+09 99.23 01-APR-18:10 0.345699E+09 349.05 01-APR-07:10
May 0.109232E+09 99.23 01-MAY-19:10 0.356869E+09 349.05 01-MAY-06:10
June 0.105414E+09 99.23 01-JUN-19:10 0.345169E+09 349.05 01-JUN-06:10
July 0.110090E+09 99.23 01-JUL-18:10 0.357399E+09 349.05 01-JUL-07:10
August 0.108797E+09 99.23 01-AUG-19:10 0.356604E+09 349.05 01-AUG-06:10
September 0.106285E+09 99.23 01-SEP-19:10 0.345699E+09 349.05 01-SEP-06:10
October 0.109654E+09 99.23 01-OCT-18:10 0.357134E+09 349.05 01-OCT-07:10
November 0.106271E+09 99.23 01-NOV-19:10 0.345699E+09 349.05 01-NOV-06:10
December 0.110104E+09 99.23 01-DEC-20:10 0.357399E+09 349.05 01-DEC-07:10
             
Annual Sum or Average 0.129005E+10     0.420424E+10    
Minimum of Months 99041085.40 99.23   0.322564E+09 349.05  
Maximum of Months 0.110104E+09 99.23   0.357399E+09 349.05  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM220_223

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.440416E+09 396.90 01-JAN-19:10 0.142960E+10 1396.20 01-JAN-08:09
February 0.396164E+09 396.90 01-FEB-20:10 0.129026E+10 1396.20 01-FEB-07:10
March 0.435186E+09 396.90 01-MAR-20:10 0.142641E+10 1396.20 01-MAR-07:10
April 0.425027E+09 396.90 01-APR-18:10 0.138280E+10 1396.20 01-APR-07:10
May 0.436930E+09 396.90 01-MAY-19:10 0.142748E+10 1396.20 01-MAY-06:10
June 0.421655E+09 396.90 01-JUN-19:10 0.138067E+10 1396.20 01-JUN-06:10
July 0.440359E+09 396.90 01-JUL-18:10 0.142960E+10 1396.20 01-JUL-07:10
August 0.435186E+09 396.90 01-AUG-19:10 0.142641E+10 1396.20 01-AUG-06:10
September 0.425142E+09 396.90 01-SEP-19:10 0.138280E+10 1396.20 01-SEP-06:10
October 0.438616E+09 396.90 01-OCT-18:10 0.142854E+10 1396.20 01-OCT-07:10
November 0.425084E+09 396.90 01-NOV-19:10 0.138280E+10 1396.20 01-NOV-06:10
December 0.440416E+09 396.90 01-DEC-20:10 0.142960E+10 1396.20 01-DEC-07:10
             
Annual Sum or Average 0.516018E+10     0.168170E+11    
Minimum of Months 0.396164E+09 396.90   0.129026E+10 1396.20  
Maximum of Months 0.440416E+09 396.90   0.142960E+10 1396.20  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM224

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110104E+09 99.23 01-JAN-19:10 0.357399E+09 349.05 01-JAN-08:09
February 99041085.40 99.23 01-FEB-20:10 0.322564E+09 349.05 01-FEB-07:10
March 0.108797E+09 99.23 01-MAR-20:10 0.356604E+09 349.05 01-MAR-07:10
April 0.106257E+09 99.23 01-APR-18:10 0.345699E+09 349.05 01-APR-07:10
May 0.109232E+09 99.23 01-MAY-19:10 0.356869E+09 349.05 01-MAY-06:10
June 0.105414E+09 99.23 01-JUN-19:10 0.345169E+09 349.05 01-JUN-06:10
July 0.110090E+09 99.23 01-JUL-18:10 0.357399E+09 349.05 01-JUL-07:10
August 0.108797E+09 99.23 01-AUG-19:10 0.356604E+09 349.05 01-AUG-06:10
September 0.106285E+09 99.23 01-SEP-19:10 0.345699E+09 349.05 01-SEP-06:10
October 0.109654E+09 99.23 01-OCT-18:10 0.357134E+09 349.05 01-OCT-07:10
November 0.106271E+09 99.23 01-NOV-19:10 0.345699E+09 349.05 01-NOV-06:10
December 0.110104E+09 99.23 01-DEC-20:10 0.357399E+09 349.05 01-DEC-07:10
             
Annual Sum or Average 0.129005E+10     0.420424E+10    
Minimum of Months 99041085.40 99.23   0.322564E+09 349.05  
Maximum of Months 0.110104E+09 99.23   0.357399E+09 349.05  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONTSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 15028313.11 8.98 01-JAN-08:09 0.00 0.00 01-JAN-00:10
February 13573960.23 8.98 01-FEB-08:09 0.00 0.00 01-FEB-00:10
March 15028313.11 8.98 01-MAR-08:09 0.00 0.00 01-MAR-00:10
April 14543528.81 8.98 01-APR-07:10 0.00 0.00 01-APR-00:10
May 15028313.11 8.98 01-MAY-07:10 0.00 0.00 01-MAY-00:10
June 14543528.81 8.98 01-JUN-07:10 0.00 0.00 01-JUN-00:10
July 15028313.11 8.98 01-JUL-07:10 0.00 0.00 01-JUL-00:10
August 15028313.11 8.98 01-AUG-07:10 0.00 0.00 01-AUG-00:10
September 14543528.81 8.98 01-SEP-07:10 0.00 0.00 01-SEP-00:10
October 15028313.11 8.98 01-OCT-07:10 0.00 0.00 01-OCT-00:10
November 14543528.81 8.98 01-NOV-07:10 0.00 0.00 01-NOV-00:10
December 15028313.11 8.98 01-DEC-08:09 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.176946E+09     0.00    
Minimum of Months 13573960.23 8.98   0.00 0.00  
Maximum of Months 15028313.11 8.98   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONTSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.283482E+09 105.84 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.256048E+09 105.84 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.283482E+09 105.84 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.274337E+09 105.84 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.283482E+09 105.84 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.274337E+09 105.84 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.283482E+09 105.84 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.283482E+09 105.84 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.274337E+09 105.84 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.283482E+09 105.84 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.274337E+09 105.84 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.283482E+09 105.84 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.333777E+10     0.00    
Minimum of Months 0.256048E+09 105.84   0.00 0.00  
Maximum of Months 0.283482E+09 105.84   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: REARSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.283549E+09 105.87 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.256109E+09 105.87 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.283549E+09 105.87 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.274403E+09 105.87 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.283549E+09 105.87 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.274403E+09 105.87 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.283549E+09 105.87 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.283549E+09 105.87 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.274403E+09 105.87 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.283549E+09 105.87 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.274403E+09 105.87 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.283549E+09 105.87 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.333857E+10     0.00    
Minimum of Months 0.256109E+09 105.87   0.00 0.00  
Maximum of Months 0.283549E+09 105.87   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDORFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.111188E+10 415.13 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.100428E+10 415.13 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.111188E+10 415.13 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.107601E+10 415.13 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.111188E+10 415.13 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.107601E+10 415.13 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.111188E+10 415.13 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.111188E+10 415.13 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.107601E+10 415.13 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.111188E+10 415.13 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.107601E+10 415.13 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.111188E+10 415.13 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.130915E+11     0.00    
Minimum of Months 0.100428E+10 415.13   0.00 0.00  
Maximum of Months 0.111188E+10 415.13   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: REARSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 24052766.60 14.37 01-JAN-08:09 0.00 0.00 01-JAN-00:10
February 21725079.51 14.37 01-FEB-08:09 0.00 0.00 01-FEB-00:10
March 24052766.60 14.37 01-MAR-08:09 0.00 0.00 01-MAR-00:10
April 23276870.90 14.37 01-APR-07:10 0.00 0.00 01-APR-00:10
May 24052766.60 14.37 01-MAY-07:10 0.00 0.00 01-MAY-00:10
June 23276870.90 14.37 01-JUN-07:10 0.00 0.00 01-JUN-00:10
July 24052766.60 14.37 01-JUL-07:10 0.00 0.00 01-JUL-00:10
August 24052766.60 14.37 01-AUG-07:10 0.00 0.00 01-AUG-00:10
September 23276870.90 14.37 01-SEP-07:10 0.00 0.00 01-SEP-00:10
October 24052766.60 14.37 01-OCT-07:10 0.00 0.00 01-OCT-00:10
November 23276870.90 14.37 01-NOV-07:10 0.00 0.00 01-NOV-00:10
December 24052766.60 14.37 01-DEC-08:09 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.283202E+09     0.00    
Minimum of Months 21725079.51 14.37   0.00 0.00  
Maximum of Months 24052766.60 14.37   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM301

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM302_305

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM306_308

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM309_312

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.440447E+09 396.93 01-JAN-19:10 0.142970E+10 1396.30 01-JAN-08:09
February 0.396192E+09 396.93 01-FEB-20:10 0.129035E+10 1396.30 01-FEB-07:10
March 0.435217E+09 396.93 01-MAR-20:10 0.142652E+10 1396.30 01-MAR-07:10
April 0.425057E+09 396.93 01-APR-18:10 0.138290E+10 1396.30 01-APR-07:10
May 0.436961E+09 396.93 01-MAY-19:10 0.142758E+10 1396.30 01-MAY-06:10
June 0.421685E+09 396.93 01-JUN-19:10 0.138077E+10 1396.30 01-JUN-06:10
July 0.440390E+09 396.93 01-JUL-18:10 0.142970E+10 1396.30 01-JUL-07:10
August 0.435217E+09 396.93 01-AUG-19:10 0.142652E+10 1396.30 01-AUG-06:10
September 0.425172E+09 396.93 01-SEP-19:10 0.138290E+10 1396.30 01-SEP-06:10
October 0.438647E+09 396.93 01-OCT-18:10 0.142864E+10 1396.30 01-OCT-07:10
November 0.425115E+09 396.93 01-NOV-19:10 0.138290E+10 1396.30 01-NOV-06:10
December 0.440447E+09 396.93 01-DEC-20:10 0.142970E+10 1396.30 01-DEC-07:10
             
Annual Sum or Average 0.516055E+10     0.168182E+11    
Minimum of Months 0.396192E+09 396.93   0.129035E+10 1396.30  
Maximum of Months 0.440447E+09 396.93   0.142970E+10 1396.30  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM313

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM314

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110104E+09 99.23 01-JAN-19:10 0.357399E+09 349.05 01-JAN-08:09
February 99041085.40 99.23 01-FEB-20:10 0.322564E+09 349.05 01-FEB-07:10
March 0.108797E+09 99.23 01-MAR-20:10 0.356604E+09 349.05 01-MAR-07:10
April 0.106257E+09 99.23 01-APR-18:10 0.345699E+09 349.05 01-APR-07:10
May 0.109232E+09 99.23 01-MAY-19:10 0.356869E+09 349.05 01-MAY-06:10
June 0.105414E+09 99.23 01-JUN-19:10 0.345169E+09 349.05 01-JUN-06:10
July 0.110090E+09 99.23 01-JUL-18:10 0.357399E+09 349.05 01-JUL-07:10
August 0.108797E+09 99.23 01-AUG-19:10 0.356604E+09 349.05 01-AUG-06:10
September 0.106285E+09 99.23 01-SEP-19:10 0.345699E+09 349.05 01-SEP-06:10
October 0.109654E+09 99.23 01-OCT-18:10 0.357134E+09 349.05 01-OCT-07:10
November 0.106271E+09 99.23 01-NOV-19:10 0.345699E+09 349.05 01-NOV-06:10
December 0.110104E+09 99.23 01-DEC-20:10 0.357399E+09 349.05 01-DEC-07:10
             
Annual Sum or Average 0.129005E+10     0.420424E+10    
Minimum of Months 99041085.40 99.23   0.322564E+09 349.05  
Maximum of Months 0.110104E+09 99.23   0.357399E+09 349.05  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM315_318

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.440416E+09 396.90 01-JAN-19:10 0.142960E+10 1396.20 01-JAN-08:09
February 0.396164E+09 396.90 01-FEB-20:10 0.129026E+10 1396.20 01-FEB-07:10
March 0.435186E+09 396.90 01-MAR-20:10 0.142641E+10 1396.20 01-MAR-07:10
April 0.425027E+09 396.90 01-APR-18:10 0.138280E+10 1396.20 01-APR-07:10
May 0.436930E+09 396.90 01-MAY-19:10 0.142748E+10 1396.20 01-MAY-06:10
June 0.421655E+09 396.90 01-JUN-19:10 0.138067E+10 1396.20 01-JUN-06:10
July 0.440359E+09 396.90 01-JUL-18:10 0.142960E+10 1396.20 01-JUL-07:10
August 0.435186E+09 396.90 01-AUG-19:10 0.142641E+10 1396.20 01-AUG-06:10
September 0.425142E+09 396.90 01-SEP-19:10 0.138280E+10 1396.20 01-SEP-06:10
October 0.438616E+09 396.90 01-OCT-18:10 0.142854E+10 1396.20 01-OCT-07:10
November 0.425084E+09 396.90 01-NOV-19:10 0.138280E+10 1396.20 01-NOV-06:10
December 0.440416E+09 396.90 01-DEC-20:10 0.142960E+10 1396.20 01-DEC-07:10
             
Annual Sum or Average 0.516018E+10     0.168170E+11    
Minimum of Months 0.396164E+09 396.90   0.129026E+10 1396.20  
Maximum of Months 0.440416E+09 396.90   0.142960E+10 1396.20  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ELEVATORCOREFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM319

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM320_323

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.440416E+09 396.90 01-JAN-19:10 0.142960E+10 1396.20 01-JAN-08:09
February 0.396164E+09 396.90 01-FEB-20:10 0.129026E+10 1396.20 01-FEB-07:10
March 0.435186E+09 396.90 01-MAR-20:10 0.142641E+10 1396.20 01-MAR-07:10
April 0.425027E+09 396.90 01-APR-18:10 0.138280E+10 1396.20 01-APR-07:10
May 0.436930E+09 396.90 01-MAY-19:10 0.142748E+10 1396.20 01-MAY-06:10
June 0.421655E+09 396.90 01-JUN-19:10 0.138067E+10 1396.20 01-JUN-06:10
July 0.440359E+09 396.90 01-JUL-18:10 0.142960E+10 1396.20 01-JUL-07:10
August 0.435186E+09 396.90 01-AUG-19:10 0.142641E+10 1396.20 01-AUG-06:10
September 0.425142E+09 396.90 01-SEP-19:10 0.138280E+10 1396.20 01-SEP-06:10
October 0.438616E+09 396.90 01-OCT-18:10 0.142854E+10 1396.20 01-OCT-07:10
November 0.425084E+09 396.90 01-NOV-19:10 0.138280E+10 1396.20 01-NOV-06:10
December 0.440416E+09 396.90 01-DEC-20:10 0.142960E+10 1396.20 01-DEC-07:10
             
Annual Sum or Average 0.516018E+10     0.168170E+11    
Minimum of Months 0.396164E+09 396.90   0.129026E+10 1396.20  
Maximum of Months 0.440416E+09 396.90   0.142960E+10 1396.20  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM324

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONTSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 15028313.11 8.98 01-JAN-08:09 0.00 0.00 01-JAN-00:10
February 13573960.23 8.98 01-FEB-08:09 0.00 0.00 01-FEB-00:10
March 15028313.11 8.98 01-MAR-08:09 0.00 0.00 01-MAR-00:10
April 14543528.81 8.98 01-APR-07:10 0.00 0.00 01-APR-00:10
May 15028313.11 8.98 01-MAY-07:10 0.00 0.00 01-MAY-00:10
June 14543528.81 8.98 01-JUN-07:10 0.00 0.00 01-JUN-00:10
July 15028313.11 8.98 01-JUL-07:10 0.00 0.00 01-JUL-00:10
August 15028313.11 8.98 01-AUG-07:10 0.00 0.00 01-AUG-00:10
September 14543528.81 8.98 01-SEP-07:10 0.00 0.00 01-SEP-00:10
October 15028313.11 8.98 01-OCT-07:10 0.00 0.00 01-OCT-00:10
November 14543528.81 8.98 01-NOV-07:10 0.00 0.00 01-NOV-00:10
December 15028313.11 8.98 01-DEC-08:09 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.176946E+09     0.00    
Minimum of Months 13573960.23 8.98   0.00 0.00  
Maximum of Months 15028313.11 8.98   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONTSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.283482E+09 105.84 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.256048E+09 105.84 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.283482E+09 105.84 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.274337E+09 105.84 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.283482E+09 105.84 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.274337E+09 105.84 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.283482E+09 105.84 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.283482E+09 105.84 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.274337E+09 105.84 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.283482E+09 105.84 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.274337E+09 105.84 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.283482E+09 105.84 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.333777E+10     0.00    
Minimum of Months 0.256048E+09 105.84   0.00 0.00  
Maximum of Months 0.283482E+09 105.84   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: REARSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.283549E+09 105.87 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.256109E+09 105.87 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.283549E+09 105.87 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.274403E+09 105.87 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.283549E+09 105.87 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.274403E+09 105.87 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.283549E+09 105.87 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.283549E+09 105.87 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.274403E+09 105.87 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.283549E+09 105.87 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.274403E+09 105.87 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.283549E+09 105.87 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.333857E+10     0.00    
Minimum of Months 0.256109E+09 105.87   0.00 0.00  
Maximum of Months 0.283549E+09 105.87   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDORFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.111188E+10 415.13 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.100428E+10 415.13 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.111188E+10 415.13 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.107601E+10 415.13 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.111188E+10 415.13 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.107601E+10 415.13 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.111188E+10 415.13 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.111188E+10 415.13 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.107601E+10 415.13 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.111188E+10 415.13 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.107601E+10 415.13 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.111188E+10 415.13 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.130915E+11     0.00    
Minimum of Months 0.100428E+10 415.13   0.00 0.00  
Maximum of Months 0.111188E+10 415.13   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: REARSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 24052766.60 14.37 01-JAN-08:09 0.00 0.00 01-JAN-00:10
February 21725079.51 14.37 01-FEB-08:09 0.00 0.00 01-FEB-00:10
March 24052766.60 14.37 01-MAR-08:09 0.00 0.00 01-MAR-00:10
April 23276870.90 14.37 01-APR-07:10 0.00 0.00 01-APR-00:10
May 24052766.60 14.37 01-MAY-07:10 0.00 0.00 01-MAY-00:10
June 23276870.90 14.37 01-JUN-07:10 0.00 0.00 01-JUN-00:10
July 24052766.60 14.37 01-JUL-07:10 0.00 0.00 01-JUL-00:10
August 24052766.60 14.37 01-AUG-07:10 0.00 0.00 01-AUG-00:10
September 23276870.90 14.37 01-SEP-07:10 0.00 0.00 01-SEP-00:10
October 24052766.60 14.37 01-OCT-07:10 0.00 0.00 01-OCT-00:10
November 23276870.90 14.37 01-NOV-07:10 0.00 0.00 01-NOV-00:10
December 24052766.60 14.37 01-DEC-08:09 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.283202E+09     0.00    
Minimum of Months 21725079.51 14.37   0.00 0.00  
Maximum of Months 24052766.60 14.37   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM401

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110112E+09 99.23 01-JAN-19:10 0.357425E+09 349.07 01-JAN-08:09
February 99048113.69 99.23 01-FEB-20:10 0.322587E+09 349.07 01-FEB-07:10
March 0.108804E+09 99.23 01-MAR-20:10 0.356629E+09 349.07 01-MAR-07:10
April 0.106264E+09 99.23 01-APR-18:10 0.345724E+09 349.07 01-APR-07:10
May 0.109240E+09 99.23 01-MAY-19:10 0.356894E+09 349.07 01-MAY-06:10
June 0.105421E+09 99.23 01-JUN-19:10 0.345193E+09 349.07 01-JUN-06:10
July 0.110098E+09 99.23 01-JUL-18:10 0.357425E+09 349.07 01-JUL-07:10
August 0.108804E+09 99.23 01-AUG-19:10 0.356629E+09 349.07 01-AUG-06:10
September 0.106293E+09 99.23 01-SEP-19:10 0.345724E+09 349.07 01-SEP-06:10
October 0.109662E+09 99.23 01-OCT-18:10 0.357159E+09 349.07 01-OCT-07:10
November 0.106279E+09 99.23 01-NOV-19:10 0.345724E+09 349.07 01-NOV-06:10
December 0.110112E+09 99.23 01-DEC-20:10 0.357425E+09 349.07 01-DEC-07:10
             
Annual Sum or Average 0.129014E+10     0.420454E+10    
Minimum of Months 99048113.69 99.23   0.322587E+09 349.07  
Maximum of Months 0.110112E+09 99.23   0.357425E+09 349.07  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM402_405

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM406_408

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM409_412

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.440447E+09 396.93 01-JAN-19:10 0.142970E+10 1396.30 01-JAN-08:09
February 0.396192E+09 396.93 01-FEB-20:10 0.129035E+10 1396.30 01-FEB-07:10
March 0.435217E+09 396.93 01-MAR-20:10 0.142652E+10 1396.30 01-MAR-07:10
April 0.425057E+09 396.93 01-APR-18:10 0.138290E+10 1396.30 01-APR-07:10
May 0.436961E+09 396.93 01-MAY-19:10 0.142758E+10 1396.30 01-MAY-06:10
June 0.421685E+09 396.93 01-JUN-19:10 0.138077E+10 1396.30 01-JUN-06:10
July 0.440390E+09 396.93 01-JUL-18:10 0.142970E+10 1396.30 01-JUL-07:10
August 0.435217E+09 396.93 01-AUG-19:10 0.142652E+10 1396.30 01-AUG-06:10
September 0.425172E+09 396.93 01-SEP-19:10 0.138290E+10 1396.30 01-SEP-06:10
October 0.438647E+09 396.93 01-OCT-18:10 0.142864E+10 1396.30 01-OCT-07:10
November 0.425115E+09 396.93 01-NOV-19:10 0.138290E+10 1396.30 01-NOV-06:10
December 0.440447E+09 396.93 01-DEC-20:10 0.142970E+10 1396.30 01-DEC-07:10
             
Annual Sum or Average 0.516055E+10     0.168182E+11    
Minimum of Months 0.396192E+09 396.93   0.129035E+10 1396.30  
Maximum of Months 0.440447E+09 396.93   0.142970E+10 1396.30  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM413

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM414

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM415_418

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.440416E+09 396.90 01-JAN-19:10 0.142960E+10 1396.20 01-JAN-08:09
February 0.396164E+09 396.90 01-FEB-20:10 0.129026E+10 1396.20 01-FEB-07:10
March 0.435186E+09 396.90 01-MAR-20:10 0.142641E+10 1396.20 01-MAR-07:10
April 0.425027E+09 396.90 01-APR-18:10 0.138280E+10 1396.20 01-APR-07:10
May 0.436930E+09 396.90 01-MAY-19:10 0.142748E+10 1396.20 01-MAY-06:10
June 0.421655E+09 396.90 01-JUN-19:10 0.138067E+10 1396.20 01-JUN-06:10
July 0.440359E+09 396.90 01-JUL-18:10 0.142960E+10 1396.20 01-JUL-07:10
August 0.435186E+09 396.90 01-AUG-19:10 0.142641E+10 1396.20 01-AUG-06:10
September 0.425142E+09 396.90 01-SEP-19:10 0.138280E+10 1396.20 01-SEP-06:10
October 0.438616E+09 396.90 01-OCT-18:10 0.142854E+10 1396.20 01-OCT-07:10
November 0.425084E+09 396.90 01-NOV-19:10 0.138280E+10 1396.20 01-NOV-06:10
December 0.440416E+09 396.90 01-DEC-20:10 0.142960E+10 1396.20 01-DEC-07:10
             
Annual Sum or Average 0.516018E+10     0.168170E+11    
Minimum of Months 0.396164E+09 396.90   0.129026E+10 1396.20  
Maximum of Months 0.440416E+09 396.90   0.142960E+10 1396.20  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ELEVATORCOREFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     0.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM419

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110104E+09 99.23 01-JAN-19:10 0.357399E+09 349.05 01-JAN-08:09
February 99041085.40 99.23 01-FEB-20:10 0.322564E+09 349.05 01-FEB-07:10
March 0.108797E+09 99.23 01-MAR-20:10 0.356604E+09 349.05 01-MAR-07:10
April 0.106257E+09 99.23 01-APR-18:10 0.345699E+09 349.05 01-APR-07:10
May 0.109232E+09 99.23 01-MAY-19:10 0.356869E+09 349.05 01-MAY-06:10
June 0.105414E+09 99.23 01-JUN-19:10 0.345169E+09 349.05 01-JUN-06:10
July 0.110090E+09 99.23 01-JUL-18:10 0.357399E+09 349.05 01-JUL-07:10
August 0.108797E+09 99.23 01-AUG-19:10 0.356604E+09 349.05 01-AUG-06:10
September 0.106285E+09 99.23 01-SEP-19:10 0.345699E+09 349.05 01-SEP-06:10
October 0.109654E+09 99.23 01-OCT-18:10 0.357134E+09 349.05 01-OCT-07:10
November 0.106271E+09 99.23 01-NOV-19:10 0.345699E+09 349.05 01-NOV-06:10
December 0.110104E+09 99.23 01-DEC-20:10 0.357399E+09 349.05 01-DEC-07:10
             
Annual Sum or Average 0.129005E+10     0.420424E+10    
Minimum of Months 99041085.40 99.23   0.322564E+09 349.05  
Maximum of Months 0.110104E+09 99.23   0.357399E+09 349.05  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM420_423

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.440416E+09 396.90 01-JAN-19:10 0.142960E+10 1396.20 01-JAN-08:09
February 0.396164E+09 396.90 01-FEB-20:10 0.129026E+10 1396.20 01-FEB-07:10
March 0.435186E+09 396.90 01-MAR-20:10 0.142641E+10 1396.20 01-MAR-07:10
April 0.425027E+09 396.90 01-APR-18:10 0.138280E+10 1396.20 01-APR-07:10
May 0.436930E+09 396.90 01-MAY-19:10 0.142748E+10 1396.20 01-MAY-06:10
June 0.421655E+09 396.90 01-JUN-19:10 0.138067E+10 1396.20 01-JUN-06:10
July 0.440359E+09 396.90 01-JUL-18:10 0.142960E+10 1396.20 01-JUL-07:10
August 0.435186E+09 396.90 01-AUG-19:10 0.142641E+10 1396.20 01-AUG-06:10
September 0.425142E+09 396.90 01-SEP-19:10 0.138280E+10 1396.20 01-SEP-06:10
October 0.438616E+09 396.90 01-OCT-18:10 0.142854E+10 1396.20 01-OCT-07:10
November 0.425084E+09 396.90 01-NOV-19:10 0.138280E+10 1396.20 01-NOV-06:10
December 0.440416E+09 396.90 01-DEC-20:10 0.142960E+10 1396.20 01-DEC-07:10
             
Annual Sum or Average 0.516018E+10     0.168170E+11    
Minimum of Months 0.396164E+09 396.90   0.129026E+10 1396.20  
Maximum of Months 0.440416E+09 396.90   0.142960E+10 1396.20  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: GUESTROOM424

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.110104E+09 99.23 01-JAN-19:10 0.357399E+09 349.05 01-JAN-08:09
February 99041085.40 99.23 01-FEB-20:10 0.322564E+09 349.05 01-FEB-07:10
March 0.108797E+09 99.23 01-MAR-20:10 0.356604E+09 349.05 01-MAR-07:10
April 0.106257E+09 99.23 01-APR-18:10 0.345699E+09 349.05 01-APR-07:10
May 0.109232E+09 99.23 01-MAY-19:10 0.356869E+09 349.05 01-MAY-06:10
June 0.105414E+09 99.23 01-JUN-19:10 0.345169E+09 349.05 01-JUN-06:10
July 0.110090E+09 99.23 01-JUL-18:10 0.357399E+09 349.05 01-JUL-07:10
August 0.108797E+09 99.23 01-AUG-19:10 0.356604E+09 349.05 01-AUG-06:10
September 0.106285E+09 99.23 01-SEP-19:10 0.345699E+09 349.05 01-SEP-06:10
October 0.109654E+09 99.23 01-OCT-18:10 0.357134E+09 349.05 01-OCT-07:10
November 0.106271E+09 99.23 01-NOV-19:10 0.345699E+09 349.05 01-NOV-06:10
December 0.110104E+09 99.23 01-DEC-20:10 0.357399E+09 349.05 01-DEC-07:10
             
Annual Sum or Average 0.129005E+10     0.420424E+10    
Minimum of Months 99041085.40 99.23   0.322564E+09 349.05  
Maximum of Months 0.110104E+09 99.23   0.357399E+09 349.05  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONTSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 15028313.11 8.98 01-JAN-08:09 0.00 0.00 01-JAN-00:10
February 13573960.23 8.98 01-FEB-08:09 0.00 0.00 01-FEB-00:10
March 15028313.11 8.98 01-MAR-08:09 0.00 0.00 01-MAR-00:10
April 14543528.81 8.98 01-APR-07:10 0.00 0.00 01-APR-00:10
May 15028313.11 8.98 01-MAY-07:10 0.00 0.00 01-MAY-00:10
June 14543528.81 8.98 01-JUN-07:10 0.00 0.00 01-JUN-00:10
July 15028313.11 8.98 01-JUL-07:10 0.00 0.00 01-JUL-00:10
August 15028313.11 8.98 01-AUG-07:10 0.00 0.00 01-AUG-00:10
September 14543528.81 8.98 01-SEP-07:10 0.00 0.00 01-SEP-00:10
October 15028313.11 8.98 01-OCT-07:10 0.00 0.00 01-OCT-00:10
November 14543528.81 8.98 01-NOV-07:10 0.00 0.00 01-NOV-00:10
December 15028313.11 8.98 01-DEC-08:09 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.176946E+09     0.00    
Minimum of Months 13573960.23 8.98   0.00 0.00  
Maximum of Months 15028313.11 8.98   0.00 0.00  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: FRONTSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.283482E+09 105.84 01-JAN-00:10 0.00 0.00 01-JAN-00:10
February 0.256048E+09 105.84 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.283482E+09 105.84 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.274337E+09 105.84 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.283482E+09 105.84 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.274337E+09 105.84 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.283482E+09 105.84 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.283482E+09 105.84 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.274337E+09 105.84 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.283482E+09 105.84 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.274337E+09 105.84 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.283482E+09 105.84 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.333777E+10     0.00    
Minimum of Months 0.256048E+09 105.84   0.00 0.00  
Maximum of Months 0.283482E+09 105.84   0.00 0.00  



Table of Contents

Report: SpaceGainsMonthly

For: REARSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.316594E+09
February 0.00 0.256109E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.242428E+09
March 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.205612E+09
April 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 3007955.41 0.120507E+09
May 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 1334256.84 62443983.01
June 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 6303550.65 35216534.70
July 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 2173663.78 25291872.90
August 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 2311063.05 39147055.58
September 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 1439519.91 68577341.89
October 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.133070E+09
November 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.217434E+09
December 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.277122E+09
                   
Annual Sum or Average 0.00 0.333857E+10 0.00 0.00 0.00 0.00 0.00 16570009.63 0.174344E+10
Minimum of Months 0.00 0.256109E+09 0.00 0.00 0.00 0.00 0.00 0.00 25291872.90
Maximum of Months 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 6303550.65 0.316594E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDORFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.133427E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.186926E+11
February 0.00 0.120515E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.143425E+11
March 0.00 0.133427E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.110293E+11
April 0.00 0.129123E+10 0.00 0.00 0.00 0.00 0.00 87273079.87 0.751339E+10
May 0.00 0.133427E+10 0.00 0.00 0.00 0.00 0.00 81508088.56 0.403327E+10
June 0.00 0.129123E+10 0.00 0.00 0.00 0.00 0.00 0.521409E+09 0.212101E+10
July 0.00 0.133427E+10 0.00 0.00 0.00 0.00 0.00 0.419946E+09 0.129154E+10
August 0.00 0.133427E+10 0.00 0.00 0.00 0.00 0.00 0.426549E+09 0.160308E+10
September 0.00 0.129123E+10 0.00 0.00 0.00 0.00 0.00 0.306401E+09 0.363236E+10
October 0.00 0.133427E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.739649E+10
November 0.00 0.129123E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.112191E+11
December 0.00 0.133427E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.156853E+11
                   
Annual Sum or Average 0.00 0.157099E+11 0.00 0.00 0.00 0.00 0.00 0.184309E+10 0.985599E+11
Minimum of Months 0.00 0.120515E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.129154E+10
Maximum of Months 0.00 0.133427E+10 0.00 0.00 0.00 0.00 0.00 0.521409E+09 0.186926E+11



Table of Contents

Report: SpaceGainsMonthly

For: REARSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 0.00 0.305767E+09
February 0.00 21725079.51 0.00 0.00 0.00 0.00 0.00 0.00 0.231657E+09
March 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 0.00 0.191321E+09
April 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 4179638.88 0.110651E+09
May 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 2335265.63 53941467.12
June 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 8732604.39 29826071.01
July 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 3869792.10 20649221.30
August 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 3984165.65 33642529.03
September 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 2497133.68 62305274.49
October 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 1370.79 0.123751E+09
November 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 0.00 0.207126E+09
December 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 0.00 0.266182E+09
                   
Annual Sum or Average 0.00 0.283202E+09 0.00 0.00 0.00 0.00 0.00 25599971.11 0.163682E+10
Minimum of Months 0.00 21725079.51 0.00 0.00 0.00 0.00 0.00 0.00 20649221.30
Maximum of Months 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 8732604.39 0.305767E+09



Table of Contents

Report: SpaceGainsMonthly

For: FRONTLOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487593E+10 0.123758E+10 0.427743E+10 0.00 0.00 0.00 0.00 0.00 0.257295E+09
February 0.442763E+10 0.102568E+10 0.386349E+10 0.00 0.00 0.00 0.00 0.00 0.198189E+09
March 0.495149E+10 0.100956E+10 0.427743E+10 0.00 0.00 0.00 0.00 0.00 0.174471E+09
April 0.473489E+10 0.927055E+09 0.413945E+10 0.00 0.00 0.00 0.00 1584861.32 0.106826E+09
May 0.492630E+10 0.898021E+09 0.427743E+10 0.00 0.00 0.00 0.00 724301.04 55453548.92
June 0.478526E+10 0.858192E+09 0.413945E+10 0.00 0.00 0.00 0.00 5557404.38 27012774.82
July 0.487593E+10 0.895176E+09 0.427743E+10 0.00 0.00 0.00 0.00 3054401.52 15601430.82
August 0.495149E+10 0.918059E+09 0.427743E+10 0.00 0.00 0.00 0.00 3682729.83 22934194.34
September 0.473489E+10 0.943512E+09 0.413945E+10 0.00 0.00 0.00 0.00 2692144.93 46788858.53
October 0.490112E+10 0.105917E+10 0.427743E+10 0.00 0.00 0.00 0.00 0.00 0.100965E+09
November 0.473489E+10 0.116854E+10 0.413945E+10 0.00 0.00 0.00 0.00 0.00 0.167627E+09
December 0.487593E+10 0.132859E+10 0.427743E+10 0.00 0.00 0.00 0.00 0.00 0.219849E+09
                   
Annual Sum or Average 0.577758E+11 0.122691E+11 0.503633E+11 0.00 0.00 0.00 0.00 17295843.03 0.139301E+10
Minimum of Months 0.442763E+10 0.858192E+09 0.386349E+10 0.00 0.00 0.00 0.00 0.00 15601430.82
Maximum of Months 0.495149E+10 0.132859E+10 0.427743E+10 0.00 0.00 0.00 0.00 5557404.38 0.257295E+09



Table of Contents

Report: SpaceGainsMonthly

For: RESTROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.161458E+09 0.325774E+09 0.00 0.00 0.00 0.00 0.00 0.00 37645085.31
February 0.146613E+09 0.294247E+09 0.00 0.00 0.00 0.00 0.00 0.00 29606067.77
March 0.163960E+09 0.325774E+09 0.00 0.00 0.00 0.00 0.00 0.00 26372387.33
April 0.156787E+09 0.315265E+09 0.00 0.00 0.00 0.00 0.00 223935.42 15944700.73
May 0.163126E+09 0.325774E+09 0.00 0.00 0.00 0.00 0.00 102341.52 7895975.15
June 0.158455E+09 0.315265E+09 0.00 0.00 0.00 0.00 0.00 785256.42 3819817.30
July 0.161458E+09 0.325774E+09 0.00 0.00 0.00 0.00 0.00 431578.44 2204558.38
August 0.163960E+09 0.325774E+09 0.00 0.00 0.00 0.00 0.00 520360.06 3240729.27
September 0.156787E+09 0.315265E+09 0.00 0.00 0.00 0.00 0.00 380398.95 6648614.66
October 0.162292E+09 0.325774E+09 0.00 0.00 0.00 0.00 0.00 0.00 14529840.45
November 0.156787E+09 0.315265E+09 0.00 0.00 0.00 0.00 0.00 0.00 25327125.39
December 0.161458E+09 0.325774E+09 0.00 0.00 0.00 0.00 0.00 0.00 32903452.55
                   
Annual Sum or Average 0.191314E+10 0.383573E+10 0.00 0.00 0.00 0.00 0.00 2443870.82 0.206138E+09
Minimum of Months 0.146613E+09 0.294247E+09 0.00 0.00 0.00 0.00 0.00 0.00 2204558.38
Maximum of Months 0.163960E+09 0.325774E+09 0.00 0.00 0.00 0.00 0.00 785256.42 37645085.31



Table of Contents

Report: SpaceGainsMonthly

For: MEETINGROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.106153E+10 0.834574E+09 0.179790E+09 0.00 0.00 0.00 0.00 0.00 89577118.89
February 0.965488E+09 0.701717E+09 0.162391E+09 0.00 0.00 0.00 0.00 0.00 69089569.17
March 0.108298E+10 0.696928E+09 0.179790E+09 0.00 0.00 0.00 0.00 0.00 59932453.19
April 0.103190E+10 0.652308E+09 0.173991E+09 0.00 0.00 0.00 0.00 551243.90 36053487.77
May 0.107583E+10 0.627783E+09 0.179790E+09 0.00 0.00 0.00 0.00 251927.36 18782630.09
June 0.104620E+10 0.596110E+09 0.173991E+09 0.00 0.00 0.00 0.00 1932965.11 9210434.30
July 0.106153E+10 0.622944E+09 0.179790E+09 0.00 0.00 0.00 0.00 1062376.90 5425006.79
August 0.108298E+10 0.634807E+09 0.179790E+09 0.00 0.00 0.00 0.00 1280919.01 7976529.74
September 0.103190E+10 0.657708E+09 0.173991E+09 0.00 0.00 0.00 0.00 936372.75 15888004.48
October 0.106868E+10 0.732966E+09 0.179790E+09 0.00 0.00 0.00 0.00 0.00 33504138.81
November 0.103190E+10 0.790089E+09 0.173991E+09 0.00 0.00 0.00 0.00 0.00 58095754.94
December 0.106153E+10 0.906116E+09 0.179790E+09 0.00 0.00 0.00 0.00 0.00 76716132.99
                   
Annual Sum or Average 0.126024E+11 0.845405E+10 0.211689E+10 0.00 0.00 0.00 0.00 6015805.03 0.480251E+09
Minimum of Months 0.965488E+09 0.596110E+09 0.162391E+09 0.00 0.00 0.00 0.00 0.00 5425006.79
Maximum of Months 0.108298E+10 0.906116E+09 0.179790E+09 0.00 0.00 0.00 0.00 1932965.11 89577118.89



Table of Contents

Report: SpaceGainsMonthly

For: MECHANICALROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.101070E+09 0.00 0.00 0.00 0.00 0.00 0.00 38591468.49
February 0.00 91288912.54 0.00 0.00 0.00 0.00 0.00 0.00 30422485.98
March 0.00 0.101070E+09 0.00 0.00 0.00 0.00 0.00 0.00 27592682.22
April 0.00 97809549.15 0.00 0.00 0.00 0.00 0.00 54773.95 17572483.87
May 0.00 0.101070E+09 0.00 0.00 0.00 0.00 0.00 12373.34 10078589.36
June 0.00 97809549.15 0.00 0.00 0.00 0.00 0.00 189290.31 5932694.82
July 0.00 0.101070E+09 0.00 0.00 0.00 0.00 0.00 19755.48 4537808.91
August 0.00 0.101070E+09 0.00 0.00 0.00 0.00 0.00 50312.10 6035592.55
September 0.00 97809549.15 0.00 0.00 0.00 0.00 0.00 39768.73 9081098.12
October 0.00 0.101070E+09 0.00 0.00 0.00 0.00 0.00 0.00 16726276.28
November 0.00 97809549.15 0.00 0.00 0.00 0.00 0.00 0.00 26849544.25
December 0.00 0.101070E+09 0.00 0.00 0.00 0.00 0.00 0.00 33875551.15
                   
Annual Sum or Average 0.00 0.119002E+10 0.00 0.00 0.00 0.00 0.00 366273.92 0.227296E+09
Minimum of Months 0.00 91288912.54 0.00 0.00 0.00 0.00 0.00 0.00 4537808.91
Maximum of Months 0.00 0.101070E+09 0.00 0.00 0.00 0.00 0.00 189290.31 38591468.49



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM101

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34486149.34
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26816568.94
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23688494.38
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 173404.72 14649919.43
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 62403.56 7810659.95
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 452294.08 4327421.11
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 136401.71 3072770.73
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 203581.12 4308838.80
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 158646.38 7190552.13
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14041142.45
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23441302.68
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30001662.98
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1186731.56 0.193835E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3072770.73
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 452294.08 34486149.34



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM102

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33877399.12
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26241229.80
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22966475.86
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 209511.41 14040569.60
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85285.00 7306619.33
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 550158.95 3940092.23
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 201433.43 2708289.56
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 276764.99 3878801.16
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 214297.87 6744283.50
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13462633.27
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22784189.27
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29365554.45
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1537451.65 0.187316E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2708289.56
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 550158.95 33877399.12



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM103

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.333455E+09 0.110112E+09 0.357425E+09 0.00 0.00 0.00 0.00 0.00 35821509.12
February 0.301372E+09 99048113.69 0.322587E+09 0.00 0.00 0.00 0.00 0.00 27549895.77
March 0.334054E+09 0.108804E+09 0.356629E+09 0.00 0.00 0.00 0.00 0.00 23531239.05
April 0.322827E+09 0.106264E+09 0.345724E+09 0.00 0.00 0.00 0.00 329485.14 13605125.39
May 0.333854E+09 0.109240E+09 0.356894E+09 0.00 0.00 0.00 0.00 172305.43 6429179.38
June 0.323226E+09 0.105421E+09 0.345193E+09 0.00 0.00 0.00 0.00 1157220.10 2958833.69
July 0.333455E+09 0.110098E+09 0.357425E+09 0.00 0.00 0.00 0.00 780829.38 1719498.19
August 0.334054E+09 0.108804E+09 0.356629E+09 0.00 0.00 0.00 0.00 875267.84 2600262.48
September 0.322827E+09 0.106293E+09 0.345724E+09 0.00 0.00 0.00 0.00 571743.26 5518642.78
October 0.333655E+09 0.109662E+09 0.357159E+09 0.00 0.00 0.00 0.00 454.60 12480178.40
November 0.322827E+09 0.106279E+09 0.345724E+09 0.00 0.00 0.00 0.00 0.00 22820301.62
December 0.333455E+09 0.110112E+09 0.357425E+09 0.00 0.00 0.00 0.00 0.00 30679949.97
                   
Annual Sum or Average 0.392906E+10 0.129014E+10 0.420454E+10 0.00 0.00 0.00 0.00 3887305.75 0.185715E+09
Minimum of Months 0.301372E+09 99048113.69 0.322587E+09 0.00 0.00 0.00 0.00 0.00 1719498.19
Maximum of Months 0.334054E+09 0.110112E+09 0.357425E+09 0.00 0.00 0.00 0.00 1157220.10 35821509.12



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM104

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 36087740.17
February 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 27832555.83
March 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 0.00 23946031.58
April 0.322827E+09 0.106257E+09 0.345699E+09 0.00 0.00 0.00 0.00 327863.04 13816911.36
May 0.333854E+09 0.109232E+09 0.356869E+09 0.00 0.00 0.00 0.00 170453.50 6509922.83
June 0.323226E+09 0.105414E+09 0.345169E+09 0.00 0.00 0.00 0.00 1169677.91 2951970.02
July 0.333455E+09 0.110090E+09 0.357399E+09 0.00 0.00 0.00 0.00 799818.29 1647161.23
August 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 884857.26 2529822.78
September 0.322827E+09 0.106285E+09 0.345699E+09 0.00 0.00 0.00 0.00 575883.19 5512800.10
October 0.333655E+09 0.109654E+09 0.357134E+09 0.00 0.00 0.00 0.00 456.75 12608488.58
November 0.322827E+09 0.106271E+09 0.345699E+09 0.00 0.00 0.00 0.00 0.00 23042341.29
December 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 30960639.56
                   
Annual Sum or Average 0.392906E+10 0.129005E+10 0.420424E+10 0.00 0.00 0.00 0.00 3929009.95 0.187446E+09
Minimum of Months 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 1647161.23
Maximum of Months 0.334054E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 1169677.91 36087740.17



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM105

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 36915738.78
February 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 28521721.28
March 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 0.00 24626270.22
April 0.322827E+09 0.106257E+09 0.345699E+09 0.00 0.00 0.00 0.00 324623.84 14214080.62
May 0.333854E+09 0.109232E+09 0.356869E+09 0.00 0.00 0.00 0.00 169294.90 6719397.57
June 0.323226E+09 0.105414E+09 0.345169E+09 0.00 0.00 0.00 0.00 1167537.54 3068834.73
July 0.333455E+09 0.110090E+09 0.357399E+09 0.00 0.00 0.00 0.00 798581.97 1769283.00
August 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 883236.20 2662517.92
September 0.322827E+09 0.106285E+09 0.345699E+09 0.00 0.00 0.00 0.00 574870.05 5599774.30
October 0.333655E+09 0.109654E+09 0.357134E+09 0.00 0.00 0.00 0.00 453.88 12710026.72
November 0.322827E+09 0.106271E+09 0.345699E+09 0.00 0.00 0.00 0.00 0.00 23437117.50
December 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 31644838.28
                   
Annual Sum or Average 0.392906E+10 0.129005E+10 0.420424E+10 0.00 0.00 0.00 0.00 3918598.38 0.191890E+09
Minimum of Months 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 1769283.00
Maximum of Months 0.334054E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 1167537.54 36915738.78



Table of Contents

Report: SpaceGainsMonthly

For: EMPLOYEELOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.657344E+09 0.278490E+09 0.812993E+09 0.00 0.00 0.00 0.00 0.00 38821006.33
February 0.607733E+09 0.251540E+09 0.734316E+09 0.00 0.00 0.00 0.00 0.00 30454142.75
March 0.702251E+09 0.278490E+09 0.812993E+09 0.00 0.00 0.00 0.00 0.00 26976550.02
April 0.645797E+09 0.269507E+09 0.786767E+09 0.00 0.00 0.00 0.00 223860.71 16019826.15
May 0.687282E+09 0.278490E+09 0.812993E+09 0.00 0.00 0.00 0.00 102306.20 7895779.74
June 0.675734E+09 0.269507E+09 0.786767E+09 0.00 0.00 0.00 0.00 785023.05 3820121.02
July 0.657344E+09 0.278490E+09 0.812993E+09 0.00 0.00 0.00 0.00 431334.70 2204912.27
August 0.702251E+09 0.278490E+09 0.812993E+09 0.00 0.00 0.00 0.00 520140.75 3241144.96
September 0.645797E+09 0.269507E+09 0.786767E+09 0.00 0.00 0.00 0.00 380326.99 6648623.71
October 0.672313E+09 0.278490E+09 0.812993E+09 0.00 0.00 0.00 0.00 0.00 14529314.38
November 0.645797E+09 0.269507E+09 0.786767E+09 0.00 0.00 0.00 0.00 0.00 25581080.40
December 0.657344E+09 0.278490E+09 0.812993E+09 0.00 0.00 0.00 0.00 0.00 33750564.13
                   
Annual Sum or Average 0.795699E+10 0.327900E+10 0.957233E+10 0.00 0.00 0.00 0.00 2442992.40 0.209943E+09
Minimum of Months 0.607733E+09 0.251540E+09 0.734316E+09 0.00 0.00 0.00 0.00 0.00 2204912.27
Maximum of Months 0.702251E+09 0.278490E+09 0.812993E+09 0.00 0.00 0.00 0.00 785023.05 38821006.33



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRYROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.181490E+09 0.395890E+09 0.241866E+10 0.357977E+11 0.00 0.00 0.00 0.00 0.244098E+09
February 0.163926E+09 0.335801E+09 0.218460E+10 0.323334E+11 0.00 0.00 0.00 0.00 0.212067E+09
March 0.181490E+09 0.328583E+09 0.241866E+10 0.357977E+11 0.00 0.00 0.00 0.00 0.227007E+09
April 0.175635E+09 0.319633E+09 0.234064E+10 0.346430E+11 0.00 0.00 0.00 0.00 0.173878E+09
May 0.181490E+09 0.313318E+09 0.241866E+10 0.357977E+11 0.00 0.00 0.00 0.00 0.130625E+09
June 0.175635E+09 0.299531E+09 0.234064E+10 0.346430E+11 0.00 0.00 0.00 0.00 0.105530E+09
July 0.181490E+09 0.311320E+09 0.241866E+10 0.357977E+11 0.00 0.00 0.00 0.00 92018409.20
August 0.181490E+09 0.309981E+09 0.241866E+10 0.357977E+11 0.00 0.00 0.00 0.00 0.110264E+09
September 0.175635E+09 0.315923E+09 0.234064E+10 0.346430E+11 0.00 0.00 0.00 0.00 0.119546E+09
October 0.181490E+09 0.349492E+09 0.241866E+10 0.357977E+11 0.00 0.00 0.00 0.00 0.159330E+09
November 0.175635E+09 0.380499E+09 0.234064E+10 0.346430E+11 0.00 0.00 0.00 0.00 0.202081E+09
December 0.181490E+09 0.439234E+09 0.241866E+10 0.357977E+11 0.00 0.00 0.00 0.00 0.227207E+09
                   
Annual Sum or Average 0.213690E+10 0.409920E+10 0.284778E+11 0.421489E+12 0.00 0.00 0.00 0.00 0.200365E+10
Minimum of Months 0.163926E+09 0.299531E+09 0.218460E+10 0.323334E+11 0.00 0.00 0.00 0.00 92018409.20
Maximum of Months 0.181490E+09 0.439234E+09 0.241866E+10 0.357977E+11 0.00 0.00 0.00 0.00 0.244098E+09



Table of Contents

Report: SpaceGainsMonthly

For: ELEVATORCOREFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.112056E+11 0.00 0.00 0.00 0.00 0.00 0.143575E+09
February 0.00 0.00 0.101212E+11 0.00 0.00 0.00 0.00 0.00 0.123306E+09
March 0.00 0.00 0.112056E+11 0.00 0.00 0.00 0.00 0.00 0.129578E+09
April 0.00 0.00 0.108441E+11 0.00 0.00 0.00 0.00 0.00 99657155.00
May 0.00 0.00 0.112056E+11 0.00 0.00 0.00 0.00 0.00 73286311.94
June 0.00 0.00 0.108441E+11 0.00 0.00 0.00 0.00 0.00 59432030.36
July 0.00 0.00 0.112056E+11 0.00 0.00 0.00 0.00 0.00 51803086.72
August 0.00 0.00 0.112056E+11 0.00 0.00 0.00 0.00 0.00 62352664.50
September 0.00 0.00 0.108441E+11 0.00 0.00 0.00 0.00 0.00 66944291.22
October 0.00 0.00 0.112056E+11 0.00 0.00 0.00 0.00 0.00 90886246.56
November 0.00 0.00 0.108441E+11 0.00 0.00 0.00 0.00 0.00 0.117881E+09
December 0.00 0.00 0.112056E+11 0.00 0.00 0.00 0.00 0.00 0.133547E+09
                   
Annual Sum or Average 0.00 0.00 0.131937E+12 0.00 0.00 0.00 0.00 0.00 0.115225E+10
Minimum of Months 0.00 0.00 0.101212E+11 0.00 0.00 0.00 0.00 0.00 51803086.72
Maximum of Months 0.00 0.00 0.112056E+11 0.00 0.00 0.00 0.00 0.00 0.143575E+09



Table of Contents

Report: SpaceGainsMonthly

For: EXERCISECENTERFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.149522E+10 0.564070E+09 0.710346E+09 0.00 0.00 0.00 0.00 0.00 36349692.34
February 0.135052E+10 0.509483E+09 0.641603E+09 0.00 0.00 0.00 0.00 0.00 27922036.07
March 0.149522E+10 0.564070E+09 0.710346E+09 0.00 0.00 0.00 0.00 0.00 24020648.73
April 0.144698E+10 0.545875E+09 0.687432E+09 0.00 0.00 0.00 0.00 223916.72 14019456.21
May 0.149522E+10 0.564070E+09 0.710346E+09 0.00 0.00 0.00 0.00 102332.95 7123650.86
June 0.144698E+10 0.545875E+09 0.687432E+09 0.00 0.00 0.00 0.00 785186.57 3506311.91
July 0.149522E+10 0.564070E+09 0.710346E+09 0.00 0.00 0.00 0.00 431516.03 2100932.51
August 0.149522E+10 0.564070E+09 0.710346E+09 0.00 0.00 0.00 0.00 520279.65 3041385.97
September 0.144698E+10 0.545875E+09 0.687432E+09 0.00 0.00 0.00 0.00 380367.80 6033414.90
October 0.149522E+10 0.564070E+09 0.710346E+09 0.00 0.00 0.00 0.00 0.00 12731198.96
November 0.144698E+10 0.545875E+09 0.687432E+09 0.00 0.00 0.00 0.00 0.00 23017710.14
December 0.149522E+10 0.564070E+09 0.710346E+09 0.00 0.00 0.00 0.00 0.00 31029586.59
                   
Annual Sum or Average 0.176050E+11 0.664148E+10 0.836375E+10 0.00 0.00 0.00 0.00 2443599.73 0.190896E+09
Minimum of Months 0.135052E+10 0.509483E+09 0.641603E+09 0.00 0.00 0.00 0.00 0.00 2100932.51
Maximum of Months 0.149522E+10 0.564070E+09 0.710346E+09 0.00 0.00 0.00 0.00 785186.57 36349692.34



Table of Contents

Report: SpaceGainsMonthly

For: FRONTOFFICEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.135765E+10 0.103365E+10 0.248187E+10 0.00 0.00 0.00 0.00 0.00 0.145521E+09
February 0.124360E+10 0.906775E+09 0.225598E+10 0.00 0.00 0.00 0.00 0.00 0.112239E+09
March 0.141324E+10 0.947855E+09 0.252769E+10 0.00 0.00 0.00 0.00 0.00 98499285.57
April 0.132581E+10 0.919254E+09 0.241166E+10 0.00 0.00 0.00 0.00 895734.58 59487167.29
May 0.139471E+10 0.902434E+09 0.251242E+10 0.00 0.00 0.00 0.00 409338.67 31032839.37
June 0.136287E+10 0.861051E+09 0.244221E+10 0.00 0.00 0.00 0.00 3140922.29 15196625.65
July 0.135765E+10 0.895760E+09 0.248187E+10 0.00 0.00 0.00 0.00 1726192.25 8818321.72
August 0.141324E+10 0.904315E+09 0.252769E+10 0.00 0.00 0.00 0.00 2081332.80 12962815.60
September 0.132581E+10 0.912281E+09 0.241166E+10 0.00 0.00 0.00 0.00 1521541.26 26270478.55
October 0.137618E+10 0.976383E+09 0.249714E+10 0.00 0.00 0.00 0.00 0.00 56023016.31
November 0.132581E+10 0.997105E+09 0.241166E+10 0.00 0.00 0.00 0.00 0.00 94596166.16
December 0.135765E+10 0.108043E+10 0.248187E+10 0.00 0.00 0.00 0.00 0.00 0.124382E+09
                   
Annual Sum or Average 0.162542E+11 0.113373E+11 0.294437E+11 0.00 0.00 0.00 0.00 9775061.84 0.785028E+09
Minimum of Months 0.124360E+10 0.861051E+09 0.225598E+10 0.00 0.00 0.00 0.00 0.00 8818321.72
Maximum of Months 0.141324E+10 0.108043E+10 0.252769E+10 0.00 0.00 0.00 0.00 3140922.29 0.145521E+09



Table of Contents

Report: SpaceGainsMonthly

For: FRONTSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.284667E+09
February 0.00 0.256048E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.213070E+09
March 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 66307.77 0.179968E+09
April 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 4137273.88 0.107291E+09
May 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 1887754.30 57907175.03
June 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 5832070.46 36614926.19
July 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 1866892.42 27652733.15
August 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 2123604.49 41344739.77
September 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 1753904.24 68058877.02
October 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 32552.62 0.124379E+09
November 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.201781E+09
December 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.249950E+09
                   
Annual Sum or Average 0.00 0.333777E+10 0.00 0.00 0.00 0.00 0.00 17700360.17 0.159268E+10
Minimum of Months 0.00 0.256048E+09 0.00 0.00 0.00 0.00 0.00 0.00 27652733.15
Maximum of Months 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 5832070.46 0.284667E+09



Table of Contents

Report: SpaceGainsMonthly

For: FRONTSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 0.00 48260515.33
February 0.00 13573960.23 0.00 0.00 0.00 0.00 0.00 0.00 36835855.34
March 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 0.00 31992319.29
April 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 421448.57 19372316.44
May 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 174888.14 10472523.17
June 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 835599.52 6044709.06
July 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 293338.82 4232966.33
August 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 369437.12 6117676.93
September 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 305354.51 10495165.71
October 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 459.68 20060041.66
November 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 0.00 33138856.40
December 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 0.00 41944154.56
                   
Annual Sum or Average 0.00 0.176946E+09 0.00 0.00 0.00 0.00 0.00 2400526.36 0.268967E+09
Minimum of Months 0.00 13573960.23 0.00 0.00 0.00 0.00 0.00 0.00 4232966.33
Maximum of Months 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 835599.52 48260515.33



Table of Contents

Report: SpaceGainsMonthly

For: REARSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.324607E+09
February 0.00 0.256109E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.254197E+09
March 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.224477E+09
April 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 1414090.53 0.139994E+09
May 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 447035.92 78311114.15
June 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 3747575.16 44643441.12
July 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 935234.79 32569400.31
August 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 1490520.15 45164133.39
September 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 1042749.93 71811262.09
October 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.134676E+09
November 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.217431E+09
December 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.279621E+09
                   
Annual Sum or Average 0.00 0.333857E+10 0.00 0.00 0.00 0.00 0.00 9077206.47 0.184750E+10
Minimum of Months 0.00 0.256109E+09 0.00 0.00 0.00 0.00 0.00 0.00 32569400.31
Maximum of Months 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 3747575.16 0.324607E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDORFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.253197E+09
February 0.00 0.100428E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.195589E+09
March 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.172305E+09
April 0.00 0.107601E+10 0.00 0.00 0.00 0.00 0.00 1548859.87 0.105101E+09
May 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 706243.30 54550417.08
June 0.00 0.107601E+10 0.00 0.00 0.00 0.00 0.00 5434616.53 26544753.42
July 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 2977371.34 15403671.86
August 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 3592127.77 22625759.33
September 0.00 0.107601E+10 0.00 0.00 0.00 0.00 0.00 2629942.02 45654451.43
October 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 0.00 96997311.25
November 0.00 0.107601E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.164352E+09
December 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.216385E+09
                   
Annual Sum or Average 0.00 0.130915E+11 0.00 0.00 0.00 0.00 0.00 16889160.84 0.136870E+10
Minimum of Months 0.00 0.100428E+10 0.00 0.00 0.00 0.00 0.00 0.00 15403671.86
Maximum of Months 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 5434616.53 0.253197E+09



Table of Contents

Report: SpaceGainsMonthly

For: REARSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 0.00 0.303572E+09
February 0.00 21725079.51 0.00 0.00 0.00 0.00 0.00 0.00 0.234715E+09
March 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 0.00 0.201606E+09
April 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 2293383.86 0.124394E+09
May 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 1116209.78 66220651.46
June 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 5788135.86 36853176.58
July 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 2163328.50 25836481.77
August 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 3065016.41 37321981.03
September 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 2229387.31 62255450.24
October 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 8973.93 0.119212E+09
November 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 0.00 0.198739E+09
December 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 0.00 0.259044E+09
                   
Annual Sum or Average 0.00 0.283202E+09 0.00 0.00 0.00 0.00 0.00 16664435.66 0.166977E+10
Minimum of Months 0.00 21725079.51 0.00 0.00 0.00 0.00 0.00 0.00 25836481.77
Maximum of Months 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 5788135.86 0.303572E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM201

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 98651348.61
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76566340.42
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 67378304.11
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 405127.97 42908896.34
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 125480.06 23997470.08
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1210358.81 13475519.25
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 364256.95 9502630.86
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 618963.43 12837996.46
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 554104.75 20251536.93
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38737038.55
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64584171.33
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83956501.02
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3278291.98 0.552848E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9502630.86
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1210358.81 98651348.61



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM202_205

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.133382E+10 0.440447E+09 0.142970E+10 0.00 0.00 0.00 0.00 0.00 0.148005E+09
February 0.120549E+10 0.396192E+09 0.129035E+10 0.00 0.00 0.00 0.00 0.00 0.114188E+09
March 0.133621E+10 0.435217E+09 0.142652E+10 0.00 0.00 0.00 0.00 0.00 98589930.72
April 0.129131E+10 0.425057E+09 0.138290E+10 0.00 0.00 0.00 0.00 1322663.74 57804008.66
May 0.133542E+10 0.436961E+09 0.142758E+10 0.00 0.00 0.00 0.00 691802.22 27817894.46
June 0.129291E+10 0.421685E+09 0.138077E+10 0.00 0.00 0.00 0.00 4715881.07 12903798.56
July 0.133382E+10 0.440390E+09 0.142970E+10 0.00 0.00 0.00 0.00 3180305.88 7787877.77
August 0.133621E+10 0.435217E+09 0.142652E+10 0.00 0.00 0.00 0.00 3565750.12 11382989.91
September 0.129131E+10 0.425172E+09 0.138290E+10 0.00 0.00 0.00 0.00 2334508.44 23136471.29
October 0.133462E+10 0.438647E+09 0.142864E+10 0.00 0.00 0.00 0.00 1844.80 51817750.97
November 0.129131E+10 0.425115E+09 0.138290E+10 0.00 0.00 0.00 0.00 0.00 94216938.19
December 0.133382E+10 0.440447E+09 0.142970E+10 0.00 0.00 0.00 0.00 0.00 0.126597E+09
                   
Annual Sum or Average 0.157162E+11 0.516055E+10 0.168182E+11 0.00 0.00 0.00 0.00 15812756.27 0.774247E+09
Minimum of Months 0.120549E+10 0.396192E+09 0.129035E+10 0.00 0.00 0.00 0.00 0.00 7787877.77
Maximum of Months 0.133621E+10 0.440447E+09 0.142970E+10 0.00 0.00 0.00 0.00 4715881.07 0.148005E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM206_208

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.100036E+10 0.355746E+09 0.115476E+10 0.00 0.00 0.00 0.00 0.00 0.119920E+09
February 0.904116E+09 0.320002E+09 0.104220E+10 0.00 0.00 0.00 0.00 0.00 92637689.38
March 0.100216E+10 0.351522E+09 0.115219E+10 0.00 0.00 0.00 0.00 0.00 80087845.84
April 0.968481E+09 0.343316E+09 0.111695E+10 0.00 0.00 0.00 0.00 1068468.84 46864834.32
May 0.100156E+10 0.352930E+09 0.115304E+10 0.00 0.00 0.00 0.00 558889.41 22482703.35
June 0.969679E+09 0.340592E+09 0.111524E+10 0.00 0.00 0.00 0.00 3810441.54 10400645.53
July 0.100036E+10 0.355700E+09 0.115476E+10 0.00 0.00 0.00 0.00 2570413.29 6252389.15
August 0.100216E+10 0.351522E+09 0.115219E+10 0.00 0.00 0.00 0.00 2881924.42 9152969.14
September 0.968481E+09 0.343408E+09 0.111695E+10 0.00 0.00 0.00 0.00 1886604.96 18682555.12
October 0.100096E+10 0.354292E+09 0.115390E+10 0.00 0.00 0.00 0.00 1482.88 41926641.01
November 0.968481E+09 0.343362E+09 0.111695E+10 0.00 0.00 0.00 0.00 0.00 76388782.25
December 0.100036E+10 0.355746E+09 0.115476E+10 0.00 0.00 0.00 0.00 0.00 0.102651E+09
                   
Annual Sum or Average 0.117872E+11 0.416813E+10 0.135839E+11 0.00 0.00 0.00 0.00 12778225.33 0.627448E+09
Minimum of Months 0.904116E+09 0.320002E+09 0.104220E+10 0.00 0.00 0.00 0.00 0.00 6252389.15
Maximum of Months 0.100216E+10 0.355746E+09 0.115476E+10 0.00 0.00 0.00 0.00 3810441.54 0.119920E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM209_212

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.133382E+10 0.440447E+09 0.142970E+10 0.00 0.00 0.00 0.00 0.00 0.148884E+09
February 0.120549E+10 0.396192E+09 0.129035E+10 0.00 0.00 0.00 0.00 0.00 0.114996E+09
March 0.133621E+10 0.435217E+09 0.142652E+10 0.00 0.00 0.00 0.00 0.00 99327118.32
April 0.129131E+10 0.425057E+09 0.138290E+10 0.00 0.00 0.00 0.00 1325187.10 57943730.76
May 0.133542E+10 0.436961E+09 0.142758E+10 0.00 0.00 0.00 0.00 692678.76 27683732.54
June 0.129291E+10 0.421685E+09 0.138077E+10 0.00 0.00 0.00 0.00 4719439.81 12752010.09
July 0.133382E+10 0.440390E+09 0.142970E+10 0.00 0.00 0.00 0.00 3182529.58 7599526.79
August 0.133621E+10 0.435217E+09 0.142652E+10 0.00 0.00 0.00 0.00 3570280.53 11189495.45
September 0.129131E+10 0.425172E+09 0.138290E+10 0.00 0.00 0.00 0.00 2337423.78 23063671.25
October 0.133462E+10 0.438647E+09 0.142864E+10 0.00 0.00 0.00 0.00 1825.00 51945252.35
November 0.129131E+10 0.425115E+09 0.138290E+10 0.00 0.00 0.00 0.00 0.00 94857522.90
December 0.133382E+10 0.440447E+09 0.142970E+10 0.00 0.00 0.00 0.00 0.00 0.127516E+09
                   
Annual Sum or Average 0.157162E+11 0.516055E+10 0.168182E+11 0.00 0.00 0.00 0.00 15829364.57 0.777758E+09
Minimum of Months 0.120549E+10 0.396192E+09 0.129035E+10 0.00 0.00 0.00 0.00 0.00 7599526.79
Maximum of Months 0.133621E+10 0.440447E+09 0.142970E+10 0.00 0.00 0.00 0.00 4719439.81 0.148884E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM213

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.333455E+09 0.110112E+09 0.357425E+09 0.00 0.00 0.00 0.00 0.00 36770790.61
February 0.301372E+09 99048113.69 0.322587E+09 0.00 0.00 0.00 0.00 0.00 28292077.34
March 0.334054E+09 0.108804E+09 0.356629E+09 0.00 0.00 0.00 0.00 0.00 24246634.43
April 0.322827E+09 0.106264E+09 0.345724E+09 0.00 0.00 0.00 0.00 332258.11 14132421.32
May 0.333854E+09 0.109240E+09 0.356894E+09 0.00 0.00 0.00 0.00 173543.77 6774727.66
June 0.323226E+09 0.105421E+09 0.345193E+09 0.00 0.00 0.00 0.00 1180406.56 3133711.63
July 0.333455E+09 0.110098E+09 0.357425E+09 0.00 0.00 0.00 0.00 796033.55 1853319.87
August 0.334054E+09 0.108804E+09 0.356629E+09 0.00 0.00 0.00 0.00 893220.08 2745852.20
September 0.322827E+09 0.106293E+09 0.345724E+09 0.00 0.00 0.00 0.00 584670.63 5679226.09
October 0.333655E+09 0.109662E+09 0.357159E+09 0.00 0.00 0.00 0.00 465.46 12724310.17
November 0.322827E+09 0.106279E+09 0.345724E+09 0.00 0.00 0.00 0.00 0.00 23289872.09
December 0.333455E+09 0.110112E+09 0.357425E+09 0.00 0.00 0.00 0.00 0.00 31415918.38
                   
Annual Sum or Average 0.392906E+10 0.129014E+10 0.420454E+10 0.00 0.00 0.00 0.00 3960598.18 0.191059E+09
Minimum of Months 0.301372E+09 99048113.69 0.322587E+09 0.00 0.00 0.00 0.00 0.00 1853319.87
Maximum of Months 0.334054E+09 0.110112E+09 0.357425E+09 0.00 0.00 0.00 0.00 1180406.56 36770790.61



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM214

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 37264540.33
February 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 28838119.23
March 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 0.00 24977065.20
April 0.322827E+09 0.106257E+09 0.345699E+09 0.00 0.00 0.00 0.00 331940.64 14497670.76
May 0.333854E+09 0.109232E+09 0.356869E+09 0.00 0.00 0.00 0.00 172895.13 6876970.84
June 0.323226E+09 0.105414E+09 0.345169E+09 0.00 0.00 0.00 0.00 1193745.09 3152884.58
July 0.333455E+09 0.110090E+09 0.357399E+09 0.00 0.00 0.00 0.00 814692.05 1817497.78
August 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 901851.77 2728503.68
September 0.322827E+09 0.106285E+09 0.345699E+09 0.00 0.00 0.00 0.00 587582.57 5744143.31
October 0.333655E+09 0.109654E+09 0.357134E+09 0.00 0.00 0.00 0.00 462.85 13031976.29
November 0.322827E+09 0.106271E+09 0.345699E+09 0.00 0.00 0.00 0.00 0.00 23774327.07
December 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 31943300.11
                   
Annual Sum or Average 0.392906E+10 0.129005E+10 0.420424E+10 0.00 0.00 0.00 0.00 4003170.09 0.194647E+09
Minimum of Months 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 1817497.78
Maximum of Months 0.334054E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 1193745.09 37264540.33



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM215_218

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.174093E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.137697E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.124548E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 291390.33 76972216.24
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96817.18 41699280.94
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1373362.28 22464069.58
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370094.22 15361727.35
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 581118.25 20850113.80
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 456892.77 35146245.93
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70309463.68
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.117392E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.151964E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3169675.04 0.988498E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15361727.35
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1373362.28 0.174093E+09



Table of Contents

Report: SpaceGainsMonthly

For: ELEVATORCOREFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 84613151.43
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 68486841.56
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64649100.07
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43609426.52
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27584034.21
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 461.62 18073567.72
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14764369.87
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2692.15 18506215.48
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24060114.23
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 39952674.78
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 60346728.70
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74697724.13
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3153.78 0.539344E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14764369.87
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2692.15 84613151.43



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM219

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 38698257.26
February 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 30225583.33
March 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 0.00 25520864.92
April 0.322827E+09 0.106257E+09 0.345699E+09 0.00 0.00 0.00 0.00 330772.84 14901756.70
May 0.333854E+09 0.109232E+09 0.356869E+09 0.00 0.00 0.00 0.00 172472.68 7361260.08
June 0.323226E+09 0.105414E+09 0.345169E+09 0.00 0.00 0.00 0.00 1193465.83 3492495.49
July 0.333455E+09 0.110090E+09 0.357399E+09 0.00 0.00 0.00 0.00 814461.28 2259059.68
August 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 900795.33 3258307.43
September 0.322827E+09 0.106285E+09 0.345699E+09 0.00 0.00 0.00 0.00 586185.40 6051411.92
October 0.333655E+09 0.109654E+09 0.357134E+09 0.00 0.00 0.00 0.00 459.82 13197463.45
November 0.322827E+09 0.106271E+09 0.345699E+09 0.00 0.00 0.00 0.00 0.00 24191816.83
December 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 32658970.35
                   
Annual Sum or Average 0.392906E+10 0.129005E+10 0.420424E+10 0.00 0.00 0.00 0.00 3998613.16 0.201817E+09
Minimum of Months 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 2259059.68
Maximum of Months 0.334054E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 1193465.83 38698257.26



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM220_223

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.133382E+10 0.440416E+09 0.142960E+10 0.00 0.00 0.00 0.00 0.00 0.149362E+09
February 0.120549E+10 0.396164E+09 0.129026E+10 0.00 0.00 0.00 0.00 0.00 0.115475E+09
March 0.133621E+10 0.435186E+09 0.142641E+10 0.00 0.00 0.00 0.00 0.00 99964427.43
April 0.129131E+10 0.425027E+09 0.138280E+10 0.00 0.00 0.00 0.00 1330892.52 57911558.37
May 0.133542E+10 0.436930E+09 0.142748E+10 0.00 0.00 0.00 0.00 693023.04 27380062.69
June 0.129291E+10 0.421655E+09 0.138067E+10 0.00 0.00 0.00 0.00 4780254.39 12487553.33
July 0.133382E+10 0.440359E+09 0.142960E+10 0.00 0.00 0.00 0.00 3264397.77 7110945.56
August 0.133621E+10 0.435186E+09 0.142641E+10 0.00 0.00 0.00 0.00 3615825.83 10698514.79
September 0.129131E+10 0.425142E+09 0.138280E+10 0.00 0.00 0.00 0.00 2356546.21 22834842.57
October 0.133462E+10 0.438616E+09 0.142854E+10 0.00 0.00 0.00 0.00 1888.34 52015631.69
November 0.129131E+10 0.425084E+09 0.138280E+10 0.00 0.00 0.00 0.00 0.00 95082751.13
December 0.133382E+10 0.440416E+09 0.142960E+10 0.00 0.00 0.00 0.00 0.00 0.127898E+09
                   
Annual Sum or Average 0.157162E+11 0.516018E+10 0.168170E+11 0.00 0.00 0.00 0.00 16042828.10 0.778222E+09
Minimum of Months 0.120549E+10 0.396164E+09 0.129026E+10 0.00 0.00 0.00 0.00 0.00 7110945.56
Maximum of Months 0.133621E+10 0.440416E+09 0.142960E+10 0.00 0.00 0.00 0.00 4780254.39 0.149362E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM224

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 36958779.70
February 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 28514933.08
March 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 0.00 24629039.62
April 0.322827E+09 0.106257E+09 0.345699E+09 0.00 0.00 0.00 0.00 332832.29 14317397.45
May 0.333854E+09 0.109232E+09 0.356869E+09 0.00 0.00 0.00 0.00 173270.83 6806212.89
June 0.323226E+09 0.105414E+09 0.345169E+09 0.00 0.00 0.00 0.00 1194596.14 3118791.66
July 0.333455E+09 0.110090E+09 0.357399E+09 0.00 0.00 0.00 0.00 815577.71 1777012.64
August 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 903139.82 2672195.81
September 0.322827E+09 0.106285E+09 0.345699E+09 0.00 0.00 0.00 0.00 588583.62 5697535.67
October 0.333655E+09 0.109654E+09 0.357134E+09 0.00 0.00 0.00 0.00 480.23 12925052.03
November 0.322827E+09 0.106271E+09 0.345699E+09 0.00 0.00 0.00 0.00 0.00 23526086.55
December 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 31618660.48
                   
Annual Sum or Average 0.392906E+10 0.129005E+10 0.420424E+10 0.00 0.00 0.00 0.00 4008480.64 0.192562E+09
Minimum of Months 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 1777012.64
Maximum of Months 0.334054E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 1194596.14 36958779.70



Table of Contents

Report: SpaceGainsMonthly

For: FRONTSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 0.00 48096436.04
February 0.00 13573960.23 0.00 0.00 0.00 0.00 0.00 0.00 37107509.82
March 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 0.00 32686251.51
April 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 351233.42 20234376.54
May 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 140995.38 11119971.80
June 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 766858.79 6344836.06
July 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 280477.67 4392342.44
August 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 410872.16 6058633.50
September 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 371208.46 10052165.81
October 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 4126.03 19131091.40
November 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 0.00 32121705.28
December 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 0.00 41266073.45
                   
Annual Sum or Average 0.00 0.176946E+09 0.00 0.00 0.00 0.00 0.00 2325771.92 0.268611E+09
Minimum of Months 0.00 13573960.23 0.00 0.00 0.00 0.00 0.00 0.00 4392342.44
Maximum of Months 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 766858.79 48096436.04



Table of Contents

Report: SpaceGainsMonthly

For: FRONTSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.284679E+09
February 0.00 0.256048E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.219159E+09
March 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.193292E+09
April 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 2222134.39 0.123108E+09
May 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 845223.94 71950466.17
June 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 3451497.57 45400591.84
July 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 894173.96 34162047.20
August 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 1544572.12 45509118.27
September 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 1686022.25 67962514.68
October 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 70127.58 0.120093E+09
November 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.194655E+09
December 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.244570E+09
                   
Annual Sum or Average 0.00 0.333777E+10 0.00 0.00 0.00 0.00 0.00 10713751.81 0.164454E+10
Minimum of Months 0.00 0.256048E+09 0.00 0.00 0.00 0.00 0.00 0.00 34162047.20
Maximum of Months 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 3451497.57 0.284679E+09



Table of Contents

Report: SpaceGainsMonthly

For: REARSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.342913E+09
February 0.00 0.256109E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.269474E+09
March 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.239092E+09
April 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 1293189.54 0.151968E+09
May 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 336188.13 87407075.01
June 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 3443533.31 50867013.39
July 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 819847.41 37776633.07
August 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 1463373.29 50690427.15
September 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 1122335.60 76700580.46
October 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.139898E+09
November 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.225759E+09
December 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.292735E+09
                   
Annual Sum or Average 0.00 0.333857E+10 0.00 0.00 0.00 0.00 0.00 8478467.28 0.196528E+10
Minimum of Months 0.00 0.256109E+09 0.00 0.00 0.00 0.00 0.00 0.00 37776633.07
Maximum of Months 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 3443533.31 0.342913E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDORFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.280020E+09
February 0.00 0.100428E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.215130E+09
March 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.184038E+09
April 0.00 0.107601E+10 0.00 0.00 0.00 0.00 0.00 1704181.96 0.108606E+09
May 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 775486.22 56517260.33
June 0.00 0.107601E+10 0.00 0.00 0.00 0.00 0.00 5931611.04 27980746.31
July 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 3240092.83 17072557.09
August 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 3904987.75 24991491.40
September 0.00 0.107601E+10 0.00 0.00 0.00 0.00 0.00 2892566.47 46656462.69
October 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 0.00 95772430.32
November 0.00 0.107601E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.176316E+09
December 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.239075E+09
                   
Annual Sum or Average 0.00 0.130915E+11 0.00 0.00 0.00 0.00 0.00 18448926.27 0.147218E+10
Minimum of Months 0.00 0.100428E+10 0.00 0.00 0.00 0.00 0.00 0.00 17072557.09
Maximum of Months 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 5931611.04 0.280020E+09



Table of Contents

Report: SpaceGainsMonthly

For: REARSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 0.00 0.310140E+09
February 0.00 21725079.51 0.00 0.00 0.00 0.00 0.00 0.00 0.240835E+09
March 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 0.00 0.208387E+09
April 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 2141359.97 0.133205E+09
May 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 971916.88 74244374.10
June 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 5015385.20 43595331.77
July 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 1622840.97 31971253.30
August 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 2814149.00 43848518.43
September 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 2252907.24 66427124.15
October 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 65260.97 0.120484E+09
November 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 0.00 0.199557E+09
December 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 0.00 0.261564E+09
                   
Annual Sum or Average 0.00 0.283202E+09 0.00 0.00 0.00 0.00 0.00 14883820.23 0.173426E+10
Minimum of Months 0.00 21725079.51 0.00 0.00 0.00 0.00 0.00 0.00 31971253.30
Maximum of Months 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 5015385.20 0.310140E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM301

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.106704E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 80908801.68
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 69465060.79
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 518787.91 44251174.73
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 180561.21 24873893.12
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1413434.24 14141012.41
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 453935.67 10049807.31
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 809676.66 13474408.68
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 759046.48 20515328.66
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19150.32 38387596.47
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 66477900.12
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 88765298.58
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4154592.50 0.578014E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10049807.31
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1413434.24 0.106704E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM302_305

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.142413E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.110214E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96780743.62
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 597806.28 61948097.02
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 184829.26 34557841.40
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1784018.49 19521660.32
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 539654.76 13955199.57
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 950892.65 18739289.38
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 859424.41 28534617.33
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10324.21 53597016.92
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 91421180.11
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.120498E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4926950.06 0.792181E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13955199.57
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1784018.49 0.142413E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM306_308

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.116749E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 90726487.13
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 80120835.74
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 454494.69 51104154.28
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134795.22 28257494.75
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1453462.32 15703006.66
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 442510.90 11145306.34
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 774354.30 15035808.26
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 677472.18 23202573.61
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2269.85 44146174.59
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 75312893.38
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 99069007.78
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3939359.46 0.650572E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11145306.34
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1453462.32 0.116749E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM309_312

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.133382E+10 0.440447E+09 0.142970E+10 0.00 0.00 0.00 0.00 0.00 0.163994E+09
February 0.120549E+10 0.396192E+09 0.129035E+10 0.00 0.00 0.00 0.00 0.00 0.126527E+09
March 0.133621E+10 0.435217E+09 0.142652E+10 0.00 0.00 0.00 0.00 0.00 0.109115E+09
April 0.129131E+10 0.425057E+09 0.138290E+10 0.00 0.00 0.00 0.00 1459972.53 63707339.06
May 0.133542E+10 0.436961E+09 0.142758E+10 0.00 0.00 0.00 0.00 762053.76 30550428.77
June 0.129291E+10 0.421685E+09 0.138077E+10 0.00 0.00 0.00 0.00 5199704.85 14045592.49
July 0.133382E+10 0.440390E+09 0.142970E+10 0.00 0.00 0.00 0.00 3501133.51 8322283.64
August 0.133621E+10 0.435217E+09 0.142652E+10 0.00 0.00 0.00 0.00 3933056.09 12273483.35
September 0.129131E+10 0.425172E+09 0.138290E+10 0.00 0.00 0.00 0.00 2577763.40 25304282.63
October 0.133462E+10 0.438647E+09 0.142864E+10 0.00 0.00 0.00 0.00 1993.71 56866508.27
November 0.129131E+10 0.425115E+09 0.138290E+10 0.00 0.00 0.00 0.00 0.00 0.104059E+09
December 0.133382E+10 0.440447E+09 0.142970E+10 0.00 0.00 0.00 0.00 0.00 0.140235E+09
                   
Annual Sum or Average 0.157162E+11 0.516055E+10 0.168182E+11 0.00 0.00 0.00 0.00 17435677.84 0.855001E+09
Minimum of Months 0.120549E+10 0.396192E+09 0.129035E+10 0.00 0.00 0.00 0.00 0.00 8322283.64
Maximum of Months 0.133621E+10 0.440447E+09 0.142970E+10 0.00 0.00 0.00 0.00 5199704.85 0.163994E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM313

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35275139.60
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27234172.17
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23610199.03
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 197075.41 14770732.74
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 78462.24 7973752.98
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 538797.66 4392525.85
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 197219.46 3060390.61
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 324029.54 4218963.64
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271443.26 6769811.79
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3956.82 13041953.79
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22481742.51
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29893884.93
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1610984.39 0.192723E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3060390.61
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 538797.66 35275139.60



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM314

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 40765811.80
February 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 31451720.56
March 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 0.00 27133066.11
April 0.322827E+09 0.106257E+09 0.345699E+09 0.00 0.00 0.00 0.00 365746.43 15795096.78
May 0.333854E+09 0.109232E+09 0.356869E+09 0.00 0.00 0.00 0.00 190203.92 7554174.25
June 0.323226E+09 0.105414E+09 0.345169E+09 0.00 0.00 0.00 0.00 1314540.47 3464105.86
July 0.333455E+09 0.110090E+09 0.357399E+09 0.00 0.00 0.00 0.00 895426.20 1987700.40
August 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 992214.41 2983118.95
September 0.322827E+09 0.106285E+09 0.345699E+09 0.00 0.00 0.00 0.00 647126.43 6287074.60
October 0.333655E+09 0.109654E+09 0.357134E+09 0.00 0.00 0.00 0.00 512.13 14173825.31
November 0.322827E+09 0.106271E+09 0.345699E+09 0.00 0.00 0.00 0.00 0.00 25843424.41
December 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 34842674.45
                   
Annual Sum or Average 0.392906E+10 0.129005E+10 0.420424E+10 0.00 0.00 0.00 0.00 4405769.99 0.212282E+09
Minimum of Months 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 1987700.40
Maximum of Months 0.334054E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 1314540.47 40765811.80



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM315_318

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.133382E+10 0.440416E+09 0.142960E+10 0.00 0.00 0.00 0.00 0.00 0.166774E+09
February 0.120549E+10 0.396164E+09 0.129026E+10 0.00 0.00 0.00 0.00 0.00 0.129216E+09
March 0.133621E+10 0.435186E+09 0.142641E+10 0.00 0.00 0.00 0.00 0.00 0.111866E+09
April 0.129131E+10 0.425027E+09 0.138280E+10 0.00 0.00 0.00 0.00 1461202.64 64780706.29
May 0.133542E+10 0.436930E+09 0.142748E+10 0.00 0.00 0.00 0.00 760479.13 30791339.65
June 0.129291E+10 0.421655E+09 0.138067E+10 0.00 0.00 0.00 0.00 5259732.23 14142763.39
July 0.133382E+10 0.440359E+09 0.142960E+10 0.00 0.00 0.00 0.00 3583617.41 8248061.63
August 0.133621E+10 0.435186E+09 0.142641E+10 0.00 0.00 0.00 0.00 3969367.67 12294339.22
September 0.129131E+10 0.425142E+09 0.138280E+10 0.00 0.00 0.00 0.00 2588078.55 25567018.78
October 0.133462E+10 0.438616E+09 0.142854E+10 0.00 0.00 0.00 0.00 2014.41 57860996.38
November 0.129131E+10 0.425084E+09 0.138280E+10 0.00 0.00 0.00 0.00 0.00 0.106210E+09
December 0.133382E+10 0.440416E+09 0.142960E+10 0.00 0.00 0.00 0.00 0.00 0.142962E+09
                   
Annual Sum or Average 0.157162E+11 0.516018E+10 0.168170E+11 0.00 0.00 0.00 0.00 17624492.05 0.870713E+09
Minimum of Months 0.120549E+10 0.396164E+09 0.129026E+10 0.00 0.00 0.00 0.00 0.00 8248061.63
Maximum of Months 0.133621E+10 0.440416E+09 0.142960E+10 0.00 0.00 0.00 0.00 5259732.23 0.166774E+09



Table of Contents

Report: SpaceGainsMonthly

For: ELEVATORCOREFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76069559.68
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 59908966.61
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53735766.17
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 171877.30 33766045.50
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42331.40 19262098.27
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 603363.03 10854189.75
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 138200.59 7846732.88
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 253524.46 10420312.67
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 223053.75 16141187.69
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30369073.91
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50536201.68
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 65588890.69
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1432350.54 0.434499E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7846732.88
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 603363.03 76069559.68



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM319

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41557124.97
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32845344.22
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29525134.89
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 91708.87 18418678.70
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27681.24 10402004.42
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 378997.39 5697503.90
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 102077.43 4056829.31
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 161660.83 5447358.70
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 130210.76 8633462.94
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16525655.22
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27562434.99
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35802730.45
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 892336.53 0.236474E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4056829.31
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 378997.39 41557124.97



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM320_323

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.133382E+10 0.440416E+09 0.142960E+10 0.00 0.00 0.00 0.00 0.00 0.164606E+09
February 0.120549E+10 0.396164E+09 0.129026E+10 0.00 0.00 0.00 0.00 0.00 0.127161E+09
March 0.133621E+10 0.435186E+09 0.142641E+10 0.00 0.00 0.00 0.00 0.00 0.110035E+09
April 0.129131E+10 0.425027E+09 0.138280E+10 0.00 0.00 0.00 0.00 1466105.29 63771719.48
May 0.133542E+10 0.436930E+09 0.142748E+10 0.00 0.00 0.00 0.00 762249.54 30209938.59
June 0.129291E+10 0.421655E+09 0.138067E+10 0.00 0.00 0.00 0.00 5264677.11 13756436.95
July 0.133382E+10 0.440359E+09 0.142960E+10 0.00 0.00 0.00 0.00 3588918.34 7790520.92
August 0.133621E+10 0.435186E+09 0.142641E+10 0.00 0.00 0.00 0.00 3979485.15 11731601.58
September 0.129131E+10 0.425142E+09 0.138280E+10 0.00 0.00 0.00 0.00 2596258.20 25134163.95
October 0.133462E+10 0.438616E+09 0.142854E+10 0.00 0.00 0.00 0.00 2078.12 57200781.29
November 0.129131E+10 0.425084E+09 0.138280E+10 0.00 0.00 0.00 0.00 0.00 0.104508E+09
December 0.133382E+10 0.440416E+09 0.142960E+10 0.00 0.00 0.00 0.00 0.00 0.140792E+09
                   
Annual Sum or Average 0.157162E+11 0.516018E+10 0.168170E+11 0.00 0.00 0.00 0.00 17659771.74 0.856698E+09
Minimum of Months 0.120549E+10 0.396164E+09 0.129026E+10 0.00 0.00 0.00 0.00 0.00 7790520.92
Maximum of Months 0.133621E+10 0.440416E+09 0.142960E+10 0.00 0.00 0.00 0.00 5264677.11 0.164606E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM324

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36904791.24
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28638440.67
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25318819.23
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 201693.72 15492310.99
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 72103.28 8379834.95
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 563347.88 4462831.19
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 225202.43 2961142.43
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 330401.79 4050838.28
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 283077.21 7003979.31
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 611.91 13881480.45
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23911739.22
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31467365.70
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1676438.21 0.202474E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2961142.43
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 563347.88 36904791.24



Table of Contents

Report: SpaceGainsMonthly

For: FRONTSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 0.00 50535792.34
February 0.00 13573960.23 0.00 0.00 0.00 0.00 0.00 0.00 39134758.70
March 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 0.00 34579867.69
April 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 353941.18 21750816.39
May 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 132131.81 12281772.14
June 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 718455.17 7223497.61
July 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 242427.35 5106542.17
August 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 412137.73 6796057.93
September 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 409180.48 10631792.35
October 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 12493.04 19635089.51
November 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 0.00 33207594.10
December 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 0.00 43000563.32
                   
Annual Sum or Average 0.00 0.176946E+09 0.00 0.00 0.00 0.00 0.00 2280766.76 0.283884E+09
Minimum of Months 0.00 13573960.23 0.00 0.00 0.00 0.00 0.00 0.00 5106542.17
Maximum of Months 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 718455.17 50535792.34



Table of Contents

Report: SpaceGainsMonthly

For: FRONTSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.300197E+09
February 0.00 0.256048E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.233567E+09
March 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 1519.68 0.206162E+09
April 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 2083099.48 0.134295E+09
May 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 711328.14 80957505.55
June 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 3089268.51 52099249.76
July 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 775311.27 39541345.27
August 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 1581119.30 50585678.48
September 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 1993294.10 71343418.58
October 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 141666.65 0.122380E+09
November 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.199945E+09
December 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.254928E+09
                   
Annual Sum or Average 0.00 0.333777E+10 0.00 0.00 0.00 0.00 0.00 10376607.14 0.174600E+10
Minimum of Months 0.00 0.256048E+09 0.00 0.00 0.00 0.00 0.00 0.00 39541345.27
Maximum of Months 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 3089268.51 0.300197E+09



Table of Contents

Report: SpaceGainsMonthly

For: REARSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.327773E+09
February 0.00 0.256109E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.259299E+09
March 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.233004E+09
April 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 129349.20 0.151297E+09
May 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 594.95 92848163.75
June 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 804927.92 55558376.09
July 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 20979.25 44349478.18
August 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 214288.92 57169956.80
September 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 49873.68 79019656.50
October 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.136471E+09
November 0.00 0.274403E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.212686E+09
December 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.277904E+09
                   
Annual Sum or Average 0.00 0.333857E+10 0.00 0.00 0.00 0.00 0.00 1220013.91 0.192738E+10
Minimum of Months 0.00 0.256109E+09 0.00 0.00 0.00 0.00 0.00 0.00 44349478.18
Maximum of Months 0.00 0.283549E+09 0.00 0.00 0.00 0.00 0.00 804927.92 0.327773E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDORFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.300154E+09
February 0.00 0.100428E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.230580E+09
March 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.197161E+09
April 0.00 0.107601E+10 0.00 0.00 0.00 0.00 0.00 1816169.31 0.115372E+09
May 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 824727.78 58017970.22
June 0.00 0.107601E+10 0.00 0.00 0.00 0.00 0.00 6302242.95 28597312.31
July 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 3450050.54 17643402.18
August 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 4162077.01 25394769.34
September 0.00 0.107601E+10 0.00 0.00 0.00 0.00 0.00 3080877.87 47760200.89
October 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.101275E+09
November 0.00 0.107601E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.188369E+09
December 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.256286E+09
                   
Annual Sum or Average 0.00 0.130915E+11 0.00 0.00 0.00 0.00 0.00 19636145.46 0.156661E+10
Minimum of Months 0.00 0.100428E+10 0.00 0.00 0.00 0.00 0.00 0.00 17643402.18
Maximum of Months 0.00 0.111188E+10 0.00 0.00 0.00 0.00 0.00 6302242.95 0.300154E+09



Table of Contents

Report: SpaceGainsMonthly

For: REARSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 0.00 0.302187E+09
February 0.00 21725079.51 0.00 0.00 0.00 0.00 0.00 0.00 0.235263E+09
March 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 0.00 0.205779E+09
April 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 739904.45 0.133518E+09
May 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 143514.62 78468548.20
June 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 2196469.22 46193351.34
July 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 399126.39 35999498.18
August 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 1097314.13 47965725.90
September 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 681776.14 66954645.70
October 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 0.00 0.117894E+09
November 0.00 23276870.90 0.00 0.00 0.00 0.00 0.00 0.00 0.190758E+09
December 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 0.00 0.251696E+09
                   
Annual Sum or Average 0.00 0.283202E+09 0.00 0.00 0.00 0.00 0.00 5258104.95 0.171268E+10
Minimum of Months 0.00 21725079.51 0.00 0.00 0.00 0.00 0.00 0.00 35999498.18
Maximum of Months 0.00 24052766.60 0.00 0.00 0.00 0.00 0.00 2196469.22 0.302187E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM401

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.333455E+09 0.110112E+09 0.357425E+09 0.00 0.00 0.00 0.00 0.00 0.133683E+09
February 0.301372E+09 99048113.69 0.322587E+09 0.00 0.00 0.00 0.00 0.00 0.102297E+09
March 0.334054E+09 0.108804E+09 0.356629E+09 0.00 0.00 0.00 0.00 0.00 87317564.67
April 0.322827E+09 0.106264E+09 0.345724E+09 0.00 0.00 0.00 0.00 1196125.69 51012323.54
May 0.333854E+09 0.109240E+09 0.356894E+09 0.00 0.00 0.00 0.00 623127.89 25153901.76
June 0.323226E+09 0.105421E+09 0.345193E+09 0.00 0.00 0.00 0.00 4262613.60 11632165.20
July 0.333455E+09 0.110098E+09 0.357425E+09 0.00 0.00 0.00 0.00 2866169.77 6967617.77
August 0.334054E+09 0.108804E+09 0.356629E+09 0.00 0.00 0.00 0.00 3216925.31 10217255.34
September 0.322827E+09 0.106293E+09 0.345724E+09 0.00 0.00 0.00 0.00 2111952.41 20453507.13
October 0.333655E+09 0.109662E+09 0.357159E+09 0.00 0.00 0.00 0.00 1643.35 45151200.93
November 0.322827E+09 0.106279E+09 0.345724E+09 0.00 0.00 0.00 0.00 0.00 83548045.09
December 0.333455E+09 0.110112E+09 0.357425E+09 0.00 0.00 0.00 0.00 0.00 0.113826E+09
                   
Annual Sum or Average 0.392906E+10 0.129014E+10 0.420454E+10 0.00 0.00 0.00 0.00 14278558.02 0.691260E+09
Minimum of Months 0.301372E+09 99048113.69 0.322587E+09 0.00 0.00 0.00 0.00 0.00 6967617.77
Maximum of Months 0.334054E+09 0.110112E+09 0.357425E+09 0.00 0.00 0.00 0.00 4262613.60 0.133683E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM402_405

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.148370E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.112182E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96956823.03
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 416794.65 62455654.13
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 117549.06 36187065.85
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1635446.59 20010653.64
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 431878.92 14474636.07
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 725202.74 19358375.06
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 600506.96 28417022.35
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 52553194.97
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 90845249.82
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.123209E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3927378.91 0.805019E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14474636.07
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1635446.59 0.148370E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM406_408

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.120133E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 91569707.42
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 79897702.11
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 324906.51 51578603.75
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 94365.98 29648533.19
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1319842.08 16212369.41
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 348038.69 11679702.23
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 582169.61 15643452.14
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 476035.61 23250948.01
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43471893.80
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74370008.61
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 99984658.01
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3145358.47 0.657440E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11679702.23
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1319842.08 0.120133E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM409_412

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.133382E+10 0.440447E+09 0.142970E+10 0.00 0.00 0.00 0.00 0.00 0.174660E+09
February 0.120549E+10 0.396192E+09 0.129035E+10 0.00 0.00 0.00 0.00 0.00 0.134704E+09
March 0.133621E+10 0.435217E+09 0.142652E+10 0.00 0.00 0.00 0.00 0.00 0.116628E+09
April 0.129131E+10 0.425057E+09 0.138290E+10 0.00 0.00 0.00 0.00 1555539.30 68309219.90
May 0.133542E+10 0.436961E+09 0.142758E+10 0.00 0.00 0.00 0.00 811277.47 33247678.83
June 0.129291E+10 0.421685E+09 0.138077E+10 0.00 0.00 0.00 0.00 5549290.22 15286690.38
July 0.133382E+10 0.440390E+09 0.142970E+10 0.00 0.00 0.00 0.00 3733629.41 9154719.52
August 0.133621E+10 0.435217E+09 0.142652E+10 0.00 0.00 0.00 0.00 4190010.55 13428476.90
September 0.129131E+10 0.425172E+09 0.138290E+10 0.00 0.00 0.00 0.00 2747709.44 27292809.62
October 0.133462E+10 0.438647E+09 0.142864E+10 0.00 0.00 0.00 0.00 2080.62 60978053.72
November 0.129131E+10 0.425115E+09 0.138290E+10 0.00 0.00 0.00 0.00 0.00 0.110641E+09
December 0.133382E+10 0.440447E+09 0.142970E+10 0.00 0.00 0.00 0.00 0.00 0.149184E+09
                   
Annual Sum or Average 0.157162E+11 0.516055E+10 0.168182E+11 0.00 0.00 0.00 0.00 18589537.01 0.913515E+09
Minimum of Months 0.120549E+10 0.396192E+09 0.129035E+10 0.00 0.00 0.00 0.00 0.00 9154719.52
Maximum of Months 0.133621E+10 0.440447E+09 0.142970E+10 0.00 0.00 0.00 0.00 5549290.22 0.174660E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM413

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 37092128.29
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27982109.66
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23902612.35
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 129396.59 15006254.75
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33599.90 8437571.21
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 447271.33 4604455.93
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 124184.61 3276718.55
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 221543.99 4479602.95
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 181075.42 6837686.56
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 107.81 12952403.27
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22584283.52
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30817778.86
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1137179.65 0.197974E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3276718.55
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 447271.33 37092128.29



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM414

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 37610943.70
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29053089.84
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25684909.30
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 90206.55 15945279.61
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28922.51 9104638.99
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 405408.20 4886826.10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 109178.47 3454236.47
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 171023.19 4630656.78
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 133529.72 7346214.19
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14067430.33
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23739779.60
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31656080.91
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 938268.63 0.207180E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3454236.47
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 405408.20 37610943.70



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM415_418

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.133382E+10 0.440416E+09 0.142960E+10 0.00 0.00 0.00 0.00 0.00 0.175590E+09
February 0.120549E+10 0.396164E+09 0.129026E+10 0.00 0.00 0.00 0.00 0.00 0.136025E+09
March 0.133621E+10 0.435186E+09 0.142641E+10 0.00 0.00 0.00 0.00 0.00 0.118414E+09
April 0.129131E+10 0.425027E+09 0.138280E+10 0.00 0.00 0.00 0.00 1561490.72 68600407.28
May 0.133542E+10 0.436930E+09 0.142748E+10 0.00 0.00 0.00 0.00 811977.34 32835829.25
June 0.129291E+10 0.421655E+09 0.138067E+10 0.00 0.00 0.00 0.00 5618073.18 14983779.65
July 0.133382E+10 0.440359E+09 0.142960E+10 0.00 0.00 0.00 0.00 3825323.26 8606589.82
August 0.133621E+10 0.435186E+09 0.142641E+10 0.00 0.00 0.00 0.00 4238663.38 12897392.74
September 0.129131E+10 0.425142E+09 0.138280E+10 0.00 0.00 0.00 0.00 2765721.26 27160198.69
October 0.133462E+10 0.438616E+09 0.142854E+10 0.00 0.00 0.00 0.00 2162.66 61623403.93
November 0.129131E+10 0.425084E+09 0.138280E+10 0.00 0.00 0.00 0.00 0.00 0.111723E+09
December 0.133382E+10 0.440416E+09 0.142960E+10 0.00 0.00 0.00 0.00 0.00 0.150210E+09
                   
Annual Sum or Average 0.157162E+11 0.516018E+10 0.168170E+11 0.00 0.00 0.00 0.00 18823411.80 0.918670E+09
Minimum of Months 0.120549E+10 0.396164E+09 0.129026E+10 0.00 0.00 0.00 0.00 0.00 8606589.82
Maximum of Months 0.133621E+10 0.440416E+09 0.142960E+10 0.00 0.00 0.00 0.00 5618073.18 0.175590E+09



Table of Contents

Report: SpaceGainsMonthly

For: ELEVATORCOREFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74713073.93
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58173869.12
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51430434.35
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 249711.33 31398138.37
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73619.45 17186034.72
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 868000.15 8982198.62
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 279913.17 6077521.10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 426788.55 8291896.58
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 375655.11 13961034.87
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27778829.30
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48077633.39
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 63754592.01
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2273687.77 0.409825E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6077521.10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 868000.15 74713073.93



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM419

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 43841086.10
February 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 33939714.99
March 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 0.00 29509674.42
April 0.322827E+09 0.106257E+09 0.345699E+09 0.00 0.00 0.00 0.00 389986.38 17120970.90
May 0.333854E+09 0.109232E+09 0.356869E+09 0.00 0.00 0.00 0.00 202752.78 8208549.59
June 0.323226E+09 0.105414E+09 0.345169E+09 0.00 0.00 0.00 0.00 1403596.44 3750418.19
July 0.333455E+09 0.110090E+09 0.357399E+09 0.00 0.00 0.00 0.00 955286.98 2157812.52
August 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 1058326.25 3231438.55
September 0.322827E+09 0.106285E+09 0.345699E+09 0.00 0.00 0.00 0.00 690535.45 6791218.79
October 0.333655E+09 0.109654E+09 0.357134E+09 0.00 0.00 0.00 0.00 534.93 15382070.18
November 0.322827E+09 0.106271E+09 0.345699E+09 0.00 0.00 0.00 0.00 0.00 27879173.60
December 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 37497867.71
                   
Annual Sum or Average 0.392906E+10 0.129005E+10 0.420424E+10 0.00 0.00 0.00 0.00 4701019.21 0.229310E+09
Minimum of Months 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 2157812.52
Maximum of Months 0.334054E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 1403596.44 43841086.10



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM420_423

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.133382E+10 0.440416E+09 0.142960E+10 0.00 0.00 0.00 0.00 0.00 0.175545E+09
February 0.120549E+10 0.396164E+09 0.129026E+10 0.00 0.00 0.00 0.00 0.00 0.135769E+09
March 0.133621E+10 0.435186E+09 0.142641E+10 0.00 0.00 0.00 0.00 0.00 0.118004E+09
April 0.129131E+10 0.425027E+09 0.138280E+10 0.00 0.00 0.00 0.00 1563468.11 68377417.69
May 0.133542E+10 0.436930E+09 0.142748E+10 0.00 0.00 0.00 0.00 812916.21 32683941.57
June 0.129291E+10 0.421655E+09 0.138067E+10 0.00 0.00 0.00 0.00 5620861.83 14878178.31
July 0.133382E+10 0.440359E+09 0.142960E+10 0.00 0.00 0.00 0.00 3828534.53 8494037.97
August 0.133621E+10 0.435186E+09 0.142641E+10 0.00 0.00 0.00 0.00 4243078.92 12756340.94
September 0.129131E+10 0.425142E+09 0.138280E+10 0.00 0.00 0.00 0.00 2769478.35 27039679.63
October 0.133462E+10 0.438616E+09 0.142854E+10 0.00 0.00 0.00 0.00 2168.25 61443798.33
November 0.129131E+10 0.425084E+09 0.138280E+10 0.00 0.00 0.00 0.00 0.00 0.111481E+09
December 0.133382E+10 0.440416E+09 0.142960E+10 0.00 0.00 0.00 0.00 0.00 0.150076E+09
                   
Annual Sum or Average 0.157162E+11 0.516018E+10 0.168170E+11 0.00 0.00 0.00 0.00 18840506.21 0.916549E+09
Minimum of Months 0.120549E+10 0.396164E+09 0.129026E+10 0.00 0.00 0.00 0.00 0.00 8494037.97
Maximum of Months 0.133621E+10 0.440416E+09 0.142960E+10 0.00 0.00 0.00 0.00 5620861.83 0.175545E+09



Table of Contents

Report: SpaceGainsMonthly

For: GUESTROOM424

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 43540915.44
February 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 33486563.79
March 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 0.00 28947806.17
April 0.322827E+09 0.106257E+09 0.345699E+09 0.00 0.00 0.00 0.00 390618.26 16842539.34
May 0.333854E+09 0.109232E+09 0.356869E+09 0.00 0.00 0.00 0.00 203042.34 8122060.93
June 0.323226E+09 0.105414E+09 0.345169E+09 0.00 0.00 0.00 0.00 1404182.34 3708485.87
July 0.333455E+09 0.110090E+09 0.357399E+09 0.00 0.00 0.00 0.00 955906.35 2118260.27
August 0.334054E+09 0.108797E+09 0.356604E+09 0.00 0.00 0.00 0.00 1059270.00 3181253.15
September 0.322827E+09 0.106285E+09 0.345699E+09 0.00 0.00 0.00 0.00 691318.74 6711817.30
October 0.333655E+09 0.109654E+09 0.357134E+09 0.00 0.00 0.00 0.00 552.82 15118638.63
November 0.322827E+09 0.106271E+09 0.345699E+09 0.00 0.00 0.00 0.00 0.00 27475427.06
December 0.333455E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 0.00 37136685.86
                   
Annual Sum or Average 0.392906E+10 0.129005E+10 0.420424E+10 0.00 0.00 0.00 0.00 4704890.86 0.226390E+09
Minimum of Months 0.301372E+09 99041085.40 0.322564E+09 0.00 0.00 0.00 0.00 0.00 2118260.27
Maximum of Months 0.334054E+09 0.110104E+09 0.357399E+09 0.00 0.00 0.00 0.00 1404182.34 43540915.44



Table of Contents

Report: SpaceGainsMonthly

For: FRONTSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 0.00 52417329.26
February 0.00 13573960.23 0.00 0.00 0.00 0.00 0.00 0.00 40592716.87
March 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 0.00 35874423.89
April 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 237332.88 22459416.31
May 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 56218.25 12860160.12
June 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 532846.03 7310973.14
July 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 139410.17 5206737.15
August 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 268625.99 6844674.55
September 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 290418.71 10567514.50
October 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 2352.74 19797895.12
November 0.00 14543528.81 0.00 0.00 0.00 0.00 0.00 0.00 33729349.11
December 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 0.00 44308406.76
                   
Annual Sum or Average 0.00 0.176946E+09 0.00 0.00 0.00 0.00 0.00 1527204.77 0.291970E+09
Minimum of Months 0.00 13573960.23 0.00 0.00 0.00 0.00 0.00 0.00 5206737.15
Maximum of Months 0.00 15028313.11 0.00 0.00 0.00 0.00 0.00 532846.03 52417329.26



Table of Contents

Report: SpaceGainsMonthly

For: FRONTSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.303822E+09
February 0.00 0.256048E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.234648E+09
March 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.205306E+09
April 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 885905.50 0.134551E+09
May 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 70254.20 84225459.97
June 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 1280556.81 53979464.22
July 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 115368.47 42117139.44
August 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 480193.28 52220991.47
September 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 816139.28 69429397.93
October 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 51209.43 0.118267E+09
November 0.00 0.274337E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.193080E+09
December 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.253065E+09
                   
Annual Sum or Average 0.00 0.333777E+10 0.00 0.00 0.00 0.00 0.00 3699626.97 0.174471E+10
Minimum of Months 0.00 0.256048E+09 0.00 0.00 0.00 0.00 0.00 0.00 42117139.44
Maximum of Months 0.00 0.283482E+09 0.00 0.00 0.00 0.00 0.00 1280556.81 0.303822E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: REARSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 105.87 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 375.31 18-JAN-20:00
February 0.00 01-FEB-00:10 105.87 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 259.56 01-FEB-21:00
March 0.00 01-MAR-00:10 105.87 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 224.86 06-MAR-08:00
April 0.00 01-APR-00:10 105.87 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 57.32 15-APR-15:00 174.20 25-APR-05:55
May 0.00 01-MAY-00:10 105.87 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 27.01 05-MAY-15:00 100.77 01-MAY-24:00
June 0.00 01-JUN-00:10 105.87 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 51.01 18-JUN-15:55 86.72 02-JUN-05:00
July 0.00 01-JUL-00:10 105.87 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 24.64 25-JUL-16:00 46.75 10-JUL-14:00
August 0.00 01-AUG-00:10 105.87 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 21.52 03-AUG-16:00 53.19 06-AUG-05:55
September 0.00 01-SEP-00:10 105.87 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 20.55 06-SEP-14:00 85.90 18-SEP-22:55
October 0.00 01-OCT-00:10 105.87 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 141.14 24-OCT-05:55
November 0.00 01-NOV-00:10 105.87 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 279.22 20-NOV-22:00
December 0.00 01-DEC-00:10 105.87 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 438.20 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   105.87   0.00   0.00 0.00 0.00 0.00 0.00   46.75  
Maximum of Months 0.00   105.87   0.00   0.00 0.00 0.00 0.00 57.32   438.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDORFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 498.16 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 66551.92 31-JAN-07:02
February 0.00 01-FEB-00:10 498.16 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 77233.90 02-FEB-07:01
March 0.00 01-MAR-00:10 498.16 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 40549.09 06-MAR-07:01
April 0.00 01-APR-00:10 498.16 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 6243.85 15-APR-16:52 33414.85 03-APR-06:01
May 0.00 01-MAY-00:10 498.16 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 5140.75 31-MAY-17:00 22807.74 02-MAY-06:01
June 0.00 01-JUN-00:10 498.16 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 8839.83 11-JUN-16:10 18093.15 03-JUN-06:01
July 0.00 01-JUL-00:10 498.16 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 6120.96 26-JUL-16:10 12456.94 23-JUL-06:01
August 0.00 01-AUG-00:10 498.16 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 9345.58 04-AUG-16:10 15990.52 07-AUG-06:01
September 0.00 01-SEP-00:10 498.16 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 7809.85 07-SEP-16:10 25178.77 29-SEP-06:01
October 0.00 01-OCT-00:10 498.16 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 28633.92 23-OCT-06:01
November 0.00 01-NOV-00:10 498.16 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 62829.77 26-NOV-07:02
December 0.00 01-DEC-00:10 498.16 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 54990.56 09-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   498.16   0.00   0.00 0.00 0.00 0.00 0.00   12456.94  
Maximum of Months 0.00   498.16   0.00   0.00 0.00 0.00 0.00 9345.58   77233.90  



Table of Contents

Report: PeakSpaceGainsMonthly

For: REARSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 14.37 01-JAN-08:09 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 365.14 18-JAN-20:00
February 0.00 01-FEB-00:10 14.37 01-FEB-08:09 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 255.21 01-FEB-21:00
March 0.00 01-MAR-00:10 14.37 01-MAR-08:09 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 216.82 06-MAR-08:00
April 0.00 01-APR-00:10 14.37 01-APR-07:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 67.30 15-APR-15:00 166.09 25-APR-05:55
May 0.00 01-MAY-00:10 14.37 01-MAY-07:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 36.74 05-MAY-15:00 93.58 01-MAY-24:00
June 0.00 01-JUN-00:10 14.37 01-JUN-07:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 57.35 18-JUN-15:55 81.03 02-JUN-05:00
July 0.00 01-JUL-00:10 14.37 01-JUL-07:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 30.84 25-JUL-16:00 42.43 10-JUL-14:00
August 0.00 01-AUG-00:10 14.37 01-AUG-07:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 26.71 03-AUG-15:55 49.69 06-AUG-06:01
September 0.00 01-SEP-00:10 14.37 01-SEP-07:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 25.12 06-SEP-14:00 81.82 18-SEP-22:55
October 0.00 01-OCT-00:10 14.37 01-OCT-07:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.98 20-OCT-15:00 134.69 24-OCT-05:55
November 0.00 01-NOV-00:10 14.37 01-NOV-07:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 268.06 20-NOV-22:00
December 0.00 01-DEC-00:10 14.37 01-DEC-08:09 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 428.67 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   14.37   0.00   0.00 0.00 0.00 0.00 0.00   42.43  
Maximum of Months 0.00   14.37   0.00   0.00 0.00 0.00 0.00 67.30   428.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONTLOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 4897.20 01-JAN-07:10 1474.30 01-JAN-16:40 4249.25 01-JAN-06:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 314.30 18-JAN-20:00
February 4897.20 01-FEB-06:10 1474.30 01-FEB-17:19 4249.25 01-FEB-06:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 212.63 04-FEB-23:00
March 4897.20 01-MAR-06:10 1474.30 01-MAR-17:00 4249.25 01-MAR-06:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 194.68 06-MAR-08:00
April 4897.20 01-APR-06:10 918.03 10-APR-07:10 4249.25 01-APR-05:10 0.00 0.00 0.00 0.00 34.14 15-APR-15:00 156.91 25-APR-05:55
May 4897.20 01-MAY-05:10 776.04 25-MAY-07:10 4249.25 01-MAY-05:10 0.00 0.00 0.00 0.00 15.32 31-MAY-13:00 91.21 01-MAY-08:55
June 4897.20 01-JUN-05:10 868.29 13-JUN-07:10 4249.25 01-JUN-05:10 0.00 0.00 0.00 0.00 39.29 18-JUN-16:00 70.94 02-JUN-05:00
July 4897.20 01-JUL-06:10 878.01 09-JUL-07:10 4249.25 01-JUL-05:10 0.00 0.00 0.00 0.00 24.25 25-JUL-15:55 34.04 10-JUL-14:00
August 4897.20 01-AUG-05:10 838.95 31-AUG-07:10 4249.25 01-AUG-05:10 0.00 0.00 0.00 0.00 23.61 04-AUG-16:33 35.17 06-AUG-06:15
September 4897.20 01-SEP-05:10 921.64 21-SEP-07:10 4249.25 01-SEP-05:10 0.00 0.00 0.00 0.00 21.24 11-SEP-15:00 64.48 27-SEP-10:00
October 4897.20 01-OCT-06:10 1474.30 28-OCT-16:00 4249.25 01-OCT-05:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 111.40 24-OCT-06:00
November 4897.20 01-NOV-05:10 1474.30 01-NOV-16:00 4249.25 01-NOV-05:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 214.03 20-NOV-22:00
December 4897.20 01-DEC-06:10 1474.30 01-DEC-16:30 4249.25 01-DEC-06:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 356.98 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 4897.20   776.04   4249.25   0.00 0.00 0.00 0.00 0.00   34.04  
Maximum of Months 4897.20   1474.30   4249.25   0.00 0.00 0.00 0.00 39.29   356.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RESTROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 162.16 01-JAN-07:10 121.63 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 45.63 18-JAN-20:00
February 162.16 01-FEB-06:10 121.63 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 30.26 10-FEB-22:00
March 162.16 01-MAR-06:10 121.63 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 28.56 06-MAR-08:00
April 162.16 01-APR-06:10 121.63 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 4.82 15-APR-15:00 23.18 25-APR-06:00
May 162.16 01-MAY-05:10 121.63 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 2.17 31-MAY-13:00 12.89 01-MAY-09:00
June 162.16 01-JUN-05:10 121.63 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 5.55 18-JUN-15:55 10.02 02-JUN-05:00
July 162.16 01-JUL-06:10 121.63 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 3.43 25-JUL-15:55 4.81 10-JUL-14:00
August 162.16 01-AUG-05:10 121.63 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 3.34 04-AUG-16:33 4.97 06-AUG-06:20
September 162.16 01-SEP-05:10 121.63 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 3.00 11-SEP-15:00 9.11 27-SEP-09:55
October 162.16 01-OCT-06:10 121.63 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 16.09 24-OCT-06:00
November 162.16 01-NOV-05:10 121.63 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 33.38 20-NOV-22:00
December 162.16 01-DEC-06:10 121.63 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 51.53 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 162.16   121.63   0.00   0.00 0.00 0.00 0.00 0.00   4.81  
Maximum of Months 162.16   121.63   0.00   0.00 0.00 0.00 0.00 5.55   51.53  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MEETINGROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2838.00 01-JAN-08:09 838.14 01-JAN-16:40 237.69 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 109.32 18-JAN-20:00
February 2838.00 01-FEB-08:09 838.14 01-FEB-17:19 237.69 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 73.96 04-FEB-22:55
March 2838.00 01-MAR-08:09 838.14 01-MAR-17:00 237.69 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 67.71 06-MAR-08:00
April 2838.00 01-APR-07:10 722.99 10-APR-07:10 237.69 01-APR-07:10 0.00 0.00 0.00 0.00 11.87 15-APR-15:00 54.15 25-APR-05:55
May 2838.00 01-MAY-07:10 662.13 04-MAY-07:10 237.69 01-MAY-07:10 0.00 0.00 0.00 0.00 5.33 31-MAY-13:00 29.14 01-MAY-24:00
June 2838.00 01-JUN-07:10 677.79 13-JUN-07:10 237.69 01-JUN-07:10 0.00 0.00 0.00 0.00 13.66 18-JUN-16:00 24.66 02-JUN-05:00
July 2838.00 01-JUL-07:10 686.50 09-JUL-07:10 237.69 01-JUL-07:10 0.00 0.00 0.00 0.00 8.43 25-JUL-16:00 11.82 10-JUL-14:00
August 2838.00 01-AUG-07:10 678.13 24-AUG-07:10 237.69 01-AUG-07:10 0.00 0.00 0.00 0.00 8.21 04-AUG-16:33 12.23 06-AUG-06:20
September 2838.00 01-SEP-07:10 727.74 21-SEP-07:10 237.69 01-SEP-07:10 0.00 0.00 0.00 0.00 7.39 11-SEP-15:00 20.90 18-SEP-22:55
October 2838.00 01-OCT-07:10 838.14 28-OCT-16:00 237.69 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 38.33 24-OCT-06:10
November 2838.00 01-NOV-07:10 838.14 01-NOV-16:00 237.69 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 77.22 20-NOV-22:00
December 2838.00 01-DEC-08:09 838.14 01-DEC-16:30 237.69 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 124.16 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2838.00   662.13   237.69   0.00 0.00 0.00 0.00 0.00   11.82  
Maximum of Months 2838.00   838.14   237.69   0.00 0.00 0.00 0.00 13.66   124.16  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECHANICALROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 60.38 01-JAN-08:09 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 46.80 18-JAN-20:00
February 0.00 01-FEB-00:10 60.38 01-FEB-08:09 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 31.23 10-FEB-22:00
March 0.00 01-MAR-00:10 60.38 01-MAR-08:09 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 29.05 06-MAR-08:00
April 0.00 01-APR-00:10 60.38 01-APR-07:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 2.49 15-APR-15:00 24.62 25-APR-05:55
May 0.00 01-MAY-00:10 60.38 01-MAY-07:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.87 31-MAY-13:00 14.19 01-MAY-09:00
June 0.00 01-JUN-00:10 60.38 01-JUN-07:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 3.02 11-JUN-15:00 11.61 02-JUN-05:00
July 0.00 01-JUL-00:10 60.38 01-JUL-07:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.66 25-JUL-15:55 7.21 10-JUL-14:00
August 0.00 01-AUG-00:10 60.38 01-AUG-07:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 1.45 04-AUG-16:01 6.94 06-AUG-06:00
September 0.00 01-SEP-00:10 60.38 01-SEP-07:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 1.42 06-SEP-14:00 10.71 27-SEP-09:55
October 0.00 01-OCT-00:10 60.38 01-OCT-07:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 17.58 24-OCT-06:00
November 0.00 01-NOV-00:10 60.38 01-NOV-07:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 34.61 20-NOV-22:00
December 0.00 01-DEC-00:10 60.38 01-DEC-08:09 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 52.88 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   60.38   0.00   0.00 0.00 0.00 0.00 0.00   6.94  
Maximum of Months 0.00   60.38   0.00   0.00 0.00 0.00 0.00 3.02   52.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM101

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 42.41 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 27.76 01-FEB-21:00
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 26.04 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 3.97 15-APR-15:10 21.49 25-APR-05:55
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 1.77 31-MAY-13:00 11.71 01-MAY-09:00
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 4.04 18-JUN-16:00 9.88 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 1.99 25-JUL-16:00 5.63 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 2.17 04-AUG-16:30 5.73 06-AUG-05:55
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 2.21 06-SEP-14:00 9.00 18-SEP-22:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 15.36 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 30.83 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 48.60 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   5.63  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 4.04   48.60  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM102

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 41.71 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 27.48 01-FEB-21:00
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 25.61 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 4.37 15-APR-15:10 20.83 25-APR-05:55
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 1.97 31-MAY-13:00 11.21 01-MAY-09:00
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 4.43 18-JUN-16:00 9.46 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 2.36 25-JUL-16:00 5.25 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 2.44 04-AUG-16:30 5.37 06-AUG-05:55
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 2.42 06-SEP-14:00 8.61 18-SEP-22:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 14.88 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 30.13 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 47.93 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   5.25  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 4.43   47.93  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM103

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 198.00 01-JAN-00:10 99.23 01-JAN-19:10 349.07 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 44.41 18-JAN-20:00
February 198.00 01-FEB-00:10 99.23 01-FEB-20:10 349.07 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 30.04 04-FEB-22:55
March 198.00 01-MAR-00:10 99.23 01-MAR-20:10 349.07 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 27.51 06-MAR-08:00
April 198.00 01-APR-00:10 99.23 01-APR-18:10 349.07 01-APR-07:10 0.00 0.00 0.00 0.00 6.76 15-APR-16:52 20.36 25-APR-06:00
May 198.00 01-MAY-00:10 99.23 01-MAY-19:10 349.07 01-MAY-06:10 0.00 0.00 0.00 0.00 3.97 05-MAY-15:06 10.86 02-MAY-03:00
June 198.00 01-JUN-00:10 99.23 01-JUN-19:10 349.07 01-JUN-06:10 0.00 0.00 0.00 0.00 7.41 18-JUN-16:00 8.36 02-JUN-05:00
July 198.00 01-JUL-00:10 99.23 01-JUL-18:10 349.07 01-JUL-07:10 0.00 0.00 0.00 0.00 5.15 25-JUL-16:00 4.47 10-JUL-14:00
August 198.00 01-AUG-00:10 99.23 01-AUG-19:10 349.07 01-AUG-06:10 0.00 0.00 0.00 0.00 4.86 04-AUG-16:52 4.64 06-AUG-07:10
September 198.00 01-SEP-00:10 99.23 01-SEP-19:10 349.07 01-SEP-06:10 0.00 0.00 0.00 0.00 4.84 11-SEP-15:07 7.90 27-SEP-08:00
October 198.00 01-OCT-00:10 99.23 01-OCT-18:10 349.07 01-OCT-07:10 0.00 0.00 0.00 0.00 0.77 20-OCT-15:06 14.03 24-OCT-06:00
November 198.00 01-NOV-00:10 99.23 01-NOV-19:10 349.07 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 30.24 20-NOV-22:00
December 198.00 01-DEC-00:10 99.23 01-DEC-20:10 349.07 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 50.44 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 198.00   99.23   349.07   0.00 0.00 0.00 0.00 0.00   4.47  
Maximum of Months 198.00   99.23   349.07   0.00 0.00 0.00 0.00 7.41   50.44  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM104

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 198.00 01-JAN-00:10 99.23 01-JAN-19:10 349.05 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 44.41 18-JAN-20:00
February 198.00 01-FEB-00:10 99.23 01-FEB-20:10 349.05 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 30.04 04-FEB-22:55
March 198.00 01-MAR-00:10 99.23 01-MAR-20:10 349.05 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 27.51 06-MAR-08:00
April 198.00 01-APR-00:10 99.23 01-APR-18:10 349.05 01-APR-07:10 0.00 0.00 0.00 0.00 6.76 15-APR-16:52 20.36 25-APR-06:00
May 198.00 01-MAY-00:10 99.23 01-MAY-19:10 349.05 01-MAY-06:10 0.00 0.00 0.00 0.00 3.97 05-MAY-15:06 11.10 01-MAY-08:00
June 198.00 01-JUN-00:10 99.23 01-JUN-19:10 349.05 01-JUN-06:10 0.00 0.00 0.00 0.00 7.41 18-JUN-16:00 8.36 02-JUN-05:00
July 198.00 01-JUL-00:10 99.23 01-JUL-18:10 349.05 01-JUL-07:10 0.00 0.00 0.00 0.00 5.15 25-JUL-16:00 4.47 10-JUL-14:00
August 198.00 01-AUG-00:10 99.23 01-AUG-19:10 349.05 01-AUG-06:10 0.00 0.00 0.00 0.00 4.86 04-AUG-16:52 4.63 06-AUG-07:10
September 198.00 01-SEP-00:10 99.23 01-SEP-19:10 349.05 01-SEP-06:10 0.00 0.00 0.00 0.00 4.84 11-SEP-15:06 8.10 27-SEP-08:00
October 198.00 01-OCT-00:10 99.23 01-OCT-18:10 349.05 01-OCT-07:10 0.00 0.00 0.00 0.00 0.77 20-OCT-15:05 14.21 24-OCT-07:50
November 198.00 01-NOV-00:10 99.23 01-NOV-19:10 349.05 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 30.24 20-NOV-22:00
December 198.00 01-DEC-00:10 99.23 01-DEC-20:10 349.05 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 50.44 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 0.00   4.47  
Maximum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 7.41   50.44  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM105

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 198.00 01-JAN-00:10 99.23 01-JAN-19:10 349.05 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 44.41 18-JAN-20:00
February 198.00 01-FEB-00:10 99.23 01-FEB-20:10 349.05 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 30.04 04-FEB-23:00
March 198.00 01-MAR-00:10 99.23 01-MAR-20:10 349.05 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 27.74 06-MAR-08:10
April 198.00 01-APR-00:10 99.23 01-APR-18:10 349.05 01-APR-07:10 0.00 0.00 0.00 0.00 6.76 15-APR-16:52 20.36 25-APR-06:00
May 198.00 01-MAY-00:10 99.23 01-MAY-19:10 349.05 01-MAY-06:10 0.00 0.00 0.00 0.00 3.97 05-MAY-15:07 11.36 01-MAY-07:55
June 198.00 01-JUN-00:10 99.23 01-JUN-19:10 349.05 01-JUN-06:10 0.00 0.00 0.00 0.00 7.41 18-JUN-16:00 8.36 02-JUN-05:00
July 198.00 01-JUL-00:10 99.23 01-JUL-18:10 349.05 01-JUL-07:10 0.00 0.00 0.00 0.00 5.15 25-JUL-16:00 4.47 10-JUL-14:00
August 198.00 01-AUG-00:10 99.23 01-AUG-19:10 349.05 01-AUG-06:10 0.00 0.00 0.00 0.00 4.86 04-AUG-16:52 4.64 06-AUG-07:10
September 198.00 01-SEP-00:10 99.23 01-SEP-19:10 349.05 01-SEP-06:10 0.00 0.00 0.00 0.00 4.84 11-SEP-15:06 8.39 27-SEP-10:10
October 198.00 01-OCT-00:10 99.23 01-OCT-18:10 349.05 01-OCT-07:10 0.00 0.00 0.00 0.00 0.77 20-OCT-15:06 14.84 24-OCT-07:10
November 198.00 01-NOV-00:10 99.23 01-NOV-19:10 349.05 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 30.24 20-NOV-22:00
December 198.00 01-DEC-00:10 99.23 01-DEC-20:10 349.05 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 50.44 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 0.00   4.47  
Maximum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 7.41   50.44  



Table of Contents

Report: PeakSpaceGainsMonthly

For: EMPLOYEELOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1663.20 03-JAN-12:09 207.09 01-JAN-08:09 672.25 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 47.58 18-JAN-20:00
February 1663.20 01-FEB-12:09 207.09 01-FEB-08:09 672.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 30.98 10-FEB-22:00
March 1663.20 01-MAR-12:09 207.09 01-MAR-08:09 672.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 29.28 06-MAR-08:00
April 1663.20 03-APR-11:09 207.09 01-APR-07:10 672.25 01-APR-07:10 0.00 0.00 0.00 0.00 4.82 15-APR-15:00 23.18 25-APR-05:55
May 1663.20 01-MAY-11:09 207.09 01-MAY-07:10 672.25 01-MAY-07:10 0.00 0.00 0.00 0.00 2.16 31-MAY-13:00 12.89 01-MAY-09:00
June 1663.20 01-JUN-11:09 207.09 01-JUN-07:10 672.25 01-JUN-07:10 0.00 0.00 0.00 0.00 5.55 18-JUN-15:55 10.02 02-JUN-05:00
July 1663.20 03-JUL-11:09 207.09 01-JUL-07:10 672.25 01-JUL-07:10 0.00 0.00 0.00 0.00 3.43 25-JUL-15:55 4.81 10-JUL-14:00
August 1663.20 01-AUG-11:09 207.09 01-AUG-07:10 672.25 01-AUG-07:10 0.00 0.00 0.00 0.00 3.34 04-AUG-16:33 4.97 06-AUG-06:20
September 1663.20 01-SEP-11:09 207.09 01-SEP-07:10 672.25 01-SEP-07:10 0.00 0.00 0.00 0.00 3.00 11-SEP-15:00 9.11 27-SEP-09:55
October 1663.20 02-OCT-11:09 207.09 01-OCT-07:10 672.25 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 16.09 24-OCT-06:00
November 1663.20 01-NOV-11:09 207.09 01-NOV-07:10 672.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 33.39 20-NOV-22:00
December 1663.20 01-DEC-12:09 207.09 01-DEC-08:09 672.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 50.91 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1663.20   207.09   672.25   0.00 0.00 0.00 0.00 0.00   4.81  
Maximum of Months 1663.20   207.09   672.25   0.00 0.00 0.00 0.00 5.55   50.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRYROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 250.19 01-JAN-10:09 558.09 01-JAN-16:40 2709.07 01-JAN-08:09 40096.03 01-JAN-09:09 0.00 0.00 0.00 0.00 01-JAN-00:10 322.43 18-JAN-16:00
February 250.19 01-FEB-10:09 533.15 01-FEB-16:00 2709.07 01-FEB-08:09 40096.03 01-FEB-09:09 0.00 0.00 0.00 0.00 01-FEB-00:10 259.30 10-FEB-15:00
March 250.19 01-MAR-10:09 513.17 12-MAR-07:10 2709.07 01-MAR-08:09 40096.03 01-MAR-09:09 0.00 0.00 0.00 0.00 01-MAR-00:10 291.71 12-MAR-16:00
April 250.19 01-APR-09:09 471.80 10-APR-07:10 2709.07 01-APR-07:10 40096.03 01-APR-08:09 0.00 0.00 0.00 0.00 01-APR-00:10 253.99 24-APR-16:00
May 250.19 01-MAY-09:09 466.52 24-MAY-15:50 2709.07 01-MAY-07:10 40096.03 01-MAY-08:09 0.00 0.00 0.00 0.00 01-MAY-00:10 182.59 01-MAY-12:00
June 250.19 01-JUN-09:09 438.89 09-JUN-15:20 2709.07 01-JUN-07:10 40096.03 01-JUN-08:09 0.00 0.00 0.00 0.00 01-JUN-00:10 142.82 14-JUN-11:00
July 250.19 01-JUL-09:09 444.29 31-JUL-15:20 2709.07 01-JUL-07:10 40096.03 01-JUL-08:09 0.00 0.00 0.00 0.00 01-JUL-00:10 140.17 10-JUL-14:00
August 250.19 01-AUG-09:09 450.83 16-AUG-14:30 2709.07 01-AUG-07:10 40096.03 01-AUG-08:09 0.00 0.00 0.00 0.00 01-AUG-00:10 128.56 06-AUG-14:00
September 250.19 01-SEP-09:09 473.99 29-SEP-15:00 2709.07 01-SEP-07:10 40096.03 01-SEP-08:09 0.00 0.00 0.00 0.00 01-SEP-00:10 159.71 17-SEP-15:00
October 250.19 01-OCT-09:09 507.58 21-OCT-07:10 2709.07 01-OCT-07:10 40096.03 01-OCT-08:09 0.00 0.00 0.00 0.00 01-OCT-00:10 188.13 24-OCT-12:00
November 250.19 01-NOV-09:09 558.09 06-NOV-16:00 2709.07 01-NOV-07:10 40096.03 01-NOV-08:09 0.00 0.00 0.00 0.00 01-NOV-00:10 288.52 20-NOV-17:00
December 250.19 01-DEC-10:09 558.09 01-DEC-16:30 2709.07 01-DEC-08:09 40096.03 01-DEC-09:09 0.00 0.00 0.00 0.00 01-DEC-00:10 340.19 09-DEC-09:10
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 250.19   438.89   2709.07   40096.03   0.00 0.00 0.00 0.00   128.56  
Maximum of Months 250.19   558.09   2709.07   40096.03   0.00 0.00 0.00 0.00   340.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ELEVATORCOREFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 8074.65 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 181.32 18-JAN-18:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 8074.65 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 146.69 10-FEB-22:00
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 8074.65 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 139.63 12-MAR-16:10
April 0.00 01-APR-00:10 0.00 01-APR-00:10 8074.65 01-APR-06:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 128.16 24-APR-17:00
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 8074.65 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 86.43 01-MAY-09:00
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 8074.65 01-JUN-06:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:10 82.34 18-JUN-21:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 8074.65 01-JUL-06:10 0.00 0.00 0.00 0.00 0.00 01-JUL-00:10 57.91 14-JUL-17:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 8074.65 01-AUG-06:10 0.00 0.00 0.00 0.00 0.00 01-AUG-00:10 59.53 04-AUG-18:51
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 8074.65 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 69.26 24-SEP-16:10
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 8074.65 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 91.20 24-OCT-08:00
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 8074.65 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 146.28 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 8074.65 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 178.31 09-DEC-09:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   8074.65   0.00 0.00 0.00 0.00 0.00   57.91  
Maximum of Months 0.00   0.00   8074.65   0.00 0.00 0.00 0.00 0.00   181.32  



Table of Contents

Report: PeakSpaceGainsMonthly

For: EXERCISECENTERFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 924.00 01-JAN-07:10 315.90 01-JAN-07:10 606.20 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 44.41 18-JAN-20:00
February 924.00 01-FEB-07:10 315.90 01-FEB-07:10 606.20 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 30.04 04-FEB-22:55
March 924.00 01-MAR-07:10 315.90 01-MAR-07:10 606.20 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 27.51 06-MAR-08:00
April 924.00 01-APR-06:10 315.90 01-APR-06:10 606.20 01-APR-06:10 0.00 0.00 0.00 0.00 4.82 15-APR-15:00 20.36 25-APR-05:55
May 924.00 01-MAY-06:10 315.90 01-MAY-06:10 606.20 01-MAY-06:10 0.00 0.00 0.00 0.00 2.17 31-MAY-13:00 11.23 01-MAY-09:00
June 924.00 01-JUN-06:10 315.90 01-JUN-06:10 606.20 01-JUN-06:10 0.00 0.00 0.00 0.00 5.55 18-JUN-16:00 8.36 02-JUN-05:00
July 924.00 01-JUL-06:10 315.90 01-JUL-06:10 606.20 01-JUL-06:10 0.00 0.00 0.00 0.00 3.43 25-JUL-16:00 4.81 10-JUL-14:00
August 924.00 01-AUG-06:10 315.90 01-AUG-06:10 606.20 01-AUG-06:10 0.00 0.00 0.00 0.00 3.34 04-AUG-16:33 4.97 06-AUG-06:20
September 924.00 01-SEP-06:10 315.90 01-SEP-06:10 606.20 01-SEP-06:10 0.00 0.00 0.00 0.00 3.00 11-SEP-15:00 8.09 27-SEP-10:00
October 924.00 01-OCT-06:10 315.90 01-OCT-06:10 606.20 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 14.03 24-OCT-06:00
November 924.00 01-NOV-06:10 315.90 01-NOV-06:10 606.20 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 30.24 20-NOV-22:00
December 924.00 01-DEC-07:10 315.90 01-DEC-07:10 606.20 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 50.44 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 924.00   315.90   606.20   0.00 0.00 0.00 0.00 0.00   4.81  
Maximum of Months 924.00   315.90   606.20   0.00 0.00 0.00 0.00 5.55   50.44  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONTOFFICEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1320.00 03-JAN-08:09 609.04 01-JAN-16:40 1663.95 03-JAN-10:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 177.65 18-JAN-20:00
February 1320.00 01-FEB-08:09 592.77 11-FEB-16:00 1663.95 01-FEB-10:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 120.18 04-FEB-22:55
March 1320.00 01-MAR-08:09 581.15 12-MAR-07:10 1663.95 01-MAR-10:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 110.03 06-MAR-08:00
April 1320.00 03-APR-07:10 556.53 10-APR-07:10 1663.95 03-APR-09:09 0.00 0.00 0.00 0.00 19.29 15-APR-15:00 81.46 25-APR-06:00
May 1320.00 01-MAY-07:10 537.75 24-MAY-15:00 1663.95 01-MAY-09:09 0.00 0.00 0.00 0.00 8.66 31-MAY-13:00 51.17 01-MAY-09:00
June 1320.00 01-JUN-07:10 535.66 13-JUN-07:10 1663.95 01-JUN-09:09 0.00 0.00 0.00 0.00 22.20 18-JUN-15:55 38.90 02-JUN-05:00
July 1320.00 03-JUL-07:10 539.98 09-JUL-07:10 1663.95 03-JUL-09:09 0.00 0.00 0.00 0.00 13.71 25-JUL-15:55 19.25 10-JUL-14:00
August 1320.00 01-AUG-07:10 516.84 16-AUG-14:30 1663.95 01-AUG-09:09 0.00 0.00 0.00 0.00 13.35 04-AUG-16:33 19.88 06-AUG-06:17
September 1320.00 01-SEP-07:10 553.86 29-SEP-15:00 1663.95 01-SEP-09:09 0.00 0.00 0.00 0.00 12.01 11-SEP-15:00 36.45 27-SEP-10:00
October 1320.00 02-OCT-07:10 577.20 21-OCT-07:10 1663.95 02-OCT-09:09 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 58.89 24-OCT-06:00
November 1320.00 01-NOV-07:10 609.04 06-NOV-16:00 1663.95 01-NOV-09:09 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 120.97 20-NOV-22:00
December 1320.00 01-DEC-08:09 609.04 01-DEC-16:30 1663.95 01-DEC-10:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 201.77 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1320.00   516.84   1663.95   0.00 0.00 0.00 0.00 0.00   19.25  
Maximum of Months 1320.00   609.04   1663.95   0.00 0.00 0.00 0.00 22.20   201.77  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONTSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 105.84 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 353.06 18-JAN-20:00
February 0.00 01-FEB-00:10 105.84 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 232.01 01-FEB-21:00
March 0.00 01-MAR-00:10 105.84 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 6.28 25-MAR-15:00 202.31 06-MAR-08:00
April 0.00 01-APR-00:10 105.84 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 69.64 15-APR-15:00 162.34 25-APR-05:55
May 0.00 01-MAY-00:10 105.84 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 35.72 05-MAY-15:00 93.92 01-MAY-24:00
June 0.00 01-JUN-00:10 105.84 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 50.59 18-JUN-15:55 89.27 02-JUN-05:00
July 0.00 01-JUL-00:10 105.84 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 25.83 25-JUL-15:55 48.59 10-JUL-14:00
August 0.00 01-AUG-00:10 105.84 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 19.59 04-AUG-16:11 57.36 06-AUG-05:55
September 0.00 01-SEP-00:10 105.84 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 23.50 06-SEP-14:00 88.12 18-SEP-22:55
October 0.00 01-OCT-00:10 105.84 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 6.04 20-OCT-15:00 135.94 24-OCT-05:55
November 0.00 01-NOV-00:10 105.84 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 264.59 20-NOV-22:00
December 0.00 01-DEC-00:10 105.84 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 411.35 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   105.84   0.00   0.00 0.00 0.00 0.00 0.00   48.59  
Maximum of Months 0.00   105.84   0.00   0.00 0.00 0.00 0.00 69.64   411.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONTSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 8.98 01-JAN-08:09 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 60.24 18-JAN-20:00
February 0.00 01-FEB-00:10 8.98 01-FEB-08:09 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 39.16 01-FEB-21:00
March 0.00 01-MAR-00:10 8.98 01-MAR-08:09 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 35.74 06-MAR-08:00
April 0.00 01-APR-00:10 8.98 01-APR-07:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 8.84 15-APR-15:00 28.65 25-APR-05:55
May 0.00 01-MAY-00:10 8.98 01-MAY-07:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 3.92 05-MAY-15:00 16.17 01-MAY-24:00
June 0.00 01-JUN-00:10 8.98 01-JUN-07:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 7.39 18-JUN-15:55 14.62 02-JUN-05:00
July 0.00 01-JUL-00:10 8.98 01-JUL-07:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 3.85 25-JUL-15:55 7.87 10-JUL-14:00
August 0.00 01-AUG-00:10 8.98 01-AUG-07:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 3.39 04-AUG-16:21 8.56 06-AUG-05:55
September 0.00 01-SEP-00:10 8.98 01-SEP-07:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 3.60 06-SEP-14:00 13.49 18-SEP-22:55
October 0.00 01-OCT-00:10 8.98 01-OCT-07:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.27 20-OCT-15:00 22.08 24-OCT-05:55
November 0.00 01-NOV-00:10 8.98 01-NOV-07:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 43.82 20-NOV-22:00
December 0.00 01-DEC-00:10 8.98 01-DEC-08:09 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 69.07 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   8.98   0.00   0.00 0.00 0.00 0.00 0.00   7.87  
Maximum of Months 0.00   8.98   0.00   0.00 0.00 0.00 0.00 8.84   69.07  



Table of Contents

Report: PeakSpaceGainsMonthly

For: REARSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 105.87 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 378.09 18-JAN-20:00
February 0.00 01-FEB-00:10 105.87 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 267.73 01-FEB-21:00
March 0.00 01-MAR-00:10 105.87 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 235.55 06-MAR-08:00
April 0.00 01-APR-00:10 105.87 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 38.91 15-APR-15:00 191.45 25-APR-05:55
May 0.00 01-MAY-00:10 105.87 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 12.86 31-MAY-13:00 112.19 01-MAY-24:00
June 0.00 01-JUN-00:10 105.87 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 41.17 18-JUN-15:55 95.05 02-JUN-05:00
July 0.00 01-JUL-00:10 105.87 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 17.06 25-JUL-16:00 53.12 10-JUL-14:00
August 0.00 01-AUG-00:10 105.87 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 18.17 04-AUG-16:20 57.45 06-AUG-05:55
September 0.00 01-SEP-00:10 105.87 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 18.80 06-SEP-14:00 88.49 18-SEP-22:55
October 0.00 01-OCT-00:10 105.87 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 140.25 24-OCT-05:55
November 0.00 01-NOV-00:10 105.87 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 278.19 20-NOV-22:00
December 0.00 01-DEC-00:10 105.87 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 432.83 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   105.87   0.00   0.00 0.00 0.00 0.00 0.00   53.12  
Maximum of Months 0.00   105.87   0.00   0.00 0.00 0.00 0.00 41.17   432.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDORFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 415.13 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 309.12 18-JAN-20:00
February 0.00 01-FEB-00:10 415.13 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 209.12 04-FEB-22:55
March 0.00 01-MAR-00:10 415.13 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 191.49 06-MAR-08:00
April 0.00 01-APR-00:10 415.13 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 33.45 15-APR-15:00 149.55 25-APR-05:55
May 0.00 01-MAY-00:10 415.13 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 15.01 31-MAY-13:00 86.65 01-MAY-08:53
June 0.00 01-JUN-00:10 415.13 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 38.53 18-JUN-15:55 68.64 02-JUN-05:00
July 0.00 01-JUL-00:10 415.13 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 23.75 25-JUL-15:55 33.55 10-JUL-14:00
August 0.00 01-AUG-00:10 415.13 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 23.15 04-AUG-16:33 34.64 06-AUG-06:20
September 0.00 01-SEP-00:10 415.13 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 20.79 11-SEP-15:00 60.51 27-SEP-10:00
October 0.00 01-OCT-00:10 415.13 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 103.59 24-OCT-05:55
November 0.00 01-NOV-00:10 415.13 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 212.52 20-NOV-22:00
December 0.00 01-DEC-00:10 415.13 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 351.08 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   415.13   0.00   0.00 0.00 0.00 0.00 0.00   33.55  
Maximum of Months 0.00   415.13   0.00   0.00 0.00 0.00 0.00 38.53   351.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: REARSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 14.37 01-JAN-08:09 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 358.11 18-JAN-17:52
February 0.00 01-FEB-00:10 14.37 01-FEB-08:09 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 256.64 01-FEB-21:00
March 0.00 01-MAR-00:10 14.37 01-MAR-08:09 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 220.93 06-MAR-08:00
April 0.00 01-APR-00:10 14.37 01-APR-07:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 50.69 15-APR-15:00 178.44 25-APR-05:55
May 0.00 01-MAY-00:10 14.37 01-MAY-07:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 23.34 05-MAY-15:00 101.60 01-MAY-24:00
June 0.00 01-JUN-00:10 14.37 01-JUN-07:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 48.34 18-JUN-15:55 86.62 02-JUN-05:00
July 0.00 01-JUL-00:10 14.37 01-JUL-07:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 24.58 25-JUL-16:00 46.40 10-JUL-14:00
August 0.00 01-AUG-00:10 14.37 01-AUG-07:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 23.54 03-AUG-15:55 52.57 06-AUG-05:55
September 0.00 01-SEP-00:10 14.37 01-SEP-07:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 24.30 06-SEP-14:00 82.02 18-SEP-22:55
October 0.00 01-OCT-00:10 14.37 01-OCT-07:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 2.46 20-OCT-15:00 128.44 24-OCT-05:55
November 0.00 01-NOV-00:10 14.37 01-NOV-07:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 258.28 20-NOV-22:00
December 0.00 01-DEC-00:10 14.37 01-DEC-08:09 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 412.86 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   14.37   0.00   0.00 0.00 0.00 0.00 0.00   46.40  
Maximum of Months 0.00   14.37   0.00   0.00 0.00 0.00 0.00 50.69   412.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM201

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 120.47 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 82.97 01-FEB-21:00
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 73.53 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 10.73 15-APR-14:00 62.64 25-APR-05:55
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 4.72 31-MAY-13:00 34.89 01-MAY-09:00
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 12.15 11-JUN-15:00 28.97 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 5.55 25-JUL-15:55 16.45 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 6.63 04-AUG-16:12 16.97 06-AUG-05:55
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 7.12 06-SEP-14:00 26.02 18-SEP-22:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 41.84 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 86.56 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 139.41 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   16.45  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 12.15   139.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM202_205

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 792.00 01-JAN-00:10 396.93 01-JAN-19:10 1396.30 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 182.66 18-JAN-20:00
February 792.00 01-FEB-00:10 396.93 01-FEB-20:10 1396.30 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 123.57 04-FEB-22:55
March 792.00 01-MAR-00:10 396.93 01-MAR-20:10 1396.30 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 113.15 06-MAR-08:00
April 792.00 01-APR-00:10 396.93 01-APR-18:10 1396.30 01-APR-07:10 0.00 0.00 0.00 0.00 27.74 15-APR-16:52 83.77 25-APR-06:00
May 792.00 01-MAY-00:10 396.93 01-MAY-19:10 1396.30 01-MAY-06:10 0.00 0.00 0.00 0.00 16.26 05-MAY-15:06 46.76 01-MAY-07:55
June 792.00 01-JUN-00:10 396.93 01-JUN-19:10 1396.30 01-JUN-06:10 0.00 0.00 0.00 0.00 30.40 18-JUN-16:00 34.40 02-JUN-05:00
July 792.00 01-JUL-00:10 396.93 01-JUL-18:10 1396.30 01-JUL-07:10 0.00 0.00 0.00 0.00 21.14 25-JUL-16:00 18.84 09-JUL-21:00
August 792.00 01-AUG-00:10 396.93 01-AUG-19:10 1396.30 01-AUG-06:10 0.00 0.00 0.00 0.00 19.92 04-AUG-16:52 19.11 06-AUG-07:10
September 792.00 01-SEP-00:10 396.93 01-SEP-19:10 1396.30 01-SEP-06:10 0.00 0.00 0.00 0.00 19.82 11-SEP-15:06 33.47 27-SEP-08:00
October 792.00 01-OCT-00:10 396.93 01-OCT-18:10 1396.30 01-OCT-07:10 0.00 0.00 0.00 0.00 3.14 20-OCT-15:05 57.91 24-OCT-07:50
November 792.00 01-NOV-00:10 396.93 01-NOV-19:10 1396.30 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 124.41 20-NOV-22:00
December 792.00 01-DEC-00:10 396.93 01-DEC-20:10 1396.30 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 207.46 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 792.00   396.93   1396.30   0.00 0.00 0.00 0.00 0.00   18.84  
Maximum of Months 792.00   396.93   1396.30   0.00 0.00 0.00 0.00 30.40   207.46  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM206_208

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 594.00 01-JAN-00:10 320.60 01-JAN-19:10 1127.78 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 147.54 18-JAN-20:00
February 594.00 01-FEB-00:10 320.60 01-FEB-20:10 1127.78 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 99.81 04-FEB-22:55
March 594.00 01-MAR-00:10 320.60 01-MAR-20:10 1127.78 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 91.39 06-MAR-08:00
April 594.00 01-APR-00:10 320.60 01-APR-18:10 1127.78 01-APR-07:10 0.00 0.00 0.00 0.00 22.41 15-APR-16:52 67.66 25-APR-06:00
May 594.00 01-MAY-00:10 320.60 01-MAY-19:10 1127.78 01-MAY-06:10 0.00 0.00 0.00 0.00 13.14 05-MAY-15:06 37.77 01-MAY-07:55
June 594.00 01-JUN-00:10 320.60 01-JUN-19:10 1127.78 01-JUN-06:10 0.00 0.00 0.00 0.00 24.55 18-JUN-16:00 27.78 02-JUN-05:00
July 594.00 01-JUL-00:10 320.60 01-JUL-18:10 1127.78 01-JUL-07:10 0.00 0.00 0.00 0.00 17.07 25-JUL-16:00 15.13 09-JUL-21:00
August 594.00 01-AUG-00:10 320.60 01-AUG-19:10 1127.78 01-AUG-06:10 0.00 0.00 0.00 0.00 16.09 04-AUG-16:52 15.43 06-AUG-07:10
September 594.00 01-SEP-00:10 320.60 01-SEP-19:10 1127.78 01-SEP-06:10 0.00 0.00 0.00 0.00 16.01 11-SEP-15:06 27.04 27-SEP-08:00
October 594.00 01-OCT-00:10 320.60 01-OCT-18:10 1127.78 01-OCT-07:10 0.00 0.00 0.00 0.00 2.53 20-OCT-15:05 47.03 24-OCT-07:50
November 594.00 01-NOV-00:10 320.60 01-NOV-19:10 1127.78 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 100.49 20-NOV-22:00
December 594.00 01-DEC-00:10 320.60 01-DEC-20:10 1127.78 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 167.56 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 594.00   320.60   1127.78   0.00 0.00 0.00 0.00 0.00   15.13  
Maximum of Months 594.00   320.60   1127.78   0.00 0.00 0.00 0.00 24.55   167.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM209_212

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 792.00 01-JAN-00:10 396.93 01-JAN-19:10 1396.30 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 182.66 18-JAN-20:00
February 792.00 01-FEB-00:10 396.93 01-FEB-20:10 1396.30 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 123.57 04-FEB-22:55
March 792.00 01-MAR-00:10 396.93 01-MAR-20:10 1396.30 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 113.15 06-MAR-08:00
April 792.00 01-APR-00:10 396.93 01-APR-18:10 1396.30 01-APR-07:10 0.00 0.00 0.00 0.00 27.74 15-APR-16:52 83.77 25-APR-06:00
May 792.00 01-MAY-00:10 396.93 01-MAY-19:10 1396.30 01-MAY-06:10 0.00 0.00 0.00 0.00 16.26 05-MAY-15:06 46.76 01-MAY-07:55
June 792.00 01-JUN-00:10 396.93 01-JUN-19:10 1396.30 01-JUN-06:10 0.00 0.00 0.00 0.00 30.40 18-JUN-16:00 34.40 02-JUN-05:00
July 792.00 01-JUL-00:10 396.93 01-JUL-18:10 1396.30 01-JUL-07:10 0.00 0.00 0.00 0.00 21.14 25-JUL-16:00 18.45 09-JUL-21:00
August 792.00 01-AUG-00:10 396.93 01-AUG-19:10 1396.30 01-AUG-06:10 0.00 0.00 0.00 0.00 19.92 04-AUG-16:52 19.11 06-AUG-07:10
September 792.00 01-SEP-00:10 396.93 01-SEP-19:10 1396.30 01-SEP-06:10 0.00 0.00 0.00 0.00 19.83 11-SEP-15:06 33.47 27-SEP-08:00
October 792.00 01-OCT-00:10 396.93 01-OCT-18:10 1396.30 01-OCT-07:10 0.00 0.00 0.00 0.00 3.14 20-OCT-15:05 58.79 24-OCT-07:50
November 792.00 01-NOV-00:10 396.93 01-NOV-19:10 1396.30 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 124.41 20-NOV-22:00
December 792.00 01-DEC-00:10 396.93 01-DEC-20:10 1396.30 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 207.46 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 792.00   396.93   1396.30   0.00 0.00 0.00 0.00 0.00   18.45  
Maximum of Months 792.00   396.93   1396.30   0.00 0.00 0.00 0.00 30.40   207.46  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM213

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 198.00 01-JAN-00:10 99.23 01-JAN-19:10 349.07 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 45.67 18-JAN-20:00
February 198.00 01-FEB-00:10 99.23 01-FEB-20:10 349.07 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 30.89 04-FEB-22:55
March 198.00 01-MAR-00:10 99.23 01-MAR-20:10 349.07 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 28.29 06-MAR-08:00
April 198.00 01-APR-00:10 99.23 01-APR-18:10 349.07 01-APR-07:10 0.00 0.00 0.00 0.00 6.94 15-APR-16:52 20.94 25-APR-06:00
May 198.00 01-MAY-00:10 99.23 01-MAY-19:10 349.07 01-MAY-06:10 0.00 0.00 0.00 0.00 4.07 05-MAY-15:06 11.18 02-MAY-03:00
June 198.00 01-JUN-00:10 99.23 01-JUN-19:10 349.07 01-JUN-06:10 0.00 0.00 0.00 0.00 7.60 18-JUN-16:00 8.60 02-JUN-05:00
July 198.00 01-JUL-00:10 99.23 01-JUL-18:10 349.07 01-JUL-07:10 0.00 0.00 0.00 0.00 5.28 25-JUL-16:00 4.60 10-JUL-14:00
August 198.00 01-AUG-00:10 99.23 01-AUG-19:10 349.07 01-AUG-06:10 0.00 0.00 0.00 0.00 4.98 04-AUG-16:52 4.78 06-AUG-07:10
September 198.00 01-SEP-00:10 99.23 01-SEP-19:10 349.07 01-SEP-06:10 0.00 0.00 0.00 0.00 4.96 11-SEP-15:06 7.97 27-SEP-08:00
October 198.00 01-OCT-00:10 99.23 01-OCT-18:10 349.07 01-OCT-07:10 0.00 0.00 0.00 0.00 0.78 20-OCT-15:05 14.44 24-OCT-06:00
November 198.00 01-NOV-00:10 99.23 01-NOV-19:10 349.07 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 31.10 20-NOV-22:00
December 198.00 01-DEC-00:10 99.23 01-DEC-20:10 349.07 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 51.86 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 198.00   99.23   349.07   0.00 0.00 0.00 0.00 0.00   4.60  
Maximum of Months 198.00   99.23   349.07   0.00 0.00 0.00 0.00 7.60   51.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM214

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 198.00 01-JAN-00:10 99.23 01-JAN-19:10 349.05 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 45.67 18-JAN-20:00
February 198.00 01-FEB-00:10 99.23 01-FEB-20:10 349.05 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 30.89 04-FEB-22:55
March 198.00 01-MAR-00:10 99.23 01-MAR-20:10 349.05 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 28.29 06-MAR-08:00
April 198.00 01-APR-00:10 99.23 01-APR-18:10 349.05 01-APR-07:10 0.00 0.00 0.00 0.00 6.94 15-APR-16:52 20.94 25-APR-06:00
May 198.00 01-MAY-00:10 99.23 01-MAY-19:10 349.05 01-MAY-06:10 0.00 0.00 0.00 0.00 4.07 05-MAY-15:06 11.69 01-MAY-07:55
June 198.00 01-JUN-00:10 99.23 01-JUN-19:10 349.05 01-JUN-06:10 0.00 0.00 0.00 0.00 7.60 18-JUN-16:00 8.60 02-JUN-05:00
July 198.00 01-JUL-00:10 99.23 01-JUL-18:10 349.05 01-JUL-07:10 0.00 0.00 0.00 0.00 5.28 25-JUL-16:00 4.60 10-JUL-14:00
August 198.00 01-AUG-00:10 99.23 01-AUG-19:10 349.05 01-AUG-06:10 0.00 0.00 0.00 0.00 4.98 04-AUG-16:52 4.78 06-AUG-07:10
September 198.00 01-SEP-00:10 99.23 01-SEP-19:10 349.05 01-SEP-06:10 0.00 0.00 0.00 0.00 4.96 11-SEP-15:06 8.37 27-SEP-08:00
October 198.00 01-OCT-00:10 99.23 01-OCT-18:10 349.05 01-OCT-07:10 0.00 0.00 0.00 0.00 0.78 20-OCT-15:06 14.85 24-OCT-07:50
November 198.00 01-NOV-00:10 99.23 01-NOV-19:10 349.05 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 31.10 20-NOV-22:00
December 198.00 01-DEC-00:10 99.23 01-DEC-20:10 349.05 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 51.86 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 0.00   4.60  
Maximum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 7.60   51.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM215_218

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 208.73 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 141.28 10-FEB-22:00
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 131.57 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 10.75 15-APR-15:00 107.00 25-APR-05:55
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 4.83 31-MAY-13:00 62.20 01-MAY-09:00
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 15.79 11-JUN-15:00 48.12 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 6.93 25-JUL-16:00 26.88 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 8.61 04-AUG-16:12 26.15 06-AUG-05:55
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 8.04 06-SEP-14:00 44.69 27-SEP-09:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 74.70 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 150.27 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 233.69 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   26.15  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 15.79   233.69  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ELEVATORCOREFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 100.75 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 72.78 10-FEB-22:00
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 62.63 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 54.72 25-APR-05:55
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 35.10 01-MAY-09:00
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.32 11-JUN-15:00 26.97 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 01-JUL-00:10 19.05 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.43 04-AUG-16:00 17.29 04-AUG-19:00
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 25.40 27-SEP-09:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 38.59 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 76.95 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 110.65 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   17.29  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.43   110.65  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM219

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 198.00 01-JAN-00:10 99.23 01-JAN-19:10 349.05 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 46.03 18-JAN-18:08
February 198.00 01-FEB-00:10 99.23 01-FEB-20:10 349.05 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 37.40 01-FEB-21:00
March 198.00 01-MAR-00:10 99.23 01-MAR-20:10 349.05 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 29.37 06-MAR-08:08
April 198.00 01-APR-00:10 99.23 01-APR-18:10 349.05 01-APR-07:10 0.00 0.00 0.00 0.00 6.94 15-APR-16:52 20.94 25-APR-06:00
May 198.00 01-MAY-00:10 99.23 01-MAY-19:10 349.05 01-MAY-06:10 0.00 0.00 0.00 0.00 4.07 05-MAY-15:10 11.73 01-MAY-10:09
June 198.00 01-JUN-00:10 99.23 01-JUN-19:10 349.05 01-JUN-06:10 0.00 0.00 0.00 0.00 7.60 18-JUN-16:00 8.60 02-JUN-05:00
July 198.00 01-JUL-00:10 99.23 01-JUL-18:10 349.05 01-JUL-07:10 0.00 0.00 0.00 0.00 5.28 25-JUL-16:00 7.45 10-JUL-15:40
August 198.00 01-AUG-00:10 99.23 01-AUG-19:10 349.05 01-AUG-06:10 0.00 0.00 0.00 0.00 4.98 04-AUG-16:54 7.63 19-AUG-06:20
September 198.00 01-SEP-00:10 99.23 01-SEP-19:10 349.05 01-SEP-06:10 0.00 0.00 0.00 0.00 4.96 11-SEP-15:10 9.32 24-SEP-15:30
October 198.00 01-OCT-00:10 99.23 01-OCT-18:10 349.05 01-OCT-07:10 0.00 0.00 0.00 0.00 0.78 20-OCT-15:09 15.35 24-OCT-07:09
November 198.00 01-NOV-00:10 99.23 01-NOV-19:10 349.05 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 31.10 20-NOV-22:00
December 198.00 01-DEC-00:10 99.23 01-DEC-20:10 349.05 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 51.86 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 0.00   7.45  
Maximum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 7.60   51.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM220_223

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 792.00 01-JAN-00:10 396.90 01-JAN-19:10 1396.20 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 182.66 18-JAN-20:00
February 792.00 01-FEB-00:10 396.90 01-FEB-20:10 1396.20 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 123.57 04-FEB-23:00
March 792.00 01-MAR-00:10 396.90 01-MAR-20:10 1396.20 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 113.15 06-MAR-08:00
April 792.00 01-APR-00:10 396.90 01-APR-18:10 1396.20 01-APR-07:10 0.00 0.00 0.00 0.00 27.74 15-APR-16:52 83.77 25-APR-06:00
May 792.00 01-MAY-00:10 396.90 01-MAY-19:10 1396.20 01-MAY-06:10 0.00 0.00 0.00 0.00 16.26 05-MAY-15:06 46.76 01-MAY-07:55
June 792.00 01-JUN-00:10 396.90 01-JUN-19:10 1396.20 01-JUN-06:10 0.00 0.00 0.00 0.00 30.40 18-JUN-16:00 34.40 02-JUN-05:00
July 792.00 01-JUL-00:10 396.90 01-JUL-18:10 1396.20 01-JUL-07:10 0.00 0.00 0.00 0.00 21.14 25-JUL-16:00 18.41 10-JUL-14:00
August 792.00 01-AUG-00:10 396.90 01-AUG-19:10 1396.20 01-AUG-06:10 0.00 0.00 0.00 0.00 19.92 04-AUG-16:52 19.10 06-AUG-07:10
September 792.00 01-SEP-00:10 396.90 01-SEP-19:10 1396.20 01-SEP-06:10 0.00 0.00 0.00 0.00 19.82 11-SEP-15:06 33.47 27-SEP-08:00
October 792.00 01-OCT-00:10 396.90 01-OCT-18:10 1396.20 01-OCT-07:10 0.00 0.00 0.00 0.00 3.14 20-OCT-15:05 59.41 24-OCT-07:50
November 792.00 01-NOV-00:10 396.90 01-NOV-19:10 1396.20 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 124.41 20-NOV-22:00
December 792.00 01-DEC-00:10 396.90 01-DEC-20:10 1396.20 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 207.46 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 792.00   396.90   1396.20   0.00 0.00 0.00 0.00 0.00   18.41  
Maximum of Months 792.00   396.90   1396.20   0.00 0.00 0.00 0.00 30.40   207.46  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM224

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 198.00 01-JAN-00:10 99.23 01-JAN-19:10 349.05 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 45.67 18-JAN-20:00
February 198.00 01-FEB-00:10 99.23 01-FEB-20:10 349.05 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 30.89 04-FEB-22:55
March 198.00 01-MAR-00:10 99.23 01-MAR-20:10 349.05 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 28.29 06-MAR-08:00
April 198.00 01-APR-00:10 99.23 01-APR-18:10 349.05 01-APR-07:10 0.00 0.00 0.00 0.00 6.94 15-APR-16:52 20.94 25-APR-06:00
May 198.00 01-MAY-00:10 99.23 01-MAY-19:10 349.05 01-MAY-06:10 0.00 0.00 0.00 0.00 4.07 05-MAY-15:06 11.69 01-MAY-07:55
June 198.00 01-JUN-00:10 99.23 01-JUN-19:10 349.05 01-JUN-06:10 0.00 0.00 0.00 0.00 7.60 18-JUN-16:00 8.60 02-JUN-05:00
July 198.00 01-JUL-00:10 99.23 01-JUL-18:10 349.05 01-JUL-07:10 0.00 0.00 0.00 0.00 5.28 25-JUL-16:00 4.60 10-JUL-14:00
August 198.00 01-AUG-00:10 99.23 01-AUG-19:10 349.05 01-AUG-06:10 0.00 0.00 0.00 0.00 4.98 04-AUG-16:52 4.78 06-AUG-07:10
September 198.00 01-SEP-00:10 99.23 01-SEP-19:10 349.05 01-SEP-06:10 0.00 0.00 0.00 0.00 4.96 11-SEP-15:06 8.36 27-SEP-08:00
October 198.00 01-OCT-00:10 99.23 01-OCT-18:10 349.05 01-OCT-07:10 0.00 0.00 0.00 0.00 0.78 20-OCT-15:06 14.47 24-OCT-07:50
November 198.00 01-NOV-00:10 99.23 01-NOV-19:10 349.05 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 31.10 20-NOV-22:00
December 198.00 01-DEC-00:10 99.23 01-DEC-20:10 349.05 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 51.86 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 0.00   4.60  
Maximum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 7.60   51.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONTSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 8.98 01-JAN-08:09 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 59.94 18-JAN-20:00
February 0.00 01-FEB-00:10 8.98 01-FEB-08:09 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 39.45 01-FEB-21:00
March 0.00 01-MAR-00:10 8.98 01-MAR-08:09 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 36.30 06-MAR-08:00
April 0.00 01-APR-00:10 8.98 01-APR-07:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 8.14 15-APR-15:00 29.66 25-APR-05:55
May 0.00 01-MAY-00:10 8.98 01-MAY-07:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 3.36 05-MAY-15:00 16.90 01-MAY-09:00
June 0.00 01-JUN-00:10 8.98 01-JUN-07:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 7.22 18-JUN-16:00 14.81 02-JUN-05:00
July 0.00 01-JUL-00:10 8.98 01-JUL-07:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 3.86 25-JUL-16:00 7.96 10-JUL-14:00
August 0.00 01-AUG-00:10 8.98 01-AUG-07:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 3.57 04-AUG-16:30 8.47 06-AUG-05:55
September 0.00 01-SEP-00:10 8.98 01-SEP-07:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 3.87 06-SEP-14:00 13.30 18-SEP-22:55
October 0.00 01-OCT-00:10 8.98 01-OCT-07:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.85 20-OCT-15:00 21.25 24-OCT-05:55
November 0.00 01-NOV-00:10 8.98 01-NOV-07:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 43.18 20-NOV-22:00
December 0.00 01-DEC-00:10 8.98 01-DEC-08:09 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 68.24 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   8.98   0.00   0.00 0.00 0.00 0.00 0.00   7.96  
Maximum of Months 0.00   8.98   0.00   0.00 0.00 0.00 0.00 8.14   68.24  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONTSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 105.84 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 349.97 18-JAN-17:52
February 0.00 01-FEB-00:10 105.84 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 235.84 01-FEB-21:00
March 0.00 01-MAR-00:10 105.84 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 208.20 06-MAR-08:00
April 0.00 01-APR-00:10 105.84 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 53.01 15-APR-15:00 176.53 25-APR-05:55
May 0.00 01-MAY-00:10 105.84 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 21.52 05-MAY-15:00 104.09 01-MAY-24:00
June 0.00 01-JUN-00:10 105.84 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 40.93 18-JUN-15:55 96.81 02-JUN-05:00
July 0.00 01-JUL-00:10 105.84 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 19.29 25-JUL-15:55 53.85 10-JUL-14:00
August 0.00 01-AUG-00:10 105.84 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 17.15 04-AUG-16:01 60.54 06-AUG-05:55
September 0.00 01-SEP-00:10 105.84 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 23.58 06-SEP-14:00 89.46 18-SEP-22:55
October 0.00 01-OCT-00:10 105.84 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 8.73 20-OCT-15:00 130.00 24-OCT-05:55
November 0.00 01-NOV-00:10 105.84 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 257.38 20-NOV-22:00
December 0.00 01-DEC-00:10 105.84 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 398.46 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   105.84   0.00   0.00 0.00 0.00 0.00 0.00   53.85  
Maximum of Months 0.00   105.84   0.00   0.00 0.00 0.00 0.00 53.01   398.46  



Table of Contents

Report: PeakSpaceGainsMonthly

For: REARSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 105.87 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 399.19 18-JAN-17:52
February 0.00 01-FEB-00:10 105.87 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 287.12 01-FEB-21:00
March 0.00 01-MAR-00:10 105.87 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 249.80 06-MAR-08:00
April 0.00 01-APR-00:10 105.87 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 38.86 15-APR-15:00 205.69 25-APR-05:55
May 0.00 01-MAY-00:10 105.87 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 12.07 31-MAY-13:00 122.91 01-MAY-08:53
June 0.00 01-JUN-00:10 105.87 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 42.35 18-JUN-15:55 102.97 02-JUN-05:00
July 0.00 01-JUL-00:10 105.87 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 16.15 25-JUL-16:00 58.03 10-JUL-14:00
August 0.00 01-AUG-00:10 105.87 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 18.18 04-AUG-16:01 64.58 04-AUG-18:51
September 0.00 01-SEP-00:10 105.87 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 20.43 06-SEP-14:00 96.04 18-SEP-22:55
October 0.00 01-OCT-00:10 105.87 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 145.85 24-OCT-05:55
November 0.00 01-NOV-00:10 105.87 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 292.80 20-NOV-22:00
December 0.00 01-DEC-00:10 105.87 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 454.99 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   105.87   0.00   0.00 0.00 0.00 0.00 0.00   58.03  
Maximum of Months 0.00   105.87   0.00   0.00 0.00 0.00 0.00 42.35   454.99  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDORFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 415.13 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 342.06 18-JAN-20:00
February 0.00 01-FEB-00:10 415.13 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 231.40 04-FEB-22:55
March 0.00 01-MAR-00:10 415.13 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 211.90 06-MAR-08:00
April 0.00 01-APR-00:10 415.13 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 36.89 15-APR-15:00 156.93 25-APR-05:55
May 0.00 01-MAY-00:10 415.13 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 16.56 31-MAY-13:00 86.76 01-MAY-08:53
June 0.00 01-JUN-00:10 415.13 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 42.46 18-JUN-16:00 69.54 02-JUN-05:00
July 0.00 01-JUL-00:10 415.13 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 25.71 25-JUL-16:00 37.20 10-JUL-14:00
August 0.00 01-AUG-00:10 415.13 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 23.83 04-AUG-16:40 38.38 06-AUG-06:01
September 0.00 01-SEP-00:10 415.13 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 22.90 11-SEP-15:00 61.91 18-SEP-22:55
October 0.00 01-OCT-00:10 415.13 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 108.20 24-OCT-05:55
November 0.00 01-NOV-00:10 415.13 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 233.03 20-NOV-22:00
December 0.00 01-DEC-00:10 415.13 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 388.47 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   415.13   0.00   0.00 0.00 0.00 0.00 0.00   37.20  
Maximum of Months 0.00   415.13   0.00   0.00 0.00 0.00 0.00 42.46   388.47  



Table of Contents

Report: PeakSpaceGainsMonthly

For: REARSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 14.37 01-JAN-08:09 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 369.18 18-JAN-17:52
February 0.00 01-FEB-00:10 14.37 01-FEB-08:09 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 268.18 01-FEB-21:00
March 0.00 01-MAR-00:10 14.37 01-MAR-08:09 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 226.10 06-MAR-08:00
April 0.00 01-APR-00:10 14.37 01-APR-07:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 51.85 15-APR-15:00 190.62 25-APR-05:55
May 0.00 01-MAY-00:10 14.37 01-MAY-07:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 22.01 05-MAY-15:00 110.14 01-MAY-24:00
June 0.00 01-JUN-00:10 14.37 01-JUN-07:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 48.03 18-JUN-15:55 94.23 02-JUN-05:00
July 0.00 01-JUL-00:10 14.37 01-JUL-07:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 22.65 25-JUL-15:55 50.81 10-JUL-14:00
August 0.00 01-AUG-00:10 14.37 01-AUG-07:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 22.16 04-AUG-12:00 61.00 06-AUG-05:55
September 0.00 01-SEP-00:10 14.37 01-SEP-07:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 26.23 06-SEP-14:00 90.09 18-SEP-22:55
October 0.00 01-OCT-00:10 14.37 01-OCT-07:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 6.73 20-OCT-15:00 130.52 24-OCT-05:55
November 0.00 01-NOV-00:10 14.37 01-NOV-07:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 264.82 20-NOV-22:00
December 0.00 01-DEC-00:10 14.37 01-DEC-08:09 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 420.91 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   14.37   0.00   0.00 0.00 0.00 0.00 0.00   50.81  
Maximum of Months 0.00   14.37   0.00   0.00 0.00 0.00 0.00 51.85   420.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM301

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 133.31 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 91.81 01-FEB-21:00
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 80.28 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 13.05 15-APR-14:00 65.61 25-APR-05:55
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 5.50 31-MAY-13:00 36.06 01-MAY-24:00
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 13.40 11-JUN-15:00 30.48 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 6.38 25-JUL-15:55 17.09 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 7.31 04-AUG-16:12 18.44 06-AUG-05:55
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 8.44 06-SEP-14:00 27.74 18-SEP-22:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 1.93 20-OCT-14:00 42.45 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 89.43 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 154.27 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   17.09  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 13.40   154.27  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM302_305

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 175.35 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 119.35 01-FEB-21:00
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 108.48 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 16.27 15-APR-14:00 91.95 25-APR-05:55
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 6.88 31-MAY-13:00 50.22 01-MAY-09:00
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 17.42 11-JUN-15:00 41.90 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 7.94 25-JUL-15:55 23.46 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 9.50 04-AUG-16:12 25.23 06-AUG-05:55
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 10.52 06-SEP-14:00 38.02 18-SEP-22:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 1.38 20-OCT-14:00 59.56 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 123.76 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 200.54 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   23.46  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 17.42   200.54  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM306_308

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 143.35 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 96.80 01-FEB-21:00
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 89.22 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 12.41 15-APR-14:00 75.09 25-APR-05:55
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 5.55 31-MAY-13:00 41.28 01-MAY-09:00
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 14.07 11-JUN-15:00 33.68 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 6.38 25-JUL-15:55 18.95 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 7.67 04-AUG-16:12 20.09 06-AUG-05:55
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 8.34 06-SEP-14:00 30.56 18-SEP-22:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.50 20-OCT-14:00 48.72 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 101.75 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 163.79 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   18.95  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 14.07   163.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM309_312

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 792.00 01-JAN-00:10 396.93 01-JAN-19:10 1396.30 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 202.13 18-JAN-20:00
February 792.00 01-FEB-00:10 396.93 01-FEB-20:10 1396.30 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 136.74 04-FEB-22:55
March 792.00 01-MAR-00:10 396.93 01-MAR-20:10 1396.30 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 125.22 06-MAR-08:00
April 792.00 01-APR-00:10 396.93 01-APR-18:10 1396.30 01-APR-07:10 0.00 0.00 0.00 0.00 30.62 15-APR-16:52 92.73 25-APR-06:00
May 792.00 01-MAY-00:10 396.93 01-MAY-19:10 1396.30 01-MAY-06:10 0.00 0.00 0.00 0.00 17.93 05-MAY-15:06 51.69 01-MAY-08:00
June 792.00 01-JUN-00:10 396.93 01-JUN-19:10 1396.30 01-JUN-06:10 0.00 0.00 0.00 0.00 33.57 18-JUN-16:00 38.10 02-JUN-05:00
July 792.00 01-JUL-00:10 396.93 01-JUL-18:10 1396.30 01-JUL-07:10 0.00 0.00 0.00 0.00 23.33 25-JUL-16:00 20.41 10-JUL-14:00
August 792.00 01-AUG-00:10 396.93 01-AUG-19:10 1396.30 01-AUG-06:10 0.00 0.00 0.00 0.00 21.98 04-AUG-16:52 21.17 06-AUG-07:10
September 792.00 01-SEP-00:10 396.93 01-SEP-19:10 1396.30 01-SEP-06:10 0.00 0.00 0.00 0.00 21.87 11-SEP-15:06 36.09 27-SEP-08:00
October 792.00 01-OCT-00:10 396.93 01-OCT-18:10 1396.30 01-OCT-07:10 0.00 0.00 0.00 0.00 3.44 20-OCT-15:06 63.93 24-OCT-06:00
November 792.00 01-NOV-00:10 396.93 01-NOV-19:10 1396.30 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 137.70 20-NOV-22:00
December 792.00 01-DEC-00:10 396.93 01-DEC-20:10 1396.30 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 229.55 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 792.00   396.93   1396.30   0.00 0.00 0.00 0.00 0.00   20.41  
Maximum of Months 792.00   396.93   1396.30   0.00 0.00 0.00 0.00 33.57   229.55  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM313

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 43.32 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 29.84 01-FEB-21:00
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 26.68 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 4.63 15-APR-14:00 21.88 25-APR-05:55
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 2.01 31-MAY-13:00 12.03 01-MAY-08:53
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 4.63 18-JUN-15:55 9.98 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 2.54 25-JUL-16:00 5.44 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 2.54 04-AUG-12:00 5.94 06-AUG-05:55
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 2.84 06-SEP-14:00 9.18 18-SEP-22:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.46 20-OCT-14:00 14.62 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 30.56 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 50.13 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   5.44  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 4.63   50.13  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM314

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 198.00 01-JAN-00:10 99.23 01-JAN-19:10 349.05 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 50.53 18-JAN-20:00
February 198.00 01-FEB-00:10 99.23 01-FEB-20:10 349.05 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 34.19 04-FEB-22:55
March 198.00 01-MAR-00:10 99.23 01-MAR-20:10 349.05 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 31.30 06-MAR-08:00
April 198.00 01-APR-00:10 99.23 01-APR-18:10 349.05 01-APR-07:10 0.00 0.00 0.00 0.00 7.66 15-APR-16:52 23.18 25-APR-06:00
May 198.00 01-MAY-00:10 99.23 01-MAY-19:10 349.05 01-MAY-06:10 0.00 0.00 0.00 0.00 4.48 05-MAY-15:06 12.94 01-MAY-07:55
June 198.00 01-JUN-00:10 99.23 01-JUN-19:10 349.05 01-JUN-06:10 0.00 0.00 0.00 0.00 8.39 18-JUN-16:00 9.52 02-JUN-05:00
July 198.00 01-JUL-00:10 99.23 01-JUL-18:10 349.05 01-JUL-07:10 0.00 0.00 0.00 0.00 5.83 25-JUL-16:00 5.10 10-JUL-14:00
August 198.00 01-AUG-00:10 99.23 01-AUG-19:10 349.05 01-AUG-06:10 0.00 0.00 0.00 0.00 5.50 04-AUG-16:52 5.29 06-AUG-07:10
September 198.00 01-SEP-00:10 99.23 01-SEP-19:10 349.05 01-SEP-06:10 0.00 0.00 0.00 0.00 5.47 11-SEP-15:06 8.83 27-SEP-08:00
October 198.00 01-OCT-00:10 99.23 01-OCT-18:10 349.05 01-OCT-07:10 0.00 0.00 0.00 0.00 0.86 20-OCT-15:05 15.98 24-OCT-06:00
November 198.00 01-NOV-00:10 99.23 01-NOV-19:10 349.05 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 34.42 20-NOV-22:00
December 198.00 01-DEC-00:10 99.23 01-DEC-20:10 349.05 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 57.39 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 0.00   5.10  
Maximum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 8.39   57.39  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM315_318

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 792.00 01-JAN-00:10 396.90 01-JAN-19:10 1396.20 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 202.13 18-JAN-20:00
February 792.00 01-FEB-00:10 396.90 01-FEB-20:10 1396.20 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 136.74 04-FEB-23:00
March 792.00 01-MAR-00:10 396.90 01-MAR-20:10 1396.20 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 125.47 06-MAR-08:10
April 792.00 01-APR-00:10 396.90 01-APR-18:10 1396.20 01-APR-07:10 0.00 0.00 0.00 0.00 30.62 15-APR-16:52 92.73 25-APR-06:00
May 792.00 01-MAY-00:10 396.90 01-MAY-19:10 1396.20 01-MAY-06:10 0.00 0.00 0.00 0.00 17.93 05-MAY-15:06 51.77 01-MAY-07:55
June 792.00 01-JUN-00:10 396.90 01-JUN-19:10 1396.20 01-JUN-06:10 0.00 0.00 0.00 0.00 33.57 18-JUN-16:00 38.10 02-JUN-05:00
July 792.00 01-JUL-00:10 396.90 01-JUL-18:10 1396.20 01-JUL-07:10 0.00 0.00 0.00 0.00 23.33 25-JUL-16:00 20.41 10-JUL-14:00
August 792.00 01-AUG-00:10 396.90 01-AUG-19:10 1396.20 01-AUG-06:10 0.00 0.00 0.00 0.00 21.98 04-AUG-16:52 21.17 06-AUG-07:10
September 792.00 01-SEP-00:10 396.90 01-SEP-19:10 1396.20 01-SEP-06:10 0.00 0.00 0.00 0.00 21.87 11-SEP-15:07 37.06 27-SEP-08:00
October 792.00 01-OCT-00:10 396.90 01-OCT-18:10 1396.20 01-OCT-07:10 0.00 0.00 0.00 0.00 3.44 20-OCT-15:06 67.06 24-OCT-07:20
November 792.00 01-NOV-00:10 396.90 01-NOV-19:10 1396.20 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 137.70 20-NOV-22:00
December 792.00 01-DEC-00:10 396.90 01-DEC-20:10 1396.20 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 229.55 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 792.00   396.90   1396.20   0.00 0.00 0.00 0.00 0.00   20.41  
Maximum of Months 792.00   396.90   1396.20   0.00 0.00 0.00 0.00 33.57   229.55  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ELEVATORCOREFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 90.94 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 61.96 04-FEB-22:55
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 57.20 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 6.29 15-APR-15:00 46.93 25-APR-05:55
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 2.12 31-MAY-13:00 27.78 01-MAY-09:00
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 7.42 11-JUN-15:00 22.26 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 2.91 25-JUL-15:55 12.99 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 3.95 04-AUG-16:11 12.88 06-AUG-05:55
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 3.93 06-SEP-14:00 19.85 18-SEP-22:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 32.40 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 65.72 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 102.89 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   12.88  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 7.42   102.89  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM319

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 50.11 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 34.25 04-FEB-22:55
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 31.39 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 3.28 15-APR-17:00 25.63 25-APR-06:00
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 1.33 31-MAY-13:00 15.43 01-MAY-08:53
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 4.35 11-JUN-15:00 11.74 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 1.90 25-JUL-16:00 6.94 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 2.37 04-AUG-16:12 6.61 06-AUG-05:55
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 2.22 06-SEP-14:00 10.48 18-SEP-22:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 17.55 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 36.33 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 56.55 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   6.61  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 4.35   56.55  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM320_323

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 792.00 01-JAN-00:10 396.90 01-JAN-19:10 1396.20 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 202.13 18-JAN-20:00
February 792.00 01-FEB-00:10 396.90 01-FEB-20:10 1396.20 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 136.74 04-FEB-22:55
March 792.00 01-MAR-00:10 396.90 01-MAR-20:10 1396.20 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 125.22 06-MAR-08:00
April 792.00 01-APR-00:10 396.90 01-APR-18:10 1396.20 01-APR-07:10 0.00 0.00 0.00 0.00 30.62 15-APR-16:52 92.73 25-APR-06:00
May 792.00 01-MAY-00:10 396.90 01-MAY-19:10 1396.20 01-MAY-06:10 0.00 0.00 0.00 0.00 17.93 05-MAY-15:06 51.78 01-MAY-07:55
June 792.00 01-JUN-00:10 396.90 01-JUN-19:10 1396.20 01-JUN-06:10 0.00 0.00 0.00 0.00 33.57 18-JUN-16:00 38.10 02-JUN-05:00
July 792.00 01-JUL-00:10 396.90 01-JUL-18:10 1396.20 01-JUL-07:10 0.00 0.00 0.00 0.00 23.33 25-JUL-16:00 20.41 10-JUL-14:00
August 792.00 01-AUG-00:10 396.90 01-AUG-19:10 1396.20 01-AUG-06:10 0.00 0.00 0.00 0.00 21.98 04-AUG-16:52 21.04 06-AUG-07:10
September 792.00 01-SEP-00:10 396.90 01-SEP-19:10 1396.20 01-SEP-06:10 0.00 0.00 0.00 0.00 21.87 11-SEP-15:06 36.48 27-SEP-08:00
October 792.00 01-OCT-00:10 396.90 01-OCT-18:10 1396.20 01-OCT-07:10 0.00 0.00 0.00 0.00 3.44 20-OCT-15:05 64.07 24-OCT-07:50
November 792.00 01-NOV-00:10 396.90 01-NOV-19:10 1396.20 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 137.70 20-NOV-22:00
December 792.00 01-DEC-00:10 396.90 01-DEC-20:10 1396.20 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 229.55 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 792.00   396.90   1396.20   0.00 0.00 0.00 0.00 0.00   20.41  
Maximum of Months 792.00   396.90   1396.20   0.00 0.00 0.00 0.00 33.57   229.55  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM324

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 45.36 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 30.20 01-FEB-21:00
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 28.12 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 5.05 15-APR-17:00 22.54 25-APR-06:00
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 1.75 31-MAY-13:00 13.29 01-MAY-08:53
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 5.26 18-JUN-16:00 10.44 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 2.68 25-JUL-16:00 5.53 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 2.87 04-AUG-16:30 5.66 06-AUG-05:55
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 2.83 06-SEP-14:00 9.24 18-SEP-22:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.18 20-OCT-15:00 15.41 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 32.21 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 51.75 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   5.53  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 5.26   51.75  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONTSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 8.98 01-JAN-08:09 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 63.18 18-JAN-20:00
February 0.00 01-FEB-00:10 8.98 01-FEB-08:09 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 42.01 01-FEB-21:00
March 0.00 01-MAR-00:10 8.98 01-MAR-08:09 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 38.23 06-MAR-08:00
April 0.00 01-APR-00:10 8.98 01-APR-07:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 8.70 15-APR-15:00 31.83 25-APR-05:55
May 0.00 01-MAY-00:10 8.98 01-MAY-07:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 3.41 05-MAY-15:00 18.44 01-MAY-09:00
June 0.00 01-JUN-00:10 8.98 01-JUN-07:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 7.48 18-JUN-15:55 16.18 02-JUN-05:00
July 0.00 01-JUL-00:10 8.98 01-JUL-07:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 3.82 25-JUL-15:55 8.65 10-JUL-14:00
August 0.00 01-AUG-00:10 8.98 01-AUG-07:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 3.54 04-AUG-16:11 9.55 06-AUG-05:55
September 0.00 01-SEP-00:10 8.98 01-SEP-07:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 4.29 06-SEP-14:00 14.56 18-SEP-22:55
October 0.00 01-OCT-00:10 8.98 01-OCT-07:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 1.54 20-OCT-15:00 22.01 24-OCT-05:55
November 0.00 01-NOV-00:10 8.98 01-NOV-07:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 45.40 20-NOV-22:00
December 0.00 01-DEC-00:10 8.98 01-DEC-08:09 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 71.81 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   8.98   0.00   0.00 0.00 0.00 0.00 0.00   8.65  
Maximum of Months 0.00   8.98   0.00   0.00 0.00 0.00 0.00 8.70   71.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONTSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 105.84 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 369.40 18-JAN-17:52
February 0.00 01-FEB-00:10 105.84 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 260.98 01-FEB-21:00
March 0.00 01-MAR-00:10 105.84 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 2.26 25-MAR-15:00 222.35 21-MAR-01:00
April 0.00 01-APR-00:10 105.84 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 53.51 15-APR-15:00 190.43 25-APR-05:55
May 0.00 01-MAY-00:10 105.84 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 19.54 05-MAY-15:00 114.32 01-MAY-24:00
June 0.00 01-JUN-00:10 105.84 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 41.67 18-JUN-15:55 105.35 02-JUN-05:00
July 0.00 01-JUL-00:10 105.84 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 18.79 25-JUL-15:55 58.86 10-JUL-14:00
August 0.00 01-AUG-00:10 105.84 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 17.41 04-AUG-16:01 66.99 04-AUG-18:51
September 0.00 01-SEP-00:10 105.84 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 26.36 06-SEP-14:00 96.91 18-SEP-22:55
October 0.00 01-OCT-00:10 105.84 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 13.38 20-OCT-15:00 132.82 24-OCT-05:55
November 0.00 01-NOV-00:10 105.84 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 269.75 20-NOV-22:00
December 0.00 01-DEC-00:10 105.84 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 422.40 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   105.84   0.00   0.00 0.00 0.00 0.00 0.00   58.86  
Maximum of Months 0.00   105.84   0.00   0.00 0.00 0.00 0.00 53.51   422.40  



Table of Contents

Report: PeakSpaceGainsMonthly

For: REARSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 105.87 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 385.40 29-JAN-11:00
February 0.00 01-FEB-00:10 105.87 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 279.75 01-FEB-21:00
March 0.00 01-MAR-00:10 105.87 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 237.95 05-MAR-15:00
April 0.00 01-APR-00:10 105.87 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 11.50 15-APR-12:00 184.50 25-APR-05:55
May 0.00 01-MAY-00:10 105.87 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 1.21 31-MAY-08:51 119.96 13-MAY-13:00
June 0.00 01-JUN-00:10 105.87 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 24.11 18-JUN-15:55 94.25 02-JUN-05:00
July 0.00 01-JUL-00:10 105.87 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 2.58 26-JUL-14:05 60.13 10-JUL-14:00
August 0.00 01-AUG-00:10 105.87 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 7.66 04-AUG-15:00 83.13 04-AUG-18:51
September 0.00 01-SEP-00:10 105.87 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 5.25 06-SEP-14:00 87.90 18-SEP-22:55
October 0.00 01-OCT-00:10 105.87 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 127.90 24-OCT-05:55
November 0.00 01-NOV-00:10 105.87 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 269.81 20-NOV-22:00
December 0.00 01-DEC-00:10 105.87 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 451.05 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   105.87   0.00   0.00 0.00 0.00 0.00 0.00   60.13  
Maximum of Months 0.00   105.87   0.00   0.00 0.00 0.00 0.00 24.11   451.05  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDORFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 415.13 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 366.63 18-JAN-20:00
February 0.00 01-FEB-00:10 415.13 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 248.02 04-FEB-22:55
March 0.00 01-MAR-00:10 415.13 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 227.14 06-MAR-08:00
April 0.00 01-APR-00:10 415.13 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 39.41 15-APR-15:00 168.28 25-APR-06:00
May 0.00 01-MAY-00:10 415.13 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 17.69 31-MAY-13:00 89.82 02-MAY-03:00
June 0.00 01-JUN-00:10 415.13 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 45.46 18-JUN-16:00 69.16 02-JUN-05:00
July 0.00 01-JUL-00:10 415.13 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 27.96 25-JUL-15:55 39.65 10-JUL-14:00
August 0.00 01-AUG-00:10 415.13 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 25.57 03-AUG-15:55 37.64 06-AUG-09:00
September 0.00 01-SEP-00:10 415.13 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 24.43 11-SEP-15:00 61.00 27-SEP-10:00
October 0.00 01-OCT-00:10 415.13 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 116.02 24-OCT-06:00
November 0.00 01-NOV-00:10 415.13 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 249.82 20-NOV-22:00
December 0.00 01-DEC-00:10 415.13 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 416.35 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   415.13   0.00   0.00 0.00 0.00 0.00 0.00   37.64  
Maximum of Months 0.00   415.13   0.00   0.00 0.00 0.00 0.00 45.46   416.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: REARSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 14.37 01-JAN-08:09 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 359.38 29-JAN-13:00
February 0.00 01-FEB-00:10 14.37 01-FEB-08:09 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 264.17 01-FEB-21:00
March 0.00 01-MAR-00:10 14.37 01-MAR-08:09 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 216.46 05-MAR-15:00
April 0.00 01-APR-00:10 14.37 01-APR-07:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 31.46 15-APR-12:00 174.84 24-APR-17:00
May 0.00 01-MAY-00:10 14.37 01-MAY-07:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 8.34 31-MAY-08:51 106.55 13-MAY-13:00
June 0.00 01-JUN-00:10 14.37 01-JUN-07:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 29.54 18-JUN-15:55 84.81 02-JUN-05:00
July 0.00 01-JUL-00:10 14.37 01-JUL-07:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 11.24 25-JUL-12:00 52.02 10-JUL-14:00
August 0.00 01-AUG-00:10 14.37 01-AUG-07:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 15.16 04-AUG-12:00 80.06 04-AUG-18:51
September 0.00 01-SEP-00:10 14.37 01-SEP-07:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 13.29 06-SEP-14:00 82.44 24-SEP-17:55
October 0.00 01-OCT-00:10 14.37 01-OCT-07:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 113.80 24-OCT-05:55
November 0.00 01-NOV-00:10 14.37 01-NOV-07:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 246.15 20-NOV-22:00
December 0.00 01-DEC-00:10 14.37 01-DEC-08:09 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 393.59 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   14.37   0.00   0.00 0.00 0.00 0.00 0.00   52.02  
Maximum of Months 0.00   14.37   0.00   0.00 0.00 0.00 0.00 31.46   393.59  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM401

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 198.00 01-JAN-00:10 99.23 01-JAN-19:10 349.07 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 166.66 18-JAN-20:00
February 198.00 01-FEB-00:10 99.23 01-FEB-20:10 349.07 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 112.75 04-FEB-22:55
March 198.00 01-MAR-00:10 99.23 01-MAR-20:10 349.07 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 103.25 06-MAR-08:00
April 198.00 01-APR-00:10 99.23 01-APR-18:10 349.07 01-APR-07:10 0.00 0.00 0.00 0.00 25.19 15-APR-16:52 76.49 25-APR-05:55
May 198.00 01-MAY-00:10 99.23 01-MAY-19:10 349.07 01-MAY-06:10 0.00 0.00 0.00 0.00 14.73 05-MAY-15:06 40.83 02-MAY-03:00
June 198.00 01-JUN-00:10 99.23 01-JUN-19:10 349.07 01-JUN-06:10 0.00 0.00 0.00 0.00 27.62 18-JUN-16:00 31.44 02-JUN-05:00
July 198.00 01-JUL-00:10 99.23 01-JUL-18:10 349.07 01-JUL-07:10 0.00 0.00 0.00 0.00 19.18 25-JUL-16:00 16.87 10-JUL-14:00
August 198.00 01-AUG-00:10 99.23 01-AUG-19:10 349.07 01-AUG-06:10 0.00 0.00 0.00 0.00 18.08 04-AUG-16:52 17.24 06-AUG-07:20
September 198.00 01-SEP-00:10 99.23 01-SEP-19:10 349.07 01-SEP-06:10 0.00 0.00 0.00 0.00 17.98 11-SEP-15:07 27.73 27-SEP-10:00
October 198.00 01-OCT-00:10 99.23 01-OCT-18:10 349.07 01-OCT-07:10 0.00 0.00 0.00 0.00 2.80 20-OCT-15:06 52.74 24-OCT-05:55
November 198.00 01-NOV-00:10 99.23 01-NOV-19:10 349.07 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 113.56 20-NOV-22:00
December 198.00 01-DEC-00:10 99.23 01-DEC-20:10 349.07 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 189.26 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 198.00   99.23   349.07   0.00 0.00 0.00 0.00 0.00   16.87  
Maximum of Months 198.00   99.23   349.07   0.00 0.00 0.00 0.00 27.62   189.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM402_405

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 185.76 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 127.91 01-FEB-21:00
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 111.88 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 12.60 15-APR-15:00 89.79 24-APR-17:00
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 5.66 31-MAY-13:00 49.68 01-MAY-09:00
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 18.61 11-JUN-15:00 39.94 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 8.11 25-JUL-16:00 24.58 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 10.14 04-AUG-16:12 24.39 06-AUG-09:00
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 9.47 06-SEP-14:00 36.33 18-SEP-22:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 55.81 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 119.88 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 214.94 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   24.39  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 18.61   214.94  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM406_408

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 150.04 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 103.31 01-FEB-21:00
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 90.36 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 10.18 15-APR-15:00 75.41 24-APR-17:00
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 4.57 31-MAY-13:00 41.01 01-MAY-09:00
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 15.03 11-JUN-15:00 32.21 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 6.55 25-JUL-16:00 19.98 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 8.19 04-AUG-16:12 19.70 06-AUG-09:00
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 7.65 06-SEP-14:00 29.32 18-SEP-22:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 45.69 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 98.36 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 173.61 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   19.70  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 15.03   173.61  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM409_412

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 792.00 01-JAN-00:10 396.93 01-JAN-19:10 1396.30 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 216.65 18-JAN-20:00
February 792.00 01-FEB-00:10 396.93 01-FEB-20:10 1396.30 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 146.56 04-FEB-22:55
March 792.00 01-MAR-00:10 396.93 01-MAR-20:10 1396.30 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 134.22 06-MAR-08:00
April 792.00 01-APR-00:10 396.93 01-APR-18:10 1396.30 01-APR-07:10 0.00 0.00 0.00 0.00 32.74 15-APR-16:52 99.43 25-APR-06:00
May 792.00 01-MAY-00:10 396.93 01-MAY-19:10 1396.30 01-MAY-06:10 0.00 0.00 0.00 0.00 19.15 05-MAY-15:06 53.80 01-MAY-12:00
June 792.00 01-JUN-00:10 396.93 01-JUN-19:10 1396.30 01-JUN-06:10 0.00 0.00 0.00 0.00 35.90 18-JUN-16:00 40.87 02-JUN-05:00
July 792.00 01-JUL-00:10 396.93 01-JUL-18:10 1396.30 01-JUL-07:10 0.00 0.00 0.00 0.00 24.94 25-JUL-15:55 22.15 10-JUL-16:40
August 792.00 01-AUG-00:10 396.93 01-AUG-19:10 1396.30 01-AUG-06:10 0.00 0.00 0.00 0.00 23.50 04-AUG-16:52 22.48 30-AUG-16:27
September 792.00 01-SEP-00:10 396.93 01-SEP-19:10 1396.30 01-SEP-06:10 0.00 0.00 0.00 0.00 23.37 11-SEP-15:07 36.75 27-SEP-08:00
October 792.00 01-OCT-00:10 396.93 01-OCT-18:10 1396.30 01-OCT-07:10 0.00 0.00 0.00 0.00 3.65 20-OCT-15:06 68.56 24-OCT-06:00
November 792.00 01-NOV-00:10 396.93 01-NOV-19:10 1396.30 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 147.62 20-NOV-22:00
December 792.00 01-DEC-00:10 396.93 01-DEC-20:10 1396.30 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 246.03 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 792.00   396.93   1396.30   0.00 0.00 0.00 0.00 0.00   22.15  
Maximum of Months 792.00   396.93   1396.30   0.00 0.00 0.00 0.00 35.90   246.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM413

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 46.44 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 31.98 01-FEB-21:00
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 27.97 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 3.44 15-APR-12:00 20.69 25-APR-05:55
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 1.41 31-MAY-13:00 11.76 01-MAY-09:00
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 4.65 11-JUN-15:00 9.47 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 2.03 25-JUL-16:00 5.69 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 2.54 04-AUG-16:12 5.79 04-AUG-19:00
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 2.37 06-SEP-14:00 8.78 18-SEP-22:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.07 20-OCT-12:00 13.72 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 29.85 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 53.74 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   5.69  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 4.65   53.74  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM414

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 46.44 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 31.98 01-FEB-21:00
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 27.97 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 3.15 15-APR-15:00 21.53 25-APR-06:00
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 1.41 31-MAY-13:00 13.66 01-MAY-09:00
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 4.65 11-JUN-15:00 9.82 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 2.03 25-JUL-16:00 5.93 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 2.54 04-AUG-16:12 5.79 04-AUG-18:53
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 2.37 06-SEP-14:00 8.93 18-SEP-22:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 14.55 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 31.67 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 53.74 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   5.79  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 4.65   53.74  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM415_418

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 792.00 01-JAN-00:10 396.90 01-JAN-19:10 1396.20 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 216.65 18-JAN-20:00
February 792.00 01-FEB-00:10 396.90 01-FEB-20:10 1396.20 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 146.56 04-FEB-22:55
March 792.00 01-MAR-00:10 396.90 01-MAR-20:10 1396.20 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 134.22 06-MAR-08:00
April 792.00 01-APR-00:10 396.90 01-APR-18:10 1396.20 01-APR-07:10 0.00 0.00 0.00 0.00 32.74 15-APR-16:52 99.43 25-APR-06:00
May 792.00 01-MAY-00:10 396.90 01-MAY-19:10 1396.20 01-MAY-06:10 0.00 0.00 0.00 0.00 19.15 05-MAY-15:06 55.53 01-MAY-07:55
June 792.00 01-JUN-00:10 396.90 01-JUN-19:10 1396.20 01-JUN-06:10 0.00 0.00 0.00 0.00 35.90 18-JUN-16:00 40.87 02-JUN-05:00
July 792.00 01-JUL-00:10 396.90 01-JUL-18:10 1396.20 01-JUL-07:10 0.00 0.00 0.00 0.00 24.94 25-JUL-15:55 21.92 10-JUL-14:00
August 792.00 01-AUG-00:10 396.90 01-AUG-19:10 1396.20 01-AUG-06:10 0.00 0.00 0.00 0.00 23.50 04-AUG-16:52 22.41 06-AUG-07:19
September 792.00 01-SEP-00:10 396.90 01-SEP-19:10 1396.20 01-SEP-06:10 0.00 0.00 0.00 0.00 23.37 11-SEP-15:06 38.28 27-SEP-08:00
October 792.00 01-OCT-00:10 396.90 01-OCT-18:10 1396.20 01-OCT-07:10 0.00 0.00 0.00 0.00 3.65 20-OCT-15:06 68.56 24-OCT-06:00
November 792.00 01-NOV-00:10 396.90 01-NOV-19:10 1396.20 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 147.62 20-NOV-22:00
December 792.00 01-DEC-00:10 396.90 01-DEC-20:10 1396.20 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 246.03 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 792.00   396.90   1396.20   0.00 0.00 0.00 0.00 0.00   21.92  
Maximum of Months 792.00   396.90   1396.20   0.00 0.00 0.00 0.00 35.90   246.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ELEVATORCOREFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 89.34 18-JAN-20:00
February 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 60.94 04-FEB-22:55
March 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 55.84 06-MAR-08:00
April 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 7.49 15-APR-17:00 43.21 25-APR-05:55
May 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 2.44 31-MAY-13:00 25.59 01-MAY-09:00
June 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 8.95 18-JUN-16:00 19.53 02-JUN-05:00
July 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 4.37 25-JUL-16:00 11.43 10-JUL-14:00
August 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 4.71 03-AUG-16:00 10.75 06-AUG-09:00
September 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 4.49 06-SEP-14:00 17.42 18-SEP-22:55
October 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 29.58 24-OCT-05:55
November 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 63.11 20-NOV-22:00
December 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 101.95 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 0.00   10.75  
Maximum of Months 0.00   0.00   0.00   0.00 0.00 0.00 0.00 8.95   101.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM419

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 198.00 01-JAN-00:10 99.23 01-JAN-19:10 349.05 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 54.16 18-JAN-20:00
February 198.00 01-FEB-00:10 99.23 01-FEB-20:10 349.05 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 36.64 04-FEB-22:55
March 198.00 01-MAR-00:10 99.23 01-MAR-20:10 349.05 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 33.55 06-MAR-08:00
April 198.00 01-APR-00:10 99.23 01-APR-18:10 349.05 01-APR-07:10 0.00 0.00 0.00 0.00 8.19 15-APR-16:52 24.86 25-APR-06:00
May 198.00 01-MAY-00:10 99.23 01-MAY-19:10 349.05 01-MAY-06:10 0.00 0.00 0.00 0.00 4.79 05-MAY-15:06 13.88 01-MAY-07:55
June 198.00 01-JUN-00:10 99.23 01-JUN-19:10 349.05 01-JUN-06:10 0.00 0.00 0.00 0.00 8.98 18-JUN-16:00 10.22 02-JUN-05:00
July 198.00 01-JUL-00:10 99.23 01-JUL-18:10 349.05 01-JUL-07:10 0.00 0.00 0.00 0.00 6.23 25-JUL-15:55 5.48 10-JUL-14:00
August 198.00 01-AUG-00:10 99.23 01-AUG-19:10 349.05 01-AUG-06:10 0.00 0.00 0.00 0.00 5.88 04-AUG-16:52 5.63 06-AUG-07:10
September 198.00 01-SEP-00:10 99.23 01-SEP-19:10 349.05 01-SEP-06:10 0.00 0.00 0.00 0.00 5.84 11-SEP-15:06 9.47 27-SEP-08:00
October 198.00 01-OCT-00:10 99.23 01-OCT-18:10 349.05 01-OCT-07:10 0.00 0.00 0.00 0.00 0.91 20-OCT-15:06 17.14 24-OCT-06:00
November 198.00 01-NOV-00:10 99.23 01-NOV-19:10 349.05 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 36.90 20-NOV-22:00
December 198.00 01-DEC-00:10 99.23 01-DEC-20:10 349.05 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 61.51 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 0.00   5.48  
Maximum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 8.98   61.51  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM420_423

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 792.00 01-JAN-00:10 396.90 01-JAN-19:10 1396.20 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 216.65 18-JAN-20:00
February 792.00 01-FEB-00:10 396.90 01-FEB-20:10 1396.20 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 146.56 04-FEB-22:55
March 792.00 01-MAR-00:10 396.90 01-MAR-20:10 1396.20 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 134.22 06-MAR-08:00
April 792.00 01-APR-00:10 396.90 01-APR-18:10 1396.20 01-APR-07:10 0.00 0.00 0.00 0.00 32.74 15-APR-16:52 99.43 25-APR-06:00
May 792.00 01-MAY-00:10 396.90 01-MAY-19:10 1396.20 01-MAY-06:10 0.00 0.00 0.00 0.00 19.15 05-MAY-15:06 55.53 01-MAY-07:55
June 792.00 01-JUN-00:10 396.90 01-JUN-19:10 1396.20 01-JUN-06:10 0.00 0.00 0.00 0.00 35.90 18-JUN-16:00 40.87 02-JUN-05:00
July 792.00 01-JUL-00:10 396.90 01-JUL-18:10 1396.20 01-JUL-07:10 0.00 0.00 0.00 0.00 24.94 25-JUL-15:55 21.92 10-JUL-14:00
August 792.00 01-AUG-00:10 396.90 01-AUG-19:10 1396.20 01-AUG-06:10 0.00 0.00 0.00 0.00 23.50 04-AUG-16:52 22.41 06-AUG-07:20
September 792.00 01-SEP-00:10 396.90 01-SEP-19:10 1396.20 01-SEP-06:10 0.00 0.00 0.00 0.00 23.37 11-SEP-15:06 38.09 27-SEP-08:00
October 792.00 01-OCT-00:10 396.90 01-OCT-18:10 1396.20 01-OCT-07:10 0.00 0.00 0.00 0.00 3.65 20-OCT-15:06 68.56 24-OCT-06:00
November 792.00 01-NOV-00:10 396.90 01-NOV-19:10 1396.20 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 147.62 20-NOV-22:00
December 792.00 01-DEC-00:10 396.90 01-DEC-20:10 1396.20 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 246.03 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 792.00   396.90   1396.20   0.00 0.00 0.00 0.00 0.00   21.92  
Maximum of Months 792.00   396.90   1396.20   0.00 0.00 0.00 0.00 35.90   246.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: GUESTROOM424

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 198.00 01-JAN-00:10 99.23 01-JAN-19:10 349.05 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 54.16 18-JAN-20:00
February 198.00 01-FEB-00:10 99.23 01-FEB-20:10 349.05 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 36.64 04-FEB-22:55
March 198.00 01-MAR-00:10 99.23 01-MAR-20:10 349.05 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 33.56 06-MAR-08:00
April 198.00 01-APR-00:10 99.23 01-APR-18:10 349.05 01-APR-07:10 0.00 0.00 0.00 0.00 8.19 15-APR-16:52 24.86 25-APR-06:00
May 198.00 01-MAY-00:10 99.23 01-MAY-19:10 349.05 01-MAY-06:10 0.00 0.00 0.00 0.00 4.79 05-MAY-15:06 13.52 01-MAY-08:00
June 198.00 01-JUN-00:10 99.23 01-JUN-19:10 349.05 01-JUN-06:10 0.00 0.00 0.00 0.00 8.98 18-JUN-16:00 10.22 02-JUN-05:00
July 198.00 01-JUL-00:10 99.23 01-JUL-18:10 349.05 01-JUL-07:10 0.00 0.00 0.00 0.00 6.23 25-JUL-15:55 5.48 10-JUL-14:00
August 198.00 01-AUG-00:10 99.23 01-AUG-19:10 349.05 01-AUG-06:10 0.00 0.00 0.00 0.00 5.88 04-AUG-16:52 5.60 06-AUG-07:20
September 198.00 01-SEP-00:10 99.23 01-SEP-19:10 349.05 01-SEP-06:10 0.00 0.00 0.00 0.00 5.84 11-SEP-15:06 9.01 27-SEP-09:55
October 198.00 01-OCT-00:10 99.23 01-OCT-18:10 349.05 01-OCT-07:10 0.00 0.00 0.00 0.00 0.91 20-OCT-15:06 17.14 24-OCT-05:55
November 198.00 01-NOV-00:10 99.23 01-NOV-19:10 349.05 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 36.90 20-NOV-22:00
December 198.00 01-DEC-00:10 99.23 01-DEC-20:10 349.05 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 61.51 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 0.00   5.48  
Maximum of Months 198.00   99.23   349.05   0.00 0.00 0.00 0.00 8.98   61.51  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONTSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 8.98 01-JAN-08:09 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 64.10 29-JAN-11:00
February 0.00 01-FEB-00:10 8.98 01-FEB-08:09 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 44.13 01-FEB-21:00
March 0.00 01-MAR-00:10 8.98 01-MAR-08:09 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 38.70 06-MAR-08:00
April 0.00 01-APR-00:10 8.98 01-APR-07:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 6.48 15-APR-15:00 31.15 25-APR-05:55
May 0.00 01-MAY-00:10 8.98 01-MAY-07:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 1.83 05-MAY-15:01 18.55 01-MAY-09:00
June 0.00 01-JUN-00:10 8.98 01-JUN-07:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 6.76 18-JUN-16:00 15.26 02-JUN-05:00
July 0.00 01-JUL-00:10 8.98 01-JUL-07:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 2.94 25-JUL-16:00 8.90 10-JUL-14:00
August 0.00 01-AUG-00:10 8.98 01-AUG-07:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 3.00 04-AUG-16:20 9.74 04-AUG-18:51
September 0.00 01-SEP-00:10 8.98 01-SEP-07:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 3.65 06-SEP-14:00 13.80 18-SEP-22:55
October 0.00 01-OCT-00:10 8.98 01-OCT-07:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.59 20-OCT-15:00 21.21 24-OCT-05:55
November 0.00 01-NOV-00:10 8.98 01-NOV-07:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 46.02 20-NOV-22:00
December 0.00 01-DEC-00:10 8.98 01-DEC-08:09 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 74.05 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   8.98   0.00   0.00 0.00 0.00 0.00 0.00   8.90  
Maximum of Months 0.00   8.98   0.00   0.00 0.00 0.00 0.00 6.76   74.05  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FRONTSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 105.84 01-JAN-00:10 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 384.38 29-JAN-11:00
February 0.00 01-FEB-00:10 105.84 01-FEB-00:10 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 279.73 01-FEB-21:00
March 0.00 01-MAR-00:10 105.84 01-MAR-00:10 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 210.71 06-MAR-08:00
April 0.00 01-APR-00:10 105.84 01-APR-00:10 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 31.27 15-APR-15:00 175.59 25-APR-05:55
May 0.00 01-MAY-00:10 105.84 01-MAY-00:10 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 4.79 05-MAY-15:33 116.01 13-MAY-13:00
June 0.00 01-JUN-00:10 105.84 01-JUN-00:10 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 29.42 18-JUN-15:55 95.59 02-JUN-05:00
July 0.00 01-JUL-00:10 105.84 01-JUL-00:10 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 5.40 25-JUL-12:00 59.40 10-JUL-14:00
August 0.00 01-AUG-00:10 105.84 01-AUG-00:10 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 11.38 04-AUG-15:00 80.19 04-AUG-18:51
September 0.00 01-SEP-00:10 105.84 01-SEP-00:10 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 18.51 06-SEP-14:00 87.85 18-SEP-22:55
October 0.00 01-OCT-00:10 105.84 01-OCT-00:10 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 5.18 20-OCT-15:00 119.38 24-OCT-05:55
November 0.00 01-NOV-00:10 105.84 01-NOV-00:10 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 256.88 20-NOV-22:00
December 0.00 01-DEC-00:10 105.84 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 452.80 09-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   105.84   0.00   0.00 0.00 0.00 0.00 0.00   59.40  
Maximum of Months 0.00   105.84   0.00   0.00 0.00 0.00 0.00 31.27   452.80  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: REARSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.35 27-JAN-10:55 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 164.69
February 0.23 02-FEB-10:55 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 177.28
March 0.27 25-MAR-13:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 27.72
April 0.26 10-APR-12:55 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 8.86
May 0.06 02-MAY-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 35.58
June 0.02 13-JUN-11:50 0.00 105.87 0.00 0.00 0.00 0.00 0.00 10.17 0.00
July 0.01 24-JUL-07:53 0.00 317.60 0.00 0.00 0.00 0.00 0.00 0.00 10.74
August 0.06 13-AUG-12:00 0.00 105.87 0.00 0.00 0.00 0.00 0.00 0.00 8.60
September 0.25 15-SEP-09:55 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.23 19-OCT-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 43.20
November 0.24 11-NOV-11:35 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 110.35
December 0.43 15-DEC-10:55 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 69.13
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.01   0.00 105.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.43   0.00 317.60 0.00 0.00 0.00 0.00 0.00 10.17 177.28



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDORFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3231.82 13-JAN-22:05 0.00 3985.27 0.00 0.00 0.00 0.00 0.00 0.00 64.28
February 4128.62 25-FEB-22:04 0.00 3985.27 0.00 0.00 0.00 0.00 0.00 0.00 75.67
March 4475.85 20-MAR-21:04 0.00 3985.27 0.00 0.00 0.00 0.00 0.00 0.00 224.23
April 13023.73 15-APR-16:11 0.00 4981.59 0.00 0.00 0.00 0.00 0.00 6236.61 0.00
May 12236.34 31-MAY-16:21 0.00 4981.59 0.00 0.00 0.00 0.00 0.00 4839.86 0.00
June 16512.88 11-JUN-16:10 0.00 4981.59 0.00 0.00 0.00 0.00 0.00 8839.83 0.00
July 13873.04 26-JUL-16:02 0.00 4981.59 0.00 0.00 0.00 0.00 0.00 6119.80 0.00
August 17380.89 04-AUG-16:10 0.00 4981.59 0.00 0.00 0.00 0.00 0.00 9345.58 0.00
September 15980.08 07-SEP-16:10 0.00 4981.59 0.00 0.00 0.00 0.00 0.00 7809.85 0.00
October 7029.31 21-OCT-17:02 0.00 3985.27 0.00 0.00 0.00 0.00 0.00 0.00 1312.06
November 5511.69 03-NOV-17:07 0.00 2988.95 0.00 0.00 0.00 0.00 0.00 0.00 1947.85
December 3429.95 02-DEC-22:14 0.00 2490.80 0.00 0.00 0.00 0.00 0.00 0.00 82.45
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3231.82   0.00 2490.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17380.89   0.00 4981.59 0.00 0.00 0.00 0.00 0.00 9345.58 1947.85



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: REARSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 71.63
February 0.00 01-FEB-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 127.99
March 0.00 01-MAR-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 142.78
April 0.00 01-APR-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 36.97
May 0.00 01-MAY-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 41.54
June 0.00 01-JUN-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 19.83
July 0.00 01-JUL-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 9.26
August 0.00 01-AUG-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 12.91
September 0.00 01-SEP-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 22.82
October 0.00 01-OCT-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 39.70
November 0.00 01-NOV-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 33.49
December 0.00 01-DEC-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 79.80
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 9.26
Maximum of Months 0.00   0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 142.78



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONTLOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4899.86 14-JAN-07:01 39177.60 5897.22 33994.00 0.00 0.00 0.00 0.00 0.00 77.23
February 4937.40 26-FEB-07:01 39177.60 5781.97 33994.00 0.00 0.00 0.00 0.00 0.00 54.07
March 4989.37 21-MAR-08:53 19588.80 2476.83 16997.00 0.00 0.00 0.00 0.00 0.00 120.47
April 5270.97 01-APR-06:01 39177.60 4820.50 33994.00 0.00 0.00 0.00 0.00 0.00 29.66
May 5274.08 31-MAY-08:51 48972.00 6192.08 42492.50 0.00 0.00 0.00 0.00 4.18 0.00
June 5723.98 26-JUN-09:00 14691.60 1857.62 12747.75 0.00 0.00 0.00 0.00 8.50 0.00
July 5838.92 03-JUL-08:51 48972.00 6192.08 42492.50 0.00 0.00 0.00 0.00 2.83 0.00
August 5910.30 03-AUG-08:53 19588.80 2476.83 16997.00 0.00 0.00 0.00 0.00 10.41 0.00
September 5715.00 11-SEP-08:51 48972.00 6192.08 42492.50 0.00 0.00 0.00 0.00 0.03 0.00
October 4953.03 23-OCT-06:00 9794.40 884.58 8498.50 0.00 0.00 0.00 0.00 0.00 42.95
November 5869.10 12-NOV-07:01 39177.60 4946.56 33994.00 0.00 0.00 0.00 0.00 0.00 21.58
December 5116.57 03-DEC-07:01 39177.60 5897.22 33994.00 0.00 0.00 0.00 0.00 0.00 42.22
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4899.86   9794.40 884.58 8498.50 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5910.30   48972.00 6192.08 42492.50 0.00 0.00 0.00 0.00 10.41 120.47



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RESTROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 23.17 121.63 0.00 0.00 0.00 0.00 0.00 0.00 9.19
February 166.10 25-FEB-17:03 463.32 1216.30 0.00 0.00 0.00 0.00 0.00 0.00 5.63
March 156.42 22-MAR-16:03 926.64 1216.30 0.00 0.00 0.00 0.00 0.00 0.00 9.41
April 517.17 09-APR-15:01 463.32 1216.30 0.00 0.00 0.00 0.00 0.00 0.00 3.02
May 363.82 31-MAY-16:52 463.32 608.15 0.00 0.00 0.00 0.00 0.00 1.64 0.00
June 418.85 30-JUN-16:52 463.32 608.15 0.00 0.00 0.00 0.00 0.00 1.33 0.00
July 451.16 05-JUL-16:52 463.32 608.15 0.00 0.00 0.00 0.00 0.00 0.51 0.00
August 449.94 02-AUG-16:52 463.32 608.15 0.00 0.00 0.00 0.00 0.00 2.08 0.00
September 474.25 07-SEP-16:52 463.32 608.15 0.00 0.00 0.00 0.00 0.00 0.81 0.00
October 308.25 29-OCT-04:02 139.00 729.78 0.00 0.00 0.00 0.00 0.00 0.00 6.17
November 549.64 15-NOV-09:01 1621.62 1216.30 0.00 0.00 0.00 0.00 0.00 0.00 12.07
December 0.00 01-DEC-00:10 23.17 121.63 0.00 0.00 0.00 0.00 0.00 0.00 10.41
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   23.17 121.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 549.64   1621.62 1216.30 0.00 0.00 0.00 0.00 0.00 2.08 12.07



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MEETINGROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6104.69 30-JAN-17:51 0.00 8381.38 1144.44 0.00 0.00 0.00 0.00 0.00 33.92
February 4993.41 05-FEB-17:41 0.00 8381.38 1144.44 0.00 0.00 0.00 0.00 0.00 23.49
March 3722.47 05-MAR-12:41 0.00 3592.77 176.07 0.00 0.00 0.00 0.00 0.00 50.14
April 3389.62 03-APR-07:01 19866.00 4522.19 1663.85 0.00 0.00 0.00 0.00 0.00 32.36
May 2338.70 02-MAY-07:01 19866.00 4572.19 1663.85 0.00 0.00 0.00 0.00 0.00 22.08
June 1974.71 26-JUN-13:00 2838.00 368.78 237.69 0.00 0.00 0.00 0.00 5.33 0.00
July 2008.99 05-JUL-13:00 2838.00 435.22 237.69 0.00 0.00 0.00 0.00 0.85 0.00
August 2025.72 02-AUG-13:00 2838.00 433.39 237.69 0.00 0.00 0.00 0.00 3.58 0.00
September 2644.33 30-SEP-07:01 19866.00 4968.84 1663.85 0.00 0.00 0.00 0.00 0.00 17.82
October 2969.08 23-OCT-07:01 19866.00 5291.79 1663.85 0.00 0.00 0.00 0.00 0.00 14.98
November 4386.06 24-NOV-08:61 19866.00 4924.48 1663.85 0.00 0.00 0.00 0.00 0.00 32.01
December 5103.03 11-DEC-14:21 0.00 6526.06 2376.92 0.00 0.00 0.00 0.00 0.00 17.73
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1974.71   0.00 368.78 176.07 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6104.69   19866.00 8381.38 2376.92 0.00 0.00 0.00 0.00 5.33 50.14



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECHANICALROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 9.54
February 0.00 01-FEB-00:10 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 15.26
March 0.00 01-MAR-00:10 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 18.91
April 0.00 01-APR-00:10 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 4.90
May 0.00 01-MAY-00:10 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 6.65
June 0.00 01-JUN-00:10 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 3.15
July 0.00 01-JUL-00:10 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 1.68
August 0.00 01-AUG-00:10 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 2.23
September 0.00 01-SEP-00:10 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 3.47
October 0.00 01-OCT-00:10 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 5.08
November 0.00 01-NOV-00:10 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 4.07
December 0.00 01-DEC-00:10 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 10.81
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 1.68
Maximum of Months 0.00   0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 18.91



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM101

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 580.91 30-JAN-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.33
February 642.07 02-FEB-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.38
March 372.43 05-MAR-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.84
April 281.49 01-APR-14:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.29
May 114.32 13-MAY-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.76
June 120.85 01-JUN-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.99
July 50.14 10-JUL-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.30
August 39.90 30-AUG-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.35
September 121.94 28-SEP-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.90
October 182.83 22-OCT-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.51
November 493.51 25-NOV-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.54
December 509.93 11-DEC-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.96
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 39.90   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.99
Maximum of Months 642.07   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.54



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM102

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 583.25 30-JAN-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.09
February 643.81 02-FEB-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.22
March 377.00 05-MAR-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.41
April 287.08 01-APR-14:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.04
May 120.06 13-MAY-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.47
June 125.67 01-JUN-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.89
July 55.87 10-JUL-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.92
August 45.78 30-AUG-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.00
September 127.08 28-SEP-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.64
October 188.47 22-OCT-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.26
November 499.60 25-NOV-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.13
December 513.13 11-DEC-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.82
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 45.78   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.89
Maximum of Months 643.81   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.13



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM103

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 944.06 16-JAN-16:03 594.00 327.48 1124.80 0.00 0.00 0.00 0.00 0.00 6.22
February 2165.53 26-FEB-09:01 594.00 555.70 2404.74 0.00 0.00 0.00 0.00 0.00 6.81
March 2468.01 21-MAR-18:01 1067.22 618.23 1330.36 0.00 0.00 0.00 0.00 0.00 9.71
April 2402.17 20-APR-18:01 1067.22 618.23 1330.36 0.00 0.00 0.00 0.00 0.00 4.30
May 2500.78 21-MAY-19:51 1287.00 992.33 2559.88 0.00 0.00 0.00 0.00 0.00 1.83
June 2465.40 23-JUN-20:01 1762.20 883.18 2715.03 0.00 0.00 0.00 0.00 0.00 0.86
July 2460.82 18-JUL-18:31 1524.60 883.18 1900.52 0.00 0.00 0.00 0.00 0.00 0.17
August 2596.30 06-AUG-17:01 1069.20 843.49 1978.09 0.00 0.00 0.00 0.00 0.00 2.26
September 2610.20 20-SEP-17:01 1069.20 664.87 1978.09 0.00 0.00 0.00 0.00 0.00 1.97
October 2474.81 28-OCT-08:61 594.00 555.70 2404.74 0.00 0.00 0.00 0.00 0.00 2.41
November 2607.05 12-NOV-09:01 594.00 555.70 2404.74 0.00 0.00 0.00 0.00 0.00 5.74
December 1912.64 03-DEC-09:01 594.00 555.70 2404.74 0.00 0.00 0.00 0.00 0.00 9.20
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 944.06   594.00 327.48 1124.80 0.00 0.00 0.00 0.00 0.00 0.17
Maximum of Months 2610.20   1762.20 992.33 2715.03 0.00 0.00 0.00 0.00 0.00 9.71



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM104

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2621.28 02-JAN-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 13.87
February 2598.57 21-FEB-09:01 396.00 436.59 1667.68 0.00 0.00 0.00 0.00 0.00 7.94
March 2683.94 21-MAR-08:61 396.00 436.59 1667.68 0.00 0.00 0.00 0.00 0.00 16.23
April 2610.42 01-APR-08:61 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 8.58
May 2649.03 06-MAY-16:51 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 2.83
June 2575.75 22-JUN-16:41 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.51
July 2563.49 23-JUL-16:21 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 0.20
August 2648.56 07-AUG-16:31 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.83
September 2734.88 20-SEP-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 1.82
October 2650.09 28-OCT-08:61 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 2.48
November 2974.41 25-NOV-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 23.12
December 2793.36 25-DEC-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 9.67
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2563.49   396.00 277.83 1667.68 0.00 0.00 0.00 0.00 0.00 0.20
Maximum of Months 2974.41   1069.20 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 23.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM105

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4263.56 07-JAN-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 13.16
February 4180.44 05-FEB-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 12.26
March 4042.28 06-MAR-09:01 396.00 436.59 1667.68 0.00 0.00 0.00 0.00 0.00 23.12
April 3942.45 30-APR-18:21 1287.00 992.26 1900.38 0.00 0.00 0.00 0.00 0.00 1.96
May 4013.91 21-MAY-16:51 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 1.98
June 3833.40 22-JUN-16:41 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.55
July 3800.81 23-JUL-16:21 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 0.20
August 3912.64 06-AUG-16:51 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 2.26
September 4064.01 24-SEP-16:11 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 6.25
October 3992.99 30-OCT-16:11 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 3.71
November 4230.22 26-NOV-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 9.14
December 4224.73 09-DEC-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 48.38
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3800.81   396.00 277.83 1667.68 0.00 0.00 0.00 0.00 0.00 0.20
Maximum of Months 4263.56   1287.00 992.26 2404.57 0.00 0.00 0.00 0.00 0.00 48.38



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: EMPLOYEELOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6701.33 30-JAN-13:01 3801.60 1656.72 4625.07 0.00 0.00 0.00 0.00 0.00 20.45
February 3535.86 24-FEB-13:00 1663.20 207.09 672.25 0.00 0.00 0.00 0.00 0.00 4.89
March 3653.68 20-MAR-12:00 1663.20 207.09 672.25 0.00 0.00 0.00 0.00 0.00 9.40
April 3947.85 18-APR-12:00 1663.20 207.09 672.25 0.00 0.00 0.00 0.00 3.11 0.00
May 4032.45 31-MAY-12:00 1663.20 207.09 672.25 0.00 0.00 0.00 0.00 1.45 0.00
June 4086.33 29-JUN-12:00 1663.20 207.09 672.25 0.00 0.00 0.00 0.00 1.52 0.00
July 4106.99 05-JUL-12:00 1663.20 207.09 672.25 0.00 0.00 0.00 0.00 0.27 0.00
August 4143.47 02-AUG-12:00 1663.20 207.09 672.25 0.00 0.00 0.00 0.00 1.10 0.00
September 4128.10 07-SEP-12:00 1663.20 207.09 672.25 0.00 0.00 0.00 0.00 0.00 0.00
October 3829.08 20-OCT-12:00 1663.20 207.09 672.25 0.00 0.00 0.00 0.00 0.00 1.18
November 3710.94 03-NOV-12:00 1663.20 207.09 672.25 0.00 0.00 0.00 0.00 0.00 2.61
December 3434.76 05-DEC-13:00 1663.20 207.09 672.25 0.00 0.00 0.00 0.00 0.00 20.25
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3434.76   1663.20 207.09 672.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6701.33   3801.60 1656.72 4625.07 0.00 0.00 0.00 0.00 3.11 20.45



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRYROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 56.33
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 71.61
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 99.54
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28.73
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48.51
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.45
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.49
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.29
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.44
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32.32
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.47
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 66.52
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.49
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 99.54



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ELEVATORCOREFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 0.00 1929.17 0.00 0.00 0.00 0.00 0.00 37.51
February 0.00 01-FEB-00:10 0.00 0.00 1929.17 0.00 0.00 0.00 0.00 0.00 46.64
March 0.00 01-MAR-00:10 0.00 0.00 1929.17 0.00 0.00 0.00 0.00 0.00 65.42
April 0.00 01-APR-00:10 0.00 0.00 1929.17 0.00 0.00 0.00 0.00 0.00 19.10
May 0.00 01-MAY-00:10 0.00 0.00 1929.17 0.00 0.00 0.00 0.00 0.00 32.68
June 0.00 01-JUN-00:10 0.00 0.00 1929.17 0.00 0.00 0.00 0.00 0.00 18.68
July 0.00 01-JUL-00:10 0.00 0.00 1929.17 0.00 0.00 0.00 0.00 0.00 12.73
August 0.00 01-AUG-00:10 0.00 0.00 1929.17 0.00 0.00 0.00 0.00 0.00 15.98
September 0.00 01-SEP-00:10 0.00 0.00 1929.17 0.00 0.00 0.00 0.00 0.00 21.48
October 0.00 01-OCT-00:10 0.00 0.00 1929.17 0.00 0.00 0.00 0.00 0.00 21.59
November 0.00 01-NOV-00:10 0.00 0.00 1929.17 0.00 0.00 0.00 0.00 0.00 16.32
December 0.00 01-DEC-00:10 0.00 0.00 1929.17 0.00 0.00 0.00 0.00 0.00 44.33
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 1929.17 0.00 0.00 0.00 0.00 0.00 12.73
Maximum of Months 0.00   0.00 0.00 1929.17 0.00 0.00 0.00 0.00 0.00 65.42



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: EXERCISECENTERFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4033.44 30-JAN-23:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.44
February 3903.71 03-FEB-12:41 0.00 3159.00 0.00 0.00 0.00 0.00 0.00 0.00 15.73
March 2974.12 06-MAR-03:31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.95
April 1358.10 25-APR-19:05 1848.00 631.80 1212.40 0.00 0.00 0.00 0.00 0.00 7.66
May 1375.31 01-MAY-20:01 7392.00 2527.20 2424.80 0.00 0.00 0.00 0.00 0.00 9.61
June 1245.78 26-JUN-16:00 1848.00 631.80 1212.40 0.00 0.00 0.00 0.00 2.34 0.00
July 1242.10 05-JUL-16:00 1848.00 631.80 1212.40 0.00 0.00 0.00 0.00 0.47 0.00
August 1262.50 04-AUG-15:55 1848.00 631.80 1212.40 0.00 0.00 0.00 0.00 2.59 0.00
September 1439.62 28-SEP-20:01 7392.00 2527.20 2424.80 0.00 0.00 0.00 0.00 0.00 3.69
October 1466.91 31-OCT-18:40 1848.00 631.80 1212.40 0.00 0.00 0.00 0.00 0.00 2.44
November 3702.58 26-NOV-03:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.11
December 3518.81 09-DEC-01:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.70
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1242.10   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4033.44   7392.00 3159.00 2424.80 0.00 0.00 0.00 0.00 2.59 41.70



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONTOFFICEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2916.74 30-JAN-19:22 1320.00 1691.79 5241.44 0.00 0.00 0.00 0.00 0.00 67.09
February 2960.18 04-FEB-09:22 3300.00 1461.70 5241.44 0.00 0.00 0.00 0.00 0.00 50.33
March 2121.36 05-MAR-23:53 1056.00 1353.43 2196.41 0.00 0.00 0.00 0.00 0.00 67.31
April 2252.49 18-APR-10:30 2640.00 584.68 3327.90 0.00 0.00 0.00 0.00 7.25 0.00
May 2511.52 31-MAY-10:15 5280.00 1169.36 6655.80 0.00 0.00 0.00 0.00 3.62 0.00
June 2709.01 29-JUN-10:01 10560.00 2338.71 13311.59 0.00 0.00 0.00 0.00 3.79 0.00
July 2747.17 05-JUL-10:30 2640.00 584.68 3327.90 0.00 0.00 0.00 0.00 0.14 0.00
August 2853.16 02-AUG-10:15 5280.00 1169.36 6655.80 0.00 0.00 0.00 0.00 3.25 0.00
September 2765.87 07-SEP-10:40 2640.00 584.68 3327.90 0.00 0.00 0.00 0.00 3.58 0.00
October 1774.94 11-OCT-16:00 2640.00 1102.77 3327.90 0.00 0.00 0.00 0.00 0.00 11.36
November 2687.51 26-NOV-00:42 1056.00 1353.43 2196.41 0.00 0.00 0.00 0.00 0.00 67.77
December 2475.78 09-DEC-11:32 0.00 2069.90 4193.15 0.00 0.00 0.00 0.00 0.00 165.90
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1774.94   0.00 584.68 2196.41 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2960.18   10560.00 2338.71 13311.59 0.00 0.00 0.00 0.00 7.25 165.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONTSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.13 28-JAN-01:00 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.17 06-FEB-12:40 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 119.42
March 0.00 01-MAR-00:10 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 135.27
April 0.11 26-APR-06:45 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 4.94
May 0.00 01-MAY-00:10 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 41.26
June 0.00 01-JUN-00:10 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 22.73
July 0.00 01-JUL-00:10 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 12.32
August 0.01 16-AUG-07:00 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.06 15-SEP-09:55 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 01-OCT-00:10 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 40.11
November 0.00 01-NOV-00:10 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 32.87
December 0.11 09-DEC-02:30 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 338.56
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17   0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 338.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONTSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 11.62
February 0.00 01-FEB-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 19.57
March 0.00 01-MAR-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 23.42
April 0.00 01-APR-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 6.06
May 0.00 01-MAY-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 7.40
June 0.00 01-JUN-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 3.62
July 0.00 01-JUL-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 1.82
August 0.00 01-AUG-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 2.40
September 0.00 01-SEP-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 3.92
October 0.00 01-OCT-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 6.38
November 0.00 01-NOV-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 5.16
December 0.00 01-DEC-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 12.77
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 1.82
Maximum of Months 0.00   0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 23.42



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: REARSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.53 30-JAN-11:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 146.39
February 0.44 02-FEB-10:55 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 181.13
March 0.43 06-MAR-11:35 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 127.09
April 0.38 10-APR-12:55 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 21.19
May 0.41 02-MAY-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 39.87
June 0.20 13-JUN-11:30 0.00 105.87 0.00 0.00 0.00 0.00 0.00 0.00 2.02
July 0.05 11-JUL-11:00 0.00 105.87 0.00 0.00 0.00 0.00 0.00 0.00 14.02
August 0.31 13-AUG-12:00 0.00 105.87 0.00 0.00 0.00 0.00 0.00 0.00 10.88
September 0.41 20-SEP-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 14.45
October 0.46 20-OCT-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 19.21
November 0.45 11-NOV-11:35 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 108.82
December 0.60 01-DEC-10:55 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 105.55
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.05   0.00 105.87 0.00 0.00 0.00 0.00 0.00 0.00 2.02
Maximum of Months 0.60   0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 181.13



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDORFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1817.82 06-JAN-05:13 0.00 1245.38 0.00 0.00 0.00 0.00 0.00 0.00 81.33
February 1505.12 05-FEB-09:23 0.00 1660.51 0.00 0.00 0.00 0.00 0.00 0.00 88.08
March 1183.39 10-MAR-22:23 0.00 1245.38 0.00 0.00 0.00 0.00 0.00 0.00 25.29
April 1730.59 17-APR-18:02 0.00 4151.28 0.00 0.00 0.00 0.00 0.00 0.00 5.34
May 1779.46 31-MAY-15:01 0.00 4151.28 0.00 0.00 0.00 0.00 0.00 13.35 0.00
June 1973.29 21-JUN-19:01 0.00 2905.90 0.00 0.00 0.00 0.00 0.00 0.00 16.32
July 2146.34 15-JUL-19:01 0.00 2905.90 0.00 0.00 0.00 0.00 0.00 0.00 3.32
August 2086.29 29-AUG-18:03 0.00 2905.90 0.00 0.00 0.00 0.00 0.00 0.00 7.96
September 1949.24 12-SEP-17:52 0.00 4151.28 0.00 0.00 0.00 0.00 0.00 0.00 3.56
October 1094.64 11-OCT-18:22 0.00 4151.28 0.00 0.00 0.00 0.00 0.00 0.00 23.70
November 1107.66 12-NOV-03:00 0.00 415.13 0.00 0.00 0.00 0.00 0.00 0.00 41.47
December 1589.16 11-DEC-20:10 0.00 1660.51 0.00 0.00 0.00 0.00 0.00 0.00 70.56
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1094.64   0.00 415.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2146.34   0.00 4151.28 0.00 0.00 0.00 0.00 0.00 13.35 88.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: REARSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 71.24
February 0.00 01-FEB-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 127.96
March 0.00 01-MAR-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 141.90
April 0.00 01-APR-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 39.17
May 0.00 01-MAY-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 49.07
June 0.00 01-JUN-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 25.35
July 0.00 01-JUL-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 12.47
August 0.00 01-AUG-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 15.27
September 0.00 01-SEP-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 24.29
October 0.00 01-OCT-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 39.04
November 0.00 01-NOV-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 32.95
December 0.00 01-DEC-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 76.34
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 12.47
Maximum of Months 0.00   0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 141.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM201

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 393.49 18-JAN-15:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 104.61
February 361.67 05-FEB-15:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.76
March 324.27 05-MAR-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54.76
April 240.21 03-APR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.52
May 103.80 13-MAY-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.34
June 152.95 30-JUN-18:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.69 0.00
July 156.35 03-JUL-18:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 107.99 04-AUG-15:33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.90 0.00
September 100.51 18-SEP-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.03
October 149.78 22-OCT-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.87
November 417.99 25-NOV-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 66.67
December 396.05 08-DEC-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85.45
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 100.51   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 417.99   0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.90 104.61



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM202_205

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9438.95 14-JAN-09:01 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 63.02
February 9815.09 26-FEB-09:01 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 29.15
March 10161.73 21-MAR-08:61 1584.00 1746.50 6671.21 0.00 0.00 0.00 0.00 0.00 67.19
April 10486.74 17-APR-16:51 4276.80 1111.41 7912.36 0.00 0.00 0.00 0.00 0.00 2.16
May 10728.57 21-MAY-17:01 4276.80 3373.95 7912.36 0.00 0.00 0.00 0.00 0.00 8.21
June 10172.11 16-JUN-16:21 4276.80 1111.41 7912.36 0.00 0.00 0.00 0.00 0.00 4.77
July 10307.10 22-JUL-16:31 4197.60 1309.90 6671.21 0.00 0.00 0.00 0.00 0.00 5.58
August 10629.45 07-AUG-16:31 4276.80 1111.41 7912.36 0.00 0.00 0.00 0.00 0.00 5.36
September 10585.24 12-SEP-16:21 4276.80 1111.41 7912.36 0.00 0.00 0.00 0.00 0.00 1.96
October 9780.38 28-OCT-08:61 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 10.14
November 10213.63 12-NOV-09:01 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 23.86
December 9497.97 02-DEC-09:01 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 66.04
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 9438.95   1584.00 1111.41 6671.21 0.00 0.00 0.00 0.00 0.00 1.96
Maximum of Months 10728.57   4276.80 3373.95 9618.95 0.00 0.00 0.00 0.00 0.00 67.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM206_208

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8266.02 02-JAN-09:01 1782.00 1795.35 7769.15 0.00 0.00 0.00 0.00 0.00 46.10
February 8433.77 12-FEB-09:01 1782.00 1795.35 7769.15 0.00 0.00 0.00 0.00 0.00 39.34
March 8591.88 21-MAR-08:61 1188.00 1410.63 5388.28 0.00 0.00 0.00 0.00 0.00 54.59
April 8710.49 17-APR-16:51 3207.60 897.68 6390.76 0.00 0.00 0.00 0.00 0.00 1.74
May 8940.89 21-MAY-17:01 3207.60 2725.11 6390.76 0.00 0.00 0.00 0.00 0.00 6.62
June 8483.06 16-JUN-16:21 3207.60 897.68 6390.76 0.00 0.00 0.00 0.00 0.00 3.93
July 8584.33 22-JUL-16:31 3148.20 1058.00 5388.28 0.00 0.00 0.00 0.00 0.00 4.55
August 8850.63 07-AUG-16:31 3207.60 897.68 6390.76 0.00 0.00 0.00 0.00 0.00 4.37
September 8837.65 24-SEP-16:11 3148.20 1058.00 5388.28 0.00 0.00 0.00 0.00 0.00 20.38
October 8232.20 28-OCT-08:61 1782.00 1795.35 7769.15 0.00 0.00 0.00 0.00 0.00 8.19
November 8679.89 12-NOV-09:01 1782.00 1795.35 7769.15 0.00 0.00 0.00 0.00 0.00 19.48
December 8301.10 05-DEC-16:01 3207.60 897.68 3258.03 0.00 0.00 0.00 0.00 0.00 63.96
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8232.20   1188.00 897.68 3258.03 0.00 0.00 0.00 0.00 0.00 1.74
Maximum of Months 8940.89   3207.60 2725.11 7769.15 0.00 0.00 0.00 0.00 0.00 63.96



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM209_212

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 10490.23 15-JAN-09:01 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 53.50
February 10339.55 18-FEB-09:01 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 40.93
March 9767.03 05-MAR-19:01 3603.60 2778.52 5321.45 0.00 0.00 0.00 0.00 0.00 64.05
April 9606.96 17-APR-16:51 4276.80 1111.41 7912.36 0.00 0.00 0.00 0.00 0.00 2.17
May 9921.24 21-MAY-17:01 4276.80 3373.95 7912.36 0.00 0.00 0.00 0.00 0.00 8.27
June 9259.40 22-JUN-16:51 4276.80 1111.41 7912.36 0.00 0.00 0.00 0.00 0.00 2.44
July 8999.45 24-JUL-16:21 4276.80 1111.41 7912.36 0.00 0.00 0.00 0.00 0.00 5.12
August 9640.65 07-AUG-16:31 4276.80 1111.41 7912.36 0.00 0.00 0.00 0.00 0.00 4.91
September 9760.02 20-SEP-17:01 4276.80 2659.47 7912.36 0.00 0.00 0.00 0.00 0.00 9.08
October 9200.82 28-OCT-08:61 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 10.18
November 10482.78 25-NOV-09:01 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 95.33
December 10193.22 16-DEC-09:01 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 60.96
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8999.45   2376.00 1111.41 5321.45 0.00 0.00 0.00 0.00 0.00 2.17
Maximum of Months 10490.23   4276.80 3373.95 9618.95 0.00 0.00 0.00 0.00 0.00 95.33



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM213

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 779.80 13-JAN-16:02 1069.20 277.85 1008.44 0.00 0.00 0.00 0.00 0.00 6.82
February 2193.13 25-FEB-09:01 594.00 555.70 2404.74 0.00 0.00 0.00 0.00 0.00 6.57
March 2443.07 21-MAR-18:01 1067.22 618.23 1330.36 0.00 0.00 0.00 0.00 0.00 10.06
April 2599.79 17-APR-16:51 1069.20 277.85 1978.09 0.00 0.00 0.00 0.00 0.00 0.54
May 2651.57 06-MAY-16:51 1049.40 327.48 1667.80 0.00 0.00 0.00 0.00 0.00 3.32
June 2508.02 22-JUN-16:51 1069.20 277.85 1978.09 0.00 0.00 0.00 0.00 0.00 0.60
July 2449.70 18-JUL-18:31 1524.60 883.18 1900.52 0.00 0.00 0.00 0.00 0.00 0.17
August 2648.25 06-AUG-17:01 1069.20 843.49 1978.09 0.00 0.00 0.00 0.00 0.00 2.47
September 2619.99 20-SEP-17:01 1069.20 664.87 1978.09 0.00 0.00 0.00 0.00 0.00 2.10
October 2364.64 28-OCT-08:61 594.00 555.70 2404.74 0.00 0.00 0.00 0.00 0.00 2.42
November 2409.71 04-NOV-18:01 900.90 694.63 1330.36 0.00 0.00 0.00 0.00 0.00 4.13
December 774.99 06-DEC-16:03 1069.20 277.85 1008.44 0.00 0.00 0.00 0.00 0.00 13.71
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 774.99   594.00 277.85 1008.44 0.00 0.00 0.00 0.00 0.00 0.17
Maximum of Months 2651.57   1524.60 883.18 2404.74 0.00 0.00 0.00 0.00 0.00 13.71



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM214

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3073.12 15-JAN-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 13.25
February 3030.30 18-FEB-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 10.15
March 2914.66 13-MAR-08:61 396.00 436.59 1667.68 0.00 0.00 0.00 0.00 0.00 7.43
April 2973.76 17-APR-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.53
May 3039.58 06-MAY-16:51 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 3.49
June 2868.73 22-JUN-16:41 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.58
July 2830.31 23-JUL-16:21 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 0.22
August 2937.97 06-AUG-16:51 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 2.35
September 3022.99 20-SEP-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 2.12
October 2867.43 20-OCT-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 2.03
November 3095.61 25-NOV-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 23.82
December 2935.70 25-DEC-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 10.02
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2830.31   396.00 277.83 1667.68 0.00 0.00 0.00 0.00 0.00 0.22
Maximum of Months 3095.61   1069.20 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 23.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM215_218

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2373.16 19-JAN-16:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 49.96
February 2580.30 24-FEB-17:21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.49
March 3076.40 28-MAR-16:35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34.16
April 3760.54 18-APR-16:12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.10
May 4001.02 31-MAY-16:22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.68 0.00
June 4079.25 29-JUN-16:22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.67 0.00
July 4063.71 15-JUL-16:32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.24
August 4056.03 02-AUG-16:22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.90 0.00
September 4006.93 07-SEP-16:21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.11 0.00
October 3362.05 20-OCT-16:35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.47
November 3046.01 03-NOV-16:22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16.90
December 2382.19 03-DEC-17:22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 59.79
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2373.16   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4079.25   0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.90 59.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ELEVATORCOREFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22.04
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.88
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.34
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.08
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.53
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.96
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.49
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.39
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.88
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.30
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.23
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.96
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.88



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM219

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13168.56 31-JAN-10:41 396.00 277.83 1008.37 0.00 0.00 0.00 0.00 0.00 18.49
February 13329.11 04-FEB-10:31 594.00 406.82 1124.72 0.00 0.00 0.00 0.00 0.00 19.38
March 12975.34 28-MAR-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 5.95
April 13043.27 17-APR-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.33
May 13099.84 21-MAY-19:21 1287.00 992.26 2559.70 0.00 0.00 0.00 0.00 0.00 1.63
June 13084.44 22-JUN-16:41 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.30
July 13078.87 23-JUL-16:21 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 0.02
August 13068.06 16-AUG-16:21 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.17 0.00
September 13058.41 14-SEP-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 1.32
October 12986.85 20-OCT-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 1.43
November 12899.38 03-NOV-16:11 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 2.95
December 7993.63 03-DEC-16:01 594.00 327.45 1124.72 0.00 0.00 0.00 0.00 0.00 11.26
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7993.63   396.00 277.83 1008.37 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13329.11   1287.00 992.26 2559.70 0.00 0.00 0.00 0.00 0.17 19.38



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM220_223

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11335.34 07-JAN-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 53.16
February 11016.17 05-FEB-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 49.48
March 10251.90 05-MAR-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 81.70
April 9850.90 17-APR-16:51 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 2.13
May 10022.19 06-MAY-16:51 4197.60 1309.81 6670.74 0.00 0.00 0.00 0.00 0.00 13.83
June 9526.97 22-JUN-16:41 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 2.37
July 9320.43 23-JUL-16:21 4197.60 1309.81 6670.74 0.00 0.00 0.00 0.00 0.00 0.92
August 9560.73 07-AUG-16:31 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 3.75
September 9917.00 20-SEP-16:51 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 8.34
October 9447.17 28-OCT-08:61 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 10.18
November 11336.40 26-NOV-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 36.86
December 11327.10 10-DEC-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 77.99
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 9320.43   2376.00 1111.33 6670.74 0.00 0.00 0.00 0.00 0.00 0.92
Maximum of Months 11336.40   4276.80 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 81.70



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM224

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2496.41 14-JAN-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 15.60
February 2567.39 26-FEB-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 7.14
March 2725.53 21-MAR-08:61 396.00 436.59 1667.68 0.00 0.00 0.00 0.00 0.00 16.79
April 2775.63 17-APR-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.50
May 2828.66 06-MAY-16:51 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 3.17
June 2715.86 22-JUN-16:41 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.58
July 2666.46 23-JUL-16:21 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 0.22
August 2726.52 07-AUG-16:31 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.90
September 2799.01 20-SEP-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 1.81
October 2605.29 23-OCT-08:61 396.00 436.59 1667.68 0.00 0.00 0.00 0.00 0.00 5.65
November 2758.25 12-NOV-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 6.01
December 2537.76 02-DEC-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 16.45
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2496.41   396.00 277.83 1667.68 0.00 0.00 0.00 0.00 0.00 0.22
Maximum of Months 2828.66   1069.20 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 16.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONTSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 11.62
February 0.00 01-FEB-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 19.65
March 0.00 01-MAR-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 23.34
April 0.00 01-APR-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 6.22
May 0.00 01-MAY-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 7.95
June 0.00 01-JUN-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 3.95
July 0.00 01-JUL-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 1.94
August 0.00 01-AUG-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 2.47
September 0.00 01-SEP-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 3.92
October 0.00 01-OCT-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 6.19
November 0.00 01-NOV-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 5.04
December 0.00 01-DEC-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 12.46
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 1.94
Maximum of Months 0.00   0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 23.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONTSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.18 28-JAN-01:00 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.23 06-FEB-12:50 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 110.50
March 0.09 28-MAR-10:45 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 45.99
April 0.16 18-APR-09:55 0.00 211.68 0.00 0.00 0.00 0.00 0.00 15.04 0.00
May 0.06 02-MAY-10:45 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 35.38
June 0.03 09-JUN-08:11 0.00 1058.40 0.00 0.00 0.00 0.00 0.00 0.00 3.45
July 0.00 01-JUL-00:10 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 15.90
August 0.04 11-AUG-09:55 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.17 0.00
September 0.11 15-SEP-09:55 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.02 19-OCT-10:45 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 31.75
November 0.00 01-NOV-00:10 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 32.33
December 0.18 09-DEC-03:00 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 259.19
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.23   0.00 1058.40 0.00 0.00 0.00 0.00 0.00 15.04 259.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: REARSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.51 27-JAN-10:55 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 176.99
February 0.51 02-FEB-10:55 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 194.21
March 0.35 05-MAR-10:55 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 174.27
April 0.39 15-APR-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 11.10 0.00
May 0.27 02-MAY-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 42.32
June 0.16 13-JUN-11:40 0.00 105.87 0.00 0.00 0.00 0.00 0.00 0.23 0.00
July 0.09 31-JUL-13:40 0.00 105.87 0.00 0.00 0.00 0.00 0.00 0.00 0.09
August 0.28 11-AUG-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 4.27 0.00
September 0.37 20-SEP-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 12.05
October 0.43 20-OCT-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 17.55
November 0.42 11-NOV-11:35 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 110.70
December 0.55 01-DEC-10:55 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 109.79
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.09   0.00 105.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.55   0.00 211.73 0.00 0.00 0.00 0.00 0.00 11.10 194.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDORFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 415.13 0.00 0.00 0.00 0.00 0.00 0.00 65.51
February 871.11 08-FEB-19:35 0.00 830.26 0.00 0.00 0.00 0.00 0.00 0.00 72.93
March 874.61 24-MAR-22:35 0.00 830.26 0.00 0.00 0.00 0.00 0.00 0.00 36.77
April 1057.70 06-APR-06:12 0.00 1660.51 0.00 0.00 0.00 0.00 0.00 0.00 35.42
May 1231.18 31-MAY-18:13 0.00 1245.38 0.00 0.00 0.00 0.00 0.00 6.70 0.00
June 1318.65 30-JUN-18:50 0.00 415.13 0.00 0.00 0.00 0.00 0.00 3.05 0.00
July 1414.68 15-JUL-18:52 0.00 4151.28 0.00 0.00 0.00 0.00 0.00 0.00 3.15
August 1303.48 04-AUG-18:42 0.00 4151.28 0.00 0.00 0.00 0.00 0.00 0.00 20.35
September 1221.03 07-SEP-15:13 0.00 3321.03 0.00 0.00 0.00 0.00 0.00 3.43 0.00
October 895.32 31-OCT-18:45 0.00 830.26 0.00 0.00 0.00 0.00 0.00 0.00 19.57
November 808.59 04-NOV-02:00 0.00 415.13 0.00 0.00 0.00 0.00 0.00 0.00 29.80
December 33.98 03-DEC-15:00 0.00 415.13 0.00 0.00 0.00 0.00 0.00 0.00 80.09
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 415.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1414.68   0.00 4151.28 0.00 0.00 0.00 0.00 0.00 6.70 80.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: REARSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 71.88
February 0.00 01-FEB-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 132.79
March 0.00 01-MAR-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 143.30
April 0.00 01-APR-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 41.83
May 0.00 01-MAY-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 55.36
June 0.00 01-JUN-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 31.63
July 0.00 01-JUL-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 16.73
August 0.00 01-AUG-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 18.68
September 0.00 01-SEP-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 27.81
October 0.00 01-OCT-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 40.77
November 0.00 01-NOV-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 34.64
December 0.00 01-DEC-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 75.09
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 16.73
Maximum of Months 0.00   0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 143.30



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM301

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 294.63 02-JAN-15:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35.12
February 281.69 17-FEB-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.29
March 306.53 05-MAR-15:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 62.02
April 239.75 01-APR-14:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.46
May 119.82 13-MAY-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.39
June 159.85 30-JUN-18:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.75 0.00
July 159.21 03-JUL-18:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 91.80 04-AUG-16:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.04 0.00
September 117.60 18-SEP-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.65
October 152.31 22-OCT-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.99
November 286.27 21-NOV-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.54
December 276.67 20-DEC-15:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32.36
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 91.80   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 306.53   0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.04 62.02



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM302_305

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2164.51 30-JAN-15:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73.95
February 2275.44 01-FEB-15:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73.03
March 1431.24 05-MAR-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 78.61
April 1077.43 01-APR-14:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.68
May 539.64 13-MAY-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.47
June 558.20 01-JUN-14:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.13
July 530.77 05-JUL-17:37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 339.45 02-AUG-16:45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.19 0.00
September 517.99 18-SEP-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.13
October 684.38 22-OCT-14:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.33
November 1845.56 25-NOV-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96.54
December 1736.88 08-DEC-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 122.82
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 339.45   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2275.44   0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.19 122.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM306_308

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1705.43 30-JAN-15:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 60.53
February 1909.41 02-FEB-15:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48.77
March 1148.77 05-MAR-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 65.27
April 855.48 03-APR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.02
May 409.19 13-MAY-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.80
June 440.59 30-JUN-17:37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.29 0.00
July 478.47 05-JUL-17:27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 331.47 02-AUG-16:33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.42 0.00
September 388.83 18-SEP-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.30
October 526.79 22-OCT-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.80
November 1466.17 25-NOV-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 79.34
December 1436.01 11-DEC-15:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.77
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 331.47   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1909.41   0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.42 79.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM309_312

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8839.46 02-JAN-09:01 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 62.99
February 8987.02 12-FEB-09:01 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 53.70
March 9120.70 04-MAR-09:01 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 53.30
April 9133.72 17-APR-16:51 4276.80 1111.41 7912.36 0.00 0.00 0.00 0.00 0.00 2.43
May 9437.87 21-MAY-17:01 4276.80 3373.95 7912.36 0.00 0.00 0.00 0.00 0.00 9.21
June 8782.32 22-JUN-16:51 4276.80 1111.41 7912.36 0.00 0.00 0.00 0.00 0.00 2.73
July 8536.74 18-JUL-18:31 6098.40 3532.72 7602.08 0.00 0.00 0.00 0.00 0.00 0.80
August 9123.29 06-AUG-17:01 4276.80 3373.95 7912.36 0.00 0.00 0.00 0.00 0.00 11.24
September 9189.28 20-SEP-17:01 4276.80 2659.47 7912.36 0.00 0.00 0.00 0.00 0.00 10.14
October 8636.32 28-OCT-08:61 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 11.10
November 9168.14 12-NOV-09:01 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 26.42
December 8680.54 17-DEC-09:01 2376.00 2222.82 9618.95 0.00 0.00 0.00 0.00 0.00 37.42
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8536.74   2376.00 1111.41 7602.08 0.00 0.00 0.00 0.00 0.00 0.80
Maximum of Months 9437.87   6098.40 3532.72 9618.95 0.00 0.00 0.00 0.00 0.00 62.99



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM313

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 418.05 05-JAN-15:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.35
February 381.07 05-FEB-15:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.54
March 338.39 05-MAR-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.57
April 246.08 03-APR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.22
May 111.89 13-MAY-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.23
June 113.19 01-JUN-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.11
July 61.03 05-JUL-18:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.04
August 31.96 30-AUG-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.35
September 108.78 18-SEP-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.74
October 151.64 22-OCT-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.33
November 436.63 25-NOV-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.97
December 409.29 08-DEC-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.59
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 31.96   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.04
Maximum of Months 436.63   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM314

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1372.02 13-JAN-19:01 1067.22 618.18 1330.27 0.00 0.00 0.00 0.00 0.00 6.36
February 2334.00 26-FEB-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 7.81
March 2379.65 21-MAR-18:01 1067.22 618.18 1330.27 0.00 0.00 0.00 0.00 0.00 11.09
April 2589.33 17-APR-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.60
May 2634.67 06-MAY-16:51 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 3.79
June 2488.39 22-JUN-16:41 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.66
July 2444.00 23-JUL-16:21 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 0.25
August 2491.67 06-AUG-16:51 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 2.43
September 2549.02 20-SEP-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 2.05
October 2360.39 20-OCT-20:11 1762.20 883.12 2714.83 0.00 0.00 0.00 0.00 0.00 3.55
November 2344.43 04-NOV-08:61 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 4.00
December 2278.52 03-DEC-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 10.53
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1372.02   594.00 277.83 1330.27 0.00 0.00 0.00 0.00 0.00 0.25
Maximum of Months 2634.67   1762.20 883.12 2714.83 0.00 0.00 0.00 0.00 0.00 11.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM315_318

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12838.43 07-JAN-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 59.68
February 12564.51 05-FEB-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 55.81
March 11768.97 06-MAR-09:01 1584.00 1746.38 6670.74 0.00 0.00 0.00 0.00 0.00 104.53
April 11615.39 30-APR-17:11 3421.44 2698.97 6329.44 0.00 0.00 0.00 0.00 0.00 10.43
May 11715.48 21-MAY-16:51 4197.60 1309.81 6670.74 0.00 0.00 0.00 0.00 0.00 9.21
June 11634.81 22-JUN-16:21 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 3.05
July 11064.07 15-JUL-16:21 4197.60 1309.81 6670.74 0.00 0.00 0.00 0.00 0.00 4.43
August 11202.01 06-AUG-16:51 4197.60 1309.81 6670.74 0.00 0.00 0.00 0.00 0.00 10.56
September 11498.34 24-SEP-16:11 4197.60 1309.81 6670.74 0.00 0.00 0.00 0.00 0.00 27.45
October 11131.02 30-OCT-16:11 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 16.28
November 12824.78 26-NOV-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 41.32
December 12736.56 10-DEC-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 87.56
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11064.07   1584.00 1111.33 6329.44 0.00 0.00 0.00 0.00 0.00 3.05
Maximum of Months 12838.43   4276.80 2698.97 9618.27 0.00 0.00 0.00 0.00 0.00 104.53



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ELEVATORCOREFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.54
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.84
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.97
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.68
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.49
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.29
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.12
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.16
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.48
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.57
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.67
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.70
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.12
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM319

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 570.55 30-JAN-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.81
February 644.15 02-FEB-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16.28
March 363.27 05-MAR-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.06
April 258.20 01-APR-14:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.98
May 147.00 31-MAY-09:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.07
June 140.73 29-JUN-09:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.32
July 147.02 05-JUL-08:52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.07
August 157.91 02-AUG-09:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.05
September 95.65 28-SEP-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.97
October 151.14 22-OCT-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.63
November 457.40 25-NOV-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.35
December 489.08 11-DEC-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.42
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 95.65   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.07
Maximum of Months 644.15   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.35



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM320_323

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9750.64 15-JAN-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 58.89
February 9644.64 18-FEB-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 45.23
March 9225.11 05-MAR-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 89.51
April 8778.23 17-APR-16:51 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 2.32
May 8949.46 06-MAY-16:51 4197.60 1309.81 6670.74 0.00 0.00 0.00 0.00 0.00 14.97
June 8527.79 22-JUN-16:41 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 2.67
July 8352.73 23-JUL-16:21 4197.60 1309.81 6670.74 0.00 0.00 0.00 0.00 0.00 1.05
August 8550.46 07-AUG-16:31 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 4.30
September 8712.99 20-SEP-16:51 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 8.58
October 8496.45 28-OCT-08:61 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 11.28
November 9865.03 25-NOV-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 105.92
December 9453.93 16-DEC-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 67.01
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8352.73   2376.00 1111.33 6670.74 0.00 0.00 0.00 0.00 0.00 1.05
Maximum of Months 9865.03   4276.80 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 105.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM324

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 524.42 30-JAN-15:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.72
February 587.19 02-FEB-15:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.05
March 357.50 05-MAR-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.36
April 267.72 01-APR-14:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.80
May 119.70 13-MAY-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.37
June 125.33 01-JUN-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.21
July 41.41 10-JUL-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.16
August 25.07 30-AUG-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.13
September 110.34 18-SEP-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.70
October 163.82 22-OCT-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.57
November 458.11 25-NOV-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.72
December 449.31 11-DEC-15:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.80
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 25.07   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.21
Maximum of Months 587.19   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.72



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONTSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 12.16
February 0.00 01-FEB-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 20.82
March 0.00 01-MAR-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 24.30
April 0.00 01-APR-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 6.69
May 0.00 01-MAY-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 8.91
June 0.00 01-JUN-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 4.73
July 0.00 01-JUL-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 2.39
August 0.00 01-AUG-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 2.89
September 0.00 01-SEP-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 4.41
October 0.00 01-OCT-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 6.49
November 0.00 01-NOV-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 5.30
December 0.00 01-DEC-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 12.83
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 2.39
Maximum of Months 0.00   0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 24.30



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONTSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.19 28-JAN-01:00 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.28 06-FEB-12:40 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 127.35
March 0.05 06-MAR-11:35 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 106.06
April 0.21 18-APR-09:55 0.00 211.68 0.00 0.00 0.00 0.00 0.00 14.43 0.00
May 0.01 02-MAY-10:45 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 37.82
June 0.00 01-JUN-00:10 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 34.72
July 0.00 01-JUL-00:10 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 19.12
August 0.00 01-AUG-00:10 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 21.32
September 0.03 15-SEP-09:55 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.02 19-OCT-10:45 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 28.49
November 0.03 26-NOV-06:00 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 62.86
December 0.19 09-DEC-03:00 0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 272.08
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 105.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.28   0.00 211.68 0.00 0.00 0.00 0.00 0.00 14.43 272.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: REARSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1.64 06-JAN-11:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 133.54
February 1.73 24-FEB-11:35 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 62.63
March 1.82 06-MAR-11:35 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 125.40
April 1.96 09-APR-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 34.91
May 1.61 30-MAY-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 9.54
June 1.28 08-JUN-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 15.28
July 1.53 29-JUL-10:35 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 2.70
August 2.06 11-AUG-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.95 0.00
September 2.37 15-SEP-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 7.69
October 2.36 20-OCT-10:45 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 19.88
November 1.80 04-NOV-10:35 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 41.77
December 1.96 07-DEC-11:35 0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 61.90
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1.28   0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.37   0.00 211.73 0.00 0.00 0.00 0.00 0.00 0.95 133.54



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDORFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 415.13 0.00 0.00 0.00 0.00 0.00 0.00 70.24
February 625.79 25-FEB-12:45 0.00 830.26 0.00 0.00 0.00 0.00 0.00 0.00 53.37
March 877.75 10-MAR-16:02 0.00 4151.28 0.00 0.00 0.00 0.00 0.00 0.00 51.93
April 1770.48 18-APR-15:02 0.00 4151.28 0.00 0.00 0.00 0.00 0.00 22.24 0.00
May 2113.09 31-MAY-14:50 0.00 415.13 0.00 0.00 0.00 0.00 0.00 15.98 0.00
June 2150.64 09-JUN-14:10 0.00 415.13 0.00 0.00 0.00 0.00 0.00 1.68 0.00
July 2170.71 05-JUL-14:00 0.00 415.13 0.00 0.00 0.00 0.00 0.00 3.95 0.00
August 2011.86 01-AUG-15:23 0.00 1660.51 0.00 0.00 0.00 0.00 0.00 11.92 0.00
September 2203.04 07-SEP-13:30 0.00 415.13 0.00 0.00 0.00 0.00 0.00 5.86 0.00
October 740.22 16-OCT-19:05 0.00 830.26 0.00 0.00 0.00 0.00 0.00 0.00 35.50
November 681.06 09-NOV-14:45 0.00 830.26 0.00 0.00 0.00 0.00 0.00 0.00 132.51
December 0.00 01-DEC-00:10 0.00 415.13 0.00 0.00 0.00 0.00 0.00 0.00 78.69
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 415.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2203.04   0.00 4151.28 0.00 0.00 0.00 0.00 0.00 22.24 132.51



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: REARSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 67.04
February 0.00 01-FEB-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 128.96
March 0.00 01-MAR-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 132.59
April 0.00 01-APR-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 40.08
May 0.00 01-MAY-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 54.34
June 0.00 01-JUN-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 32.48
July 0.00 01-JUL-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 16.89
August 0.00 01-AUG-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 18.14
September 0.00 01-SEP-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 27.48
October 0.00 01-OCT-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 37.62
November 0.00 01-NOV-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 31.02
December 0.00 01-DEC-00:10 0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 70.20
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 16.89
Maximum of Months 0.00   0.00 3.59 0.00 0.00 0.00 0.00 0.00 0.00 132.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM401

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 639.29 13-JAN-19:04 1067.22 618.23 1330.36 0.00 0.00 0.00 0.00 0.00 20.94
February 815.13 25-FEB-16:02 594.00 327.48 1124.80 0.00 0.00 0.00 0.00 0.00 21.60
March 2780.60 23-MAR-18:01 1524.60 883.18 1900.52 0.00 0.00 0.00 0.00 0.00 18.90
April 3223.38 17-APR-17:42 641.52 398.92 1186.85 0.00 0.00 0.00 0.00 0.00 3.59
May 3354.99 21-MAY-18:01 1287.00 992.33 1900.52 0.00 0.00 0.00 0.00 0.00 7.88
June 3154.28 16-JUN-16:21 1069.20 277.85 1978.09 0.00 0.00 0.00 0.00 0.00 5.07
July 3239.60 22-JUL-16:31 1049.40 327.48 1667.80 0.00 0.00 0.00 0.00 0.00 5.73
August 3326.08 29-AUG-16:11 1069.20 277.85 1978.09 0.00 0.00 0.00 0.00 0.00 6.80
September 3234.50 12-SEP-16:21 1069.20 277.85 1978.09 0.00 0.00 0.00 0.00 0.00 1.98
October 2679.40 30-OCT-16:11 1069.20 277.85 1978.09 0.00 0.00 0.00 0.00 0.00 11.73
November 2663.71 04-NOV-18:01 900.90 694.63 1330.36 0.00 0.00 0.00 0.00 0.00 14.22
December 675.67 02-DEC-19:04 900.90 694.63 1330.36 0.00 0.00 0.00 0.00 0.00 22.59
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 639.29   594.00 277.85 1124.80 0.00 0.00 0.00 0.00 0.00 1.98
Maximum of Months 3354.99   1524.60 992.33 1978.09 0.00 0.00 0.00 0.00 0.00 22.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM402_405

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1278.31 03-JAN-15:43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.57
February 1154.82 17-FEB-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.37
March 1339.41 05-MAR-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83.13
April 1001.36 03-APR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 39.73
May 1155.84 31-MAY-16:45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.35 0.00
June 1510.30 25-JUN-16:54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.03 0.00
July 1617.07 05-JUL-16:54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
August 1407.92 04-AUG-15:23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.04 0.00
September 1318.65 07-SEP-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 546.63 22-OCT-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.82
November 1135.70 21-NOV-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.47
December 1169.14 25-DEC-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 39.63
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 546.63   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1617.07   0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.03 83.13



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM406_408

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1046.45 24-JAN-15:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 46.07
February 1164.45 05-FEB-15:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.05
March 1072.67 05-MAR-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 69.13
April 949.05 15-APR-16:33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.05 0.00
May 1069.69 31-MAY-16:45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.71 0.00
June 1384.15 25-JUN-16:54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.14 0.00
July 1467.76 05-JUL-16:54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
August 1295.63 02-AUG-16:22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.68 0.00
September 1212.50 07-SEP-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 419.74 23-OCT-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.03
November 1240.56 25-NOV-15:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 82.37
December 923.66 20-DEC-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34.92
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 419.74   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1467.76   0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.14 82.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM409_412

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8063.77 12-JAN-16:01 4276.80 1111.41 4033.75 0.00 0.00 0.00 0.00 0.00 42.19
February 10006.96 21-FEB-16:01 4276.80 1111.41 4033.75 0.00 0.00 0.00 0.00 0.00 30.89
March 10947.33 21-MAR-18:01 4268.88 2472.90 5321.45 0.00 0.00 0.00 0.00 0.00 49.17
April 11720.26 17-APR-17:42 2566.08 1595.68 4747.42 0.00 0.00 0.00 0.00 0.00 4.74
May 12708.72 20-MAY-17:21 4276.80 3373.95 7912.36 0.00 0.00 0.00 0.00 0.00 14.78
June 12345.40 08-JUN-16:21 4276.80 1111.41 7912.36 0.00 0.00 0.00 0.00 0.00 3.08
July 12531.88 23-JUL-16:21 4197.60 1309.90 6671.21 0.00 0.00 0.00 0.00 0.00 2.33
August 12587.76 16-AUG-16:21 4276.80 1111.41 7912.36 0.00 0.00 0.00 0.00 0.00 3.96
September 11722.58 12-SEP-16:21 4276.80 1111.41 7912.36 0.00 0.00 0.00 0.00 0.00 2.66
October 10973.98 19-OCT-17:11 3421.44 2127.58 6329.89 0.00 0.00 0.00 0.00 0.00 12.82
November 10455.27 04-NOV-18:01 3603.60 2778.52 5321.45 0.00 0.00 0.00 0.00 0.00 19.50
December 8609.64 02-DEC-16:01 2376.00 1309.90 4499.19 0.00 0.00 0.00 0.00 0.00 17.26
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8063.77   2376.00 1111.41 4033.75 0.00 0.00 0.00 0.00 0.00 2.33
Maximum of Months 12708.72   4276.80 3373.95 7912.36 0.00 0.00 0.00 0.00 0.00 49.17



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM413

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 289.29 02-JAN-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.28
February 253.13 17-FEB-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.31
March 305.21 05-MAR-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.66
April 224.03 03-APR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.75
May 255.08 31-MAY-16:45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.84 0.00
June 364.94 30-JUN-17:45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.38 0.00
July 384.84 05-JUL-17:27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01
August 354.16 04-AUG-15:23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.26 0.00
September 379.03 07-SEP-16:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.12 0.00
October 112.28 23-OCT-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.91
November 250.01 21-NOV-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.20
December 262.30 25-DEC-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.91
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 112.28   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 384.84   0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.26 20.66



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM414

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 354.87 27-JAN-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22.71
February 357.66 05-FEB-15:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.23
March 330.10 05-MAR-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.53
April 228.31 03-APR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.00
May 193.40 31-MAY-11:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57 0.00
June 224.03 26-JUN-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.82 0.00
July 217.33 05-JUL-11:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.09
August 216.41 04-AUG-15:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.26 0.00
September 230.63 07-SEP-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.97 0.00
October 132.68 22-OCT-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.76
November 345.53 24-NOV-15:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.54
December 287.55 25-DEC-15:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.32
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 132.68   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 357.66   0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.26 22.71



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM415_418

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 10496.98 02-JAN-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 67.52
February 11008.31 19-FEB-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 66.36
March 11404.11 05-MAR-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 96.44
April 11573.58 30-APR-17:11 3421.44 2698.97 6329.44 0.00 0.00 0.00 0.00 0.00 11.07
May 11712.54 21-MAY-16:51 4197.60 1309.81 6670.74 0.00 0.00 0.00 0.00 0.00 9.88
June 11825.05 22-JUN-16:21 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 3.46
July 11087.07 15-JUL-16:21 4197.60 1309.81 6670.74 0.00 0.00 0.00 0.00 0.00 4.76
August 11114.57 06-AUG-16:51 4197.60 1309.81 6670.74 0.00 0.00 0.00 0.00 0.00 11.34
September 11949.52 15-SEP-16:21 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 2.24
October 11072.53 20-OCT-16:51 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 10.72
November 11223.33 12-NOV-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 28.97
December 11190.63 25-DEC-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 47.32
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10496.98   2376.00 1111.33 6329.44 0.00 0.00 0.00 0.00 0.00 2.24
Maximum of Months 11949.52   4276.80 2698.97 9618.27 0.00 0.00 0.00 0.00 0.00 96.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ELEVATORCOREFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.67
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.63
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35.84
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.10
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.02
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.38
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.34
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.22
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.41
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.70
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.01
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.66
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.34
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35.84



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM419

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2309.55 13-JAN-16:01 1069.20 277.83 1008.37 0.00 0.00 0.00 0.00 0.00 8.12
February 2865.46 19-FEB-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 16.16
March 2962.77 05-MAR-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 23.55
April 3085.18 17-APR-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.63
May 3146.82 21-MAY-16:51 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 2.45
June 3177.97 22-JUN-16:21 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.83
July 2989.67 15-JUL-16:21 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 1.11
August 3032.22 06-AUG-16:51 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 2.80
September 3126.14 20-SEP-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 2.52
October 3005.43 20-OCT-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 2.64
November 2932.35 12-NOV-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 7.08
December 2755.52 02-DEC-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 19.73
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2309.55   594.00 277.83 1008.37 0.00 0.00 0.00 0.00 0.00 0.63
Maximum of Months 3177.97   1069.20 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 23.55



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM420_423

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9877.42 02-JAN-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 67.69
February 10304.75 19-FEB-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 66.39
March 10700.37 05-MAR-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 96.55
April 10625.66 30-APR-17:11 3421.44 2698.97 6329.44 0.00 0.00 0.00 0.00 0.00 10.68
May 10865.40 21-MAY-16:51 4197.60 1309.81 6670.74 0.00 0.00 0.00 0.00 0.00 9.96
June 10745.03 22-JUN-16:21 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 3.25
July 10002.63 23-JUL-16:21 4197.60 1309.81 6670.74 0.00 0.00 0.00 0.00 0.00 1.09
August 10289.71 06-AUG-16:51 4197.60 1309.81 6670.74 0.00 0.00 0.00 0.00 0.00 11.46
September 10604.55 20-SEP-16:51 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 10.39
October 10148.29 20-OCT-16:51 4276.80 1111.33 7911.80 0.00 0.00 0.00 0.00 0.00 10.61
November 10531.55 12-NOV-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 29.03
December 10564.34 25-DEC-09:01 2376.00 2222.66 9618.27 0.00 0.00 0.00 0.00 0.00 47.51
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 9877.42   2376.00 1111.33 6329.44 0.00 0.00 0.00 0.00 0.00 1.09
Maximum of Months 10865.40   4276.80 2698.97 9618.27 0.00 0.00 0.00 0.00 0.00 96.55



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GUESTROOM424

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 659.37 09-JAN-19:04 1067.22 618.18 1330.27 0.00 0.00 0.00 0.00 0.00 10.94
February 1984.54 25-FEB-09:01 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 7.79
March 2591.28 28-MAR-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 7.11
April 2997.82 17-APR-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.63
May 3073.96 21-MAY-16:51 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 2.41
June 2898.10 22-JUN-16:41 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 0.69
July 2862.72 23-JUL-16:21 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 0.26
August 2939.74 06-AUG-16:51 1049.40 327.45 1667.68 0.00 0.00 0.00 0.00 0.00 2.80
September 3025.17 20-SEP-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 2.49
October 2755.60 20-OCT-16:51 1069.20 277.83 1977.95 0.00 0.00 0.00 0.00 0.00 2.20
November 2522.86 04-NOV-08:61 594.00 555.66 2404.57 0.00 0.00 0.00 0.00 0.00 4.08
December 733.08 01-DEC-16:04 1069.20 277.83 1008.37 0.00 0.00 0.00 0.00 0.00 5.47
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 659.37   594.00 277.83 1008.37 0.00 0.00 0.00 0.00 0.00 0.26
Maximum of Months 3073.96   1069.20 618.18 2404.57 0.00 0.00 0.00 0.00 0.00 10.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONTSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 12.46
February 0.00 01-FEB-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 21.98
March 0.00 01-MAR-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 24.58
April 0.00 01-APR-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 6.75
May 0.00 01-MAY-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 9.05
June 0.00 01-JUN-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 4.73
July 0.00 01-JUL-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 2.26
August 0.00 01-AUG-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 2.74
September 0.00 01-SEP-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 4.40
October 0.00 01-OCT-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 6.36
November 0.00 01-NOV-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 5.13
December 0.00 01-DEC-00:10 0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 13.38
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 2.26
Maximum of Months 0.00   0.00 2.24 0.00 0.00 0.00 0.00 0.00 0.00 24.58



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FRONTSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.72 08-JAN-11:35 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 100.25
February 0.93 19-FEB-11:35 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 89.06
March 1.74 28-MAR-10:45 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 44.39
April 2.32 15-APR-10:45 0.00 211.68 0.00 0.00 0.00 0.00 0.00 12.34 0.00
May 1.77 30-MAY-10:45 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 7.55
June 1.74 11-JUN-08:53 0.00 423.36 0.00 0.00 0.00 0.00 0.00 1.65 0.00
July 1.77 17-JUL-09:55 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.21 0.00
August 2.35 11-AUG-10:45 0.00 211.68 0.00 0.00 0.00 0.00 0.00 3.42 0.00
September 2.64 05-SEP-10:45 0.00 211.68 0.00 0.00 0.00 0.00 0.00 1.99 0.00
October 2.06 20-OCT-10:45 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 6.20
November 1.12 14-NOV-11:35 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 34.70
December 1.11 02-DEC-11:35 0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 58.63
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.72   0.00 211.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.64   0.00 423.36 0.00 0.00 0.00 0.00 0.00 12.34 100.25



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.176977E+12 182141.01 31-JAN-07:10 0.164932E+12 151346.75 31-JAN-09:09
February 0.137851E+12 206318.75 02-FEB-07:10 0.142416E+12 156628.46 02-FEB-09:39
March 0.118924E+12 117140.72 06-MAR-07:10 0.144338E+12 136380.55 05-MAR-09:50
April 0.105287E+12 95803.92 03-APR-06:10 0.130503E+12 132456.42 03-APR-11:20
May 0.110030E+12 82413.22 31-MAY-08:00 0.127628E+12 124719.78 07-MAY-08:09
June 0.119133E+12 83288.67 25-JUN-08:00 0.119527E+12 122994.79 11-JUN-08:00
July 0.128240E+12 82795.29 02-JUL-08:00 0.120366E+12 122302.37 01-JUL-08:20
August 0.125545E+12 84253.36 04-AUG-16:10 0.119070E+12 121439.55 06-AUG-08:20
September 0.111516E+12 75495.88 10-SEP-08:00 0.116134E+12 121843.32 16-SEP-08:09
October 0.104995E+12 79205.00 23-OCT-06:19 0.123611E+12 123535.66 28-OCT-08:30
November 0.122807E+12 165636.70 26-NOV-07:10 0.131953E+12 145774.56 26-NOV-09:09
December 0.154379E+12 155052.14 09-DEC-07:10 0.152000E+12 146794.33 09-DEC-09:50
             
Annual Sum or Average 0.151569E+13     0.159248E+13    
Minimum of Months 0.104995E+12 75495.88   0.116134E+12 121439.55  
Maximum of Months 0.176977E+12 206318.75   0.164932E+12 156628.46  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.173962E+11 0.526970E+10 0.400397E+11 0.00 0.241610E+11 21729603.40 0.875311E+11 0.255797E+10 0.00 0.00 0.00 0.00 0.00
February 0.154994E+11 0.439078E+10 0.361667E+11 0.00 0.217853E+11 19626738.56 0.568015E+11 0.318806E+10 0.00 0.00 0.00 0.00 0.00
March 0.168118E+11 0.435074E+10 0.400456E+11 0.00 0.238438E+11 21729603.40 0.270985E+11 0.675206E+10 0.00 0.00 0.00 0.00 0.00
April 0.162497E+11 0.368726E+10 0.387494E+11 0.00 0.231997E+11 21028648.45 0.948314E+10 0.138965E+11 0.00 0.00 0.00 0.00 0.00
May 0.165923E+11 0.335362E+10 0.400436E+11 0.00 0.242202E+11 21729603.40 0.762939E+09 0.250358E+11 0.00 0.00 0.00 0.00 0.00
June 0.160040E+11 0.301616E+10 0.387533E+11 0.00 0.237517E+11 21028648.45 0.191833E+09 0.373953E+11 0.00 0.00 0.00 0.00 0.00
July 0.166190E+11 0.321444E+10 0.400397E+11 0.00 0.246895E+11 21729603.40 6599139.31 0.436489E+11 0.00 0.00 0.00 0.00 0.00
August 0.165960E+11 0.360910E+10 0.400456E+11 0.00 0.245877E+11 21729603.40 20520519.70 0.406644E+11 0.00 0.00 0.00 0.00 0.00
September 0.162623E+11 0.397706E+10 0.387494E+11 0.00 0.235322E+11 21028648.45 0.125695E+10 0.277166E+11 0.00 0.00 0.00 0.00 0.00
October 0.169899E+11 0.465007E+10 0.400417E+11 0.00 0.239139E+11 21729603.40 0.603384E+10 0.133442E+11 0.00 0.00 0.00 0.00 0.00
November 0.167684E+11 0.496656E+10 0.387494E+11 0.00 0.231048E+11 21028648.45 0.316709E+11 0.752608E+10 0.00 0.00 0.00 0.00 0.00
December 0.176489E+11 0.539744E+10 0.400397E+11 0.00 0.239534E+11 21729603.40 0.641051E+11 0.321269E+10 0.00 0.00 0.00 0.00 0.00
                           
Annual Sum or Average 0.199438E+12 0.498829E+11 0.471464E+12 0.00 0.284743E+12 0.255849E+09 0.284963E+12 0.224938E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.154994E+11 0.301616E+10 0.361667E+11 0.00 0.217853E+11 19626738.56 6599139.31 0.255797E+10 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.176489E+11 0.539744E+10 0.400456E+11 0.00 0.246895E+11 21729603.40 0.875311E+11 0.436489E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.357977E+11 0.00 0.320343E+11 0.00 0.970997E+11 0.00 0.00
February 0.323334E+11 0.00 0.212248E+11 0.00 0.888582E+11 0.00 0.00
March 0.357977E+11 0.00 0.108086E+11 0.00 0.977316E+11 0.00 0.00
April 0.346430E+11 0.00 0.376016E+10 0.00 0.921001E+11 0.00 0.00
May 0.357977E+11 0.00 0.319635E+09 0.00 0.915108E+11 0.00 0.00
June 0.346430E+11 0.00 61061369.32 0.00 0.848234E+11 0.00 0.00
July 0.357977E+11 0.00 561433.61 0.00 0.845679E+11 0.00 0.00
August 0.357977E+11 0.00 3808450.31 0.00 0.832680E+11 0.00 0.00
September 0.346430E+11 0.00 0.269625E+09 0.00 0.812212E+11 0.00 0.00
October 0.357977E+11 0.00 0.132075E+10 0.00 0.864928E+11 0.00 0.00
November 0.346430E+11 0.00 0.100145E+11 0.00 0.872957E+11 0.00 0.00
December 0.357977E+11 0.00 0.221198E+11 0.00 0.940824E+11 0.00 0.00
               
Annual Sum or Average 0.421489E+12 0.00 0.101938E+12 0.00 0.106905E+13 0.00 0.00
Minimum of Months 0.323334E+11 0.00 561433.61 0.00 0.812212E+11 0.00 0.00
Maximum of Months 0.357977E+11 0.00 0.320343E+11 0.00 0.977316E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 9436.17 01-JAN-08:09 3177.58 01-JAN-00:10 35131.01 01-JAN-08:09 0.00 11645.01 30-JAN-17:49 8.11 24-JAN-12:50 129479.92 31-JAN-07:10
February 9183.34 04-FEB-19:10 3177.58 01-FEB-00:10 35131.01 04-FEB-08:09 0.00 11706.74 01-FEB-17:49 8.11 01-FEB-08:09 153452.85 02-FEB-07:10
March 9246.28 12-MAR-07:10 3177.58 01-MAR-00:10 35131.01 04-MAR-08:09 0.00 10664.69 28-MAR-16:40 8.11 01-MAR-08:09 67740.39 06-MAR-07:10
April 9183.34 01-APR-18:40 3177.58 01-APR-00:10 35131.01 01-APR-07:10 0.00 10816.84 16-APR-16:40 8.11 01-APR-07:10 46172.93 03-APR-06:10
May 8968.10 13-MAY-18:00 3177.58 01-MAY-00:10 35131.01 06-MAY-07:10 0.00 10873.61 31-MAY-16:00 8.11 01-MAY-07:10 15858.90 02-MAY-06:30
June 9070.57 11-JUN-18:00 3177.58 01-JUN-00:10 35131.01 03-JUN-07:10 0.00 10967.34 25-JUN-16:49 8.11 01-JUN-07:10 7734.99 03-JUN-06:49
July 8931.39 01-JUL-19:00 3177.58 01-JUL-00:10 35131.01 01-JUL-07:10 0.00 10970.92 03-JUL-16:00 8.11 22-JUL-07:00 639.08 10-JUL-15:09
August 9183.34 26-AUG-18:00 3177.58 01-AUG-00:10 35131.01 05-AUG-07:10 0.00 10994.30 04-AUG-15:30 8.11 20-AUG-07:10 2772.02 07-AUG-06:10
September 9183.34 02-SEP-18:49 3177.58 01-SEP-00:10 35131.01 02-SEP-07:10 0.00 10895.54 07-SEP-16:19 8.11 01-SEP-07:10 21459.98 30-SEP-06:30
October 9217.82 22-OCT-07:10 3177.58 01-OCT-00:10 35131.01 01-OCT-07:10 0.00 10678.32 20-OCT-16:40 8.11 01-OCT-07:10 25431.20 28-OCT-06:10
November 9212.91 05-NOV-07:10 3177.58 01-NOV-00:10 35131.01 04-NOV-07:10 0.00 10823.15 26-NOV-09:09 8.11 01-NOV-07:10 119311.98 26-NOV-07:10
December 9486.08 23-DEC-08:09 3177.58 01-DEC-00:10 35131.01 02-DEC-08:09 0.00 10889.35 09-DEC-09:09 8.11 09-DEC-10:20 108360.83 09-DEC-07:10
                           
Annual Sum or Average             0.00            
Minimum of Months 8931.39   3177.58   35131.01   0.00 10664.69   8.11   639.08  
Maximum of Months 9486.08   3177.58   35131.01   0.00 11706.74   8.11   153452.85  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 7169.78 13-JAN-19:10 0.00 0.00 0.00 0.00 0.00
February 11120.57 24-FEB-19:10 0.00 0.00 0.00 0.00 0.00
March 22576.41 19-MAR-20:10 0.00 0.00 0.00 0.00 0.00
April 34111.79 18-APR-15:09 0.00 0.00 0.00 0.00 0.00
May 41517.91 31-MAY-08:00 0.00 0.00 0.00 0.00 0.00
June 44237.93 11-JUN-15:09 0.00 0.00 0.00 0.00 0.00
July 42259.11 03-JUL-18:10 0.00 0.00 0.00 0.00 0.00
August 47771.05 04-AUG-15:09 0.00 0.00 0.00 0.00 0.00
September 39450.33 06-SEP-15:09 0.00 0.00 0.00 0.00 0.00
October 24752.48 20-OCT-20:19 0.00 0.00 0.00 0.00 0.00
November 18395.38 03-NOV-15:09 0.00 0.00 0.00 0.00 0.00
December 7261.16 02-DEC-16:10 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00
Minimum of Months 7169.78   0.00 0.00 0.00 0.00 0.00
Maximum of Months 47771.05   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 182141.01 31-JAN-07:10 7568.56 31369.28 3177.58 0.00 10537.55 8.11 129479.92 0.00 0.00
February 206318.75 02-FEB-07:10 7568.56 31369.28 3177.58 0.00 10742.37 8.11 153452.85 0.00 0.00
March 117140.72 06-MAR-07:10 7335.42 31369.28 0.00 0.00 10170.04 8.11 67740.39 517.47 0.00
April 95803.92 03-APR-06:10 7341.17 31369.28 0.00 0.00 10066.45 8.11 46172.93 845.98 0.00
May 82413.22 31-MAY-08:00 7308.61 22916.29 0.00 0.00 10662.29 8.11 0.00 41517.91 0.00
June 83288.67 25-JUN-08:00 7905.41 26950.62 0.00 0.00 10657.11 8.11 0.00 37767.42 0.00
July 82795.29 02-JUL-08:00 7883.03 26950.62 0.00 0.00 10661.60 8.11 0.00 37291.93 0.00
August 84253.36 04-AUG-16:10 6099.06 21231.33 0.00 0.00 10967.44 8.11 0.00 45947.42 0.00
September 75495.88 10-SEP-08:00 7836.54 26950.62 0.00 0.00 10609.07 8.11 0.00 30091.54 0.00
October 79205.00 23-OCT-06:19 7568.56 31369.28 3177.58 0.00 10040.07 8.11 24749.56 2291.84 0.00
November 165636.70 26-NOV-07:10 6820.87 25914.38 3177.58 0.00 10403.77 8.11 119311.98 0.00 0.00
December 155052.14 09-DEC-07:10 6820.87 25914.38 3177.58 0.00 10375.64 8.11 108360.83 394.73 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 75495.88   6099.06 21231.33 0.00 0.00 10040.07 8.11 0.00 0.00 0.00
Maximum of Months 206318.75   7905.41 31369.28 3177.58 0.00 10967.44 8.11 153452.85 45947.42 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 40096.03 01-JAN-09:09 0.00 28806.52 31-JAN-08:09 0.00 94576.11 29-JAN-08:39 0.00
February 40096.03 01-FEB-09:09 0.00 35248.02 02-FEB-08:09 0.00 95277.14 18-FEB-08:39 0.00
March 40096.03 01-MAR-09:09 0.00 14238.10 05-MAR-12:00 0.00 95096.88 04-MAR-08:39 0.00
April 40096.03 01-APR-08:09 0.00 9688.93 03-APR-11:20 0.00 92685.51 02-APR-07:40 0.00
May 40096.03 01-MAY-08:09 0.00 1885.96 03-MAY-02:00 0.00 86624.36 06-MAY-07:19 0.00
June 40096.03 01-JUN-08:09 0.00 1131.26 03-JUN-03:00 0.00 85345.18 03-JUN-07:19 0.00
July 40096.03 01-JUL-08:09 0.00 112.12 24-JUL-04:00 0.00 84123.76 01-JUL-07:19 0.00
August 40096.03 01-AUG-08:09 0.00 394.33 07-AUG-03:00 0.00 83160.58 06-AUG-07:19 0.00
September 40096.03 01-SEP-08:09 0.00 1994.41 30-SEP-03:00 0.00 83746.96 30-SEP-07:19 0.00
October 40096.03 01-OCT-08:09 0.00 2294.41 26-OCT-09:20 0.00 84889.85 29-OCT-07:19 0.00
November 40096.03 01-NOV-08:09 0.00 23675.62 26-NOV-08:09 0.00 86196.66 26-NOV-08:20 0.00
December 40096.03 01-DEC-09:09 0.00 22550.99 09-DEC-09:09 0.00 91445.10 31-DEC-08:39 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 40096.03   0.00 112.12   0.00 83160.58   0.00
Maximum of Months 40096.03   0.00 35248.02   0.00 95277.14   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: REARSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDORFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: REARSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONTLOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RESTROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MEETINGROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 20.03 0.00 20.03 0.00 20.03 0.00 20.03
                 
Annual Sum or Average 0.17 20.03 0.00 20.03 0.00 20.03 0.00 20.03
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 20.03 0.00 20.03 0.00 20.03 0.00 20.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECHANICALROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM101

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM102

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM103

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 20.55 0.33 20.55 0.00 20.55 0.00 20.55
February 1.00 20.48 1.00 20.48 0.00 20.48 0.00 20.48
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.67 21.82 1.67 21.82
May 0.00 0.00 0.00 0.00 6.83 21.84 6.83 21.84
June 0.00 0.00 0.00 0.00 12.83 22.16 12.83 22.16
July 0.00 0.00 0.00 0.00 18.50 22.38 18.50 22.38
August 0.00 0.00 0.00 0.00 19.00 22.36 19.00 22.36
September 0.00 0.00 0.00 0.00 9.17 22.21 9.17 22.21
October 0.00 0.00 0.00 0.00 0.33 21.77 0.33 21.77
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.33 20.50 1.33 20.50 68.33 22.18 68.33 22.21
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 20.55 1.00 20.55 19.00 22.38 19.00 22.38



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM104

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.50 21.81 2.50 21.81
May 0.00 0.00 0.00 0.00 9.67 21.87 9.67 21.87
June 0.00 0.00 0.00 0.00 16.17 22.12 16.17 22.12
July 0.00 0.00 0.00 0.00 23.17 22.26 23.17 22.26
August 0.00 0.00 0.00 0.00 23.00 22.27 23.00 22.27
September 0.00 0.00 0.00 0.00 12.33 22.12 12.33 22.12
October 0.00 0.00 0.00 0.00 0.83 21.77 0.83 21.77
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   87.67 22.16 87.67 22.16
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 23.17 22.27 23.17 22.27



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM105

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.50 21.94 0.50 21.94
February 0.00 0.00 0.00 0.00 0.83 21.93 0.83 21.93
March 0.00 0.00 0.00 0.00 0.83 21.78 0.83 21.78
April 0.00 0.00 0.00 0.00 4.00 21.93 4.00 21.93
May 0.00 0.00 0.00 0.00 12.67 21.97 12.67 21.97
June 0.00 0.00 0.00 0.00 16.17 22.02 16.17 22.02
July 0.00 0.00 0.00 0.00 23.17 22.05 23.17 22.05
August 0.00 0.00 0.00 0.00 23.00 22.04 23.00 22.04
September 0.00 0.00 0.00 0.00 12.50 21.95 12.50 21.95
October 0.00 0.00 0.00 0.00 1.17 21.87 1.17 21.87
November 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   95.00 22.01 95.00 22.01
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 23.17 22.05 23.17 22.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: EMPLOYEELOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.17 25.13 2.17 25.13
February 0.00 0.00 0.00 0.00 13.67 24.88 13.67 24.88
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   15.83 24.91 15.83 24.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 13.67 25.13 13.67 25.13



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRYROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ELEVATORCOREFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: EXERCISECENTERFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 19.58 0.00 19.58 0.00 19.58 0.00 19.58
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 19.58 0.00 19.58 0.00 19.58 0.00 19.58
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.58 0.00 19.58 0.00 19.58 0.00 19.58



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONTOFFICEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONTSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONTSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: REARSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDORFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: REARSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM201

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM202_205

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 20.46 0.17 20.46 0.00 20.46 0.00 20.46
February 0.50 20.41 0.50 20.41 0.00 20.41 0.00 20.41
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 3.00 22.13 3.00 22.13
May 0.00 0.00 0.00 0.00 9.50 22.23 9.50 22.23
June 0.00 0.00 0.00 0.00 13.17 22.34 13.17 22.34
July 0.00 0.00 0.00 0.00 18.50 22.40 18.50 22.40
August 0.00 0.00 0.00 0.00 19.00 22.36 19.00 22.36
September 0.00 0.00 0.00 0.00 9.33 22.20 9.33 22.20
October 0.00 0.00 0.00 0.00 0.67 21.92 0.67 21.92
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 20.41 0.50 20.41 0.00 20.41 0.00 20.41
                 
Annual Sum or Average 1.17 20.42 1.17 20.42 73.17 22.26 73.17 22.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 20.46 0.50 20.46 19.00 22.40 19.00 22.40



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM206_208

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.17 20.48 0.17 20.48 0.00 20.48 0.00 20.48
March 0.00 0.00 0.00 0.00 0.33 21.70 0.33 21.70
April 0.00 0.00 0.00 0.00 3.00 22.11 3.00 22.11
May 0.00 0.00 0.00 0.00 9.50 22.19 9.50 22.19
June 0.00 0.00 0.00 0.00 13.17 22.29 13.17 22.29
July 0.00 0.00 0.00 0.00 18.50 22.34 18.50 22.34
August 0.00 0.00 0.00 0.00 19.00 22.30 19.00 22.30
September 0.00 0.00 0.00 0.00 9.33 22.16 9.33 22.16
October 0.00 0.00 0.00 0.00 0.67 21.94 0.67 21.94
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 20.48 0.17 20.48 73.50 22.25 73.50 22.26
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 20.48 0.17 20.48 19.00 22.34 19.00 22.34



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM209_212

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.50 21.76 0.50 21.76
April 0.00 0.00 0.00 0.00 3.17 22.18 3.17 22.18
May 0.00 0.00 0.00 0.00 9.33 22.32 9.33 22.32
June 0.00 0.00 0.00 0.00 13.17 22.43 13.17 22.43
July 0.00 0.00 0.00 0.00 18.50 22.51 18.50 22.51
August 0.00 0.00 0.00 0.00 19.00 22.46 19.00 22.46
September 0.00 0.00 0.00 0.00 9.33 22.28 9.33 22.28
October 0.00 0.00 0.00 0.00 0.67 22.03 0.67 22.03
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   73.67 22.40 73.67 22.40
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 19.00 22.51 19.00 22.51



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM213

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 20.54 0.50 20.54 0.00 20.54 0.00 20.54
February 0.83 20.46 0.83 20.46 0.00 20.46 0.00 20.46
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.00 22.06 2.00 22.06
May 0.00 0.00 0.00 0.00 8.50 22.01 8.50 22.01
June 0.00 0.00 0.00 0.00 13.00 22.27 13.00 22.27
July 0.00 0.00 0.00 0.00 18.50 22.34 18.50 22.34
August 0.00 0.00 0.00 0.00 19.00 22.30 19.00 22.30
September 0.00 0.00 0.00 0.00 9.00 22.13 9.00 22.13
October 0.00 0.00 0.00 0.00 0.33 21.69 0.33 21.69
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 20.55 0.17 20.55 0.00 20.55 0.00 20.55
                 
Annual Sum or Average 1.50 20.50 1.50 20.50 70.33 22.17 70.33 22.20
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.83 20.55 0.83 20.55 19.00 22.34 19.00 22.34



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM214

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 3.67 21.97 3.67 21.97
May 0.00 0.00 0.00 0.00 12.50 22.03 12.50 22.03
June 0.00 0.00 0.00 0.00 16.17 22.16 16.17 22.16
July 0.00 0.00 0.00 0.00 23.17 22.22 23.17 22.22
August 0.00 0.00 0.00 0.00 23.00 22.20 23.00 22.20
September 0.00 0.00 0.00 0.00 12.33 22.06 12.33 22.06
October 0.00 0.00 0.00 0.00 1.00 21.78 1.00 21.78
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   91.83 22.14 91.83 22.14
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 23.17 22.22 23.17 22.22



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM215_218

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ELEVATORCOREFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM219

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 57.33 28.78 57.33 28.78
February 0.00 0.00 0.00 0.00 82.00 30.72 82.00 30.72
March 0.00 0.00 0.00 0.00 0.33 28.70 0.33 28.70
April 0.00 0.00 0.00 0.00 2.17 28.83 2.17 28.83
May 0.00 0.00 0.00 0.00 5.00 28.57 5.00 28.57
June 0.00 0.00 0.00 0.00 5.50 27.97 5.50 27.97
July 0.00 0.00 0.00 0.00 7.67 28.30 7.67 28.30
August 0.00 0.00 0.00 0.00 9.50 28.43 9.50 28.43
September 0.00 0.00 0.00 0.00 4.83 28.06 4.83 28.06
October 0.00 0.00 0.00 0.00 0.50 28.70 0.50 28.70
November 0.00 0.00 0.00 0.00 5.50 27.37 5.50 27.37
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   180.33 29.53 180.33 29.53
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 82.00 30.72 82.00 30.72



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM220_223

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.50 21.70 0.50 21.70
April 0.00 0.00 0.00 0.00 3.83 22.10 3.83 22.10
May 0.00 0.00 0.00 0.00 12.67 22.16 12.67 22.16
June 0.00 0.00 0.00 0.00 16.17 22.35 16.17 22.35
July 0.00 0.00 0.00 0.00 23.17 22.42 23.17 22.42
August 0.00 0.00 0.00 0.00 23.17 22.38 23.17 22.38
September 0.00 0.00 0.00 0.00 12.33 22.19 12.33 22.19
October 0.00 0.00 0.00 0.00 1.00 21.84 1.00 21.84
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   92.83 22.31 92.83 22.31
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 23.17 22.42 23.17 22.42



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM224

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 20.54 0.17 20.54 0.00 20.54 0.00 20.54
February 1.00 20.50 1.00 20.50 0.00 20.50 0.00 20.50
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.83 21.92 2.83 21.92
May 0.00 0.00 0.00 0.00 11.50 21.94 11.50 21.94
June 0.00 0.00 0.00 0.00 16.17 22.16 16.17 22.16
July 0.00 0.00 0.00 0.00 23.17 22.24 23.17 22.24
August 0.00 0.00 0.00 0.00 23.00 22.21 23.00 22.21
September 0.00 0.00 0.00 0.00 11.83 22.03 11.83 22.03
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.17 20.51 1.17 20.51 88.50 22.10 88.50 22.12
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 20.54 1.00 20.54 23.17 22.24 23.17 22.24



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONTSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONTSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: REARSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDORFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.83 24.45 0.00 24.45
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.83 24.45 0.00 24.45
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.83 24.45 0.00 24.45



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: REARSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM301

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM302_305

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM306_308

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM309_312

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 20.55 0.17 20.55 0.00 20.55 0.00 20.55
February 0.17 20.51 0.17 20.51 0.00 20.51 0.00 20.51
March 0.00 0.00 0.00 0.00 0.33 21.75 0.33 21.75
April 0.00 0.00 0.00 0.00 3.17 22.22 3.17 22.22
May 0.00 0.00 0.00 0.00 9.17 22.38 9.17 22.38
June 0.00 0.00 0.00 0.00 13.17 22.49 13.17 22.49
July 0.00 0.00 0.00 0.00 18.50 22.56 18.50 22.56
August 0.00 0.00 0.00 0.00 19.00 22.50 19.00 22.50
September 0.00 0.00 0.00 0.00 9.17 22.30 9.17 22.30
October 0.00 0.00 0.00 0.00 0.67 21.96 0.67 21.96
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 20.46 0.33 20.46 0.00 20.46 0.00 20.46
                 
Annual Sum or Average 0.67 20.50 0.67 20.50 73.17 22.42 73.17 22.44
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 20.55 0.33 20.55 19.00 22.56 19.00 22.56



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM313

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM314

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.50 20.54 0.50 20.54 0.00 20.54 0.00 20.54
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 3.17 22.07 3.17 22.07
May 0.00 0.00 0.00 0.00 12.17 22.08 12.17 22.08
June 0.00 0.00 0.00 0.00 16.33 22.30 16.33 22.30
July 0.00 0.00 0.00 0.00 23.17 22.38 23.17 22.38
August 0.00 0.00 0.00 0.00 23.33 22.34 23.33 22.34
September 0.00 0.00 0.00 0.00 12.33 22.14 12.33 22.14
October 0.00 0.00 0.00 0.00 0.17 21.80 0.17 21.80
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.50 20.54 0.50 20.54 90.67 22.25 90.67 22.26
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 20.54 0.50 20.54 23.33 22.38 23.33 22.38



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM315_318

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.83 21.94 0.83 21.94
April 0.00 0.00 0.00 0.00 4.00 22.14 4.00 22.14
May 0.00 0.00 0.00 0.00 12.67 22.19 12.67 22.19
June 0.00 0.00 0.00 0.00 16.17 22.27 16.17 22.27
July 0.00 0.00 0.00 0.00 23.17 22.31 23.17 22.31
August 0.00 0.00 0.00 0.00 23.00 22.29 23.00 22.29
September 0.00 0.00 0.00 0.00 12.33 22.15 12.33 22.15
October 0.00 0.00 0.00 0.00 1.00 22.02 1.00 22.02
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   93.17 22.25 93.17 22.25
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 23.17 22.31 23.17 22.31



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ELEVATORCOREFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM319

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM320_323

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.33 20.52 0.33 20.52 0.00 20.52 0.00 20.52
March 0.00 0.00 0.00 0.00 0.33 21.72 0.33 21.72
April 0.00 0.00 0.00 0.00 3.83 22.15 3.83 22.15
May 0.00 0.00 0.00 0.00 12.50 22.23 12.50 22.23
June 0.00 0.00 0.00 0.00 16.33 22.46 16.33 22.46
July 0.00 0.00 0.00 0.00 23.17 22.54 23.17 22.54
August 0.00 0.00 0.00 0.00 23.33 22.48 23.33 22.48
September 0.00 0.00 0.00 0.00 12.33 22.23 12.33 22.23
October 0.00 0.00 0.00 0.00 0.83 21.82 0.83 21.82
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 20.52 0.33 20.52 92.67 22.39 92.67 22.40
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 20.52 0.33 20.52 23.33 22.54 23.33 22.54



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM324

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONTSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONTSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: REARSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 1.67 6.56 0.00 6.56 0.00 6.56 0.00 6.56
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.67 6.56 0.00 6.56 0.00 6.56 0.00 6.56
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.67 6.56 0.00 6.56 0.00 6.56 0.00 6.56



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDORFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 2.00 20.54 0.00 20.54 0.00 20.54 0.00 20.54
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 1.50 24.53 0.00 24.53
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 3.67 24.67 0.00 24.67
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2.00 20.54 0.00 20.54 5.17 23.49 0.00 23.49
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.00 20.54 0.00 20.54 3.67 24.67 0.00 24.67



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: REARSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM401

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.50 20.37 2.50 20.37 0.00 20.37 0.00 20.37
February 7.17 20.30 7.17 20.30 0.00 20.30 0.00 20.30
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.50 21.98 2.50 21.98
May 0.00 0.00 0.00 0.00 8.83 22.05 8.83 22.05
June 0.00 0.00 0.00 0.00 13.00 22.16 13.00 22.16
July 0.00 0.00 0.00 0.00 18.50 22.19 18.50 22.19
August 0.00 0.00 0.00 0.00 17.83 22.15 17.83 22.15
September 0.00 0.00 0.00 0.00 8.00 22.01 8.00 22.01
October 0.00 0.00 0.00 0.00 0.67 21.72 0.67 21.72
November 0.17 20.52 0.17 20.52 0.00 20.52 0.00 20.52
December 1.17 20.47 1.17 20.47 0.00 20.47 0.00 20.47
                 
Annual Sum or Average 11.00 20.34 11.00 20.34 69.33 21.69 69.33 21.88
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7.17 20.52 7.17 20.52 18.50 22.19 18.50 22.19



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM402_405

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM406_408

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM409_412

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.33 20.45 2.33 20.45 0.00 20.45 0.00 20.45
February 1.67 20.33 1.67 20.33 0.00 20.33 0.00 20.33
March 0.00 0.00 0.00 0.00 0.50 22.01 0.50 22.01
April 0.00 0.00 0.00 0.00 3.17 22.12 3.17 22.12
May 0.00 0.00 0.00 0.00 9.17 22.18 9.17 22.18
June 0.00 0.00 0.00 0.00 13.00 22.27 13.00 22.27
July 0.00 0.00 0.00 0.00 18.50 22.30 18.50 22.30
August 0.00 0.00 0.00 0.00 19.00 22.24 19.00 22.24
September 0.00 0.00 0.00 0.00 9.00 22.12 9.00 22.12
October 0.00 0.00 0.00 0.00 0.67 22.04 0.67 22.04
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.50 20.51 1.50 20.51 0.00 20.51 0.00 20.51
                 
Annual Sum or Average 5.50 20.43 5.50 20.43 73.00 21.99 73.00 22.10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.33 20.51 2.33 20.51 19.00 22.30 19.00 22.30



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM413

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM414

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM415_418

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 20.50 0.50 20.50 0.00 20.50 0.00 20.50
February 1.33 20.43 1.33 20.43 0.00 20.43 0.00 20.43
March 0.00 0.00 0.00 0.00 0.83 21.87 0.83 21.87
April 0.00 0.00 0.00 0.00 4.00 22.10 4.00 22.10
May 0.00 0.00 0.00 0.00 12.67 22.15 12.67 22.15
June 0.00 0.00 0.00 0.00 16.17 22.24 16.17 22.24
July 0.00 0.00 0.00 0.00 23.17 22.29 23.17 22.29
August 0.00 0.00 0.00 0.00 23.00 22.25 23.00 22.25
September 0.00 0.00 0.00 0.00 12.33 22.10 12.33 22.10
October 0.00 0.00 0.00 0.00 1.00 21.96 1.00 21.96
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 20.53 0.33 20.53 0.00 20.53 0.00 20.53
                 
Annual Sum or Average 2.17 20.46 2.17 20.46 93.17 22.13 93.17 22.17
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.33 20.53 1.33 20.53 23.17 22.29 23.17 22.29



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ELEVATORCOREFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM419

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.83 20.51 0.83 20.51 0.00 20.51 0.00 20.51
March 0.00 0.00 0.00 0.00 0.50 21.70 0.50 21.70
April 0.00 0.00 0.00 0.00 4.00 22.00 4.00 22.00
May 0.00 0.00 0.00 0.00 12.50 22.07 12.50 22.07
June 0.00 0.00 0.00 0.00 16.17 22.14 16.17 22.14
July 0.00 0.00 0.00 0.00 23.17 22.20 23.17 22.20
August 0.00 0.00 0.00 0.00 23.00 22.16 23.00 22.16
September 0.00 0.00 0.00 0.00 12.17 22.03 12.17 22.03
October 0.00 0.00 0.00 0.00 1.00 21.80 1.00 21.80
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.83 20.51 0.83 20.51 92.50 22.09 92.50 22.11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.83 20.51 0.83 20.51 23.17 22.20 23.17 22.20



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM420_423

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.17 20.52 1.17 20.52 0.00 20.52 0.00 20.52
February 1.50 20.43 1.50 20.43 0.00 20.43 0.00 20.43
March 0.00 0.00 0.00 0.00 0.67 21.80 0.67 21.80
April 0.00 0.00 0.00 0.00 4.00 22.15 4.00 22.15
May 0.00 0.00 0.00 0.00 12.50 22.22 12.50 22.22
June 0.00 0.00 0.00 0.00 16.33 22.30 16.33 22.30
July 0.00 0.00 0.00 0.00 23.17 22.38 23.17 22.38
August 0.00 0.00 0.00 0.00 23.33 22.33 23.33 22.33
September 0.00 0.00 0.00 0.00 12.33 22.15 12.33 22.15
October 0.00 0.00 0.00 0.00 1.00 21.89 1.00 21.89
November 0.17 20.55 0.17 20.55 0.00 20.55 0.00 20.55
December 0.83 20.52 0.83 20.52 0.00 20.52 0.00 20.52
                 
Annual Sum or Average 3.67 20.48 3.67 20.48 93.33 22.15 93.33 22.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00 20.43 0.00 20.43
Maximum of Months 1.50 20.55 1.50 20.55 23.33 22.38 23.33 22.38



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GUESTROOM424

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.00 20.52 1.00 20.52 0.00 20.52 0.00 20.52
February 1.50 20.40 1.50 20.40 0.00 20.40 0.00 20.40
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 3.17 21.97 3.17 21.97
May 0.00 0.00 0.00 0.00 12.33 22.00 12.33 22.00
June 0.00 0.00 0.00 0.00 16.00 22.14 16.00 22.14
July 0.00 0.00 0.00 0.00 23.17 22.19 23.17 22.19
August 0.00 0.00 0.00 0.00 23.00 22.16 23.00 22.16
September 0.00 0.00 0.00 0.00 11.83 21.99 11.83 21.99
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 20.51 0.33 20.51 0.00 20.51 0.00 20.51
                 
Annual Sum or Average 2.83 20.46 2.83 20.46 89.50 22.01 89.50 22.06
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.50 20.52 1.50 20.52 23.17 22.19 23.17 22.19



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONTSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FRONTSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: REARSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDORFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: REARSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONTLOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.12 554.50 21.11 554.50 21.11
February 672.00 21.20 301.33 21.18 301.33 21.16
March 744.00 21.83 171.50 21.69 171.50 21.60
April 577.50 22.57 78.50 22.67 14.83 22.64
May 233.17 23.69 281.83 23.80 49.33 23.81
June 163.83 23.87 549.00 23.88 134.50 23.88
July 254.67 23.89 732.50 23.89 254.67 23.89
August 242.67 23.89 709.33 23.89 242.67 23.89
September 153.50 23.64 340.50 23.81 11.00 23.81
October 552.00 23.41 14.17 23.42 0.00 23.42
November 616.83 21.87 120.83 21.76 116.33 21.67
December 744.00 21.14 337.17 21.13 337.17 21.13
             
Annual Sum or Average 5698.17 22.17 4191.17 22.48 2187.83 22.39
Minimum of Months 153.50 21.12 14.17 21.11 0.00 21.11
Maximum of Months 744.00 23.89 732.50 23.89 554.50 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: RESTROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 22.34 744.00 22.34 744.00 22.34
February 672.00 22.76 672.00 22.76 672.00 22.76
March 637.83 23.23 492.50 23.15 491.67 23.12
April 417.17 23.74 206.50 23.69 200.17 23.66
May 60.33 23.89 12.00 23.89 0.00 23.89
June 12.83 23.89 136.00 23.89 0.00 23.89
July 0.00 0.00 240.33 23.89 0.00 23.89
August 0.00 0.00 234.50 23.89 0.00 23.89
September 22.00 23.89 119.67 23.89 0.00 23.89
October 165.50 23.89 0.00 23.89 0.00 23.89
November 434.50 23.39 259.00 23.27 259.00 23.21
December 744.00 22.88 744.00 22.88 744.00 22.88
             
Annual Sum or Average 3910.17 23.03 3860.50 23.02 3110.83 22.96
Minimum of Months 0.00 0.00 0.00 22.34 0.00 22.34
Maximum of Months 744.00 23.89 744.00 23.89 744.00 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: MEETINGROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 175.00 21.13 116.17 21.13 116.17 21.12
February 159.00 21.18 60.50 21.17 60.50 21.16
March 178.00 21.43 26.83 21.39 26.83 21.36
April 151.83 21.95 12.00 22.08 2.83 22.09
May 87.33 23.30 48.50 23.51 4.83 23.52
June 63.67 23.60 96.17 23.77 33.83 23.79
July 50.00 23.89 139.17 23.89 49.83 23.89
August 45.50 23.89 134.83 23.89 44.50 23.89
September 59.83 23.15 59.67 23.52 0.67 23.52
October 160.83 22.53 1.50 22.54 0.00 22.54
November 161.83 21.76 19.33 21.69 19.17 21.64
December 175.00 21.17 52.00 21.16 52.00 21.16
             
Annual Sum or Average 1467.83 21.98 766.67 22.30 411.17 22.26
Minimum of Months 45.50 21.13 1.50 21.13 0.00 21.12
Maximum of Months 178.00 23.89 139.17 23.89 116.17 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECHANICALROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM101

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM102

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM103

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.67 646.33 20.64 646.33 20.63
February 672.00 20.78 420.50 20.71 420.50 20.68
March 744.00 20.97 343.50 20.89 343.50 20.85
April 713.17 21.33 81.50 21.33 79.17 21.31
May 727.17 21.92 82.83 22.09 78.17 22.22
June 638.50 21.98 100.33 22.32 56.33 22.45
July 586.33 22.14 154.50 22.71 71.67 22.89
August 591.67 22.13 155.17 22.70 68.17 22.87
September 619.50 21.77 67.33 22.11 6.67 22.13
October 734.50 21.58 2.50 21.59 1.17 21.59
November 720.00 21.19 166.50 21.10 166.50 21.04
December 744.00 20.81 534.00 20.76 534.00 20.74
             
Annual Sum or Average 8234.83 21.41 2755.00 21.43 2472.17 21.37
Minimum of Months 586.33 20.67 2.50 20.64 1.17 20.63
Maximum of Months 744.00 22.14 646.33 22.71 646.33 22.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM104

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.91 433.83 20.85 433.83 20.82
February 672.00 21.03 203.17 20.95 203.17 20.91
March 744.00 21.26 84.50 21.22 84.50 21.18
April 711.67 21.53 10.50 21.54 7.83 21.54
May 707.67 21.94 36.50 22.05 24.17 22.11
June 609.83 21.87 86.00 22.22 31.83 22.31
July 564.83 21.92 127.67 22.47 33.33 22.58
August 568.67 21.95 136.83 22.52 44.50 22.65
September 614.17 21.75 57.50 22.04 0.83 22.04
October 735.33 21.70 1.17 21.71 0.00 21.71
November 720.00 21.39 60.83 21.34 60.83 21.31
December 744.00 21.06 159.50 21.00 159.50 20.96
             
Annual Sum or Average 8136.17 21.50 1398.00 21.58 1084.33 21.55
Minimum of Months 564.83 20.91 1.17 20.85 0.00 20.82
Maximum of Months 744.00 21.95 433.83 22.52 433.83 22.65



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM105

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.61 0.00 21.61 0.00 21.61
February 672.00 21.65 0.00 21.65 0.00 21.65
March 733.17 21.72 8.50 21.76 0.00 21.76
April 660.17 21.69 31.17 21.86 0.00 21.86
May 540.67 21.54 97.50 22.13 2.67 22.15
June 456.33 21.40 129.00 22.25 6.50 22.29
July 395.00 21.30 185.83 22.56 9.50 22.61
August 401.67 21.36 185.00 22.58 14.33 22.66
September 501.83 21.44 90.00 22.05 0.33 22.05
October 702.50 21.70 15.83 21.78 0.00 21.78
November 718.83 21.72 0.33 21.72 0.00 21.72
December 744.00 21.66 0.00 21.66 0.00 21.66
             
Annual Sum or Average 7270.17 21.60 743.17 21.94 33.33 21.96
Minimum of Months 395.00 21.30 0.00 21.61 0.00 21.61
Maximum of Months 744.00 21.72 185.83 22.58 14.33 22.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: EMPLOYEELOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 76.67 21.80 319.67 23.49 0.00 23.49
February 42.33 21.69 323.33 23.67 0.00 23.67
March 17.67 23.72 405.17 23.88 15.00 23.88
April 63.67 23.89 433.67 23.89 63.67 23.89
May 191.83 23.89 465.00 23.89 191.83 23.89
June 261.00 23.89 450.00 23.89 261.00 23.89
July 304.00 23.89 465.00 23.89 304.00 23.89
August 295.00 23.89 465.00 23.89 295.00 23.89
September 208.50 23.89 450.00 23.89 208.50 23.89
October 77.17 23.89 465.00 23.89 77.17 23.89
November 45.33 23.44 402.33 23.84 35.17 23.85
December 23.50 21.79 349.67 23.76 0.00 23.76
             
Annual Sum or Average 1606.67 23.69 4993.83 23.84 1451.33 23.85
Minimum of Months 17.67 21.69 319.67 23.49 0.00 23.49
Maximum of Months 304.00 23.89 465.00 23.89 304.00 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRYROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 248.00 80.86 248.00 80.86 248.00 80.86
February 224.00 81.25 224.00 81.25 224.00 81.25
March 248.00 81.76 248.00 81.76 248.00 81.76
April 240.00 82.43 240.00 82.43 240.00 82.43
May 248.00 83.40 248.00 83.40 248.00 83.40
June 240.00 84.05 240.00 84.05 240.00 84.05
July 248.00 84.43 248.00 84.43 248.00 84.43
August 248.00 84.37 248.00 84.37 248.00 84.37
September 240.00 83.98 240.00 83.98 240.00 83.98
October 248.00 83.02 248.00 83.02 248.00 83.02
November 240.00 82.15 240.00 82.15 240.00 82.15
December 248.00 81.26 248.00 81.26 248.00 81.26
             
Annual Sum or Average 2920.00 82.75 2920.00 82.75 2920.00 82.75
Minimum of Months 224.00 80.86 224.00 80.86 224.00 80.86
Maximum of Months 248.00 84.43 248.00 84.43 248.00 84.43



Table of Contents

Report: ComfortReportSimple55Monthly

For: ELEVATORCOREFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: EXERCISECENTERFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 496.00 21.11 66.33 21.11 66.33 21.11
February 448.00 21.11 74.33 21.11 74.33 21.11
March 487.33 21.37 4.17 21.37 4.17 21.37
April 385.67 21.60 49.50 21.86 0.00 21.86
May 155.67 22.55 233.67 23.34 16.17 23.36
June 139.67 23.35 383.17 23.74 88.33 23.76
July 178.00 23.84 484.50 23.87 171.17 23.88
August 167.83 23.78 468.83 23.86 155.17 23.86
September 141.67 22.36 246.50 23.33 1.17 23.33
October 413.83 21.87 19.67 21.96 0.00 21.96
November 447.50 21.43 14.50 21.47 5.33 21.47
December 496.00 21.11 25.33 21.11 25.33 21.11
             
Annual Sum or Average 3957.17 21.72 2070.50 22.38 607.50 22.45
Minimum of Months 139.67 21.11 4.17 21.11 0.00 21.11
Maximum of Months 496.00 23.84 484.50 23.87 171.17 23.88



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONTOFFICEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 682.00 21.14 542.00 21.13 542.00 21.12
February 616.00 21.23 307.50 21.19 307.50 21.17
March 682.00 21.73 196.33 21.60 196.33 21.51
April 580.83 22.37 57.67 22.38 30.33 22.32
May 287.33 23.44 103.50 23.56 0.00 23.56
June 85.50 23.63 387.50 23.84 12.00 23.84
July 44.00 23.89 601.17 23.89 44.00 23.89
August 52.50 23.89 552.83 23.89 48.67 23.89
September 195.00 23.46 224.00 23.69 0.00 23.69
October 627.83 23.11 0.00 23.11 0.00 23.11
November 616.67 21.92 127.33 21.78 127.33 21.68
December 682.00 21.16 407.00 21.14 407.00 21.13
             
Annual Sum or Average 5151.67 22.01 3506.83 22.26 1715.17 22.09
Minimum of Months 44.00 21.14 0.00 21.13 0.00 21.12
Maximum of Months 682.00 23.89 601.17 23.89 542.00 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONTSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONTSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: REARSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDORFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: REARSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM201

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM202_205

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.80 568.33 20.77 568.33 20.75
February 672.00 20.97 286.33 20.89 286.33 20.85
March 742.67 21.27 145.33 21.21 145.33 21.16
April 668.33 21.55 43.00 21.72 13.50 21.73
May 610.67 21.87 109.67 22.40 30.83 22.53
June 504.17 21.81 169.00 22.62 44.50 22.81
July 440.00 21.96 250.83 23.08 74.50 23.33
August 455.83 21.94 220.17 22.99 71.50 23.24
September 551.17 21.66 98.67 22.25 11.67 22.31
October 726.00 21.64 14.67 21.71 0.83 21.71
November 719.83 21.26 161.17 21.18 161.17 21.12
December 744.00 20.89 422.00 20.84 422.00 20.81
             
Annual Sum or Average 7578.67 21.41 2489.17 21.64 1830.50 21.60
Minimum of Months 440.00 20.80 14.67 20.77 0.83 20.75
Maximum of Months 744.00 21.96 568.33 23.08 568.33 23.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM206_208

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.90 466.67 20.85 466.67 20.83
February 672.00 21.08 218.83 21.00 218.83 20.95
March 738.17 21.35 61.17 21.33 59.00 21.29
April 665.33 21.58 35.83 21.77 3.67 21.78
May 610.33 21.85 109.83 22.40 26.33 22.51
June 504.67 21.77 158.83 22.58 38.17 22.74
July 438.17 21.91 233.33 23.03 67.17 23.27
August 460.67 21.93 209.67 22.96 66.33 23.19
September 553.50 21.65 95.17 22.23 9.33 22.28
October 725.33 21.66 14.33 21.73 0.00 21.73
November 719.83 21.34 110.17 21.27 110.17 21.21
December 744.00 21.00 285.33 20.94 285.33 20.90
             
Annual Sum or Average 7576.00 21.45 1999.17 21.71 1351.00 21.69
Minimum of Months 438.17 20.90 14.33 20.85 0.00 20.83
Maximum of Months 744.00 21.93 466.67 23.03 466.67 23.27



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM209_212

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.99 371.83 20.93 371.83 20.90
February 672.00 21.14 167.33 21.07 167.33 21.02
March 740.33 21.39 30.67 21.39 30.00 21.37
April 674.67 21.61 33.17 21.78 6.67 21.80
May 637.83 21.92 102.50 22.39 35.00 22.52
June 535.67 21.88 140.33 22.55 50.50 22.75
July 475.33 22.06 210.33 23.00 85.50 23.26
August 495.50 22.05 196.83 22.93 81.83 23.18
September 576.50 21.73 89.17 22.24 14.00 22.30
October 726.00 21.67 13.67 21.74 0.17 21.74
November 719.83 21.40 65.50 21.35 65.50 21.31
December 744.00 21.09 180.00 21.03 180.00 20.99
             
Annual Sum or Average 7741.67 21.53 1601.33 21.78 1088.33 21.80
Minimum of Months 475.33 20.99 13.67 20.93 0.17 20.90
Maximum of Months 744.00 22.06 371.83 23.00 371.83 23.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM213

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.61 683.33 20.59 683.33 20.58
February 672.00 20.75 442.50 20.68 442.50 20.65
March 744.00 21.00 326.50 20.91 326.50 20.86
April 699.83 21.39 75.67 21.43 63.67 21.41
May 681.67 21.93 87.00 22.23 48.00 22.35
June 577.67 21.92 123.33 22.47 58.17 22.64
July 528.17 22.14 179.67 22.91 84.83 23.16
August 556.33 22.14 172.67 22.85 79.83 23.07
September 607.83 21.73 76.83 22.13 11.67 22.18
October 733.50 21.46 9.00 21.49 7.00 21.50
November 720.00 21.04 271.17 20.95 271.17 20.90
December 744.00 20.69 649.67 20.66 649.67 20.65
             
Annual Sum or Average 8009.00 21.35 3097.33 21.41 2726.33 21.35
Minimum of Months 528.17 20.61 9.00 20.59 7.00 20.58
Maximum of Months 744.00 22.14 683.33 22.91 683.33 23.16



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM214

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.04 302.17 20.97 302.17 20.93
February 672.00 21.22 144.00 21.14 144.00 21.09
March 739.50 21.49 14.00 21.49 12.67 21.48
April 674.33 21.64 21.00 21.74 0.83 21.75
May 622.50 21.81 87.33 22.22 14.17 22.28
June 501.67 21.65 120.83 22.35 25.17 22.47
July 428.50 21.59 174.50 22.65 34.67 22.81
August 453.50 21.71 171.50 22.68 43.33 22.86
September 550.67 21.60 81.33 22.10 2.17 22.11
October 728.67 21.73 9.50 21.77 0.00 21.77
November 719.83 21.45 39.33 21.42 39.33 21.39
December 744.00 21.15 122.67 21.10 122.67 21.06
             
Annual Sum or Average 7579.17 21.48 1288.17 21.72 741.17 21.71
Minimum of Months 428.50 21.04 9.50 20.97 0.00 20.93
Maximum of Months 744.00 21.81 302.17 22.68 302.17 22.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM215_218

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ELEVATORCOREFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM219

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 359.50 22.23 255.67 23.15 48.83 23.60
February 315.33 23.60 278.33 24.38 80.83 25.15
March 239.67 21.56 306.50 22.35 12.33 22.51
April 163.00 22.99 384.33 23.04 40.17 23.43
May 120.50 28.02 523.33 24.35 114.83 24.96
June 141.17 27.57 602.67 24.07 141.17 24.63
July 190.50 27.73 690.50 24.40 190.50 24.99
August 181.50 27.94 666.33 24.50 181.50 25.11
September 113.17 27.31 531.33 23.94 100.17 24.51
October 108.17 22.64 387.17 22.73 21.33 22.98
November 209.67 21.26 291.17 22.15 4.50 22.20
December 335.00 21.12 212.50 21.91 0.00 21.91
             
Annual Sum or Average 2477.17 23.83 5129.83 23.55 936.17 24.07
Minimum of Months 108.17 21.12 212.50 21.91 0.00 21.91
Maximum of Months 359.50 28.02 690.50 24.50 190.50 25.15



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM220_223

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.10 224.33 21.03 224.33 20.99
February 672.00 21.25 122.00 21.19 122.00 21.14
March 739.83 21.50 8.00 21.50 7.00 21.49
April 677.33 21.63 20.00 21.73 1.33 21.74
May 638.33 21.85 81.00 22.21 22.67 22.30
June 525.83 21.74 114.17 22.33 37.17 22.48
July 469.00 21.80 161.50 22.65 60.17 22.87
August 495.50 21.87 163.33 22.65 66.00 22.87
September 576.33 21.67 71.17 22.06 3.17 22.08
October 732.83 21.72 6.67 21.75 0.00 21.75
November 720.00 21.44 31.67 21.41 31.67 21.39
December 744.00 21.18 100.00 21.13 100.00 21.09
             
Annual Sum or Average 7735.00 21.53 1103.83 21.74 675.50 21.76
Minimum of Months 469.00 21.10 6.67 21.03 0.00 20.99
Maximum of Months 744.00 21.87 224.33 22.65 224.33 22.87



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM224

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.77 547.83 20.73 547.83 20.71
February 672.00 20.93 271.17 20.86 271.17 20.82
March 744.00 21.26 125.17 21.20 125.17 21.15
April 696.17 21.56 22.50 21.61 10.33 21.61
May 659.67 21.88 67.33 22.16 19.83 22.23
June 541.50 21.76 109.50 22.33 33.50 22.46
July 472.17 21.76 154.83 22.61 47.17 22.80
August 517.50 21.90 157.00 22.64 57.00 22.83
September 596.17 21.71 65.67 22.07 2.50 22.08
October 738.33 21.67 1.83 21.67 1.33 21.67
November 720.00 21.24 146.67 21.16 146.67 21.10
December 744.00 20.87 403.33 20.80 403.33 20.77
             
Annual Sum or Average 7845.50 21.40 2072.83 21.51 1665.83 21.45
Minimum of Months 472.17 20.77 1.83 20.73 1.33 20.71
Maximum of Months 744.00 21.90 547.83 22.64 547.83 22.83



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONTSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONTSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: REARSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDORFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: REARSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM301

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM302_305

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM306_308

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM309_312

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.84 534.50 20.80 534.50 20.78
February 672.00 21.00 262.50 20.92 262.50 20.88
March 743.00 21.27 108.83 21.23 108.83 21.19
April 678.17 21.53 38.00 21.68 14.17 21.70
May 646.00 21.93 102.50 22.37 39.50 22.50
June 548.17 21.90 144.33 22.53 59.00 22.72
July 502.50 22.12 204.33 22.96 94.17 23.22
August 530.17 22.12 190.50 22.89 89.67 23.12
September 600.67 21.75 81.67 22.19 16.50 22.26
October 729.67 21.55 14.67 21.61 3.00 21.61
November 720.00 21.22 168.17 21.16 168.17 21.11
December 744.00 20.92 393.00 20.86 393.00 20.83
             
Annual Sum or Average 7858.33 21.46 2243.00 21.64 1783.00 21.62
Minimum of Months 502.50 20.84 14.67 20.80 3.00 20.78
Maximum of Months 744.00 22.12 534.50 22.96 534.50 23.22



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM313

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM314

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.67 619.17 20.63 619.17 20.62
February 672.00 20.85 357.00 20.78 357.00 20.74
March 743.83 21.17 185.50 21.10 185.50 21.04
April 686.33 21.47 39.17 21.53 24.33 21.51
May 646.33 21.85 74.50 22.17 21.00 22.25
June 528.33 21.73 122.17 22.35 37.00 22.49
July 464.83 21.77 167.67 22.66 48.83 22.85
August 504.67 21.89 164.17 22.68 57.50 22.87
September 584.50 21.65 69.67 22.04 2.67 22.05
October 738.00 21.55 4.17 21.56 3.17 21.56
November 720.00 21.09 235.67 21.00 235.67 20.95
December 744.00 20.75 579.00 20.71 579.00 20.69
             
Annual Sum or Average 7776.83 21.32 2617.83 21.42 2170.83 21.35
Minimum of Months 464.83 20.67 4.17 20.63 2.67 20.62
Maximum of Months 744.00 21.89 619.17 22.68 619.17 22.87



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM315_318

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.38 15.67 21.35 15.67 21.33
February 672.00 21.52 21.00 21.50 21.00 21.47
March 733.17 21.67 8.33 21.71 0.00 21.71
April 651.17 21.66 43.50 21.88 0.50 21.88
May 524.33 21.54 119.00 22.21 9.33 22.26
June 456.67 21.51 198.50 22.46 20.67 22.56
July 407.33 21.51 270.00 22.77 30.33 22.90
August 417.33 21.58 239.83 22.77 36.50 22.92
September 513.50 21.50 103.83 22.12 1.83 22.13
October 722.83 21.73 13.67 21.80 0.00 21.80
November 719.50 21.62 0.33 21.62 0.33 21.62
December 744.00 21.46 6.67 21.44 6.67 21.43
             
Annual Sum or Average 7305.83 21.56 1040.33 21.95 142.83 21.98
Minimum of Months 407.33 21.38 0.33 21.35 0.00 21.33
Maximum of Months 744.00 21.73 270.00 22.77 36.50 22.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: ELEVATORCOREFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM319

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM320_323

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.96 414.83 20.91 414.83 20.88
February 672.00 21.12 184.00 21.05 184.00 21.01
March 742.17 21.41 38.17 21.38 38.17 21.36
April 683.17 21.58 18.00 21.66 3.00 21.67
May 655.17 21.89 75.83 22.20 29.00 22.29
June 546.00 21.79 116.50 22.33 48.33 22.49
July 498.17 21.90 156.17 22.63 72.83 22.87
August 543.50 21.99 159.50 22.64 76.67 22.85
September 605.83 21.73 61.17 22.04 5.50 22.07
October 737.33 21.65 4.00 21.66 2.50 21.67
November 720.00 21.31 102.00 21.26 102.00 21.23
December 744.00 21.03 256.33 20.96 256.33 20.92
             
Annual Sum or Average 7891.33 21.50 1586.50 21.64 1233.17 21.63
Minimum of Months 498.17 20.96 4.00 20.91 2.50 20.88
Maximum of Months 744.00 21.99 414.83 22.64 414.83 22.87



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM324

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONTSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONTSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: REARSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDORFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: REARSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM401

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.47 744.00 20.47 744.00 20.47
February 672.00 20.50 658.33 20.49 658.33 20.49
March 741.67 20.74 571.00 20.66 571.00 20.63
April 669.17 21.08 341.00 21.12 304.67 21.04
May 603.67 21.75 139.00 22.31 53.17 22.41
June 521.33 21.87 202.17 22.64 71.33 22.86
July 485.67 22.15 266.50 23.08 92.50 23.35
August 491.67 22.02 236.17 22.93 77.83 23.17
September 576.83 21.52 141.33 22.01 52.67 22.03
October 728.00 21.07 316.00 21.05 303.00 21.00
November 720.00 20.69 573.83 20.65 573.83 20.63
December 744.00 20.48 744.00 20.48 744.00 20.48
             
Annual Sum or Average 7698.00 21.11 4933.33 21.23 4246.33 21.14
Minimum of Months 485.67 20.47 139.00 20.47 52.67 20.47
Maximum of Months 744.00 22.15 744.00 23.08 744.00 23.35



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM402_405

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM406_408

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM409_412

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.64 683.33 20.62 683.33 20.61
February 672.00 20.83 467.33 20.76 467.33 20.74
March 734.33 21.16 305.67 21.10 298.67 21.05
April 654.67 21.43 137.00 21.62 93.17 21.60
May 584.17 21.87 133.17 22.52 41.17 22.72
June 519.33 21.95 208.50 22.74 66.50 22.99
July 484.33 22.22 289.33 23.15 101.67 23.45
August 483.33 22.09 265.83 23.04 88.33 23.31
September 556.83 21.67 128.17 22.27 29.17 22.38
October 717.83 21.47 54.00 21.57 36.50 21.55
November 718.67 21.06 316.33 20.98 316.17 20.94
December 744.00 20.71 664.33 20.68 664.33 20.67
             
Annual Sum or Average 7613.50 21.35 3653.00 21.55 2886.33 21.49
Minimum of Months 483.33 20.64 54.00 20.62 29.17 20.61
Maximum of Months 744.00 22.22 683.33 23.15 683.33 23.45



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM413

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM414

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM415_418

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.82 550.67 20.77 550.67 20.75
February 672.00 21.07 279.83 20.98 279.83 20.93
March 735.00 21.43 136.33 21.40 129.67 21.34
April 643.67 21.48 71.50 21.67 27.67 21.65
May 534.83 21.57 122.17 22.19 16.17 22.27
June 483.17 21.63 206.17 22.47 34.83 22.61
July 450.00 21.76 282.83 22.79 55.17 22.97
August 457.83 21.78 262.83 22.77 59.17 22.96
September 533.83 21.53 116.33 22.09 4.50 22.11
October 726.83 21.65 11.17 21.71 0.33 21.71
November 720.00 21.26 200.00 21.17 200.00 21.11
December 744.00 20.90 462.67 20.84 462.67 20.81
             
Annual Sum or Average 7445.17 21.36 2702.50 21.60 1820.67 21.54
Minimum of Months 450.00 20.82 11.17 20.77 0.33 20.75
Maximum of Months 744.00 21.78 550.67 22.79 550.67 22.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: ELEVATORCOREFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM419

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.77 546.50 20.72 546.50 20.70
February 672.00 21.02 274.33 20.93 274.33 20.88
March 736.67 21.39 126.33 21.34 122.50 21.29
April 658.00 21.50 51.50 21.67 15.17 21.66
May 559.50 21.64 105.83 22.19 12.83 22.25
June 487.83 21.63 170.67 22.42 29.17 22.55
July 443.33 21.69 230.83 22.72 42.67 22.89
August 456.17 21.75 204.50 22.71 49.83 22.89
September 545.67 21.56 88.00 22.05 2.67 22.06
October 728.83 21.64 10.00 21.69 0.17 21.69
November 720.00 21.22 195.00 21.13 195.00 21.07
December 744.00 20.86 450.50 20.79 450.50 20.76
             
Annual Sum or Average 7496.00 21.35 2454.00 21.54 1741.33 21.48
Minimum of Months 443.33 20.77 10.00 20.72 0.17 20.70
Maximum of Months 744.00 21.75 546.50 22.72 546.50 22.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM420_423

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.81 581.00 20.77 581.00 20.75
February 672.00 21.02 315.33 20.94 315.33 20.90
March 736.67 21.38 152.83 21.33 148.67 21.28
April 661.83 21.50 76.83 21.65 37.67 21.63
May 574.83 21.69 102.83 22.19 21.33 22.28
June 503.67 21.68 172.67 22.41 41.17 22.56
July 472.67 21.84 237.17 22.74 66.67 22.95
August 481.67 21.85 210.33 22.70 70.83 22.92
September 563.67 21.61 82.83 22.04 7.00 22.07
October 731.50 21.64 11.83 21.68 3.50 21.68
November 720.00 21.22 227.33 21.14 227.33 21.09
December 744.00 20.87 511.00 20.82 511.00 20.80
             
Annual Sum or Average 7606.50 21.38 2682.00 21.55 2031.50 21.50
Minimum of Months 472.67 20.81 11.83 20.77 3.50 20.75
Maximum of Months 744.00 21.85 581.00 22.74 581.00 22.95



Table of Contents

Report: ComfortReportSimple55Monthly

For: GUESTROOM424

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.55 715.50 20.54 715.50 20.53
February 672.00 20.69 533.50 20.64 533.50 20.63
March 744.00 21.08 347.17 20.98 347.17 20.93
April 677.83 21.37 127.50 21.37 111.17 21.30
May 615.00 21.76 85.00 22.16 20.17 22.23
June 507.00 21.66 159.50 22.37 39.83 22.50
July 468.17 21.77 199.17 22.66 51.00 22.85
August 488.33 21.83 173.50 22.64 59.33 22.84
September 576.00 21.59 75.17 21.97 9.50 21.98
October 738.33 21.47 45.17 21.46 44.67 21.46
November 720.00 20.93 381.00 20.84 381.00 20.80
December 744.00 20.58 711.17 20.57 711.17 20.57
             
Annual Sum or Average 7694.67 21.22 3553.33 21.29 3024.00 21.20
Minimum of Months 468.17 20.55 45.17 20.54 9.50 20.53
Maximum of Months 744.00 21.83 715.50 22.66 715.50 22.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONTSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FRONTSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDORFLR1_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDORFLR2_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDORFLR3_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDORFLR4_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ELEVATORCOREFLR1_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ELEVATORCOREFLR2_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ELEVATORCOREFLR3_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ELEVATORCOREFLR4_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: EMPLOYEELOUNGEFLR1_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 465.00000 0.00000 0.00000 0.00000 0.00000
February 420.00000 0.00000 0.00000 0.00000 0.00000
March 465.00000 0.00000 0.00000 0.00000 0.00000
April 450.00000 0.00000 0.00000 0.00000 0.00000
May 465.00000 0.00000 0.00000 0.00000 0.00000
June 450.00000 0.00000 0.00000 0.00000 0.00000
July 465.00000 0.00000 0.00000 0.00000 0.00000
August 465.00000 0.00000 0.00000 0.00000 0.00000
September 450.00000 0.00000 0.00000 0.00000 0.00000
October 465.00000 0.00000 0.00000 0.00000 0.00000
November 450.00000 0.00000 0.00000 0.00000 0.00000
December 465.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 5475.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 420.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 465.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: EXERCISECENTERFLR1_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 496.00000 0.00000 0.00000 0.00000 0.00000
February 448.00000 0.00000 0.00000 0.00000 0.00000
March 496.00000 0.00000 0.00000 0.00000 0.00000
April 480.00000 0.00000 0.00000 0.00000 0.00000
May 496.00000 0.00000 0.00000 0.00000 0.00000
June 480.00000 0.00000 0.00000 0.00000 0.00000
July 496.00000 0.00000 0.00000 0.00000 0.00000
August 496.00000 0.00000 0.00000 0.00000 0.00000
September 480.00000 0.00000 0.00000 0.00000 0.00000
October 496.00000 0.00000 0.00000 0.00000 0.00000
November 480.00000 0.00000 0.00000 0.00000 0.00000
December 496.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 5840.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 448.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 496.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONTLOUNGEFLR1_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONTOFFICEFLR1_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 682.00000 0.00000 0.00000 0.00000 0.00000
February 616.00000 0.00000 0.00000 0.00000 0.00000
March 682.00000 0.00000 0.00000 0.00000 0.00000
April 660.00000 0.00000 0.00000 0.00000 0.00000
May 682.00000 0.00000 0.00000 0.00000 0.00000
June 660.00000 0.00000 0.00000 0.00000 0.00000
July 682.00000 0.00000 0.00000 0.00000 0.00000
August 682.00000 0.00000 0.00000 0.00000 0.00000
September 660.00000 0.00000 0.00000 0.00000 0.00000
October 682.00000 0.00000 0.00000 0.00000 0.00000
November 660.00000 0.00000 0.00000 0.00000 0.00000
December 682.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8030.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 616.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 682.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONTSTAIRSFLR1_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONTSTAIRSFLR2_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONTSTAIRSFLR3_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONTSTAIRSFLR4_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONTSTORAGEFLR1_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONTSTORAGEFLR2_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONTSTORAGEFLR3_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: FRONTSTORAGEFLR4_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM101_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM102_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM103_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM104_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM105_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM201_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM202_205_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM206_208_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM209_212_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM213_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM214_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM215_218_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM219_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM220_223_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM224_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM301_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM302_305_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM306_308_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM309_312_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM313_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM314_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM315_318_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM319_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM320_323_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM324_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM401_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM402_405_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM406_408_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM409_412_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM413_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM414_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM415_418_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM419_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM420_423_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: GUESTROOM424_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRYROOMFLR1_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 248.00000 0.00000 0.00000 0.00000 0.00000
February 224.00000 0.00000 0.00000 0.00000 0.00000
March 248.00000 0.00000 0.00000 0.00000 0.00000
April 240.00000 0.00000 0.00000 0.00000 0.00000
May 248.00000 0.00000 0.00000 0.00000 0.00000
June 240.00000 0.00000 0.00000 0.00000 0.00000
July 248.00000 0.00000 0.00000 0.00000 0.00000
August 248.00000 0.00000 0.00000 0.00000 0.00000
September 240.00000 0.00000 0.00000 0.00000 0.00000
October 248.00000 0.00000 0.00000 0.00000 0.00000
November 240.00000 0.00000 0.00000 0.00000 0.00000
December 248.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 2920.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 224.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 248.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECHANICALROOMFLR1_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MEETINGROOMFLR1_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 175.00000 0.00000 0.00000 0.00000 0.00000
February 159.00000 0.00000 0.00000 0.00000 0.00000
March 178.00000 0.00000 0.00000 0.00000 0.00000
April 170.00000 0.00000 0.00000 0.00000 0.00000
May 177.00000 0.00000 0.00000 0.00000 0.00000
June 172.00000 0.00000 0.00000 0.00000 0.00000
July 175.00000 0.00000 0.00000 0.00000 0.00000
August 178.00000 0.00000 0.00000 0.00000 0.00000
September 170.00000 0.00000 0.00000 0.00000 0.00000
October 176.00000 0.00000 0.00000 0.00000 0.00000
November 170.00000 0.00000 0.00000 0.00000 0.00000
December 175.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 2075.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 159.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 178.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: REARSTAIRSFLR1_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: REARSTAIRSFLR2_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: REARSTAIRSFLR3_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: REARSTAIRSFLR4_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: REARSTORAGEFLR1_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: REARSTORAGEFLR2_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: REARSTORAGEFLR3_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: REARSTORAGEFLR4_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000     0.00000 0.00000
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RESTROOMFLR1_PEOPLE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 744.00000 0.00000 0.00000 0.00000 0.00000
February 672.00000 0.00000 0.00000 0.00000 0.00000
March 744.00000 0.00000 0.00000 0.00000 0.00000
April 720.00000 0.00000 0.00000 0.00000 0.00000
May 744.00000 0.00000 0.00000 0.00000 0.00000
June 720.00000 0.00000 0.00000 0.00000 0.00000
July 744.00000 0.00000 0.00000 0.00000 0.00000
August 744.00000 0.00000 0.00000 0.00000 0.00000
September 720.00000 0.00000 0.00000 0.00000 0.00000
October 744.00000 0.00000 0.00000 0.00000 0.00000
November 720.00000 0.00000 0.00000 0.00000 0.00000
December 744.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 8760.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 672.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 744.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: 101 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10
June 302545.59 85703.13 2.00 222745.10 79800.49 0.00 0.04 11-JUN-15:00 0.00 01-JUN-00:10 81.25 11-JUN-15:00 58.77 11-JUN-15:00 22.48 11-JUN-15:00 23.55 11-JUN-15:00 0.00 01-JUN-00:10
July 1549211.71 405747.29 12.01 1011820.78 537390.93 0.00 0.07 03-JUL-14:40 0.00 01-JUL-00:10 128.72 03-JUL-14:40 84.37 03-JUL-14:40 44.59 03-JUL-15:00 34.56 03-JUL-14:40 0.00 01-JUL-00:10
August 960670.62 264217.24 3.50 557953.28 402717.34 0.00 0.13 04-AUG-15:00 0.00 01-AUG-00:10 255.09 04-AUG-14:30 140.82 04-AUG-15:00 115.48 04-AUG-14:30 70.94 04-AUG-15:00 0.00 01-AUG-00:10
September 966288.89 277777.45 5.80 913567.67 52721.22 0.00 0.08 07-SEP-14:30 0.00 01-SEP-00:10 129.81 07-SEP-14:30 124.33 07-SEP-14:30 7.03 08-SEP-14:30 37.76 07-SEP-14:30 0.00 01-SEP-00:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 3778716.80 1033445.12 23.31 2706086.82 1072629.98 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 1549211.71 405747.29 12.01 1011820.78 537390.93 0.00 0.13   0.00   255.09   140.82   115.48   70.94   0.00  



Table of Contents

Report: DXReportMonthly

For: 102 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  



Table of Contents

Report: DXReportMonthly

For: 103 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 601366.51 148954.80 0.50 446978.27 154388.24 0.00 0.43 16-JAN-16:03 0.00 01-JAN-00:10 1112.44 16-JAN-16:03 731.90 16-JAN-16:03 380.54 16-JAN-16:03 266.44 16-JAN-16:03 0.00 01-JAN-00:10
February 2497432.63 591813.50 4.44 1818461.40 678971.23 0.00 1.00 25-FEB-16:01 0.00 01-FEB-00:10 2948.71 25-FEB-16:01 2081.73 25-FEB-19:01 1028.54 25-FEB-16:01 640.04 25-FEB-16:01 0.00 01-FEB-00:10
March 51893356.50 12811460.91 79.81 36556267.38 15337089.13 0.00 1.00 19-MAR-15:01 0.00 01-MAR-00:10 3150.58 19-MAR-15:01 2364.15 21-MAR-18:01 1453.26 19-MAR-15:01 677.21 19-MAR-15:01 0.00 01-MAR-00:10
April 0.311769E+09 76656752.45 227.55 0.227761E+09 84007741.14 0.00 1.00 06-APR-18:01 0.00 01-APR-00:10 3317.74 18-APR-08:51 2540.18 17-APR-16:51 1494.56 18-APR-08:54 727.82 15-APR-15:01 0.00 01-APR-00:10
May 0.843489E+09 0.205496E+09 462.69 0.599247E+09 0.244242E+09 0.00 1.00 01-MAY-08:61 0.00 01-MAY-02:30 3446.51 11-MAY-20:21 2629.62 06-MAY-16:51 1916.32 11-MAY-20:22 723.44 11-MAY-20:21 0.00 01-MAY-00:10
June 0.156962E+10 0.381886E+09 523.91 0.113021E+10 0.439411E+09 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 3477.47 13-JUN-08:51 2615.79 23-JUN-20:01 1838.17 13-JUN-08:52 734.66 25-JUN-08:51 0.00 01-JUN-00:10
July 0.197796E+10 0.472461E+09 527.13 0.140483E+10 0.573131E+09 0.00 1.00 01-JUL-07:51 0.00 01-JUL-05:11 3507.97 17-JUL-08:51 2648.55 18-JUL-18:31 1811.03 20-JUL-08:52 735.45 17-JUL-08:51 0.00 01-JUL-00:10
August 0.193478E+10 0.463179E+09 531.60 0.139530E+10 0.539489E+09 0.00 1.00 01-AUG-08:51 0.00 01-AUG-05:11 3528.93 22-AUG-08:51 2727.58 06-AUG-17:01 1836.94 22-AUG-08:53 738.96 04-AUG-15:01 0.00 01-AUG-00:10
September 0.139653E+10 0.339247E+09 539.57 0.110711E+10 0.289414E+09 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 3381.46 11-SEP-08:51 2766.86 20-SEP-17:01 1436.08 11-SEP-08:56 714.19 11-SEP-08:51 0.00 01-SEP-00:10
October 0.558366E+09 0.137549E+09 487.94 0.443767E+09 0.114598E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-07:01 3171.11 09-OCT-15:01 2452.18 29-OCT-18:01 1360.01 09-OCT-15:03 680.73 09-OCT-15:01 0.00 01-OCT-00:10
November 0.233862E+09 57551688.16 184.75 0.173720E+09 60141969.44 0.00 1.00 01-NOV-08:61 0.00 01-NOV-07:01 3168.80 08-NOV-16:01 2478.96 04-NOV-18:01 1346.52 08-NOV-16:03 680.34 08-NOV-16:01 0.00 01-NOV-00:10
December 1903224.40 460242.00 1.34 1458306.53 444917.87 0.00 0.87 03-DEC-16:01 0.00 01-DEC-00:10 2488.59 03-DEC-16:01 1759.72 03-DEC-09:01 838.83 03-DEC-16:01 552.89 03-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.888327E+10 0.214804E+10 3571.23 0.652222E+10 0.236105E+10 0.00                            
Minimum of Months 601366.51 148954.80 0.50 446978.27 154388.24 0.00 0.43   0.00   1112.44   731.90   380.54   266.44   0.00  
Maximum of Months 0.197796E+10 0.472461E+09 539.57 0.140483E+10 0.573131E+09 0.00 1.00   0.00   3528.93   2766.86   1916.32   738.96   0.00  



Table of Contents

Report: DXReportMonthly

For: 104 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 5064337.08 1198342.45 9.98 3918021.20 1146315.87 0.00 1.00 01-JAN-09:01 0.00 01-JAN-00:10 2993.97 13-JAN-16:01 2397.05 02-JAN-09:01 814.64 13-JAN-16:01 651.09 13-JAN-16:01 0.00 01-JAN-00:10
February 18627887.09 4470713.47 34.39 14096634.85 4531252.24 0.00 1.00 08-FEB-16:01 0.00 01-FEB-00:10 3088.74 25-FEB-16:01 2462.14 26-FEB-09:01 1093.28 20-FEB-16:01 669.94 25-FEB-16:01 0.00 01-FEB-00:10
March 0.143538E+09 35389007.66 156.46 0.108977E+09 34561173.21 0.00 1.00 11-MAR-09:01 0.00 01-MAR-00:10 3275.27 19-MAR-15:01 2536.59 11-MAR-09:01 1323.77 19-MAR-15:02 704.09 19-MAR-15:01 0.00 01-MAR-00:10
April 0.460571E+09 0.113237E+09 345.29 0.350495E+09 0.110077E+09 0.00 1.00 01-APR-08:61 0.00 01-APR-00:10 3393.17 16-APR-08:11 2741.41 17-APR-16:51 1384.24 14-APR-15:03 734.88 15-APR-15:01 0.00 01-APR-00:10
May 0.111728E+10 0.271954E+09 564.13 0.834909E+09 0.282366E+09 0.00 1.00 01-MAY-08:61 0.00 01-MAY-07:01 3509.60 11-MAY-18:11 2815.66 06-MAY-16:51 1729.83 11-MAY-18:13 742.73 31-MAY-08:51 0.00 01-MAY-00:10
June 0.176009E+10 0.428150E+09 554.23 0.129552E+10 0.464570E+09 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 3523.69 14-JUN-16:51 2752.40 22-JUN-16:41 1642.92 13-JUN-08:05 754.76 11-JUN-15:01 0.00 01-JUN-00:10
July 0.213480E+10 0.510754E+09 551.16 0.153654E+10 0.598268E+09 0.00 1.00 01-JUL-07:01 0.00 01-JUL-05:11 3567.30 20-JUL-08:61 2742.41 23-JUL-16:21 1733.36 20-JUL-08:04 750.65 26-JUL-08:51 0.00 01-JUL-00:10
August 0.208764E+10 0.500225E+09 551.65 0.152557E+10 0.562072E+09 0.00 1.00 01-AUG-06:51 0.00 01-AUG-05:11 3575.05 31-AUG-08:61 2846.40 07-AUG-16:31 1727.39 31-AUG-08:04 764.51 04-AUG-15:01 0.00 01-AUG-00:10
September 0.156420E+10 0.380235E+09 582.70 0.125971E+10 0.304488E+09 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 3452.17 11-SEP-08:61 2923.86 20-SEP-16:51 1368.60 11-SEP-08:07 732.98 11-SEP-08:61 0.00 01-SEP-00:10
October 0.805954E+09 0.198570E+09 608.01 0.667415E+09 0.138539E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-07:01 3241.31 02-OCT-17:21 2747.68 20-OCT-16:51 1198.00 09-OCT-15:03 698.16 02-OCT-17:21 0.00 01-OCT-00:10
November 0.353713E+09 87037714.75 297.35 0.276114E+09 77598810.33 0.00 1.00 01-NOV-08:61 0.00 01-NOV-07:01 3240.15 08-NOV-16:01 2631.55 12-NOV-09:01 1211.76 08-NOV-16:03 697.95 08-NOV-16:01 0.00 01-NOV-00:10
December 14566725.21 3450228.40 20.01 11662049.05 2904676.16 0.00 1.00 01-DEC-16:01 0.00 01-DEC-00:10 3066.33 03-DEC-16:01 2519.23 25-DEC-09:01 936.11 03-DEC-16:01 665.58 03-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.104660E+11 0.253467E+10 4275.35 0.788492E+10 0.258112E+10 0.00                            
Minimum of Months 5064337.08 1198342.45 9.98 3918021.20 1146315.87 0.00 1.00   0.00   2993.97   2397.05   814.64   651.09   0.00  
Maximum of Months 0.213480E+10 0.510754E+09 608.01 0.153654E+10 0.598268E+09 0.00 1.00   0.00   3575.05   2923.86   1733.36   764.51   0.00  



Table of Contents

Report: DXReportMonthly

For: 105 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.389814E+09 97024237.81 399.05 0.358806E+09 31008382.35 0.00 1.00 01-JAN-09:01 0.00 01-JAN-08:61 4346.25 16-JAN-16:01 4013.94 08-JAN-09:01 927.37 16-JAN-16:02 944.67 16-JAN-16:01 0.00 01-JAN-00:10
February 0.630289E+09 0.157035E+09 470.14 0.577234E+09 53055003.08 0.00 1.00 04-FEB-16:01 0.00 01-FEB-00:10 4310.52 20-FEB-16:01 4006.53 18-FEB-09:01 785.34 20-FEB-16:02 937.42 20-FEB-16:01 0.00 01-FEB-00:10
March 0.110746E+10 0.274681E+09 660.69 0.100236E+10 0.105098E+09 0.00 1.00 01-MAR-09:01 0.00 01-MAR-08:61 4602.46 19-MAR-18:41 4166.00 28-MAR-16:51 1102.85 19-MAR-20:12 993.72 19-MAR-18:41 0.00 01-MAR-00:10
April 0.156818E+10 0.386750E+09 646.43 0.137749E+10 0.190685E+09 0.00 1.00 01-APR-08:61 0.00 01-APR-07:01 4855.86 16-APR-08:11 4320.20 30-APR-17:11 1659.14 16-APR-08:14 1037.28 16-APR-08:11 0.00 01-APR-00:10
May 0.225022E+10 0.547945E+09 639.16 0.188514E+10 0.365077E+09 0.00 1.00 01-MAY-08:61 0.00 01-MAY-07:01 4979.67 11-MAY-21:11 4369.60 06-MAY-16:51 1989.56 11-MAY-21:15 1056.83 11-MAY-21:11 0.00 01-MAY-00:10
June 0.273182E+10 0.668836E+09 612.33 0.219830E+10 0.533519E+09 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 5033.93 13-JUN-08:61 4202.29 22-JUN-16:41 2074.52 13-JUN-08:05 1065.04 13-JUN-08:61 0.00 01-JUN-00:10
July 0.301953E+10 0.729926E+09 606.22 0.235863E+10 0.660902E+09 0.00 1.00 01-JUL-07:01 0.00 01-JUL-05:11 5085.79 20-JUL-08:61 4196.08 23-JUL-16:21 2164.85 20-JUL-08:05 1072.69 20-JUL-08:61 0.00 01-JUL-00:10
August 0.294021E+10 0.711873E+09 606.97 0.232039E+10 0.619815E+09 0.00 1.00 01-AUG-06:51 0.00 01-AUG-05:11 5076.82 31-AUG-08:61 4268.83 06-AUG-16:51 2145.20 31-AUG-08:05 1081.18 04-AUG-07:41 0.00 01-AUG-00:10
September 0.247514E+10 0.604999E+09 632.63 0.212577E+10 0.349367E+09 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 4913.59 11-SEP-08:61 4379.12 20-SEP-16:51 1719.66 11-SEP-08:04 1046.54 11-SEP-08:61 0.00 01-SEP-00:10
October 0.193665E+10 0.476050E+09 701.42 0.174747E+10 0.189179E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-07:01 4620.33 02-OCT-17:21 4272.25 19-OCT-17:11 1090.06 02-OCT-18:03 996.95 02-OCT-17:21 0.00 01-OCT-00:10
November 0.128879E+10 0.318522E+09 645.23 0.115575E+10 0.133048E+09 0.00 1.00 01-NOV-08:61 0.00 01-NOV-07:01 4432.32 08-NOV-09:01 4100.02 03-NOV-16:11 1011.22 08-NOV-09:02 961.73 08-NOV-09:01 0.00 01-NOV-00:10
December 0.662816E+09 0.165402E+09 568.29 0.617411E+09 45405409.36 0.00 1.00 01-DEC-09:01 0.00 01-DEC-08:61 4317.80 30-DEC-16:01 4041.55 06-DEC-09:01 856.56 31-DEC-16:02 938.90 30-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.210009E+11 0.513904E+10 7188.55 0.177248E+11 0.327616E+10 0.00                            
Minimum of Months 0.389814E+09 97024237.81 399.05 0.358806E+09 31008382.35 0.00 1.00   0.00   4310.52   4006.53   785.34   937.42   0.00  
Maximum of Months 0.301953E+10 0.729926E+09 701.42 0.235863E+10 0.660902E+09 0.00 1.00   0.00   5085.79   4379.12   2164.85   1081.18   0.00  



Table of Contents

Report: DXReportMonthly

For: 201 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 13274.49 3575.15 0.17 10277.41 2997.08 0.00 0.01 16-APR-15:00 0.00 01-APR-00:10 22.12 16-APR-15:00 17.13 16-APR-15:00 5.00 16-APR-15:00 5.96 16-APR-15:00 0.00 01-APR-00:10
May 1003505.74 270269.31 4.69 808675.87 194829.87 0.00 0.07 31-MAY-15:00 0.00 01-MAY-00:10 140.51 31-MAY-15:00 113.95 31-MAY-15:00 26.56 31-MAY-15:00 38.78 31-MAY-15:00 0.00 01-MAY-00:10
June 24064012.83 6547081.62 61.70 18401235.46 5662777.37 0.00 0.17 11-JUN-15:00 0.00 01-JUN-00:10 347.06 11-JUN-15:00 245.15 11-JUN-15:00 101.91 11-JUN-15:00 98.52 11-JUN-15:00 0.00 01-JUN-00:10
July 27997832.83 7278259.70 90.72 20524024.75 7473808.08 0.00 0.14 03-JUL-15:00 0.00 01-JUL-00:10 309.76 03-JUL-15:00 209.46 03-JUL-15:00 112.90 26-JUL-15:00 82.79 03-JUL-15:00 0.00 01-JUL-00:10
August 9823042.82 2609184.09 34.69 6305614.29 3517428.53 0.00 0.23 04-AUG-15:00 0.00 01-AUG-00:10 506.91 04-AUG-15:00 280.43 04-AUG-15:00 226.48 04-AUG-15:00 139.34 04-AUG-15:00 0.00 01-AUG-00:10
September 2826301.44 798027.78 13.57 2615811.57 210489.87 0.00 0.09 07-SEP-15:00 0.00 01-SEP-00:10 174.84 07-SEP-15:00 167.01 07-SEP-15:00 12.63 11-SEP-15:00 50.51 07-SEP-15:00 0.00 01-SEP-00:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 65727970.14 17506397.65 205.54 48665639.34 17062330.80 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 27997832.83 7278259.70 90.72 20524024.75 7473808.08 0.00 0.23   0.00   506.91   280.43   226.48   139.34   0.00  



Table of Contents

Report: DXReportMonthly

For: 202_205 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 6326300.78 1459555.63 1.32 4735445.07 1590855.71 0.00 1.00 01-JAN-09:01 0.00 01-JAN-00:10 11508.14 13-JAN-19:01 8837.68 14-JAN-09:01 3521.16 13-JAN-19:01 2501.47 13-JAN-19:01 0.00 01-JAN-00:10
February 56019332.64 13372607.81 21.43 40929138.70 15090193.94 0.00 1.00 08-FEB-16:01 0.00 01-FEB-00:10 12003.02 25-FEB-16:01 9306.84 26-FEB-09:01 4455.83 20-FEB-16:01 2597.67 25-FEB-16:01 0.00 01-FEB-00:10
March 0.645685E+09 0.159064E+09 170.98 0.493723E+09 0.151962E+09 0.00 1.00 10-MAR-16:01 0.00 01-MAR-00:10 12777.47 19-MAR-15:01 9777.32 21-MAR-18:01 5503.76 19-MAR-15:02 2733.92 19-MAR-15:01 0.00 01-MAR-00:10
April 0.240558E+10 0.590862E+09 414.51 0.190279E+10 0.502787E+09 0.00 1.00 01-APR-08:61 0.00 01-APR-00:10 13595.93 18-APR-08:51 11119.17 17-APR-16:51 5930.02 18-APR-08:55 2859.60 18-APR-08:51 0.00 01-APR-00:10
May 0.498724E+10 0.121375E+10 598.65 0.381458E+10 0.117267E+10 0.00 1.00 01-MAY-08:61 0.00 01-MAY-07:01 13883.79 11-MAY-20:21 11321.82 06-MAY-16:51 6935.83 11-MAY-20:24 2899.42 11-MAY-20:21 0.00 01-MAY-00:10
June 0.722145E+10 0.175959E+10 584.30 0.537082E+10 0.185062E+10 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 14132.93 13-JUN-08:51 10860.62 16-JUN-16:21 7276.22 13-JUN-08:53 2932.06 13-JUN-08:51 0.00 01-JUN-00:10
July 0.826038E+10 0.198265E+10 570.45 0.595109E+10 0.230929E+10 0.00 1.00 01-JUL-07:51 0.00 01-JUL-05:11 14060.48 17-JUL-08:51 11161.95 23-JUL-16:31 6967.26 17-JUL-08:53 2936.63 17-JUL-08:51 0.00 01-JUL-00:10
August 0.767287E+10 0.184943E+10 570.82 0.554279E+10 0.213007E+10 0.00 1.00 01-AUG-08:51 0.00 01-AUG-05:11 14244.96 22-AUG-08:51 11385.22 07-AUG-16:31 7375.31 22-AUG-08:53 2946.47 22-AUG-08:51 0.00 01-AUG-00:10
September 0.531424E+10 0.130045E+10 575.63 0.418649E+10 0.112774E+10 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 13562.48 11-SEP-08:51 11293.54 12-SEP-16:21 5951.09 12-SEP-08:55 2855.16 11-SEP-08:51 0.00 01-SEP-00:10
October 0.225331E+10 0.556335E+09 532.59 0.178989E+10 0.463422E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-07:01 12584.21 09-OCT-15:01 9993.43 19-OCT-17:11 5183.95 09-OCT-15:02 2701.52 09-OCT-15:01 0.00 01-OCT-00:10
November 0.946254E+09 0.233239E+09 210.14 0.702190E+09 0.244064E+09 0.00 1.00 01-NOV-08:61 0.00 01-NOV-07:01 12498.92 02-NOV-15:01 9883.68 04-NOV-18:01 5190.91 20-NOV-16:01 2686.89 02-NOV-15:01 0.00 01-NOV-00:10
December 11492096.47 2634252.81 1.41 8670848.68 2821247.79 0.00 1.00 02-DEC-09:01 0.00 01-DEC-00:10 11793.37 03-DEC-16:01 9134.82 02-DEC-09:01 4346.89 03-DEC-16:01 2557.81 03-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.397808E+11 0.966285E+10 4252.25 0.298087E+11 0.997214E+10 0.00                            
Minimum of Months 6326300.78 1459555.63 1.32 4735445.07 1590855.71 0.00 1.00   0.00   11508.14   8837.68   3521.16   2501.47   0.00  
Maximum of Months 0.826038E+10 0.198265E+10 598.65 0.595109E+10 0.230929E+10 0.00 1.00   0.00   14244.96   11385.22   7375.31   2946.47   0.00  



Table of Contents

Report: DXReportMonthly

For: 206_208 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 14113424.01 3297138.20 7.17 11007034.35 3106389.66 0.00 1.00 01-JAN-09:01 0.00 01-JAN-00:10 9466.06 13-JAN-16:01 7633.40 02-JAN-09:01 2605.37 13-JAN-16:01 2058.28 13-JAN-16:01 0.00 01-JAN-00:10
February 95339037.08 23016762.29 57.00 73874923.26 21464113.82 0.00 1.00 08-FEB-16:01 0.00 01-FEB-00:10 9856.09 25-FEB-16:01 8004.11 26-FEB-09:01 3264.32 20-FEB-16:02 2134.89 25-FEB-16:01 0.00 01-FEB-00:10
March 0.641949E+09 0.158187E+09 222.48 0.510797E+09 0.131152E+09 0.00 1.00 04-MAR-09:01 0.00 01-MAR-00:10 10347.48 19-MAR-20:01 8326.49 21-MAR-18:01 3861.32 19-MAR-15:02 2223.73 19-MAR-20:01 0.00 01-MAR-00:10
April 0.208853E+10 0.513833E+09 449.83 0.169048E+10 0.398055E+09 0.00 1.00 01-APR-08:61 0.00 01-APR-00:10 11158.16 18-APR-08:51 9259.74 17-APR-16:51 4724.90 18-APR-08:55 2352.25 18-APR-08:51 0.00 01-APR-00:10
May 0.404768E+10 0.986404E+09 599.09 0.314364E+10 0.904041E+09 0.00 1.00 01-MAY-08:61 0.00 01-MAY-07:01 11403.31 11-MAY-20:21 9431.43 06-MAY-16:51 5545.04 11-MAY-20:24 2386.78 11-MAY-20:21 0.00 01-MAY-00:10
June 0.571325E+10 0.139579E+10 582.78 0.428568E+10 0.142758E+10 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 11624.57 13-JUN-08:51 9077.51 16-JUN-16:21 5866.99 13-JUN-08:53 2416.25 13-JUN-08:51 0.00 01-JUN-00:10
July 0.651054E+10 0.156696E+10 568.35 0.472658E+10 0.178396E+10 0.00 1.00 01-JUL-07:51 0.00 01-JUL-05:11 11560.95 17-JUL-08:51 9329.20 23-JUL-16:31 5614.99 17-JUL-08:54 2419.61 17-JUL-08:51 0.00 01-JUL-00:10
August 0.604978E+10 0.146203E+10 569.86 0.440559E+10 0.164419E+10 0.00 1.00 01-AUG-08:51 0.00 01-AUG-05:11 11706.21 22-AUG-08:51 9500.39 07-AUG-16:31 5928.38 22-AUG-08:53 2426.95 22-AUG-08:51 0.00 01-AUG-00:10
September 0.423960E+10 0.103952E+10 580.10 0.337686E+10 0.862748E+09 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 11161.38 11-SEP-08:51 9403.48 12-SEP-16:21 4780.84 12-SEP-08:55 2352.99 11-SEP-08:51 0.00 01-SEP-00:10
October 0.192351E+10 0.475472E+09 561.81 0.156519E+10 0.358311E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-07:01 10280.49 02-OCT-17:21 8521.23 19-OCT-17:11 3883.83 09-OCT-15:02 2212.11 02-OCT-17:21 0.00 01-OCT-00:10
November 0.831858E+09 0.205275E+09 245.48 0.634499E+09 0.197358E+09 0.00 1.00 01-NOV-08:61 0.00 01-NOV-07:01 10253.35 08-NOV-16:01 8316.52 04-NOV-18:01 3858.25 08-NOV-16:02 2207.36 08-NOV-16:01 0.00 01-NOV-00:10
December 24871318.21 5821377.05 9.86 19952429.71 4918888.51 0.00 1.00 01-DEC-16:01 0.00 01-DEC-00:10 9711.10 03-DEC-16:01 7862.34 02-DEC-09:01 3148.20 03-DEC-16:01 2107.06 03-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.321810E+11 0.783561E+10 4453.80 0.244441E+11 0.773688E+10 0.00                            
Minimum of Months 14113424.01 3297138.20 7.17 11007034.35 3106389.66 0.00 1.00   0.00   9466.06   7633.40   2605.37   2058.28   0.00  
Maximum of Months 0.651054E+10 0.156696E+10 599.09 0.472658E+10 0.178396E+10 0.00 1.00   0.00   11706.21   9500.39   5928.38   2426.95   0.00  



Table of Contents

Report: DXReportMonthly

For: 209_212 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 33219728.86 7654384.25 9.02 25702793.29 7516935.57 0.00 1.00 01-JAN-09:01 0.00 01-JAN-00:10 10777.64 16-JAN-16:01 9156.07 15-JAN-09:01 4016.32 16-JAN-16:01 2339.87 16-JAN-16:01 0.00 01-JAN-00:10
February 0.127367E+09 30490653.81 57.08 96635759.45 30731594.46 0.00 1.00 07-FEB-16:01 0.00 01-FEB-00:10 11060.91 25-FEB-16:01 9115.15 18-FEB-09:01 3886.16 20-FEB-16:02 2394.30 25-FEB-16:01 0.00 01-FEB-00:10
March 0.728612E+09 0.178683E+09 207.77 0.562877E+09 0.165734E+09 0.00 1.00 03-MAR-19:01 0.00 01-MAR-00:10 11613.43 19-MAR-20:01 9057.05 21-MAR-18:01 4609.20 19-MAR-15:03 2493.19 19-MAR-20:01 0.00 01-MAR-00:10
April 0.225798E+10 0.554077E+09 431.68 0.176684E+10 0.491142E+09 0.00 1.00 01-APR-08:61 0.00 01-APR-00:10 12538.01 18-APR-08:51 10123.60 17-APR-16:51 5609.99 18-APR-08:55 2637.84 18-APR-08:51 0.00 01-APR-00:10
May 0.446221E+10 0.108445E+10 591.19 0.334439E+10 0.111782E+10 0.00 1.00 01-MAY-08:61 0.00 01-MAY-07:01 12844.38 11-MAY-20:21 10360.68 06-MAY-16:51 6559.70 11-MAY-20:23 2681.83 31-MAY-08:51 0.00 01-MAY-00:10
June 0.640504E+10 0.155974E+10 577.08 0.463631E+10 0.176872E+10 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 13108.69 13-JUN-08:51 9824.96 22-JUN-16:51 7018.69 13-JUN-08:52 2714.39 13-JUN-08:51 0.00 01-JUN-00:10
July 0.740020E+10 0.177430E+10 562.82 0.518316E+10 0.221704E+10 0.00 1.00 01-JUL-07:51 0.00 01-JUL-05:11 13137.15 17-JUL-08:51 9643.72 23-JUL-16:51 6829.12 17-JUL-08:53 2730.28 17-JUL-08:51 0.00 01-JUL-00:10
August 0.692836E+10 0.166729E+10 564.79 0.487748E+10 0.205088E+10 0.00 1.00 01-AUG-08:51 0.00 01-AUG-05:11 13268.52 22-AUG-08:51 10285.42 07-AUG-16:31 7118.44 22-AUG-08:53 2734.35 22-AUG-08:51 0.00 01-AUG-00:10
September 0.487997E+10 0.119278E+10 578.26 0.379186E+10 0.108811E+10 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 12623.08 11-SEP-08:51 10336.77 20-SEP-17:01 5665.85 12-SEP-08:54 2650.16 11-SEP-08:51 0.00 01-SEP-00:10
October 0.229339E+10 0.565547E+09 561.91 0.182926E+10 0.464126E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-07:01 11539.62 02-OCT-17:21 9374.71 19-OCT-17:11 4531.74 09-OCT-15:03 2480.53 02-OCT-17:21 0.00 01-OCT-00:10
November 0.103272E+10 0.253835E+09 255.00 0.772273E+09 0.260443E+09 0.00 1.00 01-NOV-08:61 0.00 01-NOV-07:01 11502.68 08-NOV-16:01 9131.98 04-NOV-18:01 4571.45 08-NOV-16:03 2474.13 08-NOV-16:01 0.00 01-NOV-00:10
December 56758025.80 12939702.22 11.68 44663797.77 12094228.03 0.00 1.00 01-DEC-09:01 0.00 01-DEC-00:10 10952.19 03-DEC-16:01 9050.10 16-DEC-09:01 4135.40 31-DEC-16:01 2373.71 03-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.366058E+11 0.888178E+10 4408.29 0.269315E+11 0.967437E+10 0.00                            
Minimum of Months 33219728.86 7654384.25 9.02 25702793.29 7516935.57 0.00 1.00   0.00   10777.64   9050.10   3886.16   2339.87   0.00  
Maximum of Months 0.740020E+10 0.177430E+10 591.19 0.518316E+10 0.221704E+10 0.00 1.00   0.00   13268.52   10360.68   7118.44   2734.35   0.00  



Table of Contents

Report: DXReportMonthly

For: 213 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 318427.60 79327.86 0.33 234264.87 84162.73 0.00 0.35 13-JAN-16:02 0.00 01-JAN-00:10 907.13 13-JAN-16:02 612.06 13-JAN-16:02 295.06 13-JAN-16:02 219.94 13-JAN-16:02 0.00 01-JAN-00:10
February 2795219.76 664696.73 5.53 1951409.38 843810.38 0.00 1.00 25-FEB-09:01 0.00 01-FEB-00:10 3015.97 25-FEB-16:01 2109.40 25-FEB-09:01 1145.55 25-FEB-16:01 653.52 25-FEB-16:01 0.00 01-FEB-00:10
March 73544789.22 18179116.34 104.12 52564388.99 20980400.23 0.00 1.00 19-MAR-08:61 0.00 01-MAR-00:10 3235.99 19-MAR-15:01 2372.96 21-MAR-18:01 1551.72 19-MAR-15:01 692.66 19-MAR-15:01 0.00 01-MAR-00:10
April 0.407132E+09 99969758.70 277.04 0.308310E+09 98822052.40 0.00 1.00 05-APR-18:01 0.00 01-APR-00:10 3415.56 18-APR-08:51 2768.13 17-APR-16:51 1552.16 18-APR-08:54 720.61 18-APR-08:51 0.00 01-APR-00:10
May 0.983828E+09 0.239579E+09 522.10 0.721128E+09 0.262700E+09 0.00 1.00 01-MAY-08:61 0.00 01-MAY-07:01 3511.60 11-MAY-20:21 2824.33 06-MAY-16:51 1902.53 11-MAY-20:22 735.89 31-MAY-08:51 0.00 01-MAY-00:10
June 0.164300E+10 0.400305E+09 547.52 0.119737E+10 0.445623E+09 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 3578.65 13-JUN-08:51 2684.73 22-JUN-16:51 1940.45 13-JUN-08:51 747.66 25-JUN-08:51 0.00 01-JUN-00:10
July 0.197491E+10 0.473576E+09 553.84 0.140631E+10 0.568594E+09 0.00 1.00 01-JUL-07:51 0.00 01-JUL-05:11 3613.74 17-JUL-08:51 2656.04 18-JUL-18:31 1921.56 17-JUL-08:52 750.79 17-JUL-08:51 0.00 01-JUL-00:10
August 0.183451E+10 0.441583E+09 554.00 0.130923E+10 0.525285E+09 0.00 1.00 01-AUG-08:51 0.00 01-AUG-05:11 3631.62 22-AUG-08:51 2798.97 06-AUG-17:01 1971.01 22-AUG-08:52 749.69 22-AUG-08:51 0.00 01-AUG-00:10
September 0.121133E+10 0.295986E+09 529.50 0.941063E+09 0.270269E+09 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 3468.50 11-SEP-08:51 2796.42 20-SEP-17:01 1542.48 11-SEP-08:55 728.27 11-SEP-08:51 0.00 01-SEP-00:10
October 0.367765E+09 90732279.86 363.60 0.278474E+09 89290296.40 0.00 1.00 01-OCT-08:61 0.00 01-OCT-00:10 3266.62 10-OCT-15:01 2391.97 29-OCT-18:01 1594.95 09-OCT-15:01 697.67 10-OCT-15:01 0.00 01-OCT-00:10
November 0.155688E+09 38476139.89 143.30 0.108880E+09 46808773.65 0.00 1.00 01-NOV-08:61 0.00 01-NOV-00:10 3251.03 08-NOV-16:01 2443.39 04-NOV-18:01 1566.23 08-NOV-16:01 695.13 08-NOV-16:01 0.00 01-NOV-00:10
December 596063.74 149199.06 0.67 464773.92 131289.82 0.00 0.28 03-DEC-09:01 0.00 01-DEC-00:10 702.80 03-DEC-09:01 545.44 03-DEC-09:01 157.37 03-DEC-09:01 172.36 03-DEC-09:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.865542E+10 0.209928E+10 3601.56 0.632598E+10 0.232943E+10 0.00                            
Minimum of Months 318427.60 79327.86 0.33 234264.87 84162.73 0.00 0.28   0.00   702.80   545.44   157.37   172.36   0.00  
Maximum of Months 0.197491E+10 0.473576E+09 554.00 0.140631E+10 0.568594E+09 0.00 1.00   0.00   3631.62   2824.33   1971.01   750.79   0.00  



Table of Contents

Report: DXReportMonthly

For: 214 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 19540786.91 4742154.89 31.69 15235893.23 4304893.68 0.00 1.00 01-JAN-09:01 0.00 01-JAN-00:10 3364.27 01-JAN-16:01 2829.73 15-JAN-09:01 1267.50 01-JAN-16:01 729.41 01-JAN-16:01 0.00 01-JAN-00:10
February 82469304.96 20360411.10 138.66 65584939.19 16884365.77 0.00 1.00 07-FEB-16:01 0.00 01-FEB-00:10 3411.96 25-FEB-16:01 2814.25 18-FEB-09:01 1230.79 20-FEB-16:01 738.45 25-FEB-16:01 0.00 01-FEB-00:10
March 0.342080E+09 84550895.24 332.12 0.280372E+09 61708134.28 0.00 1.00 04-MAR-09:01 0.00 01-MAR-00:10 3497.63 18-MAR-15:01 2881.47 28-MAR-16:51 1292.36 18-MAR-15:02 754.12 18-MAR-15:01 0.00 01-MAR-00:10
April 0.854844E+09 0.210134E+09 518.53 0.702408E+09 0.152436E+09 0.00 1.00 01-APR-08:61 0.00 01-APR-02:40 3722.05 16-APR-08:11 3200.84 17-APR-16:51 1427.27 16-APR-08:15 791.67 16-APR-08:11 0.00 01-APR-00:10
May 0.163128E+10 0.396241E+09 620.87 0.130277E+10 0.328517E+09 0.00 1.00 01-MAY-08:61 0.00 01-MAY-07:01 3805.60 11-MAY-21:11 3269.57 06-MAY-16:51 1672.72 11-MAY-21:15 804.55 31-MAY-08:51 0.00 01-MAY-00:10
June 0.220216E+10 0.535890E+09 606.43 0.170012E+10 0.502039E+09 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 3891.93 13-JUN-08:61 3105.79 22-JUN-16:41 1811.67 13-JUN-08:04 816.82 13-JUN-08:61 0.00 01-JUN-00:10
July 0.250823E+10 0.601616E+09 602.64 0.187900E+10 0.629229E+09 0.00 1.00 01-JUL-07:01 0.00 01-JUL-05:11 3946.19 20-JUL-08:61 3095.86 23-JUL-16:21 1911.26 20-JUL-08:04 824.26 20-JUL-08:61 0.00 01-JUL-00:10
August 0.237325E+10 0.570902E+09 600.93 0.178878E+10 0.584478E+09 0.00 1.00 01-AUG-06:51 0.00 01-AUG-05:11 3957.80 31-AUG-08:61 3165.13 06-AUG-16:51 1939.18 31-AUG-08:04 830.14 04-AUG-07:41 0.00 01-AUG-00:10
September 0.177411E+10 0.432694E+09 621.47 0.145712E+10 0.316982E+09 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 3793.54 11-SEP-08:61 3277.48 20-SEP-16:51 1521.82 11-SEP-08:06 802.59 11-SEP-08:61 0.00 01-SEP-00:10
October 0.969314E+09 0.239334E+09 654.17 0.818920E+09 0.150393E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-07:01 3526.76 02-OCT-17:21 3098.30 20-OCT-16:51 1094.68 09-OCT-15:02 759.28 02-OCT-17:21 0.00 01-OCT-00:10
November 0.442227E+09 0.109191E+09 350.81 0.354202E+09 88025057.05 0.00 1.00 01-NOV-08:61 0.00 01-NOV-07:01 3440.85 08-NOV-16:01 2893.34 04-NOV-18:01 1224.98 20-NOV-16:01 743.82 08-NOV-16:01 0.00 01-NOV-00:10
December 31474286.53 7565286.89 49.48 25083575.26 6390711.28 0.00 1.00 01-DEC-09:01 0.00 01-DEC-00:10 3394.84 03-DEC-16:01 2736.25 05-DEC-19:01 1290.57 31-DEC-16:01 735.23 03-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.132310E+11 0.321322E+10 5127.80 0.103896E+11 0.284139E+10 0.00                            
Minimum of Months 19540786.91 4742154.89 31.69 15235893.23 4304893.68 0.00 1.00   0.00   3364.27   2736.25   1094.68   729.41   0.00  
Maximum of Months 0.250823E+10 0.601616E+09 654.17 0.187900E+10 0.629229E+09 0.00 1.00   0.00   3957.80   3277.48   1939.18   830.14   0.00  



Table of Contents

Report: DXReportMonthly

For: 215_218 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.196606E+10 0.499724E+09 601.55 0.196606E+10 -0.0 0.00 0.09 13-JAN-17:21 0.00 03-JAN-06:45 2343.08 13-JAN-17:23 2343.08 13-JAN-17:23 0.00 02-JAN-15:20 592.13 13-JAN-17:23 0.00 01-JAN-00:10
February 0.233720E+10 0.593515E+09 574.89 0.233720E+10 -0.0 0.00 0.10 24-FEB-17:21 0.00 01-FEB-00:42 2589.87 24-FEB-17:23 2589.87 24-FEB-17:23 0.00 20-FEB-15:05 653.69 24-FEB-17:23 0.00 01-FEB-00:10
March 0.375357E+10 0.951622E+09 741.40 0.375357E+10 0.00 0.00 0.13 28-MAR-15:00 0.00 06-MAR-06:23 3416.66 19-MAR-15:00 3416.66 19-MAR-15:00 0.00 21-MAR-14:40 858.25 19-MAR-15:00 0.00 01-MAR-00:10
April 0.476078E+10 0.120858E+10 720.00 0.474521E+10 15575265.92 0.00 0.19 18-APR-15:00 0.01 03-APR-07:23 5261.48 18-APR-15:00 5000.61 18-APR-15:00 260.87 18-APR-15:00 1406.28 18-APR-15:00 0.00 01-APR-00:10
May 0.642366E+10 0.162271E+10 744.00 0.637482E+10 48841279.68 0.00 0.20 31-MAY-15:00 0.03 02-MAY-05:27 5423.49 31-MAY-15:00 5301.97 31-MAY-15:00 300.59 29-MAY-15:00 1498.54 31-MAY-15:00 0.00 01-MAY-00:10
June 0.717026E+10 0.183719E+10 720.00 0.702685E+10 0.143407E+09 0.00 0.22 11-JUN-15:00 0.04 05-JUN-07:33 6036.46 11-JUN-15:00 5543.09 11-JUN-15:00 502.14 13-JUN-15:00 1764.28 11-JUN-15:00 0.00 01-JUN-00:10
July 0.793370E+10 0.201637E+10 744.00 0.771046E+10 0.223237E+09 0.00 0.20 03-JUL-15:00 0.06 08-JUL-07:51 5786.36 26-JUL-15:00 5296.36 02-JUL-15:00 676.85 26-JUL-15:00 1581.72 26-JUL-15:00 0.00 01-JUL-00:10
August 0.769479E+10 0.195811E+10 744.00 0.749806E+10 0.196727E+09 0.00 0.22 04-AUG-15:00 0.05 25-AUG-07:22 6156.46 04-AUG-15:00 5524.54 04-AUG-15:00 631.93 04-AUG-15:00 1815.79 04-AUG-15:00 0.00 01-AUG-00:10
September 0.643232E+10 0.163930E+10 720.00 0.639847E+10 33852090.73 0.00 0.20 06-SEP-15:00 0.03 30-SEP-06:23 5561.74 06-SEP-15:00 5401.36 07-SEP-15:00 229.64 11-SEP-15:00 1602.34 06-SEP-15:00 0.00 01-SEP-00:10
October 0.497728E+10 0.125919E+10 744.00 0.497728E+10 -0.0 0.00 0.15 20-OCT-15:00 0.02 27-OCT-06:35 4047.78 20-OCT-15:00 4047.78 20-OCT-15:00 0.00 04-OCT-14:10 1013.29 20-OCT-15:00 0.00 01-OCT-00:10
November 0.350848E+10 0.889420E+09 703.16 0.350817E+10 308749.96 0.00 0.12 03-NOV-15:00 0.00 25-NOV-07:01 3336.80 03-NOV-15:00 3336.80 03-NOV-15:00 9.84 09-NOV-02:00 838.07 03-NOV-15:00 0.00 01-NOV-00:10
December 0.244431E+10 0.621085E+09 692.52 0.244431E+10 0.00 0.00 0.09 03-DEC-17:22 0.00 08-DEC-15:02 2371.27 03-DEC-17:22 2371.27 03-DEC-17:22 0.00 22-DEC-15:40 599.19 03-DEC-17:22 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.594024E+11 0.150968E+11 8449.51 0.587404E+11 0.661949E+09 0.00                            
Minimum of Months 0.196606E+10 0.499724E+09 574.89 0.196606E+10 -0.0 0.00 0.09   0.00   2343.08   2343.08   0.00   592.13   0.00  
Maximum of Months 0.793370E+10 0.201637E+10 744.00 0.771046E+10 0.223237E+09 0.00 0.22   0.06   6156.46   5543.09   676.85   1815.79   0.00  



Table of Contents

Report: DXReportMonthly

For: 219 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.549845E+10 0.137035E+10 683.27 0.542714E+10 71308068.36 0.00 1.00 06-JAN-10:01 0.00 01-JAN-08:61 17698.53 31-JAN-10:41 17698.53 31-JAN-10:41 722.58 16-JAN-09:01 3834.99 31-JAN-10:41 0.00 01-JAN-00:10
February 0.517231E+10 0.128636E+10 587.17 0.507486E+10 97455151.94 0.00 1.00 04-FEB-10:31 0.00 01-FEB-00:42 17870.55 04-FEB-10:31 17870.55 04-FEB-10:31 795.89 20-FEB-09:01 3867.48 04-FEB-10:31 0.00 01-FEB-00:10
March 0.697895E+10 0.173180E+10 737.55 0.680468E+10 0.174261E+09 0.00 1.00 19-MAR-18:41 0.00 01-MAR-08:61 17846.96 19-MAR-18:41 17280.46 28-MAR-16:51 1371.74 19-MAR-18:41 3863.36 19-MAR-18:41 0.00 01-MAR-00:10
April 0.744869E+10 0.184744E+10 704.50 0.717298E+10 0.275712E+09 0.00 1.00 10-APR-18:11 0.00 01-APR-07:01 18216.30 18-APR-08:61 17289.82 17-APR-16:51 2582.65 18-APR-08:61 3931.36 18-APR-08:61 0.00 01-APR-00:10
May 0.842606E+10 0.207909E+10 706.79 0.793804E+10 0.488023E+09 0.00 1.00 03-MAY-18:11 0.00 01-MAY-07:01 18353.84 12-MAY-08:11 17381.85 21-MAY-19:21 2972.40 12-MAY-08:11 3994.98 31-MAY-08:51 0.00 01-MAY-00:10
June 0.878779E+10 0.219742E+10 672.55 0.811686E+10 0.670931E+09 0.00 1.00 06-JUN-18:21 0.00 01-JUN-07:01 18466.89 13-JUN-08:61 17339.96 22-JUN-16:41 3321.39 13-JUN-08:61 4001.66 28-JUN-08:51 0.00 01-JUN-00:10
July 0.921251E+10 0.228572E+10 675.42 0.839840E+10 0.814114E+09 0.00 1.00 01-JUL-08:61 0.00 01-JUL-05:11 18540.75 20-JUL-08:61 17365.19 23-JUL-16:21 3468.28 20-JUL-08:61 4011.56 26-JUL-08:51 0.00 01-JUL-00:10
August 0.906340E+10 0.225072E+10 679.83 0.829546E+10 0.767938E+09 0.00 1.00 01-AUG-06:51 0.00 01-AUG-05:11 18534.78 31-AUG-08:61 17375.83 16-AUG-16:21 3471.53 31-AUG-08:61 3987.88 31-AUG-08:61 0.00 01-AUG-00:10
September 0.835798E+10 0.207730E+10 683.91 0.790693E+10 0.451057E+09 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 18392.75 11-SEP-08:61 17340.07 04-SEP-16:41 3010.09 11-SEP-08:61 3962.92 11-SEP-08:61 0.00 01-SEP-00:10
October 0.786193E+10 0.194438E+10 736.17 0.759858E+10 0.263358E+09 0.00 1.00 01-OCT-18:21 0.00 01-OCT-07:01 17885.88 11-OCT-18:21 17311.11 20-OCT-16:51 1649.66 11-OCT-18:21 3870.65 11-OCT-18:21 0.00 01-OCT-00:10
November 0.679724E+10 0.168663E+10 710.86 0.660291E+10 0.194329E+09 0.00 1.00 03-NOV-16:11 0.00 01-NOV-07:01 17230.31 26-NOV-08:11 17230.31 26-NOV-08:11 924.45 08-NOV-09:01 3743.64 26-NOV-08:11 0.00 01-NOV-00:10
December 0.615050E+10 0.153186E+10 740.01 0.605698E+10 93525236.46 0.00 0.68 03-DEC-16:01 0.00 01-DEC-08:61 10573.37 03-DEC-16:01 10325.55 03-DEC-16:01 756.71 31-DEC-09:01 2433.18 03-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.897558E+11 0.222891E+11 8318.01 0.853938E+11 0.436201E+10 0.00                            
Minimum of Months 0.517231E+10 0.128636E+10 587.17 0.507486E+10 71308068.36 0.00 0.68   0.00   10573.37   10325.55   722.58   2433.18   0.00  
Maximum of Months 0.921251E+10 0.228572E+10 740.01 0.839840E+10 0.814114E+09 0.00 1.00   0.00   18540.75   17870.55   3471.53   4011.56   0.00  



Table of Contents

Report: DXReportMonthly

For: 220_223 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 56347361.28 13093219.27 16.12 44573043.60 11774317.67 0.00 1.00 01-JAN-09:01 0.00 01-JAN-00:10 11106.20 01-JAN-16:01 9511.79 15-JAN-09:01 4112.59 01-JAN-16:01 2410.35 01-JAN-16:01 0.00 01-JAN-00:10
February 0.170998E+09 41137407.88 74.38 0.132055E+09 38943221.28 0.00 1.00 05-FEB-09:01 0.00 01-FEB-00:10 11342.93 25-FEB-16:01 9498.54 18-FEB-09:01 4096.27 20-FEB-16:01 2455.74 25-FEB-16:01 0.00 01-FEB-00:10
March 0.894676E+09 0.219885E+09 265.73 0.703830E+09 0.190846E+09 0.00 1.00 01-MAR-09:01 0.00 01-MAR-00:10 11761.66 19-MAR-18:41 9408.94 11-MAR-09:01 4350.80 12-MAR-15:01 2531.81 19-MAR-18:41 0.00 01-MAR-00:10
April 0.241673E+10 0.593617E+09 462.07 0.190109E+10 0.515641E+09 0.00 1.00 01-APR-08:61 0.00 01-APR-00:10 12469.98 16-APR-08:11 10435.30 17-APR-16:51 4957.43 16-APR-08:16 2648.51 16-APR-08:11 0.00 01-APR-00:10
May 0.490630E+10 0.119256E+10 607.84 0.373268E+10 0.117361E+10 0.00 1.00 01-MAY-08:61 0.00 01-MAY-07:01 12747.97 11-MAY-21:11 10604.31 06-MAY-16:51 5853.86 11-MAY-21:15 2697.27 31-MAY-08:51 0.00 01-MAY-00:10
June 0.666517E+10 0.162370E+10 591.07 0.485164E+10 0.181353E+10 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 13036.82 13-JUN-08:61 10157.02 22-JUN-16:41 6329.25 13-JUN-08:04 2732.16 11-JUN-15:01 0.00 01-JUN-00:10
July 0.756303E+10 0.181586E+10 584.02 0.528812E+10 0.227491E+10 0.00 1.00 01-JUL-07:01 0.00 01-JUL-05:11 13238.50 20-JUL-08:61 10053.53 23-JUL-16:21 6720.39 20-JUL-08:04 2758.53 20-JUL-08:61 0.00 01-JUL-00:10
August 0.706428E+10 0.170117E+10 577.93 0.496608E+10 0.209820E+10 0.00 1.00 01-AUG-06:51 0.00 01-AUG-05:11 13229.03 31-AUG-08:61 10328.32 07-AUG-16:31 6673.11 31-AUG-08:04 2789.60 04-AUG-07:41 0.00 01-AUG-00:10
September 0.507856E+10 0.124199E+10 602.10 0.396180E+10 0.111676E+10 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 12772.91 11-SEP-08:61 10596.51 20-SEP-16:51 5394.43 11-SEP-08:06 2693.92 11-SEP-08:61 0.00 01-SEP-00:10
October 0.253371E+10 0.625968E+09 613.45 0.204440E+10 0.489309E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-07:01 11827.55 02-OCT-17:21 9943.62 20-OCT-16:51 4296.53 09-OCT-15:02 2543.29 02-OCT-17:21 0.00 01-OCT-00:10
November 0.114509E+10 0.281770E+09 285.28 0.867598E+09 0.277491E+09 0.00 1.00 01-NOV-08:61 0.00 01-NOV-07:01 11690.95 08-NOV-16:01 9622.97 26-NOV-09:01 4340.03 20-NOV-16:02 2519.34 08-NOV-16:01 0.00 01-NOV-00:10
December 78743354.86 18051635.44 21.16 62718280.99 16025073.87 0.00 1.00 01-DEC-09:01 0.00 01-DEC-00:10 11235.88 03-DEC-16:01 9860.21 10-DEC-09:01 4188.76 31-DEC-16:01 2435.43 03-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.385736E+11 0.936880E+10 4701.16 0.285566E+11 0.100170E+11 0.00                            
Minimum of Months 56347361.28 13093219.27 16.12 44573043.60 11774317.67 0.00 1.00   0.00   11106.20   9408.94   4096.27   2410.35   0.00  
Maximum of Months 0.756303E+10 0.181586E+10 613.45 0.528812E+10 0.227491E+10 0.00 1.00   0.00   13238.50   10604.31   6720.39   2789.60   0.00  



Table of Contents

Report: DXReportMonthly

For: 224 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 1203123.24 283078.71 1.31 902407.39 300715.85 0.00 1.00 14-JAN-09:01 0.00 01-JAN-00:10 2993.34 14-JAN-09:01 2378.45 14-JAN-09:01 665.84 13-JAN-19:01 651.69 14-JAN-09:01 0.00 01-JAN-00:10
February 8793790.26 2125358.73 18.88 6410047.80 2383742.45 0.00 1.00 20-FEB-09:01 0.00 01-FEB-00:10 3230.22 25-FEB-16:01 2475.37 26-FEB-09:01 1203.90 25-FEB-16:01 699.66 25-FEB-16:01 0.00 01-FEB-00:10
March 0.152864E+09 37802329.28 159.24 0.116292E+09 36571630.00 0.00 1.00 11-MAR-09:01 0.00 01-MAR-00:10 3433.53 19-MAR-15:01 2574.76 21-MAR-08:61 1493.05 19-MAR-15:02 735.94 19-MAR-15:01 0.00 01-MAR-00:10
April 0.564224E+09 0.138784E+09 384.07 0.441336E+09 0.122888E+09 0.00 1.00 01-APR-08:61 0.00 01-APR-00:10 3549.67 16-APR-08:11 2981.50 17-APR-16:51 1415.92 08-APR-15:01 754.73 16-APR-08:11 0.00 01-APR-00:10
May 0.132691E+10 0.323134E+09 601.03 0.102342E+10 0.303491E+09 0.00 1.00 01-MAY-08:61 0.00 01-MAY-07:01 3634.89 11-MAY-18:11 3039.22 06-MAY-16:51 1695.26 11-MAY-18:14 769.50 31-MAY-08:51 0.00 01-MAY-00:10
June 0.193115E+10 0.470553E+09 588.31 0.145146E+10 0.479687E+09 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 3703.38 13-JUN-08:61 2931.15 22-JUN-16:41 1775.87 13-JUN-08:04 777.47 13-JUN-08:61 0.00 01-JUN-00:10
July 0.222087E+10 0.533202E+09 581.79 0.161657E+10 0.604301E+09 0.00 1.00 01-JUL-07:01 0.00 01-JUL-05:11 3764.79 20-JUL-08:61 2902.82 23-JUL-16:21 1884.78 20-JUL-08:03 785.88 20-JUL-08:61 0.00 01-JUL-00:10
August 0.206395E+10 0.497165E+09 575.11 0.150662E+10 0.557333E+09 0.00 1.00 01-AUG-06:51 0.00 01-AUG-05:11 3773.64 31-AUG-08:61 2976.39 07-AUG-16:31 1924.17 31-AUG-08:03 793.39 04-AUG-07:41 0.00 01-AUG-00:10
September 0.145235E+10 0.355057E+09 588.45 0.115637E+10 0.295988E+09 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 3639.71 11-SEP-08:61 3033.96 20-SEP-16:51 1509.53 11-SEP-08:05 768.34 11-SEP-08:61 0.00 01-SEP-00:10
October 0.594547E+09 0.147041E+09 522.63 0.473327E+09 0.121220E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-07:01 3465.31 09-OCT-15:01 2758.23 20-OCT-16:51 1549.22 09-OCT-15:02 741.22 09-OCT-15:01 0.00 01-OCT-00:10
November 0.248932E+09 61435713.54 206.13 0.185112E+09 63820537.73 0.00 1.00 01-NOV-08:61 0.00 01-NOV-07:01 3419.91 08-NOV-16:01 2636.78 04-NOV-18:01 1443.48 06-NOV-16:02 733.65 08-NOV-16:01 0.00 01-NOV-00:10
December 1961420.46 463814.67 1.40 1493594.21 467826.25 0.00 1.00 02-DEC-09:01 0.00 01-DEC-00:10 3020.77 03-DEC-09:01 2478.18 02-DEC-09:01 627.87 03-DEC-16:01 657.57 03-DEC-09:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.105678E+11 0.256705E+10 4228.35 0.797931E+10 0.258845E+10 0.00                            
Minimum of Months 1203123.24 283078.71 1.31 902407.39 300715.85 0.00 1.00   0.00   2993.34   2378.45   627.87   651.69   0.00  
Maximum of Months 0.222087E+10 0.533202E+09 601.03 0.161657E+10 0.604301E+09 0.00 1.00   0.00   3773.64   3039.22   1924.17   793.39   0.00  



Table of Contents

Report: DXReportMonthly

For: 301 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10
May 716683.67 191895.92 4.07 575136.44 141547.23 0.00 0.05 31-MAY-15:00 0.00 01-MAY-00:10 77.80 31-MAY-15:00 63.19 31-MAY-15:00 15.34 31-MAY-17:23 21.51 31-MAY-15:00 0.00 01-MAY-00:10
June 21286236.50 5749533.49 52.45 16095048.54 5191187.95 0.00 0.22 25-JUN-14:20 0.00 01-JUN-00:10 343.18 25-JUN-14:20 254.48 25-JUN-14:20 88.87 11-JUN-15:00 94.87 25-JUN-14:20 0.00 01-JUN-00:10
July 19818785.92 5134032.53 63.49 14118036.13 5700749.80 0.00 0.16 03-JUL-18:03 0.00 01-JUL-00:10 254.15 03-JUL-17:23 174.66 03-JUL-18:03 83.68 03-JUL-15:00 67.00 03-JUL-17:23 0.00 01-JUL-00:10
August 5185658.77 1376671.75 16.66 3039970.73 2145688.04 0.00 0.28 04-AUG-14:10 0.00 01-AUG-00:10 479.81 04-AUG-14:10 232.42 04-AUG-14:10 247.39 04-AUG-14:10 126.84 04-AUG-14:10 0.00 01-AUG-00:10
September 681881.09 194065.69 5.65 636368.75 45512.34 0.00 0.07 07-SEP-15:00 0.00 01-SEP-00:10 94.67 07-SEP-15:00 90.67 07-SEP-15:00 4.65 08-SEP-15:00 27.42 07-SEP-15:00 0.00 01-SEP-00:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 47689245.95 12646199.38 142.32 34464560.59 13224685.36 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 21286236.50 5749533.49 63.49 16095048.54 5700749.80 0.00 0.28   0.00   479.81   254.48   247.39   126.84   0.00  



Table of Contents

Report: DXReportMonthly

For: 302_305 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 501824.05 133949.75 1.71 400761.53 101062.52 0.00 0.02 16-APR-17:23 0.00 01-APR-00:10 116.59 16-APR-17:23 92.89 16-APR-17:23 23.70 16-APR-17:23 30.99 16-APR-17:23 0.00 01-APR-00:10
May 4398237.31 1176179.73 6.80 3562685.12 835552.19 0.00 0.10 31-MAY-15:00 0.00 01-MAY-00:10 452.81 31-MAY-15:00 373.34 31-MAY-15:00 79.47 31-MAY-15:00 124.50 31-MAY-15:00 0.00 01-MAY-00:10
June 73367940.19 19797785.54 71.06 56912332.50 16455607.69 0.00 0.21 11-JUN-15:00 0.00 01-JUN-00:10 1033.80 11-JUN-15:00 744.83 11-JUN-15:00 288.97 11-JUN-15:00 290.87 11-JUN-15:00 0.00 01-JUN-00:10
July 98263929.96 25365186.34 98.69 72214870.10 26049059.86 0.00 0.17 03-JUL-15:00 0.00 01-JUL-00:10 864.96 03-JUL-15:00 593.57 03-JUL-15:00 300.69 26-JUL-15:00 230.14 03-JUL-15:00 0.00 01-JUL-00:10
August 30756067.62 8086552.28 34.39 20776381.85 9979685.77 0.00 0.31 04-AUG-14:10 0.00 01-AUG-00:10 1649.55 04-AUG-14:10 929.23 04-AUG-14:10 720.31 04-AUG-14:10 442.30 04-AUG-14:10 0.00 01-AUG-00:10
September 7605782.45 2145163.80 11.83 7161470.13 444312.32 0.00 0.12 07-SEP-14:30 0.00 01-SEP-00:10 535.84 07-SEP-14:30 520.91 07-SEP-14:30 25.56 08-SEP-15:00 154.80 07-SEP-14:30 0.00 01-SEP-00:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.214894E+09 56704817.45 224.47 0.161029E+09 53865280.35 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 98263929.96 25365186.34 98.69 72214870.10 26049059.86 0.00 0.31   0.00   1649.55   929.23   720.31   442.30   0.00  



Table of Contents

Report: DXReportMonthly

For: 306_308 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 1128011.54 302119.76 2.83 913035.03 214976.51 0.00 0.04 16-APR-17:23 0.00 01-APR-00:10 162.00 16-APR-17:23 130.52 16-APR-17:23 31.49 16-APR-17:23 43.02 16-APR-17:23 0.00 01-APR-00:10
May 4815964.38 1286673.52 7.62 3908998.56 906965.82 0.00 0.10 31-MAY-15:00 0.00 01-MAY-00:10 427.33 31-MAY-15:00 353.57 31-MAY-15:00 73.76 31-MAY-15:00 117.54 31-MAY-15:00 0.00 01-MAY-00:10
June 66924854.02 18039529.25 74.65 52571711.62 14353142.40 0.00 0.19 11-JUN-15:00 0.00 01-JUN-00:10 869.95 11-JUN-15:00 644.79 11-JUN-14:10 232.43 11-JUN-15:00 246.24 11-JUN-15:00 0.00 01-JUN-00:10
July 90673934.60 23422846.35 99.74 67943491.21 22730443.39 0.00 0.16 03-JUL-15:00 0.00 01-JUL-00:10 749.20 03-JUL-15:00 522.04 03-JUL-15:00 250.80 26-JUL-15:00 200.07 03-JUL-15:00 0.00 01-JUL-00:10
August 31126160.52 8173691.82 39.74 21951178.97 9174981.55 0.00 0.25 04-AUG-14:10 0.00 01-AUG-00:10 1202.11 04-AUG-14:10 680.61 04-AUG-14:10 521.50 04-AUG-14:10 326.30 04-AUG-14:10 0.00 01-AUG-00:10
September 8336466.63 2341431.98 14.96 7799761.82 536704.81 0.00 0.12 07-SEP-15:00 0.00 01-SEP-00:10 468.88 07-SEP-15:00 458.37 07-SEP-15:00 25.00 06-SEP-15:00 135.09 07-SEP-15:00 0.00 01-SEP-00:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.203005E+09 53566292.68 239.56 0.155088E+09 47917214.47 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 90673934.60 23422846.35 99.74 67943491.21 22730443.39 0.00 0.25   0.00   1202.11   680.61   521.50   326.30   0.00  



Table of Contents

Report: DXReportMonthly

For: 309_312 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 8771709.36 2003058.98 1.77 6602905.12 2168804.24 0.00 1.00 01-JAN-09:01 0.00 01-JAN-00:10 10067.51 13-JAN-19:01 7799.84 02-JAN-09:01 2983.80 13-JAN-16:01 2189.15 13-JAN-19:01 0.00 01-JAN-00:10
February 59509468.54 14025324.20 22.58 43790991.21 15718477.33 0.00 1.00 07-FEB-19:01 0.00 01-FEB-00:10 10504.97 25-FEB-16:01 8121.49 26-FEB-09:01 3749.31 20-FEB-16:02 2275.03 25-FEB-16:01 0.00 01-FEB-00:10
March 0.523403E+09 0.128100E+09 148.79 0.392627E+09 0.130776E+09 0.00 1.00 04-MAR-09:01 0.00 01-MAR-00:10 11197.03 19-MAR-15:01 8556.97 21-MAR-18:01 4772.51 19-MAR-15:03 2397.91 19-MAR-15:01 0.00 01-MAR-00:10
April 0.194452E+10 0.475543E+09 363.52 0.149629E+10 0.448227E+09 0.00 1.00 01-APR-08:61 0.00 01-APR-00:10 11922.76 18-APR-08:51 9579.71 17-APR-16:51 5411.58 18-APR-08:55 2510.30 18-APR-08:51 0.00 01-APR-00:10
May 0.409632E+10 0.993133E+09 567.23 0.302425E+10 0.107208E+10 0.00 1.00 01-MAY-08:61 0.00 01-MAY-07:01 12270.16 11-MAY-20:21 9831.85 06-MAY-16:51 6413.08 11-MAY-20:23 2560.39 31-MAY-08:51 0.00 01-MAY-00:10
June 0.607548E+10 0.147615E+10 564.11 0.434827E+10 0.172721E+10 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 12472.24 13-JUN-08:51 9280.60 22-JUN-16:51 6817.70 13-JUN-08:51 2595.87 25-JUN-08:51 0.00 01-JUN-00:10
July 0.708909E+10 0.169606E+10 556.53 0.490936E+10 0.217973E+10 0.00 1.00 01-JUL-07:51 0.00 01-JUL-05:11 12612.64 17-JUL-08:51 9148.62 18-JUL-18:31 6771.26 17-JUL-08:52 2613.36 17-JUL-08:51 0.00 01-JUL-00:10
August 0.651617E+10 0.156560E+10 558.49 0.451352E+10 0.200265E+10 0.00 1.00 01-AUG-08:51 0.00 01-AUG-05:11 12656.44 22-AUG-08:51 9547.91 06-AUG-17:01 6963.91 22-AUG-08:51 2607.44 22-AUG-08:51 0.00 01-AUG-00:10
September 0.422738E+10 0.103198E+10 538.31 0.321129E+10 0.101608E+10 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 12079.57 11-SEP-08:51 9697.02 20-SEP-17:01 5520.41 12-SEP-08:54 2532.69 11-SEP-08:51 0.00 01-SEP-00:10
October 0.149941E+10 0.368368E+09 395.28 0.114043E+10 0.358981E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-01:40 11309.52 09-OCT-15:01 8578.78 19-OCT-17:11 5310.53 09-OCT-15:03 2416.42 09-OCT-15:01 0.00 01-OCT-00:10
November 0.635508E+09 0.156056E+09 160.77 0.443079E+09 0.192428E+09 0.00 1.00 01-NOV-08:61 0.00 01-NOV-00:10 11306.77 08-NOV-16:01 8459.14 04-NOV-18:01 5347.69 08-NOV-16:03 2415.97 08-NOV-16:01 0.00 01-NOV-00:10
December 13601105.34 3114081.26 1.52 10439409.84 3161695.50 0.00 1.00 02-DEC-09:01 0.00 01-DEC-00:10 10315.77 03-DEC-16:01 8032.70 02-DEC-09:01 3676.85 03-DEC-16:01 2238.69 03-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.326892E+11 0.791013E+10 3878.91 0.235399E+11 0.914921E+10 0.00                            
Minimum of Months 8771709.36 2003058.98 1.52 6602905.12 2168804.24 0.00 1.00   0.00   10067.51   7799.84   2983.80   2189.15   0.00  
Maximum of Months 0.708909E+10 0.169606E+10 567.23 0.490936E+10 0.217973E+10 0.00 1.00   0.00   12656.44   9831.85   6963.91   2613.36   0.00  



Table of Contents

Report: DXReportMonthly

For: 313 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10
June 1857397.83 505289.53 11.45 1334540.71 522857.12 0.00 0.07 26-JUN-14:30 0.00 01-JUN-00:10 121.96 26-JUN-14:30 89.52 26-JUN-14:30 34.06 27-JUN-15:00 34.04 26-JUN-14:30 0.00 01-JUN-00:10
July 2015871.67 528799.92 10.63 1341875.10 673996.57 0.00 0.06 03-JUL-15:00 0.00 01-JUL-00:10 98.99 03-JUL-15:00 64.53 05-JUL-18:03 35.70 03-JUL-15:00 26.61 03-JUL-15:00 0.00 01-JUL-00:10
August 528999.80 146176.32 0.75 278736.26 250263.54 0.00 0.13 04-AUG-15:00 0.00 01-AUG-00:10 235.34 04-AUG-15:00 125.11 04-AUG-15:00 110.84 04-AUG-14:30 65.12 04-AUG-15:00 0.00 01-AUG-00:10
September 69974.91 20410.10 0.67 67349.91 2625.00 0.00 0.03 07-SEP-15:00 0.00 01-SEP-00:10 52.89 07-SEP-15:00 51.16 07-SEP-15:00 1.73 07-SEP-15:00 15.42 07-SEP-15:00 0.00 01-SEP-00:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 4472244.21 1200675.88 23.50 3022501.97 1449742.23 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 2015871.67 528799.92 11.45 1341875.10 673996.57 0.00 0.13   0.00   235.34   125.11   110.84   65.12   0.00  



Table of Contents

Report: DXReportMonthly

For: 314 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 745363.12 181200.21 0.87 541972.77 203390.36 0.00 0.69 13-JAN-19:01 0.00 01-JAN-00:10 1843.09 13-JAN-19:01 1260.40 13-JAN-19:01 582.69 13-JAN-19:01 422.66 13-JAN-19:01 0.00 01-JAN-00:10
February 7103911.78 1722840.91 14.60 5096933.35 2006978.43 0.00 1.00 08-FEB-19:01 0.00 01-FEB-00:10 2922.16 25-FEB-16:01 2206.59 26-FEB-09:01 1083.52 25-FEB-16:01 633.19 25-FEB-16:01 0.00 01-FEB-00:10
March 0.134054E+09 33056928.55 135.67 0.101385E+09 32669177.34 0.00 1.00 12-MAR-08:61 0.00 01-MAR-00:10 3121.38 19-MAR-15:01 2313.55 28-MAR-16:51 1334.27 19-MAR-15:02 668.80 19-MAR-15:01 0.00 01-MAR-00:10
April 0.555492E+09 0.135768E+09 349.62 0.436248E+09 0.119244E+09 0.00 1.00 01-APR-08:61 0.00 01-APR-00:10 3221.62 16-APR-08:11 2749.04 17-APR-16:51 1318.87 08-APR-15:01 684.98 16-APR-08:11 0.00 01-APR-00:10
May 0.130451E+10 0.315904E+09 591.63 0.100374E+10 0.300769E+09 0.00 1.00 01-MAY-08:61 0.00 01-MAY-07:01 3314.57 11-MAY-18:11 2797.26 06-MAY-16:51 1584.11 11-MAY-18:14 698.98 11-MAY-18:11 0.00 01-MAY-00:10
June 0.195743E+10 0.473670E+09 585.27 0.147542E+10 0.482009E+09 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 3365.21 13-JUN-08:61 2659.92 22-JUN-16:41 1627.68 13-JUN-08:04 706.19 13-JUN-08:61 0.00 01-JUN-00:10
July 0.228945E+10 0.545764E+09 588.85 0.167608E+10 0.613366E+09 0.00 1.00 01-JUL-07:01 0.00 01-JUL-05:11 3424.42 20-JUL-08:61 2644.65 23-JUL-16:21 1729.07 20-JUL-08:03 714.27 20-JUL-08:61 0.00 01-JUL-00:10
August 0.210511E+10 0.503819E+09 583.69 0.154135E+10 0.563755E+09 0.00 1.00 01-AUG-06:51 0.00 01-AUG-05:11 3433.45 31-AUG-08:61 2696.35 07-AUG-16:31 1782.39 31-AUG-08:03 721.79 04-AUG-07:41 0.00 01-AUG-00:10
September 0.138702E+10 0.337210E+09 558.52 0.109892E+10 0.288098E+09 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 3306.08 11-SEP-08:61 2739.58 20-SEP-16:51 1375.18 11-SEP-08:06 697.74 11-SEP-08:61 0.00 01-SEP-00:10
October 0.439230E+09 0.108235E+09 417.55 0.339807E+09 99422965.29 0.00 1.00 01-OCT-08:61 0.00 01-OCT-04:02 3148.35 09-OCT-15:01 2513.82 20-OCT-16:51 1486.59 09-OCT-15:01 673.26 09-OCT-15:01 0.00 01-OCT-00:10
November 0.177975E+09 43923418.81 155.94 0.126694E+09 51280653.41 0.00 1.00 01-NOV-08:61 0.00 01-NOV-00:10 3144.11 08-NOV-16:01 2361.79 04-NOV-18:01 1461.62 08-NOV-16:02 672.57 08-NOV-16:01 0.00 01-NOV-00:10
December 1351138.18 323481.46 1.09 1000016.24 351121.94 0.00 1.00 03-DEC-09:01 0.00 01-DEC-00:10 2719.14 03-DEC-09:01 2156.18 03-DEC-09:01 568.25 03-DEC-16:01 591.99 03-DEC-09:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.103595E+11 0.249958E+10 3983.30 0.780629E+10 0.255317E+10 0.00                            
Minimum of Months 745363.12 181200.21 0.87 541972.77 203390.36 0.00 0.69   0.00   1843.09   1260.40   568.25   422.66   0.00  
Maximum of Months 0.228945E+10 0.545764E+09 591.63 0.167608E+10 0.613366E+09 0.00 1.00   0.00   3433.45   2797.26   1782.39   721.79   0.00  



Table of Contents

Report: DXReportMonthly

For: 315_318 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.335564E+09 81847758.23 138.58 0.283253E+09 52310343.65 0.00 1.00 01-JAN-09:01 0.00 01-JAN-05:00 12874.67 01-JAN-16:01 11182.61 07-JAN-09:01 4328.94 16-JAN-16:02 2789.36 01-JAN-16:01 0.00 01-JAN-00:10
February 0.901479E+09 0.223740E+09 312.15 0.772683E+09 0.128796E+09 0.00 1.00 05-FEB-09:01 0.00 01-FEB-00:10 12737.44 23-FEB-16:01 11233.96 05-FEB-09:01 3663.14 23-FEB-16:02 2763.02 23-FEB-16:01 0.00 01-FEB-00:10
March 0.230253E+10 0.569558E+09 536.85 0.198080E+10 0.321734E+09 0.00 1.00 01-MAR-09:01 0.00 01-MAR-00:10 13391.77 19-MAR-18:41 11546.54 28-MAR-16:51 3716.26 19-MAR-18:44 2884.02 19-MAR-18:41 0.00 01-MAR-00:10
April 0.427762E+10 0.105113E+10 625.39 0.361303E+10 0.664591E+09 0.00 1.00 01-APR-08:61 0.00 01-APR-07:01 14026.48 16-APR-08:11 12396.28 30-APR-17:11 5114.08 16-APR-08:16 2990.58 16-APR-08:11 0.00 01-APR-00:10
May 0.701032E+10 0.169952E+10 643.48 0.566275E+10 0.134757E+10 0.00 1.00 01-MAY-08:61 0.00 01-MAY-07:01 14390.33 11-MAY-21:11 12444.96 21-MAY-16:51 6021.94 11-MAY-21:16 3046.97 11-MAY-21:11 0.00 01-MAY-00:10
June 0.877152E+10 0.213366E+10 614.28 0.676835E+10 0.200316E+10 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 14678.97 13-JUN-08:61 12372.02 22-JUN-16:21 6538.41 13-JUN-08:05 3089.30 13-JUN-08:61 0.00 01-JUN-00:10
July 0.974146E+10 0.233768E+10 605.80 0.725403E+10 0.248742E+10 0.00 1.00 01-JUL-07:01 0.00 01-JUL-05:11 14894.26 20-JUL-08:61 11802.61 23-JUL-16:21 6928.18 20-JUL-08:05 3119.49 20-JUL-08:61 0.00 01-JUL-00:10
August 0.916215E+10 0.220591E+10 606.08 0.685733E+10 0.230482E+10 0.00 1.00 01-AUG-06:51 0.00 01-AUG-05:11 14884.84 31-AUG-08:61 12007.35 07-AUG-16:31 6892.55 31-AUG-08:05 3146.90 04-AUG-07:41 0.00 01-AUG-00:10
September 0.690091E+10 0.168504E+10 629.16 0.565154E+10 0.124937E+10 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 14340.56 11-SEP-08:61 12373.79 20-SEP-16:51 5574.62 11-SEP-08:06 3039.45 11-SEP-08:61 0.00 01-SEP-00:10
October 0.423080E+10 0.104432E+10 687.45 0.361998E+10 0.610820E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-07:01 13446.46 02-OCT-17:21 11924.59 20-OCT-16:51 3911.67 02-OCT-18:03 2893.62 02-OCT-17:21 0.00 01-OCT-00:10
November 0.220568E+10 0.545097E+09 470.24 0.181463E+10 0.391051E+09 0.00 1.00 01-NOV-08:61 0.00 01-NOV-07:01 12961.34 08-NOV-09:01 11321.61 26-NOV-09:01 4029.32 23-NOV-16:02 2805.73 08-NOV-09:01 0.00 01-NOV-00:10
December 0.472050E+09 0.115907E+09 226.46 0.401094E+09 70955857.19 0.00 1.00 01-DEC-09:01 0.00 01-DEC-08:61 12871.95 31-DEC-16:01 11471.39 10-DEC-09:01 4359.58 31-DEC-16:02 2788.84 31-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.563121E+11 0.136934E+11 6095.91 0.446795E+11 0.116326E+11 0.00                            
Minimum of Months 0.335564E+09 81847758.23 138.58 0.283253E+09 52310343.65 0.00 1.00   0.00   12737.44   11182.61   3663.14   2763.02   0.00  
Maximum of Months 0.974146E+10 0.233768E+10 687.45 0.725403E+10 0.248742E+10 0.00 1.00   0.00   14894.26   12444.96   6928.18   3146.90   0.00  



Table of Contents

Report: DXReportMonthly

For: 319 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 1758086.48 473574.87 10.19 1563888.01 194198.48 0.00 0.07 18-APR-15:00 0.00 01-APR-00:10 184.56 18-APR-15:00 158.88 18-APR-15:00 25.68 18-APR-15:00 49.76 18-APR-15:00 0.00 01-APR-00:10
May 9143711.13 2400935.50 40.83 7856701.84 1287009.30 0.00 0.10 31-MAY-15:00 0.00 01-MAY-00:10 267.57 31-MAY-15:00 243.54 31-MAY-15:00 35.52 30-MAY-14:30 74.40 31-MAY-15:00 0.00 01-MAY-00:10
June 52468927.89 13929185.76 231.51 44786815.18 7682112.70 0.00 0.14 11-JUN-15:00 0.00 01-JUN-00:10 369.75 11-JUN-15:00 294.34 11-JUN-15:00 75.41 11-JUN-15:00 107.21 11-JUN-15:00 0.00 01-JUN-00:10
July 66903486.47 17245022.44 309.50 54774359.10 12129127.38 0.00 0.10 03-JUL-15:00 0.00 01-JUL-00:10 280.67 03-JUL-15:00 229.46 02-JUL-15:00 88.59 26-JUL-15:00 76.48 03-JUL-15:00 0.00 01-JUL-00:10
August 34054760.66 8897556.40 173.61 27039370.62 7015390.04 0.00 0.15 04-AUG-15:00 0.00 01-AUG-00:10 413.15 04-AUG-15:00 276.03 04-AUG-15:00 137.12 04-AUG-15:00 118.25 04-AUG-15:00 0.00 01-AUG-00:10
September 9455040.98 2610548.22 55.35 8884587.07 570453.91 0.00 0.10 07-SEP-14:05 0.00 01-SEP-00:10 254.91 07-SEP-14:05 247.51 07-SEP-14:10 24.61 11-SEP-15:00 74.32 07-SEP-14:05 0.00 01-SEP-00:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.173784E+09 45556823.18 820.99 0.144906E+09 28878291.80 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 66903486.47 17245022.44 309.50 54774359.10 12129127.38 0.00 0.15   0.00   413.15   294.34   137.12   118.25   0.00  



Table of Contents

Report: DXReportMonthly

For: 320_323 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 21044370.84 4811059.83 4.61 16359248.05 4685122.79 0.00 1.00 01-JAN-09:01 0.00 01-JAN-00:10 9715.08 13-JAN-19:01 8307.96 15-JAN-09:01 2912.04 13-JAN-16:01 2112.27 13-JAN-19:01 0.00 01-JAN-00:10
February 79492734.83 18729513.54 35.90 59903814.26 19588920.57 0.00 1.00 07-FEB-09:01 0.00 01-FEB-00:10 10075.80 25-FEB-16:01 8305.09 18-FEB-09:01 3683.07 20-FEB-16:01 2183.24 25-FEB-16:01 0.00 01-FEB-00:10
March 0.605862E+09 0.148138E+09 180.12 0.460247E+09 0.145615E+09 0.00 1.00 04-MAR-09:01 0.00 01-MAR-00:10 10576.86 19-MAR-15:01 8221.47 11-MAR-09:01 4183.14 29-MAR-15:02 2274.33 19-MAR-15:01 0.00 01-MAR-00:10
April 0.196006E+10 0.479262E+09 396.71 0.150277E+10 0.457286E+09 0.00 1.00 01-APR-08:61 0.00 01-APR-00:10 11164.55 16-APR-08:11 9208.82 17-APR-16:51 4546.83 16-APR-08:17 2370.44 16-APR-08:11 0.00 01-APR-00:10
May 0.428696E+10 0.103861E+10 592.74 0.318178E+10 0.110518E+10 0.00 1.00 01-MAY-08:61 0.00 01-MAY-07:01 11467.62 11-MAY-18:11 9376.82 06-MAY-16:51 5519.78 11-MAY-18:14 2420.75 31-MAY-08:51 0.00 01-MAY-00:10
June 0.611825E+10 0.148408E+10 575.85 0.436570E+10 0.175255E+10 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 11659.23 13-JUN-08:61 9005.61 22-JUN-16:41 5844.75 13-JUN-08:04 2454.29 11-JUN-15:01 0.00 01-JUN-00:10
July 0.707218E+10 0.168981E+10 569.36 0.484994E+10 0.222224E+10 0.00 1.00 01-JUL-07:01 0.00 01-JUL-05:11 11856.37 20-JUL-08:61 8883.41 23-JUL-16:21 6252.39 20-JUL-08:03 2469.12 20-JUL-08:61 0.00 01-JUL-00:10
August 0.649941E+10 0.155835E+10 560.82 0.446500E+10 0.203440E+10 0.00 1.00 01-AUG-06:51 0.00 01-AUG-05:11 11858.13 04-AUG-07:41 9145.53 07-AUG-16:31 6227.30 04-AUG-07:44 2503.83 04-AUG-15:01 0.00 01-AUG-00:10
September 0.429449E+10 0.104714E+10 559.75 0.325858E+10 0.103591E+10 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 11459.13 11-SEP-08:61 9244.86 20-SEP-16:51 4977.56 11-SEP-08:06 2414.35 11-SEP-08:61 0.00 01-SEP-00:10
October 0.161308E+10 0.396757E+09 462.35 0.123526E+10 0.377825E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-04:02 10803.63 09-OCT-15:01 8602.50 20-OCT-16:51 4866.91 09-OCT-15:03 2312.77 09-OCT-15:01 0.00 01-OCT-00:10
November 0.692686E+09 0.169875E+09 178.35 0.487524E+09 0.205162E+09 0.00 1.00 01-NOV-08:61 0.00 01-NOV-00:10 10871.41 08-NOV-16:01 8269.01 12-NOV-09:01 5044.51 08-NOV-16:03 2323.93 08-NOV-16:01 0.00 01-NOV-00:10
December 29269802.62 6672843.15 4.25 22974451.25 6295351.38 0.00 1.00 01-DEC-09:01 0.00 01-DEC-00:10 9944.27 03-DEC-16:01 8207.39 16-DEC-09:01 3476.16 03-DEC-16:01 2157.90 03-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.332728E+11 0.804224E+10 4120.81 0.239060E+11 0.936674E+10 0.00                            
Minimum of Months 21044370.84 4811059.83 4.25 16359248.05 4685122.79 0.00 1.00   0.00   9715.08   8207.39   2912.04   2112.27   0.00  
Maximum of Months 0.707218E+10 0.168981E+10 592.74 0.484994E+10 0.222224E+10 0.00 1.00   0.00   11858.13   9376.82   6252.39   2503.83   0.00  



Table of Contents

Report: DXReportMonthly

For: 324 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10
June 27408.75 7690.00 0.67 19881.41 7527.35 0.00 0.01 26-JUN-14:40 0.00 01-JUN-00:10 18.68 26-JUN-14:40 13.59 26-JUN-14:40 5.10 26-JUN-14:40 5.25 26-JUN-14:40 0.00 01-JUN-00:10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 11979.04 3359.37 0.17 6193.40 5785.64 0.00 0.01 04-AUG-15:00 0.00 01-AUG-00:10 19.97 04-AUG-15:00 10.32 04-AUG-15:00 9.64 04-AUG-15:00 5.60 04-AUG-15:00 0.00 01-AUG-00:10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 39387.80 11049.37 0.83 26074.81 13312.99 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 27408.75 7690.00 0.67 19881.41 7527.35 0.00 0.01   0.00   19.97   13.59   9.64   5.60   0.00  



Table of Contents

Report: DXReportMonthly

For: 401 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 106845.24 26675.93 0.13 80593.60 26251.63 0.00 0.20 13-JAN-19:04 0.00 01-JAN-00:10 583.17 13-JAN-19:04 423.86 13-JAN-19:04 159.31 13-JAN-19:04 144.92 13-JAN-19:04 0.00 01-JAN-00:10
February 596273.59 148249.60 0.48 438443.72 157829.87 0.00 0.34 25-FEB-16:02 0.00 01-FEB-00:10 1059.29 25-FEB-16:02 695.56 25-FEB-16:02 363.72 25-FEB-16:02 257.00 25-FEB-16:02 0.00 01-FEB-00:10
March 34129792.83 8337544.15 37.41 25246508.52 8883284.31 0.00 1.00 18-MAR-18:01 0.00 01-MAR-00:10 3829.48 19-MAR-15:01 2952.43 23-MAR-18:01 1750.04 26-MAR-08:61 820.58 19-MAR-15:01 0.00 01-MAR-00:10
April 0.375116E+09 92278844.83 193.50 0.290287E+09 84828328.26 0.00 1.00 06-APR-18:01 0.00 01-APR-00:10 4070.86 18-APR-08:51 3520.10 17-APR-17:42 1830.64 11-APR-15:01 858.26 18-APR-08:51 0.00 01-APR-00:10
May 0.927305E+09 0.226094E+09 472.89 0.686759E+09 0.240547E+09 0.00 1.00 01-MAY-15:01 0.00 01-MAY-00:10 4191.90 11-MAY-20:21 3580.30 06-MAY-17:42 2078.63 11-MAY-20:23 875.15 11-MAY-20:21 0.00 01-MAY-00:10
June 0.183281E+10 0.450035E+09 532.54 0.138333E+10 0.449482E+09 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 4275.15 13-JUN-08:51 3491.29 19-JUN-16:32 2336.47 13-JUN-08:51 886.00 13-JUN-08:51 0.00 01-JUN-00:10
July 0.219936E+10 0.531676E+09 567.56 0.161638E+10 0.582980E+09 0.00 1.00 01-JUL-07:51 0.00 01-JUL-05:11 4293.62 20-JUL-08:51 3522.47 23-JUL-16:31 2242.59 20-JUL-08:52 891.00 17-JUL-08:51 0.00 01-JUL-00:10
August 0.191912E+10 0.467049E+09 561.31 0.139400E+10 0.525119E+09 0.00 1.00 01-AUG-08:51 0.00 01-AUG-05:11 4337.25 22-AUG-08:51 3606.97 07-AUG-16:31 2361.85 31-AUG-08:51 893.77 22-AUG-08:51 0.00 01-AUG-00:10
September 0.101286E+10 0.250070E+09 417.52 0.787920E+09 0.224936E+09 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 4125.15 11-SEP-08:51 3539.90 01-SEP-17:52 1875.68 12-SEP-08:53 866.10 11-SEP-08:51 0.00 01-SEP-00:10
October 0.121803E+09 29857814.36 125.09 86400950.55 35402360.06 0.00 1.00 01-OCT-15:01 0.00 01-OCT-00:10 3889.17 10-OCT-15:01 2843.55 01-OCT-18:51 1970.01 09-OCT-15:01 830.39 10-OCT-15:01 0.00 01-OCT-00:10
November 43217756.69 10682486.40 57.15 26707667.93 16510088.75 0.00 1.00 03-NOV-15:01 0.00 01-NOV-00:10 3937.35 07-NOV-16:01 2801.54 04-NOV-18:01 2154.04 07-NOV-16:01 838.08 07-NOV-16:01 0.00 01-NOV-00:10
December 97482.35 24324.96 0.13 74955.32 22527.03 0.00 0.21 02-DEC-19:04 0.00 01-DEC-00:10 631.33 02-DEC-19:04 470.08 02-DEC-19:04 161.25 02-DEC-19:04 156.50 02-DEC-19:04 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.846651E+10 0.206628E+10 2965.70 0.629762E+10 0.216889E+10 0.00                            
Minimum of Months 97482.35 24324.96 0.13 74955.32 22527.03 0.00 0.20   0.00   583.17   423.86   159.31   144.92   0.00  
Maximum of Months 0.219936E+10 0.531676E+09 567.56 0.161638E+10 0.582980E+09 0.00 1.00   0.00   4337.25   3606.97   2361.85   893.77   0.00  



Table of Contents

Report: DXReportMonthly

For: 402_405 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 55236793.65 14589341.49 24.02 50181425.78 5055367.87 0.00 0.20 16-APR-15:00 0.00 01-APR-00:10 1308.35 16-APR-15:00 1106.64 16-APR-15:00 201.71 16-APR-15:00 345.00 16-APR-15:00 0.00 01-APR-00:10
May 0.100998E+09 26166607.17 60.26 92473905.09 8524170.11 0.00 0.24 31-MAY-15:00 0.00 01-MAY-00:10 1548.87 31-MAY-15:00 1414.54 31-MAY-15:00 234.90 30-MAY-15:00 421.14 31-MAY-15:00 0.00 01-MAY-00:10
June 0.490052E+09 0.129211E+09 178.96 0.426248E+09 63804342.10 0.00 0.36 11-JUN-15:00 0.00 01-JUN-00:10 2370.80 11-JUN-15:00 1887.75 11-JUN-15:00 555.75 13-JUN-15:00 662.32 11-JUN-15:00 0.00 01-JUN-00:10
July 0.621788E+09 0.158966E+09 218.88 0.523420E+09 98368816.65 0.00 0.32 03-JUL-15:00 0.00 01-JUL-00:10 2204.91 03-JUL-15:00 1698.30 05-JUL-16:42 686.55 26-JUL-15:00 580.27 03-JUL-15:00 0.00 01-JUL-00:10
August 0.403842E+09 0.104547E+09 171.58 0.339074E+09 64767824.90 0.00 0.41 04-AUG-15:00 0.00 01-AUG-00:10 2790.63 04-AUG-15:00 2004.65 04-AUG-15:00 785.98 04-AUG-15:00 771.52 04-AUG-15:00 0.00 01-AUG-00:10
September 0.177060E+09 47208331.82 80.72 0.168460E+09 8599834.24 0.00 0.28 07-SEP-15:00 0.00 01-SEP-00:10 1701.09 07-SEP-15:00 1693.93 07-SEP-15:00 127.89 01-SEP-14:40 479.25 07-SEP-15:00 0.00 01-SEP-00:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.184898E+10 0.480689E+09 734.43 0.159986E+10 0.249120E+09 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.621788E+09 0.158966E+09 218.88 0.523420E+09 98368816.65 0.00 0.41   0.00   2790.63   2004.65   785.98   771.52   0.00  



Table of Contents

Report: DXReportMonthly

For: 406_408 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 56190648.80 14811292.39 27.22 51660424.79 4530224.01 0.00 0.21 16-APR-15:00 0.00 01-APR-00:10 1222.04 16-APR-15:00 1044.23 16-APR-15:00 177.80 16-APR-15:00 322.17 16-APR-15:00 0.00 01-APR-00:10
May 0.109261E+09 28192762.53 69.67 0.101429E+09 7831928.34 0.00 0.24 31-MAY-15:00 0.00 01-MAY-00:10 1384.98 31-MAY-15:00 1275.64 31-MAY-15:00 204.27 30-MAY-15:00 377.03 31-MAY-15:00 0.00 01-MAY-00:10
June 0.445171E+09 0.117260E+09 182.12 0.392191E+09 52979623.16 0.00 0.35 11-JUN-15:00 0.00 01-JUN-00:10 2041.20 11-JUN-15:00 1650.61 11-JUN-15:00 482.81 13-JUN-15:00 573.00 11-JUN-15:00 0.00 01-JUN-00:10
July 0.563729E+09 0.144153E+09 219.78 0.482305E+09 81423318.89 0.00 0.32 03-JUL-15:00 0.00 01-JUL-00:10 1925.06 03-JUL-15:00 1541.31 05-JUL-16:42 573.52 26-JUL-15:00 508.38 03-JUL-15:00 0.00 01-JUL-00:10
August 0.377154E+09 97563153.66 177.18 0.322207E+09 54946921.73 0.00 0.39 04-AUG-15:00 0.00 01-AUG-00:10 2386.80 04-AUG-15:00 1740.57 04-AUG-15:00 646.23 04-AUG-15:00 663.70 04-AUG-15:00 0.00 01-AUG-00:10
September 0.170872E+09 45452917.10 85.01 0.163324E+09 7547674.25 0.00 0.28 07-SEP-15:00 0.00 01-SEP-00:10 1528.17 07-SEP-15:00 1521.66 07-SEP-15:00 123.14 01-SEP-14:40 430.72 07-SEP-15:00 0.00 01-SEP-00:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.172238E+10 0.447434E+09 760.97 0.151312E+10 0.209260E+09 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.563729E+09 0.144153E+09 219.78 0.482305E+09 81423318.89 0.00 0.39   0.00   2386.80   1740.57   646.23   663.70   0.00  



Table of Contents

Report: DXReportMonthly

For: 409_412 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 3500184.27 844158.47 0.58 2481659.94 1018524.33 0.00 0.90 12-JAN-16:01 0.00 01-JAN-00:10 11087.67 12-JAN-16:01 7875.67 12-JAN-16:01 3212.00 12-JAN-16:01 2452.78 12-JAN-16:01 0.00 01-JAN-00:10
February 44985842.50 10772362.45 13.84 32469700.25 12516142.25 0.00 1.00 08-FEB-16:01 0.00 01-FEB-00:10 13151.91 20-FEB-16:01 9731.11 21-FEB-16:01 4493.81 20-FEB-16:02 2845.29 20-FEB-16:01 0.00 01-FEB-00:10
March 0.447213E+09 0.109565E+09 119.56 0.334256E+09 0.112958E+09 0.00 1.00 07-MAR-16:01 0.00 01-MAR-00:10 13874.55 19-MAR-20:01 10978.69 28-MAR-16:51 5950.33 29-MAR-15:02 2972.94 19-MAR-20:01 0.00 01-MAR-00:10
April 0.187888E+10 0.462359E+09 302.45 0.145832E+10 0.420560E+09 0.00 1.00 03-APR-15:01 0.00 01-APR-00:10 14909.28 18-APR-08:51 13100.53 17-APR-16:32 6578.31 18-APR-08:55 3132.35 18-APR-08:51 0.00 01-APR-00:10
May 0.390424E+10 0.953280E+09 548.05 0.288502E+10 0.101922E+10 0.00 1.00 01-MAY-08:61 0.00 01-MAY-02:20 15291.23 11-MAY-20:01 12997.05 06-MAY-16:32 7187.72 11-MAY-20:24 3184.37 11-MAY-20:01 0.00 01-MAY-00:10
June 0.623989E+10 0.153685E+10 567.81 0.454365E+10 0.169624E+10 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 15630.81 13-JUN-08:51 12919.05 08-JUN-16:21 8387.72 13-JUN-08:52 3227.56 13-JUN-08:51 0.00 01-JUN-00:10
July 0.733748E+10 0.177928E+10 569.01 0.518458E+10 0.215290E+10 0.00 1.00 01-JUL-07:51 0.00 01-JUL-05:11 15477.65 20-JUL-08:51 13125.00 23-JUL-16:21 7926.82 20-JUL-08:53 3219.40 17-JUL-08:51 0.00 01-JUL-00:10
August 0.660063E+10 0.160814E+10 565.86 0.463936E+10 0.196127E+10 0.00 1.00 01-AUG-08:51 0.00 01-AUG-05:11 15669.07 22-AUG-08:51 13224.87 16-AUG-16:21 8294.97 22-AUG-08:52 3232.56 22-AUG-08:51 0.00 01-AUG-00:10
September 0.398097E+10 0.983400E+09 505.52 0.303531E+10 0.945666E+09 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 14897.95 11-SEP-08:51 13132.37 15-SEP-16:32 6929.74 12-SEP-08:54 3131.10 11-SEP-08:51 0.00 01-SEP-00:10
October 0.116490E+10 0.286483E+09 312.14 0.865920E+09 0.298977E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-00:10 14058.59 09-OCT-15:01 11616.92 19-OCT-17:11 6453.68 09-OCT-15:02 3003.28 09-OCT-15:01 0.00 01-OCT-00:10
November 0.482261E+09 0.118853E+09 125.52 0.325687E+09 0.156575E+09 0.00 1.00 01-NOV-15:01 0.00 01-NOV-00:10 14171.55 08-NOV-16:01 10765.48 04-NOV-18:01 6944.83 08-NOV-16:01 3021.48 08-NOV-16:01 0.00 01-NOV-00:10
December 5519136.82 1319120.14 1.00 3993539.97 1525596.85 0.00 1.00 02-DEC-16:01 0.00 01-DEC-00:10 12932.30 03-DEC-16:01 8574.47 02-DEC-16:01 4659.41 03-DEC-16:01 2803.76 03-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.320905E+11 0.785115E+10 3631.35 0.233110E+11 0.877943E+10 0.00                            
Minimum of Months 3500184.27 844158.47 0.58 2481659.94 1018524.33 0.00 0.90   0.00   11087.67   7875.67   3212.00   2452.78   0.00  
Maximum of Months 0.733748E+10 0.177928E+10 569.01 0.518458E+10 0.215290E+10 0.00 1.00   0.00   15669.07   13224.87   8387.72   3232.56   0.00  



Table of Contents

Report: DXReportMonthly

For: 413 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 9154945.92 2444086.58 18.35 8312310.30 842635.62 0.00 0.12 16-APR-15:00 0.00 01-APR-00:10 270.38 16-APR-15:00 229.57 16-APR-15:00 40.82 16-APR-15:00 72.26 16-APR-15:00 0.00 01-APR-00:10
May 14529943.54 3819069.32 29.02 13018347.77 1511595.77 0.00 0.18 31-MAY-15:00 0.00 01-MAY-00:10 393.10 31-MAY-15:00 353.48 31-MAY-15:00 55.86 30-MAY-15:00 107.95 31-MAY-15:00 0.00 01-MAY-00:10
June 91796160.81 24560012.46 133.03 79679781.38 12116379.43 0.00 0.25 11-JUN-15:00 0.00 01-JUN-00:10 580.73 11-JUN-15:00 470.39 11-JUN-15:00 115.79 13-JUN-15:00 165.69 11-JUN-15:00 0.00 01-JUN-00:10
July 0.119557E+09 30879245.16 167.22 0.101131E+09 18425805.95 0.00 0.22 03-JUL-15:00 0.00 01-JUL-00:10 511.10 03-JUL-15:00 404.00 05-JUL-17:27 146.21 26-JUL-15:00 137.21 03-JUL-15:00 0.00 01-JUL-00:10
August 75819175.80 19816986.01 129.98 63348833.28 12470342.53 0.00 0.31 04-AUG-15:00 0.00 01-AUG-00:10 738.41 04-AUG-15:00 522.32 04-AUG-15:00 216.10 04-AUG-15:00 207.57 04-AUG-15:00 0.00 01-AUG-00:10
September 39285510.27 10569982.06 69.29 37382674.69 1902835.58 0.00 0.23 07-SEP-15:00 0.00 01-SEP-00:10 493.46 07-SEP-15:00 489.38 07-SEP-15:00 32.88 01-SEP-16:11 140.20 07-SEP-15:00 0.00 01-SEP-00:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.350143E+09 92089381.60 546.88 0.302873E+09 47269594.88 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.119557E+09 30879245.16 167.22 0.101131E+09 18425805.95 0.00 0.31   0.00   738.41   522.32   216.10   207.57   0.00  



Table of Contents

Report: DXReportMonthly

For: 414 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 3751064.22 1012276.22 12.42 3327512.56 423551.66 0.00 0.11 18-APR-15:00 0.00 01-APR-00:10 224.56 18-APR-15:00 192.80 18-APR-15:00 31.77 18-APR-15:00 60.12 18-APR-15:00 0.00 01-APR-00:10
May 10604665.88 2833493.91 24.50 9300731.20 1303934.68 0.00 0.18 31-MAY-15:00 0.00 01-MAY-00:10 343.94 31-MAY-15:00 317.34 31-MAY-14:40 37.63 30-MAY-14:40 94.63 31-MAY-15:00 0.00 01-MAY-00:10
June 72709881.32 19582301.18 150.88 62701103.39 10008777.94 0.00 0.24 11-JUN-15:00 0.00 01-JUN-00:10 486.48 11-JUN-15:00 387.35 26-JUN-14:10 100.20 11-JUN-15:00 138.59 11-JUN-15:00 0.00 01-JUN-00:10
July 80815212.31 21001119.78 183.57 66977353.15 13837859.16 0.00 0.18 03-JUL-15:00 0.00 01-JUL-00:10 375.20 03-JUL-15:00 304.51 02-JUL-14:30 119.14 26-JUL-15:00 100.96 03-JUL-15:00 0.00 01-JUL-00:10
August 50416555.02 13385558.64 129.72 40915293.31 9501261.71 0.00 0.28 04-AUG-15:00 0.00 01-AUG-00:10 570.12 04-AUG-15:00 414.36 04-AUG-15:00 155.76 04-AUG-15:00 161.51 04-AUG-15:00 0.00 01-AUG-00:10
September 23372248.50 6480497.13 61.62 22345479.37 1026769.13 0.00 0.22 07-SEP-14:05 0.00 01-SEP-00:10 404.23 07-SEP-14:05 400.50 07-SEP-14:10 24.80 11-SEP-15:00 115.97 07-SEP-14:05 0.00 01-SEP-00:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.241670E+09 64295246.86 562.70 0.205567E+09 36102154.27 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 80815212.31 21001119.78 183.57 66977353.15 13837859.16 0.00 0.28   0.00   570.12   414.36   155.76   161.51   0.00  



Table of Contents

Report: DXReportMonthly

For: 415_418 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 12299073.73 2837327.88 3.94 9227437.37 3071636.36 0.00 1.00 01-JAN-09:01 0.00 01-JAN-00:10 12534.27 13-JAN-16:01 9752.80 02-JAN-09:01 3757.23 13-JAN-16:01 2722.81 13-JAN-16:01 0.00 01-JAN-00:10
February 84642306.55 20284092.29 38.02 64042906.36 20599400.19 0.00 1.00 07-FEB-09:01 0.00 01-FEB-00:10 12964.70 20-FEB-16:01 10497.78 19-FEB-09:01 4648.89 20-FEB-16:01 2805.91 20-FEB-16:01 0.00 01-FEB-00:10
March 0.690614E+09 0.169689E+09 194.23 0.537482E+09 0.153133E+09 0.00 1.00 05-MAR-09:01 0.00 01-MAR-00:10 13375.58 19-MAR-18:41 11319.21 28-MAR-16:51 5114.88 12-MAR-15:01 2880.55 19-MAR-18:41 0.00 01-MAR-00:10
April 0.222574E+10 0.548022E+09 386.50 0.175435E+10 0.471392E+09 0.00 1.00 01-APR-08:61 0.00 01-APR-00:10 14131.40 16-APR-08:11 12369.92 30-APR-17:11 5471.06 08-APR-15:02 3006.26 16-APR-08:11 0.00 01-APR-00:10
May 0.465976E+10 0.113713E+10 602.02 0.354195E+10 0.111781E+10 0.00 1.00 01-MAY-08:61 0.00 01-MAY-07:01 14558.59 12-MAY-08:11 12449.63 21-MAY-16:51 6329.80 12-MAY-08:15 3071.69 31-MAY-08:32 0.00 01-MAY-00:10
June 0.680387E+10 0.167141E+10 598.75 0.502127E+10 0.178260E+10 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 14969.86 13-JUN-08:61 12431.63 22-JUN-16:21 7223.91 13-JUN-08:04 3128.51 13-JUN-08:61 0.00 01-JUN-00:10
July 0.786708E+10 0.190409E+10 599.97 0.560930E+10 0.225778E+10 0.00 1.00 01-JUL-07:01 0.00 01-JUL-05:11 15159.28 20-JUL-08:61 11800.33 23-JUL-16:21 7555.17 20-JUL-08:04 3153.66 20-JUL-08:61 0.00 01-JUL-00:10
August 0.713274E+10 0.173411E+10 596.87 0.507157E+10 0.206117E+10 0.00 1.00 01-AUG-06:51 0.00 01-AUG-05:11 15141.06 31-AUG-08:61 12006.07 07-AUG-16:31 7494.38 31-AUG-08:04 3163.76 04-AUG-07:41 0.00 01-AUG-00:10
September 0.456899E+10 0.112610E+10 561.48 0.354209E+10 0.102690E+10 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 14449.69 11-SEP-08:61 12691.05 15-SEP-16:21 5848.19 11-SEP-08:06 3054.78 11-SEP-08:61 0.00 01-SEP-00:10
October 0.163269E+10 0.403472E+09 456.37 0.126135E+10 0.371338E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-00:10 13589.10 02-OCT-17:21 11858.35 20-OCT-16:51 5033.08 09-OCT-15:02 2917.57 02-OCT-17:21 0.00 01-OCT-00:10
November 0.681869E+09 0.168377E+09 176.74 0.481666E+09 0.200203E+09 0.00 1.00 01-NOV-08:61 0.00 01-NOV-00:10 13665.95 08-NOV-16:01 10671.26 11-NOV-09:01 5757.74 08-NOV-16:02 2930.61 08-NOV-16:01 0.00 01-NOV-00:10
December 17762846.23 4124974.77 5.28 13646637.26 4116208.97 0.00 1.00 02-DEC-09:01 0.00 01-DEC-00:10 12814.68 03-DEC-16:01 10277.40 02-DEC-09:01 4435.17 03-DEC-16:01 2777.53 03-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.363781E+11 0.888966E+10 4220.16 0.269079E+11 0.947011E+10 0.00                            
Minimum of Months 12299073.73 2837327.88 3.94 9227437.37 3071636.36 0.00 1.00   0.00   12534.27   9752.80   3757.23   2722.81   0.00  
Maximum of Months 0.786708E+10 0.190409E+10 602.02 0.560930E+10 0.225778E+10 0.00 1.00   0.00   15159.28   12691.05   7555.17   3163.76   0.00  



Table of Contents

Report: DXReportMonthly

For: 419 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 1766447.66 415047.68 2.78 1306909.95 459537.71 0.00 0.99 13-JAN-16:01 0.00 01-JAN-00:10 3357.09 13-JAN-16:01 2314.67 13-JAN-16:01 1042.42 13-JAN-16:01 730.59 13-JAN-16:01 0.00 01-JAN-00:10
February 18351127.21 4444367.43 32.48 13709484.67 4641642.54 0.00 1.00 07-FEB-16:01 0.00 01-FEB-00:10 3528.82 25-FEB-16:01 2780.55 19-FEB-09:01 1318.63 20-FEB-16:01 763.35 25-FEB-16:01 0.00 01-FEB-00:10
March 0.189574E+09 46714761.03 191.16 0.148570E+09 41004277.77 0.00 1.00 05-MAR-09:01 0.00 01-MAR-00:10 3627.83 29-MAR-15:01 3053.83 28-MAR-16:51 1399.47 29-MAR-15:02 781.27 29-MAR-15:01 0.00 01-MAR-00:10
April 0.649227E+09 0.159784E+09 404.05 0.520684E+09 0.128543E+09 0.00 1.00 01-APR-08:61 0.00 01-APR-00:10 3826.40 18-APR-08:61 3328.01 30-APR-17:11 1480.72 08-APR-15:01 814.34 18-APR-08:61 0.00 01-APR-00:10
May 0.139321E+10 0.339631E+09 614.26 0.108853E+10 0.304679E+09 0.00 1.00 01-MAY-08:61 0.00 01-MAY-07:01 3922.23 11-MAY-21:11 3379.74 06-MAY-16:51 1681.29 11-MAY-21:15 831.16 31-MAY-08:32 0.00 01-MAY-00:10
June 0.201092E+10 0.492784E+09 601.39 0.153197E+10 0.478952E+09 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 4027.90 13-JUN-08:61 3390.63 22-JUN-16:21 1929.74 13-JUN-08:04 844.08 13-JUN-08:61 0.00 01-JUN-00:10
July 0.231937E+10 0.559916E+09 599.19 0.171412E+10 0.605249E+09 0.00 1.00 01-JUL-07:01 0.00 01-JUL-05:11 4103.19 20-JUL-08:61 3229.46 23-JUL-16:21 2022.07 20-JUL-08:04 854.21 20-JUL-08:61 0.00 01-JUL-00:10
August 0.211060E+10 0.512009E+09 596.70 0.155595E+10 0.554647E+09 0.00 1.00 01-AUG-06:51 0.00 01-AUG-05:11 4116.87 31-AUG-08:61 3279.51 07-AUG-16:31 2058.67 31-AUG-08:03 856.00 31-AUG-08:61 0.00 01-AUG-00:10
September 0.137122E+10 0.337295E+09 574.26 0.109086E+10 0.280353E+09 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 3917.13 11-SEP-08:61 3393.48 20-SEP-16:51 1578.41 11-SEP-08:06 828.20 11-SEP-08:61 0.00 01-SEP-00:10
October 0.475615E+09 0.117599E+09 451.68 0.371991E+09 0.103624E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-00:10 3665.34 02-OCT-17:21 3248.54 20-OCT-16:51 1431.25 09-OCT-15:02 787.81 02-OCT-17:21 0.00 01-OCT-00:10
November 0.191919E+09 47461027.34 173.72 0.137440E+09 54478978.89 0.00 1.00 01-NOV-08:61 0.00 01-NOV-00:10 3718.59 08-NOV-16:01 2889.98 04-NOV-18:01 1585.56 08-NOV-16:02 796.85 08-NOV-16:01 0.00 01-NOV-00:10
December 2802098.92 657253.39 3.46 2118243.98 683854.94 0.00 1.00 02-DEC-09:01 0.00 01-DEC-00:10 3477.11 03-DEC-16:01 2729.73 02-DEC-09:01 1250.54 03-DEC-16:01 753.60 03-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.107346E+11 0.261871E+10 4245.13 0.817725E+10 0.255732E+10 0.00                            
Minimum of Months 1766447.66 415047.68 2.78 1306909.95 459537.71 0.00 0.99   0.00   3357.09   2314.67   1042.42   730.59   0.00  
Maximum of Months 0.231937E+10 0.559916E+09 614.26 0.171412E+10 0.605249E+09 0.00 1.00   0.00   4116.87   3393.48   2058.67   856.00   0.00  



Table of Contents

Report: DXReportMonthly

For: 420_423 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 8917815.32 2049614.32 1.51 6807368.68 2110446.63 0.00 1.00 01-JAN-09:01 0.00 01-JAN-00:10 11125.06 01-JAN-09:01 9005.79 02-JAN-09:01 2959.55 13-JAN-19:01 2421.89 01-JAN-09:01 0.00 01-JAN-00:10
February 51416841.04 12088814.26 21.09 38215589.85 13201251.19 0.00 1.00 07-FEB-09:01 0.00 01-FEB-00:10 12001.45 25-FEB-16:01 9662.15 19-FEB-09:01 4389.71 20-FEB-16:01 2597.55 25-FEB-16:01 0.00 01-FEB-00:10
March 0.524440E+09 0.128308E+09 166.26 0.397223E+09 0.127217E+09 0.00 1.00 04-MAR-09:01 0.00 01-MAR-00:10 12473.24 29-MAR-15:01 10159.29 28-MAR-16:51 5128.56 29-MAR-15:02 2682.69 29-MAR-15:01 0.00 01-MAR-00:10
April 0.186912E+10 0.459422E+09 351.89 0.143942E+10 0.429705E+09 0.00 1.00 01-APR-08:61 0.00 01-APR-00:10 13137.27 16-APR-08:11 11265.76 30-APR-17:11 5292.50 11-APR-15:02 2791.83 16-APR-08:11 0.00 01-APR-00:10
May 0.407743E+10 0.993338E+09 580.20 0.302507E+10 0.105236E+10 0.00 1.00 01-MAY-08:61 0.00 01-MAY-03:00 13503.12 12-MAY-08:11 11460.02 21-MAY-16:51 6059.41 12-MAY-08:15 2849.20 31-MAY-08:32 0.00 01-MAY-00:10
June 0.611037E+10 0.149891E+10 590.31 0.440137E+10 0.170900E+10 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 13869.58 13-JUN-08:61 11255.60 22-JUN-16:21 6893.35 13-JUN-08:04 2898.02 13-JUN-08:61 0.00 01-JUN-00:10
July 0.712501E+10 0.172127E+10 592.25 0.494660E+10 0.217841E+10 0.00 1.00 01-JUL-07:01 0.00 01-JUL-05:11 14119.26 20-JUL-08:61 10827.64 23-JUL-16:21 7272.60 20-JUL-08:03 2930.86 20-JUL-08:61 0.00 01-JUL-00:10
August 0.644177E+10 0.156263E+10 586.24 0.445782E+10 0.198395E+10 0.00 1.00 01-AUG-06:51 0.00 01-AUG-05:11 14113.19 31-AUG-08:61 11048.23 07-AUG-16:31 7208.86 31-AUG-08:04 2945.13 04-AUG-07:41 0.00 01-AUG-00:10
September 0.401800E+10 0.988657E+09 540.85 0.304765E+10 0.970355E+09 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 13461.63 11-SEP-08:61 11352.76 20-SEP-16:51 5650.59 11-SEP-08:06 2840.68 11-SEP-08:61 0.00 01-SEP-00:10
October 0.128779E+10 0.317218E+09 412.58 0.967735E+09 0.320060E+09 0.00 1.00 01-OCT-08:61 0.00 01-OCT-00:10 12602.56 02-OCT-17:21 10805.78 20-OCT-16:51 5197.61 09-OCT-15:02 2704.92 02-OCT-17:21 0.00 01-OCT-00:10
November 0.547651E+09 0.134806E+09 152.38 0.374019E+09 0.173633E+09 0.00 1.00 01-NOV-08:61 0.00 01-NOV-00:10 12913.96 08-NOV-16:01 9847.88 11-NOV-09:01 6075.80 08-NOV-16:03 2756.50 08-NOV-16:01 0.00 01-NOV-00:10
December 13208844.51 3019068.58 2.29 10254434.56 2954409.94 0.00 1.00 02-DEC-09:01 0.00 01-DEC-00:10 11773.56 03-DEC-16:01 9484.43 25-DEC-09:01 4229.71 03-DEC-16:01 2554.11 03-DEC-16:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.320751E+11 0.782172E+10 3997.85 0.231122E+11 0.896296E+10 0.00                            
Minimum of Months 8917815.32 2049614.32 1.51 6807368.68 2110446.63 0.00 1.00   0.00   11125.06   9005.79   2959.55   2421.89   0.00  
Maximum of Months 0.712501E+10 0.172127E+10 592.25 0.494660E+10 0.217841E+10 0.00 1.00   0.00   14119.26   11460.02   7272.60   2945.13   0.00  



Table of Contents

Report: DXReportMonthly

For: 424 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 352663.90 88173.83 0.36 249194.56 103469.34 0.00 0.24 13-JAN-16:03 0.00 01-JAN-00:10 696.37 13-JAN-16:03 472.33 13-JAN-16:03 224.04 13-JAN-16:03 171.71 13-JAN-16:03 0.00 01-JAN-00:10
February 1679939.17 406302.60 1.18 1166047.48 513891.69 0.00 0.93 24-FEB-16:01 0.00 01-FEB-00:10 3095.74 24-FEB-16:01 2017.68 24-FEB-16:01 1078.06 24-FEB-16:01 679.92 24-FEB-16:01 0.00 01-FEB-00:10
March 72604107.31 17854462.22 91.17 52068363.49 20535743.82 0.00 1.00 18-MAR-15:01 0.00 01-MAR-00:10 3604.20 19-MAR-15:01 2750.40 28-MAR-16:51 1650.05 29-MAR-15:01 773.68 19-MAR-15:01 0.00 01-MAR-00:10
April 0.426535E+09 0.104993E+09 272.92 0.326659E+09 99875739.21 0.00 1.00 05-APR-15:01 0.00 01-APR-00:10 3767.52 16-APR-08:11 3227.70 17-APR-16:51 1653.71 11-APR-15:01 800.18 16-APR-08:11 0.00 01-APR-00:10
May 0.108807E+10 0.265489E+09 555.28 0.816385E+09 0.271687E+09 0.00 1.00 01-MAY-08:61 0.00 01-MAY-02:00 3849.33 11-MAY-18:11 3306.41 06-MAY-16:51 1763.26 12-MAY-08:14 812.48 11-MAY-18:11 0.00 01-MAY-00:10
June 0.180520E+10 0.443013E+09 581.98 0.134904E+10 0.456158E+09 0.00 1.00 01-JUN-08:61 0.00 01-JUN-07:01 3931.64 13-JUN-08:61 3140.18 22-JUN-16:41 1948.38 13-JUN-08:03 824.20 13-JUN-08:61 0.00 01-JUN-00:10
July 0.213241E+10 0.515327E+09 590.28 0.154683E+10 0.585583E+09 0.00 1.00 01-JUL-07:01 0.00 01-JUL-05:11 4006.95 20-JUL-08:61 3132.45 23-JUL-16:21 2055.55 20-JUL-08:03 834.37 20-JUL-08:61 0.00 01-JUL-00:10
August 0.189691E+10 0.460669E+09 583.47 0.136489E+10 0.532019E+09 0.00 1.00 01-AUG-06:51 0.00 01-AUG-05:11 4016.80 31-AUG-08:61 3184.87 07-AUG-16:31 2121.10 31-AUG-08:61 838.77 04-AUG-07:41 0.00 01-AUG-00:10
September 0.112628E+10 0.277395E+09 511.62 0.871734E+09 0.254547E+09 0.00 1.00 01-SEP-08:51 0.00 01-SEP-07:01 3851.52 11-SEP-08:61 3283.55 20-SEP-16:51 1605.81 21-SEP-15:02 812.80 11-SEP-08:61 0.00 01-SEP-00:10
October 0.229730E+09 56570159.75 259.83 0.165885E+09 63844619.83 0.00 1.00 01-OCT-08:61 0.00 01-OCT-00:10 3708.06 09-OCT-15:01 2988.55 20-OCT-16:51 1836.96 09-OCT-15:01 790.83 09-OCT-15:01 0.00 01-OCT-00:10
November 96842493.65 23979084.26 111.30 62621170.99 34221322.66 0.00 1.00 01-NOV-15:01 0.00 01-NOV-00:10 3697.05 08-NOV-16:01 2605.16 04-NOV-18:01 1853.25 08-NOV-16:01 789.06 08-NOV-16:01 0.00 01-NOV-00:10
December 615086.44 153705.26 0.55 459546.96 155539.48 0.00 0.25 02-DEC-19:03 0.00 01-DEC-00:10 709.65 02-DEC-19:03 485.72 01-DEC-16:04 236.28 02-DEC-16:03 174.88 02-DEC-19:03 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.887723E+10 0.216594E+10 3559.94 0.655799E+10 0.231924E+10 0.00                            
Minimum of Months 352663.90 88173.83 0.36 249194.56 103469.34 0.00 0.24   0.00   696.37   472.33   224.04   171.71   0.00  
Maximum of Months 0.213241E+10 0.515327E+09 590.28 0.154683E+10 0.585583E+09 0.00 1.00   0.00   4016.80   3306.41   2121.10   838.77   0.00  



Table of Contents

Report: DXReportMonthly

For: CORRIDORFLR1 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.316690E+09 80586170.41 107.94 0.316690E+09 0.00 0.00 0.10 13-JAN-22:05 0.00 01-JAN-06:01 3371.93 13-JAN-22:05 3371.93 13-JAN-22:05 0.00 18-JAN-03:20 849.38 13-JAN-22:05 0.00 01-JAN-00:10
February 0.755126E+09 0.191817E+09 179.96 0.755126E+09 -0.0 0.00 0.13 25-FEB-22:04 0.00 01-FEB-00:10 4179.41 25-FEB-22:04 4179.41 25-FEB-22:04 0.00 25-FEB-17:00 1048.92 25-FEB-22:04 0.00 01-FEB-00:10
March 0.251506E+10 0.636141E+09 373.11 0.250694E+10 8115668.62 0.00 0.16 19-MAR-16:00 0.00 01-MAR-00:10 5671.56 19-MAR-16:00 5386.83 19-MAR-15:55 588.68 19-MAR-17:03 1416.79 19-MAR-16:00 0.00 01-MAR-00:10
April 0.638946E+10 0.161477E+10 529.75 0.606434E+10 0.325121E+09 0.00 0.48 16-APR-16:20 0.00 01-APR-05:01 18270.92 16-APR-16:20 14733.55 15-APR-16:13 4696.47 18-APR-17:00 4683.24 16-APR-16:20 0.00 01-APR-00:10
May 0.127372E+11 0.318989E+10 685.58 0.116759E+11 0.106132E+10 0.00 0.46 31-MAY-17:00 0.00 01-MAY-05:01 17430.26 31-MAY-17:00 13867.99 31-MAY-16:23 4337.91 11-MAY-17:02 4513.65 31-MAY-17:00 0.00 01-MAY-00:10
June 0.182193E+11 0.460179E+10 689.67 0.155844E+11 0.263490E+10 0.00 0.69 11-JUN-16:20 0.00 01-JUN-06:01 27627.38 11-JUN-16:20 18352.26 11-JUN-16:02 9517.15 11-JUN-16:20 7260.30 11-JUN-16:20 0.00 01-JUN-00:10
July 0.220508E+11 0.549162E+10 727.40 0.179890E+11 0.406175E+10 0.00 0.68 26-JUL-16:20 0.00 01-JUL-06:01 29596.46 26-JUL-16:20 15561.83 26-JUL-16:02 14546.99 26-JUL-16:30 7221.11 26-JUL-16:20 0.00 01-JUL-00:10
August 0.212174E+11 0.529715E+10 718.27 0.176140E+11 0.360342E+10 0.00 0.79 04-AUG-16:10 0.00 01-AUG-06:01 32819.92 04-AUG-16:10 19242.23 04-AUG-16:02 14372.94 04-AUG-16:20 8506.28 04-AUG-16:10 0.00 01-AUG-00:10
September 0.145045E+11 0.365967E+10 669.90 0.136739E+11 0.830608E+09 0.00 0.55 06-SEP-16:20 0.00 01-SEP-06:01 20690.40 06-SEP-16:20 17776.75 07-SEP-16:02 4133.86 11-SEP-16:30 5481.84 06-SEP-16:20 0.00 01-SEP-00:10
October 0.755324E+10 0.190042E+10 634.57 0.749550E+10 57732323.78 0.00 0.23 21-OCT-17:02 0.00 01-OCT-05:01 8452.59 21-OCT-17:02 7831.84 21-OCT-17:02 949.06 02-OCT-17:05 2086.70 21-OCT-17:02 0.00 01-OCT-00:10
November 0.356521E+10 0.899148E+09 394.59 0.350601E+10 59203806.14 0.00 0.18 08-NOV-18:15 0.00 01-NOV-06:01 6719.00 08-NOV-18:15 5970.23 03-NOV-17:07 920.59 08-NOV-18:15 1669.32 08-NOV-18:15 0.00 01-NOV-00:10
December 0.644021E+09 0.163869E+09 200.51 0.644021E+09 0.00 0.00 0.10 02-DEC-22:14 0.00 01-DEC-06:01 3441.81 02-DEC-22:14 3441.81 02-DEC-22:14 0.00 03-DEC-05:08 866.72 02-DEC-22:14 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.110468E+12 0.277269E+11 5911.24 0.978258E+11 0.126422E+11 0.00                            
Minimum of Months 0.316690E+09 80586170.41 107.94 0.316690E+09 -0.0 0.00 0.10   0.00   3371.93   3371.93   0.00   849.38   0.00  
Maximum of Months 0.220508E+11 0.549162E+10 727.40 0.179890E+11 0.406175E+10 0.00 0.79   0.00   32819.92   19242.23   14546.99   8506.28   0.00  



Table of Contents

Report: DXReportMonthly

For: CORRIDORFLR2 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 9387796.03 2383577.91 19.18 8915780.48 472015.55 0.00 0.08 19-MAR-18:52 0.00 01-MAR-00:10 290.03 19-MAR-18:52 263.97 19-MAR-18:52 26.06 19-MAR-18:52 73.37 19-MAR-18:52 0.00 01-MAR-00:10
April 0.573007E+09 0.141326E+09 188.17 0.500573E+09 72433594.58 0.00 0.60 18-APR-15:00 0.00 01-APR-00:10 2440.49 18-APR-15:00 1979.25 18-APR-15:00 496.20 18-APR-13:00 610.42 18-APR-15:00 0.00 01-APR-00:10
May 0.186376E+10 0.456339E+09 615.21 0.161669E+10 0.247068E+09 0.00 0.63 31-MAY-15:00 0.00 01-MAY-00:10 2467.49 31-MAY-15:00 2214.07 31-MAY-15:00 480.42 29-MAY-16:21 638.83 31-MAY-15:00 0.00 01-MAY-00:10
June 0.371065E+10 0.901367E+09 665.75 0.304703E+10 0.663622E+09 0.00 0.78 11-JUN-15:10 0.00 02-JUN-02:30 3228.68 11-JUN-15:10 2454.23 11-JUN-15:01 824.35 13-JUN-15:00 853.87 11-JUN-15:10 0.00 01-JUN-00:10
July 0.498454E+10 0.119165E+10 744.00 0.393586E+10 0.104868E+10 0.00 0.75 26-JUL-15:20 0.12 23-JUL-05:00 3267.18 26-JUL-18:20 2309.60 02-JUL-15:02 1172.77 26-JUL-18:30 805.29 26-JUL-15:20 0.00 01-JUL-00:10
August 0.456037E+10 0.109617E+10 744.00 0.364289E+10 0.917476E+09 0.00 0.82 04-AUG-15:13 0.05 07-AUG-05:55 3453.39 04-AUG-15:13 2510.37 04-AUG-15:13 1173.08 04-AUG-13:00 914.45 04-AUG-15:13 0.00 01-AUG-00:10
September 0.234592E+10 0.575076E+09 559.94 0.212442E+10 0.221500E+09 0.00 0.68 06-SEP-15:01 0.00 15-SEP-03:30 2663.57 06-SEP-15:01 2411.37 07-SEP-15:01 479.89 11-SEP-09:00 711.95 06-SEP-15:00 0.00 01-SEP-00:10
October 0.181182E+09 45310699.12 140.67 0.174431E+09 6750469.71 0.00 0.25 20-OCT-16:42 0.00 01-OCT-00:10 920.53 20-OCT-16:47 920.53 20-OCT-16:47 123.41 02-OCT-15:10 226.75 20-OCT-16:47 0.00 01-OCT-00:10
November 23736109.33 6016508.28 41.53 22047054.43 1689054.90 0.00 0.13 03-NOV-15:02 0.00 01-NOV-00:10 444.81 03-NOV-15:02 444.81 03-NOV-15:02 34.52 08-NOV-19:13 111.78 03-NOV-15:02 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.182526E+11 0.441563E+10 3718.45 0.150729E+11 0.317969E+10 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.498454E+10 0.119165E+10 744.00 0.393586E+10 0.104868E+10 0.00 0.82   0.12   3453.39   2510.37   1173.08   914.45   0.00  



Table of Contents

Report: DXReportMonthly

For: CORRIDORFLR3 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 0.207189E+09 49630984.63 74.13 0.151019E+09 56170206.56 0.00 0.85 16-APR-15:13 0.00 01-APR-00:10 1668.35 18-APR-15:00 1222.44 16-APR-15:13 489.62 18-APR-15:11 396.06 16-APR-15:23 0.00 01-APR-00:10
May 0.456888E+09 0.108835E+09 204.58 0.330870E+09 0.126018E+09 0.00 0.95 31-MAY-15:02 0.00 01-MAY-00:10 1827.77 31-MAY-15:02 1527.24 31-MAY-15:00 510.86 29-MAY-18:41 443.26 31-MAY-15:00 0.00 01-MAY-00:10
June 0.211984E+10 0.493995E+09 527.66 0.147647E+10 0.643373E+09 0.00 1.00 11-JUN-12:30 0.00 01-JUN-02:70 2099.98 11-JUN-15:10 1573.58 29-JUN-15:55 854.41 13-JUN-15:00 516.01 11-JUN-15:00 0.00 01-JUN-00:10
July 0.299175E+10 0.686711E+09 711.61 0.196097E+10 0.103077E+10 0.00 1.00 02-JUL-12:00 0.00 11-JUL-01:40 2293.96 26-JUL-19:00 1513.39 05-JUL-15:20 1204.41 26-JUL-19:00 506.91 26-JUL-18:00 0.00 01-JUL-00:10
August 0.239594E+10 0.556769E+09 666.35 0.156791E+10 0.828029E+09 0.00 1.00 02-AUG-14:10 0.00 06-AUG-06:01 2242.69 04-AUG-13:00 1424.78 01-AUG-15:20 1121.50 04-AUG-08:02 531.23 04-AUG-16:00 0.00 01-AUG-00:10
September 0.937314E+09 0.225208E+09 337.46 0.741182E+09 0.196132E+09 0.00 0.96 06-SEP-15:11 0.00 01-SEP-03:00 1849.42 06-SEP-15:11 1625.49 07-SEP-15:20 500.07 11-SEP-20:42 462.56 06-SEP-15:02 0.00 01-SEP-00:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.910892E+10 0.212115E+10 2521.79 0.622842E+10 0.288050E+10 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.299175E+10 0.686711E+09 711.61 0.196097E+10 0.103077E+10 0.00 1.00   0.00   2293.96   1625.49   1204.41   531.23   0.00  



Table of Contents

Report: DXReportMonthly

For: CORRIDORFLR4 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 0.291521E+09 70149162.64 68.25 0.235490E+09 56031230.14 0.00 0.90 18-APR-15:00 0.00 01-APR-00:10 2587.37 18-APR-15:00 2057.44 16-APR-15:02 605.03 18-APR-13:00 613.22 18-APR-15:00 0.00 01-APR-00:10
May 0.762031E+09 0.181864E+09 231.40 0.627174E+09 0.134856E+09 0.00 0.99 31-MAY-15:00 0.00 01-MAY-00:10 2775.45 31-MAY-15:00 2477.34 31-MAY-15:00 636.79 31-MAY-09:01 673.53 31-MAY-15:00 0.00 01-MAY-00:10
June 0.229506E+10 0.542853E+09 417.83 0.177975E+10 0.515310E+09 0.00 1.00 11-JUN-11:40 0.00 01-JUN-00:10 3041.01 13-JUN-15:02 2435.74 29-JUN-15:45 1135.00 26-JUN-08:02 743.95 11-JUN-15:00 0.00 01-JUN-00:10
July 0.300786E+10 0.699639E+09 545.75 0.221414E+10 0.793719E+09 0.00 1.00 02-JUL-11:40 0.00 01-JUL-01:30 3132.31 26-JUL-16:52 2433.69 29-JUL-15:00 1193.53 26-JUL-17:01 727.53 26-JUL-15:10 0.00 01-JUL-00:10
August 0.247669E+10 0.583296E+09 486.14 0.182795E+10 0.648747E+09 0.00 1.00 01-AUG-14:10 0.00 01-AUG-00:10 3155.55 04-AUG-11:10 2318.88 01-AUG-15:00 1413.85 04-AUG-08:02 764.24 04-AUG-16:00 0.00 01-AUG-00:10
September 0.103563E+10 0.251769E+09 260.51 0.906973E+09 0.128660E+09 0.00 1.00 06-SEP-14:15 0.00 01-SEP-00:10 2798.53 06-SEP-15:23 2659.10 07-SEP-14:00 558.37 11-SEP-11:20 703.98 06-SEP-14:20 0.00 01-SEP-00:10
October 3791690.46 954530.47 4.83 3791690.46 0.00 0.00 0.14 20-OCT-15:01 0.00 01-OCT-00:10 329.77 20-OCT-15:01 329.77 20-OCT-15:01 0.00 20-OCT-15:55 82.68 20-OCT-15:01 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.987259E+10 0.233052E+10 2014.70 0.759526E+10 0.227732E+10 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.300786E+10 0.699639E+09 545.75 0.221414E+10 0.793719E+09 0.00 1.00   0.00   3155.55   2659.10   1413.85   764.24   0.00  



Table of Contents

Report: DXReportMonthly

For: SAC_FRONTOFFICE COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 69207424.72 15133171.42 46.14 68009641.79 1197782.93 0.00 0.30 28-MAR-15:00 0.00 01-MAR-00:10 1136.74 28-MAR-15:00 1136.74 28-MAR-15:00 79.91 29-MAR-16:00 243.43 28-MAR-15:00 0.00 01-MAR-00:10
April 0.708748E+09 0.150821E+09 201.08 0.597305E+09 0.111443E+09 0.00 0.86 18-APR-11:00 0.00 01-APR-00:10 3930.53 18-APR-11:00 2933.43 18-APR-15:00 1049.80 18-APR-10:50 790.18 18-APR-11:00 0.00 01-APR-00:10
May 0.229205E+10 0.482809E+09 566.57 0.190568E+10 0.386364E+09 0.00 0.91 31-MAY-10:35 0.00 01-MAY-00:10 4106.54 31-MAY-09:55 3290.94 31-MAY-13:00 1080.90 30-MAY-09:55 836.11 31-MAY-10:45 0.00 01-MAY-00:10
June 0.464300E+10 0.963415E+09 667.10 0.361469E+10 0.102831E+10 0.00 1.00 26-JUN-09:01 0.00 01-JUN-03:00 4966.18 26-JUN-09:33 3607.54 26-JUN-15:55 1639.59 26-JUN-09:01 1009.45 26-JUN-10:35 0.00 01-JUN-00:10
July 0.607537E+10 0.123988E+10 744.00 0.450990E+10 0.156547E+10 0.00 1.00 03-JUL-12:30 0.05 23-JUL-04:00 5291.08 26-JUL-16:00 3426.43 03-JUL-15:00 1954.51 26-JUL-15:20 1091.70 26-JUL-16:00 0.00 01-JUL-00:10
August 0.578945E+10 0.118609E+10 741.97 0.437162E+10 0.141783E+10 0.00 1.00 01-AUG-09:55 0.00 07-AUG-03:10 5810.69 04-AUG-13:00 3878.85 04-AUG-15:55 2330.63 04-AUG-09:01 1305.70 04-AUG-16:00 0.00 01-AUG-00:10
September 0.328484E+10 0.689955E+09 602.87 0.289920E+10 0.385640E+09 0.00 1.00 06-SEP-15:00 0.00 04-SEP-05:23 4392.03 06-SEP-15:10 3734.35 07-SEP-14:05 1150.48 11-SEP-09:02 956.55 06-SEP-15:10 0.00 01-SEP-00:10
October 0.665823E+09 0.143242E+09 291.33 0.634897E+09 30925972.93 0.00 0.53 20-OCT-15:00 0.00 01-OCT-00:10 2189.37 02-OCT-15:01 2121.47 20-OCT-15:00 429.02 02-OCT-15:30 449.98 02-OCT-15:01 0.00 01-OCT-00:10
November 0.263124E+09 56763660.24 119.85 0.231798E+09 31325956.36 0.00 0.40 08-NOV-16:01 0.00 01-NOV-00:10 1624.42 08-NOV-16:01 1495.01 03-NOV-15:00 371.95 08-NOV-12:00 341.15 08-NOV-16:01 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.237916E+11 0.492811E+10 3980.91 0.188331E+11 0.495851E+10 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.607537E+10 0.123988E+10 744.00 0.450990E+10 0.156547E+10 0.00 1.00   0.05   5810.69   3878.85   2330.63   1305.70   0.00  



Table of Contents

Report: DXReportMonthly

For: SAC_FRONTLOUNGE COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 0.704768E+09 0.175218E+09 59.65 0.477137E+09 0.227631E+09 0.00 0.69 18-APR-08:51 0.00 01-APR-00:10 8282.79 18-APR-08:51 4828.35 18-APR-09:00 3454.80 18-APR-08:51 1879.67 18-APR-08:51 0.00 01-APR-00:10
May 0.125675E+10 0.309204E+09 133.45 0.839650E+09 0.417105E+09 0.00 0.78 31-MAY-08:51 0.00 01-MAY-00:10 9398.80 31-MAY-08:51 6186.48 31-MAY-09:00 3642.64 31-MAY-08:61 2173.91 31-MAY-08:51 0.00 01-MAY-00:10
June 0.594318E+10 0.144913E+10 394.86 0.383742E+10 0.210576E+10 0.00 0.93 26-JUN-07:11 0.00 01-JUN-00:10 12596.20 26-JUN-07:11 6872.09 26-JUN-09:00 6705.96 26-JUN-07:11 2684.24 26-JUN-07:11 0.00 01-JUN-00:10
July 0.856946E+10 0.204783E+10 543.84 0.515572E+10 0.341374E+10 0.00 0.91 03-JUL-08:25 0.00 01-JUL-00:10 11985.42 03-JUL-08:30 6518.67 02-JUL-08:51 6275.38 07-JUL-08:51 2583.35 03-JUL-08:30 0.00 01-JUL-00:10
August 0.734877E+10 0.176136E+10 470.27 0.447376E+10 0.287501E+10 0.00 1.00 03-AUG-06:12 0.00 01-AUG-00:10 16158.48 04-AUG-06:50 7061.49 03-AUG-08:53 10317.78 04-AUG-06:50 3325.85 04-AUG-06:50 0.00 01-AUG-00:10
September 0.303519E+10 0.753266E+09 258.06 0.229164E+10 0.743548E+09 0.00 0.83 11-SEP-08:50 0.00 01-SEP-00:10 10554.06 11-SEP-08:50 6350.19 08-SEP-08:52 4580.24 11-SEP-08:50 2323.49 11-SEP-08:50 0.00 01-SEP-00:10
October 35083930.47 8790017.62 9.50 32649685.03 2434245.45 0.00 0.29 20-OCT-15:10 0.00 01-OCT-00:10 2815.71 20-OCT-15:10 2734.95 20-OCT-15:01 196.30 21-OCT-15:00 692.72 20-OCT-15:10 0.00 01-OCT-00:10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.268932E+11 0.650480E+10 1869.63 0.171080E+11 0.978523E+10 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.856946E+10 0.204783E+10 543.84 0.515572E+10 0.341374E+10 0.00 1.00   0.00   16158.48   7061.49   10317.78   3325.85   0.00  



Table of Contents

Report: DXReportMonthly

For: SAC_MEETINGROOM COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 382031.97 84624.40 0.33 354905.51 27126.46 0.00 0.10 28-MAR-12:50 0.00 01-MAR-00:10 489.30 28-MAR-12:50 458.80 28-MAR-12:50 30.50 28-MAR-12:50 108.14 28-MAR-12:50 0.00 01-MAR-00:10
April 0.375624E+09 81982061.51 127.44 0.270212E+09 0.105411E+09 0.00 0.68 18-APR-13:00 0.00 01-APR-00:10 4401.32 18-APR-13:00 2755.20 18-APR-13:00 1646.12 18-APR-13:00 912.20 18-APR-13:00 0.00 01-APR-00:10
May 0.966969E+09 0.210205E+09 499.11 0.710760E+09 0.256208E+09 0.00 0.71 31-MAY-13:00 0.00 01-MAY-00:10 4390.97 31-MAY-13:00 3257.38 31-MAY-13:00 1443.27 30-MAY-13:00 961.85 31-MAY-13:00 0.00 01-MAY-00:10
June 0.284696E+10 0.615033E+09 616.05 0.197141E+10 0.875552E+09 0.00 0.81 27-JUN-13:00 0.00 01-JUN-07:01 5537.78 13-JUN-13:00 3557.15 26-JUN-13:00 2610.15 13-JUN-13:00 1126.79 27-JUN-13:00 0.00 01-JUN-00:10
July 0.395525E+10 0.839944E+09 740.67 0.260344E+10 0.135181E+10 0.00 0.89 03-JUL-13:00 0.00 10-JUL-09:23 6246.78 03-JUL-13:00 3268.25 03-JUL-13:00 2978.53 03-JUL-13:00 1254.34 03-JUL-13:00 0.00 01-JUL-00:10
August 0.375596E+10 0.800460E+09 741.46 0.252104E+10 0.123492E+10 0.00 1.00 04-AUG-12:40 0.00 06-AUG-09:01 7492.36 04-AUG-13:00 3702.15 04-AUG-13:00 3790.21 04-AUG-13:00 1528.85 04-AUG-13:00 0.00 01-AUG-00:10
September 0.185456E+10 0.406147E+09 563.62 0.150618E+10 0.348381E+09 0.00 0.78 06-SEP-13:00 0.00 12-SEP-09:01 4848.20 06-SEP-13:00 3720.50 07-SEP-13:00 1623.90 11-SEP-09:00 1058.96 06-SEP-13:00 0.00 01-SEP-00:10
October 0.117880E+09 26019219.59 152.74 0.103465E+09 14414342.70 0.00 0.34 20-OCT-13:00 0.00 01-OCT-00:10 1881.72 20-OCT-13:00 1703.57 20-OCT-13:00 490.79 02-OCT-12:10 400.19 20-OCT-13:00 0.00 01-OCT-00:10
November 17909872.53 3978329.56 43.96 14193591.79 3716280.74 0.00 0.18 03-NOV-12:30 0.00 01-NOV-00:10 974.72 03-NOV-12:30 794.81 03-NOV-12:13 219.22 08-NOV-13:40 212.59 03-NOV-12:30 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.138915E+11 0.298385E+10 3485.38 0.970106E+10 0.419044E+10 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.395525E+10 0.839944E+09 741.46 0.260344E+10 0.135181E+10 0.00 1.00   0.00   7492.36   3720.50   3790.21   1528.85   0.00  



Table of Contents

Report: DXReportMonthly

For: SAC_EMPLOYEELOUNGE COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.176999E+10 0.383219E+09 470.45 0.176999E+10 -0.0 0.00 0.83 30-JAN-13:01 0.00 02-JAN-22:12 5951.49 30-JAN-13:01 5951.49 30-JAN-13:01 0.00 12-JAN-12:05 1167.27 30-JAN-13:01 0.00 01-JAN-00:10
February 0.239267E+10 0.514811E+09 519.33 0.239267E+10 0.00 0.00 0.49 24-FEB-13:00 0.00 01-FEB-00:10 3401.89 24-FEB-13:00 3401.89 24-FEB-13:00 0.00 24-FEB-16:07 707.20 24-FEB-13:00 0.00 01-FEB-00:10
March 0.396954E+10 0.847987E+09 723.57 0.396408E+10 5459229.14 0.00 0.55 28-MAR-12:00 0.00 04-MAR-03:50 4048.24 19-MAR-16:10 3971.25 28-MAR-12:00 262.27 29-MAR-12:00 832.44 19-MAR-16:10 0.00 01-MAR-00:10
April 0.533320E+10 0.113262E+10 720.00 0.520093E+10 0.132267E+09 0.00 0.79 18-APR-12:00 0.02 03-APR-04:00 6270.82 18-APR-12:00 5101.86 18-APR-12:00 1168.97 18-APR-12:00 1311.89 18-APR-12:00 0.00 01-APR-00:10
May 0.754561E+10 0.158173E+10 744.00 0.707232E+10 0.473291E+09 0.00 0.79 31-MAY-12:00 0.13 03-MAY-03:00 6124.98 31-MAY-12:00 5284.57 31-MAY-12:00 1057.52 30-MAY-12:00 1324.43 31-MAY-12:00 0.00 01-MAY-00:10
June 0.900294E+10 0.189349E+10 720.00 0.797501E+10 0.102793E+10 0.00 0.84 26-JUN-12:00 0.17 03-JUN-04:00 6658.01 27-JUN-12:00 5412.48 26-JUN-12:00 1507.18 13-JUN-12:00 1451.65 11-JUN-15:10 0.00 01-JUN-00:10
July 0.102438E+11 0.212709E+10 744.00 0.870769E+10 0.153614E+10 0.00 0.83 03-JUL-12:00 0.24 24-JUL-04:00 6842.89 03-JUL-12:00 5266.94 25-JUL-12:00 1689.90 03-JUL-12:00 1433.32 26-JUL-15:55 0.00 01-JUL-00:10
August 0.995627E+10 0.207267E+10 744.00 0.857682E+10 0.137945E+10 0.00 0.91 04-AUG-12:00 0.22 07-AUG-04:00 7507.77 04-AUG-12:00 5443.00 04-AUG-12:00 2064.77 04-AUG-12:00 1614.49 04-AUG-12:00 0.00 01-AUG-00:10
September 0.768802E+10 0.162190E+10 720.00 0.733737E+10 0.350649E+09 0.00 0.80 06-SEP-12:00 0.12 30-SEP-04:00 6325.02 11-SEP-12:00 5453.00 07-SEP-12:00 1121.99 11-SEP-12:00 1345.14 06-SEP-12:00 0.00 01-SEP-00:10
October 0.581763E+10 0.123125E+10 744.00 0.577892E+10 38708962.36 0.00 0.62 20-OCT-12:00 0.11 23-OCT-05:55 4752.02 02-OCT-12:00 4571.61 20-OCT-12:00 615.98 02-OCT-12:00 963.26 02-OCT-12:00 0.00 01-OCT-00:10
November 0.405917E+10 0.865334E+09 667.61 0.401140E+10 47775531.76 0.00 0.59 03-NOV-12:00 0.00 24-NOV-02:20 4529.44 08-NOV-13:00 4115.77 03-NOV-12:00 571.73 08-NOV-13:00 922.24 08-NOV-13:00 0.00 01-NOV-00:10
December 0.251691E+10 0.542967E+09 630.66 0.251691E+10 -0.0 0.00 0.43 02-DEC-16:00 0.00 07-DEC-02:40 2906.55 02-DEC-16:00 2906.55 02-DEC-16:00 0.00 02-DEC-16:06 609.73 02-DEC-16:00 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.702958E+11 0.148151E+11 8147.64 0.653041E+11 0.499167E+10 0.00                            
Minimum of Months 0.176999E+10 0.383219E+09 470.45 0.176999E+10 -0.0 0.00 0.43   0.00   2906.55   2906.55   0.00   609.73   0.00  
Maximum of Months 0.102438E+11 0.212709E+10 744.00 0.870769E+10 0.153614E+10 0.00 0.91   0.24   7507.77   5951.49   2064.77   1614.49   0.00  



Table of Contents

Report: DXReportMonthly

For: SAC_EXERCISECENTER COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10 0.00 01-JAN-00:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 16076337.56 3500609.51 18.75 13127701.22 2948636.34 0.00 0.35 19-MAR-16:00 0.00 01-MAR-00:10 672.12 19-MAR-16:00 496.02 19-MAR-16:00 176.13 19-MAR-15:55 142.47 19-MAR-16:00 0.00 01-MAR-00:10
April 0.338297E+09 69255581.05 103.13 0.239876E+09 98421760.10 0.00 1.00 16-APR-15:01 0.00 01-APR-00:10 2415.74 16-APR-15:55 1717.34 15-APR-16:00 808.19 18-APR-10:00 491.57 16-APR-15:55 0.00 01-APR-00:10
May 0.849596E+09 0.175128E+09 316.99 0.591668E+09 0.257927E+09 0.00 1.00 30-MAY-15:45 0.00 01-MAY-00:10 2368.49 31-MAY-15:01 1857.62 31-MAY-15:10 821.52 29-MAY-15:01 494.68 31-MAY-15:01 0.00 01-MAY-00:10
June 0.231137E+10 0.466290E+09 471.48 0.150824E+10 0.803129E+09 0.00 1.00 10-JUN-15:01 0.00 01-JUN-00:10 3648.21 11-JUN-15:01 2214.17 11-JUN-15:01 1438.45 13-JUN-15:01 798.60 11-JUN-15:01 0.00 01-JUN-00:10
July 0.312901E+10 0.618252E+09 580.41 0.189323E+10 0.123577E+10 0.00 1.00 01-JUL-15:11 0.00 01-JUL-00:10 3986.76 26-JUL-18:01 1926.48 26-JUL-16:00 2248.56 26-JUL-19:00 796.76 26-JUL-18:01 0.00 01-JUL-00:10
August 0.283869E+10 0.565067E+09 535.64 0.174306E+10 0.109563E+10 0.00 1.00 01-AUG-09:01 0.00 01-AUG-00:10 4187.21 04-AUG-16:00 2340.46 04-AUG-15:55 2035.27 04-AUG-13:00 919.25 04-AUG-16:00 0.00 01-AUG-00:10
September 0.127868E+10 0.263287E+09 346.52 0.996185E+09 0.282500E+09 0.00 1.00 06-SEP-12:10 0.00 01-SEP-00:10 2728.17 06-SEP-15:01 2127.94 07-SEP-16:00 816.40 11-SEP-09:55 598.02 06-SEP-15:01 0.00 01-SEP-00:10
October 91496993.97 19600056.07 68.54 76049283.05 15447710.91 0.00 0.57 20-OCT-15:01 0.00 01-OCT-00:10 1081.49 20-OCT-15:01 1019.74 20-OCT-15:01 297.75 02-OCT-15:01 221.82 20-OCT-15:01 0.00 01-OCT-00:10
November 8177471.69 1798552.46 14.85 6368901.36 1808570.33 0.00 0.22 03-NOV-15:01 0.00 01-NOV-00:10 376.14 03-NOV-15:01 340.72 03-NOV-15:01 112.70 08-NOV-19:03 81.51 03-NOV-15:01 0.00 01-NOV-00:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.108614E+11 0.218218E+10 2456.32 0.706781E+10 0.379359E+10 0.00                            
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00  
Maximum of Months 0.312901E+10 0.618252E+09 580.41 0.189323E+10 0.123577E+10 0.00 1.00   0.00   4187.21   2340.46   2248.56   919.25   0.00  



Table of Contents

Report: DXReportMonthly

For: SAC_RESTROOM COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 8464.12 1757.60 0.27 2722.22 5741.90 0.00 0.02 13-JAN-17:10 0.00 01-JAN-00:10 18.49 13-JAN-17:10 5.97 13-JAN-17:10 12.52 13-JAN-17:10 3.83 13-JAN-17:10 0.00 01-JAN-00:10
February 9376144.74 1932749.81 27.62 4263573.90 5112570.84 0.00 0.75 24-FEB-17:03 0.00 01-FEB-00:10 685.25 24-FEB-17:03 260.63 25-FEB-17:03 429.61 24-FEB-17:03 127.90 24-FEB-17:03 0.00 01-FEB-00:10
March 0.115984E+09 24857036.36 269.02 89449943.35 26534295.33 0.00 0.52 22-MAR-16:03 0.00 01-MAR-00:10 413.93 19-MAR-14:40 251.04 22-MAR-16:03 239.35 19-MAR-14:40 82.69 22-MAR-16:03 0.00 01-MAR-00:10
April 0.349339E+09 74405209.63 565.43 0.295113E+09 54225352.97 0.00 1.00 09-APR-15:01 0.00 01-APR-01:20 1018.26 09-APR-15:01 622.04 09-APR-15:01 455.00 06-APR-16:01 192.68 09-APR-15:01 0.00 01-APR-00:10
May 0.703055E+09 0.147995E+09 742.06 0.632908E+09 70146864.43 0.00 0.71 31-MAY-17:00 0.00 01-MAY-02:40 495.92 31-MAY-17:00 456.46 31-MAY-16:52 59.33 02-MAY-09:02 108.45 31-MAY-17:00 0.00 01-MAY-00:10
June 0.921296E+09 0.193014E+09 720.00 0.846452E+09 74844441.99 0.00 0.79 26-JUN-17:00 0.22 06-JUN-04:00 553.85 30-JUN-17:00 511.46 30-JUN-16:52 59.09 12-JUN-09:00 123.31 26-JUN-17:00 0.00 01-JUN-00:10
July 0.110388E+10 0.227577E+09 744.00 0.102502E+10 78860882.16 0.00 0.82 03-JUL-17:00 0.39 12-JUL-04:00 584.55 05-JUL-17:00 543.76 05-JUL-16:52 60.52 27-JUL-09:00 125.54 03-JUL-17:00 0.00 01-JUL-00:10
August 0.110826E+10 0.228504E+09 744.00 0.102821E+10 80051309.52 0.00 0.84 04-AUG-16:30 0.42 07-AUG-04:00 587.89 04-AUG-17:00 542.53 02-AUG-16:52 65.13 04-AUG-17:33 132.86 04-AUG-16:00 0.00 01-AUG-00:10
September 0.905812E+09 0.188372E+09 719.25 0.838158E+09 67654083.86 0.00 0.87 07-SEP-17:00 0.00 30-SEP-02:30 606.39 07-SEP-17:00 566.85 07-SEP-16:52 59.70 11-SEP-09:00 133.79 07-SEP-17:00 0.00 01-SEP-00:10
October 0.583182E+09 0.123588E+09 740.92 0.520806E+09 62375783.54 0.00 0.63 29-OCT-04:02 0.00 08-OCT-03:40 458.41 29-OCT-04:02 415.40 29-OCT-04:02 47.56 11-OCT-09:00 92.65 29-OCT-04:02 0.00 01-OCT-00:10
November 0.242052E+09 51541983.60 444.68 0.206898E+09 35153482.48 0.00 1.00 15-NOV-09:01 0.00 10-NOV-03:40 966.53 15-NOV-09:01 656.15 15-NOV-09:01 310.38 15-NOV-09:01 183.86 15-NOV-09:01 0.00 01-NOV-00:10
December 3190256.42 657134.96 12.98 1171551.47 2018704.96 0.00 0.18 03-DEC-16:00 0.00 01-DEC-00:10 151.28 03-DEC-16:00 56.69 03-DEC-16:30 95.91 03-DEC-15:40 30.93 03-DEC-16:00 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.604543E+10 0.126245E+10 5730.22 0.548845E+10 0.556984E+09 0.00                            
Minimum of Months 8464.12 1757.60 0.27 2722.22 5741.90 0.00 0.02   0.00   18.49   5.97   12.52   3.83   0.00  
Maximum of Months 0.110826E+10 0.228504E+09 744.00 0.102821E+10 80051309.52 0.00 1.00   0.42   1018.26   656.15   455.00   192.68   0.00  



Table of Contents

Report: WindowReportMonthly

For: W_CORRIDORFLR1_2_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 93.21 63.74 29.47 79.24 120.00 0.00 0.00 0.00
February 101.57 69.14 32.43 90.63 98.16 0.00 0.00 0.00
March 85.79 44.61 41.18 79.00 72.48 0.00 0.00 0.00
April 78.75 37.01 41.74 82.44 55.40 0.00 0.00 0.00
May 64.96 17.62 47.33 71.35 32.68 0.00 0.00 0.00
June 63.01 12.81 50.21 77.85 21.90 0.00 0.00 0.00
July 66.97 17.05 49.92 87.12 18.37 0.00 0.00 0.00
August 73.62 25.40 48.22 97.14 22.20 0.00 0.00 0.00
September 89.94 46.83 43.11 111.38 37.23 0.00 0.00 0.00
October 95.89 60.42 35.47 102.08 56.85 0.00 0.00 0.00
November 71.81 44.95 26.86 63.65 82.85 0.00 0.00 0.00
December 76.18 57.62 18.56 70.01 113.18 0.00 0.00 0.00
                 
Annual Sum or Average 80.01 41.27 38.74 84.28 60.76 0.00 0.00 0.00
Minimum of Months 63.01 12.81 18.56 63.65 18.37 0.00 0.00 0.00
Maximum of Months 101.57 69.14 50.21 111.38 120.00 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: D_CORRIDORFLR1_16_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.65 0.00 14.65 0.00 256.00 0.00 0.00 0.00
February 19.43 0.00 19.43 0.00 214.50 0.00 0.00 0.00
March 27.50 0.00 27.50 2.37 149.43 0.00 0.00 0.00
April 35.79 0.37 35.42 13.78 103.90 0.00 0.00 0.00
May 46.23 2.54 43.69 28.28 53.12 0.00 0.00 0.00
June 57.86 6.68 51.18 60.60 34.51 0.00 0.00 0.00
July 55.33 4.62 50.71 60.91 26.72 0.00 0.00 0.00
August 43.34 1.30 42.04 44.70 33.50 0.00 0.00 0.00
September 32.92 0.03 32.89 25.96 64.98 0.00 0.00 0.00
October 22.45 0.00 22.45 2.68 111.32 0.00 0.00 0.00
November 14.19 0.00 14.19 0.21 169.72 0.00 0.00 0.00
December 10.30 0.00 10.30 0.00 226.47 0.00 0.00 0.00
                 
Annual Sum or Average 31.73 1.30 30.43 20.07 119.87 0.00 0.00 0.00
Minimum of Months 10.30 0.00 10.30 0.00 26.72 0.00 0.00 0.00
Maximum of Months 57.86 6.68 51.18 60.91 256.00 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_CORRIDORFLR1_20_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 31.98 12.97 19.00 12.52 137.98 0.00 0.00 0.00
February 46.51 22.82 23.70 27.27 112.99 0.00 0.00 0.00
March 55.85 20.81 35.04 37.73 76.14 0.00 0.00 0.00
April 81.42 40.23 41.18 79.88 55.56 0.00 0.00 0.00
May 81.64 32.62 49.02 87.82 32.24 0.00 0.00 0.00
June 95.65 41.37 54.27 116.78 22.21 0.00 0.00 0.00
July 102.91 48.91 54.00 130.08 18.87 0.00 0.00 0.00
August 89.69 41.02 48.67 112.93 22.53 0.00 0.00 0.00
September 72.78 34.51 38.28 82.54 38.29 0.00 0.00 0.00
October 50.94 22.71 28.24 42.39 60.99 0.00 0.00 0.00
November 30.47 11.32 19.16 15.80 91.61 0.00 0.00 0.00
December 23.54 11.19 12.34 11.24 127.01 0.00 0.00 0.00
                 
Annual Sum or Average 63.69 28.38 35.31 63.26 66.14 0.00 0.00 0.00
Minimum of Months 23.54 11.19 12.34 11.24 18.87 0.00 0.00 0.00
Maximum of Months 102.91 48.91 54.27 130.08 137.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_FRONTLOUNGEFLR1_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.29 14.32 20.98 15.85 134.16 0.00 0.00 0.00
February 51.34 25.18 26.16 33.57 107.11 0.00 0.00 0.00
March 61.64 22.96 38.68 47.55 69.66 0.00 0.00 0.00
April 89.86 44.41 45.46 94.07 50.10 0.00 0.00 0.00
May 90.11 36.00 54.11 104.77 29.71 0.00 0.00 0.00
June 105.57 45.67 59.90 136.74 19.72 0.00 0.00 0.00
July 113.59 53.98 59.61 151.42 16.58 0.00 0.00 0.00
August 99.00 45.28 53.72 132.02 20.04 0.00 0.00 0.00
September 80.33 38.09 42.25 97.08 35.52 0.00 0.00 0.00
October 56.23 25.06 31.16 51.59 57.52 0.00 0.00 0.00
November 33.64 12.49 21.14 20.17 85.61 0.00 0.00 0.00
December 25.98 12.36 13.62 14.15 121.56 0.00 0.00 0.00
                 
Annual Sum or Average 70.29 31.32 38.97 75.12 62.07 0.00 0.00 0.00
Minimum of Months 25.98 12.36 13.62 14.15 16.58 0.00 0.00 0.00
Maximum of Months 113.59 53.98 59.90 151.42 134.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_FRONTLOUNGEFLR1_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.29 14.32 20.98 15.85 134.16 0.00 0.00 0.00
February 51.34 25.18 26.16 33.57 107.11 0.00 0.00 0.00
March 61.64 22.96 38.68 47.55 69.66 0.00 0.00 0.00
April 89.86 44.41 45.46 94.07 50.10 0.00 0.00 0.00
May 90.11 36.00 54.11 104.77 29.71 0.00 0.00 0.00
June 105.57 45.67 59.90 136.74 19.72 0.00 0.00 0.00
July 113.59 53.98 59.61 151.42 16.58 0.00 0.00 0.00
August 99.00 45.28 53.72 132.02 20.04 0.00 0.00 0.00
September 80.33 38.09 42.25 97.08 35.52 0.00 0.00 0.00
October 56.23 25.06 31.16 51.59 57.52 0.00 0.00 0.00
November 33.64 12.49 21.14 20.17 85.61 0.00 0.00 0.00
December 25.98 12.36 13.62 14.15 121.56 0.00 0.00 0.00
                 
Annual Sum or Average 70.29 31.32 38.97 75.12 62.07 0.00 0.00 0.00
Minimum of Months 25.98 12.36 13.62 14.15 16.58 0.00 0.00 0.00
Maximum of Months 113.59 53.98 59.90 151.42 134.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_FRONTLOUNGEFLR1_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.29 14.32 20.98 15.85 134.16 0.00 0.00 0.00
February 51.34 25.18 26.16 33.57 107.11 0.00 0.00 0.00
March 61.64 22.96 38.68 47.55 69.66 0.00 0.00 0.00
April 89.86 44.41 45.46 94.07 50.10 0.00 0.00 0.00
May 90.11 36.00 54.11 104.77 29.71 0.00 0.00 0.00
June 105.57 45.67 59.90 136.74 19.72 0.00 0.00 0.00
July 113.59 53.98 59.61 151.42 16.58 0.00 0.00 0.00
August 99.00 45.28 53.72 132.02 20.04 0.00 0.00 0.00
September 80.33 38.09 42.25 97.08 35.52 0.00 0.00 0.00
October 56.23 25.06 31.16 51.59 57.52 0.00 0.00 0.00
November 33.64 12.49 21.14 20.17 85.61 0.00 0.00 0.00
December 25.98 12.36 13.62 14.15 121.56 0.00 0.00 0.00
                 
Annual Sum or Average 70.29 31.32 38.97 75.12 62.07 0.00 0.00 0.00
Minimum of Months 25.98 12.36 13.62 14.15 16.58 0.00 0.00 0.00
Maximum of Months 113.59 53.98 59.90 151.42 134.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_FRONTLOUNGEFLR1_5_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.29 14.32 20.98 15.85 134.16 0.00 0.00 0.00
February 51.34 25.18 26.16 33.57 107.11 0.00 0.00 0.00
March 61.64 22.96 38.68 47.55 69.66 0.00 0.00 0.00
April 89.86 44.41 45.46 94.07 50.10 0.00 0.00 0.00
May 90.11 36.00 54.11 104.77 29.71 0.00 0.00 0.00
June 105.57 45.67 59.90 136.74 19.72 0.00 0.00 0.00
July 113.59 53.98 59.61 151.42 16.58 0.00 0.00 0.00
August 99.00 45.28 53.72 132.02 20.04 0.00 0.00 0.00
September 80.33 38.09 42.25 97.08 35.52 0.00 0.00 0.00
October 56.23 25.06 31.16 51.59 57.52 0.00 0.00 0.00
November 33.64 12.49 21.14 20.17 85.61 0.00 0.00 0.00
December 25.98 12.36 13.62 14.15 121.56 0.00 0.00 0.00
                 
Annual Sum or Average 70.29 31.32 38.97 75.12 62.07 0.00 0.00 0.00
Minimum of Months 25.98 12.36 13.62 14.15 16.58 0.00 0.00 0.00
Maximum of Months 113.59 53.98 59.90 151.42 134.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_FRONTLOUNGEFLR1_5_0_0_0_4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 35.29 14.32 20.98 15.85 134.16 0.00 0.00 0.00
February 51.34 25.18 26.16 33.57 107.11 0.00 0.00 0.00
March 61.64 22.96 38.68 47.55 69.66 0.00 0.00 0.00
April 89.86 44.41 45.46 94.07 50.10 0.00 0.00 0.00
May 90.11 36.00 54.11 104.77 29.71 0.00 0.00 0.00
June 105.57 45.67 59.90 136.74 19.72 0.00 0.00 0.00
July 113.59 53.98 59.61 151.42 16.58 0.00 0.00 0.00
August 99.00 45.28 53.72 132.02 20.04 0.00 0.00 0.00
September 80.33 38.09 42.25 97.08 35.52 0.00 0.00 0.00
October 56.23 25.06 31.16 51.59 57.52 0.00 0.00 0.00
November 33.64 12.49 21.14 20.17 85.61 0.00 0.00 0.00
December 25.98 12.36 13.62 14.15 121.56 0.00 0.00 0.00
                 
Annual Sum or Average 70.29 31.32 38.97 75.12 62.07 0.00 0.00 0.00
Minimum of Months 25.98 12.36 13.62 14.15 16.58 0.00 0.00 0.00
Maximum of Months 113.59 53.98 59.90 151.42 134.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_MEETINGROOMFLR1_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.55 7.93 11.62 8.56 77.57 0.00 0.00 0.00
February 28.44 13.95 14.49 18.26 62.41 0.00 0.00 0.00
March 34.14 12.72 21.42 26.05 40.94 0.00 0.00 0.00
April 49.77 24.60 25.18 52.00 29.37 0.00 0.00 0.00
May 49.91 19.94 29.97 57.58 17.41 0.00 0.00 0.00
June 58.47 25.29 33.18 75.16 11.52 0.00 0.00 0.00
July 62.91 29.90 33.01 83.23 9.72 0.00 0.00 0.00
August 54.83 25.08 29.75 72.60 11.81 0.00 0.00 0.00
September 44.49 21.09 23.40 53.55 20.66 0.00 0.00 0.00
October 31.14 13.88 17.26 28.92 33.09 0.00 0.00 0.00
November 18.63 6.92 11.71 11.15 49.86 0.00 0.00 0.00
December 14.39 6.84 7.55 7.70 70.54 0.00 0.00 0.00
                 
Annual Sum or Average 38.93 17.35 21.58 41.34 36.12 0.00 0.00 0.00
Minimum of Months 14.39 6.84 7.55 7.70 9.72 0.00 0.00 0.00
Maximum of Months 62.91 29.90 33.18 83.23 77.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_MEETINGROOMFLR1_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.55 7.93 11.62 8.56 77.57 0.00 0.00 0.00
February 28.44 13.95 14.49 18.26 62.41 0.00 0.00 0.00
March 34.14 12.72 21.42 26.05 40.94 0.00 0.00 0.00
April 49.77 24.60 25.18 52.00 29.37 0.00 0.00 0.00
May 49.91 19.94 29.97 57.58 17.41 0.00 0.00 0.00
June 58.47 25.29 33.18 75.16 11.52 0.00 0.00 0.00
July 62.91 29.90 33.01 83.23 9.72 0.00 0.00 0.00
August 54.83 25.08 29.75 72.60 11.81 0.00 0.00 0.00
September 44.49 21.09 23.40 53.55 20.66 0.00 0.00 0.00
October 31.14 13.88 17.26 28.92 33.09 0.00 0.00 0.00
November 18.63 6.92 11.71 11.15 49.86 0.00 0.00 0.00
December 14.39 6.84 7.55 7.70 70.54 0.00 0.00 0.00
                 
Annual Sum or Average 38.93 17.35 21.58 41.34 36.12 0.00 0.00 0.00
Minimum of Months 14.39 6.84 7.55 7.70 9.72 0.00 0.00 0.00
Maximum of Months 62.91 29.90 33.18 83.23 77.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_MEETINGROOMFLR1_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.55 7.93 11.62 8.56 77.57 0.00 0.00 0.00
February 28.44 13.95 14.49 18.26 62.41 0.00 0.00 0.00
March 34.14 12.72 21.42 26.05 40.94 0.00 0.00 0.00
April 49.77 24.60 25.18 52.00 29.37 0.00 0.00 0.00
May 49.91 19.94 29.97 57.58 17.41 0.00 0.00 0.00
June 58.47 25.29 33.18 75.16 11.52 0.00 0.00 0.00
July 62.91 29.90 33.01 83.23 9.72 0.00 0.00 0.00
August 54.83 25.08 29.75 72.60 11.81 0.00 0.00 0.00
September 44.49 21.09 23.40 53.55 20.66 0.00 0.00 0.00
October 31.14 13.88 17.26 28.92 33.09 0.00 0.00 0.00
November 18.63 6.92 11.71 11.15 49.86 0.00 0.00 0.00
December 14.39 6.84 7.55 7.70 70.54 0.00 0.00 0.00
                 
Annual Sum or Average 38.93 17.35 21.58 41.34 36.12 0.00 0.00 0.00
Minimum of Months 14.39 6.84 7.55 7.70 9.72 0.00 0.00 0.00
Maximum of Months 62.91 29.90 33.18 83.23 77.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM101_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.55 7.93 11.62 8.69 75.35 0.00 0.00 0.00
February 28.44 13.95 14.49 18.39 60.75 0.00 0.00 0.00
March 34.14 12.72 21.42 25.89 40.14 0.00 0.00 0.00
April 49.77 24.60 25.18 51.51 29.15 0.00 0.00 0.00
May 49.91 19.94 29.97 56.90 17.19 0.00 0.00 0.00
June 58.47 25.29 33.18 73.58 12.01 0.00 0.00 0.00
July 62.91 29.90 33.01 81.09 10.72 0.00 0.00 0.00
August 54.83 25.08 29.75 70.54 12.95 0.00 0.00 0.00
September 44.49 21.09 23.40 52.11 21.65 0.00 0.00 0.00
October 31.14 13.88 17.26 28.12 33.51 0.00 0.00 0.00
November 18.63 6.92 11.71 10.85 49.88 0.00 0.00 0.00
December 14.39 6.84 7.55 7.67 69.30 0.00 0.00 0.00
                 
Annual Sum or Average 38.93 17.35 21.58 40.56 35.93 0.00 0.00 0.00
Minimum of Months 14.39 6.84 7.55 7.67 10.72 0.00 0.00 0.00
Maximum of Months 62.91 29.90 33.18 81.09 75.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM102_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.55 7.93 11.62 8.86 73.89 0.00 0.00 0.00
February 28.44 13.95 14.49 18.66 59.38 0.00 0.00 0.00
March 34.14 12.72 21.42 26.40 38.90 0.00 0.00 0.00
April 49.77 24.60 25.18 52.11 27.92 0.00 0.00 0.00
May 49.91 19.94 29.97 57.78 16.27 0.00 0.00 0.00
June 58.47 25.29 33.18 74.54 11.12 0.00 0.00 0.00
July 62.91 29.90 33.01 82.05 9.86 0.00 0.00 0.00
August 54.83 25.08 29.75 71.44 12.04 0.00 0.00 0.00
September 44.49 21.09 23.40 52.84 20.52 0.00 0.00 0.00
October 31.14 13.88 17.26 28.67 32.23 0.00 0.00 0.00
November 18.63 6.92 11.71 11.13 48.34 0.00 0.00 0.00
December 14.39 6.84 7.55 7.81 67.73 0.00 0.00 0.00
                 
Annual Sum or Average 38.93 17.35 21.58 41.14 34.73 0.00 0.00 0.00
Minimum of Months 14.39 6.84 7.55 7.81 9.86 0.00 0.00 0.00
Maximum of Months 62.91 29.90 33.18 82.05 73.89 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM103_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.55 7.93 11.62 8.92 74.64 1.17 0.00 0.00
February 28.44 13.95 14.49 18.78 59.51 0.17 0.00 0.00
March 34.14 12.72 21.42 26.96 38.05 0.00 0.00 0.00
April 49.77 24.60 25.18 53.08 26.06 0.00 0.00 0.00
May 49.91 19.94 29.97 59.31 14.31 0.00 0.00 0.00
June 58.47 25.29 33.18 76.82 9.00 0.00 0.00 0.00
July 62.91 29.90 33.01 84.59 7.65 0.00 0.00 0.00
August 54.83 25.08 29.75 73.71 9.66 0.00 0.00 0.00
September 44.49 21.09 23.40 54.46 17.78 0.00 0.00 0.00
October 31.14 13.88 17.26 29.46 29.77 0.00 0.00 0.00
November 18.63 6.92 11.71 11.48 46.71 0.00 0.00 0.00
December 14.39 6.84 7.55 7.92 67.68 0.00 0.00 0.00
                 
Annual Sum or Average 38.93 17.35 21.58 42.24 33.28 1.33 0.00 0.00
Minimum of Months 14.39 6.84 7.55 7.92 7.65 0.00 0.00 0.00
Maximum of Months 62.91 29.90 33.18 84.59 74.64 1.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM104_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.72 8.15 11.57 8.14 74.61 0.33 0.00 0.00
February 25.96 11.36 14.60 14.52 58.97 0.00 0.00 0.00
March 35.39 14.01 21.38 27.44 38.08 0.00 0.00 0.00
April 43.42 19.01 24.41 43.20 26.29 0.00 0.00 0.00
May 54.60 23.85 30.75 64.15 14.03 0.00 0.00 0.00
June 60.09 26.18 33.91 78.50 8.84 0.00 0.00 0.00
July 60.72 28.06 32.66 81.17 7.41 0.00 0.00 0.00
August 51.12 21.99 29.12 68.01 9.28 0.00 0.00 0.00
September 45.80 21.70 24.10 55.98 17.43 0.00 0.00 0.00
October 29.04 12.10 16.95 25.65 29.16 0.00 0.00 0.00
November 17.18 5.59 11.60 8.60 47.08 0.00 0.00 0.00
December 13.23 5.65 7.58 5.54 68.13 0.00 0.00 0.00
                 
Annual Sum or Average 38.08 16.49 21.59 40.21 33.16 0.33 0.00 0.00
Minimum of Months 13.23 5.59 7.58 5.54 7.41 0.00 0.00 0.00
Maximum of Months 60.72 28.06 33.91 81.17 74.61 0.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM105_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.72 8.15 11.57 7.58 80.12 0.00 0.00 0.00
February 25.96 11.36 14.60 13.63 63.80 0.00 0.00 0.00
March 35.39 14.01 21.38 25.74 41.64 0.00 0.00 0.00
April 43.42 19.01 24.41 41.52 29.11 0.00 0.00 0.00
May 54.60 23.85 30.75 62.21 15.66 0.00 0.00 0.00
June 60.09 26.18 33.91 76.84 10.04 0.00 0.00 0.00
July 60.72 28.06 32.66 79.68 8.43 0.00 0.00 0.00
August 51.12 21.99 29.12 66.68 10.36 0.00 0.00 0.00
September 45.80 21.70 24.10 54.83 18.85 0.00 0.00 0.00
October 29.04 12.10 16.95 24.49 31.20 0.00 0.00 0.00
November 17.18 5.59 11.60 8.00 50.78 0.00 0.00 0.00
December 13.23 5.65 7.58 5.20 73.31 0.00 0.00 0.00
                 
Annual Sum or Average 38.08 16.49 21.59 39.00 35.98 0.00 0.00 0.00
Minimum of Months 13.23 5.59 7.58 5.20 8.43 0.00 0.00 0.00
Maximum of Months 60.72 28.06 33.91 79.68 80.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_EMPLOYEELOUNGEFLR1_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.72 8.15 11.57 6.77 91.20 0.00 0.00 0.00
February 25.96 11.36 14.60 12.34 74.67 0.00 0.00 0.00
March 35.39 14.01 21.38 22.85 51.36 0.00 0.00 0.00
April 43.42 19.01 24.41 37.97 37.84 0.00 0.00 0.00
May 54.60 23.85 30.75 57.06 21.83 0.00 0.00 0.00
June 60.09 26.18 33.91 71.47 15.56 0.00 0.00 0.00
July 60.72 28.06 32.66 74.39 13.43 0.00 0.00 0.00
August 51.12 21.99 29.12 61.78 15.77 0.00 0.00 0.00
September 45.80 21.70 24.10 50.78 25.96 0.00 0.00 0.00
October 29.04 12.10 16.95 21.31 40.23 0.00 0.00 0.00
November 17.18 5.59 11.60 6.70 61.99 0.00 0.00 0.00
December 13.23 5.65 7.58 4.57 85.04 0.00 0.00 0.00
                 
Annual Sum or Average 38.08 16.49 21.59 35.79 44.43 0.00 0.00 0.00
Minimum of Months 13.23 5.59 7.58 4.57 13.43 0.00 0.00 0.00
Maximum of Months 60.72 28.06 33.91 74.39 91.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_LAUNDRYROOMFLR1_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.72 8.15 11.57 2.53 166.36 738.00 0.00 0.00
February 25.96 11.36 14.60 6.28 146.89 661.00 0.00 0.00
March 35.39 14.01 21.38 13.10 119.40 718.00 0.00 0.00
April 43.42 19.01 24.41 23.66 102.14 682.33 0.00 0.00
May 54.60 23.85 30.75 31.72 75.57 679.67 0.00 0.00
June 60.09 26.18 33.91 40.27 64.54 634.50 0.00 0.00
July 60.72 28.06 32.66 42.20 61.41 655.50 0.00 0.00
August 51.12 21.99 29.12 31.50 65.72 673.17 0.00 0.00
September 45.80 21.70 24.10 29.32 84.66 658.33 0.00 0.00
October 29.04 12.10 16.95 10.49 108.63 712.67 0.00 0.00
November 17.18 5.59 11.60 2.59 137.44 707.17 0.00 0.00
December 13.23 5.65 7.58 1.86 161.01 736.50 0.00 0.00
                 
Annual Sum or Average 38.08 16.49 21.59 19.69 107.61 8256.83 0.00 0.00
Minimum of Months 13.23 5.59 7.58 1.86 61.41 634.50 0.00 0.00
Maximum of Months 60.72 28.06 33.91 42.20 166.36 738.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_LAUNDRYROOMFLR1_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.72 8.15 11.57 2.53 166.36 738.00 0.00 0.00
February 25.96 11.36 14.60 6.28 146.89 661.00 0.00 0.00
March 35.39 14.01 21.38 13.10 119.40 718.00 0.00 0.00
April 43.42 19.01 24.41 23.66 102.14 682.33 0.00 0.00
May 54.60 23.85 30.75 31.72 75.57 679.67 0.00 0.00
June 60.09 26.18 33.91 40.27 64.54 634.50 0.00 0.00
July 60.72 28.06 32.66 42.20 61.41 655.50 0.00 0.00
August 51.12 21.99 29.12 31.50 65.72 673.17 0.00 0.00
September 45.80 21.70 24.10 29.32 84.66 658.33 0.00 0.00
October 29.04 12.10 16.95 10.49 108.63 712.67 0.00 0.00
November 17.18 5.59 11.60 2.59 137.44 707.17 0.00 0.00
December 13.23 5.65 7.58 1.86 161.01 736.50 0.00 0.00
                 
Annual Sum or Average 38.08 16.49 21.59 19.69 107.61 8256.83 0.00 0.00
Minimum of Months 13.23 5.59 7.58 1.86 61.41 634.50 0.00 0.00
Maximum of Months 60.72 28.06 33.91 42.20 166.36 738.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_LAUNDRYROOMFLR1_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.72 8.15 11.57 2.53 166.36 738.00 0.00 0.00
February 25.96 11.36 14.60 6.28 146.89 661.00 0.00 0.00
March 35.39 14.01 21.38 13.10 119.40 718.00 0.00 0.00
April 43.42 19.01 24.41 23.66 102.14 682.33 0.00 0.00
May 54.60 23.85 30.75 31.72 75.57 679.67 0.00 0.00
June 60.09 26.18 33.91 40.27 64.54 634.50 0.00 0.00
July 60.72 28.06 32.66 42.20 61.41 655.50 0.00 0.00
August 51.12 21.99 29.12 31.50 65.72 673.17 0.00 0.00
September 45.80 21.70 24.10 29.32 84.66 658.33 0.00 0.00
October 29.04 12.10 16.95 10.49 108.63 712.67 0.00 0.00
November 17.18 5.59 11.60 2.59 137.44 707.17 0.00 0.00
December 13.23 5.65 7.58 1.86 161.01 736.50 0.00 0.00
                 
Annual Sum or Average 38.08 16.49 21.59 19.69 107.61 8256.83 0.00 0.00
Minimum of Months 13.23 5.59 7.58 1.86 61.41 634.50 0.00 0.00
Maximum of Months 60.72 28.06 33.91 42.20 166.36 738.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_EXERCISECENTERFLR1_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.72 8.15 11.57 8.10 76.31 0.00 0.00 0.00
February 25.96 11.36 14.60 14.47 60.35 0.00 0.00 0.00
March 35.39 14.01 21.38 27.37 39.31 0.00 0.00 0.00
April 43.42 19.01 24.41 43.03 27.55 0.00 0.00 0.00
May 54.60 23.85 30.75 63.53 15.51 0.00 0.00 0.00
June 60.09 26.18 33.91 77.83 10.35 0.00 0.00 0.00
July 60.72 28.06 32.66 80.68 8.83 0.00 0.00 0.00
August 51.12 21.99 29.12 67.70 10.58 0.00 0.00 0.00
September 45.80 21.70 24.10 55.82 18.71 0.00 0.00 0.00
October 29.04 12.10 16.95 25.93 29.95 0.00 0.00 0.00
November 17.18 5.59 11.60 8.67 47.84 0.00 0.00 0.00
December 13.23 5.65 7.58 5.56 69.24 0.00 0.00 0.00
                 
Annual Sum or Average 38.08 16.49 21.59 40.03 34.42 0.00 0.00 0.00
Minimum of Months 13.23 5.59 7.58 5.56 8.83 0.00 0.00 0.00
Maximum of Months 60.72 28.06 33.91 80.68 76.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_FRONTOFFICEFLR1_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.72 8.15 11.57 8.29 74.22 0.00 0.00 0.00
February 25.96 11.36 14.60 14.72 58.66 0.00 0.00 0.00
March 35.39 14.01 21.38 27.60 38.36 0.00 0.00 0.00
April 43.42 19.01 24.41 42.96 27.32 0.00 0.00 0.00
May 54.60 23.85 30.75 63.37 15.70 0.00 0.00 0.00
June 60.09 26.18 33.91 77.55 10.32 0.00 0.00 0.00
July 60.72 28.06 32.66 80.39 8.62 0.00 0.00 0.00
August 51.12 21.99 29.12 67.47 10.52 0.00 0.00 0.00
September 45.80 21.70 24.10 55.50 19.17 0.00 0.00 0.00
October 29.04 12.10 16.95 25.51 30.81 0.00 0.00 0.00
November 17.18 5.59 11.60 8.63 47.38 0.00 0.00 0.00
December 13.23 5.65 7.58 5.66 67.44 0.00 0.00 0.00
                 
Annual Sum or Average 38.08 16.49 21.59 39.94 33.93 0.00 0.00 0.00
Minimum of Months 13.23 5.59 7.58 5.66 8.62 0.00 0.00 0.00
Maximum of Months 60.72 28.06 33.91 80.39 74.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_FRONTOFFICEFLR1_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.72 8.15 11.57 8.29 74.22 0.00 0.00 0.00
February 25.96 11.36 14.60 14.72 58.66 0.00 0.00 0.00
March 35.39 14.01 21.38 27.60 38.36 0.00 0.00 0.00
April 43.42 19.01 24.41 42.96 27.32 0.00 0.00 0.00
May 54.60 23.85 30.75 63.37 15.70 0.00 0.00 0.00
June 60.09 26.18 33.91 77.55 10.32 0.00 0.00 0.00
July 60.72 28.06 32.66 80.39 8.62 0.00 0.00 0.00
August 51.12 21.99 29.12 67.47 10.52 0.00 0.00 0.00
September 45.80 21.70 24.10 55.50 19.17 0.00 0.00 0.00
October 29.04 12.10 16.95 25.51 30.81 0.00 0.00 0.00
November 17.18 5.59 11.60 8.63 47.38 0.00 0.00 0.00
December 13.23 5.65 7.58 5.66 67.44 0.00 0.00 0.00
                 
Annual Sum or Average 38.08 16.49 21.59 39.94 33.93 0.00 0.00 0.00
Minimum of Months 13.23 5.59 7.58 5.66 8.62 0.00 0.00 0.00
Maximum of Months 60.72 28.06 33.91 80.39 74.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_FRONTOFFICEFLR1_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.72 8.15 11.57 8.29 74.22 0.00 0.00 0.00
February 25.96 11.36 14.60 14.72 58.66 0.00 0.00 0.00
March 35.39 14.01 21.38 27.60 38.36 0.00 0.00 0.00
April 43.42 19.01 24.41 42.96 27.32 0.00 0.00 0.00
May 54.60 23.85 30.75 63.37 15.70 0.00 0.00 0.00
June 60.09 26.18 33.91 77.55 10.32 0.00 0.00 0.00
July 60.72 28.06 32.66 80.39 8.62 0.00 0.00 0.00
August 51.12 21.99 29.12 67.47 10.52 0.00 0.00 0.00
September 45.80 21.70 24.10 55.50 19.17 0.00 0.00 0.00
October 29.04 12.10 16.95 25.51 30.81 0.00 0.00 0.00
November 17.18 5.59 11.60 8.63 47.38 0.00 0.00 0.00
December 13.23 5.65 7.58 5.66 67.44 0.00 0.00 0.00
                 
Annual Sum or Average 38.08 16.49 21.59 39.94 33.93 0.00 0.00 0.00
Minimum of Months 13.23 5.59 7.58 5.66 8.62 0.00 0.00 0.00
Maximum of Months 60.72 28.06 33.91 80.39 74.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_FRONTOFFICEFLR1_3_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.72 8.15 11.57 8.29 74.22 0.00 0.00 0.00
February 25.96 11.36 14.60 14.72 58.66 0.00 0.00 0.00
March 35.39 14.01 21.38 27.60 38.36 0.00 0.00 0.00
April 43.42 19.01 24.41 42.96 27.32 0.00 0.00 0.00
May 54.60 23.85 30.75 63.37 15.70 0.00 0.00 0.00
June 60.09 26.18 33.91 77.55 10.32 0.00 0.00 0.00
July 60.72 28.06 32.66 80.39 8.62 0.00 0.00 0.00
August 51.12 21.99 29.12 67.47 10.52 0.00 0.00 0.00
September 45.80 21.70 24.10 55.50 19.17 0.00 0.00 0.00
October 29.04 12.10 16.95 25.51 30.81 0.00 0.00 0.00
November 17.18 5.59 11.60 8.63 47.38 0.00 0.00 0.00
December 13.23 5.65 7.58 5.66 67.44 0.00 0.00 0.00
                 
Annual Sum or Average 38.08 16.49 21.59 39.94 33.93 0.00 0.00 0.00
Minimum of Months 13.23 5.59 7.58 5.66 8.62 0.00 0.00 0.00
Maximum of Months 60.72 28.06 33.91 80.39 74.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_CORRIDORFLR2_2_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 45.49 31.11 14.38 39.00 57.25 0.00 0.00 0.00
February 49.57 33.74 15.82 44.77 46.36 0.00 0.00 0.00
March 41.87 21.77 20.10 39.35 33.88 0.00 0.00 0.00
April 38.43 18.06 20.37 40.93 25.76 0.00 0.00 0.00
May 31.70 8.60 23.10 35.63 15.40 0.00 0.00 0.00
June 30.75 6.25 24.50 39.00 10.02 0.00 0.00 0.00
July 32.68 8.32 24.36 43.59 8.29 0.00 0.00 0.00
August 35.93 12.39 23.53 48.43 10.13 0.00 0.00 0.00
September 43.89 22.85 21.04 55.28 17.18 0.00 0.00 0.00
October 46.80 29.49 17.31 50.84 26.35 0.00 0.00 0.00
November 35.04 21.94 13.11 31.79 38.42 0.00 0.00 0.00
December 37.18 28.12 9.06 34.63 53.30 0.00 0.00 0.00
                 
Annual Sum or Average 39.05 20.14 18.91 41.92 28.44 0.00 0.00 0.00
Minimum of Months 30.75 6.25 9.06 31.79 8.29 0.00 0.00 0.00
Maximum of Months 49.57 33.74 24.50 55.28 57.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_CORRIDORFLR2_15_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 7.32 0.00 7.32 0.00 71.42 0.00 0.00 0.00
February 9.28 0.00 9.28 0.18 58.23 0.00 0.00 0.00
March 13.91 0.00 13.91 3.23 37.68 0.00 0.00 0.00
April 16.10 0.11 15.99 7.79 26.27 0.00 0.00 0.00
May 20.98 0.81 20.16 17.18 14.34 0.00 0.00 0.00
June 24.46 2.21 22.25 27.34 9.38 0.00 0.00 0.00
July 22.95 1.54 21.41 26.98 7.87 0.00 0.00 0.00
August 19.29 0.40 18.89 22.20 9.64 0.00 0.00 0.00
September 14.75 0.01 14.74 12.88 17.68 0.00 0.00 0.00
October 10.96 0.00 10.96 3.65 29.00 0.00 0.00 0.00
November 7.66 0.00 7.66 0.70 44.60 0.00 0.00 0.00
December 4.97 0.00 4.97 0.00 63.36 0.00 0.00 0.00
                 
Annual Sum or Average 14.41 0.43 13.99 10.24 32.33 0.00 0.00 0.00
Minimum of Months 4.97 0.00 4.97 0.00 7.87 0.00 0.00 0.00
Maximum of Months 24.46 2.21 22.25 27.34 71.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM201_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.64 7.97 11.67 9.47 67.82 0.00 0.00 0.00
February 28.57 14.01 14.56 19.45 54.87 0.00 0.00 0.00
March 34.30 12.78 21.52 27.27 36.20 0.00 0.00 0.00
April 50.01 24.71 25.30 52.25 27.08 0.00 0.00 0.00
May 50.14 20.03 30.11 57.02 16.94 0.00 0.00 0.00
June 58.75 25.41 33.34 73.44 11.99 0.00 0.00 0.00
July 63.21 30.04 33.17 81.17 10.65 0.00 0.00 0.00
August 55.09 25.20 29.89 70.94 12.49 0.00 0.00 0.00
September 44.70 21.19 23.51 53.19 19.89 0.00 0.00 0.00
October 31.29 13.95 17.34 29.73 29.83 0.00 0.00 0.00
November 18.72 6.95 11.77 11.97 43.32 0.00 0.00 0.00
December 14.46 6.88 7.58 8.36 61.23 0.00 0.00 0.00
                 
Annual Sum or Average 39.12 17.43 21.68 41.30 32.59 0.00 0.00 0.00
Minimum of Months 14.46 6.88 7.58 8.36 10.65 0.00 0.00 0.00
Maximum of Months 63.21 30.04 33.34 81.17 67.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM202_205_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.64 7.97 11.67 8.85 75.41 0.83 0.00 0.00
February 28.57 14.01 14.56 18.59 60.53 1.00 0.00 0.00
March 34.30 12.78 21.52 26.31 39.28 0.00 0.00 0.00
April 50.01 24.71 25.30 52.13 27.73 0.00 0.00 0.00
May 50.14 20.03 30.11 57.92 15.66 0.00 0.00 0.00
June 58.75 25.41 33.34 75.74 10.05 0.00 0.00 0.00
July 63.21 30.04 33.17 83.77 8.55 0.00 0.00 0.00
August 55.09 25.20 29.89 73.16 10.42 0.00 0.00 0.00
September 44.70 21.19 23.51 54.22 18.35 0.00 0.00 0.00
October 31.29 13.95 17.34 29.34 30.10 0.00 0.00 0.00
November 18.72 6.95 11.77 11.47 46.83 0.00 0.00 0.00
December 14.46 6.88 7.58 7.92 68.01 0.17 0.00 0.00
                 
Annual Sum or Average 39.12 17.43 21.68 41.73 34.12 2.00 0.00 0.00
Minimum of Months 14.46 6.88 7.58 7.92 8.55 0.00 0.00 0.00
Maximum of Months 63.21 30.04 33.34 83.77 75.41 1.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM202_205_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.64 7.97 11.67 8.85 75.41 0.83 0.00 0.00
February 28.57 14.01 14.56 18.59 60.53 1.00 0.00 0.00
March 34.30 12.78 21.52 26.31 39.28 0.00 0.00 0.00
April 50.01 24.71 25.30 52.13 27.73 0.00 0.00 0.00
May 50.14 20.03 30.11 57.92 15.66 0.00 0.00 0.00
June 58.75 25.41 33.34 75.74 10.05 0.00 0.00 0.00
July 63.21 30.04 33.17 83.77 8.55 0.00 0.00 0.00
August 55.09 25.20 29.89 73.16 10.42 0.00 0.00 0.00
September 44.70 21.19 23.51 54.22 18.35 0.00 0.00 0.00
October 31.29 13.95 17.34 29.34 30.10 0.00 0.00 0.00
November 18.72 6.95 11.77 11.47 46.83 0.00 0.00 0.00
December 14.46 6.88 7.58 7.92 68.01 0.17 0.00 0.00
                 
Annual Sum or Average 39.12 17.43 21.68 41.73 34.12 2.00 0.00 0.00
Minimum of Months 14.46 6.88 7.58 7.92 8.55 0.00 0.00 0.00
Maximum of Months 63.21 30.04 33.34 83.77 75.41 1.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM202_205_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.64 7.97 11.67 8.85 75.41 0.83 0.00 0.00
February 28.57 14.01 14.56 18.59 60.53 1.00 0.00 0.00
March 34.30 12.78 21.52 26.31 39.28 0.00 0.00 0.00
April 50.01 24.71 25.30 52.13 27.73 0.00 0.00 0.00
May 50.14 20.03 30.11 57.92 15.66 0.00 0.00 0.00
June 58.75 25.41 33.34 75.74 10.05 0.00 0.00 0.00
July 63.21 30.04 33.17 83.77 8.55 0.00 0.00 0.00
August 55.09 25.20 29.89 73.16 10.42 0.00 0.00 0.00
September 44.70 21.19 23.51 54.22 18.35 0.00 0.00 0.00
October 31.29 13.95 17.34 29.34 30.10 0.00 0.00 0.00
November 18.72 6.95 11.77 11.47 46.83 0.00 0.00 0.00
December 14.46 6.88 7.58 7.92 68.01 0.17 0.00 0.00
                 
Annual Sum or Average 39.12 17.43 21.68 41.73 34.12 2.00 0.00 0.00
Minimum of Months 14.46 6.88 7.58 7.92 8.55 0.00 0.00 0.00
Maximum of Months 63.21 30.04 33.34 83.77 75.41 1.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM202_205_5_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.64 7.97 11.67 8.85 75.41 0.83 0.00 0.00
February 28.57 14.01 14.56 18.59 60.53 1.00 0.00 0.00
March 34.30 12.78 21.52 26.31 39.28 0.00 0.00 0.00
April 50.01 24.71 25.30 52.13 27.73 0.00 0.00 0.00
May 50.14 20.03 30.11 57.92 15.66 0.00 0.00 0.00
June 58.75 25.41 33.34 75.74 10.05 0.00 0.00 0.00
July 63.21 30.04 33.17 83.77 8.55 0.00 0.00 0.00
August 55.09 25.20 29.89 73.16 10.42 0.00 0.00 0.00
September 44.70 21.19 23.51 54.22 18.35 0.00 0.00 0.00
October 31.29 13.95 17.34 29.34 30.10 0.00 0.00 0.00
November 18.72 6.95 11.77 11.47 46.83 0.00 0.00 0.00
December 14.46 6.88 7.58 7.92 68.01 0.17 0.00 0.00
                 
Annual Sum or Average 39.12 17.43 21.68 41.73 34.12 2.00 0.00 0.00
Minimum of Months 14.46 6.88 7.58 7.92 8.55 0.00 0.00 0.00
Maximum of Months 63.21 30.04 33.34 83.77 75.41 1.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM206_208_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.64 7.97 11.67 8.69 76.48 0.17 0.00 0.00
February 28.57 14.01 14.56 18.33 61.53 0.00 0.00 0.00
March 34.30 12.78 21.52 25.94 40.00 0.00 0.00 0.00
April 50.01 24.71 25.30 51.89 28.13 0.00 0.00 0.00
May 50.14 20.03 30.11 57.82 15.72 0.00 0.00 0.00
June 58.75 25.41 33.34 75.75 10.01 0.00 0.00 0.00
July 63.21 30.04 33.17 83.81 8.47 0.00 0.00 0.00
August 55.09 25.20 29.89 73.20 10.35 0.00 0.00 0.00
September 44.70 21.19 23.51 54.19 18.36 0.00 0.00 0.00
October 31.29 13.95 17.34 29.20 30.32 0.00 0.00 0.00
November 18.72 6.95 11.77 11.31 47.54 0.00 0.00 0.00
December 14.46 6.88 7.58 7.78 69.09 0.00 0.00 0.00
                 
Annual Sum or Average 39.12 17.43 21.68 41.61 34.54 0.17 0.00 0.00
Minimum of Months 14.46 6.88 7.58 7.78 8.47 0.00 0.00 0.00
Maximum of Months 63.21 30.04 33.34 83.81 76.48 0.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM206_208_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 40.53 16.44 24.09 17.95 157.75 0.17 0.00 0.00
February 58.96 28.92 30.04 37.85 126.91 0.00 0.00 0.00
March 70.79 26.37 44.42 53.56 82.51 0.00 0.00 0.00
April 103.20 51.00 52.20 107.10 58.02 0.00 0.00 0.00
May 103.48 41.34 62.14 119.35 32.43 0.00 0.00 0.00
June 121.24 52.44 68.79 156.35 20.65 0.00 0.00 0.00
July 130.45 61.99 68.45 172.99 17.47 0.00 0.00 0.00
August 113.69 52.00 61.69 151.08 21.36 0.00 0.00 0.00
September 92.26 43.74 48.52 111.86 37.87 0.00 0.00 0.00
October 64.57 28.78 35.79 60.28 62.54 0.00 0.00 0.00
November 38.63 14.35 24.28 23.36 98.05 0.00 0.00 0.00
December 29.83 14.19 15.65 16.07 142.50 0.00 0.00 0.00
                 
Annual Sum or Average 80.72 35.97 44.75 85.89 71.25 0.17 0.00 0.00
Minimum of Months 29.83 14.19 15.65 16.07 17.47 0.00 0.00 0.00
Maximum of Months 130.45 61.99 68.79 172.99 157.75 0.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM206_208_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.64 7.97 11.67 8.69 76.48 0.17 0.00 0.00
February 28.57 14.01 14.56 18.33 61.53 0.00 0.00 0.00
March 34.30 12.78 21.52 25.94 40.00 0.00 0.00 0.00
April 50.01 24.71 25.30 51.89 28.13 0.00 0.00 0.00
May 50.14 20.03 30.11 57.82 15.72 0.00 0.00 0.00
June 58.75 25.41 33.34 75.75 10.01 0.00 0.00 0.00
July 63.21 30.04 33.17 83.81 8.47 0.00 0.00 0.00
August 55.09 25.20 29.89 73.20 10.35 0.00 0.00 0.00
September 44.70 21.19 23.51 54.19 18.36 0.00 0.00 0.00
October 31.29 13.95 17.34 29.20 30.32 0.00 0.00 0.00
November 18.72 6.95 11.77 11.31 47.54 0.00 0.00 0.00
December 14.46 6.88 7.58 7.78 69.09 0.00 0.00 0.00
                 
Annual Sum or Average 39.12 17.43 21.68 41.61 34.54 0.17 0.00 0.00
Minimum of Months 14.46 6.88 7.58 7.78 8.47 0.00 0.00 0.00
Maximum of Months 63.21 30.04 33.34 83.81 76.48 0.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM209_212_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.64 7.97 11.67 8.64 76.93 0.33 0.00 0.00
February 28.57 14.01 14.56 18.29 61.81 0.33 0.00 0.00
March 34.30 12.78 21.52 25.96 40.07 0.00 0.00 0.00
April 50.01 24.71 25.30 52.10 27.91 0.00 0.00 0.00
May 50.14 20.03 30.11 58.25 15.40 0.00 0.00 0.00
June 58.75 25.41 33.34 76.28 9.66 0.00 0.00 0.00
July 63.21 30.04 33.17 84.35 8.12 0.00 0.00 0.00
August 55.09 25.20 29.89 73.64 10.03 0.00 0.00 0.00
September 44.70 21.19 23.51 54.44 18.11 0.00 0.00 0.00
October 31.29 13.95 17.34 29.24 30.30 0.00 0.00 0.00
November 18.72 6.95 11.77 11.27 47.83 0.00 0.00 0.00
December 14.46 6.88 7.58 7.74 69.58 0.00 0.00 0.00
                 
Annual Sum or Average 39.12 17.43 21.68 41.80 34.52 0.67 0.00 0.00
Minimum of Months 14.46 6.88 7.58 7.74 8.12 0.00 0.00 0.00
Maximum of Months 63.21 30.04 33.34 84.35 76.93 0.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM209_212_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.64 7.97 11.67 8.64 76.93 0.33 0.00 0.00
February 28.57 14.01 14.56 18.29 61.81 0.33 0.00 0.00
March 34.30 12.78 21.52 25.96 40.07 0.00 0.00 0.00
April 50.01 24.71 25.30 52.10 27.91 0.00 0.00 0.00
May 50.14 20.03 30.11 58.25 15.40 0.00 0.00 0.00
June 58.75 25.41 33.34 76.28 9.66 0.00 0.00 0.00
July 63.21 30.04 33.17 84.35 8.12 0.00 0.00 0.00
August 55.09 25.20 29.89 73.64 10.03 0.00 0.00 0.00
September 44.70 21.19 23.51 54.44 18.11 0.00 0.00 0.00
October 31.29 13.95 17.34 29.24 30.30 0.00 0.00 0.00
November 18.72 6.95 11.77 11.27 47.83 0.00 0.00 0.00
December 14.46 6.88 7.58 7.74 69.58 0.00 0.00 0.00
                 
Annual Sum or Average 39.12 17.43 21.68 41.80 34.52 0.67 0.00 0.00
Minimum of Months 14.46 6.88 7.58 7.74 8.12 0.00 0.00 0.00
Maximum of Months 63.21 30.04 33.34 84.35 76.93 0.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM209_212_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.64 7.97 11.67 8.64 76.93 0.33 0.00 0.00
February 28.57 14.01 14.56 18.29 61.81 0.33 0.00 0.00
March 34.30 12.78 21.52 25.96 40.07 0.00 0.00 0.00
April 50.01 24.71 25.30 52.10 27.91 0.00 0.00 0.00
May 50.14 20.03 30.11 58.25 15.40 0.00 0.00 0.00
June 58.75 25.41 33.34 76.28 9.66 0.00 0.00 0.00
July 63.21 30.04 33.17 84.35 8.12 0.00 0.00 0.00
August 55.09 25.20 29.89 73.64 10.03 0.00 0.00 0.00
September 44.70 21.19 23.51 54.44 18.11 0.00 0.00 0.00
October 31.29 13.95 17.34 29.24 30.30 0.00 0.00 0.00
November 18.72 6.95 11.77 11.27 47.83 0.00 0.00 0.00
December 14.46 6.88 7.58 7.74 69.58 0.00 0.00 0.00
                 
Annual Sum or Average 39.12 17.43 21.68 41.80 34.52 0.67 0.00 0.00
Minimum of Months 14.46 6.88 7.58 7.74 8.12 0.00 0.00 0.00
Maximum of Months 63.21 30.04 33.34 84.35 76.93 0.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM209_212_5_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.64 7.97 11.67 8.64 76.93 0.33 0.00 0.00
February 28.57 14.01 14.56 18.29 61.81 0.33 0.00 0.00
March 34.30 12.78 21.52 25.96 40.07 0.00 0.00 0.00
April 50.01 24.71 25.30 52.10 27.91 0.00 0.00 0.00
May 50.14 20.03 30.11 58.25 15.40 0.00 0.00 0.00
June 58.75 25.41 33.34 76.28 9.66 0.00 0.00 0.00
July 63.21 30.04 33.17 84.35 8.12 0.00 0.00 0.00
August 55.09 25.20 29.89 73.64 10.03 0.00 0.00 0.00
September 44.70 21.19 23.51 54.44 18.11 0.00 0.00 0.00
October 31.29 13.95 17.34 29.24 30.30 0.00 0.00 0.00
November 18.72 6.95 11.77 11.27 47.83 0.00 0.00 0.00
December 14.46 6.88 7.58 7.74 69.58 0.00 0.00 0.00
                 
Annual Sum or Average 39.12 17.43 21.68 41.80 34.52 0.67 0.00 0.00
Minimum of Months 14.46 6.88 7.58 7.74 8.12 0.00 0.00 0.00
Maximum of Months 63.21 30.04 33.34 84.35 76.93 0.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM213_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.64 7.97 11.67 8.92 75.05 1.33 0.00 0.00
February 28.57 14.01 14.56 18.73 60.11 0.67 0.00 0.00
March 34.30 12.78 21.52 26.75 38.67 0.00 0.00 0.00
April 50.01 24.71 25.30 52.70 26.79 0.00 0.00 0.00
May 50.14 20.03 30.11 58.73 14.88 0.00 0.00 0.00
June 58.75 25.41 33.34 76.48 9.34 0.00 0.00 0.00
July 63.21 30.04 33.17 84.41 7.89 0.00 0.00 0.00
August 55.09 25.20 29.89 73.70 9.80 0.00 0.00 0.00
September 44.70 21.19 23.51 54.67 17.68 0.00 0.00 0.00
October 31.29 13.95 17.34 29.82 29.42 0.00 0.00 0.00
November 18.72 6.95 11.77 11.71 46.24 1.17 0.00 0.00
December 14.46 6.88 7.58 8.00 67.59 1.33 0.00 0.00
                 
Annual Sum or Average 39.12 17.43 21.68 42.17 33.50 4.50 0.00 0.00
Minimum of Months 14.46 6.88 7.58 8.00 7.89 0.00 0.00 0.00
Maximum of Months 63.21 30.04 33.34 84.41 75.05 1.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM214_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.82 8.19 11.63 7.95 76.46 0.33 0.00 0.00
February 26.09 11.41 14.67 14.19 60.87 0.33 0.00 0.00
March 35.55 14.08 21.48 26.68 39.74 0.00 0.00 0.00
April 43.63 19.10 24.53 42.31 27.88 0.00 0.00 0.00
May 54.86 23.96 30.90 63.04 15.13 0.00 0.00 0.00
June 60.38 26.31 34.07 77.63 9.63 0.00 0.00 0.00
July 61.01 28.19 32.82 80.45 8.09 0.00 0.00 0.00
August 51.36 22.10 29.26 67.45 9.95 0.00 0.00 0.00
September 46.02 21.80 24.22 55.65 18.06 0.00 0.00 0.00
October 29.18 12.15 17.03 25.36 29.84 0.00 0.00 0.00
November 17.27 5.61 11.65 8.46 48.05 0.00 0.00 0.00
December 13.30 5.68 7.62 5.46 69.56 0.00 0.00 0.00
                 
Annual Sum or Average 38.26 16.57 21.69 39.69 34.31 0.67 0.00 0.00
Minimum of Months 13.30 5.61 7.62 5.46 8.09 0.00 0.00 0.00
Maximum of Months 61.01 28.19 34.07 80.45 76.46 0.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM215_218_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.82 8.19 11.63 6.47 94.47 0.00 0.00 0.00
February 26.09 11.41 14.67 11.98 77.48 0.00 0.00 0.00
March 35.55 14.08 21.48 22.38 53.42 0.00 0.00 0.00
April 43.63 19.10 24.53 37.20 39.81 0.00 0.00 0.00
May 54.86 23.96 30.90 55.56 23.32 0.00 0.00 0.00
June 60.38 26.31 34.07 69.69 16.87 0.00 0.00 0.00
July 61.01 28.19 32.82 72.52 14.66 0.00 0.00 0.00
August 51.36 22.10 29.26 60.06 17.05 0.00 0.00 0.00
September 46.02 21.80 24.22 49.63 27.45 0.00 0.00 0.00
October 29.18 12.15 17.03 20.81 41.86 0.00 0.00 0.00
November 17.27 5.61 11.65 6.49 64.03 0.00 0.00 0.00
December 13.30 5.68 7.62 4.44 87.57 0.00 0.00 0.00
                 
Annual Sum or Average 38.26 16.57 21.69 34.89 46.35 0.00 0.00 0.00
Minimum of Months 13.30 5.61 7.62 4.44 14.66 0.00 0.00 0.00
Maximum of Months 61.01 28.19 34.07 72.52 94.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM215_218_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.82 8.19 11.63 6.47 94.47 0.00 0.00 0.00
February 26.09 11.41 14.67 11.98 77.48 0.00 0.00 0.00
March 35.55 14.08 21.48 22.38 53.42 0.00 0.00 0.00
April 43.63 19.10 24.53 37.20 39.81 0.00 0.00 0.00
May 54.86 23.96 30.90 55.56 23.32 0.00 0.00 0.00
June 60.38 26.31 34.07 69.69 16.87 0.00 0.00 0.00
July 61.01 28.19 32.82 72.52 14.66 0.00 0.00 0.00
August 51.36 22.10 29.26 60.06 17.05 0.00 0.00 0.00
September 46.02 21.80 24.22 49.63 27.45 0.00 0.00 0.00
October 29.18 12.15 17.03 20.81 41.86 0.00 0.00 0.00
November 17.27 5.61 11.65 6.49 64.03 0.00 0.00 0.00
December 13.30 5.68 7.62 4.44 87.57 0.00 0.00 0.00
                 
Annual Sum or Average 38.26 16.57 21.69 34.89 46.35 0.00 0.00 0.00
Minimum of Months 13.30 5.61 7.62 4.44 14.66 0.00 0.00 0.00
Maximum of Months 61.01 28.19 34.07 72.52 94.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM215_218_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.82 8.19 11.63 6.47 94.47 0.00 0.00 0.00
February 26.09 11.41 14.67 11.98 77.48 0.00 0.00 0.00
March 35.55 14.08 21.48 22.38 53.42 0.00 0.00 0.00
April 43.63 19.10 24.53 37.20 39.81 0.00 0.00 0.00
May 54.86 23.96 30.90 55.56 23.32 0.00 0.00 0.00
June 60.38 26.31 34.07 69.69 16.87 0.00 0.00 0.00
July 61.01 28.19 32.82 72.52 14.66 0.00 0.00 0.00
August 51.36 22.10 29.26 60.06 17.05 0.00 0.00 0.00
September 46.02 21.80 24.22 49.63 27.45 0.00 0.00 0.00
October 29.18 12.15 17.03 20.81 41.86 0.00 0.00 0.00
November 17.27 5.61 11.65 6.49 64.03 0.00 0.00 0.00
December 13.30 5.68 7.62 4.44 87.57 0.00 0.00 0.00
                 
Annual Sum or Average 38.26 16.57 21.69 34.89 46.35 0.00 0.00 0.00
Minimum of Months 13.30 5.61 7.62 4.44 14.66 0.00 0.00 0.00
Maximum of Months 61.01 28.19 34.07 72.52 94.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM215_218_3_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.82 8.19 11.63 6.47 94.47 0.00 0.00 0.00
February 26.09 11.41 14.67 11.98 77.48 0.00 0.00 0.00
March 35.55 14.08 21.48 22.38 53.42 0.00 0.00 0.00
April 43.63 19.10 24.53 37.20 39.81 0.00 0.00 0.00
May 54.86 23.96 30.90 55.56 23.32 0.00 0.00 0.00
June 60.38 26.31 34.07 69.69 16.87 0.00 0.00 0.00
July 61.01 28.19 32.82 72.52 14.66 0.00 0.00 0.00
August 51.36 22.10 29.26 60.06 17.05 0.00 0.00 0.00
September 46.02 21.80 24.22 49.63 27.45 0.00 0.00 0.00
October 29.18 12.15 17.03 20.81 41.86 0.00 0.00 0.00
November 17.27 5.61 11.65 6.49 64.03 0.00 0.00 0.00
December 13.30 5.68 7.62 4.44 87.57 0.00 0.00 0.00
                 
Annual Sum or Average 38.26 16.57 21.69 34.89 46.35 0.00 0.00 0.00
Minimum of Months 13.30 5.61 7.62 4.44 14.66 0.00 0.00 0.00
Maximum of Months 61.01 28.19 34.07 72.52 94.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM219_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.82 8.19 11.63 6.58 91.57 0.00 0.00 0.00
February 26.09 11.41 14.67 12.18 75.92 0.00 0.00 0.00
March 35.55 14.08 21.48 22.89 50.30 0.00 0.00 0.00
April 43.63 19.10 24.53 37.81 37.27 0.00 0.00 0.00
May 54.86 23.96 30.90 56.39 22.17 0.00 0.00 0.00
June 60.38 26.31 34.07 70.73 15.75 0.00 0.00 0.00
July 61.01 28.19 32.82 73.34 13.92 0.00 0.00 0.00
August 51.36 22.10 29.26 60.81 16.40 0.00 0.00 0.00
September 46.02 21.80 24.22 50.51 25.95 0.00 0.00 0.00
October 29.18 12.15 17.03 21.44 39.17 0.00 0.00 0.00
November 17.27 5.61 11.65 6.81 60.57 0.00 0.00 0.00
December 13.30 5.68 7.62 4.65 83.60 0.00 0.00 0.00
                 
Annual Sum or Average 38.26 16.57 21.69 35.47 44.23 0.00 0.00 0.00
Minimum of Months 13.30 5.61 7.62 4.65 13.92 0.00 0.00 0.00
Maximum of Months 61.01 28.19 34.07 73.34 91.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM220_223_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.82 8.19 11.63 8.05 75.77 0.17 0.00 0.00
February 26.09 11.41 14.67 14.34 60.16 0.00 0.00 0.00
March 35.55 14.08 21.48 26.99 39.16 0.00 0.00 0.00
April 43.63 19.10 24.53 42.70 27.32 0.00 0.00 0.00
May 54.86 23.96 30.90 63.65 14.72 0.00 0.00 0.00
June 60.38 26.31 34.07 78.33 9.23 0.00 0.00 0.00
July 61.01 28.19 32.82 81.21 7.64 0.00 0.00 0.00
August 51.36 22.10 29.26 68.20 9.39 0.00 0.00 0.00
September 46.02 21.80 24.22 56.20 17.46 0.00 0.00 0.00
October 29.18 12.15 17.03 25.76 29.17 0.00 0.00 0.00
November 17.27 5.61 11.65 8.63 47.23 0.00 0.00 0.00
December 13.30 5.68 7.62 5.53 68.73 0.00 0.00 0.00
                 
Annual Sum or Average 38.26 16.57 21.69 40.10 33.71 0.17 0.00 0.00
Minimum of Months 13.30 5.61 7.62 5.53 7.64 0.00 0.00 0.00
Maximum of Months 61.01 28.19 34.07 81.21 75.77 0.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM220_223_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.82 8.19 11.63 8.05 75.77 0.17 0.00 0.00
February 26.09 11.41 14.67 14.34 60.16 0.00 0.00 0.00
March 35.55 14.08 21.48 26.99 39.16 0.00 0.00 0.00
April 43.63 19.10 24.53 42.70 27.32 0.00 0.00 0.00
May 54.86 23.96 30.90 63.65 14.72 0.00 0.00 0.00
June 60.38 26.31 34.07 78.33 9.23 0.00 0.00 0.00
July 61.01 28.19 32.82 81.21 7.64 0.00 0.00 0.00
August 51.36 22.10 29.26 68.20 9.39 0.00 0.00 0.00
September 46.02 21.80 24.22 56.20 17.46 0.00 0.00 0.00
October 29.18 12.15 17.03 25.76 29.17 0.00 0.00 0.00
November 17.27 5.61 11.65 8.63 47.23 0.00 0.00 0.00
December 13.30 5.68 7.62 5.53 68.73 0.00 0.00 0.00
                 
Annual Sum or Average 38.26 16.57 21.69 40.10 33.71 0.17 0.00 0.00
Minimum of Months 13.30 5.61 7.62 5.53 7.64 0.00 0.00 0.00
Maximum of Months 61.01 28.19 34.07 81.21 75.77 0.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM220_223_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.82 8.19 11.63 8.05 75.77 0.17 0.00 0.00
February 26.09 11.41 14.67 14.34 60.16 0.00 0.00 0.00
March 35.55 14.08 21.48 26.99 39.16 0.00 0.00 0.00
April 43.63 19.10 24.53 42.70 27.32 0.00 0.00 0.00
May 54.86 23.96 30.90 63.65 14.72 0.00 0.00 0.00
June 60.38 26.31 34.07 78.33 9.23 0.00 0.00 0.00
July 61.01 28.19 32.82 81.21 7.64 0.00 0.00 0.00
August 51.36 22.10 29.26 68.20 9.39 0.00 0.00 0.00
September 46.02 21.80 24.22 56.20 17.46 0.00 0.00 0.00
October 29.18 12.15 17.03 25.76 29.17 0.00 0.00 0.00
November 17.27 5.61 11.65 8.63 47.23 0.00 0.00 0.00
December 13.30 5.68 7.62 5.53 68.73 0.00 0.00 0.00
                 
Annual Sum or Average 38.26 16.57 21.69 40.10 33.71 0.17 0.00 0.00
Minimum of Months 13.30 5.61 7.62 5.53 7.64 0.00 0.00 0.00
Maximum of Months 61.01 28.19 34.07 81.21 75.77 0.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM220_223_3_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.82 8.19 11.63 8.05 75.77 0.17 0.00 0.00
February 26.09 11.41 14.67 14.34 60.16 0.00 0.00 0.00
March 35.55 14.08 21.48 26.99 39.16 0.00 0.00 0.00
April 43.63 19.10 24.53 42.70 27.32 0.00 0.00 0.00
May 54.86 23.96 30.90 63.65 14.72 0.00 0.00 0.00
June 60.38 26.31 34.07 78.33 9.23 0.00 0.00 0.00
July 61.01 28.19 32.82 81.21 7.64 0.00 0.00 0.00
August 51.36 22.10 29.26 68.20 9.39 0.00 0.00 0.00
September 46.02 21.80 24.22 56.20 17.46 0.00 0.00 0.00
October 29.18 12.15 17.03 25.76 29.17 0.00 0.00 0.00
November 17.27 5.61 11.65 8.63 47.23 0.00 0.00 0.00
December 13.30 5.68 7.62 5.53 68.73 0.00 0.00 0.00
                 
Annual Sum or Average 38.26 16.57 21.69 40.10 33.71 0.17 0.00 0.00
Minimum of Months 13.30 5.61 7.62 5.53 7.64 0.00 0.00 0.00
Maximum of Months 61.01 28.19 34.07 81.21 75.77 0.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM224_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.82 8.19 11.63 8.15 74.47 1.17 0.00 0.00
February 26.09 11.41 14.67 14.54 58.96 0.33 0.00 0.00
March 35.55 14.08 21.48 27.34 38.41 0.00 0.00 0.00
April 43.63 19.10 24.53 42.87 26.91 0.00 0.00 0.00
May 54.86 23.96 30.90 63.53 14.62 0.00 0.00 0.00
June 60.38 26.31 34.07 78.04 9.26 0.00 0.00 0.00
July 61.01 28.19 32.82 80.88 7.71 0.00 0.00 0.00
August 51.36 22.10 29.26 67.89 9.47 0.00 0.00 0.00
September 46.02 21.80 24.22 56.06 17.46 0.00 0.00 0.00
October 29.18 12.15 17.03 25.86 28.94 0.00 0.00 0.00
November 17.27 5.61 11.65 8.73 46.47 0.00 0.00 0.00
December 13.30 5.68 7.62 5.59 67.43 0.17 0.00 0.00
                 
Annual Sum or Average 38.26 16.57 21.69 40.09 33.22 1.67 0.00 0.00
Minimum of Months 13.30 5.61 7.62 5.59 7.71 0.00 0.00 0.00
Maximum of Months 61.01 28.19 34.07 80.88 74.47 1.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_CORRIDORFLR3_2_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 45.49 31.11 14.38 39.44 55.68 0.00 0.00 0.00
February 49.57 33.74 15.82 45.33 44.78 0.00 0.00 0.00
March 41.87 21.77 20.10 40.20 32.15 0.00 0.00 0.00
April 38.43 18.06 20.37 41.73 23.91 0.00 0.00 0.00
May 31.70 8.60 23.10 36.42 14.41 0.00 0.00 0.00
June 30.75 6.25 24.50 39.54 9.41 0.00 0.00 0.00
July 32.68 8.32 24.36 43.98 7.94 0.00 0.00 0.00
August 35.93 12.39 23.53 48.83 9.69 0.00 0.00 0.00
September 43.89 22.85 21.04 55.99 15.96 0.00 0.00 0.00
October 46.80 29.49 17.31 52.18 23.99 0.00 0.00 0.00
November 35.04 21.94 13.11 32.56 36.22 0.00 0.00 0.00
December 37.18 28.12 9.06 35.01 51.58 0.00 0.00 0.00
                 
Annual Sum or Average 39.05 20.14 18.91 42.58 27.06 0.00 0.00 0.00
Minimum of Months 30.75 6.25 9.06 32.56 7.94 0.00 0.00 0.00
Maximum of Months 49.57 33.74 24.50 55.99 55.68 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_CORRIDORFLR3_15_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 7.32 0.00 7.32 0.01 69.30 0.00 0.00 0.00
February 9.28 0.00 9.28 0.26 56.04 0.00 0.00 0.00
March 13.91 0.00 13.91 3.82 35.57 0.00 0.00 0.00
April 16.10 0.11 15.99 8.56 24.27 0.00 0.00 0.00
May 20.98 0.81 20.16 18.15 13.39 0.00 0.00 0.00
June 24.46 2.21 22.25 28.01 8.78 0.00 0.00 0.00
July 22.95 1.54 21.41 27.48 7.52 0.00 0.00 0.00
August 19.29 0.40 18.89 22.71 9.20 0.00 0.00 0.00
September 14.75 0.01 14.74 13.60 16.32 0.00 0.00 0.00
October 10.96 0.00 10.96 4.61 26.11 0.00 0.00 0.00
November 7.66 0.00 7.66 1.00 41.84 0.00 0.00 0.00
December 4.97 0.00 4.97 0.00 61.14 0.00 0.00 0.00
                 
Annual Sum or Average 14.41 0.43 13.99 10.75 30.67 0.00 0.00 0.00
Minimum of Months 4.97 0.00 4.97 0.00 7.52 0.00 0.00 0.00
Maximum of Months 24.46 2.21 22.25 28.01 69.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM301_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.74 65.17 0.00 0.00 0.00
February 28.49 13.97 14.52 19.95 52.06 0.00 0.00 0.00
March 34.21 12.74 21.47 28.25 33.81 0.00 0.00 0.00
April 49.87 24.64 25.23 53.02 25.34 0.00 0.00 0.00
May 50.00 19.98 30.03 57.75 16.28 0.00 0.00 0.00
June 58.58 25.34 33.24 73.81 11.64 0.00 0.00 0.00
July 63.04 29.96 33.08 81.39 10.48 0.00 0.00 0.00
August 54.94 25.13 29.81 71.31 12.19 0.00 0.00 0.00
September 44.58 21.14 23.45 53.98 18.75 0.00 0.00 0.00
October 31.20 13.91 17.29 30.99 27.23 0.00 0.00 0.00
November 18.67 6.93 11.73 12.70 40.07 0.00 0.00 0.00
December 14.42 6.86 7.56 8.66 57.78 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.90 30.80 0.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.66 10.48 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 81.39 65.17 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM302_305_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.52 67.51 0.00 0.00 0.00
February 28.49 13.97 14.52 19.56 54.52 0.00 0.00 0.00
March 34.21 12.74 21.47 27.55 36.00 0.00 0.00 0.00
April 49.87 24.64 25.23 52.41 27.09 0.00 0.00 0.00
May 50.00 19.98 30.03 57.26 17.13 0.00 0.00 0.00
June 58.58 25.34 33.24 73.55 12.19 0.00 0.00 0.00
July 63.04 29.96 33.08 81.16 10.98 0.00 0.00 0.00
August 54.94 25.13 29.81 71.06 12.77 0.00 0.00 0.00
September 44.58 21.14 23.45 53.55 19.72 0.00 0.00 0.00
October 31.20 13.91 17.29 30.44 28.82 0.00 0.00 0.00
November 18.67 6.93 11.73 12.33 42.24 0.00 0.00 0.00
December 14.42 6.86 7.56 8.44 60.54 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.51 32.35 0.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.44 10.98 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 81.16 67.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM302_305_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.52 67.51 0.00 0.00 0.00
February 28.49 13.97 14.52 19.56 54.52 0.00 0.00 0.00
March 34.21 12.74 21.47 27.55 36.00 0.00 0.00 0.00
April 49.87 24.64 25.23 52.41 27.09 0.00 0.00 0.00
May 50.00 19.98 30.03 57.26 17.13 0.00 0.00 0.00
June 58.58 25.34 33.24 73.55 12.19 0.00 0.00 0.00
July 63.04 29.96 33.08 81.16 10.98 0.00 0.00 0.00
August 54.94 25.13 29.81 71.06 12.77 0.00 0.00 0.00
September 44.58 21.14 23.45 53.55 19.72 0.00 0.00 0.00
October 31.20 13.91 17.29 30.44 28.82 0.00 0.00 0.00
November 18.67 6.93 11.73 12.33 42.24 0.00 0.00 0.00
December 14.42 6.86 7.56 8.44 60.54 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.51 32.35 0.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.44 10.98 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 81.16 67.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM302_305_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.52 67.51 0.00 0.00 0.00
February 28.49 13.97 14.52 19.56 54.52 0.00 0.00 0.00
March 34.21 12.74 21.47 27.55 36.00 0.00 0.00 0.00
April 49.87 24.64 25.23 52.41 27.09 0.00 0.00 0.00
May 50.00 19.98 30.03 57.26 17.13 0.00 0.00 0.00
June 58.58 25.34 33.24 73.55 12.19 0.00 0.00 0.00
July 63.04 29.96 33.08 81.16 10.98 0.00 0.00 0.00
August 54.94 25.13 29.81 71.06 12.77 0.00 0.00 0.00
September 44.58 21.14 23.45 53.55 19.72 0.00 0.00 0.00
October 31.20 13.91 17.29 30.44 28.82 0.00 0.00 0.00
November 18.67 6.93 11.73 12.33 42.24 0.00 0.00 0.00
December 14.42 6.86 7.56 8.44 60.54 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.51 32.35 0.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.44 10.98 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 81.16 67.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM302_305_5_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.52 67.51 0.00 0.00 0.00
February 28.49 13.97 14.52 19.56 54.52 0.00 0.00 0.00
March 34.21 12.74 21.47 27.55 36.00 0.00 0.00 0.00
April 49.87 24.64 25.23 52.41 27.09 0.00 0.00 0.00
May 50.00 19.98 30.03 57.26 17.13 0.00 0.00 0.00
June 58.58 25.34 33.24 73.55 12.19 0.00 0.00 0.00
July 63.04 29.96 33.08 81.16 10.98 0.00 0.00 0.00
August 54.94 25.13 29.81 71.06 12.77 0.00 0.00 0.00
September 44.58 21.14 23.45 53.55 19.72 0.00 0.00 0.00
October 31.20 13.91 17.29 30.44 28.82 0.00 0.00 0.00
November 18.67 6.93 11.73 12.33 42.24 0.00 0.00 0.00
December 14.42 6.86 7.56 8.44 60.54 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.51 32.35 0.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.44 10.98 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 81.16 67.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM306_308_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.35 68.81 0.00 0.00 0.00
February 28.49 13.97 14.52 19.27 55.74 0.00 0.00 0.00
March 34.21 12.74 21.47 27.09 36.97 0.00 0.00 0.00
April 49.87 24.64 25.23 52.03 27.69 0.00 0.00 0.00
May 50.00 19.98 30.03 57.03 17.25 0.00 0.00 0.00
June 58.58 25.34 33.24 73.51 12.14 0.00 0.00 0.00
July 63.04 29.96 33.08 81.16 10.87 0.00 0.00 0.00
August 54.94 25.13 29.81 71.03 12.68 0.00 0.00 0.00
September 44.58 21.14 23.45 53.42 19.79 0.00 0.00 0.00
October 31.20 13.91 17.29 30.14 29.32 0.00 0.00 0.00
November 18.67 6.93 11.73 12.11 43.22 0.00 0.00 0.00
December 14.42 6.86 7.56 8.29 61.85 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.31 32.92 0.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.29 10.87 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 81.16 68.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM306_308_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 40.53 16.44 24.09 19.36 142.34 0.00 0.00 0.00
February 58.96 28.92 30.04 39.89 115.31 0.00 0.00 0.00
March 70.79 26.37 44.42 56.08 76.47 0.00 0.00 0.00
April 103.20 51.00 52.20 107.68 57.27 0.00 0.00 0.00
May 103.48 41.34 62.14 118.04 35.69 0.00 0.00 0.00
June 121.24 52.44 68.79 152.13 25.12 0.00 0.00 0.00
July 130.45 61.99 68.45 167.97 22.50 0.00 0.00 0.00
August 113.69 52.00 61.69 147.01 26.24 0.00 0.00 0.00
September 92.26 43.74 48.52 110.56 40.94 0.00 0.00 0.00
October 64.57 28.78 35.79 62.38 60.65 0.00 0.00 0.00
November 38.63 14.35 24.28 25.07 89.39 0.00 0.00 0.00
December 29.83 14.19 15.65 17.17 127.94 0.00 0.00 0.00
                 
Annual Sum or Average 80.72 35.97 44.75 85.50 68.10 0.00 0.00 0.00
Minimum of Months 29.83 14.19 15.65 17.17 22.50 0.00 0.00 0.00
Maximum of Months 130.45 61.99 68.79 167.97 142.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM306_308_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.35 68.81 0.00 0.00 0.00
February 28.49 13.97 14.52 19.27 55.74 0.00 0.00 0.00
March 34.21 12.74 21.47 27.09 36.97 0.00 0.00 0.00
April 49.87 24.64 25.23 52.03 27.69 0.00 0.00 0.00
May 50.00 19.98 30.03 57.03 17.25 0.00 0.00 0.00
June 58.58 25.34 33.24 73.51 12.14 0.00 0.00 0.00
July 63.04 29.96 33.08 81.16 10.87 0.00 0.00 0.00
August 54.94 25.13 29.81 71.03 12.68 0.00 0.00 0.00
September 44.58 21.14 23.45 53.42 19.79 0.00 0.00 0.00
October 31.20 13.91 17.29 30.14 29.32 0.00 0.00 0.00
November 18.67 6.93 11.73 12.11 43.22 0.00 0.00 0.00
December 14.42 6.86 7.56 8.29 61.85 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.31 32.92 0.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.29 10.87 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 81.16 68.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM309_312_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 8.74 75.83 0.50 0.00 0.00
February 28.49 13.97 14.52 18.41 60.88 0.50 0.00 0.00
March 34.21 12.74 21.47 26.19 39.43 0.00 0.00 0.00
April 49.87 24.64 25.23 52.16 27.43 0.00 0.00 0.00
May 50.00 19.98 30.03 58.31 15.26 0.00 0.00 0.00
June 58.58 25.34 33.24 76.27 9.52 0.00 0.00 0.00
July 63.04 29.96 33.08 84.32 8.00 0.00 0.00 0.00
August 54.94 25.13 29.81 73.69 9.85 0.00 0.00 0.00
September 44.58 21.14 23.45 54.67 17.64 0.00 0.00 0.00
October 31.20 13.91 17.29 29.67 29.47 0.00 0.00 0.00
November 18.67 6.93 11.73 11.55 46.60 0.00 0.00 0.00
December 14.42 6.86 7.56 7.85 68.30 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.94 33.89 1.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 7.85 8.00 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 84.32 75.83 0.50 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM309_312_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 8.74 75.83 0.50 0.00 0.00
February 28.49 13.97 14.52 18.41 60.88 0.50 0.00 0.00
March 34.21 12.74 21.47 26.19 39.43 0.00 0.00 0.00
April 49.87 24.64 25.23 52.16 27.43 0.00 0.00 0.00
May 50.00 19.98 30.03 58.31 15.26 0.00 0.00 0.00
June 58.58 25.34 33.24 76.27 9.52 0.00 0.00 0.00
July 63.04 29.96 33.08 84.32 8.00 0.00 0.00 0.00
August 54.94 25.13 29.81 73.69 9.85 0.00 0.00 0.00
September 44.58 21.14 23.45 54.67 17.64 0.00 0.00 0.00
October 31.20 13.91 17.29 29.67 29.47 0.00 0.00 0.00
November 18.67 6.93 11.73 11.55 46.60 0.00 0.00 0.00
December 14.42 6.86 7.56 7.85 68.30 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.94 33.89 1.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 7.85 8.00 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 84.32 75.83 0.50 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM309_312_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 8.74 75.83 0.50 0.00 0.00
February 28.49 13.97 14.52 18.41 60.88 0.50 0.00 0.00
March 34.21 12.74 21.47 26.19 39.43 0.00 0.00 0.00
April 49.87 24.64 25.23 52.16 27.43 0.00 0.00 0.00
May 50.00 19.98 30.03 58.31 15.26 0.00 0.00 0.00
June 58.58 25.34 33.24 76.27 9.52 0.00 0.00 0.00
July 63.04 29.96 33.08 84.32 8.00 0.00 0.00 0.00
August 54.94 25.13 29.81 73.69 9.85 0.00 0.00 0.00
September 44.58 21.14 23.45 54.67 17.64 0.00 0.00 0.00
October 31.20 13.91 17.29 29.67 29.47 0.00 0.00 0.00
November 18.67 6.93 11.73 11.55 46.60 0.00 0.00 0.00
December 14.42 6.86 7.56 7.85 68.30 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.94 33.89 1.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 7.85 8.00 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 84.32 75.83 0.50 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM309_312_5_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 8.74 75.83 0.50 0.00 0.00
February 28.49 13.97 14.52 18.41 60.88 0.50 0.00 0.00
March 34.21 12.74 21.47 26.19 39.43 0.00 0.00 0.00
April 49.87 24.64 25.23 52.16 27.43 0.00 0.00 0.00
May 50.00 19.98 30.03 58.31 15.26 0.00 0.00 0.00
June 58.58 25.34 33.24 76.27 9.52 0.00 0.00 0.00
July 63.04 29.96 33.08 84.32 8.00 0.00 0.00 0.00
August 54.94 25.13 29.81 73.69 9.85 0.00 0.00 0.00
September 44.58 21.14 23.45 54.67 17.64 0.00 0.00 0.00
October 31.20 13.91 17.29 29.67 29.47 0.00 0.00 0.00
November 18.67 6.93 11.73 11.55 46.60 0.00 0.00 0.00
December 14.42 6.86 7.56 7.85 68.30 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.94 33.89 1.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 7.85 8.00 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 84.32 75.83 0.50 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM313_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.51 67.23 0.00 0.00 0.00
February 28.49 13.97 14.52 19.55 54.23 0.00 0.00 0.00
March 34.21 12.74 21.47 27.73 35.37 0.00 0.00 0.00
April 49.87 24.64 25.23 52.87 26.02 0.00 0.00 0.00
May 50.00 19.98 30.03 58.11 16.12 0.00 0.00 0.00
June 58.58 25.34 33.24 74.47 11.22 0.00 0.00 0.00
July 63.04 29.96 33.08 82.01 10.06 0.00 0.00 0.00
August 54.94 25.13 29.81 71.80 11.90 0.00 0.00 0.00
September 44.58 21.14 23.45 54.00 18.94 0.00 0.00 0.00
October 31.20 13.91 17.29 30.63 28.28 0.00 0.00 0.00
November 18.67 6.93 11.73 12.39 41.82 0.00 0.00 0.00
December 14.42 6.86 7.56 8.42 60.35 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.90 31.69 0.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.42 10.06 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 82.01 67.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM314_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.21 73.59 1.17 0.00 0.00
February 26.02 11.38 14.63 14.58 58.44 0.17 0.00 0.00
March 35.46 14.04 21.42 27.43 38.12 0.00 0.00 0.00
April 43.51 19.05 24.46 42.79 26.75 0.00 0.00 0.00
May 54.71 23.89 30.81 63.32 14.71 0.00 0.00 0.00
June 60.21 26.24 33.97 77.70 9.36 0.00 0.00 0.00
July 60.84 28.11 32.73 80.47 7.89 0.00 0.00 0.00
August 51.22 22.04 29.18 67.59 9.66 0.00 0.00 0.00
September 45.89 21.74 24.15 56.01 17.39 0.00 0.00 0.00
October 29.10 12.12 16.98 26.18 28.47 0.00 0.00 0.00
November 17.22 5.60 11.62 8.89 45.55 0.50 0.00 0.00
December 13.26 5.66 7.60 5.63 66.49 0.67 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 40.04 32.92 2.50 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.63 7.89 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 80.47 73.59 1.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM315_318_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 7.75 78.20 0.00 0.00 0.00
February 26.02 11.38 14.63 13.84 62.47 0.00 0.00 0.00
March 35.46 14.04 21.42 26.06 40.96 0.00 0.00 0.00
April 43.51 19.05 24.46 41.69 28.81 0.00 0.00 0.00
May 54.71 23.89 30.81 62.31 15.78 0.00 0.00 0.00
June 60.21 26.24 33.97 76.91 10.14 0.00 0.00 0.00
July 60.84 28.11 32.73 79.77 8.54 0.00 0.00 0.00
August 51.22 22.04 29.18 66.91 10.39 0.00 0.00 0.00
September 45.89 21.74 24.15 55.24 18.49 0.00 0.00 0.00
October 29.10 12.12 16.98 25.06 30.28 0.00 0.00 0.00
November 17.22 5.60 11.62 8.28 49.07 0.00 0.00 0.00
December 13.26 5.66 7.60 5.33 71.16 0.00 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 39.23 35.23 0.00 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.33 8.54 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 79.77 78.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM315_318_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 7.75 78.20 0.00 0.00 0.00
February 26.02 11.38 14.63 13.84 62.47 0.00 0.00 0.00
March 35.46 14.04 21.42 26.06 40.96 0.00 0.00 0.00
April 43.51 19.05 24.46 41.69 28.81 0.00 0.00 0.00
May 54.71 23.89 30.81 62.31 15.78 0.00 0.00 0.00
June 60.21 26.24 33.97 76.91 10.14 0.00 0.00 0.00
July 60.84 28.11 32.73 79.77 8.54 0.00 0.00 0.00
August 51.22 22.04 29.18 66.91 10.39 0.00 0.00 0.00
September 45.89 21.74 24.15 55.24 18.49 0.00 0.00 0.00
October 29.10 12.12 16.98 25.06 30.28 0.00 0.00 0.00
November 17.22 5.60 11.62 8.28 49.07 0.00 0.00 0.00
December 13.26 5.66 7.60 5.33 71.16 0.00 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 39.23 35.23 0.00 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.33 8.54 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 79.77 78.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM315_318_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 7.75 78.20 0.00 0.00 0.00
February 26.02 11.38 14.63 13.84 62.47 0.00 0.00 0.00
March 35.46 14.04 21.42 26.06 40.96 0.00 0.00 0.00
April 43.51 19.05 24.46 41.69 28.81 0.00 0.00 0.00
May 54.71 23.89 30.81 62.31 15.78 0.00 0.00 0.00
June 60.21 26.24 33.97 76.91 10.14 0.00 0.00 0.00
July 60.84 28.11 32.73 79.77 8.54 0.00 0.00 0.00
August 51.22 22.04 29.18 66.91 10.39 0.00 0.00 0.00
September 45.89 21.74 24.15 55.24 18.49 0.00 0.00 0.00
October 29.10 12.12 16.98 25.06 30.28 0.00 0.00 0.00
November 17.22 5.60 11.62 8.28 49.07 0.00 0.00 0.00
December 13.26 5.66 7.60 5.33 71.16 0.00 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 39.23 35.23 0.00 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.33 8.54 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 79.77 78.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM315_318_3_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 7.75 78.20 0.00 0.00 0.00
February 26.02 11.38 14.63 13.84 62.47 0.00 0.00 0.00
March 35.46 14.04 21.42 26.06 40.96 0.00 0.00 0.00
April 43.51 19.05 24.46 41.69 28.81 0.00 0.00 0.00
May 54.71 23.89 30.81 62.31 15.78 0.00 0.00 0.00
June 60.21 26.24 33.97 76.91 10.14 0.00 0.00 0.00
July 60.84 28.11 32.73 79.77 8.54 0.00 0.00 0.00
August 51.22 22.04 29.18 66.91 10.39 0.00 0.00 0.00
September 45.89 21.74 24.15 55.24 18.49 0.00 0.00 0.00
October 29.10 12.12 16.98 25.06 30.28 0.00 0.00 0.00
November 17.22 5.60 11.62 8.28 49.07 0.00 0.00 0.00
December 13.26 5.66 7.60 5.33 71.16 0.00 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 39.23 35.23 0.00 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.33 8.54 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 79.77 78.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM319_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 7.57 79.54 0.00 0.00 0.00
February 26.02 11.38 14.63 13.51 64.57 0.00 0.00 0.00
March 35.46 14.04 21.42 25.36 43.30 0.00 0.00 0.00
April 43.51 19.05 24.46 40.34 31.76 0.00 0.00 0.00
May 54.71 23.89 30.81 59.64 18.82 0.00 0.00 0.00
June 60.21 26.24 33.97 73.46 12.94 0.00 0.00 0.00
July 60.84 28.11 32.73 76.14 11.27 0.00 0.00 0.00
August 51.22 22.04 29.18 63.63 13.38 0.00 0.00 0.00
September 45.89 21.74 24.15 52.91 21.82 0.00 0.00 0.00
October 29.10 12.12 16.98 24.12 33.36 0.00 0.00 0.00
November 17.22 5.60 11.62 7.92 51.42 0.00 0.00 0.00
December 13.26 5.66 7.60 5.20 72.56 0.00 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 37.61 37.77 0.00 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.20 11.27 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 76.14 79.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM320_323_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.10 74.69 0.33 0.00 0.00
February 26.02 11.38 14.63 14.42 59.25 0.33 0.00 0.00
March 35.46 14.04 21.42 27.16 38.57 0.00 0.00 0.00
April 43.51 19.05 24.46 42.80 26.83 0.00 0.00 0.00
May 54.71 23.89 30.81 63.74 14.46 0.00 0.00 0.00
June 60.21 26.24 33.97 78.37 9.01 0.00 0.00 0.00
July 60.84 28.11 32.73 81.23 7.45 0.00 0.00 0.00
August 51.22 22.04 29.18 68.29 9.15 0.00 0.00 0.00
September 45.89 21.74 24.15 56.40 16.99 0.00 0.00 0.00
October 29.10 12.12 16.98 26.13 28.41 0.00 0.00 0.00
November 17.22 5.60 11.62 8.82 46.12 0.00 0.00 0.00
December 13.26 5.66 7.60 5.57 67.53 0.00 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 40.22 33.08 0.67 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.57 7.45 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 81.23 74.69 0.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM320_323_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.10 74.69 0.33 0.00 0.00
February 26.02 11.38 14.63 14.42 59.25 0.33 0.00 0.00
March 35.46 14.04 21.42 27.16 38.57 0.00 0.00 0.00
April 43.51 19.05 24.46 42.80 26.83 0.00 0.00 0.00
May 54.71 23.89 30.81 63.74 14.46 0.00 0.00 0.00
June 60.21 26.24 33.97 78.37 9.01 0.00 0.00 0.00
July 60.84 28.11 32.73 81.23 7.45 0.00 0.00 0.00
August 51.22 22.04 29.18 68.29 9.15 0.00 0.00 0.00
September 45.89 21.74 24.15 56.40 16.99 0.00 0.00 0.00
October 29.10 12.12 16.98 26.13 28.41 0.00 0.00 0.00
November 17.22 5.60 11.62 8.82 46.12 0.00 0.00 0.00
December 13.26 5.66 7.60 5.57 67.53 0.00 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 40.22 33.08 0.67 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.57 7.45 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 81.23 74.69 0.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM320_323_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.10 74.69 0.33 0.00 0.00
February 26.02 11.38 14.63 14.42 59.25 0.33 0.00 0.00
March 35.46 14.04 21.42 27.16 38.57 0.00 0.00 0.00
April 43.51 19.05 24.46 42.80 26.83 0.00 0.00 0.00
May 54.71 23.89 30.81 63.74 14.46 0.00 0.00 0.00
June 60.21 26.24 33.97 78.37 9.01 0.00 0.00 0.00
July 60.84 28.11 32.73 81.23 7.45 0.00 0.00 0.00
August 51.22 22.04 29.18 68.29 9.15 0.00 0.00 0.00
September 45.89 21.74 24.15 56.40 16.99 0.00 0.00 0.00
October 29.10 12.12 16.98 26.13 28.41 0.00 0.00 0.00
November 17.22 5.60 11.62 8.82 46.12 0.00 0.00 0.00
December 13.26 5.66 7.60 5.57 67.53 0.00 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 40.22 33.08 0.67 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.57 7.45 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 81.23 74.69 0.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM320_323_3_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.10 74.69 0.33 0.00 0.00
February 26.02 11.38 14.63 14.42 59.25 0.33 0.00 0.00
March 35.46 14.04 21.42 27.16 38.57 0.00 0.00 0.00
April 43.51 19.05 24.46 42.80 26.83 0.00 0.00 0.00
May 54.71 23.89 30.81 63.74 14.46 0.00 0.00 0.00
June 60.21 26.24 33.97 78.37 9.01 0.00 0.00 0.00
July 60.84 28.11 32.73 81.23 7.45 0.00 0.00 0.00
August 51.22 22.04 29.18 68.29 9.15 0.00 0.00 0.00
September 45.89 21.74 24.15 56.40 16.99 0.00 0.00 0.00
October 29.10 12.12 16.98 26.13 28.41 0.00 0.00 0.00
November 17.22 5.60 11.62 8.82 46.12 0.00 0.00 0.00
December 13.26 5.66 7.60 5.57 67.53 0.00 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 40.22 33.08 0.67 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.57 7.45 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 81.23 74.69 0.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM324_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.61 69.29 0.00 0.00 0.00
February 26.02 11.38 14.63 15.05 55.12 0.00 0.00 0.00
March 35.46 14.04 21.42 27.89 36.62 0.00 0.00 0.00
April 43.51 19.05 24.46 42.83 26.56 0.00 0.00 0.00
May 54.71 23.89 30.81 62.68 15.66 0.00 0.00 0.00
June 60.21 26.24 33.97 76.12 10.53 0.00 0.00 0.00
July 60.84 28.11 32.73 78.72 9.09 0.00 0.00 0.00
August 51.22 22.04 29.18 66.22 10.86 0.00 0.00 0.00
September 45.89 21.74 24.15 55.27 18.42 0.00 0.00 0.00
October 29.10 12.12 16.98 26.42 28.48 0.00 0.00 0.00
November 17.22 5.60 11.62 9.14 43.71 0.00 0.00 0.00
December 13.26 5.66 7.60 5.86 62.69 0.00 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 39.70 32.15 0.00 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.86 9.09 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 78.72 69.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_CORRIDORFLR4_2_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 45.49 31.11 14.38 39.69 54.58 0.00 0.00 0.00
February 49.57 33.74 15.82 45.56 43.70 0.00 0.00 0.00
March 41.87 21.77 20.10 40.33 31.15 0.00 0.00 0.00
April 38.43 18.06 20.37 41.64 22.84 0.00 0.00 0.00
May 31.70 8.60 23.10 36.32 13.39 0.00 0.00 0.00
June 30.75 6.25 24.50 39.34 8.70 0.00 0.00 0.00
July 32.68 8.32 24.36 43.74 7.39 0.00 0.00 0.00
August 35.93 12.39 23.53 48.63 9.01 0.00 0.00 0.00
September 43.89 22.85 21.04 56.01 14.87 0.00 0.00 0.00
October 46.80 29.49 17.31 52.39 22.83 0.00 0.00 0.00
November 35.04 21.94 13.11 32.82 35.01 0.00 0.00 0.00
December 37.18 28.12 9.06 35.21 50.43 0.00 0.00 0.00
                 
Annual Sum or Average 39.05 20.14 18.91 42.62 26.08 0.00 0.00 0.00
Minimum of Months 30.75 6.25 9.06 32.82 7.39 0.00 0.00 0.00
Maximum of Months 49.57 33.74 24.50 56.01 54.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_CORRIDORFLR4_15_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 7.32 0.00 7.32 0.01 67.91 0.00 0.00 0.00
February 9.28 0.00 9.28 0.28 54.69 0.00 0.00 0.00
March 13.91 0.00 13.91 3.88 34.45 0.00 0.00 0.00
April 16.10 0.11 15.99 8.47 23.14 0.00 0.00 0.00
May 20.98 0.81 20.16 18.14 12.43 0.00 0.00 0.00
June 24.46 2.21 22.25 27.92 8.15 0.00 0.00 0.00
July 22.95 1.54 21.41 27.32 7.04 0.00 0.00 0.00
August 19.29 0.40 18.89 22.59 8.57 0.00 0.00 0.00
September 14.75 0.01 14.74 13.61 15.18 0.00 0.00 0.00
October 10.96 0.00 10.96 4.75 24.83 0.00 0.00 0.00
November 7.66 0.00 7.66 1.08 40.41 0.00 0.00 0.00
December 4.97 0.00 4.97 0.00 59.74 0.00 0.00 0.00
                 
Annual Sum or Average 14.41 0.43 13.99 10.73 29.59 0.00 0.00 0.00
Minimum of Months 4.97 0.00 4.97 0.00 7.04 0.00 0.00 0.00
Maximum of Months 24.46 2.21 22.25 27.92 67.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM401_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.29 71.58 0.00 0.00 0.00
February 28.49 13.97 14.52 19.24 56.92 0.00 0.00 0.00
March 34.21 12.74 21.47 27.38 36.41 0.00 0.00 0.00
April 49.87 24.64 25.23 52.57 25.03 0.00 0.00 0.00
May 50.00 19.98 30.03 57.78 14.13 0.00 0.00 0.00
June 58.58 25.34 33.24 75.20 8.86 0.00 0.00 0.00
July 63.04 29.96 33.08 83.11 7.53 0.00 0.00 0.00
August 54.94 25.13 29.81 72.64 9.29 0.00 0.00 0.00
September 44.58 21.14 23.45 54.53 16.32 0.00 0.00 0.00
October 31.20 13.91 17.29 30.68 26.91 0.00 0.00 0.00
November 18.67 6.93 11.73 12.43 43.00 0.17 0.00 0.00
December 14.42 6.86 7.56 8.38 63.97 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 42.05 31.55 0.17 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.38 7.53 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 83.11 71.58 0.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM402_405_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.79 63.79 0.00 0.00 0.00
February 28.49 13.97 14.52 19.89 50.61 0.00 0.00 0.00
March 34.21 12.74 21.47 27.88 32.57 0.00 0.00 0.00
April 49.87 24.64 25.23 52.01 24.35 0.00 0.00 0.00
May 50.00 19.98 30.03 56.40 15.62 0.00 0.00 0.00
June 58.58 25.34 33.24 72.55 11.13 0.00 0.00 0.00
July 63.04 29.96 33.08 80.09 10.08 0.00 0.00 0.00
August 54.94 25.13 29.81 70.00 11.73 0.00 0.00 0.00
September 44.58 21.14 23.45 53.07 17.87 0.00 0.00 0.00
October 31.20 13.91 17.29 30.67 25.79 0.00 0.00 0.00
November 18.67 6.93 11.73 12.71 38.39 0.00 0.00 0.00
December 14.42 6.86 7.56 8.67 56.33 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.25 29.76 0.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.67 10.08 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 80.09 63.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM402_405_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.79 63.79 0.00 0.00 0.00
February 28.49 13.97 14.52 19.89 50.61 0.00 0.00 0.00
March 34.21 12.74 21.47 27.88 32.57 0.00 0.00 0.00
April 49.87 24.64 25.23 52.01 24.35 0.00 0.00 0.00
May 50.00 19.98 30.03 56.40 15.62 0.00 0.00 0.00
June 58.58 25.34 33.24 72.55 11.13 0.00 0.00 0.00
July 63.04 29.96 33.08 80.09 10.08 0.00 0.00 0.00
August 54.94 25.13 29.81 70.00 11.73 0.00 0.00 0.00
September 44.58 21.14 23.45 53.07 17.87 0.00 0.00 0.00
October 31.20 13.91 17.29 30.67 25.79 0.00 0.00 0.00
November 18.67 6.93 11.73 12.71 38.39 0.00 0.00 0.00
December 14.42 6.86 7.56 8.67 56.33 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.25 29.76 0.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.67 10.08 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 80.09 63.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM402_405_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.79 63.79 0.00 0.00 0.00
February 28.49 13.97 14.52 19.89 50.61 0.00 0.00 0.00
March 34.21 12.74 21.47 27.88 32.57 0.00 0.00 0.00
April 49.87 24.64 25.23 52.01 24.35 0.00 0.00 0.00
May 50.00 19.98 30.03 56.40 15.62 0.00 0.00 0.00
June 58.58 25.34 33.24 72.55 11.13 0.00 0.00 0.00
July 63.04 29.96 33.08 80.09 10.08 0.00 0.00 0.00
August 54.94 25.13 29.81 70.00 11.73 0.00 0.00 0.00
September 44.58 21.14 23.45 53.07 17.87 0.00 0.00 0.00
October 31.20 13.91 17.29 30.67 25.79 0.00 0.00 0.00
November 18.67 6.93 11.73 12.71 38.39 0.00 0.00 0.00
December 14.42 6.86 7.56 8.67 56.33 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.25 29.76 0.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.67 10.08 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 80.09 63.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM402_405_5_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.79 63.79 0.00 0.00 0.00
February 28.49 13.97 14.52 19.89 50.61 0.00 0.00 0.00
March 34.21 12.74 21.47 27.88 32.57 0.00 0.00 0.00
April 49.87 24.64 25.23 52.01 24.35 0.00 0.00 0.00
May 50.00 19.98 30.03 56.40 15.62 0.00 0.00 0.00
June 58.58 25.34 33.24 72.55 11.13 0.00 0.00 0.00
July 63.04 29.96 33.08 80.09 10.08 0.00 0.00 0.00
August 54.94 25.13 29.81 70.00 11.73 0.00 0.00 0.00
September 44.58 21.14 23.45 53.07 17.87 0.00 0.00 0.00
October 31.20 13.91 17.29 30.67 25.79 0.00 0.00 0.00
November 18.67 6.93 11.73 12.71 38.39 0.00 0.00 0.00
December 14.42 6.86 7.56 8.67 56.33 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.25 29.76 0.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.67 10.08 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 80.09 63.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM406_408_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.67 64.33 0.00 0.00 0.00
February 28.49 13.97 14.52 19.62 51.33 0.00 0.00 0.00
March 34.21 12.74 21.47 27.41 33.22 0.00 0.00 0.00
April 49.87 24.64 25.23 51.58 24.85 0.00 0.00 0.00
May 50.00 19.98 30.03 56.12 15.76 0.00 0.00 0.00
June 58.58 25.34 33.24 72.41 11.13 0.00 0.00 0.00
July 63.04 29.96 33.08 79.99 10.05 0.00 0.00 0.00
August 54.94 25.13 29.81 69.89 11.72 0.00 0.00 0.00
September 44.58 21.14 23.45 52.87 18.00 0.00 0.00 0.00
October 31.20 13.91 17.29 30.30 26.26 0.00 0.00 0.00
November 18.67 6.93 11.73 12.47 39.01 0.00 0.00 0.00
December 14.42 6.86 7.56 8.55 56.90 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.01 30.12 0.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.55 10.05 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 79.99 64.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM406_408_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.67 64.33 0.00 0.00 0.00
February 28.49 13.97 14.52 19.62 51.33 0.00 0.00 0.00
March 34.21 12.74 21.47 27.41 33.22 0.00 0.00 0.00
April 49.87 24.64 25.23 51.58 24.85 0.00 0.00 0.00
May 50.00 19.98 30.03 56.12 15.76 0.00 0.00 0.00
June 58.58 25.34 33.24 72.41 11.13 0.00 0.00 0.00
July 63.04 29.96 33.08 79.99 10.05 0.00 0.00 0.00
August 54.94 25.13 29.81 69.89 11.72 0.00 0.00 0.00
September 44.58 21.14 23.45 52.87 18.00 0.00 0.00 0.00
October 31.20 13.91 17.29 30.30 26.26 0.00 0.00 0.00
November 18.67 6.93 11.73 12.47 39.01 0.00 0.00 0.00
December 14.42 6.86 7.56 8.55 56.90 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.01 30.12 0.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.55 10.05 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 79.99 64.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM406_408_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 40.53 16.44 24.09 20.02 133.07 0.00 0.00 0.00
February 58.96 28.92 30.04 40.62 106.17 0.00 0.00 0.00
March 70.79 26.37 44.42 56.74 68.71 0.00 0.00 0.00
April 103.20 51.00 52.20 106.76 51.41 0.00 0.00 0.00
May 103.48 41.34 62.14 116.15 32.60 0.00 0.00 0.00
June 121.24 52.44 68.79 149.87 23.02 0.00 0.00 0.00
July 130.45 61.99 68.45 165.54 20.78 0.00 0.00 0.00
August 113.69 52.00 61.69 144.64 24.24 0.00 0.00 0.00
September 92.26 43.74 48.52 109.42 37.23 0.00 0.00 0.00
October 64.57 28.78 35.79 62.72 54.34 0.00 0.00 0.00
November 38.63 14.35 24.28 25.82 80.71 0.00 0.00 0.00
December 29.83 14.19 15.65 17.71 117.72 0.00 0.00 0.00
                 
Annual Sum or Average 80.72 35.97 44.75 84.88 62.30 0.00 0.00 0.00
Minimum of Months 29.83 14.19 15.65 17.71 20.78 0.00 0.00 0.00
Maximum of Months 130.45 61.99 68.79 165.54 133.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM409_412_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 8.93 74.07 0.33 0.00 0.00
February 28.49 13.97 14.52 18.53 59.26 0.50 0.00 0.00
March 34.21 12.74 21.47 26.13 38.18 0.00 0.00 0.00
April 49.87 24.64 25.23 51.66 26.23 0.00 0.00 0.00
May 50.00 19.98 30.03 57.45 14.44 0.00 0.00 0.00
June 58.58 25.34 33.24 75.35 8.84 0.00 0.00 0.00
July 63.04 29.96 33.08 83.39 7.40 0.00 0.00 0.00
August 54.94 25.13 29.81 72.84 9.22 0.00 0.00 0.00
September 44.58 21.14 23.45 54.14 16.73 0.00 0.00 0.00
October 31.20 13.91 17.29 29.52 28.24 0.00 0.00 0.00
November 18.67 6.93 11.73 11.68 45.04 0.00 0.00 0.00
December 14.42 6.86 7.56 8.01 66.53 1.17 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.58 32.73 2.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.01 7.40 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 83.39 74.07 1.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM409_412_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 8.93 74.07 0.33 0.00 0.00
February 28.49 13.97 14.52 18.53 59.26 0.50 0.00 0.00
March 34.21 12.74 21.47 26.13 38.18 0.00 0.00 0.00
April 49.87 24.64 25.23 51.66 26.23 0.00 0.00 0.00
May 50.00 19.98 30.03 57.45 14.44 0.00 0.00 0.00
June 58.58 25.34 33.24 75.35 8.84 0.00 0.00 0.00
July 63.04 29.96 33.08 83.39 7.40 0.00 0.00 0.00
August 54.94 25.13 29.81 72.84 9.22 0.00 0.00 0.00
September 44.58 21.14 23.45 54.14 16.73 0.00 0.00 0.00
October 31.20 13.91 17.29 29.52 28.24 0.00 0.00 0.00
November 18.67 6.93 11.73 11.68 45.04 0.00 0.00 0.00
December 14.42 6.86 7.56 8.01 66.53 1.17 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.58 32.73 2.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.01 7.40 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 83.39 74.07 1.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM409_412_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 8.93 74.07 0.33 0.00 0.00
February 28.49 13.97 14.52 18.53 59.26 0.50 0.00 0.00
March 34.21 12.74 21.47 26.13 38.18 0.00 0.00 0.00
April 49.87 24.64 25.23 51.66 26.23 0.00 0.00 0.00
May 50.00 19.98 30.03 57.45 14.44 0.00 0.00 0.00
June 58.58 25.34 33.24 75.35 8.84 0.00 0.00 0.00
July 63.04 29.96 33.08 83.39 7.40 0.00 0.00 0.00
August 54.94 25.13 29.81 72.84 9.22 0.00 0.00 0.00
September 44.58 21.14 23.45 54.14 16.73 0.00 0.00 0.00
October 31.20 13.91 17.29 29.52 28.24 0.00 0.00 0.00
November 18.67 6.93 11.73 11.68 45.04 0.00 0.00 0.00
December 14.42 6.86 7.56 8.01 66.53 1.17 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.58 32.73 2.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.01 7.40 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 83.39 74.07 1.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM409_412_5_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 8.93 74.07 0.33 0.00 0.00
February 28.49 13.97 14.52 18.53 59.26 0.50 0.00 0.00
March 34.21 12.74 21.47 26.13 38.18 0.00 0.00 0.00
April 49.87 24.64 25.23 51.66 26.23 0.00 0.00 0.00
May 50.00 19.98 30.03 57.45 14.44 0.00 0.00 0.00
June 58.58 25.34 33.24 75.35 8.84 0.00 0.00 0.00
July 63.04 29.96 33.08 83.39 7.40 0.00 0.00 0.00
August 54.94 25.13 29.81 72.84 9.22 0.00 0.00 0.00
September 44.58 21.14 23.45 54.14 16.73 0.00 0.00 0.00
October 31.20 13.91 17.29 29.52 28.24 0.00 0.00 0.00
November 18.67 6.93 11.73 11.68 45.04 0.00 0.00 0.00
December 14.42 6.86 7.56 8.01 66.53 1.17 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.58 32.73 2.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.01 7.40 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 83.39 74.07 1.17 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM413_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.59 7.95 11.64 9.75 64.05 0.00 0.00 0.00
February 28.49 13.97 14.52 19.86 50.83 0.00 0.00 0.00
March 34.21 12.74 21.47 28.10 32.48 0.00 0.00 0.00
April 49.87 24.64 25.23 52.56 23.76 0.00 0.00 0.00
May 50.00 19.98 30.03 57.35 15.04 0.00 0.00 0.00
June 58.58 25.34 33.24 73.45 10.54 0.00 0.00 0.00
July 63.04 29.96 33.08 80.92 9.56 0.00 0.00 0.00
August 54.94 25.13 29.81 70.76 11.27 0.00 0.00 0.00
September 44.58 21.14 23.45 53.58 17.54 0.00 0.00 0.00
October 31.20 13.91 17.29 30.86 25.76 0.00 0.00 0.00
November 18.67 6.93 11.73 12.76 38.47 0.00 0.00 0.00
December 14.42 6.86 7.56 8.64 56.63 0.00 0.00 0.00
                 
Annual Sum or Average 39.01 17.38 21.62 41.66 29.56 0.00 0.00 0.00
Minimum of Months 14.42 6.86 7.56 8.64 9.56 0.00 0.00 0.00
Maximum of Months 63.04 29.96 33.24 80.92 64.05 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM414_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 9.14 64.59 0.00 0.00 0.00
February 26.02 11.38 14.63 15.63 51.44 0.00 0.00 0.00
March 35.46 14.04 21.42 28.43 33.87 0.00 0.00 0.00
April 43.51 19.05 24.46 42.55 24.68 0.00 0.00 0.00
May 54.71 23.89 30.81 61.82 15.05 0.00 0.00 0.00
June 60.21 26.24 33.97 74.74 10.29 0.00 0.00 0.00
July 60.84 28.11 32.73 77.10 9.11 0.00 0.00 0.00
August 51.22 22.04 29.18 64.78 10.85 0.00 0.00 0.00
September 45.89 21.74 24.15 54.55 17.64 0.00 0.00 0.00
October 29.10 12.12 16.98 26.80 26.64 0.00 0.00 0.00
November 17.22 5.60 11.62 9.67 40.02 0.00 0.00 0.00
December 13.26 5.66 7.60 6.26 57.84 0.00 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 39.42 30.07 0.00 0.00 0.00
Minimum of Months 13.26 5.60 7.60 6.26 9.11 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 77.10 64.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM415_418_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.15 73.56 1.00 0.00 0.00
February 26.02 11.38 14.63 14.36 58.45 0.33 0.00 0.00
March 35.46 14.04 21.42 26.75 38.03 0.00 0.00 0.00
April 43.51 19.05 24.46 42.12 26.28 0.00 0.00 0.00
May 54.71 23.89 30.81 62.74 14.07 0.00 0.00 0.00
June 60.21 26.24 33.97 77.28 8.70 0.00 0.00 0.00
July 60.84 28.11 32.73 80.10 7.19 0.00 0.00 0.00
August 51.22 22.04 29.18 67.25 8.91 0.00 0.00 0.00
September 45.89 21.74 24.15 55.66 16.52 0.00 0.00 0.00
October 29.10 12.12 16.98 25.71 27.81 0.00 0.00 0.00
November 17.22 5.60 11.62 8.73 45.35 0.17 0.00 0.00
December 13.26 5.66 7.60 5.59 66.53 0.17 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 39.67 32.50 1.67 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.59 7.19 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 80.10 73.56 1.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM415_418_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.15 73.56 1.00 0.00 0.00
February 26.02 11.38 14.63 14.36 58.45 0.33 0.00 0.00
March 35.46 14.04 21.42 26.75 38.03 0.00 0.00 0.00
April 43.51 19.05 24.46 42.12 26.28 0.00 0.00 0.00
May 54.71 23.89 30.81 62.74 14.07 0.00 0.00 0.00
June 60.21 26.24 33.97 77.28 8.70 0.00 0.00 0.00
July 60.84 28.11 32.73 80.10 7.19 0.00 0.00 0.00
August 51.22 22.04 29.18 67.25 8.91 0.00 0.00 0.00
September 45.89 21.74 24.15 55.66 16.52 0.00 0.00 0.00
October 29.10 12.12 16.98 25.71 27.81 0.00 0.00 0.00
November 17.22 5.60 11.62 8.73 45.35 0.17 0.00 0.00
December 13.26 5.66 7.60 5.59 66.53 0.17 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 39.67 32.50 1.67 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.59 7.19 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 80.10 73.56 1.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM415_418_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.15 73.56 1.00 0.00 0.00
February 26.02 11.38 14.63 14.36 58.45 0.33 0.00 0.00
March 35.46 14.04 21.42 26.75 38.03 0.00 0.00 0.00
April 43.51 19.05 24.46 42.12 26.28 0.00 0.00 0.00
May 54.71 23.89 30.81 62.74 14.07 0.00 0.00 0.00
June 60.21 26.24 33.97 77.28 8.70 0.00 0.00 0.00
July 60.84 28.11 32.73 80.10 7.19 0.00 0.00 0.00
August 51.22 22.04 29.18 67.25 8.91 0.00 0.00 0.00
September 45.89 21.74 24.15 55.66 16.52 0.00 0.00 0.00
October 29.10 12.12 16.98 25.71 27.81 0.00 0.00 0.00
November 17.22 5.60 11.62 8.73 45.35 0.17 0.00 0.00
December 13.26 5.66 7.60 5.59 66.53 0.17 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 39.67 32.50 1.67 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.59 7.19 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 80.10 73.56 1.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM415_418_3_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.15 73.56 1.00 0.00 0.00
February 26.02 11.38 14.63 14.36 58.45 0.33 0.00 0.00
March 35.46 14.04 21.42 26.75 38.03 0.00 0.00 0.00
April 43.51 19.05 24.46 42.12 26.28 0.00 0.00 0.00
May 54.71 23.89 30.81 62.74 14.07 0.00 0.00 0.00
June 60.21 26.24 33.97 77.28 8.70 0.00 0.00 0.00
July 60.84 28.11 32.73 80.10 7.19 0.00 0.00 0.00
August 51.22 22.04 29.18 67.25 8.91 0.00 0.00 0.00
September 45.89 21.74 24.15 55.66 16.52 0.00 0.00 0.00
October 29.10 12.12 16.98 25.71 27.81 0.00 0.00 0.00
November 17.22 5.60 11.62 8.73 45.35 0.17 0.00 0.00
December 13.26 5.66 7.60 5.59 66.53 0.17 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 39.67 32.50 1.67 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.59 7.19 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 80.10 73.56 1.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM419_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.02 74.60 1.33 0.00 0.00
February 26.02 11.38 14.63 14.22 59.31 0.67 0.00 0.00
March 35.46 14.04 21.42 26.61 38.63 0.00 0.00 0.00
April 43.51 19.05 24.46 41.98 26.78 0.00 0.00 0.00
May 54.71 23.89 30.81 62.48 14.43 0.00 0.00 0.00
June 60.21 26.24 33.97 77.09 8.96 0.00 0.00 0.00
July 60.84 28.11 32.73 79.93 7.42 0.00 0.00 0.00
August 51.22 22.04 29.18 67.07 9.19 0.00 0.00 0.00
September 45.89 21.74 24.15 55.52 16.89 0.00 0.00 0.00
October 29.10 12.12 16.98 25.57 28.28 0.00 0.00 0.00
November 17.22 5.60 11.62 8.63 46.07 0.33 0.00 0.00
December 13.26 5.66 7.60 5.52 67.44 0.67 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 39.52 33.04 3.00 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.52 7.42 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 79.93 74.60 1.33 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM420_423_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.18 73.25 1.00 0.00 0.00
February 26.02 11.38 14.63 14.45 58.01 0.33 0.00 0.00
March 35.46 14.04 21.42 27.01 37.62 0.00 0.00 0.00
April 43.51 19.05 24.46 42.41 25.92 0.00 0.00 0.00
May 54.71 23.89 30.81 63.12 13.79 0.00 0.00 0.00
June 60.21 26.24 33.97 77.71 8.45 0.00 0.00 0.00
July 60.84 28.11 32.73 80.54 6.92 0.00 0.00 0.00
August 51.22 22.04 29.18 67.67 8.61 0.00 0.00 0.00
September 45.89 21.74 24.15 55.99 16.19 0.00 0.00 0.00
October 29.10 12.12 16.98 25.98 27.45 0.00 0.00 0.00
November 17.22 5.60 11.62 8.84 44.90 0.17 0.00 0.00
December 13.26 5.66 7.60 5.62 66.12 0.33 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 39.93 32.15 1.83 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.62 6.92 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 80.54 73.25 1.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM420_423_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.18 73.25 1.00 0.00 0.00
February 26.02 11.38 14.63 14.45 58.01 0.33 0.00 0.00
March 35.46 14.04 21.42 27.01 37.62 0.00 0.00 0.00
April 43.51 19.05 24.46 42.41 25.92 0.00 0.00 0.00
May 54.71 23.89 30.81 63.12 13.79 0.00 0.00 0.00
June 60.21 26.24 33.97 77.71 8.45 0.00 0.00 0.00
July 60.84 28.11 32.73 80.54 6.92 0.00 0.00 0.00
August 51.22 22.04 29.18 67.67 8.61 0.00 0.00 0.00
September 45.89 21.74 24.15 55.99 16.19 0.00 0.00 0.00
October 29.10 12.12 16.98 25.98 27.45 0.00 0.00 0.00
November 17.22 5.60 11.62 8.84 44.90 0.17 0.00 0.00
December 13.26 5.66 7.60 5.62 66.12 0.33 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 39.93 32.15 1.83 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.62 6.92 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 80.54 73.25 1.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM420_423_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.18 73.25 1.00 0.00 0.00
February 26.02 11.38 14.63 14.45 58.01 0.33 0.00 0.00
March 35.46 14.04 21.42 27.01 37.62 0.00 0.00 0.00
April 43.51 19.05 24.46 42.41 25.92 0.00 0.00 0.00
May 54.71 23.89 30.81 63.12 13.79 0.00 0.00 0.00
June 60.21 26.24 33.97 77.71 8.45 0.00 0.00 0.00
July 60.84 28.11 32.73 80.54 6.92 0.00 0.00 0.00
August 51.22 22.04 29.18 67.67 8.61 0.00 0.00 0.00
September 45.89 21.74 24.15 55.99 16.19 0.00 0.00 0.00
October 29.10 12.12 16.98 25.98 27.45 0.00 0.00 0.00
November 17.22 5.60 11.62 8.84 44.90 0.17 0.00 0.00
December 13.26 5.66 7.60 5.62 66.12 0.33 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 39.93 32.15 1.83 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.62 6.92 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 80.54 73.25 1.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM420_423_3_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.18 73.25 1.00 0.00 0.00
February 26.02 11.38 14.63 14.45 58.01 0.33 0.00 0.00
March 35.46 14.04 21.42 27.01 37.62 0.00 0.00 0.00
April 43.51 19.05 24.46 42.41 25.92 0.00 0.00 0.00
May 54.71 23.89 30.81 63.12 13.79 0.00 0.00 0.00
June 60.21 26.24 33.97 77.71 8.45 0.00 0.00 0.00
July 60.84 28.11 32.73 80.54 6.92 0.00 0.00 0.00
August 51.22 22.04 29.18 67.67 8.61 0.00 0.00 0.00
September 45.89 21.74 24.15 55.99 16.19 0.00 0.00 0.00
October 29.10 12.12 16.98 25.98 27.45 0.00 0.00 0.00
November 17.22 5.60 11.62 8.84 44.90 0.17 0.00 0.00
December 13.26 5.66 7.60 5.62 66.12 0.33 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 39.93 32.15 1.83 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.62 6.92 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 80.54 73.25 1.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: W_GUESTROOM424_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.76 8.17 11.60 8.35 71.99 1.33 0.00 0.00
February 26.02 11.38 14.63 14.78 56.81 0.00 0.00 0.00
March 35.46 14.04 21.42 27.66 36.89 0.00 0.00 0.00
April 43.51 19.05 24.46 42.79 25.53 0.00 0.00 0.00
May 54.71 23.89 30.81 63.15 13.86 0.00 0.00 0.00
June 60.21 26.24 33.97 77.53 8.63 0.00 0.00 0.00
July 60.84 28.11 32.73 80.32 7.16 0.00 0.00 0.00
August 51.22 22.04 29.18 67.49 8.85 0.00 0.00 0.00
September 45.89 21.74 24.15 56.04 16.29 0.00 0.00 0.00
October 29.10 12.12 16.98 26.44 27.16 0.00 0.00 0.00
November 17.22 5.60 11.62 9.10 43.97 2.33 0.00 0.00
December 13.26 5.66 7.60 5.73 64.76 1.67 0.00 0.00
                 
Annual Sum or Average 38.16 16.53 21.63 40.09 31.71 5.33 0.00 0.00
Minimum of Months 13.26 5.60 7.60 5.73 7.16 0.00 0.00 0.00
Maximum of Months 60.84 28.11 33.97 80.32 71.99 2.33 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: W_CORRIDORFLR1_2_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.249656E+09 0.170727E+09 78928911.76 0.212240E+09 0.321418E+09
February 0.245719E+09 0.167274E+09 78445088.97 0.219252E+09 0.237462E+09
March 0.229782E+09 0.119480E+09 0.110303E+09 0.211588E+09 0.194125E+09
April 0.204122E+09 95931862.17 0.108190E+09 0.213688E+09 0.143600E+09
May 0.173977E+09 47206277.56 0.126771E+09 0.191094E+09 87532946.73
June 0.163324E+09 33192138.83 0.130132E+09 0.201777E+09 56763039.12
July 0.179384E+09 45667742.80 0.133716E+09 0.233343E+09 49191932.43
August 0.197180E+09 68019339.80 0.129161E+09 0.260170E+09 59471351.11
September 0.233115E+09 0.121383E+09 0.111732E+09 0.288708E+09 96501274.32
October 0.256842E+09 0.161841E+09 95000976.95 0.273422E+09 0.152270E+09
November 0.186131E+09 0.116509E+09 69622178.56 0.164978E+09 0.214737E+09
December 0.204036E+09 0.154325E+09 49710052.86 0.187510E+09 0.303141E+09
           
Annual Sum or Average 0.252327E+10 0.130156E+10 0.122171E+10 0.265777E+10 0.191621E+10
Minimum of Months 0.163324E+09 33192138.83 49710052.86 0.164978E+09 49191932.43
Maximum of Months 0.256842E+09 0.170727E+09 0.133716E+09 0.288708E+09 0.321418E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: D_CORRIDORFLR1_16_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 39232728.77 0.00 39232728.77 0.00 0.685661E+09
February 47011315.11 0.00 47011315.11 0.00 0.518911E+09
March 73657307.92 3424.99 73653882.93 6356525.65 0.400222E+09
April 92765031.88 958405.49 91806626.39 35706964.51 0.269308E+09
May 0.123831E+09 6807073.57 0.117024E+09 75746976.78 0.142288E+09
June 0.149965E+09 17308062.50 0.132657E+09 0.157085E+09 89438683.48
July 0.148206E+09 12383569.25 0.135823E+09 0.163151E+09 71563043.03
August 0.116069E+09 3479466.22 0.112590E+09 0.119724E+09 89715919.42
September 85328102.87 86546.35 85241556.52 67286896.39 0.168437E+09
October 60128037.27 0.00 60128037.27 7168284.58 0.298146E+09
November 36771985.94 0.00 36771985.94 547211.87 0.439922E+09
December 27579343.52 0.00 27579343.52 0.00 0.606586E+09
           
Annual Sum or Average 0.100055E+10 41026548.35 0.959519E+09 0.632773E+09 0.378020E+10
Minimum of Months 27579343.52 0.00 27579343.52 0.00 71563043.03
Maximum of Months 0.149965E+09 17308062.50 0.135823E+09 0.163151E+09 0.685661E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_CORRIDORFLR1_20_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 85644603.88 34743038.95 50901564.93 33536720.80 0.369577E+09
February 0.112527E+09 55195802.84 57331541.52 65975598.00 0.273346E+09
March 0.149590E+09 55725553.69 93864176.70 0.101044E+09 0.203929E+09
April 0.211035E+09 0.104286E+09 0.106749E+09 0.207038E+09 0.144009E+09
May 0.218661E+09 87362280.38 0.131299E+09 0.235222E+09 86363879.13
June 0.247917E+09 0.107240E+09 0.140677E+09 0.302695E+09 57573056.11
July 0.275643E+09 0.130997E+09 0.144647E+09 0.348404E+09 50541672.71
August 0.240236E+09 0.109872E+09 0.130363E+09 0.302472E+09 60341942.97
September 0.188656E+09 89438581.83 99217661.33 0.213931E+09 99250994.59
October 0.136448E+09 60822963.81 75624676.36 0.113531E+09 0.163355E+09
November 78988554.69 29338650.17 49649904.53 40954425.95 0.237451E+09
December 63040601.10 29982039.91 33058561.19 30098167.74 0.340172E+09
           
Annual Sum or Average 0.200839E+10 0.895004E+09 0.111338E+10 0.199490E+10 0.208591E+10
Minimum of Months 63040601.10 29338650.17 33058561.19 30098167.74 50541672.71
Maximum of Months 0.275643E+09 0.130997E+09 0.144647E+09 0.348404E+09 0.369577E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_FRONTLOUNGEFLR1_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 94529119.24 38347178.02 56181941.22 42454593.05 0.359336E+09
February 0.124201E+09 60921650.54 63278944.37 81206072.11 0.259119E+09
March 0.165108E+09 61506356.16 0.103601E+09 0.127357E+09 0.186583E+09
April 0.232927E+09 0.115104E+09 0.117823E+09 0.243827E+09 0.129849E+09
May 0.241345E+09 96424982.37 0.144920E+09 0.280621E+09 79564115.16
June 0.273635E+09 0.118365E+09 0.155270E+09 0.354423E+09 51118898.18
July 0.304238E+09 0.144586E+09 0.159652E+09 0.405556E+09 44417655.64
August 0.265157E+09 0.121270E+09 0.143887E+09 0.353593E+09 53674442.88
September 0.208227E+09 98716673.13 0.109510E+09 0.251638E+09 92068167.31
October 0.150602E+09 67132556.38 83469754.37 0.138192E+09 0.154072E+09
November 87182591.40 32382154.09 54800437.30 52269955.17 0.221899E+09
December 69580244.74 33092287.17 36487957.57 37888531.45 0.325589E+09
           
Annual Sum or Average 0.221673E+10 0.987849E+09 0.122888E+10 0.236903E+10 0.195729E+10
Minimum of Months 69580244.74 32382154.09 36487957.57 37888531.45 44417655.64
Maximum of Months 0.304238E+09 0.144586E+09 0.159652E+09 0.405556E+09 0.359336E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_FRONTLOUNGEFLR1_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 94529119.24 38347178.02 56181941.22 42454593.05 0.359336E+09
February 0.124201E+09 60921650.54 63278944.37 81206072.11 0.259119E+09
March 0.165108E+09 61506356.16 0.103601E+09 0.127357E+09 0.186583E+09
April 0.232927E+09 0.115104E+09 0.117823E+09 0.243827E+09 0.129849E+09
May 0.241345E+09 96424982.37 0.144920E+09 0.280621E+09 79564115.16
June 0.273635E+09 0.118365E+09 0.155270E+09 0.354423E+09 51118898.18
July 0.304238E+09 0.144586E+09 0.159652E+09 0.405556E+09 44417655.64
August 0.265157E+09 0.121270E+09 0.143887E+09 0.353593E+09 53674442.88
September 0.208227E+09 98716673.13 0.109510E+09 0.251638E+09 92068167.31
October 0.150602E+09 67132556.38 83469754.37 0.138192E+09 0.154072E+09
November 87182591.40 32382154.09 54800437.30 52269955.17 0.221899E+09
December 69580244.74 33092287.17 36487957.57 37888531.45 0.325589E+09
           
Annual Sum or Average 0.221673E+10 0.987849E+09 0.122888E+10 0.236903E+10 0.195729E+10
Minimum of Months 69580244.74 32382154.09 36487957.57 37888531.45 44417655.64
Maximum of Months 0.304238E+09 0.144586E+09 0.159652E+09 0.405556E+09 0.359336E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_FRONTLOUNGEFLR1_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 94529119.24 38347178.02 56181941.22 42454593.05 0.359336E+09
February 0.124201E+09 60921650.54 63278944.37 81206072.11 0.259119E+09
March 0.165108E+09 61506356.16 0.103601E+09 0.127357E+09 0.186583E+09
April 0.232927E+09 0.115104E+09 0.117823E+09 0.243827E+09 0.129849E+09
May 0.241345E+09 96424982.37 0.144920E+09 0.280621E+09 79564115.16
June 0.273635E+09 0.118365E+09 0.155270E+09 0.354423E+09 51118898.18
July 0.304238E+09 0.144586E+09 0.159652E+09 0.405556E+09 44417655.64
August 0.265157E+09 0.121270E+09 0.143887E+09 0.353593E+09 53674442.88
September 0.208227E+09 98716673.13 0.109510E+09 0.251638E+09 92068167.31
October 0.150602E+09 67132556.38 83469754.37 0.138192E+09 0.154072E+09
November 87182591.40 32382154.09 54800437.30 52269955.17 0.221899E+09
December 69580244.74 33092287.17 36487957.57 37888531.45 0.325589E+09
           
Annual Sum or Average 0.221673E+10 0.987849E+09 0.122888E+10 0.236903E+10 0.195729E+10
Minimum of Months 69580244.74 32382154.09 36487957.57 37888531.45 44417655.64
Maximum of Months 0.304238E+09 0.144586E+09 0.159652E+09 0.405556E+09 0.359336E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_FRONTLOUNGEFLR1_5_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 94529119.24 38347178.02 56181941.22 42454593.05 0.359336E+09
February 0.124201E+09 60921650.54 63278944.37 81206072.11 0.259119E+09
March 0.165108E+09 61506356.16 0.103601E+09 0.127357E+09 0.186583E+09
April 0.232927E+09 0.115104E+09 0.117823E+09 0.243827E+09 0.129849E+09
May 0.241345E+09 96424982.37 0.144920E+09 0.280621E+09 79564115.16
June 0.273635E+09 0.118365E+09 0.155270E+09 0.354423E+09 51118898.18
July 0.304238E+09 0.144586E+09 0.159652E+09 0.405556E+09 44417655.64
August 0.265157E+09 0.121270E+09 0.143887E+09 0.353593E+09 53674442.88
September 0.208227E+09 98716673.13 0.109510E+09 0.251638E+09 92068167.31
October 0.150602E+09 67132556.38 83469754.37 0.138192E+09 0.154072E+09
November 87182591.40 32382154.09 54800437.30 52269955.17 0.221899E+09
December 69580244.74 33092287.17 36487957.57 37888531.45 0.325589E+09
           
Annual Sum or Average 0.221673E+10 0.987849E+09 0.122888E+10 0.236903E+10 0.195729E+10
Minimum of Months 69580244.74 32382154.09 36487957.57 37888531.45 44417655.64
Maximum of Months 0.304238E+09 0.144586E+09 0.159652E+09 0.405556E+09 0.359336E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_FRONTLOUNGEFLR1_5_0_0_0_4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 94529119.24 38347178.02 56181941.22 42454593.05 0.359336E+09
February 0.124201E+09 60921650.54 63278944.37 81206072.11 0.259119E+09
March 0.165108E+09 61506356.16 0.103601E+09 0.127357E+09 0.186583E+09
April 0.232927E+09 0.115104E+09 0.117823E+09 0.243827E+09 0.129849E+09
May 0.241345E+09 96424982.37 0.144920E+09 0.280621E+09 79564115.16
June 0.273635E+09 0.118365E+09 0.155270E+09 0.354423E+09 51118898.18
July 0.304238E+09 0.144586E+09 0.159652E+09 0.405556E+09 44417655.64
August 0.265157E+09 0.121270E+09 0.143887E+09 0.353593E+09 53674442.88
September 0.208227E+09 98716673.13 0.109510E+09 0.251638E+09 92068167.31
October 0.150602E+09 67132556.38 83469754.37 0.138192E+09 0.154072E+09
November 87182591.40 32382154.09 54800437.30 52269955.17 0.221899E+09
December 69580244.74 33092287.17 36487957.57 37888531.45 0.325589E+09
           
Annual Sum or Average 0.221673E+10 0.987849E+09 0.122888E+10 0.236903E+10 0.195729E+10
Minimum of Months 69580244.74 32382154.09 36487957.57 37888531.45 44417655.64
Maximum of Months 0.304238E+09 0.144586E+09 0.159652E+09 0.405556E+09 0.359336E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_MEETINGROOMFLR1_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52356257.99 21239082.36 31117175.62 22922599.09 0.207756E+09
February 68790207.80 33742247.02 35047960.78 44179355.58 0.150984E+09
March 91447208.25 34066093.82 57381114.43 69762583.69 0.109659E+09
April 0.129010E+09 63751874.14 65258030.76 0.134791E+09 76120626.01
May 0.133672E+09 53406228.25 80265809.73 0.154225E+09 46626180.40
June 0.151557E+09 65558120.36 85998544.22 0.194827E+09 29853541.68
July 0.168506E+09 80080812.03 88425495.12 0.222921E+09 26035173.59
August 0.146861E+09 67167104.09 79693904.66 0.194445E+09 31631795.56
September 0.115329E+09 54675510.93 60653827.91 0.138798E+09 53539584.30
October 83413167.70 37182237.85 46230929.85 77458538.34 88621057.90
November 48287282.80 17935276.42 30352006.38 28896213.22 0.129229E+09
December 38537976.92 18328592.85 20209384.08 20611448.18 0.188924E+09
           
Annual Sum or Average 0.122777E+10 0.547133E+09 0.680634E+09 0.130384E+10 0.113898E+10
Minimum of Months 38537976.92 17935276.42 20209384.08 20611448.18 26035173.59
Maximum of Months 0.168506E+09 80080812.03 88425495.12 0.222921E+09 0.207756E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_MEETINGROOMFLR1_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52356257.99 21239082.36 31117175.62 22922599.09 0.207756E+09
February 68790207.80 33742247.02 35047960.78 44179355.58 0.150984E+09
March 91447208.25 34066093.82 57381114.43 69762583.69 0.109659E+09
April 0.129010E+09 63751874.14 65258030.76 0.134791E+09 76120626.01
May 0.133672E+09 53406228.25 80265809.73 0.154225E+09 46626180.40
June 0.151557E+09 65558120.36 85998544.22 0.194827E+09 29853541.68
July 0.168506E+09 80080812.03 88425495.12 0.222921E+09 26035173.59
August 0.146861E+09 67167104.09 79693904.66 0.194445E+09 31631795.56
September 0.115329E+09 54675510.93 60653827.91 0.138798E+09 53539584.30
October 83413167.70 37182237.85 46230929.85 77458538.34 88621057.90
November 48287282.80 17935276.42 30352006.38 28896213.22 0.129229E+09
December 38537976.92 18328592.85 20209384.08 20611448.18 0.188924E+09
           
Annual Sum or Average 0.122777E+10 0.547133E+09 0.680634E+09 0.130384E+10 0.113898E+10
Minimum of Months 38537976.92 17935276.42 20209384.08 20611448.18 26035173.59
Maximum of Months 0.168506E+09 80080812.03 88425495.12 0.222921E+09 0.207756E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_MEETINGROOMFLR1_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52356257.99 21239082.36 31117175.62 22922599.09 0.207756E+09
February 68790207.80 33742247.02 35047960.78 44179355.58 0.150984E+09
March 91447208.25 34066093.82 57381114.43 69762583.69 0.109659E+09
April 0.129010E+09 63751874.14 65258030.76 0.134791E+09 76120626.01
May 0.133672E+09 53406228.25 80265809.73 0.154225E+09 46626180.40
June 0.151557E+09 65558120.36 85998544.22 0.194827E+09 29853541.68
July 0.168506E+09 80080812.03 88425495.12 0.222921E+09 26035173.59
August 0.146861E+09 67167104.09 79693904.66 0.194445E+09 31631795.56
September 0.115329E+09 54675510.93 60653827.91 0.138798E+09 53539584.30
October 83413167.70 37182237.85 46230929.85 77458538.34 88621057.90
November 48287282.80 17935276.42 30352006.38 28896213.22 0.129229E+09
December 38537976.92 18328592.85 20209384.08 20611448.18 0.188924E+09
           
Annual Sum or Average 0.122777E+10 0.547133E+09 0.680634E+09 0.130384E+10 0.113898E+10
Minimum of Months 38537976.92 17935276.42 20209384.08 20611448.18 26035173.59
Maximum of Months 0.168506E+09 80080812.03 88425495.12 0.222921E+09 0.207756E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM101_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52356257.99 21239082.36 31117175.62 23281564.99 0.201823E+09
February 68790207.80 33742247.02 35047960.78 44494105.28 0.146977E+09
March 91447208.25 34066093.82 57381114.43 69341429.26 0.107508E+09
April 0.129010E+09 63751874.14 65258030.76 0.133521E+09 75544362.79
May 0.133672E+09 53406228.25 80265809.73 0.152409E+09 46048439.61
June 0.151557E+09 65558120.36 85998544.22 0.190731E+09 31127931.60
July 0.168506E+09 80080812.03 88425495.12 0.217193E+09 28721042.69
August 0.146861E+09 67167104.09 79693904.66 0.188930E+09 34673735.59
September 0.115329E+09 54675510.93 60653827.91 0.135063E+09 56127063.32
October 83413167.70 37182237.85 46230929.85 75318955.30 89750117.40
November 48287282.80 17935276.42 30352006.38 28111153.04 0.129283E+09
December 38537976.92 18328592.85 20209384.08 20553392.34 0.185612E+09
           
Annual Sum or Average 0.122777E+10 0.547133E+09 0.680634E+09 0.127895E+10 0.113320E+10
Minimum of Months 38537976.92 17935276.42 20209384.08 20553392.34 28721042.69
Maximum of Months 0.168506E+09 80080812.03 88425495.12 0.217193E+09 0.201823E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM102_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52356257.99 21239082.36 31117175.62 23727217.10 0.197901E+09
February 68790207.80 33742247.02 35047960.78 45138454.20 0.143651E+09
March 91447208.25 34066093.82 57381114.43 70715129.47 0.104181E+09
April 0.129010E+09 63751874.14 65258030.76 0.135074E+09 72358819.08
May 0.133672E+09 53406228.25 80265809.73 0.154754E+09 43590376.26
June 0.151557E+09 65558120.36 85998544.22 0.193204E+09 28827332.13
July 0.168506E+09 80080812.03 88425495.12 0.219773E+09 26419267.54
August 0.146861E+09 67167104.09 79693904.66 0.191357E+09 32235422.00
September 0.115329E+09 54675510.93 60653827.91 0.136972E+09 53185658.12
October 83413167.70 37182237.85 46230929.85 76801098.01 86328413.77
November 48287282.80 17935276.42 30352006.38 28851131.90 0.125306E+09
December 38537976.92 18328592.85 20209384.08 20926790.84 0.181413E+09
           
Annual Sum or Average 0.122777E+10 0.547133E+09 0.680634E+09 0.129729E+10 0.109540E+10
Minimum of Months 38537976.92 17935276.42 20209384.08 20926790.84 26419267.54
Maximum of Months 0.168506E+09 80080812.03 88425495.12 0.219773E+09 0.197901E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM103_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52356257.99 21239082.36 31117175.62 23893557.99 0.199904E+09
February 68790207.80 33742247.02 35047960.78 45426400.47 0.143960E+09
March 91447208.25 34066093.82 57381114.43 72218613.26 0.101904E+09
April 0.129010E+09 63751874.14 65258030.76 0.137583E+09 67542101.55
May 0.133672E+09 53406228.25 80265809.73 0.158853E+09 38339854.03
June 0.151557E+09 65558120.36 85998544.22 0.199114E+09 23324421.55
July 0.168506E+09 80080812.03 88425495.12 0.226577E+09 20488787.92
August 0.146861E+09 67167104.09 79693904.66 0.197424E+09 25869152.26
September 0.115329E+09 54675510.93 60653827.91 0.141150E+09 46091826.91
October 83413167.70 37182237.85 46230929.85 78907749.30 79742560.68
November 48287282.80 17935276.42 30352006.38 29765556.05 0.121077E+09
December 38537976.92 18328592.85 20209384.08 21214839.44 0.181279E+09
           
Annual Sum or Average 0.122777E+10 0.547133E+09 0.680634E+09 0.133213E+10 0.104952E+10
Minimum of Months 38537976.92 17935276.42 20209384.08 21214839.44 20488787.92
Maximum of Months 0.168506E+09 80080812.03 88425495.12 0.226577E+09 0.199904E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM104_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52824908.68 21827689.37 30997219.31 21796617.93 0.199841E+09
February 62813624.97 27482740.55 35330884.42 35120632.12 0.142650E+09
March 94780095.50 37523677.75 57256417.75 73505938.32 0.101983E+09
April 0.112557E+09 49284740.22 63272523.73 0.111962E+09 68154776.91
May 0.146238E+09 63874556.19 82363868.15 0.171814E+09 37582319.63
June 0.155759E+09 67870301.44 87888276.14 0.203470E+09 22901705.88
July 0.162641E+09 75151558.34 87489639.30 0.217407E+09 19836649.23
August 0.136908E+09 58909459.56 77998906.28 0.182162E+09 24856480.56
September 0.118711E+09 56236777.04 62473780.16 0.145100E+09 45182991.68
October 77789259.40 32397768.15 45391491.25 68708648.13 78114774.57
November 44542235.29 14478780.22 30063455.07 22292089.67 0.122038E+09
December 35447476.85 15138523.77 20308953.09 14838056.46 0.182489E+09
           
Annual Sum or Average 0.120101E+10 0.520177E+09 0.680835E+09 0.126818E+10 0.104563E+10
Minimum of Months 35447476.85 14478780.22 20308953.09 14838056.46 19836649.23
Maximum of Months 0.162641E+09 75151558.34 87888276.14 0.217407E+09 0.199841E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM105_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52824908.68 21827689.37 30997219.31 20293910.65 0.214605E+09
February 62813624.97 27482740.55 35330884.42 32977753.03 0.154356E+09
March 94780095.50 37523677.75 57256417.75 68949834.06 0.111532E+09
April 0.112557E+09 49284740.22 63272523.73 0.107625E+09 75454117.48
May 0.146238E+09 63874556.19 82363868.15 0.166620E+09 41956054.18
June 0.155759E+09 67870301.44 87888276.14 0.199173E+09 26036408.40
July 0.162641E+09 75151558.34 87489639.30 0.213418E+09 22575560.30
August 0.136908E+09 58909459.56 77998906.28 0.178607E+09 27759182.53
September 0.118711E+09 56236777.04 62473780.16 0.142131E+09 48848956.09
October 77789259.40 32397768.15 45391491.25 65602089.33 83570505.83
November 44542235.29 14478780.22 30063455.07 20725434.91 0.131623E+09
December 35447476.85 15138523.77 20308953.09 13921125.24 0.196361E+09
           
Annual Sum or Average 0.120101E+10 0.520177E+09 0.680835E+09 0.123004E+10 0.113468E+10
Minimum of Months 35447476.85 14478780.22 20308953.09 13921125.24 22575560.30
Maximum of Months 0.162641E+09 75151558.34 87888276.14 0.213418E+09 0.214605E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_EMPLOYEELOUNGEFLR1_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52824908.68 21827689.37 30997219.31 18126170.26 0.244268E+09
February 62813624.97 27482740.55 35330884.42 29859236.78 0.180639E+09
March 94780095.50 37523677.75 57256417.75 61196877.35 0.137573E+09
April 0.112557E+09 49284740.22 63272523.73 98427631.96 98084006.12
May 0.146238E+09 63874556.19 82363868.15 0.152820E+09 58477143.04
June 0.155759E+09 67870301.44 87888276.14 0.185242E+09 40334389.87
July 0.162641E+09 75151558.34 87489639.30 0.199249E+09 35958750.86
August 0.136908E+09 58909459.56 77998906.28 0.165465E+09 42231268.97
September 0.118711E+09 56236777.04 62473780.16 0.131623E+09 67289924.03
October 77789259.40 32397768.15 45391491.25 57071535.02 0.107758E+09
November 44542235.29 14478780.22 30063455.07 17367540.56 0.160690E+09
December 35447476.85 15138523.77 20308953.09 12230476.56 0.227772E+09
           
Annual Sum or Average 0.120101E+10 0.520177E+09 0.680835E+09 0.112868E+10 0.140108E+10
Minimum of Months 35447476.85 14478780.22 20308953.09 12230476.56 35958750.86
Maximum of Months 0.162641E+09 75151558.34 87888276.14 0.199249E+09 0.244268E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_LAUNDRYROOMFLR1_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52824908.68 21827689.37 30997219.31 6775063.45 0.445573E+09
February 62813624.97 27482740.55 35330884.42 15196903.51 0.355354E+09
March 94780095.50 37523677.75 57256417.75 35077069.29 0.319794E+09
April 0.112557E+09 49284740.22 63272523.73 61323504.12 0.264742E+09
May 0.146238E+09 63874556.19 82363868.15 84947570.23 0.202394E+09
June 0.155759E+09 67870301.44 87888276.14 0.104388E+09 0.167276E+09
July 0.162641E+09 75151558.34 87489639.30 0.113037E+09 0.164468E+09
August 0.136908E+09 58909459.56 77998906.28 84361543.15 0.176013E+09
September 0.118711E+09 56236777.04 62473780.16 76006904.43 0.219440E+09
October 77789259.40 32397768.15 45391491.25 28085143.79 0.290948E+09
November 44542235.29 14478780.22 30063455.07 6719535.21 0.356243E+09
December 35447476.85 15138523.77 20308953.09 4974259.31 0.431253E+09
           
Annual Sum or Average 0.120101E+10 0.520177E+09 0.680835E+09 0.620892E+09 0.339350E+10
Minimum of Months 35447476.85 14478780.22 20308953.09 4974259.31 0.164468E+09
Maximum of Months 0.162641E+09 75151558.34 87888276.14 0.113037E+09 0.445573E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_LAUNDRYROOMFLR1_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52824908.68 21827689.37 30997219.31 6775063.45 0.445573E+09
February 62813624.97 27482740.55 35330884.42 15196903.51 0.355354E+09
March 94780095.50 37523677.75 57256417.75 35077069.29 0.319794E+09
April 0.112557E+09 49284740.22 63272523.73 61323504.12 0.264742E+09
May 0.146238E+09 63874556.19 82363868.15 84947570.23 0.202394E+09
June 0.155759E+09 67870301.44 87888276.14 0.104388E+09 0.167276E+09
July 0.162641E+09 75151558.34 87489639.30 0.113037E+09 0.164468E+09
August 0.136908E+09 58909459.56 77998906.28 84361543.15 0.176013E+09
September 0.118711E+09 56236777.04 62473780.16 76006904.43 0.219440E+09
October 77789259.40 32397768.15 45391491.25 28085143.79 0.290948E+09
November 44542235.29 14478780.22 30063455.07 6719535.21 0.356243E+09
December 35447476.85 15138523.77 20308953.09 4974259.31 0.431253E+09
           
Annual Sum or Average 0.120101E+10 0.520177E+09 0.680835E+09 0.620892E+09 0.339350E+10
Minimum of Months 35447476.85 14478780.22 20308953.09 4974259.31 0.164468E+09
Maximum of Months 0.162641E+09 75151558.34 87888276.14 0.113037E+09 0.445573E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_LAUNDRYROOMFLR1_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52824908.68 21827689.37 30997219.31 6775063.45 0.445573E+09
February 62813624.97 27482740.55 35330884.42 15196903.51 0.355354E+09
March 94780095.50 37523677.75 57256417.75 35077069.29 0.319794E+09
April 0.112557E+09 49284740.22 63272523.73 61323504.12 0.264742E+09
May 0.146238E+09 63874556.19 82363868.15 84947570.23 0.202394E+09
June 0.155759E+09 67870301.44 87888276.14 0.104388E+09 0.167276E+09
July 0.162641E+09 75151558.34 87489639.30 0.113037E+09 0.164468E+09
August 0.136908E+09 58909459.56 77998906.28 84361543.15 0.176013E+09
September 0.118711E+09 56236777.04 62473780.16 76006904.43 0.219440E+09
October 77789259.40 32397768.15 45391491.25 28085143.79 0.290948E+09
November 44542235.29 14478780.22 30063455.07 6719535.21 0.356243E+09
December 35447476.85 15138523.77 20308953.09 4974259.31 0.431253E+09
           
Annual Sum or Average 0.120101E+10 0.520177E+09 0.680835E+09 0.620892E+09 0.339350E+10
Minimum of Months 35447476.85 14478780.22 20308953.09 4974259.31 0.164468E+09
Maximum of Months 0.162641E+09 75151558.34 87888276.14 0.113037E+09 0.445573E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_EXERCISECENTERFLR1_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52824908.68 21827689.37 30997219.31 21683667.78 0.204401E+09
February 62813624.97 27482740.55 35330884.42 35006265.88 0.145997E+09
March 94780095.50 37523677.75 57256417.75 73305167.31 0.105281E+09
April 0.112557E+09 49284740.22 63272523.73 0.111534E+09 71415648.62
May 0.146238E+09 63874556.19 82363868.15 0.170168E+09 41553950.68
June 0.155759E+09 67870301.44 87888276.14 0.201728E+09 26830870.76
July 0.162641E+09 75151558.34 87489639.30 0.216084E+09 23648128.62
August 0.136908E+09 58909459.56 77998906.28 0.181325E+09 28343729.80
September 0.118711E+09 56236777.04 62473780.16 0.144692E+09 48483654.72
October 77789259.40 32397768.15 45391491.25 69448040.30 80230522.53
November 44542235.29 14478780.22 30063455.07 22461148.72 0.123995E+09
December 35447476.85 15138523.77 20308953.09 14891832.64 0.185445E+09
           
Annual Sum or Average 0.120101E+10 0.520177E+09 0.680835E+09 0.126233E+10 0.108562E+10
Minimum of Months 35447476.85 14478780.22 20308953.09 14891832.64 23648128.62
Maximum of Months 0.162641E+09 75151558.34 87888276.14 0.216084E+09 0.204401E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_FRONTOFFICEFLR1_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52824908.68 21827689.37 30997219.31 22214077.72 0.198796E+09
February 62813624.97 27482740.55 35330884.42 35607517.64 0.141918E+09
March 94780095.50 37523677.75 57256417.75 73924389.64 0.102744E+09
April 0.112557E+09 49284740.22 63272523.73 0.111351E+09 70801070.26
May 0.146238E+09 63874556.19 82363868.15 0.169743E+09 42060804.67
June 0.155759E+09 67870301.44 87888276.14 0.201001E+09 26741283.03
July 0.162641E+09 75151558.34 87489639.30 0.215311E+09 23075103.47
August 0.136908E+09 58909459.56 77998906.28 0.180699E+09 28176276.92
September 0.118711E+09 56236777.04 62473780.16 0.143856E+09 49685634.57
October 77789259.40 32397768.15 45391491.25 68326502.39 82516617.59
November 44542235.29 14478780.22 30063455.07 22377668.78 0.122805E+09
December 35447476.85 15138523.77 20308953.09 15162620.42 0.180642E+09
           
Annual Sum or Average 0.120101E+10 0.520177E+09 0.680835E+09 0.125957E+10 0.106996E+10
Minimum of Months 35447476.85 14478780.22 20308953.09 15162620.42 23075103.47
Maximum of Months 0.162641E+09 75151558.34 87888276.14 0.215311E+09 0.198796E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_FRONTOFFICEFLR1_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52824908.68 21827689.37 30997219.31 22214077.72 0.198796E+09
February 62813624.97 27482740.55 35330884.42 35607517.64 0.141918E+09
March 94780095.50 37523677.75 57256417.75 73924389.64 0.102744E+09
April 0.112557E+09 49284740.22 63272523.73 0.111351E+09 70801070.26
May 0.146238E+09 63874556.19 82363868.15 0.169743E+09 42060804.67
June 0.155759E+09 67870301.44 87888276.14 0.201001E+09 26741283.03
July 0.162641E+09 75151558.34 87489639.30 0.215311E+09 23075103.47
August 0.136908E+09 58909459.56 77998906.28 0.180699E+09 28176276.92
September 0.118711E+09 56236777.04 62473780.16 0.143856E+09 49685634.57
October 77789259.40 32397768.15 45391491.25 68326502.39 82516617.59
November 44542235.29 14478780.22 30063455.07 22377668.78 0.122805E+09
December 35447476.85 15138523.77 20308953.09 15162620.42 0.180642E+09
           
Annual Sum or Average 0.120101E+10 0.520177E+09 0.680835E+09 0.125957E+10 0.106996E+10
Minimum of Months 35447476.85 14478780.22 20308953.09 15162620.42 23075103.47
Maximum of Months 0.162641E+09 75151558.34 87888276.14 0.215311E+09 0.198796E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_FRONTOFFICEFLR1_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52824908.68 21827689.37 30997219.31 22214077.72 0.198796E+09
February 62813624.97 27482740.55 35330884.42 35607517.64 0.141918E+09
March 94780095.50 37523677.75 57256417.75 73924389.64 0.102744E+09
April 0.112557E+09 49284740.22 63272523.73 0.111351E+09 70801070.26
May 0.146238E+09 63874556.19 82363868.15 0.169743E+09 42060804.67
June 0.155759E+09 67870301.44 87888276.14 0.201001E+09 26741283.03
July 0.162641E+09 75151558.34 87489639.30 0.215311E+09 23075103.47
August 0.136908E+09 58909459.56 77998906.28 0.180699E+09 28176276.92
September 0.118711E+09 56236777.04 62473780.16 0.143856E+09 49685634.57
October 77789259.40 32397768.15 45391491.25 68326502.39 82516617.59
November 44542235.29 14478780.22 30063455.07 22377668.78 0.122805E+09
December 35447476.85 15138523.77 20308953.09 15162620.42 0.180642E+09
           
Annual Sum or Average 0.120101E+10 0.520177E+09 0.680835E+09 0.125957E+10 0.106996E+10
Minimum of Months 35447476.85 14478780.22 20308953.09 15162620.42 23075103.47
Maximum of Months 0.162641E+09 75151558.34 87888276.14 0.215311E+09 0.198796E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_FRONTOFFICEFLR1_3_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52824908.68 21827689.37 30997219.31 22214077.72 0.198796E+09
February 62813624.97 27482740.55 35330884.42 35607517.64 0.141918E+09
March 94780095.50 37523677.75 57256417.75 73924389.64 0.102744E+09
April 0.112557E+09 49284740.22 63272523.73 0.111351E+09 70801070.26
May 0.146238E+09 63874556.19 82363868.15 0.169743E+09 42060804.67
June 0.155759E+09 67870301.44 87888276.14 0.201001E+09 26741283.03
July 0.162641E+09 75151558.34 87489639.30 0.215311E+09 23075103.47
August 0.136908E+09 58909459.56 77998906.28 0.180699E+09 28176276.92
September 0.118711E+09 56236777.04 62473780.16 0.143856E+09 49685634.57
October 77789259.40 32397768.15 45391491.25 68326502.39 82516617.59
November 44542235.29 14478780.22 30063455.07 22377668.78 0.122805E+09
December 35447476.85 15138523.77 20308953.09 15162620.42 0.180642E+09
           
Annual Sum or Average 0.120101E+10 0.520177E+09 0.680835E+09 0.125957E+10 0.106996E+10
Minimum of Months 35447476.85 14478780.22 20308953.09 15162620.42 23075103.47
Maximum of Months 0.162641E+09 75151558.34 87888276.14 0.215311E+09 0.198796E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_CORRIDORFLR2_2_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.121837E+09 83318398.15 38518973.27 0.104464E+09 0.153330E+09
February 0.119916E+09 81633068.74 38282857.55 0.108310E+09 0.112159E+09
March 0.112139E+09 58308630.86 53830002.05 0.105402E+09 90731235.59
April 99615629.23 46816771.60 52798857.63 0.106100E+09 66763593.64
May 84904501.91 23037658.86 61866843.05 95424189.10 41246694.33
June 79705522.24 16198463.65 63507058.59 0.101077E+09 25981398.44
July 87542987.82 22286821.46 65256166.36 0.116747E+09 22207266.42
August 96228096.39 33194872.11 63033224.28 0.129725E+09 27126226.39
September 0.113765E+09 59237649.66 54527402.55 0.143296E+09 44527039.65
October 0.125344E+09 78981980.71 46362479.99 0.136163E+09 70575420.84
November 90835706.31 56858615.09 33977091.22 82396671.75 99595265.23
December 99573649.27 75314095.27 24259554.00 92762732.19 0.142751E+09
           
Annual Sum or Average 0.123141E+10 0.635187E+09 0.596221E+09 0.132187E+10 0.896994E+09
Minimum of Months 79705522.24 16198463.65 24259554.00 82396671.75 22207266.42
Maximum of Months 0.125344E+09 83318398.15 65256166.36 0.143296E+09 0.153330E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_CORRIDORFLR2_15_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 19610029.31 0.00 19610029.31 3519.56 0.191304E+09
February 22455712.01 0.00 22455712.01 427382.35 0.140869E+09
March 37266677.14 1010.90 37265666.24 8639712.13 0.100914E+09
April 41723531.10 283946.25 41439584.85 20204449.82 68085655.98
May 56182114.19 2175662.54 54006451.65 46012772.67 38397196.04
June 63402171.80 5727469.14 57674702.65 70865880.26 24304112.70
July 61461961.32 4123825.70 57338135.62 72249913.42 21082044.47
August 51661636.28 1076297.01 50585339.27 59449846.63 25819654.21
September 38233270.48 25544.51 38207725.97 33385370.80 45832613.40
October 29346564.00 0.00 29346564.00 9785133.57 77663907.54
November 19866023.67 0.00 19866023.67 1803351.96 0.115608E+09
December 13315836.12 0.00 13315836.12 0.00 0.169713E+09
           
Annual Sum or Average 0.454526E+09 13413756.05 0.441112E+09 0.322827E+09 0.101959E+10
Minimum of Months 13315836.12 0.00 13315836.12 0.00 21082044.47
Maximum of Months 63402171.80 5727469.14 57674702.65 72249913.42 0.191304E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM201_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52603806.49 21339503.56 31264302.93 25374156.80 0.181654E+09
February 69115458.47 33901784.83 35213673.63 47042825.81 0.132744E+09
March 91879585.08 34227162.82 57652422.26 73034313.05 96954119.21
April 0.129620E+09 64053301.44 65566582.39 0.135423E+09 70191717.77
May 0.134304E+09 53658739.97 80645320.77 0.152721E+09 45383141.94
June 0.152273E+09 65868087.83 86405160.75 0.190369E+09 31090976.36
July 0.169303E+09 80459444.71 88843586.77 0.217416E+09 28512201.00
August 0.147555E+09 67484679.05 80070711.53 0.190017E+09 33456026.47
September 0.115875E+09 54934023.98 60940609.95 0.137875E+09 51546418.27
October 83807558.06 37358040.40 46449517.66 79617928.19 79891052.57
November 48515592.57 18020076.78 30495515.78 31027475.94 0.112278E+09
December 38720190.41 18415252.86 20304937.56 22399274.19 0.163996E+09
           
Annual Sum or Average 0.123357E+10 0.549720E+09 0.683852E+09 0.130232E+10 0.102770E+10
Minimum of Months 38720190.41 18020076.78 20304937.56 22399274.19 28512201.00
Maximum of Months 0.169303E+09 80459444.71 88843586.77 0.217416E+09 0.181654E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM202_205_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52603806.49 21339503.56 31264302.93 23703820.07 0.201967E+09
February 69115458.47 33901784.83 35213673.63 44970299.02 0.146435E+09
March 91879585.08 34227162.82 57652422.26 70459144.47 0.105210E+09
April 0.129620E+09 64053301.44 65566582.39 0.135113E+09 71885630.44
May 0.134304E+09 53658739.97 80645320.77 0.155134E+09 41954989.97
June 0.152273E+09 65868087.83 86405160.75 0.196310E+09 26057507.66
July 0.169303E+09 80459444.71 88843586.77 0.224367E+09 22889436.78
August 0.147555E+09 67484679.05 80070711.53 0.195963E+09 27914689.35
September 0.115875E+09 54934023.98 60940609.95 0.140542E+09 47571307.16
October 83807558.06 37358040.40 46449517.66 78583640.48 80626427.00
November 48515592.57 18020076.78 30495515.78 29724005.88 0.121379E+09
December 38720190.41 18415252.86 20304937.56 21222601.32 0.182145E+09
           
Annual Sum or Average 0.123357E+10 0.549720E+09 0.683852E+09 0.131609E+10 0.107604E+10
Minimum of Months 38720190.41 18020076.78 20304937.56 21222601.32 22889436.78
Maximum of Months 0.169303E+09 80459444.71 88843586.77 0.224367E+09 0.201967E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM202_205_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52603806.49 21339503.56 31264302.93 23703820.07 0.201967E+09
February 69115458.47 33901784.83 35213673.63 44970299.02 0.146435E+09
March 91879585.08 34227162.82 57652422.26 70459144.47 0.105210E+09
April 0.129620E+09 64053301.44 65566582.39 0.135113E+09 71885630.44
May 0.134304E+09 53658739.97 80645320.77 0.155134E+09 41954989.97
June 0.152273E+09 65868087.83 86405160.75 0.196310E+09 26057507.66
July 0.169303E+09 80459444.71 88843586.77 0.224367E+09 22889436.78
August 0.147555E+09 67484679.05 80070711.53 0.195963E+09 27914689.35
September 0.115875E+09 54934023.98 60940609.95 0.140542E+09 47571307.16
October 83807558.06 37358040.40 46449517.66 78583640.48 80626427.00
November 48515592.57 18020076.78 30495515.78 29724005.88 0.121379E+09
December 38720190.41 18415252.86 20304937.56 21222601.32 0.182145E+09
           
Annual Sum or Average 0.123357E+10 0.549720E+09 0.683852E+09 0.131609E+10 0.107604E+10
Minimum of Months 38720190.41 18020076.78 20304937.56 21222601.32 22889436.78
Maximum of Months 0.169303E+09 80459444.71 88843586.77 0.224367E+09 0.201967E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM202_205_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52603806.49 21339503.56 31264302.93 23703820.07 0.201967E+09
February 69115458.47 33901784.83 35213673.63 44970299.02 0.146435E+09
March 91879585.08 34227162.82 57652422.26 70459144.47 0.105210E+09
April 0.129620E+09 64053301.44 65566582.39 0.135113E+09 71885630.44
May 0.134304E+09 53658739.97 80645320.77 0.155134E+09 41954989.97
June 0.152273E+09 65868087.83 86405160.75 0.196310E+09 26057507.66
July 0.169303E+09 80459444.71 88843586.77 0.224367E+09 22889436.78
August 0.147555E+09 67484679.05 80070711.53 0.195963E+09 27914689.35
September 0.115875E+09 54934023.98 60940609.95 0.140542E+09 47571307.16
October 83807558.06 37358040.40 46449517.66 78583640.48 80626427.00
November 48515592.57 18020076.78 30495515.78 29724005.88 0.121379E+09
December 38720190.41 18415252.86 20304937.56 21222601.32 0.182145E+09
           
Annual Sum or Average 0.123357E+10 0.549720E+09 0.683852E+09 0.131609E+10 0.107604E+10
Minimum of Months 38720190.41 18020076.78 20304937.56 21222601.32 22889436.78
Maximum of Months 0.169303E+09 80459444.71 88843586.77 0.224367E+09 0.201967E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM202_205_5_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52603806.49 21339503.56 31264302.93 23703820.07 0.201967E+09
February 69115458.47 33901784.83 35213673.63 44970299.02 0.146435E+09
March 91879585.08 34227162.82 57652422.26 70459144.47 0.105210E+09
April 0.129620E+09 64053301.44 65566582.39 0.135113E+09 71885630.44
May 0.134304E+09 53658739.97 80645320.77 0.155134E+09 41954989.97
June 0.152273E+09 65868087.83 86405160.75 0.196310E+09 26057507.66
July 0.169303E+09 80459444.71 88843586.77 0.224367E+09 22889436.78
August 0.147555E+09 67484679.05 80070711.53 0.195963E+09 27914689.35
September 0.115875E+09 54934023.98 60940609.95 0.140542E+09 47571307.16
October 83807558.06 37358040.40 46449517.66 78583640.48 80626427.00
November 48515592.57 18020076.78 30495515.78 29724005.88 0.121379E+09
December 38720190.41 18415252.86 20304937.56 21222601.32 0.182145E+09
           
Annual Sum or Average 0.123357E+10 0.549720E+09 0.683852E+09 0.131609E+10 0.107604E+10
Minimum of Months 38720190.41 18020076.78 20304937.56 21222601.32 22889436.78
Maximum of Months 0.169303E+09 80459444.71 88843586.77 0.224367E+09 0.201967E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM206_208_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52603806.49 21339503.56 31264302.93 23271365.95 0.204846E+09
February 69115458.47 33901784.83 35213673.63 44345852.89 0.148863E+09
March 91879585.08 34227162.82 57652422.26 69470552.13 0.107144E+09
April 0.129620E+09 64053301.44 65566582.39 0.134486E+09 72908325.22
May 0.134304E+09 53658739.97 80645320.77 0.154864E+09 42110976.51
June 0.152273E+09 65868087.83 86405160.75 0.196341E+09 25940692.12
July 0.169303E+09 80459444.71 88843586.77 0.224482E+09 22678496.05
August 0.147555E+09 67484679.05 80070711.53 0.196050E+09 27728613.23
September 0.115875E+09 54934023.98 60940609.95 0.140469E+09 47581638.15
October 83807558.06 37358040.40 46449517.66 78209576.76 81200957.38
November 48515592.57 18020076.78 30495515.78 29322486.83 0.123220E+09
December 38720190.41 18415252.86 20304937.56 20841596.49 0.185041E+09
           
Annual Sum or Average 0.123357E+10 0.549720E+09 0.683852E+09 0.131215E+10 0.108926E+10
Minimum of Months 38720190.41 18020076.78 20304937.56 20841596.49 22678496.05
Maximum of Months 0.169303E+09 80459444.71 88843586.77 0.224482E+09 0.204846E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM206_208_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.108559E+09 44038753.72 64520593.19 48064199.51 0.422513E+09
February 0.142635E+09 69963780.99 72670949.75 91568925.23 0.307029E+09
March 0.189613E+09 70635269.95 0.118978E+09 0.143444E+09 0.220988E+09
April 0.267499E+09 0.132188E+09 0.135311E+09 0.277612E+09 0.150382E+09
May 0.277165E+09 0.110737E+09 0.166429E+09 0.319668E+09 86870393.00
June 0.314249E+09 0.135933E+09 0.178315E+09 0.405250E+09 53518998.26
July 0.349393E+09 0.166046E+09 0.183348E+09 0.463328E+09 46794314.27
August 0.304512E+09 0.139269E+09 0.165243E+09 0.404654E+09 57207355.96
September 0.239132E+09 0.113368E+09 0.125764E+09 0.289939E+09 98162760.07
October 0.172955E+09 77096523.65 95858525.86 0.161463E+09 0.167498E+09
November 0.100122E+09 37188387.32 62934043.31 60546663.21 0.254150E+09
December 79907503.50 38003919.97 41903583.53 43036826.25 0.381669E+09
           
Annual Sum or Average 0.254574E+10 0.113447E+10 0.141128E+10 0.270858E+10 0.224678E+10
Minimum of Months 79907503.50 37188387.32 41903583.53 43036826.25 46794314.27
Maximum of Months 0.349393E+09 0.166046E+09 0.183348E+09 0.463328E+09 0.422513E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM206_208_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52603806.49 21339503.56 31264302.93 23271365.95 0.204846E+09
February 69115458.47 33901784.83 35213673.63 44345852.89 0.148863E+09
March 91879585.08 34227162.82 57652422.26 69470552.13 0.107144E+09
April 0.129620E+09 64053301.44 65566582.39 0.134486E+09 72908325.22
May 0.134304E+09 53658739.97 80645320.77 0.154864E+09 42110976.51
June 0.152273E+09 65868087.83 86405160.75 0.196341E+09 25940692.12
July 0.169303E+09 80459444.71 88843586.77 0.224482E+09 22678496.05
August 0.147555E+09 67484679.05 80070711.53 0.196050E+09 27728613.23
September 0.115875E+09 54934023.98 60940609.95 0.140469E+09 47581638.15
October 83807558.06 37358040.40 46449517.66 78209576.76 81200957.38
November 48515592.57 18020076.78 30495515.78 29322486.83 0.123220E+09
December 38720190.41 18415252.86 20304937.56 20841596.49 0.185041E+09
           
Annual Sum or Average 0.123357E+10 0.549720E+09 0.683852E+09 0.131215E+10 0.108926E+10
Minimum of Months 38720190.41 18020076.78 20304937.56 20841596.49 22678496.05
Maximum of Months 0.169303E+09 80459444.71 88843586.77 0.224482E+09 0.204846E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM209_212_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52603806.49 21339503.56 31264302.93 23138043.26 0.206052E+09
February 69115458.47 33901784.83 35213673.63 44245284.06 0.149520E+09
March 91879585.08 34227162.82 57652422.26 69532317.95 0.107334E+09
April 0.129620E+09 64053301.44 65566582.39 0.135036E+09 72342853.43
May 0.134304E+09 53658739.97 80645320.77 0.156025E+09 41260321.12
June 0.152273E+09 65868087.83 86405160.75 0.197725E+09 25040072.83
July 0.169303E+09 80459444.71 88843586.77 0.225914E+09 21753004.82
August 0.147555E+09 67484679.05 80070711.53 0.197242E+09 26855230.49
September 0.115875E+09 54934023.98 60940609.95 0.141117E+09 46933881.90
October 83807558.06 37358040.40 46449517.66 78325698.62 81151466.49
November 48515592.57 18020076.78 30495515.78 29222034.26 0.123976E+09
December 38720190.41 18415252.86 20304937.56 20717931.27 0.186355E+09
           
Annual Sum or Average 0.123357E+10 0.549720E+09 0.683852E+09 0.131824E+10 0.108857E+10
Minimum of Months 38720190.41 18020076.78 20304937.56 20717931.27 21753004.82
Maximum of Months 0.169303E+09 80459444.71 88843586.77 0.225914E+09 0.206052E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM209_212_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52603806.49 21339503.56 31264302.93 23138043.26 0.206052E+09
February 69115458.47 33901784.83 35213673.63 44245284.06 0.149520E+09
March 91879585.08 34227162.82 57652422.26 69532317.95 0.107334E+09
April 0.129620E+09 64053301.44 65566582.39 0.135036E+09 72342853.43
May 0.134304E+09 53658739.97 80645320.77 0.156025E+09 41260321.12
June 0.152273E+09 65868087.83 86405160.75 0.197725E+09 25040072.83
July 0.169303E+09 80459444.71 88843586.77 0.225914E+09 21753004.82
August 0.147555E+09 67484679.05 80070711.53 0.197242E+09 26855230.49
September 0.115875E+09 54934023.98 60940609.95 0.141117E+09 46933881.90
October 83807558.06 37358040.40 46449517.66 78325698.62 81151466.49
November 48515592.57 18020076.78 30495515.78 29222034.26 0.123976E+09
December 38720190.41 18415252.86 20304937.56 20717931.27 0.186355E+09
           
Annual Sum or Average 0.123357E+10 0.549720E+09 0.683852E+09 0.131824E+10 0.108857E+10
Minimum of Months 38720190.41 18020076.78 20304937.56 20717931.27 21753004.82
Maximum of Months 0.169303E+09 80459444.71 88843586.77 0.225914E+09 0.206052E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM209_212_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52603806.49 21339503.56 31264302.93 23138043.26 0.206052E+09
February 69115458.47 33901784.83 35213673.63 44245284.06 0.149520E+09
March 91879585.08 34227162.82 57652422.26 69532317.95 0.107334E+09
April 0.129620E+09 64053301.44 65566582.39 0.135036E+09 72342853.43
May 0.134304E+09 53658739.97 80645320.77 0.156025E+09 41260321.12
June 0.152273E+09 65868087.83 86405160.75 0.197725E+09 25040072.83
July 0.169303E+09 80459444.71 88843586.77 0.225914E+09 21753004.82
August 0.147555E+09 67484679.05 80070711.53 0.197242E+09 26855230.49
September 0.115875E+09 54934023.98 60940609.95 0.141117E+09 46933881.90
October 83807558.06 37358040.40 46449517.66 78325698.62 81151466.49
November 48515592.57 18020076.78 30495515.78 29222034.26 0.123976E+09
December 38720190.41 18415252.86 20304937.56 20717931.27 0.186355E+09
           
Annual Sum or Average 0.123357E+10 0.549720E+09 0.683852E+09 0.131824E+10 0.108857E+10
Minimum of Months 38720190.41 18020076.78 20304937.56 20717931.27 21753004.82
Maximum of Months 0.169303E+09 80459444.71 88843586.77 0.225914E+09 0.206052E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM209_212_5_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52603806.49 21339503.56 31264302.93 23138043.26 0.206052E+09
February 69115458.47 33901784.83 35213673.63 44245284.06 0.149520E+09
March 91879585.08 34227162.82 57652422.26 69532317.95 0.107334E+09
April 0.129620E+09 64053301.44 65566582.39 0.135036E+09 72342853.43
May 0.134304E+09 53658739.97 80645320.77 0.156025E+09 41260321.12
June 0.152273E+09 65868087.83 86405160.75 0.197725E+09 25040072.83
July 0.169303E+09 80459444.71 88843586.77 0.225914E+09 21753004.82
August 0.147555E+09 67484679.05 80070711.53 0.197242E+09 26855230.49
September 0.115875E+09 54934023.98 60940609.95 0.141117E+09 46933881.90
October 83807558.06 37358040.40 46449517.66 78325698.62 81151466.49
November 48515592.57 18020076.78 30495515.78 29222034.26 0.123976E+09
December 38720190.41 18415252.86 20304937.56 20717931.27 0.186355E+09
           
Annual Sum or Average 0.123357E+10 0.549720E+09 0.683852E+09 0.131824E+10 0.108857E+10
Minimum of Months 38720190.41 18020076.78 20304937.56 20717931.27 21753004.82
Maximum of Months 0.169303E+09 80459444.71 88843586.77 0.225914E+09 0.206052E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM213_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52603806.49 21339503.56 31264302.93 23901118.02 0.201008E+09
February 69115458.47 33901784.83 35213673.63 45302573.77 0.145412E+09
March 91879585.08 34227162.82 57652422.26 71651269.53 0.103577E+09
April 0.129620E+09 64053301.44 65566582.39 0.136595E+09 69436127.26
May 0.134304E+09 53658739.97 80645320.77 0.157312E+09 39852776.93
June 0.152273E+09 65868087.83 86405160.75 0.198225E+09 24201625.45
July 0.169303E+09 80459444.71 88843586.77 0.226076E+09 21126091.49
August 0.147555E+09 67484679.05 80070711.53 0.197395E+09 26252707.91
September 0.115875E+09 54934023.98 60940609.95 0.141706E+09 45821953.38
October 83807558.06 37358040.40 46449517.66 79862794.21 78786503.68
November 48515592.57 18020076.78 30495515.78 30360498.01 0.119848E+09
December 38720190.41 18415252.86 20304937.56 21437331.54 0.181045E+09
           
Annual Sum or Average 0.123357E+10 0.549720E+09 0.683852E+09 0.132982E+10 0.105637E+10
Minimum of Months 38720190.41 18020076.78 20304937.56 21437331.54 21126091.49
Maximum of Months 0.169303E+09 80459444.71 88843586.77 0.226076E+09 0.201008E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM214_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53074673.03 21930893.58 31143779.45 21304427.51 0.204789E+09
February 63110617.56 27612682.59 35497934.97 34319407.77 0.147252E+09
March 95228230.66 37701094.67 57527135.99 71472525.91 0.106429E+09
April 0.113089E+09 49517764.99 63571687.62 0.109668E+09 72274628.47
May 0.146930E+09 64176563.55 82753299.08 0.168850E+09 40522925.55
June 0.156495E+09 68191201.21 88303827.57 0.201224E+09 24961685.20
July 0.163410E+09 75506884.86 87903306.11 0.215476E+09 21661123.36
August 0.137556E+09 59187991.28 78367698.97 0.180663E+09 26645896.35
September 0.119272E+09 56502671.97 62769167.18 0.144244E+09 46822360.69
October 78157059.18 32550949.09 45606110.09 67937073.10 79916280.82
November 44752837.98 14547237.81 30205600.17 21915699.48 0.124553E+09
December 35615078.05 15210100.71 20404977.34 14611380.13 0.186307E+09
           
Annual Sum or Average 0.120669E+10 0.522636E+09 0.684055E+09 0.125169E+10 0.108213E+10
Minimum of Months 35615078.05 14547237.81 20404977.34 14611380.13 21661123.36
Maximum of Months 0.163410E+09 75506884.86 88303827.57 0.215476E+09 0.204789E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM215_218_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53074673.03 21930893.58 31143779.45 17341393.74 0.253034E+09
February 63110617.56 27612682.59 35497934.97 28990970.46 0.187451E+09
March 95228230.66 37701094.67 57527135.99 59929849.96 0.143085E+09
April 0.113089E+09 49517764.99 63571687.62 96421672.47 0.103193E+09
May 0.146930E+09 64176563.55 82753299.08 0.148821E+09 62447536.67
June 0.156495E+09 68191201.21 88303827.57 0.180640E+09 43720106.99
July 0.163410E+09 75506884.86 87903306.11 0.194249E+09 39278005.62
August 0.137556E+09 59187991.28 78367698.97 0.160877E+09 45676722.27
September 0.119272E+09 56502671.97 62769167.18 0.128643E+09 71152107.22
October 78157059.18 32550949.09 45606110.09 55746842.78 0.112131E+09
November 44752837.98 14547237.81 30205600.17 16827550.99 0.165960E+09
December 35615078.05 15210100.71 20404977.34 11888113.30 0.234549E+09
           
Annual Sum or Average 0.120669E+10 0.522636E+09 0.684055E+09 0.110038E+10 0.146168E+10
Minimum of Months 35615078.05 14547237.81 20404977.34 11888113.30 39278005.62
Maximum of Months 0.163410E+09 75506884.86 88303827.57 0.194249E+09 0.253034E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM215_218_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53074673.03 21930893.58 31143779.45 17341393.74 0.253034E+09
February 63110617.56 27612682.59 35497934.97 28990970.46 0.187451E+09
March 95228230.66 37701094.67 57527135.99 59929849.96 0.143085E+09
April 0.113089E+09 49517764.99 63571687.62 96421672.47 0.103193E+09
May 0.146930E+09 64176563.55 82753299.08 0.148821E+09 62447536.67
June 0.156495E+09 68191201.21 88303827.57 0.180640E+09 43720106.99
July 0.163410E+09 75506884.86 87903306.11 0.194249E+09 39278005.62
August 0.137556E+09 59187991.28 78367698.97 0.160877E+09 45676722.27
September 0.119272E+09 56502671.97 62769167.18 0.128643E+09 71152107.22
October 78157059.18 32550949.09 45606110.09 55746842.78 0.112131E+09
November 44752837.98 14547237.81 30205600.17 16827550.99 0.165960E+09
December 35615078.05 15210100.71 20404977.34 11888113.30 0.234549E+09
           
Annual Sum or Average 0.120669E+10 0.522636E+09 0.684055E+09 0.110038E+10 0.146168E+10
Minimum of Months 35615078.05 14547237.81 20404977.34 11888113.30 39278005.62
Maximum of Months 0.163410E+09 75506884.86 88303827.57 0.194249E+09 0.253034E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM215_218_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53074673.03 21930893.58 31143779.45 17341393.74 0.253034E+09
February 63110617.56 27612682.59 35497934.97 28990970.46 0.187451E+09
March 95228230.66 37701094.67 57527135.99 59929849.96 0.143085E+09
April 0.113089E+09 49517764.99 63571687.62 96421672.47 0.103193E+09
May 0.146930E+09 64176563.55 82753299.08 0.148821E+09 62447536.67
June 0.156495E+09 68191201.21 88303827.57 0.180640E+09 43720106.99
July 0.163410E+09 75506884.86 87903306.11 0.194249E+09 39278005.62
August 0.137556E+09 59187991.28 78367698.97 0.160877E+09 45676722.27
September 0.119272E+09 56502671.97 62769167.18 0.128643E+09 71152107.22
October 78157059.18 32550949.09 45606110.09 55746842.78 0.112131E+09
November 44752837.98 14547237.81 30205600.17 16827550.99 0.165960E+09
December 35615078.05 15210100.71 20404977.34 11888113.30 0.234549E+09
           
Annual Sum or Average 0.120669E+10 0.522636E+09 0.684055E+09 0.110038E+10 0.146168E+10
Minimum of Months 35615078.05 14547237.81 20404977.34 11888113.30 39278005.62
Maximum of Months 0.163410E+09 75506884.86 88303827.57 0.194249E+09 0.253034E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM215_218_3_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53074673.03 21930893.58 31143779.45 17341393.74 0.253034E+09
February 63110617.56 27612682.59 35497934.97 28990970.46 0.187451E+09
March 95228230.66 37701094.67 57527135.99 59929849.96 0.143085E+09
April 0.113089E+09 49517764.99 63571687.62 96421672.47 0.103193E+09
May 0.146930E+09 64176563.55 82753299.08 0.148821E+09 62447536.67
June 0.156495E+09 68191201.21 88303827.57 0.180640E+09 43720106.99
July 0.163410E+09 75506884.86 87903306.11 0.194249E+09 39278005.62
August 0.137556E+09 59187991.28 78367698.97 0.160877E+09 45676722.27
September 0.119272E+09 56502671.97 62769167.18 0.128643E+09 71152107.22
October 78157059.18 32550949.09 45606110.09 55746842.78 0.112131E+09
November 44752837.98 14547237.81 30205600.17 16827550.99 0.165960E+09
December 35615078.05 15210100.71 20404977.34 11888113.30 0.234549E+09
           
Annual Sum or Average 0.120669E+10 0.522636E+09 0.684055E+09 0.110038E+10 0.146168E+10
Minimum of Months 35615078.05 14547237.81 20404977.34 11888113.30 39278005.62
Maximum of Months 0.163410E+09 75506884.86 88303827.57 0.194249E+09 0.253034E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM219_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53074673.03 21930893.58 31143779.45 17625771.45 0.245274E+09
February 63110617.56 27612682.59 35497934.97 29473436.67 0.183659E+09
March 95228230.66 37701094.67 57527135.99 61301920.22 0.134727E+09
April 0.113089E+09 49517764.99 63571687.62 97995686.97 96596022.99
May 0.146930E+09 64176563.55 82753299.08 0.151022E+09 59386474.46
June 0.156495E+09 68191201.21 88303827.57 0.183328E+09 40823198.67
July 0.163410E+09 75506884.86 87903306.11 0.196426E+09 37286552.56
August 0.137556E+09 59187991.28 78367698.97 0.162875E+09 43919997.14
September 0.119272E+09 56502671.97 62769167.18 0.130923E+09 67272256.11
October 78157059.18 32550949.09 45606110.09 57435522.83 0.104913E+09
November 44752837.98 14547237.81 30205600.17 17645827.28 0.156999E+09
December 35615078.05 15210100.71 20404977.34 12464418.82 0.223919E+09
           
Annual Sum or Average 0.120669E+10 0.522636E+09 0.684055E+09 0.111852E+10 0.139478E+10
Minimum of Months 35615078.05 14547237.81 20404977.34 12464418.82 37286552.56
Maximum of Months 0.163410E+09 75506884.86 88303827.57 0.196426E+09 0.245274E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM220_223_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53074673.03 21930893.58 31143779.45 21550752.37 0.202951E+09
February 63110617.56 27612682.59 35497934.97 34684762.24 0.145536E+09
March 95228230.66 37701094.67 57527135.99 72288715.88 0.104877E+09
April 0.113089E+09 49517764.99 63571687.62 0.110677E+09 70824425.68
May 0.146930E+09 64176563.55 82753299.08 0.170478E+09 39422857.57
June 0.156495E+09 68191201.21 88303827.57 0.203025E+09 23934955.52
July 0.163410E+09 75506884.86 87903306.11 0.217525E+09 20450338.00
August 0.137556E+09 59187991.28 78367698.97 0.182673E+09 25142491.42
September 0.119272E+09 56502671.97 62769167.18 0.145683E+09 45266226.07
October 78157059.18 32550949.09 45606110.09 68984158.82 78133374.33
November 44752837.98 14547237.81 30205600.17 22373705.74 0.122419E+09
December 35615078.05 15210100.71 20404977.34 14800426.51 0.184091E+09
           
Annual Sum or Average 0.120669E+10 0.522636E+09 0.684055E+09 0.126474E+10 0.106305E+10
Minimum of Months 35615078.05 14547237.81 20404977.34 14800426.51 20450338.00
Maximum of Months 0.163410E+09 75506884.86 88303827.57 0.217525E+09 0.202951E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM220_223_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53074673.03 21930893.58 31143779.45 21550752.37 0.202951E+09
February 63110617.56 27612682.59 35497934.97 34684762.24 0.145536E+09
March 95228230.66 37701094.67 57527135.99 72288715.88 0.104877E+09
April 0.113089E+09 49517764.99 63571687.62 0.110677E+09 70824425.68
May 0.146930E+09 64176563.55 82753299.08 0.170478E+09 39422857.57
June 0.156495E+09 68191201.21 88303827.57 0.203025E+09 23934955.52
July 0.163410E+09 75506884.86 87903306.11 0.217525E+09 20450338.00
August 0.137556E+09 59187991.28 78367698.97 0.182673E+09 25142491.42
September 0.119272E+09 56502671.97 62769167.18 0.145683E+09 45266226.07
October 78157059.18 32550949.09 45606110.09 68984158.82 78133374.33
November 44752837.98 14547237.81 30205600.17 22373705.74 0.122419E+09
December 35615078.05 15210100.71 20404977.34 14800426.51 0.184091E+09
           
Annual Sum or Average 0.120669E+10 0.522636E+09 0.684055E+09 0.126474E+10 0.106305E+10
Minimum of Months 35615078.05 14547237.81 20404977.34 14800426.51 20450338.00
Maximum of Months 0.163410E+09 75506884.86 88303827.57 0.217525E+09 0.202951E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM220_223_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53074673.03 21930893.58 31143779.45 21550752.37 0.202951E+09
February 63110617.56 27612682.59 35497934.97 34684762.24 0.145536E+09
March 95228230.66 37701094.67 57527135.99 72288715.88 0.104877E+09
April 0.113089E+09 49517764.99 63571687.62 0.110677E+09 70824425.68
May 0.146930E+09 64176563.55 82753299.08 0.170478E+09 39422857.57
June 0.156495E+09 68191201.21 88303827.57 0.203025E+09 23934955.52
July 0.163410E+09 75506884.86 87903306.11 0.217525E+09 20450338.00
August 0.137556E+09 59187991.28 78367698.97 0.182673E+09 25142491.42
September 0.119272E+09 56502671.97 62769167.18 0.145683E+09 45266226.07
October 78157059.18 32550949.09 45606110.09 68984158.82 78133374.33
November 44752837.98 14547237.81 30205600.17 22373705.74 0.122419E+09
December 35615078.05 15210100.71 20404977.34 14800426.51 0.184091E+09
           
Annual Sum or Average 0.120669E+10 0.522636E+09 0.684055E+09 0.126474E+10 0.106305E+10
Minimum of Months 35615078.05 14547237.81 20404977.34 14800426.51 20450338.00
Maximum of Months 0.163410E+09 75506884.86 88303827.57 0.217525E+09 0.202951E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM220_223_3_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53074673.03 21930893.58 31143779.45 21550752.37 0.202951E+09
February 63110617.56 27612682.59 35497934.97 34684762.24 0.145536E+09
March 95228230.66 37701094.67 57527135.99 72288715.88 0.104877E+09
April 0.113089E+09 49517764.99 63571687.62 0.110677E+09 70824425.68
May 0.146930E+09 64176563.55 82753299.08 0.170478E+09 39422857.57
June 0.156495E+09 68191201.21 88303827.57 0.203025E+09 23934955.52
July 0.163410E+09 75506884.86 87903306.11 0.217525E+09 20450338.00
August 0.137556E+09 59187991.28 78367698.97 0.182673E+09 25142491.42
September 0.119272E+09 56502671.97 62769167.18 0.145683E+09 45266226.07
October 78157059.18 32550949.09 45606110.09 68984158.82 78133374.33
November 44752837.98 14547237.81 30205600.17 22373705.74 0.122419E+09
December 35615078.05 15210100.71 20404977.34 14800426.51 0.184091E+09
           
Annual Sum or Average 0.120669E+10 0.522636E+09 0.684055E+09 0.126474E+10 0.106305E+10
Minimum of Months 35615078.05 14547237.81 20404977.34 14800426.51 20450338.00
Maximum of Months 0.163410E+09 75506884.86 88303827.57 0.217525E+09 0.202951E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM224_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53074673.03 21930893.58 31143779.45 21827401.82 0.199460E+09
February 63110617.56 27612682.59 35497934.97 35172781.38 0.142641E+09
March 95228230.66 37701094.67 57527135.99 73236008.41 0.102888E+09
April 0.113089E+09 49517764.99 63571687.62 0.111122E+09 69760928.97
May 0.146930E+09 64176563.55 82753299.08 0.170146E+09 39153503.17
June 0.156495E+09 68191201.21 88303827.57 0.202290E+09 23995733.49
July 0.163410E+09 75506884.86 87903306.11 0.216621E+09 20639697.46
August 0.137556E+09 59187991.28 78367698.97 0.181844E+09 25373951.26
September 0.119272E+09 56502671.97 62769167.18 0.145301E+09 45262150.86
October 78157059.18 32550949.09 45606110.09 69270226.87 77500005.71
November 44752837.98 14547237.81 30205600.17 22617310.24 0.120448E+09
December 35615078.05 15210100.71 20404977.34 14974794.64 0.180604E+09
           
Annual Sum or Average 0.120669E+10 0.522636E+09 0.684055E+09 0.126442E+10 0.104773E+10
Minimum of Months 35615078.05 14547237.81 20404977.34 14974794.64 20639697.46
Maximum of Months 0.163410E+09 75506884.86 88303827.57 0.216621E+09 0.199460E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_CORRIDORFLR3_2_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.121837E+09 83318398.15 38518973.27 0.105649E+09 0.149130E+09
February 0.119916E+09 81633068.74 38282857.55 0.109668E+09 0.108324E+09
March 0.112139E+09 58308630.86 53830002.05 0.107667E+09 86097356.04
April 99615629.23 46816771.60 52798857.63 0.108171E+09 61981923.67
May 84904501.91 23037658.86 61866843.05 97553582.43 38602854.32
June 79705522.24 16198463.65 63507058.59 0.102481E+09 24390485.47
July 87542987.82 22286821.46 65256166.36 0.117802E+09 21270751.05
August 96228096.39 33194872.11 63033224.28 0.130794E+09 25951786.11
September 0.113765E+09 59237649.66 54527402.55 0.145138E+09 41373368.20
October 0.125344E+09 78981980.71 46362479.99 0.139767E+09 64263415.15
November 90835706.31 56858615.09 33977091.22 84398263.51 93885969.48
December 99573649.27 75314095.27 24259554.00 93780007.97 0.138154E+09
           
Annual Sum or Average 0.123141E+10 0.635187E+09 0.596221E+09 0.134287E+10 0.853426E+09
Minimum of Months 79705522.24 16198463.65 24259554.00 84398263.51 21270751.05
Maximum of Months 0.125344E+09 83318398.15 65256166.36 0.145138E+09 0.149130E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_CORRIDORFLR3_15_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 19610029.31 0.00 19610029.31 20182.20 0.185617E+09
February 22455712.01 0.00 22455712.01 637545.63 0.135564E+09
March 37266677.14 1010.90 37265666.24 10236321.40 95275296.51
April 41723531.10 283946.25 41439584.85 22193733.57 62900925.63
May 56182114.19 2175662.54 54006451.65 48607905.28 35870179.02
June 63402171.80 5727469.14 57674702.65 72591631.19 22766076.34
July 61461961.32 4123825.70 57338135.62 73601889.56 20153709.84
August 51661636.28 1076297.01 50585339.27 60829232.81 24640554.90
September 38233270.48 25544.51 38207725.97 35249435.39 42314080.70
October 29346564.00 0.00 29346564.00 12335343.33 69939307.21
November 19866023.67 0.00 19866023.67 2596323.87 0.108437E+09
December 13315836.12 0.00 13315836.12 340.08 0.163751E+09
           
Annual Sum or Average 0.454526E+09 13413756.05 0.441112E+09 0.338900E+09 0.967229E+09
Minimum of Months 13315836.12 0.00 13315836.12 340.08 20153709.84
Maximum of Months 63402171.80 5727469.14 57674702.65 73601889.56 0.185617E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM301_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 26087707.63 0.174559E+09
February 68924134.55 33807939.06 35116195.48 48273531.75 0.125933E+09
March 91625245.77 34132416.35 57492829.42 75676480.20 90547237.76
April 0.129261E+09 63875991.27 65385081.43 0.137423E+09 65680080.07
May 0.133932E+09 53510203.67 80422078.98 0.154673E+09 43602953.89
June 0.151852E+09 65685754.02 86165974.55 0.191312E+09 30167044.10
July 0.168834E+09 80236719.61 88597650.50 0.217988E+09 28074289.72
August 0.147147E+09 67297870.25 79849060.43 0.190999E+09 32659819.32
September 0.115554E+09 54781957.48 60771914.63 0.139906E+09 48589009.43
October 83575563.73 37254627.14 46320936.60 83014096.62 72932077.80
November 48381292.70 17970194.22 30411098.49 32919169.68 0.103856E+09
December 38613006.01 18364276.38 20248729.63 23204484.33 0.154763E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.132148E+10 0.971363E+09
Minimum of Months 38613006.01 17970194.22 20248729.63 23204484.33 28074289.72
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.217988E+09 0.174559E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM302_305_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 25492734.85 0.180824E+09
February 68924134.55 33807939.06 35116195.48 47322485.48 0.131896E+09
March 91625245.77 34132416.35 57492829.42 73800717.17 96409126.47
April 0.129261E+09 63875991.27 65385081.43 0.135843E+09 70222126.77
May 0.133932E+09 53510203.67 80422078.98 0.153355E+09 45877154.46
June 0.151852E+09 65685754.02 86165974.55 0.190649E+09 31606636.82
July 0.168834E+09 80236719.61 88597650.50 0.217385E+09 29398693.99
August 0.147147E+09 67297870.25 79849060.43 0.190324E+09 34190759.49
September 0.115554E+09 54781957.48 60771914.63 0.138792E+09 51108622.35
October 83575563.73 37254627.14 46320936.60 81539888.72 77181038.63
November 48381292.70 17970194.22 30411098.49 31960396.54 0.109492E+09
December 38613006.01 18364276.38 20248729.63 22600301.59 0.162137E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.130906E+10 0.102034E+10
Minimum of Months 38613006.01 17970194.22 20248729.63 22600301.59 29398693.99
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.217385E+09 0.180824E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM302_305_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 25492734.85 0.180824E+09
February 68924134.55 33807939.06 35116195.48 47322485.48 0.131896E+09
March 91625245.77 34132416.35 57492829.42 73800717.17 96409126.47
April 0.129261E+09 63875991.27 65385081.43 0.135843E+09 70222126.77
May 0.133932E+09 53510203.67 80422078.98 0.153355E+09 45877154.46
June 0.151852E+09 65685754.02 86165974.55 0.190649E+09 31606636.82
July 0.168834E+09 80236719.61 88597650.50 0.217385E+09 29398693.99
August 0.147147E+09 67297870.25 79849060.43 0.190324E+09 34190759.49
September 0.115554E+09 54781957.48 60771914.63 0.138792E+09 51108622.35
October 83575563.73 37254627.14 46320936.60 81539888.72 77181038.63
November 48381292.70 17970194.22 30411098.49 31960396.54 0.109492E+09
December 38613006.01 18364276.38 20248729.63 22600301.59 0.162137E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.130906E+10 0.102034E+10
Minimum of Months 38613006.01 17970194.22 20248729.63 22600301.59 29398693.99
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.217385E+09 0.180824E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM302_305_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 25492734.85 0.180824E+09
February 68924134.55 33807939.06 35116195.48 47322485.48 0.131896E+09
March 91625245.77 34132416.35 57492829.42 73800717.17 96409126.47
April 0.129261E+09 63875991.27 65385081.43 0.135843E+09 70222126.77
May 0.133932E+09 53510203.67 80422078.98 0.153355E+09 45877154.46
June 0.151852E+09 65685754.02 86165974.55 0.190649E+09 31606636.82
July 0.168834E+09 80236719.61 88597650.50 0.217385E+09 29398693.99
August 0.147147E+09 67297870.25 79849060.43 0.190324E+09 34190759.49
September 0.115554E+09 54781957.48 60771914.63 0.138792E+09 51108622.35
October 83575563.73 37254627.14 46320936.60 81539888.72 77181038.63
November 48381292.70 17970194.22 30411098.49 31960396.54 0.109492E+09
December 38613006.01 18364276.38 20248729.63 22600301.59 0.162137E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.130906E+10 0.102034E+10
Minimum of Months 38613006.01 17970194.22 20248729.63 22600301.59 29398693.99
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.217385E+09 0.180824E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM302_305_5_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 25492734.85 0.180824E+09
February 68924134.55 33807939.06 35116195.48 47322485.48 0.131896E+09
March 91625245.77 34132416.35 57492829.42 73800717.17 96409126.47
April 0.129261E+09 63875991.27 65385081.43 0.135843E+09 70222126.77
May 0.133932E+09 53510203.67 80422078.98 0.153355E+09 45877154.46
June 0.151852E+09 65685754.02 86165974.55 0.190649E+09 31606636.82
July 0.168834E+09 80236719.61 88597650.50 0.217385E+09 29398693.99
August 0.147147E+09 67297870.25 79849060.43 0.190324E+09 34190759.49
September 0.115554E+09 54781957.48 60771914.63 0.138792E+09 51108622.35
October 83575563.73 37254627.14 46320936.60 81539888.72 77181038.63
November 48381292.70 17970194.22 30411098.49 31960396.54 0.109492E+09
December 38613006.01 18364276.38 20248729.63 22600301.59 0.162137E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.130906E+10 0.102034E+10
Minimum of Months 38613006.01 17970194.22 20248729.63 22600301.59 29398693.99
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.217385E+09 0.180824E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM306_308_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 25047161.37 0.184304E+09
February 68924134.55 33807939.06 35116195.48 46619352.86 0.134856E+09
March 91625245.77 34132416.35 57492829.42 72554828.34 99018224.02
April 0.129261E+09 63875991.27 65385081.43 0.134849E+09 71760873.30
May 0.133932E+09 53510203.67 80422078.98 0.152750E+09 46212454.94
June 0.151852E+09 65685754.02 86165974.55 0.190526E+09 31466656.17
July 0.168834E+09 80236719.61 88597650.50 0.217378E+09 29127423.97
August 0.147147E+09 67297870.25 79849060.43 0.190253E+09 33973989.21
September 0.115554E+09 54781957.48 60771914.63 0.138460E+09 51298668.92
October 83575563.73 37254627.14 46320936.60 80715377.11 78521132.60
November 48381292.70 17970194.22 30411098.49 31393358.19 0.112013E+09
December 38613006.01 18364276.38 20248729.63 22216838.29 0.165661E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.130276E+10 0.103821E+10
Minimum of Months 38613006.01 17970194.22 20248729.63 22216838.29 29127423.97
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.217378E+09 0.184304E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM306_308_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.108559E+09 44038753.72 64520593.19 51860628.57 0.381240E+09
February 0.142635E+09 69963780.99 72670949.75 96512420.90 0.278948E+09
March 0.189613E+09 70635269.95 0.118978E+09 0.150201E+09 0.204821E+09
April 0.267499E+09 0.132188E+09 0.135311E+09 0.279112E+09 0.148442E+09
May 0.277165E+09 0.110737E+09 0.166429E+09 0.316158E+09 95600206.79
June 0.314249E+09 0.135933E+09 0.178315E+09 0.394325E+09 65098362.19
July 0.349393E+09 0.166046E+09 0.183348E+09 0.449896E+09 60262760.10
August 0.304512E+09 0.139269E+09 0.165243E+09 0.393761E+09 70285461.36
September 0.239132E+09 0.113368E+09 0.125764E+09 0.286571E+09 0.106128E+09
October 0.172955E+09 77096523.65 95858525.86 0.167078E+09 0.162434E+09
November 0.100122E+09 37188387.32 62934043.31 64991120.86 0.231705E+09
December 79907503.50 38003919.97 41903583.53 45994205.12 0.342681E+09
           
Annual Sum or Average 0.254574E+10 0.113447E+10 0.141128E+10 0.269646E+10 0.214765E+10
Minimum of Months 79907503.50 37188387.32 41903583.53 45994205.12 60262760.10
Maximum of Months 0.349393E+09 0.166046E+09 0.183348E+09 0.449896E+09 0.381240E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM306_308_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 25047161.37 0.184304E+09
February 68924134.55 33807939.06 35116195.48 46619352.86 0.134856E+09
March 91625245.77 34132416.35 57492829.42 72554828.34 99018224.02
April 0.129261E+09 63875991.27 65385081.43 0.134849E+09 71760873.30
May 0.133932E+09 53510203.67 80422078.98 0.152750E+09 46212454.94
June 0.151852E+09 65685754.02 86165974.55 0.190526E+09 31466656.17
July 0.168834E+09 80236719.61 88597650.50 0.217378E+09 29127423.97
August 0.147147E+09 67297870.25 79849060.43 0.190253E+09 33973989.21
September 0.115554E+09 54781957.48 60771914.63 0.138460E+09 51298668.92
October 83575563.73 37254627.14 46320936.60 80715377.11 78521132.60
November 48381292.70 17970194.22 30411098.49 31393358.19 0.112013E+09
December 38613006.01 18364276.38 20248729.63 22216838.29 0.165661E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.130276E+10 0.103821E+10
Minimum of Months 38613006.01 17970194.22 20248729.63 22216838.29 29127423.97
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.217378E+09 0.184304E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM309_312_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 23396477.49 0.203106E+09
February 68924134.55 33807939.06 35116195.48 44537419.85 0.147270E+09
March 91625245.77 34132416.35 57492829.42 70136081.19 0.105617E+09
April 0.129261E+09 63875991.27 65385081.43 0.135211E+09 71092935.76
May 0.133932E+09 53510203.67 80422078.98 0.156173E+09 40869081.14
June 0.151852E+09 65685754.02 86165974.55 0.197684E+09 24674275.16
July 0.168834E+09 80236719.61 88597650.50 0.225836E+09 21430250.23
August 0.147147E+09 67297870.25 79849060.43 0.197366E+09 26389096.23
September 0.115554E+09 54781957.48 60771914.63 0.141695E+09 45732781.73
October 83575563.73 37254627.14 46320936.60 79472974.68 78942019.14
November 48381292.70 17970194.22 30411098.49 29947372.44 0.120796E+09
December 38613006.01 18364276.38 20248729.63 21034148.53 0.182948E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.132249E+10 0.106887E+10
Minimum of Months 38613006.01 17970194.22 20248729.63 21034148.53 21430250.23
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.225836E+09 0.203106E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM309_312_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 23396477.49 0.203106E+09
February 68924134.55 33807939.06 35116195.48 44537419.85 0.147270E+09
March 91625245.77 34132416.35 57492829.42 70136081.19 0.105617E+09
April 0.129261E+09 63875991.27 65385081.43 0.135211E+09 71092935.76
May 0.133932E+09 53510203.67 80422078.98 0.156173E+09 40869081.14
June 0.151852E+09 65685754.02 86165974.55 0.197684E+09 24674275.16
July 0.168834E+09 80236719.61 88597650.50 0.225836E+09 21430250.23
August 0.147147E+09 67297870.25 79849060.43 0.197366E+09 26389096.23
September 0.115554E+09 54781957.48 60771914.63 0.141695E+09 45732781.73
October 83575563.73 37254627.14 46320936.60 79472974.68 78942019.14
November 48381292.70 17970194.22 30411098.49 29947372.44 0.120796E+09
December 38613006.01 18364276.38 20248729.63 21034148.53 0.182948E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.132249E+10 0.106887E+10
Minimum of Months 38613006.01 17970194.22 20248729.63 21034148.53 21430250.23
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.225836E+09 0.203106E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM309_312_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 23396477.49 0.203106E+09
February 68924134.55 33807939.06 35116195.48 44537419.85 0.147270E+09
March 91625245.77 34132416.35 57492829.42 70136081.19 0.105617E+09
April 0.129261E+09 63875991.27 65385081.43 0.135211E+09 71092935.76
May 0.133932E+09 53510203.67 80422078.98 0.156173E+09 40869081.14
June 0.151852E+09 65685754.02 86165974.55 0.197684E+09 24674275.16
July 0.168834E+09 80236719.61 88597650.50 0.225836E+09 21430250.23
August 0.147147E+09 67297870.25 79849060.43 0.197366E+09 26389096.23
September 0.115554E+09 54781957.48 60771914.63 0.141695E+09 45732781.73
October 83575563.73 37254627.14 46320936.60 79472974.68 78942019.14
November 48381292.70 17970194.22 30411098.49 29947372.44 0.120796E+09
December 38613006.01 18364276.38 20248729.63 21034148.53 0.182948E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.132249E+10 0.106887E+10
Minimum of Months 38613006.01 17970194.22 20248729.63 21034148.53 21430250.23
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.225836E+09 0.203106E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM309_312_5_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 23396477.49 0.203106E+09
February 68924134.55 33807939.06 35116195.48 44537419.85 0.147270E+09
March 91625245.77 34132416.35 57492829.42 70136081.19 0.105617E+09
April 0.129261E+09 63875991.27 65385081.43 0.135211E+09 71092935.76
May 0.133932E+09 53510203.67 80422078.98 0.156173E+09 40869081.14
June 0.151852E+09 65685754.02 86165974.55 0.197684E+09 24674275.16
July 0.168834E+09 80236719.61 88597650.50 0.225836E+09 21430250.23
August 0.147147E+09 67297870.25 79849060.43 0.197366E+09 26389096.23
September 0.115554E+09 54781957.48 60771914.63 0.141695E+09 45732781.73
October 83575563.73 37254627.14 46320936.60 79472974.68 78942019.14
November 48381292.70 17970194.22 30411098.49 29947372.44 0.120796E+09
December 38613006.01 18364276.38 20248729.63 21034148.53 0.182948E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.132249E+10 0.106887E+10
Minimum of Months 38613006.01 17970194.22 20248729.63 21034148.53 21430250.23
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.225836E+09 0.203106E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM313_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 25468122.82 0.180059E+09
February 68924134.55 33807939.06 35116195.48 47295978.71 0.131204E+09
March 91625245.77 34132416.35 57492829.42 74284822.22 94726951.93
April 0.129261E+09 63875991.27 65385081.43 0.137028E+09 67445230.97
May 0.133932E+09 53510203.67 80422078.98 0.155651E+09 43170591.72
June 0.151852E+09 65685754.02 86165974.55 0.193037E+09 29081039.31
July 0.168834E+09 80236719.61 88597650.50 0.219655E+09 26953488.78
August 0.147147E+09 67297870.25 79849060.43 0.192314E+09 31872326.42
September 0.115554E+09 54781957.48 60771914.63 0.139980E+09 49094200.36
October 83575563.73 37254627.14 46320936.60 82032184.39 75747156.55
November 48381292.70 17970194.22 30411098.49 32113718.64 0.108384E+09
December 38613006.01 18364276.38 20248729.63 22549261.35 0.161635E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.132141E+10 0.999373E+09
Minimum of Months 38613006.01 17970194.22 20248729.63 22549261.35 26953488.78
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.219655E+09 0.180059E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM314_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 21980024.35 0.197115E+09
February 62935916.04 27536246.10 35399669.94 35279410.66 0.141379E+09
March 94964621.74 37596731.77 57367889.97 73463223.51 0.102093E+09
April 0.112776E+09 49380691.59 63395708.86 0.110912E+09 69346710.53
May 0.146523E+09 63998912.16 82524222.06 0.169596E+09 39403623.44
June 0.156062E+09 68002436.64 88059385.55 0.201411E+09 24266815.65
July 0.162958E+09 75297869.26 87659972.69 0.215518E+09 21141684.62
August 0.137175E+09 59024149.09 78150762.09 0.181022E+09 25886065.93
September 0.118942E+09 56346263.19 62595410.10 0.145172E+09 45073964.99
October 77940706.36 32460842.65 45479863.71 70120247.52 76263692.01
November 44628954.05 14506968.64 30121985.40 23046472.29 0.118071E+09
December 35516489.11 15167996.63 20348492.48 15086820.06 0.178080E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.126261E+10 0.103812E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 15086820.06 21141684.62
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.215518E+09 0.197115E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM315_318_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 20752559.82 0.209449E+09
February 62935916.04 27536246.10 35399669.94 33490077.99 0.151117E+09
March 94964621.74 37596731.77 57367889.97 69794039.98 0.109702E+09
April 0.112776E+09 49380691.59 63395708.86 0.108067E+09 74680117.04
May 0.146523E+09 63998912.16 82524222.06 0.166901E+09 42268902.15
June 0.156062E+09 68002436.64 88059385.55 0.199363E+09 26290252.50
July 0.162958E+09 75297869.26 87659972.69 0.213650E+09 22886538.88
August 0.137175E+09 59024149.09 78150762.09 0.179216E+09 27819318.48
September 0.118942E+09 56346263.19 62595410.10 0.143173E+09 47916150.35
October 77940706.36 32460842.65 45479863.71 67112347.66 81093730.38
November 44628954.05 14506968.64 30121985.40 21467140.08 0.127180E+09
December 35516489.11 15167996.63 20348492.48 14283245.18 0.190595E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.123727E+10 0.111100E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 14283245.18 22886538.88
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.213650E+09 0.209449E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM315_318_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 20752559.82 0.209449E+09
February 62935916.04 27536246.10 35399669.94 33490077.99 0.151117E+09
March 94964621.74 37596731.77 57367889.97 69794039.98 0.109702E+09
April 0.112776E+09 49380691.59 63395708.86 0.108067E+09 74680117.04
May 0.146523E+09 63998912.16 82524222.06 0.166901E+09 42268902.15
June 0.156062E+09 68002436.64 88059385.55 0.199363E+09 26290252.50
July 0.162958E+09 75297869.26 87659972.69 0.213650E+09 22886538.88
August 0.137175E+09 59024149.09 78150762.09 0.179216E+09 27819318.48
September 0.118942E+09 56346263.19 62595410.10 0.143173E+09 47916150.35
October 77940706.36 32460842.65 45479863.71 67112347.66 81093730.38
November 44628954.05 14506968.64 30121985.40 21467140.08 0.127180E+09
December 35516489.11 15167996.63 20348492.48 14283245.18 0.190595E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.123727E+10 0.111100E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 14283245.18 22886538.88
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.213650E+09 0.209449E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM315_318_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 20752559.82 0.209449E+09
February 62935916.04 27536246.10 35399669.94 33490077.99 0.151117E+09
March 94964621.74 37596731.77 57367889.97 69794039.98 0.109702E+09
April 0.112776E+09 49380691.59 63395708.86 0.108067E+09 74680117.04
May 0.146523E+09 63998912.16 82524222.06 0.166901E+09 42268902.15
June 0.156062E+09 68002436.64 88059385.55 0.199363E+09 26290252.50
July 0.162958E+09 75297869.26 87659972.69 0.213650E+09 22886538.88
August 0.137175E+09 59024149.09 78150762.09 0.179216E+09 27819318.48
September 0.118942E+09 56346263.19 62595410.10 0.143173E+09 47916150.35
October 77940706.36 32460842.65 45479863.71 67112347.66 81093730.38
November 44628954.05 14506968.64 30121985.40 21467140.08 0.127180E+09
December 35516489.11 15167996.63 20348492.48 14283245.18 0.190595E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.123727E+10 0.111100E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 14283245.18 22886538.88
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.213650E+09 0.209449E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM315_318_3_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 20752559.82 0.209449E+09
February 62935916.04 27536246.10 35399669.94 33490077.99 0.151117E+09
March 94964621.74 37596731.77 57367889.97 69794039.98 0.109702E+09
April 0.112776E+09 49380691.59 63395708.86 0.108067E+09 74680117.04
May 0.146523E+09 63998912.16 82524222.06 0.166901E+09 42268902.15
June 0.156062E+09 68002436.64 88059385.55 0.199363E+09 26290252.50
July 0.162958E+09 75297869.26 87659972.69 0.213650E+09 22886538.88
August 0.137175E+09 59024149.09 78150762.09 0.179216E+09 27819318.48
September 0.118942E+09 56346263.19 62595410.10 0.143173E+09 47916150.35
October 77940706.36 32460842.65 45479863.71 67112347.66 81093730.38
November 44628954.05 14506968.64 30121985.40 21467140.08 0.127180E+09
December 35516489.11 15167996.63 20348492.48 14283245.18 0.190595E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.123727E+10 0.111100E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 14283245.18 22886538.88
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.213650E+09 0.209449E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM319_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 20277882.71 0.213034E+09
February 62935916.04 27536246.10 35399669.94 32672482.76 0.156208E+09
March 94964621.74 37596731.77 57367889.97 67937043.34 0.115983E+09
April 0.112776E+09 49380691.59 63395708.86 0.104562E+09 82314524.50
May 0.146523E+09 63998912.16 82524222.06 0.159739E+09 50420706.65
June 0.156062E+09 68002436.64 88059385.55 0.190417E+09 33533422.35
July 0.162958E+09 75297869.26 87659972.69 0.203930E+09 30180036.59
August 0.137175E+09 59024149.09 78150762.09 0.170425E+09 35835930.23
September 0.118942E+09 56346263.19 62595410.10 0.137133E+09 56547316.24
October 77940706.36 32460842.65 45479863.71 64592323.17 89364488.90
November 44628954.05 14506968.64 30121985.40 20522394.54 0.133273E+09
December 35516489.11 15167996.63 20348492.48 13924720.75 0.194341E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.118613E+10 0.119103E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 13924720.75 30180036.59
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.203930E+09 0.213034E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM320_323_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 21695514.15 0.200048E+09
February 62935916.04 27536246.10 35399669.94 34876960.43 0.143345E+09
March 94964621.74 37596731.77 57367889.97 72737393.44 0.103302E+09
April 0.112776E+09 49380691.59 63395708.86 0.110925E+09 69542476.47
May 0.146523E+09 63998912.16 82524222.06 0.170734E+09 38729928.48
June 0.156062E+09 68002436.64 88059385.55 0.203123E+09 23351863.58
July 0.162958E+09 75297869.26 87659972.69 0.217564E+09 19941217.76
August 0.137175E+09 59024149.09 78150762.09 0.182898E+09 24519988.11
September 0.118942E+09 56346263.19 62595410.10 0.146182E+09 44028353.05
October 77940706.36 32460842.65 45479863.71 69985869.67 76095992.49
November 44628954.05 14506968.64 30121985.40 22855628.29 0.119541E+09
December 35516489.11 15167996.63 20348492.48 14921793.54 0.180874E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.126850E+10 0.104332E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 14921793.54 19941217.76
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.217564E+09 0.200048E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM320_323_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 21695514.15 0.200048E+09
February 62935916.04 27536246.10 35399669.94 34876960.43 0.143345E+09
March 94964621.74 37596731.77 57367889.97 72737393.44 0.103302E+09
April 0.112776E+09 49380691.59 63395708.86 0.110925E+09 69542476.47
May 0.146523E+09 63998912.16 82524222.06 0.170734E+09 38729928.48
June 0.156062E+09 68002436.64 88059385.55 0.203123E+09 23351863.58
July 0.162958E+09 75297869.26 87659972.69 0.217564E+09 19941217.76
August 0.137175E+09 59024149.09 78150762.09 0.182898E+09 24519988.11
September 0.118942E+09 56346263.19 62595410.10 0.146182E+09 44028353.05
October 77940706.36 32460842.65 45479863.71 69985869.67 76095992.49
November 44628954.05 14506968.64 30121985.40 22855628.29 0.119541E+09
December 35516489.11 15167996.63 20348492.48 14921793.54 0.180874E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.126850E+10 0.104332E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 14921793.54 19941217.76
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.217564E+09 0.200048E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM320_323_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 21695514.15 0.200048E+09
February 62935916.04 27536246.10 35399669.94 34876960.43 0.143345E+09
March 94964621.74 37596731.77 57367889.97 72737393.44 0.103302E+09
April 0.112776E+09 49380691.59 63395708.86 0.110925E+09 69542476.47
May 0.146523E+09 63998912.16 82524222.06 0.170734E+09 38729928.48
June 0.156062E+09 68002436.64 88059385.55 0.203123E+09 23351863.58
July 0.162958E+09 75297869.26 87659972.69 0.217564E+09 19941217.76
August 0.137175E+09 59024149.09 78150762.09 0.182898E+09 24519988.11
September 0.118942E+09 56346263.19 62595410.10 0.146182E+09 44028353.05
October 77940706.36 32460842.65 45479863.71 69985869.67 76095992.49
November 44628954.05 14506968.64 30121985.40 22855628.29 0.119541E+09
December 35516489.11 15167996.63 20348492.48 14921793.54 0.180874E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.126850E+10 0.104332E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 14921793.54 19941217.76
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.217564E+09 0.200048E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM320_323_3_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 21695514.15 0.200048E+09
February 62935916.04 27536246.10 35399669.94 34876960.43 0.143345E+09
March 94964621.74 37596731.77 57367889.97 72737393.44 0.103302E+09
April 0.112776E+09 49380691.59 63395708.86 0.110925E+09 69542476.47
May 0.146523E+09 63998912.16 82524222.06 0.170734E+09 38729928.48
June 0.156062E+09 68002436.64 88059385.55 0.203123E+09 23351863.58
July 0.162958E+09 75297869.26 87659972.69 0.217564E+09 19941217.76
August 0.137175E+09 59024149.09 78150762.09 0.182898E+09 24519988.11
September 0.118942E+09 56346263.19 62595410.10 0.146182E+09 44028353.05
October 77940706.36 32460842.65 45479863.71 69985869.67 76095992.49
November 44628954.05 14506968.64 30121985.40 22855628.29 0.119541E+09
December 35516489.11 15167996.63 20348492.48 14921793.54 0.180874E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.126850E+10 0.104332E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 14921793.54 19941217.76
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.217564E+09 0.200048E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM324_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 23056265.03 0.185596E+09
February 62935916.04 27536246.10 35399669.94 36419089.99 0.133345E+09
March 94964621.74 37596731.77 57367889.97 74692618.28 98074112.12
April 0.112776E+09 49380691.59 63395708.86 0.111018E+09 68840678.73
May 0.146523E+09 63998912.16 82524222.06 0.167886E+09 41933524.32
June 0.156062E+09 68002436.64 88059385.55 0.197298E+09 27297891.44
July 0.162958E+09 75297869.26 87659972.69 0.210854E+09 24356172.36
August 0.137175E+09 59024149.09 78150762.09 0.177373E+09 29097095.88
September 0.118942E+09 56346263.19 62595410.10 0.143250E+09 47747108.82
October 77940706.36 32460842.65 45479863.71 70758618.23 76282639.83
November 44628954.05 14506968.64 30121985.40 23697487.41 0.113284E+09
December 35516489.11 15167996.63 20348492.48 15704792.35 0.167922E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.125201E+10 0.101378E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 15704792.35 24356172.36
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.210854E+09 0.185596E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_CORRIDORFLR4_2_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.121837E+09 83318398.15 38518973.27 0.106295E+09 0.146180E+09
February 0.119916E+09 81633068.74 38282857.55 0.110216E+09 0.105711E+09
March 0.112139E+09 58308630.86 53830002.05 0.108023E+09 83420465.71
April 99615629.23 46816771.60 52798857.63 0.107936E+09 59190875.53
May 84904501.91 23037658.86 61866843.05 97284704.80 35876613.27
June 79705522.24 16198463.65 63507058.59 0.101977E+09 22543740.41
July 87542987.82 22286821.46 65256166.36 0.117154E+09 19804058.41
August 96228096.39 33194872.11 63033224.28 0.130264E+09 24121065.06
September 0.113765E+09 59237649.66 54527402.55 0.145189E+09 38531407.41
October 0.125344E+09 78981980.71 46362479.99 0.140314E+09 61146041.04
November 90835706.31 56858615.09 33977091.22 85072341.03 90751211.42
December 99573649.27 75314095.27 24259554.00 94301371.42 0.135076E+09
           
Annual Sum or Average 0.123141E+10 0.635187E+09 0.596221E+09 0.134403E+10 0.822352E+09
Minimum of Months 79705522.24 16198463.65 24259554.00 85072341.03 19804058.41
Maximum of Months 0.125344E+09 83318398.15 65256166.36 0.145189E+09 0.146180E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_CORRIDORFLR4_15_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 19610029.31 0.00 19610029.31 25637.03 0.181901E+09
February 22455712.01 0.00 22455712.01 677523.41 0.132314E+09
March 37266677.14 1010.90 37265666.24 10397373.65 92259784.38
April 41723531.10 283946.25 41439584.85 21960771.77 59974183.67
May 56182114.19 2175662.54 54006451.65 48579436.24 33280426.79
June 63402171.80 5727469.14 57674702.65 72360821.13 21132952.32
July 61461961.32 4123825.70 57338135.62 73183441.03 18849116.92
August 51661636.28 1076297.01 50585339.27 60499017.16 22942013.25
September 38233270.48 25544.51 38207725.97 35276146.17 39357284.33
October 29346564.00 0.00 29346564.00 12716335.65 66512369.31
November 19866023.67 0.00 19866023.67 2806011.01 0.104753E+09
December 13315836.12 0.00 13315836.12 1730.42 0.160018E+09
           
Annual Sum or Average 0.454526E+09 13413756.05 0.441112E+09 0.338484E+09 0.933294E+09
Minimum of Months 13315836.12 0.00 13315836.12 1730.42 18849116.92
Maximum of Months 63402171.80 5727469.14 57674702.65 73183441.03 0.181901E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM401_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 24870634.94 0.191732E+09
February 68924134.55 33807939.06 35116195.48 46553714.80 0.137693E+09
March 91625245.77 34132416.35 57492829.42 73335108.00 97518260.71
April 0.129261E+09 63875991.27 65385081.43 0.136263E+09 64874674.61
May 0.133932E+09 53510203.67 80422078.98 0.154760E+09 37856087.68
June 0.151852E+09 65685754.02 86165974.55 0.194915E+09 22961267.56
July 0.168834E+09 80236719.61 88597650.50 0.222611E+09 20172946.00
August 0.147147E+09 67297870.25 79849060.43 0.194571E+09 24870625.75
September 0.115554E+09 54781957.48 60771914.63 0.141349E+09 42313315.26
October 83575563.73 37254627.14 46320936.60 82175448.05 72077293.11
November 48381292.70 17970194.22 30411098.49 32209152.97 0.111454E+09
December 38613006.01 18364276.38 20248729.63 22441163.68 0.171345E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.132605E+10 0.994869E+09
Minimum of Months 38613006.01 17970194.22 20248729.63 22441163.68 20172946.00
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.222611E+09 0.191732E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM402_405_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 26226412.84 0.170862E+09
February 68924134.55 33807939.06 35116195.48 48118625.89 0.122429E+09
March 91625245.77 34132416.35 57492829.42 74671783.19 87223789.05
April 0.129261E+09 63875991.27 65385081.43 0.134815E+09 63112060.55
May 0.133932E+09 53510203.67 80422078.98 0.151057E+09 41831201.18
June 0.151852E+09 65685754.02 86165974.55 0.188052E+09 28838388.83
July 0.168834E+09 80236719.61 88597650.50 0.214505E+09 27001749.40
August 0.147147E+09 67297870.25 79849060.43 0.187483E+09 31430530.89
September 0.115554E+09 54781957.48 60771914.63 0.137563E+09 46330704.36
October 83575563.73 37254627.14 46320936.60 82158718.44 69078646.82
November 48381292.70 17970194.22 30411098.49 32932485.81 99497024.46
December 38613006.01 18364276.38 20248729.63 23230550.19 0.150881E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.130081E+10 0.938516E+09
Minimum of Months 38613006.01 17970194.22 20248729.63 23230550.19 27001749.40
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.214505E+09 0.170862E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM402_405_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 26226412.84 0.170862E+09
February 68924134.55 33807939.06 35116195.48 48118625.89 0.122429E+09
March 91625245.77 34132416.35 57492829.42 74671783.19 87223789.05
April 0.129261E+09 63875991.27 65385081.43 0.134815E+09 63112060.55
May 0.133932E+09 53510203.67 80422078.98 0.151057E+09 41831201.18
June 0.151852E+09 65685754.02 86165974.55 0.188052E+09 28838388.83
July 0.168834E+09 80236719.61 88597650.50 0.214505E+09 27001749.40
August 0.147147E+09 67297870.25 79849060.43 0.187483E+09 31430530.89
September 0.115554E+09 54781957.48 60771914.63 0.137563E+09 46330704.36
October 83575563.73 37254627.14 46320936.60 82158718.44 69078646.82
November 48381292.70 17970194.22 30411098.49 32932485.81 99497024.46
December 38613006.01 18364276.38 20248729.63 23230550.19 0.150881E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.130081E+10 0.938516E+09
Minimum of Months 38613006.01 17970194.22 20248729.63 23230550.19 27001749.40
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.214505E+09 0.170862E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM402_405_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 26226412.84 0.170862E+09
February 68924134.55 33807939.06 35116195.48 48118625.89 0.122429E+09
March 91625245.77 34132416.35 57492829.42 74671783.19 87223789.05
April 0.129261E+09 63875991.27 65385081.43 0.134815E+09 63112060.55
May 0.133932E+09 53510203.67 80422078.98 0.151057E+09 41831201.18
June 0.151852E+09 65685754.02 86165974.55 0.188052E+09 28838388.83
July 0.168834E+09 80236719.61 88597650.50 0.214505E+09 27001749.40
August 0.147147E+09 67297870.25 79849060.43 0.187483E+09 31430530.89
September 0.115554E+09 54781957.48 60771914.63 0.137563E+09 46330704.36
October 83575563.73 37254627.14 46320936.60 82158718.44 69078646.82
November 48381292.70 17970194.22 30411098.49 32932485.81 99497024.46
December 38613006.01 18364276.38 20248729.63 23230550.19 0.150881E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.130081E+10 0.938516E+09
Minimum of Months 38613006.01 17970194.22 20248729.63 23230550.19 27001749.40
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.214505E+09 0.170862E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM402_405_5_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 26226412.84 0.170862E+09
February 68924134.55 33807939.06 35116195.48 48118625.89 0.122429E+09
March 91625245.77 34132416.35 57492829.42 74671783.19 87223789.05
April 0.129261E+09 63875991.27 65385081.43 0.134815E+09 63112060.55
May 0.133932E+09 53510203.67 80422078.98 0.151057E+09 41831201.18
June 0.151852E+09 65685754.02 86165974.55 0.188052E+09 28838388.83
July 0.168834E+09 80236719.61 88597650.50 0.214505E+09 27001749.40
August 0.147147E+09 67297870.25 79849060.43 0.187483E+09 31430530.89
September 0.115554E+09 54781957.48 60771914.63 0.137563E+09 46330704.36
October 83575563.73 37254627.14 46320936.60 82158718.44 69078646.82
November 48381292.70 17970194.22 30411098.49 32932485.81 99497024.46
December 38613006.01 18364276.38 20248729.63 23230550.19 0.150881E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.130081E+10 0.938516E+09
Minimum of Months 38613006.01 17970194.22 20248729.63 23230550.19 27001749.40
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.214505E+09 0.170862E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM406_408_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 25899306.99 0.172297E+09
February 68924134.55 33807939.06 35116195.48 47474499.13 0.124167E+09
March 91625245.77 34132416.35 57492829.42 73409778.99 88967376.84
April 0.129261E+09 63875991.27 65385081.43 0.133698E+09 64412734.17
May 0.133932E+09 53510203.67 80422078.98 0.150308E+09 42210323.02
June 0.151852E+09 65685754.02 86165974.55 0.187697E+09 28845437.31
July 0.168834E+09 80236719.61 88597650.50 0.214234E+09 26905427.88
August 0.147147E+09 67297870.25 79849060.43 0.187183E+09 31379621.75
September 0.115554E+09 54781957.48 60771914.63 0.137037E+09 46643986.87
October 83575563.73 37254627.14 46320936.60 81155168.10 70348058.50
November 48381292.70 17970194.22 30411098.49 32333522.07 0.101123E+09
December 38613006.01 18364276.38 20248729.63 22908469.06 0.152412E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.129334E+10 0.949712E+09
Minimum of Months 38613006.01 17970194.22 20248729.63 22908469.06 26905427.88
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.214234E+09 0.172297E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM406_408_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 25899306.99 0.172297E+09
February 68924134.55 33807939.06 35116195.48 47474499.13 0.124167E+09
March 91625245.77 34132416.35 57492829.42 73409778.99 88967376.84
April 0.129261E+09 63875991.27 65385081.43 0.133698E+09 64412734.17
May 0.133932E+09 53510203.67 80422078.98 0.150308E+09 42210323.02
June 0.151852E+09 65685754.02 86165974.55 0.187697E+09 28845437.31
July 0.168834E+09 80236719.61 88597650.50 0.214234E+09 26905427.88
August 0.147147E+09 67297870.25 79849060.43 0.187183E+09 31379621.75
September 0.115554E+09 54781957.48 60771914.63 0.137037E+09 46643986.87
October 83575563.73 37254627.14 46320936.60 81155168.10 70348058.50
November 48381292.70 17970194.22 30411098.49 32333522.07 0.101123E+09
December 38613006.01 18364276.38 20248729.63 22908469.06 0.152412E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.129334E+10 0.949712E+09
Minimum of Months 38613006.01 17970194.22 20248729.63 22908469.06 26905427.88
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.214234E+09 0.172297E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM406_408_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.108559E+09 44038753.72 64520593.19 53618548.90 0.356428E+09
February 0.142635E+09 69963780.99 72670949.75 98275113.39 0.256858E+09
March 0.189613E+09 70635269.95 0.118978E+09 0.151961E+09 0.184044E+09
April 0.267499E+09 0.132188E+09 0.135311E+09 0.276720E+09 0.133250E+09
May 0.277165E+09 0.110737E+09 0.166429E+09 0.311096E+09 87324359.02
June 0.314249E+09 0.135933E+09 0.178315E+09 0.388464E+09 59676541.23
July 0.349393E+09 0.166046E+09 0.183348E+09 0.443382E+09 55665380.13
August 0.304512E+09 0.139269E+09 0.165243E+09 0.387402E+09 64919353.90
September 0.239132E+09 0.113368E+09 0.125764E+09 0.283620E+09 96500957.18
October 0.172955E+09 77096523.65 95858525.86 0.167980E+09 0.145535E+09
November 0.100122E+09 37188387.32 62934043.31 66932936.96 0.209191E+09
December 79907503.50 38003919.97 41903583.53 47421641.52 0.315294E+09
           
Annual Sum or Average 0.254574E+10 0.113447E+10 0.141128E+10 0.267687E+10 0.196469E+10
Minimum of Months 79907503.50 37188387.32 41903583.53 47421641.52 55665380.13
Maximum of Months 0.349393E+09 0.166046E+09 0.183348E+09 0.443382E+09 0.356428E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM409_412_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 23912201.07 0.198384E+09
February 68924134.55 33807939.06 35116195.48 44830078.39 0.143362E+09
March 91625245.77 34132416.35 57492829.42 69994196.73 0.102271E+09
April 0.129261E+09 63875991.27 65385081.43 0.133901E+09 67989118.44
May 0.133932E+09 53510203.67 80422078.98 0.153866E+09 38676253.51
June 0.151852E+09 65685754.02 86165974.55 0.195320E+09 22926188.18
July 0.168834E+09 80236719.61 88597650.50 0.223340E+09 19810785.47
August 0.147147E+09 67297870.25 79849060.43 0.195095E+09 24698563.92
September 0.115554E+09 54781957.48 60771914.63 0.140333E+09 43356239.31
October 83575563.73 37254627.14 46320936.60 79076892.65 75627003.85
November 48381292.70 17970194.22 30411098.49 30262789.49 0.116756E+09
December 38613006.01 18364276.38 20248729.63 21451762.65 0.178204E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.131138E+10 0.103206E+10
Minimum of Months 38613006.01 17970194.22 20248729.63 21451762.65 19810785.47
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.223340E+09 0.198384E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM409_412_5_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 23912201.07 0.198384E+09
February 68924134.55 33807939.06 35116195.48 44830078.39 0.143362E+09
March 91625245.77 34132416.35 57492829.42 69994196.73 0.102271E+09
April 0.129261E+09 63875991.27 65385081.43 0.133901E+09 67989118.44
May 0.133932E+09 53510203.67 80422078.98 0.153866E+09 38676253.51
June 0.151852E+09 65685754.02 86165974.55 0.195320E+09 22926188.18
July 0.168834E+09 80236719.61 88597650.50 0.223340E+09 19810785.47
August 0.147147E+09 67297870.25 79849060.43 0.195095E+09 24698563.92
September 0.115554E+09 54781957.48 60771914.63 0.140333E+09 43356239.31
October 83575563.73 37254627.14 46320936.60 79076892.65 75627003.85
November 48381292.70 17970194.22 30411098.49 30262789.49 0.116756E+09
December 38613006.01 18364276.38 20248729.63 21451762.65 0.178204E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.131138E+10 0.103206E+10
Minimum of Months 38613006.01 17970194.22 20248729.63 21451762.65 19810785.47
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.223340E+09 0.198384E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM409_412_5_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 23912201.07 0.198384E+09
February 68924134.55 33807939.06 35116195.48 44830078.39 0.143362E+09
March 91625245.77 34132416.35 57492829.42 69994196.73 0.102271E+09
April 0.129261E+09 63875991.27 65385081.43 0.133901E+09 67989118.44
May 0.133932E+09 53510203.67 80422078.98 0.153866E+09 38676253.51
June 0.151852E+09 65685754.02 86165974.55 0.195320E+09 22926188.18
July 0.168834E+09 80236719.61 88597650.50 0.223340E+09 19810785.47
August 0.147147E+09 67297870.25 79849060.43 0.195095E+09 24698563.92
September 0.115554E+09 54781957.48 60771914.63 0.140333E+09 43356239.31
October 83575563.73 37254627.14 46320936.60 79076892.65 75627003.85
November 48381292.70 17970194.22 30411098.49 30262789.49 0.116756E+09
December 38613006.01 18364276.38 20248729.63 21451762.65 0.178204E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.131138E+10 0.103206E+10
Minimum of Months 38613006.01 17970194.22 20248729.63 21451762.65 19810785.47
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.223340E+09 0.198384E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM409_412_5_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 23912201.07 0.198384E+09
February 68924134.55 33807939.06 35116195.48 44830078.39 0.143362E+09
March 91625245.77 34132416.35 57492829.42 69994196.73 0.102271E+09
April 0.129261E+09 63875991.27 65385081.43 0.133901E+09 67989118.44
May 0.133932E+09 53510203.67 80422078.98 0.153866E+09 38676253.51
June 0.151852E+09 65685754.02 86165974.55 0.195320E+09 22926188.18
July 0.168834E+09 80236719.61 88597650.50 0.223340E+09 19810785.47
August 0.147147E+09 67297870.25 79849060.43 0.195095E+09 24698563.92
September 0.115554E+09 54781957.48 60771914.63 0.140333E+09 43356239.31
October 83575563.73 37254627.14 46320936.60 79076892.65 75627003.85
November 48381292.70 17970194.22 30411098.49 30262789.49 0.116756E+09
December 38613006.01 18364276.38 20248729.63 21451762.65 0.178204E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.131138E+10 0.103206E+10
Minimum of Months 38613006.01 17970194.22 20248729.63 21451762.65 19810785.47
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.223340E+09 0.198384E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM413_5_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52458189.72 21280432.27 31177757.46 26105324.53 0.171560E+09
February 68924134.55 33807939.06 35116195.48 48052177.20 0.122960E+09
March 91625245.77 34132416.35 57492829.42 75272533.77 86981754.44
April 0.129261E+09 63875991.27 65385081.43 0.136245E+09 61582056.18
May 0.133932E+09 53510203.67 80422078.98 0.153595E+09 40275517.35
June 0.151852E+09 65685754.02 86165974.55 0.190390E+09 27323726.97
July 0.168834E+09 80236719.61 88597650.50 0.216744E+09 25612747.95
August 0.147147E+09 67297870.25 79849060.43 0.189526E+09 30175189.93
September 0.115554E+09 54781957.48 60771914.63 0.138877E+09 45465127.40
October 83575563.73 37254627.14 46320936.60 82659721.88 69000864.12
November 48381292.70 17970194.22 30411098.49 33073494.69 99706954.09
December 38613006.01 18364276.38 20248729.63 23136184.32 0.151685E+09
           
Annual Sum or Average 0.123016E+10 0.548198E+09 0.681959E+09 0.131368E+10 0.932329E+09
Minimum of Months 38613006.01 17970194.22 20248729.63 23136184.32 25612747.95
Maximum of Months 0.168834E+09 80236719.61 88597650.50 0.216744E+09 0.171560E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM414_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 24492575.12 0.172989E+09
February 62935916.04 27536246.10 35399669.94 37817247.97 0.124447E+09
March 94964621.74 37596731.77 57367889.97 76152847.43 90716402.75
April 0.112776E+09 49380691.59 63395708.86 0.110295E+09 63977389.68
May 0.146523E+09 63998912.16 82524222.06 0.165584E+09 40317828.91
June 0.156062E+09 68002436.64 88059385.55 0.193715E+09 26674708.04
July 0.162958E+09 75297869.26 87659972.69 0.206500E+09 24393740.94
August 0.137175E+09 59024149.09 78150762.09 0.173519E+09 29069394.43
September 0.118942E+09 56346263.19 62595410.10 0.141399E+09 45715938.24
October 77940706.36 32460842.65 45479863.71 71790196.73 71353262.60
November 44628954.05 14506968.64 30121985.40 25076626.28 0.103736E+09
December 35516489.11 15167996.63 20348492.48 16761231.77 0.154932E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.124310E+10 0.948323E+09
Minimum of Months 35516489.11 14506968.64 20348492.48 16761231.77 24393740.94
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.206500E+09 0.172989E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM415_418_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 21826301.97 0.197026E+09
February 62935916.04 27536246.10 35399669.94 34728468.55 0.141400E+09
March 94964621.74 37596731.77 57367889.97 71651320.77 0.101865E+09
April 0.112776E+09 49380691.59 63395708.86 0.109165E+09 68104824.24
May 0.146523E+09 63998912.16 82524222.06 0.168033E+09 37689595.40
June 0.156062E+09 68002436.64 88059385.55 0.200303E+09 22562557.27
July 0.162958E+09 75297869.26 87659972.69 0.214531E+09 19252742.43
August 0.137175E+09 59024149.09 78150762.09 0.180130E+09 23861905.32
September 0.118942E+09 56346263.19 62595410.10 0.144265E+09 42808239.32
October 77940706.36 32460842.65 45479863.71 68851962.92 74479433.76
November 44628954.05 14506968.64 30121985.40 22618226.99 0.117537E+09
December 35516489.11 15167996.63 20348492.48 14967293.56 0.178194E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.125107E+10 0.102478E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 14967293.56 19252742.43
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.214531E+09 0.197026E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM415_418_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 21826301.97 0.197026E+09
February 62935916.04 27536246.10 35399669.94 34728468.55 0.141400E+09
March 94964621.74 37596731.77 57367889.97 71651320.77 0.101865E+09
April 0.112776E+09 49380691.59 63395708.86 0.109165E+09 68104824.24
May 0.146523E+09 63998912.16 82524222.06 0.168033E+09 37689595.40
June 0.156062E+09 68002436.64 88059385.55 0.200303E+09 22562557.27
July 0.162958E+09 75297869.26 87659972.69 0.214531E+09 19252742.43
August 0.137175E+09 59024149.09 78150762.09 0.180130E+09 23861905.32
September 0.118942E+09 56346263.19 62595410.10 0.144265E+09 42808239.32
October 77940706.36 32460842.65 45479863.71 68851962.92 74479433.76
November 44628954.05 14506968.64 30121985.40 22618226.99 0.117537E+09
December 35516489.11 15167996.63 20348492.48 14967293.56 0.178194E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.125107E+10 0.102478E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 14967293.56 19252742.43
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.214531E+09 0.197026E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM415_418_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 21826301.97 0.197026E+09
February 62935916.04 27536246.10 35399669.94 34728468.55 0.141400E+09
March 94964621.74 37596731.77 57367889.97 71651320.77 0.101865E+09
April 0.112776E+09 49380691.59 63395708.86 0.109165E+09 68104824.24
May 0.146523E+09 63998912.16 82524222.06 0.168033E+09 37689595.40
June 0.156062E+09 68002436.64 88059385.55 0.200303E+09 22562557.27
July 0.162958E+09 75297869.26 87659972.69 0.214531E+09 19252742.43
August 0.137175E+09 59024149.09 78150762.09 0.180130E+09 23861905.32
September 0.118942E+09 56346263.19 62595410.10 0.144265E+09 42808239.32
October 77940706.36 32460842.65 45479863.71 68851962.92 74479433.76
November 44628954.05 14506968.64 30121985.40 22618226.99 0.117537E+09
December 35516489.11 15167996.63 20348492.48 14967293.56 0.178194E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.125107E+10 0.102478E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 14967293.56 19252742.43
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.214531E+09 0.197026E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM415_418_3_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 21826301.97 0.197026E+09
February 62935916.04 27536246.10 35399669.94 34728468.55 0.141400E+09
March 94964621.74 37596731.77 57367889.97 71651320.77 0.101865E+09
April 0.112776E+09 49380691.59 63395708.86 0.109165E+09 68104824.24
May 0.146523E+09 63998912.16 82524222.06 0.168033E+09 37689595.40
June 0.156062E+09 68002436.64 88059385.55 0.200303E+09 22562557.27
July 0.162958E+09 75297869.26 87659972.69 0.214531E+09 19252742.43
August 0.137175E+09 59024149.09 78150762.09 0.180130E+09 23861905.32
September 0.118942E+09 56346263.19 62595410.10 0.144265E+09 42808239.32
October 77940706.36 32460842.65 45479863.71 68851962.92 74479433.76
November 44628954.05 14506968.64 30121985.40 22618226.99 0.117537E+09
December 35516489.11 15167996.63 20348492.48 14967293.56 0.178194E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.125107E+10 0.102478E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 14967293.56 19252742.43
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.214531E+09 0.197026E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM419_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 21484931.52 0.199801E+09
February 62935916.04 27536246.10 35399669.94 34390651.90 0.143479E+09
March 94964621.74 37596731.77 57367889.97 71279712.20 0.103457E+09
April 0.112776E+09 49380691.59 63395708.86 0.108822E+09 69414824.86
May 0.146523E+09 63998912.16 82524222.06 0.167338E+09 38640921.69
June 0.156062E+09 68002436.64 88059385.55 0.199811E+09 23213721.26
July 0.162958E+09 75297869.26 87659972.69 0.214088E+09 19864417.87
August 0.137175E+09 59024149.09 78150762.09 0.179632E+09 24618307.80
September 0.118942E+09 56346263.19 62595410.10 0.143896E+09 43770384.16
October 77940706.36 32460842.65 45479863.71 68497795.26 75755978.72
November 44628954.05 14506968.64 30121985.40 22369818.86 0.119401E+09
December 35516489.11 15167996.63 20348492.48 14775042.93 0.180641E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.124638E+10 0.104206E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 14775042.93 19864417.87
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.214088E+09 0.199801E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM420_423_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 21898223.95 0.196197E+09
February 62935916.04 27536246.10 35399669.94 34953084.71 0.140337E+09
March 94964621.74 37596731.77 57367889.97 72350328.61 0.100763E+09
April 0.112776E+09 49380691.59 63395708.86 0.109916E+09 67181846.62
May 0.146523E+09 63998912.16 82524222.06 0.169073E+09 36941378.43
June 0.156062E+09 68002436.64 88059385.55 0.201428E+09 21896371.25
July 0.162958E+09 75297869.26 87659972.69 0.215721E+09 18527076.02
August 0.137175E+09 59024149.09 78150762.09 0.181242E+09 23070647.06
September 0.118942E+09 56346263.19 62595410.10 0.145119E+09 41967563.89
October 77940706.36 32460842.65 45479863.71 69581309.50 73518784.31
November 44628954.05 14506968.64 30121985.40 22911895.64 0.116368E+09
December 35516489.11 15167996.63 20348492.48 15043824.49 0.177097E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.125924E+10 0.101387E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 15043824.49 18527076.02
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.215721E+09 0.196197E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM420_423_3_0_0_0_1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 21898223.95 0.196197E+09
February 62935916.04 27536246.10 35399669.94 34953084.71 0.140337E+09
March 94964621.74 37596731.77 57367889.97 72350328.61 0.100763E+09
April 0.112776E+09 49380691.59 63395708.86 0.109916E+09 67181846.62
May 0.146523E+09 63998912.16 82524222.06 0.169073E+09 36941378.43
June 0.156062E+09 68002436.64 88059385.55 0.201428E+09 21896371.25
July 0.162958E+09 75297869.26 87659972.69 0.215721E+09 18527076.02
August 0.137175E+09 59024149.09 78150762.09 0.181242E+09 23070647.06
September 0.118942E+09 56346263.19 62595410.10 0.145119E+09 41967563.89
October 77940706.36 32460842.65 45479863.71 69581309.50 73518784.31
November 44628954.05 14506968.64 30121985.40 22911895.64 0.116368E+09
December 35516489.11 15167996.63 20348492.48 15043824.49 0.177097E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.125924E+10 0.101387E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 15043824.49 18527076.02
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.215721E+09 0.196197E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM420_423_3_0_0_0_2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 21898223.95 0.196197E+09
February 62935916.04 27536246.10 35399669.94 34953084.71 0.140337E+09
March 94964621.74 37596731.77 57367889.97 72350328.61 0.100763E+09
April 0.112776E+09 49380691.59 63395708.86 0.109916E+09 67181846.62
May 0.146523E+09 63998912.16 82524222.06 0.169073E+09 36941378.43
June 0.156062E+09 68002436.64 88059385.55 0.201428E+09 21896371.25
July 0.162958E+09 75297869.26 87659972.69 0.215721E+09 18527076.02
August 0.137175E+09 59024149.09 78150762.09 0.181242E+09 23070647.06
September 0.118942E+09 56346263.19 62595410.10 0.145119E+09 41967563.89
October 77940706.36 32460842.65 45479863.71 69581309.50 73518784.31
November 44628954.05 14506968.64 30121985.40 22911895.64 0.116368E+09
December 35516489.11 15167996.63 20348492.48 15043824.49 0.177097E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.125924E+10 0.101387E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 15043824.49 18527076.02
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.215721E+09 0.196197E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM420_423_3_0_0_0_3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 21898223.95 0.196197E+09
February 62935916.04 27536246.10 35399669.94 34953084.71 0.140337E+09
March 94964621.74 37596731.77 57367889.97 72350328.61 0.100763E+09
April 0.112776E+09 49380691.59 63395708.86 0.109916E+09 67181846.62
May 0.146523E+09 63998912.16 82524222.06 0.169073E+09 36941378.43
June 0.156062E+09 68002436.64 88059385.55 0.201428E+09 21896371.25
July 0.162958E+09 75297869.26 87659972.69 0.215721E+09 18527076.02
August 0.137175E+09 59024149.09 78150762.09 0.181242E+09 23070647.06
September 0.118942E+09 56346263.19 62595410.10 0.145119E+09 41967563.89
October 77940706.36 32460842.65 45479863.71 69581309.50 73518784.31
November 44628954.05 14506968.64 30121985.40 22911895.64 0.116368E+09
December 35516489.11 15167996.63 20348492.48 15043824.49 0.177097E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.125924E+10 0.101387E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 15043824.49 18527076.02
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.215721E+09 0.196197E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: W_GUESTROOM424_3_0_0_0_0

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52927752.82 21870185.22 31057567.60 22367205.95 0.192823E+09
February 62935916.04 27536246.10 35399669.94 35766422.78 0.137441E+09
March 94964621.74 37596731.77 57367889.97 74097091.87 98793366.67
April 0.112776E+09 49380691.59 63395708.86 0.110909E+09 66186122.27
May 0.146523E+09 63998912.16 82524222.06 0.169152E+09 37123285.25
June 0.156062E+09 68002436.64 88059385.55 0.200969E+09 22373957.68
July 0.162958E+09 75297869.26 87659972.69 0.215124E+09 19173881.18
August 0.137175E+09 59024149.09 78150762.09 0.180774E+09 23712694.80
September 0.118942E+09 56346263.19 62595410.10 0.145254E+09 42236147.08
October 77940706.36 32460842.65 45479863.71 70820342.28 72732473.33
November 44628954.05 14506968.64 30121985.40 23592169.91 0.113963E+09
December 35516489.11 15167996.63 20348492.48 15352948.17 0.173461E+09
           
Annual Sum or Average 0.120335E+10 0.521189E+09 0.682161E+09 0.126418E+10 0.100002E+10
Minimum of Months 35516489.11 14506968.64 20348492.48 15352948.17 19173881.18
Maximum of Months 0.162958E+09 75297869.26 88059385.55 0.215124E+09 0.192823E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: REARSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDORFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 45.50 467.72 139.83 76.71 63.12 0.00 0.00
February 76.00 383.75 167.52 91.96 75.56 0.00 0.00
March 97.62 276.57 169.14 65.42 103.73 0.00 0.00
April 168.50 207.27 195.96 77.61 118.34 0.00 0.00
May 183.70 114.30 192.83 52.78 140.04 0.00 0.00
June 252.47 75.86 216.51 60.86 155.66 0.00 0.00
July 276.38 62.23 225.22 70.58 154.64 0.00 0.00
August 253.68 77.15 206.65 67.72 138.93 0.00 0.00
September 215.63 136.26 195.64 81.37 114.27 0.00 0.00
October 132.24 214.25 169.29 83.13 86.15 0.00 0.00
November 57.86 322.37 116.47 56.27 60.20 0.00 0.00
December 49.81 435.23 110.01 68.81 41.20 0.00 0.00
               
Annual Sum or Average 151.15 230.32 175.42 70.95 104.47 0.00 0.00
Minimum of Months 45.50 62.23 110.01 52.78 41.20 0.00 0.00
Maximum of Months 276.38 467.72 225.22 91.96 155.66 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: REARSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONTLOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 79.25 670.80 176.47 71.59 104.88 0.00 0.00
February 167.84 535.55 256.70 125.91 130.78 0.00 0.00
March 237.75 348.31 308.22 114.82 193.40 0.00 0.00
April 470.35 250.48 449.32 222.04 227.28 0.00 0.00
May 523.86 148.53 450.54 180.00 270.53 0.00 0.00
June 683.69 98.61 527.85 228.33 299.52 0.00 0.00
July 757.09 82.92 567.95 269.91 298.04 0.00 0.00
August 660.08 100.20 494.99 226.39 268.61 0.00 0.00
September 485.41 177.60 401.67 190.43 211.25 0.00 0.00
October 257.97 287.62 281.14 125.32 155.82 0.00 0.00
November 100.83 428.05 168.18 62.47 105.71 0.00 0.00
December 70.73 607.81 129.89 61.78 68.12 0.00 0.00
               
Annual Sum or Average 375.61 310.33 351.46 156.62 194.84 0.00 0.00
Minimum of Months 70.73 82.92 129.89 61.78 68.12 0.00 0.00
Maximum of Months 757.09 670.80 567.95 269.91 299.52 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RESTROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MEETINGROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 25.67 232.70 58.64 23.79 34.85 0.00 0.00
February 54.79 187.23 85.31 41.84 43.46 0.00 0.00
March 78.14 122.83 102.43 38.16 64.27 0.00 0.00
April 156.01 88.10 149.32 73.79 75.53 0.00 0.00
May 172.74 52.22 149.72 59.82 89.90 0.00 0.00
June 225.49 34.55 175.41 75.88 99.54 0.00 0.00
July 249.69 29.16 188.74 89.70 99.04 0.00 0.00
August 217.79 35.43 164.49 75.23 89.26 0.00 0.00
September 160.65 61.97 133.48 63.28 70.20 0.00 0.00
October 86.76 99.26 93.43 41.65 51.78 0.00 0.00
November 33.44 149.57 55.89 20.76 35.13 0.00 0.00
December 23.09 211.61 43.17 20.53 22.64 0.00 0.00
               
Annual Sum or Average 124.03 108.35 116.80 52.05 64.75 0.00 0.00
Minimum of Months 23.09 29.16 43.17 20.53 22.64 0.00 0.00
Maximum of Months 249.69 232.70 188.74 89.70 99.54 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECHANICALROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM101

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 8.69 75.35 19.55 7.93 11.62 0.00 0.00
February 18.39 60.75 28.44 13.95 14.49 0.00 0.00
March 25.89 40.14 34.14 12.72 21.42 0.00 0.00
April 51.51 29.15 49.77 24.60 25.18 0.00 0.00
May 56.90 17.19 49.91 19.94 29.97 0.00 0.00
June 73.58 12.01 58.47 25.29 33.18 0.00 0.00
July 81.09 10.72 62.91 29.90 33.01 0.00 0.00
August 70.54 12.95 54.83 25.08 29.75 0.00 0.00
September 52.11 21.65 44.49 21.09 23.40 0.00 0.00
October 28.12 33.51 31.14 13.88 17.26 0.00 0.00
November 10.85 49.88 18.63 6.92 11.71 0.00 0.00
December 7.67 69.30 14.39 6.84 7.55 0.00 0.00
               
Annual Sum or Average 40.56 35.93 38.93 17.35 21.58 0.00 0.00
Minimum of Months 7.67 10.72 14.39 6.84 7.55 0.00 0.00
Maximum of Months 81.09 75.35 62.91 29.90 33.18 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM102

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 8.86 73.89 19.55 7.93 11.62 0.00 0.00
February 18.66 59.38 28.44 13.95 14.49 0.00 0.00
March 26.40 38.90 34.14 12.72 21.42 0.00 0.00
April 52.11 27.92 49.77 24.60 25.18 0.00 0.00
May 57.78 16.27 49.91 19.94 29.97 0.00 0.00
June 74.54 11.12 58.47 25.29 33.18 0.00 0.00
July 82.05 9.86 62.91 29.90 33.01 0.00 0.00
August 71.44 12.04 54.83 25.08 29.75 0.00 0.00
September 52.84 20.52 44.49 21.09 23.40 0.00 0.00
October 28.67 32.23 31.14 13.88 17.26 0.00 0.00
November 11.13 48.34 18.63 6.92 11.71 0.00 0.00
December 7.81 67.73 14.39 6.84 7.55 0.00 0.00
               
Annual Sum or Average 41.14 34.73 38.93 17.35 21.58 0.00 0.00
Minimum of Months 7.81 9.86 14.39 6.84 7.55 0.00 0.00
Maximum of Months 82.05 73.89 62.91 29.90 33.18 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM103

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 8.92 74.64 19.55 7.93 11.62 0.00 0.00
February 18.78 59.51 28.44 13.95 14.49 0.00 0.00
March 26.96 38.05 34.14 12.72 21.42 0.00 0.00
April 53.08 26.06 49.77 24.60 25.18 0.00 0.00
May 59.31 14.31 49.91 19.94 29.97 0.00 0.00
June 76.82 9.00 58.47 25.29 33.18 0.00 0.00
July 84.59 7.65 62.91 29.90 33.01 0.00 0.00
August 73.71 9.66 54.83 25.08 29.75 0.00 0.00
September 54.46 17.78 44.49 21.09 23.40 0.00 0.00
October 29.46 29.77 31.14 13.88 17.26 0.00 0.00
November 11.48 46.71 18.63 6.92 11.71 0.00 0.00
December 7.92 67.68 14.39 6.84 7.55 0.00 0.00
               
Annual Sum or Average 42.24 33.28 38.93 17.35 21.58 0.00 0.00
Minimum of Months 7.92 7.65 14.39 6.84 7.55 0.00 0.00
Maximum of Months 84.59 74.64 62.91 29.90 33.18 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM104

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 8.14 74.61 19.72 8.15 11.57 0.00 0.00
February 14.52 58.97 25.96 11.36 14.60 0.00 0.00
March 27.44 38.08 35.39 14.01 21.38 0.00 0.00
April 43.20 26.29 43.42 19.01 24.41 0.00 0.00
May 64.15 14.03 54.60 23.85 30.75 0.00 0.00
June 78.50 8.84 60.09 26.18 33.91 0.00 0.00
July 81.17 7.41 60.72 28.06 32.66 0.00 0.00
August 68.01 9.28 51.12 21.99 29.12 0.00 0.00
September 55.98 17.43 45.80 21.70 24.10 0.00 0.00
October 25.65 29.16 29.04 12.10 16.95 0.00 0.00
November 8.60 47.08 17.18 5.59 11.60 0.00 0.00
December 5.54 68.13 13.23 5.65 7.58 0.00 0.00
               
Annual Sum or Average 40.21 33.16 38.08 16.49 21.59 0.00 0.00
Minimum of Months 5.54 7.41 13.23 5.59 7.58 0.00 0.00
Maximum of Months 81.17 74.61 60.72 28.06 33.91 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM105

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 7.58 80.12 19.72 8.15 11.57 0.00 0.00
February 13.63 63.80 25.96 11.36 14.60 0.00 0.00
March 25.74 41.64 35.39 14.01 21.38 0.00 0.00
April 41.52 29.11 43.42 19.01 24.41 0.00 0.00
May 62.21 15.66 54.60 23.85 30.75 0.00 0.00
June 76.84 10.04 60.09 26.18 33.91 0.00 0.00
July 79.68 8.43 60.72 28.06 32.66 0.00 0.00
August 66.68 10.36 51.12 21.99 29.12 0.00 0.00
September 54.83 18.85 45.80 21.70 24.10 0.00 0.00
October 24.49 31.20 29.04 12.10 16.95 0.00 0.00
November 8.00 50.78 17.18 5.59 11.60 0.00 0.00
December 5.20 73.31 13.23 5.65 7.58 0.00 0.00
               
Annual Sum or Average 39.00 35.98 38.08 16.49 21.59 0.00 0.00
Minimum of Months 5.20 8.43 13.23 5.59 7.58 0.00 0.00
Maximum of Months 79.68 80.12 60.72 28.06 33.91 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: EMPLOYEELOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 6.77 91.20 19.72 8.15 11.57 0.00 0.00
February 12.34 74.67 25.96 11.36 14.60 0.00 0.00
March 22.85 51.36 35.39 14.01 21.38 0.00 0.00
April 37.97 37.84 43.42 19.01 24.41 0.00 0.00
May 57.06 21.83 54.60 23.85 30.75 0.00 0.00
June 71.47 15.56 60.09 26.18 33.91 0.00 0.00
July 74.39 13.43 60.72 28.06 32.66 0.00 0.00
August 61.78 15.77 51.12 21.99 29.12 0.00 0.00
September 50.78 25.96 45.80 21.70 24.10 0.00 0.00
October 21.31 40.23 29.04 12.10 16.95 0.00 0.00
November 6.70 61.99 17.18 5.59 11.60 0.00 0.00
December 4.57 85.04 13.23 5.65 7.58 0.00 0.00
               
Annual Sum or Average 35.79 44.43 38.08 16.49 21.59 0.00 0.00
Minimum of Months 4.57 13.43 13.23 5.59 7.58 0.00 0.00
Maximum of Months 74.39 91.20 60.72 28.06 33.91 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRYROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 7.59 499.07 59.17 24.45 34.72 0.00 0.00
February 18.85 440.67 77.89 34.08 43.81 0.00 0.00
March 39.29 358.19 106.16 42.03 64.13 0.00 0.00
April 70.98 306.41 130.27 57.04 73.23 0.00 0.00
May 95.15 226.70 163.80 71.54 92.25 0.00 0.00
June 120.82 193.61 180.28 78.55 101.72 0.00 0.00
July 126.61 184.22 182.17 84.18 97.99 0.00 0.00
August 94.49 197.15 153.35 65.98 87.36 0.00 0.00
September 87.97 253.98 137.40 65.09 72.31 0.00 0.00
October 31.46 325.88 87.13 36.29 50.84 0.00 0.00
November 7.78 412.32 51.55 16.76 34.80 0.00 0.00
December 5.57 483.03 39.70 16.96 22.75 0.00 0.00
               
Annual Sum or Average 59.07 322.82 114.25 49.48 64.77 0.00 0.00
Minimum of Months 5.57 184.22 39.70 16.76 22.75 0.00 0.00
Maximum of Months 126.61 499.07 182.17 84.18 101.72 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ELEVATORCOREFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: EXERCISECENTERFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 8.10 76.31 19.72 8.15 11.57 0.00 0.00
February 14.47 60.35 25.96 11.36 14.60 0.00 0.00
March 27.37 39.31 35.39 14.01 21.38 0.00 0.00
April 43.03 27.55 43.42 19.01 24.41 0.00 0.00
May 63.53 15.51 54.60 23.85 30.75 0.00 0.00
June 77.83 10.35 60.09 26.18 33.91 0.00 0.00
July 80.68 8.83 60.72 28.06 32.66 0.00 0.00
August 67.70 10.58 51.12 21.99 29.12 0.00 0.00
September 55.82 18.71 45.80 21.70 24.10 0.00 0.00
October 25.93 29.95 29.04 12.10 16.95 0.00 0.00
November 8.67 47.84 17.18 5.59 11.60 0.00 0.00
December 5.56 69.24 13.23 5.65 7.58 0.00 0.00
               
Annual Sum or Average 40.03 34.42 38.08 16.49 21.59 0.00 0.00
Minimum of Months 5.56 8.83 13.23 5.59 7.58 0.00 0.00
Maximum of Months 80.68 76.31 60.72 28.06 33.91 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONTOFFICEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 33.18 296.89 78.89 32.60 46.29 0.00 0.00
February 58.87 234.65 103.86 45.44 58.42 0.00 0.00
March 110.40 153.44 141.55 56.04 85.51 0.00 0.00
April 171.84 109.26 173.70 76.06 97.64 0.00 0.00
May 253.50 62.81 218.40 95.39 123.00 0.00 0.00
June 310.19 41.27 240.37 104.74 135.63 0.00 0.00
July 321.55 34.46 242.89 112.23 130.66 0.00 0.00
August 269.86 42.08 204.46 87.98 116.49 0.00 0.00
September 222.00 76.68 183.20 86.79 96.41 0.00 0.00
October 102.04 123.23 116.17 48.38 67.79 0.00 0.00
November 34.53 189.51 68.74 22.34 46.39 0.00 0.00
December 22.64 269.78 52.94 22.61 30.33 0.00 0.00
               
Annual Sum or Average 159.76 135.71 152.34 65.98 86.36 0.00 0.00
Minimum of Months 22.64 34.46 52.94 22.34 30.33 0.00 0.00
Maximum of Months 321.55 296.89 242.89 112.23 135.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONTSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONTSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: REARSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDORFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 29.33 119.00 52.81 31.11 21.70 0.00 0.00
February 36.94 96.58 58.85 33.74 25.11 0.00 0.00
March 40.67 69.65 55.78 21.77 34.01 0.00 0.00
April 48.44 51.73 54.53 18.17 36.36 0.00 0.00
May 52.47 29.40 52.68 9.41 43.26 0.00 0.00
June 65.86 18.93 55.21 8.46 46.75 0.00 0.00
July 70.26 15.86 55.63 9.86 45.77 0.00 0.00
August 70.50 19.63 55.22 12.80 42.42 0.00 0.00
September 67.97 34.67 58.64 22.86 35.78 0.00 0.00
October 53.05 53.91 57.76 29.49 28.27 0.00 0.00
November 28.59 79.14 42.71 21.94 20.77 0.00 0.00
December 27.89 109.92 42.15 28.12 14.03 0.00 0.00
               
Annual Sum or Average 49.40 58.02 53.46 20.57 32.89 0.00 0.00
Minimum of Months 27.89 15.86 42.15 8.46 14.03 0.00 0.00
Maximum of Months 70.50 119.00 58.85 33.74 46.75 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: REARSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM201

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 9.47 67.82 19.64 7.97 11.67 0.00 0.00
February 19.45 54.87 28.57 14.01 14.56 0.00 0.00
March 27.27 36.20 34.30 12.78 21.52 0.00 0.00
April 52.25 27.08 50.01 24.71 25.30 0.00 0.00
May 57.02 16.94 50.14 20.03 30.11 0.00 0.00
June 73.44 11.99 58.75 25.41 33.34 0.00 0.00
July 81.17 10.65 63.21 30.04 33.17 0.00 0.00
August 70.94 12.49 55.09 25.20 29.89 0.00 0.00
September 53.19 19.89 44.70 21.19 23.51 0.00 0.00
October 29.73 29.83 31.29 13.95 17.34 0.00 0.00
November 11.97 43.32 18.72 6.95 11.77 0.00 0.00
December 8.36 61.23 14.46 6.88 7.58 0.00 0.00
               
Annual Sum or Average 41.30 32.59 39.12 17.43 21.68 0.00 0.00
Minimum of Months 8.36 10.65 14.46 6.88 7.58 0.00 0.00
Maximum of Months 81.17 67.82 63.21 30.04 33.34 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM202_205

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 35.40 301.62 78.56 31.87 46.69 0.00 0.00
February 74.36 242.12 114.28 56.05 58.22 0.00 0.00
March 105.23 157.12 137.22 51.12 86.10 0.00 0.00
April 208.51 110.93 200.03 98.85 101.18 0.00 0.00
May 231.68 62.66 200.57 80.14 120.44 0.00 0.00
June 302.95 40.21 234.99 101.65 133.34 0.00 0.00
July 335.08 34.18 252.84 120.16 132.68 0.00 0.00
August 292.66 41.69 220.36 100.78 119.58 0.00 0.00
September 216.89 73.41 178.82 84.77 94.04 0.00 0.00
October 117.36 120.41 125.16 55.79 69.37 0.00 0.00
November 45.87 187.31 74.87 27.81 47.06 0.00 0.00
December 31.69 272.02 57.83 27.50 30.32 0.00 0.00
               
Annual Sum or Average 166.93 136.48 156.47 69.73 86.74 0.00 0.00
Minimum of Months 31.69 34.18 57.83 27.50 30.32 0.00 0.00
Maximum of Months 335.08 301.62 252.84 120.16 133.34 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM206_208

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 35.32 310.71 79.81 32.38 47.43 0.00 0.00
February 74.51 249.98 116.10 56.95 59.15 0.00 0.00
March 105.43 162.51 139.40 51.93 87.47 0.00 0.00
April 210.87 114.27 203.22 100.42 102.79 0.00 0.00
May 234.99 63.88 203.77 81.41 122.36 0.00 0.00
June 307.84 40.66 238.73 103.27 135.47 0.00 0.00
July 340.61 34.41 256.87 122.07 134.79 0.00 0.00
August 297.47 42.06 223.87 102.39 121.48 0.00 0.00
September 220.25 74.59 181.67 86.13 95.54 0.00 0.00
October 118.68 123.17 127.15 56.68 70.47 0.00 0.00
November 45.98 193.13 76.06 28.25 47.81 0.00 0.00
December 31.63 280.67 58.75 27.94 30.81 0.00 0.00
               
Annual Sum or Average 169.10 140.33 158.96 70.84 88.12 0.00 0.00
Minimum of Months 31.63 34.41 58.75 27.94 30.81 0.00 0.00
Maximum of Months 340.61 310.71 256.87 122.07 135.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM209_212

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 34.56 307.72 78.56 31.87 46.69 0.00 0.00
February 73.16 247.22 114.28 56.05 58.22 0.00 0.00
March 103.84 160.30 137.22 51.12 86.10 0.00 0.00
April 208.39 111.64 200.03 98.85 101.18 0.00 0.00
May 233.01 61.62 200.57 80.14 120.44 0.00 0.00
June 305.13 38.64 234.99 101.65 133.34 0.00 0.00
July 337.39 32.49 252.84 120.16 132.68 0.00 0.00
August 294.57 40.11 220.36 100.78 119.58 0.00 0.00
September 217.77 72.43 178.82 84.77 94.04 0.00 0.00
October 116.97 121.19 125.16 55.79 69.37 0.00 0.00
November 45.10 191.32 74.87 27.81 47.06 0.00 0.00
December 30.94 278.31 57.83 27.50 30.32 0.00 0.00
               
Annual Sum or Average 167.20 138.07 156.47 69.73 86.74 0.00 0.00
Minimum of Months 30.94 32.49 57.83 27.50 30.32 0.00 0.00
Maximum of Months 337.39 307.72 252.84 120.16 133.34 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM213

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 8.92 75.05 19.64 7.97 11.67 0.00 0.00
February 18.73 60.11 28.57 14.01 14.56 0.00 0.00
March 26.75 38.67 34.30 12.78 21.52 0.00 0.00
April 52.70 26.79 50.01 24.71 25.30 0.00 0.00
May 58.73 14.88 50.14 20.03 30.11 0.00 0.00
June 76.48 9.34 58.75 25.41 33.34 0.00 0.00
July 84.41 7.89 63.21 30.04 33.17 0.00 0.00
August 73.70 9.80 55.09 25.20 29.89 0.00 0.00
September 54.67 17.68 44.70 21.19 23.51 0.00 0.00
October 29.82 29.42 31.29 13.95 17.34 0.00 0.00
November 11.71 46.24 18.72 6.95 11.77 0.00 0.00
December 8.00 67.59 14.46 6.88 7.58 0.00 0.00
               
Annual Sum or Average 42.17 33.50 39.12 17.43 21.68 0.00 0.00
Minimum of Months 8.00 7.89 14.46 6.88 7.58 0.00 0.00
Maximum of Months 84.41 75.05 63.21 30.04 33.34 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM214

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 7.95 76.46 19.82 8.19 11.63 0.00 0.00
February 14.19 60.87 26.09 11.41 14.67 0.00 0.00
March 26.68 39.74 35.55 14.08 21.48 0.00 0.00
April 42.31 27.88 43.63 19.10 24.53 0.00 0.00
May 63.04 15.13 54.86 23.96 30.90 0.00 0.00
June 77.63 9.63 60.38 26.31 34.07 0.00 0.00
July 80.45 8.09 61.01 28.19 32.82 0.00 0.00
August 67.45 9.95 51.36 22.10 29.26 0.00 0.00
September 55.65 18.06 46.02 21.80 24.22 0.00 0.00
October 25.36 29.84 29.18 12.15 17.03 0.00 0.00
November 8.46 48.05 17.27 5.61 11.65 0.00 0.00
December 5.46 69.56 13.30 5.68 7.62 0.00 0.00
               
Annual Sum or Average 39.69 34.31 38.26 16.57 21.69 0.00 0.00
Minimum of Months 5.46 8.09 13.30 5.61 7.62 0.00 0.00
Maximum of Months 80.45 76.46 61.01 28.19 34.07 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM215_218

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 25.90 377.89 79.26 32.75 46.51 0.00 0.00
February 47.93 309.94 104.35 45.66 58.69 0.00 0.00
March 89.50 213.69 142.22 56.30 85.91 0.00 0.00
April 148.80 159.25 174.52 76.42 98.10 0.00 0.00
May 222.25 93.26 219.43 95.84 123.59 0.00 0.00
June 278.76 67.47 241.50 105.23 136.27 0.00 0.00
July 290.10 58.66 244.04 112.76 131.28 0.00 0.00
August 240.26 68.21 205.43 88.39 117.04 0.00 0.00
September 198.52 109.80 184.06 87.20 96.87 0.00 0.00
October 83.25 167.46 116.72 48.61 68.11 0.00 0.00
November 25.97 256.11 69.06 22.45 46.61 0.00 0.00
December 17.75 350.28 53.19 22.72 30.47 0.00 0.00
               
Annual Sum or Average 139.57 185.40 153.06 66.29 86.76 0.00 0.00
Minimum of Months 17.75 58.66 53.19 22.45 30.47 0.00 0.00
Maximum of Months 290.10 377.89 244.04 112.76 136.27 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ELEVATORCOREFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM219

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 6.58 91.57 19.82 8.19 11.63 0.00 0.00
February 12.18 75.92 26.09 11.41 14.67 0.00 0.00
March 22.89 50.30 35.55 14.08 21.48 0.00 0.00
April 37.81 37.27 43.63 19.10 24.53 0.00 0.00
May 56.39 22.17 54.86 23.96 30.90 0.00 0.00
June 70.73 15.75 60.38 26.31 34.07 0.00 0.00
July 73.34 13.92 61.01 28.19 32.82 0.00 0.00
August 60.81 16.40 51.36 22.10 29.26 0.00 0.00
September 50.51 25.95 46.02 21.80 24.22 0.00 0.00
October 21.44 39.17 29.18 12.15 17.03 0.00 0.00
November 6.81 60.57 17.27 5.61 11.65 0.00 0.00
December 4.65 83.60 13.30 5.68 7.62 0.00 0.00
               
Annual Sum or Average 35.47 44.23 38.26 16.57 21.69 0.00 0.00
Minimum of Months 4.65 13.92 13.30 5.61 7.62 0.00 0.00
Maximum of Months 73.34 91.57 61.01 28.19 34.07 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM220_223

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 32.18 303.09 79.26 32.75 46.51 0.00 0.00
February 57.35 240.63 104.35 45.66 58.69 0.00 0.00
March 107.96 156.63 142.22 56.30 85.91 0.00 0.00
April 170.80 109.30 174.52 76.42 98.10 0.00 0.00
May 254.60 58.88 219.43 95.84 123.59 0.00 0.00
June 313.31 36.94 241.50 105.23 136.27 0.00 0.00
July 324.86 30.54 244.04 112.76 131.28 0.00 0.00
August 272.81 37.55 205.43 88.39 117.04 0.00 0.00
September 224.82 69.86 184.06 87.20 96.87 0.00 0.00
October 103.02 116.69 116.72 48.61 68.11 0.00 0.00
November 34.53 188.92 69.06 22.45 46.61 0.00 0.00
December 22.10 274.93 53.19 22.72 30.47 0.00 0.00
               
Annual Sum or Average 160.42 134.84 153.06 66.29 86.76 0.00 0.00
Minimum of Months 22.10 30.54 53.19 22.45 30.47 0.00 0.00
Maximum of Months 324.86 303.09 244.04 112.76 136.27 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM224

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 8.15 74.47 19.82 8.19 11.63 0.00 0.00
February 14.54 58.96 26.09 11.41 14.67 0.00 0.00
March 27.34 38.41 35.55 14.08 21.48 0.00 0.00
April 42.87 26.91 43.63 19.10 24.53 0.00 0.00
May 63.53 14.62 54.86 23.96 30.90 0.00 0.00
June 78.04 9.26 60.38 26.31 34.07 0.00 0.00
July 80.88 7.71 61.01 28.19 32.82 0.00 0.00
August 67.89 9.47 51.36 22.10 29.26 0.00 0.00
September 56.06 17.46 46.02 21.80 24.22 0.00 0.00
October 25.86 28.94 29.18 12.15 17.03 0.00 0.00
November 8.73 46.47 17.27 5.61 11.65 0.00 0.00
December 5.59 67.43 13.30 5.68 7.62 0.00 0.00
               
Annual Sum or Average 40.09 33.22 38.26 16.57 21.69 0.00 0.00
Minimum of Months 5.59 7.71 13.30 5.61 7.62 0.00 0.00
Maximum of Months 80.88 74.47 61.01 28.19 34.07 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONTSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONTSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: REARSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDORFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 30.08 115.61 52.81 31.11 21.70 0.00 0.00
February 37.93 93.15 58.85 33.74 25.11 0.00 0.00
March 42.30 66.00 55.78 21.77 34.01 0.00 0.00
April 50.05 47.94 54.53 18.17 36.36 0.00 0.00
May 54.21 27.45 52.68 9.41 43.26 0.00 0.00
June 67.10 17.75 55.21 8.46 46.75 0.00 0.00
July 71.18 15.18 55.63 9.86 45.77 0.00 0.00
August 71.41 18.75 55.22 12.80 42.42 0.00 0.00
September 69.45 32.14 58.64 22.86 35.78 0.00 0.00
October 55.63 48.95 57.76 29.49 28.27 0.00 0.00
November 29.94 74.44 42.71 21.94 20.77 0.00 0.00
December 28.57 106.27 42.15 28.12 14.03 0.00 0.00
               
Annual Sum or Average 50.72 55.12 53.46 20.57 32.89 0.00 0.00
Minimum of Months 28.57 15.18 42.15 8.46 14.03 0.00 0.00
Maximum of Months 71.41 115.61 58.85 33.74 46.75 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: REARSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM301

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 9.74 65.17 19.59 7.95 11.64 0.00 0.00
February 19.95 52.06 28.49 13.97 14.52 0.00 0.00
March 28.25 33.81 34.21 12.74 21.47 0.00 0.00
April 53.02 25.34 49.87 24.64 25.23 0.00 0.00
May 57.75 16.28 50.00 19.98 30.03 0.00 0.00
June 73.81 11.64 58.58 25.34 33.24 0.00 0.00
July 81.39 10.48 63.04 29.96 33.08 0.00 0.00
August 71.31 12.19 54.94 25.13 29.81 0.00 0.00
September 53.98 18.75 44.58 21.14 23.45 0.00 0.00
October 30.99 27.23 31.20 13.91 17.29 0.00 0.00
November 12.70 40.07 18.67 6.93 11.73 0.00 0.00
December 8.66 57.78 14.42 6.86 7.56 0.00 0.00
               
Annual Sum or Average 41.90 30.80 39.01 17.38 21.62 0.00 0.00
Minimum of Months 8.66 10.48 14.42 6.86 7.56 0.00 0.00
Maximum of Months 81.39 65.17 63.04 29.96 33.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM302_305

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 38.07 270.05 78.34 31.78 46.56 0.00 0.00
February 78.24 218.08 113.96 55.90 58.06 0.00 0.00
March 110.22 143.98 136.84 50.97 85.86 0.00 0.00
April 209.63 108.37 199.48 98.57 100.90 0.00 0.00
May 229.02 68.51 200.02 79.91 120.10 0.00 0.00
June 294.21 48.78 234.34 101.37 132.97 0.00 0.00
July 324.65 43.90 252.14 119.83 132.31 0.00 0.00
August 284.24 51.06 219.75 100.50 119.25 0.00 0.00
September 214.19 78.87 178.32 84.54 93.78 0.00 0.00
October 121.77 115.26 124.81 55.64 69.18 0.00 0.00
November 49.32 168.97 74.66 27.73 46.93 0.00 0.00
December 33.75 242.14 57.67 27.43 30.24 0.00 0.00
               
Annual Sum or Average 166.04 129.42 156.03 69.53 86.50 0.00 0.00
Minimum of Months 33.75 43.90 57.67 27.43 30.24 0.00 0.00
Maximum of Months 324.65 270.05 252.14 119.83 132.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM306_308

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 38.07 279.96 79.70 32.33 47.37 0.00 0.00
February 78.44 226.79 115.94 56.87 59.07 0.00 0.00
March 110.26 150.41 139.21 51.86 87.35 0.00 0.00
April 211.73 112.64 202.94 100.29 102.65 0.00 0.00
May 232.10 70.20 203.49 81.30 122.19 0.00 0.00
June 299.14 49.39 238.41 103.13 135.28 0.00 0.00
July 330.29 44.25 256.52 121.91 134.61 0.00 0.00
August 289.08 51.61 223.57 102.25 121.32 0.00 0.00
September 217.40 80.53 181.42 86.01 95.41 0.00 0.00
October 122.65 119.28 126.98 56.60 70.38 0.00 0.00
November 49.30 175.82 75.96 28.21 47.75 0.00 0.00
December 33.76 251.64 58.67 27.90 30.77 0.00 0.00
               
Annual Sum or Average 168.12 133.94 158.74 70.74 88.00 0.00 0.00
Minimum of Months 33.76 44.25 58.67 27.90 30.77 0.00 0.00
Maximum of Months 330.29 279.96 256.52 121.91 135.28 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM309_312

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 34.94 303.32 78.34 31.78 46.56 0.00 0.00
February 73.64 243.50 113.96 55.90 58.06 0.00 0.00
March 104.74 157.73 136.84 50.97 85.86 0.00 0.00
April 208.66 109.71 199.48 98.57 100.90 0.00 0.00
May 233.23 61.04 200.02 79.91 120.10 0.00 0.00
June 305.07 38.08 234.34 101.37 132.97 0.00 0.00
July 337.27 32.00 252.14 119.83 132.31 0.00 0.00
August 294.75 39.41 219.75 100.50 119.25 0.00 0.00
September 218.66 70.58 178.32 84.54 93.78 0.00 0.00
October 118.69 117.89 124.81 55.64 69.18 0.00 0.00
November 46.22 186.41 74.66 27.73 46.93 0.00 0.00
December 31.41 273.22 57.67 27.43 30.24 0.00 0.00
               
Annual Sum or Average 167.74 135.57 156.03 69.53 86.50 0.00 0.00
Minimum of Months 31.41 32.00 57.67 27.43 30.24 0.00 0.00
Maximum of Months 337.27 303.32 252.14 119.83 132.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM313

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 9.51 67.23 19.59 7.95 11.64 0.00 0.00
February 19.55 54.23 28.49 13.97 14.52 0.00 0.00
March 27.73 35.37 34.21 12.74 21.47 0.00 0.00
April 52.87 26.02 49.87 24.64 25.23 0.00 0.00
May 58.11 16.12 50.00 19.98 30.03 0.00 0.00
June 74.47 11.22 58.58 25.34 33.24 0.00 0.00
July 82.01 10.06 63.04 29.96 33.08 0.00 0.00
August 71.80 11.90 54.94 25.13 29.81 0.00 0.00
September 54.00 18.94 44.58 21.14 23.45 0.00 0.00
October 30.63 28.28 31.20 13.91 17.29 0.00 0.00
November 12.39 41.82 18.67 6.93 11.73 0.00 0.00
December 8.42 60.35 14.42 6.86 7.56 0.00 0.00
               
Annual Sum or Average 41.90 31.69 39.01 17.38 21.62 0.00 0.00
Minimum of Months 8.42 10.06 14.42 6.86 7.56 0.00 0.00
Maximum of Months 82.01 67.23 63.04 29.96 33.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM314

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 8.21 73.59 19.76 8.17 11.60 0.00 0.00
February 14.58 58.44 26.02 11.38 14.63 0.00 0.00
March 27.43 38.12 35.46 14.04 21.42 0.00 0.00
April 42.79 26.75 43.51 19.05 24.46 0.00 0.00
May 63.32 14.71 54.71 23.89 30.81 0.00 0.00
June 77.70 9.36 60.21 26.24 33.97 0.00 0.00
July 80.47 7.89 60.84 28.11 32.73 0.00 0.00
August 67.59 9.66 51.22 22.04 29.18 0.00 0.00
September 56.01 17.39 45.89 21.74 24.15 0.00 0.00
October 26.18 28.47 29.10 12.12 16.98 0.00 0.00
November 8.89 45.55 17.22 5.60 11.62 0.00 0.00
December 5.63 66.49 13.26 5.66 7.60 0.00 0.00
               
Annual Sum or Average 40.04 32.92 38.16 16.53 21.63 0.00 0.00
Minimum of Months 5.63 7.89 13.26 5.60 7.60 0.00 0.00
Maximum of Months 80.47 73.59 60.84 28.11 33.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM315_318

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 30.99 312.80 79.04 32.66 46.38 0.00 0.00
February 55.37 249.86 104.06 45.53 58.53 0.00 0.00
March 104.23 163.83 141.82 56.15 85.67 0.00 0.00
April 166.77 115.25 174.04 76.20 97.83 0.00 0.00
May 249.25 63.13 218.82 95.58 123.24 0.00 0.00
June 307.66 40.57 240.84 104.94 135.89 0.00 0.00
July 319.07 34.18 243.37 112.45 130.91 0.00 0.00
August 267.65 41.55 204.86 88.15 116.71 0.00 0.00
September 220.95 73.94 183.55 86.95 96.60 0.00 0.00
October 100.23 121.11 116.40 48.48 67.92 0.00 0.00
November 33.13 196.27 68.87 22.39 46.48 0.00 0.00
December 21.33 284.64 53.04 22.65 30.39 0.00 0.00
               
Annual Sum or Average 156.93 140.92 152.63 66.11 86.52 0.00 0.00
Minimum of Months 21.33 34.18 53.04 22.39 30.39 0.00 0.00
Maximum of Months 319.07 312.80 243.37 112.45 135.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ELEVATORCOREFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM319

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 7.57 79.54 19.76 8.17 11.60 0.00 0.00
February 13.51 64.57 26.02 11.38 14.63 0.00 0.00
March 25.36 43.30 35.46 14.04 21.42 0.00 0.00
April 40.34 31.76 43.51 19.05 24.46 0.00 0.00
May 59.64 18.82 54.71 23.89 30.81 0.00 0.00
June 73.46 12.94 60.21 26.24 33.97 0.00 0.00
July 76.14 11.27 60.84 28.11 32.73 0.00 0.00
August 63.63 13.38 51.22 22.04 29.18 0.00 0.00
September 52.91 21.82 45.89 21.74 24.15 0.00 0.00
October 24.12 33.36 29.10 12.12 16.98 0.00 0.00
November 7.92 51.42 17.22 5.60 11.62 0.00 0.00
December 5.20 72.56 13.26 5.66 7.60 0.00 0.00
               
Annual Sum or Average 37.61 37.77 38.16 16.53 21.63 0.00 0.00
Minimum of Months 5.20 11.27 13.26 5.60 7.60 0.00 0.00
Maximum of Months 76.14 79.54 60.84 28.11 33.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM320_323

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 32.40 298.76 79.04 32.66 46.38 0.00 0.00
February 57.67 237.01 104.06 45.53 58.53 0.00 0.00
March 108.63 154.27 141.82 56.15 85.67 0.00 0.00
April 171.18 107.32 174.04 76.20 97.83 0.00 0.00
May 254.98 57.84 218.82 95.58 123.24 0.00 0.00
June 313.46 36.04 240.84 104.94 135.89 0.00 0.00
July 324.92 29.78 243.37 112.45 130.91 0.00 0.00
August 273.15 36.62 204.86 88.15 116.71 0.00 0.00
September 225.59 67.94 183.55 86.95 96.60 0.00 0.00
October 104.52 113.64 116.40 48.48 67.92 0.00 0.00
November 35.27 184.48 68.87 22.39 46.48 0.00 0.00
December 22.28 270.12 53.04 22.65 30.39 0.00 0.00
               
Annual Sum or Average 160.90 132.33 152.63 66.11 86.52 0.00 0.00
Minimum of Months 22.28 29.78 53.04 22.39 30.39 0.00 0.00
Maximum of Months 324.92 298.76 243.37 112.45 135.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM324

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 8.61 69.29 19.76 8.17 11.60 0.00 0.00
February 15.05 55.12 26.02 11.38 14.63 0.00 0.00
March 27.89 36.62 35.46 14.04 21.42 0.00 0.00
April 42.83 26.56 43.51 19.05 24.46 0.00 0.00
May 62.68 15.66 54.71 23.89 30.81 0.00 0.00
June 76.12 10.53 60.21 26.24 33.97 0.00 0.00
July 78.72 9.09 60.84 28.11 32.73 0.00 0.00
August 66.22 10.86 51.22 22.04 29.18 0.00 0.00
September 55.27 18.42 45.89 21.74 24.15 0.00 0.00
October 26.42 28.48 29.10 12.12 16.98 0.00 0.00
November 9.14 43.71 17.22 5.60 11.62 0.00 0.00
December 5.86 62.69 13.26 5.66 7.60 0.00 0.00
               
Annual Sum or Average 39.70 32.15 38.16 16.53 21.63 0.00 0.00
Minimum of Months 5.86 9.09 13.26 5.60 7.60 0.00 0.00
Maximum of Months 78.72 69.29 60.84 28.11 33.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONTSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONTSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: REARSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDORFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 30.48 113.28 52.81 31.11 21.70 0.00 0.00
February 38.30 90.85 58.85 33.74 25.11 0.00 0.00
March 42.55 63.93 55.78 21.77 34.01 0.00 0.00
April 49.88 45.74 54.53 18.17 36.36 0.00 0.00
May 54.10 25.46 52.68 9.41 43.26 0.00 0.00
June 66.85 16.44 55.21 8.46 46.75 0.00 0.00
July 70.81 14.18 55.63 9.86 45.77 0.00 0.00
August 71.07 17.42 55.22 12.80 42.42 0.00 0.00
September 69.50 29.92 58.64 22.86 35.78 0.00 0.00
October 56.02 46.55 57.76 29.49 28.27 0.00 0.00
November 30.38 71.90 42.71 21.94 20.77 0.00 0.00
December 28.90 103.87 42.15 28.12 14.03 0.00 0.00
               
Annual Sum or Average 50.80 53.12 53.46 20.57 32.89 0.00 0.00
Minimum of Months 28.90 14.18 42.15 8.46 14.03 0.00 0.00
Maximum of Months 71.07 113.28 58.85 33.74 46.75 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: REARSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM401

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 9.29 71.58 19.59 7.95 11.64 0.00 0.00
February 19.24 56.92 28.49 13.97 14.52 0.00 0.00
March 27.38 36.41 34.21 12.74 21.47 0.00 0.00
April 52.57 25.03 49.87 24.64 25.23 0.00 0.00
May 57.78 14.13 50.00 19.98 30.03 0.00 0.00
June 75.20 8.86 58.58 25.34 33.24 0.00 0.00
July 83.11 7.53 63.04 29.96 33.08 0.00 0.00
August 72.64 9.29 54.94 25.13 29.81 0.00 0.00
September 54.53 16.32 44.58 21.14 23.45 0.00 0.00
October 30.68 26.91 31.20 13.91 17.29 0.00 0.00
November 12.43 43.00 18.67 6.93 11.73 0.00 0.00
December 8.38 63.97 14.42 6.86 7.56 0.00 0.00
               
Annual Sum or Average 42.05 31.55 39.01 17.38 21.62 0.00 0.00
Minimum of Months 8.38 7.53 14.42 6.86 7.56 0.00 0.00
Maximum of Months 83.11 71.58 63.04 29.96 33.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM402_405

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 39.17 255.17 78.34 31.78 46.56 0.00 0.00
February 79.56 202.43 113.96 55.90 58.06 0.00 0.00
March 111.52 130.26 136.84 50.97 85.86 0.00 0.00
April 208.05 97.40 199.48 98.57 100.90 0.00 0.00
May 225.59 62.47 200.02 79.91 120.10 0.00 0.00
June 290.20 44.50 234.34 101.37 132.97 0.00 0.00
July 320.35 40.33 252.14 119.83 132.31 0.00 0.00
August 279.99 46.94 219.75 100.50 119.25 0.00 0.00
September 212.29 71.50 178.32 84.54 93.78 0.00 0.00
October 122.70 103.16 124.81 55.64 69.18 0.00 0.00
November 50.82 153.54 74.66 27.73 46.93 0.00 0.00
December 34.69 225.33 57.67 27.43 30.24 0.00 0.00
               
Annual Sum or Average 164.99 119.04 156.03 69.53 86.50 0.00 0.00
Minimum of Months 34.69 40.33 57.67 27.43 30.24 0.00 0.00
Maximum of Months 320.35 255.17 252.14 119.83 132.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM406_408

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 39.36 261.73 79.70 32.33 47.37 0.00 0.00
February 79.87 208.83 115.94 56.87 59.07 0.00 0.00
March 111.55 135.15 139.21 51.86 87.35 0.00 0.00
April 209.92 101.11 202.94 100.29 102.65 0.00 0.00
May 228.39 64.12 203.49 81.30 122.19 0.00 0.00
June 294.70 45.28 238.41 103.13 135.28 0.00 0.00
July 325.51 40.87 256.52 121.91 134.61 0.00 0.00
August 284.41 47.67 223.57 102.25 121.32 0.00 0.00
September 215.16 73.22 181.42 86.01 95.41 0.00 0.00
October 123.32 106.87 126.98 56.60 70.38 0.00 0.00
November 50.77 158.73 75.96 28.21 47.75 0.00 0.00
December 34.81 231.53 58.67 27.90 30.77 0.00 0.00
               
Annual Sum or Average 166.91 122.53 158.74 70.74 88.00 0.00 0.00
Minimum of Months 34.81 40.87 58.67 27.90 30.77 0.00 0.00
Maximum of Months 325.51 261.73 256.52 121.91 135.28 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM409_412

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 35.71 296.27 78.34 31.78 46.56 0.00 0.00
February 74.12 237.04 113.96 55.90 58.06 0.00 0.00
March 104.53 152.73 136.84 50.97 85.86 0.00 0.00
April 206.64 104.92 199.48 98.57 100.90 0.00 0.00
May 229.79 57.76 200.02 79.91 120.10 0.00 0.00
June 301.42 35.38 234.34 101.37 132.97 0.00 0.00
July 333.54 29.59 252.14 119.83 132.31 0.00 0.00
August 291.36 36.89 219.75 100.50 119.25 0.00 0.00
September 216.56 66.91 178.32 84.54 93.78 0.00 0.00
October 118.10 112.94 124.81 55.64 69.18 0.00 0.00
November 46.70 180.18 74.66 27.73 46.93 0.00 0.00
December 32.04 266.13 57.67 27.43 30.24 0.00 0.00
               
Annual Sum or Average 166.33 130.91 156.03 69.53 86.50 0.00 0.00
Minimum of Months 32.04 29.59 57.67 27.43 30.24 0.00 0.00
Maximum of Months 333.54 296.27 252.14 119.83 132.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM413

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 9.75 64.05 19.59 7.95 11.64 0.00 0.00
February 19.86 50.83 28.49 13.97 14.52 0.00 0.00
March 28.10 32.48 34.21 12.74 21.47 0.00 0.00
April 52.56 23.76 49.87 24.64 25.23 0.00 0.00
May 57.35 15.04 50.00 19.98 30.03 0.00 0.00
June 73.45 10.54 58.58 25.34 33.24 0.00 0.00
July 80.92 9.56 63.04 29.96 33.08 0.00 0.00
August 70.76 11.27 54.94 25.13 29.81 0.00 0.00
September 53.58 17.54 44.58 21.14 23.45 0.00 0.00
October 30.86 25.76 31.20 13.91 17.29 0.00 0.00
November 12.76 38.47 18.67 6.93 11.73 0.00 0.00
December 8.64 56.63 14.42 6.86 7.56 0.00 0.00
               
Annual Sum or Average 41.66 29.56 39.01 17.38 21.62 0.00 0.00
Minimum of Months 8.64 9.56 14.42 6.86 7.56 0.00 0.00
Maximum of Months 80.92 64.05 63.04 29.96 33.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM414

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 9.14 64.59 19.76 8.17 11.60 0.00 0.00
February 15.63 51.44 26.02 11.38 14.63 0.00 0.00
March 28.43 33.87 35.46 14.04 21.42 0.00 0.00
April 42.55 24.68 43.51 19.05 24.46 0.00 0.00
May 61.82 15.05 54.71 23.89 30.81 0.00 0.00
June 74.74 10.29 60.21 26.24 33.97 0.00 0.00
July 77.10 9.11 60.84 28.11 32.73 0.00 0.00
August 64.78 10.85 51.22 22.04 29.18 0.00 0.00
September 54.55 17.64 45.89 21.74 24.15 0.00 0.00
October 26.80 26.64 29.10 12.12 16.98 0.00 0.00
November 9.67 40.02 17.22 5.60 11.62 0.00 0.00
December 6.26 57.84 13.26 5.66 7.60 0.00 0.00
               
Annual Sum or Average 39.42 30.07 38.16 16.53 21.63 0.00 0.00
Minimum of Months 6.26 9.11 13.26 5.60 7.60 0.00 0.00
Maximum of Months 77.10 64.59 60.84 28.11 33.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM415_418

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 32.60 294.24 79.04 32.66 46.38 0.00 0.00
February 57.42 233.80 104.06 45.53 58.53 0.00 0.00
March 107.01 152.13 141.82 56.15 85.67 0.00 0.00
April 168.46 105.10 174.04 76.20 97.83 0.00 0.00
May 250.94 56.29 218.82 95.58 123.24 0.00 0.00
June 309.11 34.82 240.84 104.94 135.89 0.00 0.00
July 320.39 28.75 243.37 112.45 130.91 0.00 0.00
August 269.01 35.64 204.86 88.15 116.71 0.00 0.00
September 222.63 66.06 183.55 86.95 96.60 0.00 0.00
October 102.83 111.23 116.40 48.48 67.92 0.00 0.00
November 34.90 181.38 68.87 22.39 46.48 0.00 0.00
December 22.35 266.12 53.04 22.65 30.39 0.00 0.00
               
Annual Sum or Average 158.68 129.98 152.63 66.11 86.52 0.00 0.00
Minimum of Months 22.35 28.75 53.04 22.39 30.39 0.00 0.00
Maximum of Months 320.39 294.24 243.37 112.45 135.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ELEVATORCOREFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM419

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 8.02 74.60 19.76 8.17 11.60 0.00 0.00
February 14.22 59.31 26.02 11.38 14.63 0.00 0.00
March 26.61 38.63 35.46 14.04 21.42 0.00 0.00
April 41.98 26.78 43.51 19.05 24.46 0.00 0.00
May 62.48 14.43 54.71 23.89 30.81 0.00 0.00
June 77.09 8.96 60.21 26.24 33.97 0.00 0.00
July 79.93 7.42 60.84 28.11 32.73 0.00 0.00
August 67.07 9.19 51.22 22.04 29.18 0.00 0.00
September 55.52 16.89 45.89 21.74 24.15 0.00 0.00
October 25.57 28.28 29.10 12.12 16.98 0.00 0.00
November 8.63 46.07 17.22 5.60 11.62 0.00 0.00
December 5.52 67.44 13.26 5.66 7.60 0.00 0.00
               
Annual Sum or Average 39.52 33.04 38.16 16.53 21.63 0.00 0.00
Minimum of Months 5.52 7.42 13.26 5.60 7.60 0.00 0.00
Maximum of Months 79.93 74.60 60.84 28.11 33.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM420_423

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 32.70 293.01 79.04 32.66 46.38 0.00 0.00
February 57.79 232.04 104.06 45.53 58.53 0.00 0.00
March 108.05 150.48 141.82 56.15 85.67 0.00 0.00
April 169.62 103.68 174.04 76.20 97.83 0.00 0.00
May 252.50 55.17 218.82 95.58 123.24 0.00 0.00
June 310.85 33.79 240.84 104.94 135.89 0.00 0.00
July 322.16 27.67 243.37 112.45 130.91 0.00 0.00
August 270.67 34.45 204.86 88.15 116.71 0.00 0.00
September 223.95 64.76 183.55 86.95 96.60 0.00 0.00
October 103.91 109.80 116.40 48.48 67.92 0.00 0.00
November 35.36 179.58 68.87 22.39 46.48 0.00 0.00
December 22.47 264.48 53.04 22.65 30.39 0.00 0.00
               
Annual Sum or Average 159.72 128.60 152.63 66.11 86.52 0.00 0.00
Minimum of Months 22.47 27.67 53.04 22.39 30.39 0.00 0.00
Maximum of Months 322.16 293.01 243.37 112.45 135.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GUESTROOM424

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 8.35 71.99 19.76 8.17 11.60 0.00 0.00
February 14.78 56.81 26.02 11.38 14.63 0.00 0.00
March 27.66 36.89 35.46 14.04 21.42 0.00 0.00
April 42.79 25.53 43.51 19.05 24.46 0.00 0.00
May 63.15 13.86 54.71 23.89 30.81 0.00 0.00
June 77.53 8.63 60.21 26.24 33.97 0.00 0.00
July 80.32 7.16 60.84 28.11 32.73 0.00 0.00
August 67.49 8.85 51.22 22.04 29.18 0.00 0.00
September 56.04 16.29 45.89 21.74 24.15 0.00 0.00
October 26.44 27.16 29.10 12.12 16.98 0.00 0.00
November 9.10 43.97 17.22 5.60 11.62 0.00 0.00
December 5.73 64.76 13.26 5.66 7.60 0.00 0.00
               
Annual Sum or Average 40.09 31.71 38.16 16.53 21.63 0.00 0.00
Minimum of Months 5.73 7.16 13.26 5.60 7.60 0.00 0.00
Maximum of Months 80.32 71.99 60.84 28.11 33.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONTSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FRONTSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: REARSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDORFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.121858E+09 0.125274E+10 0.374533E+09 0.205470E+09 0.169063E+09 0.00 0.00
February 0.183867E+09 0.928359E+09 0.405257E+09 0.222469E+09 0.182788E+09 0.00 0.00
March 0.261475E+09 0.740763E+09 0.453029E+09 0.175209E+09 0.277821E+09 0.00 0.00
April 0.436761E+09 0.537245E+09 0.507922E+09 0.201176E+09 0.306746E+09 0.00 0.00
May 0.492027E+09 0.306149E+09 0.516470E+09 0.141376E+09 0.375094E+09 0.00 0.00
June 0.654402E+09 0.196619E+09 0.561206E+09 0.157741E+09 0.403465E+09 0.00 0.00
July 0.740265E+09 0.166664E+09 0.603233E+09 0.189048E+09 0.414185E+09 0.00 0.00
August 0.679465E+09 0.206628E+09 0.553485E+09 0.181371E+09 0.372114E+09 0.00 0.00
September 0.558926E+09 0.353190E+09 0.507099E+09 0.210909E+09 0.296191E+09 0.00 0.00
October 0.354198E+09 0.573847E+09 0.453418E+09 0.222664E+09 0.230754E+09 0.00 0.00
November 0.149964E+09 0.835595E+09 0.301891E+09 0.145847E+09 0.156044E+09 0.00 0.00
December 0.133424E+09 0.116571E+10 0.294655E+09 0.184308E+09 0.110348E+09 0.00 0.00
               
Annual Sum or Average 0.476663E+10 0.726351E+10 0.553220E+10 0.223759E+10 0.329461E+10 0.00 0.00
Minimum of Months 0.121858E+09 0.166664E+09 0.294655E+09 0.141376E+09 0.110348E+09 0.00 0.00
Maximum of Months 0.740265E+09 0.125274E+10 0.603233E+09 0.222664E+09 0.414185E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: REARSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONTLOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.212273E+09 0.179668E+10 0.472646E+09 0.191736E+09 0.280910E+09 0.00 0.00
February 0.406030E+09 0.129560E+10 0.621003E+09 0.304608E+09 0.316395E+09 0.00 0.00
March 0.636784E+09 0.932914E+09 0.825539E+09 0.307532E+09 0.518007E+09 0.00 0.00
April 0.121913E+10 0.649245E+09 0.116464E+10 0.575520E+09 0.589115E+09 0.00 0.00
May 0.140310E+10 0.397821E+09 0.120672E+10 0.482125E+09 0.724598E+09 0.00 0.00
June 0.177212E+10 0.255594E+09 0.136818E+10 0.591826E+09 0.776350E+09 0.00 0.00
July 0.202778E+10 0.222088E+09 0.152119E+10 0.722930E+09 0.798259E+09 0.00 0.00
August 0.176796E+10 0.268372E+09 0.132579E+10 0.606351E+09 0.719435E+09 0.00 0.00
September 0.125819E+10 0.460341E+09 0.104113E+10 0.493583E+09 0.547551E+09 0.00 0.00
October 0.690958E+09 0.770360E+09 0.753012E+09 0.335663E+09 0.417349E+09 0.00 0.00
November 0.261350E+09 0.110949E+10 0.435913E+09 0.161911E+09 0.274002E+09 0.00 0.00
December 0.189443E+09 0.162795E+10 0.347901E+09 0.165461E+09 0.182440E+09 0.00 0.00
               
Annual Sum or Average 0.118451E+11 0.978645E+10 0.110837E+11 0.493925E+10 0.614441E+10 0.00 0.00
Minimum of Months 0.189443E+09 0.222088E+09 0.347901E+09 0.161911E+09 0.182440E+09 0.00 0.00
Maximum of Months 0.202778E+10 0.179668E+10 0.152119E+10 0.722930E+09 0.798259E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RESTROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MEETINGROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 68767797.27 0.623269E+09 0.157069E+09 63717247.09 93351526.87 0.00 0.00
February 0.132538E+09 0.452952E+09 0.206371E+09 0.101227E+09 0.105144E+09 0.00 0.00
March 0.209288E+09 0.328976E+09 0.274342E+09 0.102198E+09 0.172143E+09 0.00 0.00
April 0.404372E+09 0.228362E+09 0.387030E+09 0.191256E+09 0.195774E+09 0.00 0.00
May 0.462676E+09 0.139879E+09 0.401016E+09 0.160219E+09 0.240797E+09 0.00 0.00
June 0.584482E+09 89560625.04 0.454670E+09 0.196674E+09 0.257996E+09 0.00 0.00
July 0.668762E+09 78105520.77 0.505519E+09 0.240242E+09 0.265276E+09 0.00 0.00
August 0.583334E+09 94895386.69 0.440583E+09 0.201501E+09 0.239082E+09 0.00 0.00
September 0.416394E+09 0.160619E+09 0.345988E+09 0.164027E+09 0.181961E+09 0.00 0.00
October 0.232376E+09 0.265863E+09 0.250240E+09 0.111547E+09 0.138693E+09 0.00 0.00
November 86688639.66 0.387687E+09 0.144862E+09 53805829.27 91056019.13 0.00 0.00
December 61834344.54 0.566771E+09 0.115614E+09 54985778.54 60628152.23 0.00 0.00
               
Annual Sum or Average 0.391151E+10 0.341694E+10 0.368330E+10 0.164140E+10 0.204190E+10 0.00 0.00
Minimum of Months 61834344.54 78105520.77 0.115614E+09 53805829.27 60628152.23 0.00 0.00
Maximum of Months 0.668762E+09 0.623269E+09 0.505519E+09 0.240242E+09 0.265276E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECHANICALROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM101

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 23281564.99 0.201823E+09 52356257.99 21239082.36 31117175.62 0.00 0.00
February 44494105.28 0.146977E+09 68790207.80 33742247.02 35047960.78 0.00 0.00
March 69341429.26 0.107508E+09 91447208.25 34066093.82 57381114.43 0.00 0.00
April 0.133521E+09 75544362.79 0.129010E+09 63751874.14 65258030.76 0.00 0.00
May 0.152409E+09 46048439.61 0.133672E+09 53406228.25 80265809.73 0.00 0.00
June 0.190731E+09 31127931.60 0.151557E+09 65558120.36 85998544.22 0.00 0.00
July 0.217193E+09 28721042.69 0.168506E+09 80080812.03 88425495.12 0.00 0.00
August 0.188930E+09 34673735.59 0.146861E+09 67167104.09 79693904.66 0.00 0.00
September 0.135063E+09 56127063.32 0.115329E+09 54675510.93 60653827.91 0.00 0.00
October 75318955.30 89750117.40 83413167.70 37182237.85 46230929.85 0.00 0.00
November 28111153.04 0.129283E+09 48287282.80 17935276.42 30352006.38 0.00 0.00
December 20553392.34 0.185612E+09 38537976.92 18328592.85 20209384.08 0.00 0.00
               
Annual Sum or Average 0.127895E+10 0.113320E+10 0.122777E+10 0.547133E+09 0.680634E+09 0.00 0.00
Minimum of Months 20553392.34 28721042.69 38537976.92 17935276.42 20209384.08 0.00 0.00
Maximum of Months 0.217193E+09 0.201823E+09 0.168506E+09 80080812.03 88425495.12 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM102

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 23727217.10 0.197901E+09 52356257.99 21239082.36 31117175.62 0.00 0.00
February 45138454.20 0.143651E+09 68790207.80 33742247.02 35047960.78 0.00 0.00
March 70715129.47 0.104181E+09 91447208.25 34066093.82 57381114.43 0.00 0.00
April 0.135074E+09 72358819.08 0.129010E+09 63751874.14 65258030.76 0.00 0.00
May 0.154754E+09 43590376.26 0.133672E+09 53406228.25 80265809.73 0.00 0.00
June 0.193204E+09 28827332.13 0.151557E+09 65558120.36 85998544.22 0.00 0.00
July 0.219773E+09 26419267.54 0.168506E+09 80080812.03 88425495.12 0.00 0.00
August 0.191357E+09 32235422.00 0.146861E+09 67167104.09 79693904.66 0.00 0.00
September 0.136972E+09 53185658.12 0.115329E+09 54675510.93 60653827.91 0.00 0.00
October 76801098.01 86328413.77 83413167.70 37182237.85 46230929.85 0.00 0.00
November 28851131.90 0.125306E+09 48287282.80 17935276.42 30352006.38 0.00 0.00
December 20926790.84 0.181413E+09 38537976.92 18328592.85 20209384.08 0.00 0.00
               
Annual Sum or Average 0.129729E+10 0.109540E+10 0.122777E+10 0.547133E+09 0.680634E+09 0.00 0.00
Minimum of Months 20926790.84 26419267.54 38537976.92 17935276.42 20209384.08 0.00 0.00
Maximum of Months 0.219773E+09 0.197901E+09 0.168506E+09 80080812.03 88425495.12 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM103

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 23893557.99 0.199904E+09 52356257.99 21239082.36 31117175.62 0.00 0.00
February 45426400.47 0.143960E+09 68790207.80 33742247.02 35047960.78 0.00 0.00
March 72218613.26 0.101904E+09 91447208.25 34066093.82 57381114.43 0.00 0.00
April 0.137583E+09 67542101.55 0.129010E+09 63751874.14 65258030.76 0.00 0.00
May 0.158853E+09 38339854.03 0.133672E+09 53406228.25 80265809.73 0.00 0.00
June 0.199114E+09 23324421.55 0.151557E+09 65558120.36 85998544.22 0.00 0.00
July 0.226577E+09 20488787.92 0.168506E+09 80080812.03 88425495.12 0.00 0.00
August 0.197424E+09 25869152.26 0.146861E+09 67167104.09 79693904.66 0.00 0.00
September 0.141150E+09 46091826.91 0.115329E+09 54675510.93 60653827.91 0.00 0.00
October 78907749.30 79742560.68 83413167.70 37182237.85 46230929.85 0.00 0.00
November 29765556.05 0.121077E+09 48287282.80 17935276.42 30352006.38 0.00 0.00
December 21214839.44 0.181279E+09 38537976.92 18328592.85 20209384.08 0.00 0.00
               
Annual Sum or Average 0.133213E+10 0.104952E+10 0.122777E+10 0.547133E+09 0.680634E+09 0.00 0.00
Minimum of Months 21214839.44 20488787.92 38537976.92 17935276.42 20209384.08 0.00 0.00
Maximum of Months 0.226577E+09 0.199904E+09 0.168506E+09 80080812.03 88425495.12 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM104

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 21796617.93 0.199841E+09 52824908.68 21827689.37 30997219.31 0.00 0.00
February 35120632.12 0.142650E+09 62813624.97 27482740.55 35330884.42 0.00 0.00
March 73505938.32 0.101983E+09 94780095.50 37523677.75 57256417.75 0.00 0.00
April 0.111962E+09 68154776.91 0.112557E+09 49284740.22 63272523.73 0.00 0.00
May 0.171814E+09 37582319.63 0.146238E+09 63874556.19 82363868.15 0.00 0.00
June 0.203470E+09 22901705.88 0.155759E+09 67870301.44 87888276.14 0.00 0.00
July 0.217407E+09 19836649.23 0.162641E+09 75151558.34 87489639.30 0.00 0.00
August 0.182162E+09 24856480.56 0.136908E+09 58909459.56 77998906.28 0.00 0.00
September 0.145100E+09 45182991.68 0.118711E+09 56236777.04 62473780.16 0.00 0.00
October 68708648.13 78114774.57 77789259.40 32397768.15 45391491.25 0.00 0.00
November 22292089.67 0.122038E+09 44542235.29 14478780.22 30063455.07 0.00 0.00
December 14838056.46 0.182489E+09 35447476.85 15138523.77 20308953.09 0.00 0.00
               
Annual Sum or Average 0.126818E+10 0.104563E+10 0.120101E+10 0.520177E+09 0.680835E+09 0.00 0.00
Minimum of Months 14838056.46 19836649.23 35447476.85 14478780.22 20308953.09 0.00 0.00
Maximum of Months 0.217407E+09 0.199841E+09 0.162641E+09 75151558.34 87888276.14 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM105

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 20293910.65 0.214605E+09 52824908.68 21827689.37 30997219.31 0.00 0.00
February 32977753.03 0.154356E+09 62813624.97 27482740.55 35330884.42 0.00 0.00
March 68949834.06 0.111532E+09 94780095.50 37523677.75 57256417.75 0.00 0.00
April 0.107625E+09 75454117.48 0.112557E+09 49284740.22 63272523.73 0.00 0.00
May 0.166620E+09 41956054.18 0.146238E+09 63874556.19 82363868.15 0.00 0.00
June 0.199173E+09 26036408.40 0.155759E+09 67870301.44 87888276.14 0.00 0.00
July 0.213418E+09 22575560.30 0.162641E+09 75151558.34 87489639.30 0.00 0.00
August 0.178607E+09 27759182.53 0.136908E+09 58909459.56 77998906.28 0.00 0.00
September 0.142131E+09 48848956.09 0.118711E+09 56236777.04 62473780.16 0.00 0.00
October 65602089.33 83570505.83 77789259.40 32397768.15 45391491.25 0.00 0.00
November 20725434.91 0.131623E+09 44542235.29 14478780.22 30063455.07 0.00 0.00
December 13921125.24 0.196361E+09 35447476.85 15138523.77 20308953.09 0.00 0.00
               
Annual Sum or Average 0.123004E+10 0.113468E+10 0.120101E+10 0.520177E+09 0.680835E+09 0.00 0.00
Minimum of Months 13921125.24 22575560.30 35447476.85 14478780.22 20308953.09 0.00 0.00
Maximum of Months 0.213418E+09 0.214605E+09 0.162641E+09 75151558.34 87888276.14 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: EMPLOYEELOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 18126170.26 0.244268E+09 52824908.68 21827689.37 30997219.31 0.00 0.00
February 29859236.78 0.180639E+09 62813624.97 27482740.55 35330884.42 0.00 0.00
March 61196877.35 0.137573E+09 94780095.50 37523677.75 57256417.75 0.00 0.00
April 98427631.96 98084006.12 0.112557E+09 49284740.22 63272523.73 0.00 0.00
May 0.152820E+09 58477143.04 0.146238E+09 63874556.19 82363868.15 0.00 0.00
June 0.185242E+09 40334389.87 0.155759E+09 67870301.44 87888276.14 0.00 0.00
July 0.199249E+09 35958750.86 0.162641E+09 75151558.34 87489639.30 0.00 0.00
August 0.165465E+09 42231268.97 0.136908E+09 58909459.56 77998906.28 0.00 0.00
September 0.131623E+09 67289924.03 0.118711E+09 56236777.04 62473780.16 0.00 0.00
October 57071535.02 0.107758E+09 77789259.40 32397768.15 45391491.25 0.00 0.00
November 17367540.56 0.160690E+09 44542235.29 14478780.22 30063455.07 0.00 0.00
December 12230476.56 0.227772E+09 35447476.85 15138523.77 20308953.09 0.00 0.00
               
Annual Sum or Average 0.112868E+10 0.140108E+10 0.120101E+10 0.520177E+09 0.680835E+09 0.00 0.00
Minimum of Months 12230476.56 35958750.86 35447476.85 14478780.22 20308953.09 0.00 0.00
Maximum of Months 0.199249E+09 0.244268E+09 0.162641E+09 75151558.34 87888276.14 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRYROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 20325190.35 0.133672E+10 0.158475E+09 65483068.12 92991657.92 0.00 0.00
February 45590710.52 0.106606E+10 0.188441E+09 82448221.66 0.105993E+09 0.00 0.00
March 0.105231E+09 0.959382E+09 0.284340E+09 0.112571E+09 0.171769E+09 0.00 0.00
April 0.183971E+09 0.794225E+09 0.337672E+09 0.147854E+09 0.189818E+09 0.00 0.00
May 0.254843E+09 0.607182E+09 0.438715E+09 0.191624E+09 0.247092E+09 0.00 0.00
June 0.313163E+09 0.501829E+09 0.467276E+09 0.203611E+09 0.263665E+09 0.00 0.00
July 0.339111E+09 0.493404E+09 0.487924E+09 0.225455E+09 0.262469E+09 0.00 0.00
August 0.253085E+09 0.528038E+09 0.410725E+09 0.176728E+09 0.233997E+09 0.00 0.00
September 0.228021E+09 0.658320E+09 0.356132E+09 0.168710E+09 0.187421E+09 0.00 0.00
October 84255431.38 0.872845E+09 0.233368E+09 97193304.45 0.136174E+09 0.00 0.00
November 20158605.63 0.106873E+10 0.133627E+09 43436340.67 90190365.21 0.00 0.00
December 14922777.94 0.129376E+10 0.106342E+09 45415571.30 60926859.26 0.00 0.00
               
Annual Sum or Average 0.186268E+10 0.101805E+11 0.360304E+10 0.156053E+10 0.204251E+10 0.00 0.00
Minimum of Months 14922777.94 0.493404E+09 0.106342E+09 43436340.67 60926859.26 0.00 0.00
Maximum of Months 0.339111E+09 0.133672E+10 0.487924E+09 0.225455E+09 0.263665E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ELEVATORCOREFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: EXERCISECENTERFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 21683667.78 0.204401E+09 52824908.68 21827689.37 30997219.31 0.00 0.00
February 35006265.88 0.145997E+09 62813624.97 27482740.55 35330884.42 0.00 0.00
March 73305167.31 0.105281E+09 94780095.50 37523677.75 57256417.75 0.00 0.00
April 0.111534E+09 71415648.62 0.112557E+09 49284740.22 63272523.73 0.00 0.00
May 0.170168E+09 41553950.68 0.146238E+09 63874556.19 82363868.15 0.00 0.00
June 0.201728E+09 26830870.76 0.155759E+09 67870301.44 87888276.14 0.00 0.00
July 0.216084E+09 23648128.62 0.162641E+09 75151558.34 87489639.30 0.00 0.00
August 0.181325E+09 28343729.80 0.136908E+09 58909459.56 77998906.28 0.00 0.00
September 0.144692E+09 48483654.72 0.118711E+09 56236777.04 62473780.16 0.00 0.00
October 69448040.30 80230522.53 77789259.40 32397768.15 45391491.25 0.00 0.00
November 22461148.72 0.123995E+09 44542235.29 14478780.22 30063455.07 0.00 0.00
December 14891832.64 0.185445E+09 35447476.85 15138523.77 20308953.09 0.00 0.00
               
Annual Sum or Average 0.126233E+10 0.108562E+10 0.120101E+10 0.520177E+09 0.680835E+09 0.00 0.00
Minimum of Months 14891832.64 23648128.62 35447476.85 14478780.22 20308953.09 0.00 0.00
Maximum of Months 0.216084E+09 0.204401E+09 0.162641E+09 75151558.34 87888276.14 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONTOFFICEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 88856310.88 0.795185E+09 0.211300E+09 87310757.49 0.123989E+09 0.00 0.00
February 0.142430E+09 0.567670E+09 0.251254E+09 0.109931E+09 0.141324E+09 0.00 0.00
March 0.295698E+09 0.410974E+09 0.379120E+09 0.150095E+09 0.229026E+09 0.00 0.00
April 0.445403E+09 0.283204E+09 0.450229E+09 0.197139E+09 0.253090E+09 0.00 0.00
May 0.678971E+09 0.168243E+09 0.584954E+09 0.255498E+09 0.329455E+09 0.00 0.00
June 0.804003E+09 0.106965E+09 0.623034E+09 0.271481E+09 0.351553E+09 0.00 0.00
July 0.861245E+09 92300413.88 0.650565E+09 0.300606E+09 0.349959E+09 0.00 0.00
August 0.722794E+09 0.112705E+09 0.547633E+09 0.235638E+09 0.311996E+09 0.00 0.00
September 0.575424E+09 0.198743E+09 0.474842E+09 0.224947E+09 0.249895E+09 0.00 0.00
October 0.273306E+09 0.330066E+09 0.311157E+09 0.129591E+09 0.181566E+09 0.00 0.00
November 89510675.12 0.491220E+09 0.178169E+09 57915120.89 0.120254E+09 0.00 0.00
December 60650481.69 0.722569E+09 0.141790E+09 60554095.06 81235812.34 0.00 0.00
               
Annual Sum or Average 0.503829E+10 0.427985E+10 0.480405E+10 0.208071E+10 0.272334E+10 0.00 0.00
Minimum of Months 60650481.69 92300413.88 0.141790E+09 57915120.89 81235812.34 0.00 0.00
Maximum of Months 0.861245E+09 0.795185E+09 0.650565E+09 0.300606E+09 0.351553E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONTSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONTSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: REARSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDORFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 78556325.44 0.318724E+09 0.141447E+09 83318398.15 58129002.58 0.00 0.00
February 89354915.15 0.233644E+09 0.142372E+09 81633068.74 60738569.56 0.00 0.00
March 0.108938E+09 0.186541E+09 0.149405E+09 58309641.76 91095668.30 0.00 0.00
April 0.125547E+09 0.134092E+09 0.141339E+09 47100717.85 94238442.48 0.00 0.00
May 0.140527E+09 78733778.32 0.141087E+09 25213321.40 0.115873E+09 0.00 0.00
June 0.170718E+09 49061276.76 0.143108E+09 21925932.80 0.121182E+09 0.00 0.00
July 0.188186E+09 42478385.65 0.149005E+09 26410647.16 0.122594E+09 0.00 0.00
August 0.188817E+09 52588330.29 0.147890E+09 34271169.12 0.113619E+09 0.00 0.00
September 0.176189E+09 89867225.70 0.151998E+09 59263194.17 92735128.52 0.00 0.00
October 0.142100E+09 0.144391E+09 0.154691E+09 78981980.71 75709043.99 0.00 0.00
November 74116284.21 0.205120E+09 0.110702E+09 56858615.09 53843114.89 0.00 0.00
December 74702790.35 0.294404E+09 0.112889E+09 75314095.27 37575390.12 0.00 0.00
               
Annual Sum or Average 0.155775E+10 0.182965E+10 0.168593E+10 0.648601E+09 0.103733E+10 0.00 0.00
Minimum of Months 74116284.21 42478385.65 0.110702E+09 21925932.80 37575390.12 0.00 0.00
Maximum of Months 0.188817E+09 0.318724E+09 0.154691E+09 83318398.15 0.122594E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: REARSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM201

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 25374156.80 0.181654E+09 52603806.49 21339503.56 31264302.93 0.00 0.00
February 47042825.81 0.132744E+09 69115458.47 33901784.83 35213673.63 0.00 0.00
March 73034313.05 96954119.21 91879585.08 34227162.82 57652422.26 0.00 0.00
April 0.135423E+09 70191717.77 0.129620E+09 64053301.44 65566582.39 0.00 0.00
May 0.152721E+09 45383141.94 0.134304E+09 53658739.97 80645320.77 0.00 0.00
June 0.190369E+09 31090976.36 0.152273E+09 65868087.83 86405160.75 0.00 0.00
July 0.217416E+09 28512201.00 0.169303E+09 80459444.71 88843586.77 0.00 0.00
August 0.190017E+09 33456026.47 0.147555E+09 67484679.05 80070711.53 0.00 0.00
September 0.137875E+09 51546418.27 0.115875E+09 54934023.98 60940609.95 0.00 0.00
October 79617928.19 79891052.57 83807558.06 37358040.40 46449517.66 0.00 0.00
November 31027475.94 0.112278E+09 48515592.57 18020076.78 30495515.78 0.00 0.00
December 22399274.19 0.163996E+09 38720190.41 18415252.86 20304937.56 0.00 0.00
               
Annual Sum or Average 0.130232E+10 0.102770E+10 0.123357E+10 0.549720E+09 0.683852E+09 0.00 0.00
Minimum of Months 22399274.19 28512201.00 38720190.41 18020076.78 20304937.56 0.00 0.00
Maximum of Months 0.217416E+09 0.181654E+09 0.169303E+09 80459444.71 88843586.77 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM202_205

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 94815280.30 0.807870E+09 0.210415E+09 85358014.22 0.125057E+09 0.00 0.00
February 0.179881E+09 0.585741E+09 0.276462E+09 0.135607E+09 0.140855E+09 0.00 0.00
March 0.281837E+09 0.420839E+09 0.367518E+09 0.136909E+09 0.230610E+09 0.00 0.00
April 0.540451E+09 0.287543E+09 0.518480E+09 0.256213E+09 0.262266E+09 0.00 0.00
May 0.620536E+09 0.167820E+09 0.537216E+09 0.214635E+09 0.322581E+09 0.00 0.00
June 0.785241E+09 0.104230E+09 0.609093E+09 0.263472E+09 0.345621E+09 0.00 0.00
July 0.897468E+09 91557747.10 0.677212E+09 0.321838E+09 0.355374E+09 0.00 0.00
August 0.783851E+09 0.111659E+09 0.590222E+09 0.269939E+09 0.320283E+09 0.00 0.00
September 0.562169E+09 0.190285E+09 0.463499E+09 0.219736E+09 0.243762E+09 0.00 0.00
October 0.314335E+09 0.322506E+09 0.335230E+09 0.149432E+09 0.185798E+09 0.00 0.00
November 0.118896E+09 0.485516E+09 0.194062E+09 72080307.13 0.121982E+09 0.00 0.00
December 84890405.27 0.728578E+09 0.154881E+09 73661011.43 81219750.22 0.00 0.00
               
Annual Sum or Average 0.526437E+10 0.430414E+10 0.493429E+10 0.219888E+10 0.273541E+10 0.00 0.00
Minimum of Months 84890405.27 91557747.10 0.154881E+09 72080307.13 81219750.22 0.00 0.00
Maximum of Months 0.897468E+09 0.807870E+09 0.677212E+09 0.321838E+09 0.355374E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM206_208

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 94606931.41 0.832205E+09 0.213767E+09 86717760.84 0.127049E+09 0.00 0.00
February 0.180261E+09 0.604755E+09 0.280866E+09 0.137767E+09 0.143098E+09 0.00 0.00
March 0.282385E+09 0.435276E+09 0.373373E+09 0.139090E+09 0.234283E+09 0.00 0.00
April 0.546584E+09 0.296198E+09 0.526738E+09 0.260295E+09 0.266444E+09 0.00 0.00
May 0.629396E+09 0.171092E+09 0.545774E+09 0.218054E+09 0.327719E+09 0.00 0.00
June 0.797932E+09 0.105400E+09 0.618795E+09 0.267669E+09 0.351126E+09 0.00 0.00
July 0.912293E+09 92151306.36 0.687999E+09 0.326965E+09 0.361035E+09 0.00 0.00
August 0.796754E+09 0.112665E+09 0.599623E+09 0.274239E+09 0.325384E+09 0.00 0.00
September 0.570878E+09 0.193326E+09 0.470882E+09 0.223236E+09 0.247645E+09 0.00 0.00
October 0.317883E+09 0.329900E+09 0.340570E+09 0.151813E+09 0.188758E+09 0.00 0.00
November 0.119192E+09 0.500589E+09 0.197154E+09 73228540.89 0.123925E+09 0.00 0.00
December 84720019.22 0.751752E+09 0.157348E+09 74834425.69 82513458.64 0.00 0.00
               
Annual Sum or Average 0.533288E+10 0.442531E+10 0.501289E+10 0.223391E+10 0.277898E+10 0.00 0.00
Minimum of Months 84720019.22 92151306.36 0.157348E+09 73228540.89 82513458.64 0.00 0.00
Maximum of Months 0.912293E+09 0.832205E+09 0.687999E+09 0.326965E+09 0.361035E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM209_212

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 92552173.03 0.824208E+09 0.210415E+09 85358014.22 0.125057E+09 0.00 0.00
February 0.176981E+09 0.598081E+09 0.276462E+09 0.135607E+09 0.140855E+09 0.00 0.00
March 0.278129E+09 0.429335E+09 0.367518E+09 0.136909E+09 0.230610E+09 0.00 0.00
April 0.540146E+09 0.289371E+09 0.518480E+09 0.256213E+09 0.262266E+09 0.00 0.00
May 0.624102E+09 0.165041E+09 0.537216E+09 0.214635E+09 0.322581E+09 0.00 0.00
June 0.790902E+09 0.100160E+09 0.609093E+09 0.263472E+09 0.345621E+09 0.00 0.00
July 0.903654E+09 87012019.28 0.677212E+09 0.321838E+09 0.355374E+09 0.00 0.00
August 0.788968E+09 0.107421E+09 0.590222E+09 0.269939E+09 0.320283E+09 0.00 0.00
September 0.564466E+09 0.187736E+09 0.463499E+09 0.219736E+09 0.243762E+09 0.00 0.00
October 0.313303E+09 0.324606E+09 0.335230E+09 0.149432E+09 0.185798E+09 0.00 0.00
November 0.116888E+09 0.495905E+09 0.194062E+09 72080307.13 0.121982E+09 0.00 0.00
December 82871725.10 0.745420E+09 0.154881E+09 73661011.43 81219750.22 0.00 0.00
               
Annual Sum or Average 0.527296E+10 0.435430E+10 0.493429E+10 0.219888E+10 0.273541E+10 0.00 0.00
Minimum of Months 82871725.10 87012019.28 0.154881E+09 72080307.13 81219750.22 0.00 0.00
Maximum of Months 0.903654E+09 0.824208E+09 0.677212E+09 0.321838E+09 0.355374E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM213

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 23901118.02 0.201008E+09 52603806.49 21339503.56 31264302.93 0.00 0.00
February 45302573.77 0.145412E+09 69115458.47 33901784.83 35213673.63 0.00 0.00
March 71651269.53 0.103577E+09 91879585.08 34227162.82 57652422.26 0.00 0.00
April 0.136595E+09 69436127.26 0.129620E+09 64053301.44 65566582.39 0.00 0.00
May 0.157312E+09 39852776.93 0.134304E+09 53658739.97 80645320.77 0.00 0.00
June 0.198225E+09 24201625.45 0.152273E+09 65868087.83 86405160.75 0.00 0.00
July 0.226076E+09 21126091.49 0.169303E+09 80459444.71 88843586.77 0.00 0.00
August 0.197395E+09 26252707.91 0.147555E+09 67484679.05 80070711.53 0.00 0.00
September 0.141706E+09 45821953.38 0.115875E+09 54934023.98 60940609.95 0.00 0.00
October 79862794.21 78786503.68 83807558.06 37358040.40 46449517.66 0.00 0.00
November 30360498.01 0.119848E+09 48515592.57 18020076.78 30495515.78 0.00 0.00
December 21437331.54 0.181045E+09 38720190.41 18415252.86 20304937.56 0.00 0.00
               
Annual Sum or Average 0.132982E+10 0.105637E+10 0.123357E+10 0.549720E+09 0.683852E+09 0.00 0.00
Minimum of Months 21437331.54 21126091.49 38720190.41 18020076.78 20304937.56 0.00 0.00
Maximum of Months 0.226076E+09 0.201008E+09 0.169303E+09 80459444.71 88843586.77 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM214

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 21304427.51 0.204789E+09 53074673.03 21930893.58 31143779.45 0.00 0.00
February 34319407.77 0.147252E+09 63110617.56 27612682.59 35497934.97 0.00 0.00
March 71472525.91 0.106429E+09 95228230.66 37701094.67 57527135.99 0.00 0.00
April 0.109668E+09 72274628.47 0.113089E+09 49517764.99 63571687.62 0.00 0.00
May 0.168850E+09 40522925.55 0.146930E+09 64176563.55 82753299.08 0.00 0.00
June 0.201224E+09 24961685.20 0.156495E+09 68191201.21 88303827.57 0.00 0.00
July 0.215476E+09 21661123.36 0.163410E+09 75506884.86 87903306.11 0.00 0.00
August 0.180663E+09 26645896.35 0.137556E+09 59187991.28 78367698.97 0.00 0.00
September 0.144244E+09 46822360.69 0.119272E+09 56502671.97 62769167.18 0.00 0.00
October 67937073.10 79916280.82 78157059.18 32550949.09 45606110.09 0.00 0.00
November 21915699.48 0.124553E+09 44752837.98 14547237.81 30205600.17 0.00 0.00
December 14611380.13 0.186307E+09 35615078.05 15210100.71 20404977.34 0.00 0.00
               
Annual Sum or Average 0.125169E+10 0.108213E+10 0.120669E+10 0.522636E+09 0.684055E+09 0.00 0.00
Minimum of Months 14611380.13 21661123.36 35615078.05 14547237.81 20404977.34 0.00 0.00
Maximum of Months 0.215476E+09 0.204789E+09 0.163410E+09 75506884.86 88303827.57 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM215_218

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 69365574.96 0.101214E+10 0.212299E+09 87723574.31 0.124575E+09 0.00 0.00
February 0.115964E+09 0.749805E+09 0.252442E+09 0.110451E+09 0.141992E+09 0.00 0.00
March 0.239719E+09 0.572341E+09 0.380913E+09 0.150804E+09 0.230109E+09 0.00 0.00
April 0.385687E+09 0.412773E+09 0.452358E+09 0.198071E+09 0.254287E+09 0.00 0.00
May 0.595284E+09 0.249790E+09 0.587719E+09 0.256706E+09 0.331013E+09 0.00 0.00
June 0.722558E+09 0.174880E+09 0.625980E+09 0.272765E+09 0.353215E+09 0.00 0.00
July 0.776996E+09 0.157112E+09 0.653641E+09 0.302028E+09 0.351613E+09 0.00 0.00
August 0.643506E+09 0.182707E+09 0.550223E+09 0.236752E+09 0.313471E+09 0.00 0.00
September 0.514573E+09 0.284608E+09 0.477087E+09 0.226011E+09 0.251077E+09 0.00 0.00
October 0.222987E+09 0.448522E+09 0.312628E+09 0.130204E+09 0.182424E+09 0.00 0.00
November 67310203.96 0.663840E+09 0.179011E+09 58188951.25 0.120822E+09 0.00 0.00
December 47552453.20 0.938196E+09 0.142460E+09 60840402.84 81619909.36 0.00 0.00
               
Annual Sum or Average 0.440150E+10 0.584671E+10 0.482676E+10 0.209054E+10 0.273622E+10 0.00 0.00
Minimum of Months 47552453.20 0.157112E+09 0.142460E+09 58188951.25 81619909.36 0.00 0.00
Maximum of Months 0.776996E+09 0.101214E+10 0.653641E+09 0.302028E+09 0.353215E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ELEVATORCOREFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM219

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 17625771.45 0.245274E+09 53074673.03 21930893.58 31143779.45 0.00 0.00
February 29473436.67 0.183659E+09 63110617.56 27612682.59 35497934.97 0.00 0.00
March 61301920.22 0.134727E+09 95228230.66 37701094.67 57527135.99 0.00 0.00
April 97995686.97 96596022.99 0.113089E+09 49517764.99 63571687.62 0.00 0.00
May 0.151022E+09 59386474.46 0.146930E+09 64176563.55 82753299.08 0.00 0.00
June 0.183328E+09 40823198.67 0.156495E+09 68191201.21 88303827.57 0.00 0.00
July 0.196426E+09 37286552.56 0.163410E+09 75506884.86 87903306.11 0.00 0.00
August 0.162875E+09 43919997.14 0.137556E+09 59187991.28 78367698.97 0.00 0.00
September 0.130923E+09 67272256.11 0.119272E+09 56502671.97 62769167.18 0.00 0.00
October 57435522.83 0.104913E+09 78157059.18 32550949.09 45606110.09 0.00 0.00
November 17645827.28 0.156999E+09 44752837.98 14547237.81 30205600.17 0.00 0.00
December 12464418.82 0.223919E+09 35615078.05 15210100.71 20404977.34 0.00 0.00
               
Annual Sum or Average 0.111852E+10 0.139478E+10 0.120669E+10 0.522636E+09 0.684055E+09 0.00 0.00
Minimum of Months 12464418.82 37286552.56 35615078.05 14547237.81 20404977.34 0.00 0.00
Maximum of Months 0.196426E+09 0.245274E+09 0.163410E+09 75506884.86 88303827.57 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM220_223

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 86203009.47 0.811802E+09 0.212299E+09 87723574.31 0.124575E+09 0.00 0.00
February 0.138739E+09 0.582143E+09 0.252442E+09 0.110451E+09 0.141992E+09 0.00 0.00
March 0.289155E+09 0.419508E+09 0.380913E+09 0.150804E+09 0.230109E+09 0.00 0.00
April 0.442710E+09 0.283298E+09 0.452358E+09 0.198071E+09 0.254287E+09 0.00 0.00
May 0.681913E+09 0.157691E+09 0.587719E+09 0.256706E+09 0.331013E+09 0.00 0.00
June 0.812101E+09 95739822.09 0.625980E+09 0.272765E+09 0.353215E+09 0.00 0.00
July 0.870099E+09 81801352.00 0.653641E+09 0.302028E+09 0.351613E+09 0.00 0.00
August 0.730691E+09 0.100570E+09 0.550223E+09 0.236752E+09 0.313471E+09 0.00 0.00
September 0.582731E+09 0.181065E+09 0.477087E+09 0.226011E+09 0.251077E+09 0.00 0.00
October 0.275937E+09 0.312533E+09 0.312628E+09 0.130204E+09 0.182424E+09 0.00 0.00
November 89494822.94 0.489675E+09 0.179011E+09 58188951.25 0.120822E+09 0.00 0.00
December 59201706.03 0.736365E+09 0.142460E+09 60840402.84 81619909.36 0.00 0.00
               
Annual Sum or Average 0.505897E+10 0.425219E+10 0.482676E+10 0.209054E+10 0.273622E+10 0.00 0.00
Minimum of Months 59201706.03 81801352.00 0.142460E+09 58188951.25 81619909.36 0.00 0.00
Maximum of Months 0.870099E+09 0.811802E+09 0.653641E+09 0.302028E+09 0.353215E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM224

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 21827401.82 0.199460E+09 53074673.03 21930893.58 31143779.45 0.00 0.00
February 35172781.38 0.142641E+09 63110617.56 27612682.59 35497934.97 0.00 0.00
March 73236008.41 0.102888E+09 95228230.66 37701094.67 57527135.99 0.00 0.00
April 0.111122E+09 69760928.97 0.113089E+09 49517764.99 63571687.62 0.00 0.00
May 0.170146E+09 39153503.17 0.146930E+09 64176563.55 82753299.08 0.00 0.00
June 0.202290E+09 23995733.49 0.156495E+09 68191201.21 88303827.57 0.00 0.00
July 0.216621E+09 20639697.46 0.163410E+09 75506884.86 87903306.11 0.00 0.00
August 0.181844E+09 25373951.26 0.137556E+09 59187991.28 78367698.97 0.00 0.00
September 0.145301E+09 45262150.86 0.119272E+09 56502671.97 62769167.18 0.00 0.00
October 69270226.87 77500005.71 78157059.18 32550949.09 45606110.09 0.00 0.00
November 22617310.24 0.120448E+09 44752837.98 14547237.81 30205600.17 0.00 0.00
December 14974794.64 0.180604E+09 35615078.05 15210100.71 20404977.34 0.00 0.00
               
Annual Sum or Average 0.126442E+10 0.104773E+10 0.120669E+10 0.522636E+09 0.684055E+09 0.00 0.00
Minimum of Months 14974794.64 20639697.46 35615078.05 14547237.81 20404977.34 0.00 0.00
Maximum of Months 0.216621E+09 0.199460E+09 0.163410E+09 75506884.86 88303827.57 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONTSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONTSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: REARSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDORFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 80575702.83 0.309653E+09 0.141447E+09 83318398.15 58129002.58 0.00 0.00
February 91759067.05 0.225342E+09 0.142372E+09 81633068.74 60738569.56 0.00 0.00
March 0.113305E+09 0.176774E+09 0.149405E+09 58309641.76 91095668.30 0.00 0.00
April 0.129734E+09 0.124252E+09 0.141339E+09 47100717.85 94238442.48 0.00 0.00
May 0.145208E+09 73519715.78 0.141087E+09 25213321.40 0.115873E+09 0.00 0.00
June 0.173912E+09 45995505.83 0.143108E+09 21925932.80 0.121182E+09 0.00 0.00
July 0.190642E+09 40662952.93 0.149005E+09 26410647.16 0.122594E+09 0.00 0.00
August 0.191259E+09 50228742.27 0.147890E+09 34271169.12 0.113619E+09 0.00 0.00
September 0.180007E+09 83306872.25 0.151998E+09 59263194.17 92735128.52 0.00 0.00
October 0.148995E+09 0.131095E+09 0.154691E+09 78981980.71 75709043.99 0.00 0.00
November 77616803.11 0.192945E+09 0.110702E+09 56858615.09 53843114.89 0.00 0.00
December 76514685.45 0.284640E+09 0.112889E+09 75314095.27 37575390.12 0.00 0.00
               
Annual Sum or Average 0.159953E+10 0.173841E+10 0.168593E+10 0.648601E+09 0.103733E+10 0.00 0.00
Minimum of Months 76514685.45 40662952.93 0.110702E+09 21925932.80 37575390.12 0.00 0.00
Maximum of Months 0.191259E+09 0.309653E+09 0.154691E+09 83318398.15 0.122594E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: REARSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM301

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 26087707.63 0.174559E+09 52458189.72 21280432.27 31177757.46 0.00 0.00
February 48273531.75 0.125933E+09 68924134.55 33807939.06 35116195.48 0.00 0.00
March 75676480.20 90547237.76 91625245.77 34132416.35 57492829.42 0.00 0.00
April 0.137423E+09 65680080.07 0.129261E+09 63875991.27 65385081.43 0.00 0.00
May 0.154673E+09 43602953.89 0.133932E+09 53510203.67 80422078.98 0.00 0.00
June 0.191312E+09 30167044.10 0.151852E+09 65685754.02 86165974.55 0.00 0.00
July 0.217988E+09 28074289.72 0.168834E+09 80236719.61 88597650.50 0.00 0.00
August 0.190999E+09 32659819.32 0.147147E+09 67297870.25 79849060.43 0.00 0.00
September 0.139906E+09 48589009.43 0.115554E+09 54781957.48 60771914.63 0.00 0.00
October 83014096.62 72932077.80 83575563.73 37254627.14 46320936.60 0.00 0.00
November 32919169.68 0.103856E+09 48381292.70 17970194.22 30411098.49 0.00 0.00
December 23204484.33 0.154763E+09 38613006.01 18364276.38 20248729.63 0.00 0.00
               
Annual Sum or Average 0.132148E+10 0.971363E+09 0.123016E+10 0.548198E+09 0.681959E+09 0.00 0.00
Minimum of Months 23204484.33 28074289.72 38613006.01 17970194.22 20248729.63 0.00 0.00
Maximum of Months 0.217988E+09 0.174559E+09 0.168834E+09 80236719.61 88597650.50 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM302_305

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.101971E+09 0.723297E+09 0.209833E+09 85121729.06 0.124711E+09 0.00 0.00
February 0.189290E+09 0.527586E+09 0.275697E+09 0.135232E+09 0.140465E+09 0.00 0.00
March 0.295203E+09 0.385637E+09 0.366501E+09 0.136530E+09 0.229971E+09 0.00 0.00
April 0.543370E+09 0.280889E+09 0.517044E+09 0.255504E+09 0.261540E+09 0.00 0.00
May 0.613420E+09 0.183509E+09 0.535729E+09 0.214041E+09 0.321688E+09 0.00 0.00
June 0.762597E+09 0.126427E+09 0.607407E+09 0.262743E+09 0.344664E+09 0.00 0.00
July 0.869540E+09 0.117595E+09 0.675337E+09 0.320947E+09 0.354391E+09 0.00 0.00
August 0.761297E+09 0.136763E+09 0.588588E+09 0.269191E+09 0.319396E+09 0.00 0.00
September 0.555168E+09 0.204434E+09 0.462215E+09 0.219128E+09 0.243088E+09 0.00 0.00
October 0.326160E+09 0.308724E+09 0.334302E+09 0.149019E+09 0.185284E+09 0.00 0.00
November 0.127842E+09 0.437969E+09 0.193525E+09 71880776.87 0.121644E+09 0.00 0.00
December 90401206.36 0.648548E+09 0.154452E+09 73457105.52 80994918.51 0.00 0.00
               
Annual Sum or Average 0.523626E+10 0.408138E+10 0.492063E+10 0.219279E+10 0.272784E+10 0.00 0.00
Minimum of Months 90401206.36 0.117595E+09 0.154452E+09 71880776.87 80994918.51 0.00 0.00
Maximum of Months 0.869540E+09 0.723297E+09 0.675337E+09 0.320947E+09 0.354391E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM306_308

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.101955E+09 0.749847E+09 0.213476E+09 86599618.26 0.126876E+09 0.00 0.00
February 0.189751E+09 0.548659E+09 0.280483E+09 0.137580E+09 0.142903E+09 0.00 0.00
March 0.295311E+09 0.402857E+09 0.372864E+09 0.138900E+09 0.233964E+09 0.00 0.00
April 0.548811E+09 0.291964E+09 0.526021E+09 0.259940E+09 0.266081E+09 0.00 0.00
May 0.621659E+09 0.188025E+09 0.545030E+09 0.217757E+09 0.327273E+09 0.00 0.00
June 0.775377E+09 0.128032E+09 0.617952E+09 0.267305E+09 0.350647E+09 0.00 0.00
July 0.884652E+09 0.118518E+09 0.687062E+09 0.326519E+09 0.360543E+09 0.00 0.00
August 0.774266E+09 0.138233E+09 0.598806E+09 0.273865E+09 0.324941E+09 0.00 0.00
September 0.563491E+09 0.208725E+09 0.470240E+09 0.222932E+09 0.247308E+09 0.00 0.00
October 0.328508E+09 0.319477E+09 0.340106E+09 0.151606E+09 0.188500E+09 0.00 0.00
November 0.127778E+09 0.455731E+09 0.196885E+09 73128775.76 0.123756E+09 0.00 0.00
December 90427881.69 0.674004E+09 0.157134E+09 74732472.73 82401042.78 0.00 0.00
               
Annual Sum or Average 0.530199E+10 0.422407E+10 0.500606E+10 0.223086E+10 0.277519E+10 0.00 0.00
Minimum of Months 90427881.69 0.118518E+09 0.157134E+09 73128775.76 82401042.78 0.00 0.00
Maximum of Months 0.884652E+09 0.749847E+09 0.687062E+09 0.326519E+09 0.360543E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM309_312

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 93585909.95 0.812423E+09 0.209833E+09 85121729.06 0.124711E+09 0.00 0.00
February 0.178150E+09 0.589080E+09 0.275697E+09 0.135232E+09 0.140465E+09 0.00 0.00
March 0.280544E+09 0.422467E+09 0.366501E+09 0.136530E+09 0.229971E+09 0.00 0.00
April 0.540846E+09 0.284372E+09 0.517044E+09 0.255504E+09 0.261540E+09 0.00 0.00
May 0.624693E+09 0.163476E+09 0.535729E+09 0.214041E+09 0.321688E+09 0.00 0.00
June 0.790734E+09 98697100.65 0.607407E+09 0.262743E+09 0.344664E+09 0.00 0.00
July 0.903344E+09 85721000.91 0.675337E+09 0.320947E+09 0.354391E+09 0.00 0.00
August 0.789464E+09 0.105556E+09 0.588588E+09 0.269191E+09 0.319396E+09 0.00 0.00
September 0.566779E+09 0.182931E+09 0.462215E+09 0.219128E+09 0.243088E+09 0.00 0.00
October 0.317892E+09 0.315768E+09 0.334302E+09 0.149019E+09 0.185284E+09 0.00 0.00
November 0.119789E+09 0.483184E+09 0.193525E+09 71880776.87 0.121644E+09 0.00 0.00
December 84136594.13 0.731790E+09 0.154452E+09 73457105.52 80994918.51 0.00 0.00
               
Annual Sum or Average 0.528996E+10 0.427547E+10 0.492063E+10 0.219279E+10 0.272784E+10 0.00 0.00
Minimum of Months 84136594.13 85721000.91 0.154452E+09 71880776.87 80994918.51 0.00 0.00
Maximum of Months 0.903344E+09 0.812423E+09 0.675337E+09 0.320947E+09 0.354391E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM313

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 25468122.82 0.180059E+09 52458189.72 21280432.27 31177757.46 0.00 0.00
February 47295978.71 0.131204E+09 68924134.55 33807939.06 35116195.48 0.00 0.00
March 74284822.22 94726951.93 91625245.77 34132416.35 57492829.42 0.00 0.00
April 0.137028E+09 67445230.97 0.129261E+09 63875991.27 65385081.43 0.00 0.00
May 0.155651E+09 43170591.72 0.133932E+09 53510203.67 80422078.98 0.00 0.00
June 0.193037E+09 29081039.31 0.151852E+09 65685754.02 86165974.55 0.00 0.00
July 0.219655E+09 26953488.78 0.168834E+09 80236719.61 88597650.50 0.00 0.00
August 0.192314E+09 31872326.42 0.147147E+09 67297870.25 79849060.43 0.00 0.00
September 0.139980E+09 49094200.36 0.115554E+09 54781957.48 60771914.63 0.00 0.00
October 82032184.39 75747156.55 83575563.73 37254627.14 46320936.60 0.00 0.00
November 32113718.64 0.108384E+09 48381292.70 17970194.22 30411098.49 0.00 0.00
December 22549261.35 0.161635E+09 38613006.01 18364276.38 20248729.63 0.00 0.00
               
Annual Sum or Average 0.132141E+10 0.999373E+09 0.123016E+10 0.548198E+09 0.681959E+09 0.00 0.00
Minimum of Months 22549261.35 26953488.78 38613006.01 17970194.22 20248729.63 0.00 0.00
Maximum of Months 0.219655E+09 0.180059E+09 0.168834E+09 80236719.61 88597650.50 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM314

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 21980024.35 0.197115E+09 52927752.82 21870185.22 31057567.60 0.00 0.00
February 35279410.66 0.141379E+09 62935916.04 27536246.10 35399669.94 0.00 0.00
March 73463223.51 0.102093E+09 94964621.74 37596731.77 57367889.97 0.00 0.00
April 0.110912E+09 69346710.53 0.112776E+09 49380691.59 63395708.86 0.00 0.00
May 0.169596E+09 39403623.44 0.146523E+09 63998912.16 82524222.06 0.00 0.00
June 0.201411E+09 24266815.65 0.156062E+09 68002436.64 88059385.55 0.00 0.00
July 0.215518E+09 21141684.62 0.162958E+09 75297869.26 87659972.69 0.00 0.00
August 0.181022E+09 25886065.93 0.137175E+09 59024149.09 78150762.09 0.00 0.00
September 0.145172E+09 45073964.99 0.118942E+09 56346263.19 62595410.10 0.00 0.00
October 70120247.52 76263692.01 77940706.36 32460842.65 45479863.71 0.00 0.00
November 23046472.29 0.118071E+09 44628954.05 14506968.64 30121985.40 0.00 0.00
December 15086820.06 0.178080E+09 35516489.11 15167996.63 20348492.48 0.00 0.00
               
Annual Sum or Average 0.126261E+10 0.103812E+10 0.120335E+10 0.521189E+09 0.682161E+09 0.00 0.00
Minimum of Months 15086820.06 21141684.62 35516489.11 14506968.64 20348492.48 0.00 0.00
Maximum of Months 0.215518E+09 0.197115E+09 0.162958E+09 75297869.26 88059385.55 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM315_318

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 83010239.28 0.837797E+09 0.211711E+09 87480740.89 0.124230E+09 0.00 0.00
February 0.133960E+09 0.604467E+09 0.251744E+09 0.110145E+09 0.141599E+09 0.00 0.00
March 0.279176E+09 0.438810E+09 0.379858E+09 0.150387E+09 0.229472E+09 0.00 0.00
April 0.432268E+09 0.298720E+09 0.451106E+09 0.197523E+09 0.253583E+09 0.00 0.00
May 0.667602E+09 0.169076E+09 0.586093E+09 0.255996E+09 0.330097E+09 0.00 0.00
June 0.797453E+09 0.105161E+09 0.624247E+09 0.272010E+09 0.352238E+09 0.00 0.00
July 0.854600E+09 91546155.51 0.651831E+09 0.301191E+09 0.350640E+09 0.00 0.00
August 0.716865E+09 0.111277E+09 0.548700E+09 0.236097E+09 0.312603E+09 0.00 0.00
September 0.572694E+09 0.191665E+09 0.475767E+09 0.225385E+09 0.250382E+09 0.00 0.00
October 0.268449E+09 0.324375E+09 0.311763E+09 0.129843E+09 0.181919E+09 0.00 0.00
November 85868560.33 0.508722E+09 0.178516E+09 58027874.57 0.120488E+09 0.00 0.00
December 57132980.74 0.762379E+09 0.142066E+09 60671986.50 81393969.94 0.00 0.00
               
Annual Sum or Average 0.494908E+10 0.444399E+10 0.481340E+10 0.208476E+10 0.272864E+10 0.00 0.00
Minimum of Months 57132980.74 91546155.51 0.142066E+09 58027874.57 81393969.94 0.00 0.00
Maximum of Months 0.854600E+09 0.837797E+09 0.651831E+09 0.301191E+09 0.352238E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ELEVATORCOREFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM319

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 20277882.71 0.213034E+09 52927752.82 21870185.22 31057567.60 0.00 0.00
February 32672482.76 0.156208E+09 62935916.04 27536246.10 35399669.94 0.00 0.00
March 67937043.34 0.115983E+09 94964621.74 37596731.77 57367889.97 0.00 0.00
April 0.104562E+09 82314524.50 0.112776E+09 49380691.59 63395708.86 0.00 0.00
May 0.159739E+09 50420706.65 0.146523E+09 63998912.16 82524222.06 0.00 0.00
June 0.190417E+09 33533422.35 0.156062E+09 68002436.64 88059385.55 0.00 0.00
July 0.203930E+09 30180036.59 0.162958E+09 75297869.26 87659972.69 0.00 0.00
August 0.170425E+09 35835930.23 0.137175E+09 59024149.09 78150762.09 0.00 0.00
September 0.137133E+09 56547316.24 0.118942E+09 56346263.19 62595410.10 0.00 0.00
October 64592323.17 89364488.90 77940706.36 32460842.65 45479863.71 0.00 0.00
November 20522394.54 0.133273E+09 44628954.05 14506968.64 30121985.40 0.00 0.00
December 13924720.75 0.194341E+09 35516489.11 15167996.63 20348492.48 0.00 0.00
               
Annual Sum or Average 0.118613E+10 0.119103E+10 0.120335E+10 0.521189E+09 0.682161E+09 0.00 0.00
Minimum of Months 13924720.75 30180036.59 35516489.11 14506968.64 20348492.48 0.00 0.00
Maximum of Months 0.203930E+09 0.213034E+09 0.162958E+09 75297869.26 88059385.55 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM320_323

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 86782056.61 0.800192E+09 0.211711E+09 87480740.89 0.124230E+09 0.00 0.00
February 0.139508E+09 0.573381E+09 0.251744E+09 0.110145E+09 0.141599E+09 0.00 0.00
March 0.290950E+09 0.413207E+09 0.379858E+09 0.150387E+09 0.229472E+09 0.00 0.00
April 0.443701E+09 0.278170E+09 0.451106E+09 0.197523E+09 0.253583E+09 0.00 0.00
May 0.682935E+09 0.154920E+09 0.586093E+09 0.255996E+09 0.330097E+09 0.00 0.00
June 0.812491E+09 93407454.30 0.624247E+09 0.272010E+09 0.352238E+09 0.00 0.00
July 0.870258E+09 79764871.05 0.651831E+09 0.301191E+09 0.350640E+09 0.00 0.00
August 0.731592E+09 98079952.42 0.548700E+09 0.236097E+09 0.312603E+09 0.00 0.00
September 0.584729E+09 0.176113E+09 0.475767E+09 0.225385E+09 0.250382E+09 0.00 0.00
October 0.279943E+09 0.304384E+09 0.311763E+09 0.129843E+09 0.181919E+09 0.00 0.00
November 91422513.18 0.478164E+09 0.178516E+09 58027874.57 0.120488E+09 0.00 0.00
December 59687174.18 0.723497E+09 0.142066E+09 60671986.50 81393969.94 0.00 0.00
               
Annual Sum or Average 0.507400E+10 0.417328E+10 0.481340E+10 0.208476E+10 0.272864E+10 0.00 0.00
Minimum of Months 59687174.18 79764871.05 0.142066E+09 58027874.57 81393969.94 0.00 0.00
Maximum of Months 0.870258E+09 0.800192E+09 0.651831E+09 0.301191E+09 0.352238E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM324

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 23056265.03 0.185596E+09 52927752.82 21870185.22 31057567.60 0.00 0.00
February 36419089.99 0.133345E+09 62935916.04 27536246.10 35399669.94 0.00 0.00
March 74692618.28 98074112.12 94964621.74 37596731.77 57367889.97 0.00 0.00
April 0.111018E+09 68840678.73 0.112776E+09 49380691.59 63395708.86 0.00 0.00
May 0.167886E+09 41933524.32 0.146523E+09 63998912.16 82524222.06 0.00 0.00
June 0.197298E+09 27297891.44 0.156062E+09 68002436.64 88059385.55 0.00 0.00
July 0.210854E+09 24356172.36 0.162958E+09 75297869.26 87659972.69 0.00 0.00
August 0.177373E+09 29097095.88 0.137175E+09 59024149.09 78150762.09 0.00 0.00
September 0.143250E+09 47747108.82 0.118942E+09 56346263.19 62595410.10 0.00 0.00
October 70758618.23 76282639.83 77940706.36 32460842.65 45479863.71 0.00 0.00
November 23697487.41 0.113284E+09 44628954.05 14506968.64 30121985.40 0.00 0.00
December 15704792.35 0.167922E+09 35516489.11 15167996.63 20348492.48 0.00 0.00
               
Annual Sum or Average 0.125201E+10 0.101378E+10 0.120335E+10 0.521189E+09 0.682161E+09 0.00 0.00
Minimum of Months 15704792.35 24356172.36 35516489.11 14506968.64 20348492.48 0.00 0.00
Maximum of Months 0.210854E+09 0.185596E+09 0.162958E+09 75297869.26 88059385.55 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONTSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONTSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: REARSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDORFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 81636959.44 0.303398E+09 0.141447E+09 83318398.15 58129002.58 0.00 0.00
February 92660546.45 0.219793E+09 0.142372E+09 81633068.74 60738569.56 0.00 0.00
March 0.113961E+09 0.171221E+09 0.149405E+09 58309641.76 91095668.30 0.00 0.00
April 0.129300E+09 0.118567E+09 0.141339E+09 47100717.85 94238442.48 0.00 0.00
May 0.144889E+09 68182306.77 0.141087E+09 25213321.40 0.115873E+09 0.00 0.00
June 0.173268E+09 42607001.11 0.143108E+09 21925932.80 0.121182E+09 0.00 0.00
July 0.189659E+09 37975533.95 0.149005E+09 26410647.16 0.122594E+09 0.00 0.00
August 0.190364E+09 46664152.15 0.147890E+09 34271169.12 0.113619E+09 0.00 0.00
September 0.180137E+09 77560115.13 0.151998E+09 59263194.17 92735128.52 0.00 0.00
October 0.150051E+09 0.124680E+09 0.154691E+09 78981980.71 75709043.99 0.00 0.00
November 78736087.97 0.186362E+09 0.110702E+09 56858615.09 53843114.89 0.00 0.00
December 77418519.13 0.278208E+09 0.112889E+09 75314095.27 37575390.12 0.00 0.00
               
Annual Sum or Average 0.160208E+10 0.167522E+10 0.168593E+10 0.648601E+09 0.103733E+10 0.00 0.00
Minimum of Months 77418519.13 37975533.95 0.110702E+09 21925932.80 37575390.12 0.00 0.00
Maximum of Months 0.190364E+09 0.303398E+09 0.154691E+09 83318398.15 0.122594E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: REARSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM401

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 24870634.94 0.191732E+09 52458189.72 21280432.27 31177757.46 0.00 0.00
February 46553714.80 0.137693E+09 68924134.55 33807939.06 35116195.48 0.00 0.00
March 73335108.00 97518260.71 91625245.77 34132416.35 57492829.42 0.00 0.00
April 0.136263E+09 64874674.61 0.129261E+09 63875991.27 65385081.43 0.00 0.00
May 0.154760E+09 37856087.68 0.133932E+09 53510203.67 80422078.98 0.00 0.00
June 0.194915E+09 22961267.56 0.151852E+09 65685754.02 86165974.55 0.00 0.00
July 0.222611E+09 20172946.00 0.168834E+09 80236719.61 88597650.50 0.00 0.00
August 0.194571E+09 24870625.75 0.147147E+09 67297870.25 79849060.43 0.00 0.00
September 0.141349E+09 42313315.26 0.115554E+09 54781957.48 60771914.63 0.00 0.00
October 82175448.05 72077293.11 83575563.73 37254627.14 46320936.60 0.00 0.00
November 32209152.97 0.111454E+09 48381292.70 17970194.22 30411098.49 0.00 0.00
December 22441163.68 0.171345E+09 38613006.01 18364276.38 20248729.63 0.00 0.00
               
Annual Sum or Average 0.132605E+10 0.994869E+09 0.123016E+10 0.548198E+09 0.681959E+09 0.00 0.00
Minimum of Months 22441163.68 20172946.00 38613006.01 17970194.22 20248729.63 0.00 0.00
Maximum of Months 0.222611E+09 0.191732E+09 0.168834E+09 80236719.61 88597650.50 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM402_405

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.104906E+09 0.683447E+09 0.209833E+09 85121729.06 0.124711E+09 0.00 0.00
February 0.192475E+09 0.489715E+09 0.275697E+09 0.135232E+09 0.140465E+09 0.00 0.00
March 0.298687E+09 0.348895E+09 0.366501E+09 0.136530E+09 0.229971E+09 0.00 0.00
April 0.539259E+09 0.252448E+09 0.517044E+09 0.255504E+09 0.261540E+09 0.00 0.00
May 0.604226E+09 0.167325E+09 0.535729E+09 0.214041E+09 0.321688E+09 0.00 0.00
June 0.752206E+09 0.115354E+09 0.607407E+09 0.262743E+09 0.344664E+09 0.00 0.00
July 0.858021E+09 0.108007E+09 0.675337E+09 0.320947E+09 0.354391E+09 0.00 0.00
August 0.749933E+09 0.125722E+09 0.588588E+09 0.269191E+09 0.319396E+09 0.00 0.00
September 0.550251E+09 0.185323E+09 0.462215E+09 0.219128E+09 0.243088E+09 0.00 0.00
October 0.328635E+09 0.276315E+09 0.334302E+09 0.149019E+09 0.185284E+09 0.00 0.00
November 0.131730E+09 0.397988E+09 0.193525E+09 71880776.87 0.121644E+09 0.00 0.00
December 92922200.77 0.603526E+09 0.154452E+09 73457105.52 80994918.51 0.00 0.00
               
Annual Sum or Average 0.520325E+10 0.375406E+10 0.492063E+10 0.219279E+10 0.272784E+10 0.00 0.00
Minimum of Months 92922200.77 0.108007E+09 0.154452E+09 71880776.87 80994918.51 0.00 0.00
Maximum of Months 0.858021E+09 0.683447E+09 0.675337E+09 0.320947E+09 0.354391E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM406_408

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.105417E+09 0.701022E+09 0.213476E+09 86599618.26 0.126876E+09 0.00 0.00
February 0.193224E+09 0.505193E+09 0.280483E+09 0.137580E+09 0.142903E+09 0.00 0.00
March 0.298780E+09 0.361979E+09 0.372864E+09 0.138900E+09 0.233964E+09 0.00 0.00
April 0.544116E+09 0.262075E+09 0.526021E+09 0.259940E+09 0.266081E+09 0.00 0.00
May 0.611713E+09 0.171745E+09 0.545030E+09 0.217757E+09 0.327273E+09 0.00 0.00
June 0.763858E+09 0.117367E+09 0.617952E+09 0.267305E+09 0.350647E+09 0.00 0.00
July 0.871849E+09 0.109476E+09 0.687062E+09 0.326519E+09 0.360543E+09 0.00 0.00
August 0.761768E+09 0.127679E+09 0.598806E+09 0.273865E+09 0.324941E+09 0.00 0.00
September 0.557694E+09 0.189789E+09 0.470240E+09 0.222932E+09 0.247308E+09 0.00 0.00
October 0.330291E+09 0.286231E+09 0.340106E+09 0.151606E+09 0.188500E+09 0.00 0.00
November 0.131600E+09 0.411437E+09 0.196885E+09 73128775.76 0.123756E+09 0.00 0.00
December 93238579.65 0.620118E+09 0.157134E+09 74732472.73 82401042.78 0.00 0.00
               
Annual Sum or Average 0.526355E+10 0.386411E+10 0.500606E+10 0.223086E+10 0.277519E+10 0.00 0.00
Minimum of Months 93238579.65 0.109476E+09 0.157134E+09 73128775.76 82401042.78 0.00 0.00
Maximum of Months 0.871849E+09 0.701022E+09 0.687062E+09 0.326519E+09 0.360543E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM409_412

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 95648804.30 0.793537E+09 0.209833E+09 85121729.06 0.124711E+09 0.00 0.00
February 0.179320E+09 0.573450E+09 0.275697E+09 0.135232E+09 0.140465E+09 0.00 0.00
March 0.279977E+09 0.409085E+09 0.366501E+09 0.136530E+09 0.229971E+09 0.00 0.00
April 0.535604E+09 0.271956E+09 0.517044E+09 0.255504E+09 0.261540E+09 0.00 0.00
May 0.615464E+09 0.154705E+09 0.535729E+09 0.214041E+09 0.321688E+09 0.00 0.00
June 0.781280E+09 91704752.70 0.607407E+09 0.262743E+09 0.344664E+09 0.00 0.00
July 0.893360E+09 79243141.87 0.675337E+09 0.320947E+09 0.354391E+09 0.00 0.00
August 0.780379E+09 98794255.69 0.588588E+09 0.269191E+09 0.319396E+09 0.00 0.00
September 0.561331E+09 0.173425E+09 0.462215E+09 0.219128E+09 0.243088E+09 0.00 0.00
October 0.316308E+09 0.302508E+09 0.334302E+09 0.149019E+09 0.185284E+09 0.00 0.00
November 0.121051E+09 0.467026E+09 0.193525E+09 71880776.87 0.121644E+09 0.00 0.00
December 85807050.58 0.712814E+09 0.154452E+09 73457105.52 80994918.51 0.00 0.00
               
Annual Sum or Average 0.524553E+10 0.412825E+10 0.492063E+10 0.219279E+10 0.272784E+10 0.00 0.00
Minimum of Months 85807050.58 79243141.87 0.154452E+09 71880776.87 80994918.51 0.00 0.00
Maximum of Months 0.893360E+09 0.793537E+09 0.675337E+09 0.320947E+09 0.354391E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM413

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 26105324.53 0.171560E+09 52458189.72 21280432.27 31177757.46 0.00 0.00
February 48052177.20 0.122960E+09 68924134.55 33807939.06 35116195.48 0.00 0.00
March 75272533.77 86981754.44 91625245.77 34132416.35 57492829.42 0.00 0.00
April 0.136245E+09 61582056.18 0.129261E+09 63875991.27 65385081.43 0.00 0.00
May 0.153595E+09 40275517.35 0.133932E+09 53510203.67 80422078.98 0.00 0.00
June 0.190390E+09 27323726.97 0.151852E+09 65685754.02 86165974.55 0.00 0.00
July 0.216744E+09 25612747.95 0.168834E+09 80236719.61 88597650.50 0.00 0.00
August 0.189526E+09 30175189.93 0.147147E+09 67297870.25 79849060.43 0.00 0.00
September 0.138877E+09 45465127.40 0.115554E+09 54781957.48 60771914.63 0.00 0.00
October 82659721.88 69000864.12 83575563.73 37254627.14 46320936.60 0.00 0.00
November 33073494.69 99706954.09 48381292.70 17970194.22 30411098.49 0.00 0.00
December 23136184.32 0.151685E+09 38613006.01 18364276.38 20248729.63 0.00 0.00
               
Annual Sum or Average 0.131368E+10 0.932329E+09 0.123016E+10 0.548198E+09 0.681959E+09 0.00 0.00
Minimum of Months 23136184.32 25612747.95 38613006.01 17970194.22 20248729.63 0.00 0.00
Maximum of Months 0.216744E+09 0.171560E+09 0.168834E+09 80236719.61 88597650.50 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM414

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 24492575.12 0.172989E+09 52927752.82 21870185.22 31057567.60 0.00 0.00
February 37817247.97 0.124447E+09 62935916.04 27536246.10 35399669.94 0.00 0.00
March 76152847.43 90716402.75 94964621.74 37596731.77 57367889.97 0.00 0.00
April 0.110295E+09 63977389.68 0.112776E+09 49380691.59 63395708.86 0.00 0.00
May 0.165584E+09 40317828.91 0.146523E+09 63998912.16 82524222.06 0.00 0.00
June 0.193715E+09 26674708.04 0.156062E+09 68002436.64 88059385.55 0.00 0.00
July 0.206500E+09 24393740.94 0.162958E+09 75297869.26 87659972.69 0.00 0.00
August 0.173519E+09 29069394.43 0.137175E+09 59024149.09 78150762.09 0.00 0.00
September 0.141399E+09 45715938.24 0.118942E+09 56346263.19 62595410.10 0.00 0.00
October 71790196.73 71353262.60 77940706.36 32460842.65 45479863.71 0.00 0.00
November 25076626.28 0.103736E+09 44628954.05 14506968.64 30121985.40 0.00 0.00
December 16761231.77 0.154932E+09 35516489.11 15167996.63 20348492.48 0.00 0.00
               
Annual Sum or Average 0.124310E+10 0.948323E+09 0.120335E+10 0.521189E+09 0.682161E+09 0.00 0.00
Minimum of Months 16761231.77 24393740.94 35516489.11 14506968.64 20348492.48 0.00 0.00
Maximum of Months 0.206500E+09 0.172989E+09 0.162958E+09 75297869.26 88059385.55 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM415_418

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 87305207.88 0.788103E+09 0.211711E+09 87480740.89 0.124230E+09 0.00 0.00
February 0.138914E+09 0.565601E+09 0.251744E+09 0.110145E+09 0.141599E+09 0.00 0.00
March 0.286605E+09 0.407458E+09 0.379858E+09 0.150387E+09 0.229472E+09 0.00 0.00
April 0.436659E+09 0.272419E+09 0.451106E+09 0.197523E+09 0.253583E+09 0.00 0.00
May 0.672131E+09 0.150758E+09 0.586093E+09 0.255996E+09 0.330097E+09 0.00 0.00
June 0.801212E+09 90250229.06 0.624247E+09 0.272010E+09 0.352238E+09 0.00 0.00
July 0.858122E+09 77010969.74 0.651831E+09 0.301191E+09 0.350640E+09 0.00 0.00
August 0.720518E+09 95447621.29 0.548700E+09 0.236097E+09 0.312603E+09 0.00 0.00
September 0.577061E+09 0.171233E+09 0.475767E+09 0.225385E+09 0.250382E+09 0.00 0.00
October 0.275408E+09 0.297918E+09 0.311763E+09 0.129843E+09 0.181919E+09 0.00 0.00
November 90472907.96 0.470149E+09 0.178516E+09 58027874.57 0.120488E+09 0.00 0.00
December 59869174.25 0.712775E+09 0.142066E+09 60671986.50 81393969.94 0.00 0.00
               
Annual Sum or Average 0.500428E+10 0.409912E+10 0.481340E+10 0.208476E+10 0.272864E+10 0.00 0.00
Minimum of Months 59869174.25 77010969.74 0.142066E+09 58027874.57 81393969.94 0.00 0.00
Maximum of Months 0.858122E+09 0.788103E+09 0.651831E+09 0.301191E+09 0.352238E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ELEVATORCOREFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM419

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 21484931.52 0.199801E+09 52927752.82 21870185.22 31057567.60 0.00 0.00
February 34390651.90 0.143479E+09 62935916.04 27536246.10 35399669.94 0.00 0.00
March 71279712.20 0.103457E+09 94964621.74 37596731.77 57367889.97 0.00 0.00
April 0.108822E+09 69414824.86 0.112776E+09 49380691.59 63395708.86 0.00 0.00
May 0.167338E+09 38640921.69 0.146523E+09 63998912.16 82524222.06 0.00 0.00
June 0.199811E+09 23213721.26 0.156062E+09 68002436.64 88059385.55 0.00 0.00
July 0.214088E+09 19864417.87 0.162958E+09 75297869.26 87659972.69 0.00 0.00
August 0.179632E+09 24618307.80 0.137175E+09 59024149.09 78150762.09 0.00 0.00
September 0.143896E+09 43770384.16 0.118942E+09 56346263.19 62595410.10 0.00 0.00
October 68497795.26 75755978.72 77940706.36 32460842.65 45479863.71 0.00 0.00
November 22369818.86 0.119401E+09 44628954.05 14506968.64 30121985.40 0.00 0.00
December 14775042.93 0.180641E+09 35516489.11 15167996.63 20348492.48 0.00 0.00
               
Annual Sum or Average 0.124638E+10 0.104206E+10 0.120335E+10 0.521189E+09 0.682161E+09 0.00 0.00
Minimum of Months 14775042.93 19864417.87 35516489.11 14506968.64 20348492.48 0.00 0.00
Maximum of Months 0.214088E+09 0.199801E+09 0.162958E+09 75297869.26 88059385.55 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM420_423

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 87592895.82 0.784787E+09 0.211711E+09 87480740.89 0.124230E+09 0.00 0.00
February 0.139812E+09 0.561349E+09 0.251744E+09 0.110145E+09 0.141599E+09 0.00 0.00
March 0.289401E+09 0.403051E+09 0.379858E+09 0.150387E+09 0.229472E+09 0.00 0.00
April 0.439665E+09 0.268727E+09 0.451106E+09 0.197523E+09 0.253583E+09 0.00 0.00
May 0.676293E+09 0.147766E+09 0.586093E+09 0.255996E+09 0.330097E+09 0.00 0.00
June 0.805712E+09 87585485.01 0.624247E+09 0.272010E+09 0.352238E+09 0.00 0.00
July 0.862883E+09 74108304.10 0.651831E+09 0.301191E+09 0.350640E+09 0.00 0.00
August 0.724968E+09 92282588.25 0.548700E+09 0.236097E+09 0.312603E+09 0.00 0.00
September 0.580475E+09 0.167870E+09 0.475767E+09 0.225385E+09 0.250382E+09 0.00 0.00
October 0.278325E+09 0.294075E+09 0.311763E+09 0.129843E+09 0.181919E+09 0.00 0.00
November 91647582.57 0.465474E+09 0.178516E+09 58027874.57 0.120488E+09 0.00 0.00
December 60175297.96 0.708389E+09 0.142066E+09 60671986.50 81393969.94 0.00 0.00
               
Annual Sum or Average 0.503695E+10 0.405546E+10 0.481340E+10 0.208476E+10 0.272864E+10 0.00 0.00
Minimum of Months 60175297.96 74108304.10 0.142066E+09 58027874.57 81393969.94 0.00 0.00
Maximum of Months 0.862883E+09 0.784787E+09 0.651831E+09 0.301191E+09 0.352238E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GUESTROOM424

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 22367205.95 0.192823E+09 52927752.82 21870185.22 31057567.60 0.00 0.00
February 35766422.78 0.137441E+09 62935916.04 27536246.10 35399669.94 0.00 0.00
March 74097091.87 98793366.67 94964621.74 37596731.77 57367889.97 0.00 0.00
April 0.110909E+09 66186122.27 0.112776E+09 49380691.59 63395708.86 0.00 0.00
May 0.169152E+09 37123285.25 0.146523E+09 63998912.16 82524222.06 0.00 0.00
June 0.200969E+09 22373957.68 0.156062E+09 68002436.64 88059385.55 0.00 0.00
July 0.215124E+09 19173881.18 0.162958E+09 75297869.26 87659972.69 0.00 0.00
August 0.180774E+09 23712694.80 0.137175E+09 59024149.09 78150762.09 0.00 0.00
September 0.145254E+09 42236147.08 0.118942E+09 56346263.19 62595410.10 0.00 0.00
October 70820342.28 72732473.33 77940706.36 32460842.65 45479863.71 0.00 0.00
November 23592169.91 0.113963E+09 44628954.05 14506968.64 30121985.40 0.00 0.00
December 15352948.17 0.173461E+09 35516489.11 15167996.63 20348492.48 0.00 0.00
               
Annual Sum or Average 0.126418E+10 0.100002E+10 0.120335E+10 0.521189E+09 0.682161E+09 0.00 0.00
Minimum of Months 15352948.17 19173881.18 35516489.11 14506968.64 20348492.48 0.00 0.00
Maximum of Months 0.215124E+09 0.192823E+09 0.162958E+09 75297869.26 88059385.55 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONTSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FRONTSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -12.6 -13.1 -15.2 6.10 -26.1 37.55 107.22 0.02
February -7.7 -8.6 -10.9 6.39 -21.3 45.57 135.04 0.00
March 0.33 -1.4 -4.2 6.99 -10.6 74.69 127.11 0.00
April 7.02 4.40 1.63 6.38 -3.6 77.59 184.47 0.02
May 14.19 11.30 8.94 5.14 4.70 102.33 182.89 0.00
June 19.16 15.71 13.79 4.87 8.84 110.26 213.51 0.04
July 20.92 17.87 16.31 4.22 9.95 102.99 231.93 0.03
August 20.05 17.00 15.28 4.97 11.01 95.97 190.14 0.00
September 15.39 11.24 8.10 4.97 3.18 72.67 177.74 0.01
October 7.43 4.69 1.56 5.55 -3.9 55.50 131.91 0.00
November -0.0 -1.5 -3.9 6.30 -10.9 41.35 79.05 0.00
December -7.6 -8.4 -10.6 6.09 -20.0 22.97 92.59 0.00
                 
Annual Sum or Average 6.46 4.16 1.81 5.66 -4.8 70.09 154.52 0.01
Minimum of Months -12.6 -13.1 -15.2 4.22 -26.1 22.97 79.05 0.00
Maximum of Months 20.92 17.87 16.31 6.99 11.01 110.26 231.93 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 6.10 17-JAN-23:19 3.74 0.93 10.63 -0.4 0.00 0.00
February 8.30 24-FEB-14:00 5.62 2.80 5.20 -7.3 71.00 794.50
March 18.90 19-MAR-15:00 13.93 10.60 8.80 7.95 139.50 237.50
April 30.00 15-APR-15:20 19.12 13.53 12.70 15.70 115.83 790.83
May 30.00 31-MAY-12:00 19.70 14.40 6.20 19.52 251.00 580.50
June 33.30 11-JUN-14:00 24.81 21.70 10.30 24.50 281.00 458.50
July 30.00 26-JUL-15:20 25.67 24.23 5.13 20.98 260.33 436.00
August 33.90 04-AUG-14:00 25.31 22.20 4.60 23.82 194.50 612.00
September 32.20 06-SEP-13:00 21.19 16.10 6.20 18.28 135.00 769.00
October 23.30 20-OCT-14:00 13.36 5.60 7.20 7.35 55.00 745.50
November 16.10 03-NOV-13:00 10.47 5.60 6.70 0.51 82.00 691.00
December 7.20 02-DEC-13:00 3.94 0.00 7.70 -3.9 75.00 301.00
                 
Annual Sum or Average                
Minimum of Months 6.10   3.74 0.00 4.60 -7.3 0.00 0.00
Maximum of Months 33.90   25.67 24.23 12.70 24.50 281.00 794.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -31.1 31-JAN-03:00 -31.3 -34.4 4.60 -46.7 0.00 0.00
February -36.7 02-FEB-05:00 -36.8 -40.2 3.10 -59.6 0.00 0.00
March -17.2 06-MAR-00:00 -17.6 -20.0 5.20 -36.8 0.00 0.00
April -7.2 03-APR-05:19 -8.0 -9.8 7.37 -15.9 0.00 0.00
May 0.60 03-MAY-02:00 -0.1 -1.1 1.50 -15.5 0.00 0.00
June 5.00 01-JUN-04:00 5.00 5.00 3.10 -7.8 30.50 132.50
July 10.00 23-JUL-03:00 9.66 9.40 2.60 -4.3 0.00 0.00
August 8.30 07-AUG-03:00 7.41 6.70 3.10 -3.2 0.00 0.00
September -1.1 30-SEP-00:00 -2.4 -4.4 4.10 -17.8 0.00 0.00
October -3.3 23-OCT-05:00 -4.2 -6.1 3.60 -19.1 0.00 0.00
November -28.9 26-NOV-06:00 -29.0 -30.6 1.50 -50.2 0.00 0.00
December -22.8 09-DEC-00:20 -23.0 -25.0 13.40 -37.7 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -36.7   -36.8 -40.2 1.50 -59.6 0.00 0.00
Maximum of Months 10.00   9.66 9.40 13.40 -3.2 30.50 132.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 5.60 18-JAN-00:00 5.60 5.60 7.70 0.30 0.00 0.00
February 5.88 24-FEB-15:00 8.30 3.30 5.70 -7.3 54.50 665.50
March 13.93 19-MAR-15:00 18.90 10.60 8.80 7.95 139.50 237.50
April 20.94 18-APR-11:00 27.80 17.80 13.90 17.57 334.00 447.00
May 19.93 29-MAY-13:00 23.30 18.30 6.20 20.75 379.00 52.00
June 24.81 11-JUN-14:00 33.30 21.70 10.30 24.50 281.00 458.50
July 26.15 26-JUL-18:00 27.80 25.60 3.10 19.35 33.50 51.00
August 26.64 04-AUG-12:00 31.70 25.00 4.60 25.66 235.00 593.50
September 21.19 06-SEP-13:00 32.20 16.10 6.20 18.28 135.00 769.00
October 14.84 02-OCT-14:00 18.30 12.80 3.60 12.41 202.00 164.00
November 13.04 09-NOV-04:00 15.00 11.70 10.30 10.88 0.00 0.00
December 3.94 02-DEC-13:00 7.20 0.00 7.70 -3.9 75.00 301.00
                 
Annual Sum or Average                
Minimum of Months 3.94   5.60 0.00 3.10 -7.3 0.00 0.00
Maximum of Months 26.64   33.30 25.60 13.90 25.66 379.00 769.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 5.60 18-JAN-00:00 5.60 5.60 7.70 0.30 0.00 0.00
February 3.30 24-FEB-15:00 8.30 5.88 5.70 -7.3 54.50 665.50
March 11.10 26-MAR-05:00 13.30 12.04 8.20 9.13 0.00 0.00
April 18.30 18-APR-09:00 25.60 20.52 14.40 15.57 196.00 741.50
May 18.30 29-MAY-13:00 23.30 19.93 6.20 20.75 379.00 52.00
June 22.20 13-JUN-11:00 26.70 23.35 8.80 16.85 273.50 600.50
July 25.60 26-JUL-18:00 27.80 26.15 3.10 19.35 33.50 51.00
August 25.00 04-AUG-12:00 31.70 26.64 4.60 25.66 235.00 593.50
September 18.30 12-SEP-02:00 18.90 18.46 5.70 14.28 0.00 0.00
October 12.80 02-OCT-13:00 17.40 14.50 3.40 11.65 249.50 141.50
November 11.70 08-NOV-10:00 13.90 12.62 7.20 9.91 158.00 0.50
December 0.00 02-DEC-11:00 5.00 2.79 7.20 -8.3 115.50 562.00
                 
Annual Sum or Average                
Minimum of Months 0.00   5.00 2.79 3.10 -8.3 0.00 0.00
Maximum of Months 25.60   31.70 26.64 14.40 25.66 379.00 741.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 4.29 14.52 0.00
February 18.00 13.00 16.00 3.18 19.75 0.00
March 18.00 13.00 16.00 3.75 28.43 0.00
April 18.00 13.00 16.00 5.88 38.20 0.00
May 18.00 13.00 16.00 9.06 44.89 0.00
June 18.00 13.00 16.00 12.40 51.07 0.00
July 18.00 13.00 16.00 15.02 51.61 0.00
August 18.00 13.00 16.00 16.22 43.31 0.00
September 18.00 13.00 16.00 15.63 34.41 0.00
October 18.00 13.00 16.00 13.44 22.83 0.00
November 18.00 13.00 16.00 10.25 13.98 0.00
December 18.00 13.00 16.00 6.92 10.24 0.00
             
Annual Sum or Average 18.00 13.00 16.00 9.71 31.16 0.00
Minimum of Months 18.00 13.00 16.00 3.18 10.24 0.00
Maximum of Months 18.00 13.00 16.00 16.22 51.61 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH SHOWER WATER HEATER

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.247235E+11 -0.236451E+11 0.00 0.00 744.00 0.00 -0.107835E+10 58.98 0.00 0.00
February 0.227727E+11 -0.218087E+11 0.00 0.00 672.00 0.00 -964077063.9 58.98 0.00 0.00
March 0.249844E+11 -0.239404E+11 0.00 0.00 744.00 0.00 -0.104405E+10 58.98 0.00 0.00
April 0.232058E+11 -0.222282E+11 0.00 0.00 720.00 0.00 -977638942.8 58.98 0.00 0.00
May 0.225937E+11 -0.216195E+11 0.00 0.00 744.00 0.00 -974164437.9 58.98 0.00 0.00
June 0.204472E+11 -0.195282E+11 0.00 0.00 720.00 0.00 -919031125.8 58.98 0.00 0.00
July 0.199348E+11 -0.190011E+11 0.00 0.00 744.00 0.00 -933673784.7 58.98 0.00 0.00
August 0.194634E+11 -0.185299E+11 0.00 0.00 744.00 0.00 -933465858.2 58.98 0.00 0.00
September 0.190619E+11 -0.181437E+11 0.00 0.00 720.00 0.00 -918173114.4 58.98 0.00 0.00
October 0.206867E+11 -0.197012E+11 0.00 0.00 744.00 0.00 -985550503.2 58.98 0.00 0.00
November 0.213836E+11 -0.203966E+11 0.00 0.00 720.00 0.00 -987001335.6 58.98 0.00 0.00
December 0.235697E+11 -0.225086E+11 0.00 0.00 744.00 0.00 -0.106115E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.262827E+12 -0.251051E+12 0.00 0.00 8760.00 0.00 -0.117763E+11 58.98 0.00 0.00
Minimum of Months 0.190619E+11 -0.239404E+11 0.00 0.00 672.00 0.00 -0.107835E+10 58.98 0.00 0.00
Maximum of Months 0.249844E+11 -0.181437E+11 0.00 0.00 744.00 0.00 -918173114.4 58.98 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY WATER HEATER

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.378171E+11 -0.373104E+11 0.00 0.00 744.00 0.00 -506656588.9 81.30 0.00 0.00
February 0.346350E+11 -0.341858E+11 0.00 0.00 672.00 0.00 -449266934.5 81.32 0.00 0.00
March 0.380592E+11 -0.375770E+11 0.00 0.00 744.00 0.00 -482171218.6 81.29 0.00 0.00
April 0.358101E+11 -0.353604E+11 0.00 0.00 720.00 0.00 -449687337.2 81.30 0.00 0.00
May 0.354387E+11 -0.349998E+11 0.00 0.00 744.00 0.00 -438866883.1 81.30 0.00 0.00
June 0.327073E+11 -0.322992E+11 0.00 0.00 720.00 0.00 -408022499.9 81.30 0.00 0.00
July 0.325169E+11 -0.321059E+11 0.00 0.00 744.00 0.00 -411003814.1 81.27 0.00 0.00
August 0.319387E+11 -0.315255E+11 0.00 0.00 744.00 0.00 -413232454.0 81.34 0.00 0.00
September 0.311928E+11 -0.307843E+11 0.00 0.00 720.00 0.00 -408556989.6 81.29 0.00 0.00
October 0.333185E+11 -0.328718E+11 0.00 0.00 744.00 0.00 -446742098.2 81.29 0.00 0.00
November 0.337639E+11 -0.333083E+11 0.00 0.00 720.00 0.00 -455585446.6 81.30 0.00 0.00
December 0.365326E+11 -0.360375E+11 0.00 0.00 744.00 0.00 -495085824.2 81.31 0.00 0.00
                     
Annual Sum or Average 0.413731E+12 -0.408366E+12 0.00 0.00 8760.00 0.00 -0.536488E+10 81.30 0.00 0.00
Minimum of Months 0.311928E+11 -0.375770E+11 0.00 0.00 672.00 0.00 -506656588.9 81.27 0.00 0.00
Maximum of Months 0.380592E+11 -0.307843E+11 0.00 0.00 744.00 0.00 -408022499.9 81.34 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: FRONTLOUNGEFLR1_DAYLCTRL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 214.17 0.47 0.42 01-JAN-10:09 705.14 21.89 75.83 237.33 360.74 24.39 174.83 151.00
February 226.83 0.47 0.42 01-FEB-10:09 631.57 21.79 100.83 248.00 274.58 22.89 195.50 174.83
March 334.33 0.45 0.42 01-MAR-08:50 1128.30 24.18 191.00 331.33 420.66 25.26 280.17 257.00
April 285.17 0.45 0.42 02-APR-14:39 2893.41 26.10 171.50 357.00 888.84 26.28 289.83 271.50
May 428.67 0.45 0.42 01-MAY-07:19 1688.79 23.10 225.00 410.17 699.52 23.97 358.83 340.67
June 400.67 0.45 0.42 01-JUN-06:19 2252.51 23.61 240.50 413.33 687.68 24.49 361.67 346.67
July 414.00 0.44 0.42 01-JUL-06:19 2587.27 23.93 238.50 418.67 835.97 24.65 373.83 356.67
August 410.83 0.45 0.42 01-AUG-06:00 2071.73 24.43 238.33 393.17 855.20 25.38 348.17 326.67
September 326.50 0.45 0.42 01-SEP-07:40 2034.67 25.90 185.67 338.67 608.70 26.25 301.67 275.67
October 325.17 0.46 0.42 01-OCT-08:09 828.21 23.46 161.00 301.33 357.53 25.01 254.50 230.17
November 254.83 0.47 0.42 01-NOV-08:00 555.26 21.63 102.17 243.17 395.82 24.45 187.67 162.33
December 186.17 0.50 0.42 01-DEC-12:20 591.78 20.86 31.17 209.67 407.18 24.28 109.50 90.50
                         
Annual Sum or Average 3807.33 0.46     1636.47 23.62 1961.50 3901.83 603.61 24.83 3236.17 2983.67
Minimum of Months 186.17 0.44 0.42   555.26 20.86 31.17 209.67 274.58 22.89 109.50 90.50
Maximum of Months 428.67 0.50 0.42   2893.41 26.10 240.50 418.67 888.84 26.28 373.83 356.67



Table of Contents

Report: DaylightingReportMonthly

For: MEETINGROOMFLR1_DAYLCTRL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 214.17 0.62 0.44 02-JAN-14:30 716.98 17.79 44.33 116.00 265.25 20.31 64.33 40.33
February 226.83 0.61 0.44 01-FEB-13:00 909.54 17.51 41.83 151.00 324.18 20.47 72.00 60.17
March 334.33 0.58 0.44 03-MAR-11:20 515.90 16.15 0.00 223.00 286.49 21.04 140.33 106.67
April 285.17 0.56 0.44 02-APR-15:20 1158.84 18.23 29.17 231.33 698.92 23.31 129.83 112.00
May 428.67 0.57 0.44 01-MAY-12:50 1488.85 18.53 63.50 279.00 540.19 20.69 170.67 134.50
June 400.67 0.56 0.44 01-JUN-15:50 2404.72 19.72 78.67 293.00 727.36 21.25 175.00 148.83
July 414.00 0.55 0.44 01-JUL-11:00 2532.34 19.82 77.00 290.17 853.13 21.47 190.50 169.83
August 410.83 0.56 0.44 01-AUG-13:20 1541.65 19.61 74.00 278.17 720.15 22.33 187.00 163.17
September 326.50 0.57 0.44 01-SEP-11:20 894.35 17.65 29.33 221.00 453.23 22.14 139.83 112.83
October 325.17 0.60 0.44 01-OCT-13:20 499.06 15.65 7.33 188.33 549.22 21.60 115.00 84.17
November 254.83 0.62 0.44 01-NOV-13:20 632.44 17.46 47.83 139.83 353.50 21.32 80.67 30.67
December 186.17 0.69 0.44 01-DEC-14:09 614.59 16.39 35.33 55.83 223.70 18.27 16.17 10.67
                         
Annual Sum or Average 3807.33 0.58     1280.72 18.08 528.33 2466.67 539.95 21.33 1481.33 1173.83
Minimum of Months 186.17 0.55 0.44   499.06 15.65 0.00 55.83 223.70 18.27 16.17 10.67
Maximum of Months 428.67 0.69 0.44   2532.34 19.82 78.67 293.00 853.13 23.31 190.50 169.83



Table of Contents

Report: DaylightingReportMonthly

For: FRONTOFFICEFLR1_DAYLCTRL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 214.17 0.71 0.48 02-JAN-09:09 641.02 16.35 43.17 64.17 160.29 18.02 25.50 18.83
February 226.83 0.70 0.48 01-FEB-08:30 733.91 15.58 41.17 73.33 351.45 19.82 47.67 43.17
March 334.33 0.67 0.48 01-MAR-09:09 839.66 15.59 45.33 125.50 462.59 20.52 90.17 67.17
April 285.17 0.67 0.48 03-APR-08:39 445.58 13.33 10.50 99.67 228.87 18.97 74.00 68.33
May 428.67 0.67 0.48 01-MAY-06:00 268.58 12.86 0.00 147.67 220.38 19.06 110.33 110.00
June 400.67 0.65 0.48 01-JUN-05:40 290.59 13.17 0.00 149.67 247.71 19.48 121.17 116.17
July 414.00 0.66 0.48 01-JUL-06:10 283.45 13.09 0.00 157.33 244.02 19.50 119.33 116.67
August 410.83 0.66 0.48 01-AUG-06:19 324.90 13.09 4.83 156.00 224.89 19.19 109.83 105.50
September 326.50 0.67 0.48 01-SEP-07:49 1073.44 15.49 48.67 125.50 236.91 19.00 95.00 88.17
October 325.17 0.70 0.48 01-OCT-07:30 689.87 15.19 54.17 96.17 318.73 20.50 82.83 58.67
November 254.83 0.73 0.48 01-NOV-08:09 308.86 13.84 22.67 50.67 174.89 19.01 31.00 13.33
December 186.17 0.77 0.48 01-DEC-08:00 156.52 10.52 0.00 14.83 302.72 18.55 25.67 20.67
                         
Annual Sum or Average 3807.33 0.68     492.89 13.95 270.50 1260.50 263.45 19.36 932.50 826.67
Minimum of Months 186.17 0.65 0.48   156.52 10.52 0.00 14.83 160.29 18.02 25.50 13.33
Maximum of Months 428.67 0.77 0.48   1073.44 16.35 54.17 157.33 462.59 20.52 121.17 116.67



Table of Contents

Report: DaylightingReportMonthly

For: LAUNDRYROOMFLR1_DAYLCTRL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 214.17 0.68 0.48 01-JAN-10:30 679.93 17.42 44.00 109.33 333.38 19.37 31.33 19.33
February 226.83 0.67 0.48 01-FEB-08:39 507.76 15.07 16.33 122.00 406.08 19.51 44.17 37.83
March 334.33 0.63 0.48 01-MAR-09:09 527.63 16.45 16.17 207.83 230.03 20.31 110.33 73.67
April 285.17 0.63 0.48 03-APR-08:09 1006.90 17.76 37.67 210.00 480.34 21.93 105.33 82.67
May 428.67 0.62 0.48 01-MAY-06:40 2090.60 20.66 114.83 261.17 849.19 22.52 159.17 135.00
June 400.67 0.61 0.48 01-JUN-05:30 2353.71 20.54 98.67 278.00 592.65 21.95 151.00 132.00
July 414.00 0.61 0.48 01-JUL-05:00 2374.62 20.71 101.83 270.50 857.07 22.63 150.83 129.00
August 410.83 0.62 0.48 01-AUG-05:00 1300.16 18.76 69.33 250.33 851.42 23.00 166.67 132.00
September 326.50 0.63 0.48 01-SEP-06:19 809.81 17.06 28.17 202.33 359.44 21.14 122.00 101.50
October 325.17 0.66 0.48 01-OCT-06:00 356.18 14.55 0.00 168.17 174.98 18.66 58.50 40.83
November 254.83 0.69 0.48 01-NOV-08:00 297.34 14.12 0.00 111.83 192.64 19.09 34.17 10.33
December 186.17 0.74 0.48 01-DEC-08:30 199.67 12.06 0.00 28.33 266.85 19.85 35.17 22.67
                         
Annual Sum or Average 3807.33 0.64     1201.36 17.66 527.00 2219.83 513.88 21.12 1168.67 916.83
Minimum of Months 186.17 0.61 0.48   199.67 12.06 0.00 28.33 174.98 18.66 31.33 10.33
Maximum of Months 428.67 0.74 0.48   2374.62 20.71 114.83 278.00 857.07 23.00 166.67 135.00



Table of Contents

Report: CoilReportMonthly

For: 101 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 102 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 330864.08 113.99 02-FEB-16:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 330864.08     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 330864.08 113.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 103 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.150806E+10 1868.29 01-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.106132E+10 1868.29 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.625292E+09 1868.29 01-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.199446E+09 1868.29 01-APR-15:01 0.00 0.00 0.00 0.00 0.00
May 6215782.61 1278.42 02-MAY-08:02 0.00 0.00 0.00 0.00 0.00
June 696443.90 988.34 03-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 22174.61 128.65 11-JUL-08:56 0.00 0.00 0.00 0.00 0.00
August 116620.49 923.46 07-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 2787638.03 1330.00 30-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 10212007.92 1524.33 28-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.416189E+09 1868.29 22-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.104577E+10 1868.29 01-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.487613E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 22174.61 128.65   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.150806E+10 1868.29   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 104 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.990153E+09 1891.34 05-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.654872E+09 1891.34 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.316301E+09 1891.34 01-MAR-16:01 0.00 0.00 0.00 0.00 0.00
April 88381890.54 1431.75 26-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 2362492.05 1316.43 02-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 932040.71 908.67 15-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 42750.61 193.52 19-JUL-08:06 0.00 0.00 0.00 0.00 0.00
August 197849.15 606.37 25-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 1809742.19 1157.02 30-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 5056632.93 1269.41 31-OCT-18:04 0.00 0.00 0.00 0.00 0.00
November 0.227654E+09 1891.34 26-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.618801E+09 1891.34 08-DEC-16:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.290656E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 42750.61 193.52   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.990153E+09 1891.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 105 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.114093E+09 1342.11 01-JAN-09:03 0.00 0.00 0.00 0.00 0.00
February 0.103380E+09 1342.11 05-FEB-09:03 0.00 0.00 0.00 0.00 0.00
March 6535899.10 1342.11 01-MAR-09:03 0.00 0.00 0.00 0.00 0.00
April 3975124.73 1342.11 01-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 1158801.40 1342.11 02-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 594789.92 856.87 02-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 182556.83 659.31 18-JUL-18:35 0.00 0.00 0.00 0.00 0.00
August 592939.05 596.85 17-AUG-18:45 0.00 0.00 0.00 0.00 0.00
September 1762921.43 1266.61 29-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 3173871.81 1342.11 13-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 12938409.52 1342.11 09-NOV-16:03 0.00 0.00 0.00 0.00 0.00
December 37054661.52 1342.11 01-DEC-09:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.285443E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 182556.83 596.85   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.114093E+09 1342.11   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 201 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.105500E+09 762.25 26-JAN-15:13 0.00 0.00 0.00 0.00 0.00
February 0.105925E+09 667.45 02-FEB-15:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 7179555.92 400.92 26-NOV-15:07 0.00 0.00 0.00 0.00 0.00
December 44590617.20 566.19 09-DEC-15:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.263195E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.105925E+09 762.25   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 202_205 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.417736E+10 4908.57 01-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.260921E+10 4908.57 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.122917E+10 4908.57 01-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.270861E+09 4908.57 01-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 4448649.11 3482.94 02-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 2854173.92 3015.28 04-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 340172.26 1278.39 11-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 988112.71 1601.06 06-AUG-20:16 0.00 0.00 0.00 0.00 0.00
September 9347645.37 4908.57 29-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 43152072.09 4908.57 18-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.137507E+10 4908.57 22-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.310260E+10 4908.57 07-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.128254E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 340172.26 1278.39   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.417736E+10 4908.57   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 206_208 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.288795E+10 3860.93 02-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.173370E+10 3860.93 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.729518E+09 3860.93 01-MAR-16:01 0.00 0.00 0.00 0.00 0.00
April 0.141591E+09 3860.93 01-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 2972892.66 2801.49 02-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 2215712.66 2209.47 04-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 608636.25 1255.76 18-JUL-21:56 0.00 0.00 0.00 0.00 0.00
August 715607.19 1167.49 16-AUG-21:56 0.00 0.00 0.00 0.00 0.00
September 5261963.93 3860.93 29-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 21028305.96 3860.93 17-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.873194E+09 3860.93 10-NOV-16:03 0.00 0.00 0.00 0.00 0.00
December 0.206520E+10 3860.93 01-DEC-19:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.846395E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 608636.25 1167.49   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.288795E+10 3860.93   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 209_212 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.317723E+10 4812.02 01-JAN-09:03 0.00 0.00 0.00 0.00 0.00
February 0.196070E+10 4812.02 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.846539E+09 4812.02 03-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 0.187838E+09 4812.02 03-APR-08:02 0.00 0.00 0.00 0.00 0.00
May 6379878.06 3822.64 01-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 3266340.82 3329.90 05-JUN-15:04 0.00 0.00 0.00 0.00 0.00
July 92407.03 461.52 18-JUL-21:57 0.00 0.00 0.00 0.00 0.00
August 1016422.52 2038.06 07-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 8351755.21 3979.01 29-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 30641348.09 4812.02 27-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.946479E+09 4812.02 10-NOV-09:03 0.00 0.00 0.00 0.00 0.00
December 0.221530E+10 4812.02 02-DEC-09:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.938384E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 92407.03 461.52   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.317723E+10 4812.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 213 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.161122E+10 1741.29 01-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.106277E+10 1741.29 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.574926E+09 1741.29 01-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.164503E+09 1741.29 01-APR-15:01 0.00 0.00 0.00 0.00 0.00
May 4019647.49 1192.93 18-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 728554.99 810.60 01-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 59879.53 404.67 11-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 125308.92 346.40 25-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 8073604.94 1006.70 25-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 49848521.67 1292.02 23-OCT-15:03 0.00 0.00 0.00 0.00 0.00
November 0.580899E+09 1741.29 17-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.123542E+10 1741.29 01-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.529260E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 59879.53 346.40   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.161122E+10 1741.29   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 214 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.763114E+09 1734.89 06-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.437729E+09 1734.89 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.138793E+09 1529.04 21-MAR-15:03 0.00 0.00 0.00 0.00 0.00
April 21447827.57 1638.04 01-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 510354.94 798.48 02-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 204029.81 558.83 05-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 6157.60 102.63 18-JUL-21:56 0.00 0.00 0.00 0.00 0.00
August 25032.43 106.15 29-AUG-19:56 0.00 0.00 0.00 0.00 0.00
September 709345.46 816.73 24-SEP-16:14 0.00 0.00 0.00 0.00 0.00
October 2566805.72 1497.14 26-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.185364E+09 1734.89 26-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.473306E+09 1734.89 09-DEC-16:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.202378E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 6157.60 102.63   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.763114E+09 1734.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 215_218 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 219 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 220_223 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.276979E+10 4811.67 01-JAN-09:03 0.00 0.00 0.00 0.00 0.00
February 0.169728E+10 4811.67 01-FEB-16:01 0.00 0.00 0.00 0.00 0.00
March 0.668641E+09 4811.67 01-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 0.159595E+09 4811.67 04-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 5909592.42 3702.77 01-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 3414420.52 2885.09 06-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 425221.12 1566.49 11-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 1081442.46 2473.69 25-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 5814805.27 3598.90 29-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 22170539.71 4017.32 18-OCT-18:04 0.00 0.00 0.00 0.00 0.00
November 0.822870E+09 4811.67 10-NOV-09:03 0.00 0.00 0.00 0.00 0.00
December 0.191571E+10 4811.67 02-DEC-16:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.807270E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 425221.12 1566.49   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.276979E+10 4811.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 224 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.116768E+10 1545.17 02-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.751115E+09 1545.17 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.329116E+09 1545.17 01-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 77534984.38 1478.50 25-APR-15:03 0.00 0.00 0.00 0.00 0.00
May 821564.92 758.71 02-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 370644.26 738.50 05-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 17981.99 82.24 22-JUL-08:36 0.00 0.00 0.00 0.00 0.00
August 88099.78 314.06 06-AUG-18:05 0.00 0.00 0.00 0.00 0.00
September 886956.01 692.53 29-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 9739115.31 1492.55 28-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.362884E+09 1545.17 22-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.853204E+09 1545.17 06-DEC-16:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.355346E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 17981.99 82.24   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.116768E+10 1545.17   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 301 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.547361E+09 789.34 19-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 0.301344E+09 930.73 02-FEB-15:02 0.00 0.00 0.00 0.00 0.00
March 16886813.16 325.88 05-MAR-15:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 98579973.67 585.11 26-NOV-16:00 0.00 0.00 0.00 0.00 0.00
December 0.259018E+09 825.14 09-DEC-15:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.122319E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.547361E+09 930.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 302_305 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.123845E+09 2888.18 19-JAN-15:05 0.00 0.00 0.00 0.00 0.00
February 0.155803E+09 3093.25 03-FEB-15:05 0.00 0.00 0.00 0.00 0.00
March 383136.54 291.91 01-MAR-15:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 13641016.47 1892.60 26-NOV-15:07 0.00 0.00 0.00 0.00 0.00
December 61312838.89 2153.12 11-DEC-15:07 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.354985E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.155803E+09 3093.25   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 306_308 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 40201961.01 1961.70 19-JAN-15:08 0.00 0.00 0.00 0.00 0.00
February 48163222.97 2320.53 01-FEB-15:08 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 5320989.90 1305.46 26-NOV-15:10 0.00 0.00 0.00 0.00 0.00
December 20132175.46 1867.72 11-DEC-15:07 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.113818E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 48163222.97 2320.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 309_312 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.398743E+10 5009.43 03-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.250747E+10 5009.43 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.119587E+10 5009.43 01-MAR-16:01 0.00 0.00 0.00 0.00 0.00
April 0.323497E+09 5009.43 01-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 8397737.12 5009.43 02-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 3128895.73 3441.36 05-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 168067.23 1014.06 23-JUL-21:47 0.00 0.00 0.00 0.00 0.00
August 498962.77 2799.66 07-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 27656885.93 3935.06 30-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 0.158478E+09 5009.43 13-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.143277E+10 5009.43 22-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.300054E+10 5009.43 08-DEC-16:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.126459E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 168067.23 1014.06   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.398743E+10 5009.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 313 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.122066E+09 610.53 19-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 96711746.01 691.32 02-FEB-15:02 0.00 0.00 0.00 0.00 0.00
March 228760.21 95.73 01-MAR-15:30 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 10237956.14 423.66 26-NOV-16:00 0.00 0.00 0.00 0.00 0.00
December 69601494.87 660.84 09-DEC-15:07 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.298846E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122066E+09 691.32   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 314 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.146486E+10 1804.07 01-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.921352E+09 1804.07 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.433280E+09 1804.07 01-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.121003E+09 1804.07 02-APR-15:01 0.00 0.00 0.00 0.00 0.00
May 1555020.25 1344.25 02-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 651265.31 778.46 04-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 51332.20 343.64 10-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 107328.50 435.71 25-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 5316021.52 1277.18 30-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 36835154.98 1353.89 14-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.534623E+09 1804.07 21-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.112701E+10 1804.07 01-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.464664E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 51332.20 343.64   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.146486E+10 1804.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 315_318 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.153371E+10 4970.13 02-JAN-09:03 0.00 0.00 0.00 0.00 0.00
February 0.850008E+09 4970.13 04-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.123807E+09 4970.13 03-MAR-09:03 0.00 0.00 0.00 0.00 0.00
April 13147064.47 4970.13 03-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 1075712.06 1980.80 01-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 898459.48 2405.75 05-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 72902.65 565.69 23-JUL-18:36 0.00 0.00 0.00 0.00 0.00
August 133036.81 900.47 07-AUG-21:16 0.00 0.00 0.00 0.00 0.00
September 1913107.20 2236.89 21-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 6925489.28 2872.36 26-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.326494E+09 4970.13 21-NOV-09:03 0.00 0.00 0.00 0.00 0.00
December 0.782087E+09 4970.13 04-DEC-09:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.364027E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 72902.65 565.69   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153371E+10 4970.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 319 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 320_323 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.345006E+10 4897.96 03-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.216558E+10 4897.96 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.959442E+09 4897.96 01-MAR-16:01 0.00 0.00 0.00 0.00 0.00
April 0.285752E+09 4897.96 02-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 7093591.22 3190.47 17-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 1912634.92 3018.10 02-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 88928.90 568.83 23-JUL-21:57 0.00 0.00 0.00 0.00 0.00
August 405562.60 1237.20 06-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 18830234.08 4156.84 30-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 0.120405E+09 4897.96 17-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.120648E+10 4897.96 13-NOV-09:03 0.00 0.00 0.00 0.00 0.00
December 0.255127E+10 4897.96 02-DEC-09:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.107673E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 88928.90 568.83   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.345006E+10 4897.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 324 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 7526349.91 497.65 31-JAN-15:10 0.00 0.00 0.00 0.00 0.00
February 6388799.30 723.92 01-FEB-15:08 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 364520.78 162.23 26-NOV-15:30 0.00 0.00 0.00 0.00 0.00
December 3499982.09 464.85 09-DEC-15:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 17779652.09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 7526349.91 723.92   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 401 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.328703E+10 2408.72 01-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.230370E+10 2408.72 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.141653E+10 2408.72 01-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.577957E+09 2408.72 01-APR-08:61 0.00 0.00 0.00 0.00 0.00
May 58344576.62 2408.72 02-MAY-08:61 0.00 0.00 0.00 0.00 0.00
June 11670899.90 653.20 04-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 130834.88 276.14 22-JUL-08:55 0.00 0.00 0.00 0.00 0.00
August 174319.82 894.25 07-AUG-08:03 0.00 0.00 0.00 0.00 0.00
September 0.106111E+09 2408.72 27-SEP-08:61 0.00 0.00 0.00 0.00 0.00
October 0.519064E+09 2408.72 06-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.155940E+10 2408.72 01-NOV-08:61 0.00 0.00 0.00 0.00 0.00
December 0.274027E+10 2408.72 01-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.125804E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 130834.88 276.14   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.328703E+10 2408.72   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 402_405 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.234867E+10 3278.71 03-JAN-15:47 0.00 0.00 0.00 0.00 0.00
February 0.128242E+10 3944.99 02-FEB-07:23 0.00 0.00 0.00 0.00 0.00
March 0.166026E+09 1067.99 06-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 5285564.12 274.18 03-APR-05:45 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.502330E+09 2391.08 26-NOV-07:00 0.00 0.00 0.00 0.00 0.00
December 0.137821E+10 3012.99 09-DEC-15:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.568293E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.234867E+10 3944.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 406_408 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.161144E+10 2283.88 19-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 0.883475E+09 2993.96 02-FEB-07:23 0.00 0.00 0.00 0.00 0.00
March 71195610.55 815.88 01-MAR-15:17 0.00 0.00 0.00 0.00 0.00
April 844887.19 99.77 03-APR-05:45 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.321667E+09 1786.08 26-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.872275E+09 2306.01 09-DEC-15:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.376090E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.161144E+10 2993.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 409_412 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.565056E+10 6281.93 01-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.372469E+10 6281.93 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.200108E+10 6281.93 01-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.720206E+09 6281.93 01-APR-15:01 0.00 0.00 0.00 0.00 0.00
May 50906885.45 4882.18 18-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 7960573.64 4835.85 02-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 679888.21 2311.52 10-JUL-21:16 0.00 0.00 0.00 0.00 0.00
August 1860190.84 1969.11 10-AUG-21:16 0.00 0.00 0.00 0.00 0.00
September 0.104909E+09 4468.15 29-SEP-15:03 0.00 0.00 0.00 0.00 0.00
October 0.552309E+09 5255.78 28-OCT-08:02 0.00 0.00 0.00 0.00 0.00
November 0.233947E+10 6281.93 14-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.444919E+10 6281.93 01-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.196038E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 679888.21 1969.11   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.565056E+10 6281.93   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 413 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.867945E+09 981.22 31-JAN-06:13 0.00 0.00 0.00 0.00 0.00
February 0.465031E+09 1239.99 02-FEB-07:23 0.00 0.00 0.00 0.00 0.00
March 82809720.55 420.19 06-MAR-06:00 0.00 0.00 0.00 0.00 0.00
April 3806706.80 138.09 03-APR-05:45 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.196414E+09 804.36 26-NOV-07:00 0.00 0.00 0.00 0.00 0.00
December 0.518174E+09 1034.01 09-DEC-15:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.213418E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.867945E+09 1239.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 414 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.390187E+09 724.92 19-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 0.216125E+09 859.87 02-FEB-16:00 0.00 0.00 0.00 0.00 0.00
March 7987294.28 210.75 06-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 61730396.70 618.36 27-NOV-15:50 0.00 0.00 0.00 0.00 0.00
December 0.171114E+09 817.33 09-DEC-16:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.847144E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.390187E+09 859.87   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 415_418 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.447695E+10 6227.35 01-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.283856E+10 6227.35 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.134919E+10 6227.35 01-MAR-16:01 0.00 0.00 0.00 0.00 0.00
April 0.471949E+09 5922.45 06-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 26599832.82 3349.03 06-MAY-16:55 0.00 0.00 0.00 0.00 0.00
June 4887154.13 3055.99 05-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 1861553.09 2084.98 09-JUL-16:56 0.00 0.00 0.00 0.00 0.00
August 2656208.04 1843.56 20-AUG-20:16 0.00 0.00 0.00 0.00 0.00
September 58558476.69 5238.23 29-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 0.322578E+09 5528.58 28-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.168954E+10 6227.35 11-NOV-09:03 0.00 0.00 0.00 0.00 0.00
December 0.335821E+10 6227.35 04-DEC-16:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.146015E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1861553.09 1843.56   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.447695E+10 6227.35   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 419 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.123094E+10 1708.85 01-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.759654E+09 1708.85 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.351074E+09 1708.85 01-MAR-16:01 0.00 0.00 0.00 0.00 0.00
April 0.111502E+09 1432.05 25-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 3173824.12 873.02 02-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 309017.71 712.06 02-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 155626.86 277.52 11-JUL-18:06 0.00 0.00 0.00 0.00 0.00
August 247769.93 531.90 06-AUG-16:55 0.00 0.00 0.00 0.00 0.00
September 10151317.64 1226.32 26-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 67849011.85 1457.90 14-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.451291E+09 1708.85 21-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.925266E+09 1708.85 04-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.391161E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 155626.86 277.52   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.123094E+10 1708.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 420_423 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.443041E+10 5819.44 01-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.287834E+10 5819.44 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.144585E+10 5819.44 01-MAR-16:01 0.00 0.00 0.00 0.00 0.00
April 0.530077E+09 5819.44 06-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 38601299.60 3463.88 01-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 6389144.56 3424.02 01-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 1471955.96 2439.95 22-JUL-18:56 0.00 0.00 0.00 0.00 0.00
August 1274531.57 2570.76 25-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 72801318.33 4501.42 29-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 0.371719E+09 5819.44 28-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.174996E+10 5819.44 12-NOV-09:03 0.00 0.00 0.00 0.00 0.00
December 0.339357E+10 5819.44 03-DEC-09:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.149205E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1274531.57 2439.95   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.443041E+10 5819.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 424 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.201562E+10 1991.94 01-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.134872E+10 1991.94 01-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.717563E+09 1991.94 01-MAR-09:01 0.00 0.00 0.00 0.00 0.00
April 0.263651E+09 1991.94 01-APR-15:01 0.00 0.00 0.00 0.00 0.00
May 14956365.94 1063.94 01-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 1531413.60 880.56 02-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 120111.48 311.21 21-JUL-18:36 0.00 0.00 0.00 0.00 0.00
August 133882.50 287.94 15-AUG-18:06 0.00 0.00 0.00 0.00 0.00
September 29584148.86 1216.43 29-SEP-15:03 0.00 0.00 0.00 0.00 0.00
October 0.181555E+09 1638.40 26-OCT-08:61 0.00 0.00 0.00 0.00 0.00
November 0.839580E+09 1991.94 10-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.160731E+10 1991.94 01-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.702033E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 120111.48 287.94   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.201562E+10 1991.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDORFLR1 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.114081E+11 65484.59 31-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.779375E+10 76487.20 02-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.390163E+10 37497.70 06-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 0.197234E+10 29556.83 01-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.352270E+09 19187.25 03-MAY-06:04 0.00 0.00 0.00 0.00 0.00
June 92973798.65 11194.75 03-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 8081291.63 6611.20 07-AUG-06:06 0.00 0.00 0.00 0.00 0.00
September 0.398097E+09 20204.10 29-SEP-06:04 0.00 0.00 0.00 0.00 0.00
October 0.143222E+10 28371.17 23-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.419181E+10 60708.83 26-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.765614E+10 52661.60 09-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.392074E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.114081E+11 76487.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDORFLR2 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.273766E+10 4060.99 06-JAN-05:17 0.00 0.00 0.00 0.00 0.00
February 0.145012E+10 3741.04 05-FEB-09:25 0.00 0.00 0.00 0.00 0.00
March 0.396063E+09 1228.66 06-MAR-06:00 0.00 0.00 0.00 0.00 0.00
April 26321241.48 516.38 03-APR-05:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.584350E+09 1952.41 26-NOV-06:55 0.00 0.00 0.00 0.00 0.00
December 0.165116E+10 3816.42 11-DEC-19:57 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.684568E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.273766E+10 4060.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDORFLR3 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.661497E+10 3951.35 31-JAN-04:00 0.00 0.00 0.00 0.00 0.00
February 0.452920E+10 4366.46 02-FEB-07:12 0.00 0.00 0.00 0.00 0.00
March 0.258155E+10 2548.03 06-MAR-06:00 0.00 0.00 0.00 0.00 0.00
April 0.819815E+09 2626.84 06-APR-06:15 0.00 0.00 0.00 0.00 0.00
May 4531132.55 256.88 02-MAY-05:27 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 39498874.77 687.30 30-SEP-06:35 0.00 0.00 0.00 0.00 0.00
October 0.376942E+09 876.11 27-OCT-05:55 0.00 0.00 0.00 0.00 0.00
November 0.284055E+10 3578.09 26-NOV-06:55 0.00 0.00 0.00 0.00 0.00
December 0.547752E+10 3667.78 09-DEC-09:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.232846E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.661497E+10 4366.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDORFLR4 PTAC HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.965645E+10 5678.29 31-JAN-04:00 0.00 0.00 0.00 0.00 0.00
February 0.686052E+10 5798.44 02-FEB-00:20 0.00 0.00 0.00 0.00 0.00
March 0.441439E+10 4122.15 06-MAR-04:40 0.00 0.00 0.00 0.00 0.00
April 0.192081E+10 3048.48 03-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.160633E+09 1328.78 03-MAY-05:00 0.00 0.00 0.00 0.00 0.00
June 44242119.92 752.29 03-JUN-04:50 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.338714E+09 1900.80 30-SEP-05:02 0.00 0.00 0.00 0.00 0.00
October 0.168937E+10 2083.72 28-OCT-06:00 0.00 0.00 0.00 0.00 0.00
November 0.488284E+10 5275.12 26-NOV-07:00 0.00 0.00 0.00 0.00 0.00
December 0.829842E+10 5182.40 09-DEC-09:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.382664E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.965645E+10 5798.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FRONTSTAIRSFLR1 UNITHEATER HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 1169373.28 52.37 02-FEB-04:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1169373.28     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1169373.28 52.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FRONTSTAIRSFLR2 UNITHEATER HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 7334628.04 131.35 02-FEB-09:43 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 7334628.04     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 7334628.04 131.35   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FRONTSTAIRSFLR3 UNITHEATER HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 12385419.12 138.28 31-JAN-07:53 0.00 0.00 0.00 0.00 0.00
February 38505086.14 250.13 02-FEB-09:43 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 7942517.79 175.91 09-DEC-09:58 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 58833023.05     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 38505086.14 250.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FRONTSTAIRSFLR4 UNITHEATER HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.209991E+09 473.39 31-JAN-07:53 0.00 0.00 0.00 0.00 0.00
February 0.153199E+09 605.48 02-FEB-02:40 0.00 0.00 0.00 0.00 0.00
March 836539.26 80.74 06-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 19351369.61 307.57 26-NOV-04:00 0.00 0.00 0.00 0.00 0.00
December 91445640.77 539.76 09-DEC-09:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.474823E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.209991E+09 605.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: REARSTAIRSFLR1 UNITHEATER HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: REARSTAIRSFLR2 UNITHEATER HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: REARSTAIRSFLR3 UNITHEATER HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: REARSTAIRSFLR4 UNITHEATER HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 32631339.80 268.32 19-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 35871376.35 306.69 02-FEB-01:20 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 1377787.63 84.30 26-NOV-04:20 0.00 0.00 0.00 0.00 0.00
December 27409893.81 306.69 09-DEC-01:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 97290397.59     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 35871376.35 306.69   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECHRM UNITHEATER HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: SAC_FRONTOFFICE HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.436510E+10 7577.51 30-JAN-19:24 0.00 0.00 0.00 0.00 0.00
February 0.279447E+10 7647.88 04-FEB-09:24 0.00 0.00 0.00 0.00 0.00
March 0.118324E+10 5533.81 05-MAR-23:55 0.00 0.00 0.00 0.00 0.00
April 0.295941E+09 1370.71 03-APR-05:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.108195E+10 6978.47 26-NOV-00:45 0.00 0.00 0.00 0.00 0.00
December 0.280616E+10 6451.33 09-DEC-11:35 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.125269E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.436510E+10 7647.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: SAC_FRONTLOUNGE HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.646731E+10 9617.26 05-JAN-21:14 0.00 0.00 0.00 0.00 0.00
February 0.392610E+10 11142.01 01-FEB-10:24 0.00 0.00 0.00 0.00 0.00
March 0.160284E+10 4224.24 04-MAR-02:00 0.00 0.00 0.00 0.00 0.00
April 0.273271E+09 1589.44 03-APR-04:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.145246E+10 6287.71 26-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.395367E+10 8747.17 11-DEC-20:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.176757E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.646731E+10 11142.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: SAC_MEETINGROOM HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.461899E+10 16105.57 30-JAN-17:57 0.00 0.00 0.00 0.00 0.00
February 0.316479E+10 13149.76 05-FEB-17:47 0.00 0.00 0.00 0.00 0.00
March 0.166592E+10 9831.06 05-MAR-12:49 0.00 0.00 0.00 0.00 0.00
April 0.642783E+09 3251.58 03-APR-07:03 0.00 0.00 0.00 0.00 0.00
May 10741211.76 1644.00 02-MAY-09:04 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 941901.65 247.42 29-SEP-16:56 0.00 0.00 0.00 0.00 0.00
October 0.112338E+09 1881.73 23-OCT-09:03 0.00 0.00 0.00 0.00 0.00
November 0.156878E+10 5354.87 25-NOV-17:56 0.00 0.00 0.00 0.00 0.00
December 0.329013E+10 13418.47 11-DEC-14:27 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.150754E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.461899E+10 16105.57   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: SAC_EMPLOYEELOUNGE HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 58342485.58 782.91 31-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.109538E+09 1167.50 02-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 4401617.36 460.29 26-NOV-07:00 0.00 0.00 0.00 0.00 0.00
December 4312894.73 177.08 11-DEC-05:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.176595E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.109538E+09 1167.50   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: SAC_EXERCISECENTER HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.605359E+10 7599.15 05-JAN-04:12 0.00 0.00 0.00 0.00 0.00
February 0.428680E+10 7599.15 03-FEB-12:42 0.00 0.00 0.00 0.00 0.00
March 0.269302E+10 7599.15 06-MAR-03:32 0.00 0.00 0.00 0.00 0.00
April 0.126391E+10 2249.92 03-APR-05:00 0.00 0.00 0.00 0.00 0.00
May 0.198160E+09 1256.92 03-MAY-03:00 0.00 0.00 0.00 0.00 0.00
June 39596136.19 741.67 03-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 359850.08 71.92 24-JUL-05:00 0.00 0.00 0.00 0.00 0.00
August 2452775.87 254.49 07-AUG-04:00 0.00 0.00 0.00 0.00 0.00
September 0.175784E+09 1332.37 30-SEP-04:00 0.00 0.00 0.00 0.00 0.00
October 0.755997E+09 1514.35 23-OCT-05:00 0.00 0.00 0.00 0.00 0.00
November 0.256031E+10 7599.15 26-NOV-03:12 0.00 0.00 0.00 0.00 0.00
December 0.469534E+10 7599.15 09-DEC-01:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.227253E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 359850.08 71.92   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.605359E+10 7599.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: SAC_RESTROOM HEATING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 3050474.72 56.41 03-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3050474.72     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 3050474.72 56.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 101 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00
June 0.00 0.00 302545.59 222745.10 81.25 11-JUN-15:00 58.77 0.00
July 0.00 0.00 1549211.71 1011820.78 128.72 03-JUL-14:40 84.37 0.00
August 0.00 0.00 960670.62 557953.28 255.09 04-AUG-14:30 139.60 0.00
September 0.00 0.00 966288.89 913567.67 129.81 07-SEP-14:30 124.33 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 3778716.80 2706086.82       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 1549211.71 1011820.78 255.09   139.60 0.00



Table of Contents

Report: CoilReportMonthly

For: 102 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.00 0.00       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 103 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 601366.51 446978.27 1112.44 16-JAN-16:03 731.90 0.00
February 0.00 0.00 2497432.63 1818461.40 2948.71 25-FEB-16:01 1920.18 0.00
March 0.00 0.00 51893356.50 36556267.38 3150.58 19-MAR-15:01 1697.32 0.00
April 0.00 0.00 0.311769E+09 0.227761E+09 3317.74 18-APR-08:51 1849.54 0.00
May 0.00 0.00 0.843489E+09 0.599247E+09 3446.51 11-MAY-20:21 1537.93 0.00
June 0.00 0.00 0.156962E+10 0.113021E+10 3477.47 13-JUN-08:51 1639.64 0.00
July 0.00 0.00 0.197796E+10 0.140483E+10 3507.97 17-JUL-08:51 1714.32 0.00
August 0.00 0.00 0.193478E+10 0.139530E+10 3528.93 22-AUG-08:51 1697.91 0.00
September 0.00 0.00 0.139653E+10 0.110711E+10 3381.46 11-SEP-08:51 2006.46 0.00
October 0.00 0.00 0.558366E+09 0.443767E+09 3171.11 09-OCT-15:01 1824.19 0.00
November 0.00 0.00 0.233862E+09 0.173720E+09 3168.80 08-NOV-16:01 1838.71 0.00
December 0.00 0.00 1903224.40 1458306.53 2488.59 03-DEC-16:01 1649.76 0.00
                 
Annual Sum or Average 0.00 0.00 0.888327E+10 0.652222E+10       0.00
Minimum of Months 0.00 0.00 601366.51 446978.27 1112.44   731.90 0.00
Maximum of Months 0.00 0.00 0.197796E+10 0.140483E+10 3528.93   2006.46 0.00



Table of Contents

Report: CoilReportMonthly

For: 104 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 5064337.08 3918021.20 2993.97 13-JAN-16:01 2179.33 0.00
February 0.00 0.00 18627887.09 14096634.85 3088.74 25-FEB-16:01 2096.78 0.00
March 0.00 0.00 0.143538E+09 0.108977E+09 3275.27 19-MAR-15:01 1959.09 0.00
April 0.00 0.00 0.460571E+09 0.350495E+09 3393.17 16-APR-08:11 2118.87 0.00
May 0.00 0.00 0.111728E+10 0.834909E+09 3509.60 11-MAY-18:11 1787.65 0.00
June 0.00 0.00 0.176009E+10 0.129552E+10 3523.69 14-JUN-16:51 2053.49 0.00
July 0.00 0.00 0.213480E+10 0.153654E+10 3567.30 20-JUL-08:61 1855.14 0.00
August 0.00 0.00 0.208764E+10 0.152557E+10 3575.05 31-AUG-08:61 1872.40 0.00
September 0.00 0.00 0.156420E+10 0.125971E+10 3452.17 11-SEP-08:61 2184.07 0.00
October 0.00 0.00 0.805954E+09 0.667415E+09 3241.31 02-OCT-17:21 2295.87 0.00
November 0.00 0.00 0.353713E+09 0.276114E+09 3240.15 08-NOV-16:01 2063.80 0.00
December 0.00 0.00 14566725.21 11662049.05 3066.33 03-DEC-16:01 2130.22 0.00
                 
Annual Sum or Average 0.00 0.00 0.104660E+11 0.788492E+10       0.00
Minimum of Months 0.00 0.00 5064337.08 3918021.20 2993.97   1787.65 0.00
Maximum of Months 0.00 0.00 0.213480E+10 0.153654E+10 3575.05   2295.87 0.00



Table of Contents

Report: CoilReportMonthly

For: 105 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.389814E+09 0.358806E+09 4346.25 16-JAN-16:01 3482.75 0.00
February 0.00 0.00 0.630289E+09 0.577234E+09 4310.52 20-FEB-16:01 3592.01 0.00
March 0.00 0.00 0.110746E+10 0.100236E+10 4602.46 19-MAR-18:41 3716.45 0.00
April 0.00 0.00 0.156818E+10 0.137749E+10 4855.86 16-APR-08:11 3458.54 0.00
May 0.00 0.00 0.225022E+10 0.188514E+10 4979.67 11-MAY-21:11 3178.58 0.00
June 0.00 0.00 0.273182E+10 0.219830E+10 5033.93 13-JUN-08:61 3123.91 0.00
July 0.00 0.00 0.301953E+10 0.235863E+10 5085.79 20-JUL-08:61 3066.65 0.00
August 0.00 0.00 0.294021E+10 0.232039E+10 5076.82 31-AUG-08:61 3087.19 0.00
September 0.00 0.00 0.247514E+10 0.212577E+10 4913.59 11-SEP-08:61 3393.65 0.00
October 0.00 0.00 0.193665E+10 0.174747E+10 4620.33 02-OCT-17:21 3815.31 0.00
November 0.00 0.00 0.128879E+10 0.115575E+10 4432.32 08-NOV-09:01 3479.78 0.00
December 0.00 0.00 0.662816E+09 0.617411E+09 4317.80 30-DEC-16:01 3528.70 0.00
                 
Annual Sum or Average 0.00 0.00 0.210009E+11 0.177248E+11       0.00
Minimum of Months 0.00 0.00 0.389814E+09 0.358806E+09 4310.52   3066.65 0.00
Maximum of Months 0.00 0.00 0.301953E+10 0.235863E+10 5085.79   3815.31 0.00



Table of Contents

Report: CoilReportMonthly

For: 201 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 13274.49 10277.41 22.12 16-APR-15:00 17.13 0.00
May 0.00 0.00 1003505.74 808675.87 140.51 31-MAY-15:00 113.95 0.00
June 0.00 0.00 24064012.83 18401235.46 347.06 11-JUN-15:00 245.15 0.00
July 0.00 0.00 27997832.83 20524024.75 309.76 03-JUL-15:00 209.46 0.00
August 0.00 0.00 9823042.82 6305614.29 506.91 04-AUG-15:00 280.43 0.00
September 0.00 0.00 2826301.44 2615811.57 174.84 07-SEP-15:00 167.01 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 65727970.14 48665639.34       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 27997832.83 20524024.75 506.91   280.43 0.00



Table of Contents

Report: CoilReportMonthly

For: 202_205 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 6326300.78 4735445.07 11508.14 13-JAN-19:01 7986.99 0.00
February 0.00 0.00 56019332.64 40929138.70 12003.02 25-FEB-16:01 7791.59 0.00
March 0.00 0.00 0.645685E+09 0.493723E+09 12777.47 19-MAR-15:01 7297.60 0.00
April 0.00 0.00 0.240558E+10 0.190279E+10 13595.93 18-APR-08:51 7905.88 0.00
May 0.00 0.00 0.498724E+10 0.381458E+10 13883.79 11-MAY-20:21 7070.94 0.00
June 0.00 0.00 0.722145E+10 0.537082E+10 14132.93 13-JUN-08:51 6883.09 0.00
July 0.00 0.00 0.826038E+10 0.595109E+10 14060.48 17-JUL-08:51 7135.78 0.00
August 0.00 0.00 0.767287E+10 0.554279E+10 14244.96 22-AUG-08:51 6894.51 0.00
September 0.00 0.00 0.531424E+10 0.418649E+10 13562.48 11-SEP-08:51 8056.66 0.00
October 0.00 0.00 0.225331E+10 0.178989E+10 12584.21 09-OCT-15:01 7436.41 0.00
November 0.00 0.00 0.946254E+09 0.702190E+09 12498.92 02-NOV-15:01 7563.95 0.00
December 0.00 0.00 11492096.47 8670848.68 11793.37 03-DEC-16:01 7446.48 0.00
                 
Annual Sum or Average 0.00 0.00 0.397808E+11 0.298087E+11       0.00
Minimum of Months 0.00 0.00 6326300.78 4735445.07 11508.14   6883.09 0.00
Maximum of Months 0.00 0.00 0.826038E+10 0.595109E+10 14244.96   8056.66 0.00



Table of Contents

Report: CoilReportMonthly

For: 206_208 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 14113424.01 11007034.35 9466.06 13-JAN-16:01 6860.69 0.00
February 0.00 0.00 95339037.08 73874923.26 9856.09 25-FEB-16:01 6869.18 0.00
March 0.00 0.00 0.641949E+09 0.510797E+09 10347.48 19-MAR-20:01 7021.36 0.00
April 0.00 0.00 0.208853E+10 0.169048E+10 11158.16 18-APR-08:51 6679.08 0.00
May 0.00 0.00 0.404768E+10 0.314364E+10 11403.31 11-MAY-20:21 5986.63 0.00
June 0.00 0.00 0.571325E+10 0.428568E+10 11624.57 13-JUN-08:51 5795.14 0.00
July 0.00 0.00 0.651054E+10 0.472658E+10 11560.95 17-JUL-08:51 6003.53 0.00
August 0.00 0.00 0.604978E+10 0.440559E+10 11706.21 22-AUG-08:51 5815.94 0.00
September 0.00 0.00 0.423960E+10 0.337686E+10 11161.38 11-SEP-08:51 6748.75 0.00
October 0.00 0.00 0.192351E+10 0.156519E+10 10280.49 02-OCT-17:21 7549.94 0.00
November 0.00 0.00 0.831858E+09 0.634499E+09 10253.35 08-NOV-16:01 6445.73 0.00
December 0.00 0.00 24871318.21 19952429.71 9711.10 03-DEC-16:01 6562.90 0.00
                 
Annual Sum or Average 0.00 0.00 0.321810E+11 0.244441E+11       0.00
Minimum of Months 0.00 0.00 14113424.01 11007034.35 9466.06   5795.14 0.00
Maximum of Months 0.00 0.00 0.651054E+10 0.472658E+10 11706.21   7549.94 0.00



Table of Contents

Report: CoilReportMonthly

For: 209_212 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 33219728.86 25702793.29 10777.64 16-JAN-16:01 6761.32 0.00
February 0.00 0.00 0.127367E+09 96635759.45 11060.91 25-FEB-16:01 7447.59 0.00
March 0.00 0.00 0.728612E+09 0.562877E+09 11613.43 19-MAR-20:01 7669.30 0.00
April 0.00 0.00 0.225798E+10 0.176684E+10 12538.01 18-APR-08:51 7093.16 0.00
May 0.00 0.00 0.446221E+10 0.334439E+10 12844.38 11-MAY-20:21 6388.25 0.00
June 0.00 0.00 0.640504E+10 0.463631E+10 13108.69 13-JUN-08:51 6092.99 0.00
July 0.00 0.00 0.740020E+10 0.518316E+10 13137.15 17-JUL-08:51 6318.78 0.00
August 0.00 0.00 0.692836E+10 0.487748E+10 13268.52 22-AUG-08:51 6156.89 0.00
September 0.00 0.00 0.487997E+10 0.379186E+10 12623.08 11-SEP-08:51 7246.98 0.00
October 0.00 0.00 0.229339E+10 0.182926E+10 11539.62 02-OCT-17:21 8182.61 0.00
November 0.00 0.00 0.103272E+10 0.772273E+09 11502.68 08-NOV-16:01 7034.89 0.00
December 0.00 0.00 56758025.80 44663797.77 10952.19 03-DEC-16:01 7201.75 0.00
                 
Annual Sum or Average 0.00 0.00 0.366058E+11 0.269315E+11       0.00
Minimum of Months 0.00 0.00 33219728.86 25702793.29 10777.64   6092.99 0.00
Maximum of Months 0.00 0.00 0.740020E+10 0.518316E+10 13268.52   8182.61 0.00



Table of Contents

Report: CoilReportMonthly

For: 213 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 318427.60 234264.87 907.13 13-JAN-16:02 612.06 0.00
February 0.00 0.00 2795219.76 1951409.38 3015.97 25-FEB-16:01 1870.42 0.00
March 0.00 0.00 73544789.22 52564388.99 3235.99 19-MAR-15:01 1684.27 0.00
April 0.00 0.00 0.407132E+09 0.308310E+09 3415.56 18-APR-08:51 1894.03 0.00
May 0.00 0.00 0.983828E+09 0.721128E+09 3511.60 11-MAY-20:21 1619.08 0.00
June 0.00 0.00 0.164300E+10 0.119737E+10 3578.65 13-JUN-08:51 1638.20 0.00
July 0.00 0.00 0.197491E+10 0.140631E+10 3613.74 17-JUL-08:51 1692.51 0.00
August 0.00 0.00 0.183451E+10 0.130923E+10 3631.62 22-AUG-08:51 1660.72 0.00
September 0.00 0.00 0.121133E+10 0.941063E+09 3468.50 11-SEP-08:51 1972.52 0.00
October 0.00 0.00 0.367765E+09 0.278474E+09 3266.62 10-OCT-15:01 1803.28 0.00
November 0.00 0.00 0.155688E+09 0.108880E+09 3251.03 08-NOV-16:01 1684.80 0.00
December 0.00 0.00 596063.74 464773.92 702.80 03-DEC-09:01 545.44 0.00
                 
Annual Sum or Average 0.00 0.00 0.865542E+10 0.632598E+10       0.00
Minimum of Months 0.00 0.00 318427.60 234264.87 702.80   545.44 0.00
Maximum of Months 0.00 0.00 0.197491E+10 0.140631E+10 3631.62   1972.52 0.00



Table of Contents

Report: CoilReportMonthly

For: 214 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 19540786.91 15235893.23 3364.27 01-JAN-16:01 2096.77 0.00
February 0.00 0.00 82469304.96 65584939.19 3411.96 25-FEB-16:01 2343.61 0.00
March 0.00 0.00 0.342080E+09 0.280372E+09 3497.63 18-MAR-15:01 2222.11 0.00
April 0.00 0.00 0.854844E+09 0.702408E+09 3722.05 16-APR-08:11 2474.77 0.00
May 0.00 0.00 0.163128E+10 0.130277E+10 3805.60 11-MAY-21:11 2202.74 0.00
June 0.00 0.00 0.220216E+10 0.170012E+10 3891.93 13-JUN-08:61 2123.26 0.00
July 0.00 0.00 0.250823E+10 0.187900E+10 3946.19 20-JUL-08:61 2065.27 0.00
August 0.00 0.00 0.237325E+10 0.178878E+10 3957.80 31-AUG-08:61 2043.75 0.00
September 0.00 0.00 0.177411E+10 0.145712E+10 3793.54 11-SEP-08:61 2385.19 0.00
October 0.00 0.00 0.969314E+09 0.818920E+09 3526.76 02-OCT-17:21 2615.46 0.00
November 0.00 0.00 0.442227E+09 0.354202E+09 3440.85 08-NOV-16:01 2395.53 0.00
December 0.00 0.00 31474286.53 25083575.26 3394.84 03-DEC-16:01 2294.38 0.00
                 
Annual Sum or Average 0.00 0.00 0.132310E+11 0.103896E+11       0.00
Minimum of Months 0.00 0.00 19540786.91 15235893.23 3364.27   2043.75 0.00
Maximum of Months 0.00 0.00 0.250823E+10 0.187900E+10 3957.80   2615.46 0.00



Table of Contents

Report: CoilReportMonthly

For: 215_218 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.196606E+10 0.196606E+10 2343.08 13-JAN-17:23 2343.08 0.00
February 0.00 0.00 0.233720E+10 0.233720E+10 2589.87 24-FEB-17:23 2589.87 0.00
March 0.00 0.00 0.375357E+10 0.375357E+10 3416.66 19-MAR-15:00 3416.66 0.00
April 0.00 0.00 0.476078E+10 0.474521E+10 5261.48 18-APR-15:00 5000.61 0.00
May 0.00 0.00 0.642366E+10 0.637482E+10 5423.49 31-MAY-15:00 5301.97 0.00
June 0.00 0.00 0.717026E+10 0.702685E+10 6036.46 11-JUN-15:00 5543.09 0.00
July 0.00 0.00 0.793370E+10 0.771046E+10 5786.36 26-JUL-15:00 5109.51 0.00
August 0.00 0.00 0.769479E+10 0.749806E+10 6156.46 04-AUG-15:00 5524.54 0.00
September 0.00 0.00 0.643232E+10 0.639847E+10 5561.74 06-SEP-15:00 5399.91 0.00
October 0.00 0.00 0.497728E+10 0.497728E+10 4047.78 20-OCT-15:00 4047.78 0.00
November 0.00 0.00 0.350848E+10 0.350817E+10 3336.80 03-NOV-15:00 3336.80 0.00
December 0.00 0.00 0.244431E+10 0.244431E+10 2371.27 03-DEC-17:22 2371.27 0.00
                 
Annual Sum or Average 0.00 0.00 0.594024E+11 0.587404E+11       0.00
Minimum of Months 0.00 0.00 0.196606E+10 0.196606E+10 2343.08   2343.08 0.00
Maximum of Months 0.00 0.00 0.793370E+10 0.771046E+10 6156.46   5543.09 0.00



Table of Contents

Report: CoilReportMonthly

For: 219 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.549845E+10 0.542714E+10 17698.53 31-JAN-10:41 17698.53 0.00
February 0.00 0.00 0.517231E+10 0.507486E+10 17870.55 04-FEB-10:31 17870.55 0.00
March 0.00 0.00 0.697895E+10 0.680468E+10 17846.96 19-MAR-18:41 16475.22 0.00
April 0.00 0.00 0.744869E+10 0.717298E+10 18216.30 18-APR-08:61 15633.64 0.00
May 0.00 0.00 0.842606E+10 0.793804E+10 18353.84 12-MAY-08:11 15381.44 0.00
June 0.00 0.00 0.878779E+10 0.811686E+10 18466.89 13-JUN-08:61 15145.49 0.00
July 0.00 0.00 0.921251E+10 0.839840E+10 18540.75 20-JUL-08:61 15072.47 0.00
August 0.00 0.00 0.906340E+10 0.829546E+10 18534.78 31-AUG-08:61 15063.25 0.00
September 0.00 0.00 0.835798E+10 0.790693E+10 18392.75 11-SEP-08:61 15382.66 0.00
October 0.00 0.00 0.786193E+10 0.759858E+10 17885.88 11-OCT-18:21 16236.22 0.00
November 0.00 0.00 0.679724E+10 0.660291E+10 17230.31 26-NOV-08:11 17230.31 0.00
December 0.00 0.00 0.615050E+10 0.605698E+10 10573.37 03-DEC-16:01 10325.55 0.00
                 
Annual Sum or Average 0.00 0.00 0.897558E+11 0.853938E+11       0.00
Minimum of Months 0.00 0.00 0.517231E+10 0.507486E+10 10573.37   10325.55 0.00
Maximum of Months 0.00 0.00 0.921251E+10 0.839840E+10 18540.75   17870.55 0.00



Table of Contents

Report: CoilReportMonthly

For: 220_223 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 56347361.28 44573043.60 11106.20 01-JAN-16:01 6993.61 0.00
February 0.00 0.00 0.170998E+09 0.132055E+09 11342.93 25-FEB-16:01 7636.83 0.00
March 0.00 0.00 0.894676E+09 0.703830E+09 11761.66 19-MAR-18:41 8169.94 0.00
April 0.00 0.00 0.241673E+10 0.190109E+10 12469.98 16-APR-08:11 8073.68 0.00
May 0.00 0.00 0.490630E+10 0.373268E+10 12747.97 11-MAY-21:11 7071.46 0.00
June 0.00 0.00 0.666517E+10 0.485164E+10 13036.82 13-JUN-08:61 6799.80 0.00
July 0.00 0.00 0.756303E+10 0.528812E+10 13238.50 20-JUL-08:61 6570.55 0.00
August 0.00 0.00 0.706428E+10 0.496608E+10 13229.03 31-AUG-08:61 6623.14 0.00
September 0.00 0.00 0.507856E+10 0.396180E+10 12772.91 11-SEP-08:61 7688.69 0.00
October 0.00 0.00 0.253371E+10 0.204440E+10 11827.55 02-OCT-17:21 8331.77 0.00
November 0.00 0.00 0.114509E+10 0.867598E+09 11690.95 08-NOV-16:01 7462.90 0.00
December 0.00 0.00 78743354.86 62718280.99 11235.88 03-DEC-16:01 7462.83 0.00
                 
Annual Sum or Average 0.00 0.00 0.385736E+11 0.285566E+11       0.00
Minimum of Months 0.00 0.00 56347361.28 44573043.60 11106.20   6570.55 0.00
Maximum of Months 0.00 0.00 0.756303E+10 0.528812E+10 13238.50   8331.77 0.00



Table of Contents

Report: CoilReportMonthly

For: 224 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1203123.24 902407.39 2993.34 14-JAN-09:01 2378.45 0.00
February 0.00 0.00 8793790.26 6410047.80 3230.22 25-FEB-16:01 2026.33 0.00
March 0.00 0.00 0.152864E+09 0.116292E+09 3433.53 19-MAR-15:01 1944.75 0.00
April 0.00 0.00 0.564224E+09 0.441336E+09 3549.67 16-APR-08:11 2281.00 0.00
May 0.00 0.00 0.132691E+10 0.102342E+10 3634.89 11-MAY-18:11 1969.32 0.00
June 0.00 0.00 0.193115E+10 0.145146E+10 3703.38 13-JUN-08:61 1948.85 0.00
July 0.00 0.00 0.222087E+10 0.161657E+10 3764.79 20-JUL-08:61 1890.67 0.00
August 0.00 0.00 0.206395E+10 0.150662E+10 3773.64 31-AUG-08:61 1854.80 0.00
September 0.00 0.00 0.145235E+10 0.115637E+10 3639.71 11-SEP-08:61 2220.00 0.00
October 0.00 0.00 0.594547E+09 0.473327E+09 3465.31 09-OCT-15:01 1920.79 0.00
November 0.00 0.00 0.248932E+09 0.185112E+09 3419.91 08-NOV-16:01 2003.91 0.00
December 0.00 0.00 1961420.46 1493594.21 3020.77 03-DEC-09:01 2426.17 0.00
                 
Annual Sum or Average 0.00 0.00 0.105678E+11 0.797931E+10       0.00
Minimum of Months 0.00 0.00 1203123.24 902407.39 2993.34   1854.80 0.00
Maximum of Months 0.00 0.00 0.222087E+10 0.161657E+10 3773.64   2426.17 0.00



Table of Contents

Report: CoilReportMonthly

For: 301 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.00 0.00 716683.67 575136.44 77.80 31-MAY-15:00 63.19 0.00
June 0.00 0.00 21286236.50 16095048.54 343.18 25-JUN-14:20 254.48 0.00
July 0.00 0.00 19818785.92 14118036.13 254.15 03-JUL-17:23 171.25 0.00
August 0.00 0.00 5185658.77 3039970.73 479.81 04-AUG-14:10 232.42 0.00
September 0.00 0.00 681881.09 636368.75 94.67 07-SEP-15:00 90.67 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 47689245.95 34464560.59       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 21286236.50 16095048.54 479.81   254.48 0.00



Table of Contents

Report: CoilReportMonthly

For: 302_305 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 501824.05 400761.53 116.59 16-APR-17:23 92.89 0.00
May 0.00 0.00 4398237.31 3562685.12 452.81 31-MAY-15:00 373.34 0.00
June 0.00 0.00 73367940.19 56912332.50 1033.80 11-JUN-15:00 744.83 0.00
July 0.00 0.00 98263929.96 72214870.10 864.96 03-JUL-15:00 593.57 0.00
August 0.00 0.00 30756067.62 20776381.85 1649.55 04-AUG-14:10 929.23 0.00
September 0.00 0.00 7605782.45 7161470.13 535.84 07-SEP-14:30 520.91 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.214894E+09 0.161029E+09       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 98263929.96 72214870.10 1649.55   929.23 0.00



Table of Contents

Report: CoilReportMonthly

For: 306_308 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 1128011.54 913035.03 162.00 16-APR-17:23 130.52 0.00
May 0.00 0.00 4815964.38 3908998.56 427.33 31-MAY-15:00 353.57 0.00
June 0.00 0.00 66924854.02 52571711.62 869.95 11-JUN-15:00 637.52 0.00
July 0.00 0.00 90673934.60 67943491.21 749.20 03-JUL-15:00 522.04 0.00
August 0.00 0.00 31126160.52 21951178.97 1202.11 04-AUG-14:10 680.61 0.00
September 0.00 0.00 8336466.63 7799761.82 468.88 07-SEP-15:00 458.37 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.203005E+09 0.155088E+09       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 90673934.60 67943491.21 1202.11   680.61 0.00



Table of Contents

Report: CoilReportMonthly

For: 309_312 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 8771709.36 6602905.12 10067.51 13-JAN-19:01 7097.19 0.00
February 0.00 0.00 59509468.54 43790991.21 10504.97 25-FEB-16:01 6913.81 0.00
March 0.00 0.00 0.523403E+09 0.392627E+09 11197.03 19-MAR-15:01 6468.76 0.00
April 0.00 0.00 0.194452E+10 0.149629E+10 11922.76 18-APR-08:51 6632.13 0.00
May 0.00 0.00 0.409632E+10 0.302425E+10 12270.16 11-MAY-20:21 5927.06 0.00
June 0.00 0.00 0.607548E+10 0.434827E+10 12472.24 13-JUN-08:51 5654.54 0.00
July 0.00 0.00 0.708909E+10 0.490936E+10 12612.64 17-JUL-08:51 5842.00 0.00
August 0.00 0.00 0.651617E+10 0.451352E+10 12656.44 22-AUG-08:51 5692.53 0.00
September 0.00 0.00 0.422738E+10 0.321129E+10 12079.57 11-SEP-08:51 6742.85 0.00
October 0.00 0.00 0.149941E+10 0.114043E+10 11309.52 09-OCT-15:01 6000.98 0.00
November 0.00 0.00 0.635508E+09 0.443079E+09 11306.77 08-NOV-16:01 5962.40 0.00
December 0.00 0.00 13601105.34 10439409.84 10315.77 03-DEC-16:01 6638.92 0.00
                 
Annual Sum or Average 0.00 0.00 0.326892E+11 0.235399E+11       0.00
Minimum of Months 0.00 0.00 8771709.36 6602905.12 10067.51   5654.54 0.00
Maximum of Months 0.00 0.00 0.708909E+10 0.490936E+10 12656.44   7097.19 0.00



Table of Contents

Report: CoilReportMonthly

For: 313 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00
June 0.00 0.00 1857397.83 1334540.71 121.96 26-JUN-14:30 89.52 0.00
July 0.00 0.00 2015871.67 1341875.10 98.99 03-JUL-15:00 63.29 0.00
August 0.00 0.00 528999.80 278736.26 235.34 04-AUG-15:00 125.11 0.00
September 0.00 0.00 69974.91 67349.91 52.89 07-SEP-15:00 51.16 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 4472244.21 3022501.97       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 2015871.67 1341875.10 235.34   125.11 0.00



Table of Contents

Report: CoilReportMonthly

For: 314 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 745363.12 541972.77 1843.09 13-JAN-19:01 1260.40 0.00
February 0.00 0.00 7103911.78 5096933.35 2922.16 25-FEB-16:01 1838.64 0.00
March 0.00 0.00 0.134054E+09 0.101385E+09 3121.38 19-MAR-15:01 1791.44 0.00
April 0.00 0.00 0.555492E+09 0.436248E+09 3221.62 16-APR-08:11 2104.79 0.00
May 0.00 0.00 0.130451E+10 0.100374E+10 3314.57 11-MAY-18:11 1748.13 0.00
June 0.00 0.00 0.195743E+10 0.147542E+10 3365.21 13-JUN-08:61 1753.86 0.00
July 0.00 0.00 0.228945E+10 0.167608E+10 3424.42 20-JUL-08:61 1703.38 0.00
August 0.00 0.00 0.210511E+10 0.154135E+10 3433.45 31-AUG-08:61 1651.76 0.00
September 0.00 0.00 0.138702E+10 0.109892E+10 3306.08 11-SEP-08:61 2008.20 0.00
October 0.00 0.00 0.439230E+09 0.339807E+09 3148.35 09-OCT-15:01 1661.76 0.00
November 0.00 0.00 0.177975E+09 0.126694E+09 3144.11 08-NOV-16:01 1683.80 0.00
December 0.00 0.00 1351138.18 1000016.24 2719.14 03-DEC-09:01 2156.18 0.00
                 
Annual Sum or Average 0.00 0.00 0.103595E+11 0.780629E+10       0.00
Minimum of Months 0.00 0.00 745363.12 541972.77 1843.09   1260.40 0.00
Maximum of Months 0.00 0.00 0.228945E+10 0.167608E+10 3433.45   2156.18 0.00



Table of Contents

Report: CoilReportMonthly

For: 315_318 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.335564E+09 0.283253E+09 12874.67 01-JAN-16:01 8635.09 0.00
February 0.00 0.00 0.901479E+09 0.772683E+09 12737.44 23-FEB-16:01 9190.26 0.00
March 0.00 0.00 0.230253E+10 0.198080E+10 13391.77 19-MAR-18:41 10379.37 0.00
April 0.00 0.00 0.427762E+10 0.361303E+10 14026.48 16-APR-08:11 9654.49 0.00
May 0.00 0.00 0.701032E+10 0.566275E+10 14390.33 11-MAY-21:11 8744.80 0.00
June 0.00 0.00 0.877152E+10 0.676835E+10 14678.97 13-JUN-08:61 8393.73 0.00
July 0.00 0.00 0.974146E+10 0.725403E+10 14894.26 20-JUL-08:61 8163.60 0.00
August 0.00 0.00 0.916215E+10 0.685733E+10 14884.84 31-AUG-08:61 8212.36 0.00
September 0.00 0.00 0.690091E+10 0.565154E+10 14340.56 11-SEP-08:61 9217.03 0.00
October 0.00 0.00 0.423080E+10 0.361998E+10 13446.46 02-OCT-17:21 10318.66 0.00
November 0.00 0.00 0.220568E+10 0.181463E+10 12961.34 08-NOV-09:01 9297.82 0.00
December 0.00 0.00 0.472050E+09 0.401094E+09 12871.95 31-DEC-16:01 8594.57 0.00
                 
Annual Sum or Average 0.00 0.00 0.563121E+11 0.446795E+11       0.00
Minimum of Months 0.00 0.00 0.335564E+09 0.283253E+09 12737.44   8163.60 0.00
Maximum of Months 0.00 0.00 0.974146E+10 0.725403E+10 14894.26   10379.37 0.00



Table of Contents

Report: CoilReportMonthly

For: 319 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 1758086.48 1563888.01 184.56 18-APR-15:00 158.88 0.00
May 0.00 0.00 9143711.13 7856701.84 267.57 31-MAY-15:00 243.54 0.00
June 0.00 0.00 52468927.89 44786815.18 369.75 11-JUN-15:00 294.34 0.00
July 0.00 0.00 66903486.47 54774359.10 280.67 03-JUL-15:00 210.82 0.00
August 0.00 0.00 34054760.66 27039370.62 413.15 04-AUG-15:00 276.03 0.00
September 0.00 0.00 9455040.98 8884587.07 254.91 07-SEP-14:05 247.49 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.173784E+09 0.144906E+09       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 66903486.47 54774359.10 413.15   294.34 0.00



Table of Contents

Report: CoilReportMonthly

For: 320_323 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 21044370.84 16359248.05 9715.08 13-JAN-19:01 6929.15 0.00
February 0.00 0.00 79492734.83 59903814.26 10075.80 25-FEB-16:01 6617.56 0.00
March 0.00 0.00 0.605862E+09 0.460247E+09 10576.86 19-MAR-15:01 6607.85 0.00
April 0.00 0.00 0.196006E+10 0.150277E+10 11164.55 16-APR-08:11 7053.98 0.00
May 0.00 0.00 0.428696E+10 0.318178E+10 11467.62 11-MAY-18:11 6018.08 0.00
June 0.00 0.00 0.611825E+10 0.436570E+10 11659.23 13-JUN-08:61 5853.32 0.00
July 0.00 0.00 0.707218E+10 0.484994E+10 11856.37 20-JUL-08:61 5613.68 0.00
August 0.00 0.00 0.649941E+10 0.446500E+10 11858.13 04-AUG-07:41 5685.70 0.00
September 0.00 0.00 0.429449E+10 0.325858E+10 11459.13 11-SEP-08:61 6687.23 0.00
October 0.00 0.00 0.161308E+10 0.123526E+10 10803.63 09-OCT-15:01 5959.50 0.00
November 0.00 0.00 0.692686E+09 0.487524E+09 10871.41 08-NOV-16:01 5841.83 0.00
December 0.00 0.00 29269802.62 22974451.25 9944.27 03-DEC-16:01 6468.11 0.00
                 
Annual Sum or Average 0.00 0.00 0.332728E+11 0.239060E+11       0.00
Minimum of Months 0.00 0.00 21044370.84 16359248.05 9715.08   5613.68 0.00
Maximum of Months 0.00 0.00 0.707218E+10 0.484994E+10 11858.13   7053.98 0.00



Table of Contents

Report: CoilReportMonthly

For: 324 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00
June 0.00 0.00 27408.75 19881.41 18.68 26-JUN-14:40 13.59 0.00
July 0.00 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00
August 0.00 0.00 11979.04 6193.40 19.97 04-AUG-15:00 10.32 0.00
September 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 39387.80 26074.81       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 27408.75 19881.41 19.97   13.59 0.00



Table of Contents

Report: CoilReportMonthly

For: 401 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 106845.24 80593.60 583.17 13-JAN-19:04 423.86 0.00
February 0.00 0.00 596273.59 438443.72 1059.29 25-FEB-16:02 695.56 0.00
March 0.00 0.00 34129792.83 25246508.52 3829.48 19-MAR-15:01 2261.69 0.00
April 0.00 0.00 0.375116E+09 0.290287E+09 4070.86 18-APR-08:51 2284.79 0.00
May 0.00 0.00 0.927305E+09 0.686759E+09 4191.90 11-MAY-20:21 2155.46 0.00
June 0.00 0.00 0.183281E+10 0.138333E+10 4275.15 13-JUN-08:51 1938.68 0.00
July 0.00 0.00 0.219936E+10 0.161638E+10 4293.62 20-JUL-08:51 2053.09 0.00
August 0.00 0.00 0.191912E+10 0.139400E+10 4337.25 22-AUG-08:51 2015.74 0.00
September 0.00 0.00 0.101286E+10 0.787920E+09 4125.15 11-SEP-08:51 2378.77 0.00
October 0.00 0.00 0.121803E+09 86400950.55 3889.17 10-OCT-15:01 2152.29 0.00
November 0.00 0.00 43217756.69 26707667.93 3937.35 07-NOV-16:01 1783.31 0.00
December 0.00 0.00 97482.35 74955.32 631.33 02-DEC-19:04 470.08 0.00
                 
Annual Sum or Average 0.00 0.00 0.846651E+10 0.629762E+10       0.00
Minimum of Months 0.00 0.00 97482.35 74955.32 583.17   423.86 0.00
Maximum of Months 0.00 0.00 0.219936E+10 0.161638E+10 4337.25   2378.77 0.00



Table of Contents

Report: CoilReportMonthly

For: 402_405 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 55236793.65 50181425.78 1308.35 16-APR-15:00 1106.64 0.00
May 0.00 0.00 0.100998E+09 92473905.09 1548.87 31-MAY-15:00 1414.54 0.00
June 0.00 0.00 0.490052E+09 0.426248E+09 2370.80 11-JUN-15:00 1887.75 0.00
July 0.00 0.00 0.621788E+09 0.523420E+09 2204.91 03-JUL-15:00 1669.93 0.00
August 0.00 0.00 0.403842E+09 0.339074E+09 2790.63 04-AUG-15:00 2004.65 0.00
September 0.00 0.00 0.177060E+09 0.168460E+09 1701.09 07-SEP-15:00 1693.93 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.184898E+10 0.159986E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.621788E+09 0.523420E+09 2790.63   2004.65 0.00



Table of Contents

Report: CoilReportMonthly

For: 406_408 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 56190648.80 51660424.79 1222.04 16-APR-15:00 1044.23 0.00
May 0.00 0.00 0.109261E+09 0.101429E+09 1384.98 31-MAY-15:00 1275.64 0.00
June 0.00 0.00 0.445171E+09 0.392191E+09 2041.20 11-JUN-15:00 1650.61 0.00
July 0.00 0.00 0.563729E+09 0.482305E+09 1925.06 03-JUL-15:00 1483.55 0.00
August 0.00 0.00 0.377154E+09 0.322207E+09 2386.80 04-AUG-15:00 1740.57 0.00
September 0.00 0.00 0.170872E+09 0.163324E+09 1528.17 07-SEP-15:00 1521.66 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.172238E+10 0.151312E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.563729E+09 0.482305E+09 2386.80   1740.57 0.00



Table of Contents

Report: CoilReportMonthly

For: 409_412 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 3500184.27 2481659.94 11087.67 12-JAN-16:01 7875.67 0.00
February 0.00 0.00 44985842.50 32469700.25 13151.91 20-FEB-16:01 8734.78 0.00
March 0.00 0.00 0.447213E+09 0.334256E+09 13874.55 19-MAR-20:01 9794.00 0.00
April 0.00 0.00 0.187888E+10 0.145832E+10 14909.28 18-APR-08:51 8570.16 0.00
May 0.00 0.00 0.390424E+10 0.288502E+10 15291.23 11-MAY-20:01 8274.39 0.00
June 0.00 0.00 0.623989E+10 0.454365E+10 15630.81 13-JUN-08:51 7245.60 0.00
July 0.00 0.00 0.733748E+10 0.518458E+10 15477.65 20-JUL-08:51 7565.27 0.00
August 0.00 0.00 0.660063E+10 0.463936E+10 15669.07 22-AUG-08:51 7381.07 0.00
September 0.00 0.00 0.398097E+10 0.303531E+10 14897.95 11-SEP-08:51 8686.66 0.00
October 0.00 0.00 0.116490E+10 0.865920E+09 14058.59 09-OCT-15:01 7617.46 0.00
November 0.00 0.00 0.482261E+09 0.325687E+09 14171.55 08-NOV-16:01 7226.72 0.00
December 0.00 0.00 5519136.82 3993539.97 12932.30 03-DEC-16:01 8272.89 0.00
                 
Annual Sum or Average 0.00 0.00 0.320905E+11 0.233110E+11       0.00
Minimum of Months 0.00 0.00 3500184.27 2481659.94 11087.67   7226.72 0.00
Maximum of Months 0.00 0.00 0.733748E+10 0.518458E+10 15669.07   9794.00 0.00



Table of Contents

Report: CoilReportMonthly

For: 413 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 9154945.92 8312310.30 270.38 16-APR-15:00 229.57 0.00
May 0.00 0.00 14529943.54 13018347.77 393.10 31-MAY-15:00 353.48 0.00
June 0.00 0.00 91796160.81 79679781.38 580.73 11-JUN-15:00 470.39 0.00
July 0.00 0.00 0.119557E+09 0.101131E+09 511.10 03-JUL-15:00 394.10 0.00
August 0.00 0.00 75819175.80 63348833.28 738.41 04-AUG-15:00 522.32 0.00
September 0.00 0.00 39285510.27 37382674.69 493.46 07-SEP-15:00 489.38 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.350143E+09 0.302873E+09       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.119557E+09 0.101131E+09 738.41   522.32 0.00



Table of Contents

Report: CoilReportMonthly

For: 414 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 3751064.22 3327512.56 224.56 18-APR-15:00 192.80 0.00
May 0.00 0.00 10604665.88 9300731.20 343.94 31-MAY-15:00 317.13 0.00
June 0.00 0.00 72709881.32 62701103.39 486.48 11-JUN-15:00 386.28 0.00
July 0.00 0.00 80815212.31 66977353.15 375.20 03-JUL-15:00 282.37 0.00
August 0.00 0.00 50416555.02 40915293.31 570.12 04-AUG-15:00 414.36 0.00
September 0.00 0.00 23372248.50 22345479.37 404.23 07-SEP-14:05 400.45 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.241670E+09 0.205567E+09       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 80815212.31 66977353.15 570.12   414.36 0.00



Table of Contents

Report: CoilReportMonthly

For: 415_418 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 12299073.73 9227437.37 12534.27 13-JAN-16:01 8777.04 0.00
February 0.00 0.00 84642306.55 64042906.36 12964.70 20-FEB-16:01 8315.81 0.00
March 0.00 0.00 0.690614E+09 0.537482E+09 13375.58 19-MAR-18:41 10225.14 0.00
April 0.00 0.00 0.222574E+10 0.175435E+10 14131.40 16-APR-08:11 9425.99 0.00
May 0.00 0.00 0.465976E+10 0.354195E+10 14558.59 12-MAY-08:11 8496.58 0.00
June 0.00 0.00 0.680387E+10 0.502127E+10 14969.86 13-JUN-08:61 7865.90 0.00
July 0.00 0.00 0.786708E+10 0.560930E+10 15159.28 20-JUL-08:61 7683.57 0.00
August 0.00 0.00 0.713274E+10 0.507157E+10 15141.06 31-AUG-08:61 7743.67 0.00
September 0.00 0.00 0.456899E+10 0.354209E+10 14449.69 11-SEP-08:61 8985.86 0.00
October 0.00 0.00 0.163269E+10 0.126135E+10 13589.10 02-OCT-17:21 9940.98 0.00
November 0.00 0.00 0.681869E+09 0.481666E+09 13665.95 08-NOV-16:01 7950.03 0.00
December 0.00 0.00 17762846.23 13646637.26 12814.68 03-DEC-16:01 8379.50 0.00
                 
Annual Sum or Average 0.00 0.00 0.363781E+11 0.269079E+11       0.00
Minimum of Months 0.00 0.00 12299073.73 9227437.37 12534.27   7683.57 0.00
Maximum of Months 0.00 0.00 0.786708E+10 0.560930E+10 15159.28   10225.14 0.00



Table of Contents

Report: CoilReportMonthly

For: 419 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1766447.66 1306909.95 3357.09 13-JAN-16:01 2314.67 0.00
February 0.00 0.00 18351127.21 13709484.67 3528.82 25-FEB-16:01 2343.70 0.00
March 0.00 0.00 0.189574E+09 0.148570E+09 3627.83 29-MAR-15:01 2246.63 0.00
April 0.00 0.00 0.649227E+09 0.520684E+09 3826.40 18-APR-08:61 2559.27 0.00
May 0.00 0.00 0.139321E+10 0.108853E+10 3922.23 11-MAY-21:11 2337.20 0.00
June 0.00 0.00 0.201092E+10 0.153197E+10 4027.90 13-JUN-08:61 2122.09 0.00
July 0.00 0.00 0.231937E+10 0.171412E+10 4103.19 20-JUL-08:61 2101.54 0.00
August 0.00 0.00 0.211060E+10 0.155595E+10 4116.87 31-AUG-08:61 2072.98 0.00
September 0.00 0.00 0.137122E+10 0.109086E+10 3917.13 11-SEP-08:61 2443.85 0.00
October 0.00 0.00 0.475615E+09 0.371991E+09 3665.34 02-OCT-17:21 2683.56 0.00
November 0.00 0.00 0.191919E+09 0.137440E+09 3718.59 08-NOV-16:01 2144.04 0.00
December 0.00 0.00 2802098.92 2118243.98 3477.11 03-DEC-16:01 2226.58 0.00
                 
Annual Sum or Average 0.00 0.00 0.107346E+11 0.817725E+10       0.00
Minimum of Months 0.00 0.00 1766447.66 1306909.95 3357.09   2072.98 0.00
Maximum of Months 0.00 0.00 0.231937E+10 0.171412E+10 4116.87   2683.56 0.00



Table of Contents

Report: CoilReportMonthly

For: 420_423 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 8917815.32 6807368.68 11125.06 01-JAN-09:01 8678.08 0.00
February 0.00 0.00 51416841.04 38215589.85 12001.45 25-FEB-16:01 7933.44 0.00
March 0.00 0.00 0.524440E+09 0.397223E+09 12473.24 29-MAR-15:01 7383.37 0.00
April 0.00 0.00 0.186912E+10 0.143942E+10 13137.27 16-APR-08:11 8616.37 0.00
May 0.00 0.00 0.407743E+10 0.302507E+10 13503.12 12-MAY-08:11 7598.25 0.00
June 0.00 0.00 0.611037E+10 0.440137E+10 13869.58 13-JUN-08:61 7030.82 0.00
July 0.00 0.00 0.712501E+10 0.494660E+10 14119.26 20-JUL-08:61 6878.21 0.00
August 0.00 0.00 0.644177E+10 0.445782E+10 14113.19 31-AUG-08:61 6948.38 0.00
September 0.00 0.00 0.401800E+10 0.304765E+10 13461.63 11-SEP-08:61 8166.55 0.00
October 0.00 0.00 0.128779E+10 0.967735E+09 12602.56 02-OCT-17:21 8811.63 0.00
November 0.00 0.00 0.547651E+09 0.374019E+09 12913.96 08-NOV-16:01 6849.02 0.00
December 0.00 0.00 13208844.51 10254434.56 11773.56 03-DEC-16:01 7543.85 0.00
                 
Annual Sum or Average 0.00 0.00 0.320751E+11 0.231122E+11       0.00
Minimum of Months 0.00 0.00 8917815.32 6807368.68 11125.06   6849.02 0.00
Maximum of Months 0.00 0.00 0.712501E+10 0.494660E+10 14119.26   8811.63 0.00



Table of Contents

Report: CoilReportMonthly

For: 424 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 352663.90 249194.56 696.37 13-JAN-16:03 472.33 0.00
February 0.00 0.00 1679939.17 1166047.48 3095.74 24-FEB-16:01 2017.68 0.00
March 0.00 0.00 72604107.31 52068363.49 3604.20 19-MAR-15:01 2198.96 0.00
April 0.00 0.00 0.426535E+09 0.326659E+09 3767.52 16-APR-08:11 2460.12 0.00
May 0.00 0.00 0.108807E+10 0.816385E+09 3849.33 11-MAY-18:11 2175.16 0.00
June 0.00 0.00 0.180520E+10 0.134904E+10 3931.64 13-JUN-08:61 1990.78 0.00
July 0.00 0.00 0.213241E+10 0.154683E+10 4006.95 20-JUL-08:61 1953.32 0.00
August 0.00 0.00 0.189691E+10 0.136489E+10 4016.80 31-AUG-08:61 1895.70 0.00
September 0.00 0.00 0.112628E+10 0.871734E+09 3851.52 11-SEP-08:61 2345.58 0.00
October 0.00 0.00 0.229730E+09 0.165885E+09 3708.06 09-OCT-15:01 1871.10 0.00
November 0.00 0.00 96842493.65 62621170.99 3697.05 08-NOV-16:01 1843.80 0.00
December 0.00 0.00 615086.44 459546.96 709.65 02-DEC-19:03 485.24 0.00
                 
Annual Sum or Average 0.00 0.00 0.887723E+10 0.655799E+10       0.00
Minimum of Months 0.00 0.00 352663.90 249194.56 696.37   472.33 0.00
Maximum of Months 0.00 0.00 0.213241E+10 0.154683E+10 4016.80   2460.12 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDORFLR1 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.316690E+09 0.316690E+09 3371.93 13-JAN-22:05 3371.93 0.00
February 0.00 0.00 0.755126E+09 0.755126E+09 4179.41 25-FEB-22:04 4179.41 0.00
March 0.00 0.00 0.251506E+10 0.250694E+10 5671.56 19-MAR-16:00 5386.74 0.00
April 0.00 0.00 0.638946E+10 0.606434E+10 18270.92 16-APR-16:20 13637.31 0.00
May 0.00 0.00 0.127372E+11 0.116759E+11 17430.26 31-MAY-17:00 13825.31 0.00
June 0.00 0.00 0.182193E+11 0.155844E+11 27627.38 11-JUN-16:20 18110.23 0.00
July 0.00 0.00 0.220508E+11 0.179890E+11 29596.46 26-JUL-16:20 15329.31 0.00
August 0.00 0.00 0.212174E+11 0.176140E+11 32819.92 04-AUG-16:10 19212.95 0.00
September 0.00 0.00 0.145045E+11 0.136739E+11 20690.40 06-SEP-16:20 16825.97 0.00
October 0.00 0.00 0.755324E+10 0.749550E+10 8452.59 21-OCT-17:02 7831.84 0.00
November 0.00 0.00 0.356521E+10 0.350601E+10 6719.00 08-NOV-18:15 5798.40 0.00
December 0.00 0.00 0.644021E+09 0.644021E+09 3441.81 02-DEC-22:14 3441.81 0.00
                 
Annual Sum or Average 0.00 0.00 0.110468E+12 0.978258E+11       0.00
Minimum of Months 0.00 0.00 0.316690E+09 0.316690E+09 3371.93   3371.93 0.00
Maximum of Months 0.00 0.00 0.220508E+11 0.179890E+11 32819.92   19212.95 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDORFLR2 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 9387796.03 8915780.48 290.03 19-MAR-18:52 263.97 0.00
April 0.00 0.00 0.573007E+09 0.500573E+09 2440.49 18-APR-15:00 1979.25 0.00
May 0.00 0.00 0.186376E+10 0.161669E+10 2467.49 31-MAY-15:00 2214.07 0.00
June 0.00 0.00 0.371065E+10 0.304703E+10 3228.68 11-JUN-15:10 2452.16 0.00
July 0.00 0.00 0.498454E+10 0.393586E+10 3267.18 26-JUL-18:20 2098.10 0.00
August 0.00 0.00 0.456037E+10 0.364289E+10 3453.39 04-AUG-15:13 2510.37 0.00
September 0.00 0.00 0.234592E+10 0.212442E+10 2663.57 06-SEP-15:01 2355.22 0.00
October 0.00 0.00 0.181182E+09 0.174431E+09 920.53 20-OCT-16:47 920.53 0.00
November 0.00 0.00 23736109.33 22047054.43 444.81 03-NOV-15:02 444.81 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.182526E+11 0.150729E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.498454E+10 0.393586E+10 3453.39   2510.37 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDORFLR3 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.207189E+09 0.151019E+09 1668.35 18-APR-15:00 1193.51 0.00
May 0.00 0.00 0.456888E+09 0.330870E+09 1827.77 31-MAY-15:02 1525.38 0.00
June 0.00 0.00 0.211984E+10 0.147647E+10 2099.98 11-JUN-15:10 1406.05 0.00
July 0.00 0.00 0.299175E+10 0.196097E+10 2293.96 26-JUL-19:00 1089.55 0.00
August 0.00 0.00 0.239594E+10 0.156791E+10 2242.69 04-AUG-13:00 1193.68 0.00
September 0.00 0.00 0.937314E+09 0.741182E+09 1849.42 06-SEP-15:11 1527.77 0.00
October 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.910892E+10 0.622842E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.299175E+10 0.196097E+10 2293.96   1527.77 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDORFLR4 PTAC PTAC COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.291521E+09 0.235490E+09 2587.37 18-APR-15:00 2054.37 0.00
May 0.00 0.00 0.762031E+09 0.627174E+09 2775.45 31-MAY-15:00 2477.34 0.00
June 0.00 0.00 0.229506E+10 0.177975E+10 3041.01 13-JUN-15:02 2087.97 0.00
July 0.00 0.00 0.300786E+10 0.221414E+10 3132.31 26-JUL-16:52 1941.79 0.00
August 0.00 0.00 0.247669E+10 0.182795E+10 3155.55 04-AUG-11:10 1868.62 0.00
September 0.00 0.00 0.103563E+10 0.906973E+09 2798.53 06-SEP-15:23 2452.12 0.00
October 0.00 0.00 3791690.46 3791690.46 329.77 20-OCT-15:01 329.77 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.987259E+10 0.759526E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.300786E+10 0.221414E+10 3155.55   2477.34 0.00



Table of Contents

Report: CoilReportMonthly

For: SAC_FRONTOFFICE COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 69207424.72 68009641.79 1136.74 28-MAR-15:00 1136.74 0.00
April 0.00 0.00 0.708748E+09 0.597305E+09 3930.53 18-APR-11:00 2883.54 0.00
May 0.00 0.00 0.229205E+10 0.190568E+10 4106.54 31-MAY-09:55 3199.38 0.00
June 0.00 0.00 0.464300E+10 0.361469E+10 4966.18 26-JUN-09:33 3391.38 0.00
July 0.00 0.00 0.607537E+10 0.450990E+10 5291.08 26-JUL-16:00 3340.69 0.00
August 0.00 0.00 0.578945E+10 0.437162E+10 5810.69 04-AUG-13:00 3656.04 0.00
September 0.00 0.00 0.328484E+10 0.289920E+10 4392.03 06-SEP-15:10 3687.58 0.00
October 0.00 0.00 0.665823E+09 0.634897E+09 2189.37 02-OCT-15:01 1767.71 0.00
November 0.00 0.00 0.263124E+09 0.231798E+09 1624.42 08-NOV-16:01 1326.52 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.237916E+11 0.188331E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.607537E+10 0.450990E+10 5810.69   3687.58 0.00



Table of Contents

Report: CoilReportMonthly

For: SAC_FRONTLOUNGE COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.704768E+09 0.477137E+09 8282.79 18-APR-08:51 4827.99 0.00
May 0.00 0.00 0.125675E+10 0.839650E+09 9398.80 31-MAY-08:51 6186.10 0.00
June 0.00 0.00 0.594318E+10 0.383742E+10 12596.20 26-JUN-07:11 5890.24 0.00
July 0.00 0.00 0.856946E+10 0.515572E+10 11985.42 03-JUL-08:30 6023.54 0.00
August 0.00 0.00 0.734877E+10 0.447376E+10 16158.48 04-AUG-06:50 5840.71 0.00
September 0.00 0.00 0.303519E+10 0.229164E+10 10554.06 11-SEP-08:50 5973.82 0.00
October 0.00 0.00 35083930.47 32649685.03 2815.71 20-OCT-15:10 2732.34 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.268932E+11 0.171080E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.856946E+10 0.515572E+10 16158.48   6186.10 0.00



Table of Contents

Report: CoilReportMonthly

For: SAC_MEETINGROOM COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 382031.97 354905.51 489.30 28-MAR-12:50 458.80 0.00
April 0.00 0.00 0.375624E+09 0.270212E+09 4401.32 18-APR-13:00 2755.20 0.00
May 0.00 0.00 0.966969E+09 0.710760E+09 4390.97 31-MAY-13:00 3257.38 0.00
June 0.00 0.00 0.284696E+10 0.197141E+10 5537.78 13-JUN-13:00 2927.63 0.00
July 0.00 0.00 0.395525E+10 0.260344E+10 6246.78 03-JUL-13:00 3268.25 0.00
August 0.00 0.00 0.375596E+10 0.252104E+10 7492.36 04-AUG-13:00 3702.15 0.00
September 0.00 0.00 0.185456E+10 0.150618E+10 4848.20 06-SEP-13:00 3528.68 0.00
October 0.00 0.00 0.117880E+09 0.103465E+09 1881.72 20-OCT-13:00 1703.57 0.00
November 0.00 0.00 17909872.53 14193591.79 974.72 03-NOV-12:30 794.42 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.138915E+11 0.970106E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.395525E+10 0.260344E+10 7492.36   3702.15 0.00



Table of Contents

Report: CoilReportMonthly

For: SAC_EMPLOYEELOUNGE COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.176999E+10 0.176999E+10 5951.49 30-JAN-13:01 5951.49 0.00
February 0.00 0.00 0.239267E+10 0.239267E+10 3401.89 24-FEB-13:00 3401.89 0.00
March 0.00 0.00 0.396954E+10 0.396408E+10 4048.24 19-MAR-16:10 3898.07 0.00
April 0.00 0.00 0.533320E+10 0.520093E+10 6270.82 18-APR-12:00 5101.86 0.00
May 0.00 0.00 0.754561E+10 0.707232E+10 6124.98 31-MAY-12:00 5284.57 0.00
June 0.00 0.00 0.900294E+10 0.797501E+10 6658.01 27-JUN-12:00 5228.25 0.00
July 0.00 0.00 0.102438E+11 0.870769E+10 6842.89 03-JUL-12:00 5152.98 0.00
August 0.00 0.00 0.995627E+10 0.857682E+10 7507.77 04-AUG-12:00 5443.00 0.00
September 0.00 0.00 0.768802E+10 0.733737E+10 6325.02 11-SEP-12:00 5203.03 0.00
October 0.00 0.00 0.581763E+10 0.577892E+10 4752.02 02-OCT-12:00 4136.04 0.00
November 0.00 0.00 0.405917E+10 0.401140E+10 4529.44 08-NOV-13:00 3957.71 0.00
December 0.00 0.00 0.251691E+10 0.251691E+10 2906.55 02-DEC-16:00 2906.55 0.00
                 
Annual Sum or Average 0.00 0.00 0.702958E+11 0.653041E+11       0.00
Minimum of Months 0.00 0.00 0.176999E+10 0.176999E+10 2906.55   2906.55 0.00
Maximum of Months 0.00 0.00 0.102438E+11 0.870769E+10 7507.77   5951.49 0.00



Table of Contents

Report: CoilReportMonthly

For: SAC_EXERCISECENTER COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 16076337.56 13127701.22 672.12 19-MAR-16:00 496.02 0.00
April 0.00 0.00 0.338297E+09 0.239876E+09 2415.74 16-APR-15:55 1698.22 0.00
May 0.00 0.00 0.849596E+09 0.591668E+09 2368.49 31-MAY-15:01 1857.45 0.00
June 0.00 0.00 0.231137E+10 0.150824E+10 3648.21 11-JUN-15:01 2214.17 0.00
July 0.00 0.00 0.312901E+10 0.189323E+10 3986.76 26-JUL-18:01 1807.81 0.00
August 0.00 0.00 0.283869E+10 0.174306E+10 4187.21 04-AUG-16:00 2340.29 0.00
September 0.00 0.00 0.127868E+10 0.996185E+09 2728.17 06-SEP-15:01 2118.95 0.00
October 0.00 0.00 91496993.97 76049283.05 1081.49 20-OCT-15:01 1019.74 0.00
November 0.00 0.00 8177471.69 6368901.36 376.14 03-NOV-15:01 340.72 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.108614E+11 0.706781E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.312901E+10 0.189323E+10 4187.21   2340.29 0.00



Table of Contents

Report: CoilReportMonthly

For: SAC_RESTROOM COOLING COIL

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 8464.12 2722.22 18.49 13-JAN-17:10 5.97 0.00
February 0.00 0.00 9376144.74 4263573.90 685.25 24-FEB-17:03 255.64 0.00
March 0.00 0.00 0.115984E+09 89449943.35 413.93 19-MAR-14:40 174.58 0.00
April 0.00 0.00 0.349339E+09 0.295113E+09 1018.26 09-APR-15:01 622.04 0.00
May 0.00 0.00 0.703055E+09 0.632908E+09 495.92 31-MAY-17:00 456.44 0.00
June 0.00 0.00 0.921296E+09 0.846452E+09 553.85 30-JUN-17:00 511.45 0.00
July 0.00 0.00 0.110388E+10 0.102502E+10 584.55 05-JUL-17:00 543.75 0.00
August 0.00 0.00 0.110826E+10 0.102821E+10 587.89 04-AUG-17:00 534.38 0.00
September 0.00 0.00 0.905812E+09 0.838158E+09 606.39 07-SEP-17:00 566.85 0.00
October 0.00 0.00 0.583182E+09 0.520806E+09 458.41 29-OCT-04:02 415.40 0.00
November 0.00 0.00 0.242052E+09 0.206898E+09 966.53 15-NOV-09:01 656.15 0.00
December 0.00 0.00 3190256.42 1171551.47 151.28 03-DEC-16:00 56.06 0.00
                 
Annual Sum or Average 0.00 0.00 0.604543E+10 0.548845E+10       0.00
Minimum of Months 0.00 0.00 8464.12 2722.22 18.49   5.97 0.00
Maximum of Months 0.00 0.00 0.110826E+10 0.102821E+10 1018.26   656.15 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYSSHOWER

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 9586.11 22602.10 29-JAN-08:11
February 0.00 0.00 01-FEB-00:10 9772.77 22780.76 19-FEB-08:17
March 0.00 0.00 01-MAR-00:10 9696.48 22722.26 01-MAR-07:09
April 0.00 0.00 01-APR-00:10 9334.35 22182.96 01-APR-07:17
May 0.00 0.00 01-MAY-00:10 8832.74 21092.93 01-MAY-06:08
June 0.00 0.00 01-JUN-00:10 8295.68 19749.95 01-JUN-06:09
July 0.00 0.00 01-JUL-00:10 7856.65 18572.31 01-JUL-07:18
August 0.00 0.00 01-AUG-00:10 7681.11 17773.54 02-AUG-06:09
September 0.00 0.00 01-SEP-00:10 7762.83 18221.27 30-SEP-07:12
October 0.00 0.00 01-OCT-00:10 8117.72 19274.03 30-OCT-06:09
November 0.00 0.00 01-NOV-00:10 8630.11 20586.99 30-NOV-07:06
December 0.00 0.00 01-DEC-00:10 9162.76 21861.09 31-DEC-08:12
             
Annual Sum or Average 0.00     8721.28    
Minimum of Months 0.00 0.00   7681.11 17773.54  
Maximum of Months 0.00 0.00   9772.77 22780.76  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYSLAUNDRY

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 10087.04 30733.33 31-JAN-08:33
February 0.00 0.00 01-FEB-00:10 10298.09 30944.55 20-FEB-08:26
March 0.00 0.00 01-MAR-00:10 10191.29 30900.24 01-MAR-08:61
April 0.00 0.00 01-APR-00:10 9790.11 30087.16 01-APR-07:01
May 0.00 0.00 01-MAY-00:10 9206.19 28568.12 01-MAY-07:01
June 0.00 0.00 01-JUN-00:10 8592.54 26657.03 01-JUN-07:01
July 0.00 0.00 01-JUL-00:10 8113.95 24970.10 01-JUL-07:01
August 0.00 0.00 01-AUG-00:10 7896.42 23859.92 01-AUG-07:01
September 0.00 0.00 01-SEP-00:10 8002.96 24451.94 30-SEP-07:33
October 0.00 0.00 01-OCT-00:10 8402.43 26011.71 31-OCT-07:33
November 0.00 0.00 01-NOV-00:10 8986.30 27861.13 30-NOV-08:37
December 0.00 0.00 01-DEC-00:10 9599.48 29608.23 31-DEC-08:33
             
Annual Sum or Average 0.00     9090.15    
Minimum of Months 0.00 0.00   7896.42 23859.92  
Maximum of Months 0.00 0.00   10298.09 30944.55  



Table of Contents

Report: FanReportMonthly

For: FRONTSTAIRSFLR1 UNITHEATER FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 1522084.03 0.08 0.57 01-JAN-00:10 0.08
February 1374785.57 0.08 0.57 01-FEB-00:10 0.08
March 1522084.03 0.08 0.57 01-MAR-00:10 0.08
April 1472984.54 0.08 0.57 01-APR-00:10 0.08
May 1522084.03 0.08 0.57 01-MAY-00:10 0.08
June 1472984.54 0.08 0.57 01-JUN-00:10 0.08
July 1522084.03 0.08 0.57 01-JUL-00:10 0.08
August 1522084.03 0.08 0.57 01-AUG-00:10 0.08
September 1472984.54 0.08 0.57 01-SEP-00:10 0.08
October 1522084.03 0.08 0.57 01-OCT-00:10 0.08
November 1472984.54 0.08 0.57 01-NOV-00:10 0.08
December 1522084.03 0.08 0.57 01-DEC-00:10 0.08
           
Annual Sum or Average 17921311.94 0.08      
Minimum of Months 1374785.57 0.08 0.57   0.08
Maximum of Months 1522084.03 0.08 0.57   0.08



Table of Contents

Report: FanReportMonthly

For: FRONTSTAIRSFLR2 UNITHEATER FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 1522084.03 0.08 0.57 01-JAN-00:10 0.08
February 1374785.57 0.08 0.57 01-FEB-00:10 0.08
March 1522084.03 0.08 0.57 01-MAR-00:10 0.08
April 1472984.54 0.08 0.57 01-APR-00:10 0.08
May 1522084.03 0.08 0.57 01-MAY-00:10 0.08
June 1472984.54 0.08 0.57 01-JUN-00:10 0.08
July 1522084.03 0.08 0.57 01-JUL-00:10 0.08
August 1522084.03 0.08 0.57 01-AUG-00:10 0.08
September 1472984.54 0.08 0.57 01-SEP-00:10 0.08
October 1522084.03 0.08 0.57 01-OCT-00:10 0.08
November 1472984.54 0.08 0.57 01-NOV-00:10 0.08
December 1522084.03 0.08 0.57 01-DEC-00:10 0.08
           
Annual Sum or Average 17921311.94 0.08      
Minimum of Months 1374785.57 0.08 0.57   0.08
Maximum of Months 1522084.03 0.08 0.57   0.08



Table of Contents

Report: FanReportMonthly

For: FRONTSTAIRSFLR3 UNITHEATER FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 1522084.03 0.08 0.57 01-JAN-00:10 0.08
February 1374785.57 0.08 0.57 01-FEB-00:10 0.08
March 1522084.03 0.08 0.57 01-MAR-00:10 0.08
April 1472984.54 0.08 0.57 01-APR-00:10 0.08
May 1522084.03 0.08 0.57 01-MAY-00:10 0.08
June 1472984.54 0.08 0.57 01-JUN-00:10 0.08
July 1522084.03 0.08 0.57 01-JUL-00:10 0.08
August 1522084.03 0.08 0.57 01-AUG-00:10 0.08
September 1472984.54 0.08 0.57 01-SEP-00:10 0.08
October 1522084.03 0.08 0.57 01-OCT-00:10 0.08
November 1472984.54 0.08 0.57 01-NOV-00:10 0.08
December 1522084.03 0.08 0.57 01-DEC-00:10 0.08
           
Annual Sum or Average 17921311.94 0.08      
Minimum of Months 1374785.57 0.08 0.57   0.08
Maximum of Months 1522084.03 0.08 0.57   0.08



Table of Contents

Report: FanReportMonthly

For: FRONTSTAIRSFLR4 UNITHEATER FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 3005601.42 0.08 1.12 01-JAN-00:10 0.08
February 2714736.77 0.08 1.12 01-FEB-00:10 0.08
March 3005601.42 0.08 1.12 01-MAR-00:10 0.08
April 2908646.53 0.08 1.12 01-APR-00:10 0.08
May 3005601.42 0.08 1.12 01-MAY-00:10 0.08
June 2908646.53 0.08 1.12 01-JUN-00:10 0.08
July 3005601.42 0.08 1.12 01-JUL-00:10 0.08
August 3005601.42 0.08 1.12 01-AUG-00:10 0.08
September 2908646.53 0.08 1.12 01-SEP-00:10 0.08
October 3005601.42 0.08 1.12 01-OCT-00:10 0.08
November 2908646.53 0.08 1.12 01-NOV-00:10 0.08
December 3005601.42 0.08 1.12 01-DEC-00:10 0.08
           
Annual Sum or Average 35388532.83 0.08      
Minimum of Months 2714736.77 0.08 1.12   0.08
Maximum of Months 3005601.42 0.08 1.12   0.08



Table of Contents

Report: FanReportMonthly

For: REARSTAIRSFLR1 UNITHEATER FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 1522448.57 0.08 0.57 01-JAN-00:10 0.08
February 1375114.84 0.08 0.57 01-FEB-00:10 0.08
March 1522448.57 0.08 0.57 01-MAR-00:10 0.08
April 1473337.32 0.08 0.57 01-APR-00:10 0.08
May 1522448.57 0.08 0.57 01-MAY-00:10 0.08
June 1473337.32 0.08 0.57 01-JUN-00:10 0.08
July 1522448.57 0.08 0.57 01-JUL-00:10 0.08
August 1522448.57 0.08 0.57 01-AUG-00:10 0.08
September 1473337.32 0.08 0.57 01-SEP-00:10 0.08
October 1522448.57 0.08 0.57 01-OCT-00:10 0.08
November 1473337.32 0.08 0.57 01-NOV-00:10 0.08
December 1522448.57 0.08 0.57 01-DEC-00:10 0.08
           
Annual Sum or Average 17925604.11 0.08      
Minimum of Months 1375114.84 0.08 0.57   0.08
Maximum of Months 1522448.57 0.08 0.57   0.08



Table of Contents

Report: FanReportMonthly

For: REARSTAIRSFLR2 UNITHEATER FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 1522448.57 0.08 0.57 01-JAN-00:10 0.08
February 1375114.84 0.08 0.57 01-FEB-00:10 0.08
March 1522448.57 0.08 0.57 01-MAR-00:10 0.08
April 1473337.32 0.08 0.57 01-APR-00:10 0.08
May 1522448.57 0.08 0.57 01-MAY-00:10 0.08
June 1473337.32 0.08 0.57 01-JUN-00:10 0.08
July 1522448.57 0.08 0.57 01-JUL-00:10 0.08
August 1522448.57 0.08 0.57 01-AUG-00:10 0.08
September 1473337.32 0.08 0.57 01-SEP-00:10 0.08
October 1522448.57 0.08 0.57 01-OCT-00:10 0.08
November 1473337.32 0.08 0.57 01-NOV-00:10 0.08
December 1522448.57 0.08 0.57 01-DEC-00:10 0.08
           
Annual Sum or Average 17925604.11 0.08      
Minimum of Months 1375114.84 0.08 0.57   0.08
Maximum of Months 1522448.57 0.08 0.57   0.08



Table of Contents

Report: FanReportMonthly

For: REARSTAIRSFLR3 UNITHEATER FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 1522448.57 0.08 0.57 01-JAN-00:10 0.08
February 1375114.84 0.08 0.57 01-FEB-00:10 0.08
March 1522448.57 0.08 0.57 01-MAR-00:10 0.08
April 1473337.32 0.08 0.57 01-APR-00:10 0.08
May 1522448.57 0.08 0.57 01-MAY-00:10 0.08
June 1473337.32 0.08 0.57 01-JUN-00:10 0.08
July 1522448.57 0.08 0.57 01-JUL-00:10 0.08
August 1522448.57 0.08 0.57 01-AUG-00:10 0.08
September 1473337.32 0.08 0.57 01-SEP-00:10 0.08
October 1522448.57 0.08 0.57 01-OCT-00:10 0.08
November 1473337.32 0.08 0.57 01-NOV-00:10 0.08
December 1522448.57 0.08 0.57 01-DEC-00:10 0.08
           
Annual Sum or Average 17925604.11 0.08      
Minimum of Months 1375114.84 0.08 0.57   0.08
Maximum of Months 1522448.57 0.08 0.57   0.08



Table of Contents

Report: FanReportMonthly

For: REARSTAIRSFLR4 UNITHEATER FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 1522448.57 0.08 0.57 01-JAN-00:10 0.08
February 1375114.84 0.08 0.57 01-FEB-00:10 0.08
March 1522448.57 0.08 0.57 01-MAR-00:10 0.08
April 1473337.32 0.08 0.57 01-APR-00:10 0.08
May 1522448.57 0.08 0.57 01-MAY-00:10 0.08
June 1473337.32 0.08 0.57 01-JUN-00:10 0.08
July 1522448.57 0.08 0.57 01-JUL-00:10 0.08
August 1522448.57 0.08 0.57 01-AUG-00:10 0.08
September 1473337.32 0.08 0.57 01-SEP-00:10 0.08
October 1522448.57 0.08 0.57 01-OCT-00:10 0.08
November 1473337.32 0.08 0.57 01-NOV-00:10 0.08
December 1522448.57 0.08 0.57 01-DEC-00:10 0.08
           
Annual Sum or Average 17925604.11 0.08      
Minimum of Months 1375114.84 0.08 0.57   0.08
Maximum of Months 1522448.57 0.08 0.57   0.08



Table of Contents

Report: FanReportMonthly

For: MECHRM UNITHEATER FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: 101 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 8519883.49 0.02 76.34 01-JAN-15:05 0.55
February 7695378.63 0.02 76.34 01-FEB-15:02 0.55
March 8519883.49 0.02 76.34 01-MAR-15:05 0.55
April 8245048.54 0.02 76.34 01-APR-14:05 0.55
May 8519883.49 0.02 76.34 01-MAY-14:10 0.55
June 8245048.54 0.02 76.34 01-JUN-14:05 0.54
July 8562433.16 0.03 76.34 01-JUL-14:10 0.54
August 8521664.71 0.02 76.34 01-AUG-14:10 0.54
September 8249393.87 0.02 76.34 01-SEP-14:10 0.54
October 8519883.49 0.02 76.34 01-OCT-14:10 0.55
November 8245048.54 0.02 76.34 01-NOV-14:10 0.55
December 8519883.49 0.02 76.34 01-DEC-15:05 0.55
           
Annual Sum or Average 0.100363E+09 0.02      
Minimum of Months 7695378.63 0.02 76.34   0.54
Maximum of Months 8562433.16 0.03 76.34   0.55



Table of Contents

Report: FanReportMonthly

For: 102 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 6911468.50 0.02 61.93 01-JAN-15:05 0.55
February 6242616.71 0.02 61.93 01-FEB-15:02 0.55
March 6911468.50 0.02 61.93 01-MAR-15:05 0.55
April 6688517.90 0.02 61.93 01-APR-14:05 0.55
May 6911468.50 0.02 61.93 01-MAY-14:10 0.55
June 6688517.90 0.02 61.93 01-JUN-14:05 0.54
July 6911468.50 0.02 61.93 01-JUL-14:10 0.54
August 6911468.50 0.02 61.93 01-AUG-14:10 0.54
September 6688517.90 0.02 61.93 01-SEP-14:10 0.54
October 6911468.50 0.02 61.93 01-OCT-14:10 0.55
November 6688517.90 0.02 61.93 01-NOV-14:10 0.55
December 6911468.50 0.02 61.93 01-DEC-15:05 0.55
           
Annual Sum or Average 81376967.76 0.02      
Minimum of Months 6242616.71 0.02 61.93   0.54
Maximum of Months 6911468.50 0.02 61.93   0.55



Table of Contents

Report: FanReportMonthly

For: 103 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.225161E+09 0.44 111.74 01-JAN-00:10 0.54
February 0.203653E+09 0.43 111.74 01-FEB-00:10 0.55
March 0.224473E+09 0.41 111.74 01-MAR-00:10 0.55
April 0.217614E+09 0.42 111.74 01-APR-00:10 0.54
May 0.225453E+09 0.44 111.74 01-MAY-00:10 0.54
June 0.222030E+09 0.49 111.74 01-JUN-00:10 0.54
July 0.232300E+09 0.51 111.74 01-JUL-00:10 0.54
August 0.232089E+09 0.51 111.74 01-AUG-00:10 0.54
September 0.222106E+09 0.50 111.74 01-SEP-00:10 0.54
October 0.224800E+09 0.43 111.74 01-OCT-00:10 0.55
November 0.217278E+09 0.41 111.74 01-NOV-00:10 0.55
December 0.224738E+09 0.42 111.74 01-DEC-00:20 0.54
           
Annual Sum or Average 0.267169E+10 0.45      
Minimum of Months 0.203653E+09 0.41 111.74   0.54
Maximum of Months 0.232300E+09 0.51 111.74   0.55



Table of Contents

Report: FanReportMonthly

For: 104 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.233479E+09 0.41 116.23 01-JAN-00:10 0.54
February 0.210908E+09 0.41 116.23 01-FEB-00:10 0.55
March 0.233481E+09 0.41 116.23 01-MAR-00:10 0.55
April 0.226638E+09 0.43 116.23 01-APR-00:10 0.54
May 0.236208E+09 0.49 116.23 01-MAY-00:10 0.54
June 0.232311E+09 0.51 116.23 01-JUN-00:10 0.54
July 0.242190E+09 0.52 116.23 01-JUL-00:10 0.54
August 0.242299E+09 0.52 116.23 01-AUG-00:10 0.54
September 0.232279E+09 0.52 116.23 01-SEP-00:10 0.54
October 0.234940E+09 0.49 116.23 01-OCT-00:10 0.55
November 0.226293E+09 0.43 116.23 01-NOV-00:10 0.55
December 0.233479E+09 0.41 116.23 01-DEC-00:10 0.54
           
Annual Sum or Average 0.278451E+10 0.46      
Minimum of Months 0.210908E+09 0.41 116.23   0.54
Maximum of Months 0.242299E+09 0.52 116.23   0.55



Table of Contents

Report: FanReportMonthly

For: 105 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.337505E+09 0.47 167.38 01-JAN-00:10 0.55
February 0.306144E+09 0.50 167.38 01-FEB-00:10 0.55
March 0.341106E+09 0.52 167.38 01-MAR-00:10 0.55
April 0.332966E+09 0.53 167.38 01-APR-00:10 0.55
May 0.348346E+09 0.54 167.38 01-MAY-00:10 0.55
June 0.340765E+09 0.53 167.38 01-JUN-00:10 0.54
July 0.353743E+09 0.53 167.38 01-JUL-00:10 0.54
August 0.353576E+09 0.53 167.38 01-AUG-00:10 0.54
September 0.339969E+09 0.54 167.38 01-SEP-00:10 0.54
October 0.346337E+09 0.54 167.38 01-OCT-00:10 0.55
November 0.331130E+09 0.53 167.38 01-NOV-00:10 0.55
December 0.338686E+09 0.50 167.38 01-DEC-00:10 0.55
           
Annual Sum or Average 0.407027E+10 0.52      
Minimum of Months 0.306144E+09 0.47 167.38   0.54
Maximum of Months 0.353743E+09 0.54 167.38   0.55



Table of Contents

Report: FanReportMonthly

For: 201 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 13810015.98 0.19 85.97 01-JAN-15:05 0.55
February 13358585.01 0.12 85.97 01-FEB-15:02 0.55
March 9594533.12 0.02 85.97 01-MAR-15:05 0.55
April 9285032.05 0.02 85.97 01-APR-14:05 0.55
May 9624939.03 0.03 85.97 01-MAY-14:10 0.55
June 10026794.22 0.07 85.97 01-JUN-14:05 0.54
July 10518517.49 0.09 85.97 01-JUL-14:10 0.54
August 9844995.21 0.05 85.97 01-AUG-14:10 0.54
September 9350527.66 0.03 85.97 01-SEP-14:10 0.54
October 9594533.12 0.02 85.97 01-OCT-14:10 0.55
November 9522879.82 0.04 85.97 01-NOV-14:10 0.55
December 11379283.37 0.10 85.97 01-DEC-15:05 0.55
           
Annual Sum or Average 0.125911E+09 0.06      
Minimum of Months 9285032.05 0.02 85.97   0.54
Maximum of Months 13810015.98 0.19 85.97   0.55



Table of Contents

Report: FanReportMonthly

For: 202_205 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.890955E+09 0.41 443.52 01-JAN-00:20 0.54
February 0.805131E+09 0.41 443.52 01-FEB-00:10 0.55
March 0.891634E+09 0.42 443.52 01-MAR-00:10 0.55
April 0.871080E+09 0.46 443.52 01-APR-00:10 0.54
May 0.913904E+09 0.52 443.52 01-MAY-00:20 0.54
June 0.900775E+09 0.52 443.52 01-JUN-00:10 0.54
July 0.939517E+09 0.52 443.52 01-JUL-00:10 0.54
August 0.934082E+09 0.52 443.52 01-AUG-00:10 0.54
September 0.889577E+09 0.51 443.52 01-SEP-00:10 0.54
October 0.896454E+09 0.47 443.52 01-OCT-00:10 0.55
November 0.863663E+09 0.43 443.52 01-NOV-00:10 0.55
December 0.890947E+09 0.41 443.52 01-DEC-00:10 0.54
           
Annual Sum or Average 0.106877E+11 0.47      
Minimum of Months 0.805131E+09 0.41 443.52   0.54
Maximum of Months 0.939517E+09 0.52 443.52   0.55



Table of Contents

Report: FanReportMonthly

For: 206_208 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.736476E+09 0.41 366.63 01-JAN-00:10 0.54
February 0.665235E+09 0.41 366.63 01-FEB-00:10 0.55
March 0.737504E+09 0.43 366.63 01-MAR-00:10 0.55
April 0.720752E+09 0.47 366.63 01-APR-00:10 0.54
May 0.755248E+09 0.52 366.63 01-MAY-00:10 0.54
June 0.742946E+09 0.52 366.63 01-JUN-00:10 0.54
July 0.774448E+09 0.52 366.63 01-JUL-00:10 0.54
August 0.770141E+09 0.52 366.63 01-AUG-00:10 0.54
September 0.734359E+09 0.52 366.63 01-SEP-00:10 0.54
October 0.741583E+09 0.47 366.63 01-OCT-00:10 0.55
November 0.714047E+09 0.43 366.63 01-NOV-00:10 0.55
December 0.736476E+09 0.41 366.63 01-DEC-00:10 0.54
           
Annual Sum or Average 0.882922E+10 0.47      
Minimum of Months 0.665235E+09 0.41 366.63   0.54
Maximum of Months 0.774448E+09 0.52 366.63   0.55



Table of Contents

Report: FanReportMonthly

For: 209_212 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.822337E+09 0.41 409.37 01-JAN-00:10 0.54
February 0.742814E+09 0.41 409.37 01-FEB-00:10 0.55
March 0.823457E+09 0.43 409.37 01-MAR-00:10 0.55
April 0.803587E+09 0.46 409.37 01-APR-00:10 0.54
May 0.840861E+09 0.51 409.37 01-MAY-00:10 0.54
June 0.826543E+09 0.52 409.37 01-JUN-00:20 0.54
July 0.862258E+09 0.52 409.37 01-JUL-00:10 0.54
August 0.858013E+09 0.52 409.37 01-AUG-00:10 0.54
September 0.819219E+09 0.52 409.37 01-SEP-00:10 0.54
October 0.828821E+09 0.48 409.37 01-OCT-00:10 0.55
November 0.797631E+09 0.43 409.37 01-NOV-00:10 0.55
December 0.822337E+09 0.41 409.37 01-DEC-00:10 0.54
           
Annual Sum or Average 0.984788E+10 0.47      
Minimum of Months 0.742814E+09 0.41 409.37   0.54
Maximum of Months 0.862258E+09 0.52 409.37   0.55



Table of Contents

Report: FanReportMonthly

For: 213 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.228233E+09 0.46 112.52 01-JAN-00:10 0.54
February 0.205542E+09 0.43 112.52 01-FEB-00:10 0.55
March 0.226038E+09 0.41 112.52 01-MAR-00:10 0.55
April 0.219676E+09 0.43 112.52 01-APR-00:10 0.54
May 0.228516E+09 0.48 112.52 01-MAY-00:10 0.54
June 0.225395E+09 0.50 112.52 01-JUN-00:10 0.54
July 0.235524E+09 0.52 112.52 01-JUL-00:10 0.54
August 0.234287E+09 0.52 112.52 01-AUG-00:10 0.54
September 0.223501E+09 0.49 112.52 01-SEP-00:10 0.54
October 0.226228E+09 0.42 112.52 01-OCT-00:10 0.55
November 0.218914E+09 0.42 112.52 01-NOV-00:10 0.55
December 0.227059E+09 0.43 112.52 01-DEC-00:10 0.54
           
Annual Sum or Average 0.269891E+10 0.46      
Minimum of Months 0.205542E+09 0.41 112.52   0.54
Maximum of Months 0.235524E+09 0.52 112.52   0.55



Table of Contents

Report: FanReportMonthly

For: 214 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.253371E+09 0.41 126.13 01-JAN-00:10 0.54
February 0.228867E+09 0.41 126.13 01-FEB-00:10 0.55
March 0.254011E+09 0.44 126.13 01-MAR-00:10 0.55
April 0.248337E+09 0.48 126.13 01-APR-00:10 0.55
May 0.261301E+09 0.53 126.13 01-MAY-00:10 0.54
June 0.257134E+09 0.53 126.13 01-JUN-00:10 0.54
July 0.267410E+09 0.53 126.13 01-JUL-00:10 0.54
August 0.266625E+09 0.53 126.13 01-AUG-00:10 0.54
September 0.254801E+09 0.53 126.13 01-SEP-00:10 0.54
October 0.256771E+09 0.52 126.13 01-OCT-00:10 0.55
November 0.246173E+09 0.44 126.13 01-NOV-00:10 0.55
December 0.253371E+09 0.41 126.13 01-DEC-00:10 0.54
           
Annual Sum or Average 0.304817E+10 0.48      
Minimum of Months 0.228867E+09 0.41 126.13   0.54
Maximum of Months 0.267410E+09 0.53 126.13   0.55



Table of Contents

Report: FanReportMonthly

For: 215_218 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.256964E+09 0.55 1240.61 01-JAN-15:05 0.55
February 0.297617E+09 0.59 1240.61 01-FEB-15:02 0.55
March 0.304136E+09 0.63 1240.61 01-MAR-15:05 0.55
April 0.337610E+09 0.63 1240.61 01-APR-14:05 0.55
May 0.404123E+09 0.63 1240.61 01-MAY-14:30 0.55
June 0.426046E+09 0.63 1240.61 01-JUN-14:05 0.54
July 0.458880E+09 0.63 1240.61 01-JUL-14:10 0.54
August 0.449738E+09 0.63 1240.61 01-AUG-14:10 0.54
September 0.400060E+09 0.63 1240.61 01-SEP-14:10 0.54
October 0.351670E+09 0.63 1240.61 01-OCT-14:10 0.55
November 0.288439E+09 0.62 1240.61 01-NOV-14:10 0.55
December 0.250592E+09 0.60 1240.61 01-DEC-15:05 0.55
           
Annual Sum or Average 0.422587E+10 0.62      
Minimum of Months 0.250592E+09 0.55 1240.61   0.54
Maximum of Months 0.458880E+09 0.63 1240.61   0.55



Table of Contents

Report: FanReportMonthly

For: 219 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.140020E+10 0.56 660.68 01-JAN-00:20 0.55
February 0.129028E+10 0.56 660.68 01-FEB-00:10 0.55
March 0.138877E+10 0.56 660.68 01-MAR-00:10 0.55
April 0.134974E+10 0.56 660.68 01-APR-00:10 0.55
May 0.140106E+10 0.56 660.68 01-MAY-00:10 0.55
June 0.136176E+10 0.56 660.68 01-JUN-00:10 0.55
July 0.140815E+10 0.55 660.68 01-JUL-00:10 0.54
August 0.140681E+10 0.55 660.68 01-AUG-00:10 0.54
September 0.135880E+10 0.56 660.68 01-SEP-00:10 0.54
October 0.139627E+10 0.56 660.68 01-OCT-00:10 0.55
November 0.134438E+10 0.56 660.68 01-NOV-00:10 0.55
December 0.138177E+10 0.56 660.68 01-DEC-00:10 0.55
           
Annual Sum or Average 0.164880E+11 0.56      
Minimum of Months 0.129028E+10 0.55 660.68   0.54
Maximum of Months 0.140815E+10 0.56 660.68   0.55



Table of Contents

Report: FanReportMonthly

For: 220_223 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.844334E+09 0.41 420.32 01-JAN-00:10 0.54
February 0.762695E+09 0.41 420.32 01-FEB-00:10 0.55
March 0.846333E+09 0.44 420.32 01-MAR-00:10 0.55
April 0.826421E+09 0.48 420.32 01-APR-00:10 0.54
May 0.867695E+09 0.52 420.32 01-MAY-00:10 0.54
June 0.850532E+09 0.53 420.32 01-JUN-00:30 0.54
July 0.882807E+09 0.52 420.32 01-JUL-00:10 0.54
August 0.879985E+09 0.52 420.32 01-AUG-00:10 0.54
September 0.842649E+09 0.53 420.32 01-SEP-00:10 0.54
October 0.853109E+09 0.51 420.32 01-OCT-00:10 0.55
November 0.819508E+09 0.44 420.32 01-NOV-00:10 0.55
December 0.844360E+09 0.41 420.32 01-DEC-00:10 0.54
           
Annual Sum or Average 0.101204E+11 0.48      
Minimum of Months 0.762695E+09 0.41 420.32   0.54
Maximum of Months 0.882807E+09 0.53 420.32   0.55



Table of Contents

Report: FanReportMonthly

For: 224 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.241392E+09 0.42 120.12 01-JAN-00:10 0.54
February 0.218335E+09 0.42 120.12 01-FEB-00:10 0.55
March 0.241322E+09 0.41 120.12 01-MAR-00:10 0.55
April 0.234981E+09 0.44 120.12 01-APR-00:10 0.54
May 0.246614E+09 0.52 120.12 01-MAY-00:10 0.54
June 0.242900E+09 0.52 120.12 01-JUN-00:10 0.54
July 0.252550E+09 0.52 120.12 01-JUL-00:10 0.54
August 0.251541E+09 0.52 120.12 01-AUG-00:10 0.54
September 0.240142E+09 0.52 120.12 01-SEP-00:10 0.54
October 0.242026E+09 0.45 120.12 01-OCT-00:10 0.55
November 0.233654E+09 0.42 120.12 01-NOV-00:10 0.55
December 0.241393E+09 0.41 120.12 01-DEC-00:10 0.54
           
Annual Sum or Average 0.288685E+10 0.47      
Minimum of Months 0.218335E+09 0.41 120.12   0.54
Maximum of Months 0.252550E+09 0.52 120.12   0.55



Table of Contents

Report: FanReportMonthly

For: 301 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 24192009.88 0.41 62.76 01-JAN-15:05 0.55
February 15897958.98 0.24 62.76 01-FEB-15:02 0.55
March 7487914.57 0.07 62.76 01-MAR-15:05 0.55
April 6777860.12 0.02 62.76 01-APR-14:05 0.55
May 7029309.20 0.03 62.76 01-MAY-14:10 0.55
June 7479785.28 0.06 62.76 01-JUN-14:05 0.54
July 7714077.15 0.07 62.76 01-JUL-14:10 0.54
August 7141140.45 0.03 62.76 01-AUG-14:10 0.54
September 6795387.64 0.03 62.76 01-SEP-14:10 0.54
October 7003788.79 0.02 62.76 01-OCT-14:10 0.55
November 9829597.95 0.12 62.76 01-NOV-14:10 0.55
December 14947963.87 0.33 62.76 01-DEC-15:05 0.55
           
Annual Sum or Average 0.122297E+09 0.12      
Minimum of Months 6777860.12 0.02 62.76   0.54
Maximum of Months 24192009.88 0.41 62.76   0.55



Table of Contents

Report: FanReportMonthly

For: 302_305 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 24441891.94 0.08 202.45 01-JAN-15:05 0.55
February 25250470.13 0.08 202.45 01-FEB-15:02 0.55
March 22593433.53 0.02 202.45 01-MAR-15:05 0.55
April 21885773.88 0.02 202.45 01-APR-14:05 0.55
May 22742344.94 0.03 202.45 01-MAY-14:10 0.55
June 24212544.57 0.08 202.45 01-JUN-14:05 0.54
July 26045194.91 0.10 202.45 01-JUL-14:10 0.54
August 23505978.27 0.05 202.45 01-AUG-14:10 0.54
September 22070613.60 0.03 202.45 01-SEP-14:10 0.54
October 22593433.53 0.02 202.45 01-OCT-14:10 0.55
November 21866351.54 0.02 202.45 01-NOV-14:10 0.55
December 23574334.05 0.07 202.45 01-DEC-15:05 0.55
           
Annual Sum or Average 0.280782E+09 0.05      
Minimum of Months 21866351.54 0.02 202.45   0.54
Maximum of Months 26045194.91 0.10 202.45   0.55



Table of Contents

Report: FanReportMonthly

For: 306_308 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 20590270.10 0.03 184.14 01-JAN-15:05 0.55
February 19863505.82 0.05 184.14 01-FEB-15:02 0.55
March 20550002.87 0.02 184.14 01-MAR-15:05 0.55
April 19929154.41 0.02 184.14 01-APR-14:05 0.55
May 20715360.71 0.03 184.14 01-MAY-14:10 0.55
June 22074744.14 0.08 184.14 01-JUN-14:05 0.54
July 23759490.72 0.10 184.14 01-JUL-14:10 0.54
August 21525966.17 0.05 184.14 01-AUG-14:10 0.54
September 20126259.32 0.03 184.14 01-SEP-14:10 0.54
October 20550002.87 0.02 184.14 01-OCT-14:10 0.55
November 19887099.55 0.02 184.14 01-NOV-14:10 0.55
December 20550002.87 0.02 184.14 01-DEC-15:05 0.55
           
Annual Sum or Average 0.250122E+09 0.04      
Minimum of Months 19863505.82 0.02 184.14   0.54
Maximum of Months 23759490.72 0.10 184.14   0.55



Table of Contents

Report: FanReportMonthly

For: 309_312 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.783836E+09 0.41 390.20 01-JAN-00:10 0.54
February 0.708155E+09 0.41 390.20 01-FEB-00:10 0.55
March 0.784205E+09 0.41 390.20 01-MAR-00:10 0.55
April 0.764488E+09 0.45 390.20 01-APR-00:10 0.54
May 0.798838E+09 0.50 390.20 01-MAY-00:10 0.54
June 0.785922E+09 0.51 390.20 01-JUN-00:10 0.54
July 0.819956E+09 0.52 390.20 01-JUL-00:10 0.54
August 0.814609E+09 0.52 390.20 01-AUG-00:10 0.54
September 0.776219E+09 0.49 390.20 01-SEP-00:10 0.54
October 0.785998E+09 0.43 390.20 01-OCT-00:10 0.55
November 0.758888E+09 0.41 390.20 01-NOV-00:10 0.55
December 0.783843E+09 0.41 390.20 01-DEC-00:10 0.54
           
Annual Sum or Average 0.936496E+10 0.46      
Minimum of Months 0.708155E+09 0.41 390.20   0.54
Maximum of Months 0.819956E+09 0.52 390.20   0.55



Table of Contents

Report: FanReportMonthly

For: 313 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 11449920.05 0.22 69.28 01-JAN-15:05 0.55
February 10224608.63 0.12 69.28 01-FEB-15:02 0.55
March 7731140.04 0.02 69.28 01-MAR-15:05 0.55
April 7481748.42 0.02 69.28 01-APR-14:05 0.55
May 7731140.04 0.02 69.28 01-MAY-14:10 0.55
June 7523843.74 0.03 69.28 01-JUN-14:05 0.54
July 7803219.09 0.03 69.28 01-JUL-14:10 0.54
August 7731140.04 0.02 69.28 01-AUG-14:10 0.54
September 7481748.42 0.02 69.28 01-SEP-14:10 0.54
October 7731140.04 0.02 69.28 01-OCT-14:10 0.55
November 7721862.37 0.05 69.28 01-NOV-14:10 0.55
December 9937993.26 0.11 69.28 01-DEC-15:05 0.55
           
Annual Sum or Average 0.100550E+09 0.06      
Minimum of Months 7481748.42 0.02 69.28   0.54
Maximum of Months 11449920.05 0.22 69.28   0.55



Table of Contents

Report: FanReportMonthly

For: 314 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.220136E+09 0.44 109.02 01-JAN-00:10 0.54
February 0.198601E+09 0.43 109.02 01-FEB-00:10 0.55
March 0.219042E+09 0.41 109.02 01-MAR-00:10 0.55
April 0.213572E+09 0.44 109.02 01-APR-00:10 0.54
May 0.224126E+09 0.51 109.02 01-MAY-00:10 0.54
June 0.221799E+09 0.52 109.02 01-JUN-00:10 0.54
July 0.231014E+09 0.53 109.02 01-JUL-00:10 0.54
August 0.229655E+09 0.52 109.02 01-AUG-00:10 0.54
September 0.218260E+09 0.50 109.02 01-SEP-00:10 0.54
October 0.219394E+09 0.43 109.02 01-OCT-00:10 0.55
November 0.212037E+09 0.42 109.02 01-NOV-00:10 0.55
December 0.219691E+09 0.42 109.02 01-DEC-00:10 0.54
           
Annual Sum or Average 0.262733E+10 0.46      
Minimum of Months 0.198601E+09 0.41 109.02   0.54
Maximum of Months 0.231014E+09 0.53 109.02   0.55



Table of Contents

Report: FanReportMonthly

For: 315_318 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.964255E+09 0.42 479.77 01-JAN-00:10 0.54
February 0.873349E+09 0.45 479.77 01-FEB-00:10 0.55
March 0.975333E+09 0.50 479.77 01-MAR-00:20 0.55
April 0.956825E+09 0.52 479.77 01-APR-00:10 0.55
May 0.100641E+10 0.54 479.77 01-MAY-00:10 0.54
June 0.986742E+09 0.53 479.77 01-JUN-00:10 0.54
July 0.102391E+10 0.53 479.77 01-JUL-00:10 0.54
August 0.101993E+10 0.53 479.77 01-AUG-00:10 0.54
September 0.975188E+09 0.54 479.77 01-SEP-00:10 0.54
October 0.986246E+09 0.53 479.77 01-OCT-00:10 0.55
November 0.941090E+09 0.48 479.77 01-NOV-00:10 0.55
December 0.964668E+09 0.42 479.77 01-DEC-00:10 0.54
           
Annual Sum or Average 0.116739E+11 0.50      
Minimum of Months 0.873349E+09 0.42 479.77   0.54
Maximum of Months 0.102391E+10 0.54 479.77   0.55



Table of Contents

Report: FanReportMonthly

For: 319 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 12643149.20 0.02 113.29 01-JAN-15:05 0.55
February 11419618.63 0.02 113.29 01-FEB-15:02 0.55
March 12643149.20 0.02 113.29 01-MAR-15:05 0.55
April 12256083.81 0.03 113.29 01-APR-14:05 0.55
May 12951884.30 0.05 113.29 01-MAY-14:10 0.55
June 13956766.66 0.21 113.29 01-JUN-14:05 0.54
July 14840742.22 0.27 113.29 01-JUL-14:10 0.54
August 13580099.30 0.15 113.29 01-AUG-14:10 0.54
September 12409979.25 0.06 113.29 01-SEP-14:10 0.54
October 12643149.20 0.02 113.29 01-OCT-14:10 0.55
November 12235305.67 0.02 113.29 01-NOV-14:10 0.55
December 12643149.20 0.02 113.29 01-DEC-15:05 0.55
           
Annual Sum or Average 0.154223E+09 0.08      
Minimum of Months 11419618.63 0.02 113.29   0.54
Maximum of Months 14840742.22 0.27 113.29   0.55



Table of Contents

Report: FanReportMonthly

For: 320_323 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.755004E+09 0.41 375.85 01-JAN-00:10 0.54
February 0.681948E+09 0.41 375.85 01-FEB-00:10 0.55
March 0.755739E+09 0.42 375.85 01-MAR-00:10 0.55
April 0.737411E+09 0.46 375.85 01-APR-00:10 0.54
May 0.773442E+09 0.52 375.85 01-MAY-00:10 0.54
June 0.759723E+09 0.52 375.85 01-JUN-00:10 0.54
July 0.789234E+09 0.52 375.85 01-JUL-00:10 0.54
August 0.785422E+09 0.52 375.85 01-AUG-00:10 0.54
September 0.749713E+09 0.51 375.85 01-SEP-00:10 0.54
October 0.757922E+09 0.45 375.85 01-OCT-00:10 0.55
November 0.731096E+09 0.42 375.85 01-NOV-00:10 0.55
December 0.755004E+09 0.41 375.85 01-DEC-00:20 0.54
           
Annual Sum or Average 0.903166E+10 0.46      
Minimum of Months 0.681948E+09 0.41 375.85   0.54
Maximum of Months 0.789234E+09 0.52 375.85   0.55



Table of Contents

Report: FanReportMonthly

For: 324 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 7344879.32 0.02 65.81 01-JAN-15:05 0.55
February 6634084.55 0.02 65.81 01-FEB-15:02 0.55
March 7344879.32 0.02 65.81 01-MAR-15:05 0.55
April 7107947.73 0.02 65.81 01-APR-14:05 0.55
May 7344879.32 0.02 65.81 01-MAY-14:10 0.55
June 7107947.73 0.02 65.81 01-JUN-14:05 0.54
July 7344879.32 0.02 65.81 01-JUL-14:10 0.54
August 7344879.32 0.02 65.81 01-AUG-14:10 0.54
September 7107947.73 0.02 65.81 01-SEP-14:10 0.54
October 7344879.32 0.02 65.81 01-OCT-14:10 0.55
November 7107947.73 0.02 65.81 01-NOV-14:10 0.55
December 7344879.32 0.02 65.81 01-DEC-15:05 0.55
           
Annual Sum or Average 86480030.70 0.02      
Minimum of Months 6634084.55 0.02 65.81   0.54
Maximum of Months 7344879.32 0.02 65.81   0.55



Table of Contents

Report: FanReportMonthly

For: 401 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.291364E+09 0.53 133.80 01-JAN-00:10 0.54
February 0.255580E+09 0.51 133.80 01-FEB-00:10 0.55
March 0.272542E+09 0.46 133.80 01-MAR-00:10 0.55
April 0.263150E+09 0.45 133.80 01-APR-00:10 0.54
May 0.274800E+09 0.49 133.80 01-MAY-00:10 0.54
June 0.273582E+09 0.51 133.80 01-JUN-00:10 0.54
July 0.285428E+09 0.52 133.80 01-JUL-00:10 0.54
August 0.283147E+09 0.52 133.80 01-AUG-00:10 0.54
September 0.267506E+09 0.48 133.80 01-SEP-00:10 0.54
October 0.269102E+09 0.42 133.80 01-OCT-00:10 0.55
November 0.266478E+09 0.48 133.80 01-NOV-00:10 0.54
December 0.285215E+09 0.53 133.80 01-DEC-00:10 0.54
           
Annual Sum or Average 0.328789E+10 0.49      
Minimum of Months 0.255580E+09 0.42 133.80   0.54
Maximum of Months 0.291364E+09 0.53 133.80   0.55



Table of Contents

Report: FanReportMonthly

For: 402_405 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.125877E+09 0.47 273.20 01-JAN-15:05 0.55
February 80260366.34 0.27 273.20 01-FEB-15:05 0.55
March 37340414.81 0.13 273.20 01-MAR-15:05 0.55
April 31633685.24 0.05 273.20 01-APR-14:05 0.55
May 34287748.07 0.07 273.20 01-MAY-14:10 0.55
June 46901119.23 0.16 273.20 01-JUN-14:05 0.54
July 52072839.03 0.18 273.20 01-JUL-14:10 0.54
August 44225467.01 0.15 273.20 01-AUG-14:10 0.54
September 35523863.60 0.08 273.20 01-SEP-14:10 0.54
October 30488618.39 0.02 273.20 01-OCT-14:10 0.55
November 49781198.82 0.17 273.20 01-NOV-14:10 0.55
December 85928605.99 0.43 273.20 01-DEC-15:05 0.55
           
Annual Sum or Average 0.654321E+09 0.18      
Minimum of Months 30488618.39 0.02 273.20   0.54
Maximum of Months 0.125877E+09 0.47 273.20   0.55



Table of Contents

Report: FanReportMonthly

For: 406_408 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.100402E+09 0.42 245.44 01-JAN-15:05 0.55
February 65350366.12 0.24 245.44 01-FEB-15:02 0.55
March 30659467.20 0.09 245.44 01-MAR-15:05 0.55
April 28509401.12 0.05 245.44 01-APR-14:05 0.55
May 31523523.01 0.08 245.44 01-MAY-14:10 0.55
June 42347723.39 0.16 245.44 01-JUN-14:05 0.54
July 46992760.33 0.18 245.44 01-JUL-14:10 0.54
August 40256746.89 0.15 245.44 01-AUG-14:10 0.54
September 32353387.85 0.09 245.44 01-SEP-14:10 0.54
October 27391360.64 0.02 245.44 01-OCT-14:10 0.55
November 40994546.64 0.14 245.44 01-NOV-14:10 0.55
December 66415849.74 0.37 245.44 01-DEC-15:05 0.55
           
Annual Sum or Average 0.553198E+09 0.17      
Minimum of Months 27391360.64 0.02 245.44   0.54
Maximum of Months 0.100402E+09 0.42 245.44   0.55



Table of Contents

Report: FanReportMonthly

For: 409_412 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.983981E+09 0.45 484.71 01-JAN-00:10 0.54
February 0.884860E+09 0.43 484.71 01-FEB-00:10 0.55
March 0.975273E+09 0.42 484.71 01-MAR-00:10 0.55
April 0.954629E+09 0.46 484.71 01-APR-00:10 0.54
May 0.100010E+10 0.51 484.71 01-MAY-00:10 0.54
June 0.985871E+09 0.51 484.71 01-JUN-00:10 0.54
July 0.102753E+10 0.52 484.71 01-JUL-00:10 0.54
August 0.102047E+10 0.52 484.71 01-AUG-00:10 0.54
September 0.969873E+09 0.50 484.71 01-SEP-00:10 0.54
October 0.978401E+09 0.45 484.71 01-OCT-00:10 0.55
November 0.944070E+09 0.42 484.71 01-NOV-00:10 0.54
December 0.979895E+09 0.44 484.71 01-DEC-00:10 0.54
           
Annual Sum or Average 0.117050E+11 0.47      
Minimum of Months 0.884860E+09 0.42 484.71   0.54
Maximum of Months 0.102753E+10 0.52 484.71   0.55



Table of Contents

Report: FanReportMonthly

For: 413 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 45803229.16 0.48 97.20 01-JAN-15:05 0.55
February 28663108.29 0.29 97.20 01-FEB-15:02 0.55
March 14244279.43 0.16 97.20 01-MAR-15:05 0.55
April 10964875.49 0.05 97.20 01-APR-14:05 0.55
May 11379454.42 0.05 97.20 01-MAY-14:10 0.55
June 13702373.18 0.13 97.20 01-JUN-14:05 0.54
July 15002332.69 0.15 97.20 01-JUL-14:10 0.54
August 13386625.20 0.12 97.20 01-AUG-14:10 0.54
September 11836075.64 0.07 97.20 01-SEP-14:10 0.54
October 10847828.11 0.02 97.20 01-OCT-14:10 0.55
November 18407048.63 0.19 97.20 01-NOV-14:10 0.55
December 31617611.69 0.43 97.20 01-DEC-15:05 0.55
           
Annual Sum or Average 0.225855E+09 0.18      
Minimum of Months 10847828.11 0.02 97.20   0.54
Maximum of Months 45803229.16 0.48 97.20   0.55



Table of Contents

Report: FanReportMonthly

For: 414 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 23315199.43 0.30 84.81 01-JAN-15:05 0.55
February 16338371.30 0.15 84.81 01-FEB-15:02 0.55
March 9761607.90 0.04 84.81 01-MAR-15:05 0.55
April 9235754.69 0.03 84.81 01-APR-14:05 0.55
May 9816077.65 0.04 84.81 01-MAY-14:10 0.55
June 11603067.16 0.14 84.81 01-JUN-14:05 0.54
July 12114670.77 0.16 84.81 01-JUL-14:10 0.54
August 10950713.07 0.12 84.81 01-AUG-14:10 0.54
September 9842526.84 0.07 84.81 01-SEP-14:10 0.54
October 9465150.73 0.02 84.81 01-OCT-14:10 0.55
November 11340478.89 0.08 84.81 01-NOV-14:10 0.55
December 15418762.56 0.17 84.81 01-DEC-15:05 0.55
           
Annual Sum or Average 0.149202E+09 0.11      
Minimum of Months 9235754.69 0.02 84.81   0.54
Maximum of Months 23315199.43 0.30 84.81   0.55



Table of Contents

Report: FanReportMonthly

For: 415_418 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.964957E+09 0.43 479.20 01-JAN-00:10 0.54
February 0.871446E+09 0.42 479.20 01-FEB-00:10 0.55
March 0.966300E+09 0.44 479.20 01-MAR-00:10 0.55
April 0.948164E+09 0.48 479.20 01-APR-00:20 0.54
May 0.998409E+09 0.53 479.20 01-MAY-00:10 0.54
June 0.982750E+09 0.53 479.20 01-JUN-00:10 0.54
July 0.102061E+10 0.53 479.20 01-JUL-00:10 0.54
August 0.101493E+10 0.53 479.20 01-AUG-00:10 0.54
September 0.965697E+09 0.52 479.20 01-SEP-00:10 0.54
October 0.971418E+09 0.49 479.20 01-OCT-00:10 0.55
November 0.933338E+09 0.43 479.20 01-NOV-00:10 0.54
December 0.964564E+09 0.42 479.20 01-DEC-00:20 0.54
           
Annual Sum or Average 0.116026E+11 0.48      
Minimum of Months 0.871446E+09 0.42 479.20   0.54
Maximum of Months 0.102061E+10 0.53 479.20   0.55



Table of Contents

Report: FanReportMonthly

For: 419 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.261764E+09 0.43 129.95 01-JAN-00:10 0.54
February 0.236174E+09 0.42 129.95 01-FEB-00:20 0.55
March 0.261723E+09 0.44 129.95 01-MAR-00:10 0.55
April 0.256681E+09 0.47 129.95 01-APR-00:10 0.54
May 0.270778E+09 0.53 129.95 01-MAY-00:10 0.54
June 0.267049E+09 0.53 129.95 01-JUN-00:10 0.54
July 0.277542E+09 0.53 129.95 01-JUL-00:10 0.54
August 0.275935E+09 0.53 129.95 01-AUG-00:10 0.54
September 0.262076E+09 0.52 129.95 01-SEP-00:20 0.54
October 0.262817E+09 0.48 129.95 01-OCT-00:10 0.55
November 0.252953E+09 0.43 129.95 01-NOV-00:10 0.54
December 0.261659E+09 0.42 129.95 01-DEC-00:10 0.54
           
Annual Sum or Average 0.314715E+10 0.48      
Minimum of Months 0.236174E+09 0.42 129.95   0.54
Maximum of Months 0.277542E+09 0.53 129.95   0.55



Table of Contents

Report: FanReportMonthly

For: 420_423 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.893169E+09 0.43 443.74 01-JAN-00:10 0.54
February 0.806458E+09 0.42 443.74 01-FEB-00:10 0.55
March 0.893602E+09 0.43 443.74 01-MAR-00:10 0.55
April 0.875270E+09 0.47 443.74 01-APR-00:10 0.54
May 0.920136E+09 0.52 443.74 01-MAY-00:10 0.54
June 0.905132E+09 0.52 443.74 01-JUN-00:10 0.54
July 0.939950E+09 0.53 443.74 01-JUL-00:20 0.54
August 0.934789E+09 0.52 443.74 01-AUG-00:10 0.54
September 0.889980E+09 0.51 443.74 01-SEP-00:10 0.54
October 0.896992E+09 0.47 443.74 01-OCT-00:10 0.55
November 0.863561E+09 0.43 443.74 01-NOV-00:10 0.54
December 0.892934E+09 0.42 443.74 01-DEC-00:10 0.54
           
Annual Sum or Average 0.107120E+11 0.47      
Minimum of Months 0.806458E+09 0.42 443.74   0.54
Maximum of Months 0.939950E+09 0.53 443.74   0.55



Table of Contents

Report: FanReportMonthly

For: 424 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.262512E+09 0.49 126.98 01-JAN-00:10 0.54
February 0.234104E+09 0.45 126.98 01-FEB-00:10 0.55
March 0.255346E+09 0.42 126.98 01-MAR-00:10 0.55
April 0.249160E+09 0.45 126.98 01-APR-00:10 0.54
May 0.261758E+09 0.51 126.98 01-MAY-00:10 0.54
June 0.259225E+09 0.52 126.98 01-JUN-00:10 0.54
July 0.269522E+09 0.53 126.98 01-JUL-00:10 0.54
August 0.267608E+09 0.52 126.98 01-AUG-00:10 0.54
September 0.253996E+09 0.50 126.98 01-SEP-00:10 0.54
October 0.255525E+09 0.43 126.98 01-OCT-00:10 0.54
November 0.248211E+09 0.43 126.98 01-NOV-00:10 0.54
December 0.259560E+09 0.47 126.98 01-DEC-00:10 0.54
           
Annual Sum or Average 0.307653E+10 0.48      
Minimum of Months 0.234104E+09 0.42 126.98   0.54
Maximum of Months 0.269522E+09 0.53 126.98   0.55



Table of Contents

Report: FanReportMonthly

For: CORRIDORFLR1 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.371835E+10 0.55 1388.27 01-JAN-00:10 0.55
February 0.335851E+10 0.55 1388.27 01-FEB-00:10 0.55
March 0.371835E+10 0.55 1388.27 01-MAR-00:10 0.55
April 0.359841E+10 0.55 1388.27 01-APR-00:10 0.55
May 0.371835E+10 0.54 1388.27 01-MAY-00:10 0.55
June 0.359841E+10 0.54 1388.27 01-JUN-00:10 0.54
July 0.371835E+10 0.54 1388.27 01-JUL-00:10 0.54
August 0.371835E+10 0.54 1388.27 01-AUG-00:10 0.54
September 0.359841E+10 0.55 1388.27 01-SEP-00:10 0.54
October 0.371835E+10 0.55 1388.27 01-OCT-00:10 0.55
November 0.359841E+10 0.55 1388.27 01-NOV-00:10 0.55
December 0.371835E+10 0.55 1388.27 01-DEC-00:10 0.55
           
Annual Sum or Average 0.437806E+11 0.55      
Minimum of Months 0.335851E+10 0.54 1388.27   0.54
Maximum of Months 0.371835E+10 0.55 1388.27   0.55



Table of Contents

Report: FanReportMonthly

For: CORRIDORFLR2 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.446696E+09 0.55 166.78 01-JAN-00:10 0.55
February 0.403467E+09 0.55 166.78 01-FEB-00:10 0.55
March 0.446696E+09 0.55 166.78 01-MAR-00:10 0.55
April 0.432286E+09 0.55 166.78 01-APR-00:10 0.55
May 0.446696E+09 0.54 166.78 01-MAY-00:10 0.55
June 0.432286E+09 0.54 166.78 01-JUN-00:10 0.54
July 0.446696E+09 0.54 166.78 01-JUL-00:10 0.54
August 0.446696E+09 0.54 166.78 01-AUG-00:10 0.54
September 0.432286E+09 0.55 166.78 01-SEP-00:10 0.54
October 0.446696E+09 0.55 166.78 01-OCT-00:10 0.55
November 0.432286E+09 0.55 166.78 01-NOV-00:10 0.55
December 0.446696E+09 0.55 166.78 01-DEC-00:10 0.55
           
Annual Sum or Average 0.525949E+10 0.55      
Minimum of Months 0.403467E+09 0.54 166.78   0.54
Maximum of Months 0.446696E+09 0.55 166.78   0.55



Table of Contents

Report: FanReportMonthly

For: CORRIDORFLR3 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.146408E+09 0.55 54.66 01-JAN-00:10 0.55
February 0.132239E+09 0.55 54.66 01-FEB-00:10 0.55
March 0.146408E+09 0.55 54.66 01-MAR-00:10 0.55
April 0.141685E+09 0.55 54.66 01-APR-00:10 0.55
May 0.146408E+09 0.54 54.66 01-MAY-00:10 0.55
June 0.141685E+09 0.54 54.66 01-JUN-00:10 0.55
July 0.146408E+09 0.54 54.66 01-JUL-00:10 0.54
August 0.146408E+09 0.54 54.66 01-AUG-00:10 0.54
September 0.141685E+09 0.54 54.66 01-SEP-00:10 0.54
October 0.146408E+09 0.55 54.66 01-OCT-00:10 0.55
November 0.141685E+09 0.55 54.66 01-NOV-00:10 0.55
December 0.146408E+09 0.55 54.66 01-DEC-00:10 0.55
           
Annual Sum or Average 0.172384E+10 0.55      
Minimum of Months 0.132239E+09 0.54 54.66   0.54
Maximum of Months 0.146408E+09 0.55 54.66   0.55



Table of Contents

Report: FanReportMonthly

For: CORRIDORFLR4 PTAC SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.241008E+09 0.55 89.98 01-JAN-00:10 0.55
February 0.217685E+09 0.55 89.98 01-FEB-00:10 0.55
March 0.241008E+09 0.55 89.98 01-MAR-00:10 0.55
April 0.233234E+09 0.55 89.98 01-APR-00:10 0.55
May 0.241008E+09 0.54 89.98 01-MAY-00:10 0.55
June 0.233234E+09 0.54 89.98 01-JUN-00:10 0.54
July 0.241008E+09 0.54 89.98 01-JUL-00:10 0.54
August 0.241008E+09 0.54 89.98 01-AUG-00:10 0.54
September 0.233234E+09 0.54 89.98 01-SEP-00:10 0.54
October 0.241008E+09 0.55 89.98 01-OCT-00:10 0.55
November 0.233234E+09 0.55 89.98 01-NOV-00:10 0.55
December 0.241008E+09 0.55 89.98 01-DEC-00:10 0.55
           
Annual Sum or Average 0.283768E+10 0.55      
Minimum of Months 0.217685E+09 0.54 89.98   0.54
Maximum of Months 0.241008E+09 0.55 89.98   0.55



Table of Contents

Report: FanReportMonthly

For: SAC_FRONTOFFICE_ADDAQ SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.121165E+10 0.97 452.38 02-JAN-14:10 0.97
February 0.109439E+10 0.97 452.38 02-FEB-17:01 0.97
March 0.121165E+10 0.96 452.38 01-MAR-22:00 0.97
April 0.117256E+10 0.96 452.38 01-APR-18:03 0.96
May 0.121165E+10 0.96 452.38 13-MAY-18:50 0.96
June 0.117256E+10 0.95 452.38 04-JUN-21:20 0.96
July 0.121165E+10 0.95 452.38 01-JUL-00:10 0.95
August 0.121165E+10 0.95 452.38 02-AUG-09:33 0.95
September 0.117256E+10 0.96 452.38 24-SEP-04:10 0.96
October 0.121165E+10 0.96 452.38 12-OCT-08:43 0.96
November 0.117256E+10 0.96 452.38 03-NOV-07:23 0.96
December 0.121165E+10 0.97 452.38 01-DEC-17:38 0.96
           
Annual Sum or Average 0.142662E+11 0.96      
Minimum of Months 0.109439E+10 0.95 452.38   0.95
Maximum of Months 0.121165E+10 0.97 452.38   0.97



Table of Contents

Report: FanReportMonthly

For: SAC_FRONTLOUNGE_ADDAQ SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.134196E+10 0.62 640.01 05-JAN-21:14 0.72
February 0.117513E+10 0.60 669.43 01-FEB-10:24 0.73
March 0.124810E+10 0.59 535.95 04-MAR-02:00 0.64
April 0.118318E+10 0.58 485.11 03-APR-04:00 0.60
May 0.121717E+10 0.57 454.44 04-MAY-08:57 0.57
June 0.117791E+10 0.57 454.44 07-JUN-13:30 0.57
July 0.121717E+10 0.57 454.44 09-JUL-18:35 0.57
August 0.121730E+10 0.57 529.00 04-AUG-06:50 0.62
September 0.117791E+10 0.57 454.44 17-SEP-21:00 0.57
October 0.121717E+10 0.57 454.44 20-OCT-16:35 0.57
November 0.120593E+10 0.58 575.76 26-NOV-07:10 0.67
December 0.129346E+10 0.60 623.22 11-DEC-20:05 0.70
           
Annual Sum or Average 0.146724E+11 0.58      
Minimum of Months 0.117513E+10 0.57 454.44   0.57
Maximum of Months 0.134196E+10 0.62 669.43   0.73



Table of Contents

Report: FanReportMonthly

For: SAC_MEETINGROOM_ADDAQ SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.591836E+09 0.92 516.74 01-JAN-08:04 0.96
February 0.530693E+09 0.70 516.74 01-FEB-08:08 0.97
March 0.578399E+09 0.55 516.74 01-MAR-08:11 0.97
April 0.566000E+09 0.53 516.74 01-APR-07:12 0.96
May 0.603825E+09 0.89 516.74 01-MAY-09:33 0.96
June 0.633137E+09 0.97 516.74 01-JUN-07:29 0.96
July 0.687652E+09 1.04 516.74 01-JUL-07:01 0.96
August 0.679214E+09 1.04 516.74 01-AUG-07:03 0.95
September 0.616683E+09 0.96 516.74 01-SEP-07:04 0.96
October 0.582269E+09 0.58 516.74 01-OCT-09:00 0.96
November 0.560581E+09 0.55 516.74 01-NOV-12:30 0.96
December 0.581956E+09 0.67 516.74 01-DEC-08:15 0.96
           
Annual Sum or Average 0.721225E+10 0.79      
Minimum of Months 0.530693E+09 0.53 516.74   0.95
Maximum of Months 0.687652E+09 1.04 516.74   0.97



Table of Contents

Report: FanReportMonthly

For: SAC_EMPLOYEELOUNGE_ADDAQ SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.244970E+10 0.96 914.61 01-JAN-04:00 0.95
February 0.221263E+10 0.95 914.61 01-FEB-06:40 0.96
March 0.244970E+10 0.95 914.61 01-MAR-05:13 0.96
April 0.237068E+10 0.95 914.61 01-APR-08:43 0.95
May 0.244970E+10 0.95 914.61 01-MAY-17:23 0.95
June 0.237068E+10 0.94 914.61 01-JUN-07:55 0.95
July 0.244970E+10 0.94 914.61 01-JUL-07:10 0.94
August 0.244970E+10 0.94 914.61 01-AUG-00:40 0.94
September 0.237068E+10 0.95 914.61 01-SEP-13:20 0.95
October 0.244970E+10 0.95 914.61 01-OCT-10:45 0.95
November 0.237068E+10 0.95 914.61 01-NOV-07:26 0.95
December 0.244970E+10 0.95 914.61 01-DEC-06:01 0.95
           
Annual Sum or Average 0.288432E+11 0.95      
Minimum of Months 0.221263E+10 0.94 914.61   0.94
Maximum of Months 0.244970E+10 0.96 914.61   0.96



Table of Contents

Report: FanReportMonthly

For: SAC_EXERCISECENTER_ADDAQ SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.474603E+09 0.97 177.20 03-JAN-18:01 0.97
February 0.428674E+09 0.97 177.20 11-FEB-22:06 0.97
March 0.474603E+09 0.96 177.20 07-MAR-10:33 0.97
April 0.459293E+09 0.96 177.20 04-APR-22:20 0.97
May 0.474603E+09 0.96 177.20 09-MAY-17:09 0.95
June 0.459293E+09 0.95 177.20 04-JUN-15:45 0.96
July 0.474603E+09 0.95 177.20 23-JUL-07:10 0.95
August 0.474603E+09 0.95 177.20 01-AUG-05:57 0.95
September 0.459293E+09 0.96 177.20 13-SEP-07:07 0.95
October 0.474603E+09 0.96 177.20 11-OCT-16:28 0.96
November 0.459293E+09 0.96 177.20 12-NOV-06:23 0.97
December 0.474603E+09 0.97 177.20 13-DEC-07:02 0.97
           
Annual Sum or Average 0.558807E+10 0.96      
Minimum of Months 0.428674E+09 0.95 177.20   0.95
Maximum of Months 0.474603E+09 0.97 177.20   0.97



Table of Contents

Report: FanReportMonthly

For: SAC_RESTROOM_ADDAQ SUPPLY FAN

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.248468E+09 0.94 92.77 13-JAN-17:15 0.94
February 0.224423E+09 0.94 92.77 02-FEB-02:30 0.94
March 0.248468E+09 0.94 92.77 18-MAR-16:05 0.94
April 0.240453E+09 0.95 92.77 01-APR-07:12 0.95
May 0.248468E+09 0.95 92.77 27-MAY-09:09 0.95
June 0.240453E+09 0.96 92.77 01-JUN-03:00 0.96
July 0.248468E+09 0.96 92.77 01-JUL-16:04 0.96
August 0.248468E+09 0.96 92.77 01-AUG-15:11 0.96
September 0.240453E+09 0.96 92.77 01-SEP-15:28 0.96
October 0.248468E+09 0.95 92.77 25-OCT-15:11 0.95
November 0.240453E+09 0.95 92.77 01-NOV-01:50 0.96
December 0.248468E+09 0.94 92.77 01-DEC-17:14 0.94
           
Annual Sum or Average 0.292551E+10 0.95      
Minimum of Months 0.224423E+09 0.94 92.77   0.94
Maximum of Months 0.248468E+09 0.96 92.77   0.96



Table of Contents

Report: PumpReportMonthly

For: SWHSYSSHOWER PUMP

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 21729602.91 18470162.47 8.11 01-JAN-00:10 6.90 6.90 52.02 0.18
February 19626738.11 16682727.40 8.11 01-FEB-00:10 6.90 6.90 51.29 0.18
March 21729602.91 18470162.47 8.11 01-MAR-00:10 6.90 6.90 51.40 0.18
April 21028647.98 17874350.78 8.11 01-APR-00:10 6.90 6.90 53.27 0.18
May 21729602.91 18470162.47 8.11 01-MAY-00:10 6.90 6.90 53.36 0.18
June 21028647.98 17874350.78 8.11 01-JUN-00:10 6.90 6.90 54.00 0.18
July 21729602.91 18470162.47 8.11 01-JUL-00:10 6.90 6.90 54.67 0.18
August 21729602.91 18470162.47 8.11 01-AUG-00:10 6.90 6.90 55.11 0.18
September 21028647.98 17874350.78 8.11 01-SEP-00:10 6.90 6.90 54.19 0.18
October 21729602.91 18470162.47 8.11 01-OCT-00:10 6.90 6.90 54.89 0.18
November 21028647.98 17874350.78 8.11 01-NOV-00:10 6.90 6.90 53.85 0.18
December 21729602.91 18470162.47 8.11 01-DEC-00:10 6.90 6.90 52.23 0.18
                 
Annual Sum or Average 0.255849E+09 0.217471E+09            
Minimum of Months 19626738.11 16682727.40 8.11   6.90 6.90 51.29 0.18
Maximum of Months 21729602.91 18470162.47 8.11   6.90 6.90 55.11 0.18



Table of Contents

Report: PumpReportMonthly

For: SWHSYSLAUNDRY PUMP

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.49 0.15 0.00 01-JAN-08:61 0.00 0.00 5.36 0.13
February 0.45 0.13 0.00 01-FEB-08:61 0.00 0.00 3.45 0.13
March 0.49 0.15 0.00 01-MAR-08:61 0.00 0.00 3.17 0.13
April 0.48 0.14 0.00 01-APR-07:01 0.00 0.00 4.60 0.13
May 0.49 0.15 0.00 01-MAY-07:01 0.00 0.00 7.33 0.13
June 0.48 0.14 0.00 01-JUN-07:01 0.00 0.00 10.80 0.13
July 0.49 0.15 0.00 01-JUL-07:01 0.00 0.00 13.88 0.13
August 0.49 0.15 0.00 01-AUG-07:01 0.00 0.00 15.90 0.13
September 0.48 0.14 0.00 01-SEP-07:01 0.00 0.00 16.21 0.13
October 0.49 0.15 0.00 01-OCT-07:01 0.00 0.00 14.79 0.13
November 0.48 0.14 0.00 01-NOV-07:01 0.00 0.00 11.93 0.13
December 0.49 0.15 0.00 01-DEC-08:61 0.00 0.00 8.56 0.13
                 
Annual Sum or Average 5.81 1.74            
Minimum of Months 0.45 0.13 0.00   0.00 0.00 3.17 0.13
Maximum of Months 0.49 0.15 0.00   0.00 0.00 16.21 0.13



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYSSHOWER

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 52.02 59.60 9586.11 22602.10 29-JAN-08:11
February 0.00 0.00 01-FEB-00:10 51.29 58.51 9772.77 22780.76 19-FEB-08:17
March 0.00 0.00 01-MAR-00:10 51.40 58.67 9696.48 22722.26 01-MAR-07:09
April 0.00 0.00 01-APR-00:10 53.27 58.58 9334.35 22182.96 01-APR-07:17
May 0.00 0.00 01-MAY-00:10 53.36 58.37 8832.74 21092.93 01-MAY-06:08
June 0.00 0.00 01-JUN-00:10 54.00 58.71 8295.68 19749.95 01-JUN-06:09
July 0.00 0.00 01-JUL-00:10 54.67 59.13 7856.65 18572.31 01-JUL-07:18
August 0.00 0.00 01-AUG-00:10 55.11 59.75 7681.11 17773.54 02-AUG-06:09
September 0.00 0.00 01-SEP-00:10 54.19 58.33 7762.83 18221.27 30-SEP-07:12
October 0.00 0.00 01-OCT-00:10 54.89 59.47 8117.72 19274.03 30-OCT-06:09
November 0.00 0.00 01-NOV-00:10 53.85 58.49 8630.11 20586.99 30-NOV-07:06
December 0.00 0.00 01-DEC-00:10 52.23 59.04 9162.76 21861.09 31-DEC-08:12
                 
Annual Sum or Average 0.00         8721.28    
Minimum of Months 0.00 0.00   51.29 58.33 7681.11 17773.54  
Maximum of Months 0.00 0.00   55.11 59.75 9772.77 22780.76  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYSLAUNDRY

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 5.36 5.36 10087.04 30733.33 31-JAN-08:33
February 0.00 0.00 01-FEB-00:10 3.47 3.47 10298.09 30944.55 20-FEB-08:26
March 0.00 0.00 01-MAR-00:10 3.17 3.17 10191.29 30900.24 01-MAR-08:61
April 0.00 0.00 01-APR-00:10 4.56 4.56 9790.11 30087.16 01-APR-07:01
May 0.00 0.00 01-MAY-00:10 7.29 7.29 9206.19 28568.12 01-MAY-07:01
June 0.00 0.00 01-JUN-00:10 10.75 10.75 8592.54 26657.03 01-JUN-07:01
July 0.00 0.00 01-JUL-00:10 13.84 13.84 8113.95 24970.10 01-JUL-07:01
August 0.00 0.00 01-AUG-00:10 15.89 15.89 7896.42 23859.92 01-AUG-07:01
September 0.00 0.00 01-SEP-00:10 16.22 16.22 8002.96 24451.94 30-SEP-07:33
October 0.00 0.00 01-OCT-00:10 14.82 14.82 8402.43 26011.71 31-OCT-07:33
November 0.00 0.00 01-NOV-00:10 11.98 11.98 8986.30 27861.13 30-NOV-08:37
December 0.00 0.00 01-DEC-00:10 8.62 8.62 9599.48 29608.23 31-DEC-08:33
                 
Annual Sum or Average 0.00         9090.15    
Minimum of Months 0.00 0.00   3.17 3.17 7896.42 23859.92  
Maximum of Months 0.00 0.00   16.22 16.22 10298.09 30944.55  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: REARSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDORFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: REARSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONTLOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RESTROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MEETINGROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECHANICALROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM101

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM102

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM103

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM104

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM105

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: EMPLOYEELOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRYROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ELEVATORCOREFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: EXERCISECENTERFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONTOFFICEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONTSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONTSTORAGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: REARSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDORFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: REARSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM201

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM202_205

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM206_208

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM209_212

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM213

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM214

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM215_218

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ELEVATORCOREFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM219

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM220_223

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM224

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONTSTORAGEFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONTSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: REARSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDORFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: REARSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM301

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM302_305

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM306_308

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM309_312

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM313

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM314

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM315_318

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ELEVATORCOREFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM319

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM320_323

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM324

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONTSTORAGEFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONTSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: REARSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDORFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: REARSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM401

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM402_405

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM406_408

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM409_412

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM413

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM414

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM415_418

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ELEVATORCOREFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM419

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM420_423

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GUESTROOM424

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONTSTORAGEFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FRONTSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: SAC_FRONTOFFICE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.121165E+10 0.00 0.00
February 0.00 0.00 0.00 0.109439E+10 0.00 0.00
March 0.00 0.00 0.00 0.122678E+10 0.00 0.00
April 0.00 0.00 0.00 0.132338E+10 0.00 0.00
May 0.00 0.00 0.00 0.169446E+10 0.00 0.00
June 0.00 0.00 0.00 0.213598E+10 0.00 0.00
July 0.00 0.00 0.00 0.245153E+10 0.00 0.00
August 0.00 0.00 0.00 0.239774E+10 0.00 0.00
September 0.00 0.00 0.00 0.186252E+10 0.00 0.00
October 0.00 0.00 0.00 0.135489E+10 0.00 0.00
November 0.00 0.00 0.00 0.122933E+10 0.00 0.00
December 0.00 0.00 0.00 0.121165E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.191943E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.109439E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.245153E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: SAC_FRONTLOUNGE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.134196E+10 0.00 0.00
February 0.00 0.00 0.00 0.117513E+10 0.00 0.00
March 0.00 0.00 0.00 0.124810E+10 0.00 0.00
April 0.00 0.00 0.00 0.135840E+10 0.00 0.00
May 0.00 0.00 0.00 0.152637E+10 0.00 0.00
June 0.00 0.00 0.00 0.262704E+10 0.00 0.00
July 0.00 0.00 0.00 0.326500E+10 0.00 0.00
August 0.00 0.00 0.00 0.297866E+10 0.00 0.00
September 0.00 0.00 0.00 0.193117E+10 0.00 0.00
October 0.00 0.00 0.00 0.122596E+10 0.00 0.00
November 0.00 0.00 0.00 0.120593E+10 0.00 0.00
December 0.00 0.00 0.00 0.129346E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.211772E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.117513E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.326500E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: SAC_MEETINGROOM

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.591836E+09 0.00 0.00
February 0.00 0.00 0.00 0.530693E+09 0.00 0.00
March 0.00 0.00 0.00 0.578484E+09 0.00 0.00
April 0.00 0.00 0.00 0.647982E+09 0.00 0.00
May 0.00 0.00 0.00 0.814030E+09 0.00 0.00
June 0.00 0.00 0.00 0.124817E+10 0.00 0.00
July 0.00 0.00 0.00 0.152760E+10 0.00 0.00
August 0.00 0.00 0.00 0.147967E+10 0.00 0.00
September 0.00 0.00 0.00 0.102283E+10 0.00 0.00
October 0.00 0.00 0.00 0.608288E+09 0.00 0.00
November 0.00 0.00 0.00 0.564559E+09 0.00 0.00
December 0.00 0.00 0.00 0.581956E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.101961E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.530693E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.152760E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: SAC_EMPLOYEELOUNGE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.283292E+10 0.00 0.00
February 0.00 0.00 0.00 0.272744E+10 0.00 0.00
March 0.00 0.00 0.00 0.329769E+10 0.00 0.00
April 0.00 0.00 0.00 0.350330E+10 0.00 0.00
May 0.00 0.00 0.00 0.403143E+10 0.00 0.00
June 0.00 0.00 0.00 0.426417E+10 0.00 0.00
July 0.00 0.00 0.00 0.457678E+10 0.00 0.00
August 0.00 0.00 0.00 0.452237E+10 0.00 0.00
September 0.00 0.00 0.00 0.399258E+10 0.00 0.00
October 0.00 0.00 0.00 0.368095E+10 0.00 0.00
November 0.00 0.00 0.00 0.323601E+10 0.00 0.00
December 0.00 0.00 0.00 0.299267E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.436583E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.272744E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.457678E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: SAC_EXERCISECENTER

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.474603E+09 0.00 0.00
February 0.00 0.00 0.00 0.428674E+09 0.00 0.00
March 0.00 0.00 0.00 0.478104E+09 0.00 0.00
April 0.00 0.00 0.00 0.528549E+09 0.00 0.00
May 0.00 0.00 0.00 0.649731E+09 0.00 0.00
June 0.00 0.00 0.00 0.925584E+09 0.00 0.00
July 0.00 0.00 0.00 0.109285E+10 0.00 0.00
August 0.00 0.00 0.00 0.103967E+10 0.00 0.00
September 0.00 0.00 0.00 0.722580E+09 0.00 0.00
October 0.00 0.00 0.00 0.494203E+09 0.00 0.00
November 0.00 0.00 0.00 0.461092E+09 0.00 0.00
December 0.00 0.00 0.00 0.474603E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.777025E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.428674E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.109285E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: SAC_RESTROOM

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.248470E+09 0.00 0.00
February 0.00 0.00 0.00 0.226356E+09 0.00 0.00
March 0.00 0.00 0.00 0.273325E+09 0.00 0.00
April 0.00 0.00 0.00 0.314858E+09 0.00 0.00
May 0.00 0.00 0.00 0.396463E+09 0.00 0.00
June 0.00 0.00 0.00 0.433467E+09 0.00 0.00
July 0.00 0.00 0.00 0.476046E+09 0.00 0.00
August 0.00 0.00 0.00 0.476973E+09 0.00 0.00
September 0.00 0.00 0.00 0.428825E+09 0.00 0.00
October 0.00 0.00 0.00 0.372056E+09 0.00 0.00
November 0.00 0.00 0.00 0.291995E+09 0.00 0.00
December 0.00 0.00 0.00 0.249125E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.418796E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.226356E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.476973E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: SAC_FRONTOFFICE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.121165E+10 0.00 0.436510E+10 0.00 0.00 0.00 0.00 0.00
February 0.109439E+10 0.00 0.279447E+10 0.00 0.00 0.00 0.00 0.00
March 0.121165E+10 69207424.72 0.118324E+10 0.00 0.00 0.00 0.00 0.00
April 0.117256E+10 0.708748E+09 0.295941E+09 0.00 0.00 0.00 0.00 0.00
May 0.121165E+10 0.229205E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.117256E+10 0.464300E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.121165E+10 0.607537E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.121165E+10 0.578945E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.117256E+10 0.328484E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.121165E+10 0.665823E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.117256E+10 0.263124E+09 0.108195E+10 0.00 0.00 0.00 0.00 0.00
December 0.121165E+10 0.00 0.280616E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.142662E+11 0.237916E+11 0.125269E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109439E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.121165E+10 0.607537E+10 0.436510E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: SAC_FRONTLOUNGE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.134196E+10 0.00 0.646731E+10 0.00 0.00 0.00 0.00 0.00
February 0.117513E+10 0.00 0.392610E+10 0.00 0.00 0.00 0.00 0.00
March 0.124810E+10 0.00 0.160284E+10 0.00 0.00 0.00 0.00 0.00
April 0.118318E+10 0.704768E+09 0.273271E+09 0.00 0.00 0.00 0.00 0.00
May 0.121717E+10 0.125675E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.117791E+10 0.594318E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.121717E+10 0.856946E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.121730E+10 0.734877E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.117791E+10 0.303519E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.121717E+10 35083930.47 0.00 0.00 0.00 0.00 0.00 0.00
November 0.120593E+10 0.00 0.145246E+10 0.00 0.00 0.00 0.00 0.00
December 0.129346E+10 0.00 0.395367E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.146724E+11 0.268932E+11 0.176757E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.117513E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.134196E+10 0.856946E+10 0.646731E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: SAC_MEETINGROOM

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.591836E+09 0.00 0.461899E+10 0.00 0.00 0.00 0.00 0.00
February 0.530693E+09 0.00 0.316479E+10 0.00 0.00 0.00 0.00 0.00
March 0.578399E+09 382031.97 0.166592E+10 0.00 0.00 0.00 0.00 0.00
April 0.566000E+09 0.375624E+09 0.642783E+09 0.00 0.00 0.00 0.00 0.00
May 0.603825E+09 0.966969E+09 10741211.76 0.00 0.00 0.00 0.00 0.00
June 0.633137E+09 0.284696E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.687652E+09 0.395525E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.679214E+09 0.375596E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.616683E+09 0.185456E+10 941901.65 0.00 0.00 0.00 0.00 0.00
October 0.582269E+09 0.117880E+09 0.112338E+09 0.00 0.00 0.00 0.00 0.00
November 0.560581E+09 17909872.53 0.156878E+10 0.00 0.00 0.00 0.00 0.00
December 0.581956E+09 0.00 0.329013E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.721225E+10 0.138915E+11 0.150754E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530693E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.687652E+09 0.395525E+10 0.461899E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: SAC_EMPLOYEELOUNGE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.244970E+10 0.176999E+10 58342485.58 0.00 0.00 0.00 0.00 0.00
February 0.221263E+10 0.239267E+10 0.109538E+09 0.00 0.00 0.00 0.00 0.00
March 0.244970E+10 0.396954E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.237068E+10 0.533320E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.244970E+10 0.754561E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.237068E+10 0.900294E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.244970E+10 0.102438E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.244970E+10 0.995627E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.237068E+10 0.768802E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.244970E+10 0.581763E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.237068E+10 0.405917E+10 4401617.36 0.00 0.00 0.00 0.00 0.00
December 0.244970E+10 0.251691E+10 4312894.73 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.288432E+11 0.702958E+11 0.176595E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.221263E+10 0.176999E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.244970E+10 0.102438E+11 0.109538E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: SAC_EXERCISECENTER

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.474603E+09 0.00 0.605359E+10 0.00 0.00 0.00 0.00 0.00
February 0.428674E+09 0.00 0.428680E+10 0.00 0.00 0.00 0.00 0.00
March 0.474603E+09 16076337.56 0.269302E+10 0.00 0.00 0.00 0.00 0.00
April 0.459293E+09 0.338297E+09 0.126391E+10 0.00 0.00 0.00 0.00 0.00
May 0.474603E+09 0.849596E+09 0.198160E+09 0.00 0.00 0.00 0.00 0.00
June 0.459293E+09 0.231137E+10 39596136.19 0.00 0.00 0.00 0.00 0.00
July 0.474603E+09 0.312901E+10 359850.08 0.00 0.00 0.00 0.00 0.00
August 0.474603E+09 0.283869E+10 2452775.87 0.00 0.00 0.00 0.00 0.00
September 0.459293E+09 0.127868E+10 0.175784E+09 0.00 0.00 0.00 0.00 0.00
October 0.474603E+09 91496993.97 0.755997E+09 0.00 0.00 0.00 0.00 0.00
November 0.459293E+09 8177471.69 0.256031E+10 0.00 0.00 0.00 0.00 0.00
December 0.474603E+09 0.00 0.469534E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.558807E+10 0.108614E+11 0.227253E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.428674E+09 0.00 359850.08 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.474603E+09 0.312901E+10 0.605359E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: SAC_RESTROOM

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.248468E+09 8464.12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.224423E+09 9376144.74 3050474.72 0.00 0.00 0.00 0.00 0.00
March 0.248468E+09 0.115984E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.240453E+09 0.349339E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.248468E+09 0.703055E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.240453E+09 0.921296E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.248468E+09 0.110388E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.248468E+09 0.110826E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.240453E+09 0.905812E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.248468E+09 0.583182E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.240453E+09 0.242052E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.248468E+09 3190256.42 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.292551E+10 0.604543E+10 3050474.72 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.224423E+09 8464.12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.248468E+09 0.110826E+10 3050474.72 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: SAC_FRONTOFFICE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.121165E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109439E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.121165E+10 0.00 0.00 0.00 15133171.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.117256E+10 0.00 0.00 0.00 0.150821E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.121165E+10 0.00 0.00 0.00 0.482809E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.117256E+10 0.00 0.00 0.00 0.963415E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.121165E+10 0.00 0.00 0.00 0.123988E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.121165E+10 0.00 0.00 0.00 0.118609E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.117256E+10 0.00 0.00 0.00 0.689955E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.121165E+10 0.00 0.00 0.00 0.143242E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.117256E+10 0.00 0.00 0.00 56763660.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.121165E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.142662E+11 0.00 0.00 0.00 0.492811E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109439E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.121165E+10 0.00 0.00 0.00 0.123988E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: SAC_FRONTLOUNGE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.134196E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.117513E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.124810E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.118318E+10 0.00 0.00 0.00 0.175218E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.121717E+10 0.00 0.00 0.00 0.309204E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.117791E+10 0.00 0.00 0.00 0.144913E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.121717E+10 0.00 0.00 0.00 0.204783E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.121730E+10 0.00 0.00 0.00 0.176136E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.117791E+10 0.00 0.00 0.00 0.753266E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.121717E+10 0.00 0.00 0.00 8790017.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.120593E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129346E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.146724E+11 0.00 0.00 0.00 0.650480E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.117513E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.134196E+10 0.00 0.00 0.00 0.204783E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: SAC_MEETINGROOM

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.591836E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530693E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.578399E+09 0.00 0.00 0.00 84624.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.566000E+09 0.00 0.00 0.00 81982061.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.603825E+09 0.00 0.00 0.00 0.210205E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.633137E+09 0.00 0.00 0.00 0.615033E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.687652E+09 0.00 0.00 0.00 0.839944E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.679214E+09 0.00 0.00 0.00 0.800460E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.616683E+09 0.00 0.00 0.00 0.406147E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.582269E+09 0.00 0.00 0.00 26019219.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.560581E+09 0.00 0.00 0.00 3978329.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.581956E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.721225E+10 0.00 0.00 0.00 0.298385E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530693E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.687652E+09 0.00 0.00 0.00 0.839944E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: SAC_EMPLOYEELOUNGE

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.244970E+10 0.00 0.00 0.00 0.383219E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.221263E+10 0.00 0.00 0.00 0.514811E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.244970E+10 0.00 0.00 0.00 0.847987E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.237068E+10 0.00 0.00 0.00 0.113262E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.244970E+10 0.00 0.00 0.00 0.158173E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.237068E+10 0.00 0.00 0.00 0.189349E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.244970E+10 0.00 0.00 0.00 0.212709E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.244970E+10 0.00 0.00 0.00 0.207267E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.237068E+10 0.00 0.00 0.00 0.162190E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.244970E+10 0.00 0.00 0.00 0.123125E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.237068E+10 0.00 0.00 0.00 0.865334E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.244970E+10 0.00 0.00 0.00 0.542967E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.288432E+11 0.00 0.00 0.00 0.148151E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.221263E+10 0.00 0.00 0.00 0.383219E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.244970E+10 0.00 0.00 0.00 0.212709E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: SAC_EXERCISECENTER

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.474603E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.428674E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.474603E+09 0.00 0.00 0.00 3500609.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.459293E+09 0.00 0.00 0.00 69255581.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.474603E+09 0.00 0.00 0.00 0.175128E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.459293E+09 0.00 0.00 0.00 0.466290E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.474603E+09 0.00 0.00 0.00 0.618252E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.474603E+09 0.00 0.00 0.00 0.565067E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.459293E+09 0.00 0.00 0.00 0.263287E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.474603E+09 0.00 0.00 0.00 19600056.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.459293E+09 0.00 0.00 0.00 1798552.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.474603E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.558807E+10 0.00 0.00 0.00 0.218218E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.428674E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.474603E+09 0.00 0.00 0.00 0.618252E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: SAC_RESTROOM

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.248468E+09 0.00 0.00 0.00 1757.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.224423E+09 0.00 0.00 0.00 1932749.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.248468E+09 0.00 0.00 0.00 24857036.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.240453E+09 0.00 0.00 0.00 74405209.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.248468E+09 0.00 0.00 0.00 0.147995E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.240453E+09 0.00 0.00 0.00 0.193014E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.248468E+09 0.00 0.00 0.00 0.227577E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.248468E+09 0.00 0.00 0.00 0.228504E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.240453E+09 0.00 0.00 0.00 0.188372E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.248468E+09 0.00 0.00 0.00 0.123588E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.240453E+09 0.00 0.00 0.00 51541983.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.248468E+09 0.00 0.00 0.00 657134.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.292551E+10 0.00 0.00 0.00 0.126245E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.224423E+09 0.00 0.00 0.00 1757.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.248468E+09 0.00 0.00 0.00 0.228504E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: REARSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDORFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.185745E+10 0.00 0.00 1071659.10 0.00 0.240828E+10 0.659060E+09 0.00 0.33
February 0.168518E+10 0.00 0.00 2349064.51 0.00 0.126985E+10 0.924536E+09 0.00 0.33
March 0.134550E+10 0.00 0.00 8097039.95 0.00 0.404957E+09 0.148147E+10 0.00 0.33
April 0.633666E+09 67849315.98 0.00 17251024.10 1461.70 0.157975E+09 0.146148E+10 0.00 0.33
May 83732200.91 86391871.68 0.00 37193276.52 10942.54 45138013.92 0.101392E+10 0.00 0.33
June 32718617.80 0.613205E+09 0.00 23650499.55 429663.88 14034410.81 0.446233E+09 0.00 0.33
July 15574260.71 0.876130E+09 0.00 16374899.42 738704.06 0.00 0.109450E+09 0.00 0.33
August 25051027.39 0.733729E+09 0.00 22038797.24 295956.35 2887078.46 0.209479E+09 0.00 0.33
September 69522681.36 0.174601E+09 0.00 35362130.89 3111.83 47898487.00 0.938858E+09 0.00 0.33
October 0.237799E+09 0.00 0.00 24998583.86 0.00 0.137684E+09 0.191207E+10 0.00 0.33
November 0.111736E+10 0.00 0.00 11010388.40 0.00 0.585927E+09 0.144964E+10 0.00 0.33
December 0.191576E+10 0.00 0.00 2235929.94 0.00 0.117249E+10 0.117310E+10 0.00 0.33
                   
Annual Sum or Average 0.901932E+10 0.255191E+10 0.00 0.201633E+09 1479840.37 0.624713E+10 0.117793E+11 0.00 0.33
Minimum of Months 15574260.71 0.00 0.00 1071659.10 0.00 0.00 0.109450E+09 0.00 0.33
Maximum of Months 0.191576E+10 0.876130E+09 0.00 37193276.52 738704.06 0.240828E+10 0.191207E+10 0.00 0.33



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FRONTLOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.101688E+11 0.00 0.00 0.00 0.00 0.191790E+10 0.00 0.00 0.65
February 0.818938E+10 0.00 0.00 1753.01 0.00 0.141003E+10 14158293.07 0.00 0.66
March 0.751554E+10 0.00 0.00 2879459.24 0.00 0.196425E+09 0.935081E+09 0.00 0.69
April 0.417237E+10 88208629.90 0.00 12792850.80 0.00 0.00 0.312386E+10 0.00 0.91
May 0.364093E+09 87669702.76 0.00 33354324.60 0.00 0.00 0.721431E+10 0.00 1.55
June 29188031.48 0.954483E+09 0.00 32252360.17 0.00 0.00 0.497240E+10 0.00 1.85
July 0.00 0.140633E+10 0.00 32940963.29 0.00 0.00 0.401298E+10 0.00 2.21
August 0.00 0.123572E+10 0.00 38209297.14 0.00 0.00 0.507214E+10 0.00 2.12
September 0.303760E+09 0.228597E+09 0.00 35290270.19 0.00 0.00 0.667640E+10 0.00 1.68
October 0.232276E+10 0.00 0.00 19826472.56 0.00 0.00 0.595772E+10 0.00 0.92
November 0.641697E+10 0.00 0.00 7577832.45 0.00 0.260546E+09 0.223738E+10 0.00 0.75
December 0.998335E+10 0.00 0.00 0.00 0.00 0.541618E+09 0.00 0.00 0.65
                   
Annual Sum or Average 0.494662E+11 0.400100E+10 0.00 0.215126E+09 0.00 0.432652E+10 0.402164E+11 0.00 1.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.65
Maximum of Months 0.101688E+11 0.140633E+10 0.00 38209297.14 0.00 0.191790E+10 0.721431E+10 0.00 2.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RESTROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MEETINGROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.446475E+10 0.00 0.00 0.00 0.00 0.141944E+10 0.00 0.00 0.72
February 0.368892E+10 0.00 0.00 0.00 0.00 0.843796E+09 0.00 0.00 0.72
March 0.349811E+10 0.00 0.00 8458.26 0.00 24643959.23 17791453.49 0.00 0.71
April 0.236315E+10 85790767.73 0.00 890451.40 0.00 324559.94 0.131711E+09 0.00 0.72
May 0.733619E+09 78638338.94 0.00 4499025.79 0.00 0.00 0.685364E+09 0.00 0.75
June 0.323832E+09 0.706118E+09 0.00 4463831.42 0.00 0.00 0.350257E+09 0.00 0.80
July 1181975.72 0.897177E+09 0.00 4434850.60 0.00 0.00 0.213079E+09 0.00 0.84
August 0.00 0.789747E+09 0.00 6189200.41 0.00 0.00 0.287259E+09 0.00 0.83
September 0.586720E+09 0.243593E+09 0.00 6092750.71 0.00 0.00 0.629524E+09 0.00 0.78
October 0.210693E+10 0.00 0.00 1053029.71 0.00 0.00 0.345341E+09 0.00 0.72
November 0.340646E+10 0.00 0.00 312618.60 0.00 34793627.24 0.144195E+09 0.00 0.71
December 0.442832E+10 0.00 0.00 0.00 0.00 0.497799E+09 0.00 0.00 0.71
                   
Annual Sum or Average 0.256020E+11 0.280106E+10 0.00 27944216.89 0.00 0.282080E+10 0.280452E+10 0.00 0.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.71
Maximum of Months 0.446475E+10 0.897177E+09 0.00 6189200.41 0.00 0.141944E+10 0.685364E+09 0.00 0.84



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECHANICALROOMFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM101

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 51303182.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
February 38324983.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
March 28426834.23 0.00 0.00 0.00 378531.66 0.00 0.00 0.00 0.02
April 21745760.61 0.00 0.00 0.00 2406069.70 0.00 0.00 0.00 0.02
May 9134503.13 0.00 0.00 0.00 2622792.47 0.00 0.00 0.00 0.02
June 8085099.00 0.00 0.00 0.00 5993049.89 0.00 0.00 0.00 0.02
July 6172936.75 43549.49 0.00 125.30 5307131.14 0.00 0.00 0.00 0.02
August 5918263.16 2084.81 0.00 0.00 5158340.95 0.00 0.00 0.00 0.02
September 13431832.90 4213.81 0.00 0.00 2297196.98 0.00 0.00 0.00 0.02
October 19316821.06 0.00 0.00 0.00 580412.35 0.00 0.00 0.00 0.02
November 31664274.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
December 43377950.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
                   
Annual Sum or Average 0.276902E+09 49848.11 0.00 125.30 24743525.14 0.00 0.00 0.00 0.02
Minimum of Months 5918263.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 51303182.92 43549.49 0.00 125.30 5993049.89 0.00 0.00 0.00 0.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM102

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 50192289.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
February 37372180.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
March 27360192.85 0.00 0.00 0.00 399075.92 0.00 0.00 0.00 0.02
April 20818432.99 0.00 0.00 0.00 2545730.54 0.00 0.00 0.00 0.02
May 8452571.92 0.00 0.00 0.00 2882131.18 0.00 0.00 0.00 0.02
June 7492528.67 0.00 0.00 0.00 6336917.36 0.00 0.00 0.00 0.02
July 5762606.03 0.00 0.00 0.00 5564830.74 0.00 0.00 0.00 0.02
August 5590880.40 0.00 0.00 0.00 5618747.46 0.00 0.00 0.00 0.02
September 12542961.45 0.00 0.00 0.00 2539912.74 0.00 0.00 0.00 0.02
October 18379559.05 0.00 0.00 0.00 697543.39 0.00 0.00 0.00 0.02
November 30573603.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
December 42259862.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
                   
Annual Sum or Average 0.266798E+09 0.00 0.00 0.00 26584889.32 0.00 0.00 0.00 0.02
Minimum of Months 5590880.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 50192289.71 0.00 0.00 0.00 6336917.36 0.00 0.00 0.00 0.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM103

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 37850827.03 0.00 0.00 29042.76 0.00 0.138606E+10 19234799.78 0.00 0.34
February 43137155.13 0.00 0.00 107663.47 0.00 0.101620E+10 0.111568E+09 0.00 0.34
March 59791349.10 0.00 0.00 592106.50 0.00 0.683400E+09 0.289725E+09 0.00 0.34
April 63003258.51 8770427.30 20617.31 1869860.73 656624.57 0.228472E+09 0.454599E+09 966.36 0.34
May 78431064.58 7859713.62 25517.28 4939037.66 505537.61 1485256.76 0.328904E+09 1108.63 0.34
June 37714859.96 0.123329E+09 49169.01 4516429.23 6418297.74 488970.40 0.128696E+09 588.93 0.34
July 32236459.58 0.176077E+09 77525.08 3789559.24 14499786.69 33439.57 27022189.78 442.20 0.35
August 42895513.99 0.141057E+09 59816.24 5429028.79 12695872.21 58185.26 51635641.83 664.97 0.35
September 46965431.63 32761790.67 2105.12 5985347.47 1074609.19 1224524.49 0.293070E+09 87.67 0.34
October 52714658.55 0.00 0.00 4319149.81 0.00 3826683.93 0.676812E+09 0.00 0.34
November 53184371.19 0.00 0.00 1887596.01 0.00 0.367099E+09 0.548054E+09 0.00 0.34
December 53719766.21 0.00 0.00 96976.80 0.00 0.113468E+10 0.101545E+09 0.00 0.34
                   
Annual Sum or Average 0.601645E+09 0.489855E+09 234750.04 33561798.46 35850727.99 0.482304E+10 0.303087E+10 3858.76 0.34
Minimum of Months 32236459.58 0.00 0.00 29042.76 0.00 33439.57 19234799.78 0.00 0.34
Maximum of Months 78431064.58 0.176077E+09 77525.08 5985347.47 14499786.69 0.138606E+10 0.676812E+09 1108.63 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM104

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 76535379.92 0.00 0.00 308508.06 0.00 0.104601E+10 0.320446E+09 0.00 0.34
February 57749411.89 0.00 0.00 692295.74 0.00 0.582442E+09 0.525453E+09 0.00 0.34
March 61368114.96 0.00 0.00 1698496.19 0.00 0.301377E+09 0.655196E+09 0.00 0.34
April 56939166.43 11325839.57 9673.06 3149544.73 432697.47 46760167.46 0.620797E+09 273.58 0.34
May 51082994.75 11432370.86 8806.63 6368314.73 983163.56 1383276.71 0.318822E+09 325.47 0.34
June 28176687.90 0.133950E+09 132557.76 4753636.32 6939666.49 436436.16 0.121697E+09 685.05 0.35
July 24328461.96 0.194162E+09 16040.00 3692556.18 14731940.42 32085.35 24886027.45 551.33 0.35
August 33552406.42 0.155154E+09 20848.09 5259957.97 12916192.43 60580.99 51271990.06 304.17 0.35
September 37783927.27 37568467.45 854.77 6847190.54 1077041.70 990810.54 0.289405E+09 43.11 0.35
October 36916368.47 0.00 0.00 5605308.10 0.00 2788901.62 0.669884E+09 0.00 0.34
November 49450580.03 0.00 0.00 3034618.05 0.00 0.169299E+09 0.733842E+09 0.00 0.34
December 68720126.53 0.00 0.00 815109.54 0.00 0.515232E+09 0.706022E+09 0.00 0.34
                   
Annual Sum or Average 0.582604E+09 0.543592E+09 188780.32 42225536.16 37080702.07 0.266682E+10 0.503772E+10 2182.73 0.34
Minimum of Months 24328461.96 0.00 0.00 308508.06 0.00 32085.35 24886027.45 0.00 0.34
Maximum of Months 76535379.92 0.194162E+09 132557.76 6847190.54 14731940.42 0.104601E+10 0.733842E+09 685.05 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM105

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 71821362.61 0.00 0.00 5663659.68 0.00 5504973.95 0.135207E+10 0.00 0.34
February 39716667.80 0.00 0.00 5771799.44 0.00 3179593.83 0.108844E+10 0.00 0.34
March 23832059.10 0.00 0.00 7466481.89 0.00 3055672.14 0.935914E+09 0.00 0.34
April 20219773.15 16484175.24 39431.99 8002453.71 576849.22 2002087.96 0.639290E+09 1120.03 0.34
May 29099251.13 20924381.42 41686.15 9484944.82 1891747.97 707409.88 0.283084E+09 1039.75 0.35
June 14430019.41 0.162678E+09 136567.09 5674861.09 8201703.80 226218.68 0.104399E+09 6913.90 0.35
July 12774366.09 0.235703E+09 368868.92 3178167.27 15878153.50 43553.28 25391543.45 6598.22 0.35
August 18519658.10 0.188743E+09 290211.38 4851372.71 13834662.27 75544.97 51908769.51 11991.85 0.35
September 24425266.03 46718875.00 73857.40 8790235.09 1279277.50 780327.84 0.276538E+09 5524.43 0.35
October 9348829.10 0.00 0.00 10028232.86 0.00 2046591.48 0.654764E+09 0.00 0.35
November 20215003.22 0.00 0.00 8036934.13 0.00 2892413.87 0.884637E+09 0.00 0.34
December 53596400.24 0.00 0.00 6452839.90 0.00 4620857.68 0.120499E+10 0.00 0.34
                   
Annual Sum or Average 0.337999E+09 0.671251E+09 950622.93 83401982.60 41662394.25 25135245.57 0.750143E+10 33188.18 0.35
Minimum of Months 9348829.10 0.00 0.00 3178167.27 0.00 43553.28 25391543.45 0.00 0.34
Maximum of Months 71821362.61 0.235703E+09 368868.92 10028232.86 15878153.50 5504973.95 0.135207E+10 11991.85 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: EMPLOYEELOUNGEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.130014E+10 0.00 0.00 20197579.06 0.00 0.00 0.480581E+10 0.00 1.75
February 0.842619E+09 0.00 0.00 21246734.25 0.00 0.00 0.399394E+10 0.00 1.75
March 19468243.38 0.00 0.00 26908904.45 0.00 0.00 0.409989E+10 0.00 1.76
April 0.00 73967846.12 0.00 26433489.32 0.00 0.00 0.287385E+10 0.00 1.76
May 0.00 95827224.18 0.00 29646626.96 0.00 0.00 0.150176E+10 0.00 1.76
June 0.00 0.647773E+09 0.00 17273474.41 0.00 0.00 0.669481E+09 0.00 1.76
July 0.00 0.945581E+09 0.00 9878315.78 0.00 0.00 0.198228E+09 0.00 1.76
August 0.00 0.793782E+09 0.00 14690223.69 0.00 0.00 0.363914E+09 0.00 1.77
September 0.00 0.152401E+09 0.00 26849120.35 0.00 0.00 0.143377E+10 0.00 1.76
October 0.00 0.00 0.00 30310458.56 0.00 0.00 0.293061E+10 0.00 1.76
November 0.156696E+09 0.00 0.00 25948289.70 0.00 0.00 0.382036E+10 0.00 1.76
December 0.411719E+09 0.00 0.00 23928730.19 0.00 0.00 0.494752E+10 0.00 1.74
                   
Annual Sum or Average 0.273064E+10 0.270933E+10 0.00 0.273312E+09 0.00 0.00 0.316391E+11 0.00 1.76
Minimum of Months 0.00 0.00 0.00 9878315.78 0.00 0.00 0.198228E+09 0.00 1.74
Maximum of Months 0.130014E+10 0.945581E+09 0.00 30310458.56 0.00 0.00 0.494752E+10 0.00 1.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: EXERCISECENTERFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.734095E+10 0.00 0.00 0.00 0.00 0.112347E+10 0.00 0.00 2.52
February 0.598569E+10 0.00 0.00 0.00 0.00 0.625521E+09 0.00 0.00 2.52
March 0.532348E+10 0.00 0.00 428148.89 0.00 26152009.77 0.153895E+09 0.00 2.53
April 0.354063E+10 49316495.41 0.00 1827957.22 0.00 0.00 0.362624E+09 0.00 2.53
May 0.140419E+10 44189770.25 0.00 6618439.49 0.00 0.00 0.110719E+10 0.00 2.55
June 0.632503E+09 0.477010E+09 0.00 6637501.72 0.00 0.00 0.671535E+09 0.00 2.56
July 0.273119E+09 0.613842E+09 0.00 6829489.75 0.00 0.00 0.449078E+09 0.00 2.56
August 0.412608E+09 0.542698E+09 0.00 8250811.39 0.00 0.00 0.561928E+09 0.00 2.56
September 0.126190E+10 0.110071E+09 0.00 6746941.00 0.00 0.00 0.964532E+09 0.00 2.55
October 0.337985E+10 0.00 0.00 1499965.83 0.00 0.00 0.619265E+09 0.00 2.53
November 0.512513E+10 0.00 0.00 382087.96 0.00 49196062.02 0.271571E+09 0.00 2.53
December 0.693568E+10 0.00 0.00 0.00 0.00 0.359252E+09 0.00 0.00 2.51
                   
Annual Sum or Average 0.416157E+11 0.183713E+10 0.00 39221343.24 0.00 0.218359E+10 0.516162E+10 0.00 2.54
Minimum of Months 0.273119E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.51
Maximum of Months 0.734095E+10 0.613842E+09 0.00 8250811.39 0.00 0.112347E+10 0.110719E+10 0.00 2.56



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FRONTOFFICEFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.513220E+10 0.00 0.00 0.00 0.00 0.195726E+10 0.00 0.00 0.52
February 0.441943E+10 0.00 0.00 12498.97 0.00 0.113422E+10 12388668.97 0.00 0.53
March 0.442197E+10 0.00 0.00 752800.40 0.00 69804626.75 0.243312E+09 0.00 0.53
April 0.277514E+10 57014509.48 0.00 3283019.23 0.00 0.00 0.674907E+09 0.00 0.53
May 0.670938E+09 62968317.89 0.00 11553195.19 0.00 0.00 0.148999E+10 0.00 0.53
June 0.171633E+09 0.545915E+09 0.00 11051396.69 0.00 0.00 0.860596E+09 0.00 0.53
July 0.00 0.773707E+09 0.00 8918078.53 0.00 0.00 0.419239E+09 0.00 0.53
August 0.00 0.661992E+09 0.00 12048947.74 0.00 0.00 0.652510E+09 0.00 0.53
September 0.465973E+09 0.124793E+09 0.00 13682709.61 0.00 0.00 0.147273E+10 0.00 0.53
October 0.218528E+10 0.00 0.00 6141028.75 0.00 0.00 0.147843E+10 0.00 0.53
November 0.399585E+10 0.00 0.00 2245124.57 0.00 0.115526E+09 0.572296E+09 0.00 0.53
December 0.545545E+10 0.00 0.00 0.00 0.00 0.661801E+09 0.00 0.00 0.52
                   
Annual Sum or Average 0.296939E+11 0.222639E+10 0.00 69688799.68 0.00 0.393861E+10 0.787641E+10 0.00 0.53
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.52
Maximum of Months 0.545545E+10 0.773707E+09 0.00 13682709.61 0.00 0.195726E+10 0.148999E+10 0.00 0.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FRONTSTAIRSFLR1

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: REARSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDORFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.309285E+10 0.00 0.00 0.00 0.00 0.901975E+09 0.00 0.00 0.40
February 0.241256E+10 0.00 0.00 0.00 0.00 0.689021E+09 0.00 0.00 0.40
March 0.251481E+10 0.00 0.00 196966.16 0.00 0.00 42444592.84 0.00 0.41
April 0.154458E+10 58054871.00 0.00 2535461.28 0.00 0.00 0.267570E+09 0.00 0.41
May 0.237133E+09 81345861.47 0.00 9621593.32 0.00 0.00 0.743905E+09 0.00 0.41
June 81245049.10 0.523374E+09 0.00 6071960.87 0.00 0.00 0.350719E+09 0.00 0.41
July 0.00 0.771558E+09 0.00 4689622.73 0.00 0.00 0.117006E+09 0.00 0.41
August 0.00 0.639275E+09 0.00 6866419.80 0.00 0.00 0.219511E+09 0.00 0.41
September 0.348177E+09 0.146860E+09 0.00 8606964.97 0.00 0.00 0.557962E+09 0.00 0.41
October 0.154442E+10 4346.13 0.00 1826212.42 0.00 0.00 0.325579E+09 0.00 0.41
November 0.241462E+10 0.00 0.00 373574.19 0.00 0.00 0.120607E+09 0.00 0.40
December 0.283484E+10 0.00 0.00 0.00 0.00 0.570519E+09 0.00 0.00 0.40
                   
Annual Sum or Average 0.170252E+11 0.222047E+10 0.00 40788775.74 0.00 0.216152E+10 0.274530E+10 0.00 0.41
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.40
Maximum of Months 0.309285E+10 0.771558E+09 0.00 9621593.32 0.00 0.901975E+09 0.743905E+09 0.00 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM201

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 40533659.36 0.00 0.00 0.00 0.00 36525248.68 0.00 0.00 0.03
February 29504316.89 0.00 0.00 0.00 0.00 44431110.08 0.00 0.00 0.03
March 25229618.36 0.00 0.00 0.00 273207.02 0.00 0.00 0.00 0.02
April 19112195.17 0.00 0.00 0.00 1656253.03 0.00 0.00 0.00 0.02
May 8180762.40 7304.45 0.00 45.55 1190293.15 0.00 16.70 0.00 0.02
June 6268505.84 3538628.25 0.00 3205.32 2911359.07 0.00 11748.75 0.00 0.02
July 4290452.36 2785252.60 0.00 34584.37 4299387.36 0.00 135374.84 0.00 0.03
August 4295254.57 1033514.80 0.00 7306.77 4297353.18 0.00 45359.47 0.00 0.02
September 10991812.64 69669.94 0.00 78.91 2166977.73 0.00 19.41 0.00 0.02
October 16128445.70 0.00 0.00 0.00 581860.05 0.00 0.00 0.00 0.02
November 26868073.13 0.00 0.00 0.00 0.00 1870400.40 0.00 0.00 0.02
December 32698085.42 0.00 0.00 0.00 0.00 17474730.98 0.00 0.00 0.03
                   
Annual Sum or Average 0.224101E+09 7434370.04 0.00 45220.92 17376690.58 0.100301E+09 192519.17 0.00 0.03
Minimum of Months 4290452.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 40533659.36 3538628.25 0.00 34584.37 4299387.36 44431110.08 135374.84 0.00 0.03



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM202_205

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.301791E+09 0.00 0.00 497702.54 0.00 0.469910E+10 0.784885E+09 0.00 0.41
February 0.216747E+09 0.00 0.00 2240209.40 0.00 0.252101E+10 0.194127E+10 0.00 0.41
March 0.254265E+09 0.00 0.00 7215199.55 0.00 0.112870E+10 0.269677E+10 0.00 0.41
April 0.233345E+09 52913180.97 0.00 15483627.87 1446298.67 88162200.31 0.255609E+10 0.00 0.42
May 0.216579E+09 49521165.39 156192.91 26934588.61 3901975.60 3312453.15 0.128430E+10 6266.66 0.42
June 0.112009E+09 0.543757E+09 149095.09 20150472.49 21019693.23 1598695.16 0.521945E+09 6719.50 0.43
July 0.116721E+09 0.748639E+09 222687.17 16135935.28 44951937.93 94918.49 0.147106E+09 7400.21 0.43
August 0.151629E+09 0.580799E+09 290748.47 21388910.56 40467663.68 418615.62 0.266335E+09 9409.29 0.43
September 0.176076E+09 0.127063E+09 59785.10 23080958.12 3071109.20 4236964.95 0.123166E+10 2207.35 0.42
October 0.183143E+09 0.00 0.00 16887557.82 0.00 12965182.88 0.275372E+10 0.00 0.41
November 0.207254E+09 0.00 0.00 7747294.96 0.00 0.124437E+10 0.243708E+10 0.00 0.41
December 0.271301E+09 0.00 0.00 959592.82 0.00 0.342715E+10 0.148096E+10 0.00 0.41
                   
Annual Sum or Average 0.244086E+10 0.210269E+10 878508.75 0.158722E+09 0.114859E+09 0.131311E+11 0.181021E+11 32003.01 0.42
Minimum of Months 0.112009E+09 0.00 0.00 497702.54 0.00 94918.49 0.147106E+09 0.00 0.41
Maximum of Months 0.301791E+09 0.748639E+09 290748.47 26934588.61 44951937.93 0.469910E+10 0.275372E+10 9409.29 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM206_208

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.238188E+09 0.00 0.00 940514.46 0.00 0.311895E+10 0.116532E+10 0.00 0.40
February 0.195358E+09 0.00 0.00 3042900.36 0.00 0.157055E+10 0.187526E+10 0.00 0.40
March 0.195168E+09 0.00 0.00 7427653.22 0.00 0.382681E+09 0.258245E+10 0.00 0.41
April 0.174173E+09 43454885.78 6377.26 13469868.00 1257938.31 9222028.32 0.203732E+10 1600.53 0.41
May 0.162804E+09 41537023.40 131173.32 21294013.14 3458158.51 1928673.43 0.990279E+09 7035.88 0.41
June 81049753.80 0.434269E+09 240446.81 15310067.63 17986368.65 1188076.92 0.401945E+09 9435.96 0.42
July 85796608.28 0.597992E+09 412589.70 11846043.71 38158087.18 182680.13 0.109311E+09 10391.90 0.43
August 0.111816E+09 0.464946E+09 198198.25 15898005.48 33941327.03 378549.20 0.203499E+09 8567.83 0.42
September 0.133876E+09 0.103679E+09 32654.23 17998943.98 2705163.90 3042986.91 0.953192E+09 2516.21 0.42
October 0.136082E+09 0.00 0.00 14065463.60 0.00 8870890.09 0.213711E+10 0.00 0.41
November 0.156012E+09 0.00 0.00 7289391.26 0.00 0.688044E+09 0.217276E+10 0.00 0.40
December 0.214055E+09 0.00 0.00 1728846.98 0.00 0.203936E+10 0.178756E+10 0.00 0.40
                   
Annual Sum or Average 0.188438E+10 0.168588E+10 1021439.57 0.130312E+09 97507043.58 0.782440E+10 0.164160E+11 39548.32 0.41
Minimum of Months 81049753.80 0.00 0.00 940514.46 0.00 182680.13 0.109311E+09 0.00 0.40
Maximum of Months 0.238188E+09 0.597992E+09 412589.70 21294013.14 38158087.18 0.311895E+10 0.258245E+10 10391.90 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM209_212

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.309749E+09 0.00 0.00 2428804.69 0.00 0.248736E+10 0.297778E+10 0.00 0.41
February 0.251746E+09 0.00 0.00 4853045.91 0.00 0.127120E+10 0.313282E+10 0.00 0.41
March 0.254526E+09 0.00 0.00 9968199.75 0.00 0.113188E+09 0.369141E+10 0.00 0.41
April 0.239534E+09 48091469.47 0.00 16366266.00 1365812.68 15619085.41 0.262081E+10 0.00 0.42
May 0.230634E+09 43139736.07 0.00 26309309.62 3374115.95 3755061.97 0.131010E+10 0.00 0.42
June 0.122442E+09 0.501287E+09 59508.09 20265736.11 19304847.31 1849235.16 0.541831E+09 1056.27 0.43
July 0.132471E+09 0.690855E+09 76578.50 17211011.20 41566503.97 160127.66 0.151053E+09 906.68 0.43
August 0.162597E+09 0.538487E+09 52229.14 22368988.99 37743136.73 585457.69 0.280690E+09 1711.39 0.43
September 0.181285E+09 0.115242E+09 16493.57 23171066.86 2844548.53 4284802.59 0.124547E+10 778.08 0.42
October 0.181123E+09 0.00 0.00 17728333.15 0.00 11669233.97 0.274749E+10 0.00 0.41
November 0.203269E+09 0.00 0.00 10342935.84 0.00 0.445288E+09 0.321629E+10 0.00 0.41
December 0.277676E+09 0.00 0.00 4001083.27 0.00 0.104692E+10 0.383964E+10 0.00 0.41
                   
Annual Sum or Average 0.254705E+10 0.193710E+10 204809.31 0.175015E+09 0.106199E+09 0.540188E+10 0.257554E+11 4452.42 0.42
Minimum of Months 0.122442E+09 0.00 0.00 2428804.69 0.00 160127.66 0.151053E+09 0.00 0.41
Maximum of Months 0.309749E+09 0.690855E+09 76578.50 26309309.62 41566503.97 0.248736E+10 0.383964E+10 1711.39 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM213

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 29155554.99 0.00 0.00 19021.59 0.00 0.140970E+10 14487342.09 0.00 0.41
February 40687361.67 0.00 0.00 116796.80 0.00 0.102454E+10 0.112184E+09 0.00 0.41
March 59331878.16 0.00 0.00 752017.96 0.00 0.642617E+09 0.330689E+09 0.00 0.41
April 64316988.67 11603996.67 1208.38 2404198.18 355240.08 0.178208E+09 0.496655E+09 68.52 0.41
May 72311790.21 10191605.39 19635.49 5377183.76 708455.86 955362.31 0.323661E+09 784.33 0.42
June 36142329.67 0.129908E+09 8354.40 4626880.35 5290854.60 436568.62 0.133684E+09 386.91 0.42
July 33207422.74 0.180334E+09 18027.44 3943215.27 11179781.21 16043.86 34206217.16 414.05 0.43
August 41364068.58 0.139077E+09 29364.81 5330908.75 10103994.94 65680.98 64209476.81 1409.99 0.43
September 51168099.36 31148309.55 0.00 5106064.45 816201.59 1081522.89 0.308678E+09 0.00 0.42
October 55255390.57 0.00 0.00 2925867.47 0.00 4321699.84 0.702121E+09 0.00 0.41
November 46558401.32 0.00 0.00 1087759.45 0.00 0.622913E+09 0.316617E+09 0.00 0.41
December 50067584.37 0.00 0.00 32265.54 0.00 0.121809E+10 29147360.42 0.00 0.41
                   
Annual Sum or Average 0.579567E+09 0.502263E+09 76590.53 31722179.57 28454528.27 0.510295E+10 0.286634E+10 3063.80 0.42
Minimum of Months 29155554.99 0.00 0.00 19021.59 0.00 16043.86 14487342.09 0.00 0.41
Maximum of Months 72311790.21 0.180334E+09 29364.81 5377183.76 11179781.21 0.140970E+10 0.702121E+09 1409.99 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM214

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 79063522.21 0.00 0.00 788289.98 0.00 0.702562E+09 0.667198E+09 0.00 0.41
February 64025050.76 0.00 0.00 1639408.26 0.00 0.349364E+09 0.748352E+09 0.00 0.41
March 56480452.99 0.00 0.00 3351781.63 0.00 35793332.85 0.908091E+09 0.00 0.41
April 42600596.90 15117122.16 24425.84 5061727.97 403183.79 2204205.34 0.649155E+09 200.46 0.42
May 40776247.23 17438408.89 488.51 7925982.10 1333773.93 387775.47 0.298988E+09 10.87 0.42
June 19164568.07 0.153391E+09 25204.28 5301316.38 6227694.60 142075.12 0.118504E+09 169.98 0.43
July 17728633.55 0.219103E+09 65846.81 3758874.57 12147296.47 13539.23 30695723.48 460.67 0.43
August 24755327.69 0.172408E+09 73259.03 5278113.33 10812611.86 74849.14 59642650.18 399.49 0.43
September 29688396.40 41642581.91 2639.63 7038379.48 909178.00 652125.26 0.294788E+09 85.44 0.43
October 20384255.45 0.00 0.00 5909201.62 0.00 2103146.36 0.679541E+09 0.00 0.42
November 46390994.54 0.00 0.00 3376448.48 0.00 0.108662E+09 0.793813E+09 0.00 0.41
December 70974035.00 0.00 0.00 1389242.93 0.00 0.264776E+09 0.959735E+09 0.00 0.41
                   
Annual Sum or Average 0.512032E+09 0.619099E+09 191864.11 50818766.73 31833738.66 0.146673E+10 0.620851E+10 1326.90 0.42
Minimum of Months 17728633.55 0.00 0.00 788289.98 0.00 13539.23 30695723.48 0.00 0.41
Maximum of Months 79063522.21 0.219103E+09 73259.03 7925982.10 12147296.47 0.702562E+09 0.959735E+09 460.67 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM215_218

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 10417054.14 0.00 0.00 10881002.87 0.00 0.00 0.453126E+09 0.00 0.04
February 25558237.44 0.00 0.00 12448924.52 0.00 0.00 0.481046E+09 0.00 0.05
March 0.00 193149.89 0.00 18188774.34 0.00 0.00 0.309826E+09 0.00 0.05
April 0.00 14538117.99 0.00 20998994.59 0.00 0.00 0.240018E+09 0.00 0.05
May 0.00 20365254.71 0.00 25486121.06 0.00 0.00 0.125551E+09 0.00 0.06
June 0.00 0.114704E+09 0.00 15130552.38 0.00 0.00 59979694.11 0.00 0.07
July 0.00 0.165653E+09 0.00 7704304.42 0.00 0.00 14675965.68 0.00 0.07
August 0.00 0.140546E+09 0.00 11827466.60 0.00 0.00 25316966.23 0.00 0.07
September 0.00 25829490.70 0.00 24063273.93 0.00 0.00 0.133662E+09 0.00 0.06
October 0.00 0.00 0.00 23445139.89 0.00 0.00 0.244365E+09 0.00 0.05
November 0.00 83.43 0.00 16978162.24 0.00 0.00 0.306546E+09 0.00 0.05
December 10998883.22 0.00 0.00 12528706.48 0.00 0.00 0.355781E+09 0.00 0.04
                   
Annual Sum or Average 46974174.80 0.481829E+09 0.00 0.199681E+09 0.00 0.00 0.274989E+10 0.00 0.06
Minimum of Months 0.00 0.00 0.00 7704304.42 0.00 0.00 14675965.68 0.00 0.04
Maximum of Months 25558237.44 0.165653E+09 0.00 25486121.06 0.00 0.00 0.481046E+09 0.00 0.07



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM219

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 42268134.64 0.00 0.00 0.148661E+10 0.00 0.43
February 0.00 0.00 0.00 49170832.14 0.00 0.00 0.120603E+10 0.00 0.44
March 2570643.63 4964.04 0.00 29981548.65 853.80 0.00 0.934065E+09 0.00 0.43
April 5354088.23 23510236.09 0.00 28655809.19 457008.00 0.00 0.612840E+09 0.00 0.43
May 10202943.20 40493096.35 0.00 24245473.06 1782689.90 0.00 0.243071E+09 0.00 0.43
June 5683072.67 0.216188E+09 0.00 13232334.10 6438385.48 0.00 74300780.17 0.00 0.44
July 6033901.39 0.319787E+09 0.00 5073889.53 12102446.43 0.00 16567110.96 0.00 0.44
August 7760869.32 0.259743E+09 0.00 9055522.20 10949151.25 0.00 37538972.45 0.00 0.44
September 11675429.31 68447626.72 0.00 22348390.50 1132015.47 0.00 0.249345E+09 0.00 0.43
October 3200542.00 49872.51 0.00 32080093.51 6930.69 0.00 0.613002E+09 0.00 0.43
November 334376.17 0.00 0.00 30203974.50 0.00 0.00 0.881271E+09 0.00 0.43
December 0.00 0.00 0.00 28043948.75 0.00 0.00 0.126792E+10 0.00 0.42
                   
Annual Sum or Average 52815865.91 0.928223E+09 0.00 0.314360E+09 32869481.01 0.00 0.762255E+10 0.00 0.43
Minimum of Months 0.00 0.00 0.00 5073889.53 0.00 0.00 16567110.96 0.00 0.42
Maximum of Months 11675429.31 0.319787E+09 0.00 49170832.14 12102446.43 0.00 0.148661E+10 0.00 0.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM220_223

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.315249E+09 0.00 0.00 3918358.09 0.00 0.156262E+10 0.389923E+10 0.00 0.41
February 0.256040E+09 0.00 0.00 6130660.93 0.00 0.906654E+09 0.349159E+10 0.00 0.41
March 0.233822E+09 0.00 0.00 11957189.85 0.00 26781849.80 0.377954E+10 0.00 0.41
April 0.202300E+09 50697148.25 20501.97 17570984.91 1355900.49 15245015.93 0.263304E+10 131.55 0.42
May 0.187510E+09 50617078.03 134537.24 29096802.04 4108205.43 3562323.48 0.128363E+10 4880.26 0.42
June 0.101455E+09 0.520164E+09 55944.49 20888063.19 20023595.18 1810333.95 0.524641E+09 8016.28 0.43
July 0.100663E+09 0.726755E+09 150138.46 17478503.13 40505847.35 140955.32 0.144171E+09 5699.42 0.43
August 0.140834E+09 0.564318E+09 105030.71 22459358.35 37342630.73 464776.73 0.270736E+09 8063.68 0.43
September 0.155687E+09 0.124674E+09 70391.88 25317243.62 2605959.66 4323548.49 0.123871E+10 584.81 0.42
October 0.140356E+09 0.00 0.00 18811172.85 0.00 11267897.54 0.276130E+10 0.00 0.42
November 0.195419E+09 0.00 0.00 11306643.09 0.00 0.237478E+09 0.341920E+10 0.00 0.41
December 0.280351E+09 0.00 0.00 5412257.22 0.00 0.616932E+09 0.426906E+10 0.00 0.41
                   
Annual Sum or Average 0.230969E+10 0.203723E+10 536544.76 0.190347E+09 0.105942E+09 0.338728E+10 0.277149E+11 27375.99 0.42
Minimum of Months 0.100663E+09 0.00 0.00 3918358.09 0.00 140955.32 0.144171E+09 0.00 0.41
Maximum of Months 0.315249E+09 0.726755E+09 150138.46 29096802.04 40505847.35 0.156262E+10 0.426906E+10 8063.68 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM224

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 70284553.09 0.00 0.00 91127.34 0.00 0.124877E+10 0.130201E+09 0.00 0.41
February 49125725.24 0.00 0.00 370732.12 0.00 0.766458E+09 0.359344E+09 0.00 0.41
March 62600417.10 0.00 0.00 1614331.75 0.00 0.330247E+09 0.629105E+09 0.00 0.41
April 55088247.95 13147102.32 46851.17 3508811.98 362956.31 44709015.99 0.619347E+09 822.27 0.41
May 46973655.74 14215932.87 44888.81 6826580.11 1123543.59 571646.77 0.310382E+09 1161.23 0.42
June 25373282.52 0.143039E+09 76308.51 5018617.58 5934287.55 244779.99 0.122297E+09 1055.77 0.43
July 24176929.26 0.202300E+09 151585.60 3887416.18 11772097.38 59086.12 28986670.12 1483.89 0.43
August 34098271.60 0.156346E+09 168097.55 5261136.09 10629471.30 54394.04 57540342.47 2343.07 0.43
September 41989733.11 36172912.95 63520.35 6184051.28 805409.96 747793.01 0.295807E+09 1037.28 0.42
October 45499832.58 0.00 0.00 4244286.34 0.00 2861766.03 0.684177E+09 0.00 0.41
November 52371307.67 0.00 0.00 1885718.85 0.00 0.340987E+09 0.578970E+09 0.00 0.41
December 61638682.01 0.00 0.00 161164.40 0.00 0.988076E+09 0.248324E+09 0.00 0.41
                   
Annual Sum or Average 0.569221E+09 0.565221E+09 551251.99 39053974.02 30627766.09 0.372378E+10 0.406448E+10 7903.52 0.42
Minimum of Months 24176929.26 0.00 0.00 91127.34 0.00 54394.04 28986670.12 0.00 0.41
Maximum of Months 70284553.09 0.202300E+09 168097.55 6826580.11 11772097.38 0.124877E+10 0.684177E+09 2343.07 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FRONTSTAIRSFLR2

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: REARSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDORFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.399142E+10 0.00 0.00 0.40
February 0.162062E+09 0.00 0.00 0.00 0.00 0.291920E+10 0.00 0.00 0.40
March 0.807701E+09 0.00 0.00 0.00 1203.13 0.166987E+10 0.00 0.00 0.40
April 0.132210E+10 49741805.87 0.00 463442.84 854789.13 0.341322E+09 44313288.39 0.00 0.40
May 0.873865E+09 65915960.47 0.00 1757863.54 203549.32 0.00 0.143609E+09 0.00 0.41
June 0.295063E+09 0.523024E+09 0.00 2538951.11 0.00 0.00 0.136643E+09 0.00 0.41
July 25250406.46 0.773184E+09 0.00 2376967.52 0.00 0.00 0.121778E+09 0.00 0.41
August 72894287.74 0.580260E+09 0.00 2973891.41 3539.58 0.00 0.183297E+09 0.00 0.41
September 0.716115E+09 0.146387E+09 0.00 2282085.39 928.75 0.00 0.148085E+09 0.00 0.41
October 0.168506E+10 0.00 0.00 0.00 74450.91 0.00 0.00 0.00 0.40
November 0.572915E+09 0.00 0.00 0.00 0.00 0.187130E+10 0.00 0.00 0.40
December 7483971.83 0.00 0.00 0.00 0.00 0.339298E+10 0.00 0.00 0.40
                   
Annual Sum or Average 0.654051E+10 0.213851E+10 0.00 12393201.81 1138460.81 0.141861E+11 0.777725E+09 0.00 0.41
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.40
Maximum of Months 0.168506E+10 0.773184E+09 0.00 2973891.41 854789.13 0.399142E+10 0.183297E+09 0.00 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM301

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 10841512.29 0.00 0.00 0.00 0.00 0.186266E+09 0.00 0.00 0.08
February 18275280.00 0.00 0.00 0.00 0.00 0.113640E+09 0.00 0.00 0.06
March 22871499.43 0.00 0.00 0.00 332984.35 3296271.59 0.00 0.00 0.02
April 17390707.45 0.00 0.00 0.00 1795680.49 0.00 0.00 0.00 0.02
May 7142309.55 7716.84 0.00 29.57 1271209.77 0.00 42.04 0.00 0.02
June 5627024.51 2651902.37 0.00 2052.34 3748965.66 0.00 3144.68 0.00 0.03
July 4283355.96 1764887.01 0.00 16171.15 5107480.95 0.00 92023.81 0.00 0.03
August 3998869.58 572754.71 0.00 1547.26 4681557.05 0.00 15891.82 0.00 0.02
September 9537956.12 15707.16 0.00 1.51 2297640.42 0.00 0.00 0.00 0.02
October 13779004.78 0.00 0.00 0.00 846716.07 0.00 0.00 0.00 0.02
November 17682929.05 0.00 0.00 0.00 0.00 31525108.96 0.00 0.00 0.03
December 21058508.71 0.00 0.00 0.00 0.00 78683133.30 0.00 0.00 0.05
                   
Annual Sum or Average 0.152489E+09 5012968.10 0.00 19801.84 20082234.77 0.413411E+09 111102.34 0.00 0.03
Minimum of Months 3998869.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 22871499.43 2651902.37 0.00 16171.15 5107480.95 0.186266E+09 92023.81 0.00 0.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM302_305

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.180923E+09 0.00 0.00 0.00 0.00 29943187.31 0.00 0.00 0.02
February 0.136707E+09 0.00 0.00 0.00 0.00 73058037.96 0.00 0.00 0.03
March 99138306.81 0.00 0.00 0.00 1769868.74 0.00 0.00 0.00 0.02
April 77201175.68 27564.41 0.00 0.00 8664011.13 0.00 0.00 0.00 0.02
May 33434898.65 68380.10 0.00 332.40 7760936.67 0.00 392.56 0.00 0.02
June 27092873.03 15274194.12 0.00 36178.74 14266624.25 0.00 319876.59 0.00 0.03
July 16618527.12 13118701.81 0.00 165247.82 20146715.08 0.00 1295523.80 0.00 0.03
August 19023092.16 4013144.74 0.00 44572.87 20651154.94 0.00 527921.97 0.00 0.02
September 43481233.21 252365.29 0.00 424.35 10001337.12 0.00 1309.90 0.00 0.02
October 60961101.60 0.00 0.00 0.00 3761714.12 0.00 0.00 0.00 0.02
November 0.104461E+09 0.00 0.00 0.00 0.00 402114.57 0.00 0.00 0.02
December 0.142632E+09 0.00 0.00 0.00 0.00 20133989.03 0.00 0.00 0.02
                   
Annual Sum or Average 0.941674E+09 32754350.47 0.00 246756.18 87022362.04 0.123537E+09 2145024.83 0.00 0.02
Minimum of Months 16618527.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 0.180923E+09 15274194.12 0.00 165247.82 20651154.94 73058037.96 1295523.80 0.00 0.03



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM306_308

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.148040E+09 0.00 0.00 0.00 0.00 1749366.41 0.00 0.00 0.02
February 0.111123E+09 0.00 0.00 0.00 0.00 18276851.49 0.00 0.00 0.02
March 81300917.92 0.00 0.00 0.00 1233687.01 0.00 0.00 0.00 0.02
April 63020329.60 52890.03 0.00 0.00 6619737.85 0.00 0.00 0.00 0.02
May 27270578.47 161679.92 0.00 152.81 6067694.64 0.00 3.52 0.00 0.02
June 21440507.42 12224409.61 0.00 67800.47 11635368.91 0.00 475061.26 0.00 0.03
July 12977591.80 11056709.91 0.00 180283.80 16189980.59 0.00 952469.04 0.00 0.03
August 15020160.01 3524962.98 0.00 66070.27 16542725.50 0.00 586213.91 0.00 0.02
September 35251638.61 352342.47 0.00 5862.95 7725062.77 0.00 46639.12 0.00 0.02
October 49989827.01 0.00 0.00 0.00 2739823.83 0.00 0.00 0.00 0.02
November 84949015.72 0.00 0.00 0.00 0.00 300339.62 0.00 0.00 0.02
December 0.121641E+09 0.00 0.00 0.00 0.00 1026643.07 0.00 0.00 0.02
                   
Annual Sum or Average 0.772024E+09 27372994.91 0.00 320170.30 68754081.11 21353200.59 2060386.86 0.00 0.02
Minimum of Months 12977591.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 0.148040E+09 12224409.61 0.00 180283.80 16542725.50 18276851.49 952469.04 0.00 0.03



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM309_312

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.300446E+09 0.00 0.00 770209.68 0.00 0.437434E+10 0.108904E+10 0.00 0.41
February 0.225739E+09 0.00 0.00 2694410.02 0.00 0.224039E+10 0.219058E+10 0.00 0.41
March 0.252760E+09 0.00 0.00 7238535.65 0.00 0.735777E+09 0.308899E+10 0.00 0.41
April 0.255172E+09 47457130.13 0.00 14311947.72 1377942.83 64292331.17 0.258731E+10 0.00 0.41
May 0.253891E+09 41645970.10 0.00 25440485.80 3177400.79 3845795.77 0.132502E+10 0.00 0.42
June 0.137217E+09 0.491385E+09 77121.96 20143341.69 18427911.13 1836410.26 0.556783E+09 597.04 0.43
July 0.139708E+09 0.670218E+09 6460.78 17734254.12 39946398.54 184934.86 0.155586E+09 10.62 0.43
August 0.169700E+09 0.512986E+09 0.00 23003523.94 36013775.56 378791.53 0.291632E+09 0.00 0.43
September 0.204644E+09 0.107145E+09 0.00 21226607.72 2727902.53 5660365.83 0.127733E+10 0.00 0.42
October 0.221078E+09 0.00 0.00 13545326.20 0.00 18589713.59 0.279457E+10 0.00 0.41
November 0.217797E+09 0.00 0.00 6395922.75 0.00 0.117205E+10 0.253085E+10 0.00 0.41
December 0.270339E+09 0.00 0.00 1298690.57 0.00 0.316430E+10 0.172220E+10 0.00 0.41
                   
Annual Sum or Average 0.264849E+10 0.187084E+10 83582.74 0.153803E+09 0.101671E+09 0.117816E+11 0.196099E+11 607.66 0.42
Minimum of Months 0.137217E+09 0.00 0.00 770209.68 0.00 184934.86 0.155586E+09 0.00 0.41
Maximum of Months 0.300446E+09 0.670218E+09 77121.96 25440485.80 39946398.54 0.437434E+10 0.308899E+10 597.04 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM313

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 34667157.23 0.00 0.00 0.00 0.00 43857536.69 0.00 0.00 0.03
February 28444347.78 0.00 0.00 0.00 0.00 38906064.19 0.00 0.00 0.03
March 24300200.19 0.00 0.00 0.00 499576.67 0.00 0.00 0.00 0.02
April 18730718.66 0.00 0.00 0.00 2454308.41 0.00 0.00 0.00 0.02
May 7677099.48 0.00 0.00 0.00 2531452.73 0.00 0.00 0.00 0.02
June 6782658.98 26970.39 0.00 240.23 5816779.25 0.00 1476.80 0.00 0.02
July 5331852.01 98107.07 0.00 108.17 5686476.85 0.00 0.00 0.00 0.02
August 5059097.70 0.00 0.00 0.00 5733746.14 0.00 0.00 0.00 0.02
September 10617817.75 0.00 0.00 0.00 2623848.38 0.00 0.00 0.00 0.02
October 14910640.84 0.00 0.00 0.00 1052909.68 0.00 0.00 0.00 0.02
November 24241787.31 0.00 0.00 0.00 0.00 3648959.03 0.00 0.00 0.02
December 29557111.43 0.00 0.00 0.00 0.00 25767031.33 0.00 0.00 0.03
                   
Annual Sum or Average 0.210320E+09 125077.46 0.00 348.40 26399098.11 0.112180E+09 1476.80 0.00 0.03
Minimum of Months 5059097.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 34667157.23 98107.07 0.00 240.23 5816779.25 43857536.69 1476.80 0.00 0.03



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM314

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 41724570.59 0.00 0.00 48018.58 0.00 0.136488E+10 40741567.77 0.00 0.41
February 44759203.51 0.00 0.00 269525.25 0.00 0.894868E+09 0.232503E+09 0.00 0.41
March 61379293.03 0.00 0.00 1359966.87 0.00 0.462289E+09 0.496147E+09 0.00 0.41
April 54030926.51 14316753.03 0.00 3392029.37 381262.44 91329123.79 0.574611E+09 0.00 0.41
May 47973152.05 15554557.31 13392.33 7050648.56 1176151.59 871299.63 0.312095E+09 575.72 0.42
June 25107887.58 0.148860E+09 10039.90 5149585.43 5803243.18 427242.46 0.126341E+09 794.76 0.43
July 22526911.03 0.209709E+09 5125.67 4134778.31 11387676.70 13484.50 30559677.08 449.16 0.43
August 30766726.66 0.161462E+09 13965.07 5620742.96 10139994.73 56166.83 60847067.37 361.52 0.43
September 43390878.62 38135840.45 0.00 6020653.77 836261.75 1136958.21 0.302039E+09 116.70 0.42
October 50881473.53 0.00 0.00 3447523.09 0.00 3156819.53 0.695099E+09 0.00 0.41
November 50348695.07 0.00 0.00 1267690.49 0.00 0.557680E+09 0.371429E+09 0.00 0.41
December 53675696.63 0.00 0.00 74661.52 0.00 0.116499E+10 75321001.31 0.00 0.41
                   
Annual Sum or Average 0.526565E+09 0.588039E+09 42522.97 37835824.21 29724590.39 0.454169E+10 0.331773E+10 2297.85 0.42
Minimum of Months 22526911.03 0.00 0.00 48018.58 0.00 13484.50 30559677.08 0.00 0.41
Maximum of Months 61379293.03 0.209709E+09 13965.07 7050648.56 11387676.70 0.136488E+10 0.695099E+09 794.76 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM315_318

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.321121E+09 0.00 0.00 11565256.65 0.00 25322071.01 0.540667E+10 0.00 0.41
February 0.242750E+09 0.00 0.00 13726135.34 0.00 19541468.56 0.431828E+10 0.00 0.41
March 0.185793E+09 0.00 0.00 20931658.15 0.00 15145556.46 0.372785E+10 0.00 0.42
April 0.121185E+09 63127514.65 19177.19 25299516.18 1586680.87 7834257.90 0.260363E+10 745.79 0.42
May 0.123504E+09 73796154.11 170973.06 34775864.78 5563154.03 764367.63 0.122732E+10 1460.18 0.43
June 69524880.70 0.609892E+09 195935.22 22181852.19 23590385.71 491282.72 0.478826E+09 2994.30 0.43
July 68465633.91 0.863097E+09 307581.26 15584918.58 46556448.25 80035.85 0.128790E+09 2151.01 0.44
August 94701304.90 0.677165E+09 673640.58 21533929.40 42408214.53 157859.52 0.251968E+09 5291.58 0.44
September 0.112536E+09 0.158761E+09 177264.78 29079784.75 3242170.90 1845983.05 0.120131E+10 2954.89 0.43
October 48438643.82 0.00 0.00 25589452.88 0.00 6351025.95 0.274428E+10 0.00 0.42
November 0.167465E+09 0.00 0.00 18228501.28 0.00 16219286.69 0.356584E+10 0.00 0.42
December 0.283147E+09 0.00 0.00 13178624.90 0.00 23258343.87 0.482330E+10 0.00 0.41
                   
Annual Sum or Average 0.183863E+10 0.244584E+10 1544572.10 0.251675E+09 0.122947E+09 0.117012E+09 0.304781E+11 15597.75 0.42
Minimum of Months 48438643.82 0.00 0.00 11565256.65 0.00 80035.85 0.128790E+09 0.00 0.41
Maximum of Months 0.321121E+09 0.863097E+09 673640.58 34775864.78 46556448.25 25322071.01 0.540667E+10 5291.58 0.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM319

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 54005859.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
February 41344959.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
March 31482311.77 0.00 0.00 0.00 242205.11 0.00 0.00 0.00 0.02
April 23650538.73 569375.53 0.00 94.52 1324516.97 0.00 675.06 0.00 0.02
May 10705469.93 871295.23 0.00 15129.08 1143226.09 0.00 36440.34 0.00 0.02
June 6598663.15 8611651.42 0.00 104779.26 997443.25 0.00 1048984.35 0.00 0.03
July 2555175.63 8780365.59 0.00 138806.06 2418805.44 0.00 1350676.66 0.00 0.03
August 3520056.75 5428669.27 0.00 72312.60 2659474.53 0.00 1168074.00 0.00 0.02
September 13640535.47 1768330.44 0.00 4479.12 656037.98 0.00 19111.13 0.00 0.02
October 19980733.94 0.00 0.00 0.00 405801.81 0.00 0.00 0.00 0.02
November 32578566.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
December 45444229.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
                   
Annual Sum or Average 0.285507E+09 26029687.49 0.00 335600.64 9847511.17 0.00 3623961.55 0.00 0.02
Minimum of Months 2555175.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 54005859.20 8780365.59 0.00 138806.06 2659474.53 0.00 1350676.66 0.00 0.03



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM320_323

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.307161E+09 0.00 0.00 1782391.85 0.00 0.315599E+10 0.229764E+10 0.00 0.41
February 0.250318E+09 0.00 0.00 3971869.03 0.00 0.154964E+10 0.285184E+10 0.00 0.41
March 0.250128E+09 0.00 0.00 9385140.32 0.00 0.221157E+09 0.359103E+10 0.00 0.41
April 0.213821E+09 48394593.14 135630.51 15552925.26 1302879.98 16594536.12 0.265897E+10 593.74 0.42
May 0.207469E+09 47462298.08 23386.19 28004578.96 3703601.03 3750775.68 0.131780E+10 53.40 0.42
June 0.124009E+09 0.501800E+09 111364.36 21306622.30 18781221.45 1343724.85 0.541308E+09 370.16 0.43
July 0.117262E+09 0.693990E+09 638049.95 18923825.32 38616345.70 148617.28 0.143458E+09 2104.62 0.43
August 0.163387E+09 0.531646E+09 298103.73 23791085.88 36053118.79 388325.79 0.272343E+09 1198.86 0.43
September 0.194748E+09 0.114428E+09 110764.06 23737899.96 2386826.55 4672949.57 0.125795E+10 292.22 0.42
October 0.194112E+09 0.00 0.00 14937786.14 0.00 19009319.75 0.279798E+10 0.00 0.41
November 0.219644E+09 0.00 0.00 7735001.67 0.00 0.690869E+09 0.299656E+10 0.00 0.41
December 0.273139E+09 0.00 0.00 2665522.61 0.00 0.194607E+10 0.293342E+10 0.00 0.41
                   
Annual Sum or Average 0.251520E+10 0.193772E+10 1317298.80 0.171795E+09 0.100844E+09 0.760964E+10 0.236603E+11 4613.00 0.42
Minimum of Months 0.117262E+09 0.00 0.00 1782391.85 0.00 148617.28 0.143458E+09 0.00 0.41
Maximum of Months 0.307161E+09 0.693990E+09 638049.95 28004578.96 38616345.70 0.315599E+10 0.359103E+10 2104.62 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM324

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 47504489.39 0.00 0.00 0.00 0.00 111633.41 0.00 0.00 0.02
February 35382786.51 0.00 0.00 0.00 0.00 412387.09 0.00 0.00 0.02
March 26206567.27 0.00 0.00 0.00 380078.63 0.00 0.00 0.00 0.02
April 19852962.59 0.00 0.00 0.00 2363158.85 0.00 0.00 0.00 0.02
May 8278468.44 0.00 0.00 0.00 2275068.37 0.00 0.00 0.00 0.02
June 7087659.29 0.00 0.00 0.00 5691331.32 0.00 0.00 0.00 0.02
July 5638703.57 0.00 0.00 0.00 5483952.43 0.00 0.00 0.00 0.02
August 5084910.57 0.00 0.00 0.00 5742758.18 0.00 0.00 0.00 0.02
September 11135464.61 0.00 0.00 0.00 2701648.18 0.00 0.00 0.00 0.02
October 16068651.55 0.00 0.00 0.00 895032.02 0.00 0.00 0.00 0.02
November 27400270.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
December 39372013.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
                   
Annual Sum or Average 0.249013E+09 0.00 0.00 0.00 25533027.98 524020.51 0.00 0.00 0.02
Minimum of Months 5084910.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 47504489.39 0.00 0.00 0.00 5742758.18 412387.09 0.00 0.00 0.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FRONTSTAIRSFLR3

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: REARSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDORFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.399163E+10 0.00 0.00 0.40
February 27718471.41 0.00 0.00 0.00 0.00 0.305284E+10 0.00 0.00 0.40
March 0.272214E+09 0.00 0.00 0.00 0.00 0.220224E+10 0.00 0.00 0.40
April 0.563651E+09 52506573.08 0.00 751493.48 1691255.32 0.109868E+10 34209051.69 0.00 0.40
May 0.741831E+09 75450327.48 0.00 2878933.44 21077.41 80800196.94 0.138228E+09 0.00 0.41
June 0.390949E+09 0.454989E+09 0.00 2354816.47 48377.42 11710200.36 52844312.66 0.00 0.41
July 0.175435E+09 0.650303E+09 0.00 1940556.50 257601.10 0.00 54105177.37 0.00 0.41
August 0.262204E+09 0.513593E+09 0.00 2394930.83 1316793.91 0.00 64676504.38 0.00 0.41
September 0.587881E+09 0.124710E+09 0.00 2345365.22 358979.53 0.193573E+09 78990737.56 0.00 0.41
October 0.657433E+09 940.26 0.00 47175.01 0.00 0.100127E+10 3245699.34 0.00 0.40
November 0.208866E+09 0.00 0.00 0.00 0.00 0.222267E+10 0.00 0.00 0.40
December 0.00 0.00 0.00 0.00 0.00 0.340050E+10 0.00 0.00 0.40
                   
Annual Sum or Average 0.388818E+10 0.187155E+10 0.00 12713270.94 3694084.69 0.172559E+11 0.426300E+09 0.00 0.40
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.40
Maximum of Months 0.741831E+09 0.650303E+09 0.00 2878933.44 1691255.32 0.399163E+10 0.138228E+09 0.00 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM401

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 2907.52 0.00 0.148962E+10 417445.69 0.00 0.44
February 3428327.24 0.00 0.00 15583.11 0.00 0.117675E+10 4157507.40 0.00 0.43
March 24072264.39 0.00 0.00 320977.99 0.00 0.917270E+09 73250974.26 0.00 0.42
April 48535874.75 14487178.86 0.00 1715362.71 382042.29 0.514696E+09 0.171447E+09 0.00 0.42
May 57878976.19 14276653.34 5213.53 4682482.81 1239858.34 89330175.31 0.268075E+09 367.33 0.42
June 30892815.63 0.144388E+09 40515.86 3981704.62 5251276.14 27439384.57 0.125279E+09 1134.75 0.43
July 31080489.81 0.194554E+09 65938.43 3442430.15 11677443.84 28057.04 42995540.18 2160.94 0.44
August 38318991.88 0.147840E+09 32809.41 4461096.48 10179117.31 89714.93 78265503.96 922.98 0.43
September 51608948.31 33278509.52 0.00 3540958.95 892623.40 0.139152E+09 0.203426E+09 0.00 0.42
October 52385927.66 0.00 0.00 880657.66 0.00 0.563529E+09 0.171477E+09 0.00 0.41
November 15623752.44 0.00 0.00 256523.54 0.00 0.907395E+09 73797358.06 0.00 0.42
December 0.00 0.00 0.00 3288.09 0.00 0.130303E+10 588466.24 0.00 0.43
                   
Annual Sum or Average 0.353826E+09 0.548825E+09 144477.24 23303973.65 29622361.32 0.712832E+10 0.121318E+10 4585.99 0.43
Minimum of Months 0.00 0.00 0.00 2907.52 0.00 28057.04 417445.69 0.00 0.41
Maximum of Months 57878976.19 0.194554E+09 65938.43 4682482.81 11677443.84 0.148962E+10 0.268075E+09 2160.94 0.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM402_405

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 68885338.92 0.00 0.00 0.00 0.00 0.876452E+09 0.00 0.00 0.09
February 86047732.78 0.00 0.00 0.00 0.00 0.532524E+09 0.00 0.00 0.06
March 93445589.17 0.00 0.00 0.00 1422855.38 43197977.01 0.00 0.00 0.03
April 75180565.88 8271115.94 0.00 129884.46 1468095.38 1283800.08 2673512.81 0.00 0.02
May 34631797.21 6793025.15 0.00 430686.66 1972203.61 0.00 4625517.24 0.00 0.03
June 14234481.76 61587608.61 0.00 1151342.65 1793517.39 0.00 12177833.93 0.00 0.04
July 4738278.86 79481365.56 0.00 927073.67 1473577.22 0.00 7554163.32 0.00 0.04
August 3547294.18 48988620.45 0.00 945028.05 5265869.48 0.00 11435338.46 0.00 0.03
September 37443439.28 14249008.84 0.00 452713.05 0.00 0.00 7014195.82 0.00 0.03
October 61079085.67 0.00 0.00 0.00 2951758.25 0.00 0.00 0.00 0.02
November 75301103.88 0.00 0.00 0.00 0.00 0.171079E+09 0.00 0.00 0.04
December 81757036.37 0.00 0.00 0.00 0.00 0.443030E+09 0.00 0.00 0.06
                   
Annual Sum or Average 0.636292E+09 0.219371E+09 0.00 4036728.54 16347876.71 0.206757E+10 45480561.59 0.00 0.04
Minimum of Months 3547294.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 93445589.17 79481365.56 0.00 1151342.65 5265869.48 0.876452E+09 12177833.93 0.00 0.09



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM406_408

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 86121846.09 0.00 0.00 0.00 0.00 0.584834E+09 0.00 0.00 0.08
February 79145660.39 0.00 0.00 0.00 0.00 0.368171E+09 0.00 0.00 0.06
March 79198394.82 0.00 0.00 0.00 966878.79 17911223.82 0.00 0.00 0.02
April 60292893.03 6887404.78 0.00 142906.61 963774.26 215391.69 3611372.32 0.00 0.02
May 27796880.99 6624244.25 0.00 530985.02 807806.92 0.00 4582213.63 0.00 0.03
June 10829960.32 49676743.96 0.00 1104883.62 1541142.18 0.00 9923180.62 0.00 0.03
July 3060812.35 65230997.30 0.00 841078.37 891259.75 0.00 5981062.77 0.00 0.04
August 734753.04 40492921.83 0.00 891377.44 4269949.05 0.00 10529998.63 0.00 0.03
September 30140116.98 11690954.24 0.00 469308.68 0.00 0.00 5965193.76 0.00 0.03
October 50555416.09 0.00 0.00 0.00 2054400.72 0.00 0.00 0.00 0.02
November 70298527.57 0.00 0.00 0.00 0.00 0.106391E+09 0.00 0.00 0.03
December 69715827.06 0.00 0.00 0.00 0.00 0.292742E+09 0.00 0.00 0.05
                   
Annual Sum or Average 0.567891E+09 0.180603E+09 0.00 3980539.74 11495211.67 0.137026E+10 40593021.72 0.00 0.04
Minimum of Months 734753.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 86121846.09 65230997.30 0.00 1104883.62 4269949.05 0.584834E+09 10529998.63 0.00 0.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM409_412

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.109832E+09 0.00 0.00 158068.45 0.00 0.557052E+10 0.135348E+09 0.00 0.42
February 0.163902E+09 0.00 0.00 1184222.47 0.00 0.387080E+10 0.665061E+09 0.00 0.41
March 0.249715E+09 0.00 0.00 4916646.90 0.00 0.235386E+10 0.151093E+10 0.00 0.41
April 0.225771E+09 53660145.61 27063.05 11697199.65 1475258.89 0.861871E+09 0.186706E+10 2747.19 0.42
May 0.215728E+09 51124865.66 166121.41 22381671.56 4641544.02 35134593.55 0.139836E+10 3733.87 0.42
June 0.118711E+09 0.509955E+09 532169.18 17325394.84 18466806.69 2190415.90 0.613382E+09 11646.53 0.43
July 0.130714E+09 0.687122E+09 426298.11 15179050.96 42162889.74 200343.94 0.193257E+09 9957.30 0.43
August 0.157750E+09 0.527910E+09 699071.19 19097064.52 37761586.83 687486.32 0.341560E+09 14733.44 0.43
September 0.189550E+09 0.115455E+09 73922.27 17731124.75 3052109.81 0.102644E+09 0.127322E+10 5767.56 0.42
October 0.205515E+09 0.00 0.00 9684551.55 0.00 0.759643E+09 0.214627E+10 0.00 0.41
November 0.183965E+09 0.00 0.00 3573018.21 0.00 0.265689E+10 0.113394E+10 0.00 0.41
December 0.149312E+09 0.00 0.00 215548.99 0.00 0.485414E+10 0.189750E+09 0.00 0.41
                   
Annual Sum or Average 0.210047E+10 0.194523E+10 1924645.21 0.123144E+09 0.107560E+09 0.210686E+11 0.114681E+11 48585.89 0.42
Minimum of Months 0.109832E+09 0.00 0.00 158068.45 0.00 200343.94 0.135348E+09 0.00 0.41
Maximum of Months 0.249715E+09 0.687122E+09 699071.19 22381671.56 42162889.74 0.557052E+10 0.214627E+10 14733.44 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM413

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 10490653.86 0.00 0.00 0.00 0.00 0.228581E+09 0.00 0.00 0.09
February 17753202.10 0.00 0.00 0.00 0.00 0.133711E+09 0.00 0.00 0.06
March 21720502.07 0.00 0.00 0.00 419597.96 15222658.94 0.00 0.00 0.03
April 18652469.66 1582880.85 0.00 20048.27 761382.27 637230.37 129316.80 0.00 0.02
May 8608176.13 671052.69 0.00 43671.30 1569249.75 0.00 131296.12 0.00 0.02
June 5117277.08 11719781.17 0.00 184855.75 739338.56 0.00 1029929.39 0.00 0.03
July 1655377.39 14214142.80 0.00 186586.08 1544491.90 0.00 1478161.15 0.00 0.03
August 2374776.45 8752154.77 0.00 179251.86 2270990.60 0.00 1203809.29 0.00 0.03
September 9783776.26 3058668.33 0.00 93757.92 143990.87 0.00 1073994.71 0.00 0.03
October 15119214.98 0.00 0.00 0.00 831725.95 0.00 0.00 0.00 0.02
November 16281771.70 0.00 0.00 0.00 0.00 47410508.83 0.00 0.00 0.04
December 18243012.54 0.00 0.00 0.00 0.00 0.117036E+09 0.00 0.00 0.06
                   
Annual Sum or Average 0.145800E+09 39998680.62 0.00 708171.17 8280767.86 0.542598E+09 5046507.46 0.00 0.04
Minimum of Months 1655377.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 21720502.07 14214142.80 0.00 186586.08 2270990.60 0.228581E+09 1478161.15 0.00 0.09



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM414

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 21276139.70 0.00 0.00 0.00 0.00 0.118954E+09 0.00 0.00 0.05
February 25660229.20 0.00 0.00 0.00 0.00 71425962.00 0.00 0.00 0.04
March 25988356.29 0.00 0.00 0.00 279512.16 1620113.45 0.00 0.00 0.02
April 20179849.24 1571720.27 0.00 0.00 476061.73 0.00 0.00 0.00 0.02
May 9548617.23 1098862.77 0.00 0.00 1076287.06 0.00 0.00 0.00 0.02
June 5368515.30 12088682.88 0.00 35138.08 255581.49 0.00 1368564.65 0.00 0.03
July 2211776.59 12202231.48 0.00 37758.33 1894934.74 0.00 1434684.24 0.00 0.03
August 2543273.36 9143485.48 0.00 24582.16 1476053.17 0.00 1327292.13 0.00 0.03
September 11061475.38 2960166.50 0.00 7800.35 43267.18 0.00 853733.31 0.00 0.02
October 16573869.25 0.00 0.00 0.00 619232.75 0.00 0.00 0.00 0.02
November 23408555.63 0.00 0.00 0.00 0.00 17129781.81 0.00 0.00 0.03
December 26095963.91 0.00 0.00 0.00 0.00 49704268.31 0.00 0.00 0.04
                   
Annual Sum or Average 0.189917E+09 39065149.38 0.00 105278.92 6120930.28 0.258834E+09 4984274.33 0.00 0.03
Minimum of Months 2211776.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 26095963.91 12202231.48 0.00 37758.33 1894934.74 0.118954E+09 1434684.24 0.00 0.05



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM415_418

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.237814E+09 0.00 0.00 696878.64 0.00 0.483599E+10 0.717938E+09 0.00 0.41
February 0.212038E+09 0.00 0.00 2543921.21 0.00 0.297357E+10 0.149779E+10 0.00 0.41
March 0.212382E+09 0.00 0.00 8236432.18 0.00 0.137039E+10 0.249817E+10 0.00 0.42
April 0.158005E+09 57966663.57 22860.68 14921043.77 1419656.34 0.466172E+09 0.228006E+10 1822.61 0.42
May 0.134531E+09 62406246.63 191365.77 26957279.72 5375027.71 2997065.96 0.140841E+10 4002.43 0.43
June 85363702.24 0.543838E+09 483469.05 18635979.77 19774516.55 1700519.96 0.588144E+09 20382.30 0.43
July 85989860.08 0.752445E+09 709004.92 15987688.35 40139907.76 405402.02 0.187192E+09 28600.58 0.44
August 0.112546E+09 0.583113E+09 1130556.57 19861077.09 37038519.06 870645.27 0.340096E+09 28902.89 0.43
September 0.141125E+09 0.132808E+09 330070.25 21620244.49 2726123.00 26860672.19 0.132007E+10 13363.89 0.43
October 0.115973E+09 0.00 0.00 13333498.62 0.00 0.231940E+09 0.268310E+10 0.00 0.42
November 0.182465E+09 0.00 0.00 5744707.10 0.00 0.182478E+10 0.192454E+10 0.00 0.41
December 0.237046E+09 0.00 0.00 1058813.56 0.00 0.377128E+10 0.117724E+10 0.00 0.41
                   
Annual Sum or Average 0.191528E+10 0.213258E+10 2867327.23 0.149598E+09 0.106474E+09 0.155070E+11 0.166228E+11 97074.71 0.42
Minimum of Months 85363702.24 0.00 0.00 696878.64 0.00 405402.02 0.187192E+09 0.00 0.41
Maximum of Months 0.237814E+09 0.752445E+09 1130556.57 26957279.72 40139907.76 0.483599E+10 0.268310E+10 28902.89 0.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM419

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 58048130.31 0.00 0.00 108108.91 0.00 0.127285E+10 0.120078E+09 0.00 0.41
February 53598993.62 0.00 0.00 503338.12 0.00 0.816869E+09 0.302640E+09 0.00 0.41
March 54788553.99 0.00 0.00 1943820.31 0.00 0.377855E+09 0.585468E+09 0.00 0.41
April 39708901.04 15800556.97 8013.07 3865277.69 387701.73 0.117869E+09 0.559185E+09 21.39 0.42
May 33870653.27 17897334.76 6207.46 7137824.23 1446520.11 522927.53 0.329402E+09 277.00 0.43
June 20306772.46 0.150191E+09 13351.93 4768996.97 5683131.34 242673.74 0.134033E+09 269.69 0.43
July 19823111.96 0.209709E+09 52000.79 3749674.94 11306375.16 60495.72 37758386.90 2461.50 0.44
August 26562255.18 0.162991E+09 59105.08 4897036.59 10187759.97 94948.32 72233364.63 2551.98 0.43
September 33348863.90 38409786.72 42164.69 5632787.70 823827.99 4600125.65 0.316188E+09 1011.12 0.43
October 36131989.70 0.00 0.00 3513402.82 0.00 47208498.09 0.664558E+09 0.00 0.41
November 47638670.05 0.00 0.00 1408860.78 0.00 0.499316E+09 0.434063E+09 0.00 0.41
December 58632450.45 0.00 0.00 162423.84 0.00 0.105588E+10 0.185063E+09 0.00 0.41
                   
Annual Sum or Average 0.482459E+09 0.594998E+09 180843.02 37691552.89 29835316.31 0.419337E+10 0.374067E+10 6592.67 0.42
Minimum of Months 19823111.96 0.00 0.00 108108.91 0.00 60495.72 37758386.90 0.00 0.41
Maximum of Months 58632450.45 0.209709E+09 59105.08 7137824.23 11306375.16 0.127285E+10 0.664558E+09 2551.98 0.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM420_423

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.238764E+09 0.00 0.00 610147.63 0.00 0.482103E+10 0.720676E+09 0.00 0.41
February 0.212127E+09 0.00 0.00 2116853.71 0.00 0.304634E+10 0.141972E+10 0.00 0.41
March 0.228615E+09 0.00 0.00 7101794.48 0.00 0.141200E+10 0.245405E+10 0.00 0.41
April 0.181076E+09 53394201.50 0.00 13796705.98 1318935.15 0.485694E+09 0.226396E+10 550.45 0.42
May 0.167347E+09 55834686.62 192450.98 26343587.81 4880879.43 3428961.16 0.142468E+10 11499.92 0.43
June 96940905.86 0.509607E+09 272088.12 18827163.69 18105178.40 1913628.57 0.609329E+09 17206.80 0.43
July 98887155.68 0.702575E+09 357889.86 16865688.10 38055962.22 439490.44 0.197550E+09 21846.32 0.43
August 0.132389E+09 0.541545E+09 444586.18 20908471.64 34983887.42 458966.62 0.349389E+09 17920.11 0.43
September 0.159074E+09 0.120382E+09 103567.98 21119129.02 2441383.55 31214021.19 0.133602E+10 3360.11 0.42
October 0.162597E+09 0.00 0.00 11981695.16 0.00 0.251022E+09 0.266308E+10 0.00 0.41
November 0.203065E+09 0.00 0.00 5058007.13 0.00 0.186014E+10 0.188710E+10 0.00 0.41
December 0.235865E+09 0.00 0.00 938085.22 0.00 0.378174E+10 0.115600E+10 0.00 0.41
                   
Annual Sum or Average 0.211675E+10 0.198334E+10 1370583.11 0.145667E+09 99786226.17 0.156954E+11 0.164816E+11 72383.71 0.42
Minimum of Months 96940905.86 0.00 0.00 610147.63 0.00 439490.44 0.197550E+09 0.00 0.41
Maximum of Months 0.238764E+09 0.702575E+09 444586.18 26343587.81 38055962.22 0.482103E+10 0.266308E+10 21846.32 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: GUESTROOM424

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 9173221.87 0.00 0.00 10037.98 0.00 0.145891E+10 1624620.79 0.00 0.42
February 28940257.97 0.00 0.00 51735.07 0.00 0.112518E+10 32933192.98 0.00 0.42
March 55593076.11 0.00 0.00 687486.65 0.00 0.774494E+09 0.204590E+09 0.00 0.41
April 50127188.45 14255657.68 23828.10 2429493.12 364185.71 0.334946E+09 0.355372E+09 80.09 0.42
May 45126615.27 15622279.66 18011.20 6028544.63 1326090.30 15202903.86 0.328620E+09 1104.16 0.42
June 24538414.51 0.144214E+09 33496.81 4368458.28 5418008.51 355993.18 0.143509E+09 619.31 0.43
July 23219770.94 0.199696E+09 82781.74 3738212.07 10930358.43 41254.47 39918453.74 2098.86 0.43
August 31551182.05 0.152361E+09 55169.53 4798341.49 9766423.59 111115.66 75123386.66 1431.40 0.43
September 43643537.95 35171658.96 46558.15 4770631.19 776844.39 37756419.50 0.293054E+09 2058.98 0.42
October 50570211.20 0.00 0.00 1862969.13 0.00 0.260365E+09 0.476344E+09 0.00 0.41
November 34765045.60 0.00 0.00 593122.12 0.00 0.801291E+09 0.165520E+09 0.00 0.41
December 13677279.30 0.00 0.00 16787.98 0.00 0.128823E+10 3527181.93 0.00 0.42
                   
Annual Sum or Average 0.410926E+09 0.561321E+09 259845.54 29355819.73 28581910.94 0.609688E+10 0.212014E+10 7392.79 0.42
Minimum of Months 9173221.87 0.00 0.00 10037.98 0.00 41254.47 1624620.79 0.00 0.41
Maximum of Months 55593076.11 0.199696E+09 82781.74 6028544.63 10930358.43 0.145891E+10 0.476344E+09 2098.86 0.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: FRONTSTAIRSFLR4

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:47:03

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.167778E+12 0.302123E+11 0.00 0.412325E+11 0.234938E+11
February 0.190798E+12 0.236688E+11 0.00 0.340235E+11 0.232392E+11
March 0.295064E+12 0.199129E+11 0.00 0.305487E+11 0.381506E+11
April 0.355333E+12 0.130835E+11 0.00 0.231716E+11 0.722869E+11
May 0.410607E+12 0.691565E+10 0.00 0.158423E+11 0.128990E+12
June 0.428741E+12 0.165731E+10 0.00 0.576113E+10 0.192297E+12
July 0.434313E+12 -603385258.4 0.00 0.993266E+09 0.227343E+12
August 0.381900E+12 0.565410E+09 0.00 0.340582E+10 0.211226E+12
September 0.272891E+12 0.615445E+10 0.00 0.136631E+11 0.142185E+12
October 0.201546E+12 0.129132E+11 0.00 0.247713E+11 0.686167E+11
November 0.120604E+12 0.194450E+11 0.00 0.305924E+11 0.417925E+11
December 0.937486E+11 0.258163E+11 0.00 0.381266E+11 0.237832E+11
           
Annual Sum or Average 0.335332E+13 0.159741E+12 0.00 0.262132E+12 0.119340E+13
Minimum of Months 0.937486E+11 -603385258.4 0.00 0.993266E+09 0.232392E+11
Maximum of Months 0.434313E+12 0.302123E+11 0.00 0.412325E+11 0.227343E+12